Premium and Atrium using EcoStruxure™ Control Expert
35006224 12/2018
Premium and Atrium using
EcoStruxure™
Control Expert
Motion Control Modules for Step by Step
Motor
User Manual
(Original Document)
12/2018 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this document on any medium whatsoever without permission of Schneider Electric, given in writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2018 Schneider Electric. All rights reserved.
35006224 12/2018
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part I The servo drive axis control in Premium PLCs. . . . .
Chapter 1 General on step by step axes control . . . . . . . . . . . . . . .
Presentation of the step by step axes control range . . . . . . . . . . . . . .
Functionality offered by the axes control modules . . . . . . . . . . . . . . .
General on the step by step axes control . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Introduction to step by step axis command . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Implementation methodology . . . . . . . . . . . . . . . . . . . . .
Installation Phase Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Introductory example . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of the example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the TSX CFY module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting the TSX CFY module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbolization of variables in the example . . . . . . . . . . . . . . . . . . . . .
Programming preliminary processing . . . . . . . . . . . . . . . . . . . . . . . . .
SFC Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming transitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming actions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming subsequent processing . . . . . . . . . . . . . . . . . . . . . . . . .
Taking over in manual mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Debugging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part II TSX CFY axis control modules. . . . . . . . . . . . . . . . .
Chapter 5 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Base configuration necessary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General precautions for wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
61
62
63
53
55
57
59
46
47
49
51
35
38
39
43
27
29
30
34
22
23
24
27
16
17
19
21
7
11
13
15
35006224 12/2018
3
4
5.2 Connection of translator signals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signal labeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection to a translator with RS 422/485 interface . . . . . . . . . . . . .
Connecting to a translator with NPN open collector interface . . . . . . .
Overview of the TSX TAP S15xx wiring accessories. . . . . . . . . . . . . .
5.3 Connecting sensors/pre-actuators and supply modules . . . . . . . . . . .
Signal labeling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting auxiliary inputs and outputs to processor.. . . . . . . . . . . . .
Principle of connecting I/O channel 0. . . . . . . . . . . . . . . . . . . . . . . . . .
Connection using a TSX CDP 301/501 pre-wired strand. . . . . . . . . . .
Connection with TELEFAST pre-wiring system . . . . . . . . . . . . . . . . . .
Availability of signals on TELEFAST . . . . . . . . . . . . . . . . . . . . . . . . . .
Correspondence between TELEFAST terminals and HE10 connector
Wiring precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6 Characteristics and maintenance of the TSX CFY. . . . . .
General characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Characteristics of translator inputs (SUB-D connector) . . . . . . . . . . . .
Characteristics of translator outputs (SUB-D connector) . . . . . . . . . . .
Characteristics of auxiliary inputs (HE10 connector) . . . . . . . . . . . . . .
Characteristics of Q0 brake output. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Programming step by step axes control . . . . . . . . . . . . . .
Principles of programming a step by step axis. . . . . . . . . . . . . . . . . . .
Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming the SMOVE function (in automatic mode) . . . . . . . . . .
Inputting SMOVE function parameters. . . . . . . . . . . . . . . . . . . . . . . . .
Description of the SMOVE function parameters . . . . . . . . . . . . . . . . .
Instruction codes for the SMOVE function . . . . . . . . . . . . . . . . . . . . . .
Description of basic movements with the SMOVE function . . . . . . . . .
Description of SMOVE instruction codes . . . . . . . . . . . . . . . . . . . . . . .
Example of using an indexed position (repetitive movements) . . . . . .
Movement command sequencing . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Deferred PAUSE function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Feed hold function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Event processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Managing operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Managing faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of external hardware faults . . . . . . . . . . . . . . . . . . . . . . . .
95
97
98
100
102
104
109
111
89
91
93
94
84
85
86
87
113
115
117
119
120
123
77
78
80
83
72
73
75
76
68
69
70
71
64
65
66
67
35006224 12/2018
Description of application faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of the command refused faults . . . . . . . . . . . . . . . . . . . . .
Management of manual mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Visual movement commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Incremental movement commands . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference point command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Forced reference point command . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Management of direct mode (DIRDRIVE) . . . . . . . . . . . . . . . . . . . . . .
Management of stop mode (OFF) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8 Configuring step by step axes control. . . . . . . . . . . . . . .
Description of the configuration screen of an axis control module . . .
Access to the parameters configuration screen . . . . . . . . . . . . . . . . .
Configuring user units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the translator’s command mode. . . . . . . . . . . . . . . . . . . .
Configuring control parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring translator inversion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring translator boost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the step by step motor’s brake . . . . . . . . . . . . . . . . . . . . .
Configuring event tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference point configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Validating the configuration parameters . . . . . . . . . . . . . . . . . . . . . . .
Chapter 9 Adjusting step by step axes control . . . . . . . . . . . . . . . .
Preliminary operations before adjustment . . . . . . . . . . . . . . . . . . . . . .
Accessing adjustment parameters . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trajectory adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting brake output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting the stop stage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting manual mode parameters . . . . . . . . . . . . . . . . . . . . . . . . . .
Confirmation of adjustment parameters . . . . . . . . . . . . . . . . . . . . . . .
Saving / Restoring adjustment parameters . . . . . . . . . . . . . . . . . . . . .
Reconfiguration in connected mode . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 10 Debugging a step by step axes control program . . . . . .
Debugging principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User interface of the debug screen . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of the debug screens . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Detailed Information on the Debug Screen . . . . . . . . . . . . . . . . . . . . .
Stop Mode (Off) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Direct Mode (Dir Drive) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35006224 12/2018
164
166
168
170
171
172
173
175
149
150
151
152
157
159
160
161
176
178
180
182
186
187
136
137
138
140
142
144
146
148
125
126
127
129
131
132
133
134
5
6
Manual mode (Man.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Automatic mode (Auto) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Channel diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
188
189
190
191
Storage, document and simulation. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 11 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
193
Designing an operator dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
193
Chapter 12 Diagnostics and maintenance . . . . . . . . . . . . . . . . . . . . .
195
Fault monitoring and command execution commands. . . . . . . . . . . . .
Diagnostic help. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimension learning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
196
197
Chapter 13 Complementary functions. . . . . . . . . . . . . . . . . . . . . . . . .
201
201
Chapter 14 Characteristics and performance . . . . . . . . . . . . . . . . . . .
205
Performance characteristics and limitations. . . . . . . . . . . . . . . . . . . . .
205
Chapter 15 Application-specific step by step axes control language objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
209
Introduction to the language objects of the application-specific step by step axes control function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Implicit Exchange Language Objects Associated with the Application-
Specific Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Explicit Exchange Language Objects Associated with the Application-
Specific Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Management of Exchanges and Reports with Explicit Objects . . . . . .
210
211
212
214
Internal control objects (implicit exchange) of the IODDT of type
T_STEPPER_STD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal control objects (implicit exchange) of the IODDT of type
T_STEPPER_STD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal control objects (explicit exchange) of the IODDT of type
T_STEPPER_STD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Objects of the adjustment parameters (explicit exchanges) of the
IODDT of the T_STEPPER_STD type . . . . . . . . . . . . . . . . . . . . . . . . .
Exchanges between the processor and the axes control module . . . .
List of error codes CMD_FLT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Details of the Language Objects of the T_GEN_MOD-Type IODDT . .
218
220
222
224
225
226
230
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
231
35006224 12/2018
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
35006224 12/2018
7
8
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
BEFORE YOU BEGIN
Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine.
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on factors such as the control function required, degree of protection required, production methods, unusual conditions, government regulations, etc. In some applications, more than one processor may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and factors present during setup, operation, and maintenance of the machine and, therefore, can determine the automation equipment and the related safeties and interlocks which can be properly used. When selecting automation and control equipment and related software for a particular application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as pointof-operation guarding must be provided. This is necessary if the operator's hands and other parts of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software cannot be substituted for or take the place of point-of-operation protection.
35006224 12/2018
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have been installed and are operational before placing the equipment into service. All interlocks and safeties related to point-of-operation protection must be coordinated with the related automation equipment and software programming.
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation protection is outside the scope of the Function Block Library, System User Guide, or other implementation referenced in this documentation.
START-UP AND TEST
Before using electrical control and automation equipment for regular operation after installation, the system should be given a start-up test by qualified personnel to verify correct operation of the equipment. It is important that arrangements for such a check be made and that enough time is allowed to perform complete and satisfactory testing.
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not installed according to local regulations (according to the National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
35006224 12/2018
9
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
10
35006224 12/2018
About the Book
At a Glance
Document Scope
This manual describes the software implementation of the motion control application for step by step motors in Premium PLC’s, using Control Expert software.
Validity Note
This documentation is valid for EcoStruxure™ Control Expert 14.0 or later.
The technical characteristics of the devices described in the present document also appear online.
To access the information online:
Step
1
2
3
4
5
6
Action
Go to the Schneider Electric home page www.schneider-electric.com
.
In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks ( * ).
If you entered a reference, go to the Product Datasheets search results and click on the reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the product range that interests you.
If more than one reference appears in the Products search results, click on the reference that interests you.
Depending on the size of your screen, you may need to scroll down to see the data sheet.
To save or print a data sheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.
35006224 12/2018
11
Related Documents
Title of documentation
Premium and Atrium using EcoStruxure™ Control Expert, Processors, racks and power supply modules, Implementation Manual
Premium and Atrium using EcoStruxure™ Control Expert, Axis Control
Modules for Servomotors, User Manual
EcoStruxure™ Control Expert, Operating Modes
EcoStruxure™ Control Expert, I/O Management, Block Library
Reference number
35010524 (English),
35010525 (French),
35006162 (German),
35012772 (Italian),
35006163 (Spanish),
35012773 (Chinese)
35006220 (English),
35006221 (French),
35006222 (German),
35014004 (Italian),
35006223 (Spanish),
35014005 (Chinese)
33003101 (English),
33003102 (French),
33003103 (German),
33003104 (Spanish),
33003696 (Italian),
33003697 (Chinese)
33002531 (English),
33002532 (French),
33002533 (German),
33003684 (Italian),
33002534 (Spanish),
33003685 (Chinese)
You can download these technical publications and other technical information from our website at
www.schneider-electric.com/en/download
.
Product Related Information
WARNING
UNINTENDED EQUIPMENT OPERATION
The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter, and apply this product.
Follow all local and national safety codes and standards.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
12
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Step by step axis control
35006224 12/2018
The servo drive axis control in Premium PLCs
Part I
The servo drive axis control in Premium PLCs
Aim of the part
This part offers an overview of the step by step axis control range and describes the methodology for the installation of the axes.
What Is in This Part?
This part contains the following chapters:
Chapter
1
2
3
4
Chapter Name
General on step by step axes control
Introduction to step by step axis command
Implementation methodology
Introductory example
Page
35006224 12/2018
13
Step by step axis control
14
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
General
35006224 12/2018
General on step by step axes control
Chapter 1
General on step by step axes control
Subject of this chapter
This chapter introduces step by step axes control, describes it and the associated applicationspecific functions.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Presentation of the step by step axes control range
Functionality offered by the axes control modules
General on the step by step axes control
Page
35006224 12/2018
15
General
Presentation of the step by step axes control range
Introduction
The diagram below shows the control architecture for step by step axes:
Step by step axes control environment
The step by step axes control environment for Premium PLCs is made up of 2 modules:
TSX CFY 11 (1 limited linear axis),
TSX CFY 21 (2 independently limited linear axes).
The Control Expert software includes the basic application-specific step by step movement function, used to program these step by step axes control modules.
Basic movements are driven from the machine’s principal sequential control program, but carried out and controlled by the TSX CFY modules.
These modules control the rotation speed of a step by step motor, as well as its accelerations and decelerations, by delivering a frequency control to a translator (fmax = 187 KHz). The translator transforms each pulse into a basic movement of the step by step motor.
Control of the step by step motor is carried out in open loop. End of run, reference point and event inputs allow the module to control the movements of the moving part on the axis.
Some translators include a step failure mechanism: this information is made available to the user program, which can create a new reference point.
The step by step axes control environment also includes the TSX CXP 611 cable to link the TSX
CFY11/21 modules directly to the MSD and MS translators from the manufacturer Phyton Lektronik
GmbH.
16
35006224 12/2018
General
Functionality offered by the axes control modules
General
The axes control modules offer application inputs and outputs for each axis which allow you to implement the different functions.
The following structural breakdown presents the inputs/outputs associated to a channel:
Application inputs/outputs
The step by step axes control modules offer for each of the axes: for auxiliary inputs/outputs:
one cam reference point input, two end of run inputs, one event input, one emergency stop input, one external stop input, one static output for the axis brake.
35006224 12/2018
17
General
for translator inputs/inputs:
one translator check input, one step failure control input, one differential translator validation output, two differential pulse outputs, one positive, one negative, one differential step by step motor boost output, one differential step failure reset output.
Programming a movement
In Control Expert language, each movement is described by a SMOVE movement control function.
From this SMOVE command and the position of the moving part, the TSX CFY module creates the position/speed setpoint and generates the pulses for this movement.
Configuration and control parameters
These parameters are used to define the specifications of use, limits, etc.
Specific functions of the TSX CFY modules
The functions offered by the step by step axes control modules are as follows:
Event processing: the events detected by the module can be used to activate an event task in the sequential program.
Boost command: this function allows you to boost the step by step motor during acceleration or deceleration phases.
Brake command: this function allows you to control the brake of the step by step motor when starting and stopping the movement.
Feed hold: this function allows you to stop the movement in progress momentarily.
Deferred pause: this function allows you to stop a machine cycle momentarily without disrupting it.
End of run limits: overshooting these limits triggers the stopping of the movement. Having overshot an end of run limit, only return movements between the limits are accepted.
External stop: activation of the external stop input causes the movement to stop.
Step failure input and step failure control reset output: these functions allow you, via the application, to manage step failure information originating from the translator. For the module, the activation of step failure input does not constitute a stop condition, nor an error condition.
18
35006224 12/2018
General
General on the step by step axes control
Introduction to specific functions
The specific functions of step by step axes control apply to the whole control system made up of:
the command the translator the step by step motor.
The important ideas are as follows:
the start stop frequency SS_FREQ the boost the brake output
Diagram of the step by step axes control system
This diagram describes a typical step by step axes control system.
Description
Block
Command
Translator
Step by step motor
Description
The command function is carried out by a channel of a TSX CFY 11 or 21 module. The principal function of this channel is to provide a series of pulses of constantly controlled frequency, in order to carry out the required functions.
The translator’s essential function is to transform each received pulse into a step
(elementary rotation) of the motor, by circulating suitable currents in its windings.
Step by step motors are built according to different technologies. For example permanent magnet motors, variable reluctance motors and hybrid motors which combine the two techniques. Furthermore, different winding solutions exist on the market: two, four or five phase motors.
Each type of motor is thus associated with a specific type of translator optimized for its technology.
35006224 12/2018
19
General
Start stop frequency
The control of different step by step systems must generally obey a common restraint, due to the response of the inertial system (motor and axis) to a pulsed command. The common constraint is the start stop frequency.
The start stop frequency is the frequency at which the motor can stop or start without ramp and without losing step. Its maximum threshold depends upon the external inertia related to the motor axis. Its average value is 400 Hz in a 1/2 step (1 turn/sec) and can be critical beyond 600/800 Hz
(1.5 to 2 turns/sec) (typical values for Phytron Elektronik tranlators/200 step motors/lathes).
This constraint exists at the stopping as at the starting of all movements, whence its name: start stop frequency, SS_FREQ. The TSX CFY modules allow you to adjust this value.
NOTE: in this manual, the terms frequency and speed are used interchangeably. In the same way, the units of pulse position and pulse are the same. It is the same for the units of speed Hertz and
Pulses/s and the acceleration units Hertz/s and Pulses/s 2 .
Boost
Some translators have a boost input. This function consists in increasing the current in the motor windings.
The boost output from a channel of a TSX CFY module controls this input to the translator. It is thus possible to control the intensity of the motor current in synchronization with the movement. Notably automatic control mode for this output supports its activation during acceleration and deceleration phases.
Brake output
When a brake is present on the axis, this static output supports its control in synchronization with the movement or at the request of the user.
This function is useful when you want to interrupt the supply to the motor in load carrying applications.
NOTE: when the channel is in the safety position, this output makes the brake active (generally the brake is active when voltage is absent).
20
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Introduction
35006224 12/2018
Introduction to step by step axis command
Chapter 2
Introduction to step by step axis command
Subject of this chapter
This Chapter introduces the step by step axis command.
What Is in This Chapter?
This chapter contains the following topics:
Topic
General
Physical description
Standard functions
Page
35006224 12/2018
21
Introduction
General
Step by step axis command offer
The TSX CFY 11/21 step by step axis command for Premium PLCs is offered to satisfy the demands of the machine manufacturers.
It is designed for machines, which require a step by step movement command by a motor linked with a sequential command by a programmable PLC.
Illustration:
At a Glance
Two modules are available:
TSX CFY 11 module: an axis with a command output with one translator,
TSX CFY 21 module: two axes with two command outputs with two translators.
Illustration:
22
35006224 12/2018
Physical description
Description of step-by-step axis command modules.
TSX CFY 11 module:
TSX CFY 21:
Introduction
35006224 12/2018
23
Introduction
Standard functions
Illustration
Summary of step-by-step axis command module:
24
35006224 12/2018
Features of TSX CFY 11/21 step-by-step axis command modules
Each axis of TSX CFM 11/21 axis command modules has:
inputs
a translator check input,
an control input for loss of step, a + end limit input, a - end limit input, a reference point cam input,
an event input, an emergency stop input, an external stop input, outputs
brake output,
pulse+ output, pulse - output or direction, loss of step control reactivation output, boost output, translator enable output.
Introduction
35006224 12/2018
25
Introduction
26
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Methodology
35006224 12/2018
Implementation methodology
Chapter 3
Implementation methodology
Installation Phase Overview
Introduction
The software installation of the application-specific modules is carried out from the various Control
Expert editors:
in offline mode in online mode
If you do not have a processor to connect to, Control Expert allows you to carry out an initial test using the simulator. In this case the installation
( see page 28 )
The following order of installation phases is recommended but it is possible to change the order of certain phases (for example, starting with the configuration phase).
Installation Phases with Processor
The following table shows the various phases of installation with the processor:
Phase
Declaration of variables
Programming
Configuration
Description
Declaration of IODDT-type variables for the application-specific modules and variables of the project.
Project programming.
Declaration of modules.
Module channel configuration.
Entry of configuration parameters.
Mode
Offline (1)
Offline (1)
Offline
Association
Generation
Operation/
Diagnostic
Association of IODDTs with the channels configured (variable editor).
Project generation (analysis and editing of links).
Transfer
Adjustment/
Debugging
Transfer project to PLC.
Project debugging from debug screens, animation tables.
Modifying the program and adjustment parameters.
Documentation Building documentation file and printing miscellaneous information relating to the project.
Offline (1)
Offline
Online
Online
Online (1)
Displaying miscellaneous information necessary for supervisory control of the project. Online
Diagnostic of project and modules.
Key:
(1) These various phases can also be performed in the other mode.
35006224 12/2018
27
Methodology
Implementation Phases with Simulator
The following table shows the various phases of installation with the simulator.
Phase Description
Declaration of variables Declaration of IODDT-type variables for the application-specific modules and variables of the project.
Programming
Configuration
Project programming.
Declaration of modules.
Module channel configuration.
Entry of configuration parameters.
Mode
Offline (1)
Offline (1)
Offline
Association
Generation
Transfer
Simulation
Association of IODDTs with the modules configured (variable editor). Offline (1)
Project generation (analysis and editing of links). Offline
Transfer project to simulator.
Program simulation without inputs/outputs.
Online
Online
Online Adjustment/Debugging Project debugging from debug screens, animation tables.
Modifying the program and adjustment parameters.
Key:
(1) These various phases can also be performed in the other mode.
NOTE: The simulator is only used for the discrete or analog modules.
28
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Introductory example
35006224 12/2018
Introductory example
Chapter 4
Introductory example
Subject of this chapter
This chapter describes the implementation of an axes control application with the help of a TSX
CFY module. This instructional example allows you to follow all the phases necessary to the implementation of step by step axis control.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Description of the example
Prerequisites
Configuring the TSX CFY module
Adjusting the TSX CFY module
Symbolization of variables in the example
Programming preliminary processing
SFC Programming
Programming transitions
Programming actions
Programming subsequent processing
Taking over in manual mode
Debugging
Page
35006224 12/2018
29
Introductory example
Description of the example
Introduction
The following example allows you to follow all the implementation phases of a TSX CFY axes control application. It complements the set-up methodologies.
Transfer Device
A transfer device removes parts coming out of machining. This device is made up of a claw that can move in space (X, Y axes) on a plane parallel to the ground.
As soon as a part appears on output conveyor belt A, the claw automatically goes to fetch it and put it on belt B or belt C according to the part type. Then the claw returns to the stand-by position and will move again as soon as a new machined part is detected.
The following figure illustrates this transfer device:
30
35006224 12/2018
Introductory example
Inputs/outputs
The inputs/outputs are as follows:
I/O
C1
C2
C3
Description
Machined part detection cell
Sensor to identify the part type.
Grab open / grab closed detection sensor.
C4
ENC0
Part edge detection cell (located in the grab), connected to the module’s event input.
Incremental encoder in the X axis position.
ENC1 Incremental encoder in the Y axis position.
O/C grab Open / close claw command.
SFC of the application
The sequential graph of the application is as follows:
35006224 12/2018
31
Introductory example
Trajectory description
The following diagram shows the trajectory of the grab:
1 Reference point at speed Vp0,
2 Movement at speed Vret to the stand-by position (Xatt, Yatt) with stop,
3 Movement towards belt A (XA, YA) at speed VA, as far as detection of the machined part,
4 Movement towards conveyor B (XB, YB) at speed VB, with stop,
6 Movement towards conveyor C (XC, YC) at speed VC, with stop,
5, 7 Movement to waiting position (Xatt, Yatt) at speed Vret, with stop.
32
35006224 12/2018
Introductory example
Front Panel of the Human-Machine Interface
The following controls grouped on a panel, allow you to drive the moving part manually when the installation has failed. The controls and the indicators are managed by a discrete input module and a discrete output module.
Auto/Man. Operating mode selection switch.
Starting cycle Executes the automatic cycle.
Stop cycle Stops the automatic cycle.
Select axis X / Y Selects axis to be driven in manual mode.
Reference point Manual reference point on the selected axis.
Forward / Back Control for manual movement of the selected axis in a positive or negative direction.
Fault Indicator of all hardware faults and application errors.
Ack. Fault Fault acknowledgement control.
Emergency stop Immediate stop of the moving part whatever the selected mode.
Open grab Control for opening grab.
Close grab Control for closing grab.
35006224 12/2018
33
Introductory example
Prerequisites
Prerequisites
In order that only functions specific to axis control are described, it is assumed that the following operations have been carried out:
Control Expert software is installed,
The hardware installation has been carried out: modules, translators driving the 2 axes have been connected.
34
35006224 12/2018
Introductory example
Configuring the TSX CFY module
Software declaration in the PLC configuration
Start the Control Expert software, select the command File → New, select a Premium processor.
From within the Project Browser, access the configuration editor in the following way:
2
3
Step
1
Action
Open the folder Station (double click on the icon or click on its attachment).
Open the folder Configuration (double click on the icon or click on its attachment).
Double click on the icon Bus X.
You must then select each constituent of the PLC configuration. The following selections have been made in this application:
rack 0 and rack 1: TSX RKY 8EX, processor: TSX P57 204, supply modules: TSX PSY 2600 for rack 0 and TSX PSY 5500 for rack 1,
32 inputs module: TSX DEY 32D2K in position 3 of rack 0,
32 outputs module: TSX DSY 32T2K in position 4 of rack 0, axes control module: TSX CFY 21 in position 3 in rack 1,
35006224 12/2018
35
Introductory example
Example of a module configuration screen
36
35006224 12/2018
Introductory example
Enter the axes configuration parameters.
For each axis, enter the configuration parameters in the following way:
Step Action
1 Select position 3 in rack 1 then execute the command Edit → Open module (or double click on the selected module).
2 Configure the parameters of channel 0. To do that:
select channel 0,
select the function Positioning, select the task MAST, enter the parameters, in accordance with the following screen:
Configuration screen for channel 0
35006224 12/2018
3 Confirm your entries using the command Edition → Confirm or by clicking on the confirm icon.
4 Carry out the same configuration for channel 1 of the module by repeating the procedure from step
2 for channel 1.
37
Introductory example
Adjusting the TSX CFY module
Inputting axes adjustment parameters
For each axis, enter the configuration parameters in the following way:
Step Action
1 Select position 3 in rack 1 then execute the command Edit → Open module (or double click on the selected module).
2 Click on the Adjustment tab.
3 Configure the adjustment parameters for channel 0. To do this:
select channel 0,
enter the adjustment parameters, in line with the following screen:
Adjustment screen for channel 0
38
4 Confirm your entries using the command Edition → Confirm or by clicking on the confirm icon.
5 Carry out the same adjustments for channel 1 of the module by repeating the procedure from step
3 for channel 1
6 Then confirm the global configuration using the command Edit → Confirm or by clicking on the confirm icon
35006224 12/2018
Introductory example
Symbolization of variables in the example
Entering variables
Access to symbols entry is by means of a double-click in the Application browser, then on the icons
Variables and Elementary variables for example to obtain the following screen which permits the input of all the variables described in the following paragraphs.
Variables entry screen
Internal variables symbols
The following internal variables are symbolized:
Address Symbol
%M0 CYCLE
Comment
Condition of the machine in work mode
%MD50 X_STAND-BY Stand-by position (X axis)
%MD52 Y_STAND-BY Stand-by position (Y axis)
%MD54 X_B
%MD56 Y_B
%MD58 X_C
%MD60 Y_C
Position of belt B (X axis)
Position of belt B (Y axis)
Position of belt C (X axis)
Position of belt C (Y axis)
35006224 12/2018
39
Introductory example
Symbols for the discrete inputs module
The discrete inputs module is positioned in slot 3 in rack 0. Its symbols are as follows:
Address
%I0.3.0
%I0.3.1
%I0.3.2
%I0.3.3
%I0.3.4
%I0.3.5
I%I0.3.6
%I0.3.7
%I0.3.8
%I0.3.9
%I0.3.10
%I0.3.12
%I0.3.13
%I0.3.14
Symbol
SENSOR_1
SENSOR_2
SENSOR_3
AUTO_MAN
START_CYCLE
STOP_CYCLE
SELECTION_X_Y
PO_MAN
Forward
BACK
ACK_ERROR
EMERGENCY_STOP
OPEN_CLAW
CLOSE_CLAW
Comment
Detector to detect presence of machined part
Sensor to identify the part type (0 = type 2, 1 = type 1)
Sensor to detect claw open / claw closed
Switch to select mode (0 = Auto, 1 = Manual)
Push button to execute automatic cycle
Push button to stop automatic cycle
Select axis to drive in Manual mode (1 = X, 0 = Y)
Manual reference point
Move the moving part in the positive direction
Move the moving part in the negative direction
Fault acknowledgment
Emergency stop
Push button to open claw
Push button to close claw
Symbols for the discrete outputs module
The discrete outputs module is positioned in slot 4 in rack 0. Its symbols are as follows:
Address
%Q0.40.0
%Q0.4.1
Symbol
CLAW
Error
Comment
Command to open or close the claw (0 = Open, 1 = Close)
Signals an error
Internal constants
The speed of the moving part along the different axes is contained in the internal constants. In the case of 2 independent axes, the symbols and the values of these constants are as follows:
Address
%KD0
%KD4
%KD6
%KD8
%KD10
%KD12
Symbol
SPEED_O_C
Value
5000
SPEED_X_WAIT
SPEED_Y_WAIT
10000
10000
SPEED_POS_A_X 15000
SPEED_POS_A_Y 15000
SPEED_POS_B_X 15000
Comment
Speed from the reference point along the axis of the X and Y axes
Speed towards the X axis stand-by position
Speed towards the Y axis stand-by position
Speed towards the X axis belt A position
Speed towards the Y axis belt A position
Speed towards the X axis belt B position
40
35006224 12/2018
Introductory example
Address
%KD14
%KD16
%KD18
Symbol Value
SPEED_POS_B_Y 15000
SPEED_POS_C_X 12000
SPEED_POS_C_Y 12000
Comment
Speed towards the Y axis belt B position
Speed towards the X axis belt C position
Speed towards the Y axis belt C position
Symbols for the axes control module
The axes control module is positioned in slot 3 in rack 1. Its symbols are as follows:
Address
%CH1.3.0
%I1.3.0.9
Symbol
AXIS_X
AT_POINT
Address
%CH1.3.1
%I103.1.9
Symbol
AXIS_Y
AT_POINT_Y
Symbols of the axes control module linked to IODDT de type T_STEPPER_STD
The table below shows the T_STEPPER_STD type IODDT objects which are used for the two channels in the programming example:
Address
%Ir.m.c.0
%Ir.m.c.1
%Ir.m.c.2
%Ir.m.c.3
%Ir.m.c.4
%Ir.m.c.5
%Ir.m.c.6
%Ir.m.c.11
%Ir.m.c.12
%Ir.m.c.16
%Ir.m.c.17
%Ir.m.c.18
%Ir.m.c.19
%Ir.m.c.35
%Qr.m.c.0
%Qr.m.c.1
%Qr.m.c.2
%Qr.m.c.3
%Qr.m.c.4
%Qr.m.c.5
Standard symbol
NEXT
DONE
AX_FLT
AX_OK
HD_ERR
AX_ERR
CMD_NOK
CONF_OK
REF_OK
IN_DROFF
IN_DIRDR
IN_MANU
IN_AUTO
ST_DRIVE
DIRDRV
JOG_P
JOG_M
INC_P
INC_M
SET_RP
35006224 12/2018
41
Introductory example
Address
%Qr.m.c.6
%Qr.m.c.9
%Qr.m.c.10
%Qr.m.c.11
%MDr.m.c.22
Standard symbol
RP_HERE
ACK_FLT
ENABLE
EXT_EVT
RP_POS
42
35006224 12/2018
Introductory example
Programming preliminary processing
Introduction
Preliminary processing is a section at the beginning of the program that manages the operating modes:
With a blocking error:
The chart is disabled.
You can then drive the moving part in Manual mode, fix the error and acknowledge it from the panel.
The chart is reinitialized when the error is fixed and acknowledged.
On switching to Manual mode:
The chart is disabled.
The chart is reinitialized when Automatic mode is selected again.
Program in Ladder language
Initializing positions
35006224 12/2018
43
Introductory example
Starting cycle
Confirming controller
Selecting automatic mode
Selecting manual mode
44
35006224 12/2018
Disabling chart on error or when switching to manual mode
Introductory example
Reinitializing chart
Signaling errors
35006224 12/2018
45
Introductory example
SFC Programming
At a Glance
The SFC allows you to program the sequential handling of the application: automatic cycle processing.
Sequential processing
Representation of sequential processing:
46
35006224 12/2018
Introductory example
Programming transitions
At a Glance
Transitions drawn in the Grafcet are programmed in the following way:
Step 0 -> 1
! (*X channel not in error, claw open, Auto_man switch set to Auto, Y channel not in error and automatic mode activated*)
NOT Axis_ch0.Ax_flt AND NOT Capteur_3 AND NOT Auto_man AND Cycle AND NOT
Axis_ch1.Ax_flt AND Mode_Auto
Step 1 -> 2
! (*Test: axes ready and referenced*)
Axis_ch0.Done AND Axis_ch0.Ref_OK AND Axis_ch1.Done AND Axis_ch1.Ref_OK
Step 2 -> 3
! (*Moving part in stand-by position and part detected on belt A*)
Capteur_1 AND Cycle AND Axis_ch0.Next AND Axis_ch1.Next
Step 3 -> 4
! (*Moving part in position to take part detected on belt A*)
Axis_ch0.At_point AND Axis_ch0.Next AND Axis_ch1.Next AND
Axis_ch1.At_point
Step 4 -> 5
! (*Type 1 part and claw closed*)
Capteur_2 AND Capteur_3
Step 4 -> 8
! (*Type 2 part and claw closed*)
NOT Capteur_2 AND Capteur_3
Step 5 -> 6
! (*Moving part in position on conveyor belt B*)
Axis_ch0.At_point AND Axis_ch0.Next AND Axis_ch1.Next AND
Axis_ch1.At_point
35006224 12/2018
47
Introductory example
Step 8 -> 6
! (*Moving part in position on conveyor belt C*)
Axis_ch0.At_point AND Axis_ch0.Next AND Axis_ch1.Next AND
Axis_ch1.At_point
Step 6 -> 2
! (*Claw open*)
NOT Capteur_3 AND Cycle
48
35006224 12/2018
Introductory example
Programming actions
At a Glance
In Grafcet it is possible to program actions for each step. Three types of action are possible:
on activation continuous on deactivation
When for a given step the type of action is not described, this means that it has not been programmed.
Step 1: Action on activation
! (*Reference point taken along the X and Y axes*)
SMOVE (Axis_ch0, 1, 90, 14, 0, Vitesse_p_o, 16#0000);
SMOVE (Axis_ch1, 1, 90, 14, 0, Vitesse_p_o, 16#0000);
Step 2: Action on activation
! (*Movement to stand-by position (Xatt, Yatt*)
SMOVE (Axis_ch0, 2, 90, 9, X_attente, Vitesse_x_attente, 16#0000);
SMOVE (Axis_ch1, 2, 90, 9, Y_attente, Vitesse_y_attente, 16#0000);
Step 3: Action on activation
! (*Movement towards belt A*)
SMOVE (Axis_ch0, 3, 90, 10, 19500, Vitesse_pos_a_x, 16#0000);
SMOVE (Axis_ch1, 3, 90, 10, 19500, Vitesse_pos_a_y, 16#0000);
Step 4: Continuous action
! (*Close claw*)
SET(Claw);
Step 5: Action on activation
! (*Movement to conveyor belt B*)
SMOVE (Axis_ch0, 4, 90, 9, X_b, Vitesse_pos_b_x, 16#0000);
SMOVE (Axis_ch1, 4, 90, 9, Y_b, Vitesse_pos_b_y, 16#0000);
35006224 12/2018
49
Introductory example
Step 8: Action on activation
! (*Movement to conveyor belt C*)
SMOVE (Axis_ch0, 5, 90, 9, X_c, Vitesse_pos_c_x, 16#0000);
SMOVE (Axis_ch1, 5, 90, 9, Y_c, Vitesse_pos_c_y, 16#0000);
Step 6: Continuous action
! (*Open claw*)
RESET (Claw);
50
35006224 12/2018
Introductory example
Programming subsequent processing
Introduction
Subsequent processing is a section at the end of the program that manages the manual operating mode.
MAST - POST
! (*Test selected mode*)
IF Mode_auto AND Mode_auto_y AND Axis_ch0.Conf_ok AND Axis_ch1.Conf_ok
THEN JUMP %L200;
END_IF;
! (*Selecting the axis to be driven*)
%L100: IF NOT Selection_x_y
THEN JUMP %L200;
END_IF;
! (*Reference point taken manually on X axis*)
IF RE(Po_man)
THEN SET(Axis_ch0.Set_rp);
END_IF;
IF NOT Po_man
THEN RESET(Axis_ch0.Set_rp);
END_IF;
! (*Movement of the moving part in the + direction along the X axis*)
Jog_p := Front;
! (*Movement of the moving part in the - direction along the X axis*)
Jog_m := Back;
%L200: IF selection_x_y
THEN JUMP %L300;
END_IF;
! (*Reference point taken manually on Y axis*)
IF RE(Po_man)
THEN SET(Axis_ch1.Set_rp);
END_IF;
IF NOT Po_man
35006224 12/2018
51
Introductory example
THEN RESET(Axis_ch1.Set_rp);
END_IF;
! (*Movement of the moving part in the + direction along the Y axis*)
Axis_ch1.Jog_p := Front;
! (*Movement of the moving part in the - direction along the Y axis*)
Axis_ch1.Jog_p := Back;
! (*Open claw*)
%L300: IF Auto_man AND Ouv_pince
THEN RESET(Claw);
END_IF;
! (*Closure of the claw*)
IF Auto_man AND Ferm_pince
THEN SET(Claw);
END_IF;
! (*Error acknowledgement*)
Axis_ch0.Ack_def := Axis_ch1.Ack_def := Acq_defauts;
%L999:
52
35006224 12/2018
Introductory example
Taking over in manual mode
Accessing manual mode
If you want to move the moving part without first going through the programming phase, use
Manual mode. To do that, access the debug screen, in connected mode:
Step
1
2
3
4
Action
Activate the command Tools → Configuration.
Select the TSX CFY module to be opened.
Execute the command Services → Open the module (or double click on the module to be opened).
The following debug screen is then displayed:
35006224 12/2018
53
Introductory example
Movements in manual mode
To move the moving part in Manual mode, you must carry out the following operations:
Step
1
Action
2
3
4
5
6
7
Put the PLC into RUN mode, using the command AP → Run or by clicking on the icon
Select the axis to drive: channel 0 (X axis) or channel 1 (Y axis).
Select Manual mode by turning the switch to Man. mode.
Confirm the safety relays of the speed controller by clicking on the button Confirmation in the Axis box.
Acknowledge the errors by clicking on the button Ack in the Errors box.
Take a manual origin:
either by selecting the command Manual reference point,
or by selecting the command Forced reference point. In this case, first enter in the Param field, the value of the position of the moving part in relation to the origin.
Move the moving part:
in the positive direction by using the command JOG+,
or in the negative direction by using the command JOG-.
The position of the moving part is displayed in the field X and the speed is displayed in the field
F in the Movement / Speed box.
54
35006224 12/2018
Introductory example
Debugging
Debugging procedure
You can debug the program by proceeding in the following manner:
Step
1
2
3
4
Action
Put the PLC into RUN mode.
Display the debugging screen for the TSX CFY module.
Simultaneously display the Grafcet screen in order to follow the evolution of the sequential processing.
Start the program by pressing the Start_cycle button on the panel.
35006224 12/2018
55
Introductory example
56
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
TSX CFY axis control modules
35006224 12/2018
TSX CFY axis control modules
Part II
TSX CFY axis control modules
Aim of this part
This part presents the TSX CFY step by step axis command modules, their functionalities and their installation.
What Is in This Part?
This part contains the following chapters:
12
13
14
15
10
11
8
9
Chapter
5
6
7
Chapter Name
Installation
Characteristics and maintenance of the TSX CFY
Programming step by step axes control
Configuring step by step axes control
Adjusting step by step axes control
Debugging a step by step axes control program
Operation
Diagnostics and maintenance
Complementary functions
Characteristics and performance
Application-specific step by step axes control language objects
Page
35006224 12/2018
57
TSX CFY axis control modules
58
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Installation
35006224 12/2018
Installation
Chapter 5
Installation
Subject of this chapter
This Chapter deals with the installation of step-by-step axis command modules.
What Is in This Chapter?
This chapter contains the following sections:
Section
5.1
5.2
5.3
Topic
General
Connection of translator signals
Connecting sensors/pre-actuators and supply modules
Page
35006224 12/2018
59
Installation
General
Section 5.1
General
Subject of this section
This Section introduces general points for installing TSX CFY modules.
What Is in This Section?
This section contains the following topics:
Topic
Base configuration necessary
Installation procedure
General precautions for wiring
Page
60
35006224 12/2018
Installation
Base configuration necessary
Introduction
The step by step axes control modules can be installed in any of the slots on a TSX RKY•• rack.
The power of the supply to the rack must be selected according to the number of modules fitted.
Maximum number of TSX CFY •1 modules per station
Each step by step control module comprises:
1 application specific channel for the TSX CFY 11 module,
2 application specific channels for the TSX CFY 21 module.
Given that the maximum number of application specific channels managed by a PLC station depends on the processor type installed, the maximum number of TSX CFY •1 modules in a PLC station will depend on:
the processor type installed, the number of application specific channels already in use other than step by step application specific control channels.
As a result, a global assessment must be made at PLC station level to find out the number of application specific channels already in use, in order to define the number of TSX CFY •1 modules that can be used.
Number of "application-specific" channels supported:
Premium
(see Premium and Atrium using EcoStruxure™ Control Expert, Processors, racks and power supply modules, Implementation Manual)
Atrium
(see Premium and Atrium using EcoStruxure™ Control Expert, Processors, racks and power supply modules, Implementation Manual)
35006224 12/2018
61
Installation
Installation procedure
General
The module can be installed or removed without cutting the rack power supply, to ensure that a device is available.
CAUTION
POSSIBLE DAMAGE TO TRANSLATORS
Do not connect or disconnect Translators connectors with Translators powered on.
It is not recommended, though allowed, to disconnect Auxiliary modules input/output connectors with modules powered on.
Failure to follow these instructions can result in injury or equipment damage.
The module fixing screws and connectors must be correctly screwed in place in order to guarantee effective resistance to electrostatic and electromagnetic interference.
62
35006224 12/2018
Installation
General precautions for wiring
General
The power supply to sensors and actuators need fast-blow fuses against overload or overvoltage.
when wiring use wires of sufficient size to avoid on-line voltage falls and overheating, keep sensor and actuator cables away from any source of radiation resulting from high-power electric circuit switching, all cables connecting the translators must be shielded, the shielding must be good quality and connected to the protective ground both for the module and the translator. Continuity must be ensured throughout connections. Do not transmit any other signals in the cable than those for the translators.
For reasons of performance the auxiliary inputs of the module have a short response time. You must therefore make sure that there is enough self-sufficient supply to these inputs to ensure the module continues to operate correctly in the event of a short power break. It is recommended that you use a regulated supply to ensure more reliable response times from the actuators and sensors.
The 0 V supply must be connected to the protective ground nearest to the supply module output.
35006224 12/2018
63
Installation
Connection of translator signals
Section 5.2
Connection of translator signals
Subject of this section
This Section deals with the connection of translator signals.
What Is in This Section?
This section contains the following topics:
Topic
Signal labeling
Connection to a translator with RS 422/485 interface
Connecting to a translator with NPN open collector interface
Overview of the TSX TAP S15xx wiring accessories
Page
64
35006224 12/2018
Signal labeling
Diagram of the principle
This diagram illustrates the principles for labeling:
Installation
Description
Each module output signal is RS 485, for each output there is therefore a direct signal (+) and its complement (-). The outputs are TTL type current extraction compatible. The 5 V insulated voltage is only available, if necessary, to supply translator input and output. The 0 V is common to inputs and outputs. 5 V must only be used with translators with open collector outputs and TTL type inputs
(5 V insulated not provided by the translator).
Illustration:
The proposed type of connection is direct wiring by soldering onto the connector: the TSX CAP
( see page 68 )
kit comprising a SUB-D connector and its protective cover.
35006224 12/2018
65
Installation
Connection to a translator with RS 422/485 interface
Diagram of the principle
It is recommended that you use a shielded cable containing 7 twisted pairs. The + and – wires of each module output signal must be connected in the same pair.
This diagram illustrates the principle of connection:
66
35006224 12/2018
Installation
Connecting to a translator with NPN open collector interface
Diagram of the principle
Only one wire is used per input/output signal. If the translator does not provide 5 V insulated voltage do not forget to supply the interface from the insulated 5 V provided by the module.
This diagram illustrates the principle of connection:
35006224 12/2018
67
Installation
Overview of the TSX TAP S15xx wiring accessories
General
The TSX TAP S15•• wiring accessories make it possible to connect an incremental encoder to the counting module, by using a specific cable (supplied by the encoder manufacturer):
TSX TAP S15 05: makes it possible to connect an incremental encoder with a 5 VDC supply: encoder with RS 422 line issuer outputs,
TSX TAP S15 24: makes it possible to connect an incremental encoder with a 24 VDC supply: encoder with totem pole outputs or open collector PNP outputs.
The TSX TAP S15•• has 2 connectors:
a female 12-pin DIN base, labeled in an anti-clockwise direction. This connector makes it possible to connect the encoder, via a cable supplied by the manufacturer of the encoder, a standard 15-pin SUB-D connector making it possible to connect the module counting inputs to the SUB-D connector, using a standard TSX CCP S15 cable.
The TSX TAP S15•• product can be fixed onto a DIN rail using a bracket supplied with the accessories, or it can be fixed to a cabinet lead-in with a gasket, which is supplied with the product.
Illustration:
68
35006224 12/2018
Connecting sensors/pre-actuators and supply modules
Section 5.3
Connecting sensors/pre-actuators and supply modules
Installation
Subject of this section
This Section deals with the connection of sensors/pre-actuators and supply modules.
What Is in This Section?
This section contains the following topics:
Topic
Signal labeling
Connections
Connecting auxiliary inputs and outputs to processor.
Principle of connecting I/O channel 0
Connection using a TSX CDP 301/501 pre-wired strand
Connection with TELEFAST pre-wiring system
Availability of signals on TELEFAST
Correspondence between TELEFAST terminals and HE10 connector
Wiring precautions
Page
35006224 12/2018
69
Installation
Signal labeling
Diagram of the principle
This diagram illustrates the principles for labeling signals:
The 0 V of sensors/pre-actuators is connected in the module to the protective ground by an R/C network with the value: R = 100MΩ / C = 4.7 nF.
70
35006224 12/2018
Installation
Connections
General
There are several possible options for connecting the sensors/pre-actuators of the TSX CFY 11 /
21 module. They can be connected directly by the TSX CDP 301 / 501 via the Discrete TELEFAST pre-wiring system.
(see Premium and Atrium using EcoStruxure™ Control Expert, Axis Control Modules for Servomotors, User Manual)
strip or
35006224 12/2018
71
Installation
Connecting auxiliary inputs and outputs to processor.
General
To ensure optimum operation, the event and reference point inputs have a weak immunity. It is recommended that you use contacts without bounce (proximity sensor for example).
72
35006224 12/2018
Principle of connecting I/O channel 0
Diagram of the principle
This diagram illustrates the principles for connecting I/O channel 0:
Installation
35006224 12/2018
73
Installation
Description
The emergency stop or end limit switch contacts are open.
End limit switch contacts are not contacts which have to be wired in series with the emergency input. End limit switch contacts are used to command movement stop with deceleration. The end limit switch (ELS+) stops movement in the +direction, the end limit switch (ELS-) stops movement in the- direction. It is therefore important to positions them at the correct end of the axis (see diagram below).
Illustration:
74
35006224 12/2018
Installation
Connection using a TSX CDP 301/501 pre-wired strand
General
Connection using a pre-wired strand enables direct contact to the actuators, pre-actuators or any terminal system. This strand comprises 20 gage 22 wires (0.34 mm 2 ) with a connector at one end and free wires at the other end, labeled using a color code.
Illustration
This diagram shows the color code:
35006224 12/2018
75
Installation
Connection with TELEFAST pre-wiring system
Diagram of the principle
This connection is made using a TELEFAST 2 base: ABE-7H16R20.
76
NO: normally open,
NC: normally conductor.
35006224 12/2018
Availability of signals on TELEFAST
Illustration
This diagram shows the availability of signals on TELEFAST:
Installation
(1) At the ABE-7H16R20 base, the position of the jumper wire determines the polarity of all terminals from 200 to 215:
jumper wire in position 1 or 2: terminals 200 to 215 have + polarity, jumper wire in position 3 or 4: terminals 200 to 215 have - polarity,
(2) At the ABE-7H16R20 base, it is possible to add an optional ABE-7BV20 strip to create a second shared sensor (+ or - according to user’s choice).
35006224 12/2018
77
Installation
Correspondence between TELEFAST terminals and HE10 connector
General
This table shows the correspondence between TELEFAST terminals and the module’s HE10 connector:
Nature of signal
104
105
106
107
108
109
110
TELEFAST screw terminal block
(Terminal No.)
100
101
102
103
111
112
113
114
115
+ 24 VDC
- 0 VDC
+ 24 VDC
2
3
- 0 VDC
1
4
9
10
11
5
6
7
8
16
17
18
19
20
12
13
14
15
1
2
3
4
HE10 20-pin connector
(Pin No.)
I0 cam reference point
I3 event
I1 emergency stop
I4 external stop
I2 limit
I5 limit
I0 cam reference point
I3 event
I1 emergency stop
I4 external stop
I2 limit+
I5 limit-
Q0 brake output nc
Q0 brake output nc (1)
Auxiliary input sensor supply
Terminals 200 to 215 at - 0 VDC channel 0 channel 1 channel 0 channel 1
Terminals 200 to 215 at + 24 VDC
78
35006224 12/2018
Installation
TELEFAST screw terminal block
(Terminal No.)
200...215
HE10 20-pin connector
(Pin No.)
Nature of signal
300...315
Connecting shared sensors to:
+ 24 VDC if terminals 1 and 2 are connected,
- 0 VDC if terminals 3 and 4 are connected
On the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected by a wire to the shared voltage.
(1) nc = not connected
For a TSX CFY 11 module, the signals corresponding to the channel are not connected.
35006224 12/2018
79
Installation
Wiring precautions
General
To ensure the best performance, inputs I0 to I5 are rapid inputs. If the actuator is a dry contact, the inputs must be connected by a twisted pair, or by a shielded cable if the sensor is a two or threewire proximity detector.
The module includes as standard basic protection against short circuits or voltage inversions.
However, the module cannot remain operational for long with an error. You must therefore ensure that the fuses in series with the supply carry out their protective function. These are 1A maximum fast-blow fuses, the supply energy must be sufficient to ensure their fusion.
Important note: wiring of Q0 static outputs
The actuator connected to the Q0 brake output has its shared pin connected to supply 0 V. If for any reason there is a 0 V outage of the output amplifier supply (e.g. poor contact or accidental unplugging), when the 0 V of the actuators remains connected to the 0 V supply, there may be enough mA output current from the amplifier to keep low-power actuators triggered.
Illustration:
80
35006224 12/2018
Installation
Connection via TELEFAST
If the shared actuators are connected to the bar for shared points 200 to 215 (jumper wire in position 1-2), there can be no outage of the shared module without an outage of the shared actuators.
Connection using a TSX CDP 301 / 501 pre-wired strand
This kind of connection must be carried out with the greatest care and attention. It is recommended that you take special care in wiring this cable, for example using the cable ferules on screw terminals. It may be necessary to double the connections in order to ensure permanent contacts.
When the actuator supply is a long distance away from the modules and close to the shared actuators, there may be an accidental break of the link between the latter and the 0 V terminal of the module(s).
Illustration:
If there is a break of the supply section between A and B, there is a risk that the RL actuators may not remain operational. You must, if possible, double connections of 0 V supply to the modules.
35006224 12/2018
81
Installation
Connection using a TSX CDP 301 / 501 pre-wired strand:
82
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Characteristics and maintenance
35006224 12/2018
Characteristics and maintenance of the TSX CFY
Chapter 6
Characteristics and maintenance of the TSX CFY
Aim of this part
This part presents the various electrical characteristics of TSX CFY modules and describes the maintenance actions to be performed to ensure that the module operates correctly.
What Is in This Chapter?
This chapter contains the following topics:
Topic
General characteristics
Characteristics of translator inputs (SUB-D connector)
Characteristics of translator outputs (SUB-D connector)
Characteristics of auxiliary inputs (HE10 connector)
Characteristics of Q0 brake output
Page
35006224 12/2018
83
Characteristics and maintenance
General characteristics
Table of characteristics
This table introduces the general characteristics of TSX CFY modules:
Maximum frequency of pulses
Current consumed on internal 5 V
Current consumed by the module on sensor/pre-actuator 24V with no sensor/pre-actuator current
Power dissipated in the module
Module
TSX CFY 11
TSX CFY 21
TSX CFY 11
TSX CFY 21
TSX CFY 11
TSX CFY 21
187.316 KHz
Value
510 mA
650 mA
50 mA
100 mA
3.8 W
5.6 W
> 10 MΩ under 500 VDC
1000 Veff 50 / 60 Hz for 1 mn
Insulation resistance
Dielectric rigidity between I/O "translator" and protective ground or PLC logic
Operating temperature
Storage temperature
Hygrometry (without condensation)
Operating altitude
0 to 60 °C
-25 °C to 70 °C
5% to 95%
< 2000 m
84
35006224 12/2018
Characteristics of translator inputs (SUB-D connector)
Diagram
These inputs have positive logic current extraction:
Characteristics and maintenance
Characteristics
The following table shows the characteristics of translator inputs:
Characteristics
Nominal current
(Ue = 0 V)
Voltage for ON state
Voltage for OFF state
Immunity of loss of step input
Immunity of translator error input
Symbol
Ie
Uon
Uoff
Value
4,5
2
3,6
15 to 30
3 to 10
Unit mA
V
V
μs ms
35006224 12/2018
85
Characteristics and maintenance
Characteristics of translator outputs (SUB-D connector)
Table of characteristics
These outputs are insulated RS 422/485. There are two complemented outputs per signal.
Characteristics
Differential voltage output on R load ≤ 100Ω
Short-circuit current
Permitted shared mode voltage
Permitted differential voltage
Values
+/- 2
< 150
≤ 7
≤ 12
Units
V mA
V
V
86
35006224 12/2018
Characteristics of auxiliary inputs (HE10 connector)
Illustration
Diagram:
Characteristics and maintenance
Characteristics
Table of characteristics for auxiliary inputs:
Electrical characteristics
Nominal voltage
Nominal voltage limits
(ripple included)
Nominal current
Input impedance (at Unom)
Voltage for "On" state
Current at Uon (11 V)
Voltage for "Off" state
Current at "Off" state
Input immunity:
Cam reference point input and event
Other inputs
IEC 1131 compatibility with sensors
Compatibility with 2 and 3-wire sensors
Type of input
Logic type
35006224 12/2018
Symbol
Un
U1
Utime (1)
In
Re
Uon
Ion
Uoff
Ioff
7
3,4
≥11
>6
Value
24
19 to 30
34
<5
<2 ton/toff (2) ton/toff
< 250
3 to 10
μs ms type 2 all proximity sensors supplied at 24 VDC current ducts
Positive (sink)
Unit
V
V mA kΩ
V mA
V mA
87
Characteristics and maintenance
Electrical characteristics
Pre-actuator voltage check
Time of supply detection supply threshold OK supply threshold error supply OK supply error
Symbol Value
> 18
< 14
< 30
> 1
Unit
V
V ms
ms
(1) Utime: maximum permitted voltage for 1 hour in every 24 hours.
(2) Inputs: reference point cam and events are fast inputs (response time < 250 μs) compliant with maximum frequency of 187.316 KHz of translator command outputs.
88
35006224 12/2018
Characteristics of Q0 brake output
Illustration
Brake output:
Characteristics and maintenance
Characteristics
Table of characteristics:
Electrical characteristics
Nominal voltage
Voltage limits
Temporary voltage
Nominal current
Max voltage fall "On"
Leakage current at "OFF" state
Load impedance
Max current to 30 V and to 34 V
Communication time
Electro unload time
Max switching frequency
(on inductive load)
Compatibility with inductive inputs
IEC 1131 compatibility
35006224 12/2018
Value
24
19 to 30
34 (1)
500
< 1
< 0,3
80<Zon<1500
625
< 250
< L/R
F<0.6 / (LI 2 )
Unit
V
V
V mA
V mA
Ω mA
μs s
Hz
Any input whose Re is less than 15 kΩ and has positive logic
Yes
89
Characteristics and maintenance
Electrical characteristics
Protection from overloads and short-circuits
Monitoring short-circuits of each channel
Reset
via application program
automatic
Protection against channel overvoltage
Protection against polarity inversions
Power of a filament lamp
Pre-actuator voltage check
Reaction time of voltage check
Value by current limiter and circuit breaker thermal, signaling: 1 bit per channel
One bit per module
Unit
Zener (55 V) between outputs and +24 V
Using a reverse diode on the supply
8
OK if supply > 18
(ascending) not OK if supply < 14
(decreasing)
NOK --> OK<30
OK --> NOK>1
W
V
V ms ms
(1) maximum permitted voltage for 1 hour in every 24 hours of operation.
90
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Programming
35006224 12/2018
Programming step by step axes control
Chapter 7
Programming step by step axes control
Subject of this chapter
This chapter describes the programming principles for the different operating modes: it describes the principal instructions and the operating modes.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Principles of programming a step by step axis
Operating modes
Programming the SMOVE function (in automatic mode)
Inputting SMOVE function parameters
Description of the SMOVE function parameters
Instruction codes for the SMOVE function
Description of basic movements with the SMOVE function
Description of SMOVE instruction codes
Example of using an indexed position (repetitive movements)
Movement command sequencing
Deferred PAUSE function
Feed hold function
Event processing
Managing operating modes
Managing faults
Description of external hardware faults
Description of application faults
Description of the command refused faults
Management of manual mode
Visual movement commands
Incremental movement commands
Reference point command
Forced reference point command
Page
35006224 12/2018
91
Programming
Management of direct mode (DIRDRIVE)
Management of stop mode (OFF)
Topic Page
92
35006224 12/2018
Programming
Principles of programming a step by step axis
Introduction
Each channel (axis) of the axes control module is programmed using:
the SMOVE function for movements in automatic mode,
the bit objects (%I and %Q) and words (%IW, %QW and %MW), (See
Application-specific step by step axes control language objects, page 209
associated with the module to define:
the selection of operating modes, the control of movements, except for automatic mode, the monitoring of the operating status of the axis and the module.
Bit objects and words
The bit objects and words can be retrieved using their address or their symbol. The symbols are defined in the variables editor which offers as a default a symbol name for each of the objects.
35006224 12/2018
93
Programming
Operating modes
At a Glance
You can use each axes control channel in 4 operating modes:
Operating mode
Automatic (AUTO)
Manual (MANU)
Direct (DIRDRIVE)
Stop (OFF)
Description
This mode supports the execution of movement commands driven by the
SMOVE functions.
This mode supports the visual driving of the moving part, from a front panel or an operator dialog desk. The commands are enabled via output bits %Q.
In this mode the output behaves like a digital / frequency converter. This mode controls the movement according to the movement setpoint indicated in the variable PARAM.
In this mode the channel does not monitor the moving part; it only reports on current position and speed.
This mode is forced at start up, if the axis is configured and error free.
Selecting the mode
The mode is selected by means of the word MOD_SELECT (%QWr.m.c.0)
The following table indicates the selected mode, according to the value of the word MOD_SELECT:
1
2
Value
0
3
Selected mode
OFF
DIRDRIVE
MANU
AUTO
Description
Switch to stopped movement
Order to move in direct mode.
Order to move in manual mode.
Order to move in automatic mode.
For any other value of MOD_SELECT, the OFF mode is selected.
Changing mode during a movement
Changing operating mode while a movement is in progress (DONE bit set to 1: %Ir.m.c.1) causes the moving part to stop. When the moving part is stopped (NO_MOTION bit set to 1: %Ir.m.c.7 ), the new operating mode is then activated.
NOTE: Only the commands concerning the current mode are examined. The other commands are ignored: for example, the channel in MANU mode (IN_MANU set to 1: %Ir.m.c.18), if the DIRDRV
(%Qr.m.c.0) command is activated, it is ignored. It is necessary to change firstly to DIRDRIVE mode.
94
35006224 12/2018
Programming
Programming the SMOVE function (in automatic mode)
At a Glance
You can program an SMOVE function in any programming module in ladder language (by means of an operation block), in instruction list language (between square brackets) or in structured text language. In all cases the syntax remains the same.
Assisted input screen
You can enter the SMOVE function or through the entry help screen use:
35006224 12/2018
95
Programming
Assisted input
In the editor of the ST program for example, proceed in the following way:
Step
1
2
3
4
Action
Right-click on the place you wish to insert the SMOVE function and select the FFB input
Assistant....
Enter SMOVE in the field Type FFB.
Result: The entry help window of the SMOVE function appears automatically and allows you to enter the parameters or to enter the details screen.
Press the Special Assistant button and complete the different fields offered
can also enter the function variables directly into the parameter input area.
. You
Confirm with OK. The function is then displayed.
96
35006224 12/2018
Programming
Inputting SMOVE function parameters
Introduction
A movement command is programmed via a SMOVE function, with the following syntax:
SMOVE (Axis_ch1,N_Run,G9x,G,X,F,M)
The Details screen allows you to enter each of the parameters with help.
Details screen for the SMOVE function
The Details screen for the SMOVE function is as follows:
The entry fields (parameters for the SMOVE function) are as follows:
Parameter
Axis_ch1
N_Run
X
F
G9x
G
M
Description
IODDT type variable corresponding to channel 1 on which the function must be carried out.
Example: AXIS_CH1 is of the type T_STEPPER_STD
Movement number.
Movement type.
Instruction code.
Coordinate of the position to be reached.
Speed of movement of the moving part.
Event processing, auxiliary discrete outputs associated with the channel.
35006224 12/2018
97
Programming
Description of the SMOVE function parameters
At a Glance
You must enter the following parameters in order to program a movement function:
SMOVE (Axis_ch1,N_Run,G9_,G,X,F,M)
IODDT
AXIS_CH1 is a variable of type IODDT
(see EcoStruxure™ Control Expert, Operating Modes)
AXIS_CH1 is of the type T_STEPPER_STD .
corresponding to a channel 1 of the axes control module on which the function is to be performed.
Movement number
N_Run defines the movement number (between 0 and 32767). This number identifies the movement carried out by the SMOVE function.
In debug mode, this number tells you which movement is in progress.
Movement type.
G9_ defines the movement type:
Code
90
91
98
Movement type.
Absolute movement.
Movement relative to the current position.
Movement relative to the stored PREF1 position. The storing of the PREF1 position is achieved using the instruction code G07.
To select the movement type, use the browse button situated to the right of the G9_ field or enter the code directly when inputting directly (without going to the Details screen).
Instruction code
G defines the instruction code
( see page 100 )
98
35006224 12/2018
Programming
Coordinate of the position to be reached
X defines the coordinate of the position to be reached or towards which the moving part must move
(in the case of a continuous movement). This position can be:
immediate, coded in a double internal word %MDi or internal constant %KDi (this word can be indexed).
This value is expressed in the unit defined by the configuration parameter Length Units (e.g. micron).
NOTE: In the case of instructions G14, G21 and G62, this parameter represents the value of the reference point.
Speed of movement of the moving part
F defines the speed of movement of the moving part. This speed can be:
immediate, coded in a double internal word %MDi or internal constant %KDi (this word can be indexed).
The unit of speed is Hertz.
NOTE: The speed can be modulated in the course of the movement by means of the CMV (Speed
Modulation Coefficient). Actual F = programmed F x CMV/1000. This parameter, initialized by default at 1000, can be in between [02000], the resulting speed must always be more than
SS_FREQ. The value 0 signifies the moving part has been stopped.
Parameter M
M defines a word which is coded in 4-bit bytes (in hexadecimal):
the activation or non activation of the trigger for application event processing, for instructions
G10, G11, G05 and G07:
M = 16#1000: activation of the associated event task,
M = 16#0000: non activation of the event task when the SMOVE command is executed.
For example:
NOTE: Coding is automatically performed in the M field in the Details screen, when you make selections using the check boxes and radio buttons available in this screen.
35006224 12/2018
99
11
14
62
05
07
Programming
Instruction codes for the SMOVE function
Introduction
The G defines the instruction code.
To select the instruction code you can use the browse button situated to the right of the G field, click on the icon corresponding to the movement or enter the code directly when inputting directly
(without going to the Details screen ).
List of instruction codes
The instruction codes that you can select in the Details screen are as follows:
Instruction code
09
Meaning
Movement to position with stop.
Icon
01
10
Continuous movement to position.
Movement to event with stop.
Continuous movement to event.
Reference point.
Forced reference point.
Await event.
Storage of position on event.
100
35006224 12/2018
Details screen gaphics
The Details screen also display a graphic which represents the selected movement.
For example, code G09:
Programming
35006224 12/2018
101
Programming
Description of basic movements with the SMOVE function
At a Glance
Some instructions of the SMOVE function allow you to carry out basic movements.
When programming these movements, the user defines the position to be reached and the speed.
The acceleration parameter (constant, trapezoidal law of speed) is defined by this adjustable parameter.
The movements can be:
absolute in relation to the machine origin 90 relative in relation to the current position 91 relative in relation to the stored position PREF 98
Absolute movement in relation to the machine origin
Example of an absolute movement in relation to the machine origin 90.
102
35006224 12/2018
Relative movement in relation to the current position
Example of a relative movement in relation to the current position 91.
Programming
Relative movement in relation to the stored position
Example of a relative movement in relation to the stored position PREF 98.
35006224 12/2018
103
Programming
Description of SMOVE instruction codes
At a Glance
Three classes of movement can be programmed:
movements to a position (instruction codes 01 and 09) movements until the detection of an event (instruction codes 11 and 10) reference point (instruction 14)
To find out about the execution conditions for instructions, see
Diagnostics and maintenance, page 195
.
Continuous movements to a position
Example of a continuous movement to a position: instruction code 01.
104
NOTE: If the instruction 01 is not followed by any movement instruction, the moving part continues the movement until it reaches the soft stops (after passing the position to be reached, the CMV
(Speed Modulation Coefficient) is no longer interpreted).
35006224 12/2018
Movements to a position with stop
Example of a movement to a position with stop: instruction code 09.
Programming
Continuous movement until an event
Example of a continuous movement until an event: instruction code 11.
NOTE: The event can be a rising or falling edge on the dedicated event cam input, or a rising edge on the EXT_EVT bit (%Qr.m.c.11) by program.
It is essential that the position parameter be defined. If the event is not detected, the instruction is terminated when the requested target position is reached.
These instructions 11 and 12 can activate the event task when the event is detected if M is equal to 16#1000.
35006224 12/2018
105
Programming
Movement until an event with stop
Example of a movement until an event with stop: instruction code 10.
Reference point
Example of setting a reference point: instruction code 14. Reference point configured towards short cam in the + direction. At the start, the moving part moves away from the cam.
106
NOTE: This instruction triggers a reference point sequence according to the selection made in configuration. The value provided in the X parameter corresponds to the coordinate to be loaded with the current value when the reference point is detected.
35006224 12/2018
Programming
Example of setting a reference point: instruction code 14. Reference point configured towards long cam in the + direction. At the start, the moving part moves towards the cam.
NOTE: This command is only accepted if the moving part is at rest: NO_MOTION bit = 1
(%Ir.m.c.7).
Forced reference point
This command performs a forced reference point (without movement of the part), the instruction code is 62. The current value of the reference point is forced to the value entered in the position parameter X.
Example: SMOVE (Axis_ch0,1, 90, 62 , 100000, 100, 0) .
When this instruction is executed, the position of the moving part is forced to 100000.
NOTE: Regardless of the status of the axis, referenced or not, this command is accepted and it has the action of referencing the axis when the execution is completed. This command is only accepted if the moving part is at rest, NO_MOTION bit = 1 (%Ir.m.c.7).
Await event
This command, instruction code 05, makes the channel wait for an event which can be:
a change of state of the reflex input (rising or falling edge according to the selection made at configuration), a rising edge for the EVT_EXT bit (%Qr.m.c.11)
In the context of this instruction, the F parameter specifies the time envelope with a resolution of
10 ms. If the event is not triggered at the end of the time envelope, the command is deactivated. If
F = 0, the wait carries on indefinitely.
Example: SMOVE (Axis_ch0,1, 90, 05 , 500, 100, 0) .
35006224 12/2018
107
Programming
It is possible to associate event processing
16#1000.
( see page 117 )
, to do that you must program M to
NOTE: When executing this instruction, the T_SPEED object (%MDr.m.c.10) does not contain the parameter F for the wait time. On the other hand, it is advised to systematically associate an event process to this command as the bit TO_G05 (%Ir.m.c.39), which allows the application to distinguish whether the command is terminated by detecting an event or by the time-out of the time envelope, is only refreshed if this process is activated.
Storage of the current position on event.
After the execution of this instruction, code 07, when the trigger input is entered the event defined in configuration is produced and the current position is stored in the PREF register.
NOTE: The parameter of position X must be equal to 1.
Example: SMOVE (Axis_ch0,1, 90, 07 , 1, 0, 0) .
Descriptive table for storing the current position on event.
Type of event on event input Timing diagram Configuration selection
108
NOTE: This instruction is not blocking, the program carries on straightaway to the next instruction.
The stored value of the current position can be accessed in the PREF register (%IWr.m.c.7) only if activation of event processing is requested (M=16#10000).
NOTE: When this instruction is carried out, the object T_XPOS (%MDr.m.c.8) does not contain the parameter X=1.
35006224 12/2018
Programming
Example of using an indexed position (repetitive movements)
At a Glance
We want to carry out the sequence of the following basic movements 9 times:
movement A until the detection of the edge of part 1, movement B as far as position 2 = +20000 in relation to the edge of part 1, movement C as far as position 3 = +10000 in relation to the edge of part 1, movement D as far as the edge of part 1.
In this example, the reference point is assumed to be taken and the moving part is at the reference point. We use an AXIS_CH0 IODDT type variable associated with channel 0 of the axis command module on which the function is to be applied. AXIS_CH0 is of the type T_STEPPER_STD .
Illustration
Position diagram.
NOTE: the sequence of basic movements is represented in bold on the curve. The numbers given correspond to the program step numbers included in the SMOVE function.
35006224 12/2018
109
Programming
Description of the program
Grafcet for the operation of repetitive movements.
110
NOTE: all the actions must be programmed on activation.
35006224 12/2018
Programming
Movement command sequencing
Creating a trajectory
The creation of a trajectory is carried out by programming a series of basic movement instructions
(SMOVE function). This function applies to an IODDT type variable T_STEPPER_STD . In the example shown, we declare the AXIS_0 variable of type T_STEPPER_STD .
Each basic command to execute an SMOVE function must only be done once. You must program the execution either:
in Grafcet: in a step programmed for activation or deactivation, in structured text or Ladder language, in one bit rising edge.
The report on the execution of the function is supplied by the module, via the bits NEXT and DONE.
Memory buffer
The TSX CFY module has a mechanism that supports the sequencing of movement commands.
Each axis of the TSX CFY module includes a memory buffer that allows it to receive 2 movement commands, in addition to that which it is executing. Thus, after finishing executing the current command, it carries on immediately to the first command present in the buffer memory.
Command sequencing:
Sequencing between 2 commands
The sequencing between 2 movement commands is carried out in the following way:
instantaneously if the first movement is continuous, as soon as the moving part has stopped, if the first movement is with stop.
For sequencing to be instantaneous, the execution time of the instruction in progress must be greater than the period of the master task.
NOTE: A new command must only be transmitted to the module if the memory buffer associated with the axis to be controlled is not full.
35006224 12/2018
111
Programming
Bits associated with the sequencing mechanism
The bits associated with the sequencing mechanism are as follows:
Addressing
NEXT (%Ir.m.c.0)
Description
Indicates to the program user that the module is ready to receive the next movement command.
DONE (%Ir.m.c.1) Indicates the end of the execution of the current command and the absence of a new command in the memory buffer.
AT_PNT (%Ir.m.c.8) Indicates that the moving part has reached the point aimed for:
for a continuous movement, remains at 0,
for a movement with stop, is equivalent to NO_MOTION.
NOTE: The program must always test either the NEXT bit or the DONE bit before executing an
SMOVE command.
Example
The following diagram represents the timing diagram of a sequence:
112
For a movement with stop: DONE switches to 1 when NO_MOTION (%Ir.m.c.7) switches to 1 and when the memory buffer is available.
For a continuous movement: DONE switches to 1 when the target position is exceeded and when the buffer memory is empty.
35006224 12/2018
Programming
Deferred PAUSE function
At a Glance
The command PAUSE (%Qr.m.c.12) allows you to suspend the sequence of movements. It only becomes active when the moving part is stopped, that is, at the end of a G09 or G10 instruction.
The next movement starts as soon as the PAUSE command is reset to 0.
The ON_PAUSE bit (%Ir.m.c.26) indicates when set to 1 that the axis is in PAUSE status.
This function has 2 possible uses:
the block by block execution of the movement program, synchronization of the axes by the same step by step axes control module.
Block by block execution of the movement program
If the instruction in progress is with stop, the activation of the PAUSE command in the debug screen in automatic mode or the setting of the PAUSE bit (%Qr.m.c.12) to 1, causes a switch to standby after the execution of the instruction in progress: this stops the movement sequencing.
It is thus possible by successively activating and deactivating the PAUSE command to execute the movements block by block with the aim of facilitating the debug.
Synchronization of several axes
For each axis, the setting of the PAUSE bit (%Qr.m.c.12) to 1 by the program causes a switch to standby after the execution of the instruction in progress.
When the PAUSE bit is reset to 0, the module continues the execution of the instructions.
35006224 12/2018
113
Programming
Example
The execution of the movement of the moving part 1 is stopped when moving part 0 reaches position 100000. The movement is activated again when the moving part 0 reaches dimension
500000. We use AXIS_0 of type T_STEPPER_STD as an IODDT variable associated with the channel
NOTE: The PAUSE command is only processed when AUTO mode is active.
114
35006224 12/2018
Programming
Feed hold function
At a Glance
This function allows you, in automatic mode, to cause the moving part to stop, while assuring, at the time of the command to restart the movement, the continuation of the programmed trajectory
(with no risk of commands being refused).
Activating the function
The Feed Hold function is activated by assigning the value 0 to the CMV (Speed Modulation
Coefficient) word (%QWr.m.c.1).
It causes the moving part to stop in accordance with the programmed deceleration.
The status report on the pause is indicated by the IM_PAUSE bit (%Ir.m.c.27).
Deactivating the function
The Feed Hold function is deactivated by reassigning the initial value (> 0) to the CMV (Speed
Modulation Coefficient) word.
It causes the interrupted movement to restart at the speed corresponding to:
F x CMV / 1000.
35006224 12/2018
115
Programming
Example
Activation / deactivation of the Feed Hold function applied to the channel 0 of a module located in slot 2 of a standard rack to which the variable Axis_0 of type T_STEPPER_STD has been added:
116
NOTE: Upon a STOP order or a blocking error, this command is deactivated.
NOTE: when the position aimed for is exceeded, when there is a stop following a Feed Hold command, the movement in progress is considered terminated. In this case the trajectory restarts with the movement which was on standby in the memory buffer.
35006224 12/2018
Programming
Event processing
At a Glance
The channels of the TSX CFY modules can activate an event task. To do that you must have enabled the functionality in the configuration screen, by associating an event processing number to the channel
( see page 151 )
.
Activating an event task
The following instructions trigger the sending of an event that activates the event task:
Movement until an event, codes 10 and 11: the event processing application is activated, when the event is detected.
Await event, code 05: the event processing application is activated, at the end of the instruction.
Storing the current position when the event appears, code 07: the event processing application is activated at the end of storing the PREF position.
The event processing application is activated, if bit 12 in the M parameter of the SMOVE function associated to the instruction is set to 1 (M equals 16#1000).
Variables which can be used by the event task
If several event sources are selected, the following bits allow you to determine what caused the event processing application to be triggered:
EVT_G1X (%Ir.m.c.40): end of G10 or G11 on event,
EVT_G05 (%Ir.m.c.38): end of G05 on event,
TO_G05 (%Ir.m.c.39): G05 timing elapsed,
EVT_G07 (%Ir.m.c.37): storage of position,
The OVR_EVT bit (%Ir.m.c.36) allows you to detect a delay in the sending of the event or a loss of event.
Value of the stored position PREF (%IWr.m.c.7).
NOTE: The bits and the words described above are the only values refreshed in the event task, and are only updated into the PLC when the task is activated.
35006224 12/2018
117
Programming
Masking events
The programming language offers 2 methods of masking events:
Instruction for the global masking of events: MASKEVT() (the instruction UNMASKEVT() is used for unmasking).
ACTIVEVT bit = 0 (%S38) global disabling of events. The ACTIVEVT bit is normally set to 1.
Summary diagram:
118
35006224 12/2018
Programming
Managing operating modes
Powering up the module
When powering up the module or when plugging it in, the TSX CFY module carries out auto-tests with the outputs in safety position (outputs at 0).
At the end of the auto-tests:
If the auto-tests have not detected any errors.
have detected an error or the configuration is incorrect.
Then the module tests the configuration with the outputs in safety position. If the configuration is correct, the module switches to disabled mode (OFF).
signals an error and retains the outputs in safety position.
PLC in RUN mode
All the operating modes of the configured channels are usable.
Switching the PLC from RUN to STOP mode
When switching the PLC from RUN mode to STOP mode or when there is a loss of communication between the processor and the module, the moving part decelerates and stops and the module switches to STOP mode (OFF).
NOTE: The IRSTSCANRUN bit (%S13) allows you to detect when the PLC switches to STOP mode. It is set to 1 during the first cycle after the PLC switches to RUN mode.
Changing configuration (reconfiguration)
The moving part decelerates and stops.
The channel becomes unconfigured.
The channel tests the new configuration with the outputs in safety position.
If the new configuration is correct, the channel switches to STOP mode (OFF).
If the configuration is incorrect, the module signals an error and retains the outputs in safety position.
Power outage and return
When there is a power outage, the moving part stops.
At the time of a cold start or a warm restart, the configuration of the channels is automatically transmitted by the processor to the module The latter switches to STOP mode (OFF).
35006224 12/2018
119
Programming
Managing faults
At a Glance
The monitoring of faults is essential in the area of position control due to the inherent risks with moving parts.
The checks are carried out internally and automatically by the module.
Types of fault
The module detects 4 types of faults:
Module faults. These are the hardware faults internal to the module. All the axes driven by the module are thus affected by the appearance of this type of fault. They can be detected during auto-tests (when reinitializing the module) or during normal operation (I/O fault).
Hardware channel faults external to the module (for example, brake output short-circuit).
Application channel fault linked to the axes (for example, exceeding soft stop).
The monitoring of faults at axis level is permanently active when the axis is configured.
Commands refused channel faults. These are the faults which can appear when executing a movement, configuration transfer, adjustment parameters transfer or change of operating modes command.
NOTE: The monitoring of some faults at axis level can be enabled or disabled by the axes control parameters. These control parameters can be adjusted in the adjustment screen.
In STOP mode (OFF), the monitoring of application faults is disabled
Levels of gravity
Faults are classified into 2 levels of gravity:
Critical or blocking faults which cause the moving part (in the case of an axis fault) or the moving parts managed by the module (in the case of a module fault) to stop. They cause the following processes:
signaling of the fault,
deceleration of the moving part until it stops, disabling of the translator, activation of the brake, clearing of all the stored commands, the wait for an acknowledgement.
The fault must have disappeared and been acknowledged for you to be able to restart the application.
Non critical faults which cause a signaling of the fault without stopping the moving part. You must program the action to be taken with this type of fault in Control Expert.
The fault message disappears when the fault has gone and has been acknowledged (the acknowledgement is not stored and is only effective if the fault has gone).
120
35006224 12/2018
Programming
NOTE: in the case of opening the emergency stop input, or of disabling the translator ENABLE =
0(%Qr.m.c.10), the deceleration phase is not carried out and the stop is immediate. However, the appearance of step failure information is not considered to be a blocking fault, and is simply signaled to the application.
Programming faults
Faults can be displayed, fixed and acknowledged from the debug screen, but it can be useful in operation to be able to drive the moving part and fix faults from a console. For this end, the application has all the necessary information and commands.
Signaling faults
The module offers a lot of information in the form of status bits and words, which can be accessed via the Control Expert program. These bits allow faults to be handled hierarchically:
to act on the principle program, to simply signal the fault.
Levels of signaling
2 levels of signaling are provided:
First level: general information
Bit
MOD_ERROR (%Ir.m.c.ERR)
AX_OK (%Ir.m.c.3)
AX_FLT (%Ir.m.c.2)
HD_ERR (%Ir.m.c.4)
AX_ERR (%Ir.m.c.5)
CMD_NOK (%Ir.m.c.6)
Fault
Channel fault
No blocking fault (with stop of moving part) is detected
Fault (groups all the faults together)
External hardware fault
Application fault
Command refused
Second level: detailed information
Module and axis fault status words CH_FLT(%MWr.m.c.2) and AX_STS(%MWr.m.c.3). These
words are obtained via explicit exchange requests described in language objects
( see page 209 )
NOTE: On encountering a blocking fault, we advise you to stop the development of the sequential processing to which the axis is associated and to fix the fault by driving the moving part in manual mode. The correction of the fault must be followed by an acknowledgement of the fault.
35006224 12/2018
121
Programming
Fault acknowledgment
When a fault appears:
The fault bits AX_FLT, HD_ERR, AX_ERR and the extract bits of the status words concerned by the fault are set to 1.
If the fault is blocking the AX_OK bit is set to 0.
When the fault disappears, all the fault bits remain in their status. The fault is stored until the acknowledgement is obtained, by setting the ACK_FLT bit (%Qr.m.c.9) to 1 (or re-initializing the module). The acknowledgement must be carried out after the fault has gone (except for soft stop faults)
If several faults are detected, the acknowledgement order only works on the faults that have effectively disappeared. The faults still present must be acknowledged again after they have disappeared.
NOTE: The acknowledgement of a fault can also be carried out on initialization of the PLC, or when a correct new command is accepted in the case of a command refused fault.
Summary table for the different types of faults
The following table summarizes the different types of fault and the associated bits:
Channel fault
(MOD_ERROR bit:
%Ir.m.c.ERR)
Internal
Communication
Configuration
Configuration or adjustment
External hardware (HD_ERR bit: %Ir.m.c.4)
Process faults (AX_FLT bit: %Ir.m.c.2)
AX_OK: %Ir.m.c.3 (No blocking fault detected)
Application (AX_ERR bit:
%Ir.m.c.5)
Soft stops Emergency stop
Translator
24 Volt supply
Brake output short circuit
Command refused
(CMD_NOK bit:
%Ir.m.c.6)
Coding of the fault in the word
CMD_FLT:
%MWr.m.c.7
(*) These faults are non blocking faults and have no influence on the AX_OK bit.
Description of the channel faults
The MOD_ERROR bit groups all the faults at channel level:
Internal fault MOD_FLT (%MWr.m.c.2.4): module absent, out of service or in auto-test.
Communication fault COM_FLT (%MWr.m.c.2.6): communication fault with the processor.
Configuration fault COM_FLT (%MWr.m.c.2.6): difference between the declaration of the position of the module in the configuration and its actual position.
NOTE: The words %MW require a READ_STS command in order to be updated.
122
35006224 12/2018
Programming
Description of external hardware faults
At a Glance
These faults are signaled by the bit HD_ERR (%Ir.m.c.4). These faults are blocking faults and cannot be deactivated.
Emergency stop
The following table shows the cause, the signal and the remedy to be applied in the case of a
Emergency stop fault:
Cause
Parameters
Consequence
Signal
Remedy
Circuit open between the 24V and the Emergency stop input on the front panel of the module
None
The moving part is forced to stop
EMG_STOP (%Ir.m.c.29) and EMG_STP (%MWr.m.c.3.5) bits
Re-establish the connection between the input and the 24V then acknowledge the fault.
24V supply
The following table shows the cause, the signal and the remedy to be applied in the case of a 24V supply fault:
Cause
Parameters
Consequence
Signal
Remedy
24V supply fault
None
The axis is not referenced, the moving part is forced to stop
AUX_SUP bit (%MWr.m.c.3.6)
Re-establish the connection then acknowledge the fault
Brake output short circuit
The following table shows the cause, signal and the remedy to be applied in the case of a Brake output short circuit fault:
Cause
Parameters
Consequence
Signal
Remedy
Short circuit detected on the module’s brake output
None
The axis is not referenced, the moving part is forced to stop
BRAKE_FLT bit (%MWr.m.c.3.1)
Remove the short circuit then acknowledge the fault
35006224 12/2018
123
Programming
Translator
The following table shows the cause, the signal and the remedy to be applied in the case of a
Translator fault:
Cause
Parameters
Consequence
Signal
Remedy
The translator check input does not receive the level translator OK defined in the channel configuration
None
The axis is not referenced, the moving part is forced to stop
DRV_FLT bit (%MWr.m.c.3.2)
Remove the translator fault then acknowledge the fault
124
35006224 12/2018
Programming
Description of application faults
At a Glance
These faults are signaled by the AX_ERR bit (%Ir.m.c.5). The parameters can be accessed via the
Configuration editor adjustment screen.
Soft stops
The following table shows the cause, the signal and the remedy to be applied in the case of a Soft stop fault: This fault is blocking and cannot be deactivated.
Cause
Parameters
Consequence
Signal
Remedy
The moving part is no longer situated between the 2 thresholds: software Lo limit and software Hi Limit (this monitoring is activated as soon as the axis is referenced)
Software Hi Limit: SL_MAX (%MDr.m.c.14)
Software Lo Limit: SL_MIN (%MDr.m.c.16)
The moving part is forced to stop
SLMAX bit (%MWr.m.c.3.3): Software Hi Limit passed
SLMIN bit (%MWr.m.c.3.4): Software Lo Limit exceeded
Acknowledge the fault and, in manual mode, remove the moving part exceeding the soft stops to within the valid measurement zone. To do that, you must check:
that no movement is in progress, that manual mode is selected,
that the STOP command is set to 0, that the axis on which the command is carried out is referenced, that there is no other fault with stop on the axis.
The moving part can either be brought back manually or by means of the commands
JOG+ and JOG-.
35006224 12/2018
125
Programming
Description of the command refused faults
At a Glance
A command refused fault is generated each time that a command cannot be executed. This command is not compatible with the status of the axis or the current mode or at least one of the parameters is not valid.
These faults are signaled by the indicator Command Refused in the debug screens. The DIAG key at the channel level tells you the source of the command refused. This information can also be
accessed by program via the CMD_NOK bit (%Ir.m.c.6) and the CMD_FLT word (%MWr.m.c.7)
( see page 226 )
Command refused
The following table shows the cause, the signal and the remedy to be applied in the case of a
Command refused fault.
Cause
Parameters
Consequence
Signal
Remedy
Unauthorized movement command
Transfer of incorrect configuration or parameters
None
Immediate stop of the movement in progress
Reset to 0 of the memory buffer receiving the movement commands in automatic mode
CMD_NOK bit (%Ir.m.c.6): movement command refused
CMD_FLT word (%MWr.m.c.7): type of fault detected
Least significant byte: executable commands,
Most significant byte: adjustment configuration and parameters.
Acknowledgement is implicit upon receipt of a new accepted command
Acknowledgement is equally possible via the command ACK_FLT (%Qr.m.c.9)
NOTE: In the case of movement sequencing in automatic mode, we advise you to condition the execution of each movement with the end of the execution of the preceding movement and with the AX_FLT bit (%Ir.m.c.2). This means that the following command is not sequenced, when the current command has experienced a command refusal.
126
35006224 12/2018
Programming
Management of manual mode
At a Glance
You can select and control the manual mode from the debug screen, but also via an application program, from a panel or an operator or supervisor dialog desk.
In this case, the dialog is programmed in Ladder, Instruction List or Structured Text language, using basic commands (movements, reference points, etc.)
Selecting manual mode
This is done by assigning the value 2 to the word MODE_SEL (%QWr.m.c.0).
The switch from the mode in use to manual mode forces the moving part to stop if a movement is in progress. Manual mode is effective as soon as the moving part has stopped.
When the command to switch into manual mode has been recognized, the IN_MANU bit
(%Ir.m.c.22) bit is set to 1.
Executing manual commands
The basic commands associated with manual mode and accessible via command bits %Qr.m.c.j are as follows:
Visual movement in the + direction JOG_P (%Qr.m.c.1).
Visual movement in the - direction JOG_M (%Qr.m.c.2).
Incremental movement in the + direction INC_P (%Qr.m.c.3).
Incremental movement in – direction INC_M (%Qr.m.c.4).
Manual reference point SET_RP (%Qr.m.c.5).
Forced reference point RP_HERE (%Qr.m.c.6).
These commands are equivalent to those accessible from the debug screen of the TSX CFY module.
Manual commands:
35006224 12/2018
127
Programming
General conditions for executing commands in manual mode
The following conditions must be fulfilled in order to execute commands in manual mode:
Target position within in the software limits.
Axis without blocking fault (AX_OK bit = 1: %Ir.m.c.3).
No command being executed (DONE bit = 1: %Ir.m.c.1).
STOP command (%Qr.m.c.8) inactive and confirmation bit of the translator relay ENABLE
(%Qxy.i.10) set to 1.
NOTE: Except, in the case of a software limit fault, for commands JOG_P and JOG_M and after fault acknowledgement.
Stopping a movement
A movement may be stopped by:
The appearance of the STOP command (%Qr.m.c.8) or the setting to 0 of the ENABLE bit
(%Qr.m.c.10) or the STOP input.
The appearance of a blocking fault.
Changing the operating mode.
Receiving a configuration.
The switch to plus (or minus) end of run limit during a movement in the plus (or minus) direction.
128
35006224 12/2018
Programming
Visual movement commands
At a Glance
To carry out a visual movement, you must use the manual commands JOG_P and JOG_M.
The bits JOG_P (%Qr.m.c.1) and JOG_M (%Qr.m.c.2) control the movement of the moving part in the positive or negative direction. The operator must visually follow the position of the moving part.
The movement continues for as long as the command is present and it is not disabled by a STOP command or a fault.
The commands JOG_P and JOG_M are taken into account on edge and are kept active on state, whether the axis is referenced or not.
Movement speed
The movement is carried out at the manual mode speed MAN_SPD, defined in the adjustment screen (or in the double word MAN_SPD (%MDr.m.c.20)).
The speed can be modulated during movement by means of the CMV (Speed Modulation
Coefficient) (%QWr.m.c.1).
Any movement speed higher than FMAX (maximum speed of the axis defined at configuration) is limited to the FMAX value.
Movement speed of the moving part:
35006224 12/2018
129
Programming
Notes on the JOG_P and JOG_M commands
The commands JOG_P and JOG_M are used to release the moving part when a software limit fault is detected. This is done after first acknowledging the fault.
If the JOG_P or JOG_M bit is set to 1 when switching to manual mode, this command is not recognized. It will only be recognized when the bit has been cleared and then reset to 1
(detection of rising edge).
130
35006224 12/2018
Programming
Incremental movement commands
At a Glance
To carry out an incremental movement, you must use the manual commands INC_P and INC_M.
The bits INC_P (%Qr.m.c.3) and INC_M (%Qr.m.c.4) control the movement to increment the position of the moving part in the positive or negative direction.
The value of the position increment PARAM is entered in the double word PARAM (%QDr.m.c.2) or in the debug screen of the TSX CFY module.
Further to the general conditions of execution in manual mode, the commands INC_P and INC_M are active on rising edge when:
The axis is referenced.
The target position is between the software limits.
Movement speed
The movement is carried out at the manual mode speed, defined in the adjustment screen or in the double word MAN_SPD (%MDr.m.c.20)).
The speed can be modulated during movement by means of the SMC coefficient (%QWr.m.c.1).
Any movement speed higher than FMAX (maximum speed of the axis defined at configuration) is limited to the FMAX value.
Movement speed of the moving part:
35006224 12/2018
131
Programming
Reference point command
At a Glance
You can take a reference point by using the command SET_RP.
The bit SET_RP (%Qr.m.c.5) takes a manual reference point with movement.
The type and the direction of the reference point are defined at configuration in the Reference point
( see page 152 )
parameter. The value of the source is defined in the adjustment screen by the
parameter RP Value or the double word RP_POS: (%MDr.m.c.22).
Approach speed
The approach speed is the manual speed defined in the adjustment screen or in the double word
MAN_SPD (%MDr.m.c.20) multiplied by the CMV (Speed Modulation Coefficient). The reference point speed varies according to the type of reference point selected.
Any movement speed higher than FMAX (maximum speed of the axis defined at configuration) is limited to the FMAX value.
Example: short cam only and + direction
132
35006224 12/2018
Programming
Forced reference point command
At a Glance
You can take a forced reference point by using the command RP_HERE.
The bit RP_HERE (%Qr.m.c.6) takes a forced reference point without moving, at the value defined in the PARAM parameter. This value is entered in the double word PARAM (%QDr.m.c.2) or in the debug screen of the TSX CFY 11/21 module.
The forced reference point command is used to reference the axis without carrying out a movement.
NOTE: The command RP_HERE does not modify the value of the RP_POS parameter.
The value of the PARAM parameter must be between the software limits.
No blocking fault is tolerated during execution of this command.
35006224 12/2018
133
Programming
Management of direct mode (DIRDRIVE)
At a Glance
DIRDRIVE mode is used to simulate the axes control without operating the functional part; all the returned information is calculated.
The behavior of the axis can therefore be analyzed independently from the functional part.
Selecting direct mode
Direct mode is selected by assigning value 1 to the word MODE_SEL (%QWr.m.c.0.).
On a request to change mode, the moving part is stopped, then the mode is changed. When the command for switching into direct mode has been recognized, the bit IN_DIRDR (%Ir.m.c.17) is set to 1.
Execution of commands in direct mode
Direct mode includes the movement command DIRDRV (%Qr.m.c.0).
The speed setpoint is transmitted periodically by the variable PARAM (%QDr.m.c.2). The sign of this variable gives the movement direction.
The speed of the translator is controlled between SS_FREQ and FMAX. These values are defined in the configuration screen (FMAX) and in the adjustment screen (SS_FREQ).
The bit ST_DIRDR (%Ir.m.c.20) indicates that a movement is in progress in DIRDRIVE mode.
Speed law
When the setpoint is changed, the output achieves the new setpoint according to a trapezoid speed law, respecting the parameterized acceleration .
134
35006224 12/2018
Programming
Execution of the DIRDRIVE command
The general conditions for execution of the DIRDRIVE command are as follows:
Axis without blocking fault bit AX_OK = : (%Ir.m.c.3).
STOP command (%Qr.m.c.8) inactive and confirmation bit of the translator relay ENABLE
(%Qxy.i.10) set to 1.
Parameter PARAM (%QDr.m.c.2) between - FMAX and -SS_FREQ or between SS_FREQ and
FMAX of the selected axis.
Stopping a movement
A movement may be stopped by:
The appearance of the STOP command or the setting to 0 of the confirmation bit of the translator relay ENABLE (%Qr.m.c.10).
The appearance of a blocking error or a software limit error.
Changing the operating mode.
Receiving a configuration.
The switch to the end of run plus limit (or minus) during a movement in the plus (or minus) direction.
NOTE: Software limit monitoring remains active is the axis is referenced. To disable this monitoring, cause the axis reference to be lost by temporarily diasabling ENABLE (%Qr.m.c.10) to
0 and confirming by setting ENABLE to 1 or by pressing the confirmation button.
35006224 12/2018
135
Programming
Management of stop mode (OFF)
At a Glance
This mode is mainly used in debug from within the configuration editor. It can however be programdriven. In this mode the module remains passive, but continues to update the current position information POS (%IDr.m.c.0) and the current speed information SPEED (%IDr.m.c.2).
Selecting stop mode
Stop mode is selected by assigning value 0 to the word MODE_SEL (%QWr.m.c.0.).
Stop mode is also selected by the module when the PLC is in STOP mode. It is selected by default following channel configuration.
Execution of commands in stop mode
The OFF mode has no associated movement command.
The movement of the moving part is not monitored and the monitoring of software errors is disabled
(with the exception of the software limit monitoring).
The translator enable output continues to be monitored by the command ENABLE (%Qr.m.c.10).
136
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Configuration
35006224 12/2018
Configuring step by step axes control
Chapter 8
Configuring step by step axes control
Subject of this chapter
This chapter describes the configuration screens in the TSX CFY modules.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Description of the configuration screen of an axis control module
Access to the parameters configuration screen
Configuring user units
Configuring the translator’s command mode
Configuring control parameters
Configuring translator inversion
Configuring translator boost
Configuring the step by step motor’s brake
Configuring event tasks
Reference point configuration
Validating the configuration parameters
Page
35006224 12/2018
137
Configuration
Description of the configuration screen of an axis control module
General
The configuration screen is a graphics tool designed to configure
(see EcoStruxure™ Control
Expert, Operating Modes)
a selected module in a rack. It displays the parameters associated to channels of this module, and makes it possible to modify them in local and connected mode.
It also gives access to debug and adjustment screens (the latter only in connected mode).
NOTE: it is not possible to configure a module by program directly using %KW language objects, these words are accessible in read only.
Illustration
The figure below represents a configuration screen.
138
35006224 12/2018
Configuration
Description
The following table shows the different configuration screen elements and their functions.
2
3
Address Element
1 Tabs
4
5
Module zone
Channel zone
Function
The tab in the foreground shows the current mode (Configuration for this example). Each mode can be selected by the corresponding tab. The modes available are:
Configuration,
Adjustment,
Note : in online mode, other tabs appear that allow you to command the module and debug the program.
Summary of the abbreviated heading of the module.
Is used:
By clicking on the reference number, to display the tabs:
Description which gives the characteristics of the device.
I/O Objects (see EcoStruxure™ Control Expert, Operating Modes) which is used to presymbolize the input/output objects.
Fault which shows the device faults (in online mode).
General parameters zone
To select the channel,
To display the Symbol, name of the channel defined by the user (using the variable editor).
Makes it possible to choose the axis control function and the task associated to the channel :
Function : Positioning. By default, No function is configured.
Task: defines the task (MAST or FAST) in which the implicit exchange objects or the channel will be exchanged.
Configurationzone Makes it possible to configure the channel parameters. This zone includes different headings, displayed according to the function selected. Some choices may be disabled and appear grayed out.
For each parameter, the limits are displayed in the status bar.
35006224 12/2018
139
Configuration
Access to the parameters configuration screen
Accessing module parameterization
To access module parameterization, double click on its graphical representation in the rack or:
select the module (by clicking on it), activate the command Open module from the Edit menu.
Parametering screen
The following screen allows you to parameterize the module:
140
2
3
4
This screen is made up of 4 areas for information or the selection of parameters.
Area
1
Description
This header is a reminder of the catalog reference of the module and its geographical address in the PLC (rack number and position in the rack).
This command field indicates the current mode: Configuration.
This module level area contains the short title of the module.
This channel level field allows you to select the channel to be configured, the associated function: Position and the task in which the implicit exchange objects are exchanged: MAST or
FAST.
35006224 12/2018
Channel configuration parameters input area
The lower right part of the screen gives access to parameter entry.
Configuration
NOTE: For each parameter, the limits are displayed in the status bar.
35006224 12/2018
141
Configuration
Configuring user units
Introduction
Movements and positions are always expressed in numbers of pulses or increments. Speeds are always expressed in pulses per second (Hertz).
Units pick list
The units pick list is as follows:
142
35006224 12/2018
Configuration
Description
Two selections are possible.
Unit
Hertz/s
Meaning
When this selection is enabled, we will speak of the moving part’s gradient of acceleration and deceleration.
Acceleration in Hertz/s: is equal to the speed gradient, dF/dt ms When this selection is enabled, we will speak of the duration of acceleration and deceleration of the moving part in miliseconds.
Acceleration in ms: is equal to the acceleration time for the speed to go from SS_FREQ to maximum speed
35006224 12/2018
143
Configuration
Configuring the translator’s command mode
Introduction
The speed setpoint is sent to the translator in order to control the step by step motor. This menu allows you to determine the manner in which this information is transmitted.
Command mode pick list
The command mode for the translator is as follows:
Description
Two selections are possible.
Selection Meaning
A = + Pulse B = - Pulse A pulse on A is a movement command (a step) in the positive direction along the axis, a pulse on B is a movement command in the negative direction along the axis.
+ pulse, - pulse mode
144
35006224 12/2018
Configuration
Selection Meaning
A = Pulse B = Direction In this pulse mode, A is a step movement command, the direction of the movement is indicated by B:
if B is set to 1 the movement is in the positive direction, if B is set to 0 the movement is in the negative direction.
Pulse / direction mode
35006224 12/2018
145
Configuration
Configuring control parameters
Introduction
The control parameters fields allow you to define the maximum speed and the maximum acceleration of the axes control.
NOTE: the terms speed and frequency are used interchangeably to characterize the ideas of speed.
Control parameters selection screen
The control parameters selection screen for the translator is as follows:
146
35006224 12/2018
Configuration
Description
Two fields are to be completed.
Selection Meaning
Max. speed The maximum speed (frequency) depends on the translator – motor – moving part as a whole.
The pulse generation circuit has a resolution of 1024 pulses on the frequency dynamic (zero frequency included).
The selection of a maximum speed has an influence on the frequency resolution of the channel. The following list gives the frequency resolution (Minimum Frequency) for a given max. frequency interval:
[1 Hz …936 Hz] mini frequency 0.92 Hz
[937 Hz …1873 Hz] mini frequency 1.83 Hz
[1874 Hz …4682 Hz] mini frequency 4.58 Hz
[4683 Hz …9365 Hz] mini frequency 9.16 Hz
[9366 Hz …46829 Hz] mini frequence 45.78 Hz
[46830 Hz …93658 Hz] mini frequence 91.55 Hz
[93659 Hz … 187316 Hz] mini frequency 183.11 Hz
Max. acc.
Example: for a max. frequency of 20 KHz, the resolution (Min. Frequency) is 45.78 Hz.
The effective acceleration of the axis that is defined in adjustment, must always be less than or equal to the maximum acceleration defined in the configuration.
The TSX CFY 11 and 21 modules are capable of modifying the rate of acceleration or deceleration every 5 ms. The dynamic resolution is 63 point, which means that when the selected unit of acceleration is the Hertz/s, in a given interval of maximum speed the acceleration can be between 1 and 63 times the minimum acceleration. The following list gives the authorized minimum accelerations for a given speed interval:
[1 Hz …936 Hz] minimum acceleration 183 Hz/s
[937 Hz …1873 Hz] minimum acceleration 366 Hz/s
[1874 Hz …4682 Hz] minimum acceleration 916 Hz/s
[4683 Hz,9365 Hz] minimum acceleration 1831 Hz/s
[9366 Hz,46829 Hz] minimum acceleration 9155 Hz/s
[46830 Hz …93658 Hz] minimum acceleration 18311 Hz/s
[93659 Hz …187316 Hz] minimum acceleration 36621 Hz/s
When acceleration is given in ms, the maximum acceleration corresponds to the minimum time taken to reach maximum speed when accelerating from the start stop frequency
(SS_FREQ).
35006224 12/2018
147
Configuration
Configuring translator inversion
Introduction
The translator is controlled by the channel of the TSX CFY 11 or 21 module. It is possible to configure the logic state of the translator enable output and the translator monitor input as well as the movement direction of the control of the signals A and B.
Configuration screen for translator inversions
The configuration screen for translator inversions is as follows:
Description
Three selections are envisaged.
Field
Enable
Output
Input
Monitoring
Command direction
Meaning
For translators having input validation, when this box is not selected, output validation is set to 1, when the translator is enabled. If not, it is set to 0.
For translators having input disabling, when this box is selected, output validation is set to 0, when the translator is enabled. If not, it is set to 1.
When this box is not selected, when the input monitor is set to 1, the translator is unavailable.
If not, it is available (configuration case for Phytron MSD/SD translator)
When this box is selected, when the input monitor is set to 1, the translator is available. If not, it is unavailable.
When this case is not selected, the direction of the signals A and B is that specified in the section Configuring the command mode
When this box is selected, the logic of the command is inverted. The selection A=+ Pulse /
B=-Pulse becomes A=-Pulse / B=+ Pulse and the selection A=Pulse / B=Direction is such that
B set to 1 commands a negative direction along the axis and B set to 0 commands a positive direction along the axis.
148
35006224 12/2018
Configuration
Configuring translator boost
At a Glance
Some translators have a boost input that can be configured on the TSX CFY 11 and 21.
Boost configuration screen
The configuration screen for translator boost is as follows:
Description
Two selections are conceivable:
Field
Automatic control
Inversion
Meaning
For translators with a boost input, when this box is not checked, the translator boost is
controlled by the object %Qr.m.c.14 BOOST ( see page 209 )
.
NOTE: The BOOST command remains active in automatic control mode. If the Automatic control option is checked, it is important to refrain from using this command to avoid any conflicts.
For translators with a boost input, when this box is checked, the translator boost is automatically activated in the acceleration or deceleration phase of the moving part.
When this box is not checked, the translator boost is active when the boost output is set to 1.
When this box is selected, the translator boost is active when the boost output is set to 0.
35006224 12/2018
149
Configuration
Configuring the step by step motor’s brake
At a Glance
Within the context of load carrying applications, it is possible to use a brake on the step by step motor.
Brake configuration screen
The brake configuration screen is as follows.
Description
Two selections are conceivable.
Field
Automatic control
Inversion
Meaning
When this box is not selected, the brake is controlled by the object %Qr.m.c.13 BRAKE
NOTE: The BRAKE command remains active in automatic control mode. If the Automatic control option is checked, it is important to refrain from using this command to avoid any conflicts.
When this box is checked, the control of the step by step motor’s brake is automatically activated when the moving part is stopped and deactivated when it starts.
When this box is not selected, the brake output is set to 0 when the brake command is active, if not it is set to 1 (24V) in order to deactivate the brake.
When this box is checked, the brake output is set to 1 when the brake command is active, if not it is set to 0.
150
35006224 12/2018
Configuration
Configuring event tasks
At a Glance
When you want to carry out a complementary process that uses the reflex entry, it is necessary to configure an event task associated to the axes control channel.
Event configuration screen
The configuration screen for the event task is as follows:
Description
Two fields are to be completed.
Field
Evt
Meaning
When this box is selected, this signifies that you want to associate an event task to the axes control channel.
Task number This number indicates the number of the event task that will be attached to the axes control channel. This number is between 0 and 31 for the TSX P57 1••, between 0 and 63 for the
TSX P57 2••, TSX P57 3•• and TSX P57 4•• and between 0 and 127 for the TSX P57 5••.
35006224 12/2018
151
Configuration
Reference point configuration
At a Glance
In order for a movement to be transformed into a position, it is necessary to assign a known dimension (generally selected as equal to 0) to a specific point on the axis. This operation is called setting the reference point. An axis on which a reference point has been set is known as
"referenced".
Illustration of the Reference point field
The reference point pick list is as follows.
Description
The Reference point field defines the type and direction of the reference point.
The types short cam and long cam are linked by connecting a reference point detector on the cam reference point input. The types end of run limit assume that end of run detectors have been installed.
Possibilities
Short cam, + direction
Approach speed (1) Reference Point Speed Icon
F F (2)
Short cam, - direction F
Long cam, + direction F
SS_FREQ
SS_FREQ
(2)
(2)
152
35006224 12/2018
Possibilities
Long cam, - direction
Approach speed (1) Reference Point Speed Icon
F SS_FREQ (2)
Configuration
End of run limit, + direction F SS_FREQ (2)
End of run limit, - direction F SS_FREQ (2)
(1) F is the speed programmed in the instruction in automatic mode or the FMANU speed (defined in the adjustment screen) in manual mode. This speed can be modulated by the CMV (Speed
Modulation Coefficient).
(2) The icon illustrates the reference point.
Reference point command
The reference point command is carried out:
in automatic mode, using instruction code 14: set reference point, in manual mode, using the command SET_RP: set manual reference point.
If SS_FREQ is zero, and if the reference point speed is SS_FREQ, then the actual reference point speed is the smallest that the module can generate in the selected range.
NOTE: SS_FREQ = the start stop frequency.
Forced reference point
There is also a forced reference point mechanism:
command G62 in Auto mode, command RP_HERE in Manu mode.
This setting of the reference point consists in forcing the position to a specified value. This operation does not entail any movement and therefore does not take account of the type of RP selected.
35006224 12/2018
153
Configuration
Short cam reference point
The following table gives a detailed description of short cam reference points
Type
Direction
Icon
Short cam
+Direction -Direction
154
35006224 12/2018
Configuration
Long cam reference point
The following table gives a detailed description of long cam reference points
Type
Direction
Icon
Long cam
+ Direction, start away from the cam - Direction, start away from the cam
Direction
Icon
+ Direction, start towards the cam - Direction, start towards the cam
35006224 12/2018
155
Configuration
Reference point end of run limit
The following table gives a detailed description of end of run limit reference points
Type
Direction
Icon
End of run limit
+ Direction, start away from the cam - Direction, start away from the cam
Direction
Icon
+ Direction, start towards the cam - Direction, start towards the cam
156
35006224 12/2018
Configuration
Validating the configuration parameters
At a Glance
When all the configuration parameters have been defined, the configuration must be confirmed using the Edit → Confirm command or by activating the associated icon:
Invalid configuration parameters
If one or several parameter values are outside the permitted limits, an error message is displayed to signal the invalid parameter.
For example the Maximum speed value is invalid:
The invalid parameters must be corrected before your configuration can be confirmed.
NOTE: In the configuration screens, invalid parameters are shown in red. The grayed out parameters cannot be modified because they depend on faulty parameters.
Invalid adjustment parameters
The first time the configuration is confirmed, the adjustment parameters are initialized. If subsequent modifications made to the configuration values result in the adjustment parameters being incorrect, an error message is displayed to signal the parameter in question.
For example, the speeds are outside the limits:
You must access the adjustment screen, correct the invalid parameter, then confirm.
35006224 12/2018
157
Configuration
Acknowledgment of confirmation
Your configuration has been acknowledged when:
all the configuration parameters are correct, all the adjustment parameters are correct, you have confirmed everything from the main screen of the configuration editor.
158
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Adjustment
35006224 12/2018
Adjusting step by step axes control
Chapter 9
Adjusting step by step axes control
Subject of this chapter
This chapter describes the principles of parameter adjustment: access to the screens, description of parameters and the adjustment procedure.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Preliminary operations before adjustment
Accessing adjustment parameters
Trajectory adjustment
Adjusting brake output
Adjusting the stop stage
Adjusting manual mode parameters
Confirmation of adjustment parameters
Saving / Restoring adjustment parameters
Reconfiguration in connected mode
Page
35006224 12/2018
159
Adjustment
Preliminary operations before adjustment
Preliminary conditions
TSX CFY module(s) installed on the PLC,
Axes control application(s) connected to the TSX CFY module(s),
Terminal connected to the PLC via the terminal port or via network,
Axes control configuration and program completed and transferred to the PLC processor,
PLC in RUN mode. You are advised to disable the movement command application program
(by using, for example, a program execution condition bit), in order to facilitate the adjustment operations.
Preliminary checks
Check the cabling,
Check that the movements can take place safely,
Check that the mechanical stops are cabled conforming to the safety rules (generally they act directly on the power supply sequence of the translator),
Check and adjust the translator according to manufacturer’s instructions,
160
35006224 12/2018
Adjustment
Accessing adjustment parameters
At a Glance
To access adjustment parameters, use the command Adjustment from the View menu in the configuration screen of the TSX CFY. You can also select Adjustment in the module zone in the configuration or debugging screens.
Accessing parameters
The adjustment screen allows you to select the channel to be adjusted and gives you access to the current or initial parameters:
Command
Choose axis
Function
Select channel 0 for example.
This button allows you to display either the current parameters or the initial parameters.
Initial parameters
The initial parameters are:
The parameters entered (or defined by default) in the configuration screen in local mode. These parameters have been enabled at configuration and transferred to the PLC.
The parameters taken into account at the time of the last reconfiguration in connected mode.
Current parameters
The current parameters are those which have been modified and enabled from the adjustment screen in connected mode (or by the program through an explicit exchange). These parameters are replaced by the initial parameters at the time of a cold restart.
NOTE: It is imperative to follow a session of determining adjustment parameters with an operation to save parameters.
35006224 12/2018
161
Adjustment
Illustration
The figure below shows an adjustment screen.
162
35006224 12/2018
Adjustment
Description
The table below presents the various elements of the adjustment screen and their function.
2
3
Number Element
1 Tabs
4
5 module zone
Channel zone
Function
The tab in the foreground indicates the current mode (Adjustment in this example). Each mode can be selected by the corresponding tab. The modes available are:
Adjustment
Configuration
Debug (or diagnostics), accessible in online mode only
Summary of the abbreviated heading of the module.
Is used:
By clicking on the reference number, to display the tabs:
Description which gives the characteristics of the device.
I/O Objects (see EcoStruxure™ Control Expert, Operating Modes) which is used to presymbolize the input/output objects.
Fault which shows the device faults (in online mode).
General parameters zone
To select the channel,
To display the Symbol, name of the channel defined by the user (using the variable editor).
Allows you to choose the axis control function and task associated with the channel :
Function : Position control. By default, no function is configured (None).
Task: defines the task (MAST or FAST or AUX0/1) in which the objects
(implicit exchange) of the channel will be exchanged.
Adjustment zone This zone contains the various values of the adjustment parameters.
35006224 12/2018
163
Adjustment
Trajectory adjustment
At a Glance
The adjustment screen supports characterization of the trajectory on the axis:
start and stop frequency, acceleration, software hi limit, software lo limit.
Illustration
The input area for trajectory characteristics is as follows.
164
35006224 12/2018
Adjustment
Description
The table below describes the dialog box for inputting trajectory characteristics.
Field Description
Start/stop frequency Called SS_FREQ, this is the minimum speed of the movement of the moving part.
If FMAX, the maximum speed defined in configuration, is lower than 4 KHz, SS_FREQ must be contained between 0 and FMAX.
Otherwise, SS_FREQ must be contained between 0 and 4KHz.
When SS_FREQ is left at zero, the start and stop frequency is the smallest frequency in the range
Acceleration Called ACC, this is the moving part’s acceleration and deceleration gradient or the period of acceleration needed to go from the speed SS_FREQ to FMAX (See
Configuring control parameters, page 146 ).
When the user-defined unit is Hertz/s, this parameter must be between the lower acceleration limit for the range of max speed and the acceleration entered in
configuration (See Description, page 147 ).
When the user-defined unit is ms, this parameter must be between the value of the max acceleration entered at configuration and 5000 ms.
Software Hi Limit
Software Lo limit
Called SLMAX and expressed by number of pulses, this is the maximum position of the movement of the moving part in the positive direction.
Called SLMIN and expressed by number of pulses, this is the minimum position of the movement of the moving part in the negative direction.
The software limits must respect the following differences:
SLMIN less than or equal to SLMAX
SLMIN and SLMAX between 16 777 216 and 16 777 215
When the two software limits SLMIN and SLMAX are zero, the monitoring of these software limits is not activated. Movements can be executed on the whole of the counting range from -16 777 216 to + 16 777 215 without, however, exceeding one of these limits.
35006224 12/2018
165
Adjustment
Adjusting brake output
At a Glance
The adjustment screen is used to parameterize the brake output, when automatic brake management has been selected at configuration. The delay can be set:
on activation, on deactivation.
Illustration
The zone for inputting delays on activation and deactivation is as follows.
166
35006224 12/2018
Adjustment
Description
The table below describes the dialog box for entering delays on activation and deactivation.
Field Description
Delay on activation This parameter is between –1000 and 1000 milliseconds. A negative value indicates an anticipation of the end of a movement. A positive value indicates a delay.
Delay on deactivation
This parameter is between –1000 and 1000 milliseconds. A negative value indicates an anticipation of the beginning of a movement. A positive value indicates a delay.
Diagram showing operation of the delay on output Brake.
1 Anticipation, delay on deactivation, negative value.
2 Delay, delay on deactivation, positive value.
3 Anticipation, delay on activation, negative value.
4 Delay, delay on activation, positive value.
35006224 12/2018
167
Adjustment
Adjusting the stop stage
At a Glance
This field is the period of the stop stage order when the speed is equal to the start and stop speed,
FDA. This period must be between 0 and 1000 ms.
There is a relation between the duration of the stop stage and the brake activation delay (when this delay value is negative) in cases when automatic management configured.
( see page 150 )
168
35006224 12/2018
Adjustment
Operation
How axes control operates with regard to the duration of the stop stage.
If the duration of the stop stage is greater than the brake activation delay
Then the brake is activated as soon as the speed has reached start/stop speed,
SS_FREQ. The duration of the stop stage is that of the adjustment parameter.
less than the brake activation delay the duration of the stop stage is forced to the duration of the brake activation, regardless of the value fixed in adjustment mode. The brake is activated as soon as the speed of the moving part has reached start/stop speed, FDA.
35006224 12/2018
169
Adjustment
Adjusting manual mode parameters
At a Glance
Adjustment of manual mode parameters defines the action of the moving part in manual mode
( see page 127 )
speed, the value of the reference point.
Illustration
The manual mode parameter input zone is as follows.
Description
The table below describes the dialog zone for inputting manual mode parameters.
Field
Speed
RP Value
Description
This is the movement speed, MAN_SPD, of the moving part in manual mode.
The value of the field determines the speed of the moving part in manual mode, when it is controlled by instructions JOG+, JOG-, INC+, INC- and the approach and stopping speed in
SET_RP, etc. The value of this field must be between the start/stop speed SS_FREQ and the
maximum speed FMAX set in the configuration
Modulation Coefficient (CMV).
.
Just as in automatic mode, the actual movement speed is modulated by the Speed
This is the value loaded into the current position when taking a reference point in manual mode.
The value of the Reference point field, RP_POS, is transferred to the immediate position,
X_POS when taking a reference point in manual mode with axes control in manual mode.
Generally speaking, the value of this field must be between SLMIN and SLMAX. In the special case, where SLMIN=SLMAX=0, the value of this field must be between -16 777 216 and
16 777 215.
170
35006224 12/2018
Adjustment
Confirmation of adjustment parameters
Introduction
When you have entered the adjustment parameters, you must confirm these parameters using the command Edit/Confirm or by clicking the icon.
Parameters outside the limits
If one or several parameter values are not within the authorized limits, an error message appears referencing the parameter concerned.
You must fix the parameter(s) that are at fault, then execute a further confirmation.
No modification of the configuration parameters
If you have not modified the configuration parameters, the modification of the adjustment parameters does not interrupt the working of the axis but changes its behavior.
The modified adjustment parameters are the current parameters (the initial parameters remain unchanged).
NOTE: During a cold start the current parameters are replaced by the initial parameters.
The initial parameters can be updated by the save command or by a reconfiguration operation.
35006224 12/2018
171
Adjustment
Saving / Restoring adjustment parameters
Saving parameters
To save current parameters (updating initial parameters), activate the command Services → Save parameters .
Restoring parameters
To replace the current parameters by the initial parameters, activate the command Services →
Restore parameters.
172
NOTE: The instruction RESTORE_PARAM allows the application to carry out this restoration operation. The restoration is also carried out automatically at the time of a cold start.
35006224 12/2018
Adjustment
Reconfiguration in connected mode
Introduction
When configuration parameters are modified, you must confirm these parameters using the command Edit → Confirm or by clicking on the icon.
Parameters which can be modified in connected mode
Only parameters that are not grayed out can be modified in connected mode. Other parameters like activation of an event task must be modified in local mode. Every time that you reconfigure, the corrected resolution becomes the initial resolution.
Stopping the movement in progress
All configuration in connected mode brings about a stop in the operation of the channel concerned and thus the stopping of the movement in progress. This is signaled by a dialog box:
35006224 12/2018
173
Adjustment
Parameter exchange when reconfiguring
The following diagram presents the parameter exchanges when reconfiguring in connected mode:
174
(1) or adjustment screen if a configuration parameter has first been modified in the configuration screen.
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Debugging
35006224 12/2018
Debugging a step by step axes control program
Chapter 10
Debugging a step by step axes control program
Subject of this chapter
This chapter describes the debugging functions for an axes control channel, in the different modes: stop, direct, manual, automatic. It also describes the diagnostics screen which gives you access to possible errors.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Debugging principles
User interface of the debug screen
Description of the debug screens
Detailed Information on the Debug Screen
Stop Mode (Off)
Direct Mode (Dir Drive)
Manual mode (Man.)
Automatic mode (Auto)
Channel diagnostics
Storage, document and simulation
Page
35006224 12/2018
175
Debugging
Debugging principles
At a Glance
Axes control, being integrated into the Control Expert program, uses the Control Expert debug functions.
Recap of the possibilities offered by Control Expert
Real time display and animation of the program.
For example, in Grafcet language, if you program each movement in a step, it will be easy to know which movement is in progress.
Inserting program breakpoints and execution points: cycle by cycle, network by network or statement by statement.
Accessing animation tables. This allows you to display the status words and bits and control the command bits for the SMOVE. You can also force object bits and block the Grafcet development.
176
35006224 12/2018
Debugging
Application specific debug screen
The Control Expert software also offers you an application specific debug screen specific to the
TSX CFY modules, which gives you access to all necessary information and commands:
35006224 12/2018
177
Debugging
User interface of the debug screen
Accessing the debug screen
You can only access the debug screen if the terminal is in connected mode.
If this is the case, access the debug screen in the following way:
Select the Configuration editor,
Select and confirm (or double click on) the rack position that contains the axes control module,
By default in connected mode, the debug screen is displayed.
Command buttons
The operation of the command buttons
is as follows:
For the on state commands (except JOG commands):
Pressing then releasing the button activates the associated command. The button’s internal light is lit when this command is recognized (the corresponding command bit %Q is set to 1).
Pressing then releasing the button a second time deactivates the command. The button’s internal light is extinguished when this command is recognized (the corresponding command bit
%Q is set to 0).
For on edge commands:
The command is activated as soon as the button is pressed then released. The button’s internal light lights up then is automatically extinguished.
The light situated next to the button signals the recognition of the command by the module.
Input field
All values entered into an input field must be confirmed using the button.
Using the keyboard
You can use the keyboard to browse in the screens or activate a command:
Keys
Shift F2
Tab
Arrow keys
Space Bar
Action
Allows you to move from one zone to another
In the same zone, allows you to move from one group of commands to another
In a group of commands, allows you to move from one command to another
Allows you to activate or deactivate a command
178
35006224 12/2018
Debugging
Conflicts with the program
There can be conflicts between the Control Expert program that carries out the commands or writes the variables and the commands executed from the debug screen. In all cases, it is the last recognized command that will be active.
Animation
You can stop animation in the display fields:
The command Services → Stop animation stops animation in the display fields and disables the command buttons. For this function you can also use the icon
The command Services → Animate reactivates animation. You can also use the icon
35006224 12/2018
179
Debugging
Description of the debug screens
At a Glance
The debug screens have a common header, made up of a module zone and a channel/function zone.
Module zone
This table describes the module zone:
Light
RUN
ERR
IO
State
On
On
Flashing
On
Meaning
Module is operating
Module is out of service
Communication error with the processor
Process error (AX_FLT %Ir.m.c.2 bit)
Module failed. In choosing the Default tab associated with this button, a diagnostics window appears in order to clarify the source of the error
(See Diagnostics and maintenance, page 195
).
180
35006224 12/2018
Debugging
Channel/function zone
In addition to Channel and Function options (common to all screens), this zone also includes a mode selector button and an unforcing button:
Command Function
Button to select the operating mode
If you want to change the operating mode, click on the name of the new mode to be selected (or click as many times as necessary on the button).
Using the keyboard, select the button using the Tab key then press as many times as necessary on the Space bar.
You can also access the operating modes via the View menu.
When the selected mode is actually recognized by the module, the monitoring zone for movements in the selected mode is displayed.
Caution: although selected, it is possible for the selected mode not to be recognized by the module channel (for example, if the PLC is in STOP mode).
The unforcing button enables global unforcing of all forced objects.
35006224 12/2018
181
Debugging
Detailed Information on the Debug Screen
At a Glance
The debug screen is different according to the switch position selected. There are four possible choices:
Stop Mode (Off), page 186
Direct Mode (Dir Drive), page 187
Manual mode (Man.), page 188
Automatic mode (Auto), page 189
The fields and buttons that appear in the four screens are detailed below.
Description of the Movement / Speed Field
This table describes the display zones of the Movement / Speed field:
Display zone Description
X Current Displays the position of the moving part in number of pulses.
X Target Displays the position setpoint of the moving part (position to be reached)
X Remainder Displays the number of pulses left to run
F Current
F Target
N G G9
Displays the speed of the moving part in number of pulses
Displays the speed setpoint of the moving part: speed to be reached (manual speed modulated by the SMC (Speed Modulation Coefficient))
In auto mode, displays the instruction currently being executed:
N for the number of steps
G9 for the type of movement
G for the instruction code
Position
Speed
This slider shows the evolution of the moving part between the limits defined in the configuration screen. The color of the slider is green and becomes red if the limits are exceeded.
This slider displays as a % the speed of the moving part in relation to the maximum speed.
The color of the slider is green and becomes red if VMAX is exceeded.
This table describes the indicators in the Movement / Speed field:
Indicator
+Direction
-Direction
AT Point
NEXT
/
Status
On
On
Meaning
Indicates a movement of the moving part in the positive direction
Indicates a movement of the moving part in the negative direction
Indicates that the movement in progress has finished and that the moving part has reached the target point
Indicates that the moving part is ready to receive a movement command
182
35006224 12/2018
Debugging
Indicator Status
DONE On
Immediate pause On
Meaning
Indicates that the movement in progress has finished
Indicates that the immediate pause function is activated SMC (Speed
Modulation Coefficient) set to 1). At this moment the target position contains the immediate pause stop position.
Description of Axis Field
This table describes the display and command zones of the Axis field:
Indicator / Button Status
OK On
Referenced
Stopped
Enable /
On
On
Meaning
Axis in operational state (no blocking fault)
Referenced axis:
Moving part stationary
This button is used to control the variable speed controller activation relay
Description of I/O Field
This table describes the display zones of the I/O field:
Indicator Meaning
External stop Signal state (0 or 1) on External stopinput. The indicator is on when the external stop is activated, with presence of 24V on the input.
End of run +/- Activity of +/- limit switch function. The indicator is on when the moving part is at the limit switch stop, with absence of 24V on the input.
RP Cam Signal state (0 or 1) on Reference point input. The indicator is on when the moving part is on the cam, with presence of 24V.
Event Cam
Ctrl trans
Signal state (0 or 1) on Event input. The indicator is on when the moving part is on the event cam, with presence of 24V.
The indicator is on when the translator does not deliver the signal ready. The indicator is off when the translator gives the signal OK. The levels depend on the selection made at configuration.
Loss of step Signal state (0 or 1) onLoss of step monitoring input, signal delivered by the translator. The indicator is on when the input is set to 1(cable disconnected), otherwise it is off.
Reset step This button controls the resetting of the detection system which detects loss of translator step.
1 = indicator on, 0 = indicator off
35006224 12/2018
183
Debugging
Description of Commands
This table describes the command zone:
Command
STOP
Param
SMC (Speed Modulation
Coefficient)
Description
Causes the moving part to stop according to the deceleration defined on configuration
Is used to enter the value of an incremental movement (INC+ or INC- command) or the forced reference point
Is used to enter a value from 0 to 2000 which determines the speed multiplier coefficient (0.000 to 2.000 in steps of 1/1000)
Descriptions of EVT Sources
This table describes the EVT sources zone:
Command
RefP (indicator)
RefP (field)
End G10/G11
End G05
TO G05
Description
Indicates positioning of the event cam (reflex input) in response to SMOVE request
(G07)
Displays the stored PREF position
Indicates that an event has occurred during execution of the G10 or G11 instruction
Indicates the end of execution of the G05 instruction
Indicates that the Time Out, defined in the G05 instruction, has elapsed
Description of Commands Field
This table describes the buttons of the Commands field:
Command
JOG-
JOG+
INC-
INC+
Manual reference point
Forced reference point
Description
Visual movement command in the negative direction (1)
Visual movement command in the positive direction (1)
Incremental movement command in the negative direction, for a distance defined in the
Param field
Incremental movement command in the positive direction, for a distance defined in the
Param field
Order to search and take manual reference point. The current position takes the value
RP Value, defined in the adjustment screen, having found the reference point conforming to the type defined on configuration.
With an incremental encoder, forced reference point order. The current position is forced to the value defined in the Param field
This type of reference point does not cause movement of the moving part
184
35006224 12/2018
Debugging
Command
Brake
Boost
Pause
PLC Sync
Description
Manual command for the activation or deactivation of the brake output
In the case where automatic brake management is configured, it is the last activation or deactivation command edge between this manual BRAKE command (%Qr.m.c.13) and the automatic command that is taken into account.
Manual command for the activation or deactivation of the boost output
In the case where automatic boost management is configured, it is the last activation or deactivation command edge between this manual BOOST command (%Qr.m.c.14) and the automatic command that is taken into account.
Stop the movement sequence at the end of the next movement with stop
Order to trigger an event from the processor
(1) These commands remain active as long as the button is pressed. They are used to release the moving part outside the soft stops (after fault acknowledgment).
Description of Faults Field
This table describes the display and command zones of the Faults field:
Indicator/ Button
Cmd refused
Hardware
Axis
Ack.
Status
On
On
/
On
Meaning
Refusal of last command
External hardware fault (encoder, variable speed controller, outputs, etc.)
Application fault (following error, soft stops, etc.)
Fault acknowledgment button. Pressing this button acknowledges all the faults that have disappeared
35006224 12/2018
185
Debugging
Stop Mode (Off)
At a Glance
In this mode, the axis control channel only reports on position and speed. The module movement is not monitored by the channel. The translator confirmation output continues to be monitored by the ENABLE (%Qr.m.c.10). command.
186
For details on the fields and buttons in this screen, see
Detailed Information on the Debug Screen, page 182
.
35006224 12/2018
Debugging
Direct Mode (Dir Drive)
At a Glance
Direct mode allows you to directly control the movement of the moving part, according to the movement setpoint indicated in the PARAM variable.
For details on the fields and buttons in this screen, see
Detailed Information on the Debug Screen, page 182
.
35006224 12/2018
187
Debugging
Manual mode (Man.)
At a Glance
Manual mode allows you to directly control the movement of the moving part, from the debug screen. To do this you can use the commands JOG+, JOG-, INC+,
188
For details on the fields and buttons in this screen, see
Detailed Information on the Debug Screen, page 182
.
35006224 12/2018
Automatic mode (Auto)
At a Glance
Automatic mode is the mode in which the SMOVE functions are executed.
Debugging
For details on the fields and buttons in this screen, see
Detailed Information on the Debug Screen, page 182
.
35006224 12/2018
189
Debugging
Channel diagnostics
At a Glance
The module screens propose a Default tab in online mode that provides access to details of faults detected on the module and channel.
Example of channel diagnostics.
Description of different fields
The Default screen offers the following fields:
Field
Internal faults
External faults
Other faults
Commands refused
Description
Internal errors in the module that generally necessitate the replacement of the module
Errors coming from the operating part
Faults from the application ( see page 125 )
Indicate the cause and the message number of a command refused
190
35006224 12/2018
Debugging
Storage, document and simulation
Storage
When you have debugged your program in connected mode, you must carry out the following save operations:
Save the adjustment parameters if these have been modified. To do this, select the adjustment screen and use the command Services → Save parameters,
Save the application on to disk using the command File → Save.
Documentation
The documentation for the axes control application is included in the complete documentation for the Control Expert application. This documentation allows you to group in a file:
The program,
The saved Configuration and Adjustment parameters.
Simulation
To operate the channels of the TSX CFY module, all you need is the Telefast discrete simulator strip, reference ABE-6TES160, supplied by the 24 volts available on the rack supply, and to connect it directly to the TSX CFY’s auxiliary I/O HE10 connector via a ribbon cable.
For channel 0, add a level 1 to inputs 2, 4 and 5 (emergency stops and end of runs).
For channel 1 (only TSX CFY 21), inputs 8, 10 and 11. Leave the level 0 everywhere else.
When configuring the axis control channel, check the box drive inversionsmonitor input. This supports operation in the absence of any connection to the SUB D translator.
Confirm
How to carry out simulation with a TSC CFY
To operate the channels of the TSX CFY module, all you need is the Telefast discrete simulator strip, reference ABE-6TES160, supplied by the 24 volts available on the rack supply, and to connect it directly to the TSX CFY’s auxiliary I/O HE10 connector via a ribbon cable.
Step
1
2
3
4
5
Action
For channel 0, add a level 1 to inputs 2, 4 and 5 (emergency stops and end of runs).
For channel 1 (only TSX CFY 21), add a level 1 to inputs 8, 10 and 11. Leave the level 0 everywhere else.
When configuring the axis control channel, check the box drive inversionsmonitor input. This supports operation in the absence of any connection to the SUB D translator.
Confirm the channel in the implementation screen in manual mode.
Use the buttons JOG+ or JOG- to simulate movements of the moving part.
35006224 12/2018
191
Debugging
192
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Operation
35006224 12/2018
Operation
Chapter 11
Operation
Designing an operator dialog
Buttons box
To design a simple or a complex button box, you have at your disposal elementary commands and information, in the form of command and status bits and words
( see page 209 )
.
35006224 12/2018
193
Operation
194
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Diagnostic and maintenance
35006224 12/2018
Diagnostics and maintenance
Chapter 12
Diagnostics and maintenance
Subject of this chapter
This chapter describes what to do in certain maintenance situations (symptoms, diagnostics and course of action to undertake).
What Is in This Chapter?
This chapter contains the following topics:
Topic
Fault monitoring and command execution commands
Diagnostic help
Page
35006224 12/2018
195
Diagnostic and maintenance
Fault monitoring and command execution commands
Fault monitoring
You have several methods of detecting a possible fault:
the LEDs on the front panel of the module,
The diagnostics screens which can be accessed by means of the DIAG key in connected mode,
from all the application-specific screens
The debug screens
( see page 180
The fault bits and the status words
)
(
( see page 190
see page 209 )
)
Movement commands
In order for the movement commands (in automatic or manual mode) to be executable, the following conditions must be met:
The axis is configured and free of blocking errors,
The variable speed controller command is active: ENABLE (%Qr.m.c.10) and the STOP command is inactive (%Qr.m.c.8)
Automatic or manual mode is selected,
For commands using absolute position, the position is between the limits SL_MIN and SL_MAX,
For commands using relative position, the target calculated from the current relative position is between the limits SL_MIN and SL_MAX,
The axes are referenced, except for reference point and JOG commands,
The speed F must be less than or equal to FMAX,
If the moving part is outside the end of run limits, the movement direction requested must be that which returns it to within limits.
Modifying the CMV (Speed Modulation Coefficient) parameter
If a modification of the CMV (Speed Modulation Coefficient) parameter involves a speed higher than FMAX, then this is limited to FMAX.
Sequence control
If you have not selected the option Sequence control at configuration, a continuous movement followed by any sequence control will continue until the soft stops.
196
35006224 12/2018
Diagnostic and maintenance
Diagnostic help
At a Glance
You might be faced with situations that you need to resolve. The following procedure helps you to diagnose these situations and informs you of what to do.
Procedure to follow in various situations
New parameters are not recognized
Symptom
Diagnostics
What to do
The TSX CFY module does not seem to have recognized the new parameters written by WRITE_PARAM
Program a READ_PARAM instruction into your application so that you can find out the values actually used by the module.
A WRITE_PARAM activated while another adjustment exchange is in progress is ignored.
Test the ADJ_IN_PROGR bit (%MWr.m.c.0.2) before any adjustment exchange
Event processing
Symptom
Diagnostics
What to do
The event processing associated with the axes control channel is not executed
Check that the whole event trace string is valid
Event number declared in the configuration is identical to that in the event
processing,
The event source is unmasked (code M of the SMOVE command),
Events are authorized at system level ACTIVEVT = 1 (%S38),
Events are unmasked at system level (UNMASKEVT)
Refer to the use of events
Adjustments are lost
Symptom
Diagnostics
What to do
Your adjustments have been lost
A cold start causes the loss of the current adjustments carried out via the screen or a
WRITE_PARAM instruction
Save the current adjustments using the command Service → Save parameters or using the instruction SAVE_PARAM
Inconsistent status words
Symptom
Diagnostics
What to do
The status words EXCH_RPT (%MWr.m.c.1) and CH_FLT (%MWr.m.c.2) are not consistent with the status of the axis control channel.
These words are only updated on the explicit request READ_STS
Program a READ_STS instruction in your application
35006224 12/2018
197
Diagnostic and maintenance
Ineffectual commands
Symptom
Diagnostics
What to do
The commands from the debug screen are not having any effect
The application or the task is in STOP mode
Switch the application or the task into RUN mode
Non modifiable commands
Symptom
Diagnostics
What to do
Certain commands from the debug screen are not modifiable
These bits are written by the application
Use bit forcing for objects of type %Qr.m.c.d or rewrite your application so that it does not write these bits systematically (modification on transition and not on state)
Impossible to enter characters
Symptom
Diagnostics
What to do
It is impossible to enter more than 3 characters in the numeric fields of the adjustment and configuration screens
In the Windows configuration panel, you have not selected the thousand separator
In the Windows configuration panel, select the icon International in the field Number format.
Activate the Modify command and select a thousand separator
Command refused
Symptom
Diagnostics
What to do
In DIRDRIVE mode, after a stop after exceeding the soft stops, commands are refused.
The DIRDRIVE mode is activated after a session in MANU or AUTO mode during which a reference point has been taken. The axis is referenced. Monitoring of soft stops is active.
Exceeding one of these limits causes a stop with an error.
No further movement in DIRDRIVE mode is accepted.
Two types of actions are possible to restart movements:
Cause the loss of the axis reference, after the moving part has completely stopped:
unset the channel, ENABLE = 0 (%Qr.m.c.10) reset the channel, ENABLE = 1 (%Qr.m.c.10) acknowledge the error (rising edge on the command ACK_FLT (%Qr.m.c.9))
Force the position of the moving part between the soft stops:
switch for a moment to MANU mode
acknowledge the error: ACK_FLT (%Qr.m.c.9) take a forced reference point at a position situated between the soft stops switch back to DIRDRIVE mode.
198
35006224 12/2018
Diagnostic and maintenance
Bad recognition of commands in AUTO mode
Symptom
Diagnostics
What to do
In AUTO mode, after overshooting the soft stops of the end of run, movement commands are not carried out correctly.
After overshooting an end of run limit, the only commands accepted are movement commands going back in the return direction between the end of run limits.
Check whether the movement requested and incorrectly carried out was aiming to bring the moving part back between the end of run limits.
35006224 12/2018
199
Diagnostic and maintenance
200
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Complementary functions
35006224 12/2018
Complementary functions
Chapter 13
Complementary functions
Dimension learning
At a Glance
The following example of a Control Expert program supports learning and the use of 16 dimensions.
In the use part we will have first declared an AXIS_0 variable of the T_STEPPER_STD_ type
Dimension learning
This chart supports the programming of learning 16 dimensions.
STEP 50 ACTION ON ACTIVATION
<stores %MW99 with a view to use it as a limit
! %MW98 := %MW99;
<Initializes the index during the learning phase
! %MW99 := -1;
TRANSITION: X50 -> X51
! RE AXIS_0.NEXT
35006224 12/2018
201
Complementary functions
STEP 51 ACTION ON ACTIVATION
<updates the index
! %MW99 :=%MW99+1;
<learning of the positions
! %MD200[%MW99] := AXIS_0.POS;
TRANSITION: X51 -> X52
! %MW99 <= 16
TRANSITION: X51 -> X53
! %MW99 > 16
TRANSITION: X53 -> X50
! RE AXIS_0.DONE
TRANSITION: X52 -> X51
! RE AXIS_0.NEXT
TRANSITION: X52 -> X50
! RE AXIS_0.DONE
202
35006224 12/2018
Using dimensions
This chart supports the programming of using dimensions
Complementary functions
STEP 42 ACTION ON ACTIVATION
<initializes %MW97 as execution index
! %MW97 := -1;
TRANSITION: X42 -> X43
! RE AXIS_0.AX_FLT
STEP 43 ACTION ON ACTIVATION
<increments execution index
! %MW97 := %MW97+1;
<executes the next segment
! SMOVE (AXIS_0,%MW97,%KW8,%KW1,%MD200[%MW97],150000,0);
%KW8 : 90 movement to absolute value
%KW1 : 09 go to breakpoint
TRANSITION: X43 -> X46
! AXIS80.NEXT AND %MW97 < %MW98) AND NOT AXIS_0.AX_FLT
TRANSITION: X43 -> X42
! AXIS_0.DONE AND (%MW97 >= %MW98) OR AXIS_0.AX_FLT
TRANSITION: X46 -> X43
! TRUE
35006224 12/2018
203
Complementary functions
204
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Characteristics and performance
35006224 12/2018
Characteristics and performance
Chapter 14
Characteristics and performance
Performance characteristics and limitations
At a Glance
This section describes the performance and characteristics of the step by step control functions:
the memory size used by a SMOVE function, the time taken for the execution of step by step control functions, the module cycle time, the characteristics of the low-order value movements,
Size of an SMOVE function
This table indicates the memory zones used during an SMOVE instruction as well as the corresponding size in number of 16 bit words.
TSX CFY 11
TSX CFY 21
Additional cost of first configured channel
Bit memory
29
58
0
Data zone
390
780
0
Program zone
170
220
2290
35006224 12/2018
205
Characteristics and performance
Execution time
This table details the execution time for functions associated with step by step axes control.
Function description
Acquisition of inputs/outputs from TSX CFY
SMOVE function
READ_STATUS
READ_PARAM
WRITE_PARAM
SAVE_PARAM
RESTORE_PARAM
Recognition of an adjustment (following a WRITE_PARAM instruction)
Recognition of the reconfiguration of a channel
Execution time
95 micro-seconds
840 micro-seconds
540 micro-seconds
460 micro-seconds
760 micro-seconds
500 micro-seconds
780 micro-seconds
60 ms for the TSX CFY 11
210 ms for the TSX CFY 21
1.5 s
NOTE: the module cycle time is 10 ms
206
35006224 12/2018
Characteristics and performance
Small-sized movement characteristics
A low-order value movement corresponds to a movement that does not enable the speed specified in the instruction to be reached. The speed law resembles a triangle instead of a trapezoid.
Example of the instruction SMOVE (Axis_ch1,1, 90, 09, X1, V ,0) ,
Axis_ch1 is an IODDT type variable (T_STEPPER_STD),
X1 is the position to be reached,
V the cruising speed at which the movement must be made.
note X0 , the start position of the moving part.
This table describes the possible scenarios.
If the distance to run is X0 to X1 is sufficient to reach the specified speed V
Then the movement is executed according to a trapezoidal trajectory. This trajectory reveals the acceleration and deceleration periods equal to t_ACC is insufficient to reach the specified speed V the movement is executed according to a triangular trajectory, the periods of the acceleration and deceleration phases are reduced in proportion to the speed.
35006224 12/2018
207
Characteristics and performance
208
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Language objects
35006224 12/2018
Application-specific step by step axes control language objects
Chapter 15
Application-specific step by step axes control language objects
Subject of this chapter
This chapter describes the language objects associated to application-specific axes control as well as the different ways of using them.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Introduction to the language objects of the application-specific step by step axes control function
Implicit Exchange Language Objects Associated with the Application-Specific Function
Explicit Exchange Language Objects Associated with the Application-Specific Function
Management of Exchanges and Reports with Explicit Objects
Internal control objects (implicit exchange) of the IODDT of type T_STEPPER_STD
Internal control objects (implicit exchange) of the IODDT of type T_STEPPER_STD
Internal control objects (explicit exchange) of the IODDT of type T_STEPPER_STD
Objects of the adjustment parameters (explicit exchanges) of the IODDT of the
T_STEPPER_STD type
Exchanges between the processor and the axes control module
List of error codes CMD_FLT
Details of the Language Objects of the T_GEN_MOD-Type IODDT
Page
35006224 12/2018
209
Language objects
Introduction to the language objects of the application-specific step by step axes control function
General
The IODDTs are predefined by the manufacturer. They contain input/output language objects belonging to a channel of an application-specific module.
Step by step axis modules have an associated IODDT.
There is an IODDT type for the application-specific axis:
T_STEPPER_STD which applies to the 2 modules TSX CFY 11/21
NOTE: IODDT variables can be created in two different ways:
Using the I/O objects
Data Editor
(see EcoStruxure™ Control Expert, Operating Modes)
(see EcoStruxure™ Control Expert, Operating Modes)
.
tab,
Language object types
This IODDT contains a set of language objects that enable their operation to be controlled and verified.
There are two types of language object:
implicit exchange objects, which are automatically exchanged on each cycle revolution of the task associated to the module, explicit exchange objects, which are exchanged at the request of the application, using explicit exchange instructions.
The explicit exchanges concern the inputs/outputs of the module: measurement results, information and commands.
The explicit exchanges are used for the parametering and diagnostics of the module.
210
35006224 12/2018
Language objects
Implicit Exchange Language Objects Associated with the Application-Specific Function
At a Glance
An integrated application-specific interface or the addition of a module automatically enhances the language objects application used to program this interface or module.
These objects correspond to the input/output images and software data of the module or integrated application-specific interface.
Reminders
The module inputs ( %I and %IW ) are updated in the PLC memory at the start of the task, the PLC being in RUN or STOP mode.
The outputs ( %Q and %QW ) are updated at the end of the task, only when the PLC is in RUN mode.
NOTE: When the task occurs in STOP mode, either of the following are possible, depending on the configuration selected:
outputs are set to fallback position (fallback mode) outputs are maintained at their last value (maintain mode)
Figure
The following diagram shows the operating cycle of a PLC task (cyclical execution).
35006224 12/2018
211
Language objects
Explicit Exchange Language Objects Associated with the Application-Specific Function
Introduction
Explicit exchanges are performed at the user program's request using these instructions:
READ_STS (read status words)
WRITE_CMD (write command words)
WRITE_PARAM (write adjustment parameters)
READ_PARAM (read adjustment parameters)
SAVE_PARAM (save adjustment parameters)
RESTORE_PARAM (restore adjustment parameters)
For more details about instructions, refer to
EcoStruxure™ Control Expert, I/O Management, Block
Library
.
These exchanges apply to a set of %MW objects of the same type (status, commands or parameters) that belong to a channel.
These objects can:
provide information about the module (for example, type of error detected in a channel)
have command control of the module (for example, switch command) define the module’s operating modes (save and restore adjustment parameters in the process of application)
NOTE: To avoid several simultaneous explicit exchanges for the same channel, it is necessary to test the value of the word EXCH_STS ( %MWr.m.c.0
) of the IODDT associated to the channel before calling any EF addressing this channel.
NOTE: Explicit exchanges are not supported when X80 analog and digital I/O modules are configured through an eX80 adapter module (BMECRA31210) in a Quantum EIO configuration.
You cannot set up a module's parameters from the PLC application during operation.
212
35006224 12/2018
Language objects
General Principle for Using Explicit Instructions
The diagram below shows the different types of explicit exchanges that can be made between the application and module.
Managing Exchanges
During an explicit exchange, check performance to see that the data is only taken into account when the exchange has been correctly executed.
To do this, two types of information is available:
information concerning the exchange in progress
( see page 217 )
( see page 217 )
The following diagram describes the management principle for an exchange.
NOTE: In order to avoid several simultaneous explicit exchanges for the same channel, it is necessary to test the value of the word EXCH_STS ( %MWr.m.c.0
) of the IODDT associated to the channel before calling any EF addressing this channel.
35006224 12/2018
213
Language objects
Management of Exchanges and Reports with Explicit Objects
At a Glance
When data is exchanged between the PLC memory and the module, the module may require several task cycles to acknowledge this information. IODDTs use two words to manage exchanges:
EXCH_STS ( %MWr.m.c.0
): exchange in progress
EXCH_RPT ( %MWr.m.c.1
): report
NOTE:
Depending on the localization of the module, the management of the explicit exchanges
( %MW0.0.MOD.0.0
for example) will not be detected by the application:
For in-rack modules, explicit exchanges are done immediately on the local PLC Bus and are finished before the end of the execution task. So, the READ_STS , for example, is finished when the %MW0.0.mod.0.0
bit is checked by the application.
For remote bus (Fipio for example), explicit exchanges are not synchronous with the execution task, so the detection is possible by the application.
Illustration
The illustration below shows the different significant bits for managing exchanges:
214
35006224 12/2018
Language objects
Description of Significant Bits
Each bit of the words EXCH_STS ( %MWr.m.c.0
) and EXCH_RPT ( %MWr.m.c.1
) is associated with a type of parameter:
Rank 0 bits are associated with the status parameters:
The STS_IN_PROGR bit ( %MWr.m.c.0.0
) indicates whether a read request for the status
words is in progress.
The STS_ERR bit ( %MWr.m.c.1.0
) specifies whether a read request for the status words is accepted by the module channel.
Rank 1 bits are associated with the command parameters:
The CMD_IN_PROGR bit ( %MWr.m.c.0.1
) indicates whether command parameters are
being sent to the module channel.
The CMD_ERR bit ( %MWr.m.c.1.1
) specifies whether the command parameters are accepted by the module channel.
Rank 2 bits are associated with the adjustment parameters:
The ADJ_IN_PROGR bit ( %MWr.m.c.0.2
) indicates whether the adjustment parameters are being exchanged with the module channel (via WRITE_PARAM, READ_PARAM,
SAVE_PARAM, RESTORE_PARAM ).
The ADJ_ERR bit ( %MWr.m.c.1.2
) specifies whether the adjustment parameters are accepted by the module. If the exchange is correctly executed, the bit is set to 0.
Rank 15 bits indicate a reconfiguration on channel c of the module from the console
(modification of the configuration parameters + cold start-up of the channel).
The
r
,
m
and
c
bits indicates the following elements: the r bit represents the rack number.
The m bit represents the position of the module in the rack.
The c bit represents the channel number in the module.
NOTE: r represents the rack number, m the position of the module in the rack, while c represents the channel number in the module.
NOTE: Exchange and report words also exist at module level EXCH_STS ( %MWr.m.MOD
) and
EXCH_RPT ( %MWr.m.MOD.1
) as per IODDT type T_GEN_MOD .
35006224 12/2018
215
Language objects
Example
Phase 1: Sending data by using the WRITE_PARAM instruction
When the instruction is scanned by the PLC, the Exchange in progress bit is set to 1 in %MWr.m.c
.
Phase 2: Analysis of the data by the I/O module and report.
When the data is exchanged between the PLC memory and the module, acknowledgement by the module is managed by the ADJ_ERR bit ( %MWr.m.c.1.2
).
This bit makes the following reports:
0: correct exchange
1: incorrect exchange)
NOTE: There is no adjustment parameter at module level.
216
35006224 12/2018
Language objects
Execution Indicators for an Explicit Exchange: EXCH_STS
The table below shows the control bits of the explicit exchanges: EXCH_STS ( %MWr.m.c.0
)
Standard Symbol
STS_IN_PROGR
CMD_IN_PROGR
Type Access Meaning
BOOL R
Address
Reading of channel status words in progress %MWr.m.c.0.0
BOOL R Command parameters exchange in progress
%MWr.m.c.0.1
ADJ_IN_PROGR BOOL R
RECONF_IN_PROGR BOOL R
Adjust parameters exchange in progress %MWr.m.c.0.2
Reconfiguration of the module in progress %MWr.m.c.0.15
NOTE: If the module is not present or is disconnected, explicit exchange objects ( READ_STS for example) are not sent to the module ( STS_IN_PROG (%MWr.m.c.0.0) = 0), but the words are refreshed.
Explicit Exchange Report: EXCH_RPT
The table below shows the report bits: EXCH_RPT ( %MWr.m.c.1
)
Standard Symbol Type Access Meaning
STS_ERR BOOL R Error detected while reading channel status words
(1 = detected error)
CMD_ERR BOOL R
ADJ_ERR
RECONF_ERR
BOOL R
BOOL R
Error detected during a command parameter exchange
(1 = detected error)
Error dectected during an adjust parameter exchange
(1 = detected error)
Error detected during reconfiguration of the channel
(1 = detected error)
Address
%MWr.m.c.1.0
%MWr.m.c.1.1
%MWr.m.c.1.2
%MWr.m.c.1.15
Counting Module Use
The following table describes the steps realized between a couting module and the system after a power-on.
2
3
Step
1
Action
Power on.
The system sends the configuration parameters.
The system sends the adjust parameters by WRITE_PARAM method.
Note: When the operation is finished, the bit %MWr.m.c.0.2 switches to 0.
If, in the begining of your application, you use a WRITE_PARAM command, wait until the bit
%MWr.m.c.0.2 switches to 0.
35006224 12/2018
217
Language objects
Internal control objects (implicit exchange) of the IODDT of type T_STEPPER_STD
List of objects (implicit exchange)
The table below presents the internal status objects (implicit exchange) of the IODDT of type
T_STEPPER_STD
Standard symbol
CH_ERROR
NEXT
DONE
AX_FLT
AX_OK
HD_ERR
AX_ERR
CMD_NOK
NO_MOTION
AT_PNT
CONF_OK
REF_OK
AX_EVT
HOME
DIRECT
IN_DROFF
IN_DIRDR
IN_MANU
IN_AUTO
ST_DIRDR
ST_JOG_P
ST_JOG_M
ST_INC_P
ST_INC_M
ST_SETRP
Type Access Description
EBOOL R Channel fault
EBOOL R
EBOOL R
Ready to receive a new movement command (in AUTO mode)
All instructions have been carried out: no instructions in the stack
EBOOL R
EBOOL R
Error present on the axis
No errors to stop the moving part
EBOOL
EBOOL
R
EBOOL R
EBOOL R
R
EBOOL R
Hardware fault present
Application fault present
Command refused
Moving part stationary
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Position of the moving part on target (in the window at the point, on instruction with stop)
Axis configured
Reference point taken (axis referenced)
Copy event physical inputs
Copy the CAME physical input of the module’s reference point
Indicates the movement direction.
ARRET mode active
Direct mode active manuel mode active automatique mode active
Movement in direct mode in progress
Unlimited movement in the + direction in progress
Unlimited movement in the - direction in progress
Unlimited incremental movement in the + direction in progress
Unlimited incremental movement in the - direction in progress
Manual reference point in progress
Address
%Ir.m.c.ERR
%Ir.m.c.0
%Ir.m.c.1
%Ir.m.c.2
%Ir.m.c.3
%Ir.m.c.4
%Ir.m.c.5
%Ir.m.c.6
%Ir.m.c.7
%Ir.m.c.8
%Ir.m.c.11
%Ir.m.c.12
%Ir.m.c.13
%Ir.m.c.3
%Ir.m.c.15
%Ir.m.c.16
%Ir.m.c.17
%Ir.m.c.18
%Ir.m.c.19
%Ir.m.c.3
%Ir.m.c.21
%Ir.m.c.22
%Ir.m.c.23
%Ir.m.c.24
%Ir.m.c.25
218
35006224 12/2018
Language objects
Standard symbol
ON_PAUSE
IM_PAUSE
STEP_FLT
EMG_STOP
EXT_STOP
HD_LMAX
HD_LMIN
ST_BRAKE
ST_BOOST
ST_DRIVE
OVR_EVT
EVT_G07
EVT_G05
TO_G05
EVT_G1X
POS
SPEED
REMAIN
SYNC_N_RUN
PREF
Type Access Description
EBOOL R
EBOOL R
Movement sequencing suspended
Movement suspended (immediate PAUSE)
EBOOL R
EBOOL R
EBOOL R
EBOOL R
Loss of step input status
Emergency stop input status
External stop input status
End of run + limit status
EBOOL R
EBOOL R
EBOOL R
EBOOL R
EBOOL R
End of run – limit status
Image of the step by step motor brake output
Image of the BOOST output activity
Translator status
Event overrun
EBOOL R
EBOOL R
EBOOL R
EBOOL R
DINT
DINT
DINT
INT
DINT
R
R
R
R
R
Event source: save position
Event source: end of G05 on event
Event source: G05 timing elapsed
Event source: end of G10 or G11 on event position measured speed measured number of pulses left to run number of steps in progress value of PREF register (only refreshed on activating event processing).
Address
%Ir.m.c.26
%Ir.m.c.27
%Ir.m.c.28
%Ir.m.c.29
%Ir.m.c.30
%Ir.m.c.31
%Ir.m.c.32
%Ir.m.c.33
%Ir.m.c.34
%Ir.m.c.35
%Ir.m.c.36
%Ir.m.c.37
%Ir.m.c.38
%Ir.m.c.39
%Ir.m.c.40
%IDr.m.c.0
%IDr.m.c.2
%IDr.m.c.4
%IWr.m.c.6
%IDr.m.c.7
35006224 12/2018
219
Language objects
Internal control objects (implicit exchange) of the IODDT of type T_STEPPER_STD
List of objects (implicit exchange)
The table below presents the internal control objects (implicit exchange) of the IODDT of type
T_STEPPER_STD
Standard symbol
DIRDRV
JOG_P
JOG_M
INC_P
INC_M
SET_RP
RP_HERE
STOP
ACK_FLT
ENABLE
EXT_EVT
PAUSE
BRAKE
BOOST
ACK_STEPFLT
MOD_SELECT
SMC
PARAM
Type Access Active on Description
EBOOL R/W Edge Command to move in direct mode.
EBOOL R/W Edge
EBOOL R/W Edge
Unlimited manual movement in the + direction
Unlimited manual movement in the - direction
EBOOL R/W
EBOOL R/W
Edge
Edge
Order for incremental movement (PARAM) in the + direction
Order for incremental movement (PARAM) in the - direction
EBOOL R/W Edge Manual reference point (RP_POS = source value) or switch to the non-referenced state
EBOOL R/W
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
EBOOL
R/W
R/W
R/W
R/W
R/W
R/W
EBOOL R/W
EBOOL R/W
INT
INT
DINT
R/W
R/W
R/W
Edge
State
Edge
State
Edge
State
Edge
Edge
State
Address
%Qr.m.c.0
%Qr.m.c.1
%Qr.m.c.2
%Qr.m.c.3
%Qr.m.c.4
%Qr.m.c.5
Forced reference point of a defined value in
PARAM or switch to the referenced state / calculation offset
%Qr.m.c.6
Immediate stop command (stopping of the moving part)
Fault acknowledgment
Confirmation of the axis controller safety relay
%Qr.m.c.8
%Qr.m.c.9
%Qr.m.c.10
Order to trigger an event from the processor %Qr.m.c.11
Command to suspend movements at end of the movement in progress
%Qr.m.c.12
Command to apply brake on the step by step motor
%Qr.m.c.13
Boost translator %Qr.m.c.14
Command to reset translator step monitoring %Qr.m.c.15
mode selector speed modulation
Value = speed modulation setpoint value.
This setpoint is between 0 and 2, in 1/1000 increments.
value of movement increment
%QWr.m.c.0
%QWr.m.c.1
%QDr.m.c.2
220
35006224 12/2018
Mode selector
MOD_SELECT : mode selector
1
2
Value
0
3
Mode
DRV_OFF
DIRDRIVE
MANU
AUTO
Description mesure mode: disables CNA output
Loop control disabled mode: direct control in operation manuel mode automatique mode
Language objects
35006224 12/2018
221
Language objects
Internal control objects (explicit exchange) of the IODDT of type T_STEPPER_STD
At a Glance
This part presents the internal status objects (explicit exchange) of the IODDT the
T_STEPPER_STD type which applies to the TSX CFY11/21 modules. It groups the word type objects, the bits of which have a special significance. These objects are presented in detail below.
Notes
Generally, the significance of the bits is given for status 1 of the bit. In some cases each bit status is explained.
Not all the bits are used.
Management of the exchanges: EXCH_STS
The table below shows the meaning of channel exchange check bits EXCH_STS (%MWr.m.c.0).
Standard symbol
STS_IN_PROGR
Type
BOOL
CMD_IN_PROGR
ADJ_IN_PROGR
BOOL
BOOL
RECONF_IN_PROGR BOOL
R
R
Access Meaning
R Exchange in progress of status parameters
(STATUS)
R
Command parameters exchange in progress
Adjustment parameters exchange in progress
Reconfiguration of the module in progress
Address
%MWr.m.c.0.0
%MWr.m.c.0.1
%MWr.m.c.0.2
%MWr.m.c.0.15
Exchange report: EXCH_RPT
The table below shows the meaning of report bits EXCH_RPT (%MWr.m.c.1)..
Standard symbol
STS_ERR
CMD_ERR
ADJ_ERR
RECONF_ERR
Type
BOOL
BOOL
BOOL
BOOL
R
R
Access Meaning
R status parameters (STATUS) exchange report
R
Command parameters exchange report
Adjustment parameters exchange report
Configuration fault
Address
%MWr.m.c.1.0
%MWr.m.c.1.1
%MWr.m.c.1.2
%MWr.m.c.1.15
Channel operation status: CH_FLT
The table below shows the meanings of the bits of the CH_FLT (%MWr.m.c.1) status word.
Standard symbol Type Access Meaning
EXT_FLT
MOD_FLT
CONF_FLT
BOOL R
BOOL R
BOOL R
External error (idem HD_ERR bit)
Internal error: module absent, out of order or in self-test mode
Hardware or software configuration error
Address
%MWr.m.c.2.0
%MWr.m.c.2.4
%MWr.m.c.2.5
222
35006224 12/2018
Language objects
Standard symbol Type Access Meaning
COM_FLT
APP_FLT
BOOL R
BOOL R
Communication error with the processor
Application fault (invalid configuration) or command fault
CH_LED_LOW BOOL R
CH_LED_HIGH BOOL R
Status of the channel light, there are three scenarios:
bit 8 = bit 9 = 0 channel LED off
bit 8 = bit 9 = 0 channel LED flashing bit 8 = bit 9 = 1 channel LED lit
Address
%MWr.m.c.2.6
%MWr.m.c.2.7
%MWr.m.c.2.7
%MWr.m.c.2.9
Axis operation status: AX_STS
The table below shows the meanings of the bits of the AX_STS (%MWr.m.c.3) status word.
Standard symbol Type Access
Hardware faults: HD_ERR (%Ir.m.c.4) (groups together the faults below)
BRAKE_FLT BOOL R
Meaning
DRV_FLT
EMG_STP
AUX_SUP BOOL R
Application faults: AX_ERR (%Ir.m.c.5) (groups the faults below)
SLMAX
SLMIN
BOOL
BOOL
BOOL
BOOL
R
R
R
R
Short-circuit fault on the brake output
Drive fault
Emergency stop fault
24V supply fault
Maximum soft stop overshoot
Minimum soft stop overshoot
Address
%MWr.m.c.3.1
%MWr.m.c.3.2
%MWr.m.c.3.5
%MWr.m.c.3.6
%MWr.m.c.3.3
%MWr.m.c.3.4
Other status data
The table below presents the meanings of the other status data.
Standard symbol
N_RUN
G9_COD
G_COD
CMD_FLT
T_XPOS
T_SPEED
Type
INT
INT
INT
INT
DINT
DINT
R
R
R
R
R
Access
R
Meaning number of steps in progress type of movement in progress code of instruction in progress refusal report target of the position to be reached speed to be reached
Address
%MWr.m.c.4
%MWr.m.c.5
%MWr.m.c.6
%MWr.m.c.7
%MDr.m.c.8
%MDr.m.c.10
NOTE: all this internal status data is updated on execution of the instruction READ_STS.
35006224 12/2018
223
Language objects
Objects of the adjustment parameters (explicit exchanges) of the IODDT of the
T_STEPPER_STD type
Adjustment parameters
%MWr.m.c.d
or %MDr.m.c.d
Standard symbol Type
ACC DINT
SL_MAX DINT
SL_MIN
SS_FREQ
MAN_SPD
RP_POS
BRK_DLY1
BRK_DLY2
STOP_DLY
DINT
DINT
DINT
DINT
INT
INT
INT
Access Description
R/W
Address
Acceleration value, dependent on the user-defined unit %MDr.m.c.12
R/W %MDr.m.c.14
R/W
High soft stop: SLMIN to LMAX for limited axis
Modulo in points for infinite axis
Lower soft stop: LMIN to SLMAX for limited axis
Modulo value in user units for infinite axis
%MDr.m.c.16
R/W
R/W
R/W
Start and stop speed: 0 to FMAX
Manual mode speed: 10 to VMAX
Reference point value in manual mode: SLMIN to
SLMAX
%MDr.m.c.18
%MDr.m.c.20
%MDr.m.c.22
R/W
R/W
R/W
Shift register to brake deactivation: -1000 to 1000
Shift register to brake activation: -1000 to 1000
The duration of the stop stage at the start and stop speed: 0 to 1000
%MWr.m.c.24
%MWr.m.c.25
%MWr.m.c.26
NOTE: these adjustment parameters are updated on the execution of a READ_PARAM function.
224
35006224 12/2018
Language objects
Exchanges between the processor and the axes control module
Diagram showing the exchanges
The different exchanges between the processor and the axis control module are as follows:
(1) Read or write from the adjustment screen or from the application, using explicit exchange instructions.
(2) Saving or restoring using commands Save parameters or Restore parameters from the
Control Expert Services menu or using the instructions SAVE_PARAM or RESTORE_PARAM.
35006224 12/2018
225
Language objects
List of error codes CMD_FLT
At a Glance
The command refused word CMD_FLT (%MWr.m.c.7) is read by explicit change. The messages are also available in non-encrypted format in the diagnostics dialog box, which can be accessed via the command DIAG.
Each byte of the word CMD_FLT is associated to a type of error:
The most significant byte signals an error in the configuration and adjustment parameters
(XX00).
The least significant byte signals a refusal to execute the movement command (00XX).
For example: CMD_FLT = 0004 (the least significant byte signals an error in the command JOG+).
Mot CMD_FLT
Configuration
These errors are signaled in the most significant byte of the word CMD_FLT. The numbers in brackets indicate the hexadecimal value of the code.
Value
2 (2)
3 (3)
4 (4)
5 (5)
Meaning
Reference point configuration error
Event priority configuration error
Maximum frequency configuration error
Maximum acceleration configuration error
Adjustment parameter
These errors are signaled in the most significant byte of the word CMD_FLT. The numbers in brackets indicate the hexadecimal value of the code.
Value
7 (07)
8 (08)
9 (09)
10 (0A)
11 (0B)
Meaning
Acceleration profile parameter error
Software Hi Limit parameter error
Software Low limit parameter error
Start and stop frequency parameter error
Frequency parameter error in manual mode
226
35006224 12/2018
Language objects
Value
12 (0C)
13 (0D)
14 (0E)
15 (0F)
32 (20)
Meaning
Reference point value parameter error
Delay on deactivation of brake parameter error
Delay on activation of brake parameter error
Stop stage parameter error
Parameter error, more than one WRITE_PARAM during movement
Movement command refused
These errors are signaled in the least significant byte of the word CMD_FLT. The numbers in brackets indicate the hexadecimal value of the code.
8 (8)
9 (9)
10 (0A)
11 (0B)
12 (0C)
13 (0D)
14 (0E)
15 (0F)
Value
1 (1)
2 (2)
3 (3)
4 (4)
5 (5)
6 (6)
7 (7)
16 (10)
17 (11)
18 (12)
21 (15)
22 (16)
23 (17)
24 (18)
25 (19)
26 (1A)
Message
MAN. command error insufficient conditions (Mode, Value, etc.)
MAN. command error MAN. movement in progress
MAN. command error simultaneous commands
MAN. command error JogP
MAN. command error JogM
MAN. command error IncP
MAN. command error IncM
MAN. command error IncP parameter
MAN. command error IncM parameter
MAN. command error manual RP
MAN. command error forced RP
AUTO command error insufficient conditions (parameters)
AUTO command error AUTO movement in progress
SMOVE command error insufficient conditions (Mode)
SMOVE G01 command error (1)
SMOVE G09 command error (1)
SMOVE G10 command error (1)
SMOVE G11 command error (1)
SMOVE G14 command error (1)
SMOVE G05 command error (1)
SMOVE G07 command error (1)
SMOVE G62 command error (1)
SMOVE execution command error
AUTO command error movement in progress
35006224 12/2018
227
Language objects
Value
27 (1B)
48 (30)
49 (31)
50 (32)
51 (33)
52 (34)
53 (35)
54 (36)
55 (37)
56 (38)
57 (39)
58 (3A)
59 (3B)
60 (3C)
61 (3D)
96 (60)
97 (61)
101 (65)
119 (77)
124 (7C)
125 (7D)
126 (7E)
127 (7F)
130 (82)
131 (83)
132 (84)
102 (66)
103 (67)
108 (6C)
109 (6D)
110 (6E)
113 (71)
116 (74)
118 (76)
Message
AUTO Command error, stack full
DIRDRIVE command error, insufficient command
DIRDRIVE command error, with mode change in progress
DIRDRIVE command error, with moving axis
DIRDRIVE command error, with stopped axis
DIRDRIVE command error, with disabled axis
DIRDRIVE command error, with blocking fault
DIRDRIVE command error, with frequency less than SS_FREQ
DIRDRIVE command error, with frequency more than FMAX
DIRDRIVE command error, with axis at the end of run + limit
DIRDRIVE command error, with axis at the end of run - limit
DIRDRIVE command error, with axis outside the end of run + limit
DIRDRIVE command error, with axis outside the end of run - limit
DIRDRIVE command error, with axis outside the Software Hi Limit
DIRDRIVE command error, with axis outside the Software Low Limit
MAN. JogP command error in Software Hi Limit
MAN. JogP command error, with stopped axis
MAN. JogP command error, JogM movement in progress
MAN. JogP command error at the end of run + limit
MAN. JogP command error position above the end of run + limit
MAN. JogP command error blocking fault other than software limit
MAN. JogP command error unacknowledged software limit blocking fault
MAN. JogP command error, disabled axis
MAN. JogM command error, stopped axis
MAN. JogM command error, JogP movement in progress
MAN. JogM command error at the end of run - limit
MAN. JogM command error position above the end of run - limit
MAN. JogM command error blocking fault other than software limit
MAN. JogM command error unacknowledged software limit blocking fault
MAN. JogM command error, disabled axis
MAN. JogM command error in Software Lo Limit
MAN. IncP command error position less than the Software Lo Limit
MAN. IncP command error position more than the Software Hi Limit
MAN. IncP command error, JogP movement in progress
228
35006224 12/2018
Language objects
150 (96)
151 (97)
152 (98)
154 (9A)
155 (9B)
158 (9E)
164 (A4)
165 (A5)
170 (AA)
174 (AE)
178 (B2)
179 (B3)
180 (B4)
181 (B5)
189 (BD)
190 (BE)
Value
133 (85)
134 (86)
135 (87)
136 (88)
137 (89)
138 (8A)
141 (8D)
146 (92)
147 (93)
148 (94)
149 (95)
Message
MAN. IncP command error, JogM movement in progress
MAN. IncP command error at the end of run - limit
MAN. IncP command error position above the end of run + limit
MAN. IncP command error, axis not referenced
MAN. IncP command error causes movement of the Software Lo Limit
MAN. Inc P command error stop condition
MAN. IncP command error, disabled axis
MAN. IncM command error position less than the Software Lo Limit
MAN. IncM command error position above the Software Hi Limit
MAN. IncM command error, JogP movement in progress
MAN. IncM command error, JogM movement in progress
MAN. IncM command error at the end of run - limit
MAN. IncM command error position above the end of run + limit
MAN. IncM command error, axis not referenced
MAN. command error IncM stop condition
MAN. IncM command error causes movement of the Software Hi Limit
MAN. IncM command error, disabled axis
MAN. manual RP manual IncP command error, JogP movement in progress
MAN. manual PO manual IncM command error, JogM movement in progress
MAN. error command manual PO stop condition
MAN. command error, manual PO disabled axis
MAN. command error forced RP position less than the Software Lo Limit
MAN. command error forced RP position above the Software Hi Limit
MAN. command error, forced RP JogP movement in progress
MAN. command error, forced RP JogM movement in progress
MAN. command error forced RP with unacknowledged software limit error
MAN. command error, forced PO disabled axis
(1) Indicates that one of the parameters of the SMOVE function does not conform. Examples: invalid movement type code, position outside the software limits, speed greater than FMAX, etc.
35006224 12/2018
229
Language objects
Details of the Language Objects of the T_GEN_MOD-Type IODDT
Introduction
Modules of Premium PLCs have an associated IODDT of type T_GEN_MOD .
Observations
In general, the meaning of the bits is given for bit status 1. In specific cases, an explanation is given for each status of the bit.
Not all bits are used.
List of Objects
The table below presents the objects of the IODDT:
Standard symbol
MOD_ERROR
EXCH_STS
STS_IN_PROGR
EXCH_RPT
STS_ERR
MOD_FLT
MOD_FAIL
CH_FLT
BLK
CONF_FLT
NO_MOD
EXT_MOD_FLT
MOD_FAIL_EXT
CH_FLT_EXT
BLK_EXT
CONF_FLT_EXT
NO_MOD_EXT
Type
BOOL
INT
BOOL
INT
BOOL
INT
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
R
R
R
R
R
R
R
R
R
R
R
R
R
R
Access Meaning
R Module error bit
Module exchange control word
Reading of status words of the module in progress
Exchange report word
Error detected while reading module status words
R
R
Internal error word of the module
Internal error, inoperable module
Channel error detected
Terminal block error
Hardware or software configuration mismatch
Module missing or inoperative
Internal error word of the module (Fipio extension only)
Address
%Ir.m.MOD.ERR
%MWr.m.MOD.0
%MWr.m.MOD.0.0
%MWr.m.MOD.1
%MWr.m.MOD.1.0
%MWr.m.MOD.2
%MWr.m.MOD.2.0
%MWr.m.MOD.2.1
%MWr.m.MOD.2.2
%MWr.m.MOD.2.5
%MWr.m.MOD.2.6
%MWr.m.MOD.2.7
Module is unserviceable (Fipio extension only) %MWr.m.MOD.2.8
Channel error detected (Fipio extension only) %MWr.m.MOD.2.9
%MWr.m.MOD.2.10
Terminal block error detected (Fipio extension only)
Hardware or software configuration mismatch
(Fipio extension only)
%MWr.m.MOD.2.13
Module missing or inoperative (Fipio extension only)
%MWr.m.MOD.2.14
230
35006224 12/2018
Premium and Atrium using EcoStruxure™ Control Expert
Index
35006224 12/2018
Index
A
automatic mode,
77
95
B
bit sequencing, buffer memory,
111
111
C
channel data structure for stepper motor con trol modules
T_STEPPER_STD, configuring,
137
connection bases,
69
translator signals, connection devices,
64
65
70
69
209
D
debugging,
182
209
134
E
226
event processing,
117
F
197
fault management, fault monitoring application,
functions,
159
125
17
115
120
35006224 12/2018
J
JOG,
127
speed,
129
M
127
O
136
186
P
205
91
209
Q
29
R
132
S
SMOVE,
98
SMOVE events-G05,
SMOVE events-G07,
100
107
108
T
83
83
209
TSXCFY11,
TSXCFY21,
68
209
231
Index
68
W
80
232
35006224 12/2018