Chapter 5 FUNCTION CODES
Code Name Data setting range
(Transistor signal) [Y1]
Selecting function code data assigns the corresponding function to terminals [Y1] to [Y3], [Y5A/C], and [30A/B/C]
E21
E22
[Y2]
Setting the value of 1000s in parentheses ( ) shown below assigns a negative logic input to a terminal.
E24 (Relay contact signal)
E27
0 (1000): Inverter running
[30A/B/C]
3 (1003): Undervoltage detected
(Inverter stopped)
5 (1005): Inverter output limiting
6 (1006): Auto-restarting after momentary power failure
(FDT)
(LU)
(IOL)
7 (1007): Motor overload early warning
10 (1010): Inverter ready to run
11:
(IPF)
(OL)
(RDY)
Switch motor drive source between commercial power and inverter output
(For MC on commercial line) (SW88)
12:
(RUN)
(FAR)
13:
Switch motor drive source between commercial power and inverter output
(For secondary side) (SW52-2)
Switch motor drive source between commercial power and inverter output
(For primary side) (SW52-1)
15 (1015): Select AX terminal function
(For MC on primary side)
25 (1025): Cooling fan in operation
26 (1026): Auto-resetting
27 (1027): Universal DO
28 (1028): Heat sink overheat early warning
30 (1030): Service life alarm
33 (1033): Command loss detected
35 (1035): Inverter output on
36 (1036): Overload prevention control
37 (1037): Current detected
42 (1042): PID alarm
43 (1043): Under PID control
44 (1044): Motor stopping due to slow flowrate under PID control
(AX)
(FAN)
(TRY)
(U-DO)
(OH)
(LIFE)
(REF OFF)
(RUN2)
(OLP)
(ID)
(PID-ALM)
(PID-CTL)
45 (1045): Low output torque detected
54 (1054): Inverter in remote operation
55 (1055): Run command activated
56 (1056): Motor overheat detected (PTC)
59 (1059): Terminal [C1] wire break
60 (1060): Mount motor 1, inverter-driven
(PID-STP)
(U-TL)
(RMT)
(AX2)
(THM)
(C1OFF)
(M1_I)
61 (1061): Mount motor 1, commercial-power-driven (M1_L)
62 (1062): Mount motor 2, inverter-driven (M2_I)
63 (1063): Mount motor 2, commercial-power-driven (M2_L)
64 (1064): Mount motor 3, inverter-driven (M3_I)
65 (1065): Mount motor 3, commercial-power-driven (M3_L)
67 (1067): Mount motor 4, commercial-power-driven (M4_L)
68 (1068): Periodic switching early warning (MCHG)
69 (1069): Pump control limit signal (MLIM)
99 (1099): Alarm output (for any alarm) (ALM)
Increment
Unit
— —
Change when running
Data copying
Default setting
Refer to page:
N Y 0 5-52
— —
— —
— —
— —
N
N
Y
Y
1
2
N Y 15
(10)
*
1
N Y 99
* 1 Values in parentheses ( ) in the above table denote default settings for the EU version.
5-8
Code
E35
Name
E40 PID Display Coefficient
A
E41 PID Display Coefficient
B
0.0 to 120.0
(Timer) 0.01 to 600.00
*
1
Data setting range
E32 (Hysteresis
Warning 0: (Disable)
/Current Detection Current value of 1 to 150% of the inverter rated current
(Level)
-999 to 0.00 to 999
*
1
-999 to 0.00 to 999
*
1
0: Speed monitor (Select by E48.)
Increment
0.1
0.1
Unit
Change when running
Data copying
Hz
Default setting
Refer to page:
60.0
(50.0)
*
2
5-57-1
Hz
0.01
0.01
0.01
Y2 the motor rated current
5-58 s Y Y 10.00
—
0.01
—
— — Y Y 0
*
10: PID process command (Final)
12: PID feedback value
14: PID output
15: Load factor
16: Motor output
17: Analog input
0: Running status, rotational direction and operation
1: Bar charts for output frequency, current and calculated torque
— —
— —
1: English
2: German
3: French
4: Spanish
5: Italian
E47 (Contrast 1 —
— —
4: Load shaft speed in r/min
7: Display speed in %
0.01 to 200.00
*
1
0.01
—
Indication
Y Y 0
Y Y 1
Y Y 5
Y Y 0
Input Watt-hour Data
0.000: (Cancel/reset)
0.001 to 9999
0.001
—
E52 Keypad
(Menu display mode)
0: Function code data editing mode (Menus #0, #1 and #7)
1: Function code data check mode (Menus #2 and #7)
2: Full-menu mode (Menus #0 through #7)
— — Y Y 0 —
The shaded function codes ( ) are applicable to the quick setup.
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*
2
Values in parentheses ( ) in the above table denote default settings for the EU version.
*
3
LCD monitor settings are applicable only to the inverter equipped with a multi-function keypad.
5-9
Code Name
H80 Gain for Suppression of
Output Current Fluctuation for Motor
0.00 to 0.40
*
0 to 2
Data setting range
Increment
0.01
Unit
—
Change when running
Data copying
Default setting
Refer to page:
Y Y
*
3
Depend ing on the inverter capacity
—
1 — Y Y1
Y2
*
4
Depend ing on the inverter capacity
*
*
*
*
Break Detection
H92 Continue to Run
25.0 to 120.0
0 to 3, 999
0, 1
0, 1
0.0: Disable alarm detection
0.1 to 60.0 s: Wire break detection time
0.000 to 10.000. 999
*
1
0.1
Hz
1 —
— —
— —
0.1
0.001 Times
Y N 0
Y Y 0
Y Y 0
—
Y2
*
1
0.001
H94 Cumulative Run Time of
Motor
Change or reset the cumulative data
(Braking response mode)
0: Slow
1: Quick
H96 STOP Key Priority/
Start Check Function
Data STOP key priority
0: Disable
Start check function
Disable
H97 Clear Alarm Data
1: Enable
2: Disable
Disable
Enable
3: Enable Enable
Setting H97 data to "1" clears alarm data and then returns to zero.
— —
— —
— —
— —
Y2
N N — 5-74
Y Y 1 5-40
Y Y 0 —
Y N 0 5-75
H98 Protection/
Maintenance Function
0 to 63: Display data on the keypad's LED monitor in decimal format (In each bit, "0" for disabled, "1" for enabled.)
Bit 0: Lower the carrier frequency automatically
Bit 1: Detect input phase loss
Bit 2: Detect output phase loss
Bit 3: Select life judgment criteria of DC link bus capacitor
Bit 4: Judge the life of DC link bus capacitor
Bit 5: Detect DC fan lock
— — Y Y 19
(Bits 4,
1, 0 = 1
Bits 5, 3,
2 = 0)
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*
2
The H86 through H91 are displayed, but they are reserved for particular manufacturers. Unless otherwise specified, do not access these function codes.
*
3
Select 0.10 for models of 45 kW or above (200 V series) and 55 kW or above (400 V series), 0.20 for models of 37 kW or below (200 V series) and 45 kW or below (400 V series).
*
4
Select 2 for models of 45 kW or above (200 V series) and 55 kW or above (400 V series), 0 for models of 37 kW or below (200 V series) and 45 kW or below (400 V series).
5-16
The table below lists functions that can be assigned to terminals [Y1], [Y2], [Y3], [Y5A/C], and
[30A/B/C].
To make the explanations simpler, the examples shown below are all written for the normal logic
(Active ON.)
Function code data
Active ON Active OFF
0
1
2
1001
Functions assigned
Frequency arrival signal
11 -
Symbol
(RUN)
(FAR)
(FDT)
(LU)
(IOL)
(IPF)
(OL)
(RDY)
(SW88)
12
13
-
-
Switch motor drive source between commercial power and inverter output (For MC on commercial line)
Switch motor drive source between commercial power and inverter output (For secondary side)
Switch motor drive source between commercial power and inverter output (For primary side)
(SW52-2)
(SW52-1)
(AX)
(FAN)
35
36
37
42
45
65
67
68
69
1045
1065
1067
1068
1069
Low output torque detected
Mount motor 3, commercial-power-driven
Mount motor 4, commercial-power-driven
Periodic switching early warning
Pump control limit signal
(U-DO)
(OH)
(LIFE)
(REF OFF)
(RUN2)
(OLP)
(ID)
(PID-ALM)
(PID-CTL)
(PID-STP)
(U-TL)
(RMT)
(AX2)
(THM)
(C1OFF)
(M1_I)
(M1_L)
(M2_I)
(M2_L)
(M3_I)
(M3_L)
(M4_L)
(MCHG)
(MLIM)
(ALM)
A mark "-" in the Active OFF column means that a negative logic cannot be applied to the terminal function.
5-53
Inverter running -- (RUN)
(Function code data = 0)
This output signal is used to tell the external equipment that the inverter is running at a starting frequency or higher. It comes ON when the output frequency exceeds the starting frequency, and it goes OFF when it is less than the stop frequency. It is also OFF when the DC braking is in operation.
If this signal is assigned in negative logic (Active OFF), it can be used as a signal indicating
"inverter being stopped."
Frequency arrival signal -- (FAR)
(Function code data = 1)
This output signal comes ON when the difference between the output frequency and reference frequency comes within the allowable error zone. (prefixed to 2.5 Hz).
Frequency detected -- (FDT)
(Function code data = 2)
This output signal comes ON when the output frequency exceeds the frequency detection level specified by function code E31, and it goes OFF when the output frequency drops below the
"Detection level (E31) - Hysteresis width (E32)."
Undervoltage detected -- (LU)
(Function code data = 3)
This output signal comes ON when the DC link bus voltage of the inverter drops below the specified undervoltage level, and it goes OFF when the voltage exceeds the level.
This signal is ON also when the undervoltage protective function is activated so that the motor is in an abnormal stop state (e.g., tripped).
When this signal is ON, a run command is disabled if given.
Inverter output limiting -- (IOL)
(Function code data = 5)
This output signal comes ON when the inverter is limiting the output frequency by activating any of the following actions (minimum width of the output signal: 100 ms).
• Current limiting by software (F43 and F44: Current limiter (Mode selection) and (Level))
• Instantaneous overcurrent limiting by hardware (H12 = 1)
• Automatic deceleration (H69 = 3))
When the (IOL) signal is ON, it may mean that the output frequency may have deviated from (or dropped below) the frequency specified by the frequency command because of this limiting function.
Auto-restarting after momentary power failure -- (IPF)
(Function code data = 6)
This output signal is ON either during continuous running after a momentary power failure or during the period from when the inverter has detected an undervoltage condition and shut down the output until restart has been completed (the output has reached the reference frequency).
To enable this (IPF) signal, set F14 (Restart mode after momentary power failure) to "3: Enable restart (Continue to run)," "4: Enable restart (Restart at the frequency at which the power failure occurred)," or "5: Enable restart (Restart at the starting frequency)" beforehand.
5-54
Inverter output on -- (RUN2)
(Function code data = 35)
This output signal comes ON when the inverter is running at the starting frequency or below or the
DC braking is in operation.
Overload prevention control -- (OLP)
(Function code data = 36)
This output signal comes ON when the overload prevention control is activated. The minimum
ON-duration is 100 ms.
For details of the overload prevention control, refer to the descriptions of function code H70.
Current detected -- (ID)
(Function code data = 37)
This output signal comes ON when the output current of the inverter exceeds the level specified by E34 (Current detection (Level)) for the time longer than the one specified by E35 (Current detection (Timer)). The minimum ON-duration is 100 ms.
This signal goes OFF when the output current drops below 90% of the rated operation level.
Function code E34 is effective for not only the motor overload early warning (OL), but also for the operation level of the current detection (ID).
For details of the current detection, refer to the descriptions of function codes E34 and E35.
Low output torque detected -- (U-TL)
(Function code data = 45)
This output signal comes ON when the torque value calculated by the inverter decreases below the level specified by E80 (Detect low torque (Detection level)) for the time longer than the one specified by E81 (Detect low torque (Timer)). The minimum ON-duration is 100 ms.
For details of the low output torque detection, refer to the description of function codes E80 and E81.
Inverter in remote operation -- (RMT)
(Function code data = 54)
This output signal comes ON when the inverter switches from local to remote mode.
For details about the remote and local modes, refer to Chapter 3, Section 3.3.3 "Switching between remote and local modes."
Terminal [C1] wire break -- (C1OFF)
(Function code data = 59)
This output signal comes ON when the inverter detects that the input current (after filtered with
C38) on analog input terminal [C1] drops below 2 mA, interpreting it as a terminal [C1] wire broken.
Alarm output (for any alarm) -- (ALM)
(Function code data = 99)
This output signal comes ON if any of the protective functions is activated and the inverter enters
Alarm mode.
5-57
E31, E32
Frequency Detection (Detection level and Hysteresis width)
If the output frequency exceeds the frequency detection level specified by E31, the FDT signal comes ON; if it drops below the "Frequency detection level (E31) minus hysteresis width (E32)," it goes OFF.
It is necessary to assign the signal (FDT) to one of the output terminals Y1 to Y3, Y5A/C, and
30A/B/C using any of E20 to E22, E24, and E27 (data = 2).
- Data setting range: 0.0 to 120.0 (Hz)
5-57-1
H69
H70
Automatic Deceleration
H69 specifies whether automatic deceleration control is to be enabled or disabled. During deceleration of the motor, if regenerative energy exceeds the level that can be handled by the inverter, overvoltage trip may happen. With automatic deceleration enabled, when the DC link bus voltage exceeds the level (internally fixed) for starting automatic deceleration, the output frequency is controlled to prevent the DC link bus voltage from rising further; thus regenerative energy is suppressed.
If automatic deceleration is enabled, deceleration may take a longer time. This is designed to limit the torque during deceleration, and is therefore of no use where there is a braking load.
Disable the automatic deceleration when a braking unit is connected. The automatic deceleration control may be activated at the same time when a braking unit starts operation, which may make the acceleration time fluctuate. In case the set deceleration time is so short, the DC link bus voltage of the inverter rises quickly, and consequently, the automatic deceleration may not follow the voltage rise. In such a case, prolong the deceleration time.
Even if the time period of 3 times of the deceleration time 1 (F08) has elapsed after the inverter entered automatic deceleration, there may be a case that the motor does not stop or the frequency dose not decrease. In this case, cancel the automatic deceleration forcibly for safety and decelerate the motor according to the set deceleration time.
Prolong the deceleration time also.
Overload Prevention Control
H70 specifies the rate of decreasing the output frequency to prevent an overload condition.
Under this control, an overload trip is prevented by decreasing the output frequency of the inverter before the inverter trips because of the overheating of the cooling fan or the overloading of the inverter (with an alarm indication of 0h1 or 0lu ). This control is useful for facilities such as pumps where a decrease in the output frequency leads to a decrease in the load and it is necessary to keep the motor running even when the output frequency goes low.
Data for H70
0.00
0.01 to 100.0
999
Function
Decelerate the motor by deceleration time 1 specified by F08
Decelerate the motor by deceleration rate 0.01 to 100.0 (Hz/s)
Disable overload prevention control
In applications where a decrease in the output frequency does not lead to a decrease in the load, this function is of no use and should not be enabled.
5-74
H91
H94
PID Feedback Wire Break Detection
Using the analog input terminal [C1] (current input) for feedback signals under PID control (E62 =
5) enables wire break detection and alarm ( cof
) issuance. H91 specifies whether to enable the wire break detection or the duration of less than 2 mA on the terminal [C1]*.
If the inverter detects that the input current on [C1] is less than 2 mA (after filtered with C38) for the duration specified by H91, it interprets the state as a terminal [C1] wire break and issues an alarm ( cof
).
- Data setting range: 0.0 (Disable alarm detection)
0.1 to 60.0 s (If the current level is less than 2 mA for this duration, detect wire break and issue cof alarm.)
*It is also possible to assign the signal (C1OFF) to one of the output terminals Y1 to Y3, Y5A/C, and 30A/B/C using any of E20 to E22, E24, and E27 (data = 59). The C1OFF goes ON if the input current level (after filtered with C38) on [C1] drops below 2 mA, and it goes OFF if the current level rises to 2 mA or above.
Cumulative Run Time of Motor
You can view the cumulative run time of the motor on the keypad. This feature is useful for management and maintenance of the mechanical system. With this function code (H94), you can set the cumulative run time of the motor to any value you choose. For example, by specifying "0," you can clear the cumulative run time of the motor.
The data for H94 is in hexadecimal notation. Check the cumulative run time of the motor on the keypad.
5-74-1