Horizontal Left (Supply-Air Discharge) Applications. Bryant 345MAV, Series F
Add to My manuals44 Pages
advertisement
2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection.
3. Connect collector box pressure tube (green label) to pressure switch connection labeled "collector box."
4. Use remaining smaller diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (pink label) which was previously connected to pressure switch.
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
E.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
IV.
HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE)
APPLICATIONS
A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.
NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 10.) See Electrical
Connection section for J-Box relocation.
A.
Condensate Trap Location
The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 10.
To relocate condensate trap from the blower shelf to desired location, perform the following:
PLUG
CAP
AUXILIARY " J " BOX
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.
WARNING: Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated.
Failure to follow this warning could result in electrical shock, fire, personal injury or death.
4. Install condensate trap into casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).
B.
Condensate Trap Tubing
NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.
1. Collector Box Drain Tube a. Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp (factorysupplied in loose parts bag) to drain tube coupling, extending collector box drain tube.
c. Route extended tube (blue label) to condensate trap and cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
COLLECTOR BOX
DRAIN TUBE
(BLUE AND WHITE STRIPED)
CONDENSATE
TRAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR
BOX EXTENSION
DRAIN TUBE
COLLECTOR BOX
EXTENSION TUBE
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
040, 060, AND 080 HEATING INPUT FURNACES
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
DRAIN TUBE (BLUE)
Fig. 10—Horizontal Left Tube Configuration
—9—
A00215
COMBUSTION–AIR
INTAKE
A 3-IN. MINIMUM CLEARANCE
TO COMBUSTION-AIR INTAKE
IS REQUIRED.
VENT
30-IN. MIN
WORK AREA
A 12-IN. MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT) VENT SYSTEMS
TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
5 3 ⁄ 4
″
MANUAL
SHUTOFF
GAS VALVE
ACCESS OPENING
FOR TRAP
SEDIMENT
TRAP
DRAIN
CONDENSATE
TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
C.
A96184
2. Inducer Housing Drain Tube
Fig. 11—Attic Location and Working Platform
Modify tube as described below.
a. Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
b. Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to the condensate trap.
2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.
3. Route extended tube: c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
a. Behind inducer housing.
b. Between blower shelf and inducer housing.
c. Behind inducer motor bracket.
d. Between inducer motor and pressure switch.
3. Relief Port Tube a. Use smaller diameter tube (factory-supplied in loose parts bag) to extend collector box tube (green label) which was previously connected to the condensate trap.
4. Determine appropriate length, cut, and reconnect tube to pressure switch connection labeled COLLECTOR BOX.
b. Route extended collector box pressure tube to relief port connection on the condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
E.
Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommendations and procedures.
Condensate Trap Field Drain Attachment
Refer to Condensate Drain section for recommendations and procedures.
F.
Construct a Working Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 11.)
D.
Pressure Switch Tubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the pressure switch in
HORIZONTAL LEFT applications.
NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.
CAUTION: The condensate trap MUST be installed below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. Failure to follow this caution will result in intermittent unit operation.
NOTE:
Table 6.)
Vent pipe length is restricted to a minimum of 5 ft. (See
—10—
advertisement
Related manuals
advertisement
Table of contents
- 2 DIMENSIONAL DRAWING
- 3 SAFETY CONSIDERATIONS
- 3 Clearances to Combustibles
- 4 CODES AND STANDARDS
- 5 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
- 5 INTRODUCTION
- 5 APPLICATIONS
- 5 General
- 6 Upflow Applications
- 7 Downflow Applications
- 9 Horizontal Left (Supply-Air Discharge) Applications
- 11 Horizontal Right (Supply-Air Discharge) Applications
- 12 LOCATION
- 12 General
- 13 Furnace Location Relative to Cooling Equipment
- 13 Hazardous Locations
- 13 AIR FOR COMBUSTION AND VENTILATION
- 13 General
- 14 Unconfined Space
- 14 Confined Space
- 15 INSTALLATION
- 15 Leveling Legs (If Desired)
- 17 Installation In Upflow or Downflow Applications
- 17 Installation In Horizontal Applications
- 17 Air Ducts
- 17 General Requirements
- 17 Ductwork Acoustical Treatment
- 17 Supply Air Connections
- 18 Return Air Connections
- 18 Filter Arrangement
- 19 Bottom Closure Panel
- 19 Gas Piping
- 20 Electrical Connections
- 21 115-v Wiring
- 21 24-v Wiring
- 22 Accessories
- 22 Venting
- 22 Vent Systems
- 23 Combustion-Air and Vent Piping
- 31 Vent Termination
- 31 Multiventing
- 31 Condensate Drain
- 31 General
- 33 Application
- 33 Condensate Drain Protection
- 33 SAFETY CHECK
- 33 General
- 34 Prime Condensate Trap With Water
- 34 Purge Gas Lines
- 34 Sequence of Operation
- 34 Heating Mode
- 35 Cooling Mode
- 35 Continuous Blower Mode
- 35 Heat Pump Mode
- 35 Component Test
- 36 Adjustments
- 36 Set Gas Input Rate
- 40 Set Temperature Rise
- 41 Blower Off Delay (Heat Mode)
- 41 Set Thermostat Heat Anticipator
- 41 Check Safety Controls
- 41 Check Primary Limit Control