APEX CBT
INSTALLATION INSTRUCTIONS
GENERAL
INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER
Please take time to read these instructions thoroughly. Not following the instructions could result in a faulty installation causing serious problems. Along with these general instructions you must follow the specifi c instructions which pertain to your particular installation i.e.: add-on to electric, gas, oil or independent installations.
FREIGHT DAMAGE
its arrival. If damage is found report it to the carrier and then immediately fi le a freight damage claim. Blaze King will not be held responsible for damage incurred once the product leaves our factories.
PARTS INCLUDED WITH THE APEX CBT
1. 2 Fan limit controls and bracket
3. Rake
5. Insulation strips (3 pieces)
6. Digital Combustor thermometer
OPTIONAL EQUIPMENT
1. Blower and cabinet for independent use (900 cfm. to 1200 cfm.), see “VB1000 BLOWER” on page 24.
2. 24 volt control transformer
USAGE
1. An add-on to any of the following furnaces:
A. An electric forced air furnace rated at 15 KW to 27 KW with a minimum size fan of 900
cfm. (see “INSTALLATION INSTRUCTIONS - Combination APEX-Electric” on page 19)
B. A forced air gas furnace with a maximum output of 120,000 btu. and a minimum size fan
of 900 cfm. (see “INSTALLATION INSTRUCTIONS - Combination APEX-Gas/Oil” on page
C. An oil furnace having an oil input as shown on the nameplate of not more than 1.2 usgph.
and a fan capacity of not less than 900 cfm. (see “INSTALLATION INSTRUCTIONS -
Combination APEX-Gas/Oil” on page 21)
2. As an independent forced air wood furnace equipped with a blower of not less than 900
cfm. Capacity (see “INSTALLATION INSTRUCTIONS - Wood only” on page 23).
Page 9
OM-APEX E V1.06
November 19, 2012
Page 10
APEX CBT
INSTALLATION INSTRUCTIONS cont.
CAUTIONS
properly sized and fi tted according to the installation codes. Upstream of the supply connection, the fi tter shall provide a manual shut-off valve.
1. All installations must comply with local building safety codes.
2. Installation shall be by a licensed, qualifi ed installer experienced in heating equipment installations.
3. THE WOOD SECTION MUST BE VENTED INTO A CHIMNEY APPROVED FOR SOLID FUEL
USE IN GOOD CONDITION. MOST GAS FURNACES ARE VENTED INTO “B” VENTS, THIS
IS UNACCEPTABLE FOR SOLID FUEL APPLIANCES. THE APEX CBT MUST NOT BE
VENTED INTO ANY TYPE OF CHIMNEY THAT ALSO SERVES ANOTHER APPLIANCE.
4. DO NOT CONNECT THE DUCT WORK SO REVERSE OR PARALLEL FLOW IS POSSIBLE.
5. DO NOT RELOCATE ANY OF THE CONTROLS ON THE ORIGINAL OR ALTERNATE
FURNACE.
6. Ensure that all existing or alternate furnace systems are in good operating condition before installing the add-on. Always maintain required clearances from the existing or alternate furnace.
Blaze King supports the WETT ( Wood Energy Technology Transfer Inc, Canada) & NFI (National Fireplace and maintenance of wood heating systems.
CLEARANCES TO COMBUSTIBLES
WOOD CHARGING END (DOOR) 48 in. (1220 mm)
ONE SIDE (A) 6 in. (150 mm)
OTHER SIDE
BACK (B)
18 in. (460 mm)
3.5 in. (90 mm)
PLENUM & FIRST 2 FT (0.6 M) OF DUCT
FLUE (D*)
FLUE (C)
1 in. (25 mm)
10* in. (250 mm)
18 in. (460 mm) IN CANADA
*check with local codes, 18” may be required for single wall pipe*
Fig. 1a
If the furnace sits on a combustible fl oor, a non-combustible shield must be used underneath the furnace and extending 18 in. out from the charging end and 8 in. on either side of the fuel-loading door. A non-combustible shield is also required underneath the chimney connector and extending at least 2 in. on either side of the chimney connector. (minimum size fl oor protector= 65” x 31.5”)
It is not required to be a heat protective covering.
This furnace must be installed in compliance with all local codes and regulations.
OM-APEX E V1.06
November 19, 2012
APEX CBT
INSTALLATION INSTRUCTIONS cont.
Page 11
Fig. 1b
Can be as little as 6” but 8” is recommended for easier access to the bypass handle
FURNACE LOCATION
installation. Ceiling height of the furnace room needs to be a minimum of
6’ 6”(1.98 M). Hot air Plenum and Duct work can only run Horizontally or Up, NEVER down.
12 in. x 17 in. typical installations see fi g. 3.
alternate furnace is located. Cut the opening max. 1 1/2 inches from the fl oor and locate close to the front, about
Note the bypass handle is located on the left side of the Apex, but can be moved to the right side, this might be required in some installations to clear return air plenum or counter fl ow on existing or alternate furnace. See
“INSTALLATION INSTRUCTIONS cont.” on page 14 for instructions.
OM-APEX E V1.06
November 19, 2012
Page 12
HOT AIR TO HOUSE
ALTERNATE
HOT AIR
PLENUM
GAS, OIL
ELECTIRC
UP FLOW
FURNACE
CBT
HOT AIR TO HOUSE
RETURN
AIR
PLENUM
COUNTER/
FLOW GAS
ELECTRIC
OR OIL
CBT
35 KIT
WARNING:
Hot air Plenum and
Duct work can only
LAYOUT
NEVER down.
Fig. 3 Typical installation illustration
INSTALLATION INSTRUCTIONS cont.
APEX CBT
HOT AIR TO HOUSE
ALTERNATE
HOT AIR
PLENUM
GAS, OIL
ELECTRIC
UP FLOW
FURNACE
EXISTING
CBT
HOT AIR SUPPLY
PLENUM
RETURN
AIR
COUNTER/
FLOW GAS
ELECTRIC
IT
PLENUM
ED
OR OIL
PR
WOOD COUNTERFLOW
INSTALLATION REQUIRES
CF6 KIT OPTION
NOTE
IN THIS CONFIGURATION
SPECIAL CLEARANCES APPLY
SEE CF6KIT INSTRUCTIONS.
DO NOT INSTALL IN THIS
CONFIGURATION WITHOUT
OM-APEX E V1.06
November 19, 2012
APEX CBT
Page 13
INSTALLATION INSTRUCTIONS cont.
Apex CBT as independent furnace:
When the blower is installed on the left side of the Apex CBT, the bypass handle needs to be moved to the right
side.
Install the blower more to the front of the unit as that is where most of the heat is. When using the VB1000 blower cut an opening 13 1/4” W x 11 13/16” H in the side panel about 9” from the front (Distance A, see fi g. opening that way. Use the pre-punched cutouts if applicable.
W
H
Casing
A
Fig. 4
Metal strip
Fig. 5
Insulation
DO NOT USE INTERCONNECT DUCT ELBOWS THAT HAVE AN INSIDE RADIUS OF LESS THAN
6” (150mm.). THE WARM-AIR SUPPLY OF THE APEX FURNACE SHALL NOT BE CONNECTED
TO THE COLD-AIR RETURN INLET OF THE EXISTING OR ALTERNATE FURNACE. THE
POSSIBILITY EXISTS THAT THE COMPONENTS OF THE EXISTING OR ALTERNATE FURNACE
MAY OVERHEAT, CAUSING THE CENTRAL FURNACE TO OPERATE OTHER THAN INTENDED.
COMBUSTION AIR
Insure adequate combustion air allowing for all other exhausting type appliances in the dwelling (range hoods, dryers, etc). In airtight houses it is recommended to install a fresh air inlet into the basement room where the furnace is located. Recommended intake size is 1.5 sq in
2 per 1000 BTU’s.
OM-APEX E V1.06
November 19, 2012
Page 14
APEX CBT
INSTALLATION INSTRUCTIONS cont.
MOVE BYPASS HANDLE SYSTEM FROM LEFT TO RIGHT SIDE FURNACE
In some installations it is necessary to move the bypass handle system from the left (default) to the right side of the right makes place for the bypass handle but need to be installed on the left aft er the change-over). Make sure to adjust the handle position and latch so proper seal is achieved on bypass door. Reroute wiring. Fig. 7 shows the correct mounting of the handle latches when moved to right side.
Fig. 6
Fig. 7
PRESSURE LOSS
Before any changes are made to the existing furnace system you must establish the working parameters of that system. You can then insure that addition of the add-on has not degraded the operation of the original system, and correct air fl ow will be maintained. Change all fi lters in the system to insure maximum free air fl ow. Using an accurate manometer check the static pressure at the end of a typical duct near the exit to the house. Check the static pressure in the plenum above the existing furnace also.
Pressure drop = Static pressure at furnace -(minus) static pressure at duct exit
Record the pressure drop of the original system.
Addition of the add-on furnace will add airfl ow resistance in the system. Aft er installation is complete measure the pressure drop in the same run measured before add-on installation. If the air fl ow has diminished the blower speed should be adjusted to compensate. When using a belted blower the pulley size should be changed or adjusted to speed up the blower. If the pulley size is adjusted measure the blower motor current to insure that it is still within the motor plate specifi cation. It may be necessary to replace the motor with a more powerful motor. If a direct drive blower is used change to a higher motor speed. Do not change the blower size.
OM-APEX E V1.06
November 19, 2012
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 INTRODUCTION
- 4 SPECIFICATIONS
- 5 APPLIANCE DIMENSIONS
- 6 PRODUCT INFORMATION
- 7 CERTIFICATION LABEL
- 8 SAFETY PRECAUTIONS
- 9 INSTALLATION INSTRUCTIONS
- 15 INSTALLATION INSTRUCTIONS - Venting
- 19 INSTALLATION INSTRUCTIONS - Combination APEX-Electric
- 21 INSTALLATION INSTRUCTIONS - Combination APEX-Gas/Oil
- 23 INSTALLATION INSTRUCTIONS - Wood only
- 24 VB1000 BLOWER
- 25 OPERATING INSTRUCTIONS
- 25 BYPASS
- 25 CATALYTIC MONITOR (THERMOMETER)
- 25 FUEL
- 26 AIR SETTINGS
- 26 THERMOSTATS
- 27 FAN OPERATION
- 27 LIGHTING THE FIRE
- 28 OPERATION DURING POWER FAILURE CONDITIONS
- 29 MAINTENANCE
- 29 ASHES
- 29 CATALYTIC COMBUSTOR REPLACEMENT
- 30 GASKET INSPECTION
- 30 LOADING DOOR GASKET REPLACEMENT
- 31 BYPASS DOOR GASKET REPLACEMENT
- 31 ADJUSTING BYPASS HANDLE
- 32 CREOSOTE
- 33 BRICK LAYOUT
- 34 REPLACEMENT PARTS
- 36 WARRANTY
- 40 NOTES