Mitsubishi Electric Low-Voltage Air Circuit Breakers series Type AE-SW Instruction Manual


Add to my manuals
43 Pages

advertisement

Mitsubishi Electric Low-Voltage Air Circuit Breakers series Type AE-SW Instruction Manual | Manualzz

MITSUBISHI Low-Voltage Air Circuit Breakers series

World Super AE

三菱低压空气断路器 World Super AE

三菱低圧気中遮断器 World Super AE

MODEL

AE-SW

INSTRUCTION MANUAL

使用说明书

取扱説明書

Types covered in this manual

本手册适用于以下型号产品

対象機種

AE630-SW AE1000-SW AE1250-SW AE1600-SW

AE2000-SWA

AE2000-SW AE2500-SW AE3200-SW

AE4000-SWA

AE4000-SW AE5000-SW AE6300-SW

IMPORTANT NOTE: Before using these Series AE breakers, please read these instructions carefully, and make sure that all actual users also read them.

重要注释: 在使用 AE 断路器系列以前,请务必仔细阅读本说明书,

并确保所有用户也阅读本说明。

ご使用の前に必ずこの取扱説明書をお読みください。

この説明書は、最終ユーザまでお届けください。

22B

Safety precautions

Before using this device, make sure to read this instruction manual thoroughly.

Important safety information is included in this manual. Be sure to follow the instructions.

Please make sure that the end user receives this instruction manual.

This instruction manual is prepared for an electrical expert.

Symbols have the following meaning.

Incorrect handling of the product will result in a hazardous situation, such as death or serious injury.

Incorrect handling of the product may result in a hazardous situation according to circumstances.

Warning for possible electrical shock under certain conditions.

Warning for possible outbreak of a fire under certain conditions.

This means prohibition. Never ignore this instruction.

Be sure to follow these instructions without fail.

Do not use the product under the conditions with over-rated current. Otherwise, ground-fault or short circuit fault could occur due to dielectric breakdown, or explosion could occur due to a short circuit protection failure.

Do not touch terminal area. There is a risk of electrical shock.

The electrical work shall be performed by qualified personnel (electrical expert).

Inspection and maintenance should be performed by qualified personnel (electrical expert). Before performing wiring works, turn off the upstream circuit breaker. Failure to do so may expose you to electrical shock.

Tighten the terminal screw with the torque specified in the instruction manual. Failure to do so may cause a fire.

Do not install or store in an abnormal environment with high temperature, high humidity, dust, corrosive gas, vibrations, or shocks, etc. To do so may cause a fire, malfunction of the circuit breaker or make it inoperative.

Protect the circuit breaker so that foreign particles, such as dust, concrete powder and iron powder, and rain water will not enter the circuit breaker. Failure to do so may cause malfunction or fire.

When the circuit breaker trips automatically, remove the cause before turning on the handle. Failure to do so may cause an electric shock or a fire.

Retighten the terminals periodically. Failure to do so may cause a fire.

Use the product in 50/60 Hz. Failure to do so may cause malfunction, inoperativeness or fire.

Do not use in strong magnetic field.

When using a transceiver, keep it off at least 1 meter from the ACB.

Do not disassemble.

Malfunction and operation fallures can be caused.

Dispose of the product as industrial waste.

E-2

Table of contents

Safety precautions ………………………………… 2

External view ………………………………………… 4

Internal structure …………………………………… 5

Outline dimensions and product weight ………… 5

Unpacking …………………………………………… 6

Storage ……………………………………………… 6

Transportation ……………………………………… 7

Installation …………………………………………… 8

Installation of the drawout handle ………………… 9

Installation of the inter-phase barrier (BA) ……… 9

Connection ……………………………………… 10

Insert operation ………………………………… 12

Drawout operation ……………………………… 14

Charging operation ……………………………… 16

Open/close operation …………………………… 17

Door interlock (DI) ……………………………… 19

Cylinder lock (CYL) and Castell lock (CAL) …… 19

OCR alarm (AL) [MRE: manual reset type] …… 19

Shutter lock (SST-LOCK) ……………………… 20

Safety shutter nameplate ……………………… 20

Functions of electronic trip relay (ETR) parts … 21

Characteristics setting for the WS type ……… 23

Characteristics setting for the WM type ……… 24

Characteristics setting for the WB type ……… 25

Characteristics setting for the WF type ……… 26

Characteristics setting for the optional setting modules … 28

Setting procedure for the electronic trip characteristics … 30

Wiring diagram …………………………………… 32

Technical notes (Arc space, Reverse connection) … 34

Technical notes (Performance of withstand voltage) … 34

Technical notes (Operation environment) ……… 35

Warranty ………………………………………… 35

Inspection and maintenance …………………… 36

Service network ………………………………… 42

E-3

External view

< Fixed type >

Padlock hook allows a padlock to be attached to the

OFF button

Electronic trip relay

(ETR)

Control circuit terminal block

Arc-extinguishing chamber

Lifting hook (HP)

OFF button

ON button

Charging handle

Charging indicator

< Drawout type >

Lifting holes

ON/OFF indicator

Rated nameplate

Manual reset button (option)

Note: The fixed type includes lifting hook (HP).

Fig. 4-1

Control circuit terminal block

Cradle

Extension rail

Lock plate

Drawout position indicator

Aperture for the drawout handle

Drawout state

Drawout handle

Note: The drawout type includes a drawout handle.

Fig. 4-2

<Drawout type>

Back mounting hole (P.8)

Fixing bolts (P.13)

Fig. 4-3

Fig. 4-1 shows AE1600-SW 3-pole fixed type, Fig. 4-2 shows AE1600-SW 3-pole drawout type, and Fig. 4-3 shows AE6300-

SW 3-pole drawout type.

E-4

Internal structure

Fig. 5-1

(Breaker OFF and charging)

① Control circuit terminal block

② Control circuit connector

③ Auxiliary switch

④ Shunt trip device, closing coil, undervoltage trip device

⑤ Electronic trip relay (ETR)

⑥ Cover

⑦ Open/close mechanism

⑧ Drawout mechanism

⑨ Intermediate base

⑩ Arc-extinguishing chamber

⑪ Contact on the movable side

⑫ Contact on the fixed side

⑬ Conductor on the breaker

⑭ Conductor on the cradle

⑮ Main circuit junction

⑯ Base

⑰ Contact spring

⑱ Flexible conductor

⑲ Conductor on the breaker

⑳ Conductor on the cradle

Power supply CT

Current sensor coil

Cradle

Cradle nameplate

Outline dimensions and product weight

Table 5-1

Model

Outline dimensions Note 1) a × b × c × d

(mm)

Product weight

Note 2)

(kg)

Fixed type

Drawout type

Fixed type

Drawout type

Cradle only

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

AE630-SW AE1000-SW AE1250-SW AE1600-SW

340 × 410 × 290 × 40

425 × 410 × 290 × 40

35

42

56

70

300 × 430 × 375 × 61

385 × 430 × 375 × 61

35

42

56

70

24

28

43

35

43

56

70

AE2000-SWA

340 × 410 × 290 × 108

425 × 410 × 290 × 108

300 × 430 × 375 × 104

385 × 430 × 375 × 104

44

54

62

75

27

32

Note 1) d dimensions: when the product is connected horizontally. For AE2000-SWA, when it is connected vertically.

Note 2) Weight (reference value) when an electronic trip relay is attached. It does not include any other accessories.

Table 5-2

Model

Outline dimensions Note 1) a × b × c × d

Product weight

Note 2)

(mm)

(kg)

Fixed type

Drawout type

Fixed type

Drawout type

Cradle only

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

AE2000-SW AE2500-SW AE3200-SW

475 × 410 × 290 × 40

51

64

81

101

605 × 410 × 290 × 40

435 × 430 × 375 × 61

565 × 430 × 375 × 61

52

64

81

101

33

40

54

67

85

106

34

42

AE4000-SWA

475 × 410 × 290 × 117

605 × 410 × 290 × 117

439 × 430 × 375 × 109

569 × 430 × 375 × 109

73

92

101

127

46

58

Note 1) d dimensions: when the product is connected horizontally. For AE4000-SWA, when it is connected vertically.

Note 2) Weight (reference value) when an electronic trip relay is attached. It does not include any other accessories.

Table 5-3

Model

Outline dimensions Note 1) a × b × c × d

(mm)

AE4000-SW AE5000-SW

874 × 414 × 290 × 136

1004(1134) × 414 × 290 × 136

889 × 480 × 375 × 123

1019(1149) × 480 × 375 × 123

141

159(179)

194

223(247)

98

113(127)

AE6300-SW

Product weight

Note 2)

(kg)

Fixed type

Drawout type

Fixed type

Drawout type

Cradle only

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

3 poles

4 poles

148

166(188)

208

238(269)

107

121(138)

Note 1) d dimensions: it is connected vertically.

Note 2) Weight (reference value) when an electronic trip relay is attached. It does not include any other accessories.

Fixed type

Operating panel center a 7

Fig. 5-2

Drawout type

Operating panel center c d a(Max.)

17 c d

Aperture for the drawout handle

Fig. 5-3

Drawout handle

200

Fig. 5-4

E-5

Unpacking

① Make sure that the packing case is free from any abnormality such as being broken and/or wet.

② Check the indication on the package and the rated nameplate of the breaker, and confirm that it matches your order.

Serial number is indicated on the rated nameplate and on the cradle nameplate (Fig. 5-1 ).

Fixed type Drawout type

Accessories nameplate

*This is not included.

Fig. 6-1

Baseplate for fixing

Fig. 6-2

Installation screw

Fig. 6-3

Installation bracket

CT rated nameplate

Rated nameplate

Fig. 6-4

Storage

* If this product is used after being stored for more than 6 years, maitenance is required including lubrication etc. before operation. Please contact our representative office.

Storage temperature

-20 °C to +60 °C

Avoid humidity Avoid direct sunlight

+60°C

-20°C

Store within this range.

Average daily temperature

+35 °C or less

Fig. 6-5

Relative humidity 85% or less, without condensation

Fig. 6-6

Avoid direct sunlight during usage. Failure to do so could result in temperature rise and malfunction. It could also lead to discoloration of nameplates and molded cases.

Fig. 6-7

Caution on dust

Completely seal the product with the packaging case or a plastic bag.

Avoid corrosive gases

H

2

S 0.01 ppm or less

SO

2

0.05 ppm or less

NH

3

0.25 ppm or less

Fig. 6-9

Store in the OFF and DISCHARGED state.

No direct storage

E-6

Store the drawout type in the CONNECT position.

Fig. 6-8

OFF

Fig. 6-10

Transportation

Do not drop the product during transportation and storage.

Fig. 7-1

Do not roll the product.

Fig. 7-2

Wire length 1 m or more

Lifting hook hole

R12.5

Wire length 1 m or more

Lifting hook (HP)

25

CONNECT position

Fixed type

Fig. 7-3

Take caution not to scratch the control circuit terminal block when lifting the product with the lifting hook (HP). Securely attach the lifting hook (HP) so that they will not come off during transportation.

Locking plate

Drawout type

Fig. 7-4

When transporting the product with its cradle attached, check that the lock plate is protruded in the CONNECT position. Do not use anything else but the lifting holes.

Fig. 7-5

Since the conductors side is heavy, be careful not to give an impact to the product and the conductors when landing the product.

1 m or longer

Fig. 7-6

When transporting a drawout type breaker (AE4000-SW ~ AE6300-SW), be sure to use 4 wires with a length of 1 m or longer, or a lifter.

E-7

Installation

< Drawout type >

Installation surface flatness

1 mm or less

AE630-SW ~ AE3200-SW, AE2000-SWA, AE4000-SWA

Insert M12 bolts from above, and attach the cradle.

Bolt l Appropriate tightening torque

Max.

14 mm

Bolt size Tightening torque (N∙m) Nut

M12 45±5

1 mm or less

M12

M8

Earth terminal

Fig. 8-2 Fig. 8-1

For AE4000-SW ~ AE6300-SW 3-pole and 4-pole (HN) products, insert four M12 bolts from the bottom and two from the back and attach the cradle as shown in Fig. 8-3. For the 4-pole (FN)* products, insert six M12 bolts from the bottom and two from the back and attach the cradle as shown in Fig. 8-4.

AE4000-SW ~ AE6300-SW 3-pole & 4-pole (HN)

Cradle

Installation bracket

(Panel side:non-magnetic steel)

AE4000-SW ~ AE6300-SW 4-pole (FN)*

Installation bracket (Panel side:non-magnetic steel)

2×M12

Weld nut

(included as standard)

2×M12

Weld nut

(included as standard)

Max.

25 mm

4×M12

Max.

25 mm

6×M12

Bolt Bolt

Fig. 8-3 Fig. 8-4

*4-pole product (FN): 4-pole product of which neutral poles have the same current capacity as the other poles.

Perform drawout operation (connect position to drawout position) as instructed. (Refer to P.14 and 15)

Lifting using a lifter or with lifting hook(HP)

CAUTION CAUTION

Lift

Fig. 8-5

< Fixed type >

l Appropriate tightening torque

Bolt size

M12

Tightening torque (N∙m)

45±5

M12

When the main body is drawn out, the center of gravity shifts to the front. If the cradle is not secured, take measures against overturning and dropping.

Fig. 8-6

Supporter

On AE4000-SWA,AE4000-SW ~ AE6300-

SW, the center of gravity of the cradle is located at the terminal position.

When the main body is removed from the cradle, the cradle may turn over backward. Take measures against overturning.

Fig. 8-7

Precautions for mounting l Mounting direction

M8 Earth terminal

(standard supply)

E-8

* Insertion direction of bolts is arbitrary.

Fig. 8-8 l Earth terminal

Unless there are any special circumstances, connect the earth terminal to the ground.

Fig. 8-9

Installation of the drawout handle

The drawout handle can be installed either onto the right or left of the cradle as required.

A drawout handle, installation bracket, installation screws, and hexagon nuts are provided with the breaker.

 Installation onto the left side

Installation bracket

 Installation onto the right side

Drawout handle

Note) When a mechanical interlock (MI) or door interlock (DI) is attached, the drawout handle cannot be installed onto the right side of the cradle.

Mechanical interlock (MI) or Door interlock (DI)

Cradle

Fig. 9-1

Hexagon nut M5 (supplied)

Installation screw (+) M5 × 12 (supplied)

Tightenning torque:3.2 ± 0.4 N∙m

Fig. 9-2

Fig. 9-3

Installation of the inter-phase barrier (BA)

Insert in the slot on the breaker. (Refer to Fig. 9-4 and Fig. 9-5)

< Fixed type > < Drawout type >

Fig. 9-4 Fig. 9-5

E-9

Connection

Use M12 screws (made of copper), spring washers, and small washers to connect to the conductors.

Clean the contact surface and securely tighten the screws with a appropriate torque.

The connecting area on main circuit terminal of the breaker is different depending on the shape of the breaker’s terminal.

Refer to the outline dimensions in the catalog.

 Main circuit

Horizontal connection CAUTION

25mm

CAUTION

Small washer

M12

45±5N·m

Small washer

Spring washer

Small washer

Conductor

Fig. 10-1

Use small washers to connect that the washers do not overlap with each other.

Fig. 10-2

CAUTION

Conductor

Small washer

Spring washer

Breaker terminal

(silver plated)

Fig. 10-3

Appropriate tightening torque for conductor connection

Bolt size Tightening torque (N·m)

M12 45±5

Keep an insulation distance between the conductors to be connected according to the standard of the panel.

Breaker

Bolt

Please tighten screws after checking breaker’s terminal and conductor certainly contact with each other.

Make sure the conductor doesn’t apply the force to breaker’s terminal in any direction.

Fig. 10-4

E-10

Since fault current flowing through the conductors causes large electromagnetic forces, the conductors should be secured firmly, using the values in the below table as a reference. Max. distance between fixing support and breaker bus bar should be less than 200mm.

Breaker

Conductor

200 mm or less

Supporting fixture

Supporting between live parts of different poles and between the power supply and load terminals.

Fig. 11-1

Table 11-1 Electromagnetic force per 1 m of conductor (in the case of three phase short circuit)

Type

AE630-SW ~

AE1600-SW

AE2000-SWA AE2000-SW ~

AE3200-SW

Drawout type

AE4000-SWA

Fixed type

(N/m)

AE4000-SW ~

AE6300-SW

3 poles 4 poles 3 poles 4 poles 3 poles 4 poles

Conductor distance (mm)

Prospective fault current kA (pf)

30(0.2)

42(0.2)

50(0.2)

65(0.2)

75(0.2)

85(0.2)

100(0.2)

130(0.2)

85

-

-

-

-

7700

15100

21400

36100

115

-

-

-

-

5700

11200

15800

26700

105

-

-

-

-

6300

12200

17300

29300

130

5100

9900

14000

23600

31500

40400

-

-

190

3500

6800

9600

16200

21500

27600

-

-

170

3900

7600

10700

18100

24100

30900

-

-

152

4300

8500

12000

20200

26900

34500

-

-

145

4500

8900

12600

21200

28200

36200

-

-

262

2500

5000

7000

11800

15800

20000

27800

47000

When selecting conductors to be connected to the breakers, ensure that they have a sufficient current capacity. Refer to the right table.

Table 11-2 Conductor size

(IEC 60947-1, Ambient Temp. 40 °C, Open air)

Rated current

MAX (A)

630

1000

1250

1600

2000

2500

3200* 1

Conductor to be connected (copper)

Quantity Conductor size (mm) Arrangement

2

2

40 x 5

60 x 5

2

2

3

4

3

2

80 x 5

100 x 5

100 x 5

100 x 5

100 x 10

150 x 10

4000

AE4000-SWA drawout type

4000

AE4000-SWA fixed type

4

3

150 x 10

150 x 10

Vertical

(Note) Table 11-2 shows the conductor size that is indicated in IEC 60947-1 with an ambient temperature of 40 °C and in an open air environment.

Fig. 11-2 shows the testing conditions.

3m

Breaker

2m

4000

(AE4000-SW)

4 100 x 10

5000

6300

4

4

150 x 10

200 x 10 Fig. 11-2

*1 For 3200 A, connect a conductor which is sized for 3150 A.

For 3200 A or higher, there is no specification by IEC (IEC 60947-1). (Specification by the manufacturer)

 Control circuit terminal block

Tighteing with excessive torque above the specification may cause damages of terminals and screws.

Be sure to tighten with the specified torque.

After removing screws, make sure not to tighten the screws diagonally.

Be careful not to apply excessive tension to the wirings.

Use a cross-head screwdriver with a diameter that matches the cross-shaped groove.

M3.5 ................................. No. 2

Crossover wiring

M3.5 x 10

Torque: 1.0 ± 0.2N·m

Control circuit terminal block

Applicable crimp-type terminals

A A

A = 7.2 mm or less

Applicable crimp-type terminals for M3.5 screws with an outer diameter of 7.2 mm or less.

(Wire size 1.25 mm 2 ~ 2.0 mm 2 )

Fig. 11-3 Fig. 11-4 Fig. 11-5

E-11

Insert operation

 DRAWOUT position  CONNECT position

① Pull the lock lever toward you (step 1), unhook the lock lever from the cradle, and then pull out the extension rail (step 2).

Step 1

② With the extension rail pulled out to the furthest position, lift the breaker once by using a lifter or dedicated lifting hook (HP), and then lower the breaker down onto the drawout rail. Place the dent of the breaker onto the notch of the drawout rail. (Fig. 12-5)

Using a lifter or with lifting hook (HP)

Step 2

Extension rail

Lock lever

Fig. 12-1

③ With the extension rail pulled out to the furthest position, slowly push the breaker in until you hear the clicking sound when it does not move.

When inserting the breaker from the DRAWOUT position to the

DISCONNECT position, be sure to do so evenly on the right and left sides. (Do not forcefully push the right or left terminal area only.)

If it is uneven (if the breaker is inserted diagonally), it does not go in smoothly.

For a breaker installed in an elevated location, perform this operation with two people.

CAUTION

Fig. 12-2

Breaker dent

Fig. 12-3

Click!

④ Insert the drawout handle while pressing the OFF button. Check that the drawout position indicator indicates DISCONNECT (Fig. 12-7).

OFF button

Drop

If the breaker is placed on the rail while the cradle is not secured, the center of gravity shifts forward. Be sure to take preventative measures against the unit tipping over.

Fig. 12-4

Rail notch

Fig. 12-5

CAUTION

When placing the breaker in the panel, take care not to hurt your fingers or hands with the in-panel structure.

Pinched finger

DISCONNECT position

Press

Insert

Fig. 12-6

Aperture for the drawout handle

Drawout handle

Fig. 12-7

(Prohibition)

Do not insert the drawout handle without pressing the

OFF button. When inserting or pulling out the drawout handle or during operation, be sure to place the drawout handle straight into the Aperture for the drawout handle. Failure to do so could result in breakage.

E-12

⑤ Press in the lock plate until it clicks onto the latch, and unlock.

(Caution)

(a) If unlocking the lock plate feels difficult, slightly rotate the drawout handles to the right or left.

(b) Be sure to push in the lock plate to the unlock position.

The position indicator may not operate correctly.

Lock plate

Lock position

Push

⑥ Unlock, release your hands from the lock plate, and rotate the drawout handle clockwise.

(Caution)

Do not draw out during the insert operation. The drawout position may not be indicated correctly. If that is the case, pull out the breaker to the DISCONNECT position once, and then retry the insert operation.

Cover Latch

Unlock position

Fig. 13-1

⑦ When the breaker is inserted to the testing position, the drawout position indicator shows TEST position, and the lock plate is protruded automatically, locking the drawout handle rotation.

(Caution)

Do not rotate the drawout handle while the lock plate is protruded.

TEST position

Fig. 13-3

⑨ For AE4000-SW ~ AE6300-SW, always tighten the fixing bolts on both sides of the cradle as shown in Table

13-5, and securely fix the breaker.

Fixing bolt

Fig. 13-2

⑧ Insert the lock plate, and rotate the drawout handle clockwise. When the breaker is inserted to the CONNECT position, the lock plate is protruded automatically, completing the insert operation. At this time, the drawout position indicator shows the CONNECT position. For all breaker types, the operation load becomes heavy during operation from the TEST position to the CONNECT position or at the main circuit junction insertion position, but this is not a fault.

CAUTION

Be sure to insert until the lock plate is protruded. If it is not protruded, the connection may be incomplete.

(Caution)

(a) After completing the insertion, do not rotate the drawout handle.

(b) The drawout position indicator shows the position

(CONNECT, TEST) when the lock plate is protruded.

When the lock plate is unlocked, it shows a reference position.

(c) The breaker cannot be closed with the drawout handle inserted.

Checkpoint 1

Lock plate is protruded

Automatic

Fig. 13-5

Checkpoint 2

In CONNECT position

Fig. 13-4

E-13

Drawout operation

 CONNECT position  DRAWOUT position

① For AE4000-SW ~ AE6300-SW, unfasten the two fixing bolts on both sides of the cradle, and unlock. If drawout is performed without unlocking, the cradle and the drawout mechanism may be damaged.

(Fig. 14-1)

Unlocked state

Fig. 14-1

OFF button

② Insert the drawout handle while pushing the OFF button.

CONNECT position

Push

Fig. 14-2

(Prohibition)

Do not insert the drawout handle without pressing the OFF button. Failure to do so could result in breakage.

③ Push in the lock plate until it clicks onto the latch, and unlock.

(Caution)

(a) If unlocking the lock plate feels difficult, slightly rotate the drawout handles to the right or left.

(b) Be sure to press in the lock plate to the unlock position. The position indicator may not operate correctly.

Push

Fig. 14-3

Drawout handle

Lock plate

Lock position

Cover

Fig. 14-4

Latch

Unlock position

④ Unlock, release your hands from the lock plate, and rotate the drawout handle counterclockwise.

(Caution)

Do not insert during the drawout operation. The drawout position may not be indicated correctly.

To perform the insert operation, pull out the breaker to the DISCONNECT position once, and then retry the insert operation. When transitioning from the

CONNECT position to the TEST position, and when the breaker terminals are detached from the main circuit junction, the operation may feel light, but this is not a fault.

E-14

Fig. 14-5

⑤ When the breaker is drawn out to the TEST position, the drawout position indicator shows TEST position, and the lock plate is protruded automatically, locking the drawout handle rotation.

(Caution)

Do not rotate the drawout handle while the lock plate is protruded.

Automatic

TEST position

Fig. 15-1

⑥ Next, insert the locking plate and rotate the handle counterclockwise until the drawout position indicator shows DISCONNECT and the breaker does not move.

Drawout operation is now completed.

The breaker can be pulled out using both hands.

(Caution)

(a) The lock plate sometimes gets protruded before reaching the DISCONNECT position. If that is the case, push in the lock plate to stay in the unlocked state, and continue rotating the handle.

(b) If unlocking the lock plate feels difficult, slightly rotate the drawout handles to the right and left.

(c) At the DISCONNECT position the drawout handle may spin around without the lock plate being protruded.

⑦ To detach the breaker from the cradle, pull the lock lever toward you, unhook, pull out the extension rail evenly on the right and left side, and then pull out the breaker.

CAUTION CAUTION

Pinched finger

Drop

By pulling the breaker, the center of gravity shifts forward.

Be sure to take preventative measures against a fall or drop when the cradle is not secured.

Fig. 15-3

When pulling out the breaker, take care not to hurt your fingers or hands with the in-panel structure.

DISCONNECT position

Fig. 15-2

Fig. 15-4

Lock lever

E-15

⑧ When pulling out the breaker, be sure to do so evenly on the right and left sides.

(Do not forcefully pull the right or left area only.)

If it is uneven (if the breaker is coming out diagonally), it does not come out smoothly.

For a breaker installed in an elevated location, perform this operation with two people.

(Caution)

AE4000-SWA and AE4000-SW ~ AE6300-SW have their cradle center of gravity on their terminal areas.

Be sure to take preventative measures against a fall or drop by installing a support for the cradle (Fig. 16-1).

Fig. 16-1

Cradle supporter

Charging operation

< Manual charging >

Press the charging handle down at full stroke 7 or 8 times until a click sounds. (It is completion when a charging handle becomes light.) Then, the closing spring will be fully charged. The charging indicator will show CHARGED.

(Caution)

Do not forcefully press down the charging handle.

Doing so could result in breakage.

Model

AE630-SW ~ AE1600-SW,

AE2000-SWA 3pole

AE2000-SW ~ AE3200-SW,

AE2000-SWA 4pole, AE4000-SWA

AE4000-SW ~ AE6300-SW

Charging operation power

* Values in the tables are reference values.

30N·m

40N·m

< Motor charging (MD) >

Option

The closing spring is charged by an electric motor. When the breaker is closed, the spring is charged automatically

(ON-charge method).

 Manual charging operation is also possible using the charging handle.

 Although the charging motor has a short time rating it can be continuously operated for up to ten times.

 Since the charging complete switch is separate from the motor charging circuit, the sequence can be arranged as required.

OFF charging method

U1

Axb

Control supply

U2

OFF charging method is also available.

The closing spring is charged automatically when the breaker is opened. This is available only by externally connecting b contact (AXb) of the auxiliary switch to the motor charging circuit in series.

In case of DC power supply, please use high capacity auxiliary switch (HAX).

Polarity of DC circuit use

+

U1

U2

E-16

Charging handle

Fig. 16-2

Table 16-1 Motor charging rating

Rated voltage

(V)

24DC

48DC

100-125

AC/DC

200-250

AC/DC

Applicable voltage range

(V)

18 ~ 26.4

36 ~ 52.8

85 ~ 137.5

170 ~ 275

Applied voltage

(V)

24

48

100

125

200

250

Inrush

Current

[Peak value]

(A)

22

14

10(10)

12(12)

5(7)

6(8) time

(s)

< 0.4

< 0.4

AC: < 0.45

DC: < 0.25

AC: < 0.45

DC: < 0.25

Steady current

(A)

6

3

3(4)

3(4)

1(2)

1(2)

Charging time

(s)

≤5

Criterion for power requirement

(VA, W)

500

700

1000

700

1000

Note1 ) Values in parentheses show values for AE4000-SWA 4 pole and AE4000-SW ~ AE6300-SW.

Note2 ) We cannot manufacture AE4000-SWA 4 pole and AE4000-SW ~ AE6300-SW in 24V DC and

48V DC rating.

Note3 ) When choosing from the power supply capacity required to perform motor charging, make sure that its voltage after a voltage drop at power input is still within the applicable voltage range.

Note4 ) These values are for reference, not guaranteed values.

Note5 ) Common use for 50 and 60Hz in AC.

Motor charging circuit diagram

Charged Signal

413

414

Control supply

U1

U2

Charging completion switch

Charging limit switch

M

Motor

Breaker

Control relay

Motor charging circuit

For 24VDC and 48VDC, the Diode rectifier is not included.

Fig. 16-3

Open/close operation

< Conditions for closing operation >

ON operation becomes available when the following conditions are met.

 The breaker is OFF condition.

 The closing spring is charged.

The charging indicator shows “CHARGED”.

 The state without OFF operations.

• Without SHT operation

• Without mechanical lock (Padlock, Cylinder lock, Mechanical interlock etc.)

• UVT controller power is supplied and no operation with trip terminals.

• The manual reset button is being reset

Manual open/close operation

< Closing >

Push the ON button, the breaker will close. The ON/OFF indicator will show “ON”, and the charging indicator will show

“DISCHARGED”. Operating force is less than 50N.

(Caution)

When an OFF locking device (padlock, cylinder lock, etc.) is being used, release the lock, and then perform the closing operation.

When closing or opening a drawout type breaker at the CONNECT or TEST position, do so with the locking plate protruded.

When an undervoltage trip device (UVT) is equipped, wait 1.5 sec. after applying the rated voltage before closing the breaker.

To perform the ON operation, check that the drawout position indicator shows “CHARGED” before pressing the ON button. (Fig. 17-2)

* If undervoltage tripping device ( UVT ) is UVT with a-contact, wait for 1.8 sec. Instead of 1.5 sec.

< Opening >

Push the OFF button, the breaker will be opened and the

ON/OFF indicator will show “OFF”. Operating force is less than 50N.

ON

OFF non-OFF instructions

Manual reset button

OFF

Fig. 17-1

Fig. 17-2

ON

Fig. 17-3

OFF

E-17

Electric open/close operation

< Closing >

Opening operation can be performed electrically by using a closing coil (CC). By applying the rated voltage to A1 and

A2 on the control circuit terminal block, the breaker can be closed.

The pumping preventing relay that performs only one operation with one input command is built in.

To close again, turn OFF the closing coil control supply

(between A1 and A2 ) once, and apply the rated voltage again. For a closing command to CC, wait at least a 0.5 sec. interval after completing charging and turning OFF the breaker.

(Caution)

For a closing command to CC after completing charging, wait at least a 0.5 sec. interval. If a closing command is given within 0.5 sec. after charging completion, the design life of the opening/closing operation may be shortened.

In some cases, the breaker does not close by a closing command given within 0.5 sec. after a manual OFF operation or an OFF operation by SHT.

When an undervoltage trip device (UVT) is equipped, the breaker does not close unless the power supply is applied.

(After applying the control supply to UVT, wait 1.5 sec. for the closing operation to become available.)

If undervoltage tripping device ( UVT ) is UVT with a-contact, wait for 1.8 sec. Instead of 1.5 sec.

< Opening >

Opening operation can be performed electrically by using a shunt trip device (SHT) or undervoltage trip device (UVT).

For SHT, apply a rated voltage to C1 and C2 of the control circuit terminal block.

For UVT, open between the trip terminals DT1 and DT2 of the control circuit terminal block. (A short-circuit bar is equipped when shipped from the factory. Remove this before using.)

Alternatively, turn OFF the voltage applied to D1 and D2 .

UVT circuit diagram (with the 100 to 120 V AC, 200 to 240 V AC, or DC spec. models)

+

D1

UVT controller

D2

DT1

UVT coil

OFF operating

Press button

Min. 0.2 sec.

2 m or less

DT2

Breaker

Note) For the rating of the OFF operation press button switch, use one for 150 V DC and 0.5 A or higher.

Fig. 18-3

CC circuit diagram

+

A1

Control supply

A2

Breaker

One-pulse circuit

CC unit

CC

Note) The 24 V DC to 48 V DC models are not equipped with rectifier circuits.

Fig. 18-1

SHT circuit diagram

+

C1

Control supply

C2

Breaker Cut-off switch

SHT

SHT unit

Note) The 24 V DC to 48 V DC models are not equipped with rectifier circuits.

Fig. 18-2

UVT circuit diagram (with the 380 to 460 V AC models)

IN1 OUT3

IN2

External unit

OUT4

+

D1

D2

UVT controller

UVT coil

DT1

OFF operating

Press button

Min. 0.2 sec.

2 m or less

DT2

Breaker

Note) For the rating of the OFF operation press button switch, use one for 150 V DC and 0.5 A or higher.

The external unit is dedicated to AE-SW. Only one UVT controller can be connected to one external unit.

Fig. 18-4

E-18

Door interlock (DI)

< Procedures for releasing the door interlock >

Interlocks can be manually released even if the breaker is in the ON state.

For this, make a hole of ø7 or larger in the panel door. (Refer to Fig. 19-1)

For the details such as installation and adjustment methods, check the instruction manual provided with the door interlock.

Door

Door hook

(prepared by the customer)

A

Release

Arm

(Breaker ON)

ø7 or larger hole for releasing

Arm

(Breaker OFF)

A

Fig. 19-1

Cylinder lock (CYL) and Castell lock (CAL)

< OFF lock procedures >

Press the OFF button to turn off the breaker.

Turn the key counterclockwise while pressing the OFF button to lock the OFF state. Then, you can remove the key. (Fig.

19-2)

< Releasing procedure >

Insert the key and rotate it clockwise.

If the key is stiff to rotate, push down the OFF button and rotate the key clockwise. (Fig. 19-3)

The key cannot be removed in the released state.

LOCK (OFF)

Keep Pushing

OFF Button

RELEASE

Keep Pushing

OFF Button

RELEASE

Lock

Fig. 19-2

Keep Pushing

OFF Button

RELEASE

Fig. 19-3

Release

OCR alarm (AL) [MRE: manual reset type]

When the breaker is tripped, the OCR alarm (AL) is continuously output.

After the breaker is tripped, press the manual reset button, which is located in front of the breaker, to reset.

Without a reset, the breaker cannot be turned ON.

Manual reset button (trip state)

Fig. 19-4

E-19

Shutter lock (SST-LOCK)

When pulling out a breaker equipped with a safety shutter

(SST) from the cradle, its safety shutter can be locked in the closing position so that the live parts cannot be touched.

A padlock (shackle diameter ø5 or less) is provided by the customer.

Padlock

(shackle diameter ø5 or less)

Shutter lock

Fig. 20-1

Safety shutter nameplate

Please refer to the example below when using the safety shutter nameplates “BUSBARS” and “CABLES,” which are enclosed with the safety shutter (SST).

(Fig. 20-2)

Remove debris and dust from the safety shutter before adhering the nameplate.

(BUSBARS: Line side, CABLES: Load side)

Safety shutter nameplate

(One each is supplied)

Safety shutter nameplate can be adhered

Fig. 20-2

E-20

Functions of electronic trip relay (ETR) parts

< Function description of each part >

① ERR. LED, contact output

When any abnormality or setting failure is found in the

ETR, this provides a notification of the abnormal status.

When the power supply type is P3 ~ P5, contact output is given between 513 and 574 on the control circuit terminal block.

• Functional abnormality in ETR (microprocessor, H/W)

• Incorrect setting (mis-setting of Int/MCR)

• Abnormality in in-breaker wiring related to ETR

② RUN LED (ETR)

ETR indicates the operable state. If the control power supply is applied, or when approx. 10% of the rated current flows to the main circuit, the internal circuit is activated, turning on this LED.

③ RUN LED (option setting module) Option

This indicates that the option setting module is in an operable state.

If the control power supply is applied, or when approx.

10% of the rated current flows to the main circuit, the internal circuit is activated, turning on this LED.

④ Trip cause indicator (LED, contact output) Option

The cause of a trip is indicated by LED. When the power supply type is P3 ~ P5, a contact output is given between 513 (common) and 524 , 534 , 544 , or 554 on the control circuit terminal block.

PAL LED will blink when the current exceeds the prealarm current setting (Ip), and will be lit after 1/2 of the

LTD time is passed. At this time, the contact output will also be made.

⑤ TAL LED, contact output Option

The ETR temperature detector becomes operable when a TAL sensor is installed. When the power supply type is P3 ~ P5, a contact output is given between 513 and

564 on the control circuit terminal block. When the temperature drops, the output will be reset. To retain the output, use an external sequence.

⑥ MCR (Making-current release) Option

The setting can be switched between the instantaneous current (INST) and MCR functional current (MCR). In the

MCR setting, INST characteristic is enabled from the time of breaker closing (OFF to ON), and after closing, the INST characteristic becomes disabled.

If specified at the time of ordering, an MCR switch is built in to the breaker. When shipped from the factory, this is set to the INST side.(Fig. 21-2)

⑦ RESET button

To reset the trip cause indicator (LED, contact output), use the “RESET” button in front of ETR, or short-circuit

RS1 and RS2 on the control circuit terminal block for 0.5 seconds or longer.

(The power supply type P1 and P2 are not provided with the function to reset from the control circuit terminal block.)

There is also a function to temporarily lock LTD and STD to test the INST characteristic by using a dedicated field testing device. (For operating instructions, refer to the instruction manual of the tester.)

⑥ MCR

② RUN LED

(ETR)

① ERR. LED

④ Trip cause indicator

LED

⑤ TAL LED

Fig. 21-2

③ RUN LED

(GFR)

④ Trip cause indicator

LED

⑦ RESET button

Fig. 21-1 Example) WS1G1

For the display (including measuring functions) and interface unit, see the separate instruction manual.

E-21

< Load current indicator LED >

The current value, which is used as a reference by the load current indicator LED, varies depending on the applications and relay types.

Table 22-1

Application classification

Relay type

Reference current for LED display

LED display

General use

Generator protection

WS

WS1

WS2

WS3

WM

WM1

WM2

WM3

Uninterrupted current

I

Iu

L

LTD pick-up current

100

80

60

40

%I

L

OVER

100

80

60

%Iu

Special purpose

WB

WB1

WB2

WB3

Ir

Rated current setting

OVER

100

80

60

%Ir

Protection coordination

WF

WF1

WF2

WF3

Ir

Rated current setting

OVER

100

80

60

%Ir

Note) When the “OVER” LED of WS, WB, or WF type or the “100%” LED of

WM type is lit, the current value is over the uninterrupted current. The breaker will trip after the ETR set time is passed.

< Pre-alarm operation >

PAL LED will blink when the current exceeds the pre-alarm current setting (Ip), and will be lit after 1/2 of the long time lag (T

L

) is passed. The power supply type P3 to P5 will also perform a contact output. For the operation time period, refer to the characteristic curve.

Current

Ip

Load current

PAL LED

PAL contact output

Blinking

1/2 T

L

ON

Lit

OFF

Time passed t

< Control power supply >

This is required for the trip cause indicator (LED, contact output), the measurement extension module, displays, etc. Over-current and short-circuit protection is performed by the power supply CT energy, even if the control power supply is not available.

Power supply type

Rated voltage

(V)

Applicable voltage range

(V)

Criterion for power requiement

(VA)

Alarm output contacts

P1

P2

P3

P4

P5

100-240 AC/DC

24-60 DC

100-240 AC

100-125 DC

24-60 DC

100-240 DC

85-264 AC/DC

18-72 DC

85-264 AC

85-138 DC

18-72 DC

85-264 DC

15

10

15

10

15

6 contacts

6 contacts

6 non-contacts (SSR)

(1) Overcurrent protection is powered by the CT, which is built into the breaker. It is operable regardless of the external power supply.

Ground fault protection (GFR) is also operable at 0.2 to 1.0 rated current (In) settings, regardless of the control power supply.

(2) 6 contact outputs are set as below.

① LTD

Self-hold type

② STD/INST

Self-hold type

③ G1/E1/AP

See the table below.

④ PAL

Auto-reset type

⑤ TAL

Auto-reset type

⑥ ERR.

Auto-reset type

Dial setting

TRIP side

ALARM side

G1

Self-hold type

Auto-reset type

E1

Self-hold type

Auto-reset type

AP

Auto-reset type

Self-hold type ....The output state is held until it is reset.

Auto-reset type...Output is reset upon returning to the normal condition.

Contact capacity (power supply type P3, P4)

Current (A)

Voltage (V)

Resistance load Induction load cosø=1.0

cosø=0.4

L/R=0.7

AC

(50/60 Hz)

DC

240

120

125

30

1

1

0.1

1

0.5

1

0.05

1

Current capacity (power supply type P5)

Voltage (V)

Steady current

(A)

Permissible peak current at open/close

(A)

AC

(50/60 Hz)

DC

240

120

240

30

0.1

0.1

0.1

0.1

0.3

0.3

0.3

0.3

ON resistance (Ω)

(Max.)

5

5

5

5

CAUTION

With the power supply types P3 and P4, high-sensitivity relays are used for contact outputs. Because of that, contact outputs may trigger chattering noise (approx. 1 ms of mis-outputs) at breaker opening/closing in some panel installation conditions. When using the product in a fast-response sequence, install a filtering circuit of a few milliseconds or perform double reading of samples.

E-22

Characteristics setting for the WS type

Pre-alarm current: Ip

② Uninterrupted current: Iu

③ LTD time: TL

⑧ Pre-alarm

time: Tp

④ STD pick-up

current: Isd

1

2

6

3

5

4

⑤ STD time: Tsd

With MCR

7

I 2 t ON

(ramp)

I 2 t OFF

⑥ INST/MCR pick-up

current: Ii

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

Current (%)

Note) The figure shows a model with an optional

G1 setting module, a display, and an MCR switch.

Table 23

No.

Setting item

Rated current

② Uninterrupted current

LTD time

STD pick-up current

Symbol

Ir

Iu

T

L

Isd

Characteristic setting range

0.5 to 1.0 (0.05 step) x In (CT rating)

0.8 to 1.0 x Ir (0.02 step), pick-up current: 1.15 x Iu

12-25-50-100-150s at Iu x 2

1.5-2-2.5-3-4-5-6-7-8-9-10 x Ir

⑤ STD time Tsd

0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s

(I 2 t ON) (I 2 t OFF) at Isd x 1.5

INST/MCR pick-up current

Ii

AE630-SW ~ AE1600-SW

AE2000-SW ~ AE3200-SW, AE4000-SW

AE2000-SWA, AE4000-SWA

AE5000-SW

(INST) (MCR)

12-10-8-6-4-2-2-4-6-8-10-12 x Ir

(INST) (MCR)

Pre-alarm current

Pre-alarm time

Ip

Tp

AE6300-SW

1/2 T

L

10-8-6-4-2-2-4-6-8-10

(INST)

Iu x 0.68 to 1.0 (0.04 step)-OVER

Remark (1) For WS relay, Pre-alarm current “OVER” setting is lu x 1.15.

Remark (2) The table shows data obtained on the breakers provided with MCR (optional).

(MCR)

x Ir

at Iu x 2 (PAL contact output after passing 1/2 of T

L

)

WS1

WS2

WS3

Accuracy

1.05 x Iu ..... Pick up not performed

1.25 x Iu ..... Pick up performed

±20%

±15%

±20%

It operates in the range between 0.04 and 0.08s

when the time set at 0.06s.

±15%

±10%

±20%

Factory default value

1.0

1.0

150

10

0.5 (I 2 t ON)

WS1…16 (INST)

WS2…12 (INST)

WS3…10 (INST)

OVER

Systematic diagram of setting dial coordination

In (CT rating) Ir Iu Ip

Isd

Ii

Ip2 (P.29)

Load current LED (60, 80, 100%, OVER)

Ig (P.28)

E-23

Characteristics setting for the WM type

⑦ Pre-alarm current: Ip

② LTD pick-up

current: I

L

③ LTD time: T

L

⑧ Pre-alarm

time: Tp

④ STD pick-up

current: Isd

⑤ STD time: Tsd

1

2

6

3

5

4

With MCR

7 I 2 t ON

(ramp)

I 2 t OFF

⑥ INST/MCR pick-up

current: Ii

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

Note) The figure shows a model with an optional G1 setting module, a display, and an MCR switch.

Current (%)

Table 24

No.

Setting item

Rated current

LTD pick-up current

LTD time

STD pick-up current

Symbol

Ir

I

L

T

L

Isd

STD time

INST/MCR pick-up current

Pre-alarm current

Pre-alarm time

Tsd

Ii

Ip

Tp

Characteristic setting range Accuracy Factory default value

Set to the specified value at the factory Note 1)

1.0-1.05-1.1-1.15-1.2 x Ir

15-20-25-30-40-60s at I

L

x 1.2

1.5-2-2.5-3-3.5-4-4.5-5 x Ir

±5%

±20%

0.5-0.4-0.3-0.2-0.1-0.06-0.06-0.1-0.2-0.3-0.4-0.5s

(I 2 t ON) (I 2 t OFF) at Isd x 1.5

AE630-SW ~ AE1600-SW

AE2000-SW ~ AE3200-SW

AE4000-SW

16-12-10-8-6-4-2-2-4-6-8-10-12-16

(INST) (MCR)

WM1

AE2000-SWA, AE4000-SWA

AE5000-SW

12-10-8-6-4-2-2-4-6-8-10-12 x Ir

(INST) (MCR)

WM2

AE6300-SW

10-8-6-4-2-2-4-6-8-10 x Ir

(INST) (MCR)

WM3

I

L

× 0.68 to 1.0 (0.04 step) -OVER

1/2 T

L

at IL × 1.2 (PAL contact output after passing 1/2 of T

L

)

±15%

±20% Note 2)

It operates in the range between 0.04

and 0.08s when the time set at 0.06s.

±15% Note 2)

±5%

±20%

To be complied with ordering indication

1.15

20

5

0.5 (I 2 t ON)

WM1…16 (INST)

WM2…12 (INST)

WM3…10 (INST)

OVER

Remark (1) For WM relay only, when Pre-alarm current Ip is set a “OVER” the Ip value becomes equal to “I

L x 1.0”.

Remark (2) The table shows data obtained on the breakers provided with MCR (optional).

Systematic diagram of setting dial coordination

In (CT rating) Ir (Fixed) I

L

Ip

E-24

Ig (P.28)

Isd

Ii

Ip2 (P.29)

Load current LED (40, 60, 80, 100%)

Note 1) CT rating 250 A and 315 A can be set in 0.1 A steps, and

500 A or higher can be set in 1 A steps.

Note 2) When used without voltage applied to the control power supply (ETR power supply module) Tsd, Ii operation time may increase max. 20ms.

Characteristics setting for the WB type

⑦ Pre-alarm current: Ip

⑧ Pre-alarm

time: Tp

Max. energizing time

Max. setting value of external OCR

⑥ INST/MCR pick-up current: Ii

1 6

Up to Icw

Up to Icw

7

Note) The figure shows a model with an optional

MCR switch.

Current (%)

Table 25

No.

Setting item Symbol Characteristic setting range

Rated current

INST/MCR pick-up current

Ir

Ii

0.5 to 1.0 (0.05 step) x In (CT rating)

AE630-SW ~ AE1600-SW

AE2000-SW ~ AE3200-SW, AE4000-SW

AE2000-SWA, AE4000-SWA

AE5000-SW

(INST) (MCR)

12-10-8-6-4-2-2-4-6-8-10-12

(INST) (MCR)

x Ir

Pre-alarm current

Pre-alarm time

Ip

Tp

AE6300-SW

10-8-6-4-2-2-4-6-8-10 x Ir

(INST) (MCR)

Ir x 0.68 to 1.0 (0.04 step)-OVER

75 s at Ir x 2 (PAL contact output after passing 75 s)

Remark (1) For WB relay, when Pre-alarm current Ip is set at “OVER”, the Ip value is “I r x 1.15”.

Remark (2) The table shows data obtained on the breakers provided with MCR (optional).

WB1

WB2

WB3

Systematic diagram of setting dial coordination

In (CT rating) Ir Ii

Ip

Load current LED (60, 80, 100%, OVER)

Ig (P.28)

Accuracy

±15%

±10%

±20%

Max. shutoff time period

(0.05 s for AE4000-SW to 6300-SW)

Factory default value

1.0

WB1…16 (INST)

WB2…12 (INST)

WB3…10 (INST)

OVER

E-25

Characteristics setting for the WF type

The selectable characteristics are the following five curves.

4

5

6

2

1

3

12

8

9

10

11

(I 4 -1)t = const.

(I 3 -1)t = const.

(I 2 -1)t = const.

(I -1)t = const.

(I 0.02 -1)t = const.

16

13

15

I (current)

LTD characteristics curves

14

LTD curve can be selected by the LTD curve setting dial.

Trip indicator LED

Pre-alarm LED

Temperature alarm LED

Load current LED

RUN LED

ERR. LED

Current setting dial

LTD time setting dial

LTD curve setting dial

STD pick-up setting dial

STD time setting dial

INST/MCR pick-up current setting dial

Optional setting module

Pre-alarm current setting dial

RESET button (TEST L/S LOCK button)

TEST terminal

Note) The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.

G1, DP1 and MCR are optional equipments.

[LTD curve setting "a=2"] a=2

10000

5000

4000

3000

2000

1000

1

.5

.4

.3

.2

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

500

400

300

200

100

60

50

40

30

20

5

4

3

2

10

LTD operating time t

LTD

Note1 t

LTD

(4/1.1155) a

(I/1.1155Ir)

-1 a

-1

L

Accuracy : a = 2

I = load current (A)

Ir= 0.5~1.0 x In (A)

T L = 1~18 (s)

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

PAL operating time t

PAL

Note2 t PAL

(I/0.97lp) a -1 a -1

L a = 2

I = load current (A)

Ip= 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

Accuracy :

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

Pre-alarm time : Tp

T

L

/2 ± 20% (at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

.1

.05

.04

.03

.02

.01

1

Note1 : LTD operating time is 0.8s(FLAT)when the operating

time becomes 0.8s or less.

Note2 : PAL operating time is 0.5s(FLAT) when the operating

time becomes 0.5s or less.

Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.

I 2 t is selectable ON or OFF.

2 5 10 20 50

I 2

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

Current (%)

5000 10000

Table 26

No.

Setting item

⑦ Current setting

LTD time

LTD curve setting

STD pick-up current

Symbol

Ir

T

L a

Isd

Characteristic setting range

0.5 ~ 1.0 (0.05step) x In (CT rating)

LTD pick-up current : 1.15 x Ir

1–2–3–4–5–6–8–10–12–15–18s

0.02–1–2–3–4

1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir at Ir x 4

Accuracy

1.10 x Ir…Non Pick-up

1.20 x Ir…Pick-up

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

± 15%

± 20%

It operates in the range between 0.04 and 0.08 when the time set at 0.06s.

Factory default value

1.0

18

2

10

0.5 (I 2 t ON) ⑪ STD time

INST/MCR pick-up current

Pre-alarm current

Pre-alarm time

Tsd

Ii

Ip

Tp

0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s

(I 2 t ON) (I 2 t OFF) at Isd x 1.5

AE630-SW~AE1600-SW

AE2000-SW~AE3200-SW

AE4000-SW

AE2000-SWA, AE4000-SWA

AE5000-SW

AE6300-SW

16-12-10-8-6-4-2-2-4-6-8-10-12-16

(INST) (MCR)

12-10-8-6-4-2-2-4-6-8-10-12

(INST) (MCR)

10-8-6-4-2-2-4-6-8-10 x Ir

(INST) (MCR)

Ir x 0.68 ~ 1.0 (0.04step) –OVER

x Ir

x Ir

WF1

WF2

WF3

1/2 T

L

at Ir x 4 (after 1/2 T

L

, PAL contact output turns on.)

Remark (1) The table and the figure include both optional display and MCR.

Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".

Relation of setting dial

In (CT rating) Ir

Ig (P.28)

E-26

Isd

Ii

Ip

Ip2 (P.29)

Load current LED (60, 80, 100%, OVER)

± 15%

± 5%

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

WF1…16 (INST)

WF2…12 (INST)

WF3…10 (INST)

OVER

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=0.02"] a=0.02

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2

STD time : Tsd

0.06-0.1-0.2-0.3-0.4-0.5(s) ±

Note3

20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

5

Pre-alarm time : Tp

T

L

/2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

With MCR

10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12 ±

15% WF1

15% WF2

Ir x 2-4-6-8-10 ± 15% WF3

50 100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000

Current (%)

10000

[LTD curve setting "a=3"] a=3

10000

500

400

300

200

100

60

50

40

30

20

5000

4000

3000

2000

1000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp Note2

T L /2 ± 20% (at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

10

5

4

3

2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

1

.5

.4

.3

.2

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

50 100 150

125 200

Current (%)

500 1000 2000

1600

5000 10000

Note 1: LTD operating time t

LTD

is calculated by the following equations.

a = LTD curve setting t LTD =

(4/1.1155) a -1

(I/1.1155Ir) a -1 x T L

I = load current (A)

Ir = 0.5~1.0 x In (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current<4Ir) or ± 20% (4Ir ≦ load current).

LTD operating time is 0.8s(FLAT) when the operating time becomes 0.8s or less.

Note 3: When Tsd = "0.06" setting, operating time is 0.04~0.08s.

I 2 t is selectable : ON or OFF.

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=1"] a=1

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up 1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2 5

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

10 20

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

±

±

15% WF1

15% WF2

15% WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

[LTD curve setting "a=4"] a=4

10000

100

60

50

40

30

20

10

5000

4000

3000

2000

1000

500

400

300

200

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

5

4

3

2

1

.5

.4

.3

.2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x ± 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

15% : WF1

15% : WF2

± 15% : WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

Note 2: PAL operating time t

PAL

is calculated by the following equations.

a = LTD curve setting t

PAL

=

(4Ir/0.97Ip) a -1

(I/0.97Ip) a -1 x

T

L

2

I = load current (A)

Ir = 0.5~1.0 x In (A)

Ip = 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current < 4Ir) or ± 20% (4Ir ≦ load current).

PAL operating time is 0.5s(FLAT) when the operating time becomes 0.5s or less.

4

5

6

2

1

3

16

The selectable characteristics are the following five curves.

12

8

9

10

11

(I 4 -1)t = const.

(I 3 -1)t = const.

(I 2 -1)t = const.

(I -1)t = const.

(I 0.02 -1)t = const.

13

15

I (current)

LTD characteristics curves

14

LTD curve can be selected by the LTD curve setting dial.

Trip indicator LED

Pre-alarm LED

Temperature alarm LED

Load current LED

RUN LED

ERR. LED

Current setting dial

LTD time setting dial

LTD curve setting dial

STD pick-up setting dial

STD time setting dial

INST/MCR pick-up current setting dial

Optional setting module

Pre-alarm current setting dial

RESET button (TEST L/S LOCK button)

TEST terminal

Note) The figure shows WF1 type with G1 module, Display (DP1) and MCR switch.

G1, DP1 and MCR are optional equipments.

[LTD curve setting "a=2"] a=2

10000

5000

4000

3000

2000

1000

1

.5

.4

.3

.2

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

500

400

300

200

100

60

50

40

30

20

5

4

3

2

10

LTD operating time t

LTD

Note1 t

LTD

(4/1.1155) a

(I/1.1155Ir)

-1 a

-1

L

Accuracy : a = 2

I = load current (A)

Ir= 0.5~1.0 x In (A)

T L = 1~18 (s)

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

PAL operating time t

PAL

Note2 t PAL

(I/0.97lp) a -1 a -1

L a = 2

I = load current (A)

Ip= 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

Accuracy :

± 30%(1.5Ir load current<4Ir)

± 20%(4Ir load current)

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

Pre-alarm time : Tp

T

L

/2 ± 20% (at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

.1

.05

.04

.03

.02

.01

1

Note1 : LTD operating time is 0.8s(FLAT)when the operating

time becomes 0.8s or less.

Note2 : PAL operating time is 0.5s(FLAT) when the operating

time becomes 0.5s or less.

Note3 : When Tsd ="0.06" setting,operating time is 0.04~0.08s.

I 2 t is selectable ON or OFF.

I 2

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

2 5 10 20 50 100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

Current (%)

5000 10000

No.

Setting item

Current setting

LTD time

LTD curve setting

STD pick-up current

Symbol

Ir

T a

L

Isd

Characteristic setting range

0.5 ~ 1.0 (0.05step) x In (CT rating)

LTD pick-up current : 1.15 x Ir

1–2–3–4–5–6–8–10–12–15–18s

0.02–1–2–3–4

1.5–2–2.5–3–4–5–6–7–8–9–10 x Ir at Ir x 4

Accuracy

1.10 x Ir…Non Pick-up

1.20 x Ir…Pick-up

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

± 15%

± 20%

It operates in the range between 0.04 and 0.08 when the time set at 0.06s.

Factory default value

1.0

18

2

10

0.5 (I 2 t ON) ⑪

STD time

INST/MCR pick-up current

Pre-alarm current

Pre-alarm time

Tsd

Ii

Ip

Tp

0.5–0.4–0.3–0.2–0.1–0.06–0.06–0.1–0.2–0.3–0.4–0.5s

(I 2 t ON) (I 2 t OFF) at Isd x 1.5

AE630-SW~AE1600-SW

AE2000-SW~AE3200-SW

AE4000-SW

AE2000-SWA, AE4000-SWA

AE5000-SW

AE6300-SW

16-12-10-8-6-4-2-2-4-6-8-10-12-16

(INST) (MCR)

12-10-8-6-4-2-2-4-6-8-10-12

(INST) (MCR)

10-8-6-4-2-2-4-6-8-10 x Ir

(INST) (MCR)

Ir x 0.68 ~ 1.0 (0.04step) –OVER

x Ir

x Ir

WF1

WF2

WF3

1/2 T

L

at Ir x 4 (after 1/2 T

L

, PAL contact output turns on.)

Remark (1) The table and the figure include both optional display and MCR.

Remark (2) For WF relay, when Pre-alarm current Ip is set at "OVER", the Ip value is "Ir x 1.15".

Relation of setting dial

In (CT rating) Ir

Ig (P.28) Isd

Ii

Ip

Ip2 (P.29)

Load current LED (60, 80, 100%, OVER)

± 15%

± 5%

± 30% (1.5Ir

≦ load current<4Ir)

± 20% (4Ir ≦ load current)

WF1…16 (INST)

WF2…12 (INST)

WF3…10 (INST)

OVER

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=0.02"] a=0.02

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2

STD time : Tsd

0.06-0.1-0.2-0.3-0.4-0.5(s) ±

Note3

20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

5

Pre-alarm time : Tp

T

L

/2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

With MCR

10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12 ±

Ir x 2-4-6-8-10 ±

15% WF1

15% WF2

15% WF3

50 100 150

125 200

500

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000

Current (%)

10000

[LTD curve setting "a=3"] a=3

10000

500

400

300

200

100

60

50

40

30

20

5000

4000

3000

2000

1000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp Note2

T L /2 ± 20% (at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

10

5

4

3

2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

1

.5

.4

.3

.2

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

15% : WF1

± 15% : WF2

± 15% : WF3

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

50 100 150

125 200

Current (%)

500 1000 2000

1600

5000 10000

Note 1: LTD operating time t

LTD

is calculated by the following equations.

a = LTD curve setting t LTD =

(4/1.1155) a -1

(I/1.1155Ir) a -1 x T L

I = load current (A)

Ir = 0.5~1.0 x In (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current<4Ir) or ± 20% (4Ir ≦ load current).

LTD operating time is 0.8s(FLAT) when the operating time becomes 0.8s or less.

Note 3: When Tsd = "0.06" setting, operating time is 0.04~0.08s.

I 2 t is selectable : ON or OFF.

100

60

50

40

30

20

10

.5

.4

.3

.2

.1

5

4

3

2

1

.05

.04

.03

.02

.01

1

[LTD curve setting "a=1"] a=1

10000

5000

4000

3000

2000

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up 1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up 1000

500

400

300

200

2 5

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

10 20

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T L Note1

1-2-3-4-5-6-8-10-12-15-18(s) ± 20%

(at Ir x 4)

With MCR

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

±

±

15% WF1

15% WF2

15% WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

[LTD curve setting "a=4"] a=4

10000

100

60

50

40

30

20

10

5000

4000

3000

2000

1000

500

400

300

200

Pre-alarm current : Ip

Ir x 0.68~1.0(0.04step)-OVER ± 5%

Current setting : Ir

0.5~1.0(0.05step) x In(CT rating)

LTD pick-up

1.10 x Ir ... Non pick-up

1.20 x Ir ... Pick-up

Pre-alarm time : Tp

T L /2 ± 20%

Note2

(at Ir x 4)

LTD time : T

L

1-2-3-4-5-6-8-10-12-15-18(s) ±

Note1

20%

(at Ir x 4)

5

4

3

2

1

.5

.4

.3

.2

STD time : Tsd Note3

0.06-0.1-0.2-0.3-0.4-0.5(s) ± 20%

(at Isd x 1.5)

STD pick-up current : Isd

Ir x ± 1.5-2-2.5-3-4-5-6-7-8-9-10 ± 15%

With MCR

.1

.05

.04

.03

.02

.01

1 2 5 10 20

I 2 t ON

(ramp)

I 2 t OFF

INST/MCR pick-up current : Ii

Ir x 2-4-6-8-10-12-16 ±

Ir x 2-4-6-8-10-12

Ir x 2-4-6-8-10

±

15% : WF1

15% : WF2

± 15% : WF3

500 50 100 150

125 200

Current (%)

Max. breaking time

(In case of AE4000-SW~

6300-SW, it is 0.05s)

1000 2000

1600

5000 10000

Note 2: PAL operating time t

PAL

is calculated by the following equations.

a = LTD curve setting t

PAL

=

(4Ir/0.97Ip) a -1

(I/0.97Ip) a -1 x

T

L

2

I = load current (A)

Ir = 0.5~1.0 x In (A)

Ip = 0.68~1.15 x Ir (A)

T

L

= 1~18 (s)

The accuracy of operating time is ± 30% (1.5Ir

≦ load current < 4Ir) or ± 20% (4Ir ≦ load current).

PAL operating time is 0.5s(FLAT) when the operating time becomes 0.5s or less.

E-27

Characteristics setting for the optional setting modules

< Characteristics setting for the G1 module >

1

① Ground fault pick-up current: Ig

1.0

0.1

3.0±20%

2

˜ To provide ground fault protection for a 3-pole breaker used in the 3-phase 4-wire system, a neutral pole CT (NCT) is required. For the specification, refer to the catalog.

For the installation of the NCT, refer to the instruction manual provided with the NCT.

˜ The G1 module cannot be attached to the AE630-SW low rating models (CT rating:

500 A, 315 A, 250 A).

To set the ground fault pick-up current Ig to 0.1, the control power supply must be applied. (If the control power supply is not applied, ground fault protection cannot be provided correctly.)

Table 28-1

No.

Setting item

Ground fault pick-up current

Symbol

Ig

Ground fault operating time

– Alarm output

Tg

Characteristic setting range

0.1 to 1.0 × In (0.1 step)

Accuracy

±20%

Factory default value

1.0

3.0-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3.0 s

(TRIP) (ALARM)

(at 1.5×Ig)

TRIP: self-hold type / ALARM: automatic reset type

±20%

3s(TRIP)

Self-hold type(TRIP)

< Characteristics setting for the E1 module >

E1 module, in combination with an external ZCT, provides electric leakage protection.

To provide the electric leakage protection, a control power supply is required.

ZCT for load circuit

ZCT type

ZCT163

ZCT323

Breaker type, number of poles

AE630-SW ~ AE1600-SW 3-pole

AE630-SW ~ AE1600-SW 4-pole

AE2000-SW ~ AE3200-SW 3-pole

AE2000-SW ~ AE3200-SW 4-pole ZCT324

Type combinations shown in this table are for reference.

Choose the one that matches the size of the conductor to be connected.

ZCT with primary conductor

ZCT type

ZTA1200A

ZTA2000A

Breaker type, number of poles

AE630-SW ~ AE1000-SW 3-pole model

AE1250-SW ~ AE2000-SW 3-pole model

AE2000-SWA 3-pole model

The types not listed above can also be used if their rated current setting (Ir) is ZCT permissible current value or lower.

ZCT for transformer earth wire

ZT15B ZT30B

ZCT type

ZT40B ZT60B ZT80B ZT100B

 Be sure to use with the ZCT specified by Mitsubishi Electric.

 For the ZCT installation, refer to the instruction manual provided with the ZCT.

Table 28-2

No.

Setting item

ER Pick-up current

Symbol

I∆n

ER Operating time

Te

– Alarm output –

Characteristic setting range

1-2-3-5-10A

3-1.5-0.8-0.5-0.3-0.15-<0.1s - <0.1-0.15-0.3-0.5-0.8-1.5-3 s

(TRIP) (ALARM)

(at 1.5×I∆n)

TRIP: self-hold type / ALARM: automatic reset type

Accuracy

0%

-30%

Factory default value

10A

±20%

3s(TRIP)

Self-hold type(TRIP)

E-28

1

② Ground fault operating time: Tg

0.15±20%

<0.1

(0.04 to 0.1s)

Ground fault current (% of CT rating In)

1A

① ER Pick-up current: I∆n

10A

3.0s±20%

② ER Operating time: Te

0.15s±20%

<0.1s

(0.04 to 0.1s)

Electric leakage current (A)

2

< Characteristics setting for the AP module >

By combining this with the pre-alarm function installed as standard, the two-step pre-alarms can be constructed.

For the AE630-SW low rating types, be sure to apply the control power supply.

This cannot be combined with the WB type.

˜ With the WS type

1

˜ With the WM type

2

① 2nd pre-alarm

Current: Ip2

LTD time: T

L

12-25-50-100-150s (at Iu x 2)

① 2nd pre-alarm

Current: Ip2

LTD time: T

L

15-20-25-30-40-60 s (at I

L

x 1.2)

② 2nd pre-alarm

Time: Tp2 (FLAT)

② 2nd pre-alarm

Time: Tp2 (FLAT)

② 2nd pre-alarm

Time: Tp2 ( x T

L

)

② 2nd pre-alarm

Time: Tp2 ( x T

L

)

Current (% of Iu)

Current (% of I

L

)

Table 29

No.

Setting item

① 2nd pre-alarm current

Symbol

Ip2

2nd pre-alarm time

Tp2

Characteristic setting range

0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x Iu

0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x I

L

0.9-0.8-0.7-0.6-0.5-0.4-0.3 x T

L

- 5-10-15-20-30-40-60s

(x T

L

) (FLAT)

WS

WM

Accuracy

±10%

±5%

±20%

WS

WM

Factory default value

1.0

0.9(x T

L

)

< N5 module >

LTD and pre-alarm characteristics of the neutral pole are 50% of the voltage pole.

However, STD and INST characteristics are the same as for the voltage pole (100%).

For the AE630-SW low rating types, be sure to apply the control power supply.

This cannot be combined with the WB type.

E-29

Setting procedure for the electronic trip characteristics

< Setting procedure >

Note) Move the screwdriver in the direction of the arrow.

CAUTION

Before changing the setting, turn off the breaker’s main power supply and, the ETR’s control power supply, and confirm that no current is flowing.

① Prepare a small flat tipped screwdriver.

0.8 mm or less Side view of the tip

6 mm or less

ETR cover

Operating hole for RESET button

Fig. 30-1

Test terminal

Fig. 30-2

Sealing hole

(a) Stepping type

RESET button

(b) Push button type

② Insert a flat tipped screwdriver into the upper opening of the ETR cover. Then, lightly push the handle as shown in

Fig. 28-1 to open the ETR cover.

③ There are 2 types of switches. Operate them accordingly.

(a) Stepping type

• This is a rotary stepping switch. Do not stop in between steps.

• If the dial is in the middle, the settings on either side are enabled.

• Operate in the range of 0.02N.m torque or less.

• When MCR (option) is not attached, Ii is set as shown in Fig. 30-3.

Do not set to the “Do not set” area. Always set to the INST side.

(For the function descriptions of MCR, refer to P.21.)

• In the bold line area, where there is a range, the setting is the same for the entire area. (Fig. 30-4)

INST

6 4

10

8

12

16

2 l i(xlr)

Do not set

Fig. 30-3

(With T

L

)

Fig. 30-4

(b) Push button type

This is a self-recovering push button switch. Push with 3N force or less.

④ After changing a characteristic setting, check the tripping characteristic with a field testing device.

Characteristics can be checked through the ETR test terminal by using a dedicated field testing device. For the check procedure, refer to the instruction manual of the testing device.

Specifications of the field testing device Y-2005

Test item

Testable range

External dimensions mm

Counter

Control voltage

Mass

LTD, STD, INST, GFR, PAL

1% to 2500% × In

220 (width) × 150 (height) × 340 (depth)

0.000 to 999.999 s

100-240 V AC (50/60 Hz)

4.8 kg

E-30

< Electronic trip relay setting example >

Calculation method for the setting value is explained using the example of the AE1600-SW 1600A WS1G1 relay.

Ir=0.8×In

=0.8×1600A

=1280A

Iu=0.9×Ir

=0.9×1280A

=1152A

Isd=3×Ir

=3×1280A

=3840A

Ig=0.1×In

=0.1×1600A

=160A

Ip=0.8×Iu

=0.8×1152A

=921.6A

In=1600A

Ii=12×Ir

=12×1280A

=15360A

T

L

= 100 sec.

Current twice the amount of Iu

= operating time at

1152 × 2 = 2304 A

Ir = Rated current setting

Iu = Uninterrupted current

T

L

= LTD time

Isd = STD pick-up current

Tsd = STD time

Ii = INST/MCR pick-up current

Ip = Pre-alarm current

Tg = Ground fault operating time

Tsd = 0.3 sec.

Current 1.5 times of Isd

= operating time at

3840 × 1.5 = 5760 A

Tg = 0.8 sec.

Current 1.5 times of Ig

= operating time at

160 × 1.5 = 240 A

Fig. 31-1

Tp = 1/2T

L

At 2304 A,

1/2 of T

L

100 × 0.5 = 50 sec.

Sealing hole

Table 31 Current value and operating time by setting value

In (CT rating) = 1600 A

Ir = 1280 A

Iu = 1152 A

T

L

=

Isd = 3840 A ± 15%

Ii

Ip

Tp

Ig

Tg

= 15360 A ± 15%

= 921.6 A ± 10%

= 50 sec. ± 20% (at 2304 A)

= 160 A ± 20%

= 0.8 sec. (at 240 A) ± 20%

< Relay sealing >

When sealing is required, use the sealing hole located on top of the ETR cover. (Fig. 31-2)

Fig. 31-2

E-31

Wiring diagram

* The wiring diagram below shows a fully equipped model.

L1 L2 L3 N

Terminals for extension RS1

Wiring length

2 m or less

RS2

Control power supply

513 P1

+

P2 97 C1

+

A1

+

See the figure below for wiring.

+ +

D2 D1 413 U1

+

Electronic trip relay

(ETR)

Reset circuit Power supply circuit

Alarm contacts

(Power supply type P3 ~ P5 only)

SHT CC

UVT

M

Breaker

Main circuit

N1 N2 Z1 Z2 P4

(

M8 screw

)

NCT ※ ZCT ※

※ Voltage forbid to be applied.

FG

Dielectric test forbidden

574 564 554 544 534 524 98 C2 A2 DT2 DT1 414 U2

Shorting bar

Push button for tripping

Wiring length

2 m or less

Electronic trip relay

Control power supply circuit/ alarm contact

OCR alarm

Electric operation circuit

E-32

Terminal description

13 14 ~ 53 54

11

U1

12

U2

~ 51 52

413 414

D1 D2

DT1 DT2

A1

C1

97

P1

P4

RS1 RS2

513 524

513 534

513 544

513 554

513 564

513 574

Z1 Z2

N1 N2

A2

C2

98

P2

Extension terminals

Auxiliary switch "a"

Auxiliary switch "b"

Motor charging

Charged signal (Normal open)

Voltage Input terminal of UVT

Trip terminal of UVT (Remote trip)

Closing coil

Shunt trip

OCR alarm

Power supply for ETR

FG of power supply (FG:Frame Ground)

Alarm reset (Trip cause LED, alarm contact)

Alarm contact for LTD Trip

Alarm contact for STD or INST Trips

Alarm contact for Ground fault, Earth leakage trips or 2nd Pre-alarm contact

Pre-alarm contact

Temperature alarm contact

Error alarm contact

For external ZCT

For Neutral CT

For external display DP2

For Interface unit

For VT unit

Fig. 32

CC

M

UVT

AX

AL

CLS

SBC

CL

Accessory Symbols

SHT Shunt tripping device

Closing coil

Motor(Motor charging device)

UVT coil

Auxiliary switch

OCR alarm switch

Charge limit switch

Shorting b-contact

Cell switch

Internal wiring

External wiring (user's wiring)

Control circuit connecter (drawout type)

51

+

41

+

31

+

21

+

11

+

53

+

43

+

33

+

23

+

13

+

341

+

331

+

321

+

311

+

Cell switch

52 42 32 22 12 54 44 34 24 14 344 342 334 332 324 322 314 312

Auxiliary switch (“b” contact) Auxiliary switch (“a” contact)

UVT controller voltage application

For 100-120 V AC

For 200-240 V AC

DC ratings

Apply voltage

D2 D1

For 380-460 V AC

Apply voltage

IN2 IN1

External unit

OUT4 OUT3

D2 D1

Control circuit terminal block

Applicable crimp terminal

A A

A = 7.2 mm or less

Applicable crimp-type terminals for M3.5 screws with an outer diameter of 7.2 mm or less.

(Wire size 1.25 mm 2 to 2.0 mm 2 )

Cell switch

˜

˜

For the drawout type, the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5mm.

When a coil load is connected in the same control circuit as the ETR, surge absorbers are required to absorb the surge voltage.

˜ OCR alarm (AL)

The contact output of the OCR alarm (Standard type AL) is the one-pulse output and the output time is 30~50ms.

For this reason, this output needs self-holding circuit.

˜ For Power supply type P3 and P4, the high sensitive relay used in contact output may cause the chattering noise (wrong output of 1ms level) during ON and OFF operation, depending on the

Panel placing condition. When it is used in the quick responsive sequence, the filter circuit of a few milli-second (ms) should be provided or the double reading sampling should be implemented.

˜

˜

Closing coil (CC)

As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.

Inserting AXb will cause anti-pumping function to be ineffective.

Under voltage trip device (UVT)

Use the switch that can open and close 150V DC, 0.5A for remote trip.

Remote trip terminal has short bar at shipment, so remove it before using this function.

Disconnect the voltage input wires during dielectric testing of main circuit.

˜ Since some terminals are polarized, the wiring should be done correctly as the polarity shown in the wiring diagram when the control voltage is DC. Auxiliary switch (AX) Standard type has no polarity.

˜ Alarm reset (Terminal: RS1 and RS2 ) is available only for Power supply type P3, P4 and P5.

For Power supply type P1 and P2, it can not be reset from the Control circuit terminal block ( RS1 and RS2 ).

˜ 513 574 P3 P4

˜ FG (Terminal: P4 ) is the protective earth for power supply (Terminal: P1 , P2 ).

It is recommended to use this terminal to reduce surge (M8 screw required).

˜ Shorting b-contact (SBC)

SBC can be provided for all AX b contacts. At the time of shipment from factory, SBC is already connected to control circuit terminal block. Only one more crimp terminal can be added on contact, overlapping with SBC’s contact on Terminal: 11 ~ 51 .

* The wiring diagram below shows a fully equipped model.

L1 L2 L3 N

Terminals for extension RS1

Wiring length

2 m or less

RS2

Control power supply

513 P1

+

P2 97 C1

+

A1

+

See the figure below for wiring.

+ +

D2 D1 413 U1

+

Electronic trip relay

(ETR)

Reset circuit Power supply circuit

Alarm contacts

(Power supply type P3 ~ P5 only)

SHT CC

UVT

M

Breaker

Main circuit

N1 N2 Z1 Z2 P4

(

M8 screw

)

NCT ※ ZCT ※

※ Voltage forbid to be applied.

FG

Dielectric test forbidden

574 564 554 544 534 524 98 C2 A2 DT2 DT1 414 U2

Shorting bar

Push button for tripping

Wiring length

2 m or less

Electronic trip relay

Control power supply circuit/ alarm contact

OCR alarm

Electric operation circuit

Terminal description

13 14 ~ 53 54

11

U1

12

U2

~ 51 52

413 414

D1 D2

DT1 DT2

A1

C1

97

P1

P4

RS1 RS2

513 524

513 534

513 544

513 554

513 564

513 574

Z1 Z2

N1 N2

A2

C2

98

P2

Extension terminals

Auxiliary switch "a"

Auxiliary switch "b"

Motor charging

Charged signal (Normal open)

Voltage Input terminal of UVT

Trip terminal of UVT (Remote trip)

Closing coil

Shunt trip

OCR alarm

Power supply for ETR

FG of power supply (FG:Frame Ground)

Alarm reset (Trip cause LED, alarm contact)

Alarm contact for LTD Trip

Alarm contact for STD or INST Trips

Alarm contact for Ground fault, Earth leakage trips or 2nd Pre-alarm contact

Pre-alarm contact

Temperature alarm contact

Error alarm contact

For external ZCT

For Neutral CT

For external display DP2

For Interface unit

For VT unit

CC

M

UVT

AX

AL

CLS

SBC

CL

Accessory Symbols

SHT Shunt tripping device

Closing coil

Motor(Motor charging device)

UVT coil

Auxiliary switch

OCR alarm switch

Charge limit switch

Shorting b-contact

Cell switch

Internal wiring

External wiring (user's wiring)

Control circuit connecter (drawout type)

51

+

41

+

31

+

21

+

11

+

53

+

43

+

33

+

23

+

13

+

341

+

331

+

321

+

311

+

Cell switch

52 42 32 22 12 54 44 34 24 14 344 342 334 332 324 322 314 312

Auxiliary switch (“b” contact) Auxiliary switch (“a” contact)

UVT controller voltage application

For 100-120 V AC

For 200-240 V AC

DC ratings

Apply voltage

D2 D1

For 380-460 V AC

Apply voltage

IN2 IN1

External unit

OUT4 OUT3

D2 D1

Control circuit terminal block

Applicable crimp terminal

A A

A = 7.2 mm or less

Applicable crimp-type terminals for M3.5 screws with an outer diameter of 7.2 mm or less.

(Wire size 1.25 mm 2 to 2.0 mm 2 )

Cell switch

˜

˜

For the drawout type, the cables should have the length which allow the control circuit terminal block to be moved to the left or right by 5mm.

When a coil load is connected in the same control circuit as the ETR, surge absorbers are required to absorb the surge voltage.

˜ OCR alarm (AL)

The contact output of the OCR alarm (Standard type AL) is the one-pulse output and the output time is 30~50ms.

For this reason, this output needs self-holding circuit.

˜ For Power supply type P3 and P4, the high sensitive relay used in contact output may cause the chattering noise (wrong output of 1ms level) during ON and OFF operation, depending on the

Panel placing condition. When it is used in the quick responsive sequence, the filter circuit of a few milli-second (ms) should be provided or the double reading sampling should be implemented.

˜

˜

Closing coil (CC)

As CC is one-pulse driven, it is not necessary to insert AXb for burning prevention purposes.

Inserting AXb will cause anti-pumping function to be ineffective.

Under voltage trip device (UVT)

Use the switch that can open and close 150V DC, 0.5A for remote trip.

Remote trip terminal has short bar at shipment, so remove it before using this function.

Disconnect the voltage input wires during dielectric testing of main circuit.

˜ Since some terminals are polarized, the wiring should be done correctly as the polarity shown in the wiring diagram when the control voltage is DC. Auxiliary switch (AX) Standard type has no polarity.

˜ Alarm reset (Terminal: RS1 and RS2 ) is available only for Power supply type P3, P4 and P5.

For Power supply type P1 and P2, it can not be reset from the Control circuit terminal block ( RS1 and RS2 ).

˜ 513 574 P3 P4

˜ FG (Terminal: P4 ) is the protective earth for power supply (Terminal: P1 , P2 ).

It is recommended to use this terminal to reduce surge (M8 screw required).

˜ Shorting b-contact (SBC)

SBC can be provided for all AX b contacts. At the time of shipment from factory, SBC is already connected to control circuit terminal block. Only one more crimp terminal can be added on contact, overlapping with SBC’s contact on Terminal: 11 ~ 51 .

E-33

Technical notes

Arc space

When a short circuit current is interrupted, hot gas blows out from the exhaust port of the arc-extinguishing chamber.

Provide a clearance as shown in Fig. 34.

For the drawout type, ensure appropriate clearance (dimension B) to avoid pinching a finger during the drawout operation.

※ For the fixed type, maintenance can be performed with the clearance shown in Fig. 34.

Electric equipment, device, or screen, etc.

Panel

Table 34 Clearance dimensions

Model

Applied circuit voltage

A

Fixed type

B

C

D

A

Drawout type

B

C

D

AE630-SW ~ AE3200-SW

AE2000-SWA, AE4000-SWA

600 V AC or less

(Note1) 0

660 V, 690 V AC

(Note1) 100

(Note3)

(Note2)

50

162

50

0

(Note3)

(Note2)

50

240

50

(Note3)

(Note2)

(Note3)

(Note2)

50

162

50

100

50

240

50

(mm)

AE4000-SW ~

AE6300-SW

690 V AC or less

(Note1) 200

(Note3) 50

-

200

200

(Note3) 50

-

(Note2) 200

Side board

Note 1: To inspect the arc-extinguishing chamber and main contacts,

300 mm or more is required.

Note 2: Dimension D is the wiring space from the control circuit terminal block.

Note 3: When a mechanical interlock (MI) or door interlock (DI) is being used, dimension B needs to be long enough to install such devices.

Fig. 34

Reverse connection

Line and Load are not defined on the Main circuit terminals.

Therefore, reverse connection is available without any limitation.

Performance of withstand voltage

Main circuit (Note 1)

Control circuit

Test points

Between the main circuit live parts and the ground

Between live parts of different polarity poles

Between the power supply and load terminals

Between the main circuit live parts and all the control circuit terminal block

Between all the accessories on the control circuit terminal block (Note 2) and the ground

Between all the electronic trip relays on the control circuit terminal block (Note 3) and the ground

Withstand voltage (AC)

3500 V AC 1 minute

2000 V AC 1 minute

Rated impulse withstand voltage

Uimp

12 kV

6 kV (Note 4)

4 kV

Note 1: When testing the dielectric strength with a UVT attached, remove the wiring on the voltage input terminals (D1 and D2).

(When the UVT rating is 380-460 V AC, remove the wiring on the external unit input terminals (IN1, IN2).)

Note 2: Terminals of accessories AX/HAX, MD, UVT, CC, SHT, and AL

Note 3: Electronic trip relay terminals (P1, P2, 513, 524, 534, 544, 554, 564, 574)

Note 4: This is 4 kV for the AE4000-SW ~ AE6300-SW drawout type.

Note 5: Terminals N1, N2, Z1, Z2, RS1, RS2, and P4 of the control circuit terminal block are forbidden for dielectric testing.

E-34

1. Standard operation environment

The standard operation environment is an environment where all of the following conditions are met. Unless otherwise specified, use the AE Series air circuit breaker in the following environment.

① Standard ambient temperature

Use in the range of +40 °C max. and -5 °C min. However, the average temperature over 24 hours must not exceed

+35 °C.

② Altitude: 2000 m (6600 feet) or less.

③ Environmental conditions

The air must be clean with the max. temperature of

+40 °C and the relative humidity of 85% or less, and without condensation.

Do not use and store in an atmosphere with corrosive gas, such as sulfide gas and ammonia gas.

(H 2 S 0.01 ppm or less, SO 2 0.05 ppm or less, NH 3 0.25 ppm or less)

④ Installation condition

Install the AE Series air circuit breaker in accordance with the instructions on the catalog and the instruction manual.

⑤ Guideline for replacement

Expected product life is 15 years in the standard operation environment.

Time of replacement is highly influenced by the operation environment. Refer to the inspection and maintenance section of this instruction manual.

Warranty

If any faults or defects (hereinafter “Failure”) found to be the responsibility of Mitsubishi Electric occurs during use of the product within the warranty period, the product shall be repaired at no cost via the sales representative or Mitsubishi

Electric Sales office. However, if repairs are required onsite at domestic or overseas locations, expenses to send an engineer will be charged.

1. Warranty period

The warranty period of the product shall be for twelve

(12) months after the date of purchase or delivery to the designated place. Note that after manufacture and shipment from Mitsubishi Electric, the maximum distribution period shall be six (6) months, and the longest warranty period after manufacturing shall be eighteen (18) months. The warranty period of the repaired parts shall not exceed the warranty period of the original product before repairs.

2. Warranty coverage

(1) The primary failure diagnosis should be performed by users. However, if required by users, Mitsubishi

Electric or Mitsubishi Electric Sales office may be able to perform the diagnosis. In that case, for damages caused by any cause found to be the responsibility of

Mitsubishi Electric, the diagnosis will be performed at no cost. For details, contact a distributor.

(2) The coverage shall be limited to ordinary use within the usage state, usage methods, usage environment, and other conditions which follow the instructions and precautions given in the instruction manual, user’s manual, and caution labels on the product.

(3) Even within the warranty period, repair cost shall be charged for the following cases.

[1] Failure occurring from inappropriate storage or handling, carelessness or negligence by the user.

Failure caused by selection of hardware or software design on the user side.

2. Special operation environment

When the product is used in a condition other than the standard operation environment, its service life may be shorter.

① Special operation environment

Operation with high temperature and high humidity.

Operation in an environment where corrosive gas is present.

② Special ambient temperature

When the ambient temperature exceeds +40 °C,

“uninterrupted current” is reduced.

③ Special altitude

When using the product at an altitude over 2000 m, heat dissipation becomes less. This leads to a reduction of the operation voltage, current capacity, and breaking capacity. The dielectric strength is also lowered by the air pressure. Please contact us for details.

[2] Failure caused by modifications, etc. to the product by the user without any approvals from Mitsubishi

Electric.

[3] In case Mitsubishi Electric product is assembled into a user’s device, failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user’s device is subject to or as necessary by industry standards, had been provided.

[4] Failure that could have been avoided if the maintenance described in the user’s manual has been performed.

[5] Failure caused by external irresistible forces such as fires or abnormal voltages, and failure caused by natural disasters such as earthquakes, lightning, wind and water damages.

[6] Failure caused by reasons unpredictable based on scientific technology standards at the time of shipment from Mitsubishi Electric.

[7] Any other failure found not to be the responsibility of Mitsubishi Electric or that admitted not to be so by the user.

In addition, the warranty applies only to the product delivered. It does not apply to the damage that is caused by the failure of the product.

3. The period to supply the spare parts after discontinuation of production

Mitsubishi Electric shall supply spare parts for five years after discontinuation of production.

After five years, Mitsubishi Electric shall supply spare parts until the spare parts run out of stock.

E-35

Inspection and maintenance

1. Guideline for inspection and replacement ... 36

2. Appearance and structure..................... 37

3. Preparation before inspection ............... 37

4. Inspection .............................................. 37

5. Handling of abnormal operations .......... 40

The maintenance and inspection items and frequency differ by their operation environment. Carefully read the contents of the manual and perform thorough inspection and maintenance.

CAUTION

 Inspection and maintenance should be performed by an expert with the required knowledge. Failure to do so could result in electrical shock.

 Inspection and maintenance should only be performed after turning off the upper breakers and verifying that there is no current flowing. Failure to do so could result in electrical shock.

If the electricity cannot be shut off, wear rubber gloves and shoes, stand on a rubber mat, and use insulated tools. Pay special attention to the insulation between the human body and live parts as the person must approach close to the live parts.

Normal closing/opening operation is safe as the operation parts are insulated with molded material from the live parts.

1. Guideline for inspection and replacement

< Purpose>

Inspection: The purpose of inspecting breakers is to maintain the breaker performance and to prevent accidents caused by aging parts. This can be achieved by finding faulty parts at an early stage and by replacing consumable and wearable parts in a timely manner.

Maintenance: To maintain the breaker’s performance, periodic servicing including lubrication is required. Please contact our service department. Do this once every 2 periodic inspections.

1.1 Guideline for periodic inspection, maintenance and replacement based on the operating period and environment

The initial inspection should be performed once after 1 month of operation. After that, periodic inspections should be performed according to the operation environment.

Guideline for replacement

Standard operation environment

Harsh environment

1

2

1

2

Operation environment Case example

Guideline for inspection

Guideline for maintenance

Environment where air is always clear and dry

Indoors with little debris and dust and no corrosive gas

Environment with little debris and dust and with sulfurous, hydrosulfuric, saline, or high humidity gas present

Environment where average daily ambient temperature exceeds 35 °C

Environment difficult for a person to remain in for a long time, and environment with excessive debris and dust

Electric chamber with dust prevention and air control

In an independent electric chamber, a panel, or a box without dust prevention and air control

Geothermal plant, wastewater treatment plant, or steel, paper, or pulp factory, etc.

Chemical factory, quarry, or mine site, etc.

Once every

2 to 3 years

Once every year

Once every six months

Every 2 periodic inspections

Once every

2 years

Once every year

Approx. 15 years

Approx. 7 ~ 15 years

Approx. 3 ~ 7 years

Approx. 1 ~ 3 years

1.2 Guidelines for inspection and replacement based on the number of operating cycles

Model

Guideline for inspection

Number of operating cycles with rated current*1

Number of operating cycles without rated current*2

With rated current Without current

Product performance

Number of operating cycles (cycles)

Total

AE630-SW

AE1000-SW

AE1250-SW

AE1600-SW

AE2000-SWA

AE2000-SW

AE2500-SW

AE3200-SW

AE4000-SWA

AE4000-SW 3 poles

AE5000-SW 3 poles

AE6300-SW 3 poles

AE4000-SW 4 poles

AE5000-SW 4 poles

AE6300-SW 4 poles

Every 500 cycles

Every 150 cycles

Every 100 cycles

Every 50 cycles

Every 100 cycles

Every 2000 cycles

Every 1000 cycles

Every 500 cycles

5,000

1,500

1,000

500

1,000

20,000

23,500

18,500

19,000

19,500

9,000

4,000

25,000

20,000

10,000

5,000

6 times the rated current

*1 Regardless of the amount of current, when current is turned on and off, it is considered to be an operating cycle with rated current.

*2 Maintenance guideline based on the number of operating cycles is 2000 cycles for all models.

E-36

Overload characteristic

Current

Number of operating cycles

12 cycles

3 cycles

2. Appearance and structure

Refer to P.4 and P.5 of this instruction manual.

3. Preparation before inspection

To perform a normal (initial or periodic) inspection, open

(turn off) the upper breakers and verify that there is no current flowing. For the control circuit, perform an inspection with the power shut off whenever possible, except when inspecting its operation.

CAUTION

When inspecting a drawout type breaker with its breaker pulled out, turn off the breaker. (Refer to P.14.)

ON

4. Inspection

4.1 Initial inspection

4.1.1 Inspection items

After installing a breaker, inspect the following points before applying the current.

Inspection items

1. Cables and conductors securely connected to the main circuit terminals

2. Conductive foreign objects, such as screws, processing chips from the panel processing, or lead wires connected in withstand voltage tests, left around terminals

Criteria

Connected at specified tightening torque (M12 screw: 45 ± 5 N·m)

Free of objects and clean

3. Cracks or breakage on the front cover and the base

4. Flood or condensation on the breaker

No cracks or breakage

No flood or condensation

(1) When measuring the insulation resistance with a 500 V insulation tester, follow the standards described in 4.1.2.

(2) When performing a withstand voltage test, follow the standards described in 4.1.2.

4.1.2 Points and standards for the insulation resistance test and withstand voltage test

(1) Points for the insulation resistance test and withstand voltage test

Test point

Between the main circuit live parts and the ground

Between live parts of different polarity poles

Between the power supply and load terminals

Between the main circuit live parts and the control/operation circuit live parts

Between the control/operation circuit live parts and the ground

Insulation resistance test

ON OFF

™

™

™

™

™

™

™

™

™

Withstand voltage test

ON OFF

™

™

™

™

™

™

™

™

™

(2) Standards for the insulation resistance test and the AC withstand voltage test

Insulation resistance test : Must be 5 MΩ or more (50 MΩ or more for the air circuit breaker alone)

AC withstand voltage test :

Apply for

1 minute

Between the main circuit live parts and the ground

Between live parts of different polarity poles

Between the power supply and load terminals

: 3500 V

: 3500 V

: 3500 V

Between the main circuit live parts and the control/operation circuit live parts : 3500 V

Between the control/operation circuit live parts and the ground : 2000 V

(for the dielectric test forbidden area, follow the specification on the control circuit terminal block nameplate)

CAUTION

When performing the withstand voltage test on the main circuit with the breaker built into a panel, remove the wiring “D1” and “D2” to the UVT controller (for 380-460V AC, the external unit input terminals “IN1” and “ IN2”). Failure to do so could break the UVT controller.

E-37

4.2 Periodic inspection

To prevent accidents and use the breaker stably for a long period of time, we recommend an initial inspection to be performed after 1 month of operation followed by periodic inspections according to the operation environment.

4.2.1 Appearance of the air circuit breaker

Inspection items

1. Debris, dust and soiling

Inspection methods

Visual check

2. Loose connection in the main circuit terminal block

3. Loose connection in the control circuit terminal block

Fasten with a torque wrench.

Fasten with a screwdriver.

4. Cracks, breakage, or deformation of the front cover, base, or control circuit terminal block

Visual check

5. Flooding, immersion in water

6. Extension rail

7. Lost parts

No flooding or water immersion

Visual check

Visual check

Criteria

No debris, dust or dirt attached

Treatment

Vacuum with a vacuum cleaner during periodic inspections, or clean with a dry cloth.

Do not use any solvents, such as thinner, on the front cover and rating nameplates.

Securely tightened

(M12 bolt: 45 ± 5N·m)

Securely tightened

(M3.5 screw: 1.0 ± 0.2N·m)

No cracks, breakage, or deformation

When loose, fasten at the specified torque.

When loose, fasten at the specified torque.

No flooding or water immersion

The rail can be drawn out/inserted smoothly.

None of the screws, nuts, washers, or retaining rings are lost.

If any abnormality is found on the front cover or the control circuit terminal block, please contact your local branch office or agency. When there is an abnormality on the base, replace the breaker.

In case of flooding or water immersion, replace the breaker.

If any abnormality is found with the rail, contact your local branch office or agency.

If any parts are missing, contact your local branch office or agency.

4.2.2 Conductive parts of the main circuit (Appearance)

Inspection items

1. Insulation resistance measurement

Inspection methods

Measure with a 500 V insulation tester

Criteria

5 MΩ or more (50 MΩ or more for a breaker alone). Refer to section

4.1 for measurement points.

2. Soiling of the main circuit terminals and connection conductors

Visual check No debris, dust or soot attached

Treatment

Remove debris and dust with a dry cloth and measure again.

If the insulation does not recover, replace the breaker and the cradle.

Clean with a dry cloth.

4.2.3 Arc-extinguishing chamber

Inspection items

1. Soot and soiling

Inspection methods

Visual check It is clean.

Criteria

2. Breakage

3. Looseness in fixing screws

Visual check

Fasten with a screwdriver.

No breakage

Securely tightened

(M6 screw: 3.25 ± 0.75N·m).

Treatment

Take care not to let debris and dirt enter the arc-extinguishing chamber, and vacuum them with a vacuum cleaner or clean with a dry cloth.

If any abnormality is found, contact your local branch office or agency.

Fasten at the specified torque.

4.2.4 Electronic trip relay

Inspection items

1. Appearance of the electronic trip relay

2. Debris, dust and soiling

3. Operation characteristics of the electronic trip relay

Inspection methods

Visual check

Visual check

Measurement

Criteria

No breakage or deformation of the external area or the setting dial

Treatment

If any breakage or deformation is found, contact your local branch office or agency.

No debris, dust or dirt attached Clean with a dry cloth.

Do not use any solvents, such as thinner.

Values checked with a dedicated field test device (Y-2005) are within reference values.

If the value is outside of the reference values, contact your local branch office or agency.

E-38

4.2.5 Accessory (Please contact us for special accessories other than the ones listed below.)

Inspection items

1. Closing coil (CC)

Shunt trip device (SHT)

Inspection methods

Electric operation

Criteria

Operates fully and smoothly in the rated voltage range.

Treatment

If any abnormality is seen in the operation, contact your local branch office or agency.

2. Auxiliary switch (AX/HAX) Conduction check on AXa and AXb Fully switched over by the opening/closing of the breaker.

If any abnormality is seen in the operation, contact your local branch office or agency.

3. Motor charging device (MD)

4. Undervoltage trip device (UVT)

5. Safety shutter (SST)

6. Cell switch (CL)

7. Mechanical interlock (MI)

Electric operation

Electric operation

Drawout/insert operation

Drawout/insert operation

Interlock function check

Charging is fully completed within the specified time period (5 sec.) and the applicable voltage.

(1)Closing is not available at 45% or less of the rated voltage, and available at 85% or more.

(2)Tripping is available at 45% to 70% of the rated voltage.

(1)No broken parts

If any abnormality is seen in the operation, contact your local branch office or agency.

If any abnormality is seen in the operation, contact your local branch office or agency.

If a broken part is found, contact your local branch office or agency.

(2)Drawout/insert operation can be performed smoothly.

① If the drawout/insert operation is blocked by a broken piece, remove the piece.

② If the drawout/insert operation cannot be performed, contact your local branch office or agency.

(3)The shutter closes in the disconnect/drawout position, and the main circuit junction is not visible.

If the shutter does not shut, contact your local branch office or agency.

Be sure to fully switch over to one of

“DISCONNECT,” “TEST,” or “CONNECT” position.

Gap between the tripping pin and the lever: 0.2 to 1.2 mm

For other installation and adjustment procedures, refer to the MI installation manual.

If any abnormality is seen in the operation, contact your local branch office or agency.

If adjustment is not possible, contact your local branch office or agency.

4.3 Inspection after circuit breaking

If the breaker interrupts off the overload current or short-circuit current, check the periodic inspection items listed in section 4.2.

The breaker can be used again if criteria are met.

Do not close the breaker again until the cause of the accident is confirmed and removed.

When a large fault current is estimated to be interrupted, it is recommended to replace the breaker as soon as possible.

Until replacement, use the breaker but monitor for an abnormal temperature rise or other abnormalities.

Level of breaking current and the treatment methods are listed below for reference.

Level of breaking current

1. 6 times the rated current or less

(LTD, STD range)

2. 70% of the rated breaking current or less

(STD, INST range)

3. Large fault current close to the rated breaking current

Level of damage to the breaker

(1)No abnormality is seen on the Appearance by a visual check.

(2)Wear and soot soiling on main contacts are light.

(1)Soiling on the entire exhaust port, which is caused by soot, etc., is visible.

(2)Main contacts and the arc-extinguishing chamber are lightly damaged.

Treatment

The breaker can be used again.

For the life of the opening/closing operation at the rated current, refer to section 1.2.

The breaker can be used again.

The breaker can be used again if criteria in section

4.2 are met.

(1)Entire exhaust port is heavily soiled by soot, etc.

(2)Main contacts and the arc-extinguishing chamber are heavily damaged.

(1)Immediately replacement is recommended.

(2)If immediately replacement is not possible, use it carefully at the reduced rated current on the condition that criteria in section 4.2 are met.

As an additional test, perform the withstand voltage test on the live parts of the breaker’s main circuit at twice the rated insulation voltage, which is 2000 V, and no abnormality should be found.

However, replace it soon.

(Note) 1. As for the cause of tripping, the level of breaking current can be determined from the trip cause indicator LEDs of ETR.

2. If the level of the fault current cannot be estimated, handle as in point 3 in section 4.3.

E-39

5. Handling of abnormal operations

Types and states of abnormality

1. Unable to close

Faulty behaviors/estimated causes

Investigation/primary treatment

Treatment

Secondary treatment

1. Closing operation cannot be performed.

(1)OFF locking device (CYL. CAL, Padlock) is not released.

(2)Drawout position is inappropriate.

(3)Drawout handle is inserted.

(4)No voltage is applied to UVT.

(5)Closing springs are not charged.

(6)Closing coil does not operate.

(It closes by manual operation.)

Release the OFF locking device (CYL. CAL,

Padlock).

Be sure to be at one of “DISCONNECT,”

“TEST,” or “CONNECT” position.

If closing is still unavailable after the first treatment, contact your local branch office or agency.

Take out the drawout handle.

Apply voltage to UVT.

Charge.

When the UVT is faulty, refer to the section of “UVT does not draw in.”

1. If manual charging is unavailable, contact your local branch office or agency.

2. If motor charging is unavailable, refer to the section of “Motor charging is unavailable.”

1. When no voltage is applied, investigate the operation circuit.

2. When a voltage is applied, check that the connector on the control circuit terminal block is securely inserted.

Contact your local branch office or agency.

2. Closing can be performed.

(1)It trips (OFF) at the same time as closing.

Contact your local branch office or agency.

(2)It turns OFF when charging after closing.

3. ON button is broken.

4. Unable to push the ON button.

External sequence could be the cause.

Contact your local branch office or agency.

Contact your local branch office or agency.

Contact your local branch office or agency.

Investigate the external sequence.

Contact your local branch office or agency.

2. Closing trip occurs when the charging is completed.

3. Unable to open

4. Unable to charge

5. Abnormal temperature rise

1. Unable to open (OFF) even by pressing the OFF button.

2. SHT does not operate.

(It opens by manual operation.)

3. Unable to push the OFF button.

4. OFF button is broken.

1. Manual charging is not possible.

2. Motor charging is unavailable.

3. Motor operates but it does not charge.

1. Connection of the conductors is loose.

Contact your local branch office or agency.

Note 1

1. When no voltage is applied, investigate the operation circuit.

2. When voltage is applied, contact your local branch office or agency.

Contact your local branch office or agency.

Contact your local branch office or agency.

Contact your local branch office or agency.

1. Check the power supply from the control circuit.

2. Check the applicable voltage.

Contact your local branch office or agency.

Fasten them at the specified torque.

2. Main circuit junction is broken.

3. Flowing current is large.

Contact your local branch office or agency.

Lower the flowing current.

Note 1: When drawing out the breaker forcefully, do so after opening upper breakers.

If it is drawn out in the energized state, a major accident could occur.

If the motor does not operate even though the correct voltage is applied, contact your local branch office or agency.

If discoloration of conductors and terminal mold is seen, contact your local branch office or agency.

E-40

Types and states of abnormality

6. Electronic trip relay (ETR)

(1)It trips unnecessarily.

(2)Abnormality in operation characteristics

(3)Abnormality in display functions and contact outputs

7. Drawout/insert operation can be performed.

Faulty behaviors/estimated causes

1. It trips unnecessarily under normal load.

2. It trips unnecessarily when the load is started.

3. Unnecessary operation due to noise/surge

1. It does not trip with overcurrent.

Treatment

Investigation/primary treatment

Check that the load current and ETR are set correctly.

Check the trip characteristic with a field test device.

If the INST and STD settings are overlapping with the start inrush current, raise the settings.

Secondary treatment

If any abnormality is found in the characteristics, contact your local branch office or agency.

If any abnormality is found, contact your local branch office or agency.

Temporarily raise the setting values of ETR.

Connect the control power supply frame ground.

Suppress noise/surge sources. Add noise/surge absorber.

Check that the load current and ETR are set correctly.

Check the trip characteristic with a field test device.

If no abnormality is found on ETR and the cause is unknown, contact your local branch office or agency.

2. The characteristic is not observed during testing with a field test device.

Check the setting value of the field test device.

If any abnormality is found in the characteristics, contact your local branch office or agency.

1. Trip cause LEDs and the pre-alarm contact outputs are not working.

2. Display (DP1, DP2) does not operate.

3. ERR. LED is lit.

4. RUN LED does not turn on.

5. Keypad operation on the display is not available.

Check that the control power supply is correctly applied and check ERR. LED and RUN LED.

For DP2, check the wiring to DP2 from the control circuit terminal block.

If any abnormality is found, contact your local branch office or agency.

Setting check: Check if Ii is set to the “Do not set” position.

Check the light up conditions (lit when the control power supply is applied or when the load current is 10% or more)

Contact your local branch office or agency.

(For the causes, refer to P.21.)

Contact your local branch office or agency.

Check the instruction manual of the display again. Contact your local branch office or agency.

1. Drawout handle cannot be inserted.

2. Drawout handle cannot be rotated.

Insert the drawout handle while pressing the OFF button.

If the drawout handle still cannot be inserted while pressing the OFF button, contact your local branch office or agency.

Check if the lock plate is pushed in.

For AE4000-SW ~ AE6300-SW, check if the fixing bolts on both sides of the cradle are released.

Contact your local branch office or agency.

If it cannot be pushed in, contact your local branch office or agency.

3. The lock plate cannot be pressed in.

Slightly rotate the drawout handles to the right and left, and push the lock plate into a position where it goes in slightly.

Contact your local branch office or agency.

4. Lock plate does not get protruded at

“TEST” and “CONNECT” positions.

5. The lock plate is protruded at “TEST” and

“CONNECT” positions, but the drawout/insert operation does not get locked.

Contact your local branch office or agency.

6. Drawout position indicator does not change. Contact your local branch office or agency.

7. The main circuit junction is broken and interrupting the drawout/insert operation.

8. The control circuit terminal block is broken and interrupting the drawout/insert operation.

Contact your local branch office or agency.

Contact your local branch office or agency.

9. The breaker cannot be inserted.

The breaker stops in the middle of insertion.

Contact your local branch office or agency.

Safety shutter (SST) barrier or unit rod is Contact your local branch office or agency.

broken.

8. Safety shutter (SST) does not operate.

9. Control circuit terminal block is not conducted at “TEST” or

“CONNECT” position.

1. Mold of the control circuit terminal block is broken.

Contact your local branch office or agency.

10. UVT does not draw in.

(Abnormality in the

UVT controller)

11. Auxiliary switch does not turn over.

2. Terminals of the control circuit terminal block are broken.

1. Applied voltage is too low

(or too high).

2. Power supply capacity is not sufficient.

3. Trip terminal DT1 and DT2 are open.

1. Abnormality in auxiliary switch parts

(inside the breaker)

Contact your local branch office or agency.

Check the applied voltage, and change the applied voltage in accordance with the UVT controller specifications.

Contact your local branch office or agency.

Check the power supply capacity.

Short-circuit between the trip terminal DT1 and DT2.

When using a push button switch for tripping, check the push button switch.

Contact your local branch office or agency.

Contact your local branch office or agency.

Contact your local branch office or agency.

E-41

SERVICE NETWORK

According to Registration of Broadcasting and Communication Equipments belonging in “KC”, we inform of the following user guidance.

Applicable models are Electronic type of ACBs, MCCBs and ELCBs.

사용자 안내문

Applicant: MITSUBISHI ELECTRIC AUTOMATION KOREA CO,LTD

Equipment Name : ACB

Country of Origin : JAPAN

Date of Manufacture : Otherwise Noted

Manufactrurer : MITSUBISHI ELECTRIC CORPORATION

사용자 안내문

이 기기는 업무용 환경에서 사용할 목적으로 적합성평가를 받은 기기로서

가정용 환경에서 사용하는 경우 전파간섭의 우려가 있습니다.

E-42

MITSUBISHI Low-Voltage Air Circuit Breakers World Super AE

三菱低压空气断路器 World Super AE

三菱低圧気中遮断器 World Super AE

MODEL AE-SW

型 号

AE-SW

形 名

AE-SW

東京都千代田区丸の内 2-7-3 100-8310

HEAD OFFICE: TOKYO BLDG., MARUNOUCHI, 2-7-3, CHIYODAKU, TOKYO 100-8310.

三菱電機株式会社 福山製作所

〒 720-8647 広島県福山市緑町 1 番 8 号 TEL (084)921-3211 FAX (084)931-4714

MITSUBISHI ELECTRIC FUKUYAMA WORKS

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals