GENERATOR OUTPUTS/GAUGE READING

Maximum Amps

Table 10 shows the maximum amps the generator can provide. DO NOT exceed the maximum amps as listed.

Table 10. Generator Maximum Amps

Model

Rated Voltage

DCA400SSI

Maximum Amps

Single Phase 120 Volt 888.9 amps (4 wire)

Single Phase 240 Volt 444.4 amps (4 wire)

Three Phase 240 Volt

Three Phase 480 Volt

962.3 amps

481.1 amps

Figure 14. AC Voltmeter

Change-Over Switch

Figure 16. AC Ammeter

Change-Over Switch

HOW TO READ THE OUTPUT TERMINAL GAUGE

The AC ammeter and AC voltmeter change-over switches on the control panel DO NOT effect the generator output.

They are provided to help observe how much power is being supplied, produced at the UVWO terminals lugs.

When the voltage change-over board is jumpered for 3Ø,

240V operation (See Figures 14 and15), place the AC

Voltmeter Change-Over Switch (See Figures 16 and 17) to the W-U position and the AC Ammeter Change-Over

Switch (Figure 16) to the U or W position to read the output on the selected leg.

Figure 15. AC Voltmeter

Gauge (Volt reading on

W-U Lug)

Figure 17. AC Ammeter

(Amp reading on U lug)

NOTICE

The ammeter gauge will only show a reading when the Output Terminal Lugs are connected to a load and in use.

Figure 13. Voltage Change-Over Board 240V

Confi guration

DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08) — PAGE 27