Typical BMS – EMS – BAS System Variables. Modine Manufacturing Atherion MPR


Add to my manuals
96 Pages

advertisement

Typical BMS – EMS – BAS System Variables. Modine Manufacturing Atherion MPR | Manualzz

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables

Read/

Write

Carel Side

Variable Name

Data

Type

BACNet

Carel

Index

Description

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Return Air

Humidity

Space

Temperature

Building

Pressure

Mixed Air

Temperature

Return Air

Temperature

Liquid Line

Pressure

Outside Air

Humidity

Suction

Pressure

Sensor

Outside Air

Temperature

Supply

Temperature pAD

Temperature

Setpoint

Duct Static

Pressure

Neutral Air

Temperature

Setpoint

Outdoor

Dewpoint

Setpoint

Supply Air

Cooling Setpoint

Supply Air

Heating

Setpoint

Unoccupied

Heating

Setpoint

Cooling

Unoccupied

Setpoint

NA Heating

Changeover

NA Cooling

Changeover

(continued next page)

R

R

R

R

R

R

R

R

R

R

R

Ret_Air_Hum pAD_Temperature1

Build_Press

Mixed_temp return_temp

LL_Press

OA_hum

LP_sensor

OA_Temp supply_temp

R/W pAD_Setp_Temp

Static_Pressure

R/W na_setpt

R/W OA_Dp_Sp

R/W space_cl_sa_sp_oc

R/W space_ht_sa_sp_oc

R/W space_ht_sa_sp_unoc

R/W space_cl_sa_sp_unoc

R/W NA_Heating_Lockout

R/W NA_Cooling_Lockout

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

A

MCP15-525.0

AV1

AV2

AV3

AV4

AV5

AV6

AV7

AV8

AV9

AV10

AV11

AV12

AV13

AV14

AV15

AV16

AV17

AV18

AV19

AV20

BMS Side

LonWorks nvoSpaceTemp nvoLLPress nvoOutAirHum nvoSucPress nvoOutAirTemp nvoSupAirTemp nvo/nviSpaceTempSetC nvo/nviSupAirCoolSet nvo/nviSupAirHeatSet

SNVT temp_p count lev_percent count temp_p temp_p temp_p temp_p temp_p

87

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Read/

Write

Carel Side

Variable Name

Data

Type

BACNet

Carel

Index

Description

21

22

23

24

25

26

27

28

29

35

36

37

38

39

Suction

Pressure

Setpoint

ERM Entering

(True Outside)

Humidity

ERV Entering

(ERM True

Outside)

Temperature

Actual Supply

Air Setpoint

Space Heating

Setpoint

Heat Setpoint =

Cool Setpoint

Minus Diff

The OA Temp

ERM Econ

Mode is

Disabled

Unoccupied

Dehum Dew

Point Set Point

Supply Fan

Speed Adjust

Liquid Line pressure converted to temperature

Liquid Line

Temperature

Subcool

Superheat

Compressor

Discharge

Temperature

(continued next page)

R/W LP_Sp

R

R

R

R

R

R

R

R

R

Ent_Hum

Ent_Temp sa_setpt space_ht_sp

R/W Heat_Offset

R/W Erv_Wheel_econ_lock

R/W Un_Dehum_DP_SP

R/W Sup_Fan_Adj

LL_Press_T

LL_temp

Subcool

A10_SH_SH

Discharge_Temp

A

A

A

A

A

A

A

A

A

A

A

A

A

A

AV21

AV22

AV23

AV24

AV25

AV26

AV27

AV28

AV29

AV35

AV36

AV37

AV38

AV39

BMS Side

LonWorks nvoErmOaHum nvoErmOaTemp nvoSpaceTempSetH nvo/nviSpaceSetDiff

SNVT lev_percent temp_p temp_p temp_p

88 MCP15-525.0

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Carel

Index

1

Description

Space Humidity

2

3

4

Space Humidity

Setpoint

Space CO2

Level

Space CO2

Setpoint

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Compressor

Modulation

Condenser Fan

Modulation

Hot Gas Reheat

Modulation

Gas or Electric

Heat Modulation

Supply Fan

Modulation

Exhaust Fan

Modulation

20kw

Supplementary

Electric Heat

Modulation

ERM Exhaust

Fan Modulation

ERM Wheel

Modulation

Outside Air

Damper Position

Cooling

Demand

Dehumidification

Demand

Heat Demand

Outsdie Air

Minimum Open

Position

Unit Mode: 0=

(Blank)

Venting= 1

Heating= 2

Cooling= 3

Return Air

Damper Position

Occupied

Display

Read/

Write

R

Carel Side

Variable Name pAD_hum

R/W

R

R/W

R

R

R

R

R

R

R

R

R

R

R

R

R

R/W

R

R

R pAD_Setp_Humid

CO2

CO2_SP

Comp_mod_disp

Cond_fan_mod_disp

HGRH_mod_disp

Heat_mod_disp

Supply_Fan_Mod_Disp

Ex_Fan_Mod_Disp

AO1_pCOe_disp

ERV_Exh_Fan_Spd_Disp

Wheel_Spd_Disp

Damper

Cooling_demand_disp

Dehum_Demand_disp

Heat_demand_disp

Min_damp_open

Mode ra_damper

Occupied_disp

(continued next page)

Data

Type

I

BACNet

AV1001

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

AV1002

AV1003

AV1004

AV1005

AV1006

AV1007

AV1008

AV1009

AV1010

AV1011

AV1012

AV1013

AV1014

AV1015

AV1016

AV1017

AV1018

AV1019

AV1020

AV1021

MCP15-525.0

BMS Side

LonWorks nvoSpaceHum nvo/nviSpaceHumSet nvoSpaceCO2 nvo/nviSpaceCO2Set nvoOADampPoss nvoCoolDemand nvoHeatDemand nvo/nviOADampMin nvoUnitMode nvoRADampPoss

SNVT count count count count count count count count count

89

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Carel

Index

Description

22

23

24

25

26

27

30

31

32

80

81

82

83

84

Enthalpy

Lockout 0=

None, 1= Comp

1, 2= Comp 2,

3= Comp 1 and

2

1=UNIT ON,

2=OFF by

ALARM, 3=OFF by pLAN, 4=

OFF by BM,

5=OFF by

CLOCK,

6=OFF-

DIGITALIN,

7=OFF-

KEYPAD, 10=

OFF-DEMAND,

12=OFF-OPEN

DOOR,

15=WAIT SUP

FAN, 16=WAIT-

DAMPER

Compressor 1

Enthalpy

Lockout

Setpoint

Compressor 2

Enthalpy

Lockout

Setpoint

Space

Unoccupied

Dehum Humidity

Setpoint

Loop Delay

From Heating to

Cooling

Alarm Code

Number variable

1

Alarm Code

Number variable

2

Alarm Code

Number variable

3

Current day

Current month

Current year

Current hour

Current minute

(continued next page)

Read/

Write

Carel Side

Variable Name

R

R

Enthalpy_Lockout

UnitStatus

R/W Comp1_Enth_Lock_Out

R/W Comp2_Enthalpy_Lock_Out

R/W Un_Dehum_Hum_SP

R/W Heat_Cool_CO_Delay

R

R

R

R

R

R

R

R

Alarm_Code

Alarm_Code_2

Alarm_Code_3

CURRENT_DAY

CURRENT_MONTH

CURRENT_YEAR

CURRENT_HOUR

CURRENT_MINUTE

Data

Type

BACNet

I

I

I

I

I

I

I

I

I

I

I

I

I

I

AV1022

AV1023

AV1024

AV1025

AV1026

AV1027

AV1030

AV1031

AV1032

AV1080

AV1081

AV1082

AV1083

AV1084

90 MCP15-525.0

BMS Side

LonWorks nvoUnitStatus nvoAlrCode1 nvoAlrCode2 nvoAlrCode3

SNVT count count count count

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Read/

Write

Carel Side

Variable Name

Data

Type

BACNet

Carel

Index

Description

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

Unit On - Off

Control Switch

Supply Fan

Speed 2 Switch

Supply Fan

Speed 3 Switch

Compressor

Locked Out

Heating Locked

Out

Heat 3 Output

Heat 4 Output

Compressor 1

Output

Compressor 2

Output

High Pressure

Switch

Low Pressure

Switch

Supply Fan

Status Switch

Smoke Detector

Switch

Main Filter Dirty

Switch

Damper End

Switch

Occupied

Switch (Digital

Input)

EC3 Controller

Alarm Switch

Condensate

Pan Float

Switch

Main Gas Valve

1 On Switch

Mian Gas Valve

2 On Switch

Hot Water Coil

Freeze

Protection

Switch

Supply Fan

Door Switch

(continued next page)

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

HP_sw

LP_sw

Supply_fan_sw

Smoke_detector_sw

Filter_sw

Damper_end_sw

Occupied_sw

Digital_comp_sw

Cond_float_sw

Gas_valve1_sw

Gas_valve2_sw

Freeze_stat_sw door_sw

Dig_In_OnOff

DI_Sup_Fan_Speed2

DI_Sup_Fan_Speed3

DX_Cooling_Lockout

Heating_Lockout

Heat_3

Heat_4

C1_On

C2_On

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

MCP15-525.0

BV1

BV2

BV3

BV4

BV5

BV6

BV7

BV8

BV9

BV10

BV11

BV12

BV13

BV14

BV15

BV16

BV17

BV18

BV19

BV20

BV21

BV22

BMS Side

LonWorks nvoHPSwitch nvoLPSwitch nvoAirFlowSwitch nvoFilterDirty nvoSmokeAlarm nvoDamperSwitch nvoDigCompAlarm nvoCondFltSwitch nvoDoorSwitch nvoComp1 nvoComp2 switch switch switch

SNVT switch switch switch switch switch switch switch switch

91

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Carel

Index

Description

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

Outside Air

Damper

Opening

Outside Air

Damper Closing

Supply Fan

Output

Condenser Fan

Output

Heat 1 Output

Heat 2 Output

Hot Gas Reheat

Stage 2 Output

Gas Heat 1

Exhaust Fan Hi

Speed Output

Gas Heat 2

Exhaust Fan Hi

Speed Output

Hot Gas Reheat

Close Off Valve

Output

Return Air

Damper

Opening

Return Air

Damper Closing

Exhaust Fan

Output

General Alarm

Output

Occupied Mode

0= Unoccupied

1= Occupied

BMS Occupied

Comand

Alarm Reset by

BMS Comand

Unit is in Manual

Mode

BMS On-Off

Comand

ERM High

Wheel Pressure

Drop Switch

(continued next page)

Read/

Write

Carel Side

Variable Name

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

Gas_Heat_1_On

Gas_Heat_2_On

R/W Occupied_Bms

R/W BMS_Reset

R

R/W Superv_OnOff

R oa_damper_open oa_damper_close

Supply_fan_out

Cond_fan

HGRH_S2 ht_exh_fan_1 ht_exh_fan_2

HGRH_CV ra_damper_open ra_damper_close

Ex_Fan

General_Alarm

Occupied

Manual_OnOff

Wheel_P_SW

Data

Type

BACNet

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

BV23

BV24

BV25

BV26

BV27

BV28

BV29

BV30

BV31

BV32

BV33

BV34

BV35

BV36

BV37

BV38

BV39

BV40

BV41

BV42

BMS Side

LonWorks nvoSupFan nvoCondFan nvoHeat1 nvoHeat2 nvoExhustFan nvoGenAlarm nvoOccupied nviOccComand nviAlarmReset nviOnOffComand

92 MCP15-525.0

SNVT switch switch switch switch switch switch switch switch switch switch

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Carel

Index

Description

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

ERM Filter

Switch (Supply or Return)

ERM Exhaust

Fan Status

Switch

ERM Exhaust

Fan Door Switch

ERM Wheel

Output

ERM By-Pass

Damper Output

ERM Filter

Alarm

ERM Exhaust

Fan Output

ERM Preheater

Output

ERM Wheel

Status

Compressor

High Pressure

Alarm

Compressor

Low Pressure

Alarm

Supply Fan

Alarm

Supply Fan Duct

Static Pressure

Alarm

Condensate

Pan Float

Switch Alarm

Gas Valve 1

Alarm

If the Supply Air

Temp Does not

Rise above 36F

(Adjustable) after the blower comes on

59

60

Gas Valve 2

Alarm

Unit Shut Down

Due to Low

Supply Air

Temperature

(continued next page)

Read/

Write

Carel Side

Variable Name

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

R

ERV_Filter_SW

ERV_Exh_Fan_Stat

ERV_Door_SW

Wheel_on

Bypass_Damp mERV_Filter_AL

ERV_Exh_Fan_En

ERV_Preheater_En

ERV_Wheel_Status mHP_alarm mlp_alarm mSupply_fan_sw_al

Sup_Fan_DSP_AL mCFS_AL mGas_Valve1_al

SA_Low_Limit_Temp_AL mGas_Valve2_al mSA_Lockout

Data

Type

BACNet

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

D

BV43

BV44

BV45

BV46

BV47

BV48

BV49

BV50

BV51

BV52

BV53

BV54

BV55

BV56

BV57

BV58

BV59

BV60

MCP15-525.0

BMS Side

LonWorks nvoErmDoorSw nvoErmWheel nvoExhFan

SNVT switch switch switch

93

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

Typical BMS – EMS – BAS System Variables (continued):

Carel

Index

Description

Read/

Write

Carel Side

Variable Name

Data

Type

BACNet

61

62

63

64

65

66

67

68

69

Digital

Compressor

Switch Alarm

Exhaust Fan

Status Switch

Compressor

Alarm Shuts

Down Unit

Compressor

Alarm Shuts

Down Unit

Selection

Exhaust Fan

Alarm memory

Exhaust Fan

Shutdown

Wheel Alarm memory Wheel

Shut Down

ERM Wheel

Pressure Drop

Alarm

R

R

R

R

R

R

R

R

R mDCS_AL

Exhaust_Fan_Switch

DX_Cooling_Alarm_Unit_Shutdown

DX_Cooling_Alarm_Unit_SD_Sel mExh_Fan_AL mExh_Fan_SD mWheel_AL mWheel_SD mWheel_Press_AL

D

D

D

D

D

D

D

D

D

BV61

BV62

BV63

BV64

BV65

BV66

BV67

BV68

BV69

BMS Side

LonWorks SNVT

94 MCP15-525.0

MODINE CONTROL SYSTEM MANUAL

Models MPR & ERM

MCP15-525.0 95

Modine Manufacturing Company has a continuous product improvement program, and therefore reserves the right to change design and specifications without notice.

Commercial Products Group

Modine Manufacturing Company 1500 DeKoven Avenue • Racine, Wisconsin, USA 53403

Phone: 1.800.828.4328 (HEAT)

• www.modinehvac.com

© Modine Manufacturing Company 2012 MCP15-525.0

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement

Table of contents