Empire Comfort Systems DVP42FP3(0,1,2,3)(N,P)


Add to my manuals
56 Pages

advertisement

Empire Comfort Systems DVP42FP3(0,1,2,3)(N,P) | Manualzz

INSTALLATION INSTRUCTIONS

AND

OWNER’S MANUAL

The Tahoe Direct Vent Zero Clearance

Gas Fireplace Heater

DIRECT VENT

GAS FIREPLACE HEATER

MODEL SERIES

MILLIVOLT STANDING PILOT

DVP42FP3(0,1,2,3)(N,P)-1

DVP48FP3(0,1,2,3)(N,P)-1

INTERMITTENT PILOT

DVP42FP7(0,1,2,3)(N,P)-1

DVP48FP7(0,1,2,3)(N,P)-1

REMOTE RF MODELS

DVP42FP9(1,3)(N,P)-1

DVP48FP9(1,3)(N,P)-1

GAS-FIRED

Installer: Leave these instructions with the consumer.

Consumer: Retain these instructions for future use.

Warning: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

- WHAT TO DO IF YOU SMELL GAS

● Do not try to light any appliance.

● Do not touch any electrical switch; do not use any phone in your building.

● Immediately call your gas supplier from a neighbors phone. Follow the gas supplier's instructions.

● If you cannot reach your gas supplier, call the fire department.

- Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

17375-10-0706

EFFECTIVE DATE

JULY 2006

UL FILE NO. MH30033

This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by state or local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

WARNING: If not installed, operated and maintained in accordance with the manufacturer’s instructions, this product could expose you to substances in fuel or from fuel combustion which can cause death or serious illness.

Page 1

MAIN TITLE

Section Page

Important Safety Information ......................................................................................................... 3

Safety Information for Users of LP Gas ......................................................................................... 4

Requirements for Massachusetts .................................................................................................... 5

Introduction ................................................................................................................................... 6

Specifications ................................................................................................................................. 7

Fireplace Dimensions ..................................................................................................................... 7

Clearances ...................................................................................................................................... 8

Locating Fireplace .......................................................................................................................... 8

Gas Supply ..................................................................................................................................... 9

Rear Vent Conversion/Vent Systems ............................................................................................ 10

Installation ..............................................................................................................................11-14

Venting Fireplace-Top Vent .....................................................................................................15-18

Venting Fireplace-Rear Vent ...................................................................................................19-20

Termination Clearances ................................................................................................................ 21

Vent Clearances ............................................................................................................................ 22

Vent System Identification ........................................................................................................... 23

Framing and Finishing ............................................................................................................24-25

Horizontal Termination ................................................................................................................ 25

DVVK-5F Flex Vent .................................................................................................................... 26

Vertical Termination ...............................................................................................................27-28

Log Placement ............................................................................................................................. 29

Operating Instructions .............................................................................................................30-31

Wiring Diagram-Standing Pilot .................................................................................................... 32

Lighting Instructions-Standing Pilot ............................................................................................ 33

Troubleshooting-Standing Pilot ................................................................................................... 34

Intermittent Pilot Operating Instructions ...................................................................................... 35

Intermittent Pilot Wiring Instructions .......................................................................................... 35

Intermittent Pilot Lighting Instruction ......................................................................................... 36

Intermittent Pilot Troubleshooting ..........................................................................................37-40

RF Standing Pilot Operating Instructions .................................................................................... 41

RF Transmitter Functions ............................................................................................................. 42

RF Wiring Diagram ...................................................................................................................... 43

RF Standing Pilot Lighting Instructions ....................................................................................... 44

Maintenance and Service ............................................................................................................. 45

Parts View .................................................................................................................................... 46

Parts List ..................................................................................................................................47-48

FBB4 Optional Variable Speed Blower Installation ...............................................................49-50

Junction Box Wiring Installation Instruction ............................................................................... 51

Optional Brick Liner Installation Instruction ............................................................................... 51

Accessories ................................................................................................................................... 52

How To Order Repair Parts .......................................................................................................... 53

Service Notes ...........................................................................................................................53-56

Page 2 17375-10-0706

IMPORTANT SAFETY INFORMATION

Before enclosing the vent pipe assembly, operate the appliance to ensure it is venting properly.

DO NOT OPERATE THIS APPLIANCE WITHOUT GLASS FRONT PANEL INSTALLED

• If this appliance is installed directly on carpeting, tile or other combustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance.

The base referred to above does not mean the fireproof base as used on wood stoves. The protection is for rugs that are extremely thick and light colored tile.

• Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition.

• Young children should be carefully supervised when they are in the same room as the appliance.

• Clothing or other flammable material should not be placed on or near the appliance.

• Adequate accessibility clearances for servicing and proper operation.

• This appliance must not share or be connected to a flue serving a separate solid-fuel burning appliance.

• Keep the area around your appliance clear of combustible materials, gasoline and other flammable vapor and liquids.

• Under no circumstances should any solid fuels (wood, coal, paper or cardboard etc.) be used in this appliance.

• The flow of combustion and ventilation air must not be obstructed in any way.

• Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies.

• The glass front or any part removed for servicing the appliance must be replaced prior to operating the appliance. Work should be done by a qualified service person.

• Keep burner and control compartment clean.

• Vent cap is hot while fireplace is in operation.

• Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding materials, etc. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean.

• Do not put anything around the fireplace that will obstruct the flow of ventilation air.

• Clearance in accordance with local installation codes and the requirements of the gas supplier.

• Do keep the appliance area clear and free from combustible material, gasoline and other flammable vapors and liquids.

• Do examine venting system periodically and replace damaged parts.

• Do make a periodic visual check of pilot and burners. Clean and replace damaged parts.

• CAUTION: The glass used in your fireplace is tempered glass.

If the glass is cracked or damaged in any way, it should be replaced only with a complete glass frame assembly from

Empire. See parts list on Pages 47 and 48 for ordering.

• Do not use this fireplace if any part has been under water.

Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.

• Any safety screen or guard removed for servicing an appliance must be replaced prior to operating the appliance.

17375-10-0706 Page 3

SAFETY INFORMATION FOR USERS OF LP GAS

Propane (LP-Gas) is a flammable gas which can cause fires and explosions. In its natural state, propane is odorless and colorless. You may not know all the following safety precautions which can protect both you and your family from an accident. Read them carefully now, then review them point by point with the members of your household. Someday when there may not be a minute to lose, everyone’s safety will depend on knowing exactly what to do. If, after reading the following information, you feel you still need more information, please contact your gas supplier.

LP-GAS WARNING ODOR

If a gas leak happens, you should be able to smell the gas because of the odorant put in the LP-Gas.

That’s your signal to go into immediate action!

• Do not operate electric switches, light matches, use your phone.

Do not do anything that could ignite the gas.

• Get everyone out of the building, vehicle, trailer, or area. Do that IMMEDIATELY.

• Close all gas tank or cylinder supply valves.

• LP-Gas is heavier than air and may settle in low areas such as basements. When you have reason to suspect a gas leak, keep out of basements and other low areas. Stay out until firefighters declare them to be safe.

• Use your neighbor’s phone and call a trained LP-Gas service person and the fire department. Even though you may not continue to smell gas, do not turn on the gas again. Do not re-enter the building, vehicle, trailer, or area.

Finally, let the service man and firefighters check for escaped gas. Have them air out the area before you return. Properly trained LP-Gas service people should repair the leak, then check and relight the gas appliance for you.

NO ODOR DETECTED - ODOR FADE

Some people cannot smell well. Some people cannot smell the odor of the chemical put into the gas. You must find out if you

can smell the odorant in propane. Smoking can decrease your ability to smell. Being around an odor for a time can affect your sensitivity or ability to detect that odor. Sometimes other odors in the area mask the gas odor. People may not smell the gas odor or their minds are on something else. Thinking about smelling a gas odor can make it easier to smell.

The odorant in LP-Gas is colorless, and it can fade under some

circumstances. For example, if there is an underground leak, the movement of the gas through soil can filter the odorant. Odorants in LP-Gas also are subject to oxidation. This fading can occur if there is rust inside the storage tank or in iron gas pipes.

The odorant in escaped gas can adsorb or absorb onto or into walls, masonry and other materials and fabrics in a room. That will take some of the odorant out of the gas, reducing its odor intensity.

LP-Gas may stratify in a closed area, and the odor intensity could vary at different levels. Since it is heavier than air, there may be more odor at lower levels. Always be sensitive to the slightest gas odor. If you detect any odor, treat it as a serious leak. Immediately go into action as instructed earlier.

SOME POINTS TO REMEMBER

• Learn to recognize the odor of LP-Gas. Your local LP-Gas

Dealer can give you a “Scratch and Sniff” pamphlet. Use it to find out what the propane odor smells like. If you suspect that your LP-Gas has a weak or abnormal odor, call your LP-Gas

Dealer.

• If you are not qualified, do not light pilot lights, perform service, or make adjustments to appliances on the LP-Gas system. If you are qualified, consciously think about the odor of LP-Gas prior to and while lighting pilot lights or performing service or making adjustments.

• Sometimes a basement or a closed-up house has a musty smell that can cover up the LP-Gas odor. Do not try to light pilot lights, perform service, or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP-Gas.

• Odor fade, due to oxidation by rust or adsorption on walls of new cylinders and tanks, is possible. Therefore, people should be particularly alert and careful when new tanks or cylinders are placed in service. Odor fade can occur in new tanks, or reinstalled old tanks, if they are filled and allowed to set too long before refilling. Cylinders and tanks which have been out of service for a time may develop internal rust which will cause odor fade. If such conditions are suspected to exist, a periodic sniff test of the gas is advisable. If you have any

question about the gas odor, call your LP-Gas dealer. A periodic sniff test of the LP-Gas is a good safety measure under any condition.

• If, at any time, you do not smell the LP-Gas odorant and you think you should, assume you have a leak. Then take the same immediate action recommended above for the occasion when you do detect the odorized LP-Gas.

• If you experience a complete “gas out,” (the container is under no vapor pressure), turn the tank valve off immediately. If the container valve is left on, the container may draw in some air through openings such as pilot light orifices. If this occurs, some new internal rusting could occur. If the valve is left open, then treat the container as a new tank. Always be sure your container is under vapor pressure by turning it off at the container before it goes completely empty or having it refilled before it is completely empty.

Page 4 17375-10-0706

REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the

Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and IAS certified.

3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled

“Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the

Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(d) MANUFACTURER REQUIREMENTS - GAS

EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies

“special venting systems”, the following requirements shall be satisfied by the manufacturer:

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2. The “special venting systems” shall be Product

Approved by the Board, and the instructions for that system shal include a parts list and detailed installation instruction.

(e) A copy of all installation instructions for all Product

Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

17375-10-0706 Page 5

Instructions to Installer

1. Installer must leave instruction manual with owner after installation.

2. Installer must have owner fill out and mail warranty card supplied with the fireplace.

3. Installer should show owner how to start and operate the fireplace.

This direct vent gas fireplace heater is designed to operate with all combustion air being siphoned from the outside of the building and all exhaust gases expelled to the outside of the building. The information contained in this manual pertains to all models and gas control systems unless otherwise noted.

Warning: This unit is not for use with solid fuels.

Appliance Certification

This fireplace is design certified in accordance with American

National Standard/CSA Standard ANSI Z.21-88/CSA 2.33 and by

Underwriters Laboratories as a Direct Vent Gas Fireplace Heater and shall be installed according to these instructions.

Consult your local building code agency, prior to installation, to ensure compliance with local codes-including permits and inspections.

The fireplace, when installed, must be electrically grounded in accordance with local codes or, in absence of local codes, with the

National Electric Code ANSI/NFPA 70 or Canadian Electric code,

CSA C22.1, if an external electrical source is utilized.

These models may be installed in a bedroom or bed-sitting room in the U.S.A. and Canada.

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment or accessories and repair and servicing of equipment shall be performed only by a qualified agency. The term “qualified agency” means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation or replacement of gas piping or (b) the connection, installation, repair or servicing of equipment, who is experienced in such work, familiar with all precautions required and has complied with all the requirements of the authority having jurisdiction.

State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of

Massachusetts.

The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA

54* Natural Gas and Propane Installation Code, or CSA B149.1

in Canada.

*Available from the American National Standards Institute, Inc. 11 West 42nd

St., New York, N.Y. 10036.

Warning: ANY CHANGE TO THIS FIREPLACE OR ITS

CONTROLS CAN BE DANGEROUS.

Improper installation or use of the fireplace can cause serious injury or death from fire, burns, explosions, or carbon monoxide poisoning.

INTRODUCTION

Any alteration of the original design, installed other than as shown in these instructions or use with a type of gas not shown on the rating plate is the responsibility of the person and company making the change.

Important

All correspondence should refer to complete Model Number, Serial

Number and type of gas.

High Altitude

When installing this unit at an elevation above 2000 feet (in the

United States) it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size. Generally, input should be reduced 4 percent for each 1000 feet above sea level. However, if the heating value of the gas has been reduced, this general rule may not apply. Check with local gas utility for proper orifice size identification.

Canadian High Altitude

Altitude: 0-4500 feet (0-1370 m)

When installing this unit at an elevation above 4500 feet (in Canada), check with local authorities.

Consult your local gas utility for assistance in determining the proper orifice for location.

Preparation

This direct vent gas fireplace and its components are tested and safe when installed in accordance with this Installation Manual. Report to your dealer any parts damaged in shipment, specifically check glass condition. Do not install unit with damaged, incomplete, or substitute parts. Read all instructions before starting installation and follow these instructions carefully during installation to insure maximum benefit and safety. Failure to follow them will void your warranty and may present a fire hazard.

The warranty will be voided by, and the warranter disclaims any responsibility for the following actions:

• Installation of any damaged fireplace or vent system component.

• Modification of the fireplace or direct vent system.

• Installation other than as instructed by Empire Comfort Systems,

Inc.

• Improper positioning of the logs, glass door or decorative rock.

• Installation and/or use of any component part not manufactured or approved by manufacturer.

Page 6 17375-10-0706

Input Btu/hr Maximum

Btu/hr Minimum (millivolt only)

KWH (Maximum)

(Minimum)

NAT.

Orifice

Air Shutter Opening

LP

Orifice

Air Shutter Opening

Height without standoff

Width

Depth

Gas Inlet Shutoff Valve (Pipe)

SPECIFICATIONS

DVP42

28,000

19,000

8.2

5.5

DVP48

30,000

20,500

8.8

6.0

#38 (.1015)

P-203

1/8"(3.2mm)

#37 (.1040) P-213

1/8"(3.2mm)

#52 (.0635")

P-213

1.65MM

P-250

FULL OPEN FULL OPEN

34 3/4"(3.2mm) 34 3/4"(3.2mm)

43"(1092mm) 49"(1245mm)

19 7/8"(505mm) 19 7/8"(505mm)

1/2 NPT 1/2 NPT

NOTE: Air shutter settings are factory minimum settings.

Some venting configurations may require minor air shutter adjustments for optimum performance.

Venting Options

DVVK-5TS

DVVK-5T

DVVK-5R

DVVK-5V

DVVK-5F

Description

TOP VENT KIT (HORZ.) - 4½" to 6" wall thickness (114.3mm to 152mm) top vent kit (horz.) - 8" to 12" wall thickness

(203mm to 305mm) rear vent kit (horz.) - 5" to 7" wall thickness

(203mm to 305mm)

VERTICAL vent kit

HORIZONTAL FLEX VENT KIT (4' FLEX)

(1.22M)

17375-10-0706

Remote Control Options &

Accessories

FRBC

FRBTC

TMW

TRW

FWS-1

Description

Millivolt Batt. Remote ON/OFF

Millivolt Batt. Remote T-Stat

Millivolt WIRELESS Wall Thermostat

Millivolt REED SWITCH Wall Thermostat

Direct Ignition/Millivolt Wall Switch

FIREPLACE DIMENSIONS

RIGHT SIDE VIEW

H

J

K

DVP42

A 43"

1092mm

B 40"

1016mm

C 25 1/16"

636 mm

D 37 5/8"

956 mm

E 34 3/4"

883 mm

F 19 7/8"

505 mm

G 26"

660 mm

H 7 1/8"

181 mm

I 26 1/2"

826 mm

J 13 1/4"

337 mm

K 12 3/4"

324 mm

Figure 1

19 7/8"

505 mm

26"

660 mm

7 1/8"

181 mm

32 1/2"

826 mm

16 1/4"

413 mm

12 3/4"

324 mm

DVP48

49"

1245mm

46"

1168mm

25 1/16"

636 mm

37 5/8"

956 mm

34 3/4"

883 mm

Page 7

Clearance to Combustibles

Back

Side

Floor

Top Stand-off

0" (0 mm)

0" (0 mm)

0" (0 mm)

0" (0 mm)

Top Framing Edge 3" (76 mm)

SEE MANTLE CHART FOR

MAXIMUM MANTLE DEPTH

SEE MANTLE CHART

FOR MINIMUM HEIGHT

OF MANTLE ABOVE UNIT

2" x 4" HEADER

STAND OFF

3" (76 mm) HEIGHT

ABOVE TOP OF

FIREPLACE

CLEARANCES

Mantel Chart (Figure 3)

12” (305mm)

10” (254mm)

MANTEL

8”

15”

(381mm)

6”

13 3/4”

4 ½”

3 3/4”

3”

11”

9”

8”

7”

6”

5”

4”

3”

TOP EDGE OF FIREPLACE

FINISHED WALL

(COMBUSTIBLE)

NON-COMBUSTIBLE

FIRST 3 (SEE MAGNIFIED

VIEW)

NAILING

FLANGES

3"

COMBUSTIBLE TRIM AND MANTELS

ALLOWED IN SHADED AREA

2 1/4”

1 ½”

3/4”

Figure 3

Clearances (Figure 4)

Clearance from top front edge of fireplace to ceiling is 36"

Clearance from side of fireplace to adjacent sidewall is 6".

TOP FRAMING

LEDGE

GLASS FRONT

(914mm)

Figure 2

Combustible Material

No greeting cards, stockings or ornamentation of any type should be placed on or attached to the fireplace. The flow of heat can ignite combustibles.

LOCATING FIREPLACE

Figure 4

Note: Island (C) and Room Divider

(D) installation is possible as long as the horizontal portion of the vent system (H) does not exceed

20 feet with a minimum vertical run of 8 feet. See details in Venting

Section.

When you install your Direct Vent

Fireplace in (D) Room divider or

(E) Flat on wall corner positions, a minimum of 6 inches clearance must be maintained from the perpendicular wall and the front edge of the appliance.

Page 8

CORNER

INSTALLATION

ANGLED CORNER

INSTALLATION

ISLAND

INSTALLATION

CABINET

INSTALLATION

ROOM DIVIDER

INSTALLATION

FLUSH WALL

INSTALLATION

Figure 5

17375-10-0706

The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI

Z223.1 CAN/CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length Schedule 40 Pipe

Inside Diameter

Nat.

L.P.

0-10ft

0-3m

11-40ft

4-12m

1/2"

12.7mm

1/2"

12.7mm

3/8"

9.5mm

1/2"

12.7mm

Tubing, Type L

Outside Diameter

Nat.

1/2"

12.7mm

5/8"

15.9mm

L.P.

3/8"

9.5mm

1/2"

12.7mm

41-100ft

13-30m

101-150ft

31-46m

1/2"

12.7mm

3/4"

19mm

1/2"

12.7mm

1/2"

12.7mm

3/4"

19mm

7/8"

22.2mm

1/2"

12.7mm

3/4"

1.9 mm

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings.

— ANS Z21.45 Assembled Flexible Appliance Connectors of

Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

Natural Gas

LP (Propane)

Figure 6

Gas Supply Pressure (inches w.c.)

Minimum Normal

4.5"

10.8"

7.0"

11.0"

Maximum

*14.0"

*14.0"

GAS SUPPLY

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

NOTE: The millivolt gas controls are equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.

On direct ignition valves, hex plugs may be replaced with hose fittings for pressure checks, then reinstalled before operating fireplace.

When using copper or flex connector use only approved fittings.

The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).

Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition.

Checking Manifold Pressures

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c.

(1.120kPa) for the purpose of input adjustment to a maximum of

14.0" w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 10.8" w.c. (2.68kPa) for the purpose of input adjustment to a maximum of 14.0" w.c. (3.484kPa).

Manifold Pressure (inches w.c.)

Natural Gas

Normal (HI)

3.5"

LP (Propane) 10.0"

*NOTE: Remote "RF" Models - 10.5" w.c. maximum

Figure 7

17375-10-0706 Page 9

REAR VENT CONVERSION

Note: It is recommended that the flue cover plate tab be pulled outward prior to removal.

VERTICAL VENTING

Note: Discard insulation

& retainer when venting off top of fireplace.

Note: Discard insulation

& retainer when using vertical venting off

INLET VENT COLLAR

HORIZONTAL VENTING

INLET VENT

COVER PLATE

FLUE COVER PLATE

This will ensure that the plate is not accidentally dropped inside the rear air chamber.

FLUE OUTLET

COLLAR

FLUE INSULATION

INSULATION

RETAINER

FLUE COVER PLATE

(See note above)

INLET VENT

COVER PLATE

Converting flue take-off to rear venting

When switching out the flue and inlet vent collars to run horizontally off the rear vent, the following steps must be taken.

1. Remove the inlet vent collar (8 screws) and flue collar (4 screws) from the top of the fireplace, and set to the side.

2. Remove the inlet cover plate and flue cover plate located on the back of the fireplace. These will be used to close the top flue and inlet openings.

3. Insert the insulation retainer bracket and insulation into the top

INLET VENT COLLAR flue pipe before reinstalling the flue cover plate over the top flue with 4 screws.

4. Reinstall the inlet cover plate over the top inlet opening with 4 screws. See illustration above..

5. Install the flue collar assembly to the rear flue with 4 screws.

6. Install the inlet vent collar to the rear of the fireplace with 8 screws.

7. This completes the conversion for a rear vent application.

Note: for top vented installations, the insulation and retainer are to be removed from the flue pipe and discarded.

VENT SYSTEMS

The following vent systems are acceptable for use with the

DVP (42,48) series fireplaces:

Simpson Duravent® GS 5" - 8", Refer to Page 23

*American Metal Products 5" - 8"

*Selkirk Direct-Temp® 5" - 8"

*Security Secure Vent® 5" - 8"

Empire Flexvent Kit DVVK-5F, Refer to Page 26

* Can not be used in side wall horizontal vent installations in the State of Massachusetts.

Page 10 17375-10-0706

INSTALLATION

Framing and Finishing

1. Choose unit location.

2. Frame in fireplace with a header across the top. It is important to allow for finished face when setting the depth of the frame.

3. Attach fireplace to frame using adjustable frame. Preset depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths).

4. Use (8) 1/2" hex-head screws supplied in hardware package, to screw through slotted holes in drywall strip and then screw into pre-drilled holes on fireplace side. Measure from face of fireplace to face of drywall strip to determine final depth.

Vent Pipe Clearance

Note: Maintain one inch (1") of clearance around vertical vent pipe. See Fig. 9A. For horizontal vent, maintain a minimum 1" clearance to the bottom and sides of the vent, and 3" clearance to combustibles above the vent pipe. See Fig. 9B

Figure 8

VENT PIPE

Top of Vent

3"

(76 mm)

1"

(25 mm)

17375-10-0706

Figure 9B

Combustibles NOT allowed in shaded area

5” Diameter flue

8” Diameter intake vent

1" MINIMUM CLEARANCE AROUND VENT PIPE

Figure 9A

1"

(25 mm)

Page 11

INSTALLATION (continued)

Flush Mount Mantel Installation (Figure 10)

The fireplace must extend 3/4" beyond finished wall surface when using a flush mount mantel. Refer to Figure 10 to locate nailing flanges on fireplace sides. Mark and drill two (2) 1/8" holes into fireplace side to mount each nailing flange. Use eight (8) 1/2" hex-head screws supplied in hardware package to attach nailing flanges to fireplace sides.

NAIL OR OTHER SUITABLE FASTENER

Figure 10

Framing (Figure 11)

Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommodate wall covering and fireplace facing material. The fireplace framing should be constructed of 2 x 4 lumber or heavier. The framing headers may rest on the fireplace standoffs. Refer to Figure 11 for minimum framing dimensions.

CAUTION: MEASURE FIREPLACE DIMENSIONS AND

VERIFY FRAMING METHODS, AND WALL COVERING

DETAILS BEFORE FRAMING CONSTRUCTION

BEGINS.

Framing dimension "A" includes a three inch clearance for standoffs on firebox. After installing firebox into framing, the finished wall surface must cover the three inch opening above the firebox.

DVP42 DVP48

"A" 37 3/4" 37 3/4"

"B" 43 3/8" 49 3/8"

"C" 19 7/8" 19 7/8"

Figure 11

Attention: If a base or mantel is not used and the appliance is installed directly on carpeting, tile or other combustible material other than wood flooring, it shall be installed on a metal or wood panel extending the full width and depth of the appliance. The vertical dimension in Figure 11 must be adjusted when a metal or wood panel is placed beneath the appliance.

Finishing (Figures 12 and 13)

Finish the walls with the material of your choice. Figure 3 on page 8 shows the minimum vertical and corresponding maximum horizontal dimensions of mantels or other combustible projections above the top front edge of the fireplace.

Only non-combustible materials may be used to cover the black fireplace front.

Warning: When finishing the fireplace never obstruct or modify the air inlet/outlet louvers in any manner. Provide adequate clearances around air openings into the combustion chamber.

Caution: If the joints between the finished wall and the fireplace surround (top and sides) are sealed, a 300°F minimum sealant material must be used. These joints are not required to be sealed.

Only non-combustible material (using 300°F minimum adhesive if needed), can be applied as facing to the fireplace surround.

Page 12 17375-10-0706

Flush Wall Installation

FINISHED WALL

3! OF NON-COMBUSTIBLE MATERIAL

FRONT TRIM OR NON-

COMBUSTIBLE MA TERIAL

(INSTALLA TION IS OPTIONAL)

JOINT BETWEEN FINISHED

WALL AND UNIT SEALED

WITH 300° F, 149° C SEALANT

MATERIAL (SEALANT IS OPTIONAL)

Attention: Cold climate installation recommendation:

When installing this unit against a non-insulated exterior wall, it is recommended that the outer walls be insulated to conform to applicable insulation codes.

Vent Runs (Figures 14, 15, 16, 17 and 18)

In planning the installation for the fireplace, it is necessary to install certain components before the appliance is completely positioned and installed. These include the direct vent system, gas piping for the appliance and the electrical wiring. (If the fan option is used.)

The appliance can be mounted on any of the following surfaces:

1. A flat, hard combustible (burnable) surface.

2. A raised wooden platform.

3. Four (4) corner supports. (Example: Four (4) concrete masonry blocks.) These supports must be positioned so they contact all four (4) perimeter edges on the bottom of the unit.

VERTICAL, 90° ELBOW WITH HORIZONTAL

TERMINATION

Figure 12

Combustible Surround Installation

2 X 4

HEADER

STAND OFF

MANTELSHELF

COMBUSTIBLE SURROUND

FINISHED WALL

3! OF NON-COMBUSTIBLE MATERIAL

FRONT TRIM OR NON-COMBUSTIBLE

MATERIAL (INSTALLATION IS OPTIONAL)

JOINT BETWEEN FINISHED WALL AND

UNIT SEALED WITH 300° F 149

SEALANT

° C

MATERIAL (SEALANT IS OPTIONAL)

DVP42, 48

49 ½”(126 mm)

TO BOTTOM

OF UNIT

VENT CAP/

THIMBLE

/

THIMBLE

Figure 14

17375-10-0706

Figure 13

Page 13

INSTALLATION (continued)

HORIZONTAL ONLY, STRAIGHT OUT THE BACK

" A"

PIPE LENGTH

CORNER INSTALLATION VERTICAL, 90° ELBOW TO

HORIZONTAL OUT THE WALL

WALL FIRESTOP/

THIMBLE

VENT

CAP

VENT CAP

WALL FIRESTOP/

THIMBLE

"A" "B"

6"(152mm) 5 1/8"(130mm) to 6 /2"(165mm)

9"(229mm) 8 1/8"(206mm) to 91/2"(241mm)

MODEL

DVP 42,48

DVP 42

12"(305mm) 11 1/8"(283mm) to 12 1/2"(317mm) DVP 42

Figure 15

VERTICAL, 90° ELBOW TO

HORIZONTAL OUT THE WALL

Dim.

A

B

C

D

DVP42

45 3/8"

1152mm

32 1/8"

816mm

DVP48

49 5/8"

1260mm

35 1/8"

892mm

13 3/8"

34 mm

15 1/2"

39 mm

64 1/8" 70 1/8"

1628mm

Figure 17

1781mm

CORNER INSTALLATION HORIZONTAL, 45° ELBOW

TO HORIZONTAL OUT THE WALL

WALL FIRESTOP/

THIMBLE

WALL FIRESTOP/

THIMBLE

"A" "B"

6"(152mm) 11 1/4"(286mm) to

12 3/4"(324mm)

9"(229mm) 14 1/4"(362mm) to

15 3/4"(400mm)

12"(305mm) 17 1/4"(438mm) to

18 3/4"(476mm)

Figure 16

Page 14

"C"

4 3/4"(121mm) to

6 1/4"(159mm)

7 3/4"(197mm) to

9 1/4"(235MM)

10 3/4"(273mm) to

12 1/4"(311mm)

DVP42

"A" "B"

6"(152mm) 4"(102mm) to

5 1/2"(140mm)

9"(229mm) 6"(152mm) to

7 /2"(191mm)

12"(305mm) 9"(229mm) to

10 1/2"(267mm)

DVP48

"B"

4"(102mm) to

5"(127mm)

6"(152mm) to

7 1/2"(191mm)

9"(229mm) to

10 1/2"(267mm)

Figure 18

17375-10-0706

VENTING FIREPLACE - TOP

Venting Graph (Dimensions in Feet)

To Use the Vent Graph (Figure 19)

1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line.

2. From the point of this intersection, draw a vertical line to the bottom of the graph.

3. Select the indicated dimension, and position the unit in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 35 feet, the horizontal run to the outer wall flange must not exceed 6.5 feet.

EXAMPLE B:

If the vertical dimension from the floor of the unit is 6.5 feet, the horizontal run to the outer wall flange must not exceed 14.5 feet.

Special Note: For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system.

Reduce 3' for every 90° elbow.

Example: According to the chart the maximum horizontal vent length is 20' and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17'.

The maximum number of 45 degree elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

Note: On vertical venting the first elbow does not get counted.

17375-10-0706

Figure 19

Acceptable vertical and horizontal vent run.

(40' maximum vertical and 20' maximum horizontal)

Unacceptable vertical and horizontal vent run.

Page 15

VENTING FIREPLACE - TOP (continued)

Below Grade Installation

When it is not possible to meet the required vent terminal clearances of 12" (305mm) above grade level, a snorkel kit is recommended.

It allows installation depth down to 7" (178mm) below grade level.

The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.

Firestop at

Ceiling Level

TYPICAL BASEMENT INSTALLATION

Figure 20

Examples of possible venting systems using one (1) 90° elbow.

Eight (8) feet is listed as minimum vertical vent run with 20 feet of maximum horizontal vent run. Vertical dimensions are based on centerline to centerline of pipe. Horizontal dimensions are based on centerline of pipe to end of termination.

Figure 21

Examples of possible venting systems using two (2) 90° elbows.

V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two (2) 90° elbows as shown in Figure

22 is 20 feet.

Attention: Refer to Figure 19 for additional venting requirements.

Firestop at

Ceiling Level

Page 16

Figure 22

17375-10-0706

30

2

A

CENTER OF

ELBOW

OUT

(MINIMUM)

Figure 24

Figure 23

MINIMUM HOLE LOCATION DIMENSIONS FOR

THROUGH THE WALL HORIZONTAL INSTALLATIONS

WITH 90 DEGREE ELBOW OFF TOP OF FIREPLACE

FIREPLACE

SERIES

HARD ELBOW DIMENSIONS

"A"

DVP42FP 43-1/2"

(1105mm)

DVP48FP 43-1/2"

(1105mm)

"B"

5"

(127mm)

5"

(127mm)

"C"

7"

(178mm)

7"

(178mm)

FIREPLACE

SERIES

DVP42FP

DVP48FP

FLEX PIPE 90 DEGREE BEND

"A"

46"

(1143mm)

46"

(1143mm)

"B"

5"

(127mm)

5"

(127mm)

"C"

7"

(178mm)

7"

(178mm)

Positioning the Fireplace

Determine the exact position of the appliance so the direct vent termination will be centered (if possible) between two (2) studs. This will avoid any extra framing. All vent kit pipes should be assembled on the unit after the unit is moved into the final position.

Cutting the Hole (Figures 23)

After the fireplace has been positioned in its permanent location, the hole through the exterior wall of the house can be cut. This hole must be 12" (305mm) high x 10" (254mm) wide with its center line determined by the amount of vertical rise and horizontal run of the termination. (See Figure 23) When locating the hole it must be noted that the bottom of the cap must be 12" (305mm) above the ground level, and top of the cap must be no less than 18" (457mm) below a combustible projection, and no closer than 9" (229mm) to any wall running parallel to vent termination. (See Figure 24)

MAXIMUM HORIZONTAL

RUN WITH NO VERTICAL

RISE AND 90° ELBOW

MAXIMUM HORIZONTAL

RUN WITH MINIMUM

VERTICAL RISE AND

90° ELBOW

Figure 25

17375-10-0706 minimum

Page 17

EXAMPLES - TOP VENT RUN

24”

24” MINIMUM

CLEARANCE TO

COMBUSTIBLES

Figure 27

Figure 26

Page 18

Figure 28

17375-10-0706

To Use the Vent Graph (Figure 29)

1. Determine the height of the center of the horizontal vent pipe. Using this dimension on the Sidewall Vent Graph, locate the point it intersects with the slanted graph line.

2. From the point of this intersection, draw a vertical line to the bottom of the graph.

3. Select the indicated dimension, and position the unit in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 12 feet, 4 inches the horizontal run to the outer wall flange must not exceed 12 feet, 3 inches.

EXAMPLE B:

If the vertical dimension from the floor of the unit is

6 feet, 9 inches the horizontal run to the outer wall flange must not exceed 6 feet, 6 inches.

Special Note: For each 45 degree elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system. Reduce 3' for every 90° elbow.

Example: According to the chart the maximum horizontal vent length is 20' and if two 45 degree elbows are required in the horizontal vent it must be reduced to 17'.

The maximum number of 45 degree elbows permitted per side wall installation is two (2).

These elbows can be installed in either the vertical or horizontal run.

VENTING FIREPLACE - REAR

Venting Graph (Dimensions in Feet)

28

27

26

31

30

29

34

33

32

39

38

37

36

35

40

REAR EXIT - VERTICAL AND HORIZONTAL TERMINATION

(DIMENSIONS IN FEET)

A

B

DVP48FP(ONLY)

REAR HORIZONTAL

VENT CONNECTION

17375-10-0706

HORIZONTAL RUN

Figure 29

Acceptable vertical and horizontal vent run.

Unacceptable vertical and horizontal vent run.

Page 19

EXAMPLES - REAR VENT RUN

Model

DVP42

DVP48

Maximum Pipe

Length H1

24"

6"

Figure 32

Figure 30

Model Maximum Pipe

Length H1

DVP42 24"

DVP48 18"

Page 20

Figure 31

Figure 33

17375-10-0706

TERMINATION CLEARANCES

Termination clearance for buildings with combustible and noncombustible exteriors.

Vertical Sidewall Installations

Important! Minimum clearance between vent pipes and combustible materials is three (3") (76mm) on top, and (1") (25mm) on bottom and sides.

Figure 34

Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the siding. SD-1284 termination cap must be used.

Information on Various Venting Routes and Components

Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm) (See Figure 19).

Venting terminals shall not be recessed into wall or siding.

17375-10-0706 Page 21

VENT CLEARANCES

Figure 35

A = *Clearance above grade, veranda, porch, deck or balcony

[*12 inches (30cm) minimum]

B = clearance to window or door that may be opened [*12 inches

(30cm) minimum for appliances < 100,000 Btuh (30kW)

C = clearance to permanently closed window [minimum 12 inches (30cm) recommended to prevent condensation on window]

D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (60 cm) from the center of the terminal [18 Inches (46 cm) minimum

E = clearance to unventilated soffit [12 inches 30cm) minimum]

F = clearance to outside corner [See Page 21]

G = clearance to inside corner [See Page 21]

H = *not to be installed above a meter/regulator assembly within 3 feet (90cm) horizontally from the center-line of the regulator

I = clearance to service regulator vent outlet [*6 feet (1.8m) minimum]

J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance [*12 inches

(30cm) minimum for appliances ≤ 100,000 Btuh (30 kW)

36 inches (90cm) minimum for appliances > 100,000 Btuh

(30kW)]

K = clearance to a mechanical air supply inlet [* 6 feet (1.8m) minimum]

L = †clearance above paved sidewalk or a paved driveway located on public property [*7 feet (2.1m) minimum]

M = clearance under veranda, porch, deck, or balcony [*12 inches

(30cm) minimum ¥]

† a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings*

¥ only permitted if veranda, porch, deck, or balcony, is fully open on a minimum of 2 sides beneath the floor*

* as specified in CGA B149 Installations Codes or ANSI

Z223.1. Note: Local Codes or Regulations may require different clearances.

Page 22 17375-10-0706

VENT SYSTEM IDENTIFICATION

Installing Vent Components (Figure 36)

Begin the vent system installation by installing the first Simpson

Duravent component, 90° elbow to the starting collars or straight pipe on the top of the appliance, then the straight pipe length and then horizontal or vertical termination kit.

NOTE: All outer connection joints must be sealed with aluminum tape, screws or silicone sealant rated above 300°F/149°C. The inner flue joints do not require any sealant.

Simpson Duravent vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto the appliance collar or previously installed component end with four (4) equally spaced indented sections.

When the internal beads of each starting outer pipe line up, rotate pipe section clockwise 90° (approximately 3 inches). The vent pipe is now locked together.

Continue adding components per the pre-planned vent system configuration. Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.

WALL THIMBLE

(MAXIMUM OF

THREE 90 ELBOWS)

(MAXIMUM OF

TWO 90 ELBOWS)

Special DV Vent Kits - Simpson Duravent and Empire Comfort Systems, Inc.

Can be purchased from Empire Comfort Systems, Inc.

DVVK-5R

Direct-Vent Fireplace Vent Kit for Rear Vent, 6 to 12 inch wall thickness, Includes SD-1208, SD-1247, and SD-2184

DVVK-5T

DVVK-5V

Direct-Vent Fireplace Vent Kit for Top Vent, Thru-the-wall, 4 to 6 inch wall thickness, Includes SD-1290, SD-1284, SD-1208 and SD-1247

Direct Vent Fireplace Vent Kit - Vertical, Includes SD-1291,

SD-1253, and SD-1243

Figure 36

17375-10-0706

Special Venting Components

Simpson Dura-Vent

SD-1250

SD-1245

SD-1290

SD-1249

SD-1263

SD-1243

SD-1253

SD-91291

SD-1281

SD-1282

SD-1247

Can be purchased from Simpson Duravent or from

Empire Comfort Systems, Inc.

Part Number Description

SD-1208

SD-1207

SD-1206

6" Pipe Length

9" Pipe Length

12" Pipe Length

SD-1204

SD-1203

SD-1202

SD-1211

SD-1284

24" Pipe Length

36" Pipe Length

48" Pipe Length

Adjustable Pipe Length 11 - 14 5/8"

Horizontal Square Termination Cap

Vinyl Siding Standoff

45° Elbow

90° Elbow

Wall Firestop

Ceiling Firestop

Roof Flashing - 0/12 to 6/12 Roof Pitch

Storm Collar

High Wind Vertical Top

36" Snorkel

14" Firestop Snorkel

Wall Thimble Firestop

Page 23

FRAMING AND FINISHING

Installing Support Brackets (Figure 37)

A horizontal pipe support MUST BE used for each 3 feet of horizontal run. The pipe supports should be placed around the pipe and nailed in place to framing members. There MUST BE a 3 inch clearance to combustibles above 8 inch diameter pipe and elbows and 1 inch clearance on both sides and bottom of the 8 inch dia. pipe to combustibles on all horizontal pipe sections and elbows.

Vertical runs of this vent systems must be supported every 4 feet above the appliance flue outlet by wall brackets attached to the

8 inch vent pipe and secured with nails or screws to structural framing members.

10 3/8

12 3/8

Figure 37

Installing Firestops (Figures 38, 39, 40 and 41)

Firestops are required for safety whenever the vent system passes through an interior wall, an exterior wall, or a ceiling. These firestops act as a firebreak heat shield and as a means to insure that minimum clearances are maintained to the vent system.

Horizontal runs in the vent system which pass through either interior or exterior walls, require the use of wall firestops on both sides of the wall through which the vent passes.

Cut a 10-3/8 inch x 12-3/8 inch hole in wall. Position firestop

(SD1249) on interior side of wall for 10-3/8 inch x 12-3/8 inch hole.

Attention: Wall firestop hole is off-set towards bottom of wall opening. Secure with nails or screws. Continue the vent run through the firestop (See Figure 38).

WALL FIRESTOP

HOLE IS OFF-SET

TOWARDS BOTTOM

OF WALL OPENING.

Figure 38

Vertical runs of this system which pass through ceilings require the use of ONE (1) ceiling firestop at the hole in each ceiling through which the vent passes.

Position a plumb bob directly over the center of the vertical vent component and mark the ceiling to establish the center point of the vent. Drill a hole or drive a nail through this center point and check the floor above for any obstructions such as wiring or plumbing runs. Reposition the appliance and vent system, if necessary, to accommodate ceiling joists and/or obstructions.

Cut a 10 1/2 inch x 10 1/2 inch hole through the ceiling, using the center point previously marked. Frame the hole with framing lumber the same size as the ceiling joists. (See Figure 39) If the area above the ceiling is NOT an attic, position and secure the ceiling firestop (SD-1263) on the ceiling side of the previously cut and framed hole. (See Figure 40) If the area above the ceiling is an attic, position and secure the firestop on top of the previously framed hole. (See Figure 41)

NOTE: Remove insulation from the framed area in the attic before installing the firestop and/or vent pipes.

Page 24 17375-10-0706

FRAMING AND FINISHING (continued)

Figure 39

Figure 41

See Horizontal Termination Page 25 and Vertical Termination

Page 27-28.

Figure 40

HORIZONTAL TERMINATION

NOTE: Termination cap should pass through the wall firestop from the exterior of the building. Adjust the termination cap to its final exterior position on the building.

Warning: Termination cap must be positioned so that arrow is pointing up.

Attach the termination cap with the four wood screws provided.

Before attachment of the termination, run a bead of silicone sealant rated above 250°F on its outside edge too, so as to make a seal to the exterior wall.

NOTE: Wood screws can and should be replaced with appropriate fasteners for use on stucco, brick, concrete or other types of siding.

CAUTION: If exterior walls are finished with vinyl siding, (or materials that could become discolored or warp) it is necessary to install the vinyl siding standoff SD-1250.

Vinyl siding standoff SD-1250 will be installed between the vent termination and the exterior wall. (See Figure 42) This horizontal vent termination bolts onto the flat portion of the vinyl siding standoff, so an air space will exist between the wall and the termination cap.

17375-10-0706

Figure 42

Page 25

DVVK-5F FLEX VENT INSTRUCTIONS

The DVVK-5F FLEX VENT KIT includes the following components:

• (1) Horizontal Termination Cap

• (1) 4-foot section of Flex vent with spacers (5" flue/8" outer pipe)

with flue adapter collar

• (1) Wall Firestop/Thimble Assembly

• Hardware pack that includes band clamps and screws

Flex venting can be installed either vertically or horizontally off of the DVP Series fireplaces. When installing a horizontal vent run from top connections, maintain at least ½" rise for every 12" of vent run. When venting horizontal off the rear vent connections, allow a minimum rise of 2". Refer to the Figure 42 when mounting termination near vinyl siding.

CAUTION: Always stretch and secure venting with wire or metal strapping to ensure that the horizontal runs do not sag.

If space permits, it is generally easier to attach venting in the top vent configuration.

Because of sharp edges, always use gloves when handling the flex vent components.

Vent connections should overlap a minimum of 1" for proper sealing.

Always follow the general venting requirements for vent terminal location, vent lengths, and clearance to combustible materials.

INSTALLATION

1. Unpack vent components and check that all items are included.

2. Check to see that the vent spacer springs are located around the flue vent at 8" and 12" intervals along its length. See Figure A.

If not, stretch the spacer springs to about 15" long and wrap them around the flue, then interlock the ends of each spring about 2".

See Figure B. Maintain equal distance between spring spacers.

SPACER

SPRINGS

7. Attach the Termination Cap to the outside of the house.

8. Prior to making the vent connections, apply high temperature sealant (1000 degree F min.) to the vent connections before securing with the band clamps provided. Note: the flue pipe end without the adapter is to be installed to the Termination Cap.

9. Apply sealant to the outside of the flue pipe adapter and connect to the flex flue pipe. Then insert the adapter into the fireplace flue. Secure flue adapter to the fireplace flue with a minimum of two screws provided. See Figure C.

10. Attach the Outer Vent pipe to the 8" dia. Collar on the fireplace with a large band clamp provided. Sealant may also be used on the outer vent connections.

11. Check all vent connections for tightness. Make sure horizontal venting has the proper rise and combustible clearances required.

Refer to venting charts in fireplace instruction manual.

FLEX OUTER VENT

Figure A

FLEX FLUE PIPE

8”

(203 mm)

8”

(203 mm)

8”

(203 mm)

8” DIA. FLEX

VENT PIPE

5” DIA. FLEX

FLUE PIPE

5” DIA. FLUE

ADAPTOR

COLLAR

Figure C

BAND CLAMP

8” DIA. FIREPLACE

INLET COLLAR

APPLY HIGH

TEMPERATURE

SEALANT

4” FLEX

VENT PIPE

SPACER

SPRING

Figure B

4. Install the Wall Firestop/Thimble assembly as required through the wall. Refer to the venting charts in the fireplace manual to determine the proper height and size of the vent opening. The minimum opening should be 10" wide by 12" high. The minimum combustible clearance from the horizontal vent is 1" from sides and bottom, and 3" above the vent pipe. See Figure D.

5. In most cases, after determining the length of the vent that is needed, it may be easier to install the flue and outer vent pipes to the Termination Cap first, then from the outside, feed the venting through the wall to the fireplace.

6. If the venting is to long, trim off any excess vent before attaching the vent end connectors.

Page 26

Top of Vent

3" (76 mm)

1"

(25 mm)

Combustibles NOT allowed in shaded area

5” Diameter flue

8” Diameter intake vent

1"

(25 mm)

Figure D

17375-10-0706

GAS VENT

VERTICAL TERMINATION

Locate and mark the center point of the venting pipe. Using a nail on the underside of the roof and drive this nail through this center point. Make the outline of the roof hole around this center point.

NOTE: Size of the roof hole dimensions depend on the pitch of the roof. There must be a 1 inch clearance (25mm) to the vertical pipe sections. This clearance is to all combustible material.

Cover the opening of the vent pipe and cut and frame the roof hole.

Use framing lumber the same size as the roof rafters and install the frame securely. Flashing anchored to frame must withstand high winds. The storm collar is placed over this joint to make a watertight seal. Non-hardening sealant should be used to completely seal this flashing installation.

Determining Minimum Vent Height Above the Roof.

WARNING: Major U.S. building codes specify minimum chimney and/or vent height above the roof top. These minimum heights are necessary in the interest of safety. These specifications are summarized in Figure 43.

VENT CAP

LOWEST

DISCHARGE

OPENING

2. Remove the cap and shine a flashlight down the vent. Remove any bird nests or other foreign material.

3. Check for evidence of excessive condensate, such as water droplets forming in the inner liner and subsequently dripping out at joints. Condensate can cause corrosion of caps, pipe and fittings. It may be caused by having excessive lateral runs, too many elbows and exterior portions of the system being exposed to cold weather.

4. Inspect joints to verify that no pipe sections or fittings have been disturbed and, consequently, loosened. Also, check mechanical supports, such as wall straps or plumbers’ tape for rigidity.

Venting terminal shall not be recessed into a wall or siding.

A removable panel or other means must be provided in the enclosure for visual inspection of the flue connection.

NOTE: This also pertains to vertical vent systems installed on the outside of the building.

Slide the vertical top SD-1291 over the ends of the vent pipe and secure. (See Figure 44)

Installing the Vent System in a Chase

A chase is a vertical box-like structure built to enclose the gas appliance and/or it’s vent system. Vertical vent runs on the outside of a building may be, but are not required to be installed inside a chase.

H

ROOF PITCH

Flat to 6/12

6/12 to 7/12

Over 7/12 to 8/12

Over 8/12 to 16/12

Over 16/12 to 21/12

ROOF PITCH IS X/12

H (Min.) - Minimum height from roof to lowest discharge opening

H (Min.)

12" (305 mm)

15" (381 mm)

18" (457 mm)

24" (610 mm)

36" (914 mm)

Figure 43

Note that for steep roof pitches, the vent height must be increased.

In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down-drafting. In these cases, increasing the vent height may solve this problem.

General Maintenance

Conduct an inspection of the venting system semi-annually.

Recommended areas to inspect are as follows:

1. Check areas of the venting system which are exposed to the elements for corrosion. These will appear as rust spots or streaks and, in extreme cases, holes. These components should immediately be replaced.

Figure 44

CAUTION: Treatment of firestop spacers and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes.

Therefore, your local building codes must be checked to determine the requirements for these steps.

NOTE: When installing this vent system in a chase, it is always good building practice to insulate the chase as you would the outside walls of your home. This is especially important for cold climate installations. Upon completion of building your chase framing, install the vent system by following the instructions in this manual. Remember to build the chase large enough so that minimum clearance of combustible materials (including insulation) to the vent system are maintained.

17375-10-0706 Page 27

VERTICAL TERMINATION (continued)

Reassembly and Resealing Vent Pipe System

Attach vent pipe to inlet and outlet vent adaptor on fireplace in either the vertical or horizontal position, replace horizontal and vertical pipe lengths, elbows and horizontal or vertical termination kit.

All vent system components lock into place by sliding the concentric pipe section with four (4) equally spaced interior beads onto the appliance collar or previously installed component end with four

(4) equally spaced indented sections. When the internal beads of each starting outer pipe line up, rotate pipe section clockwise 90°

(approximately 3 inches). The vent pipe is now locked together.

Continue replacing components per the vent system configuration.

Be certain that each succeeding vent component is securely fitted and locked into the preceding component in the vent system.

Reassembly and Resealing Gas Accumulation Relief System

Glass Frame Assembly and Combustion Chamber

Whenever the glass frame assembly is pivoted open by a delayed ignition in the main burner, the glass frame assembly gaskets and combustion chamber must be examined by a qualified service person for damage. All damaged gaskets on the glass frame assembly and combustion chamber must be replaced by a qualified service person.

If damage occurs to the combustion chamber, it must be replaced by a qualified service person. Contact Empire Comfort Systems,

Inc. for replacement parts.

Vertical Through the Roof Applications (Figure 45)

Your Gas Fireplace has been approved for: a) Vertical installations up to 40 feet in height.

b) Two sets of 45 degree elbow offsets within these vertical installations. From 0 to a maximum of 8 ft. a vent pipe can be used between elbows.

c) Wall straps must be used to support offset pipe every 4'.

This application will require that you first determine the roof pitch and use the appropriate venting components.

40

12.19

Figure 45

Page 28 17375-10-0706

LOG PLACEMENT (3 LOG SET)

Before you begin: If you are installing logs into the DVP42 or

DVP48 model then this fireplace is supplied with a set of three ceramic fiber logs. Do not handle these logs with your bare hands.

Always wear gloves to prevent skin irritation from ceramic fibers.

After handling logs, wash your hands gently with soap and water to remove any traces of fiber.

The positioning of logs is critical to safe and clean operation of this fireplace. Sooting and other problems may result if the logs are not properly and firmly positioned in the fireplace. Please refer to Figure 48A, Figure 48B, and Figure 49 and corresponding

WARNING, when completing the following log placement steps.

1. Remove top louver, grasp louver, lift and pull forward.

2. Lower bottom louver, lift and hinge forward.

3. Release two glass frame spring clamps at bottom of firebox

4. Place bottom log onto main burner. Align holes on bottom log with (4) locator pins on burner.

5. Place rear log on rear log shelf. Place rear log so that the locator holes align with the (2) locator tabs in the log support shelf.

6. Place top branch onto flat area of rear log and over the front of the bottom log.

7. Place decorative rock in front of grates and sides of main burner.

ATTENTION: Do not place decorative rock on logs or on burner. The decorative rock should only be placed on the fireplace floor.

8. After all logs are properly positioned, place small "dime" size pieces of Rockwool lightly across the front round "blueflame" ports. Place the ember material (Rockwool pieces) side by side.

Do not stack more than one layer of embers across the burner ports. See Figure 48A.

9. Replace glass door onto firebox.

10. Secure the two glass frame spring clamps at bottom of firebox.

11. Align the tabs on top louver brackets with slots in front posts to secure top louver.

12. Close bottom louver. Lift slightly to engage the end tabs into the slots in fireplace sides to close louver panel.

Figure 48B

WARNING: Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.

Attention: Do not use Figure 48B or Figure 49 to order logs.

Refer to parts view on page 46 and parts list on page 47 and

48 to order logs and/or ember material for your appropriate fireplace model.

TOP BRANCH

REAR LOG

BOTTOM LOG

REAR LOG LOCATOR TABS

Figure 49

EMBER PLACEMENT

BOTTOM LOG LOCATOR PINS

17375-10-0706

Figure 48A

Page 29

OPERATING INSTRUCTIONS

750 Millivolt System

The standing pilot (750 millivolt system) is a continuous burning pilot. The pilot remains ON even when the main burner is OFF.

When you ignite the pilot, the thermopile produces millivolts

(electrical current) which energizes the magnet in the gas valve.

After 30 seconds to 1 minute time period you can release the gas control knob and the pilot will stay ON. Allow your pilot flame to operate an additional one (1) to two (2) minutes before you turn the gas control knob from the PILOT position to the ON position. This time period allows the millivolts (electrical current) to build-up to a sufficient level allowing the gas control to operate properly.

1. Follow the SAFETY and LIGHTING INSTRUCTIONS for standing pilot controls found in this manual and on labels found in control compartment behind the door assembly.

CAUTION: During the initial purging and subsequent lightings, never allow the gas valve control knob to remain depressed in the “pilot” position without pushing the piezo ignitor button at least once every second.

2. During the operating season, leave the control valve knob in the

“ON” position. This will allow the pilot flame to remain lit. Turn the burner flame on or off with the fireplace Remote/OFF/ON switch, wall switch or remote controls.

NOTE: The gas control valve allows you to increase or decrease the height of the main burner flame. The control valve has a pressure regulator with a knob as shown in Figure 50. Rotate the knob clockwise to “HI” to increase the flame height and counterclockwise to “LO” to decrease the flame height.

3. When the operating season is over, turn the Remote/OFF/ON switch to “OFF” and the control valve to “OFF”. The system, including the pilot light, will be shut down.

The OWNER should carefully read and follow these operating instructions at all times. Lower the door assembly to view the gas controls for the fireplace.

Initial Lighting

Upon completing the gas line or turning the gas valve on after it has been in the “OFF” position, a small amount of air will be in the lines. When first lighting the fireplace, it will take a few minutes for the lines to purge themselves of this air. Once the purging is complete, the fireplace will light and operate satisfactorily.

Subsequent lightings of the appliance will not require such purging if the gas valve is not turned to “OFF.”

Pilot Flame (Figure 51)

The thermopile/thermocouple (standing pilot) tips should be covered with flame.

HI/LO REGULATOR

Figure 51

CONTROL KNOB

Figure 50

Page 30 17375-10-0706

OPERATING INSTRUCTIONS (continued)

STANDING PILOT OPERATING INSTRUCTIONS

Remote/Off/On Switch

The fireplace is equipped with a Remote/OFF/ON switch. A wire harness is attached to the Remote/OFF/ON switch. The red, black and green (wires) female push-ons attach to the Remote/OFF/ON switch. At the opposite end of the wire harness, the black and green

(wires) female push-ons attach to the gas valve. An additional green wire and the red wire, which are stripped and bare, will attach to one of the accessories that can be purchased for use with your fireplace.

Operation of REMOTE/OFF/ON Switch with no Accessories

To ignite main burner, turn the control knob on the gas valve from the PILOT position to the ON position. Turn the Remote/OFF/ON switch from the OFF position to the ON position. The additional green wire and red wire, which are stripped and bare are not used.

Wall Switch, FWS-1

Connect the green and red, stripped and bare, wires on the

REMOTE/OFF/ON switch wire harness to the wall switch. Turn the REMOTE/OFF/ON switch to the Remote position. Pivot the rocker switch on the FWS-1 to the ON position.

Wall Thermostats (optional)

TRW - Wireless for Millivolt models

TMV - Reed switch for Millivolt models

Battery Operated Remote Controls, FRBC, FBRTC, and

TRW

Connect the green and red, stripped and bare, wires on the

REMOTE/OFF/ON switch wire harness to the remote receiver that is a component in the remote kit. Turn the REMOTE/OFF/ON switch to the remote position. Follow instructions included with the remote to complete installation.

Note: If batteries fail in the remote, and immediate heat is desired, turn the REMOTE/OFF/ON switch from the REMOTE position to the ON position.

Electric (120 volt) Operated Remote Control, FREC

Connect the green and red, stripped and bare, wires on the REMOTE/

OFF/ON switch wire harness to the wires on remote receiver that is a component in the FREC. Turn the REMOTE/OFF/ON switch to the REMOTE position. Follow instructions in the FREC to complete installation.

NOTE: If electric (120 colt) fails in FREC, and immediate heat is desired, turn the REMOTE/OFF/ON switch from the REMOTE position to the ON position.

Installation of Remote Receiver

Place remote receiver on the floor of fireplace behind the louver as far forward as possible.

Attention: The velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.

Refer to remote control installation and operating instructions for more details on remote control.

Millivolt Control

The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.

Millivolt thermopile is self generating. Gas valve does not require

24 volts or 110 volts.

Check System Operation

Millivolt system and all individual components may be checked with a millivolt meter 0-1000 MV range.

It is important to use wire of a gauge proper for the length of the wire:

Recommended Wire Gauges

Maximum Length Wire Gauge

1' to 10'

10' to 25'

25' to 35'

18

16

14

17375-10-0706 Page 31

STANDING PILOT WIRING DIAGRAM

(OPTIONAL) THERMOSTAT

(OPTIONAL) WALL SWITCH

Page 32

Figure 52

17375-10-0706

STANDING PILOT LIGHTING INSTRUCTIONS

FOR YOUR SAFETY, READ BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance has a pilot which must be lighted by hand.

When lighting the pilot, follow these instructions exactly.

B. Before lighting smell all around the appliance area for gas.

Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

What To Do If You Smell Gas

• Do not try to light any appliance.

• Do not touch any electrical switch;

• Do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob.

Never use tools. If the knob will not push in or turn by hand, don't try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

1. Stop! Read the safety information above.

2. Set REMOTE/OFF/ON switch to OFF.

3. Turn off all electric power to the appliance (if applicable).

4. Lower bottom louver assembly.

5. Push in gas control knob slightly and turn clockwise to "OFF."

GAS CONTROL KNOB SHOWN

IN "OFF" POSITION

LIGHTING INSTRUCTIONS

REMOTE

OFF

ON

9. Push in control knob all the way and hold in. Repeatedly push the piezo ignitor button until the pilot is lit. Continue to hold the control knob in the for about one (1) minute after the pilot is lit. Release knob, and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 9.

• If the control knob does not pop up when released, STOP and IMMEDIATELY call a qualified service technician or gas supplier.

• If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.

10. Turn gas control knob counterclockwise to "ON."

11. Close bottom louver assembly.

12. Turn on all electric power to the appliance (if applicable).

13. Set REMOTE/OFF/ON switch to desired setting.

Note: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.

6. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you then smell gas, STOP! Follow

"B" in the safety information above. If you do not smell gas, go to the next step.

THERMOCOUPLE

ELECTRODE

PILOT

THERMOPILE

7. Find pilot - Follow metal tube from gas control. The pilot is behind the burner on the right side.

8. Turn gas control knob counterclockwise

to "PILOT."

TO TURN OFF GAS TO FIREPLACE

1. Set REMOTE/OFF/ON switch to OFF.

2. Turn off all electric power to the appliance if service is to be performed (if applicable).

3. Lower bottom louver assembly.

4. Push in gas control knob slightly and turn clockwise

to "OFF." Do not force.

5. Close bottom louver assembly.

17375-10-0706 Page 33

STANDING PILOT TROUBLESHOOTING

With proper installation and maintenance, your new Direct Vent Gas Fireplace will provide years of trouble-free service. If you do experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.

1. Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.

a. Defective ignitor (no spark electrode)

—Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor.

b. No gas or low gas pressure.

—Check remote shut off valves from fireplace. Usually there is a valve near the main. There can be more than one

(1) valve between the fireplace and main.

—Low pressure can be caused by a variety of situations such as a bent line, too narrow diameter of pipe, or low line pressure. Consult with plumber or gas supplier.

c. No LP in tank.

—Check LP (propane) tank. Refill tank.

2. Pilot will not stay lit after carefully following lighting instructions.

a. Defective thermocouple.

—Check that pilot flame impinges on thermocouple. Clean and/or adjust pilot for maximum flame impingement.

—Ensure the thermocouple connection at the gas valve is fully inserted and tight (hand tight plus 1/4 turn). Faulty thermocouple if reading is below specified minimum of 15 millivolts.

—Disconnect the thermocouple from the valve, place one millivolt meter lead wire on the end of the thermocouple and the other millivolt meter lead wire on the thermocouple copper wire. Start the pilot and hold the valve knob in. If the millivolt reading is less than 15 millivolt, replace the thermocouple.

b. Defective valve.

—If thermocouple is producing more than 15 millivolts, replace faulty valve.

3. Pilot burning, no gas to burner, valve knob “ON”, REMOTE/

OFF/ON switch “ON.”

a. REMOTE/OFF/ON switch, wall switch, remote control or wires defective.

—Check REMOTE/OFF/ON switch and wires for proper connections. Place jumper wires across terminal at switch.

If burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or connections are bad.

b. Thermopile may not be generating sufficient millivolts.

—If the pilot flame is not close enough physically to the thermopile, adjust the pilot flame.

—Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket.

—Check the thermopile with a millivolt meter. Take the reading at TH-TP & TP terminals of the gas valve. The meter should read 350 millivolts minimum, while holding the valve knob depressed in the pilot position, with the pilot lit, and the REMOTE/OFF/ON switch in the OFF position.

Replace the faulty thermopile if the reading is below the specified minimum.

—With the pilot in the ON position, disconnect the thermopile leads from the valve. Take a reading at the thermopile leads.

The reading should be 350 millivolts minimum. Replace the thermopile if the reading is below the minimum.

c. Defective valve.

—Turn valve knob to ON. Place REMOTE/OFF/ON switch to ON. Check with millivolt meter at thermopile terminals.

Millivolt meter should read greater than 200 millivolts. If the reading is okay and the main burner does not ignite, replace the gas valve.

d. Plugged main burner orifice.

—Check main burner orifice for blockage and remove.

4. Frequent pilot outage problem.

a. Pilot flame may be too high or too low, or blowing (high), causing pilot safety to drop out.

—Clean and adjust flame for maximum flame impingement on the thermocouple. Follow lighting instructions carefully.

5. The pilot and main burner extinguish while in operation.

a. No LP (Propane) in tank.

Check LP (Propane) tank. Refill fuel tank.

b. Inner vent pipe leaking exhaust gases back into system

—Check for leaks.

c. Glass too loose, gasket leaks in corners after usage.

—Be certain glass assembly is installed correctly.

d. Horizontal vent improperly pitched.

—The horizontal vent cap should slope down only enough to prevent any water from entering the unit. The maximum downwards slope is 1/4 inch.

e. Bad thermopile or thermocouple.

—Replace if necessary.

f. Improper vent cap installation.

—Check for proper installation and freedom from debris or blockage.

6. Glass soots.

a. Flame impingement on logs.

—Check and adjust log position. Contact Empire Comfort

Systems, Inc.

b. Debris around throat of main burner.

—Inspect the opening at the base of the main burner. It is imperative that NO material be placed in this opening.

7. Flame burns blue and lifts off main burner.

a. Insufficient oxygen being supplied.

—Check to make sure vent cap is installed properly and free of debris. Make sure that vent system joints are tight and have no leaks.

—Check to make sure that no material has been placed at the main burner base.

Page 34 17375-10-0706

INTERMITTENT PILOT OPERATING INSTRUCTIONS

The intermittent pilot (120/24 volt system) is ON when the main burner is ON. When the main burner is OFF the intermittent pilot is OFF.

The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip of the flame rod.

To adjust:

1. Remove the pilot adjustment cover screw.

2. Turn the inner adjustment screw clockwise decrease or counterclockwise

to

to increase pilot flame. Pilot adjustment is shipped at full flow rate. Turn the inner adjustment screw clockwise if the inlet pressure is too high.

3. Replace the cover screw after the adjustment to prevent gas leakage.

Label all wires prior to disconnection when servicing controls.

Wiring errors can cause improper and dangerous operation.

Verify proper operation after servicing.

Provided on the intermittent pilot wiring harness are two (2) stripped and bare wires that are labeled THERMOSTAT. The wires will be used for attachment of 24 volt thermostat, optional FWS-1 wall switch or will attach into the receiver on an optional FRBC-1,

FRBTC-1 or FREC-1 remote control.

Installation of Remote Receiver

Place remote receiver on the floor of fireplace behind the louver as far forward as possible.

Attention: The velcro loop and hook are not necessary in this installation but can be used to secure remote receiver.

INTERMITTENT PILOT WIRING DIAGRAM

CAUTION: ALL WIRING SHOULD BE DONE BY A QUALI-

FIED ELECTRICIAN AND SHALL BE IN COMPLIANCE

WITH ALL LOCAL, CITY AND STATE BUILDING CODES.

BEFORE MAKING THE ELECTRICAL CONNECTION,

MAKE SURE THAT MAIN POWER SUPPLY IS DISCON-

NECTED. THE APPLIANCE, WHEN INSTALLED, MUST

BE ELECTRICALLY GROUNDED IN ACCORDANCE

WITH LOCAL CODES OR, IN THE ABSENCE OF LO-

CAL CODES, WITH THE NATIONAL ELECTRICAL CODE

ANSI/NFPA 70 (LATEST EDITION).

Figure 54

ELECTRICAL CONNECTION (Figure 55)

The DVP Intermittent Pilot Models with optional fan requires 120

VAC electrical hookup to the electrical box (installed).

The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, if an external electrical source is utilized.

17375-10-0706

Figure 55

1. To wire Junction Box Receptacle, remove the tab on the side of the receptacle (hot side) to split receptacle. This will be required to separate blower and valve circuits.

2. Power for switched and live sides of Duplex Receptacle must come from the same power source. (One circuit breaker on main panel must switch all power off.)

3. From the wall box to the fireplace a 3-wire conductor with ground is recommended, however (2) two-wire conductors with grounds may be used in place of a 3-wire conductor with a ground if the black wires from the thermostat and blower switch are identified.

4. Two wall switches, or a wall switch and thermostat may be used to activate the two receptacle plugs independently.

Page 35

INTERMITTENT PILOT LIGHTING INSTURCTIONS

FOR YOUR SAFETY, READ BEFORE LIGHTING

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.

B. Before lighting smell all around the appliance area for gas.

Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

What To Do If You Smell Gas

• Do not try to light any appliance.

• Do not touch any electrical switch;

• Do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.

• If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob.

Never use tools. If the knob will not push in or turn by hand, don't try to repair it; call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. Stop! Read the safety information above.

2. Set the thermostat to lowest setting.

3. Turn off all electric power to the appliance.

7. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow

"B" in the safety information above. If you don't smell gas, go to the next step.

4. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.

8. Turn gas control knob counterclockwise

"ON".

9. Close louver front assembly.

to

GAS CONTROL KNOB

SHOWN IN "OFF” POSITION.

10. Turn on all electric power to the appliance.

ON

OFF

11. Set thermostat to desired setting.

12. If the appliance will not operate, follow the instructions "TO

TURN OFF GAS TO APPLIANCE" and call your service technician or gas supplier.

HONEYWELL

5. Lower louver front assembly.

6. Turn gas control knob clockwise to "OFF."

TO TURN OFF GAS TO APPLIANCE

1. Set the thermostat to lowest setting. (if applicable.)

2. Turn off all electric power to the appliance if service is to be performed.

3. Open bottom louver assembly.

4. Turn gas control knob clockwise force.

5. Close bottom louver assembly.

Page 36 to "OFF". Do not

17375-10-0706

INTERMITTENT PILOT TROUBLESHOOTING

Call Serviceman

GENERAL: All fireplaces have been fire-tested to check for proper operation. This includes, main burner flame, pilot flame, fan operation, fan control, limit control and automatic valve operation.

If the fireplace fails to function on initial installation, it is advisable to re-check the following:

1. 115 volts to the junction box.

STEP 2: Review Normal Operating Sequence and Module

Specifications.

2. Inlet gas pressure.

3. The 24 volt system.

4. Type of gas being used and that shown on the rating label.

The Service Department at Empire Comfort Systems, Inc. may be contacted to assist in servicing furnace.

Gas Leak Test: Paint pipe joints with rich soap and water solution. Bubbles indicate gas leak. Tighten joints to stop leak.

STEP 3: Reset the Module.

A. Turn the thermostat to its lowest setting.

B. Wait one minute.

As you do Steps 4 and 5, watch for points where operation deviates from normal. Refer to Troubleshooting Chart to correct problem.

Servicing the Pilot and Main Burners, Pilot Orifice, and Main

Burner Orifices: Disconnect the gas supply at the inlet to the control valve. Then remove the burner door to which the above components are attached.

S8600H INTERMITTENT IGNITION MODULE

SPECIFICATIONS

Lockout timing is 90 seconds. Ignition timing is until pilot lights or lockout occurs.

Module shuts down and cuts power to gas control on flame failure.

Gas control closes to provide 100 percent lockout on flame failure.

Manual reset required.

STEP 4: Check Safety Lockout Operation.

A. Turn gas supply off.

B. Set thermostat above room temperature to call for heat.

C. Watch for spark at pilot burner.

D. Time length of spark operation. Maximum spark time is 90 seconds.

E. Open manual gas cock and make sure no gas is flowing to pilot or main burner.

F. Set thermostat below room temperature and wait one minute before continuing.

ELECTRICAL RATINGS:

Voltage and frequency: 20.5 to 28.5V (24V nom.) 60 Hz.

Current rating: 0.2 A.

Valve contact ratings (at 24 Vac):

Run

Pilot 1.0 A

Main 1.0 A

Inrush

10.0 A

10.0 A

SPARK GENERATOR OUTPUT: 13kV peak at 25 pf load.

THERMOSTAT ANTICIPATOR SETTING: 0.2 A plus pilot valve rating plus main valve rating.

THERMOSTAT COMPATIBILITY: Standard models compatible with all open-close switch type 24 Vac thermostats capable of supplying rated voltage and current to the module.

AMBIENT TEMPERATURE RATING: Minus 40 F to plus 175

F (minus 40 C to plus 79 C).

RELATIVE HUMIDITY RATING: 5 to 90 percent RH at 95 F.

FLAME FAILURE RESPONSE TIME: 0.8 seconds at 1.0 uA flame current.

FLAME CURRENT: 1 uA, min.

STEP 5: Check Normal Operation.

A. Set thermostat above room temperature to call for heat.

B. Make sure pilot lights smoothly when gas reaches the pilot burner.

C. Make sure main burner lights smoothly without flashback. Make sure burner operates smoothly without floating or lifting.

D. If gas line has been disturbed, complete gas leak test.

Gas leak test: Paint gas control gasket edges and all pipe connections downstream of gas control, including pilot tubing connections, with rich soap and water solution. Bubbles indicate gas leaks. Tighten joints and screws or replace component to stop gas leak.

E. Turn thermostat below room temperature. Make sure main burner and pilot flames go out.

OPERATION

Module operation can be conveniently divided into two phases for S8600H. The phases are trial for ignition and main burner operation.

CHECKOUT

Check out the gas control system:

1. At initial installation of the appliance.

2. As part of regular maintenance procedures.

3. As the first step in troubleshooting.

4. Any time work is done on the system.

TRIAL FOR IGNITION

Pilot Ignition

Following call for heat (system start on S8600H), the module energizes the first main valve operator. The first main valve opens, which allows gas to flow to the pilot burner. At the same time, the electronic spark generator in the module produces a 13,000 volt spark pulse output (at 25 pf load). The voltage generates a spark at the igniter-sensor that lights the pilot.

STEP 1: Perform Visual Inspection.

A. With power off, make sure all wiring connections are clean and tight.

B. Turn on power to appliance and ignition module.

C. Open manual shutoff valves in the gas line to the appliance.

D. Do gas leak test ahead of gas control if piping has been disturbed.

17375-10-0706

If the pilot does not light, or the pilot flame current is not at least

1.0 uA and steady, the module will not energize the second main valve and the main burner will not light.

Page 37

INTERMITTENT PILOT TROUBLESHOOTING

Safety Lockout

S8600H provides 100 percent shutoff, or safety lockout. A timer starts timing the moment the trial for ignition starts. Ignition spark continues only until the timed trial for ignition period ends. Then the module goes into safety lockout. Lockout de-energizes the first main valve operator and closes the first main valve in the gas control, stopping pilot gas flow. The control system must be reset by setting the thermostat below room temperature for one minute or by turning off power to the module for one minute.

Main Burner Operation

When the pilot flame is established, a flame rectification circuit is completed between the sensor and burner ground. The flame sensing circuit in the module detects the flame current, shuts off the spark generator and energizes the second main valve operator. The second main valve opens and gas flows to the main burner, where it is ignited by the pilot burner. The flame current also holds the safety lockout timer in the reset (normal) operating condition.

When the call for heat ends, both main valve operators are de-energized, and both main valves in the gas control close.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

S8600H NORMAL OPERATING SEQUENCE

START

STAGE 1

Trial for Ignition

Thermostat, Wall Switch,

Remote, Etc. Calls for Heat

POWER INTERRUPTION

System shuts off. Restarts when power is restored.

PILOT FLAME FAILURE

Second main operator closes.

Module starts trial for ignition.

Spark Generator Powered

First Valve (Pilot)

Operator Opens

PILOT BURNER OPERATION

Pilot burner lights.

Module senses flame current.

OR

Pilot burner does not light

MODULE RESPONSE

S8600H After 90 seconds*pilot valve closes, spark stops.

* Lockout timing is stamped on module.

IF FLAME CURRENT SENSED

Spark generator off

Second valve operator

(Main) opens.

MAIN BURNER OPERATION

Module monitors pilot flame current.

THERMOSTAT SATISFIED

Valves close. Pilot and main burners are off.

END

Page 38 17375-10-0706

Important

1. The following service procedures are provided as a general guide.

2. Meter readings between gas control and ignition module must be taken within the trial for ignition period. Once the ignition module locks out, the system must be reset by setting the thermostat down for at least one minute before continuing.

3. If any component does not function properly, make sure it is correctly installed and wired before replacing it.

4. The ignition module cannot be repaired. If it malfunctions, it must be replaced.

5. Only trained, experienced service technicians should service intermittent pilot systems.

Perform the CHECKOUT steps on page 37 as the first step in troubleshooting. Then check TROUBLESHOOTING GUIDE to pinpoint the cause of the problem. If troubleshooting indicates an ignition problem, see Ignition System Checks below to isolate and correct the problem.

Following troubleshooting, perform the

CHECKOUT procedure

(page 37 ) again to be sure system is operating normally.

Ignition System Checks

Step 1: Check ignition cable.

Make sure:

A. Ignition cable does not touch any metal surfaces.

B. Ignition cable is no more than 36 inches long.

C. Connections to the ignition module and to the igniter-sensor are clean and tight.

D. Ignition cable provides good electrical continuity.

Step 2: Check ignition system grounding.

Nuisance shutdowns are often caused by a poor or erratic ground.

A. A common ground, usually supplied by the pilot burner bracket, is required for the module and the pilot burner/igniter sensor.

• Check for good metal-to-metal contact between the pilot burner bracket and the main burner.

• Check the ground lead from GND (BURNER) terminal on the module to the pilot burner. Make sure connections are clean and tight. If the wire is damaged or deteriorated, replace it with No. 14-18 gauge, moisture-resistant, thermoplastic insulated wire with 105 C (221 F) minimum rating.

• If flame rod or bracket are bent out of position, restore to correct position.

• Replace pilot burner/igniter sensor if insulator is cracked.

Step 3: Check spark ignition circuit. You will need a short jumper

wire made from ignition cable or other heavily insulated wire.

A. Close the manual gas valve.

B. Disconnect the ignition cable at the SPARK terminal on the module.

WARNING

When performing the following steps, do not touch stripped end of jumper or SPARK terminal. The ignition circuit generates 13,000 volts at 25 pf load and electrical shock can result.

C. Energize the module and immediately touch one end of the jumper firmly to the GND terminal on the module. Move the free end of the jumper slowly toward the SPARK terminal until a spark is established.

D. Pull the jumper slowly away from the terminal and note the length of the gap when sparking stops. Check table below.

ARC LENGTH

No arc or arc less than 1/8 inch.

ACTION

Check external fuse, if provided.

Verify power and module input terminal.

Replace module if fuse and power okay.

Arc 1/8 inch or longer Voltage output is okay.

Step 4: Check pilot flame current.

A. Turn off furnace at thermostat.

B. Disconnect main valve wire from the TH or MV terminal on the gas control.

C. Disconnect ground wire from GND (BURNER) terminal at module.

D. Connect a meter (dc microamp scale) in series with the ground lead.

• Disconnect ground lead from GND terminal on ignition module.

• Connect the black (negative) meter lead to the ignition module GND (BURNER) terminal.

• Connect the red (positive) meter lead to the free end of the ground lead.

E. Set thermostat to call for heat. The spark will light the pilot but the main burner will not light because the main valve actuator is disconnected.

F. Read the meter. The flame sensor current must be steady and at least 1.0 uA.

G. If the reading is less than the minimum or unsteady,

• Make sure pilot flame envelopes 3/8 to 1/2 inch of the flame rod.

• If necessary, adjust pilot flame by turning the pilot adjustment screw on the gas control clockwise to decrease or counterclockwise to increase pilot flame. Following adjustment, always replace pilot adjustment cover screw and tighten firmly to assure proper gas control operation.

• Check for cracked ceramic insulator, which can cause short to ground, and replace igniter-sensor if necessary.

• Make sure electrical connections are clean and tight. Replace damaged wire with moisture-resistant No. 18 wire rated for continuous duty up to 105 C (221 F).

H. Remove meter and reconnect all wires. Return system to normal operation before leaving job.

17375-10-0706 Page 39

INTERMITTENT PILOT TROUBLESHOOTING (continued)

S8600H TROUBLESHOOTING GUIDE

Page 40

START

Turn gas supply off

Turn thermostat to call for heat.

Power to module.

(24 VAC nominal)

Yes

Spark across ignitor/sensor gap.

Yes

Turn gas supply on.

Pilot burner lights?

Yes

Spark stops when pilot is lit?

Yes

Main burner lights?

Yes

System runs until call for heat ends?

Yes

Call for heat ends.

System shuts off?

No

Note: Before troubleshooting, familiarize yourself with the startup and checkout procedure.

Check line voltage power, low voltage transformer limit control, thermostat and wiring.

No

No

No

No

No

No

Pull ignition lead and check spark at ignition stud.

Spark okay?

Yes

No Replace module.

• Check ignition cable, ground wiring, ceramic insulator, and gap, and correct.

• Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

• Check that all manual gas valves are open. Supply tubing

And pressures are good, and pilot burner orifice is not blocked.

• Check electrical connections between module and pilot

Operator on gas control.

Check for 24 VAC across PV - MV/PV terminals on module.

If voltage is okay, replace gas control. If not, replace module.

Note: If S8600H goes into lockout, reset system.

Check continuity of ignition cable and ground wire.

Check that pilot flame covers electrode.

Adjust pilot flame current. Minimum signal should read 1.0

microamp.

If problem persists, replace module.

Check for 24 VAC across MV-MV/PV terminals. If no voltage, replace module.

Check electrical connections between module and gas control.

If okay, replace gas control.

Note: If S8600H goes into lockout, reset system.

Check continuity of ignition cable and ground wire. Note: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

If checks are okay, replace module.

Check for proper thermostat operation.

Remove MV lead at module: If valve closes, recheck thermostat and wiring. If not, replace gas control.

Troubleshooting ends.

Repeat procedure until troublefree operation is obtained.

17375-10-0706

RF STANDING PILOT OPERATING INSTRUCTIONS

Features

• Self powered millivolt receiver/valve

• Thermostat performance

• Auto mode

• Self powered millivolt control

• Integrated Valve Electronics

• Failure analysis

• Pilotstat interlock

• F or C temperature units

Benefits

• No external power or batteries required to operate valve and flame modulation

• Flame cycles and modulates such that heat output equals heat loss from the room

• Flame & fan are controlled automatically

• No external power required to control gas valve and flame modulation

• No electronics, rheostat, or limit installation required

• Troubleshooting with information from LED

• When valve is turned off, power unit must drop out before pilot can be relit

• Display local temperature units

Please review and retain the instructions included with the RF Transmitter. It provides additional information and details concerning the operational procedures and functions for the RF Remote Control.

Functions

• Flame powered system

• Flame powered flame modulation

• Electronics integrated into valve to provide thermostat, flame, and fan functions with RF commands

• Temperature compensated RF receiver

• Main burner goes to "high" when manual switch is set on "local"

• Fan powered by 120 vac

Transmitter Signal

• When the transmitter is in the Auto mode, a signal is sent every 10 minutes if there is a change in the room temperature

• When the transmitter is in the On or Off modes, a signal is also sent every 10 minutes with the status of On or Off condition

• The transmitter will work at a minimum of 25 feet from the receiver

• Make sure antennae is not touching metal and is horizontal. Refer to Figure 56.

Receiver Shutdown of Burner

• In the remote, auto mode the valve shuts off if it does not receive a signal within 3 hours from the transmitter

• In the local mode the valve does not shut off

• In the remote, manual mode the valve shuts off if it does not receive a signal within 6 hours from the transmitter

Thermopiles

• The negative leads (white) must be connected to the terminals with the one white dot marked next to them

• Each thermopile must provide at least 500 mV open circuit voltage

• If output is erratic, check thermopile for intermittent shorts

LED Troubleshooting

Note: In normal operation, LED blinks once every two seconds; also, LED will be on for one second after every valid command received by the RV8310D; these are not error codes.

Failure codes (see Table) can occur anytime after the pilot burner is lit. Failure code timing is 1/4 second on, 1/2 second off.

Sequence is failure code followed by LED not blinking for four seconds.

In the event of multiple failure codes, the next failure code follows the previous failure code by approximately three seconds.

Code Service Action

8 Replace valve

7 Confirm stepper motor connection exists

4

3

Fuel conversion plug missing or has poor connection (RV8310E only)

Replace thermopile with Q313

2

1

Device too hot. Check application

None required. This is normal operation and indicates the control is powered

For additional Standing Pilot Troubleshooting refer to Page 34

17375-10-0706 Page 41

RF TRANSMITTER FUNCTIONS

FIRST USE OF TRANSMITTER

Status

Begin communication between transmitter and receiver/valve.

Action

Transmit unique code.

Move LOCAL/REMOTE Switch to LOCAL position for at least two seconds; then move switch to the REMOTE position.

Press Fan or Flame key within 30 seconds.

Confirm recognition between transmitter and receiver/valve.

Observe LED turns on for one second.

Chose Remote or Local operation.

Move LOCAL/REMOTE switch to LOCAL or leave in REMOTE.

Operation in the Remote Position

AUTO Mode

With the control in the AUTO mode, the flame in the main burner will turn on, off, or change height based on the heat needed to maintain the set temperature.

Status Action

Set to AUTO.

Press MODE button until mode is AUTO.

Change set temperature.

Press UP or DOWN key to change set temperature.

Flame.

Fan.

To Set Delay Timer.

Automatically changes.

Automatically changes.

Press TIME key followed by either an UP or DOWN arrow key.

CAUTION

Properly Damage Hazard.

Excessive heat can cause property damage.

In AUTO mode, the main burner will cycle indefinitely to maintain the set temperature. Keep the transmitter in a heated living space to make sure that the main burner is not on continuously.

On Mode

When the control is in the ON mode, the flame and fan levels and the delay timer are changed with the UP and DOWN arrow keys.

Status Action

Set to ON.

Press MODE button until mode is ON.

Flame.

Fan.

Delay Time.

Press FLAME button and press UP or DOWN arrow key to change flame height.

Press FAN button and press UP or DOWN arrow key to change fan speed.

Press DELAY TIMER button and press UP or DOWN key to change timer.

Press MODE until mode is OFF.

OFF Mode

The flame in the main burner will turn off and the room temperature will be displayed in the remote window.

Operation in the LOCAL Mode.

NOTE: Remote/Local switch on the receiver/valve must be in the LOCAL position.

FAN

Flame height and fan speed both go to the highest position.

Other Functions:

Change between Fahrenheit and Celsius temperature units.

In LOCAL mode, to turn flame on/off, rotate manual knob from ON to

PILOT position.

Fan Override during AUTO Mode.

Disable thermostat function in the AUTO Mode

Press UP and DOWN arrow keys at the same time and hold for at least three seconds.

Press FAN button, and press UP or DOWN arrow key to change the fan speed.

Press the TIME, DOWN and FLAME arrow keys at the same time and hold for at least three seconds.

Page 42 17375-10-0706

RF WIRING DIAGRAM

WIRING DIAGRAM WITH BLOWER

17375-10-0706

Figure 56

Page 43

RF STANDING PILOT LIGHTING INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR

EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR

LOSS OF LIFE.

A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B. BEFORE LIGHTING, smell around the appliance area for gas. Be sure to smell next to the floor because some gas in heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.

• Do not touch any electrical switch.

• Do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. If you can not reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D. Do not use this appliance if any part has been under water.

Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

LIGHTING INSTRUCTIONS

1. STOP! Read the safet information above.

2. Turn off all electric power to the appliance (if applicable).

3. Lower louver front assembly.

4. Push in gas control knob slightly and turn clockwise

to "OFF".

NOTE: Knob cannot be turned from "PILOT" to "OFF" unless knob is pushed in slightly. Do not force.

5. Wait ten (10) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,

STOP! Follow "B" in the safety information above. If you do not smell gas, go to the next step.

6. Find pilot - follow metal tube from gas control.

The pilot is behind the middle log on the right side.

7. Turn gas control knob counterclockwise

"PILOT".

to

8. Push in control knob all the way and hold in. Immediately light the pilot with the Piezo Pilot ignitor or use a match.

Continue to hold the control knob in until LED blinks (one brief blink every two seconds). Holding time is about one

(1) minute after the pilot is lit. Release knob, and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 4 through 8.

If knob does not pop up when released, stop and immediately call a qualified service technician or gas supplier.

If the pilot will not stay lit after several tries, turn the gas control knob to "OFF" and call your service technician or gas supplier.

9. Turn gas control knob counterclockwise to

"ON".

10. Close louver front assembly.

11. Turn on all electric power to the appliance (if applicable).

TO TURN OFF GAS TO APPLIANCE

1. Turn off all electric power to the appliance if service is to be performed (if applicable).

2. Lower louver front assembly.

3. Push in gas control knob slightly and turn clockwise

to "OFF". Do not force.

4. Close louver front assembly.

Page 44 17375-10-0706

MAINTENANCE AND SERVICE

Please Note

It is normal for appliances fabricated of steel to give off some expansion and/or contraction noise during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.

It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process.

Please ensure that your room is well ventilated - open all windows.

It is recommended that you burn your fireplace for at least six

(6) hours the first time you use it. If optional fan kit has been installed, place fan in the “OFF” position during this time.

IMPORTANT: Turn off gas before servicing appliance. It is recommended that a qualified service person perform these checkups at the beginning of each heating season.

• Clean Burner and Control Compartment

Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year.

Cleaning Procedure

1. Turn off pilot light at gas valve.

2. Remove glass front. (See Glass Removal)

3. Vacuum burner compartment.

4. Reinstall glass front.

5. Ignite pilot. (See Lighting Instructions)

6. Operate the pilot burner. If it appears abnormal call a service person.

• Check Vent System

The appliance and venting system should be inspected before initial use and at least annually by a qualified service person.

Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the air flow.

Glass Cleaning

It will be necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint curing may deposit a slight film on the glass. It is therefore recommended that the glass be cleaned two or three times with a non-abrasive household cleaner and warm water

(we recommend gas fireplace glass cleaner). After that the glass should be cleaned two or three times during each heating season depending on the circumstances present.

General Glass Information

Warning: Do not operate appliance with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.

Only glass approved for use by the manufacturer in fireplace may be used for replacement. The glass replacement should be done by a licensed or qualified service person.

WARNING:

1. The use of substitute glass will void all product warranties.

2. Care must be taken to avoid breakage of the glass.

17375-10-0706

3. Under no circumstances should this appliance be operated without the glass front or with a broken glass front. Replacement of the glass (with gasket) as supplied by the manufacturer should be done by a qualified service person.

4. Do not abuse the glass by striking or hitting the glass.

WARNING: Do not use abrasive cleaners on glass. Do not attempt to clean glass when glass is hot.

Glass Removal and Replacement (Figure 57)

1. Remove top louver, grasp louver and pull forward.

2. Lower bottom louver.

3. Release two glass frame clamps at bottom of firebox.

4. Remove glass frame.

5. Place glass frame onto firebox.

6. Attach two glass frame clamps at bottom of firebox.

7. Align clips on top louver with slots on front posts. Replace top louver into fireplace.

8. Close bottom louver.

Figure 57

Louver Removal and Installation

1. Remove top louver, grasp louver and pull forward.

2. Lower bottom louver.

3. Align clips on top louver with slots on front posts. Replace top louver into fireplace.

4. Close bottom louver.

Page 45

Page 46

PARTS VIEW

16

7

8

9

11

4

3

2

5

6

1

10

12

11

12

17

19

18

20

12

15*

29

24

26

27

22c

23

28

31

30

33

37c

34

36c

RF VALVE BURNER ASSEMBLY

47

32

12

21

13

14

15

29

24

26

27

22a

23

28

24

26

27

22b

23

28

31

30

29

31

30

33

32

33

34

35

42

36b

32

37b

39b

43

44

45

INTERMITTENT PILOT BURNER ASSEMBLY

38

34

37a

36a

39a

40

MILLIVOLT BURNER ASSEMBLY

41

38

50

51

46

48

49

52

LOG SET ASSEMBLY

BLOWER ASSEMBLY - RF MODELS

17375-10-0706

INDEX

NO.

21

22a

22a

22b

17

18

19

20

22b

22c

22c

23

24

13

14

15

16

9

10

11

12

7

8

5

6

3

4

1

2

17363

M170

17142

R-7575

17430

R-7574

17247

10554

17162

R-3492

17357

17445

17804

17381

17187

17190

17188

R-7612

R-7611

R-5747

R-5748

R-6116

R-6117

M173

11269

PART NUMBER

DVP42

R-7654

17426

R-7567

R-7573

DVP48

R-7654

17426

R-7567

R-7573

17363

M170

17142

R-7575

17430

R-7574

17247

10554

17162

R-3492

17357

17446

17805

17447

17210

17213

17211

R-7612

R-7611

R-5747

R-5748

R-6116

R-6117

M173

11269

PARTS LIST

DESCRIPTION

FLUE INSULATION

FLUE INSULATION RETAINER

INLET VENT ADAPTOR

INLET VENT GASKET

FLUE OUTLET ASSEMBLY

FLUE CONNECTOR GASKET

VENT COVER PLATE

VENT COVER PLATE GASKET

FLUE COVER PLATE

FLUE OUTLET GASKET

TOP STANDOFF (2 REQUIRED)

NAILING FLANGE (4 REQUIRED)

JUNCTION BOX ASSEMBLY

RECEPTACLE, 3 - PRONG

JUNCTION BOX SHIELD

TOP SHIELD

INNER TOP HEAT SHIELD

BAFFLE, FLUE VENT

LOUVER ASSEMBLY - UPPER

GLASS DOOR FRAME ASSEMBLY

LOUVER ASSEMBLY - LOWER

PILOT, SIT GAS (NAT)

PILOT, SIT GAS (LP)

PILOT, INTERMITTENT GAS (NAT)

PILOT, INTERMITTENT GAS (LP)

PILOT, RF GAS (NAT)

PILOT, RF GAS (LP)

PILOT GASKET

GAS LINE BRACKET

Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.

17375-10-0706 Page 47

INDEX

NO.

45

46

47

48

41

42

43

44

49

50

51

52

36c

37a

37b

37c

38

39a

39b

40

33

34

35

36a

36a

36b

36b

36c

29

30

31

32

26

27

27

28

PARTS LIST (continued)

16223

R-3435

R-5751

R-2708+

R-3436+

R-1995+

R-5160

R-1616+

R-721+

-

18858

R-7731

R-7831

R-7643

R-7642

R-7641

11499

11377

17370

17368

17369

R-2423+

R-1109+

R-7577

R-7578

R-5745

R-5746

R-6114

R-6115

17161

17795

17796

PART NUMBER

DVP42

P200

P203

P185+

R-5676

DVP48

P200

P213

P250

R-5676

11499

11377

17386

17385

17369

R-1995+

R-5160

R-1616+

R-721+

-

18858

R-7731

R-7831

R-7643

R-7642

R-7641

R-2423+

R-1109+

R-7577

R-7578

R-5745

R-5746

R-6114

R-6115

17161

17795

17796

16223

R-3435

R-5751

R-2708+

R-3436+

DESCRIPTION

ORIFICE FITTING

ORIFICE (NAT)

ORIFICE (LP)

AIR SHUTTER

BURNER BRACKET LEFT

BURNER BRACKET RIGHT

SLOPE BURNER

BURNER BASE PLATE ASSEMBLY

TUBING ASSEMBLY

MALE CONNECTOR

BUSHING, FLUSH TYPE (IP ONLY)

VALVE, SIT GAS (NAT)

VALVE, SIT GAS (LP)

VALVE, INTERMITTENT PILOT GAS (NAT)

VALVE, INTERMITTENT PILOT GAS (LP)

VALVE, RF GAS (NAT)

VALVE, RF GAS (LP)

VALVE BRACKET (SIT)

VALVE BRACKET (IP)

VALVE BRACKET (RF)

SPRING LATCH ASSEMBLY

WIRING HARNESS (SIT)

WIRING HARNESS (IP)

PIEZO IGNITOR

REMOTE OFF/ON SWITCH

TRANSFORMER (IP)

TRANSFORMER CORD SET (IP)

CONTROL MODULE (IP)

WIRING ASSEMBLY (IP)

AIR DEFLECTOR (RF)

BLOWER BASE (RF)

BLOWER MOTOR ASSEMBLY (RF)

BLOWER CORD SET (RF)

TOP LOG - TWIG

REAR LOG

MAIN LOG

Page 48

Use Only Manufacturer’s Replacement Parts. Use of Any Other Parts Could Cause Injury Or Death.

17375-10-0706

FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION

Attention: Install blower assembly before connecting gas inlet supply line

Note: Junction box on right side of fireplace must be pre-wired at time of fireplace installation for use with blower assembly.

It is recommended that an ON/OFF wall switch be installed that will activate the power supply to the furnace by a qualified electrician.

1. If installed, turn OFF gas supply to fireplace.

2. If applicable, turn OFF electric supply to fireplace.

3. Lower bottom louver on fireplace.

4. Refer to page 51, "Junction Box Wiring Installation

Instructions" to complete wiring of junction box.

Attention: If installed, do not damage gas inlet supply line when blower assembly is inserted into fireplace. If necessary, remove gas inlet supply line.

5. Insert blower assembly into interior, bottom of fireplace.

Position blower assembly behind gas valve, align notch on back of blower assembly with center screw on fireplace back and push blower assembly against fireplace back. The magnets on the back and bottom of blower assembly will sufficiently hold blower assembly in place.

6. Position speed control box to the right of gas valve. Attach speed control box to bottom of fireplace. The magnets on bottom of speed control box will sufficiently hold speed control box in place.

7. With base (flush face) of fan control switch facing upward, insert base of fan control switch under the mounting tabs on valve bracket. The base (flush face) of fan control switch must be in contact with bottom of firebox.

8. Insert power cord plug into junction box.

9. Close bottom louver on fireplace.

10. Installation of FBB4 optional variable speed blower assembly is completed.

Wiring

The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, if an external electrical source is utilized. This appliance is equipped with a three-prong [grounding] plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug. For an ungrounded receptacle, an adapter, which has two prongs and a wire for grounding, can be purchased, plugged into the ungrounded receptacle and its wire connected to the receptacle mounting screw. With this wire completing the ground, the appliance cord plug can be plugged into the adapter and be electrically grounded.

Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

Blower Motor

The blower motor does not have oiling holes. Do not attempt to oil the blower motor.

Blower Wheels

The blower wheels will collect lint and could require periodic cleaning. If the air output decreases or the noise level increases, it indicates a dirty blower wheel. Remove fan and clean blower wheels.

Warning: Unplugging of blower accessory will not stop the heater from cycling. To turn off gas to the heater (millivolt model): push in gas control knob slightly and turn clockwise to "OFF." Do not force. To turn off gas on direct ignition model, turn gas line valve to "OFF."

FAN SWITCH

FAN KIT

VALVE BRACKET

SEE NOTE*

JUNCTION BOX

SPEED CONTROL

SWITCH HOLDER

(TOP OF VALVE BRACKET)

*Note: Refer to Junction Box wiring instructions on page 51 for proper operation.

17375-10-0706 Page 49

FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION

1

2

3

4

FBB4 B L O W E R A S S E M B LY

COMPLETE

R7649 FAN CONTROL

R4192 SPEED CONTROL KNOB

R4186 SPEED CONTROL

Page 50

JUNCTION BOX

FAN

110 VOLT AC

BLACK

FAN

SWITCH

WHITE

SPEED

CONTROL

GROUND

17375-10-0706

JUNCTION BOX WIRING INSTALLATION INSTRUCTIONS

CAUTION: ALL WIRING SHOULD BE DONE BY A QUALIFIED ELECTRICIAN AND SHALL BE IN COMPLIANCE

WITH ALL LOCAL, CITY AND STATE BUILDING CODES. BEFORE MAKING THE ELECTRICAL CONNECTION,

MAKE SURE THAT MAIN POWER SUPPLY IS DISCONNECTED. THE APPLIANCE, WHEN INSTALLED, MUST BE

ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR, IN THE ABSENCE OF LOCAL CODES,

WITH THE NATIONAL ELECTRICAL CODE ANSI/NFPA 70 (LATEST EDITION).

*

A factory installed junction box is located on the lower right side of the fireplace. Wiring must be fed to the junction box and attached to the receptacle that is provided. Leave approximately 6" of wire in the junction box for connection.

Attach black wire to one side of the receptacle and white wire to opposite side of receptacle. The ground wire should be attached to the green

(ground) screw.

Install the receptacle into the junction box. Attach cover plate.

*Note: For intermittent pilot models, refer to wiring instructions on page 35.

OPTIONAL BRICK LINER INSTALLATION INSTRUCTIONS

1. Using gloves, unpack liner components and check for damaged or missing components.

2. Lower bottom louver and remove upper louver on fireplace.

3. Remove glass frame assembly from fireplace.

4. Remove rear logs from burner assembly.

5. Place brick panel (rear) against rear wall in fireplace.

Note

: The top edge will have a half-moon cutout relief to match up with the rear flue vent hole.

6. While holding finished edge on brick panel (side), place brick panel (sides) against side walls in fireplace. Move side panels rearward until the back edge meets the rear brick panel. Slide side brick panels down so they rest on firebox bottom.

7. Align grout lines on top brick panel with the grout lines on the side brick panels. Place the top brick panel into brick panel holder. With needle-nose pliers, carefully bend hold-down tabs on brick panel holder over the edges of the top brick panel.

The hold-down tabs will securely hold the top brick panel in place.

8. Replace rear logs onto burner assembly. (Refer to log placement, page 29.)

9. Attach glass frame assembly onto fireplace.

10. Raise bottom louver and replace top louver onto fireplace.

11. Installation of optional brick liner is complete.

17375-10-0706 Page 51

ACCESSORIES

The following accessory parts can be obtained from your Empire Comfort Systems dealer. If you need additional information beyond what your dealer can furnish, contact Empire Comfort Systems Inc., Nine Eighteen Freeburg Ave., Belleville, Illinois

62220-2623.

Accessory

Fan Kit

Description

This fan kit was designed to provide forced air flow.

(Note: For use with Millivolt and intermittent pilot models only. "RF" Fireplace models are equipped with blower assembly.)

Model Number

Variable Speed

FBB4

Simulated Brick Panels

Simulated Brick Panels

The simulated brick panels were designed to enhance the appearance of your fireplace, imitating the look of authentic masonry.

DVP3DH(DVP42)

DVP4DH(DVP48)

HERRINGBONE

The simulated brick panels were designed to enhance the appearance of your fireplace, imitating the look of authentic masonry.

DVP3DA(DVP42)

DVP4DA(DVP48)

AGED BRICK

Decorative Louver Mission

DECORATIVE ACCESSORIES

Decorative Louver Arch

Decorative Louver Leaf

Decorative Frame Rectangle with hinges

Decorative Door Leaf Rectangle

Decorative Door Mission Rectangle

Decorative Door Plain Rectangle

Decorative Frame Arch with hinges

Decorative Door Leaf Arch Decorative Door Mission Arch Decorative Door Plain Arch

Decorative Frame Arch without hinges only Black

Page 52

Window Trim

STD Louvers 45 Deg

Outside Frame Kits

17375-10-0706

SERVICE NOTES

HOW TO ORDER REPAIR PARTS

Parts can be ordered only through your service person or dealer. For best results, the service person or dealer should order parts through the distributor. Parts can be shipped directly to the service person/dealer.

All parts listed in the Parts List have a Part Number. When ordering parts, first obtain the Model Number from the name plate on your equipment. Then determine the Part Number ( not the Index Number) and the Description of each part from the following appropriate illustration and list. Be sure to give all this information.

Fireplace Number

Fireplace Serial Number

Type of Gas (Propane or Natural)

Part Description

Part Number

Do not order bolts, screws, washers or nuts. They are standard hardware items and can be purchased at any local hardware store.

Shipments contingent upon strikes, fires and all causes beyond our control.

Empire Comfort Systems, Inc. Nine Eighteen Freeburg Ave. Belleville, Illinois 62222-2623

17375-10-0706 Page 53

SERVICE NOTES

Page 54 17375-10-0706

SERVICE NOTES

17375-10-0706 Page 55

Page 56

Empire Comfort Systems, Inc.

918 Freeburg Ave. Belleville, IL 62220

PH: 618-233-7420 or 800-851-3153

FAX: 618-233-7097 or 800-443-8648 [email protected]

www.empirecomfort.com

17375-10-0706

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals