BAUD RATE SETTING. WattMaster VAV CommLink 5 Communications Interface
Anuncio
Anuncio
COMMUNICATION SETTINGS
Baud Rate Setting
Setting the CommLink 5 Baud Rate
Back of CommLink 5
SERIAL #
LOOP BAUD
BAUD
Switch Set To High Baud
Rate (115,200)
CommLink 5 Baud Rate Setting
The Baud Rate Switch Located On The Back Of
The CommLink 5 Housing Must Be Set Correctly
For Your Specific Application In Order For The
CommLink 5 To Function At Maximum Efficiency.
The CommLink 5 Is Factory Set For Low Baud
Rate Applications.
The Baud Rate Should Be Set To “High” In The
Following Situations:
You Are Using Only AZ 2 Controllers, Only
GPC-XP Controllers (Set To High Speed),
Only VCC-X Controllers, or Only VCB-X
Controllers (Set To High Speed) On Your
System or a Combination of These
Controllers Set to High Speed (If Applicable).
The Baud Rate Should Be Set To “Low” In The
Following Situations:
You Are Using Orion Controllers In Combination
With VCB-X or GPC-XP Controllers. For Example,
VCB-X or GPC-XP Controllers With VCM-X or
VCM Controllers. In This Application, The VCB-X
Controller and GPC-XP Controller Must Also Be
Set To Low Speed.
NOTE: Refer To Each Individual Controller’s
Technical Guide On How To Set The Baud Rate
For That Controller.
BAUD
Switch Set To Low Baud
Rate (Anything Less Than
115,200)
Figure 3: Setting the Baud Rate
CommLink 5 Technical Guide
7