Features
1
1
Greatly suppressed power supply harmonics
The HC2 converters, being the self-excitation three-phase bridge circuit under "the Harmonic Suppression Guidelines for
Specific Consumers", take the conversion coefficient of the equivalent capacity (K5 = 0).
Harmonic Conversion Coefficient of the Equivalent Capacity
(Excerpt from the Guidelines Appendix)
Classification Circuit type
6-pulse converter
Conversion coefficient Application examples
K11 = 1 Railway substation
1
3
5
Three-phase bridge 12-pulse converter
24-pulse converter
Three-phase bridge
(smoothing capacitor)
Without a reactor
With a reactor (on AC side)
With a reactor (on DC side)
With reactors (on AC/DC sides)
Self-excitation three-phase bridge
K12 = 5.5
K13 = 0.25
K31 = 3.4
K32 = 1.8
K33 = 1.8
K34 = 1.4
K5 = 0
Electro-chemistry
Other
General-purpose inverter
Lift
Refrigerating air conditioner
Other
PWM converter
The waveform with high peaks, which is typical of inverter's input current, is reshaped to be a sine wave with lower input current effective values.
The lowered effective value enables adoption of smaller power-supply-side devices, such as a power supply transformer, MCCB, and cables.
Such smaller equipment saves the cost of equipment.
Power supply voltage
Input current
Power supply voltage
Input current
[Without FR-HC2] [With FR-HC2]
2
Power regeneration function for energy saving
The power regeneration function, which comes as a standard feature, eliminates the need for brake units. The power regeneration function gives a great breaking capability.
(Regeneration is available continuously with 100% torque, and for 60s with the maximum of 150% torque.)
The regenerative power from the motor is returned to the power source, and such a system significantly saves energy.
500
300
200
100
50
30
7.5K
15K 30K 55K
10
10 20 30 40 50 60 70 80
Short-time permissible regenerative power (kW)
[55K or lower]
3
Connectable to multiple inverters
Inverter
The common converter method enables the connection to up to
10 inverters.
*1
The power returned during regenerative driving can be supplied to another inverter, saving the overall energy.
FR-HC2
Max.10 units connectable
Inverter
*1 : Be sure to use a converter with the capacity higher than the total capacities of the inverters.
(Refer to page 8.)
Inverter
4
Compact design for space saving
The high power factor converters (excluding 15K) and input reactors (75K or higher) have become much smaller than their conventional models (FR-HC, MT-HC).
5
Long life parts and life diagnosis function
(1) Longer life parts
The service life of the cooling fans is now 10 years
*1
and that can be even longer with the ON/OFF control of the cooling fan.
Capacitors with a design life of 10 years *1*2 are adapted.
(Using a surrounding air temperature of 105˚C for 5000 hours). With these capacitors, the service life of the converter is further extended.
*1 : Surrounding air temperature: Annual average of 40ºC (free from corrosive gas, flammable gas, oil mist, dust and dirt).
The design life is a calculated value and is not a guaranteed product life.
*2 : Input current: 80% of the high power factor converter rating
Estimated service lifespan of the consumable parts
Part name
Cooling Fan
Estimated lifespan
10 years
Reference value by JEMA *3
2 to 3 years
Main circuit smoothing capacitor
Smoothing capacitors on the printed board
10 years
10 years
5 years
5 years
*3 : Excerpt from "The Periodic Inspection Recommendations on General-purpose
Inverters" by the Japan Electrical Manufactures Association (JEMA).
(2) The leading-edge life diagnosis function
The degree of deterioration of the main circuit capacitor, cooling fan, and inrush current limit circuit can be diagnosed on the monitor.
Using the self-diagnosis function, the part life warning can be output and the deterioration degree can be monitored. Thus, the self-diagnosis function prevents troubles from occurring.
*4 : A warning is output when any of the control circuit capacitor, inrush current limit circuit, and cooling fan reaches its output level.
6
Operation panel equipped with the setting dial
(FR-DU07-CNV)
7
Supporting more network protocols
Parameters can be copied using the operation panel
(FR-DU07-CNV).
The setting values of the parameters can be stored to the operation panel and the option parameter unit (FR-PU07).
Items such as input current, input voltage, input power (with the regenerative display), bus voltage, etc. can be monitored.
Operation can be easily performed with the setting dial.
HC2 supports RS-485 as a standard. With the option
FR-A7NC, HC2 also supports CC-Link.
•The power can be monitored during driving/regenerative driving, and this monitoring tells you the energy saving effect.
•Alarm functions and voltage monitors of each phase help you to spot the cause of the alarm.
FR-HC2 Inverter Inverter
Parameter change example
Programmable controller
Terminating resistor
FR-A7NC FR-A7NC
CC-Link dedicated cable
CC-Link network
FR-A7NC
Terminating resistor
Applications
[Ceiling crane]
G
Trolley line
Trolley line
IM
IM
Crane
IM G
W
Traveling wheel
Rail
Power supply
Standard accessories
High power factor converter
(FR-HC2)
Inverter
Inverter
Inverter
B
Traveling motor
B
Traveling motor
Hosting motor
B
•The power regeneration function is installed. A brake
unit is not required.
•The mechanical brake is powered from the power
supply side of the standard accessories.
[Water treatment plant (pump)]
Power supply
Standard accessories
High power factor converter
(FR-HC2)
Inverter
Inverter
•Power supply harmonics of inverters can be
suppressed.
•The power regeneration function is installed.
A brake unit is not required.
Motor
Motor
Protective Functions
Dimension Drawings
Extensive lineup
Model
F R - H C 2 - 7.5K
High power factor converter basic model name
Capacity (kW)
Three-phase 200V class
Three-phase 400V class
7.5
15
30
Symbol
No sign
H
55
Voltage
200V class
400V class
75
Symbol
7.5K to 560K
Applicable capacity
Represents the capacity kW.
110
−
160
−
220
−
280
−
400
−
560
−
: Available model −: Not available
Compatible with UL, cUL, EC Directives (CE marking) as standard.
Compliant with the RoHS Directive. Friendly to people and to the environment.
To obtain higher environmental resistance, the FR-HC2 has coated printed circuit boards and copper plated conductors.
Magnetic contactors also have anti-corrosive coatings on.
The coated printed circuit board model (FR-HC-K-60
)of the conventional series is replaceable with the standard model of this series.
[Note]
•These coating treatments do not guarantee an operation environment beyond the range indicated in the product specification.
•Coating is applied to the printed circuit board areas excluding its LEDs, connectors, terminal blocks and their peripherals, where coating cannot be applied.
•As for the anti-corrosive treatment of the magnetic contactor, plating is applied to the copper areas where no surface treatment is applied.
Standard accessories
Refer to page 6
High power factor converter
*1
(FR-HC2)
Reactor 1
(FR-HCL21)
Reactor 2
(FR-HCL22)
Outside box
(FR-HCB2)
*2
*1 : Use in combination with standard accessories. Cables for connecting standard accessories are not provided.
*2 : Peripheral devices are separately provided for 280K or higher (not provided as the outside box).
2
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 FR-HC2 catalog
- 2 Features
- 3 Connection example
- 4 Standard specification rating
- 5 Common specifications
- 6 Checking peripheral devices
- 7 Compatible inverter for the high power factor converter
- 8 Wiring of several inverters to one converter
- 9 Outline dimension drawings
- 13 Protruding the heatsink
- 15 Terminal connection diagram (when using with the FR-A700 series)
- 17 Terminal specifications
- 19 Parameter list
- 21 Protective functions
- 22 Option and peripheral devices
- 22 Option List
- 22 Peripheral devices/cable size list
- 25 Precaution on selection and operation
- 25 Installation Precautions
- 25 Wiring distance
- 25 Reactor installation at power supply side
- 25 Operating Precautions
- 25 Selection Precautions
- 25 Connectable inverter
- 25 Sine wave filter selection precautions
- 25 Peripheral Device SelectionPrecautions
- 25 Selection and installation of themoulded case circuit breaker
- 25 Electromagnetic interference
- 26 Warranty
- 26 Related Factory Automation Products