OMRON SYSMAC CPM2B Programmable Controller Operation Manual
Below you will find brief information for SYSMAC CPM2B. This compact programmable controller is ideal for building into control equipment. It offers features like synchronized pulse control, high-speed counters, and various communication options (Host Link, 1:1 PC Link, etc.) for easy integration into distributed systems. This manual provides setup and operational instructions.
Advertisement
Advertisement
Cat.No. W371–E1–1
SYSMAC
CPM2B
Programmable Controller
OPERATION MANUAL
SYSMAC CPM2B
Programmable Controller
Operation Manual
Produced February 2000
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 2000
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 CPM2B Features and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 System Configurations
1-3 Structure and Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Board Specifications and Components . . . . . . . . . . . . . . .
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Board Components and their Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 I/O Connector and Terminal Pin Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Design Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Selecting an Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Assembling the CPM2B Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Installing the CPM2B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Wiring and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Memory Areas
4-1 Introduction
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 I/O Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 SR Area
4-4 AR Area
4-5 PC Setup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Error Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Instruction Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 CPM2B Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Alphabetic List by Mnemonic
5-3 Expansion Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Using Programming Devices . . . . . . . . . . . . . . . . . . . . . . .
6-1 Using a Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
22
29
33
77
78
84
106
53
54
55
58
60
64
69
71
72
73
76
35
36
36
38
39
40 xi xii xii xii xiii xiii xv
1
2
6
13 vii
viii
TABLE OF CONTENTS
SECTION 7
Test Runs and Error Processing . . . . . . . . . . . . . . . . . . . .
7-1 Initial System Checks and Test Run Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 CPM2B Test Run Procedure
7-3 Self-diagnostic Functions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-5 Maintenance Inspections
7-6 Battery Replacement
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices
A Standard Models
B Dimensions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
129
133
135
139
113
114
114
115
118
125
126
About this Manual:
This manual describes the installation and operation of the CPM2B and includes the sections described below.
The CPM2B is a compact, high-speed board Programmable Controller (PC) designed for control operations. There are two manuals describing the setup and operation of the CPM2B: The CPM2B Operation
Manual (this manual) and the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual
(W353). (The CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual is referred to as simply the Programming Manual in this manual.)
This manual describes the system configuration and installation of the CPM2B and provides a basic explanation of operating procedures for the Programming Consoles. Read this manual first to acquaint yourself with the CPM2B.
The Programming Manual (W353) provides detailed descriptions of the CPM2B’s programming functions. The SYSMAC Support Software Operation Manuals: Basics and C-series PCs (W247 and W248) provide descriptions of SSS operations for the CPM2B and other SYSMAC C-series PCs. The SYSMAC-
CPT Support Software Quick Start Guide (W332) and User Manual (W333) provide descriptions of ladder diagram operations in the Windows environment. The WS02-CXPC1-E CX-Programmer User Manual
(W361) and the CX-Server User Manual (W362) provide details of operations for the WS02-CXPC1-E
CX-Programmer.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the CP2MB.
Section 1 describes the CPM2B’s special features and functions, shows the possible system configurations, and outlines the steps required before operation. Read this section first when using the CPM2B for the first time. Refer to the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353) for details on programming.
Section 2 provides the technical specifications of the CPM2B Boards and describes the main components of the Boards.
Section 3 provides information on installing and wiring a CPM2B PC. Be sure to follow the directions and precautions in this section when installing the CPM2B in a panel or cabinet, wiring the power supply, or wiring I/O.
Section 4 describes the structure of the PC memory areas and explains how to use them.
Section 5 provides a brief summary of the instruction set. Refer to the CPM1/CPM1A/CPM2A/
CPM2C/SRM1(-V2) Programming Manual (W353) for details on specific instructions.
Section 6 provides information on Programming Console operations.
Section 7 describes procedures for trial CPM2B operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during PC operation.
Appendices provides lists of standard models and Board dimensions.
!
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
PRECAUTIONS
This section provides general precautions for using the Programmable Controller (PC) and related devices.
The information contained in this section is important for the safe and reliable application of the Programmable Controller. You must read this section and understand the information contained before attempting to set up or operate a
PC system.
1 Intended Audience
2 General Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xiii xiii xv xi
Safety Precautions
1
2
Intended Audience
3
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
•
Personnel in charge of installing FA systems.
•
Personnel in charge of designing FA systems.
•
Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!
WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the above-mentioned applications.
3 Safety Precautions
!
WARNING Do not attempt to take any board apart while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not touch any of the terminals, terminal blocks or, for the CPM2B, the CPU board or expansion I/O board while the power is being supplied. Doing so may result in electric shock.
!
WARNING When handling the Memory Backup Battery, never drop, disassemble, distort, short-circuit, heat to a high temperature, or throw into fire. Otherwise the Battery may explode, catch fire, or leak fluid.
!
WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
!
WARNING Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, in order to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents.
xii
Application Precautions
4
5
5
•
Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
•
The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed. As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
•
The PC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
!
WARNING When transferring programs to other nodes, or when making changes to I/O memory, confirm the safety of the destination node before transfer. Not doing so may result in injury.
!
Caution Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, the input signals may not be readable.
!
Caution Tighten the screws on the terminal block to the torque specified in the operation manual. The loose screws may result in burning or malfunction.
Operating Environment Precautions
!
Caution Do not operate the control system in the following places:
•
Locations subject to direct sunlight.
•
Locations subject to temperatures or humidity outside the range specified in the specifications.
•
Locations subject to condensation as the result of severe changes in temperature.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to exposure to water, oil, or chemicals.
•
Locations subject to shock or vibration.
!
Caution Take appropriate and sufficient countermeasures when installing systems in the following locations:
•
Locations subject to static electricity or other forms of noise.
•
Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radioactivity.
•
Locations close to power supplies.
!
Caution The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
Application Precautions
Observe the following precautions when using the PC System.
!
WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.
•
Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
xiii
Application Precautions 5
•
Mounting or dismounting the CPU board or expansion I/O board.
•
Setting switches or rotary switches.
•
Connecting or wiring the cables.
•
Connecting or disconnecting the connectors.
!
Caution Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC. Always heed these precautions.
•
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
•
Construct a control circuit so that power supply for the I/O circuits does not come ON before power supply for the PC. If power supply for the I/O circuits comes ON before power supply for the PC, normal operation may be temporarily interrupted.
•
If the operating mode is changed from RUN or MONITOR mode to PROGRAM mode, with the IOM Hold Bit ON, the output will hold the most recent status. In such a case, ensure that the external load does not exceed specifications. (If operation is stopped because of an operation error (including FALS instructions), the values in the internal memory of the CPU board will be saved, but the outputs will all turn OFF.)
•
Always use the power supply voltage specified in the operation manuals. An incorrect voltage may result in malfunction or burning.
•
Take appropriate measures to ensure that the specified power with the rated voltage is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
•
Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
•
Do not apply voltages to the input terminals in excess of the rated input voltage.
Excess voltages may result in burning.
•
Do not apply voltages or connect loads to the output terminals in excess of the maximum switching capacity. Excess voltage or loads may result in burning.
•
Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunction.
•
When wiring the CPM2B, take countermeasures to prevent wiring cuttings from coming into contact with the product, such as covering the whole product with a dustproof cover. If wiring cuttings adhere to the PCB or circuit elements they may cause short-circuiting.
•
Be sure to perform wiring in accordance with the relevant operation manual.
Incorrect wiring may result in burning.
•
Double-check all the wiring before turning ON the power supply. Incorrect wiring may result in burning.
•
Be sure that the terminal blocks, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
•
Be sure that terminal blocks and connectors are connected in the specified direction with the correct polarity. Not doing so may result in malfunction.
•
Check the user program for proper execution before actually running it on the
PC. Not checking the program may result in an unexpected operation.
•
Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
xiv
EC Directives 6
EC Directives
•
Changing the operating mode of the PC.
•
Force-setting/force-resetting any bit in memory.
•
Changing the present value of any word or any set value in memory.
•
Resume operation only after transferring to the new CPU board the contents of the DM and HR Areas required for resuming operation. Not doing so may result in an unexpected operation.
•
Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables.
•
Do not place objects on top of the cables. Doing so may break the cables.
•
Under no circumstances should batteries be short-circuited between positive
(+) and negative (–) terminals, charged, disassembled, heated, or thrown into fire.
•
When replacing parts, be sure to confirm that the rating of a new part is correct.
Not doing so may result in malfunction or burning.
•
When transporting or storing the CPM2B, cover the circuit boards in antistatic material to protect them from static electricity and maintain the proper storage temperature.
•
Before touching the Unit, be sure to first touch a grounded metallic object in order to discharge any static build-up. Not doing so may result in malfunction or damage.
•
Do not touch the expansion I/O connecting cable while the power is being supplied in order to prevent any malfunction due to static electricity.
•
Do not touch CPM2B circuit boards or the components mounted to them with your bare hands. There are sharp leads and other parts on the boards that may cause injury if handled improperly.
•
When disposing the product, observe local ordinances and regulations.
6
6-1 Applicable Directives
•
EMC Directives
•
Low Voltage Directive
6-2 Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related
EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
Note Applicable EMC (Electromagnetic Compatibility) standards are as follows:
EMS (Electromagnetic Susceptibility): EN61131-2
EMI (Electromagnetic Interference): EN50081-2
(Radiated emission: 10-m regulations)
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to
1,500 VDC meet the required safety standards for the PC (EN61131-2).
xv
EC Directives 6
6-3 Conformance to EC Directives
The CPM2B PCs comply with EC Directives. To ensure that the machine or device in which the CPM2B PC is used complies with EC directives, the PC must be installed as follows:
1, 2, 3...
1. The CPM2B PC must be installed within a control panel.
2. Reinforced insulation or double insulation must be used for the DC power supplies used for the communications and I/O power supplies.
3. CPM2B PCs complying with EC Directives also conform to the Common
Emission Standard (EN50081-2). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. You must therefore confirm that the overall machine or equipment complies with EC Directives.
6-4 Relay Output Noise Reduction Methods
The CPM2B PCs conform to the Common Emission Standards (EN50081-2) of the EMC Directives. However, the noise generated when the PC is switched ON or OFF using the relay output may not satisfy these standards. In such a case, a noise filter must be connected to the load side or other appropriate countermeasures must be provided external to the PC.
Countermeasures taken to satisfy the standards vary depending on the devices on the load side, wiring, configuration of machines, etc. Following are examples of countermeasures for reducing the generated noise.
Countermeasures
(Refer to EN50081-2 for more details.)
Countermeasures are not required if the frequency of load switching for the whole system with the PC included is less than 5 times per minute.
Countermeasures are required if the frequency of load switching for the whole system with the PC included is 5 times or more per minute.
xvi
EC Directives 6
Countermeasure Examples
When switching an inductive load, connect a surge protector, diodes, etc., in parallel with the load or contact as shown below.
Circuit
CR method
Power supply
Diode method
Power supply
Varistor method
Power supply
Current
AC DC
Characteristic
Yes Yes If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset.
If the supply voltage is 24 to 48 V, insert the surge protector in parallel with the load. If the supply voltage is
100 to 200 V, insert the surge protector between the contacts.
No Yes The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load.
This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method.
Yes Yes The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset.
If the supply voltage is 24 to 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to
200 V, insert the varistor between the contacts.
Required element
The capacitance of the capacitor must be 1 to 0.5
µ
F per contact current of
1 A and resistance of the resistor must be 0.5 to 1
Ω
per contact voltage of
1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again.
The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity.
The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value.
The forward current of the diode must be the same as or larger than the load current.
The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the surge protector is applied to electronic circuits with low circuit voltages.
--xvii
SECTION 1
Introduction
This section describes the CPM2B’s special features and functions, shows the possible system configurations, and outlines the steps required before operation. Read this section first when using the CPM2B for the first time.
Refer to the CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2) Programming Manual (W353) for details on programming.
1-1 CPM2B Features and Functions
1-1-1 CPM2B Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1-2 Overview of CPM2B Functions
1-2 System Configurations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-1 CPU Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 Expansion I/O Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-3 Connecting a Programming Console
1-2-4 Support Software
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-5 One-to-one Computer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-6 One-to-N Computer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-7 OMRON PT Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-8 One-to-one PC Link Connections
1-3 Structure and Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 CPU Board Structure
1-3-2 Operating Modes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-3 Operating Mode at Startup
1-3-4 PC Operation at Startup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-5 Cyclic Operation and Interrupts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
11
12
13
8
8
9
6
7
5
6
2
2
13
14
14
15
16
1
CPM2B Features and Functions Section 1-1
1-1 CPM2B Features and Functions
1-1-1 CPM2B Features
The CPM2B PCs are compact Board PCs that can be incorporated easily into control equipment. The PCs are equipped with a variety of advanced features including synchronized pulse control, interrupt inputs, high-speed counters, pulse outputs, and a clock function.
•
The compact Board design is ideal for incorporation into control equipment.
•
The CPU Board itself can handle a wide range of machine control applications, so it is ideal for use as a built-in control unit in control equipment.
•
The CPM2B is equipped with a full complement of communications functions to provide communications with personal computers, other OMRON PCs, and
OMRON Programmable Terminals. These communications capabilities allow the user to design a low-cost distributed production system.
Peripheral Port
Programming Devices are compatible with other models of OMRON PCs. This port can also be used for Host Link or no-protocol communications.
RS-232C Port
This port can be used for a Host Link, no-protocol, 1:1 PC Link, or 1:1 NT Link communications.
Relay Output Board Transistor Output Board
The CPU Board has 32 I/O points and Expansion
I/O Boards can be added to provide a total I/O capacity of up to 128 I/O points.
Basic Functions
CPU Board I/O
Expansion I/O Boards
Share Programming
Devices
The CPM2B CPU Board itself is equipped with 32 I/O points in I/O terminals or
I/O connectors. There are 2 types of outputs available (relay outputs and sinking transistor outputs). The power supply is 24 V DC only.
Up to 3 Expansion I/O Boards can be connected to the CPU Board to increase the PC’s I/O capacity to a maximum of 128 I/O points. There are 2 types of
32-point Expansion I/O Boards available: one with relay outputs and the other with sinking transistor outputs.
The same Programming Devices, such as Programming Consoles and Support
Software, can be used for the C200H, C200HS, C200HX/HG/HE, CQM1,
CPM1, CPM1A, CPM2A, CPM2C, and SRM1 (-V2) PCs, so existing ladder program resources can be used effectively.
Built-in Motor Control Capability
Synchronized Pulse
Control
(Transistor Outputs Only)
Synchronized pulse control provides an easy way to synchronize the operation of a peripheral piece of equipment with the main equipment. The output pulse frequency can be controlled as some multiple of the input pulse frequency, al-
2
CPM2B Features and Functions Section 1-1 lowing the speed of a peripheral piece of equipment (such as a supply conveyor) to be synchronized with the speed of the main piece of equipment.
Encoder Motor driver Motor
CPM2B
Pulses are output as a fixed multiple of the input frequency.
High-speed Counters and
Interrupts
Easy Position Control with Pulse Outputs
(Transistor Outputs Only)
High-speed Input Capabilities for Machine Control
High-speed Interrupt
Input Function
There are four inputs used for interrupt inputs (shared with quick-response inputs and interrupt inputs in counter mode) with a minimum input signal width of
50
µ s and response time of 0.3 ms. When an interrupt input goes ON, the main program is stopped and the interrupt program is executed.
Quick-response Input
Function
Stabilizing Input Filter
Function
There are four inputs used for quick-response inputs (shared with interrupt inputs and interrupt inputs in counter mode) that can reliably read input signals with a signal width as short as 50
µ s.
The input time constant for all inputs can be set to 1 ms, 2 ms, 3 ms, 5 ms,
10 ms, 20 ms, 40 ms, or 80 ms. The effects of chattering and external noise can be reduced by increasing the input time constant.
Other Functions
Interval Timer Interrupts
The CPM2B has a total of five high-speed counter inputs. The one high-speed counter input has a response frequency of 20 kHz/5 kHz and the four interrupt inputs in counter mode have a response frequency of 2 kHz.
The high-speed counter can be used in any one of the four input modes: differential phase mode (5 kHz), pulse plus direction input mode (20 kHz), up/down pulse mode (20 kHz), or increment mode (20 kHz). Interrupts can be triggered when the count matches a set value or falls within a specified range.
The interrupt inputs in counter mode can be used for incrementing counters or decrementing counters (2 kHz) and trigger an interrupt (executing the interrupt program) when the count matches the target value.
CPM2B PCs with transistor outputs have two outputs that can produce 10 Hz to
10 kHz pulses (single-phase outputs).
When used as single-phase pulse outputs, there can be two outputs with a frequency range of 10 Hz to 10 kHz with a fixed duty ratio or 0.1 to 999.9 Hz with a variable duty ratio (0 to 100% duty ratio).
When used as pulse plus direction or up/down pulse outputs, there can be just one output with a frequency range of 10 Hz to 10 kHz.
Analog Settings
DIP Switch Inputs
Calendar/Clock
Long-term Timer
The interval timer can be set between 0.5 and 319,968 ms and can be set to generate just one interrupt (one-shot mode) or periodic interrupts (scheduled interrupt mode).
There are two controls on the CPU Board that can be turned to change the analog settings (0 to 200 BCD) in IR 250 and IR 251. These controls can be used to easily change or fine-tune machine settings such as a conveyor belt’s pause time or feed rate.
A DIP switch is provided that controls the status of four input bits.
The built-in clock (accuracy within 1 minute/month) can be read from the program to show the current year, month, day, day of the week, and time. The clock can be set from a Programming Device (such as a Programming Console) or the time can be adjusted by rounding up or down to the nearest minute.
TIML(––) is a long-term timer that accommodates set values up to 99,990 seconds (27 hours, 46 minutes, 30 seconds). When combined with the SECONDS
3
CPM2B Features and Functions
Expansion Memory Unit
Section 1-1
TO HOURS conversion instruction (HMS(––)), the long-term timer provides an easy way to control equipment scheduling.
The CPM1-EMU01-V1 Expansion Memory Unit is a program loader for smallsize or micro PCs. Using the CPM1-EMU01-V1, simple on-site transfer of user programs and data memory is possible with PCs.
Peripheral port
CPM2C-CN111
(0.1 m) (See note 2.)
Expansion Memory Unit
EEPROM
CS1W-CN114
(0.05 m)
Indicator
UPLOAD+DM Button UPLOAD Button
CPM2B CPU Board
Note 1. Refer to the CPM 2A Operation Manual (W352) or CPM2C Operation Manu-
al for details on the CPM1-EMV01-V1.
2. The CPM2C-CN111 can be connected only to the peripheral port.
Complete Communications Capabilities
Host Link A Host Link connection can be made through the PC’s RS-232C port or Peripheral port. A personal computer or Programmable Terminal connected in Host
Link mode can be used for operations such as reading/writing data in the PC’s
I/O memory or reading/changing the PC’s operating mode.
1:1 Host Link Communications 1:N Host Link Communications
CPM2B
CPM2B
No-protocol
Communications
4
(Up to 32 PCs can be connected.)
The TXD(48) and RXD(47) instructions can be used in no-protocol mode to exchange data with standard serial devices. For example, data can be received
CPM2B Features and Functions Section 1-1 from a bar code reader or transmitted to a serial printer. The serial devices can be connected to the RS-232C port or Peripheral port.
Inputting data from a bar code reader
Bar code reader
CPM2B
Outputting data to a serial printer
Serial printer
CPM2B
High-speed 1:1 NT Link
Communications
In a 1:1 NT Link, an OMRON Programmable Terminal (PT) can be connected directly to the CPM2B. The PT must be connected to the RS-232C port; it cannot be connected to the Peripheral port.
CPM2B
OMRON PT
One-to-one PC Link A CPM2B can be linked directly to another CPM2B, CQM1, CPM1, CPM1A,
CPM2A, CPM2C, SRM1(-V2), C200HS or C200HX/HG/HE PC. The 1:1 PC Link allows automatic data link connections. The PCs must be connected through the
RS-232C ports; they cannot be connected through the Peripheral ports.
CPM2B CPM2B
1-1-2 Overview of CPM2B Functions
Main function
Interrupts Interrupt inputs
4 inputs, see note 1.
Response time: 50 µ s
Interval timer interrupts
1 input
Set value: 0.5 to 319,968 ms
Precision: 0.1 ms
Variations/Details
Scheduled interrupts
One-shot interrupt
5
System Configurations Section 1-2
Main function
High-speed counters
Variations/Details
High-speed counter
1 input, see note 2.
Differential phase mode (5 kHz)
Pulse plus direction input mode (20 kHz)
Up/down input mode (20 kHz)
Increment mode (20 kHz)
No interrupt
Count-check interrupt
(An interrupt can be generated when the count equals the set value or the count lies within a preset range.)
Pulse outputs
Interrupt inputs in counter mode
4 inputs, see note 1.
No interrupt
Incrementing counter (2 kHz)
Decrementing counter (2 kHz)
Count-up interrupt
2 outputs:
Single-phase pulse output without acceleration/deceleration (See note 3.)
10 Hz to 10 kHz
2 outputs:
Variable duty ratio pulse output (See note 3.)
0.1 to 999.9 Hz, duty ratio 0 to 100%
1 output:
Pulse output with trapezoidal acceleration/deceleration (See note 3.)
Pulse plus direction output, up/down pulse output, 10 Hz to 10 kHz
Synchronized pulse control 1 point, see notes 2 and 3.
Quick-response input
Analog settings
Input time constant
Calendar/Clock
Error log
Input frequency range: 10 to 500 Hz, 20 Hz to 1 kHz, or 300 Hz to 20 kHz
Output frequency range: 10 Hz to 10 kHz
4 inputs, see note 1.
Maximum input signal width: 50
µ s
2 controls (setting ranges: 0 to 200 BCD)
Determines the input time constant for all inputs. (Settings: 1, 2, 3, 5, 10, 20, 40, or 80 ms)
Shows the current year, month, day of the week, day of the month, hour, minute, and second.
Records the time of occurrence and error code.
Note 1. These four inputs are shared by interrupt inputs, interrupt inputs in counter mode, and quick-response inputs, but each input can be used for only one purpose.
2. This input is shared by the high-speed counter and synchronized pulse control functions.
3. This output is shared by the pulse output and synchronized pulse control functions. These functions can be used with transistor outputs only.
1-2 System Configurations
1-2-1 CPU Boards
CPU Board with 32 I/O points
(Relay outputs)
CPU Board with 32 I/O points
(Transistor outputs)
6
System Configurations Section 1-2
CPU Board
32 I/O points
Inputs Outputs Battery
16 inputs,
24 V DC
16 relay outputs
(Terminal-block)
---
Yes
16 inputs, 16 sinking transistor ---
24 V DC outputs (Connector)
Yes
---
Yes
---
Yes
Clock RS-232C port
---
Yes
---
Yes
Model
CPM2B-32C1DR-D
CPM2B-32C2DR-D
CPM2B-32C1DT-D
CPM2B-32C2DT-D
1-2-2 Expansion I/O Boards
Up to 3 Expansion I/O Boards can be connected to the CPU Board.
Expansion I/O Board with 32 I/O points
(Relay outputs)
Expansion I/O Board with 32 I/O points
(Transistor outputs)
CPU Board Expansion connector
Expansion I/O Board
Expansion connector
A PC with 128 I/O points (the maximum) can be assembled by connecting three
Expansion I/O Boards. The following configuration provides 64 inputs and 64 sinking transistor outputs:
CPM2B-32C1DT-D
(16 inputs, 16 outputs)
×
1 Board +
CPM2B-32EDT
(16 inputs, 16 outputs)
×
3 Boards = 64 inputs, 64 outputs
Expansion I/O Boards
Expansion I/O
Board
32 I/O points
(16 inputs,
16 outputs)
Inputs Outputs
16 inputs, 24 V DC 16 relay outputs
(Terminal-block)
16 inputs, 24 V DC 16 sinking transistor outputs (Connector)
Model
CPM2B-32EDR
CPM2B-32EDT
Note When an NT-AL001-E Adapter is connected to the RS-232C port, only one Expansion I/O Board can be connected because of power supply limitations.
7
System Configurations Section 1-2
1-2-3 Connecting a Programming Console
A Programming Console can be connected to the CPM2B CPU Board’s peripheral port, as shown below.
CS1W-CN114
Connecting Cable
(0.05 m)
Attached cable (2 m)
CQM1-PRO01-E
C200H-CN222 (2 m) or
C200H-CN422 (4 m)
Connecting Cable
CS1W-CN224 (2 m) or
CS1W-CN624 (4 m)
Connecting Cable
Peripheral port connector
CPM2C-CN111
Connecting Cable
(0.1 m) (See note 2.)
C200H-PRO27-E
SW201
(See note 1.)
Peripheral port
CPM2B CPU Board
Note 1. Always turn OFF SW 201 before connecting the Programming Console.
2. Only the peripheral port connector can be used when a CPM2C-CN111
Connecting Cable is connected.
1-2-4 Support Software
A personal computer running the CX-Programmer or SYSMAC-CPT Support
Software (in MS Windows) or the SSS (in MS-DOS) can be connected to the
CPU Board’s Peripheral port or RS-232C port. Refer to 1-2-5 One-to-one Com-
puter Connections for details on the computer connection.
Always turn ON Communications Switch SW201 when using Support Software instead of a Programming Console. The setting on Communications Switch
SW202 determines whether the communications settings in the PC Setup or the standard settings will be used, as shown in the following table.
SW202 setting
ON
OFF
Communications settings
Peripheral port RS-232C port
Standard settings (The standard settings and PC Setup default settings are Host Link communications at 9,600 bps with 1 start bit, 7-bit data, 2 stop bits, and even parity.)
PC Setup settings in DM 6650 and
DM 6651
PC Setup settings in DM 6645 and
DM 6646
When using the SSS, set the PC Model to “CQM1.” When using the SYSMAC-
CPT, set the PC Model to “CQM1” with the “CPU43” CPU version.
8
System Configurations Section 1-2
1-2-5 One-to-one Computer Connections
Use one of the connecting cables shown in the following diagram to connect a personal computer with Support Software to the CPM2B for a 1:1 Host Link communications or no-protocol (serial) communications.
RS-232C Port Connection Peripheral Port Connection
IBM PC/AT or compatible computer
Connecting Cable
XW2Z-200S-V (2 m)
XW2Z-500S-V (5 m)
IBM PC/AT or compatible computer
CQM1-CIF02
(3.3 m)
CS1W-CN114
(0.05 m)
RS-232C port
(D-sub 9-pin)
Peripheral port
Connecting Cable
XW2Z-200S-V (2 m)
XW2Z-500S-V (5 m)
CPM1-CIF01
RS-232C Adapter
CPM2B CPU Board
CPM2B CPU Board
Note 1. The CQM1-CIF11 Connecting Cable cannot be used. (If one is connected, the CPM2C will not recognize it; the PC will enter RUN mode at startup if
Communications Switch SW201 is ON and DM 6600 of the PC Setup is set to its default setting so that the Programming Console’s mode switch controls the startup mode.)
2. Refer to Appendix A Standard Models for details on the Support Software that can be used with the CPM2B.
9
System Configurations Section 1-2
1-2-6 One-to-N Computer Connections
Up to 32 OMRON PCs, including CPM2B PCs, can be connected to a host computer.
Using the RS-232C Port
Connecting Cable
XW2Zj 00S-V
IBM PC/AT or compatible computer
3G2A9-AL004-E or NT-AL001-E (requires +5 V)
(See notes 1 and 2.)
RS-422 (Total length: 500 m max.)
NT-AL001-E
(See note 1.)
NT-AL001-E
(See note 1.)
NT-AL001-E
(See note 1.)
CPM2B CPU Board CPM2B CPU Board
Up to 32 PCs
CPM2B CPU Board
Using the Peripheral Port
IBM PC/AT or
Connecting Cable
XW2Zj
00S-V compatible computer
CS1W-CN114
3G2A9-AL004-E or NT-AL001-E (requires +5 V)
(See notes 1.)
RS-422 (Total length: 500 m max.)
CPM1-CIF11
(See note 3.)
CS1W-CN114
CPM1-CIF11
(See note 3.)
CS1W-CN114
CPM1-CIF11
(See note 3.)
CPM2B CPU Board CPM2B CPU Board
Up to 32 PCs
CPM2B CPU Board
Note 1. The NT-AL001-E must be supplied externally with 5 V DC. When an NT-
AL001-E is connected to a CPM2B PC, pin 6 of the CPM2B’s RS-232C port supplies +5 V DC and an external power supply is not necessary. When the
NT-AL001-E is connected to a host computer, it is necessary to supply 5 V
DC from an external power supply.
If an NT-AL001-E is connected to the CPM2B’s RS-232C port, only one Expansion I/O Board can be connected to the CPU Board because the NT-
AL001-E draws its 5-V DC power from the CPU Board.
Use an XW2Z-070T-1 (0.7 m) or XW2Z-200T-1 (2 m) cable to connect the
NT-AL001-E to the CPM2B’s RS-232C port.
2. The 3G2A9-AL004-E requires an external AC power supply (110 V AC or
220 V AC).
3. The CPM1-CIF11 is supplied +5 V DC from the peripheral port so an external power supply is not necessary.
10
System Configurations Section 1-2
1-2-7 OMRON PT Connections
In a 1:1 NT Link, a CPM2B can be connected directly to a Programmable Terminal through the RS-232C port. (The Programmable Terminal cannot be connected directly to the peripheral port.)
An OMRON PT can also be connected to the CPM2B with a host link connection.
Either the RS-232C port or peripheral port can be used for a host link connection.
Connecting Cable
XW2Z-200T (2 m)
XW2Z-500T (5 m)
RS-232C port
(D-sub 9-pin)
Connecting Cable
XW2Z-200T (2 m)
XW2Z-500T (5 m)
Peripheral port
OMRON
Programmable
Terminal
RS-422 connection
CPM1-CIF01
RS-232C Adapter
CPM1-CIF02
RS-422
Adapter
CS1W-CN114
(0.05 m)
CPM2B CPU Board
NT-AL001-E
RS-232C Adapter
XW2Z-070T-1 (0.7 m)
XW2Z-200T-1 (2 m)
Note The Programmable Terminal cannot be connected through the peripheral port for direct access.
11
System Configurations Section 1-2
1-2-8 One-to-one PC Link Connections
A CPM2B can be linked to another CPM2B, a CQM1, CPM1, CPM1A, CPM2A,
CPM2C, SRM1 (-V2) or a C200HS or C200HX/HG/HE PC. The PCs must be connected through the RS-232C ports; they cannot be connected through the
Peripheral ports.
1:1 Link Master
RS-232C port
(D-sub 9-pin)
1:1 Link Slave
RS-232C port
(D-sub 9-pin)
Connecting Cable
XW2Z-200T (2 m)
XW2Z-500T (5 m)
CPM2B CPU Board
OMRON PC (CQM1, CPM1, CPM1A,
CPM2A, CPM2B, CPM2C, SRM1(-V2),
C200HS, or C200HX/HG/HE)
CPM2B CPU Board
OMRON PC (CQM1, CPM1, CPM1A,
CPM2A, CPM2B, CPM2C, SRM1(-V2),
C200HS, or C200HX/HG/HE)
12
Structure and Operation
1-3 Structure and Operation
Section 1-3
1-3-1 CPU Board Structure
The following diagram shows the internal structure of the CPU Board.
External input devices
I/O memory
Program
PC Setup
Settings
External output devices
RS-232C port
Peripheral port
Settings
Settings
Communications switch
I/O Memory
Program
PC Setup
Communications
Switches
The program reads and writes data in this memory area during execution. Part of the I/O memory contains the bits that reflect the status of the PC’s inputs and outputs. Parts of the I/O memory are cleared when the power is turned ON and other parts are retained.
Note Refer to Section 4 Memory Areas for more details on I/O memory.
This is the program written by the user. The CPM2B executes the program cyclically. (Refer to 1-3-5 Cyclic Operation and Interrupts for details.)
The program can be divided broadly into two parts: the “main program” that is executed cyclically and the “interrupt programs” that are executed only when the corresponding interrupt is generated.
The PC Setup contains various startup and operating parameters. The PC Setup parameters can be changed from a Programming Device only; they cannot be changed from the program.
Some parameters are accessed only when PC’s power supply is turned on and others are accessed regularly while the power is on. It will be necessary to turn the power off and then on again to enable a new setting if the parameter is accessed only when the power is turned on.
Note Refer to 4-5 PC Setup for more details.
The Communications Switches determine whether the peripheral port and
RS-232C port operate with the standard communications settings or the communications settings in the PC Setup. Refer to 2-2 Board Components and their
Functions for more details.
13
Structure and Operation Section 1-3
1-3-2 Operating Modes
CPM2B CPU Boards have 3 operating modes: PROGRAM, MONITOR, and
RUN.
PROGRAM Mode The program cannot be executed in PROGRAM mode. This mode is used to perform the following operations in preparation for program execution
•
Changing initial/operating parameters such as those in the PC Setup
•
Writing, transferring, or checking the program
•
Checking wiring by force-setting and force-resetting I/O bits
!
Caution The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly if the corresponding output bit is turned ON by changing the contents of I/O memory from a Programming Device.
MONITOR Mode
RUN Mode
The program is executed in MONITOR mode and the following operations can be performed from a Programming Device. In general, MONITOR mode is used to debug the program, test operation, and make adjustments.
•
Online editing
•
Monitoring I/O memory during operation
•
Force-setting/force-resetting I/O bits, changing set values, and changing present values during operation
The program is executed at normal speed in RUN mode. Operations such as online editing, force-setting/force-resetting I/O bits, and changing set values/ present values cannot be performed in RUN mode, but the status of I/O bits can be monitored.
1-3-3 Operating Mode at Startup
The operating mode of the CPM2B when the power is turned ON depends upon the PC Setup settings and the Programming Console’s mode switch setting if a
Programming Console is connected.
PC Setup setting
Word Bits Setting
DM 6600 08 to 15 00
01
02
00 to 07 00
01
02
Operating mode
See note.
Startup mode is the same as the operating mode before power was interrupted.
Startup mode is determined by bits 00 to 07.
PROGRAM mode
MONITOR mode
RUN mode
Note The startup mode depends upon the setting of Communications Switch SW201 and the Programming Device connected to the peripheral port.
Programming
Device
None
Programming
Console
Other device
SW201 OFF SW201 ON
PROGRAM mode
Operating mode set on the
Programming Console’s mode switch
PROGRAM mode (see note 1)
RUN mode (see note 2)
PROGRAM mode
(see note 1)
PROGRAM mode
Note 1. The CPM2B will not be able to communicate with the Programming Device in these cases.
2. The default setting of bits 08 to 15 of DM 6600 is 00. With this default setting, the PC will automatically enter RUN mode if a Programming Console is not connected and SW201 is ON. Be sure that it is safe for the PC to operate before turning it ON under these conditions.
14
Structure and Operation Section 1-3
1-3-4 PC Operation at Startup
Time Required for
Initialization
The time required for startup initialization depends on several factors, such as the operating conditions (including power supply voltage, system configuration, and ambient temperature) and the program contents.
Power OFF Operation
Minimum Power Supply Voltage
The PC will stop and all outputs will be turned OFF if the power supply voltage falls below 85% of the rated value.
Momentary Power Interruption
A power interruption will not be detected and CPU Board operation will continue if the power interruption lasts less than 2 ms for a DC power supply.
A power interruption may or may not be detected for power interruptions somewhat longer than 2 ms for a DC power supply.
When a power interruption is detected, the CPU Board will stop operating and all outputs will be turned OFF.
Automatic Reset
Operation will restart automatically when the power supply voltage is restored to more than 85% of the rated voltage.
Timing Chart of Power OFF Operation
The power interruption detection time is the time required for a power interruption to be detected after the power supply voltage drops below 85% of the rated value.
1, 2, 3...
1. Minimum power interruption detection time
Power interruptions that are shorter than 2 ms will not be detected.
2. Undetermined additional time
Power interruptions only slightly longer than the minimum power interruption time may not be detected.
85% of rated voltage
Detection of power interruption
1. Minimum time 2. Additional time
Program execution Executing Stopped
CPU reset signal
CPU Board operation will continue if voltage is restored in this region.
CPU Board operation may continue if voltage is restored in this region.
Note If the power supply voltage fluctuates around 85% of the PC’s rated voltage, PC operation may stop and restart repeatedly. When repeated stopping and starting will cause problems with the controlled system, set up a protective circuit such as a circuit that shuts off the power supply to sensitive equipment until the power supply voltage returns to the rated value.
15
Structure and Operation Section 1-3
1-3-5 Cyclic Operation and Interrupts
Basic CPU Operation Initialization processing is performed when the power is turned on. If there are no initialization errors, the overseeing processes, program execution, I/O refreshing, and communications port servicing are performed repeatedly (cyclically).
Startup initialization
S
Check hardware.
S
Check memory.
S
Read data from flash memory (program, read-only DM data, and PC Setup settings).
Overseeing processes
S Check for battery error.
S Preset the watch (maximum) cycle time.
S Check program memory.
S Refresh bits for expansion functions.
Program execution
Cycle time calculation
S
Execute the program.
(Refer to the Programming Manual (W353) for details on cycle time and I/O response times.)
S
Wait for minimum cycle time if a minimum cycle time has been set in the PC Setup
(DM 6619).
S
Calculate cycle time.
I/O refreshing
S
Read input data from input bits.
S
Write output data to output bits.
RS-232C port servicing
Peripheral port servicing
S
Perform RS-232C port communications processing. (Can be changed in DM 6616.)
S Perform Peripheral port communications processing. (Can be changed in DM 6617.)
The cycle time can be read from a Programming Device.
AR 14 contains the maximum cycle time and AR 15 contains the present cycle time in 4-digit BCD.
16
Structure and Operation Section 1-3
Program Execution in
Cyclic Operation
The cycle time will vary slightly depending on the processing being performed in each cycle, so the calculated cycle time will not always match the actual cycle time.
The following diagram shows the cyclic operation of the CPM2B when the program is being executed normally.
Normally, the results of program execution are transferred to I/O memory just after program execution (during I/O refreshing), but IORF(97) can be used to refresh a specified range of I/O words during program execution. The specified range of I/O words will be refreshed when IORF(97) is executed.
The cycle time is the sum of the time required for program execution, I/O refreshing, and communications port servicing.
A minimum cycle time (1 to 9,999 ms) can be set in the PC Setup (DM 6619).
When a minimum cycle time has been set, CPU operation is paused after program execution until the minimum cycle time is reached. CPU operation will not be paused if the actual cycle time is longer than the minimum cycle time set in
DM 6619.
Note A fatal error will occur and PC operation will stop if a maximum cycle time has been set in the PC Setup (DM 6618) and the actual cycle time exceeds that setting.
The default settings for RS-232C port servicing and Peripheral port servicing are
5% of the cycle time, but these settings can be changed (between 1% and 99%) in the PC Setup. The RS-232C port’s setting is in DM 6616 and the Peripheral port’s setting is in DM 6617.
Overseeing processes
Main program
Cycle time
I/O refreshing
RS-232C port servicing
Peripheral port servicing
If a minimum cycle time has been set in DM 6619, CPU operation is paused until the minimum cycle time is reached.
The servicing time can be set in DM 6616.
The servicing time can be set in DM 6617.
17
Structure and Operation
Interrupt Program
Execution
Section 1-3
When an interrupt is generated during execution of the main program, main program execution is interrupted immediately and the interrupt program is executed. The following diagram shows the cyclic operation of the CPM2B when an interrupt program is executed.
Normally, the results of interrupt program execution are transferred to I/O memory just after program execution (during I/O refreshing), but IORF(97) can be used to refresh a specified range of I/O words during execution of the interrupt program. The specified range of I/O words will be refreshed when IORF(97) is executed.
The normal cycle time is extended by the time required for execution of the interrupt program.
Refer to Section 7 PC Operations and Processing Time in the CPM1/CPM1A/
CPM2A/CPM2C/SRM1(-V2) Programmable Controllers Programming Manual
(W353) for more details and precautions on the cycle time.
Overseeing processes
Main program
Interrupt generated.
Interrupt program
Cycle time
I/O refreshing
RS-232C port servicing
Peripheral port servicing
!
Caution Although IORF(97) can be used in interrupt subroutines, you must be careful of the interval between IORF(97) executions. If IORF(97) is executed too frequently, a fatal system error may occur (FALS 9F), stopping operation. The interval between executions of IORF(97) should be at least 1.3 ms + total execution time of the interrupt subroutine.
Immediate Refreshing IORF(97) can be executed in the program to refresh a specified range of I/O words. The specified I/O words will be refreshed when IORF(97) is executed.
IORF(97) can be used to refresh I/O from the main program or the interrupt program.
18
Structure and Operation Section 1-3
When IORF(97) is used, the cycle time is extended by the time required to refresh the specified I/O words.
Overseeing processes
Main program
Cycle time
IORF(97) executed.
Immediate refreshing
I/O refreshing
I/O refreshing
RS-232C port servicing
Peripheral port servicing
19
SECTION 2
Board Specifications and Components
This section provides the technical specifications of the CPM2B Boards and describes the main components of the Boards.
2-1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 I/O Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Board Components and their Functions
2-2-1 CPU Board Components
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Expansion I/O Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 I/O Connector and Terminal Pin Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
29
32
33
22
22
23
25
21
Specifications Section 2-1
2-1 Specifications
2-1-1 General Specifications
Item CPU Boards
Supply voltage
With relay outputs With transistor outputs
24 V DC
(Allowable range: 20.4 to 26.4 V DC)
Power consumption 20 W max.
300 g max.
With relay outputs
Supplied from CPU Board.
300 g max.
Expansion I/O Boards
With transistor outputs
Inputs: Connector
Outputs: Terminal block
2 ms min.
---
Inrush current 20 A max.
---
Insulation resistance 20 M
Ω
min. (at 500 V DC) between the external DC terminals and non-current carrying metal parts
Dielectric strength 1,000 V AC 50/60 Hz for 1 min between the external DC terminals and non-current carrying metal parts
Noise immunity Conforms to IEC6100-4-4; 2 kV (power lines)
Vibration resistance 10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s 2 in X, Y, and Z directions for 80 minutes each
(8 minutes of vibration
×
10 repetitions= total time 80 minutes)
Shock resistance 147 m/s 2 three times each in X, Y, and Z directions
Ambient temperature Operating: 0 to 55
°
C
Storage: –25 to 70
°
C (excluding the battery)
Ambient humidity Operating: 10% to 90% (with no condensation)
Ambient atmosphere Operating: Must be free from corrosive gas
I/O configuration Inputs: Connector
Outputs: Connector
Inputs: Connector
Outputs: Terminal block
Inputs: Connector
Outputs: Connector
Power supply retention time
Weight
22
Specifications
2-1-2 Characteristics
Section 2-1
Control method
Item
I/O control method
CPU Boards
With relay outputs
Stored program method
With transistor outputs
Cyclic scan with direct output (Immediate refreshing can be performed with
IORF(97).)
Ladder diagram Programming language
Instruction length
Instructions Basic instructions 14
Special instructions
105 instructions, 185 variations
Execution time Basic instructions 0.64
µ s (LD instruction)
Special 7.8
µ s (MOV instruction) instructions
Program capacity 4,096 words
Max. I/O capacity
CPU Board only
With Expansion
I/O Boards
1 step per instruction, 1 to 5 words per instruction
32 points
128 points max.
Input bits
Output bits
Work bits
IR 00000 to IR 00915 (Words not used for input bits can be used for work bits.)
IR 01000 to IR 01915 (Words not used for output bits can be used for work bits.)
928 bits: IR 02000 to IR 04915 and IR 20000 to IR 22715
Special bits (SR area)
Temporary bits (TR area)
Holding bits (HR area)
Auxiliary bits (AR area)
448 bits: SR 22800 to SR 25515
8 bits (TR0 to TR7)
320 bits: HR 0000 to HR 1915 (Words HR 00 to HR 19)
384 bits: AR 0000 to AR 2315 (Words AR 00 to AR 23)
Link bits (LR area)
Timers/Counters
Data memory
Interrupt processing
High-speed counter
Read/Write
256 bits: LR 0000 to LR 1515 (Words LR 00 to LR 15)
256 timers/counters (TIM/CNT 000 to TIM/CNT 255)
1-ms timers: TMHH(––)
10-ms timers: TIMH(15)
100-ms timers: TIM
1-s/10-s timers: TIML(––)
Decrementing counters: CNT
Reversible counters: CNTR(12)
2,048 words (DM 0000 to DM 2047) The Error Log is contained in DM 2000 to
DM 2021.
456 words (DM 6144 to DM 6599)
56 words (DM 6600 to DM 6655)
Read-only
PC Setup
External interrupts 4 (Also used for external interrupt inputs in counter mode and quick-response inputs.)
Interval timer interrupts
1 (Scheduled Interrupt Mode or Single Interrupt Mode)
High-speed counter 1 (20 kHz single-phase or 5 kHz two-phase (linear count method))
Counter interrupt 1 (set value comparison or set-value range comparison)
Interrupt Inputs
(Counter mode)
4 inputs (Also used for interrupt inputs and quick-response inputs.)
Counter interrupts 4 (Also used for the external interrupt inputs and quick-response inputs.)
Pulse output 2 points with no acceleration/deceleration, 10 Hz to 10 kHz each, and no direction control.
1 point with trapezoidal acceleration/deceleration, 10 Hz to 10 kHz, and direction control.
2 points with variable duty-ratio outputs.
(Pulse outputs can be used with transistor outputs only, they cannot be used with relay outputs.)
23
Specifications Section 2-1
Synchronized pulse control
Quick-response inputs
CPU Boards
With relay outputs With transistor outputs
1 point:
A pulse output can be created by combining the high-speed counter with pulse outputs and multiplying the frequency of the input pulses from the high-speed counter by a fixed factor.
(This output is possible with transistor outputs only, it cannot be used with relay outputs.)
4 points (Min. input pulse width: 50
µ s max.) (Also used for interrupt inputs and for interrupt inputs in counter mode.)
Can be set for all input points.
(1 ms, 2 ms, 3 ms, 5 ms, 10 ms, 20 ms, 40 ms, or 80 ms)
Input time constant
(ON response time = OFF response time)
Clock function
Communications functions
Memory protection
(See notes 1 and 2.)
Memory backup
(See notes 1 and 2.)
Self-diagnostic functions
Program checks
Shows the year, month, day of the week, day, hour, minute, and second.
(Backed up by the battery.)
(The clock function is available only in CPU Boards equipped with a clock.)
Built-in peripheral port:
Supports Host Link, peripheral bus, no-protocol, or Programming Console connections.
Built-in RS-232C port:
Supports Host Link, no-protocol, 1:1 PC Link (Master/Slave), or 1:1 NT Link connections.
(RS-232C communications are available only in CPU Boards equipped with an
RS-232C port.)
HR area, AR area, program contents, read/write DM area contents, and counter values maintained during power interruptions.
Flash memory:
Program, read-only DM area, and PC Setup
Battery or capacitor backup:
The read/write DM area, HR area, AR area, and counter values are backed up by a battery.
CPU Boards with clock: Backup is approximately 5 years at 25 ° C.
CPU Boards without clock: Backup is approximately 5 days at 25
°
C.
CPU error (watchdog timer), I/O bus error, battery error, and memory error
No END instruction, programming errors (checked when operation is started)
Note 1. The DM area, HR area, AR area, and counter values are backed up by the
CPU Board’s built-in battery or capacitor. If the battery or capacitor is discharged, the contents of these areas will be lost and the data values will revert to the defaults.
2. The contents of the program area, read-only DM area (DM 6144 to
DM 6599), and PC Setup (DM 6600 to DM 6655) are stored in flash memory. The contents of these areas will be read from flash memory the next time the power is turned ON, even if the backup battery or capacitor is discharged.
When data has been changed in any of these areas, write the new values to flash memory by switching the CPM2B to MONITOR or RUN mode, or by turning the power OFF and then ON again.
24
Specifications
2-1-3 I/O Specifications
CPU Board Input Specifications
Item
Input voltage
Input impedance
Input current
Inputs
All
IN00007 and up
24 V DC +10% /
–15%
IN00000 to IN00001 2.7 k
Ω
IN00002 to IN00006 3.9 k
Ω
4.7 k
Ω
IN00000 to IN00001 8 mA typical
IN00002 to IN00006 6 mA typical
IN00007 and up 5 mA typical
Specification
ON voltage/current IN00000 to IN00001 17 V DC min., 5 mA
IN00002 and up 14.4 V DC min., 3 mA
OFF voltage/current All
ON delay All
5.0 V DC max., 1 mA
1 to 80 ms max. Default: 10 ms (See note.)
OFF delay All
Circuit configuration IN00000 to IN00001
1 to 80 ms max. Default: 10 ms (See note.)
IN
Input LED
0.01
µ
F
IN 2.7 k
Ω Internal circuits
COM 680
Ω
Section 2-1
IN00002 to IN00006
IN
IN 3.9 k
Ω
750
Ω
COM
Input LED
Internal circuits
IN00007 and up
IN
IN
4.7 k
Ω
750
Ω
COM
Input LED
Internal circuits
Note The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PC
Setup. See page 66.
Max. Number of Inputs
Simultaneously ON
The maximum number of inputs that can be ON simultaneously depends upon the ambient operating temperature and the installation orientation, as shown in the following diagrams.
1, 2, 3...
1. Installation orientation: Vertical with edge down
All inputs can be ON simultaneously with this orientation.
25
Specifications
16
14
2. Installation orientation: Vertical with end down
Input voltage
26.4 V DC
16
14
Section 2-1
Input voltage
24 V DC
0 10 20 30 40 50 55 (
°
C)
49
16
13
3. Installation orientation: Horizontal
Input voltage
26.4 V DC
16
13
0 10 20 30 40 50 55 (
°
C)
49
Input voltage
24 V DC
0 10 20 30 40 50 55 (
°
C)
45
0 10 20 30 40 50 55 (
°
C)
45
High-speed Counter
Inputs
Inputs IN00000 through IN00002 can be used as high-speed counter inputs, as shown in the following table. The maximum count frequency is 5 kHz in differential phase mode and 20 kHz in the other modes.
Input
Differential phase mode Pulse plus direction
IN00000 A-phase pulse input
IN00001 B-phase pulse input input mode
Pulse input
Direction input
Function
Up/down input mode
Increment pulse input
Decrement pulse input
Increment mode
Increment pulse input
Normal input
IN00002 Z-phase pulse input or hardware reset input
(IN00002 can be used as a normal input when it is not used as a high-speed counter input.)
The minimum pulse widths for inputs IN00000 (A-phase input) and IN00001 (Bphase input) are as follows:
Pulse plus direction input mode, Up/down input mode, Increment mode
50
µ s min.
Phase A
Differential phase mode
100
µ s min.
Phase B
12.5
µ s min.
12.5
µ s min.
T
1
T
2
T
3
T
4
T
1
T
2
T
3
T
4
: 12.5
µ s min.
The minimum pulse width for input IN00002 (Z-phase input) is as follows:
50
µ s min.
Phase Z
500
µ s min.
26
Specifications
Interrupt Inputs
Section 2-1
Inputs IN00003 through IN00006 can be used as interrupt inputs (interrupt input mode or counter mode) and quick-response inputs. The minimum pulse width for these inputs is 50
µ s.
Expansion I/O Board Input Specifications
Item
Input voltage
Input impedance
Input current
ON voltage
OFF voltage
ON delay
OFF delay
Circuit configuration
Specification
24 V DC +10% /
–15%
4.7 k
Ω
5 mA typical
14.4 V DC min.
5.0 V DC max.
1 to 80 ms max. Default: 10 ms (See note.)
1 to 80 ms max. Default: 10 ms (See note.)
IN
4.7 k
Ω
750
Ω
COM
Input LED
Note The input time constant can be set to 1, 2, 3, 5, 10, 20, 40, or 80 ms in the PC
Setup. See page 66.
CPU Board and Expansion I/O Board Output Specifications
Relay Outputs
Item
Max. switching capacity
Min. switching capacity
Service life of relay
(See note.)
ON delay
OFF delay
Circuit configuration
Specification
2 A, 250 V AC (cos
φ
= 1)
2 A, 24 V DC
(4 A/common)
10 mA, 5 V DC
Electrical: 150,000 operations (24-V DC resistive load)
100,000 operations (240-V AC inductive load, cos
φ
= 0.4)
20,000,000 operations Mechanical:
15 ms max.
15 ms max.
OUT
COM
Output LED
27
Specifications Section 2-1
Note The service life of the CPM2B’s relay output contacts shown in the table assumes the worst conditions. The following graph shows the results of OMRON’s service life tests at a switching rate of 1,800 times/hour.
Life (x 10 4 )
120 V AC, resistive load
24 V DC,
τ
= 7 ms
120 V AC, cos
φ
= 0.4
240 V AC, cos
φ
= 0.4
24 V DC/240 V AC, resistive load
Contact current (A)
Switching rate:
1,800 times/hour
Transistor Outputs (Sinking or Sourcing)
Item
Max. switching capacity
Leakage current
Residual voltage
ON delay
OFF delay
Fuse
Circuit configuration
Specification
OUT01000 and OUT01001: 4.5 to 30 V DC, 0.2 A/output (See note 1.)
OUT01002 and up: 4.5 to 30 V DC, 0.3 A/output (See note 1.)
0.1 mA max.
1.5 V max.
OUT01000 and OUT01001: 20
µ s max.
OUT01002 and up: 0.1 ms max.
OUT01000 and OUT01001: 40 µ s max. for 4.5 to 26.4 V, 10 to 100 mA
0.1 ms max. for 4.5 to 30 V, 10 to 200 mA
OUT01002 and up: 1 ms max. for 4.5 to 30 V, 10 to 300 mA
1 fuse/output (cannot be replaced by user)
Sinking Outputs
Output LED
OUT
Internal circuits
OUT
24 V DC
COM (–)
Note When using OUT01000 or OUT01001 for pulse outputs, connect a dummy resistor as required to bring the load current between 0.01 and 0.1 A. If the load current is below 0.01 A, the ON-to-OFF response time will be too long and highspeed pulses will not be output.
!
Caution Do not apply voltage in excess of the maximum switching capacity to an output terminal. It may result in damage to the product or fire.
28
Board Components and their Functions
2-2 Board Components and their Functions
2-2-1 CPU Board Components
CPU Boards with Relay Outputs
8. RS-232C port
7. Peripheral port
9. Communications Switch SW201
9. Communications Switch SW202
10. Analog settings
11. DIP Switch inputs
2. Input connector
Section 2-2
4. PC status indicators
5. Input indicators
12. Expansion I/O connector
6. Output indicators
13. Battery
1. Power supply terminals
CPU Boards with Transistor Outputs
8. RS-232C port
7. Peripheral port
3. Output terminals
9. Communications Switch SW201
9. Communications Switch SW202
10. Analog settings
11. DIP Switch inputs
2. Input connector
4. PC status indicators
5. Input indicators
12. Expansion I/O connector
6. Output indicators
3. Output connector
13. Battery
1. Power supply terminals
29
Board Components and their Functions Section 2-2
CPU Board Component Descriptions
1, 2, 3...
1. Power Supply Terminals
Connect the power supply (24 V DC) to these terminals.
2. Input Connector
Connects the CPU Board to external input devices.
3. Output Terminals/Connector
Connects the CPU Board to external output devices.
4. PC Status Indicators
These indicators show the operating status of the PC, as shown in the following table.
Indicator Status
PWR
(green)
Lit
Not lit
RUN
(green)
Lit
ERR
(red)
Meaning
Power is being supplied to the PC.
Power isn’t being supplied to the PC.
The PC is operating in RUN or MONITOR mode.
Not lit
Lit
The PC is in PROGRAM mode or a fatal error has occurred.
A fatal error has occurred. (PC operation stops.)
Flashing A non-fatal error has occurred. (PC operation continues.)
Not lit Indicates normal operation.
PERI
(orange)
COMM
(orange)
Flashing
Not lit
Data is being transferred through the peripheral port.
The peripheral port is not in use.
Flashing Data is being transferred through the RS-232C port.
Not lit The RS-232C port is not in use.
5. Input Indicators
The input indicators are lit when the corresponding input terminal is ON. The status of an input indicator will reflect the status of the input even when that input is being used for a high-speed counter.
Note a) When interrupt inputs are used in interrupt input mode, the indicator may not light even when the interrupt condition is met if the input is not ON long enough. When a high-speed counter is being used, the indicator may not light depending on the speed of the pulses.
b) Input indicators will reflect the status of the corresponding inputs even when the PC is stopped, but the corresponding input bits will not be refreshed.
6. Output Indicators
The output indicators are lit when the corresponding output terminal is ON.
The indicators are lit during I/O refreshing. When an output is being used as a pulse output, the corresponding will remain lit while pulses are being output.
7. Peripheral Port
Connects the PC to a Programming Device (including Programming
Consoles), host computer, or standard external device.
8. RS-232C Port
Connects the PC to a Programming Device (excluding Programming
Consoles), host computer, Programmable Terminal, or standard external device.
30
Board Components and their Functions Section 2-2
9. Communications Switches SW201 and SW202
The Communications Switches control the communications settings for the peripheral port and RS-232C port.
ON
SW201
ON
SW202
OFF
(OFF when shipped.)
OFF
(OFF when shipped.)
Switch settings
SW202 SW201
OFF OFF
OFF ON
ON
ON
OFF
ON
Peripheral port communications
RS-232C port communications
Programming Console connection The settings in the PC
Other Programming Device:
Setup (DM 6645 to
The settings in the PC Setup
DM 6649) are used.
(DM 6650 to DM 6654) are used.
Programming Console connection The standard settings are used.
Other Programming Device:
The standard settings are used.
Note a) The standard settings are 1 start bit, 7 data bits, 2 stop bits, even parity, and 9,600 bps baud rate.
b) Be sure that Communications Switch SW201 is OFF when connecting a Programming Console.
10. Analog Settings
Turning these controls changes the contents of IR 250 and IR 251. The contents of these words can be set independently between 0 and 200.
11. DIP Switch Inputs
The ON/OFF status of IR 00108 through IR 00111 reflects the ON/OFF status of these DIP switch pins.
3
4
1
2
Pin Corresponding input bit
IR 00108
IR 00109
IR 00110
IR 00111
12. Expansion I/O Connector
Connects the CPU Board to an Expansion I/O Board. Up to 3 Expansion I/O
Boards can be connected to a CPU Board.
13. Battery
This battery backs up memory in CPU Boards equipped with an internal clock. The battery is connected when the Unit is shipped.
31
Board Components and their Functions
2-2-2 Expansion I/O Boards
Expansion I/O Boards with Relay Outputs
Section 2-2
1. Input connector
3. Input indicators
4. Output indicators
Expansion I/O Boards with Transistor Outputs
5. Expansion I/O connector
2. Output terminals
1. Input connector
32
3. Input indicators
4. Output indicators
5. Expansion I/O connector
2. Output connector
1, 2, 3...
1. Input Connector
Connects the Expansion I/O Board to external input devices.
2. Output Terminals/Connector
Connects the Expansion I/O Board to external output devices.
3. Input Indicators
The input indicators are lit when the corresponding input terminal is ON.
4. Output Indicators
The output indicators are lit when the corresponding output terminal is ON.
5. Expansion I/O Connector
Connects the Expansion I/O Board to the CPU Board or the previous Expansion Unit or Expansion I/O Unit. Up to 3 Expansion I/O Boards can be connected to a CPU Board. An Expansion I/O Cable is included with each Expansion I/O Board.
I/O Connector and Terminal Pin Allocation Section 2-3
Note Do not touch the cables during operation to prevent unexpected operation due to static discharge.
2-3 I/O Connector and Terminal Pin Allocation
CPU Boards
CPU Board with relay outputs
IR 001 IR 000
19
20
03 02 01 00
COM
03 02 01 00
COM
1
07 06 05 04
NC
07 06 05 04
NC
2
Inputs (24 V DC)
CPU Board with transistor outputs
Relay outputs
IR 010 IR 011
1 00 01 02 03
COM
04 05 06 07
COM
10 1 00 01 02 03
COM
04 05 06 07
COM
10
Sinking transistor outputs
IR 010 IR 011
19
20
00 01 02 03
COM
00 01 02 03
COM
1
04 05 06 07
COM
04 04 06 07
COM
2
33
I/O Connector and Terminal Pin Allocation
Expansion I/O Boards
Expansion I/O Board #1: IR 002
Expansion I/O Board #2: IR 003
Expansion I/O Board #3: IR 004
19
20
11 10 09 08
COM
03 02 01 00
COM
1
15 14 13 12
NC
07 06 05 04
NC
2
Inputs (24 V DC)
Expansion I/O Board with relay outputs
Expansion I/O Board with transistor outputs
Section 2-3
Relay outputs
Expansion I/O Board #1: IR 012
Expansion I/O Board #2: IR 013
Expansion I/O Board #3: IR 014
1 00 01 02 03
COM
04 05 06 07
COM
10 1 08 09 10 11
COM
12 13 14 15
COM
10
Sinking transistor outputs
Expansion I/O Board #1: IR 012
Expansion I/O Board #2: IR 013
Expansion I/O Board #3: IR 014
19
20
00 01 02 03
COM
08 09 10 11
COM
1
04 05 06 07
COM
12 13 14 15
COM
2
34
SECTION 3
Installation and Wiring
This section provides information on installing and wiring a CPM2B PC. Be sure to follow the directions and precautions in this section when installing the CPM2B in a panel or cabinet, wiring the power supply, or wiring I/O.
3-1 Design Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-1 Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-2 Power Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-3 Interlock and Limit Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Selecting an Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Installation Site Conditions
3-2-2 Panel/Cabinet Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Assembling the CPM2B Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Installing the CPM2B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Wiring and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-1 Power Supply Wiring
3-5-2 I/O Wiring Procedures
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-3 Connecting Input Devices
3-5-4 Output Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
40
41
42
45
49
36
37
37
38
36
36
36
36
35
Selecting an Installation Site Section 3-2
3-1 Design Precautions
Observe the following precautions when designing a system incorporating a
CPM2B PC.
3-1-1 Power Supply Wiring
Separate the power supply wiring from the power system, control system,
CPM2B system, and DC I/O system wiring. Separate the control circuits that supply power to the main Unit from the main circuits using dedicated circuit protectors and fuses.
3-1-2 Power Supply Voltage
!
Caution Use the power supply voltages indicated in Section 2-1 Specification. Failure to adhere to the specifications may result in fire.
If the power supply voltage falls below 85% of the rated voltage, the CPM2B will stop and all outputs will be turned OFF. If low voltage affects the equipment, etc., provide a protection circuit which shuts off the output until the supply voltage returns to the rated value.
In places where power supply conditions are poor, take steps to ensure that power is supplied at the rated voltage. Be sure to adhere to safety precautions, such as providing breakers to prevent short circuits in external wiring.
When conducting any of the following operations, turn OFF the power to the PC.
Electrocution, product damage and malfunction may result.
•
Connecting or disconnecting Expansion I/O Boards and CPU Boards.
•
Assembling equipment.
•
Connecting cables and wiring.
3-1-3 Interlock and Limit Circuits
!
WARNING Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits (i.e., not in the
Programmable Controller) to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not providing proper safety measures may result in serious accidents.
The following diagram shows an example of an interlock circuit.
Interlock Circuit
01005
MC1
CPM2B MC2
Motor forward
01006
MC1
MC2
Motor reverse
In the interlock circuit above, MC1 and MC2 can’t be ON at the same time even if
CPM2B outputs 01005 and 01006 are both ON (an incorrect PC operation).
3-2 Selecting an Installation Site
The CPM2B is resistant to harsh conditions and highly reliable, but installing the
PC in a favorable site will maximize its reliability and operating lifetime.
36
Selecting an Installation Site Section 3-2
!
Caution Be sure to install the CPM2B correctly, as outlined in this manual. Failure to do so may result in Board malfunction.
3-2-1 Installation Site Conditions
Note Do not install the CPM2B under any of the following conditions.
•
Locations subject to direct sunlight.
•
Locations subject to an ambient temperature below 0
°
C or over 55
°
C.
•
Locations subject to an ambient humidity below 10% or over 90%.
•
Locations subject to condensation as the result of severe changes in temperature.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to shock or vibration.
•
Locations subject to exposure to water, oil, or chemicals.
Be sure that the conditions at the installation site conform to the CPM2B’s general specifications. Refer to 2-1-1 General Specifications for details.
Note Provide proper shielding when installing in the following locations:
•
Locations subject to static electricity or other sources of noise.
•
Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radiation.
•
Locations near to power supply lines.
3-2-2 Panel/Cabinet Installation
Overheating
Consider PC operation, maintenance, and surrounding conditions when installing the CPM2B in a panel or cabinet.
The ambient operating temperature range for the CPM2B is 0 _ C to 55 _ C. Be sure that there is adequate ventilation for cooling.
•
Allow enough space for air circulation.
•
Do not install the CPM2B above equipment that generates a large amount of heat, such as heaters, transformers, or large resistors.
•
Install a cooling fan or system when the ambient temperature exceeds 55
_
C.
Control panel
Fan
Electrical Noise
CPM2B
Air vent
Power lines and high-voltage equipment can cause electrical noise in the PC.
•
Do not install the CPM2B in a panel or cabinet with high-voltage equipment.
•
Allow at least 200 mm between the CPM2B and nearby power lines.
200 mm min.
CPM2B
200 mm min.
37
Assembling the CPM2B Boards Section 3-3
Accessibility Ensure that the CPM2B can be accessed for normal operation and maintenance. High-voltage equipment, power lines, and moving machinery could be dangerous if they are in the way during routine operations.
3-3 Assembling the CPM2B Boards
Board Assembly Up to 3 Expansion I/O Boards can be connected to a CPM2B CPU Board. The following diagram shows how to assemble the Boards. The screws and standoffs are included with the CPU Board, Expansion I/O Board, and Mounting
Bracket.
Note Use M3 screws for the standoffs and tighten to a torque of 0.5 N
S m.
38
CPM2B-ATT01
Mounting Bracket
(See note.)
Note The CPM2B-ATT01 Mounting Bracket is required when the system must meet UL/CSA standards.
Board or Bracket
CPU Board
Expansion I/O Board
Hardware and cables included
Four M3 standoffs (short)
Four M3 screws
Four M3 standoffs (long)
One CPM2B-CN601
Expansion I/O Cable
Mounting Bracket Four M3 screws
Note Some of the CPM2B’s electrical components such as leads are sharp, so do not touch the components or the surface of the circuit board.
Installing the CPM2B Section 3-4
Installing the Expansion I/O Connecting Cables
1, 2, 3...
1. Insert the Expansion I/O Cable into the connectors on the CPU Board and
Expansion I/O Board.
CPU Board
Expansion
I/O Board
The cable from the CPU Board connects to the upper Expansion
I/O Connector (the one with the short locks.)
Expansion I/O Cable
(included with the Expansion
I/O Board)
Install the shorter connector of the cable in the lower Board and the longer connector in the upper Board.
2. Push the cable’s connector into the Board’s connector until both lock levers lock solidly.
Lock lever
To remove the Expansion I/O Cable, open the connectors lock levers and pull out the cable’s connector.
Lock lever
3-4 Installing the CPM2B
Install the CPM2B as shown in the following diagram. The CPM2B cannot be installed on DIN Track.
Four M4 screws
186
100
39
Wiring and Connections
Example Installations
Section 3-5
Mounting Bracket
Screw and nut installation
Screw and tapped panel installation
Note 1. Use M4 screws and tighten to a torque of 1.2 N
S m.
2. The CPM2B can be installed without a CPM2B-ATT01 Mounting Bracket, but the Mounting Bracket must be used to conform to UL/CSA standards.
Refer to Appendix B for mounting dimensions.
3. Installing the CPM2B horizontally or with its narrow edge down affects cooling and limits the number of inputs that can be ON simultaneously at high temperatures. Refer to page 26 for details.
3-5 Wiring and Connections
This section provides basic information on power supply wiring and I/O wiring.
General Precautions for Wiring
!
Caution Cover the CPM2B Boards with plastic or use some other method to prevent strands of wire from getting on the Board or inside the Board’s components during wiring. Wire strands may short circuit the Board’s components.
I/O Line Noise Do not run CPM2B I/O lines in the same duct or conduit as power lines.
Hanging Ducts
Leave at least 300 mm between the power cables and the I/O or control wiring, as shown in the following diagram.
CPM2B I/O lines
Control cables and
CPM2B power lines
Power cables
300 mm min.
300 mm min.
Floor Ducts
Leave at least 200 mm between the wiring and the top of the duct, as shown in the following diagram.
CPM2B I/O lines
Control cables and
CPM2B power lines Power cables
Metal plate (iron)
200 mm min.
40
Wiring and Connections Section 3-5
Conduits
Separate the CPM2B I/O lines, power and control lines, and power cables, as shown in the following diagram.
CPM2B I/O lines
Control cables and
CPM2B power lines Power cables
3-5-1 Power Supply Wiring
The power supply terminal specifications are shown below. Supply the power supply terminals with 24 V DC.
Terminal Specifications
Compatible Wires and
Terminals
24 V DC
0 V
(Not connected)
Item
Screw size
Recommended torque
Specifications
M3
0.5 to 0.6 N S m
Recommended screwdriver: OMRON XW4E-00C
Wire/terminal
Solid wire
Stranded wire
Two-condu Solid ctor wires
Stranded
Stranded with pin terminal
Pin terminals
Specification
0.2 to 2.5 mm 2 (AWG 24 to AWG 12)
Strip 7 mm (1/4 inch) of insulation.
0.2 to 2.5 mm 2 (AWG 24 to AWG 12)
Strip 7 mm (1/4 inch) of insulation.
2
×
(0.2 to 1.0 mm 2 ) (AWG 24 to AWG 20)
2
×
(0.2 to 1.5 mm 2 ) (AWG 24 to AWG 16)
2
×
(0.25 to 1.0 mm 2 ) (AWG 24 to AWG 20) without an insulating sleeve
0.2 to 2.5 mm 2 diameter, 7-mm long pin terminal
The following diagram shows how to wire the power supply.
The power supply terminal block is removable.
24 V DC 0 V
Note 1. Do not perform a voltage withstand test on the DC power supply terminals.
The test might damage the PC’s internal components.
2. When equipment must conform to the EC Directives (Low-voltage Directives), use a power supply with double insulation or reinforced insulation.
41
Wiring and Connections Section 3-5
3-5-2 I/O Wiring Procedures
Removing and Wiring I/O Terminal Blocks
The following tables provide output terminal block specifications.
CPU Boards and Expansion I/O Boards with relay outputs
Output terminal blocks
Terminal Block
Specifications
Recommended Wire and
Terminals
Screw size
Item
Recommended tightening torque
Specification
M3
0.5 to 0.6 N S m
Recommended screwdriver: OMRON XW4E-00C
Item Specification
Solid wire 0.2 to 2.5 mm 2 (AWG 24 to AWG12) (Strip 7 mm.)
Stranded wire (See notes.) 0.2 to 2.5 mm 2 (AWG 24 to AWG12) (Strip 7 mm.)
Two-cond Solid uctor
Stranded wires
Pin terminals
Stranded with pin terminal
2
×
(0.2 to 1.0 mm 2 ) (AWG 24 to AWG 20)
2
×
(0.2 to 1.5 mm 2 ) (AWG 24 to AWG 16)
2
×
(0.25 to 1.0 mm 2 ) (AWG 24 to AWG 20) without an insulating sleeve
0.2 to 2.5 mm
2
diameter, 7-mm long pin terminal
Bridge (shorts terminals) Terminal pitch 5.08 mm
Recommended Bridges:
OMRON XW4Z-02C (2 pole)
OMRON XW4Z-03C (3 pole)
Note 1. When using stranded wire, be sure to avoid stray wire strands that might short-circuit an adjacent terminal.
2. Do not solder the ends of stranded wires. Solder can break and cause wiring problems. Also, the solder can cause corrosion on the contact surface.
3. Be sure to use the correct pin allocation when assembling and wiring connectors or terminal blocks.
Removing and Wiring a
Terminal Block
Use the following procedure when wiring a terminal block.
1, 2, 3...
1. Use a flatblade screwdriver to loosen the screws at the left and right sides of the terminal block.
42
Wiring and Connections
2. Pull the terminal block out of the Board.
Section 3-5
3. Insert each lead wire into the terminal block and tighten that terminal’s screw.
4. After wiring the terminal block, insert the block into the Unit and tighten the screws at the left and right sides of the terminal block.
Removing and Wiring I/O Connectors
The following tables provide specifications of compatible OMRON I/O connectors.
MIL 20P Flat Cable Connector
XG4T-2004
Strain Relief
XG4M-2030
Set
XG4M-2030
Socket
Flat cable: XY3A-200 j
Note The max. rated current for flat cable is 1 A. Be sure that the current at the common terminal does not exceed 1A.
43
Wiring and Connections
OMRON Crimping Tools
Crimping Tool
Attachment
MIL 20P Loose-wire Pressure Connector
XG5S-2012
Full Cover*
XY2B-0002
XY2B-1007
Section 3-5
XG5S-1001
Partial Cover*
Using Relay Terminal and
Terminal Blocks
Inserting and Removing
I/O Connectors
Sockets
For AWG 24: XG5M-2032N
For AWG 26 to AWG 28: XG5M-2035N
Note Two Full Covers or Partial Covers are required for each socket.
OMRON Pressing Tools
Pressing Tool Set (Handy Press)
Simple Pressing Tool
XY2B-2104
XY2B-7006
A G79-A j
C (Loose-wire Connecting Cable) can be used to connect to a Relay
Terminal. (A pressure connector must be attached on the PC side of the cable.)
A special cable is not provided for connection to the XW2B-20G4 or
XW2B-20G5 Terminal Blocks, so one must be made. (The Terminal Block requires the kind of MIL 20P connector described above.)
When inserting a cable, first open the lock levers on each side of the connector and then insert the cable’s connector. Press the cable’s connector firmly until both lock levers lock onto the connector.
To remove the cable, open the lock levers to the left and right before removing the cable’s connector.
44
Wiring and Connections Section 3-5
3-5-3 Connecting Input Devices
Wire inputs to the CPM2B CPU Board and Expansion I/O Boards as shown in the following diagrams.
Note When equipment must conform to the EC Directives (Low-voltage Directives), use a power supply with double insulation or reinforced insulation.
CPU Boards (All Models)
Input Connector
Expansion I/O Boards (All Models)
19 17 15 13 11 9 7 5 3 1
20 18 16 14 12 10 8 6 4 2
Input Connector j j j j j j j j
19 17 15 13 11 9 7 5 3 1
20 18 16 14 12 10 8 6 4 2 j j j j j j j j
45
Wiring and Connections
Input Devices
Section 3-5
The following table shows how to connect various input devices.
Device
Relay output
Circuit diagram
5 mA/6 mA/8 mA
IN
COM (+)
CPM2B
NPN open collector
Sensor power supply
NPN current output
Output
5 mA/6 mA/8 mA
0 V
IN
COM (+)
CPM2B
Use the same power supply for the input and sensor.
Constant current circuit
Output
5 mA/6 mA/8 mA
0 V
+
IN
COM (+)
CPM2B
PNP current output
Sensor power supply
5 mA/6 mA/8 mA
Output
0 V
IN
COM (–)
CPM2B
Voltage output
Output
0 V
COM (+)
IN CPM2B
Sensor power supply
Note Do not use the following wiring with voltage-output devices:
Output
0 V
Sensor power supply
Incorrect Wiring
CPM2B IN
COM(+)
46
Wiring and Connections Section 3-5
High-speed Counter Inputs
Differential Phase Mode
(Count frequency: 5 kHz)
Using IR 00000 to IR 00002 as High-speed Counter Inputs
In these examples, Encoders with an external 24-V DC open-collector output are connected.
CPM2B
Pulse Plus Direction Input Mode
(Count frequency: 20 kHz)
CPM2B
Encoder 00000 A-phase input
Encoder 00000 Pulse input
00001 B-phase input
Sensor or switch
00002 Z-phase input
Sensor or switch
00001 Direction input
00002 Reset input
Sensor
24 V DC
Up/Down Mode
(Count frequency: 20 kHz)
COM
CPM2B
00000 CW input*
00001 CCW input*
Sensor
Sensor or switch 00002 Reset input
COM
24 V DC
Increment Mode
(Count frequency: 20 kHz)
CPM2B
Encoder
00000 Pulse input
00001 Normal input
00002 Normal input
PC Setup Settings
COM COM
24 V DC 24 V DC
Note *CW is clockwise and CCW is counter-clockwise.
Using IR 00003 to IR 00006 as Interrupt Inputs (Counter Mode)
In these examples, an Encoder with an external 24-V DC open-collector output is connected.
Increment or decrement
(Count frequency: 2 kHz)
CPM2B
Input (00003 to 00006)
Encoder
COM
24 V DC
The input bits shown in the following tables can operate as normal inputs or they can be assigned special functions in the PC Setup.
Special functions for input bits IR 00000 through IR 00002 are set in DM 6642:
Bit address
PC Setup setting (DM 6642 bits 08 to15)
00
IR 00000 Used as normal inputs.
IR 00001
01
Used as high-speed counter inputs.
Used as inputs for synchronized pulse control.
02, 03, or 04
IR 00002 Used as a normal input.
47
Wiring and Connections Section 3-5
Special functions for input bits IR 00003 through IR 00006 are set in DM 6628:
Bit Bits in address DM 6628
PC Setup setting (in DM 6628)
0
IR 00003 00 to 03 Used as normal
IR 00004 04 to 07 inputs.
1
Used as interrupt inputs (including counter mode).
Used as
2 quick-response inputs.
IR 00005 08 to 11
IR 00006 12 to 15
High-speed Counter Input Connection Examples
Differential Phase Mode
(Count frequency: 5 kHz)
E6B2-CWZ6C
Encoder
(NPN open-collector output)
Black
White
CPM2B
00000 A-phase input
00001 B-phase input
Pulse Plus Direction Input mode
(Count frequency: 20 kHz)
CPM2B
E6A2-CS5C
Encoder 00000 Pulse input
00001 Direction input
Orange
Brown
Blue
24 V DC
00002 Z-phase input
COM
Sensor or switch
Sensor or switch
00002 Reset input
Sensor power
24 V DC
COM
Leakage Current A leakage current can cause false inputs when using 2-wire sensors (proximity switches or photoelectric switches) or limit switches with LEDs. False inputs won’t occur if the leakage current is less than 1.0 mA (2.5 mA for IN00000 to
IN00002). If the leakage current exceeds these values, insert a bleeder resistor in the circuit to reduce the input impedance, as shown in the following diagram.
Input power supply
Bleeder resistor
2-wire sensor, etc.
I: Device’s leakage current (mA)
R: Bleeder resistance (k
Ω
)
W: Bleeder resistor’s power rating (W)
R CPM2B
I
L
E
C
C
C
: CPM2B’s input impedance (k
Ω
)
: CPM2B’s input current (mA)
: CPM2B’s OFF voltage (V) = 5.0 V
R +
L
C
I L
C
5.0
–5.0
k W max.
W
+
2.3
R
W min.
The equations above were derived from the following equations:
I
R
Input voltage (24)
Input Current (I
C
)
R
)
Input voltage (24)
Input Current (I
C
) x
OFF voltage (E
C
: 5.0)
W y
Input voltage (24)
R
Input voltage (24) tolerance (4)
Refer to 2-1-3 I/O Specifications for details on the values L
C
, I
C
, and E
C
.
The input impedance, input current, and OFF voltage may vary depending on the input being used. (IN00000 through IN00002 have different values.)
Inductive Loads When connecting an inductive load to an input, connect a diode in parallel with the load. The diode should satisfy the following requirements:
1, 2, 3...
1. Peak reverse-breakdown voltage must be at least 3 times the load voltage.
48
Wiring and Connections Section 3-5
2. Average rectified current must be 1 A.
Diode
IN
CPM2B
COM
3-5-4 Output Wiring
Relay Output Wiring
Wire the outputs to the CPM2B’s CPU Board and Expansion I/O Boards as shown in the following diagrams.
Don’t exceed the output capacity or the maximum common current. Refer to
2-1-3 I/O Specifications for details.
!
WARNING The PC outputs may remain ON or OFF due to fusing or burning of the output relays or destruction of the output transistors. External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.
CPU Boards with Relay Outputs
Terminal Block #1
(Left side)
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
Terminal Block #2
(Right side)
L L L L L L L L L L L L L L L L
Output capacity
2 A (250 V AC or 24 V DC)
Expansion I/O Boards with Relay Outputs
Terminal Block #1
(Left side)
1 2 3 4 5 6 7 8 9 10 j j j j
L L L L j
L j
L j
L j
L
Max. common capacity
4 A/common
1 2 3 4 5 6 7 8 9 10 j j j j
L L L L j
L j
L j
L j
L
Terminal Block #2
(Right side)
Output capacity
2 A (250 V AC or 24 V DC)
Max. common capacity
4 A/common
49
Wiring and Connections
CPU Boards with Sinking Transistor Outputs
Output connector
L L L L L L L L
19 17 15 13 11 9 7 5 3 1
20 18 16 14 12 10 8 6 4 2
L L L L L L L L
Section 3-5
Output capacity
01000, 01001: 200 mA (30 V DC)
01002 and up: 300 mA (30 V DC)
Expansion I/O Boards with Sinking Transistor Outputs
Output connector
Max. common capacity
1.2 A/common
L L L L j j j j j
L j
L j
L j
L j
19 17 15 13 11 9 7 5 3 1
20 18 16 14 12 10 8 6 4 2 j j j j j j j
L L L L L L L L
Output capacity
300 mA (30 V DC)
Max. common capacity
1.2 A/common
50
Wiring and Connections Section 3-5
Using Pulse Outputs Use the PULS(65), SPED(––), ACC(––), PWM(––), and SYNC(––) instructions to produce pulse outputs (rather than normal outputs) from output bits IR 01000 and IR 01001. Pulse outputs are possible from CPU Boards with transistor outputs only.
Single-phase pulse output
(Fixed duty ratio)
CPM2B
Pulse output 0: 01000
Motor driver
Single-phase pulse output
(Variable duty ratio)
CPM2B
Pulse output 0: 01000
Relay
COM COM
Motor driver Relay
Pulse output 1: 01001 Pulse output 1: 01001
COM COM
Pulse plus direction output
CPM2B
Pulse output 0: 01000
COM
Direction output: 01001
COM
Motor driver
Increment pulse output
CPM2B
Motor driver
CW input
CW* pulse output: 01000
COM
Direction input
CCW input
CCW* pulse output: 01001
COM
Output Wiring
Precautions
Note *CW is clockwise and CCW is counter-clockwise.
Observe the following precautions to protect the PC’s internal components.
Output Short Protection
The output or internal circuitry might be damaged when the load connected to an output is short-circuited, so it is recommended to install a protective fuse in each output circuit.
Inductive Loads
When connecting an inductive load to an input, connect a surge protector or diode in parallel with the load.
The surge protector’s components should have the following ratings:
Relay Output
OUT
CPM2B
COM
Surge protector
Relay Output
Transistor Output
(Sinking) CPM2B
OUT
COM
Diode
51
Wiring and Connections Section 3-5
The diode should satisfy the following requirements:
Peak reverse-breakdown voltage must be at least 3 times the load voltage.
Average rectified current must be 1 A.
Inrush Current Considerations
When a relay or transistor output is used to switch a load with a high inrush current such as an incandescent lamp, suppress the inrush current as shown below.
Countermeasure 1
OUT OUT
Countermeasure 2
R
R
COM COM
Providing a dark current of approx. one-third of the rated value through an incandescent lamp
Providing a limiting resistor
Fuse Insertion
The CPM2B with transistor output may burn if the load is short-circuited, therefore, insert a protective fuse in series with the load.
52
SECTION 4
Memory Areas
This section describes the structure of the PC memory areas and explains how to use them.
4-1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 I/O Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 SR Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 AR Area
4-5 PC Setup
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-1 Changing the PC Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-2 PC Setup Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Error Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
64
64
65
54
54
55
58
69
53
Introduction Section 4-1
4-1 Introduction
Most data areas in the CPM2B can be accessed as bits or words. (The TR area can be accessed by bit address only and the DM area can be accessed by word address only.)
The following diagram shows the structure of the IR area and the relationship between bit and word addresses.
Bit number
IR 000
IR 001
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit addresses
IR 00011
Word Bit number
IR 010
IR 011 IR 01107
Word Bit number
Data area
Input area
Output area
Work area
SR area
TR area
Size
160 bits
(10 words)
160 bits
(10 words)
928 bits
(58 words)
448 bits
(28 words)
8 bits
HR area
AR area
320 bits
(20 words)
384 bits
(24 words)
LR area 256 bits
(16 words)
Timer/Counter area
DM area
Read/write
256 bits
2,026 words
Words Bits
IR 000 to IR 009 IR 00000 to IR 00915
(See note 1.)
IR 010 to IR 019 IR 01000 to IR 01915
These bits can be allocated to the external
I/O terminals.
Function
IR 020 to IR 049
IR 200 to IR 227
SR 228 to
SR 255
TR 0 to TR 7
HR 00 to HR 19
IR 02000 to IR 04915
IR 20000 to IR 22715
Work bits can be freely used within the program.
SR 22800 to SR 25515 These bits serve specific functions such as flags and control bits.
HR 0000 to HR 1915
These bits are used to temporarily store
ON/OFF status at program branches.
These bits store data and retain their
ON/OFF status when power is turned off.
AR 00 to AR 23
LR 00 to LR 15
AR 0000 to AR 2315
LR 0000 to LR 1515
TIM/CNT 000 to TIM/CNT 255
DM 0000 to DM 1999
DM 2022 to DM 2047
Error log 22 words DM 2000 to DM 2021
Read-only 456 words DM 6144 to DM 6599
PC Setup 56 words DM 6600 to DM 6655
These bits serve specific functions such as flags and control bits.
Used for a 1:1 data link with another PC.
The same numbers are used for both timers and counters.
DM area data can be accessed in word units only. Word values are retained when the power is turned off.
The read-only area and PC Setup cannot be overwritten from program. Change these settings with a Programming Device.
Note 1. Input bits IR 00108 to IR 00111 reflect the status of the DIP switch on the
CPU Board.
2. The contents of the HR area, AR area, Counter area, and read/write DM area are backed up by the CPU Board’s backup battery or capacitor. If the battery or capacitor discharges completely, memory contents will be returned to their default settings.
3. The program and data in DM 6144 to DM 6655 are stored in flash memory.
4-1-1 Functions
IR Area The functions of the IR area are explained below.
IR area bits in the input and output areas are allocated to terminals on the CPU
Board and Expansion I/O Boards. They reflect the ON/OFF status of input and output signals. Input bits begin at IR 00000, and output bits begin at IR 01000.
54
I/O Allocation Section 4-2
Work Bits
SR Area
TR Area
HR Area
AR Area
LR Area
Timer/Counter Area
DM Area
IR words that are not allocated to inputs or outputs can be used as work words.
The work bits can be used freely within the program. They can only be used within the program, however, and not for direct external I/O.
These bits mainly serve as flags for CPM2B operation or contain present and set values for various functions. SR 253 to SR 255 are read-only. Refer to 4-3 SR
Area for details on the various bit functions.
When a complex ladder diagram cannot be programmed in mnemonic code just as it is, these bits are used to temporarily store ON/OFF execution conditions at program branches. They are used only for mnemonic code. When programming directly with ladder diagrams using the Support Software, TR bits are automatically processed for you.
The same TR bits cannot be used more than once within the same instruction block, but can be used again in different instruction blocks. The ON/OFF status of TR bits cannot be monitored from a Programming Device.
These bits retain their ON/OFF status even after the PC power supply has been turned off or when operation begins or stops. They are used in the same way as work bits.
These bits mainly serve as flags related to PC operation. These bits retain their status even after the PC power supply has been turned off or when operation begins or stops. Refer to 4-4 AR Area for details on the various bit functions.
When the CPM2B is linked 1:1 with another CPM2B or a CPM1/CPM1A/
CPM2A/CPM2C/SRM1(-V2), a CQM1, a C200HS or a C200HX/HG/HE PC, these bits are used to share data.
LR words can be used as work words when they are not used for a 1:1 PC Link.
This area is used to manage timers and counters created with TIM, TIMH(15),
TMHH(––), TIML(––), CNT, and CNTR(12). The same numbers are used for both timers and counters and each number can be used only once in the user program. Do not use the same TC number twice even for different instructions.
Use TC numbers 000 to 003 for TIMH(15) and TC numbers 004 to 007 for
TMHH(––). When these timer numbers are used, timing is performed as an interrupt process and the cycle time is not affected.
TC numbers are used to create timers and counters, as well as to access
Completion Flags and present values (PVs). If a TC number is designated for word data, it will access the present value (PV); if it is used for bit data, it will access the Completion Flag for the timer/counter.
DM area data is accessed in word units only. The contents of the DM area are retained even after the PC power supply has been turned off or when operation begins or stops.
DM words DM 0000 to DM 1999 and DM 2022 to DM 2047 can be used freely in the program; other DM words are allocated specific functions.
DM 2000 to DM 2021 contain the error log information. Refer to Section 4-6 Error
Log for details on the error log.
DM 6600 to DM 6655 contain the PC Setup. Refer to 4-5 PC Setup for details.
4-2 I/O Allocation
IR bits are allocated to actual input terminals and output terminals on the CPU
Board and Expansion I/O Boards. IR words that are not allocated to inputs or outputs can be used as work words.
55
I/O Allocation
CPU Board I/O Allocation
Section 4-2
CPU Board inputs are allocated input bits starting from IR 00000 and CPU Board outputs are allocated output bits starting from IR 01000. Input bits IR 00108 to
IR 00111 are allocated to the CPU Board’s DIP switch inputs.
16 inputs
IR 00000 to IR 00007
IR 00100 to IR 00107
16 outputs
IR 01000 to IR 01007
IR 01100 to IR 01107
Bits
Inputs
IR 000
IR 001
Outputs
IR 010
IR 011
15 14 13
Do not use
12 11 10 09 08
ÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉ
07 06 05 04 03 02 01 00
Expansion I/O Board I/O
Allocation
Note 1. The unused bits in IR 000 and IR 001 cannot be used as work bits.
2. IR 00108 to IR 00111 are used as an input DIP switch.
Up to 3 Expansion I/O Boards can be connected.
Input bits are allocated to Expansion I/O Boards starting from word (m+1), where
“m” is the last input word allocated to the CPU Board or to the previous Expansion I/O Board if one is already connected.
Output bits are allocated to Expansion I/O Boards starting from word (n+1), where “n” is the last output word allocated to the CPU Board or to the previous
Expansion I/O Board if one is already connected.
16 inputs
Bits 00 to 15 in IR (m+1)
16 outputs
Bits 00 to 15 in IR (n+1)
Inputs
Bits
Outputs m+1 n+1
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
CPU Board and One
Expansion I/O Board
The following example shows the I/O allocation when one Expansion I/O Board is connected to the CPU Board. Expansion I/O Board inputs are allocated
IR 00200 through IR 00215 and the outputs are allocated IR 01200 through
IR 01215.
Bits
Inputs
IR 000
IR 001
IR 002
IR 010
Outputs IR 011
IR 012
15 14 13
Do not use as work bits.
12 11 10 09 08
ÍÍÍÍÍÍÍ
07
ÍÍÍÍÍÍÍ
06 05 04 03 02 01 00
56
I/O Allocation
CPU Board and Three
Expansion I/O Boards
CPU Board
(32 I/O points)
16 inputs
IR 00000 to IR 00007
IR 00100 to IR 00107
Section 4-2
The following example shows the I/O allocation when three Expansion I/O
Boards are connected to the CPU Board.
Expansion I/O Board
(32 I/O points)
16 inputs
IR 00200 to IR 00215
Expansion I/O Board
(32 I/O points)
16 inputs
IR 00300 to IR 00315
Expansion I/O Board
(32 I/O points)
16 inputs
IR 00400 to IR 00415
16 outputs
IR 01000 to IR 01007
IR 01100 to IR 01107
16 outputs
IR 01200 to IR 01215
16 outputs
IR 01300 to IR 01315
16 outputs
IR 01400 to IR 01415
Bits
Inputs
IR 000
IR 001
IR 002
IR 003
IR 004
IR 010
IR 011
Outputs IR 012
IR 013
IR 014
15 14 13
Do not use as work bits.
12 11 10 09 08
ÉÉÉÉÉÉÉ
07
ÉÉÉÉÉÉÉ
06 05 04 03 02 01 00
57
SR Area Section 4-3
4-3 SR Area
These bits mainly serve as flags related to CPM2A/CPM2C operation or contain present and set values for various functions. The functions of the SR area are explained in the following table.
Note “Read-only” words and bits can be read as status in controller PC operation, but they cannot be written from the ladder program. Bits and words that are “Not used” are also read-only.
Word(s)
SR 228,
SR 229
SR 230,
SR 231
SR 232 to
SR 235
SR 236 to
SR 239
SR 240
SR 241
SR 242
SR 243
SR 244
SR 245
SR 246
SR 247
SR 248,
SR 249
SR 250
SR 251
Bit(s) Function
00 to 15 Pulse Output PV 0
Contains the pulse output PV (–16,777,215 to 16,777,215). SR 22915 acts as the sign bit; a negative number is indicated when SR 22915 is ON.
(The same PV data can be read immediately with PRV(62).)
Only Pulse Output PV 0 is used for ACC(––).
00 to 15 Pulse Output PV 1
Contains the pulse output PV (–16,777,215 to 16,777,215). SR 23115 acts as the sign bit; a negative number is indicated when SR 23115 is ON.
(The same PV data can be read immediately with PRV(62).)
00 to 15 Macro Function Input Area
Contains the input operands for MCRO(99).
(Can be used as work bits when MCRO(99) is not used.)
00 to 15 Macro Function Output Area
Contains the output operands for MCRO(99).
(Can be used as work bits when MCRO(99) is not used.)
00 to 15 Interrupt Input 00003 Counter Mode SV
SV when interrupt input 00003 is used in counter mode (4 digits hexadecimal).
(Can be used as work bits when interrupt input 00003 is not used in counter mode.)
00 to 15 Interrupt Input 00004 Counter Mode SV
SV when interrupt input 00004 is used in counter mode (4 digits hexadecimal).
(Can be used as work bits when interrupt input 00004 is not used in counter mode.)
00 to 15 Interrupt Input 00005 Counter Mode SV
SV when interrupt input 00005 is used in counter mode (4 digits hexadecimal).
(Can be used as work bits when interrupt input 00005 is not used in counter mode.)
00 to 15 Interrupt Input 00006 Counter Mode SV
SV when interrupt input 00006 is used in counter mode (4 digits hexadecimal).
(Can be used as work bits when interrupt input 00006 is not used in counter mode.)
00 to 15 Interrupt Input 00003 Counter Mode PV
Counter PV when interrupt input 00003 is used in counter mode (4 digits hexadecimal).
00 to 15 Interrupt Input 00004 Counter Mode PV
Counter PV when interrupt input 00004 is used in counter mode (4 digits hexadecimal).
00 to 15 Interrupt Input 00005 Counter Mode PV
Counter PV when interrupt input 00005 is used in counter mode (4 digits hexadecimal).
00 to 15 Interrupt Input 00006 Counter Mode PV
Counter PV when interrupt input 00006 is used in counter mode (4 digits hexadecimal).
00 to 15 High-speed Counter PV Area
The PVs can have the following values. The leftmost digit of SR 249 acts as the sign indicator; a negative number is indicated when the leftmost digit of SR 249 is F.
Differential phase input mode:
Pulse +direction input mode:
–8,388,608 (F838 8608) to 8,388,607
–8,388,608 (F838 8608) to 8,388,607
Up/down pulse input mode:
Increment mode:
Synchronized pulse control:
–8,388,608 (F838 8608) to 8,388,607
0 to 16,777,215
0 to 20,000 Hz
(Can be used as work bits when the high-speed counter is not used.)
00 to 15 Analog Setting 0
Used to store the 4-digit BCD set value (0000 to 0200) from analog control 0.
00 to 15 Analog Setting 1
Used to store the 4-digit BCD set value (0000 to 0200) from analog control 1.
Read/ write
Readonly
Read/ write
Readonly
58
SR Area Section 4-3
Word(s)
SR 252
SR 253
Bit(s)
00 High-speed Counter Reset Bit
Function Read/ write
Read/ write
13
14
15
01 to 03 Not used.
04 Pulse Output 0 PV Reset Bit
Turn ON to clear the PV of pulse output 0.
05
06, 07
Pulse Output 1 PV Reset Bit
Turn ON to clear the PV of pulse output 1.
Not used.
08
09
10
11
12
Peripheral Port Reset Bit
Turn ON to reset the peripheral port. Automatically turns OFF when reset is complete.
RS-232C Port Reset Bit
Turn ON to reset the RS-232C port. Automatically turns OFF when reset is complete.
PC Setup Reset Bit
Turn ON to initialize PC Setup (DM 6600 through DM 6655). Automatically turns OFF again when reset is complete. Only effective if the PC is in PROGRAM mode.
Forced Status Hold Bit (See note.)
OFF: The forced status of bits that are forced set/reset is cleared when switching between PROGRAM mode and MONITOR mode.
ON: The status of bits that are forced set/reset are maintained when switching between
PROGRAM mode and MONITOR mode.
The PC Setup can be set to maintain the status of this bit when the PC is turned off.
I/O Hold Bit (See note.)
OFF: IR and LR bits are reset when starting or stopping operation.
ON: IR and LR bit status is maintained when starting or stopping operation.
The PC Setup can be set to maintain the status of this bit when the PC is turned off.
13
14
Not used.
Error Log Reset Bit
Turn ON to clear error log. Automatically turns OFF again when operation is complete.
Not used.
15
00 to 07 FAL Error Code
The error code (a 2-digit number) is stored here when an error occurs. The FAL number is stored here when FAL(06) or FALS(07) is executed. This word is reset (to 00) by executing a FAL 00 instruction or by clearing the error from a Programming Device.
08 Battery Error Flag
Turns ON when the CPU Board backup battery’s voltage is too low.
09 Cycle Time Overrun Flag
Turns ON when a cycle time overrun occurs (i.e., when the cycle time exceeds the maximum cycle time set in the PC Setup).
10,11
12
Not used.
Changing RS-232C Setup Flag
Turns ON when the RS-232C port’s settings are being changed.
Always ON Flag
Always OFF Flag
First Cycle Flag
Turns ON for 1 cycle at the start of operation.
Read/ write
Read/ write
Read/ write
Readonly
Read/ write
Readonly
59
AR Area Section 4-4
Word(s)
SR 254
SR 255
Bit(s) Function
00
01
1-minute clock pulse (30 seconds ON; 30 seconds OFF)
0.02-second clock pulse (0.01 second ON; 0.01 second OFF)
02 Negative (N) Flag
Turns ON when the result of a calculation is negative (leftmost bit of binary result ON.)
Not used.
03
04
05
06
07
Overflow (OF) Flag
Turns ON when an overflow occurs in a signed binary calculation.
Underflow (UF) Flag
Turns ON when an underflow occurs in a signed binary calculation.
Differential Monitor Complete Flag
Turns ON when differential monitoring is completed.
STEP(08) Execution Flag
Turns ON for 1 cycle only at the start of process based on STEP(08).
08 to 15 Not used.
00
01
02
03
04
05
06
0.1-second clock pulse (0.05 second ON; 0.05 second OFF)
0.2-second clock pulse (0.1 second ON; 0.1 second OFF)
1.0-second clock pulse (0.5 second ON; 0.5 second OFF)
Instruction Execution Error (ER) Flag
Turns ON when an error occurs during execution of an instruction.
Carry (CY) Flag
Turns ON when there is a carry in the results of an instruction execution.
Greater Than (GR) Flag
Turns ON when the result of a comparison operation is “greater.”
Equals (EQ) Flag
Turns ON when the result of a comparison operation is “equal,” or when the result of an instruction execution is 0.
07 Less Than (LE) Flag
Turns ON when the result of a comparison operation is “less.”
08 to 15 Not used.
Read/ write
Readonly
Readonly
Readonly
Note DM 6601 in the PC Setup can be set to maintain the previous status of the
Forced Status Hold Bit (SR 25211) and the I/O Hold Bit (SR 25212) when power is turned OFF. Refer to 4-5 PC Setup for details.
4-4 AR Area
These bits mainly serve as flags related to CPM2B operation. These bits retain their status even after the CPM2B power supply has been turned off or when operation begins or stops.
Word(s)
AR 00,
AR 01
AR 02
AR 03 to
AR 07
Bit(s)
00 to 15 Not used.
Function
00 to 07 Not used.
08 to 11 Number of Expansion I/O Boards Connected
12 to 15 Not used.
00 to 15 Not used.
60
AR Area Section
Word(s)
AR 08
AR 09
AR 10
Bit(s)
00 to 03 RS-232C Port Error Code (1-digit BCD)
0: Normal completion
1: Parity error
2: Frame error
3: Overrun error
Function
04
05
06
07
RS-232C Communications Error Flag
Turns ON when an RS-232C port communications error occurs.
RS-232C Transmit Ready Flag
Turns ON when the PC is ready to transmit data. (No-protocol and Host Link only)
RS-232C Reception Completed Flag
Turns ON when the PC has completed reading data. (No-protocol only)
RS-232C Reception Overflow Flag
Turns ON when an overflow has occurred. (No-protocol only)
08 to 11 Peripheral Port Error Code (1-digit BCD)
0: Normal completion
1: Parity error
2: Frame error
3: Overrun error
12
13
14
15
Peripheral Port Communications Error Flag
Turns ON when a peripheral port communications error occurs.
Peripheral Port Transmit Ready Flag
Turns ON when the PC is ready to transmit data. (No-protocol and Host Link only)
Peripheral Port Reception Completed Flag
Turns ON when the PC has completed reading data. (No-protocol only)
Peripheral Port Reception Overflow Flag
Turns ON when an overflow has occurred. (No-protocol only)
00 to 15 RS-232C Port Reception Counter (4-digit BCD)
Valid only when no-protocol communications are used.
00 to 15 Peripheral Port Reception Counter (4-digit BCD)
Valid only when no-protocol communications are used.
4-4
61
AR Area
Word(s)
AR 11
(Note 1)
AR 12
(Note 1)
Bit(s) Function
00 to 07 High-speed Counter Range Comparison Flags
00 ON: Counter PV is within comparison range 1
01 ON: Counter PV is within comparison range 2
02 ON: Counter PV is within comparison range 3
03 ON: Counter PV is within comparison range 4
04 ON: Counter PV is within comparison range 5
05 ON: Counter PV is within comparison range 6
06 ON: Counter PV is within comparison range 7
07 ON: Counter PV is within comparison range 8
08
09
High-speed Counter Comparison Operation
ON: Operating
OFF: Stopped
High-speed Counter PV Overflow/Underflow Flag
ON: An overflow or underflow occurred.
OFF: Normal operation
10
11
12
Not used.
Pulse Output 0 Output Status
ON: Pulse output 0 is accelerating or decelerating.
OFF: Pulse output 0 is operating at a constant rate.
Pulse Output 0 Overflow/Underflow Flag
ON: An overflow or underflow occurred.
OFF: Normal operation
13
14
Pulse Output 0 Pulse Quantity Set Flag
ON: Pulse quantity has been set.
OFF: Pulse quantity has not been set.
Pulse Output 0 Pulse Output Completed Flag
ON: Completed
OFF: Not completed
15 Pulse Output 0 Output Status
ON: Pulses being output.
OFF: Stopped.
00 to 10 Not used.
11 Pulse Output 1 Output Status
ON: Pulse output 1 is accelerating or decelerating.
OFF: Pulse output 1 is operating at a constant rate.
12 Pulse Output 1 Overflow/Underflow Flag
ON: An overflow or underflow occurred.
OFF: Normal operation
13
14
15
Pulse Output 1 Pulse Quantity Set Flag
ON: Pulse quantity has been set.
OFF: Pulse quantity has not been set.
Pulse Output 1 Pulse Output Completed Flag
ON: Completed
OFF: Not completed
Pulse Output 1 Output Status
ON: Pulses being output.
OFF: Stopped.
Section 4-4
62
AR Area Section 4-4
AR 16
AR 17
(Note 2)
AR 18
(Note 2)
AR 19
(Note 2)
AR 20
(Note 2)
Word(s)
AR 13
AR 14
AR 15
Bit(s)
00
01
02
03, 04
05
06, 07
08
09
10
11
12
13
14
Function
Power-up PC Setup Error Flag
Turns ON when there is an error in DM 6600 to DM 6614 (the part of the PC Setup area that is read at power-up).
Start-up PC Setup Error Flag
Turns ON when there is an error in DM 6615 to DM 6644 (the part of the PC Setup area that is read at the beginning of operation).
RUN PC Setup Error Flag
Turns ON when there is an error in DM 6645 to DM 6655 (the part of the PC Setup area that is always read).
Not used.
Cycle Time Too Long Flag
Turns ON if the actual cycle time is longer than the cycle time set in DM 6619.
Not used.
Memory Area Specification Error Flag
Turns ON when a non-existent data area address is specified in the program.
Flash Memory Error Flag
Turns ON when there is an error in flash memory.
Read-only DM Error Flag
Turns ON when a checksum error occurs in the read-only DM (DM 6144 to DM 6599).
PC Setup Error Flag
Turns ON when a checksum error occurs in the PC Setup area.
Program Error Flag
Turns ON when a checksum error occurs in the program memory (UM) area, or when an improper instruction is executed.
Expansion Instruction Area Error Flag
Turns ON when a checksum error occurs in the expansion instruction assignments area. The expansion instruction assignments will be cleared to their default settings.
Data Save Error Flag
Turns ON if data could not be retained with the backup battery or capacitor.
The following words are normally backed up:
DM read/write words (DM 0000 to DM 1999 and DM 2022 to DM 2047), Error Log (DM 2000 to
DM 2021), HR area, counter area, SR 25511, SR 25512 (if DM 6601 is set to hold I/O memory at startup), AR 23, operating mode (if DM 6600 is set to use the previous operating mode).
If the above words cannot be retained, all data will be cleared except that AR 2114 will be turned
ON in CPU Boards equipped with a clock. The CPU Board will start in PROGRAM mode if DM
6600 is set to use the previous operating mode. (If DM 6604 is set to generate an error, the PC will start in PROGRAM mode regardless.)
Not used.
15
00 to 15 Maximum Cycle Time (4-digit BCD, see note 3)
The longest cycle time since the beginning of operation is stored. It is not cleared when operation stops, but it is cleared when operation starts again.
00 to 15 Current Cycle Time (4-digit BCD, see note 3)
The most recent cycle time during operation is stored. The Current Cycle Time is not cleared when operation stops.
00 to 15 Not used.
00 to 07 Minute (00 to 59, BCD)
08 to 15 Hour (00 to 59, BCD)
00 to 07 Second (00 to 59, BCD)
08 to 15 Minute (00 to 59, BCD)
00 to 07 Hour (00 to 23, BCD)
08 to 15 Day of the Month (01 to 31, BCD)
00 to 07 Month (01 to 12, BCD)
08 to 15 Year (00 to 99, BCD)
63
PC Setup Section 4-5
Word(s)
AR 21
(Note 2)
AR 22
AR 23
Bit(s)
00 to 07 Day of the Week (00 to 06, BCD)
00: Sunday 01: Monday
04: Thursday 05: Friday
Function
02: Tuesday
06: Saturday
03: Wednesday
08 to 12 Not used.
13 30-second Compensation Bit
Turn this bit ON to round off to the nearest minute. When the seconds are 00 to 29, the seconds are cleared to 00 and the rest of the time setting is left unchanged. When the seconds are 30 to
59, the seconds are cleared to 00 and the time is incremented by one minute.
14
15
Clock Stop Bit
Turn this bit ON to stop the clock. The time/date can be overwritten while this bit is ON.
Clock Set Bit
To change the time/date, turn ON AR 2114, write the new time/date (being sure to leave AR
2114 ON), and then turn this bit ON to enable a new time/date setting. The clock will restart and both AR 2114 and AR 2115 will be turned OFF automatically.
00 to 15 Not used.
00 to 15 Power-off Counter (4-digit BCD)
This is the count of the number of times that the power has been turned off.
To clear the count, write “0000” from a Programming Device.
Note 1. The same data can be read immediately with PRV(62).
2. The time and date can be set while AR 2114 is ON. The new setting becomes effective when AR 2115 is turned ON. (AR 2114 and AR 2115 are turned OFF automatically when the new setting goes into effect.)
3. The units for the maximum and current cycle times are determined by the setting in bits 08 to 15 of DM 6618. A setting of 00 specifies 0.1-ms units, 01 specifies 0.1-ms units, 02 specifies 1-ms units, and 03 specifies 10-ms units.
4-5 PC Setup
The PC Setup comprises various operating parameters that control PC operation. In order to make the maximum use of PC functionality when using interrupt processing and communications functions, the PC Setup may be customized according to operating conditions.
After the PC Setup has been changed, be sure to switch the CPM2B to MON-
ITOR or RUN mode or turn the power OFF and then ON again.
4-5-1 Changing the PC Setup
The PC Setup settings in DM 6600 to DM 6655 can be changed from a Programming Device. The CPM2B must be in PROGRAM mode in order to change the settings in DM 6600 to DM 6644. The settings in DM 6645 to DM 6655 can be changed in MONITOR or PROGRAM mode, but CPM2B’s cycle time will be long if the settings are changed in MONITOR mode.
All of the PC Setup settings are set to their defaults when the CPM2B is shipped.
The default values for the PC Setup are 0000 for all words (except for the low battery error enable in DM 6655 bits 12 to 15).
Effectiveness of Changes PC Setup settings are accessed at various times depending on the setting, as described below.
Words Timing
DM 6600 to DM 6614 Accessed only when PC’s power supply is turned ON.
DM 6615 to DM 6644 Accessed only when program execution begins.
DM 6645 to DM 6655 Accessed regularly when the power is ON.
Since changes in the PC Setup become effective only at the times given above, the PC will have to be restarted to make changes in DM 6600 to DM 6614 effec-
64
PC Setup Section 4-5
Errors in the PC Setup tive, and program execution will have to be restarted to make changes in
DM 6615 to DM 6644 effective.
If an incorrect PC Setup setting is accessed, a non-fatal error (error code 9B) will be generated, the corresponding error flag (AR 1300 to AR 1302) will be turned
ON, and the default setting will be used instead of the incorrect setting.
4-5-2 PC Setup Settings
Word(s) Bit(s)
Startup Processing (DM 6600 to DM 6614)
Function
The following settings are effective after transfer to the PC only after the PC is restarted.
DM 6600 00 to 07 Startup mode (effective when bits 08 to 15 are set to 02).
00: PROGRAM; 01: MONITOR; 02: RUN
08 to 15 Startup mode designation
00: According to communications switch SW201 and peripheral port connection
(See table at the bottom of this page.)
01: Continue operating mode last used before power was turned OFF.
02: Setting in 00 to 07
DM 6601
DM 6602
00 to 07 Not used.
08 to 11 IOM Hold Bit (SR 25212) Status at Startup
0: Reset to 0; 1: Maintain previous status
12 to 15 Forced Status Hold Bit (SR 25211) Status at Startup
0: Reset to 0; 1: Maintain previous status
00 to 03 Program memory write-protection
0: Program memory unprotected
1: Program memory write-protected (except DM 6602 itself)
DM 6603
DM 6604
DM 6605 to
DM 6614
04 to 07 Programming Console display language
0: English; 1: Japanese
08 to 11 Expansion instruction function code assignments
0: Default settings
1: User assignments
12 to 15 Not used.
00 to 15 Not used.
00 to 07 00: A memory error will not be generated if data could not be retained by the battery.
01: A memory error will be generated if data could not be retained by the battery.
08 to 15 Not used.
00 to 15 Not used.
Note The startup operating mode will be as shown in the following table is bits 08 to 15 of DM 6600 are set to 00.
Peripheral port connected to
Nothing
Programming
Console
Other Programming
Device
PROGRAM
Communications switch SW201
OFF ON
RUN
Mode set on Programming
Console mode switch
PROGRAM (The CPM2B will not be able to communicate with Programming Console.)
PROGRAM PROGRAM (The CPM2B will not be able to communicate with Programming Device.)
Word(s) Bit(s)
Cycle Time Settings (DM 6615 to DM 6619)
Function
The following settings are effective after transfer to the PC the next time operation is started.
DM 6615 00 to 15 Not used.
65
PC Setup Section 4-5
Word(s)
DM 6616
DM 6617
DM 6618
DM 6619
Bit(s) Function
00 to 07 Servicing time for RS-232C port (Effective when bits 08 to 15 are set to 01.)
00 to 99 (BCD): Percentage of cycle time used to service RS-232C port.
08 to 15 RS-232C port servicing setting enable
00: 5% of the cycle time
01: Use time in bits 00 to 07.
00 to 07 Servicing time for peripheral port (Effective when bits 08 to 15 are set to 01.)
00 to 99 (BCD): Percentage of cycle time used to service peripheral.
08 to 15 Peripheral port servicing setting enable
00: 5% of the cycle time
01: Use time in bits 00 to 07.
00 to 07 Cycle monitor time (Effective when bits 08 to 15 are set to 01, 02, or 03.)
00 to 99 (BCD): Setting (See bits 08 to 15, below.)
A fatal error will be generated and PC operation will stop if the cycle time exceeds the cycle monitor time set here.
08 to 15 Cycle monitor enable (Setting in 00 to 07
×
units; 99 s max.)
00: 120 ms (setting in bits 00 to 07 disabled)
01: Setting units: 10 ms
02: Setting units: 100 ms
03: Setting units: 1 s
00 to 15 Minimum cycle time
0000: Variable (no minimum)
0001 to 9999 (BCD): Minimum time in ms
Interrupt Processing (DM 6620 to DM 6639)
The following settings are effective after transfer to the PC the next time operation is started.
DM 6620
DM 6621
DM 6622
DM 6623
DM 6624
DM 6625
00 to 03 Input time constant for IR 00000 to IR 00002
0: 10 ms; 1: 1 ms; 2: 2 ms; 3: 3 ms; 4: 5 ms; 5: 10 ms; 6: 20 ms; 7: 40 ms; 8: 80 ms
04 to 07 Input time constant for IR 00003 and IR 00004 (Setting same as bits 00 to 03)
08 to 11 Input time constant for IR 00005 and IR 00006 (Setting same as bits 00 to 03)
12 to 15 Input time constant for IR 00007 to IR 00011 (Setting same as bits 00 to 03)
00 to 07 Input time constant for IR 001
00: 10 ms
05: 10 ms
01: 1 ms
06: 20 ms
02: 2 ms
07: 40 ms
03: 3 ms
08: 80 ms
04: 5 ms
08 to 15 Input constant for IR 002 (Setting same as for IR 001.)
00 to 07 Input constant for IR 003 (Setting same as for IR 001.)
08 to 15 Input constant for IR 004 (Setting same as for IR 001.)
00 to 07 Input constant for IR 005 (Setting same as for IR 001.)
08 to 15 Input constant for IR 006 (Setting same as for IR 001.)
00 to 07 Input constant for IR 007 (Setting same as for IR 001.)
08 to 15 Input constant for IR 008 (Setting same as for IR 001.)
00 to 07 Input constant for IR 009 (Setting same as for IR 001.)
08 to 15 Not used.
00 to 15 Not used.
DM 6626 to
DM 6627
DM6628 00 to 03 Interrupt enable for IR 00003 (0: Normal input; 1: Interrupt input; 2: Quick-response)
04 to 07 Interrupt enable for IR 00004 (0: Normal input; 1: Interrupt input; 2: Quick-response)
08 to 11 Interrupt enable for IR 00005 (0: Normal input; 1: Interrupt input; 2: Quick-response)
12 to 15 Interrupt enable for IR 00006 (0: Normal input; 1: Interrupt input; 2: Quick-response)
DM 6629
DM 6630 to
DM 6641
00 to 03 PV coordinate system for pulse output 0
0: Relative coordinates; 1: Absolute coordinates
04 to 07 PV coordinate system for pulse output 1
0: Relative coordinates; 1: Absolute coordinates
08 to 15 Not used.
00 to 15 Not used.
66
PC Setup Section 4-5
Word(s) Bit(s)
High-speed Counter Settings (DM 6642 to DM 6644)
Function
The following settings are effective after transfer to the PC the next time operation is started.
DM 6642 00 to 03 High-speed counter mode (Effective only when bits 08 to 15 are not set to 00.)
0: Differential phase mode (5 kHz)
1: Pulse + direction input mode (20 kHz)
2: Up/down input mode (20 kHz)
4: Increment mode (20 kHz)
04 to 07 High-speed counter reset mode (Effective only when bits 08 to 15 are set to 01.)
0: Z phase and software reset; 1: Software reset only
08 to 15 High-speed counter/Synchronized pulse control for IR 00000 to IR 00002
00: Don’t use either function.
01: Use as high-speed counters.
02: Use for synchronized pulse control (10 to 500 Hz).
03: Use for synchronized pulse control (20 Hz to 1 kHz).
04: Use for synchronized pulse control (300 Hz to 20 kHz).
00 to 15 Not used.
DM 6643,
DM 6644
RS-232C Port Communications Settings
The following settings are effective after transfer to the PC.
If CPU Board communications switch SW202 is ON, communications through the RS-232C port are governed by the default settings (all 0) regardless of the settings in DM 6645 through DM 6649.
DM 6645 00 to 03 Port settings
0: Standard (1 start bit, 7 data bits, even parity, 2 stop bits, 9,600 bps, Host Link unit number: 0)
1: Settings in DM 6646
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
04 to 07 CTS control setting
0: Disable CTS control; 1: Enable CTS control
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
08 to 11 Link words for 1:1 PC Link
0: LR 00 to LR 15 (Any other settings are ineffective.)
12 to 15 Communications mode
0: Host Link; 1: No-protocol; 2: 1:1 PC Link Slave; 3: 1:1 PC Link Master; 4: NT Link
DM 6646
DM 6647
(Any other setting causes a non-fatal error and turns ON AR 1302.)
00 to 07 Baud rate
00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps
08 to 15 Frame format
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
10:
11:
Start bits
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
1 bit
Data bits
7 bits
7 bits
7 bits
7 bits
7 bits
7 bits
8 bits
8 bits
8 bits
8 bits
8 bits
8 bits
Stop bits
1 bit
1 bit
1 bit
2 bits
2 bits
2 bits
1 bit
1 bit
1 bit
2 bits
2 bits
2 bits
Parity
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits), causes a non-fatal error, and turns ON AR 1302.)
00 to 15 Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.)
(Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.)
67
PC Setup Section 4-5
Word(s)
DM 6648
DM 6649
Bit(s)
00 to 07 Node number (Host Link)
00 to 31 (BCD)
Function
(Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR
1302.)
08 to 11 Start code selection for no-protocol communications
0: Disables start code; 1: Enables start code in DM 6649
(Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.)
12 to 15 End code selection for no-protocol communications
0: Disables end code; 1: Enables end code in DM 6649; 2: Sets end code of CR, LF.
(Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.)
00 to 07 Start code (00 to FF)
(This setting is valid only when bits 8 to 11 of DM 6648 are set to 1.)
08 to 15 When bits 12 to 15 of DM 6648 set to 0:
Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes)
When bits 12 to 15 of DM 6648 set to 1:
Sets the end code. (00 to FF)
Peripheral Port Communications Settings
The following settings are effective after transfer to the PC.
If CPU Board Communications Switch SW202 is ON, communications through the peripheral port are governed by the default settings (all 0) regardless of the settings in DM 6650 through DM 6654. Communications through the peripheral port are governed by the Programming Console protocol if Communications Switch SW201 is OFF.
DM 6650 00 to 03 Port settings
00: Standard (1 start bit, 7 data bits, even parity, 2 stop bits, 9,600 bps, Host Link unit number: 0)
01: Settings in DM 6651
DM 6651
(Any other setting specifies standard settings, causes a non-fatal error, and turns ON AR 1302.)
04 to 11 Not used.
12 to 15 Communications mode
0: Host Link or peripheral bus; 1: No-protocol
(Any other setting specifies Host Link, causes a non-fatal error, and turns ON AR 1302.)
00 to 07 Baud rate
00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps
08 to 15 Frame format
Start bits
00: 1 bit
01: 1 bit
02: 1 bit
03: 1 bit
04: 1 bit
05: 1 bit
06: 1 bit
07: 1 bit
08: 1 bit
09: 1 bit
10: 1 bit
11: 1 bit
Data bits
7 bits
7 bits
7 bits
7 bits
7 bits
7 bits
8 bits
8 bits
8 bits
8 bits
8 bits
8 bits
Stop bits
1 bit
1 bit
1 bit
2 bits
2 bits
2 bits
1 bit
1 bit
1 bit
2 bits
2 bits
2 bits
Parity
Even
Odd
None
Even
Odd
None
Even
Odd
None
Even
Odd
None
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop bits), causes a non-fatal error, and turns ON AR 1302.)
68
Error Log Section 4-6
Word(s)
DM 6652
DM 6653
Bit(s) Function
00 to 15 Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.)
(Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON AR 1302.)
00 to 07 Node number (Host Link)
00 to 31 (BCD)
(Any other setting specifies a node number of 00, causes a non-fatal error, and turns ON AR
1302.)
08 to 11 Start code selection for no-protocol communications
0: Disables start code; 1: Enables start code in DM 6654
(Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.)
DM 6654
12 to 15 End code selection for no-protocol communications
0: Disables end code; 1: Enables end code in DM 6654; 2: Sets end code of CR, LF.
(Any other setting disables the end code, causes a non-fatal error, and turns ON AR 1302.)
00 to 07 Start code (00 to FF)
(This setting is valid only when bits 8 to 11 of DM 6653 are set to 1.)
08 to 15 When bits 12 to 15 of DM 6653 set to 0:
Sets the number of bytes to receive. (00: 256 bytes; 01 to FF: 1 to 255 bytes)
Error Log Settings (DM 6655)
The following settings are effective after transfer to the PC.
DM 6655
When bits 12 to 15 of DM 6653 set to 1:
Sets the end code. (00 to FF)
00 to 03 Style
0: Shift after 7 records have been stored
1: Store only first 7 records (no shifting)
2 to F: Do not store records
04 to 07 Not used.
08 to 11 Cycle time monitor enable
0: Generate a non-fatal error for a cycle time that is too long.
1: Do not generate a non-fatal error.
12 to 15 Low battery error enable
0: Generate a non-fatal error for low battery voltage.
1: Do not generate a non-fatal error.
Low battery error detection is disabled (i.e., set to 1) by default in CPU Boards that do not have a clock. If the PC Setup is cleared, the setting will changed to 0 and a low battery error will occur.
4-6 Error Log
DM 2000 Error log pointer
DM 2021 Error log record 1
DM 2022 (3 words used.)
DM 2023
The error log function registers the error code of any fatal or non-fatal error that occurs in the PC. The date and time at which the error occurred are registered along with the error code. The error code is also stored in AR 253.
The error log is stored in DM 2000 through DM 2021. Up to 7 error records can be stored.
Indicates the number of records stored in the log (0 to 7). A 0 indicates no records.
to
DM 2019 Error log record 7
DM 2020 (3 words used.)
DM 2021
Each error log record is configured as follows:
15 8 7
Leading word
Leading word + 1
Leading word + 2
Error classification
Min
Day
Error code
Sec
Hour
Error classification: 00: Non-fatal
80: Fatal
0
Each stored in
2 digits BCD.
Note 1. An error record with an error code of 00 will be stored in the error log for power interruptions. Refer to 7-3 Self-diagnostic Functions for tables listing error codes.
69
Error Log Section 4-6
2. In CPU Boards without a clock, the time that the error occurred will be set to all zeroes.
Error Log Storage Methods
The error log storage method is set in the PC Setup (bits 00 to 03 of DM 6655).
Set any of the following methods.
1, 2, 3...
1. DM 6655 bits 00 to 03 set to 0:
Stores the most recent 7 error log records and discard older records. This is achieved by shifting the records as shown below so that the oldest record
(record 0) is lost whenever a new record is generated.
Lost
Error log record 1
Error log record 2
All records shifted
Error log record 6
Error log record 7
New record added
2. DM 6655 bits 00 to 03 set to 1:
Stores only the first 7 error log records, and ignores any subsequent errors beyond those 7.
3. DM 6655 bits 00 to 03 set to any value other than 0 or 1:
Disables the log so that no records are stored.
The default setting is the first method. Refer to the preceding page for details on the error log settings in DM 6655.
Clearing the Error Log
To clear the entire error log, turn ON SR 25214 from a Programming Device. (After the error log has been cleared, SR 25214 will turn OFF again automatically.)
70
SECTION 5
Instruction Set
The CPM2B PCs have large a programming instruction set that allows for easy programming of complicated control processes. This section provides a brief summary of the instruction set.
5-1 CPM2B Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Alphabetic List by Mnemonic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Expansion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72
73
76
71
CPM2B Function Codes Section 5-1
5-1 CPM2B Function Codes
The following table lists the CPM2B instructions that have fixed function codes.
Each instruction is listed by mnemonic and by instruction name. Use the numbers in the leftmost column as the left digit and the number in the column heading as the right digit of the function code.
Left digit
0
1
2
3
4
5
6
7
8
9
0
NOP
NO
OPERATION
SFT
SHIFT
REGISTER
CMP
COMPARE
CMPL
DOUBLE
COMPARE
(@) XFER
BLOCK
TRANSFER
(@) DIST
SINGLE
WORD
DISTRIBUTE
---
END
END
1
KEEP
KEEP
(@) MOV
MOVE
(@) ADD
BCD ADD
(@) STC
SET CARRY
(@) ADB
BINARY ADD
(@) SUB
BCD
SUBTRACT
(@) CLC
CLEAR
CARRY
(@) SBB
BINARY
SUBTRACT
(@) INI
MODE CON-
TROL
(@) BSET
BLOCK SET
(@) COLL
DATA
COLLECT
(@) SBS
SUBROU-
TINE
ENTRY
2
IL
INTERLOCK
CNTR
REVERS-
IBLE
COUNTER
(@) MVN
MOVE NOT
(@) MUL
BCD
MULTIPLY
---
3
ILC
INTERLOCK
CLEAR
DIFU
DIFFER-
ENTIATE UP
(@) BIN
BCD TO
BINARY
(@) DIV
BCD
DIVIDE
---
JMP
JUMP
4
Right digit
DIFD
DIFFER-
ENTIATE
DOWN
(@) BCD
BINARY TO
BCD
(@) ANDW
LOGICAL
AND
---
(@) ADDL
DOUBLE
BCD ADD
5
JME
JUMP END
TIMH
HIGH-
SPEED
TIMER
(@) ASL
SHIFT LEFT
6
(@) FAL
FAILURE
ALARM AND
RESET
(@) WSFT
WORD
SHIFT
(@) ORW
LOGICAL OR
---
(@) SUBL
DOUBLE
BCD
SUBTRACT
(@) ASR
SHIFT
RIGHT
(@) XORW
EXCLUSIVE
OR
(@) MSG
MESSAGE
DISPLAY
(@) MULL
DOUBLE
BCD
MULTIPLY
(@) DIVL
DOUBLE
BCD
DIVIDE
(@) SPED
SPEED OUT-
PUT
(@) PULS
SET PULSES
(@) SCL
SCALING
7
FALS
SEVERE
FAILURE
ALARM
(@) ASFT
ASYNCHRO-
NOUS SHIFT
REGISTER
(@) ROL
ROTATE
LEFT
(@) XNRW
EXCLUSIVE
NOR
(@) RXD
RECEIVE
8
STEP
STEP
DEFINE
---
(@) ROR
ROTATE
RIGHT
(@) INC
INCREMENT
(@) TXD
TRANSMIT
(@) BCNT
BIT COUNT-
ER
(@) BINL
DOUBLE
BCD-TO-
DOUBLE
BINARY
(@) BCMP
BLOCK
COMPARE
9
SNXT
STEP START
---
(@) COM
COMPLE-
MENT
(@) DEC
DECRE-
MENT
---
(@) MLB
BINARY
MULTIPLY
(@) PRV
HIGH-
SPEED
COUNTER
PV READ
---
(@) DVB
BINARY
DIVIDE
(@) CTBL
COMPARI-
SON TABLE
LOAD
(@) BCDL
DOUBLE
BINARY-TO-
DOUBLE
BCD
(@) STIM
INTERVAL
TIMER
(@) MOVB
MOVE BIT
(@) XCHG
DATA
EXCHANGE
(@) MOVD
MOVE DIGIT
(@) SLD
ONE DIGIT
SHIFT LEFT
(@) SFTR
REVERS-
IBLE SHIFT
REGISTER
---
(@) SRD
ONE DIGIT
SHIFT
RIGHT
(@) TCMP
TABLE
COMPARE
(@) MLPX
4-TO-16
DECODER
(@) ASC
ASCII
CONVERT
(@) DMPX
16-TO-4
ENCODER
---
(@) SDEC
7-SEGMENT
DECODER
---
---
(@) INT
INTERRUPT
CONTROL
SBN
SUBROU-
TINE
DEFINE
RET
SUBROU-
TINE
RETURN
----(@) IORF
I/O
REFRESH
--(@) MCRO
MACRO
Note 1. The shaded areas are function codes to which expansion instructions are allocated by default or to which the user can allocate expansion instructions.
Refer to 5-3 Expansion Instructions for more details.
2. Instruction execution times are the same as those for the CPM2A and
CPM2C. Refer to the Programming Manual (W353) for details.
72
Alphabetic List by Mnemonic Section 5-2
5-2 Alphabetic List by Mnemonic
Dashes (“––”) in the Code column indicate expansion instructions, which do not have fixed function codes. “None” indicates instructions for which function codes are not used.
Mnemonic
ACC (@)
ADB (@)
ADD (@)
––
Code
50
30
ADDL (@) 54
AND None
AND LD None
AND NOT None
ANDW (@) 34
ASC (@) 86
ASFT(@) 17
ASL (@) 25
ASR (@)
AVG
26
––
BCD (@) 24
BCDL (@) 59
BCMP (@) 68
BCNT (@) 67
BIN (@) 23
BINL (@) 58
BSET (@) 71
CLC (@)
CMP
CMPL
CNT
41
20
60
None
CNTR 12
COLL (@) 81
COM (@) 29
CTBL(@) 63
DEC (@)
DIFD
39
14
DIFU 13
DIST (@) 80
DIV (@) 33
DIVL (@) 57
DMPX (@) 77
DVB (@) 53
END
FAL (@)
FALS
FCS (@)
HEX (@)
01
06
07
––
––
HMS
IL
ILC
––
02
03
2
4
2
2
2
4
3
4
4
2
1
3
3
4
4
3
3
3
2
4
4
4
2
4
4
1
1
4
1
4
4
4
2
4
1
2
4
4
4
4
4
4
1
1
Words Name
ACCELERATION CONTROL
BINARY ADD
BCD ADD
DOUBLE BCD ADD
AND
AND LOAD
AND NOT
LOGICAL AND
ASCII CONVERT
ASYNCHRONOUS SHIFT REGISTER
ARITHMETIC SHIFT LEFT
ARITHMETIC SHIFT RIGHT
AVERAGE VALUE
BINARY TO BCD
DOUBLE BINARY-TO-DOUBLE BCD
BLOCK COMPARE
BIT COUNTER
BCD-TO-BINARY
DOUBLE BCD-TO-DOUBLE BINARY
BLOCK SET
CLEAR CARRY
COMPARE
DOUBLE COMPARE
COUNTER
REVERSIBLE COUNTER
DATA COLLECT
COMPLEMENT
COMPARISON TABLE LOAD
BCD DECREMENT
DIFFERENTIATE DOWN
DIFFERENTIATE UP
SINGLE WORD DISTRIBUTE
BCD DIVIDE
DOUBLE BCD DIVIDE
16-TO-4 ENCODER
BINARY DIVIDE
END
FAILURE ALARM AND RESET
SEVERE FAILURE ALARM
FCS CALCULATE
ASCII-TO-HEXADECIMAL
SECONDS TO HOURS
INTERLOCK
INTERLOCK CLEAR
73
Alphabetic List by Mnemonic Section 5-2
PID
PRV (@)
––
62
PULS (@) 65
PWM (@) ––
RET
ROL (@)
ROR (@)
RSET
93
27
28
None
RXD (@)
SBB (@)
SBN
SBS (@)
SCL (@) 66
SCL2 (@) ––
SCL3 (@) ––
SDEC (@) 78
SEC ––
47
51
92
91
SET
SFT
None
10
SFTR (@) 84
Mnemonic
INC (@)
INI (@)
INT (@) 89
IORF (@) 97
JME
JMP
05
04
38
61
Code
KEEP
LD
LD NOT
MAX (@)
MCRO (@) 99
MIN (@) ––
MLB (@) 52
MLPX (@) 76
11
None
None
––
MOV (@) 21
MOVB (@) 82
MOVD (@) 83
MSG (@) 46
MUL (@) 32
MULL (@) 56
MVN (@) 22
NEG (@)
NOP
OR
OR LD
––
00
None
None
OR NOT None
ORW (@) 35
OUT None
OUT NOT None
4
4
4
4
2
2
1
4
1
1
4
1
4
4
4
2
3
3
4
4
4
4
4
1
4
2
1
2
2
4
3
2
4
2
3
4
4
4
4
4
4
2
2
4
4
2
2
1
2
Words Name
INCREMENT
MODE CONTROL
INTERRUPT CONTROL
I/O REFRESH
JUMP END
JUMP
KEEP
LOAD
LOAD NOT
FIND MAXIMUM
MACRO
FIND MINIMUM
BINARY MULTIPLY
4-TO-16 DECODER
MOVE
MOVE BIT
MOVE DIGIT
MESSAGE
BCD MULTIPLY
DOUBLE BCD MULTIPLY
MOVE NOT
2’S COMPLEMENT
NO OPERATION
OR
OR LOAD
OR NOT
LOGICAL OR
OUTPUT
OUTPUT NOT
PID CONTROL
HIGH-SPEED COUNTER PV READ
SET PULSES
PULSE WITH VARIABLE DUTY RATIO
SUBROUTINE RETURN
ROTATE LEFT
ROTATE RIGHT
RESET
RECEIVE
BINARY SUBTRACT
SUBROUTINE DEFINE
SUBROUTINE ENTRY
SCALING
SIGNED BINARY TO BCD SCALING
BCD TO SIGNED BINARY SCALING
7-SEGMENT DECODER
HOURS TO SECONDS
SET
SHIFT REGISTER
REVERSIBLE SHIFT REGISTER
74
Alphabetic List by Mnemonic Section 5-2
Mnemonic
SLD (@)
SNXT
SPED (@) 64
SRCH (@) ––
SRD (@)
STC (@)
75
40
74
09
Code
STEP 08
STIM (@) 69
STUP
SUB (@)
––
31
SUBL (@) 55
SUM (@) ––
SYNC (@) ––
TCMP (@) 85
TIM
TIMH
TIML
TMHH
TXD (@) 48
WSFT (@) 16
XCHG (@) 73
None
15
––
––
XFER (@) 70
XNRW (@) 37
XORW (@) 36
ZCP ––
ZCPL ––
2
3
4
4
4
4
3
4
2
4
3
1
4
4
3
2
4
4
4
4
4
4
3
4
4
3
Words Name
ONE DIGIT SHIFT LEFT
STEP START
SPEED OUTPUT
DATA SEARCH
ONE DIGIT SHIFT RIGHT
SET CARRY
STEP DEFINE
INTERVAL TIMER
CHANGE RS-232C SETUP
BCD SUBTRACT
DOUBLE BCD SUBTRACT
SUM
SYNCHRONIZED PULSE CONTROL
TABLE COMPARE
TIMER
HIGH-SPEED TIMER
LONG TIMER
VERY HIGH-SPEED TIMER
TRANSMIT
WORD SHIFT
DATA EXCHANGE
BLOCK TRANSFER
EXCLUSIVE NOR
EXCLUSIVE OR
AREA RANGE COMPARE
DOUBLE AREA RANGE COMPARE
75
Expansion Instructions Section 5-3
Function Codes for
Expansion Instructions
Mnemonic
ASFT (@)
(open)
(open)
RXD (@)
TXD (@)
CMPL
INI (@)
PRV (@)
CTBL (@)
SPED (@)
PULS (@)
SCL (@)
BCNT (@)
5-3 Expansion Instructions
A set of expansion instructions is provided to aid in special programming needs.
Function codes can be assigned to up to 18 of the expansion instructions to enable using them in programs. This allows the user to pick the instructions needed by each program to more effectively use the function codes required to input instructions.
The mnemonics of expansion instructions are followed by “(––)” as the function code to indicate that they must be assigned function codes by the user in the instructions table before they can be used in programming (unless they are used under their default settings).
Refer to the 6-2-5 Assigning Expansion Instruction Function Codes for a description of the Programming Console operations used to change expansion instruction allocations.
Refer to the SYSMAC Support Software Operation Manuals: C-series PCs
(W248), the SYSMAC-CPT Support Software User Manual (W333), or the
WS02-CXPC1-E CX-Programmer User Manual (W361) for a description of the corresponding Support Software operations.
62
63
64
65
66
67
17
18
19
47
48
60
61
Code
The following 18 function codes can be used for expansion instructions:
17, 18, 19, 47, 48, 60, 61, 62, 63, 64, 65, 66, 67, 68, 69, 87, 88, and 89
The 35 expansion instructions that can be used are listed below, along with the default function codes that are assigned when the CPM2B is shipped.
Code Code Mnemonic
BCMP (@)
STIM (@)
(open)
(open)
INT (@)
ACC (@)
AVG
FCS (@)
HEX (@)
HMS (@)
MAX (@)
MIN (@)
NEG (@)
---
---
---
---
---
---
68
69
87
88
89
---
---
Mnemonic
PID
PWM (@)
SCL2 (@)
SCL3 (@)
SEC (@)
SRCH (@)
STUP (@)
SUM (@)
SYNC (@)
TIML
TMHH
ZCP
ZCPL
---
---
---
---
---
---
---
---
---
---
---
---
---
76
SECTION 6
Using Programming Devices
This section outlines the operations possible with the Programming Consoles.
6-1 Using a Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-1 Compatible Programming Consoles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-2 Changing the CPM2B’s Mode with the Mode Switch . . . . . . . . . . . . . . . . . . . . .
6-1-3 Connecting the Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-4 Preparation for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-5 Entering the Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Programming Console Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-2 Clearing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-3 Reading/Clearing Error Messages
6-2-4 Buzzer Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-5 Assigning Expansion Instruction Function Codes . . . . . . . . . . . . . . . . . . . . . . . .
6-2-6 Setting and Reading a Program Memory Address and Monitoring I/O Bit Status
6-2-7 Entering or Editing Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-8 Instruction Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-9 Bit Operand Search . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-10 Inserting and Deleting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-11 Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-12 Bit, Digit, Word Monitor
6-2-13 Differentiation Monitor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-14 Binary Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-15 Three-Word Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-16 Signed Decimal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-17 Unsigned Decimal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-18 Three-Word Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-19 Changing Timer, Counter SV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-20 Hexadecimal, BCD Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-21 Binary Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-22 Signed Decimal Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-23 Unsigned Decimal Data Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-24 Force Set, Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-25 Clear Force Set/Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-26 Hex-ASCII Display Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-27 Displaying the Cycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-28 Reading and Setting the Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-1 Preparatory Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-2 Example Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-3 Programming Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-4 Checking the Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3-5 Test Run in MONITOR Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
101
102
103
104
99
99
100
101
94
96
97
98
98
92
93
94
104
105
105
106
106
106
108
109
111
112
87
88
88
91
84
85
86
86
81
82
83
84
78
78
80
77
Using a Programming Console Section 6-1
6-1 Using a Programming Console
This section provides information on connecting and using a Programming Console.
6-1-1 Compatible Programming Consoles
There are two Programming Consoles that can be used with the CPM2B: The
CQM1-PRO01-E and the C200H-PRO27-E. The key functions for these Programming Consoles are identical.
Press and hold the Shift Key to input a letter shown in the upper-left corner of the key or the upper function of a key that has two functions. For example, the
CQM1-PRO01-E’s AR/HR Key can specify either the AR or HR Area; press and release the Shift Key and then press the AR/HR Key to specify the AR Area.
CQM1-PRO01-E
Attached Connecting
Cable (2 m)
LCD display
Mode switch
Operation keys
C200H-PRO27-E
LCD display
Mode switch
Operation keys
Cassette recorded jack
(Cannot be used with the CPM2B).
Connecting Cables
C200H-CN222 (2 m)
C200H-CN422 (4 m)
78
Using a Programming Console
Different Keys
Section 6-1
The following keys are labeled differently on the CQM1-PRO01-E and the
C200H-PRO27-E, but the operation of the keys in each pair is identical.
C200H-PRO27-E Keys CQM1-PRO01-E Keys
AR
HR
HR
SET
PLAY
SET
RESET
REC
RESET
Note To specify the AR area, use SHIFT and HR Keys for the C200H-PRO27-E and use SHIFT and AR/HR Keys for the CQM1-PRO01-E.
A shift symbol will be displayed in the upper-right corner of the screen when the
Shift Key is pressed. The shift input can be cleared by pressing the Shift Key again.
SHIFT
^ Shift input symbol
Mode Switch
Contrast Control
The mode switch controls the CPM2B’s operating mode. The key can be removed when the switch is set to RUN or MONITOR but it cannot be removed when the switch is set to PROGRAM.
The display contrast can be adjusted with the control on the right side of the Programming Console.
Contrast control
Buzzer Volume The C200H-PRO27-E’s buzzer volume can be adjusted with the lever on the right side of the Programming Console. The CQM1-PRO01-E’s buzzer volume cannot be adjusted.
Low volume
High volume
C200H-PRO27-E
Note The buzzer volume can be turned on and off with a key operation. See 6-2-4
Buzzer Operation for details.
79
Using a Programming Console Section 6-1
6-1-2 Changing the CPM2B’s Mode with the Mode Switch
Once the Programming Console has been connected, its mode switch can be used to change the CPM2B’s operating mode. The mode display (<PRO-
GRAM>, <MONITOR>, or <RUN>) will appear on the Programming Console screen.
•
No key operations can be performed while the mode display is displayed on the Programming Console screen. Press CLR to clear the display so that key operations can be performed.
•
If the SHIFT Key is pressed while the mode switch is turned, the original display will remain on the Programming Console’s screen and the mode display won’t appear.
•
The CPM2B will enter RUN mode automatically if a Programming Console isn’t connected when the CPM2B is turned on.
MONITOR
RUN PROGRAM
MONITOR
RUN PROGRAM
MONITOR
RUN PROGRAM
Mode display
<PROGRAM> BZ <MONITOR> BZ <RUN> BZ
CLR
Operation
Initial display
00000
Operation
SHIFT CLR
Operating Modes
PROGRAM Mode
The CPM2B program isn’t executed in PROGRAM mode. Use PROGRAM mode to create and edit the program, clear memory, or check the program for errors, or check output wiring.
MONITOR Mode
The CPM2B program is executed in MONITOR mode and I/O is processed just as it is in RUN mode. Use MONITOR mode to test system operations, such as monitoring CPM2B operating status, force-setting and resetting I/O bits, changing the SV/PV of timers and counters, changing word data, and online editing.
RUN Mode
This is the CPM2B’s normal operating mode. The CPM2B’s operating status can be monitored from a Programming Device, but bits can’t be force-set/force-reset and the SV/PV of timers and counters can’t be changed.
!
Caution Check the system thoroughly before changing the operating mode of the PC to prevent any accidents that might occur when the program is first started.
!
Caution Never change the mode while pressing any of the keys.
80
Using a Programming Console Section 6-1
Startup Operating Mode The operating mode of the CPM2B when the power is turned ON depends upon the PC Setup setting in DM 6600 and the Programming Console’s mode switch setting if the Programming Console is connected.
PC Setup setting
(DM 6600)
00xx
01xx
0200
0201
0202
Programming
Console connected
The startup mode determined by the mode switch setting.
Programming Console not connected
RUN mode if no Programming Device is connected. PROGRAM mode if another Programming Device is connected.
The startup mode is the same as the operating mode before power was interrupted.
PROGRAM mode
MONITOR mode
RUN mode
Note The default setting is 00xx. With this default setting, the PC will automatically enter RUN mode if a Programming Console is not connected and SW201 is ON.
Be sure that it is safe for the PC to operate before turning it ON under these conditions.
6-1-3 Connecting the Programming Console
Connect the Programming Console’s connecting cable to the CPM2B’s peripheral port, as shown below.
CS1W-CN114
Connecting Cable
(0.05 m)
Attached cable (2 m)
CQM1-PRO01-E
C200H-CN222 (2 m) or
C200H-CN422 (4 m)
Connecting Cable
CS1W-CN224 (2 m) or
CS1W-CN624 (4 m)
Connecting Cable
Peripheral port connector
CPM2C-CN111
Connecting Cable
(0.1 m) (See note 2.)
C200H-PRO27-E
SW201
(See note 1.)
Peripheral port
CPM2B CPU Board
Note 1. Always turn OFF SW 201 before connecting the Programming Console.
2. Only the peripheral port connector can be used when a CPM2C-CN111
Connecting Cable is connected.
81
Using a Programming Console
Panel Installation
Section 6-1
The C200H-PRO27-E Programming Console can be installed in a control panel as shown in the following diagram. (The C200H-ATT01 Mounting Bracket is sold separately.)
Mounting Bracket
Mounting hole dimensions
(DIN43700 standards)
Two screws
186
+1.1
–0
Panel thickness: 1.0 to 3.2 mm 92
+0.8
–0
Allow at least 80 mm for the cable connector above the Programming Console.
37
15
At least 80 mm is required.
Either connector may be used.
About 70 mm is required.
6-1-4 Preparation for Operation
This section describes the procedures required to begin Programming Console operation when using the Programming Console for the first time.
!
Caution Always confirm that the Programming Console is in PROGRAM mode when turning ON the PC with a Programming Console connected unless another mode is desired for a specific purpose. If the Programming Console is in RUN mode when PC power is turned ON, any program in Program Memory will be executed, possibly causing a PC-controlled system to begin operation.
The following sequence of operations must be performed before beginning initial program input.
1, 2, 3...
1. Be sure that the PC is OFF.
2. Connect the Programming Console to the CPU Board’s peripheral port. See
6-1-3 Connecting the Programming Console for details.
(The CPU Board’s Communications Switch setting has no effect on communications with the Programming Console.)
3. Set the mode switch to PROGRAM mode.
4. Turn ON the PC.
5. Enter the password. See 6-1-5 Entering the Password for details.
6. Clear (All Clear) the PC’s memory. See 6-2-2 Clearing Memory for details.
7. Read and clear all errors and messages. See 6-2-3 Reading/Clearing Error
Messages for details.
82
Using a Programming Console Section 6-1
8. Start programming.
6-1-5 Entering the Password
To gain access to the PC’s programming functions, you must first enter the password. The password prevents unauthorized access to the program.
The PC prompts you for a password when PC power is turned on or, if PC power is already on, after the Programming Console has been connected to the PC. To gain access to the system when the “Password!” message appears, press CLR and then MONTR. Then press CLR to clear the display.
If the Programming Console is connected to the PC when PC power is already on, the first display below will indicate the mode the PC was in before the Programming Console was connected. Ensure that the PC is in PROGRAM mode
before you enter the password. When the password is entered, the PC will shift to the mode set on the mode switch, causing PC operation to begin if the mode is set to RUN or MONITOR. The mode can be changed to RUN or MON-
ITOR with the mode switch after entering the password.
<PROGRAM>
PASSWORD!
<PROGRAM> BZ
Indicates the mode set by the mode selector switch.
83
Programming Console Operations
6-2 Programming Console Operations
Section 6-2
6-2-1 Overview
The following table lists the programming and monitoring operations that can be performed from a Programming Console. Refer to the rest of this section for details on operational procedures.
messages
Name
Clearing memory
Reading/clearing error
Buzzer operation
Function
Clears all or part of the Program Memory and any data areas that are not read-only, as well as the contents of the Programming Console’s memory.
85
Displays and clears error messages and displays MESSAGE instruction messages.
Turns on and off the buzzer that sounds when Programming Console keys are pressed.
86
86
Reads or changes the function codes assigned to expansion instructions 87
Page
Assigning expansion instruction function codes
Setting a program memory address
Reading a program memory address
Instruction search
Bit operand search
Sets the specified program memory address when reading, writing, inserting and deleting programs.
Reads the contents of the Program Memory. Displays the status of the currently displayed bit in PROGRAM and MONITOR modes.
Finds occurrences of the specified instruction in the program.
Finds occurrences of the specified operand bit in the program.
Inserting and deleting instructions
Inserts or deletes instructions from the program.
Entering or editing programs Overwrites the contents of the current Program Memory to either input a program for the first time or to change a program that already exists.
Checking the program Checks for programming errors and displays the program address and error when errors are found.
Bit, digit, word monitor
Multiple address monitor
Monitors the status of up to 16 bits and words, although only 3 can be shown on the display at one time.
Monitors the status of up to 6 bits and words simultaneously.
88
88
91
92
93
88
94
94
96
96
97
Differentiation monitor
Binary monitor
Three-word monitor
Signed decimal monitor
Unsigned decimal data modification
Monitors the up or down differentiation status of a particular bit.
Monitors the ON/OFF status of any word’s 16 bits.
Monitors the status of three consecutive words.
Converts the contents of the specified word from signed hexadecimal
(two’s complement format) to signed decimal for display.
Converts hexadecimal data in a word to unsigned decimal for display.
Unsigned decimal monitor
3-word data modification Changes the contents of one or more of the 3 consecutive words displayed in the 3-Word Monitor operation.
Changing timer, counter SV 1 Changes the SV of a timer or counter.
Changing timer, counter SV 2 Makes fine adjustment changes to the SV of the timer or counter.
Changes the BCD or hexadecimal value of a word being monitored.
Hexadecimal, BCD data modification
Binary data modification
Signed decimal data modification
Changes the status of a word’s bits when the word is being monitored.
Changes the decimal value of a word being monitored as signed decimal data, within a range of –32,768 to 32,767. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format.)
Changes the decimal value of a word being monitored as unsigned decimal data, within a range of 0 to 65,535. A change into hexadecimal data is made automatically.
98
98
99
99
100
100
101
101
102
103
Force set/reset
Clear force set/reset
Hex-ASCII display change
Forces bits ON (force set) or OFF (force reset.)
Restores the status of all bits which have been force set of reset.
Converts word data displays back and forth between 4-digit hexadecimal data and ASCII.
104
104
105
84
Programming Console Operations Section 6-2
Name
Displaying the cycle time
Reading and setting the clock Reads or sets the internal clock.
Function
Displays the current average cycle time (scan time.)
Page
105
106
6-2-2 Clearing Memory
This operation is used to clear all or part of the Program Memory and data areas, as well as the contents of the Programming Console’s memory. This operation is possible in PROGRAM mode only.
All Clear
No
RUN
No
MONITOR
OK
PROGRAM
Before beginning to program for the first time or when installing a new program, clear all areas.
The following procedure is used to clear memory completely, including the program, all data areas, counter PVs, Data Memory, and the PC Setup (DM 6600 to
DM 6655).
1, 2, 3...
1. Bring up the initial display by pressing the CLR Key repeatedly.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
SET NOT RESET
00000MEMORY CLR?
HR CNT DM
3. Press the MONTR Key to clear memory completely.
MONTR
00000MEMORY CLR
END HR CNT DM
!
Caution The PC Setup (DM 6600 through DM 6655) will be cleared when this operation is performed.
Partial Clear It is possible to retain the data in specified areas or part of the Program Memory.
To retain the data in the HR, TC, or DM Areas, press the appropriate key after pressing SET, NOT, and RESET. Any data area that still appears on the display will be cleared when the MONTR Key is pressed.
The HR Key is used to specify both the AR and HR Areas, the CNT Key is used to specify the entire timer/counter area, and the DM Key is used to specify the DM
Area.
It is also possible to retain a portion of the Program Memory from the first memory address to a specified address. After designating the data areas to be retained, specify the first Program Memory address to be cleared. For example, input 030 to leave addresses 000 to 029 untouched, but to clear addresses from 030 to the end of Program Memory.
As an example, follow the procedure below to retain the timer/counter area and
Program Memory addresses 000 through 122:
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET, NOT, and then the RESET Key to begin the operation.
3. Press the CNT Key to remove the timer/counter area from the data areas shown on the display. (Counter PVs will not be cleared.)
CNT
00000MEMORY CLR?
HR DM
4. Press 123 to specify 123 as the starting program address.
B
1
C
2
D
3
00123MEMORY CLR?
HR DM
85
Programming Console Operations Section 6-2
5. Press the MONTR Key to clear the specified regions of memory.
MONTR
00000MEMORY CLR
END HR DM
6-2-3 Reading/Clearing Error Messages
This operation is used to display and clear error messages. It is possible to display and clear non-fatal errors and MESSAGE instruction messages in any mode, but fatal errors can be cleared in PROGRAM mode only.
OK
RUN
OK
MONITOR
OK
PROGRAM
Key Sequence
Before inputting a new program, any error messages recorded in memory should be cleared. It is assumed here that the causes of any of the errors for which error messages appear have already been taken care of. If the buzzer sounds when an attempt is made to clear an error message, eliminate the cause of the error, and then clear the error message. (Refer to Section 7 Test
Runs and Error Processing for troubleshooting information.)
Follow the procedure below to display and clear messages.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN and then the MONTR Key to begin the operation. If there are no messages, the following display will appear:
ERR/MSG CHK OK
FUN MONTR
If there are messages, the most serious message will be displayed when the
MONTR Key is pressed. Pressing MONTR again will clear the present message and display the next most serious error message. Continue pressing
MONTR until all messages have been cleared. These are some examples of error messages:
A memory error:
MEMORY ERR
MONTR
A system error:
MONTR
SYS FAIL FAL01
A message (displayed with MSG(46)):
MATERIAL USED UP
MONTR
All messages cleared:
MONTR
ERR/MSG CHK OK
6-2-4 Buzzer Operation
This operation is used to turn on and off the buzzer that sounds when Programming Console keys are pressed. This buzzer will also sound whenever an error occurs during PC operation. Buzzer operation for errors is not affected by this setting.
This operation is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
86
Programming Console Operations
Key Sequence
Section 6-2
Follow the procedure below to turn the key-input buzzer on and off.
1, 2, 3...
1. Press the CLR, SHIFT, and then the CLR Key to bring up the mode display.
In this case the PC is in PROGRAM mode and the buzzer is ON.
<MONITOR> BZ
CLR SHIFT CLR
2. Press the SHIFT and then the 1 Key to turn off the buzzer.
SHIFT
B
1
<MONITOR>
The buzzer will not sound when “BZ” is not displayed.
3. Press the SHIFT and then the 1 Key again to turn the buzzer back ON.
<MONITOR> BZ
SHIFT
B
1
6-2-5 Assigning Expansion Instruction Function Codes
This operation is used to display or change the expansion instructions assigned to expansion instruction function codes. The assignments can be displayed in any mode, but can be changed in PROGRAM mode only.
Operation
Read assignment OK
Change assignment No
RUN
OK
No
MONITOR
OK
PROGRAM
OK
Assign expansion instruction function codes before inputting the program.
The CPM2B will not operate properly if expansion instructions aren’t assigned correctly. An expansion instruction can be assigned to one function code only.
The PC Setup must be set for user-defined expansion instruction assignments. Set bits 8 to 11 of DM 6602 to 1 and turn the PC’s power off and then on again to enable the new setting.
There are tables in Section 5 Instruction Set showing the default function code assignments in the CPM2B.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the EXT Key to display the assignment for the first function code (17).
EXT
INST TBL READ
FUN017:ASFT
3. Press the Up and Down Arrow Keys to scroll through the expansion instruction function codes.
↓
CHG
INST TBL READ
FUN018:FUN
4. Press the CHG Key to assign a different expansion instruction to the selected function code.
INST TBL CHG?
FUN018:FUN ~????
5. Press the Up and Down Arrow Keys to scroll through the expansion instructions that can be assigned to the selected function code.
↓
INST TBL CHG?
FUN018:FUN ~HEX
87
Programming Console Operations Section 6-2
6. Press the WRITE Key to assign the displayed instruction to the function code.
WRITE
INST TBL READ
FUN018:HEX
6-2-6 Setting and Reading a Program Memory Address and Monitoring
I/O Bit Status
This operation is used to display the specified program memory address and is possible in any mode. In the RUN or MONITOR mode, the I/O bit status of bits in the program will be displayed.
OK
RUN
OK
MONITOR
OK
PROGRAM
When inputting a program for the first time, it is generally written to Program
Memory starting from address 000. Because this address appears when the display is cleared, it is not necessary to specify it.
When inputting a program starting from other than 000 or to read or modify a program that already exists in memory, the desired address must be designated.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the desired address. It is not necessary to input leading zeroes.
C
2
A
0
A
0
00200
3. Press the Down Arrow Key.
↓
00200READ OFF
LD 00000
In the RUN or MONITOR mode, ON/OFF status of the bit will be displayed.
Pressing the MONTR Key will change to the I/O monitor display. Bits can be force-set or force-reset from the I/O monitor display. Press the CLR Key to return to I/O bit status monitoring of the initial address.
Note The ON/OFF status of any displayed bit will be shown if the PC is in
RUN or MONITOR mode.
4. Press the Up and Down Arrow Keys to scroll through the program.
↓
00201READ ON
AND 00001
↑
00200READ OFF
LD 00000
6-2-7 Entering or Editing Programs
This operation is used enter or edit programs. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
The same procedure is used to either input a program for the first time or to change a program that already exists. In either case, the current contents of
Program Memory is overwritten.
88
Programming Console Operations Section 6-2
The program shown in the following diagram will be entered to demonstrate this operation.
00002
TIM 000
#0123
12.3 s
Address Instruction
00200
00201
LD
TIM
MOV(021)
#0100
LR 10
00202 MOV(021)
00203 ADB(050)
ADB(050)
#0100
#FFF6
DM 0000
IR
Operands
00002
000
#0123
LR
#0100
10
#0100
#FFF6
DM 0000
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Specify the address where the program will begin.
3. Input the address where the program will begin and press the Down Arrow
Key. It is not necessary to input leading zeroes.
C
2
A
0
A
0
↓
00200READ
NOP (000)
4. Input the first instruction and operand.
LD
C
2
00200
LD 00002
5. Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00201READ
NOP (000)
If a mistake was made inputting the instruction, press the Up Arrow Key to return to the previous program address and input the instruction again. The mistaken instruction will be overwritten
To specify the Completion Flag for a timer or counter, press the LD, AND,
OR, or NOT Key followed by the TIM or CNT Key, and then input the timer/ counter number last.
6. Input the second instruction and operand. (In this case it isn’t necessary to enter the timer number, because it’s 000.) Press the WRITE Key to write the instruction to Program Memory.
TIM Timer number WRITE
00201 TIM DATA
#0000
7. Input the second operand (123 to specify 12.3 seconds) and press the
WRITE Key. The next program address will be displayed.
B
1
C
2
D
3 WRITE
00202READ
NOP (000)
If a mistake was made inputting the operand, press the Up Arrow Key to return to display the mistaken operand and input the operand again.
Note a) Counters are input in the same basic way as timers except the
CNT Key is pressed instead of the TIM Key.
b) Timer and counter SVs are input in BCD, so it isn’t necessary to press the CONT/# Key.
89
Programming Console Operations Section 6-2
8. Input the third instruction and its operands. First input the instruction by pressing the FUN Key and then the function code (21 in this case).
FUN
C
2
B
1
00202
MOV (021)
To input the differentiated version of an instruction, press the NOT Key after the function code (FUN 2 1 NOT). The “@” symbol will be displayed next to differentiated instructions. Press the NOT Key again to change back the instruction back to a non-differentiated instruction. The “@” symbol will disappear.
To change an instruction after it has been entered, simply scroll through the program until the desired instruction is displayed and press the NOT Key.
The “@” symbol should be displayed next to the instruction.
9. Press the WRITE Key to write the instruction to Program Memory. The input display for the first operand will be displayed.
WRITE
00202 MOV DATA A
000
•
Writing Hexadecimal, BCD Constant
10. Input the first operand.
The operands of MOV (21) are normally word addresses, but a constant can be input by pressing the CONT/# Key first. When the CONT/# Key is pressed, the display will change to “#0000,” indicating that a constant can be entered.
CONT
#
B
1
A
0
A
0
00202 MOV DATA A
#0100
Press the WRITE Key to write the instruction to Program Memory. The input display for the second operand will appear.
WRITE
00202 MOV DATA B
000
Note The operands of MOV(21) can be word addresses, so the CONT/#
Key must be pressed to input a constant.
•
Writing a Word Address
11. Input the second operand.
*EM
LR
B
1
A
0
00202 MOV DATA B
LR 10
Press the WRITE Key to write the instruction to Program Memory. The next program address will be displayed.
WRITE
00203READ
NOP (000)
Note When the default display value is “000”, a word address can be input immediately without pressing the Shift and CH/# Keys.
12. Input the next instruction.
FUN
F
5
A
0
00203
ADB (050)
Press the WRITE Key to write the instruction to Program Memory.
WRITE
00203 ADB DATA A
000
90
Programming Console Operations Section 6-2
•
Writing an Unsigned Decimal Number
13. The first operand is input as an unsigned integer.
CONT
#
SHIFT TR NOT
00203 ADB DATA A
#00000
Input the value of the operand from 0 to 65535.
C
2
F
5 6
00203 ADB DATA A
#00256
Note If an erroneous input is made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
14. Restore the hexadecimal display.
SHIFT TR
00203 ADB DATA A
#0100
Note If an input is made outside of the permissible range, a buzzer will sound and the hexadecimal display will not be displayed.
WRITE
00203 ADB DATA B
000
15. The second operand is input as a signed integer.
CONT
#
SHIFT TR
00203 ADB DATA B
#+00000
Input the value of the operand from –32,768 to 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
RESET
B
1
A
0
00203 ADB DATA B
#Ć00010
Note If an erroneous input is made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
16. Restore the hexadecimal display.
SHIFT TR
00203 ADB DATA B
#FFF6
WRITE
00203 ADB DATA C
000
•
Writing a Word Address (DM 0000)
17. Input the final operand and then press the WRITE Key. (It isn’t necessary to input leading zeroes.)
EM
DM
WRITE
00203 ADB DATA C
DM 0000
00204READ
NOP (000)
6-2-8 Instruction Search
This operation is used to find occurrences of the specified instruction in the program and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or
MONITOR mode.
91
Programming Console Operations Section 6-2
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address from which the search will begin and press the Down
Arrow Key. It is not necessary to input leading zeroes.
OUT
B
1
A
0
A
0
↓
00100READ
TIM 001
3. Input the instruction to be found and press the SRCH Key. In this case, the search is for OUT 01000.
B
1
In this case, the next OUT 01000 instruction is at address 200, as shown below.
A
0
A
0
A
0 SRCH
00200SRCH
OUT 01000
4. Press the Down Arrow Key to display the instruction’s operands or press the
SRCH Key to search for the next occurrence of the instruction.
5. The search will continue until an END instruction or the end of Program
Memory is reached. In this case, an END instruction was reached at address 397.
Indicates the address of END instruction.
SRCH
00397SRCH
END (001)00.4KW
Indicates the amount used by the user program in units of 0.1 Kwords.
6-2-9 Bit Operand Search
This operation is used to find occurrences of the specified operand bit in the program and is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
The ON/OFF status of any displayed bit will be shown if the PC is in RUN or
MONITOR mode.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the operand address. It is not necessary to input leading zeroes.
SHIFT
CONT
#
F
5
00000CONT SRCH
LD 00005
3. Press the SRCH Key to begin the search.
SRCH
00123CONT SRCH
LD 00005
4. Press the SRCH Key to search for the next occurrence of the operand bit.
SRCH
00255CONT SRCH
AND NOT 00005
5. The search will continue until an END instruction or the end of Program
Memory is reached. In this case, an END instruction was reached.
Indicates the address of END instruction.
SRCH
00397CONT SRCH
END (001)00.4KW
Indicates the amount used by the user program in units of 0.1 Kwords.
92
Programming Console Operations Section 6-2
6-2-10 Inserting and Deleting Instructions
This operation is used to insert or delete instructions from the program. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
To demonstrate this operation, an IR 00105 NO condition will be inserted at program address 00206 and an IR 00103 NO condition deleted from address
00205, as shown in the following diagram.
Original Program
Address Instruction Operands
00100 00101 00103 00104
01000
00201 00102
Delete
00105
Insert
END(01)
Delete
00205
00206
00207
00208
AND
AND NOT
OUT
END(01)
00103
00104
01000
-
Insert
Insertion
Deletion
Follow the procedure below to insert the IR 00105 NO condition at address
00206.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address where the NO condition will be inserted and press the
Down Arrow Key. It is not necessary to input leading zeroes.
C
2
A
0 6
↓
↓
00206READ
AND NOT 00104
3. Input the new instruction and press the INS Key.
AND
B
1
A
0
F
5 INS
00206INSERT?
AND 00105
4. Press the Down Arrow Key to insert the new instruction.
00207INSERT END
AND NOT 00104
Note For instructions that require more operands (such as set values), input the operands and then press the WRITE Key.
Follow the procedure below to delete the IR 00103 NO condition at address
00205.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address where the NO condition will be deleted and press the
Down Arrow Key. It is not necessary to input leading zeroes.
C
2
A
0
F
5
↓
00205READ
AND 00103
3. Press the DEL Key.
DEL
00205DELETE?
AND 00103
4. Press the Up Arrow Key to delete the specified instruction.
If the instruction has more operands, the operands will be deleted automatically with the instruction.
↑
00205 DELETE END
AND 00105
93
Programming Console Operations Section 6-2
After completing the insertion and deletion procedures, use the Up and Down
Arrow Keys to scroll through the program and verify that it has been changed correctly, as shown in the following diagram.
Corrected Program
00100 00101 00105 00104
Address Instruction Operands
01000
00201 00102
END(01)
00205
00206
00207
00208
AND
AND NOT
OUT
END(01)
00105
00104
01000
-
6-2-11 Checking the Program
This operation checks for programming errors and displays the program address and error when errors are found. It is possible in PROGRAM mode only.
No
RUN
No
MONITOR
OK
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH
00000PROG CHK
CHK LBL (0Ć2)?
3. Input the desired check level (0, 1, or 2). The program check will begin when the check level is input, and the first error found will be displayed.
A
0
00178CIRCUIT ERR
OUT 00200
4. Press the SRCH Key to continue the search. The next error will be displayed. Continue pressing the SRCH Key to continue the search.
The search will continue until an END instruction or the end of Program
Memory is reached. A display like this will appear if the end of Program
Memory is reached:
SRCH
00300NO END INST
END
A display like this will appear if an END instruction is reached:
SRCH
00310PROG CHK
END (001)00.3KW
No more errors exist if the END instruction is displayed.
If errors are displayed, edit the program to correct the errors and check the program again. Continue checking the program by pressing the SRCH Key again until all errors have been corrected.
6-2-12 Bit, Digit, Word Monitor
This operation is used to monitor the status of up to 16 bits and words, although only 3 can be shown on the display at any one time. Operation is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
94
Programming Console Operations Section 6-2
Program Read then Monitor When a program address is being displayed, the status of the bit or word in that address can be monitored by pressing the MONTR Key.
Bit Monitor
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the desired program address and press the Down Arrow Key.
C
2
A
0
A
0
↓
00200READ
TIM 000
3. Press the MONTR Key to begin monitoring.
MONTR
T000
1234
If the status of a bit is being monitored, that bit’s status can be changed using the Force Set/Reset operation. Refer to 6-2-24 Force Set, Reset for details.
If the status of a word is being monitored, that word’s value can be changed using the Hexadecimal/BCD Data Modification operation. Refer to 4-3-19
Hexadecimal, BCD Data Modification, 4-3-20 Binary Data Modification,
4-3-21 Signed Decimal Data Modification, and 4-3-22 Unsigned Decimal
Data Modification for details.
4. Press the CLR Key to end monitoring.
CLR
00200
TIM 000
Follow the procedure below to monitor the status of a particular bit.
Word Monitor
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the bit address of the desired bit and press the MONTR Key.
SHIFT
CONT
#
B
1 MONTR
00001
^ ON
The Up or Down Arrow Key can be pressed to display the status of the previous or next bit.
The displayed bit’s status can be changed using the Force Set/Reset operation. Refer to 6-2-24 Force Set, Reset for details.
3. Press the CLR Key to end monitoring.
CLR
00000
CONT 00001
Follow the procedure below to monitor the status of a particular word.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the word address of the desired word.
SHIFT
CH
*DM
*EM
LR
B
1
00000
CHANNEL LR 01
3. Press the MONTR Key to begin monitoring.
MONTR
cL01
FFFF
The Up or Down Arrow Key can be pressed to display the status of the previous or next word.
The displayed word’s status can be changed using the Hexadecimal/BCD
Data Modification operation. Refer to Refer to 4 3-19 Hexadecimal, BCD
Data Modification, 4-3-20 Binary Data Modification, 4-3-21 Singed Decimal
Data Modification, and 4-3-22 Unsigned Decimal Data Modification for details.
95
Programming Console Operations Section 6-2
Multiple Address
Monitoring
4. Press the CLR Key to end monitoring.
CLR
00000
CHANNEL LR 01
Note The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
The status of up to six bits and words can be monitored simultaneously, although only three can be shown on the display at any one time.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Input the address of the first bit or word and press the MONTR Key.
TIM MONTR
T000
0100
3. Repeat step 2 up to 6 times to display the next addresses to be monitored.
SHIFT
CONT
#
B
1 MONTR
00001 T000
^ OFF 0100
EM
DM
MONTR
D000000001 T000
0000^ OFF 0100
If 4 or more bits and words are being monitored, the bits and words that do not appear on the display can be displayed by pressing the MONTR Key. If the MONTR Key is pressed alone, the display will shift to the right.
If more than six bits and words are input, monitoring of the bit or word input first will be canceled.
4. Press the CLR Key to stop monitoring the leftmost bit or word and clear it from the display.
CLR
00001 T000
^ OFF 0100
5. Press the SHIFT and CLR Keys to end monitoring altogether.
SHIFT CLR
00000
CONT 00001
Note Press the SHIFT Key, CLR Key, and then CLR Key again to return to the initial
Programming Console display with the multiple address monitoring state unchanged. Press the SHIFT Key and then the MONTR Key from the initial display to return to the multiple address monitoring state. The monitoring states can be retained for 6 bits and words.
The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
6-2-13 Differentiation Monitor
This operation is used to monitor the up or down differentiation status of a particular bit. When detected, the up or down differentiation will be displayed and the buzzer will sound. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
6-2-12 Bit, Digit, Word Monitor. If 2 or more bits are being monitored, the desired bit should be leftmost on the display.
In this case the differentiation status of LR 00 will be monitored.
L000000001H0000
^ OFF^ OFF^ OFF
96
Programming Console Operations Section 6-2
2. To specify up-differentiation monitoring, press the SHIFT and then the Up
Arrow Key. The symbols “U@” will appear.
SHIFT
↑
L000000001H0000
U@OFF^ OFF^ OFF
Indicates waiting for the bit to turn ON.
To specify down-differentiation monitoring, press the SHIFT and then the
Down Arrow Key. The symbols “D@” will appear.
SHIFT
↓
L000000001H0000
D@OFF^ OFF^ OFF
3. The buzzer will sound when the specified bit goes from off to on (for up-differentiation) or from on to off (for down-differentiation).
L000000001H0000
^ ON^ OFF^ OFF
Note The buzzer will not sound if it has been turned off.
4. Press the CLR Key to end differentiation monitoring and return to the normal monitoring display.
CLR
L000000001H0000
^ OFF^ OFF^ OFF
6-2-14 Binary Monitor
This operation is used to monitor the ON/OFF status of any word’s 16 bits. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. The desired word should be leftmost on the display if 2 or more words are being monitored.
c010
0000
(Word monitor)
2. Press the SHIFT and then the MONTR Key to begin binary monitoring. The
ON/OFF status of the selected word’s 16 bits will be shown along the bottom of the display. A 1 indicates a bit is on, and a 0 indicates it is off.
SHIFT MONTR
c010 MONTR
0000000000000000
Bit 15 Bit 00
The status of force-set bits is indicated by “S,” and the status of a force-reset bits is indicated by “R,” as shown below.
c010 MONTR
000S0000000R0000
Force-set bit Force-reset bit
Note a) The status of displayed bits can be changed at this point. Refer to
6-2-21 Binary Data Modification for details.
b) The Up or Down Arrow Key can be pressed to display the status of the previous or next word’s bits.
97
Programming Console Operations Section 6-2
3. Press the CLR Key to end binary monitoring and return to the normal monitoring display.
CLR
c010
0000
6-2-15 Three-Word Monitor
This operation is used to monitor the status of three consecutive words. It is possible in any mode.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the first of the three words according to the procedure described in 6-2-12 Bit, Digit, Word Monitor.
If 2 or more words are being monitored, the desired first word should be leftmost on the display.
c200
89AB
(Word monitor)
2. Press the EXT Key to begin 3-word monitoring. The status of the selected word and the next two words will be displayed, as shown below. In this case,
DM 0000 was selected.
EXT
c202 c201 c200
0123 4567 89AB
The Up and Down Arrow Keys can be used to shift one address up or down.
The status of the displayed words can be changed at this point. Refer to
6-2-18 Three-word Data Modification.
The display can be changed to display ASCII text, which is useful when three consecutive words containing an ASCII message are displayed. Refer to 6-2-26 Hex-ASCII Display Change.
3. Press the CLR Key to end 3-word monitoring and return to the normal monitoring display. The rightmost word on the 3-word monitor display will be monitored.
CLR
c200
89AB
Note The operating mode can be changed without altering the current monitor display by holding down the SHIFT Key and then changing the operating mode.
6-2-16 Signed Decimal Monitor
This operation converts the contents of the specified word from signed hexadecimal (two’s complement format) to signed decimal for display. The operation can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor with sign. During multiple address monitoring, the leftmost word will be converted.
c200 cL0020000
FFF0 0000^ OFF
(Multiple address monitor)
2. Press the SHIFT+TR Keys to display the leftmost word as signed decimal.
SHIFT TR
c200
Ć00016
98
Programming Console Operations Section 6-2
At this point, the contents of the displayed word can be changed with a signed-decimal input. Refer to 6-2-22 Signed Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal display and return to normal monitoring.
CLR
c200 cL0020000
FFF0 0000^ OFF
6-2-17 Unsigned Decimal Monitor
This operation is used to convert hexadecimal data in a word to unsigned decimal for display. The operation can be executed while using I/O monitoring, multiple address monitoring or 3-word monitoring.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the word that is to be used for decimal monitor without sign. During multiple address monitoring, the leftmost word will be converted.
c200 cL0020000
FFF0 0000^ OFF
Multiple address monitoring
2. Press the SHIFT+TR+NOT Keys to display the leftmost word as unsigned decimal.
SHIFT TR NOT
CLR
c200
65520
At this point, the contents of the displayed word can be changed with an unsigned-decimal input. Refer to 6-2-23 Unsigned Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal display and return to normal monitoring.
c200 cL0020000
FFF0 0000^ OFF
6-2-18 Three-Word Data Modification
This operation is used to change the contents of one or more of the 3 consecutive words displayed in the Three-Word Monitor operation. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired words according to the procedure described 6-2-15 Three-Word Monitor.
D0002D0001D0000
0123 4567 89AB
(Three-word monitor)
2. Press the CHG Key to begin 3-word data modification. The cursor will appear next to the contents of the leftmost word.
CHG
D0002 3CH CHG?
00123 4567 89AB
3. Input the new value for the leftmost word on the display and press the CHG
Key if more changes will be made.
99
Programming Console Operations Section 6-2
(Input the new value and press the WRITE Key to write the changes in memory if no more changes will be made.)
B
1 CHG
D0002 3CH CHG?
0001 4567 89AB
4. Input the new value for the middle word on the display and press the CHG
Key if the rightmost word will be changed. Input the new value and press the
WRITE Key to write the changes in memory if the rightmost word will not be changed. (In this case, it will not.)
C
2
D
3
E
4 WRITE
D0002D0001D0000
0001 0234 89AB
Note If the CLR Key is pressed before the WRITE Key, the operation will be cancelled and the 3-word monitor display will return without any changes in data memory.
6-2-19 Changing Timer, Counter SV
There are two operations that can be used to change the SV of a timer or counter. They are possible in MONITOR or PROGRAM mode only. In MON-
ITOR mode, the SV can be changed while the program is being executed.
No
RUN
OK
MONITOR
OK
PROGRAM
The timer or counter SV can be changed either by inputting a new value or by incrementing or decrementing the current SV.
Inputting a New SV
Constant
This operation can be used to input a new SV constant, as well as to change an
SV from a constant to a word address designation and vice versa. The following examples show how to input a new SV constant and how to change the SV from a constant to an address.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
B
1 SRCH
00201SRCH
TIM 001
3. Press the Down Arrow Key and then the CHG Key.
↓
CHG
00201DATA?
T001 #0134 #????
4. At this point a new SV constant can be input or the SV constant can be changed to a word address designation a) To input a new SV constant, input the constant and press the WRITE
Key.
SHIFT
B
1
C
2
E
4 WRITE
00201 TIM DATA
#0124 b) To change to a word address designation, input the word address and press the WRITE Key.
CH
*DM
AR
HR
B
1
A
0 WRITE
00201 TIM DATA
HR 10
Incrementing and
Decrementing a Constant
This operation can be used to increment and decrement an SV constant. It is possible only when the SV has been entered as a constant.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM SRCH
00201SRCH
TIM 000
100
Programming Console Operations Section 6-2
3. Press the Down Arrow, CHG, and then the EXT Key.
↓
CHG EXT
00201DATA ? U/D
T000 #0123 #0123
The constant on the left is the old SV and the constant on the right will become the new SV constant in step 5.
4. Press the Up and Down Arrow Keys to increment and decrement the constant on the right. (In this case the SV is incremented once.)
↓
00201DATA ? U/D
T000 #0123 #0124
5. Press the CLR Key twice to change the timer’s SV to the new value.
CLR CLR
00201 TIM DATA
#0124
6-2-20 Hexadecimal, BCD Data Modification
This operation is used to change the BCD or hexadecimal value of a word being monitored using the procedure described in 6-2-12 Bit, Digit, Word
Monitor. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
Words SR 253 to SR 255 cannot be changed.
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired word should be leftmost on the display.
D0000
0119
(Word monitor)
2. Press the CHG Key to begin hexadecimal, BCD data modification.
CHG
PRES VAL?
D0000 0119 ????
3. Input the new PV and press the WRITE Key to change the PV.
The operation will end and the normal monitoring display will return when the WRITE Key is pressed.
C
2
A
0
A
0 WRITE
D0000
0200
6-2-21 Binary Data Modification
This operation is used to change the status of a word’s bits when the word is monitored using the procedure described in 6-2-14 Binary Monitor. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
Bits SR 25300 to SR 25507 and timer/counter flags cannot be changed.
101
Programming Console Operations Section 6-2
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired word according to the procedure described
6-2-14 Binary Monitor.
(Binary monitor)
c010 MONTR
1000010101010101
Bit 15
2. Press the CHG Key to begin binary data modification.
Bit 00
CHG
c010 CHG?
1000010101010101
A flashing cursor will appear over bit 15. The cursor indicates which bit can be changed.
3. Three sets of keys are used to move the cursor and change bit status: a) Use the Up and Down Arrow Keys to move the cursor to the left and right.
↓ ↓
c010 CHG?
1000010101010101 b) Use the 1 and 0 Keys to change a bit’s status to on or off. The cursor will move one bit to the right after one of these keys is pressed.
B
1
c010 CHG?
1010010101010101 c) Use the SHIFT+SET and SHIFT+RESET Keys to force-set or force-reset a bit’s status. The cursor will move one bit to the right after one of these keys is pressed. The NOT Key will clear force-set or force-reset status.
Note Bits in the DM Area cannot be force-set or force-reset.
4. Press the WRITE Key to write the changes in memory and return to the binary monitor.
WRITE
c010 MONTR
1010010101010101
6-2-22 Signed Decimal Data Modification
This operation is used to change the decimal value of a word being monitored as signed decimal data, within a range of –32,768 to 32,767. The contents of the specified word are converted automatically to signed hexadecimal (two’s complement format).
Words SR 253 to SR 255 cannot be changed.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
102
Programming Console Operations Section 6-2
1, 2, 3...
1. Monitor (signed decimal) the status of the word for which the present value is to be changed.
(Signed decimal monitor)
D0200
Ć00016
2. Press the CHG Key to begin decimal data modification.
CHG
PRES VAL?
D0200Ć00016
3. Input the new PV and press the WRITE Key to change the PV. The operation will end and the signed-decimal monitoring display will return when the
WRITE Key is pressed.
The PV can be set within a range of –32,768 and 32,767. Use the SET Key to input a positive number, and use the RESET Key to input a negative number.
RESET
D
3
C
2 7 6 8 WRITE
D0200
Ć32768
If an erroneous input has been made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
The buzzer will sound if a value outside the specified range is input, allowing no writing.
6-2-23 Unsigned Decimal Data Modification
This operation is used to change the decimal value of a word being monitored as unsigned decimal data, within a range of 0 to 65,535. A change into hexadecimal data is made automatically.
Words SR 253 to SR 255 cannot be changed.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3...
1. Monitor (unsigned decimal) the status of the word for which the present value is to be changed.
c200
65520
(Unsigned decimal monitor)
2. Press the CHG Key to begin decimal data modification.
CHG
PRES VAL?
c200 65520
3. Input the new PV and press the WRITE Key to change the PV. The operation will end and the decimal-without-sign monitoring display will return when the
WRITE Key is pressed.
D
3
The PV can be set within a range of 0 to 65,535.
C
2 7 6 8 WRITE
c200
32768
If an erroneous input has been made, press the CLR Key to restore the status prior to the input. Then enter the correct input.
The buzzer will sound if a value outside the specified range is input, allowing no writing.
103
Programming Console Operations Section 6-2
6-2-24 Force Set, Reset
This operation is used to force bits ON (force set) or OFF (force reset) and is useful when debugging the program or checking output wiring. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
1, 2, 3...
1. Monitor the status of the desired bit according to the procedure described in
6-2-12 Bit, Digit, Word Monitor. If two or more words are being monitored, the desired bit should be leftmost on the display.
0000020000
^ OFF^ ON
(Multiple address monitor)
2. Press the SET Key to force the bit ON or press the RESET Key to force the bit OFF.
SET
0000020000
ON^ ON
The cursor in the lower left corner of the display indicates that the force set/ reset is in progress. Bit status will remain ON or OFF only as long as the key is held down; the original status will return one cycle after the key is released.
3. Press the SHIFT and SET Keys or SHIFT and RESET Keys to maintain the status of the bit after the key is released. In this case, the force-set status is indicated by an “S” and the force-reset status is indicated by an “R.”
To return the bit to its original status, press the NOT Key or perform the Clear
Force Set/Reset operation. Refer to 6-2-25 Clear Force Set/Reset for details.
Forced status will also be cleared in the following cases: a) When the PC’s operating mode is changed (although the forced status will not be cleared when the mode is changed from PROGRAM to MON-
ITOR if SR 25211 is ON) b) When the PC stops because a fatal error occurred c) When the PC stops because of a power interruption d) When the Clear Force Set/Reset Operation is performed
6-2-25 Clear Force Set/Reset
This operation is used to restore the status of all bits which have been force set or reset. It is possible in MONITOR or PROGRAM mode only.
No
RUN
OK
MONITOR
OK
PROGRAM
!
Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Board or Expansion I/O Boards may operate unexpectedly.
104
Programming Console Operations Section 6-2
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the SET and then the RESET Key. A confirmation message will appear.
00000FORCE RELE?
SET
RESET
Note If you mistakenly press the wrong key, press CLR and start again from the beginning.
3. Press the NOT Key to clear the force-set/reset status of bits in all data areas.
NOT
00000FORCE RELE
END
6-2-26 Hex-ASCII Display Change
This operation is used to convert word data displays back and forth between
4-digit hexadecimal data and ASCII. It is possible in any mode.
The displayed PV of the timer or counter cannot be changed.
OK
RUN
OK
MONITOR
OK
PROGRAM
1, 2, 3...
1. Monitor the status of the desired word(s) according to the procedure described in 6-2-12 Bit, Digit, Word Monitor. While the multiple addresses are being monitored, the leftmost word is subject to change.
D0000D0001
4142 3031
(Multiple address monitor)
2. Press the TR Key to switch to ASCII display. The display will toggle between hexadecimal and ASCII displays each time the TR Key is pressed.
TR
TR
D0000D0001
"AB" 3031
D0000D0001
4142 3031
Note 1. A message contained in three words can be displayed by using ASCII display in combination with the Three-word monitor operation.
2. The Hexadecimal, BCD Data Modification Operation can be used while displaying ASCII data. Input values in 4-digit hexadecimal.
6-2-27 Displaying the Cycle Time
This operation is used to display the current average cycle time (scan time).
It is possible only in RUN or MONITOR mode while the program is being executed.
OK
RUN
OK
MONITOR
No
PROGRAM
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the MONTR Key to display the cycle time.
MONTR
00000SCAN TIME
012.1MS
“MS” in the display indicates the unit “ms” for the cycle time.
There might be differences in displayed values when the MONTR Key is pressed repeatedly. These differences are caused by changing execution conditions.
105
Programming Example Section 6-3
6-2-28 Reading and Setting the Clock
This operation is used to read or set the CPU’s clock. The clock can be read in any mode, but can be set in MONITOR or PROGRAM mode only.
Operation
Read clock
Set clock
OK
No
RUN
OK
OK
MONITOR
OK
PROGRAM
OK
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
2. Press the FUN Key, SHIFT Key, and then the MONTR Key to display the date and time.
FUN SHIFT MONTR
TIM 99Ć02Ć22
11:04:32 MON(1)
3. Press the CHG Key to change the date and/or time.
CHG
TIM CHG?99Ć02Ć22
11:04:32 MON(1)
The digit that can be changed will flash. If necessary, input a new value with the Up and Down Arrow Keys or Numeric Keys. Press the CHG Key to move the cursor to the next digit. The following table shows the setting ranges for each value.
Year Month Day Hour Minute Second Day-of-week
00 to 99 01 to 12 01 to 31 00 to 23 00 to 59 00 to 59 0 to 6
(SUN to SAT)
4. Press the WRITE Key to write the new value.
WRITE
INST TBL READ
FUN018:HEX
Press the CLR Key to return to the initial display.
6-3 Programming Example
This section demonstrates all of the steps needed to write a program with the
Programming Console.
6-3-1 Preparatory Operations
Use the following procedure when writing a program to the CPM2B for the first time.
1, 2, 3...
1. Set the Programming Console’s mode switch to PROGRAM mode and turn on the CPM2B’s power supply. The password input display will appear on the Programming Console.
MONITOR
RUN PROGRAM
<PROGRAM>
PASSWORD!
2. Enter the password by pressing the CLR and then the MONTR Key.
CLR MONTR
<PROGRAM> BZ
106
Programming Example Section 6-3
3. Clear the CPM2B’s memory by pressing the CLR, SET, NOT, RESET, and then the MONTR Key. Press the CLR Key several times if memory errors are displayed.
00000
CLR
SET NOT RESET
MONTR
00000MEMORY CLR?
HR CNT DM
00000MEMORY CLR
END HR CNT DM
4. Display and clear error messages by pressing the CLR, FUN, and then the
MONTR Key. Continue pressing the MONTR Key until all error messages have been cleared.
00000
CLR
FUN
MONTR
00000
FUN (0??)
ERR/MSG CHK OK
5. Press the CLR Key to bring up the initial programming display (program address 00000). The new program can be written at this point.
00000
CLR
!
Caution Check the system thoroughly before starting or stopping the CPM2B to prevent any accidents that might occur when the program is first started.
107
Programming Example Section 6-3
6-3-2 Example Program
The following ladder program will be used to demonstrate how to write a program with the Programming Console. This program makes output IR 01000 flicker ON/OFF (one second ON, one second OFF) ten times after input
IR 00000 is turned ON.
Start input
00000 C000
20000 Self-holding bit
00000
20000
00004
20000 T002
TIM 001
#0010
1-second timer
00007
20000 T002
TIM 002
#0020
2-second timer
20000 T001
00010
20000
Count input
CP
R
CNT 000
#0010
10-count counter
Reset input
00014
20000 T001
01000
Flicker output (10 counts)
ON
OFF
END(01)
1
S
00017
The mnemonic list for the example program is shown in the following table. The steps required to enter this program from a Programming Console are described in 6-3-3 Programming Procedures.
Address Instruction Data Programming example procedures in 6-3-3
Programming Procedures
(1) Self-holding bit 00000
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
00017
LD
OR
AND NOT
OUT
LD
AND NOT
TIM
LD
AND NOT
TIM
LD
AND
LD NOT
CNT
LD
AND NOT
OUT
END (01)
C
T
#
T
#
T
#
T
00000
20000
000
20000
20000
002
001
0010
20000
002
002
0020
20000
001
20000
000
0010
20000
001
01000
---
(2) 1-second timer
(3) 2-second timer
(4) 10-count counter
(5) Flicker output (10 counts)
(6) END(01) instruction
108
Programming Example Section 6-3
6-3-3 Programming Procedures
The example program will be written to the CPM2B according to the mnemonic list in 6-3-2 Example Program. The procedure is performed beginning with the initial display. (Clear the memory before entering a new program.)
Note If an error occurs while inputting the program, refer to the Programming Manual for details on correcting the error.
(1) Inputting the Self-holding Bit
1, 2, 3...
1. Input the normally open condition IR 00000.
(It isn’t necessary to input leading zeroes.)
LD
00000
LD 00000
OR
WRITE
00001READ
NOP (000)
2. Input the OR condition IR 20000.
C
2
A
0
A
0
A
0
A
0
00001
OR 20000
WRITE
00002READ
NOP (000)
3. Input the normally closed AND condition C000.
(It isn’t necessary to input leading zeroes.)
OUT
AND
NOT CNT
00002
AND NOT CNT 000
WRITE
00003READ
NOP (000)
4. Input the OUT instruction IR 20000.
C
2
A
0
A
0
A
0
A
0
WRITE
00003
OUT 20000
00004READ
NOP (000)
(2) Inputting the One-second Timer
1, 2, 3...
1. Input the normally open condition IR 20000.
LD
C
2
A
0
A
0
A
0
A
0
00004
LD 20000
WRITE
00005READ
NOP (000)
2. Input the normally closed AND condition T002.
(It isn’t necessary to input leading zeroes.)
AND
NOT TIM
C
2
00005
AND NOT TIM 002
WRITE
00006READ
NOP (000)
3. Input the 1-second timer T001.
TIM
B
1
WRITE
00006
TIM 001
00006 TIM DATA
#0000
109
Programming Example Section
4. Input the SV for T001 (#0010 = 1.0 s).
B
1
A
0
WRITE
00006 TIM DATA
#0010
00007READ
NOP (000)
The following key operations are used to input the 2-second timer.
(3) Inputting the
Two-second Timer
1, 2, 3...
1. Input the normally open condition IR 20000.
LD
C
2
A
0
A
0
A
0
A
0
00007
LD 20000
WRITE
00008READ
NOP (000)
2. Input the normally closed AND condition T002.
(It isn’t necessary to input leading zeroes.)
AND
NOT TIM
C
2
WRITE
00008
AND NOT TIM 002
00009READ
NOP (000)
3. Input the 2-second timer T002.
TIM
C
2
00009
TIM 002
WRITE
00009 TIM DATA
#0000
4. Input the SV for T002 (#0020 = 2.0 s).
C
2
A
0
WRITE
00009 TIM DATA
#0020
00010READ
NOP (000)
(4) Inputting the 10-count
Counter
The following key operations are used to input the 10-count counter.
1, 2, 3...
1. Input the normally open condition IR 20000.
LD
C
2
A
0
A
0
A
0
A
0
WRITE
00010
LD 20000
00011READ
NOP (000)
2. Input the normally open AND condition T001.
(It isn’t necessary to input leading zeroes.)
AND
TIM
B
1
00011
AND TIM 001
WRITE
00012READ
NOP (000)
3. Input the normally closed condition IR 20000.
LD
NOT
C
2
A
0
A
0
A
0
A
0
WRITE
00012
LD NOT 20000
00013READ
NOP (000)
6-3
110
Programming Example Section 6-3
4. Input the counter 000.
CNT
A
0
00013
CNT 000
WRITE
00013 CNT DATA
#0000
5. Input the SV for counter 000 (#0010 = 10 counts).
B
1
A
0
WRITE
00013 CNT DATA
#0010
00014READ
NOP (000)
(5) Inputting the Flicker Output
1, 2, 3...
1. Input the normally open condition IR 20000.
LD
C
2
A
0
A
0
A
0
A
0
000014
LD 20000
AND
NOT TIM
WRITE
B
1
00015READ
NOP (000)
2. Input the normally closed AND condition T001.
(It isn’t necessary to input leading zeroes.)
00015
AND NOT TIM 001
WRITE
00016READ
NOP (000)
3. Input the OUT instruction IR 01000.
(It isn’t necessary to input leading zeroes.)
OUT
B
1
A
0
A
0
A
0
WRITE
00016
OUT 01000
00017READ
NOP (000)
(6) Inputting the END(001)
Instruction
Input END(01). (The display shows three digits in the function code, but only the last two digits are input for CPM2B PCs.)
A
0
FUN
B
1
WRITE
00017
FUN (0??)
00017
END (001)
00018READ
NOP (000)
6-3-4 Checking the Program
Check the program syntax in PROGRAM mode to make sure that the program has been input correctly.
1, 2, 3...
1. Press the CLR Key to bring up the initial display.
00000
CLR
111
Programming Example Section 6-3
2. Press the SRCH Key. An input prompt will appear requesting the desired check level.
SRCH
A
0
00000PROG CHK
CHK LBL (0Ć2)?
3. Input the desired check level (0, 1, or 2). The program check will begin when the check level is input, and the first error found will be displayed. If no errors are found, the following display will appear.
00017PROG CHK
END (001)00.1KW
Note Refer to the Programming Manual for details on check levels and the programming errors that may be displayed during a program check.
4. Press the SRCH Key to continue the search. The next error will be displayed. Continue pressing the SRCH Key to continue the search.
The search will continue until an END(01) instruction or the end of Program
Memory is reached.
If errors are displayed, edit the program to correct the errors and check the program again. Continue checking the program until all errors have been corrected.
6-3-5 Test Run in MONITOR Mode
Switch the CPM2B in MONITOR mode and check the operation of the program.
1, 2, 3...
1. Set the Programming Console’s mode switch to MONITOR mode.
RUN
MONITOR
PROGRAM
<MONITOR> BZ
2. Press the CLR Key to bring up the initial display.
00000
CLR
3. Force-set the start input bit (IR 00000) from the Programming Console to start the program.
LD
00000
LD 00000
MONTR
00000
^ OFF
SET
00000
ON
The cursor in the lower left corner of the display indicates that the force set is in progress. The bit will remain ON as long as the Set Key is held down.
4. The output indicator for output IR 01000 will flash ten times if the program is operating correctly. The indicator should go OFF after ten one-second flashes.
There is a mistake in the program if the output indicator doesn’t flash. In this case, check the program and force set/reset bits to check operation.
112
SECTION 7
Test Runs and Error Processing
This section describes procedures for test runs of CPM2B operation, self-diagnosis functions, and error processing to identify and correct the hardware and software errors that can occur during PC operation.
7-1 Initial System Checks and Test Run Procedure
7-1-1 Initial System Checks
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1-2 Flash Memory Precautions
7-2 CPM2B Test Run Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3 Self-diagnostic Functions
7-3-1 Identifying Errors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3-2 User-defined Errors
7-3-3 Non-fatal Errors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3-4 Fatal Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Troubleshooting Flowcharts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-5 Maintenance Inspections
7-6 Battery Replacement
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
114
114
114
114
115
115
116
116
117
118
125
126
113
CPM2B Test Run Procedure Section 7-2
7-1 Initial System Checks and Test Run Procedure
7-1-1 Initial System Checks
Check the following items after setting up and wiring the CPM2B, but before performing a test run.
Item
Power supply and
I/O connections
Points to check
Is the wiring correct?
Are the terminals securely tightened?
Are there any shorts between crimp terminals or wires?
Refer to 3-5 Wiring and Connections for details.
Connecting cables Are the cables all connected correctly and locked?
Refer to 3-5 Wiring and Connections for details.
Clearing Memory
Operating Mode at
Startup
Always clear memory before beginning to program the CPM2B. Although memory is cleared before the CPU Board is shipped, the contents of the DM,
HR, AR, and counter areas may change in transit.
When a CPU Board without a clock is being used and the contents of DM have been cleared, battery error detection must be disabled in the PC Setup by setting the leftmost digit of DM 6655 to 1.
See 1-3-3 Operating Mode at Startup to determine what mode the CPM2B will enter when the power is turned on.
7-1-2 Flash Memory Precautions
Observe the following precautions to protect the flash memory and ensure proper operation.
1, 2, 3...
1. If changes are made in the read-only DM area (DM 6144 through DM 6599) or PC Setup (DM 6600 through DM 6655), the PC’s operating mode must be changed to write the new contents to flash memory. If backup battery is replaced before the changes are written to flash memory, the changes will be lost.
The changes can be saved by switching the CPM2B to RUN or MONITOR mode or turning the CPM2B OFF and then ON again.
2. When contents of the program, read-only DM (DM 6144 through DM 6599), or PC Setup (DM 6600 through DM 6655) have been changed, startup processing will take up to 1,200 ms longer than usual. Be sure to take this onetime startup delay into account if it may affect operations.
3. If one of the following three operations is performed in MONITOR or RUN mode, the CPM2B’s cycle time will be extended by up to 1,200 ms and interrupts will be disabled while the program or PC Setup is being overwritten.
•
Program changes with the online edit operation
•
Changes to the read-only DM area (DM 6144 through DM 6599)
•
Changes to the PC Setup (DM 6600 through DM 6655)
A “SCAN TIME OVER” error won’t occur during these operations. Be sure to take this delay in the CPM2B’s I/O response times into account when performing online editing.
7-2 CPM2B Test Run Procedure
1, 2, 3...
1. Power Supply Application a) Check the CPM2B’s power supply voltage and terminal connections.
b) Check the I/O devices’ power supply voltage and terminal connections.
c) Turn on the power supply and check that the “PWR” indicator lights.
114
Self-diagnostic Functions Section 7-3 d) Use a Programming Device to set the CPM2B to PROGRAM mode.
2. I/O Wiring Checks a) With the CPM2B in PROGRAM mode, check the output wiring by turning on the output bits with the force set and force reset operations.
b) Check the input wiring with the CPM2B’s input indicators or a Programming Device’s monitor operations.
3. Test Run a) Use a Programming Device to set the CPM2B to RUN or MONITOR mode and check that the “RUN” indicator lights.
b) Check the sequence of operation with the force set/reset operations, etc.
4. Debugging
Correct any programming errors that are detected.
5. Saving the Program a) Use a Programming Device to write the program to a backup floppy disk.
b) Print out a hard copy of the program with a printer.
Note Refer to Section 4 Using Programming Devices for details on the Support Software and Programming Console operations.
7-3 Self-diagnostic Functions
The CPM2B is equipped with a variety of self-diagnostic functions to help identify and correct errors and reduce down time.
7-3-1 Identifying Errors
An error can be identified by the error message displayed on a Programming
Device, error flags in the AR and SR areas, and the error code output to SR 253.
Fatal and Non-fatal
Errors
Error Messages
Error Flags
Error Code
PC errors are divided into 2 categories based on the severity of the errors. The status of the ERR indicator (lit or flashing) shows which type of error has occurred.
ERR Lit (Fatal Error)
Fatal errors are serious errors which stop CPM2B operation. There are two ways to restart operation:
•
Turn the PC off and then on again.
•
Use a Programming Device to switch the PC to PROGRAM mode, and read/ clear the error.
ERR Flashing (Non-fatal Error)
Non-fatal errors are less serious errors which don’t stop CPM2B operation.
When an error is detected, a corresponding error message will be displayed on the Programming Console or other Programming Device connected to the PC.
When a hardware error is detected, the corresponding error flag in the AR or SR area will be turned ON.
When an error is detected, a specific 2-digit hexadecimal error code is output to
SR 25300 to SR 25307. The error code and time of occurrence are also output to the Error Log Area (DM 2000 to DM 2021).
!
WARNING When the CPM2B’s self-diagnosis function detects a fatal error or when a severe failure alarm (FALS) instruction is executed, PC operation will stop and all outputs will be turned OFF. External safety measures must be provided to ensure safety in the system. Not providing proper safety measures may result in serious accidents.
115
Self-diagnostic Functions Section 7-3
7-3-2 User-defined Errors
There are three instructions that can be used to define errors or messages.
FAL(06) causes a non-fatal error, FAL(07) causes a fatal error, and MSG(46) sends a message to the Programming Console or host computer connected to the PC.
FAILURE ALARM –
FAL(06)
FAL(06) is an instruction that causes a non-fatal error. The following will occur when an FAL(06) instruction is executed:
1, 2, 3...
1. The ERR indicator on the CPU Board will flash. PC operation will continue.
2. The instruction’s 2-digit BCD FAL number (01 to 99) will be written to
SR 25300 to SR 25307.
The FAL numbers can be set arbitrarily to indicate particular conditions, but the same number should not be used as both an FAL number and an FALS number.
To clear an FAL error, correct the cause of the error and then execute FAL 00 or use a Programming Device to clear the error.
SEVERE FAILURE ALARM –
FALS(07)
MESSAGE – MSG(46)
FALS(07) is an instruction that causes a fatal error. The following will occur when an FALS(07) instruction is executed:
1, 2, 3...
1. Program execution will be stopped and all outputs will be turned OFF.
2. The ERR indicator on the CPU Board will be lit.
3. The instruction’s 2-digit BCD FALS number (01 to 99) will be written to
SR 25300 to SR 25307.
The FALS numbers can be set arbitrarily to indicate particular conditions, but the same number should not be used as both an FAL number and an FALS number.
To clear an FALS error, use a Programming Device to switch the PC to PRO-
GRAM Mode, correct the cause of the error, and then clear the error.
MSG(46) is used to display a message on a Programming Device connected to the CPM2B. The message, which can be up to 16 characters long, is displayed when the instruction’s execution condition is ON.
7-3-3 Non-fatal Errors
PC operation and program execution will continue after one or more of these errors have occurred. Although PC operation will continue, the cause of the error should be corrected and the error cleared as soon as possible.
When one of these errors occurs, the POWER and RUN indicators will remain lit and the ERR indicator will flash.
Message
SYS FAIL FAL**
(** is 01 to 99 or 9B.)
SCAN TIME OVER
Battery error
(no message)
FAL No.
Meaning and appropriate response
01 to 99 An FAL(06) instruction has been executed in the program. Check the FAL number to determine conditions that would cause execution, correct the cause, and clear the error.
9B An error has been detected in the PC Setup. Check flags AR 1300 to AR 1302, and correct as directed.
AR 1300 ON: An incorrect setting was detected in the PC Setup (DM 6600 to
DM 6614) when power was turned on. Correct the settings in PROGRAM Mode and turn on the power again.
AR 1301 ON: An incorrect setting was detected in the PC Setup (DM 6615 to
DM 6644) when switching to RUN or MONITOR mode. Correct the settings in
PROGRAM Mode and switch to RUN or MONITOR mode again.
F8
F7
AR 1302 ON: An incorrect setting was detected in the PC Setup (DM 6645 to
DM 6655) during operation. Correct the settings and clear the error.
The cycle time has exceeded 100 ms. (SR 25309 will be ON.)
This indicates that the program cycle time is longer than recommended. Reduce cycle time if possible. (The CPM2B can be set so that this error won’t be detected.)
If the voltage of the C500-BAT08 backup battery is below the minimum level, the ERR indicator will flash and SR 25308 will be turned ON.
Replace the battery. (See 7-6 Battery Replacement for details.)
116
Self-diagnostic Functions Section 7-3
7-3-4 Fatal Errors
PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of these errors have occurred. CPM2B operation can’t be restarted until the PC is turned off and then on again or a Programming Device is used to switch the PC to PROGRAM mode and clear the fatal error.
All CPU Board indicators will be OFF for the power interruption error. For all other fatal operating errors, the POWER and ERR indicators will be lit. The RUN indicator will be OFF.
Message
Power interruption
(no message)
MEMORY ERR
NO END INST
I/O BUS ERR
I/O UNIT OVER
SYS FAIL FALS**
(** is 01 to 99 or 9F.)
FALS
No.
00
Meaning and appropriate response
F1
Power has been interrupted for more than 2 ms.
Check power supply voltage and power lines. Try to power-up again.
AR 1308 ON: There is a non-existent bit or word address in the user program. Check the program and correct errors.
AR 1309 ON: An error has occurred in flash memory. Replace the CPU Board.
F0
C0
AR 1310 ON: A checksum error has occurred in read-only DM (DM 6144 to DM 6599).
Check and correct the settings in the read-only DM area.
AR 1311 ON: A checksum error has occurred in the PC Setup. Initialize the PC Setup and input the settings again.
AR 1312 ON: A checksum error has occurred in the program. Check the program and correct any errors detected.
AR 1313 ON: A checksum error has occurred in the expansion instructions data and all function codes have been set the their default values. Reset the expansion instructions.
AR 1314 ON: Data was not maintained in an area specified for holding. Clear the error, check the data in the areas specified for holding, and try again.
END(01) is not written in the program. Write END(01) at the end of the program.
An error has occurred during data transfer between the CPU Board and an Expansion
I/O Board. Check the Board’s connecting cable.
Too many Expansion I/O Boards have been connected. Check the Board configuration.
E1
01 to 99 A FALS(07) instruction has been executed in the program. Check the FALS number to determine the conditions that caused execution, correct the cause, and clear the error.
9F The cycle time has exceeded the Maximum (Watch) Cycle Time setting (DM 6618).
Check the cycle time and adjust the Maximum Cycle Time setting if necessary.
117
Troubleshooting Flowcharts Section 7-4
7-4 Troubleshooting Flowcharts
Use the following flowcharts to troubleshoot errors that occur during operation.
Main Check
Error
PWR indicator lit?
Yes
No
Check power supply. (See page 119.)
RUN indicator lit?
Yes
No
Operation stopped. Check for fatal errors.
(See page 120.)
ERR indicator flashing?
Not lit
Flashing
Is I/O sequence normal?
Yes
No
Operating environment normal?
No
Yes
Replace the CPU
Board.
Check for non-fatal errors. (See page 121.)
Check I/O. (See page 122.)
Check operating environment. (See page 124.)
118
Troubleshooting Flowcharts
Power Supply Check
Section 7-4
PWR indicator not lit.
Is power being supplied?
Yes
No
No
Connect power supply.
Is PWR indicator lit?
Yes
Is voltage adequate?
No
Yes
No
Set supply voltage within acceptable limits.
Is PWR indicator lit?
Yes
Are there any loose terminal screws or broken wires?
No
Yes
No
Tighten screws or replace wires.
Is PWR indicator lit?
Yes
Has the external power supply shorted or overloaded?
No
Yes
No
Correct the short circuit or limit the connected load to the specification range.
Is PWR indicator lit?
Yes
Replace the CPU
Board.
End
119
Troubleshooting Flowcharts
Fatal Error Check
RUN indicator not lit.
No
Is the ERR indicator lit?
Yes
Determine the cause of the error with a
Programming Device.
Section
Yes
Is PC mode displayed on Programming
Device?
No
Is PC mode displayed on
Programming Device?
Yes
No
Turn the power supply OFF, and then ON again.
Is a fatal error displayed?
No
Switch to RUN or
MONITOR mode.
Yes
Identify the error, eliminate its cause, and clear the error.
Follow the Memory Error
Check flowchart if a memory error has occurred.
7-4
Is the RUN indicator lit?
Yes
End
No
Replace the CPU
Board.
120
Troubleshooting Flowcharts
Non-fatal Error Check
Section 7-4
ERR indicator flashing.
Determine the cause of the error with a Programming Device.
Is a non-fatal error indicated?
No
Yes
Identify the error, eliminate its cause, and clear the error.
Is the ERR indicator flashing?
Not lit
Flashing
End
Replace the CPU
Board.
121
Troubleshooting Flowcharts
I/O Check
Section
The I/O check flowchart is based on the following ladder diagram section.
7-4
(LS1)
00002
(LS2)
00003
01003
01003
SOL1
SOL1 malfunction.
Malfunction of SOL1
Is the
IR 01003 output indicator operating normally?
No
Yes
Check the voltage at the
IR 01003 terminals.
Wire correctly.
Operation OK?
Yes
No
No
Is output wiring correct?
Yes
Is the external power supply shorted or overloaded?
No
Yes
Disconnect the external wires and check the conductivity of each wire.
Correct the short circuit or limit the connected load to the specified range.
Monitor the ON/OFF status of IR 01003 with a Programming
Device.
Operation OK?
Yes
No
A
To next page
Yes
Operation OK?
No
Check output device
SOL1.
Replace the CPU Board or Expansion I/O Board with the problem.
122
Troubleshooting Flowcharts
A
From previous
Are the IR 00002 and IR 00003 input indicators operating normally?
Yes page
Check the voltage at the IR 00002 and
IR 00003 terminals.
Section
Check the voltage at the IR 00002 and
IR 00003 terminals.
Operation OK?
No
Yes
No
Yes
Check operation by using a dummy input signal to turn the input ON and OFF.
Operation OK?
No
Yes
Is input wiring correct?
No
Wire correctly.
Yes
Tighten the terminal screws
Are the terminal screws loose?
No
No
Operation OK?
Yes
Replace the CPU
Board or Expansion
I/O Board.
Check input devices
LS1 and LS2.
Return to “start.”
Replace the CPU
Board or Expansion
I/O Board.
7-4
123
Troubleshooting Flowcharts
Environmental Conditions Check
Section 7-4
Environmental conditions check
Is the ambient temperature below 55
°
C?
Yes
No
Consider using a fan or cooler.
Is the ambient temperature above
0
°
C?
Yes
No Consider using a heater.
Is the ambient humidity between 10% and
85%?
Yes
No
Is noise being controlled?
Yes
Consider using an air conditioner.
No
Install surge protectors or other noisereducing equipment at noise sources.
Is the installation environment okay?
End.
Yes
No
Consider constructing an instrument panel or cabinet.
124
Maintenance Inspections
Memory Error Check
Memory error occurred.
AR 1309 ON?
No
Yes Replace the CPU
Board.
AR 1314 ON?
No
Yes Check/correct backed-up data and clear error.
Section 7-5
AR 1308 ON?
No
Yes
Check the program, correct any errors, and clear the error.
No
AR 1310 to
AR 1312 ON?
No
Yes
Turned ON during startup?
No
Yes
Check the error indicated by the flag that is ON, correct settings as required, and write data to the flash memory.
Check the external environment.
End
7-5 Maintenance Inspections
In order for your SYSMAC system to operate in optimum condition, be sure to carry out daily or periodical inspections.
Inspection Items The main system components of a SYSMAC system are semiconductors, and it contains few components with limited lifetimes. Poor environmental conditions, however, can lead to deterioration of the electrical components, making regular maintenance necessary.
125
Battery Replacement Section 7-6
The standard period for maintenance checks is 6 months to 1 year, but more frequent checks are required if the PC is operated in more demanding conditions.
If the criteria are not met, adjust to within the specified ranges.
Inspection items
Power supply
Details
Determine whether the voltage fluctuation at the power supply terminals is within specifications.
Environmental conditions
I/O power supply
Is the ambient temperature inside the panel appropriate?
Is the ambient humidity inside the panel appropriate?
Has dirt or dust collected?
Is the voltage fluctuation measured at the
I/O terminals within the standard range?
Are all Boards securely installed?
Installation status
Are all connection cables and connectors inserted completely and locked?
Are any of the external wiring screws loose?
Are any of the external wiring cables frayed?
Product service life Contact output relay
Criteria
Within the voltage variation range (20.4 to 26.4 VDC)
0 to 55
_
C
35% to 85% RH with no condensation
None
Each I/O terminal must conform to the specifications
Nothing is loose
Nothing is loose
Nothing is loose
No external abnormalities
Tester
Remarks
Thermometer
Hygrometer
Visual inspection
Tester
Phillips screwdriver
Visual inspection
Phillips screwdriver
Visual inspection
---
Battery (C500-BAT08)
Electrical:
Resistance load:
300,000 operations
Inductive load:
100,000 operations
Mechanical:
10,000,000 operations
5 years ---
Required Tools Standard Tools (Required)
•
Screwdrivers (Phillips and flat-blade)
•
Voltage tester or digital voltage meter
•
Industrial alcohol and a cotton cloth
Measurement Devices (May be Needed)
•
Synchroscope
•
Cathode-ray oscilloscope
•
Thermometer, hygrometer
Note Do not attempt to disassemble, repair, or modify the PC in any way.
7-6 Battery Replacement
!
WARNING Do not drop, disassemble, crush, short-circuit, recharge, or dispose of the battery in fire. The battery may explode, burn, or leak and cause personal injury.
Precautions Turn ON the power supply for at least 5 minutes before replacing the battery in order to recharge the backup capacitor.
Turn OFF the power supply to the CPU Board before replacing the battery.
Use the procedure below when replacing the battery. This procedure must be completed within 5 minutes to prevent loss of memory contents.
Dispose of the old battery properly.
Replacement Procedure CPU Boards that are equipped with a clock are also equipped with a backup battery that has a 5-year lifetime at 25
_
C. Use the following procedure when replacing the backup battery.
1, 2, 3...
1. Stop CPM2B operation and turn OFF the CPM2B’s power supply.
126
Battery Replacement Section 7-6
2. Disconnect the battery connector and remove the battery.
3. Install the new battery. Check the alignment of the connector and fully insert the connector. Make sure that the power wires are not pinched.
4. Enable the detection of battery errors in the PC Setup by setting the leftmost digit of DM 6655 to 0.
127
Appendix A
Standard Models
CPU Boards
Appearance Relay outputs
CPM2B-32C1DR-D
CPM2B-32C2DR-D
---
---
---
---
Transistor outputs
(sinking)
Internal clock.
RS-232C port, and battery
No
Number of inputs
16 points
Yes
CPM2B-32C1DT-D No
CPM2B-32C2DT-D Yes
Number of outputs
16 points
Accessories: Four studs, four M3 screws
Expansion I/O Boards
Appearance Relay outputs
CPM2B-32EDR ---
Transistor outputs
(sinking)
Power supply
---
Number of inputs
16 points
Number of outputs
16 points
--CPM2B-32EDT --16 points 16 points
Accessories: Four long studs, four M3 screws
Expansion I/O Cable
Appearance Model
CPM2B-CN601
Specifications
Connects an Expansion I/O Board to the CPU Board or another Expansion
I/O Board. (This cable is identical to the cable supplied with an Expansion
I/O Board.)
Mounting Bracket
Appearance Model
CPM2B-ATT01
Specifications
Includes four M3
×
4 mounting screws.
Note The CPM2B-ATT01 Mounting Bracket is required when the system must meet UL/CSA standards.
129
Standard Models
I/O Connectors
Appearance
Appendix A
Model
XG5M-2032-N
XG5M-2035-N
XG5S-2012
XG5S-1001
XG4M-2030
XG4T-2004
Socket (for AWG 24 wire)
Name
Socket (for AWG 26 to AWG 28 wire)
Full Cover (two are required for each socket)
Partial Cover (two are required for each socket)
Socket
Strain Relief
Communications Port Connecting Cables
Appearance Name
CS1W-CN114
Connecting Cable
CPM2C-CN111
Connecting Cable
Specifications
Peripheral port to Programming Console cable.
Peripheral port to Programming Console cable.
0.05 m
Length
0.1 m
Peripheral Devices
Appearance Model Number
CQM1-PRO01-E
Name
Programming Console
Specifications
2-m Connecting Cable attached
C200H-PRO27-E
C200H-CN222
C200H-CN422
CS1W-CN224
CS1W-CN624
WS02-CXPC1-E CX-Programmer
C500-ZL3AT1-E
WS01-CPTB1-E
SYSMAC Support
Software
SYSMAC-CPT
Hand-held, w/backlight; requires a
C200H-CN222 or C200H-CN422 Connecting
Cable, see below.
Connects the C200H-PRO27-E.
2-m cable
4-m cable
Connects the C200H-PRO27-E directly to a CPM2B CPU Board.
2-m cable
6-m cable
For MS-Windows 95/98/NT (CD-ROM)
3.5”, 2HD for IBM PC/AT compatible
For IBM PC/AT or compatible computers
(3.5” disks (2HD) and CDROM)
130
Standard Models
Maintenance Accessories
Appearance Model Number
C500-BAT08
Name
Backup Battery
Appendix A
Specifications
---
CPM1-EMU01-V1 Expansion Memory Unit Uploads the ladder program and DM 6144 to DM 6655 from the PC to the EEPROM and downloads the ladder program and
DM 6144 to DM 6655 from the EEPROM to the PC.
EEROM-JD EEPROM 256 K bit
Adapters and Connecting Cables (1:1 Connection)
CPM2B port
Peripheral
Appearance Model number
CQM1-CIF02
Name
RS-232C
Comments Cable length
For a 9-pin computer serial port 3.3 m
CPM1-CIF01 Use for peripheral port to
RS-232C level conversion
RS-232C XW2Z-200S-V
XW2Z-500S-V
RS-232C For a 9-pin computer serial port 2 m
Cable
5 m
Adapters and Connecting Cables (1:N Connections)
Appearance Model number
NT-AL001-E
Name
RS-422 Adapter
3G2A9-AL004-E Link Adapter
Specifications
Use for CPM2B RS-232C port to RS-422A conversion.
Requires a 5-VDC, 150 mA power supply which is supplied through the CPM2B connection.
(Can also be connected to a personal computer, but this connection requires an external 5-VDC power supply.)
Use for personal computer RS-232C port to RS-422A.
(Can also be connected to a CPM2B.)
CPM1-CIF11 RS-422 Adapter Use for CPM2B peripheral port to RS-422A conversion.
XW2Z-070T-1
XW2Z-200T-1
RS-232C Cables
(For use with the
NT-AL001-E.)
Use for CPM2B RS-232C port to NT-AL001-E connection. (0.7-m cable)
Use for CPM2B RS-232C port to NT-AL001-E connection. (2-m cable)
131
Appendix B
Dimensions
All dimensions are in millimeters.
CPU Boards and Expansion I/O Boards
Mounting Bracket (CPM2B-ATT01)
164
174
Six 3.5 dia.
Four 4.5 dia.
164
186
196
133
Dimensions
Assembly Dimensions
Front view
28
28
28
28
14
Side view
164
186
206
Appendix B
CPU Board
Expansion I/O Board
Mounting Bracket
134
Numbers
1:N connections, 10
A arc killer, examples, xvii
ASCII, converting displays, Programming Console, 105 atmosphere, 22
B battery, replacing, 126 binary data, modifying, Programming Console, 101 bit status, force-set/reset, Programming Console, 104 bits, searching, Programming Console, 92 buzzer operation, Programming Console, 86
C cabinet installation, precautions, 37
Programming Console installation, 82 cables, available models, 130, 131 characteristics, 23 checking, program syntax, Programming Console, 94 circuit configuration inputs, 25 outputs, relay, 27 clearing, memory areas, Programming Console, 85 clock, reading and setting the clock, 106 communications capabilities, overview, 4 components, Expansion I/O Boards, 32 conduit installation, 41 counters changing SV, Programming Console, 100 example of inputting, 110
CPU Boards available models, 129 dimensions, 133
CPU Units cyclic operation, 16 internal structure, 13
CX-Programmer, 8 cycle time, displaying, Programming Console, 105 cyclic operation, 16
Index
D data, modifying, Programming Console, 99–100, 101, 102, 103 data link, 5, 12 date. See clock decimal data with sign. See signed decimal data decimal data without sign. See unsigned decimal data dielectric strength, 22 differentiated instructions, entering, 90 dimensions, 133 displays converting between hex and ASCII, Programming Console,
105 cycle time, Programming Console, 105 duct installation, 40
E
EC Directives, precautions, xv electrical noise, preventing, 37, 40
ERR indicator flashing, 116 lit, 117 error log, 69 errors error processing, 113 fatal, 117 identifying, 115 non-fatal, 116
PC Setup, 65 reading/clearing messages, Programming Console, 86 user-defined errors, 116
Expansion I/O Boards available models, 129 components, 32 dimensions, 133
Expansion I/O Cable, available models, 129 expansion instructions function codes, 76 reading and changing function code assignments, 87
F–H
FAL numbers, 116
FAL(06), 116
FALS numbers, 117
FALS(07), 116 false inputs, 48 fatal errors, troubleshooting, 120
135
features, 2 flash memory, precautions, 114 flicker output, example, 111 force-set/reset clearing, Programming Console, 104
Programming Console, 104 function codes expansion instructions, 76 reading and changing expansion instruction assignments, 87 functions, 5 hexadecimal data, converting displays, Programming Console,
105
I–L
I/O capacity, 23
I/O connectors available models, 130 pin allocation, Expansion I/O Units, 33 wiring, 43
I/O errors, troubleshooting, 122
I/O line noise, preventing, 40
I/O terminals, allocation, Expansion I/O Units, 33 indicators flashing ERR indicator, 116 lit ERR indicator, 117
PC status indicators, 30 inductive loads, 48, 51 initialization, time required, 15 input devices, connecting, 46 input specifications, 25, 27 inputs, wiring, 45 inrush current, suppressing, 52 inspections, 125 installation, site, selecting, 36 instructions expansion, 76 inserting and deleting, Programming Console, 93 mnemonics list, ladder, 73 searching, Programming Console, 91 insulation resistance, 22 interlocks, 36 interrupt program execution, in cyclic operation, 18 leakage current, 48
LED indicators, 30 limit switches, preventing false inputs, 48
Index
M maintenance, 125 memory backup, 24 protection, 24 memory areas
AR area bits, CPM2A/CPM2C, 60 clearing, Programming Console, 85 flags and control bits, CPM2A/CPM2C, 58 partial clear, 85 messages, reading/clearing, 86 mode, changing the PC mode, 80 modes, operating modes, 14 modifying binary data, Programming Console, 101 data, Programming Console, 99 hexadecimal/BCD data, Programming Console, 101 signed decimal data, Programming Console, 102
SV, Programming Console, 100 unsigned decimal data, Programming Console, 103
MONITOR mode description, 80 example test run, 112 monitoring
3-word monitor, Programming Console, 98 binary monitor, Programming Console, 97–98 differentiation monitor, Programming Console, 96–97 signed decimal monitor, Programming Console, 98–99 status, Programming Console, 94 unsigned decimal monitor, Programming Console, 99 motor control, capabilities, 2
MSG(46), 116
N noise, preventing electrical noise, 37, 40 noise immunity, 22 non-fatal errors, troubleshooting, 121
NPN current output, connecting, 46
NPN open collector, connecting, 46
NT Link, connections, 11
O operating conditions, troubleshooting, 124 operating modes, 14 operating mode at startup, 14 operation, preparations, 82 output short protection, 51 output specifications relay output, 27 transistor output, sink type, 28
136
output wiring, relay output, 49
P–R panel, Programming Console installation, 82 panel installation, precautions, 37 password, entering on Programming Console, 83
PC mode, changing, 80
PC Setup. See settings
PC status, indicators, 30
Peripheral Devices, 130 available models, 130 photoelectric switches, preventing false inputs, 48
PNP current output, connecting, 46 position control, 3 power, consumption, 22 power cables, 40 power interruption, detection, 15 power supply precautions, 36 troubleshooting, 119, 125 wiring, 41 precautions design precautions, 36 general, xi program, programming example, 106 program capacity, 23 program execution, in cyclic operation, 17 program memory, setting address and reading content, Programming Console, 88
PROGRAM mode, description, 80 programming checking the program, 111–112 checks for syntax, Programming Console, 94 inserting and deleting instructions, Programming Console,
93–94 preparation for, 106 searching, Programming Console, 91–92 setting and reading a memory address, Programming Console, 88 special features, 76
Programming Console connecting, 81 connections, 8 keys, 78 models, 78 operations, 84
Programming Devices, using, 77 programming example, 106 programs, entering and editing, Programming Console, 88 proximity switches, preventing false inputs, 48
Index pulse control, 2 pulse outputs, 3 wiring, 51 quick-response inputs, 3 relay outputs, connecting, 46
Relay Terminals, connections, 44
RUN mode, description, 80
S search instruction, Programming Console, 91–92 operands, Programming Console, 92 self-diagnosis functions, 24 self-holding bit, example, 109 self-diagnostic functions, 115 settings, changing, 64 shock resistance, 22 signed decimal data modifying, Programming Console, 102 monitoring, 98–99 specifications characteristics, 23 general specifications, 22 input specifications, 25, 27 output specifications relay output, 27 transistor output, sink type, 28 terminal blocks, 42 status, monitoring, Programming Console, 94
Support Software, 8
SV, modifying, Programming Console, 100 syntax, checking the program, Programming Console, 94
SYSMAC Support Software, 8
SYSMAC-CPT Support Software, 8 system, checks, 114 system configuration, 6
T temperature, operating, storage, 22 temperature, ambient, 22 terminal blocks connections, 44 specifications, 42 wiring, 42 test run example, 112 procedure, 114 time. See clock timers
137
changing SV, Programming Console, 100 example of inputting, 110 troubleshooting, 118 fatal errors, 120
I/O errors, 122 non-fatal errors, 121 operating conditions, 124 power supply, 119, 125
U unsigned decimal data
Index modifying, Programming Console, 103 monitoring, 99
V–W vibration resistance, 22 voltage, supply voltage, 22 voltage output, connecting, 46 wiring, 40
I/O connectors, 43 power supply, 41 terminal blocks, 42
138
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W371-E1-1
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
1
Date
February 2000 Original production
Revised content
139
Download
Advertisement
Key features
Compact Board Design
Synchronized Pulse Control
High-speed Counters & Interrupts
Multiple Communication Options
Expansion I/O Boards (up to 128 I/O points)
Built-in Clock and Timer Functions
Frequently asked questions
Relay outputs and sinking transistor outputs are available.
The CPM2B can handle up to 128 I/O points with expansion boards.
It supports Host Link, no-protocol communications, 1:1 PC Link, and 1:1 NT Link communications.
There are five high-speed counter inputs.
The clock provides the current year, month, day, day of the week, and time; it can be read from the program and adjusted.