Termination Clearances. Empire Comfort Systems DVP42FP731P-1, DVP36FP31N-1, DVP48FP9(1,3)(N,P)-1, DVP36FP73P-1, P)-1, DVP48FP730N-1, DVP42FP9(1,3)(N,P)-1, DVP36FP72P-2, DVP42FP933P-1, DVP48FP931N-1


Add to my manuals
56 Pages

advertisement

Termination Clearances. Empire Comfort Systems DVP42FP731P-1, DVP36FP31N-1, DVP48FP9(1,3)(N,P)-1, DVP36FP73P-1, P)-1, DVP48FP730N-1, DVP42FP9(1,3)(N,P)-1, DVP36FP72P-2, DVP42FP933P-1, DVP48FP931N-1 | Manualzz

TERMINATION CLEARANCES

Termination clearance for buildings with combustible and noncombustible exteriors.

Vertical Sidewall Installations

Important! Minimum clearance between vent pipes and combustible materials is three (3") (76mm) on top, and (1") (25mm) on bottom and sides.

Figure 34

Important! When vent termination exits through foundation less than 20" below siding outcrop, the vent pipe must flush up with the siding. SD-1284 termination cap must be used.

Information on Various Venting Routes and Components

Important: It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.

Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various vent lengths allowable.

The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

The maximum horizontal vent run is 20 feet (457 cm) when the vertical vent rise is 8 feet (244 cm) (See Figure 19).

Venting terminals shall not be recessed into wall or siding.

17375-10-0706 Page 21

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals