- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- MGE UPS Systems
- Comet EXtreme 4.5
- Installation And User Manual
MGE UPS Systems | 5103304XXX | 5103304 Comet EXtreme | 5103359 Comet EXtreme | Comet EXtreme 4.5 | Installation And User Manual | Comet EXtreme
Add to my manuals
32 Pages
MGE UPS Systems 5103304 Comet EXtreme protects your electrical equipment with its many features. Its compact design, either as a tower or rack, suits your preferences. During a power outage, it automatically switches to battery power within milliseconds, so your equipment experiences no disruption. This UPS also includes a variety of customizable settings for a personalized experience.
advertisement
Comet EXtreme
4.5/6/9/12 kVA
Installation and
User Manual
w w w . m g e u p s . c o m
86-153719-00 B00
- Page 1
Introduction
Note
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Comet EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products.
Measures that have made Comet EXtreme a reference in environmental protection include:
◗
production in an ISO 14001 certified factory;
◗
recycling of Comet EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Comet EXtreme range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
For service call
1-800-438-7373
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Page 2 -
86-153719-00 B00
Safety Instructions
Important: Save these instructions.
This manual contains important instructions for Comet EXtreme UPS Models that must be followed during installation, operation and maintenance of the UPS and batteries.
The Comet EXtreme UPS Models that are covered in this manual are listed below.
5103304XXX
5103306XXX
5103309XXX
5103312XXX
5103354XXX
5103356XXX
5103359XXX
5103362XXX
Tightening torque for all input and output terminal blocks shall be 10.6 - 12.3 in - lbs. (1.2 - 1.4 Nm) for 4.5
and 6 kVA models and 21.8 - 26.1 in - lbs (2.5 - 3 Nm) for 9 and 12 kVA models.
The normal battery voltage for all models is 240 VDC.
The Comet EXtreme server UPS is intended for installation in a temperature controlled indoor area, free of conductive contaminants.
86-153719-00 B00
- Page 3
Safety of persons
A UPS has its own internal power source (the battery). Consequently, the output terminals may be energized even if the UPS is disconnected from the AC-power source.
Dangerous voltage levels are present within the UPS. It should be opened exclusively by qualified service personnel.
The UPS must be properly earthed.
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed.
◗
Never operate the UPS if the ambient temperature and relative humidity are higher than the levels specified in the documentation.
◗
Never burn the battery (risk of explosion).
◗
Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
◗
Comply with all applicable regulations for the disposal of the battery.
Product safety
The UPSs connection to the AC-power source must be protected by a circuit breaker that is easily accessible.
The UPS can be disconnected from the AC-power source by opening the circuit breaker.
◗
Never install the UPS near liquids or in an excessively damp environment.
◗
Never let a liquid or foreign body penetrate inside the UPS.
◗
Never block the ventilation grates on the front or back of the UPS.
◗
Never expose the UPS to direct sunlight or a source of heat.
Special precautions
The UPS connection instructions contained in this manual must be followed in the indicated order.
Check that the indications on the rating plate correspond to your AC-power system and to the actual electrical consumption of all the equipment to be connected to the UPS.
If the UPS is positioned flat, check that not more than five modules are stacked on top of each other.
If the UPS must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -40
°
C to +50
°
C.
If the UPS remains de-energized for a long period, we recommend that you energize the UPS for a period of 24 hours, at least once every month.
This charges the battery, thus avoiding possible irreversible damage.
Page 4 -
86-153719-00 B00
Warning
Batteries can present a risk of electrical shock and/or burn from high short circuit current. Observe proper precautions. Do not open battery packs. There are NO user-servicable parts within. Do not allow anything to touch the battery terminals. Do not pierce battery pack wiring insulation. Do not allow conductive tools or jewelry to touch battery packs or battery terminals.
86-153719-00 B00
- Page 5
Foreword
Using this document
Information may be found primarily by consulting:
◗
the contents;
◗
the index.
Pictograms
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Page 6 -
86-153719-00 B00
Contents
1.
Presentation
1.1
Comet EXtreme range ................................................................................................................ 9
1.2
Back ........................................................................................................................................... 11
1.3
Control panel ............................................................................................................................... 12
2.
Installation
2.1
Unpacking and checks ............................................................................................................... 13
"Tower" and "rack" model: 4,5 and 6 kVA ..................................................................................... 13
"Tower" and "rack" model: 9 and 12 kVA ...................................................................................... 13
2.2
Installation (rack version) .......................................................................................................... 14
2.3
Battery-module connections ..................................................................................................... 15
2.4
Connection to the RS 232 communications port (optional) ................................................... 16
2.5
Installation of the communications-card option ...................................................................... 16
2.6
Connection to the connection modules ................................................................................... 17
2.7
Emergency Power Off ................................................................................................................. 18
3.
Operation
3.1
Operating mode .......................................................................................................................... 19
ON-LINE mode ............................................................................................................................. 19
3.2
Start-up ........................................................................................................................................ 20
3.3
Bargraph indications .................................................................................................................. 20
3.4
Failure of AC input power and operation on battery power .................................................... 21
Transfer to battery power .............................................................................................................. 21
Threshold for the low-battery shutdown warning .......................................................................... 21
End of backup time ....................................................................................................................... 21
Sleep mode ................................................................................................................................... 21
Return of AC input power .............................................................................................................. 21
86-153719-00 B00
- Page 7
Contents
3.5
Personalization ............................................................................................................................ 22
Function .................................................................................................................................................. 22
"ON / OFF conditions" tab ....................................................................................................................... 22
"Battery" tab ............................................................................................................................................ 23
"Output" tab ............................................................................................................................................. 23
"By-pass" tab .......................................................................................................................................... 23
3.6
Shutdown ...................................................................................................................................... 24
4.
Maintenance
4.1
Troubleshooting ........................................................................................................................... 25
4.2
Replacement of the electronic module ...................................................................................... 26
5.
Environment
............................................................................................................................ 27
6.
Appendices
6.1
Glossary ........................................................................................................................................ 28
6.2
Index .............................................................................................................................................. 30
Page 8 -
86-153719-00 B00
1.1 Comet EXtreme range
4,5 and 6 kVA tower models:
4,5 and 6 kVA rack models:
1. Presentation
Electronic module
Battery module
Dimensions in inches
(H x W x D)
17.45 x 6.81 x 18.3
17.45 x 6.81 x 18.3
Electronic module
Battery module
Weight in lbs.
31
106
Electronic module
Battery module
Dimensions in inches
(H x W x D)
6.97(4u) x 19.01 x 18.19
6.97(4u) x 19.01 x 18.19
Electronic module
Battery module
Weight in lbs.
40
112
86-153719-00 B00
- Page 9
1. Presentation
9 and 12 kVA tower models:
9 and 12 kVA rack models:
Electronic module
Battery module
Dimensions in inches
(H x W x D)
17.45 x 8.50 x 18.3
17.45 x 6.81 x 18.3
Electronic module
Battery module
Weight in lbs.
48
106
Electronic module
Battery module
Dimensions in inches
(H x W x D)
8.7 (5u) x 19 x 18.18
6.96 (4u) x 19 x 18.18
Electronic module
Battery module
Weight in lbs.
60
112
Page 10 -
86-153719-00 B00
1.2 Back
Comet EXtreme 4,5 and 6 kVA:
5a connector for battery extension modules.
5b emergency power off.
Comet EXtreme 9 and 12 kVA:
1. Presentation
1
RS232 communications port.
2 battery circuit breaker.
3 communications-card option.
4
EXB battery module connector.
6 rating plate.
7 manual by-pass switch.
8 connection module.
9 output terminal block.
10 input terminal block.
5b emergency power off.
4 EXB battery module connector.
86-153719-00 B00
- Page 11
1. Presentation
1.3 Control panel
Alarms
11
UPS overload
% battery
remaining
100%
12 electronics fault
80%
50% 13 battery fault
14
15
16 ambient temp.
> 40
°
C hold down to display percent load.
lamp test or buzzer OFF.
20%
17
18 operation on manual bypass.
operation in Automatic Bypass mode.
19
20 operation in ON-LINE mode.
operation on battery power.
21
ON/OFF.
% load
100%
80%
50%
20%
Page 12 -
86-153719-00 B00
2.1 Unpacking and checks
Comet EXtreme 4,5 and 6 kVA:
Electronic module
22
24
Battery module
23
27
25
26
27
25
2. Installation
Comet EXtreme 9 and 12 kVA:
Electronic module
22
24
22
26
23
24
25
Battery module
25
23
25
22
23
24
26
25
25
27
27
26
25
27
27
86-153719-00 B00
- Page 13
2. Installation
2.2 Installation (rack version)
Rack mounting diagram with rails.
1
3
3
3
3
2
The rails and the necessary mounting hardware are supplied with the UPS in the package.
4
Page 14 -
86-153719-00 B00
2.3 Battery-module connections
Comet EXtreme 4,5 and 6 kVA:
2
4
27 battery modules.
2. Installation
Comet EXtreme 9 and 12 kVA :
2
4 battery modules.
27
* Transformer connections (120 volt models)
Refer to Transformer Installation Guide.
86-153719-00 B00
- Page 15
2. Installation
2.4 Connection to the RS 232 communications port (optional)
1 port on the computer.
22
The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.
Pin-out diagram for the RS 232 communications port on the UPS.
1
RD TD
OV
5 4 3 2 1
9 8 7 6
RTS
2.5 Installation of the communications-card option
3
Slots for communications card.
It is not necessary to shut down the UPS to install the communications card:
2. Insert the card in the slot.
3. Secure the card with the two screws.
Page 16 -
86-153719-00 B00
2. Installation
2.6 Connection to the connection modules
This type of connection must be carried out by qualified electrical personnel.
and that the upstream protection devices ( AC-power source) are open (OFF).
29
28
The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.
cable size gauge
EXtreme 4,5 to 6 kVA
EXtreme 9 to 12 kVA
20 to 6 AWG
20 to 6 AWG
2. Remove the cable entry knockouts from the cover.
4. Insert the cable supplying the equipment and the power cable
9
10
28
Always connect the earthing wire first.
5. Connect the three wires of the equipment cable to the output
6. Connect the three wires of the power cable to the input
29
10
9
Earthing wires
86-153719-00 B00
- Page 17
2. Installation
2.7 Emergency Power Off (EPO)
The end user is responsible for the installation of an emergeny power off function. Installation must be carried out in compliance with local code regulations.
To power down the entire installation via an emergency power off function, the action should perform the following via a single device:
◗
◗
◗ sever the AC input power to the Comet EXtreme remotely trip off the battery circuit breaker on the Comet EXtreme remotely trip off the circuit breaker for the additional battery cabinet(s), if applicable
Battery circuuit breaker shunt trip connection
To accomodate the EPO function, the Comet EXtreme UPS and battery cabinets come equipped with battery circuit breakers with shunt trip mechanisms. By applying 24 Vdc or 24 VAC across the shunt trip coil, the circuit breaker will trip off, thereby disconnecting battery input to the inverter.
◗
◗
◗
Check that the upstream circuit breaker on the low voltage switchboard, the input circuit breaker, and the battery circuit breaker are all in "off" position
◗
Connect the 24Vdc or 24 VAC output of the EPO circuit to the shunt trip coil across terminals 1 and 4
Once the connections are made, reposition the connection cover panel and reset all circuit
breakers
Connection diagram for battery circuit breaker shunt trip on terminal block
1
Emergency Power Off
2 3 4
emergency off button
+
24 VDC/VAC
–
Page 18 -
86-153719-00 B00
3.1 Operating mode
ON-LINE mode
3. Operation
19
This is the standard operating mode, set by default in the factory.
It makes use of electronic double conversion of the input power.
Two possible cases:
from the AC-power source and supplied to the protected equipment via the UPS.
from the battery and supplied to the protected equipment.
20
86-153719-00 B00
- Page 19
3. Operation
3.2 Start-up
The protected equipment connected to the UPS can be energized, whether AC input power is available or not.
Prior to initial start-up, check the UPS voltage settings. If the protected equipment voltage is other than 208 V / 60 Hz, the UPS settings must be modified using the "UPS Driver" software
24
(see section 3.5).
2
21
All connected equipment is energized. The buzzer sounds.
3.3 Bargraph indications
11
12
13
14
15
1. Remaining backup time in percent (in ON-LINE mode).
2. Percent load drawn by the protected equipment,
3. Operating faults (flashing LED and beeps):
11 Overload.
12
UPS fault.
13
Battery fault.
14
Excessive ambient temperature.
Page 20 -
86-153719-00 B00
3. Operation
3.4 Failure of AC input power and operation on battery power
AC input power is not available, the battery steps in to supply the protected equipment.
Transfer to battery power
the buzzer beeps three times.
20
Threshold for the low-battery shutdown warning
The low-battery shutdown warning threshold can be set by the user, with the "UPS Driver" software (see section 3.5).
20
The buzzer beeps every three seconds.
There is very little remaining battery backup time.
Close all applications because UPS automatic shutdown is imminent.
End of backup time
The buzzer sounds continuously.
16
The equipment is no longer supplied with power.
Sleep mode
This operating mode may be personalized using the "UPS Driver" software (see section 3.5).
It saves battery power when no equipment is connected to the UPS.
The UPS automatically restarts when the AC-power source returns to within tolerances.
Return of AC input power
If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function
(activated by return of AC input power) has not been disabled (see section 3.5).
86-153719-00 B00
- Page 21
3. Operation
3.5 Personalization
Function
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
is closed.
"UPS Driver" installation:
1. Insert the "UPS Driver" diskette in the drive of an IBM-compatible microcomputer.
2. Select the disk drive (A :\).
3. Double-click "upsdriv.exe".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters.
2
"ON / OFF conditions" tab
Personalizable function
Automatic start
Cold start (battery power)
Forced shutdown
Sleep mode
UPS ON / OFF via software
Default setting
Enabled
Enabled
Enabled
Disabled
Enabled
Page 22 -
86-153719-00 B00
3. Operation
"Battery" tab
Personalizable function
"Battery test" intervals
Default setting
Every day
"Output" tab
"Low-battery shutdown warning" threshold
Charger
20% remaining battery backup time
Standard
Rated AC-power source voltage (see figure 1)
Rated AC-power source frequency
Tolerance for AC-power source frequency (fig. 2)
Frequency-regulation rate
Alarm threshold for overload
Restart inverter after short circuit
208 V
60 Hz
±
5%
Standard
100%
Disabled
Options
Once a week
Once a month
No test
40% remaining battery backup time
CLA (2, 4 or 8 hours)
200 V-208 V-220 V-240 V
50 Hz
±
1% to
±
10% , in 1% steps
Redundancy (see section 6.1)
0 to 100%, in 10% steps
Enabled (click to add check)
"By-pass" tab
Authorized voltage range for transfer to bypass
(see figure 3) if fault or overload
Authorized frequency range for transfer to bypass
(see figure 2) if fault or overload
Transfer to bypass if overload
Transfer to bypass following a fault, whatever the conditions on the AC-power source
187 V to 265 V (for
208 V rated voltage)
±
10%
Enabled
Disabled
187 V to 265 V, in 1V steps
±
1% to
±
10%, in 1% steps
Disabled (click to remove check)
Enabled (click to add check)
The value selected for the rated UPS voltage impacts on the power available at UPS output
(see the diagram below).
Available power as a percentage of the rated power
Authorized frequency range for transfer to bypass
Tolerance for AC-power
source frequency
Fig. 1
Voltage in V
Fig. 2
Mini Maxi
86-153719-00 B00
- Page 23
3. Operation
3.6 Shutdown
21
The connected equipment is no longer supplied with power.
The battery is no longer recharged.
2
Page 24 -
86-153719-00 B00
4. Maintenance
4.1 Troubleshooting
If a LED flashes, the bargraph data is no longer displayed.
Troubleshooting not requiring MGE after-sales support
Indication
beeps.
beeps.
Signification
UPS overload. Overload is too long or too high. The UPS cuts the supply of power to the connected equipment and the buzzer sounds continuously.
The ambient temperature is higher than
40
°
C.
Correction
Check the power drawn by the equipment and disconnect any non-priority devices.
Install the UPS in a room where the ambient temperature is not greater than 40
°
C.
The UPS is not designed to operate more than eight hours under these conditions.
The UPS is in maintenance mode
(bypass)
UPS electronics have detected a UPS fault.
Depending on the UPS personalization parameters (see section 3.5), there are two possibilities:
◗
the equipment connected to the UPS continues to be supplied, but directly from the AC-power source (via the
Turn the manual bypass switch to "NORMAL" position.
Follow the UPS replacement procedure (see section 4.2).
Call the after-sales support department.
1-800-523-0142
◗
the connected equipment is no longer supplied.
The equipment connected to
the UPS is no longer protected.
A battery fault was detected during the battery test.
Make sure that the battery circuit breaker(s) is closed.If
that is the case, call the aftersales support department because the battery is not OK
86-153719-00 B00
- Page 25
4. Maintenance
4.2 Replacement of the electronic module
Disconnecting the connection module:
Before turning the switch, see the manual to the intermediate position.
NORMAL BY-PASS position.
18
position and call the after-sales support department at 1-800-523-0142.
position to the BYPASS position.
The connected equipment is supplied by the AC-power source, via the manual bypass.
position).
Before turning the switch, see the manual
NORMAL
BY-PASS
21
7. Remove the connection cable(s) from the battery module(s).
The UPS can be replaced. The connected equipment is supplied by the AC-power source.
Reconnecting the connection module:
3. Reconnect the connection cable(s) to the battery module(s).
Check that UPS personalization settings still correspond to the equipment to be supplied
(see section 3.5).
2
intermediate position and call the after-sales support department.
30
8 position to the NORMAL position.
The connected equipment is again protected by the UPS.
Page 26 -
86-153719-00 B00
5. Environment
This product has been designed to respect the environment:
It does not contain CFCs or HCFCs.
It was manufactured in a factory certified ISO 14001.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
Warning:
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not correctly recycled by specialized companies.
Web site : www.mgeups.com
86-153719-00 B00
- Page 27
6. Appendices
6.1 Glossary
Authorized voltage range for transfer to bypass if fault or overload
Automatic bypass
Automatic start following return of AC input power
Backup time
Bargraph
Battery test
Cold start
Connection module
Upper and lower voltage thresholds within which the UPS can operate on the automatic bypass in the event of a UPS fault or overload.
Automatic switch controlled by the UPS, used to connect the equipment directly to the AC-power source.
When AC input power returns following shutdown at the end of the battery backup time, UPS automatic start can be enabled or disabled.
Time that the connected equipment can operate on battery power.
Device on the front panel indicating the percent remaining backup time or the percent load.
Internal UPS test on battery status.
See "Start on battery power".
Unit grouping the receptacles for connection to the AC-power source and the equipment.
Dialog box
Double conversion
A window in a computer program displayed for selection by the user of various options and parameter settings.
The power supplied to the connected equipment is completely regenerated by continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power.
Devices or systems connected to the UPS output.
Equipment
Forced shutdown
Ten-second interruption in the supply of power to the connected equipment following a system shutdown, even if AC input power returns during the interruption period.
Frequency-regulation rate
The rate at which the UPS frequency is synchronized with that of the AC-power source. Two possible cases:
1. The installation comprises a single UPS. The frequency-regulation rate is set to "Standard".
2. The installation comprises two UPSs connected in series. The AC-power source supplies power to the first UPS which in turn supplies the second UPS.
The connected equipment is supplied by the second UPS.
The frequency regulation rate of the first UPS must be set to "Standard", the frequency regulation rate of the second UPS must be set to "Redundancy".
Page 28 -
86-153719-00 B00
6. Appendices
Manual bypass
ON-LINE mode
Percent load
Personalization
Redundancy
Sleep mode
Start on battery power
Tolerance for AC-power source frequency
UPS
UPS ON / OFF via software
Rotary switch controlled by the user, used to connect the equipment directly to the AC-power source. Transfer of the load to the manual bypass enables
UPS maintenance or replacement, without interrupting the supply of power to the connected equipment.
The normal UPS operating mode, by which the AC-power source supplies the UPS, which in turn, following double conversion of the AC power, supplies the connected equipment.
Ratio between the power drawn by the connected equipment and the total power that the UPS can supply.
A number of UPS functions can be modified using the "UPS Driver" software to better meet the user's needs.
See "Frequency-regulation rate".
This function shuts down the UPS when it operates on battery power and no load is detected on the UPS output.
This function makes it possible to energize the connected equipment even when AC input power is not available (operation exclusively on battery power).
The range of frequency supplied by the AC-power source within which the UPS can operate in ON-LINE mode (double conversion).
Uninterruptible Power Supply.
It is possible to enable or disable use of UPS ON / OFF controls by the computer-system protection software.
86-153719-00 B00
- Page 29
6. Appendices
6.2 Index
A
AC power
Failure ........................................................... 21
Frequency tolerance ..................................... 23
Rated frequency ............................................ 23
Rated voltage ................................................ 23
Return ............................................................ 21
B
Bargraph .............................................................. 20
Battery
Battery test .................................................... 23
End of backup time ....................................... 21
Fault ........................................................ 12, 20
Low-battery shutdown warning ..................... 21
Recycling ....................................................... 27
Transfer to battery power .............................. 21
Buzzer .................................................. 6, 12, 20, 21
By-pass
Automatic bypass .................................... 12, 25
Manual bypass ........................................ 12, 26
C
Communication .................................................... 17
Connection
Communications card ................................... 17
Connection modules ..................................... 18
RS 232 communications port ........................ 17
F
Fault (UPS)
Load .............................................................. 12
Transfer to automatic bypass ........................ 25
L
LEDs
Lamp test ....................................................... 12
M
ON-LINE mode ........................................ 12, 19
O
Overload ................................................... 12, 23, 25
P
Personalization ............................................. 22, 23
Battery .......................................................... 23
ON / OFF conditions ..................................... 22
Output ........................................................... 23
R
Rack ...................................................... 9, 10, 13-15
S
Safety .................................................................... 4
Shutdown
Forced shutdown ........................................... 22
UPS ON / OFF via software .......................... 22
UPS shutdown ........................................ 12, 24
Sleep mode .................................................. 21, 22
Software
UPS Driver ................................... 13, 14, 20-23
Start-up
Automatic start .............................................. 22
T
Temperature
Excessive ambient temp .................. 12, 20, 25
U
UPS Driver ......................................... 13, 14, 20-23
Page 30 -
86-153719-00 B00
86-153719-00 B00
- Page 31
MGE UPS SYSTEMS
USA (headquarters)
1660 Scenic Avenue
Costa Mesa, CA 92626 www.mgeups.com
Page 32 -
86-153719-00 B00
N o t h i n g w i l l s t o p y o u n o w
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
Frequently Answers and Questions
What is the normal battery voltage for all models of the MGE UPS Systems Comet EXtreme UPS?
What is the maximum number of modules that can be stacked on top of each other if the UPS is positioned flat?
What should be done if the UPS remains de-energized for a long period?
What are some important safety instructions to follow when using the MGE UPS Systems Comet EXtreme UPS?
What is the function of the ON / OFF conditions tab in the personalization settings?
advertisement
Table of contents
- 12 Control panel
- 13 Unpacking and checks
- 13 "Tower" and "rack" model: 4,5 and 6 kVA
- 13 "Tower" and "rack" model: 9 and 12 kVA
- 14 Installation (rack version)
- 15 Battery-module connections
- 16 Connection to the RS 232 communications port (optional)
- 16 Installation of the communications-card option
- 17 Connection to the connection modules
- 18 Emergency Power Off
- 19 Operating mode
- 19 ON-LINE mode
- 20 Start-up
- 20 Bargraph indications
- 21 Failure of AC input power and operation on battery power
- 21 Transfer to battery power
- 21 Threshold for the low-battery shutdown warning
- 21 End of backup time
- 21 Sleep mode
- 21 Return of AC input power
- 22 Personalization
- 22 Function
- 22 "ON / OFF conditions" tab
- 23 "Battery" tab
- 23 "Output" tab
- 23 "By-pass" tab
- 24 Shutdown
- 25 Troubleshooting
- 26 Replacement of the electronic module
- 28 Glossary
- 30 Index