Schneider Electric PL7 Junior/Pro - Premium PLC Application-specific functions - Step-by-step axis control User Guide
Oglas
Oglas
PL7 Junior/Pro
Premium PLC
Application-specific functions
Step-by-step axis control
TLX DS 57 PL7 40E engV4.0
2
Related Documentation
Introduction This manual is made up of 8 volumes: l Volume 1 l l
Common specific-functions
Discrete I/O function l l
AS-i bus setup
Man-machine interface function l l
Volume 2 l Counting function
Volume 3 l l l l Axis Control function
Volume 4 l Step-by-step axis control function
Volume 5 l Electronic cam function
Volume 6 l l l SERCOS function
Volume 7 l l
Analog function l PID Control function l Weighing function
Volume 8
Process control function
Related Documentation
TLX DS 57 PL7 40E 09.2000
3
Related Documentation
4
TLX DS 57 PL7 40E 09.2000
Table of Contents
About the book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
General on step by step axes control . . . . . . . . . . . . . . . . . . . . 11
Introduction to the step by step axes control environment . . . . . . . . . . . . . . . . . 12
Functionality offered by the axes control modules . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Implementation methodology . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Implementation methodology for step by step axes control . . . . . . . . . . . . . . . . 19
Chapter 3
Introductory example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chapter 4
Configuring step by step axes control . . . . . . . . . . . . . . . . . . . 51
Accessing the parameters configuration screen . . . . . . . . . . . . . . . . . . . . . . . . . 56
Configuring the translator’s command mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
5
6
Chapter 5
Programming step by step axes control . . . . . . . . . . . . . . . . . 75
Principles of programming a step by step axis . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Programming the SMOVE function (in automatic mode) . . . . . . . . . . . . . . . . . . . 79
Description of the SMOVE function parameters . . . . . . . . . . . . . . . . . . . . . . . . . 81
Description of basic movements with the SMOVE function . . . . . . . . . . . . . . . . . 85
Example of using an indexed position (repetitive movements) . . . . . . . . . . . . . . 93
Management of direct mode (DIRDRIVE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Chapter 6
Adjusting step by step axes control . . . . . . . . . . . . . . . . . . . 123
Saving / Restoring adjustment parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Chapter 7
Debugging a step by step axes control program . . . . . . . . . 139
Detailed information on the debugging screen . . . . . . . . . . . . . . . . . . . . . . . . . 146
Chapter 8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Chapter 9
Diagnostics and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 159
Fault monitoring and conditions of command runnability . . . . . . . . . . . . . . . . . 160
Chapter 10
Complementary functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Chapter 11
Characteristics and performance . . . . . . . . . . . . . . . . . . . . . . 169
Chapter 12 Application-specific step by step axes control language objects
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Introduction to the language objects of the application-specific step by step axes
Exchanges between the processor and the axes control module . . . . . . . . . . . 175
Explicit object exchange and report management . . . . . . . . . . . . . . . . . . . . . . 180
Internal command data (implicit exchanges). . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Adjustment parameters (explicit exchanges) . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195
7
8
About the book
At a Glance
Document Scope This manual describes the software implementation of step-by-step axis control function in TSX Premium PLC’s, using PL7 software.
Validity Note The updated of this manual takes into account the functionality of PL7 V4. Nevertheless it can be used for the implementation of previous versions of PL7.
Revision History
Rev. No.
1
Changes
Stepper motor axis control (specific functions)
Related Documents
Title of Documentation
Hardware installation manual
Reference Number
TSX DM 57 40E
Product Related
Warnings
User Comments We welcome your comments about this document. You can reach us by e-mail at
TLX DS 57 PL7 40E 09.2000
9
About the book
10
TLX DS 57 PL7 40E 09.2000
General on step by step axes control
1
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter introduces step by step axes control, describes it and the associated application-specific functions.
This Chapter contains the following Maps:
Topic
Introduction to the step by step axes control environment
Functionality offered by the axes control modules
General on the step by step axes control
Page
11
TLX DS 57 PL7 40E 09.2000
General
Introduction to the step by step axes control environment
Introduction The configuration of a step by step axes control architecture is as follows:
Pulses Translator
TSX Premium
Step by step motor
TSX CFY 21
Step by step axes control environment
PL7 Junior/Pro
End of run and reference point cams
The step by step axes control environment for TSX Premium PLCs is made up of 2 modules: l l
TSX CFY 11 (1 limited linear axis),
TSX CFY 21 (2 independently limited linear axes).
The PL7 software integrates basic application-specific step by step movement supporting the programming of these step by step axes control modules.
Basic movements are driven from the machine’s principal sequential control program, but carried out and controlled by the TSX CFY modules.
These modules control the rotation speed of a step by step motor, its accelerations and decelerations by delivering a frequency command to a translator (fmax = 187
KHz). The translator transforms each impulse into a basic movement of the step by step motor.
Control of the step by step motor is carried out in open loop. End of run, reference point and event inputs allow the module to control the movements of the moving part on the axis.
Some translators include a step failure mechanism: this information is put at the disposition of the user program which can initiate a new reference point.
The step by step axes control environment also includes the TSX CXP 611 cable to link the TSX CFY11/21 modules directly to the MSD and MS translators from the manufacturer Phyton Lektronik GmbH.
12
TLX DS 57 PL7 40E 09.2000
General
Functionality offered by the axes control modules
General
I
O
N
P
R
O
G
R
A
M
L
I
C
A
T
A
P
P
The axes control modules offer application inputs and outputs for each axis which allow you to implement the different functions.
The following structural breakdown presents the inputs/outputs associated to a channel:
Enabling monitoring
Command check
Modes
Operating parameters
Status
Pulse generator
Cams and limits
I
N
T
E
R
F
A
C
E
Enabling translator
Boost
+ Pulses
- Pulses or directions
Translator check
Losing steps
Resetting step loss command
Brake
Emergency stop
External stop
End of run limit - direction
End of run limit + direction
Reference point cam
External event
TLX DS 57 PL7 40E 09.2000
13
General
Application inputs/outputs
Programming a movement
The step by step axes control modules offer for each of the axes:
for auxiliary inputs/outputs: l l l l l l l l l l l one cam reference point input, two end of run inputs, one event input, one emergency stop input, one external stop input, l one static output for the axis brake.
for translator inputs/inputs: one translator check input, one step failure control input, one differential translator validation output, two differential impulse outputs, one positive, one negative, one differential step by step motor boost output, one differential step failure reset output.
In PL7 language, each movement is described by a movement command function
SMOVE. From this command SMOVE and the position of the moving part, the TSX
CFY module works out the position/speed setpoint and generates the pulses for this movement.
These parameters support the definition of specifications of use, limits,… Configuration and control parameters
14
TLX DS 57 PL7 40E 09.2000
Specific functionality of
TSX CFY modules
General
Functionality offered by the step by step axes control modules is as follows: l Event processing: the events detected by the module can be used to activate a sequential task in the sequential program.
l Boost command: this function allows you to boost the step by step motor during acceleration or deceleration phases.
l Brake command: this function allows you to control the brake of the step by step motor when starting and stopping the movement.
l l
Feed hold: this function allows you to stop the movement in progress momentarily.
Deferred pause: this function allows you to stop a machine cycle momentarily without disrupting it.
l l
end of run limits: overshooting these limits triggers the stopping of the movement. Having overshot an end of run limit, only return movements between the limits are accepted.
External stop: activation of the external stop input triggers the stopping of the l movement.
Step failure input and step failure control reset output: these functions allow you, via the application, to manage step failure information originating from the translator. For the module, the activation of step failure input does not constitute a stop condition, nor an error condition.
TLX DS 57 PL7 40E 09.2000
15
General
General on the step by step axes control
Introduction to specific functions
The specific functions of step by step axes control apply to the whole control system made up of: l l l l l l the command the translator the step by step motor.
The important ideas are as follows: the start stop frequency SS_FREQ the boost the brake output
Diagram of the step by step axes control system
This diagram describes a typical step by step axes control system.
Command Translator Step by step motor
Description
Block
Command
Description
The command function is carried out by a channel of a TSX FCY 11 or 21 module. The principal function of this channel is to provide a series of pulses of constantly controlled frequency, in order to carry out the required functions.
Translator The translator’s essential function is to transform each received pulse into a step (elementary rotation) of the motor, by circulating suitable currents in its windings.
Step by step motor
Step by step motors are built according to different technologies. For example permanent magnet motors, variable reluctance motors and hybrid motors which combine the two techniques. Furthermore, different winding solutions exist on the market: two, four or five phase motors.
Each type of motor is thus associated with a specific type of translator optimized for its technology.
16
TLX DS 57 PL7 40E 09.2000
Start stop frequency
Boost
Brake output
General
The control of different step by step systems must generally obey a common restraint, due to the response of the inertial system (motor and axis) to a pulsed command. The common constraint is the start stop frequency.
The start stop frequency is the frequency at which the motor can stop or start without ramp and without losing step. Its maximum threshold depends upon the external inertia related to the motor axis. Its average value is 400 Hz in a 1/2 step (1 turn/sec) and can be critical beyond 600/800 Hz (1.5 to 2 turns/sec) (typical values for Phytron
Elektronik tranlators/200 step motors/lathes).
This constraint exists at the stopping as at the starting of all movements, whence its name: start stop frequency, SS_FREQ. The TSX CFY modules allow you to adjust this value.
Note: in this manual, the terms frequency and speed are used interchangeably.
In the same way, the units of pulse position and pulse are the same. It is the same for the units of speed Hertz and Pulses/s and the acceleration units Hertz/s and
Pulses/s
2
.
Some translators have a boost input. This function consists in increasing the current in the motor windings.
The boost output from a channel of a TSX CFY module controls this input to the translator. It is thus possible to control the intensity of the motor current in synchronization with the movement. Notably automatic control mode for this output supports its activation during acceleration and deceleration phases.
When a brake is present on the axis, this static output supports its control in synchronization with the movement or at the request of the user.
This function is useful when you want to interrupt the supply to the motor in load carrying applications.
Note: when the channel is in the safety position, this output makes the brake active
(generally the brake is active when voltage is absent).
TLX DS 57 PL7 40E 09.2000
17
General
18
TLX DS 57 PL7 40E 09.2000
Implementation methodology
2
Implementation methodology for step by step axes control
Structural breakdown of the implementation methodology of a step by step axis
The following flowchart summarizes the different implementation phases. In order to fully understand the different phases, please also look at the Introductory example
TLX DS 57 PL7 40E 09.2000
19
Methodology
20
(See
Introductory example, p. 23) which complements this flowchart.
In local mode
Configuration editor
1
Registering the module in the
PLC configuration
2
Configuration of axis parameters
Configuration editor
Configuration and adjustment modes
Design
3
Programming movements (2)
Program editor
(1)
4
Transferring the application to
PLC memory
In connected mode
5
Adjustment and
Debugging
6
Adjusting axes parameters
Tests and debugging
Configuration editor
Adjustment mode
Configuration editor
Debugging mode
Documentation editor
Folder editor
7
In connected mode
Operation
8
Operation
CCX 17
TLX DS 57 PL7 40E 09.2000
Methodology
(1) If before the programming phase, you want to switch into manual mode, the moving part on different axes, it is possible to miss out step 3. On the other hand, steps 1, 2, 4, 5 and
6 are mandatory.
(2) The programming phase can be preceded by a phase of variable pre-symbolization, carried out using the variables editor. Pre-symbolization allows you to automatically generate the axes control module symbols.
TLX DS 57 PL7 40E 09.2000
21
Methodology
22
TLX DS 57 PL7 40E 09.2000
Introductory example
3
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes the implementation of an axes control application with the help of a TSX CFY module. This instructional example allows you to follow all the phases necessary to the implementation of step by step axis control.
This Chapter contains the following Maps:
Topic
Description of the example
Prerequisites
Configuring the TSX CFY module
Adjusting the TSX CFY module
Symbolization of variables in the example
Programming preliminary processing
Programming Grafcet
Programming transitions
Programming actions
Programming subsequent handling
Program transfer
Taking over in manual mode
Debugging
Archiving
Page
23
TLX DS 57 PL7 40E 09.2000
Introductory example
Description of the example
Introduction
Transfer device
The following example allows you to follow all the implementation phases of a TSX
CFY axes control application. It complements the implementation methodologies.
A transfer device removes parts coming out of machining. This device is made up of a claw that can move in space (X, Y axes) on a plane parallel to the ground.
As soon as a part appears on output conveyor belt A, the claw automatically goes to fetch it and put it on belt B or belt C according to the part type. Then the claw returns to the stand-by position and will move again as soon as a new machined part is detected.
The following picture illustrates the transfer device:
C1
Machining device
C2
Conveyor belt A
C3
C4
Conveyor belt B
Conveyor belt C
24
TLX DS 57 PL7 40E 09.2000
Inputs/outputs
Introductory example
The inputs/outputs are as follows:
I/O
C1
C2
C3
C4
Description
Detector to detect the presence of machined part
Sensor to identify the part type.
Sensor to detect claw open / claw closed.
Detector to detect edge of part (situated in the claw), linked to the event input from the module.
ENC0
ENC1
Incremental encoder of position in the X axis.
Incremental encoder of position in the Y axis.
O/F claw Open / close claw command.
Grafcet for the application
The Grafcet for the application is as follows:
0
1
2
3
4
5
6
Reference point
Referenced axes
Movement to standby position
Detection of a machined part
Movement to conveyor belt A
Detection of edge of part and claw stationary
Close claw
Type 1 part and claw closed
Movement to conveyor belt B
Claw stationary
8
Open claw
Claw open
Type 2 part and claw closed
Movement to conveyor belt C
Grab stationary
TLX DS 57 PL7 40E 09.2000
25
Introductory example
Description of the trajectory
The following diagram describes the trajectory of the claw:
Y_LMAX
4
Conveyor belt A
3
2
5
Standby position
7
Conveyor belt B
6
Conveyor belt C
1
X_LMIN
X_LMAX
Y_LMIN
1 Reference point at speed Vp0,
2 Movement at speed Vret to the stand-by position (Xatt, Yatt) with stop,
3 Movement towards belt A (XA, YA) at speed VA, as far as detection of the machined part,
4 Movement towards belt B (XB, YB) at speed VB, with stop,
6 Movement towards belt C (XC, YC) at speed VC, with stop,
5, 7 Movement at speed Vret to the stand-by position (Xatt, Yatt), with stop.
26
TLX DS 57 PL7 40E 09.2000
Introductory example
Operator dialog panel
The following controls grouped on a panel, allow you to drive the moving part manually when the installation has failed. The controls and the indicators are managed by a discrete input module and a discrete output module.
Auto X Y Error
Manual Select axis
Start cycle
Reference point
Ack.
Error
Stop cycle
Reverse Forward Emergency stop
Open claw
Close claw
Auto / Manual Operating mode selection switch.
Start cycle Executes automatic cycle.
Stop cycle Stops automatic cycle.
Select axis X / Y Selects axis to be driven in manual mode.
Reference point Manual reference point on selected axis.
Forward / Back Controls manual movement in the selected axis, in the positive or negative direction.
Error Indicator of all hardware faults and application errors.
Ack. Error Fault acknowledgement command.
Emergency stop Immediate halt of the moving part, regardless of which mode is selected.
Open claw Open claw command.
Close claw Close claw command.
TLX DS 57 PL7 40E 09.2000
27
Introductory example
Prerequisites
Prerequisites In order that only functions specific to axis control are described, it is assumed that l l the following operations have been carried out:
PL7 software is installed,
The hardware installation has been carried out: modules, translators driving the
2 axes have been cabled.
28
TLX DS 57 PL7 40E 09.2000
Introductory example
Configuring the TSX CFY module
Software declaration in the
PLC configuration
Start the PL7 software, select the command File
→
New, select a Premium processor and check the Grafcet option.
From within the Application Browser, access the configuration editor in the following way:
Step
1
2
3
Action
Open the folder Station (double click on the icon or click on its attachment).
Open the folder Configuration (double click on the icon or click on its attachment).
Double click on the icon Hardware configuration.
You must then select each constituent of the PLC configuration. The following selections have been made in this application: l l l l l l rack 0 and rack 1: TSX RKY 8E, processor: TSX P57 203 V5.0, supply modules: TSX PSY 2600 for rack 0 and TSX PSY 5500 for rack 1,
32 inputs module: TSX DEY 32D2K in position 3 in rack 0,
32 outputs module: TSX DSY 32T2K in position 4 in rack 0, axes control module: TSX CFY 21 in position 3 in rack 1,
Module configuration screen
Configuration
TSX 57203 V5.0...
XMWI
XTI..
0
2
6
0
0
P
S
Y
0
5
7
2
0
3
T
S
X
2 3
D
E
Y
3
2
D
2
K
4
D
S
Y
3
2
T
2
K
5 6
1
0
0
5
5
P
S
Y
1 2 3
2
1
C
F
Y
4 5 6
TLX DS 57 PL7 40E 09.2000
29
Introductory example
Enter the axes configuration parameters
For each axis, enter the configuration parameters in the following way:
Step
1
2
Action
Select position 3 in rack 1 then execute the command Edit
→
Open module or double click on the selected module).
Configure the parameters of channel 0. To do that: l l l select the function Positioning, select the task MAST, enter the parameters, in accordance with the following screen:
Configuration screen for channel 0
TSX CFY 21 [RACK1 POSITION 3]
Configuration
Designation: MOD.MOT.PAS A PAS 2 VOIES
Symbol:
Choose Axis: Function:
Channel 0 Positioning
Task:
MAST
Unit
Acceleration ms
Command mode
A = +Pulse/ B = -Pulse
Command parameters
Max. speed
Acc max.
VMax/
18 000
200
Event input
Rising edge
Falling edge
Hertz ms
Drive inversions
Enable output
Input Check
Direction of command
Reference point
Short cam / - Direction
Boost
Automatic control
Inversion
Brake
Automatic control
Inversion
Event
EVT
3 Confirm your entries using the command Edit
→
Confirm or by clicking on the icon
4 Carry out the same configuration for channel 1 of the module by repeating the procedure from step 2 for channel 1.
30
TLX DS 57 PL7 40E 09.2000
Introductory example
Adjusting the TSX CFY module
Inputting axes adjustment parameters
For each axis, enter the configuration parameters in the following way:
Step Action
1 Select position 3 in rack 1 then execute the command Edit
→
Open module (or double click on the selected module).
2 Click on the arrow situated to the right of the Configuration field and select Ad-
justment.
3 Configure the adjustment parameters for channel 0. To do this: l l select channel 0, enter the adjustment parameters, in line with the following screen:
Adjustment screen for channel 0
TSX CFY 21 [RACK1 POSITION 3]
Configuration
Designation: MOD.MOT.PAS A PAS 2 VOIES
Symbol:
Choose Axis: Function:
Channel 0 Positioning
Task:
MAST
Unit
Acceleration ms
Command mode
A = +Pulse/ B = -Pulse
Command parameters
Max. speed
Acc max.
VMax/
18 000
200
Event input
Rising edge
Falling edge
Hertz ms
Drive inversions
Enable output
Input Check
Direction of command
Reference point
Short cam / - Direction
Boost
Automatic control
Inversion
Brake
Automatic control
Inversion
Event
EVT
TLX DS 57 PL7 40E 09.2000
31
Introductory example
Step
4
Action
Confirm your entries using the command Edit
→
Confirm or by clicking on the icon
5
6
Carry out the same adjustments for channel 1 of the module by repeating the procedure from step 3 for channel 1
Then confirm the global configuration using the command Edit
→
Confirm or by clicking on the icon
32
TLX DS 57 PL7 40E 09.2000
Introductory example
Symbolization of variables in the example
Entering symbols
Access to symbols entry is by means of a double click in the Application Browser, then on the icons Variables and I/O.
Symbols entry screen
File Edit Utilities
PL7 Junior: CINZIA2 - [Variables]
View Application AP Debug Options Window ?
Parameters I/O Module address
Address Type Symbol
%I3.10
%I3.5
%I3.12
%I3.9
%I3.3
%I3.8
%I3.0
%I3.1
%I3.2
EBOOL ACQ_DEFAUTS
EBOOL ARRET_CYCLE
EBOOL ARRET_URGENCE
EBOOL Reverse
EBOOL AUTO_MAN
EBOOL Forward
EBOOL SENSOR_1
EBOOL CAPTEUR_2
EBOOL SENSOR_3
%I3.4
%I3.14
%I3.13
%I3.7
EBOOL DEPART_CYCLE
EBOOL FERM_PINCE
EBOOL OUV_PINCE
EBOOL PO_MAN
%I36
%CH3MOD
EBOOL SELECTION_X_Y
CH
%I3.MOD.ERR
BOOL
%MW3.MOD
WORD
%MW3.MOD.1
WORD
%MW3.MOD.2
WORD
%CH3.0
%I3.0.ERR
%MW3.0
%MW3.0.1
CH
BOOL
WORD
WORD
Ready LOCAL U:SYS
3 Entry field
Comment
Fault acknowledgement push-button to stop automatic cycle emergency stop travel of moving part in negative direction
AUTO or MANU mode selection switch travel of moving part in positive direction cell which detects for presence of machined part sensor for identifying type of part sensor for detecting open claw / closed claw push-button to start automatic cycle push-button to close claw push-button to open claw manual reference point selects axis to be controlled manually
MODIF
Internal variables symbols
The following internal variables are symbolized:
Address Symbol
%M0 Cycle
Comment
Condition of the machine in work mode
%MD50 X_ATTENTE Stand-by position (X axis)
%MD52 Y_ATTENTE Stand-by position (Y axis)
%MD54 X_B Position of belt B (X axis)
%MD56 Y_B
%MD58 X_C
%MD60 Y_C
Position of belt B (Y axis)
Position of belt C (X axis)
Position of belt C (Y axis)
TLX DS 57 PL7 40E 09.2000
33
Introductory example
Symbols for the discrete inputs module
The discrete inputs module is positioned in slot 3 in rack 0. Its symbols are as follows:
Address Symbol
%I3.0
CAPTEUR_1
%I3.1
%I3.2
CAPTEUR_2
CAPTEUR_3
%I3.3
%I3.4
%I3.5
AUTO_MAN
DEPART_CYC
LE
ARRET_CYCL
E
I%I3.6
%I3.7
%I3.8
%I3.9
%I3.10
SELECTION_X
_Y
PO_MAN
AVANT
ARRIERE
ACQ_DEFAUT
S
%I3.12
%I3.13
%I3.14
Comment
Detector to detect presence of machined part
Sensor to identify the part type (0 = type 2, 1 = type 1)
Sensor to detect claw open / claw closed
Switch to select mode (0 = Auto, 1 = Manual)
Push button to execute automatic cycle
Push button to stop automatic cycle
Select axis to drive in Manual mode (1 = X, 0 = Y)
Manual reference point
Move the moving part in the positive direction
Move the moving part in the negative direction
Fault acknowledgment
ARRET_URGE
NCE
Emergency stop
OUV_PINCE Push button to open claw
FERM_PINCE Push button to close claw
Symbols for the discrete outputs module
The discrete outputs module is positioned in slot 4 in rack 0. Its symbols are as follows:
Address Symbol
%Q4.0
PINCE
%Q4.1
DEFAUT
Comment
Command to open or close the claw (0 = Open, 1 = Close)
Signals an error
34
TLX DS 57 PL7 40E 09.2000
Introductory example
Symbols for the axes control module
The axes control module is positioned in slot 3 in rack 1. Its symbols are as follows:
Address
%CH103.0
%I103.0
%I103.0.1
%I103.0.2
%I103.0.3
%I103.0.4
%I103.0.5
%I103.0.6
%I103.0.9
%I103.0.11
%I103.0.12
%I103.0.16
%I103.0.17
%I103.0.18
%I103.0.19
Symbol
AXE_X
NEXT
DONE
ERROR
OK
HARD_ERR_X
AXIS_ERROR_X
REF_CMD_X
AT_POINT
CONF_X
CALIB
MODE_DRIVE_OFF
MODE_DIR_DRIVE
MODE_MANUEL
MODE_AUTO
%I103.0.35
%Q103.0
%Q103.0.1
%Q103.0.2
%Q103.0.3
%Q103.0.4
%Q103.0.5
%Q103.0.6
VARVALID_X
DIRDRIVE
JOG_P
JOG_M
INC_P
INC_M
SETRP
RP_HERE
%Q103.0.9
%Q103.0.10
ACQ_DEF
ENABLE
%Q103.0.11
EVENT_UC
%MD103.0.22
POSRP
Address
%CH103.1
%I103.1
%I103.1.1
%I103.1.2
%I103.1.3
%I103.1.4
%I103.1.5
%I103.1.6
%I103.1.9
%I103.1.11
%I103.1.12
%I103.1.16
%I103.1.17
%I103.1.18
%I103.1.19
Symbol
AXE_Y
NEXT_Y
DONE_Y
ERROR_Y
OK_Y
HARD_ERR_Y
AXIS_ERROR_Y
REF_CMD_Y
AT_POINT_Y
CONF_Y
CALIB_Y
MODE_DRIVE_OFF_Y
MODE_DIR_DRIVE_Y
MODE_MANUEL_Y
MODE_AUTO_Y
%I103.1.35
%Q103.1
%Q103.1.1
%Q103.1.2
%Q103.1.3
%Q103.1.4
%Q103.1.5
%Q103.1.6
VARVALID_Y
DIRDRIVE_Y
JOG_P_Y
JOG_M_Y
INC_P_Y
INC_M_Y
SETRP_Y
RP_HERE_Y
%Q103.1.9
%Q103.1.10
ACQ_DEF_Y
ENABLE_Y
%Q103.1.11
EVENT_UC_Y
%MD103.1.22
POSRP_Y
TLX DS 57 PL7 40E 09.2000
35
Introductory example
Internal constants
The speed of the moving part along the different axes is contained in the internal constants. In the case of 2 independent axes, the symbols and the values of these constants are as follows:
Address Symbol
%KD0 VITESSE_P_O
%KD4
Value
5000
Comment
Speed from the reference point along the axis of the X and Y axes
Speed towards the X axis stand-by position
%KD6
%KD8
%KD10
%KD12
%KD14
%KD16
%KD18
VITESSE_X_ATTE
NTE
VITESSE_Y_ATTE
NTE
VITESSE_POS_A_
X
VITESSE_POS_A_
Y
10000
10000
15000
15000
VITESSE_POS_B_
X
VITESSE_POS_B_
Y
15000
15000
VITESSE_POS_C_
X
12000
VITESSE_POS_C_
Y
12000
Speed towards the Y axis stand-by position
Speed towards the X axis belt A position
Speed towards the Y axis belt A position
Speed towards the X axis belt B position
Speed towards the Y axis belt B position
Speed towards the X axis belt C position
Speed towards the Y axis belt C position
36
TLX DS 57 PL7 40E 09.2000
Introductory example
Programming preliminary processing
Introduction Preliminary processing allows you to manage the operating modes: l l
With a blocking error:
The chart is disabled.
You can then drive the moving part in Manual mode, fix the error and acknowledge it from the panel.
l l l The chart is reinitialized when the error is fixed and acknowledged.
On switching to Manual mode:
The chart is disabled.
The chart is reinitialized when Automatic mode is selected again.
Program in
Ladder language
Initializing positions
%S0
%S1
OPERATE
X_ATTENTE:= 14000
OPERATE
Y_ATTENTE:= 10000
OPERATE
X_B:= 18000
OPERATE
Y_B:= 14000
OPERATE
X_C:= 16000
Y_C:= 2000
OPERATE
Starting cycle
CYCLE
P
CYCLE
%I103.M>> = %I103.MOD.ERR
DEPART_>> = DEPART_CYCLE
ARRET_>> = ARRET_CYCLE
TLX DS 57 PL7 40E 09.2000
37
Introductory example
Confirming controller
%I103.M>>
ERROR
ERROR_Y
%I103.M>> = %I103.MOD.ERR
Selecting automatic mode
AUTO_MAN VARVALID_X
N
VARVALID_Y
OPERATE
%QW103.0:= 3
OPERATE
%QW103.1:= 3
ENABLE
S
ENABLE_Y
S
Selecting manual mode
AUTO_MAN
P
OPERATE
%QW103.0:= 2
OPERATE
%QW103.1:= 2
Disabling chart on error or when switching into manual mode
MODE_>>
MODE_>>
OK
OK_Y
MODE_>> = MODE_AUTO
MODE_>> = MODE_AUTO_Y
%M1 = fixed Grafcet
%S23
S
%M1
S
38
TLX DS 57 PL7 40E 09.2000
TLX DS 57 PL7 40E 09.2000
Reinitializing chart
OK OK_Y MODE_>> MODE_>> %M1
Introductory example
%S23
R
%S21
S
%M1
R
MODE_>> = Mode_AUTO
MODE_>> = MODE_AUTO_Y
%M1 = fixed Grafcet
Signaling errors
OK %S6
OK_Y
Error
39
Introductory example
Programming Grafcet
Introduction
Sequential handling
Grafcet allows you to program the sequential handling of the operation: the handling of the automatic cycle.
CHART - PAGE 0
0
1
(*Start*)
(*Reference point*)
2
(*Referenced axes*)
(*Movement to standby position*)
(*Detection of machined part*)
3 (*Movement to conveyor belt A*)
(*Detect edge of part*)
4
(*Type 1 part and claw closed*)
(*Movement to conveyor belt B*)
(*Moving part in position on conveyor belt B*)
5
6
(*Close claw*)
(*Type 2 part and claw closed*)
(*Movement to conveyor belt C*)
(*Moving part in position on conveyor belt C*)
8
(*Open claw*)
(*Claw open*)
40
TLX DS 57 PL7 40E 09.2000
Introductory example
Programming transitions
Introduction
Step 0 -> 1
Step 1 -> 2
Step 2 -> 3
Step 3 -> 4
Step 4 -> 5
Step 4 -> 8
Step 5 -> 6
Step 8 -> 6
Step 6 -> 2
The transitions drawn in the Grafcet are programmed in the following way:
! (*X channel not in error, claw open, Auto_man switch set to Auto, Y channel not in error and automatic mode activated*)
NOT ERROR AND NOT CAPTEUR_3 AND NOT AUTO_MAN AND CYCLE AND NOT
ERROR_Y AND MODE_AUTO
! (*Test: axes ready and referenced*)
DONE AND CALIB AND DONE_Y AND CALIB_Y
! (*Moving part in stand-by position and part detected on belt A*)
CAPTEUR_1 AND CYCLE AND NEXT AND NEXT_Y
! (*Moving part in position to take part detected on belt A*)
AT_POINT AND NEXT AND NEXT_Y AND AT_POINT_Y
! (*Type 1 part and claw closed*)
CAPTEUR_2 AND CAPTEUR_3
! (*Type 2 part and claw closed*)
NOT CAPTEUR_2 AND CAPTEUR_3
! (*Moving part in position on belt B*)
AT_POINT AND NEXT AND NEXT_Y AND AT_POINT_Y
! (*Moving part in position on belt C*)
AT_POINT AND NEXT AND NEXT_Y AND AT_POINT_Y
! (*Claw open)
NOT CAPTEUR_3 AND CYCLE
TLX DS 57 PL7 40E 09.2000
41
Introductory example
Programming actions
Introduction In Grafcet it is possible to program actions for each step. Three types of action are possible: l l l on activation continuous on deactivation
When for a given step the type of action is not described, this means that it has not been programmed.
Step 1: Action on activation
! (*Origin taken along the X and Y axes*)
SMOVE AXE_X (1, 90, 14, 0, VITESSE_P_O, 16#0000);
SMOVE AXE_Y (1, 90, 14, 0, VITESSE_P_O, 16#0000);
Step 2: Action on activation
! (*Movement to stand-by position (XATT, YATT*)
SMOVE AXE_X (2, 90, 9, X_ATTENTE, VITESSE_X_ATTENTE, 16#0000);
SMOVE AXE_Y (2, 90, 9, Y_ATTENTE, VITESSE_Y_ATTENTE, 16#0000);
Step 3: Action on activation
! (*Movement towards belt A*)
SMOVE AXE_X (3, 90, 10, 19500, VITESSE_POS_A_X, 16#0000);
SMOVE AXE_Y (3, 90, 10, 19500, VITESSE_POS_A_Y, 16#0000);
Step 4:
Continuous action
! (*Closure of the claw*)
SET PINCE;
Step 5: Action on activation
! (*Movement towards belt B*)
SMOVE AXE_X (4, 90, 9, X_B, VITESSE_POS_B_X, 16#0000);
SMOVE AXE_Y (4, 90, 9, Y_B, VITESSE_POS_B_Y, 16#0000);
Step 8: Action on activation
! (*Movement towards belt C*)
SMOVE AXE_X (5, 90, 9, X_C, VITESSE_POS_C_X, 16#0000);
SMOVE AXE_Y (5, 90, 9, Y_C, VITESSE_POS_C_Y, 16#0000);
Step 6:
Continuous action
! (*Opening of the claw*)
RESET PINCE;
42
TLX DS 57 PL7 40E 09.2000
Introductory example
Programming subsequent handling
Introduction
MAST - POST
Post-processing allows you to program the management of manual mode.
! (*Test selected mode*)
IF MODE_AUTO AND MODE_AUTO_Y AND CONF_X AND CONF_Y
THEN JUMP %L200;
END_IF;
! (*Selecting the axis to be driven*)
%L100: IF NOT SELECTION_X_Y
THEN JUMP %L200;
END_IF;
! (*Origin taken manually on X axis*)
IF RE PO_MAN
THEN SET SETRP;
END_IF;
IF NOT PO_MAN
THEN RESET SETRP;
END_IF;
! (*Movement of the moving part in the positive direction along the X axis*)
JOG_P:= AVANT;
! (*Movement of the moving part in the negative direction along the X axis*)
JOG_M:= ARRIERE;
%L200: IF SELECTION_X_Y
THEN JUMP %L300;
END_IF;
! (*Origin taken manually on Y axis*)
IF RE PO_MAN
THEN SET SETRP_Y;
END_IF;
IF NOT PO_MAN
THEN RESET SETRP_Y;
END_IF;
! (*Movement of the moving part in the positive direction along the Y axis*)
JOG_P_Y:= AVANT;
! (*Movement of the moving part in the negative direction along the Y axis*)
JOG_M_Y:= ARRIERE;
! (*Opening of the claw*)
%L300: IF AUTO_MAN AND OUV_PINCE
THEN RESET PINCE;
END_IF;
! (*Closure of the claw*)
IF AUTO_MAN AND FERM_PINCE
THEN SET PINCE;
TLX DS 57 PL7 40E 09.2000
43
Introductory example
END_IF;
! (*Error acknowledgement*)
ACK_DEF:= ACK_DEF_Y:= ACQ_DEFAUTS;
%L999:
44
TLX DS 57 PL7 40E 09.2000
Introductory example
Program transfer
Procedure for transferring a program
After having configured your application and input your program, you must transfer them into the PLC processor’s memory, by following the procedure below:
Step
1
2
3
4
Action
Connect the terminal to the PLC using the command AP
→
Connect
Activate the command AP
→
Transfer program.
Select the option Terminal - > PLC.
Confirm the transfer.
TLX DS 57 PL7 40E 09.2000
45
Introductory example
Taking over in manual mode
Accessing manual mode
If you want to move the moving part without first going through the programming phase, use Manual mode. To do that, access the debug screen, in connected mode:
Step
1
2
3
4
Action
Activate the command Tools
→
Configuration.
Select the TSX CFY module to be opened.
Execute the command Services
→
Open the module (or double click on the module to be opened).
The following debug screen is then displayed:
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
Symbol:
Choose axis: Function:
Channel 0 Positioning
Movement: Pulse Speed: Hertz
X
Current
0
Target
0
F
0 0
Position
Speed 0%
STOP
F8
Parameter: [-16 777 216, 16 777 215]
Manu
Auto
Dir
Drive
CH0
Global unforcing
DIAG...
Off
Remainder
0
DONE
-Direction
AT Point
Axis
OK
Referenced
Stopped
Enable
Commands
- JOG
- INC
+ JOG
+ INC
Manual reference point
I/O
Extern Stop
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Reactivate st
Faults
Refuse Cmd
Hardware
Axis
Forced reference point
Brake
Boost Ack.
CONNECT RUN U:SYS
46
TLX DS 57 PL7 40E 09.2000
Movements in manual mode
Introductory example
To move the moving part in Manual mode, you must carry out the following operations:
Step
1
Action
Put the PLC into RUN mode, using the command AP
→
Run or by clicking on the icon
2
3
4
5
6
7
Select the axis to drive: channel 0 (X axis) or channel 1 (Y axis).
Select Manual mode by turning the switch to Manu mode.
Confirm the safety relays of the speed controller by clicking on the button Con-
firmation in the Axis box.
Acknowledge the errors by clicking on the button Ack in the Errors box.
Take a manual origin: l l either by selecting the command Manual reference point, or by selecting the command Forced reference point. In this case, first enter in the Param field, the value of the position of the moving part in relation to the origin.
Move the moving part: l l in the positive direction by using the command JOG+, or in the negative direction by using the command JOG-.
The position of the moving part is displayed in the field X and the speed is displayed in the field F in the Movement / Speed box.
TLX DS 57 PL7 40E 09.2000
47
Introductory example
Debugging
Debugging procedure
You can debug the program by proceeding in the following manner:
Step
1
2
3
Action
Put the PLC into RUN mode.
Display the debugging screen for the TSX CFY module.
Simultaneously display the Grafcet screen in order to follow the evolution of the sequential processing.
The following screen shows the debugging screen and the Grafcet screen together:
4
File File Edit Edit Utilities View Application AP Debug Options Window
GRAFCET: MAST - CHART
STOP
Debugging
0
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
1
(*Start*)
RUN
(*Referenced axes*)
Symbol:
6
Choose axis: Function:
Channel 0
2
Dir
Drive
ERR IO
CH0
Global unforcing
3
Movement: Pulse Speed: Hertz
X
Current
52 282
Target
500 000
F 0 0
(*Detection of edges>>
Remainder
447 718
DONE
-Direction
AT Point
Axis
OK
Referenced
Stopped
Position
Speed 0%
Commands
- JOG
Enable
+ JOG
DIAG...
DIAG...
I/O
Extern Stop
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Reactivate step
Faults
Refuse Cmd
- INC + INC Hardware
Manual reference point
Axis
STOP
F8
Forced reference point
Brake
Boost
Ack.
Parameter: [-16 777 216, 16 777 215] CONNECT RUN U:SYS
Start the program by pressing the Depart_cycle button on the panel.
48
TLX DS 57 PL7 40E 09.2000
Introductory example
Archiving
Storing procedure
When the debugging is finished you must proceed to storage. To do that:
Step
1
2
Action
If parameters have been modified during debugging, activate the command
Services
→
Save parameters.
l l l l
Transfer the application from the PLC processor to the hard disk:
Activate the command AP
→
Transfer program option PLC -> terminal,
Activate the command File
→
Save as, give a name to the application, confirm.
TLX DS 57 PL7 40E 09.2000
49
Introductory example
50
TLX DS 57 PL7 40E 09.2000
Configuring step by step axes control
4
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes the configuration screens in the TSX CFY modules.
This Chapter contains the following Maps:
Topic
Configuring axes control modules
Declaring axes control modules
Accessing the parameters configuration screen
Configuring user units
Configuring the translator’s command mode
Configuring control parameters
Configuring translator inversion
Configuring translator boost
Configuring the step by step motor’s brake
Configuring event tasks
Reference point configuration
Confirmation of configuration parameters
Page
TLX DS 57 PL7 40E 09.2000
51
Configuration
Configuring axes control modules
Introduction
Accessing the configuration editor
Before you create an application program, you must define the context of the physical and software operation in which it will be executed: Type of TSX Premium processor, input/output modules used.
In addition, programming axes control modules necessitates definition of the configuration parameters for the axes used. To do that the PL7 software offers the configuration editor that allows you to carry out these operations easily.
The configuration editor also gives access to the axes adjustment parameters and to the debugging functions in connected mode.
The Application Browser allows you to access the configuration editor. To do that:
Step
1
2
3
Action
Open the Station folder (double click on the icon or click on its attachment).
Open the Configuration folder (double click on the icon or click on its attachment),
Double click on the icon Hardware configuration
Application browser
Structure view
STATION
Configuration
Hardware configuration
Software configuration
Program
Mast task
Events
DFB types
Variables
Animation tables
Documentation file
Runtime screens
4 If the Application Browser window is not present on the screen: l pull down the Tools menu and activate the command Application Brows-
er, l in the toolbar, click on the Application Browser icon:
52
TLX DS 57 PL7 40E 09.2000
Configuration
Declaring axes control modules
Introduction This operation consists in declaring the axes control modules in the PLC configuration.
TLX DS 57 PL7 40E 09.2000
53
Configuration
Adding a module To add an axes control module into the PLC configuration, proceed in the following way:
Step
1
2
Action
Select the rack in which you want to install the axes control module by clicking on the corresponding rack.
In the rack, select and confirm the position in which you want to install the TSX module by clicking on it twice.
The following dialog box allows you to add the module to the configuration:
Add module
Family:
Analog Module 1.5
Communication1.5
Counting 1.5
Remote BusX 1.0
Movement 1.5
Wheighing
Simulation
Discrete
1.5
1.0
1.5
Module:
TSX CAY 21
CAY 33
TSX CAY 41
TSX CAY 42
TSX CFY 11
TSX CFY 21
2 CHAN. AXIS CONT. MOD
MOD.CDE AXE 3
4 CHAN. AXIS CONT. MOD
4 CHAN. AXIS CONT. MOD
1 CH STEPPER MOTOR MOD.
2 CH STEPPER MOTOR MOD.
OK
Cancel
5
6
3
4
Select Movement in the Family field.
Select the reference of the module (TSX CFY) in the Module field.
Confirm with OK.
After confirmation, the module is declared in its position.
Configuration
TSX 57203 XMWI
XTI..
0
2
6
0
0
P
S
Y
0
5
7
2
0
3
T
S
X
2 3
D
E
Y
3
2
D
2
K
4
D
S
Y
3
2
T
2
K
5 6
1
5
5
0
0
P
S
Y
1 2 3
2
1
C
F
Y
4 5 6
2
54
TLX DS 57 PL7 40E 09.2000
Configuration
Deleting a module
To delete a module from its postion: l l l click on it to select it, press the Del key, which displays a dialog box,
Confirm the deletion of the module.
Moving a module To move a module from one position to another: l l l l l click on it to select it, activate the command Edit
Fix the destination position.
You can also:
→
Move a module, select the module using the mouse, without releasing the left mouse button, move the module to its destination position (Drag and Drop).
TLX DS 57 PL7 40E 09.2000
55
Configuration
Accessing the parameters configuration screen
Accessing module parameterization
To access module parameterization, double click on its graphical representation in l l the rack or: select the module (by clicking on it), activate the command Open module from the pull-down menu Services.
Parametering screen
The following screen allows you to parameterize the module:
1
2
3
TSX CFY 21 [RACK1 POSITION 3]
Configuration
Designation: MOD.MOT.PAS A PAS 2 VOIES
Symbol:
Choose Axis: Function:
Channel 0 Positioning
4
Task:
MAST
2
3
4
This screen is made up of 4 areas for information or the selection of parameters.
Area
1
Description
This header is a reminder of the catalog reference of the module and its geographical address in the PLC (rack number and position in the rack).
This command field indicates the current mode: Configuration.
This module level area contains the short title of the module.
This channel level field allows you to select the channel to be configured, the associated function: Position and the task in which the default exchange objects are exchanged: MAST or FAST.
56
TLX DS 57 PL7 40E 09.2000
Configuration
Channel configuration parameters input area
The lower part of the screen gives access to parameter entry.
TSX CFY 21 [RACK1 POSITION 3]
Configuration
Designation: MOD.MOT.PAS A PAS 2 VOIES
Symbol:
Choose Axis: Function:
Channel 0 Positioning
Task:
MAST
Unit
Acceleration ms
Command mode
A = +Pulse/ B = -Pulse
Command parameters
Max. speed
Acc max.
VMax/
18 000
200
Event input
Rising edge
Falling edge
Hertz ms
Drive inversions
Enable output
Input Check
Direction of command
Reference point
Short cam / - Direction
Boost
Automatic control
Inversion
Brake
Automatic control
Inversion
Event
EVT
To display the whole parameter configuration area, activate the commands View
→
Module zone or View
→
Channel field (you can also use these commands to restore these areas).
Note: For each parameter, the limits are displayed in the status bar.
TLX DS 57 PL7 40E 09.2000
57
Configuration
Configuring user units
Introduction
Units pick list
Movements and positions are always expressed in numbers of pulses or increments. Speeds are always expressed in pulses per second (Hertz).
The units pick list is as follows:
Unit
Acceleration Hertz/s
Hertz/s ms
58
TLX DS 57 PL7 40E 09.2000
Description
Configuration
Two selections are possible.
Unit
Hertz/s
Meaning
When this selection is enabled, we will speak of the moving part’s gradient of acceleration and deceleration.
Acceleration in Hertz/s: is equal to the speed gradient, dF/dt
F (Hertz)
F ms
SS_FREQ t(s)
0 t
When this selection is enabled, we will speak of the duration of acceleration and deceleration of the moving part in miliseconds.
Acceleration in ms: is equal to the acceleration time for the speed to go from
SS_FREQ to maximum speed
F (Hertz)
Fmax
SS_FREQ
0 t(ms)
T_ACC
TLX DS 57 PL7 40E 09.2000
59
Configuration
Configuring the translator’s command mode
Introduction The speed setpoint is sent to the translator in order to control the step by step motor.
This menu allows you to determine the manner in which this information is transmitted.
Command mode pick list
The command mode for the translator is as follows:
Command mode
A = +Pulse/ B = -Pulse
A = +Pulse/ B = -Pulse
A = Pulse / B = Direction
60
TLX DS 57 PL7 40E 09.2000
Description
Configuration
Two selections are possible.
Selection
A = + Pulse B = -
Pulse
Meaning
A pulse on A is a movement command (a step) in the positive direction along the axis, a pulse on B is a movement command in the negative direction along the axis.
+ pulse, - pulse mode
Speed
Hertz
SS_FREQ
0
SS_FREQ t
A
+ Pulse t
B
Pulse t
A = Pulse B = Direction In this pulse mode, A is a step movement command, the direction of the movement is indicated by B: l l if B is set to 1 the movement is in the positive direction, if B is set to 0 the movement is in the negative direction.
Pulse / direction mode
Speed
Hertz
SS_FREQ
0
-SS_FREQ t
A
Pulse
B
Direction t t
TLX DS 57 PL7 40E 09.2000
61
Configuration
Configuring control parameters
Introduction The control parameters fields allow you to define the maximum speed and the maximum acceleration of the axes control.
Note: the terms speed and frequency are used interchangeably to characterize the ideas of speed.
Control parameters selection screen
The control parameters selection screen for the translator is as follows:
Command parameters
Max. speed
Acc max. VMax/
Hertz
400 ms
62
TLX DS 57 PL7 40E 09.2000
Description
Configuration
Two fields are to be completed.
Selection
Max. speed
Max. acc.
Meaning
The maximum speed (frequency) depends on the translator – motor – moving part as a whole.
The pulse generation circuit has a resolution of 1024 pulses on the frequency dynamic (zero frequency included).
The selection of a maximum speed has an influence on the frequency resolution of the channel. The following list gives the frequency resolution (Minimum Frequency) for a given max. frequency interval: l l l l l l l
[1 Hz …936 Hz] mini frequency 0.92 Hz
[937 Hz …1873 Hz] mini frequency 1.83 Hz
[1874 Hz …4682 Hz] mini frequency 4.58 Hz
[4683 Hz …9365 Hz] mini frequency 9.16 Hz
[9366 Hz …46829 Hz] mini frequence 45.78 Hz
[46830 Hz …93658 Hz] mini frequence 91.55 Hz
[93659 Hz … 187316 Hz] mini frequency 183.11 Hz
Example: for a max. frequency of 20 KHz, the resolution (Min. Frequency) is 45.78 Hz.
The effective acceleration of the axis that is defined in adjustment, must always be less than or equal to the maximum acceleration defined in the configuration.
The TSX CFY 11 and 21 modules are capable of modifying the rate of acceleration or deceleration every 5 ms. The dynamic resolution is 63 point, which means that when the selected unit of acceleration is the Hertz/s, in a given interval of maximum speed the acceleration can be between 1 and 63 times the minimum acceleration. The following list gives the authorized minimum accelerations for a given speed interval: l l l l l l l
[1 Hz …936 Hz] minimum acceleration 183 Hz/s
[937 Hz …1873 Hz] minimum acceleration 366 Hz/s
[1874 Hz …4682 Hz] minimum acceleration 916 Hz/s
[4683 Hz,9365 Hz] minimum acceleration 1831 Hz/s
[9366 Hz,46829 Hz] minimum acceleration 9155 Hz/s
[46830 Hz …93658 Hz] minimum acceleration 18311 Hz/s
[93659 Hz …187316 Hz] minimum acceleration 36621 Hz/s
When acceleration is given in ms, the maximum acceleration corresponds to the minimum time taken to reach maximum speed when accelerating from the start stop frequency (SS_FREQ).
TLX DS 57 PL7 40E 09.2000
63
Configuration
Configuring translator inversion
Introduction
Configuration screen for translator inversions
The translator is controlled by the channel of the TSX CFY 11 or 21 module. It is possible to configure the logic state of the translator enable output and the translator
monitor input as well as the movement direction of the control of the signals A and B.
The configuration screen for translator inversions is as follows:
Drive inversions
Enable output
Input Check
Command direction
Description Three selections are envisaged.
Field
Enable Output
Input Monitoring
Command direction
Meaning
For translators having input validation, when this box is not selected, output validation is set to 1, when the translator is enabled. If not, it is set to 0.
For translators having input disabling, when this box is selected, output validation is set to 0, when the translator is enabled. If not, it is set to 1.
When this box is not selected, when the input monitor is set to 1, the translator is unavailable. If not, it is available (configuration case for Phytron MSD/SD translator)
When this box is selected, when the input monitor is set to 1, the translator is available. If not, it is unavailable.
When this case is not selected, the direction of the signals A and B is that specified in the section Configuring the command mode (See Configuring the trans-
lator’s command mode, p. 60 ).
When this box is selected, the logic of the command is inverted. The selection
A=+ Pulse / B=-Pulse becomes A=-Pulse / B=+ Pulse and the selection
A=Pulse / B=Direction is such that B set to 1 commands a negative direction along the axis and B set to 0 commands a positive direction along the axis.
64
TLX DS 57 PL7 40E 09.2000
Configuration
Configuring translator boost
Introduction
Boost configuration screen
Description
Some translators have a boost input that can be configured on the TSX CFY 11 and
21s.
The configuration screen for translator boost is as follows:
Boost
Automatic control
Inversion
Two selections are conceivable.
Field
Automatic control
Inversion
Meaning
For translators having a boost input, when this box is not checked, the translator boost is controlled by the object %Qxy.i.14 BOOST (See Application-spe-
cific step by step axes control language objects, p. 173 ). WARNING: the
BOOST command remains active in automatic control mode, if the Automatic control option is checked, it is important to refrain from using this command in order to avoid any conflicts.
For translators having a boost input, when this box is checked, the translator boost is automatically activated in the acceleration or deceleration phase of the moving part.
When this box is not selected, the translator boost is active when the boost output is set to 1.
When this box is selected, the translator boost is active when the boost output is set to 0.
TLX DS 57 PL7 40E 09.2000
65
Configuration
Configuring the step by step motor’s brake
Introduction
Brake configuration screen
Description
Within the context of load carrying applications, it is possible to use a brake on the step by step motor.
The brake configuration screen is as follows.
Brake
Automatic control
Inversion
Two selections are conceivable.
Field
Automatic control
Inversion
Meaning
When this box is not selected, the brake is controlled by the object %Qxy.i.13
BRAKE (See Application-specific step by step axes control language objects,
p. 173 ). WARNING: the BRAKE command remains active in automatic control
mode, if the Automatic control option is checked, it is important to refrain from using this command in order to avoid any conflicts.
When this box is checked, the control of the step by step motor’s brake is automatically activated when the moving part is stopped and deactivated when it starts.
When this box is not selected, the brake output is set to 0 when the brake command is active, if not it is set to 1 (24V) in order to deactivate the brake.
When this box is selected, the brake output is set to 1 when the brake command is active, if not it is set to 0.
66
TLX DS 57 PL7 40E 09.2000
Configuration
Configuring event tasks
Introduction
Event configuration screen
Description
When you want to carry out a complementary process that uses the reflex entry, it is necessary to configure an event task associated to the axes control channel.
The configuration screen for the event task is as follows:
Event
EVT
2
Two fields are to be completed.
Field
Evt
Task number
Meaning
When this box is selected, this signifies that you want to associate an event task to the axes control channel.
This number indicates the number of the event task that will be attached to the axes control channel. This number is from 0 to 31 for the TSX 57-1• and from
0 to 63 for the TSX 57-2••, TSX 57-3•• and TSX 57-4••.
TLX DS 57 PL7 40E 09.2000
67
Configuration
Reference point configuration
Introduction So that a movement can be turned into a position, it is necessary to assign a known dimension (generally selected as equal to 0) to a particular point on the axis. This operation is called setting the origin or reference point. An axis on which a reference point has been set is known as "referenced".
Illustration of the
Reference point field
The reference point pick list is as follows.
Reference point
Short cam / + Direction
Short cam / + Direction
Short cam / - Direction
Short cam / + Direction
Short cam / - Direction
On limit stop / + Direction
Description The Reference point field defines the type and the direction of the reference point.
The types short cam and long cam are linked to the installation of a reference point sensor on the cam reference point input. The types end of run limit assume an installation of end of run detectors.
Possibilities Icon
Short cam, + direction
Approach speed (1)
F
Reference
Point Speed
F (2)
Short cam, - direction
Long cam, + direction
F
F
SS_FREQ (2)
SS_FREQ (2)
68
TLX DS 57 PL7 40E 09.2000
Possibilities
Long cam, - direction
End of run limit, + direction
End of run limit, - direction
Approach speed (1)
F
Configuration
Reference
Point Speed
SS_FREQ
Icon
(2)
F SS_FREQ (2)
F SS_FREQ (2)
(1) F is the speed programmed in the instruction in automatic mode or the speed
FMANU (defined in the adjustment screen) in manual mode. This speed can be modulated by the CMV coefficient.
(2) The icon illustrates the reference point.
Reference point command
The reference point command is carried out: l l in automatic mode, using instruction code 14: set reference point, in manual mode, using the command SET_RP: set manual reference point.
If SS_FREQ is zero, and if the reference point speed is SS_FREQ, then the actual reference point speed is the smallest that the module can generate in the selected range.
Note: SS_FREQ = the start stop frequency.
Forced reference point
There is also a forced reference point mechanism: l l command G62 in Auto mode, command RP_HERE in Manu mode.
This setting of the reference point consists in forcing the position to a specified value. This operation does not entail any movement and therefore does not take account of the type of RP selected.
TLX DS 57 PL7 40E 09.2000
69
Configuration
Reference point short cam
The following table gives a detailed description of reference points short cam
Type
Direction
Icon
Short cam
+ Direction - Direction
Movement
Cam
Reference point long cam
The following table gives a detailed description of reference points long cam
Type
Direction
Long cam
+ Direction, start away from the cam
- Direction, start away from the cam
Icon
Movement
Cam
70
TLX DS 57 PL7 40E 09.2000
Type
Direction
Icon
Configuration
Long cam
+ Direction, start towards the cam
- Direction, start towards the cam
Movement
Cam
Reference point end of run limit
The following table gives a detailed description of reference points end of run limit
Type
Direction
End of run limit
+ Direction, start away from the cam
- Direction, start away from the cam
Icon
Movement
Cam
TLX DS 57 PL7 40E 09.2000
71
Configuration
Type
Direction
Icon
End of run limit
+ Direction, start towards the cam
- Direction, start towards the cam
Movement
Cam
72
TLX DS 57 PL7 40E 09.2000
Configuration
Confirmation of configuration parameters
Introduction When you have defined all the configuration parameters, you must confirm your configuration using the command Edit
→
Confirm or by activating the associated icon:
Incorrect configuration parameters
If one or several parameter values are not within the authorized limits, an error message is displayed to indicate the faulty parameter.
For example, the value of maximum speed is invalid:
Validate
S T O P
Cannot validate!
Error in adjustment parameters:
Stop and start speed out of range.
OK
You must correct the faulty parameters to make the confirmation of your configuration possible.
Note: In the configuration screens, the faulty parameters appear in red. The grayed out parameters cannot be modified because they are dependent upon the faulty parameters.
TLX DS 57 PL7 40E 09.2000
73
Configuration
Incorrect adjustment parameters
When you confirm your configuration for the first time, the adjustment parameters are initialized. If, following modifications to the configuration value, the adjustment parameters are no longer correct, an error message is displayed to indicate the offending parameter.
For example, the speeds are outside limits:
Validate
S T O P
Cannot validate!
Error in configuration parameters:
Maximum speed out of range.
OK
Recognition of confirmation
You must access the adjustment screen, correct the faulty parameter then confirm.
l l l
Your configuration is effectively recognized: when all the configuration parameters are correct, when all the adjustment parameters are correct, when you have confirmed at the level of the standard screen of the configuration editor.
74
TLX DS 57 PL7 40E 09.2000
Programming step by step axes control
5
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes the programming principles for the different operating modes: it describes the principal instructions and the operating modes.
This Chapter contains the following Maps:
Topic
Principles of programming a step by step axis
Operating modes
Programming the SMOVE function (in automatic mode)
Inputting SMOVE function parameters
Description of the SMOVE function parameters
Instruction codes for the SMOVE function
Description of basic movements with the SMOVE function
Description of SMOVE instruction codes
Example of using an indexed position (repetitive movements)
Movement command sequencing
Deferred PAUSE function
Immediate PAUSE function
Event processing
Managing operating modes
Managing errors
Description of external hardware faults
Description of application errors
Description of the command refused errors
Management of manual mode
Visual movement commands
Page
TLX DS 57 PL7 40E 09.2000
75
Programming
Topic
Incremental movement commands
Reference point command
Forced reference point command
Management of direct mode (DIRDRIVE)
Management of stop mode (OFF)
Page
76
TLX DS 57 PL7 40E 09.2000
Programming
Principles of programming a step by step axis
Introduction
Bit objects and words l l
Each channel (axis) of the axes control module is programmed using: the SMOVE function for movements in automatic mode, the bit objects (%I and %Q) and words (%IW, %QW and %MW), (See Applica-
tion-specific step by step axes control language objects, p. 173 associated with
the module to define: l the selection of operating modes, l l the control of movements, except for automatic mode, the monitoring of the operating status of the axis and the module.
The bit objects and words can be retrieved using their address or their symbol. The symbols are defined in the variables editor which offers as a default a symbol name for each of the objects.
TLX DS 57 PL7 40E 09.2000
77
Programming
Operating modes
Introduction You can use each axes control channel in 4 operating modes:
Operating mode
Automatic (AUTO)
Manual (MANU)
Direct (DIRDRIVE)
Stop (OFF)
Description
This mode supports the execution of movement commands driven by the SMOVE functions.
This mode supports the visual driving of the moving part, from a panel or from an operator dialog desk. The commands are enabled via output bits %Q.
In this mode the output behaves like a digital / frequency convertor. This mode controls the movement according to the movement setpoint indicated in the variable PARAM.
In this mode the channel does not monitor the moving part; it only reports on current position and speed.
This mode is forced at start up, if the axis is configured and error free.
Selecting the mode
The mode selection is carried out by means of the word MODE_SEL (%Qwxy.i.0)
The following table indicates the selected mode, according to the value of the word
%QWxy.i.0:
1
2
Value
0
3
Selected mode
OFF
DIRDRIVE
MANU
AUTO
Description
Switching to stopped movement
Order to move in direct mode.
Order to move in manual mode.
Order to move in automatic mode.
For any other value of %QWxy.i.0, OFF mode is selected.
Changing mode during a movement
Changing operating mode while a movement is in progress (DONE bit: %Ixy.i.1 set to 1) makes the moving part stop. When the moving part is effectively stopped (NO-
MOTION bit: %Ixy.i.8 set to 1), the new operating mode is then activated.
Note: Only the commands concerning the current mode are examined. The other commands are ignored: for example, the channel being in MANU mode (IN_MANU equals 1), if the DIRDRV command is activated, it is ignored. It is first necessary to switch into DIRDRIVE mode.
78
TLX DS 57 PL7 40E 09.2000
Programming
Programming the SMOVE function (in automatic mode)
Introduction
Assisted input screen
You can program an SMOVE function in any programming module in ladder language (by means of an operation block), in instruction list language (between square brackets) or in structured text language. In all cases the syntax remains the same.
You can input the SMOVE function directly or via the assisted input screen.: Func-
tion call:
Function call
Function information: Parameters
Family
Character strings
Movement Cmd
Communication
Digital conversions
V.Bib
V.App
1.1
-
1.0
-
1.6
-
1.1
-
Call format
METHOD parameter:
Name Type Nature
Channel MAIN Channel
NRUN WORD IN
G9_ WORD IN
Name
SMOVE
Comment
Movement number
G9
Comment
Automatic movement command
Entry field
Call display
SMOVE ( )
OK Cancel Detail...
Assisted input In the editor of the selected program, proceed in the following way:
Step
1
4
5
2
3
6
Action
Press keys Shift and F8 at the same time or click on the icon F(…). The window Function call is then displayed.
Select the option Parameters.
Select the family Movement command in the library.
Select the function SMOVE.
Press the Details button and complete the different fields offered (See Input-
ting SMOVE function parameters, p. 80
). You can also enter the function variables directly into the parameter input area.
Confirm using OK or Enter. The function is then displayed.
TLX DS 57 PL7 40E 09.2000
79
Programming
Inputting SMOVE function parameters
Introduction
Details screen for the SMOVE function
A movement command is programmed via a SMOVE function, with the following syntax:
SMOVE %CHxy.i(N_Run,G9_,G,X,F,M)
The Details screen allows you to enter each of the parameters with help.
The Details screen for the SMOVE function is as follows:
F x
G01
G14
G09
G62
+
+
++
0.0
G11
G07
1 2 3
G10
G05
SMOVE
Channel address
N_Run 1 Cancel
Movement codes
Movement number
G9_ Cancel
G
X Position increment
F 500 Cancel
Parameters M
Z
Movement speed
Digital auxillary outputs
Evt source Unchanged
Synchronous with mvt
Consecutive with mvt
AUX 0
OK Cancel
The entry fields (parameters for the SMOVE function) are as follows:
G
X
F
M
Parameter
%CHxy.i
N_Run
G9_
Description
Channel address.
Movement number.
Movement type.
Instruction code.
Coordinate of the position to be reached.
Speed of movement of the moving part.
Event processing, auxiliary discrete outputs associated with the channel.
80
TLX DS 57 PL7 40E 09.2000
Programming
Description of the SMOVE function parameters
Introduction You must enter the following parameters in order to program a movement function:
SMOVE %CHxy.i(N_Run,G9_,G,X,F,M)
Channel address %CHxy.i defines the channel address of the axes control module in the PLC configuration: i y
Parameter x
Meaning
Rack number.
Position of the module in the rack.
Channel number.
l l
0 for a TSX CFY 11 module,
0 and 1 for a TSX CFY 21 module,
Movement number
Movement type
N_Run defines the movement number (between 0 and 32767). This number identifies the movement carried out by the SMOVE function.
In debugging mode, this number tells you which movement is in progress.
G9_ defines the movement type:
Code
90
91
98
Movement type.
Absolute movement.
Movement relative to the current position.
Movement relative to the stored PREF1 position. The storing of the
PREF1 position is achieved using the instruction code G07.
To select the movement type use the browse button situated to the right of the G9_ field or enter the code directly when inputting directly (without going to the Details screen).
Instruction code G defines the instruction code (See
Instruction codes for the SMOVE function, p. 83)
for the SMOVE function
TLX DS 57 PL7 40E 09.2000
81
Programming
Coordinate of the position to be reached
X defines the coordinate of the position to be reached or towards which the moving l l part must move (in the case of a continuous movement).This position can be: immediate, coded in a double internal word %MDi or internal constant %KDi (this word can be indexed).
This value is expressed in the unit defined by the configuration parameter Length
Units (e.g. micron).
Note: In the case of instruction G14, G21 and G62 this parameter represents the value of the reference point.
Speed of movement of the moving part
F defines the speed of movement of the moving part. This speed can be: l l immediate, coded in a double internal word %MDi or internal constant %KDi (this word can be indexed).
The unit of speed is Hertz.
Note: The speed can be modulated in the course of the movement by means of the CMV (coefficient of speed modulation). Actual F = programmed F x CMV/
1000. This parameter initialized by default at 1000 can be inbetween [0…2000], the resulting speed must always be more than SS_FREQ. The value 0 signifies the moving part has been stopped.
Parameter M M defines a word which is coded in 4-bit bytes (in hexadecimal): l the activation or non activation of the trigger for application event processing, for instructions G10, G11, G05 and G07: l M = 16#1000: activation of the associated event task, l M = 16#0000: non activation of the event task when the SMOVE command is executed.
For example:
Byte 3 2 1 0
16#
Note: Coding is automatically realized in the M field in the Details screen, when you make selections using the check boxes and buttons offered by this screen.
82
TLX DS 57 PL7 40E 09.2000
Programming
Instruction codes for the SMOVE function
Introduction
List of instruction codes
The G defines the instruction code.
To select the instruction code you can use the browse button situated to the right of the G field, click on the icon corresponding to the movement or enter the code directly when inputting directly (without going to the Details screen ).
The instruction codes that you can select in the Details screen are as follows:
Instruction code
09
Meaning
Movement to position with stop.
Icon
01 Continuous movement to position.
14
62
05
07
10
11
Movement to event with stop.
Continuous movement to event.
Reference point.
Forced reference point.
Await event.
Storage of position on event.
TLX DS 57 PL7 40E 09.2000
83
Programming
Details screen gaphics
The Details screen also display a graphic which represents the selected movement.
For example, code G09:
84
TLX DS 57 PL7 40E 09.2000
Programming
Description of basic movements with the SMOVE function
Introduction
Absolute movement in relation to the machine origin
Some instructions of the SMOVE function allow you to carry out basic movements.
When programming these movements, the user defines the position to be reached and the speed. The acceleration parameter (constant, trapezoidal law of speed) is l l l defined by this adjustable parameter.
The movements can be: absolute in relation to the machine origin 90 relative in relation to the current position 91 relative in relation to the stored position PREF 98
Example of an absolute movement in relation to the machine origin 90.
Example: SMOVE %CH102.0 (1,90,01,50000,1000,0)
Speed
(Hertz)
1000
SS_FREQ
0
50000 position
(pulses)
TLX DS 57 PL7 40E 09.2000
85
Programming
Relative movement in relation to the current position
Example of a relative movement in relation to the current position 91.
Example: SMOVE %CH102.0 (1,91,01,40000,1000,0)
Speed
(Hertz)
1000
SS_FREQ
0
X X+40000 position
(pulses)
Relative movement in relation to the stored position
Example of a relative movement in relation to the stored position PREF 98.
Example: SMOVE %CH102.0 (1,98,01,30000,1000,0)
Speed
(Hertz)
1000
SS_FREQ
0
PREF PREF+30000 position
(pulses)
86
TLX DS 57 PL7 40E 09.2000
Programming
Description of SMOVE instruction codes
Introduction Three classes of movement can be programmed: l l l movements to a position (instruction codes 01 and 09) movements until the detection of an event (instruction codes 11 and 10) taking of reference point (instruction 14)
To find out about the execution conditions for instructions, see Diagnostics and
Continuous movements to a position
Example of a continuous movement to a position: instruction code 01.
Example: SMOVE %CH102.0 (1,90,01,50000,1000,0)
Speed
(Hertz)
1000
SS_FREQ
0
50000 position
(pulses)
Note: If the instruction 01 is not followed by any movement instruction, the moving part continues the movement until it reaches the soft stops (after passing the position to be reached, the coefficient of speed modulation CMV is no longer interpreted).
TLX DS 57 PL7 40E 09.2000
87
Programming
Movements to a position with stop
Example of a movement to a position with stop: instruction code 09.
Example: SMOVE %CH102.0 (1,90,09,50000,1000,0)
Speed
(Hertz)
1000
SS_FREQ
0 50000 position
(pulses)
Continuous movement until an event
Example of a continuous movement until an event: instruction code 11.
Example: SMOVE %CH102.0 (1,90,11,500000,3000,0)
Speed
(Hertz)
3000 event
SS_FREQ
0
50000 position
(pulses)
Note: The event can be a rising or falling edge on the dedicated cam event input or rising edge on the EXT_EVT bit (%Qxy.I.11) by program.
The position parameter must obligatorily be defined. If the event is not detected, the instruction is terminated when the requested target position is reached.
These instructions 11 and 12 can activate the event task when the event is detected if M is equal to 16#1000.
88
TLX DS 57 PL7 40E 09.2000
Movement until an event with stop
Example of a movement until an event with stop: instruction code 10.
Example: SMOVE %CH102.0 (1,90,10,500000,2000,0)
Speed
(Hertz)
2000 event
Programming
Set reference point
SS_FREQ
0
50000 position
(pulses)
Example of setting reference point: instruction code 14. Reference point configured towards short cam in the + direction. At the start, the moving part is outside the cam.
Example: SMOVE %CH102.0 (1,90,10,500000,2000,0)
Speed
(Hertz)
2000
Reference point
SS_FREQ
0 position
(pulses)
50000
Note: This instruction triggers a reference point sequence according to the selection made in configuration. The value provided in the X parameter corresponds to the coordinate to be loaded with the current value when the point is detected.
TLX DS 57 PL7 40E 09.2000
89
Programming
Example of setting reference point: instruction code 14. Reference point configured towards long cam in the + direction. At the start, the moving part is on the cam.
Example: SMOVE %CH102.0 (1,90,14,500000,2000,0)
Reference point Speed (Hertz)
SS_FREQ 5000000
Position (pulses)
SS_FREQ
2000
Note: this command is only accepted if the moving part is at rest: NOMOTION bit
= 1 (%Ixy.i.7 = 1).
Forced reference point
This command carries out the taking of a forced reference point (without moving the moving part). The instruction code is 62. The current position value is forced to the value entered in the parameter position X.
Example: SMOVE %CH102.0 (1, 90, 62, 100000, 100, 0) .
When this instruction is executed, the position of the moving part is forced to
100000.
Note: regardless of the status of the axis, referenced or not, this command is accepted and it has the action of referencing the axis when the execution is completed. This command is only accepted if the moving part is at rest, NOMOTION bit =
1 (%Ixy.i.7=1).
90
TLX DS 57 PL7 40E 09.2000
Await event
Programming
This command, instruction code 05, makes the channel wait for an event which can be: l a change of state of the trigger input (rising or falling edge according to the selection made at configuration), l a rising edge for the EVT_EXT bit (%Qxy.11)
In the context of this instruction, the F parameter specifies the time envelope with a resolution of 10 ms. If the event is not triggered at the end of the time envelope, the command is deactivated. If F = 0, the wait carries on indefinitely.
Example: SMOVE %CH102.0 (1, 90, 05, 500, 100, 0) .
It is possible to associate event processing (See
Event processing, p. 101), to do
that you must program M to 16#1000.
Note: when executing this instruction, the object %MDxy.i.10 (T_SPEED speed to be reached) does not contain the parameter F for the wait time. On the other hand it is advised to systematically associate an event process to this command as the bit TO_G05 (%Ixy.i.39), which allows the application to distinguish whether the command is terminated by detecting an event or by the passing of the time envelope, is only refreshed if this process is activated.
Storage of the current position on event.
After the execution of this instruction, code 07, when the trigger input is entered the event defined in configuration is produced and the current position is stored in the
PREF register.
Note: the parameter of position X must be equal to 1.
Example: SMOVE %CH102.0 (1, 90, 07, 1, 0, 0) .
TLX DS 57 PL7 40E 09.2000
91
Programming
Descriptive table for storing the current position on event.
Type of event on event input
Timing diagram
Rising edge
Falling edge
Position
Behavior
PREF
Configuration selection t
Note: this instruction is not blocking, the program carries on straightaway to the next instruction. The stored value of the current position can be accessed in the register PREF (%IDxy.i.7) only if activation of event processing is requested
(M=16#10000).
Note: when executing this instruction, the object %MDxy.i.8 (T_XPOS, target position to be reached) does not contain the parameter X=1.
92
TLX DS 57 PL7 40E 09.2000
Programming
Example of using an indexed position (repetitive movements)
Introduction
Illustration
We want to carry out the sequence of the following basic movements 9 times: l l l l movement A until the detection of the edge of part 1, movement B as far as position 2 = +20000 in relation to the edge of part 1, movement C as far as position 3 = +10000 in relation to the edge of part 1, movement D as far as the edge of part 1.
In this example, the reference point is assumed taken and the moving part is at the reference point.
Position diagram.
Speed
(Hertz)
500 event
A
SS_FREQ
1
0
DSS_FREQ
D
B
3
C
2 event event
8000000
REFP REFP REFP
Note: the sequence of basic movements is represented in bold on the curve. The numbers given correspond to the program step numbers included in the SMOVE function.
TLX DS 57 PL7 40E 09.2000
93
Programming
Description of the program
Grafcet for the operation of repetitive movements.
0
!%MW0:=0;%QW2.0:=3 (*%QW2.0:MOD_SEL:=AUTO*)
1
!RE %I1.0 AND %I2.0.3 AND %I2.0.19 (*I2.0.3:AX_OK
%I2.0.19:IN_AUTO*)
!SMOVE %CH2.0(1,90,7,1,0,0);INC %MW0;
2
!%I2.0 (*I2.0.0:NEXT*)
!SMOVE %CH2.0(2,90,11,800000,500,0)
3
!%I2.0
!SMOVE %CH2.0(2,98,09,20000,500,0)
4
!%I2.0
!SMOVE %CH2.0(4,98,09,10000,100,0)
5
!%I2.0
!SMOVE %CH2.0(5,98,09,0,100,0)
!%I2.0 AND (%MW0<=10)
Note: all the actions must be programmed on activation.
94
TLX DS 57 PL7 40E 09.2000
Programming
Movement command sequencing
Creating a trajectory
Memory buffer
The creation of a trajectory is carried out by programming a series of basic movement instructions (SMOVE function).
Each basic command to execute an SMOVE function must only be done once. You must program the execution either: l in Grafcet: in a step programmed for activation or deactivation, l in structured text or Ladder language, in one bit rising edge.
The report on the execution of the function is supplied by the module, via the bits
NEXT and DONE.
The TSX CFY module has a mechanism that supports the sequencing of movement commands.
Each axis of the TSX CFY module includes a memory buffer that allows it to receive
2 movement commands, in addition to that, which it is executing. Thus, after finishing executing the current command, it carries on immediately to the first command present in the buffer memory.
Command sequencing:
SMOVE
SMOVE %CH102.0 (01,90,01,...)
SMOVE %CH102.0 (02,90,09,...)
SMOVE %CH102.0 (03,90,09,...)
NEXT
Sequencing between 2 commands
The sequencing between 2 movement commands is carried out in the following way: l l instantaneously if the first movement is continuous, as soon as the moving part has stopped, if the first movement is with stop.
For sequencing to be instantaneous, the execution time of the instruction in progress must be greater than the period of the master task.
Note: A new command must only be transmitted to the module if the memory buffer associated with the axis to be controlled is not full.
TLX DS 57 PL7 40E 09.2000
95
Programming
Bits associated with the sequencing mechanism
The bits associated with the sequencing mechanism are as follows:
Addressing
NEXT (%Ixy.i.0)
DONE (%Ixy.i.1)
AT_PNT (%Ixy.i.8)
Description
Indicates to the program user that the module is ready to receive the next movement command.
Indicates the end of the execution of the current command and the absence of a new command in the memory buffer.
Signals that the moving part has reached the point aimed for: l l for a continuous movement, remains at 0, for a movement with stop, is equivalent to NOMOTION.
Example
Note: The program must always test either the NEXT bit or the DONE bit before executing an SMOVE command.
The following diagram represents the timing diagram of a sequence:
F
SS FREQ
SMOVE%CH2(1,90,01 L
SMOVE%CH2(2,90,09,..; L
SMOVE%CH2(3,90,09,..;
L
WAIT
WAIT
SMOVE%CH2(4,90,09,..;
SMOVE%CH2(5,90,11,..;
L
WAIT
WAIT WAIT t (s)
L
NEXT
DONE
AT PNT
S = Start
For a movement with stop: DONE switches to 1 when NOMOTION switches to 1 and when the memory buffer is available.
For a continuous movement: DONE switches to 1 when the target position is overshot and when the buffer memory is empty.
96
TLX DS 57 PL7 40E 09.2000
Programming
Deferred PAUSE function
Introduction The command PAUSE (%Qxy.i.16) allows you to suspend the sequence of movements. It only becomes active when the moving part is stopped, that is, at the end of a G09 or G10 instruction.
The next movement starts as soon as the PAUSE command is reset to 0.
The bit ON_PAUSE (%Ixy.i.26) signals when it is set to 1 that the axis is in a PAUSE l l state.
This function has 2 possible uses: the block by block execution of the movement program, synchronization of the axes by the same step by step axes control module.
Block by block execution of the movement program
If the current instruction is an instruction with stop, the activation of the command
PAUSE in the debugging screen in automatic mode or setting the PAUSE bit
(%Qxy.i.16) to 1 causes, after the end of the execution of the current instruction, the switch to wait mode: the stopping of the movement sequencing.
It is thus possible by successively activating and deactivating the PAUSE command to execute the movements block by block with the aim of facilitating the debugging.
Synchronization of several axes
For each axis, the setting of the PAUSE bit (%Qxy.i.12) to 1 by the program causes, after the end of the execution of the current instruction, the switch to wait mode.
When the PAUSE bit is reset to 0, the module continues the execution of the instructions.
TLX DS 57 PL7 40E 09.2000
97
Programming
Example The execution of the movement of the moving part 1 is stopped when moving part 0 reaches position 100000. The movement is activated again when the moving part 0 reaches dimension 500000.
IF (%ID2.1 >= 100000) THEN SET %Q2.1.12;
...............................
IF (%ID2.1 >= 500000) THEN RESET %Q2.1.12;
Speed (Hertz)
100000 500000
SS_FREQ
Moving part 0
PAUSE bit
Position
(pulses)
Time
SS_FREQ
Moving part 1
0
Time
Note: The PAUSE command is only processed when AUTO mode is active.
98
TLX DS 57 PL7 40E 09.2000
Programming
Immediate PAUSE function
Introduction
Activating the function
This function allows you, in automatic mode, to cause the moving part to stop, while assuring, at the time of the command to restart the movement, the continuation of the programmed trajectory (with no risk of commands being refused).
The immediate PAUSE function is activated by assigning the value 0 to the word
CMV (%QWxy.i.1), the coefficient of speed modulation.
It makes the moving part stop in accordance with the programmed deceleration.
The status report on the pause is signaled by the bit IM_PAUSE (%Ixy.i.34).
Deactivating the function
The immediate PAUSE function is deactivated by reassigning the initial value (> 0) to the word CMV, the coefficient of speed modulation.
It causes the interrupted movement to restart at the speed corresponding to:
F x CMV / 1000.
Example Activation / deactivation of the immediate PAUSE function:
SMOVE %CH2.0 (1,90,10,5000000,1000,0);
SMOVE %CH2.0 (2,90,09,7500000,500,0);
...............................
IF RE %M10 THEN %MW100:= %QWxy.i.1; %QWxy.i.1:= 0;
IF RE %M10 THEN %QWxy.i.1:= %MW100;
Speed (mm / min)
1000
500
SS_FREQ
SMC
0
1000
0
5000000 7500000 Position
Position
Note: Upon a STOP order or a blocking error, this command is deactivated.
TLX DS 57 PL7 40E 09.2000
99
Programming
Note: when the aimed for position is overstepped when there is a stop following an immediate pause command, the current movement is considered terminated. In this case the trajectory restarts with the movement which was waiting in the memory buffer.
100
TLX DS 57 PL7 40E 09.2000
Programming
Event processing
Introduction
Activating an event task
The channels of the TSX CFY modules can activate an event task. To do that you must have enabled the functionality in the configuration screen, by associating a event processing number to the channel (See
Configuring event tasks, p. 67).
The following instructions set off the sending of an event that activates the event task: l Movement until an event, codes 10 and 11: the event processing application is activated, when the event is detected.
l Await event, code 05: the event processing application is activated, at the end of l the instruction.
Storing the current position when the event appears, code 07: the event processing application is activated at the end of storing the position PREF.
The event processing application is activated, if bit 12 in the M parameter of the
SMOVE function associated to the instruction is set to 1 (M equals 16#1000).
Variables which can be used by the event task l l l
If several event sources are selected, the following bits allow you to determine the source of the trigger of the event processing application: l l
EVT_G1X (%Ixy.i.40): end of G10 or G11 on event,
EVT_G05 (%Ixy.i.38): end of G05 on event, l l
TO_G05 (%Ixy.i.39): G05 timing elapsed,
EVT_G07 (%Ixy.i.37): storage of position,
The OVR_EVT bit (%Ixy.i.36) allows you to detect a delay in the sending of the event or a loss of event.
Value of the stored position PREF (%IDxy.i.7).
Note: The bits and the words described above are the only values refreshed in the event task and they are only updated into the PLC when the task is activated.
Masking events PL7 language offers 2 methods of masking events: l Instruction for the global masking of events: MASKEVT() (the instruction UN-
MASKEVT() allows unmasking). l Bit %S38 = 0 (global disabling of events). The %S38 bit is normally set to 1.
TLX DS 57 PL7 40E 09.2000
101
Programming
Summary diagram:
TSX CFY
G05
Event task
EVTi
M
M
G07
M
G10/G11
UNMASKEVT
MASKEVT
Processor
%S38
EVTi event task
102
TLX DS 57 PL7 40E 09.2000
Programming
Managing operating modes
Powering up the module
When powering up the module or when plugging it in, the TSX CFY module carries out auto-tests with the outputs in safety position (outputs at 0).
At the end of the auto-tests:
If the auto-tests … have not detected any errors.
have detected an error or the configuration is incorrect.
Then the module … tests the configuration with the outputs in safety position.
If the configuration is correct, the module switches to disabled mode (OFF).
signals an error and retains the outputs in safety position.
PLC in RUN mode
All the operating modes of the configured channels are usable.
Switching the
PLC from RUN to
STOP mode
When switching the PLC from RUN mode to STOP mode or when there is a loss of communication between the processor and the module, the moving part decelerates and stops and the module switches to STOP mode (OFF).
Note: The bit %S13 allows you to detect the PLC switching to STOP mode. It is set to 1 during the first cycle after the PLC switches to RUN mode.
Changing configuration
(reconfiguration) l l l l l
The moving part decelerates and stops.
The channel becomes unconfigured.
The channel tests the new configuration with the outputs in safety position.
If the new configuration is correct, the channel switches to STOP mode (OFF).
If the configuration is incorrect, the module signals an error and retains the outputs in safety position.
Power outage and return
When there is a power outage, the moving part stops.
At the time of a cold start or a warm restart, the configuration of the channels is automatically transmitted by the processor to the module The latter switches into
STOP mode (OFF).
TLX DS 57 PL7 40E 09.2000
103
Programming
Managing errors
Introduction
Error types
The monitoring of errors is essential in the area of position control because of the inherent risks with moving parts.
The checks are carried out internally and automatically by the module.
The module detects 4 types of errors: l Module errors. These are the hardware faults internal to the module, all the axes driven by the module are thus affected by the appearance of this type of error.
They can be detected in the course of the auto-tests (when reinitializing the module) or in the course of normal operation (I/O error).
l Hardware channel faults external to the module (for example, brake output short-circuit). l Application channel errors linked to the axes (for example, crossing outside soft stop).
The monitoring of errors at axis level is permanently active when the axis is configured.
l Commands refused channel errors. These are the errors which can appear when executing a movement, configuration transfer, adjustment parameters transfer or change of operating modes command.
Note: The monitoring of some errors at the axis level can be enabled or disabled by the axes control parameters. These control parameters can be adjusted in the adjustment screen.
In STOP mode (OFF), the monitoring of application errors is disabled
104
TLX DS 57 PL7 40E 09.2000
Programming
Levels of gravity The errors are classed into 2 levels of gravity: l Critical or blocking errors which cause the moving part in the case of an axis error or the moving parts managed by the module in the case of a module error l l to stop. They cause the following processes: l signaling of the error, deceleration of the moving part until it stops, disabling of the translator, activation of the brake, l clearing of all the stored commands, l the wait for an acknowledgement.
The error must have gone and been acknowledged for you to be able to restart the application.
l Non critical errors which cause a signaling of the error without stopping the moving part. You must program in PL7 the action to be taken with this type of error.
The error message disappears when the error has gone and has been acknowledged (the acknowledgement is not stored and is only effective if the error has gone).
Note: in the case of opening emergency stop input, or of the disabling of the translator (%Qxy.i.10=0), the deceleration phase is not carried out, the stop is immediate. On the other hand, the appearance of loss of step information is not considered to be a blocking error, it is simply signaled to the application.
Programming errors
Errors can be displayed, fixed and acknowledged from the debugging screen, but it can be useful in operation to be able to drive the moving part and fix errors from a console. For this end, the application has all the necessary information and commands.
Signaling errors The module offers a lot of information in the form of status bits and words, which can be accessed via the PL7 program. These bits allow the errors to be handled hierarl l chically: to act on the principle program, to simply signal the error.
TLX DS 57 PL7 40E 09.2000
105
Programming
Levels of signaling
2 levels of signaling are provided:
First level: general information
Bit
%Ixy.i.ERR
AX_OK (%Ixy.i.3)
AX_FLT (%Ixy.i.2)
HD_ERR (%Ixy.i.4)
AX_ERR (%Ixy.i.5)
CMD_NOK (%Ixy.i.6)
Error
Channel fault
No blocking error (with stop of moving part) is detected
Error (groups all the errors together)
External hardware fault
Application error
Command refused
Second level: detailed information
Module and axis error status words (%MWxy.i.2 and %MWxy.i.3), these words are obtained via explicit exchange requests described in language objects (See Appli-
cation-specific step by step axes control language objects, p. 173).
Note: On encountering a blocking error, we advise you to stop the development of the sequential processing to which the axis is associated and to fix the error by driving the moving part in manual mode. The correction of the error must be followed by an acknowledgement of the error.
Fault acknowledgment
When an error appears: l The error bits AX_FLT, HD_ERR, AX_ERR and the extract bits of the status words concerned by the error are set to 1.
l If the error is blocking the AX_OK bit is set to 0.
When the error disappears, all the error bits remain in their state. The error is stored until the acknowledgement obtained by resetting the bit ACK_DEF %Qxy.i.9 to 1 (or reinitialization of the module). The acknowledgement must be carried out after the error has gone (except for soft stop errors)
If several errors are detected, the acknowledgement order only works on the errors that have effectively disappeared. The errors still present must be acknowledged again after they have disappeared.
Note: The acknowledgement of an error can also be carried out at initialization of the PLC or when a correct new command is accepted in the case of a command refused error.
106
TLX DS 57 PL7 40E 09.2000
Programming
Summary table for the different types of errors
The following table summarizes the difference types of error and the associated bits:
Channel fault
(Bit %Ixy.i.ERR) l l l l
Internal
Communication
Configuration
Configuration or adjustment
Process errors (Bit AX_FLT: %Ixy.i.2)
AX_OK: %Ixy.i.3 (No blocking error detected)
External hardware (Bit
HD_ERR: %Ixy.i.4)
Application (Bit
AX_ERR: %Ixy.i.5) l l l l
Emergency stop
Translator
24 Volt supply
Brake output short circuit l Soft stops
Command refused (Bit
CMD_NOK:
%Ixy.i.6)
Coding of the error in the word
CMD_FLT:
%MWxy.i.7
(*) These errors are non blocking errors and have no influence on the bit AX_OK.
Description of the channel errors l l l
The bit %Ixy.i.ERR groups all the errors at channel level:
Internal error (%MWxy.i.2:X4): module absent, out of service or in auto-test.
Communication error (%MWxy.i.2:X6): communication error with the processor.
Configuration error (%MWxy.i.2:X5): difference between the declaration of the position of the module in the configuration and its actual position.
Note: The words %MW require a READ_STS command in order to be updated.
TLX DS 57 PL7 40E 09.2000
107
Programming
Description of external hardware faults
Introduction These errors are signaled by the bit HD_ERR (%Ixy.i.4). These errors are blocking errors and cannot be deactivated.
Emergency stop The following table shows the cause, the signal and the remedy to be applied in the case of a Emergency stop error:
Cause
Parameter
Consequence
Signal
Remedy
Circuit open between the 24V and the Emergency stop input in the module panel
None
The moving part is forced to stop
Bit EMG_STOP (%Ixy.i.29) and EMG_STP (%MWxy.i.3:X5)
Re-establish the connection between the input and the 24V then acknowledge the error.
24V supply
Brake output short circuit
The following table shows the cause, the signal and the remedy to be applied in the case of a 24V supply error:
Cause
Parameter
Consequence
Signal
Remedy
24V supply fault
None
The axis is not referenced, the moving part is forced to stop
Bit AUX_SUP (%MWxy.i.3:X6)
Re-establish the connection then acknowledge the error
The following table shows the cause, signal and the remedy to be applied in the case of a Brake output short circuit:
Cause
Parameter
Consequence
Signal
Remedy
Short circuit detected on the module’s brake output
None
The axis is not referenced, the moving part is forced to stop
Bit BRAKE_FLT (%MWxy.i.3:X1)
Remove the short circuit then acknowledge the error
108
TLX DS 57 PL7 40E 09.2000
Translator
Programming
The following table shows the cause, the signal and the remedy to be applied in the case of a Translator error:
Cause
Parameter
Consequence
Signal
Remedy
The translator check input does not receive the level translator OK defined in the channel configuration
None
The axis is not referenced, the moving part is forced to stop
Bit DRIVE_FLT (%MWxy.i.3:X2)
Remove the translator fault then acknowledge the error
TLX DS 57 PL7 40E 09.2000
109
Programming
Description of application errors
Introduction
Soft stops
These bits are signaled by the bit AX_ERR (%Ixy.i.5). The parameters can be accessed via the Configuration editor adjustment screen.
The following table shows the cause, the signal and the remedy to be applied in the case of a Soft stop error: This error is blocking and cannot be deactivated.
Cause
Parameter
Consequence
Signal
Remedy
The moving part is no longer situated between the 2 thresholds: software Lo limit and software Hi Limit (this monitoring is activated as soon as the axis is referenced)
Software Hi Limit: SL_MAX (%MDxy.i.14)
Software Lo Limit: SL_MIN (%MDxy.i.16)
The moving part is forced to stop
Bit %MWxy.i.3:X3: Software Hi Limit passed
Bit %MWxy.i.3:X4: Software Lo Limit passed
Acknowledge the error and in manual mode remove the moving part from outside the soft stops into the zone of valid measurements. To do that, you must check: l l l l l that no movement is in progress, that manual mode is selected, that the STOP command is set to 0, that the axis on which the command is carried out is referenced, that there is no other error with stop on the axis.
The moving part can either be brought back manually or by means of the commands JOG+ and JOG-.
110
TLX DS 57 PL7 40E 09.2000
Programming
Description of the command refused errors
Introduction
Command refused
A command refused error is generated each time that a command cannot be executed. This command is not compatible with the status of the axis or the current mode or at least one of the parameters is not valid.
These errors are signaled by the indicator Command Refused in the debugging screens. The DIAG key at the channel level tells you the source of the command refused. This information can also be accessed via the program via the bit
CMD_NOK (%Ixy.i.6) and the word CMD_FLT (%MWxy.i.7) (See List of error codes
The following table shows the cause, the signal and the remedy to be applied in the case of a Command refused error.
Cause
Parameter
Consequence
Signal
Remedy
Unauthorized movement command
Transfer of incorrect configuration or parameters
None
Immediate stop of the movement in progress
Reset to 0 of the memory buffer receiving the movement commands in automatic mode
Bit CMD_NOK (%Ixy.i.6): movement command refused
Word CMD_FLT (%MWxy.i.7): type of error detected l l
Least significant byte: executable commands,
Most significant byte: adjustment configuration and parameters.
Acknowledgement is implicit upon receipt of a new accepted command
Acknowledgement is equally possible via the command ACK_DEF
(%Qxy.i.9)
Note: In the case of movement sequencing in automatic mode, we advise you to condition the execution of each movement with the end of the execution of the preceding movement and with the bit AX_FLT (%Ixy.i.2). This means that the following command is not sequenced, when the current command has experienced a command refusal.
TLX DS 57 PL7 40E 09.2000
111
Programming
Management of manual mode
At a Glance You can select and control the manual mode from the debugging screen, but also via an application program, from a panel or an operator or supervisor dialog desk.
In this case, the dialog is programmed in ladder, instruction list or structured text language, using basic commands (movements, reference points, etc.)
Selecting manual mode
This is done by assigning value 2 to the word MOD_SEL (%QWxy.i.0).
The switch from the mode in use to manual mode forces the moving part to stop if a movement is in progress. Manual mode is effective as soon as the moving part has stopped.
When the command to switch into manual mode has been recognized, the bit
IN_MANU (%Ixy.i.22) bit is set to 1.
Executing manual commands
The basic commands associated with manual mode and accessible via command bits %Qxy.i.j are as follows: l l l l l l
Visual movement in the + direction JOG_P (%Qxy.i.1).
Visual movement in the - direction JOG_M (%Qxy.i.2).
Incremental movement in the + direction INC_P (%Qxy.i.3).
Incremental movement in – direction INC_M (%Qxy.i.4).
Manual reference point SET_RP (%Qxy.i.5).
Forced reference point RP_HERE (%Qxy.i.6).
These commands are equivalent to those accessible from the debugging screen of the TSX CFY module.
Manual commands:
Commands
- JOG + JOG
- INC + INC
Manual reference point
Forced reference point
Brake
Boost
112
TLX DS 57 PL7 40E 09.2000
General conditions for executing commands in manual mode
Programming
The following conditions must be fulfilled in order to execute commands in manual l l l l mode:
Target position within in the software limits.
Axis free of blocking error (AX_OK bit: %Ixy.i.3 = 1).
No command being executed (DONE bit: %Ixy.i.1 = 1).
STOP command (%Qxy.i.8) inactive and confirmation bit of the translator relay
ENABLE (%Qxy.i.10) set to 1
Note: Except, in the case of a software limit error, for commands JOG_P and
JOG_M and after error acknowledgement.
Stopping a movement l l l l
A movement may be stopped by: l The appearance of the STOP command (%Qxy.i.8) or the setting to 0 of the EN-
ABLE bit (%Qxy.i.10) or the STOP input.
The appearance of a blocking error.
Changing the operating mode.
Receiving a configuration.
The switch to the end of run plus limit (or minus) during a movement in the plus
(or minus) direction.
TLX DS 57 PL7 40E 09.2000
113
Programming
Visual movement commands
At a Glance To carry out a visual movement, you must use the manual commands JOG_P and
JOG_M.
The bits JOG_P (%Qxy.i.1) and JOG_M (%Qxy.i.2) control the movement of the moving part in the positive or negative direction. The operator must visually follow the position of the moving part. The movement continues for as long as the command is present and it is not disabled by a STOP command or an error.
The commands JOG_P and JOG_M are taken into account on edge and are kept active on state, whether the axis is referenced or not.
Movement speed The movement occurs at the manual mode speed MAN_SPD, defined in the adjustment screen (or in the double word %MDxy.i.20).
The speed can be modulated during movement by means of the CMV coefficient
(%QWxy.i.1).
Any movement speed higher than FMAX (maximum speed of the axis defined at configuration) is limited to the FMAX value.
Movement speed of the moving part:
Speed
MAN-SPD
JOG_P
Time SS_FREQ
0
DSS_FREQ
JOG_P
1
0
JOG_M
1
0
JOG_M
Time
Time
114
TLX DS 57 PL7 40E 09.2000
Notes on the
JOG_P and
JOG_M commands
Programming l l
The commands JOG_P and JOG_M are used to release the moving part when a software limit error is detected. This is done after first acknowledging the error.
If the JOG_P or JOG_M bit is set to 1 when switching to manual mode, this command is not recognized. It will only be recognized when the bit has been cleared and then reset to 1(detection of rising edge).
TLX DS 57 PL7 40E 09.2000
115
Programming
Incremental movement commands
At a Glance To carry out an incremental movement, you must use the manual commands INC_P and INC_M.
The bits INC_P (%Qxy.i.3) and INC_M (%Qxy.i.4) control the movement to increment the position of the moving part in the positive or negative direction.
The value of the position increment PARAM is entered in the double word
%QDxy.i.2 or in the debugging screen of the TSX CFY module.
Further to the general conditions of execution in manual mode, the commands l l
INC_P and INC_M are active on rising edge when:
The axis is referenced.
The target position is between the software limits.
Movement speed The movement is carried out at the manual mode speed MAN_SPD, defined in the adjustment screen (or in the double word %MDxy.i.20).
The speed can be modulated during movement by means of the CMV coefficient
(%QWxy.i.1).
Any movement speed higher than FMAX (maximum speed of the axis defined at configuration) is limited to the FMAX value.
Movement speed of the moving part:
Speed
MAN-SPD
SS_FREQ
DSS_FREQ
0
1
INC_P
0
1
INC_M
0
INC_P
PARAM -PARAM
INC_M
Time
Time
Time
116
TLX DS 57 PL7 40E 09.2000
Programming
Reference point command
At a Glance You can take a reference point by using the command SET_RP.
The bit SET_RP (%Qxy.i.5) takes a manual reference point with movement.
The type and the direction of the reference point are defined at configuration in the
Reference point (See
Reference point configuration, p. 68) parameter. The value of
the source is defined in the adjustment screen by the parameter RP Value (or the double word RP_POS: %MDxy.i.22).
Approach speed The approach speed is the manual speed MAN_SPD defined in the adjustment screen (or in the double word %MDxy.i.20) multiplied by the CMV speed modulation coefficient. The reference point speed varies according to the type of reference point selected.
Any movement speed higher than FMAX (maximum speed of the axis defined at configuration) is limited to the FMAX value.
Example: short cam only and + direction
Speed
(Hertz)
SET_RP
Cam
SS_FREQ
0
1
SET_RP
0
SET_OK
1
0
RP_POS
Position
(pulses)
Time
Time
TLX DS 57 PL7 40E 09.2000
117
Programming
Forced reference point command
At a Glance You can take a forced reference point by using the command RP_HERE.
The bit RP_HERE (%Qxy.i.6) takes a forced reference point without moving, at the value defined in the PARAM parameter. This value is entered in the double word
%QDxy.i.2 or in the debugging screen of the TSX CFY 11/21 module.
The forced reference point command is used to reference the axis without carrying out a movement.
Note: The command RP_HERE does not modify the value of the RP_POS parameter.
The value of the PARAM parameter must be between the software limits.
No blocking fault is tolerated during execution of this command.
118
TLX DS 57 PL7 40E 09.2000
Programming
Management of direct mode (DIRDRIVE)
At a Glance DIRDRIVE mode is used to simulate the axes control without operating the functional part; all the returned information is calculated.
The behavior of the axis can therefore be analyzed independently from the functional part.
Selecting direct mode
Direct mode is selected by assigning value 1 to the word MOD_SEL %QWxy.i.0.
On a request to change mode, the moving part is stopped, then the mode is changed. When the command for switching into direct mode has been recognized, the bit IN_DIRDR %Ixy.i.17 is set to 1.
Execution of commands in direct mode
Speed law
Direct mode includes the movement command DIRDRV %Qxy.i.0.
The speed setpoint is transmitted periodically by the variable PARAM %QDxy.i.2.
The sign of this variable gives the movement direction.
The speed of the translator is controlled between SS_FREQ and FMAX. These values are defined in the configuration screen (FMAX) and in the adjustment screen
(SS_FREQ).
The bit ST_DIRDR (%Ixy.i.20) indicates that a movement is in progress in DIR-
DRIVE mode.
When the setpoint is changed, the output achieves the new setpoint according to a trapezoid speed law, respecting the parameterized acceleration .
Speed (Hertz)
PARAM
SS_FREQ
0
-SS_FREQ
DIRDRV
%Qxy.i.0
1
0
Position
Time
TLX DS 57 PL7 40E 09.2000
119
Programming
Execution of the
DIRDRIVE command
The general conditions for execution of the DIRDRIVE command are as follows: l l
Axis without blocking fault (AX_OK bit: %Ixy.i.3 = 1).
STOP command (%Qxy.i.8) inactive and confirmation bit of the translator relay l
ENABLE (%Qxy.i.10) set to 1.
Parameter PARAM (%QDxy.i.2) between - FMAX and -SS_FREQ or between
SS_FREQ and FMAX of the selected axis.
Stopping a movement l l l l
A movement may be stopped by: l The appearance of the STOP command or the setting to 0 of the confirmation bit of the translator relay ENABLE (%Qxy.i.10).
The appearance of a blocking error or a software limit error.
Changing the operating mode.
Receiving a configuration.
The switch to the end of run plus limit (or minus) during a movement in the plus
(or minus) direction.
Note: Software limit monitoring remains active is the axis is referenced. To disable this monitoring, cause the axis reference to be lost by temporarily diasabling EN-
ABLE (%Qxy.i.10) to 0 and confirming by setting ENABLE to 1 or by pressing the confirmation button.
120
TLX DS 57 PL7 40E 09.2000
Programming
Management of stop mode (OFF)
At a Glance
Selecting stop mode
Execution of commands in stop mode
This mode is mainly used in debugging from within the configuration editor. It can however be program-driven. In this mode the module remains passive, but continues to update the current position information (%IDxy.i.0) and the current speed information (%IDxy.i.2).
Stop mode is selected by assigning value 0 to the word MOD_SEL %QWxy.i.0.
Stop mode is also selected by the module when the PLC is in STOP mode. It is selected by default following channel configuration.
The OFF mode has no associated movement command.
The movement of the moving part is not monitored and the monitoring of software errors is disabled (with the exception of the software limit monitoring).
The translator enable output continues to be monitored by the command ENABLE
(%Qxy.i.10).
TLX DS 57 PL7 40E 09.2000
121
Programming
122
TLX DS 57 PL7 40E 09.2000
Adjusting step by step axes control
6
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes the principles of parameter adjustment: access to the screens, description of parameters and the adjustment procedure.
This Chapter contains the following Maps:
Topic
Preliminary operations before adjustment
Accessing adjustment parameters
Trajectory adjustment
Adjusting brake output
Adjusting the stop stage
Adjusting manual mode parameters
Confirmation of adjustment parameters
Saving / Restoring adjustment parameters
Reconfiguration in connected mode
Page
TLX DS 57 PL7 40E 09.2000
123
Adjustment
Preliminary operations before adjustment
Preliminary conditions
Preliminary checks l l l l l
TSX CFY module(s) installed on the PLC,
Axes control application(s) connected to the TSX CFY module(s),
Terminal connected to the PLC via the terminal port or via network,
Axes control configuration and program completed and transferred to the PLC processor,
PLC in RUN mode. You are advised to disable the movement command application program (by using, for example, a program execution condition bit), in order to facilitate the adjustment operations.
l l l l
Check the cabling,
Check that the movements can take place safely,
Check that the mechanical stops are cabled conforming to the safety rules (generally they act directly on the power supply sequence of the translator),
Check and adjust the translator according to manufacturer’s instructions,
124
TLX DS 57 PL7 40E 09.2000
Adjustment
Accessing adjustment parameters
Introduction
Accessing parameters
To access adjustment parameters, use the command Adjust from the View menu in the configuration screen of the TSX CFY. You can also select Adjust in the module zone in the configuration or debugging screens.
The adjustment screen allows you to select the channel to be adjusted and gives you access to the current or initial parameters:
Command
Choose Axis
Function
Select channel 0 for example.
This button allows you to display either the current parameters or the initial parameters.
Initial parameters
Current parameters
The initial parameters are: l The parameters entered (or defined by default) in the configuration screen in local mode. These parameters have been enabled at configuration and transferred to l the PLC.
The parameters taken into account at the time of the last reconfiguration in connected mode.
The current parameters are those which have been modified and enabled from the adjustment screen in connected mode (or by the program through an explicit exchange). These parameters are replaced by the initial parameters at the time of a cold restart.
Note: it is imperative to follow a session of determining adjustment parameters with an operation to save parameters.
TLX DS 57 PL7 40E 09.2000
125
Adjustment
Adjustment parameters
The adjustment screen offers the following parameters:
File Edit
Trajectory
Start/stop frequency
Acceleration
Software Hi Limit
Software Lo limit
Output brake
Off delay
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
TSX CFY 21 [RACK 0 POSITION 3]
200
50 000
500 000
-1 000 000
Hertz
Hertz/s
Pulses
Pulses
Stop level
Period 50 ms
Manual mode parameters
Speed 5 000 Hertz
RP Value 0 pulse
0 ms On delay 0 ms
?
Acceleration: [9 155, 100 000] CONNECT RUN U:SYS
Note: for each parameter, the limits are displayed in the status bar.
To display the whole of the adjustment parameters zone, select the commands:
View
→
Module zone or View
→
Channel zone (to restore these zones, select the same commands).
126
TLX DS 57 PL7 40E 09.2000
Adjustment
Trajectory adjustment
At a Glance
Illustration
Description
The adjustment screen supports characterization of the trajectory on the axis: l l l l start and stop frequency, acceleration, software hi limit, software lo limit.
The input area for trajectory characteristics is as follows.
Trajectory
Start/stop frequency
Acceleration
Software Hi Limit
Software Lo limit
100 Hertz
9 155 Hertz/s
10 000 000 pulses
-10 000 000 pulses
The table below describes the dialog box for inputting trajectory characteristics.
Field Description
Start/stop frequency Called SS_FREQ, this is the minimum speed of the movement of the moving part.
If FMAX, the maximum speed defined in configuration, is lower than 4
KHz, SS_FREQ must be contained between 0 and FMAX.
Otherwise, SS_FREQ must be contained between 0 and 4KHz.
When SS_FREQ is left at zero, the start and stop frequency is the smallest frequency in the range (See Configuring control parameters,
Acceleration Called ACC, this is the moving part’s acceleration and deceleration gradient or the period of acceleration needed to go from the speedSS_FREQ to FMAX (See Configuring control parameters, p.
When the user-defined unit is Hertz/s, this parameter must be between the lower acceleration limit for the range of max speed and the acceleration entered in configuration (See
When the user-defined unit is ms, this parameter must be between the value of the max acceleration entered at configuration and 5000 ms.
TLX DS 57 PL7 40E 09.2000
127
Adjustment
Field
Software Hi Limit
Software Lo limit
Description
Called SLMAX and expressed by number of pulses, this is the maximum position of the movement of the moving part in the positive direction.
Called SLMIN and expressed by number of pulses, this is the minimum position of the movement of the moving part in the negative direction.
The software limits must respect the following differences: l l
SLMIN less than or equal to SLMAX
SLMIN and SLMAX between 16 777 216 and 16 777 215
When the two software limits SLMIN and SLMAX are zero, the monitoring of these software limits is not activated. Movements can be executed on the whole of the counting range from
-16 777 216 to + 16 777 215 without, however, exceeding one of these limits.
128
TLX DS 57 PL7 40E 09.2000
Adjustment
Adjusting brake output
At a Glance
Illustration
The adjustment screen is used to parameterize the brake output, when automatic l l brake management has been selected at configuration. The delay can be set: on activation, on deactivation.
The zone for inputting delays on activation and deactivation is as follows.
Output brake
Off delay 5 ms On delay 0 ms
TLX DS 57 PL7 40E 09.2000
129
Adjustment
Description The table below describes the dialog box for entering delays on activation and deactivation.
Field
Delay on deactivation
Description
Delay on activation This parameter is between –1000 and 1000 milliseconds. A negative value indicates an anticipation of the end of a movement. A positive value indicates a delay.
This parameter is between –1000 and 1000 milliseconds. A negative value indicates an anticipation of the beginning of a movement. A positive value indicates a delay.
Diagram showing operation of the delay on output Brake.
F
SS_FREQ
0
F
SS_FREQ t (s)
0 t (s)
(1)
(3) t (s) t (s)
(2)
(4) t (s) t (s)
1 Anticipation, delay on deactivation, negative value.
2 Delay, delay on deactivation, positive value.
3 Anticipation, delay on activation, negative value.
4 Delay, delay on activation, positive value.
130
TLX DS 57 PL7 40E 09.2000
Adjustment
Adjusting the stop stage
At a Glance This field is the period of the stop stage order when the speed is equal to the start and stop speed, FDA. This period must be between 0 and 1000 ms.
There is a relation between the duration of the stop stage and the brake activation delay (when this delay value is negative) in cases when automatic management
(See
Configuring the step by step motor’s brake, p. 66) of the brake is configured.
TLX DS 57 PL7 40E 09.2000
131
Adjustment
Operation How axes control operates with regard to the duration of the stop stage.
If the duration of the stop stage is…
Then… greater than the brake activation delay the brake is activated as soon as the speed has reached start/stop speed, SS_FREQ. The duration of the stop stage is that of the adjustment parameter.
Speed (Hertz)
SS_FREQ
0
Brake output
< 0
Inactive Active t(s)
Stop plateau= 500
On delay = -200 t(s) less than the brake activation delay the duration of the stop stage is forced to the duration of the brake activation, regardless of the value fixed in adjustment mode. The brake is activated as soon as the speed of the moving part has reached start/stop speed, FDA.
Speed (Hertz)
SS_FREQ
0
Brake output
< 0
Inactive Active t(s)
Stop plateau= 500
On delay = -200 t(s)
Effective duration of
stop plateau = -200
132
TLX DS 57 PL7 40E 09.2000
Adjustment
Adjusting manual mode parameters
At a Glance
Illustration
Adjustment of manual mode parameters defines the action of the moving part in manual mode (See
Management of manual mode, p. 112). There are two parame-
ters: l l speed, the value of the reference point.
The manual mode parameter input zone is as follows.
Manual mode parameters
Speed
RP Value
300 Hertz
10 000 pulses
Description The table below describes the dialog zone for inputting manual mode parameters.
Field
Speed
Reference point value
Description
This is the movement speed, MAN_SPD, of the moving part in manual mode.
The value of the field determines the speed of the moving part in manual mode, when it is controlled by instructions JOG+, JOG-, INC+,
INC- and the approach and stopping speed in SET_RP, etc. The value of this field must be between the start/stop speed SS_FREQ and the
maximum speed FMAX set in the configuration (See Configuring con-
).
Just as in automatic mode, the actual movement speed is modulated by the modulation coefficient CMV.
This is the value loaded into the current position when taking a reference point in manual mode.
The value of the Reference point field, RP_POS, is transferred to the immediate position, X_POS when taking a reference point in manual mode with axes control in manual mode.
Generally speaking, the value of this field must be between SLMIN and
SLMAX. In the special case, where SLMIN=SLMAX=0, the value of this field must be between -16 777 216 and 16 777 215.
TLX DS 57 PL7 40E 09.2000
133
Adjustment
Confirmation of adjustment parameters
Introduction When you have entered the adjustment parameters, you must confirm these parameters using the command Edit/Confirm or by clicking the icon.
Parameters outside the limits
If one or several parameter values are not within the authorized limits, an error message appears referencing the parameter concerned.
You must fix the parameter(s) that are at fault, then execute a further confirmation.
No modification of the configuration parameters
If you have not modified the configuration parameters, the modification of the adjustment parameters does not interrupt the working of the axis but changes its behavior.
The modified adjustment parameters are the current parameters (the initial parameters remain unchanged).
PLC processor Axes control channel
Adjustment screen
Current adjustment parameters
Cold restart
Initial adjustment parameters
Current adjustment parameters
Note: During a cold start the current parameters are replaced by the initial parameters.
The initial parameters can be updated by the save command or by a reconfiguration operation.
134
TLX DS 57 PL7 40E 09.2000
Adjustment
Saving / Restoring adjustment parameters
Saving parameters
To save current parameters (updating initial parameters), activate the command
Services
→
Save parameters .
PLC processor Axes control channel
Current adjustment parameters
Save
parameters
Current adjustment parameters
Initial adjustment parameters
Restoring parameters
To replace the current parameters by the initial parameters, activate the command
Services
→
Restore parameters.
PLC processor Axes control channel
Current adjustment parameters
Restore
parameters
Current adjustment parameters
Initial adjustment parameters
TLX DS 57 PL7 40E 09.2000
Note: The instruction RESTORE_PARAM allows the application to carry out this restoration operation. The restoration is also carried out automatically at the time of a cold start.
135
Adjustment
Reconfiguration in connected mode
Introduction When configuration parameters are modified, you must confirm these parameters using the command Edit
→
Confirm or by clicking on the icon.
Parameters which can be modified in connected mode
Only parameters that are not grayed out can be modified in connected mode. Other parameters like activation of an event task must be modified in local mode. Every time that you reconfigure, the corrected resolution becomes the initial resolution.
Stopping the movement in progress
All configuration in connected mode brings about a stop in the operation of the channel concerned and thus the stopping of the movement in progress. This is signaled by a dialog box:
Validate
Reconfiguration will STOP channel 0.
Are you sure you want to reconfigure channel 0?
Yes No
136
TLX DS 57 PL7 40E 09.2000
Adjustment
Parameter exchange when reconfiguring
The following diagram presents the parameter exchanges when reconfiguring in connected mode:
Configuration screen (1) PLC processor Axes control channel
Parameters for configuring
Parameters for configuring
Reconfiguration
Parameters for configuring
Current adjustment parameters
Current adjustment parameters
Current adjustment parameters
Initial adjustment parameters
(1) or adjustment screen if a configuration parameter has first been modified in the configuration screen.
TLX DS 57 PL7 40E 09.2000
137
Adjustment
138
TLX DS 57 PL7 40E 09.2000
Debugging a step by step axes control program
7
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes the debugging functions for an axes control channel, in the different modes: stop, direct, manual, automatic. It also describes the diagnostics screen which gives you access to possible errors.
This Chapter contains the following Maps:
Topic
Debugging principles
User interface of the debugging screen
Description of the debugging screens
Detailed information on the debugging screen
Stop Mode (Off)
Direct Mode (Dir Drive)
Manual mode (Manu)
Automatic mode (Auto)
Channel diagnostics
Storage, document and simulation
Page
139
TLX DS 57 PL7 40E 09.2000
Debugging
Debugging principles
Introduction
Recap of the possibilities offered by PL7
Application specific debugging screen
Axes control, being integrated into the PL7 program, uses the PL7 debugging functions. l l l
Real time display and animation of the program.
For example, in Grafcet language, if you program each movement in a step, it will be easy to know which movement is in progress.
Inserting program breakpoints and execution points: cycle by cycle, network by network or statement by statement.
Accessing animation tables. This allows you to display the status words and bits and control the command bits for the SMOVE. You can also force object bits and block the Grafcet development.
The PL7 software also offers you a application specific debugging screen specific to the TSX CFY modules, which gives you access to all necessary information and commands:
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
?
Module zone
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
Channel zone
Monitoring zone
Symbol:
Choose axis: Function:
Channel 0 Positioning
Manu
Auto
Dir
Drive
CH0
Global unforcing
DIAG...
Off
Movement: Pulse Speed: Hertz
X
Current
0
Target
0
F
0 0
N
Position
Speed
CMV
1 G9_
1 000
90 G
EVT Sources
5
G10/G11 limit
0%
Remainder
0
DONE
+Direction
AT Point
NEXT Pause
Axis
OK
Referenced
Stopped
Immediate
I/O
Extern Stop
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Commands
Enable Reactivate step
Faults
Refuse Cmd
Brake
Hardware
G05 limit Boost
Axis
RefP TO G05
Pause
STOP
F8
RefP 0 pulses
PLC Sync
Ack.
Speed modulation coefficient: [0,2 000] CONNECT RUN U:SYS
140
TLX DS 57 PL7 40E 09.2000
Debugging
This screen is includes 3 zones: l l l
Module zone,
Channel zone,
A moving part and program control zone. This zone depends upon the operating mode that you have selected via the mode switch: Automatic (Auto), Manual
(Manu), Direct (Dir Drive) or Stop (Off).
TLX DS 57 PL7 40E 09.2000
141
Debugging
User interface of the debugging screen
Accessing the debugging screen
Command buttons
You can only access the debugging screen if the terminal is in connected mode.
l l
If this is the case, access the debugging screen in the following way:
Select the Configuration editor,
Select and confirm (or double click on) the rack position that contains the axes control module, l By default in connected mode, the debugging screen is displayed.
The operation of the command buttons is as follows:
Input field l For the on state commands (except JOG commands):
Pressing then releasing the button activates the associated command. The button’s internal light is lit when this command is recognized (the corresponding command bit %Q is set to 1).
Pressing then releasing the button a second time deactivates the command. The button’s internal light is extinguished when this command is recognized (the corresponding command bit %Q is set to 0).
For on edge commands: l
The command is activated as soon as the button is pressed then released. The button’s internal light lights up then is automatically extinguished.
The light situated next to the button signals the recognition of the command by the module.
All values entered into an input field must be confirmed using the button.
Using the keyboard
You can use the keyboard to browse in the screens or activate a command:
Keys
Shift F2
Tab
Arrow keys
Space Bar
Action
Allows you to move from one zone to another
In the same zone, allows you to move from one group of commands to another
In a group of commands, allows you to move from one command to another
Allows you to activate or deactivate a command
142
TLX DS 57 PL7 40E 09.2000
Debugging
Conflicts with the program
There can be conflicts between the PL7 program that carries out the commands or writes the variables and the commands executed from the debugging screen. In all cases, it is the last recognized command that will be active.
Animation You can stop animation in the display fields: l The command Services
→
Stop animation stops animation in the display fields and disables the command buttons. For this function you can also use the icon l The command Services
→
Animate reactivates animation. You can also use the icon
TLX DS 57 PL7 40E 09.2000
143
Debugging
Description of the debugging screens
Introduction The debugging screens have a common header, made up of a module zone and a channel zone.
TSX CFY 21 [RACK 0 POSITION 6]
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
Symbol:
Choose axis: Function:
Channel 0 Positioning
Auto
Manu
Off
Dir
Drive
Global unforcing
CH0 DIAG...
Module zone This table describes the module zone:
Light
RUN
ERR
I/O
DIAG
State
On
On
Flashing
On
On
Meaning
Module is operating
Module is out of service
Communication fault with the processor
Process error (AX_FLT %Ixy.i.2 bit)
Module failed. If you press the button associated with this light, a diagnostics module dialog box appears in order to clarify the source of the error (See Diagnostics and main-
144
TLX DS 57 PL7 40E 09.2000
Channel zone
DIAG
Debugging
In addition to the fields Choose axis and Function (common to all screens), this zone includes the following commands and lights:
Command
(1)
Force to 0
Force toà 1
Unforce
F4
F5
F6
(2)
Function
Button to select the operating mode
If you want to change the operating mode, click on the name of the new mode to be selected (or click as many times as necessary on the button).
Using the keyboard, select the button using the Tab key then press as many times as necessary on the Space bar.
You can also access the operating modes via the View menu.
When the selected mode is actually recognized by the module, the monitoring zone for movements in the selected mode is displayed.
Caution: although selected, it is possible for the selected mode not to be recognized by the module channel (for example, if the
PLC is in STOP mode).
Forcing command menu.
If an object can be forced, a right click on the corresponding button (1) displays a menu (2) that gives access to the forcing commands: Forcing to 0 , Forcing to 1 or Unforcing.
After selecting the command by clicking on it, forcing is applied and the forcing status is signaled at the level of the button (3): l l
F for forcing to 0,
F in reverse video for forcing to 1.
The button Global unforcing in the module zone supports unforcing of all the forced objects.
(3)
CHi On: Axis (channel) configured and error free.
Flashing: Axis failed.
Off: Axis not configured.
On: Channel failed.
If you press the button associated with this light, a dialog box appears, clarifying the source of the error (See Diagnostics and
TLX DS 57 PL7 40E 09.2000
145
Debugging
Detailed information on the debugging screen
At a Glance
Description of the Movement /
Speed field
The debugging screen is different according to the switch position selected. There are four possible choices: l l l
Direct Mode (Dir Drive), p. 151
l
The fields and buttons that appear in the four screens are detailed below.
This table describes the display zones of the Movement / Speed field:
Display zone
X Current
X Target
X Remainder
F Current
F Target
N G G9
Position
Speed
Description
Displays the position of the moving part in number of pulses.
Displays the position setpoint of the moving part (position to be reached)
Displays the number of pulses left to run
Displays the speed of the moving part in number of pulses
Displays the speed setpoint of the moving part: speed to be reached
(manual speed modulated by the CMV coefficient)
In auto mode, displays the instruction currently being executed: l l l
N for the number of steps
G9 for the type of movement
G for the instruction code
This slide shows the evolution of the moving part between the limits defined in the configuration screen. The color of the slide is green and becomes red if the limits are exceeded
This slide displays as a % the speed of the moving part in relation to the maximum speed. The color of the slide is green and becomes red if
VMAX is exceeded
146
TLX DS 57 PL7 40E 09.2000
Debugging
This table describes the lights in the Movement / Speed field:
Light
+Direction
-Direction
AT Point
NEXT
/
State
On
On
DONE On
Immediate pause On
Meaning
Indicates a movement of the moving part in the positive direction
Indicates a movement of the moving part in the negative direction
Indicates that the movement in progress has finished and that the moving part has reached the target point
Indicates that the moving part is ready to receive a movement command
Indicates that the movement in progress has finished
Indicates that the immediate pause function is activated
(coefficient CMVset to 1). At this moment the target position contains the immediate pause stop position.
Description of
Axis field
This table describes the display and command zones of the Axis field:
Light / Button
OK
Referenced
Stopped
Confirmation /
State
On
On
On
Meaning
Axis in operational state (no blocking fault)
Referenced axis:
Moving part stationary
This button is used to control the variable speed controller confirmation relay
Description of I/O field
This table describes the display zones of the I/O field:
Light
External stop
End of run +/-
RP cam
Evt cam
Meaning
Signal state (0 or 1) on External stop input. The light is on when the
external stop is activated, presence of 24V on the input.
Function activity end of run +/-. The light is on when the moving part is at the end of run limit, absence of 24V on the input.
Signal state (0 or 1) on Reference point input. The light is on when the moving part is on the cam, presence of 24V.
Signal state (0 or 1) on Event input. The light is on when the moving part is on the event cam, presence of 24V.
TLX DS 57 PL7 40E 09.2000
147
Debugging
Description of commands
Light
Ctrl trans
Loss of step
Reset step
Meaning
The light is on when the translator does not deliver the signal ready.
The light is off when the translator gives the signal OK. The levels depend on the selection made at configuration.
Signal state (0 or 1) on Loss of step monitoring input, signal delivered by the translator. The light is on when the input is set to 1(cable disconnected), otherwise it is off.
This button controls the resetting of the detection system which detects loss of translator step.
1 = light on, 0 = light off
This table describes the command zone:
Command
STOP
Param
CMV
Description
Causes the moving part to stop according to the deceleration defined on configuration
Is used to enter the value of an incremental movement (INC+ or INC- command) or the forced reference point
Is used to enter a value from 0 to 2000 which determines the speed multiplier coefficient (0.000 to 2.000 in steps of 1/1000)
Description of
Commands field
This table describes the buttons of the Commands field:
Command
JOG-
JOG+
INC-
INC+
Manual reference point
Forced reference point
Description
Visual movement command in the negative direction (1)
Visual movement command in the positive direction (1)
Incremental movement command in the negative direction, for a distance defined in the field Param
Incremental movement command in the positive direction, for a distance defined in the field Param
Order to search and take manual reference point. The current position takes the value Value PO, defined in the adjustment screen, having found the reference point conforming to the type defined on configuration.
With an incremental encoder, forced reference point order. The current position is forced to the value defined in the field Param
This type of reference point does not cause movement of the moving part
148
TLX DS 57 PL7 40E 09.2000
Description of
Faults field
Debugging
Command
Brake
Boost
Pause
Description
Manual command for the activation or deactivation of the brake output
In the case where automatic brake management is configured, it is the last activation or deactivation command edge between this manual command (%Qxy.i.13) and the automatic command that is taken into account.
Manual command for the activation or deactivation of the boost output
In the case where automatic boost management is configured, it is the last activation or deactivation command edge between this manual command (%Qxy.i.14) and the automatic command that is taken into account.
Stop the movement sequencing at the end of the next movement with stop
Order to trigger an event from the proccessor PLC Sync.
(1) These commands remain active as long as the button is pressed. They are used to release the moving part outside the soft stops (after fault acknowledgement).
This table describes the display and command zones of the Faults field:
Light / Button State
Command refused On
Hardware On
Axis
Ack.
/
On
Meaning
Refusal of last command
External hardware fault (encoder, variable speed controller, outputs, …)
Application fault (following error, soft stops, ...)
Fault acknowledgement button. An action on this button acknowledges all the faults that have disappeared
TLX DS 57 PL7 40E 09.2000
149
Debugging
Stop Mode (Off)
At a Glance In this mode, the axis control channel only reports on position and speed. The module movement is not monitored by the channel. The translator confirmation output continues to be monitored by the ENABLE (%Qxy.i.10) command.
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
?
Symbol:
Choose axis: Function:
Channel 0 Positioning
Movement: Pulse Speed: Hertz
Current
X
0
F 0
Auto
Manu
Dir
Drive
CH0 DIAG...
Off
Axis
OK
Referenced
Stopped
Faults
Hardware
Axis
Ack.
CONNECT RUN U:SYS
For details on the fields and buttons in this screen, see Detailed information on the
150
TLX DS 57 PL7 40E 09.2000
Debugging
Direct Mode (Dir Drive)
Introduction Direct mode allows you to directly control the movement of the moving part, according to the movement setpoint indicated in the PARAM variable.
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
?
Symbol:
Choose axis: Function:
Channel 0
Movement: Pulse Speed: Hertz
Current
X
F
0
0
Position
Speed
Param
STOP
F8
Positioning
Parameter: [-10 000, 10 000 ]
0 Hertz
Auto
0%
Manu
Dir
Drive
CH0
Global unforcing
DIAG...
Off
Axis
OK
Referenced
Stopped
Command
Enable
I/O
Extern Stop
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Reactivate step
Faults
Refuse Cmd
Hardware
Axis
Ack.
CONNECT RUN U:SYS
For details on the fields and buttons on this screen, see Detailed information on the
TLX DS 57 PL7 40E 09.2000
151
Debugging
Manual mode (Manu)
Introduction Manual mode allows you to directly control the movement of the moving part, from the debugging screen. To do this you can use the commands JOG+, JOG-, INC+…
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
?
Symbol:
Choose axis: Function:
Channel 0 Positioning
Movement: Pulse Speed: Hertz
X
Current
0
Target
0
F 0 0
Position
Speed 0%
STOP
F8
Parameter: [-16 777 216, 16 777 215]
Manu
Auto
Dir
Drive
CH0
Global unforcing
DIAG...
Off
Remainder
0
DONE
-Direction
AT Point
Axis
OK
Referenced
Stopped
Commands
- JOG
- INC
Enable
+ JOG
+ INC
I/O
Extern Stop
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Reactivate step
Faults
Refuse Cmd
Hardware
Manual reference point
Axis
Forced reference point
Brake
Boost Ack.
CONNECT RUN U:SYS
For details on the fields and buttons on this screen, see Detailed information on the
152
TLX DS 57 PL7 40E 09.2000
Debugging
Automatic mode (Auto)
Introduction Automatic mode is the mode in which the SMOVE functions are executed.
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
?
Symbol:
Choose axis: Function:
Channel 0 Positioning
Auto
Manu
Dir
Drive
CH0
Global unforcing
DIAG...
Off
Movement: Pulse Speed: Hertz
X
Current
0
Target
0
F
0 0
N 1 G9_ 90 G 5
Position
Speed
STOP
F8
1 000
EVT Sources
G10/G11 limit
RefP
RefP 0
0%
Remainder
0
DONE
NEXT
G05 limit
TO G05 pulses
-Direction
Axis
OK
Referenced
Stopped AT Point
Pause
Immediate
Commands
Brake
Boost
Pause
Enable
I/O
Extern Stop
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Reactivate step
Faults
Refuse Cmd
Hardware
Axis
PLC Sync Ack.
Speed modulation coefficient: [0,2 000] CONNECT RUN U:SYS
For details on the fields and buttons on this screen, see Detailed information on the
TLX DS 57 PL7 40E 09.2000
153
Debugging
Channel diagnostics
Introduction In connected mode the different debugging, adjustment and configuration screens offer a DIAG button that gives access to the details on the faults detected for the module and for the channel.
Example of module diagnostics.
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
?
Symbol:
Choose axis: Function:
Chann Positioning
Manu
Auto
Dir
Module diagnostics
CH0 DIAG...
Internal faults
Movement: Pulse Speed: Hertz
X
Current
0
Target
0
F
0 0
N 1 G9_ 90 G 5
Position
Speed 0%
STOP
F8
1 000
EVT Sources
G10/G11 limit
RefP
RefP 0
G05 limit
TO G05 pulses
Used to read module diagnostics
Remainder
0
DONE
NEXT
-Direction
AT Point
Pause
Immediate
Axis
OK
I/O
Extern Stop
Reference
Stopped
+ Limit
- Limit
RP Cam
Event Cam
Ctrl transl
Loss of step
Enable Reactivate step
Faults
Brake
Boost
Pause
Refuse Cmd
Hardware
Axis
PLC Sync
Ack.
CONNECT RUN U:SYS
154
TLX DS 57 PL7 40E 09.2000
Example of channel diagnostics.
File Edit
PL7 Junior: AXIS - [TSX CFY 21 [RACK 0 POSITION 3]]
Utilities View Application AP Debug Options Window
STOP
Debugging
Designation: MOD.MOT.PAS A PAS 2 VOIES Version: 1.0
RUN ERR IO DIAG...
Symbol:
Choose axis: Function:
Channel 0 Positioning
Internal faults
Manu
Auto
Dir
Drive
CH0
Off
Global unforcing
Channel diagnostics
External faults Other faults
DIAG...
Drive fault
?
Debugging
Description of different fields
Commands refused
Configuration:
Adjust
Command: 16#9a MANU command error IncM stop condition
STOP
F8
OK
CONNECT RUN U:SYS
The Channel diagnostics screen offers the following fields:
Field
Internal errors
External errors
Other faults
Commands refused
Description
Internal errors in the module that generally necessitate the replacement of the module
Errors coming from the operating part (See Description of ex-
ternal hardware faults, p. 108 )
Faults from the application (See Description of application er-
Indicate the cause and the message number of a command refused (See
Description of the command refused errors, p. 111 )
TLX DS 57 PL7 40E 09.2000
155
Debugging
Storage, document and simulation
Storage
Documentation
Simulation
When you have debugged your program in connected mode, you must carry out the following save operations: l l
Save the adjustment parameters if these have been modified. To do this, select the adjustment screen and use the command Services
→
Save parameters,
Save the application on to disk using the command File
→
Save.
l l
The documentation for the axes control application is included in the complete documentation for the PL7 application. This documentation allows you to group in a file:
The program,
The saved Configuration and Adjustment parameters.
To operate the channels of the TSX CFY module, all you need is the Telefast discrete simulator strip, reference ABE-6TES160, supplied by the 24 volts available on the rack supply, and to connect it directly to the TSX CFY’s auxiliary I/O HE10 connector via a ribbon cable.
For channel 0, add a level 1 to inputs 2, 4 and 5 (emergency stops and end of runs).
For channel 1 (only TSX CFY 21), inputs 8, 10 and 11. Leave the level 0 everywhere else.
When configuring the axis control channel, check the box drive inversions…mon-
itor input. This supports operation in the absence of any connection to the SUB D translator.
Confirm
How to carry out simulation with a
TSC CFY
To operate the channels of the TSX CFY module, all you need is the Telefast discrete simulator strip, reference ABE-6TES160, supplied by the 24 volts available on the rack supply, and to connect it directly to the TSX CFY’s auxiliary I/O HE10 connector via a ribbon cable.
Step
1
2
3
4
5
Action
For channel 0, add a level 1 to inputs 2, 4 and 5 (emergency stops and end of runs).
For channel 1 (only TSX CFY 21), add a level 1 to inputs 8, 10 and 11. Leave the level 0 everywhere else.
When configuring the axis control channel, check the box drive inver-
sions…monitor input. This supports operation in the absence of any connection to the SUB D translator.
Confirm the channel in the implementation screen in manual mode.
Use the buttons JOG+ or JOG- to simulate movements of the moving part.
156
TLX DS 57 PL7 40E 09.2000
Operation
8
Designing an operator dialog
Buttons box To design a simple or a complex button box, you have at your disposal elementary commands and information, in the form of command and status bits and words (See
Application-specific step by step axes control language objects, p. 173).
Operator dialog on CCX 17
The following example allows you to carry out a movement in manual mode, of the type visual movement JOG+ and to change the coefficient of speed modulation
CMV, on an operator dialog terminal CCX 17.
It does not matter whether you carry out this command or this modification of the speed coefficient from the application specific debugging screen or from the CCX 17 terminal.
In the following ladder, %M200 corresponds to the status of the button on the
CCX 17 terminal that activates the JOG+ command.
%M200
P
%M200
N
%17.0.22
%17.0.22
%Q7.0.1
S
%Q7.0.1
R
The following ladder supports allows refreshing of the %M200 bit on each cycle, for the detection of fronts.
%M200 %M200
In the following ladder, %M200 contains the setpoint of the coefficient CMV, defined on the CCX 17 terminal. %MW0 contains the last saved setpoint CMV entered on the terminal.
COMPARE
%MW0<>%MW200
OPERATE
OPERATE
%MW0:=%MW200
TLX DS 57 PL7 40E 09.2000
157
Operation
158
TLX DS 57 PL7 40E 09.2000
Diagnostics and maintenance
9
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes what to do in certain maintenance situations (symptoms, diagnostics and course of action to undertake).
This Chapter contains the following Maps:
Topic
Fault monitoring and conditions of command runnability
Diagnostic help
Page
TLX DS 57 PL7 40E 09.2000
159
Diagnostic and maintenance
Fault monitoring and conditions of command runnability
Fault monitoring You have at your disposal several methods of detecting a possible fault: l l the lights on the module’s panel,
The diagnostics screens which can be accessed by means of the DIAG in connected mode, from all the application-specific screens (See Channel diagnostics, l l
p. 154) in the axes control module,
The debugging screens (See
Description of the debugging screens, p. 144),
The error bits and the status words (See Application-specific step by step axes
control language objects, p. 173).
Movement commands
In order for the movement commands (in automatic or manual mode) to be executl l l l l l l able, the following conditions must be met:
The axis is configured and free of blocking errors,
The variable speed controller confirmation command ENABLE is active
(%Qxy.i.10 bit set to 1) and the STOP command is inactive,
Automatic or manual mode is selected,
For commands using absolute position, the position is between the limits SL_MIN and SL_MAX, l For commands using relative position, the target calculated from the current relative position is between the limits SL_MIN and SL_MAX,
The axes are referenced, except for reference point and JOG commands,
The speed F must be less than or equal to FMAX,
If the moving part is outside the end of run limits, the movement direction requested must be that which returns it to within limits.
Modifying the
CMV parameter
Sequence control
If a modification of the speed modulation CMV parameter involves a speed higher than FMAX, then this is limited to FMAX.
If you have not selected the option Sequence control at configuration, a continuous movement followed by any sequence control will continue until the soft stops.
160
TLX DS 57 PL7 40E 09.2000
Diagnostic and maintenance
Diagnostic help
Introduction It can happen that you meet situations that you need to resolve. The following procedure to follow helps you to diagnose these situations and informs you of what to do.
Procedure to follow in various situations
New parameters are not recognized
Symptom
Diagnostics
What to do
The TSX CFY module does not seem to have recognized the new parameters written by WRITE_PARAM
Program a READ_PARAM instruction into your application so that you can find out the values really used by the module.
A WRITE_PARAM activated while another adjustment exchange is in progress is ignored.
Test the %MWxy.i.0:X2 bit before all adjustment exchange
Event processing
Symptom
Diagnostics
What to do
The event processing associated with the axes control channel is not executed l l l
Check that the whole of the string trace back for the event is valid l Event number declared in the configuration is identical to that in the event processing,
The event source is unmasked (code M of the SMOVE command),
Events are authorized at system level (%S38 = 1),
Events are unmasked at system level (UNMASKEVT())
Refer to the use of events
Adjustments are lost
Symptom
Diagnostics
What to do
Your adjustments have been lost
A cold start causes the loss of the current adjustments carried out via the screen or a WRITE_PARAM instruction
Save the current adjustments using the command Service
→
Save pa-
rameters or using the instruction SAVE_PARAM
Inconsistent status words
Symptom
Diagnostics
What to do
The status words %MWxy.i.1 and %MWxy.i.2 are not consistent with the status of the axes control channel
These words are only updated on the explicit request READ_STS
Program a READ_STS instruction in your application
TLX DS 57 PL7 40E 09.2000
161
Diagnostic and maintenance
Ineffectual commands
Symptom
Diagnostics
What to do
The commands from the debugging screen are not having any effect
The application or the task is in STOP mode
Switch the application or the task into RUN mode
Non modifiable commands
Symptom
Diagnostics
What to do
Certain commands from the debugging screen are not modifiable
These bits are written by the application
Use bit forcing (for objects of type %Qxy.i.r) or rewrite your application so that it does not write these bits systematically (modification on transition and not on state)
Impossible to enter characters
Symptom
Diagnostics
What to do
It is impossible to enter more than 3 characters in the numeric fields in the adjustment and configuration screens
In the Windows configuration panel, you have not selected the thousand separator
In the Windows configuration panel, select the icon International in the field Number format.
Activate the command Modify and select a thousand separator
162
TLX DS 57 PL7 40E 09.2000
TLX DS 57 PL7 40E 09.2000
Diagnostic and maintenance
Command refused
Symptom
Diagnostics
What to do
IN DIRDRIVE mode, after a stop after overshooting the soft stops, commands are refused.
The DIRDRIVE mode is activated after a session in MANU or AUTO mode during which a reference point has been taken. The axis is referenced. Monitoring of soft stops is active.
Overshooting one of these limits causes a stop with an error.
No further movement in DIRDRIVE mode is accepted.
Two types of actions are possible to restart movements: l Cause the loss of the axis reference, after the moving part has completely stopped: l l l unset the channel, %Qxy.i.10 set to 0 (ENABLE) reset the channel, %Qxy.i.10 set to 1 (ENABLE) acknowledge the error (rising edge on the command ACK_DEF,
%Qxy.i.9
l l l l
Force the position of the moving part between the soft stops: switch for a moment to MANU mode acknowledge the error (ACK_DEF) take a forced reference point at a position situated between the l soft stops switch back to DIRDRIVE mode.
Bad recognition of commands in AUTO mode
Symptom
Diagnostics
What to do
In AUTO mode, after overshooting the soft stops of the end of run, movement commands are not carried out correctly.
After overshooting an end of run limit, the only commands accepted are movement commands going back in the direction to return between the end of run limits.
Check whether the movement requested and incorrectly carried out was aiming to bring the moving part back between the end of run limits.
163
Diagnostic and maintenance
164
TLX DS 57 PL7 40E 09.2000
Complementary functions
10
Dimension learning
Introduction
Dimension learning
The following example of a PL7 program supports learning and the use of 16 dimensions.
This chart supports the programming of learning 16 dimensions.
50
51
52 53
TLX DS 57 PL7 40E 09.2000
STEP 50 ACTION ON ACTIVATION
<stores %MW99 with a view to use it as a limit
! %MW98:= %MW99;
<Initialize the index during the learning phase
! %MW99:= -1;
TRANSITION: X50 -> X51
! RE %I2.0
STEP 51 ACTION ON ACTIVATION
<updates the index
! %MW99:= %MW99+1;
165
Complementary functions
<learning of the positions
! %MD200[%MW99]:= %ID7.0;
TRANSITION: X51 -> X52
! %MW99 <= 16
TRANSITION: X51 -> X53
! %MW99 > 16
-TRANSITION: X53 -> X50
! RE %I2.1
TRANSITION: X52 -> X51
! RE %I2.0
TRANSITION: X52 -> X50
! RE %I2.1
166
TLX DS 57 PL7 40E 09.2000
Using dimensions
This chart supports the programming of using dimensions
Complementary functions
42
43
46
STEP 42 ACTION ON ACTIVATION
<initialize %MW97 as execution index
! %MW97:= -1;
TRANSITION: X42 -> X43
! RE %I2.2
STEP 43 ACTION ON ACTIVATION
<increments execution index
! %MW97:= %MW97+1;
<executes the next segment
! SMOVE %CH7.0 (%MW97,%KW8,%KW1,%MD200[%MW97],150000,0);
%KW8: 90 movement to absolute value
%KW1: 09 go to breakpoint
TRANSITION: X43 -> X46
! %I7.0.0 AND (%MW97 < %MW98) AND NOT %I7.0.2
TRANSITION: X43 -> X42
! (%I7.0.1 AND (%MW97 >= %MW98)) OR %I7.0.2
TRANSITION: X46 -> X43
! TRUE
TLX DS 57 PL7 40E 09.2000
167
Complementary functions
168
TLX DS 57 PL7 40E 09.2000
Characteristics and performance
11
Performance characteristics and limitations
At a Glance l l l l
This section describes the performance and characteristics of the step by step control functions: the memory size used by a SMOVE function, the time taken for the execution of step by step control functions, the module cycle time, the characteristics of the low-order value movements,
Size of an
SMOVE function
This table indicates the memory zones used during an SMOVE instruction as well as the corresponding size in number of 16 bit words.
TSX CFY 11
TSX CFY 21
Bit memory
29
58
Additional cost of first configured channel
0
Data zone
390
780
0
Program zone
170
220
2290
Execution time This table details the execution time for functions associated with step by step axes control.
Function description
Acquisition of inputs/outputs from TSX CFY
SMOVE function
READ_STATUS
READ_PARAM
WRITE_PARAM
SAVE_PARAM
Execution time
95 micro-seconds
840 micro-seconds
540 micro-seconds
460 micro-seconds
760 micro-seconds
500 micro-seconds
TLX DS 57 PL7 40E 09.2000
169
Characteristics and performance
Function description
RESTORE_PARAM
Recognition of an adjustment (following a
WRITE_PARAM instruction)
Recognition of the reconfiguration of a channel
Execution time
780 micro-seconds
60 ms for the TSX CFY 11
210 ms for the TSX CFY 21
1.5 s
Note: the module cycle time is 10 ms
Small-sized movement characteristics
A low-order value movement corresponds to a movement that does not enable the speed specified in the instruction to be reached. The speed law resembles a triangle instead of a trapezoid.
l l l
Example of the instruction SMOVE %CH7.1(1, 90, 09, X1, V ,0),
X1 is the position to be reached,
V the cruising speed at which the movement must be made.
note X0, the start position of the moving part.
170
TLX DS 57 PL7 40E 09.2000
TLX DS 57 PL7 40E 09.2000
Characteristics and performance
This table describes the possible scenarios.
If the distance to run is X0 to X1…
Then… is sufficient to reach the specified speed V the movement is executed according to a trapezoidal trajectory. This trajectory reveals the acceleration and deceleration periods equal to t_ACC
V
SS_FREQ t t_ACC t_ACC is insufficient to reach the specified speed V the movement is executed according to a triangular trajectory, the periods of the acceleration and deceleration phases are reduced in proportion to the speed.
V
Vp: programmed speed
Vr : real speed
Vp
Vr t
171
Characteristics and performance
172
TLX DS 57 PL7 40E 09.2000
Application-specific step by step axes control language objects
12
Introduction
Subject of this chapter
What’s in this
Chapter?
This chapter describes the language objects associated to application-specific axes control as well as the different ways of using them.
This Chapter contains the following Maps:
Topic
Introduction to the language objects of the application-specific step by step axes control function
Exchanges between the processor and the axes control module
Introduction to implicit exchanges
Introduction to explicit exchanges
Explicit object exchange and report management
General module data
Internal command data (implicit exchanges)
Internal status data (implicit exchanges)
Internal status data (explicit exchanges)
Adjustment parameters (explicit exchanges)
List of error codes CMD_FLT
Page
173
TLX DS 57 PL7 40E 09.2000
Language objects
Introduction to the language objects of the application-specific step by step axes control function
General Axes control modules configured in a given position automatically generate a group of language objects enabling them to be programmed, and measurement results and diagnostics to be read.
There are two main types of language object: l implicit exchange objects which are automatically exchanged on each cycle revolution of the task associated to the module, l explicit exchange objects, which are exchanged at the request of the application, using explicit exchange instructions.
The former (implicit exchanges) involve images of module input/output: positioning results, software information and commands, necessary for operation.
The latter (explicit exchanges) are used to parameterize the module and provide additional arguments (parameters, commands and information) for advanced programming. They are not essential for normal programming.
174
TLX DS 57 PL7 40E 09.2000
Language objects
Exchanges between the processor and the axes control module
Diagram showing the exchanges
The different exchanges between the processor and the axis control module are as follows:
Processor TSX CFY module
Configuration
Adjustment parameters
WRITE_PARAM (1)
READ_PARAM (1)
SAVE_PARAM (2)
RESTORE_PARAM (2)
Configuration
Adjustment parameters
Saving
Program
PL7
%I %IW
%Q %QW
Status word
%MW
Task
Event
SMOVE
Implicit exchange
READ_STS (1)
EVT
TLX DS 57 PL7 40E 09.2000
175
Language objects
(1) Read or write from the adjustment screen or from the application, using explicit exchange instructions.
(2) Saving or restoring uisng commands Save parameters or Restore parameters from the PL7 Services menu or using the instructions SAVE_PARAM or
RESTORE_PARAM.
176
TLX DS 57 PL7 40E 09.2000
Language objects
Introduction to implicit exchanges
At a Glance
Reminders
Illustration
These objects allow you to access inputs and software information for the application-specific function concerned.
The addressing system for words and bits is given in the Common application-specific functions section.
The images (%I and %IW) of entries to the module are updated in the processor at the beginning of the task cycle, in RUN or STOP mode.
Output commands (%Q and %QW) are updated in the module at the end of the task cycle, only when this is in RUN mode.
xy represents the position of the module, i represents the channel number (counted from 0) in the module.
The diagram below illustrates the operation cycle relating to a PLC task (cyclic execution).
Internal processing
Acquisition of input
RUN STOP
Program processing
Update output
TLX DS 57 PL7 40E 09.2000
177
Language objects
Introduction to explicit exchanges
At a Glance Explicit exchanges are exchanges carried out on request of the program user using instructions: l l l l l l
READ_STS (reading of status words),
WRITE_CMD (writing of command words)
WRITE_PARAM (writing of adjustment parameters),
READ_PARAM (reading of adjustment parameters),
SAVE_PARAM (saving of adjustment parameters),
RESTORE_PARAM (restoring of adjustment parameters),
These exchanges apply to a group of %MW objects that are of the same type (status, command or parameter) on the same channel.
Note: These objects are not essential when programming a application-specific function, but they carry extra information (eg: Type of channel fault…), and supplementary commands (e.g.: positioning and adjustment commands) for more specialized programming of the application.
General principles on the use of the explicit instructions
The diagram below presents the different kinds of explicit exchanges that are possible between the PLC’s processor and the module (or the built-in interface).
PLC processor Application or interface module built-in application
%MWxy.i.r objects
or
%MWxy.MOD.r (1)
Status parameters
READ_STS
Status parameters
Command parameters
WRITE_CMD
Command parameters
Adjustment parameters current
WRITE_PARAM
READ_PARAM
SAVE_PARAM
Adjustment parameters current
Initial adjustment parameters
RESTORE_PARAM
(1) Only with the instructions READ_STS and WRITE_CMD.
178
TLX DS 57 PL7 40E 09.2000
Management of the exchanges
Language objects
During an explicit exchange, it may be interesting to monitor the progress that this makes, in order, for example, not to take into consideration the data read until the exchange has been carried out successfully.
For this, two kinds of information are available: l detecting an exchange in progress (See Explicit exchange operation indicators: l
an end of exchange report (See
Explicit exchange report: %MWxy.i.1, p. 182).
The diagram below describes the principal of the management of an exchange
Execution of an explicit exchange
Detection of an exchange in progress
Report of the end of the exchange
TLX DS 57 PL7 40E 09.2000
179
Language objects
Explicit object exchange and report management
At a Glance
Illustration
When the data is exchanged between the PLC memory and the module, the considl l erations taken by the module may require the running of several task cycles. To manage the exchanges, 2 words are used:
%MWxy.i: Exchange in progress,
%MWxy.i.1: Report.
The illustration below shows the different data bits for managing the exchanges.
Reconfiguration (X15)
Adjustment (X2)
Command (X1)
State (X0)
Status parameters
Command parameters
Adjustment parameters
READ_STS
WRITE_CMD
WRITE_PARAM
READ_PARAM
SAVE_PARAM
RESTORE_PARAM
180
TLX DS 57 PL7 40E 09.2000
Description of the data bits
Language objects
Each of the word bits %MWxy.i and %Mwxy.i.1 is associated with a parameter type: l l l the bits in position 0 are associated with the status parameters: l the bit %Mwxy.i.X0 indicates if a status word read request is in progress, the bits in position 1 are associated with the command parameters: l the bit %Mwxy.i.0:X1 shows whether the command parameters are sent to l channel i of the module, the bit %MWxy.i.1:X1 specifies whether the command parameters are accepted by channel i of the module, the bits in position 2 are associated with the adjustment parameters: l the bit MWxy.i.0:X2 indicates whether the adjustment parameters are exchanged with channel i of the module (by WRITE_PARAM, READ_PARAM, l l
SAVE_PARAM, RESTORE_PARAM), the bit %MWxy.i.1:X2 specifies whether the adjustment parameters are accepted by the module. If the exchange has progressed correctly, the bit changes to 0, the bits in position 15 show a reconfiguration on channel i of the module from the terminal (modification of configuration parameters + cold start of the channel).
Note: The exchange and report words also exist at module level (%MWxy.MOD and %MWxy.MOD.1).
Example Phase 1: Transmitting data with the help of the WRITE_PARAM instruction
PLC memory
Status parameters
Command parameters
1
0
Adjustment parameters
TSX CFY module memory
Status parameters
Command parameters
Adjustment parameters
When the instruction is scanned by the PLC processor, the Exchange in progress bit is set to 1 in %MWxy.
TLX DS 57 PL7 40E 09.2000
181
Language objects
Explicit exchange operation indicators:
%MWxy.i.0
Explicit exchange report:
%MWxy.i.1
Phase 2: Analysis of data by the I/O and report module
PLC memory
Status parameters
Command parameters
0
1
Adjustment parameters
TSX CFY module memory
Status parameters
Command parameters
Adjustment parameters
When the data is exchanged between the PLC memory and the module, the considerations taken by the data module are managed by the bit %MWxy.i.1:X2: Report (0
=correct exchange, 1= unsuccessful exchange).
Note: There are no adjustment parameters at the module level.
The table below shows the meaning of channel exchange check bits EXCH_STS.
1
2
Bit
0
15
Standard symbol
STS_IN_PROGR
Meaning
Channel status word exchange in progress
COMMAND_IN_PROGR Command word exchange in progress
ADJUST_IN_PROGR Adjustment word (parameters) exchange in progress
RECONF_IN_PROGR Channel reconfiguration in progress
The table below shows the meaning of report bits EXCH_ERR.
1
2
Bit
0
15
Standard symbol
STS_READ_ERR
COMMAND_ERR
ADJUST_ERR
RECONF_ERR
Meaning
Failure when reading channel status
Failure when sending a command word
Failure when sending an adjustment word
Failure when reconfiguring the channel
182
TLX DS 57 PL7 40E 09.2000
Language objects
General module data
Fault bit
Status word
%Ixy.MOD.ERR
This bit is updated implicitly
%MWxy.MOD.2:Xj = Standard state word
5
6
1
3
Bit
0
Description
Internal error (module out of action)
Functional error
Module in self-test mode
Hardware or software configuration error
Missing module
This word is updated by an explicit exchange by means of the command
READ_STS % CHxy.MOD.
TLX DS 57 PL7 40E 09.2000
183
Language objects
Internal command data (implicit exchanges)
Output bits
8
9
10
11
12
%Qxy.i.j
= Processor -> TSX CFY
1
2
Bit
0
3
Symbol
DIRDRV
JOG_P
JOG_M
INC_P
Active on
State
State
State
Edge
4
5
6
13
14
15
INC_M
SET_RP
RP_HERE
STOP
ACK_DEF
ENABLE
EXT_EVT
PAUSE
Edge
Edge
Edge
State
Edge
State
Edge
State
BRAKE Edge
BOOST Edge
ACK_STEPFLT State
Description
Movement command in loop control disabled mode
Unlimited manual movement in the + direction
Unlimited manual movement in the - direction
Order for incremental movement (PARAM) in the + direction
Order for incremental movement (PARAM) in the - direction
Manual reference point (RP_POS = source value) or switch to the non-referenced state
Forced reference point of a defined value in PARAM or switch to the referenced state / calculation offset
Immediate stop command
Fault acknowledgment
Confirmation of the axis controller safety relay
Order to trigger an event from the processor
Command to suspend movements at end of the movement in progress
Command to apply brake on the step by step motor
Boost translator
Command to reset translator step monitoring
Mode selector %QWxy.i.0
= MOD_SEL: mode selector
1
2
Value
0
3
Mode
DRV_OFF
DIRDRIVE
MANU
AUTO
Description
Measurement mode: disables CNA output
Loop control disabled mode: direct control in operation
Manual mode
Automatic mode
184
TLX DS 57 PL7 40E 09.2000
Speed modulation
Movement increment
Language objects
%QWxy.i.1
= SMC: speed modulation
Value = speed modulation setpoint value. This setpoint is between 0 and 2, in 1/
1000 increments.
%QDxy.i.2
= PARAM: value of movement increment
TLX DS 57 PL7 40E 09.2000
185
Language objects
Internal status data (implicit exchanges)
Input bits
186
28
29
30
31
25
26
27
22
23
24
19
20
21
16
17
18
11
12
13
14
15
CONF_OK
REF_OK
AX_EVT
HOME
DIRECT
IN_OFF
IN_DIRDR
IN_MANU
IN_AUTO
ST_DIRDR
ST_JOG_P
ST_JOG_M
ST_INC_P
ST_INC_M
ST_SETRP
ON_PAUSE
IM_PAUSE
STEP_FLT
EMG_STOP
EXT_STOP
HD_LMAX
%Ixy.i.j
= TSX CFY -> Processor
5
6
3
4
7
8
1
2
Bit
0
Symbol
NEXT
DONE
AX_FLT
AX_OK
HD_ERR
AX_ERR
CMD_NOK
NOMOTION
AT_PNT
Description
Ready to receive a new movement command (in AUTO mode)
All instructions have been carried out: no instructions in the stack
Error present on the axis
No errors to stop the moving part
Hardware fault present
Application fault present
Command refused
Moving part stationary
Position of the moving part on target (in the window at the point, on instruction with stop)
Axis configured
Reference point taken (axis referenced)
Copy event physical inputs
Copy the CAME physical input of the module’s reference point
Signal the direction of movement, 1 + direction, 0 - direction
Stop mode selected
Direct mode active
Manual mode active
Automatic mode active
DIRDRIVE command active
Unlimited movement in the + direction in progress
Unlimited movement in the - direction in progress
Unlimited incremental movement in the + direction in progress
Unlimited incremental movement in the - direction in progress
Manual reference point in progress
Movement sequencing suspended
Movement suspended (immediate PAUSE)
Loss of step input status
Emergency stop input status
External stop input status
End of run + limit status
TLX DS 57 PL7 40E 09.2000
Language objects
38
39
40
34
35
36
37
Bit
32
33
Symbol
HD_LMIN
ST_BRAKE
ST_BOOST
ST_DRIVE
OVR_EVT
EVT_G07
EVT_G05
TO_G05
EVT_G1X
Description
End of run – limit status
Image of the step by step motor brake output
Image of the BOOST output activity
Translator status
Event overrun
Event source: save position
Event source: end of G05 on event
Event source: G05 timing elapsed
Event source: end of G10 or G11 on event
Other status data %IDxy.i.0
= POS: instant position
%IDxy.i.2
= SPEED: instant speed
%IDxy.i.4
= REMAIN: number of pulses left to run
%IWxy.i.6
= SYNC_N_RUN: number of steps in progress
%IDxy.i.7
= PREF: value of PREF register (only refreshed on activating event processing).
TLX DS 57 PL7 40E 09.2000
187
Language objects
Internal status data (explicit exchanges)
Channel operation status
%MWxy.i.2:Xj = Channel operation status
X6
X7
X8
X9
Bit
X0
X4
X5
Symbol
EXT_FLT
MOD_FLT
CONF_FLT
COM_FLT
APP_FLT
CH_LED_LOW
CH_LED_HIGH
Description
External error (idem HD_ERR bit)
Internal error: module absent, out of order or in self-test mode
Hardware or software configuration error
Communication error with the processor
Application fault (invalid configuration) or command fault
Status of the channel light, there are three scenarios: l l l
X8=X9=0 channel led off
X8=1, X9=0 channel led flashing
X8=0, X9=1 channel led on
Axis operation status
%MWxy.i.3:Xj = Axis operation status
Bit Symbol Description
Hardware faults: %Ixy.i.4 HD_ERR switches to 1 and groups together the faults below
X1
X2
BRAKE_FLT
DRV_FLT
Short-circuit fault on the brake output
Translator fault
X5
X6
EMG_STP
AUX_SUP
Emergency stop fault
24V supply fault
Application faults: %Ixy.i.5 AX_ERR switches to 1 and groups together the faults below
X3 SLMAX Maximum soft stop overshoot
X4 SLMIN Minimum soft stop overshoot
Other status data %MWxy.i.4
= N_RUN: number of steps in progress
%MWxy.i.5
= G9_COD: type of movement in progress
%MWxy.i.6
= G_COD: code of instruction in progress
%MWxy.i.7
= CMD_FLT: refusal report
%MDxy.i.8
= T_XPOS: target of the position to be reached
%MDxy.i.10
= T_SPEED: speed to be reached
Note: all this internal status data is updated on execution of the instruction
READ_PARAM %CHxy.i
188
TLX DS 57 PL7 40E 09.2000
Language objects
Adjustment parameters (explicit exchanges)
Adjustment parameters
%MWxy.i.j
or %MDxy.i.j
Word
%MDxy.i.12
Symbol
ACC
%MDxy.i.14
%MDxy.i.16
%MDxy.i.18
%MDxy.i.20
%MDxy.i.22
%MWxy.i.24
%MWxy.i.25
SL_MAX
SL_MIN
SS_FREQ
MAN_SPD
RP_POS
BRK_DLY1
BRK_DLY2
%MWxy.i.26
STOP_DLY
Description
Acceleration value, dependent on the user-defined unit
High soft stop
Lower soft stop
Start and stop speed 0 to FMAX
Manual mode speed: SS_FREQ to FMAX
Reference point value in manual mode: SLMIN to SLMAX
Shift register to brake deactivation: -1000 to
1000)
Shift register to brake activation: -1000 to
1000)
The duration of the stop stage at the start and stop speed: 0 to 1000)
Note: these adjustment parameters are updated on the execution of a
READ_PARAM %Chxy.i. instruction.
TLX DS 57 PL7 40E 09.2000
189
Language objects
List of error codes CMD_FLT
At a Glance
Configuration parameters
The command refused word CMD_FLT (%MWxy.i.7) is read by explicit change. The messages are also available in non-encrypted format in the diagnostics dialog box, which can be accessed via the commandDIAG.
Each byte of the word CMD_FLT is associated to a type of error: l The most significant byte signals an error in the configuration and adjustment parameters (XX00). l The least significant byte signals a refusal to execute the movement command
(00XX).
For example: CMD_FLT = 0004 (the least significant byte signals an error in the command JOG+)
Mot %MWxy.i.7
Configuration
and adjustment parameters
Most significant byte
Movement command
Least significant byte
These errors are signaled in the most significant byte of the word %MWxy.i.7. The numbers in brackets indicate the hexadecimal value of the code.
Value
2 (2)
3 (3)
4 (4)
5 (5)
Meaning
Reference point configuration error
Event priority configuration error
Maximum frequency configuration error
Maximum acceleration configuration error
Adjustment parameter
These errors are signaled in the most significant byte of the word %MWxy.i.7. The numbers in brackets indicate the hexadecimal value of the code.
Value
7 (07)
8 (08)
9 (09)
10 (0A)
11 (0B)
12 (0C)
13 (0D)
Meaning
Acceleration profile parameter error
Software Hi Limit parameter error
Software Lo limit parameter error
Start and stop frequency parameter error
Frequency parameter error in manual mode
Reference point value parameter error
Delay on deactivation of brake parameter error
190
TLX DS 57 PL7 40E 09.2000
Value
14 (0E)
15 (0F)
32 (20)
Language objects
Meaning
Delay on activation of brake parameter error
Stop stage parameter error
Parameter error, more than one WRITE_PARAM during movement
Movement command refused
TLX DS 57 PL7 40E 09.2000
These errors are signaled in the least significant byte of the word %MWxy.i.7. The numbers in brackets indicate the hexadecimal value of the code.
16 (10)
17 (11)
18 (12)
21 (15)
22 (16)
23 (17)
24 (18)
25 (19)
26 (1A)
27 (1B)
48 (30)
49 (31)
8 (8)
9 (9)
10 (0A)
11 (0B)
12 (0C)
13 (0D)
14 (0E)
15 (0F)
Value
1 (1)
2 (2)
3 (3)
4 (4)
5 (5)
6 (6)
7 (7)
Message
MANU command error insufficient conditions (Mode, Value, etc.)
MANU command error MANU movement in progress
MANU command error simultaneous commands
MANU command error JogP
MANU command error JogM
MANU command error IncP
MANU command error IncM
MANU command error IncP parameter
MANU command error IncM parameter
MANU command error manual RP
MANU command error forced RP
AUTO command error insufficient conditions (parameters)
AUTO command error AUTO movement in progress
SMOVE command error insufficient conditions (Mode)
SMOVE G01 command error (1)
SMOVE G09 command error (1)
SMOVE G10 command error (1)
SMOVE G11 command error (1)
SMOVE G14 command error (1)
SMOVE G05 command error (1)
SMOVE G07 command error (1)
SMOVE G62 command error (1)
SMOVE execution command error
AUTO command error movement in progress
AUTO Command error, stack full
DIRDRIVE command error, insufficient command
DIRDRIVE command error, with mode change in progress
191
Language objects
192
56 (38)
57 (39)
58 (3A)
59 (3B)
60 (3C)
61 (3D)
96 (60)
97 (61)
Value
50 (32)
51 (33)
52 (34)
53 (35)
54 (36)
55 (37)
Message
DIRDRIVE command error, with moving axis
DIRDRIVE command error, with stopped axis
DIRDRIVE command error, with disabled axis
DIRDRIVE command error, with blocking fault
DIRDRIVE command error, with frequency less than SS_FREQ
DIRDRIVE command error, with frequency more than FMAX
DIRDRIVE command error, with axis at the end of run + limit
DIRDRIVE command error, with axis at the end of run - limit
DIRDRIVE command error, with axis outside the end of run + limit
DIRDRIVE command error, with axis outside the end of run - limit
DIRDRIVE command error, with axis outside the Software Hi Limit
DIRDRIVE command error, with axis outside the Software Lo Limit
MANU JogP command error in Software Hi Limit
MANU JogP command error, with stopped axis
101 (65)
102 (66)
MANU JogP command error, JogM movement in progress
MANU JogP command error at the end of run + limit
103 (67) MANU JogP command error position above the end of run + limit
108 (6C) MANU JogP command error blocking fault other than software limit
109 (6D) MANU JogP command error unacknowledged software limit blocking fault
110 (6E) MANU JogP command error, disabled axis
113 (71)
116 (74)
MANU JogM command error, stopped axis
MANU JogM command error, JogP movement in progress
118 (76)
119 (77)
MANU JogM command error at the end of run - limit
MANU JogM command error position above the end of run - limit
124 (7C) MANU JogM command error blocking fault other than software limit
125 (7D) MANU JogM command error unacknowledged software limit blocking fault
126 (7E) MANU JogM command error, disabled axis
127 (7F) MANU JogM command error in Software Lo Limit
130 (82)
131 (83)
132 (84)
133 (85)
134 (86)
135 (87)
MANU IncP command error position less than the Software Lo Limit
MANU IncP command error position more than the Software Hi Limit
MANU IncP command error, JogP movement in progress
MANU IncP command error, JogM movement in progress
MANU IncP command error at the end of run - limit
MANU IncP command error position above the end of run + limit
TLX DS 57 PL7 40E 09.2000
TLX DS 57 PL7 40E 09.2000
Language objects
Value
136 (88)
137 (89)
138 (8A)
141 (8D)
146 (92)
147 (93)
148 (94)
149 (95)
150 (96)
151 (97)
152 (98)
154 (9A)
155 (9B)
158 (9E)
Message
MANU IncP command error, axis not referenced
MANU IncP command error causes movement of the Software Lo Limit
MANU Inc P command error stop condition
MANU IncP command error, disabled axis
MANU IncM command error position less than the Software Lo Limit
MANU IncM command error position above the Software Hi Limit
MANU IncM command error, JogP movement in progress
MANU IncM command error, JogM movement in progress
MANU IncM command error at the end of run - limit
MANU IncM command error position above the end of run + limit
MANU IncM command error, axis not referenced
MANU IncM command error stop condition
MANU IncM command error causes movement of the Software Hi Limit
MANU IncM command error, disabled axis
164 (A4)
165 (A5)
MANU manual RP manual IncP command error, JogP movement in progress
MANU manual PO manual IncM command error, JogM movement in progress
170 (AA) MANU error command manual PO stop condition
174 (AE) MANU command error, manual PO disabled axis
178 (B2)
179 (B3)
180 (B4)
181 (B5)
MANU command error forced RP position less than the Software Lo Limit
MANU command error forced RP position above the Software Hi Limit
MANU command error, forced RP JogP movement in progress
MANU command error, forced RP JogM movement in progress
189 (BD) MANU command error forced RP with unacknowledged software limit error
(1) Indicates that one of the parameters of the SMOVE function does not conform.
Examples: invalid movement type code, position outside the software limits, speed greater than FMAX, …
193
Language objects
194
TLX DS 57 PL7 40E 09.2000
Index
A C
Symbols
Numerics
A
Adjustment
Application
B
Brake output short circuit, 108
C
Configuration
TLX DS 57 PL7 40E 09/200
195
Index
D
Debugging
E
Errors
Example
I
Exchanges
Exemple
External hardware faults, 104, 108
F
G
J
196
TLX DS 57 PL7 40E 09/2000
L
Language objects
Description of instruction codes, 87
Operating modes of a channel, 78
Index
M
N
P
Program
R
Releasing the software limits, 115
Restoring
O
S
Saving
SMOVE
TLX DS 57 PL7 40E 09/2000
197
Index
Switching from RUN to STOP mode, 103
Synchronization of several axes, 97
T
V
X
198
TLX DS 57 PL7 40E 09/2000