Yaskawa SGDV MECHATROLINK-III Manual
Anúncio
Anúncio
AC Servo Drives
DC Power Input
-
V
Series
USER'S MANUAL
Design and Maintenance
Rotational Motor
MECHATROLINK-
III
Communications Reference
SGMMV Servomotor
SGDV SERVOPACK
MANUAL NO. SIEP S800000 83B
Outline
SigmaWin+
Wiring and Connection
Operation
Adjustments
Utility Functions (Fn
)
Monitor Displays (Un
)
Troubleshooting
Appendix
7
8
5
6
9
3
4
1
2
Copyright
©
2011 YASKAWA ELECTRIC CORPORATION
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
About this Manual
This manual describes information required for designing, testing, adjusting, and maintaining DC Power Input
Σ -V Series SERVOPACKs.
Keep this manual in a location where it can be accessed for reference whenever required. Manuals outlined on the following page must also be used as required by the application.
Description of Technical Terms
The following table shows the meanings of terms used in this manual.
Term
Servomotor
SERVOPACK
Servo Drive
Servo System
MIII Model
Servo ON
Servo OFF
Base Block (BB)
Servo Lock
Main Circuit Cable
Meaning
Σ -Vmini Series SGMMV servomotor
DC Power Input Σ -V Series SGDV servo amplifier
A set including a servomotor and SERVOPACK (i.e., a servo amplifier)
A servo control system that includes the combination of a servo drive with a host controller and peripheral devices
MECHATROLINK-III communications reference used for SERVOPACK interface
Power to motor ON
Power to motor OFF
Power supply to motor is turned OFF by shutting off the base current to the power transistor in the current amplifier.
A state in which the motor is stopped and is in position loop with a position reference of 0.
Cables which connect to the main circuit terminals, including power supply cables, servomotor main circuit cables, and others.
IMPORTANT Explanations
The following icon is displayed for explanations requiring special attention.
• Indicates important information that should be memorized, as well as precautions, such as alarm displays, that do not involve potential damage to equipment.
iii
iv
Notation Used in this Manual
• Notation for Reverse Signals
The names of reverse signals (i.e., ones that are valid when low) are written with a forward slash (/) before the signal name.
Notation Example
BK = /BK
• Notation for Parameters
The notation depends on whether the parameter requires a value setting (parameter for numeric settings) or requires the selection of a function (parameter for selecting functions).
• Parameters for Numeric Settings
Control methods for which the parameter applies.
Speed : Speed control Position : Position control Torque : Torque control
Emergency Stop Torque Speed Position Torque
Pn406
Setting Range
0% to 800%
Setting Unit
1%
Factory Setting When Enabled
800 After change
Parameter number
Indicates the setting range for the parameter.
Indicates the minimum setting unit for the parameter.
Indicates the parameter setting before shipment.
Indicates when a change to the parameter will be effective.
Classification
Setup
Indicates the parameter classification.
• Parameters for Selecting Functions
Pn002
Parameter n.
0
[Factory setting] n.
1
Meaning
Uses the absolute encoder as an absolute encoder.
Uses the absolute encoder as an incremental encoder.
Parameter number
When Enabled
After restart
Classification
The notation “n.
” indicates a parameter for selecting functions. Each corresponds to the setting value of that digit. The notation shown here means that the third digit is 1.
This section explains the selections for the function.
Setup
Notation Example
(Display Example for Pn002)
㨚㧜㧜㧜㧜
3rd digit
4th digit
Pn002.2
Pn002.3
Digit Notation
1st digit
2nd digit
Notation
Pn002.0
Pn002.1
Meaning
Indicates the value for the
1st digit of parameter Pn002.
Indicates the value for the
2nd digit of parameter Pn002.
Indicates the value for the
3rd digit of parameter Pn002.
Indicates the value for the
4th digit of parameter Pn002.
Notation
Setting Notation
Meaning
Pn002.0 = x or n.
x
Indicates that the value for the
1st digit of parameter Pn002 is x.
Pn002.1 = x or n.
x
Indicates that the value for the
2nd digit of parameter Pn002 is x.
Pn002.2 = x or n.
x
Indicates that the value for the
3rd digit of parameter Pn002 is x.
Pn002.3 = x or n.x
Indicates that the value for the
4th digit of parameter Pn002 is x.
Manuals Related to the DC Power Input Σ -V Series
Refer to the following manuals as required.
Name
Selecting
Models and
Peripheral
Devices
Ratings and
Specifications
System
Design
Panels and
Wiring
Trial
Operation
DC Power Input Σ -V Series
User's Manual
Setup
Rotational Motor
(No.: SIEP S800000 80)
Σ -V Series
Product Catalog
(No.: KAEP S800000 42)
DC Power Input Σ -V Series
User's Manual
Design and Maintenance
Rotational Motor/
MECHATROLINKIII
Communications Reference
(this manual)
Σ -V Series
User's Manual
MECHATROLINKIII
Standard Servo Profile
Commands
(No.: SIEP S800000 63)
DC Power Input Σ -V Series
AC SERVOPACK SGDV
Safety Precautions
(No.: TOBP C710829 06)
AC SERVOMOTOR
Safety Precautions
(No.: TOBP C230200 00)
Trial
Operation and Servo
Adjustment
Maintenance and
Inspection
v
vi
Trademarks
MECHATROLINK is a trademark of the MECHATROLINK Members Association.
Safety Information
The following conventions are used to indicate precautions in this manual. Failure to heed precautions provided in this manual can result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
WARNING
Indicates precautions that, if not heeded, could possibly result in loss of life or serious injury.
CAUTION
Indicates precautions that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
In some situations, the precautions indicated could have serious consequences if not heeded.
PROHIBITED
Indicates prohibited actions that must not be performed. For example, this symbol would be used to indicate that fire is prohibited as follows:
MANDATORY
Indicates compulsory actions that must be performed. For example, this symbol would be used to indicate that grounding is compulsory as follows:
Safety Precautions
This section describes important precautions that must be followed during storage, transportation, installation, wiring, operation, maintenance, inspection, and disposal. Be sure to always observe these precautions thoroughly.
WARNING
• Never touch any rotating servomotor parts during operation.
Failure to observe this warning may result in injury.
• Before starting operation with a machine connected, make sure that an emergency stop can be applied at any time.
Failure to observe this warning may result in injury or damage to the equipment.
• Never touch the inside of the SERVOPACKs.
Failure to observe this warning may result in electric shock.
• Immediately after the power is turned OFF or after a voltage resistance test, do not touch terminals.
Residual voltage may cause electric shock.
• Follow the procedures and instructions provided in the manuals for the products being used in the trial operation.
Failure to do so may result not only in faulty operation and damage to equipment, but also in personal injury.
• The multiturn limit value need not be changed except for special applications.
Changing it inappropriately or unintentionally can be dangerous.
• If the Multiturn Limit Disagreement alarm occurs, check the setting of parameter Pn205 in the SER-
VOPACK to be sure that it is correct.
If Fn013 is executed when an incorrect value is set in Pn205, an incorrect value will be set in the encoder. The alarm will disappear even if an incorrect value is set, but incorrect positions will be detected, resulting in a dangerous situation where the machine will move to unexpected positions.
• Do not remove the cables or connectors from the SERVOPACK while the power is ON.
Failure to observe this warning may result in electric shock.
• Do not damage, pull, exert excessive force on, or place heavy objects on the cables.
Failure to observe this warning may result in electric shock, stopping operation of the product, or fire.
• Do not modify the product.
Failure to observe this warning may result in injury, damage to the equipment, or fire.
• Provide appropriate braking devices on the machine side to ensure safety. The holding brake on a servomotor with a brake is not a braking device for ensuring safety.
Failure to observe this warning may result in injury.
• Do not come close to the machine immediately after resetting an instantaneous power interruption to avoid an unexpected restart. Take appropriate measures to ensure safety against an unexpected restart.
Failure to observe this warning may result in injury.
• Connect the ground terminal according to local electrical codes (100 Ω or less).
Improper grounding may result in electric shock or fire.
• Installation, disassembly, or repair must be performed only by authorized personnel.
Failure to observe this warning may result in electric shock or injury.
vii
viii
Storage and Transportation
CAUTION
• Do not store or install the product in the following locations.
Failure to observe this caution may result in fire, electric shock, or damage to the equipment.
• Locations subject to direct sunlight
• Locations subject to temperatures outside the range specified in the storage/installation temperature conditions
• Locations subject to humidity outside the range specified in the storage/installation humidity conditions
• Locations subject to condensation as the result of extreme changes in temperature
• Locations subject to corrosive or flammable gases
• Locations subject to dust, salts, or iron dust
• Locations subject to exposure to water, oil, or chemicals
• Locations subject to shock or vibration
• Do not hold the product by the cables, motor shaft, or encoder while transporting it.
Failure to observe this caution may result in injury or malfunction.
• Do not place any load exceeding the limit specified on the packing box.
Failure to observe this caution may result in injury or malfunction.
• If disinfectants or insecticides must be used to treat packing materials such as wooden frames, pallets, or plywood, the packing materials must be treated before the product is packaged, and methods other than fumigation must be used.
Example: Heat treatment, where materials are kiln-dried to a core temperature of 56 ° C for 30
minutes or more.
If the electronic products, which include stand-alone products and products installed in machines, are packed with fumigated wooden materials, the electrical components may be greatly damaged by the gases or fumes resulting from the fumigation process. In particular, disinfectants containing halogen, which includes chlorine, fluorine, bromine, or iodine can contribute to the erosion of the capacitors.
Installation
CAUTION
• Never use the product in an environment subject to water, corrosive gases, flammable gases, or combustibles.
Failure to observe this caution may result in electric shock or fire.
• Do not step on or place a heavy object on the product.
Failure to observe this caution may result in injury or malfunction.
• Do not cover the inlet or outlet ports and prevent any foreign objects from entering the product.
Failure to observe this caution may cause internal elements to deteriorate resulting in malfunction or fire.
• Be sure to install the product in the correct direction.
Failure to observe this caution may result in malfunction.
• Provide the specified clearances between the SERVOPACK and the control panel or with other devices.
Failure to observe this caution may result in fire or malfunction.
• Do not apply any strong impact.
Failure to observe this caution may result in malfunction.
Wiring
CAUTION
• Be sure to wire correctly and securely.
Failure to observe this caution may result in motor overrun, injury, or malfunction.
• Do not connect a commercial power supply to the U, V, or W terminals for the servomotor connection.
Failure to observe this caution may result in injury or fire.
• Securely connect the main circuit terminals.
Failure to observe this caution may result in fire.
• Do not bundle or run the servomotor main circuit cables together with the I/O signal cables or the encoder cables in the same duct. Keep the servomotor main circuit cables separated from the I/O signal cables and encoder cables by at least 30 cm.
Placing these cables too close to each other may result in malfunction.
• Use shielded twisted-pair cables or screened unshielded twisted-pair cables for I/O signal cables and the encoder cables.
• The maximum wiring length is 3 m for I/O signal cables, 50 m for servomotor main circuit cables and encoder cables, and 10 m for power supply cables.
• Install the battery in the battery unit of the encoder cable with a battery unit.
• Voltage remains in the SERVOPACK even after the power supply is turned OFF. To prevent electric shock, do not touch the input terminals for the main circuit power supply or those for the control power supply.
Before wiring or inspections, confirm that the SERVOPACK has completely discharged.
• Be sure to observe the following precautions when wiring the SERVOPACK main circuit terminal blocks.
• Do not turn the SERVOPACK power ON until all wiring, including the main circuit terminal blocks, has been completed.
• Remove detachable power supply input connectors or motor connectors from the SERVOPACK before wiring.
• Make sure that the wiring for both the main circuit power supply and control power supply is correct.
Incorrect wiring may cause damage.
• Make sure that the polarity of the input power supply is correct.
Incorrect polarity may cause damage.
• Always use the specified power supply voltage.
An incorrect voltage may result in fire or malfunction.
• Take appropriate measures to ensure that the input power supply is supplied within the specified voltage fluctuation range.
An incorrect power supply may result in damage to the equipment.
• Install external breakers or other safety devices against short-circuiting in external wiring.
Failure to observe this caution may result in fire.
• Take appropriate and sufficient countermeasures for each form of potential interference when installing systems in the following locations.
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields and magnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
Failure to observe this caution may result in damage to the equipment.
• Do not reverse the polarity of the battery when connecting it.
Failure to observe this caution may damage the battery, the SERVOPACK or servomotor, or cause an explosion.
• Wiring or inspection must be performed by a technical expert.
• Use a 24-VDC or 48-VDC power supply with double insulation or reinforced insulation.
• Failures caused by incorrect wiring or wrong voltage application in the brake circuit may damage the equipment or cause an accident resulting in death or injury. Follow the procedures and instructions for wiring and trial operation precisely as described in this manual.
• When using a detector or a breaker for leakage current, select the appropriate one by considering the grounding conditions and the leakage current of noise filter. For details, contact the manufacturer of the noise filter.
• Incorrect wiring or incorrect voltage application to the output circuit may cause short-circuit.
The above failures will prevent the holding brake from working, which may damage the machine or cause an accident resulting in death or injury.
ix
x
CAUTION
• Inverting the polarity of the brake signal (/BK), i.e. positive logic, will prevent the holding brake from working in case of its signal line disconnection.
If this setting is absolutely necessary, check the operation and confirm that there are no safety problems.
• Provide separate AC/DC power supplies for the main circuits and for controls.
Failure to observe this caution may result in malfunction.
• Do not connect devices (such as motors or solenoids) that greatly change the load or devices (such as electromagnetic switches) that generate surge voltages to the controller power line.
Failure to observe this caution may result in deterioration of the internal elements or a blown fuse.
Operation
CAUTION
• Always use the servomotor and SERVOPACK in one of the specified combinations.
Failure to observe this caution may result in fire or malfunction.
• Conduct trial operation on the servomotor alone with the motor shaft disconnected from the machine to avoid accidents.
Failure to observe this caution may result in injury.
• During trial operation, confirm that the holding brake works correctly. Furthermore, secure system safety against problems such as signal line disconnection.
• Before starting operation with a machine connected, change the parameter settings to match the parameters of the machine.
Starting operation without matching the proper settings may cause the machine to run out of control or malfunction.
• Do not turn the power ON and OFF more than necessary.
Do not use the SERVOPACK for applications that require the power to turn ON and OFF frequently. Such applications will cause elements in the SERVOPACK to deteriorate.
As a guideline, at least one hour should be allowed between the power being turned ON and OFF once actual operation has been started.
• When carrying out JOG operation (Fn002), origin search (Fn003), or EasyFFT (Fn206), forcing movable machine parts to stop does not work for forward overtravel or reverse overtravel. Take necessary precautions.
Failure to observe this caution may result in damage to the equipment.
• When using the servomotor for a vertical axis, install safety devices to prevent workpieces from falling due to alarms or overtravels. Set the servomotor so that it will stop in the zero clamp state when overtravel occurs.
Failure to observe this caution may cause workpieces to fall due to overtravel.
• When not using the tuning-less function, set the correct moment of inertia ratio (Pn103).
Setting an incorrect moment of inertia ratio may cause machine vibration.
• Do not touch the SERVOPACK heat sinks or servomotor while power is ON or soon after the power is turned OFF.
Failure to observe this caution may result in burns due to high temperatures.
• Do not make any extreme adjustments or setting changes of parameters.
Failure to observe this caution may result in injury or damage to the equipment due to unstable operation.
• When an alarm occurs, remove the cause, reset the alarm after confirming safety, and then resume operation.
Failure to observe this caution may result in damage to the equipment, fire, or injury.
• Do not use the holding brake of the servomotor for braking.
Failure to observe this caution may result in malfunction.
• The servomotor will decelerate to a stop if the main-circuit or the control-circuit power supply turns
OFF during operation without turning servo OFF.
• An alarm or warning may occur if communications are performed with the host controller while the
SigmaWin+ is operating.
If an alarm or warning occurs, it may stop the current process and stop the system.
Maintenance and Inspection
CAUTION
• Do not disassemble the SERVOPACK and the servomotor.
Failure to observe this caution may result in electric shock or injury.
• Do not attempt to change wiring while the power is ON.
Failure to observe this caution may result in electric shock or injury.
• When replacing the SERVOPACK, resume operation only after copying the previous SERVOPACK parameters to the new SERVOPACK.
Failure to observe this caution may result in damage to the equipment.
Disposal
CAUTION
• When disposing of the products, treat them as ordinary industrial waste.
General Precautions
Observe the following general precautions to ensure safe application.
• The products shown in illustrations in this manual are sometimes shown without covers or protective guards.
Always replace the cover or protective guard as specified first, and then operate the products in accordance with the manual.
• The drawings presented in this manual are typical examples and may not match the product you received.
• If the manual must be ordered due to loss or damage, inform your nearest Yaskawa representative or one of the offices listed on the back of this manual.
xi
xii
Warranty
(1) Details of Warranty
Warranty Period
The warranty period for a product that was purchased (hereinafter called “delivered product”) is one year from the time of delivery to the location specified by the customer or 18 months from the time of shipment from the
Yaskawa factory, whichever is sooner.
Warranty Scope
Yaskawa shall replace or repair a defective product free of charge if a defect attributable to Yaskawa occurs during the warranty period above. This warranty does not cover defects caused by the delivered product reaching the end of its service life and replacement of parts that require replacement or that have a limited service life.
This warranty does not cover failures that result from any of the following causes.
1. Improper handling, abuse, or use in unsuitable conditions or in environments not described in product catalogs or manuals, or in any separately agreed-upon specifications
2. Causes not attributable to the delivered product itself
3. Modifications or repairs not performed by Yaskawa
4. Abuse of the delivered product in a manner in which it was not originally intended
5. Causes that were not foreseeable with the scientific and technological understanding at the time of shipment from Yaskawa
6. Events for which Yaskawa is not responsible, such as natural or human-made disasters
(2) Limitations of Liability
1. Yaskawa shall in no event be responsible for any damage or loss of opportunity to the customer that arises due to failure of the delivered product.
2. Yaskawa shall not be responsible for any programs (including parameter settings) or the results of program execution of the programs provided by the user or by a third party for use with programmable Yaskawa products.
3. The information described in product catalogs or manuals is provided for the purpose of the customer purchasing the appropriate product for the intended application. The use thereof does not guarantee that there are no infringements of intellectual property rights or other proprietary rights of Yaskawa or third parties, nor does it construe a license.
4. Yaskawa shall not be responsible for any damage arising from infringements of intellectual property rights or other proprietary rights of third parties as a result of using the information described in catalogs or manuals.
(3) Suitability for Use
1. It is the customer’s responsibility to confirm conformity with any standards, codes, or regulations that apply if the Yaskawa product is used in combination with any other products.
2. The customer must confirm that the Yaskawa product is suitable for the systems, machines, and equipment used by the customer.
3. Consult with Yaskawa to determine whether use in the following applications is acceptable. If use in the application is acceptable, use the product with extra allowance in ratings and specifications, and provide safety measures to minimize hazards in the event of failure.
• Outdoor use, use involving potential chemical contamination or electrical interference, or use in conditions or environments not described in product catalogs or manuals
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, vehicle systems, medical equipment, amusement machines, and installations subject to separate industry or government regulations
• Systems, machines, and equipment that may present a risk to life or property
• Systems that require a high degree of reliability, such as systems that supply gas, water, or electricity, or systems that operate continuously 24 hours a day
• Other systems that require a similar high degree of safety
4. Never use the product for an application involving serious risk to life or property without first ensuring that the system is designed to secure the required level of safety with risk warnings and redundancy, and that the
Yaskawa product is properly rated and installed.
5. The circuit examples and other application examples described in product catalogs and manuals are for reference. Check the functionality and safety of the actual devices and equipment to be used before using the product.
6. Read and understand all use prohibitions and precautions, and operate the Yaskawa product correctly to prevent accidental harm to third parties.
(4) Specifications Change
The names, specifications, appearance, and accessories of products in product catalogs and manuals may be changed at any time based on improvements and other reasons. The next editions of the revised catalogs or manuals will be published with updated code numbers. Consult with your Yaskawa representative to confirm the actual specifications before purchasing a product.
xiii
xiv
Harmonized Standards
North American Safety Standards (UL)
SERVOPACK SGDV
Model
Servomotor SGMMV
European Directives
UL Standards
UL508C
UL1004
SERVOPACK
Servomotor
Model
SGDV
SGMMV
European Directives
EMC Directive
2004/108/EC
EMC Directive
2004/108/EC
Low Voltage Directive
2006/95/EC
Harmonized Standards
EN 55011 /group 1, class A
EN 61000-6-2
EN 61800-3
Low Voltage Directive
2006/95/EC
EN 61800-5-1
EN 55011 /group 1, class A
EN 61000-6-2
EN 61800-3
EN 60034-1
EN 60034-5
Contents
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii
Harmonized Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
Chapter 1 Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1.1 DC Power Input
Σ
-V Series SERVOPACKs. . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2 Part Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.3 SERVOPACK Ratings and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3.1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3.2 Basic Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.3.3 MECHATROLINKIII Function Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.4 SERVOPACK Internal Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
1.4.1 MECHATROLINKIII Communication Reference (Model: SGDV E21A) . . . . . . . . . 1-7
1.5 Examples of Servo System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.6 SERVOPACK Model Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
1.7 Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Chapter 2 SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2.1 SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2 Preparing SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.3 Connecting a PC with SigmaWin+. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.4 Starting and Operating the SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5 Parameters (Pn ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.1 Parameter Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.2 Notation for Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.3 Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Chapter 3 Wiring and Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3.1 Main Circuit Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.1.1 Main Circuit Terminals (CN3, CN4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.1.2 Main Circuit Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.1.3 Typical Main Circuit Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.1.4 Power Supply Capacities and Power Losses. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.1.5 Input Power Supply, Molded-case Circuit Breaker, and Fuse . . . . . . . . . . . . . . . . . . . . . . 3-5
3.1.6 Using More Than One SERVOPACK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.1.7 General Precautions for Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
3.2 I/O Signal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.2.1 I/O Signal (CN1) Names and Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.2.2 Example of I/O Signal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.3 I/O Signal Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.1 Input Signal Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.2 Output Signal Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.4 Examples of Connection to Host Controller . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
3.4.1 Sequence Input Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
3.4.2 Sequence Output Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
3.5 Wiring MECHATROLINKIII Communications. . . . . . . . . . . . . . . . . . . . . . . 3-23 xv
xvi
3.6 Encoder Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.6.1 Encoder Signal (CN2) Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.6.2 Encoder Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.7 Noise Control and Measures for Harmonic Suppression . . . . . . . . . . . . . . . 3-26
3.7.1 Wiring for Noise Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-26
3.7.2 Precautions on Connecting Noise Filter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
Chapter 4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
4.1 MECHATROLINKIII Communications Settings. . . . . . . . . . . . . . . . . . . . . . . 4-3
4.1.1 Setting Switches S1 and S2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2 MECHATROLINKIII Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.3 Basic Functions Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.1 Servomotor Rotation Direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.2 Overtravel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.3.3 Software Limit Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
4.3.4 Holding Brakes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.3.5 Stopping Servomotors after SV_OFF Command or Alarm Occurrence. . . . . . . . . . . . . . 4-15
4.3.6 Setting Motor Overload Detection Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
4.4 Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4.4.1 Inspection and Checking before Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4.4.2 Trial Operation via MECHATROLINKIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
4.4.3 Electronic Gear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
4.5 Test Without Motor Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
4.5.1 Motor Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
4.5.2 Motor Position and Speed Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.5.3 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
4.6 Limiting Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
4.6.1 Internal Torque Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
4.6.2 External Torque Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
4.6.3 Checking Output Torque Limiting during Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
4.7 Absolute Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
4.7.1 Connecting the Absolute Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
4.7.2 Absolute Data Request (SENS ON Command) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
4.7.3 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
4.7.4 Absolute Encoder Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
4.7.5 Multiturn Limit Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35
4.7.6 Multiturn Limit Disagreement Alarm (A.CC0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
4.7.7 Absolute Encoder Origin Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-39
4.8 Other Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.8.1 Servo Alarm Output Signal (ALM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.8.2 Warning Output Signal (/WARN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.8.3 Rotation Detection Output Signal (/TGON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
4.8.4 Servo Ready Output Signal (/S-RDY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
4.8.5 Speed Coincidence Output Signal (/V-CMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-42
4.8.6 Positioning Completed Output Signal (/COIN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
4.8.7 Positioning Near Output Signal (/NEAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
4.8.8 Speed Limit Detection Signal (/VLT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
Chapter 5 Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
5.1 Type of Adjustments and Basic Adjustment Procedure . . . . . . . . . . . . . . . . . 5-3
5.1.1 Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.1.2 Basic Adjustment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.1.3 Monitoring Operation during Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.1.4 Safety Precautions on Adjustment of Servo Gains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5.2 Tuning-less Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.2.1 Tuning-less Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.2.2 Tuning-less Levels Setting (Fn200) Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5.2.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5.3 Advanced Autotuning (Fn201) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.3.1 Advanced Autotuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.3.2 Advanced Autotuning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5.3.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-33
5.4 Advanced Autotuning by Reference (Fn202). . . . . . . . . . . . . . . . . . . . . . . . 5-34
5.4.1 Advanced Autotuning by Reference. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34
5.4.2 Advanced Autotuning by Reference Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
5.4.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
5.5 One-parameter Tuning (Fn203) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.5.1 One-parameter Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.5.2 One-parameter Tuning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.5.3 One-parameter Tuning Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-52
5.5.4 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-53
5.6 Anti-Resonance Control Adjustment Function (Fn204) . . . . . . . . . . . . . . . . 5-54
5.6.1 Anti-Resonance Control Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure. . . . . . . . . . . . . . . . 5-55
5.6.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-63
5.7 Vibration Suppression Function (Fn205) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-64
5.7.1 Vibration Suppression Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-64
5.7.2 Vibration Suppression Function Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-65
5.7.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-70
5.8 Additional Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-71
5.8.1 Switching Gain Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-71
5.8.2 Manual Adjustment of Friction Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
5.8.3 Current Control Mode Selection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
5.8.4 Current Gain Level Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
5.8.5 Speed Detection Method Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
5.8.6 Backlash Compensation Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-78
5.9 Compatible Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-84
5.9.1 Feedforward Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-84
5.9.2 Mode Switch (P/PI Switching) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-85
5.9.3 Torque Reference Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-87
5.9.4 Position Integral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-89
Chapter 6 Utility Functions (Fn
) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
6.1 List of Utility Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Alarm History Display (Fn000) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.3 JOG Operation (Fn002) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.4 Origin Search (Fn003) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.5 Program JOG Operation (Fn004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.6 Initializing Parameter Settings (Fn005) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
6.7 Clearing Alarm History (Fn006) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-19
6.8 Offset Adjustment of Analog Monitor Output (Fn00C) . . . . . . . . . . . . . . . . . 6-20
6.9 Gain Adjustment of Analog Monitor Output (Fn00D) . . . . . . . . . . . . . . . . . . 6-22
6.10 Automatic Offset-Signal Adjustment of the Motor Current Detection Signal
(Fn00E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
6.11 Manual Offset-Signal Adjustment of the Motor Current Detection Signal
(Fn00F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
6.12 Write Prohibited Setting (Fn010) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28
6.13 Servomotor Model Display (Fn011) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-30
6.14 Software Version Display (Fn012) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-31
xvii
xviii
6.15 Vibration Detection Level Initialization (Fn01B) . . . . . . . . . . . . . . . . . . . . . 6-32
6.16 Display of SERVOPACK and Servomotor ID (Fn01E) . . . . . . . . . . . . . . . . 6-35
6.17 Software Reset (Fn030) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-36
6.18 EasyFFT (Fn206) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-41
6.19 Online Vibration Monitor (Fn207) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-45
Chapter 7 Monitor Displays (Un
) . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-1
7.1 List of Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.2 Viewing Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2.1 System Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2.2 Status Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
7.2.3 Motion Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
7.2.4 Input Signal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
7.2.5 Output Signal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Chapter 8 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-1
8.1 Alarm Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.1.1 List of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.1.2 Troubleshooting of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2 Warning Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
8.2.1 List of Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
8.2.2 Troubleshooting of Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-19
8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning . . 8-23
8.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24
Chapter 9 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-1
9.1 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.1.1 Utility Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.1.2 Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
9.1.3 MECHATROLINKIII Common Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-34
9.2 List of Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-42
9.3 Parameter Recording Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-43
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1
Revision History
1
Outline
1.1 DC Power Input
Σ
-V Series SERVOPACKs . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2 Part Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.3 SERVOPACK Ratings and Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3.1 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.3.2 Basic Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.3.3 MECHATROLINKIII Function Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1.4 SERVOPACK Internal Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
1.4.1 MECHATROLINKIII Communication Reference (Model: SGDV E21A) . . . . . . 1-7
1.5 Examples of Servo System Configurations . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.6 SERVOPACK Model Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
1.7 Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1
1-1
1-2
1 Outline
1.1
DC Power Input Σ -V Series SERVOPACKs
The DC Power Input Σ -V Series SERVOPACKs are designed for applications that require frequent highspeed, high-precision positioning. The SERVOPACK makes the most of machine performance in the shortest time possible, thus contributing to improving productivity.
1.2
Part Names
This section describes the part names of SGDV SERVOPACK for MECHATROLINK-III communications reference.
SERVOPACK model
Refer to 1.6 SERVOPACK Model Designation .
Nameplate (Found on side of SERVOPACK.)
Indicates the SERVOPACK model and ratings.
CN2 Connector for encoder
Connects the encoder in the servomotor.
Refer to 3.6 Encoder Connection .
CN4 Connector for servomotor
Connects the main circuit cable for servomotor.
Refer to 3.1 Main Circuit Wiring .
CN3 Connector for power supply
Used for main circuit or control power supply input.
Refer to 3.1 Main Circuit Wiring .
M-III
CN6A/CN6B Connectors for MECHATROLINK-
III communications
Connects MECHATROLINKIII -supported devices.
Refer to 3.5 Wiring MECHATROLINKIII Communications .
CN1 Connector for I/O signal
Used for reference input signals and sequence I/O signals.
Refer to 3.2 I/O Signal Connections .
LED indicator (LK1, LK2, CON, RDY, ALM)
LK1, LK2 (green): Lights during MECHATROLINK communications.
CON (green): Lights when the SERVOPACK correctly receives the
CONNECT command.
RDY (green): Lights when the SERVOPACK is
in Servo Ready status without alarm.
ALM (red): Lights when an alarm occurs.
DIP Switches (S1 and S2)
Used to set MECHATROLINK-
III
communications.
Refer to 4.1.1 Setting Switches S1 and S2 .
CN7 Connector for personal computer (USB connector)
Communicates with a personal computer.
Use the connection cable (model: JZSP-CVS06-02-E).
When not in use, cover this connector.
CN5 Connector for external monitor
Used for Connection cable (model: JZSP-CF1S06-A3-E) connected to the analog monitor unit serving as a hub (model:
JUSP-PC001-E) to which a cable specially for the actual analog monitor is connected.
When not in use, cover this connector.
Refer to 1.5 Examples of Servo System Configurations .
1.3 SERVOPACK Ratings and Specifications
1.3
SERVOPACK Ratings and Specifications
This section describes the ratings and specifications of SERVOPACKs.
1.3.1
Ratings
Ratings of SERVOPACKs are as shown below.
SGDV
Continuous Output Current [Arms]
Instantaneous Max. Output Current [Arms]
Main Circuit Power Supply
Control Power Supply
Overvoltage Category
24 VDC
± 15%
1R7
1.7
4.1
48 VDC
± 15%
24 VDC
± 15%
24 VDC ± 15%
I
2R9
2.9
8.6
48 VDC
± 15%
∗ You can use either 24 or 48 VDC for the main circuit power supply. If using a 24-VDC input, the torque-motor speed characteristics of the servomotor will be less than the characteristics of a 48-VDC input. For details, refer to Torque-
Motor Speed Characteristics of the SGMMV servomotor in
S800000 42).
Σ -V Series Product Catalog (Catalog No.: KAEP
1
1-3
1-4
1 Outline
1.3.2 Basic Specifications
1.3.2
Basic Specifications
Basic specifications of SERVOPACKs are shown below.
Drive Method
Feedback
Surrounding Air
Temperature
Storage Temperature
Ambient Humidity
Storage Humidity
Vibration Resistance
Operating
Conditions
Shock Resistance
Protection Class
Sine-wave current drive with PWM control
Encoder: 17-bit (incremental/absolute)
0 ° C to +55 ° C
-20 ° C to +85 ° C
90% RH or less
90% RH or less
4.9 m/s
2
19.6 m/s
2
With no freezing or condensation
Pollution Degree
IP10
2
An environment that satisfies the following conditions.
• Free of corrosive or flammable gases
• Free of exposure to water, oil, or chemicals
• Free of dust, salts, or iron dust
Mounting
Performance
Altitude
Others
Harmonized Standards
1000 m or less
Free of static electricity, strong electromagnetic fields, magnetic fields or exposure to radioactivity
UL508C
EN 55011/group 1, class A, EN 61000-6-2, EN 61800-3, EN 61800-5-1
Base-mounted
Speed Control Range
1:5000 (The lower limit of the speed control range must be lower than the point at which the rated torque does not cause the servomotor to stop.)
Speed
Regulation
*
Load
Regulation
Voltage
Regulation
Temperature
Regulation
Torque Control
Tolerance
(Repeatability)
0% to 100% load: ± 0.01% max. (at rated speed)
Rated voltage ± 10%: 0% (at rated speed)
25 ± 25
± 1%
° C: ± 0.1% max. (at rated speed)
Soft Start Time
Setting
0 to 10 s (Can be set individually for acceleration and deceleration.)
1.3 SERVOPACK Ratings and Specifications
I/O
Signals
Supports SigmaWin+.
Based on the USB 1.1 standard (12 Mbps).
(cont’d)
Number of
Channels
3 ch
Sequence
Input
Sequence
Output
Input
Signals which can be allocated
Output
Signals which can be allocated
Functions
Functions
• Homing deceleration switch (/DEC)
• External latch (/EXT 1)
• Forward run prohibited (P-OT), reverse run prohibited
(N-OT)
• Forward external torque limit (/P-CL), reverse external torque limit (/N-CL)
Signal allocations can be performed, and positive and negative logic can be changed.
Fixed Output Servo alarm (ALM)
Number of
Channels
3 ch
• Positioning completion (/COIN)
• Speed coincidence detection (/V-CMP)
• Rotation detection (/TGON)
• Servo ready (/S-RDY)
• Torque limit detection (/CLT)
• Speed limit detection (/VLT)
• Brake (/BK)
• Warning (/WARN)
• Near (/NEAR)
Signal allocations can be performed, and positive and negative logic can be changed.
Communications
Function
LED Display
Personal Computer
Communications (USB)
MECHATROLINKIII
Communications Setting Switches
ALM (red), RDY (green), LK1 (green), LK2 (green), CON (green)
DIP Switch (S1) Number of pins: Eight pins (Refer to 4.1.1
)
DIP Switch (S2) Number of pins: Four pins (Refer to 4.1.1
)
Analog Monitor
Dynamic Brake (DB)
Regenerative Processing
Overtravel Prevention (OT)
Protective Function
Utility Function
Number of points: 2
Output voltage: ± 10 VDC (linearity effective range ± 8 V)
Output through the analog monitor unit (model: JUSP-PC001-E), the connection cable (model: JZSP-CF1S06-A3-E), and the analog monitor cable
(model: JZSP-CA01-E).
Not supported.
Not supported.
Deceleration to a stop or free run to a stop at P-OT or N-OT
Overcurrent, overvoltage, overload, and so on.
Gain adjustment, alarm history, JOG operation, origin search, and so on.
∗ Speed regulation by load regulation is defined as follows:
Speed regulation =
No-load motor speed Total load motor speed
Rated motor speed
×
100%
M-III
1
1-5
1-6
1 Outline
1.3.3 MECHATROLINKIII Function Specifications
1.3.3
MECHATROLINK-
III
Function Specifications
The following table shows the basic specifications of MECHATROLINK-III.
MECHATROLINKIII
Communication
Function
Communication
Protocol
Station Address
Baud Rate
Transmission Cycle
Number of
Transmission Bytes
Control Method
Reference Method Reference Input
Profile
MECHATROLINK-III
Specifications
03H to EFH (Max. number of stations: 62)
Can be selected by the DIP switch (S1).
100 Mbps
125 μ s, 250 μ s, 500 μ s, 750 μ s, and 1.0 ms to 4.0 ms (increments of 0.5 ms)
16, 32, or 48 bytes per station
Can be selected by the DIP switch (S2).
Position, speed, or torque control with MECHATROLINK-
III communication
MECHATROLINK commands (sequence, motion, data setting/reference, monitoring, or adjustment)
MECHATROLINK-III standard servo profile
MECHATROLINK-II-compatible profile
1.4 SERVOPACK Internal Block Diagrams
1.4
SERVOPACK Internal Block Diagrams
1.4.1
MECHATROLINK-
III
Communication Reference (Model: SGDV-
E21A)
M-III
Servomotor
Main circuit power supply
CN3
L1
L2
+
CN4
U
V
W
M
+12.5 V
Voltage sensor
DC/DC converter
(non
-isolated) +5 V
Gate drive overcurrent protector
Current sensor
CN2
ENC
Control power supply
C1
C2
+
DC/DC converter
(non
-isolated)
+5 V
+3.3 V
ASIC
(PWM control, etc.)
CON LK2 LK1 RDY ALM
CN5 CN7
External monitor
Personal computer
CPU
(Position/speed calculation, etc.)
I/O
I/F
CN1
CN6A
I/O signal
MECHATROLINK-
III communications
CN6B
1
1-7
1-8
1 Outline
1.5
Examples of Servo System Configurations
This section describes examples of basic servo system configuration.
SGDVE21A
SERVOPACK
Molded-case circuit breaker
(MCCB)
Protects the power line by shutting the circuit OFF when overcurrent is detected.
Power supply
Single-phase 100/200 VAC
R T
Encoder cable
Noise filter
Eliminates external noise from the power line.
Non-isolated
AC/DC converter for control power supply
Battery case
(when an absolute
encoder is used.)
Magnetic contactor
Turns the servo
ON and OFF.
Install a surge absorber.
Servomotor main circuit cable
Power supply cable
100/200 VAC
Non-isolated
AC/DC converter
Grounding wire for power supply for main circuit power supply
Brake power supply
∗
Used for a servomotor with a brake.
Magnetic contactor
Turns the brake power supply
ON and OFF.
Install a surge absorber.
M-III
Connect to the
MECHATROLINK-
III
I/O signal cable
Host controller
Connection cable for personal computer
Personal computer
Connection cable for analog monitor unit
Analog monitor unit
Cable for analog monitor
YASKAWA ELECTRIC CORPORATION
SGMMV Servomotor
∗ Use a 24-VDC power supply. (Not included.)
1.6 SERVOPACK Model Designation
1.6
SERVOPACK Model Designation
This section shows SERVOPACK model designation .
SGDV –
1st + 2nd +
3rd digits
4th digit
5th + 6th
digits
7th digit
2R9 E 21 A
8th + 9th +
10th digits
000
11th + 12th
digits
00
13th digit
0
Series
SGDV Σ -V Series
7th digit: Design
Revision Order
1st + 2nd + 3rd digits: Current
1R7
2R9
1.7
2.9
4th digit: Voltage
Code
E
Voltage
48 VDC *
13th digit: Parameter Specification
Code Specification
0 Standard
11
21
5th + 6th digits: Interface Specifications
Code
S1
P1
Interface
Analog voltage reference, rotational servomotor
Pulse train reference, rotational servomotor
MECHATROLINKII communications reference, rotational servomotor
MECHATROLINKIII communications reference, rotational servomotor
11th + 12th digits: Software
Code
00
Specification
Specification
Standard
8th + 9th + 10th digits: Hardware Specifications
Code
000 Standard
Specifications
∗ 24 VDC for the main circuit power supply also can be used.
Note: If the option codes digits 8 to 13 are all zeros, they are omitted.
1
1-9
1-10
1 Outline
1.7
Inspection and Maintenance
This section describes the inspection and maintenance of SERVOPACK.
(1) SERVOPACK Inspection
For inspection and maintenance of the SERVOPACK, follow the inspection procedures in the following table at least once every year. Other routine inspections are not required.
Exterior
Item
Loose Screws
Frequency
At least once a year
Procedure
Check for dust, dirt, and oil on the surfaces.
Check for loose connector screws.
Comments
Clean with compressed air.
Tighten any loose screws.
(2) SERVOPACK’s Parts Replacement Schedule
The electric or electronic parts are subject to deterioration over time. To avoid failure, replace these parts at the frequency indicated.
Refer to the standard replacement period in the following table and contact your Yaskawa representative.
After an examination of the part in question, we will determine whether the parts should be replaced or not.
The parameters of any SERVOPACKs overhauled by Yaskawa are reset to the factory settings before shipping. Be sure to confirm that the parameters are properly set before starting operation.
Smoothing Capacitor
(Aluminum Electrolytic
Capacitor)
Part
Standard Replacement
Period
7 to 8 years
Operating Conditions
• Surrounding Air Temperature: Annual average of
30 ° C
• Load Factor: 80% max.
• Operation Rate: 20 hours/day max.
Note: If the above operating conditions are not used, replacement may be required sooner than the standard replacement period. To extend the life of the parts, reduce the ambient temperature. Contact your Yaskawa representative if you require more-detailed information.
2
SigmaWin+
2.1 SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2 Preparing SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.3 Connecting a PC with SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.4 Starting and Operating the SigmaWin+ . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2.5 Parameters (Pn ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.1 Parameter Classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.2 Notation for Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.5.3 Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2
2-1
2-2
2 SigmaWin+
2.1
SigmaWin+
SigmaWin+ is a software application that can be used to view SERVOPACK status, set parameters, and perform setup tuning.
2.2
Preparing SigmaWin+
Install SigmaWin+ after downloading the software application from the following Yaskawa website.
http://www.e-mechatronics.com.
2.3
Connecting a PC with SigmaWin+
A PC with SigmaWin+ installed can be connected to SERVOPACKs by one of two methods.
Connection Method
Conventional
With a Controller
Description
Use a communications cable to connect one PC with SigmaWin+ installed to one SERVOPACK.
To use SigmaWin+ with a different SERVOPACK, disconnect the cable and reconnect the PC to the other SERVOPACK.
Use a communications cable to connect one PC with SigmaWin+ installed to one controller and then connect the controller to one SERVOPACK.
If using this method, several SERVOPACKs can be connected to the controller at the same time.
For more information on how to connect a PC with SigmaWin+, refer to the SigmaWin+ Online Manual. To view the online manual, use the following procedure.
1.
Turn on the computer.
2.
Double click YE_Applications icon.
3.
Double click MANUAL icon.
4.
Double click SigmaWin+ English Edition Online Manual .
2.4 Starting and Operating the SigmaWin+
2.4
Starting and Operating the SigmaWin+
Use the following procedure to display the main window of the SigmaWin+.
1.
Connect a SERVOPACK to a computer which has SigmaWin+ installed.
For details, refer to the figure provided in 1.5 Examples of Servo System Configurations .
2.
Turn on the SERVOPACK.
3.
Turn on the computer.
4.
Double click the YE_Applications icon.
5.
Double click the SigmaWin+ English Edition icon.
The SigmaWin+ startup window will appear. When the startup of SigmaWin+ has been completed, the
Connect window will appear.
Setup Window
6.
Click Search .
The Search Condition Setting box will appear.
Connect Window
2
Search Condition Setting box
Note: Use the offline mode when running SigmaWin+ without connecting to the SERVOPACK.
7.
Select the Σ V .
2-3
2-4
2 SigmaWin+
8.
Click Search .
A message will appear first to indicate that a search is being carried out, and then the search results will be shown in the Connect window.
MECHA
Note: If the message, "SERVOPACK not found", is shown, refer to the online manual. To view the online manual, refer to 2.3 Connecting a PC with SigmaWin+ .
9.
Select the SERVOPACK to be connected.
10.
Click Connect .
The SigmaWin+ main window will appear.
Note: For details on how to operate SigmaWin+, refer to the online manual for SigmaWin+. Refer to 2.3 Connecting a PC with SigmaWin+ for the procedure to access the Online Manual.
2.5 Parameters (Pn )
2.5
Parameters (Pn
)
This section describes the classifications, methods of notation, and settings for parameters given in this manual.
2.5.1
Parameter Classification
Parameters of the Σ -V Series SERVOPACK are classified into two types of parameters. One type of parameters is required for setting up the basic conditions for operation and the other type is required for tuning parameters that are required to adjust servomotor characteristics.
Classification
Setup Parameters
Tuning Parameters
Meaning
Parameters required for setup.
Parameters for tuning control gain and other parameters.
Display Method
Always displayed (Factory setting: Pn00B.0 = 0)
Set Pn00B.0 to 1.
Setting Method
Set each parameter individually.
There is no need to set each parameter individually.
There are two types of notation used for parameters, one for parameter that requires a value setting (parameter for numeric settings) and one for parameter that requires the selection of a function (parameter for selecting functions).
The notation and settings for both types of parameters are described next.
2.5.2
Notation for Parameters
(1) Parameters for Numeric Settings
The control methods for which the parameters applies.
Speed : Speed control Position : Position control Torque : Torque control
Pn406
Emergency Stop Torque
Setting Range
0% to 800%
Setting Unit
1%
Speed Position Torque
Factory Setting When Enabled
800 After change
Parameter number
Indicates the setting range for the parameter.
Indicates the minimum setting unit for the parameter.
Indicates the parameter setting before shipment.
Indicates when a change to the parameter will be effective.
Classification
Setup
Indicates the parameter classification.
(2) Parameters for Selecting Functions
Pn002
Parameter Meaning n.
0
[Factory setting]
Uses the absolute encoder as an absolute encoder. n.
1
Uses the absolute encoder as an incremental encoder.
Parameter number
When Enabled Classification
After restart
The notation “n.
” indicates a parameter for selecting functions. Each corresponds to the setting value of that digit. The notation shown here means that the third digit is 1.
This section explains the selections for the function.
Setup
2
2-5
2-6
2 SigmaWin+
2.5.3 Setting Parameters
2.5.3
Setting Parameters
There are two ways to set parameters. These are as follows:
• Using the Parameter Editing dialog box
• Using the Online Parameter Editing dialog box
These methods are described below.
(1) Using the Parameter Editing Dialog Box
1.
In the SigmaWin+ main window, click Parameters - Edit Parameters .
The Parameter Editing dialog box will appear.
MECH
A
2.
Select a parameter to edit.
If the parameter cannot be seen in the Parameter Editing dialog box, click the arrows to view the parameter.
MECH
A
2.5 Parameters (Pn )
3.
Click Edit .
The Edit box for the selected parameter will appear.
4.
Change the value of the parameter.
<For parameters for numeric settings>
Enter the value to be set.
<For parameters for selecting functions>
Click the arrow to open the setting list for each digit and select one item in each list.
5.
Click OK .
6.
Click Write .
The new parameter settings will be saved in the SERVOPACK.
This completes the editing of the parameter. If the following window appears, go to step 7.
MECHA
7.
Click OK .
8.
To enable the change in the setting, restart the SERVOPACK.
2
2-7
2 SigmaWin+
2.5.3 Setting Parameters
(2) Using the Online Parameter Editing Dialog Box
• Values edited in the Online Parameter Editing dialog box are immediately changed in the SERVOPACK.
• If the power to the SERVOPACK is turned OFF or the communication between the
SERVOPACK and the SigmaWin+ is interrupted while editing parameters online, the edited values will not be saved in the SERVOPACK.
1.
In the SigmaWin+ main window, click Parameters - Edit Online Parameters .
The Online Parameter Editing dialog box will appears.
MECHA
2-8
2.
Click Setup .
The Set Parameters box will appear.
MECHA
3.
Click one of the Set buttons located on the right of the parameter list.
The Parameters list box will appear.
MECHA
2.5 Parameters (Pn )
4.
Select a parameter to edit, and then click OK .
The Set Parameters box will appear again.
5.
Click OK .
The Online Parameter Editing dialog box will appear again.
6.
Click the setting arrows to change the value of the setting.
If an allowable range is specified, set the value within that range.
The value of the parameter in the SERVOPACK will immediately change to the new value.
2
2-9
3
Wiring and Connection
3.1 Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.1.1 Main Circuit Terminals (CN3, CN4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.1.2 Main Circuit Wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.1.3 Typical Main Circuit Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3.1.4 Power Supply Capacities and Power Losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
3.1.5 Input Power Supply, Molded-case Circuit Breaker, and Fuse . . . . . . . . . . . . . . . . . . . 3-5
3.1.6 Using More Than One SERVOPACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.1.7 General Precautions for Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.2 I/O Signal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.2.1 I/O Signal (CN1) Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.2.2 Example of I/O Signal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
3.3 I/O Signal Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.1 Input Signal Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
3.3.2 Output Signal Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
3.4 Examples of Connection to Host Controller . . . . . . . . . . . . . . . . . . . . . . 3-21
3.4.1 Sequence Input Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-21
3.4.2 Sequence Output Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
3.5 Wiring MECHATROLINKIII Communications . . . . . . . . . . . . . . . . . . . . 3-23
3.6 Encoder Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.6.1 Encoder Signal (CN2) Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.6.2 Encoder Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-24
3.7 Noise Control and Measures for Harmonic Suppression . . . . . . . . . . . . 3-26
3.7.1 Wiring for Noise Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-26
3.7.2 Precautions on Connecting Noise Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-28
3
3-1
3-2
3 Wiring and Connection
3.1.1 Main Circuit Terminals (CN3, CN4)
3.1
Main Circuit Wiring
The names and specifications of the main circuit terminals are given below.
Also this section describes the general precautions for wiring and precautions under special environments.
3.1.1
Main Circuit Terminals (CN3, CN4)
M-III
: Main circuit terminals
Connector
Number
CN3
Terminal
Symbol
L1
L2
C1
C2
CN4
U
V
W
Pin
Number
6
3
5
4
1, 2
1
2
3
4
Name Specification
Main circuit power input terminal (+)
Main circuit power input terminal (-)
Control power input terminal (+)
Control power input terminal (-)
24 VDC ± 15% or 48 VDC ± 15%
24 VDC ± 15%
Ground terminals
Use for connecting the power supply ground terminal.
Servomotor connection terminal
(phase U)
Servomotor connection terminal
(phase V)
Servomotor connection terminal
(phase W)
Use for connecting to the servomotor.
Ground terminals
Use for connecting the servomotor ground terminal.
3.1 Main Circuit Wiring
3.1.2
Main Circuit Wires
Use the following cables for main circuit. These cables are manufactured by YASKAWA Controls Co., Ltd.
Cable
For power supply
For servomotor main circuit
Terminal
Symbols
1R7E
L1, L2, C1, C2, JZSP-CF1G00 -E
SERVOPACK Model: SGDV-
2R9E
U, V, W,
JZSP-CF1M00 -E (For servomotors without brakes)
JZSP-CF1M10 -E (For servomotors with brakes)
JZSP-CF1M20 -E (For servomotors without brakes, flexible type)
JZSP-CF1M30 -E (For servomotors with brakes, flexible type)
If you make cables by yourself, read the following items.
• Wire sizes are selected for three cables per bundle at 40 ° C surrounding air temperature with the rated current.
• Use the withstand voltage wires (for 100 V or more).
• Use the wires whose outside diameter of insulator is 1.85 mm or less.
• If cables are bundled in PVC or metal ducts, take into account the reduction of the allowable current.
• Use a heat-resistant wire under high surrounding air or panel temperatures.
• The length of cables for power supply is 10 m max., and the length of cables for servomotor main circuit is 50 m max.
Cable
Connector
Contact
CN3 for power supply
For main circuit power supply
(L1, L2, )
For control circuit power supply
(C1, C2, )
CN4 for servomotor main circuit
Connector
(SERVOPACK side)
Contact
(SERVOPACK side)
Connector
(servomotor side) without brake with brake
Contact
(servomotor side)
Power line for servomotor main circuit
(U, V, W, brake power supply, )
SERVOPACK Model: SGDV-
1R7E 2R9E
43025-0600 (Made by Molex
Japan Co., Ltd.)
43030-0001 (Made by Molex
Japan Co., Ltd.)
UL1007, AWG20
UL1007, AWG20
43025-0400 (Made by Molex
Japan Co., Ltd.)
43030-0001 (Made by Molex
Japan Co., Ltd.)
43020-0401 (Made by Molex
Japan Co., Ltd.)
43020-0601 (Made by Molex
Japan Co., Ltd.)
43031-0001 (Made by Molex
Japan Co., Ltd.)
UL1007, AWG20
Remarks
6 poles
–
Rated voltage
300 V,
Rated temperature
80 ° C
Rated voltage
300 V,
Rated temperature
80 ° C
4 poles
–
4 poles
6 poles
–
Rated voltage
300 V,
Rated temperature
80 ° C
3
3-3
3-4
3 Wiring and Connection
3.1.3 Typical Main Circuit Wiring Examples
3.1.3
Typical Main Circuit Wiring Examples
Note the following points when designing the power ON sequence.
• Design the power ON sequence so that main power is turned OFF when a servo alarm signal (ALM) is output.
• The ALM signal is output for a maximum of five seconds when the control power is turned ON. Take this into consideration when designing the power ON sequence. Design the sequence so the ALM signal is activated and the alarm detection relay (1Ry) is turned OFF to stop the main circuit’s power supply to the SERVOPACK.
Control power supply 5.0 s max.
ALM signal
• Select the power supply specifications for the parts in accordance with the input power supply.
• When turning ON the control power supply and the main circuit power supply, turn them ON at the same time or turn the main circuit power supply after the control power supply. When turning OFF the power supplies, first turn the power for the main circuit OFF and then turn OFF the control power supply.
• Provide separate AC/DC power supplies for the main circuits and for controls.
• Power supplies must have double or reinforced insulation that conforms to safety standards.
• Do not connect devices (such as motors or solenoids) that greatly change the load or devices (such as electromagnetic switches) that generate surge voltages to the controller power line.
Failure to observe this caution may result in deterioration of the internal elements or a blown fuse.
The typical main circuit wiring examples are shown below.
WARNING
• Voltage remains in the SERVOPACK even after the power supply is turned OFF. To prevent electric shock, do not touch the input terminals for the main circuit power supply or those for the control power supply.
Before wiring or inspections, confirm that the SERVOPACK has completely discharged.
1QF
R T
1FLT
1KM
Non-isolated AC/DC converter for main circuit power supply
CN3
L1
L2
C1
C2
Non-isolated AC/DC converter for control power supply
1Ry
(For servo alarm display)
1PL
Main power supply ON
Main power supply OFF
1Ry
1KM
SERVOPACK
SGDV
CN4
U
V
W
CN1
4
5
ALM
COM_SG
MECHA
M
ENC
1Ry
1D
+24 V
0 V
1KM 1SA
1QF
1FLT
1KM
: Molded-case circuit breaker
: Noise filter
: Magnetic contactor (for main circuit power supply)
1Ry
1PL
1SA
1D
: Relay
: Indicator lamp
: Surge absorber
: Flywheel diode
3.1 Main Circuit Wiring
3.1.4
Power Supply Capacities and Power Losses
The following table shows the SERVOPACK’s power supply capacities and power losses.
Main
Circuit
Power
Supply
24 VDC
48 VDC
Maximum
Applicable
Servomotor
Capacity
[W]
11
30
11
30
SERVOPACK
Model
SGDV-
Power Supply
Capacity per
SERVOPACK
[W]
1R7E
2R9E
1R7E
2R9E
108
165
169
411
Output
Current
[Arms]
1.7
2.9
1.7
2.9
Main
Circuit
Power
Loss
[W]
3.4
6.9
3.4
6.9
Control
Circuit
Power
Loss [W]
7.2
Total
Power
Loss [W]
3.1.5
Input Power Supply, Molded-case Circuit Breaker, and Fuse
Use input power supplies that meet the following conditions.
• The main circuit power supply must be a 24-VDC or a 48-VDC power supply.
• The control circuit power supply must be a 24-VDC power supply.
• The main circuit power supply and the control power supply must be two separate input power supplies.
• Power supplies must have double or reinforced insulation that conforms to safety standards.
When choosing molded-case circuit breakers and fuses for input power supplies on the AC side, confirm the specifications of the input power supplies and refer to this table.
Also, choose molded-case circuit breakers and fuses that meet the following cutoff characteristics.
Cutoff characteristics (25 ° C): ⋅ 300% of the rated load input current, five seconds min.
⋅ Does not cut off at the inrush current value of the power supply.
SERVOPACK
Model
SGDV-
1R7E
2R9E
Main
Circuit
Power
Supply
24 VDC
48 VDC
24 VDC
48 VDC
Input Current Capacity
Max.
Applicable
Servomotor
Capacity
[W]
Power Supply
Capacity per
SERVOPACK
*1
[W]
Main Circuit
Continuous
Rated
[A]
Instantaneous
Max.
[A]
Control
Circuit
*2
[A]
100
V
200
V
Rated Voltage
Fuse
[V]
MCCB
[V]
400
V
100
V
200
V
400
V
11
30
108
169
165
411
2.0
1.0
3.5
2.0
5.5
4.5
8.5
10.5
0.3
250 600 240 480
∗1.
Values with instantaneous maximum load.
∗2.
Values with rated load.
10.6
14.1
10.6
14.1
3
3-5
3-6
3 Wiring and Connection
3.1.6 Using More Than One SERVOPACK
3.1.6
Using More Than One SERVOPACK
This section shows an example of the wiring and the precautions when more than one SERVOPACK is used.
(1) Wiring Example
The alarm output (ALM) of each SERVOPACK operates a separate alarm detection relay (1Ry, 2Ry or 3Ry).
When the alarm occurs, the ALM output signal transistor is turned OFF.
R T
MECHA
1QF
1FLT
1KM
Non-isolated AC/DC converter for main circuit power supply
Non-isolated AC/DC converter for control power supply
Relay terminal
Relay terminal
CN3
L1
L2
SERVOPACK
C1
C2
Servomotor
M
CN1
4 ALM
1Ry
+24V
1Ry
(For servo alarm display)
2Ry
1PL
3Ry
Main power supply ON
Main power supply OFF
1Ry 2Ry 3Ry
1KM
Relay terminal
Relay terminal
5 COM_SG
1D
0V
CN3
SERVOPACK
L1
L2
Servomotor
M
C1
C2
CN1
4 ALM
2Ry
+24V
1KM
1SA
5 COM_SG
2D
0V
CN3
L1
L2
SERVOPACK
Servomotor
M
1QF : Molded-case circuit breaker
1FLT : Noise filter
1KM : Magnetic contactor (for main circuit power supply)
1Ry : Relay
2Ry
3Ry
1PL
1SA
1D
2D
3D
: Relay
: Relay
: Indicator lamp
: Surge absorber
: Flywheel diode
: Flywheel diode
: Flywheel diode
C1
C2
CN1
4
5
ALM
COM_SG
3D
0V
3Ry
+24V
(2) Precautions
• Multiple SERVOPACKs can share a single molded-case circuit breaker (1QF) or noise filter. Always select a molded-case circuit breaker or noise filter that has enough capacity for the total power supply capacity
(load conditions) of the SERVOPACKs.
• The same ground, COM_SG, is used for all four sequence output signals for a Σ -series SERVOPACK with a
DC power input. If the alarm outputs from the SERVOPACKs are connected in series, it will not be possible to receive the output signals normally when an alarm occurs.
3.1 Main Circuit Wiring
3.1.7
General Precautions for Wiring
• Always use a molded-case circuit breaker (1QF) or a fuse to protect the servo system from intersystem faults.
• Install a ground fault detector.
The SERVOPACK does not have a built-in protective circuit for grounding.
To configure a safer system, install a ground fault detector against overloads and short-circuiting, or install a ground fault detector combined with a molded-case circuit breaker.
• Do not turn the power ON and OFF more than necessary.
• Do not use the SERVOPACK for applications that require the power to turn ON and
OFF frequently. Such applications will cause elements in the SERVOPACK to deteriorate.
• As a guideline, at least one hour should be allowed between the power being turned ON and OFF once actual operation has been started.
To ensure safe, stable application of the servo system, observe the following precautions when wiring.
• Use the connection cables specified in Σ -V Series Product Catalog (Catalog No.: KAEP S800000 42).
Design and arrange the system so that each cable will be as short as possible.
• Use shielded twisted-pair cables or screened unshielded twisted-pair cables for I/O signal cables and encoder cables.
• The maximum wiring length is 3 m for I/O signal cables, 50 m for servomotor main circuit cables and encoder cables, and 10 m for power supply cables.
• Observe the following precautions when wiring the ground.
• Use a cable as thick as possible.
• Ground to a ground resistance of 100 Ω or less.
• Be sure to ground at only one point.
• Ground the servomotor directly if the servomotor is insulated from the machine.
• The signal cable conductors are as thin as 0.2 mm 2 tension.
or 0.3 mm 2 . Do not impose excessive bending force or
Precaution When Wiring a Magnetic Contactor on the DC Side of the Main Circuit Power
Supply
To shut OFF the main circuit power supply to the SERVOPACK, we recommend that you do so on the AC side of the AC/DC power supply. To shut OFF the power supply on the DC side, connect a capacitor (1C) with the following specifications after the magnetic contactor (1KM). Wire the capacitor (1C) as close to the SER-
VOPACK as possible.
Main
Circuit
Power
Supply
24 VDC
48 VDC
SERVOPACK
Model
SGDV-1R7E
SGDV-2R9E
SGDV-1R7E
SGDV-2R9E
1A
1A
1A
1A
Recommended Capacitor Specifications per SERVOPACK
Recommended Capacitor
Rated
Voltage
Rated Capacitance
Model
* Manufacturer
50 VDC min.
100 VDC min.
3,000 μ F to 3,900 μ F UPJ1H152MHD × 2
3,600 μ F to 4,700 μ F UPJ1H182MHD × 2
2,700 μ F to 3,900 μ F LGU2A272MELB
3,300 μ F to 4,700 μ F LGU2A332MELB
Nichicon
Corporation
∗ Use the capacitor given above or the equivalent.
3
3-7
3-8
3 Wiring and Connection
3.1.7 General Precautions for Wiring
• The larger the capacitance of the capacitor (1C), the more charging current will flow when the power supply is turned ON. Select an AC/DC power supply so that there will not be insufficient current. Consult the manufacturer of the power supply for the output current capacity of the power supply.
• If you connect a capacitor (1C), more time may be required until the servo ready output signal (/S-RDY) turns ON. Consider this when you design the operation sequence.
Also, more time will be required to discharge after the main circuit power supply is shut OFF. Be careful of electric shock.
For the recommended AC/DC power supplies, refer to the Σ -V Series Product Catalog
(Catalog No.: KAEP S800000 42).
A wiring example is provided below for connecting a magnetic contactor on the DC side of the main circuit power supply.
1QF
R T
1FLT
Insulated AC/DC converter for main circuit power supply 1KM
+
1C
Insulated AC/DC converter for control power supply
1Ry
(For servo alarm display)
Main circuit power supply
ON
Main circuit power supply
OFF
1Ry
1PL
1KM
CN3
L1
L2
C1
C2
SGDV
SERVOPACK
CN4
U
V
W
M
ENC
CN1
4 ALM
1Ry
+24 V
5 COM_SG
1D
1KM 1SA
1QF: Molded-case circuit breaker
1FLT: Noise filter
1KM: Magnetic contactor for main circuit power supply
1C: Capacitor (for main circuit power supply)
1Ry: Relay
1PL: Indicator lamp
1SA: Surge absorber
1D: Flywheel diode
0 V
3.2 I/O Signal Connections
3.2
I/O Signal Connections
This section describes the names and functions of I/O signals (CN1). Also connection examples by control method are shown.
3.2.1
I/O Signal (CN1) Names and Functions
The following table shows the names and functions of I/O signals (CN1).
(1) Input Signals
Signal Pin No.
Name Function
Reference
Section
/DEC
P-OT
N-OT
7
3
8
Homing deceleration switch signal
Forward run prohibited,
Reverse run prohibited
Connects the deceleration limit switch for homing.
With overtravel prevention: Stops servomotor when movable part travels beyond the allowable range of motion.
−
4.3.1
/EXT 1
Can be allocated
+24VIN 2
External latch signal 1
Control power supply for sequence signal
Connects the external signals that latch the current feedback pulse counter.
Note: To use this signal, allocate it to CN1-7.
Control power supply input for sequence signals
Allowable voltage fluctuation range: 11 to 25 V
Note: The 24 VDC power supply is not included.
−
3.4.1
Note 1. The functions allocated to /DEC, P-OT, and N-OT input signals can be changed by using the parameters. For details, refer to 3.3.1 Input Signal Allocations .
2. To use /EXT1, allocate it to CN1-7. For details, refer to 3.3.1 Input Signal Allocations .
3. If the Forward run prohibited/ Reverse run prohibited function is used, the SERVOPACK is stopped by software controls, not by electrical or mechanical means. If the application does not satisfy the safety requirements, add an external circuit for safety reasons as required.
(2) Output Signals
Signal Pin No.
Name Function
Reference
Section
ALM 4
Servo alarm output signal
Turns OFF when an error is detected.
−
/BK
(/SO1)
/SO2
/SO3
11
10
9
Brake interlock signal
General-purpose output signal
Controls the brake. The brake is released when the signal turns ON.
Allocation can be changed to general-purpose output signals
(/SO1).
Used for general-purpose output.
Note: Set the parameter to allocate a function.
4.3.2
−
/COIN
/V-CMP
/TGON
/S-RDY
/CLT
/VLT
/WARN
/NEAR
Can be allocated
COM_SG 5
Positioning completion
Speed coincidence detection
Rotation detection
Servo ready
Torque limit
Speed limit detection
Warning
Near
Common output ground
The allocation of an output signal to a pin can be changed in accordance with the function required.
Common output ground for the output signals (/SO1 to /
SO3).
−
−
FG 1 Frame ground Connects the shielded wire from the I/O signal cable.
−
Note: The functions allocated to /SO1 to /SO3 output signals can be changed by using the parameters. For details, refer to
3.3.2 Output Signal Allocations.
3
3-9
3-10
3 Wiring and Connection
3.2.2 Example of I/O Signal Connections
3.2.2
Example of I/O Signal Connections
The following diagram shows a typical connection example.
Control power supply for sequence signal
Forward run prohibited
(Prohibited when OFF)
Reverse run prohibited
(Prohibited when OFF)
Homing deceleration switch
(Decelerated when ON)
+24V
∗
+24VIN
P-OT
CN1
2
3
3.3 k
Ω
N-OT
/DEC
8
7
SERVOPACK
Photocoupler output
Max. operating voltage: 30 VDC
Max. output current: 50 mA DC
MECHA
4 ALM
Servo alarm output
(OFF for an alarm)
11
10
/BK (SO1)
Brake
(Brake released when ON)
/SO2
9
5
/SO3
COM_SG
1 FG
∗ The 24-VDC power supply is not included. Use a 24-VDC power supply with double insulation or reinforced insulation.
Note: The functions allocated to the input signals /DEC, P-OT, N-OT and the output signals /SO1, /SO2, and /SO3 can be changed by using the parameters. Refer to 3.3.1 Input Signal Allocations and 3.3.2 Output Signal Allocations .
3.3 I/O Signal Allocations
3.3
I/O Signal Allocations
This section describes the I/O signal allocations.
3.3.1
Input Signal Allocations
• Inverting the polarity of the forward run prohibited and reverse run prohibited signals from the factory setting will prevent the overtravel function from working in case of signal line disconnections or other failures.
If this setting is absolutely necessary, check the operation and confirm that there are no safety problems.
• When two or more signals are allocated to the same input circuit, input signal level is valid for all allocated signals, resulting in an unexpected machine operation.
Input signals are allocated as shown in the following table.
Refer to the Interpreting the Input Signal Allocation Tables and change the allocations accordingly.
<Interpreting the Input Signal Allocation Tables>
Level at which input signal allocations are valid.
The parameter set values to be used are shown.
Signals are allocated to CN1 pins according to the selected set values.
Values in cells in bold lines are the factory settings.
Input Signal Names and Parameters
Validity
Level
Input
Signal
CN1 Pin Numbers
Forward Run Prohibited
Pn50A.3
H
L
P-OT
/P-OT
7
0
9
3 8
1 2 to 6
A B to F
Connection Not
Required
(SERVOPACK judges the connection)
Always
ON
Always
OFF
7 8
If always ON (7) or always OFF (8) is set, signals will be processed in the SERVOPACK, which will eliminate the need for wiring changes.
Input Signal Names and
Parameters
Validity
Level
Input
Signal
Forward Run Prohibited
Pn50A.3
Reverse Run Prohibited
Pn50B.0
Forward External Torque
Limit
Pn50B.2
H
L
H
L
L
H
P-OT
/P-OT
N-OT
/N-OT
/P-CL
P-CL
0
9
0
9
0
9
CN1 Pin Numbers
7 3 8
Connection Not
Required
(SERVOPACK judges the connection)
Always
ON
Always
OFF
1 2 to 6
A B to F
1 2 to 6
A B to F
1 2 to 6
A B to F
7
7
7
8
8
8
3
3-11
3-12
3 Wiring and Connection
3.3.1 Input Signal Allocations
Input Signal Names and
Parameters
Validity
Level
Reserve External Torque
Limit
Pn50B.3
Homing Deceleration LS
Pn511.0
External Latch Signal 1
Pn511.1
L
H
L
H
L
H
Input
Signal
CN1 Pin Numbers
7 3 8
(cont’d)
Connection Not
Required
(SERVOPACK judges the connection)
Always
ON
Always
OFF
/N-CL
N-CL
0
9
1
A
2 to 6
B to F
/DEC 0 1 2 to 6
DEC 9 A B to F
/EXT1 0 to 6 – –
EXT1 9 to F – –
7
7
7
8
8
8
Example of Changing Input Signal Allocations
The procedure to set the forward run prohibited signal (P-OT) allocated CN1-3 to “enable forward drive” and instead allocate the forward external torque limit signal (P-CL) to CN1-3 is shown below.
<Parameter Changes>
• Pn50A is changed from n.1881 to n.8881.
• Pn50B is changed from n.8882 to n.8182.
1.
In the SigmaWin+ main window, click Parameters - Edit Parameters .
The Parameter Editing dialog box will appear.
ME-
CHA
3.3 I/O Signal Allocations
2.
Select Pn50A .
If Pn50A cannot be seen in the Parameter Editing dialog box, click the arrows button to view the parameter.
ME-
CHA
3.
Click Edit .
The Edit box for Pn50A will appear.
ME-
CHA
3
3-13
3-14
3 Wiring and Connection
3.3.1 Input Signal Allocations
4.
For the 3rd digit, select 8: Forward run allowed in the P-OT Signal Mapping list.
ME-
CHA
5.
Click OK .
The Edit box will close, and Parameter Editing dialog box will appear again.
6.
Select Pn50B .
If Pn50B cannot be seen in the Parameter Editing dialog box, click the arrows button to view the parameter.
ME-
CHA
7.
Click Edit .
The Edit box for Pn50B will appear.
ME-
CHA
3.3 I/O Signal Allocations
8.
For the 2nd digit, select 1: ON when CN1-3 input signal is ON (L-level) in the /P-CL Signal
Mapping list.
ME-
CHA
3
3-15
3 Wiring and Connection
3.3.1 Input Signal Allocations
9.
Click OK .
The Edit box will close, and the Parameter Editing dialog box will appear again.
ME-
CHA
10.
Click Write .
The following window will appear after the new parameter setting has been saved in the SERVOPACK.
ME-
CHA
3-16
11.
Click OK .
12.
To enable the change in the setting, restart the SERVOPACK.
3.3 I/O Signal Allocations
3.3.2
Output Signal Allocations
• The signals not detected are considered as " Invalid.
" For example, Positioning Completion (/COIN) signal in speed control is " Invalid.
"
• Inverting the polarity of the brake signal (/BK), i.e. positive logic, will prevent the holding brake from working in case of its signal line disconnection.
If this setting is absolutely necessary, check the operation and confirm that there are no safety problems.
• When two or more signals are allocated to the same output circuit, a signal is output with OR logic circuit.
Output signals are allocated as shown in the following table.
Refer to the Interpreting the Output Signal Allocation Tables and change the allocations accordingly.
<Interpreting the Output Signal Allocation Tables>
MECHA
The parameter set values to be used are shown.
Signals are allocated to CN1 pins according to the selected set values.
Values in cells in bold lines are the factory settings.
Output Signal Names and Parameters
Brake
Pn50F.2
Output Signal
/BK
11
1
CN1 Pin Numbers
10
2
Output Signal Names and Parameters
Positioning Completion
Pn50E.0
Speed Coincidence
Detection
Pn50E.1
Rotation Detection
Pn50E.2
Servo Ready
Pn50E.3
Torque Limit Detection
Pn50F.0
Speed Limit Detection
Pn50F.1
Brake
Pn50F.2
Warning
Pn50F.3
Near
Pn510.0
Pn512.0=1
Pn512.1=1
Pn512.2=1
Output Signal
/COIN
/V-CMP
/TGON
/S-RDY
/CLT
/VLT
/BK
/WARN
/NEAR
11
1
1
1
1
1
1
1
1
1
CN1 Pin Numbers
10
2
2
2
2
2
2
2
2
2
Polarity inversion of CN1-11
Polarity inversion of CN1-10
Polarity inversion of CN1-9
9
3
9
3
3
3
3
3
3
3
3
3
Invalid
㧔 not use 㧕
0
Invalid
(not use)
0
0
0
0
0
0
0
0
0
0
(Not invert at factory setting)
3
3-17
3-18
3 Wiring and Connection
3.3.2 Output Signal Allocations
Example of Changing Output Signal Allocations
The procedure to set the position completion signal (/COIN) that was previously disabled is allocated to CN1-
10 is shown below.
<Parameter Changes>
• Pn50E is changed from n.0000 to n.0002.
1.
In the SigmaWin+ main window, click Parameters - Edit Parameters .
The Parameter Editing dialog box will appear.
ME-
CHA
3.3 I/O Signal Allocations
2.
Select Pn50E .
If Pn50E cannot be seen in the Parameter Editing dialog box, click the arrows button to view the parameter.
ME-
CHA
3.
Click Edit .
The Edit box for Pn50E will appear.
ME-
CHA
3
3-19
3-20
3 Wiring and Connection
3.3.2 Output Signal Allocations
4.
For the zero digit, select 2: Outputs the signal from CN1-10 output terminal in the
Positioning Completion Signal Mapping (/COIN) list.
ME-
CHA
5.
Click OK .
The Edit box will close, and the Parameter Editing dialog box will appear again.
6.
Click Write .
The following window will appear after the new parameter setting has been saved in the SERVOPACK.
ME-
CHA
7.
Click OK .
8.
To enable the change in the setting, restart the SERVOPACK.
3.4 Examples of Connection to Host Controller
3.4
Examples of Connection to Host Controller
This section shows examples of SERVOPACK I/O signal connection to the host controller.
3.4.1
Sequence Input Circuit
(1) Photocoupler Input Circuit
CN1 connector terminals 2, 3, 7, 8 are explained below.
The sequence input circuit interface is connected through a relay or open-collector transistor circuit. When connecting through a relay, use a low-current relay. If a low-current relay is not used, a faulty contact may result.
Open-collector Circuit Example
24 VDC
Relay Circuit Example
SERVOPACK
+24 VIN
3.3 k
Ω
/DEC, etc.
24 VDC
SERVOPACK
+24 VIN
3.3 k
Ω
/DEC, etc.
Note: The 24 VDC external power supply capacity must be 50 mA minimum.
The SERVOPACK’s input circuit uses bidirectional photocoupler. Select either the sink circuit or the source circuit according to the specifications required for each machine.
Note:
•
The connection example in 3.2.2
shows sink circuits.
• The ON/OFF polarity differs between when a sink circuit is connected and when a source circuit is connected.
Sink Circuit Source Circuit
24 V
+
− SERVOPACK input
24 V
+
− SERVOPACK input
Signal
ON
OFF
Input Signal Polarities
Level
Voltage
Level
Low (L) level
High (H) level
0 V
24 V
Contact
Close
Open
Signal
ON
OFF
Input Signal Polarities
Level
Voltage
Level
High (H) level
Low (L) level
24 V
0 V
Contact
Close
Open
3
3-21
3-22
3 Wiring and Connection
3.4.2 Sequence Output Circuit
3.4.2
Sequence Output Circuit
The signal output circuit from the SERVOPACK is described below.
Incorrect wiring or incorrect voltage application to the output circuit may cause short-circuit.
If a short-circuit occurs as a result of any of these causes, the holding brake will not work. This could damage the machine or cause an accident resulting in death or injury.
(1) Photocoupler Output Circuit
Photocoupler output circuits are used for servo alarm (ALM) and other sequence output signal circuits. Connect a photocoupler output circuit through a relay or line receiver circuit.
Relay Circuit Example
SERVOPACK
5 to 24 VDC
Relay
Line Receiver Circuit Example
SERVOPACK
5 to 12 VDC
0 V
Note: The maximum allowable voltage and the allowable range of current capacity for photocoupler output circuits are as follows.
• Voltage: 30 VDC
• Current: 5 to 50 mA DC
3.5 Wiring MECHATROLINKIII Communications
3.5
Wiring MECHATROLINK-
III
Communications
The following diagram shows an example of connections between a host controller and a SERVOPACK using.
MECHATROLINK-III communications cables (CN6A, CN6B).
DC24V
DC 0V
MP2300
YASKAWA
RDY
ALM
TX
SVC-01
RUN ERR
RUN
ERR
BAT
LK1 LK2
STOP
SUP
INT
CNFG
MON
TEST
ࠉ SW1
OFF
ࠉ
ON
MI / II
M/S
OFF ON
BATTERY
MECHATROLINK
L1
L2 Ln
M-III
Note: The length of the cable between stations (L1, L2 ... Ln) must be 50 m maximum.
For removing the MECHATROLINK-III communications cable connectors from the SERVOPACK, refer to the following procedure.
Slide the lock injector of the connector to the SERVOPACK side to unlock and remove the MECHATROLINK-III communications cable connectors.
SERVOPACK
1. Slide the lock injector to
the SERVOPACK side.
M-III
Lock injector
2. Remove the connector while the lock
injector is slid to the SERVOPACK
side.
Note: The MECHATROLINK-III communications cable connector may be damaged if it is removed without being unlocking.
3
3-23
3-24
3 Wiring and Connection
3.6.1 Encoder Signal (CN2) Names and Functions
3.6
Encoder Connection
This section describes the encoder signal (CN2) names, functions, and connection examples.
3.6.1
Encoder Signal (CN2) Names and Functions
The following table shows the names and functions of encoder signals (CN2).
Signal Name
PG 5 V
PG 0 V
(BAT (+))*
(BAT (-))*
PS
/PS
Shield
3
4
1
2
5
6
Shell
Pin No.
Function
Encoder power supply +5 V
Encoder power supply 0 V
Battery (+)
Battery (-)
Serial data (+)
Serial data (-)
–
∗ It is not necessary to connect these pins to the SERVOPACK.
3.6.2
Encoder Connection Examples
The following diagrams show connection examples of the encoder and the SERVOPACK.
(1) Using as an Incremental Encoder
SERVOPACK
MECHA
Incremental encoder
∗
PS
/PS
CN2
5
6
ENC
PG5V
PG0V
1
2
(Shell) Shielded wire
Connector shell
∗ : represents shielded twisted-pair wires.
3.6 Encoder Connection
(2) Using as an Absolute Encoder
SERVOPACK
Absolute encoder
ENC
∗
1
PS
/PS
CN2
5
6
Output line-driver SN75ALS174 or the equivalent
PG5 V
PG0 V
1
2
MECHA
(Shell)
Battery
BAT +
∗
2
BAT -
∗ 2
3
4
Connector shell
∗1.
: represents shielded twisted-pair wires.
∗2.
When using an absolute encoder, provide power by installing an encoder cable with a JUSP-BA01-E Battery Case.
3
3-25
3-26
3 Wiring and Connection
3.7.1 Wiring for Noise Control
3.7
Noise Control and Measures for Harmonic Suppression
This section describes the wiring for noise control and the DC reactor for harmonic suppression.
3.7.1
Wiring for Noise Control
• Because the SERVOPACK is designed as an industrial device, it provides no mechanism to prevent noise interference.
• The SERVOPACK uses high-speed switching elements in the main circuit. Therefore peripheral devices may receive switching noise. If the equipment is to be used near private houses or if radio interference is a problem, take countermeasures against noise.
• If installation conditions by the EMC directive must be met, refer to DC Power Input Σ -
V Series User's Manual Setup Rotational Motor (Manual No.: SIEP S800000 80).
The SERVOPACK uses microprocessors. Therefore it may receive switching noise from peripheral devices.
To prevent the noise from the SERVOPACK or the peripheral devices from causing a malfunction of any one of these devices, take the following precautions against noise as required.
• Position the input reference device and noise filter as close to the SERVOPACK as possible.
• Always install a surge absorber in the relay, solenoid and electromagnetic contactor coils.
• Do not bundle or run the servomotor main circuit cables together with the I/O signal cables or the encoder cables in the same duct. Keep the servomotor main circuit cables separated from the I/O signal cables and encoder cables by at least 30 cm.
• Do not share the power supply with an electric welder or electrical discharge machine. When the SERVO-
PACK is placed near a high-frequency generator, install a noise filter on the input side of the power supply cables. As for the wiring of noise filter, refer to (1) Noise Filter shown below.
• Take the grounding measures correctly. As for the grounding, refer to (2) Correct Grounding.
3.7 Noise Control and Measures for Harmonic Suppression
(1) Noise Filter
The SERVOPACK has a built-in microprocessor (CPU), so protect it from external noise as much as possible by installing a noise filter in the appropriate place.
The following is an example of wiring for noise control.
Noise filter
*3
AC power supply
2.0 mm 2 min.
Non-isolated AC/DC converter for main circuit power supply
CN3
SERVOPACK
L1
CN4
U
L2
Non-isolated AC/DC converter for control power supply
C1
V
W
C2
CN2
2.0 mm 2 min.
2.0 mm 2 min.
CN1
M
(FG)
ENC
*2
Noise filter
*3
*2
AC/DC converter
*2
Operation relay sequence
Signal generation circuit (not included)
2.0 mm 2 min.
0.5 mm 2
(Ground plate)
*1
Ground: Ground to an independent ground
∗1.
For ground wires connected to the ground plate, use a thick wire (preferably, plain stitch cooper wire).
∗2.
should be twisted-pair wires.
∗3.
When using a noise filter, follow the precautions in 3.7.2 Precautions on Connecting Noise Filter .
(2) Correct Grounding
Take the following grounding measures to prevent the malfunction due to noise.
Grounding the Motor Frame
Always connect servomotor frame terminal FG to the SERVOPACK ground terminal . Also be sure to ground the ground terminal .
If the servomotor is grounded via the machine, a switching noise current will flow from the SERVOPACK main circuit through servomotor stray capacitance. The above grounding is required to prevent the adverse effects of switching noise.
Noise on the I/O Signal Cable
If the I/O signal cable receives noise, ground the 0 V line (SG) of the I/O signal cable. If the servomotor main circuit cable is accommodated in a metal conduit, ground the conduit and its junction box. For all grounding, ground at one point only.
3
3-27
3-28
3 Wiring and Connection
3.7.2 Precautions on Connecting Noise Filter
3.7.2
Precautions on Connecting Noise Filter
This section describes the precautions on installing a noise filter.
(1) Noise Filter Brake Power Supply
If using a servomotor with a holding brake, use the following noise filter on the brake power supply input.
Model: FN2070-6/07 (Manufactured by SCHAFFNER Electronic.)
(2) Precautions on Using Noise Filters
Always observe the following installation and wiring instructions.
Some noise filters have large leakage currents. The grounding measures taken also affects the extent of the leakage current. If necessary, select an appropriate leakage current detector or leakage current breaker taking into account the grounding measures that are used and leakage current from the noise filter. Contact the manufacturer of the noise filter for details.
Do not put the input and output lines in the same duct or bundle them together.
Incorrect Correct
Noise
Filter
Ground plate Ground plate
Noise
Filter
Noise
Filter
Noise
Filter
Ground plate Ground plate
Separate these circuits.
Separate the noise filter ground wire from the output lines.
Do not accommodate the noise filter ground wire, output lines and other signal lines in the same duct or bundle them together.
Incorrect Correct
Noise
Filter
Noise
Filter
The ground wire can be close to input lines.
Ground plate Ground plate
3.7 Noise Control and Measures for Harmonic Suppression
Connect the noise filter ground wire directly to the ground plate.
Do not connect the noise filter ground wire to other ground wires.
Incorrect Correct
Noise
Filter
SERVOPACK SERVOPACK
Noise
Filter
SERVOPACK SERVOPACK
Shielded ground wire
Ground plate Ground plate
If a noise filter is located inside a control panel, first connect the noise filter ground wire and the ground wires from other devices inside the control panel to the ground plate for the control panel, then ground the plates.
Noise
Filter
Control Panel
AC/DC converter
SERVOPACK
SERVOPACK
Ground
Ground plate
3
3-29
4
Operation
4.1 MECHATROLINK-
III
Communications Settings . . . . . . . . . . . . . . . . . . . . 4-3
4.1.1 Setting Switches S1 and S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.2 MECHATROLINK-
III
Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4.3 Basic Functions Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.1 Servomotor Rotation Direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
4.3.2 Overtravel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.3.3 Software Limit Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
4.3.4 Holding Brakes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.3.5 Stopping Servomotors after SV_OFF Command or Alarm Occurrence . . . . . . . . . . 4-15
4.3.6 Setting Motor Overload Detection Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
4.4 Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4.4.1 Inspection and Checking before Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4.4.2 Trial Operation via MECHATROLINKIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
4.4.3 Electronic Gear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
4.5 Test Without Motor Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
4.5.1 Motor Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
4.5.2 Motor Position and Speed Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4.5.3 Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
4.6 Limiting Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
4.6.1 Internal Torque Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
4.6.2 External Torque Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
4.6.3 Checking Output Torque Limiting during Operation . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
4.7 Absolute Encoders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
4.7.1 Connecting the Absolute Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28
4.7.2 Absolute Data Request (SENS ON Command) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
4.7.3 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
4.7.4 Absolute Encoder Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
4.7.5 Multiturn Limit Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35
4.7.6 Multiturn Limit Disagreement Alarm (A.CC0) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
4.7.7 Absolute Encoder Origin Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-39
4
4-1
4-2
4 Operation
4.8 Other Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.8.1 Servo Alarm Output Signal (ALM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.8.2 Warning Output Signal (/WARN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
4.8.3 Rotation Detection Output Signal (/TGON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
4.8.4 Servo Ready Output Signal (/S-RDY) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
4.8.5 Speed Coincidence Output Signal (/V-CMP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-42
4.8.6 Positioning Completed Output Signal (/COIN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
4.8.7 Positioning Near Output Signal (/NEAR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
4.8.8 Speed Limit Detection Signal (/VLT) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
4.1 MECHATROLINKIII Communications Settings
4.1
MECHATROLINK-
III
Communications Settings
This section describes the switch settings necessary for MECHATROLINK-III communications.
4.1.1
Setting Switches S1 and S2
The S2 DIP switch is used to make the settings for MECHATROLINK-III communications.
The S1 DIP switch is used to make the settings for the station address.
OFF
ON
1 2 3 4 5 6 7 8
S1 (factory settings)
(1) Settings of the S2 DIP Switch
The following table shows the settings of the S2 DIP switch.
OFF
ON
1 2 3 4
S2 (factory settings)
S2 Function
Pins 1 and 2
Sets the number of transmission bytes.
1
OFF
ON
OFF
ON
M-III
2
OFF
OFF
ON
ON
Setting
Number of transmission bytes
16 bytes
32 bytes
48 bytes
Reserved.
(Do not use this setting.)
Pin 3
Pin 4
Reserved. (Do not change.)
Reserved. (Do not change.)
Factory setting
1: OFF
2: ON
OFF
OFF
• When using the MECHATROLINKIII standard servo profile, set the number of transmission bytes to either 32 or 48.
• When using the MECHATROLINKII -compatible profile, set the number of transmission bytes to either
16 or 32.
• To enable the change in the setting, restart the SERVOPACK.
4
4-3
4-4
4 Operation
(2) Settings of the S1 DIP Switch
Set the station address using the S1 DIP switch.
Station
Address
00H
01H
02H
03H
04H
0FH
10H
11H
EFH
F0H
FFH
1 2 3 4
Setting
5 6 7 8
Remarks
OFF
ON
OFF
ON
OFF OFF OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF OFF OFF
ON OFF OFF OFF OFF OFF OFF
ON
Disabled
(Do not use these address.)
OFF OFF OFF OFF OFF OFF Factory setting
OFF OFF ON OFF OFF OFF OFF OFF −
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
ON
−
OFF OFF OFF OFF −
ON OFF OFF OFF −
ON OFF OFF OFF −
−
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON −
ON
Disabled
(Do not use these address.)
ON
Note: The station address setting is displayed in binary, with S1-8 as the most significant bit and S1-1 as the least significant bit.
To set missing station addresses in previous table, calculate ON as 1 and OFF as 0.
4.2
MECHATROLINK-
III
Commands
For information on the MECHATROLINK-III commands, refer to Σ -V Series User’s Manual MECHA-
TROLINK-III Standard Servo Profile Commands (Manual No.: SIEP S800000 63).
4.3 Basic Functions Settings
4.3
Basic Functions Settings
This section describes how to set the basic functions for operation.
4.3.1
Servomotor Rotation Direction
The servomotor rotation direction can be reversed with parameter Pn000.0 without changing the polarity of the speed/position reference.
The standard setting for forward rotation is counterclockwise (CCW) as viewed from the load end of the servomotor.
Pn000
Parameter
Forward/
Reverse
Reference
Direction of Motor Rotation
Motor speed
+ Torque reference n.
0
Sets CCW as forward direction.
[Factory setting]
Forward
Reference
Time
CCW
Motor speed
+ Motor speed
Torque reference
Time
Reverse
Reference
Motor speed
CW
+
Motor speed
Torque reference n.
1
Sets CW as forward direction.
(Reverse Rotation
Mode)
Forward
Reference
Reverse
Reference
Time
CW
Motor speed
+
Motor speed
Torque reference
Time
CCW
Motor speed
Note: SigmaWin+ trace waveforms are shown in the above table.
Applicable
Overtravel (OT)
P-OT
N-OT
P-OT
N-OT
4
4-5
4-6
4 Operation
4.3.2 Overtravel
4.3.2
Overtravel
The overtravel limit function forces movable machine parts to stop if they exceed the allowable range of motion and turn ON a limit switch.
For rotating application such as disc table and conveyor, overtravel function is not necessary. In such a case, no wiring for overtravel input signals is required.
CAUTION
• Installing limit switches
For machines that move using linear motion, connect limit switches to P-OT and N-OT of CN1 as shown below to prevent machine damage. To prevent a contact fault or disconnection from causing accidents, make sure that the limit switches are normally closed.
Servomotor
Limit switch
Forward direction
SERVOPACK
MECHA
Limit switch
N-OT
CN1
8
P-OT
3
• Axes to which external force is applied in overtravel
Vertical axes:
Occurrence of overtravel may cause a workpiece to fall, because the /BK signal is on, that is when the brake is released. Set the parameter (Pn001 = n.
1 ) to bring the servomotor to zero clamp state after stopping to prevent a workpiece from falling.
Other axes to which external force is applied:
Overtravel will bring about a baseblock state after the servomotor stops, which may cause the servomotor to be pushed back by the load’s external force. To prevent this, set the parameter (Pn001 = n.
1 ) to bring the servomotor to zero clamp state after stopping.
For details on how to set the parameter, refer to (3) Servomotor Stopping Method When Overtravel is Used .
(1) Signal Setting
Type Name
Connector
Pin Number
Setting Meaning
Input
P-OT
N-OT
CN1-3
CN1-8
ON
OFF
ON
OFF
Forward run allowed.
Normal operation status.
Forward run prohibited. Forward overtravel.
Reverse run allowed. Normal operation status.
Reverse run prohibited. Reverse overtravel.
Rotation in the opposite direction is possible during overtravel by inputting the reference.
4.3 Basic Functions Settings
(2) Overtravel Function Setting
Parameters Pn50A and Pn50B can be set to enable or disable the overtravel function.
If the overtravel function is not used, no wiring for overtravel input signals will be required.
Parameter Meaning
When
Enabled
Pn50A
Pn50B n.1
[Factory setting] n.8
n.
2
[Factory setting] n.
8
Inputs the Forward Run Prohibited (P-OT) signal from
CN1-3.
Disables the Forward Run Prohibited (P-OT) signal.
Allows constant forward rotation.
Inputs the Reverse Run Prohibited (N-OT) signal from
CN1-8.
Disables the Reverse Run Prohibited (N-OT) signal.
Allows constant reverse rotation.
After restart
Classification
Setup
A parameter can be used to re-allocate input connector number for the P-OT and N-OT signals. Refer to 3.3.1
Input Signal Allocations for details.
(3) Servomotor Stopping Method When Overtravel is Used
There are two servomotor stopping methods when an overtravel is used.
• Decelerate to a stop
Stops by using emergency stop torque.
• Coast to a stop
Stops naturally, with no control, by using the friction resistance of the servomotor in operation.
After servomotor stopping, there are two modes.
• Coast mode
Stopped naturally, with no control, by using the friction resistance of the servomotor in operation.
• Zero clamp mode
A mode forms a position loop by using the position reference zero.
The servomotor stopping method when an overtravel (P-OT, N-OT) signal is input while the servomotor is operating can be set with parameter Pn001.
Pn001
Parameter n.
02
[Factory setting] n.
1 n.
2
Stop Method
Mode After
Stopping
Coast Coast
Deceleration to a stop
Zero clamp
Coast
When Enabled Classification
After restart Setup
• A servomotor under torque control cannot be decelerated to a stop. Coast status is maintained after the servomotor coasts to a stop.
• For details on servomotor stopping methods after the SV_OFF command is received or an alarm occurs, refer to 4.3.5 Stopping Servomotors after SV_OFF Command or Alarm Occurrence .
When Servomotor Stopping Method is Set to Decelerate to Stop
Emergency stop torque can be set with Pn406.
Pn406
Emergency Stop Torque Speed Position Torque
Setting Range
0 to 800
Setting Unit
1%
Factory Setting
800
When Enabled
Immediately
Classification
Setup
• The setting unit is a percentage of the rated torque.
• The factory setting is 800% so that the setting is large enough a value to operate the servomotor at maximum torque. The maximum value of emergency stop torque that is actually available, however, is limited to the maximum torque of the servomotor.
4
4-7
4-8
4 Operation
4.3.2 Overtravel
(4) Overtravel Warning Function
This function detects an overtravel warning (A.9A0) if overtravel occurs while the servomotor power is ON.
Using this function enables notifying the host controller when the SERVOPACK detects overtravel even if the overtravel signal is ON only momentarily.
To use this function, perform the following settings.
• Set Pn00D = n.1
(overtravel warning function).
• Allocate one of the output signals to the warning signal.
Warning Output Timing
Command
Motion command ALM_CLR command
Servomotor power OFF ON
MECHA
Overtravel input signal
㧔 P-OT, N-OT signals 㧕
Disabled Enabled
Overtravel warning
㧔 A.9A0
㧕
Disabled
Normal operation
Enabled Disabled
Warning status Normal operation
Warning not detected.
<Notes>
• Warnings are detected for overtravel in the same direction as the reference.
• Warnings are not detected for overtravel in the reverse direction from the reference.
Example: A warning will not be output for a forward reference even if the N-OT signal (reverse run prohibited) turns ON.
• A warning can be detected in either the forward or reverse direction, when there is no reference.
• A warning will not be detected when the servomotor power is OFF even if overtravel occurs.
• A warning will not be detected when the servomotor power changes from OFF to ON even if overtravel status exists.
• To clear the overtravel warning, send a Clear Warning or Alarm command (ALM_CLR) regardless of the status of the servomotor power and the overtravel signal. If the warning is cleared by this method during an overtravel state, the occurrence of the warning will not be indicated until the overtravelling is corrected and reset.
• The overtravel warning will be detected when the software limit is in effect.
CAUTION
• The overtravel warning function only detects warnings. It does not affect on stopping for overtravel or motion operations at the host controller. The next step (e.g., the next motion or other command) can be executed even if an overtravel warning exists. However, depending on the processing specifications and programming for warnings in the host controller, operation may be affected when an overtravel warning occurs (e.g., motion may stop or not stop). Confirm the specifications and programming in the host controller.
• When an overtravel occurs, the SERVOPACK will perform stop processing for overtravel. Therefore, when an overtravel warning occurs, the servomotor may not reach the target position specified by the host controller. Check the feedback position to make sure that the axis is stopped at a safe position.
Related Parameter
Pn00D
Parameter n.0
[Factory setting] n.1
Meaning
Does not detect overtravel warning.
Detects overtravel warning.
When Enabled Classification
Immediately Setup
4.3 Basic Functions Settings
4.3.3
Software Limit Settings
The software limits set limits in software for machine movement that do not use the overtravel signals (P-OT and N-OT). If a software limit is exceeded, an emergency stop will be executed in the same way as it is for overtravel.
(1) Software Limit Function
The software limit function can be enabled or disabled.
Use the parameter Pn801.0 to enable the software limit function.
The software limit function can be enabled under the following conditions. Under all other circumstances, the software limits will not be enabled even if a software limit is exceeded.
• The ZRET command has been executed.
• REFE = 1 using the POS_SET command.
Enable or disable the software limits using one of the following settings.
Pn801
Parameter n.
0 n.
1 n.
2 n.
3
[Factory setting]
Description
Software limits enabled in both direction.
Forward software limit enabled.
Reverse software limit enabled.
Both software limits disabled.
When Enabled Classification
Immediately Setup
(2) Software Limit Check using References
Enable or disable software limit checks when target position references such as POSING or INTERPOLATE are input. When the input target position exceeds the software limit, a deceleration stop will be performed from the software limit set position.
Pn801
Parameter n.
0
[Factory setting] n.
1
Description
No software limit check using references.
Software limit check using references.
When Enabled Classification
Immediately Setup
(3) Software Limit Setting
Set software limits value in the forward and reverse directions.
Because the limit zone is set according to the forward or reverse direction, the reverse limit must be less than the forward limit.
Pn804
Pn806
Forward Software Limit
Setting Range
-1073741823 to
1073741823
Reverse Software Limit
Setting Unit
1 Reference Unit
Setting Range
-1073741823 to
1073741823
Setting Unit
1 Reference Unit
Factory Setting
1073741823
Factory Setting
-1073741823
Position
When Enabled
Immediately
Position
When Enabled
Immediately
Classification
Setup
Classification
Setup
4
4-9
4-10
4 Operation
4.3.4 Holding Brakes
4.3.4
Holding Brakes
A holding brake is a brake used to hold the position of the movable part of the machine when the SERVO-
PACK is turned OFF so that movable part does not move due to gravity or external forces. Holding brakes are built into servomotors with brakes.
The holding brake is used in the following cases.
Vertical Shaft
Servomotor
Shaft with External Force Applied
Holding brake
Prevents the movable part from moving due to its own weight when the power is OFF.
External force
Movable part of machine
Movable part of machine
Servomotor
Holding brake
Prevents the movable part (table) from moving due to external force.
• The brake built into the servomotor with brakes is a de-energization brake, which is used only to hold and cannot be used for braking. Use the holding brake only to hold a stopped servomotor.
There is a delay in the braking operation. Set the following ON/OFF timing.
Servo ON command
(SV_ON)
OFF
OFF
Servomotor power
OFF
Brake signal (/BK)
Brake contact part
(lining)
Brake applied
*1
Position reference/
Speed reference
0
ON
ON
ON
Brake release
*1
OFF
*3
OFF
OFF
Brake applied
MECHA
Motor speed
*2
∗1.
The delay time in brake operation is given in the following table. This is just example of the operation delay time for switching with a direct current. Always evaluate performance on the actual equipment before actual operation.
SGMMV
Model Voltage
24 VDC
Brake Release Time (ms)
40
Brake Applied Time (ms)
100
∗2.
After the SV_ON command has been sent and 50 ms has passed since the brake was released, output the reference from the host controller to the SERVOPACK.
∗3.
Use Pn506, Pn507, and Pn508 to set the timing of when the brake will be activated and when the servomotor power will be turned OFF.
4.3 Basic Functions Settings
(1) Wiring Example
Use the brake signal (/BK) and the brake power supply to form a brake ON/OFF circuit. The following diagram shows a standard wiring example.
The timing can be easily set using the brake signal (/BK).
Servomotor with holding brake
Power supply
Non-isolated
AC/DC converter for main power supply
SERVOPACK
CN3
L1
L2
CN4
U
V
W
C1
C2
CN2 Non-isolated
AC/DC converter for control power supply
CN1
11 /BK
BK-RY
5 COM_SG
1D
+24V
0 V
Surge absorber
M
ENC
BK
Brake power supply BK-RY
BK-RY: Brake control relay
Brake power supply for 24 VDC is not included.
MECHA
• Always connect a surge absorber.
Recommended surge absorber: Z15D151 (manufactured by SEMITEC Corporation)
• After the surge absorber is connected, check the total time the brake is applied for the system. Depending on the surge absorber, the total time the brake is applied can be changed.
• Configure the relay circuit to apply the holding brake by the emergency stop.
Relay Circuit Example
SERVOPACK
5 to 24 VDC
Emergency stop
Photocoupler
0 V
• The allocation of the /BK signal can be changed. Refer to (3) Brake Signal (/BK) Allocation to set the parameter Pn50F.
• Always separate the 24-VDC power supply for the 24-V brake from other power supplies, such as the control or I/O signal (CN1) power supplies. If the power supply is shared, the I/O signals might malfunction.
4
4-11
4-12
4 Operation
4.3.4 Holding Brakes
(2) Brake Signal (/BK) Setting
This output signal controls the brake. The allocation of the /BK signal can be changed. Refer to (3) Brake Signal (/BK) Allocation for allocation.
The /BK signal turns OFF (applies the brake) when an alarm is detected or the SV_OFF command is received.
The brake OFF timing can be adjusted with Pn506.
Type
Output /BK
Name
Connector
Pin Number
CN1-11
Setting
ON (closed)
OFF (open)
Meaning
Releases the brake.
Applies the brake.
The /BK signal is still ON during overtravel and the brake is still released.
(3) Brake Signal (/BK) Allocation
Use parameter Pn50F.2 to allocate the /BK signal.
Pn50F
Parameter n.
0 n.
1
[Factory setting] n.
2 n.
3
Connector
Pin Number
–
Meaning
The /BK signal is not used.
CN1-11
CN1-10
CN1-9
When
Enabled
The /BK signal is output from output terminal CN1-11.
The /BK signal is output from output terminal CN1-10.
The /BK signal is output from output terminal CN1-9.
After restart
Classification
Setup
When multiple signals are allocated to the same output terminal, the signals are output with OR logic. For the /BK signal, do not use the output terminal that is already being used for another signal.
4.3 Basic Functions Settings
(4) Brake ON Timing after the Servomotor Stops
When the servomotor stops, the /BK signal turns OFF at the same time as the SV_OFF command is received.
Use parameter Pn506 to change the timing to turn OFF the servomotor power after the SV_OFF command has been received.
Pn506
Brake Reference-Servo OFF Delay Time Speed Position Torque
Setting Range
0 to 50
Setting Unit
10 ms
Factory Setting
0
When Enabled
Immediately
Classification
Setup
• When using the servomotor to control a vertical axis, the machine movable part may shift slightly depending on the brake ON timing due to gravity or an external force. To eliminate this slight shift, set parameter so that the power to the servomotor turns
OFF after the brake is applied.
• This parameter changes the brake ON timing while the servomotor is stopped.
SV_OFF command Servo ON Servo OFF
/BK output
Power to motor
MECHA
Brake released
(ON)
Brake applied
(OFF)
Power to motor No power to motor
Pn506
The servomotor will turn OFF immediately when an alarm occurs, regardless of the setting of this parameter. The machine movable part may shift due to gravity or external force before the brake operates.
4
4-13
4-14
4 Operation
4.3.4 Holding Brakes
(5) Brake Signal (/BK) Output Timing during Servomotor Rotation
If an alarm occurs while the servomotor is rotating, the servomotor will come to a stop and the brake signal
(/BK) will be turned OFF. The timing of brake signal (/BK) output can be adjusted by setting the brake reference output speed level (Pn507) and the waiting time for brake signal when motor running (Pn508).
Note: If the servomotor is set so that it comes to a zero-speed stop for an alarm, follow the information in (4) Brake ON
Timing after the Servomotor Stops after the servomotor comes to a stop for a zero position reference.
Pn507
Pn508
Brake Reference Output Speed Level Speed Position Torque
Setting Range
0 to 10000
Setting Unit
1 min
-1
Factory Setting
100
When Enabled
Immediately
Waiting Time for Brake Signal When Motor Running Speed Position Torque
Setting Range
10 to 100
Setting Unit
10 ms
Factory Setting
50
When Enabled
Immediately
Classification
Setup
Classification
Setup
/BK Signal Output Conditions
When Servomotor Rotating
The /BK signal goes to high level
(brake ON) when either of the following conditions is satisfied:
• When the motor speed falls below the level set in Pn507 after the power to the servomotor is turned OFF.
• When the time set in Pn508 is exceeded after the power to the servomotor is turned OFF.
SV_OFF command or alarm or power OFF
Motor speed
Power to motor
/BK output
Servo ON
ON
Brake released
(ON)
Servo OFF
Pn-507 Motor stopped by coasting Pn001.0
OFF
Brake applied
(OFF)
Pn508
MECHA
• The servomotor will be limited to its maximum speed even if the value set in Pn507 is higher than the maximum speed.
• Do not allocate the rotation detection signal (/TGON) and the brake signal (/BK) to the same terminal. The /TGON signal will otherwise be turned ON by the falling speed on a vertical axis, and the brake may not operate.
For the /BK signal, do not use the terminal that is already being used for another signal.
4.3 Basic Functions Settings
4.3.5
Stopping Servomotors after SV_OFF Command or Alarm Occurrence
The servomotor stopping method can be selected after the SV_OFF command is received or an alarm occurs.
• The elements in the SERVOPACK will deteriorate if turning the power supply ON and
OFF or starting and stopping the servomotor during the servo ON status while there is a reference input. Use a speed reference or position reference to start and stop the servomotor.
• If turning OFF the main circuit power supply or the control power supply during operation without turning OFF the servo, the servomotor will coast to a stop. In this case, the stop method cannot be set in a parameter.
• To minimize the coasting distance of the servomotor to come to a stop when an alarm occurs, the zero-speed stopping method is factory-set for alarms to which the zerospeed stopping method is applicable. However, in some applications, coasting to a stop may be more suitable than the zero-speed stopping method.
For example, for multiple shafts in coupled operation (e.g., a twin-drive operation), machinery may damage due to differences in the stopping operation if a zero-speed stop alarm occurs for one of the coupled shafts and the other coupled shaft coasts to a stop. In such cases, change the stopping method so that the servomotor coasts to a stop.
(1) Stopping Method for Servomotor after SV_OFF Command is Received
The servomotor coasts to a stop when the servo is turned OFF.
(2) Stopping Method for Servomotor When an Alarm Occurs
There are two types of alarms, Gr.1 and Gr.2, that vary in the stopping method when the alarm occurs.
When a Gr.1 alarm occurs, the servomotor coasts to a stop.
When a Gr.2 alarm occurs, the stopping method that is set in Pn00B.1 is used.
Refer to the information on alarm stopping methods in 8.1.1 List of Alarms .
Stopping Method for Servomotor for Gr.2 Alarms
Parameter Stop Mode
Mode After
Stopping
When
Enabled
Classification
Pn00B n.
0
[Factory setting] n.
1
Zero-speed stopping*
Coast
Coast
After restart
Setup
∗ Zero-speed stopping: The speed reference is set to 0 to stop quickly.
Note: The setting of Pn00B.1 is effective for position control and speed control. The setting of Pn00B.1 is ignored for torque control and the servomotor coasts to a stop.
4
4-15
4-16
4 Operation
4.3.6 Setting Motor Overload Detection Level
4.3.6
Setting Motor Overload Detection Level
In this SERVOPACK, the detection timing of the warnings and alarms can be changed by changing how to detect an overload warning (A.910) and overload (low load) alarm (A.720).
The overload characteristics and the detection level of the overload (high load) alarm (A.710) cannot be changed.
(1) Changing Detection Timing of Overload Warning (A.910)
The overload warning level is set by default to 20% so that an overload warning is detected in 20% of the time required to detect an overload alarm. The time required to detect an overload warning can be changed by changing the setting of the overload warning level (Pn52B). This protective function enables the warning output signal (/WARN) to serve as a protective function and to be output at the best timing for your system.
The following graph shows an example of the detection of an overload warning when the overload warning level (Pn52B) is changed from 20% to 50%. An overload warning is detected in half of the time required to detect an overload alarm.
Overload detection time
Detection curve of overload warning when
Pn52B=50%
Detection curve of overload alarm
Detection curve of overload warning when Pn52B=20% (factory setting)
100% 200% Torque reference [%]
Note: For details, refer to Overload Characteristics listed in the section for the relevant servomotor in the uct Catalog (Catalog No.: KAEP S800000 42).
Σ -V Series Prod-
Pn52B
Overload Warning Level
Setting Range
1 to 100
Setting Unit
1%
Speed Position Torque
Factory Setting When Enabled
20 Immediately
Classification
Setup
4.3 Basic Functions Settings
(2) Changing Detection Timing of Overload (Low Load) Alarm (A.720)
An overload (low load) alarm (A.720) can be detected earlier to protect the servomotor from overloading. The time required to detect an overload alarm can be shortened by using the derated motor base current obtained with the following equation.
Note: The detection level of the overload (high load) alarm (A.710) cannot be changed.
Motor base current × Derating of base current at detecting overload of motor (Pn52C)
= Derated motor base current
Motor base current: Threshold value of motor current to start calculation for overload alarm
Derating of base current at detecting overload of motor (Pn52C): Derating of motor base current
The following graph shows an example of the detection of an overload alarm when Pn52C is set to 50%. The calculation for the overload of motors starts at 50% of the motor base current and then an overload alarm will be detected earlier.
Changing the setting of Pn52C will change the detection timing of the overload alarm, so the time required to detect the overload warning will also be changed.
Overload detection time
Detection curve of overload alarm when
Pn52C=100% (factory setting)
Detection curve of overload alarm when Pn52C=50%
50% 100% 200% Torque reference [%]
As a guideline of motor heating conditions, the relationship between the heat sink sizes and deratings of base current is shown in a graph in:
Servomotor Heating Conditions in Rotary Servomotors General Instruction in
(Catalog No.: KAEP S800000 42).
Σ -V Series Product Catalog
Set Pn52C to a value in accordance with the heat sink size and derating shown in the graph, so that an overload alarm can be detected at the best timing to protect the servomotor from overloading.
Note: For details, refer to Overload Characteristics listed in the section for the relevant servomotor in the Σ -V Series Product Catalog ( Catalog No.
: KAEP S800000 42).
Pn52C
Derating of Base Current at Detecting Overload of
Motor
Setting Range Setting Unit
Speed
Factory Setting
Position Torque
When Enabled
10 to 100 1% 100 After restart
Classification
Setup
4
4-17
4-18
4 Operation
4.4.1 Inspection and Checking before Trial Operation
4.4
Trial Operation
This section describes a trial operation using MECHATROLINK-III communications.
4.4.1
Inspection and Checking before Trial Operation
To ensure safe and correct trial operation, inspect and check the following items before starting trial operation.
(1) Servomotors
Inspect and check the following items, and take appropriate measures before performing trial operation if any problem exists.
• Are all wiring and connections correct?
• Are all nuts and bolts securely tightened?
Note: When performing trial operation on a servomotor that has been stored for a long period of time, perform the inspection according to the procedures described in AC Servomotor Safety Precautions (Manual No.: TOBP C230200 00).
(2) SERVOPACKs
Inspect and check the following items, and take appropriate measures before performing trial operation if any problem exists.
• Are all wiring and connections correct?
• Is the correct power supply voltage being supplied to the SERVOPACK?
4.4 Trial Operation
4.4.2
Trial Operation via MECHATROLINK-
III
The following table provides the procedures for trial operation via MECHATROLINK-III.
Step
1
2
Description
Confirm that the wiring is correct, and then connect the I/O signal connector (CN1 connector).
Turn ON the power supply to the SERVOPACK, and then turn ON the power supply to the host controller.
When a communications connection is established, the LED lamp (LK1 or LK2) for the connector to which the MECHATROLINK-III cable is connected (CN6A or CN6B) will light. If the LK1 or LK2 LED lamp does not light, recheck the settings of MECHATROLINK-III setting switches (S1 and S2) and then restart the SERVOPACK.
Reference
3 Wiring and Connection
–
3
4
5
6
Send the CONNECT command from the host controller.
If the SERVOPACK correctly receives the CONNECT command, the
CON, LED indicator will light up.
If the CON does not light up, the set value of the CONNECT command is incorrect. Reset the CONNECT command, and then resend it from the host controller.
Check the product type using an ID_RD command.
A reply showing the product type, such as SGDV-2R9E21A, is received from the SERVOPACK.
Set the following items to the necessary settings for a trial operation.
• Electronic gear settings
• Rotational direction of servomotor
• Overtravel
Save these settings (step 5).
• If saving the settings in the host controller, use the SVPRM_WR command (set the mode to RAM area).
• If saving the settings in the SERVOPACK, use the SVPRM_WR command (set the mode to the non-volatile memory area).
7 Send the CONFIG command to enable the settings.
8
Send the SENS_ON command to obtain the position data (encoder ready response).
Σ -V Series User’s Manual
MECHATROLINK-III Standard
Servo Profile Commands
(Manual No.: SIEP S800000 63)
4.4.3 Electronic Gear
4.3.1 Servomotor Rotation Direction
4.3.2 Overtravel
Σ -V Series User’s Manual
MECHATROLINK-III Standard
Servo Profile Commands
(Manual No.: SIEP S800000 63)
9
10
11
Send the SV_ON command.
A response showing that the servomotor has switched to Drive status and that SVON=1 (servomotor power is ON) is received.
Run the servomotor at low speed.
<Example using a positioning command>
Command used: POSING
Command setting: Positioning position =10000 (If using the absolute encoder, add 10000 to the present position), rapid traverse speed= 400
–
Check the following points while running the servomotor at low speed
(step 10).
• Confirm that the rotational direction of the servomotor correctly coincides with the forward rotation or reverse rotation reference. If they do not coincide, reset the direction.
• Confirm that no unusual vibrations, noises, or temperature rises occur.
If any abnormalities are seen, correct the conditions.
Note: Because the running-in of the load machine is not sufficient at the time of the trial operation, the servomotor may become overloaded.
4.3.1 Servomotor Rotation Direction
8.4 Troubleshooting Malfunction
Based on Operation and Conditions of the Servomotor
4
4-19
4-20
4 Operation
4.4.3 Electronic Gear
4.4.3
Electronic Gear
The electronic gear enables the workpiece travel distance per reference unit input from the host controller. The minimum unit of the position data moving a load is called a reference unit.
The section indicates the difference between using and not using an electronic gear when a workpiece is moved 10 mm in the following configuration.
Workpiece
Encoder resolution (17 bit) 131072
Ball screw pitch: 6 mm
When the Electronic Gear is Not Used:
1 Calculate the revolutions.
1 revolution is 6 mm. Therefore, 10/6 revolutions.
2 Calculate the required reference units.
131072 reference units is 1 revolution. Therefore, 10/6 × 131072 = 218453.33
reference units.
3 Input 218453 references as reference units.
Reference units must be calculated per reference.
→
complicated
When the Electronic Gear is Used:
The reference unit is 1 μ m. Therefore, to move the workpiece 10 mm (10000 μ m),
1 reference unit = 1 μ ÷
Input 10000 pulses as reference units.
Calculation of reference units per reference is not required.
→
simplified
4.4 Trial Operation
(1) Electronic Gear Ratio
Set the electronic gear ratio using Pn20E and Pn210.
Pn20E
Pn210
Electronic Gear Ratio (Numerator)
Setting Range
1 to 1073741824
Setting Unit
1
Electronic Gear Ratio (Denominator)
Setting Range
1 to 1073741824
Setting Unit
1
Factory Setting
1
Factory Setting
1
Position
When Enabled
After restart
Position
When Enabled
After restart
Classification
Setup
Classification
Setup
If the gear ratio of the servomotor and the load shaft is given as n/m where m is the rotation of the servomotor and n is the rotation of the load shaft,
Electronic gear ratio:
B
A
=
Pn20E
Pn210
=
Encoder resolution
Travel distance per load shaft revolution (reference units)
× m n
Encoder Resolution
Encoder resolution can be checked with servomotor model designation.
SGMMV
2 17-bit absolute 131072
Electronic gear ratio setting range: 0.001 ≤ Electronic gear ratio (B/A) ≤ 4000
If the electronic gear ratio is outside this range, a parameter setting error 1 (A.040) will be output.
(2) Electronic Gear Ratio Setting Examples
The following examples show electronic gear ratio settings for different load configurations.
Step
1
Operation
Ball Screw
Reference unit: 0.001 mm
Load shaft
17-bit encoder Ball screw pitch: 6 mm
Check machine specifications.
• Ball screw pitch: 6 mm
• Gear ratio: 1/1
Load Configuration
Disc Table
Reference unit: 0.01
°
Load shaft
17-bit encoder
Belt and Pulley
Reference unit: 0.005 mm
Load shaft
Gear ratio:
1/100
Gear ratio
1/50
Pulley diameter:
100 mm
17-bit encoder
Rotation angle per revolution: 360 °
Gear ratio: 1/100
Pulley diameter: 100 mm
(pulley circumference: 314 mm)
• Gear ratio: 1/50
2
3
4
5
6
Check the encoder resolution.
Determine the reference unit used.
Calculate the travel distance per load shaft revolution. (Reference unit)
131072 (17-bit)
Reference unit: 0.001 mm
(1 μ m)
6 mm/0.001 mm=6000
Calculate the electronic gear ratio.
Set parameters.
B
A
=
131072
6000
Pn20E: 131072
Pn210: 6000
1
1
131072 (17-bit)
Reference unit: 0.01
°
360 ° /0.01
° =36000
B
A
=
131072
36000
Pn20E: 13107200
Pn210: 36000
100
1
131072 (17-bit)
Reference unit: 0.005 mm
(5 μ m)
314 mm/0.005 mm=62800
B
A
=
131072
62800
Pn20E: 6553600
Pn210: 62800
50
1
4
4-21
4 Operation
4.5.1 Motor Information
4.5
Test Without Motor Function
The test without a motor is used to check the operation of the host controller and peripheral devices by simulating the operation of the servomotor in the SERVOPACK, i.e., without actually operating a servomotor. This function enables you to check wiring, verify the system while debugging, and verify parameters, thus shortening the time required for setup work and preventing damage to the machine that may result from possible malfunctions. The operation of the motor can be checked during performing this function regardless of whether the motor is actually connected or not.
Reference
Host controller
SERVOPACK
Reference
Simulates the operation without motor.
4-22
M-III
Response Response
Use Pn00C.0 to enable or disable the test without a motor.
Pn00C
Parameter n.
0
[Factory setting] n.
1
Meaning
Disables the test without a motor.
Enables the test without a motor.
When
Enabled
After restart
Classification
Setup
4.5.1
Motor Information
The motor information that is used for a test without a motor is given below.
(1) Motor Connected
If a motor is connected, the information from the connected motor is used for the motor and encoder information. The set values of Pn00C.1 and Pn00C.2 are not used.
(2) Motor Not Connected
The virtual motor information that is stored in the SERVOPACK is used. The set values of Pn00C.1 and
Pn00C.2 are used for the encoder information.
Encoder Resolution
The encoder information for the motor is set in Pn00C.1.
Parameter Meaning
When
Enabled
Classification
Pn00C n.
0
[Factory setting] n.
1
Sets 13 bits as encoder resolution for the test without a motor.
Sets 20 bits as encoder resolution for the test without a motor.
Encoder Type
The encoder information for the motor is set in Pn00C.2.
After restart Setup
Pn00C
Parameter n.
0
[Factory setting] n.
1
Meaning
When
Enabled
Classification
Sets an incremental encoder as encoder type for the test without a motor.
Sets an absolute encoder as encoder type for the test without a motor.
After restart Setup
4.5 Test Without Motor Function
Rated Motor Speed and Maximum Motor Speed
The values previously saved in the SERVOPACK will be used for the rated motor speed and maximum motor speed. Use the monitor displays (Un020: Motor rated speed and Un021: Motor maximum speed) to check the values.
4.5.2
Motor Position and Speed Responses
For the test without a motor, the following responses are simulated for references from the host controller according to the gain settings for position or speed control.
• Servomotor position
• Servomotor speed
However, the load model will be a rigid system with the moment of inertia ratio that is set in Pn103.
4
4-23
4-24
4 Operation
4.5.3 Limitations
4.5.3
Limitations
The following functions cannot be used during the test without a motor.
• Brake output signal (The brake output signal can be checked with the I/O signal monitor function of the SigmaWin+.)
• Items marked with " × " in the following utility function table.
Fn No.
Contents
Fn000 Alarm history display
Fn002 JOG operation
Fn003 Origin search
Fn004 Program JOG operation
Fn005 Initializing parameter settings
Fn006 Clearing alarm history
Fn008 Absolute encoder multiturn reset and encoder alarm reset
Fn00C Offset adjustment of analog monitor output
Fn00D Gain adjustment of analog monitor output
Fn00E Automatic offset-signal adjustment of the motor current detection signal
Fn00F Manual offset-signal adjustment of the motor current detection signal
Fn010 Write prohibited setting
Fn011 Servomotor model display
Fn012 Software version display
Fn013
Multiturn limit value setting change when a multiturn limit disagreement alarm occurs
Fn01B Vibration detection level initialization
Fn01E Display of SERVOPACK and servomotor ID
Fn030 Software reset
Fn200 Tuning-less levels setting
Fn201 Advanced autotuning
Fn202 Advanced autotuning by reference
Fn203 One-parameter tuning
Fn204 Anti-resonance control adjustment function
Fn205 Vibration suppression function
Fn206 EasyFFT
Fn207 Online vibration monitor
Note: : Can be used
× : Cannot be used
×
×
×
Can be used or not
Motor not connected
Motor connected
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
4.6 Limiting Torque
4.6
Limiting Torque
The SERVOPACK provides the following four methods for limiting output torque to protect the machine.
Limiting Method
Internal torque limit
External torque limit
Torque limit with the command data (TLIM)
*
Description
Always limits torque by setting the parameter.
Limits torque by input signal from the host controller.
Limits torque by using the command data (TLIM) for torque limiting function settable commands.
Reference
Section
4.6.1
4.6.2
–
Torque limit with P_CL and
N_CL signals of the servo command output signals
(SVCMD_IO)
*
Limits torque by using P_CL and N_CL signals of the servo command output signals (SVCMD_IO).
–
∗ For details, refer to
SIEP S800000 63).
Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
Note: The maximum torque of the servomotor is used when the set value exceeds the maximum torque.
(Manual No.:
4.6.1
Internal Torque Limit
This function always limits maximum output torque by setting values of following parameters.
Pn402
Pn403
Forward Torque Limit Speed Position Torque
Setting Range Setting Unit Factory Setting When Enabled
0 to 800 1% 800 Immediately
Reverse Torque Limit Speed Position Torque
Setting Range Setting Unit Factory Setting When Enabled
0 to 800 1% 800 Immediately
Classification
Setup
Classification
Setup
The setting unit is a percentage of the rated torque.
Note: If the settings of Pn402 and Pn403 are too low, the torque may be insufficient for acceleration or deceleration of the servomotor.
Torque waveform
No Internal Torque Limit
(Maximum torque can be output)
Internal Torque Limit
Maximum torque
Speed
Limiting torque
Speed
Pn402 t t
Pn403
4
4-25
4-26
4 Operation
4.6.2 External Torque Limit
4.6.2
External Torque Limit
Use this function to limit torque by inputting a signal from the host controller at specific times during machine operation. For example, some pressure must continually be applied (but not enough to damage the workpiece) when the robot is holding a workpiece or when a device is stopping on contact.
(1) Input Signals
Use the following input signals to limit a torque by external torque limit.
Type
Input
Input
Signal
Name
/P-CL
/N-CL
Connector
Pin Number
Setting
Must be allocated
Must be allocated
ON
(closed)
OFF
(open)
ON
(closed)
OFF
(open)
Meaning
Pn403
Limit value
Forward external torque limit ON
The smaller value of these settings: Pn402 or Pn404
Forward external torque limit
OFF
Pn402
Reverse external torque limit
OFF
Note: Use parameter Pn50B.2 and Pn50B.3 to allocate the /P-CL signal and the /N-CL signal for use. For details, refer to
3.3.1 Input Signal Allocations .
(2) Related Parameters
Set the following parameters for external torque limit.
Pn402
Pn403
Pn404
Pn405
Forward Torque Limit
Setting Range
0 to 800
Reverse Torque Limit
Setting Range
Setting Unit
1%
Setting Unit
0 to 800 1%
Forward External Torque Limit
Setting Range Setting Unit
0 to 800
Reverse External Torque Limit
1%
Setting Range
0 to 800
Setting Unit
1%
Speed Position Torque
Factory Setting When Enabled
800 Immediately
Speed Position Torque
Factory Setting When Enabled
800 Immediately
Speed Position Torque
Factory Setting When Enabled
100 Immediately
Speed Position Torque
Factory Setting When Enabled
100 Immediately
Classification
Setup
Classification
Setup
Classification
Setup
Classification
Setup
The setting unit is a percentage of the rated torque.
Note: If the settings of Pn402, Pn403, Pn404, and Pn405 are too low, the torque may be insufficient for acceleration or deceleration of the servomotor.
4.6 Limiting Torque
(3) Changes in Output Torque during External Torque Limiting
The following diagrams show the change in output torque when the internal torque limit is set to 800%.
In this example, the servomotor rotation direction is Pn000.0 = 0 (Sets CCW as forward direction).
/P-CL
OFF ON
Pn402 Pn402
Speed Speed
Pn404
OFF
0 0
Torque Torque
/N-CL
Pn403
Pn402
Speed
Pn403
Pn402
Pn404
Speed
ON
0
Pn405
0
Pn405
Torque Torque
Pn403 Pn403
4.6.3
Checking Output Torque Limiting during Operation
The following signal can be output to indicate that the servomotor output torque is being limited.
Type Signal Name
Connector
Pin Number
Setting Meaning
Output /CLT Must be allocated
ON (closed)
OFF (open)
Servomotor output torque is being limited.
Servomotor output torque is not being limited.
Note: Use parameter Pn50F.0 to allocate the /CLT signal for use. For details, refer to 3.3.2 Output Signal Allocations .
4
4-27
4-28
4 Operation
4.7.1 Connecting the Absolute Encoder
4.7
Absolute Encoders
If using an absolute encoder, a system to detect the absolute position can be designed for use with the host controller. As a result, an operation can be performed without a zero point return operation immediately after the power is turned ON.
A battery case is required to save position data in the absolute encoder.
The battery is attached to the battery case of the encoder cable.
Set Pn002.2 to 0 (factory setting) to use the absolute encoder.
When
Enabled
Classification
Pn002
Parameter Meaning n.
0
[Factory setting] n.
1
Uses the absolute encoder as an absolute encoder.
Uses the absolute encoder as an incremental encoder.
After restart Setup
The SEN signal and battery are not required when using the absolute encoder as an incremental encoder.
4.7.1
Connecting the Absolute Encoder
The following diagram shows the connection between a servomotor with an absolute encoder, the SERVO-
PACK, and the host controller.
SERVOPACK
MEC
HA
Absolute encoder
ENC
∗
1
PS
/PS
CN2
5
6
Output line driver
SN75ALS174 or the equivalent
PG5 V
PG0 V
1
2
(Shell)
Battery
BAT (+)
∗ 2
BAT (-)
∗ 2
3
4
Connector shell
∗1.
: represents shielded twisted-pair wires.
∗2.
When using an absolute encoder, provide power by installing an encoder cable with a JUSP-BA01-E Battery Case or install a battery on the host controller.
4.7 Absolute Encoders
• When Installing a Battery on the Encoder Cable
Use the encoder cable with a battery case that is specified by Yaskawa.
For details, refer to the Σ -V Series Product Catalog (Catalog No.: KAEP S800000 42).
• When Installing a Battery on the Host Controller
Insert a diode near the battery to prevent reverse current flow.
Circuit Example
+
- Battery
4.7.2
Absolute Data Request (SENS ON Command)
The Turn Sensor ON command (SENS_ON) must be sent to obtain absolute data as an output from the SER-
VOPACK.
The SENS_ON command is sent at the following timing.
SERVOPACK control power supply
OFF
ON
5 seconds max.
ON (Normal status)
*
OFF
M-
III
ALM signal OFF
(Alarm status)
SENS_ON
(Turn Sensor ON)
OFF
OFF
ON
OFF
OFF
ON
Servomotor power
OFF OFF
Approx. 560 ms max.
The servomotor will not be turned ON even if the SV_ON command is received during this interval.
∗ Send the SENS_OFF command to turn OFF the control power supply.
4
4-29
4-30
4 Operation
4.7.3 Battery Replacement
4.7.3
Battery Replacement
If the battery voltage drops to approximately 2.7 V or less, an absolute encoder battery error alarm (A.830) or an absolute encoder battery error warning (A.930) will be displayed.
If this alarm or warning is displayed, replace the batteries using the following procedure.
Use Pn008.0 to set either an alarm (A.830) or a warning (A.930).
When
Enabled
Classification
Pn008
Parameter Meaning n.
0
[Factory setting] n.
1
Outputs the alarm A.830 when the battery voltage drops.
Outputs the warning A.930 when the battery voltage drops.
After restart Setup
• If Pn008.0 is set to 0, alarm detection will be enabled for 4 seconds after the ALM signal outputs max. 5 seconds when the control power is turned ON.
No battery-related alarm will be displayed even if the battery voltage drops below the specified value after these 4 seconds.
• If Pn008.0 is set to 1, alarm detection will be always enabled after the ALM signal outputs max. 5 seconds when the control power supply is turned ON.
ON
Control power
OFF
ALM
Alarm status
Alarm A.830
(Pn008.0 = 0)
5 s max.
Normal status
4 s
Battery voltage being monitored
Warning A.930
(Pn008.0 = 1)
Battery voltage being monitored
4.7 Absolute Encoders
(1) Battery Replacement Procedure
1. Turn ON the control power supply of the SERVOPACK only.
2. Open the battery case cover.
Open the cover.
3. Remove the old battery and mount the new JZSP-BA01 battery as shown below.
To the SERVOPACK
Encoder Cable
Mount the JZSP-BA01 battery.
4. Close the battery case cover.
Close the cover.
5. After replacing the battery, turn OFF the control power supply to clear the absolute encoder battery error alarm (A.830).
6. Turn ON the control power supply again.
7. Check that the alarm display has been cleared and that the SERVOPACK operates normally.
If the SERVOPACK control power supply is turned OFF and the battery is disconnected
(which includes disconnecting the encoder cable), the absolute encoder data will be deleted.
4
4-31
4 Operation
4.7.4 Absolute Encoder Setup
4.7.4
Absolute Encoder Setup
CAUTION
• The rotational data will be a value between -2 and +2 rotations when the absolute encoder setup is executed. The reference position of the machine system will change. Set the reference position of the host controller to the position after setup.
If the machine is started without adjusting the position of the host controller, unexpected operation may cause injury or damage to the machine. Take sufficient care when operating the machine.
Setting up the absolute encoder is necessary in the following cases.
• When starting the machine for the first time
• When an encoder backup error alarm (A.810) is generated
• When an encoder checksum error alarm (A.820) is generated
• When initializing the rotational serial data of the absolute encoder
(1) Precautions on Setup
• If the following absolute encoder alarms are displayed, cancel the alarm by using the same method as the absolute encoder setup. They cannot be canceled with the SERVOPACK Clear Warning or Alarm command
(ALM_CLR).
• Encoder backup error alarm (A.810)
• Encoder checksum error alarm (A.820)
• Any other alarms (A.8
) that monitor the inside of the encoder should be canceled by turning OFF the power.
(2) Preparation
The following conditions must be met to setup the absolute encoder.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be OFF.
(3) Operating Procedure
Use the following procedure.
This setting can be performed using the write memory command (MEM_WR). For details, refer to Σ -V Series
User’s Manual MECHATROLINK-III Standard Servo Profile Commands (Manual No.: SIEP S800000 63).
1.
Make sure that the motor power is OFF.
2.
In the SigmaWin+ main window, click Setup – Set Absolute Encoder – Reset Absolute
Encoder .
A warning message will appear confirming if you want to continue the processing.
MEC
HA
4-32
Click Cancel to return to the main window without resetting the absolute encoder.
3.
Click Continue .
The Absolute encoder Setup box will appear.
MEC
HA
4.7 Absolute Encoders
The Alarm Name box displays the code and name of the alarm that is occurring now.
4.
Click Execute setting .
A verification message will appear confirming if you want to continue although the coordinate system will change.
MECHA
Click Cancel to return to the previous window without resetting the absolute encoder.
5.
Click Continue to set up the encoder.
<If Setup is Unsuccessful>
If setting up is attempted with the servo ON, a reset conditions error occurs, and the processing is aborted.
MECHA
Click OK to return to the main window.
<If Setup Completes Normally>
MECHA
4
If the encoder is set up successfully, a warning message will appear reminding you that the coordinate system has changed and must also be reset.
4-33
4-34
4 Operation
4.7.4 Absolute Encoder Setup
6.
Click OK to return to the main window.
7.
To perform an origin search, restart the SERVOPACK.
4.7 Absolute Encoders
4.7.5
Multiturn Limit Setting
The multiturn limit setting is used in position control applications for a turntable or other rotating device. For example, consider a machine that moves the turntable in the following diagram in only one direction.
Turntable
Gear
Servomotor
Because the turntable moves in only one direction, the upper limit for revolutions that can be counted by an absolute encoder will eventually be exceeded. The multiturn limit setting is used in cases like this to prevent fractions from being produced by the integral ratio of the motor revolutions and turntable revolutions.
For a machine with a gear ratio of n:m, as shown above, the value of m minus 1 will be the setting for the multiturn limit setting (Pn205).
Multiturn limit setting (Pn205) = m-1
The case in which the relationship between the turntable revolutions and motor revolutions is m = 100 and n =
3 is shown in the following graph.
Pn205 is set to 99.
Pn205 = 100 − 1 = 99
Table rotations
6
5
4
3
2
1
0
9
8
7
Table rotations
Rotational data
Set value of Pn205 = 99
100 200 300 0
Motor rotations
Rotational serial data
100
50
Pn205
Multiturn Limit Setting
Setting Range
0 to 65535
Setting Unit
1 Rev
Speed
Factory Setting
65535
Position Torque
When Enabled
After restart
Classification
Setup
Note: This parameter is valid when the absolute encoder is used.
The range of the data will vary when this parameter is set to anything other than the factory setting.
1. When the motor rotates in the reverse direction with the rotational data at 0, the rotational data will change to the setting of Pn205.
2. When the motor rotates in the forward direction with the rotational data at the Pn205 setting, the rotational data will change to 0.
4
4-35
4-36
4 Operation
4.7.6 Multiturn Limit Disagreement Alarm (A.CC0)
Set the value, the desired rotational amount -1, to Pn205.
Factory Setting (= 65535)
+32767
Forward Reverse
Rotational
0 data
Other Setting ( ≠ 65535)
Pn205 setting value
Rotational data
0
Forward Reverse
Motor rotations
-32768 Motor rotations
4.7.6
Multiturn Limit Disagreement Alarm (A.CC0)
When the multiturn limit set value is changed with parameter Pn205, a multiturn limit disagreement alarm
(A.CC0) will be displayed because the value differs from that of the encoder.
Alarm
Display
Alarm Name Alarm Output Meaning
A.CC0
Multiturn Limit Disagreement OFF (H)
Different multiturn limits have been set in the encoder and SERVOPACK.
If this alarm is displayed, perform the procedure given in (2) Operating Procedure to change the multiturn limit value in the encoder to the value set in Pn205.
(1) Preparation
The following condition must be met to clear the alarm and change the multiturn limit value.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
(2) Operating Procedure
Use the following procedure.
This setting can be performed with the write memory command (MEM_WR).
For information the write memory command (MEM_WR), refer to Σ -V Series User’s Manual MECHA-
TROLINK-III Standard Servo Profile Commands (Manual No.: SIEP S800000 63).
1.
In the SigmaWin+ main window, click Setup – Set Absolute Encoder – Multi-Turn Limit
Setting .
A verification message will appear confirming if you want to continue although the position data will change.
MEC
HA
Click Cancel to return to the main window without setting the multi-turn limit.
2.
Click Continue .
The Multi-Turn Limit Setting box will appear.
MEC
HA
4.7 Absolute Encoders
3.
Change the setting to the desired number of revolutions.
MEC
HA
4.
To save the settings, click Writing into the Servopack .
A warning message will appear.
MEC
HA
5.
Click OK and the settings are changed to the new ones.
6.
Restart the SERVOPACK.
Because only the settings for the SERVOPACK were made, the settings for the servomotor are still incomplete and an alarm occurs.
4
4-37
4-38
4 Operation
4.7.6 Multiturn Limit Disagreement Alarm (A.CC0)
7.
Return to the SigmaWin+ main window. To make the settings for the servomotor, click Setup –
Multi-Turn Limit Setting again.
A verification message will appear confirming if you want to continue although the position data will change.
MEC
HA
8.
Click Continue .
The Multi-Turn Limit Setting box will appear. To change the settings, click Re-Change .
MEC
HA
9.
To save the settings, click Writing into the Motor .
A warning message will appear.
MEC
HA
10.
Click OK .
4.7 Absolute Encoders
4.7.7
Absolute Encoder Origin Offset
If using the absolute encoder, the positions of the encoder and the offset of the machine coordinate system
(APOS) can be set. Use Pn808 to make the setting. After the SENS_ON command is received by MECHA-
TROLINK communications, this parameter will be enabled.
Pn808
Absolute Encoder Origin Offset
Setting Range
-1073741823 to
1073741823
Setting Unit
1 reference unit
Position
Factory Setting When Enabled
0 Immediately
<Example>
If the encoder position (X) is set at the origin of the machine coordinate system (0), Pn808 = X.
Classification
Setup
Origin
MECHA
Machine coordinate system position
(APOS)
Encoder position
Encoder position: Origin
Pn808 Encoder position
4
4-39
4-40
4 Operation
4.8.1 Servo Alarm Output Signal (ALM)
4.8
Other Output Signals
This section explains other output signals.
Use these signals according to the application needs, e.g., for machine protection.
4.8.1
Servo Alarm Output Signal (ALM)
This section describes signals that are output when the SERVOPACK detects errors and resetting methods.
(1) Servo Alarm Output Signal (ALM)
This signal is output when the SERVOPACK detects an error.
Configure an external circuit so that this alarm output turns OFF the main circuit power supply for the SERVOPACK whenever an error occurs.
Type
Signal
Name
Connector
Pin Number
Setting Meaning
Output ALM CN1-4
ON (closed)
OFF (open)
Normal SERVOPACK status
SERVOPACK alarm status
(2) Alarm Reset Method
If a servo alarm (ALM) occurs, use one of the following methods to reset the alarm after eliminating the cause of the alarm.
Be sure to eliminate the cause of the alarm before resetting it.
If the alarm is reset and operation continued without eliminating the cause of the alarm, it may result in damage to the equipment or fire.
Resetting Alarms by Sending Clear Warning or Alarm Command (ALM_CLR)
For details, refer to Σ -V Series User’s Manual, MECHATROLINK-III Standard Servo Profile Command
(Manual No.: SIEP S800000 63).
s
4.8.2
Warning Output Signal (/WARN)
This signal is for a warning issued before the occurrence of an alarm.
Refer to 8.2.1 List of Warnings .
Signal Specifications
Type
Signal
Name
Connector Pin
Number
Setting Meaning
Output /WARN Must be allocated
ON (closed)
OFF (open)
Warning status
Normal status
Note: Use parameter Pn50F.3 to allocate the /WARN signal for use. For details, refer to 3.3.2 Output Signal Allocations .
4.8 Other Output Signals
4.8.3
Rotation Detection Output Signal (/TGON)
This output signal indicates that the servomotor is rotating at the speed set for Pn502 or a higher speed.
(1) Signal Specifications
Type
Signal
Name
Connector Pin
Number
Setting Meaning
Output /TGON Must be allocated
ON (closed)
OFF (open)
Servomotor is rotating with the motor speed above the setting in Pn502.
Servomotor is rotating with the motor speed below the setting in Pn502.
Note: Use parameter Pn50E.2 to allocate the /TGON signal for use. For details, refer to 3.3.2 Output Signal Allocations .
(2) Related Parameter
Set the range in which the /TGON signal is output using the following parameter.
Pn502
Rotation Detection Level
Setting Range
1 to 10000
Setting Unit
1 min
-1
Speed Position Torque
Factory Setting When Enabled
20 Immediately
Classification
Setup
4.8.4
Servo Ready Output Signal (/S-RDY)
This signal is turned ON when the SERVOPACK is ready to accept the servo ON (SV_ON) command.
The /S-RDY signal is turned ON under the following conditions.
• The main circuit power supply is ON.
• No servo alarms
• The Turn Sensor ON (SENS_ON) command is received. (When an absolute encoder is used.)
• If an absolute encoder is used, the output of absolute data to the host controller must have been completed when the SENS_ON command is received.
(1) Signal Specifications
Type
Signal
Name
Connector Pin
Number
Setting Meaning
Output /S-RDY Must be allocated
ON (closed)
OFF (open)
The SERVOPACK is ready to accept the SV_ON command.
The SERVOPACK is not ready to accept the
SV_ON command.
Note: Use parameter Pn50E.3 to allocate the /S-RDY signal for use. For details, refer to 3.3.2 Output Signal Allocations .
4
4-41
4-42
4 Operation
4.8.5 Speed Coincidence Output Signal (/V-CMP)
4.8.5
Speed Coincidence Output Signal (/V-CMP)
The speed coincidence output signal (/V-CMP) is output when the actual servomotor speed is the same as the reference speed. The host controller uses the signal as an interlock. This signal is the output signal during speed control.
Type
Signal
Name
Connector Pin
Number
Setting Meaning
Output /V-CMP Must be allocated
ON (closed)
OFF (open)
Speed coincides.
Speed does not coincide.
Note: Use parameter Pn50E.1 to allocate the /V-CMP signal for use. Refer to 3.3.2 Output Signal Allocations for details.
Pn503
Speed Coincidence Signal Output Width
Setting Range
0 to 100
Setting Unit
1 min
-1
Speed
Factory Setting
10
When Enabled
Immediately
Classification
Setup
The /V-CMP signal is output when the difference between the reference speed and actual motor speed is below this setting.
Motor speed
Pn503
Reference speed
/V-CMP is output in this range.
<Example>
The /V-CMP signal is output at 1900 to 2100 min
-1
if the Pn503 is set to 100 and the reference speed is 2000 min -1 .
4.8 Other Output Signals
4.8.6
Positioning Completed Output Signal (/COIN)
This signal indicates that servomotor movement has been completed during position control.
When the difference between the number of references output by the host controller and the travel distance of the servomotor (position error) drops below the set value in the parameter, the positioning completion signal will be output.
Use this signal to check the completion of positioning from the host controller.
Type
Signal
Name
Output /COIN
Connector
Pin Number
Must be allocated
Setting
ON (closed)
OFF (open)
Meaning
Positioning has been completed.
Positioning is not completed.
Note: Use parameter Pn50E.0 to allocate the /COIN signal for use. Refer to 3.3.2 Output Signal Allocations for details.
Pn522
Positioning Completed Width
Setting Range
0 to 1073741824
Setting Unit
1 reference unit
Factory Setting
7
Position
When Enabled
Immediately
The positioning completed width setting has no effect on final positioning accuracy.
Classification
Setup
Reference
Motor speed
Motor speed
Position error
/COIN
Pn522
Time
Time
Time
Effective at ON (close).
Note: If the parameter is set to a value that is too large, a positioning completed signal might be output if the position error is low during a low speed operation. This will cause the positioning completed signal to be output continuously. If this signal is output unexpectedly, reduce the set value until it is no longer output.
If the position error is kept to a minimum when the positioning completed width is small, use Pn207.3 to change output timing for the /COIN signal.
Pn207
Parameter Name Meaning n.0
[Factory setting] n.1
n.2
/COIN Output
Timing
When the absolute value of the position error is below the positioning completed width (Pn522).
When the absolute value of the position error is below the positioning completed width (Pn522), and the reference after applying the position reference filter is 0.
When the absolute value of the position error is below the positioning completed width (Pn522), and the position reference input is 0.
When
Enabled
After restart
Classification
Setup
4
4-43
4-44
4 Operation
4.8.7 Positioning Near Output Signal (/NEAR)
4.8.7
Positioning Near Output Signal (/NEAR)
Before confirming that the positioning completed signal has been received, the host controller first receives a positioning near signal and can prepare the operating sequence after positioning has been completed. The time required for this sequence after positioning can be shortened.
This signal is generally used in combination with the positioning completed output signal.
Type
Signal
Name
Connector
Pin Number
Setting Meaning
Output /NEAR Must be allocated
ON (closed)
OFF (open)
The servomotor has reached a point near to positioning completed.
The servomotor has not reached a point near to positioning completed.
Note: Use parameter Pn510.0 to allocate the /NEAR signal for use. Refer to 3.3.2 Output Signal Allocations for details.
NEAR Signal Width
Position
When Enabled
Immediately
Classification
Pn524 Setting Range
1 to 1073741824
Setting Unit
1 reference unit
Factory Setting
1073741824 Setup
The positioning near signal (/NEAR) is output when the difference between the number of references output by the host controller and the travel distance of the servomotor (position error) is less than the set value.
Motor speed Reference
Motor speed
Position error
0
/NEAR
/COIN
Pn524 Pn522 Time
Time
Time
Effective at ON (close).
Effective at ON (close).
Time
Note: Normally, the value of Pn524 should be larger than that for the positioning completed width (Pn522).
4.8.8
Speed Limit Detection Signal (/VLT)
This function limits the speed of the servomotor to protect the machine.
A servomotor in torque control is controlled to output the specified torque, but the motor speed is not controlled. Therefore, if an excessive reference torque is set for the load torque on the machinery side, the speed of the servomotor may increase greatly. If that may occur, use this function to limit the speed.
Note: The actual limit value of motor speed depends on the load conditions of the servomotor.
With No Speed Limit With Speed Limit
Motor speed
Maximum speed
Danger of damage due to critical speed.
Motor speed
Safe operation with speed limit.
Limiting speed
Time
Time
Refer to the following parameters for speed limit.
4.8 Other Output Signals
(1) Signals Output during Servomotor Speed Limit
The following signal is output when the motor speed reaches the limit speed.
Type
Signal
Name
Connector
Pin Number
Setting Meaning
Output /VLT Must be allocated
ON (closed)
OFF (open)
Servomotor speed limit being applied.
Servomotor speed limit not being applied.
Note: Use parameter Pn50F.1 to allocate the /VLT signal for use. For details, refer to 3.3.2 Output Signal Allocations .
(2) Speed Limit Setting
Select the speed limit mode with Pn002.1.
Parameter Meaning
When
Enabled
Classification
Pn002 n.
0
[Factory setting] n.
1
VLIM (the speed limit value during torque control) is not available. Uses the value set in Pn407 as the speed limit (internal speed limit function).
VLIM operates as the speed limit value (external speed limit function).
After restart Setup
Internal Speed Limit Function
If the internal speed limit function is selected in Pn002.1, set the limit of the maximum speed of the servomotor in Pn407. The limit of the speed in Pn408.1 can be either the maximum speed of the servomotor or the overspeed alarm detection speed. Select the overspeed alarm detection speed to limit the speed to the maximum speed of the servomotor or the equivalent.
Pn407
Speed Limit During Torque Control
Setting Range
0 to 10000
Setting Unit
1 min
-1
Factory Setting
10000
Torque
When Enabled
Immediately
Classification
Setup
Note: The servomotor’s maximum speed or the overspeed alarm detection speed will be used when the setting in this parameter exceeds the maximum speed of the servomotor used.
Parameter Meaning
When
Enabled
Classification
Pn408 n.
0
[Factory setting] n.
1
Uses the smaller value of the maximum motor speed and the value of Pn407 as the speed limit value.
Uses the smaller value of the overspeed alarm detection speed and the value of Pn407 as speed limit value.
After restart Setup
External Speed Limit Function
If the external speed limit function is selected in Pn002.1, the motor speed is controlled by the speed limit value (VLIM). For details, refer to Σ -V Series User’s Manual, MECHATROLINK-III Standard Servo Profile
Commands (Manual No.: SIEP S800000 63).
4
4-45
5
Adjustments
5.1 Type of Adjustments and Basic Adjustment Procedure . . . . . . . . . . . . . . 5-3
5.1.1 Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5.1.2 Basic Adjustment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5.1.3 Monitoring Operation during Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.1.4 Safety Precautions on Adjustment of Servo Gains . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5.2 Tuning-less Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.2.1 Tuning-less Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5.2.2 Tuning-less Levels Setting (Fn200) Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5.2.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5.3 Advanced Autotuning (Fn201) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.3.1 Advanced Autotuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18
5.3.2 Advanced Autotuning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5.3.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-33
5.4 Advanced Autotuning by Reference (Fn202) . . . . . . . . . . . . . . . . . . . . . 5-34
5.4.1 Advanced Autotuning by Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-34
5.4.2 Advanced Autotuning by Reference Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
5.4.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
5.5 One-parameter Tuning (Fn203) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.5.1 One-parameter Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.5.2 One-parameter Tuning Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
5.5.3 One-parameter Tuning Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-52
5.5.4 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-53
5.6 Anti-Resonance Control Adjustment Function (Fn204) . . . . . . . . . . . . . 5-54
5.6.1 Anti-Resonance Control Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure . . . . . . . . . . . . 5-55
5.6.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-63
5.7 Vibration Suppression Function (Fn205) . . . . . . . . . . . . . . . . . . . . . . . . 5-64
5.7.1 Vibration Suppression Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-64
5.7.2 Vibration Suppression Function Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . 5-65
5.7.3 Related Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-70
5
5-1
5-2
5 Adjustments
5.8 Additional Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-71
5.8.1 Switching Gain Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-71
5.8.2 Manual Adjustment of Friction Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-75
5.8.3 Current Control Mode Selection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
5.8.4 Current Gain Level Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
5.8.5 Speed Detection Method Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-77
5.8.6 Backlash Compensation Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-78
5.9 Compatible Adjustment Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-84
5.9.1 Feedforward Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-84
5.9.2 Mode Switch (P/PI Switching) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-85
5.9.3 Torque Reference Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-87
5.9.4 Position Integral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-89
5.1 Type of Adjustments and Basic Adjustment Procedure
5.1
Type of Adjustments and Basic Adjustment Procedure
This section describes type of adjustments and the basic adjustment procedure.
5.1.1
Adjustments
Adjustments (tuning) are performed to optimize the responsiveness of the SERVOPACK.
The responsiveness is determined by the servo gain that is set in the SERVOPACK.
The servo gain is set using a combination of parameters, such as speed loop gain, position loop gain, filters, friction compensation, and moment of inertia ratio. These parameters influence each other. Therefore, the servo gain must be set considering the balance between the set values.
Generally, the responsiveness of a machine with high rigidity can be improved by increasing the servo gain. If the servo gain of a machine with low rigidity is increased, however, the machine will vibrate and the responsiveness may not be improved. In such case, it is possible to suppress the vibration with a variety of vibration suppression functions in the SERVOPACK.
The servo gains are factory-set to appropriate values for stable operation. The following utility function can be used to adjust the servo gain to increase the responsiveness of the machine in accordance with the actual conditions. With this function, parameters related to adjustment above will be adjusted automatically and the need to adjust them individually will be eliminated.
This section describes the following utility adjustment functions. The SigmaWin+ is required to make adjustments.
Utility Function for
Adjustment
Tuning-less
Levels Setting
(Fn200)
Advanced Autotuning
(Fn201)
Advanced Autotuning by
Reference (Fn202)
One-parameter Tuning
(Fn203)
Outline
Applicable Control
Method
This function is enabled when the factory settings are used. This function can be used to obtain a stable response regardless of the type of machine or changes in the load.
The following parameters are automatically adjusted using internal references in the SERVOPACK during automatic operation.
• Moment of inertia ratio
• Gains (position loop gain, speed loop gain, etc.)
• Filters (torque reference filter, notch filter)
• Friction compensation
• Anti-resonance control adjustment function
• Vibration suppression function
The following parameters are automatically adjusted with the position reference input from the host controller while the machine is in operation.
• Gains (position loop gain, speed loop gain, etc.)
• Filters (torque reference filter, notch filter)
• Friction compensation
• Anti-resonance control adjustment function
• Vibration suppression function
The following parameters are manually adjusted with the position or speed reference input from the host controller while the machine is in operation.
• Gains (position loop gain, speed loop gain, etc.)
• Filters (torque reference filter, notch filter)
• Friction compensation
• Anti-resonance control adjustment function
Speed and Position
Speed and Position
Position
Speed and Position
Anti-Resonance Control
Adjustment Function
(Fn204)
Vibration Suppression
Function (Fn205)
This function effectively suppresses continuous vibration.
Speed and Position
This function effectively suppresses residual vibration if it occurs when positioning.
Position
5
5-3
5-4
5 Adjustments
5.1.2 Basic Adjustment Procedure
5.1.2
Basic Adjustment Procedure
The basic adjustment procedure is shown in the following flowchart. Make suitable adjustments considering the conditions and operating requirements of the machine.
Start adjusting servo gain.
(1) Adjust using Tuning-less Function.
Runs the servomotor without any adjustments.
Refer to 5.2 Tuning-less Function .
Results OK?
Yes
Completed.
No
(2) Adjust using Advanced Autotuning.
Automatically adjusts the moment of inertia ratio, gains, and filters with internal references in the SERVOPACK.
Refer to 5.3 Advanced Autotuning (Fn201) .
Results OK?
Yes
Completed.
No
(3) Adjust using Advanced Autotuning by Reference.
Automatically adjusts gains and filters with user reference inputs.
Refer to 5.4 Advanced Autotuning by Reference (Fn202) .
Results OK?
Yes
Completed.
No
(4) Adjust using One-parameter Tuning.
Manually adjusts gains and filters.
Position loop gain, speed loop gain, filters, and friction compensation adjustments are available.
Refer to 5.5 One-parameter Tuning (Fn203) .
Results OK?
Yes
Completed.
No
Continuous vibration occurs.
Reduce the vibration using Anti-resonance Control Adjustment Function.
Refer to 5.6 Anti-Resonance Control Adjustment Function (Fn204) .
Residual vibration occurs at positioning.
Reduce the vibration using Vibration Suppression Function.
Refer to 5.7 Vibration Suppression Function (Fn205) .
No
Results OK?
Yes
Completed.
5.1 Type of Adjustments and Basic Adjustment Procedure
5.1.3
Monitoring Operation during Adjustment
While adjusting the servo gain, always monitor the operating status of the machine and the signal waveform.
Connect a measurement instrument, such as a memory recorder, to the SERVOPACK to monitor the signal waveform.
The settings and parameters that are related to monitoring the analog signal are described in the following sections.
(1) Connecting the Measurement Instrument
Use the external monitor connector (CN5) on the SERVOPACK to connect the measurement instrument. The devices and cables that are required for connection are listed below.
• Analog monitor unit (model: JUSP-PC001-E)
• Analog monitor unit connection cable (model: JZSP-CF1S06-A3-E)
• Analog monitor cable (model: JZSP-CA01-E)
Connection examples are shown below.
Connection cable for analog monitor unit
Analog monitor unit
Cable for analog monitor
White
Black
M-III
Measuring probe
Probe GND
Measuring probe
Measuring instrument*
Red
Black
Probe GND
∗ Measuring instrument is not included.
Line Color Signal Name
White Analog monitor 1
Red Analog monitor 2
Black (2 lines) GND
Factory Setting
Torque reference: 1 V/100% rated torque
Motor speed: 1 V/1000 min
-1
Analog monitor GND: 0 V
(2) Monitor Signal
The shaded parts in the following diagram indicate analog output signals that can be monitored.
Torque reference
Speed reference
CN6A/CN6B
SERVOPACK
Speed feedforward
Position reference
Torque feedforward
MECHA
Position reference speed
Speed conversion
Position loop
Electronic gear
Backlash compensation
-
+
Position amplifier error
Error counter
Kp
+
+
-
Error counter
1
Electronic gear
Motor rotational speed
Position error
Positioning completed
Completion of position reference
Speed reference
Active gain
-
+ +
Speed loop
+ +
Torque reference
CN4
Current loop
(U/V/W)
CN2
Speed conversion
M
ENC
Load
5
5-5
5-6
5 Adjustments
5.1.3 Monitoring Operation during Adjustment
The following signals can be monitored by selecting functions with parameters Pn006 and Pn007.
Pn006 is used for analog monitor 1 and Pn007 is used for analog monitor 2.
Description
Unit Remarks
Parameter
Monitor Signal n.
00
[Pn007
Factory
Setting]
Motor rotating speed n.
01 Speed reference n.
02
[Pn006
Factory
Setting]
Torque reference n.
03 Position error n.
04 Position amplifier error
Pn006
Pn007 n.
05 Position reference speed n.
06 n.
07
Reserved (Do not change.) n.
08 Positioning completed n.
09 Speed feedforward n.
0A Torque feedforward n.
0B Active gain
* n.
0C Completion of position reference n.
0D Reserved (Do not change.)
1 V/1000 min
-1
1 V/1000 min
-1
−
−
1 V/100% rated torque −
0.05 V/1 reference unit 0 V at speed/torque control
0.05 V/1 encoder pulse unit
Position error after electronic gear conversion
1 V/1000 min
-1 −
− −
Positioning completed:
5 V
Positioning not completed: 0 V
Completion indicated by output voltage.
1 V/1000 min
-1 −
1 V/100% rated torque −
1st gain: 1 V
2nd gain: 2 V
Gain type indicated by output voltage.
Completed: 5 V
Not completed: 0 V
−
Completion indicated by output voltage.
−
∗ Refer to 5.8.1 Switching Gain Settings for details.
5.1 Type of Adjustments and Basic Adjustment Procedure
(3) Setting Monitor Factor
The output voltages on analog monitors 1 and 2 are calculated by the following equations.
Analog monitor 1 output voltage = (-1)
Analog monitor 2 output voltage = (-1)
×
×
Signal selection
(Pn006=n.00
غغ )
Signal selection
(Pn007=n.00
غغ )
×
Multiplier + Offset voltage [V]
(Pn552)
(Pn550)
×
Multiplier + Offset voltage [V]
(Pn553) (Pn551)
<Example>
Analog monitor output at n.
00 (motor rotating speed setting)
When multiplier is set to
×
1:
Analog monitor output voltage [V]
+6 V
When multiplier is set to
×
10:
Analog monitor output voltage [V]
+10 V (approx.)
+8 V
+6 V
-6000
+6000 Motor speed
[min -1 ]
-800 -600
+600 +800 Motor speed
[min -1 ]
-6 V
-6 V
-8 V
-10 V (approx.)
Note: Linear effective range: within ± 8 V
Output resolution: 16-bit
(4) Related Parameters
Use the following parameters to change the monitor factor and the offset.
Pn550
Pn551
Pn552
Pn553
Analog Monitor 1 Offset Voltage
Setting Range
-10000 to 10000
Setting Unit
0.1 V
Analog Monitor 2 Offset Voltage
Setting Range
-10000 to 10000
Setting Unit
0.1 V
Analog Monitor Magnification ( × 1)
Setting Range
-10000 to 10000
Setting Unit
× 0.01
Analog Monitor Magnification ( × 2)
Setting Range
-10000 to 10000
Setting Unit
× 0.01
Speed Position Torque
Factory Setting
0
When Enabled
Immediately
Speed Position Torque
Factory Setting
0
When Enabled
Immediately
Speed Position Torque
Factory Setting
100
When Enabled
Immediately
Speed Position Torque
Factory Setting
100
When Enabled
Immediately
Classification
Setup
Classification
Setup
Classification
Setup
Classification
Setup
5
5-7
5-8
5 Adjustments
5.1.4 Safety Precautions on Adjustment of Servo Gains
5.1.4
Safety Precautions on Adjustment of Servo Gains
CAUTION
• If adjusting the servo gains, observe the following precautions.
• Do not touch the rotating section of the servomotor while power is being supplied to the motor.
• Before starting the servomotor, make sure that the SERVOPACK can come to an emergency stop at any time.
• Make sure that a trial operation has been performed without any trouble.
• Install a safety brake on the machine.
Set the following protective functions of the SERVOPACK to the correct settings before starting to adjust the servo gains.
(1) Overtravel Function
Set the overtravel function. For details on how to set the overtravel function, refer to 4.3.2 Overtravel .
(2) Torque Limit
The torque limit calculates the torque required to operate the machine and sets the torque limits so that the output torque will not be greater than required. Setting torque limits can reduce the amount of shock applied to the machine when troubles occur, such as collisions or interference. If a torque limit is set lower than the value that is needed for operation, overshooting or vibration can be occurred.
For details, refer to 4.6 Limiting Torque .
(3) Excessive Position Error Alarm Level
The excessive position error alarm is a protective function that will be enabled when the SERVOPACK is used in position control.
If this alarm level is set to a suitable value, the SERVOPACK will detect an excessive position error and will stop the servomotor if the servomotor does not operate according to the reference. The position error indicates the difference between the position reference value and the actual motor position.
The position error can be calculated from the position loop gain (Pn102) and the motor speed with the following equation.
Position Error [reference unit] =
Motor Speed [min ]
60
Encoder Resolution
Pn102 [0.1/s]/10 *2
• Excessive Position Error Alarm Level (Pn520 [1 reference unit])
*1
Pn210
Pn20E
Pn520 >
60
×
Encoder Resolution
Pn102 [0.1/s]/10 *2
*1
×
Pn210
Pn20E
× (1.2 to 2)
∗1.
Refer to 4.4.3 Electronic Gear .
∗2.
To check the Pn102 setting, change the parameter display setting to display all parameters (Pn00B.0 = 1).
At the end of the equation, a coefficient is shown as " × (1.2 to 2).
" This coefficient is used to add a margin that prevents a position error overflow alarm (A.d00) from occurring in actual operation of the servomotor.
Set the level to a value that satisfies these equations, and no position error overflow alarm (A.d00) will be generated during normal operation. The servomotor will be stopped, however, if it does not operate according to the reference and the SERVOPACK detects an excessive position error.
The following example outlines how the maximum limit for position deviation is calculated. These conditions apply.
•
• Maximum speed = 6000
• Encoder resolution = 131072 (17 bits)
• Pn102 = 400
Pn210
Pn20E
=
1
1
5.1 Type of Adjustments and Basic Adjustment Procedure
Under these conditions, the following equation is used to calculate the maximum limit (Pn520).
Pn520 =
=
6000
60
×
327680 × 2
131072
400/10
×
1
1
× 2
= 655360
If the acceleration/deceleration of the position reference exceeds the capacity of the servomotor, the servomotor cannot perform at the requested speed, and the allowable level for position error will be increased as not to satisfy these equations. If so, lower the level of the acceleration/deceleration for the position reference so that the servomotor can perform at the requested speed or increase the excessive position error alarm level
(Pn520).
Related Parameter
Pn520
Excessive Position Error Alarm Level
Setting Range
1 to 1073741823
Setting Unit
1 reference unit
Position
Factory Setting
5242880
When Enabled
Immediately
Related Alarm
Alarm
Display
A.d00
Alarm Name Meaning
Position Error Overflow Position errors exceeded parameter Pn520.
Classification
Setup
(4) Vibration Detection Function
Set the vibration detection function to an appropriate value with the vibration detection level initialization
(Fn01B). For details on how to set the vibration detection function, refer to 6.15 Vibration Detection Level
Initialization (Fn01B) .
(5) Excessive Position Error Alarm Level at Servo ON
If position errors remain in the error counter when turning ON the servomotor power, the servomotor will move and this movement will clear the counter of all position errors. Because the servomotor will move suddenly and unexpectedly, safety precautions are required. To prevent the servomotor from moving suddenly, select the appropriate level for the excessive position error alarm level at servo ON (Pn526) to restrict operation of the servomotor.
Related Parameters
Pn526
Excessive Position Error Alarm Level at Servo ON
Setting Range
1 to 1073741823
Setting Unit
1 reference unit
Position
Factory Setting
5242880
When Enabled
Immediately
Classification
Setup
Pn528
Excessive Position Error Warning Level at Servo ON
Setting Range
10 to 100
Setting Unit
1%
Position
Factory Setting
100
Pn529
Speed Limit Level at Servo ON
Setting Range
0 to 10000
Setting Unit
1 min
-1
Position
Factory Setting
10000
When Enabled
Immediately
Classification
Setup
When Enabled
Immediately
Classification
Setup
5
5-9
5-10
5 Adjustments
5.1.4 Safety Precautions on Adjustment of Servo Gains
Related Alarms
Alarm
Display
Alarm Name Meaning
A.d01
A.d02
Position Error Overflow
Alarm at Servo ON
Position Error Overflow
Alarm by Speed Limit at
Servo ON
This alarm occurs if the servomotor power is turned ON when the position error is greater than the set value of Pn526 while the servomotor power is
OFF.
When the position errors remain in the error counter, Pn529 limits the speed if the servomotor power is turned ON. If Pn529 limits the speed in such a state, this alarm occurs when position references are input and the number of position errors exceeds the value set for the excessive position error alarm level (Pn520).
When an alarm occurs, refer to 8 Troubleshooting and take the corrective actions.
5.2 Tuning-less Function
5.2
Tuning-less Function
The tuning-less function is enabled in the factory settings. If resonance is generated or excessive vibration occurs, refer to 5.2.2 Tuning-less Levels Setting (Fn200) Procedure and change the set value of Pn170.2 for the rigidity level and the set value in Pn170.3 for the load level.
CAUTION
• The tuning-less function is enabled in the factory settings. A sound may be heard for a moment when the
SV_ON command is received for the first time after the servo drive is mounted to the machine. This sound does not indicate any problems; it means that the automatic notch filter was set. The sound will not be heard from the next time the SV_ON command is received. For details on the automatic notch filter, refer to (3) Automatically Setting the Notch Filter on the next page.
• The servomotor may vibrate if the load moment of inertia exceeds the allowable load value.
If vibration occurs, set the load level to mode 2 in the Pn170 parameter or lower the rigidity level.
5.2.1
Tuning-less Function
The tuning-less function obtains a stable response without manual adjustment regardless of the type of machine or changes in the load.
(1) Enabling/Disabling Tuning-less Function
The following parameter is used to enable or disable the tuning-less function.
Pn170
Parameter n.
0 n.
1
[Factory setting] n.
0
[Factory setting]
Meaning
Disables tuning-less function.
Enables tuning-less function.
Used as speed control.
When Enabled Classification
After restart Setup n.
1
Used as speed control and host controller used as position control.
(2) Application Restrictions
The tuning-less function can be used in position control or speed control. This function is not available in torque control. The following application restrictions apply to the tuning-less function.
Vibration detection level initialization
(Fn01B)
Function
Advanced autotuning (Fn201)
Advanced autotuning by reference (Fn202)
One-parameter tuning (Fn203)
Anti-resonance control adjustment function (Fn204)
Vibration suppression function (Fn205)
EasyFFT (Fn206)
Friction compensation
Gain switching
Availability
Available
Available
(Some conditions apply)
Not available
Not available
Not available
Not available
Available
Not available
Not available
Remarks
–
• This function can be used when the moment of inertia is calculated.
• While this function is being used, the tuning-less function cannot be used. After completion of the autotuning, it can be used again.
–
–
–
–
While this function is being used, the tuningless function cannot be used. After completion of the EasyFFT, it can be used again.
–
–
5
5-11
5-12
5 Adjustments
5.2.1 Tuning-less Function
Function
Offline moment of inertia calculation *
Mechanical analysis*
Availability
Not available
Available
(cont’d)
Remarks
Disable the tuning-less function by setting
Pn170.0 to 0 before executing this function.
While this function is being used, the tuningless function cannot be used. After completion of the analysis, it can be used again.
∗ Operate using SigmaWin+.
(3) Automatically Setting the Notch Filter
Usually, set this function to Auto Setting. (The notch filter is factory-set to Auto Setting.)
If this function is set to Auto Setting, vibration will be detected automatically and the notch filter will be set when the tuning-less function is enabled.
Set this function to Not Auto Setting only if you do not change the notch filter setting before executing tuningless function.
Pn460
Parameter n.
0 n.
1
[Factory setting]
Meaning
Does not set the 2nd notch filter automatically with utility function.
Set the 2nd notch filter automatically with utility function.
When Enabled Classification
Immediately Tuning
(4) Tuning-less Level Settings
Two tuning-less levels are available: the rigidity level and load level. Both levels can be set in the Pn170 parameter.
Rigidity Level
Pn170
Parameter n.
0 n.
1 n.
2 n.
3 n.
4
[Factory setting]
Meaning
Rigidity level 0 (Level 0)
Rigidity level 1 (Level 1)
Rigidity level 2 (Level 2)
Rigidity level 3 (Level 3)
Rigidity level 4 (Level 4)
Load Level
Pn170
Parameter n.0
n.1
[Factory setting] n.2
Meaning
Load level : Low (Mode 0)
Load level : Medium (Mode 1)
Load level : High (Mode 2)
When Enabled Classification
Immediately
When Enabled Classification
Immediately
Setup
Setup
5.2 Tuning-less Function
5.2.2
Tuning-less Levels Setting (Fn200) Procedure
CAUTION
• To ensure safety, perform the tuning-less function in a state where the SERVOPACK can come to an emergency stop at any time.
The procedure to use the tuning-less function is given below.
The SigmaWin+ is required to execute this function.
(1) Preparation
The following conditions must be met to perform the tuning-less function.
• The tuning-less function must be enabled (Pn170.0 = 1).
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The test without a motor function must be disabled. (Pn00C.0 = 0).
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Parameters - Edit Parameters .
The Parameter Editing dialog box will appear.
ME-
CHA
5
5-13
5-14
5 Adjustments
5.2.2 Tuning-less Levels Setting (Fn200) Procedure
2.
Select Pn170 in the Parameter Editing dialog box.
If Pn170 cannot be seen in the Parameter Editing dialog box, click the arrows to view the parameter.
ME-
CHA
3.
Click Edit .
The Edit box for Pn170 will appear.
ME-
CHA
5.2 Tuning-less Function
4.
For 3rd digit, select one of the load levels in the Tuning-less Load Level list.
• If the response waveform results in overshooting or if the load moment of inertia exceeds the allowable level, select 2: Tuning-less Load Level 2 . (If any damage caused when the load moment of inertia exceeds the allowable level, these conditions are regarded as being outside the scope of the warranty.)
• If a high-frequency noise is heard, select 0: Tuning-less Load Level 0 .
ME-
CHA
5.
For 2nd digit, select one of the tuning-less levels in the Tuning-less Level list.
The higher the value of the level is, the higher the gain will be. A higher gain means better response.
Note 1. If the tuning-less level is too high, vibration might occur. Lower the level if vibration occurs.
2. If the tuning-less level is changed, the automatically set notch filter will be canceled (disabled). If any vibration occurs, the notch filter will automatically be set again.
ME-
CHA
6.
Click OK .
7.
To enable the change in the setting, restart the SERVOPACK.
5
5-15
5-16
5 Adjustments
5.2.2 Tuning-less Levels Setting (Fn200) Procedure
(3) Alarm and Corrective Actions
The autotuning alarm (A.521) will occur if resonance sound is generated or excessive vibration occurs during position control. In such case, take the following actions.
• Increase the setting of Pn170.3 or reduce the setting of Pn170.2.
(4) Parameters Disabled by Tuning-less Function
When the tuning-less function is enabled in the factory settings, the settings of these parameters are not available: Pn100, Pn101, Pn102, Pn103, Pn104, Pn105, Pn106, Pn160, Pn139, and Pn408. These gain-related parameters, however, may become effective depending on the executing conditions of the functions specified in the following table. For example, if EasyFFT is executed when the tuning-less function is enabled, the settings in Pn100, Pn104, Pn101, Pn105, Pn102, Pn106, and Pn103, as well as the manual gain switch setting, will be enabled, but the settings in Pn408.3, Pn160.0, and Pn139.0 will be not enabled
.
Item
Parameters Disabled by Tuning-less Function
Name Pn Number
Gain
Advanced
Control
Speed Loop Gain
2nd Speed Loop Gain
Speed Loop Integral Time Constant
2nd Speed Loop Integral Time Constant
Position Loop Gain
2nd Position Loop Gain
Moment of Inertia Ratio
Friction Compensation Function Selection
Anti-resonance Control Adjustment
Selection
Gain
Switching
Gain Switching Selection Switch
Pn100
Pn104
Pn101
Pn105
Pn102
Pn106
Pn103
Pn408.3
Pn160.0
Pn139.0
∗ : Parameter enabled
× : Parameter disabled
(5) Tuning-less Function Type
The following table shows the types of tuning-less functions.
Pn14F
Parameter n.
0 n.
1
[Factory setting]
Meaning
Tuning-less type 1
Tuning-less type 2
(The level of noise produced is lower than that of
Type 1.)
Related Functions and Parameters*
Torque
Control
Easy
FFT
Mechanical
Analysis
(Vertical Axis
Mode)
×
×
×
×
×
×
×
×
×
×
×
When Enabled Classification
After restart
Tuning
5.2 Tuning-less Function
5.2.3
Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn170
Pn401
Pn40C
Pn40D
Name
Tuning-less Function Related Switch
Torque Reference Filter Time Constant
2nd Notch Filter Frequency
2nd Notch Filter Q Value
Mid-execution changes
No
No
No
No
Automatic changes
Yes
Yes
Yes
Yes
5
5-17
5-18
5 Adjustments
5.3.1 Advanced Autotuning
5.3
Advanced Autotuning (Fn201)
This section describes the adjustment using advanced autotuning.
• Advanced autotuning starts adjustments based on the set speed loop gain (Pn100).
Therefore, precise adjustments cannot be made if there is vibration when starting adjustments. In this case, make adjustments after lowering the speed loop gain
(Pn100) until vibration is eliminated.
• Before performing advanced autotuning with the tuning-less function enabled
(Pn170.0 = 1: Factory setting), always set Jcalc to ON to calculate the load moment of inertia. The tuning-less function will automatically be disabled, and the gain will be set by advanced autotuning.
With Jcalc set to OFF so the load moment of inertia is not calculated, "Error" will be displayed on the panel operator, and advanced autotuning will not be performed.
• If the operating conditions, such as the machine-load or drive system, are changed after advanced autotuning, then change the following related parameters to disable any values that were adjusted before performing advanced autotuning once again with the setting to calculate the moment of inertia (Jcalc = ON). If advanced autotuning is performed without changing the parameters, machine vibration may occur, resulting in damage to the machine.
Pn00B.0=1 (Displays all parameters.)
Pn140.0=0 (Does not use model following control.)
Pn160.0=0 (Does not use anti-resonance control.)
Pn408=n.00
0 (Does not use friction compensation, 1st notch filter, or 2nd notch filter.)
5.3.1
Advanced Autotuning
Advanced autotuning automatically operates the servo system (in reciprocating movement in the forward and reverse directions) within set limits and adjust the SERVOPACK automatically according to the mechanical characteristics while the servo system is operating.
Advanced autotuning can be performed without connecting the host controller.
The following automatic operation specifications apply.
• Maximum speed: Rated motor speed × 2/3
• Acceleration torque: Approximately 100% of rated motor torque
The acceleration torque varies with the influence of the moment of inertia ratio
(Pn103), machine friction, and external disturbance.
• Travel distance: The travel distance can be set freely. The distance is factory-set to a value equivalent to 3 motor rotations.
Movement
Speed
M-III
Travel distance
Rated motor speed
×
2/3 t: time
Reference
Response
SERVOPACK
Execute advanced autotuning after a JOG operation to move the position to ensure a suitable movement range.
Rated motor speed
×
2/3
Rated motor torque
Approx. 100%
Rated motor torque
Approx. 100%
Automatic operation t: time
5.3 Advanced Autotuning (Fn201)
Advanced autotuning performs the following adjustments.
• Moment of inertia ratio
• Gains (e.g., position loop gain and speed loop gain)
• Filters (torque reference filter and notch filter)
• Friction compensation
• Anti-resonance control
• Vibration suppression (Mode = 2 or 3)
Refer to 5.3.3 Related Parameters for parameters used for adjustments.
CAUTION
• Because advanced autotuning adjusts the SERVOPACK during automatic operation, vibration or overshooting may occur. To ensure safety, perform advanced autotuning in a state where the SERVOPACK can come to an emergency stop at any time.
(1) Preparation
The following conditions must be met to perform advanced autotuning.
• The main circuit power supply must be ON.
• There must be no overtravel.
• The servomotor power must be OFF.
• The control method must not be set to torque control.
• The gain selection switch must be in manual switching mode (Pn139.0 = 0).
• Gain setting 1 must be selected.
• The test without a motor function must be disabled (Pn00C.0 = 0).
• All alarms and warning must be cleared.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• Jcalc must be set to ON to calculate the load moment of inertia when the tuning-less function is enabled
(Pn170.0 = 1: factory setting) or the tuning-less function must be disabled (Pn170.0 = 0).
Note:
• If advanced autotuning is started while the SERVOPACK is in speed control, the mode will change to position control automatically to perform advanced autotuning. The mode will return to speed control after completing the adjustment. To perform advanced autotuning in speed control, set the mode to 1 (Mode = 1).
(2) When Advanced Autotuning Cannot Be Performed
Advanced autotuning cannot be performed normally under the following conditions. Refer to 5.4 Advanced
Autotuning by Reference (Fn202) and 5.5 One-parameter Tuning (Fn203) for details.
• The machine system can work only in a single direction.
• The operating range is within 0.5 rotation.
5
5-19
5-20
5 Adjustments
5.3.1 Advanced Autotuning
(3) When Advanced Autotuning Cannot Be Performed Successfully
Advanced autotuning cannot be performed successfully under the following conditions. Refer to 5.4
Advanced Autotuning by Reference (Fn202) and 5.5 One-parameter Tuning (Fn203) for details.
• The operating range is not applicable.
• The moment of inertia changes within the set operating range.
• The machine has high friction.
• The rigidity of the machine is low and vibration occurs when positioning is performed.
• The position integration function is used.
• P control operation (proportional control) is used.
Note: If a setting is made for calculating the moment of inertia, an error will result when P control operation is selected using /V_PPI of the servo command output signals (SVCMD_IO) while the moment of inertia is being calculated.
• The mode switch is used.
Note: If a setting is made for calculating the moment of inertia, the mode switch function will be disabled while the moment of inertia is being calculated. At that time, PI control will be used. The mode switch function will be enabled after calculating the moment of inertia.
• Speed feedforward or torque feedforward is input.
• The positioning completed width (Pn522) is too small.
• Advanced autotuning makes adjustments by referring to the positioning completed width (Pn522). If the SERVOPACK is operated in position control (Pn000.1=1), set the electronic gear ratio (Pn20E/Pn210) and positioning completed width (Pn522) to the actual value during operation. If the SERVOPACK is operated in speed control
(Pn000.1=0), set Mode to 1 to perform advanced autotuning.
Change only the overshoot detection level (Pn561) to finely adjust the amount of overshooting without changing the positioning completed width (Pn522). Because Pn561 is set by default to 100%, the allowable amount of overshooting is the same amount as that for the positioning completed width.
When Pn561 is set to 0%, the amount of overshooting can be adjusted to prevent overshooting the positioning completed width. If the setting of Pn561 is changed, however, the positioning time may be extended.
Pn561
Overshoot Detection Level
Setting Range
0 to 100
Setting Unit
1%
Speed Position Torque
Factory Setting
100
When Enabled
Immediately
Classification
Setup
5.3 Advanced Autotuning (Fn201)
5.3.2
Advanced Autotuning Procedure
The following procedure is used for advanced autotuning.
The SigmaWin+ is required to execute this function.
CAUTION
• When using the SERVOPACK with Jcalc = OFF (load moment of inertia is not calculated), be sure to set a suitable value for the moment of inertia ratio (Pn103). If the setting greatly differs from the actual moment of inertia ratio, normal control of the SERVOPACK may not be possible, and vibration may result.
• When using the MP2000 Series with phase control, select the mode = 1 (standard level). If 2 or 3 is selected, phase control of the MP2000 Series may not be possible.
(1) Operating Procedure
Use the following procedure.
WARNING
Advanced autotuning involves motor operation, and it is therefore hazardous.
Refer to the SigmaWin+ Operation Manual before performing autotuning without reference input.
Be particularly careful of the following point.
• Ensure safety near all moving parts.
Vibration may occur during autotuning. Provide an emergency stop means to shut OFF the power supply during implementation. The motor will move in both directions within the movement range. Check the movement range and direction, and provide overtravel prevention means and other safety measures as required.
CAUTION
Two methods are available to stop advanced autotuning while the motor is running, and the motor will stop according to the method selected. Make sure to select the best method for the situation.
• If the SERVO OFF button is used, the motor will stop according to the stopping method after servo off specified by the parameters.
• If the CANCEL button is used, the motor will decelerate to a stop and then enter a zero clamp state.
Note: The CANCEL button may be invalid in some SERVOPACKs.
5
5-21
5-22
5 Adjustments
5.3.2 Advanced Autotuning Procedure
1.
In the SigmaWin+ main window, click Tuning – Tuning .
MECHA
Click Cancel to return to the SigmaWin+ main window without executing tuning.
2.
Click Execute .
The following window will appear.
MECHA
3.
Click Execute .
The following window will appear.
5.3 Advanced Autotuning (Fn201)
MECHA
Speed Loop Setting
Set the speed loop gain and integral time constant.
If the response of the speed loop is poor, the moment of inertia (mass) ratio cannot be measured accurately.
The speed loop setting to get the required response for the moment of inertia (mass) setting is already set to the default setting. Normally, this setting does not have to be changed.
If this speed loop gain is too high, and is causing excitation in the mechanism, lower the setting. However, do not set it to a value that is higher than the default setting.
Identification Start Level
Set the moment of inertia (mass) identification start level.
With a heavy load or low-rigidity machine, torque limit may be applied and the moment of inertia identification may fail.
In this case, double the identification start level and execute identification again.
Edit
Click Edit to view the Speed Loop-Related Setting Change box or the Identification Start Level Setting
Change box.
Help
Click Help to open the window for guidelines on the reference condition settings.
•Run the motor to measure the load's inertial moment (mass) of the machine to compare it with the rotor's inertial moment of the motor in the moment of inertia (mass) ratio.
•Set the driving mode, reference pattern (maximum acceleration, maximum speed, and maximum moving distance), and parameters related to the speed loop.
•Accurate measurement of the moment of inertia (mass) ratio depends on the settings. See the measurement results to determine the proper settings.
Reference Selection
Select a reference pattern from the Reference Selection box or create the reference pattern by directly entering the values.
As the setting for maximum acceleration increases, the accuracy of the inertia identification tends to improve.
Consider the pulley diameter or the speed reduction ratio such as the ball screw pitches, and set the maximum acceleration within the operable range.
5
5-23
5 Adjustments
5.3.2 Advanced Autotuning Procedure
Confirm
Click Confirm to view the driving pattern.
MECHA
5-24
Detailed Setting
Create the reference pattern for setting the moment of inertia (mass) by changing the values with the slider or by directly entering the values.
Next
Click Next to view the Reference Transmission box.
Cancel
Click Cancel to return to the main window without changing the conditions.
CAUTION
• The amount of movement is the value for each operation (a forward run or a reverse run). After several operations, the operation starting position may have moved in either direction. Confirm the operable range before each measurement and operation.
• Certain settings for the parameters or inertia size of the mechanism may result in overshooting or undershooting, and cause the speed to temporarily exceed the maximum speed. Allow a margin when making the settings.
<If the moment of inertia (mass) ratio cannot be measured accurately>
If the torque (force) is limited, the moment of inertia (mass) ratio identification cannot be made correctly. Adjust the setting of the limit or decrease the acceleration in Reference Selection so that the torque (force) will not be limited.
4.
Click Next .
The following window will appear.
MECHA
Start
Click to Start to transfer the reference conditions to the SERVOPACK. A progress bar displays the progress status of the transfer.
Cancel
The Cancel button is available only during the transfer to the SERVOPACK. After the transmission is finished, it is unavailable and cannot be selected.
Back
Click Back to return to the Condition Setting box. The Back button is unavailable during a data transfer.
5.3 Advanced Autotuning (Fn201)
Next
The Next button is available if the data is transferred successfully. If an error occurs or if the transmission is interrupted, it is unavailable and cannot be selected.
Click Next to view the Operation/Measurement box.
Cancel
Click Cancel to stop processing and return to the main window.
5.
Click Start to transfer the reference conditions to the SERVOPACK.
6.
Click Next .
The following window will appear.
MECHA
7.
Click Servo On .
8.
Click Forward to take measurements by turning (moving) the motor forward.
After the measurements and the data transmission are finished, the following window will appear.
MECHA
9.
Click Reverse to take measurements by turning (moving) the motor in reverse.
After the measurements and the data transmission are finished, the following window will appear.
MECHA
5
5-25
5-26
5 Adjustments
5.3.2 Advanced Autotuning Procedure
10.
Repeat steps 7 through 9 until all the measurements have been taken.
Measurements will be made from two to seven times and then verification will be performed. The actual number of times the measurements have been taken is displayed in the upper left part on the screen. The progress bar displays the percentage of data that has been transferred.
11.
After the measurement has been successfully completed, click Servo ON to turn to the servo
OFF status.
12.
Click Next .
The following window will appear.
MECHA
Identified Moment of Inertia (Mass) Ratio
Displays the moment of inertia (mass) ratio calculated in the operation/measurement.
Writing Results
Click Writing Results to assign the value displayed in the identified moment of inertia (mass) ratio to
SERVOPACK parameter Pn103.
Pn103: Moment of Inertia (Mass) Ratio
Displays the value assigned to the parameter.
Click Writing Results , and the new ratio calculated from the operation/measurement will be displayed.
Back
The Back button is unavailable.
Cancel
Click Cancel to return to the main window.
<Supplement>
When Next is clicked without turning to the servo OFF status, the following message appears. Click OK to turn to the servo OFF status.
MECHA
13.
Click Writing Results to set the moment of inertia (mass) ratio calculated in the operation/ measurement to the parameters.
5.3 Advanced Autotuning (Fn201)
14.
After confirming that the value displayed in the identified moment of inertia (mass) ratio and the value displayed in the Pn103: Moment of Inertia Ratio are the same, click Finish .
The following window will appear.
MECHA
15.
Click OK .
The following window will appear.
MECHA
16.
Click Execute to save the change of Pn103 (Moment of Inertia (Mass) Ratio) to SERVOPACK.
After the saving is finished, the tuning main window will appear.
17.
Select the No reference input option under Reference input from host controller in the
Tuning main window, and then click Autotuning .
The following window will appear.
MECHA
5
5-27
5 Adjustments
5.3.2 Advanced Autotuning Procedure
18.
Select whether or not to use the load moment of inertia (load mass) identification from the
Switching the load moment of inertia (load mass) identification box, the mode from the
Mode selection box, the mechanism from the Mechanism selection box, and enter the moving distance. Then, click Next .
When the Start tuning using the default settings . check box is selected in the Autotuning-Setting Conditions box, tuning will be executed using the tuning parameters set to the default values.
MECHA
19.
Click Servo ON .
The following window will appear.
MECHA
5-28
20.
Click Start tuning .
The following box will appear.
MECHA
5.3 Advanced Autotuning (Fn201)
21.
After confirming the safety of the area adjoining the drive unit, click Yes .
The motor will start rotating and tuning will start.
MECHA
Vibration generated during tuning is automatically detected, and the optimum setting for the detected vibration will be made. When the setting is complete, the LED indicator lamps (bottom left of the box) of the functions used for the setting will light up.
22.
When tuning is completed, click Finish to return to the main window.
The results of tuning will be written in the parameters.
5
5-29
5-30
5 Adjustments
5.3.2 Advanced Autotuning Procedure
(2) Failure in Operation
When Operation Cannot be Performed
Probable Cause
The main circuit power supply was OFF.
An alarm or warning occurred.
Overtraveling occurred.
Gain setting 2 was selected by gain switching.
Corrective Actions
Turn ON the main circuit power supply.
Remove the cause of the alarm or the warning.
Remove the cause of the overtravel.
Disable the automatic gain switching.
When an Error Occurs
Error
The gain adjustment was not successfully completed.
Machine vibration is occurring or the positioning completed signal (/COIN) is turning
ON and OFF when the servomotor is stopped.
Probable Cause Corrective Actions
• Increase the set value for Pn522.
• Change the mode from 2 to 3.
• If machine vibration occurs, suppress the vibration with the anti-resonance control adjustment function and the vibration suppression function.
An error occurred during the calculation of the moment of inertia.
Refer to the following table
Inertia .
When an Error Occurs during Calculation of Moment of
Travel distance setting error
The travel distance is set to approximately
0.5 rotation or less, which is less than the minimum adjustable travel distance.
The positioning completed signal (/COIN) did not turn ON within approximately 10 seconds after positioning adjustment was completed.
The moment of inertia cannot be calculated when the tuning-less function was activated.
The positioning completed width is too narrow or proportional control (P control) is being used.
When the tuning-less function was activated, Jcalc was set to OFF so the moment of inertia was not calculated.
Increase the travel distance. It is recommended to set the number of motor rotations to around 3.
• Increase the set value for Pn522.
• Set 0 to V_PPI in the servo command output signals (SVCMD_IO).
• Turn OFF the tuning-less function.
• Set Jcalc to ON , so the moment of inertia will be calculated.
When an Error Occurs during Calculation of Moment of Inertia
The following table shows the probable causes of errors that may occur during the calculation of the moment of inertia with the Jcalc set to ON, along with corrective actions for the errors.
Probable Cause
The SERVOPACK started calculating the moment of inertia, but the calculation was not completed.
The moment of inertia fluctuated greatly and did not converge within 10 tries.
Low-frequency vibration was detected.
The torque limit was reached.
Corrective Actions
• Increase the speed loop gain (Pn100).
• Increase the STROKE (travel distance).
Set the calculation value based on the machine specifications in
Pn103 and execute the calculation with the Jcalc set to OFF.
Double the set value of the moment of inertia calculating start level (Pn324).
• When using the torque limit, increase the torque limit.
• Double the set value of the moment of inertia calculating start level (Pn324).
While calculating the moment of inertia, the speed control was set to proportional control by setting 1 to
V_PPI in the servo command output signals
(SVCMD_IO).
Operate the SERVOPACK with PI control while calculating the moment of inertia.
5.3 Advanced Autotuning (Fn201)
(3) Related Functions on Advanced Autotuning
This section describes functions related to advanced tuning.
Notch Filter
Usually, set this function to Auto Setting. (The notch filter is factory-set to Auto Setting.)
If this function is set to Auto Setting, vibration will be detected automatically during advanced autotuning and the notch filter will be set.
Set this function to Not Auto Setting only if you do not change the notch filter setting before executing advanced autotuning.
Pn460
Parameter n.
n.
1
[Factory setting] n.
0
0
n.
1
[Factory setting]
Function
Does not set the 1st notch filter automatically with the utility function.
Sets the 1st notch filter automatically with the utility function.
Does not set the 2nd notch filter automatically with the utility function.
Sets the 2nd notch filter automatically with the utility function.
When Enabled Classification
Immediately Tuning
Anti-Resonance Control Adjustment
This function reduces low vibration frequency, which the notch filter does not detect.
Usually, set this function to Auto Setting. (The anti-resonance control is factory-set to Auto Setting.)
When this function is set to Auto Setting, vibration will be automatically detected during advanced autotuning and anti-resonance control will be automatically adjusted and set.
Pn160
Parameter n.
0 n.
1
[Factory setting]
Function
Does not use the anti-resonance control automatically with the utility function.
Uses the anti-resonance control automatically with the utility function.
When Enabled Classification
Immediately Tuning
Vibration Suppression
The vibration suppression function suppresses transitional vibration at frequency as low as 1 to 100 Hz that is generated mainly when positioning if the machine stand vibrates.
Usually, set this function to Auto Setting. (The vibration suppression function is factory-set to Auto Setting.)
When this function is set to Auto Setting, vibration will be automatically detected during advanced autotuning and vibration suppression will be automatically adjusted and set.
Set this function to Not Auto Setting only if you do not change the setting for vibration suppression before executing advanced autotuning.
Note: This function uses model following control. Therefore, the function can be executed only if the mode is set to 2 or 3.
• Related Parameter
Pn140
Parameter n.
0 n.
1
[Factory setting]
Function
Does not use the vibration suppression function automatically with the utility function.
Uses the vibration suppression function automatically with the utility function.
When Enabled Classification
Immediately Tuning
5
5-31
5-32
5 Adjustments
5.3.2 Advanced Autotuning Procedure
Friction Compensation
This function compensates for changes in the following conditions.
• Changes in the viscous resistance of the lubricant, such as the grease, on the sliding parts of the machine
• Changes in the friction resistance resulting from variations in the machine assembly
• Changes in the friction resistance due to aging
The conditions for applying friction compensation depend on the mode. The friction compensation setting in
Pn408.3 applies when the Mode is 1. The friction compensation function is always enabled regardless of the friction compensation setting in Pn408.3 when the Mode is 2 or 3.
Friction
Compensation
Selecting n.0
[Factory setting]
Pn408 n.1
Mode
Mode = 1
Adjusted without the friction compensation function
Adjusted with the friction compensation function
Mode = 2
Adjusted with the friction compensation function
Mode = 3
Adjusted with the friction compensation function
Feedforward
If Pn140 is set to the factory setting and the mode setting is changed to 2 or 3, the feedforward gain (Pn109), speed feedforward (VFF) input, and torque feedforward (TFF) input will be disabled.
Set Pn140.3 to 1 if model following control is used together with the speed feedforward (VFF) input and torque feedforward (TFF) input from the host controller.
Pn140
Parameter n.0
[Factory setting] n.1
Function
Model following control is not used together with the speed/torque feedforward input.
Model following control is used together with the speed/torque feedforward input.
When Enabled Classification
Immediately Tuning
Refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands (Manual No.:
SIEP S800000 63) for details.
• Model following control is used to make optimum feedforward settings in the SERVO-
PACK when model following control is used with the feedforward function. Therefore, model following control is not normally used together with either the speed feedforward (VFF) input or torque feedforward (TFF) input from the host controller. However, model following control can be used with the speed feedforward (VFF) input or torque feedforward (TFF) input if required. An improper feedforward input may result in overshooting.
5.3 Advanced Autotuning (Fn201)
5.3.3
Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn161
Pn163
Pn531
Pn533
Pn534
Pn535
Pn536
Pn141
Pn142
Pn143
Pn144
Pn145
Pn146
Pn147
Pn160
Pn125
Pn401
Pn408
Pn409
Pn40A
Pn40C
Pn40D
Pn140
Pn100
Pn101
Pn102
Pn103
Pn121
Pn123
Pn124
Name
Speed Loop Gain
Speed Loop Integral Time Constant
Position Loop Gain
Moment of Inertia Ratio
Friction Compensation Gain
Friction Compensation Coefficient
Friction Compensation Frequency Correction
Friction Compensation Gain Correction
Torque Reference Filter Time Constant
Torque Related Function Switch
1st Notch Filter Frequency
1st Notch Filter Q Value
2nd Notch Filter Frequency
2nd Notch Filter Q Value
Model Following Control Related Switch
Model Following Control Gain
Model Following Control Gain Compensation
Model Following Control Bias (Forward Direction)
Model Following Control Bias (Reverse Direction)
Vibration Suppression 1 Frequency A
Vibration Suppression 1 Frequency B
Model Following Control Speed Feedforward Compensation
Anti-Resonance Control Related Switch
Anti-Resonance Frequency
Anti-Resonance Damping Gain
Program JOG Movement Distance
Program JOG Movement Speed
Program JOG Acceleration/Deceleration Time
Program JOG Waiting Time
Number of Times of Program JOG Movement
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
Yes
No
No
Mid-execution changes
No
No
No
No
No
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Automatic changes
Yes
Yes
Yes
No
Yes
5
5-33
5-34
5 Adjustments
5.4.1 Advanced Autotuning by Reference
5.4
Advanced Autotuning by Reference (Fn202)
Adjustments with advanced autotuning by reference are described below.
• Advanced autotuning by reference starts adjustments based on the set speed loop gain (Pn100). Therefore, precise adjustments cannot be made if there is vibration when starting adjustments. In this case, make adjustments after lowering the speed loop gain (Pn100) until vibration is eliminated.
5.4.1
Advanced Autotuning by Reference
Advanced autotuning by reference is used to automatically achieve optimum tuning of the SERVOPACK in response to the user reference inputs from the host controller.
Advanced autotuning by reference is performed generally to fine-tune the SERVOPACK after advanced autotuning of the SERVOPACK has been performed.
If the moment of inertia ratio is correctly set to Pn103, advanced autotuning by reference can be performed without performing advanced autotuning.
Movement speed
Reference
Reference
M-III
Travel distance
Response
Host controller
SERVOPACK
Advanced autotuning by reference performs the following adjustments.
• Gains (e.g., position loop gain and speed loop gain)
• Filters (torque reference filter and notch filter)
• Friction compensation
• Anti-resonance control
• Vibration suppression
Refer to 5.4.3 Related Parameters for parameters used for adjustments.
CAUTION
• Because advanced autotuning by reference adjusts the SERVOPACK during automatic operation, vibration or overshooting may occur. To ensure safety, perform advanced autotuning by reference in a state where the SERVOPACK can come to an emergency stop at any time.
5.4 Advanced Autotuning by Reference (Fn202)
(1) Preparation
The following conditions must be met to perform advanced autotuning by reference.
• The SERVOPACK must be in Servo Ready status (Refer to 4.8.4
).
• There must be no overtravel.
• The servomotor power must be OFF.
• The position control must be selected when the servomotor power is ON.
• The gain selection switch must be in manual switching mode (Pn139.0 = 0).
• Gain setting 1 must be selected.
• The test without a motor function must be disabled. (Pn00C.0 = 0).
• All warnings must be cleared.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The tuning-less function must be disabled (Pn170.0 = 0).
(2) When Advanced Autotuning by Reference Cannot Be Performed Successfully
Advanced autotuning by reference cannot be performed successfully under the following conditions. If the result of autotuning is not satisfactory, perform one-parameter tuning (Fn203). Refer to 5.5 One-parameter
Tuning (Fn203) for details.
• The travel distance in response to references from the host controller is smaller than the set positioning completed width (Pn522).
• The motor speed in response to references from the host controller is smaller than the set rotation detection level (Pn502).
• The stopping time, i.e., the period while the positioning completed /COIN signal is OFF, is 10 ms or less.
• The rigidity of the machine is low and vibration occurs when positioning is performed.
• The position integration function is used.
• P control operation (proportional control) is performed.
• The mode switch is used.
• The positioning completed width (Pn522) is too small.
• Advanced autotuning by reference starts adjustments based on the positioning completed width (Pn522). Set the electronic gear ratio (Pn20E/Pn210) and positioning completed width (Pn522) to the actual value during operation.
• Unless the positioning completed signal (/COIN) is turned ON within approximately 3 seconds after positioning has been completed, "WAITING" will flash. Furthermore, unless the positioning completed signal (/COIN) is turned ON within approximately 10 seconds, "Error" will flash for 2 seconds and tuning will be aborted.
Change only the overshoot detection level (Pn561) to finely adjust the amount of overshooting without changing the positioning completed width (Pn522). Because Pn561 is set by default to 100%, the allowable amount of overshooting is the same amount as that for the positioning completed width.
When Pn561 is set to 0%, the amount of overshooting can be adjusted without any overshooting in the positioning completed width. If the setting of Pn561 is changed, however, the positioning time may be extended.
Pn561
Overshoot Detection Level
Setting Range
0 to 100
Setting Unit
1%
Speed Position Torque
Factory Setting
100
When Enabled
Immediately
Classification
Setup
5
5-35
5-36
5 Adjustments
5.4.2 Advanced Autotuning by Reference Procedure
5.4.2
Advanced Autotuning by Reference Procedure
The following procedure is used for advanced autotuning by reference.
The SigmaWin+ is required to execute this function.
CAUTION
• When using the MP2000 Series with phase control, select the mode = 1 (standard level). If 2 or 3 is selected, phase control of the MP2000 Series may not be possible.
(1) Operating Procedure
Use the following procedure.
1.
Confirm that the correct moment of inertia ratio in Pn103 is set by using the advanced autotuning.
2.
In the SigmaWin+ main window, click Tuning - Tuning .
MECHA
Click Cancel to return to the SigmaWin+ main window without executing tuning.
3.
Click Execute .
The following window will appear.
MECHA
4.
Click OK .
The following window will appear.
5.4 Advanced Autotuning by Reference (Fn202)
MECHA
5.
Select the Position reference input option under Reference input from host controller in the Tuning main window, and then click Autotuning .
The following window will appear.
MECHA
5
5-37
5-38
5 Adjustments
5.4.2 Advanced Autotuning by Reference Procedure
6.
Select the mode from the Mode selection combo box and the mechanism from Mechanism selection combo box, and then click Next .
When the Start tuning using the default settings . check box is selected in the Autotuning-Setting Conditions box, tuning will be executed using tuning parameters set to the default value.
MECHA
7.
Click Yes .
The following box will appear.
MECHA
8.
Enter the correct moment of inertia ratio and then click Next .
The following window will appear.
MECHA
5.4 Advanced Autotuning by Reference (Fn202)
9.
Turn the servo on and then input the reference from the host controller. Click Start tuning .
MECHA
10.
After confirming the safety of the area adjoining the drive unit, click Yes .
The motor will start rotating and tuning will start.
MECHA
Vibration generated during tuning is automatically detected, and the optimum setting for the detected vibration will be made. When the setting is complete, the LED indicator lamps (bottom left of the box) of the functions used for the setting will light up.
11.
When tuning is completed, click Finish to return to the main window.
The results of tuning will be written in the parameters.
5
5-39
5-40
5 Adjustments
5.4.2 Advanced Autotuning by Reference Procedure
(2) Failure in Operation
When Operation Cannot be Performed
Probable Cause
The main circuit power supply was OFF.
An alarm or warning occurred.
Overtraveling occurred.
Gain setting 2 was selected by gain switching.
When an Error Occurs
Corrective Actions
Turn ON the main circuit power supply.
Remove the cause of the alarm or the warning.
Remove the cause of the overtravel.
Disable the automatic gain switching.
Error
The gain adjustment was not successfully completed.
Probable Cause
Machine vibration is occurring or the positioning completed signal (/COIN) is turning
ON and OFF when the servomotor is stopped.
Corrective Actions
• Increase the set value for Pn522.
• Change the mode from 2 to 3.
• If machine vibration occurs, suppress the vibration with the anti-resonance control adjustment function and the vibration suppression function.
The positioning completed signal
(/COIN) did not turn ON within approximately 10 seconds after positioning adjustment was completed.
The positioning completed width is too narrow or proportional control (P control) is being used.
• Increase the set value for Pn522.
• Set 0 to V_PPI in the servo command output signals (SVCMD_IO).
(3) Related Functions on Advanced Autotuning by Reference
This section describes functions related to advanced autotuning by reference.
Notch Filter
Usually, set this function to Auto Setting. (The notch filter is factory-set to Auto Setting.)
If this function is set to Auto Setting, vibration will be detected automatically during advanced autotuning by reference, and the notch filter will be set.
Set this function to Not Auto Setting only if you do not change the notch filter setting before executing advanced autotuning by reference.
Pn460
Parameter n.
n.
1
[Factory setting] n.
0
0
n.
1
[Factory setting]
Function
Does not set the 1st notch filter automatically with the utility function.
Sets the 1st notch filter automatically with the utility function.
Does not set the 2nd notch filter automatically with the utility function.
Sets the 2nd notch filter automatically with the utility function.
When Enabled Classification
Immediately Tuning
Anti-Resonance Control Adjustment
This function reduces low vibration frequency, which the notch filter does not detect.
Usually, set this function to Auto Setting. (The anti-resonance control is factory-set to Auto Setting.)
When this function is set to Auto Setting, vibration will be automatically detected during advanced autotuning by reference and anti-resonance control will be automatically adjusted and set.
Pn160
Parameter n.
0 n.
1
[Factory setting]
Function
Does not use the anti-resonance control automatically with the utility function.
Uses the anti-resonance control automatically with the utility function.
When Enabled Classification
Immediately Tuning
5.4 Advanced Autotuning by Reference (Fn202)
Vibration Suppression
The vibration suppression function suppresses transitional vibration at frequency as low as 1 to 100 Hz that is generated mainly when positioning if the machine stand vibrates.
Usually, set this function to Auto Setting. (The vibration suppression function is factory-set to Auto Setting.)
When this function is set to Auto Setting, vibration will be automatically detected during advanced autotuning by reference and vibration suppression will be automatically adjusted and set.
Set this function to Not Auto Setting only if you do not change the setting for vibration suppression before executing advanced autotuning by reference.
Note: This function uses model following control. Therefore, the function can be executed only if the mode is set to 2 or 3.
• Related Parameters
Parameter n.
0
Pn140 n.
1
[Factory setting]
Friction Compensation
Function
Does not use the vibration suppression function automatically.
Uses the vibration suppression function automatically.
When Enabled Classification
Immediately Tuning
This function compensates for changes in the following conditions.
• Changes in the viscous resistance of the lubricant, such as the grease, on the sliding parts of the machine
• Changes in the friction resistance resulting from variations in the machine assembly
• Changes in the friction resistance due to aging
Conditions to which friction compensation is applicable depend on the mode. The friction compensation setting in Pn408.3 applies when the mode is 1. Mode = 2 and Mode = 3 are adjusted with the friction compensation function regardless of the friction compensation setting in P408.3.
Mode
Friction
Compensation
Selecting n.0
[Factory setting]
Pn408 n.1
Mode = 1 Mode = 2
Adjusted without the friction compensation function
Adjusted with the friction compensation function
Adjusted with the friction compensation function
Mode = 3
Adjusted with the friction compensation function
Feedforward
If Pn140 is set to the factory setting and the mode setting is changed to 2 or 3, the feedforward gain (Pn109), speed feedforward (VFF) input, and torque feedforward (TFF) input will be disabled.
Set Pn140.3 to 1 if model following control is used together with the speed feedforward (VFF) input and torque feedforward (TFF) input from the host controller.
Pn140
Parameter n.0
[Factory setting] n.1
Function
Model following control is not used together with the speed/torque feedforward input.
Model following control is used together with the speed/torque feedforward input.
When Enabled Classification
Immediately Tuning
Refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands (Manual No.:
SIEP S800000 63) for details.
• Model following control is used to make optimum feedforward settings in the SERVO-
PACK when model following control is used with the feedforward function. Therefore, model following control is not normally used together with either the speed feedforward (VFF) input or torque feedforward (TFF) input from the host controller. However, model following control can be used with the speed feedforward (VFF) input or torque feedforward (TFF) input if required. An improper feedforward input may result in overshooting.
5
5-41
5-42
5 Adjustments
5.4.3 Related Parameters
5.4.3
Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn125
Pn401
Pn408
Pn409
Pn40A
Pn40C
Pn40D
Pn140
Pn100
Pn101
Pn102
Pn103
Pn121
Pn123
Pn124
Pn141
Pn142
Pn143
Pn144
Pn145
Pn146
Pn147
Pn160
Pn161
Pn163
Name
Speed Loop Gain
Speed Loop Integral Time Constant
Position Loop Gain
Moment of Inertia Ratio
Friction Compensation Gain
Friction Compensation Coefficient
Friction Compensation Frequency Correction
Friction Compensation Gain Correction
Torque Reference Filter Time Constant
Torque Related Function Switch
1st Notch Filter Frequency
1st Notch Filter Q Value
2nd Notch Filter Frequency
2nd Notch Filter Q Value
Model Following Control Related Switch
Model Following Control Gain
Model Following Control Gain Compensation
Model Following Control Bias (Forward Direction)
Model Following Control Bias (Reverse Direction)
Vibration Suppression 1 Frequency A
Vibration Suppression 1 Frequency B
Model Following Control Speed Feedforward Compensation
Anti-Resonance Control Related Switch
Anti-Resonance Frequency
Anti-Resonance Damping Gain
No
No
No
No
No
Yes
No
No
No
Yes
No
No
Mid-execution changes
No
No
No
No
No
Yes
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Automatic changes
Yes
Yes
Yes
No
Yes
5.5 One-parameter Tuning (Fn203)
5.5
One-parameter Tuning (Fn203)
Adjustments with one-parameter tuning are described below.
5.5.1
One-parameter Tuning
One-parameter tuning is used to manually make tuning level adjustments during operation with a position reference or speed reference input from the host controller.
One-parameter tuning enables automatically setting related servo gain settings to balanced conditions by adjusting one or two tuning levels.
One-parameter tuning performs the following adjustments.
• Gains (e.g., position loop gain and speed loop gain)
• Filters (torque reference filter and notch filter)
• Friction compensation
• Anti-resonance control
Refer to 5.5.4 Related Parameters for parameters used for adjustments.
Perform one-parameter tuning if satisfactory response characteristics is not obtained with advanced autotuning or advanced autotuning by reference.
To fine-tune each servo gain after one-parameter tuning, refer to 5.8 Additional Adjustment Function .
CAUTION
• Vibration or overshooting may occur during adjustment. To ensure safety, perform one-parameter tuning in a state where the SERVOPACK can come to an emergency stop at any time.
Preparation
The following conditions must be met to perform one-parameter tuning.
• The test without a motor function must be disabled (Pn00C.0 = 0).
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The tuning-less function must be disabled (Pn170.0 = 0).
• The tuning mode must be set to 0 or 1 when performing speed control.
5.5.2
One-parameter Tuning Procedure
The following procedure is used for one-parameter tuning.
There are the following two operation procedures depending on the tuning mode being used.
• When the tuning mode is set to 0 or 1, the model following control will be disabled and one-parameter tuning will be used as the tuning method for applications other than positioning.
• When the tuning mode is set to 2 or 3, the model following control will be enabled and it can be used for tuning for positioning.
The operating procedure that is provided here is for when the Tuning Mode is set to 0 to give priority to setting a servo gain for stability.
The SigmaWin+ is required to execute this function.
CAUTION
• When using the MP2000 Series with phase control, select the tuning mode = 0 or 1. If 2 or 3 is selected, phase control of the MP2000 Series may not be possible.
5
5-43
5-44
5 Adjustments
5.5.2 One-parameter Tuning Procedure
(1) Operating Procedure
WARNING
Be sure to carefully read the SigmaWin+ Operation Manual before executing this function.
Special care must be taken for the following.
• Before executing this function, make sure that the emergency stop (power off) can be activated when needed.
When tuning is initiated by this function, some parameters will be overwritten with the recommended values. As a result, the response speeds may change considerably. Before executing this function, make sure that the emergency stop (power off) can be activated when needed.
• Set a correct moment of inertia (mass) ratio to execute this function.
If not correctly set, vibration may be generated.
• Note the timing when the feedforward level setting is validated.
The set feedforward level will not be immediately validated, but will be validated after the Positioning Completion signal (/COIN) is output.
1.
Confirm that the correct moment of inertia ratio in Pn103 is set by using the advanced autotuning.
2.
In the SigmaWin+ main window, click Tuning - Tuning .
ME-
CHA
Click Cancel to return to the SigmaWin+ main window without executing tuning.
3.
Click Execute .
The following window will appear.
5.5 One-parameter Tuning (Fn203)
MECHA
<Supplement>
If the following window will appear, click OK and confirm that the correct moment of inertia ratio in
Pn103 is set by using the Moment of Inertia (Mass) Setting window.
MECHA
4.
Click Advanced adjustment .
The following box will appear.
MECHA
5
5-45
5-46
5 Adjustments
5.5.2 One-parameter Tuning Procedure
5.
Click Custom tuning .
The following box will appear.
MECHA
The tuning modes that can be selected will vary according to the SERVOPACK setting.
6.
Select the tuning mode from the Tuning mode box and the mechanism from the Mechanism selection box, and then click Next .
The following box will appear.
MECHA
5.5 One-parameter Tuning (Fn203)
7.
Enter the correct moment of inertia ratio and then click Next .
The following window will appear.
MECHA
8.
Turn the servo on and then input the reference from the host controller. Click Start tuning .
MECHA
5
5-47
5-48
5 Adjustments
5.5.2 One-parameter Tuning Procedure
9.
Change the tuning level by clicking the setting arrows. Continue to raise the level until an overshoot occurs.
Note: The set feedforward level will not be applied until the Positioning Completion signal (/COIN) is output.
The notch filter/anti-resonance control auto setting function, the anti-resonance control adjustment function, or autotuning with reference input can be used as required.
See Functions To Suppress Vibration for details.
To reset to the original settings and status, click Back .
MECHA
10.
When tuning is complete, click Completed to return to the main window.
The settings will be written in the SERVOPACK.
5.5 One-parameter Tuning (Fn203)
Functions To Suppress Vibration
• <Notch Filter/Anti-resonance Control Adjustment Auto Setting Function>
For vibration frequencies above 1,000 Hz when servo gains are increased, the notch filter auto setting function provides effective suppression. For vibration frequencies between 100 and 1,000 Hz, the anti-resonance control adjustment auto setting function is effective.
• Auto Setting
To use auto setting, enable the notch filter/anti-resonance control adjustment auto setting function by using parameters.
During tuning, the notch filter frequency (anti-resonance control frequency for the anti-resonance control adjustment auto setting function) effective for the detected vibration is automatically set and displayed in 1 step or 2 step (in Anti-res Adj when using the anti-resonance control adjustment auto setting function).
MECHA
Window with Notch Filter Automatically Set
• Cancel
If the automatically set notch filter frequency (or anti-resonance control frequency) does not effectively suppress vibration, click Cancel to reset to the preceding frequency.
When the frequency is reset, vibration detection will restart.
• Vib Detect (vibration detection)
While the notch filter/anti-resonance control adjustment auto setting function is enabled, click Vib
Detect (vibration detection) to manually detect vibration. The SERVOPACK detects vibration at the moment Vib Detect (vibration detection) is clicked, and the notch filter frequency (or anti-resonance control frequency) effective for the detected vibration is set and displayed in 1 step or 2 step (or in
Anti-res Adj ). Manual vibration detection can also be executed when the SERVOPACK does not detect vibration.
• Anti-res Ctrl Adj (anti-resonance control)
Click Anti-res Ctrl Adj (anti-resonance control) to execute the anti-resonance control function if further adjustment is required. See 5.6 Anti-Resonance Control Adjustment Function (Fn204) for details.
• <Autotuning with Reference Input>
To Autotuning
Click To Autotuning to execute autotuning using reference inputs from the host controller. Refer to 5.4
Advanced Autotuning by Reference (Fn202) for details.
5
5-49
5-50
5 Adjustments
5.5.2 One-parameter Tuning Procedure
(2) Related Functions on One-parameter Tuning
This section describes functions related to one-parameter tuning.
Notch Filter
Usually, set this function to Auto Setting. (The notch filter is factory-set to Auto Setting.)
If this function is set to Auto Setting, vibration will be detected automatically during one-parameter tuning and the notch filter will be set.
Set this function to Not Auto Setting only if you do not change the notch filter setting before executing oneparameter tuning.
Pn460
Parameter n.
0 n.
1
[Factory setting] n.
0 n.
1
[Factory setting]
Function
Does not set the 1st notch filter automatically with the utility function.
Sets the 1st notch filter automatically with the utility function.
Does not set the 2nd notch filter automatically with the utility function.
Sets the 2nd notch filter automatically with the utility function.
When Enabled Classification
Immediately
Anti-Resonance Control Adjustment
This function reduces low vibration frequency, which the notch filter does not detect.
Tuning
Usually, set this function to Auto Setting. (The anti-resonance control is factory-set to Auto Setting.)
When this function is set to Auto Setting, vibration will be automatically detected during one-parameter tuning and anti-resonance control will be automatically adjusted and set.
When Enabled Classification
Pn160
Parameter n.
0 n.
1
[Factory setting]
Function
Does not use the anti-resonance control automatically with the utility function.
Uses the anti-resonance control automatically with the utility function.
Friction Compensation
This function compensates for changes in the following conditions.
Immediately Tuning
• Changes in the viscous resistance of the lubricant, such as the grease, on the sliding parts of the machine
• Changes in the friction resistance resulting from variations in the machine assembly
• Changes in the friction resistance due to aging
Conditions to which friction compensation is applicable depend on the tuning mode. The friction compensation setting in F408.3 applies when the mode is 0 or 1. Tuning Mode = 2 and Tuning Mode = 3 are adjusted with the friction compensation function regardless of the friction compensation setting in P408.3.
Friction
Compensation
Selecting
Pn408
Mode
Tuning Mode = 0 n.0
[Factory setting] n.1
Adjusted without the friction compensation function
Adjusted with the friction compensation function
Tuning Mode = 1
Adjusted without the friction compensation function
Adjusted with the friction compensation function
Tuning Mode = 2
Adjusted with the friction compensation function
Tuning Mode = 3
Adjusted with the friction compensation function
5.5 One-parameter Tuning (Fn203)
Feedforward
If Pn140 is set to the factory setting and the tuning mode setting is changed to 2 or 3, the feedforward gain
(Pn109), speed feedforward (VFF) input, and torque feedforward (TFF) input will be disabled.
Set Pn140.3 to 1 if model following control is used together with the speed feedforward (VFF) input and torque feedforward (TFF) input from the host controller.
Pn140
Parameter n.0
[Factory setting] n.1
Function
Model following control is not used together with the speed/torque feedforward input.
Model following control is used together with the speed/torque feedforward input.
When Enabled Classification
Immediately Tuning
Refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands (Manual No.:
SIEP S800000 63) for details.
• Model following control is used to make optimum feedforward settings in the SERVO-
PACK when model following control is used with the feedforward function. Therefore, model following control is not normally used together with either the speed feedforward (VFF) input or torque feedforward (TFF) input from the host controller. However, model following control can be used with the speed feedforward (VFF) input or torque feedforward (TFF) input if required. An improper feedforward input may result in overshooting.
5
5-51
5-52
5 Adjustments
5.5.3 One-parameter Tuning Example
5.5.3
One-parameter Tuning Example
The following procedure is used for one-parameter tuning on the condition that the tuning mode is set to 2 or
3. This mode is used to reduce positioning time.
Step Measuring Instrument Display Example
1
Operation
Position error
Reference speed
M
EC
H
A
Measure the positioning time after setting the moment of inertia ratio (Pn103) correctly. Tuning will be completed if the specifications are met here. The tuning results will be saved in the SERVOPACK.
Positioning completed signal
2
The positioning time will become shorter if the FF level is increased. The tuning will be completed if the specifications are met. The tuning results will be saved in the SERVOPACK.
If overshooting occurs before the specifications are met, go to step 3.
3
4
5
Overshooting will be reduced if the FB level is increased. If the overshooting is eliminated, go to step 4.
The graph shows overshooting generated with the FF level increased after step 3. In this state, the overshooting occurs, but the positioning settling time is shorter. The tuning will be completed if the specifications are met. The adjustment results are saved in the SERVOPACK. If overshooting occurs before the specifications are met, repeat steps 3 and 4.
If vibration occurs before the overshooting is eliminated, the vibration will be suppressed by the automatic notch filter and anti-resonance control.
The adjustment results are saved in the SERVOPACK.
5.5 One-parameter Tuning (Fn203)
5.5.4
Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn125
Pn401
Pn408
Pn409
Pn40A
Pn40C
Pn40D
Pn140
Pn100
Pn101
Pn102
Pn103
Pn121
Pn123
Pn124
Pn141
Pn142
Pn143
Pn144
Pn145
Pn146
Pn147
Pn160
Pn161
Pn163
Name
Speed Loop Gain
Speed Loop Integral Time Constant
Position Loop Gain
Moment of Inertia Ratio
Friction Compensation Gain
Friction Compensation Coefficient
Friction Compensation Frequency Correction
Friction Compensation Gain Correction
Torque Reference Filter Time Constant
Torque Related Function Switch
1st Notch Filter Frequency
1st Notch Filter Q Value
2nd Notch Filter Frequency
2nd Notch Filter Q Value
Model Following Control Related Switch
Model Following Control Gain
Model Following Control Gain Compensation
Model Following Control Bias (Forward Direction)
Model Following Control Bias (Reverse Direction)
Vibration Suppression 1 Frequency A
Vibration Suppression 1 Frequency B
Model Following Control Speed Feedforward Compensation
Anti-Resonance Control Related Switch
Anti-Resonance Frequency
Anti-Resonance Damping Gain
No
No
No
No
No
Yes
No
No
No
Yes
No
No
Mid-execution changes
No
No
No
No
No
Yes
No
No
No
No
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Automatic changes
Yes
Yes
Yes
No
Yes
5
5-53
5-54
5 Adjustments
5.6.1 Anti-Resonance Control Adjustment Function
5.6
Anti-Resonance Control Adjustment Function (Fn204)
This section describes the anti-resonance control adjustment function.
5.6.1
Anti-Resonance Control Adjustment Function
The anti-resonance control adjustment function increases the effectiveness of the vibration suppression after one-parameter tuning. This function is effective in supporting anti-resonance control adjustment if the vibration frequencies are from 100 to 1000 Hz.
This function rarely needs to be used because it is automatically set by the advanced autotuning or advanced autotuning by reference input. Use this function only if fine-tuning is required, or vibration detection is failed and readjustment is required.
Perform one-parameter tuning (Fn203) or use another method to improve the response characteristics after performing this function. If the anti-resonance gain is increased with one-parameter tuning performed, vibration may result again. If that occurs, perform this function again to fine-tune the settings.
CAUTION
• If this function is executed, related parameters will be set automatically. Therefore, there will be a large response change after this function is executed. Enable the function in a state where the machine can come to an emergency stop at any time to ensure the safety operation of the machine.
• Be sure to set a suitable value for the moment of inertia ratio (Pn103) using advanced autotuning before executing the anti-resonance control adjustment function. If the setting greatly differs from the actual moment of inertia ratio, normal control of the machine may not be possible, and vibration may result.
• This function detects vibration between 100 and 1000 Hz. Vibration will not be detected for frequencies outside of this range, and instead, "F----" will be displayed. If that occurs, use one-parameter tuning with tuning mode 2 selected to automatically set a notch filter or use the vibration suppression function (Fn205).
• Vibration can be reduced more effectively by increasing the anti-resonance damping gain (Pn163). The amplitude of vibration may become larger if the damping gain is excessively high. Increase the damping gain from about 0% to 200% in 10% increments while checking the effect of vibration reduction. If the effect of vibration reduction is still insufficient at a gain of 200%, cancel the setting, and lower the control gain using a different method, such as one-parameter tuning.
Before Performing Anti-Resonance Control Adjustment Function
The following conditions must be met to perform anti-resonance control adjustment function.
• The tuning-less function must be disabled (Pn170.0 = 0).
• The test without a motor function must be disabled (Pn00C.0 = 0).
• The control must not be set to torque control.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
5.6 Anti-Resonance Control Adjustment Function (Fn204)
5.6.2
Anti-Resonance Control Adjustment Function Operating Procedure
With this function, an operation reference is sent, and the function is executed while vibration is occurring.
The SigmaWin+ is required to execute this function.
The following methods can be used for the anti-resonance control adjustment function.
• With undetermined vibration frequency
• With determined vibration frequency
The following describes the operating procedures.
CAUTION
Be sure to carefully read the SigmaWin+ Operation Manual before executing this function.
Special care must be taken for the following.
• Before executing this function, make sure that the emergency stop (power off) can be activated when needed.
This function will automatically set parameters when used. As a result, the response speeds may change considerably after execution. Before executing this function, make sure that the emergency stop (power off) can be activated when needed.
• The moment of inertia (mass) must be correctly set to execute this function.
If it is not correctly set, satisfactory anti-resonance control cannot be achieved.
• If the frequency is changed while the anti-resonance control adjustment function is being used, the current anti-resonance control effect will be lost. Care must be taken when automatic frequency detection is executed in Auto Detect mode.
• If vibration cannot be suppressed by executing this function, cancel execution and reduce the servo gain by other methods such as custom tuning.
• Use an adjustment method such as custom tuning to improve response characteristics after executing this function.
When the servo gain is increased during an adjustment such as custom tuning, vibration may be generated again. In this case, execute the anti-resonance control adjustment function again for fine adjustment.
The anti-resonance control adjustment function supports the adjustment of anti-resonance control effective for vibration frequencies from 100 to 1,000 Hz when servo gain is increased. Vibration can be suppressed by setting vibration frequency by auto detection or by manual setting to adjust damping gain. Input a reference and execute this function when there is vibration.
5
5-55
5-56
5 Adjustments
5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure
(1) With Undetermined Vibration Frequency
1.
In the SigmaWin+ main window, click Tuning - Tuning .
ME-
CHA
Click Cancel to return to the SigmaWin+ main window without executing tuning.
2.
Click Execute .
The following window will appear.
MECHA
3.
Click Advanced adjustment .
The following box will appear.
5.6 Anti-Resonance Control Adjustment Function (Fn204)
MECHA
4.
Click Custom tuning .
The following box will appear.
MECHA
5.
Select the tuning mode from the Tuning mode box and the mechanism from the Mechanism selection box, and then click Next .
The following box will appear.
MECHA
5
5-57
5 Adjustments
5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure
6.
Enter the correct moment of inertia ratio and then click Next .
The following window will appear.
MECHA
5-58
7.
Click Anti-res Ctrl Adj .
The following window will appear.
MECHA
MECHA
8.
Click Auto Detect to set the frequency and click Start adjustment .
The following window will appear.
5.6 Anti-Resonance Control Adjustment Function (Fn204)
MECHA
9.
Adjust the damping gain by clicking the setting arrows.
Click Reset to reset the settings to their original values during adjustment.
10.
When the adjustment is complete, click Finish to return to the main window.
The set values will be written in the SERVOPACK.
(2) With Determined Vibration Frequency
1.
In the SigmaWin+ main window, click Tuning - Tuning .
ME-
CHA
Click Cancel to return to the SigmaWin+ main window without executing tuning.
5
5-59
5-60
5 Adjustments
5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure
2.
Click Execute .
The following window will appear.
MECHA
3.
Click Advanced adjustment .
The following box will appear.
4.
Click Custom tuning .
The following box will appear.
MECHA
MECHA
5.6 Anti-Resonance Control Adjustment Function (Fn204)
5.
Select the tuning mode from the Tuning mode box and the mechanism from the Mechanism selection box, and then click Next .
The following box will appear.
MECHA
6.
Enter the correct moment of inertia ratio and then click Next .
The following window will appear.
MECHA
MECHA
7.
Click Anti-res Ctrl Adj .
The following window will appear.
5
5-61
5 Adjustments
5.6.2 Anti-Resonance Control Adjustment Function Operating Procedure
MECHA
8.
Click Manual Set to set the frequency and click Start adjustment .
The following window will appear.
MECHA
9.
Adjust the frequency by clicking the setting arrows.
MECHA
Click Reset to reset the settings to their original values during adjustment.
10.
Adjust the damping gain by clicking the setting arrows.
5-62
Click Reset to reset the settings to their original values during adjustment.
11.
When the adjustment is complete, click Finish to return to the main window.
The set values will be written in the SERVOPACK.
5.6 Anti-Resonance Control Adjustment Function (Fn204)
5.6.3
Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn160
Pn161
Pn162
Pn163
Pn164
Pn165
Name
Anti-Resonance Control Related Switch
Anti-Resonance Frequency
Anti-Resonance Gain Compensation
Anti-Resonance Damping Gain
Anti-Resonance Filter Time Constant 1 Compensation
Anti-Resonance Filter Time Constant 2 Compensation
Mid-execution changes
Yes
No
Yes
No
Yes
Yes
Automatic changes
Yes
Yes
No
Yes
No
No
5
5-63
5-64
5 Adjustments
5.7.1 Vibration Suppression Function
5.7
Vibration Suppression Function (Fn205)
The vibration suppression function is described in this section.
5.7.1
Vibration Suppression Function
The vibration suppression function suppresses transitional vibration at frequency as low as 1 to 100 Hz that is generated mainly when positioning if the machine stand vibrates. This function is effective for vibration frequencies for which notch filter and anti-resonance control adjustment functions are not applicable.
This function is set automatically when advanced autotuning or advanced autotuning by reference is executed.
In most cases, this function is not necessary. Use this function only if fine-tuning is required or readjustment is required as a result of a failure to detect vibration. Before executing this function, input an operation reference to create vibration.
Perform one-parameter tuning (Fn203) if required to improve the response characteristics after performing this function.
CAUTION
• If this function is executed, related parameters will be set automatically. Therefore, there will be a large response change after this function is enabled or disabled. Enable the function in a state where the machine can come to an emergency stop at any time to ensure the safety operation of the machine.
• If the parameter settings are changed while the motor is moving, the new settings will become valid after the /COIN signal is output.
• Be sure to set a suitable value for the moment of inertia ratio (Pn103) using advanced autotuning before executing the vibration suppression function. If the setting greatly differs from the actual moment of inertia ratio, normal control of the SERVOPACK may not be possible, and vibration may result.
• Phase control of the MP2000 Series may not be possible, if the vibration suppression function is performed when using the MP2000 Series with phase control.
• This function detects vibration frequency between 1 to 100 Hz. Vibration will not be detected for frequencies outside of this range, and instead, "F-----" will be displayed.
• Frequency detection will not be performed if no vibration results from position error or the vibration frequencies are outside the range of detectable frequencies. If so, use a device, such as a displacement sensor or vibration sensor, to measure the vibration frequency.
• If vibration frequencies automatically detected are not suppressed, the actual frequency and the detected frequency may differ. Fine-tune the detected frequency if necessary.
(1) Preparation
The following conditions must be met to perform the vibration suppression function.
• The control must be set to position control.
• The tuning-less function must be disabled (Pn170.0 = 0).
• The test without a motor function must be disabled (Pn00C.0 = 0).
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
(2) Items Influencing Performance
If continuous vibration occurs when the servomotor is not rotating, the vibration suppression function cannot be used to suppress the vibration effectively. If the result is not satisfactory, perform anti-resonance control adjustment function (Fn204) or one-parameter tuning (Fn203).
5.7 Vibration Suppression Function (Fn205)
(3) Detection of Vibration Frequencies
No frequency detection may be possible if the vibration does not appear as a position error or the vibration resulting from the position error is too small.
The detection sensitivity can be adjusted by changing the setting for the remained vibration detection width
(Pn560) which is set as a percentage of the positioning completed width (Pn522). Perform the detection of vibration frequencies again after adjusting the remained vibration detection width (Pn560).
Remained Vibration Detection Width
Setting Range
1 to 3000
Setting Unit
0.1%
Position
Factory Setting
400
Classification
Pn560 When Enabled
Immediately Setup
Note: As a guideline, change the setting 10% at a time. The smaller the set value is, the higher the detection sensitivity will be. If the value is too small, however, the vibration may not be detected accurately.
The vibration frequencies that are automatically detected may vary somewhat with each positioning operation.
Perform positioning several times and make adjustments while checking the effect of vibration suppression.
5.7.2
Vibration Suppression Function Operating Procedure
The following procedure is used for vibration suppression function.
The SigmaWin+ is required to execute this function.
(1) Operating Procedure
1.
In the SigmaWin+ main window, click Tuning - Tuning .
ME-
CHA
Click Cancel to return to the SigmaWin+ main window without executing tuning.
5
5-65
5-66
5 Adjustments
5.7.2 Vibration Suppression Function Operating Procedure
2.
Click Execute .
The following window will appear.
MECHA
3.
Click Advanced adjustment .
The following box will appear.
4.
Click Custom tuning .
The following box will appear.
MECHA
MECHA
5.7 Vibration Suppression Function (Fn205)
5.
Select the 2 or 3 of tuning mode from the Tuning mode box and the mechanism from the
Mechanism selection box, and then click Next .
The following box will appear.
ME-
CHA
6.
Click Vib Suppress .
The Vibration suppression Function box will appear.
ME-
CHA
5
5-67
5 Adjustments
5.7.2 Vibration Suppression Function Operating Procedure
7.
Set a frequency by using the Import function or by manually selecting the frequency.
Click Import . The value of the residual vibration frequency being monitored will be imported to the Set frequency box. This function, however, is effective only when the residual vibration frequency is between 1.0 and 100.0.
The Set frequency can be manually selected by clicking the setting arrows.
ME-
CHA
8.
Click Set .
MECHA
If any vibration still occurs, manually make fine adjustments to the Set frequency , and click Set .
MECHA
5-68
If you need to undo the change you made while making adjustments, click Reset . The setting will be restored to the original value.
5.7 Vibration Suppression Function (Fn205)
9.
After the vibration has been successfully suppressed, click Finish .
The value of the Set frequency will be transferred to and saved in the SERVOPACK.
No settings related to the vibration suppression function will be changed during operation.
If the servomotor does not stop approximately 10 seconds after the setting changes, a timeout error will result and the previous setting will be automatically enabled again.
The vibration suppression function will be enabled in step 9. The motor response, however, will change when the servomotor comes to a stop with no reference input.
(2) Related Function on Vibration Suppression Function
This section describes functions related to vibration suppression function.
Feedforward
The feedforward gain (Pn109), speed feedforward (VFF) input, and torque feedforward (TFF) input will be disabled in the factory setting.
Set Pn140.3 to 1 if model following control is used together with the speed feedforward (VFF) input and torque feedforward (TFF) input from the host controller.
Pn140
Parameter n.0
[Factory setting] n.1
Function
Model following control is not used together with the speed/torque feedforward input.
Model following control is used together with the speed/torque feedforward input.
When Enabled Classification
Immediately Tuning
Refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
SIEP S800000 63) for details.
(Manual No.:
• Model following control is used to make optimum feedforward settings in the SERVO-
PACK when model following control is used with the feedforward function. Therefore, model following control is not normally used together with either the speed feedforward (VFF) input or torque feedforward (TFF) input from the host controller. However, model following control can be used with the speed feedforward (VFF) input or torque feedforward (TFF) input if required. An improper feedforward input may result in overshooting.
5
5-69
5-70
5 Adjustments
5.7.3 Related Parameters
5.7.3
Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn140
Pn141
Pn142
Pn143
Pn144
Pn145
Pn146
Pn147
Pn14A
Pn14B
Name
Model Following Control Related Switch
Model Following Control Gain
Model Following Control Gain Compensation
Model Following Control Bias (Forward Direction)
Model Following Control Bias (Reverse Direction)
Vibration Suppression 1 Frequency A
Vibration Suppression 1 Frequency B
Model Following Control Speed Feedforward Compensation
Vibration Suppression 2 Frequency
Vibration Suppression 2 Compensation
Mid-execution changes
Yes
No
No
No
No
No
No
No
No
No
Automatic changes
Yes
Yes
No
No
No
Yes
Yes
No
No
No
5.8 Additional Adjustment Function
5.8
Additional Adjustment Function
This section describes the functions that can be used for additional fine tuning after making adjustments with advanced autotuning, advanced autotuning by reference, or one-parameter tuning.
• Switching gain settings
• Friction compensation
• Current control mode selection
• Current gain level setting
• Speed detection method selection
5.8.1
Switching Gain Settings
Two gain switching functions are available, manual switching and automatic switching. The manual switching function uses an external input signal to switch gains, and the automatic switching function switches gains automatically.
By using the gain switching function, the positioning time can be shortened by increasing the gain during positioning and vibration can be suppressed by decreasing the gain while it is stopped.
Pn139
Parameter n.
0
[Factory setting] n.
2
Function
Manual gain switching
Automatic gain switching
Note: n.
1 is reserved. Do not use.
When Enabled Classification
Immediately
For the gain combinations for switching, refer to (1) Gain Combinations for Switching .
Tuning
For the manual gain switching, refer to (2) Manual Gain Switching .
For the automatic gain switching, refer to (3) Automatic Gain Switching .
(1) Gain Combinations for Switching
Setting
Gain
Setting 1
Gain
Setting 2
Speed Loop
Gain
Pn100
Speed Loop
Gain
Pn104
2nd Speed Loop
Gain
Speed Loop
Integral Time
Constant
Pn101
Speed Loop
Integral Time
Constant
Pn105
2nd Speed Loop
Integral Time
Constant
Position Loop
Pn102
Gain
Gain
Position Loop
Pn106
2nd Position
Loop Gain
Torque
Reference
Filter
Pn401
Torque Reference Filter Time
Constant
Model
Following
Control Gain
Pn141
Model Following Control
Gain
*
Pn412
1st Step 2nd
Torque Reference Filter Time
Constant
Pn148
*
2nd Model Following Control
Gain
Model
Following
Control Gain
Compensation
Pn142
*
Model Following Control
Gain Compensation
Pn149
*
2nd Model Following Control
Gain Compensation
Friction
Compensation
Gain
Pn121
Friction Compensation Gain
Pn122
2nd Gain for
Friction
Compensation
∗ The switching gain settings for the model following control gain and the model following control gain compensation are available only for manual gain switching. To enable the gain switching of these parameters, a gain switching input signal must be sent, and the following conditions must be met.
• No command being executed.
• Motor having been completely stopped.
If these conditions are not satisfied, the applicable parameters will not be switched although the other parameters shown in this table will be switched.
5
5-71
5-72
5 Adjustments
5.8.1 Switching Gain Settings
(2) Manual Gain Switching
Manual gain switching uses G-SEL of the servo command output signals (SVCMD_IO) to switch between gain setting 1 and gain setting 2.
Type
Input
Command Name
G-SEL of the servo command output signals
(SVCMD_IO)
0
1
Setting Meaning
Switches to gain setting 1.
Switches to gain setting 2.
(3) Automatic Gain Switching
Automatic gain switching is enabled only in position control. The switching conditions are specified using the following settings.
Parameter Setting
Pn139 n.
2
Switching Condition
Condition A satisfied.
Condition A not satisfied.
Setting
Gain setting 1 to gain setting 2
Gain setting 2 to gain setting 1
Select one of the following settings for switching condition A.
Pn139
Parameter
Switching Condition A for Position Control
For Other than
Position Control (No
Switching) n.
0
[Factory setting] n.
n.
n.
n.
n.
1
2
3
4
5
Positioning completed signal (/COIN) ON
Positioning completed signal (/COIN) OFF
Positioning near signal
(/NEAR) ON
Positioning near signal
(/NEAR) OFF
No output for position reference filter and position reference input OFF
Position reference input
ON
Fixed in gain setting 1
Fixed in gain setting 2
Fixed in gain setting 1
Fixed in gain setting 2
Fixed in gain setting 1
Fixed in gain setting 2
Switching Wait
Time
Pn135
Gain Switching
Waiting Time 1
Pn136
Gain Switching
Waiting Time 2
When
Enabled
Immediately
Switching Time
Pn131
Gain Switching
Time 1
Pn132
Gain Switching
Time 2
Classification
Tuning
Automatic switching pattern 1 (Pn139.0 = 2)
Condition A satisfied
Switching Waiting Time 1 Pn135
Switching Time 1 Pn131
Gain
Settings 1
Pn100
Pn101
Pn102
Pn121
Pn401
Switching Waiting Time 2 ޓ Pn136
Switching Time 2 ޓ Pn132
Condition A not satisfied
Gain
Settings 2
Pn104
Pn105
Pn106
Pn122
Pn412
5.8 Additional Adjustment Function
Relationship between the Waiting and Switching Times for Gain Switching
In this example, the "positioning completed signal (/COIN) ON" condition is set as condition A for automatic gain switching. The position loop gain is switched from the value in Pn102 (position loop gain) to the value in
Pn106 (2nd position loop gain). When the /COIN signal goes ON, the switching operation begins after the waiting time set in Pn135. The switching operation changes the position loop gain linearly from Pn102 to
Pn106 within the switching time set in Pn131.
Pn102
Position Loop Gain
Switching
Waiting Time
Pn135
Switching Time
Pn131
Pn106
2nd Position
Loop Gain
/COIN
Switching condition A satisfied
Note: Automatic gain switching is available in the PI and I-P controls (Pn10B).
(4) Related Parameters
Pn100
Pn101
Pn102
Pn401
Pn141
Pn142
Pn121
Pn104
Speed Loop Gain
Setting Range
10 to 20000
Setting Unit
0.1 Hz
Speed Loop Integral Time Constant
Setting Range
15 to 51200
Position Loop Gain
Setting Unit
0.01 ms
Setting Range
10 to 20000
Setting Unit
0.1/s
Torque Reference Filter Time Constant
Setting Range
0 to 65535
Model Following Control Gain
Setting Unit
0.01 ms
Setting Range
10 to 20000
Setting Unit
0.1/s
Model Following Control Gain Compensation
Setting Range
500 to 2000
Setting Unit
0.1%
Speed Position
Factory Setting
400
Speed Position
Factory Setting
2000
Factory Setting
400
When Enabled
Immediately
Position
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
Classification
Tuning
Speed Position Torque
Factory Setting
100
When Enabled
Immediately
Classification
Tuning
Factory Setting
500
Factory Setting
1000
When Enabled
Immediately
Position
When Enabled
Immediately
Position
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
Friction Compensation Gain
Setting Range
10 to 1000
Setting Unit
1%
2nd Speed Loop Gain
Setting Range
10 to 20000
Setting Unit
0.1 Hz
Speed Position
Factory Setting
100
Factory Setting
400
When Enabled
Immediately
Speed Position
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
5
5-73
5-74
5 Adjustments
5.8.1 Switching Gain Settings
Pn105
Pn106
Pn412
Pn148
Pn149
Pn122
(cont’d)
2nd Speed Loop Integral Time Constant
Setting Range
15 to 51200
2nd Position Loop Gain
Setting Unit
0.01 ms
Speed
Factory Setting
2000
Position
When Enabled
Immediately
Setting Range
10 to 20000
Setting Unit
0.1/s
1st Step 2nd Torque Reference Filter Time
Constant
Setting Range Setting Unit
0 to 65535 0.01 ms
Factory Setting
Speed
400
Factory Setting
100
Position
Position
When Enabled
Immediately
Torque
When Enabled
Immediately
2nd Model Following Control Gain
Setting Range
10 to 20000
Setting Unit
0.1/s
Factory Setting
500
Position
When Enabled
Immediately
2nd Model Following Control Gain Compensation
Setting Range
500 to 2000
Setting Unit
0.1%
Factory Setting
1000
Position
When Enabled
Immediately
2nd Gain for Friction Compensation
Setting Range
10 to 1000
Setting Unit
1%
Speed Position
Factory Setting
100
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
Classification
Tuning
Classification
Tuning
Classification
Tuning
Classification
Tuning
(5) Parameters for Automatic Gain Switching
Pn131
Pn132
Pn135
Pn136
Gain Switching Time 1
Setting Range
0 to 65535
Setting Unit
1 ms
Gain Switching Time 2
Setting Range
0 to 65535
Setting Unit
Gain Switching Waiting Time 1
1 ms
Setting Range
0 to 65535
Setting Unit
Gain Switching Waiting Time 2
1 ms
Setting Range
0 to 65535
Setting Unit
1 ms
(6) Related Monitor
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
Monitor No. (Un)
Un014
Name
Effective gain monitor
Value
1
2
For gain setting 1
Remarks
For gain setting 2
Note: When using the tuning-less function, gain setting 1 is enabled.
Parameter No.
Analog
Monitor
Name Output Value
Pn006
Pn007 n.
0B
Effective gain monitor
1 V
2 V
Remarks
Gain setting 1 is enabled.
Gain setting 2 is enabled.
5.8 Additional Adjustment Function
5.8.2
Manual Adjustment of Friction Compensation
Friction compensation rectifies the viscous friction change and regular load change.
The friction compensation function can be automatically adjusted with advanced autotuning (Fn201), advanced autotuning by reference input (Fn202), or one-parameter tuning (Fn203). This section describes the steps to follow if manual adjustment is required.
(1) Required Parameter Settings
The following parameter settings are required to use friction compensation.
Pn408
Parameter n.0
[Factory setting] n.1
Function
Does not use friction compensation.
Uses friction compensation.
When Enabled Classification
Immediately Setup
Pn121
Pn123
Pn124
Pn125
Friction Compensation Gain
Setting Range
10 to 1000
Setting Unit
1%
Friction Compensation Coefficient
Setting Range
0 to 100
Setting Unit
1%
Friction Compensation Frequency Correction
Setting Range
-10000 to 10000
Setting Unit
0.1 Hz
Friction Compensation Gain Correction
Setting Range
1 to 1000
Setting Unit
1%
Speed Position
Factory Setting
100
When Enabled
Immediately
Classification
Tuning
Speed Position
Factory Setting
0
When Enabled
Immediately
Classification
Tuning
Speed Position
Factory Setting
0
When Enabled
Immediately
Classification
Tuning
Speed Position
Factory Setting
100
When Enabled
Immediately
Classification
Tuning
5
5-75
5-76
5 Adjustments
5.8.2 Manual Adjustment of Friction Compensation
(2) Operating Procedure for Friction Compensation
The following procedure is used for friction compensation.
CAUTION
• Before using friction compensation, set the moment of inertia ratio (Pn103) as accurately as possible. If the wrong moment of inertia ratio is set, vibration may result.
Step
1
Operation
Set the following parameters for friction compensation to the factory setting as follows.
Friction compensation gain (Pn121): 100
Friction compensation coefficient (Pn123): 0
Friction compensation frequency correction (Pn124): 0
Friction compensation gain correction (Pn125): 100
Note: Always use the factory-set values for friction compensation frequency correction (Pn124) and friction compensation gain correction (Pn125).
To check the effect of friction compensation, gradually increase the friction compensation coefficient (Pn123).
Note: Usually, set the friction compensation coefficient value to 95% or less. If the effect is insufficient, increase the friction compensation gain (Pn121) by 10% increments until it stops vibrating.
2
Effect of Parameters for Adjustment
Pn121: Friction Compensation Gain
This parameter sets the responsiveness for external disturbance. The higher the set value is, the better the responsiveness will be. If the equipment has a resonance frequency, however, vibration may result if the set value is excessively high.
Pn123: Friction Compensation Coefficient
This parameter sets the effect of friction compensation. The higher the set value is, the more effective friction compensation will be. If the set value is excessively high, however, the vibration will occur easily. Usually, set the value to 95% or less.
Effect of Adjustment
The following graph shows the responsiveness with and without proper adjustment.
Insufficient responsiveness because of friction
Small friction
Responsiveness
ᡂᄢ㧘ᡂዊ friction compensation.
MECHA
3
Large friction
Without friction compensation With friction compensation
5.8 Additional Adjustment Function
5.8.3
Current Control Mode Selection Function
This function reduces high-frequency noises while the servomotor is being stopped. This function is enabled by default and set to be effective under different application conditions. Set Pn009.1 = 1 to use this function.
When Enabled Classification
Pn009
Parameter n. 0 n. 1
[Factory setting]
Meaning
Selects the current control mode 1.
Selects the current control mode 2 (low noise).
After restart Tuning
• If current control mode 2 is selected, the load ratio may increase while the servomotor is being stopped.
5.8.4
Current Gain Level Setting
This function reduces noises by adjusting the parameter value for current control inside the SERVOPACK according to the speed loop gain (Pn100). The noise level can be reduced by reducing the current gain level
(Pn13D) from its factory setting of 2000% (disabled). If the set value of Pn13D is decreased, the level of noise will be lowered, but the response characteristics of the SERVOPACK will also be degraded. Adjust the current gain level within the allowable range at which SERVOPACK response characteristics can be secured.
Pn13D
Current Gain Level
Setting Range
100 to 2000
Speed Position
Factory Setting
2000
When Enabled
Immediately
Classification
Setting Unit
1% Tuning
• If the parameter setting of the current gain level is changed, the responses characteristics of the speed loop will also change. The SERVOPACK must, therefore, be readjusted again.
5.8.5
Speed Detection Method Selection
This function can ensure smooth movement of the servomotor while the servomotor is running. Set the value of Pn009.2 to 1 and select speed detection 2 to smooth the movement of the servomotor while the servomotor is running.
Pn009
Parameter n. 0
[Factory setting] n. 1
Meaning
Selects speed detection 1.
Selects speed detection 2.
When Enabled
After restart
Classification
Tuning
• If the speed detection method is changed, the response characteristics of the speed loop will change and the SERVOPACK must be readjusted again.
5
5-77
5-78
5 Adjustments
5.8.6 Backlash Compensation Function
5.8.6
Backlash Compensation Function
(1) Overview
When driving a machine with backlash, there will be a deviation between the travel distance in the position reference that is managed by the host controller and the travel distance of the actual machine. Use backlash compensation function to add the backlash compensation value to the position reference and use the result to drive the servomotor. This means that the travel distance of the actual machine will be the same as the travel distance in the host controller.
Note 1. This function is supported only for position control.
2. Software version 0023 or higher is required to use this function. The software version can be confirmed in Fn012.
For details, refer to 6.14 Software Version Display (Fn012) .
Machine axis
Travel distance by position reference
MECHA
Backlash compensation value
Travel distance by position reference
Motor axis
Reference forward rotational direction
Machine axis (e.g. table)
Motor axis
Backlash (play due to mechanical precision)
(2) Related Parameter
Set the following parameter to use backlash compensation.
Backlash Compensation Direction
Set the direction in which to apply backlash compensation.
Pn230
Parameter n. 0
[Factory setting] n. 1
Function
Compensates with a reference in the forward direction.
When Enabled Classification
After restart Setup
Compensates with a reference in the reverse direction.
Backlash Compensation Value
Set the amount of backlash compensation to add to the position reference.
The amount is set in increments of 0.1 reference unit. However, when the amount is converted to encoder pulses, it is rounded off at the decimal point.
Example: If Pn231 is set to 6,553.6 [reference unit] and the electronic gear ratio (Pn20E/Pn210) is set to 4/1, then the pulse equivalent is 6,553.6 × 4 = 26,214.4 [pulses].
The backlash compensation value will be 26,214 encoder pulses.
Pn231
Backlash compensation value
Setting Range
-500000 to +500000
Position
Setting Unit Factory Setting When Enabled
0.1 reference unit
0 Immediately
Classification
Setup
5.8 Additional Adjustment Function
• The backlash compensation value is restricted by the following formula. The specified compensation is not performed if this condition is not met.
Pn231 ҇
Pn210
Pn20E
×
Maximum motor speed [min -1 ]
60
× Encoder resolution × 0.00025
∗ For details, refer to 4.4.3 Electronic Gear .
Example:
If Pn20E is set to 4, Pn210 is set to 1, the maximum motor speed is 6,000 [min
-1
], and the encoder resolution is 131,072 (17 bits),
1/4 × 6000/60 × 131072 × 0.00025 = 819.2 [reference units]
Therefore, the maximum backlash compensation value is 819.2 reference units.
• Do not exceed the upper limit of the backlash compensation value. The upper limit of the backlash compensation value can be confirmed in Un031.
Backlash Compensation Time Constant
Set a time constant for a first order lag filter to use when adding the backlash compensation value (Pn231) to the position reference.
If you set Pn233 to 0, the first order lag filter is disabled.
Pn233
Backlash compensation time constant
Setting Range
0 to 65535
Position
Setting Unit Factory Setting When Enabled
0.01 ms 0 Immediately
Classification
Setup
Note: Changes to the set value are applied when there is no position reference input and the servomotor is stopped. The current operation is not affected if the set value is changed during servomotor operation.
(3) Related Monitor
The following monitoring parameters provide information on backlash compensation.
Un No.
Un030
Un031
Displayed Information
The current backlash compensation value
Backlash compensation setting limit value
Unit
0.1 reference unit
0.1 reference unit
(4) Compensation Operation
This section describes the operation that is performed for backlash compensation.
Note: The following figures are for when backlash compensation is applied for references in the forward direction
(Pn230.0 = 0). The following monitoring information is provided in the figures: TPOS (target position in the reference coordinate system), POS (reference position in the reference coordinate system), and APOS (feedback position in the machine coordinate system). The monitoring information includes the feedback position in machine coordinate system (APOS) and other feedback information. The backlash compensation value is subtracted from the feedback positions in the monitoring information, so it is not necessary for the host controller to consider the backlash compensation value.
CAUTION
• The encoder dividing pulse output will output the number of encoder pulses for which driving was actually performed, including the backlash compensation value. If using the encoder dividing pulse output for position feedback at the host controller, must consider the backlash compensation value.
5
5-79
5-80
5 Adjustments
5.8.6 Backlash Compensation Function
When Servo is ON
The backlash compensation value (Pn231) is added in the compensation direction when the servo is ON (i.e., the servomotor is powered) and a reference is input in the same direction as the backlash compensation direction (Pn230.0). If there is a reference input in the direction opposite to the backlash compensation direction, the backlash compensation value is not added (i.e., backlash compensation is not performed).
The relationship between APOS and the servomotor shaft position is as follows:
• If a reference is input in the compensation direction: APOS = Motor shaft position - Pn231
• If a reference is input in the direction opposite to the compensation direction: APOS = Motor shaft position
The following figure shows driving the servomotor in the forward direction from target position TPOS0 to
TPOS1 and then to TPOS2, and then returning from TPOS2 to TPOS1 and then to TPOS0.
Backlash compensation is applied when moving from TPOS0 to TPOS1, but not when moving from TPOS2 to
TPOS1.
Servo ON
If a reference is input in the compensation direction
POS
APOS
Machine axis
Target position
TPOS0
Travel distance 䋱
Target position
TPOS1
Travel distance 䋲
Target position
TPOS2
Pn231
Travel distance 䋱 Travel distance 䋲
Motor axis
MECHA
Machine axis
Motor axis
If a reference is input in the direction opposite to the compensation direction
POS
APOS
Machine axis
Motor axis
Machine axis
Motor axis
Backlash (= Pn231)
Travel distance
Travel distance
䋱
䋱
Travel distance 䋲
Travel distance 䋲
Pn231
Backlash (= Pn231)
5.8 Additional Adjustment Function
When Servo is OFF
Backlash compensation is not applied when the servo is OFF (i.e., when the servomotor is not powered).
Therefore, the reference position POS moves by only the backlash compensation value.
The relationship between APOS and the servomotor shaft position is as follows:
• When servo is OFF: APOS = Servomotor shaft position
The following figure shows what happens when the servo is turned OFF after driving the servomotor in the forward direction from target position TPOS0 to TPOS1. Backlash compensation is not applied when the servo is OFF (i.e., the SERVOPACK manages the position data so that APOS and POS are the same).
Servo OFF MECHA
Target position
TPOS0
Target position
TPOS1
Travel distance
POS
APOS
Status with no backlash compensation POS = APOS
Machine axis
Pn231
Travel distance
Motor axis
Machine axis
Motor axis
Backlash 䋨 = Pn231 䋩
When There is Overtravel
When there is overtravel (i.e., when driving is prohibited due to an overtravel signal or software limit), the operation is the same as for When Servo is OFF , i.e., backlash compensation is not applied.
When Control is Changed
Backlash compensation is performed only for position control.
Backlash compensation is not applied if changing from position control to any other type of control.
Backlash compensation is applied in the same way as When Servo is ON if changing from any other type of control to position control.
(5) Monitor Functions (Un Monitoring)
Un No.
Displayed Information
Un007 Input reference speed
Un008 Position error amount
Un00C Input reference counter
Un00D Feedback pulse counter
Un013 Feedback pulse counter
Unit min
-1
Reference unit
Reference unit
Encoder pulse
Reference unit
Specification
Indicates the input reference speed before backlash compensation.
Displays the position error with respect to the position reference after backlash compensation.
Displays the input reference counter before backlash compensation.
Displays the pulse count of the actually driven motor encoder.
Displays the pulse count of the actually driven encoder in reference units.
5
5-81
5-82
5 Adjustments
5.8.6 Backlash Compensation Function
(6) MECHATROLINK Monitor Information
This section describes the information that is set for the MECHATROLINK monitoring information (Monitor
1, Monitor 2, Monitor 3, and Monitor 4) and the backlash compensation operation.
Monitor
Code
0
1
2
3
4
5
6
E
F
Designation
POS
Meaning
Reference position in the reference coordinate system (after the position reference filter)
MPOS Reference position
PERR Position error
APOS
LPOS
IPOS
TPOS
OMN1
OMN2
Feedback position in the machine coordinate system
Feedback latch position in the machine coordinate system
Reference position in the reference coordinate system (before the position reference filter)
Target position in the reference coordinate system
Option monitor 1
(selected with Pn824)
Option monitor 2
(selected with Pn825)
Unit Remarks
Reference unit
Reference unit
Reference unit
Reference unit
Reference unit
Reference unit
Reference unit
–
–
–
–
Feedback position with the backlash compensation subtracted
Feedback position with the backlash compensation subtracted
–
–
–
– –
Parameters Monitor Information
0003H Position error (lower 32 bits)
Pn824
Pn825
0004H Position error (upper 32 bits)
000AH Encoder count (lower 32 bits)
000BH Encoder count (upper 32 bits)
000CH
000DH
Reserved
0017H Un007: Input reference speed
0018H Un008: Position error amount
001CH Un00C: Input reference counter
001DH Un00D: Feedback pulse counter
0080H
Previous value of latched feedback position (LPOS)
Output Unit
Reference unit
Reference unit
Reference unit
Reference unit
Remarks
–
–
Count value of the actually driven motor encoder
– – min
-1
Reference unit
Reference unit
Encoder pulse
Encoder pulse
Same as monitor mode Un007
Same as monitor mode Un008
Same as monitor mode Un00C
Same as monitor mode Un00D
Feedback position with the backlash compensation subtracted
5.8 Additional Adjustment Function
Related Monitoring Diagrams
MECHA
Speed conversation
[U][M]: Un00C
[A][T]: Position reference speed
[U][M]: Un007
[M]: IPOS
[M]: TPOS Position reference
Position reference filter
Electronic gear
[M]: MPOS
([M]: POS)
Backlash compensation function
[M]: PERR
Error counter
㧗
㧙
㧗
[A][T]: Speed feedforward
[A][T]: Position amplifier error
㧙
Feedforward
Error counter
Kp
<Legend symbols>
[A]: Analog monitoring
[U]: Monitor mode
(Un monitoring)
[O]: Outpur signal
[T]: Trace data object
[M]: MECHATROLINK
monitor information
㧗 㧗
Speed/ current loop
㧹 Load
Speed conversation
ENC
External
ENC
㧗 㧙
Error counter
[U]: Un013
㧝
Electronic gear
[A][T][M]: Position error
[U][M]: Un008
Output signal processing
[A][O][T]: Positioning completed
[A][T]: Completion of position reference
[O][T]: Position near [M]: APOS
[M]: Previous value for LPOS
[M]: LPOS
㧝
Electronic gear
㧝
Electronic gear
Latch signal
Backlash compensation function
[U][M]: Un00D
[U][M]: Un00E
[M]: PG count
[M]: FPG count
5
5-83
5-84
5 Adjustments
5.9.1 Feedforward Reference
5.9
Compatible Adjustment Function
The DC Power Input Σ -V series SERVOPACKs have adjustment functions as explained in sections 5.1
to 5.8
to make machine adjustments.
This section explains compatible functions provided by earlier models, such as the Σ -III Series SERVOPACK.
5.9.1
Feedforward Reference
This function applies feedforward compensation to position control and shortens positioning time.
Differential
Pn109
Feedforward Gain
MECHA
Position reference
Pn10A
Feedforward Filter
Time Constant
+ + +
Position loop gain (Kp)
-
Feedback pulse
Pn109
Feedforward Gain
Setting Range
0 to 100
Setting Unit
1%
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
Feedforward Filter Time Constant
Setting Unit
0.01 ms
Factory Setting
0
Position
When Enabled
Immediately
Classification
Pn10A
Setting Range
0 to 6400 Tuning
Note: Too high value may cause the machine to vibrate. For ordinary machines, set 80% or less in this parameter.
5.9 Compatible Adjustment Function
5.9.2
Mode Switch (P/PI Switching)
The mode switch automatically switches between proportional and PI control. Set the switching condition with Pn10B.0 and set the level of detection points with Pn10C, Pn10D, Pn10E, and Pn10F.
Overshooting caused by acceleration and deceleration can be suppressed and the settling time can be reduced by setting the switching condition and detection points.
With Mode Switch
Motor speed
Without Mode Switch
Overshoot
Actual servomotor operation
Motor speed
Reference
Overshoot
Settling time
Time
Settling time
Time
(1) Related Parameters
Select the switching condition of the mode switch with Pn10B.0.
Parameter Mode Switch Selection
Pn10B n.
0
[Factory setting] n.
n.
n.
n.
1
2
3
4
Uses an internal torque reference level for the switching conditions.
Uses a speed reference level for the switching conditions.
Uses an acceleration level for the switching conditions.
Uses a position error level for the switching conditions.
Does not use mode switch function.
Parameter
Containing
Detection
Point Setting
When
Enabled
Classification
Pn10C
Pn10D
Pn10E
Pn10F
−
Immediately
Setup
Parameters to Set the Level of Detection Points
Pn10C
Mode Switch (Torque Reference)
Setting Range Setting Unit
0 to 800 1%
Pn10D
Mode Switch (Speed Reference)
Setting Range
0 to 10000
Setting Unit
1 min
-1
Pn10E
Pn10F
Mode Switch (Acceleration)
Setting Range
0 to 30000
Setting Unit
1 min
-1
/s
Mode Switch (Position Error)
Setting Range Setting Unit
0 to 10000 1 reference unit
Speed Position
Factory Setting When Enabled
200 Immediately
Speed Position
Factory Setting When Enabled
0 Immediately
Speed Position
Factory Setting When Enabled
0 Immediately
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
Classification
Tuning
Classification
Tuning
5
5-85
5-86
5 Adjustments
5.9.2 Mode Switch (P/PI Switching)
(2) Operating Examples for Different Switching Conditions
Using the Torque Reference [Factory Setting]
With this setting, the speed loop is switched to P control when the value of torque reference input exceeds the torque set in Pn10C. The factory setting for the torque reference detection point is 200% of the rated torque.
Speed
Speed reference
Motor speed
Time
+Pn10C
Torque
Reference
0
- Pn10C
Torque reference
PI P PI Control P PI Control
Using the Speed Reference
With this setting, the speed loop is switched to P control when the value of speed reference input exceeds the speed set in Pn10D.
Speed
Speed reference
Motor speed
Pn10D
PI P Control
Time
PI Control
Using Acceleration
With this setting, the speed loop is switched to P control when the speed reference exceeds the acceleration set in Pn10E.
Speed
Speed reference
Motor speed
Time
Motor acceleration
+Pn10E
Acceleration 0
- Pn10E
PI P PI Control P PI Control
Using the Position Error
With this setting, the speed loop is switched to P control when the position error exceeds the value set in
Pn10F.
This setting is effective with position control only.
Speed reference
Speed
Motor speed
Time
Position error
Pn10F
PI P Control PI Control
5.9 Compatible Adjustment Function
5.9.3
Torque Reference Filter
As shown in the following diagram, the torque reference filter contains first order lag filter and notch filters arrayed in series, and each filter operates independently. The notch filters can be enabled and disabled with the
Pn408.
Torque Related
Function Switch
Pn408
Torque reference before filtering
Torque
Reference
Filter
(Pn401)
*
2nd
Torque
Reference
Filter
(Pn40F,
Pn410)
1st Notch
Filter
(Pn409,
Pn40A, and Pn40B)
2nd
Notch
Filter
(Pn40C,
Pn40D, and
Pn40E)
Torque reference after filtering
First order lag filter Second order lag filter
Notch filter Notch filter
* The 2nd torque reference filter is enabled when Pn40F is set to a value less than
5000 and disabled when Pn40F is set to 5000 (factory setting).
(1) Torque Reference Filter
If you suspect that machine vibration is being caused by the servo drive, try adjusting the filter time constants with Pn401. This may stop the vibration. The lower the value, the better the response will be, but there may be a limit that depends on the machine conditions.
Pn401
Torque Reference Filter Time Constant Speed Position Torque
Setting Range
0 to 65535
Setting Unit
0.01 ms
Factory Setting
100
When Enabled
Immediately
Classification
Tuning
Torque
Reference Filter Setting Guide
Use the speed loop gain (Pn100 [Hz]) and the torque filter time constant (Pn401 [ms]) to set the torque reference filter.
Adjusted value for stable control: Pn401 [ms] ≤ 1000/ (2 π × Pn100 [Hz] × 4)
Critical gains: Pn401 [ms] < 1000/ (2 π × Pn100 [Hz] × 1)
Pn40F
Pn410
2nd Step 2nd Torque Reference Filter
Frequency
Setting Range
100 to 5000
Setting Unit
1 Hz
2nd Step 2nd Torque Reference Filter
Q Value
Setting Range
50 to 100
Setting Unit
0.01
∗ The filter is disabled if 5000 is set.
Speed Position Torque
Factory Setting
5000*
When Enabled
Immediately
Speed Position Torque
Factory Setting
50
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
5
5-87
5-88
5 Adjustments
5.9.3 Torque Reference Filter
(2) Notch Filter
The notch filter can eliminate specific frequency elements generated by the vibration of sources such as resonance of the shaft of a ball screw. The notch filter puts a notch in the gain curve at the specific vibration frequency. The frequency characteristics near the notch can be reduced or removed with this filter. A higher Q value produces a sharper notch and phase delay.
Q value = 1.0
Notch Filter
Q value = 0.7
Notch Filter
100
0
Gain
(db)
-100
-200
-300
10
2
10
3
Frequency (Hz)
Notch Filter
10
4
0
-100
Phase
(deg)
-200
-300
-400
10
2
10
3
Frequency (Hz)
10
4
The notch filter can be enabled or disabled with Pn408.
100
0
Gain
(db)
-100
-200
-300
10
2
0
-100
Phase
(deg)
-200
-300
-400
10
2
Pn408
Parameter n.
0
[Factory setting] n.
1 n.
0
[Factory setting] n.
1
Meaning
Disables 1st notch filter.
Enables 1st notch filter.
Disables 2nd notch filter.
Enables 2nd notch filter.
Set the machine's vibration frequency as a parameter of the notch filter.
10
3
Frequency (Hz)
Notch Filter
10
3
Frequency (Hz)
10
4
10
4
When Enabled Classification
Immediately Setup
Pn409
Pn40A
Pn40B
Pn40C
Pn40D
1st Notch Filter Frequency
Setting Range
50 to 5000
Setting Unit
1 Hz
1st Notch Filter Q Value
Setting Range
50 to 1000
Setting Unit
0.01
1st Notch Filter Depth
Setting Range
0 to 1000
Setting Unit
0.001
2nd Notch Filter Frequency
Setting Range
50 to 5000
Setting Unit
1 Hz
2nd Notch Filter Q Value
Setting Range
50 to 1000
Setting Unit
0.01
Speed Position Torque
Factory Setting
5000
When Enabled
Immediately
Speed Position Torque
Factory Setting
70
When Enabled
Immediately
Speed Position Torque
Factory Setting
0
When Enabled
Immediately
Speed Position Torque
Factory Setting
5000
When Enabled
Immediately
Speed Position Torque
Factory Setting
70
When Enabled
Immediately
Classification
Tuning
Classification
Tuning
Classification
Tuning
Classification
Tuning
Classification
Tuning
5.9 Compatible Adjustment Function
Pn40E
2nd Notch Filter Depth
Setting Range
0 to 1000
Setting Unit
0.001
Speed Position Torque
Factory Setting
0
When Enabled
Immediately
(cont’d)
Classification
Tuning
• Sufficient precautions must be taken when setting the notch filter frequencies. Do not set the notch filter frequencies (Pn409 or Pn40C) that is close to the speed loop’s response frequency. Set the frequencies at least four times higher than the speed loop’s response frequency. Setting the notch filter frequency too close to the response frequency may cause vibration and damage the machine.
• Change the notch filter frequencies (Pn409 or Pn40C) only when the servomotor is stopped. Vibration may occur if the notch filter frequency is changed when the servomotor is rotating.
5.9.4
Position Integral
The position integral is the integral function of the position loop. It is used for the electronic cams and electronic shafts when using the SERVOPACK with YASKAWA MP900/2000 Machine Controllers.
Pn11F
Position Integral Time Constant
Setting Range
0 to 50000
Setting Unit
0.1 ms
Factory Setting
0
Position
When Enabled
Immediately
Classification
Tuning
5
5-89
6
Utility Functions (Fn
)
6.1 List of Utility Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Alarm History Display (Fn000) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
6.3 JOG Operation (Fn002) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
6.4 Origin Search (Fn003) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
6.5 Program JOG Operation (Fn004) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
6.6 Initializing Parameter Settings (Fn005) . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
6.7 Clearing Alarm History (Fn006) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-19
6.8 Offset Adjustment of Analog Monitor Output (Fn00C) . . . . . . . . . . . . . . 6-20
6.9 Gain Adjustment of Analog Monitor Output (Fn00D) . . . . . . . . . . . . . . . 6-22
6.10 Automatic Offset-Signal Adjustment of the Motor Current Detection
Signal (Fn00E) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-24
6.11 Manual Offset-Signal Adjustment of the Motor Current Detection
Signal (Fn00F) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
6.12 Write Prohibited Setting (Fn010) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28
6.13 Servomotor Model Display (Fn011) . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-30
6.14 Software Version Display (Fn012) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-31
6.15 Vibration Detection Level Initialization (Fn01B) . . . . . . . . . . . . . . . . . . 6-32
6.16 Display of SERVOPACK and Servomotor ID (Fn01E) . . . . . . . . . . . . . 6-35
6.17 Software Reset (Fn030) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-36
6.18 EasyFFT (Fn206) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-41
6.19 Online Vibration Monitor (Fn207) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-45
6
6-1
6-2
6 Utility Functions (Fn )
6.1
List of Utility Functions
Utility functions are used to execute the functions related to servomotor operation and adjustment.
Each utility function has a number starting with Fn.
The following table lists the utility functions and reference section.
Fn200
Fn201
Fn202
Fn203
Fn204
Fn205
Fn206
Fn207
Function
No.
Fn000
Fn002
Fn003
Fn004
Fn005
Fn006
Fn008
Fn00C
Fn00D
Fn00E
Fn00F
Fn010
Fn011
Fn012
Fn013
Fn01B
Fn01E
Fn030
Alarm history display
JOG operation
Origin search
Function
Program JOG operation
Initializing parameter settings
Clearing alarm history
Absolute encoder multiturn reset and encoder alarm reset
Offset adjustment of analog monitor output
Gain adjustment of analog monitor output
Automatic offset-signal adjustment of the motor current detection signal
Manual offset-signal adjustment of the motor current detection signal
Write prohibited setting
Servomotor model display
Software version display
Multiturn limit value setting change when a multiturn limit disagreement alarm occurs
Vibration detection level initialization
Display of SERVOPACK and servomotor ID
Software reset
Tuning-less levels setting
Advanced autotuning
Advanced autotuning by reference
One-parameter tuning
Anti-resonance control adjustment function
Vibration suppression function
EasyFFT
Online vibration monitor
Reference
Section
6.2
6.3
6.4
6.5
6.6
6.7
4.7.4
6.8
6.9
6.10
6.11
6.12
6.13
6.14
Comment: SigmaWin+ function names
Alarm Display
JOG Operation
Origin Search
Program JOG Operation
Editing Parameters
Alarm Display
Setting the Absolute Encoder
Adjusting Analog Monitor
Output
Adjusting Analog Monitor
Output
Adjusting Motor Current
Detection Offset
Adjusting Motor Current
Detection Offset
Write Prohibited Setting
Product Information
Product Information
4.7.6
6.15
6.16
6.17
5.2.2
5.3.2
5.4.2
5.5.2
5.6.2
5.7.2
6.18
6.19
Setting the Multi-Turn Limit
Initializing Vibration Detection Level
Product Information
Resetting the SERVOPACK by Software or MECHA-
TROLINK Communication
Reset
Editing Parameters
Tuning
Tuning
Tuning
Tuning
Tuning
EasyFFT
Online Vibration Monitor
Note: Execute the utility function with SigmaWin+.
6.2 Alarm History Display (Fn000)
6.2
Alarm History Display (Fn000)
This function displays the last ten alarms that have occurred in the SERVOPACK.
(1) Preparation
There are no tasks that must be performed before displaying the alarm history.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Alarm - Display Alarm .
The Alarm Display dialog box will appear.
MECHA
2.
Click the Alarm traceback tab to view the alarm history.
A list of past alarms can be viewed.
MECHA
Alarm number and Alarm name
Alarm history number
(The greater the number, the older the alarm is.)
6
Note:
• If the same alarm occurs after more than one hour, the alarm will be saved. If it occurs in less than one hour, it will not be saved.
• Delete the alarm history by clicking Clear . The alarm history is not cleared on alarm reset or when the SERVO-
PACK main circuit power is turned OFF.
6-3
6 Utility Functions (Fn )
6.3
JOG Operation (Fn002)
JOG operation is used to check the operation of the servomotor under speed control without connecting the
SERVOPACK to the host controller.
CAUTION
• While the SERVOPACK is in JOG operation, the overtravel function will be disabled. Consider the operating range of the machine when performing JOG operation for the SERVOPACK.
(1) Preparation
The following conditions must be met to perform a jog operation.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The main circuit power supply must be ON.
• All alarms must be cleared.
• The servomotor power must be OFF.
• The JOG speed must be set considering the operating range of the machine.
Set the jog speed in Pn304.
Pn304
Jog Speed
Setting Range
0 to 10000
Setting Unit
1 min
-1
Speed Position Torque
Factory Setting When Enabled
500 Immediately
Classification
Setup
(2) Operating Procedure
Use the following procedure. The following example is given when the rotating direction of servomotor is set as Pn000.0=0 (Forward rotation by forward reference).
1.
In the SigmaWin+ main window, click Test Run - JOG Operation .
A warning message about possible dangers will appear and ask if you want to continue.
MECHA
6-4
If these conditions are not acceptable and you do not want to continue, click Cancel to return to the main window without performing a JOG operation.
<When the Write Prohibited Setting Parameter (Fn010) is enabled.>
If writing is prohibited by the Fn010, the following message will appear and tell you to change the setting.
MECHA
6.3 JOG Operation (Fn002)
Click OK and then change the setting of the Fn010 to allow writing.
For details on how to change the setting, refer to 6.12 Write Prohibited Setting (Fn010) .
2.
Click OK .
The JOG Operation box will appear.
If the power to the servomotor is on, an error message will appear. Make sure that the power to the servomotor is off.
MECHA
The speed set in Pn304 will be shown. Click Edit if you want to change the speed.
On the left side of the Operation group, the color of the button and the text in the box changes to indicate if the power to the servomotor is on or off. The name of the square button will change to reflect the current status of the servomotor's power. When the power to the servomotor is off, the square button is labeled
Servo ON . When the power to the servomotor is on, it is labeled Servo OFF .
3.
Click Servo ON .
The JOG Operation box will appear.
MECHA
4.
Press the Forward or Reverse and hold it down. A JOG operation is performed at the speed set at step 2 only while one of the buttons is pressed.
5.
After the JOG operation has been successfully completed, restart the SERVOPACK.
6
6-5
6 Utility Functions (Fn )
6.4
Origin Search (Fn003)
The origin search is designed to position the origin pulse position of the incremental encoder (phase C) and to clamp at the position.
CAUTION
• Perform origin searches without connecting the coupling.
The forward run prohibited (P-OT) and reverse run prohibited (N-OT) signals are not effective in origin search mode.
This function is used when the motor shaft needs to be aligned to the machine.
Motor speed at the time of execution: 60 min
-1
Machine
Servomotor
For aligning the motor shaft to the machine
(1) Preparation
The following conditions must be met to perform the origin search.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The main circuit power supply must be ON.
• All alarms must be cleared.
• The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Setup - Search Origin .
A warning message about possible dangers will appear and ask if you want to continue.
MECHA
6-6
If these conditions are not acceptable and you do not want to continue, click Cancel to return to the main window without performing an origin search.
6.4 Origin Search (Fn003)
<When the Write Prohibited Setting Parameter (Fn010) is enabled.>
If writing is prohibited by the Fn010, the following message will appear and tell you to change the setting.
MECHA
Click OK and then change the setting of the Fn010 to allow writing.
For details on how to change the setting, refer to 6.12 Write Prohibited Setting (Fn010) .
2.
Click OK .
The Origin Search box will appear.
If the power to the servomotor is on, an error message will appear. Make sure that the power to the servomotor is off.
MECHA
States
Operation
Status
This shows the run status of the servomotor.
Origin Search Not Executed: The motor did not turn.
Origin Search Executing: Searching for the origin by turning forward or in reverse.
Origin Search Stopped: The Forward or Reverse button was released during the origin search, so the motor stopped.
Origin Search Completed: The point of origin was found, and the motor was stopped (clamped) at the point.
Operation
On the left side of the Operation group, the color of the button and the text in the box changes to indicate if the power to the servomotor is on or off. The name of the square button will change to reflect the current status of the servomotor's power. When the power to the servomotor is off, the square button is labeled
Servo ON . When the power to the servomotor is on, it is labeled Servo OFF .
6
6-7
6-8
6 Utility Functions (Fn )
3.
Click Servo ON .
The Origin Search box will appear.
MECHA
4.
Press the Forward or Reverse and hold it down until the servomotor stops.
The servomotor will stop after the origin search has been successfully completed.
5.
After the origin search has been successfully completed, restart the SERVOPACK.
6.5 Program JOG Operation (Fn004)
6.5
Program JOG Operation (Fn004)
The program JOG operation is a utility function, that allows continuous operation determined by the preset operation pattern, movement distance, movement speed, acceleration/deceleration time, waiting time, and number of times of movement.
This function can be used to move the servomotor without it having to be connected to a host controller for the machine as a trial operation in JOG operation mode. Program JOG operation can be used to confirm the operation and for simple positioning operations.
(1) Preparation
The following conditions must be met to perform the program JOG operation.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The main circuit power supply must be ON.
• All alarms must be cleared.
• The servomotor power must be OFF.
• The travel distance and speed must be set correctly considering the machine operation range and safe operation speed.
• There must be no overtravel.
(2) Additional Information
• The functions that are applicable for position control, such as position reference filter, can be used.
• The overtravel function is enabled in this function.
(3) Program JOG Operation Patterns
The following describes an example of program JOG operation pattern. The following example is given when the rotating direction of the servomotor is set as Pn000.0 = 0 (Forward rotation by forward reference).
Pn530.0 = 0
(Waiting time Pn535 → Forward movement Pn531) × Number of movements Pn536
Number of times of movement Pn536
Speed
Diagram
Movement speed
Pn533
At zero speed
Pn531
Movement distance
Waiting time
Pn535
Accel/Decel time
Pn534
Waiting time
Pn535
Pn531
Movement distance
Waiting time
Pn535
Pn531
Movement distance
Servomotor
Run Status
(Stop) (Forward) (Stop) (Forward) (Stop) (Forward)
Note: When Pn536 (number of times of program JOG movement) is set to 0, infinite time operation is enabled. To stop infinite time operation, press the cancel or Servo OFF of program JOG operation dialog box to turn OFF the servomotor power.
6
6-9
6 Utility Functions (Fn )
Pn530.0 = 1
(Waiting time Pn535 → Reverse movement Pn531) × Number of movements Pn536
Number of movements Pn536
At zero speed
Movement speed
Pn533
Pn531
Movement distance
Pn531
Movement distance
Pn531
Movement distance
Speed
Diagram
Waiting time
Accel/Decel time
Pn534
Pn535
Waiting time
Pn535
Waiting time
Pn535
Servomotor
Run Status
(Stop) (Reverse) (Stop) (Reverse) (Stop) (Reverse)
Note: When Pn536 (Number of Times of Program JOG Movement) is set to 0, infinite time operation is enabled. To stop infinite time operation, press the cancel or Servo OFF of program JOG operation dialog box to turn OFF the servomotor power.
Pn530.0 = 2
(Waiting time Pn535 → Forward movement Pn531) × Number of movements Pn536
(Waiting time Pn535 → Reverse movement Pn531) × Number of movements Pn536
Number of movements Pn536 Number of movements Pn536
Speed
Diagram
Movement speed
Pn533
At zero speed
Pn531
Movement distance
Waiting time
Pn535
Accel/Decel time
Pn534
Waiting time
Pn535
Pn531
Movement distance
Accel/Decel time
Waiting time
Pn534
Pn535
Waiting time
Pn535
Pn531
Movement distance
Pn531
Movement distance
Servomotor
Run Status
(Stop) (Forward) (Stop) (Forward) (Stop)
Note: When Pn530.0 is set to 2, infinite time operation is disabled.
(Reverse) (Stop) (Reverse)
Pn530.0 = 3
(Waiting time Pn535 → Reverse movement Pn531) × Number of movements Pn536
(Waiting time Pn535 → Forward movement Pn531) × Number of movements Pn536
Number of movements Pn536 Number of movements Pn536
Movement speed
Pn533
6-10
Speed
Diagram
At zero speed
Waiting time
Pn535
Accel/Decel time
Pn534 Waiting time
Pn535
Pn531
Movement distance
Pn531
Movement distance
Waiting time
Pn535
Pn531
Movement distance
Accel/Decel time
Waiting time
Pn535
Pn533
Pn534
Movement speed
Pn531
Movement distance
Servomotor
Run Status
(Stop) (Reverse) (Stop) (Reverse) (Stop)
Note: When Pn530.0 is set to 3, infinite time operation is disabled.
(Forward) (Stop) (Forward)
Movement speed
Pn533
6.5 Program JOG Operation (Fn004)
Pn530.0 = 4
(Waiting time Pn535 → Forward movement Pn531 → Waiting time Pn535 → Reserve movement Pn531)
× Number of movements Pn536
Number of movements Pn536
Speed
Diagram
Pn531
Movement distance
Movement speed
Pn533
At zero speed
Waiting time
Pn535
Waiting time
Accel/Decel time
Pn534
Pn535
Pn531
Movement distance
Pn533
Movement speed
Servomotor
Run Status
(Stop) (Forward) (Stop) (Reverse) (Stop)
Note: When Pn536 (number of times of program JOG movement) is set to 0, infinite time operation is enabled. To stop infinite time operation, press the cancel or Servo OFF of program JOG operation dialog box to turn OFF the servomotor power.
Pn530.0 = 5
(Waiting time Pn535 → Reverse movement Pn531 → Waiting time Pn535 → Forward movement Pn531)
× Number of movements Pn536
Number of movements Pn536
Speed
Diagram
At zero speed
Waiting time
Pn535
Accel/Decel time
Pn534
Waiting time
Pn535
Pn531
Movement distance
Pn531
Movement distance
Movement speed
Pn533
Pn533
Movement speed
Servomotor
Run Status
(Stop) (Reverse) (Stop) (Forward) (Stop)
Note: When Pn536 (number of times of program JOG movement) is set to 0, infinite time operation is enabled. To stop infinite time operation, press the cancel or Servo OFF of program JOG operation dialog box to turn OFF the servomotor power.
6
6-11
6-12
6 Utility Functions (Fn )
(4) Related Parameters
The following parameters set the program JOG operation pattern. Do not change the settings while the program JOG operation is being executed.
Pn530
Program JOG Operation Related Switch Speed Position Torque
Setting Range
0000 to 0005
Setting Unit
−
Factory Setting
0000
When Enabled
Immediately
Pn531
Program JOG Movement Distance Speed Position Torque
Setting Range
1 to 1073741824
Setting Unit
1 reference unit
Factory Setting
32768
When Enabled
Immediately
Pn533
Pn534
Pn535
Pn536
Program JOG Movement Speed Speed Position Torque
Setting Range
1 to 10000
Setting Unit
1 min
-1
Factory Setting
500
When Enabled
Immediately
Program JOG Acceleration/Deceleration Time Speed Position Torque
Setting Range
2 to 10000
Setting Unit
1 ms
Factory Setting
100
When Enabled
Immediately
Program JOG Waiting Time Speed Position Torque
Setting Range
0 to 10000
Setting Unit
1 ms
Factory Setting
100
When Enabled
Immediately
Number of Times of Program JOG Movement Speed Position Torque
Setting Range
0 to 1000
Setting Unit
1 time
Factory Setting
1
When Enabled
Immediately
Classification
Setup
Classification
Setup
Classification
Setup
Classification
Setup
Classification
Setup
Classification
Setup
6.5 Program JOG Operation (Fn004)
(5) Operating Procedure
Use the following procedure to perform the program JOG operation after setting a program JOG operation pattern.
CAUTION
Two methods are available to interrupt a program JOG operation and stop the motor. The motor will stop according to the method selected. Make sure to select the best method for the situation.
• When using the Servo OFF button to turn off the power to the servomotor and stop the motor, the motor will coast to a stop.
• When using the Cancel button to cancel the program JOG operation and stop the motor, the motor will decelerate to a stop and then be put in a zero clamp state.
Note: With some models of SERVOPACKs, the Cancel button cannot be used to stop the motor.
1.
In the SigmaWin+ main window, click Test Run - Program JOG Operation .
A warning message about possible dangers will appear and ask if you want to continue.
MECHA
If these conditions are not acceptable and you do not want to continue, click Cancel to return to the main window without programming JOG operation.
6
6-13
6-14
6 Utility Functions (Fn )
2.
Click OK .
The Program JOG Operation box will appear.
MECHA
3.
For each running condition in the Program JOG Operation box, enter or select the same value that have been used for the Running Condition group, and then click Apply .
The running pattern for the condition will be shown as a graph.
4.
Click Run .
The contents of the Program JOG Operation box will change to the following display.
MECHA
6.5 Program JOG Operation (Fn004)
5.
Click Servo ON and then click Execute .
After the amount of time set in Pn535 has passed, the programmed JOG operation will start.
MECHA
6.
After the programmed JOG operation has been successfully completed, restart the
SERVOPACK.
6
6-15
6-16
6 Utility Functions (Fn )
6.6
Initializing Parameter Settings (Fn005)
This function is used when returning to the factory settings after changing parameter settings.
• Be sure to initialize the parameter settings while the servomotor power is OFF .
• After initialization, restart the SERVOPACK to validate the settings.
Note: Any value adjusted with Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.
(1) Preparation
The following conditions must be met to initialize the parameter values.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Parameters - Edit Parameters .
The Parameter Editing dialog box will appear.
ME-
CHA
2.
Click Initialize .
The Verification box will appear.
6.6 Initializing Parameter Settings (Fn005)
MECHA
A message will appear as a warning to say that changes to settings might not correspond with other settings and it will then ask if you want to continue.
If these conditions are not acceptable and you do not want to continue, click Cancel to return to the
Parameter Editing dialog box without initializing the parameter settings.
3.
Click OK .
The Initialize the Servopack settings box will appear and ask if you want to continue.
MECHA
If you do not want to continue, click Cancel to return to the Parameter Editing dialog box without initializing the parameter settings.
6
6-17
6-18
6 Utility Functions (Fn )
4.
Click Initialize to start initialization.
A progress indicator will show what percentage of the process has been completed.
MECHA
After the settings are successfully initialized, the following message will appear to prompt you to verify that all parameter settings are correct for the target machine.
MECHA
5.
Click OK .
6.
Restart the SERVOPACK.
6.7 Clearing Alarm History (Fn006)
6.7
Clearing Alarm History (Fn006)
The clear alarm history function deletes all of the alarm history recorded in the SERVOPACK.
Note: The alarm history is not deleted when the alarm reset is executed or the main circuit power supply of the SERVO-
PACK is turned OFF.
(1) Preparation
The follow conditions must be met to clear the alarm history.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Alarm - Display Alarm .
The Alarm Display box will appear.
MECHA
2.
Click the Alarm traceback tab.
MECHA
3.
Click Clear .
The alarm history will be cleared.
6
6-19
6-20
6 Utility Functions (Fn )
6.8
Offset Adjustment of Analog Monitor Output (Fn00C)
If connecting an analog monitor unit, the analog monitor signal output (factory setting: torque monitor or motor speed monitor) can be monitored. The offset is adjusted in the analog monitor unit at the factory. The user need not usually use this function. To adjust the offset manually, use this function.
(1) Adjustment Example
An example of offset adjustment to the motor speed monitor is shown below.
Analog monitor output voltage
Offset adjustment
Motor speed
Item
Offset Adjustment Range
Adjustment Unit
Specifications
-2.4 V to + 2.4 V
18.9 mV/LSB
Note:
• The adjustment value will not be initialized when parameter settings are initialized using Fn005.
• Make offset adjustment with a measuring instrument connected, so that the analog monitor output is zero. An example of settings for a zero analog monitor output is shown below.
• While the servomotor is not turned ON, set the monitor signal to the torque reference.
• In speed control, set the monitor signal to the position error.
(2) Preparation
The following condition must be met to adjust the offsets of the analog monitor output.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
6.8 Offset Adjustment of Analog Monitor Output (Fn00C)
(3) Operating Procedure
Use the following procedure.
1.
Connect the measurement instrument.
For details, refer to 5.1.3
(1) Connecting the Measurement Instrument .
2.
In the SigmaWin+ main window, click Setup - Adjust Offset - Adjust the Analog Monitor
Output . The Adjust the Analog Monitor Output box will appear. Click Zero Adjustment tab.
MECHA
In the Channel box, either CH1 or CH2 can be selected.
3.
To adjust the offset, click +1 (increase) or -1 (decrease) button while viewing the analog monitor to check the output level. Keep the output as close to zero as possible.
6
6-21
6-22
6 Utility Functions (Fn )
6.9
Gain Adjustment of Analog Monitor Output (Fn00D)
If connecting an analog monitor unit, the analog monitor signal output (factory setting: torque monitor or motor speed monitor) can be monitored. The gain is adjusted in the analog monitor unit at the factory. The user need not usually use this function. To adjust the gain manually, use this function.
(1) Adjustment Example
An example of gain adjustment to the motor rotating speed monitor is shown below.
Analog monitor output voltage
1 [V]
Gain adjustment
1000 [min
-1
]
Motor speed
Item
Gain-adjustment Range
Adjustment Unit
Specifications
100 ± 50%
0.4%/LSB
The gain adjustment range is made with a 100% output set as a center value (adjustment range: 50% to 150%).
The following is a setting example.
<Setting the Set Value to − 125>
100% + ( − 125 × 0.4) = 50%
Therefore, the monitor output voltage is 0.5 time as high.
<Setting the Set Value to 125>
100% + (125 × 0.4) =150%
Therefore, the monitor output voltage is 1.5 times as high.
Note: The adjustment value will not be initialized when parameter settings are initialized using Fn005.
(2) Preparation
The following condition must be met to adjust the gain of the analog monitor output.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
6.9 Gain Adjustment of Analog Monitor Output (Fn00D)
(3) Operating Procedure
Use the following procedure to perform the gain adjustment of analog monitor output.
1.
In the SigmaWin+ main window, click Setup - Adjust Offset - Adjust the Analog Monitor
Output . The Adjust the Analog Monitor Output box will appear. Click the Gain Adjustment tab.
MECHA
In the Channel box, either CH1 or CH2 can be selected.
2.
To change the value of the gain adjustment, click +1 (increase) or -1 (decrease) button.
6
6-23
6-24
6 Utility Functions (Fn )
6.10
Automatic Offset-Signal Adjustment of the Motor Current
Detection Signal (Fn00E)
Perform this adjustment only if highly accurate adjustment is required for reducing torque ripple caused by current offset. The user need not usually use this function.
• Be sure to perform this function while the servomotor power is OFF.
• Execute the automatic offset adjustment if the torque ripple is too big when compared with those of other SERVOPACKs.
Note: The adjusted value is not initialized by executing the Fn005 function (Initializing Parameter Settings).
(1) Preparation
The following conditions must be met to automatically adjust the offset of the motor current detection signal.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The SERVOPACK must be in Servo Ready status (Refer to 4.8.4
).
• The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Setup - Adjust Offset - Adjust the Motor Current
Detection Offset .
The following message will appear and ask if you want to continue. The message informs you that the offset is set to the factory settings and that the SERVOPACK's performance might be affected if these settings are changed.
MECHA
6.10 Automatic Offset-Signal Adjustment of the Motor Current Detection Signal (Fn00E)
2.
Click Continue to adjust the motor detection offset. The Adjust the Motor Current Detection
Offset box will appear. Click the Automatic Adjustment tab.
The settings for Automatic Adjustment will appear.
MECHA
3.
Click Adjust .
The offset value automatically adjusted will be shown in the New box.
MECHA
6
6-25
6-26
6 Utility Functions (Fn )
6.11
Manual Offset-Signal Adjustment of the Motor Current
Detection Signal (Fn00F)
Use this function only if the torque ripple is still high after the automatic offset-signal adjustment of the motor current detection signal (Fn00E).
If offset is adjusted incorrectly and then executed using this function, characteristics of the servomotor performance could be affected.
Observe the following precautions when performing manual servo tuning.
• Run the servomotor at a speed of approximately 100 min
-1
.
• Adjust the offset while monitoring the torque reference with the analog monitor until the ripple of torque reference monitor's waveform is minimized.
• Adjust the phase-U and phase-V offset amounts alternately several times until these offsets are well balanced.
Note: The adjusted value is not initialized by executing the Fn005 function (Initializing Parameter Settings).
(1) Preparation
The following condition must be met to manually adjust the offset of the motor current detection signal.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
(2) Operating Procedure
Use the following procedure.
1.
Turn the motor at 100 min -1 .
2.
In the SigmaWin+ main window, click Setup - Adjust Offset - Adjust the Motor Current
Detection Offset .
The following message will appear and ask if you want to continue. The message informs you that the offset is set to the factory settings and that the SERVOPACK's performance might be affected if these settings are changed.
MECHA
6.11 Manual Offset-Signal Adjustment of the Motor Current Detection Signal (Fn00F)
3.
Click Continue . Adjust the Motor Current Detection Offset box will appear. Click the Manual
Adjustment tab.
The settings for Manual Adjustment will appear.
MECHA
4.
Select U-phase in the Channel box.
5.
To adjust the offset of the phase U, click the +1 button to increase the set value and click the -1 button to decrease.
Increase or decrease the offset by increments of 10 to minimize torque ripple. The offset can be any value between -512 and +511.
6.
Select V-phase in the Channel box.
7.
To adjust the offset of the phase V, click the +1 button to increase the set value and click the -1 button to decrease.
Increase or decrease the offset by increments of 10 to minimize torque ripple.
8.
Repeat steps 4 to 7 alternating between the U and V phases until the torque ripple cannot be reduced any further.
9.
Then adjust the offsets further by repeating steps 4 to 7 but using a unit smaller than 10.
6
6-27
6-28
6 Utility Functions (Fn )
6.12
Write Prohibited Setting (Fn010)
This function prevents changing parameters by mistake and sets restrictions on the execution of the utility function.
Parameter changes and execution of the utility function become restricted in the following manner when Write prohibited (P.0001) is assigned to the write prohibited setting parameter (Fn010).
• Parameters: Parameters can be changed from the SigmaWin+.
• Utility Function: Some functions cannot be executed. (Refer to the following table.) If you attempt to execute these utility functions a warning dialog box will appear.
Fn202
Fn203
Fn204
Fn205
Fn206
Fn207
Parameter
No.
Fn000
Fn002
Fn003
Fn004
Fn005
Fn006
Fn008
Fn00C
Fn00D
Fn00E
Fn00F
Fn010
Fn011
Fn012
Fn013
Fn01B
Fn01E
Fn030
Fn200
Fn201
Function
Alarm history display
JOG operation
Origin search
Program JOG operation
Initializing parameter settings
Clearing alarm history
Absolute encoder multiturn reset and encoder alarm reset
Offset adjustment of analog monitor output
Gain adjustment of analog monitor output
Automatic offset-signal adjustment of the motor current detection signal
Manual offset-signal adjustment of the motor current detection signal
Write prohibited setting
Servomotor model display
Software version display
Multiturn limit value setting change when a multiturn limit disagreement alarm occurs
Vibration detection level initialization
Display of SERVOPACK and servomotor ID
Software reset
Tuning-less levels setting
Advanced autotuning
Advanced autotuning by reference
One-parameter tuning
Anti-resonance control adjustment function
Vibration suppression function
EasyFFT
Online vibration monitor
Write Prohibited
Setting
Executable
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
–
Executable
Executable
Cannot be executed
Cannot be executed
Executable
Executable
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Cannot be executed
Reference
Section
6.2
6.3
6.4
6.5
6.6
6.7
4.7.4
6.8
6.9
6.10
6.11
6.12
6.13
6.14
4.7.6
6.15
6.16
6.17
5.2.2
5.3.2
5.4.2
5.5.2
5.6.2
5.7.2
6.18
6.19
6.12 Write Prohibited Setting (Fn010)
(1) Preparation
There are no tasks that must be performed before the execution.
(2) Operating Procedure
Follow the steps to set enable or disable writing.
Setting values are as follows:
• " P.0000
" : Write permitted (Releases write prohibited mode.) [Factory setting]
• " P.0001
" : Write prohibited (Parameters become write prohibited from the next power ON.)
1.
In the SigmaWin+ main window, click Setup - Write Prohibited Setting .
The Write Prohibited Setting box will appear.
MECHA
Set the parameter to enable or prohibit writing. Click the setting arrows to increase or decrease the number on the far right.
Writing enabled (factory setting): 0000
Writing prohibited: 0001
2.
Click Setting .
The following message appears and informs you that the write prohibited setting has been changed and the new setting will become valid the next time the SERVOPACK is restarted.
MECHA
3.
Click OK .
The new setting will be saved in the SERVOPACK.
4.
To enable the change in the setting, restart the SERVOPACK.
6
6-29
6-30
6 Utility Functions (Fn )
6.13
Servomotor Model Display (Fn011)
This function is used to check the servomotor model, encoder type, and encoder resolution. If the SERVO-
PACK has been custom-made, you can also check the specification codes of SERVOPACKs.
(1) Preparation
There are no tasks that must be performed before the execution.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Product Information .
The Product Informatio n box will appear.
MECHA
2.
Click OK .
The SigmaWin+ main window will appear.
6.14 Software Version Display (Fn012)
6.14
Software Version Display (Fn012)
Select Fn012 to check the SERVOPACK and encoder software version numbers.
(1) Preparation
There are no tasks that must be performed before the execution.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Product Information .
The Product Informatio n box will appear.
MECHA
2.
Click OK .
The SigmaWin+ main window will appear.
6
6-31
6-32
6 Utility Functions (Fn )
6.15
Vibration Detection Level Initialization (Fn01B)
This function detects vibration when servomotor is connected to a machine in operation and automatically adjusts the vibration detection level (Pn312) to output more exactly the vibration alarm (A.520) and the vibration warning (A.911).
The vibration detection function detects vibration elements according to the motor speed.
Parameter n.
0
[Factory setting]
Meaning
Does not detect vibration.
When Enabled Classification
Pn310 n.
1
Outputs the warning (A.911) when vibration is detected.
Outputs the alarm (A.520) when vibration is detected.
Immediately Setup n.
2
If the vibration exceeds the detection level calculated by the following formula, the alarm or warning will be output according to the setting of vibration detection switch (Pn310).
Vibration detection level (Pn312 [min
Detection level = ޓ
-1
])
100
×
Vibration detection sensitivity (Pn311 [%])
• Use this function if the vibration alarm (A.520) or the vibration warning (A.911) is not output correctly when a vibration at the factory setting of the vibration detection level (Pn312) is detected. In other cases, it is not necessary to use this function.
• The vibration alarm or warning detection sensibility differs depending on the machine conditions. In this case, fine-tune the setting of the vibration detection sensitivity (Pn311) using the above detection level formula as a guide.
Pn311
Vibration Detection Sensitivity Speed Position Torque
Setting Range
50 to 500
Setting Unit
1%
Factory Setting
100
When Enabled
Immediately
Classification
Tuning
• The vibration may not be detected because of improper servo gains. Also, not all kinds of vibrations can be detected. Use the detection result as a guideline.
• Set a proper moment of inertia ratio (Pn103). Improper setting may result in the vibration alarm, warning misdetection, or non-detection.
• The references that are used to operate your system must be input to execute this function.
• Execute this function under the operating condition for which the vibration detection level should be set.
• Execute this function while the motor speed reaches at least 10% of its maximum.
(1) Preparation
The following conditions must be met to initialize the vibration detection level.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The test without a motor function must be disabled (Pn00C.0 = 0).
6.15 Vibration Detection Level Initialization (Fn01B)
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Setup - Initialize Vibration Detection Level .
The Initialize Vibration Detection Level box will appear.
MECHA
2.
Select a percentage for Pn311: Vibration Detection Sensibility and one condition in Pn310:
Vibration Detection Switch , and then click Detection Start .
The name of the button will change from Detection Start to Execute to indicate that detection is ready to be executed.
MECHA
6
6-33
6 Utility Functions (Fn )
3.
Click Execute .
The new settings for the vibration detection level will be shown in the boxes in lower section of the box.
The new settings will be saved in the SERVOPACK.
MECHA
6-34
(3) Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn311
Pn312
Name
Vibration Detection Sensitivity
Vibration Detection Level
Mid-execution changes
Yes
No
Automatic changes
No
Yes
6.16 Display of SERVOPACK and Servomotor ID (Fn01E)
6.16
Display of SERVOPACK and Servomotor ID (Fn01E)
This function displays ID information for SERVOPACK, servomotor and encoder connected to the SERVO-
PACK.
The SigmaWin+ is required to perform this function.
The following items can be displayed.
ID
SERVOPACK ID
Servomotor ID
Encoder ID
Items to be Displayed
• SERVOPACK model
• SERVOPACK serial number
• SERVOPACK manufacturing date
• Servomotor model
• Servomotor serial number
• Servomotor manufacturing date
• Encoder model
• Encoder serial number
• Encoder manufacturing date
• Encoder type/resolution
(1) Preparation
There are no tasks that must be performed before the execution.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Product Information .
The Product Informatio n box will appear.
MECHA
Click these buttons to view the serial number and date of manufacture for each device used.
2.
Click OK .
The SigmaWin+ main window will appear.
6
6-35
6-36
6 Utility Functions (Fn )
6.17
Software Reset (Fn030)
This function enables resetting the SERVOPACK internally from software. This function is used when resetting alarms and changing the settings of parameters that normally require restarting the SERVOPACK. This function can be used to change those parameters without restarting the SERVOPACK.
There are the following two types of software resets for SigmaWin+ connection status.
• Resetting for a conventional connection
• Resetting for a connection through a controller
• Start software reset operation after the servomotor power is OFF.
• This function resets the SERVOPACK independently of host controller. The SERVO-
PACK carries out the same processing as when the power supply is turned ON and outputs the ALM signal. The status of other output signals may be forcibly changed.
• The SERVOPACK will not respond for 5 seconds after the reset begins.
Always check the status of the SERVOPACK and motor before you execute a reset.
(1) Preparation
The following condition must be met to perform a software reset.
• The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
Conventional connection
1.
In the SigmaWin+ main window, click Setup - Software Reset .
The following message will appear and remind you to check the status of the SERVOPACK and the motor for safety reasons because the SERVOPACK will stop responding for about 5 seconds after the software reset has been executed.
Note: If the moment of inertia is calculated as described in 5.3 Advanced Autotuning (Fn201) , the Software Reset box shown in step 2 will appear.
MECHA
If you do not want to continue, click Cancel . The SigmaWin+ main window will appear.
2.
Click Execute .
The Software Reset box will appear.
6.17 Software Reset (Fn030)
MECHA
3.
Click Execute .
After resetting of software has been completed, the following message will appear.
MECHA
4.
Click OK to close the Software Reset box.
All settings including parameters have been re-calculated. Disconnect the SigmaWin+ from the SERVO-
PACK, and then reconnect to validate the new settings.
6
6-37
6 Utility Functions (Fn )
Connection through a controller
1.
In the SigmaWin+ main window, click Setup - Software Reset .
The Software Reset box will appear.
Note: If the moment of inertia is calculated as described in 5.3 Advanced Autotuning (Fn201) , the Software Reset box shown in step 2 will appear.
MECHA
If you do not want to continue, click Cancel . The SigmaWin+ main window will appear.
2.
Click Execute .
The Software Reset box will appear.
MECHA
6-38
3.
Select the Reset MECHATROLINK communication .
4.
Click Execute .
If Software Reset is executed without resetting MECHATROLINK communications, communications between the controller and the SERVOPACK will be disabled and an error will be issued. Make sure to check the box for Reset MECHATROLINK communication to reset the MECHATROLINK communications.
6.17 Software Reset (Fn030)
5.
After the software reset has been completed, the following message will appear.
The message will tell you to reconnect SigmaWin+ to the SERVOPACK after the reset has been completed.
MECHA
6.
Click OK to close the Software Reset box.
All settings including parameters have been re-calculated. Disconnect SigmaWin+ from the SERVO-
PACK, and then reconnect to validate the new settings.
6
6-39
6 Utility Functions (Fn )
• When resetting only MECHATROLINK communications
MECHATROLINK communications can be reset separately.
Communication between the controller and the SERVOPACK can be restored by clearing the error that occurred during communications between them.
1.
In the SigmaWin+ main window, click Setup - MECHATROLINK Communications Reset .
The MECHATROLINK Communications Reset box will appear.
MECHA
2.
Click Reset .
A message will appear and inform you that the parameter settings to be saved in the controller will be cleared if the controller is restarted. You must use MPE720 to save the settings in the controller if you want to keep the settings. A list of parameters whose settings are to be saved is also shown.
MECHA
6-40
3.
Click Yes .
The parameters that are set to be automatically saved will be reflected in the settings of parameters in the controller in the OW register.
At the same time, the MECHATROLINK communications will be reset and the MECHATROLINK
Communications Reset box will close.
6.18 EasyFFT (Fn206)
6.18
EasyFFT (Fn206)
EasyFFT sends a frequency waveform reference from the SERVOPACK to the servomotor and slightly rotates the servomotor several times over a certain period, thus causing machine vibration. The SERVOPACK detects the resonance frequency from the generated vibration and makes notch filter settings according to the resonance frequency detection. The notch filter is effective for the elimination of high-frequency vibration and noise.
Execute this function after the servomotor power is turned OFF if operation of the SERVOPACK results in high-frequency noise and vibration.
WARNING
• The servomotor automatically will move less than a quarter of a turn several times in the specified direction when EasyFFT is executed. Do not touch the servomotor or machine during execution of EasyFFT, otherwise injury may result.
CAUTION
• Use the EasyFFT when the servo gain is low, such as in the initial stage of servo adjustment. If EasyFFT is executed after increasing the gain, the servo system may vibrate depending on the machine characteristics or gain balance.
Periodic waveform reference
Response
Rotates the shaft slightly
M-III
Slight movement
SERVOPACK
In addition to this function, online vibration monitor (Fn207) can be used to detect machine vibration and automatically make notch filter settings.
If a DC Power Input Σ -V Series SERVOPACK is used to make adjustments, it is recommended to use advanced autotuning. This built-in EasyFFT function is used to maintain interchangeability with previous models. There is normally no need to use it.
(1) Preparation
The following conditions must be met to perform EasyFFT.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The main circuit power supply must be ON.
• All alarms must be cleared.
• The servomotor power must be OFF.
• There must be no overtravel.
• The test without a motor function must be disabled (Pn00C.0 = 0).
• An external reference must not be input.
6
6-41
6-42
6 Utility Functions (Fn )
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Setup - EasyFFT .
A warning message will appear and remind you of possible dangers.
MECHA
If you do not want to continue, click Cancel . The SigmaWin+ main window will appear.
2.
Click OK .
The EasyFFT box will appear.
MECHA
3.
Click Servo ON .
6.18 EasyFFT (Fn206)
MECHA
4.
Select the percentage in the Instruction amplitude box and the rotational direction in the
Rotation direction . Click Start .
The motor will begin to rotate, and the frequency will be measured. After the frequency has been measured, the results will be shown in the lower area of the box.
MECHA
6
6-43
6 Utility Functions (Fn )
5.
Click Measurement complete .
MECHA
6-44
6.
If setting the parameters to the values shown in the measurement results, click Result Writing .
(3) Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn408
Pn409
Pn40A
Pn40C
Pn40D
Pn456
Name
Torque Related Function Switch
1st Notch Filter Frequency
1st Notch Filter Q Value
2nd Notch Filter Frequency
2nd Notch Filter Q Value
Sweep Torque Reference Amplitude
Mid-execution changes
Yes
No
No
No
No
No
Automatic changes
Yes
Yes
No
Yes
No
No
6.19 Online Vibration Monitor (Fn207)
6.19
Online Vibration Monitor (Fn207)
If vibration is generated during operation and this function is executed while the servomotor power is still ON, the machine vibration can sometimes be suppressed by setting a notch filter or torque reference filter for the vibration frequencies.
When online, vibration frequency caused by machine resonance will be detected and the frequency that has the highest peak will be displayed on the panel operator. The effective torque reference filter or notch filter frequency for the vibration frequencies will be automatically selected and the related parameters will be automatically set.
In addition to this function, EasyFFT (Fn206) can be used to detect machine vibration and automatically make notch filter settings. Use the following flowchart to determine how these functions should be used.
If a DC Power Input Σ -V Series SERVOPACK is used to make adjustments, it is recommended that you use advanced autotuning. This built-in function is used to maintain interchangeability with previous models.
There is normally no need to use it.
How to use EasyFFT (Fn206) and online vibration monitor (Fn207), when they are mainly used for servo gain adjustment.
Start
Vibration with high-frequency noise
during operation
Yes
Turn OFF the servomotor power, and execute EasyFFT (Fn206)
No
Adjust servo gain
No
Vibration
Yes
With the servomotor power ON, execute online vibration monitor (Fn207)
End
(1) Preparation
The following conditions must be met to perform online vibration monitoring.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be ON.
• There must be no overtravel.
• The correct moment of inertia (Pn103) must be set.
• The test without a motor function must be disabled (Pn00C.0 = 0).
6
6-45
6-46
6 Utility Functions (Fn )
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Online Vibration Monitor .
A message will appear as a warning to say that any changes to parameter settings might greatly affect the operation of the motor, and then ask if you want to continue.
MECHA
2.
Click OK .
The Online Vibration Monitor box will appear.
MECHA
6.19 Online Vibration Monitor (Fn207)
3.
Click Execute to activate the vibration sensor.
The vibrations are detected, and the peak frequencies of the vibrations will be shown in the Detection result table.
MECHA
4.
Click Auto Setting .
The pre-adjustment parameter settings will be shown in the Previous column in the Write result table.
MECHA
6
6-47
6-48
6 Utility Functions (Fn )
5.
Click Write result .
The parameter values those are most effective for the measured frequencies will be shown in the Current column in the Write result table, and then saved in the SERVOPACK.
MECHA
If you do not want to save the new parameter settings in the SERVOPACK, click Reset .
6.19 Online Vibration Monitor (Fn207)
(3) Related Parameters
The following table lists parameters related to this function and their possibility of being changed while executing this function or of being changed automatically after executing this function.
• Parameters related to this function
These are parameters that are used or referenced when executing this function.
• Allowed changes during execution of this function
Yes : Parameters can be changed using SigmaWin+ while this function is being executed.
No : Parameters cannot be changed using SigmaWin+ while this function is being executed.
• Automatic changes after execution of this function
Yes : Parameter set values are automatically set or adjusted after execution of this function.
No : Parameter set values are not automatically set or adjusted after execution of this function.
Parameter
Pn401
Pn408
Pn409
Pn40A
Pn40C
Pn40D
Name
Torque Reference Filter Time Constant
Torque Related Function Switch
1st Notch Filter Frequency
1st Notch Filter Q Value
2nd Notch Filter Frequency
2nd Notch Filter Q Value
Mid-execution changes
No
Yes
No
No
No
No
Automatic changes
Yes
Yes
Yes
No
No
No
6
6-49
7
Monitor Displays (Un
)
7.1 List of Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.2 Viewing Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2.1 System Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.2.2 Status Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
7.2.3 Motion Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
7.2.4 Input Signal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
7.2.5 Output Signal Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
7
7-1
7-2
7 Monitor Displays (Un )
7.1
List of Monitor Displays
The monitor displays can be used for monitoring the I/O signal status, and SERVOPACK internal status.
Refer to the following table.
Un004
Un005
Un006
Un007
Un008
Un00C
Un00D
Un012
Un013
Un014
Un020
Un021
Un030
Un031
Parameter
No.
Un000
Un001
Un002
Un003
Un009
Description
Motor rotating speed
Speed reference
Internal torque reference (in percentage to the rated torque)
Rotational angle 1 (encoder pulses from the phase-C origin: decimal display)
Rotational angle 2 (from polarity origin (electric angle))
Input signal monitor
Output signal monitor
Input reference pulse speed (valid only in position control) min
-1 min
%
-1 encoder pulse deg
−
− min
-1 reference unit
∗
Position error amount (valid only in position control)
Accumulated load ratio (in percentage to the rated torque: effective torque in cycle of 10 seconds)
%
Input reference pulse counter reference unit
Feedback pulse counter
Total operation time encoder pulse
∗
100 ms
Feedback pulse counter reference unit
Effective gain monitor (gain settings 1 = 1, gain settings 2 = 2) −
Motor rated speed min
-1
Motor maximum speed min
-1
The current backlash compensation value
Backlash compensation setting limit value
0.1 reference unit
0.1 reference unit
Unit
∗ For details, refer to 4.4.3 Electronic Gear .
7.2 Viewing Monitor Displays
7.2
Viewing Monitor Displays
Five types of SigmaWin+ monitor windows can be used.
• System Monitor
• Status Monitor
• Motion Monitor
• Input Signal Monitor
• Output Signal Monitor
The following sections describes how to open each monitor window.
7.2.1
System Monitor
To open the System Monitor box, in the SigmaWin+ main window, click Monitor - Monitor - System Monitor .
Shows current status of SERVOPACK
Shows current status of SERVOPACK signal
MECHA
Opens the System Monitor window when the
SigmaWin+ starts.
Starts main functions of SigmaWin+ directly from the System Monitor window.
7
7-3
7-4
7 Monitor Displays (Un )
7.2.2 Status Monitor
7.2.2
Status Monitor
To open the Status Monitor box, use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Monitor - Status Monitor .
The Status Monitor box will appear.
ME
CH
A
The items which can be monitored are listed.
2.
Select the items to be monitored.
The current status of the selected item is shown in the Value column.
ME
CH
A
7.2 Viewing Monitor Displays
7.2.3
Motion Monitor
To open the Motion Monitor box, use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Monitor - Motion Monitor .
The Motion Monitor box will appear.
ME
CH
A
The items which can be monitored are listed.
2.
Select the items to be monitored.
The current status of the selected item is shown in the Value column.
ME
CH
A
7
7-5
7 Monitor Displays (Un )
7.2.4 Input Signal Monitor
7.2.4
Input Signal Monitor
To open the Input Signal Monitor box, use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Monitor - Input Signal Monitor .
The Input Signal Monitor box will appear.
MECHA
The items which can be monitored are listed.
2.
Select the items to be monitored.
The current status of the selected item is shown in the Value column.
MECHA
7-6
Hi indicates that the input signal is off and Lo indicates that the input signal is on. When no input signal is allocated, Lo will be shown in the column.
7.2 Viewing Monitor Displays
7.2.5
Output Signal Monitor
To open the Output Signal Monitor box, use the following procedure.
1.
In the SigmaWin+ main window, click Monitor - Monitor - Output Signal Monitor .
The Output Signal Monitor box will appear.
MECHA
The items which can be monitored are listed.
2.
Select the items to be monitored.
The current status of the selected item is shown in the Value column.
MECHA
Hi indicates that the input signal is off and Lo indicates that the input signal is on. When no output signal is allocated, Lo will be shown in the column.
7
7-7
8
Troubleshooting
8.1 Alarm Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.1.1 List of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.1.2 Troubleshooting of Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
8.2 Warning Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
8.2.1 List of Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-17
8.2.2 Troubleshooting of Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-19
8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-23
8.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-24
8
8-1
8-2
8 Troubleshooting
8.1.1 List of Alarms
8.1
Alarm Displays
The following sections describe troubleshooting in response to alarm displays.
The alarm name, alarm meaning, alarm stopping method, and alarm reset capability are listed in order of the alarm numbers in 8.1.1 List of Alarms .
The causes of alarms and troubleshooting methods are provided in 8.1.2 Troubleshooting of Alarms .
8.1.1
List of Alarms
This section provides list of alarms.
Servomotor Stopping Method
If an alarm occurs, the servomotor can be stopped by doing either of the following operations.
Gr.1: The servomotor coasts to a stop when an alarm occurs.
Gr.2: The servomotor is stopped according to the setting in Pn00B.1 if an alarm occurs. Pn00B.1 is factory-set to stop the servomotor by setting the speed reference to " 0.
" The servomotor under torque control will always use the Gr.1 method to stop. By setting Pn00B.1 to 1, the servomotor stops using the same method as Gr.1. When coordinating a number of servomotors, use this stopping method to prevent machine damage that may result due to differences in the stop method.
Alarm Reset
Available: Removing the cause of alarm and then executing the alarm reset can clear the alarm.
N/A: Executing the alarm reset cannot clear the alarm.
Alarm
Number
A.020
A.021
A.022
A.030
A.040
A.042
A.04A
A.050
A.051
A.0b0
A.100
A.400
A.450
A.510
A.520
Alarm Name Meaning
Parameter Checksum Error 1
Parameter Format Error 1
System Checksum Error 1
Main Circuit Detector Error
Parameter Setting Error 1
Parameter Combination Error
Parameter Setting Error 2
Combination Error
Unsupported Device Alarm
Cancelled Servo ON
Command Alarm
Overcurrent or Heat Sink
Overheated
Overvoltage
Main-Circuit
Capacitor Overvoltage
Overspeed
Vibration Alarm
The data of the parameter in the SERVOPACK is incorrect.
The data of the parameter in the SERVOPACK is incorrect.
The data of the parameter in the SERVOPACK is incorrect.
Detection data for main circuit is incorrect.
The parameter setting is outside the setting range.
Combination of some parameters exceeds the setting range.
Bank member/bank data setting is incorrect.
The SERVOPACK and the servomotor capacities do not match each other.
The device unsupported was connected.
The servo ON command (SV_ON) was sent from the host controller after executing a utility function that turns ON servomotor.
An overcurrent flowed through the IGBT or the heat sink of the SERVOPACK was overheated.
Main circuit DC voltage is excessively high.
The capacitor of the main circuit has deteriorated or is faulty.
The servomotor speed is above the maximum rotational speed.
Incorrect vibration at the motor speed was detected.
Servomotor
Stopping
Method
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Alarm
Reset
N/A
N/A
N/A
Available
N/A
N/A
N/A
Available
N/A
Available
N/A
Available
N/A
Available
Available
8.1 Alarm Displays
Alarm
Number
A.521
A.710
A.720
A.7A0
A.810
A.820
A.830
A.840
A.850
A.860
A.b31
A.b32
A.b33
A.b6A
A.b6b
A.bE0
A.bF0
A.bF1
A.bF2
A.bF3
A.bF4
A.C10
A.C80
A.C90
A.C91
(cont’d)
Alarm Name Meaning
Autotuning Alarm
Overload: High Load
Overload: Low Load
Heat Sink Overheated
Encoder Backup Error
Encoder Checksum Error
Absolute Encoder Battery
Error
Encoder Data Error
Encoder Overspeed
Encoder Overheated
Current Detection Error 1
Current Detection Error 2
Vibration was detected while performing tuning-less function.
The servomotor was operating for several seconds to several tens of seconds under a torque largely exceeding ratings.
The servomotor was operating continuously under a torque exceeding ratings.
The heat sink of the SERVOPACK exceeded
90 ° C.
The power supplies to the encoder all failed and position data was lost.
The checksum results of encoder memory is incorrect.
The battery voltage was lower than the specified value after the control power supply was turned
ON.
Data in the encoder is incorrect.
The encoder was rotating at high speed when the power was turned ON.
The internal temperature of encoder is too high.
The current detection circuit for phase U is faulty.
The current detection circuit for phase V is faulty.
The detection circuit for the current is faulty.
Current Detection Error 3
MECHATROLINK
Communications
ASIC Error 1
MECHATROLINK
Communications
ASIC Error 2
ASIC error occurred in the MECHATROLINK communications.
ASIC error occurred in the MECHATROLINK communications.
Firmware Error
System Alarm 0
System Alarm 1
System Alarm 2
System Alarm 3
System Alarm 4
An internal program error occurred in the SER-
VOPACK.
"Internal program error 0" of the SERVOPACK occurred.
"Internal program error 1" of the SERVOPACK occurred.
"Internal program error 2" of the SERVOPACK occurred.
"Internal program error 3" of the SERVOPACK occurred.
"Internal program error 4" of the SERVOPACK occurred.
The servomotor ran out of control.
Servo Overrun Detected
Absolute Encoder Clear Error and Multiturn Limit Setting
Error
Encoder Communications
Error
Encoder Communications
Position Data Error
The multiturn for the absolute encoder was not properly cleared or set.
Communications between the SERVOPACK and the encoder is not possible.
An encoder position data calculation error occurred.
Servomotor
Stopping
Method
Gr.1
Gr.2
Gr.1
Gr.2
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.2
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Alarm
Reset
Available
Available
Available
Available
N/A
N/A
Available
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Available
N/A
N/A
N/A
8
8-3
8-4
8 Troubleshooting
8.1.1 List of Alarms
(cont’d)
Alarm
Number
A.C92
A.CA0
A.Cb0
A.CC0
A.d00
A.d01
A.d02
A.E02
A.E40
A.E41
A.E42
A.E50
A.E51
A.E60
A.E61
A.E62
A.E63
A.EA2
A.Ed1
Alarm Name Meaning
Encoder Communications
Timer Error
Encoder Parameter Error
Encoder Echoback Error
Multiturn Limit Disagreement
Position Error Overflow
Position Error Overflow Alarm at Servo ON
Position Error Overflow Alarm by Speed Limit at Servo ON
An error occurs in the communications timer between the encoder and the SERVOPACK.
Encoder parameters are faulty.
Contents of communications with encoder are incorrect.
Different multiturn limits have been set in the encoder and the SERVOPACK.
Position error exceeded the value of excessive position error alarm level (Pn520) when the servomotor power is ON.
This alarm occurs if the servomotor power is turned ON when the position error is greater than the set value of Pn526 while the servomotor power is OFF.
When the position errors remain in the error counter, Pn529 limits the speed if the servomotor power is turned ON. If Pn529 limits the speed in such a state, this alarm occurs when position references are input and the number of position errors exceeds the value set for the excessive position error alarm level (Pn520).
Synchronization error during MECHA-
TROLINK communications with the SERVO-
PACK.
MECHATROLINK
Internal Synchronization Error
1
MECHATROLINK
Transmission Cycle Setting
Error
MECHATROLINK
Communications Data Size
Setting Error
MECHATROLINK Station
Address Setting Error
MECHATROLINK
Synchronization Error
MECHATROLINK
Synchronization Failed
MECHATROLINK
Communications Error
(Reception error)
MECHATROLINK
Transmission Cycle Error
(Synchronization interval error)
MECHATROLINK
Communications Error
(FCS error)
MECHATROLINK
Synchronization Frame Not
Received Alarm
DRV Alarm 2 (SERVOPACK
WDC error)
The setting of the MECHATROLINK transmission cycle is out of the allowable range.
The setting of the MECHATROLINK communications data size is incorrect.
The setting of the MECHATROLINK station address is incorrect.
A synchronization error occurs during MECHA-
TROLINK communications.
A synchronization failure occurs in MECHA-
TROLINK communications.
A communications error occurs continuously during MECHATROLINK communications.
The transmission cycle fluctuates during
MECHATROLINK communications.
Communications error occurs continuously during MECHATROLINK communications.
Synchronization frames are not received continuously during MECHATROLINK communications.
A SERVOPACK DRV alarm 0 occurs.
Command Execution Timeout
A timeout error occurred when using a
MECHATROLINK command.
Servomotor
Stopping
Method
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.1
Gr.2
Gr.1
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Gr.2
Alarm
Reset
N/A
N/A
N/A
N/A
Available
Available
Available
Available
Available
Available
N/A
Available
Available
Available
Available
Available
Available
Available
Available
8.1 Alarm Displays
Alarm
Number
Alarm Name
A.F50
A.
− −
Servomotor Main Circuit
Cable Disconnection
Not an error
Meaning
The servomotor did not operate or power was not supplied to the servomotor even though the
SV_ON (Servo ON) command was input when the servomotor was ready to receive it.
Normal operation status
(cont’d)
Servomotor
Stopping
Method
Alarm
Reset
Gr.1
−
Available
−
8
8-5
8-6
8 Troubleshooting
8.1.2 Troubleshooting of Alarms
8.1.2
Troubleshooting of Alarms
If an error occurs in the servo drive, the ALM signal will be output. The alarm that occurs can be checked on the Alarm Display dialog box of the SigmaWin+.
Refer to the following table to identify the cause of an alarm and the action to be taken.
Contact your Yaskawa representative if the problem cannot be solved by the described corrective action.
Alarm Number:
Alarm Name
(Alarm Description)
A.030:
Main Circuit Detector
Error
Cause
A.020:
Parameter Checksum
Error 1
(The parameter data in the SERVOPACK is incorrect.)
A.021:
Parameter Format
Error 1
(The parameter data in the SERVOPACK is incorrect.)
A.022:
System Checksum
Error 1
(The parameter data in the SERVOPACK is incorrect.)
The power supply voltage suddenly dropped.
Measure the power supply voltage.
Set the power supply voltage within the specified range, and set Fn005 to initialize the parameter.
The power supply went OFF while changing a parameter setting.
Check the circumstances when the power supply went OFF.
Set Fn005 to initialize the parameter and then set the parameter again.
The number of times that parameters were written exceeded the limit.
Check to see if the parameters were frequently changed through the host controller.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Reconsider the method of writing parameters.
Malfunction caused by noise from the AC power supply or grounding line, static electricity noise, etc.
Gas, water drops, or cutting oil entered the SERVOPACK and caused failure of the internal components.
Restart the SERVOPACK several times. If the alarm still occurs, there may be noise interference.
Check the installation conditions.
Take countermeasures against noise.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A SERVOPACK fault occurred.
The software version of SERVO-
PACK that caused the alarm is older than that of the written parameter.
A SERVOPACK fault occurred.
The power supply voltage suddenly dropped.
The power supply went OFF while setting a utility function.
A SERVOPACK fault occurred.
Restart the SERVOPACK several times. If the alarm still occurs, the
SERVOPACK may be faulty.
Check Fn012 to see if the set software version agrees with that of the
SERVOPACK. If not, an alarm may occur.
−
Measure the power supply voltage.
Check the circumstances when the power supply went OFF.
Restart the SERVOPACK several times. If the alarm still occurs, the
SERVOPACK may be faulty.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Write the parameter of another
SERVOPACK of the same model with the same software version.
Restart the SERVOPACK.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A SERVOPACK fault occurred.
−
Investigative Actions Corrective Actions
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A.040:
Parameter Setting
Error 1
(The parameter setting was out of the setting range.)
The SERVOPACK and servomotor capacities do not match each other.
A SERVOPACK fault occurred.
Check the combination of SERVO-
PACK and servomotor capacities.
−
The parameter setting is out of the setting range.
The electronic gear ratio is out of the setting range.
Check the setting ranges of the parameters that have been changed.
Check the electronic gear ratio. The ratio must satisfy:
0.001< (Pn20E/Pn210) < 4000.
Select the proper combination of
SERVOPACK and servomotor capacities.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Set the parameter to a value within the setting range.
Set the electronic gear ratio in the range: 0.001< (Pn20E/Pn210)
< 4000.
8.1 Alarm Displays
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions
A.042:
Parameter
Combination Error
A.04A:
Parameter Setting
Error 2
The speed of program JOG operation (Fn004) is lower than the setting range after having changed the electronic gear ratio
(Pn20E/Pn210) or the servomotor.
The speed of program JOG operation (Fn004) is lower than the setting range after having changed the setting of the program JOG movement speed
(Pn533).
The moving speed of advanced autotuning is lower than the setting range after having changed the electronic gear ratio (Pn20E/
Pn210) or the servomotor.
For a 4-byte parameter bank, no registration in two consecutive bytes for two bank members.
The total amount of bank data exceeds 64. (Pn900 × Pn901 >
64)
Check if the detection conditions
*1 are satisfied.
Check if the detection conditions
*1 are satisfied.
Check if the detection conditions
*2 are satisfied.
–
–
A.050:
Combination Error
(The SERVOPACK and servomotor capacities do not correspond.)
The SERVOPACK and servomotor capacities do not match each other.
An encoder fault occurred.
A SERVOPACK fault occurred.
−
Check the capacities to see if they satisfy the following condition:
1
4
≤
Servomotor capacity
SERVOPACK capacity
≤ 4
Replace the servomotor and see if the alarm occurs again.
A.051:
Unsupported Device
Alarm
An unsupported encoder is connected to the SERVOPACK.
Check the product specifications, and select the correct model.
A.0b0:
Cancelled Servo ON
Command Alarm
After executing the utility function to turn ON the power to the motor, the servo ON command
(SV_ON) was sent from the host controller.
−
∗1.
Detection conditions
If one of the following conditions detected, an alarm occurs.
• Pn533 [min
-1
] ×
Encoder resolution
6 × 10
5
≤
Pn20E
Pn210
• Max Motor Speed [min
-1
] ×
Encoder resolution
About 3.66
× 10
12
≥
Pn20E
Pn210
∗2.
Detection conditions
If one of the following conditions detected, an alarm occurs.
•
•
Rated Motor Speed [min
-1
] ×
Max Motor Speed [min
-1
] ×
1
3
×
Encoder resolution
Encoder resolution
About 3.66
6 × 10
5
× 10
12
≥
≤
Pn20E
Pn210
Pn20E
Pn210
Corrective Actions
Decrease the setting of the electronic gear ratio (Pn20E/Pn210).
Increase the setting of the program
JOG movement speed (Pn533).
Decrease the setting of the electronic gear ratio (Pn20E/Pn210).
Change the number of bytes for bank members to an appropriate value.
Reduce the total amount of bank data to 64 or less.
Select the proper combination of
SERVOPACK and servomotor capacities.
Replace the servomotor (encoder).
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Select the correct combination of units.
Restart the SERVOPACK or execute a software reset.
8
8-7
8-8
8 Troubleshooting
8.1.2 Troubleshooting of Alarms
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions Corrective Actions
A.100:
Overcurrent or Heat
Sink Overheated
(An overcurrent flowed through the IGBT or heat sink of SERVO-
PACK overheated.)
A.400:
Overvoltage
(Detected in the SER-
VOPACK main circuit power supply section.)
Incorrect wiring or contact fault of servomotor main circuit cables.
Check the wiring. Refer to
Main Circuit Wiring.
3.1
Correct the wiring.
Short-circuit or ground fault of servomotor main circuit cables.
Short-circuit or ground fault inside the servomotor.
Short-circuit or ground fault inside the SERVOPACK.
Check for short-circuits across the servomotor terminal phases U, V, and W, or between the grounding and servomotor terminal phases U,
V, or W. Refer to 3.1 Main Circuit
Wiring .
Check for short-circuits across the servomotor terminal phases U, V, and W, or between the grounding and servomotor terminal phases U,
V, or W. Refer to 3.1 Main Circuit
Wiring .
Check for short-circuits across the servomotor connection terminals U,
V, and W on the SERVOPACK, or between the grounding and terminal
U, V, or W. Refer to 3.1 Main Circuit Wiring .
Check to see if the operating conditions are outside servo drive specifications.
The cable may be short-circuited.
Replace the cable.
The servomotor may be faulty.
Replace the servomotor.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A heavy load was applied while the servomotor was stopped or running at a low speed.
Malfunction caused by noise interference.
A SERVOPACK fault occurred.
The DC power supply voltage exceeded 60 V.
The power supply is unstable, or was influenced by a lightning surge.
Improve the wiring or installation environment, such as by reducing noise, and check to see if the alarm recurs.
−
Measure the power supply voltage.
Measure the power supply voltage.
Reduce the load applied to the servomotor or increase the operating speed.
Take countermeasures for noise, such as correct wiring of the FG.
Use an FG wire size equivalent to the SERVOPACK main circuit wire size.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Set DC power supply voltage within the specified range.
Improve the power supply conditions by installing a surge absorber, etc. Then, restart the SERVOPACK.
If the alarm still occurs, the SER-
VOPACK may be faulty. Replace the SERVOPACK.
Voltage for DC power supply was too high during acceleration or deceleration.
The moment of inertia ratio exceeded the allowable value.
A SERVOPACK fault occurred.
Check the power supply voltage and the speed and torque during operation.
Confirm that the moment of inertia ratio is within the allowable range.
−
Set DC power supply voltage within the specified range.
Increase the deceleration time, or reduce the load.
Turn the control power OFF and then ON again while the main circuit power supply is OFF. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
A.450:
Main-Circuit
Capacitor Overvoltage
A SERVOPACK fault occurred.
− Replace the SERVOPACK.
8.1 Alarm Displays
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions Corrective Actions
A.510:
Overspeed
(The servomotor speed exceeds the maximum.)
A.520:
Vibration Alarm
A.521:
Autotuning Alarm
(Vibration was detected while executing the oneparameter tuning,
EasyFFT, or tuning-less function.)
A.710:
A.720:
Overload
A.710: High Load
A.720: Low Load
A.7A0:
Heat Sink Overheated
(Detected when the heat sink temperature exceeds 90 ° C.)
The order of phases U, V, and W in the servomotor wiring is incorrect.
A reference value exceeding the overspeed detection level was input.
Check the motor wiring.
Check the input value.
Confirm that the servomotor is correctly wired.
Reduce the reference value or adjust the gain.
The motor speed exceeded the maximum.
A SERVOPACK fault occurred.
Check the motor speed waveform.
−
Reduce the speed reference input gain, adjust the servo gain, or reconsider the operating conditions.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Abnormal vibration was detected at the motor speed.
Check for abnormal noise from the servomotor, and check the speed and torque waveforms during operation.
Reduce the motor speed or reduce the speed loop gain (Pn100).
The moment of inertia ratio
(Pn103) value is greater than the actual value or is greatly changed.
Check the moment of inertia ratio.
Set the moment of inertia ratio
(Pn103) to an appropriate value.
The servomotor vibrated considerably while performing tuningless function.
The servomotor vibrated considerably during one-parameter tuning or EasyFFT.
Incorrect wiring or contact fault of servomotor and encoder.
Operation beyond the overload protection characteristics.
A SERVOPACK fault occurred.
Check the motor speed waveform.
Check the motor speed waveform.
Check the wiring.
Check the servomotor overload characteristics and executed run command.
−
Reduce the load so that the moment of inertia ratio falls within the allowable value, or raise the load level using the tuning-less levels setting (Fn200) or reduce the rigidity level.
Check the operation procedure of corresponding function and take a corrective action.
Confirm that the servomotor and encoder are correctly wired.
Reconsider the load conditions and operating conditions. Or, increase the motor capacity.
Excessive load was applied during operation because the servomotor was not driven due to mechanical problems.
Incorrect SERVOPACK installation orientation or/and insufficient space around the
SERVOPACK.
Check the executed operation reference and motor speed.
A SERVOPACK fault occurred.
The surrounding air temperature is too high.
The overload alarm has been reset by turning OFF the power too many times.
Excessive load was applied during operation.
−
Check the surrounding air temperature using a thermostat.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Decrease the surrounding air temperature by improving the SERVO-
PACK installation conditions.
Check the alarm history display
(Fn000) to see if the overload alarm was reported.
Check the accumulated load ratio
(Un009) to see the load during operation.
Change the method for resetting the alarm.
Reconsider the load conditions and operating conditions.
Check the SERVOPACK installation conditions.
Remove the mechanical problems.
Install the SERVOPACK correctly as specified.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
8
8-9
8-10
8 Troubleshooting
8.1.2 Troubleshooting of Alarms
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause
A.810:
Encoder Backup Error
(Only when an absolute encoder is connected.)
(Detected on the encoder side.)
Alarm occurred when the power to the absolute encoder was initially turned ON.
The encoder cable disconnected, and connected again.
The power from both the control power supply (+5 V) from the
SERVOPACK and the battery power supply is not being supplied.
An absolute encoder fault occurred.
Investigative Actions
Check to see if the power was turned ON initially.
Check to see if the power was turned ON initially.
Check the encoder connector battery or the connector contact status.
Replace the battery or take similar measures to supply power to the encoder, and set up the encoder
(Fn008).
Corrective Actions
Set up the encoder (Fn008).
Confirm the connection and set up the encoder (Fn008).
A.820:
Encoder Checksum
Error
(Detected on the encoder side.)
A SERVOPACK fault occurred.
An encoder fault occurred.
A SERVOPACK fault occurred.
−
−
−
−
If the alarm cannot be reset by setting up the encoder again, replace the servomotor.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
• Absolute encoder
Set up the encoder again using
Fn008. If the alarm still occurs, the servomotor may be faulty.
Replace the servomotor.
• One-turn absolute encoder or incremental encoder
The servomotor may be faulty.
Replace the servomotor.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
A.830:
Absolute Encoder
Battery Error
(The absolute encoder battery voltage is lower than the specified value.)
The battery connection is incorrect.
The battery voltage is lower than the specified value 2.7 V.
Check the battery connection.
Measure the battery voltage.
A SERVOPACK fault occurred.
−
A.840:
Encoder Data Error
(Detected on the encoder side.)
An encoder malfunctioned.
Malfunction of encoder because of noise interference, etc.
−
−
A.850:
Encoder Overspeed
(Detected when the control power supply was turned ON.)
(Detected on the encoder side.)
The servomotor speed is higher than 200 min
-1
when the control power supply was turned ON.
An encoder fault occurred.
−
A SERVOPACK fault occurred.
−
Check the motor rotating speed
(Un000) to confirm the servomotor speed when the power is turned ON.
Reconnect the battery.
Replace the battery.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Correct the wiring around the encoder by separating the encoder cable from the servomotor main circuit cable or by checking the grounding and other wiring.
Reduce the servomotor speed to a value less than 200 min
-1
, and turn
ON the control power supply.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
8.1 Alarm Displays
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause
The ambient operating temperature around the servomotor is too high.
The motor load is greater than the rated load.
A.860:
Encoder Overheated
(Only when an absolute encoder is connected.)
(Detected on the encoder side.)
An encoder fault occurred.
A.b31:
Current Detection
Error 1
A.b32:
Current Detection
Error 2
A SERVOPACK fault occurred.
The current detection circuit for phase U is faulty.
The current detection circuit for phase V is faulty.
−
−
−
−
Investigative Actions
Measure the ambient operating temperature around the servomotor.
Check the accumulated load ratio
(Un009) to see the load.
−
Corrective Actions
The ambient operating temperature must be 40 ° C or less.
The motor load must be within the specified range.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
A.b33:
Current Detection
Error 3
The detection circuit for the current is faulty.
The servomotor main circuit cable is disconnected.
A.b6A:
MECHATROLINK
Communications ASIC
Error 1
SERVOPACK MECHA-
TROLINK communication section fault.
Check for disconnection of the servomotor main circuit cable.
−
Correct the servomotor wiring.
A.b6b:
MECHATROLINK
Communications ASIC
Error 2
A.bE0:
Firmware Error
A.bF0:
System Alarm 0
A.bF1:
System Alarm 1
A.bF2:
System Alarm 2
MECHATROLINK data reception error occurred due to noise interference.
SERVOPACK MECHA-
TROLINK communication section fault.
A SERVOPACK fault occurred.
A SERVOPACK fault occurred.
A SERVOPACK fault occurred.
A SERVOPACK fault occurred.
−
−
−
−
−
−
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
8
8-11
8-12
8 Troubleshooting
8.1.2 Troubleshooting of Alarms
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions Corrective Actions
A.bF3
:
System Alarm 3
A.bF4:
System Alarm 4
A SERVOPACK fault occurred.
A SERVOPACK fault occurred.
−
−
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
The order of phases U, V, and W in the servomotor wiring is incorrect.
Check the motor wiring.
Confirm that the servomotor is correctly wired.
A.C10:
Servo Overrun
Detected
(Detected when the servomotor power is
ON.)
A.C80:
Absolute Encoder
Clear Error and Multiturn Limit Setting Error
An encoder fault occurred.
A SERVOPACK fault occurred.
An encoder fault occurred.
−
A SERVOPACK fault occurred.
−
A.C90:
Encoder
Communications Error
Contact fault of connector or incorrect wiring for encoder cable.
Cable disconnection for encoder cable or short-circuit.
Or, incorrect cable impedance.
Corrosion caused by improper temperature, humidity, or gas, short-circuit caused by intrusion of water drops or cutting oil, or connector contact fault caused by vibration.
Check the connector contact status for encoder cable.
Check the encoder cable.
Check the operating environment.
Malfunction caused by noise interference.
A SERVOPACK fault occurred.
−
−
−
−
If the alarm still occurs after restarting the SERVOPACK, even though the servomotor is correctly wired, the servomotor may be faulty.
Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Re-insert the connectors and confirm that the encoder is correctly wired.
Use the cables with the specified rating.
Improve the operating environmental conditions, and replace the cable.
If the alarm still occurs, replace the
SERVOPACK.
Correct the wiring around the encoder by separating the encoder cable from the servomotor main circuit cable or by checking the grounding and other wiring.
Connect the servomotor to another
SERVOPACK, and turn ON the control power. If no alarm occurs, the SERVOPACK may be faulty.
Replace the SERVOPACK.
8.1 Alarm Displays
Alarm Number:
Alarm Name
(Alarm Description)
A.C91:
Encoder
Communications
Position Data Error
A.C92:
Encoder
Communications
Timer Error
A.CA0:
Encoder Parameter
Error
A.Cb0:
Encoder Echoback
Error
(cont’d)
Corrective Actions Cause Investigative Actions
Noise interference occurred on the I/O signal line because the encoder cable is bent and the sheath is damaged.
The encoder cable is bundled with a high-current line or near a high-current line.
The FG potential varies because of influence from machines on the servomotor side, such as the welder.
Noise interference occurred on the I/O signal line from the encoder.
Excessive vibration and shocks were applied to the encoder.
Check the encoder cable and connector.
Check the cable layout for encoder cable.
Check the cable layout for encoder cable.
−
Check the operating environment.
An encoder fault occurred.
A SERVOPACK fault occurred.
An encoder fault occurred.
A SERVOPACK fault occurred.
−
−
−
−
Confirm that there is no problem with the cable layout.
Confirm that there is no surge voltage on the cables.
Properly ground the machines to separate from the encoder FG.
Take countermeasures against noise for the encoder wiring.
Reduce the machine vibration or correctly install the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
The wiring and contact for encoder cable are incorrect.
Check the wiring.
Correct the wiring.
Noise interference occurred due to incorrect cable specifications of encoder cable.
−
Use tinned annealed copper shielded twisted-pair or screened unshielded twisted-pair cable with a core of at least 0.12 mm
2
.
Noise interference occurred because the wiring distance for the encoder cable is too long.
The FG potential varies because of influence from machines on the servomotor side, such as the welder.
Excessive vibration and shocks were applied to the encoder.
An encoder fault occurred.
A SERVOPACK fault occurred.
−
Check the cable layout for encoder cable.
Check the operating environment.
−
−
The wiring distance must be 50 m max.
Properly ground the machines to separate from encoder FG.
Reduce the machine vibration or correctly install the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the servomotor may be faulty. Replace the servomotor.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
8
8-13
8 Troubleshooting
8.1.2 Troubleshooting of Alarms
8-14
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions Corrective Actions
A.CC0:
Multiturn Limit
Disagreement
A.d00:
Position Error
Overflow
(Position error exceeded the value set in the excessive position error alarm level (Pn520).)
The multiturn limit value of the encoder is different from that of the SERVOPACK. Or, the multiturn limit value of the SERVO-
PACK has been changed.
A SERVOPACK fault occurred.
The servomotor U, V, and W wirings is faulty.
The position reference speed is too high.
The acceleration of the position reference is too high.
Check the value of the Pn205 of the
SERVOPACK.
−
Check the servomotor main circuit cable connection.
Reduce the reference speed, and operate the SERVOPACK.
Reduce the reference acceleration, and operate the SERVOPACK.
Execute Fn013 at the occurrence of alarm.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Confirm that there is no contact fault in the motor wiring or encoder wiring.
Reduce the position reference speed or acceleration of position reference. Or, reconsider the electronic gear ratio.
Reduce the reference acceleration of the position reference using a
MECHATROLINK command, or smooth the acceleration of the position reference by selecting the position reference filter (ACCFIL) using a MECHATROLINK command.
Setting of the excessive position error alarm level (Pn520) is low against the operating condition.
Check the alarm level (Pn520) to see if it is set to an appropriate value.
Set the Pn520 to proper value.
A SERVOPACK fault occurred.
−
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
A.d01:
Position Error
Overflow Alarm at
Servo ON
A.d02:
Position Error
Overflow Alarm by
Speed Limit at Servo
ON
This alarm occurs if the servomotor power is turned ON when the position error is greater than the set value of Pn526 while the servomotor power is OFF.
When the position errors remain in the error counter, Pn529 limits the speed if the servomotor power is ON. If Pn529 limits the speed in such a state, this alarm occurs when position references are input and the number of position errors exceeds the value set for the excessive position error alarm level (Pn520).
MECHATROLINK transmission cycle fluctuated.
Check the position error amount
(Un008) while the servomotor power is OFF.
−
−
Correct the excessive position error alarm level at servo ON (Pn526).
Correct the excessive position error alarm level (Pn520).
Or, adjust the speed limit level at servo ON (Pn529).
A.E02:
MECHATROLINK
Internal
Synchronization
Error 1
A SERVOPACK fault occurred.
−
Remove the cause of transmission cycle fluctuation at host controller.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
A.E40:
MECHATROLINK
Transmission Cycle
Setting Error
A.E41:
MECHATROLINK
Communications Data
Size Setting Error
Setting of MECHATROLINK transmission cycle is out of specifications range.
Check the MECHATROLINK transmission cycle setting.
The number of transmission bytes set by the DIP switch S2 is incorrect.
Check the MECHATROLINK communications data size of the host controller.
Set the transmission cycle to the proper value.
Reset the setting of the DIP switch
S2 to change the number of transmission bytes to the proper value.
8.1 Alarm Displays
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions Corrective Actions
A.E42:
MECHATROLINK
Station Address
Setting Error
A.E50:
MECHATROLINK
Synchronization Error
A.E51:
MECHATROLINK
Synchronization
Failed
A.E60:
MECHATROLINK
Communications error
(Reception error)
A.E61:
MECHATROLINK
Transmission Cycle
Error
(Synchronization interval error)
A.E62:
MECHATROLINK
Communications error
(FCS error)
The station address is out of the allowable setting range.
Two or more stations on the communications network have the same address.
Check that two or more stations on the communications network have the same address.
WDT data of host controller was not updated correctly.
A SERVOPACK fault occurred.
Check the DIP switch S1 to see if the station address is within the allowable range from 03 to EF.
Check the WDT data updating for the host controller.
−
Check the setting for the station address of the host controller, and reset the setting of the DIP switch
S1 to change the address to the proper value between 03 and EF.
Check the setting for the station address of the host controller, and reset the setting of the DIP switch
S1 to change the address to the proper value between 03 and EF.
Update the WDT data at the host controller correctly.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
WDT data of host controller was not updated correctly at the synchronization communications start, and synchronization communications could not start.
Check the WDT data updating for the host controller.
Update the WDT data at the host controller correctly.
A SERVOPACK fault occurred.
MECHATROLINK wiring is incorrect.
MECHATROLINK data reception error occurred due to noise interference.
A SERVOPACK fault occurred.
MECHATROLINK transmission cycle fluctuated.
A SERVOPACK fault occurred.
MECHATROLINK wiring is incorrect.
MECHATROLINK data reception error occurred due to noise interference.
A SERVOPACK fault occurred.
−
Check the MECHATROLINK wirings.
−
−
Check the MECHATROLINK transmission cycle setting.
−
Check the MECHATROLINK wirings.
−
−
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Correct the MECHATROLINK wiring.
Connect the terminator correctly.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Remove the cause of transmission cycle fluctuation at host controller.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Correct the MECHATROLINK wiring.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
8
8-15
8-16
8 Troubleshooting
8.1.2 Troubleshooting of Alarms
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause Investigative Actions Corrective Actions
A.E63:
MECHATROLINK
Synchronization
Frame Not Received
Alarm
A.EA2:
DRV Alarm 2
(SERVOPACK WDT error)
A.Ed1:
Command Execution
Timeout
A.F50:
Servomotor Main
Circuit Cable
Disconnection
(The servomotor did not operate or power was not supplied to the servomotor even though the
SV_ON (Servo ON) command was input when the servomotor was ready to receive it.)
MECHATROLINK wiring is incorrect.
MECHATROLINK data reception error occurred due to noise interference.
A SERVOPACK fault occurred.
MECHATROLINK transmission cycle fluctuated.
A SERVOPACK fault occurred.
A timeout error occurred when using an MECHATROLINK command.
A SERVOPACK fault occurred.
Check the MECHATROLINK wirings.
−
−
Check the MECHATROLINK transmission cycle setting.
−
Check the motor status when the command is executed.
−
The wiring is not correct or there is a faulty contact in the motor wiring.
Check the wiring.
Correct the MECHATROLINK wiring.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Remove the cause of transmission cycle fluctuation at host controller.
Restart the SERVOPACK. If the alarm still occurs, the SERVO-
PACK may be faulty. Replace the
SERVOPACK.
Execute the SV_ON or SENS_ON command only when the motor is not running.
The SERVOPACK may have failed.
Replace the SERVOPACK.
Make sure that the servomotor is correctly wired.
8.2 Warning Displays
8.2
Warning Displays
The following sections describe troubleshooting in response to warning displays.
The warning name and warning meaning are listed in order of the warning numbers in 8.2.1 List of Warnings .
The causes of warnings and troubleshooting methods are provided in 8.2.2 Troubleshooting of Warnings .
8.2.1
List of Warnings
This section provides list of warnings.
Warning
Number
A.900
*1
A.901
A.910
A.911
A.930
A.94A
A.94B
A.94C
A.94D
A.94E
A.95A
A.95B
A.95D
A.95E
A.95F
A.960
A.962
A.963
A.97A
*1
*1
*1
*1
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
Warning Name Meaning Reset
Position Error Overflow
Position Error Overflow
Alarm at Servo ON
Overload
Vibration
Data Setting Warning 2
(Out of Range)
Data Setting Warning 3
(Calculation Error)
Position error exceeded the parameter setting
(Pn520 × Pn51E/100).
When the servomotor power is ON, the position error exceeded the parameter setting (Pn526 × Pn528/100).
This warning occurs before the overload alarms (A.710 or
A.720) occur. If the warning is ignored and operation continues, an overload alarm may occur.
Abnormal vibration at the motor speed was detected. The detection level is the same as A.520. Set whether to output an alarm or warning by the vibration detection switch (Pn310).
This warning occurs when the voltage of absolute encoder’s battery is lowered.
Required
Required
Required
Required
Absolute Encoder Battery
Error
Data Setting Warning 1
(Parameter Number Error)
Incorrect command parameter number was set.
Command input data is out of range.
Calculation error was detected.
Required
Automatic reset
*3
Automatic reset
*3
Automatic reset
*3
Automatic reset
*3
Data Setting Warning 4
(Parameter Size)
Data Setting Warning 5
(Latch Mode Error)
Command Warning 1
(Unsatisfying Command)
Data size does not match.
Latch mode error is detected.
Required
Command Warning 2
(Non-supported Command)
Command Warning 4
(Command Interference)
Command Warning 5
(Subcommand Disable)
Command Warning 6
(Undefined Command)
Command was sent although the conditions for sending a command were not satisfied.
Unsupported command was sent.
Command, especially latch command, interferes.
Subcommand and main command interfere.
Undefined command was sent.
Automatic reset
*3
Automatic reset
*3
Automatic reset
*3
Automatic reset
*3
Automatic reset
*3
MECHATROLINK
Communications Warning
MECHATROLINK
Communications Warning
(FCS Error)
MECHATROLINK
Communications Warning
(Synchronization Frame Not
Received)
Communications error occurred during MECHATROLINK communications.
Communications error occurred during MECHATROLINK communications.
The synchronization frame was not received during
MECHATROLINK communications.
Command Warning 7
(Phase Error)
Required
Required
Required
A command that cannot be executed in the current phase was sent.
Automatic reset
*3
8
8-17
8-18
8 Troubleshooting
8.2.1 List of Warnings
(cont’d)
Warning
Number
Warning Name Meaning Reset
A.97B
*2
Data Clamp
(Out of Range)
Overtravel
The set command data was clamped to a minimum or maximum value out of the allowable setting range.
Overtravel is detected while the servomotor power is ON.
Automatic reset
*3
Required A.9A0
*1
∗1.
Use Pn008.2 to activate or not the warning detection.
∗2.
Use Pn800.1 to activate or not the warning detection.
∗3.
If using the commands for the MECHATROLINK-III standard servo profile, the warning will automatically be cleared after the correct command is received.
If using the commands for the MECHATROLINK-II-compatible profile, send a Clear Warning or Alarm command
(ALM_CLR) to clear the warning.
8.2 Warning Displays
8.2.2
Troubleshooting of Warnings
Refer to the following table to identity the cause of a warning and the action to be taken. Contact your
Yaskawa representative if the problem cannot be solved by the described corrective action.
Warning
Number:
Warning Name
(Warning
Description)
A.900:
Position Error
Overflow
Cause Investigative Actions Corrective Actions
The servomotor U, V, and W wirings is faulty.
Check the servomotor main circuit cable connection.
Confirm that there is no contact fault in the motor wiring or encoder wiring.
The SERVOPACK gain is too low.
Check the SERVOPACK gain.
Increase the servo gain by using the function such as advanced autotuning.
The acceleration of the position reference is too high.
Reduce the reference acceleration, and operate the SERVOPACK.
Reduce the reference acceleration of the position reference using a
MECHATROLINK command, or smooth the acceleration of the position reference by selecting the position reference filter (ACCFIL) using a
MECHATROLINK command.
Setting of the excessive position error alarm level (Pn520) is low against the operating condition.
Check the alarm level (Pn520) to see if it is set to an appropriate value.
Set the Pn520 to proper value.
A SERVOPACK fault occurred.
−
Restart the SERVOPACK. If the alarm still occurs, the SERVOPACK may be faulty. Replace the SERVOPACK.
A.901:
Position Error
Overflow Alarm at Servo ON
When the servomotor power is ON, the position error exceeded the parameter setting
(Pn526 × Pn528/100).
−
Set an appropriate value for the excessive position error warning level at servo ON (Pn528).
A.910:
Overload
(Warning before alarm A.710 or
A.720 occurs)
Incorrect wiring or contact fault of servomotor and encoder.
Check the wiring.
Confirm that the servomotor and encoder are correctly wired.
Operation beyond the overload protection characteristics.
Excessive load was applied during operation because the servomotor was not driven due to mechanical problems.
Check the motor overload characteristics and executed run command.
Check the executed operation reference and motor speed.
Reconsider the load conditions and operating conditions. Or, increase the motor capacity.
Remove the mechanical problems.
A SERVOPACK fault occurred.
−
The SERVOPACK may be faulty.
Replace the SERVOPACK.
8
8-19
8-20
8 Troubleshooting
8.2.2 Troubleshooting of Warnings
(cont’d)
Warning
Number:
Warning Name
(Warning
Description)
Cause Investigative Actions Corrective Actions
A.911:
Vibration
A.930:
Absolute
Encoder Battery
Error
(The absolute encoder battery voltage is lower than the specified value.)
(Only when an absolute encoder is connected.)
A.94A
Data Setting
Warning 1
(Parameter Number Error)
Abnormal vibration was detected at the motor speed.
Check for abnormal noise from the servomotor, and check the speed and torque waveforms during operation.
The moment of inertia ratio (Pn103) value is greater than the actual value or is greatly changed.
The battery connection is incorrect.
Check the moment of inertia ratio.
Check the battery connection.
The battery voltage is lower than the specified value 2.7 V.
A SERVOPACK fault occurred.
Measure the battery voltage.
−
A.94B
Data Setting
Warning 2
(Out of Range)
A.94C
Data Setting
Warning 3
(Calculation
Error)
A.94D
Data Setting
Warning 4
(Parameter Size )
A.94E
Data Setting
Warning 5
(Latch mode error)
A.95A
Command
Warning 1
(Unsatisfying
Command)
A.95B
Command
Warning 2
(Non-supported
Command)
SERVOPACK received unsupported command.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Reduce the motor speed or reduce the servo gain by using the function such as one-parameter tuning.
Set the moment of inertia ratio
(Pn103) to an appropriate value.
Reconnect the battery.
Replace the battery.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
Disabled parameter number was used.
Attempted to send values outside the range to the command data.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Calculation result of set value is incorrect.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Parameter size set in command is incorrect.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Use the correct parameter number.
Set the value of the parameter within the allowable range.
Set the value of the parameter within the allowable range.
Use the correct parameter size.
Latch mode error is detected.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Change the setting value of Pn850 or the LT_MOD data for the LTMOD-
_ON command sent by the host controller to the proper value.
(When using the MECHATROLINK-
II-compatible profile.)
Command sending condition is not satisfied.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Send a command after command sending condition is satisfied.
Do not sent an unsupported command.
8.2 Warning Displays
(cont’d)
Warning
Number:
Warning Name
(Warning
Description)
A.95D
Command
Warning 4
(Command Interference)
A.95E
Command
Warning 5
(Subcommand
Disable)
A.95F
Command
Warning 6
(Undefined Command)
Cause
Command sending condition for latch-related commands is not satisfied.
Subcommand sending condition is not satisfied.
Undefined command was sent.
Investigative Actions
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Corrective Actions
Send a command after command sending condition is satisfied.
Send a command after command sending condition is satisfied.
Refer to 8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning to determine which command was the cause of the warning.
Do not use an undefined command.
A.960
MECHATROLINK
Communications
Warning
MECHATROLINK data reception error occurred due to noise interference.
A.962
MECHATROLINK
Communications
Warning
(FCS Error)
MECHATROLINK wiring is incorrect.
A SERVOPACK fault occurred.
MECHATROLINK wiring is incorrect.
MECHATROLINK data reception error occurred due to noise interference.
A SERVOPACK fault occurred.
Confirm the wiring.
Confirm the installation conditions.
–
Confirm the wiring.
Confirm the installation conditions.
–
A.963
MECHATROLINK
Communications
Warning
(Synchronization
Frame Not
Received)
MECHATROLINK wiring is incorrect.
MECHATROLINK data reception error occurred due to noise interference.
Confirm the wiring.
Confirm the installation conditions.
A SERVOPACK fault occurred.
–
Correct the MECHATROLINK wiring.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
A fault occurred in the SERVOPACK.
Replace the SERVOPACK.
Correct the MECHATROLINK wiring.
Or, connect a terminal to the terminal station.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
A fault occurred in the SERVOPACK.
Replace the SERVOPACK.
Correct the MECHATROLINK wiring.
Or, connect a terminal to the terminal station.
Take measures against noise. Check the MECHATROLINK communications cable and FG wiring and take measures such as adding ferrite core on the MECHATROLINK communications cable.
A fault occurred in the SERVOPACK.
Replace the SERVOPACK.
8
8-21
8-22
8 Troubleshooting
8.2.2 Troubleshooting of Warnings
(cont’d)
Warning
Number:
Warning Name
(Warning
Description)
A.97A
Command
Warning 7
(Phase Error)
Cause
A command that cannot be executed in the current phase was sent.
–
A.97B
Data Clamp
(Out Of Range)
The set command data was clamped to a minimum or maximum value out of the allowable setting range.
–
Investigative Actions Corrective Actions
Send a command after command sending condition is satisfied.
A.9A0:
Overtravel
(Overtravel status is detected.)
When the servomotor power is ON, overtravel status is detected.
Check the input signal monitor
(Un005) to check the status of the overtravel signals.
Set the value of the command data within the allowable range.
Refer to 8.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor . Even if overtravel signals were not shown by the input signal monitor (Un005), momentary overtravel may have been detected. Take the following precautions.
• Do not specify movements that would cause overtravel from the host controller.
• Check the wiring of the overtravel signals.
• Take countermeasures for noise.
8.3 Monitoring Communication Data on Occurrence of an Alarm or Warning
8.3
Monitoring Communication Data on Occurrence of an Alarm or
Warning
The command data received on occurrence of an alarm or warning, such as a data setting warning (A.94
) or a command warning (A.95
) can be monitored using the following parameters. The following is an example of the data when an alarm/warning has occurred in the normal state.
Command Data Monitor at Alarm/Warning Occurrence: Pn890 to Pn8A6
Response Data Monitor at Alarm/Warning Occurrence: Pn8A8 to Pn8BE
20 to 23
24 to 27
28 to 31
32 to 35
36 to 39
40 to 43
44 to 47
2
3
0
1
4 to 7
8 to 11
12 to 15
16 to 19
Command
Byte Order
Command Data Storage at
Alarm/Warning Occurrence
CMD RSP
Pn890.1 to 0
Pn890.3 to 2
Pn890.5 to 4
Pn890.7 to 6
Pn8A8.1 to 0
Pn8A8.3 to 2
Pn8A8.5 to 4
Pn8A8.7 to 6
Pn892
Pn894
Pn896
Pn898
Pn89A
Pn89C
Pn89E
Pn8A0
Pn8A2
Pn8A4
Pn8A6
Pn8AA
Pn8AC
Pn8AE
Pn8B0
Pn8B2
Pn8B4
Pn8B6
Pn8B8
Pn8BA
Pn8BC
Pn8BE
Example: Pn8A8 = 87 65 43 21
Note 1. Data is stored in little endian byte order and displayed in the hexadecimal format.
2. For details on commands, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands (Manual No.: SIEP S800000 63).
8
8-23
8-24
8 Troubleshooting
8.4
Troubleshooting Malfunction Based on Operation and
Conditions of the Servomotor
Troubleshooting for the malfunctions based on the operation and conditions of the servomotor is provided in this section.
Be sure to turn OFF the servo system before troubleshooting items shown in bold lines in the table.
Problem
Servomotor Does
Not Start
Probable Cause
The control power supply is not
ON.
The main circuit power supply is not ON.
Wiring of I/O signal connector CN1 is faulty or disconnected.
Wiring for servomotor main circuit cable or encoder cable is disconnected.
Investigative Actions
Check voltage between control power input terminals.
Check the voltage between main circuit power input terminals.
Check if the connector CN1 is properly inserted and connected.
Check the wiring.
Overloaded
Encoder type differs from parameter setting (Pn002.2).
Settings for the input signal selections (Pn50A, Pn50B and Pn511) is incorrect.
Run under no load and check the load status.
Check the settings for parameter
Pn002.2.
Check the settings for parameters
Pn50A, Pn50B and Pn511.
SV_ON command is not sent.
SENS_ON command is not sent.
Check the command sent from the host controller.
Check the command sent from the host controller.
The forward run prohibited (P-OT) and reverse run prohibited (N-OT) input signals are turned OFF.
A SERVOPACK fault occurred.
Servomotor wiring is incorrect.
Check P-OT or N-OT input signal.
−
Check the wiring.
Corrective Actions
Correct the wiring.
Correct the wiring.
Correct the connector CN1 connection.
Correct the wiring.
Reduce load or replace with larger capacity servomotor.
Set parameter Pn002.2 to the encoder type being used.
Correct the settings for parameter
Pn50A, Pn50B and Pn511.
Send the SV_ON command.
Send the command in the correct
SERVOPACK sequence.
Turn P-OT or N-OT input signal
ON.
Replace the SERVOPACK.
Correct the wiring.
Servomotor
Moves
Instantaneously, and then Stops
Servomotor
Rotates Without
Reference Input
Encoder wiring is incorrect.
The SERVOPACK suddenly entered baseblock status during servomotor operation.
The main circuit power supply voltage is 13 V or lower.
The fuse in the SERVOPACK is blown.
−
Check voltage between main circuit power input terminals during operation.
Set the power supply voltage to within the specified range.
Increase the capacity of the main circuit AC/DC power supply.
Replace the SERVOPACK.
A SERVOPACK fault occurred.
−
A fault occurred in the SERVO-
PACK.
Replace the SERVOPACK.
Servomotor
Speed Unstable
Wiring connection to servomotor is defective.
Check connections of power line
(phases U, V, and W) and encoder connectors.
Tighten any loose terminals or connectors and correct the wiring.
A SERVOPACK fault occurred.
Check the wiring.
−
Correct the wiring.
Replace the SERVOPACK.
8.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor
Problem
Abnormal Noise from Servomotor
The servomotor largely vibrated during execution of tuning-less function.
Noise interference due to incorrect cable specifications of encoder cable.
Noise interference due to length of encoder cable.
Noise interference due to damaged encoder cable.
cable.
Probable Cause
Mounting is not secured.
Bearings are defective.
Vibration source at the driven machine.
Noise interference due to incorrect
I/O signal cable specifications.
Noise interference due to length of
I/O signal cable.
Excessive noise to the encoder
SERVOPACK pulse counting error due to noise interference
Excessive vibration and shock to the encoder
An encoder fault occurred.
Investigative Actions
Check the motor speed waveform.
(cont’d)
Corrective Actions
Reduce the load so that the moment of inertia ratio becomes within the allowable value, or increase the load level or lower the tuning level for the tuning-less levels setting
(Fn200).
Check if there are any loose mounting screws.
Check if there is misalignment of couplings.
Check if there are unbalanced couplings.
Check for noise and vibration around the bearings.
Check for any foreign matter, damage, or deformations on the machinery's movable parts.
The I/O signal cable must be tinned annealed copper shielded twistedpair or screened unshielded twistedpair cable with a core of 0.12 mm
2 min.
Check the length of the I/O signal cable.
The encoder cable must be tinned annealed copper shielded twistedpair or screened unshielded twistedpair cable with a core of 0.12 mm
2 min.
Check the length of the encoder cable.
Check if the encoder cable is bent and the sheath is damaged.
Check if the encoder cable is bundled with a high-current line or near a high-current line.
Tighten the mounting screws.
Align the couplings.
Balance the couplings.
Replace the servomotor.
Contact the machine manufacturer.
Use the specified I/O signal cable.
The I/O signal cable length must be no more than 3 m.
Use the specified encoder cable.
The encoder cable must be no more than 50 m.
Replace the encoder cable and correct the cable layout.
Correct the cable layout so that no surge is applied.
The FG potential varies because of influence from machines on the servomotor side, such as the welder.
Check if the machines are correctly grounded.
Properly ground the machines to separate from the encoder FG.
Check if there is noise interference on the I/O signal line from the encoder.
Check if vibration from the machine occurred or servomotor installation is incorrect (mounting surface accuracy, fixing, alignment, etc.).
−
Take measures against noise in the encoder wiring.
Reduce vibration from the machine, or secure the servomotor installation.
Replace the servomotor.
8
8-25
8 Troubleshooting
8-26
Problem
Servomotor
Vibrates at
Frequency of
Approx. 200 to
400 Hz.
High Motor Speed
Overshoot on
Starting and
Stopping
Absolute Encoder
Position
Difference Error
(The position saved in the host controller when the power was turned OFF is different from the position when the power was next turned ON.) high.
too high.
Speed loop gain value (Pn100) too high
Position loop gain value (Pn102) too high
Incorrect speed loop integral time constant (Pn101)
Noise interference due to incorrect cable specifications of encoder cable.
Noise interference due to length of encoder cable.
Noise interference due to damaged encoder cable.
Excessive noise to the encoder cable.
Probable Cause
Unbalanced servo gains
Speed loop gain value (Pn100) too
Position loop gain value (Pn102)
Incorrect speed loop integral time constant (Pn101)
Incorrect moment of inertia ratio
(Pn103)
Unbalanced servo gains
Incorrect moment of inertia ratio data (Pn103)
Investigative Actions
Check to see if the servo gains have been correctly adjusted.
Check the speed loop gain (Pn100).
Factory setting: Kv = 40.0 Hz
Check the position loop gain
(Pn102).
Factory setting: Kp = 40.0/s
Check the speed loop integral time constant (Pn101).
Factory setting: Ti = 20.0 ms
Check the moment of inertia ratio
(Pn103).
Check to see if the servo gains have been correctly adjusted.
Check the speed loop gain (Pn100).
Factory setting: Kv = 40.0 Hz
Check the position loop gain
(Pn102).
Factory setting: Kp = 40.0/s
Check the speed loop integral time constant (Pn101).
Factory setting: Ti = 20.0 ms
Check the moment of inertia ratio
(Pn103).
The encoder cable must be tinned annealed copper shielded twistedpair or screened unshielded twistedpair cable with a core of 0.12 mm
2 min.
Check the length of the encoder cable.
Check if the encoder cable is bent and the sheath is damaged.
Check if the encoder cable is bundled with a high-current line or near a high-current line.
FG potential varies because of influence of machines such as welders at the servomotor.
Check if the machines are correctly grounded.
SERVOPACK pulse counting error due to noise interference
Excessive vibration and shock to the encoder
An encoder fault occurred.
A SERVOPACK fault occurred.
(The pulse count does not change.)
Check if there is noise interference on the I/O signal line from the encoder.
Check if vibration from the machine occurred or servomotor installation is incorrect (mounting surface accuracy, fixing, alignment, etc.).
−
−
Host controller multiturn data reading error
Check the error detection section of the host controller.
Check if the host controller is executing data parity checks.
Check noise in the cable between the SERVOPACK and the host controller.
(cont’d)
Corrective Actions
Execute the advanced autotuning.
Reduce the speed loop gain
(Pn100).
Reduce the position loop gain
(Pn102).
Correct the speed loop integral time constant (Pn101).
Correct the moment of inertia ratio
(Pn103).
Execute the advanced autotuning.
Reduce the speed loop gain
(Pn100).
Reduce the position loop gain
(Pn102).
Correct the speed loop integral time constant (Pn101).
Correct the moment of inertia ratio
(Pn103).
Use the specified encoder cable.
The encoder cable must be no more than 50 m.
Replace the encoder cable and correct the cable layout.
Correct the cable layout so that no surge is applied.
Ground machines correctly, and prevent diversion to the FG on the encoder side.
Take measures against noise in the encoder wiring.
Reduce vibration from the machine, or secure the servomotor installation.
Replace the servomotor.
Replace the SERVOPACK.
Correct the error detection section of the host controller.
Execute a multiturn data parity check.
Take measures against noise, and again execute a multiturn data parity check.
8.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor
Problem
Overtravel (OT)
Improper Stop
Position by
Overtravel (OT)
Signal
Incorrect forward or reverse run prohibited signal (P-OT/N-OT) allocation (parameters Pn50A.3,
Pn50B.0)
Probable Cause
Forward or reverse run prohibited signal is input.
Forward or reverse run prohibited signal malfunctioning.
Improper limit switch position and dog length
The overtravel limit switch position is too short for the coasting distance.
−
−
Investigative Actions
Check the external power supply
(+24 V) voltage for the input signal.
Check if the overtravel limit switch operates properly.
Check if the overtravel limit switch is wired correctly.
Check the settings for parameters
Pn50A and Pn50B.
Check the fluctuation of the external power supply (+24 V) voltage for the input signal.
Check if the overtravel limit switch operates correctly.
Check if the overtravel limit switch wiring is correct. (check for damaged cables or loose screws.)
Check if the P-OT signal is allocated in Pn50A.3.
Check if the N-OT signal is allocated in Pn50B.0.
(cont’d)
Corrective Actions
Correct the external power supply
(+24 V) voltage.
Correct the overtravel limit switch.
Correct the overtravel limit switch wiring.
Correct the settings for parameters
Pn50A and Pn50B.
Stabilize the external power supply
(+24 V) voltage.
Correct the overtravel limit switch.
Correct the overtravel limit switch wiring.
If another signal is allocated in
Pn50A.3, allocate P-OT.
If another signal is allocated in
Pn50B.0, allocate N-OT.
Install the limit switch at the appropriate position.
Install the overtravel limit switch at the appropriate position.
8
8-27
8-28
8 Troubleshooting
Problem
Position Error
(Without Alarm)
Servomotor
Overheated
Probable Cause
Noise interference due to incorrect encoder cable specifications
Noise interference due to length of encoder cable.
Noise influence due to damaged encoder cable.
Excessive noise to encoder cable.
Investigative Actions
The encoder cable must be tinned annealed copper shielded twistedpair or screened unshielded twistedpair cable with a core of 0.12 mm
2 min.
Check the length of the encoder cable.
Check if the encoder cable is bent and the sheath is damaged.
Check if the encoder cable is bundled with a high-current line or near a high-current line.
(cont’d)
Corrective Actions
Use the specified encoder cable.
The encoder cable must be no more than 50 m.
Replace the encoder cable and modify the cable layout.
Change the cable layout so that no surge is applied.
The FG potential varies because of influence from machines on the servomotor side such as the welder.
SERVOPACK pulse count error due to noise
Excessive vibration and shock to the encoder
Unsecured coupling between machine and servomotor
Noise interference due to improper
I/O signal cable specifications
Check if the machines are correctly grounded.
Check if the I/O signal line from the encoder is influenced by noise.
Check if vibration from the machine occurred or servomotor installation is incorrect (mounting surface accuracy, fixing, alignment, etc.).
Check if a position error occurs at the coupling between machine and servomotor.
The I/O signal cable must be tinned annealed copper shielded twistedpair or screened unshielded twistedpair cable with a core of 0.12 mm
2 min.
Properly ground the machines encoder FG.
Take measures against noise in the encoder wiring.
Reduce the machine vibration or mount the servomotor securely.
Secure the coupling between the machine and servomotor.
Use input signal cable with the specified specifications.
Noise interference due to length of
I/O signal cable
An encoder fault occurred. (The pulse count does not change.)
A SERVOPACK fault occurred.
Ambient operating temperature too high
Servomotor surface dirty
Servomotor overloaded
Check the I/O signal cable length.
−
−
Measure the servomotor ambient operating temperature.
Visually check the surface.
Check the load status with monitor.
The I/O signal cable length must be no more than 3 m.
Replace the servomotor.
Replace the SERVOPACK.
Reduce the ambient operating temperature to 40 ° C or less.
Clean dust and oil from the surface.
If overloaded, reduce load or replace with larger capacity SER-
VOPACK and servomotor.
9
Appendix
9.1 List of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.1.1 Utility Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.1.2 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
9.1.3 MECHATROLINKIII Common Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-34
9.2 List of Monitor Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-42
9.3 Parameter Recording Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-43
9
9-1
9-2
9 Appendix
9.1.1 Utility Functions
9.1
List of Parameters
9.1.1
Utility Functions
The following list shows the available utility functions.
Parameter
No.
Fn000
Fn002
Fn003
Fn004
Fn005
Fn006
Fn008
Fn00C
Fn00D
Fn00E
Fn00F
Fn010
Fn011
Fn012
Fn013
Alarm history display
JOG operation
Origin search
Program JOG operation
Function
Initializing parameter settings
Clearing alarm history
Absolute encoder multiturn reset and encoder alarm reset
Offset adjustment of analog monitor output
Gain adjustment of analog monitor output
Automatic offset-signal adjustment of the motor current detection signal
Manual offset-signal adjustment of the motor current detection signal
Write prohibited setting
Servomotor model display
Software version display
Multiturn limit value setting change when a multiturn limit disagreement alarm occurs
Reference
Section
6.2
6.3
6.4
6.5
6.6
6.7
4.7.4
6.8
6.9
6.10
6.11
6.12
6.13
6.14
Comment: SigmaWin+ function names
Alarm Display
JOG Operation
Origin Search
Program JOG Operation
Editing Parameters
Alarm Display
Setting the Absolute Encoder
Adjusting Analog Monitor
Output
Adjusting Analog Monitor
Output
Adjusting Motor Current
Detection Offset
Adjusting Motor Current
Detection Offset
Write Prohibited Setting
Product Information
Product Information
4.7.6
Setting the Multi-Turn Limit
Fn01B
Fn01E
Fn030
Fn200
Fn201
Fn202
Fn203
Fn204
Fn205
Fn206
Fn207
Vibration detection level initialization
Display of SERVOPACK and servomotor ID
Software reset
Tuning-less levels setting
Advanced autotuning
Advanced autotuning by reference
One-parameter tuning
Anti-resonance control adjustment function
Vibration suppression function
EasyFFT
Online vibration monitor
6.15
6.16
6.17
5.2.2
5.3.2
5.4.2
5.5.2
5.6.2
5.7.2
6.18
6.19
Initializing Vibration Detection Level
Product Information
Resetting the SERVOPACK by Software or MECHA-
TROLINK Communication
Reset
Editing Parameters
Tuning
Tuning
Tuning
Tuning
Tuning
EasyFFT
Online Vibration Monitor
Note: Execute the utility function with SigmaWin+.
9.1 List of Parameters
9.1.2
Parameters
The following table lists the parameters. Do not change any reserved parameters or any parameters that are not given in this manual from their default settings. Also, do not use any settings that are reserved.
Parameter
No.
Size Name
2
Basic Function Select
Switch 0
4th 3rd 2nd 1st digit digit digit digit n.
Pn000
Setting
Range
0000 to
00B3
Units
−
Factory
Setting
When
Enabled
0000 After restart
Direction Selection
0
1
Sets CCW as forward direction.
Sets CW as forward direction. (Reverse Rotation Mode)
2 and 3 Reserved (Do not use.)
Reserved (Do not change.)
Reserved (Do not change.)
2
MECHA
Reserved (Do not change.)
Application Function
Select Switch 1
0000 to
1122
−
4th 3rd 2nd 1st digit digit digit digit n.
Reserved (Do not change.)
0000 After restart
Pn001
Setup
Setup
−
−
−
Reference
Section
4.3.1
−
Overtravel (OT) Stop Mode
0
1
2
Stops the motor by coasting.
Sets the torque of Pn406 to the maximum value, decelerates the servomotor to a stop, and then sets it to servolock state.
Sets the torque of Pn406 to the maximum value, decelerates the servomotor to a stop, and then sets it to coasting state.
Reference
Section
4.3.2
Reserved (Do not change.)
Reserved (Do not change.)
9
9-3
9-4
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Size Name
2
Application Function
Select Switch 2
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
0000 to
4113
Units
−
Factory
Setting
When
Enabled
0011 After restart Setup
MECHATROLINK Command Position and Speed Control Option
0
1
2
3
Reserved (Do not use.)
TLM operates as the torque limit value.
Reserved (Do not use.)
Reserved (Do not use.)
Pn002
Torque Control Option
0
1
Reserved (Do not use.)
V_LIM operates as the speed limit value.
Pn006
−
Reference
Section
*1
−
M-III
Absolute Encoder Usage
0
1
Uses absolute encoder as an absolute encoder.
Uses absolute encoder as an incremental encoder.
Reserved (Do not change.)
Reference
Section
–
–
Reference
Section
4.7
2
Application Function
Select Switch 6
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
005F
− 0002 Immediately Setup − 5.1.3
06
07
08
09
0A
0B
0C
0D
Analog Monitor 1 Signal Selection
00
Motor rotating speed (1 V / 1000 min
-1
)
01
Speed reference (1 V / 1000 min -1 )
02
03
04
05
Torque reference (1 V/100% rated torque)
Position error (0.05 V/1 reference unit)
Position amplifier error (after electronic gears) (0.05 V/ 1 encoder pulse unit)
Position reference speed (1 V / 1000 min -1 )
Reserved (Do not use.)
Reserved (Do not use.)
Positioning completion (positioning completed: 5 V, positioning not completed: 0 V)
Reserved (Do not use.)
Torque feedforward (1 V/100% rated torque)
Active gain (1st gain: 1 V, 2nd gain: 2 V)
Completion of position reference (completed: 5 V, not completed: 0 V)
Reserved (Do not use.)
Reserved (Do not change.)
Reserved (Do not change.)
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
(Manual
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
2
Application Function
Select Switch 7
4th 3rd 2nd 1st digit digit digit digit n.
Pn007
Setting
Range
0000 to
005F
Units
−
Factory
Setting
When
Enabled
0000 Immediately Setup −
2
Application Function
Select Switch 8
4th 3rd 2nd 1st digit digit digit digit n.
Analog Monitor 2 Signal Selection
00
Motor rotating speed (1 V / 1000 min
-1
)
01
Speed reference (1 V / 1000 min
-1
)
02 Torque reference (1 V/100% rated torque)
03 Position error (0.05 V/1 reference unit)
04 Position amplifier error (after electronic gears) (0.05 V/ 1 encoder pulse unit)
05
Position reference speed (1 V / 1000 min
-1
)
06 Reserved (Do not use.)
07 Reserved (Do not use.)
08 Positioning completion (positioning completed: 5 V, positioning not completed: 0 V)
09 Reserved (Do not use.)
0A Torque feedforward (1 V/100% rated torque)
0B Active gain (1st gain: 1 V, 2nd gain: 2 V)
0C Completion of position reference (completed: 5 V not completed: 0 V)
0D Reserved (Do not use.)
Reserved (Do not change.)
Reserved (Do not change.)
0000 to
7121
− 4000 After restart Setup −
Pn008
Lowered Battery Voltage Alarm/Warning Selection
0
1
Outputs alarm (A.830) for lowered battery voltage.
Outputs warning (A.930) for lowered battery voltage.
Reserved (Do not change.)
Reserved (Do not change.)
5.1.3
−
Reference
Section
4.7.3
Warning Detection Selection
0
1
Detects warning.
Does not detect warning.
Reference
Section
8.2.1
9
9-5
9-6
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Size Name
2
Application Function
Select Switch 9
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
0000 to
0111
Units
−
Factory
Setting
When
Enabled
0010 After restart
Reserved (Do not change.)
Pn009
Pn00B
Current Control Method Selection
0
1
Current control method 1
Current control method 2
Speed Detection Method Selection
0
1
Speed detection 1
Speed detection 2
Reserved (Do not change.)
2
Application Function
Select Switch B
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1111
−
Parameter Display Selection
0
1
Setup parameters
All parameters
0000 After restart
Alarm Gr.2 Stop Method Selection
0
1
Stops the motor by setting the speed reference to "0".
Stops the motor by coasting.
Reserved (Do not change.)
Reserved (Do not change.)
Tuning
Setup
−
−
−
Reference
Section
5.8.3
Reference
Section
5.8.5
−
Reference
Section
2.5.1
Reference
Section
4.3.5
9.1 List of Parameters
(cont’d)
Pn100
Pn101
Pn102
Pn103
Pn104
Pn105
Pn106
Pn109
Pn10A
Parameter
No.
Size Name
2
Application Function
Select Switch C
4th 3rd 2nd 1st digit digit digit digit n.
Pn00C
Setting
Range
0000 to
0111
Units
−
Factory
Setting
When
Enabled
0000 After restart
Selection of Test without a Motor
0
1
Disables test without a motor.
Enables test without a motor.
Encoder Resolution for Test without a Motor
0
1
13 bits
20 bits
Encoder Type for Test without a Motor
0 Incremental encoder
1 Absolute encoder
Reserved (Do not change.)
Pn00D
2
Application Function
Select Switch D
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1001
−
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
0000 Immediately
Overtravel Warning Detection Selection
0
1
Does not detect overtravel warning.
Detects overtravel warning.
2 Speed Loop Gain
2
Speed Loop Integral Time
Constant
2 Position Loop Gain
2 Moment of Inertia Ratio
2 2nd Speed Loop Gain
2
2nd Speed Loop Integral
Time Constant
2 2nd Position Loop Gain
2 Feedforward Gain
2
Feedforward Filter Time
Constant
10 to 20000 0.1 Hz
10 to 20000 0.1/s
0 to 20000 1%
10 to 20000 0.1 Hz
400
15 to 51200 0.01 ms 2000 Immediately
400
100
400
Immediately
Immediately
Immediately
Immediately
15 to 51200 0.01 ms 2000 Immediately
10 to 20000 0.1/s
0 to 100 1%
0 to 6400 0.01 ms
400
0
0
Immediately
Immediately
Immediately
Setup
Setup
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
−
−
4.5
–
−
−
−
−
−
−
−
−
−
Reference
Section
4.3.2
5.8.1
5.8.1
5.8.1
5.8.1
5.8.1
5.8.1
5.8.1
5.9.1
5.9.1
9
9-7
9 Appendix
9.1.2 Parameters
9-8
Pn10C
Pn10D
Pn10E
Pn10F
Pn11F
Pn121
Pn122
Pn123
Pn124
Pn125
Pn131
Pn132
Pn135
Pn136
(cont’d)
Parameter
No.
Size Name
2
Application Function for
Gain Select Switch
4th 3rd 2nd 1st digit digit digit digit n.
Pn10B
Setting
Range
0000 to
5334
Units
−
Factory
Setting
0000
When
Enabled
−
Mode Switch Selection
0
1
2
3
4
Uses internal torque reference as the condition
(Level setting: Pn10C).
Uses speed reference as the condition
(Level setting: Pn10D).
Uses acceleration as the condition
(Level setting: Pn10E).
Uses position error as the condition
(Level setting: Pn10F).
No mode switch function available.
−
When
Enabled
Immediately
−
Classification
Reference
Section
Setup
−
5.9.2
When
Enabled
Classification
Reference
Section
Speed Loop Control Method
0 PI control
1 I-P control
2 and 3 Reserved (Do not use.)
Reserved (Do not change.)
Reserved (Do not change.)
After restart Setup −
2
2
2
Mode Switch
(torque reference)
Mode Switch
(speed reference)
Mode Switch
(acceleration)
2
Mode Switch
(position error)
2
2
2
Position Integral Time
Constant
Friction Compensation
Gain
2nd Gain for Friction
Compensation
2
2
Friction Compensation
Coefficient
Friction Compensation
Frequency Correction
2
Friction Compensation
Gain Correction
2 Gain Switching Time 1
2 Gain Switching Time 2
2
Gain Switching
Waiting Time 1
2
Gain Switching
Waiting Time 2
0 to 800 1% 200
0 to 10000 1 min
-1 s
-1
/
0 to 10000
1 reference unit
0 to 50000 0.1 ms
10 to 1000 1%
0
0
0
0
100
10 to 1000
0 to 100
-10000 to
10000
1 to 1000
0 to 65535
1%
1%
0.1 Hz
1%
0 to 65535 1 ms
0 to 65535 1 ms
0 to 65535 1 ms
1 ms
Immediately
Immediately
Immediately
Immediately
100
0
Immediately
Immediately
Immediately
Immediately
0 Immediately
100 Immediately
0
0
0
Immediately
Immediately
Immediately
0 Immediately
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
5.9.2
5.9.2
5.9.2
5.9.4
5.8.2
5.8.2
5.8.2
5.8.2
5.8.2
5.8.1
5.8.1
5.8.1
5.8.1
−
−
−
−
−
−
−
−
−
−
−
−
−
− 5.9.2
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
2
Automatic Gain
Changeover Related
Switch 1
4th 3rd 2nd 1st digit digit digit digit n.
Pn139
Pn13D
Pn140
Pn141
Pn142
Setting
Range
0000 to
0052
Units
−
Factory
Setting
0000
When
Enabled
Immediately
Tuning − 5.8.1
Gain Switching Selection Switch
0 Manual gain switching
Changes gain manually using G-SEL of the servo command output signals (SVCMD_IO).
1
2
Reserved (Do not use.)
Automatic gain switching pattern 1
Changes automatically 1st gain to 2nd gain when the switching condition A is satisfied.
Changes automatically 2nd gain to 1st gain when the switching condition A is not satisfied.
Gain Switching Condition A
0
3
4
5
1
2
Positioning completion signal (/COIN) ON
Positioning completion signal (/COIN) OFF
Positioning near signal (/NEAR) ON
Positioning near signal (/NEAR) OFF
Position reference filter output = 0 and position reference input OFF
Position reference input ON
Reserved (Do not change.)
Reserved (Do not change.)
2 Current Gain Level
2
Model Following Control
Related Switch
4th 3rd 2nd 1st digit digit digit digit n.
100 to 2000
0000 to
1121
1%
−
2000 Immediately
0100 Immediately
Model Following Control Selection
0
1
Does not use model following control.
Uses model following control.
Tuning
Tuning
Vibration Suppression Selection
0 Does not perform vibration suppression.
1
2
Performs vibration suppression over the specified frequency.
Performs vibration suppression over two different kinds of frequencies.
−
−
5.8.4
−
Vibration Suppression Adjustment Selection
0
1
Does not adjust vibration suppression automatically using utility function.
Adjusts vibration suppression automatically using utility function.
Selection of Speed Feedforward (VFF) / Torque Feedforward (TFF)
0
1
Does not use model following control and speed/torque feedforward together.
Uses model following control and speed/torque feedforward together.
2
2
Model Following Control
Gain
Model Following Control
Gain Compensation
10 to 20000 0.1/s
500 to 2000 0.1%
500
1000
Immediately
Immediately
Tuning
Tuning
−
−
Reference
Section
5.3.1, 5.4.1,
5.5.1, 5.7.1
Reference
Section
5.3.1, 5.4.1
−
−
9
9-9
9-10
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Pn143
Pn144
Pn145
Pn146
Pn147
Pn148
Pn149
Pn14A
Pn14B
Size
2
2
2
2
2
2
2
2
2
2
Name
Setting
Range
Units
Model Following Control
Bias
(Forward Direction)
Model Following Control
Bias
(Reverse Direction)
Vibration Suppression 1
Frequency A
Vibration Suppression 1
Frequency B
Model Following Control
Speed Feedforward Compensation
2nd Model Following
Control Gain
2nd Model Following
Control Gain Compensation
Vibration Suppression 2
Frequency
Vibration Suppression 2
Compensation
0 to 10000
0 to 10000
10 to 2500
10 to 2500
0 to 10000
0.1%
0.1%
0.1 Hz
0.1 Hz
0.1%
10 to 20000 0.1/s
500 to 2000 0.1%
10 to 2000
10 to 1000
0.1 Hz
1%
Control Related Switch
0000 to
0011
-
Factory
Setting
1000
1000
500
700
1000
500
1000
800
100
0011
When
Enabled
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
After restart
4th 3rd 2nd 1st digit digit digit digit n.
Pn14F
Model Following Control Type Selection
0 Model Following Control 1
1 Model Following Control 2
Tuning-less Type Selection
0 Tuning-less type 1
1 Tuning-less type 2
Reserved (Do not change.)
Reserved (Do not change.)
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
−
−
−
−
−
−
−
−
−
−
Reference
Section
5.3.1,
5.4.1,
5.5.1
Reference
Section
5.2.2
−
−
−
−
−
−
−
−
−
–
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
2
Anti-Resonance Control
Related Switch
4th 3rd 2nd 1st digit digit digit digit n.
Pn160
Setting
Range
0000 to
0011
Units
−
Factory
Setting
When
Enabled
0010 Immediately
Anti-Resonance Control Selection
0 Does not use anti-resonance control.
1 Uses anti-resonance control.
Tuning
Anti-Resonance Control Adjustment Selection
0 Does not adjust anti-resonance control automatically using utility function.
1 Adjusts anti-resonance control automatically using utility function.
Reserved (Do not change.)
Reserved (Do not change.)
−
Pn161
Pn162
Pn163
Pn164
Pn165
Pn170
Pn205
5.3.1, 5.4.1,
5.5.1, 5.7.1
2
2
2
2
2
2
Anti-Resonance Frequency
Anti-Resonance Gain
Compensation
Anti-Resonance Damping
Gain
Anti-Resonance Filter
Time Constant 1 Compensation
Anti-Resonance Filter
Time Constant 2 Compensation
Tuning-less Function
Related Switch
4th 3rd 2nd 1st digit digit digit digit n.
10 to 20000 0.1 Hz 1000 Immediately
1 to 1000
0 to 300
-1000 to
1000
-1000 to
1000
0000 to
2411
1%
1%
0.01 ms
0.01 ms
−
100 Immediately
0
0
0
1401
Immediately
Immediately
Immediately
−
Tuning-less Function Selection
0
1
Disables tuning-less function.
Enables tuning-less function.
Tuning
Tuning
Tuning
Tuning
Tuning
–
−
−
−
−
−
−
−
−
−
−
−
–
When
Enabled
After restart
Classification
Setup
Reference
Section
5.2
Control Method during Speed Control
0 Uses as speed control.
1
Uses as speed control and uses the host controller for position control.
When
Enabled
After restart
Classification
Setup
Reference
Section
5.2
Tuning-less Tuning Level
0 to 4 Sets tuning-less tuning level.
When
Enabled
Immediately
Classification
Setup
Reference
Section
5.2
2 Multiturn Limit Setting
Tuning-less Load Level
0 to 2 Sets tuning-less load level.
0 to 65535 1 rev 65535 After restart
When
Enabled
Immediately
Classification
Setup
Reference
Section
5.2
Setup − 4.7.5
9
9-11
9 Appendix
9.1.2 Parameters
9-12
Pn233
Pn281
Pn304
Pn305
Pn306
(cont’d)
Parameter
No.
Size Name
2
Position Control Function
Switch
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
0000 to
2210
Units
−
Reserved (Do not change.)
Factory
Setting
When
Enabled
0010 After restart
Pn207
Setup − −
Reserved (Do not change.)
Reserved (Do not change.)
MECHA
/COIN Output Timing
0
1
2
Outputs when the position error absolute value is the same or less than the positioning completed width (Pn522).
Outputs when the position error absolute value is the same or less than the positioning completed width (Pn522), and the reference after position reference filtering is 0.
Outputs when the position error absolute value is the same or less than the positioning completed width (Pn522), and the position reference input is 0.
Reference
Section
4.8.6
Pn20A
Pn20E
Pn210
Pn22A
Pn230
4 Reserved (Do not change.)
4
Electronic Gear Ratio
(Numerator)
4
Electronic Gear Ratio
(Denominator)
2 Reserved (Do not change.)
2
Position Control
Expanded Function
Switch
−
1 to
1073741824
1 to
1073741824
−
0000 to
0001
4th 3rd 2nd 1st digit digit digit digit n.
1
−
−
1
–
32768
1
1
0000
0000
−
After restart
After restart
−
After reset
Backlash Compensation Direction
0
1
Compensates with a reference in the forward direction.
Compensates with a reference in the reverse direction.
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
−
Setup
Setup
−
Setup
−
−
−
−
–
−
4.4.3
4.4.3
−
5.8.6
Pn231 4
Backlash Compensation
Value
-50000 to
50000
0.1 reference unit
2
Backlash Compensation
Time Constant
2 Reserved (Do not change.)
2 JOG Speed
2
2
Soft Start Acceleration
Time
Soft Start Deceleration
Time
0 to 65536
−
0.01 ms
−
0 to 10000 1 min -1
0 to 10000 1 ms
0 to 10000 1 ms
0
0
20
500
0
0
Immediately
Immediately
−
Immediately
Immediately
Immediately
Setup
Setup
−
Setup
Setup
Setup
–
–
−
−
−
−
5.8.6
5.8.6
−
6.3
−
−
9.1 List of Parameters
(cont’d)
Pn401
Pn402
Pn403
Pn404
Pn405
Pn406
Pn407
Parameter
No.
Size Name
2
Vibration Detection
Switch
4th 3rd 2nd 1st digit digit digit digit n.
Pn310
Pn311
Pn312
Pn324
Setting
Range
0000 to
0002
Units
−
Factory
Setting
When
Enabled
0000 Immediately
Vibration Detection Selection
0
1
2
Does not detect vibration.
Outputs warning (A.911) when vibration is detected.
Outputs alarm (A.520) when vibration is detected.
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
2
Vibration Detection
Sensibility
50 to 500 1%
2 Vibration Detection Level 0 to 5000 1 min
-1
2
Moment of Inertia Calculating Start Level
0 to 20000 1%
2
Torque Reference Filter
Time Constant
0 to 65535
0.01 ms
0 to 800
0 to 800
1%
1%
2 Forward Torque Limit
2 Reverse Torque Limit
2
2
Forward External Torque
Limit
Reverse External Torque
Limit
2 Emergency Stop Torque
2
Speed Limit during
Torque Control
0 to 800
0 to 800
0 to 800
1%
1%
1%
0 to 10000 1 min -1
100
50
Immediately
Immediately
300 Immediately
100
800
800
100
Immediately
Immediately
Immediately
Immediately
100 Immediately
800 Immediately
10000 Immediately
Setup
Tuning
Tuning
Setup
Tuning
Setup
Setup
Setup
Setup
Setup
Setup
− −
Reference
Section
6.15
6.15
6.15
5.3.2
5.9.3
4.6.1
4.6.1
4.6.2
4.6.2
4.3.2
4.8.8
−
−
−
−
−
−
−
−
−
−
9
9-13
9-14
9 Appendix
9.1.2 Parameters
Pn409
Pn40A
Pn40B
Pn40C
Pn40D
Pn40E
Pn40F
Pn410
(cont’d)
Parameter
No.
Size Name
2
Torque Related Function
Switch
4th 3rd 2nd 1st digit digit digit digit n.
Pn408
Setting
Range
0000 to
1111
Units
−
Factory
Setting
0000
When
Enabled
− − − −
1st Step Notch Filter Selection
0
1
N/A
Uses 1st step notch filter for torque reference.
When
Enabled
Immediately
Classification
Setup
Reference
Section
5.9.3
Speed Limit Selection
0
1
Uses the smaller of the maximum motor speed and the value of Pn407 as the speed limit value.
Uses the smaller of the overspeed detection speed and the value of Pn407 as the speed limit value.
When
Enabled
After restart
Classification
Setup
Reference
Section
4.8.8
2nd Step Notch Filter Selection
0
1
N/A
Uses 2nd step notch filter for torque reference.
When
Enabled
Immediately
Classification
Setup
Reference
Section
5.9.3
Friction Compensation Function Selection
0
1
Disables friction compensation function.
Enables friction compensation function.
When
Enabled
Immediately
Classification
Setup
Reference
Section
5.8.2
Pn412
Pn424
Pn425
Pn456
2 1st Notch Filter Frequency 50 to 5000 1 Hz
2 1st Notch Filter Q Value
2 1st Notch Filter Depth
50 to 1000
0 to 1000
0.01
0.001
2
2nd Notch Filter Frequency
50 to 5000 1 Hz
2 2nd Notch Filter Q Value 50 to 1000 0.01
0 to 1000 0.001
2 2nd Notch Filter Depth
2
2nd Step 2nd Torque Reference Filter Frequency
100 to 5000 1 Hz
2
2
2nd Step 2nd Torque Reference Filter Q Value
1st Step 2nd Torque Reference Filter Time Constant
2 Reserved (Do not change.)
2 Reserved (Do not change.)
2
Sweep Torque Reference
Amplitude
50 to 100
0 to 65535
−
−
1 to 800
0.01
0.01 ms
−
−
1%
5000
70
0
5000
70
0
5000
50
100
50
100
15
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
−
−
Immediately
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
Tuning
−
−
Tuning
−
−
−
−
−
−
−
−
−
−
−
−
5.9.3
5.9.3
5.9.3
5.9.3
5.9.3
5.9.3
5.9.3
5.9.3
5.8.1
−
−
6.18
9.1 List of Parameters
(cont’d)
Pn501
Pn502
Pn503
Pn506
Pn507
Parameter
No.
Size
Pn460
Name
2
Notch Filter Adjustment
Switch
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
0000 to
0101
Units
Factory
Setting
When
Enabled
− 0101 Immediately Tuning
Notch Filter Adjustment Selection 1
0
1
Does not adjust 1st step notch filter automatically using utility function.
Adjust 1st step notch filter automatically using utility function.
Reserved (Do not change.)
Notch Filter Adjustment Selection 2
0 Does not adjust 2nd step notch filter automatically using utility function.
1 Adjust 2nd step notch filter automatically using utility function.
Reserved (Do not change.)
Pn508
Pn509
2 Zero Clamp Level 0 to 10000 1 min -1
2 Rotation Detection Level 1 to 10000 1 min -1
2
2
Speed Coincidence Signal
Output Width
Brake Reference - Servo
OFF Delay Time
0 to 100
0 to 50
1 min
-1
10 ms
2
2
Brake Reference Output
Speed Level
Waiting Time for Brake
Signal When Motor Running
2 Reserved (Do not change.)
2 Input Signal Selection 1
0 to 10000 1 min
10 to 100
−
0000 to
FFF1
−
-1
10 ms
−
4th 3rd 2nd 1st digit digit digit digit n.
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
10
20
10
Immediately
Immediately
Immediately
0 Immediately
100 Immediately
50 Immediately
20 −
1881 After restart
Setup
Setup
Setup
Setup
Setup
Setup
−
Setup
Pn50A
P-OT Signal Mapping (Forward run prohibited when OFF (H-level))
0
1 Forward run allowed when CN1-3 input signal is ON (L-level).
2 to 6 Forward run allowed when CN1-8 input signal is ON (L-level).
7
8
Forward run allowed when CN1-7 input signal is ON (L-level).
Forward run prohibited.
Forward run allowed.
9
A
Forward run allowed when CN1-7 input signal is OFF (H-level).
Forward run allowed when CN1-3 input signal is OFF (H-level).
B to F Forward run allowed when CN1-8 input signal is OFF (H-level).
−
−
−
−
−
−
−
−
−
5.2.1,
5.3.1,
5.5.1
Reference
Section
4.3.2
−
4.8.3
4.8.5
4.3.4
4.3.4
4.3.4
−
−
9
9-15
9 Appendix
9.1.2 Parameters
(cont’d)
9-16
Parameter
No.
Size Name
2 Input Signal Selection 2
4th 3rd 2nd 1st digit digit digit digit n.
Pn50B
Setting
Range
0000 to
FFFF
Units
−
Factory
Setting
When
Enabled
8882 After restart Setup
N-OT Signal Mapping (Reverse run prohibited when OFF (H-level))
0
1 Reverse run allowed when CN1-3 input signal is ON (L-level).
2 to 6 Reverse run allowed when CN1-8 input signal is ON (L-level).
7
8
Reverse run allowed when CN1-7 input signal is ON (L-level).
Forward run prohibited.
Forward run allowed.
9
A
Reverse run allowed when CN1-7 input signal is OFF (H-level).
Reverse run allowed when CN1-3 input signal is OFF (H-level).
B to F Reverse run allowed when CN1-8 input signal is OFF (H-level).
Reserved (Do not change.)
/P-CL Signal Mapping (Torque Limit when ON (L-level))
0
1 ON when CN1-3 input signal is ON (L-level)
2 to 6 ON when CN1-8 input signal is ON (L-level)
7
8
ON when CN1-7 input signal is ON (L-level)
Always active (fixed).
Not active (fixed).
9
A
OFF when CN1-7 input signal is OFF (H-level)
OFF when CN1-3 input signal is OFF (H-level)
B to F OFF when CN1-8 input signal is OFF (H-level)
/N-CL Signal Mapping (Torque Limit when ON (L-level))
0 to F Same as /P-CL signal mapping
Pn50E
2 Output Signal Selection 1
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
3333
− 0000 After restart
Positioning Completion Signal Mapping (/COIN)
2
3
0
1
Disabled (the above signal is not used.)
Outputs the signal from CN1-11 output terminal.
Outputs the signal from CN1-10 output terminal.
Outputs the signal from CN1-9 output terminal.
Speed Coincidence Detection Signal Mapping (/V-CMP)
0 to 3 Same as /COIN Signal Mapping.
Setup
Servomotor Rotation Detection Signal Mapping (/TGON)
0 to 3 Same as /COIN Signal Mapping.
Servo Ready Signal Mapping (/S-RDY)
0 to 3 Same as /COIN Signal Mapping.
– –
Reference
Section
4.3.2
Reference
Section
4.6.2
−
Reference
Section
4.6.2
−
Reference
Section
4.8.6
Reference
Section
4.8.5
Reference
Section
4.8.3
Reference
Section
4.8.4
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
2 Output Signal Selection 2
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
0000 to
3333
Units
−
Factory
Setting
When
Enabled
0100 After restart
Torque Limit Detection Signal Mapping (/CLT)
0
1
2
3
Disabled (the above signal is not used.)
Outputs the signal from CN1-11 output terminal.
Outputs the signal from CN1-10 output terminal.
Outputs the signal from CN1-9 output terminal.
Pn50F
Speed Limit Detection Signal Mapping (/VLT)
0 to 3 Same as /CLT Signal Mapping.
Pn510
Brake Signal Mapping (/BK)
0 to 3 Same as /CLT Signal Mapping.
Warning Signal Mapping (/WARN)
0 to 3 Same as /CLT Signal Mapping.
2 Output Signal Selection 3
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
0333
− 0000 After restart
Near Signal Mapping (/NEAR)
2
3
0
1
Disabled (the above signal is not used.)
Outputs the signal from CN1-11 terminal.
Outputs the signal from CN1-10 terminal.
Outputs the signal from CN1-9 terminal.
Reserved (Do not change.)
MECHA
Reserved (Do not change.)
Reserved (Do not change.)
Setup
Setup
−
Reference
Section
4.8.7
−
Reference
Section
4.6.3
−
Reference
Section
4.8.8
Reference
Section
4.3.4
Reference
Section
4.8.2
−
9
9-17
9-18
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Size Name
2 Input Signal Selection 5
4th 3rd 2nd 1st digit digit digit digit n.
Pn511
Setting
Range
0000 to
FFFF
Units
−
Factory
Setting
When
Enabled
8880 After restart
Homing Deceleration Switch Signal Mapping (/DEC)
0 Inputs the signal from CN1-7 input terminal.
1
2 to 6 Inputs the signal from CN1-8 input terminal.
7 Always active (fixed).
8
9
Inputs the signal from CN1-3 input terminal.
Not active (fixed).
Inputs the reversal signal from CN1-7 input terminal.
A Inputs the reversal signal from CN1-3 input terminal.
B to F Inputs the reversal signal from CN1-8 input terminal.
External Latch Signal Mapping (/EXT1)
0 to 6 Inputs the reversal signal from CN1-7 input terminal.
7
8
Always active (fixed).
Not active (fixed).
9 to F Inputs the signal from CN1-7 input terminal.
Reserved (Do not change.)
Reserved (Do not change.)
Pn512
Pn517
Pn51B
Pn51E
Pn520
2
Output Signal Inverse Setting
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
0111
− 0000 After restart
Output Signal Inversion for CN1-11 Terminal
0 Does not inverse outputs.
1 Inverses outputs.
Output Signal Inversion for CN1-10 Terminal
0
1
Does not inverse outputs.
Inverses outputs.
Output Signal Inversion for CN1-9 Terminal
0
1
Does not inverse outputs.
Inverses outputs.
Reserved (Do not change.)
2
4
Reserved (Do not change.)
4 Reserved (Do not change.)
2
Excessive Position Error
Warning Level
–
–
10 to 100
Excessive Position Error
Alarm Level
1 to
1073741823
–
–
1%
1 reference unit
0000
1000
100
–
–
Immediately
5242880 Immediately
Setup
Setup
–
–
Setup
Setup
− 3.3.1
− 3.3.2
–
–
–
–
–
–
8.2.1
5.1.4,
8.1.1
9.1 List of Parameters
(cont’d)
Parameter
No.
Size
Pn522
Pn524
Pn526
Pn528
Pn529
Pn52A
Pn52B
Pn52C
Pn52D
Pn52F
Name
Setting
Range
Units
4
4
Positioning Completed
Width
4 NEAR Signal Width
0 to
1073741824
1 to
1073741824
Excessive Position Error
Alarm Level at Servo ON
1 to
1073741823
2
2
Excessive Position Error
Warning Level at Servo
ON
Speed Limit Level at
Servo ON
2 Reserved (Do not change.)
2 Overload Warning Level
2
Derating of Base Current at Detecting Overload of
Motor
2 Reserved (Do not change.)
2 Reserved (Do not change.)
2
Program JOG Operation
Related Switch
4th 3rd 2nd 1st digit digit digit digit n.
10 to 100 1%
0 to 10000 1 min -1
–
1 to 100
–
1%
10 to 100
–
–
0000 to
0005
1%
−
−
−
1 reference unit
1 reference unit
1 reference unit
Factory
Setting
7
When
Enabled
Immediately
1073741824 Immediately
5242880 Immediately
100 Immediately
10000 Immediately
20
20
100
50
0FFF
–
Immediately
After restart
–
–
0000 Immediately
Pn530
Setup
Setup
Setup
Setup
Setup
–
Setup
Setup
–
–
Setup
–
–
–
–
–
–
–
–
–
−
−
Program JOG Operation Switch
0 (Waiting time Pn535 → Forward movement Pn531) × Number of movements Pn536
1 (Waiting time Pn535 → Reverse movement Pn531) × Number of movements Pn536
2 (Waiting time Pn535 → Forward movement Pn531) × Number of movements Pn536
(Waiting time Pn535 → Reverse movement Pn531) × Number of movements Pn536
3 (Waiting time Pn535 → Reverse movement Pn531) × Number of movements Pn536
(Waiting time Pn535 → Forward movement Pn531) × Number of movements Pn536
4 (Waiting time Pn535 → Forward movement Pn531 → Waiting time Pn535
Reverse movement Pn531) × Number of movements Pn536
→
5 (Waiting time Pn535 → Reverse movement Pn531 → Waiting time Pn535
Forward movement Pn531) × Number of movements Pn536
→
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
Pn531
Pn533
Pn534
4
2
2
Program JOG Movement
Distance
Program JOG Movement
Speed
Program JOG Acceleration/Deceleration Time
1 to
1073741824
1 to 10000 1 min -1
2 to 10000
1 reference unit
1 ms
32768 Immediately
500
100
Immediately
Immediately
Setup
Setup
Setup
−
−
−
4.8.6
4.8.7
5.1.4
5.1.4
6.5
6.5
6.5
5.1.4
–
4.3.6
4.3.6
–
–
6.5
9
9-19
9-20
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Size
Pn535
Pn536
Pn550
Pn551
Pn552
Pn553
Pn560
Pn561
Pn600
Pn601
Name
2
2
2
2
2
2
2
Program JOG Waiting
Time
Number of Times of Program JOG Movement
Analog Monitor 1 Offset
Voltage
Analog Monitor 2 Offset
Voltage
Analog Monitor Magnification ( × 1)
Analog Monitor Magnification ( × 2)
Remained Vibration
Detection Width
2
Overshoot Detection
Level
2 Reserved (Do not change.)
2 Reserved (Do not change.)
Setting
Range
0 to 10000 1 ms
0 to 1000
-10000 to
10000
-10000 to
10000
-10000 to
10000
-10000 to
10000
1 to 3000
0 to 100
–
–
Units
1 time
0.1 V
0.1 V
×
×
0.01
0.01
0.1%
1%
–
–
Factory
Setting
100
When
Enabled
Immediately
1
0
0
100
100
400
100
0
0
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
–
–
Setup
Setup
Setup
Setup
–
–
Setup
Setup
Setup
Setup
5.1.3
5.1.3
5.7.1
5.3.1,
5.4.1
–
–
6.5
6.5
5.1.3
5.1.3
−
−
−
−
−
−
−
−
−
−
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
2 Communications Control
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
–
Units
–
Factory
Setting
When
Enabled
1040 Immediately Setup −
MECHATROLINKIII Communications Check Mask (for debug)
0
1
2
3
No mask
Ignores MECHATROLINK communications error (A.E60).
Ignores WDT error (A.E50).
Ignores both MECHATROLINK communications error (A.E60) and WDT error (A.E50).
Pn800
M-III
–
8
9
A
B
Warning Check Mask
0
1
6
7
2
3
4
5
No mask
Ignores data setting warning (A.94
Ignores command warning (A.95
warning (A.96
).
Ignores data setting warning (A.94
).
).
Ignores both data setting warning (A.94
Ignores communications warning (A.96
Ignores both data setting warning (A.94
Ignores both command warning (A.95
) and command warning (A.95
).
).
) and communications warning (A.96
) and communications warning (A.96
), command warning (A.95
).
).
) and communications
C
D
Ignores command warning 7 (A.97A) and data clamp (A.97B).
Ignores data setting warning (A.94
Ignores command warning (A.95
and data clamp (A.97B).
), command warning 7 (A.97A) and data clamp (A.97B).
) and command warning 7 (A.97A) and data clamp (A.97B).
Ignores data setting warning (A.94
), command warning (A.95
), command warning 7 (A.97A)
Ignores communications warning (A.96
), command warning 7 (A.97A) and data clamp (A.97B).
E
Ignores data setting warning (A.94
), communications warning (A.96
), command warning 7
(A.97A) and data clamp (A.97B).
Ignores command warning (A.95
), communications warning (A.96
), command warning 7
(A.97A) and data clamp (A.97B).
F Ignores data setting warning (A.94
), command warning (A.95
), communications warning
(A.96
), command warning 7 (A.97A) and data clamp (A.97B).
Reserved (Do not change.)
Automatic warning-clear (for debug)
*2
0 No warning-clear (for debug)
1 Automatic warning-clear (for MECHATROLINK-III specifications)
∗2.
This parameter is enabled only for MECHATROLINK-III standard servo profile.
9
9-21
9 Appendix
9.1.2 Parameters
9-22
(cont’d)
Parameter
No.
Size Name
2
Application Function
Select 6
(Software LS)
4th 3rd 2nd 1st digit digit digit digit n.
Pn801
Setting
Range
–
Units
–
Factory
Setting
When
Enabled
0003 Immediately
Software Limit Function
0
1
2
3
Enables forward and reverse software limit.
Disables forward software limit.
Disables reverse software limit.
Disables software limit in both directions.
Reserved (Do not change.)
Software Limit for Reference
0
1
Disables software limit for reference.
Enables software limit for reference.
Reserved (Do not change.)
Pn803
Pn804
Pn806
Pn808
Pn80A
Pn80B
Pn80C
Pn80D
Pn80E
Setup – 4.3.3
2 Origin Range
4 Forward Software Limit
4 Reverse Software Limit
4
2
2
2
2
Absolute Encoder Origin
Offset
1st Linear Acceleration
Constant
2nd Linear Acceleration
Constant
Acceleration Constant
Switching Speed
1st Linear Deceleration
Constant
0 to 250
-1073741823 to
1073741823
-1073741823 to
1073741823
-1073741823 to
1073741823
1 to 65535
1 to 65535
0 to 65535
1 to 65535
10000 reference unit/s
2
10000 reference unit/s
2
100 reference unit/s
10000 reference unit/s
2
1 reference unit
1 reference unit
1 reference unit
1 reference unit
10 Immediately
1073741823 Immediately
-1073741823 Immediately
0
100
100
0
100
Immediately
*3
Immediately
*4
Immediately
*4
Immediately
*4
Immediately
*4
Setup
Setup
Setup
Setup
Setup
Setup
Setup
Setup
–
–
–
–
–
–
–
–
*1
4.3.3
4.3.3
4.7.7
*1
*1
*1
*1
2
2nd Linear Deceleration
Constant
1 to 65535
10000 reference unit/s
2
100
Immediately
*4
Setup – *1
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
(Manual
∗3.
Available after the SENS_ON command is input.
∗4.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
9.1 List of Parameters
(cont’d)
Parameter
No.
Size
Pn80F
Pn810
Pn811
Pn812
Pn814
Pn816
2
2
Name
Deceleration Constant
Switching Speed
Exponential Function
Acceleration/Deceleration Bias
Exponential Function
Acceleration/Deceleration Time Constant
Setting
Range
Units
0 to 65535
0 to 65535
100 reference unit/s
100 reference unit/s
Factory
Setting
0
0
When
Enabled
Immediately
*4
Immediately
*5
2 0 to 5100 0.1 ms
2 Movement Average Time 0 to 5100 0.1 ms
0
0
Immediately
*5
Immediately
*5
4
2
Final Travel Distance for
External Positioning
Homing Mode Setting
-1073741823 to
1073741823
1 reference unit
– –
4th 3rd 2nd 1st digit digit digit digit n.
Software Limit Function
0
1
Forward
Reverse
100 Immediately
0000 Immediately
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
Pn817
*7
Pn818
*8
Pn819
Setup
Setup
Setup
Setup
Setup
Setup
–
–
–
–
–
M2
*6
*1
*1
*1
*1
*1
–
2
2
Homing Approach Speed
(Homing Approach Speed 1)
Homing Creep Speed
(Homing Approach Speed 2)
0 to 65535
0 to 65535
100 reference unit/s
100 reference unit/s
50
5
Immediately
*4
Immediately
*4
Setup
Setup
–
–
*1
*1
4
Final Travel Distance for
Homing
-1073741823 to
1073741823
1 reference unit
100 Immediately Setup – *1
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
(Manual
∗4.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
∗5.
The settings are updated only if the sending of the reference has been stopped (DEN is set to 1).
∗6.
This parameter is enabled only for MECHATROLINK-II-compatible profile.
∗7.
The set value of Pn842 is valid when the set value of Pn817 is 0. Software version 0023 or higher is required to use
Pn842.
∗8.
The set value of Pn844 is valid when the set value of Pn818 is 0. Software version 0023 or higher is required to use
Pn844.
9
9-23
9-24
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Size Name
2
Input Signal Monitor
Selection
4th 3rd 2nd 1st digit digit digit digit n.
Pn81E
Setting
Range
–
Units
–
Factory
Setting
When
Enabled
0000 Immediately
IO12 Signal Mapping
0 No mapping
Monitors CN1-13 input terminal.
1
2
3
4
5
Monitors CN1-7 input terminal.
Monitors CN1-8 input terminal.
Monitors CN1-9 input terminal.
Monitors CN1-10 input terminal.
6
7
Monitors CN1-11 input terminal.
Monitors CN1-12 input terminal.
IO13 Signal Mapping
0 to 7 Same as IO2 signal mapping.
IO14 Signal Mapping
0 to 7 Same as IO2 signal mapping.
IO15 Signal Mapping
0 to 7 Same as IO2 signal mapping.
Pn81F
2
Command Data Allocation
4th 3rd 2nd 1st digit digit digit digit n.
– – 0010 After restart
Option Field Allocation
0 Disables OPTION bit allocation.
1 Enables OPTION bit allocation.
Software Limit Function
0 Disables allocation.
1 Enables allocation.
Reserved (Do not change.)
Reserved (Do not change.)
Pn820
Pn822
Setup
Setup
M2
*6
M2
*6
–
*1
4
Forward Latching Allowable Area
-2147483648 to
2147483647
1 reference unit
0 Immediately Setup – *1
4
Reverse Latching Allowable Area
-2147483648 to
2147483647
1 reference unit
0 Immediately Setup – *1
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
∗6.
This parameter is enabled only for MECHATROLINK-II-compatible profile.
(Manual
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
Setting
Range
Units
Option Monitor 1 Selection
0000H
– –
Motor rotating speed
[1000000H/overspeed detection position]
Factory
Setting
When
Enabled
0002H Torque [1000000H/max. torque]
0004H
Position error (upper 32 bits) [reference unit]
0005H System reserved
0006H System reserved
Pn824 2
000CH System reserved
000DH System reserved
0010H Un000: Motor rotating speed [min -1
]
0011H Un001: Speed reference [min -1
]
0012H Un002: Torque reference [%]
0013H
Un003: Rotational angle 1 (encoder pulses from the phase-C origin: decimal display)
0014H Un004: Rotational angle 2 [deg]
0015H Un005: Input signal monitor
0016H Un006: Output signal monitor
0017H Un007: Input reference pulse speed [min -1
]
0018H Un008: Position error [reference unit]
0019H Un009: Accumulated load ratio [%]
001AH System reserved
001BH System reserved
0000 Immediately Setup
–
*1
001EH System reserved
001FH System reserved
0023H Primary multi-turn data [Rev]
0024H Primary incremental data [pulse]
0080H
Previous value of latched feedback position (LPOS) [encoder pulse]
M3
*2
0084H Continuous latch status
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
∗2.
This parameter is enabled only for MECHATROLINK-III standard servo profile.
(Manual
9
9-25
9-26
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Pn825
Pn827
Pn829
Size
2
2
2
2
Name
Linear Deceleration Constant 1 for Stopping
Setting
Range
Units
Option Monitor 2 Selection
0000H to
0084H
–
Same as Option Monitor 1 Selection.
–
1 to 65535
10000 reference unit/s
2
SVOFF Waiting Time
(SVOFF at deceleration to stop)
0 to 65535 10 ms
Option Field Allocation 1
0000 to
1E1E
–
Factory
Setting
0000
100
0
1813
When
Enabled
Immediately
Immediately
*4
Immediately
*4
After restart n.
4th digit
3rd digit
2nd digit
1st digit
0 to E
ACCFIL bit position
Pn82A
0
1
Disables ACCFIL bit allocation.
Enables ACCFIL bit allocation.
Pn82B
0 to E GSEL bit position
0
1
Disables GSEL bit allocation.
Enables GSEL bit allocation.
2 Option Field Allocation 2 n.
4th digit
3rd digit
2nd digit
1st digit
0000 to
1F1F
0 to F
V_PPI bit position
– 1D1C After restart
0
1
Disables V_PPI bit allocation.
Enables V_PPI bit allocation.
Setup
Setup
Setup
Setup
Setup
–
–
–
M2
*6
M2
*6
*1
*1
*1
–
–
0 to F P_PI_CLR bit position
0
1
Disables P_PI_CLR bit allocation.
Enables P_PI_CLR bit allocation.
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
(Manual
∗4.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
∗6.
This parameter is enabled only for MECHATROLINK-II-compatible profile.
9.1 List of Parameters
Parameter
No.
Size Name
2 Option Field Allocation 3 n.
4th digit
3rd digit
2nd digit
1st digit
Setting
Range
0000 to
1F1F
0 to F
P_CL bit position
Units
–
Factory
Setting
When
Enabled
1F1E After restart
Pn82C
0
1
Disables P_CL bit allocation.
Enables P_CL bit allocation.
Pn82D
Pn82E
0 to F N_CL bit position
0
1
Disables N_CL bit allocation.
Enables N_CL bit allocation.
2 Option Field Allocation 4 n.
4th digit
3rd digit
2nd digit
1st digit
0000 to
1F1C
–
0 to C
BANK_SEL1 bit position
0000 After restart
0
1
Disables BANK_SEL1 bit allocation.
Enables BANK_SEL1 bit allocation.
Setup
Setup
0 to F
LT_DISABLE bit position
0
1
Disables LT_DISABLE bit allocation.
Enables LT_DISABLE bit allocation.
2 Option Field Allocation 5
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1D1F
–
Reserved (Do not change.)
0000 After restart
Reserved (Do not change.)
0 to D OUT_SIGNAL bit position
0
1
Disables OUT_SIGNAL bit allocation.
Enables OUT_SIGNAL bit allocation.
∗6.
This parameter is enabled only for MECHATROLINK-II-compatible profile.
Setup
M2
*6
M2
*6
M2
*6
(cont’d)
–
–
–
9
9-27
9-28
9 Appendix
9.1.2 Parameters
(cont’d)
Parameter
No.
Size Name
2 Motion Setting
4th 3rd 2nd 1st digit digit digit digit n.
Pn833
Pn834
Pn836
Pn838
Pn83A
Pn83C
Pn83E
Pn840
Pn842
*7
Pn850
Pn851
Setting
Range
0000 to
0001
Units
–
Factory
Setting
When
Enabled
0000 After restart Setup – *1
Linear Accel/Decel Constant Selection
0 Uses Pn80A to Pn80F and Pn827. (Setting of Pn834 to Pn840 disabled)
1 Uses Pn834 to Pn840. (Setting of Pn80A to Pn80F and Pn827 disabled)
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
4
4
4
4
4
4
4
1st Linear Acceleration
Constant 2
2nd Linear Acceleration
Constant 2
Acceleration Constant
Switching Speed 2
1st Linear Deceleration
Constant 2
2nd Linear Deceleration
Constant 2
Deceleration Constant
Switching Speed 2
Linear Deceleration
Constant 2 for Stopping
1 to
20971520
1 to
20971520
0 to
2097152000
1 to
20971520
1 to
20971520
0 to
2097152000
1 to
20971520
10000 reference unit/s
2
10000 reference unit/s
1 reference unit/s
10000 reference unit/s
2
10000 reference unit/s
2
1 reference unit/s
10000 reference unit/s
2
100 reference unit/s
100
100
0
100
100
0
100
Immediately
*4
Immediately
*4
Immediately
*4
Immediately
*4
Immediately
*4
Immediately
*4
Immediately
*4
Setup
Setup
Setup
Setup
Setup
Setup
Setup
–
–
–
–
–
–
–
*1
*1
*1
*1
*1
*1
*1
4
Homing Approach Speed
(Homing Approach Speed
12)
0 to
20971520
0
Immediately
*4
Setup – *1
2 Latch Sequence Number 0 to 8 – 0 Immediately Setup – *1
2 Continuous Latch Count 0 to 255 – 0 Immediately Setup – *1
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
(Manual
∗4.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
∗7.
The set value of Pn842 is valid when the set value of Pn817 is 0. Software version 0023 or higher is required to use
Pn842.
9.1 List of Parameters
(cont’d)
Parameter
No.
Size Name
2
Latch Sequence Signal 1 to 4 Setting
4th 3rd 2nd 1st digit digit digit digit n.
Pn852
Setting
Range
0000 to
3333
Units
–
Factory
Setting
When
Enabled
0000 Immediately
Latch sequence 1 signal selection.
0 Phase C
EXT1 signal 1
2
3
Reserved (Do not use.)
Reserved (Do not use.)
Latch sequence 2 signal selection.
0 to 3 Same as latch sequence 1 signal selection.
Latch sequence 3 signal selection.
0 to 3 Same as latch sequence 1 signal selection.
Latch sequence 4 signal selection.
0 to 3 Same as latch sequence 1 signal selection.
Pn853
Setup – *1
2
Latch Sequence Signal 5 to 8 Setting
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
3333
– 0000 Immediately
Latch sequence 5 signal selection.
0 Phase C
EXT1 signal 1
2
3
Reserved (Do not use.)
Reserved (Do not use.)
Latch sequence 6 signal selection.
0 to 3 Same as latch sequence 5 signal selection.
Setup – *1
Latch sequence 7 signal selection.
0 to 3 Same as latch sequence 5 signal selection.
Latch sequence 8 signal selection.
0 to 3 Same as latch sequence 5 signal selection.
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
(Manual
9
9-29
9-30
9 Appendix
9.1.2 Parameters
Parameter
No.
Size Name
2
SVCMD_IO (input signal monitor) Allocation 1
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
0000 to
1717
Units
–
Factory
Setting
When
Enabled
0000 Immediately
0 to 7 Bit position of CN1-7 input terminal monitor
Pn860
0
1
Disables bit allocation for CN1-7 input terminal monitor.
Enables bit allocation for CN1-7 input terminal monitor.
Setup
0 to 7 Bit position of CN1-3 input terminal monitor
0
1
Disables bit allocation for CN1-3 input terminal monitor.
Enables bit allocation for CN1-3 input terminal monitor.
Pn861
2
SVCMD_IO (input signal monitor) Allocation 2
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1717
– 0000 Immediately
0 to 7 Bit position of CN1-8 input terminal monitor
0
1
Disables bit allocation for CN1-8 input terminal monitor.
Enables bit allocation for CN1-8 input terminal monitor.
Reserved (Do not change.)
Setup
Reserved (Do not change.)
Pn862
2
SVCMD_IO (input signal monitor) Allocation 3
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1717
–
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
0000 Immediately
∗2.
This parameter is enabled only for MECHATROLINK-III standard servo profile.
Setup
M3
*2
M3
*2
M3
*2
(cont’d)
–
–
–
9.1 List of Parameters
Parameter
No.
Size Name
2
SVCMD_IO (input signal monitor) Allocation 4
4th 3rd 2nd 1st digit digit digit digit n.
Pn863
Setting
Range
0000 to
1717
Units
–
Reserved (Do not change.)
Reserved (Do not change.)
Factory
Setting
When
Enabled
0000 Immediately
Reserved (Do not change.)
Reserved (Do not change.)
Pn864
Pn865
Pn866
Setup
2
SVCMD_IO (input signal monitor) Allocation 5
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1717
–
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
0000 Immediately
2
SVCMD_IO (input signal monitor) Allocation 6
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1717
–
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
0000 Immediately
Setup
Setup
2
SVCMD_IO (input signal monitor) Allocation 7
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1717
–
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
0000 Immediately
∗2.
This parameter is enabled only for MECHATROLINK-III standard servo profile.
Setup
M3
*2
M3
*2
M3
*2
M3
*2
(cont’d)
–
–
–
–
9
9-31
9 Appendix
9.1.2 Parameters
9-32
Parameter
No.
Size Name
2
SVCMD_IO
(output signal monitor)
Allocation 1
4th 3rd 2nd 1st digit digit digit digit n.
Pn868
Setting
Range
0000 to
1717
Units
-
Factory
Setting
When
Enabled
0000 Immediately
Output Signal Monitor Allocation for CN1-11 (SVCMD-IO)
0
1
4
5
6
7
2
3
Allocate D24 (IO_STS1) to CN1-11 output signal monitor.
Allocate D25 (IO_STS2) to CN1-11 output signal monitor.
Allocate D26 (IO_STS3) to CN1-11 output signal monitor.
Allocate D27 (IO_STS4) to CN1-11 output signal monitor.
Allocate D28 (IO_STS5) to CN1-11 output signal monitor.
Allocate D29 (IO_STS6) to CN1-11 output signal monitor.
Allocate D30 (IO_STS7) to CN1-11 output signal monitor.
Allocate D31 (IO_STS8) to CN1-11 output signal monitor.
Setup
CN1-11 Output Signal Monitor Enable/Disable Selection
0
1
Disable allocation for CN1-11 output signal monitor.
Enable allocation for CN1-11 output signal monitor.
Output Signal Monitor Allocation for CN1-10 (SVCMD_IO)
0 to 7 The settings are the same as the CN1-11 allocations.
CN1-10 Output Signal Monitor Enable/Disable Selection
0
1
Disable allocation for CN1-10 output signal monitor.
Enable allocation for CN1-10 output signal monitor.
Pn869
2
SVCMD_IO
(output signal monitor)
Allocation 2
4th 3rd 2nd 1st digit digit digit digit n.
0000 to
1717
– 0000 Immediately
Output Signal Monitor Allocation for CN1-9 (SVCMD-IO)
0 to 7 The settings are the same as the CN1-11 allocations.
CN1-9 Output Signal Monitor Enable/Disable Selection
0
1
Disable allocation for CN1-9 output signal monitor.
Enable allocation for CN1-9 output signal monitor.
Reserved (Do not change.)
Reserved (Do not change.)
Setup
Pn880
Pn881
Pn882
2
2
Station Address Monitor
(for maintenance, read only)
Setting Transmission Byte
Monitor [byte]
(for maintenance, read only)
03 to EFH
17, 32, 48
–
–
0
0
Immediately
Immediately
Setup
Setup
2
Transmission Cycle Setting Monitor [0.25 μ s]
(for maintenance, read only)
0 to FFFFH – 0 Immediately
∗2.
This parameter is enabled only for MECHATROLINK-III standard servo profile.
Setup
M3
*2
M3
*2
–
–
–
(cont’d)
–
–
–
–
–
9.1 List of Parameters
(cont’d)
Parameter
No.
Size
Pn883
Name
2
2
Communications Cycle
Setting Monitor [x transmission cycle]
(for maintenance, read only)
Communications
Control 2
4th 3rd 2nd 1st digit digit digit digit n.
Setting
Range
Units
Factory
Setting
When
Enabled
0 to 32
0000 to
0001
–
–
0 Immediately
0000 Immediately
Setup
Setup
–
M3
*2
–
–
Pn884
Pn88A
Pn890 to
Pn8A6
Pn8A8 to
Pn8BE
Pn900
Pn901
Pn902 to
Pn910
Pn920 to
Pn95F
Holding Brake Signal Status at MECHATROLINK Communications Error
0
1
Maintains the status set by the BRK_ON or BRK_OFF command when a MECHATROLINK communications error occurs.
Applies the holding brake when a MECHATROLINK communications error occurs.
Reserved (Do not change.)
Reserved (Do not change.)
Reserved (Do not change.)
2
4
MECHATROLINK
Receive Error Counter
Monitor
(for maintenance, read only)
Command Data Monitor at Alarm/Warning Occurs
(for maintenance, read only)
4
Response Data Monitor at
Alarm/Warning Occurs
(for maintenance, read only)
2 Parameter Bank Number
2
Parameter Bank Member
Number
0 to 65535
0 to
FFFFFFFF
H
0 to
FFFFFFFF
H
0 to 16
0 to 15
–
–
–
–
–
0
0
0
0
0
Immediately
Immediately
Immediately
After restart
After restart
Setup
Setup
Setup
Setup
Setup
–
–
–
–
–
–
*1
*1
*1
*1
2
Parameter Bank Member
Definition
0000H to
08FFH
– 0 After restart Setup – *1
2
Parameter Bank Data
(nonvolatile memory save disabled)
0000H to
FFFFH
– 0 Immediately Setup – *1
∗1.
For details, refer to Σ -V Series User’s Manual MECHATROLINK-III Standard Servo Profile Commands
No.: SIEP S800000 63).
∗2.
This parameter is enabled only for MECHATROLINK-III standard servo profile.
(Manual
9
9-33
9-34
9 Appendix
9.1.3 MECHATROLINKIII Common Parameters
9.1.3
MECHATROLINK-
III
Common Parameters
The following list shows the common parameters used by all devices for MECHATROLINK-III. These common parameters are used to make settings from the host controller via MECHATROLINK communications.
Do not change settings with the SigmaWin+ or any other device.
04
PnA08
05
PnA0A
06
PnA0C
07
PnA0E
08
PnA10
09
PnA12
0A
PnA14
21
PnA42
22
PnA44
23
PnA46
24
PnA48
Parameter
No.
01
PnA02
02
PnA04
03
PnA06
Size
4
4
4
Name
Encoder Type (read only)
0000H Absolute encoder
0001H Incremental encoder
Motor Type (read only)
0000H Rotational servomotor
0001H Linear servomotor
Reserved (Do not use.)
0000H Semi-closed
0001H Fully-closed
4 Rated Speed (read only)
25
PnA4A
4
4
4
4
4
4
4
4
4
Maximum Output Speed (read only)
Speed Multiplier (read only)
Rated Torque (read only)
Maximum Output Torque (read only)
4 Torque Multiplier (read only)
Resolution (read only)
Electronic Gear Ratio (Numerator)
Electronic Gear Ratio (Denominator)
Absolute Encoder Origin Offset
Multiturn Limit Setting
Setting Range
0 to 1
0 to 1
–
0 to
FFFFFFFFH
0 to
FFFFFFFFH
–
0 to
FFFFFFFFH
0 to
FFFFFFFFH
–
0 to
FFFFFFFFH
1 to
1073741824
1 to
1073741824
–1073741823 to 1073741823
0 to 65535
Units
[Resolution]
N
N
–
–
– min min
–
– pulse/rev
–
–
-1
-1 m m
1 reference unit
Rev
Factory
Setting
–
–
–
–
–
–
–
–
–
–
1
1
0
65535
When
Enabled
–
–
–
–
–
–
–
–
–
–
After restart
After restart
Immediately
*1
After restart
Classification
Device
Information
Related
Parameters
4
Limit Setting
Bit 0
Bit 1
P-OT (0: Enabled, 1: Disabled)
N-OT (0: Enabled, 1: Disabled)
0 to 33H
Bit 2
Bit 3
Bit 4
Bit 5
Reserved
Reserved
P-SOT (0: Disabled, 1: Enabled)
N-SOT (0: Disabled, 1: Enabled)
0000H
0000H
After restart
Machine
Specification
Related
Parameters
Bit 6 Reserved
Bit
7 to 31
Reserved
∗1.
Available after the SENS_ON command is input.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9.1 List of Parameters
Parameter
No.
26
PnA4C
27
PnA4E
28
PnA50
29
PnA52
41
PnA82
42
PnA84
43
PnA86
44
PnA88
45
PnA8A
46
PnA8C
47
PnA8E
48
PnA90
Size Name Setting Range
Units
[Resolution]
Factory
Setting
When
Enabled
Classification
4 Forward Software Limit
–1073741823 to
1073741823
1 reference unit 1073741823
Immediately
4
4
Reserved (Do not use.)
Reverse Software Limit
–
–1073741823 to
1073741823
–
1 reference unit
0
–1073741823
Immediately
Immediately
Machine
Specification
Related
Parameters
4 Reserved (Do not use.) – – 0
Immediately
4
Speed Unit
0000H reference unit/sec
0001H reference unit/min
0002H Percentage (%) of rated speed
*2
0 to 4 –
0
After restart
4
4
4
0003H min
-1*2
0004H Max. motor speed/40000000H
*3
Speed Base Unit
(Set the value of “n” used as the exponent in 10 n
when calculating the Speed Unit (41).)
*2*3
Position Unit
0000H reference unit
Position Base Unit
(Set the value of “n” used as the exponent in 10 n
when calculating the Position Unit (43).)
Acceleration Unit
–3 to 3
0
0
–
–
–
–
–
0
0
0
After restart
After restart
After restart Unit System
Related
Parameters
4 0000H reference unit/sec
2
0001H Not supported
0
After restart
4
Acceleration Base Unit
(Set the value of “n” used as the exponent in 10 n
when calculating the Acceleration Unit (45).)
Torque Unit
0000H Not supported
4 to 6
1 to 2
–
–
4
After restart
4
0001H Percentage (%) of rated torque
0002H Max. torque/40000000H
*4
1
After restart
4
Torque Base Unit
*4
(Set the value of “n” used as the exponent in 10 n
when calculating the Torque Unit (47).)
–5 to 0 – 0
After restart
∗2.
When 0003H is selected for the Speed Unit (parameter 41), set the Speed Base Unit (parameter 42) to a number between -3 and 0.
∗3.
When 0004H is selected for the Speed Unit (parameter 41), set the Speed Base Unit (parameter 42) to 0.
∗4.
When 0002H is selected for the Torque Unit (parameter 47), set the Torque Base Unit (parameter 48) to 0.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9
9-35
9-36
9 Appendix
9.1.3 MECHATROLINKIII Common Parameters
61
PnAC2
62
PnAC4
63
PnAC6
64
PnAC8
65
PnACA
66
PnACC
Parameter
No.
49
PnA92
Size Name Setting Range
Compliance Unit System (read only)
Speed
Bit 0
Bit 1
Bit 2 reference unit/s (1: Enabled) reference unit/min (1: Enabled)
–
Percentage (%) of rated speed (1: Enabled)
Bit 3 min
-1
(rpm) (1: Enabled)
Max. motor speed/4000000H [HEX] (1: Enabled) Bit 4
Bit
5 to 7
Position
Reserved (0: Disabled)
Units
[Resolution]
–
4
Bit 8
Bit
9 to 15 reference unit (1: Enabled)
Reserved (0: Disabled)
Acceleration
Bit 16 reference unit/s
2
(1: Enabled)
Bit 17 msec (Acceleration time taken to reach the rated speed)
(0: Disabled)
Bit
18 to 23
Reserved (0: Disabled)
4
Torque
Bit 24 N m (N) (0: Disabled)
Bit 25 Percentage (%) of rated torque (1: Enabled)
Bit 26 Max. torque/40000000 [HEX] (1: Enabled)
Bit
27 to 31 Reserved (0: Disabled)
Speed Loop Gain
1000 to
2000000
4
4
Speed Loop Integral Time Constant
Position Loop Gain
150 to 512000
1000 to
2000000
0.001 Hz
[0.1 Hz]
μ s
[0.01 ms]
0.001/s
[0.1/s]
4
4
4
Feedforward Compensation
Position Loop Integral Time Constant
Positioning Completed Width
0 to 100
0 to 5000000
0 to
1073741824
1%
μ s
[0.1 ms]
1 reference unit
67
PnACE
4 NEAR Signal Width
1 to
1073741824
1 reference unit
Factory
Setting
0601011FH
40000
20000
40000
0
0
7
1073741824
When
Enabled
Classification
–
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Unit System
Related
Parameters
Adjustment
Related
Parameters
Adjustment
Related
Parameters
9.1 List of Parameters
Parameter
No.
81
PnB02
82
PnB04
83
PnB06
84
PnB08
85
PnB0A
86
PnB0C
87
PnB0E
88
PnB10
Size
4
4
4
Time Constant
Name
Exponential Function Accel/Decel
Movement Average Time
Final Travel Distance for External
Positioning
Setting Range
0 to 510000
0 to 510000
–1073741823 to 1073741823
Units
[Resolution]
μ
μ s
[0.1 ms] s
[0.1 ms]
1 reference unit
Factory
Setting
0
0
100
When
Enabled
Immediately
*5
Immediately
*5
Immediately
Classification
4
4
Homing Approach Speed
Homing Creep Speed
0 to
3FFFFFFFH
0 to
3FFFFFFFH
10
10
-3
min
-3
min
-1
-1
500
Value converted
reference/s into 10
-3 min
-1
500
Value converted
reference/s into 10
-3 min
-1
Immediately
Immediately
4 Final Travel Distance for Homing
–1073741823 to 1073741823
0 to F
1 reference unit 100
Immediately
4
Monitor Selection 1
0000H APOS
0001H CPOS
0002H PERR
0003H LPOS1
0004H LPOS2
0005H FSPD
0006H CSPD
0007H TRQ
0008H ALARM
0009H MPOS
000AH Reserved (Undefined value)
000BH Reserved (Undefined value)
000CH CMN1 (Common monitor 1)
000DH CMN2 (Common monitor 2)
–
1
Immediately
Command
Related
Parameters
000EH OMN1 (Optional monitor 1)
000FH OMN2 (Optional monitor 2)
4
Monitor Selection 2
0000H
to
000FH
Same as Monitor Selection 1.
– –
0
Immediately
∗5.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
9
9-37
9-38
9 Appendix
9.1.3 MECHATROLINKIII Common Parameters
Parameter
No.
Size
89
PnB12
4
Name Setting Range
Units
[Resolution]
Monitor Selection for SEL_MON1
(CMN1)
0002H
0 to 6 –
0000H TPOS (Target position in the reference coordinates)
0001H IPOS (Reference position in the reference coordinates)
POS_OFSET (Offset value set in the set coordinates command
(POS_SET))
0003H TSPD (Target speed)
0004H SPD_LIM (Speed limit value)
0005H TRQ_LIM (Torque limit value)
SV_STAT
Monitor
Byte 1: Current communications phase
00H: Phase 0
01H: Phase 1
02H: Phase 2
03H: Phase 3
Byte 2: Current control mode
00H: Position control mode
01H: Speed control mode
02H: Torque control mode
Byte 3: Reserved
Byte 4: Expansion signal monitor
Bit Name Contents
0006H
Bit 0 LT_RDY1
Bit 1 LT_RDY1
Bit 2,
Bit 3
Bit 4,
Bit 5
Processing status for latch detection specified by
SVCMD_CTRL,
LT_REQ1
Processing status for latch detection specified by
SVCMD_CTRL,
LT_REQ2
LT_SEL1R Latch signal
LT_SEL2R Latch signal
Value Setting
0
Latch detection not processed
1
0
During latch detection processing
Latch detection not processed
1
During latch detection processing
0 Phase C
1
2
External input signal 1
External input signal 2
3
External input signal 3
0 Phase C
1
2
3
External input signal 1
External input signal 2
External input signal 3
Bit 6 Reserved (0)
Factory
Setting
When
Enabled
Classification
0
Immediately
Command
Related
Parameters
9.1 List of Parameters
8B
PnB16
8C
PnB18
8D
PnB1A
8E
PnB1C
8F
PnB1E
Parameter
No.
Size
8A
PnB14
Name Setting Range
4
Monitor Selection for SEL_MON2
(CMN2)
0000H
to
0006H
0 to 6
Same as Monitor Selection for SEL_MON1.
4 Origin Detection Range 0 to 250
4
4
Forward Torque Limit
Reverse Torque Limit
0 to 800
0 to 800
90
PnB20
4
4
Zero Speed Detection Range
1000 to
10000000
Speed Coincidence Signal Output
Width (read only)
Servo Command Control Field
Enabled/Disabled (read only)
Bit 0
Bit 1
CMD_PAUSE (1: Enabled)
CMD_CANCEL (1: Enabled)
Bit 2, 3 STOP_MODE (1: Enabled)
Bit 4, 5 ACCFIL (1: Enabled)
0 to 100000
–
4
Bit 6, 7 Reserved (0: Disabled)
Bit 8
Bit 9
LT_REQ1 (1: Enabled)
LT_REQ2 (1: Enabled)
Bit 10,
11
Bit 12,
13
Bit 14,
15
Bit 16 to
19
LT_SEL1 (1: Enabled)
LT_SEL2 (1: Enabled)
Reserved (0: Disabled)
SEL_MON1 (1: Enabled)
Bit 20 to
23
Bit 24 to
27
Bit 28 to
31
SEL_MON2 (1: Enabled)
SEL_MON3 (1: Enabled)
Reserved (0: Disabled)
Units
[Resolution]
–
1 reference unit
10
10
1%
1%
-3
min
-3
min
–
-1
-1
Factory
Setting
0
10
100
100
20000
10000
0FFF3F3FH
When
Enabled
Classification
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
–
Command
Related
Parameters
9
9-39
9-40
9 Appendix
9.1.3 MECHATROLINKIII Common Parameters
Parameter
No.
Size
91
PnB22
92
PnB24
Name Setting Range
4
4
Servo Command Status Field
Enabled/Disabled (read only)
–
Bit 0
Bit 1
CMD_PAUSE_CMP (1: Enabled)
CMD_CANCEL_CMP (1: Enabled)
Bit 2, 3 Reserved (0: Disabled)
Bit 4, 5 ACCFIL (1: Enabled)
Bit 6, 7 Reserved (0: Disabled)
Bit 8 L_CMP1 (1: Enabled)
Bit 9 L_CMP2 (1: Enabled)
Bit 10 POS_RDY (1: Enabled)
Bit 11 PON (1: Enabled)
Bit 12 M_RDY (1: Enabled)
Bit 13 SV_ON (1: Enabled)
Bit 14,
15
Reserved (0: Disabled)
Bit 16 to
19
Bit 20 to
23
SEL_MON1 (1: Enabled)
SEL_MON2 (1: Enabled)
Bit 24 to
27
Bit 28 to
31
SEL_MON3 (1: Enabled)
Reserved (0: Disabled)
I/O Bit Enabled/Disabled (Output)
(read only)
Bit
0 to 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit
9 to 11
Reserved (0: Disabled)
V_PPI (1: Enabled)
P_PPI (1: Enabled)
P_CL (1: Enabled)
N_CL (1: Enabled)
G_SEL (1: Enabled)
G_SEL (0: Disabled)
Bit 12 to
15
Bit 16 to
19
Bit 24 to
31
Reserved (0: Disabled)
BANK_SEL (1: Enabled)
Bit 20 to
22
SO1 to SO3 (1: Enabled)
Bit 23 Reserved (0: Disabled)
Reserved (0: Disabled)
–
Units
[Resolution]
0
–
Factory
Setting
0FFF3F33H
007F01F0H
When
Enabled
Classification
–
–
Command
Related
Parameters
9.1 List of Parameters
Parameter
No.
Size
93
PnB26
Name
4
I/O Bit Enabled/Disabled (Input)
(read only)
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Reserved (0: Disabled)
DEC (1: Enabled)
P-OT (1: Enabled)
N-OT (1: Enabled)
EXT1 (1: Enabled)
Reserved (1: Enabled)
Reserved (1: Enabled)
ESTP (1: Enabled)
Reserved (0: Disabled)
Bit 9 BRK_ON (1: Enabled)
Bit 10 P-SOT (1: Enabled)
Bit 11 N-SOT (1: Enabled)
Bit 12 DEN (1: Enabled)
Bit 13 NEAR (1: Enabled)
Bit 14 PSET (1: Enabled)
Bit 15 ZPOINT (1: Enabled)
Bit 16 T_LIM (1: Enabled)
Bit 17 V_LIM (1: Enabled)
Bit 18 V_CMP (1: Enabled)
Bit 19 ZSPD (1: Enabled)
Bit 20 to
23
Bit 24 to
31
Reserved (0: Disabled)
I0_STS1 to 8 (1: Enabled)
Setting Range
–
Units
[Resolution]
–
Factory
Setting
FF0FFEFEH
When
Enabled
Classification
–
Command
Related
Parameters
9
9-41
9-42
9 Appendix
9.2
List of Monitor Displays
The following list shows the available monitor displays.
Un00C
Un00D
Un012
Un013
Un014
Un020
Un021
Un030
Un031
Un003
Un004
Un005
Un006
Un007
Un008
Un009
Parameter
No.
Un000
Un001
Un002
Description
Motor rotating speed
Speed reference min
-1 min
-1
% Internal torque reference (in percentage to the rated torque)
Rotational angle 1 (encoder pulses from the phase-C origin: decimal display)
The current backlash compensation value
Backlash compensation setting limit value encoder pulse
*
Rotational angle 2 (from polarity origin (electric angle))
Input signal monitor
Output signal monitor
Input reference pulse speed (valid only in position control) deg
−
− min
-1 reference unit Position error amount (valid only in position control)
Accumulated load ratio (in percentage to the rated torque: effective torque in cycle of 10 seconds)
Input reference pulse counter
%
Feedback pulse counter reference unit encoder pulse
*
Total operation time
Feedback pulse counter
100 ms reference unit
Effective gain monitor (gain settings 1 = 1, gain settings 2 = 2) −
Motor rated speed min
-1
Motor maximum speed min
-1
0.1 reference unit
0.1 reference unit
Unit
∗ For details, refer to 4.4.3 Electronic Gear .
9.3 Parameter Recording Table
9.3
Parameter Recording Table
Use the following table for recording parameters.
Note: Pn10B, Pn170, and Pn408 have two kinds of digits: the digit which does not need the restart after changing the settings and the digit which needs the restart. The underlined digits of the factory setting in the following table show the digit which needs the restart.
Pn105
Pn106
Pn109
Pn10A
Pn10B
Pn10C
Pn10D
Pn10E
Pn10F
Pn11F
Pn121
Pn122
Pn123
Pn124
Parameter
Pn00B
Pn00C
Pn00D
Pn100
Pn101
Pn102
Pn103
Pn104
Pn000
Pn001
Pn002
Pn006
Pn007
Pn008
Pn009
Pn125
Pn131
Pn132
Pn135
Pn136
4000
0010
0000
0000
0000
400
2000
400
100
400
Factory
Setting
0000
0102
0011
0002
0000
Name
When
Enabled
After restart Basic Function Select Switch 0
Application Function Select Switch 1 After restart
Application Function Select Switch 2 After restart
Application Function Select Switch 6 Immediately
Application Function Select Switch 7 Immediately
Application Function Select Switch 8 After restart
Application Function Select Switch 9 After restart
Application Function Select Switch B After restart
Application Function Select Switch C After restart
Application Function Select Switch D After restart
Speed Loop Gain Immediately
Speed Loop Integral Time Constant Immediately
Position Loop Gain Immediately
Moment of Inertia Ratio
2nd Speed Loop Gain
Immediately
Immediately
200
0
0
0
0
100
100
0
2000
400
0
0
0000
0
2nd Speed Loop Integral Time Constant
2nd Position Loop Gain
Feedforward Gain
Feedforward Filter Time Constant
Immediately
Immediately
Immediately
Immediately
Application Function for Gain Select
Switch
Mode Switch (torque reference)
−
Mode Switch (speed reference)
Mode Switch (acceleration)
Mode Switch (position error)
Position Integral Time Constant
Immediately
Immediately
Immediately
Friction Compensation Gain Immediately
2nd Gain for Friction Compensation Immediately
Friction Compensation Coefficient
Friction Compensation Frequency
Correction
Immediately
Immediately
Immediately
Immediately
100
0
0
0
Friction Compensation Gain Correction
Gain Switching Time 1
Gain Switching Time 2
Gain Switching Waiting Time 1
Immediately
Immediately
Immediately
Immediately
0 Gain Switching Waiting Time 2 Immediately
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9
9-43
9 Appendix
9-44
Pn230
Pn231
Pn233
Pn281
Pn304
Pn305
Pn165
Pn170
Pn205
Pn207
Pn20A
Pn20E
Pn210
Pn22A
Pn144
Pn145
Pn146
Pn147
Pn148
Pn149
Pn14A
Pn14B
Pn14F
Pn160
Pn161
Pn162
Pn163
Pn164
Parameter
Pn139
Pn13D
Pn140
Pn141
Pn142
Pn143
Factory
Setting
0000
2000
0100
500
1000
1000
1000
500
700
Name
(cont’d)
When
Enabled
Automatic Gain Changeover Related
Switch 1
Current Gain Level
Model Following Control Related
Switch
Immediately
Immediately
Immediately
Model Following Control Gain
Model Following Control Gain Compensation
Model Following Control Bias
(Forward Direction)
Model Following Control Bias
(Reverse Direction)
Immediately
Immediately
Immediately
Immediately
Vibration Suppression 1 Frequency A Immediately
Vibration Suppression 1 Frequency B Immediately
1000
500
1000
800
100
0011
0010
Model Following Control Speed
Feedforward Compensation
2nd Model Following Control Gain
2nd Model Following Control Gain
Compensation
Vibration Suppression 2 Frequency
Immediately
Immediately
Immediately
Immediately
Vibration Suppression 2 Compensation
Control Related Switch
Immediately
After restart
Anti-Resonance Control Related
Switch
Anti-Resonance Frequency
Immediately
Immediately
Anti-Resonance Gain Compensation Immediately
Anti-Resonance Damping Gain Immediately
1000
100
0
0
0
1401
65535
0010
32768
1
1
0000
0000
Anti-Resonance Filter Time Constant 1 Compensation
Anti-Resonance Filter Time Constant 2 Compensation
Tuning-less Function Related Switch
Multiturn Limit Setting
Immediately
Immediately
−
After restart
Position Control Function Switch
Reserved
Electronic Gear Ratio (Numerator)
After restart
−
After restart
Electronic Gear Ratio (Denominator) After restart
Reserved
Position Control Expanded Function
Switch
−
After reset
0
0
20
500
Backlash Compensation Value
Backlash Compensation Time Constant
Reserved
JOG Speed
Immediately
Immediately
−
Immediately
0 Soft Start Acceleration Time Immediately
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9.3 Parameter Recording Table
Pn412
Pn424
Pn425
Pn456
Pn460
Pn501
Pn502
Pn503
Pn401
Pn402
Pn403
Pn404
Pn405
Pn406
Pn407
Pn408
Pn409
Pn40A
Pn40B
Pn40C
Pn40D
Pn40E
Pn40F
Pn506
Pn507
Pn508
Pn509
Pn50A
Pn50B
Pn50E
Pn50F
Pn510
Parameter
Pn306
Pn310
Pn311
Pn312
Pn324
Pn410
5000
70
0
5000
70
0
800
800
100
100
800
10000
0000
Factory
Setting
0
0000
100
50
300
100
5000
50
100
50
100
15
0101
10
20
10
0
Name
(cont’d)
When
Enabled
Immediately Soft Start Deceleration Time
Vibration Detection Switch
Vibration Detection Sensibility
Immediately
Immediately
Immediately Vibration Detection Level
Moment of Inertia Calculating Start
Level
Torque Reference Filter Time Constant
Forward Torque Limit
Immediately
Immediately
Reverse Torque Limit
Forward External Torque Limit
Reverse External Torque Limit
Emergency Stop Torque
Immediately
Immediately
Immediately
Immediately
Immediately
Speed Limit during Torque Control Immediately
Torque Related Function Switch −
1st Notch Filter Frequency Immediately
1st Notch Filter Q Value Immediately
1st Notch Filter Depth
2nd Notch Filter Frequency
2nd Notch Filter Q Value
2nd Notch Filter Depth
Immediately
Immediately
Immediately
Immediately
2nd Step 2nd Torque Reference Filter
Frequency
2nd Step 2nd Torque Reference Filter
Q Value
Immediately
Immediately
1st Step 2nd Torque Reference Filter
Time Constant
Immediately
Reserved
Reserved
−
−
Sweep Torque Reference Amplitude Immediately
Notch Filter Adjustment Switch
Zero Clamp Level
Rotation Detection Level
Speed Coincidence Signal Output
Width
Brake Reference - Servo OFF Delay
Time
Immediately
Immediately
Immediately
Immediately
Immediately
100
50
20
1881
8882
0000
Brake Reference Output Speed Level Immediately
Waiting Time for Brake Signal When
Motor Running
Immediately
Reserved
Input Signal Selection 1
Input Signal Selection 2
Output Signal Selection 1
−
After restart
After restart
After restart
0100
0000
Output Signal Selection 2
Output Signal Selection 3
After restart
After restart
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9
9-45
9 Appendix
9-46
Pn530
Pn531
Pn533
Pn534
Pn535
Pn536
Pn550
Pn551
Pn552
Pn553
Pn560
Pn561
Pn600
Pn601
Pn800
Pn528
Pn529
Pn52A
Pn52B
Pn52C
Pn52D
Pn52F
Parameter
Pn511
Pn512
Pn517
Pn51B
Pn51E
Pn520
Pn522
Pn524
Pn526
Pn801
Pn803
Pn804
Pn806
Pn808
Factory
Setting
8880
0000
0000
1000
100
5242880
7
1073741824
5242880
100
10000
20
20
100
50
0FFF
0000
Name
Input Signal Selection 5
Output Signal Inverse Setting
Reserved
Reserved
Excessive Position Error Warning
Level
Excessive Position Error Alarm
Level
Positioning Completed Width
NEAR Signal Width
Excessive Position Error Alarm
Level at Servo ON
Excessive Position Error Warning
Level at Servo ON
Speed Limit Level at Servo ON
Reserved
Overload Warning Level
Derating of Base Current at Detecting
Overload of Motor
Reserved
Reserved
Program JOG Operation Related
Switch
Program JOG Movement Distance
Program JOG Movement Speed
(cont’d)
When
Enabled
After restart
After restart
–
−
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
−
Immediately
After restart
−
−
Immediately
32768
500
Immediately
Immediately
100
100
1
0
0
100
100
400
100
0
0
1040
Program JOG Acceleration/Deceleration Time
Program JOG Waiting Time
Number of Times of Program JOG
Movement
Analog Monitor 1 Offset Voltage
Analog Monitor 2 Offset Voltage
Immediately
Immediately
Immediately
Immediately
Immediately
Analog Monitor Magnification ( × 1) Immediately
Analog Monitor Magnification ( × 2) Immediately
Remained Vibration Detection Width Immediately
0003
Overshoot Detection Level
Reserved
Reserved
Communications Control
Application Function Select 6
(Software LS)
Immediately
–
–
Immediately
Immediately
10
1073741823
Origin Range
Forward Software Limit
Immediately
Immediately
-1073741823 Reverse Software Limit Immediately
0 Absolute Encoder Origin Offset
Immediately
∗ 1
∗1.
Enabled after the SENS_ON command is input.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9.3 Parameter Recording Table
Pn819
Pn81E
Pn81F
Pn820
Pn822
Pn824
Pn825
Pn827
Pn829
Pn82A
Pn82B
Pn82C
Pn82D
Pn82E
Pn833
Pn834
Parameter
Pn80A
Pn80B
Pn80C
Pn80D
Pn80E
Pn80F
Pn810
Pn811
Pn812
Pn814
Pn816
Pn817
Pn818
Pn836
Factory
Setting
100
100
0
100
100
0
0
0
0
100
0000
50
5
100
0000
0010
0
0
0000
0000
100
0
(cont’d)
Speed
Name
1st Linear Acceleration Constant
2nd Linear Acceleration Constant
Acceleration Constant Switching
1st Linear Deceleration Constant
2nd Linear Deceleration Constant
Deceleration Constant Switching
Speed
Exponential Function Acceleration/
Deceleration Bias
Exponential Function Acceleration/
Deceleration Time Constant
Movement Average Time
Final Travel Distance for External
Positioning
Homing Mode Setting
Homing Approach Speed
(Homing Approach Speed 1)
Homing Creep Speed
(Homing Approach Speed 2)
Final Travel Distance for Homing
When
Enabled
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
After restart
Input Signal Monitor Selection
Command Data Allocation
Forward Latching Allowable Area
Reverse Latching Allowable Area
Option Monitor 1 Selection Immediately
Option Monitor 2 Selection Immediately
Linear Deceleration Constant 1 for
Stopping
SVOFF Waiting Time (SVOFF at deceleration to stop)
Immediately
Immediately
Immediately
∗ 2
Immediately
1813
1D1C
1F1E
0000
Option Field Allocation 1
Option Field Allocation 2
Option Field Allocation 3
Option Field Allocation 4
After restart
After restart
After restart
After restart
0000
0000
Option Field Allocation 5
Motion Setting
After restart
After restart
100 1st Linear Acceleration Constant 2
Immediately
∗ 2
100 2nd Linear Acceleration Constant 2
Immediately
∗ 2
∗2.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9
9-47
9 Appendix
9-48
Pn842
Pn850
Pn851
Pn852
Pn853
Pn860
Parameter
Pn838
Pn83A
Pn83C
Pn83E
Pn840
Pn861
Pn862
Pn863
Pn864
Pn865
Pn866
Pn868
Pn869
Pn880
Pn881
Pn882
Pn883
Pn884
Pn88A
Factory
Setting
0
100
100
0
100
0
0
0
0000
0000
0000
0000
0000
0000
0000
0000
0000
(cont’d)
Acceleration Constant Switching
Speed 2
Name
1st Linear Deceleration Constant 2
2nd Linear Deceleration Constant 2
Deceleration Constant Switching
Speed 2
Linear Deceleration Constant 2 for
Stopping
Homing Approach Speed (Homing
Approach Speed 12)
Latch Sequence Number
When
Enabled
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
∗ 2
Immediately
Continuous Latch Count Immediately
Latch Sequence Signal 1 to 4 Setting Immediately
Latch Sequence Signal 5 to 8 Setting Immediately
SVCMD_IO (input signal monitor)
Allocation 1
Immediately
SVCMD_IO (input signal monitor)
Allocation 2
SVCMD_IO (input signal monitor)
Allocation 3
Immediately
Immediately
SVCMD_IO (input signal monitor)
Allocation 4
SVCMD_IO (input signal monitor)
Allocation 5
SVCMD_IO (input signal monitor)
Allocation 6
SVCMD_IO (input signal monitor)
Allocation 7
Immediately
Immediately
Immediately
Immediately
0000
0100
0
0
SVCMD_IO (output signal monitor)
Allocation 1
SVCMD_IO (output signal monitor)
Allocation 2
Station Address Monitor
(for maintenance, read only)
Setting Transmission Byte Monitor
[byte] (for maintenance, read only)
Immediately
Immediately
Immediately
Immediately
0
0
Transmission Cycle Setting Monitor
[0.25 μ s]
(for maintenance, read only)
Communications Cycle Setting
Monitor [x transmission cycle]
(for maintenance, read only)
Immediately
Immediately
0000
0
Communications Control 2
MECHATROLINK Receive Error
Counter Monitor
(for maintenance, read only)
Immediately
Immediately
∗2.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9.3 Parameter Recording Table
Parameter
Pn890 to
Pn8A6
Pn8A8 to
Pn8BE
22
PnA44
23
PnA46
24
PnA48
25
PnA4A
08
PnA10
09
PnA12
0A
PnA14
21
PnA42
Pn900
Pn901
Pn902 to
Pn910
Pn920 to
Pn95F
01
PnA02
02
PnA04
03
PnA06
04
PnA08
05
PnA0A
06
PnA0C
07
PnA0E
26
PnA4C
27
PnA4E
28
PnA50
Factory
Setting
0
0
0
0
0
0
–
–
–
–
–
–
–
–
–
–
1
1
0
65535
0000H
1073741823
0
Limit Setting
Name
Command Data Monitor at Alarm/
Warning Occurs
(for maintenance, read only)
Response Data Monitor at Alarm/
Warning Occurs
(for maintenance, read only)
Parameter Bank Number
Parameter Bank Member Number
(cont’d)
When
Enabled
Immediately
Immediately
After restart
After restart
Parameter Bank Member Definition After restart
Parameter Bank Data (nonvolatile memory save disabled)
Immediately
Encoder Type (read only)
Motor Type (read only)
Reserved (Do not use.)
Rated Speed (read only)
Maximum Output Speed (read only)
Speed Multiplier (read only)
Rated Torque (read only)
Maximum Output Torque (read only)
Torque Multiplier (read only)
Resolution (read only)
Electronic Gear Ratio (Numerator)
Electronic Gear Ratio (Denominator)
Absolute Encoder Origin Offset
Multiturn Limit Setting
Forward Software Limit
Reserved (Do not use.)
–
–
–
–
–
–
–
–
–
–
After restart
After restart
Immediately
∗ 1
After restart
After restart
Immediately
Immediately
-1073741823 Reverse Software Limit Immediately
∗1.
Enabled after the SENS_ON command is input.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
9
9-49
9-50
9 Appendix
Parameter
48
PnA90
49
PnA92
61
PnAC2
62
PnAC4
63
PnAC6
64
PnAC8
65
PnACA
66
PnACC
44
PnA88
45
PnA8A
46
PnA8C
47
PnA8E
29
PnA52
41
PnA82
42
PnA84
43
PnA86
67
PnACE
81
PnB02
82
PnB04
83
PnB06
84
PnB08
Factory
Setting
0
0
0
0
0
0
4
1
0
0601011FH
40000
20000
40000
0
0
7
1073741824
Speed Unit
Position Unit
Torque Unit
Name
Reserved (Do not use.)
Speed Base Unit
Position Base Unit
Acceleration Unit
Acceleration Base Unit
Torque Base Unit
Compliance Unit System (read only)
Speed Loop Gain
Speed Loop Integral Time Constant
Position Loop Gain
Feedforward Compensation
(cont’d)
When
Enabled
Immediately
After restart
After restart
After restart
After restart
After restart
After restart
After restart
After restart
–
Immediately
Immediately
Immediately
Immediately
Position Loop Integral Time Constant Immediately
Positioning Completed Width
NEAR Signal Width
Immediately
Immediately
0
Exponential Function Accel/Decel
Time Constant
Immediately
∗ 2
0 Movement Average Time Immediately
∗ 2
100
Final Travel Distance for External
Positioning
Immediately
5000
Value converted reference/s into
10
-3
min
-1
Homing Approach Speed Immediately
∗2.
Change the setting when the reference is stopped (DEN is set to 1), because the change will affect the output during operation.
Note: When using parameters that are enabled after restarting the SERVOPACK, a CONFIG command must be input or the power must be turned OFF and then ON again.
8E
PnB1C
8F
PnB1E
90
PnB20
91
PnB22
92
PnB24
93
PnB26
8A
PnB14
8B
PnB16
8C
PnB18
8D
PnB1A
86
PnB0C
87
PnB0E
88
PnB10
89
PnB12
Parameter
85
PnB0A
Factory
Setting
500
Value converted reference/s into
10
-3
min
-1
100
1
0
0
0
10
100
100
20000
10000
0FFF3F3FH
0FFF3F33H
007F01F0H
FF0FFEFEH
9.3 Parameter Recording Table
Name
Homing Creep Speed
(cont’d)
When
Enabled
Immediately
Final Travel Distance for Homing
Monitor Selection 1
Monitor Selection 2
Monitor Selection for SEL_MON1
(CMN1)
Monitor Selection for SEL_MON2
(CMN2)
Origin Detection Range
Forward Torque Limit
Reverse Torque Limit
Zero Speed Detection Range
Speed Coincidence Signal Output
Width (read only)
Servo Command Control Field
Enabled/Disabled (read only)
Servo Command Status Field
Enabled/Disabled (read only)
I/O Bit Enabled/Disabled (Output)
(read only)
I/O Bit Enabled/Disabled (Input)
(read only)
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
Immediately
–
–
–
–
9
9-51
Index
Index
Symbols
/BK - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-12
/CLT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-27
/COIN - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-43
/N-CL- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-26
/NEAR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-44
/P-CL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-26
/S-RDY - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-41
/TGON - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-41
/V-CMP - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-42
/VLT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-45
/WARN - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40
A absolute data request (SENS_ON)- - - - - - - - - - - - - - - - - - - - - - 4-29 absolute encoder battery alarm (A.830) - - - - - - - - - - - - - - - - - - 4-30 absolute encoder origin offset- - - - - - - - - - - - - - - - - - - - - - - - - 4-39 absolute encoders - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-28 connection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-28 set up (initializing) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-32 additional adjustment function - - - - - - - - - - - - - - - - - - - - - - - - 5-71 advanced autotuning (Fn201) - - - - - - - - - - - - - - - - - - - - - - - - - 5-18 anti-resonance control adjustment function- - - - - - - - - - - - - 5-31 feedforward- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-32 friction compensation - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-32 notch filter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-31 vibration suppression - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-31 advanced autotuning by reference (Fn202) - - - - - - - - - - - - - - - - 5-34 anti-resonance control adjustment function- - - - - - - - - - - - - 5-40 feedforward- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-41 friction compensation - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-41 notch filter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-40 vibration suppression - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-41 alarm history display (Fn000)- - - - - - - - - - - - - - - - - - - - - - - - - - 6-3 alarm reset - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-2 alarm reset method - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40
ALM - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40 ambient/storage humidity - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 anti-resonance control adjustment function (Fn204)- - - - - - - - - - 5-54 automatic gain switching - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-72 automatic offset-signal adjustment of the motor current detection signal (Fn00E) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-24 automatically setting the notch filter - - - - - - - - - - - - - - - - - - - - 5-12
B backlash compensation function - - - - - - - - - - - - - - - - - - - - - - - 5-78 battery battery case - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-28 battery replacement - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-30
BB - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -iii brake signals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-12
C
CCW - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-5
CE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - xiv changing detection timing of overload (low load) alarm
(A.720)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-17 changing detection timing of overload warning (A.910) - - - - - - - 4-16 checking output torque limiting during operation - - - - - - - - - - - 4-27 clearing alarm history (Fn006) - - - - - - - - - - - - - - - - - - - - - - - - 6-19
Index-1
CN1 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-9
CN2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-24
CN3 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2
CN7 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2 coast to a stop - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-7 compatible adjustment function - - - - - - - - - - - - - - - - - - - - - - - 5-84 connecting the measurement instrument - - - - - - - - - - - - - - - - - - 5-5 connection to host controller (interface) sequence input circuit- - - - - - - - - - - - - - - - - - - - - - - - - - - 3-21 sequence output circuit - - - - - - - - - - - - - - - - - - - - - - - - - - 3-22 current control mode selection - - - - - - - - - - - - - - - - - - - - - - - - 5-77 current gain level setting - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-77
CW - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-5
D decelerate to stop - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-7 delay time in brake operation- - - - - - - - - - - - - - - - - - - - - - - - - 4-10
DIP switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2 display of SERVOPACK and servomotor ID (Fn01E) - - - - - - - - 6-35
E
EasyFFT (Fn206) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-41 electronic gear- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-20 electronic gear ratio - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-21 encoder signal (CN2) names and functions - - - - - - - - - - - - - - - 3-24 european directives - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - xiv examples of encoder connection- - - - - - - - - - - - - - - - - - - - - - - 3-24 external torque limit - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-26
F feedforward - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-84 feedforward compensation - - - - - - - - - - - - - - - - - - - - - - - - - - 5-84
FG- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-9 , 3-10 forward external torque limit - - - - - - - - - - - - - - - - - - - - - - - - - 4-26 friction compensation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-75
G gain adjustment of analog monitor output (Fn00D) - - - - - - - - - - 6-22
Gr.1 alarm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-15
Gr.2 alarm - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-15 grounding- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-27
G-SEL of OPTION field - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-72
H harmonized standards - - - - - - - - - - - - - - - - - - - - - - - - - - - - xiv , 1-4 holding brakes- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-10
I initializing parameter settings (Fn005) - - - - - - - - - - - - - - - - - - 6-16 input signal (CN1) allocations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-11 monitoring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-6 names and functions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-9 internal block diagrams- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-7 internal torque limit - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-25
J
JOG operation (Fn002) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-4
L
LED (ALM) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2
LED (CON) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2
LED (LK1 and LK2) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2
LED (RDY) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2 limit switches - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-6 limiting torque - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-25
Index list of alarms - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-2 list of monitor displays - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-2 list of warnings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-17
M main circuit terminals- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-2 main circuit wires - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-3 main circuit wiring examples- - - - - - - - - - - - - - - - - - - - - - - - - - 3-4 manual gain switching - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-72 manual offset-signal adjustment of the motor current detection signal (Fn00F)- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-26
MECHATROLINK-III communications connector - - - - - - - - - - - 1-2 molded-case circuit breaker- - - - - - - - - - - - - - - - - - - - - - - - - - - 3-5 monitor displays (Un ) - - - - - - - - - - - - - - - - - - - - - - 7-2 , 9-42 monitor factor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-7 multiturn limit disagreement alarm (A.CC0) - - - - - - - - - - - - - - 4-36 multiturn limit setting- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-35
N noise filter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-27
N-OT- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-6 notch filter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-89
O offset adjustment of analog monitor output (Fn00C) - - - - - - - - - 6-20 one-parameter tuning (Fn203) - - - - - - - - - - - - - - - - - - - - - - - - 5-43 anti-resonance control adjustment function - - - - - - - - - - - - 5-50 feedforward - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-51 friction compensation- - - - - - - - - - - - - - - - - - - - - - - - - - - 5-50 notch filter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-50 one-parameter tuning example - - - - - - - - - - - - - - - - - - - - - - - - 5-52 online vibration monitor (Fn207) - - - - - - - - - - - - - - - - - - - - - - 6-45 origin search (Fn003) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-6 output signal (CN1) allocations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-17 monitoring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-7 names and functions- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-9 overtravel (OT) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-6 overtravel warning function- - - - - - - - - - - - - - - - - - - - - - - - - - - 4-8
P parameter classification- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-5 parameters for numeric settings - - - - - - - - - - - - - - - - - - -iv , 2-5 parameters for selecting functions - - - - - - - - - - - - - - - - -iv , 2-5 tuning parameters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-5 parameter recording table - - - - - - - - - - - - - - - - - - - - - - - - - - - 9-43 parameters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 9-3 position integral- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-89 positioning completed signal - - - - - - - - - - - - - - - - - - - - - - - - - 4-43 positioning near signal - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-44
P-OT - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-6 power supply capacities and power losses - - - - - - - - - - - - - - - - - 3-5 precautions for wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-7 precautions on connecting noise filter - - - - - - - - - - - - - - - - - - - 3-28 program JOG operation (Fn004) - - - - - - - - - - - - - - - - - - - - - - - 6-9 protection class/pollution degree - - - - - - - - - - - - - - - - - - - - - - - 1-4
R reference unit - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-20 reverse external torque limit - - - - - - - - - - - - - - - - - - - - - - - - - 4-26 rotation detection output signal - - - - - - - - - - - - - - - - - - - - - - - 4-41
S safety precautions on adjustment of servo gains - - - - - - - - - - - - - 5-8 servo alarm output signal - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40 servo gains - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-3 servo ready output signal - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-41 servomotor model display (Fn011)- - - - - - - - - - - - - - - - - - - - - 6-30 servomotor rotation direction - - - - - - - - - - - - - - - - - - - - - - - - - 4-5
SERVOPACK basic specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 inspection and maintenance - - - - - - - - - - - - - - - - - - - - - - 1-10
MECHATROLINK-III function specifications- - - - - - - - - - - 1-6 model designation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-9 part names - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2 precautions when using more than one SERVOPACK- - - - - - 3-6 ratings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-3 setting for S1 and S2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-4 setting motor overload detection level - - - - - - - - - - - - - - - - - - 4-16 settings for DIP switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-3 signal allocations- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-11 soft start time setting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 software limit settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-9 software reset (Fn030) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6-36 software version display (Fn012) - - - - - - - - - - - - - - - - - - - - - - 6-31 speed coincidence signal - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-42 speed control range - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 speed detection method selection - - - - - - - - - - - - - - - - - - - - - - 5-77 speed regulation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 stopping method for servomotor after SV_OFF command is received- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-15 stopping method for servomotor when an alarm occurs - - - - - - - - 8-2 storage temperature - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 surrounding air temperature - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4
SW1 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2
SW2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-2 switching condition A - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-72 switching gain settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-71
T test without motor function - - - - - - - - - - - - - - - - - - - - - - - - - - 4-22 torque control tolerance - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 torque reference filter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-87 trial operation inspection and checking before trial operation - - - - - - - - - - 4-18 trial Operation via MECHATROLINK-III- - - - - - - - - - - - - 4-19 troubleshooting alarms - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-6 warnings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-19 troubleshooting malfunction based on operation and conditions of the servomotor - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8-24 tuning parameters - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 2-5 tuning-less function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 5-11 tuning-less level settings (Fn200)- - - - - - - - - - - - - - - - - - - - - - 5-12
U
UL - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - xiv using the mode switch (P/PI switching) - - - - - - - - - - - - - - - - - 5-85 utility functions (Fn )- - - - - - - - - - - - - - - - - - - - - - - - 6-2 , 9-2
V vibration detection level initialization (Fn01B) - - - - - - - - - - - - 6-32 vibration suppression function (Fn205)- - - - - - - - - - - - - - - - - - 5-64 vibration/shock resistance- - - - - - - - - - - - - - - - - - - - - - - - - - - - 1-4 viewing monitor displays - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7-3
W warning output signal- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-40 wiring examples - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-4 wiring for noise control - - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-26 wiring MECHATROLINK-III communications - - - - - - - - - - - - 3-23
Index-2
Index write prohibited setting (Fn010) - - - - - - - - - - - - - - - - - - - - - - - 6-28
Z zero clamp mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4-7
Index-3
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
MANUAL NO. SIEP S800000 83A <0>-1
Published in Japan April 2012
WEB revision number
Revision number
Date of publication
M-III
Date of
Publication
December 2016
July 2015
April 2012
November 2011
Rev.
No.
<1>
WEB
Rev.
No.
1 3.1.7
Section
<0>
–
0
1
–
Back cover
–
3.6.2, 4.7.1
4.3.3 (3)
4.5.1 (2)
8.1.1, 8.1.2
9.1.2
9.1.2, 9.3
Front cover
Back cover
3.1.4, 3.1.5
8.1.2
Back cover
–
Revised Content
Addition: Precaution when wiring a magnetic contactor on the DC side of the main circuit power supply
Revision: Address
Same revisions made as Web version SIEP S800000 83A<0>-1.
Revision: Information on battery for encoder
Revision: Factory settings of parameters
Addition: Information on rated motor speed and maximum motor speed
Addition: Information on A.bE0 and A.F50
Revision: Information on reserved parameters
Addition: Information on Pn52D, Pn860 to Pn863, Pn868, Pn869 and Pn884
Revision: Format
Revision: Address, format
Revision: Values of power supply capacity and input current capacity
Revision: Detection conditions calculation formula
Revision: Address
First edition
AC Servo Drives
DC Power Input
-
V
Series
USER'S MANUAL
Design and Maintenance
Rotational Motor
MECHATROLINK-
III
Communications Reference
IRUMA BUSINESS CENTER (SOLUTION CENTER)
480, Kamifujisawa, Iruma, Saitama, 358-8555, Japan
Phone 81-4-2962-5151 Fax 81-4-2962-6138 http://www.yaskawa.co.jp
YASKAWA AMERICA, INC.
2121, Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone 1-800-YASKAWA (927-5292) or 1-847-887-7000 Fax 1-847-887-7310 http://www.yaskawa.com
YASKAWA ELÉTRICO DO BRASIL LTDA.
777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil
Phone 55-11-3585-1100 Fax 55-11-3585-1187 http://www.yaskawa.com.br
YASKAWA EUROPE GmbH
185, Hauptstra β e, Eschborn, 65760, Germany
Phone 49-6196-569-300 Fax 49-6196-569-398 http://www.yaskawa.eu.com
YASKAWA ELECTRIC KOREA CORPORATION
9F, Kyobo Securities Bldg. 26-4, Yeouido-dong, Yeongdeungpo-gu, Seoul, 150-737, Korea
Phone 82-2-784-7844 Fax 82-2-784-8495 http://www.yaskawa.co.kr
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151, Lorong Chuan, #04-02A, New Tech Park, 556741, Singapore
Phone 65-6282-3003 Fax 65-6289-3003 http://www.yaskawa.com.sg
YASKAWA ELECTRIC (THAILAND) CO., LTD.
59, 1st-5th Floor, Flourish Building, Soi Ratchadapisek 18, Ratchadapisek Road, Huaykwang, Bangkok, 10310, Thailand
Phone 66-2-017-0099 Fax 66-2-017-0799 http://www.yaskawa.co.th
YASKAWA ELECTRIC (CHINA) CO., LTD.
22F, One Corporate Avenue, No.222, Hubin Road, Shanghai, 200021, China
Phone 86-21-5385-2200 Fax 86-21-5385-3299 http://www.yaskawa.com.cn
YASKAWA ELECTRIC (CHINA) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No.1, East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone 86-10-8518-4086 Fax 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign
Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2011-2016 YASKAWA ELECTRIC CORPORATION
MANUAL NO. SIEP S800000 83B <1>-1
Published in Japan December 2016
15-8-11
Original instructions
Download