OUTPUT TERMINAL PANEL CONNECTIONS
UVWO TERMINAL OUTPUT VOLTAGES
Various output voltages can be obtained using the UVWO output terminal lugs. The voltages at the terminals are dependent on the placement of the jumpers plates (6) on the Voltage Change-Over Board and the adjustment of the Voltage Regulator Control Knob.
Remember the voltage change-over board determines the
range of the output voltage and can be confi gured in two different positions that provide 6 different output voltages at the UVWO output terminals. The generator is shipped from the factory in the 240V confi guration. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.
3Ø-240V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 240V operation as shown in Figure 18.
3. Turn the voltage regulator knob (Figure 20) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fi ne tuning of the output voltage is required
Figure 20. Voltage Regulator Knob
1Ø-240V UVWO Terminal Output Voltages
1.
2.
Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 18.
Connect the load wires to the UVWO terminals as shown in Figure 21.
Figure 18. Voltage Change-Over Board 240V
Confi guration
2. Connect the load wires to the UVWO terminals as shown in Figure 19.
Figure 21. UVWO Terminal Lugs 1Ø-240V
Connections
1Ø-120V UVWO Terminal Output Voltages
1.
2.
3.
Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 18.
Adjust voltage regulator knob (Figure 20) for an output of 208V to obtain 120V at the UVWO terminals.
Connect the load wires to the UVWO terminals as shown in Figure 22.
Figure 19. UVWO Terminal Lugs
Figure 22. UVWO Terminal Lugs
1Ø-120V
Connections
PAGE 28 — DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08)
OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480V UVWO Terminal Output Voltages
1. Jumper the voltage change-over board for 480V operation as shown in Figure 23. This confi guration uses 6 jumper plates in 3 different positions. Remember there are 2 jumper plates at every position. Every jumper plate must be used.
1Ø-480V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 23.
2. Connect the load wires to the UVWO terminals as shown in Figure 25.
Figure 23. Voltage Change-Over Board 480V
Confi guration
2. Connect the load wires to the UVWO terminals as shown in Figure 24.
Figure 25. UVWO Terminal Lugs 1Ø-480V
Connections
1Ø-277V UVWO Terminal Output Voltages
1. Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 23.
2. Connect the load wires to the UVWO terminals as shown in Figure 26.
Figure 24. UVWO Terminal Lugs 3Ø-480V
Connections
NOTICE
ALWAYS make sure that the connections to the UVWO terminals are secure and tight. The possibility of arcing exists, that could cause a fi re.
Figure 26. UVWO Terminal Lugs 1Ø-277V
Connections
DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08) — PAGE 29
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Proposition 65 Warning
- 3 Reporting Safety Defects
- 4 Table Of Contents
- 5 Parts Ordering Procedures
- 6 Safety Information
- 12 Specifi cations
- 13 Dimensions
- 14 Installation
- 16 General Information
- 17 Major Components
- 18 Generator Control Panel
- 20 Engine Operating Panel
- 22 Output Terminal Panel Familiarization
- 25 Load Application
- 26 Generator Outputs
- 27 Gauge Reading
- 28 Output Terminal Panel Connections
- 30 Inspection/Setup
- 34 Generator Start-Up Procedure (Manual)
- 36 Generator Start-Up Procedure (Auto Mode)
- 37 Generator Shut-Down Procedures
- 38 Maintenance
- 42 Trailer Maintenance
- 46 Trailer Wiring Diagram
- 47 Generator Wiring Diagram
- 48 Engine Wiring Diagram
- 49 Controller Wiring Diagram
- 50 Troubleshooting (Generator)
- 51 Troubleshooting (Engine Controller)
- 52 Troubleshooting (Diagnostic Lamp)
- 54 Explanation Of Code In Remarks Column
- 55 Suggested Spare Parts
- 56 Generator Assembly
- 60 Engine Operating Panel Assembly
- 62 Control Box Assembly
- 68 Engine And Radiator Assembly
- 72 Output Terminal Assembly
- 74 Battery Assembly
- 78 Fuel Tank Assembly (S/N 3813334 & Below)
- 80 Fuel Tank Assembly (S/N 3813335 & Above)
- 82 Enclosure #1 Assembly
- 84 Enclosure #2 Assembly
- 86 Enclosure #3 Assembly
- 90 Rubber Seals Assembly
- 92 Nameplate And Decals Assembly
- 96 Terms And Conditions Of Sale — Parts