MITSUBISHI ELECTRIC
Low Voltage
Switchgears
Air Circuit Breakers
Air Circuit
Disconnectors
SUPER AE
AE 1000 –
AE 6300
Technical Catalogue
2004
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
New Items in this Catalogue
01/2004
The air circuit breaker program from MITSUBISHI ELECTRIC:
왘 Complete breaker program
Frame size from 1000 A to 6300 A
왘 Wide performance range
Standard version "SS" from 65 to 130 kA
High performance version "SH" with 130 kA
왘 High interrupting capacity
Growing power demands
왘 Optimum overload tripping system
Safer and more selectivity
Further Publications within the LVS, PLC and inverter range
Technical
Catalogues
WSS, PSS & Super Series Technical Catalogue
Product catalogue for circuit breakers and disconnectors from 3 A to 1600 A rated current (art no. 133207)
MS-N Technical Catalogue
Product catalogue for low voltage contactors and relays from 20 A to 1000 A rated current (art no. 62306)
PLC and Inverter Technical Catalogues
Product catalogues for programmable logic controllers and frequency inverters (more details on request)
Current information on updates, alterations, new items, and technical support you will find on MITSUBISHI ELECTRIC's web pages
(www.mitsubishi-automation.com).
In the products section of the MITSUBISHI home site various documentations of the whole product range by MITSUBISHI ELECTRIC as well as the current version of this catalogue on hand are available as download. The content is updated daily and to date is provided in German and English.
Due to the constantly growing product range, technical alteration, and new or changed characteristical features, this catalogue is updated frequently.
Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering the electronic air circuit breakers of the SUPER AE series and the associated accessories. Only the manuals supplied with the breakers are relevant for installation, commissioning and handling of the air circuit breakers and the accessories. The information given in this documentation must be read before installation and commissioning of the modules.
Should questions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact the german branch of the MITSUBISHI ELECTRIC EUROPE B.V. in Ratingen or one of its distributors (see cover page).
© MITSUBISHI ELECTRIC EUROPE B.V. 01/2004 (4th edition)
2
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
S
UPER
AE S
ERIES
BASE UNITS
ACCESSORIES
ELECTRONIC TRIP RELAY
SPECIFICATIONS
A
PPENDIX
CONTENTS
MITSUBISHI ELECTRIC
SUPER AE
3
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
BASE UNITS
Program Overview – Specifications
SUPER AE
Rated current (A) at 40 °C
햲
Rated insulation voltage (V) 50/60 Hz
Rated operating voltage (V) 50/60 Hz
Number of poles
Series
Breaker type AE 1000 - SS
I
N max
Ui
Ue
1000
1000
690
3 4
AE 1250 - SS
1250
1000
690
3 4
Standard series "SS"
AE 1600 - SS AE 2000 - SS
1600
1000
690
2000
1000
690
3 4 3 4
AE 2500 - SS
2500
1000
690
3 4
AE 3200 - SS
3200
1000
690
3 4
Ir
I
I
I
Rated current for neutral pole N breaking capacity
O-t-CO-t-CO
CS CU making capacity
Rated short time current (kA eff.) I
Maximum total breaking time
Closing time
Without inst. trip
With trip instantaneous trip
(with MCR)
Without inst. trip
CW
햳
햳
With rated current
Without rated current
AC690V
AC600V
AC500V
AC690V
1s
2s
3s
(sec)
(sec)
(A)
AC690V
AC600V
AC500V
AC690V
AC600V
AC500V
AC690V
AC690V
AC600V
AC500V a a
Fixed type
Drawout type
(with cradle)
Cradle only c c d d
Manual charging
Motor charging
Manual charging
Motor charging c a b a d b c d
40
30
0.04
0.08
5000
10000
88.2
105
143
52.5
65
500
≤
In
In
≤
≤
1000
1000
50
50
65
42
50
65
25
105
105
143
44
64
67
26
430
368
61
41
340
410
290
40
298
54
78
81
30
430
368
61
51
425
410
290
40
385
625
≤
In
≤
40
30
0.04
0.08
5000
10000
88.2
105
143
52.5
65
50
65
25
105
105
143
1250
50
50
65
42
44
64
67
26
430
368
61
41
340
410
290
40
298
1250
54
78
81
30
430
368
61
51
425
410
290
40
385
1000
≤
≤
In
≤
2000
65
65
0.04
0.08
1500
10000
105
143
143
94.5
65
65
65
45
105
143
187
2000
50
65
85
50
63
92
95
35
430
368
61
60
475
410
290
40
433
75
113
116
43
430
368
61
72
605
410
290
40
565
햲
햳
For further temperatures refer to technical information on page 48.
The figures for "without instantaneous tripping" are the values when the bare main body and the external relay are combined.
햴
햵
The number of operating cycles with rated current also include the number of operating cycles without rated current.
All specifications without peripheral accessories (e.g. UVT control unit).
햶
Further current ratings on request.
More details on request.
800
≤
In
≤
1600
60
50
0.04
0.08
5000
10000
88.2
105
143
52.5
65
50
65
25
105
105
143
1600
50
50
65
42
55
79
82
30
430
368
61
52
425
410
290
40
385
45
65
68
26
430
368
61
42
340
410
290
40
298
1600
≤
In
≤
3200
65
65
0.04
0.08
1000
10000
105
143
143
94.5
65
65
65
45
105
143
187
3200
50
65
85
50
66
95
98
36
430
368
61
63
475
410
290
40
433
78
116
119
44
430
368
61
75
605
410
290
40
565
1250
≤
In
≤
2500
65
65
0.04
0.08
1500
10000
105
143
143
94.5
65
65
65
45
105
143
187
2500
50
65
85
50
76
114
117
43
430
368
61
73
605
410
290
40
565
64
93
96
35
430
368
61
61
475
410
290
40
433
4
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
BASE UNITS
Standard series "SS"
AE 4000 - SSA AE 4000 - SSC AE 4000 - SS
High performance series "SH"
AE 5000 - SS AE 6300 - SS AE 1000 - SH AE 1250 - SH AE 1600 - SH AE 2000 - SH
3
4000
1000
690
4
4000
1000
690
3 3
4000
1000
690
4 3
5000
1000
690
4 3
6300
1000
690
4 3
1000
1000
690
4 3
1250
1000
690
4 3
1600
1000
690
4 3
2000
1000
690
4
AE 2500 - SH AE 3200 - SH
3
2500
1000
690
4 3
3200
1000
690
4
—
3200
≤
In
≤
4000 3200
≤
In
≤
4000 2000
≤
In
≤
4000 2500
≤
In
≤
5000 3150
≤
In
≤
6300 500
≤
In
≤
1000 625
≤
In
≤
1250 800
≤
In
≤
1600 1000
≤
In
≤
2000 1250
≤
In
≤
2500 1600
≤
In
≤
3200
65
65
0.04
0.08
500
5000
105
143
165
94.5
75
65
75
45
105
143
187
—
50
65
85
50
605
414
290
136
565
430
368
151
109
112
145
148
75
81
85
107
111
49
475
410
290
117
439
430
368
109
105
143
165
94.5
75
65
65
0.04
0.08
500
5000 4000
65
75
45
105
143
187
4000
50
65
85
50
605
410
290
117
569
430
368
109
99
103
136
140
61
70
70
0.05
0.08
500
2000
105
187
187
105
85
85
85
50
105
187
286
3200
50
85
130
50
70
70
0.05
0.08
500
2000
105
187
187
105
85
85
85
50
105
187
286
3200
50
85
130
50
480
368
123
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
— — — — — — 70
875 1005 875 1005 875 1005 485
475
410
290
480
368
123
480 480
368 368
123 123
480 480
368 368
123 123
430
398
61
70
70
0.05
0.08
500
2000
105
187
187
105
85
85
85
50
105
187
286
3200
50
85
130
50
—
—
0.04
0.08
3000
10000
—
—
—
—
—
—
—
—
65
85
130
1000
65
85
130
—
605 475
410 410
290 290
70 70
615 485
430 430
398 398
61 61
—
—
0.04
0.08
3000
10000
—
—
—
—
—
—
—
—
65
85
130
1250
65
85
130
—
605 475
410 410
290 290
70 70
615 485
430 430
398 398
61 61
—
—
240
244
125
—
—
263
267
140
—
—
—
—
240 263
244 267
125 140
—
—
—
—
240 263
244 267
125 140
66
69
105
108
42
79
82
127 105
130 108
50
66
69
42
79
82
127 105
130 108
50
66
69
42
—
—
0.04
0.08
2000
10000
—
—
—
—
—
—
—
—
65
85
130
1600
65
85
130
—
605
410
290
70
615
430
398
61
79
82
127
130
50
475 605
410 410
290 290
70 70
485 615
430 430
398 398
61 61
66
69
—
—
0.04
0.08
1500
10000
—
—
—
—
—
—
—
—
65
85
130
2000
65
85
130
—
79
82
105 127
108 130
42 50
66
69
105
108
42
—
—
0.04
0.08
1500
10000
—
—
—
—
—
—
—
—
65
85
130
2500
65
85
130
—
475
410
290
70
485
430
398
61
605 475
410 410
290 290
70 70
615 485
430 430
398 398
61 61
—
—
0.04
0.08
1000
10000
—
—
—
—
—
—
—
—
65
85
130
3200
65
85
130
—
605
410
290
70
615
430
398
61
79 68
82 71
127 107
130 110
50 43
81
84
129
132
51
Declaration of conformity:
Standards
Certificates
Marine approvals
IEC947-2, EN60947-2, VDE0660
ASTA, SEV (types on request)
LRS, GL, BV, ABS, DNK, NK
(other approvals on request)
MITSUBISHI ELECTRIC
SUPER AE
5
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
BASE UNITS
첸 Program Overview – Order Information
ELECTR
ONI
C TRIP
RELA
Y
MOD
EL
- CIA
MITSUBISHI
SPGT
INDICA
R
TO
TRIP
CT
T
LO
AD lu
C URREN
%
GEST
LA
R
PHASE
URRENT
C
RA
TED
MAX
TED
RA
C
URRENT separate to order: trip relay, e.g. ST1A-SAE
SUPER AE Air Circuit Breaker – Order Information
The circuit breakers of the frame sizes AE1000-SS to AE3200-SS are offered without trip relay and auxiliary switch included as standard equipment.The circuit breakers of the frame sizes
AE4000-SSA/SSC/SS to AE6300-SS are available including the trip relay ST1A and auxiliary relay.The circuit breakers of the frame sizes AE4000-SS,AE5000-SS,and AE6300-SS for handling and weight reasons are available as drawout types.The circuit breakers of the high-performance series AE-SH as well are available including the trip relay ST1A and auxiliary relay.They are available as fixed and drawout types.
To purchase a fully functional 3-pole or 4-pole fixed type circuit breaker please select the following:
앬
앬 base unit: fixed type, 3 or 4 pole with 3 current sensors (CT), electronic trip relay,
앬
앬 auxiliary switches, and the required accessory.
Please refer to order example 1.
To purchase a fully functional 3-pole or 4-pole drawout type circuit breaker please select the following:
앬
앬 the corresponding circuit breaker – fixed type, the corresponding cradle
앬 and the drawout mechanism.
Please refer to order example 2.
To purchase a fully functional 3-pole or 4-pole drawout type disconnector please select the following:
앬
앬
앬 the corresponding disconnector – fixed type, the corresponding cradle and the drawout mechanism.
Please refer to order example 3.
Order example 1:
앬
앬
앬
Base unit – fixed type, 3 pole with 3 current sensors:
AE1000-SS 3P Fix, Bare, CT, TC (art. no. 129215)
Electronic trip relay (for general use - S type): ST1A-SAE
(art. no. 135976)
Auxiliary switches: AX-SAE2A2BA (art. no. 28786)
앬
앬
Order example 2:
앬
앬
앬
Base unit – fixed type, 3 pole with 3 current sensors:
AE1000-SS 3P Fix, Bare, CT, TC (art. no. 129215)
Electronic trip relay (for general use - S type): ST1A-SAE
(art. no. 135976)
Auxiliary switches: AX-SAE2A2BA (art. no. 28786)
Cradle with horizontal terminals:
CRADLE-02SEA3 (art. no. 25897)
Drawout mechanism: REC-SAEFD (art. no. 34666)
Standard series AE-SS – Fixed type
Base unit equipment
앬
앬
앬
앬
Shipping contents:
Base unit
Further elements that must be ordered:
앪
앪
Accessories as required 햳
햲
Breaker
햴
AE 1000 - SS
AE 1250 - SS
AE 1600 - SS
AE 2000 - SS
AE 2500 - SS
AE 3200 - SS
3-pole type
AE1000-SS 3P Fix, Bare, CT, TC
AE1250-SS 3P Fix, Bare, CT, TC
AE1600-SS 3P Fix, Bare, CT, TC
AE2000-SS 3P Fix, Bare, CT, TC
AE2500-SS 3P Fix, Bare, CT, TC
AE3200-SS 3P Fix, Bare, CT, TC
Order example 3:
앬
앬
앬
Base unit (Disconnector *) – fixed type, 3 pole: AE1000-SS 3P
Fix, Bare (art. no. 129228)
Cradle with horizontal terminals:
CRADLE-02SEA3 (art. no. 25897)
Drawout mechanism: REC-SAEFD (art. no. 34666)
* Air circuit breaker without overcurrent short-circuit release and without current transformer
Art. no.
129215
129217
129220
129224
129226
129246
4-pole type
AE1000-SS 4P Fix, Bare, CT, TC
AE1250-SS 4P Fix, Bare, CT, TC
AE1600-SS 4P Fix, Bare, CT, TC
AE2000-SS 4P Fix, Bare, CT, TC
AE2500-SS 4P Fix, Bare, CT, TC
AE3200-SS 4P Fix, Bare, CT, TC
Art. no.
129216
129218
129222
129225
129227
129247
Standard series AE-SS – Drawout type
Please refer to order information above.
햲
햴
For specification and order information about electronic trip relays refer to page 20 ff.
Further breaker types with other rated current on request.
햳
For breaker accessories refer to page 8 ff.
6
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
BASE UNITS
Air circuit breaker series AE-SSA/SSC 4000 A
Base unit equipment Breaker
햴
앬
앬
앬
앬
앬
Shipping contents:
Base unit
Further elements that must be ordered:
앪
앪
Accessories as required
햳
햲
AE 4000 - SSA
AE 4000 - SSA
AE 4000 - SSC
Fixed type
AE4000-SSA 3P Fix, ST1A, AX2A2B
AE4000-SSA 4P Fix, ST1A, AX2A2B
AE4000-SSC 3P Fix, ST1A, AX2A2B
Air circuit breaker series AE-SS 4000–6300 A – Draw-out type
Base unit equipment
앬
앬
앬
앬
앬
Shipping contents:
Base unit
Breaker
AE 4000 - SS
AE 5000 - SS
AE 6300 - SS
3-pole type
AE4000-SS 3P D/O, ST1A, AX2A2B, SST
AE5000-SS 3P D/O, ST1A, AX2A2B, SST
AE6300-SS 3P D/O, ST1A, AX2A2B, SST
Further elements that must be ordered:
앪
앪
Accessories as required 햳
햲
High performance series AE-SH – Fixed type
Base unit equipment Breaker
햴
앬
앬
앬
앬
Shipping contents:
Base unit
Further elements that must be ordered:
앪
앪
Accessories as required
햳
햲
AE 1000 - SH
AE 1250 - SH
AE 1600 - SH
AE 2000 - SH
AE 2500 - SH
AE 3200 - SH
3-pole type
AE1000-SH 3P FIX, ST1A, AX2A2B
AE1250-SH 3P FIX, ST1A, AX2A2B
AE1600-SH 3P FIX, ST1A, AX2A2B
AE2000-SH 3P FIX, ST1A, AX2A2B
AE2500-SH 3P FIX, ST1A, AX2A2B
AE3200-SH 3P FIX, ST1A, AX2A2B
Art. no.
142593
142594
69984
Art. no.
56977
56976
56974
Art. no.
43713
139887
43711
139888
139889
139890
High performance series AE-SH – Draw-out type
Base unit equipment
앬
앬
앬
앬
앬
앬
Shipping contents:
Base unit
Charging handle (for manual operation)
4 auxiliary contacts (2 NO, 2 NC contactsr)
Further elements that must be ordered:
앪
앪
Accessories as required 햳
햲
Breaker
햴
AE 1000 - SH
AE 1250 - SH
AE 1600 - SH
AE 2000 - SH
AE 2500 - SH
AE 3200 - SH
3-pole type
AE1000-SH 3P D/O, ST1A, AX2A2B
AE1250-SH 3P D/O, ST1A, AX2A2B
AE1600-SH 3P D/O, ST1A, AX2A2B
AE2000-SH 3P D/O, ST1A, AX2A2B
AE2500-SH 3P D/O, ST1A, AX2A2B
AE3200-SH 3P D/O, ST1A, AX2A2B
Switch-disconnector* AE-SS – Fixed type
Base unit equipment
앬
앬
앬
Shipping contents:
Base unit
Further elements that must be ordered:
앪
앪
햳
Breaker
AE 1000 - SS
AE 1250 - SS
AE 1600 - SS
AE 2000 - SS
AE 2500 - SS
AE 3200 - SS
3-pole type
AE1000-SS 3P SS Fix, Bare
AE1250-SS 3P SS Fix, Bare
AE1600-SS 3P SS Fix, Bare
AE2000-SS 3P SS Fix, Bare
AE2500-SS 3P SS Fix, Bare
AE3200-SS 3P SS Fix, Bare
Art. no.
129228
129232
129236
129240
129242
129248
Art. no.
43701
139905
139906
43698
139907
43696
Draw-out type
AE4000-SSA 3P D/O, ST1A, AX2A2B, SST
AE4000-SSA 4P D/O, ST1A, AX2A2B, SST
AE4000-SSC 3P D/O, ST1A, AX2A2B, SST
Art. no.
142596
142599
69985
4-pole type
AE4000-SS 4P D/O, ST1A, AX2A2B, SST
AE5000-SS 4P D/O, ST1A, AX2A2B, SST
AE6300-SS 4P D/O, ST1A, AX2A2B, SST
Art. no.
56978
56975
56973
4-pole type
AE1000-SH 4P FIX, ST1A, AX2A2B
AE1250-SH 4P FIX, ST1A, AX2A2B
AE1600-SH 4P FIX, ST1A, AX2A2B
AE2000-SH 4P FIX, ST1A, AX2A2B
AE2500-SH 4P FIX, ST1A, AX2A2B
AE3200-SH 4P FIX, ST1A, AX2A2B
Art. no.
139891
139902
139903
139904
43703
43702
4-pole type
AE1000-SH 4P D/O, ST1A, AX2A2B
AE1250-SH 4P D/O, ST1A, AX2A2B
AE1600-SH 4P D/O, ST1A, AX2A2B
AE2000-SH 4P D/O, ST1A, AX2A2B
AE2500-SH 4P D/O, ST1A, AX2A2B
AE3200-SH 4P D/O, ST1A, AX2A2B
Art. no.
43695
139908
139909
139910
139911
43690
4-pole type
AE1000-SS 4P SS Fix, Bare
AE1250-SS 4P SS Fix, Bare
AE1600-SS 4P SS Fix, Bare
AE2000-SS 4P SS Fix, Bare
AE2500-SS 4P SS Fix, Bare
AE3200-SS 4P SS Fix, Bare
Art. no.
129229
129234
129238
129241
129244
129249
Switch-disconnector* AE-SS – Draw-out type
Please refer to order information on the top left side.
햲
햴
For specification and order information about electronic trip relays refer to page 20 ff.
햳
For breaker accessories refer to page 8 ff.
Further breaker types with other rated current on request. * Air circuit breaker without overcurrent short-circuit release and without current transformer
MITSUBISHI ELECTRIC
SUPER AE
7
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
Overview and mounting positions of the main accessories
Counter
Auxiliary switch
Under voltage trip device
Closing coil
Shunt trip device
Mis insertion preventer
Safety shutters
Cell switch
Page 13
Page 12
Page 11
Page 12
Page 12
Page 15
Page 14
Page 14
CNT
AX
UVT
CC
SHT
MIP
SST
CL
ONI
ELECTR
TR
IP
AY
EL
MITSUBISHI
MODEL
- C IA
CT
TOR
SPGT
TRIP
INDICA
LO %
C URRENT lu PHASE
LARGEST
MAX
RA
TED
C URRENT
RA TED
External power supply unit
Lifting hooks
Motor charging device
Cylinder lock
Castell lock
Electronic trip relay
CYL
CAL
PS
HP
MD
Page 19
Page 15
Page 10
Page 13
Page 13
Page 20
Page 6
8
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
Overview and description of the standard equipment
왎 Manual charging
OFF
ON
OFF
GESP
ANNT
The spring is charged by the manual charging handle.The breaker is closed when the ON button is pressed,and opened when the OFF button is pressed.
When the closing spring charging is completed,the charging indicator displays
CHARGED.
The indicator displays ON or OFF state of the main contacts.
The breaker cannot be closed while the
OFF button is being pressed (safety feature).
The manual charging process is one of the standard features of the breaker and part of the standard equipment.
왎 Drawout interlock
A safety device prevents the circuit breaker from being pushed in or drawn out while the breaker is on.
The drawout handle cannot be inserted unless the OFF button is pressed.
왎 Position lock
16
5
The device is for locking the drawout mechanism at the TEST position.This then indicates the TEST position.
The lock can be used during either the drawing out or pushing-in operation.
The lock is released when the lock plate is pushed in,and the next operation becomes possible.
Padlocking is possible at the CONNECTED,
TEST,and DISCONNECTED positions.Use
this lock to prevent unauthorised changing of positions.
(The padlock should be supplied by the customer)
35
왎 Interphase barrier
The interphase barrier of the circuit breaker prevent the short-circuit due to conductive matters or dust.
The interphase barrier are simple to add and have been designed as fixed types and drawout types,to suit your requirements.The table on the right shows you which circuit breakers are supplied with pre-mounted barriers.
Breaker Fixed type
쏹
쏹
Drawout type
쏹
쏹
— —
—
쏹
쏹
=Standard equipment by horizontal connection
MITSUBISHI ELECTRIC
SUPER AE
9
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
Overview and description on the optional accessories
왎 Motor charging device (MD)
In addition to manual operation,the closing spring can be charged automatically by an electric motor every time the breaker is closed (ON charging method).
If the closing spring is to be charged automatically whenever the breaker is opened, then this can be done through an additional auxiliary contact (AXb) (OFF charging method).As soon as charging is completed,a visual display on the front says
"CHARGED".
The "CHARGED" signal is also available via the 413 (TS+) and 414 (TS-) terminals
(included in the standard MD configuration).
There is always the option of manual operation in an emergency.A closing coil
(CC) is required for closing the breaker by remote control,and a shunt trip device
(SHT) is required for opening it in this way.
This warrants the prevention of pumping, both electronically and mechanically.The
circuit of the motor is separate from the
ON/OFF circuit (CC,SHT).
ON charging method
(M+)
U1
(M-)
U2
OFF charging method
AXb
(M+)
U1
(M-)
U2
Specifications
Application
Rated voltage *
Applicable voltage range
Applied voltage
Inrush current (peak value)
Steady current
Charging time
Order information
Art. no. 29453
* Rated frequency at AC = 50/60 Hz
햲
햳
Not available for AE4000-SS – AE6300-SS.
for 3-pole type
햴 for 4-pole type
MD-SAED24
AE3200-SS/-SH,
AE4000-SSC
햳
(V) 24 (DC)
햲
(V) 20.4–26.4
(V) 24
(A) 22
(A) 6
(sec)
≤
5
MD-SAED48
48
14
AE3200-SS/-SH,
AE4000-SSC
햳
48 (DC)
40.8–52.8
3
≤
5
34352
MD-SAED60
60
9
AE3200-SS/-SH,
AE4000-SSC
햳
60 (DC)
51–60
3
≤
5
34368
MD-SAEAD013
AE3200-SS/-SH,
AE4000-SSC
햳
100–125(AC/DC)
85–137.5
100 / 125
10 / 12
3
≤
5
32843
MD-SAWAD013
AE4000-SS–
AE6300-SS
햴 ,
100–125(AC/DC)
85–137.5
100 / 125
10 / 12
4
≤
5
58320
MD-SAEAD025C
AE3200-SS/-SH,
AE4000-SSC
햳
200–250 (AC/DC)
170–275
200 / 250
5 / 6
1
≤
5
25830
MD-SAWAD025C
AE4000-SS–
AE6300-SS
햴 ,
200–250 (AC/DC)
170–275
200 / 250
7 / 8
2
≤
5
58321
왎 Charging completion switch (TS)
(TS+)
413
(TS-)
414
As soon as charging has been completed, this status is reported by the 413 (TS+) and
414 (TS-) terminals (signal display of charged status).This function is available during the charging process both manually and automatically.
Specifications
Contact capacity
Order information
TS-SAE1A
refer to auxiliary switch
Art. no. 30439
10
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Undervoltage trip device (UVT)
Two trip types are available:
앬 instantaneous (for immediate tripping)
앬 with a time delay of 0.5 or 3 seconds
All UVT controllers are fitted with additional terminals for the connection of an emergency OFF switch.The UVT controller can be mounted to the left of the the unit.
If two rated voltages are used,the lowest value is applied.
If an emergency OFF trip function is required,remove the shorting wire across terminals DT1 (UO+) and DT2 (UO-) and replace with an emergency OFF switch.
Coil
Controller
This device is used for tripping the breaker when the supply voltage drops below the rated value.
The undervoltage trip device consists of a
UVT coil and a UVT controller. Both parts
must be ordered separately.
UVT circuit diagram
(UL3)
(UL2)
(UL1)
(UL0)
D4
D3
D2
D1
UVT controller
Control circuit
(U
+)
J1
J2
(U–)
J1
J2
Air circuit breaker
UVT coil see note below
Trip button
Notes on the circuit diagram:
The UVT,as delivered,has a shorting wire between the DT1 (U0+) and DT2 (U0-) terminals.
If an emergency OFF switch is used,this contact bridge must be removed.The emergency
OFF switch is not included in the package.The maximum length of the wire between DT1
(U0+) and DT2 (U0-) and the trip button should be 5 m.If longer distances are required please contact your nearest Mitsubishi distributor.
Specifications
Rated voltage (+10%/-15%) *
Operation
Operating time
Closing delay**
Pick-up/drop-out voltage
Trip function
Power consumption
Order information
(V) 24 (DC)
Instantaneous
100–125 (DC) 100–460 (AC) 24 (DC)
With time delay
100–110 (DC) 100–460 (AC) 24 (DC)
(sec) 0.1 or less 0.1 or less 0.1 or less 0.5 or more 0.5 or more 0.5 or more 3 or more
(sec) Approx. 1.5
Approx. 1.5
Approx. 1.5
Approx. 1.5
Approx. 1.5
Approx. 1.5
Approx. 3
(V) Pick-up voltage 65–85 %, drop-out voltage 45–70 %
With open circuit (terminals DT1 (UO+), DT2 (UO–); rated 0.5 A at DC 250 V)
(VA) 20
Art. no. 30440 30441 30209 30442 30443 30206
* Rated frequency at AC= 50/60 Hz
** Delay which must be taken into account between the charging of the UVT controller and the closing of the breaker.
30444
100–110 (DC) 100–460 (AC) UVT coil
3 or more
Approx. 3
30445
3 or more
Approx. 3
30208 25912
MITSUBISHI ELECTRIC
SUPER AE
11
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Closing coil (CC)
The closing coil is seperate from the motor charging power supply.
Steady current is the value at maximum rated voltage.
An interlock to prevent pumping is provided electrically.The pumping prevention is not performed,when the supply voltage is 50 % or less the minimum rated voltage.
(CC+)
A1
(CC-)
A2
The closing coil is a device to close the breaker by remote control.Only one closing signal (about 100 msec.) is sent even when the closing coil supply is maintained ON.
Specifications
Rated voltage *
Applicable voltage range
Operating voltage
CC-SAED004A
(V) 24–48 (DC)
(V) 18–52,8
(V) 24 / 48
Inrush current
Closing time
AC (A) —
(sec) max. 0.08
Order information
Art. no. 30399
* Rated frequency at AC = 50/60 Hz
Closing time is from the initial energization of the closing coil to the completion of the closing of the main contacts.
No pumping prevention takes place if an integrated auxiliary switch (AXb) is used as a cut-off switch.
An auxiliary contact with high switching capacity should be used with DC supply voltage (HAX).
CC-SAED60
60 (DC)
45–60
60
1.1
— max. 0.08
40310
CC-SAEAD025A
100–250 (AC/DC)
75–275
100 / 250
DC250 V 200 W)
0.5 / 1.0 (AC 100 V 100 VA,
AC 250 V 200 VA) max. 0.08
25909
왎 Shunt trip device (SHT)
(S+)
C1
(S-)
C2
The shunt trip device is used to open the breaker by remote control.
A cut-off switch is included.
Specifications
Rated voltage *
Applicable voltage range
Operating voltage
SHT-SAED004A
(V) 24–48 (DC)
(V) 16.8–52.8
(V) 24 / 48
SHT-SAED60
60 (DC)
42–66
60
SHT-SAED025A SHT-SAEA046A
100–250 (AC/DC) 380–500 (AC)
70–275
100 / 250
266–550
460
— DC (A)
(
(DC24 V 100 W, 1
(
(DC100 V 100 W,
AC (A) — —
(
(AC 100 V 100 VA,
(sec) max. 0.04 (AE 4000-SS – AE 6300-SS = max. 0.05) Closing time
Order information
Art. no. 27215
* Rated frequency at AC = 50/60 Hz
40309 25831 27614
왎 Auxiliary switch (AX, HAX)
(AX+)
13
(AX-)
14
(BX+)
11
(BX-)
12
These auxiliary contacts are used to remotely indicate the ON or OFF status of the breaker.
Specifications
Type
Contact capacity
(A)
Maximum number of contacts
460 V 5
AC 250 V 10
125 V 10
250 V 0.3
DC 125 V 0.6
AX-SAE2A2BA
Standard capacity (AX)
Resistance load
Inductive load
2
10
10
0.3
0.6
30 V 10
2 NO, 2 NC
6
AX-SAE5A5BA
10
0.3
0.6
Resistance load
5
10
10
5 NO, 5 NC
Order information
Art. no. 28786 25835
Note: The chattering time at the time of contact ON - OFF is below 0.025 sec.
10
0.3
0.6
Inductive load
2
10
6
10
3
5
10
10
AX-SAE5A5BAD
High capacity (HAX)
Resistance load
Inductive load
2.5
10
10
1.5
6
10
5 NO, 5 NC
10
38468
12
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Condensor trip device (COT)
Circuit diagram
AC1
AC2
S1
R1
C
N6
DC+
SHT
C1
(S+)
DC–
C2
(S–)
This device allows the electrically actuated opening of the breaker by remote control within a given period of time,despite a power cut.The COT is used in conjunction with the shunt trip device (SHT).
For dimensions refer to page 41.
Further details on request.
Specifications
Rated input voltage *
Rated charging voltage
Power supply capacity
Capacitor capacity
Voltage range
Charging time (capacitor)
Trip limit time
KF-100 KF-200
V AC 100/110 200/220
V 140/155 280/310
VA 1
µF 660
1
150
% 60–125 60–125 s max. 0.5 max. 0.5
s min. 900 min. 300
Order information
Art. no. On request On request
* Rated frequency at AC = 50/60 Hz
왎 Counter (CNT)
This is a mechanical counter which registers the total number of operating cycles
(with 1 ON/OFF switching operation =
1 operating cycle).
The number of operating cycles is displayed on the front of the unit.
Specifications
Counter type
Display
Order information
CNT-SAE
Mechanical
5 digits
Art. no. 25914
00000258
왎 Interlock device (CYL, CAL)
CYL
CAL
The interlock device locks the circuit breaker into the OFF position.
The relevant key can only be taken out in the OFF position of the circuit breaker, so that it can also be used for unlocking other breakers.
There are two locking options available:
앬
앬
Cylinder lock (CYL)
Castell lock (CAL) *
Specifications
Interlock
Closing
Cylinder
Basic
Cylinder
1
Cylinder
2
Cylinder
3
Cylinder
4
Order information
Art. no. 25838 39485 39486 39488 39489
* The closing basis for the Castell lock can be designed individually. Further details on request.
Castell
Basic
On request
MITSUBISHI ELECTRIC
SUPER AE
13
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Cell switch (CL)
The cell switches can be set for all the relevant positions,i.e.connected,test and disconnected.
Each cell switch consists of 4 individual switches.
Switch function
CL–C
CL-T
Specifications
Load
In addition to the mechanical position indicator on the front panel,it is also possible to mount these cell switches onto the cradle.
Contact capacity (A)
CL-SAE211
Resistive
Number and type of switches
Application (breaker)
Order information
4 interchange switches
AE1000-SS – AE6300-SS
Art. no. 25840
Inductive
CL-SAH211
Resistive Inductive
4 interchange switches
AE1000-SH – AE3200-SH
45578
왎 Safety shutters (SST)
The safety shutters cover the main conductors of the cradle side (supply and load side) automatically when the circuit breaker is drawn out.
When checking the main circuit,the safety shutters on the supply and load sides can be opened independently of one another.
The safety shutters can also be locked with a mechanical locking device (SST LOCK).
The padlocks have to be supplied by customer.
Specifications
Application(breaker)*
Breaker type
Number of poles
SST-
02SAE3
AE1000–1600-SS
SST-
02SAE4
Drawout
3 4
SST-
05SAE3
SST-
05SAE4
SST-
SAELOCK
shutter lock
3 4
Order information
Art. no. 25836 25837 25907 25908
* On breaker types AE 4000-SSA/SSC–SS to AE 6300-SS the safety shutters are already part of the standard version.
30458
14
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Shorting b-contact (SBC)
When moving the breaker from the connected to the test positions,this contact is used to short circuit auxiliary switch (Axb) thus maintaining the correct sequence of operation of the external control circuit.
When ordering,the same number of shorting b-contacts as auxiliary switches
(AXb) will be provided.
Specifications
Application (breaker)
Order information
SBC-SAE
All breaker
Art. no. 30456
왎 Mis-insertion preventor (MIP)
To obtain the right drawout configuration, it is extremely important that the breaker unit specifications (type,current rating, optional accessories,etc.) should match the cradle.
Mis-insertion is prevented by a combination of matching components (on the breaker and the cradle).
Specifications
Application (breaker)
Material
Order information
MIP-SAE
AE1000–AE3200-SS/SH
AE4000-SSA/SSC
Metal
Art. no. 30455
왎 Vertical terminal adapter (VTA)
Vertical terminal adapters allow you to turn power connection by 90°.
Other forms of terminal adapters on request.Dimensions see page 37 ff.
Specifications
Application (breaker)
Shipping contents
Order information
VTA-02SAE
AE1000–AE1600-SS pieces 1
Art. no. 34193
VTA-03SAE
1
34192
VTA-32SAE
AE3200-SS/SH
1
34191
왎 Lifting hooks (HP)
These hooks are used to remove the drawout breaker from the cradle.
The option is not necessary,when a special lifter (bucket type) for AE-SS is used.
The fixed type breaker is equipped with the lifting hooks as standard.
The lifting hooks can not be used for
AE4000-SS to AE6300-SS.
Specifications
Material
Order information
HP-SAE
Metal
Art. no. 30485
MITSUBISHI ELECTRIC
SUPER AE
15
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Mechanical interlock (MI)
Horizotal mounting
1000 (Max.)
Vertical mounting
47
134
The mechanical interlock is a secure interlock prohibiting the parallel closing of two or three breakers.
Any combination between AE1000-SS/SH up to AE3200-SS/SH and AE4000-SSA/SSC is possible.
The interlock can be simply installed on either fixed or drawout type breakers.
With the drawout type,the interlock operates at the connecting point and can be released at other positions,providing secure maintenance and inspection of the breaker.
For AE4000-SS up to AE6300-SS a combination is possible only between two breakers.
Note:
When using the mechanical interlock,the application of the door interlock (DI) is not possible.
ON
G
OFF ON
ON
OFF
[mm]
Specifications
Application(breaker)
Breaker type
Number of poles
AE1000–1600SS
Fixed
3 4
AE1000–1600SS
Drawout
3 4 3 4 3 4
Order information
Art. no. 30450 30451 30452 30453 30446 30447 30448 30449
Interlocking requires a separate unit for each breaker. If you have 3 breakers, you need a separate set of bowden cables MI-SAEIW.
MI-SAEIW
AE4000–6300SS
3
62327
4
62326 30454
왎 Door interlock (DI)
The device has been designed for panel doors with the groove on the left (standard).Locks for grooves on the right are available on request.
A wire-type mechanical interlock is used to allow flexibility in positioning breakers in the panel.
Note:
When using the door interlock (DI) the application of the mechanical interlock
(MI) is not possible.
This mechanical interlock device makes it impossible to open the panel door unless the circuit breaker is not switched off.
Specifications
Application (breaker)
Breaker type
Order information
DI-SAEF
For all breakers
Fixed
Art. no. 31538
DI-SAED
For all breakers
Drawout
31537
16
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Push button cover (BC-L)
This mechanical device can be locked with a padlock or a seal (not included in the package) to protect the push buttons of the breaker unit against inadvertent
ON/OFF operation.
The padlock has to be supplied by the customer.
Specifications
Material
Order information
BCL-SAE
Acrylic plate
Art. no. 27727
왎 Dust cover (DUC)
The transparent dust cover is hinged onto the panel door.It has a screw lock and prevents dust and water entering into the circuit breaker.
Specifications
Protection
Order information
DUC-SAE
IP 54
Art. no. 42618
왎 Terminal cover (TTC)
The terminal cover is a transparent cover for safety finger protection of control terminals.
The terminal cover prevents from careless touching to the live control terminals.
Specifications
Application (breaker)
Protection
Order information
TTC-SAEF TTC-SAED
Fixed type Draw-out
IP 20 IP 20
Art. no. 62482 62481
왎 Door frame (DF)
The door frame improves the appearance, after cutting out the panel door to install the breaker.
Refer to the overall dimension drawings on page 36 ff for the installation method.
Specifications
Application (breaker)
Material
Protection
Order information
DF-SAE
For all breakers
Plastic
IP 20
Art. no. 28319
MITSUBISHI ELECTRIC
SUPER AE
17
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 Current transformer (CT)
These current transformers (CT and sensor coil) are suitable for the main conductor and the N conductor.
Current transformers of type CT-06첸첸첸 serve the reduction of I n max
.on an
AE 1000.
Specifications
Application (breaker) *
Rated current I n max
** (A) 315 500 630 1000 1250
Order information
Art. no. 30476 30477 30478 33437 30479
*
More CTs on request.
Shipping contents includs CT and sensor coil for 1 pole. Other transformers on request.
** At 40°C and 50/60 Hz (other temperatures see Technical Information on page 48)
1600
30480
1250
43387
1600
62748
2000
39539
2500
39540
3200
39541
왎 Neutral current transformer (NCT)
Diagram
The neutral CT is used for ground fault protection when a 3 pole breaker is used on a
3 phase 4 wire system.It should be used together with a electronic trip relay that has the ground fault protection (GFR) option.
Elektr.Auslöserelais mit Erdschlussschutz
Specifications
Application(breaker) *
Current range
AE1000 AE1000 AE1250 AE1600 AE2000 AE2500 AE3200 AE4000 AE5000 AE6300
(A) 630 1000 1250 1600 2000 2500 3200 4000 5000 6300
Order information
Art. no. 39038 39026 33853 37323 39037 39036 39035 62330 62329 62328
* A suitable resistor (0.1
Ω
/ 10 W) is attached to the product. Further technical details on request.
For AE4000-SSC on request.
왎 External current transformer (ZCT)
Load circuit method (ZCT) Transformer ground wire method (ZT)
C2
SHT
C1
N2
714
N1
713
L2 L1
C2
SHT
C1
N2
714
N1
713
L2 L1
Power supply
Power supply
Specifications
Application
Hole diameter for wire *
ZCT-163 ZCT-323 ZCT-324 ZT-15A ZT-30A
Load circuits Transformer ground wire
(mm) 230x60 (oval) 370x108 (oval) 500x108 (oval)
∅
15
∅
30
Order information
Art. no. On request
* For detailed dimensions refer to page 46. Further specifications on request.
ZT-40A
∅
40
This option is used to detect several amperes of earth leakage when used in combination with an electronic trip relay that has the earth leakage tripping (ER) option.
Two methods are available:
앬
ZCT: three-load phase conductors (and
앬 the neutral conductor in a 4-wire system) are passed through the ZCT
ZT: The supply transformer’s ground wire passes through to earth.
ZT-60A
∅
60
ZT-80A
∅
80
ZT-100A
∅
100
18
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ACCESSORIES
왎 External power supply unit (PS)
This unit is used when a DC 24 V control supply is needed for the trip indicator on the electronic trip relay.
The unit can be installed from the front to the left side of the breaker (for dimensions
Specifications
Rated voltage *
Input voltage range
Input capacity
Output voltage
Output current
PS-A200
(V) 100–110 / 200–220 (AC)
(%) +10 / -15 %
30 VA or less
(V) 24 (DC)
±
10 %
(A) 0.42 or less
Order information
Art. no. On request
* Rated frequency at AC = 50/60 Hz
PS-D200
200 (DC)
+10 / -15 %
30 W or less
24 (DC)
±
10 %
0.42 or less
On request
PS-A400
380–415 (AC)
+10 / -15 %
30 VA or less
24 (DC)
±
10 %
0.3 or less
On request
왎 Field test devices
The test devices are for testing the functioning of the electronic trip relay.
It allows you to test the trip relay without the breaker being connected to the main supply.The breaker will trip when tested.
TING
TIME
OPERA
TESTER
MITSUBISHI
BREAKER
Y -2000
SIGNAL
S1
S2
60
Hz
ST
OP UENCY
FREQ
ST
OP
SIGNAL
50
Hz
VT
TC
OCR
TESTING
TRIP
OUTPUT
S1S2S3
50/60
TRIP
CHECK
OP
ST a?/OCR RESET
VT
OUTPUT
S3
AR
ST
T
ST
OP
888.88.8
6
8
?
7
5
3
4
2
1
0
SIGNAL
C
SET
SET
SIGNAL
ADJUST
UP
DO
WN
(Y2000)
Specifications
Test functions
Power supply *
Test current signal setting
Others
Y-160
LTD, STD, INST, Groundfault
100–120 V, 200–240 V (AC) or battery
Time counter
Order information
Art. no. 27497
* Rated frequency at AC = 50/60 Hz
Y-2000
LTD, INST, STD, Groundfault, pre-alarm
100–240 V (AC)
Ammeter, time counter
27496
왎 Test jumper (TJ)
The test jumper cable is for testing the functioning of the circuit breaker when the unit is removed from its cradle.
Take the breaker out of its cradle and use this cable to switch the breaker on and off electrically,so that you can check all its functions.
Specifications
Cable length
TJ-SAE
(m) 3 *
Order information
Art. no. 30457
* Other lengths on request
MITSUBISHI ELECTRIC
SUPER AE
19
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Introduction and selection
Functions
Long-time-delay
+ Short-time-delay
+ Instantaneuous
Trip indicator
Applicable types B type
Code — ST SPT SPGT SPET MT MPT MPGT
L
S
I
—
쏹 쏹 쏹 쏹 쏹 쏹 쏹
TRIP
—
쏹 쏹 쏹 쏹 쏹 쏹 쏹
Load current indicator
STD lock button
OCR alarm
LCI
—
쏹 쏹
AL
—
쏹 쏹
쏹 쏹 쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
—
쏹 쏹 쏹 쏹
— — —
Test terminal
Pre-alarm
TEST
—
쏹 쏹
PAL
— —
쏹
쏹
쏹
쏹
쏹
쏹 쏹
—
쏹
쏹
쏹
Ground fault
GFR
— — —
쏹
— — —
쏹
—
Remarks Reference
Page 23, 25 required *)
—
—
—
—
— required *)
For characteristics check
—
1. With ground fault alarm switch
2. If a 3-pole breaker is used in a 4-wire ordered.
3. The ground fault protection (GFR) is not
Page 22, 24
Page 22, 24
Page 23, 25
Page 29
Page 29
Page 23, 25
Page 22, 24
Accessory
3and
Earth leakage
Instantaneous / MCR
ER
— — — —
쏹
— — —
LM
—
쎻 쎻
TAL
—
쎻 쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쏹
— — — — — — —
—
햲 햲 햲 햲
— — —
—
햲 햲 햲 햲
— — —
—
An external power supply for trip indication (TRIP) and relay control is required for all type of relays.
required required *) required *)
—
—
The sensor is integrated in the breaker.
function (L) is not available.
and MCR characteristics is possible.
available.
and MCR characteristics is not possible.
—
Page 28
Page 29
Page 29
—
—
Page 22, 23
— —
쏹 Equipped with function as standard.
— Function not available.
쎻 Function available as an option.
햲 Only one of the special versions (MCR-I,or MCR-C) is available as an option.
*
No additional power supply is required as long as control power is available.
** Other voltages on request.Rated frequency at AC = 50/60 Hz.
Special notes:
The circuit breakers are equipped with the S type relay in ST1A version (applicable voltage range AC 100–120/200–240 V) as standard(refer to page 6).
All other model types and accessories can be configured and ordered individually.
In the table on page 30 and 31 the most common configurations are listed with order informations.
The trip relay type B is suitable for switch disconnectors with instantaneous MCR characteristics only.
20
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Characteristics setting table
Function Application
ST SPT SPGT SPET MT MPT MPGT
(I nmax
)
Rated current (I n
)
Uninterrupted current (I
U)
S type
S type
(I
L
)
M type
S type
Time (T
L
)
M type
(I sd
)
Time
(T sd
)
(I i
)
M type
(I n max.
)
Maximum rated current n max
)
× setting
Rated current (I setting n
)
× setting
U
)
Rated current (I n
)
×
2
U
)
×
1.2
L
)
Long-time delay
L
)
× setting
Rated current (I n
)
At short-time delay
×
1.5
sd
)
Rated current (I n
)
× setting
U
)
Long-time delay current (I
L
)
0.80–0.82–0.84–0.86–0.88–0.90–0.92–0.94–0.96–0.98–1.0
(adjustable in steps)
— —
햳
12–25–50–100–150sec
±
20 %
—
—
—
—
—
—
—
—
—
—
1–1.05–1.1–1.15–1.2
±
5 %
12–20–25–30–40–60 s
±
20 %
— — Details on request
2–3–4–6–8–10
±
15 %
0–0.1–0.2–0.3–0.4–0.5 s
±
20 %
Remark: the operating time for "0" is 0.05 sec. (only for M type)
AE5000-SS: 4–6–8–10–12
±
4–6–8–10–12–16
±
15 %
±
15 % (adjustable in steps each)
(I p
)
S type
M type
—
0.7–0.8–0.9–1.0–OVER
±
10 %
Time (T p
)
At long-time delay time (T
L
)
— 0.5 times ± 20 %
Current g
)
—
Maximum rated current n max
) × setting
—
— —
Self holding
0.1–0.2–0.3–0.5 ±20%
AE4000-SSA/SSC,
0.2–0.3–0.5
±
20 %
(adjustable in steps each)
0.3–0.8–1.5–3 s
±
20 %
—
Time (T g
)
Current e
)
Time (T e
)
S type e
) g
)
At earth leakage current (I e
)
— —
— —
— —
—
—
햲
햳
Not available at I n max
≤
315 A, 500 A and AE 1000-SH, 630 A.
At 105 % non trip, at 125 % pick up.
Note: The electronic trip relay will be delivered set to the values shown in bold type.
—
1–2–3–5 A
±
20 %
0.3–0.8–1.5–3 s
±
20 %
—
—
—
—
0.5 times ± 20 %
Automatic reset
0.1–0.2–0.3–0.5±20%
AE4000-SSA/SSC,
0.2–0.3–0.5
±
20 %
(adjustable in steps each)
0.3–0.8–1.5–3s
±
20 %
—
—
Overview of rated currents (I n max
) – CT ratings
AE1000-SS AE1250-SS AE1600-SS AE2000-SS "SS" type
Rated current n max
)
"SH" type
Rated current
(I n max
)
AE1000-SH
1250 1600
AE1250-SH AE16000-SH AE2000-SH
1250 1600 2000
AE2500-SS
2500
AE2500-SH
2500
AE3200-SS AE4000-SSA/SSC AE4000-SS
3200 4000 4000
AE3200-SH
3200
AE5000-SS
5000
AE6300-SS
6300
MITSUBISHI ELECTRIC
SUPER AE
21
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
S Types – General Protection
햲
Trip Indicator
Display of tripping condition:
앬
앬
L for Long-time delay
S/I for short-time delay (S) /
앬 instantaneous (I)
G for ground fault (GFR)
앬
E for earth leakage (ER)
Both an LED display (red) and a relay output are provided.
Remarks: 쐃, 쐇, 쐏
햳
Pre-Alarm Display
Pre-alarm display when a pre-determined load current is reached.
Display method:Both an LED display
(yellow) and a relay output are available.
앬
The "PAL" LED lights up when the preset value is exceeded (the relay is not
앬
앬 activated when this happens).
The relay output is activated when the
"PAL OUT" LED lights up.
The "PAL OUT" is self-holding and keeps lightning, even if the load value is again smaller than the set value.
Remarks: 쐃, 쐇, 쐏
햴
Temperature Alarm
An alarm signal is generated when the temperatureofthemaincontactsrisesabove thethreshold level (approx.170 °C or more).
Display methods:Both an LED indicator
(red) and a relay output are provided.
Remarks: 쐃, 쐇, 쐏
햵
Load Current Indicator
Indicates the percentage of uninterrupted current (I u
) in the following steps
60-70-80-90-100-OVER.
LED indication in different colours:
앬
60 – 80 % = green
앬
앬
90 – 100 % = yellow
OVER = red
The LEDs goes out when the breaker trips.
햲
햳
햵
햸
햻
헁
헃
헂
햹
ELECTRONIC TRIP RELAY
MODEL
SPGT - C1AT
RESET
L S/I
TRIP INDICATOR
ALARM
PAL P.U.
PAL OUT
G
TAL
LOAD CURRENT % lu
60 80 100 OVER
RATED CURRENT MAX.
(CT RATING)
I
N MAX
A
RATED CURRENT
0.7
0.8 0.91.0
0.6
0.5
X I N MAX
PAL P.U. Ip
0.9
1.0 OVER
0.8
0.7
X Iu
UNINTERRUPTED
CURRENT Iu
.88
.84
.92
.80
X I N
.96
1.0
STD P.U. lsd
2
3
4
6 8 10
X Iu
INST P.U. li
4
6
8
10 12 16
X Iu
GFR P.U. lg
0.5
0.3
0.2
0.1
X In max.
STD LOCK INST MCR
TRIP ALARM
GFR TIME
3.0
1.5
0.8
0.3
MADE IN JAPAN
OCR Alarm Contact
An alarm signal is output to the contact when the breaker is tripped by one of the following causes:
앬
L Long-time delay
앬
앬
앬
앬
S Short-time delay
I Instananeous trip (I) or MCR
G Ground fault or
E Earth leakage
Remarks: 쐋, 쐏 lu X 2 lsd X 1.5
LTD TIME
25
12
100 150
50
SEC.
STD TIME
0.2
0.3 0.4 0.5
0.1
0
SEC.
TEST
헀
햽
햺
햿
햾
헄
햶
햴
햷
햶
Indicator Reset Button
Pressing this button resets the displays and the relay output.
앬
앬
앬
Trip indicator (TRIP)
Unusual temperature indicator (TAL)
Pre-alarm (PAL)
Remarks:
All functions marked in gray are included as standard equipment (standard relay
ST1A).
This overview lists the maximum possible functionality of the units.
Trip relays with special functions (functions wich are not marked in gray) have to be
ordered seperately (please refer to order
information on page 30 and 31).
Page 28 and following contain a detailled
description of all special functions.
� An external power supply for trip indication and relay control is required for all type of relays.The voltage range for the power supply must be within one of the following ranges:
- 1: AC 100–120 / 200–240 V (standard)
- 2: DC 100–125 V
- 4: DC 24–60 V
(other voltages on request)
쐇 The LED will go out when the control power supply is interrupted or when the RESET button is pushed.
쐋 An external self-hold circuit is required, as the alarm signal pulse has a duration of only 0.03 sec.
쐏 The contact rating (A) for the signal relays are listed in the table below.
Inductive load* Voltage (V)
AC
DC
120
250
30
125
Resistive load
2
0.2
* cos ϕ
= 0,4 , L/R = 7 msec
2
0.1
22
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Basic Setting
햷
Rated Current
왘 RATED CURRENT
The maximum rated current can be selected as follows:
Max.rated current (I n max
) x setting (A)
0.5-0.6-0.7-0.8-0.9-1.0
AE4000-SSA/SSC:0.8–0.9–1.0
Changing this setting changes the following values proportionally:
앬
앬
Uninterrupted current (I u
)
Short-time delay current (I sd
)
앬
앬
Instantaneous current (I
Pre-alarm (I p
) i
)
Overload Protection
햸
Uninterrupted Current (I
u
)
왘 UNINTERRUPTED CURRENT
Rated current (I n
) x setting (A)
0.80-0.84-0.88-0.92-0.96-1.0
Used for setting the continuous uninterrupted current value.The actual tripping range is I u x 1.05 – 1.25.
The load current is displayed as a percentage of the uninterrupted current and thus changes proportionally when the uninterrupted current setting is changed.
Short-Circuit Protection (STD)
햽
Short-Time Delay P.U.Current (I
sd
)
왘 STD P.U.
Rated current (I n
) x setting (A)
2-3-4-6-8-10
Current threshold value setting for short-time delay tripping.
Ground Fault Protection (GFR)
헁
Ground Fault P.U.Current (I
g
)
왘 GFR P.U.
Max.rated current (I x setting (A) n max.
)
0.1-0.2-0.3-0.5
AE4000-SSA/SSC;AE4000–6300:
0.2-0.3-0.5
The function is not available when
I n max.
is less than 630 A and for
AE1000-SH I n max
630 A.
햾
Short-Time Delay Time (T
sd
)
왘 STD TIME
Time-delay setting (in seconds)
0-0.1-0.2-0.3-0.4-0.5
The setting value is the operating time when the current flowing is the short-time delay current setting (I sd
) × 1,5.
If the dial is set to 0 seconds the breaker will trip in 0.05 seconds.
햿
Short-Time Delay Lock Button
왘 STD LOCK
When measuring the instantaneous tripping current,press the short time delay operation inhibit button (STD LOCK) in order to disable the short-time-delay tripping function.
헂
Ground Fault Time (T
g
)
왘 GFR TIME
GFR time setting (in seconds)
0.3-0.8-1.5-3
The setting specifies the operating time when the current flowing is the ground fault current value setting (I g
) x 1.5.
헃
Ground Fault Trip Switch
왘 GFR TRIP / ALARM
The breaker will trip when the switch is set to the "TRIP" position.
When the switch is set to the "ALARM" position a red trip indicator LED will light up and the relay output will be activated when a ground fault occurs;the breaker will not trip,however.
The switch must be set to the "TRIP" position when the overcurrent tripping characteristic is activated (refer to p.28).
햹
Long-Time Delay Time (T
L
)
왘 LTD TIME
Time setting (in seconds)
12-25-50-100-150
This value specifies the operating time when the current flowing is the uninterrupted current set value × 2.
The pre-alarm operating time is half of the long-time-delay time setting.
햺
INST/MCR Switch
왘 INST/MCR
This switch makes it possible to select between instantaneous operation characteristic (INST) and MCR characteristic.
The MCR characteristics the abbreviationfor
Making Current Release.With this characteristic,instantaneous tripping is only possible if a short circuit occurs during switch-
ON.After the initial switch-ON,the time delay tripping characteristic is active but the instantaneous tripping is not possible.
Short-Circuit Protection (instantaneous)
헀
Instantaneous P.U.Current (I
i
)
Rated current (I n
) x setting (A)
4-6-8-10-12-16
AE5000:4-6-8-10-12
AE6300:4-6-8-10
Sets the threshold current value for instantaneous tripping.
Earth Leakage Protection (I
e
)
왘 ER P.U.
Current setting 1–2–3–5
Both external ZCT and SHT are required (see page 18 and 26 for further details).
Others
헄
Test Terminal
Test functions:
Tripping characteristics
앬
Long-time-delay (L)
Short-time-delay (S)
앬
앬
앬
Instantaneous (I)
Pre-alarm (P)
앬
Ground fault (GFR)
A special testing device is required
(see page 19).
햻
Pre-Alarm Current (I
p
)
왘 PAL P.U.
Rated current (I u
) x setting (A)
0.7-0.8-0.9-1.0-OVER
Current setting for pre-alarm activation.
Earth Leakage Protection (T
e
)
왘 (TE) ER TIME
Time setting (in seconds)
0.3–0.8–1.5–3
The setting represents the operating time when the current flowing is the earth leakage current value setting × 1,5.
The earth leakage protection facility is not illustrated because it is only possible to have either earth leakage or ground fault protection.
The bold marked values show the setting at time of shipment.
MITSUBISHI ELECTRIC
SUPER AE
23
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
M Types – General Protection
햲
Trip Indicator
Display of tripping condition:
앬
L for Long-time delay
앬
S/I for short-time delay (S) / instantaneous (I)
앬
G for ground fault (GFR)
Both an LED display (red) and a relay output are provided.
Remarks: 쐃, 쐇, 쐏
햳
Pre-Alarm Display
Pre-alarm display when a pre-determined load current is reached.
Display method:Both an LED display
(yellow) and a relay output are available.
앬
The "PAL" LED lights up when the preset value is exceeded (the relay is not
앬
앬 activated when this happens).
The relay output is activated when the
"PAL OUT" LED lights up.
The "PAL OUT" is self-holding and keeps lightning, even if the load value is again smaller than the set value.
Remarks: 쐃, 쐇, 쐏
햴
Temperature Alarm
An alarm signal is generated when the temperature of the main contacts rises above the threshold level (approx.170 °C or more).
Display methods:Both an LED indicator
(red) and a relay output are provided.
Remarks: 쐃, 쐇, 쐏
햵
Load Current Indicator
Indicates the percentage of uninterrupted current (I
L
) in the following steps
50-60-70-80-90-100-OVER.
LED indication in different colours:
앬
50 – 70 % = green
앬
앬
80 – 90 % = yellow
100 % = red
The LEDs goes out when the breaker trips.
햲
햳
햵
햸
햺
헀
헂
헁
햹
ELECTRONIC TRIP RELAY
MODEL
MPGT - 1AT
RESET
L
TRIP INDICATOR
ALARM
PAL P.U.
S/I
PAL OUT
G
TAL
LOAD CURRENT % l
L
50 70 90 100
RATED CURRENT MAX.
(CT RATING)
I
N MAX
A
RATED CURRENT In
A
PAL P.U. Ip
.92
.961.0
.88
.84
X I L
LTD P.U. I
L
1.05
1.0
1.15
1.1
1.2
X In
STD P.U. lsd
2.5
2
3
3.5 4 4.5
X In
INST P.U. li
6
4
8
10 12 16
X Iu
GFR P.U. lg
0.3
0.2
0.5
0.1
X In max.
TRIP ALARM
STD LOCK
GFR TIME
1.5
0.8
FINE
LTD TIME
20
15
25
30 4060 s lsd X 1.5
STD TIME
0.2
0.30.4 0.5
0.1
0 s
TEST
MADE IN JAPAN
OCR Alarm Contact
An alarm signal is output to the contact when the breaker is tripped by one of the following causes:
앬
L Long-time delay
앬
앬
S Short-time delay
I Instananeous trip (I)
앬
G Ground fault
Remarks: 쐋, 쐏
햿
햻
햾
햶
햴
햷
햽
헃
햶
Indicator Reset Button
Pressing this button resets the displays and the relay output.
앬
앬
앬
Trip indicator (TRIP)
Unusual temperature indicator (TAL)
Pre-alarm (PAL)
Remarks:
All functions marked in gray are included asstandardequipment(standardrelayMT1A).
This overview lists the maximum possible functionality of the units.
Trip relays with special functions (functions wich are not marked in gray) have to be ordered seperately (please refer to order
information on page 30 and 31).
Page 28 and following contain a detailled
description of all special functions.
� An external power supply for trip indication and relay control is required for all type of relays.The voltage range for the power supply must be within one of the following ranges:
- 1: AC 100–120 / 200–240 V (standard)
- 4: DC 24–60 V
(other voltages on request)
쐇 The LED will go out when the control power supply is interrupted or when the RESET button is pushed.
쐋 An external self-hold circuit is required, as the alarm signal pulse has a duration of only 0.03 sec.
쐏 The contact rating (A) for the signal relays are listed in the table below.
Inductive load* Voltage (V)
AC
120
DC
250
30
125
Resistive load
2
0.2
* cos ϕ
= 0,4 , L/R = 7 msec
2
0.1
24
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Basic Setting
햷
Rated Current
왘 RATED CURRENT
The rated current will be preset to a fixed value at time of shipment (select a value between 0.5 and 10 (AE4000-SSA/SSC:0.8
and 1.0) of the maximum rated current).
The value is stamped on the relay.
Note:
Specify the preset rated current in written form when ordering.
Overload Protection
햸
Long-Time Delay Current (I
L
)
왘 LTD P.U.
Rated current (I n
) x setting (A)
1-1.05-1.1-1.15-1.2
The breaker trips within a range from
(I
L
) x 0.95 to 1.05.
The load current is displayed as a percentage of the long-time delay current (I
L
).
The pre-alarm set value varies proportionally to the long-time delay current setting.
햹
Long-Time Delay Time (T
L
)
왘 LTD TIME
Time setting (in seconds)
15-20-25-30-40-60
This value specifies the operating time when the current flowing is the long-time delay current set value (I
L) x 1.2.
The pre-alarm operating time is half of the long-time delay setting.
햹
Long-Time Delay Time FINE(T
L
)
왘 FINE
Fine adjustment of long-time delay time.
Detailled information on request.
This setting has no influence on the pre-alarm time.
햺
Pre-Alarm (I
p
)
왘 PAL P.U.
Long-time-delay current value (I
L
) x setting
0.84-0.88-0.92-0.96-1.0
Threshold value for pre-alarm operation.
Short-Circuit Protection (STD)
햻
Short-Time Delay P.U.Current (I
sd
)
왘 STD P.U.
Rated current (I n
2-2.5-3-3.5-4-4.5
) x setting (A)
Current threshold value setting for short-time delay tripping.
햽
Short-Time Delay Time (T
sd
)
왘 STD TIME
Time delay setting (in seconds)
0-0.1-0.2-0.3-0.4-0.5
The setting value is the operating time when the current flowing is the short-time delay current setting (I sd
) x 1.5.
If the dial is set to 0 seconds the breaker will trip in 0.05 seconds.
햾
Short-Time Delay Lock Button
왘 STD LOCK
When measuring the instantaneous tripping current,press the short time delay operation inhibit button (STD LOCK) in order to disable the short-time-delay tripping function.
Short-Circuit Protection (instantaneous)
햿
Instantaneous P.U.Current (I
왘 INST P.U.
Rated current (I n
) x setting (A)
4-6-8-10-12-16
AE5000:4-6-8-10-12
AE6300:4-6-8-10
Sets the threshold current value for instantaneous tripping.
i
)
Ground Fault Protection
헀
Ground Fault P.U.Current (I
g
)
왘 GFR P.U.
Max.rated current (I n max.
0.1-0.2-0.3-0.5
) x setting (A)
AE4000-SSA/SSC,AE4000–6300:
0.2-0.3-0.5
This function is not available if max.
rated current values I n max is less than
630 A and for AE1000-SH,I n max
630 A.
헁
Ground Fault Time (T
g
)
왘 GFR TIME
Time setting (in seconds)
0.3-0.8-1.5-3
The setting specifies the operating time when the current flowing is the ground fault current value setting (I g
) x 1.5.
헂
Ground Fault Trip Switch
왘 GFR TRIP / ALARM
The breaker will trip when the switch is set to the "TRIP" position.
When the switch is set to the "ALARM" position a red trip indicator LED will light up and the relay output will be activated when a ground fault occurs;the breaker will not trip,however.
The switch must be set to the "TRIP" position when the overcurrent tripping characteristic is activated (refer to p.28).
Others
헃
Test Terminal
Test functions:
Tripping characteristics
앬
Long-time-delay (L)
Short-time-delay (S)
앬
앬
앬
Instantaneous (I)
Pre-alarm (P)
앬
Ground fault (GFR)
A special testing device is required
(see page 19).
The bold marked values show the setting at time of shipment.
MITSUBISHI ELECTRIC
SUPER AE
25
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
How to Adjust the Electronic Trip Relay
S type setting dial operation schematic – General use
INST Instantaneous P.U. Current Ii
Max. rated current In max
STD Short-Time Delay P.U. Current Isd
Rated Current In Pre-Alarm Current Ip
GFR Ground Fault P.U. Current Ig or
ER Earth Leackage Fault Current I
∆ n
Load Current Indicator LEDs
M type setting dial operation schematic – Generator protector use
INST Instantaneous P.U. Current Ii
Max. rated current In max
STD Short-Time Delay P.U. Current Isd
Rated Current In
Delay Current I
L
GFR Ground Fault P.U. Current Ig
Pre-Alarm Current Ip
Load Current Indicator LEDs
Characteristic curve for the example next page
1000
10
5
4
3
2
500
400
300
Pre-alarm current (I p
) setting range
100
60
50
40
Ground fault current (I g
) setting range
20
1
0,5
0,4
0,3
0,2
Ground fault operation time (T g
) setting range
0,1
0,05
0,04
0,03
0,02
Short-time delay operation time (T sd
) setting range
Long-time delay operation time (T
L
) setting range
Short-time delay current (I sd
) setting range
Instantaneous current (I i
) setting range
0,01
5 10 20 50 100 125 200
Current (%)
500 1000 1600 2000 5000
26
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Setting example for S Type – General use
The following example shows in a simple way how you can set your required values on the S type trip relay.
Additional all current settings and operation times are calculated and shown.
I n
= 0.8× I n max
I n
= 0.8 × 1600 A
I n
= 1280 A
I
I u
= 0.9× I n
I n
= 0.8 × 1280 A n
= 1152 A
I p
I n
I n
= 0.8 × I u
= 0.8 × 1152 A
= 921,6 A
I g
I n
= 0.1× I n max
= 0.1 × 1600 A
I n
= 160 A
GFR TIME = 0.8s
(at I g
× 1.5 =
160 × 1.5 = 240 A)
ELECTRONIC TRIP RELAY
MODEL
SPGT - C1AT
RESET
L
TRIP INDICATOR
ALARM
PAL P.U.
S/I
PAL OUT
G
TAL
LOAD CURRENT % lu
60 80 100 OVER
RATED CURRENT MAX.
(CT RATING)
I
N MAX
1600 A
RATED CURRENT
0.8 0.9 1.0
0.7
0.6
0.5
X I
N MAX
PAL P.U. Ip
0.9
1.0 OVER
0.8
0.7
X Iu
UNINTERRUPTED
CURRENT Iu
.88
.84
.92
.80
.96
1.0
STD P.U. lsd
2
3
4
X Iu
6 8 10
INST P.U. li
4
6
8
10 12 16
X Iu
GFR P.U. lg
0.5
0.3
0.2
0.1
X In max.
TRIP ALARM
STD LOCK INST MCR
GFR TIME
1.5
3.0
lu X 2 lsd X 1.5
LTD TIME
100150
50
25
12
SEC.
STD TIME
0.2
0.3 0.4 0.5
0.1
0
SEC.
TEST
MADE IN JAPAN
I n,max
= 1600 A
I sd
I sd
I sd
= 3 × I n
= 3 × 1280 A
= 3840 A
I i
I i
=12 × I n
= 12 × 1280 A
I i
= 15360 A
LTD TIME T
L
= 100 s
(at I u
× 2 =
1152 × 2 = 2304 A)
STD TIME T sd
= 0.3s
(at I sd
× 1.5 =
3840 × 1.5 = 5760 A)
Pre-alarm pick-up time
= 0.5× T
L
= 50 s
(at I u
× 2 = 1152 × 2
= 2304 A)
Actual settings are as in the following table
Functions
Max. Rated Current
Set rated value
Uniterrupted Current
Long-Time Delay Time
Short-Time Delay P.U. Current
Short-Time Delay Time
I n
I
Description
n max
I u
LTD TIME
I sd
STD TIME
Setting value
1600 A
1280 A
1152 A
100 s ± 20 % (at 2304 A)
3840 A ± 15 %
0.3 s ± 20 % (at 5760 A)
Functions
Instantaneous P.U. Current
Pre-Alarm Current
Pre-alarm pick-up time
Ground Fault P.U. Current
Ground Fault Time
I p i
I
Description
I
PAL pick-up time g
GFR TIME
Setting value
15360 A ± 15 %
921,6 A ± 10 %
50 s ± 20 % (at2304 A)
160 A ± 20 %
0.8 s ± 20 % (at 240 A)
MITSUBISHI ELECTRIC
SUPER AE
27
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Special Functions – Accessories
왎 Earth leakage protection (ER)
The earth leakage alarm facility is realised with an electronic trip relay with earth leakage protection (ER characteristics) and an external ZCT (refer to page 18 and 20).
When earth leakage current flows an
alarm is activated but the breaker does not
trip (see the earth leakage alarm system wiring diagram).
If you require the breaker to trip upon earth leakage you must also install an SHT device (see the earth leakage tripping system wiring diagram).Observe the voltage range specifications for the voltage tripping device SHT;the voltage tripping device (SHT) is suitable for 250 V AC/DC or less.
The earth leakage protection is not available for AE4000 to AE6300-SS breakers.
Earth leakage tripping system
C2
SHT
C1
N2
714
N1
713
L2 L1
Control power supply
Earth leakage tripping system
BZ
N2 N1
544
513
L2 L1
Control power supply
왎 Pre-alarm (PAL)
If the load current flowing through the breaker exceeds the preset value the "PAL"
LED lights up and a relay output is activated.This is a useful option for ensuring a continuous power supply to an important circuit.
The operating characteristic shown in the graph is proportional to half of the long-time-delay tripping characteristic.It
has been designed to prevent unnecessary alarms from inrush currents to the load.
T
L represents the long-time delay time.
The general use relay output is of a self-hold type;the relay type for generator protection features auto reset.(The control power supply and reset button required for the LED display is also used internally for the pre-alarm).
Characteristics (type S)
Time (t)
1 h
10 min.
2 min.
1 min.
30 sec
10 sec
4 sec
1 sec
0.4 sec
0.1 sec
0.04 sec
Pre-alarm characteristics
Pre-alarm operating time
Pre-alarm current setting range
Pre-alarm operating time
Overcurrent characteristics
10 20 40 60
100
200 400 1000
600 2000
4000
6000
Current (%)
왎 Ground fault protection (GFR)
When ground fault currents of several hundred amperes flow,it is possible that the long-time-delay or short-time-delay functions may not be able to protect the circuit.The ground fault function (GFR) can provide the necessary protection in these situations.Response sensitivity can be set in the range 0.1–0.2–0.3–0.5,multiplied by the maximum rated current (I
N max.
);operating time can be set in the range
0.3–0.8–1.5–3 seconds.
No control power supply is required for this function.
앬
앬
앬
Similary with a 3 pole breaker, ground fault protection is also possible for a
3-phase, 3-wire circuit.
In a 3-phase, 4-wire circuit ground fault protection is also possible if the
3-pole breaker is combined with a neutral pole CT (NCT). See page 18 for details.
The ground fault protection is not available if the max. rated current
(I
N max.) is less than 315 A or 500 A and less than 630 A for AE1000SH.
4 pole breaker
GFR
Current sensor coil
28
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
왎 Temperature alarm (TAL)
When the temperature of the main contacts exceeds a pre-determind (approx.
170° C),a LED lights up and a relay contact
(NO contact) is activated.
This helps to prevent malfunctions and increase the service life of the contacts as it makes it possible to detect even temporary temperature increases.Since the relayoutputisselfholdingatemporaryrise in temperature more than 6 hours can also be detected (the control supply and the reset button are used in common with the trip indicator).
Note:
The power supply which is required for the
LED indicators,is additionally used for the internal temperature measurement.
왎 Load current measurement (LM)
A direct current voltage signal which is converted from the effective value current in the electronic trip relay is taken out externally by using an isolation amplifier.Use the receiving indicator that can be operated by an input of 0–5 V DC since the voltage signal proportional to the largest phase current is transmitted.Moreover the voltage signal which is proportional to the largest phase current is then used to light the appropiate phase LED (the control supply is that used for the trip indicator).
Note:
Please consider that the wiring is within
3 m of the breaker control circuit terminal by using a twisted pair wire (with over
40 turns/meter).
The required control power supply for the LED indicator is common to the trip indicator
Output characteristics
10
5
0
0 25 100
→
Current (% of I
N max
)
200
Standard functions
The following functions are provided as standard for the electronic trip relays listed in this Catalogue.
왎 OCR alarm (AL)
The OCR alarm is a short-time operating contact (NO contact) that indicates when the breaker has tripped as a result of an overcurrent situation.The AL unit is integrated in the electronic trip relay.
It operates when the breaker trips due to long-time-delay,short-time-delay,instantaneous/MCR and ground fault (GFR).
It is not activated when the breaker is tripped by the earth leakage (ER) protection facility
Note:
Though control power supply is not required for the operation of the overcurrent alarm (AL),an external self-hold circuit is required since the relay output is only activated for 0.03 seconds.
When a continuous output signal from the
OCR alarm (AL) is required,please use the output signal from the trip indicators L,S/I and G,which is operated by the same causes as the OCR alarm.
왎 Neutral pole overcurrent protection (NP) in a 4-pole circuit
All electronic trip relays listed in this Catalogue are provided with 100 % Neutral pole protection for 4-pole breakers,if the fourth pole (neutral pole) is equipped with a CT.
More details on request.
MITSUBISHI ELECTRIC
SUPER AE
29
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Special Functions – Accessories
Unless otherwiseindicated,all circuitbrea- kers in the standard package are delivered with the electronic trip relay ST1A (see overview on pages 6 and 7).
If you require a different relay for a given circuit breaker,simply specify the relevant electronic trip relay separately when ordering the breaker.
The table on the right gives you an overview of different trip
relays.For detailed information please refer to page 20.
The table below gives you a selection of the most common electronic trip relays with the relevant ordering details.To order a certain relay,make sure you state the relevant order code.
Ordering procedure
Type (code)
SPT
Voltage code
1
Accessory
A
Type
Trip relay
Version
S
M
B
ST
ST-C
ST-I
SPT
SPT-C
SPT-I
SPGT
SPGT-C
SPGT-I
SPET
SPET-C
SPET-I
MT
MPT
MPGT
B-C
PAL
쏹
쏹
쏹
—
쏹
쏹
—
쏹
쏹
쏹
쏹
쏹
쏹
—
—
—
GFR
쏹
쏹
—
—
—
—
—
—
—
—
쏹
—
—
—
쏹
—
ER
쏹
쏹
쏹
—
—
—
—
—
—
—
—
—
—
—
—
—
Operating functions
MCR/C MCR/I
—
—
쏹
—
—
쏹
—
—
쏹
—
—
쏹
—
—
—
—
—
쏹
—
쏹
—
—
—
쏹
—
—
쏹
—
—
—
—
—
NP
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
쏹
AL
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
쏹
1
Voltage code
2 4
—
—
—
— — —
쎻
쎻
쎻
쎻
쎻
쎻
—
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
LM
Accessory
TAL
쏹 Function included in the relevant trip relay.
쎻 Function available as an option.
— Function either not included or not available.
Important:
The MCR function is not available for high performance breakers (i.e.the AE-SH series) and breaker types AE4000-SS up to AE6300-SS.
쎻
쎻
쎻
쎻
쎻
쎻
—
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
쎻
30
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Type Code
ST1A
ST2A
ST4A
STC1A
STC2A
STC4A
SPT1A
S
SPT2A
Description
Standard trip relay with OCR alarm (AL) without optional functions,
DC 100–125 V
MT4A
M
MPT1A
MPT4A
SPGTC2A
SPGTC4A
MT1A
SPT4A
SPGT1A
SPGT2A
SPGT4A
SPGTC1A
Trip relay with pre-alarm function (PAL), ground fault protection (GFR) and OCR alarm (AL),
AC 100-120 V and AC 200–240 V
Trip relay for generator protection with OCR alarm (AL), AC 100-120 V and AC 200–240 V
Trip relay for generator protection with OCR alarm (AL), DC 24–60 V
Trip relay for generator protection with pre-alarm function (PAL) and OCR alarm (AL),
AC 100-120 V and AC 200–240 V
MPGT1A
MPGT4A
B
BC0A Closing short-circuit current actuator with MCR characteristics and OCR alarm (AL)
Relay for frame sizes AE5000-SS and AE6300-SS on request.
Application
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS/SH, AE4000-SS
AE4000-SSA/SSC
AE1000–AE3200-SS
On request
136000
On request
136001
On request
136002
On request
136003
On request
136004
On request
136005
On request
136006
On request
136011
135994
On request
135995
On request
135996
On request
135997
On request
135998
On request
135999
Art. no.
135976
On request
135977
On request
135978
On request
135979
On request
135980
On request
135981
On request
135992
On request
135993
On request
SPT4A-SAE
SPT4A-SAE-45
SPGT1A-SAE
SPGT1A-SAE-45
SPGT2A-SAE
SPGT2A-SAE-45
SPGT4A-SAE
SPGT4A-SAE-45
SPGTC1A-SAE
SPGTC1A-SAE-45
SPGTC2A-SAE
SPGTC2A-SAE-45
SPGTC4A-SAE
SPGTC4A-SAE-45
MT1A-SAE
MT1A-SAE-45
MT4A-SAE
MT4A-SAE-45
MPT1A-SAE
MPT1A-SAE-45
MPT4A-SAE
MPT4A-SAE-45
MPGT1A-SAE
MPGT1A-SAE-45
MPGT4A-SAE
MPGT4A-SAE-45
BC0A-SAE
Ordering information
ST1A-SAE
ST1A-SAE-45
ST2A-SAE
ST2A-SAE-45
ST4A-SAE
ST4A-SAE-45
STC1A-SAE
STC1A-SAE-45
STC2A-SAE
STC2A-SAE-45
STC4A-SAE
STC4A-SAE-45
SPT1A-SAE
SPT1A-SAE-45
SPT2A-SAE
SPT2A-SAE-45
MITSUBISHI ELECTRIC
SUPER AE
31
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Operating Characteristics Type S
Braker types AE1000-SS/SH to AE3200-SS/SH, AE4000-SSA/SSC, AE4000-SS to AE6300-SS
1000
500
400
300
200
Pre-alarm current (I p
) setting range
Uninterruptedcurrent×setting 0.7-0.8-0.9-1.0-OVER× I u
±10%
Long-time delay operation time (T
L
) setting range
(Uninterrupted current × 2) 12-25-50-100-150 sec ± 20%
Pre-alarm operation time (T p
)
Long-time delay operation time T
L
× 0.5 ± 20%
100
60
50
40
30
20
10
Ground fault current (I
0.1-0.2-0.3-0.5× I g n max
) setting range
Max. rated current × setting
± 20%
0,10.2-0.3-0.5× I n max
± 20%
5
4
3
2
1
Short-time delay current (I sd
Rated current × setting
2-3-4-6-8-10 × I n
± 15 %
) setting range
0,5
0,4
0,3
0,2
Ground fault operation time (T g
) setting range
(Ground fault current I g
× 1.5) 0.3-0.8-1.5-3sec ± 20%
0,1
0,05
0,04
0,03
0,02
0,01
2
Setting at shipment
Adjustable
Short-time delay operation time (T sd
) setting range
(Short-time delay current I sd
× 1.5) 0-0.1-0.2-0.3-0.4-0.5 sec ± 20%
5 10
Current
Instantaneous current (I i
) setting range
Rated current × setting
4-6-8-10-12-16 × I n
± 15%
4-6-8-10-12 -16 × I n
± 15% AE5000-SS
4-6-8-10 -12-16 × I n
± 15% AE6300-SS
20 50
Long time delay, pre-alarm
Short-time delay / instantaneous
Ground fault
100125 200 500
% of uninterrupted current (I u
)
% of rated current (I n
)
% of max. rated current (I n max
)
1000 16002000 5000
32
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
ELECTRONIC TRIP RELAY
Operating Characteristics Type M
Breaker types AE1000-SS/SH to AE3200-SS/SH, AE4000-SSA/SSC, AE4000-SS to AE6300-SS
1000
Long-time delay current (I
L
Rated current × setting
) setting range
1.0-1.05-1.1-1.15-1.2 × I n
± 15%
500
400
300
200
Pre-alarm current (I p
) setting range
Long-time delay current × setting
0.84-0.88-0.92-0.96-1.0× I
L
± 20%
Long-time delay operation time (T
L
)settingrange
(Long-time delay current × 1.2) 15-20-25-30-40-60 s ± 20%
Pre-alarm operation time (T p
)
Long-time delay operation time T
L
× 0.5 ± 20%
100
60
50
40
30
20
Ground fault current (I g
) setting range
Max. rated current × setting
0.1-0.2-0.3-0.5 × I
0,10.2-0.3-0.5 × I n max
± 20%
± 20%
10
Short-time delay current (I sd
) setting range
Rated current × setting 2-2.5-3-3.5-4-4.5× I n
± 20%
5
4
3
2
1
0,5
0,4
0,3
0,2
Ground fault operation time (T g
) setting range
(GroundfaultcurrentI g
×1.5) 0.3-0.8-1.5-3s ± 20%
0,1
0,05
0,04
0,03
0,02
0,01
2
Setting at shipment
Adjustable
5
Short-time delay operation time (T s
) setting range
(Short-time delay current I sd
× 1.5) 0-0.1-0.2-0.3-0.4-0.5 s ± 20%
10
Instantaneous current (I i
) setting range
Rated current × setting
4-6-8-10-12-16 × I n
± 15%
4-6-8-10-12 -16 × I n
± 15% (AE5000-SS)
4-6-8-10 -12-16 × I n
± 15% (AE6300-SS)
Current
20 50 100 120 200 500
Pre-alarm
Long-/Short-time delay / instantaneous % of rated current (I
Ground fault
% Long time delay current (I
L n
)
% of max. rated current (I n max
)
)
1000
1600 2000
5000
MITSUBISHI ELECTRIC
SUPER AE
33
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Wiring diagram – Super AE air circuit breakers with electronic trip relay type S or M
The following circuit diagram shows the breaker with fully equipped accessories.
2000 V
Dielectric voltage
EN 50005
342 344 332 334 322 324 312 314
CLb CLa CLb CLa CLb CLa CLb CLa
Reset
1500 V
Dielectric voltage
Xa
L1
R+
TAL G / E
564 544 513
T5 T3 T0+
97
AL+
CL
CL CL CL
AL
EN 50005
CLc
341
CLc
331
CLc
321
CLc
311
R2– R1– T4– T2–
L3 L2 554 534
T1–
524
AL–
98
P S/I L
Cell switches
Description of terminal layout
Terminal
13/14, 23/24, 33/34,
43/44, 53/54
Code Function
AXa Auxiliary switch contact a
AXb Auxiliary switch contact b
413 / 414
U1 / U2
A1 / A2
C1 / C2
J1 / J2
713 / 714
TS Charged signal
MD Motor charging
CC Closing coil
SHT Shunt trip
UVT Under-voltage trip
ER Earth leakage trip
Remark
NO contact
NC contact
NO contact
Terminal
N1 / N2
Code Function
NP Neutral pole CT or ext. ZCT
Remark
M1 / M2
LM Load current measurement
97 / 98
AL OCR alarm contact
513/524/534/544
TRIP Trip indication contact L, S/I, G or E
513 / 554
PAL Pre-alarm indication contact
513 / 564
L1 / L2 / L3
311 – 344
TAL Temperature alarm indication contact
Signal
Signal
Signal
— Electronic trip relay unit control power supply See table on p. 35
— Cell switches (drawout type breakers only) e.g. for SHT trip
34
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
When using coil loads such as DC magnetic switches,etc.as operating voltage in the peripheral circuits,install diodes,surge absorbers,etc.as a countermeasure against surge (counter electromotive force) at the time of switching.On the
2000 V
Dielectric voltage drawout type,the control circuit terminal block should be moved to the left or right by 5 mm after the cables are connected.
OFF ON
OFF
M1 N1
LM+ CT+
713
ST+
J1
U+
C1 A1 U1 413 51 41 31 21 11 53 43 33 23 13
S+ CC+ M+ TS+ B10+ B9+ B8+ B7+ B6+ A5+ A4+ A3+ A2+ A1+
ON
UVT SHT CC
M
AX AX AX AX AX AX AX AX AX AX
LM– CT– ST– U–
M2 N2 714 J2
S– CC– M–
C2 A2 U2
TS–
414
B10–
52
B9–
42
B8–
32
B7–
22
B6–
12
A5–
54
A4–
44
A3– A2– A1–
34 24 14
SHT
Under-voltage trip
Charged signal Auxiliary switches
Power supply for electronic trip relay
Electrical connection
Voltage
AC
100–120 V
200–240 V
DC
100–125 V
DC
24–60 V
+
–
—
—
+
–
L1
쏹
쏹
쏹
Terminals
L2
쏹
L3
쏹
쏹
쏹
쏹
Description of symbols for the accessory
Description
Symbol Function
M
CC
SHT
UVT
Motor
Closing coil
Shunt trip device
Undervoltage trip device
S/I
Short-time delay trip indication lamp
Symbol Function
G or E
P
TAL
Ground fault trip or earth leakage indication lamp
Pre-alarm indication lamp
Unusual temperatur indication lamp
Self-holding relay
Wiring by factory
Wiring by customer
MITSUBISHI ELECTRIC
SUPER AE
35
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Fixed Type Breaker
Breaker types AE1000 to AE3200-SS/SH with standard connection (horizontal terminals)
Operating panel center
Control terminals
A B
N
eutral pole
268
3P 4P
144 88
N
eutral pole
H H H
J
4 x Ø 14
38
Breaker type
AE1000 – 1600-SS
AE2000 – 3200-SS
AE1000 – 3200-SH
C*
E
228
D*
F
Frontview
K
31
40
175*
290
288
Sideview
4P 3P
23
AE2000–3200-SS
AE1000–3200-SH
Rearview
AE2000–3200-SS
AE1000–3200-SH
3
4
3
4
Pole A
3 142
B
142
C
156
D
156
E
170
F
170
G
15
4 142 227 156 241 170 255 15
232
232
232
232
187
317
187
317
246
246
246
246
201
331
201
331
260
260
260
260
215
345
215
345
20
20
20
20
H
85
85
130 95
130 95
130 95
130 95
J
50
50
70
70
40
40
K
40
40
AE1000–1600-SS
38
17
2 - Ø 13
Main circuit terminal
38
17
4 - Ø 13
[mm]
Door frame and panel-cut
Panel-cut
Operating panel center
Door frame panel-cut
Operating panel center
8 - Ø 7
235 Breaker frame
247
271
Breaker frame
[mm]
36
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Breaker types AE1000 to AE3200-SS/SH with Vertical terminal adapter (VAT)
AE1000–1600-SS
Version A
85 85 85
N
eutral pole
T 50
4P 3P
X
Breaker
AE1000–1600-SS
AE2000–2500-SS
AE3200-SS
AE1000–2500-SH
AE3200-SH
X
108
123
123
153
153
20
25
20
25
T
15
Operating panel center
130 130
23
130
Version B
T
N
eutral pole
100
4P 3P
X
[mm]
Vertical terminal adapter (VTA)
Version A
Connecting area
38
15
Version B
38
2 - Ø 13
15
4 - Ø 13
15
Breaker
AE1000–1600-SS
AE2000–2500-SS
AE3200-SS
AE1000–2500-SH
AE3200-SH
Version
B
B
A
B
B
T
25
20
15
20
25
100
38
2 - Ø 13
Connecting area
115
38
15
5 - Ø 13
[mm]
MITSUBISHI ELECTRIC
SUPER AE
37
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Drawout Type Breaker
Breaker types AE1000 to AE3200-SS with standard connection (horizontal terminals)
Operating panel center
A
228
B
Control terminals
Disconnected position
Test position
51
35
E
Neutral pole
3P 4P
Operating panel center
K K K
N
eutral pole
L
15
59
42,5
C
200
*
D
Earth terminal
(gegenüberliegende Seite)
23
61
H
F
G
40
220
*
48
452
Drawout position
Breaker
AE1000–1600-SS
AE2000–3200-SS
4 x Ø14
Front view Side view
Pole A B C D E F G H J K L
3 150 150 149 149 311 368 366 172 15 85 50
4 150 235 149 234 311 368 366 172 15 85 50
3 243 195 239 194 311 368 366 172 25 130 103
4 243 325 239 324 311 368 366 172 25 130 103
AE1000–1600-SS
38
15
2 - Ø 13
4P 3P
Rear view
AE2000–3200-SS
38
15
Main circuit terminal
23
4 - Ø 13
[mm]
Drawout handle, door frame and panel-cut
Drawout handle Panel-cut
Operating panel center
Door frame panel-cut
8 - Ø 7 max.173
200
Ø 22
Breaker
235
247
271
[mm]
38
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Breaker types AE1000 to AE3200-SS with vertical terminal adapter
85 85 85
AE1000–1600-SS
Version A
N
eutral pole
T
50
131
AE2000–3200-SS
Version B
4P 3P
T
N
eutral pole
Operating panel center
130 130
23
130
100
Breaker
AE1000–1600-SS
AE2000–2500-SS
AE3200-SS
20
25
T
15
4P 3P
146
[mm]
Vertical terminal adapter (VTA)
Version A
Connecting area
38
15
Version B
38
2 - Ø 13
15
4 - Ø 13
15
Breaker
AE1000–1600-SS
AE2000–2500-SS
AE3200-SS
Version
A
B
B
T
15
20
25
100
38
2 - Ø 13
Connecting area
115
38
15
5 - Ø 13
[mm]
MITSUBISHI ELECTRIC
SUPER AE
39
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Drawout Type Breaker
Breaker types AE1000 to AE3200-SH with standard connection (horizontal terminals)
External accessory
(e.g. UVT controller)
243
Operating panel center
228
Control terminals
3P: 195
4P: 325
3P 4P
Neutral pole
Disconnected position
Test position
51
35
341 handle radius 100
Operating panel center
130
23
130 130
N
eutral pole
B
15
33
4 x Ø14
265
42,5
200
*
Drawout handle insertion port
3P: 220
4P: 350
2 x Ø12 screw M8 liegende Seite)
Front view
23
61
202
220
*
398
40
396
Side view
48
452
Drawout position
4P 3P
Rear view
38
15
Breaker
AE1000–2500-SH
AE3200-SH
A
20
25
B
95
103
4 - Ø 13
[mm]
Drawout handle, door frame and panel-cut
Drawout handle Panel-cut
Operating panel center
Door frame panel-cut
8 - Ø 7 max.173
200
Ø 22
Breaker
235
247
271
[mm]
40
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Breaker types AE1000 to AE3200-SH with vertical terminal adapter
Operating panel center
130 130
23
130
T
100
Neutral pole
4P 3P
146
Breaker
AE1000–2500-SH
AE3200-SH
T
20
25
[mm]
Vertical terminal adapter (VTA)
4 - Ø 13
15
38
Connecting area
115
38
15
5 - Ø 13
Breaker
AE1000–2500-SH
AE3200-SH
Vers.
B
B
T
20
25
[mm]
MITSUBISHI ELECTRIC
SUPER AE
41
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Fixed Type Breaker
Breaker typ AE4000-SSA (Fixed with vertical terminal)
Operating panel center
232 4P: 317 (3P:187)
268
Control terminals
Neutral pole
3P 4P
144 88
Panel
7
4 x Ø14
38
228
246
*
260 4P: 345 (3P: 215)
Operating panel center
152
31
11
Front view
23
152
95
* Mounting pitch
Neutral pole
31
136
40
175
*
290
31
11
Operating panel center
145
288
Side view
30,5
145 145
95
10
Rear view 3-poles
Main circuit terminals
20
48
10
Rear view 4-poles
Door frame and panel-cut
Panel-cut
Operating panel center
Door frame panel-cut
8 - Ø 7
[mm]
5 - Ø 13,5
235
247
271
[mm]
42
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Drawout Type Breaker
Breaker typ AE4000-SSA (Drawout with vertical terminal)
Operating panel center
243
228
4P: 325 (3P: 195)
3P
Control terminals
4P
Neutral pole
311
51
35
Disconnected position
Test position
15
59 239
42,5
200
*
4 x Ø14
4P: 324 (3P: 194)
Front view
23
190
Operating panel center
190
* Mounting pitch
52
10
52
10
172 40
109
23 220
*
368
366
Side view
Operating panel center
170 170
43
170
48
452
Drawout position
11 11
197 242
Rear view 3-poles
Neutral pole
327
Rear view 4-poles
242
[mm]
Main circuit terminals
Connecting area
20
48
Drawout handle
Drawout handle, door frame and panel-cut
Panel-cut
Operating panel center
Door frame panel-cut
8 - Ø 7 max.173
200
Ø 22
5 - Ø 13,5
Breaker
235
247
271
[mm]
MITSUBISHI ELECTRIC
SUPER AE
43
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Fixed/Drawout Type Breaker
Breaker typ AE4000-SSC (Fixed with vertical terminal)
Operating panel center
Control terminals
232 317
Drawout handle insertion
268
144 88
42,5
195
Operating panel center
195
70
10
10
7
4 x Ø14
38
246
*
260
228
331
*
345
Front view
* Mounting pitch
Breaker typ AE4000-SSC (Drawout with vertical terminal)
Operating panel center
Control terminals
243 325
228
31
136
Side view
40
175
*
290
288
311
Panel
Inside of the panel
(thickness 1.6 to 3.2)
51
35
Disconnected position
Test position
Rear view
[mm]
42,5
195
70
10
10
Operating panel center
195
90
10
10
59 239
42,5
200
*
4 x Ø14
324
Drawout handle insertion port
Front view
Earth terminal
(on opposite side)
146
23
172
220
*
368
366
40
* Mounting pitch
Side view
48
452
Drawout position
25
Main circuit terminals
Fixed type Drawout type
Drawout handle, door frame and panel-cut
Drawout handle
* please check before mounting!
Panel-cut
Operating panel center
53
20
*
48 max.173
200
Ø 22
15
493
Rear view
Door frame panel-cut
8 - Ø 7
[mm]
5 - Ø 13
Breaker
Recommendation:
Fixed type:
Drawout type:
Main circuit terminals per pole: 3 × connection bus bar T × B: 10 × 150 mm
Main circuit terminals for pole L1, L3: 4 × connection bus bar T × B: 10 × 150 mm
Einschubtechnik: Main circuit terminals for pole L2 : 3 × connection bus bar T × B: 10 × 150 mm
235
Type
Fixed type
Drawout type
A
179
195
247
271
[mm]
44
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Breaker
Breaker types AE4000 to AE6300-SS with standard connection (vertical)
Operating panel center
28
373,5
228
Control terminal
3P: 458,5
4P: 588,5
3P
Neutral Pole
28
4P
Test position
Disconnect position
311
51
35
44
Neutral Pole
42,5
530
*
345,5
Befestigungsschrauben
2 x M12
Earth terminal schraube M8
6 x M12
395 3P: 480
4P: 610
4P
3P: 431,5
4P: 561,5
*
*
196
42,5
262
3P
Front view
Operating panel center
431,5
*
262
Mounting screws M12
* Mounting pitch
Erdungsanschlußschraube M8
(gegenüberliegende Seite)
Side view
15
123
23
172
220
*
40
368
366
48
400
Drawout position
53
25
103
25
X
Y
Type
AE5000-SS
AE6300-SS
Dimensions**
X Y
100
105
20
25
** please check before mounting!
5 -
Ø
13
Rear view
Main circuit terminals
[mm]
Drawout handle, door frame and panel-cut
Drawout handle Panel-cut
Operating panel center
Door frame panel-cut
8 -
Ø
7 max.173
200
Ø
22
Breaker
235
247
271
Breaker frame
[mm]
MITSUBISHI ELECTRIC
SUPER AE
45
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Dimensions – Accessory
External ZCT for load circuits
F
E
Type
C
D
E
A
B
H
J
F
G
230
60
104
200
323
250
47
72
92
370
108
104
200
460
400
47
72
92
500
108
104
200
600
550
48
72
92
A
[mm]
External ZCT for transformer ground wire
E
For M5
H
A
F
6
7,7
B
ZT15A – 40 A
7
30
100
A
B
ZT60A – 100 A
Type
A
B
C
D
G
H
E
F
15A
48
15
29
62
70
25
46
15
68
30
37
82
90
50
66
30
85
40
43
92
81
40
100
50
140
60
73
150
46
160
80
82
169
48
185
100
93
190
50
[mm]
Condenser trip device (COT)
Front view
90
Side view
Screw M4
UVT controller, external power supply (PS)
6.5
215 14.5
Terminal screw M3.5
Ø
104
45 45
4-R6
75
110,6
13,3
16
15,4
87
90
106
11
45
182.2
14.6
[mm] [mm]
46
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Operating Conditions, Technical Information
Insulation clearances at the supply side
When a short-circuit current is interrupted by the breaker,ionised gases flow out of the exhaust openings of the arc extinguishing chamber.This makes it necessary to observe the insulation clearance shown in the table on the right.
The clearances required for maintenance work have also been taken into consideration in the table.
Electrical equipment, appliances and screen
B B
C
Breaker type
Applicable voltage
A
햲
Fixed type
Drawout type
C
B
햴
D
햳
A
햲
B
햴
C
D
햳
AC 600 V
0
50
162
50
0
50
240
50
AC 660, 690 V
100
50
162
50
100
50
240
50
200
50
—
200
AC 690 V
200
50
—
200
[mm]
햲
햳
햴
A clearance of 300 mm or more is necessary for inspection of the arc extinguishing chambers and main contacts.
The dimension D represents the wiring space required for the control terminal block.
Dimension B becomes larger when the breaker is fitted with the UVT controller, mechanical interlock, door interlock, etc. Further details available on request.
Normal service conditions
If all the following normal working conditions are satisfied (and not specified otherwise) the AE series air circuit breakers may be used:
앬
앬
Ambient air temperature
Range min.–5 °C to max.+40 °C (the average value however should not exceed +35 °C in any 24-hour period).
Altitude
앬
앬
앬
앬
2000 m (6600 feet) or less
Environmental conditions
The air must be free of dust and corrosive gases.Do not use and store in atmospheres with sulfide gas,ammonia gas etc.(H
2
S
≤
0,01 ppm,SO
2
≤
0,1 ppm,NH
3 not measurable).
The relative humidity should be of 85% or less at a max.of +40 °C.
Installation conditions
When installing AE series circuit breakers always follow the instructions provided in the catalogue and in the instruction manual.
Storage temperature
A range of max.+60 °C to min.-20 °C is recommended to store.
However,the average over 24 hours must not exceed +35 °C.
Replacement
Lifetime is approx.15 years.For detailed information please refer to the instruction manual.
Special service conditions
In case of special service conditions,modified circuit breakers are available (please specifiy when ordering).Service life may be shorter dependend on service conditions.
앬
Special environmental conditions
Using breakers in a high temperature and/or humidity environment can result in deterioration of insulation durability and other electrical or mechanical features.Breakers used in such environments should be specially treated to a higher corrosion proof specification and against moistural fungus.Where corrosive gases are present in the environment it is recommended that breakers to a higher corrosion proof specification are ordered (further details on request).
앬
앬
앬
Special ambient temperature
If the ambient temperature exceeds +40 °C,the continuous current rating must be reduced.The reduction value depends on the applicable standard (please refer to the following page).
Special altitude
When breakers are used at altitudes above 2,000 m the heat radiation rate is reduced,decreasing the operation voltage, uninterrupted current and breaking capacity.Reduced atmospheric pressure can also reduce insulation durability.
Further details available on request.
Installation in a separate cabinet
If the breaker is installed in a special cabinet,the following clearances have to be taken into consideration.
Rear plate
Upper plate
120 120
Door
Lower plate
Cabinet walls metal or plastic
Example:
The smallest possible cabinet dimensions for 3-pole Super AE breakers with up to 1600 A are:Hight=680 mm,Width=540 mm,
Depth=368 mm.
MITSUBISHI ELECTRIC
SUPER AE
47
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Internal resistance, reactance and power consumption (per pole)
Standard series "SS"
AE1000-SS
AE1250-SS
AE1600-SS
AE2000-SS
AE2500-SS
AE3200-SS
AE4000-SS
AE5000-SS
AE6300-SS
Breaker type
AE4000-SSA
AE4000-SSC
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Drawout
Drawout
Drawout
40
80
41
77
50
113
38
60
26
40
224
210
275
340
72
143
144
240
128
0.063
0.095
0.047
0.071
0.047
0.071
0.060
0.091
0.060
0.091
0.072
0.062
0.062
0.062
0.048
0.072
0.048
0.072
0.048
0.016
0.030
0.010
0.020
0.008
0.018
0.026
0.040
0.024
0.038
0.007
0.014
0.009
0.015
0.008
0.014
0.013
0.011
0.0085
Breaker type
AE1000-SH
AE1250-SH
AE1600-SH
AE2000-SH
AE2500-SH
AE3200-SH
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
Fixed
Drawout
High performance series "SH"
0.014
0.024
0.012
0.022
0.010
0.020
0.018
0.028
0.016
0.026
0.009
0.016
0.047
0.071
0.047
0.071
0.047
0.071
0.047
0.071
0.047
0.071
0.048
0.072
Deratings (A) by ambient temperature
Standard
DNV, BV ture= 45 °C)
60 °C
45 °C
50 °C
55 °C
60 °C
40 °C
45 °C
50 °C
55 °C
1000
1000
1000
1000
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1250
1250
1200
1600
1600
1600
1550 (1600)
1200 (1250) 1500 (1600)
1600
1600
1550 (1600)
1500 (1600)
2000
2000
2000
2000
2000
2000
2000
2000
2000
2500
2500
2500
2450
2350
2500
2500
2450
2350
3200
3200
3200
3000
2900
3200
3200
3050
2900
4000
—
3650
3300
—
—
—
—
—
4000
3800
3650
3500
3300
—
—
—
—
4000
4000
4000
3900
3750
4000
4000
3900
3750
All data in the above table are based on test conditions, connecting methods and size of the mounting rails conforming to IEC947-2, EN60947-2, VDE0660 etc.
The figures in brackets ( ) in the table above indicate the reduced current values exclusive to AE-SH series.
4750
5000
5000
5000
4750
5000
5000
5000
5000
48
88
36
61
63
125
25
41
18
28
92
164
5200
6000
5750
5500
5200
6300
6000
5750
5500
Connection arrangements
The following connecting methods are available for the AE type air circuit breaker.
Mounting method
Connection Horizontal connection
Standard
Vertical connection
Optional
Front connection
Optional
Vertical terminal adapter
Accessory
Front terminal adapter
Optional
Fixed type
——— ———
(Standard)
(FIX-VTA) (FIX-FTA)
Drawout type
(Standard) (DR-VT) (DR-FT) (DR-VTA) (DR-FTA)
Remark
48
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SPECIFICATIONS
Specifications for marinal standards
SUPER AE
Rated current (A)
Rated insulation voltage (V) 50/60 Hz
Series Standard series "SS"
Breaker type AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SSC AE4000-SS AE5000-SS AE6300-SS
I
N max
1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
Ui 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Rated operating voltage (V) 50/60 Hz
Number of poles
Ir
LR
DNV with instantaneous trip
Ue
AC690V
AC600V
AC500V
AC690V
690
3
500
≤
In
≤
1000
65
50
50
—
690
3
50
—
65
50
690
3
65
50
50
—
690
3
85
50
50
65
690
3
85
50
50
65
85
50
50
65
690
3
≤
In
≤
1250 800
≤
In
≤
1600 1000
≤
≤
In
In
≤
≤
2000
≤
In
≤
2500 1600
≤
In
≤
3200
3
3200
3200
≤
≤
In
≤
≤
(fürLR)
3800
3500
690
3
690
3
690
3
2000
≤
In
≤
4000 2500
≤
In
≤
5000 3150
≤
In
≤
6300
51,1
67
86.6
—
—
87
133
—
—
87
133
—
—
87
133
—
Ics
(kA, eff, sym.)
GL with instan-
AC600V
AC500V
AC690V
AC600V
AC500V
—
65
50
—
65
—
65
50
—
65
—
65
50
—
65
50
65
65
85
85
50
65
65
85
85
50
65
65
85
85
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
I
CU
= I
CS
BV
NK
LR
DNV with instan-
GL
BV
NK
—
—
—
87
133
—
211
330
—
—
—
—
211
330
—
—
—
—
—
—
—
—
65
85
113
147
199
—
—
—
—
143
196
—
—
—
—
—
85
65
50
65
85
106
143
196
106
143
196
187
143
196
106
143
196
105
143
85
65
50
65
85
106
143
196
106
143
196
187
143
196
106
143
196
105
143
85
65
50
65
85
106
143
196
106
143
196
187
143
196
106
143
196
105
143
65
50
50
—
65
106
—
151
106
—
151
143
112
147
106
—
151
105
—
50
—
65
50
65
106
—
151
106
—
151
143
112
147
106
—
151
105
—
65
50
50
—
65
106
—
151
106
—
151
143
112
147
106
—
151
105
—
AC690V
AC600V
AC500V
AC600V
AC500V
AC690V
AC600V
AC500V
AC690V
AC600V
AC500V
AC690V
AC600V
AC500V
AC690V
AC600V
AC500V
AC600V
AC500V
—
—
—
87
133
—
211
330
—
—
—
—
211
330
—
—
—
—
—
—
—
—
87
133
—
211
330
—
—
—
—
211
330
—
—
—
—
—
* Further current ratings on request.
SUPER AE
Rated current(A)
Rated insulation voltage (V) 50/60 Hz
Rated operating voltage (V) 50/60 Hz
Number of poles
Adjustment range
(A) Ir
Series High performance series "SH"
Breaker type AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH
I
N max
Ui
Ue
1000
1000
690
3
500
≤
In
In
≤
1000
≤
1250
1000
690
In
3
≤
1250 800
≤
1600
1000
690
In
3
≤
1600 1000
2000
1000
≤
690
3
In
≤
2000 1250
2500
1000
≤
690
3
In
≤
2500 1600
3200
1000
690
≤
3
In
≤
3200
I
Br. duty: O-t-CO-t-CO
CU
= I
CS
LR
NK
LR
NK with instan-
AC690V
AC600V
AC500V
AC600V
AC500V
AC690V
AC600V
AC500V
AC600V
AC500V
173
211
330
—
317
68
87
133
—
130
173
211
330
—
317
68
87
133
—
130
173
211
330
—
317
68
87
133
—
130
173
211
330
—
317
68
87
133
—
130
173
211
330
—
317
68
87
133
—
130
173
211
330
—
317
68
87
133
—
130
MITSUBISHI ELECTRIC
SUPER AE
49
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
SOFTWARE
왎 Calculation and Selection Software MELSHORT2
Circuit diagram of the network to be calculated,with input field
MELSHORT2 – The New Calculation Software for
Low-Voltage Switchgear
MELSHORT2 is a software package that provides all the functions needed for planning and dimensioning switchgear systems.
Increasingly demanding technical specifications and accountability regulations are making switchgear configuration much more critical than it used to be.In the past,software for calculating and dimensioning switchgear was helpful – nowadays it’s absolutely essential.
Mitsubishi Electric’s MELSHORT2 is a complete software package that provides all the functions needed for successful switchgear system configuration and layout.It supports all modern international electrical engineering standards and shines with simple and reliable operation.
The program calculates the short-circuit levels and currents at all necessary points for all switchgear components,including the power supply transformer and circuit breakers,the emergency generators,the individual motor and capacitor group branch circuits and all the other power distribution circuits,down to the last circuit breaker.This makes it possible to select the ideal breaker for every task,for optimum performance and cost-efficiency.
MELSHORT2 has a comprehensive range of powerful,easy-to-use functions,including:
앬
Selective shutdown
Backup protection
앬
앬
앬
Coordination with the main power supply systems
Allowance for the start-up currents of electric motors
These functions make it possible to optimise the configuration of your switchgear equipment for the specific requirements of your applications.
The calculated results,the hardware model suggestions and the wiring diagram with all the relevant values can be processed and used as documentation for the switchgear installation.Another
welcome extra is the free Internet update service.
Display of the trip curves of a circuit breaker in the network
Specifications
Operating system
Disk type
Order information
MELSHORT2
MS Windows 95/98/NT4.0/2000
CD-ROM
Art. no. 129115
50
SUPER AE
MITSUBISHI ELECTRIC
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
INDEX
A
Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Auxiliary switch (AX), (HAX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
C
Calculation Software MELSHORT2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Cell switch (CL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Charging completion switch (TS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Charging handle (manual charging) . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Condensor trip device (COT). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 46
Connection arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Current transformer (CT). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
D
Drawout handle . . . . . . . . . . . . . . . . . . . . . . . . . 8, see also Dimensions
Drawout interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
E
Earth leakage protection (ER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
External power supply (PS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19, 46
External current transformer (ZCT) . . . . . . . . . . . . . . . . . . . . . . . . 18, 46
F
G
Ground fault protection (GFR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
I
Insulation clearance at the supply side . . . . . . . . . . . . . . . . . . . . . . . 47
Interlock device (CYL, CAL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Internal resistance per pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
L
Load current measurement (LM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
M
Mechanical interlock (MI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mis-insertion preventer (MIP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
N
Neutral current transformer (NCT). . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Neutral pole overcurrent protection (NP) . . . . . . . . . . . . . . . . . . . . . 28
O
Operating characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32–33
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 7, 31
Overcurrent OCR-Alarm (AL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
P
Power consumption per pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Push button cover (BC-L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
R
S
Shorting b-contact (SBC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
T
Temperature alarm (TAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
U
Undervoltage trip device (UVT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
V
Vertical terminal adapter (VTA) . . . . . . . . . . 15, see also Dimensions
W
MITSUBISHI ELECTRIC
SUPER AE
51
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
HEADQUARTERS
MITSUBISHI ELECTRIC
EUROPE B.V.
German Branch
Gothaer Straße 8
EUROPE
D-40880 Ratingen
Phone: +49 (0)2102 486-0
Fax: +49 (0)2102 486-1120 e mail: [email protected]
FRANCE
MITSUBISHI ELECTRIC
EUROPE B.V.
25, Boulevard des Bouvets
F-92741 Nanterre Cedex
Phone: +33 1 55 68 55 68
Fax: +33 1 55 68 56 85 e mail: [email protected]
MITSUBISHI ELECTRIC
IRELAND
EUROPE B.V.
Irish Branch
Westgate Business Park, Ballymount
IRL-Dublin 24
Phone: +353 (0) 1 / 419 88 00
Fax: +353 (0) 1 / 419 88 90 e mail: [email protected]
MITSUBISHI ELECTRIC
ITALY
EUROPE B.V.
Italian Branch
C.D. Colleoni - P. Perseo Ing. 2
Via Paracelso 12
I-20041 Agrate Brianza (MI)
Phone: +39 (0) 39 / 60 53 1
Fax: +39 (0) 39 / 60 53 312 e mail: [email protected]
MITSUBISHI ELECTRIC
EUROPE B.V.
SPAIN
Carretera de Rubí 76-80
E-08190 Sant Cugat del Vallés
(Barcelona)
Phone: +34 9 3 / 565 3131
Fax: +34 9 3 / 589 2948
MITSUBISHI ELECTRIC
EUROPE B.V.
UK Branch
Travellers Lane
GB-Hatfield Herts. AL10 8 XB
Phone: +44 (0) 1707 / 27 61 00
Fax: +44 (0) 1707 / 27 86 95
UK
e mail: [email protected]
MITSUBISHI ELECTRIC
JAPAN
CORPORATION
8-12,1 chome, HARUMI CHUO-KU,
Office Tower „Z“ 14 F
Tokyo 104-6212
Phone: +81 3 6221 6060
Fax: +81 3 6221 6075
MITSUBISHI ELECTRIC
AUTOMATION
500 Corporate Woods Parkway
Vernon Hills, Illinois 60061
Phone: +1 (0) 847 / 478 21 00
Fax: +1 (0) 847 / 478 22 83
USA
EUROPEAN REPRESENTATIVES
Emac S.A.
Industrialaan 1
B-1702 Groot-Bijgaarden
Phone: +32 (0) 2 / 481 02 11
Fax: +32 (0) 2 / 481 03 01 e mail: [email protected]
INEA CR d.o.o.
Drvinje 63
BELGIUM
CROATIA
HR-10000 Zagreb
Phone: +385 (0) 1 / 36 67 140
Fax: +385 (0) 1 / 36 67 140 e mail: —
AutoCont .
Control Systems s.r.o
Nemocnicni 12
CZ-702 00 Ostrava 2
CZECH REPUBLIC
Phone: +420 59 / 6152 111
Fax: +420 59 / 6152 562 e mail: [email protected]
louis poulsen industri & automation
Geminivej 32
DK-2670 Greve
Phone: +45 (0) 43 / 95 95 95
DENMARK
Fax: +45 (0) 43 / 95 95 91 e mail: [email protected]
UTU POWEL OY
COMPONENTS
Palopellonkatu 7
FI-04251 Kerava
Phone: +358 09 / 274 641 1
Fax: +358 09 / 274 641 41
FINLAND
e mail: —
ELECTRAPOTHIKI ATHENS S.A. GREECE
Acharnon Av. 426
GR-11143 Athens
Phone: +30 210 2014454
Fax: +30 210 2022420 e mail: [email protected]
Meltrade Automatika Kft. HUNGARY
55, Harmat St.
HU-1105 Budapest
Phone: +36 (0)1 / 2605 602
Fax: +36 (0)1 / 2605 602 e mail: [email protected]
RIFAS UAB
Tinklu 29A
LT-5300 Panevezys
Phone: +370 (45) 582-728
Fax: +370 (45) 582-729 e mail: [email protected]
LITHUANIA
EUROPEAN REPRESENTATIVES
INTEHSIS SRL
Cuza-Voda 36/1-81
MD-2061 Chisinau
Phone: +373 (0) 2 / 562 263
MOLDOVA
Fax: +373 (0) 2 / 562 263 e mail: [email protected]
NETHERLANDS
Imtech
Marine & Industry
Sluisjesdijk 155
NL-3008 AB-Rotterdam
Phone: +31 (0) 10 / 487 19 11
Fax: +31 (0) 10 / 487 17 02 e mail: [email protected]
SCANELEC AS
NORWAY
Leirvikasen 43B
N-5020 Bergen
Phone: +47 55 50 60 00
Fax: +47 55 50 60 01 e mail: [email protected]
MPL Technology SP. z.o.o
POLAND
ul. Sliczna 36
PL-31-444 Kraków
Phone: +48 (0) 12 / 632 28 85
Fax: +48 (0) 12 / 632 47 82 e mail: [email protected]
Sirius Trading & Services srl ROMANIA
Str. Biharia Nr. 67-77
RO-013981 Bucuresti 1
Phone: +40 (0) 21 / 201 1146
Fax: +40 (0) 21 / 201 1148 e mail: [email protected]
INEA d.o.o.
Stegne 11
SI-1000 Ljubljana
Phone: +386 (0) 1- 513 8100
Fax: +386 (0) 1- 513 8170 e mail: [email protected]
Euro Energy
SLOVENIA
Components AB
Järnvägsgatan 36
S-434 24 Kungsbacka
Phone: +46 (0) 300 / 69 00 40
Fax: +46 (0) 300 / 1 64 75 e mail: [email protected]
SWEDEN
TRIELEC AG
Mühlentalstr. 136
SWITZERLAND
Phone: +41 (0) 52 / 625 84 25
Fax: +41 (0) 52 / 625 88 25 e mail: [email protected]
GTS
Darülaceze Cad. No. 43 KAT. 2
TURKEY
TR-80270 Okmeydani-Istanbul
Phone: +90 (0) 212 / 320 1640
Fax: +90 (0) 212 / 320 1649 e mail: [email protected]
MIDDLE EAST REPRESENTATIVE
GINO INDUSTRIES LTD
26, Ophir street
IL-32235 Haifa
Phone: +972 (0) 4 / 867 06 56
Fax: +972 (0) 4 / 867 42 27 e mail: [email protected]
ISRAEL
EURASIAN REPRESENTATIVE
Avtomatika Sever Ltd
Lva Tolstogo Str. 7, Off. 311
RU-197376 St Petersburg
Phone: +7 812 1183 238
Fax: +7 812 1183 239 e mail: [email protected]
Consys
Promyshlennaya St. 42
RU-198099 St Petersburg
Phone: +7 812 325 36 53
Fax: +7 812 325 36 53 e mail: [email protected]
RUSSIA
RUSSIA
Electrotechnical Systems
Siberia
RUSSIA
Partizanskaya St. 27, Office 306
RU-121355 Moscow
Phone: +7 095/ 416-4321
Fax: +7 095/ 416-4321 e mail: [email protected]
Electrotechnical Systems
Siberia
Shetinkina St. 33, Office 116
RU-630088 Novosibirsk
Phone: +7 3832 / 22-03-05
RUSSIA
Fax: +7 3832 / 22-03-05 e mail: [email protected]
Elektrostyle ul. Garschina 11
RUSSIA
RU-140070 Moscowskaja Oblast
Phone: +7 095/ 261 - 3808
Fax: +7 095/ 261 - 3808 e mail: [email protected]
ICOS
RUSSIA
Ryazanskij Prospekt, 8a, Office 100
RU-109428 Moscow
Phone: +7 095 / 232 - 0207
Fax: +7 095 / 232 - 0327 e mail: [email protected]
SSMP Rosgidromontazh Ltd. RUSSIA
23, Lesoparkovaya St.
RU-344041 Rostov On Don
Phone: +7 8632/ 36 00 22
Fax: +7 8632/ 36 00 26 e mail: —
AFRICAN REPRESENTATIVE
CBI Ltd
Private Bag 2016
SOUTH AFRICA
ZA-1600 Isando
Phone: +27 (0) 11 / 928 2000
Fax: +27 (0) 11 / 392 2354 e mail: [email protected]
Specificationssubjecttochangewithoutnotice.
Art.no.62093-D,Printed in Germany 01.04
MITSUBISHI ELECTRIC
INDUSTRIAL AUTOMATION
Gothaer Strasse 8 Phone: +49 2102 486-0 Fax: +49 2102 486-7170 www.mitsubishi-automation.de
D-40880 Ratingen Hotline: +49 1805 000-7650 [email protected] www.mitsubishi-automation.com
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 COVER
- 3 CONTENTS
- 4 BASE UNITS
- 4 Program Overview – Specifications
- 6 Program Overview – Order Information
- 6 Standard series AE-SS – Fixed type
- 6 Standard series AE-SS – Drawout type
- 7 Air circuit breaker series AE-SSA/SSC 4000 A
- 7 Air circuit breaker series AE-SS 4000–6300 A – Draw-out type
- 7 High performance series AE-SH – Fixed type
- 7 High performance series AE-SH – Draw-out type
- 7 Switch-disconnector* AE-SS – Fixed type
- 8 ACCESSORIES
- 8 Overview and mounting positions of the main accessories
- 9 Overview and description of the standard equipment
- 9 Manual charging
- 9 Drawout interlock
- 9 Position lock
- 9 Interphase barrier
- 10 Overview and description on the optional accessories
- 10 Motor charging device (MD)
- 10 Charging completion switch (TS)
- 11 Undervoltage trip device (UVT)
- 12 Closing coil (CC)
- 12 Shunt trip device (SHT)
- 12 Auxiliary switch (AX, HAX)
- 13 Condensor trip device (COT)
- 13 Counter (CNT)
- 13 Interlock device (CYL, CAL)
- 14 Cell switch (CL)
- 14 Safety shutters (SST)
- 15 Shorting b-contact (SBC)
- 15 Mis-insertion preventor (MIP)
- 15 Vertical terminal adapter (VTA)
- 15 Lifting hooks (HP)
- 16 Mechanical interlock (MI)
- 16 Door interlock (DI)
- 17 Push button cover (BC-L)
- 17 Dust cover (DUC)
- 17 Terminal cover (TTC)
- 17 Door frame (DF)
- 18 Current transformer (CT)
- 18 Neutral current transformer (NCT)
- 18 External current transformer (ZCT)
- 19 External power supply unit (PS)
- 19 Field test devices
- 19 Test jumper (TJ)
- 20 ELECTRONIC TRIP RELAY
- 20 Introduction and selection
- 21 Characteristics setting table
- 21 Overview of rated currents (In max) – CT ratings
- 22 S Types – General Protection
- 24 M Types – General Protection
- 26 How to Adjust the Electronic Trip Relay
- 28 Special Functions – Accessories
- 28 Earth leakage protection (ER)
- 28 Pre-alarm (PAL)
- 28 Ground fault protection (GFR)
- 29 Temperature alarm (TAL)
- 29 Load current measurement (LM)
- 29 Standard functions
- 29 OCR alarm (AL)
- 29 Neutral pole overcurrent protection (NP) in a 4-pole circuit
- 30 Special Functions – Accessories
- 32 Operating Characteristics Type S
- 33 Operating Characteristics Type M
- 34 SPECIFICATIONS
- 34 Super AE Leistungsschalter mit elektronischen Auslöserelais S oder M
- 36 Dimensions – Type Breaker
- 36 Breaker types AE1000 to AE3200-SS/SH with standard connection (horizontal terminals)
- 37 Breaker types AE1000 to AE3200-SS/SH with Vertical terminal adapter (VAT)
- 38 Breaker types AE1000 to AE3200-SS with standard connection (horizontal terminals)
- 39 Breaker types AE1000 to AE3200-SS with vertical terminal adapter
- 40 Breaker types AE1000 to AE3200-SH with standard connection (horizontal terminals)
- 41 Breaker types AE1000 to AE3200-SH with vertical terminal adapter
- 42 Breaker typ AE4000-SSA (Fixed with vertical terminal)
- 43 Breaker typ AE4000-SSA (Drawout with vertical terminal)
- 44 Breaker typ AE4000-SSC (Fixed with vertical terminal)
- 45 Breaker types AE4000 to AE6300-SS with standard connection (vertical)
- 46 Dimensions – Accessory
- 46 External ZCT for load circuits
- 46 External ZCT for transformer ground wire
- 46 Condenser trip device (COT)
- 47 Operating Conditions, Technical Information
- 48 Internal resistance, reactance and power consumption (per pole)
- 48 Deratings (A) by ambient temperature
- 48 Connection arrangements
- 49 Specifications for marinal standards
- 50 SOFTWARE
- 50 Calculation and Selection Software MELSHORT2
- 51 INDEX