YASKAWA V7 Drive is a versatile and powerful drive that offers a wide range of features to meet the demands of various industrial applications. With full range DC injection and trim control capabilities, it provides precise motor control and enhanced performance. The drive's advanced functionality, including multi-function digital inputs and flexible parameter settings, allows for customization and integration into complex systems.
Oglas
Oglas
A World of Automation Solutions
TM
CUSTOM SOFTWARE DESCRIPTION
DC INJECTION AND
TRIM CONTROL
Software Number: VSP018262 / VSP018252
Product: V7 Low & High HP
Base Version: VSP010026 / VSP010105
Model Number: CIMR-V7AUXXXX1-052
Release Date: 5/14/03 Author: Ty Phillips Beta Version
Overview: Full range DC injection and DC injection via multi-function input functions are added.
Trim control increase/decrease by multi-function input is also included. This manual covers both the low horsepower version VSP018262 and the high horsepower version VSP018252.
Revision History:
Date: 07/01/04, Rev: 04-07 Page 1 of 6 TM.V7SW.052
1.0 Overview:
This software adds full range DC injection, as well as a DC injection command as a multi-function input selection. DC injection causes DC current to flow in the motor windings, which aligns the motor poles and provides deceleration and/or holding torque.
A trim control feature for the frequency reference (similar to the GPD515/G5 function) is also included.
This allows for increasing or decreasing (trimming) of the frequency reference by a programmed amount through a multi-function input contact closure.
2.0 Related Parameters:
No.
Modbus
Address
Parameter Description
Stop Method:
Unit Setting Range Default
2: Full range DC injection
Trim control level at maximum frequency (n011). 100% = n011
(maximum frequency).
Trim control level at minimum n046 012EH
(maximum frequency). n089 0159H DC Injection Current n090 0015A DC Injection Time at Stop n091 0015B DC Injection Time at Start n170 01AAH Minimum Baseblock Time
0.1%
0.1%
1%
0.1 sec
0.1 sec
0.1 sec
0.0 ~ 100.0
0.0 ~ 100.0
0 ~ 100
0 ~ 25.5
0 ~ 25.5
0.1 ~ 1.0
*1
*1
10.0
10.0
50
0.0
0.0
0.5
*1: It is not possible to set n045 less than n046 or to set n046 greater than n045. . If n045 < n046 due to setting by communication, an “oP9” alarm will be displayed.
3.0 Additional Multi-function Input Settings (n050 ~ n056):
Setting Description
28 DC Injection Command
29
30
Trim Control Increase
Trim Control Decrease
When n050 ~ n056 = 28, the corresponding input terminal (S1 ~ S7) is used for commanding DC
Injection.
When n050 ~ n056 = 29/30, the corresponding input terminals (S1 ~ S7) are used for the frequency reference trim control increase/decrease function.
Date: 07/01/04, Rev: 04-07 Page 2 of 6 TM.V7SW.052
4.0 Description of Functionality:
4.1 Full Range DC Injection
When n005 = 2 and the run command is removed, the drive will Baseblock for the time in parameter n170
(Minimum Baseblock Time) and then apply DC injection. The DC injection time is based on n090 (DC
Injection Time at Stop) and output frequency as shown below. Although the minimum Baseblock time can be set as low as 0.1 Sec, caution should be observed when setting this parameter to avoid
Overvoltage or Overcurrent faults. The acceptable minimum setting will vary based on the motor and application.
Output
Frequency n090 x 10
Sec
DC Injection Time = T n170
Baseblock
Time
T n090 (DC Injection
Time at Stop) n011 x 10% n011
(Max Frequency)
Output Frequency
(when run command is removed)
Hz
Run
Command
Figure 1.0 Full Range DC Injection Timing Chart and Time Calculation Graph
Date: 07/01/04, Rev: 04-07 Page 3 of 6 TM.V7SW.052
4.2 DC Injection Multi-function Digital Input Command
• The DC Injection command will be active under the following conditions: the inverter is ready (i.e. not in program mode or in a fault state), no run command is present, and the output frequency is less than the Minimum Frequency (n016).
• The DC Injection Current Level is set by the standard parameter n089 (as a percentage of inverter rated current).
• The DC Injection at Start and DC Injection at Stop parameters n090 and n091 have priority over the external DC Injection command.
• Full range DC injection (n005 = 2) has priority over the external DC Injection command.
• The External Baseblock command has priority over the external DC Injection command.
• The RUN LED on the digital operator will be lit solid when the DC injection command is closed.
Run
Command
DC Injection
Command
10ms
Baseblock *
Output
Frequency
DC Injection DC Injection
* To prevent the 10ms Baseblock at the end of deceleration, set the DC Injection Time at Stop (n090) to 0.1 sec.
Figure 2.0 Multi-function Input DC Injection Command Timing Chart
Date: 07/01/04, Rev: 04-07 Page 4 of 6 TM.V7SW.052
4.3 Frequency Reference Trim Control Function
When the trim control increase multi-function input is closed, the control trim level will be added to the frequency reference. When the trim control decrease multi-function input is closed, the trim control level will be subtracted from the frequency reference. The inverter must be in remote mode and the frequency reference must be non-digital (n004 ≠ 1) for trim control to function. Also, trim control is disabled when any of the multi-step speed reference inputs are closed. The trim control level is determined by the frequency reference, n045 (Trim Control Level at Max Frequency), and n046 (Trim Control Level at Min
Frequency). See Figures 3.0 and 4.0 below.
% n045 (Trim control level at max frequency)
Trim Control Level n046 (Trim control level at min frequency) n016
(Min Frequency)
Frequency Reference
(Before Trim Control) n011
(Max Frequency)
Hz
Figure 3.0 Frequency Reference Trim Control Level Calculation Graph
Date: 07/01/04, Rev: 04-07 Page 5 of 6 TM.V7SW.052
n045 (Trim Control Level at Max Frequency) n046 (Trim Control Level at Min Frequency)
Frequency Reference
(Before Trim Control) n033, n034
Frequency Reference
Upper / Lower limit
Trim Control Increase
Multi-function Input
400 Hz
+
+
+
-
Trim Control Decrease
Multi-function Input n033, n034 n083 - n085
Frequency
Reference
Upper / Lower
Limit
Jump
Frequencies n016
Minimum
Frequency
Figure 4.0 Frequency Reference Block Diagram Including Trim Control
400 Hz
Frequency
Reference
Date: 07/01/04, Rev: 04-07 Page 6 of 6 TM.V7SW.052