OUTPUT TERMINAL PANEL CONNECTIONS

UVWO TERMINAL OUTPUT VOLTAGES

Various output voltages can be obtained using the UVWO output terminal lugs. The voltages at the terminals are dependent on the placement of the jumpers plates (6) on the Voltage Change-Over Board and the adjustment of the Voltage Regulator Control Knob.

Remember the voltage change-over board determines the

range of the output voltage and can be confi gured in two different positions that provide 6 different output voltages at the UVWO output terminals. The generator is shipped from the factory in the 240V confi guration. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.

3Ø-240V UVWO Terminal Output Voltages

1. Jumper the voltage change-over board for 240V operation as shown in Figure 18.

3. Turn the voltage regulator knob (Figure 20) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fi ne tuning of the output voltage is required

Figure 20. Voltage Regulator Knob

1Ø-240V UVWO Terminal Output Voltages

1.

2.

Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 18.

Connect the load wires to the UVWO terminals as shown in Figure 21.

Figure 18. Voltage Change-Over Board 240V

Confi guration

2. Connect the load wires to the UVWO terminals as shown in Figure 19.

Figure 21. UVWO Terminal Lugs 1Ø-240V

Connections

1Ø-120V UVWO Terminal Output Voltages

1.

2.

3.

Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 18.

Adjust voltage regulator knob (Figure 20) for an output of 208V to obtain 120V at the UVWO terminals.

Connect the load wires to the UVWO terminals as shown in Figure 22.

Figure 19. UVWO Terminal Lugs

Figure 22. UVWO Terminal Lugs

1Ø-120V

Connections

PAGE 28 — DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08)

OUTPUT TERMINAL PANEL CONNECTIONS

3Ø-480V UVWO Terminal Output Voltages

1. Jumper the voltage change-over board for 480V operation as shown in Figure 23. This confi guration uses 6 jumper plates in 3 different positions. Remember there are 2 jumper plates at every position. Every jumper plate must be used.

1Ø-480V UVWO Terminal Output Voltages

1. Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 23.

2. Connect the load wires to the UVWO terminals as shown in Figure 25.

Figure 23. Voltage Change-Over Board 480V

Confi guration

2. Connect the load wires to the UVWO terminals as shown in Figure 24.

Figure 25. UVWO Terminal Lugs 1Ø-480V

Connections

1Ø-277V UVWO Terminal Output Voltages

1. Make sure the voltage change-over board is jumpered for 480V operation as shown in Figure 23.

2. Connect the load wires to the UVWO terminals as shown in Figure 26.

Figure 24. UVWO Terminal Lugs 3Ø-480V

Connections

NOTICE

ALWAYS make sure that the connections to the UVWO terminals are secure and tight. The possibility of arcing exists, that could cause a fi re.

Figure 26. UVWO Terminal Lugs 1Ø-277V

Connections

DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08) — PAGE 29