5. Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
Indoor power cord
Remote controller cord
Control box cover
[Air inlet side view]
3Phase
36K/48K/54K
Heat Pump Model.
R S T N
Control box cover fitting screw(2 units)
Terminal Block of Outdoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Indoor Unit
1(L) 2(N) 3 4 5
POWER INPUT
3Phase
36K/48K/54K
Cooling Model Only.
R S T N
POWER INPUT
L N
1Phase
28K/36K
Heat Pump Model.
POWER INPUT
L N
1Phase
28K/36K
Cooling Model Only.
1Phase
18K/24K
Heat Pump Model.
POWER INPUT
Terminal Block of Indoor Unit
3(L) 4(N) 5 6 7
Terminal Block of Outdoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Outdoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Outdoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Indoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Indoor Unit
1(L) 2(N) 3 4 5
Terminal Block of Indoor Unit
1(L) 2(N) 3 4 5
1(L) 2(N)
Terminal Block of Outdoor Unit
3(L) 4(N) 5 6 7 8
Power Cord
1Phase
18K/24K
Cooling Model.
Terminal Block of Indoor Unit
3(L) 4(N) 5 6 7 1(L) 2(N)
Terminal Block of Outdoor Unit
3(L) 4(N) 5 6 7 8
Power Cord
(LT-E24
**
CL Only)
CAUTION
The power cord connected to the outdoor unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR
or SAA).
Capacity 1 Phase 3 Phase
The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
GN/YL
20mm
18, 24, 28, 30K
BTU/h
36K BTU/h
48, 54K BTU/h
2.5mm
2
5.5mm
2
-
-
2.5mm
2
3.5mm
2
GN/YL
20mm
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
(18K/24K/36K)
1.25mm
2
(48K/54K)
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
WARNING
Make sure that the screws of the terminal are free from looseness.
8
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 1.The following should be always observed for safety
- 4 2.Installation of Indoor, Outdoor Unit
- 4 1) Selection of the best location
- 5 bolt location(unit: mm)
- 6 3) The Indoor Unit Installation
- 6 4) Remote Controller Installation
- 8 5) Wiring Connection
- 9 ELECTRICAL WIRING
- 9 CONNECTING THE CABLE TO OUTDOOR UNIT
- 10 6) Connecting Pipes to the Indoor Unit
- 11 PIPING CONNECTION
- 12 7) Installation of Decorative Panel
- 13 8) Indoor Unit Drain Piping
- 14 HEAT INSULATION
- 14 FORM THE PIPINGS
- 15 3. Test running
- 15 1) PRECAUTIONS IN TEST RUN
- 15 INSTALLATION IS COMPLETE
- 16 2) Connection of power supply
- 16 3) Evaluation of the performance
- 17 4. Auxiliary operation
- 17 1) Two thermistor system
- 18 2) Ajusting to the height of ceiling
- 19 3) Group control (optional wiring)
- 20 4) Central control (optional)