Juniper JCS 1200 Hardware manual
Iklan
Iklan
Juniper Control System (JCS) 1200 Platform
Hardware Guide
Juniper Networks, Inc.
1194 North Mathilda Avenue
Sunnyvale, California 94089
USA
408-745-2000
www.juniper.net
Part Number: 530-023226-01, Revision 4
This product includes the Envoy SNMP Engine, developed by Epilogue Technology, an Integrated Systems Company. Copyright © 1986-1997, Epilogue
Technology Corporation. All rights reserved. This program and its documentation were developed at private expense, and no part of them is in the public domain.
This product includes memory allocation software developed by Mark Moraes, copyright © 1988, 1989, 1993, University of Toronto.
This product includes FreeBSD software developed by the University of California, Berkeley, and its contributors. All of the documentation and software included in the 4.4BSD and 4.4BSD-Lite Releases is copyrighted by the Regents of the University of California. Copyright © 1979, 1980, 1983, 1986, 1988,
1989, 1991, 1992, 1993, 1994. The Regents of the University of California. All rights reserved.
GateD software copyright © 1995, the Regents of the University. All rights reserved. Gate Daemon was originated and developed through release 3.0 by
Cornell University and its collaborators. Gated is based on Kirton’s EGP, UC Berkeley’s routing daemon (routed), and DCN’s HELLO routing protocol.
Development of Gated has been supported in part by the National Science Foundation. Portions of the GateD software copyright © 1988, Regents of the
University of California. All rights reserved. Portions of the GateD software copyright © 1991, D. L. S. Associates.
This product includes software developed by Maker Communications, Inc., copyright © 1996, 1997, Maker Communications, Inc.
Juniper Networks, the Juniper Networks logo, JUNOS, NetScreen, ScreenOS, and Steel-Belted Radius are registered trademarks of Juniper Networks, Inc. in the United States and other countries. JUNOSe is a trademark of Juniper Networks, Inc. All other trademarks, service marks, registered trademarks, or registered service marks are the property of their respective owners.
Juniper Networks assumes no responsibility for any inaccuracies in this document. Juniper Networks reserves the right to change, modify, transfer, or otherwise revise this publication without notice.
Products made or sold by Juniper Networks or components thereof might be covered by one or more of the following patents that are owned by or licensed to Juniper Networks: U.S. Patent Nos. 5,473,599, 5,905,725, 5,909,440, 6,192,051, 6,333,650, 6,359,479, 6,406,312, 6,429,706, 6,459,579, 6,493,347,
6,538,518, 6,538,899, 6,552,918, 6,567,902, 6,578,186, and 6,590,785.
Juniper Control System (JCS) 1200 Hardware Guide
Copyright © 2008, Juniper Networks, Inc.
All rights reserved. Printed in USA.
Writing: Charissa Fleischer
Editing: Fran Mues
Illustration: Faith Bradford Brown
Cover Design: Edmonds Design
Revision History
27 October 2008—530-023226-01. Revision 4. Populated related topics.
8 August 2008—530-023226-01. Revision 3. Updated power consumption information for AC and DC platforms.
28 July 2008—530-023226-01. Revision 2. Added information about connecting multiple T-series routing platforms to the JCS 1200 platform. Revised procedures for replacing the midplane and interposers.
18 April 2008—530-023226-01. Revision 1. Initial release.
The information in this document is current as of the date listed in the revision history.
YEAR 2000 NOTICE
Juniper Networks hardware and software products are Year 2000 compliant. The JUNOS software has no known time-related limitations through the year
2038. However, the NTP application is known to have some difficulty in the year 2036.
ii ■
END USER LICENSE AGREEMENT
READ THIS END USER LICENSE AGREEMENT (“AGREEMENT”) BEFORE DOWNLOADING, INSTALLING, OR USING THE SOFTWARE. BY DOWNLOADING,
INSTALLING, OR USING THE SOFTWARE OR OTHERWISE EXPRESSING YOUR AGREEMENT TO THE TERMS CONTAINED HEREIN, YOU (AS CUSTOMER
OR IF YOU ARE NOT THE CUSTOMER, AS A REPRESENTATIVE/AGENT AUTHORIZED TO BIND THE CUSTOMER) CONSENT TO BE BOUND BY THIS
AGREEMENT. IF YOU DO NOT OR CANNOT AGREE TO THE TERMS CONTAINED HEREIN, THEN (A) DO NOT DOWNLOAD, INSTALL, OR USE THE SOFTWARE,
AND (B) YOU MAY CONTACT JUNIPER NETWORKS REGARDING LICENSE TERMS.
1. The Parties. The parties to this Agreement are (i) Juniper Networks, Inc. (if the Customer’s principal office is located in the Americas) or Juniper Networks
(Cayman) Limited (if the Customer’s principal office is located outside the Americas) (such applicable entity being referred to herein as “Juniper”), and (ii) the person or organization that originally purchased from Juniper or an authorized Juniper reseller the applicable license(s) for use of the Software (“Customer”)
(collectively, the “Parties”).
2. The Software. In this Agreement, “Software” means the program modules and features of the Juniper or Juniper-supplied software, for which Customer has paid the applicable license or support fees to Juniper or an authorized Juniper reseller, or which was embedded by Juniper in equipment which Customer purchased from Juniper or an authorized Juniper reseller. “Software” also includes updates, upgrades and new releases of such software. “Embedded
Software” means Software which Juniper has embedded in or loaded onto the Juniper equipment and any updates, upgrades, additions or replacements which are subsequently embedded in or loaded onto the equipment.
3. License Grant. Subject to payment of the applicable fees and the limitations and restrictions set forth herein, Juniper grants to Customer a non-exclusive and non-transferable license, without right to sublicense, to use the Software, in executable form only, subject to the following use restrictions: a. Customer shall use Embedded Software solely as embedded in, and for execution on, Juniper equipment originally purchased by Customer from Juniper or an authorized Juniper reseller.
b. Customer shall use the Software on a single hardware chassis having a single processing unit, or as many chassis or processing units for which Customer has paid the applicable license fees; provided, however, with respect to the Steel-Belted Radius or Odyssey Access Client software only, Customer shall use such Software on a single computer containing a single physical random access memory space and containing any number of processors. Use of the
Steel-Belted Radius or IMS AAA software on multiple computers or virtual machines (e.g., Solaris zones) requires multiple licenses, regardless of whether such computers or virtualizations are physically contained on a single chassis.
c. Product purchase documents, paper or electronic user documentation, and/or the particular licenses purchased by Customer may specify limits to
Customer’s use of the Software. Such limits may restrict use to a maximum number of seats, registered endpoints, concurrent users, sessions, calls, connections, subscribers, clusters, nodes, realms, devices, links, ports or transactions, or require the purchase of separate licenses to use particular features, functionalities, services, applications, operations, or capabilities, or provide throughput, performance, configuration, bandwidth, interface, processing, temporal, or geographical limits. In addition, such limits may restrict the use of the Software to managing certain kinds of networks or require the Software to be used only in conjunction with other specific Software. Customer’s use of the Software shall be subject to all such limitations and purchase of all applicable licenses.
d. For any trial copy of the Software, Customer’s right to use the Software expires 30 days after download, installation or use of the Software. Customer may operate the Software after the 30-day trial period only if Customer pays for a license to do so. Customer may not extend or create an additional trial period by re-installing the Software after the 30-day trial period.
e. The Global Enterprise Edition of the Steel-Belted Radius software may be used by Customer only to manage access to Customer’s enterprise network.
Specifically, service provider customers are expressly prohibited from using the Global Enterprise Edition of the Steel-Belted Radius software to support any commercial network access services.
The foregoing license is not transferable or assignable by Customer. No license is granted herein to any user who did not originally purchase the applicable license(s) for the Software from Juniper or an authorized Juniper reseller.
4. Use Prohibitions. Notwithstanding the foregoing, the license provided herein does not permit the Customer to, and Customer agrees not to and shall not: (a) modify, unbundle, reverse engineer, or create derivative works based on the Software; (b) make unauthorized copies of the Software (except as necessary for backup purposes); (c) rent, sell, transfer, or grant any rights in and to any copy of the Software, in any form, to any third party; (d) remove any proprietary notices, labels, or marks on or in any copy of the Software or any product in which the Software is embedded; (e) distribute any copy of the Software to any third party, including as may be embedded in Juniper equipment sold in the secondhand market; (f) use any ‘locked’ or key-restricted feature, function, service, application, operation, or capability without first purchasing the applicable license(s) and obtaining a valid key from Juniper, even if such feature, function, service, application, operation, or capability is enabled without a key; (g) distribute any key for the Software provided by Juniper to any third party; (h) use the Software in any manner that extends or is broader than the uses purchased by Customer from Juniper or an authorized Juniper reseller; (i) use Embedded Software on non-Juniper equipment; (j) use Embedded Software (or make it available for use) on Juniper equipment that the
Customer did not originally purchase from Juniper or an authorized Juniper reseller; (k) disclose the results of testing or benchmarking of the Software to any third party without the prior written consent of Juniper; or (l) use the Software in any manner other than as expressly provided herein.
5. Audit. Customer shall maintain accurate records as necessary to verify compliance with this Agreement. Upon request by Juniper, Customer shall furnish such records to Juniper and certify its compliance with this Agreement.
■ iii
6. Confidentiality. The Parties agree that aspects of the Software and associated documentation are the confidential property of Juniper. As such, Customer shall exercise all reasonable commercial efforts to maintain the Software and associated documentation in confidence, which at a minimum includes restricting access to the Software to Customer employees and contractors having a need to use the Software for Customer’s internal business purposes.
7. Ownership. Juniper and Juniper’s licensors, respectively, retain ownership of all right, title, and interest (including copyright) in and to the Software, associated documentation, and all copies of the Software. Nothing in this Agreement constitutes a transfer or conveyance of any right, title, or interest in the Software or associated documentation, or a sale of the Software, associated documentation, or copies of the Software.
8. Warranty, Limitation of Liability, Disclaimer of Warranty. The warranty applicable to the Software shall be as set forth in the warranty statement that accompanies the Software (the “Warranty Statement”). Nothing in this Agreement shall give rise to any obligation to support the Software. Support services may be purchased separately. Any such support shall be governed by a separate, written support services agreement. TO THE MAXIMUM EXTENT PERMITTED
BY LAW, JUNIPER SHALL NOT BE LIABLE FOR ANY LOST PROFITS, LOSS OF DATA, OR COSTS OR PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES,
OR FOR ANY SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES ARISING OUT OF THIS AGREEMENT, THE SOFTWARE, OR ANY JUNIPER OR
JUNIPER-SUPPLIED SOFTWARE. IN NO EVENT SHALL JUNIPER BE LIABLE FOR DAMAGES ARISING FROM UNAUTHORIZED OR IMPROPER USE OF ANY
JUNIPER OR JUNIPER-SUPPLIED SOFTWARE. EXCEPT AS EXPRESSLY PROVIDED IN THE WARRANTY STATEMENT TO THE EXTENT PERMITTED BY LAW,
JUNIPER DISCLAIMS ANY AND ALL WARRANTIES IN AND TO THE SOFTWARE (WHETHER EXPRESS, IMPLIED, STATUTORY, OR OTHERWISE), INCLUDING
ANY IMPLIED WARRANTY OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, OR NONINFRINGEMENT. IN NO EVENT DOES JUNIPER
WARRANT THAT THE SOFTWARE, OR ANY EQUIPMENT OR NETWORK RUNNING THE SOFTWARE, WILL OPERATE WITHOUT ERROR OR INTERRUPTION,
OR WILL BE FREE OF VULNERABILITY TO INTRUSION OR ATTACK. In no event shall Juniper’s or its suppliers’ or licensors’ liability to Customer, whether in contract, tort (including negligence), breach of warranty, or otherwise, exceed the price paid by Customer for the Software that gave rise to the claim, or if the Software is embedded in another Juniper product, the price paid by Customer for such other product. Customer acknowledges and agrees that Juniper has set its prices and entered into this Agreement in reliance upon the disclaimers of warranty and the limitations of liability set forth herein, that the same reflect an allocation of risk between the Parties (including the risk that a contract remedy may fail of its essential purpose and cause consequential loss), and that the same form an essential basis of the bargain between the Parties.
9. Termination. Any breach of this Agreement or failure by Customer to pay any applicable fees due shall result in automatic termination of the license granted herein. Upon such termination, Customer shall destroy or return to Juniper all copies of the Software and related documentation in Customer’s possession or control.
10. Taxes. All license fees payable under this agreement are exclusive of tax. Customer shall be responsible for paying Taxes arising from the purchase of the license, or importation or use of the Software. If applicable, valid exemption documentation for each taxing jurisdiction shall be provided to Juniper prior to invoicing, and Customer shall promptly notify Juniper if their exemption is revoked or modified. All payments made by Customer shall be net of any applicable withholding tax. Customer will provide reasonable assistance to Juniper in connection with such withholding taxes by promptly: providing Juniper with valid tax receipts and other required documentation showing Customer’s payment of any withholding taxes; completing appropriate applications that would reduce the amount of withholding tax to be paid; and notifying and assisting Juniper in any audit or tax proceeding related to transactions hereunder.
Customer shall comply with all applicable tax laws and regulations, and Customer will promptly pay or reimburse Juniper for all costs and damages related to any liability incurred by Juniper as a result of Customer’s non-compliance or delay with its responsibilities herein. Customer’s obligations under this
Section shall survive termination or expiration of this Agreement.
11. Export. Customer agrees to comply with all applicable export laws and restrictions and regulations of any United States and any applicable foreign agency or authority, and not to export or re-export the Software or any direct product thereof in violation of any such restrictions, laws or regulations, or without all necessary approvals. Customer shall be liable for any such violations. The version of the Software supplied to Customer may contain encryption or other capabilities restricting Customer’s ability to export the Software without an export license.
12. Commercial Computer Software. The Software is “commercial computer software” and is provided with restricted rights. Use, duplication, or disclosure by the United States government is subject to restrictions set forth in this Agreement and as provided in DFARS 227.7201 through 227.7202-4, FAR 12.212,
FAR 27.405(b)(2), FAR 52.227-19, or FAR 52.227-14(ALT III) as applicable.
13. Interface Information. To the extent required by applicable law, and at Customer's written request, Juniper shall provide Customer with the interface information needed to achieve interoperability between the Software and another independently created program, on payment of applicable fee, if any.
Customer shall observe strict obligations of confidentiality with respect to such information and shall use such information in compliance with any applicable terms and conditions upon which Juniper makes such information available.
14. Third Party Software. Any licensor of Juniper whose software is embedded in the Software and any supplier of Juniper whose products or technology are embedded in (or services are accessed by) the Software shall be a third party beneficiary with respect to this Agreement, and such licensor or vendor shall have the right to enforce this Agreement in its own name as if it were Juniper. In addition, certain third party software may be provided with the
Software and is subject to the accompanying license(s), if any, of its respective owner(s). To the extent portions of the Software are distributed under and subject to open source licenses obligating Juniper to make the source code for such portions publicly available (such as the GNU General Public License
(“GPL”) or the GNU Library General Public License (“LGPL”)), Juniper will make such source code portions (including Juniper modifications, as appropriate) available upon request for a period of up to three years from the date of distribution. Such request can be made in writing to Juniper Networks, Inc., 1194
N. Mathilda Ave., Sunnyvale, CA 94089, ATTN: General Counsel. You may obtain a copy of the GPL at http://www.gnu.org/licenses/gpl.html
, and a copy of the LGPL at http://www.gnu.org/licenses/lgpl.html
.
15. Miscellaneous. This Agreement shall be governed by the laws of the State of California without reference to its conflicts of laws principles. The provisions of the U.N. Convention for the International Sale of Goods shall not apply to this Agreement. For any disputes arising under this Agreement, the Parties hereby consent to the personal and exclusive jurisdiction of, and venue in, the state and federal courts within Santa Clara County, California. This Agreement constitutes the entire and sole agreement between Juniper and the Customer with respect to the Software, and supersedes all prior and contemporaneous iv ■
agreements relating to the Software, whether oral or written (including any inconsistent terms contained in a purchase order), except that the terms of a separate written agreement executed by an authorized Juniper representative and Customer shall govern to the extent such terms are inconsistent or conflict with terms contained herein. No modification to this Agreement nor any waiver of any rights hereunder shall be effective unless expressly assented to in writing by the party to be charged. If any portion of this Agreement is held invalid, the Parties agree that such invalidity shall not affect the validity of the remainder of this Agreement. This Agreement and associated documentation has been written in the English language, and the Parties agree that the English version will govern. (For Canada: Les parties aux présentés confirment leur volonté que cette convention de même que tous les documents y compris tout avis qui s'y rattaché, soient redigés en langue anglaise. (Translation: The parties confirm that this Agreement and all related documentation is and will be in the English language)).
■ v
vi ■
Table of Contents
Part 1
Product Overview
JCS 1200 Platform Features and Specifications ...............................................7
Major Components of the JCS 1200 Platform ..................................................9
JCS 1200 Alarm Panel Module Overview .......................................................12
JCS 1200 Alarm Panel Module Description ..............................................12
JCS 1200 Alarm Panel Module Connectors and LEDs ..............................12
JCS 1200 Fan Module Overview ....................................................................14
JCS 1200 Fan Module Description ...........................................................14
JCS 1200 Fan Module LED ......................................................................14
JCS 1200 Management Module Overview ......................................................15
JCS 1200 Management Module Description ............................................15
JCS 1200 Management Module Connectors and LEDs .............................16
JCS 1200 Media Tray Overview .....................................................................18
JCS 1200 Media Tray Description ............................................................18
JCS 1200 Media Tray Connectors and LEDs ............................................19
JCS 1200 MUX Card Overview .......................................................................20
JCS 1200 MUX Card Description .............................................................21
JCS 1200 MUX Card LEDs .......................................................................21
JCS 1200 Power Module Overview ................................................................22
JCS 1200 Power Module Description .......................................................22
JCS 1200 Power Module LEDs .................................................................23
Table of Contents
■ vii
Juniper Control System (JCS) 1200 Platform Hardware Guide
Part 2
JCS 1200 Routing Engine Overview ...............................................................24
JCS 1200 Routing Engine Description .....................................................24
JCS 1200 Routing Engine Control Panel Buttons and LEDs .....................25
JCS 1200 Switch Module Overview ................................................................27
JCS 1200 Switch Module Description ......................................................27
JCS 1200 Switch Module Components and LEDs ....................................27
Initial Installation
Preparing the Site for JCS 1200 Platform Installation 33
Overview of Preparing the Site for JCS 1200 Platform Installation .................33
Site Preparation Checklist for the JCS 1200 Platform .....................................33
JCS 1200 Cabinet Requirements ....................................................................34
JCS 1200 Cabinet Size and Clearance Requirements ...............................34
JCS 1200 Cabinet Airflow Requirements .................................................35
JCS 1200 Rack Size and Strength ............................................................36
JCS 1200 Connection to Building Structure .............................................37
JCS 1200 Clearance Requirements for Airflow and Hardware
Unpacking the JCS 1200 Platform 39
Tools and Parts Required to Unpack the JCS 1200 Platform ..........................39
Unpacking the JCS 1200 Platform .................................................................40
Verifying Parts Received for the JCS 1200 Platform .......................................41
Installing the JCS 1200 Mounting Hardware 43
JCS 1200 Platform Rack-Mounting Hardware ................................................43
Rack Mounting Hole Locations for the JCS 1200 Platform .............................43
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack ...........46
viii ■
Table of Contents
Table of Contents
Installing the JCS 1200 Platform 49
Safety Requirements, Warnings, and Guidelines for Installing the JCS 1200
Installing the JCS 1200 Platform Using a Mechanical Lift ...............................51
Tools Required to Install the JCS 1200 Platform Using a Mechanical
Installing the JCS 1200 Platform Using a Lift ...........................................51
Installing the JCS 1200 Platform in a Rack Without a Lift ..............................54
Tools and Parts Required to Install the JCS 1200 Platform Without a
Mechanical Lift .................................................................................55
Removing Components from the JCS 1200 Platform ..............................55
Lifting the JCS 1200 Platform into the Rack or Cabinet ...........................56
Reinstalling Components into the JCS 1200 Platform ..............................57
Connecting the JCS 1200 Platform 59
Before you Begin Connecting the JCS 1200 Platform .....................................59
Tools and Parts Required for Connecting the JCS 1200 Platform ...................60
Supplying Power to the JCS 1200 Platform ....................................................60
JCS 1200 Platform Power Overview ........................................................61
Connecting the JCS 1200 AC Platform to AC Power ................................62
Connecting the JCS 1200 DC Platform to DC Power ...............................63
Disconnecting Power from the JCS 1200 Platform ..................................65
Connecting the JCS 1200 Management Module to the Network .....................68
Connecting to the JCS 1200 Management Module Using a Network
Ethernet Connection ........................................................................69
Connecting to the JCS 1200 Management Module Using a Direct Ethernet
Connection .......................................................................................69
Connecting to the JCS 1200 Management Module Using a Console Serial
Connection .......................................................................................69
Connecting to the JCS 1200 Management Module Using a Direct Serial
Connection .......................................................................................70
Establishing Your JCS 1200 Management Module Connection .......................70
Establishing Your JCS 1200 Management Module Connection Using a
Direct Ethernet Connection ..............................................................71
Establishing Your JCS 1200 Management Module Connection Using a
Direct Serial Connection ...................................................................71
Connecting a Console to the JCS 1200 Routing Engines ................................72
Powering On a JCS 1200 Routing Engine ......................................................73
Powering Off a JCS 1200 Routing Engine ......................................................74
Connecting the JCS 1200 Platform to a T-series Routing Platform .................74
Replacing the Standard CBs in the T-series Routing Platform ..................75
Connecting an Offline T-series Routing Platform to the JCS 1200
Powering On the T-series Routing Platform ............................................78
Verifying that the JCS 1200 Platform is Powered On Correctly ......................79
Table of Contents
■ ix
Juniper Control System (JCS) 1200 Platform Hardware Guide
Part 3
Configuring the JCS 1200 Platform ................................................................81
Hardware Troubleshooting and Replacement Procedures
Troubleshooting Common JCS 1200 Platform Problems 85
Overview of JCS 1200 Diagnostic Tools .........................................................85
JCS 1200 Troubleshooting Tables ..................................................................86
Overview of JCS 1200 Troubleshooting Tables ........................................86
Troubleshooting JCS 1200 Fan Module Problems ....................................86
Troubleshooting JCS 1200 Management Module Problems .....................87
Troubleshooting JCS 1200 Media Tray Problems .....................................88
Troubleshooting JCS 1200 Power Problems ............................................89
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform .............................................90
Replacing Components in a JCS 1200 Platform 93
JCS 1200 Hardware Component Installation Checklist ...................................94
JCS 1200 Hardware Component Installation Guidelines ................................95
JCS 1200 Platform System Reliability Guidelines ...........................................95
Replacing a JCS 1200 Alarm Panel Module or Module Filler ..........................96
Removing a JCS 1200 Alarm Panel Module or Module Filler ...................96
Installing a JCS 1200 Alarm Panel Module or Module Filler .....................96
Removing a JCS 1200 Bezel ....................................................................97
Installing a JCS 1200 Bezel ......................................................................98
Removing a JCS 1200 Bezel Collar ........................................................100
Installing a JCS 1200 Bezel Collar ..........................................................102
Removing a JCS 1200 Bezel Filter .........................................................107
Installing the JCS 1200 Bezel Filter ........................................................108
Replacing JCS 1200 Cable Management Trays Without a Bezel ...................110
Removing the JCS 1200 Cable Management Trays Without a Bezel ......110
Installing the JCS 1200 Cable Management Trays Without a Bezel ........111
Removing Components from a JCS 1200 Chassis .................................113
Installing Components in a Replacement JCS 1200 Chassis ..................114
Replacing a JCS 1200 DC Terminal Cover ....................................................115
Removing a JCS 1200 DC Terminal Cover .............................................115
Installing a JCS 1200 DC Terminal Cover ..............................................115
x ■
Table of Contents
Table of Contents
Replacing a JCS 1200 Fan Module ...............................................................116
Removing a JCS 1200 Fan Module ........................................................116
Installing a JCS 1200 Fan Module ..........................................................118
Replacing a JCS 1200 Fan Pack ...................................................................120
Removing a JCS 1200 Fan Pack ............................................................120
Installing a JCS 1200 Fan Pack ..............................................................121
Replacing a JCS 1200 Fan Shuttle ................................................................121
Removing a JCS 1200 Fan Shuttle .........................................................122
Installing a JCS 1200 Fan Shuttle ..........................................................123
Replacing a JCS 1200 Management Module or Module Filler .......................124
Removing a JCS 1200 Management Module or Module Filler ................124
Installing a JCS 1200 Management Module or Module Filler ..................125
Replacing a JCS 1200 Management Module Filler Tray ................................127
Removing a JCS 1200 Management Module Filler Tray .........................127
Installing a JCS 1200 Management Module Filler Tray ..........................128
Replacing a JCS 1200 Management Module Interposer ................................128
Replacing a JCS 1200 Media Tray ................................................................128
Removing a JCS 1200 Media Tray .........................................................128
Installing a JCS 1200 Media Tray ...........................................................129
Replacing a JCS 1200 Midplane ...................................................................130
Replacing a JCS 1200 MUX Card .................................................................131
Removing a JCS 1200 MUX Card ..........................................................131
Installing a JCS 1200 MUX Card ............................................................131
Replacing a JCS 1200 Network Clock Filler ..................................................132
Removing a JCS 1200 Network Clock Filler ...........................................132
Installing a JCS 1200 Network Clock Filler ............................................133
Replacing a JCS 1200 Power Box .................................................................134
Removing a JCS 1200 Power Box .........................................................134
Installing a JCS 1200 Power Box ...........................................................136
Replacing a JCS 1200 Power Module ...........................................................138
Removing a JCS 1200 Power Module ....................................................138
Installing a JCS 1200 Power Module ......................................................139
Replacing a JCS 1200 Routing Engine ..........................................................140
Removing a JCS 1200 Routing Engine ...................................................140
Installing a JCS 1200 Routing Engine ....................................................141
Replacing a JCS 1200 Switch Module or Module Filler .................................143
Removing a JCS 1200 Switch Module or Module Filler ..........................143
Installing a JCS 1200 Switch Module or Module Filler ............................143
Replacing a JCS 1200 Switch Module Filler Tray ..........................................145
Removing a JCS 1200 Switch Module Filler Tray ...................................145
Installing a JCS 1200 Switch Module Filler Tray ....................................146
Replacing a JCS 1200 Switch Module Interposer ..........................................146
Table of Contents
■ xi
Juniper Control System (JCS) 1200 Platform Hardware Guide
Part 4
Appendixes
Safety and Regulatory Compliance Information 149
Definition of Safety Warning Levels ............................................................149
JCS 1200 Safety Guidelines and Warnings ...................................................150
JCS 1200 General Safety Guidelines and Warnings ...............................151
General Safety Guidelines and Warnings for the JCS 1200
Platform ...................................................................................151
Qualified Personnel Warning for the JCS 1200 Platform .................152
Restricted Access Area Warning for the JCS 1200 Platform ............152
Preventing Electrostatic Discharge Damage to the JCS 1200
Platform ...................................................................................154
Fire Safety Requirements for the JCS 1200 Platform .............................155
JCS 1200 Installation Safety Guidelines and Warnings ..........................155
JCS 1200 Chassis Lifting Guidelines ................................................155
Installation Instructions Power Warning for the JCS 1200
Platform ...................................................................................156
Rack-Mounting Requirements and Warnings for the JCS 1200
Platform ...................................................................................156
Ramp Warning for the JCS 1200 Platform ......................................160
JCS 1200 Laser and LED Safety Guidelines and Warnings .....................160
Class 1 Laser Product Warning for the JCS 1200 Platform ..............160
Class 1 LED Product Warning for the JCS 1200 Platform ................161
Laser Beam Warning for the JCS 1200 Platform .............................162
Radiation from Open Port Apertures Warning for the JCS 1200
Platform ...................................................................................163
JCS 1200 Maintenance and Operational Safety Guidelines and
Warnings ........................................................................................164
Battery Handling Warning for the JCS 1200 Platform .....................164
Jewelry Removal Warning for the JCS 1200 Platform .....................165
Lightning Activity Warning for the JCS 1200 Platform ....................166
Operating Temperature Warning for the JCS 1200 Platform ...........167
Product Disposal Warning for the JCS 1200 Platform .....................168
JCS 1200 Electrical Safety Guidelines and Warnings .............................169
In Case of an Electrical Accident .....................................................169
JCS 1200 General Electrical Safety Guidelines and Warnings ..........170
JCS 1200 AC Power Electrical Safety Guidelines and Warnings .......174
JCS 1200 DC Power Electrical Safety Guidelines and Warnings ......175
JCS 1200 Agency Approvals and Compliance Statements .....................181
Agency Approvals for the JCS 1200 Platform ..................................181
Compliance Statements for Environmental Requirements for the
JCS 1200 Platform ....................................................................183
Electronic Emission Notices for the JCS 1200 Platform ...................183
Environmental Specifications 187
JCS 1200 Platform Environmental Specifications .........................................187
xii ■
Table of Contents
Table of Contents
Part 5
Power Requirements, Guidelines, and Specifications 189
Site Electrical Wiring Guidelines for the JCS 1200 Platform .........................189
AC Power Supply Electrical Specifications for the JCS 1200 Platform ..........190
Power Consumption for an AC-Powered JCS 1200 Platform ........................190
DC Power Supply Electrical Specifications for the JCS 1200 Platform ..........192
Power Consumption for a DC-Powered JCS 1200 Platform ..........................192
JCS 1200 Alarm Panel Module Interface Connector Electrical
Contacting Customer Support and Returning Hardware 195
Locating Component Serial Numbers ..........................................................195
Locating the JCS 1200 Chassis Serial Number .......................................196
Locating the JCS 1200 Alarm Panel Serial Number ...............................197
Locating the JCS 1200 Fan Module Serial Number ................................198
Locating the JCS 1200 Management Module Serial Number ..................199
Locating the JCS 1200 Media Tray Serial Number .................................200
Locating the JCS 1200 Midplane Serial Number ....................................201
Locating the JCS 1200 MUX Card Serial Number ...................................201
Locating the JCS 1200 Power Module Serial Number ............................202
Locating the JCS 1200 Routing Engine Serial Number ...........................203
Locating the JCS 1200 Switch Module Serial Number ............................205
Tools and Parts Required to Remove Components from the JCS 1200
Packing the JCS 1200 Platform for Shipment ..............................................208
Guidelines for Packing JCS 1200 Platform Components for Shipment .........209
Serial Cable Characteristics for the JCS 1200 Management Module .............211
Pinouts for the JCS 1200 Alarm Panel Interface Connector ..........................213
Index
Table of Contents
■ xiii
Juniper Control System (JCS) 1200 Platform Hardware Guide xiv ■
Table of Contents
List of Figures
Figure 1: Straight-on Front View of the JCS 1200 Platform ..............................5
Figure 2: Straight-on Rear View of JCS 1200 Platform with AC
Figure 3: Exploded Front View of Components in the JCS 1200 Platform ......10
Figure 4: Exploded Rear View of Components in the JCS 1200 Platform .......11
Figure 5: JCS 1200 Alarm Panel Module LEDs and Connectors ......................12
Figure 7: JCS 1200 Management Module Input and Output Connectors ........16
Figure 8: JCS 1200 Management Module LEDs and Controls .........................17
Figure 10: JCS 1200 Media Tray Components ...............................................19
Figure 11: JCS 1200 MUX Card LEDs .............................................................21
Figure 12: Top: AC Power Modules; Bottom: DC Power Modules ...................22
Figure 13: JCS 1200 Power Module LEDs ......................................................23
Figure 14: JCS 1200 Routing Engine ..............................................................24
Figure 15: JCS 1200 Routing Engine Control Panel ........................................25
Figure 16: JCS 1200 Switch Module ...............................................................27
Figure 17: JCS 1200 Switch Module Components ..........................................28
Figure 18: JCS 1200 Switch Module LEDs ......................................................29
Figure 19: Typical Open-Frame Rack ............................................................37
Figure 20: JCS 1200 Chassis Dimensions and Clearance Requirements .........38
Figure 22: Installing the JCS 1200 Mounting Hardware for an Open-Frame
Figure 23: Installing the JCS 1200 Platform in a Four-Post Rack ....................53
Figure 24: Installing the JCS 1200 Platform in an Open-Frame Rack .............54
Figure 26: Logical View of Power Domains on the JCS 1200 Platform ...........62
Figure 27: JCS 1200 DC Power Terminal Connectors ....................................63
Figure 28: Attaching the Cable Lugs to the JCS 1200 DC Power Terminal
Figure 29: DC Power Terminal Connectors on the JCS 1200 Platform ...........67
Figure 30: Ports on the JCS 1200 Management Module .................................68
Figure 31: JCS 1200 Serial Port Breakout Cable .............................................72
Figure 32: Location of Switch Modules on the JCS 1200 Platform ..................76
Figure 33: Connecting the JCS 1200 Platform to a T-series Routing
Figure 34: Removing and Installing a JCS 1200 Alarm Panel Module .............96
Figure 35: Removing and Installing a JCS 1200 Alarm Panel Module .............97
Figure 36: Removing a JCS 1200 Bezel ..........................................................98
List of Figures
■ xv
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 37: Installing a JCS 1200 Bezel ...........................................................99
Figure 38: Removing and Installing the JCS 1200 Bezel Collar .....................100
Figure 39: Removing the Light Path Extension Assembly ............................101
Figure 40: Removing the Cable Management Trays .....................................102
Figure 41: Removing and Installing the JCS 1200 Bezel Collar .....................103
Figure 42: Attaching the Cable Management Trays to the Bezel Collar ........104
Figure 43: Securing the Cable Management Trays .......................................105
Figure 44: Installing the Light Path Extension Assembly ..............................106
Figure 46: Removing the Air Filter Assembly ..............................................108
Figure 47: Cutouts on the JCS 1200 Bezel Filter ...........................................109
Figure 48: Securing the Air Filter Assembly .................................................110
Figure 49: Removing and Installing the JCS 1200 Cable Management
Figure 50: Removing and Installing the JCS 1200 Cable Management
Figure 51: Removing and Installing a JCS 1200 DC Terminal Cover ............115
Figure 52: Removing and Installing a JCS 1200 DC Terminal Cover ............116
Figure 53: Removing and Installing a JCS 1200 Fan Module ........................117
Figure 54: Removing the Shipping Block .....................................................117
Figure 55: Removing and Installing a JCS 1200 Fan Module ........................118
Figure 56: Fan Module Orientation Marks ...................................................119
Figure 57: Installing the JCS 1200 Shipping Block ........................................119
Figure 58: Removing and Installing a JCS 1200 Fan Pack ............................120
Figure 59: Removing and Installing a JCS 1200 Fan Pack ............................121
Figure 60: Removing and Installing a JCS 1200 Fan Shuttle .........................122
Figure 61: Removing and Installing a JCS 1200 Fan Shuttle .........................123
Figure 62: Removing and Installing a JCS 1200 Management Module .........125
Figure 63: Removing and Installing a JCS 1200 Management Module .........126
Figure 64: Removing and Installing a JCS 1200 Management Module Filler
Figure 65: Removing a JCS 1200 Media Tray ...............................................129
Figure 66: Installing a JCS 1200 Media Tray ................................................129
Figure 67: Positioning the Release Lever and Button on the JCS 1200 Media
Figure 68: Removing and Installing a JCS 1200 MUX Card ..........................131
Figure 69: Removing and Installing a JCS 1200 MUX Card ..........................132
Figure 70: Removing and Installing a JCS 1200 Network Clock Filler ...........133
Figure 71: Removing and Installing a JCS 1200 Network Clock Filler ...........134
Figure 72: Removing and Installing a JCS 1200 Power Box .........................135
Figure 73: Loosening Thumbscrews on the Upper Power Box .....................135
Figure 74: Loosening Thumbscrews on the Lower Power Box .....................136
Figure 75: Removing and Installing a JCS 1200 Power Box .........................136
Figure 76: Tightening Thumbscrews on the Upper Power Box ....................137
Figure 77: Tightening Thumbscrews on the Lower Power Box ....................137
Figure 78: Removing and Installing a JCS 1200 Power Module ....................138
Figure 79: Removing and Installing a JCS 1200 Power Module ....................139
Figure 80: Removing and Installing a JCS 1200 Routing Engine ..................140
Figure 81: Removing and Installing a JCS 1200 Routing Engine ..................141
Figure 82: Removing and Installing a JCS 1200 Switch Module ...................143
Figure 83: Removing and Installing a JCS 1200 Switch Module ...................144
xvi ■
List of Figures
List of Figures
Figure 84: Removing and Installing a JCS 1200 Switch Module Filler Tray ....145
Figure 85: Placing a Component into an Electrostatic Bag ...........................154
Figure 86: JCS 1200 Declaration of Conformity ...........................................185
Figure 87: Serial Number ID Label ...............................................................195
Figure 88: JCS 1200 Chassis Serial Number Label ........................................196
Figure 89: JCS 1200 Alarm Panel Module Serial Number Label ....................197
Figure 90: JCS 1200 Fan Module Serial Number Label .................................198
Figure 91: JCS 1200 Management Module Serial Number Label ..................199
Figure 92: JCS 1200 Media Tray Serial Number Label ..................................200
Figure 93: JCS 1200 Power Module Serial Number Label .............................202
Figure 94: JCS 1200 Routing Engine Serial Number Label ...........................203
Figure 95: User Label Locations on the JCS 1200 Platform ..........................204
Figure 96: JCS 1200 Switch Module Serial Number Label ............................205
List of Figures
■ xvii
Juniper Control System (JCS) 1200 Platform Hardware Guide xviii ■
List of Figures
List of Tables
Table 2: Text and Syntax Conventions ........................................................xxiii
Table 3: Technical Documentation for Supported Routing Platforms ..........xxiv
Table 4: JUNOS Software Network Operations Guides ...............................xxviii
Table 5: JUNOS Software with Enhanced Services Documentation .............xxix
Table 7: JCS 1200 Features and Specifications ................................................7
Table 8: JCS 1200 Alarm Panel Module LEDs ................................................13
Table 9: JCS 1200 Fan Module LED ...............................................................15
Table 10: JCS 1200 Management Module LEDs .............................................18
Table 11: JCS 1200 Media Tray LEDs .............................................................20
Table 12: JCS 1200 MUX Card LEDs ..............................................................21
Table 13: JCS 1200 Power Module LEDs ........................................................23
Table 14: JCS 1200 Routing Engine LEDs ......................................................26
Table 15: JCS 1200 Switch Module LEDs .......................................................29
Table 17: Parts List for a Fully Configured JCS 1200 Platform .......................41
Table 18: JCS 1200 Accessory Box Parts List .................................................42
Table 19: Open-Frame Rack Mounting Hole Locations ..................................44
Table 20: Troubleshooting JCS 1200 Fan Module Problems ...........................87
Table 21: Troubleshooting JCS 1200 Management Module Problems ............87
Table 22: Troubleshooting JCS 1200 Media Tray Problems ............................88
Table 23: Troubleshooting JCS 1200 Power Problems ...................................89
Table 24: Diagnostic LEDs on the JCS 1200 Platform ....................................90
Table 25: Platform Environmental Specifications ........................................187
Table 26: AC Power Electrical Specifications for the JCS 1200 Platform ......190
Table 27: AC-Powered Base JCS 1200 Platform Power Requirements .........191
Table 28: AC-Powered JCS 1200 Platform Component Power
Table 29: DC Power Electrical Specifications for the JCS 1200 Platform ......192
Table 30: DC-Powered Base JCS 1200 Platform Power Requirements .........192
Table 31: DC-Powered JCS 1200 Platform Component Power
Table 32: JCS 1200 Alarm Panel Interface Connector Electrical
Table 33: Information About Your JCS 1200 Platform .................................196
Table 34: Serial Cable Characteristics for the JCS 1200 Platform .................211
Table 35: Pinouts for the AMM Adapter .......................................................212
Table 36: Pinouts for the CPU Adapter and Breakout Serial Cable ...............212
Table 37: Pinouts for the Alarm Panel Interface Connector .........................213
List of Tables
■ xix
Juniper Control System (JCS) 1200 Platform Hardware Guide xx ■
List of Tables
About This Guide
This preface provides the following guidelines for using the JCS 1200 Platform Hardware
Guide:
■
■
■
■
■
■
■
Documentation Conventions on page xxii
List of Technical Publications on page xxiv
Obtaining Documentation on page xxxi
Documentation Feedback on page xxxi
Requesting Technical Support on page xxxi
Objectives
This manual describes hardware components, installation, basic configuration, and basic troubleshooting procedures for the Juniper Networks JCS 1200 platform. It explains how to prepare your site for JCS 1200 platform installation, unpack and install the hardware, power on the JCS 1200 platform, perform initial software configuration, and perform routine maintenance. After completing the installation and basic configuration procedures covered in this manual, see the JUNOS Protected
System Domain Configuration Guide for information about further configuration.
This Hardware Guide provides information about the following tasks:
■
Installing and cabling the JCS 1200 platform
■
Installing basic JCS 1200 platform optional devices:
■
Alarm panel module
■
Fan modules
■
Fan shuttles
■
■
Media trays
Management modules
■
■
■
Management module interposers
MUX cards
Power modules
Objectives
■ xxi
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
■
■
Routing Engines
Switch modules
Switch module interposers
Performing basic troubleshooting of the JCS 1200 platform
You can obtain up-to-date information about your JCS 1200 platform and other
Juniper Networks server products at http://www.juniper.net/techpubs/
.
NOTE: For additional information about Juniper Networks Internet routers and the
Physical Interface Cards (PICs) they support—either corrections to or information that might have been omitted from this guide—see the hardware release notes at http://www.juniper.net/
.
Audience
This guide is designed for network administrators who are installing and maintaining a Juniper Networks router or preparing a site for router installation. To use this guide, you need a broad understanding of networks in general, the Internet in particular, networking principles, and network configuration. Any detailed discussion of these concepts is beyond the scope of this guide.
Documentation Conventions
Table 1 on page xxii defines the notice icons used in this guide.
Table 1: Notice Icons
Icon Meaning
Informational note
Description
Indicates important features or instructions.
Caution Indicates a situation that might result in loss of data or hardware damage.
Warning
Laser warning
Alerts you to the risk of personal injury or death.
Alerts you to the risk of personal injury from a laser.
Table 2 on page xxiii defines the text and syntax conventions used in this guide.
xxii ■
Audience
About This Guide
Table 2: Text and Syntax Conventions
Convention
Bold text like this
Fixed-width text like this
Italic text like this
Italic text like this
Plain text like this
< > (angle brackets)
| (pipe symbol)
# (pound sign)
[ ] (square brackets)
Indention and braces ( { } )
; (semicolon)
Description
Represents text that you type.
Examples
To enter configuration mode, type the configure command: user@host> configure
Represents output that appears on the terminal screen.
■
■
■
Introduces important new terms.
Identifies book names.
Identifies RFC and Internet draft titles.
user@host> show chassis alarms
No alarms currently active
■
■
■
A policy term is a named structure that defines match conditions and actions.
JUNOS System Basics Configuration
Guide
RFC 1997, BGP Communities
Attribute
Represents variables (options for which you substitute a value) in commands or configuration statements.
Configure the machine’s domain name:
[edit] root@# set system domain-name
domain-name
Represents names of configuration statements, commands, files, and directories; IP addresses; configuration hierarchy levels; or labels on routing platform components.
■
■
To configure a stub area, include the stub statement at the [edit protocols ospf area area-id] hierarchy level.
The console port is labeled
CONSOLE .
Enclose optional keywords or variables.
stub <default-metric metric>;
Indicates a choice between the mutually exclusive keywords or variables on either side of the symbol. The set of choices is often enclosed in parentheses for clarity.
broadcast | multicast
(string1 | string2 | string3 )
Indicates a comment specified on the same line as the configuration statement to which it applies.
rsvp { # Required for dynamic MPLS only
Enclose a variable for which you can substitute one or more values.
Identify a level in the configuration hierarchy.
Identifies a leaf statement at a configuration hierarchy level.
community name members [
community-ids ]
}
[edit] routing-options { static { route default { nexthop address; retain;
}
}
Documentation Conventions
■ xxiii
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 2: Text and Syntax Conventions (continued)
Description Convention
J-Web GUI Conventions
Bold text like this
> (bold right angle bracket)
Examples
Represents J-Web graphical user interface (GUI) items you click or select.
■
■
In the Logical Interfaces box, select
All Interfaces.
To cancel the configuration, click
Cancel.
Separates levels in a hierarchy of J-Web selections.
In the configuration editor hierarchy, select Protocols>Ospf.
List of Technical Publications
Table 3 on page xxiv lists the software and hardware guides and release notes for
Juniper Networks J-series, M-series, MX-series, and T-series routing platforms and
describes the contents of each document. Table 4 on page xxviii lists the books included
in the Network Operations Guide series. Table 5 on page xxix lists the manuals and
release notes supporting JUNOS software with enhanced services. All documents are available at http://www.juniper.net/techpubs/
.
Table 6 on page xxx lists additional books on Juniper Networks solutions that you can
order through your bookstore. A complete list of such books is available at http://www.juniper.net/books
.
Table 3: Technical Documentation for Supported Routing Platforms
Book Description
JUNOS Software for Supported Routing Platforms
Access Privilege
Explains how to configure access privileges in user classes by using permission flags and regular expressions. Lists the permission flags along with their associated command-line interface (CLI) operational mode commands and configuration statements.
Class of Service
Provides an overview of the class-of-service (CoS) functions of the
JUNOS software and describes how to configure CoS features, including configuring multiple forwarding classes for transmitting packets, defining which packets are placed into each output queue, scheduling the transmission service level for each queue, and managing congestion through the random early detection (RED) algorithm.
CLI User Guide
Feature Guide
Describes how to use the JUNOS command-line interface (CLI) to configure, monitor, and manage Juniper Networks routing platforms. This material was formerly covered in the JUNOS System
Basics Configuration Guide.
Provides a detailed explanation and configuration examples for several of the most complex features in the JUNOS software.
xxiv ■
List of Technical Publications
About This Guide
Table 3: Technical Documentation for Supported Routing Platforms (continued)
Book
High Availability
MPLS Applications
Multicast Protocols
Multiplay Solutions
MX-series Layer 2 Configuration Guide
MX-series Layer 2 Solutions Guide
Description
Provides an overview of hardware and software resources that ensure a high level of continuous routing platform operation and describes how to configure high availability (HA) features such as nonstop active routing (NSR) and graceful Routing Engine switchover (GRES).
Provides an overview of traffic engineering concepts and describes how to configure traffic engineering protocols.
Provides an overview of multicast concepts and describes how to configure multicast routing protocols.
Describes how you can deploy IPTV and voice over IP (VoIP) services in your network.
Provides an overview of the Layer 2 functions of the MX-series routers, including configuring bridging domains, MAC address and
VLAN learning and forwarding, and spanning-tree protocols. It also details the routing instance types used by Layer 2 applications. All of this material was formerly covered in the JUNOS Routing Protocols
Configuration Guide.
Describes common configuration scenarios for the Layer 2 features supported on the MX-series routers, including basic bridged VLANs with normalized VLAN tags, aggregated Ethernet links, bridge domains, Multiple Spanning Tree Protocol (MSTP), and integrated routing and bridging (IRB).
Network Interfaces
Network Management
Policy Framework
Protected System Domain
Provides an overview of the network interface functions of the
JUNOS software and describes how to configure the network interfaces on the routing platform.
Provides an overview of network management concepts and describes how to configure various network management features, such as SNMP and accounting options.
Provides an overview of policy concepts and describes how to configure routing policy, firewall filters, and forwarding options.
Provides an overview of the JCS 1200 platform and the concept of
Protected System Domains (PSDs). The JCS 1200 platform, which contains up to six redundant pairs of Routing Engines running
JUNOS software, is connected to a T320 router or to a T640 or
T1600 routing node. To configure a PSD, you assign any number of Flexible PIC concentrators (FPCs) in the T-series routing platform to a pair of Routing Engines on the JCS 1200 platform. Each PSD has the same capabilities and functionality as a physical router, with its own control plane, forwarding plane, and administration.
Routing Protocols
Provides an overview of routing concepts and describes how to configure routing instances, and unicast routing protocols.
Secure Configuration Guide for Common Criteria and JUNOS-FIPS
Provides an overview of secure Common Criteria and JUNOS-FIPS protocols for the JUNOS software and describes how to install and configure secure Common Criteria and JUNOS-FIPS on a routing platform.
List of Technical Publications
■ xxv
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 3: Technical Documentation for Supported Routing Platforms (continued)
Book
Services Interfaces
Software Installation and Upgrade Guide
Subscriber Access
System Basics
VPNs
Description
Provides an overview of the services interfaces functions of the
JUNOS software and describes how to configure the services interfaces on the router.
Describes the JUNOS software components and packaging and explains how to initially configure, reinstall, and upgrade the JUNOS system software. This material was formerly covered in the JUNOS
System Basics Configuration Guide.
Provides an overview of the subscriber access features of the JUNOS software and describes how to configure subscriber access support on the router, including dynamic profiles, class of service, AAA, and access methods.
Describes Juniper Networks routing platforms and explains how to configure basic system parameters, supported protocols and software processes, authentication, and a variety of utilities for managing your router on the network.
Provides an overview and describes how to configure Layer 2 and
Layer 3 virtual private networks (VPNs), virtual private LAN service
(VPLS), and Layer 2 circuits. Provides configuration examples.
JUNOS References
Hierarchy and RFC Reference
Interfaces Command Reference
Routing Protocols and Policies Command
Reference
Describes the JUNOS configuration mode commands. Provides a hierarchy reference that displays each level of a configuration hierarchy, and includes all possible configuration statements that can be used at that level. This material was formerly covered in the JUNOS System Basics Configuration Guide.
Describes the JUNOS software operational mode commands you use to monitor and troubleshoot interfaces.
Describes the JUNOS software operational mode commands you use to monitor and troubleshoot routing policies and protocols, including firewall filters.
System Basics and Services Command Reference
Describes the JUNOS software operational mode commands you use to monitor and troubleshoot system basics, including commands for real-time monitoring and route (or path) tracing, system software management, and chassis management. Also describes commands for monitoring and troubleshooting services such as class of service (CoS), IP Security (IPsec), stateful firewalls, flow collection, and flow monitoring.
System Log Messages Reference
Describes how to access and interpret system log messages generated by JUNOS software modules and provides a reference page for each message.
J-Web User Guide
J-Web Interface User Guide
Describes how to use the J-Web graphical user interface (GUI) to configure, monitor, and manage Juniper Networks routing platforms.
JUNOS API and Scripting Documentation xxvi ■
List of Technical Publications
About This Guide
Table 3: Technical Documentation for Supported Routing Platforms (continued)
Book
JUNOScript API Guide
JUNOS XML API Configuration Reference
Description
Describes how to use the JUNOScript application programming interface (API) to monitor and configure Juniper Networks routing platforms.
Provides reference pages for the configuration tag elements in the
JUNOS XML API.
JUNOS XML API Operational Reference
NETCONF API Guide
DPC Guide
Provides reference pages for the operational tag elements in the
JUNOS XML API.
Describes how to use the NETCONF API to monitor and configure
Juniper Networks routing platforms.
JUNOS Configuration and Diagnostic Automation
Guide
Describes how to use the commit script and self-diagnosis features of the JUNOS software. This guide explains how to enforce custom configuration rules defined in scripts, how to use commit script macros to provide simplified aliases for frequently used configuration statements, and how to configure diagnostic event policies.
Hardware Documentation
Hardware Guide
Describes how to install, maintain, and troubleshoot routing platforms and components. Each platform has its own hardware guide.
PIC Guide
Describes the routing platform's Physical Interface Cards (PICs).
Each platform has its own PIC guide.
Describes the Dense Port Concentrators (DPCs) for all MX-series routers.
JUNOScope Documentation
JUNOScope Software User Guide
Describes the JUNOScope software graphical user interface (GUI), how to install and administer the software, and how to use the software to manage routing platform configuration files and monitor routing platform operations.
Advanced Insight Solutions (AIS) Documentation
Advanced Insight Solutions Guide
Describes the Advanced Insight Manager (AIM) application, which provides a gateway between JUNOS devices and Juniper Support
Systems (JSS) for case management and intelligence updates.
Explains how to run AI-Scripts on Juniper Networks devices.
J-series Routing Platform Documentation
Getting Started Guide
Provides an overview, basic instructions, and specifications for
J-series routing platforms. The guide explains how to prepare your site for installation, unpack and install the router and its components, install licenses, and establish basic connectivity. Use the Getting Started Guide for your router model.
Basic LAN and WAN Access Configuration Guide
Explains how to configure the interfaces on J-series Services Routers for basic IP routing with standard routing protocols, ISDN backup, and digital subscriber line (DSL) connections.
List of Technical Publications
■ xxvii
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 3: Technical Documentation for Supported Routing Platforms (continued)
Book
Advanced WAN Access Configuration Guide
Administration Guide
Description
Explains how to configure J-series Services Routers in virtual private networks (VPNs) and multicast networks, configure data link switching (DLSw) services, and apply routing techniques such as policies, stateless and stateful firewall filters, IP Security (IPsec) tunnels, and class-of-service (CoS) classification for safer, more efficient routing.
Shows how to manage users and operations, monitor network performance, upgrade software, and diagnose common problems on J-series Services Routers.
Release Notes
JUNOS Release Notes
Hardware Release Notes
JUNOScope Release Notes
AIS Release Notes
AIS AI-Scripts Release Notes
J-series Services Router Release Notes
Summarize new features and known problems for a particular software release, provide corrections and updates to published
JUNOS, JUNOScript, and NETCONF manuals, provide information that might have been omitted from the manuals, and describe upgrade and downgrade procedures.
Describe the available documentation for the routing platform and summarize known problems with the hardware and accompanying software. Each platform has its own release notes.
Contain corrections and updates to the published JUNOScope manual, provide information that might have been omitted from the manual, and describe upgrade and downgrade procedures.
Summarize AIS new features and guidelines, identify known and resolved problems, provide information that might have been omitted from the manuals, and provide initial setup, upgrade, and downgrade procedures.
Summarize AI-Scripts new features, identify known and resolved problems, provide information that might have been omitted from the manuals, and provide instructions for automatic and manual installation, including deleting and rolling back.
Briefly describe Services Router features, identify known hardware problems, and provide upgrade and downgrade instructions.
Table 4: JUNOS Software Network Operations Guides
Book
Baseline
Interfaces
Description
Describes the most basic tasks for running a network using Juniper
Networks products. Tasks include upgrading and reinstalling JUNOS software, gathering basic system management information, verifying your network topology, and searching log messages.
Describes tasks for monitoring interfaces. Tasks include using loopback testing and locating alarms.
xxviii ■
List of Technical Publications
About This Guide
Table 4: JUNOS Software Network Operations Guides (continued)
Book
MPLS
MPLS Log Reference
MPLS Fast Reroute
Hardware
Description
Describes tasks for configuring, monitoring, and troubleshooting an example MPLS network. Tasks include verifying the correct configuration of the MPLS and RSVP protocols, displaying the status and statistics of MPLS running on all routing platforms in the network, and using the layered MPLS troubleshooting model to investigate problems with an MPLS network.
Describes MPLS status and error messages that appear in the output of the show mpls lsp extensive command. The guide also describes how and when to configure Constrained Shortest Path First (CSPF) and RSVP trace options, and how to examine a CSPF or RSVP failure in a sample network.
Describes operational information helpful in monitoring and troubleshooting an MPLS network configured with fast reroute
(FRR) and load balancing.
Describes tasks for monitoring M-series and T-series routing platforms.
To configure and operate a J-series Services Router running JUNOS software with enhanced services, you must also use the configuration statements and operational mode commands documented in JUNOS configuration guides and command references. To configure and operate a WX Integrated Services Module, you must also use WX documentation.
Table 5: JUNOS Software with Enhanced Services Documentation
Description Book
All Platforms
JUNOS Software Interfaces and Routing
Configuration Guide
JUNOS Software Security Configuration Guide
JUNOS Software Administration Guide
JUNOS Software CLI Reference
Explains how to configure J-series interfaces for basic IP routing with standard routing protocols, ISDN service, firewall filters (access control lists), and class-of-service (CoS) traffic classification.
Explains how to configure and manage security services such as stateful firewall policies, IP Security (IPsec) virtual private networks (VPNs), firewall screens, Network Address
Translation (NAT), Public Key Cryptography, and Application
Layer Gateways (ALGs).
Shows how to monitor J-series devices and routing operations, firewall and security services, system alarms and events, and network performance. This guide also shows how to administer user authentication and access, upgrade software, and diagnose common problems.
Provides the complete JUNOS software with enhanced services configuration hierarchy and describes the configuration statements and operational mode commands not documented in the standard JUNOS manuals.
List of Technical Publications
■ xxix
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 5: JUNOS Software with Enhanced Services Documentation (continued)
Book Description
J-series Only
JUNOS Software with Enhanced Services Design and Implementation Guide
Provides guidelines and examples for designing and implementing IPsec VPNs), firewalls, and routing on J-series
Services Routers running JUNOS software with enhanced services.
JUNOS Software with Enhanced Services Quick
Start
Explains how to quickly set up a J-series Services Router.
This document contains router declarations of conformity.
JUNOS Software with Enhanced Services J-series
Services Router Hardware Guide
Provides an overview, basic instructions, and specifications for J-series Services Routers. This guide explains how to prepare a site, unpack and install the router, replace router hardware, and establish basic router connectivity. This guide contains hardware descriptions and specifications.
JUNOS Software with Enhanced Services
Migration Guide
Provides instructions for migrating an SSG device running
ScreenOS software or a J-series Services Router running the
JUNOS software to JUNOS software with enhanced services.
WXC Integrated Services Module Installation and
Configuration Guide
Explains how to install and initially configure a WXC
Integrated Services Module in a J-series Services Router for application acceleration.
JUNOS Software with Enhanced Services for
J-series Services Router Release Notes
Summarizes new features and known problems for a particular release of JUNOS software with enhanced services on J-series Services Routers, including J-Web interface features and problems. The release notes also contain corrections and updates to the manuals and software upgrade and downgrade instructions for JUNOS software with enhanced services.
Table 6: Additional Books Available Through http://www.juniper.net/books
Book
Interdomain Multicast
Routing
Description
Provides background and in-depth analysis of multicast routing using Protocol Independent
Multicast sparse mode (PIM SM) and Multicast Source Discovery Protocol (MSDP); details any-source and source-specific multicast delivery models; explores multiprotocol BGP (MBGP) and multicast IS-IS; explains Internet Gateway Management Protocol (IGMP) versions 1, 2, and
3; lists packet formats for IGMP, PIM, and MSDP; and provides a complete glossary of multicast terms.
JUNOS Cookbook
MPLS-Enabled Applications
Provides detailed examples of common JUNOS software configuration tasks, such as basic router configuration and file management, security and access control, logging, routing policy, firewalls, routing protocols, MPLS, and VPNs.
Provides an overview of Multiprotocol Label Switching (MPLS) applications (such as Layer 3 virtual private networks [VPNs], Layer 2 VPNs, virtual private LAN service [VPLS], and pseudowires), explains how to apply MPLS, examines the scaling requirements of equipment at different points in the network, and covers the following topics: point-to-multipoint label switched paths (LSPs), DiffServ-aware traffic engineering, class of service, interdomain traffic engineering, path computation, route target filtering, multicast support for Layer 3 VPNs, and management and troubleshooting of MPLS networks.
xxx ■
List of Technical Publications
About This Guide
Table 6: Additional Books Available Through http://www.juniper.net/books (continued)
Book Description
OSPF and IS-IS: Choosing an
IGP for Large-Scale Networks
Explores the full range of characteristics and capabilities for the two major link-state routing protocols: Open Shortest Path First (OSPF) and IS-IS. Explains architecture, packet types, and addressing; demonstrates how to improve scalability; shows how to design large-scale networks for maximum security and reliability; details protocol extensions for MPLS-based traffic engineering, IPv6, and multitopology routing; and covers troubleshooting for OSPF and IS-IS networks.
Routing Policy and Protocols for Multivendor IP Networks
Provides a brief history of the Internet, explains IP addressing and routing (Routing Information
Protocol [RIP], OSPF, IS-IS, and Border Gateway Protocol [BGP]), explores ISP peering and routing policies, and displays configurations for both Juniper Networks and other vendors' routers.
The Complete IS-IS Protocol
Provides the insight and practical solutions necessary to understand the IS-IS protocol and how it works by using a multivendor, real-world approach.
Obtaining Documentation
To obtain the most current version of all Juniper Networks technical documentation, see the products documentation page on the Juniper Networks Web site at http://www.juniper.net/
.
Copies of the Management Information Bases (MIBs) available in a software release are included on the documentation DVDs and at http://www.juniper.net/
.
Documentation Feedback
We encourage you to provide feedback, comments, and suggestions so that we can improve the documentation. You can send your comments to [email protected]
, or fill out the documentation feedback form at https://www.juniper.net/cgi-bin/docbugreport/
. If you are using e-mail, be sure to include the following information with your comments:
■
■
■
Document name
Document part number
Page number
■
Software release version (not required for Network Operations Guides [NOGs])
Requesting Technical Support
Technical product support is available through the Juniper Networks Technical
Assistance Center (JTAC). If you are a customer with an active J-Care or JNASC support contract, or are covered under warranty, and need postsales technical support, you can access our tools and resources online or open a case with JTAC.
■
JTAC policies—For a complete understanding of our JTAC procedures and policies, review the JTAC User Guide located at http://www.juniper.net/customers/support/downloads/710059.pdf
.
Obtaining Documentation
■ xxxi
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
Product warranties—For product warranty information, visit http://www.juniper.net/support/warranty/
.
JTAC Hours of Operation —The JTAC centers have resources available 24 hours a day, 7 days a week, 365 days a year.
Self-Help Online Tools and Resources
For quick and easy problem resolution, Juniper Networks has designed an online self-service portal called the Customer Support Center (CSC) that provides you with the following features:
■
■
Find CSC offerings: http://www.juniper.net/customers/support/
Search for known bugs: http://www2.juniper.net/kb/
■
■
■
Find product documentation: http://www.juniper.net/techpubs/
Find solutions and answer questions using our Knowledge Base: http://kb.juniper.net/
Download the latest versions of software and review release notes: http://www.juniper.net/customers/csc/software/
■
■
■
Search technical bulletins for relevant hardware and software notifications: https://www.juniper.net/alerts/
Join and participate in the Juniper Networks Community Forum: http://www.juniper.net/company/communities/
Open a case online in the CSC Case Management tool: http://www.juniper.net/cm/
To verify service entitlement by product serial number, use our Serial Number
Entitlement (SNE) Tool located at https://tools.juniper.net/SerialNumberEntitlementSearch/
.
Opening a Case with JTAC
You can open a case with JTAC on the Web or by telephone.
■
Use the Case Management tool in the CSC at http://www.juniper.net/cm/
.
■
Call 1-888-314-JTAC (1-888-314-5822 toll-free in the USA, Canada, and Mexico).
For international or direct-dial options in countries without toll-free numbers, visit us at
http://www.juniper.net/support/requesting-support.html
.
xxxii ■
Requesting Technical Support
Part 1
Product Overview
■
■
JCS 1200 Platform Overview on page 3
Hardware Component Overview on page 9
Product Overview
■ 1
Juniper Control System (JCS) 1200 Platform Hardware Guide
2 ■
Product Overview
Chapter 1
JCS 1200 Platform Overview
■
■
■
JCS 1200 Platform Description on page 3
JCS 1200 Hardware Overview on page 4
JCS 1200 Platform Features and Specifications on page 7
JCS 1200 Platform Description
The Juniper Control System (JCS) 1200 platform is a high-density, high-performance rack-mounted control and Routing Engine platform. The JCS 1200 platform provides
12 bays for Routing Engines and other JCS 1200 platform components, integrating common resources that are shared by the Routing Engines. The use of common resources provides a small server-system footprint that contains high-performing servers with minimal cabling.
The JCS 1200 platform connects to up to three T-series routing platforms through
Gigabit Ethernet links connected between control boards on the T-series platform and switch cards in the JCS 1200 chassis. Each Routing Engine (or Routing Engine pair) in the JCS 1200 comprises the control plane of a single Protected System Domain
(PSD).
Related Topics
PSDs provide you with the ability to divide Flexible PIC Concentrators (FPCs) on a
T-series routing platform and assign them to multiple administratively separated routers. PSDs separate the control plane from the forwarding plane and reduce capital expenses by enabling the sharing of interfaces. Each PSD acts as a self-contained router.
■
JCS 1200 Hardware Overview on page 4
■
■
Major Components of the JCS 1200 Platform on page 9
JCS 1200 Platform Features and Specifications on page 7
JCS 1200 Platform Description
■ 3
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 Hardware Overview
The JCS 1200 platform has the following hardware features:
■
Hot-swap capability, which allows you to add, remove, or replace Routing Engines, media trays, management modules, switch modules, alarm panel modules, MUX cards, power modules, and fans without removing power from the JCS 1200 platform.
■
■
■
A midplane that connects all JCS 1200 components.
A management module that functions as a systems management processor.
There are two management module bays.
Power modules that provide redundant power for all JCS 1200 components.
There are four power modules that operate in redundant pairs. Each pair provides power to selected JCS 1200 components.
■
■
■
Fans that provide cooling for most JCS 1200 components. There are three fans connected to each power module on the front of the JCS 1200 platform and four hot-swappable fan modules on the rear of the JCS 1200 platform.
Two switch modules that support external network interface connections to network resources and control boards of T-series routing platforms.
Four high-speed switch module bays that support high-speed external network interface connections to network resources and other devices.
NOTE: The high-speed switch module bays are not currently supported on the
JCS 1200 platform.
■
A media tray that contains two universal serial bus (USB) version 2.0 ports that can be used by any Routing Engine. There are two media tray bays.
Figure 1 on page 5 shows a straight-on front view of a JCS 1200 AC platform.
4 ■
JCS 1200 Hardware Overview
Chapter 1: JCS 1200 Platform Overview
Figure 1: Straight-on Front View of the JCS 1200 Platform
Figure 2 on page 6 shows a straight-on rear view of a JCS 1200 AC platform with
AC power connectors.
JCS 1200 Hardware Overview
■ 5
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 2: Straight-on Rear View of JCS 1200 Platform with AC Connectors
Related Topics
■
■
■
■
■
■
■
■
■
■
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Fan Module Description on page 14
JCS 1200 Management Module Description on page 15
JCS 1200 Media Tray Description on page 18
JCS 1200 MUX Card Description on page 21
JCS 1200 Power Module Description on page 22
JCS 1200 Routing Engine Description on page 24
JCS 1200 Switch Module Description on page 27
JCS 1200 Power Connectors on page 30
JCS 1200 Platform Features and Specifications on page 7
6 ■
JCS 1200 Hardware Overview
Chapter 1: JCS 1200 Platform Overview
JCS 1200 Platform Features and Specifications
Table 7 on page 7 provides a summary of the features and specifications of the
JCS 1200 platform.
Table 7: JCS 1200 Features and Specifications
Module bays (on front):
■
■
■
■
Media tray (on front):
Minimum: One hot-swappable media tray
Maximum: Two hot-swappable media trays
Management module:
■
■
Minimum: One hot-swappable management module
Maximum: Two hot-swappable management modules: one active, one hot stand-by
Each media tray consists of:
■
■
Two USB v2.0 ports (output power:
500 mA maximum)
Front system LED panel
Redundant cooling: Four hot-swappable fan module bays (N+1 redundant)
Routing Engine bays (on front):
Twelve hot-swappable Routing Engine (blade) bays
■
■
Security features:
■
Login password for remote connection
Secure Sockets Layer (SSL) security for remote management access
ANSI T1.276 enhanced security features
Four hot-swappable power module bays
Four hot-swappable switch module bays
NOTE: Only two switch module bays are currently supported.
■
Two hot-swappable management module bays
■
■
Predictive Failure Analysis (PFA) alerts:
Fans
Routing Engine dependent features
Module bays (on rear):
■
■
Two hot-swappable MUX card bays
One hot-swappable alarm panel module bay
■
Telco alarm connector
■
■
Direct serial connector for Routing
Engines
Rear system LED panel
Power modules:
JCS 1200 DC platform:
■
Four DC hot-swappable power modules that provide redundancy to all JCS 1200 components
■
■
Size (12 U):
■
■
Height: 21 in. (53.34 cm), minus 8 mm for clearance
Depth:
■
Without optional bezel:
25.64 in. (65.1 cm)
■
With optional bezel: 27.80 in.
(70.6 cm)
Width: 17.43 in. (44.3 cm)
Weight:
■
■
Full configured weight with Routing
Engines: Approximately 350 lb
(158.8 kg)
Empty chassis without modules or
Routing Engines: Approximately
329 lb (149.6 kg)
JCS 1200 AC platform:
■
Four AC hot-swappable power modules that provide redundancy to all JCS 1200 components
■
■
Environment:
■
Air temperature:
■
JCS 1200 platform on:
■
Altitude: –197 ft to 6000 ft (–60 to 1800 m) 41° to 104° F (5° to
40° C)
■
Altitude: 6000 ft to 13000 ft
(1800 m to 4000 m) 41° to
86° F (5° to 30° C)
■
JCS 1200 platform off: –40° to 70° C
(–40° to 158° F).
Humidity: 5% to 85%
Acoustics: declared sound power level:
7.8 bels
Electrical input (N+N redundant):
■
■
■
JCS 1200 DC platform input voltage (four inputs at 60-A rating each):
Minimum: –40 V DC
Maximum: –72 V DC
DC isolated
■
■
■
JCS 1200 AC platform input voltage (four inputs at 16 A rating each):
Minimum: 180 V AC
Maximum: 265 V AC
Sine-wave input (50/60 Hz single-phase)
Heat output:
Approximate heat output in British thermal units (Btu) per hour:
■
■
JCS 1200 DC platform:
■
■
Minimum configuration: 4270 Btu per hour (1251 watts)
Maximum configuration: 19680 Btu per hour (5766 watts)
JCS 1200 AC platform:
■
■
Minimum configuration: 4175 Btu per hour (1223 watts)
Maximum configuration: 21850 Btu per hour (6400 watts)
JCS 1200 Platform Features and Specifications
■ 7
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■
■
■
■
■
JCS 1200 Hardware Overview on page 4
JCS 1200 Platform Environmental Specifications on page 187
AC Power Supply Electrical Specifications for the JCS 1200 Platform on page 190
Power Consumption for an AC-Powered JCS 1200 Platform on page 190
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
8 ■
JCS 1200 Platform Features and Specifications
Chapter 2
Hardware Component Overview
This chapter describes the hot-swappable components for the JCS 1200 platform in the following topics:
■
■
■
■
■
■
■
■
■
■
Major Components of the JCS 1200 Platform on page 9
JCS 1200 Alarm Panel Module Overview on page 12
JCS 1200 Fan Module Overview on page 14
JCS 1200 Management Module Overview on page 15
JCS 1200 Media Tray Overview on page 18
JCS 1200 MUX Card Overview on page 20
JCS 1200 Power Module Overview on page 22
JCS 1200 Routing Engine Overview on page 24
JCS 1200 Switch Module Overview on page 27
JCS 1200 Power Connectors on page 30
Major Components of the JCS 1200 Platform
Figure 3 on page 10 and Figure 4 on page 11 show the locations of the major
components in the JCS 1200 platform. These modules supply common functions to the Routing Engines that are installed in the bays in the front of the JCS 1200 platform.
Major Components of the JCS 1200 Platform
■ 9
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 3: Exploded Front View of Components in the JCS 1200 Platform
10 ■
Major Components of the JCS 1200 Platform
Chapter 2: Hardware Component Overview
Figure 4: Exploded Rear View of Components in the JCS 1200 Platform
NOTE: The JCS 1200 platform comes with two DC power boxes or two AC power boxes. The power boxes cannot be changed from the type that is already installed.
Related Topics
■
■
■
■
■
■
■
■
■
■
JCS 1200 Hardware Overview on page 4
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Fan Module Description on page 14
JCS 1200 Management Module Description on page 15
JCS 1200 Media Tray Description on page 18
JCS 1200 MUX Card Description on page 21
JCS 1200 Power Module Description on page 22
JCS 1200 Routing Engine Description on page 24
JCS 1200 Switch Module Description on page 27
JCS 1200 Power Connectors on page 30
Major Components of the JCS 1200 Platform
■ 11
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 Alarm Panel Module Overview
Topics include:
■
■
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Alarm Panel Module Connectors and LEDs on page 12
JCS 1200 Alarm Panel Module Description
The JCS 1200 platform comes with an alarm panel module that provides telecom relays and LED alarm status. You can also connect each Routing Engine to a console by connecting an external breakout cable to the serial port on the alarm panel module.
Related Topics
■
JCS 1200 Alarm Panel Module Connectors and LEDs on page 12
■
JCS 1200 Alarm Panel Module Interface Connector Electrical
■
■
■
■
Pinouts for the JCS 1200 Alarm Panel Interface Connector on page 213
JCS 1200 Alarm Panel Module Interface Connector Electrical
Replacing a JCS 1200 Alarm Panel Module or Module Filler on page 96
Locating the JCS 1200 Alarm Panel Serial Number on page 197
JCS 1200 Alarm Panel Module Connectors and LEDs
Figure 5 on page 12 shows the location of LEDs and connectors on the alarm panel
module.
Figure 5: JCS 1200 Alarm Panel Module LEDs and Connectors
12 ■
JCS 1200 Alarm Panel Module Overview
Chapter 2: Hardware Component Overview
The JCS 1200 alarm panel module consists of the following components:
■
■
Serial connector—This DB-60 connector provides direct access to the serial ports on each of the 12 Routing Engine bays. Use this connector to attach the optional serial port breakout cable and connect up to 12 local consoles.
Telco alarm connector—The alarm panel module provides one DB-15 connector
(male) for critical, major, and minor telco alarms. Each of the alarms has a relay that enables multiple system alarm indicators to be daisy-chained together.
■
LEDs—The alarm panel module contains seven LEDs. Table 8 on page 13
describes the function of each LED.
Table 8: JCS 1200 Alarm Panel Module LEDs
Name
Power-on
Location
Critical system fault
Major system fault
Minor system fault
Color
Green
–
State
On steadily
Off
Description
Power is present in the JCS 1200 platform.
The power subsystem, the power module, or the LED has failed.
CAUTION: If the power-on LED is off, it does not mean that no electrical current is present in the JCS 1200 platform. The LED might be defective. To remove all electrical current from the
JCS 1200 platform, you must disconnect all power cords from the rear power connectors.
Blue
Amber or red
NOTE: The color of this
LED can be set to amber or red through the management module.
On steadily or flashing
Indicates that the LED has been turned on by the system administrator, to aid in visually locating the JCS 1200 platform.
After the JCS 1200 platform has been located, you can have the system administrator turn off the location LED.
On steadily The JCS 1200 platform has a critical system fault. A critical system fault is an error or event that is detected by the system and that has a significant impact to the system. In this case, the system cannot continue to operate or is operating in a nonredundant power or cooling configuration.
Amber or red
NOTE: The color of this
LED can be set to amber or red through the management module.
On steadily
Amber On steadily
The JCS 1200 platform has a major system fault. The system can continue to operate but may lose some functionality and performance.
FRU ready for removal
Alarm panel module fault
Blue
Amber
On steadily
On steadily
The JCS 1200 platform has a minor system fault. The system can continue to operate, usually without noticeable loss of functionality or performance.
It is safe to remove the alarm panel module from the JCS 1200 platform.
Indicates that there is a fault on the alarm panel module. The system can continue to operate, usually without the use of the components on the alarm panel module.
JCS 1200 Alarm Panel Module Connectors and LEDs
■ 13
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■
■
■
■
■
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Alarm Panel Module Connectors and LEDs on page 12
JCS 1200 Alarm Panel Module Interface Connector Electrical
Pinouts for the JCS 1200 Alarm Panel Interface Connector on page 213
Replacing a JCS 1200 Alarm Panel Module or Module Filler on page 96
Locating the JCS 1200 Alarm Panel Serial Number on page 197
JCS 1200 Fan Module Overview
Topics include:
■
■
JCS 1200 Fan Module Description on page 14
JCS 1200 Fan Module LED on page 14
JCS 1200 Fan Module Description
The JCS 1200 platform comes with four hot-swappable fan modules for cooling redundancy. The fan module speeds vary depending on the ambient air temperature within the JCS 1200 platform, which is reported by the media tray. If the ambient temperature is 77° F (25° C) or below, the JCS 1200 platform fan modules run at their minimum rotational speed. If the ambient temperature is above 77° F (25° C), the fan modules run faster, increasing their speed as required to control internal
JCS 1200 platform temperature. Each fan module contains two fans operating as a pair in a series. If one fan fails, the remaining fan runs at full speed and continues to cool the JCS 1200 platform. Replace a failed fan module as soon as possible to restore cooling redundancy.
NOTE: While the JCS 1200 is operating, remove only one fan module at a time.
Removing two fan modules might cause the JCS 1200 platform to overheat. If you remove two fan modules while the JCS 1200 platform is operating, the management module powers off all Routing Engines.
Related Topics
■
■
■
■
JCS 1200 Fan Module LED on page 14
Replacing a JCS 1200 Fan Module on page 116
Troubleshooting JCS 1200 Fan Module Problems on page 86
Locating the JCS 1200 Fan Module Serial Number on page 198
JCS 1200 Fan Module LED
Figure 6 on page 15 shows the location of the LED on the fan module.
14 ■
JCS 1200 Fan Module Overview
Chapter 2: Hardware Component Overview
Figure 6: JCS 1200 Fan Module
Table 9 on page 15 describes the function of the LED.
Table 9: JCS 1200 Fan Module LED
Name
Fan module error
Color
Amber
State
On steadily
Description
An error has been detected in the fan module or power to the fan module is not present. The system-error LEDs on the
JCS 1200 alarm panel are also lit.
Related Topics
■
■
■
■
JCS 1200 Fan Module Description on page 14
Replacing a JCS 1200 Fan Module on page 116
Troubleshooting JCS 1200 Fan Module Problems on page 86
Locating the JCS 1200 Fan Module Serial Number on page 198
JCS 1200 Management Module Overview
Topics include:
■
■
JCS 1200 Management Module Description on page 15
JCS 1200 Management Module Connectors and LEDs on page 16
JCS 1200 Management Module Description
The management module is a hot-swappable module that you use to configure and manage JCS 1200 components. See the JUNOS Protected System Domain Configuration
Guide for information about configuring the management module.
You can order the JCS 1200 platform with one or two hot-swappable management modules. Install the management modules in management module bay 1 and management module bay 2 to provide redundancy.
JCS 1200 Management Module Overview
■ 15
Juniper Control System (JCS) 1200 Platform Hardware Guide
NOTE: When you install a management module into the JCS 1200 platform, a management module interposer must be installed into the bay before installing the management module.
Related Topics
■
■
■
■
■
■
JCS 1200 Management Module Connectors and LEDs on page 16
Replacing a JCS 1200 Management Module Filler Tray on page 127
Replacing a JCS 1200 Management Module Interposer on page 128
Replacing a JCS 1200 Management Module or Module Filler on page 124
Troubleshooting JCS 1200 Management Module Problems on page 87
Locating the JCS 1200 Management Module Serial Number on page 199
JCS 1200 Management Module Connectors and LEDs
Figure 7 on page 16 shows the input and output connectors on the management
module.
Figure 7: JCS 1200 Management Module Input and Output Connectors
Figure 8 on page 17 shows the location of LEDs and controls on the management
module.
16 ■
JCS 1200 Management Module Connectors and LEDs
Chapter 2: Hardware Component Overview
Figure 8: JCS 1200 Management Module LEDs and Controls
The management module consists of the following components:
■
Serial connector—Use this connection to configure and manage the JCS 1200 components over a serial line through the management module CLI. This connector provides local access to the CLI and any Routing Engine. For example, you can connect a notebook computer to the serial connector and a terminal emulator program to configure the IP addresses, user accounts, and other management settings through the CLI user interface. See the JUNOS Protected
System Domain Configuration Guide for more information.
■
■
■
■
Video connector—The video connector is not supported.
Console (Ethernet) connector—Use this connector for a remote Ethernet connection to a network management station on the network.
Two USB ports for mouse and keyboard—The USB ports are not supported.
Reset button—When you press this button, the blowers operate at full speed while the management module is initializing.
■
The reset button provides the following functions:
■
Press and release the reset button to restart the management module.
■
Press and hold the reset button for 8 seconds to restore the management module to factory default settings.
LEDs—There are five LEDs on the management module that provide status information about the management module and remote management connection.
Table 10 on page 18 describes the functions of these LEDs (see
JCS 1200 Management Module Connectors and LEDs
■ 17
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 10: JCS 1200 Management Module LEDs
Name Color State Description
Power-on
Active
Management module error
Ethernet Link (LINK)
Green
Green
Amber
Green
On steadily
On steadily
On steadily
On steadily
The management module has power.
The management module is actively controlling the JCS 1200 platform. Only one management module actively controls the
JCS 1200 platform. If two management modules are installed in the JCS 1200 platform, this LED is lit on only one module.
An error has been detected in the management module. When this LED is lit, the JCS 1200 system error LED is also lit on the alarm panel.
There is an active connection through the Ethernet port to the network.
There is activity through the port over the network link.
Ethernet activity
(TX/RX)
Green Flashing
Related Topics
■
■
■
■
■
■
JCS 1200 Management Module Description on page 15
Replacing a JCS 1200 Management Module Filler Tray on page 127
Replacing a JCS 1200 Management Module Interposer on page 128
Replacing a JCS 1200 Management Module or Module Filler on page 124
Troubleshooting JCS 1200 Management Module Problems on page 87
Locating the JCS 1200 Management Module Serial Number on page 199
JCS 1200 Media Tray Overview
Topics include:
■
■
JCS 1200 Media Tray Description on page 18
JCS 1200 Media Tray Connectors and LEDs on page 19
JCS 1200 Media Tray Description
Figure 9 on page 19 shows the JCS 1200 media tray.
18 ■
JCS 1200 Media Tray Overview
Chapter 2: Hardware Component Overview
Figure 9: JCS 1200 Media Tray
The media tray is a hot-swappable module that provides two USB connectors for use by the Routing Engines, error LEDs, an ambient air temperature sensor and a pressure sensor for use by the management module, and two compact flash bays.
You can order the JCS 1200 platform with one or two hot-swappable media trays.
The media trays can be installed in media tray bay 1 and media tray bay 2 to provide redundancy.
Related Topics
■
JCS 1200 Media Tray Connectors and LEDs on page 19
■
Replacing a JCS 1200 Media Tray on page 128
■
■
Troubleshooting JCS 1200 Media Tray Problems on page 88
Locating the JCS 1200 Media Tray Serial Number on page 200
JCS 1200 Media Tray Connectors and LEDs
Figure 10 on page 19 shows the location of LEDs and connectors on the media tray.
Figure 10: JCS 1200 Media Tray Components
Each media tray consists of the following components:
■
■
USB connectors—Use these connectors to upgrade software on the Routing
Engines. The attached USB device must be compatible with USB v2.0, or earlier.
LED panel—The LEDs on the media tray provide status information for your
JCS 1200 platform. Table 11 on page 20 describes the functions of these LEDs.
JCS 1200 Media Tray Connectors and LEDs
■ 19
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 11: JCS 1200 Media Tray LEDs
Name
Power-on
Color
Green
–
Location Blue
State
On steadily
Off
Description
Power is present in the JCS 1200 platform.
The power subsystem, the power module, or the LED has failed.
CAUTION: If the power-on LED is off, it does not mean that electrical current is not present in the JCS 1200 platform. The
LED might be defective. To remove all electrical current from the JCS 1200 platform, you must disconnect all power cords from all power input connectors.
Flashing or on steadily
Indicates that this LED has been turned on by the system administrator to aid in visually locating the JCS 1200 platform.
NOTE: You can turn off the location LED through the management module.
Critical system fault (CRT)
Amber or red
NOTE: The color of this
LED can be set to amber or red through the management module.
On steadily
Major system fault (MJR)
Amber or red
NOTE: The color of this
LED can be set to amber or red through the management module.
On steadily
The JCS 1200 platform has a critical system fault. A critical system fault is an error or event that is detected by the system and that has a significant impact to the system. In this case, the system cannot continue to operate or is operating in a nonredundant power or cooling configuration.
The JCS 1200 platform has a major system fault. The system can continue to operate but might lose some function and performance.
Minor system fault (MNR)
Amber
Media tray fault Amber
On steadily
On steadily
The JCS 1200 platform has a minor system fault. The system can continue to operate, usually without noticeable loss of functionality or performance.
There is a fault on the media tray. The system can continue to operate, usually without the use of the components on the media tray.
Related Topics
■
■
■
■
JCS 1200 Media Tray Description on page 18
Replacing a JCS 1200 Media Tray on page 128
Troubleshooting JCS 1200 Media Tray Problems on page 88
Locating the JCS 1200 Media Tray Serial Number on page 200
JCS 1200 MUX Card Overview
Topics include:
■
■
JCS 1200 MUX Card Description on page 21
JCS 1200 MUX Card LEDs on page 21
20 ■
JCS 1200 MUX Card Overview
Chapter 2: Hardware Component Overview
JCS 1200 MUX Card Description
Related Topics
The JCS 1200 platform comes with two hot-swappable multiplexer (MUX) cards for redundancy. The MUX card controls the USB connectors, console redirection, and status LEDs on the JCS 1200 platform. Replace a MUX card as soon as possible, to restore redundancy.
■
JCS 1200 MUX Card LEDs on page 21
■
Replacing a JCS 1200 MUX Card on page 131
■
Locating the JCS 1200 MUX Card Serial Number on page 201
JCS 1200 MUX Card LEDs
Figure 11 on page 21 shows the location of the LEDs on the JCS 1200 MUX card.
Figure 11: JCS 1200 MUX Card LEDs
MUX card fault
The functions of the MUX card LEDs are described in Table 12 on page 21.
Table 12: JCS 1200 MUX Card LEDs
Name
FRU ready for removal
Color
Blue
State
On steadily
Amber On steadily
Description
Indicates that it is safe to remove the device from the
JCS 1200 platform.
There is a fault on the MUX card. The system can continue to operate, usually without the use of the components on the MUX card.
NOTE: When removing the MUX card, you must install another MUX card in its place to maintain proper cooling in the JCS 1200 platform.
Related Topics
■
■
JCS 1200 MUX Card Description on page 21
Replacing a JCS 1200 MUX Card on page 131
JCS 1200 MUX Card Description
■ 21
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
Locating the JCS 1200 MUX Card Serial Number on page 201
JCS 1200 Power Module Overview
Topics include:
■
■
JCS 1200 Power Module Description on page 22
JCS 1200 Power Module LEDs on page 23
JCS 1200 Power Module Description
Figure 12 on page 22 shows the AC and DC power modules.
Figure 12: Top: AC Power Modules; Bottom: DC Power Modules
The JCS 1200 platform is configured with four hot-swappable power modules.
Power modules are required in bays 1 and 2. They supply power to Routing Engine bays 1 through 6, media trays 1 and 2, management module bays 1 and 2, and switch module bays 1 through 4.
Power modules are required in power module bays 3 and 4 if you install Routing
Engines in Routing Engine bays 7 through 12 or if you install switch modules in any of switch module bays 7 through 10.
22 ■
JCS 1200 Power Module Overview
Chapter 2: Hardware Component Overview
Each pair of power modules operates as a redundant pair. If either power module fails, the remaining power module continues to supply power, but there is no redundancy; the failed power module must be replaced as soon as possible.
Related Topics
■
JCS 1200 Power Module LEDs on page 23
■
■
■
■
Replacing a JCS 1200 Power Module on page 138
Replacing a JCS 1200 Power Box on page 134
Troubleshooting JCS 1200 Power Problems on page 89
Locating the JCS 1200 Power Module Serial Number on page 202
JCS 1200 Power Module LEDs
Figure 13 on page 23 shows the LEDs on each power module.
Figure 13: JCS 1200 Power Module LEDs
The LEDs on each power module indicate the condition of the power module and fan pack.
NOTE: The orientation of the power module that is shown in Figure 13 on page 23
is for one of the top power modules. Modules in the bottom power module bays are rotated 180°.
Power module error Amber
Fan error
Table 13 on page 23 describes the functions of the LEDs on the power modules.
Table 13: JCS 1200 Power Module LEDs
Name
Input power
Color
Green
State
On steadily
Amber
On steadily
On steadily
Description
The input from the external power source connected to the power module is present and within specifications. During typical operation, both the input power and output power LEDs are lit.
A power module failure has occurred, and the power module is not operating within specifications.
A fan pack has failed and is not operating within specifications.
JCS 1200 Power Module LEDs
■ 23
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 13: JCS 1200 Power Module LEDs (continued)
Name
Output power
Color
Green
State
On steadily
Description
The output from the power module to the other components and
Routing Engines is present and within specifications. During typical operation, both the input power and output power LEDs are lit.
Related Topics
■
■
■
■
■
JCS 1200 Power Module Description on page 22
Replacing a JCS 1200 Power Module on page 138
Replacing a JCS 1200 Power Box on page 134
Troubleshooting JCS 1200 Power Problems on page 89
Locating the JCS 1200 Power Module Serial Number on page 202
JCS 1200 Routing Engine Overview
Topics include:
■
■
JCS 1200 Routing Engine Description on page 24
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
JCS 1200 Routing Engine Description
Figure 14 on page 24 shows a JCS 1200 Routing Engine.
Figure 14: JCS 1200 Routing Engine
24 ■
JCS 1200 Routing Engine Overview
Chapter 2: Hardware Component Overview
The JCS 1200 platform provides 12 bays for Routing Engines. A Routing Engine is a hot-swappable independent server with its own processors, memory, storage, network controllers, operating system, and applications. The Routing Engine is installed in a bay in the JCS 1200 platform and shares power, fans, switches, and ports with other
Routing Engines.
NOTE: JCS 1200 Routing Engines can be used only on the JCS 1200 platform.
The Ethernet controllers on the Routing Engine communicate with the network through the Ethernet-compatible switch modules on the JCS 1200 platform. Network signals to and from the Routing Engine are automatically routed to a same-network-interface switch module through circuitry in the JCS 1200 platform.
Related Topics
■
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
■
Powering On a JCS 1200 Routing Engine on page 73
■
■
■
Powering Off a JCS 1200 Routing Engine on page 74
Replacing a JCS 1200 Routing Engine on page 140
Locating the JCS 1200 Routing Engine Serial Number on page 203
JCS 1200 Routing Engine Control Panel Buttons and LEDs
NOTE: The control panel door is shown in the closed position in Figure 15 on page 25.
To access the power control button, you must open the control panel door.
Figure 15: JCS 1200 Routing Engine Control Panel
KVM select button
Activity LED
Mastership LED
Information LED
Blade-error LED
Media-tray select button
Power-control button
Power-on LED
JCS 1200 Routing Engine Control Panel Buttons and LEDs
■ 25
Juniper Control System (JCS) 1200 Platform Hardware Guide
Each Routing Engine consists of the following components:
■
Keyboard/video/mouse (KVM) select button—This button is not supported.
■
Media tray select button—Press this button to associate the shared media tray
(removable media drives and front panel USB ports) with the Routing Engine.
The LED on the button flashes while the request is being processed and then is lit when ownership of the media tray has been transferred to the Routing Engine.
It can take approximately 20 seconds for the operating system in the Routing
Engine to recognize the media tray.
■
■
If there is no response when you press the media tray select button, you can use the management module to determine whether local control has been enabled on the Routing Engine.
Power-control button—Press this button to power on or power off the Routing
Engine.
LEDs—There are five LEDs that indicate the status of the Routing Engine.
Table 14 on page 26 describes the functions of these LEDs.
Table 14: JCS 1200 Routing Engine LEDs
Name
Activity
Mastership
Information
Blade-error
Power-on
Color
Green
Blue
Amber
Amber
Green
Green
Green
State
On steadily
On steadily
On steadily
On steadily
Flashing rapidly
Flashing slowly
On steadily
Description
There is activity on the hard disk drive or network.
Indicates mastership in a redundant Routing Engine pair.
A system error in the Routing Engine has been placed in the management module event log. The information LED can be turned off through the management module
A system error has occurred in the Routing Engine (blade). The blade-error LED turns off only after the error is corrected.
The service processor (BMC) on the Routing Engine is communicating with the management module.
The Routing Engine has power but is not turned on.
The Routing Engine has power and is turned on.
Related Topics
■
■
■
■
■
JCS 1200 Routing Engine Description on page 24
Powering On a JCS 1200 Routing Engine on page 73
Powering Off a JCS 1200 Routing Engine on page 74
Replacing a JCS 1200 Routing Engine on page 140
Locating the JCS 1200 Routing Engine Serial Number on page 203
26 ■
JCS 1200 Routing Engine Control Panel Buttons and LEDs
Chapter 2: Hardware Component Overview
JCS 1200 Switch Module Overview
Topics include:
■
■
JCS 1200 Switch Module Description on page 27
JCS 1200 Switch Module Components and LEDs on page 27
JCS 1200 Switch Module Description
Figure 16 on page 27 shows the JCS 1200 switch module.
Figure 16: JCS 1200 Switch Module
The JCS 1200 platform supports two hot-swappable switch module bays (see “JCS 1200
Hardware Overview” on page 4 for the location of the switch module bays). You
must install a switch module interposer into the bay before you install a switch module into the JCS 1200 platform.
NOTE: High-speed switch modules are not supported.
Related Topics
■
■
■
■
■
JCS 1200 Switch Module Components and LEDs on page 27
Replacing a JCS 1200 Switch Module Filler Tray on page 145
Replacing a JCS 1200 Switch Module Interposer on page 146
Replacing a JCS 1200 Switch Module or Module Filler on page 143
Locating the JCS 1200 Switch Module Serial Number on page 205
JCS 1200 Switch Module Components and LEDs
Figure 17 on page 28 shows the components on the switch module.
JCS 1200 Switch Module Overview
■ 27
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 17: JCS 1200 Switch Module Components
The switch module consists of the following components:
■
■
■
One RS-232 console port that provides an additional means to install software and configure the switch module. This USB-style connector enables connection of a special serial cable to the switch module.
Six external copper 1000Base-T Ethernet ports for 10/100/1000 Mbps connections to the T-series routing platform. These ports are identified as EXT1, EXT2, EXT3,
EXT4, EXT5, and EXT6 in the switch configuration menus and are labeled
1 through
6
(from top to bottom) on the switch module. You can use RJ-45 ports labeled 1 through 3 to connect up to three T-series routing platforms running
JUNOS Release 9.2 to the JCS 1200 platform. The RJ-45 ports labeled 4 and 5 on the switch module are reserved for future use. You can use the RJ-45 port labeled
6 to manage the switch module.
Eight LEDs that indicate the status of the switch module and the network (see
28 ■
JCS 1200 Switch Module Components and LEDs
Figure 18: JCS 1200 Switch Module LEDs
Chapter 2: Hardware Component Overview
The functions of the switch module LEDs are described in Table 15 on page 29.
Table 15: JCS 1200 Switch Module LEDs
Name
OK
Gigabit Ethernet switch module error (fault) (!)
Amber
Ethernet link (LINK)
Ethernet activity
(Tx/Rx)
Color
Green
Green
Green
State
On steadily
On steadily
Description
The switch module has passed the power-on self-test
(POST) with no critical faults and is operational.
The switch module has failed the POST or detected an operational fault.
NOTE: When the Gigabit Ethernet switch module error
LED is lit, the system-error LED on the alarm panel is also lit
On steadily There is a connection (or link) to a device using that connector.
Flashing
NOTE: The flash frequency is proportional to the amount of traffic on the network link.
Data is being transmitted or received (that is, activity is occurring) between that port and another device on the network link.
Related Topics
■
■
■
■
■
JCS 1200 Switch Module Description on page 27
Replacing a JCS 1200 Switch Module Filler Tray on page 145
Replacing a JCS 1200 Switch Module Interposer on page 146
Replacing a JCS 1200 Switch Module or Module Filler on page 143
Locating the JCS 1200 Switch Module Serial Number on page 205
JCS 1200 Switch Module Components and LEDs
■ 29
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 Power Connectors
Connect a power cord from each power connector to an appropriate power source.
Related Topics
■
JCS 1200 AC Power Electrical Safety Guidelines and Warnings on page 174
■
■
■
Connecting the JCS 1200 AC Platform to AC Power on page 62
JCS 1200 DC Power Electrical Safety Guidelines on page 175
Connecting the JCS 1200 DC Platform to DC Power on page 63
30 ■
JCS 1200 Power Connectors
Part 2
Initial Installation
■
■
■
■
■
■
Preparing the Site for JCS 1200 Platform Installation on page 33
Unpacking the JCS 1200 Platform on page 39
Installing the JCS 1200 Mounting Hardware on page 43
Installing the JCS 1200 Platform on page 49
Connecting the JCS 1200 Platform on page 59
Configuration Guidelines on page 81
Initial Installation
■ 31
Juniper Control System (JCS) 1200 Platform Hardware Guide
32 ■
Initial Installation
Chapter 3
Preparing the Site for JCS 1200 Platform
Installation
Topics include:
■
■
■
■
■
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
Site Preparation Checklist for the JCS 1200 Platform on page 33
JCS 1200 Cabinet Requirements on page 34
JCS 1200 Rack Requirements on page 35
JCS 1200 Clearance Requirements for Airflow and Hardware
Overview of Preparing the Site for JCS 1200 Platform Installation
Related Topics
■
■
To prepare your site for installation, review the guidelines and requirements in the following topics:
■
■
■
General Safety Guidelines and Warnings for the JCS 1200 Platform on page 151
JCS 1200 Cabinet Size and Clearance Requirements on page 34
JCS 1200 Cabinet Airflow Requirements on page 35
■
■
■
JCS 1200 Rack Size and Strength on page 36
JCS 1200 Connection to Building Structure on page 37
JCS 1200 Clearance Requirements for Airflow and Hardware
Site Preparation Checklist for the JCS 1200 Platform on page 33
JCS 1200 Platform Environmental Specifications on page 187
Site Preparation Checklist for the JCS 1200 Platform
The checklist in Table 16 on page 34 summarizes the tasks you need to perform
when preparing a site for platform installation.
Overview of Preparing the Site for JCS 1200 Platform Installation
■ 33
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 16: Site Preparation Checklist
Item or Task
Environment
Verify that environmental factors such as temperature and humidity do not exceed platform tolerances.
Power
Locate sites for connection of system grounding.
For More Information
“JCS 1200 Platform Environmental
Performed By Date
Calculate the power consumption and requirements.
■
■
Rack
Verify that your rack meets the minimum requirements for the installation of the platform.
■
■
Plan rack location, including required space clearances.
If a rack is used, secure rack to floor and building structure.
Related Topics
■
■
“JCS 1200 Clearance Requirements for Airflow and Hardware
“JCS 1200 Connection to Building
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
JCS 1200 Platform Environmental Specifications on page 187
JCS 1200 Cabinet Requirements
The JCS 1200 platform can be installed in a standard 800-mm (or larger) enclosed cabinet. The following topics describe cabinet requirements:
■
■
JCS 1200 Cabinet Size and Clearance Requirements on page 34
JCS 1200 Cabinet Airflow Requirements on page 35
JCS 1200 Cabinet Size and Clearance Requirements
The minimum size cabinet that can accommodate the JCS 1200 platform is 600 mm wide and 800 mm deep. A cabinet larger than the minimum requirement provides better airflow and reduces the chance of overheating. To accommodate a single
JCS 1200 platform, the cabinet must be at least 12 U (21 in. (53.34 cm)) high.
34 ■
JCS 1200 Cabinet Requirements
Chapter 3: Preparing the Site for JCS 1200 Platform Installation
The minimum front and rear clearance requirements depend on the mounting configuration you choose. The minimum total clearance inside the cabinet is 30.70 in.
between the inside of the front door and the inside of the rear door.
NOTE: If you mount the JCS 1200 platform in a cabinet, be sure that sufficient room is provided for cable management and cables.
Related Topics
■
■
■
■
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
Site Preparation Checklist for the JCS 1200 Platform on page 33
JCS 1200 Platform Environmental Specifications on page 187
JCS 1200 Cabinet Airflow Requirements on page 35
JCS 1200 Cabinet Airflow Requirements
Related Topics
■
■
■
■
When you mount the JCS 1200 platform in a cabinet, you must ensure that ventilation through the cabinet is sufficient to prevent overheating. Consider the following list of requirements when you plan for chassis cooling:
■
■
■
Ensure that the cool air supply you provide through the cabinet can adequately dissipate the thermal output of the JCS 1200 platform. For information about the JCS 1200 platform's environmental specifications, including its operating
temperature and thermal output, see “JCS 1200 Platform Environmental
Ensure that the cabinet allows the chassis hot exhaust air to exit from the cabinet without recirculating into the JCS 1200 platform. An open cabinet (without a top or doors) that employs hot air exhaust extraction from the top allows the best airflow through the chassis. If the cabinet contains a top or doors, perforations in these elements assist with removing the hot air exhaust.
Route and dress all cables to minimize the blockage of airflow to and from the chassis.
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
Site Preparation Checklist for the JCS 1200 Platform on page 33
JCS 1200 Platform Environmental Specifications on page 187
JCS 1200 Cabinet Size and Clearance Requirements on page 34
JCS 1200 Rack Requirements
The JCS 1200 platform can be installed in a rack. Many types of racks are acceptable, including four-post (telco) racks and open-frame racks. An example of an open-frame
rack appears in Figure 19 on page 37.
JCS 1200 Cabinet Airflow Requirements
■ 35
Juniper Control System (JCS) 1200 Platform Hardware Guide
The following topics describe rack requirements:
■
■
JCS 1200 Rack Size and Strength on page 36
JCS 1200 Connection to Building Structure on page 37
JCS 1200 Rack Size and Strength
The JCS 1200 platform is designed for installation in a 19-in. rack as defined in
Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association ( http://www.eia.org
).
With the use of adapters, the JCS 1200 platform is designed to fit into a 600-mm-wide rack or cabinet , as defined in the four-part Equipment Engineering (EE); European
telecommunications standard for equipment practice (document numbers ETS 300
119-1 through 119-4) published by the European Telecommunications Standards
Institute ( http://www.etsi.org
). Use approved wing devices to narrow the opening between the rails.
The rack rails must be spaced widely enough to accommodate the JCS 1200 chassis's external dimensions: 21 in. (53.34 cm) high, 25.64 in. (65.1 cm) deep, and
17.43 in. (44.3 cm) wide. The outer edges of the mounting brackets extend the width to 19 in. (48.3 cm). The spacing of rails and adjacent racks must also allow for the
clearances around the JCS 1200 platform and rack that are specified in “JCS 1200
Clearance Requirements for Airflow and Hardware Maintenance” on page 38.
For instructions about installing the mounting hardware, see “Installing the JCS 1200
Mounting Hardware for an Open-Frame Rack” on page 46 or “Installing the JCS 1200
Mounting Hardware for a Four-Post Rack or Cabinet” on page 44.
The chassis height of 21 in. (53.34 cm) is approximately 20 U. A U is the standard rack unit defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D) published by the Electronics Industry Association.
The rack must be strong enough to support the weight of the fully configured platform, up to 350 lb (158.8 kg). If you stack two fully configured platforms in one rack, it must be capable of supporting about 878 lb (399.1 kg).
36 ■
JCS 1200 Rack Size and Strength
Chapter 3: Preparing the Site for JCS 1200 Platform Installation
Figure 19: Typical Open-Frame Rack
Related Topics
■
■
■
■
■
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
Site Preparation Checklist for the JCS 1200 Platform on page 33
JCS 1200 Platform Environmental Specifications on page 187
JCS 1200 Connection to Building Structure on page 37
JCS 1200 Clearance Requirements for Airflow and Hardware
JCS 1200 Connection to Building Structure
Always secure the rack to the structure of the building. If your geographical area is subject to earthquakes, bolt the rack to the floor. For maximum stability, also secure the rack to ceiling brackets.
Related Topics
■
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
■
■
Site Preparation Checklist for the JCS 1200 Platform on page 33
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
JCS 1200 Connection to Building Structure
■ 37
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
JCS 1200 Rack Size and Strength on page 36
JCS 1200 Clearance Requirements for Airflow and Hardware
JCS 1200 Clearance Requirements for Airflow and Hardware Maintenance
When planning the installation site, allow sufficient clearance around the rack (see
■
■
■
For the cooling system to function properly, the airflow around the chassis must be unrestricted.
For service personnel to remove and install hardware components, there must be adequate space at the front and back of the platform. Allow at least
30 in. (72.6 cm) in front of the rack and 24 in. (61.0 cm) behind the rack.
Airflow vents provided along the sides of the chassis must remain open and uncovered for proper cooling.
Figure 20: JCS 1200 Chassis Dimensions and Clearance Requirements
Related Topics
■
■
■
■
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
Site Preparation Checklist for the JCS 1200 Platform on page 33
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
JCS 1200 Rack Size and Strength on page 36
38 ■
JCS 1200 Clearance Requirements for Airflow and Hardware Maintenance
Chapter 4
Unpacking the JCS 1200 Platform
This chapter describes how to prepare to install the JCS 1200 platform. Topics include:
■
■
■
Tools and Parts Required to Unpack the JCS 1200 Platform on page 39
Unpacking the JCS 1200 Platform on page 40
Verifying Parts Received for the JCS 1200 Platform on page 41
Tools and Parts Required to Unpack the JCS 1200 Platform
Related Topics
■
■
To unpack the JCS 1200 platform and prepare for installation, you need the following tools:
■
■
Phillips (+) screwdriver, number 2
1/2-in. or 13-mm open-end or socket wrench to remove bracket bolts from the shipping pallet
■
Blank panels to cover any slots not occupied by a component
Unpacking the JCS 1200 Platform on page 40
Verifying Parts Received for the JCS 1200 Platform on page 41
Tools and Parts Required to Unpack the JCS 1200 Platform
■ 39
Juniper Control System (JCS) 1200 Platform Hardware Guide
Unpacking the JCS 1200 Platform
The platform is shipped in a cardboard box strapped securely to a wood pallet. Plastic straps secure the top and bottom in place. The JCS 1200 chassis is bolted to this pallet. Quick Start installation instructions and a cardboard accessory box are also included in the shipping container.
The shipping container measures 32.5 in. (82.6 cm) high, 35 in. (88.9 cm) wide, and
27 in. (68.6 cm) deep. The total weight of the container containing the JCS 1200 platform and accessories can range from 329 lb (149.6 kg) to 350 lb (158.8 kg).
NOTE: The JCS 1200 platform is maximally protected inside the shipping crate. Do not unpack it until you are ready to begin installation.
To unpack the JCS 1200 platform:
1.
Move the shipping container to a staging area as close to the installation site as possible, where you have enough room to remove the components from the chassis. While the chassis is bolted to the pallet, you can use a forklift or pallet jack to move it.
2.
3.
Position the shipping container with the wooden pallet on the bottom and the corrugated cardboard facing up.
Remove the plastic straps that hold the top and bottom of the shipping container in place.
4.
5.
6.
Remove the corrugated container cover and set it aside.
Remove the foam covering the top of the JCS 1200 platform.
Remove the accessory box and the Quick Start documentation.
7.
8.
Verify the parts received against the lists in “Verifying Parts Received for the
JCS 1200 Platform” on page 41.
Remove the vapor corrosion inhibitor (VCI) packs attached to the pallet. Be careful not to break the VCI packs open.
9.
To remove the bolts and screws from the brackets holding the chassis on the pallet, use a 1/2-in. socket wrench and a number 2 Phillips screwdriver.
10.
Store the brackets and bolts inside the accessory box.
11.
Save the corrugated shipping container cover, pallet, and packing materials in case you need to move or ship the JCS 1200 platform later. The packaging utilizes recyclable materials in the design and should be disposed of properly. Recycle packaging according to your local, state, or country specific laws and regulations.
Related Topics
To proceed with the installation, see:
■
■
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Platform Using a Lift on page 51
40 ■
Unpacking the JCS 1200 Platform
Chapter 4: Unpacking the JCS 1200 Platform
Verifying Parts Received for the JCS 1200 Platform
A packing list is included in each shipment. Check the parts in the shipment against the items on the packing list. The packing list specifies the part numbers and descriptions of each part in your order.
If any part is missing, contact a Juniper Networks customer service representative.
A fully configured JCS 1200 platform contains the JCS 1200 platform chassis with
installed components, listed in Table 17 on page 41, and an accessory box, which
contains the parts listed in Table 18 on page 42. The parts shipped with your JCS 1200
platform can vary.
Table 17: Parts List for a Fully Configured JCS 1200 Platform
Component
Chassis
Chassis bezel
Cable management collar
Routing Engines
Management modules
Management module interposer trays
Media trays
MUX cards
Switch modules
Switch module interposer trays
Power modules
Air filters
Quick Start installation instructions
Large mounting shelf
Small mounting shelf
Blank panels for slots without components installed
Quantity
12
1
1
1
1
1
2
1
1
4
2
2
1
1
1
One blank panel for each slot not occupied by a component
Verifying Parts Received for the JCS 1200 Platform
■ 41
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 18: JCS 1200 Accessory Box Parts List
Part Quantity
Front rack-mount bracket
Mid rack-mount bracket
Rack-mount screws M5 x12 mm
Serial port breakout cable, with 14 RJ-45 jacks to female
DB-9, to connect the JCS 1200 platform through the serial port
1
RJ-45 CPU adapters for use with the serial port breakout cable
12
RJ-45 ETH adapters for use with the switch module
RJ-45 AMM adapters for use with the management module
Label, accessories contents, JCS 1200
Small rear shelf for mounting the JCS 1200 platform in a four-post rack
2
2
1
1
2
2
8
Large front shelf for mounting the JCS 1200 platform in a four-post or two-post rack
1
Bottom cable manager 1
Top cable manager
Cable manager screws
Juniper Networks Compliance Form Letter, RoHS
Worldwide
Juniper Networks Product Warranty
1
7
1
1
1 End User License Agreement
Accessory box, 19" x 12" x 3" 1
Related Topics
■
■
Tools and Parts Required to Unpack the JCS 1200 Platform on page 39
Unpacking the JCS 1200 Platform on page 40
42 ■
Verifying Parts Received for the JCS 1200 Platform
Chapter 5
Installing the JCS 1200 Mounting
Hardware
This chapter describes the procedures for installing the mounting hardware:
■
■
■
■
JCS 1200 Platform Rack-Mounting Hardware on page 43
Rack Mounting Hole Locations for the JCS 1200 Platform on page 43
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
JCS 1200 Platform Rack-Mounting Hardware
The JCS 1200 platform can be installed in a four-post rack or cabinet or an open-frame rack. Before you install the JCS 1200 platform, you install the mounting hardware on the rack. The procedure for installing the mounting hardware depends on the type of rack.
All mounting options require that you to install the supplied large mounting shelf.
The supplied small mounting shelf is needed only for a four-post rack or cabinet.
Related Topics
■
Rack Mounting Hole Locations for the JCS 1200 Platform on page 43
■
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
■
■
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
Rack Mounting Hole Locations for the JCS 1200 Platform
Table 19 on page 44 specifies the holes in which you insert mounting screws (and
cage nuts if needed) to install the mounting hardware required in a four-post or two-post open-frame rack (an X indicates a mounting hole location). The hole distances are relative to one of the standard U divisions on the rack. The bottom of all mounting shelves is at 0.04 in. (0.02 U) above a U division.
JCS 1200 Platform Rack-Mounting Hardware
■ 43
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 19: Open-Frame Rack Mounting Hole Locations
Hole
18
15
12
9
30
27
24
21
2
1
6
3
17.26 in. (43.8 cm)
15.51 in. (39.4 cm)
13.76 in. (34.9 cm)
12.01 in. (30.5 cm)
10.26 in. (26.0 cm)
8.51 in. (21.6 cm)
6.76 in. (17.1 cm)
5.01 in. (12.7 cm)
3.26 in. (8.3 cm)
1.51 in. (3.8 cm)
0.88 in. (2.2 cm)
0.25 in. (0.6 cm)
Distance Above U Division
9.86 U
8.86 U
7.86 U
6.86 U
5.86 U
4.86 U
3.86 U
2.86 U
1.86 U
0.86 U
0.50 U
0.14 U
Large
Shelf
X
X
X
X
X
X
X
X
X
X
X
Chassis
Small
Shelf
X
X
X
X
X
X
X
X
Related Topics
■
■
■
■
JCS 1200 Platform Rack-Mounting Hardware on page 43
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or Cabinet
If you are installing the JCS 1200 platform in a four-post rack or cabinet, you must first install the large mounting shelf, followed by the small mounting shelf.
To install the mounting shelves (see Figure 21 on page 45):
1.
2.
3.
4.
If the rack rails require cage nuts, install cage nuts into the holes specified in
“Rack Mounting Hole Locations for the JCS 1200 Platform” on page 43 for the
large shelf on the front side of the rack rails.
On the front of each front rack rail, partially insert a mounting screw into the hole containing the lowest cage nut.
Install the large shelf on the front rack rails. Rest the bottom slot of each ear on a mounting screw.
Partially insert a mounting screw into holes 3, 6, 9, and 30 in each ear of the large shelf.
44 ■
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or Cabinet
Chapter 5: Installing the JCS 1200 Mounting Hardware
5.
6.
7.
8.
Tighten all the screws completely.
If the rack rails require cage nuts, install cage nuts into the holes specified in
“Rack Mounting Hole Locations for the JCS 1200 Platform” on page 43 for the
small shelf on the rear side of the rack rails.
On the back of each rear rack rail, partially insert a mounting screw into the hole containing the lowest cage nut.
Install the small shelf on the back rack rails. Rest the bottom slot of each ear on a mounting screw. The small shelf installs on the back of the rear rails, extending toward the center of the rack. The bottom of the small shelf should align with the bottom of the large shelf.
Partially insert screws into the open holes in the ears of the small shelf.
9.
10.
Tighten all the screws completely.
11.
On the sides of the JCS 1200 chassis, attach the front-mounting brackets using six of the mounting screws provided.
Figure 21: Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or Cabinet
Related Topics
■
■
■
JCS 1200 Platform Rack-Mounting Hardware on page 43
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
Rack Mounting Hole Locations for the JCS 1200 Platform on page 43
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or Cabinet
■ 45
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
■
Installing the JCS 1200 Platform Using a Lift on page 51
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack
If you are installing the JCS 1200 platform in a front-mount or center-mount open-frame rack, you must first install the large mounting shelf on the rack. The small mounting shelf is not needed.
For information about the holes in which you insert mounting screws (and cage-nuts if needed) to install the mounting hardware in an open-frame rack (an
X
indicates a
mounting hole location), see “Rack Mounting Hole Locations for the JCS 1200
Platform” on page 43. The hole distances are relative to one of the standard U
divisions on the rack. For reference, the bottom of all mounting shelves is at
0.04 in. (0.02 U) above a U division.
5.
6.
To install the large mounting shelf (see Figure 22 on page 47):
1.
If the rack rails require cage nuts, install cage nuts into the holes specified for the large shelf on the rear side of the rack rails.
2.
3.
If the rack rails require cage nuts, install cage nuts into the holes specified for the chassis on the front side of the rack rails
On the rear of each rack rail, partially insert a mounting screw into the highest hole specified for the large shelf.
4.
7.
Install the large shelf on the rack. Hang the shelf over the mounting screws using the keyhole slots located near the top of the large shelf flanges.
Partially insert screws into the open holes in the ears of the large shelf.
Tighten all the screws completely.
Attach the mounting brackets to the sides of the chassis:
■
If you plan to front-mount the chassis in an open-frame rack, attach the front-mounting brackets using six of the mounting screws provided.
■
If you plan to center-mount the chassis in an open-frame rack, attach the center-mounting brackets using the eight mounting screws provided.
46 ■
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack
Chapter 5: Installing the JCS 1200 Mounting Hardware
Figure 22: Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack
Related Topics
■
■
■
■
■
■
JCS 1200 Platform Rack-Mounting Hardware on page 43
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
Rack Mounting Hole Locations for the JCS 1200 Platform on page 43
Installing the JCS 1200 Platform Using a Lift on page 51
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack
■ 47
Juniper Control System (JCS) 1200 Platform Hardware Guide
48 ■
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack
Chapter 6
Installing the JCS 1200 Platform
This chapter provides instructions for installing the JCS 1200 platform into a rack and adding optional devices to your JCS 1200 platform.
■
■
■
Safety Requirements, Warnings, and Guidelines for Installing the JCS 1200
Installing the JCS 1200 Platform Using a Mechanical Lift on page 51
Installing the JCS 1200 Platform in a Rack Without a Lift on page 54
Safety Requirements, Warnings, and Guidelines for Installing the JCS 1200 Platform
To avoid harm to yourself or the platform as you install and maintain it, follow the guidelines for working with and near electrical equipment, as well as the safety procedures for working with networking equipment. However, providing an exhaustive set of guidelines for working with electrical equipment is beyond the scope of this manual.
For a discussion of how to make the installation site a safe environment, see the following topics:
■
■
■
Site Preparation Checklist for the JCS 1200 Platform on page 33
JCS 1200 Cabinet Size and Clearance Requirements on page 34
JCS 1200 Cabinet Airflow Requirements on page 35
■
■
■
JCS 1200 Rack Size and Strength on page 36
JCS 1200 Connection to Building Structure on page 37
JCS 1200 Clearance Requirements for Airflow and Hardware
For a list of safety warnings, see the following topics:
■
Definition of Safety Warning Levels on page 149
■
■
■
■
■
General Safety Guidelines and Warnings for the JCS 1200 Platform on page 151
Qualified Personnel Warning for the JCS 1200 Platform on page 152
Restricted Access Area Warning for the JCS 1200 Platform on page 152
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Fire Safety Requirements for the JCS 1200 Platform on page 155
Safety Requirements, Warnings, and Guidelines for Installing the JCS 1200 Platform
■ 49
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
■
■
■
■
■
■
■
■
■
■
■
JCS 1200 Chassis Lifting Guidelines on page 155
Installation Instructions Power Warning for the JCS 1200 Platform on page 156
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
Ramp Warning for the JCS 1200 Platform on page 160
Class 1 Laser Product Warning for the JCS 1200 Platform on page 160
Class 1 LED Product Warning for the JCS 1200 Platform on page 161
Laser Beam Warning for the JCS 1200 Platform on page 162
Radiation from Open Port Apertures Warning for the JCS 1200
Battery Handling Warning for the JCS 1200 Platform on page 164
Jewelry Removal Warning for the JCS 1200 Platform on page 165
Lightning Activity Warning for the JCS 1200 Platform on page 166
Operating Temperature Warning for the JCS 1200 Platform on page 167
Product Disposal Warning for the JCS 1200 Platform on page 168
Related Topics
■
■
For a list of electrical safety warnings, see the following topics:
■
In Case of an Electrical Accident on page 169
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
■
■
■
Grounded Equipment Warning for the JCS 1200 Platform on page 171
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
Multiple Power Supplies Disconnection Warning for the JCS 1200
■
■
■
TN Power Warning for the JCS 1200 Platform on page 173
Copper Conductors Warning for the JCS 1200 Platform on page 174
JCS 1200 AC Power Electrical Safety Guidelines and Warnings on page 174
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
DC Power Disconnection Warning for the JCS 1200 Platform on page 176
JCS 1200 DC Power Grounding Requirements and Warning on page 178
DC Power Wiring Sequence Warning for the JCS 1200 Platform on page 179
DC Power Wiring Terminations Warning for the JCS 1200 Platform on page 180
Installing the JCS 1200 Platform Using a Lift on page 51
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
50 ■
Safety Requirements, Warnings, and Guidelines for Installing the JCS 1200 Platform
Chapter 6: Installing the JCS 1200 Platform
Installing the JCS 1200 Platform Using a Mechanical Lift
Because of the JCS 1200 platform's size and weight—up to 350 lb (158.8 kg) depending on the configuration—we strongly recommend that you install the JCS 1200 platform using a mechanical lift. If you do not use a lift to install the JCS 1200
platform, see “Lifting the JCS 1200 Platform into the Rack or Cabinet” on page 56
for complete instructions to safely install the platform.
Before installing the JCS 1200 platform, you should have prepared your site and
reviewed the guidelines in “Overview of Preparing the Site for JCS 1200 Platform
Installation” on page 33. The “Site Preparation Checklist for the JCS 1200
Platform” on page 33 summarizes the tasks you need to perform when preparing a
site for platform installation. You also need to unpack the JCS 1200 platform from
the shipping container, as described in “Unpacking the JCS 1200
Topics include:
■
■
Tools Required to Install the JCS 1200 Platform Using a Mechanical Lift on page 51
Installing the JCS 1200 Platform Using a Lift on page 51
Tools Required to Install the JCS 1200 Platform Using a Mechanical Lift
Related Topics
■
■
■
To install the platform, you need the following tools:
■
■
■
Mechanical lift
Phillips (+) screwdriver, number 2
ESD grounding wrist strap
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
Installing the JCS 1200 Platform Using a Lift on page 51
Installing the JCS 1200 Platform Using a Lift
Before installing the JCS 1200 platform in the rack:
■
Read the safety information in “JCS 1200 Chassis Lifting Guidelines” on page 155.
■
Remove the JCS 1200 platform from the shipping container, as described in
“Unpacking the JCS 1200 Platform” on page 40.
■
Install the mounting hardware, as described in “Installing the JCS 1200 Mounting
Hardware for a Four-Post Rack or Cabinet” on page 44 or “Installing the JCS 1200
Mounting Hardware for an Open-Frame Rack” on page 46.
Installing the JCS 1200 Platform Using a Mechanical Lift
■ 51
Juniper Control System (JCS) 1200 Platform Hardware Guide
CAUTION: Before front mounting the JCS 1200 platform in a rack, have a qualified technician verify that the rack is strong enough to support the JCS 1200 platform's weight and is adequately supported at the installation site.
2.
3.
To install the JCS 1200 platform using a lift (see Figure 23 on page 53 and
1.
4.
5.
If you are installing the platform in an open-frame rack, ensure that the rack is in its permanent location and is secured to the building. Ensure that the installation site allows adequate clearance for both airflow and maintenance.
For details, see “Overview of Preparing the Site for JCS 1200 Platform
Load the platform onto the lift, making sure it rests securely on the lift platform.
Using the lift, position the platform in front of the rack or cabinet, centering it in front of the mounting shelves.
Lift the chassis approximately 0.75 in. (1.91 cm) above the surface of the mounting shelves and position it as close as possible to the shelves.
Carefully slide the platform onto the mounting shelves so that the bottom of the chassis and the mounting shelves overlap by approximately 2 in.
6.
7.
8.
9.
With two people pulling on the chassis from the rear of the rack or cabinet while two people push on the mounting flanges, slide the platform onto the mounting shelves until the front-mounting or center-mounting flanges contact the rack rails. The shelves ensure that the holes in the mounting flanges align with the holes in the rack rails.
Install a mounting screw into each of the open mounting holes in the rack-mounting brackets to fasten the chassis to the rack, starting from the bottom.
Move the lift away from the rack.
Visually inspect the alignment of the platform. If the platform is installed properly in the rack, all the mounting screws on one side of the rack should be aligned with the mounting screws on the opposite side, and the platform should be level.
52 ■
Installing the JCS 1200 Platform Using a Lift
Chapter 6: Installing the JCS 1200 Platform
Figure 23: Installing the JCS 1200 Platform in a Four-Post Rack
Installing the JCS 1200 Platform Using a Lift
■ 53
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 24: Installing the JCS 1200 Platform in an Open-Frame Rack
Related Topics
■
Tools Required to Install the JCS 1200 Platform Using a Mechanical Lift on page 51
Installing the JCS 1200 Platform in a Rack Without a Lift
Because of the JCS 1200 platform's size and weight—up to 350 lb (158.8 kg) depending on the configuration—we strongly recommend that you install the JCS 1200
platform using a mechanical lift, as described in “Installing the JCS 1200 Platform
Using a Lift” on page 51. If you do not use a lift to install the platform, refer to the
following procedures:
■
■
■
■
Tools and Parts Required to Install the JCS 1200 Platform Without a Mechanical
Removing Components from the JCS 1200 Platform on page 55
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
Reinstalling Components into the JCS 1200 Platform on page 57
54 ■
Installing the JCS 1200 Platform in a Rack Without a Lift
Chapter 6: Installing the JCS 1200 Platform
Tools and Parts Required to Install the JCS 1200 Platform Without a Mechanical Lift
■
■
■
To install the platform, you need the following tools and parts:
■
■
Phillips (+) screwdriver, number 2
ESD grounding wrist strap
Related Topics
■
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
Removing Components from the JCS 1200 Platform on page 55
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
Removing Components from the JCS 1200 Platform
Before lifting the JCS 1200 platform, you must remove the following components:
■
Fan modules
■
■
Fan shuttle
Management modules
■
■
■
■
Media trays
Power modules
Routing Engines
Switch modules
NOTE: For detailed instructions on removing JCS 1200 components, see the removal procedures for each component.
Related Topics
■
■
To remove the components from the JCS 1200 platform:
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Slide each component out of the chassis evenly so that it does not become stuck or damaged.
3.
4.
5.
Label each component as you remove it so you can reinstall it in the correct location.
Immediately store each removed component in an electrostatic bag.
Do not stack removed components. Lay each one on a flat surface.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Tools and Parts Required to Install the JCS 1200 Platform Without a Mechanical
Tools and Parts Required to Install the JCS 1200 Platform Without a Mechanical Lift
■ 55
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
■
■
■
■
■
■
Removing a JCS 1200 Fan Module on page 116
Removing a JCS 1200 Fan Shuttle on page 122
Removing a JCS 1200 Management Module or Module Filler on page 124
Removing a JCS 1200 Media Tray on page 128
Removing a JCS 1200 Power Module on page 138
Removing a JCS 1200 Routing Engine on page 140
Removing a JCS 1200 Switch Module or Module Filler on page 143
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
Lifting the JCS 1200 Platform into the Rack or Cabinet
Before you begin, see the following topics:
■
■
Tools and Parts Required to Install the JCS 1200 Platform Without a Mechanical
Removing Components from the JCS 1200 Platform on page 55
Lifting the chassis and mounting it in a rack requires four people. The empty chassis weighs approximately 329 lb (149.6 kg).
1.
Ensure the rack is in its permanent location and is secured to the building.
2.
3.
4.
5.
6.
Position the JCS 1200 platform in front of the rack or cabinet, centering it in front of the mounting shelves. Use a pallet jack if one is available.
With one person on each side and one person in the front, hold onto the bottom of the chassis and carefully lift it onto the large and small (if installed) mounting shelves.
Carefully slide the JCS 1200 platform onto the mounting shelves so that the bottom of the chassis and the mounting shelves overlap by approximately 2 in.
Install a mounting screw into each of the open mounting holes in the rack-mounting flanges to fasten the chassis to the rack, starting from the bottom.
Visually inspect the alignment of the JCS 1200 platform. If the JCS 1200 platform is installed properly in the rack, all the mounting screws on one side of the rack should be aligned with the mounting screws on the opposite side, and the platform should be level.
Related Topics
■
■
■
■
Tools and Parts Required to Install the JCS 1200 Platform Without a Mechanical
Removing Components from the JCS 1200 Platform on page 55
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
56 ■
Lifting the JCS 1200 Platform into the Rack or Cabinet
Chapter 6: Installing the JCS 1200 Platform
Reinstalling Components into the JCS 1200 Platform
NOTE: For detailed instructions on reinstalling JCS 1200 components, see the installation procedure for each component.
To reinstall components:
1.
2.
3.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Slide each component into the chassis evenly so that it does not become stuck or damaged.
Tighten screws, as needed, for each component.
NOTE: Make sure that all empty slots are covered with a blank panel before operating the JCS 1200 platform.
Related Topics
■
■
■
■
■
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Installing a JCS 1200 Fan Module on page 118
Installing a JCS 1200 Fan Shuttle on page 123
Installing a JCS 1200 Management Module or Module Filler on page 125
Installing a JCS 1200 Media Tray on page 129
Installing a JCS 1200 Power Module on page 139
Installing a JCS 1200 Routing Engine on page 141
Installing a JCS 1200 Switch Module or Module Filler on page 143
Reinstalling Components into the JCS 1200 Platform
■ 57
Juniper Control System (JCS) 1200 Platform Hardware Guide
58 ■
Reinstalling Components into the JCS 1200 Platform
Chapter 7
Connecting the JCS 1200 Platform
This chapter discusses the following procedures:
■
■
■
■
■
■
■
■
■
■
Before you Begin Connecting the JCS 1200 Platform on page 59
Tools and Parts Required for Connecting the JCS 1200 Platform on page 60
Supplying Power to the JCS 1200 Platform on page 60
Connecting the JCS 1200 Management Module to the Network on page 68
Establishing Your JCS 1200 Management Module Connection on page 70
Connecting a Console to the JCS 1200 Routing Engines on page 72
Powering On a JCS 1200 Routing Engine on page 73
Powering Off a JCS 1200 Routing Engine on page 74
Connecting the JCS 1200 Platform to a T-series Routing Platform on page 74
Verifying that the JCS 1200 Platform is Powered On Correctly on page 79
Before you Begin Connecting the JCS 1200 Platform
Before connecting the T-series routing platform to the JCS 1200 platform, ensure that the bootROM version for all FPCs is ROM Monitor Version 6.4 or later. If an FPC bootROM version is earlier than Version 6.4, the FPC will not come online. To upgrade the firmware, you must contact your Juniper Networks customer support representative.
To determine if you need to upgrade the FPC firmware, display the version of the firmware on all FPCs by issuing the show chassis firmware
command: user@host> show chassis firmware
Part Type Version
FPC 0 ROM Juniper ROM Monitor Version 7.5b4
O/S Version 9.1-20080222.0 by builder on 2008-0
FPC 1 ROM Juniper ROM Monitor Version 6.4b18
O/S Version 9.1-20080222.0 by builder on 2008-0
FPC 2 ROM Juniper ROM Monitor Version 7.5b4
O/S Version 9.1-20080222.0 by builder on 2008-0
FPC 4 ROM Juniper ROM Monitor Version 6.4b18
O/S Version 9.1-20080222.0 by builder on 2008-0
FPC 5 ROM Juniper ROM Monitor Version 6.4b20
O/S Version 9.1-20080222.0 by builder on 2008-0
FPC 6 ROM Juniper ROM Monitor Version 7.5b4
O/S Version 9.1-20080222.0 by builder on 2008-0
Before you Begin Connecting the JCS 1200 Platform
■ 59
Juniper Control System (JCS) 1200 Platform Hardware Guide
FPC 7 ROM Juniper ROM Monitor Version 6.4b20
O/S Version 9.1-20080222.0 by builder on 2008-0
SPMB 0 ROM Juniper ROM Monitor Version 6.4b18
O/S Version 9.1-20080222.0 by builder on 2008-0
SPMB 1 ROM Juniper ROM Monitor Version 6.4b18
O/S Version 9.1-20080222.0 by builder on 2008-0
CAUTION: By default, SNMP is enabled on the management module. Do not disable
SNMP. If you disable SNMP, you might not be able to access the management module.
Related Topics
■
Connecting the JCS 1200 Platform to a T-series Routing Platform on page 74
Tools and Parts Required for Connecting the JCS 1200 Platform
To connect the JCS 1200 platform to T-series routing platforms, power, and management devices and to power on the platform, you need the following tools and parts:
■
■
2.5-mm Phillips (+) screwdriver
7/16-in. hexagonal-head external drive socket wrench, or nut driver, with a torque range between 23 lb-in. (2.6 Nm) and 25 lb-in. (2.8 Nm), for tightening nuts to terminal studs on each power supply on a DC-powered router.
CAUTION: Do not substitute a nonmetric nut driver or wrench. A tool that does not fit the nuts exactly can damage them. If a 10-mm. tool is not available, use pliers or an adjustable wrench.
Related Topics
■
■
■
■
■
■
■
■
Wire cutters
Pliers
Electrostatic discharge (ESD) grounding wrist strap
JCS 1200 Platform Power Overview on page 61
Connecting the JCS 1200 Management Module to the Network on page 68
Establishing Your JCS 1200 Management Module Connection on page 70
Connecting a Console to the JCS 1200 Routing Engines on page 72
Connecting the JCS 1200 Platform to a T-series Routing Platform on page 74
Supplying Power to the JCS 1200 Platform
Topics include:
■
■
JCS 1200 Platform Power Overview on page 61
Connecting the JCS 1200 AC Platform to AC Power on page 62
60 ■
Tools and Parts Required for Connecting the JCS 1200 Platform
Chapter 7: Connecting the JCS 1200 Platform
■
■
Connecting the JCS 1200 DC Platform to DC Power on page 63
Disconnecting Power from the JCS 1200 Platform on page 65
JCS 1200 Platform Power Overview
The JCS 1200 platform does not have a power switch. The platform has four power connectors; each powers a power module. As viewed from the rear of the JCS 1200 platform, power connector 1 (top-right connector) supplies power to power module bay 1, power connector 2 (bottom-left connector) supplies power to power module
2, power connector 3 (top-left connector) supplies power to power module 3, and power connector 4 (bottom-right connector) supplies power to power module 4 (see
Figure 25: Direction of Power from Power Connectors to Power Modules on the
JCS 1200 Platform
Power modules 1 and 2 are redundant and provide power to Routing Engine bays
1 through 6; power modules 3 and 4 are redundant and provide power to Routing
Engine bays 7 through 12. To ensure power redundancy, a typical power configuration is to supply power to power connectors 1 and 4 from one power source location while supplying power to power connectors 2 and 3 from another power source
location. The power domains are shown in Figure 26 on page 62.
JCS 1200 Platform Power Overview
■ 61
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 26: Logical View of Power Domains on the JCS 1200 Platform
NOTE: The release handles on the fan shuttle have a safety switch that disables power output from the power boxes. If the release handles are not secured to the chassis with the thumbscrews, the JCS 1200 platform will not power on.
Related Topics
■
■
Connecting the JCS 1200 AC Platform to AC Power on page 62
Connecting the JCS 1200 DC Platform to DC Power on page 63
Connecting the JCS 1200 AC Platform to AC Power
The JCS 1200 platform has four AC power C20 input connectors. The appliance coupler at the female end of the detachable AC power cord inserts into the AC power input connector. The coupler is type C20 (right angle) as described by International
Electrotechnical Commission (IEC) standard 60320. The plug at the male end of the power cord fits into the power source receptacle that is standard for your geographical location. Use the AC power cords to connect AC power to the JCS 1200 platform.
To supply power to the JCS 1200 platform:
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Connect one end of each power cord to a power connector on the rear of the
JCS 1200 platform.
3.
Connect the other end of each power cord to a 200-240 volt, 20-amp power distribution unit or appropriate electrical outlet. An external surge protective device (SPD) is not required at the AC power input of the JCS 1200 platform.
62 ■
Connecting the JCS 1200 AC Platform to AC Power
Chapter 7: Connecting the JCS 1200 Platform
The Routing Engines in the JCS 1200 platform are connected to power but are not turned on. After the JCS 1200 platform has power, depending on the configuration settings, the Routing Engines might have to be individually turned on.
Related Topics
■
JCS 1200 Platform Power Overview on page 61
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Powering On a JCS 1200 Routing Engine on page 73
Connecting the JCS 1200 DC Platform to DC Power on page 63
Connecting the JCS 1200 DC Platform to DC Power
The JCS 1200 DC power inputs are configured for DC isolated return (DC-I). The DC return terminal or conductor is not connected to the equipment frame or the grounding means of the equipment.
CAUTION: Only trained service personnel other than Juniper Networks service technicians are authorized to make the connections to and disconnections from the
–48 volt DC power source. Juniper Networks service technicians are not certified or authorized to install or remove the –48 volt power cable. The customer is responsible for ensuring that only trained service personnel install or remove the –48 volt power cable.
The JCS 1200 DC platform has four DC power terminal connectors (see
Figure 27 on page 63). Each DC terminal has four M6 (0.25-inch) studs, one for –48
V DC, one for RETURN (
RTN
), and two for connecting the grounding cable (
GND
).
Each terminal has a terminal cover. Remove the terminal cover before connecting cables to each terminal, and reinstall the terminal cover on each terminal before
supplying power to the JCS 1200 platform. For more information, see “Replacing a
JCS 1200 DC Terminal Cover” on page 115.
Figure 27: JCS 1200 DC Power Terminal Connectors
Connecting the JCS 1200 DC Platform to DC Power
■ 63
Juniper Control System (JCS) 1200 Platform Hardware Guide
2.
3.
To connect the JCS 1200 DC platform to DC power:
1.
Ensure that the voltage across the DC power source cable leads is 0 V and that there is no chance that the cable leads might become active during installation.
4.
5.
6.
Verify that a licensed electrician has attached the cable lugs to the power cables.
Switch both circuit breakers on the power supply faceplate to the off position
( O ).
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the terminal cover for each terminal.
Attach the lugs on the DC source power cables to the terminal studs, making sure the cables are not touching or in the way of any JCS 1200 platform components. When connecting a cable lug to each stud, install a flat washer on the stud, install the cable lug, install a flat washer, install a split washer, and then
install a nut (see Figure 28 on page 64). Torque the wiring terminal nuts to
13.3 lb-in. (1.5 Nm).
Figure 28: Attaching the Cable Lugs to the JCS 1200 DC Power Terminal Connectors a.
Attach the positive (+) DC source power cable lugs to the RTN (return) terminals.
b.
c.
Attach the negative (–) DC source power cable lugs to the
–48V
(input) terminals.
Attach the safety ground wire to the other two terminals.
7.
8.
Verify that the power and ground cabling are correct.
Replace the terminal cover for each terminal.
64 ■
Connecting the JCS 1200 DC Platform to DC Power
Chapter 7: Connecting the JCS 1200 Platform
The Routing Engines in the JCS 1200 platform are connected to power but are not turned on. After the JCS 1200 platform has power, depending on the configuration settings, the Routing Engines might have to be individually turned on.
Related Topics
■
JCS 1200 Platform Power Overview on page 61
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
Replacing a JCS 1200 DC Terminal Cover on page 115
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Powering On a JCS 1200 Routing Engine on page 73
Connecting the JCS 1200 AC Platform to AC Power on page 62
Disconnecting Power from the JCS 1200 Platform
You can disconnect power from the JCS 1200 platform by powering off the Routing
Engines and disconnecting the JCS 1200 platform from the power source.
To disconnect power from the JCS 1200 platform:
1.
2.
3.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Power off each Routing Engine (for more information, see “Powering Off a
JCS 1200 Routing Engine” on page 74).
Disconnect power from the JCS 1200 platform.
NOTE: After you disconnect the JCS 1200 platform from power, wait at least 5 seconds before you connect the JCS 1200 platform to power again.
■
JCS 1200 DC platform:
Disconnecting Power from the JCS 1200 Platform
■ 65
Juniper Control System (JCS) 1200 Platform Hardware Guide a.
Make sure the Routing Engines are powered off.
CAUTION: This device does not provide a power control button. Powering off Routing
Engines or removing power modules and switch modules does not turn off electrical current to the device. The device also might have more than one power cord. To remove all electrical current from the product, make sure that all power cords are disconnected from the power source.
CAUTION: Only trained service personnel other than Juniper Networks service technicians are authorized to make the connections to and disconnections from the
–48 volt DC power source. Juniper Networks service technicians are not certified or authorized to install or remove the –48 volt power cable. The customer is responsible for ensuring that only trained service personnel install or remove the –48 volt power cable.
b.
Turn off the power source.
c.
66 ■
Disconnecting Power from the JCS 1200 Platform
Chapter 7: Connecting the JCS 1200 Platform
Figure 29: DC Power Terminal Connectors on the JCS 1200 Platform
■ d.
Remove the nut, split washer, flat washer, and cable lug from each terminal post.
e.
Remove the power cables.
JCS 1200 AC platform: a.
Make sure the Routing Engines are powered off.
CAUTION: This device does not provide a power control button. Powering off Routing
Engines or removing power modules and switch modules does not turn off electrical current to the device. The device also might have more than one power cord. To remove all electrical current from the product, make sure that all power cords are disconnected from the power source.
b.
Disconnect all power cords on the JCS 1200 platform from the power connectors.
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Disconnecting Power from the JCS 1200 Platform
■ 67
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
Connecting the JCS 1200 AC Platform to AC Power on page 62
Connecting the JCS 1200 DC Platform to DC Power on page 63
Connecting the JCS 1200 Management Module to the Network
The management module supports network connection through an Ethernet connector
or a serial connector (see Figure 30 on page 68).
Figure 30: Ports on the JCS 1200 Management Module
All management module network connections to Routing Engines are made through the CLI. You can perform initial configuration of the management module after you connect it to your network; however, because some requirements are imposed by the default management module settings, it might be easier to perform these setup operations through a direct connection.
For direct connection of a computer to the management module Ethernet connector, you need a Category 5 or higher Ethernet cable.
Network connections through the serial connector may require an Advanced
Management Module (AMM) adapter.
See the JUNOS Protected System Domain Configuration Guide for information about accessing the management module CLI.
The following topics describe how to make typical network connections for a management module:
■
■
■
■
Connecting to the JCS 1200 Management Module Using a Network Ethernet
Connecting to the JCS 1200 Management Module Using a Direct Ethernet
Connecting to the JCS 1200 Management Module Using a Console Serial
Connecting to the JCS 1200 Management Module Using a Direct Serial
68 ■
Connecting the JCS 1200 Management Module to the Network
Chapter 7: Connecting the JCS 1200 Platform
Connecting to the JCS 1200 Management Module Using a Network Ethernet Connection
3.
4.
To connect the management module to the network using the Ethernet port:
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Connect one end of an Ethernet cable to the Ethernet port on the management
module. See Figure 30 on page 68 for the location of input and output connectors
on the management module.
Connect the other end of the Ethernet cable to the network.
Check the Ethernet LEDs to make sure that the network connection is working.
■
■
A lit green Ethernet LINK LED indicates that there is an active connection through the port to the network.
A flashing green Ethernet activity ( TX/RX ) LED indicates that there is activity through the port over the network link.
Connecting to the JCS 1200 Management Module Using a Direct Ethernet Connection
To connect the Ethernet cable directly to the management module:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
4.
Connect one end of an Ethernet cable to the Ethernet port on the management
module. See Figure 30 on page 68 for the location of input and output connectors
on the management module.
Connect the other end of the Ethernet cable to the Ethernet port on the client computer.
Check the Ethernet LEDs to make sure that the network connection is working.
■
■
A lit green Ethernet
LINK
LED indicates that there is an active connection through the port to the network.
A flashing green Ethernet activity (
TX/RX
) LED indicates that there is activity through the port over the network link.
Connecting to the JCS 1200 Management Module Using a Console Serial Connection
To connect the management module to a console using a serial cable:
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Plug one end of an RJ-45 serial cable into the serial connector on the management
module. See Figure 30 on page 68 for the location of input and output connectors
on the management module.
Connecting to the JCS 1200 Management Module Using a Network Ethernet Connection
■ 69
Juniper Control System (JCS) 1200 Platform Hardware Guide
NOTE: Some consoles require that you use an AMM adapter. If needed, plug an AMM adapter into the serial connector on the management module, and then connect the
serial cable. For information about the AMM adapter pinouts, see “Pinouts for the
3.
Connect the other end of the serial cable to your console.
The serial cable must have the characteristics shown in “Serial Cable
Characteristics for the JCS 1200 Management Module” on page 211.
Connecting to the JCS 1200 Management Module Using a Direct Serial Connection
To connect the management module to a client computer using a serial cable:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Plug one end of an RJ-45 serial cable into the serial connector on the management
module. See Figure 30 on page 68 for the location of input and output connectors
on the management module.
NOTE: The serial cable must have the characteristics shown in “Serial Cable
Characteristics for the JCS 1200 Management Module” on page 211.
3.
4.
Connect the other end of the serial cable to the serial connector of the client computer, such as a notebook computer.
Configure the serial port of the client computer to the following values:
■
■
Baud rate—57600
Parity—none
■
Stop bits—1
Related Topics
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Tools and Parts Required for Connecting the JCS 1200 Platform on page 60
Establishing Your JCS 1200 Management Module Connection on page 70
Establishing Your JCS 1200 Management Module Connection
The management module has the following default settings:
■
■
■
■
IP address: 192.168.70.125
Subnet: 255.255.255.0
User ID: USERID (all capital letters)
Password: PASSW0RD (note the number zero, not the letter O, in PASSW0RD)
70 ■
Connecting to the JCS 1200 Management Module Using a Direct Serial Connection
Chapter 7: Connecting the JCS 1200 Platform
By default, the management module is configured to respond to DHCP first before using its static IP address.
The client computer that you connect to the management module must be configured to operate on the same subnet as the management module. The IP address of the management module must also be in the same local domain as the client computer.
To connect to the management module for the first time, you must change the IP properties on the client computer.
You can use one of two interfaces to connect to the management module for the first time. If you are connecting to the management module through an Ethernet connection, you can Telnet to the management module and use the CLI to configure the module. If you are connecting through a serial connection, you can use a terminal emulator to access the CLI.
The following topics describe how to establish a session between a client computer and the management module to perform initial configuration of the JCS 1200 platform.
■
■
Establishing Your JCS 1200 Management Module Connection Using a Direct
Ethernet Connection on page 71
Establishing Your JCS 1200 Management Module Connection Using a Direct Serial
Establishing Your JCS 1200 Management Module Connection Using a Direct Ethernet
Connection
After you connect the Ethernet cable from the management module to the client computer:
1.
Make sure that the subnet of the client computer is set to the same value as the default management module subnet (255.255.255.0).
2.
3.
Open a console window and log in to the default management module IP address
(192.168.70.125).
Enter the default user name, USERID, and the default password, PASSW0RD
(note the number zero, not the letter O, in PASSW0RD), to start the remote session.
After you connect the client computer to the management module for the first time, perform initial configuration of the JCS 1200 platform. See the JUNOS Protected System
Domain Configuration Guide for configuration instructions.
Establishing Your JCS 1200 Management Module Connection Using a Direct Serial
Connection
After you connect the serial cable from the management module to the client computer:
1.
Make sure that the serial port of the client computer is set to the following settings:
■
■
Baud rate—57600
Parity—none
Establishing Your JCS 1200 Management Module Connection Using a Direct Ethernet Connection
■ 71
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
Stop bits—1
2.
3.
Open a terminal emulator window and establish a connection to the management module serial port.
Enter the default user name, USERID, and the default password, PASSW0RD
(note the number zero, not the letter O, in PASSW0RD), to start the remote session.
Related Topics
After you connect to the management module for the first time, perform initial configuration of the JCS 1200 platform. See the JUNOS Protected System Domain
Configuration Guide for CLI configuration instructions.
■
Tools and Parts Required for Connecting the JCS 1200 Platform on page 60
■
Connecting the JCS 1200 Management Module to the Network on page 68
Connecting a Console to the JCS 1200 Routing Engines
To access the Routing Engines from a console, you must use the serial port breakout cable provided with the chassis to connect the JCS 1200 platform. The breakout cable provides a direct serial interface to each Routing Engine in the JCS 1200 platform
and contains 14 RJ-45 serial cable connectors (see Figure 31 on page 72).
Figure 31: JCS 1200 Serial Port Breakout Cable
NOTE: Only 12 of the 14 RJ-45 serial cable connectors are used to connect the console to the Routing Engines. Connectors 13 and 14 are reserved for future use.
To connect the console:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Connect the serial connector on the cable to the serial port connector on the alarm panel module of the JCS 1200 platform.
Connect the each of the RJ-45 connectors on the cable to your console.
72 ■
Connecting a Console to the JCS 1200 Routing Engines
Chapter 7: Connecting the JCS 1200 Platform
NOTE: Some consoles require that you use an CPU adapter. If needed, connect a
CPU adapter to each of the 12 RJ-45 connectors on the breakout cable. Then connect each CPU adapter to your console. For information about the CPU adapter pinouts,
see “Pinouts for the RJ-45 Adapters” on page 212.
Related Topics
■
■
■
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Tools and Parts Required for Connecting the JCS 1200 Platform on page 60
JCS 1200 Routing Engine Description on page 24
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
Powering On a JCS 1200 Routing Engine on page 73
Powering Off a JCS 1200 Routing Engine on page 74
Powering On a JCS 1200 Routing Engine
After you connect the Routing Engine to power through the JCS 1200 platform, the
Routing Engine can start in any of the following ways:
■
You can press the power control button on the front of the Routing Engine behind
the control panel door (see “JCS 1200 Routing Engine Control Panel Buttons and
NOTE: Wait until the power-on LED on the Routing Engine flashes slowly before you press the power control button. While the service processor in the management module is initializing, the power-on LED does not flash, and the power control button on the Routing Engine does not respond.
While the Routing Engine is starting, the power-on LED on the front of the Routing
Engine is lit.
■
■
■
If a power failure occurs, the JCS 1200 platform and then the Routing Engine can start automatically when power is restored if the Routing Engine is configured through the management module to do so.
You can power on the Routing Engine remotely through the management module.
The wake-on-LAN feature can power on the Routing Engine if the following conditions are met:
■
The Routing Engine is connected to power (the power-on LED is flashing slowly).
■
The operating system supports the wake-on-LAN feature.
■
The wake-on-LAN feature has not been disabled through the management module.
Powering On a JCS 1200 Routing Engine
■ 73
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■
■
■
■
JCS 1200 Routing Engine Description on page 24
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
Powering Off a JCS 1200 Routing Engine on page 74
Replacing a JCS 1200 Routing Engine on page 140
Locating the JCS 1200 Routing Engine Serial Number on page 203
Powering Off a JCS 1200 Routing Engine
When you power off the Routing Engine, it is still connected to power through the
JCS 1200 platform. The Routing Engine can respond to requests from the service processor, such as a remote request to power on the Routing Engine. To remove all power from the Routing Engine, you must remove it from the JCS 1200 platform.
Issue the shutdown –T system:blade[x] command (where x is a value of 1 through 12) from the management module CLI. The command shuts down the Routing Engines cleanly, so their state information is preserved. For more information, see the JUNOS
Protected System Domain Configuration Guide.
The Routing Engine can then be powered off in any of the following ways:
■
■
You can press the power control button for more than four seconds on the
Routing Engine behind the control panel door (see “JCS 1200 Routing Engine
Control Panel Buttons and LEDs” on page 25).
If the system is not operating correctly, the management module will automatically power off the Routing Engine.
Related Topics
■
■
■
■
JCS 1200 Routing Engine Description on page 24
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
Powering On a JCS 1200 Routing Engine on page 73
Replacing a JCS 1200 Routing Engine on page 140
Connecting the JCS 1200 Platform to a T-series Routing Platform
You can connect up to three of the following T-series routing platforms running
JUNOS Release 9.2 or later to the JCS 1200 platform: T320 router, T640 routing node, and T1600 routing node. The following procedures describe connecting the JCS 1200 platform to a T-series routing platform:
■
■
■
Replacing the Standard CBs in the T-series Routing Platform on page 75
Connecting an Offline T-series Routing Platform to the JCS 1200
Powering On the T-series Routing Platform on page 78
74 ■
Powering Off a JCS 1200 Routing Engine
Chapter 7: Connecting the JCS 1200 Platform
Replacing the Standard CBs in the T-series Routing Platform
Before you connect an offline T-series routing platform to the JCS 1200 platform, you must replace the standard control boards (CBs) with T-CBs. To replace the CBs with T-CBs:
1.
If the routing platform is powered on, issue the request system halt both-routing-engines
operational mode command from the console or other management device connected to the routing platform. The command shuts down the Routing Engines cleanly, so their state information is preserved.
user@host> request system halt both-routing-engines
2.
3.
Wait until a message appears on the console confirming that the operating system has halted. For more information about the command, see the JUNOS System
Basics and Services Command Reference.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Switch all circuit breakers on the power supply faceplates to the off position ( O ).
NOTE: The CBs and T-CBs are hot-removable and hot-insertable if the routing node contains redundant host subsystems. However, we recommend that you power off the routing platform before you replace the CBs and T-CBs.
4.
Set the switches on each T-CB:
■
Set the chassis ID switch to 0. You must use the same chassis ID on each
T-CB.
■
Set the
M/S
switch on the T-CB faceplate to
S
.
5.
6.
Replace each CB with a T-CB. Use the standard replacement procedure described in the hardware guide for your routing platform.
You can optionally upgrade the Routing Engines in the routing platform. To replace each Routing Engine, follow the standard replacement procedure described in the hardware guide for your routing platform.
Connecting an Offline T-series Routing Platform to the JCS 1200 Platform
After you replace the CBs with T-CBs, you connect each T-CB on the T-series routing
platform to each switch module on the JCS 1200 platform. Figure 32 on page 76
shows the location of the switch modules on the JCS 1200 platform.
Replacing the Standard CBs in the T-series Routing Platform
■ 75
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 32: Location of Switch Modules on the JCS 1200 Platform
To connect the T-CBs (see Figure 33 on page 77):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Plug an ETH adapter into the top RJ-45 port (labeled 1 ) of switch module 1 on the JCS 1200 platform.
Connect one end of a UTP Category 5 cable to the ETH adapter.
4.
Plug the other end of the cable into the port labeled
CIP
on
T-CB-0
. Dress the cable appropriately.
NOTE: The RJ-45 port labeled AUX on a T-CB is reserved for future use.
5.
If you installed a redundant switch module into switch module bay 2: a.
Plug an ETH adapter into the top RJ-45 port (labeled on the JCS 1200 platform.
1 ) of switch module 2 b.
Connect one end of a UTP Category 5 cable to the ETH adapter.
c.
Plug the other end of the cable into the port labeled CIP on T-CB-1 . Dress the cable appropriately.
76 ■
Connecting an Offline T-series Routing Platform to the JCS 1200 Platform
Chapter 7: Connecting the JCS 1200 Platform
Figure 33: Connecting the JCS 1200 Platform to a T-series Routing Platform
6.
Repeat 2 through 5 to connect up to two additional T-series routing platforms
to RJ-45 ports labeled 2 and 3 on the JCS 1200 switch module.
NOTE: To connect more than one T-series routing platform, each routing platform must run JUNOS Release 9.2 or later.
NOTE: A switch module has six external 1000Base-T Ethernet ports for 10/100/1000
Mbps connections to external Ethernet devices, such as backbones, end stations, and servers. These ports are identified as EXT1, EXT2, EXT3, EXT4, EXT5, and EXT6 in the switch configuration menus and are labeled
1
through
6
(from top to bottom) on the JCS 1200 switch module.
NOTE: The connections between the switch modules and the T-CBs are proprietary
Ethernet connections. Do not attempt to connect these components through a switch or hub.
Connecting an Offline T-series Routing Platform to the JCS 1200 Platform
■ 77
Juniper Control System (JCS) 1200 Platform Hardware Guide
Powering On the T-series Routing Platform
After you have connected the control planes between the T-series routing platform and the JCS 1200 platform, power on the routing platform, monitor the boot process, and verify the connections. Follow this procedure:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Switch the circuit breakers on one of the power supplies to the on position (
|
) and observe the LEDs on the power supply faceplate. If the power supply is correctly installed and is functioning properly, the DC OK LED lights steadily, and the CB ON LED blinks momentarily, then lights steadily.
NOTE: After powering off a power supply, wait at least 60 seconds before powering it back on. After powering on a power supply, wait at least 60 seconds before powering it off.
If the system is completely powered off when you power on the power supply, the
Routing Engine boots as the power supply completes its startup sequence. If the
Routing Engine finishes booting and you need to power off the system again, first issue the CLI request system halt command.
After a power supply is powered on, it can take up to 60 seconds for status indicators—such as the output status LED on the power supply, the show chassis command display, and messages on the LED display on the craft interface—to indicate that the power supply is functioning normally. Ignore error indicators that appear during the first 60 seconds.
3.
4.
Repeat Step 2 for the remaining power supply.
On an external management device connected to the console or auxiliary port of the CIP, monitor the startup process to verify that the system has booted properly.
NOTE: You do not need to reboot the JCS 1200 platform after the routing platform has booted.
Related Topics
■
■
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 Switch Module Description on page 27
JCS 1200 Switch Module Components and LEDs on page 27
Replacing the Standard CBs in the T-series Routing Platform on page 75
Verifying that the JCS 1200 Platform is Powered On Correctly on page 79
78 ■
Powering On the T-series Routing Platform
Chapter 7: Connecting the JCS 1200 Platform
Verifying that the JCS 1200 Platform is Powered On Correctly
Related Topics
■
■
■
■
■
After you connect the cables to the modules and route the cables, complete the following steps to start the JCS 1200 platform and verify that it is working correctly:
1.
Make sure that the following LEDs are lit, which indicate that the device is working correctly:
■
Input power and output power LEDs on each power module
■
OK LED on each management module
■
OK LED on each switch module
2.
3.
Make sure that the power-on LED on each Routing Engine is lit, either steady or flashing slowly.
Make sure there are no fault or error LEDs lit on any of the modules.
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
JCS 1200 Power Module LEDs on page 23.
JCS 1200 Management Module Connectors and LEDs on page 16
JCS 1200 Switch Module Components and LEDs on page 27
Replacing the Standard CBs in the T-series Routing Platform on page 75
Verifying that the JCS 1200 Platform is Powered On Correctly
■ 79
Juniper Control System (JCS) 1200 Platform Hardware Guide
80 ■
Verifying that the JCS 1200 Platform is Powered On Correctly
Chapter 8
Configuration Guidelines
■
Configuring the JCS 1200 Platform on page 81
Configuring the JCS 1200 Platform
CAUTION: By default, SNMP is enabled on the management module. Do not disable
SNMP. If you disable SNMP, your system might not function correctly.
Perform general configuration of the JCS 1200 platform and installed components through the management module. See the JUNOS Protected System Domain
Configuration Guide for information and instructions.
Related Topics
■
Configuring the JCS Management Module
■
■
Configuring the JCS Switch Module
Configuring an RSD and Creating PSDs
Configuring the JCS 1200 Platform
■ 81
Juniper Control System (JCS) 1200 Platform Hardware Guide
82 ■
Configuring the JCS 1200 Platform
Part 3
Hardware Troubleshooting and
Replacement Procedures
■
■
Troubleshooting Common JCS 1200 Platform Problems on page 85
Replacing Components in a JCS 1200 Platform on page 93
Hardware Troubleshooting and Replacement Procedures
■ 83
Juniper Control System (JCS) 1200 Platform Hardware Guide
84 ■
Hardware Troubleshooting and Replacement Procedures
Chapter 9
Troubleshooting Common JCS 1200
Platform Problems
This chapter provides basic troubleshooting information to help you solve some common problems that might occur while you are setting up your JCS 1200 platform.
Topics include:
■
■
■
Overview of JCS 1200 Diagnostic Tools on page 85
JCS 1200 Troubleshooting Tables on page 86
Light Path Diagnostic LEDs on page 89
Overview of JCS 1200 Diagnostic Tools
The following tools are available to help you diagnose and solve hardware-related problems:
■
Troubleshooting tables—These tables list problem symptoms and steps to correct the problems. For more information, see the following topics:
■
Troubleshooting JCS 1200 Fan Module Problems on page 86
■
Troubleshooting JCS 1200 Management Module Problems on page 87
■
Troubleshooting JCS 1200 Media Tray Problems on page 88
■
■
■
■
■
■
Troubleshooting JCS 1200 Power Problems on page 89
Diagnostic programs and error messages—The built-in self-test (BIST) program checks the JCS 1200 platform during startup and generates error messages if problems are found.
Light path diagnostic LEDs—Use the light path diagnostic LEDs on the JCS 1200 platform and the JCS 1200 components to identify system errors quickly.
Real Time Diagnostics—Real Time Diagnostics tests the major components of the JCS 1200 platform, including the management modules, switch modules, removable media drives, and the Routing Engines.
System event logs—The management module stores system events and can be accessed through the management module user interface.
Service data—The management module stores important hardware information that can be accessed through the management module user interface.
Overview of JCS 1200 Diagnostic Tools
■ 85
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■
■
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90.
JUNOS Protected System Domain Configuration Guide
JCS 1200 Troubleshooting Tables
Topics include:
■
■
■
■
■
Overview of JCS 1200 Troubleshooting Tables on page 86
Troubleshooting JCS 1200 Fan Module Problems on page 86
Troubleshooting JCS 1200 Management Module Problems on page 87
Troubleshooting JCS 1200 Media Tray Problems on page 88
Troubleshooting JCS 1200 Power Problems on page 89
Overview of JCS 1200 Troubleshooting Tables
Use the troubleshooting tables to find solutions to problems that have identifiable symptoms.
If you have run the diagnostic test programs or if running the tests does not reveal the cause of problem, contact your Juniper Networks representative.
2.
3.
4.
If you have just added a new optional device and your system is not working, complete the following steps before you use the troubleshooting tables:
1.
Remove the device that you just added.
Run the diagnostic tests to determine whether the system is running correctly.
Update the firmware for the optional device.
Reinstall the new device.
Related Topics
When you review the troubleshooting tables, follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
■
Overview of JCS 1200 Diagnostic Tools on page 85
■
■
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90
Troubleshooting JCS 1200 Fan Module Problems
Table 20 on page 87 shows common symptoms and corrective actions for
troubleshooting fan module problems.
86 ■
JCS 1200 Troubleshooting Tables
Chapter 9: Troubleshooting Common JCS 1200 Platform Problems
Table 20: Troubleshooting JCS 1200 Fan Module Problems
Symptom Action
A fan module is always operating at full speed.
1.
Make sure that:
■
■
The other fans are installed and working.
At least one management module is installed, and it is active and working.
2.
Reseat the fan module.
3.
Contact your Juniper Networks representative.
A fan module is not working.
1.
Make sure that all power cords are connected to a compatible power source and that
the power source is working (see “Connecting the JCS 1200 AC Platform to AC
Power” on page 62 or “Connecting the JCS 1200 DC Platform to DC
2.
Reseat the fan module.
3.
Contact your Juniper Networks representative.
Related Topics
■
■
■
■
■
Overview of JCS 1200 Troubleshooting Tables on page 86
Overview of JCS 1200 Diagnostic Tools on page 85
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90
Replacing a JCS 1200 Fan Module on page 116
Troubleshooting JCS 1200 Management Module Problems
Table 21 on page 87 shows common symptoms and corrective actions for
troubleshooting management module problems.
Table 21: Troubleshooting JCS 1200 Management Module Problems
Symptom Action
Cannot connect to the JCS 1200 platform using Telnet
1.
Make sure that:
■
■
The network cable is connected to the Ethernet port on the primary management module.
The network cable is not connected to the serial port on the management module.
■
The IP address or hostname is correct. The default IP address is 192.168.70.125.
2.
Reseat the management module.
NOTE: Removing the primary management module will cause an automatic failover to the redundant management module, if one is installed.
3.
Reset and reconfigure the management module (for more information, see JUNOS
Protected System Domain Configuration Guide).
4.
Contact your Juniper Networks representative.
Troubleshooting JCS 1200 Management Module Problems
■ 87
Juniper Control System (JCS) 1200 Platform Hardware Guide
Table 21: Troubleshooting JCS 1200 Management Module Problems (continued)
Symptom Action
Cannot connect to the JCS 1200 platform after a switchover to the redundant management module
1.
Make sure that:
■
■
The redundant management module has been installed for at least 45 minutes to receive the transfer of data from the primary management module.
The network cable is connected to the Ethernet port on the active (redundant) management module.
■
■
The network cable is not connected to the serial port on the active (redundant) management module.
The IP address or hostname is correct.
2.
Reseat the management module.
3.
Reset and reconfigure the management module (see the JUNOS Protected System Domain
Configuration Guide for more information).
4.
Contact your Juniper Networks representative.
Related Topics
■
■
■
■
■
Overview of JCS 1200 Troubleshooting Tables on page 86
Overview of JCS 1200 Diagnostic Tools on page 85
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90
Replacing a JCS 1200 Management Module or Module Filler on page 124
Troubleshooting JCS 1200 Media Tray Problems
Table 22 on page 88 shows common symptoms and corrective actions for
troubleshooting media tray problems.
Table 22: Troubleshooting JCS 1200 Media Tray Problems
Symptom
A USB device is not recognized by any Routing
Engine.
Action
1.
Reseat the following components: a.
USB device b.
Media tray
2.
Contact your Juniper Networks representative.
A compact flash module is not recognized by the management module.
1.
Reseat the following components: a.
Compact flash module b.
Media tray
2.
Contact your Juniper Networks representative.
88 ■
Troubleshooting JCS 1200 Media Tray Problems
Chapter 9: Troubleshooting Common JCS 1200 Platform Problems
Related Topics
■
■
■
■
■
Overview of JCS 1200 Troubleshooting Tables on page 86
Overview of JCS 1200 Diagnostic Tools on page 85
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90
Replacing a JCS 1200 Media Tray on page 128
Troubleshooting JCS 1200 Power Problems
Table 23 on page 89 shows common symptoms and corrective actions for
troubleshooting power problems.
Table 23: Troubleshooting JCS 1200 Power Problems
Symptom
The JCS 1200 platform does not start.
Action
1.
Make sure that: a.
All power cords are connected to a compatible power source and that the power sources
are working (see “Connecting the JCS 1200 AC Platform to AC Power” on page 62 or
“Connecting the JCS 1200 DC Platform to DC Power” on page 63).
b.
The input power and output power LEDs on the power modules are lit.
2.
If you just installed an optional device, remove it. If the JCS 1200 platform now starts, you might have installed more devices than the power modules support. You might have to install power modules in power module bays 3 and 4.
Related Topics
■
■
■
■
Overview of JCS 1200 Troubleshooting Tables on page 86
Overview of JCS 1200 Diagnostic Tools on page 85
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90
Light Path Diagnostic LEDs
Topics include:
■
■
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform on page 90
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200 Platform
Light path diagnostic LEDs are a system of LEDs on the alarm panel of the JCS 1200 platform and the JCS 1200 components that can be used to diagnose system errors.
If the front or rear system-error LED on the JCS 1200 platform is lit, one or more
Troubleshooting JCS 1200 Power Problems
■ 89
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■ error LEDs on the JCS 1200 components also might be lit. These LEDs help to identify the cause of the problem.
The following example shows how to use the LEDs to diagnose a system error:
1.
Note that the JCS 1200 system-fault LEDs are lit on the media tray LED panel.
2.
3.
To identify the component that is causing the error, locate module that has a lit error LED.
If the component is a module, replace the module.
Overview of JCS 1200 Diagnostic Tools on page 85
Diagnostic LEDs on the JCS 1200 Platform on page 90
Diagnostic LEDs on the JCS 1200 Platform
Use Table 24 on page 90 to find solutions to problems that are identified by LEDs
on the front and rear JCS 1200 system LED panels.
Table 24: Diagnostic LEDs on the JCS 1200 Platform
Lit LED Cause Action
JCS 1200 System LED Panels
Power-on Green indicates that power is present in the JCS 1200 platform. When this LED is off, the power subsystem, the AC power source, or the LED has failed, or the management module is not present or not functioning.
CAUTION: If the power-on LED is off, it does not mean that no electrical current is present in the
JCS 1200 platform. The LED might be burned out. To remove all electrical current from the JCS 1200 platform, you must disconnect all power cords from all power modules.
1.
Make sure that the JCS 1200 platform is connected to a compatible power source
(see “Connecting the JCS 1200 AC
Platform to AC Power” on page 62 or
“Connecting the JCS 1200 DC Platform to DC Power” on page 63).
2.
Reseat the following components: a.
Media tray b.
Management module c.
Power modules
3.
Contact your Juniper Networks representative.
Location
Critical system fault
Blue indicates that a condition has occurred in the
JCS 1200 platform that has caused the remote systems management to identify the JCS 1200 platform as needing attention.
Look for any information or error LEDs on the system LED panels, the modules, and the
Routing Engines in the JCS 1200 platform.
When this LED is lit, the JCS 1200 platform has a critical system fault. A critical system fault is an error or event that is detected by the system and that has a significant impact to the system. In this case, the system cannot continue to operate or is operating in a nonredundant power or cooling configuration.
1.
Check the error log for messages.
2.
Look for a lit error LED on the modules and Routing Engines to locate a failing component.
90 ■
Diagnostic LEDs on the JCS 1200 Platform
Chapter 9: Troubleshooting Common JCS 1200 Platform Problems
Table 24: Diagnostic LEDs on the JCS 1200 Platform (continued)
Lit LED
Major system fault
Cause
When this LED is lit, the JCS 1200 platform has a major system fault. The system can continue to operate but might lose some function and performance.
Action
1.
Check the error log for messages.
2.
Look for a lit error LED on the modules and Routing Engines to locate a failing component.
Minor system fault When this LED is lit, the JCS 1200 platform has a minor system fault. The system can continue to operate, usually without noticeable loss of function or performance.
There is an error with the media tray.
Media tray fault
(This LED is only on the media tray in the front of the JCS 1200 platform.)
Alarm panel fault
(This LED is only on the alarm panel module in the rear of the JCS 1200 platform.)
There is an error with the alarm panel module.
Check the error log for the messages. Check the LEDs on the JCS 1200 platform and the
Routing Engines to isolate the component.
1.
Reseat the media tray.
2.
Contact your Juniper Networks representative.
1.
Reseat the alarm panel module.
2.
Contact your Juniper Networks representative.
Related Topics
■
■
Overview of JCS 1200 Diagnostic Tools on page 85
Using Diagnostic LEDs to Diagnose Problems on the JCS 1200
Diagnostic LEDs on the JCS 1200 Platform
■ 91
Juniper Control System (JCS) 1200 Platform Hardware Guide
92 ■
Diagnostic LEDs on the JCS 1200 Platform
Chapter 10
Replacing Components in a JCS 1200
Platform
This chapter provides instructions for replacing components in a JCS 1200 platform.
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
JCS 1200 Hardware Component Installation Checklist on page 94
JCS 1200 Hardware Component Installation Guidelines on page 95
JCS 1200 Platform System Reliability Guidelines on page 95
Replacing a JCS 1200 Alarm Panel Module or Module Filler on page 96
Replacing a JCS 1200 Bezel on page 97
Replacing a JCS 1200 Bezel Collar on page 99
Replacing a JCS 1200 Bezel Filter on page 107
Replacing JCS 1200 Cable Management Trays Without a Bezel on page 110
Replacing a JCS 1200 Chassis on page 113
Replacing a JCS 1200 DC Terminal Cover on page 115
Replacing a JCS 1200 Fan Module on page 116
Replacing a JCS 1200 Fan Pack on page 120
Replacing a JCS 1200 Fan Shuttle on page 121
Replacing a JCS 1200 Management Module or Module Filler on page 124
Replacing a JCS 1200 Management Module Filler Tray on page 127
Replacing a JCS 1200 Management Module Interposer on page 128
Replacing a JCS 1200 Media Tray on page 128
Replacing a JCS 1200 Midplane on page 130
Replacing a JCS 1200 MUX Card on page 131
Replacing a JCS 1200 Network Clock Filler on page 132
Replacing a JCS 1200 Power Box on page 134
Replacing a JCS 1200 Power Module on page 138
Replacing a JCS 1200 Routing Engine on page 140
Replacing a JCS 1200 Switch Module or Module Filler on page 143
Replacing a JCS 1200 Switch Module Filler Tray on page 145
Replacing a JCS 1200 Switch Module Interposer on page 146
■ 93
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 Hardware Component Installation Checklist
Before you can use the JCS 1200 platform, you must install and configure the required components in the JCS 1200 platform. If you have not already done so, perform the activities on the following checklist:
1.
2.
Set up the rack or cabinet in which you will install the JCS 1200 platform. See
“JCS 1200 Platform Rack-Mounting Hardware” on page 43.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
3.
4.
5.
Remove any modules that come installed in the JCS 1200 platform to reduce the weight of the unit.
Install the JCS 1200 platform into the rack. See “Installing the JCS 1200 Platform
Reinstall the removed modules in the JCS 1200 platform.
NOTE: Make sure that the JCS 1200 platform has adequate power to support all of the installed components. The JCS 1200 platform must contain either two or four
power modules. See “JCS 1200 Platform Power Overview” on page 61 for more
information.
Related Topics
■
■
6.
7.
8.
Install the required JCS 1200 platform components.
Supply power to the JCS 1200 platform. See “Connecting the JCS 1200 AC
Platform to AC Power” on page 62 or “Connecting the JCS 1200 DC Platform to
DC Power” on page 63 for more information.
Make sure that the latest level of firmware is installed on all of the JCS 1200 components. See http://www.juniper.net/support/
for additional information.
9.
Configure the management module in the JCS 1200 platform. For information and instructions, see the JUNOS Protected System Domain Configuration Guide.
10.
Determine the JCS 1200 platform configuration settings, such as the IP address, network address, and wake-on-LAN settings. For instructions for configuring an
IP address, see the JUNOS Protected System Domain Configuration Guide.
11.
Configure the switch modules in the JCS 1200 platform. For configuration information, see the JUNOS Protected System Domain Configuration Guide.
12.
Configure the Routing Engines. For information and instructions, see the JUNOS
Protected System Domain Configuration Guide.
JCS 1200 Hardware Component Installation Guidelines on page 95
JCS 1200 Platform System Reliability Guidelines on page 95
94 ■
JCS 1200 Hardware Component Installation Checklist
Chapter 10: Replacing Components in a JCS 1200 Platform
JCS 1200 Hardware Component Installation Guidelines
Related Topics
■
■
Before you install any modules or fillers in the JCS 1200 platform, read the following information:
■
work safely.
■
■
■
Orange on a component or an orange label on or near a component indicates that the component is hot-swappable, which means that you can remove or install the component while the JCS 1200 platform is running. (Orange can also indicate touch points on hot-swappable components.) See the instructions for removing or installing a specific hot-swappable component for any additional procedures that you might have to perform before you remove or install the component.
You do not have to disconnect the JCS 1200 platform from power to install or replace any of the hot-swappable modules in the JCS 1200 platform. You must shut down the operating system and power off a Routing Engine before you remove the Routing Engine, but you do not have to shut down the JCS 1200
platform itself (see “Powering Off a JCS 1200 Routing Engine” on page 74).
Blue on a component indicates touch points where you can grip the component to open and close a latch or where you can grab a component to remove it from or install it into the JCS 1200 platform.
JCS 1200 Hardware Component Installation Checklist on page 94
JCS 1200 Platform System Reliability Guidelines on page 95
JCS 1200 Platform System Reliability Guidelines
Related Topics
■
■
To help ensure proper cooling and system reliability, make sure that the following requirements are met:
■
Each of the module bays on the JCS 1200 platform has either a module or a module filler installed.
■
■
Each of the Routing Engine bays on the front of the JCS 1200 platform has either a Routing Engine or a Routing Engine filler installed.
A removed hot-swappable module, Routing Engine, or drive is replaced within
1 minute of removal.
■
■
Cables for the optional modules are routed according to the illustrations and instructions in this document.
A failed fan is replaced as soon as possible to restore cooling redundancy.
JCS 1200 Hardware Component Installation Checklist on page 94
JCS 1200 Hardware Component Installation Guidelines on page 95
JCS 1200 Hardware Component Installation Guidelines
■ 95
Juniper Control System (JCS) 1200 Platform Hardware Guide
Replacing a JCS 1200 Alarm Panel Module or Module Filler
Topics include:
■
■
Removing a JCS 1200 Alarm Panel Module or Module Filler on page 96
Installing a JCS 1200 Alarm Panel Module or Module Filler on page 96
Removing a JCS 1200 Alarm Panel Module or Module Filler
Figure 34 on page 96 shows how to remove and install an alarm panel module.
Figure 34: Removing and Installing a JCS 1200 Alarm Panel Module
To remove an alarm panel module or module filler (see Figure 34 on page 96):
1.
2.
3.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Pull the release handle to the open position. The module moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the alarm panel module out of the bay.
Installing a JCS 1200 Alarm Panel Module or Module Filler
Figure 35 on page 97 shows how to remove and install an alarm panel module.
96 ■
Replacing a JCS 1200 Alarm Panel Module or Module Filler
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 35: Removing and Installing a JCS 1200 Alarm Panel Module
Related Topics
■
■
■
To install an alarm panel module or module filler (see Figure 35 on page 97):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
4.
Make sure that the release handle on the alarm panel module is in the open position.
Slide the alarm panel module into the alarm panel module bay until it stops.
Push the release handle to the closed position.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 Alarm Panel Module Description on page 12
Locating the JCS 1200 Alarm Panel Serial Number on page 197
Replacing a JCS 1200 Bezel
Topics include:
■
■
Removing a JCS 1200 Bezel on page 97
Installing a JCS 1200 Bezel on page 98
Removing a JCS 1200 Bezel
If the JCS 1200 bezel option is installed on your JCS 1200 platform, you must first remove the bezel to access any devices installed into the front of your JCS 1200 platform.
Replacing a JCS 1200 Bezel
■ 97
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 36 on page 98 shows how to remove a bezel.
Figure 36: Removing a JCS 1200 Bezel
To remove a bezel (see Figure 36 on page 98):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
4.
Hold the bezel and press the blue release button on each side of the bezel.
Pull the bezel away from the JCS 1200 platform.
If you are instructed to return the bezel, follow all packaging instructions and use any packaging materials for shipping that are supplied to you.
Installing a JCS 1200 Bezel
Figure 37 on page 99 shows how to install a bezel.
98 ■
Installing a JCS 1200 Bezel
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 37: Installing a JCS 1200 Bezel
3.
4.
To install a bezel (see Figure 37 on page 99):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
5.
Holding the sides of the bezel, orient the bezel so the logo is at the top and right corner.
Place the bottom edge of the bezel on the bezel retention tab.
Rotate the top of the bezel toward the JCS 1200 platform until the bezel clicks into place.
Turn the quarter-turn bezel locks to the locked position.
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Bezel Collar
Topics include:
■
■
Removing a JCS 1200 Bezel Collar on page 100
Installing a JCS 1200 Bezel Collar on page 102
Replacing a JCS 1200 Bezel Collar
■ 99
Juniper Control System (JCS) 1200 Platform Hardware Guide
Removing a JCS 1200 Bezel Collar
Figure 38 on page 100 shows how to remove and install a bezel collar.
Figure 38: Removing and Installing the JCS 1200 Bezel Collar
To install a JCS 1200 bezel collar (see Figure 38 on page 100):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Remove the bezel. See “Removing a JCS 1200 Bezel Filter” on page 107 for more
information.
Remove the light path extension assembly (see Figure 39 on page 101). Two light
path extension assemblies are shipped with the JCS 1200 Bezel to extend the light path LEDs so that they are visible through the bezel. Remove one light path extension assembly for each of the media trays installed in your JCS 1200 platform.
100 ■
Removing a JCS 1200 Bezel Collar
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 39: Removing the Light Path Extension Assembly a.
Push the release tab towards the center of the JCS 1200 platform.
b.
Pull the light path extension assembly away from the JCS 1200 platform.
c.
d.
Remove management module 1 from management module bay 1. See
“Removing a JCS 1200 Management Module or Module Filler” on page 124
for more information.
Remove the interposer from management module bay 1: i.
Pull the management module interposer release handle to the open position. The interposer moves out of the bay approximately 0.25 in.
(0.6 cm).
ii.
Slide the interposer out of the bay.
e.
Remove any switch modules or module fillers from switch module bays 7
and 8. See “Removing a JCS 1200 Switch Module or Module Filler” on page
f.
Remove the interposer from switch module bays 7 and 8: i.
Pull the switch module interposer release handle to the open position.
The interposer moves out of the bay approximately 0.25 in. (0.6 cm).
Removing a JCS 1200 Bezel Collar
■ 101
Juniper Control System (JCS) 1200 Platform Hardware Guide ii.
Slide the interposer out of the bay.
g.
Using a Phillips-head screwdriver, loosen the captive mounting screws on the cable management trays so that they do not secure the trays and bezel collar to the JCS 1200 platform.
h.
Remove the bezel collar by lifting up the bezel collar and then pulling the bezel collar away from the JCS 1200 platform.
4.
Remove the cable management trays by using a Phillips-head screwdriver to remove the M4 screws that secure each tray to the bezel.
Figure 40: Removing the Cable Management Trays
NOTE: Three M4 screws are used to secure the upper cable management tray and four M4 screws are used to secure the lower cable management tray.
5.
If you are instructed to return the bezel collar, follow all packaging instructions and use any packaging materials for shipping that are supplied to you.
Installing a JCS 1200 Bezel Collar
Figure 41 on page 103 shows how to remove and install a bezel collar.
102 ■
Installing a JCS 1200 Bezel Collar
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 41: Removing and Installing the JCS 1200 Bezel Collar
To install a JCS 1200 bezel collar (see Figure 41 on page 103):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
If installed, remove the cable management trays from the JCS 1200 platform.
See “Removing the JCS 1200 Cable Management Trays Without a Bezel” on page
3.
Attach the cable management trays to the bezel collar (see Figure 42 on page 104):
Installing a JCS 1200 Bezel Collar
■ 103
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 42: Attaching the Cable Management Trays to the Bezel Collar a.
Position the bezel collar so that the light path extension assembly retention tabs are on your left.
b.
Select one of the cable management trays and align the mounting holes of the cable management tray with the mounting holes in the bezel collar.
c.
Secure the cable management tray to the collar using the supplied M4 screws
NOTE: Three M4 screws are used to secure the upper cable management tray. Be sure to insert one screw in the hole closest to the front edge of the bezel collar on the left side; then use two screws on the right side.
d.
Repeat 2 and 3 for the remaining cable management tray.
4.
5.
information.
Remove the interposer from management module bay 1: a.
Pull the management module interposer release handle to the open position.
The interposer moves out of the bay approximately 0.25 in. (0.6 cm).
b.
Slide the interposer out of the bay.
6.
Remove any switch modules or module fillers from switch module bays 7 and
8. See “Removing a JCS 1200 Switch Module or Module Filler” on page 143 for
more information.
104 ■
Installing a JCS 1200 Bezel Collar
Chapter 10: Replacing Components in a JCS 1200 Platform
7.
Remove the interposer from switch module bays 7 and 8: a.
Pull the switch module interposer release handle to the open position. The interposer moves out of the bay approximately 0.25 in. (0.6 cm).
b.
Slide the interposer out of the bay.
8.
Attach the bezel collar to the JCS 1200 platform (see Figure 38 on page 100):
a.
Insert the lower bezel collar hooks into the bezel mounting slots on the bottom of the JCS 1200 platform; then rotate the top of the frame up until the upper collar hooks are inserted into the mounting slots.
b.
Push down on the bezel collar to completely engage the collar hooks in the mounting slots.
NOTE: The top of the collar should be flush with the top of the chassis.
c.
Secure the bezel collar to the JCS 1200 platform by using a Phillips-head screwdriver to tighten the captive mounting screws on the cable management
trays (see Figure 43 on page 105).
Figure 43: Securing the Cable Management Trays
9.
Reinstall the management module interposer into management module bay 1: a.
Make sure that the release handle on the interposer is in the open position.
b.
Slide the interposer into the management module bay until it stops.
Installing a JCS 1200 Bezel Collar
■ 105
Juniper Control System (JCS) 1200 Platform Hardware Guide c.
Push the interposer release handle to the closed position.
10.
11.
Install the light path extension assembly. Two light path extension assemblies are shipped with the JCS 1200 bezel to extend the light path LEDs so that they are visible through the bezel. Install one light path extension assembly for each of the management modules installed in your JCS 1200 platform.
Figure 44: Installing the Light Path Extension Assembly a.
Place the light path extension assembly onto the bezel collar in front of the retention tabs. The release tab should extend slightly beyond the edge of the collar.
b.
Push the assembly toward the back of the collar until the release tab clicks into place. While pushing the assembly toward the JCS 1200 platform, ensure that the locator pin is inserted into the hex locator hole to the right of the light path LEDs on the media tray.
12.
Install the filter frame (see “Installing the JCS 1200 Bezel Filter” on page 108).
106 ■
Installing a JCS 1200 Bezel Collar
Chapter 10: Replacing Components in a JCS 1200 Platform
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Bezel Filter
Topics include:
■
■
Removing a JCS 1200 Bezel Filter on page 107
Installing the JCS 1200 Bezel Filter on page 108
Removing a JCS 1200 Bezel Filter
Figure 45 on page 107 shows a bezel filter.
Figure 45: JCS 1200 Bezel Filter
2.
3.
To remove a bezel filter:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the bezel (see “Removing a JCS 1200 Bezel” on page 97).
Lay the bezel on a flat work surface and orient it so that the bottom of the bezel is closest to you and the light path holes are to the right. The large rectangles in the filter frame should be closest to you.
Replacing a JCS 1200 Bezel Filter
■ 107
Juniper Control System (JCS) 1200 Platform Hardware Guide
4.
Remove the air filter assembly from the filter frame by pulling out and rotating the air filter assembly locks until they no longer engage the air filter assembly.
Figure 46: Removing the Air Filter Assembly
5.
Remove the air filter assembly; then remove the old filter from the filter frame and dispose of it.
Installing the JCS 1200 Bezel Filter
To install a bezel filter:
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Lay the bezel on a flat work surface and orient it so that the bottom of the bezel is closest to you and the light path holes are to the right. The large rectangles in the filter frame should be closest to you.
108 ■
Installing the JCS 1200 Bezel Filter
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 47: Cutouts on the JCS 1200 Bezel Filter
3.
4.
5.
Lay the new filter on a clean flat surface and orient it so that the cutouts for the light path extension assemblies are to the right and the large cutout at the bottom of the filter is closest to you.
Orient the filter frame to the filter and place the filter frame on top of the filter; then pick up the filter assembly and install it into the bezel.
Secure the air filter assembly by pulling out and rotating the air filter assembly locks until they engage the air filter assembly.
Installing the JCS 1200 Bezel Filter
■ 109
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 48: Securing the Air Filter Assembly
6.
Install the bezel on the JCS 1200 platform (see “Installing a JCS 1200
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing JCS 1200 Cable Management Trays Without a Bezel
Topics include:
■
■
Removing the JCS 1200 Cable Management Trays Without a Bezel on page 110
Installing the JCS 1200 Cable Management Trays Without a Bezel on page 111
Removing the JCS 1200 Cable Management Trays Without a Bezel
Figure 49 on page 111 shows how to remove and install the cable management trays.
110 ■
Replacing JCS 1200 Cable Management Trays Without a Bezel
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 49: Removing and Installing the JCS 1200 Cable Management Trays
The cable management trays can be removed with or without the JCS 1200 bezel.
If you are removing the JCS 1200 bezel, see “Removing a JCS 1200 Bezel” on page
3.
4.
To remove the cable management trays that are installed without the JCS 1200 bezel
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Hold the cable management tray with one hand and use a Phillips-head screwdriver to loosen the captured thumb screws that attach the cable management tray to the JCS 1200 platform.
Pull the cable management tray away from the JCS 1200 platform.
Repeat these steps for the other cable management tray.
Installing the JCS 1200 Cable Management Trays Without a Bezel
Figure 50 on page 112 shows how to remove and install the cable management trays.
Installing the JCS 1200 Cable Management Trays Without a Bezel
■ 111
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 50: Removing and Installing the JCS 1200 Cable Management Trays
The cable management trays can be installed with or without the JCS 1200 bezel
option. If you are installing the JCS 1200 bezel, see “Installing a JCS 1200
Bezel” on page 98 for more information.
To install the cable management trays without a bezel (see Figure 50 on page 112):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
To install the upper cable management tray: a.
Orient the upper cable management tray so that the captive thumb screws are oriented toward the Routing Engine bays.
b.
Align the captive thumb screws with the screw holes above switch module bays 1 and 3.
c.
Use a Phillips-head screwdriver to tighten the captured thumb screws into the JCS 1200 platform.
3.
To install the lower cable management tray: a.
Orient the lower cable management tray so that the captive thumb screws are oriented toward the Routing Engine bays.
b.
Align the captive thumb screws with the screw holes below switch module bays 2 and 4.
c.
Use a Phillips-head screwdriver to tighten the captured thumb screws into the JCS 1200 platform.
112 ■
Installing the JCS 1200 Cable Management Trays Without a Bezel
Chapter 10: Replacing Components in a JCS 1200 Platform
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Chassis
To replace a chassis, you must remove components from the old chassis and install them in the new chassis.
Topics include:
■
■
Removing Components from a JCS 1200 Chassis on page 113
Installing Components in a Replacement JCS 1200 Chassis on page 114
Removing Components from a JCS 1200 Chassis
To remove components from a JCS 1200 chassis:
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Power off any Routing Engines in the JCS 1200 platform (see “Powering Off a
JCS 1200 Routing Engine” on page 74).
3.
4.
Remove the following components from the front of the JCS 1200 platform:
■
■
Switch modules: Pull the handle on each switch module or filler to the open
position and remove the module or filler (see “Removing a JCS 1200 Switch
Module or Module Filler” on page 143).
Management modules: Pull the handle on each management module or filler
to the open position and remove the module or filler (see “Removing a
JCS 1200 Management Module or Module Filler” on page 124).
5.
Disengage the following components from the JCS 1200 midplane using the procedure indicated:
NOTE: Make sure each component is pulled out of the JCS 1200 platform at least
1 in. (2.54 cm).
■
■
■
Routing Engines: Pull the two release handles on each Routing Engine to the
open position (see “Removing a JCS 1200 Routing Engine” on page 140).
Power modules: Pull the handle on each power module or filler to the open
position (see “Removing a JCS 1200 Power Module” on page 138).
Media tray: Pull the handle on each media tray or filler to the open position
(see “Removing a JCS 1200 Media Tray” on page 128).
6.
Remove the fan shuttle from the JCS 1200 platform (see “Removing a JCS 1200
Replacing a JCS 1200 Chassis
■ 113
Juniper Control System (JCS) 1200 Platform Hardware Guide
7.
8.
Remove the upper and lower power boxes from the rear of the JCS 1200 chassis
(see “Removing a JCS 1200 Power Box” on page 134).
If you are instructed to return the chassis, follow all packaging instructions and use any packaging materials for shipping that are supplied to you.
Installing Components in a Replacement JCS 1200 Chassis
Related Topics
■
■
■
To install a components in a replacement JCS 1200 chassis:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Install the fan shuttle into the JCS 1200 chassis (see “Installing a JCS 1200 Fan
4.
Push the following components fully into the front of the JCS 1200 platform to reengage the midplane:
■
■
Routing Engines: Slide each Routing Engine or filler into the bay; then push
the two release handles to the closed position (see “Installing a JCS 1200
Media trays: Slide each media tray or filler into the JCS 1200 platform; then
push the release handle to the closed position (see “Installing a JCS 1200
■
■
Switch modules: Slide each switch module or filler into the JCS 1200 platform;
then push the release handle to the closed position (see “Installing a JCS 1200
Switch Module or Module Filler” on page 143).
Management modules: Slide each management module or filler into the
JCS 1200 platform; then push the release handle to the closed position (see
“Installing a JCS 1200 Management Module or Module Filler” on page 125).
5.
6.
7.
Slide each power module or filler into the bay; then push the release handle to
the closed position (see “Installing a JCS 1200 Power Module” on page 139).
Reconnect the power to the JCS 1200 platform (see “Connecting the JCS 1200
Restart any Routing Engines that were powered off in the JCS 1200 platform
(see “Powering On a JCS 1200 Routing Engine” on page 73).
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Locating the JCS 1200 Chassis Serial Number on page 196
Contacting Customer Support on page 206
114 ■
Installing Components in a Replacement JCS 1200 Chassis
Chapter 10: Replacing Components in a JCS 1200 Platform
Replacing a JCS 1200 DC Terminal Cover
Topics include:
■
■
Removing a JCS 1200 DC Terminal Cover on page 115
Installing a JCS 1200 DC Terminal Cover on page 115
Removing a JCS 1200 DC Terminal Cover
Figure 51 on page 115 shows how to remove and install a DC terminal cover.
Figure 51: Removing and Installing a JCS 1200 DC Terminal Cover
To remove a DC terminal cover from a JCS 1200 DC platform (see
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Power off each Routing Engine (see “Powering Off a JCS 1200 Routing
Turn off the power source.
NOTE: After you disconnect the JCS 1200 platform from power, wait at least 5 seconds before you connect the JCS 1200 platform to power again.
4.
5.
Remove the two Phillips-head screws that attach the terminal cover to the DC power box.
Pull the terminal cover away from the JCS 1200 platform.
Installing a JCS 1200 DC Terminal Cover
Figure 52 on page 116 shows how to remove and install a DC terminal cover.
Replacing a JCS 1200 DC Terminal Cover
■ 115
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 52: Removing and Installing a JCS 1200 DC Terminal Cover
To install a DC terminal cover on a JCS 1200 DC platform (see Figure 52 on page 116):
1.
2.
3.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Make sure power has been disconnected from the JCS 1200 platform.
Turn off the power source.
NOTE: After you disconnect the JCS 1200 platform from power, wait at least 5 seconds before you connect the JCS 1200 platform to power again.
Related Topics
■
■
4.
5.
Orient the terminal cover so that the terminal cover fits over the DC power terminals and the screw holes on the terminal cover are aligned with the screw holes on the DC power box.
Install two Phillips-head screws to attach the terminal cover to the power box.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Connecting the JCS 1200 DC Platform to DC Power on page 63
Replacing a JCS 1200 Fan Module
Topics include:
■
■
Removing a JCS 1200 Fan Module on page 116
Installing a JCS 1200 Fan Module on page 118
Removing a JCS 1200 Fan Module
Figure 53 on page 117 shows how to remove and install a fan module.
116 ■
Replacing a JCS 1200 Fan Module
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 53: Removing and Installing a JCS 1200 Fan Module
NOTE: While the JCS 1200 platform is operating, only one fan module should be removed at a time. Removing two fan modules might cause the JCS 1200 platform to overheat.
To remove a fan module (see Figure 53 on page 117):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the shipping block that is installed below the release levers:
Figure 54: Removing the Shipping Block
Removing a JCS 1200 Fan Module
■ 117
Juniper Control System (JCS) 1200 Platform Hardware Guide
NOTE: When the JCS 1200 platform is shipped, each fan module has a shipping block installed below the release lever that is on the same side as the fan module orientation mark.
a.
Remove the Phillips-head screw that attaches the shipping block to the
JCS 1200 platform.
b.
Pull the shipping block away from the JCS 1200 platform. Place the shipping block and screw in a safe place.
3.
4.
Press down on the release levers on either side of the fan module you are removing. The module moves out of the bay approximately 0.25 in. (0.6 cm).
Pull the fan module out of the bay.
Installing a JCS 1200 Fan Module
Figure 55 on page 118 shows how to remove and install a fan module.
Figure 55: Removing and Installing a JCS 1200 Fan Module
To install a fan module (see Figure 55 on page 118):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Orient the fan module to the selected fan module bay.
118 ■
Installing a JCS 1200 Fan Module
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 56: Fan Module Orientation Marks a.
If you are installing a fan module in fan module bay 1 or 2, orient the fan so the orientation mark is at the bottom-right corner.
b.
If you are installing a fan module in fan module bay 3 or 4, orient the fan so the orientation mark is at the top-left corner.
3.
Slide the fan module into the bay until it stops.
NOTE: Make sure the release levers for the fan module return to a locked position.
4.
If you are shipping the JCS 1200 platform to another location, install the shipping block that came with the JCS 1200 platform.
NOTE: When the JCS 1200 platform is shipped, a shipping block must be installed for each fan module. The shipping block is installed below the release lever that is on the same side as the fan module orientation mark.
Figure 57: Installing the JCS 1200 Shipping Block a.
Orient the shipping block below the release lever on the same side as the orientation mark on the fan module.
b.
Push the shipping block into the slot below the release lever.
Installing a JCS 1200 Fan Module
■ 119
Juniper Control System (JCS) 1200 Platform Hardware Guide c.
Install the Phillips-head screw that attaches the shipping block to the JCS 1200 platform.
Related Topics
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 Fan Module Description on page 14
Locating the JCS 1200 Fan Module Serial Number on page 198
Replacing a JCS 1200 Fan Pack
Topics include:
■
■
Removing a JCS 1200 Fan Pack on page 120
Installing a JCS 1200 Fan Pack on page 121
Removing a JCS 1200 Fan Pack
Figure 58 on page 120 shows how to remove and install a fan pack.
Figure 58: Removing and Installing a JCS 1200 Fan Pack
2.
3.
To remove a fan pack from a power module (see Figure 58 on page 120):
1.
4.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the selected power module.
With the power module rear connector facing up, rotate the handle down so that it is parallel with the bottom of the module.
Press the blue release tabs on each side of the fan pack.
120 ■
Replacing a JCS 1200 Fan Pack
Chapter 10: Replacing Components in a JCS 1200 Platform
5.
6.
Pull the fan pack away from the power module.
If you are instructed to return the fan pack, follow all packaging instructions and use any packaging materials for shipping that are supplied to you.
Installing a JCS 1200 Fan Pack
Figure 59 on page 121 shows how to remove and install a fan pack.
Figure 59: Removing and Installing a JCS 1200 Fan Pack
To install a fan pack on a power module (see Figure 59 on page 121):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Make sure that the handle is rotated down so that it is parallel with the bottom of the module, with the power module rear connector facing up.
3.
4.
Slide the fan pack into position on the power module until it stops and locks into place.
Rotate the power module handle to the open position.
5.
Install the power module.
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Fan Shuttle
Topics include:
■
■
Removing a JCS 1200 Fan Shuttle on page 122
Installing a JCS 1200 Fan Shuttle on page 123
Installing a JCS 1200 Fan Pack
■ 121
Juniper Control System (JCS) 1200 Platform Hardware Guide
Removing a JCS 1200 Fan Shuttle
Figure 60 on page 122 shows how to remove and install a fan shuttle.
Figure 60: Removing and Installing a JCS 1200 Fan Shuttle
To remove the fan shuttle (see Figure 60 on page 122):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Power off any Routing Engines in the JCS 1200 platform (see “Powering Off a
JCS 1200 Routing Engine” on page 74).
3.
4.
5.
If the JCS 1200 platform is connected to a power source, disconnect the power from the JCS 1200 platform and remove the power cables.
Disconnect the cables from the modules in the rear of JCS 1200 platform.
Remove any of the following modules that are installed in the rear of the JCS 1200 platform:
■
■
Fan modules (see “Removing a JCS 1200 Fan Module” on page 116).
Network clock fillers (see “Removing a JCS 1200 Network Clock
■
■
MUX cards (see “Removing a JCS 1200 MUX Card” on page 131).
Alarm panel module (see “Removing a JCS 1200 Alarm Panel Module or
6.
Loosen the four captive thumb screws on the fan shuttle.
122 ■
Removing a JCS 1200 Fan Shuttle
Chapter 10: Replacing Components in a JCS 1200 Platform
7.
Loosen the captive thumbscrews on the release handles, and pull the handles to the open position. The fan shuttle moves out of the JCS 1200 chassis approximately 0.5 in. (1.3 cm).
CAUTION: Use your hands to hold the frame of the fan shuttle where the fan module bays are located. Do not use the release handles to hold the fan shuttle.
8.
While you support the fan shuttle with your hands, pull the fan shuttle out of the
JCS 1200 chassis.
Installing a JCS 1200 Fan Shuttle
Figure 61 on page 123 shows how to remove and install a fan shuttle.
Figure 61: Removing and Installing a JCS 1200 Fan Shuttle
To install the shuttle (see Figure 61 on page 123):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Make sure that no modules are installed in the fan shuttle and the release handles on the shuttle are in the open position.
CAUTION: Use your hands to hold the frame of the fan shuttle where the fan module bays are located. Do not use the release handles to hold the fan shuttle.
Installing a JCS 1200 Fan Shuttle
■ 123
Juniper Control System (JCS) 1200 Platform Hardware Guide
6.
7.
3.
4.
5.
Orient the fan shuttle so that fan module bays 1 and 3 are above fan module bays 2 and 4.
Align the shuttle with the JCS 1200 chassis and push the shuttle into the chassis until it stops.
Push the release handles to the closed position. The shuttle moves back fully into the JCS 1200 chassis.
Tighten the four captive thumbscrews on the fan shuttle.
Tighten the captive thumbscrew on each release handle.
CAUTION: The release handles have a safety switch that disables power output from the power boxes. If the release handles are not secured to the chassis with the thumbscrews, the JCS 1200 platform will not power on.
Related Topics
■
■
■
8.
Install any of the following modules that you removed from the rear of the
JCS 1200 platform:
■
Fan modules (see “Installing a JCS 1200 Fan Module” on page 118).
■
Network clock fillers (see “Installing a JCS 1200 Network Clock
■
MUX card (see “Installing a JCS 1200 MUX Card” on page 131).
■
Alarm panel module (see “Installing a JCS 1200 Alarm Panel Module or
9.
Reconnect any cables that you disconnected from the modules in the rear of the
JCS 1200 platform.
10.
Reconnect the power to the JCS 1200 platform (see “Connecting the JCS 1200
11.
Restart any Routing Engines that were powered off in the JCS 1200 platform.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Powering On a JCS 1200 Routing Engine on page 73
Powering Off a JCS 1200 Routing Engine on page 74
Replacing a JCS 1200 Management Module or Module Filler
Topics include:
■
■
Removing a JCS 1200 Management Module or Module Filler on page 124
Installing a JCS 1200 Management Module or Module Filler on page 125
Removing a JCS 1200 Management Module or Module Filler
Figure 62 on page 125 shows how to remove and install a management module.
124 ■
Replacing a JCS 1200 Management Module or Module Filler
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 62: Removing and Installing a JCS 1200 Management Module
When you remove a management module, keep in mind the following:
■
These instructions assume that the JCS 1200 platform is connected to power.
■
■
If you are replacing the only management module in the JCS 1200 platform and the management module is functioning, save the configuration file before you proceed. For information about saving and restoring a configuration file, see the
JUNOS Protected System Domain Configuration Guide.
If you have just installed a second management module in the JCS 1200 platform, do not remove the first (primary) management module for up to 45 minutes; the second (redundant) management module needs the time to receive initial status information and firmware from the management module.
To remove a management module or module filler (see Figure 62 on page 125):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Pull the management module release handle to the open position. The module moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the management module out of the bay.
Installing a JCS 1200 Management Module or Module Filler
Figure 63 on page 126 shows how to remove and install a management module.
Installing a JCS 1200 Management Module or Module Filler
■ 125
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 63: Removing and Installing a JCS 1200 Management Module
Related Topics
■
■
■
■
8.
9.
6.
7.
3.
4.
5.
To install a management module or module filler (see Figure 63 on page 126):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the management module filler, if one is installed.
Remove the management module interposer filler tray, if one is installed.
Install the management module interposer, if it is not already installed.
Make sure that the release handle on the management module is in the open position.
Slide the management module into the management module bay until it stops.
Push the management module release handle to the closed position.
Connect any cables to the management module.
If the JCS 1200 platform is connected to power, make sure that the OK LED on the management module is lit. If the management module is redundant, wait at least 45 minutes for the modules to copy the configuration data before you make any changes to the management module configuration.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 Management Module Description on page 15
Replacing a JCS 1200 Management Module Filler Tray on page 127
Locating the JCS 1200 Management Module Serial Number on page 199
126 ■
Installing a JCS 1200 Management Module or Module Filler
Chapter 10: Replacing Components in a JCS 1200 Platform
Replacing a JCS 1200 Management Module Filler Tray
Topics include:
■
■
Removing a JCS 1200 Management Module Filler Tray on page 127
Installing a JCS 1200 Management Module Filler Tray on page 128
Removing a JCS 1200 Management Module Filler Tray
Figure 64 on page 127 shows how to remove and install a management module filler
tray.
Figure 64: Removing and Installing a JCS 1200 Management Module Filler Tray
To remove a management module filler tray (see Figure 64 on page 127):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Remove the management module or filler from the management module bay
(see “Removing a JCS 1200 Management Module or Module Filler” on page 124).
3.
4.
Pull the management module filler tray release handle to the open position. The filler tray moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the filler tray out of the bay.
Replacing a JCS 1200 Management Module Filler Tray
■ 127
Juniper Control System (JCS) 1200 Platform Hardware Guide
Installing a JCS 1200 Management Module Filler Tray
Related Topics
■
■
■
4.
5.
6.
2.
3.
To install a management module filler tray:
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the management module filler and management module tray filler.
Make sure that the release handle on the filler tray is in the open position.
Slide the filler tray into the management module bay until it stops.
Push the filler tray release handle to the closed position.
Install a management module or filler (see “Installing a JCS 1200 Management
Module or Module Filler” on page 125).
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Management Module Interposer on page 128
Replacing a JCS 1200 Management Module or Module Filler on page 124
Replacing a JCS 1200 Management Module Interposer
NOTE: The management module interposer is not a field-replaceable unit (FRU). You cannot order a management module interposer separately. If the management module interposer requires replacement, you must replace the entire chassis. For
instructions on replacing the chassis, see “Replacing a JCS 1200 Chassis” on page 113.
Related Topics
■
■
■
Replacing a JCS 1200 Chassis on page 113
Locating the JCS 1200 Chassis Serial Number on page 196
Contacting Customer Support on page 206
Replacing a JCS 1200 Media Tray
Topics include:
■
■
Removing a JCS 1200 Media Tray on page 128
Installing a JCS 1200 Media Tray on page 129
Removing a JCS 1200 Media Tray
Figure 65 on page 129 shows how to remove a media tray.
128 ■
Installing a JCS 1200 Management Module Filler Tray
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 65: Removing a JCS 1200 Media Tray
To remove a media tray (see Figure 65 on page 129):
1.
2.
3.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Pull the media tray release handle to the open position. The media tray moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the media tray out of the bay.
Installing a JCS 1200 Media Tray
Figure 66 on page 129 shows how to install a media tray.
Figure 66: Installing a JCS 1200 Media Tray
Installing a JCS 1200 Media Tray
■ 129
Juniper Control System (JCS) 1200 Platform Hardware Guide
To install a media tray (see Figure 66 on page 129):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Make sure that the media tray release lever is in the open position and the compact flash release buttons are pushed into the in position.
Figure 67: Positioning the Release Lever and Button on the JCS 1200 Media Tray
Related Topics
■
■
■
■
3.
4.
Slide the media tray into position until it stops and locks into place.
Rotate the media tray release lever to the closed position.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 Media Tray Description on page 18
JCS 1200 Media Tray Connectors and LEDs on page 19
Locating the JCS 1200 Media Tray Serial Number on page 200
Replacing a JCS 1200 Midplane
NOTE: The midplane is not a field-replaceable unit (FRU). You cannot order a midplane separately. If the midplane requires replacement, you must replace the entire chassis.
For instructions on replacing the chassis, see “Replacing a JCS 1200
Related Topics
■
■
■
Replacing a JCS 1200 Chassis on page 113
Locating the JCS 1200 Chassis Serial Number on page 196
Contacting Customer Support on page 206
130 ■
Replacing a JCS 1200 Midplane
Chapter 10: Replacing Components in a JCS 1200 Platform
Replacing a JCS 1200 MUX Card
Topics include:
■
■
Removing a JCS 1200 MUX Card on page 131
Installing a JCS 1200 MUX Card on page 131
Removing a JCS 1200 MUX Card
Figure 68 on page 131 shows how to remove and install a multiplexer (MUX) card.
Figure 68: Removing and Installing a JCS 1200 MUX Card
To remove a MUX card (see Figure 68 on page 131):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Pull the release handle to the open position. The MUX card moves out of the bay approximately 0.25 inch (0.6 cm).
Slide the MUX card out of the bay.
Installing a JCS 1200 MUX Card
Figure 69 on page 132 shows how to remove and install a multiplexer (MUX) card.
Replacing a JCS 1200 MUX Card
■ 131
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 69: Removing and Installing a JCS 1200 MUX Card
Related Topics
■
■
■
2.
3.
4.
To install a MUX card (see Figure 69 on page 132):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Make sure that the release handle on the MUX card is in the open position.
Slide the MUX card into the bay until it stops.
Push the release handle to the closed position.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 MUX Card LEDs on page 21
Locating the JCS 1200 MUX Card Serial Number on page 201
Replacing a JCS 1200 Network Clock Filler
Topics include:
■
■
Removing a JCS 1200 Network Clock Filler on page 132
Installing a JCS 1200 Network Clock Filler on page 133
Removing a JCS 1200 Network Clock Filler
Figure 70 on page 133 shows how to remove and install a network clock filler.
132 ■
Replacing a JCS 1200 Network Clock Filler
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 70: Removing and Installing a JCS 1200 Network Clock Filler
To remove a network clock filler (see Figure 70 on page 133):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Pull the release handle to the open position. The network clock filler moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the network clock filler out of the bay.
Installing a JCS 1200 Network Clock Filler
Figure 71 on page 134 shows how to remove and install a network clock filler.
Installing a JCS 1200 Network Clock Filler
■ 133
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 71: Removing and Installing a JCS 1200 Network Clock Filler
To install a network clock filler (see Figure 71 on page 134):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
4.
Make sure that the release handle on the network clock filler is in the open position.
Slide the network clock filler into the module bay until it stops.
Push the release handle to the closed position.
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Power Box
Topics include:
■
■
Removing a JCS 1200 Power Box on page 134
Installing a JCS 1200 Power Box on page 136
Removing a JCS 1200 Power Box
Figure 72 on page 135 shows how to remove and install a power box.
134 ■
Replacing a JCS 1200 Power Box
Chapter 10: Replacing Components in a JCS 1200 Platform
Figure 72: Removing and Installing a JCS 1200 Power Box
To remove a power box (see Figure 72 on page 135):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
Power off any Routing Engines in the JCS 1200 platform (“Powering Off a
JCS 1200 Routing Engine” on page 74).
4.
5.
6.
Remove the fan shuttle from the JCS 1200 platform (see “Removing a JCS 1200
Remove the five Phillips-head screws that attach the power box to the chassis.
Loosen the two captive thumbscrews on the power box by turning them
counter-clockwise approximately eight turns (see Figure 73 on page 135 and
Figure 73: Loosening Thumbscrews on the Upper Power Box
Removing a JCS 1200 Power Box
■ 135
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 74: Loosening Thumbscrews on the Lower Power Box
7.
8.
Slide the power box away from the JCS 1200 platform.
If you are instructed to return the power box, follow all packaging instructions and use any packaging materials for shipping that are supplied to you.
Installing a JCS 1200 Power Box
Figure 75 on page 136 shows how to remove and install a power box.
Figure 75: Removing and Installing a JCS 1200 Power Box
To install a power box (see Figure 75 on page 136):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Orient the connectors on the back of the power box with the connectors in the
JCS 1200 chassis.
136 ■
Installing a JCS 1200 Power Box
Chapter 10: Replacing Components in a JCS 1200 Platform
3.
4.
Slide the power box into the JCS 1200 chassis.
Tighten the two captive thumbscrews on the power box by turning the
Figure 76: Tightening Thumbscrews on the Upper Power Box
Figure 77: Tightening Thumbscrews on the Lower Power Box
5.
6.
7.
8.
9.
Install the five Phillips-head screws that attach the power box to the chassis.
Install the fan shuttle into the JCS 1200 platform (see “Installing a JCS 1200 Fan
Reconnect any cables that were disconnected from the modules in the rear of the JCS 1200 platform.
Reconnect the power to the JCS 1200 platform (see “Connecting the JCS 1200
Restart any Routing Engines that were powered off in the JCS 1200 platform
(see “Powering On a JCS 1200 Routing Engine” on page 73).
Installing a JCS 1200 Power Box
■ 137
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Power Module
Topics include:
■
■
Removing a JCS 1200 Power Module on page 138
Installing a JCS 1200 Power Module on page 139
Removing a JCS 1200 Power Module
Figure 78 on page 138 shows how to remove and install a power module.
Figure 78: Removing and Installing a JCS 1200 Power Module
To remove a power module (see Figure 78 on page 138):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Open the power module handle, using one of the following procedures:
■
■
For a power module in one of the upper power module bays, push the inner handle release to the right; then pull the handle up to the open position.
For a power module in one of the lower power module bays, push the inner handle release to the left; then pull the handle down to the open position.
3.
Use the handle to pull the power module out of the bay.
138 ■
Replacing a JCS 1200 Power Module
Chapter 10: Replacing Components in a JCS 1200 Platform
Installing a JCS 1200 Power Module
Figure 79 on page 139 shows how to remove and install a power module.
Figure 79: Removing and Installing a JCS 1200 Power Module
3.
4.
To install a power module (see Figure 79 on page 139):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the power module filler, if one is installed.
Make sure that the handle on the power module is in the open position.
Orient the new power module to the selected power module bay:
■
For the upper power module bays, the rear connector on the power module must be facing down.
■
For the lower power module bays, the rear connector on the power module must be facing up.
Related Topics
■
■
■
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
JCS 1200 Power Module Description on page 22
JCS 1200 Power Module LEDs on page 23
Locating the JCS 1200 Power Module Serial Number on page 202
Installing a JCS 1200 Power Module
■ 139
Juniper Control System (JCS) 1200 Platform Hardware Guide
Replacing a JCS 1200 Routing Engine
Topics include:
■
■
Removing a JCS 1200 Routing Engine on page 140
Installing a JCS 1200 Routing Engine on page 141
Removing a JCS 1200 Routing Engine
Figure 80 on page 140 shows how to remove and install a Routing Engine.
Figure 80: Removing and Installing a JCS 1200 Routing Engine
CAUTION:
■
To maintain proper system cooling, do not operate the JCS 1200 platform without a Routing Engine or Routing Engine filler installed in each bay.
■
When you remove the Routing Engine, note the bay number. Reinstalling a
Routing Engine into a different bay from the one from which it was removed could have unintended consequences. Some configuration information and update options are established according to bay number; if you reinstall the
Routing Engine into a different bay, you might need to reconfigure the Routing
Engine.
To remove a Routing Engine (see Figure 80 on page 140):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
Issue the shutdown –T system:blade[x] command (where x is a value of 1 through
12) from the management module CLI. The command shuts down the Routing
140 ■
Replacing a JCS 1200 Routing Engine
Chapter 10: Replacing Components in a JCS 1200 Platform
3.
Engines cleanly, so their state information is preserved. For more information, see the JUNOS Protected System Domain Configuration Guide.
Power off the Routing Engine.
4.
5.
6.
Wait at least 30 seconds until the drives stop spinning before you proceed to the next step.
Open the two release handles as shown in Figure 80 on page 140. The Routing
Engine moves out of the bay approximately 0.25 in. (0.6 cm).
Pull the Routing Engine out of the bay.
Place either a Routing Engine filler or another Routing Engine into the bay within
1 minute.
Installing a JCS 1200 Routing Engine
Figure 81 on page 141 shows how to remove and install a Routing Engine.
Figure 81: Removing and Installing a JCS 1200 Routing Engine
CAUTION: Hazardous energy is present when the Routing Engine is connected to the power source. Always close the Routing Engine cover before installing the Routing
Engine.
To install a Routing Engine (see Figure 81 on page 141):
1.
2.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Select the bay for the Routing Engine.
Installing a JCS 1200 Routing Engine
■ 141
Juniper Control System (JCS) 1200 Platform Hardware Guide
NOTE:
■
Depending on the Routing Engine type and the optional devices that are installed in it, one or more adjacent bays might be required.
■
When any Routing Engine or device is in any Routing Engine bay 7 through 12, power modules must be installed in all four power bays.
■
To help ensure proper cooling, performance, and system reliability, make sure that each Routing Engine bay on the front of the JCS 1200 platform contains a
Routing Engine, expansion unit, or Routing Engine filler. Do not operate a
JCS 1200 platform for more than 1 minute without a Routing Engine, expansion unit, or Routing Engine filler in each Routing Engine bay.
4.
7.
8.
5.
6.
3.
9.
Remove the filler from the bay, if one is installed (see “Removing a JCS 1200
Make sure that the two release handles are in the open position.
Slide the Routing Engine into the bay until it stops.
Push the two release handles to the closed position.
Power on the Routing Engine.
Make sure that the power-on LED on the Routing Engine control panel is lit continuously, indicating that the Routing Engine is receiving power and is turned on.
If you are installing a new Routing Engine, write identifying information about one of the user labels that comes with the Routing Engine; then place the label
If you reinstall a Routing Engine that you removed, you must install it in the same
Routing Engine bay from which you removed it. Some Routing Engine configuration information and update options are established according to bay number. Reinstalling a Routing Engine into a different Routing Engine bay from the one from which it was removed can have unintended consequences, and you might have to reconfigure the Routing Engine.
Related Topics
■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
■
■
JCS 1200 Routing Engine Description on page 24
JCS 1200 Routing Engine Control Panel Buttons and LEDs on page 25
■
■
■
Powering On a JCS 1200 Routing Engine on page 73
Powering Off a JCS 1200 Routing Engine on page 74
Locating the JCS 1200 Routing Engine Serial Number on page 203
142 ■
Installing a JCS 1200 Routing Engine
Chapter 10: Replacing Components in a JCS 1200 Platform
Replacing a JCS 1200 Switch Module or Module Filler
Topics include:
■
■
Removing a JCS 1200 Switch Module or Module Filler on page 143
Installing a JCS 1200 Switch Module or Module Filler on page 143
Removing a JCS 1200 Switch Module or Module Filler
Figure 82 on page 143 shows how to remove and install a switch module.
Figure 82: Removing and Installing a JCS 1200 Switch Module
To remove a switch module or module filler (see Figure 82 on page 143):
1.
2.
3.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Pull the release handle to the open position. The module moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the switch module out of the bay.
Installing a JCS 1200 Switch Module or Module Filler
Figure 83 on page 144 shows how to remove and install a switch module.
Replacing a JCS 1200 Switch Module or Module Filler
■ 143
Juniper Control System (JCS) 1200 Platform Hardware Guide
Figure 83: Removing and Installing a JCS 1200 Switch Module
Related Topics
■
■
■
■
■
The JCS 1200 platform ships with one switch module. You can install a second switch module for redundancy.
To install a switch module (see Figure 83 on page 144):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
4.
5.
Remove the switch module filler, if one is installed (see “Removing a JCS 1200
Switch Module or Module Filler” on page 143).
Make sure that the release handle is in the open position.
Slide the switch module into the switch module interposer until it stops.
Push the switch module release handle to the closed position.
6.
Connect the cables to the switch module.
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Switch Module Interposer on page 146
JCS 1200 Switch Module Description on page 27
JCS 1200 Switch Module Components and LEDs on page 27
Locating the JCS 1200 Switch Module Serial Number on page 205
144 ■
Installing a JCS 1200 Switch Module or Module Filler
Chapter 10: Replacing Components in a JCS 1200 Platform
Replacing a JCS 1200 Switch Module Filler Tray
Topics include:
■
■
Removing a JCS 1200 Switch Module Filler Tray on page 145
Installing a JCS 1200 Switch Module Filler Tray on page 146
Removing a JCS 1200 Switch Module Filler Tray
Figure 84 on page 145 shows how to remove and install a switch module filler tray.
Figure 84: Removing and Installing a JCS 1200 Switch Module Filler Tray
To remove a switch module filler tray (see Figure 84 on page 145):
1.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
2.
3.
4.
Pull the filler tray release handle to the open position. The filler tray moves out of the bay approximately 0.25 in. (0.6 cm).
Slide the filler tray out of the bay.
Replacing a JCS 1200 Switch Module Filler Tray
■ 145
Juniper Control System (JCS) 1200 Platform Hardware Guide
Installing a JCS 1200 Switch Module Filler Tray
Related Topics
■
■
3.
4.
5.
To install a switch module filler tray:
1.
2.
6.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Remove the switch module filler and filler tray, if one is installed (see “Removing
a JCS 1200 Switch Module or Module Filler” on page 143 and “Removing a
JCS 1200 Switch Module Filler Tray” on page 145).
Make sure that the release handle is in the open position.
Slide the switch module filler tray into the switch module bay until it stops.
Push the filler tray release handle to the closed position.
Install a switch module or filler (see “Installing a JCS 1200 Switch Module or
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
Replacing a JCS 1200 Chassis on page 113
Replacing a JCS 1200 Switch Module Interposer
NOTE: The switch module interposer is not a field-replaceable unit (FRU). You cannot order a switch module interposer separately. If the switch module interposer requires replacement, you must replace the entire chassis. For instructions on replacing the
chassis, see “Replacing a JCS 1200 Chassis” on page 113.
Related Topics
■
■
■
Replacing a JCS 1200 Chassis on page 113
Locating the JCS 1200 Chassis Serial Number on page 196
Contacting Customer Support on page 206
146 ■
Installing a JCS 1200 Switch Module Filler Tray
Part 4
Appendixes
■
■
■
■
■
Safety and Regulatory Compliance Information on page 149
Environmental Specifications on page 187
Power Requirements, Guidelines, and Specifications on page 189
Contacting Customer Support and Returning Hardware on page 195
Cable Connector Pinouts on page 211
Appendixes
■ 147
Juniper Control System (JCS) 1200 Platform Hardware Guide
148 ■
Appendixes
Appendix A
Safety and Regulatory Compliance
Information
To install and use the JCS 1200 platform safely, follow proper safety procedures. This appendix discusses the following safety and regulatory compliance information:
■
■
Definition of Safety Warning Levels on page 149
JCS 1200 Safety Guidelines and Warnings on page 150
Definition of Safety Warning Levels
The JCS 1200 platform documentation uses the following three levels of safety warnings:
NOTE: You might find this information helpful in a particular situation, or might otherwise overlook it.
CAUTION: You need to observe the specified guidelines to avoid minor injury or discomfort to you, or severe damage to the routing platform.
WARNING: This symbol means danger. You are in a situation that could cause bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical circuitry and be familiar with standard practices for preventing accidents.
Waarschuwing Dit waarschuwingssymbool betekent gevaar. U verkeert in een situatie die lichamelijk letsel kan veroorzaken. Voordat u aan enige apparatuur gaat werken, dient u zich bewust te zijn van de bij elektrische schakelingen betrokken risico's en dient u op de hoogte te zijn van standaard maatregelen om ongelukken te voorkomen.
Varoitus Tämä varoitusmerkki merkitsee vaaraa. Olet tilanteessa, joka voi johtaa ruumiinvammaan. Ennen kuin työskentelet minkään laitteiston parissa, ota selvää sähkökytkentöihin liittyvistä vaaroista ja tavanomaisista onnettomuuksien ehkäisykeinoista.
Definition of Safety Warning Levels
■ 149
Juniper Control System (JCS) 1200 Platform Hardware Guide
Attention Ce symbole d'avertissement indique un danger. Vous vous trouvez dans une situation pouvant causer des blessures ou des dommages corporels. Avant de travailler sur un équipement, soyez conscient des dangers posés par les circuits
électriques et familiarisez-vous avec les procédures couramment utilisées pour éviter les accidents.
Warnung Dieses Warnsymbol bedeutet Gefahr. Sie befinden sich in einer Situation, die zu einer Körperverletzung führen könnte. Bevor Sie mit der Arbeit an irgendeinem
Gerät beginnen, seien Sie sich der mit elektrischen Stromkreisen verbundenen
Gefahren und der Standardpraktiken zur Vermeidung von Unfällen bewußt.
Avvertenza Questo simbolo di avvertenza indica un pericolo. La situazione potrebbe causare infortuni alle persone. Prima di lavorare su qualsiasi apparecchiatura, occorre conoscere i pericoli relativi ai circuiti elettrici ed essere al corrente delle pratiche standard per la prevenzione di incidenti.
Advarsel Dette varselsymbolet betyr fare. Du befinner deg i en situasjon som kan føre til personskade. Før du utfører arbeid på utstyr, må du vare oppmerksom på de faremomentene som elektriske kretser innebærer, samt gjøre deg kjent med vanlig praksis når det gjelder å unngå ulykker.
Aviso Este símbolo de aviso indica perigo. Encontra-se numa situação que lhe poderá causar danos físicos. Antes de começar a trabalhar com qualquer equipamento, familiarize-se com os perigos relacionados com circuitos eléctricos, e com quaisquer práticas comuns que possam prevenir possíveis acidentes.
¡Atención! Este símbolo de aviso significa peligro. Existe riesgo para su integridad física. Antes de manipular cualquier equipo, considerar los riesgos que entraña la corriente eléctrica y familiarizarse con los procedimientos estándar de prevención de accidentes.
Varning! Denna varningssymbol signalerar fara. Du befinner dig i en situation som kan leda till personskada. Innan du utför arbete på någon utrustning måste du vara medveten om farorna med elkretsar och känna till vanligt förfarande för att förebygga skador.
Related Topics
■
General Safety Guidelines and Warnings for the JCS 1200 Platform on page 151
JCS 1200 Safety Guidelines and Warnings
■
■
■
■
■
JCS 1200 General Safety Guidelines and Warnings on page 151
Fire Safety Requirements for the JCS 1200 Platform on page 155
JCS 1200 Installation Safety Guidelines and Warnings on page 155
JCS 1200 Laser and LED Safety Guidelines and Warnings on page 160
JCS 1200 Maintenance and Operational Safety Guidelines and
150 ■
JCS 1200 Safety Guidelines and Warnings
Appendix A: Safety and Regulatory Compliance Information
■
■
JCS 1200 Electrical Safety Guidelines and Warnings on page 169
JCS 1200 Agency Approvals and Compliance Statements on page 181
JCS 1200 General Safety Guidelines and Warnings
The following guidelines help ensure your safety and protect the platform from damage. The list of guidelines might not address all potentially hazardous situations in your working environment, so be alert and exercise good judgment at all times.
■
■
■
■
General Safety Guidelines and Warnings for the JCS 1200 Platform on page 151
Qualified Personnel Warning for the JCS 1200 Platform on page 152
Restricted Access Area Warning for the JCS 1200 Platform on page 152
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform on page 154
General Safety Guidelines and Warnings for the JCS 1200 Platform
The general safety guidelines and warnings help ensure your safety and protect the routing platform from damage. The list of guidelines might not address all potentially hazardous situations in your working environment, so be alert and exercise good judgment at all times.
■
■
Perform only the procedures explicitly described in this manual. Make sure that only authorized service personnel perform other system services.
Keep the area around the chassis clear and free from dust before, during, and after installation.
■
■
■
■
■
Keep tools away from areas where people could trip over them while walking.
Do not wear loose clothing or jewelry, such as rings, bracelets, or chains, which could become caught in the chassis.
Wear safety glasses if you are working under any conditions that could be hazardous to your eyes.
Do not perform any actions that create a potential hazard to people or make the equipment unsafe.
Never attempt to lift an object that is too heavy for one person to handle.
■
■
■
■
■
■
Never install or manipulate wiring during electrical storms.
Never install electrical jacks in wet locations unless the jacks are specifically designed for wet environments.
Operate the routing platform only when it is properly grounded.
Replace fuses only with fuses of the same type and rating. (Applies only to the
M320 and T320 routers.)
Do not open or remove chassis covers or sheet metal parts unless instructions are provided in this manual. Such an action could cause severe electrical shock.
Do not push or force any objects through any opening in the chassis frame. Such an action could result in electrical shock or fire.
General Safety Guidelines and Warnings for the JCS 1200 Platform
■ 151
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
Avoid spilling liquid onto the routing platform chassis or onto any routing platform component. Such an action could cause electrical shock or damage the routing platform.
Avoid touching uninsulated electrical wires or terminals that have not been disconnected from their power source. Such an action could cause electrical shock.
Related Topics
■
Definition of Safety Warning Levels on page 149
Qualified Personnel Warning for the JCS 1200 Platform
WARNING: Only trained and qualified personnel should install or replace the routing platform.
Waarschuwing Installatie en reparaties mogen uitsluitend door getraind en bevoegd personeel uitgevoerd worden.
Varoitus Ainoastaan koulutettu ja pätevä henkilökunta saa asentaa tai vaihtaa tämän laitteen.
Attention Tout installation ou remplacement de l'appareil doit être réalisé par du personnel qualifié et compétent.
Warnung Gerät nur von geschultem, qualifiziertem Personal installieren oder auswechseln lassen.
Avvertenza Solo personale addestrato e qualificato deve essere autorizzato ad installare o sostituire questo apparecchio.
Advarsel Kun kvalifisert personell med riktig opplæring bør montere eller bytte ut dette utstyret.
Aviso Este equipamento deverá ser instalado ou substituído apenas por pessoal devidamente treinado e qualificado.
¡Atención! Estos equipos deben ser instalados y reemplazados exclusivamente por personal técnico adecuadamente preparado y capacitado.
Varning! Denna utrustning ska endast installeras och bytas ut av utbildad och kvalificerad personal.
Related Topics
■
Definition of Safety Warning Levels on page 149
Restricted Access Area Warning for the JCS 1200 Platform
WARNING: The routing platform is intended for installation in restricted access areas.
A restricted access area is an area to which access can be gained only by service
152 ■
Qualified Personnel Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information personnel through the use of a special tool, lock and key, or other means of security, and which is controlled by the authority responsible for the location.
Waarschuwing Dit toestel is bedoeld voor installatie op plaatsen met beperkte toegang. Een plaats met beperkte toegang is een plaats waar toegang slechts door servicepersoneel verkregen kan worden door middel van een speciaal instrument, een slot en sleutel, of een ander veiligheidsmiddel, en welke beheerd wordt door de overheidsinstantie die verantwoordelijk is voor de locatie.
Varoitus Tämä laite on tarkoitettu asennettavaksi paikkaan, johon pääsy on rajoitettua.
Paikka, johon pääsy on rajoitettua, tarkoittaa paikkaa, johon vain huoltohenkilöstö pääsee jonkin erikoistyökalun, lukkoon sopivan avaimen tai jonkin muun turvalaitteen avulla ja joka on paikasta vastuussa olevien toimivaltaisten henkilöiden valvoma.
Attention Cet appareil est à installer dans des zones d'accès réservé. Ces dernières sont des zones auxquelles seul le personnel de service peut accéder en utilisant un outil spécial, un mécanisme de verrouillage et une clé, ou tout autre moyen de sécurité. L'accès aux zones de sécurité est sous le contrôle de l'autorité responsable de l'emplacement.
Warnung Diese Einheit ist zur Installation in Bereichen mit beschränktem Zutritt vorgesehen. Ein Bereich mit beschränktem Zutritt ist ein Bereich, zu dem nur
Wartungspersonal mit einem Spezialwerkzeugs, Schloß und Schlüssel oder anderer
Sicherheitsvorkehrungen Zugang hat, und der von dem für die Anlage zuständigen
Gremium kontrolliert wird.
Avvertenza Questa unità deve essere installata in un'area ad accesso limitato. Un'area ad accesso limitato è un'area accessibile solo a personale di assistenza tramite un'attrezzo speciale, lucchetto, o altri dispositivi di sicurezza, ed è controllata dall'autorità responsabile della zona.
Advarsel Denne enheten er laget for installasjon i områder med begrenset adgang.
Et område med begrenset adgang gir kun adgang til servicepersonale som bruker et spesielt verktøy, lås og nøkkel, eller en annen sikkerhetsanordning, og det kontrolleres av den autoriteten som er ansvarlig for området.
Aviso Esta unidade foi concebida para instalação em áreas de acesso restrito. Uma
área de acesso restrito é uma área à qual apenas tem acesso o pessoal de serviço autorizado, que possua uma ferramenta, chave e fechadura especial, ou qualquer outra forma de segurança. Esta área é controlada pela autoridade responsável pelo local.
¡Atención! Esta unidad ha sido diseñada para instalarse en áreas de acceso restringido. Área de acceso restringido significa un área a la que solamente tiene acceso el personal de servicio mediante la utilización de una herramienta especial, cerradura con llave, o algún otro medio de seguridad, y que está bajo el control de la autoridad responsable del local.
Varning! Denna enhet är avsedd för installation i områden med begränsat tillträde.
Ett område med begränsat tillträde får endast tillträdas av servicepersonal med ett speciellt verktyg, lås och nyckel, eller annan säkerhetsanordning, och kontrolleras av den auktoritet som ansvarar för området.
Restricted Access Area Warning for the JCS 1200 Platform
■ 153
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
Definition of Safety Warning Levels on page 149
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform
Many routing platform hardware components are sensitive to damage from static electricity. Some components can be impaired by voltages as low as 30 V. You can easily generate potentially damaging static voltages whenever you handle plastic or foam packing material or if you move components across plastic or carpets. Observe the following guidelines to minimize the potential for electrostatic discharge (ESD) damage, which can cause intermittent or complete component failures:
■
Always use an ESD wrist strap or ankle strap, and make sure that it is in direct contact with your skin.
CAUTION: For safety, periodically check the resistance value of the ESD strap. The measurement should be in the range of 1 to 10 Mohms.
■
■
■
When handling any component that is removed from the chassis, make sure the equipment end of your ESD strap is attached to one of the electrostatic discharge points on the chassis.
Avoid contact between the component and your clothing. ESD voltages emitted from clothing can still damage components.
When removing or installing a component, always place it component-side up on an antistatic surface, in an antistatic card rack, or in an electrostatic bag (see
Figure 85 on page 154). If you are returning a component, place it in an
electrostatic bag before packing it.
Figure 85: Placing a Component into an Electrostatic Bag
154 ■
Preventing Electrostatic Discharge Damage to the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Related Topics
■
Definition of Safety Warning Levels on page 149
Fire Safety Requirements for the JCS 1200 Platform
In the event of a fire emergency involving routing platforms and other network equipment, the safety of people is the primary concern. Establish procedures for protecting people in the event of a fire emergency, provide safety training, and properly provision fire-control equipment and fire extinguishers.
In addition, establish procedures to protect your equipment in the event of a fire emergency. Juniper Networks products should be installed in an environment suitable for electronic equipment. We recommend that fire suppression equipment be available in the event of a fire in the vicinity of the equipment, and that all local fire, safety, and electrical codes and ordinances be observed when installing and operating your equipment.
Related Topics
■
Definition of Safety Warning Levels on page 149
JCS 1200 Installation Safety Guidelines and Warnings
Observe the following guidelines and warnings before and during platform installation:
■
■
■
■
JCS 1200 Chassis Lifting Guidelines on page 155
Installation Instructions Power Warning for the JCS 1200 Platform on page 156
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform on page 156
Ramp Warning for the JCS 1200 Platform on page 160
JCS 1200 Chassis Lifting Guidelines
Related Topics
■
■
The weight of a fully configured chassis is about 350 lb (158.8 kg). Observe the following guidelines for lifting and moving the platform:
■
Before moving the platform, read the guidelines in “Overview of Preparing the
Site for JCS 1200 Platform Installation” on page 33 to verify that the intended
site meets the specified power, environmental, and clearance requirements.
■
Do not attempt to lift a fully configured platform by yourself. Using a mechanical lift to maneuver the platform into a rack is recommended. If a lift cannot be used, a minimum of four people must lift the platform, and you must remove components from the chassis before lifting.
■
■
Before lifting or moving the platform, disconnect all external cables.
As when lifting any heavy object, lift most of the weight with your legs rather than your back. Keep your knees bent and your back relatively straight and avoid twisting your body as you lift. Balance the load evenly and be sure that your footing is solid.
Overview of Preparing the Site for JCS 1200 Platform Installation on page 33
Definition of Safety Warning Levels on page 149
Fire Safety Requirements for the JCS 1200 Platform
■ 155
Juniper Control System (JCS) 1200 Platform Hardware Guide
Installation Instructions Power Warning for the JCS 1200 Platform
WARNING: Read the installation instructions before you connect the routing platform to a power source.
Waarschuwing Raadpleeg de installatie-aanwijzingen voordat u het systeem met de voeding verbindt.
Varoitus Lue asennusohjeet ennen järjestelmän yhdistämistä virtalähteeseen.
Attention Avant de brancher le système sur la source d'alimentation, consulter les directives d'installation.
Warnung Lesen Sie die Installationsanweisungen, bevor Sie das System an die
Stromquelle anschließen.
Avvertenza Consultare le istruzioni di installazione prima di collegare il sistema all'alimentatore.
Advarsel Les installasjonsinstruksjonene før systemet kobles til strømkilden.
Aviso Leia as instruções de instalação antes de ligar o sistema à sua fonte de energia.
¡Atención! Ver las instrucciones de instalación antes de conectar el sistema a la red de alimentación.
Varning! Läs installationsanvisningarna innan du kopplar systemet till dess strömförsörjningsenhet.
Related Topics
■
Definition of Safety Warning Levels on page 149
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform
Ensure that the equipment rack into which the routing platform is installed is evenly and securely supported, to avoid the hazardous condition that could result from uneven mechanical loading.
WARNING:
To prevent bodily injury when mounting or servicing the routing platform in a rack, take the following precautions to ensure that the system remains stable. The following directives help maintain your safety:
■
■
The routing platform must be installed into a rack that is secured to the building structure.
The routing platform should be mounted at the bottom of the rack if it is the only unit in the rack.
156 ■
Installation Instructions Power Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
■
■
When mounting the routing platform in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack.
If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the platform in the rack.
Waarschuwing Om lichamelijk letsel te voorkomen wanneer u dit toestel in een rek monteert of het daar een servicebeurt geeft, moet u speciale voorzorgsmaatregelen nemen om ervoor te zorgen dat het toestel stabiel blijft. De onderstaande richtlijnen worden verstrekt om uw veiligheid te verzekeren:
■
■
De Juniper Networks router moet in een stellage worden geïnstalleerd die aan een bouwsel is verankerd.
Dit toestel dient onderaan in het rek gemonteerd te worden als het toestel het enige in het rek is.
■
■
Wanneer u dit toestel in een gedeeltelijk gevuld rek monteert, dient u het rek van onderen naar boven te laden met het zwaarste onderdeel onderaan in het rek.
Als het rek voorzien is van stabiliseringshulpmiddelen, dient u de stabilisatoren te monteren voordat u het toestel in het rek monteert of het daar een servicebeurt geeft.
Varoitus Kun laite asetetaan telineeseen tai huolletaan sen ollessa telineessä, on noudatettava erityisiä varotoimia järjestelmän vakavuuden säilyttämiseksi, jotta vältytään loukkaantumiselta. Noudata seuraavia turvallisuusohjeita:
■
Juniper Networks router on asennettava telineeseen, joka on kiinnitetty rakennukseen.
■
■
Jos telineessä ei ole muita laitteita, aseta laite telineen alaosaan.
Jos laite asetetaan osaksi täytettyyn telineeseen, aloita kuormittaminen sen alaosasta kaikkein raskaimmalla esineellä ja siirry sitten sen yläosaan.
■
Jos telinettä varten on vakaimet, asenna ne ennen laitteen asettamista telineeseen tai sen huoltamista siinä.
Attention Pour éviter toute blessure corporelle pendant les opérations de montage ou de réparation de cette unité en casier, il convient de prendre des précautions spéciales afin de maintenir la stabilité du système. Les directives ci-dessous sont destinées à assurer la protection du personnel:
■
■
Le rack sur lequel est monté le Juniper Networks router doit être fixé à la structure du bâtiment.
Si cette unité constitue la seule unité montée en casier, elle doit être placée dans le bas.
■
■
Si cette unité est montée dans un casier partiellement rempli, charger le casier de bas en haut en plaçant l'élément le plus lourd dans le bas.
Si le casier est équipé de dispositifs stabilisateurs, installer les stabilisateurs avant de monter ou de réparer l'unité en casier.
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform
■ 157
Juniper Control System (JCS) 1200 Platform Hardware Guide
Warnung Zur Vermeidung von Körperverletzung beim Anbringen oder Warten dieser
Einheit in einem Gestell müssen Sie besondere Vorkehrungen treffen, um sicherzustellen, daß das System stabil bleibt. Die folgenden Richtlinien sollen zur
Gewährleistung Ihrer Sicherheit dienen:
■
Der Juniper Networks router muß in einem Gestell installiert werden, das in der
Gebäudestruktur verankert ist.
■
■
■
Wenn diese Einheit die einzige im Gestell ist, sollte sie unten im Gestell angebracht werden.
Bei Anbringung dieser Einheit in einem zum Teil gefüllten Gestell ist das Gestell von unten nach oben zu laden, wobei das schwerste Bauteil unten im Gestell anzubringen ist.
Wird das Gestell mit Stabilisierungszubehör geliefert, sind zuerst die Stabilisatoren zu installieren, bevor Sie die Einheit im Gestell anbringen oder sie warten.
Avvertenza Per evitare infortuni fisici durante il montaggio o la manutenzione di questa unità in un supporto, occorre osservare speciali precauzioni per garantire che il sistema rimanga stabile. Le seguenti direttive vengono fornite per garantire la sicurezza personale:
■
■
■
Il Juniper Networks router deve essere installato in un telaio, il quale deve essere fissato alla struttura dell'edificio.
Questa unità deve venire montata sul fondo del supporto, se si tratta dell'unica unità da montare nel supporto.
Quando questa unità viene montata in un supporto parzialmente pieno, caricare il supporto dal basso all'alto, con il componente più pesante sistemato sul fondo del supporto.
■
Se il supporto è dotato di dispositivi stabilizzanti, installare tali dispositivi prima di montare o di procedere alla manutenzione dell'unità nel supporto.
Advarsel Unngå fysiske skader under montering eller reparasjonsarbeid på denne enheten når den befinner seg i et kabinett. Vær nøye med at systemet er stabilt.
Følgende retningslinjer er gitt for å verne om sikkerheten:
■
■
Juniper Networks router må installeres i et stativ som er forankret til bygningsstrukturen.
Denne enheten bør monteres nederst i kabinettet hvis dette er den eneste enheten i kabinettet.
■
■
Ved montering av denne enheten i et kabinett som er delvis fylt, skal kabinettet lastes fra bunnen og opp med den tyngste komponenten nederst i kabinettet.
Hvis kabinettet er utstyrt med stabiliseringsutstyr, skal stabilisatorene installeres før montering eller utføring av reparasjonsarbeid på enheten i kabinettet.
Aviso Para se prevenir contra danos corporais ao montar ou reparar esta unidade numa estante, deverá tomar precauções especiais para se certificar de que o sistema possui um suporte estável. As seguintes directrizes ajudá-lo-ão a efectuar o seu trabalho com segurança:
158 ■
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
■
■
■
■
O Juniper Networks router deverá ser instalado numa prateleira fixa à estrutura do edificio.
Esta unidade deverá ser montada na parte inferior da estante, caso seja esta a
única unidade a ser montada.
Ao montar esta unidade numa estante parcialmente ocupada, coloque os itens mais pesados na parte inferior da estante, arrumando-os de baixo para cima.
Se a estante possuir um dispositivo de estabilização, instale-o antes de montar ou reparar a unidade.
¡Atención! Para evitar lesiones durante el montaje de este equipo sobre un bastidor, o posteriormente durante su mantenimiento, se debe poner mucho cuidado en que el sistema quede bien estable. Para garantizar su seguridad, proceda según las siguientes instrucciones:
■
■
El Juniper Networks router debe instalarse en un bastidor fijado a la estructura del edificio.
Colocar el equipo en la parte inferior del bastidor, cuando sea la única unidad en el mismo.
■
■
Cuando este equipo se vaya a instalar en un bastidor parcialmente ocupado, comenzar la instalación desde la parte inferior hacia la superior colocando el equipo más pesado en la parte inferior.
Si el bastidor dispone de dispositivos estabilizadores, instalar éstos antes de montar o proceder al mantenimiento del equipo instalado en el bastidor.
Varning! För att undvika kroppsskada när du installerar eller utför underhållsarbete på denna enhet på en ställning måste du vidta särskilda försiktighetsåtgärder för att försäkra dig om att systemet står stadigt. Följande riktlinjer ges för att trygga din säkerhet:
■
■
Juniper Networks router måste installeras i en ställning som är förankrad i byggnadens struktur.
Om denna enhet är den enda enheten på ställningen skall den installeras längst ned på ställningen.
■
■
Om denna enhet installeras på en delvis fylld ställning skall ställningen fyllas nedifrån och upp, med de tyngsta enheterna längst ned på ställningen.
Om ställningen är försedd med stabiliseringsdon skall dessa monteras fast innan enheten installeras eller underhålls på ställningen.
Related Topics
■
■
■
■
Definition of Safety Warning Levels on page 149
JCS 1200 Platform Rack-Mounting Hardware on page 43
Installing the JCS 1200 Mounting Hardware for a Four-Post Rack or
Installing the JCS 1200 Mounting Hardware for an Open-Frame Rack on page 46
Rack-Mounting Requirements and Warnings for the JCS 1200 Platform
■ 159
Juniper Control System (JCS) 1200 Platform Hardware Guide
Ramp Warning for the JCS 1200 Platform
WARNING: When you install the routing platform, do not use a ramp inclined at more than 10 degrees.
Waarschuwing Gebruik een oprijplaat niet onder een hoek van meer dan 10 graden.
Varoitus Älä käytä sellaista kaltevaa pintaa, jonka kaltevuus ylittää 10 astetta.
Attention Ne pas utiliser une rampe dont l'inclinaison est supérieure à 10 degrés.
Warnung Keine Rampen mit einer Neigung von mehr als 10 Grad verwenden.
Avvertenza Non usare una rampa con pendenza superiore a 10 gradi.
Advarsel Bruk aldri en rampe som heller mer enn 10 grader.
Aviso Não utilize uma rampa com uma inclinação superior a 10 graus.
¡Atención! No usar una rampa inclinada más de 10 grados
Varning! Använd inte ramp med en lutning på mer än 10 grader.
Related Topics
■
■
■
Definition of Safety Warning Levels on page 149
Installing the JCS 1200 Platform Using a Lift on page 51
Lifting the JCS 1200 Platform into the Rack or Cabinet on page 56
JCS 1200 Laser and LED Safety Guidelines and Warnings
Single-mode Physical Interface Cards (PICs) are equipped with laser transmitters, which are considered a Class 1 Laser Product by the U.S. Food and Drug
Administration, and are evaluated as a Class 1 Laser Product per EN 60825–1 +A11
+A2 requirements.
Observe the following guidelines and warnings:
■
■
■
■
Class 1 Laser Product Warning for the JCS 1200 Platform on page 160
Class 1 LED Product Warning for the JCS 1200 Platform on page 161
Laser Beam Warning for the JCS 1200 Platform on page 162
Radiation from Open Port Apertures Warning for the JCS 1200
Class 1 Laser Product Warning for the JCS 1200 Platform
WARNING: Class 1 laser product.
160 ■
Ramp Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Waarschuwing Klasse-1 laser produkt.
Varoitus Luokan 1 lasertuote.
Attention Produit laser de classe I.
Warnung Laserprodukt der Klasse 1.
Avvertenza Prodotto laser di Classe 1.
Advarsel Laserprodukt av klasse 1.
Aviso Produto laser de classe 1.
¡Atención! Producto láser Clase I.
Varning! Laserprodukt av klass 1.
Related Topics
■
■
■
■
Definition of Safety Warning Levels on page 149
Class 1 LED Product Warning for the JCS 1200 Platform on page 161
Laser Beam Warning for the JCS 1200 Platform on page 162
Radiation from Open Port Apertures Warning for the JCS 1200
Class 1 LED Product Warning for the JCS 1200 Platform
WARNING: Class 1 LED product.
Waarschuwing Klasse 1 LED-product.
Varoitus Luokan 1 valodiodituote.
Attention Alarme de produit LED Class I.
Warnung Class 1 LED-Produktwarnung.
Avvertenza Avvertenza prodotto LED di Classe 1.
Advarsel LED-produkt i klasse 1.
Aviso Produto de classe 1 com LED.
¡Atención! Aviso sobre producto LED de Clase 1.
Varning! Lysdiodprodukt av klass 1.
Class 1 LED Product Warning for the JCS 1200 Platform
■ 161
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■
■
■
Definition of Safety Warning Levels on page 149
Class 1 Laser Product Warning for the JCS 1200 Platform on page 160
Laser Beam Warning for the JCS 1200 Platform on page 162
Radiation from Open Port Apertures Warning for the JCS 1200
Laser Beam Warning for the JCS 1200 Platform
WARNING: Do not stare into the laser beam or view it directly with optical instruments.
Waarschuwing Niet in de straal staren of hem rechtstreeks bekijken met optische instrumenten.
Varoitus Älä katso säteeseen äläkä tarkastele sitä suoraan optisen laitteen avulla.
Attention Ne pas fixer le faisceau des yeux, ni l'observer directement à l'aide d'instruments optiques.
Warnung Nicht direkt in den Strahl blicken und ihn nicht direkt mit optischen Geräten prüfen.
Avvertenza Non fissare il raggio con gli occhi né usare strumenti ottici per osservarlo direttamente.
Advarsel Stirr eller se ikke direkte p strlen med optiske instrumenter.
Aviso Não olhe fixamente para o raio, nem olhe para ele directamente com instrumentos ópticos.
¡Atención! No mirar fijamente el haz ni observarlo directamente con instrumentos
ópticos.
Varning! Rikta inte blicken in mot strålen och titta inte direkt på den genom optiska instrument.
Related Topics
■
■
■
■
Definition of Safety Warning Levels on page 149
Class 1 Laser Product Warning for the JCS 1200 Platform on page 160
Class 1 LED Product Warning for the JCS 1200 Platform on page 161
Radiation from Open Port Apertures Warning for the JCS 1200
162 ■
Laser Beam Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Radiation from Open Port Apertures Warning for the JCS 1200 Platform
WARNING: Because invisible radiation may be emitted from the aperture of the port when no fiber cable is connected, avoid exposure to radiation and do not stare into open apertures.
Waarschuwing Aangezien onzichtbare straling vanuit de opening van de poort kan komen als er geen fiberkabel aangesloten is, dient blootstelling aan straling en het kijken in open openingen vermeden te worden.
Varoitus Koska portin aukosta voi emittoitua näkymätöntä säteilyä, kun kuitukaapelia ei ole kytkettynä, vältä säteilylle altistumista äläkä katso avoimiin aukkoihin.
Attention Des radiations invisibles à l'il nu pouvant traverser l'ouverture du port lorsqu'aucun câble en fibre optique n'y est connecté, il est recommandé de ne pas regarder fixement l'intérieur de ces ouvertures.
Warnung Aus der Port-Öffnung können unsichtbare Strahlen emittieren, wenn kein
Glasfaserkabel angeschlossen ist. Vermeiden Sie es, sich den Strahlungen auszusetzen, und starren Sie nicht in die Öffnungen!
Avvertenza Quando i cavi in fibra non sono inseriti, radiazioni invisibili possono essere emesse attraverso l'apertura della porta. Evitate di esporvi alle radiazioni e non guardate direttamente nelle aperture.
Advarsel Unngå utsettelse for stråling, og stirr ikke inn i åpninger som er åpne, fordi usynlig stråling kan emiteres fra portens åpning når det ikke er tilkoblet en fiberkabel.
Aviso Dada a possibilidade de emissão de radiação invisível através do orifício da via de acesso, quando esta não tiver nenhum cabo de fibra conectado, deverá evitar a exposição à radiação e não deverá olhar fixamente para orifícios que se encontrarem a descoberto.
¡Atención! Debido a que la apertura del puerto puede emitir radiación invisible cuando no existe un cable de fibra conectado, evite mirar directamente a las aperturas para no exponerse a la radiación.
Varning! Osynlig strålning kan avges från en portöppning utan ansluten fiberkabel och du bör därför undvika att bli utsatt för strålning genom att inte stirra in i oskyddade öppningar.
Related Topics
■
■
■
■
Definition of Safety Warning Levels on page 149
Class 1 Laser Product Warning for the JCS 1200 Platform on page 160
Class 1 LED Product Warning for the JCS 1200 Platform on page 161
Laser Beam Warning for the JCS 1200 Platform on page 162
Radiation from Open Port Apertures Warning for the JCS 1200 Platform
■ 163
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 Maintenance and Operational Safety Guidelines and Warnings
As you maintain the platform, observe the following guidelines and warnings:
■
■
■
■
■
Battery Handling Warning for the JCS 1200 Platform on page 164
Jewelry Removal Warning for the JCS 1200 Platform on page 165
Lightning Activity Warning for the JCS 1200 Platform on page 166
Operating Temperature Warning for the JCS 1200 Platform on page 167
Product Disposal Warning for the JCS 1200 Platform on page 168
Battery Handling Warning for the JCS 1200 Platform
WARNING: Replacing the battery incorrectly might result in an explosion. Replace the battery only with the same or equivalent type recommended by the manufacturer.
Dispose of used batteries according to the manufacturer's instructions.
Waarschuwing Er is ontploffingsgevaar als de batterij verkeerd vervangen wordt.
Vervang de batterij slechts met hetzelfde of een equivalent type dat door de fabrikant aanbevolen is. Gebruikte batterijen dienen overeenkomstig fabrieksvoorschriften weggeworpen te worden.
Varoitus Räjähdyksen vaara, jos akku on vaihdettu väärään akkuun. Käytä vaihtamiseen ainoastaan saman- tai vastaavantyyppistä akkua, joka on valmistajan suosittelema. Hävitä käytetyt akut valmistajan ohjeiden mukaan.
Attention Danger d'explosion si la pile n'est pas remplacée correctement. Ne la remplacer que par une pile de type semblable ou équivalent, recommandée par le fabricant. Jeter les piles usagées conformément aux instructions du fabricant.
Warnung Bei Einsetzen einer falschen Batterie besteht Explosionsgefahr. Ersetzen
Sie die Batterie nur durch den gleichen oder vom Hersteller empfohlenen Batterietyp.
Entsorgen Sie die benutzten Batterien nach den Anweisungen des Herstellers.
Avvertenza Pericolo di esplosione se la batteria non è installata correttamente.
Sostituire solo con una di tipo uguale o equivalente, consigliata dal produttore.
Eliminare le batterie usate secondo le istruzioni del produttore.
Advarsel Det kan være fare for eksplosjon hvis batteriet skiftes på feil måte. Skift kun med samme eller tilsvarende type som er anbefalt av produsenten. Kasser brukte batterier i henhold til produsentens instruksjoner.
Aviso Existe perigo de explosão se a bateria for substituída incorrectamente. Substitua a bateria por uma bateria igual ou de um tipo equivalente recomendado pelo fabricante. Destrua as baterias usadas conforme as instruções do fabricante.
¡Atención! Existe peligro de explosión si la batería se reemplaza de manera incorrecta.
Reemplazar la batería exclusivamente con el mismo tipo o el equivalente recomendado por el fabricante. Desechar las baterías gastadas según las instrucciones del fabricante.
164 ■
Battery Handling Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Varning! Explosionsfara vid felaktigt batteribyte. Ersätt endast batteriet med samma batterityp som rekommenderas av tillverkaren eller motsvarande. Följ tillverkarens anvisningar vid kassering av använda batterier.
Related Topics
■
■
■
■
■
Definition of Safety Warning Levels on page 149
Jewelry Removal Warning for the JCS 1200 Platform on page 165
Lightning Activity Warning for the JCS 1200 Platform on page 166
Operating Temperature Warning for the JCS 1200 Platform on page 167
Product Disposal Warning for the JCS 1200 Platform on page 168
Jewelry Removal Warning for the JCS 1200 Platform
WARNING: Before working on equipment that is connected to power lines, remove jewelry, including rings, necklaces, and watches. Metal objects heat up when connected to power and ground and can cause serious burns or weld the metal object to the terminals.
Waarschuwing Alvorens aan apparatuur te werken die met elektrische leidingen is verbonden, sieraden (inclusief ringen, kettingen en horloges) verwijderen. Metalen voorwerpen worden warm wanneer ze met stroom en aarde zijn verbonden, en kunnen ernstige brandwonden veroorzaken of het metalen voorwerp aan de aansluitklemmen lassen.
Varoitus Ennen kuin työskentelet voimavirtajohtoihin kytkettyjen laitteiden parissa, ota pois kaikki korut (sormukset, kaulakorut ja kellot mukaan lukien). Metalliesineet kuumenevat, kun ne ovat yhteydessä sähkövirran ja maan kanssa, ja ne voivat aiheuttaa vakavia palovammoja tai hitsata metalliesineet kiinni liitäntänapoihin.
Attention Avant d'accéder à cet équipement connecté aux lignes électriques, ôter tout bijou (anneaux, colliers et montres compris). Lorsqu'ils sont branchés à l'alimentation et reliés à la terre, les objets métalliques chauffent, ce qui peut provoquer des blessures graves ou souder l'objet métallique aux bornes.
Warnung Vor der Arbeit an Geräten, die an das Netz angeschlossen sind, jeglichen
Schmuck (einschließlich Ringe, Ketten und Uhren) abnehmen. Metallgegenstände erhitzen sich, wenn sie an das Netz und die Erde angeschlossen werden, und können schwere Verbrennungen verursachen oder an die Anschlußklemmen angeschweißt werden.
Avvertenza Prima di intervenire su apparecchiature collegate alle linee di alimentazione, togliersi qualsiasi monile (inclusi anelli, collane, braccialetti ed orologi).
Gli oggetti metallici si riscaldano quando sono collegati tra punti di alimentazione e massa: possono causare ustioni gravi oppure il metallo può saldarsi ai terminali.
Advarsel Fjern alle smykker (inkludert ringer, halskjeder og klokker) før du skal arbeide på utstyr som er koblet til kraftledninger. Metallgjenstander som er koblet
Jewelry Removal Warning for the JCS 1200 Platform
■ 165
Juniper Control System (JCS) 1200 Platform Hardware Guide til kraftledninger og jord blir svært varme og kan forårsake alvorlige brannskader eller smelte fast til polene.
Aviso Antes de trabalhar em equipamento que esteja ligado a linhas de corrente, retire todas as jóias que estiver a usar (incluindo anéis, fios e relógios). Os objectos metálicos aquecerão em contacto com a corrente e em contacto com a ligação à terra, podendo causar queimaduras graves ou ficarem soldados aos terminais.
¡Atención! Antes de operar sobre equipos conectados a líneas de alimentación, quitarse las joyas (incluidos anillos, collares y relojes). Los objetos de metal se calientan cuando se conectan a la alimentación y a tierra, lo que puede ocasionar quemaduras graves o que los objetos metálicos queden soldados a los bornes.
Varning! Tag av alla smycken (inklusive ringar, halsband och armbandsur) innan du arbetar på utrustning som är kopplad till kraftledningar. Metallobjekt hettas upp när de kopplas ihop med ström och jord och kan förorsaka allvarliga brännskador; metallobjekt kan också sammansvetsas med kontakterna.
Related Topics
■
■
■
■
■
Definition of Safety Warning Levels on page 149
Battery Handling Warning for the JCS 1200 Platform on page 164
Lightning Activity Warning for the JCS 1200 Platform on page 166
Operating Temperature Warning for the JCS 1200 Platform on page 167
Product Disposal Warning for the JCS 1200 Platform on page 168
Lightning Activity Warning for the JCS 1200 Platform
WARNING: Do not work on the system or connect or disconnect cables during periods of lightning activity.
Waarschuwing Tijdens onweer dat gepaard gaat met bliksem, dient u niet aan het systeem te werken of kabels aan te sluiten of te ontkoppelen.
Varoitus Älä työskentele järjestelmän parissa äläkä yhdistä tai irrota kaapeleita ukkosilmalla.
Attention Ne pas travailler sur le système ni brancher ou débrancher les câbles pendant un orage.
Warnung Arbeiten Sie nicht am System und schließen Sie keine Kabel an bzw.
trennen Sie keine ab, wenn es gewittert.
Avvertenza Non lavorare sul sistema o collegare oppure scollegare i cavi durante un temporale con fulmini.
Advarsel Utfør aldri arbeid på systemet, eller koble kabler til eller fra systemet når det tordner eller lyner.
166 ■
Lightning Activity Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Aviso Não trabalhe no sistema ou ligue e desligue cabos durante períodos de mau tempo (trovoada).
¡Atención! No operar el sistema ni conectar o desconectar cables durante el transcurso de descargas eléctricas en la atmósfera.
Varning! Vid åska skall du aldrig utföra arbete på systemet eller ansluta eller koppla loss kablar.
Related Topics
■
■
■
■
■
Definition of Safety Warning Levels on page 149
Battery Handling Warning for the JCS 1200 Platform on page 164
Jewelry Removal Warning for the JCS 1200 Platform on page 165
Operating Temperature Warning for the JCS 1200 Platform on page 167
Product Disposal Warning for the JCS 1200 Platform on page 168
Operating Temperature Warning for the JCS 1200 Platform
WARNING: To prevent the routing platform from overheating, do not operate it in an area that exceeds the maximum recommended ambient temperature of 104° F
(40° C). To prevent airflow restriction, allow at least 6 in. (15.2 cm) of clearance around the ventilation openings.
Waarschuwing Om te voorkomen dat welke router van de Juniper Networks router dan ook oververhit raakt, dient u deze niet te bedienen op een plaats waar de maximale aanbevolen omgevingstemperatuur van 40° C wordt overschreden. Om te voorkomen dat de luchtstroom wordt beperkt, dient er minstens 15,2 cm speling rond de ventilatie-openingen te zijn.
Varoitus Ettei Juniper Networks router-sarjan reititin ylikuumentuisi, sitä ei saa käyttää tilassa, jonka lämpötila ylittää korkeimman suositellun ympäristölämpötilan 40° C.
Ettei ilmanvaihto estyisi, tuuletusaukkojen ympärille on jätettävä ainakin 15,2 cm tilaa.
Attention Pour éviter toute surchauffe des routeurs de la gamme Juniper Networks router, ne l'utilisez pas dans une zone où la température ambiante est supérieure à
40° C. Pour permettre un flot d'air constant, dégagez un espace d'au moins 15,2 cm autour des ouvertures de ventilations.
Warnung Um einen Router der router vor Überhitzung zu schützen, darf dieser nicht in einer Gegend betrieben werden, in der die Umgebungstemperatur das empfohlene
Maximum von 40° C überschreitet. Um Lüftungsverschluß zu verhindern, achten
Sie darauf, daß mindestens 15,2 cm lichter Raum um die Lüftungsöffnungen herum frei bleibt.
Avvertenza Per evitare il surriscaldamento dei router, non adoperateli in un locale che ecceda la temperatura ambientale massima di 40° C. Per evitare che la
Operating Temperature Warning for the JCS 1200 Platform
■ 167
Juniper Control System (JCS) 1200 Platform Hardware Guide circolazione dell'aria sia impedita, lasciate uno spazio di almeno 15.2 cm di fronte alle aperture delle ventole.
Advarsel Unngå overoppheting av eventuelle rutere i Juniper Networks router Disse skal ikke brukes på steder der den anbefalte maksimale omgivelsestemperaturen overstiger 40° C (104° F). Sørg for at klaringen rundt lufteåpningene er minst 15,2 cm (6 tommer) for å forhindre nedsatt luftsirkulasjon.
Aviso Para evitar o sobreaquecimento do encaminhador Juniper Networks router, não utilize este equipamento numa área que exceda a temperatura máxima recomendada de 40° C. Para evitar a restrição à circulação de ar, deixe pelo menos um espaço de 15,2 cm à volta das aberturas de ventilação.
¡Atención! Para impedir que un encaminador de la serie Juniper Networks router se recaliente, no lo haga funcionar en un área en la que se supere la temperatura ambiente máxima recomendada de 40° C. Para impedir la restricción de la entrada de aire, deje un espacio mínimo de 15,2 cm alrededor de las aperturas para ventilación.
Varning! Förhindra att en Juniper Networks router överhettas genom att inte använda den i ett område där den maximalt rekommenderade omgivningstemperaturen på
40° C överskrids. Förhindra att luftcirkulationen inskränks genom att se till att det finns fritt utrymme på minst 15,2 cm omkring ventilationsöppningarna.
Related Topics
■
■
■
■
■
Definition of Safety Warning Levels on page 149
Battery Handling Warning for the JCS 1200 Platform on page 164
Jewelry Removal Warning for the JCS 1200 Platform on page 165
Lightning Activity Warning for the JCS 1200 Platform on page 166
Product Disposal Warning for the JCS 1200 Platform on page 168
Product Disposal Warning for the JCS 1200 Platform
WARNING: Disposal of this product must be handled according to all national laws and regulations.
Waarschuwing Dit produkt dient volgens alle landelijke wetten en voorschriften te worden afgedankt.
Varoitus Tämän tuotteen lopullisesta hävittämisestä tulee huolehtia kaikkia valtakunnallisia lakeja ja säännöksiä noudattaen.
Attention La mise au rebut définitive de ce produit doit être effectuée conformément
à toutes les lois et réglementations en vigueur.
Warnung Dieses Produkt muß den geltenden Gesetzen und Vorschriften entsprechend entsorgt werden.
168 ■
Product Disposal Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Avvertenza L'eliminazione finale di questo prodotto deve essere eseguita osservando le normative italiane vigenti in materia
Advarsel Endelig disponering av dette produktet må skje i henhold til nasjonale lover og forskrifter.
Aviso A descartagem final deste produto deverá ser efectuada de acordo com os regulamentos e a legislação nacional.
¡Atención! El desecho final de este producto debe realizarse según todas las leyes y regulaciones nacionales
Varning! Slutlig kassering av denna produkt bör skötas i enlighet med landets alla lagar och föreskrifter.
Related Topics
■
■
■
■
■
Definition of Safety Warning Levels on page 149
Battery Handling Warning for the JCS 1200 Platform on page 164
Jewelry Removal Warning for the JCS 1200 Platform on page 165
Lightning Activity Warning for the JCS 1200 Platform on page 166
Operating Temperature Warning for the JCS 1200 Platform on page 167
JCS 1200 Electrical Safety Guidelines and Warnings
When working on equipment powered by electricity, follow the guidelines described in the following topics:
■
■
■
■
In Case of an Electrical Accident on page 169
JCS 1200 General Electrical Safety Guidelines and Warnings on page 170
JCS 1200 AC Power Electrical Safety Guidelines and Warnings on page 174
JCS 1200 DC Power Electrical Safety Guidelines and Warnings on page 175
In Case of an Electrical Accident
If an electrical accident results in an injury, take the following actions in this order:
1.
2.
Use caution. Be aware of potentially hazardous conditions that could cause further injury.
Disconnect power from the platform.
3.
If possible, send another person to get medical aid. Otherwise, assess the condition of the victim, then call for help.
Related Topics
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
In Case of an Electrical Accident
■ 169
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 General Electrical Safety Guidelines and Warnings
Topics include:
■
■
■
■
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Grounded Equipment Warning for the JCS 1200 Platform on page 171
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
Multiple Power Supplies Disconnection Warning for the JCS 1200
TN Power Warning for the JCS 1200 Platform on page 173
Copper Conductors Warning for the JCS 1200 Platform on page 174
General Electrical Safety Guidelines and Warnings Electrical Codes for the JCS 1200
Platform
■
■
■
■
■
■
■
Install the routing platform in compliance with the following local, national, or international electrical codes:
■
■
United States—National Fire Protection Association (NFPA 70), United States
National Electrical Code.
Canada—Canadian Electrical Code, Part 1, CSA C22.1.
■
■
Other countries—International Electromechanical Commission (IEC) 60364,
Part 1 through Part 7.
Evaluated to the TN power system.
Locate the emergency power-off switch for the room in which you are working so that if an electrical accident occurs, you can quickly turn off the power.
Do not work alone if potentially hazardous conditions exist anywhere in your workspace.
Never assume that power is disconnected from a circuit. Always check the circuit before starting to work.
Carefully look for possible hazards in your work area, such as moist floors, ungrounded power extension cords, and missing safety grounds.
Operate the routing platform within marked electrical ratings and product usage instructions.
For the routing platform and peripheral equipment to function safely and correctly, use the cables and connectors specified for the attached peripheral equipment, and make certain they are in good condition.
Many routing platform components can be removed and replaced without powering
off or disconnecting power to the routing platform, as detailed in “JCS 1200 Hardware
Component Installation Guidelines” on page 95. Never install equipment if it appears
damaged.
Related Topics
■
Grounded Equipment Warning for the JCS 1200 Platform on page 171
■
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
170 ■
General Electrical Safety Guidelines and Warnings Electrical Codes for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
■
■
■
Multiple Power Supplies Disconnection Warning for the JCS 1200
TN Power Warning for the JCS 1200 Platform on page 173
Copper Conductors Warning for the JCS 1200 Platform on page 174
Grounded Equipment Warning for the JCS 1200 Platform
WARNING: The routing platform is intended to be grounded. Ensure that the routing platform is connected to earth ground during normal use.
Waarschuwing Deze apparatuur hoort geaard te worden Zorg dat de host-computer tijdens normaal gebruik met aarde is verbonden.
Varoitus Tämä laitteisto on tarkoitettu maadoitettavaksi. Varmista, että isäntälaite on yhdistetty maahan normaalikäytön aikana.
Attention Cet équipement doit être relié à la terre. S'assurer que l'appareil hôte est relié à la terre lors de l'utilisation normale.
Warnung Dieses Gerät muß geerdet werden. Stellen Sie sicher, daß das Host-Gerät während des normalen Betriebs an Erde gelegt ist.
Avvertenza Questa apparecchiatura deve essere collegata a massa. Accertarsi che il dispositivo host sia collegato alla massa di terra durante il normale utilizzo.
Advarsel Dette utstyret skal jordes. Forviss deg om vertsterminalen er jordet ved normalt bruk.
Aviso Este equipamento deverá estar ligado à terra. Certifique-se que o host se encontra ligado à terra durante a sua utilização normal.
¡Atención! Este equipo debe conectarse a tierra. Asegurarse de que el equipo principal esté conectado a tierra durante el uso normal.
Varning! Denna utrustning är avsedd att jordas. Se till att värdenheten är jordad vid normal användning.
Related Topics
■
■
■
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
Multiple Power Supplies Disconnection Warning for the JCS 1200
TN Power Warning for the JCS 1200 Platform on page 173
Copper Conductors Warning for the JCS 1200 Platform on page 174
Grounded Equipment Warning for the JCS 1200 Platform
■ 171
Juniper Control System (JCS) 1200 Platform Hardware Guide
Midplane Energy Hazard Warning for the JCS 1200 Platform
WARNING: High levels of electrical energy are distributed across the routing platform midplane. Be careful not to contact the midplane connectors, or any component connected to the midplane, with any metallic object while servicing components installed in the routing platform.
Related Topics
■
■
■
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Grounded Equipment Warning for the JCS 1200 Platform on page 171
Multiple Power Supplies Disconnection Warning for the JCS 1200
TN Power Warning for the JCS 1200 Platform on page 173
Copper Conductors Warning for the JCS 1200 Platform on page 174
Multiple Power Supplies Disconnection Warning for the JCS 1200 Platform
WARNING: The routing platform has more than one power supply connection. All connections must be removed completely to remove power from the unit completely.
Waarschuwing Deze eenheid heeft meer dan één stroomtoevoerverbinding; alle verbindingen moeten volledig worden verwijderd om de stroom van deze eenheid volledig te verwijderen.
Varoitus Tässä laitteessa on useampia virtalähdekytkentöjä. Kaikki kytkennät on irrotettava kokonaan, jotta virta poistettaisiin täysin laitteesta.
Attention Cette unité est équipée de plusieurs raccordements d'alimentation. Pour supprimer tout courant électrique de l'unité, tous les cordons d'alimentation doivent
être débranchés.
Warnung Diese Einheit verfügt über mehr als einen Stromanschluß; um Strom gänzlich von der Einheit fernzuhalten, müssen alle Stromzufuhren abgetrennt sein.
Avvertenza Questa unità ha più di una connessione per alimentatore elettrico; tutte le connessioni devono essere completamente rimosse per togliere l'elettricità dall'unità.
Advarsel Denne enheten har mer enn én strømtilkobling. Alle tilkoblinger må kobles helt fra for å eliminere strøm fra enheten.
Aviso Este dispositivo possui mais do que uma conexão de fonte de alimentação de energia; para poder remover a fonte de alimentação de energia, deverão ser desconectadas todas as conexões existentes.
172 ■
Midplane Energy Hazard Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
¡Atención! Esta unidad tiene más de una conexión de suministros de alimentación; para eliminar la alimentación por completo, deben desconectarse completamente todas las conexiones.
Varning! Denna enhet har mer än en strömförsörjningsanslutning; alla anslutningar måste vara helt avlägsnade innan strömtillförseln till enheten är fullständigt bruten.
Related Topics
■
■
■
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Grounded Equipment Warning for the JCS 1200 Platform on page 171
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
TN Power Warning for the JCS 1200 Platform on page 173
Copper Conductors Warning for the JCS 1200 Platform on page 174
TN Power Warning for the JCS 1200 Platform
WARNING: The routing platform is designed to work with TN power systems.
Waarschuwing Het apparaat is ontworpen om te functioneren met TN energiesystemen.
Varoitus Koje on suunniteltu toimimaan TN-sähkövoimajärjestelmien yhteydessä.
Attention Ce dispositif a été conçu pour fonctionner avec des systèmes d'alimentation
TN.
Warnung Das Gerät ist für die Verwendung mit TN-Stromsystemen ausgelegt.
Avvertenza Il dispositivo è stato progettato per l'uso con sistemi di alimentazione
TN.
Advarsel Utstyret er utfomet til bruk med TN-strømsystemer.
Aviso O dispositivo foi criado para operar com sistemas de corrente TN.
¡Atención! El equipo está diseñado para trabajar con sistemas de alimentación tipo
TN.
Varning! Enheten är konstruerad för användning tillsammans med elkraftssystem av TN-typ.
Related Topics
■
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Grounded Equipment Warning for the JCS 1200 Platform on page 171
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
TN Power Warning for the JCS 1200 Platform
■ 173
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
Multiple Power Supplies Disconnection Warning for the JCS 1200
Copper Conductors Warning for the JCS 1200 Platform on page 174
Copper Conductors Warning for the JCS 1200 Platform
WARNING: Use copper conductors only.
Waarschuwing Gebruik alleen koperen geleiders.
Varoitus Käytä vain kuparijohtimia.
Attention Utilisez uniquement des conducteurs en cuivre.
Warnung Verwenden Sie ausschließlich Kupferleiter.
Avvertenza Usate unicamente dei conduttori di rame.
Advarsel Bruk bare kobberledninger.
Aviso Utilize apenas fios condutores de cobre.
¡Atención! Emplee sólo conductores de cobre.
Varning! Använd endast ledare av koppar.
Related Topics
■
■
■
■
■
General Electrical Safety Guidelines and Warnings Electrical Codes for the
Grounded Equipment Warning for the JCS 1200 Platform on page 171
Midplane Energy Hazard Warning for the JCS 1200 Platform on page 172
Multiple Power Supplies Disconnection Warning for the JCS 1200
TN Power Warning for the JCS 1200 Platform on page 173
JCS 1200 AC Power Electrical Safety Guidelines and Warnings
The following electrical safety guidelines apply to a AC-powered platforms:
■
AC-powered platforms are shipped with three-wire electrical cords with a grounding-type plug that fits only a grounding-type power outlet. Do not circumvent this safety feature. Equipment grounding should comply with local and national electrical codes.
■
■
You must provide an external Listed circuit breaker rated minimum
15 A (250 VAC) for each AC power supply.
The cores in the mains lead are colored in accordance with the following code:
174 ■
Copper Conductors Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
■
■
■
Green and yellow—Earth
Blue—Neutral
Brown—Live
The power cable warning in Japanese is as follows:
WARNING: The attached power cable is only for this product. Do not use the cable for another product.
Related Topics
■
■
■
■
Connecting the JCS 1200 AC Platform to AC Power on page 62
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
Power Consumption for an AC-Powered JCS 1200 Platform on page 190
AC Power Supply Electrical Specifications for the JCS 1200 Platform on page 190
JCS 1200 DC Power Electrical Safety Guidelines and Warnings
When working with DC-powered equipment, observe the following guidelines and warnings:
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
DC Power Disconnection Warning for the JCS 1200 Platform on page 176
JCS 1200 DC Power Grounding Requirements and Warning on page 178
DC Power Wiring Sequence Warning for the JCS 1200 Platform on page 179
DC Power Wiring Terminations Warning for the JCS 1200 Platform on page 180
JCS 1200 DC Power Electrical Safety Guidelines
The following guidelines are provided for connecting a 60-A JCS 1200 platform to a
–48 V DC power source:
■
The power source must have a minimum of 80 A overcurrent protection. See article 240, paragraph 3, table 310-16 of the National Electric Code for more information about electrical wiring requirements.
■
The overcurrent protective device or circuit breaker must be accessible to service personnel to prevent the power from being turned on by someone other than a technician servicing the JCS 1200 platform.
JCS 1200 DC Power Electrical Safety Guidelines
■ 175
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
The JCS 1200 platform requires a DC wire rating of 4 AWG (circular mil area of
33100-52600) and of 90° C.
NOTE: The actual wire gauge and ring terminal are determined by the current draw and the length of wire run or as specified by the customer premises guidelines.
Related Topics
■
■
■
■
■
■
■
■
Flexible DC wiring is recommended to allow for minimum bend radius.
The supply wiring to the power connectors must be terminated in UL-recognized insulated ring terminals, sized for an M6 stud, 4 AWG wire (circular mil area of
33100-52600), and a wire insulation diameter of 12.8 to 13.1 mm. An example of this type of ring terminal is Amp Plasti-Grip type 520431 using Tyco Electronics
Hydraulic Crimping Tool part number 14907491.
For NEBS compliance, the grounding cable must use copper conductors with a size minimum of 6 AWG (circular mil area of 2080033100) and must be terminated in a UL-recognized two-hole lug sized for an M6 stud. An example of this type of two-hole lug is the Thomas and Betts part number 54205 using the Thomas and Betts crimping tool model TBM-25S.
Torque the wiring-terminal nuts to 13.3 lb-in. (1.5 Nm)
Connecting the JCS 1200 DC Platform to DC Power on page 63
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
DC Power Disconnection Warning for the JCS 1200 Platform
WARNING: Before performing any of the following procedures, ensure that power is removed from the DC circuit. To ensure that all power is off, locate the circuit breaker on the panel board that services the DC circuit, switch the circuit breaker to the
OFF
position, and tape the switch handle of the circuit breaker in the
OFF
position.
Waarschuwing Voordat u een van de onderstaande procedures uitvoert, dient u te controleren of de stroom naar het gelijkstroom circuit uitgeschakeld is. Om u ervan te verzekeren dat alle stroom UIT is geschakeld, kiest u op het schakelbord de stroomverbreker die het gelijkstroom circuit bedient, draait de stroomverbreker naar de UIT positie en plakt de schakelaarhendel van de stroomverbreker met plakband in de UIT positie vast.
Varoitus Varmista, että tasavirtapiirissä ei ole virtaa ennen seuraavien toimenpiteiden suorittamista. Varmistaaksesi, että virta on KATKAISTU täysin, paikanna tasavirrasta huolehtivassa kojetaulussa sijaitseva suojakytkin, käännä suojakytkin
KATKAISTU-asentoon ja teippaa suojakytkimen varsi niin, että se pysyy
KATKAISTU-asennossa.
176 ■
DC Power Disconnection Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Attention Avant de pratiquer l'une quelconque des procédures ci-dessous, vérifier que le circuit en courant continu n'est plus sous tension. Pour en être sûr, localiser le disjoncteur situé sur le panneau de service du circuit en courant continu, placer le disjoncteur en position fermée (OFF) et, à l'aide d'un ruban adhésif, bloquer la poignée du disjoncteur en position OFF.
Warnung Vor Ausführung der folgenden Vorgänge ist sicherzustellen, daß die
Gleichstromschaltung keinen Strom erhält. Um sicherzustellen, daß sämtlicher Strom abgestellt ist, machen Sie auf der Schalttafel den Unterbrecher für die
Gleichstromschaltung ausfindig, stellen Sie den Unterbrecher auf AUS, und kleben
Sie den Schaltergriff des Unterbrechers mit Klebeband in der AUS-Stellung fest.
Avvertenza Prima di svolgere una qualsiasi delle procedure seguenti, verificare che il circuito CC non sia alimentato. Per verificare che tutta l'alimentazione sia scollegata
(OFF), individuare l'interruttore automatico sul quadro strumenti che alimenta il circuito CC, mettere l'interruttore in posizione OFF e fissarlo con nastro adesivo in tale posizione.
Advarsel Før noen av disse prosedyrene utføres, kontroller at strømmen er frakoblet likestrømkretsen. Sørg for at all strøm er slått AV. Dette gjøres ved å lokalisere strømbryteren på brytertavlen som betjener likestrømkretsen, slå strømbryteren AV og teipe bryterhåndtaket på strømbryteren i AV-stilling.
Aviso Antes de executar um dos seguintes procedimentos, certifique-se que desligou a fonte de alimentação de energia do circuito de corrente contínua. Para se assegurar que toda a corrente foi DESLIGADA, localize o disjuntor no painel que serve o circuito de corrente contínua e coloque-o na posição OFF (Desligado), segurando nessa posição a manivela do interruptor do disjuntor com fita isoladora.
¡Atención! Antes de proceder con los siguientes pasos, comprobar que la alimentación del circuito de corriente continua (CC) esté cortada (OFF). Para asegurarse de que toda la alimentación esté cortada (OFF), localizar el interruptor automático en el panel que alimenta al circuito de corriente continua, cambiar el interruptor automático a la posición de Apagado (OFF), y sujetar con cinta la palanca del interruptor automático en posición de Apagado (OFF).
Varning! Innan du utför någon av följande procedurer måste du kontrollera att strömförsörjningen till likströmskretsen är bruten. Kontrollera att all strömförsörjning
är BRUTEN genom att slå AV det överspänningsskydd som skyddar likströmskretsen och tejpa fast överspänningsskyddets omkopplare i FRÅN-läget.
Related Topics
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
Connecting the JCS 1200 DC Platform to DC Power on page 63
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
DC Power Disconnection Warning for the JCS 1200 Platform
■ 177
Juniper Control System (JCS) 1200 Platform Hardware Guide
JCS 1200 DC Power Grounding Requirements and Warning
An insulated grounding conductor that is identical in size to the grounded and ungrounded branch circuit supply conductors, but is identifiable by green and yellow stripes, is installed as part of the branch circuit that supplies the unit. The grounding conductor is a separately derived system at the supply transformer or motor generator
set.“DC Power Supply Electrical Specifications for the JCS 1200 Platform” on page 192
For further information, see .“DC Power Supply Electrical Specifications for the
JCS 1200 Platform” on page 192
WARNING: When you install the platform, the ground connection must always be made first and disconnected last.
Waarschuwing Bij de installatie van het toestel moet de aardverbinding altijd het eerste worden gemaakt en het laatste worden losgemaakt.
Varoitus Laitetta asennettaessa on maahan yhdistäminen aina tehtävä ensiksi ja maadoituksen irti kytkeminen viimeiseksi.
Attention Lors de l'installation de l'appareil, la mise à la terre doit toujours être connectée en premier et déconnectée en dernier.
Warnung Der Erdanschluß muß bei der Installation der Einheit immer zuerst hergestellt und zuletzt abgetrennt werden.
Avvertenza In fase di installazione dell'unità, eseguire sempre per primo il collegamento a massa e disconnetterlo per ultimo.
Advarsel Når enheten installeres, må jordledningen alltid tilkobles først og frakobles sist.
Aviso Ao instalar a unidade, a ligação à terra deverá ser sempre a primeira a ser ligada, e a última a ser desligada.
¡Atención! Al instalar el equipo, conectar la tierra la primera y desconectarla la última.
Varning! Vid installation av enheten måste jordledningen alltid anslutas först och kopplas bort sist.
Related Topics
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
Connecting the JCS 1200 DC Platform to DC Power on page 63
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
178 ■
JCS 1200 DC Power Grounding Requirements and Warning
Appendix A: Safety and Regulatory Compliance Information
DC Power Wiring Sequence Warning for the JCS 1200 Platform
WARNING: Wire the DC power supply using the appropriate lugs. When connecting power, the proper wiring sequence is ground to ground, +RTN to +RTN, then –48 V to –48 V. When disconnecting power, the proper wiring sequence is –48 V to –48 V,
+RTN to +RTN, then ground to ground. Note that the ground wire should always be connected first and disconnected last.
Waarschuwing De juiste bedradingsvolgorde verbonden is aarde naar aarde, +RTN naar +RTN, en –48 V naar – 48 V. De juiste bedradingsvolgorde losgemaakt is en
–48 V naar –48 V, +RTN naar +RTN, aarde naar aarde.
Varoitus Oikea yhdistettava kytkentajarjestys on maajohto maajohtoon, +RTN varten
+RTN, –48 V varten – 48 V. Oikea irrotettava kytkentajarjestys on –48 V varten –
48 V, +RTN varten +RTN, maajohto maajohtoon.
Attention Câblez l'approvisionnement d'alimentation CC En utilisant les crochets appropriés à l'extrémité de câblage. En reliant la puissance, l'ordre approprié de câblage est rectifié pour rectifier, +RTN à +RTN, puis –48 V à –48 V. En débranchant la puissance, l'ordre approprié de câblage est –48 V à –48 V, +RTN à +RTN, a alors rectifié pour rectifier. Notez que le fil de masse devrait toujours être relié d'abord et débranché pour la dernière fois. Notez que le fil de masse devrait toujours être relié d'abord et débranché pour la dernière fois.
Warnung Die Stromzufuhr ist nur mit geeigneten Ringösen an das DC Netzteil anzuschliessen. Die richtige Anschlusssequenz ist: Erdanschluss zu Erdanschluss,
+RTN zu +RTN und dann -48V zu -48V. Die richtige Sequenz zum Abtrennen der
Stromversorgung ist -48V zu -48V, +RTN zu +RTN und dann Erdanschluss zu
Erdanschluss. Es ist zu beachten dass der Erdanschluss immer zuerst angeschlossen und als letztes abgetrennt wird.
Avvertenza Mostra la morsettiera dell alimentatore CC. Cablare l'alimentatore CC usando i connettori adatti all'estremità del cablaggio, come illustrato. La corretta sequenza di cablaggio è da massa a massa, da positivo a positivo (da linea ad L) e da negativo a negativo (da neutro a N). Tenere presente che il filo di massa deve sempre venire collegato per primo e scollegato per ultimo.
Advarsel Riktig tilkoples tilkoplingssekvens er jord til jord, +RTN til +RTN, –48 V til –48 V. Riktig frakoples tilkoplingssekvens er –48 V til –48 V, +RTN til +RTN, jord til jord.
Aviso Ate con alambre la fuente de potencia cc Usando los terminales apropiados en el extremo del cableado. Al conectar potencia, la secuencia apropiada del cableado se muele para moler, +RTN a +RTN, entonces –48 V a –48 V. Al desconectar potencia, la secuencia apropiada del cableado es –48 V a –48 V, +RTN a +RTN, entonces molió para moler. Observe que el alambre de tierra se debe conectar siempre primero y desconectar por último. Observe que el alambre de tierra se debe conectar siempre primero y desconectar por último.
¡Atención! Wire a fonte de alimentação de DC Usando os talões apropriados na extremidade da fiação. Ao conectar a potência, a seqüência apropriada da fiação é moída para moer, +RTN a +RTN, então –48 V a –48 V. Ao desconectar a potência,
DC Power Wiring Sequence Warning for the JCS 1200 Platform
■ 179
Juniper Control System (JCS) 1200 Platform Hardware Guide a seqüência apropriada da fiação é –48 V a –48 V, +RTN a +RTN, moeu então para moer. Anote que o fio à terra deve sempre ser conectado primeiramente e desconectado por último. Anote que o fio à terra deve sempre ser conectado primeiramente e desconectado por último.
Varning! Korrekt kopplingssekvens ar jord till jord, +RTN till +RTN, –48 V till –48
V. Korrekt kopplas kopplingssekvens ar –48 V till –48 V, +RTN till +RTN, jord till jord.
Related Topics
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
Connecting the JCS 1200 DC Platform to DC Power on page 63
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
DC Power Wiring Terminations Warning for the JCS 1200 Platform
WARNING: When stranded wiring is required, use approved wiring terminations, such as closed-loop or spade-type with upturned lugs. These terminations should be the appropriate size for the wires and should clamp both the insulation and conductor.
Waarschuwing Wanneer geslagen bedrading vereist is, dient u bedrading te gebruiken die voorzien is van goedgekeurde aansluitingspunten, zoals het gesloten-lus type of het grijperschop type waarbij de aansluitpunten omhoog wijzen. Deze aansluitpunten dienen de juiste maat voor de draden te hebben en dienen zowel de isolatie als de geleider vast te klemmen.
Varoitus Jos säikeellinen johdin on tarpeen, käytä hyväksyttyä johdinliitäntää, esimerkiksi suljettua silmukkaa tai kourumaista liitäntää, jossa on ylöspäin käännetyt kiinnityskorvat. Tällaisten liitäntöjen tulee olla kooltaan johtimiin sopivia ja niiden tulee puristaa yhteen sekä eristeen että johdinosan.
Attention Quand des fils torsadés sont nécessaires, utiliser des douilles terminales homologuées telles que celles à circuit fermé ou du type à plage ouverte avec cosses rebroussées. Ces douilles terminales doivent être de la taille qui convient aux fils et doivent être refermées sur la gaine isolante et sur le conducteur.
Warnung Wenn Litzenverdrahtung erforderlich ist, sind zugelassene
Verdrahtungsabschlüsse, z.B. für einen geschlossenen Regelkreis oder gabelförmig, mit nach oben gerichteten Kabelschuhen zu verwenden. Diese Abschlüsse sollten die angemessene Größe für die Drähte haben und sowohl die Isolierung als auch den
Leiter festklemmen.
Avvertenza Quando occorre usare trecce, usare connettori omologati, come quelli a occhiello o a forcella con linguette rivolte verso l'alto. I connettori devono avere la misura adatta per il cablaggio e devono serrare sia l'isolante che il conduttore.
180 ■
DC Power Wiring Terminations Warning for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Advarsel Hvis det er nødvendig med flertrådede ledninger, brukes godkjente ledningsavslutninger, som for eksempel lukket sløyfe eller spadetype med oppoverbøyde kabelsko. Disse avslutningene skal ha riktig størrelse i forhold til ledningene, og skal klemme sammen både isolasjonen og lederen.
Aviso Quando forem requeridas montagens de instalação eléctrica de cabo torcido, use terminações de cabo aprovadas, tais como, terminações de cabo em circuito fechado e planas com terminais de orelha voltados para cima. Estas terminações de cabo deverão ser do tamanho apropriado para os respectivos cabos, e deverão prender simultaneamente o isolamento e o fio condutor.
¡Atención! Cuando se necesite hilo trenzado, utilizar terminales para cables homologados, tales como las de tipo "bucle cerrado" o "espada", con las lengüetas de conexión vueltas hacia arriba. Estos terminales deberán ser del tamaño apropiado para los cables que se utilicen, y tendrán que sujetar tanto el aislante como el conductor.
Varning! När flertrådiga ledningar krävs måste godkända ledningskontakter användas, t.ex. kabelsko av sluten eller öppen typ med uppåtvänd tapp. Storleken på dessa kontakter måste vara avpassad till ledningarna och måste kunna hålla både isoleringen och ledaren fastklämda.
Related Topics
■
■
■
■
■
JCS 1200 DC Power Electrical Safety Guidelines on page 175
Connecting the JCS 1200 DC Platform to DC Power on page 63
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
JCS 1200 Agency Approvals and Compliance Statements
This topic discusses the following regulatory compliance information:
■
■
■
Agency Approvals for the JCS 1200 Platform on page 181
Compliance Statements for Environmental Requirements for the JCS 1200
Electronic Emission Notices for the JCS 1200 Platform on page 183
Agency Approvals for the JCS 1200 Platform
The platform complies with the following standards:
■
Safety
■
CAN/CSA-22.2 No. 60950-00/UL 1950 Third Edition, Safety of Information
Technology Equipment
Agency Approvals for the JCS 1200 Platform
■ 181
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
■
■
■
■
EN 60950 Safety of Information Technology Equipment
EMC
■
AS/NZS 3548 Class A (Australia/New Zealand)
■
BSMI Class A (Taiwan)
ICES-003 Class A (Canada)
■
■
EN55022 Class A (Europe)
FCC Part 15 Class A (USA)
■
VCCI Class A (Japan)
Immunity
■
EN-61000-3-2 Power Line Harmonics
■
EN-61000-4-2 ESD
■
■
■
■
EN-61000-4-3 Radiated Immunity
EN-61000-4-4 EFT
EN-61000-4-5 Surge
EN-61000-4-6 Low Frequency Common Immunity
■
EN-61000-4-11 Voltage Dips and Sags
ETSI
■
ETSI EN-300386-2 Telecommunication Network Equipment. Electromagnetic
Compatibility Requirements
NEBS
■
GR-1089-Core: EMC and Electrical Safety for Network Telecommunications
Equipment
■
SR-3580 NEBS Criteria Levels (Level 3 Compliance)
■
GR-63-Core: NEBS, Physical Protection
■
■
The equipment is suitable for installation as part of the Common Bonding
Network (CBN).
The equipment is suitable for installation in locations where the National
Electrical Code (NEC) applies.
■
The battery return connection is to be treated as a Common DC return
(i.e. DC-C), as defined in GR-1089-CORE.
Related Topics
■
■
Compliance Statements for Environmental Requirements for the JCS 1200
Electronic Emission Notices for the JCS 1200 Platform on page 183
182 ■
Agency Approvals for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Lithium Battery
Compliance Statements for Environmental Requirements for the JCS 1200
Platform
Batteries in this product are not based on mercury, lead, or cadmium substances.
The batteries used in this product are in compliance with EU Directives 91/157/EEC,
93/86/EEC, and 98/101/EEC. The product documentation includes instructional information about the proper method of reclamation and recycling.
Related Topics
■
■
Agency Approvals for the JCS 1200 Platform on page 181
Electronic Emission Notices for the JCS 1200 Platform on page 183
Electronic Emission Notices for the JCS 1200 Platform
Federal Communications Commission (FCC) Statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits. Juniper Networks is not responsible for any radio or television interference caused by using other than recommended cables and connectors or by unauthorized changes or modifications to this equipment.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation.
Industry Canada Class A Emission Compliance Statement
This Class A digital apparatus complies with Canadian ICES-003.
Avis de conformit la rglementation d'Industrie Canada
Cet appareil numrique de la classe A est conforme la norme NMB-003 du Canada.
Australia and New Zealand Class A Statement
CAUTION: This is a Class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take adequate measures.
Compliance Statements for Environmental Requirements for the JCS 1200 Platform
■ 183
Juniper Control System (JCS) 1200 Platform Hardware Guide
United Kingdom Telecommunications Safety Requirement
This apparatus is approved under approval number NS/G/1234/J/100003 for indirect connection to public telecommunication systems in the United Kingdom.
European Union EMC Directive Conformance Statement
This product is in conformity with the protection requirements of EU Council Directive
89/336/EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility. Juniper Networks cannot accept responsibility for any failure to satisfy the protection requirements resulting from a nonrecommended modification of the product, including the fitting of non-Juniper Networks option cards.
This product has been tested and found to comply with the limits for Class A
Information Technology Equipment according to CISPR 22/European Standard EN
55022. The limits for Class A equipment were derived for commercial and industrial environments to provide reasonable protection against interference with licensed communication equipment.
CAUTION: This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Taiwanese Class A Warning Statement
Chinese Class A Warning Statement
184 ■
Electronic Emission Notices for the JCS 1200 Platform
Appendix A: Safety and Regulatory Compliance Information
Japanese Voluntary Control Council for Interference (VCCI) Statement
JCS 1200 Declaration of Conformity
Figure 86: JCS 1200 Declaration of Conformity
Related Topics
■
Agency Approvals for the JCS 1200 Platform on page 181
Electronic Emission Notices for the JCS 1200 Platform
■ 185
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
Compliance Statements for Environmental Requirements for the JCS 1200
186 ■
Electronic Emission Notices for the JCS 1200 Platform
Appendix B
Environmental Specifications
■
JCS 1200 Platform Environmental Specifications on page 187
JCS 1200 Platform Environmental Specifications
Table 25 on page 187 specifies the environmental specifications required for normal
platform operation. In addition, the site should be as dust-free as possible. Dust can clog air intake vents, reducing cooling system efficiency. Check the vents frequently, cleaning them as necessary.
Table 25: Platform Environmental Specifications
Description
Altitude
Relative humidity
Temperature
Value
No performance degradation to 10,000 ft (3048 m)
Normal operation ensured in relative humidity range of 5% to
85%, noncondensing
Normal operation ensured in temperature range of 41° F (5° C) to
104° F (40° C)
Nonoperating storage temperature in shipping crate:
–40° F (–40° C) to 158° F (70° C)
Seismic activity
Maximum thermal output
Tested to meet Telcordia Technologies Zone 4 earthquake requirements
DC power: 10,742 BTU/hour (3150 W)
AC power: 11,935 BTU/hour (3500 W)
NOTE: These specifications are estimates and subject to change.
JCS 1200 Platform Environmental Specifications
■ 187
Juniper Control System (JCS) 1200 Platform Hardware Guide
NOTE: Install the platform only in restricted areas, such as dedicated equipment rooms and equipment closets, in accordance with Articles 110-16, 110-17, and
110-18 of the National Electrical Code, ANSI/NFPA 70.
For additional safety guidelines and requirements, see “Safety Requirements,
Warnings, and Guidelines for Installing the JCS 1200 Platform” on page 49.
Related Topics
■
■
■
Compliance Statements for Environmental Requirements for the JCS 1200
Safety Requirements, Warnings, and Guidelines for Installing the JCS 1200
JCS 1200 Platform Features and Specifications on page 7
188 ■
JCS 1200 Platform Environmental Specifications
Appendix C
Power Requirements, Guidelines, and
Specifications
For site wiring and power system guidelines, requirements, and specifications, see the following topics:
■
■
■
■
■
■
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
AC Power Supply Electrical Specifications for the JCS 1200 Platform on page 190
Power Consumption for an AC-Powered JCS 1200 Platform on page 190
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
JCS 1200 Alarm Panel Module Interface Connector Electrical
Site Electrical Wiring Guidelines for the JCS 1200 Platform
■
■
■
Distance limitations for signaling—Improperly installed wires can emit radio interference. In addition, the potential for damage from lightning strikes increases if wires exceed recommended distances or if wires pass between buildings. The electromagnetic pulse (EMP) caused by lightning can damage unshielded conductors and destroy electronic devices. If your site has previously experienced such problems, you might want to consult experts in electrical surge suppression and shielding.
Radio frequency interference—You can reduce or eliminate the emission of radio frequency interference (RFI) from your site wiring by using twisted-pair cable with a good distribution of grounding conductors. If you must exceed the recommended distances, use a high-quality twisted-pair cable with one ground conductor for each data signal when applicable.
Electromagnetic compatibility—If your site is susceptible to problems with electromagnetic compatibility (EMC), particularly from lightning or radio transmitters, you might want to seek expert advice. Strong sources of electromagnetic interference (EMI) can destroy the signal drivers and receivers in the routing platform and conduct power surges over the lines into the equipment, resulting in an electrical hazard. It is particularly important to provide a properly grounded and shielded environment and to use electrical surge-suppression devices.
Site Electrical Wiring Guidelines for the JCS 1200 Platform
■ 189
Juniper Control System (JCS) 1200 Platform Hardware Guide
CAUTION: To comply with intrabuilding lightning and surge requirements, intrabuilding wiring must be shielded, and the shield for the wiring must be grounded at both ends.
Related Topics
■
■
■
■
AC Power Supply Electrical Specifications for the JCS 1200 Platform on page 190
Power Consumption for an AC-Powered JCS 1200 Platform on page 190
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
AC Power Supply Electrical Specifications for the JCS 1200 Platform
Table 26 on page 190 lists the AC power system and power supply electrical
specifications.
Table 26: AC Power Electrical Specifications for the JCS 1200 Platform
Item
Power System
AC input voltage
AC input line frequency
AC system current rating
AC system input power
Specification
Operating range: 200 to 240 VAC
50 to 60 Hz (nominal)
32 A @ 220 VAC (16 A per inlet)
8000 W
Power Supply
Maximum output power
AC input line frequency
2880 W
50 to 60 Hz (nominal)
Related Topics
■
■
■
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
Power Consumption for an AC-Powered JCS 1200 Platform on page 190
Connecting the JCS 1200 AC Platform to AC Power on page 62
Power Consumption for an AC-Powered JCS 1200 Platform
Table 27 on page 191 lists the power requirements for base AC-powered routers
operating under typical voltage conditions and includes nonredundant and redundant power supply configurations.
190 ■
AC Power Supply Electrical Specifications for the JCS 1200 Platform
Appendix C: Power Requirements, Guidelines, and Specifications
Table 27: AC-Powered Base JCS 1200 Platform Power Requirements
AC Power Supply Configuration
Power
Requirement
(Watts)
4 AC power supplies, 4 fan modules, 1 management module, 1 media tray, 1 switch module, 1 midplane, 1
MUX card, 1 alarm panel module, (nonredundant configuration)
4 AC power supplies, 4 fan modules, 1 management module, 1 media tray, 1 switch module, 1 midplane, 1
MUX card, 1 alarm panel module, 12 Routing Engines
(nonredundant configuration)
735 W
4095 W
4 AC power supplies, 4 fan modules, 2 management modules, 2 media trays, 2 switch modules, 1 midplane,
1 MUX card, 1 alarm panel module, (redundant configuration)
1015 W
4 AC power supplies, 4 fan modules, 2 management modules, 2 media trays, 2 switch modules, 1 midplane,
1 MUX card, 1 alarm panel module, 12 Routing Engines
(redundant configuration)
4375 W
AC Input at 90%
Efficiency
817 W
(approximate)
4550 W
(approximate)
1128 W
(approximate)
4861 W
(approximate)
Table 28 on page 191 lists the lists the power requirements for various hardware
components when the platform is operating under typical voltage conditions.
Table 28: AC-Powered JCS 1200 Platform Component Power Requirements
Item
Alarm panel module
Fan module
Management module
Media tray
Midplane
MUX card
Power module
Routing Engine
20 W
15 W
10 W
15 W
36 W
280 W
Power Requirement (Watts) AC Input at 90% Efficiency
10 W
85 W
11 W
94 W
22 W
17 W
11 W
17 W
40 W
311 W
Related Topics
■
■
■
Switch module 45 W 50 W
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
AC Power Supply Electrical Specifications for the JCS 1200 Platform on page 190
Connecting the JCS 1200 AC Platform to AC Power on page 62
Power Consumption for an AC-Powered JCS 1200 Platform
■ 191
Juniper Control System (JCS) 1200 Platform Hardware Guide
DC Power Supply Electrical Specifications for the JCS 1200 Platform
Table 29 on page 192 lists the DC power supply and power system electrical
specifications.
Table 29: DC Power Electrical Specifications for the JCS 1200 Platform
Item Specification
Related Topics
■
■
■
Power System
DC input voltage
DC system current rating
DC system input
Power Supply
Maximum output power
DC input voltage
Nominal: –48 A, –60 VDC
Operating range: –40 A to –60 VDC
–48 A @ –60 VDC
8830 W
3160 W
Nominal: –48 A, –60 VDC
Operating range: –40 to –60 VDC
204 A @ –38 VDC DC input current rating
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
Power Consumption for a DC-Powered JCS 1200 Platform on page 192
Connecting the JCS 1200 DC Platform to DC Power on page 63
Power Consumption for a DC-Powered JCS 1200 Platform
Table 30 on page 192 lists the power requirements for base DC-powered routers
operating under typical voltage conditions and includes nonredundant and redundant power supply configurations.
Table 30: DC-Powered Base JCS 1200 Platform Power Requirements
DC Power Supply Configuration
Power
Requirement
(Watts)
4 DC power supplies, 4 fan modules,
1 management module, 1 media tray, 1 switch module, 1 midplane,
1 MUX card, 1 alarm panel module,
(nonredundant configuration)
735 W
DC Input at 88%
Efficiency
Current
Requirement
(Amps @
–48 VDC)
835 W
(approximate)
17.4 A
(approximate)
192 ■
DC Power Supply Electrical Specifications for the JCS 1200 Platform
Appendix C: Power Requirements, Guidelines, and Specifications
Table 30: DC-Powered Base JCS 1200 Platform Power Requirements (continued)
DC Power Supply Configuration
Power
Requirement
(Watts)
4 DC power supplies, 4 fan modules,
1 management module, 1 media tray, 1 switch module, 1 midplane,
1 MUX card, 1 alarm panel module,
12 Routing Engines (nonredundant configuration)
4095 W
4 DC power supplies, 4 fan modules,
2 management modules, 2 media trays, 2 switch modules, 1 midplane,
1 MUX card, 1 alarm panel module,
(redundant configuration)
1015 W
4 DC power supplies, 4 fan modules,
2 management modules, 2 media trays, 2 switch modules, 1 midplane,
1 MUX card, 1 alarm panel module,
12 Routing Engines (redundant configuration)
4375 W
DC Input at 88%
Efficiency
Current
Requirement
(Amps @
–48 VDC)
4653 W
(approximate)
96.9 A
(approximate)
1153 W
(approximate)
4972 W
(approximate)
24.0 A
(approximate)
103.6 A
(approximate)
Table 31 on page 193 lists the lists the power requirements for various hardware
components when the platform is operating under typical voltage conditions.
Table 31: DC-Powered JCS 1200 Platform Component Power Requirements
Item
Alarm panel module
Fan module
Power Requirement
(Watts)
10 W
85 W
Management module 20 W
Media tray
Midplane
MUX card
Power module
Routing Engine
Switch module
15 W
10 W
15 W
36 W
280 W
45 W
DC Input at 88%
Efficiency
11 W (approximate)
97 W (approximate)
23 W (approximate)
Current Requirement
(Amps @ –48 VDC)
0.2 A (approximate)
2.0 A (approximate)
0.5 A (approximate)
17 W (approximate)
11 W (approximate)
17 W (approximate)
41 W (approximate)
0.4 A (approximate)
0.2 A (approximate)
0.4 A (approximate)
0.9 A (approximate)
318 W (approximate) 6.6 A (approximate)
51 W (approximate) 1.1 A (approximate)
Related Topics
■
■
Site Electrical Wiring Guidelines for the JCS 1200 Platform on page 189
DC Power Supply Electrical Specifications for the JCS 1200 Platform on page 192
Power Consumption for a DC-Powered JCS 1200 Platform
■ 193
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
Connecting the JCS 1200 DC Platform to DC Power on page 63
JCS 1200 Alarm Panel Module Interface Connector Electrical Specifications
Table 32 on page 194 lists the electrical specifications for the JCS 1200 alarm panel
interface connector.
Table 32: JCS 1200 Alarm Panel Interface Connector Electrical Specifications
Item
Outputs
Voltage range
Current range
Worst-case VA
Inputs
Voltage range
Differential input voltage
Reset Input Activation
Pulse width
Specification
0 V DC to –100 V DC (maximum current 0.3 A at 100 V DC)
0 A to 1 A (maximum voltage 30 V DC at 1 A)
1 A at –30 V DC (30 VA maximum) indefinitely
0 V DC to –100 V DC (including transients)
3 V DC to 72 V DC
200 ms (minimum) to 300 ms
NOTE: The reset input resets only the state of the relay contact. The chassis alarm status does not change.
Related Topics
■
■
■
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Alarm Panel Module Connectors and LEDs on page 12
Replacing a JCS 1200 Alarm Panel Module or Module Filler on page 96
194 ■
JCS 1200 Alarm Panel Module Interface Connector Electrical Specifications
Appendix D
Contacting Customer Support and
Returning Hardware
This appendix describes how to return the platform or individual components to
Juniper Networks for repair or replacement:
■
■
■
■
■
■
Locating Component Serial Numbers on page 195
Contacting Customer Support on page 206
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Packing the JCS 1200 Platform for Shipment on page 208
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating Component Serial Numbers
Before contacting Juniper Networks, Inc. to request a Return Materials Authorization
(RMA), you must find the serial number on the platform or component. Most components have a small rectangular serial number ID label (see
Figure 87 on page 195) attached to the component body. You can also display the
JCS 1200 platform components and serial numbers from the management module command-line interface (CLI).
Figure 87: Serial Number ID Label
The following topics describe the label location on each type of component:
■
■
■
■
■
■
■
Locating the JCS 1200 Chassis Serial Number on page 196
Locating the JCS 1200 Alarm Panel Serial Number on page 197
Locating the JCS 1200 Fan Module Serial Number on page 198
Locating the JCS 1200 Management Module Serial Number on page 199
Locating the JCS 1200 Media Tray Serial Number on page 200
Locating the JCS 1200 Midplane Serial Number on page 201
Locating the JCS 1200 MUX Card Serial Number on page 201
Locating Component Serial Numbers
■ 195
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
■
Locating the JCS 1200 Power Module Serial Number on page 202
Locating the JCS 1200 Routing Engine Serial Number on page 203
Locating the JCS 1200 Switch Module Serial Number on page 205
Locating the JCS 1200 Chassis Serial Number
The chassis serial number, machine type, and model number are on labels on the
top, front, and rear of the chassis (see Figure 88 on page 196).
Figure 88: JCS 1200 Chassis Serial Number Label
Record information about your JCS 1200 platform in Table 33 on page 196. You will
need this information for future reference.
Table 33: Information About Your JCS 1200 Platform
Identifier
Product name
Serial number
Machine type
Model number
Value
JCS 1200 platform
To display the chassis serial number, enter the info command from the management module CLI.
The chassis serial number is located in the
Manufacturer
field as shown in the following sample output:
196 ■
Locating the JCS 1200 Chassis Serial Number
Appendix D: Contacting Customer Support and Returning Hardware system> info
UUID: DB39 735D 4512 319C BD74 4CC4 9376 DA98
Manufacturer: ZX1234
Manufacturer ID: 20301
Product code: System Enclosure/CHAS-BP-JCS1200-S/
Serial number: 01
Part no.: 740-023156
Component serial no.: JCS-CHASSIS-SN-BCG001
CLEI: Not Available
AMM slots: 2
Blade slots: 12
I/O Module slots: 10
Power Module slots: 4
Blower slots: 4
Media Tray slots: 2
Related Topics
■
■
Contacting Customer Support on page 206
JCS 1200 Return Procedure on page 207
■
■
Packing the JCS 1200 Platform for Shipment on page 208
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Alarm Panel Serial Number
The alarm panel module serial number is located on the side of the alarm panel
module (see Figure 89 on page 197).
Figure 89: JCS 1200 Alarm Panel Module Serial Number Label
To display the alarm panel module serial number, enter the info -T tap
command from the management module CLI.
The alarm panel module serial number is located in the Component serial no.
field as shown in the following sample output: system> info -T tap
UUID: A7FE 29E1 1593 11DC ADF2 FC4F AE7A C10F
Manufacturer: Not Available (SLRM)
Manufacturer ID: 20301
Product code: JCS1200 Alarm Panel
Serial number: Not Available
Locating the JCS 1200 Alarm Panel Serial Number
■ 197
Juniper Control System (JCS) 1200 Platform Hardware Guide
Part no.: 740-023160
Component serial no.: JCS-TAP-SN-BCG001
CLEI: Not Available
Related Topics
■
Replacing a JCS 1200 Alarm Panel Module or Module Filler on page 96
■
Contacting Customer Support on page 206
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Fan Module Serial Number
The fan module serial number is located on the side of the fan module (see
Figure 90: JCS 1200 Fan Module Serial Number Label
To display the fan module serial number, enter the info -T blower[x] command (where
x is a value of 1 through 4 for each fan module) from the management module CLI.
The fan module serial number is located in the
Component serial no.
field as shown in the following sample output: system> info -T blower[1]
UUID: 1601 C5E1 5799 11DC A366 BE61 4AB2 5367
Manufacturer: Not Available (DELT)
Manufacturer ID: 20301
Product code: JCS1200 Fan Tray
Serial number: Not Available
Part no.: 740-023165
Component serial no.: JCS-BLOWER-SN-BCG001
CLEI: Not Available
Status: ok
Speed ( % of Max): 59%
Avg RPM: 3296
198 ■
Locating the JCS 1200 Fan Module Serial Number
Appendix D: Contacting Customer Support and Returning Hardware
Control State: Operational
VPD: 14
Related Topics
■
Replacing a JCS 1200 Fan Module on page 116
■
Contacting Customer Support on page 206
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Management Module Serial Number
The product name, serial number, and media access control (MAC) address are located on the identification label on the side of the management module (see
Figure 91 on page 199). The MAC address and the default IP address are on a separate
label on the bottom of the front of the management module.
Figure 91: JCS 1200 Management Module Serial Number Label
To display the management module serial number, enter the info -T mm[x]
command
(where x is a value of 1 or 2 for each management module) from the management module CLI.
The management module serial number is located in the
Component serial no.
field as shown in the following sample output: system> info -T mm[1]
Name: SN#YK148178117W
UUID: 369C 7EB6 4067 11DC AAAE 0014 5EDF 924E
Manufacturer: Not Available (ASUS)
Manufacturer ID: 20301
Product code: JCS Adv Management Module
Serial number: Not Available
Part no.: 740-023172
Component serial no.: JCS-MM-SN-BCG001
Locating the JCS 1200 Management Module Serial Number
■ 199
Juniper Control System (JCS) 1200 Platform Hardware Guide
CLEI: Not Available
AMM firmware
Build ID: BPEO36F
File name: CNETCMUS.PKT
Rel date: 02-11-08
Rev: 36
Related Topics
■
Replacing a JCS 1200 Management Module or Module Filler on page 124
■
Contacting Customer Support on page 206
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Media Tray Serial Number
The media tray serial number is located on the side of the media tray (see
Figure 92: JCS 1200 Media Tray Serial Number Label
To display the media tray serial number, enter the info -T mt[x]
command (where x is a value of 1 or 2 for each media tray) from the management module CLI.
The media tray serial number is located in the Component serial no.
field as shown in the following sample output: system> info -T mt[1]
UUID: 10C9 6C41 24C7 11DC A824 DA2B 921E 8515
Manufacturer: Not Available (SLRM)
Manufacturer ID: 20301
Product code: JCS1200 Media Tray
Serial number: Not Available
Part no.: 740-023169
Component serial no.: JCS-MT-SN-BCG001
CLEI: Not Available
Related Topics
■
Replacing a JCS 1200 Media Tray on page 128
■
Contacting Customer Support on page 206
200 ■
Locating the JCS 1200 Media Tray Serial Number
Appendix D: Contacting Customer Support and Returning Hardware
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Midplane Serial Number
The midplane serial number is not visible on the chassis. To view the serial number
label, you must remove the components that attach to the midplane (see “Removing
Components from a JCS 1200 Chassis” on page 113).
To display the midplane serial number from the management module CLI, enter the info
command.
The midplane serial number is located in the Component serial no.
field as shown in the following sample output: system> info
UUID: DB39 735D 4512 319C BD74 4CC4 9376 DA98
Manufacturer: ZX1234
Manufacturer ID: 20301
Product code: System Enclosure/CHAS-BP-JCS1200-S/
Serial number: 01
Part no.: 740-023156
Component serial no.: JCS-CHASSIS-SN-BCG001
CLEI: Not Available
AMM slots: 2
Blade slots: 12
I/O Module slots: 10
Power Module slots: 4
Blower slots: 4
Media Tray slots: 2
Related Topics
■
■
■
Replacing a JCS 1200 Midplane on page 130
Contacting Customer Support on page 206
JCS 1200 Return Procedure on page 207
■
■
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 MUX Card Serial Number
The MUX card serial number is located on the side of the MUX card.
To display the MUX card serial number, enter the info -T mux[x] command (where x is a value of 1 or 2 for each MUX card) from the management module CLI.
The MUX card serial number is located in the
Component serial no.
field as shown in the following sample output:
Locating the JCS 1200 Midplane Serial Number
■ 201
Juniper Control System (JCS) 1200 Platform Hardware Guide system> info -T mux[1]
UUID: 10C9 6C41 24C7 11DC A824 DA2B 921E 8515
Manufacturer: Not Available (SLRM)
Manufacturer ID: 20301
Product code: JCS1200 MUX card
Serial number: Not Available
Part no.: 740-023169
Component serial no.: JCS-MT-SN-BCG001
CLEI: Not Available
Related Topics
■
■
Replacing a JCS 1200 MUX Card on page 131
Contacting Customer Support on page 206
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Power Module Serial Number
The power module serial number is located on the top of the power module (see
Figure 93: JCS 1200 Power Module Serial Number Label
To display the power module serial number, enter the info -T power[x] command
(where x is a value of 1 through 4 for each power module) from the management module CLI.
202 ■
Locating the JCS 1200 Power Module Serial Number
Appendix D: Contacting Customer Support and Returning Hardware
The power module serial number is located in the
Component serial no.
field as shown in the following sample output: system> info -T power[1]
UUID: D12E 12E5 8977 4A59 B119 3B74 90E2 D2DE
Manufacturer: Not Available (ASTE)
Manufacturer ID: 320
Product code: JCS1200 AC Power Supply
Serial number: Not Available
Part no.: 740-023174
Component serial no.: JCS-POWER-SN-BCG001
CLEI: Not Available
Power Module Cooling Device firmware rev.: 14
Power Module Cooling Device:
Status: ok
Count: 3
Speed: 71%
Avg RPM: 7125
Control State: Operational
Related Topics
■
■
Replacing a JCS 1200 Power Module on page 138
Contacting Customer Support on page 206
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Routing Engine Serial Number
The Routing Engine model number and serial number are located on the ID label that is behind the control panel door on the front of the Routing Engine, and on a label on the side of the Routing Engine that is visible when the Routing Engine is not
in the JCS 1200 platform (see Figure 94 on page 203).
Figure 94: JCS 1200 Routing Engine Serial Number Label
Locating the JCS 1200 Routing Engine Serial Number
■ 203
Juniper Control System (JCS) 1200 Platform Hardware Guide
To display the Routing Engine serial number, enter the info -T blade[x]
command
(where x is a value of 1 through 12 for each Routing Engine) from the management module CLI.
The Routing Engine serial number is located in the Component serial no.
field as shown in the following sample output: system> info -T blade[1]
UUID: DB39 735D 4512 319C BD74 4CC4 9376 DA98
Manufacturer: Not Available (Not Available)
Manufacturer ID: 20301
Product code: System Enclosure/JCS1200 Chassis/
Serial number: Not Available
Part no.: 740-023156
Component serial no.: JCS-CHASSIS-SN-BCG001
CLEI: Not Available
AMM slots: 2
Blade slots: 12
I/O Module slots: 10
Power Module slots: 4
Blower slots: 4
Media Tray slots: 2
A set of blank labels comes with each Routing Engine (see Figure 95 on page 204).
Record identifying information on a label, and place it on the JCS 1200 platform top bezel, just above the Routing Engine. Do not place the label on the Routing Engine itself or in any way block the ventilation holes on the Routing Engine.
Figure 95: User Label Locations on the JCS 1200 Platform
Related Topics
■
■
■
Powering Off a JCS 1200 Routing Engine on page 74
Replacing a JCS 1200 Routing Engine on page 140
Contacting Customer Support on page 206
204 ■
Locating the JCS 1200 Routing Engine Serial Number
Appendix D: Contacting Customer Support and Returning Hardware
■
■
■
JCS 1200 Return Procedure on page 207
Packing the JCS 1200 Platform for Shipment on page 208
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Locating the JCS 1200 Switch Module Serial Number
The switch module serial number is located on the side of the switch module (see
Figure 96: JCS 1200 Switch Module Serial Number Label
To display the switch module serial number, enter the info -T switch[x]
command
(where x is a value of 1 or 2 for each switch module) from the management module
CLI.
The switch module serial number is located in the Component serial no.
field as shown in the following sample output: system> info -T switch[1]
Interposer ISL installed
UUID: 0018 B11B 8900 0000 0000 0000 0000 0000
Manufacturer: Not Available (BNT)
Manufacturer ID: 20301
Product code: JCS L2/L3 Switch Module
Serial number: Not Available
Part no.: 740-023179
Component serial no.: JCS-SWITCH-SN-BCG001
CLEI: COUCAAGAAA
Unique ID 1: Not Available
Boot ROM
Build ID: WMZ04002
Rel date: 02/06/2008
Rev: 0104
Main Application 1
Build ID: WMZ04002
Rel date: 02/06/2008
Rev: 0104
Locating the JCS 1200 Switch Module Serial Number
■ 205
Juniper Control System (JCS) 1200 Platform Hardware Guide
Main Application 2
Build ID: WMZ04002
Rel date: 02/06/2008
Rev: 0104
MAC Address: 00:18:B1:1B:89:00
Related Topics
■
Replacing a JCS 1200 Switch Module or Module Filler on page 143
■
Contacting Customer Support on page 206
■
■
■
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Contacting Customer Support
You can contact Juniper Networks Technical Assistance Center (JTAC) 24 hours a day, 7 days a week in one of the following ways:
■
On the Web, using the Case Manager link at:
■ http://www.juniper.net/support/
By telephone:
From the US and Canada: 1-888-314-JTAC
From all other locations: 1-408-745-9500
If contacting JTAC by phone, enter your 11-digit case number followed by the # key if this is an existing case, or press the * key to be routed to the next available support engineer.
Related Topics
■
■
■
■
When requesting support from JTAC by telephone, be prepared to provide the following information:
■
■
■
■
Your existing case number, if you have one
Details of the failure or problem
Type of activity being performed on the platform when the problem occurred
Configuration data using one or more of the show commands
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Packing the JCS 1200 Platform for Shipment on page 208
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
206 ■
Contacting Customer Support
Appendix D: Contacting Customer Support and Returning Hardware
JCS 1200 Return Procedure
If the problem cannot be resolved by the JTAC technician, an RMA is issued. This number is used to track the returned material at the factory and to return repaired or new components to the customer as needed.
NOTE: Do not return any component to Juniper Networks, Inc. unless you have first obtained an RMA number. Juniper Networks, Inc. reserves the right to refuse shipments that do not have an RMA. Refused shipments will be returned to the customer via collect freight.
For more information about return and repair policies, see the customer support
Web page at http://www.juniper.net/support/guidelines.html
.
For product problems or technical support issues, contact the Juniper Networks
Technical Assistance Center (JTAC) using the Case Manager link at http://www.juniper.net/support/
, or at 1-888-314-JTAC (within the United States) or
1-408-745-9500 (from outside the United States).
1.
2.
When you need to return a component:
Determine the part number and serial number of the component.
Obtain a Return Materials Authorization (RMA) number from the Juniper Networks
Technical Assistance Center (JTAC). You can send e-mail or telephone as described above.
3.
Provide the following information in your e-mail message or during the telephone call:
■
■
Part number and serial number of component
Your name, organization name, telephone number, and fax number
■
Description of the failure
4.
5.
The support representative validates your request and issues an RMA number for return of the component.
Pack the platform or component for shipment, as described in “Guidelines for
Related Topics
■
■
■
■
■
■
■
■
Locating the JCS 1200 Alarm Panel Serial Number on page 197
Locating the JCS 1200 Chassis Serial Number on page 196
Locating the JCS 1200 Fan Module Serial Number on page 198
Locating the JCS 1200 Management Module Serial Number on page 199
Locating the JCS 1200 Media Tray Serial Number on page 200
Locating the JCS 1200 Midplane Serial Number on page 201
Locating the JCS 1200 MUX Card Serial Number on page 201
Locating the JCS 1200 Power Module Serial Number on page 202
JCS 1200 Return Procedure
■ 207
Juniper Control System (JCS) 1200 Platform Hardware Guide
■
■
Locating the JCS 1200 Routing Engine Serial Number on page 203
Locating the JCS 1200 Switch Module Serial Number on page 205
Tools and Parts Required to Remove Components from the JCS 1200 Platform
Related Topics
■
■
■
■
To remove components from the platform or the platform from a rack, you need the following tools and parts:
■
2.5-mm flat-blade (–) screwdriver, for detaching alarm relay terminal block
■
■
■
■
10-mm. hexagonal-head external drive socket wrench, or nut driver
3/8-in. nut driver
7/16-in. nut driver
Blank panels to cover empty slots
■
■
■
■
■
■
■
Electrostatic bag or antistatic mat, for each component
Electrostatic discharge (ESD) grounding wrist strap
Flat-blade (–) screwdriver
Mechanical lift, if available
Phillips (+) screwdrivers, numbers 1 and 2
Rubber safety cap for fiber-optic PICs or PIC cable
Wire cutters
Contacting Customer Support on page 206
JCS 1200 Return Procedure on page 207
Packing the JCS 1200 Platform for Shipment on page 208
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Packing the JCS 1200 Platform for Shipment
To pack the platform for shipment, follow this procedure:
1.
Retrieve the shipping crate and packing materials in which the platform was originally shipped. If you do not have these materials, contact your Juniper
Networks representative about approved packaging materials.
2.
3.
4.
5.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist and connect the strap to one of the ESD points on the chassis.
Shut down power to the JCS 1200 platform by pressing the power switch for all power supplies to the off ( O ) position. On both AC and DC power supplies, the switch is located on the power supply faceplate.
Disconnect power from the JCS 1200 platform.
Remove the cables that connect to all external devices. See the removal procedure for each component.
208 ■
Tools and Parts Required to Remove Components from the JCS 1200 Platform
Appendix D: Contacting Customer Support and Returning Hardware
6.
7.
Remove all field replaceable units (FRUs) from the JCS 1200 platform.
Remove the JCS 1200 platform from the rack:
■
■
If you are using a mechanical lift, place the lift platform under the JCS 1200 platform, unscrew and remove the mounting screws from the rack, and move the JCS 1200 platform to the shipping crate.
If you are not using a mechanical lift and the JCS 1200 platform weight is fully supported by a shelf or another JCS 1200 platform, unscrew and remove the mounting screws from the rack. Three people can then lift the JCS 1200 platform and move it to the shipping crate.
■
If you are not using a mechanical lift and the platform weight is not fully supported by a shelf or another platform, three people should grasp the platform while a fourth person unscrews and removes the mounting screws from the rack. The three lifters can then move the platform to the shipping crate.
8.
9.
Place the JCS 1200 platform in the shipping crate or onto the pallet. If on a pallet, bolt the JCS 1200 platform to the pallet.
Cover the JCS 1200 platform with an ESD bag and place the packing foam on top of and around the platform.
10.
Replace the accessory box on top of the packing foam.
11.
Securely tape the box closed or place the crate cover over the JCS 1200 platform.
12.
Write the RMA number on the exterior of the box to ensure proper tracking.
Related Topics
■
■
■
■
Contacting Customer Support on page 206
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Guidelines for Packing JCS 1200 Platform Components for Shipment on page 209
Guidelines for Packing JCS 1200 Platform Components for Shipment
To pack and ship individual components:
■
When you return components, make sure they are adequately protected with packing materials and packed so that the pieces are prevented from moving around inside the carton.
■
■
■
Use the original shipping materials if they are available.
Place individual boards in electrostatic bags.
Write the RMA number on the exterior of the box to ensure proper tracking.
CAUTION: Do not stack any of the routing platform components.
Guidelines for Packing JCS 1200 Platform Components for Shipment
■ 209
Juniper Control System (JCS) 1200 Platform Hardware Guide
Related Topics
■
■
■
■
Contacting Customer Support on page 206
JCS 1200 Return Procedure on page 207
Tools and Parts Required to Remove Components from the JCS 1200
Packing the JCS 1200 Platform for Shipment on page 208
210 ■
Guidelines for Packing JCS 1200 Platform Components for Shipment
Appendix E
Cable Connector Pinouts
This appendix describes the pinouts for the following cable connectors:
■
■
■
Serial Cable Characteristics for the JCS 1200 Management Module on page 211
Pinouts for the RJ-45 Adapters on page 212
Pinouts for the JCS 1200 Alarm Panel Interface Connector on page 213
Serial Cable Characteristics for the JCS 1200 Management Module
Pinouts for the management module serial cable are shown in Table 34 on page 211.
Table 34: Serial Cable Characteristics for the JCS 1200 Platform
RJ-45 Signal
TxD out
RxD in
RTS out
CTS in
DTR out
DSR in
DCD in
RI in
GND
1
2 n/a
4
5
8
7
3
RJ-45 Pins
6
RJ-45 Cable
Yellow
Green
White
Brown
Black
Blue
Orange n/a
Red
DB-9 Signal
RxD in
TxD out
CTS in
RTS out
DSR in
DTR out
DCD in
RI in
GND
4 n/a n/a
5
3
8
7
6
DB-9 Pins
2
Related Topics
■
■
■
■
JCS 1200 Management Module Description on page 15
JCS 1200 Management Module Connectors and LEDs on page 16
Connecting the JCS 1200 Management Module to the Network on page 68
Establishing Your JCS 1200 Management Module Connection on page 70
Serial Cable Characteristics for the JCS 1200 Management Module
■ 211
Juniper Control System (JCS) 1200 Platform Hardware Guide
Pinouts for the RJ-45 Adapters
If needed, you can use the RJ-45 AMM adapter to connect a console to the
management module. Pinouts for the AMM adapter are shown in Table 35 on page 212.
Table 35: Pinouts for the AMM Adapter
6
7
8
4
5
2
3
RJ-45 Female
1
GND
GND
RX
DSR
CTS
Input/Output signal
RTS
DTR
TX
3
6
RJ-45 Male
1
5
1
7
4
2 (DCD)
To connect a console to the JCS 1200 Routing Engines, you can connect a breakout serial cable to the external serial port on the alarm panel module. If needed, you can use the RJ-45 CPU adapters to connect each of the 12 RJ-45 connectors to the console.
Pinouts for the CPU adapter match the breakout cable and are shown in
Table 36: Pinouts for the CPU Adapter and Breakout Serial Cable
6
7
8
2
3
4
5
RJ-45 Female
1
TX
–
CTS
Input/Output signal
RTS
–
RX
GND
–
3
–
8
–
6
4
–
RJ-45 Male
1
Related Topics
■
■
Connecting the JCS 1200 Management Module to the Network on page 68
Connecting a Console to the JCS 1200 Routing Engines on page 72
212 ■
Pinouts for the RJ-45 Adapters
Appendix E: Cable Connector Pinouts
Pinouts for the JCS 1200 Alarm Panel Interface Connector
The alarm panel module provides one DB-15 connector (male) for critical, major, and minor telco alarms. Each of the alarms has a relay that enables multiple system
alarm indicators to be daisy-chained together. Table 37 on page 213 shows the pinouts
for the alarm panel interface connector.
Table 37: Pinouts for the Alarm Panel Interface Connector
Pin # Description Input/Output Signal
10
11
12
13
14
15
7
8
9
4
5
6
1
2
3
Minor alarm reset +
Minor alarm reset –
Major alarm reset +
Major alarm reset –
Critical alarm normally open
Critical alarm normally closed
Critical alarm common
Minor alarm normally open
Minor alarm normally closed
Minor alarm common
Major alarm normally open
Major alarm normally closed
Major alarm common
Reserved
Reserved
Output
Output
Output
Output
Output
Output
Output
Reserved
Reserved
Input
Input
Input
Input
Output
Output
Related Topics
■
■
JCS 1200 Alarm Panel Module Description on page 12
JCS 1200 Alarm Panel Module Connectors and LEDs on page 12
Pinouts for the JCS 1200 Alarm Panel Interface Connector
■ 213
Juniper Control System (JCS) 1200 Platform Hardware Guide
214 ■
Pinouts for the JCS 1200 Alarm Panel Interface Connector
Part 5
Index
■
Index
■ 215
Juniper Control System (JCS) 1200 Platform Hardware Guide
216 ■
Index
Index
Symbols
#, comments in configuration statements.................xxiii
( ), in syntax descriptions..........................................xxiii
< >, in syntax descriptions......................................xxiii
[ ], in configuration statements.................................xxiii
{ }, in configuration statements................................xxiii
| (pipe), in syntax descriptions..................................xxiii
A
AC power
connecting............................................................62
consumption.......................................................190
disconnecting........................................................65
electrical specifications.......................................190
provisioning........................................................190
accessory box
parts list................................................................41
removing..............................................................40
acoustics........................................................................7
active LED....................................................................18
agency approvals.......................................................181
air temperature..............................................................7
airflow
required clearance around chassis for...................38
alarm panel interface connector
electrical specifications.......................................194
location.................................................................12
pinouts................................................................213
alarm panel module
description............................................................12
installing...............................................................96
LEDs.....................................................................12
overview...............................................................12
removing..............................................................96
replacing...............................................................96
serial number, locating.......................................197
alarm panel module fault LED......................................13
altitude, acceptable range..........................................187
antistatic mat, using...................................................154
approvals, agency......................................................181
B
battery
environmental compliance.................................183
bezel
lithium................................................................183
installing...............................................................98
removing..............................................................97
replacing...............................................................97
bezel collar
installing.............................................................102
removing............................................................100
replacing...............................................................99
bezel filter
installing.............................................................108
removing............................................................107
replacing.............................................................107
blade See Routing Engine
braces, in configuration statements...........................xxiii
brackets
angle, in syntax descriptions..............................xxiii
square, in configuration statements...................xxiii
buttons
CD/diskette/USB (on Routing Engine)....................26
keyboard/video/mouse (on Routing Engine)..........26
media tray select (on Routing Engine)...................26
power control (on Routing Engine).......................26
reset (on management module)............................17
C
cabinet mounting
requirements........................................................34
cable management trays
installing.............................................................111
removing............................................................110
replacing.............................................................110
cabling the remote connection Ethernet port ..............69
card multiplexer See MUX card
case number, for JTAC...............................................206
chassis
installing.............................................................114
installing in rack...................................................51
lifting guidelines..................................................155
Index
■ 217
Juniper Control System (JCS) 1200 Platform Hardware Guide
removing............................................................113
replacing.............................................................113
serial number, locating.......................................196
checklist
installation............................................................94
site preparation.....................................................33
Class A electronic emission notice.............................183
clearance, around rack.................................................38
comments, in configuration statements....................xxiii
compact flash, problems..............................................88
compatibility, electromagnetic...................................189
compliance
general standards...............................................181
components
description..............................................................9
front view.........................................................4, 10
rear view...........................................................5, 11
configuration guidelines...............................................81
connectors alarm panel module
serial..............................................................13
Telco alarm....................................................13
front view.........................................................4, 10
management module
console..........................................................16
Ethernet.........................................................16
serial..............................................................16
USB...............................................................16
video.............................................................16
media tray
USB...............................................................19
rear view...........................................................5, 11
switch module
Ethernet.........................................................28
serial..............................................................28
console connector
management module............................................16
control panel, Routing Engine......................................25
conventions
notice icons.........................................................xxii
text and syntax...................................................xxii
cooling...........................................................................7
copper switch module See switch module critical system fault
media tray............................................................20
critical system fault LED
alarm panel module..............................................13
curly braces, in configuration statements..................xxiii
customer support......................................................xxxi
contacting...........................................................206
contacting JTAC..................................................xxxi
D
DC power
connecting............................................................63
consumption.......................................................192
disconnecting........................................................65
electrical specifications.......................................192
provisioning........................................................192
DC terminal cover
installing.............................................................115
removing............................................................115
replacing.............................................................115
declaration of conformity...........................................185
depth.............................................................................7
description
alarm panel module..............................................12
fan module...........................................................14
JCS 1200 components.............................................9
JCS 1200 modules...................................................9
management module............................................15
media tray............................................................18
MUX card..............................................................21
power module.......................................................22
Routing Engine.....................................................24
switch module......................................................27
diagnostic LEDs............................................................89
diagnostic tools............................................................85
documentation set
comments on.....................................................xxxi
E
earthquakes
site preparation for...............................................37
tested toleration for seismic activity....................187
EIA rack standards.......................................................36
electrical input...............................................................7
electrical specifications
AC power............................................................190
alarm panel interface connector.........................194
DC power............................................................192
electricity
safety warnings...................................................169
site wiring guidelines..........................................189
electromagnetic compatibility See EMC
pulse...................................................................189
electronic emission Class A notice.............................183
electrostatic
bag, using to store components..........................154
EMC (EMI)
EMP...........................................................................189
environmental specifications.................................7, 187
ESD
standards............................................................181
suppression........................................................189
preventing damage to components by................154
218 ■
Index
Index
Ethernet LEDs management module
Ethernet activity............................................18
Ethernet-link status........................................18
switch module
Gigabit Ethernet switch module error............29
link OK..........................................................29
Tx/Rx.............................................................29
Ethernet port, cabling .................................................69
ETSI rack standards.....................................................36
F
fan module
description............................................................14
error LED..............................................................15
installing.............................................................118
LED.......................................................................14
overview...............................................................14
problems..............................................................86
removing............................................................116
replacing.............................................................116
serial number, locating.......................................198
troubleshooting.....................................................86
fan pack
installing.............................................................121
removing............................................................120
replacing.............................................................120
fan shuttle
installing.............................................................123
removing............................................................122
replacing.............................................................121
FCC Class A notice.....................................................183
features and specifications.............................................7
fire safety specifications.............................................155
font conventions........................................................xxii
front view................................................................4, 10
FRU ready for removal LED
alarm panel module..............................................13
MUX card..............................................................21
G
Gigabit Ethernet switch module error LED...................29
guidelines
configuration........................................................81
installation............................................................95
system reliability...................................................95
H
hardware
overview.................................................................4
hardware components...................................................9
returning for repair or replacement....................195
hardware problems......................................................85
heat output....................................................................7
height.............................................................................7
humidity........................................................................7
humidity (relative), acceptable...................................187
I
immunity standards...................................................181
installation
completion............................................................79
guidelines.............................................................95
in a rack................................................................54
overview...............................................................49
parts received, verifying........................................41
power requirements...........................................189
preparing to install................................................39
requirements........................................................94
unpacking the JCS 1200 platform..........................40
instructions packing
platform for shipment.................................208
returning platform..............................................207
interference
electromagnetic..................................................189
radio frequency...................................................189
J
JCS 1200 hardware
overview.................................................................4
JCS 1200 machine type, locating................................196
JCS 1200 model number, locating..............................196
JCS 1200 platform
description..............................................................3
installation requirements......................................94
parts list................................................................41
unpacking.............................................................40
JCS 1200 power
disconnecting........................................................65
JCS 1200 serial number, locating...............................196
L
laser safety guidelines................................................160
LEDs
active (on management module)..........................18
activity (on Routing Engine)..................................26
alarm panel module..............................................12
alarm panel module fault...............................13
critical system fault........................................13
major system fault.........................................13
minor system fault.........................................13
blade-error (on Routing Engine)............................26
critical system fault
alarm panel module.......................................13
media tray.....................................................20
Index
■ 219
Juniper Control System (JCS) 1200 Platform Hardware Guide
Ethernet activity (on management module)..........18
Ethernet link OK (on switch module)....................29
Ethernet Tx/Rx......................................................29
Ethernet-link status (on management
module).............................................................18
fan module...........................................................14
fan module error...................................................15
FRU ready for removal
alarm panel module.......................................13
MUX card......................................................21
information (on Routing Engine)...........................26
location
alarm panel module.......................................13
media tray.....................................................20
major system fault
alarm panel module.......................................13
management module............................................17
management module error...................................18
mastership (on Routing Engine)............................26
media tray............................................................19
location..........................................................20
major system fault.........................................20
media tray fault.............................................20
power-on.......................................................20
minor system fault
alarm panel module.......................................13
media tray.....................................................20
MUX card..............................................................21
OK (on switch module).........................................29
power module.......................................................23
power-on
alarm panel module.......................................13
management module.....................................18
media tray.....................................................20
Routing Engine..............................................26
Routing Engine.....................................................26
activity...........................................................26
blade-error.....................................................26
information...................................................26
mastership.....................................................26
power-on.......................................................26
safety warnings...................................................160
switch module......................................................28
switch module error..............................................29
light path diagnostics
description............................................................85
features.................................................................89
LEDs.....................................................................90
light path extension assembly
installing.............................................................106
removing............................................................100
lithium battery compliance........................................183
location LED
alarm panel module..............................................13
media tray............................................................20
M
machine type, locating...............................................196
maintenance guidelines
warnings.............................................................164
major system fault LED
alarm panel module..............................................13
media tray............................................................20
management module connection
default settings..............................................70
Ethernet.........................................................71
serial..............................................................71
connectors............................................................16
default connection settings...................................70
description............................................................15
installing.............................................................125
LEDs.....................................................................17
overview...............................................................15
problems..............................................................87
removing............................................................124
replacing.............................................................124
reset button..........................................................17
serial cable pinouts.............................................211
serial number, locating.......................................199
troubleshooting.....................................................87
management module error LED...................................18
management module filler
installing.............................................................125
removing............................................................124
replacing.............................................................124
management module filler tray
installing.............................................................128
removing............................................................127
replacing.............................................................127
manuals
comments on.....................................................xxxi
media tray
description............................................................18
installing.............................................................129
LEDs.....................................................................19
overview...............................................................18
problems..............................................................88
removing............................................................128
replacing.............................................................128
serial number, locating.......................................200
troubleshooting.....................................................88
media tray fault LED....................................................20
media tray select button (on Routing Engine)...............26
midplane
replacing.............................................................130
serial number, locating.......................................201
minor system fault LED
alarm panel module..............................................13
media tray............................................................20
model number, locating.............................................196
220 ■
Index
Index module alarm panel See alarm panel module fan See fan module management See management module media tray See media tray
MUX card See MUX card power See power module switch See switch module modules
description..............................................................9
multiplexer card See MUX card
MUX card
description............................................................21
installing.............................................................131
LEDs.....................................................................21
overview...............................................................20
removing............................................................131
replacing.............................................................131
serial number, locating.......................................201
N
NEBS standards..........................................................181
network clock filler
installing.............................................................133
removing............................................................132
replacing.............................................................132
notice icons................................................................xxii
notices
electronic emission.............................................183
FCC, Class A........................................................183
O
OK LED (on switch module).........................................29
open-frame rack See rack overview
alarm panel module..............................................12
fan module...........................................................14
management module............................................15
media tray............................................................18
MUX card..............................................................20
power module.......................................................22
Routing Engine.....................................................24
switch module......................................................27
P
parentheses, in syntax descriptions...........................xxiii
PFA alerts.......................................................................7
pinouts
alarm panel interface connector.........................213
AMM adapter......................................................212
CPU adapter........................................................212
management module serial cable.......................211
RJ-45 adapters....................................................212
platform
description..............................................................3
power
AC, connecting......................................................62
connectors............................................................30
DC, connecting.....................................................63
disconnecting........................................................65
problems..............................................................89
requirements and specifications.........................189
surges.................................................................189
troubleshooting.....................................................89
power box
installing.............................................................136
removing............................................................134
replacing.............................................................134
power module
description............................................................22
installing.............................................................139
LEDs.....................................................................23
overview...............................................................22
removing............................................................138
replacing.............................................................138
serial number, locating.......................................202
power-on LED
alarm panel module..............................................13
management module............................................18
media tray............................................................20
powering off the Routing Engine..................................74
powering on the Routing Engine..................................73
prerequisites................................................................94
product data...............................................................xxii
provisioning
AC power............................................................190
DC power............................................................192
R
rack
clearance around, required...................................38
securing to building..............................................37
size and strength required....................................36
standards, EIA and ETSI........................................36
rack mounting
brackets................................................................43
front-mount flanges..............................................43
shelves..................................................................43
spacer bars...........................................................43
rack, installing toJCS 1200...........................................54
radio frequency interference, preventing...................189
rear view..................................................................5, 11
regulatory compliance................................................149
relative humidity, acceptable.....................................187
repair of platform or components..............................195
replacing components..................................................93
reset button
management module............................................17
Index
■ 221
Juniper Control System (JCS) 1200 Platform Hardware Guide
RFI.............................................................................189
Routing Engine
connecting to console...........................................72
control panel.........................................................25
description............................................................24
installing.............................................................141
LEDs.....................................................................26
overview...............................................................24
pinouts for cable connections.............................211
powering off.........................................................74
powering on..........................................................73
removing............................................................140
replacing.............................................................140
serial number, locating.......................................203
starting.................................................................73
stopping................................................................74
Routing Engine filler...................................................142
S
safety information......................................................149
See also warnings
safety standards.........................................................181
security features.............................................................7
seismic activity (earthquake), designated level...........187
serial connector
alarm panel module..............................................13
management module............................................16
serial number
alarm panel module............................................197
chassis................................................................196
fan module.........................................................198
management module..........................................199
media tray..........................................................200
midplane............................................................201
MUX card............................................................201
power module.....................................................202
Routing Engine...................................................203
switch module....................................................205
shipping container
unpacking.............................................................40
weight...................................................................40
shipping crate
repacking............................................................208
signaling, distance limitations....................................189
site
electrical wiring specifications............................189
environmental specifications..............................187
preparation
checklist........................................................33
size................................................................................7
specifications
clearance around rack...........................................38
electrical
cable and wiring..........................................189
environmental....................................................187
fire safety............................................................155
rack
connection to building structure....................37
size and strength...........................................36
thermal output....................................................187
specifications and features.............................................7
standards compliance................................................181
starting the Routing Engine..........................................73
stopping the Routing Engine........................................74
support, technical See technical support
surge protection.........................................................189
switch module
connectors............................................................27
description............................................................27
installing.............................................................144
LEDs...............................................................28, 29
overview...............................................................27
preinstallation requirements.................................94
removing............................................................143
replacing.............................................................143
serial number, locating.......................................205
switch module filler tray
installing.............................................................146
replacing.............................................................145
switch module interposer
removing............................................................145
syntax conventions....................................................xxii
system
description..............................................................3
features...................................................................7
reliability guidelines..............................................95
specifications..........................................................7
T
T-CBs, connecting........................................................75
T-series routing platform
connecting............................................................75
powering on..........................................................78
replacing CBs........................................................75
technical support
contacting JTAC..................................................xxxi
Telco alarm connector
description............................................................13
location.................................................................12
telco rack See rack
temperature, acceptable range...................................187
thermal output...........................................................187
tolerances..................................................................187
tools required chassis
returning for repair or replacement.............208
hardware components
returning for repair or replacement.............208
222 ■
Index
trays cable management See cable management trays media See media tray
troubleshooting............................................................85
charts....................................................................86
fan module...........................................................86
management module............................................87
media tray............................................................88
power...................................................................89
U
U (rack unit).................................................................36
United States electronic emission Class A notice........183
United States FCC Class A notice................................183
unpacking the JCS 1200 platform.................................40
USB device, problems..................................................88
W
warnings
electrical.............................................................169
general................................................................151
installation..........................................................155
laser and LED.....................................................160
levels defined......................................................149
maintenance and operational.............................164
weight............................................................................7
width.............................................................................7
wiring, electrical See electricity
Index
Index
■ 223
Juniper Control System (JCS) 1200 Platform Hardware Guide
224 ■
Index
Unduh
Iklan