Beckhoff C6915 Fanless Control Cabinet Industrial PC Installation and Operating Instructions
Mainos
Mainos
Installation and Operating instructions for
C6915
Fanless Control Cabinet Industrial PC
Version: 1.3
Date: 2016-06-20
Table of contents
Table of contents
1.1
Notes on the Documentation 3
1.2
Description of safety symbols
4
1.3
Basic safety measures
1.4
Operator’s obligation to exercise diligence
Procedure in the event of a fault
5
6
2.1
Product overview
2.2
Appropriate Use
2.3
Access to the battery and drives 8
2.4
Status-LEDs 9
7
8
2.5
Interfaces 10
Network connection (X102, X103)
DVI-D (Digital Visual Interface) (X108)
Additional plug-in cards (optional)
3.1
Transport and Unpacking 11
3.2
Installation of the PC in the control cabinet 12
Preparation of the control cabinet
3.3
Power supply of the Industrial PC
Beckhoff power supply technology
13
C6915 1
Table of contents
3.4
Connecting the Industrial PC
Check voltage rating and connect
4.1
Switching the Industrial PC on and off
Shutting down and switching off
First switching on and driver installation
4.2
Servicing and maintenance
20
Replacing the Battery on the Motherboard 20
19
4.3
Emergency procedures
4.4
Shutting down
20
20
5 UPS Software Components (optional)
5.1
Installation on the PC
5.2
Help files
21
21
18
9.1
Beckhoff Support and Service
Beckhoff branches and partner companies
9.2
Approvals for USA and Canada
9.3
FCC Approvals for the United States of America
9.4
FCC Approval for Canada
26
27
27
27
2 C6915
Foreword
1 Foreword
1.1 Notes on the Documentation
This description is only intended for the use of trained specialists in control and automation engineering who are familiar with the applicable national standards. It is essential that the following notes and explanations are followed when installing and commissioning these components.
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
1.1.1 Liability Conditions
The documentation has been prepared with care. The products described are, however, constantly under development. For that reason the documentation is not in every case checked for consistency with performance data, standards or other characteristics. In the event that it contains technical or editorial errors, we retain the right to make alterations at any time and without warning. No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
All pictures shown in the documentation are exemplary. Illustrated configurations can differ from standard.
1.1.2 Trademarks
Beckhoff
®
, TwinCAT
®
, EtherCAT
®
, Safety over EtherCAT
®
, TwinSAFE trademarks of and licensed by Beckhoff Automation GmbH.
Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners.
®
and XFC
®
are registered
1.1.3 Patent Pending
The EtherCAT Technology is covered, including but not limited to the following patent applications and patents: EP1590927, EP1789857, DE102004044764, DE102007017835 with corresponding applications or registrations in various other countries.
The TwinCAT Technology is covered, including but not limited to the following patent applications and patents: EP0851348, US6167425 with corresponding applications or registrations in various other countries.
1.1.4 Copyright
©
Beckhoff Automation GmbH & Co. KG.
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express authorization are prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.
1.1.5 State at Delivery
All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.
1.1.6 Delivery conditions
In addition, the general delivery conditions of the company Beckhoff Automation GmbH & Co. KG apply.
C6915 3
Foreword
1.2 Description of safety symbols
The following safety symbols are used in this operating manual. They are intended to alert the reader to the associated safety instructions.
Acute risk of injury!
DANGER
If you do not adhere the safety advise adjoining this symbol, there is immediate danger to life and health of individuals!
Risk of injury!
WARNING
If you do not adhere the safety advise adjoining this symbol, there is danger to life and health of individuals!
Hazard to individuals!
CAUTION
If you do not adhere the safety advise adjoining this symbol, there is obvious hazard to individuals!
Hazard to devices and environment
Attention
If you do not adhere the notice adjoining this symbol, there is obvious hazard to materials and environment.
Note or pointer
This symbol indicates information that contributes to better understanding.
Note
4 C6915
Foreword
1.3 Basic safety measures
Before the Industrial PC is switched off, software that is running must be properly closed.
Otherwise it is possible that data on the storage medium is lost. Please read the section
Switch off all parts of the equipment, then uncouple the fieldbus
Attention
Before opening the housing, and whenever the Industrial PC is not being used for control purposes (such as during functional checks after a repair), all parts of the equipment must first be switched off, after which the Industrial PC is to be disconnected from the equipment.
Pulling out the fieldbus connection plug uncouples the PC (optional).
Items of equipment that have been switched off must be secured against being switched on again.
The Industrial PC’s power supply unit must be supplied with 24 V
DC
.
Attention
Do not exchange any parts when under power
When components are being fitted or removed, the supply voltage must be switched off.
Fitting work on the Industrial PC can result in damage:
• if metal objects such as screws or tools fall onto operating circuit boards.
• if connecting cables internal to the PC are removed or inserted during operation.
• if plug-in cards are removed or inserted when the PC is switched on.
C6915 5
Foreword
1.4 Operator’s obligation to exercise diligence
The operator must ensure that
• the product is only used as intended (see chapter
• the product is in a sound condition and in working order during operation
• the product is operated, maintained and repaired only by suitably qualified and authorized personnel
• the personnel is instructed regularly about relevant occupational safety and environmental protection aspects, and is familiar with the operating manual and in particular the safety notes contained herein
• the operation manual is in good condition and complete, and always available for reference at the location of the product.
Only trained persons may open the Industrial PC housing
Attention
The operator is responsible for ensuring that only trained electrical staff opens the housing of the Industrial PC.
1.4.1 National regulations
Depending on the type of machine and plant in which the Industrial PC is used, national regulations governing the controllers of such machines will apply, and must be observed by the operator. These regulations cover, amongst other things, the intervals between inspections of the controller. The operator must initiate such inspections in good time.
1.4.2 Procedure in the event of a fault
In the event of faults at the Industrial PC, the list in the section
can be used to determine the measures to be taken.
1.4.3 Operator requirements
Anyone who uses the Industrial PC must have read these operating instructions and must be familiar with all the functions of the software installed on the Industrial PC to which he has access.
6 C6915
2 Product Description
2.1 Product overview
Product Description
C6915 | Fanless control cabinet Industrial PC
The C6915 Industrial PC is designed for control cabinet installation. The compact housing is equipped with a 3½-inch motherboard with Intel® Atom™ with up to four cores. All PC connections are located at the front of the housing. The Industrial PC is cooled by internal cooling fins without a fan, allowing operation at up to 55 °C, with installed hard disk up to 45 °C.
The Industrial PC offers the following benefits:
• Fanless Industrial PC for space-saving control cabinet installation
• mounting sheet at the rear wall or at the side
• all connectors on the front
• status LEDs
• lithium battery accessible behind the front flap
• protection class IP 20
• operating temperature 0…55 °C.
C6915 7
Product Description
2.2 Appropriate Use
The C6915 Industrial PC is designed for mounting in control cabinets for machine and plant engineering applications.
Risk of explosion!
The Industrial PC must not be used where there is a risk of explosion.
Danger
2.3 Access to the battery and drives
Access to the battery, the
Flash storage medium and the hard disk (optional)
2
3
8
1
Opening the front flap (1) allows access to the battery (2) and the Flash storage medium (3). Optionally the Industrial PC can be fitted with a second Flash medium or only with one hard disk.
Danger of Explosion!
WARNING
Replace battery only with the identical type or an alternative type recommended by the manufacturer. Notice correct polarity!
Polarity of the battery:
+ pole - pole
C6915
2.4 Status-LEDs
The Status-LEDs (2) are located near the power supply connector (X101):
Product Description
2
3
Description of the Status-LEDs:
1 PWR (Power):
2 FB (Fieldbus):
HDD (Hard disk): green off red blue blue/ red blinking green green/ red blinking red
Industrial PC is busy
Industrial PC is off
TwinCAT Stop Mode
TwinCAT Configuration Mode
TwinCAT Config (Fieldbus Error)
TwinCAT Run Mode
TwinCAT Run (Fieldbus Error)
Access to a memory device
X101
C6915 9
Product Description
2.5 Interfaces
X108
X106
X107
X104
X105
X103 X102 X101
2.5.1 Power Supply (X101)
The power supply for the Industrial PC is established via the socket (X101).
2.5.2 Network connection (X102, X103)
The RJ-45 connectors (X102, X103) allow the PC to be connected to a 10/100/1000 BASE-T Local Area
Network (LAN).
2.5.3 USB-Interfaces (X104 – X107)
The four USB interfaces (X104 – X107) are used for connecting peripheral devices with USB connection.
USB2.0 standard is supported.
2.5.4 DVI-D (Digital Visual Interface) (X108)
The DVI connection (X108) is used for transferring the video signal. DVI-D standard is supported.
2.5.5 Additional plug-in cards (optional)
There is a type plate on the top of the Industrial PC which provides information about the hardware configuration of the Industrial PC at the time it was supplied.
2.5.6 Earthing connection
The earthing connection is located at the mounting plate of the Industrial PC .
10 C6915
Installation
3 Installation
3.1 Transport and Unpacking
The specified storage conditions must be observed (see chapter
3.1.1 Transport
Despite the robust design of the unit, the components are sensitive to strong vibrations and impacts.
During transport, the Industrial PC should be protected from excessive mechanical stress. Therefore, please use the original packaging.
Danger of damage to the unit
Attention
If the device is transported in cold weather or is exposed to extreme variations in temperature, make sure that moisture (condensation) does not form on or inside the device.
Prior to operation, the unit must be allowed to slowly adjust to room temperature. Should condensation occur, a delay time of approximately 12 hours must be allowed before the unit is switched on.
3.1.2 Unpacking
Proceed as follows to unpack the unit:
2. Do not discard the original packaging. Keep it for future relocation.
3. Check the delivery for completeness by comparing it with your order.
4. Please keep the associated paperwork. It contains important information for handling the unit.
5. Check the contents for visible shipping damage.
6. If you notice any shipping damage or inconsistencies between the contents and your order, you should notify Beckhoff Service.
C6915 11
Installation
3.2 Installation of the PC in the control cabinet
The C6915 Industrial PC is designed for mounting in control cabinets for machine and plant engineering applications.
The ambient conditions specified for operation must be observed (see chapter
3.2.1 Preparation of the control cabinet
Four holes for the fixing bolts have to be provided in the control cabinet according to the dimensions of the PC (see chapter
Note
Circulation of air
When the unit is installed in an enclosure, adequate space for ventilation and for opening the PC must be provided.
The clearance above and below the housing must be at least 5 cm in order to ensure adequate ventilation of the PC.
Avoid extreme environmental conditions
Attention
Extreme environmental conditions should be avoided as far as possible. Protect the PC from dust, moisture and heat.
The ventilation slots of the PC must not be covered.
3.2.2 Earthing measures
Earthing connections dissipate interference from external power supply cables, signal cables or cables to peripheral equipment.
Establish a low-impedance connection from the earthing point on the PC housing to the central earthing point on the control cabinet wall, in which the computer is being installed. The earthing connection is located at the mounting plate of the Industrial PC.
12 C6915
Installation
3.3 Power supply of the Industrial PC
The Industrial PC is optionally fitted with a 24 V
DC
power supply unit .
Note
Uninterruptible power supply (UPS)
When the Industrial PC is provided with a power supply unit with integrated UPS (order option) you can realize an uninterruptible power supply (UPS) using the battery pack
C9900-U330 or C9900-U332.
Danger of Explosion!
WARNING
Danger of Explosion if using other battery packs!
3.3.1 Beckhoff power supply technology
Schematic diagram of power supply unit wirings
Industrial PCs equipped with a UPS are in actual use frequently switched off by simply turning off the supply voltage. In this case the PC shuts down via the battery. However, over time this reduces the service life of the battery.
The new Beckhoff power supply technology approach addresses this problem and now offers the user the option of switching the PC off without the need for using the battery, thereby reducing the load on the battery.
In addition to the main switch this innovative solution uses an ON/OFF switch for the machine. Basically, the main switch remains switched on and provides the power supply for the PC during shutdown. Via the
PC ON-input of the power supply the PC gets the command to shut down the operating system.
Once the PC has shut down, the PC power supply unit sets the Power Status-output (P-S) to 0, what indicates that the process is complete and that the main voltage can be switched off. This can be done manually via a signal lamp connection or via a contactor. With this solution the main switch generally only has to be switched off if the control cabinet has to be opened. The battery will only be used in the event of
C6915 13
Installation a power failure.
In order to maintain a screen display for the Industrial PC in the event of a power failure, the power supply unit is equipped with a UPS output 27 V / 1.4 A for connecting a Control Panel with a display dimension up to 19 inches. This enables a power failure to be visualized and displayed to the user. Once the PC has shut down, the UPS output is switched off.
For a detailed functional description please refer to section
3.3.1.1 Pin assignment of the connector
The power supply and the external circuit for switching the Industrial PC on and off are connected via the
8-pole plug connector.
1 2 3 4 5 6 7 8
Pin assignment for connecting the switch, the power supply and the battery pack (optional):
Pin Function
1 -
2 +
Battery Pack
(with UPS only)
3 UPS+ (Output)
4
5 -
6 +
7 PC_ON
24 V DC Power Supply
8 Power-Status
14 C6915
Installation
3.3.2 Fitting the cable
Fit the cables for the power supply of the Industrial PC, the connection of the battery pack as well as the connection of the power-switch in accordance with the wiring diagram, using the included material for assembling the connectors.
3.3.2.1 Material for assembling the connectors
Plug connector 8-pole, Strain relief housing with lacing cord
3.3.2.2 Assembling the connectors
The connector is specified for 16 A and can lift conductive cross-sections until 1.5 mm
2
.
So the connector is fitted to the cable:
1. Strip insulation from the cable ends (Length of stripped conductor is 8 – 9 mm).
2. Screw together the cable ends in the 8-pole plug connector in accordance with wiring diagram.
Thread the lacing cord into that lower part of the strain relief housing.
Put the plug connector into that lower part of the strain relief housing.
Tighten the lacing cord and pinch off the plastic strap.
Fix the upper part of the strain relief housing by snapping it onto the lower part.
C6915 15
Installation
3.3.3 Connecting Power Supply
The external wiring consists of the connection of the power supply, the battery pack (optional) and the connection of customized components for shutting down the PC.
3.3.3.1 Cable Cross Sections
For the connection of the power supply, wiring with a cable-cross-section of 1.5 mm
2
must be used.
With bigger distances between voltage source and PC, you take the voltage drop as a function of the cable-cross-section as well as voltage fluctuations of your distribution voltage into account, so that is secured that the voltage doesn't fall under 22 V at the power supply.
Insert fuse
Attention
The power supply must be protected with maximum 16 A.
3.3.3.2 Configuration for shutting down the PC
The connections for shutting down the Industrial PCs are established via the PC_ON input and the Power
Status output.
3.3.3.3 PC_ON and Power Status functions
• If the PC_ON input is connected to 24 V via a switch, the PC shuts down according to the rules.
The PC_ON signal is inverted, i.e. the PC shuts down if the 24 V connection is live.
• If the PC_ON input is NOT connected by the user, the PC can be booted in the familiar way by connecting the supply voltage and shut down via the battery by switching off the supply voltage.
Service life of the rechargeable battery
Attention
This procedure significantly reduces the service life of the rechargeable battery and should therefore not be used.
• Once the PC has shut down, the Power Status output is switched from 24 V to 0 V. Via this output a signal lamp can be connected or a contactor for de-energizing the whole system. The maximum load for the Power Status output is 0.5 A and a suitable fuse should be provided.
In order to maintain a screen display for the PC in the event of a power failure, the power supply unit is equipped with a UPS output for connecting a Control Panel. The maximum load for the output is 1.4 A.
3.3.3.5 UPS output function
• The 24 V DC connection at the UPS output is live even after a power failure. The maximum load is 1.4 A.
• Once the PC has been de-energized via the UPS software, the UPS output is switched to 0 V.
Any connected panel is thus switched off, and total discharge of the rechargeable battery is prevented.
16 C6915
Wiring according to the wiring diagram (the circuit of PC_ON and Power-Status is symbolical):
Wiring diagram external switch and power supply
Installation
Note
Connection of the Battery Pack and UPS Output
Connection of the Battery Pack and UPS Output only in combination with integrated
UPS (order option).
C6915 17
Installation
3.4 Connecting the Industrial PC
The mains plug must be disconnected
Attention
The power supply plug must be withdrawn!
Please read the documentation for the external devices prior to connecting them!
During thunderstorms, plug connector must neither be inserted nor removed!
When disconnecting a plug connector, always handle it at the plug. Do not pull the cable!
3.4.1 Connecting cables
The connections are located at the rear side of the Industrial PC and are documented in the
When connecting the cables to the Industrial PC, proceed according to the following sequence:
• Switch off all the devices that are to be connected.
• Disconnect all the devices that are to be connected from the power supply.
• Connect all the cables between the Industrial PC and to the devices that are to be connected.
• Connect all data transfer cables (if present) to the appropriate plug-in receptacles of the data/ telecommunication networks.
• Reconnect all devices to the power supply.
3.4.2 Check voltage rating and connect
Fitted with a 24 V
DC
power supply unit:
1. Check that the external power supply is providing the correct voltage.
2. Insert the power supply cable that you have assembled into the Industrial PC's power supply socket. Then connect it to your external 24 V power supply.
Use same type of rechargeable battery
Attention
If a 24 V UPS is installed, the same type of rechargeable battery must be used.
18 C6915
Operating Instructions
4 Operating Instructions
4.1 Switching the Industrial PC on and off
4.1.1 Switch on
The Industrial PC does not have its own mains switch. The Industrial PC will start when the equipment is switched on, or when it is connected to the power supply.
4.1.2 Shutting down and switching off
When the plant is switched off, or when it is disconnected from its power supply, the Industrial PC will be switched off.
Control software such as is typically used on Industrial PCs permits various users to be given different rights. A user who may not close software may also not switch the Industrial PC off, since data can be lost from the hard disk by switching off while software is running.
First shut down, then switch off the PC
Attention
If the Industrial PC is switched off as the software is writing a file to the memory drive, the file will be destroyed. Control software typically writes something to the memory drive every few seconds, so that the probability of causing damage by switching off while the software is running is very high.
Switch off power supply
Attention
When you have shut down the Industrial PC, you have to switch off power supply for at least 10 seconds before rebooting the system.
After resetting power supply the PC will start booting automatically.
4.1.3 First switching on and driver installation
When you switch on the Industrial PC for the first time, the pre-installed operating system (optional) will be started. In this case, all the required drivers for any additional, optional hardware components ordered with the PC will already have been installed.
If the PC was ordered without operating system, you have to install the operating system and the driver software for any auxiliary hardware yourself. Please follow the instructions in the documentation for the operating system and the additional devices.
C6915 19
Operating Instructions
4.2 Servicing and maintenance
4.2.1 Cleaning of the Industrial PC
Disconnect power supply
DANGER
Switch off the Industrial PC and all connected devices, and disconnect the Industrial
PC from the power supply.
The device can be cleaned with a soft, damp cleaning cloth. Do not use any aggressive cleaning materials, thinners, scouring material or hard objects that could cause scratches.
4.2.2 Maintenance
The Industrial PC is maintenance-free.
4.2.3 Replacing the Battery on the Motherboard
A used battery on the motherboard has to be replaced. See also chapter
Access to the battery and drives
Danger of Explosion!
WARNING
Replace battery only with the identical type or an alternative type recommended by the manufacturer. Notice correct polarity!
The used battery must be disposed of in accordance with national electronics scrap regulations.
4.3 Emergency procedures
In case of fire, the Industrial PC should be extinguished with powder or nitrogen.
4.4 Shutting down
4.4.1 Disposal
Observe national electronics scrap regulations
Observe the national electronics scrap regulations when disposing of the device.
Note
In order to dispose of the device, it must be removed and fully dismantled:
• Housing components (polycarbonate, polyamide (PA6.6)) are suitable for plastic recycling
• Metal parts can be sent for metal recycling
• Electronic parts such as disk drives and circuit boards must be disposed of in accordance with national electronics scrap regulations.
20 C6915
UPS Software Components (optional)
5 UPS Software Components (optional)
For operating the power supply unit as a UPS, the UPS driver software and the associated UPS driver must be installed on the Industrial PC.
On delivery of the Beckhoff Industrial PC with operating system the software is already installed. Should the software not be installed on your PC, the drivers can be installed from the driver CD provided.
5.1 Installation on the PC
To install the UPS driver software, execute file Beckhoff_UPS_vx.xx.xx.exe from the subdirectory of
UPS\… from the CD provided on the Industrial PC (Driver-archive for the Industrial-PC, C9900-S700xxxx).
The program is self-extracting and will guide the user through the installation routine.
5.2 Help files
The driver software comes with a detailed help function.
The help files can be called up either directly from the configuration register by clicking the Help button, or under via Start > Programs > Beckhoff > UPS software components.
C6915 21
Troubleshooting
6 Troubleshooting
Fault Cause
Nothing happens after the Industrial
PC has been switched on
No power supply to the Industrial
PC
Other cause
The Industrial PC does not boot fully
Computer boots, software starts, but control does not operate correctly
Setup settings are incorrect
Other cause
Cause of the fault is either in the software or in parts of the plant outside the Industrial PC
Memory device access error Faulty device
The Industrial PC functions only partially or only part of the time, e.g. no or dark picture, but disk drive responds when switching on
Defective components in the
Industrial PC
Procedure
Check power supply cable
Call Beckhoff Service
Check the setup settings
Call Beckhoff Service
Call the manufacturer of the machine or the software
Call Beckhoff Service
Call Beckhoff Service
22 C6915
Assembly dimensions
7 Assembly dimensions
The following pages show diagrams of the Industrial PC, with dimensions in mm.
Industrial PC C6915, Mounting back
Notice mounting orientation
Warning
The assembly of the unit must take place with the orientation diagrammed here.
C6915 23
Assembly dimensions
Industrial-PC C6915-C9900-M, Mounting side
Notice mounting orientation
Warning
The assembly of the unit must take place with the orientation diagrammed here.
24 C6915
Technical Data
8 Technical Data
Danger
Risk of explosion!
Do not use the Industrial PC in areas of explosive hazard!
Product name
Dimensions (B x H x T)
Weight
Supply voltage
Power consumption
C6915
47 x 157 x 116 mm (without mounting plate)
1.25 kg (basic configuration)
22–30V V
DC
(24 V
DC
power supply unit)
C6915-0000: app. 32 W (basic configuration)
C6915-0010: app. 14 W (basic configuration)
Interfaces
Protection class
Shock resistance
(Sinusoidal vibration)
1 x DVI-D
2 x RJ-45 10/100/1000 BASE-T Ethernet
4 x USB 2.0
IP20
EN 60068-2-6:
EN 60068-2-27:
10 to 58 Hz:
5 G (~ 50 m/ s
2
0,035 mm
58 to 500 Hz: 0,5 G (~ 5 m/ s
2
)
), duration: 30 ms Shock resistance
(Shock)
EMC compatibility Resistance to interference conforms to EN 61000-6-2
EMC compatibility Emission of interference conforms to EN 61000-6-4
Permissible ambient temperature 0°C to +55°C (operation)
-25°C to +65°C (transport/ storage)
Permissible relative humidity
Transport and storage to 95%, no condensation
The same values for atmospheric humidity and shock resistance are to be observed during transport and storage as in operation. Suitable packaging of the Industrial PC can improve the resistance to impact during transport.
Certifications CE
C6915 25
Appendix
9 Appendix
9.1 Beckhoff Support and Service
Beckhoff and their partners around the world offer comprehensive support and service, making available fast and competent assistance with all questions related to Beckhoff products and system solutions.
9.1.1 Beckhoff branches and partner companies
Please contact your Beckhoff branch office or partner company for local support and service on Beckhoff products!
The contact addresses for your country can be found in the list of Beckhoff branches and partner companies: www.beckhoff.com
. You will also find further documentation for Beckhoff components there.
9.1.2 Beckhoff company headquarters
Beckhoff Automation GmbH & Co. KG
Huelshorstweg 20
33415 Verl
Germany
Phone:
Fax:
E-mail:
Web:
+ 49 (0) 5246/963-0
+ 49 (0) 5246/963-198 [email protected]
http://www.beckhoff.de/
Beckhoff Support
Support offers you comprehensive technical assistance, helping you not only with the application of individual Beckhoff products, but also with other, wide-ranging services:
• world-wide support
• design, programming and commissioning of complex automation systems
• and extensive training program for Beckhoff system components
Hotline:
Fax:
E-mail:
+ 49 (0) 5246/963-157
+ 49 (0) 5246/963-9157 [email protected]
Beckhoff Service
The Beckhoff Service Center supports you in all matters of after-sales service:
• on-site service
• repair service
• spare parts service
• hotline service
Hotline:
Fax:
E-mail:
+ 49 (0) 5246/963-460
+ 49 (0) 5246/963-479 [email protected]
If servicing is required, please quote the project number of your product.
26 C6915
Appendix
9.2 Approvals for USA and Canada
9.3 FCC Approvals for the United States of America
FCC: Federal Communications Commission Radio Frequency Interference Statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Note
Technical modifications
Technological changes to the device may cause the loss of the FCC approval.
9.4 FCC Approval for Canada
FCC: Canadian Notice
This equipment does not exceed the Class A limits for radiated emissions as described in the Radio
Interference Regulations of the Canadian Department of Communications.
C6915 27