CommScope NG4access ODF Platform Value-Added Module Installation Manual
The CommScope NG4access ODF Platform Value-Added Module offers a host of features to enhance your fiber management capabilities. It provides a flexible and scalable platform for deploying and managing fiber optic networks, enabling efficient and reliable distribution of fiber optic signals. With its modular design, you can easily add or remove components to meet your changing needs, ensuring a future-proof solution for your network infrastructure.
Hirdetés
Hirdetés
NG4access
®
Frame
Installation Manual (Raised Floor)
TECP-90-708
Issue 5, April 2017
300001764826 Rev B www.commscope.com
249 8 7-A
TECP-90-708 • Issue 5 • April 2017 • Preface
COPYRIGHT
© 2016, CommScope Inc.
All Rights Reserved
REVISION HISTORY
ISSUE
1
2
3
4
5
DATE REASON FOR CHANGE
9/2012
12/2012
7/2013
Original.
Added instructions for installing Raised Floor Cable Clamp Bracket Kit.
Added instructions for installing the Fiber Optic Storage Panel (FOTSP) and the Auxiliary Cable Spool
Bracket Kit.
July 2016 Reformatted for CommScope.
April 2017 Corrected Material ID on cover.
TRADEMARK INFORMATION
CommScope and CommScope (logo), and NG4access are trademarks.
Telcordia is a registered trademark of Telcordia Technologies, Inc.
GORE is a registered trademark of W. L. Gore & Associates, Inc.
DISCLAIMER OF LIABILITY
Contents herein are current as of the date of publication. CommScope reserves the right to change the contents without prior notice.
In no event shall CommScope be liable for any damages resulting from loss of data, loss of use, or loss of profits and
CommScope further disclaims any and all liability for indirect, incidental, special, consequential or other similar damages.
This disclaimer of liability applies to all products, publications and services during and after the warranty period.
This publication may be verified at any time by contacting CommScope’s Technical Assistance Center at: http://www.commscope.com/SupportCenter
Page ii
TECP-90-708 • Issue 5 • April 2017 • Preface
TABLE OF CONTENTS
Content Page
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Related Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v
Admonishments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
General Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
List of Acronyms and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
1 TOOLS AND MATERIALS REQUIRED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 FOOTPRINT OF FRAME AND FIBER OPTIC STORAGE PANEL (FOTSP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 MOUNTING THE FRAME ON A RAISED FLOOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 INSTALLING A FIBER OPTIC STORAGE PANEL (FOTSP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5 INSTALLING A RAISED FLOOR CABLE BRACKET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6 INSTALLING A SPOOL BRACKET ASSEMBLY (FOR FRAME WITH SPLICE CHASSIS). . . . . . . . . . . . . . . . . . . . . . . . . . 44
7 INSTALLING AUXILIARY CABLE SPOOLS (FOR FRAMES WITHOUT SPLICE CHASSIS) . . . . . . . . . . . . . . . . . . . . . . . . 46
8 GROUNDING THE FRAME . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
9 SECURING TWO FRAMES TOGETHER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10 CUSTOMER INFORMATION AND ASSISTANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Page iii
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017 • Preface
TABLE OF CONTENTS
Content
Blank
Page
Page iv
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017 • Preface
ABOUT THIS MANUAL
This manual provides complete instructions for installing a NG4access frame on a raised floor.
Included are instructions for grounding the frame and joining two frames in a lineup.
RELATED PUBLICATIONS
Listed below are related manuals and their publication numbers. Copies of these publications can be ordered by contacting the CommScope Technical Assistance Center at: http://www.commscope.com/SupportCenter
Title/Description Publication Number
NG4access ODF Platform Application and Planning Manual
Contains an NG4access overview and information for planning a NG4access application.
90-701
90-702 NG4access Frame Installation Manual: Concrete Floor
Provides pictorial instructions for installing an NG4access frame on a concrete floor and grounding the frame.
NG4access ODF Platform Standard Chassis Installation Manual
Provides installation instructions for the NG4access standard chassis.
NG4access ODF Platform Splice Chassis and Splice Tray
Installation Manual
Provides installation instructions for the NG4access standard chassis.
NG4access ODF Platform Patch Cord Routing Guide
Provides pictorial guidelines for routing patch cords on a lineup consisting of one or more NG4access frames. This manual consists of laminated cards that hang on the front of the frame.
NG4access ODF Platform Rear Side Routing Guide
Provides pictorial guidelines for routing cables and installing cabled modules on the rear side of a lineup consisting of one or more NG4access frames. This manual consists of laminated cards that hang on the rear of the frame.
90-703
90-704
90-705
90-706
Page v
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017 • Preface
ADMONISHMENTS
Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment. An admonishment identifies a possible hazard and then explains what may happen if the hazard is not avoided. The admonishments — in the form of Dangers,
Warnings, and Cautions — must be followed at all times. These warnings are flagged by use of the triangular alert icon (seen below), and are listed in descending order of severity of injury or damage and likelihood of occurrence.
Danger: Danger is used to indicate the presence of a hazard that will cause severe personal injury, death, or substantial property damage if the hazard is not avoided.
Warning: Warning is used to indicate the presence of a hazard that can cause severe personal injury, death, or substantial property damage if the hazard is not avoided.
Caution: Caution is used to indicate the presence of a hazard that will or can cause minor personal injury or property damage if the hazard is not avoided.
GENERAL SAFETY PRECAUTIONS
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter packs. Exposure to invisible laser radiation may result. An optical power meter should be used to verify active fibers. A protective cap or hood MUST be immediately placed over any radiating adapter or optical fiber connector to avoid the potential of dangerous amounts of radiation exposure. This practice also prevents dirt particles from entering the adapter or
connector.
LIST OF ACRONYMS AND ABBREVIATIONS
The following acronyms are used in this manual:
FOT Fiber Optic Terminal
IFC Intra Facility Cable
OSP Outside Plant
Page vi
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
1 TOOLS AND MATERIALS REQUIRED
The tools and materials required for mounting the NG4access frame on a raised floor are specified in Table 1 and Table 2 .
Table 1. Tools Required
TOOL
Adjustable wrenches (2)
0.25 to 1 inch (8 to 25.4 mm)
PICTURE
12494-B
Crow bar
12495-B
Drill with metal and concrete drill bits
12496-B
Ruler or tape measure
12825-a
31
1 cm
File
12497-B
Torque wrench
Note: Capable of 60 ft.-lbs. (81 Nm)
Allen wrench (5/16-inch)
Note: Used for leveling frame
17721-A
18406-A
Page 1
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
TOOL
Hacksaw
Table 1. Tools Required, continued
Hammer
Jigsaw: with blades for cutting floor tile and metal
Level
PICTURE
12501-B
12499-B
12500-B
12502-B
12506-B
Set of combination open end/box wrenches
0.25 to 1 inch (8 to 25.4 mm)
Set of sockets
0.25 to 1 inch (8 to 25.4 mm)
Crimping tool
0.25 to 0.3 inches (6.35 to 7.62 mm)
Note: Used for grounding frame
12504-B
12824-A
Page 2
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Table 1. Tools Required, continued
PICTURE TOOL
Flat tip and Phillip screwdrivers
(#1, #2, and #3)
12503-B
Vacuum
12505-B
ITEM
Table 2. Ground Wire Kit Components (Accessory)
Ground cable (13 ft.)
Nylon cable clamps (8)
DESCRIPTION/PICTURE
#6 AWG (4.1 mm) solid copper wire
18413-A
12-24 x 0.5 inch screws
18414-A
2-hole copper compression lug (1) with
0.75-inch hole spacing.
Note: Accommodates #6 AWG wire
12498-B
Page 3
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Table 3. Other Components Used
PICTURE ITEM
Hold-down washer (4)
(provided with frame)
Concrete floor frame installation kit
(four anchor bolts)
STUD
TORQUE LIMITING HEX NUT
FLAT WASHER
METAL SLEEVE
21 8 99-A
NOTE: ONE PIECE TOP FLANGE
(SHEARS OFF)
TORQUE NUT
PLASTIC COVER
NYLON SPACER
18008-B
EXPANDABLE CONE
Zone 2/Zone 4 Raised Floor
Mounting Kit
Raised Floor Cable Clamp
Bracket Kit (separately ordered)
Large Cable Clamp Kit
(separately ordered)
Refer to Table 4
This kit is required if cables will be routed into the frame from under the floor. For more information, refer to Section 5 on Page 35
This kit is required, in addition to the Raised Floor Cable Clamp Bracket
Kit if large cables will be routed into the frame from under the floor.
Large cables are defined as having an Outside Diameter (OD) of 0.8 in.
(2.03 cm) up to 1.03 in. (2.61 cm). For more information, refer to
Section 5 on Page 35
Page 4
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
ITEM
Edge protector (1) 72 in.
Table 4. Raised Floor Mounting Kit Components
PICTURE ITEM
Threaded rod (4) 5/8”-11 x 30” long
PICTURE
Unistrut
10 ft. long
Plastic shoulder washer
(4)
(Note: Not used)
Wood screw (16) Unistrut nut with spring (4)
Hex nut heavy (12)
5/8” x 11
Split lock washer (12)
5/8”
Flat washer (12) 5/8”
Hold down plate (2)
Note: Not used
Page 5
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
2 FOOTPRINT OF FRAME AND FIBER OPTIC STORAGE PANEL (FOTSP)
Figure 1 shows the frame footprint. Figure 2 shows the FOTSP footprint. The FOTSP is installed adjacent to the frame on the left side of the frame looking from the front.
29.84 IN. (75.79 CM)
27/8 IN.
(7.
3 0 CM)
2227/ 3 2 IN.
(58.02 CM)
2 3 .89 IN.
(60.68 CM)
1 3 IN.
( 33 .02 CM) 95/8 IN.
(2 3 .45 CM)
71 3 /16 IN .
(19.84 CM)
FRONT
85/16 IN.
(21.11 CM)
251/2 IN. (64.77 CM)
Figure 1. Frame Footprint (Optional Template Shown)
25162-A
1.0 IN. (2.54 CM) DIAMETER
(4) PLACE S
11.88 IN. ( 3 0.17 CM)
3 .75 IN. (9.52 CM) 4.0 IN. (10.16 CM)
18.98 IN.
(48.21 CM)
10.90 IN.
(27.69 CM)
2 3 .98 IN.
(60.91 CM)
RADIU S 1.0 IN.
(2.54 CM)
2.5 IN.
(6.
3 5 CM)
FRONT
6.88 IN. (17.47 CM)
S LOT 1.75 X 1.0 IN.
(4.44 X 2.54 CM)
2524 3 -A
Figure 2. FOTSP Footprint
Page 6
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
3 MOUNTING THE FRAME ON A RAISED FLOOR
To mount the frame on a raised floor, use the following procedure.
1. Unpack the frame.
2. Set out the frame and optional template/isolation pad as shown in Figure 3 .
Note: Storage spools may loosen during shipment. Check storage spools for looseness.
Tighten spool cover screws if spools are loose.
!
NOTE: TEMPLATE/I S OLATION PAD
NOT REQUIRED FOR IN S TALLATION
CAUTION: U S E APPROPRIATE
EQUIPMENT TO LIFT RACK
OPTIONAL
TEMPLATE/I S OLATION PAD
(ORDERED S EPARATELY)
25045-A
Figure 3. Setting Out Frame and Optional Template/Isolation Pad
Page 7
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
3. Determine the frame location taking note of the clearance requirements shown in Figure 4 .
Place the optional template/isolation pad on the floor tiles and mark the tile as shown. If installing without a template, refer to Section 2 on Page 6 for installation dimensions.
Note: If optional FOTSP is present, see Figure 5 .
FRONT AI S LE
(4-FEET
RECOMMENDED
MINIMUM)
REAR AI S LE
( 3 -FEET
RECOMMENDED
MINIMUM)
25046-B
PENCIL
Page 8
© 2017, CommScope, Inc.
MARK THE S E
LOCATION S
ALIGN FRONT OF
TEMPLATE/I S OLATION PAD
WITH EDGE OF TILE
25271-A
Figure 4. Determining Frame Location
TECP-90-708 • Issue 5 • April 2017
4. If FOTSP will be installed, also mark out and cut out a hole for the FOTSP to the left of the frame template. Figure 5 shows an example.
Note: The optional FOTSP is only shown in this illustration in the frame installation procedure. For the separate FOTSP installation procedure, refer to Section 4 on Page 30 .
EXAMPLE ONLY (OTHER ARRANGEMENT S ARE PO SS IBLE)
FOT S P FOOTPRINT
FRONT
FOT S P
LOCATION
PENCIL
FRAME FOOTPRINT
2526 8 -A
MARK CUTOUT
FOR FOT S P
IF FLOOR ENTRY
WILL BE U S ED
ALIGN FRONT OF
TEMPLATE/I S OLATION PAD
WITH EDGE OF TILE
MARK HOLE S
AND CUTOUT
ON TEMPLATE
25270-A
Figure 5. FOTSP and Frame Footprints on Floor Tiles
Page 9
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
5. Remove and cut the tiles, file all edges, and set the floor tiles on the pedestals, as shown in
Figure 6 .
CUT
TILE S
DRILL
PILOT HOLE S
VACUUM
A S REQUIRED
FILE
ALL EDGE S
S ET FLOOR TILE S
ON PEDE S TAL S
Page 10
© 2017, CommScope, Inc.
Figure 6. Setting Floor Tiles on Pedestal
2504 8 -A
TECP-90-708 • Issue 5 • April 2017
6. Cut threaded rod to floor height +1-5/8in. (+/- 3/8 in.) (four places). Refer to Figure 7 .
1-5/8 IN.
(+/- 3 /8 IN.)
NOTE: MEA S URE FROM CONCRETE
TO 1-5/8 IN. (+/- 3 /8 IN.) ABOVE FLOOR TILE
THREADED
ROD
FILE
END S
PAINT END S
(OPTIONAL)
Figure 7. Cutting Threaded Rod
25049-A
Page 11
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
7. Cut the unistrut to the required length, as shown in Figure 8 .
TOP VIEW
22.1 IN.
( 3 8.4 CM)
21.4 IN.
( 3 6.6 CM)
CUT TO REQUIRED LENGTH
29.8 IN.
(75.8 CM)
TOP-RIGHT UNI S TRUT S HORTENED
TO ALLOW FOR TOP OF PEDE S TAL CUT TO REQUIRED
LENGTH
( S EE TOP VIEW)
CUT
FILE EDGE S
NOTE: LOWER UNI S TRUT CUT LENGTH
I S S HOWN FOR ONE FRAME IN S TALLATON.
25050-A
Figure 8. Cutting Unistrut
Page 12
© 2017, CommScope, Inc.
PAINT
S
IVE
PAINT FILED EDGE S
(OPTIONAL)
TECP-90-708 • Issue 5 • April 2017
8. Assemble the washer and hex nut onto the threaded rod and insert the threaded rod in the floor tile. Plumb the threaded rods from front to back and mark concrete. Repeat these steps using the same threaded rod for the three remaining slots. Refer to Figure 9 .
PLUMB THREADED
ROD FROM FRONT
TO BACK
HEX NUT
WA S HER
CENTER
THREADED
ROD IN S LOT
MARK CENTER
MAKE S URE THREADED ROD
DOE S NOT TOUCH CONCRETE
S IDE VIEW
REPEAT S TEP S U S ING S AME THREADED ROD
FOR REMAINING THREE S LOT S
Figure 9. Marking Concrete With Threaded Rod
25051 -A
Page 13
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
9. Remove the threaded rod assembly and set the floor tiles aside. Use a ruler or straight edge to draw lines on the concrete. Refer to Figure 10 .
THREADED ROD
A SS EMBLY
S ET FLOOR
TILE S A S IDE
DRAW LINE S
ON CONCRETE
RULER OR
S TRAIGHT EDGE
Figure 10. Marking Concrete
25052-A
Page 14
© 2017, CommScope, Inc.
10. Center unistruts over lines on concrete. Refer to Figure 11 .
TECP-90-708 • Issue 5 • April 2017
CENTER UNI S TRUT
ON LINE
TOP VIEW
Figure 11. Centering Unistruts on Lines
2505 3 -A
Page 15
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
11. Set the floor tiles on the pedestals. Install a spring nut in each unistrut. Assemble the 5/8inch hex nut, 5/8-inch lock washer, and 5/8-inch washer onto the threaded rod (12A).
Install the threaded rod assembly (12B) into the spring nut. Refer to Figure 12 .
S PRING NUT IN S TALLED,
S IDE VIEW
S LIDE S PRING NUT
INTO END OF UNI S TRUT
THREADED ROD
5/8-INCH HEX NUT
5/8-INCH WA S HER
5/8-INCH LOCK WA S HER
S PRING NUT
THREADED
ROD A SS EMBLY
UNI S TRUT
S PRING NUT
IN S TALLED
12A: A SS EMBLE 5/8-INCH HEX NUT, 5/8-INCH LOCK WA S HER,
AND 5/8-INCH WA S HER ONTO THREADED ROD
LEAVE S PACE BETWEEN BOTTOM
OF THREADED ROD AND TOP, IN S IDE
S URFACE OF UNI S TRUT
12B: IN S TALL THREADED ROD A SS EMBLY
INTO S PRING NUT
25054-A
Figure 12. Setting Floor Tiles on Pedestals
Page 16
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
12. Plumb the threaded rod assembly and mark anchor plate location on concrete. Install three remaining threaded rod assemblies in the same manner. See Figure 13 .
PLUMB THREADED ROD
FROM S IDE TO S IDE
IN S TALL REMAINING
THREADED ROD
A SS EMBLIE S
ANCHOR PLATE
X
UNI S TRUT
X
THREADED ROD A SS EMBLY
AND S PRING NUT
X
MARK CONCRETE
(FOUR PLACE S )
X
TOP VIEW
Figure 13. Installing Threaded Rod Assemblies
25055-A
Page 17
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
13. Set the floor tiles and unistrut assemblies aside and drill holes at the anchor bolt locations.
Refer to Figure 14 .
VACUUM A S
REQUIRED
HOLE DIMEN S ION S :
DIAMETER: 0.71-IN. (18MM)
DEPTH: 3 -15/16-IN. (100MM)
DRILL HOLE S (4)
Page 18
© 2017, CommScope, Inc.
Figure 14. Drilling Holes
25056-A
TECP-90-708 • Issue 5 • April 2017
14. Thread the washer and torque nut onto the threaded rod of the anchor bolt. The washer should touch the top of the anchor sleeve. Insert the anchor bolt assembly into the hole just drilled. Using a hammer, tap the anchor bolt assembly into the hole until the washer touches the concrete. Refer to Figure 15 .
IN S ERT ANCHOR BOLT
A SS EMBLY INTO HOLE
TORQUE NUT
WA S HER
THREADED ROD
ANCHOR S LEEVE
ANCHOR BOLT A SS EMBLY
25057-A
Figure 15. Setting Anchor Bolts
Page 19
TECP-90-708 • Issue 5 • April 2017
15. Pre-torque the anchor bolts approximately 30 ft-lbs (41 Newton meters) (16A). Loosen the torque nut several turns (16B). Then remove the torque nut and washer (16C). Refer to
Figure 16 .
TORQUE WRENCH
2505 8 -A-A
LOO S EN
TORQUE NUT
TORQUE NUT
WA S HER
THREADED ROD
16A: PRE-TORQUE ANCHOR BOLT
TO APPROXIMATELY 3 0 FT-LB S
(41N-m)
16-B: LOO S EN TORQUE NUT
Figure 16. Pre-torquing Anchor Bolts
16-C: REMOVE TORQUE NUT
AND WA S HER
Page 20
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
16. Position the unistrut assemblies over the anchor bolt threaded rods. Assemble the anchor plate, flat washer, and torque nut onto the threaded rod (17A). Tighten torque nut until top flange shears off (four places) (17B). The torque nut will be correctly set at 60 ft-lbs (81
Newton meters) (17C). Refer to Figure 17 .
UNI S TRUT A SS EMBLY CON S I S T S OF A
UNI S TRUT AND THREADED ROD A SS EMBLY (2)
ANCHOR BOLT THREADED ROD (4)
TORQUE NUT
FLAT WA S HER
ANCHOR PLATE
TOP FLANGE
TORQUE NUT
70
6 8
66
64
62
60
0
FT-LB
25059-A
TORQUE WRENCH
THREADED
ROD
17A: A SS EMBLE ANCHOR PLATE,
FLAT WA S HER, AND TORQUE NUT
ONTO THREADED ROD
17B: TIGHTEN TORQUE NUT
UNTIL TOP FLANGE S HEAR S OFF
17C: THE TORQUE NUT WILL BE
CORRECTLY S ET AT 60 FT-LB S (81N-m)
Figure 17. Positioning Unistrut Assemblies
Page 21
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
17. Assemble hex nuts, split lock washers, flat washers, unistruts, and floor tiles onto threaded rods. Refer to Figure 18 .
UNI S TRUT
25060-A
S PLIT LOCK
WA S HER 5/8-INCH
HEX NUT 5/8-INCH
FLOOR TILE
UNI S TRUT
S PACE
FLAT WA S HER 5/8-11-INCH
S IDE VIEW
NOTE: ALLOW S PACE BETWEEN
UNI S RUT AND FLOOR TILE TO MAKE S URE
FLOOR TILE I S NOT RAI S ED OFF PEDE S TAL S .
Figure 18. Placing Floor Tiles on Threaded Rods
Page 22
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
18. Cut out edge protectors to the required length for the slots in the floor tile. Secure the edge protectors to the floor tiles using self-drilling screws (provided). Refer to Figure 19 .
CUT TO REQUIRED
LENGTH
DRILL PILOT HOLE S
S ELF-DRILLING
S CREW S (PROVIDED)
NOTE: EDGE PROTECTOR MAY
BE CUT TO FIT AROUND PEDE S TAL
NOTE: IN S TALL EDGE PROTECTOR ON ALL S IDE S
OF CABLE ENTRANCE S (RECOMMENDED)
Figure 19. Installing Edge Protectors
25061-A
Page 23
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
19. Plumb threaded rod assemblies (4) and tighten hex nuts (4). Refer to Figure 20 .
TIGHTEN
HEX NUT S (4)
PLUMB THREADED
ROD A SS EMBLIE S
FROM S IDE TO S IDE
Figure 20. Plumbing Threaded Rods
25062-A
Page 24
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
20. Hand tighten the hex nuts to raise unistruts to floor tile. Refer to Figure 21 .
2506 3 -A
HAND TIGHTEN
HEX NUT S TO
RAI S E UNI S TRUT S
TO FLOOR TILE
FLOOR TILE
UNI S TRUT
( S HADED FOR CLARITY)
!
MAKE S URE FLOOR TILE S ARE
NOT RAI S ED OFF PEDE S TAL S
Figure 21. Raising Unistruts to Floor Tile
Page 25
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
21. Remove the frame front and rear troughs to access mounting slots. Refer to Figure 22 .
(Caution: Do not attempt to lift or move the frame without appropriate equipment.)
FRONT
VIEW
LOWER
TROUGH
BACK
24995-A
LOWER
TROUGH
BASE
MOUNTING SLOTS
(PARTIALLY SHOWN)
GUARD BOX
COVER
REAR VIEW
MOUNTING S LOT S
(PARTIALLY S HOWN)
25065-A
Page 26
© 2017, CommScope, Inc.
REAR COVER
Figure 22. Removing Troughs
TECP-90-708 • Issue 5 • April 2017
22. Position the frame on the optional template/isolation pad and floor tile. Install hardware
(four places). Do not fully tighten (23A). Use 5/16-inch allen wrench and adjust set screws
(4) to level rack. Refer to Figure 23 .
S ET S CREW
(FOUR PLACE S )
S EE 2 3 B, BELOW
ALIGN S LOT S IN RACK AND
TEMPLATE/I S OLATION PAD
WITH THREADED ROD S
OPTIONAL
TEMPLATE/I S OLATION PAD
( S HADED FOR CLARITY)
HEX NUT
5/8-11-INCH
S PLIT LOCK
WA S HER 5/8-INCH
HOLDDOWN WA S HER
(PROVIDED WITH RACK)
THREADED ROD
2 3 A: IN S TALL HOLDDOWN WA S HER,
S PLIT WA S HER 5/8-INCH AND HEX NUT 5/8-11 INCH
(DO NOT FULLY TIGHTEN)
2 3 B: U S E 5/16-INCH ALLEN WRENCH
AND ADJU S T S ET S CREW TO
LEVEL RACK
25066-A
Figure 23. Positioning Frame on Optional Template/Isolation Pad and Floor Tile
Page 27
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
23. Use wrench to tighten hex nuts under floor tile. Do not fully tighten. Refer to Figure 24 .
TIGHTEN HEX NUT S UNTIL
S PLIT LOCK WA S HER I S FLATTENED
S IDE VIEW
DO NOT FULLY TIGHTEN
OR RAI S E FLOOR TILE S
!
NOTE: MAKE S URE RACK REMAIN S LEVEL
Figure 24. Tightening Hex Nuts 1
Page 28
© 2017, CommScope, Inc.
25067-A
TECP-90-708 • Issue 5 • April 2017
24. Use wrench (5/8-inch) to tighten hex nuts above floor tile (four places). Then fully tighten hex nuts under floor tile. Refer to Figure 25 .
!
NOTE: MAKE S URE RACK REMAIN S LEVEL
TIGHTEN HEX NUT S (4)
ABOVE FLOOR TILE
2506 8 -A
Figure 25. Tightening Hex Nuts 2
25. If cables will be routed into the frame from under the floor:
TIGHTEN HEX NUT S (4)
UNDER FLOOR TILE
Page 29
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017 a. Install the Raised Floor Cable Clamp Bracket Kit (separately ordered). For instructions on how to install the kit, refer to Section 5 on Page 35 . b. If the cables from under the floor will be routed into a splice chassis, install a spool bracket assembly. For instructions, refer to Section on Page 46 .
26. Re-install front and rear trough as shown in Figure 26 .
27. Ground the frame. Refer to Section 9 on Page 49 .
REAR
GUARD BOX
FRONT
VIEW
LOWER
TROUGH
BACK
LOWER
TROUGH
BA S E
GUARD BOX
COVER
25069-A
Figure 26. Re-installing Troughs
4 INSTALLING A FIBER OPTIC STORAGE PANEL (FOTSP)
A Fiber Optic Storage Panel (FOTSP), installed onto the left side of the NG4access frame as looking from the front, provides storage space on the rear for Fiber Optic Terminal Equipment patch cords. The FOTSP is 12 inches wide. For a view of the frame and FOTSP footprints, refer to Section 2 on Page 6 . Use the following procedure to install a FOTSP.
1. If the front trough covers, front guard box, and the rear guard box, are present on the frame, remove them. Figure 26 above shows the same components, but being installed.
2. If cables will enter the FOTSP from under the floor, saw out a cable entry hole, referring to
Figure 2 on Page 6 for hole location and dimensions.
3. Unpack the FOTSP and set it up next to the frame, with the cross-frame troughs on the rear side corresponding to the location of the cross-frame troughs on the frame.
Page 30
© 2017, CommScope, Inc.
4. Remove the FOTSP front cover, referring to Figure 27 .
TECP-90-708 • Issue 5 • April 2017
FOT S P
FRONT
COVER
2525 8 -A
Figure 27. Removing FOTSP Front Cover
5. Remove the FOTSP back cover and cover plate ( Figure 28 ).
FOT S P
COVER
PLATE
FOT S P
BACK
COVER
25260-A
Figure 28. Removing FOTSP Back Cover and Cover Plate
Page 31
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
6. Secure the FOTSP to the NG4access frame by installing tie brackets in two places and trough ties in six places as shown in Figure 29 .
Note: Refer also to the detailed views in Figure 30 and Figure 31 .
TIE BRACKET
(2 PLACE S )
TROUGH
TIE
(6 PLACE S )
Page 32
© 2017, CommScope, Inc.
HOLE
COVER
EDGE
PROTECTOR
Figure 29. Installing Brackets
25257-A
TECP-90-708 • Issue 5 • April 2017
TOP CRO SS -FRAME TROUGH
TOP TIE
BRACKET
PLACE ONE
TROUGH TIE
ON BOTTOM
S IDE OF
EACH
JUNCTION
OF TROUGH S
3 RD-DOWN CRO SS -FRAME TROUGH
Figure 30. Rear View of Bracket Locations
MID-FRAME
TIE BRACKET
REAR VIEW
25262-A
MID-FRAME TIE BRACKET
3 RD DOWN CRO SS -FRAME TROUGH
REAR VIEW
2526 3 -A
Figure 31. Rear View With Frame Tilted to Show Brackets Under Trough
Page 33
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
7. To secure the bases of the frame and FOTSP together, install two hex bolts on the rear of the frame as shown in Figure 32 , then, as noted, install two hex bolts in the analogous location on the front of the frame.
EDGE
PROTECTOR
Page 34
© 2017, CommScope, Inc.
1/4-20 HEX BOLT S (2)
1/4 FLAT WA S HER (2)
1/4 LOCK WA S HER (2)
1/4-20 HEX NUT (2)
REAR VIEW
(REAR TROUGH NOT
NOTE: IN S TALL S AME HARDWARE
IN ANALOGOU S LOCATION
ON FRONT OF FRAME AND FOT S P
S HOWN FOR CLARITY)
Figure 32. Bolting Together Frame and FOTSP Bases
25261-A
TECP-90-708 • Issue 5 • April 2017
8. Install the edge protector on the FOTSP in the location shown in Figure 32 .
9. Install the hole cover in the location shown in Figure 29 on Page 32 .
10. Re-install the front and rear troughs, as shown in Figure 26 on Page 30 .
11. Re-install FOTSP front and rear guard boxes (reverse of steps 3 and 4, and reverse of what is shown in Figure 27 on Page 31 and Figure 28 on Page 31 ).
5 INSTALLING A RAISED FLOOR CABLE BRACKET
If cables will be brought into the frame from under the raised floor, a Raised Floor Standard
Cable Clamp Bracket (available from CommScope) must be installed on the rear side of the frame in the bottom right corner.
The kit is designed for standard size cables, with an Outside Diameter (OD) of up to 0.8 in.
(2.03 mm). If large cables are to be installed, with an OD in the range from 0.8 to 1.03 in. (2.03
to 26.16 mm), a large cable kit (NG4-ACCRFCLMP3) is also required.
This procedure covers both standard and large cables, and assumes that the installer has the kit or kits required.
Use the following procedure to install a raised floor cable clamp bracket.
1. Determine whether the cables to be installed are standard or large as defined above. Set out the bracket plate (largest piece in the kit) and identify the hole pattern to be used for mounting cables, referring to Figure 33 on Page 36 . There are separate hole patterns for
large and standard cables.
Page 35
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Page 36
© 2017, CommScope, Inc.
Figure 33. Grommet Placement on Bracket
TECP-90-708 • Issue 5 • April 2017
2. Install 8-32 x 5/16 inch pan head screws as shown in Figure 33 , Figure 34 , and Figure 35 .
Leave enough space between the screw heads and bracket for the cable clamps to be hung on the screws in a later step.
NOTE: DO NOT DRIVE THE S CREW
HEAD S TIGHT AGAIN S T THE
BRACKET. ALLOW S UFFICIENT S PACE
BETWEEN THE S CREW HEAD S AND
BRACKET FOR THE CABLE CLAMP S
TO BE HUNG ON THE S CREW S .
25127-A
183 2 x 5/16 IN.
PANHEAD S CREW
(24 PLACE S ,
EACH S IDE; 48 TOTAL)
Figure 34. Standard Cable Screw Placement
NOTE: DO NOT DRIVE THE S CREW
HEAD S TIGHT AGAIN S T THE
BRACKET. ALLOW S UFFICIENT S PACE
BETWEEN THE S CREW HEAD S AND
BRACKET FOR THE CABLE CLAMP S
TO BE HUNG ON THE S CREW S .
183 2 x 5/16 IN.
PANHEAD S CREW
(12 PLACE S , EACH S IDE;
24 TOTAL)
2512 8 -A
Figure 35. Large Cable Screw Placement
Page 37
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
3. If the frame has a splice chassis: a. Remove the splice chassis cover (if present) from the bottom rear of the NG4access frame, as shown in Figure 36 . To do this, remove the two #8 pan head screws and two star washers securing the cover to the frame. Set aside these items for re-installing the cover later.
REAR VIEW
OF FRAME
251 3 7-A
Figure 36. Removing Front Plate from Frame b. Fully slide out the splice chassis (if present), as shown in Figure 37 .
Page 38
© 2017, CommScope, Inc.
REAR VIEW
OF FRAME
Figure 37. Sliding Out the Splice Chassis
2516 8 -A
TECP-90-708 • Issue 5 • April 2017
4. If the frame does not have a splice chassis, remove the cover shown in Figure 38 .
REAR VIEW
OF FRAME 25161-A
Figure 38. Removing Rear Cover on a Non-Splice Frame
5. Place the cable bracket into the cable entry hole, and position the holes in the bracket on the threaded studs, as shown in Figure 39 . Install a #10 washer and #10 nut on each threaded stud. Tighten to 16 inch lbs. (1.8 Newton meters).
Note: This illustration shows a frame without a splice chassis.
Page 39
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
25171-A
PO S ITION BRACKET ON
THREADED S TUD.
IN S TALL #10 WA S HER
AND #10 NUT
(TWO PLACE S ).
TIGHTEN TO 16 INCH-LB S .
(1.8 NEWTON METER S )
Figure 39. Installing Bracket in Frame
6. Route the cables to be installed through the entry hole, taking care to position each cable on the correct side of the raised floor cable breakout per the cable clamp locations shown in Figure 33 on Page 36 .
Note: The Row locations shown in this same figure ( Figure 33 on Page 36 ) will also be used to figure out the DIM ‘A” values when breaking out the cables in the next step.
7. Prepare each cable as follows, referring to Figure 40 : a. Pull the cable up through the hole.
b. If the cable being installed is an NG4access cable terminated with one or more cabled module(s), obtain the appropriate DIM ‘A’ length from Table 5 based on where the cable clamp will be installed on the bracket, measure out this length from the factory breakout on the cable, and mark the cable at this location as shown in Figure 40 . This is where the cable clamp should be placed on the cable.
Page 40
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Note: There is no need for further breakout as all NG4access cables with cabled modules are of one standard length.
Table 5. Row Position vs. DIM ‘A’
CABLE SIZE
Standard
Standard
Standard
Standard
Large
Large
E
F
C
D
ROW
POSITION* DIM ‘A’
A
B
3-1/16 in. (80.96 mm)
4-11/16 in. (119.06 mm)
5-7/16 in (138.11 mm)
7-3/32 in. (180.18 mm)
3-7/8 in. (98.42 mm)
6-5/16 (160.34 mm)
* per Figure 33 on Page 36
S TANDARD LENGTH
BREAKOUT
DIM ‘A’ CABLE
CLAMP
OUTER CABLE JACKET
25140-A
Figure 40. Cabled Module Assembly Cable Clamp Position and Breakout c. If the cable being installed is designated for the splice chassis, obtain the appropriate
DIM ‘A’ length from Table 5 based on where the cable clamp will be installed on the bracket, and measure an additional length of 210 in. (533.4 cm), as shown in
Figure 41 . This is where the cable clamp should be placed on the cable. For cable routing instructions, refer to NG4access ODF Platform Splice Chassis and Splice Tray
User Manual (TECP-90-704).
210 IN. (5 33 .4 CM)
BREAKOUT
DIM ‘A’ CABLE
CLAMP
OUTER CABLE JACKET
2516 3 -A
Figure 41. Splice Cable Clamp Position and Breakout
8. If the cable diameter is 0.8 in (2.0 cm) or less, assemble the “standard” cable clamp at the cable clamp position (see Figure 42 ). There are different sizes of grommets, measured by their inside diameters of 0.4, 0.5, 0.6, and 0.7 in. (1.0, 1.27, 1.52, and 1.78 cm). Select the grommet with an inside diameter that is one size smaller than the outside diameter of the cable. After assembling the components on the mounting screws, tighten the screws until the yokes make contact, then tighten the screws four additional revolutions.
Page 41
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
MOUNTING
S CREW S
(63 2 x 1.75 IN.)
GROMMET
BACK
PLATE
RUBBER
YOKE
251 3 6-A
COVER
Figure 42. Standard Cable Clamp Exploded View
9. If the cable diameter is greater than 0.8 in (2.03 cm) and less than 1-1/32 inch (2.62 cm), assemble the “large” cable clamp at the cable clamp position (see Figure 43 ). There are different sizes of grommets, measured by their inside diameters of 0.8, 0.9, and 1.0 in.
(2.03, 2.29, and 2.54 cm). Select the grommet with an inside diameter that is one size smaller than the outside diameter of the cable. After assembling the components on the mounting screws, tighten the screws until the yokes make contact.
MOUNTING
S CREW S
(103 2 x 2.00 IN.)
GROMMET
BACK
PLATE
RUBBER
YOKE
251 3 5-A
COVER
LARGE
Figure 43. Large Cable Clamp Exploded View
Page 42
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Note: Do not continue to tighten as instructed for the standard cable clamp in Step 8 .
Note: If large cables are being installed, the last four cable clamps may need to be assembled on the cable below the raised floor.
10. Beginning at the back of the cable clamp bracket (in the middle of the frame), hang the cable clamps by positioning the hanging slots on the mounting screws, as shown in
Figure 44 . Be sure to position the clamps on the correct mounting screws as indicated in
Figure 45 . Work from the back of the bracket towards the rear of the frame. After hanging a cable clamp on the mounting screws, tighten the mounting screws until secure.
NOTE: S TART HANGING CABLE CLAMP S AT
THE BACK OF THE BRACKET, WORK TO THE
REAR OF THE FRAME. LA S T FOUR CLAMP S
MAY NEED TO BE IN S TALLED BELOW THE
RAI S ED FLOOR.
MOUNTING
S CREW S
CABLE BRACKET
CABLE
CLAMP
ROW C
ROW D
REAR OF
FRAME
251 3 9-A
Figure 44. Hanging Cable Clamps on Bracket
HANGING
S LOT
EXAMPLE S OF S TANDARD
CLAMP PO S ITION S
EXAMPLE S OF LARGE
CLAMP PO S ITION S
ROW F
Figure 45. Correct Placement of Cable Clamps
25141-A
Page 43
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
11. If the frame does not have a splice chassis, re-install the cover for non-splice applications
(removed in Step 4 on Page 39 ).
Note: See TECP-90-713 for instructions on installing auxiliary cable spools for use with
NG4access cabled module assemblies routed into the frame from the raised floor bracket.
6 INSTALLING A SPOOL BRACKET ASSEMBLY (FOR FRAME WITH SPLICE CHASSIS)
If the frame on which the bracket was just installed has a splice chassis, the Spool Bracket
Assembly (provided with the Raised Floor Standard Cable Clamp Bracket Kit) must also be installed.
Use the following procedure.
1. Install the protection plate (second largest piece in the Raised Floor Standard Cable Clamp
Bracket Kit) in the location shown in Figure 46 . Secure the plate using the mounting screws provided. Torque to 16 in.-lbs. (1.8 Newton meters).
Page 44
© 2017, CommScope, Inc.
PROTECTION
PLATE
IN S TALLED
CABLE S
AND CLAMP S
Figure 46. Installing Bracket in Frame
251 3 4-A
TECP-90-708 • Issue 5 • April 2017
2. Remove and discard #12 washer and screw securing vertical cable guide next to the bottom chassis, as shown in Figure 47 . Discard screw, washer, and cable guide.
REMOVE
VERTICAL CABLE
GUIDE
REMOVE
AND
DI S CARD
S CREW
AND
WA S HER
NOTE:
FOR CLARITY
S OME S HEET METAL
REMOVED FROM FRAME
REAR VIEW
OF FRAME
Figure 47. Removing Vertical Cable Guide
25170-A
3. Locate the spool bracket assembly that came with the Standard Cable Bracket Kit, and install the bracket in the location from which the vertical cable guide was just removed as shown in Figure 48 . Install the two screws and washers provided using the hole from which the standard bracket screw was just removed and the hole above it. Torque to 18 inch-pounds (2.03 Newton meters).
S POOL
BRACKET
A SS EMBLY
NOTE:
FOR CLARITY
S OME S HEET METAL
REMOVED FROM FRAME
REAR VIEW
OF FRAME
Figure 48. Installing Spool Bracket
IN S TALL TWO EACH
MOUNTING S CREW S
AND LOCK WA S HER S
(#12 PANHEAD).
TIGTHEN TO 18 INCH-LB S .
(2.0
3 NEWTON METER S )
2514 3 -A
Page 45
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Note: When routing a cable from the cable clamp bracket to the splice chassis, bring the cable up in front of the spool and loop the cable back and over the spool then down into the area below the splice chassis as shown in Figure 49 .
BACK
PLATE
REAR VIEW
( S PLICE
CHA SS I S
REMOVED)
25144-A
CABLE ROUTED INTO AREA
BELOW S PLICE CHA SS I S
Figure 49. Routing Cables On Spool Bracket
Note: For instructions on routing the cables into the splice chassis and splice chips, refer to NG4access ODF Platform Splice Chassis and Splice Tray User Manual (TECP-90-
704). This procedure only covers the spool bracket.
4. Slide the splice chassis back into the frame.
5. Re-install the front plate removed in Step 3 on Page 38 .
7 INSTALLING AUXILIARY CABLE SPOOLS (FOR FRAMES WITHOUT SPLICE CHASSIS)
If the frame on which the bracket was just installed does not have a splice chassis (cables will be routed to the universal chassis), auxiliary cable spool brackets (separately ordered) must also be installed. The purpose of these spools is to provide a means for looping the cables over before they are routed into the universal chassis. One kit is required for each universal chassis on the right rear side only. Before the kit can be installed, the vertical cable guide in that location must be removed.
Page 46
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
Use the following procedure.
1. On the rear side of the frame, remove the vertical cable guide by removing one #12 screw and washer holding the bracket in place. Set aside the screw and washer for use in installing the new bracket. Refer to Figure 50 .
25240-A
Figure 50. Removing the Vertical Cable Guide
2. Install the auxiliary cable spool bracket in the location from which the vertical cable guide was just removed. Refer to Figure 51 and Figure 52 .
Note: Top chassis mounting holes are different than for other chassis in frame. Mount as shown in Figure 52 .
Figure 51. Installing the Auxiliary Cable Spool Bracket
25241-A
Page 47
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
TOP CHA SS I S
ON FRAME
2.78 IN.
(7.06 CM)
BOTTOM
HOLE
MOUNTING
ALL OTHER
CHA SS I S
MOUNTING
HOLE S
25242-A
Figure 52. Rear View of Bracket Locations (Top Two Chassis)
1.81 IN.
(4.60 CM)
UPPER
HOLE
MOUNTING
8 GROUNDING THE FRAME
Standard grounding is accomplished by connecting a compression lug to a grounding point on the top member of the frame, as shown in Figure 53 .
Any 2-hole location with the correct hole spacing may be used. Use a 2-hole #10 compression lug with 3/4 inch hole (1.905 cm) spacing.
Scrape the paint to expose bare metal and apply deoxidant in the grounding location. For a grounding wire, use only 6 AWG or thicker copper wire.
Page 48
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
TO OFFICE
GROUND
GROUND
LUG
250 8 2-A
Figure 53. Grounding the Frame
9 SECURING TWO FRAMES TOGETHER
When a NG4access frame is installed adjacent to an existing NG4access frame, the frames must be secured together. This is done using the following items shipped with the frame: junction plates (6); rear splice brackets (4); and associated hardware.
Use the following procedure:
1. Position yourself on rear side of the two frames. Locate the place where the two top horizontal troughs interface with one another. Install a junction plate spanning the two troughs on the bottom side ( Figure 54 ). Secure using four 10x32 flathead screws.
Page 49
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
10 x 3 2
FLATHEAD
S CREW S
REAR
TROUGH
REAR
TROUGH
JUNCTION
PLATE
BOTTOM
VIEW
JUNCTION
PLATE
25105-A
Figure 54. Installing Junction Plates (Six Places)
2. Continue down the frames installing junction plates in a like manner for each of the remaining five levels of rear horizontal trough.
3. Install rear splice brackets. There are two sets of two brackets installed in the two locations shown in Figure 55 .
Page 50
© 2017, CommScope, Inc.
REAR S PLICE
BRACKET S
IN S ERT REAR S PLICE BRACKET INTO
CABLE TROUGH S LOT (2 PLACE S )
12-24 S CREW S (6)
NOTE: S PLICE BRACKET S
PROVIDED WITH RACK
TECP-90-708 • Issue 5 • April 2017
S PLICE BRACKET LOCATION S (2)
S HOWN IN GRAY FOR CLARITY
REAR VIEW
Figure 55. Installing Rear Splice Brackets
25070-A
Page 51
© 2017, CommScope, Inc.
TECP-90-708 • Issue 5 • April 2017
10 CUSTOMER INFORMATION AND ASSISTANCE
• To find out more about CommScope
®
products, visit the web at www.commscope.com/
• For technical assistance, customer service, or to report any missing/damaged parts, visit http://www.commscope.com/SupportCenter
Page 52