SUPER-AE (PDF/4,04Mo) [EN] Catalogue 2004


Add to my manuals
52 Pages

advertisement

SUPER-AE (PDF/4,04Mo) [EN] Catalogue 2004 | Manualzz

MITSUBISHI ELECTRIC

Low Voltage

Switchgears

Air Circuit Breakers

Air Circuit

Disconnectors

SUPER AE

AE 1000 –

AE 6300

Technical Catalogue

2004

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

New Items in this Catalogue

01/2004

The air circuit breaker program from MITSUBISHI ELECTRIC:

Complete breaker program

Frame size from 1000 A to 6300 A

Wide performance range

Standard version "SS" from 65 to 130 kA

High performance version "SH" with 130 kA

High interrupting capacity

Growing power demands

Optimum overload tripping system

Safer and more selectivity

Further Publications within the LVS, PLC and inverter range

Technical

Catalogues

WSS, PSS & Super Series Technical Catalogue

Product catalogue for circuit breakers and disconnectors from 3 A to 1600 A rated current (art no. 133207)

MS-N Technical Catalogue

Product catalogue for low voltage contactors and relays from 20 A to 1000 A rated current (art no. 62306)

PLC and Inverter Technical Catalogues

Product catalogues for programmable logic controllers and frequency inverters (more details on request)

Current information on updates, alterations, new items, and technical support you will find on MITSUBISHI ELECTRIC's web pages

(www.mitsubishi-automation.com).

In the products section of the MITSUBISHI home site various documentations of the whole product range by MITSUBISHI ELECTRIC as well as the current version of this catalogue on hand are available as download. The content is updated daily and to date is provided in German and English.

Due to the constantly growing product range, technical alteration, and new or changed characteristical features, this catalogue is updated frequently.

Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering the electronic air circuit breakers of the SUPER AE series and the associated accessories. Only the manuals supplied with the breakers are relevant for installation, commissioning and handling of the air circuit breakers and the accessories. The information given in this documentation must be read before installation and commissioning of the modules.

Should questions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact the german branch of the MITSUBISHI ELECTRIC EUROPE B.V. in Ratingen or one of its distributors (see cover page).

© MITSUBISHI ELECTRIC EUROPE B.V. 01/2004 (4th edition)

2

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

S

UPER

AE S

ERIES

BASE UNITS

웇 Program overview – main unit features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

웇 Program overview – ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

ACCESSORIES

웇 Overview of the main accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

웇 Standard equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

웇 Internal optional accessories for all breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

웇 Optional accessories for drawout breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

웇 External optional accessories for all breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

ELECTRONIC TRIP RELAY

웇 Program overview – Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

웇 Trip relay adjusting notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

웇 Special functions – accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

웇 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

웇 Operating characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

SPECIFICATIONS

웇 Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

웇 Dimensions – breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

웇 Dimensions – accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

웇 Environmental conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

웇 Specifications for marinal approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

웇 Calculation software MELSHORT2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

A

PPENDIX

웇 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

CONTENTS

MITSUBISHI ELECTRIC

SUPER AE

3

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

BASE UNITS

Program Overview – Specifications

SUPER AE

Rated current (A) at 40 °C

Rated insulation voltage (V) 50/60 Hz

Rated operating voltage (V) 50/60 Hz

Number of poles

Series

Breaker type AE 1000 - SS

I

N max

Ui

Ue

1000

1000

690

3 4

AE 1250 - SS

1250

1000

690

3 4

Standard series "SS"

AE 1600 - SS AE 2000 - SS

1600

1000

690

2000

1000

690

3 4 3 4

AE 2500 - SS

2500

1000

690

3 4

AE 3200 - SS

3200

1000

690

3 4

Ir

I

I

I

Rated current for neutral pole N breaking capacity

O-t-CO-t-CO

CS CU making capacity

Rated short time current (kA eff.) I

Maximum total breaking time

Closing time

Without inst. trip

With trip instantaneous trip

(with MCR)

Without inst. trip

CW

With rated current

Without rated current

AC690V

AC600V

AC500V

AC690V

1s

2s

3s

(sec)

(sec)

(A)

AC690V

AC600V

AC500V

AC690V

AC600V

AC500V

AC690V

AC690V

AC600V

AC500V a a

Fixed type

Drawout type

(with cradle)

Cradle only c c d d

Manual charging

Motor charging

Manual charging

Motor charging c a b a d b c d

40

30

0.04

0.08

5000

10000

88.2

105

143

52.5

65

500

In

In

1000

1000

50

50

65

42

50

65

25

105

105

143

44

64

67

26

430

368

61

41

340

410

290

40

298

54

78

81

30

430

368

61

51

425

410

290

40

385

625

In

40

30

0.04

0.08

5000

10000

88.2

105

143

52.5

65

50

65

25

105

105

143

1250

50

50

65

42

44

64

67

26

430

368

61

41

340

410

290

40

298

1250

54

78

81

30

430

368

61

51

425

410

290

40

385

1000

In

2000

65

65

0.04

0.08

1500

10000

105

143

143

94.5

65

65

65

45

105

143

187

2000

50

65

85

50

63

92

95

35

430

368

61

60

475

410

290

40

433

75

113

116

43

430

368

61

72

605

410

290

40

565

For further temperatures refer to technical information on page 48.

The figures for "without instantaneous tripping" are the values when the bare main body and the external relay are combined.

The number of operating cycles with rated current also include the number of operating cycles without rated current.

All specifications without peripheral accessories (e.g. UVT control unit).

Further current ratings on request.

More details on request.

800

In

1600

60

50

0.04

0.08

5000

10000

88.2

105

143

52.5

65

50

65

25

105

105

143

1600

50

50

65

42

55

79

82

30

430

368

61

52

425

410

290

40

385

45

65

68

26

430

368

61

42

340

410

290

40

298

1600

In

3200

65

65

0.04

0.08

1000

10000

105

143

143

94.5

65

65

65

45

105

143

187

3200

50

65

85

50

66

95

98

36

430

368

61

63

475

410

290

40

433

78

116

119

44

430

368

61

75

605

410

290

40

565

1250

In

2500

65

65

0.04

0.08

1500

10000

105

143

143

94.5

65

65

65

45

105

143

187

2500

50

65

85

50

76

114

117

43

430

368

61

73

605

410

290

40

565

64

93

96

35

430

368

61

61

475

410

290

40

433

4

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

BASE UNITS

Standard series "SS"

AE 4000 - SSA AE 4000 - SSC AE 4000 - SS

High performance series "SH"

AE 5000 - SS AE 6300 - SS AE 1000 - SH AE 1250 - SH AE 1600 - SH AE 2000 - SH

3

4000

1000

690

4

4000

1000

690

3 3

4000

1000

690

4 3

5000

1000

690

4 3

6300

1000

690

4 3

1000

1000

690

4 3

1250

1000

690

4 3

1600

1000

690

4 3

2000

1000

690

4

AE 2500 - SH AE 3200 - SH

3

2500

1000

690

4 3

3200

1000

690

4

3200

In

4000 3200

In

4000 2000

In

4000 2500

In

5000 3150

In

6300 500

In

1000 625

In

1250 800

In

1600 1000

In

2000 1250

In

2500 1600

In

3200

65

65

0.04

0.08

500

5000

105

143

165

94.5

75

65

75

45

105

143

187

50

65

85

50

605

414

290

136

565

430

368

151

109

112

145

148

75

81

85

107

111

49

475

410

290

117

439

430

368

109

105

143

165

94.5

75

65

65

0.04

0.08

500

5000 4000

65

75

45

105

143

187

4000

50

65

85

50

605

410

290

117

569

430

368

109

99

103

136

140

61

70

70

0.05

0.08

500

2000

105

187

187

105

85

85

85

50

105

187

286

3200

50

85

130

50

70

70

0.05

0.08

500

2000

105

187

187

105

85

85

85

50

105

187

286

3200

50

85

130

50

480

368

123

— — — — — — 70

875 1005 875 1005 875 1005 485

475

410

290

480

368

123

480 480

368 368

123 123

480 480

368 368

123 123

430

398

61

70

70

0.05

0.08

500

2000

105

187

187

105

85

85

85

50

105

187

286

3200

50

85

130

50

0.04

0.08

3000

10000

65

85

130

1000

65

85

130

605 475

410 410

290 290

70 70

615 485

430 430

398 398

61 61

0.04

0.08

3000

10000

65

85

130

1250

65

85

130

605 475

410 410

290 290

70 70

615 485

430 430

398 398

61 61

240

244

125

263

267

140

240 263

244 267

125 140

240 263

244 267

125 140

66

69

105

108

42

79

82

127 105

130 108

50

66

69

42

79

82

127 105

130 108

50

66

69

42

0.04

0.08

2000

10000

65

85

130

1600

65

85

130

605

410

290

70

615

430

398

61

79

82

127

130

50

475 605

410 410

290 290

70 70

485 615

430 430

398 398

61 61

66

69

0.04

0.08

1500

10000

65

85

130

2000

65

85

130

79

82

105 127

108 130

42 50

66

69

105

108

42

0.04

0.08

1500

10000

65

85

130

2500

65

85

130

475

410

290

70

485

430

398

61

605 475

410 410

290 290

70 70

615 485

430 430

398 398

61 61

0.04

0.08

1000

10000

65

85

130

3200

65

85

130

605

410

290

70

615

430

398

61

79 68

82 71

127 107

130 110

50 43

81

84

129

132

51

Declaration of conformity:

Standards

Certificates

Marine approvals

IEC947-2, EN60947-2, VDE0660

ASTA, SEV (types on request)

LRS, GL, BV, ABS, DNK, NK

(other approvals on request)

MITSUBISHI ELECTRIC

SUPER AE

5

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

BASE UNITS

Program Overview – Order Information

ELECTR

ONI

C TRIP

RELA

Y

MOD

EL

- CIA

MITSUBISHI

SPGT

INDICA

R

TO

TRIP

CT

T

LO

AD lu

C URREN

%

GEST

LA

R

PHASE

URRENT

C

RA

TED

MAX

TED

RA

C

URRENT separate to order: trip relay, e.g. ST1A-SAE

SUPER AE Air Circuit Breaker – Order Information

The circuit breakers of the frame sizes AE1000-SS to AE3200-SS are offered without trip relay and auxiliary switch included as standard equipment.The circuit breakers of the frame sizes

AE4000-SSA/SSC/SS to AE6300-SS are available including the trip relay ST1A and auxiliary relay.The circuit breakers of the frame sizes AE4000-SS,AE5000-SS,and AE6300-SS for handling and weight reasons are available as drawout types.The circuit breakers of the high-performance series AE-SH as well are available including the trip relay ST1A and auxiliary relay.They are available as fixed and drawout types.

To purchase a fully functional 3-pole or 4-pole fixed type circuit breaker please select the following:

앬 base unit: fixed type, 3 or 4 pole with 3 current sensors (CT), electronic trip relay,

앬 auxiliary switches, and the required accessory.

Please refer to order example 1.

To purchase a fully functional 3-pole or 4-pole drawout type circuit breaker please select the following:

앬 the corresponding circuit breaker – fixed type, the corresponding cradle

앬 and the drawout mechanism.

Please refer to order example 2.

To purchase a fully functional 3-pole or 4-pole drawout type disconnector please select the following:

앬 the corresponding disconnector – fixed type, the corresponding cradle and the drawout mechanism.

Please refer to order example 3.

Order example 1:

Base unit – fixed type, 3 pole with 3 current sensors:

AE1000-SS 3P Fix, Bare, CT, TC (art. no. 129215)

Electronic trip relay (for general use - S type): ST1A-SAE

(art. no. 135976)

Auxiliary switches: AX-SAE2A2BA (art. no. 28786)

Order example 2:

Base unit – fixed type, 3 pole with 3 current sensors:

AE1000-SS 3P Fix, Bare, CT, TC (art. no. 129215)

Electronic trip relay (for general use - S type): ST1A-SAE

(art. no. 135976)

Auxiliary switches: AX-SAE2A2BA (art. no. 28786)

Cradle with horizontal terminals:

CRADLE-02SEA3 (art. no. 25897)

Drawout mechanism: REC-SAEFD (art. no. 34666)

Standard series AE-SS – Fixed type

Base unit equipment

Shipping contents:

Base unit

Further elements that must be ordered:

Accessories as required 햳

Breaker

AE 1000 - SS

AE 1250 - SS

AE 1600 - SS

AE 2000 - SS

AE 2500 - SS

AE 3200 - SS

3-pole type

AE1000-SS 3P Fix, Bare, CT, TC

AE1250-SS 3P Fix, Bare, CT, TC

AE1600-SS 3P Fix, Bare, CT, TC

AE2000-SS 3P Fix, Bare, CT, TC

AE2500-SS 3P Fix, Bare, CT, TC

AE3200-SS 3P Fix, Bare, CT, TC

Order example 3:

Base unit (Disconnector *) – fixed type, 3 pole: AE1000-SS 3P

Fix, Bare (art. no. 129228)

Cradle with horizontal terminals:

CRADLE-02SEA3 (art. no. 25897)

Drawout mechanism: REC-SAEFD (art. no. 34666)

* Air circuit breaker without overcurrent short-circuit release and without current transformer

Art. no.

129215

129217

129220

129224

129226

129246

4-pole type

AE1000-SS 4P Fix, Bare, CT, TC

AE1250-SS 4P Fix, Bare, CT, TC

AE1600-SS 4P Fix, Bare, CT, TC

AE2000-SS 4P Fix, Bare, CT, TC

AE2500-SS 4P Fix, Bare, CT, TC

AE3200-SS 4P Fix, Bare, CT, TC

Art. no.

129216

129218

129222

129225

129227

129247

Standard series AE-SS – Drawout type

Please refer to order information above.

For specification and order information about electronic trip relays refer to page 20 ff.

Further breaker types with other rated current on request.

For breaker accessories refer to page 8 ff.

6

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

BASE UNITS

Air circuit breaker series AE-SSA/SSC 4000 A

Base unit equipment Breaker

Shipping contents:

Base unit

Further elements that must be ordered:

Accessories as required

AE 4000 - SSA

AE 4000 - SSA

AE 4000 - SSC

Fixed type

AE4000-SSA 3P Fix, ST1A, AX2A2B

AE4000-SSA 4P Fix, ST1A, AX2A2B

AE4000-SSC 3P Fix, ST1A, AX2A2B

Air circuit breaker series AE-SS 4000–6300 A – Draw-out type

Base unit equipment

Shipping contents:

Base unit

Breaker

AE 4000 - SS

AE 5000 - SS

AE 6300 - SS

3-pole type

AE4000-SS 3P D/O, ST1A, AX2A2B, SST

AE5000-SS 3P D/O, ST1A, AX2A2B, SST

AE6300-SS 3P D/O, ST1A, AX2A2B, SST

Further elements that must be ordered:

Accessories as required 햳

High performance series AE-SH – Fixed type

Base unit equipment Breaker

Shipping contents:

Base unit

Further elements that must be ordered:

Accessories as required

AE 1000 - SH

AE 1250 - SH

AE 1600 - SH

AE 2000 - SH

AE 2500 - SH

AE 3200 - SH

3-pole type

AE1000-SH 3P FIX, ST1A, AX2A2B

AE1250-SH 3P FIX, ST1A, AX2A2B

AE1600-SH 3P FIX, ST1A, AX2A2B

AE2000-SH 3P FIX, ST1A, AX2A2B

AE2500-SH 3P FIX, ST1A, AX2A2B

AE3200-SH 3P FIX, ST1A, AX2A2B

Art. no.

142593

142594

69984

Art. no.

56977

56976

56974

Art. no.

43713

139887

43711

139888

139889

139890

High performance series AE-SH – Draw-out type

Base unit equipment

Shipping contents:

Base unit

Charging handle (for manual operation)

4 auxiliary contacts (2 NO, 2 NC contactsr)

Further elements that must be ordered:

Accessories as required 햳

Breaker

AE 1000 - SH

AE 1250 - SH

AE 1600 - SH

AE 2000 - SH

AE 2500 - SH

AE 3200 - SH

3-pole type

AE1000-SH 3P D/O, ST1A, AX2A2B

AE1250-SH 3P D/O, ST1A, AX2A2B

AE1600-SH 3P D/O, ST1A, AX2A2B

AE2000-SH 3P D/O, ST1A, AX2A2B

AE2500-SH 3P D/O, ST1A, AX2A2B

AE3200-SH 3P D/O, ST1A, AX2A2B

Switch-disconnector* AE-SS – Fixed type

Base unit equipment

Shipping contents:

Base unit

Further elements that must be ordered:

Breaker

AE 1000 - SS

AE 1250 - SS

AE 1600 - SS

AE 2000 - SS

AE 2500 - SS

AE 3200 - SS

3-pole type

AE1000-SS 3P SS Fix, Bare

AE1250-SS 3P SS Fix, Bare

AE1600-SS 3P SS Fix, Bare

AE2000-SS 3P SS Fix, Bare

AE2500-SS 3P SS Fix, Bare

AE3200-SS 3P SS Fix, Bare

Art. no.

129228

129232

129236

129240

129242

129248

Art. no.

43701

139905

139906

43698

139907

43696

Draw-out type

AE4000-SSA 3P D/O, ST1A, AX2A2B, SST

AE4000-SSA 4P D/O, ST1A, AX2A2B, SST

AE4000-SSC 3P D/O, ST1A, AX2A2B, SST

Art. no.

142596

142599

69985

4-pole type

AE4000-SS 4P D/O, ST1A, AX2A2B, SST

AE5000-SS 4P D/O, ST1A, AX2A2B, SST

AE6300-SS 4P D/O, ST1A, AX2A2B, SST

Art. no.

56978

56975

56973

4-pole type

AE1000-SH 4P FIX, ST1A, AX2A2B

AE1250-SH 4P FIX, ST1A, AX2A2B

AE1600-SH 4P FIX, ST1A, AX2A2B

AE2000-SH 4P FIX, ST1A, AX2A2B

AE2500-SH 4P FIX, ST1A, AX2A2B

AE3200-SH 4P FIX, ST1A, AX2A2B

Art. no.

139891

139902

139903

139904

43703

43702

4-pole type

AE1000-SH 4P D/O, ST1A, AX2A2B

AE1250-SH 4P D/O, ST1A, AX2A2B

AE1600-SH 4P D/O, ST1A, AX2A2B

AE2000-SH 4P D/O, ST1A, AX2A2B

AE2500-SH 4P D/O, ST1A, AX2A2B

AE3200-SH 4P D/O, ST1A, AX2A2B

Art. no.

43695

139908

139909

139910

139911

43690

4-pole type

AE1000-SS 4P SS Fix, Bare

AE1250-SS 4P SS Fix, Bare

AE1600-SS 4P SS Fix, Bare

AE2000-SS 4P SS Fix, Bare

AE2500-SS 4P SS Fix, Bare

AE3200-SS 4P SS Fix, Bare

Art. no.

129229

129234

129238

129241

129244

129249

Switch-disconnector* AE-SS – Draw-out type

Please refer to order information on the top left side.

For specification and order information about electronic trip relays refer to page 20 ff.

For breaker accessories refer to page 8 ff.

Further breaker types with other rated current on request. * Air circuit breaker without overcurrent short-circuit release and without current transformer

MITSUBISHI ELECTRIC

SUPER AE

7

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Overview and mounting positions of the main accessories

Counter

Auxiliary switch

Under voltage trip device

Closing coil

Shunt trip device

Mis insertion preventer

Safety shutters

Cell switch

Page 13

Page 12

Page 11

Page 12

Page 12

Page 15

Page 14

Page 14

CNT

AX

UVT

CC

SHT

MIP

SST

CL

ONI

ELECTR

TR

IP

AY

EL

MITSUBISHI

MODEL

- C IA

CT

TOR

SPGT

TRIP

INDICA

LO %

C URRENT lu PHASE

LARGEST

MAX

RA

TED

C URRENT

RA TED

External power supply unit

Lifting hooks

Motor charging device

Cylinder lock

Castell lock

Electronic trip relay

CYL

CAL

PS

HP

MD

Page 19

Page 15

Page 10

Page 13

Page 13

Page 20

Page 6

8

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Overview and description of the standard equipment

Manual charging

OFF

ON

OFF

GESP

ANNT

The spring is charged by the manual charging handle.The breaker is closed when the ON button is pressed,and opened when the OFF button is pressed.

When the closing spring charging is completed,the charging indicator displays

CHARGED.

The indicator displays ON or OFF state of the main contacts.

The breaker cannot be closed while the

OFF button is being pressed (safety feature).

The manual charging process is one of the standard features of the breaker and part of the standard equipment.

Drawout interlock

A safety device prevents the circuit breaker from being pushed in or drawn out while the breaker is on.

The drawout handle cannot be inserted unless the OFF button is pressed.

Position lock

16

5

The device is for locking the drawout mechanism at the TEST position.This then indicates the TEST position.

The lock can be used during either the drawing out or pushing-in operation.

The lock is released when the lock plate is pushed in,and the next operation becomes possible.

Padlocking is possible at the CONNECTED,

TEST,and DISCONNECTED positions.Use

this lock to prevent unauthorised changing of positions.

(The padlock should be supplied by the customer)

35

Interphase barrier

The interphase barrier of the circuit breaker prevent the short-circuit due to conductive matters or dust.

The interphase barrier are simple to add and have been designed as fixed types and drawout types,to suit your requirements.The table on the right shows you which circuit breakers are supplied with pre-mounted barriers.

Breaker Fixed type

Drawout type

— —

=Standard equipment by horizontal connection

MITSUBISHI ELECTRIC

SUPER AE

9

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Overview and description on the optional accessories

Motor charging device (MD)

In addition to manual operation,the closing spring can be charged automatically by an electric motor every time the breaker is closed (ON charging method).

If the closing spring is to be charged automatically whenever the breaker is opened, then this can be done through an additional auxiliary contact (AXb) (OFF charging method).As soon as charging is completed,a visual display on the front says

"CHARGED".

The "CHARGED" signal is also available via the 413 (TS+) and 414 (TS-) terminals

(included in the standard MD configuration).

There is always the option of manual operation in an emergency.A closing coil

(CC) is required for closing the breaker by remote control,and a shunt trip device

(SHT) is required for opening it in this way.

This warrants the prevention of pumping, both electronically and mechanically.The

circuit of the motor is separate from the

ON/OFF circuit (CC,SHT).

ON charging method

(M+)

U1

(M-)

U2

OFF charging method

AXb

(M+)

U1

(M-)

U2

Specifications

Application

Rated voltage *

Applicable voltage range

Applied voltage

Inrush current (peak value)

Steady current

Charging time

Order information

Art. no. 29453

* Rated frequency at AC = 50/60 Hz

Not available for AE4000-SS – AE6300-SS.

for 3-pole type

햴 for 4-pole type

MD-SAED24

AE3200-SS/-SH,

AE4000-SSC

(V) 24 (DC)

(V) 20.4–26.4

(V) 24

(A) 22

(A) 6

(sec)

5

MD-SAED48

48

14

AE3200-SS/-SH,

AE4000-SSC

48 (DC)

40.8–52.8

3

5

34352

MD-SAED60

60

9

AE3200-SS/-SH,

AE4000-SSC

60 (DC)

51–60

3

5

34368

MD-SAEAD013

AE3200-SS/-SH,

AE4000-SSC

100–125(AC/DC)

85–137.5

100 / 125

10 / 12

3

5

32843

MD-SAWAD013

AE4000-SS–

AE6300-SS

햴 ,

100–125(AC/DC)

85–137.5

100 / 125

10 / 12

4

5

58320

MD-SAEAD025C

AE3200-SS/-SH,

AE4000-SSC

200–250 (AC/DC)

170–275

200 / 250

5 / 6

1

5

25830

MD-SAWAD025C

AE4000-SS–

AE6300-SS

햴 ,

200–250 (AC/DC)

170–275

200 / 250

7 / 8

2

5

58321

Charging completion switch (TS)

(TS+)

413

(TS-)

414

As soon as charging has been completed, this status is reported by the 413 (TS+) and

414 (TS-) terminals (signal display of charged status).This function is available during the charging process both manually and automatically.

Specifications

Contact capacity

Order information

TS-SAE1A

refer to auxiliary switch

Art. no. 30439

10

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Undervoltage trip device (UVT)

Two trip types are available:

앬 instantaneous (for immediate tripping)

앬 with a time delay of 0.5 or 3 seconds

All UVT controllers are fitted with additional terminals for the connection of an emergency OFF switch.The UVT controller can be mounted to the left of the the unit.

If two rated voltages are used,the lowest value is applied.

If an emergency OFF trip function is required,remove the shorting wire across terminals DT1 (UO+) and DT2 (UO-) and replace with an emergency OFF switch.

Coil

Controller

This device is used for tripping the breaker when the supply voltage drops below the rated value.

The undervoltage trip device consists of a

UVT coil and a UVT controller. Both parts

must be ordered separately.

UVT circuit diagram

(UL3)

(UL2)

(UL1)

(UL0)

D4

D3

D2

D1

UVT controller

Control circuit

(U

+)

J1

J2

(U–)

J1

J2

Air circuit breaker

UVT coil see note below

Trip button

Notes on the circuit diagram:

The UVT,as delivered,has a shorting wire between the DT1 (U0+) and DT2 (U0-) terminals.

If an emergency OFF switch is used,this contact bridge must be removed.The emergency

OFF switch is not included in the package.The maximum length of the wire between DT1

(U0+) and DT2 (U0-) and the trip button should be 5 m.If longer distances are required please contact your nearest Mitsubishi distributor.

Specifications

Rated voltage (+10%/-15%) *

Operation

Operating time

Closing delay**

Pick-up/drop-out voltage

Trip function

Power consumption

Order information

(V) 24 (DC)

Instantaneous

100–125 (DC) 100–460 (AC) 24 (DC)

With time delay

100–110 (DC) 100–460 (AC) 24 (DC)

(sec) 0.1 or less 0.1 or less 0.1 or less 0.5 or more 0.5 or more 0.5 or more 3 or more

(sec) Approx. 1.5

Approx. 1.5

Approx. 1.5

Approx. 1.5

Approx. 1.5

Approx. 1.5

Approx. 3

(V) Pick-up voltage 65–85 %, drop-out voltage 45–70 %

With open circuit (terminals DT1 (UO+), DT2 (UO–); rated 0.5 A at DC 250 V)

(VA) 20

Art. no. 30440 30441 30209 30442 30443 30206

* Rated frequency at AC= 50/60 Hz

** Delay which must be taken into account between the charging of the UVT controller and the closing of the breaker.

30444

100–110 (DC) 100–460 (AC) UVT coil

3 or more

Approx. 3

30445

3 or more

Approx. 3

30208 25912

MITSUBISHI ELECTRIC

SUPER AE

11

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Closing coil (CC)

The closing coil is seperate from the motor charging power supply.

Steady current is the value at maximum rated voltage.

An interlock to prevent pumping is provided electrically.The pumping prevention is not performed,when the supply voltage is 50 % or less the minimum rated voltage.

(CC+)

A1

(CC-)

A2

The closing coil is a device to close the breaker by remote control.Only one closing signal (about 100 msec.) is sent even when the closing coil supply is maintained ON.

Specifications

Rated voltage *

Applicable voltage range

Operating voltage

CC-SAED004A

(V) 24–48 (DC)

(V) 18–52,8

(V) 24 / 48

Inrush current

Closing time

AC (A) —

(sec) max. 0.08

Order information

Art. no. 30399

* Rated frequency at AC = 50/60 Hz

Closing time is from the initial energization of the closing coil to the completion of the closing of the main contacts.

No pumping prevention takes place if an integrated auxiliary switch (AXb) is used as a cut-off switch.

An auxiliary contact with high switching capacity should be used with DC supply voltage (HAX).

CC-SAED60

60 (DC)

45–60

60

1.1

— max. 0.08

40310

CC-SAEAD025A

100–250 (AC/DC)

75–275

100 / 250

DC250 V 200 W)

0.5 / 1.0 (AC 100 V 100 VA,

AC 250 V 200 VA) max. 0.08

25909

Shunt trip device (SHT)

(S+)

C1

(S-)

C2

The shunt trip device is used to open the breaker by remote control.

A cut-off switch is included.

Specifications

Rated voltage *

Applicable voltage range

Operating voltage

SHT-SAED004A

(V) 24–48 (DC)

(V) 16.8–52.8

(V) 24 / 48

SHT-SAED60

60 (DC)

42–66

60

SHT-SAED025A SHT-SAEA046A

100–250 (AC/DC) 380–500 (AC)

70–275

100 / 250

266–550

460

— DC (A)

(

(DC24 V 100 W, 1

(

(DC100 V 100 W,

AC (A) — —

(

(AC 100 V 100 VA,

(sec) max. 0.04 (AE 4000-SS – AE 6300-SS = max. 0.05) Closing time

Order information

Art. no. 27215

* Rated frequency at AC = 50/60 Hz

40309 25831 27614

Auxiliary switch (AX, HAX)

(AX+)

13

(AX-)

14

(BX+)

11

(BX-)

12

These auxiliary contacts are used to remotely indicate the ON or OFF status of the breaker.

Specifications

Type

Contact capacity

(A)

Maximum number of contacts

460 V 5

AC 250 V 10

125 V 10

250 V 0.3

DC 125 V 0.6

AX-SAE2A2BA

Standard capacity (AX)

Resistance load

Inductive load

2

10

10

0.3

0.6

30 V 10

2 NO, 2 NC

6

AX-SAE5A5BA

10

0.3

0.6

Resistance load

5

10

10

5 NO, 5 NC

Order information

Art. no. 28786 25835

Note: The chattering time at the time of contact ON - OFF is below 0.025 sec.

10

0.3

0.6

Inductive load

2

10

6

10

3

5

10

10

AX-SAE5A5BAD

High capacity (HAX)

Resistance load

Inductive load

2.5

10

10

1.5

6

10

5 NO, 5 NC

10

38468

12

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Condensor trip device (COT)

Circuit diagram

AC1

AC2

S1

R1

C

N6

DC+

SHT

C1

(S+)

DC–

C2

(S–)

This device allows the electrically actuated opening of the breaker by remote control within a given period of time,despite a power cut.The COT is used in conjunction with the shunt trip device (SHT).

For dimensions refer to page 41.

Further details on request.

Specifications

Rated input voltage *

Rated charging voltage

Power supply capacity

Capacitor capacity

Voltage range

Charging time (capacitor)

Trip limit time

KF-100 KF-200

V AC 100/110 200/220

V 140/155 280/310

VA 1

µF 660

1

150

% 60–125 60–125 s max. 0.5 max. 0.5

s min. 900 min. 300

Order information

Art. no. On request On request

* Rated frequency at AC = 50/60 Hz

Counter (CNT)

This is a mechanical counter which registers the total number of operating cycles

(with 1 ON/OFF switching operation =

1 operating cycle).

The number of operating cycles is displayed on the front of the unit.

Specifications

Counter type

Display

Order information

CNT-SAE

Mechanical

5 digits

Art. no. 25914

00000258

Interlock device (CYL, CAL)

CYL

CAL

The interlock device locks the circuit breaker into the OFF position.

The relevant key can only be taken out in the OFF position of the circuit breaker, so that it can also be used for unlocking other breakers.

There are two locking options available:

Cylinder lock (CYL)

Castell lock (CAL) *

Specifications

Interlock

Closing

Cylinder

Basic

Cylinder

1

Cylinder

2

Cylinder

3

Cylinder

4

Order information

Art. no. 25838 39485 39486 39488 39489

* The closing basis for the Castell lock can be designed individually. Further details on request.

Castell

Basic

On request

MITSUBISHI ELECTRIC

SUPER AE

13

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Cell switch (CL)

The cell switches can be set for all the relevant positions,i.e.connected,test and disconnected.

Each cell switch consists of 4 individual switches.

Switch function

CL–C

CL-T

Specifications

Load

In addition to the mechanical position indicator on the front panel,it is also possible to mount these cell switches onto the cradle.

Contact capacity (A)

CL-SAE211

Resistive

Number and type of switches

Application (breaker)

Order information

4 interchange switches

AE1000-SS – AE6300-SS

Art. no. 25840

Inductive

CL-SAH211

Resistive Inductive

4 interchange switches

AE1000-SH – AE3200-SH

45578

Safety shutters (SST)

The safety shutters cover the main conductors of the cradle side (supply and load side) automatically when the circuit breaker is drawn out.

When checking the main circuit,the safety shutters on the supply and load sides can be opened independently of one another.

The safety shutters can also be locked with a mechanical locking device (SST LOCK).

The padlocks have to be supplied by customer.

Specifications

Application(breaker)*

Breaker type

Number of poles

SST-

02SAE3

AE1000–1600-SS

SST-

02SAE4

Drawout

3 4

SST-

05SAE3

SST-

05SAE4

SST-

SAELOCK

shutter lock

3 4

Order information

Art. no. 25836 25837 25907 25908

* On breaker types AE 4000-SSA/SSC–SS to AE 6300-SS the safety shutters are already part of the standard version.

30458

14

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Shorting b-contact (SBC)

When moving the breaker from the connected to the test positions,this contact is used to short circuit auxiliary switch (Axb) thus maintaining the correct sequence of operation of the external control circuit.

When ordering,the same number of shorting b-contacts as auxiliary switches

(AXb) will be provided.

Specifications

Application (breaker)

Order information

SBC-SAE

All breaker

Art. no. 30456

Mis-insertion preventor (MIP)

To obtain the right drawout configuration, it is extremely important that the breaker unit specifications (type,current rating, optional accessories,etc.) should match the cradle.

Mis-insertion is prevented by a combination of matching components (on the breaker and the cradle).

Specifications

Application (breaker)

Material

Order information

MIP-SAE

AE1000–AE3200-SS/SH

AE4000-SSA/SSC

Metal

Art. no. 30455

Vertical terminal adapter (VTA)

Vertical terminal adapters allow you to turn power connection by 90°.

Other forms of terminal adapters on request.Dimensions see page 37 ff.

Specifications

Application (breaker)

Shipping contents

Order information

VTA-02SAE

AE1000–AE1600-SS pieces 1

Art. no. 34193

VTA-03SAE

1

34192

VTA-32SAE

AE3200-SS/SH

1

34191

Lifting hooks (HP)

These hooks are used to remove the drawout breaker from the cradle.

The option is not necessary,when a special lifter (bucket type) for AE-SS is used.

The fixed type breaker is equipped with the lifting hooks as standard.

The lifting hooks can not be used for

AE4000-SS to AE6300-SS.

Specifications

Material

Order information

HP-SAE

Metal

Art. no. 30485

MITSUBISHI ELECTRIC

SUPER AE

15

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Mechanical interlock (MI)

Horizotal mounting

1000 (Max.)

Vertical mounting

47

134

The mechanical interlock is a secure interlock prohibiting the parallel closing of two or three breakers.

Any combination between AE1000-SS/SH up to AE3200-SS/SH and AE4000-SSA/SSC is possible.

The interlock can be simply installed on either fixed or drawout type breakers.

With the drawout type,the interlock operates at the connecting point and can be released at other positions,providing secure maintenance and inspection of the breaker.

For AE4000-SS up to AE6300-SS a combination is possible only between two breakers.

Note:

When using the mechanical interlock,the application of the door interlock (DI) is not possible.

ON

G

OFF ON

ON

OFF

[mm]

Specifications

Application(breaker)

Breaker type

Number of poles

AE1000–1600SS

Fixed

3 4

AE1000–1600SS

Drawout

3 4 3 4 3 4

Order information

Art. no. 30450 30451 30452 30453 30446 30447 30448 30449

Interlocking requires a separate unit for each breaker. If you have 3 breakers, you need a separate set of bowden cables MI-SAEIW.

MI-SAEIW

AE4000–6300SS

3

62327

4

62326 30454

Door interlock (DI)

The device has been designed for panel doors with the groove on the left (standard).Locks for grooves on the right are available on request.

A wire-type mechanical interlock is used to allow flexibility in positioning breakers in the panel.

Note:

When using the door interlock (DI) the application of the mechanical interlock

(MI) is not possible.

This mechanical interlock device makes it impossible to open the panel door unless the circuit breaker is not switched off.

Specifications

Application (breaker)

Breaker type

Order information

DI-SAEF

For all breakers

Fixed

Art. no. 31538

DI-SAED

For all breakers

Drawout

31537

16

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Push button cover (BC-L)

This mechanical device can be locked with a padlock or a seal (not included in the package) to protect the push buttons of the breaker unit against inadvertent

ON/OFF operation.

The padlock has to be supplied by the customer.

Specifications

Material

Order information

BCL-SAE

Acrylic plate

Art. no. 27727

Dust cover (DUC)

The transparent dust cover is hinged onto the panel door.It has a screw lock and prevents dust and water entering into the circuit breaker.

Specifications

Protection

Order information

DUC-SAE

IP 54

Art. no. 42618

Terminal cover (TTC)

The terminal cover is a transparent cover for safety finger protection of control terminals.

The terminal cover prevents from careless touching to the live control terminals.

Specifications

Application (breaker)

Protection

Order information

TTC-SAEF TTC-SAED

Fixed type Draw-out

IP 20 IP 20

Art. no. 62482 62481

Door frame (DF)

The door frame improves the appearance, after cutting out the panel door to install the breaker.

Refer to the overall dimension drawings on page 36 ff for the installation method.

Specifications

Application (breaker)

Material

Protection

Order information

DF-SAE

For all breakers

Plastic

IP 20

Art. no. 28319

MITSUBISHI ELECTRIC

SUPER AE

17

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

Current transformer (CT)

These current transformers (CT and sensor coil) are suitable for the main conductor and the N conductor.

Current transformers of type CT-06첸첸첸 serve the reduction of I n max

.on an

AE 1000.

Specifications

Application (breaker) *

Rated current I n max

** (A) 315 500 630 1000 1250

Order information

Art. no. 30476 30477 30478 33437 30479

*

More CTs on request.

Shipping contents includs CT and sensor coil for 1 pole. Other transformers on request.

** At 40°C and 50/60 Hz (other temperatures see Technical Information on page 48)

1600

30480

1250

43387

1600

62748

2000

39539

2500

39540

3200

39541

Neutral current transformer (NCT)

Diagram

The neutral CT is used for ground fault protection when a 3 pole breaker is used on a

3 phase 4 wire system.It should be used together with a electronic trip relay that has the ground fault protection (GFR) option.

Elektr.Auslöserelais mit Erdschlussschutz

Specifications

Application(breaker) *

Current range

AE1000 AE1000 AE1250 AE1600 AE2000 AE2500 AE3200 AE4000 AE5000 AE6300

(A) 630 1000 1250 1600 2000 2500 3200 4000 5000 6300

Order information

Art. no. 39038 39026 33853 37323 39037 39036 39035 62330 62329 62328

* A suitable resistor (0.1

/ 10 W) is attached to the product. Further technical details on request.

For AE4000-SSC on request.

External current transformer (ZCT)

Load circuit method (ZCT) Transformer ground wire method (ZT)

C2

SHT

C1

N2

714

N1

713

L2 L1

C2

SHT

C1

N2

714

N1

713

L2 L1

Power supply

Power supply

Specifications

Application

Hole diameter for wire *

ZCT-163 ZCT-323 ZCT-324 ZT-15A ZT-30A

Load circuits Transformer ground wire

(mm) 230x60 (oval) 370x108 (oval) 500x108 (oval)

15

30

Order information

Art. no. On request

* For detailed dimensions refer to page 46. Further specifications on request.

ZT-40A

40

This option is used to detect several amperes of earth leakage when used in combination with an electronic trip relay that has the earth leakage tripping (ER) option.

Two methods are available:

ZCT: three-load phase conductors (and

앬 the neutral conductor in a 4-wire system) are passed through the ZCT

ZT: The supply transformer’s ground wire passes through to earth.

ZT-60A

60

ZT-80A

80

ZT-100A

100

18

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ACCESSORIES

External power supply unit (PS)

This unit is used when a DC 24 V control supply is needed for the trip indicator on the electronic trip relay.

The unit can be installed from the front to the left side of the breaker (for dimensions

please refer to page 46).

Specifications

Rated voltage *

Input voltage range

Input capacity

Output voltage

Output current

PS-A200

(V) 100–110 / 200–220 (AC)

(%) +10 / -15 %

30 VA or less

(V) 24 (DC)

±

10 %

(A) 0.42 or less

Order information

Art. no. On request

* Rated frequency at AC = 50/60 Hz

PS-D200

200 (DC)

+10 / -15 %

30 W or less

24 (DC)

±

10 %

0.42 or less

On request

PS-A400

380–415 (AC)

+10 / -15 %

30 VA or less

24 (DC)

±

10 %

0.3 or less

On request

Field test devices

The test devices are for testing the functioning of the electronic trip relay.

It allows you to test the trip relay without the breaker being connected to the main supply.The breaker will trip when tested.

TING

TIME

OPERA

TESTER

MITSUBISHI

BREAKER

Y -2000

SIGNAL

S1

S2

60

Hz

ST

OP UENCY

FREQ

ST

OP

SIGNAL

50

Hz

VT

TC

OCR

TESTING

TRIP

OUTPUT

S1S2S3

50/60

TRIP

CHECK

OP

ST a?/OCR RESET

VT

OUTPUT

S3

AR

ST

T

ST

OP

888.88.8

6

8

?

7

5

3

4

2

1

0

SIGNAL

C

SET

SET

SIGNAL

ADJUST

UP

DO

WN

(Y2000)

Specifications

Test functions

Power supply *

Test current signal setting

Others

Y-160

LTD, STD, INST, Groundfault

100–120 V, 200–240 V (AC) or battery

Time counter

Order information

Art. no. 27497

* Rated frequency at AC = 50/60 Hz

Y-2000

LTD, INST, STD, Groundfault, pre-alarm

100–240 V (AC)

Ammeter, time counter

27496

Test jumper (TJ)

The test jumper cable is for testing the functioning of the circuit breaker when the unit is removed from its cradle.

Take the breaker out of its cradle and use this cable to switch the breaker on and off electrically,so that you can check all its functions.

Specifications

Cable length

TJ-SAE

(m) 3 *

Order information

Art. no. 30457

* Other lengths on request

MITSUBISHI ELECTRIC

SUPER AE

19

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Introduction and selection

Functions

Long-time-delay

+ Short-time-delay

+ Instantaneuous

Trip indicator

Applicable types B type

Code — ST SPT SPGT SPET MT MPT MPGT

L

S

I

쏹 쏹 쏹 쏹 쏹 쏹 쏹

TRIP

쏹 쏹 쏹 쏹 쏹 쏹 쏹

Load current indicator

STD lock button

OCR alarm

LCI

쏹 쏹

AL

쏹 쏹

쏹 쏹 쏹

쏹 쏹 쏹 쏹

— — —

Test terminal

Pre-alarm

TEST

쏹 쏹

PAL

— —

쏹 쏹

Ground fault

GFR

— — —

— — —

Remarks Reference

Page 23, 25 required *)

— required *)

For characteristics check

1. With ground fault alarm switch

2. If a 3-pole breaker is used in a 4-wire ordered.

3. The ground fault protection (GFR) is not

Page 22, 24

Page 22, 24

Page 23, 25

Page 29

Page 29

Page 23, 25

Page 22, 24

Page 28

Accessory

3and

Earth leakage

Instantaneous / MCR

ER

— — — —

— — —

LM

쎻 쎻

TAL

쎻 쎻

— — — — — — —

햲 햲 햲 햲

— — —

햲 햲 햲 햲

— — —

An external power supply for trip indication (TRIP) and relay control is required for all type of relays.

required required *) required *)

The sensor is integrated in the breaker.

function (L) is not available.

and MCR characteristics is possible.

available.

and MCR characteristics is not possible.

Page 28

Page 29

Page 29

Page 22, 23

— —

쏹 Equipped with function as standard.

— Function not available.

쎻 Function available as an option.

햲 Only one of the special versions (MCR-I,or MCR-C) is available as an option.

*

No additional power supply is required as long as control power is available.

** Other voltages on request.Rated frequency at AC = 50/60 Hz.

Special notes:

The circuit breakers are equipped with the S type relay in ST1A version (applicable voltage range AC 100–120/200–240 V) as standard(refer to page 6).

All other model types and accessories can be configured and ordered individually.

In the table on page 30 and 31 the most common configurations are listed with order informations.

The trip relay type B is suitable for switch disconnectors with instantaneous MCR characteristics only.

20

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Characteristics setting table

Function Application

ST SPT SPGT SPET MT MPT MPGT

(I nmax

)

Rated current (I n

)

Uninterrupted current (I

U)

S type

S type

(I

L

)

M type

S type

Time (T

L

)

M type

(I sd

)

Time

(T sd

)

(I i

)

M type

(I n max.

)

Maximum rated current n max

)

× setting

Rated current (I setting n

)

× setting

U

)

Rated current (I n

)

×

2

U

)

×

1.2

L

)

Long-time delay

L

)

× setting

Rated current (I n

)

At short-time delay

×

1.5

sd

)

Rated current (I n

)

× setting

U

)

Long-time delay current (I

L

)

0.80–0.82–0.84–0.86–0.88–0.90–0.92–0.94–0.96–0.98–1.0

(adjustable in steps)

— —

12–25–50–100–150sec

±

20 %

1–1.05–1.1–1.15–1.2

±

5 %

12–20–25–30–40–60 s

±

20 %

— — Details on request

2–3–4–6–8–10

±

15 %

0–0.1–0.2–0.3–0.4–0.5 s

±

20 %

Remark: the operating time for "0" is 0.05 sec. (only for M type)

AE5000-SS: 4–6–8–10–12

±

4–6–8–10–12–16

±

15 %

±

15 % (adjustable in steps each)

(I p

)

S type

M type

0.7–0.8–0.9–1.0–OVER

±

10 %

Time (T p

)

At long-time delay time (T

L

)

— 0.5 times ± 20 %

Current g

)

Maximum rated current n max

) × setting

— —

Self holding

0.1–0.2–0.3–0.5 ±20%

AE4000-SSA/SSC,

0.2–0.3–0.5

±

20 %

(adjustable in steps each)

0.3–0.8–1.5–3 s

±

20 %

Time (T g

)

Current e

)

Time (T e

)

S type e

) g

)

At earth leakage current (I e

)

— —

— —

— —

Not available at I n max

315 A, 500 A and AE 1000-SH, 630 A.

At 105 % non trip, at 125 % pick up.

Note: The electronic trip relay will be delivered set to the values shown in bold type.

1–2–3–5 A

±

20 %

0.3–0.8–1.5–3 s

±

20 %

0.5 times ± 20 %

Automatic reset

0.1–0.2–0.3–0.5±20%

AE4000-SSA/SSC,

0.2–0.3–0.5

±

20 %

(adjustable in steps each)

0.3–0.8–1.5–3s

±

20 %

Overview of rated currents (I n max

) – CT ratings

AE1000-SS AE1250-SS AE1600-SS AE2000-SS "SS" type

Rated current n max

)

"SH" type

Rated current

(I n max

)

AE1000-SH

1250 1600

AE1250-SH AE16000-SH AE2000-SH

1250 1600 2000

AE2500-SS

2500

AE2500-SH

2500

AE3200-SS AE4000-SSA/SSC AE4000-SS

3200 4000 4000

AE3200-SH

3200

AE5000-SS

5000

AE6300-SS

6300

MITSUBISHI ELECTRIC

SUPER AE

21

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

S Types – General Protection

Trip Indicator

Display of tripping condition:

L for Long-time delay

S/I for short-time delay (S) /

앬 instantaneous (I)

G for ground fault (GFR)

E for earth leakage (ER)

Both an LED display (red) and a relay output are provided.

Remarks: 쐃, 쐇, 쐏

Pre-Alarm Display

Pre-alarm display when a pre-determined load current is reached.

Display method:Both an LED display

(yellow) and a relay output are available.

The "PAL" LED lights up when the preset value is exceeded (the relay is not

앬 activated when this happens).

The relay output is activated when the

"PAL OUT" LED lights up.

The "PAL OUT" is self-holding and keeps lightning, even if the load value is again smaller than the set value.

Remarks: 쐃, 쐇, 쐏

Temperature Alarm

An alarm signal is generated when the temperatureofthemaincontactsrisesabove thethreshold level (approx.170 °C or more).

Display methods:Both an LED indicator

(red) and a relay output are provided.

Remarks: 쐃, 쐇, 쐏

Load Current Indicator

Indicates the percentage of uninterrupted current (I u

) in the following steps

60-70-80-90-100-OVER.

LED indication in different colours:

60 – 80 % = green

90 – 100 % = yellow

OVER = red

The LEDs goes out when the breaker trips.

ELECTRONIC TRIP RELAY

MODEL

SPGT - C1AT

RESET

L S/I

TRIP INDICATOR

ALARM

PAL P.U.

PAL OUT

G

TAL

LOAD CURRENT % lu

60 80 100 OVER

RATED CURRENT MAX.

(CT RATING)

I

N MAX

A

RATED CURRENT

0.7

0.8 0.91.0

0.6

0.5

X I N MAX

PAL P.U. Ip

0.9

1.0 OVER

0.8

0.7

X Iu

UNINTERRUPTED

CURRENT Iu

.88

.84

.92

.80

X I N

.96

1.0

STD P.U. lsd

2

3

4

6 8 10

X Iu

INST P.U. li

4

6

8

10 12 16

X Iu

GFR P.U. lg

0.5

0.3

0.2

0.1

X In max.

STD LOCK INST MCR

TRIP ALARM

GFR TIME

3.0

1.5

0.8

0.3

MADE IN JAPAN

OCR Alarm Contact

An alarm signal is output to the contact when the breaker is tripped by one of the following causes:

L Long-time delay

S Short-time delay

I Instananeous trip (I) or MCR

G Ground fault or

E Earth leakage

Remarks: 쐋, 쐏 lu X 2 lsd X 1.5

LTD TIME

25

12

100 150

50

SEC.

STD TIME

0.2

0.3 0.4 0.5

0.1

0

SEC.

TEST

Indicator Reset Button

Pressing this button resets the displays and the relay output.

Trip indicator (TRIP)

Unusual temperature indicator (TAL)

Pre-alarm (PAL)

Remarks:

All functions marked in gray are included as standard equipment (standard relay

ST1A).

This overview lists the maximum possible functionality of the units.

Trip relays with special functions (functions wich are not marked in gray) have to be

ordered seperately (please refer to order

information on page 30 and 31).

Page 28 and following contain a detailled

description of all special functions.

� An external power supply for trip indication and relay control is required for all type of relays.The voltage range for the power supply must be within one of the following ranges:

- 1: AC 100–120 / 200–240 V (standard)

- 2: DC 100–125 V

- 4: DC 24–60 V

(other voltages on request)

쐇 The LED will go out when the control power supply is interrupted or when the RESET button is pushed.

쐋 An external self-hold circuit is required, as the alarm signal pulse has a duration of only 0.03 sec.

쐏 The contact rating (A) for the signal relays are listed in the table below.

Inductive load* Voltage (V)

AC

DC

120

250

30

125

Resistive load

2

0.2

* cos ϕ

= 0,4 , L/R = 7 msec

2

0.1

22

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Basic Setting

Rated Current

RATED CURRENT

The maximum rated current can be selected as follows:

Max.rated current (I n max

) x setting (A)

0.5-0.6-0.7-0.8-0.9-1.0

AE4000-SSA/SSC:0.8–0.9–1.0

Changing this setting changes the following values proportionally:

Uninterrupted current (I u

)

Short-time delay current (I sd

)

Instantaneous current (I

Pre-alarm (I p

) i

)

Overload Protection

Uninterrupted Current (I

u

)

UNINTERRUPTED CURRENT

Rated current (I n

) x setting (A)

0.80-0.84-0.88-0.92-0.96-1.0

Used for setting the continuous uninterrupted current value.The actual tripping range is I u x 1.05 – 1.25.

The load current is displayed as a percentage of the uninterrupted current and thus changes proportionally when the uninterrupted current setting is changed.

Short-Circuit Protection (STD)

Short-Time Delay P.U.Current (I

sd

)

STD P.U.

Rated current (I n

) x setting (A)

2-3-4-6-8-10

Current threshold value setting for short-time delay tripping.

Ground Fault Protection (GFR)

Ground Fault P.U.Current (I

g

)

GFR P.U.

Max.rated current (I x setting (A) n max.

)

0.1-0.2-0.3-0.5

AE4000-SSA/SSC;AE4000–6300:

0.2-0.3-0.5

The function is not available when

I n max.

is less than 630 A and for

AE1000-SH I n max

630 A.

Short-Time Delay Time (T

sd

)

STD TIME

Time-delay setting (in seconds)

0-0.1-0.2-0.3-0.4-0.5

The setting value is the operating time when the current flowing is the short-time delay current setting (I sd

) × 1,5.

If the dial is set to 0 seconds the breaker will trip in 0.05 seconds.

Short-Time Delay Lock Button

STD LOCK

When measuring the instantaneous tripping current,press the short time delay operation inhibit button (STD LOCK) in order to disable the short-time-delay tripping function.

Ground Fault Time (T

g

)

GFR TIME

GFR time setting (in seconds)

0.3-0.8-1.5-3

The setting specifies the operating time when the current flowing is the ground fault current value setting (I g

) x 1.5.

Ground Fault Trip Switch

GFR TRIP / ALARM

The breaker will trip when the switch is set to the "TRIP" position.

When the switch is set to the "ALARM" position a red trip indicator LED will light up and the relay output will be activated when a ground fault occurs;the breaker will not trip,however.

The switch must be set to the "TRIP" position when the overcurrent tripping characteristic is activated (refer to p.28).

Long-Time Delay Time (T

L

)

LTD TIME

Time setting (in seconds)

12-25-50-100-150

This value specifies the operating time when the current flowing is the uninterrupted current set value × 2.

The pre-alarm operating time is half of the long-time-delay time setting.

INST/MCR Switch

INST/MCR

This switch makes it possible to select between instantaneous operation characteristic (INST) and MCR characteristic.

The MCR characteristics the abbreviationfor

Making Current Release.With this characteristic,instantaneous tripping is only possible if a short circuit occurs during switch-

ON.After the initial switch-ON,the time delay tripping characteristic is active but the instantaneous tripping is not possible.

Short-Circuit Protection (instantaneous)

Instantaneous P.U.Current (I

i

)

Rated current (I n

) x setting (A)

4-6-8-10-12-16

AE5000:4-6-8-10-12

AE6300:4-6-8-10

Sets the threshold current value for instantaneous tripping.

Earth Leakage Protection (I

e

)

ER P.U.

Current setting 1–2–3–5

Both external ZCT and SHT are required (see page 18 and 26 for further details).

Others

Test Terminal

Test functions:

Tripping characteristics

Long-time-delay (L)

Short-time-delay (S)

Instantaneous (I)

Pre-alarm (P)

Ground fault (GFR)

A special testing device is required

(see page 19).

Pre-Alarm Current (I

p

)

PAL P.U.

Rated current (I u

) x setting (A)

0.7-0.8-0.9-1.0-OVER

Current setting for pre-alarm activation.

Earth Leakage Protection (T

e

)

(TE) ER TIME

Time setting (in seconds)

0.3–0.8–1.5–3

The setting represents the operating time when the current flowing is the earth leakage current value setting × 1,5.

The earth leakage protection facility is not illustrated because it is only possible to have either earth leakage or ground fault protection.

The bold marked values show the setting at time of shipment.

MITSUBISHI ELECTRIC

SUPER AE

23

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

M Types – General Protection

Trip Indicator

Display of tripping condition:

L for Long-time delay

S/I for short-time delay (S) / instantaneous (I)

G for ground fault (GFR)

Both an LED display (red) and a relay output are provided.

Remarks: 쐃, 쐇, 쐏

Pre-Alarm Display

Pre-alarm display when a pre-determined load current is reached.

Display method:Both an LED display

(yellow) and a relay output are available.

The "PAL" LED lights up when the preset value is exceeded (the relay is not

앬 activated when this happens).

The relay output is activated when the

"PAL OUT" LED lights up.

The "PAL OUT" is self-holding and keeps lightning, even if the load value is again smaller than the set value.

Remarks: 쐃, 쐇, 쐏

Temperature Alarm

An alarm signal is generated when the temperature of the main contacts rises above the threshold level (approx.170 °C or more).

Display methods:Both an LED indicator

(red) and a relay output are provided.

Remarks: 쐃, 쐇, 쐏

Load Current Indicator

Indicates the percentage of uninterrupted current (I

L

) in the following steps

50-60-70-80-90-100-OVER.

LED indication in different colours:

50 – 70 % = green

80 – 90 % = yellow

100 % = red

The LEDs goes out when the breaker trips.

ELECTRONIC TRIP RELAY

MODEL

MPGT - 1AT

RESET

L

TRIP INDICATOR

ALARM

PAL P.U.

S/I

PAL OUT

G

TAL

LOAD CURRENT % l

L

50 70 90 100

RATED CURRENT MAX.

(CT RATING)

I

N MAX

A

RATED CURRENT In

A

PAL P.U. Ip

.92

.961.0

.88

.84

X I L

LTD P.U. I

L

1.05

1.0

1.15

1.1

1.2

X In

STD P.U. lsd

2.5

2

3

3.5 4 4.5

X In

INST P.U. li

6

4

8

10 12 16

X Iu

GFR P.U. lg

0.3

0.2

0.5

0.1

X In max.

TRIP ALARM

STD LOCK

GFR TIME

1.5

0.8

FINE

LTD TIME

20

15

25

30 4060 s lsd X 1.5

STD TIME

0.2

0.30.4 0.5

0.1

0 s

TEST

MADE IN JAPAN

OCR Alarm Contact

An alarm signal is output to the contact when the breaker is tripped by one of the following causes:

L Long-time delay

S Short-time delay

I Instananeous trip (I)

G Ground fault

Remarks: 쐋, 쐏

Indicator Reset Button

Pressing this button resets the displays and the relay output.

Trip indicator (TRIP)

Unusual temperature indicator (TAL)

Pre-alarm (PAL)

Remarks:

All functions marked in gray are included asstandardequipment(standardrelayMT1A).

This overview lists the maximum possible functionality of the units.

Trip relays with special functions (functions wich are not marked in gray) have to be ordered seperately (please refer to order

information on page 30 and 31).

Page 28 and following contain a detailled

description of all special functions.

� An external power supply for trip indication and relay control is required for all type of relays.The voltage range for the power supply must be within one of the following ranges:

- 1: AC 100–120 / 200–240 V (standard)

- 4: DC 24–60 V

(other voltages on request)

쐇 The LED will go out when the control power supply is interrupted or when the RESET button is pushed.

쐋 An external self-hold circuit is required, as the alarm signal pulse has a duration of only 0.03 sec.

쐏 The contact rating (A) for the signal relays are listed in the table below.

Inductive load* Voltage (V)

AC

120

DC

250

30

125

Resistive load

2

0.2

* cos ϕ

= 0,4 , L/R = 7 msec

2

0.1

24

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Basic Setting

Rated Current

RATED CURRENT

The rated current will be preset to a fixed value at time of shipment (select a value between 0.5 and 10 (AE4000-SSA/SSC:0.8

and 1.0) of the maximum rated current).

The value is stamped on the relay.

Note:

Specify the preset rated current in written form when ordering.

Overload Protection

Long-Time Delay Current (I

L

)

LTD P.U.

Rated current (I n

) x setting (A)

1-1.05-1.1-1.15-1.2

The breaker trips within a range from

(I

L

) x 0.95 to 1.05.

The load current is displayed as a percentage of the long-time delay current (I

L

).

The pre-alarm set value varies proportionally to the long-time delay current setting.

Long-Time Delay Time (T

L

)

LTD TIME

Time setting (in seconds)

15-20-25-30-40-60

This value specifies the operating time when the current flowing is the long-time delay current set value (I

L) x 1.2.

The pre-alarm operating time is half of the long-time delay setting.

Long-Time Delay Time FINE(T

L

)

FINE

Fine adjustment of long-time delay time.

Detailled information on request.

This setting has no influence on the pre-alarm time.

Pre-Alarm (I

p

)

PAL P.U.

Long-time-delay current value (I

L

) x setting

0.84-0.88-0.92-0.96-1.0

Threshold value for pre-alarm operation.

Short-Circuit Protection (STD)

Short-Time Delay P.U.Current (I

sd

)

STD P.U.

Rated current (I n

2-2.5-3-3.5-4-4.5

) x setting (A)

Current threshold value setting for short-time delay tripping.

Short-Time Delay Time (T

sd

)

STD TIME

Time delay setting (in seconds)

0-0.1-0.2-0.3-0.4-0.5

The setting value is the operating time when the current flowing is the short-time delay current setting (I sd

) x 1.5.

If the dial is set to 0 seconds the breaker will trip in 0.05 seconds.

Short-Time Delay Lock Button

STD LOCK

When measuring the instantaneous tripping current,press the short time delay operation inhibit button (STD LOCK) in order to disable the short-time-delay tripping function.

Short-Circuit Protection (instantaneous)

Instantaneous P.U.Current (I

INST P.U.

Rated current (I n

) x setting (A)

4-6-8-10-12-16

AE5000:4-6-8-10-12

AE6300:4-6-8-10

Sets the threshold current value for instantaneous tripping.

i

)

Ground Fault Protection

Ground Fault P.U.Current (I

g

)

GFR P.U.

Max.rated current (I n max.

0.1-0.2-0.3-0.5

) x setting (A)

AE4000-SSA/SSC,AE4000–6300:

0.2-0.3-0.5

This function is not available if max.

rated current values I n max is less than

630 A and for AE1000-SH,I n max

630 A.

Ground Fault Time (T

g

)

GFR TIME

Time setting (in seconds)

0.3-0.8-1.5-3

The setting specifies the operating time when the current flowing is the ground fault current value setting (I g

) x 1.5.

Ground Fault Trip Switch

GFR TRIP / ALARM

The breaker will trip when the switch is set to the "TRIP" position.

When the switch is set to the "ALARM" position a red trip indicator LED will light up and the relay output will be activated when a ground fault occurs;the breaker will not trip,however.

The switch must be set to the "TRIP" position when the overcurrent tripping characteristic is activated (refer to p.28).

Others

Test Terminal

Test functions:

Tripping characteristics

Long-time-delay (L)

Short-time-delay (S)

Instantaneous (I)

Pre-alarm (P)

Ground fault (GFR)

A special testing device is required

(see page 19).

The bold marked values show the setting at time of shipment.

MITSUBISHI ELECTRIC

SUPER AE

25

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

How to Adjust the Electronic Trip Relay

S type setting dial operation schematic – General use

INST Instantaneous P.U. Current Ii

Max. rated current In max

STD Short-Time Delay P.U. Current Isd

Rated Current In Pre-Alarm Current Ip

GFR Ground Fault P.U. Current Ig or

ER Earth Leackage Fault Current I

∆ n

Load Current Indicator LEDs

M type setting dial operation schematic – Generator protector use

INST Instantaneous P.U. Current Ii

Max. rated current In max

STD Short-Time Delay P.U. Current Isd

Rated Current In

Delay Current I

L

GFR Ground Fault P.U. Current Ig

Pre-Alarm Current Ip

Load Current Indicator LEDs

Characteristic curve for the example next page

1000

10

5

4

3

2

500

400

300

Pre-alarm current (I p

) setting range

100

60

50

40

Ground fault current (I g

) setting range

20

1

0,5

0,4

0,3

0,2

Ground fault operation time (T g

) setting range

0,1

0,05

0,04

0,03

0,02

Short-time delay operation time (T sd

) setting range

Long-time delay operation time (T

L

) setting range

Short-time delay current (I sd

) setting range

Instantaneous current (I i

) setting range

0,01

5 10 20 50 100 125 200

Current (%)

500 1000 1600 2000 5000

26

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Setting example for S Type – General use

The following example shows in a simple way how you can set your required values on the S type trip relay.

Additional all current settings and operation times are calculated and shown.

I n

= 0.8× I n max

I n

= 0.8 × 1600 A

I n

= 1280 A

I

I u

= 0.9× I n

I n

= 0.8 × 1280 A n

= 1152 A

I p

I n

I n

= 0.8 × I u

= 0.8 × 1152 A

= 921,6 A

I g

I n

= 0.1× I n max

= 0.1 × 1600 A

I n

= 160 A

GFR TIME = 0.8s

(at I g

× 1.5 =

160 × 1.5 = 240 A)

ELECTRONIC TRIP RELAY

MODEL

SPGT - C1AT

RESET

L

TRIP INDICATOR

ALARM

PAL P.U.

S/I

PAL OUT

G

TAL

LOAD CURRENT % lu

60 80 100 OVER

RATED CURRENT MAX.

(CT RATING)

I

N MAX

1600 A

RATED CURRENT

0.8 0.9 1.0

0.7

0.6

0.5

X I

N MAX

PAL P.U. Ip

0.9

1.0 OVER

0.8

0.7

X Iu

UNINTERRUPTED

CURRENT Iu

.88

.84

.92

.80

.96

1.0

STD P.U. lsd

2

3

4

X Iu

6 8 10

INST P.U. li

4

6

8

10 12 16

X Iu

GFR P.U. lg

0.5

0.3

0.2

0.1

X In max.

TRIP ALARM

STD LOCK INST MCR

GFR TIME

1.5

3.0

lu X 2 lsd X 1.5

LTD TIME

100150

50

25

12

SEC.

STD TIME

0.2

0.3 0.4 0.5

0.1

0

SEC.

TEST

MADE IN JAPAN

I n,max

= 1600 A

I sd

I sd

I sd

= 3 × I n

= 3 × 1280 A

= 3840 A

I i

I i

=12 × I n

= 12 × 1280 A

I i

= 15360 A

LTD TIME T

L

= 100 s

(at I u

× 2 =

1152 × 2 = 2304 A)

STD TIME T sd

= 0.3s

(at I sd

× 1.5 =

3840 × 1.5 = 5760 A)

Pre-alarm pick-up time

= 0.5× T

L

= 50 s

(at I u

× 2 = 1152 × 2

= 2304 A)

Actual settings are as in the following table

Functions

Max. Rated Current

Set rated value

Uniterrupted Current

Long-Time Delay Time

Short-Time Delay P.U. Current

Short-Time Delay Time

I n

I

Description

n max

I u

LTD TIME

I sd

STD TIME

Setting value

1600 A

1280 A

1152 A

100 s ± 20 % (at 2304 A)

3840 A ± 15 %

0.3 s ± 20 % (at 5760 A)

Functions

Instantaneous P.U. Current

Pre-Alarm Current

Pre-alarm pick-up time

Ground Fault P.U. Current

Ground Fault Time

I p i

I

Description

I

PAL pick-up time g

GFR TIME

Setting value

15360 A ± 15 %

921,6 A ± 10 %

50 s ± 20 % (at2304 A)

160 A ± 20 %

0.8 s ± 20 % (at 240 A)

MITSUBISHI ELECTRIC

SUPER AE

27

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Special Functions – Accessories

Earth leakage protection (ER)

The earth leakage alarm facility is realised with an electronic trip relay with earth leakage protection (ER characteristics) and an external ZCT (refer to page 18 and 20).

When earth leakage current flows an

alarm is activated but the breaker does not

trip (see the earth leakage alarm system wiring diagram).

If you require the breaker to trip upon earth leakage you must also install an SHT device (see the earth leakage tripping system wiring diagram).Observe the voltage range specifications for the voltage tripping device SHT;the voltage tripping device (SHT) is suitable for 250 V AC/DC or less.

The earth leakage protection is not available for AE4000 to AE6300-SS breakers.

Earth leakage tripping system

C2

SHT

C1

N2

714

N1

713

L2 L1

Control power supply

Earth leakage tripping system

BZ

N2 N1

544

513

L2 L1

Control power supply

Pre-alarm (PAL)

If the load current flowing through the breaker exceeds the preset value the "PAL"

LED lights up and a relay output is activated.This is a useful option for ensuring a continuous power supply to an important circuit.

The operating characteristic shown in the graph is proportional to half of the long-time-delay tripping characteristic.It

has been designed to prevent unnecessary alarms from inrush currents to the load.

T

L represents the long-time delay time.

The general use relay output is of a self-hold type;the relay type for generator protection features auto reset.(The control power supply and reset button required for the LED display is also used internally for the pre-alarm).

Characteristics (type S)

Time (t)

1 h

10 min.

2 min.

1 min.

30 sec

10 sec

4 sec

1 sec

0.4 sec

0.1 sec

0.04 sec

Pre-alarm characteristics

Pre-alarm operating time

Pre-alarm current setting range

Pre-alarm operating time

Overcurrent characteristics

10 20 40 60

100

200 400 1000

600 2000

4000

6000

Current (%)

Ground fault protection (GFR)

When ground fault currents of several hundred amperes flow,it is possible that the long-time-delay or short-time-delay functions may not be able to protect the circuit.The ground fault function (GFR) can provide the necessary protection in these situations.Response sensitivity can be set in the range 0.1–0.2–0.3–0.5,multiplied by the maximum rated current (I

N max.

);operating time can be set in the range

0.3–0.8–1.5–3 seconds.

No control power supply is required for this function.

Similary with a 3 pole breaker, ground fault protection is also possible for a

3-phase, 3-wire circuit.

In a 3-phase, 4-wire circuit ground fault protection is also possible if the

3-pole breaker is combined with a neutral pole CT (NCT). See page 18 for details.

The ground fault protection is not available if the max. rated current

(I

N max.) is less than 315 A or 500 A and less than 630 A for AE1000SH.

4 pole breaker

GFR

Current sensor coil

28

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Temperature alarm (TAL)

When the temperature of the main contacts exceeds a pre-determind (approx.

170° C),a LED lights up and a relay contact

(NO contact) is activated.

This helps to prevent malfunctions and increase the service life of the contacts as it makes it possible to detect even temporary temperature increases.Since the relayoutputisselfholdingatemporaryrise in temperature more than 6 hours can also be detected (the control supply and the reset button are used in common with the trip indicator).

Note:

The power supply which is required for the

LED indicators,is additionally used for the internal temperature measurement.

Load current measurement (LM)

A direct current voltage signal which is converted from the effective value current in the electronic trip relay is taken out externally by using an isolation amplifier.Use the receiving indicator that can be operated by an input of 0–5 V DC since the voltage signal proportional to the largest phase current is transmitted.Moreover the voltage signal which is proportional to the largest phase current is then used to light the appropiate phase LED (the control supply is that used for the trip indicator).

Note:

Please consider that the wiring is within

3 m of the breaker control circuit terminal by using a twisted pair wire (with over

40 turns/meter).

The required control power supply for the LED indicator is common to the trip indicator

Output characteristics

10

5

0

0 25 100

Current (% of I

N max

)

200

Standard functions

The following functions are provided as standard for the electronic trip relays listed in this Catalogue.

OCR alarm (AL)

The OCR alarm is a short-time operating contact (NO contact) that indicates when the breaker has tripped as a result of an overcurrent situation.The AL unit is integrated in the electronic trip relay.

It operates when the breaker trips due to long-time-delay,short-time-delay,instantaneous/MCR and ground fault (GFR).

It is not activated when the breaker is tripped by the earth leakage (ER) protection facility

Note:

Though control power supply is not required for the operation of the overcurrent alarm (AL),an external self-hold circuit is required since the relay output is only activated for 0.03 seconds.

When a continuous output signal from the

OCR alarm (AL) is required,please use the output signal from the trip indicators L,S/I and G,which is operated by the same causes as the OCR alarm.

Neutral pole overcurrent protection (NP) in a 4-pole circuit

All electronic trip relays listed in this Catalogue are provided with 100 % Neutral pole protection for 4-pole breakers,if the fourth pole (neutral pole) is equipped with a CT.

More details on request.

MITSUBISHI ELECTRIC

SUPER AE

29

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Special Functions – Accessories

Unless otherwiseindicated,all circuitbrea- kers in the standard package are delivered with the electronic trip relay ST1A (see overview on pages 6 and 7).

If you require a different relay for a given circuit breaker,simply specify the relevant electronic trip relay separately when ordering the breaker.

The table on the right gives you an overview of different trip

relays.For detailed information please refer to page 20.

The table below gives you a selection of the most common electronic trip relays with the relevant ordering details.To order a certain relay,make sure you state the relevant order code.

Ordering procedure

Type (code)

SPT

Voltage code

1

Accessory

A

Type

Trip relay

Version

S

M

B

ST

ST-C

ST-I

SPT

SPT-C

SPT-I

SPGT

SPGT-C

SPGT-I

SPET

SPET-C

SPET-I

MT

MPT

MPGT

B-C

PAL

GFR

ER

Operating functions

MCR/C MCR/I

NP

AL

1

Voltage code

2 4

— — —

LM

Accessory

TAL

쏹 Function included in the relevant trip relay.

쎻 Function available as an option.

— Function either not included or not available.

Important:

The MCR function is not available for high performance breakers (i.e.the AE-SH series) and breaker types AE4000-SS up to AE6300-SS.

30

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Type Code

ST1A

ST2A

ST4A

STC1A

STC2A

STC4A

SPT1A

S

SPT2A

Description

Standard trip relay with OCR alarm (AL) without optional functions,

DC 100–125 V

MT4A

M

MPT1A

MPT4A

SPGTC2A

SPGTC4A

MT1A

SPT4A

SPGT1A

SPGT2A

SPGT4A

SPGTC1A

Trip relay with pre-alarm function (PAL), ground fault protection (GFR) and OCR alarm (AL),

AC 100-120 V and AC 200–240 V

Trip relay for generator protection with OCR alarm (AL), AC 100-120 V and AC 200–240 V

Trip relay for generator protection with OCR alarm (AL), DC 24–60 V

Trip relay for generator protection with pre-alarm function (PAL) and OCR alarm (AL),

AC 100-120 V and AC 200–240 V

MPGT1A

MPGT4A

B

BC0A Closing short-circuit current actuator with MCR characteristics and OCR alarm (AL)

Relay for frame sizes AE5000-SS and AE6300-SS on request.

Application

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS/SH, AE4000-SS

AE4000-SSA/SSC

AE1000–AE3200-SS

On request

136000

On request

136001

On request

136002

On request

136003

On request

136004

On request

136005

On request

136006

On request

136011

135994

On request

135995

On request

135996

On request

135997

On request

135998

On request

135999

Art. no.

135976

On request

135977

On request

135978

On request

135979

On request

135980

On request

135981

On request

135992

On request

135993

On request

SPT4A-SAE

SPT4A-SAE-45

SPGT1A-SAE

SPGT1A-SAE-45

SPGT2A-SAE

SPGT2A-SAE-45

SPGT4A-SAE

SPGT4A-SAE-45

SPGTC1A-SAE

SPGTC1A-SAE-45

SPGTC2A-SAE

SPGTC2A-SAE-45

SPGTC4A-SAE

SPGTC4A-SAE-45

MT1A-SAE

MT1A-SAE-45

MT4A-SAE

MT4A-SAE-45

MPT1A-SAE

MPT1A-SAE-45

MPT4A-SAE

MPT4A-SAE-45

MPGT1A-SAE

MPGT1A-SAE-45

MPGT4A-SAE

MPGT4A-SAE-45

BC0A-SAE

Ordering information

ST1A-SAE

ST1A-SAE-45

ST2A-SAE

ST2A-SAE-45

ST4A-SAE

ST4A-SAE-45

STC1A-SAE

STC1A-SAE-45

STC2A-SAE

STC2A-SAE-45

STC4A-SAE

STC4A-SAE-45

SPT1A-SAE

SPT1A-SAE-45

SPT2A-SAE

SPT2A-SAE-45

MITSUBISHI ELECTRIC

SUPER AE

31

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Operating Characteristics Type S

Braker types AE1000-SS/SH to AE3200-SS/SH, AE4000-SSA/SSC, AE4000-SS to AE6300-SS

1000

500

400

300

200

Pre-alarm current (I p

) setting range

Uninterruptedcurrent×setting 0.7-0.8-0.9-1.0-OVER× I u

±10%

Long-time delay operation time (T

L

) setting range

(Uninterrupted current × 2) 12-25-50-100-150 sec ± 20%

Pre-alarm operation time (T p

)

Long-time delay operation time T

L

× 0.5 ± 20%

100

60

50

40

30

20

10

Ground fault current (I

0.1-0.2-0.3-0.5× I g n max

) setting range

Max. rated current × setting

± 20%

0,10.2-0.3-0.5× I n max

± 20%

5

4

3

2

1

Short-time delay current (I sd

Rated current × setting

2-3-4-6-8-10 × I n

± 15 %

) setting range

0,5

0,4

0,3

0,2

Ground fault operation time (T g

) setting range

(Ground fault current I g

× 1.5) 0.3-0.8-1.5-3sec ± 20%

0,1

0,05

0,04

0,03

0,02

0,01

2

Setting at shipment

Adjustable

Short-time delay operation time (T sd

) setting range

(Short-time delay current I sd

× 1.5) 0-0.1-0.2-0.3-0.4-0.5 sec ± 20%

5 10

Current

Instantaneous current (I i

) setting range

Rated current × setting

4-6-8-10-12-16 × I n

± 15%

4-6-8-10-12 -16 × I n

± 15% AE5000-SS

4-6-8-10 -12-16 × I n

± 15% AE6300-SS

20 50

Long time delay, pre-alarm

Short-time delay / instantaneous

Ground fault

100125 200 500

% of uninterrupted current (I u

)

% of rated current (I n

)

% of max. rated current (I n max

)

1000 16002000 5000

32

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

ELECTRONIC TRIP RELAY

Operating Characteristics Type M

Breaker types AE1000-SS/SH to AE3200-SS/SH, AE4000-SSA/SSC, AE4000-SS to AE6300-SS

1000

Long-time delay current (I

L

Rated current × setting

) setting range

1.0-1.05-1.1-1.15-1.2 × I n

± 15%

500

400

300

200

Pre-alarm current (I p

) setting range

Long-time delay current × setting

0.84-0.88-0.92-0.96-1.0× I

L

± 20%

Long-time delay operation time (T

L

)settingrange

(Long-time delay current × 1.2) 15-20-25-30-40-60 s ± 20%

Pre-alarm operation time (T p

)

Long-time delay operation time T

L

× 0.5 ± 20%

100

60

50

40

30

20

Ground fault current (I g

) setting range

Max. rated current × setting

0.1-0.2-0.3-0.5 × I

0,10.2-0.3-0.5 × I n max

± 20%

± 20%

10

Short-time delay current (I sd

) setting range

Rated current × setting 2-2.5-3-3.5-4-4.5× I n

± 20%

5

4

3

2

1

0,5

0,4

0,3

0,2

Ground fault operation time (T g

) setting range

(GroundfaultcurrentI g

×1.5) 0.3-0.8-1.5-3s ± 20%

0,1

0,05

0,04

0,03

0,02

0,01

2

Setting at shipment

Adjustable

5

Short-time delay operation time (T s

) setting range

(Short-time delay current I sd

× 1.5) 0-0.1-0.2-0.3-0.4-0.5 s ± 20%

10

Instantaneous current (I i

) setting range

Rated current × setting

4-6-8-10-12-16 × I n

± 15%

4-6-8-10-12 -16 × I n

± 15% (AE5000-SS)

4-6-8-10 -12-16 × I n

± 15% (AE6300-SS)

Current

20 50 100 120 200 500

Pre-alarm

Long-/Short-time delay / instantaneous % of rated current (I

Ground fault

% Long time delay current (I

L n

)

% of max. rated current (I n max

)

)

1000

1600 2000

5000

MITSUBISHI ELECTRIC

SUPER AE

33

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Wiring diagram – Super AE air circuit breakers with electronic trip relay type S or M

The following circuit diagram shows the breaker with fully equipped accessories.

2000 V

Dielectric voltage

EN 50005

342 344 332 334 322 324 312 314

CLb CLa CLb CLa CLb CLa CLb CLa

Reset

1500 V

Dielectric voltage

Xa

L1

R+

TAL G / E

564 544 513

T5 T3 T0+

97

AL+

CL

CL CL CL

AL

EN 50005

CLc

341

CLc

331

CLc

321

CLc

311

R2– R1– T4– T2–

L3 L2 554 534

T1–

524

AL–

98

P S/I L

Cell switches

Description of terminal layout

Terminal

13/14, 23/24, 33/34,

43/44, 53/54

Code Function

AXa Auxiliary switch contact a

AXb Auxiliary switch contact b

413 / 414

U1 / U2

A1 / A2

C1 / C2

J1 / J2

713 / 714

TS Charged signal

MD Motor charging

CC Closing coil

SHT Shunt trip

UVT Under-voltage trip

ER Earth leakage trip

Remark

NO contact

NC contact

NO contact

Terminal

N1 / N2

Code Function

NP Neutral pole CT or ext. ZCT

Remark

M1 / M2

LM Load current measurement

97 / 98

AL OCR alarm contact

513/524/534/544

TRIP Trip indication contact L, S/I, G or E

513 / 554

PAL Pre-alarm indication contact

513 / 564

L1 / L2 / L3

311 – 344

TAL Temperature alarm indication contact

Signal

Signal

Signal

— Electronic trip relay unit control power supply See table on p. 35

— Cell switches (drawout type breakers only) e.g. for SHT trip

34

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

When using coil loads such as DC magnetic switches,etc.as operating voltage in the peripheral circuits,install diodes,surge absorbers,etc.as a countermeasure against surge (counter electromotive force) at the time of switching.On the

2000 V

Dielectric voltage drawout type,the control circuit terminal block should be moved to the left or right by 5 mm after the cables are connected.

OFF ON

OFF

M1 N1

LM+ CT+

713

ST+

J1

U+

C1 A1 U1 413 51 41 31 21 11 53 43 33 23 13

S+ CC+ M+ TS+ B10+ B9+ B8+ B7+ B6+ A5+ A4+ A3+ A2+ A1+

ON

UVT SHT CC

M

AX AX AX AX AX AX AX AX AX AX

LM– CT– ST– U–

M2 N2 714 J2

S– CC– M–

C2 A2 U2

TS–

414

B10–

52

B9–

42

B8–

32

B7–

22

B6–

12

A5–

54

A4–

44

A3– A2– A1–

34 24 14

SHT

Under-voltage trip

Charged signal Auxiliary switches

Power supply for electronic trip relay

Electrical connection

Voltage

AC

100–120 V

200–240 V

DC

100–125 V

DC

24–60 V

+

+

L1

Terminals

L2

L3

Description of symbols for the accessory

Description

Symbol Function

M

CC

SHT

UVT

Motor

Closing coil

Shunt trip device

Undervoltage trip device

S/I

Short-time delay trip indication lamp

Symbol Function

G or E

P

TAL

Ground fault trip or earth leakage indication lamp

Pre-alarm indication lamp

Unusual temperatur indication lamp

Self-holding relay

Wiring by factory

Wiring by customer

MITSUBISHI ELECTRIC

SUPER AE

35

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Fixed Type Breaker

Breaker types AE1000 to AE3200-SS/SH with standard connection (horizontal terminals)

Operating panel center

Control terminals

A B

N

eutral pole

268

3P 4P

144 88

N

eutral pole

H H H

J

4 x Ø 14

38

Breaker type

AE1000 – 1600-SS

AE2000 – 3200-SS

AE1000 – 3200-SH

C*

E

228

D*

F

Frontview

K

31

40

175*

290

288

Sideview

4P 3P

23

AE2000–3200-SS

AE1000–3200-SH

Rearview

AE2000–3200-SS

AE1000–3200-SH

3

4

3

4

Pole A

3 142

B

142

C

156

D

156

E

170

F

170

G

15

4 142 227 156 241 170 255 15

232

232

232

232

187

317

187

317

246

246

246

246

201

331

201

331

260

260

260

260

215

345

215

345

20

20

20

20

H

85

85

130 95

130 95

130 95

130 95

J

50

50

70

70

40

40

K

40

40

AE1000–1600-SS

38

17

2 - Ø 13

Main circuit terminal

38

17

4 - Ø 13

[mm]

Door frame and panel-cut

Panel-cut

Operating panel center

Door frame panel-cut

Operating panel center

8 - Ø 7

235 Breaker frame

247

271

Breaker frame

[mm]

36

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Breaker types AE1000 to AE3200-SS/SH with Vertical terminal adapter (VAT)

AE1000–1600-SS

Version A

85 85 85

N

eutral pole

T 50

4P 3P

X

Breaker

AE1000–1600-SS

AE2000–2500-SS

AE3200-SS

AE1000–2500-SH

AE3200-SH

X

108

123

123

153

153

20

25

20

25

T

15

Operating panel center

130 130

23

130

Version B

T

N

eutral pole

100

4P 3P

X

[mm]

Vertical terminal adapter (VTA)

Version A

Connecting area

38

15

Version B

38

2 - Ø 13

15

4 - Ø 13

15

Breaker

AE1000–1600-SS

AE2000–2500-SS

AE3200-SS

AE1000–2500-SH

AE3200-SH

Version

B

B

A

B

B

T

25

20

15

20

25

100

38

2 - Ø 13

Connecting area

115

38

15

5 - Ø 13

[mm]

MITSUBISHI ELECTRIC

SUPER AE

37

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Drawout Type Breaker

Breaker types AE1000 to AE3200-SS with standard connection (horizontal terminals)

Operating panel center

A

228

B

Control terminals

Disconnected position

Test position

51

35

E

Neutral pole

3P 4P

Operating panel center

K K K

N

eutral pole

L

15

59

42,5

C

200

*

D

Earth terminal

(gegenüberliegende Seite)

23

61

H

F

G

40

220

*

48

452

Drawout position

Breaker

AE1000–1600-SS

AE2000–3200-SS

4 x Ø14

Front view Side view

Pole A B C D E F G H J K L

3 150 150 149 149 311 368 366 172 15 85 50

4 150 235 149 234 311 368 366 172 15 85 50

3 243 195 239 194 311 368 366 172 25 130 103

4 243 325 239 324 311 368 366 172 25 130 103

AE1000–1600-SS

38

15

2 - Ø 13

4P 3P

Rear view

AE2000–3200-SS

38

15

Main circuit terminal

23

4 - Ø 13

[mm]

Drawout handle, door frame and panel-cut

Drawout handle Panel-cut

Operating panel center

Door frame panel-cut

8 - Ø 7 max.173

200

Ø 22

Breaker

235

247

271

[mm]

38

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Breaker types AE1000 to AE3200-SS with vertical terminal adapter

85 85 85

AE1000–1600-SS

Version A

N

eutral pole

T

50

131

AE2000–3200-SS

Version B

4P 3P

T

N

eutral pole

Operating panel center

130 130

23

130

100

Breaker

AE1000–1600-SS

AE2000–2500-SS

AE3200-SS

20

25

T

15

4P 3P

146

[mm]

Vertical terminal adapter (VTA)

Version A

Connecting area

38

15

Version B

38

2 - Ø 13

15

4 - Ø 13

15

Breaker

AE1000–1600-SS

AE2000–2500-SS

AE3200-SS

Version

A

B

B

T

15

20

25

100

38

2 - Ø 13

Connecting area

115

38

15

5 - Ø 13

[mm]

MITSUBISHI ELECTRIC

SUPER AE

39

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Drawout Type Breaker

Breaker types AE1000 to AE3200-SH with standard connection (horizontal terminals)

External accessory

(e.g. UVT controller)

243

Operating panel center

228

Control terminals

3P: 195

4P: 325

3P 4P

Neutral pole

Disconnected position

Test position

51

35

341 handle radius 100

Operating panel center

130

23

130 130

N

eutral pole

B

15

33

4 x Ø14

265

42,5

200

*

Drawout handle insertion port

3P: 220

4P: 350

2 x Ø12 screw M8 liegende Seite)

Front view

23

61

202

220

*

398

40

396

Side view

48

452

Drawout position

4P 3P

Rear view

38

15

Breaker

AE1000–2500-SH

AE3200-SH

A

20

25

B

95

103

4 - Ø 13

[mm]

Drawout handle, door frame and panel-cut

Drawout handle Panel-cut

Operating panel center

Door frame panel-cut

8 - Ø 7 max.173

200

Ø 22

Breaker

235

247

271

[mm]

40

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Breaker types AE1000 to AE3200-SH with vertical terminal adapter

Operating panel center

130 130

23

130

T

100

Neutral pole

4P 3P

146

Breaker

AE1000–2500-SH

AE3200-SH

T

20

25

[mm]

Vertical terminal adapter (VTA)

4 - Ø 13

15

38

Connecting area

115

38

15

5 - Ø 13

Breaker

AE1000–2500-SH

AE3200-SH

Vers.

B

B

T

20

25

[mm]

MITSUBISHI ELECTRIC

SUPER AE

41

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Fixed Type Breaker

Breaker typ AE4000-SSA (Fixed with vertical terminal)

Operating panel center

232 4P: 317 (3P:187)

268

Control terminals

Neutral pole

3P 4P

144 88

Panel

7

4 x Ø14

38

228

246

*

260 4P: 345 (3P: 215)

Operating panel center

152

31

11

Front view

23

152

95

* Mounting pitch

Neutral pole

31

136

40

175

*

290

31

11

Operating panel center

145

288

Side view

30,5

145 145

95

10

Rear view 3-poles

Main circuit terminals

20

48

10

Rear view 4-poles

Door frame and panel-cut

Panel-cut

Operating panel center

Door frame panel-cut

8 - Ø 7

[mm]

5 - Ø 13,5

235

247

271

[mm]

42

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Drawout Type Breaker

Breaker typ AE4000-SSA (Drawout with vertical terminal)

Operating panel center

243

228

4P: 325 (3P: 195)

3P

Control terminals

4P

Neutral pole

311

51

35

Disconnected position

Test position

15

59 239

42,5

200

*

4 x Ø14

4P: 324 (3P: 194)

Front view

23

190

Operating panel center

190

* Mounting pitch

52

10

52

10

172 40

109

23 220

*

368

366

Side view

Operating panel center

170 170

43

170

48

452

Drawout position

11 11

197 242

Rear view 3-poles

Neutral pole

327

Rear view 4-poles

242

[mm]

Main circuit terminals

Connecting area

20

48

Drawout handle

Drawout handle, door frame and panel-cut

Panel-cut

Operating panel center

Door frame panel-cut

8 - Ø 7 max.173

200

Ø 22

5 - Ø 13,5

Breaker

235

247

271

[mm]

MITSUBISHI ELECTRIC

SUPER AE

43

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Fixed/Drawout Type Breaker

Breaker typ AE4000-SSC (Fixed with vertical terminal)

Operating panel center

Control terminals

232 317

Drawout handle insertion

268

144 88

42,5

195

Operating panel center

195

70

10

10

7

4 x Ø14

38

246

*

260

228

331

*

345

Front view

* Mounting pitch

Breaker typ AE4000-SSC (Drawout with vertical terminal)

Operating panel center

Control terminals

243 325

228

31

136

Side view

40

175

*

290

288

311

Panel

Inside of the panel

(thickness 1.6 to 3.2)

51

35

Disconnected position

Test position

Rear view

[mm]

42,5

195

70

10

10

Operating panel center

195

90

10

10

59 239

42,5

200

*

4 x Ø14

324

Drawout handle insertion port

Front view

Earth terminal

(on opposite side)

146

23

172

220

*

368

366

40

* Mounting pitch

Side view

48

452

Drawout position

25

Main circuit terminals

Fixed type Drawout type

Drawout handle, door frame and panel-cut

Drawout handle

* please check before mounting!

Panel-cut

Operating panel center

53

20

*

48 max.173

200

Ø 22

15

493

Rear view

Door frame panel-cut

8 - Ø 7

[mm]

5 - Ø 13

Breaker

Recommendation:

Fixed type:

Drawout type:

Main circuit terminals per pole: 3 × connection bus bar T × B: 10 × 150 mm

Main circuit terminals for pole L1, L3: 4 × connection bus bar T × B: 10 × 150 mm

Einschubtechnik: Main circuit terminals for pole L2 : 3 × connection bus bar T × B: 10 × 150 mm

235

Type

Fixed type

Drawout type

A

179

195

247

271

[mm]

44

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Breaker

Breaker types AE4000 to AE6300-SS with standard connection (vertical)

Operating panel center

28

373,5

228

Control terminal

3P: 458,5

4P: 588,5

3P

Neutral Pole

28

4P

Test position

Disconnect position

311

51

35

44

Neutral Pole

42,5

530

*

345,5

Befestigungsschrauben

2 x M12

Earth terminal schraube M8

6 x M12

395 3P: 480

4P: 610

4P

3P: 431,5

4P: 561,5

*

*

196

42,5

262

3P

Front view

Operating panel center

431,5

*

262

Mounting screws M12

* Mounting pitch

Erdungsanschlußschraube M8

(gegenüberliegende Seite)

Side view

15

123

23

172

220

*

40

368

366

48

400

Drawout position

53

25

103

25

X

Y

Type

AE5000-SS

AE6300-SS

Dimensions**

X Y

100

105

20

25

** please check before mounting!

5 -

Ø

13

Rear view

Main circuit terminals

[mm]

Drawout handle, door frame and panel-cut

Drawout handle Panel-cut

Operating panel center

Door frame panel-cut

8 -

Ø

7 max.173

200

Ø

22

Breaker

235

247

271

Breaker frame

[mm]

MITSUBISHI ELECTRIC

SUPER AE

45

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Dimensions – Accessory

External ZCT for load circuits

F

E

Type

C

D

E

A

B

H

J

F

G

230

60

104

200

323

250

47

72

92

370

108

104

200

460

400

47

72

92

500

108

104

200

600

550

48

72

92

A

[mm]

External ZCT for transformer ground wire

E

For M5

H

A

F

6

7,7

B

ZT15A – 40 A

7

30

100

A

B

ZT60A – 100 A

Type

A

B

C

D

G

H

E

F

15A

48

15

29

62

70

25

46

15

68

30

37

82

90

50

66

30

85

40

43

92

81

40

100

50

140

60

73

150

46

160

80

82

169

48

185

100

93

190

50

[mm]

Condenser trip device (COT)

Front view

90

Side view

Screw M4

UVT controller, external power supply (PS)

6.5

215 14.5

Terminal screw M3.5

Ø

104

45 45

4-R6

75

110,6

13,3

16

15,4

87

90

106

11

45

182.2

14.6

[mm] [mm]

46

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Operating Conditions, Technical Information

Insulation clearances at the supply side

When a short-circuit current is interrupted by the breaker,ionised gases flow out of the exhaust openings of the arc extinguishing chamber.This makes it necessary to observe the insulation clearance shown in the table on the right.

The clearances required for maintenance work have also been taken into consideration in the table.

Electrical equipment, appliances and screen

B B

C

Breaker type

Applicable voltage

A

Fixed type

Drawout type

C

B

D

A

B

C

D

AC 600 V

0

50

162

50

0

50

240

50

AC 660, 690 V

100

50

162

50

100

50

240

50

200

50

200

AC 690 V

200

50

200

[mm]

A clearance of 300 mm or more is necessary for inspection of the arc extinguishing chambers and main contacts.

The dimension D represents the wiring space required for the control terminal block.

Dimension B becomes larger when the breaker is fitted with the UVT controller, mechanical interlock, door interlock, etc. Further details available on request.

Normal service conditions

If all the following normal working conditions are satisfied (and not specified otherwise) the AE series air circuit breakers may be used:

Ambient air temperature

Range min.–5 °C to max.+40 °C (the average value however should not exceed +35 °C in any 24-hour period).

Altitude

2000 m (6600 feet) or less

Environmental conditions

The air must be free of dust and corrosive gases.Do not use and store in atmospheres with sulfide gas,ammonia gas etc.(H

2

S

0,01 ppm,SO

2

0,1 ppm,NH

3 not measurable).

The relative humidity should be of 85% or less at a max.of +40 °C.

Installation conditions

When installing AE series circuit breakers always follow the instructions provided in the catalogue and in the instruction manual.

Storage temperature

A range of max.+60 °C to min.-20 °C is recommended to store.

However,the average over 24 hours must not exceed +35 °C.

Replacement

Lifetime is approx.15 years.For detailed information please refer to the instruction manual.

Special service conditions

In case of special service conditions,modified circuit breakers are available (please specifiy when ordering).Service life may be shorter dependend on service conditions.

Special environmental conditions

Using breakers in a high temperature and/or humidity environment can result in deterioration of insulation durability and other electrical or mechanical features.Breakers used in such environments should be specially treated to a higher corrosion proof specification and against moistural fungus.Where corrosive gases are present in the environment it is recommended that breakers to a higher corrosion proof specification are ordered (further details on request).

Special ambient temperature

If the ambient temperature exceeds +40 °C,the continuous current rating must be reduced.The reduction value depends on the applicable standard (please refer to the following page).

Special altitude

When breakers are used at altitudes above 2,000 m the heat radiation rate is reduced,decreasing the operation voltage, uninterrupted current and breaking capacity.Reduced atmospheric pressure can also reduce insulation durability.

Further details available on request.

Installation in a separate cabinet

If the breaker is installed in a special cabinet,the following clearances have to be taken into consideration.

Rear plate

Upper plate

120 120

Door

Lower plate

Cabinet walls metal or plastic

Example:

The smallest possible cabinet dimensions for 3-pole Super AE breakers with up to 1600 A are:Hight=680 mm,Width=540 mm,

Depth=368 mm.

MITSUBISHI ELECTRIC

SUPER AE

47

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Internal resistance, reactance and power consumption (per pole)

Standard series "SS"

AE1000-SS

AE1250-SS

AE1600-SS

AE2000-SS

AE2500-SS

AE3200-SS

AE4000-SS

AE5000-SS

AE6300-SS

Breaker type

AE4000-SSA

AE4000-SSC

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Drawout

Drawout

Drawout

40

80

41

77

50

113

38

60

26

40

224

210

275

340

72

143

144

240

128

0.063

0.095

0.047

0.071

0.047

0.071

0.060

0.091

0.060

0.091

0.072

0.062

0.062

0.062

0.048

0.072

0.048

0.072

0.048

0.016

0.030

0.010

0.020

0.008

0.018

0.026

0.040

0.024

0.038

0.007

0.014

0.009

0.015

0.008

0.014

0.013

0.011

0.0085

Breaker type

AE1000-SH

AE1250-SH

AE1600-SH

AE2000-SH

AE2500-SH

AE3200-SH

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

Fixed

Drawout

High performance series "SH"

0.014

0.024

0.012

0.022

0.010

0.020

0.018

0.028

0.016

0.026

0.009

0.016

0.047

0.071

0.047

0.071

0.047

0.071

0.047

0.071

0.047

0.071

0.048

0.072

Deratings (A) by ambient temperature

Standard

DNV, BV ture= 45 °C)

60 °C

45 °C

50 °C

55 °C

60 °C

40 °C

45 °C

50 °C

55 °C

1000

1000

1000

1000

1000

1000

1000

1000

1000

1250

1250

1250

1250

1250

1250

1250

1200

1600

1600

1600

1550 (1600)

1200 (1250) 1500 (1600)

1600

1600

1550 (1600)

1500 (1600)

2000

2000

2000

2000

2000

2000

2000

2000

2000

2500

2500

2500

2450

2350

2500

2500

2450

2350

3200

3200

3200

3000

2900

3200

3200

3050

2900

4000

3650

3300

4000

3800

3650

3500

3300

4000

4000

4000

3900

3750

4000

4000

3900

3750

All data in the above table are based on test conditions, connecting methods and size of the mounting rails conforming to IEC947-2, EN60947-2, VDE0660 etc.

The figures in brackets ( ) in the table above indicate the reduced current values exclusive to AE-SH series.

4750

5000

5000

5000

4750

5000

5000

5000

5000

48

88

36

61

63

125

25

41

18

28

92

164

5200

6000

5750

5500

5200

6300

6000

5750

5500

Connection arrangements

The following connecting methods are available for the AE type air circuit breaker.

Mounting method

Connection Horizontal connection

Standard

Vertical connection

Optional

Front connection

Optional

Vertical terminal adapter

Accessory

Front terminal adapter

Optional

Fixed type

——— ———

(Standard)

(FIX-VTA) (FIX-FTA)

Drawout type

(Standard) (DR-VT) (DR-FT) (DR-VTA) (DR-FTA)

Remark

48

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SPECIFICATIONS

Specifications for marinal standards

SUPER AE

Rated current (A)

Rated insulation voltage (V) 50/60 Hz

Series Standard series "SS"

Breaker type AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SSC AE4000-SS AE5000-SS AE6300-SS

I

N max

1000 1250 1600 2000 2500 3200 4000 4000 5000 6300

Ui 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Rated operating voltage (V) 50/60 Hz

Number of poles

Ir

LR

DNV with instantaneous trip

Ue

AC690V

AC600V

AC500V

AC690V

690

3

500

In

1000

65

50

50

690

3

50

65

50

690

3

65

50

50

690

3

85

50

50

65

690

3

85

50

50

65

85

50

50

65

690

3

In

1250 800

In

1600 1000

In

In

2000

In

2500 1600

In

3200

3

3200

3200

In

(fürLR)

3800

3500

690

3

690

3

690

3

2000

In

4000 2500

In

5000 3150

In

6300

51,1

67

86.6

87

133

87

133

87

133

Ics

(kA, eff, sym.)

GL with instan-

AC600V

AC500V

AC690V

AC600V

AC500V

65

50

65

65

50

65

65

50

65

50

65

65

85

85

50

65

65

85

85

50

65

65

85

85

I

CU

= I

CS

BV

NK

LR

DNV with instan-

GL

BV

NK

87

133

211

330

211

330

65

85

113

147

199

143

196

85

65

50

65

85

106

143

196

106

143

196

187

143

196

106

143

196

105

143

85

65

50

65

85

106

143

196

106

143

196

187

143

196

106

143

196

105

143

85

65

50

65

85

106

143

196

106

143

196

187

143

196

106

143

196

105

143

65

50

50

65

106

151

106

151

143

112

147

106

151

105

50

65

50

65

106

151

106

151

143

112

147

106

151

105

65

50

50

65

106

151

106

151

143

112

147

106

151

105

AC690V

AC600V

AC500V

AC600V

AC500V

AC690V

AC600V

AC500V

AC690V

AC600V

AC500V

AC690V

AC600V

AC500V

AC690V

AC600V

AC500V

AC600V

AC500V

87

133

211

330

211

330

87

133

211

330

211

330

* Further current ratings on request.

SUPER AE

Rated current(A)

Rated insulation voltage (V) 50/60 Hz

Rated operating voltage (V) 50/60 Hz

Number of poles

Adjustment range

(A) Ir

Series High performance series "SH"

Breaker type AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH

I

N max

Ui

Ue

1000

1000

690

3

500

In

In

1000

1250

1000

690

In

3

1250 800

1600

1000

690

In

3

1600 1000

2000

1000

690

3

In

2000 1250

2500

1000

690

3

In

2500 1600

3200

1000

690

3

In

3200

I

Br. duty: O-t-CO-t-CO

CU

= I

CS

LR

NK

LR

NK with instan-

AC690V

AC600V

AC500V

AC600V

AC500V

AC690V

AC600V

AC500V

AC600V

AC500V

173

211

330

317

68

87

133

130

173

211

330

317

68

87

133

130

173

211

330

317

68

87

133

130

173

211

330

317

68

87

133

130

173

211

330

317

68

87

133

130

173

211

330

317

68

87

133

130

MITSUBISHI ELECTRIC

SUPER AE

49

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

SOFTWARE

Calculation and Selection Software MELSHORT2

Circuit diagram of the network to be calculated,with input field

MELSHORT2 – The New Calculation Software for

Low-Voltage Switchgear

MELSHORT2 is a software package that provides all the functions needed for planning and dimensioning switchgear systems.

Increasingly demanding technical specifications and accountability regulations are making switchgear configuration much more critical than it used to be.In the past,software for calculating and dimensioning switchgear was helpful – nowadays it’s absolutely essential.

Mitsubishi Electric’s MELSHORT2 is a complete software package that provides all the functions needed for successful switchgear system configuration and layout.It supports all modern international electrical engineering standards and shines with simple and reliable operation.

The program calculates the short-circuit levels and currents at all necessary points for all switchgear components,including the power supply transformer and circuit breakers,the emergency generators,the individual motor and capacitor group branch circuits and all the other power distribution circuits,down to the last circuit breaker.This makes it possible to select the ideal breaker for every task,for optimum performance and cost-efficiency.

MELSHORT2 has a comprehensive range of powerful,easy-to-use functions,including:

Selective shutdown

Backup protection

Coordination with the main power supply systems

Allowance for the start-up currents of electric motors

These functions make it possible to optimise the configuration of your switchgear equipment for the specific requirements of your applications.

The calculated results,the hardware model suggestions and the wiring diagram with all the relevant values can be processed and used as documentation for the switchgear installation.Another

welcome extra is the free Internet update service.

Display of the trip curves of a circuit breaker in the network

Specifications

Operating system

Disk type

Order information

MELSHORT2

MS Windows 95/98/NT4.0/2000

CD-ROM

Art. no. 129115

50

SUPER AE

MITSUBISHI ELECTRIC

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

INDEX

A

Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Auxiliary switch (AX), (HAX) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

C

Calculation Software MELSHORT2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Cell switch (CL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Characteristics setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Charging completion switch (TS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Charging handle (manual charging) . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Closing coil (CC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Counter (CNT). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Condensor trip device (COT). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13, 46

Connection arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

CT ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Current transformer (CT). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

D

Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36–46

Door frame (DF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Door interlock (DI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Drawout handle . . . . . . . . . . . . . . . . . . . . . . . . . 8, see also Dimensions

Drawout interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Dust cover (DC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

E

Earth leakage protection (ER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Electronic trip relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

External power supply (PS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19, 46

External current transformer (ZCT) . . . . . . . . . . . . . . . . . . . . . . . . 18, 46

F

Field test devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

G

Ground fault protection (GFR). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

I

Insulation clearance at the supply side . . . . . . . . . . . . . . . . . . . . . . . 47

Interlock device (CYL, CAL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Internal resistance per pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Interphase barrier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

L

Lifting hooks (HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Load current measurement (LM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

M

Manual charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Marine approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5, 48

Mechanical interlock (MI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Mis-insertion preventer (MIP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Motor charging (MD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

N

Neutral current transformer (NCT). . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Neutral pole overcurrent protection (NP) . . . . . . . . . . . . . . . . . . . . . 28

O

Operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Operating characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32–33

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 7, 31

Overcurrent OCR-Alarm (AL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

P

Position lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Power consumption per pole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Pre-alarm (PAL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Program overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Push button cover (BC-L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

R

Relay adjusting notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Reactance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Resistance per pole. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

S

Safety shutters (SST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Shorting b-contact (SBC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Shunt trip device (SHT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4, 5, 20, 49

Standard accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Switch-disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

T

Temperature alarm (TAL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Terminal cover (TTC). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Terminal layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35

Test jumper (TJ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Trip relay type M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24, 25

Trip relay type S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22, 23

U

Undervoltage trip device (UVT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

UVT controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11, 46

V

Vertical terminal adapter (VTA) . . . . . . . . . . 15, see also Dimensions

W

Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34, 35

MITSUBISHI ELECTRIC

SUPER AE

51

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

HEADQUARTERS

MITSUBISHI ELECTRIC

EUROPE B.V.

German Branch

Gothaer Straße 8

EUROPE

D-40880 Ratingen

Phone: +49 (0)2102 486-0

Fax: +49 (0)2102 486-1120 e mail: [email protected]

FRANCE

MITSUBISHI ELECTRIC

EUROPE B.V.

25, Boulevard des Bouvets

F-92741 Nanterre Cedex

Phone: +33 1 55 68 55 68

Fax: +33 1 55 68 56 85 e mail: [email protected]

MITSUBISHI ELECTRIC

IRELAND

EUROPE B.V.

Irish Branch

Westgate Business Park, Ballymount

IRL-Dublin 24

Phone: +353 (0) 1 / 419 88 00

Fax: +353 (0) 1 / 419 88 90 e mail: [email protected]

MITSUBISHI ELECTRIC

ITALY

EUROPE B.V.

Italian Branch

C.D. Colleoni - P. Perseo Ing. 2

Via Paracelso 12

I-20041 Agrate Brianza (MI)

Phone: +39 (0) 39 / 60 53 1

Fax: +39 (0) 39 / 60 53 312 e mail: [email protected]

MITSUBISHI ELECTRIC

EUROPE B.V.

SPAIN

Carretera de Rubí 76-80

E-08190 Sant Cugat del Vallés

(Barcelona)

Phone: +34 9 3 / 565 3131

Fax: +34 9 3 / 589 2948

MITSUBISHI ELECTRIC

EUROPE B.V.

UK Branch

Travellers Lane

GB-Hatfield Herts. AL10 8 XB

Phone: +44 (0) 1707 / 27 61 00

Fax: +44 (0) 1707 / 27 86 95

UK

e mail: [email protected]

MITSUBISHI ELECTRIC

JAPAN

CORPORATION

8-12,1 chome, HARUMI CHUO-KU,

Office Tower „Z“ 14 F

Tokyo 104-6212

Phone: +81 3 6221 6060

Fax: +81 3 6221 6075

MITSUBISHI ELECTRIC

AUTOMATION

500 Corporate Woods Parkway

Vernon Hills, Illinois 60061

Phone: +1 (0) 847 / 478 21 00

Fax: +1 (0) 847 / 478 22 83

USA

EUROPEAN REPRESENTATIVES

Emac S.A.

Industrialaan 1

B-1702 Groot-Bijgaarden

Phone: +32 (0) 2 / 481 02 11

Fax: +32 (0) 2 / 481 03 01 e mail: [email protected]

INEA CR d.o.o.

Drvinje 63

BELGIUM

CROATIA

HR-10000 Zagreb

Phone: +385 (0) 1 / 36 67 140

Fax: +385 (0) 1 / 36 67 140 e mail: —

AutoCont .

Control Systems s.r.o

Nemocnicni 12

CZ-702 00 Ostrava 2

CZECH REPUBLIC

Phone: +420 59 / 6152 111

Fax: +420 59 / 6152 562 e mail: [email protected]

louis poulsen industri & automation

Geminivej 32

DK-2670 Greve

Phone: +45 (0) 43 / 95 95 95

DENMARK

Fax: +45 (0) 43 / 95 95 91 e mail: [email protected]

UTU POWEL OY

COMPONENTS

Palopellonkatu 7

FI-04251 Kerava

Phone: +358 09 / 274 641 1

Fax: +358 09 / 274 641 41

FINLAND

e mail: —

ELECTRAPOTHIKI ATHENS S.A. GREECE

Acharnon Av. 426

GR-11143 Athens

Phone: +30 210 2014454

Fax: +30 210 2022420 e mail: [email protected]

Meltrade Automatika Kft. HUNGARY

55, Harmat St.

HU-1105 Budapest

Phone: +36 (0)1 / 2605 602

Fax: +36 (0)1 / 2605 602 e mail: [email protected]

RIFAS UAB

Tinklu 29A

LT-5300 Panevezys

Phone: +370 (45) 582-728

Fax: +370 (45) 582-729 e mail: [email protected]

LITHUANIA

EUROPEAN REPRESENTATIVES

INTEHSIS SRL

Cuza-Voda 36/1-81

MD-2061 Chisinau

Phone: +373 (0) 2 / 562 263

MOLDOVA

Fax: +373 (0) 2 / 562 263 e mail: [email protected]

NETHERLANDS

Imtech

Marine & Industry

Sluisjesdijk 155

NL-3008 AB-Rotterdam

Phone: +31 (0) 10 / 487 19 11

Fax: +31 (0) 10 / 487 17 02 e mail: [email protected]

SCANELEC AS

NORWAY

Leirvikasen 43B

N-5020 Bergen

Phone: +47 55 50 60 00

Fax: +47 55 50 60 01 e mail: [email protected]

MPL Technology SP. z.o.o

POLAND

ul. Sliczna 36

PL-31-444 Kraków

Phone: +48 (0) 12 / 632 28 85

Fax: +48 (0) 12 / 632 47 82 e mail: [email protected]

Sirius Trading & Services srl ROMANIA

Str. Biharia Nr. 67-77

RO-013981 Bucuresti 1

Phone: +40 (0) 21 / 201 1146

Fax: +40 (0) 21 / 201 1148 e mail: [email protected]

INEA d.o.o.

Stegne 11

SI-1000 Ljubljana

Phone: +386 (0) 1- 513 8100

Fax: +386 (0) 1- 513 8170 e mail: [email protected]

Euro Energy

SLOVENIA

Components AB

Järnvägsgatan 36

S-434 24 Kungsbacka

Phone: +46 (0) 300 / 69 00 40

Fax: +46 (0) 300 / 1 64 75 e mail: [email protected]

SWEDEN

TRIELEC AG

Mühlentalstr. 136

SWITZERLAND

Phone: +41 (0) 52 / 625 84 25

Fax: +41 (0) 52 / 625 88 25 e mail: [email protected]

GTS

Darülaceze Cad. No. 43 KAT. 2

TURKEY

TR-80270 Okmeydani-Istanbul

Phone: +90 (0) 212 / 320 1640

Fax: +90 (0) 212 / 320 1649 e mail: [email protected]

MIDDLE EAST REPRESENTATIVE

GINO INDUSTRIES LTD

26, Ophir street

IL-32235 Haifa

Phone: +972 (0) 4 / 867 06 56

Fax: +972 (0) 4 / 867 42 27 e mail: [email protected]

ISRAEL

EURASIAN REPRESENTATIVE

Avtomatika Sever Ltd

Lva Tolstogo Str. 7, Off. 311

RU-197376 St Petersburg

Phone: +7 812 1183 238

Fax: +7 812 1183 239 e mail: [email protected]

Consys

Promyshlennaya St. 42

RU-198099 St Petersburg

Phone: +7 812 325 36 53

Fax: +7 812 325 36 53 e mail: [email protected]

RUSSIA

RUSSIA

Electrotechnical Systems

Siberia

RUSSIA

Partizanskaya St. 27, Office 306

RU-121355 Moscow

Phone: +7 095/ 416-4321

Fax: +7 095/ 416-4321 e mail: [email protected]

Electrotechnical Systems

Siberia

Shetinkina St. 33, Office 116

RU-630088 Novosibirsk

Phone: +7 3832 / 22-03-05

RUSSIA

Fax: +7 3832 / 22-03-05 e mail: [email protected]

Elektrostyle ul. Garschina 11

RUSSIA

RU-140070 Moscowskaja Oblast

Phone: +7 095/ 261 - 3808

Fax: +7 095/ 261 - 3808 e mail: [email protected]

ICOS

RUSSIA

Ryazanskij Prospekt, 8a, Office 100

RU-109428 Moscow

Phone: +7 095 / 232 - 0207

Fax: +7 095 / 232 - 0327 e mail: [email protected]

SSMP Rosgidromontazh Ltd. RUSSIA

23, Lesoparkovaya St.

RU-344041 Rostov On Don

Phone: +7 8632/ 36 00 22

Fax: +7 8632/ 36 00 26 e mail: —

AFRICAN REPRESENTATIVE

CBI Ltd

Private Bag 2016

SOUTH AFRICA

ZA-1600 Isando

Phone: +27 (0) 11 / 928 2000

Fax: +27 (0) 11 / 392 2354 e mail: [email protected]

Specificationssubjecttochangewithoutnotice.

Art.no.62093-D,Printed in Germany 01.04

MITSUBISHI ELECTRIC

INDUSTRIAL AUTOMATION

Gothaer Strasse 8 Phone: +49 2102 486-0 Fax: +49 2102 486-7170 www.mitsubishi-automation.de

D-40880 Ratingen Hotline: +49 1805 000-7650 [email protected] www.mitsubishi-automation.com

AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : [email protected]

advertisement