ADC NGF FOTSB Fiber Optic Terminal Storage Bay User Manual
광고
광고
ADCP-90-270 x Issue 1 x March 2000
NGF Fiber Optic Terminal Storage Bay (FOTSB)
User Manual
)
1070073 Rev A
13987-A
Fiber Optic Terminal Storage Bay
Content Page
GENERAL.......................................................................... 2
PRODUCT DESCRIPTION ............................................................... 2
Functional Description ........................................................... 2
Physical Description ............................................................ 3
INSTALLATION ...................................................................... 3
Securing the Storage Bay to a Frame ................................................. 4
Securing the Storage Bay to an End Guard .............................................. 6
Concrete Floor Mounting.......................................................... 7
Raised Floor Mounting ........................................................... 9
Removing the Bend Radius Limiter...................................................12
Cabling .....................................................................15
CUSTOMER INFORMATION AND ASSISTANCE .................................................17
Page 1
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
Revision History
ISSUE
Issue 1
DATE REASON FOR CHANGE
03/2000 Original
Trademark Information
ADC and ADC Telecommunications are registered trademarks of ADC Telecommunications, Inc.
Next Generation Frame is a registered trademark of ADC Telecommunications, Inc.
Admonishments
Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided. The admonishments — in the form of Dangers,
Warnings, and Cautions — must be followed at all times. These warnings are flagged by use of the triangular alert icon (seen below), and are listed in descending order of severity of injury or damage and likelihood of occurrence.
Danger
: Danger is used to indicate the presence of a hazard that will cause severe personal
injury, death, or substantial property damage if the hazard is not avoided.
Warning
: Warning is used to indicate the presence of a hazard that can cause severe
personal injury, death, or substantial property damage if the hazard is not avoided.
Caution
: Caution is used to indicate the presence of a hazard that will or can cause minor
personal injury or property damage if the hazard is not avoided.
1 GENERAL
This user manual describes the function and installation procedures for the ADC NGF Fiber
Optic Terminal Storage Bay.
The Next Generation Frame (NGF) Fiber Optic Terminal Storage Bay (FOTSB) is used as a storage apparatus for up to 16.4 feet (5 meters) of equipment (FOT) jumpers at the fiber frame lineup. The FOTSB can be installed between fiber frames within a lineup or between a fiber frame and an end guard at the end of a lineup.
Page 2
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
ADDITIONAL
FRAME OR
END GUARD
13988-A
FMDF FRAME
SECTION
FOT STORAGE BAY
Figure 1. Positioning of the Storage Bay within a Fiber Frame Lineup
The FOTSB is 7 feet high and 12 inches wide and is available for use with either the 24-inchdeep Fiber Main Distribution Frame (FMDF) or the 19-inch-deep Front Facing FMDF. The storage bay has vertical cable guides and spools for cable slack storage.
3 INSTALLATION
Warning
: Never install equipment in a wet location or during a lightning storm.
Installation of the storage bay is accomplished by securing the FOTSB to a frame or end guard within a frame lineup. Alternately, the bay can be secured to either a concrete or raised floor.
When attached to a frame, junction plates/spacer brackets are used. When attaching to an end guard, “L” mounting brackets are used.
Page 3
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
13044-A
Figure 2. Securing a Junction Plate/Spacer Bracket
3.1 Securing the Storage Bay to a Frame
Using the junction plates/spacer brackets, install the FOTSB as follows:
1. Align the holes in the junction plate/spacer bracket with the mounting holes in the storage bay ( Figure 2 ) and attach using two (2) #12-24 screws (provided). Repeat this step for each of the three sets of holes on this side of the bay. The mounting hole
locations are shown in Figure 3 .
Note
: Attaching a junction plate/spacer bracket in the lowest set of mounting holes is optional. The bay will be adequately secured using the upper and middle mounting holes only.
Note
: To access the lowest of the three sets of holes on the storage bay, it may be necessary to remove the rear kick plate. To do so, remove the four screws that secure the kick plate to the bay and replace after installing the bay to the frame.
2. Move the storage bay into position within the frame lineup.
3. Position the storage bay so that the empty holes in the junction plates are aligned with the mounting holes in the frame. Attach using two (2) #12-24 screws (provided) for each of the junction plates.
4. Repeat this process to secure the storage bay to a frame on the opposite side.
Page 4
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
13045-A
REMOVE KICK PLATE
Figure 3. Junction Plate Mounting Hole Locations
Page 5
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
3.2 Securing the Storage Bay to an End Guard
Using the “L” mounting brackets, install the FOTSB as follows:
1. Remove the front and rear kick plates on the FOTSB.
2. Secure the mounting brackets (supplied with the end guard) to the storage bay using the
1
/
4
" bolts, lock washers, and nuts as shown in Figure 4 .
3. Slide the end guard into position and secure the protruding edges of the mounting brackets to the end guard using the #12-24 screws (provided).
1/4" BOLT
MOUNTING BRACKET
Page 6
© 2000, ADC Telecommunications, Inc.
#12-24 SCREWS
Figure 4. Attaching an End Guard to the FOTSB
END GUARD
13046-A
ADCP-90-270 x Issue 1 x March 2000
3.3 Concrete Floor Mounting
Ensure the appropriate hardware is available for concrete floor mounting. Typically four anchors are used when the FOTSB is floor supported. The anchor has a torque nut with a breakaway cap that breaks away when tightened to the proper torque pressure. Anchor the rack to the floor using the following procedures.
1. Position the bay in its designated floor location.
2. Mark the mounting hole locations on the floor. Use the holes with the widest spacing to provide the greatest stability. See Figure 5 .
Note
: To achieve maximum anchor-holding strength, select exact drill size for hole drilling.
3. Move the bay aside. At each mounting hole location, drill an 18 mm (.07 inch) diameter hole to a depth of 80 mm (3.15 inches) in the concrete. Clean out the hole with compressed air. Check the hole depth with a tape measure or by placing the assembled anchor bolts in each hole. If a reinforcing bar is encountered while drilling, relocate the hole. Fill the unusable hole with locally approved filling product.
FRONT
13989-A
Figure 5. FOTSB Base Mounting Hole Pattern
4. Ready a floor anchor by placing the components on the stud in the order shown in Figure 6 .
Ensure that the stud is not extending beyond the bottom of the wedge. Insert the anchor into any of the mounting holes just drilled and tap it in with a hammer until the shoulder of the anchor is just even with the floor.
Page 7
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
BREAKAWAY
CAP
PLASTIC-
ENCLOSED
TORQUE
NUT
STUD
NOTE:
FOR FUTURE REMOVAL OF
TORQUE NUT AND/OR THREADED
ROD, USE A SCREWDRIVER TO
SNAP OFF THE PLASTIC COVER
EXPOSING THE TORQUE NUT.
ALWAYS REPLACE NUT WITH A
NEW TORQUE NUT.
WASHER
SHOULDER
PLASTIC
COVER
TORQUE
NUT
DISCARD
BREAKAWAY
CAP WEDGE
8013-C
Figure 6. Floor Anchor
5. Using a deep socket or box-end wrench, secure the anchor in the floor by tightening the torque nut breakaway cap until it just starts to feel snug. (Do not tighten until the breakaway cap breaks away from the plastic-enclosed torque nut.) Remove the washer, plastic-enclosed torque nut, and attached breakaway cap from the stud.
6. Repeat steps 4 and 5 above for each of the remaining floor anchors to secure them in the remaining mounting hole locations. Depending on the type of installation, you will have either two or four anchors to install.
7. After securing all the anchors in the floor as just described, position the storage bay over
the anchors. Level the bay using shim plates, if necessary, as shown in Figure 7
.
Page 8
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
HOLD
DOWN
BAR
PLASTIC-ENCLOSED
TORQUE NUT WITH
BREAKAWAY CAP
WASHER
STORAGE
BAY
BASE
SQUARE
WASHERS
HOLD DOWN
PLATES AND
SQUARE WASHERS
STORAGE BAY BASE
SHIM AS
REQUIRED
SHIM AS
REQUIRED
FLOOR LINE
13990-A
Figure 7. Shim and Hold Down Bars
8. Place a hold down bar and one or two square washers, as required, on each stud. Replace the flat washers and torque nuts removed in the previous steps. Tighten each torque nut until the breakaway cap breaks away, indicating that the anchor is properly set. Discard the breakaway caps.
3.4 Raised Floor Mounting
Various methods are used to mount equipment racks/bays to a raised floor. The method described here uses mounting hardware available in a kit from ADC. For other methods,
follow the instructions provided with that equipment. Table 1 lists the ADC kit contents. The
length of threaded rod required will depend on the raised floor height above the regular floor.
Page 9
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
Table 1. Raised Floor Mounting Kit (FDF-ACC136) Contents
ITEM
Unistrut (feet)
Flat washer – 0.625 in. (16 mm)
Lock washer – 0.50 in. (12.7 mm)
Threaded rod 1/2–13 u 30 in. (76 cm)
Insulating shoulder washer
Anchor kit
Flat washer – 0.50 in. (12.7 mm)
Hex nut (1/2–13)
Spring nuts – (1/2–13)
# = Optional
QUANTITY
4#
1
12
12
4
10
12
12
4
Ensure the appropriate hardware is available to satisfy raised floor mounting requirements. The following procedures cover a single storage bay placement. If more bays/racks in a line-up are being placed, the Unistrut lengths and positions of anchors in the lower floor must be adjusted accordingly. The anchor placed in the concrete floor is designed with a threaded stud and torque nut with a cap that will break away when tightened to the proper torque pressure. Prepare the raised floor support and anchoring hardware using the following procedures.
1. Position the storage bay in its designated floor location. Mark the mounting holes as
shown on the equipment rack footprint. See Figure 8 .
2. Move the bay aside. Drill four 16 mm (0.625 inch) clearance holes in the raised floor panel(s).
3. Remove any adjacent floor panels as needed to gain access to the lower floor.
4. Mark the lower floor in line with the holes in the raised floor panels. Use a plumb line or
equivalent for an accurate mark. See Figure 8 .
5. Draw an extended line through the centers of the mounting hole marks.
6. Cut two pieces of Unistrut into 36.0 inch (91.4 cm) lengths. Drill two 16 mm (0.625 inch) holes located 6.0 inches (15.2 cm) from each end.
7. Place the Unistrut on the lines made in step 5. Center along the line and mark the floor for the Unistrut anchor holes. Move the Unistrut out of the way for now.
8. Drill an 18 mm (.07 inch) diameter hole to a depth of 3.15 inches (80 mm) in the concrete at the marks made in step 7. Clean out the hole with compressed air. Check the hole depth with a tape measure or by placing an assembled anchor in each hole. If a reinforcing bar is encountered while drilling, relocate the hole. Fill the unusable hole with locally approved filling product.
9. Insert the anchors into each hole. Check that each anchor shoulder is even with the floor.
Use a deep socket or box-end wrench and tighten the torque nut until the anchor is just snug. Do not tighten until the torque nut cap breaks way. Repeat for each anchor. Refer
.
Page 10
© 2000, ADC Telecommunications, Inc.
MARK
HERE
EQUIPMENT
RACK
FOOTPRINT
ADCP-90-270 x Issue 1 x March 2000
RAISED
FLOOR
PANEL
CONCRETE
FLOOR
EXTENDED
CENTER LINE
UNISTRUT
ANCHOR
HOLE
UNISTRUT
ANCHOR
HOLE
RACK MOUNTING
REFERENCE
HOLES
14003-A
Figure 8. Rack Mounting Hole Markings
10. Remove the nut and washer from the studs. Position the Unistrut over the studs. Replace the flat washer and torque nut onto the stud. Tighten the torque nut until the torque cap breaks away, indicating the anchor is properly set. Discard the break-away portion of the torque nut. Repeat for each anchor.
11. Insert spring-nuts into the Unistrut, aligning them with marks on the floor made in step 4.
12. Replace as many floor panels as possible while still allowing access to the lower floor.
Position the equipment rack over the clearance holes in the floor panel.
13. Cut two lengths of Unistrut approximately 12.0 inches (30.5 cm) long. Mark the Unistrut at the hole positions of the raised floor made in step 2. Drill two 16 mm (0.625 inch) holes in the Unistrut.
14. Measure from the lower floor to the base of the equipment rack allowing sufficient length for leveling shims, hold down bar, washers, and nuts.
15. Place onto one end of the threaded rods, in order: 5/8-inch (16 mm) flat washer, 1/2-inch
(12.7 mm) flat washer, 1/2-inch (12.7 mm) lock washer, two - 1/2-inch (12.7 mm) hex nuts, 1/2-inch (12.7 mm) lock washer, 1/2-inch (12.7 mm) flat washer, 5/8-inch (16 mm) flat washer. On top of the pile up, place the shorter length Unistrut over the threaded rods.
You may find it easier to have someone hold the Unistrut beneath the raised floor panel for
Page 11
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
EQUIPMENT
RACK BASE
(FRONT)
5/8 IN. FLAT WASHER
1/2 IN. FLAT WASHER
1/2 IN. LOCK WASHER
1/2 IN. HEX NUT
SPRING
NUT
1/2 IN. HEX NUT
1/2 IN. LOCK WASHER
1/2 IN. FLAT WASHER
NYLON SHOULDER WASHER
HOLD DOWN BAR
SHIM AS
REQUIRED
RAISED
FLOOR PANEL
UNISTRUT
1/2 IN. THREADED ROD
ANCHOR
ASSEMBLY
UNISTRUT
;;; ;;
CONCRETE
FLOOR
8599-A
Figure 9. Typical Raised Floor Anchor Arrangement
;;; ;;
16. Hold the above arrangement in place while inserting the threaded rod up through the floor panel from below, up into the equipment rack base. Thread the rod down into the floor Unistrut spring nuts, then hand-tighten the lower hex nut. Repeat for each rod.
17. Thread the upper hex nut upward until the shorter Unistrut touches the bottom of the raised floor panel.
18. Place onto the upper end of the threaded rod (rack base end) the following items: 5/8-inch
(16 mm) flat washer, 1/2-inch (12.7 mm) flat washer, 1/2-inch (12.7 mm) lock washer, and 1/2-inch (12.7 mm) hex nut.
19. Align the equipment rack and tighten securely. Start with the floor Unistrut, then the
Unistrut under the raised floor and last the rack base.
3.5 Removing the Bend Radius Limiter
Removal of the bend radius limiters is recommended when using the FOTSB with a Next
Generation Frame that contains OSP cable. Removal of the radius limiters opens the vertical cable guides, which allows easier routing of OSP cable.
Perform the following procedure to remove the radius limiters:
1. Remove the two mounting screws that secure the vertical cable guide to the bay (
).
Set the screws aside.
Page 12
© 2000, ADC Telecommunications, Inc.
ADCP-90-270
• Issue 1 • March 2000
13715-A
MOUNTING SCREWS
Figure 10. Vertical Cable Guide Mounting Screws
2. Remove the assembly from the bay ( Figure 11 ).
13712-A
Figure 11. Removing the Vertical Cable Guide/Radius Limiter Assembly
Page 13
© 2000, ADC Telecommunications, Inc.
ADCP-90-270
• Issue 1 • March 2000
3. Place the removed vertical/limiter assembly on a stable surface and remove the two mounting screws that secure the bend radius limiter to the vertical cable guide ( Figure 12 ).
MOUNTING SCREWS
13713-A
MOUNTING HOLES
Figure 12. Bend Radius Limiter Mounting Screws
4. Remove bend radius limiter ( Figure 13 ).
13714-A
Figure 13. Removal of the Bend Radius Limiter
5. Reattach the vertical cable guide to the bay using the mounting screws removed in step 1.
Page 14
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
3.6 Cabling
Figure 14 shows the recommended routing of FOT jumpers when dropping from overhead.
Note
: To maintain cable integrity, do not store more than 16.4 feet (5 meters) of cable per storage bay.
FOT OSP OSP OSP OSP FOT
FOT
STORAGE
BAY
BAY 1 BAY 2
Figure 14. FOT Overhead Jumper Routing
BAY 3 FOT
STORAGE
BAY
13666-A
Page 15
© 2000, ADC Telecommunications, Inc.
ADCP-90-270 x Issue 1 x March 2000
3.6.2 Raised Floor Cabling
Figure 15 shows the recommended routing of FOT jumpers when bringing the cable up through a raised floor.
Note
: To maintain cable integrity, do not store more than 16.4 feet (5 meters) of cable per storage bay.
FOT
STORAGE
BAY
FOT
BAY 1
OSP OSP
BAY 2
OSP OSP
BAY 3
FOT
FOT
STORAGE
BAY
Page 16
© 2000, ADC Telecommunications, Inc.
Figure 15. FOT Raised Floor Jumper Routing
13991-A
ADCP-90-270 x Issue 1 x March 2000
4 CUSTOMER INFORMATION AND ASSISTANCE
For customers wanting information on ADC products or help in using them, ADC offers the services listed below. To obtain any of these services by telephone, first dial the central ADC telephone number, then dial the extension provided below.
The central number for calls originating in the U.S.A. or Canada is 1-800-366-3891. For calls originating outside the U.S.A. or Canada, dial country code “1” then dial 952-946-3000.
Sales Assistance
Extension 3000
Systems Integration
Extension 3000
BCG Technical Assistance Center
Extension 3475
E-Mail: [email protected]
Product Return Department
Extension 3748
E-Mail: repair&[email protected]
• Quotation Proposals
• Ordering and Delivery
• General Product Information
• Complete Solutions (from Concept to Installation)
• Network Design and Integration Testing
• System Turn-Up and Testing
• Network Monitoring (Upstream or Downstream)
• Power Monitoring and Remote Surveillance
• Service/Maintenance Agreements
• Systems Operation
• Technical Information
• System/Network Configuration
• Product Specification and Application
• Training (Product-Specific)
• Installation and Operation Assistance
• Troubleshooting and Repair
• ADC Return Authorization number and instructions must be obtained before returning products.
Product information may also be obtained using the ADC web site at www.adc.com or by writing ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A.
Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice. In
no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages. This disclaimer of liability applies to all products, publications and services during and after the warranty period.
This publication may be verified at any time by contacting ADC’s Technical Assistance Center at 1-800-366-3891, extension
3475 (in U.S.A. or Canada) or 952-946-3000 (outside U.S.A. and Canada), or by writing to ADC Telecommunications, Inc.,
Attn: Technical Assistance Center, Mail Station #71, P.O. Box 1101, Minneapolis, MN 55440-1101, U.S.A.
© 2000, ADC Telecommunications, Inc.
All Rights Reserved
Printed in U.S.A.