GEH-6259 Installation Instructions

Voltage Conditioner Assembly

For use with microEntelliGuard*, EntelliGuard TU, MicroVersaTrip* PM or MicroVersaTrip* Plus Trip Units

For Catalog Number GMPU5, GMPU6, & GMPU7

UL Listed Circuit Breaker Accessory

The voltage conditioner assembly is designed to operate in temperatures between 0°C and 70°C. It requires a power supply source of +24Vdc to operate properly with the microEntelliGuard,

MicroVersaTrip PM or MicroVersaTrip Plus Trip Units in Spectra

Molded Case Circuit Breakers. The power supply assembly

(catalog number SPSAA) or power supply plate (catalog number

SPSA120, SPSA208, SPSA240, SPSA480 or SPSA600) can provide this required input. This input is not required for operation with Insulated Case or Air Circuit Breakers.

The unit also requires direct AC voltage inputs from the AC source. The voltage conditioner assembly is available in three variations (shown in Table 1), each supporting three different voltages, for a total of 9 voltage ratings.

Overview

The General Electric voltage conditioner assembly is used to provide voltage-sensing signals to microEntelliGuard,

EntelliGuard TU, and MicroVersaTrip PM/Plus Trip Units.

The assembly has the maximum capacity to provide voltage-sensing signals to a Spectra Distribution Cable System consisting of 20 combined trip units with a maximum system cable length of 40 feet. When used with Insulated Case or

Air Circuit breakers, the max is 15 trip units at a max distance of 20 feet.

Table 1. GE Voltage Conditioner Assemblies

Catalog

Number

GMPU5

GMPU6

GMPU7

Position 1

230

340

600

Source Voltage

Position 2

208

277

480

Position 3

120

240

400

imagination at work

To switch between voltages in the system the user must use the selector switch to select the correct voltage. If the voltage switch is not correct it may result in incorrect metering and voltage reading of the trip unit. To remind the user of this, each unit comes with position indicators to show which position corresponds to which voltage. (See Figure 1.)

Figure 1. Voltage Selector Switch – slide switch to the correct position corresponding to the position diagram

2 GEH-6257 Installation Instructions

Dimensions

A voltage conditioner assembly dimensioned drawing is provided in Figure 2 to assist in mounting the accessory. It is recommended that the accessory be mounted via 35mm DIN rail. The Din

Rail slot is located on the back of the assembly. It runs directly through the center of the assembly horizontally. DIN rail clips are available on the top and bottom of the unit.

160.0

13.6

TYP

52.6

TYP

14.0

DIN rail clips

8.0

90.0

43.0

8.0

14.0

156.0

58.0

12.33

28.96

28.96

Figure 2. Voltage Conditioner Assembly Dimensions (mm)

12.33

3 GEH-6257 Installation Instructions

Connections

The voltage conditioner assembly contains five connection points. The following list contains a description of each.

1

Figure 3. Voltage Conditioner Connections

2 3 4 5

1. AC Input Voltage Side

Six-screw terminals for connection of the primary AC source.

The screw terminals are labeled by function for clarity. The terminal strip pockets on the AC input side accommodate wire up to 12 AWG. To make the connection simply strip the wire, leaving approximately 0.30 inches exposed, insert the wire into the connector and screw the terminal down.

The connection pattern depends on if the system is configured in either Wye or Delta. The two possible ways to connect the

AC voltage input side are detailed below.

2. To Power Supply Cat. No. SPSAA

12-pin plug connector that mates with the 12-pin connector of the distribution cable harness (catalog number SDCHA11,

SDCHA30 or SDCHA60). The other end of the harness MUST mate to either a power supply assembly (catalog number

SPSAA) or a power supply plate (catalog number SPSA120,

SPSA208, SPSA240, SPSA480 OR SPSA600). Failure to do so will result in the absence of a voltage-sensing signal and inaccuracies in voltage dependent information / metering at

Spectra RMS Molded-Case Circuit Breakers.

3. Output to ACB/ICCB

Four-screw terminal block for optional voltage-sensing signal output to MicroVersaTrip PM or EntelliGuard™ TU Trip Units in

Air Circuit Breakers and/or Insulated Case Circuit Breakers.

(Do not connect this voltage signal to a Spectra trip unit. The voltage signal structure is different between the MCCB and

ACB/ICCB trip unit platforms.)

Figure 4. AC Voltage Wiring Configurations (Note: The voltage conditioner has internal fuses to protect itself, the external fuses shown here are for additional protection if desired)

4 GEH-6257 Installation Instructions

4. COM

Two-screw terminal block for connection to communications network. A communications connection is provided for applications where data is transmitted to an external intelligent device (see Table 2).

Table 2. Associated Software and Protocol for the different Spectra

Series Breakers

Trip Unit Type

MicroVersaTrip PM

microEntelliGuard

Protocol

Commnet

Modbus

Software

GE POWER LEADER*

EnerVista Viewpoint

5. To Distribution Cable for Spectra MCCB

12-pin plug connector that mates with the 12-pin connector of a distribution cable harness (catalog number SDCHA11,

SDCHA30 or SDCHA60). The distribution cable system is used to interconnect the voltage signal on the voltage conditioner plate and the Spectra RMS Molded-Case Circuit Breakers.

The 12-pin connectors are keyed so they cannot be inserted incorrectly into a mating 12-pin receptacle connector. To connect to the voltage conditioner plate plug(s), align the receptacle interlock connector of a distribution cable harness with the plug hook connector of the voltage conditioner plate.

Insert the receptacle until the interlock and hook catch (see

Figure 5). To disconnect from the voltage conditioner plate, press down at the rear of the receptacle interlock until the interlock clears the plug hook, and withdraw the receptacle interlock (see Figure 6).

Figure 5. Side view of receptacle-plug insertion into voltage conditioner assembly

Figure 6. Side view of receptacle-plug removal from the voltage conditioner assembly

5 GEH-6257 Installation Instructions

Spectra RMS Molded Case Circuit Breaker Connection System

Figure 7 shows how the voltage conditioner assembly is used in a typical system.

Figure 7. Typical system showing voltage conditioner assembly

By plugging the voltage conditioner plate into the distribution cable system you create system wide signals that are available to all breakers connected to the system; a list of those functions appears in Table 3.

Table 3. Signals available on the Distribution Cable System by connection of the Voltage Conditioner Assembly

Spectra RMS Breaker with microEntelliGuard or MicroVersaTrip PM Trip Unit

System communications (Comm. +)

System communications (Comm. -)

Voltage 1 (defined as potential between A & N or between A & C)

Voltage 2 (defined as potential between B & N or between C & B)

Voltage 3 (defined as potential between C & N or between B & A)

+24V Aux Power (not provided by the voltage conditioner assembly)

24V Ground Line (not provided by the voltage conditioner assembly)

Spectra RMS Breaker with MicroVersaTrip Plus or

microEntelliGuard with Basic Metering Trip Unit

No signals available

A full breakout of the 12 pin connector can be viewed below.

6 GEH-6257 Installation Instructions

Parts and Options

The only user-serviceable components or parts on the voltage conditioner assembly are fuses internal to the device. The recommended replacement internal fuse is: LittleFuse part number 508.500MXP. Failure to use the proper type of fuses can result in damage to the accessory. Three fuses per voltage conditioner assembly are required. This fuse should only need to be replaced in the event of a fault or incorrect usage, ensure the issue is fixed prior to fuse replacement.

To replace the fuses, first disconnect the primary voltage from the unit to eliminate any voltage potential on the unit (if this step is not completed the user can be exposed to live voltages), and then lift the plastic tabs on the housing. After removing the housing the fuses will be easily distinguishable and are easily replaced. (See Figure 8.)

Figure 8. Voltage conditioner assembly fuses and housing

7 GEH-6257 Installation Instructions

Additional Information

Refer to these other user’s manuals for more details·:

GEH-5934 MicroVersaTrip Plus and MicroVersaTrip PM Trip

Units in Spectra RMS Molded-Case Circuit Breakers

GEH-5946 POWER LEADER Voltage Conditioner

GEH-700 Spectra G Breaker w/ microEntelliGuard Trip Unit

GEH-701 Spectra K Breaker w/ microEntelliGuard Trip Unit

GEH-702 microEntelliGuard Trip Unit Users Manual

DEH-41318 Universal Rating Plug

GEH-6250 Voltage Module

GEH-6251 Power Supply Plate

GEH-6253 Power Supply Assembly

GEH-6254 Voltage Conditioner Assembly

GEH-703 MET Battery Pack Adapter

GEH-704 MET Advanced Distribution Cable Junction Box

DEH-006 Distribution Cable Junction Box

GEH-705 MET Distribution Cable Extension (20-pin)

GEH-6256 Distribution Cable Extension (12-pin)

GEH-6255 Distribution Cable Harness (12-pin)

GEH-706 MET Distribution Cable Terminal Blocks (11 point

& 22 point)

GEH-6257 Distribution Cable Terminal Block (11 point)

GEH-6491 POWER LEADER Modbus Concentrator

GEH-6502 POWER LEADER PMCS 5.0 Network Architecture

Guide

GEH-707 MET Sealable Cover kits

DEH-4568 GTU digital test kit (GTUTK20)

GEH-5551 Shunt Trip and UVR instructions

GEH-5593 Aux switch and bell alarm

GEK-64467 TIM-1 Zone Selective Interlock Module

GE

41 Woodford Avenue

Plainville, CT 06062 www.geindustrial.com/groundfaultselftest

© 2015 General Electric Company

* Indicates a trademark of the General Electric Company and/or its subsidiaries.

Information provided is subject to change without notice. Please verify all details with GE. All values are design or typical values when measured under laboratory conditions, and GE makes no warranty or guarantee, express or implied, that such performance will be obtained under end-use conditions.

GEH-6259 8/15