Modicon Premium PLCs
TSX 57/PCX 57
Counting, Axis Command, Cam,
Sercos
eng March 2005
2
Document Set
At a Glance This documentation comprises 5 Volumes: l l
Volume 1 l l
Racks/Supply/Processors
Operation/Diagnostics/Maintenance l Standards and operating conditions l Process supply module
Volume 2 l l Discrete interfaces l Safety
Volume 3 l l Counting l Movement command
Volume 4 l l Communication l Bus interface and networks
Volume 5 l l
Analog
Weighing
Document Set
3
Document Set
4
Table of Contents
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Part I
TSX CTY 2A / 4A /2C counting modules . . . . . . . . . . . . 15
Chapter 1
Introduction to the TSX CTY 2A/ 4A /2C counting modules . . 17
Chapter 2
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Down counting function (TSX CTY 2A / 4A modules) . . . . . . . . . . . . . . . . . . . . . 24
Up counting function (TSX CTY 2A / 4A modules) . . . . . . . . . . . . . . . . . . . . . . . 25
Up/down counting function (TSX CTY 2A / 4A modules) . . . . . . . . . . . . . . . . . . 26
Up/down counting and measurement functions (TSX CTY 2C module) . . . . . . . 27
Up/down counting on the TSX CTY 2A/4A modules . . . . . . . . . . . . . . . . . . . . . . 29
Up/down counting on the TSX CTY 2A/4A modules . . . . . . . . . . . . . . . . . . . . . . 32
Up/down counting and measuring on a TSX CTY 2C module . . . . . . . . . . . . . . 40
Connection process for the EPSR "supply feedback" input . . . . . . . . . . . . . . . . 45
Chapter 3
Installing the counting modules . . . . . . . . . . . . . . . . . . . . . . . . 47
Maximum number of counting modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Types of sensor that can be used on counter inputs. . . . . . . . . . . . . . . . . . . . . . 51
Counter input characteristics (TSX CTY 2A / 4A) . . . . . . . . . . . . . . . . . . . . . . . . 53
TSX CTY 2A/4A: Characteristics of use on 5 VDC/24 VDC . . . . . . . . . . . . . . . . 54
Counter input characteristics (TSX CTY 2C). . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
5
6
TSX CTY 2C: Characteristics of use on 5 VDC/24 VDC . . . . . . . . . . . . . . . . . . . 56
Count sensor supply monitor characteristics (encoder or proximity sensor) . . . . 58
Auxiliary input characteristics (preset, confirmation, capture) . . . . . . . . . . . . . . . 59
15-pin SUB-D connectors Standard for a TSX CTY 2A / 4A module. . . . . . . . . . 63
15-pin SUB-D connectors Standard for a TSX CTY 2C module . . . . . . . . . . . . . 66
HE10 20-pin connector of a TSX CTY 2A/4A module . . . . . . . . . . . . . . . . . . . . . 69
20-pin HE10 connector of a TSX CTY 2C module . . . . . . . . . . . . . . . . . . . . . . . 72
Principle for connecting counter proximity sensors . . . . . . . . . . . . . . . . . . . . . . . 75
Connecting counter sensors and their supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Process for connecting encoder count sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Connecting an encoder to a TSX CTY 2A / 4A / 2C module . . . . . . . . . . . . . . . . 81
Example of connecting an incremental encoder with Totem Pole outputs . . . . . 83
Example of connecting an incremental encoder with NPN open
Example of connecting an incremental encoder with PNP open collector outputs87
Example of connecting an absolute encoder with a serial output or parallel outputs,
via ABE-7CPA11 adapted TELEFAST (only TSX CTY 2C module) . . . . . . . . . . 89
Principle for connecting sensors onto auxiliary I/O . . . . . . . . . . . . . . . . . . . . . . . 91
Chapter 4
Appendices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Connecting TELEFAST 2: ABE-7CPA01. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Availability of counting signals on the TELEFAST screw terminal block . . . . . . 101
Correspondence between TELEFAST ABE-7CPA01 terminal block and
TELEFAST 2 connection base: ABE-7H16R20 . . . . . . . . . . . . . . . . . . . . . . . . . 103
Availability of signals on TELEFAST screw terminal block . . . . . . . . . . . . . . . . 104
Correspondence between TELEFAST ABE-7H16R20 terminals and HE10
TELEFAST 2 connection and adaptation base: ABE-7CPA11 . . . . . . . . . . . . . 106
Physical description of the TELEFAST 2: ABE-7CPA11 . . . . . . . . . . . . . . . . . . 107
Characteristics of the TELEFAST base ABE-7CPA11 . . . . . . . . . . . . . . . . . . . 108
Connecting the TELEFAST 2 base: ABE-7CPA11 . . . . . . . . . . . . . . . . . . . . . . 111
Connecting encoders with 10…30 V supply . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Example of the multiplexing of encoders with a 5 V supply. . . . . . . . . . . . . . . . 117
Example of connection: each TSX CTY 2C channel is only connected to one
Example of connection: 2 TELEFAST are connected on the same channel . . 121
Example of connection: 3 TELEFAST are connected on the same channel . . 122
Example of connection: 4 TELEFAST are connected on the same channel . . 124
Overview of the TSX TAP S15•• wiring accessories . . . . . . . . . . . . . . . . . . . . . 134
Mounting and measurements of the TSX TAP S15 05/24 . . . . . . . . . . . . . . . . 135
Connecting an encoder with a TSX TAP S15 05 accessory. . . . . . . . . . . . . . . 137
Connecting an encoder with a TSX TAP S15 24 accessory . . . . . . . . . . . . . . . 138
Part II
TSX CAY axis command modules . . . . . . . . . . . . . . . . 143
Chapter 5
Introduction to the TSX CAY modules . . . . . . . . . . . . . . . . . . 145
Chapter 6
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Chapter 7
Implementing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
7.1
7.2
Connection of terminals with the TELEFAST pre-wiring system. . . . . . . . . . . . 169
Correspondence between the SUB-D connector pins and the TELEFAST
Connecting the variable using the TAP MAS device. . . . . . . . . . . . . . . . . . . . . 173
7.3
7
8
7.4
Information on FRB type 12 pin connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
TSX TAP S15 05 mounting and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Connecting absolute encoder // via a TELEFAST with ABE-7CPA11 adaptation189
Connecting to a NUM MDLA variable speed controller . . . . . . . . . . . . . . . . . . . 190
7.5
Connection of sensors/ pre-actuator and supply modules, without variable
TELEFAST connection and wiring accessories . . . . . . . . . . . . . . . . . . . . . . . . . 194
Example of connecting sensors to the auxiliary inputs and their supply.. . . . . . 196
Correspondence between TELEFAST terminal blocks and module
Connection using TSX CDP 301 or 501 strips. . . . . . . . . . . . . . . . . . . . . . . . . . 199
7.6
Connecting the variable speed controller signals . . . . . . . . . . . . . . . . . . . . . . . 202
Connection using the TELEFAST pre-wiring system. . . . . . . . . . . . . . . . . . . . . 205
Correspondence between TELEFAST terminals and HE10 connector . . . . . . 206
7.7
Characteristics of the variable speed controller inputs . . . . . . . . . . . . . . . . . . . 218
Chapter 8
Appendices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Compatibility of the absolute encoders with the TSX CAY modules . . . . . . . . . 221
Part III
Step by step axis command . . . . . . . . . . . . . . . . . . . . . 223
Chapter 9
Introduction to step by step axis command . . . . . . . . . . . . . 225
Chapter 10
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
10.1
10.2
Connection to a translator with RS 422/485 interface . . . . . . . . . . . . . . . . . . . . 240
Connecting to a translator with NPN open collector interface . . . . . . . . . . . . . . 241
10.3
Connecting sensors/pre-actuators and supply modules . . . . . . . . . . . . . . . . . . 242
Connecting auxiliary inputs and outputs to processor. . . . . . . . . . . . . . . . . . . . 245
Connection using a TSX CDP 301/501 pre-wired strand . . . . . . . . . . . . . . . . . 248
Connection with TELEFAST pre-wiring system . . . . . . . . . . . . . . . . . . . . . . . . 250
Correspondence between TELEFAST terminals and HE10 connector . . . . . . 252
10.4
Characteristics of translator inputs (SUB-D connector). . . . . . . . . . . . . . . . . . . 258
Characteristics of translator outputs (SUB-D connector) . . . . . . . . . . . . . . . . . 259
Characteristics of auxiliary inputs (HE10 connector). . . . . . . . . . . . . . . . . . . . . 260
Chapter 11
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
Translators compatible with TSX CFY 11/21 . . . . . . . . . . . . . . . . . . . . . . . . . . 266
Connection of Phytron translators with TSX CFY 11/21 modules. . . . . . . . . . . 267
9
10
Part IV
TSX CCY 1128 Cam module . . . . . . . . . . . . . . . . . . . . . . 269
Chapter 12
Introduction to the TSX CCY 1128 electronic cam module . 271
Introduction to the TSX CCY 1128 in its environment . . . . . . . . . . . . . . . . . . . . 272
Physical introduction of the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Electronic cam function of the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . 275
TSX CCY 1128 compatibility with the installed base . . . . . . . . . . . . . . . . . . . . . 276
Chapter 13 General instructions for installing the TSX CCY 1128
module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Installing the TSX CCY 1128 in a PLC station rack . . . . . . . . . . . . . . . . . . . . . . 278
Installing the TSX CCY 1128 in a PLC station. . . . . . . . . . . . . . . . . . . . . . . . . . 279
Number of application-specific channels managed by one PLC station . . . . . . 281
Installation precautions for the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . 282
Selecting and protecting auxiliary power supplies . . . . . . . . . . . . . . . . . . . . . . . 284
Choice of encoders for the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Chapter 14 Connecting an incremental and absolute SSI encoder
to the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Principles for connecting an encoder to a TSX CCY 1128 . . . . . . . . . . . . . . . . 288
Connecting an incremental encoder with RS422 outputs to the TSX CCY 1128289
Connecting an incremental encoder with Totem Pole outputs to the
Connecting an absolute SSI encoder to the TSX CCY 1128. . . . . . . . . . . . . . . 295
Connecting an encoder supply monitor to the TSX CCY 1128 . . . . . . . . . . . . . 298
Connecting the encoder supply to the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . 300
TSX TAP S1505/S1524 and TSX CCP S15• connection accessories . . . . . . . 304
Chapter 15 Connecting the auxiliary inputs and track outputs of the
TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 309
Introduction to the connection interfaces of the TSX CCY 1128 . . . . . . . . . . . . 310
Connecting the auxiliary inputs of the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . 313
Connecting the track outputs of the TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . 321
Chapter 16
TSX CCY 1128 module displays . . . . . . . . . . . . . . . . . . . . . . . 329
Introduction to the display block of the TSX CCY 1128 module . . . . . . . . . . . . 330
The various states of the LEDs on the TSX CCY 1128 and their meaning . . . 331
Chapter 17
TSX CCY 1128 module electrical characteristics . . . . . . . . . 333
General electrical characteristics of the TSX CCY 1128. . . . . . . . . . . . . . . . . . 334
Characteristics of the auxiliary inputs of the TSX CCY 1128 . . . . . . . . . . . . . . 335
Characteristics of the encoder supply feedback monitor for the TSX CCY 1128336
Characteristics of the auxiliary inputs of the TSX CCY 1128 . . . . . . . . . . . . . . 337
Characteristics of the track outputs of the TSX CCY 1128 . . . . . . . . . . . . . . . . 338
Chapter 18 Connecting an absolute encoder with parallel outputs to
TSX CCY 1128 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Principle for connecting an absolute encoder to a TSX CCY 1128. . . . . . . . . . 340
Pinout configuration of the 15-pin SUB-D connectors of the module and the
Connecting an absolute encoder with parallel outputs . . . . . . . . . . . . . . . . . . . 346
Wiring rules and precautions specific to the TELEFAST. . . . . . . . . . . . . . . . . . 349
Configuration of the TELEFAST connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353
Part V
SERCOS® TSX CSY 84 / 164 Modules . . . . . . . . . . . . . 355
Chapter 19
Presentation of the TSX CSY 84 / 164 modules . . . . . . . . . . . 357
Presentation of the modules in their environment . . . . . . . . . . . . . . . . . . . . . . . 358
Chapter 20
Installing the modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363
Mounting the modules in a PLC station rack. . . . . . . . . . . . . . . . . . . . . . . . . . . 364
Number of application-specific channels managed by a TSX CSY 84 or
Operating mode of the TSX CSY 84/164 modules . . . . . . . . . . . . . . . . . . . . . . 373
Chapter 21
Description of the multi-axis control system . . . . . . . . . . . . . 375
SERCOS® multi-axis control system on Premium PLCs . . . . . . . . . . . . . . . . . 376
11
12
Chapter 22
Fiber optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
Chapter 23
Characteristics, Standards and service conditions . . . . . . . 387
Characteristics of the SERCOS® network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 389
Chapter 24
Compatible variable speed controllers . . . . . . . . . . . . . . . . . 391
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 393
About the Book
At a Glance
Document Scope This manual introduces the installation for counting, axis command, Cam and l l l l l
Sercos modules.
It comprises 5 parts:
TSX CTY 2A / 4A / 2C counting module,
TSX CAY axis command module,
Step by step axis command,
TSX CCY 1228 Cam module,
Sercos.
User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected]
13
About the Book
14
TSX CTY 2A / 4A /2C counting modules
I
At a Glance
Subject of this part
What's in this
Part?
This Part deals with the installation of TSX CTY 2A / 4A / 2C counting modules.
This part contains the following chapters:
Chapter
1
2
3
4
Chapter Name
Introduction to the TSX CTY 2A/ 4A /2C counting modules
Page
Installing the counting modules
Appendices
15
TSX CTY 2A / 4A /2C counting modules
16
Introduction to the
TSX CTY 2A/ 4A /2C counting modules
1
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter introduces the different TSX CTY 2A / 4A / 2C counting modules.
This chapter contains the following topics:
Topic
General
Physical description
Page
17
Introduction
General
Introduction The TSX CTY 2A, TSX CTY 4A and TSX CTY 2C modules are standard format counting modules. They are used to count pulses from a sensor with a maximum frequency of 40 kHz (CTY 2A/4A) or 1 MHz (CTY 2C).
Installation of counting modules
The counting modules can be installed in any available slot of a Premium PLC configuration (TSX or PCX), on the condition that the following are used to the l l maximum:
8 "application-specific" channels in a TSX P57 103/PCX 57 203 configuration,
24 "application-specific" channels in a TSX P57 2•3/PCX 57 203/TSX P57 2•23 configuration, l 32 "application-specific" channels in a TSX P57 3•3/PCX 57,353/TSX P57 3623 configuration, l 48 "application-specific" channels in a TSX P57 453/ TSX P57 4823 configuration.
The only difference between the TSX CTY 2A and TSX CTY 4A modules is their number of channels (2 for the TSX CTY 2A and 4 for the TSX CTY 4A). They are used for upcounting, downcounting, or up/down counting functions for each channel.
The TSX CTY 2C module (2 channels) is used for the counting up/down functions, and measurements in normal or modulo mode.
Sensors used on the channels l l
The sensor used on each channel can be: l a 2 or 3-wire proximity sensor, type PNP or NPN. When using a mechanical l contact output, it is necessary to raise the channel’s immunity in order to curb the closing bounces of the contact, an incremental signal encoder with 5 VDC differential outputs (encoder with
RS 422/485 line transmitters), an incremental signal encoder with 10-30 VDC output (Totem Pole encoder), an absolute encoder with serial outputs, standard RS 485 interface (TSX CTY 2C l only), an absolute encoder with parallel outputs, using the adaption TELEFAST:
ABE-7CPA11 (TSX CTY 2C only).
18
Illustration This diagram shows the different sensor types:
Modules
TSX CTY 2A / 4A incremental encoder proximity sensor absolute encoder with serial output
Introduction absolute encoder with parallel outputs
TELEFAST ABE-7CPA11
Module
TSX CTY 2C
19
Introduction
Physical description
Illustration This diagram illustrates the TSX CTY 2A / 4A / 2C counting modules:
TSX CTY 2A TSX CTY 4A TSX CTY 2C
20
Number table
Introduction
This table describes the modules according to the different numbers in the diagrams above:
3
4
Number Description
1 Standard SUB D 15-pin connector for connecting: l l l the relevant count sensor(s) to channels 0 and 1 for the TSX CTY 2A/2C modules, and to channels 0, 1, 2 and 3 for the TSX CTY 4A module, the encoder supply when using this type of sensor, the return encoder supply, which is used to check that the encoder is receiving the correct supply.
2
5 l l
HE10 20-pin connectors, used for each channel to connect: l auxiliary inputs: l reset to 0 or set to the preset value, l l count confirmation, capture, of auxiliary outputs, external supplies: l l auxiliary input and output supply, supply of other sensors.
Screw for fixing module in place.
Rigid body, which guarantees: l l electromagnetic card support, locking of the module in its slot.
Module diagnostic LEDs: l module level diagnostics: l green RUN LED: indicates the operating mode of the module (operative l module), red ERR LED: indicates the internal state of the module (internal error, l l module broken down), red I/O LED: indicates an external error or application fault, module channel level diagnostics: l green CHx LED: indicates channel diagnostics.
- LED on: channel active,
- flashing LED: channel inactive,
- LED off: channel inoperative, not configured or incorrectly configured.
21
Introduction
22
Functions
2
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter introduces the various functions of the TSX CTY 2A / 4A / 2C modules.
This chapter contains the following topics:
Topic
Down counting function (TSX CTY 2A / 4A modules)
Up counting function (TSX CTY 2A / 4A modules)
Up/down counting function (TSX CTY 2A / 4A modules)
Up/down counting and measurement functions (TSX CTY 2C module)
Up/down counting on the TSX CTY 2A/4A modules
Process diagram
Up/down counting on the TSX CTY 2A/4A modules
Process diagram 1
Process diagram 2
Process diagram 3
Process diagram 4
Up/down counting and measuring on a TSX CTY 2C module
Process diagram 5
Connection process for the EPSR "supply feedback" input
Page
23
Functions
Down counting function (TSX CTY 2A / 4A modules)
General
Illustration
The down counting function allows pulses to be counted down (on 24 bits + sign) from a preset value between 0 and +16777215, and indicates when the current value is equal to or less than 0.
The format for down counting is between –16777216 and +16777215.
diagram of the principle: valid downcounting space current value measurement ≤ 0 preset with automatic preset
Note: Operation of the down counting function, the associated language objects, and the software installation are all described in the application manual.
24
Functions
Up counting function (TSX CTY 2A / 4A modules)
General
Illustration
The up counting function counts pulses (on 24 bits + sign) from 0 to a predefined value known as the setpoint value.
The format for up counting is between 0 and +16777215.
The module indicates when the setpoint value has been reached.
The current count value is constantly compared to two adjustable thresholds
(threshold 0 and threshold 1).
Diagram of the principle: valid counting space current value measurement ≤ setpoint value current value measurement ≤ threshold value 1 current value measurement ≤ threshold value 0 threshold 0 threshold 1 setpoint with automatic reset to 0
Note: Operation of the up counting function, the associated language objects, and the software installation are all described in the application manual.
25
Functions
Up/down counting function (TSX CTY 2A / 4A modules)
General The up/down counting function uses one counter to execute both the up counting and down counting of pulses (on 24 bits + sign), from a preset value between
–16777216 and +16777215.
l l
This function also offers the possibility of setting several values, which cause an alert when the current value passes them, which could in turn trigger event processing: a low setpoint and a high setpoint,
2 adjustable thresholds (thresholds 0 and 1).
Illustration of the up/down counting mode
Diagram of the principle: valid upcounting/downcounting space current value ≤ with high setpoint current value
≤
threshold 1 current value ≤ threshold 0 current value ≤ low setpoint low setpoint preset threshold 0 threshold 1 high setpoint
Note: Operation of the up/down counting function, the associated language objects, and the software installation are all described in the application manual.
26
Functions
Up/down counting and measurement functions (TSX CTY 2C module)
Up/down counting function
The up/down counting function uses one counter to execute both the up counting and down counting of pulses (on 24 bits + sign), from a preset value between
–16777216 and +16777215.
Measurement function
The measurement function is used to acquire a serial frame from an absolute encoder with serial outputs.
Illustration of the up/down counting mode
Diagram of the principle: valid upcounting/downcounting space current value ≤ threshold 1 current value ≤ threshold 0
Modulo mode preset threshold 0 threshold 1
The modulo mode enables up/down counting (on 25 bits) between 0 and
+33554431.
27
Functions
Illustration of modulo mode
Diagram of the principle: up/down counting space current value ≤ threshold 0 current value ≤ threshold 1 preset threshold 0 threshold 1
Note: The up/down counting and measurement functions also offer the possibility of setting two thresholds (thresholds 0 and 1). If the current value crosses these thresholds, this will be signaled, and will trigger event processing.
Note: Operation of the up/down counting and measurement functions, the associated language objects, and the software installation are all described in the application manual.
28
Functions
Up/down counting on the TSX CTY 2A/4A modules
Introduction The TSX CTY 2A/4A counting modules are used to enable: l l
2 independent up or down counting channels (module TSX CTY 2A),
4 independent up or down counting channels (module TSX CTY 4A).
Up/down counting signals
The relevant up/down counting signals for a channel, as well as the encoder supply
(when the sensor is an incremental encoder) are grouped together on a standard
SUB D 15-pin connector. Each up/down counting channel is able to receive 5 VDC or 24 VDC signals. Pulses are received on the IA input.
Auxiliary inputs 24 VDC auxiliary inputs (reset to 0: for up counting, set to the preset value for down counting and for confirmation of up/down counting), as well as the external supplies, are grouped together on a HE10 connector, shared by channels 0 and 1, or 2 and 3
(TSX CTY 4A only).
l l
Reset to 0 (up counting) or preset value (down counting)
Resetting to zero (up counting) or setting to the preset value (down counting) can be carried out in one of the ways described below: l by changing the state (rising or falling edge) of the IPress• input (down counting) or the IReset input (up counting), according to the choice made during configuration, l by crossing the setpoint value (up counting) or 0 (down counting), l via software,
Up/down counting enable l l
The up/down count can be enabled as follows: by setting the IVal input to 1, via software.
Note: For more information on these functions, refer to the application manual.
Line check input:
EPSR
This input is connected to the "return supply" output of an incremental encoder to ensure that the supply is correct.
In case of a line break on the cable carrying the encoder supply voltage, the fault generated is indicated and can be dealt with using the application program.
29
Functions
Counter outputs The up counting and down counting functions include counter outputs, which can be assigned, using the program, to 2 physical reflex outputs (Q0 and Q1), located on the counting modules: l down counting function: offers one counter output with predefined conditions for activation and deactivation: l l activated when the current value changes to 0, l deactivated when the down counter reaches the preset value.
up counting function: offers two counter outputs, the activation and deactivation conditions of which are predefined for counter output 0, and configurable for counter output 1: l Counter output 0
- activated when it passes the setpoint value,
- deactivated when the counter is reset to 0.
l Counter output 1
- activation and deactivation are configurable in the adjustment screen.
Physical outputs Physical outputs Q0 and Q1 can be controlled as follows: l in automatic mode: if the physical output is enabled, the state of the counter output is also applied to the physical output (counter output 0 controls physical output 0, counter output 1 controls physical output 1). If the physical output is not l enabled, it is set at 0, in manual mode: the state of the physical output is controlled manually.
Note: For more information on the installation of the counter outputs and physical outputs, refer to the application manual.
30
Functions
Process diagram
Illustration The 15-pin SUB-D connector is used to wire one single counting channel (e.g. channel 0), while the HE10 connector is shared by 2 channels ( e.g. channels 0 and
1). Other channels or pairs of channels are wired in exactly the same way.
Standard 15-pin SUB-D connector to link up counting sensor
Input pulses for up/down counting
Supply reserved exclusively to supply an encoder
(external supply report connected to HE10 connector).
Encoder return supply encoder
(must be connected)
Encoder supply
5 VDC or 10...30 VDC
Channel 0 preset input
Enable input channel 0
Channel 1 preset input
Enable input channel 1
Physical reflex outputs channel 0
Physical reflex outputs channel 1
24 VDC auxiliary input sensor supply
Auxiliary inputs
HE10 connector to connect the supply
(encoders and sensors), the auxiliary inputs
(preset, enable, etc.) and the reflex outputs
31
Functions
Up/down counting on the TSX CTY 2A/4A modules
Introduction l l
The TSX CTY 2A/4A counting modules are used to enable:
2 independent up/down counting channels (TSX CTY 2A),
4 independent up/down counting channels for the TSX CTY 4A module.
Up/down counting signals
Up/down counting on one channel can occur in many ways: l using one physical input for up counting and one for down counting. The pulses for up counting are received at the IA input, and the pulses for down counting at the IB input.
Note: All pulses at the IA and IB inputs are counted, whatever the synchronism of the signals.
l using one physical input for up/down counting and one for the count direction (up counting or down counting). Pulses for up/down counting are received at the IA input and the direction (up counting or down counting) is determined by the state of the IB input (up counting for state 0, down counting for state 1),
Note: During up counting, the pulses at the IA input are only counted if the IB input has been at 1 for more than 3 µ s.
During down counting, the pulses at the IA input are not counted if the IB input has been set at 0 for more than 3 µ s.
l l using one physical input for up/down counting, and the application to determine the direction (the 0 or 1 setting of a bit). Pulses for up/down counting are received at the IA input, using two physical entries with signals out-of-phase by π /2 (incremental encoder signals). Counting signal A is received at the IA input, and counting signal B at the IB input,
32
Functions
Auxiliary inputs The 24 VDC auxiliary inputs and the external supplies are grouped together using a
HE10 connector, shared by two channels: Channels 0 and 1 or 2 and 3
(TSX CTY 4A only). The connector comprises the following signals: preset value setting IPres , up/down counting confirmation IVal , capture of the current value
ICapt .
l Preset the preset can be performed in any of the ways described below: l l when changing the state (rising or falling edge) of the IPres• input and the software confirmation, on the rising edge of the IPres• input if the counting direction is positive or on the IPres• falling edge if the count direction is negative, with software confirmation, counting direction counting direction
Physical input IPres• l on the rising edge of the IPres• input if the direction is down counting (negative) or on the falling edge of the IPres• input if the count direction is positive, with software confirmation, counting direction counting direction
Physical input IPres• l l when the IPres• input is in state 1, with software confirmation. The current value will not change while the input is in state 1, at reference point short cam: the preset is taken into account:
- if the direction is up counting (positive): the IPres• input is in state 1 and the rising edge of the IZ input is top-turn, with software confirmation,
- if the direction is down counting (negative): the IPres• input is in state 1 and the falling edge of the IZ input is top-turn, with software confirmation, counting direction counting direction
Physical input IPres•
Top-turn input IZ
Preset Preset
33
Functions l
Comment
In theory, as the short cam is lower than an incremental encoder turn, the topturn only happens once in the cam.
If however several encoder turns occur in the cam, the last active edge of the top-turn signal triggers a preset.
at reference point long cam: the inclusion of the preset occurs on the first rising edge of the IZ top-turn input after the IPres• input has reached state 0, in an ascending or descending direction, and with software confirmation, counting direction counting direction
Physical input IPres•
Top-turn input IZ
Preset Preset l l l directly, using the software.
Up/down counting confirmation
The confirmation of up counting or down counting occurs in any of the ways described below: l by setting the IVal input to 1, l directly, using the software.
Capture
The capture of the current value occurs in any of the ways described below: l l when changing the state (rising or falling edge) of the ICapt input, with software confirmation, directly, using the software.
Note: For more information on these functions, refer to the application manual.
Line check input:
EPSR
This input, which is normally connected to the "supply feedback" output of an encoder is used to control the encoder supply and ensure that it is correct.
In case of a line break on the cable carrying the encoder supply voltage, the error generated is indicated and can be dealt with using the application program.
Counter outputs The up/down counting function comprises two counter outputs, which can be assigned, using the program, to the physical reflex outputs (Q0 and Q1), located on the counter module.
These two counter outputs have conditions for their activation and deactivation, which are defined by the user using an encoding matrix, accessible in the adjustment function.
34
Functions
Physical outputs Physical outputs Q0 and Q1 can be controlled as follows: l in automatic mode: if the physical output is enabled, the state of the counter output is also applied to the physical output (counter output 0 controls output Q0, counter output 1 controls output Q1).
If the physical output is not enabled, it is set to 0.
l in manual mode: the state of the physical output is controlled manually.
Note: For more information on the installation of the counter outputs and physical outputs, refer to the application manual.
Note: The diagrams on the following pages show the cabling process for a 15-pin
SUB-D connector (one channel). Cabling is identical for the other channels.
The HE10 connector does not appear in process diagrams 2 to 4, as its cabling is identical to that shown in process diagram 1.
35
Functions
Process diagram 1
Illustration Using a physical up/down counting input, and determining the direction (up counting or down counting) with the application.
Standard 15-pin SUB-D connector to link up counting sensor
Input pulses for up/down counting
Supply reserved exclusively to supply an encoder (external supply report connected to HE10 connector).
Encoder return supply encoder
(must be connected)
Encoder supply
5 VDC or 10...30 VDC according to encoder type
Channel 0 preset input
Enable input channel 0
Channel 0 capture input
Channel 1 preset input
Enable input channel 1
Channel 1 capture input
Physical reflex outputs channel 0
Physical reflex outputs channel 1
24 VDC auxiliary input sensor supply
Auxiliary inputs
HE10 connector to connect the supply
(encoders and sensors), the auxiliary inputs
(preset, enable, etc.) and the reflex outputs
36
Functions
Process diagram 2
Illustration Using one physical input for up/down counting and one for the count direction
(up counting or down counting).
Standard 15-pin SUB-D connector to connect counting sensor
Input pulses for up/down counting up counting
Counting input
(up/down counting) down counting
Top-turn input
Supply reserved exclusively for supply to an encoder
(external supply transfer connected to HE10 connector).
Encoder return supply signal
(must be connected)
HE10 connector
37
Functions
Process diagram 3
Illustration Using one physical input for up counting and one for down counting.
Standard 15-pin SUB-D connector to connect counting sensor
Up counting pulse input
Down counting pulse input
Counting input
(up/down counting)
Top-turn input
Supply reserved exclusively for supply to an encoder
(external supply transfer connected to HE10 connector).
Encoder return supply signal
(must be connected)
HE10 connector
38
Functions
Process diagram 4
General Using two physical inputs to cable one incremental encoder with signals out-ofphase by π /2. The option to multiply by 4 improves the resolution of the encoder : l multiplying by 1: up/down counting occurs at the rising edges of the IB input, l multiplying by 4: up/down counting occurs on all rising and falling edges of both
IA and IB inputs.
Illustration:
Standard 15-pin SUB-D connector to link up counting sensor
Signal A input
Signal B input
Top-turn input
Supply reserved exclusively to supply an encoder
(external supply report connected to HE10 connector).
Encoder return supply encoder
(must be connected)
HE10 connector
39
Functions
Up/down counting and measuring on a TSX CTY 2C module
Introduction
Up/down counting
(mechanical contacts, proximity sensor, pulse generators, incremental encoders)
Measurement
(absolute encoders)
The TSX CTY 2C counter module is used to enable 2 independent up/down counting and measuring channels (absolute encoder interface).
Up/down counting on one channel can be performed in many ways: l using one physical input for up counting and one for down counting. The up counting pulses are received at the IA input, and the down counting pulses at the l
IB input.
using one physical input for up/down counting and one for the direction (up counting or down counting). Up/down counting pulses are received at the IA input l and the direction (up counting or down counting) is determined by the status of the IB input (up counting for state 0, down counting for state 1), using one physical input for up/down counting, and the application to determine l the direction (setting the bit to 0 or 1). Up/down counting pulses for are received at the IA input.
The maximum frequency of up/down counting on each channel is 1MHz, using two physical entries with signals out-of-phase by π /2 (incremental encoder signals). Counting signal A is received at the IA input, and counting signal B at the IB input,
The maximum frequency of out-of-phase signals is 500kHz (multiplied by 1) or
250kHz (multiplied by 4).
Using one physical input for receiving series data (signals from an absolute encoder with series outputs) and one for sending the transmission clock to the encoder.
40
Functions
Auxiliary inputs The 24 VDC auxiliary inputs and the external supplies are grouped together using a
HE10 connector, shared by two channels. The connector comprises the following signals: preset value setting IPres , up/down counting confirmation IVal , capture of the current value ICapt .
l Preset the preset can be performed in any of the ways described below: l when changing the state (rising or falling edge) of the IPres• input and the l software confirmation, on the rising edge of the IPres• input if the counting direction is positive or on the IPres• falling edge if the count direction is negative, with software confirmation, counting direction counting direction
Physical input IPres• l on the rising edge of the IPres• input if the direction is down counting (negative) or on the falling edge of the IPres• input if the count direction is positive, with software confirmation, counting direction counting direction
Physical input IPres• l l when the IPres• input is in state 1, with software confirmation. The current value will not change while the input is in state 1, at reference point short cam: the preset is taken into account:
- if the direction is up counting (positive): the IPres• input is in state 1 and the rising edge of the IZ input is top-turn, with software confirmation,
- if the direction is down counting (negative): the IPres• input is in state 1 and the falling edge of the IZ input is top-turn, with software confirmation, counting direction counting direction
Physical input IPres•
Top-turn input IZ
Preset Preset
41
Functions l
Comment
In theory, as the short cam is lower than an incremental encoder turn, the topturn only happens once in the cam.
If however several encoder turns occur in the cam, the last active edge of the top-turn signal triggers a preset.
at reference point long cam: the inclusion of the preset occurs on the first rising edge of the IZ top-turn input after the IPres• input has reached state 0, in an ascending or descending direction, and with software confirmation, counting direction counting direction
Physical input IPres•
Top-turn input IZ
Preset Preset l l l directly, using the software.
Up/down counting confirmation
Up counting or down counting is confirmed in any of the ways described below: l by setting the IVal input to 1, l directly, using the software.
Capture
The capture of the current value is performed in any of the ways described below: l when changing the state (rising or falling edge) of the ICapt input, with software confirmation, l directly, using the software.
Note: For more information on these functions, refer to the application manual.
Line check input:
EPSR
This input, which is normally connected to the "supply feedback" output of an incremental encoder is used to monitor the encoder supply and ensure that it is correct.
In case of a short circuit or line break on the cable carrying the encoder supply voltage, the fault generated is indicated and can be dealt with using the application program.
Counter outputs The up/down counting function comprises two counter outputs, which can be assigned to two physical reflex outputs (Q0 and Q1), located on the counter module.
These two counter outputs have conditions for their activation and deactivation, which are defined by the user using an encoding matrix (30 possible combinations), accessible in the adjustment function.
42
Functions
Physical outputs Each channel of the TSX CTY2C module has 4 physical outputs - Q0 and Q3.
l l
Physical outputs Q0 and Q1, which are identical to those of the TSX CTY 2A or
TSX CTY 4A modules, can be controlled as follows: l in automatic mode: if the physical output is enabled, the state of the counter output is also applied to the physical output (counter output 0 controls output Q0, counter output 1 controls output Q1).
If the physical output is not enabled, it is set to 0.
in manual mode: the state of the physical output is controlled manually.
the output Q2 can only be controlled in manual mode.
The Q3 output is a configurable input/output. It can be used in programmable frequency mode, in order to provide an external synchronization loop on several channels of several counter modules.
When using an absolute encoder(s) with parallel outputs, with a TELEFAST
ABE-7CPA11 adapter, it is possible to use the Q2 and Q3 outputs as discrete outputs, which are used to address this (these) encoder(s).
Note: For more information on the installation of the counter outputs and physical outputs, refer to the application manual.
Note: The diagrams showing the cabling process for a 15-pin SUB-D connector
(one channel) are identical to those for up/down counting with a TSX CTY 2A/4A module (process diagrams 1 to 4). These diagrams are completed by process diagram 5 (below), which includes cabling for an absolute encoder with series outputs, or with parallel outputs, using a TELEFAST ABE-7CPA11 adapter.
43
Functions
Process diagram 5
Illustration Using one physical input to receive serial data and one to send data from the encoder transmission clock to the absolute SSI encoder.
Standard 15-pin SUB-D connector to link up counting sensor
Serial data inputs
Serial transmission clock output.
Supply reserved exclusively for supply to an encoder (external supply transfer connected to HE10 connector)
Encoder return supply signal (must be connected)
Absolute encoder supply
5 VDC or 10...30 VDC according to encoder type
Encoder reference voltage 10…30
VDC
Channel 0 preset input
Channel 0 enable input/output Q2
Channel 0 capture input
Channel 0 Q3 output
Channel 1 preset input
Channel 1 enable input/output Q2
Channel 1 capture input
Channel 1 Q3 output
Channel 0 physical reflex outputs
Channel 1 physical reflex outputs
Sensor supply of 24 VDC auxiliary inputs
HE10 connector to connect thesupplies (encoders and sensors),
the auxiliary inputs (reset, enable etc.)and the reflex outputs.
44
Connection process for the EPSR "supply feedback" input
Introduction This input must be connected.
The connection method of this input depends on the encoder type used.
Incremental encoder with a
"supply feedback" output the EPSR input is connected to the encoder’s "supply feedback" output:
Functions
Encoder standard 15-pin SUB-D
Absolute encoder with serial outputs and an encoder
"supply feedback" output the EPSR input is connected to the encoder’s "supply feedback" output:
Encoder standard 15-pin SUB-D
Incremental encoder with no
"return supply" output the EPSR input is connected to the + encoder supply at the encoder:
Encoder standard 15-pin SUB-D
45
Functions
Absolute encoder with serial outputs with no "supply feedback" output the EPSR input is connected to the + encoder supply at the encoder:
Encoder standard 15-pin SUB-D
Inductive proximity sensor l l the EPSR input is connected to the + supply of the count sensors, the –0 VDC output is connected to the - supply of the count sensors.
Illustration:
Encoder standard 15-pin SUB-D
Comment
If the sensor is not equipped with a "supply feedback" output, it is possible not to cable the EPSR input of a TSX CTY 2C module. In this case, it is recommended to hide the "encoder supply or proximity sensor" fault.
Note: For more information on these functions, refer to the application manual.
46
Installing the counting modules
3
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter deals with the installation of TSX CTY 2A / 4A / 2C counting modules.
This chapter contains the following topics:
Topic
Maximum number of counting modules
Types of sensor that can be used on counter inputs
General counting module characteristics
Counter input characteristics (TSX CTY 2A / 4A)
TSX CTY 2A/4A: Characteristics of use on 5 VDC/24 VDC
Counter input characteristics (TSX CTY 2C)
TSX CTY 2C: Characteristics of use on 5 VDC/24 VDC
Compatibility of IA, IB and IZ inputs
Count sensor supply monitor characteristics (encoder or proximity sensor)
Auxiliary input characteristics (preset, confirmation, capture)
Auxiliary output characteristics
15-pin SUB-D connectors Standard for a TSX CTY 2A / 4A module
15-pin SUB-D connectors Standard for a TSX CTY 2C module
HE10 20-pin connector of a TSX CTY 2A/4A module
20-pin HE10 connector of a TSX CTY 2C module
Principle for connecting counter proximity sensors
Connecting counter sensors and their supply
Wiring precautions
Process for connecting encoder count sensors
Connecting an encoder to a TSX CTY 2A / 4A / 2C module
Page
47
Installing the counting modules
Topic
Example of connecting an incremental encoder with Totem Pole outputs
Example of connecting an incremental encoder with NPN open collector outputs.
Example of connecting an incremental encoder with PNP open collector outputs
Example of connecting an absolute encoder with a serial output or parallel outputs, via ABE-7CPA11 adapted TELEFAST (only TSX CTY 2C module)
Principle for connecting sensors onto auxiliary I/O
Connecting sensors and their supply
General rules for implementation
Page
48
Installing the counting modules
Maximum number of counting modules
Introduction The TSX CTY 2A/4A/2C counting modules can be installed in any available slot of a Premium PLC configuration (TSX or PCX), providing that the maximum number of channels, as detailed in the following tables, is not exceeded:
This table shows the number of channels according to the processors:
Processor
TSX P57 103
TSX P57 153
TSX P57 203 / PCX 57 203 / TSX P57 2•23
TSX P57 253
TSX P57 2623 / TSX P57 2823
TSX P57 303
TSX P57 353 / PCX 57 353 / TSX P573623
TSX P57 453 / TSX P57 4823
24
24
24
32
8
8
Number of "application-specific" channels managed
32
48
Note: The term "application-specific" applies to all channels on an applicationspecific module (counting module, axis command module etc.).
The TSX CTY 2A/C modules comprise 2 "application-specific" channels, and the
TSX CTY 4A module comprises 4 "application-specific" channels. Only the configured channels are included.
49
Installing the counting modules
Example It is possible to install 12 TSX CTY 2A/2C modules or 6 TSX CTY 4A modules with all channels configured into the configuration of a TSX P57 203 processor.
These modules can be installed in any position on the main rack, or on the
7 extension racks.
Illustration: Example of configuration:
50
Installing the counting modules
Types of sensor that can be used on counter inputs
General
Illustration
The counter inputs of TSX CTY 2A/4A/2C modules can receive pulses generated l l by:
PNP / NPN type 2 / 3-wire proximity sensors, incremental encoders with 5 V differential output signals and RS 422/485 line transmitters, on a 10-30 V supply, l incremental encoders with 5 V differential output signals and RS 422/485 line transmitters, on a 5 V supply, incremental encoders with 10-30 V output signals l l and Totem Pole, on a 10-30 V supply, an absolute encoder with SSI serial outputs, RS 485 standard interface
(TSX CTY 2C only), absolute encoders with parallel outputs and a TELEFAST ABE7CPA11 adapter
(TSX CTY 2C only).
This diagram shows the different types of incremental encoder: incremental or absolute encoder proximity sensors
51
Installing the counting modules
General counting module characteristics
General This table shows the characteristics of counting modules:
Modules
Maximum frequency at the counter inputs
Current used by the module
5 V internal
24V sensors/preactuators
Power dissipated in the module
Typical maximum
Typical maximum
Typical maximum
Sensor/pre-actuator supply monitoring
Operating temperature
Dielectric rigidity of inputs/ground or internal logic and inputs
Insulation resistance
Hygrometry
Storage temperature
Operating altitude
TSX CTY 2A
40 kHz
280 mA
330 mA
30 mA
60 mA
TSX CTY 4A
40 kHz
330 mA
470 mA
36 mA
72 mA
4.5 W
6 W
Yes
0 to 60°C
8 W
11.5 W
Yes
0 to 60°C
1000 V efficient – 50/60 Hz/min
> 10 M
Ω
under 500 VDC
5% to 95% without condensation.
-25° to +70°C
0 to 2000m
TSX CTY 2C
1 MHz
850mA (*)
1A (*)
15 mA
18 mA
7 W
10 W
Yes
0 to 60°C
(*) with operating ventilator.
52
Counter input characteristics (TSX CTY 2A / 4A)
Characteristics for RS 422 C use
Example diagram for each counter input IA, IB and IZ:
Installing the counting modules
Opto-module PS2701-1-L line monitoring
Opto-module
The IA, IB and IZ input used in RS 422 are entirely compatible with the line transmitters of incremental encoders with RS 422 outputs, and also with encoders complemented by pushpull, on a 5 V supply. A check for line breaks is executed on each input.
53
Installing the counting modules
TSX CTY 2A/4A: Characteristics of use on 5 VDC/24 VDC
General This table shows the characteristics of use on 5 VDC/24 VDC:
Input
Logic
Nominal values
Thresholds
Voltage
Current
Sensor supply
(ripple included)
Voltage
In state 1
In state 0
Voltage
Current
Voltage
Current
5 VDC counts
(IA/IB/IZ)
Positive
5 V
18 mA
-
≤
5.5 V
≥
2.4
> 3.7 mA (1)
≤
1.2 V
< 1 mA (3)
400
Ω
> 270
Ω
24 VDC counts
(IA/IB/IZ)
Positive or negative
24 V
18 mA
19...30 V (possible up to 34 V, limited to 1hr in 24)
34 V (1hr in 24)
≥
11 V
> 6 mA (2)
≤
5 V
< 2 mA (4)
1.4k
Ω
-
Input impedance for nominal U
Input impedance for U = 2.4 V
(RS 422 compatible)
Response time
Type of inputs
IEC 1131 conformity -
2-wire proximity sensor compatibility (5) -
Maximum permitted frequency 40 kHz
Resistive Resistive
3-wire proximity sensor compatibility (5) -
Type 2
Yes
Yes
(1) for U = 2.4 V, (2) for U = 11 V, (3) for U = 1.2 V, (4) for U = 5 V
(5) see compatibility of sensors with type 1 and 2 inputs.
54
Installing the counting modules
Counter input characteristics (TSX CTY 2C)
General Example diagram of input IA:
Line monitoring
Input A
55
Installing the counting modules
TSX CTY 2C: Characteristics of use on 5 VDC/24 VDC
General This table shows the characteristics of use on 5 VDC/24 VDC:
Input
Logic
Nominal values
Voltage
Current
Sensor supply
(ripple included)
5 VDC counts
(IA/IB/IZ) or measurements
(SSI data)
Positive
5 V
18 mA
-
24 VDC counts
(IA/IB/IZ)
Positive or negative
24 V
16 mA
19...30 V (possible up to 34 V, limited to 1hr in 24)
Thresholds Voltage
In state 1
In state 0
Voltage
Current
Voltage
Current
≤
5.5 V
≥
2.4 V
> 3.6 mA (1)
≤
1,2 V
< 1 mA (3)
270
Ω
34 V (1hr in 24)
≥
11 V
> 6 mA (2)
≤
5 V
< 2 mA
1.5k
Ω
Input impedance for nominal U
Response time
Maximum permitted frequency for: l l
Counting pulses,
Incremental encoders,
1 MHz
500 kHz multiplied by 1 and 250 kHz multiplied by 4
SSICLK transmission clock: 150 kHz…1 MHz l absolute SSI encoders and with parallel outputs (with a TELEFAST ABE-7CPA11 adapter)
Type of inputs
IEC 1131 conformity
2-wire proximity sensor compatibility (3) -
3-wire proximity sensor compatibility (3) -
Resistive
-
Resistive
Type 2
Yes
Yes
(1) for U = 2.4 V, (2) for U = 11 V,
(3) see compatibility of sensors with type 1 and 2 inputs.
56
Installing the counting modules
Compatibility of IA, IB and IZ inputs
Illustration 1 RS 422 / RS 485 line transmitter outputs, 7 mA current loop Differential line monitor on each input.
220
Ω
Line monitoring
Illustration 2 Additional Totem Pole outputs, 5 V supply. Differential line monitor on each input.
220 Ω
Line monitoring
57
Installing the counting modules
Count sensor supply monitor characteristics (encoder or proximity sensor)
Process diagram Illustration:
Return supply counting sensor
0 V counting sensor
Opto-module
PS2701-1-L
Characteristics This table shows the characteristics according to the modules:
Modules
Voltage with no proximity sensor or encoder supply fault
5 V supply
10…30 V supply
TSX CTY 2A / 4A TSX CTY 2C
> 2.5 V > 3.75 V
> 2.5 V
< 0.5 mA /
> 3.75 V if the 10…30 V encoder reference voltage input is not wired (pin 4 of the HE10 connector).
> 80% of the encoder or proximity sensor supply voltage, if a 10…30 V encoder reference voltage input is wired (pin 4 of the
HE10 connector).
Current with detection of a proximity sensor or encoder supply fault
Thresholds Voltage
Current
30 V (possible up to 34 V, limited to 1hr in 24)
< 3 mA < 3 mA
Note: If the sensor is not equipped with a "supply feedback" output, it is possible not to wire the EPSR input of a TSX CTY 2C module. In this case, it is recommended to hide the "encoder supply or proximity sensor" fault.
Note: For more information on these functions, refer to the application specific manual.
58
Installing the counting modules
Auxiliary input characteristics (preset, confirmation, capture)
General This table shows the characteristics of use on 5 VDC/24 VDC:
Modules
Logic
Nominal values Voltage
Current
TSX CTY 2A / 4A
Positive
24 VDC
7 mA
TSX CTY 2C
Positive or negative
24 VDC
8 mA
Thresholds
Sensor supply (ripple included)
In state 1
In state 0
Sensor/pre-actuator voltage check threshold
Sensor/pre-actuator voltage check response time
Input impedance
Response time
Type of inputs
IEC 1131 conformity
Voltage
Current
Voltage
Current
OK
Fault
With a loss of 24V
> 18 V
< 14 V
< 2.5ms (4)
With an increase of 24V < 10 ms (4)
State 0 to 1
State 1 to 0
3.4k
Ω
< 250
µ s (3)
< 250
µ s (3)
Current ducts
2-wire proximity sensor compatibility (3)
3-wire proximity sensor compatibility (3)
19...30 V (possible up to 34 V, limited to 1hr in 24)
≥
11 V
≥
11 V
> 6 mA (1)
≤
5 V
< 2 mA
> 6 mA (1)
≤
5 V
< 2 mA
Type 2
> 18 V
< 14 V
< 2.5ms (4)
< 10 ms (4)
3.4k
Ω
< 25
µ s (3)
< 50
µ s (3)
Resistive
Type 2
Yes (all 2-wire proximity sensors at 24 VDC)
Yes (all 3-wire proximity sensors at 24 VDC)
(1) for U = 11 V,
(2) see compatibility of sensors with type 1 and 2 rapid inputs,
(3) the auxiliary inputs are rapid inputs (response time < 50 µ s or < 250 µ s) dependent on the maximum permitted frequency (1 MHz or 40 kHz) of the counter inputs,
(4) with the loss of the sensor supply voltage, the rapid auxiliary inputs can be taken into account.
Note: If the auxiliary inputs/outputs remain unused on one TSX CTY 2C module, it is possible not to wire the auxiliary supply. In this case, it is recommended to hide the "auxiliary I/O supply" fault.
Note: For more information on these functions, refer to the application manual.
59
Installing the counting modules
Illustration The auxiliary inputs use a 24 V supply provided via the connector.
Diagram of the TSX CTY 2A/4A:
60
Installing the counting modules
Auxiliary output characteristics
Diagram Illustration:
Supply check sensor/ pre-actuators
Fault monitoring short-circuit
Command
Q0 to Q3
24 V
61
Installing the counting modules
Characteristics Table of characteristics:
Modules
Nominal voltage
Voltage limit
Nominal current
TSX CTY 2A / 4A
24 VDC
TSX CTY 2C
24 VDC
19...30 V (possible up to 34 V, limited to 1hr in 24)
500 mA 500 mA
Waste voltage
Leakage current
< 0.5 V
< 0.1 mA
< 0.5 V
< 0.1 mA
Max current to 30 V and to 34 V 625 mA
Switching time < 250
µ s
Dielectric rigidity with the ground connection
1500 V eff 50/60 Hz per mn
625 mA
< 250
µ s
Compatibility with direct current inputs
All positive logic inputs whose input resistance is < 15 k
Ω
Compliance with IEC 1131-2
Protection against overloads and short-circuits
Monitoring short-circuits of each channel’s outputs
Configurable reset: l manual (using the application program), l automatic
Protection against channel overvoltage
Yes Yes
Using current limiter and thermal circuit breaker
(0.7A<id<2A)
One signaling bit per channel
One configuring bit per channel using a Zener (breakdown) diode between the outputs and the + 24 V supply
Using a reverse diode on the supply Protection against polarity inversions
Power of a filament lamp 8 W (max) 8 W (max)
62
Installing the counting modules
15-pin SUB-D connectors Standard for a TSX CTY 2A / 4A module
General These connectors are designed to connect the count sensors and the encoder l l supply:
TSX CTY 2A modules two 15-pin SUB-D connectors (channels 0 and 1),
TSX CTY 4A module: four 15-pin SUB-D connectors (channels 0, 1, 2 and 3).
Note: the pinout configuration of the different connectors is exactly the same.
63
Installing the counting modules
Illustration Pinout configuration of a 15-pin SUB-D connector:
Standard 15-pin SUB-D connector for connecting the counting sensor to channels 0, 1, 2 or 3
IA input signal
IB input signal
IZ input signal
Encoder supply
Return signal encoder supply
(must be connected)
Key:
5 VDC signal
+ IA input
- IA input
+ IB input
- IB input
+ IZ input
- IZ input
Encoder supply:
+5 VDC
-0 VDC
Encoder supply feedback
15
8
13
11
4
5
Pins
1
2
10
Key:
10…30 VDC signals
+ IA input
- IA input
+ IB input
- IB input
2
3
Pins
9
11
64
10…30 VDC signals
+ IZ input
- IZ input
Encoder supply:
+10…30 V
-0 VDC
Encoder supply feedback
7
8
13
Pins
12
5
Installing the counting modules
65
Installing the counting modules
15-pin SUB-D connectors Standard for a TSX CTY 2C module
General These connectors are designed to connect the count sensors and the encoder supply: l TSX CTY 2C module: two 15-pin SUB-D connectors (channels 0 and 1).
Note: the pinout configuration of the different connectors is exactly the same.
66
Illustration
Installing the counting modules
Pinout configuration of a 15-pin SUB-D connector:
Standard 15-pin SUB-D connector for connecting the counting sensor to channels 0, 1, 2 or 3
IA input signal
SSI Data
IB input signal
IZ input signal
Clock output
SSICLK
Encoder supply
Return signal encoder supply
(must be connected)
Key:
5 VDC signal
+ IA input
- IA input
+ IB input
- IB input
+ IZ input
- IZ input
Encoder supply:
+5 VDC
-0 VDC
Encoder supply feedback
15
8
13
11
4
5
Pins
1
2
10
Key:
10…30 VDC signals
+ IA input
- IA input
+ IB input
- IB input
2
3
Pins
9
11
67
Installing the counting modules
10…30 VDC signals
+ IZ input
- IZ input
Encoder supply:
+10…30 V
-0 VDC
Encoder supply feedback
7
8
13
Pins
12
5
Key:
Serial signals (absolute encoder with serial or parallel outputs, using a TELEFAST ABE-7CPA11 adapter)
Pins
+ SSI Data
- SSI Data
1
2
+ SSI CLK input
- SSI CLK input
Encoder supply:
+5 VDC
6
14
-0 VDC
Encoder supply feedback
15
8
13
68
Installing the counting modules
HE10 20-pin connector of a TSX CTY 2A/4A module
General This connector is used to connect the auxiliary inputs, the outputs, the encoder supplies and the other sensors.
The TSX CTY 2A module comprises only one HE10 connector for channels 0 and 1.
The TSX CTY 4A module includes 2 HE10 connectors for channels 0 and 1 and channels 2 and 3 respectively.
69
Installing the counting modules
Illustration Wiring diagram for a HE10 20-pin connector:
Supply inputs
5 VDC or 10…30 VDC encoder
Channel 0 (channel 2) reset input
Channel 0 (channel 2) enable counting input
Channel 0 (channel 2) capture input
Channel 0 (channel 3) reset input
Channel 0 (channel 3) enable counting input
Channel 0 (channel 3) capture input
Channel 0 (channel 2) physical reflex outputs
Channel 1 (channel 3) physical reflex outputs
Sensors supply
24 VDC auxiliary inputs
Key:
24 VDC signals
Channel 0 (channel 2) auxiliary input:
Preset IPres0/2
Confirmation IVal0/2
Capture ICapt0/2
Channel 1 (channel 3) auxiliary input:
Preset IPres1/3
Confirmation IVal1/3
Capture ICapt1/3
Channel 0 (channel 2) reflex output:
Output Q0
Output Q1
Channel 1 reflex output:
Output Q0
Output Q1
Pins
5
6
7
13
14
15
16
9
10
11
70
Tra sup
15-p con
Au inp
Key:
Supplies
Encoder supply:
+5 VDC
- 0 VDC
+10...30 VDC
Sensor supply:
+24 VDC
-0 VDC
Pins
1
2
3
17 or 19
18 or 20
Installing the counting modules
71
Installing the counting modules
20-pin HE10 connector of a TSX CTY 2C module
General This connector is used to connect the auxiliary inputs, the outputs, the encoder supplies and the other sensors.
The TSX CTY 2C module comprises only one HE10 connector for channels 0 and 1.
72
Illustration Wiring diagram for a 20-pin HE10 connector:
Encoder supply inputs 5 VDC or 10…30 VDC
Encoder reference voltage 10…30 VDC
Channel 0 reset input
Channel 0 enable input/Output Q2
Channel 0 Q3 output
Channel 1 reset input
Channel 1 enable input/Output Q2
Channel 1 capture input
Channel 1 Q3 output
Channel 0 physical reflex outputs
Channel 1 physical reflex outputs
Installing the counting modules
Transfer supply to
15-pin SUB-D connector(s)
Auxiliary inputs
Sensors supply
24 VDC auxiliary inputs
Key:
24 VDC signals
Channel 0 auxiliary input:
Preset IPres0
Confirmation IVal0/Output Q2
Capture ICapt0
Output Q3
Channel 1 auxiliary input:
Preset IPres1
Confirmation IVal1/Output Q2
Capture ICapt1
Output Q3
Channel 0 reflex output:
Output Q0
Output Q1
Channel 1 reflex output:
Pins
9
10
11
12
5
6
7
8
13
14
73
Installing the counting modules
24 VDC signals
Output Q0
Output Q1
Key:
Supplies
Encoder supply:
+5 VDC
- 0 VDC
+10...30 VDC
Encoder reference voltage +10…30 VDC
Sensor supply:
+24 VDC
-0 VDC
Pins
15
16
Pins
3
4
1
2
17 or 19
18 or 20
74
Installing the counting modules
Principle for connecting counter proximity sensors
Illustration Process diagram:
TSX CTY 2A TSX CTY 2C
24 VDC counting sensors supply connection
TELEFAST 2
ABE-7CPA01
Number table
Counting sensors connection
This table describes the labels on the diagram:
Number
1
2
Description
TSX CCP S15 cable (2.5m long) or TSX CCPS15050 (0.5m long) or
TSX CCP S15100 (1m long), equipped with a high-density 15-pin SUB-D connector and a standard 15-pin SUB-D connector. This cable is used to connect the counting channel to the TELEFAST 2 (ABE-7CPA01) base. It carries the various relevant signals to the counter channel.
TELEFAST 2 connection base, reference ABE-7CPA01:
Used to connect the count sensors to their supply for the relevant channel.
Note: The connection of channels 2 and 3 of a TSX CTY 4A module is exactly the same as for channels 0 and 1.
75
Installing the counting modules
Connecting counter sensors and their supply
General Process diagram:
TSX CCP S15 (2.5 m) or TSX CCP S15050 (0.5 m) or TSX CCP S15100 (1 m)
TSX CTY 2A TSX CTY 2C
Channel 0
+ + - -
+ + - -
24 VDC counting sensors connection supply
GND 4 1 8 10 14 16 18
(1)
25 27 26 28
Connection of 3-wire proximity sensor with
PNP outputs
GND
+
A
+
B
+
Z
-
4 1 8 10 14 16 18 25 27 26 28
GND
+
A
- +
B
- +
Z
-
4 1 8 10 14 16 18 25 27 26 28
Connection of 3-wire proximity sensor with
NPN outputs
Connection of
2-wire proximity sensor
A B Z
76
Installing the counting modules
Note: In order to use counter proximity sensors, it is necessary to polarize the l l
EPSR input (encoder return supply). To do this, connect: the EPSR (terminal 18) to the + 24 VDC sensor supply (terminal 26 or 28), the –0 VDC sensor supply (terminal 27) to the –0 VDC encoder supply
(terminal 25).
77
Installing the counting modules
Wiring precautions
General The IPres, IVal and ICapt inputs are rapid inputs, which should be connected to the sensor using either a twisted wire, if it is a dry contact, or using shielded cables if it is a 2 or 3-wire proximity sensor.
The module integrates basic protection against short circuits or polarity inversions.
It is necessary however, to protect the supplies using fuses in series . These should be non-delay fuses, with a maximum caliber of 1A.
Important: wiring of Q0 and Q3 static outputs
The actuator connected to the Q0 and Q3 outputs has its shared point at 0 V of the supply. If, due to an incorrect contact, or the accidental disconnection of a wire, the output amplifier is no longer connected to the 0 V supply, the point shared by the actuators remains linked to the 0 V; this could generate a current of a few mA from the amplifier, sufficient to keep the low-power actuators locked.
Illustration:
+ + - -
+ + - -
Channel 0
IPres0 IVal0/Q2 ICapt0 Q3 Q0 Q1
Channel 1
IPres1 IVal1/Q2 ICapt1 Q3 Q0 Q1
204 104 205 105 206 106 107 307
+ + +
112 312 113 313 208 108 209
+ +
109 210
+
110 111 311 114 314 115 315
RI RI RI RI RI RI
105 305 109 309
RI RI
78
Connection via
TELEFAST
Installing the counting modules
This kind of connection provides the most guarantees, on condition that shared actuators are connected to shared pin bar 2•• (jump wire in position 1-2). In this case there can be no outage of the shared module without an outage of the shared actuators.
79
Installing the counting modules
Process for connecting encoder count sensors
Illustration The TSX CTY 4A module wiring is as follows. For a TSX CTY 2A or TSX CTY 2C module, only the elements related to channels 0 and 1 should be connected.
Encoders
Encoders
Channel 0 Channel 2 Channel 0 Channel 0
Channel 1 Channel 3 Channel 1 Channel 1
Description of the different connection elements
Process for connecting the encoder to the standard 15-pin SUB-D connector, located on the TSX CTY 2A / 4A / 2C module. Given the various encoder types, it is your responsibility to carry out this connection, which consists of: l l a connector for linking to the encoder (determined by the connector on the encoder in use; normally a female 12-pin DIN connector), a standard male 15-pin SUB-D connector, to connect to the female 15-pin l
SUB-D connector on the TSX CTY 2A/4A/2C module. This connector is available under reference TSX CAP S15, a cable: l l with twisted pairs (gauge 26) and shielding for an incremental encoder with standard RS 422 line transmitter outputs or an absolute encoder, multi-conductor (gauge 24) with shielding for an incremental encoder with
Totem Pole outputs.
The type of cable shielding should be "braid and foil". The cables should be completely supported to ensure the "braid and foil" is connected to the ground connection of each connector.
Connection of the cable to the two connectors can vary according to the type of encoder supply (5 VDC or 10…30 VDC) and the type of outputs (RS 422, Totem
Pole). By way of an example, certain types of connection are described in the following pages.
80
Connecting an encoder to a TSX CTY 2A / 4A / 2C module
Installing the counting modules
Illustration Process diagram:
TSX CTY 2C TSX CTY 2A
Channel 0
Cable 1 encoder
81
Installing the counting modules
Example for connecting an incremental encoder with
RS 422 / RS 485 line transmitter outputs
Encoder characteristics l l supply voltage: 5 VDC, output voltage: 5 VDC differential, l high-level output: line transmitter, RS 422 / RS 485 standard.
Process diagram:
CTY module incremental encoder
Channel connection diagram:
DIN connector encoder
Cable 1
(connecting encoder/ TSX CTY ••) standard 15-pin
SUB-D connector standard 15-pin SUB-D
82
*EPSR: supply feedback of the encoder,
(1) link directly if the encoder is grounded.
Installing the counting modules
Example of connecting an incremental encoder with Totem Pole outputs
Encoder characteristics l l l supply voltage: 10...30 VDC, output voltage: 10…0 VDC, high-level outputs: Totem Pole.
Process diagram This diagram shows the principles for connection:
CTY module incremental encoder standard 15-pin SUB-D connector
83
Installing the counting modules
Channel connection diagram
This diagram shows the principles for connecting a channel: encoder
DIN connector cable 1
(connecting encoder/ TSX CTY ••) standard 15-pin SUB-D
*EPSR: supply feedback of the encoder.
If the encoder has no supply feedback, link the EPSR input on the encoder side to the + of the supply.
(1) link directly if the encoder is grounded.
84
Installing the counting modules
Example of connecting an incremental encoder with NPN open collector outputs.
Encoder characteristics l l l supply voltage: 24 VDC, output voltage: 24 VDC, high-level outputs: NPN open collector.
Process diagram This diagram shows the principles for connection:
CTY module incremental encoder standard 15 pin SUB-D connector
85
Installing the counting modules
Channel connection diagram
This diagram shows the principles for connecting a channel: encoder
DIN connector cable 1
(connecting encoder/ TSX CTY ••) standard 15-pin SUB-D
*EPSR: supply feedback of the encoder.
If the encoder has no supply feedback, link the EPSR input on the encoder side to the + of the supply.
(1) link directly if the encoder is grounded.
86
Installing the counting modules
Example of connecting an incremental encoder with PNP open collector outputs
Encoder characteristics l l l supply voltage: 24 VDC, output voltage: 24 VDC, high-level outputs: PNP open collector.
Process diagram This diagram shows the principles for connection:
CTY module incremental encoder standard 15 pin SUB-D connector
87
Installing the counting modules
Channel connection diagram
This diagram shows the principles for connecting a channel: encoder
DIN connector cable 1
(connecting encoder/ TSX CTY ••) standard 15-pin SUB-D
*EPSR: supply feedback of the encoder.
If the encoder has no supply feedback, link the EPSR input on the encoder side to the + of the supply.
(1) link directly if the encoder is grounded.
88
Installing the counting modules
Example of connecting an absolute encoder with a serial output or parallel outputs, via ABE-7CPA11 adapted TELEFAST (only TSX CTY 2C module)
Encoder characteristics l l supply voltage: 5 VDC or 10...30 VDC, high-level outputs: differential line transmitter.
Process diagram This diagram shows the principles for connection:
CTY module incremental encoder standard 15 pin SUB-D connector
89
Installing the counting modules
Channel connection diagram
This diagram shows the principles for connecting a channel:
DIN connector encoder cable 1
(connecting encoder/ TSX CTY 2C) standard 15-pin SUB-D
*EPSR: supply feedback of the encoder.
If the encoder has no supply feedback, link the EPSR input on the encoder side to the + of the supply.
(1) link directly if the encoder is grounded.
90
Installing the counting modules
Principle for connecting sensors onto auxiliary I/O
Connection principle
The TSX CTY 4A wiring is as follows. For a TSX CTY 2A or TSX CTY 2C module, only one TELEFAST is connected (channels 0 and 1).
TSX CDP••2 cable (1) or TSX CDP••3 cable (2)
24 VDC sensor supply 24 VDC sensor supply
Connecting:
- encoder supplies (5 VDC or 10…30 VDC)
- channels 2 and 3 preset sensors
- channels 2 and 3 counting validation sensors
- channels 2 and 3 capture sensors
- channels 2 and 3 reflex outputs
Connecting:
- encoder supplies (5 VDC or 10…30 VDC)
- channels 0 and 1 preset sensors
- channels 0 and 1 counting validation sensors
- channels 0 and 1 capture sensors
- channels 0 and 1 reflex outputs
Note: Using a discrete TELEFAST connection base is not compulsory, but advisable as it facilitates the connection of supplies, sensors and pre-actuators on to the auxiliary I/O.
(1) TSX DCP 102: 1 m in length,
TSX CDP 202: 2 m in length,
TSX CDP 302: 3 m in length,
(2) TSX CDP 053: 0.5 m in length,
TSX CDP 103: 1 m in length,
TSX CDP 203: 2 m in length,
TSX CDP 303: 3 m in length,
TSX CDP 503: 5 m in length.
91
Installing the counting modules
Description of the different connection elements
This table shows the different connection elements according to address:
Number
1
2
Description
TELEFAST 2 connection base: ABE-7H16R20. This allows rapid connection of: l l l l the 24 VDC supply for the sensors connected to the auxiliary I/O, the encoder supply (if the counting sensor is of the encoder type), the sensors onto the auxiliary I/O (preset, confirmation, capture), the pre-actuators.
Stranded and clad TSX CDP •• 2 cable or connection cable
TSX CDP ••3.
Note: The ABE-7BV20 accessory (sold in inseparable quantities of 5) facilitates shared connection.
92
Installing the counting modules
Connecting sensors and their supply
Process diagram This connection is made using a TELEFAST 2 connection base with the reference no. ABE-7H16R20:
Connecting supply of 24 VDC sensor
ABE-7H16R20
Cable
TSX CDP ••2 or cable
TSX CDP ••3
Connecting supply
Supply for an encoder with
10...30
VDC
ABE-7BV20
(shared -)
Connecting sensors onto auxiliary inputs/outputs
Channel 0 Channel 1 mechanical contact pre-actuators
Reference voltage
10…30 VDC encoder
2-wire
Supply an encoder with
5 VDC
3-wire proximity sensor PNP
Note: The connection of channels 2 and 3 of a TSX CTY 4A module is exactly the same as for channels 0 and 1.
93
Installing the counting modules
General rules for implementation
Installation Connecting or disconnecting the standard 15 pin SUB-D connectors of the
TSX CTY 2A/ 4A/ 2C modules to/from the encoder and sensor supplies present is not recommended as this may damage the encoder. Some encoders cannot withstand sudden and simultaneous signal and supply power-ups or outages.
94
General wiring instructions
Installing the counting modules
Wire sections
Use wires of a satisfactory section to avoid drops in voltage (mainly with 5 V) and overheating.
Example of falls in voltage for encoders supplied with 5 V with a cable length of
100 meters:
Section of the wire
0.08 mm
2
(gauge 28)
0.12 mm
2
(gauge 26)
0.22 mm
2
(gauge 24)
0.34 mm
2
(gauge 22)
0.5 mm
2
1 mm
2
-
-
Encoder consumption
50 mA 100 mA
1.1 V 2.2 V
1.4 V
0.8 V
0.25 V
0.17 V
0.5 V
0.34 V
0.09 V 0.17 V
-
-
150 mA
3.3 V
0.75 V
0.51 V
0.24 V
-
-
200 mA
4.4 V
1 V
0.68 V
0.34 V
Connection cable
All cables carrying the sensor supply (encoders, proximity sensor etc.) and the l l counting signals must: be at a distance from high voltage cables, be shielded with the shielding , which is linked to the protective ground connection on both the PLC and encoder side, l never carry signals other than counting signals and supplies relating to counting sensors.
The connection cable between the module and encoder should be as short as possible to avoid creating loops, as the circuit capacities can interfere with operation.
Note: If necessary, direct the flow of the signal in the same cable as the supplies.
Cables with twisted pairs should preferably be used for this.
95
Installing the counting modules
Encoder and auxiliary sensor supply
Encoder supply l l
This must: l be reserved exclusively for supplying the encoder to avoid parasitic pulses which could interfere with the encoders, whose electronics are sensitive, l be placed as close to the TELEFAST 2 base as possible to reduce drops in voltage and coupling with other cables, be protected against short circuits and overloads by fast blow fuses, work well independently to avoid micro-power outages.
Auxiliary sensor supply
Refer to the general regulations for implementing discrete modules.
Note: The – 0 VDC polarity of the auxiliary encoder and sensor supplies should be grounded as near to the supplies as possible.
The shielding of the cables carrying the voltages should be grounded.
Software implementation
Software implementation and the language objects assigned to the different counting functions are described in the "counting application" manual.
96
Appendices
4
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter deals with TELEFAST 2: ABE-7CPA01, TELEFAST 2: ABE-7H16R20, etc.
This chapter contains the following topics:
Topic
Connecting TELEFAST 2: ABE-7CPA01
Availability of counting signals on the TELEFAST screw terminal block
Correspondence between TELEFAST ABE-7CPA01 terminal block and 15 pin
SUB-D connector
Page
TELEFAST 2 connection base: ABE-7H16R20
Availability of signals on TELEFAST screw terminal block
Correspondence between TELEFAST ABE-7H16R20 terminals and HE10 connector
TELEFAST 2 connection and adaptation base: ABE-7CPA11
Physical description of the TELEFAST 2: ABE-7CPA11
Characteristics of the TELEFAST base ABE-7CPA11
Connecting the TELEFAST 2 base: ABE-7CPA11
Connecting encoders with 10…30 V supply
Connecting encoders with 5 V supply
Example of the multiplexing of encoders with a 5 V supply.
Example of connection: each TSX CTY 2C channel is only connected to one
TELEFAST
Example of connection: 2 TELEFAST are connected on the same channel
Example of connection: 3 TELEFAST are connected on the same channel
Example of connection: 4 TELEFAST are connected on the same channel
97
Appendices
Topic
Rules and precautions for wiring
Configuration of the TELEFAST base
Overview of the TSX TAP S15•• wiring accessories
Mounting and measurements of the TSX TAP S15 05/24
Connecting an encoder with a TSX TAP S15 05 accessory.
Connecting an encoder with a TSX TAP S15 24 accessory
Pre-wired strands and cable
Module display
Page
98
Appendices
Connecting TELEFAST 2: ABE-7CPA01
At a Glance Using a TELEFAST 2 (ABE-7CPA01) connection base, a standard 15 pin female l l
SUB-D connection can be transformed into a screw terminal block connection with: l 32 terminals on two rows, where the different sensors and their supplies can be connected,
4 terminals for restart (2 GND terminals + 2 N1 terminals for specific restarts),
4 terminals for connecting the sensor supply.
This means proximity detector type sensors can be quickly connected onto a counting channel of the TSX CTY 2A, TSX CTY 4A and TSX CTY 2 modules.
Illustration:
TSX CTY 2A
TSX CTY 4A
TSX CTY 2C
TSX CCP S15 (2.5 m) or TSX CCP S15050 (0.5 m) or TSX CCP S15100 (1 m)
ABE-7CPA01 counting sensor
The 9 pin SUB-D connector means information can be reported to an Altivar when this base is used with analog inputs/outputs.
99
Appendices
Wiring layout Illustration:
X1 X2
Dimensions and mounting
Dimensions
Mounting
The ABE-7CPA01 connection base is mounted on a DIN mounting rail, which has a width of 35 mm.
100
Availability of counting signals on the TELEFAST screw terminal block
Appendices
Counting channel used with proximity detector type sensors
Illustration:
Note: Each TELEFAST 2 ABE-7CPA01 connection base comes with 6 labels so that each base can be individually identified according to the function.
An optional ABE-7BV20 bar can be added, for example for a shared GND.
101
Appendices
Correspondence between TELEFAST ABE-7CPA01 terminal block and 15 pin
SUB-D connector
General This table shows the correspondences between TELEFAST ABE-7CPA01 terminal blocks and the 15 pin SUB-D connector:
27
28
29
30
23
24
25
26
31
32
19
20
21
22
15
16
17
18
11
12
13
14
7
8
9
10
5
6
3
4
1
2
TELEFAST screw terminal block
(Terminal No.)
10
3
11
4
12
5
13
6
7
8
15
14
2
9
2
1
Standard 15 pin
SUB D connector
(Pin No.)
Signal type
TSX CTY 2A / 4A
IA-
IA + 5 V RS 422C
IA-
IA + 24 VDC
IB + 5 V RS 422 C
IB + 24 VDC
IB-
IZ + 5 V RS 422 C
IZ + 24 VDC
IZ-
TSX CTY 2C
IA-
IA + 5 V RS 422C
IA-
IA + 24 VDC
IB + 5 V RS 422 C
IB + 24 VDC
IB-
IZ + 5 V RS 422 C
IZ + 24 VDC
IZ-
Encoder supply return (EPSR)
Reserved
Encoder supply input + 5 VDC
Reserved
Encoder supply input +10…30 VDC
Encoder supply input -0 VDC
Sensor supply output + 24 VDC
Sensor supply output -0 VDC
Sensor supply output + 24 VDC
102
Appendices
TELEFAST 2 connection base: ABE-7H16R20
At a Glance
Illustration
With a TELEFAST 2 (ABE-7H16R20) connection base, a 20 pin HE10 type connection can be transformed into a screw terminal block connection, so that sensors and supplies can be quickly connected to the auxiliary inputs of the
TSX CTY 2A / 4A / 2C counting modules.
This diagram shows the connection of a TELEFAST to the counting modules:
(1) TSX CDP ••2 or TSX CDP ••3 cable.
Note: The TELEFAST 2 connection bases for discrete I/O are described in the discrete I/O implementation manual.
103
Appendices
Availability of signals on TELEFAST screw terminal block
Illustration The terminal block below represents the terminal block of the ABE-7H16R20 base.
(1) On the ABE-7H16R20 base, the position of the jumper wire determines the polarity of all the 2•• terminals: l jumper wire in position 1 or 2: terminals 200 to 215 have + polarity, l jumper wire in position 3 or 4: terminals 200 to 215 have - polarity.
(2) On the ABE-7H16R20 base, it is possible to add an optional ABE-7BV20 bar to create a second shared sensor (+ or - according to user’s choice).
Note: Sensor connection and supply on the ABE-7H16R20 base are described in the discrete I/O implementation manual.
104
Appendices
Correspondence between TELEFAST ABE-7H16R20 terminals and
HE10 connector
104
105
106
107
108
109
110
111
112
113
114
115
+ 24 VDC
- 0 VDC
+ 24 VDC
- 0 VDC
3
4
1
2
200...215
General
TELEFAST screw terminal block
(Terminal No.)
100
101
102
103
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
This table introduces the correspondence between TELEFAST ABE-7H16R20 terminal blocks and the HE10 connector:
3
4
1
2
20 pin HE10 connector
(Pin No.)
Kind of signal
TSX CTY 2A / 4A TSX CTY 2C
+ 5 VDC
- 0 VDC
+ 10...30 VDC
IPres 0/2
IVal 0/2
ICapt 0/2
IPres 1/3
IVal 1/3
ICapt 1/3
+ 5 VDC
- 0 VDC
+ 10...30 VDC
Encoder reference voltage
10…30 VDC
IPres 0
IVal 0 / Q2 output channel 0
ICapt 0
Q3 output channel 0
IPres 1
IVal 1 / Q2 output channel 1
ICapt 1
Q3 output channel 1
Q0 output channel 0/2 Q0 output channel 0
Q1 output channel 0/2 Q1 output channel 0
Q0 output channel 1/3 Q0 output channel 1
Q1 output channel 1/3 Q1 output channel 1
Auxiliary input/output supply
Type of signal
Encoder supply
Auxiliary inputs channels 0 / 2
Auxiliary inputs / outputs channels 1 / 3
Reflex outputs channels 0 / 2
Reflex outputs channels 1 / 3
Terminals 200 to 215 at +24 VDC
Terminals 200 to 215 at -0 VDC
300...315
Connecting shared sensors to:
+ 24 VDC if terminals 1 and 2 are connected
- 0 VDC if terminals 3 and 4 are connected
On the ABE-7BV20 optional bar, terminals can be used as sensors
105
Appendices
TELEFAST 2 connection and adaptation base: ABE-7CPA11
At a Glance
Illustration
The TELEFAST 2 connection and adaptation base: ABE-7CPA11 is used to connect absolute encoders with parallel outputs to the TSX CTY 2C counting module.
It converts the position value provided by the absolute encoder with parallel outputs into serial information. The absolute encoder must be encoded in pure binary or
Gray with a maximum of 24 bits of data.
2 absolute encoders with parallel outputs can be connected on the same adaptation
TELEFAST. Further, serializing several ABE-7CPA11 bases (4 maximum) means up to 4 absolute encoders with parallel outputs can be multiplexed on one counting channel (position acquisition).
This diagram shows an absolute encoder with a TELEFAST ABE-7CPA11 and a
TSX CTY 2C module:
TSX CTY 2C
TELEFAST ABE-7CPA11 absolute encoder with parallel outputs
106
Physical description of the TELEFAST 2: ABE-7CPA11
Illustration This diagram shows a TELEFAST 2: ABE-7CAP11:
Appendices
Table of numbers This table describes the diagram below using numbers:
5
6
Number
1
2
3
4
Description
Standard 15 pin SUB-D connector for connecting the TELEFAST to the
TSX CTY 2C module.
Standard 15 pin SUB-D connector for putting several TELEFASTS
(maximum 4) in series.
Screw terminal block for connecting one or more absolute encoders with parallel outputs (maximum 2).
The supplies can be shared out by using additional snap on terminal blocks:
ABE-7BV10 (10 terminals) or ABE-7BV20 (20 terminals).
TELEFAST diagnostics LED. This green LED is illuminated when the
TELEFAST is powered.
Protection fuse for the 10…30 V supply (rapid 1A type).
Microswitch for configuring one or more encoders (encoder number, type, etc.).
107
Appendices
Characteristics of the TELEFAST base ABE-7CPA11
General characteristics
This is a table of the general characteristics:
Parameters
Permitted voltage at 10…30 VDC
Permitted voltage at 5 VDC
Maximum frequency for change in state of the least significant bit
Read frequency of the serial frame
Current used (excluding encoder)
Values
11…30 V
5…6V
75 kHz
Dissipated power
150 kHz...1 MHz typical: 90 mA
Max: 130 mA typical: 450 mW
Max: 1.5 W
-15% Vsuppl
+15% Vsuppl
Encoder supply return monitoring: l l on the + supply on the - supply
Insulation resistance
Dielectric rigidity
Operating temperature
Hygrometry
Storage temperature
Operating altitude
> 10 M
Ω
0…60°C
under 500 VDC
1000 Veff.50/60 Hz in 1 min
5%…95% without condensation
-25 °C…+70°C
0...2000 m
108
Appendices
Characteristics of the encoder read inputs
(in0 to in23)
Characteristics of the discrete address inputs
(AD0, AD1)
This table shows the characteristics of the read inputs (in0 to in23):
Parameters
Logic
Compatibility with encoder outputs
Values positive or negative (1)
11-30 V Totem pole outputs
5 V TTL outputs
11-30 V NPN open collector transistor outputs
Max. voltage permissible on the inputs +30 V
Max. wiring length between encoder and TELEFAST 200 m (2)
VIL input voltage
VIH input voltage
0 V < VIL < 2.5 V
3.9 V > VIL > 30 V
(1) Positive logic : voltage < 2.5 V -> state 0,
voltage > 3.9 V -> state 1,
Negative logic : voltage < 2.5 V -> state 1, voltage > 3.9 V -> state 0.
(2) 50m max with pure binary encoded encoders with NPN open collector outputs and derating according to length.
This table shows the characteristics of the discrete address inputs (AD0, AD1):
Parameters
Logic
Voltage limit l max. voltage limit permissible
Nominal values l l with voltage in current
Voltage for ON state
Current for ON state at 11 V
Voltage for OFF state
Current for OFF state
Input impedance for nominal U
Response time
Type of inputs
IEC 1131 conformity
Values positive
30 V
34 V (1hr in 24)
24 V
7 mA
≥
11 V
≥
3mA
≤
5 V
≤
2 mA
3.6 k
Ω
25
µ s...50
µ s resistive type 1
109
Appendices
Characteristics of the command outputs with 3 encoder states
(3OT0, 3OT1)
This table shows the characteristics of the command outputs with 3 encoder states
(3OT0, 3ST1):
Parameters
Output voltage
Nominal current
Max fall in voltage
Max. current
Protection against overloads and short-circuits
Values encoder supply enc. supply / 3 k
Ω
< 0.5 V
10 mA no
110
Appendices
Connecting the TELEFAST 2 base: ABE-7CPA11
15 pin SUB-D connector pinouts
Illustration:
Left connector
DATA+
DATA-
MAE
AD0ME
AD1ME
CLKS+
10...30 VDC
0 VDC
1
4
5
2
3
12
13
6
7
14
15
9
10
11
8
AD0E
AD1E nc nc
EPSR
CLKS-
5 VDC
+ - - +
TELEFAST
ABE-7CPA11
Right connector
DATA+
DATA-
MAS
AD0MES
AD1MES
CLKS+ nc
0 VDC
1
2
3
4
5
6
7
8
12
13
14
15
9
10
11
AD0ES
AD1ES nc nc
EPSR
CLKSnc
Key:
Supply
0 VDC
10...30 VDC
0 VDC
Addressing the encoders l inter-TELEFAST bus (Input):
AD0E
AD1I
AD0MI
AD1MI
MAI
Encoder supply return EPSR
4
5
9
10
3
13
8
7
15
111
Appendices
Serial link l data outputs:
DATA+
DATAl clock inputs:
CLKS+
CLKS-
Key:
Supply
0 VDC
Addressing the encoders l inter-TELEFAST bus (Output):
AD0IO
AD1IO
AD0MIO
AD1MIO
MAO
Encoder supply return EPSR
Serial link l data outputs:
DATA+
DATAl clock inputs:
CLKS+
CLKS-
8
4
5
9
10
3
13
1
2
6
14
1
2
6
14
112
Connecting encoders with 10…30 V supply
Process diagram Illustration:
+ +
TELEFAST ABE-7CPA11
Appendices
GND local
Connection to cable shielding
Absolute encoder with parallel outputs
0 V
Q1
Q0
113
Appendices
Key:
Signals
GND
+10…30 V
0 V in0 to in23
ERR
3OT0
3OT1
AD0, AD1
COM
+ EPSR
- EPSR
Meaning ground connection of the encoder(s)
+ supply terminal of the encoder(s)
- supply terminal of the encoder(s)
Terminal No.
outputs of the encoder(s) error output of the encoder(s) command to inhibit the 0 encoder outputs (for multiplexing) command to inhibit the 1 encoder outputs (for multiplexing) encoder multiplexing command shared AD0 and AD1 signals
1...24
25
26
27
28,30
32 encoder supply return input + (connector at 10…V if no monitoring)
29 encoder supply return input + (connector at 0 V without monitoring)
31
Note: refer to wiring rules and precautions (See
Rules and precautions for wiring, p. 126)
for encoder outputs.
114
Connecting encoders with 5 V supply
Process diagram Illustration:
5 VDC supply
+ +
TELEFAST ABE-7CPA11
Appendices
GND local
Connection to cable shielding
Absolute encoder with parallel outputs
0 V
Q1
Q0
TSX CTY 2C
115
Appendices
Key:
Signals
GND
+5 V
0 V in0 to in23
ERR
3OT0
3OT1
AD0, AD1
COM
+ EPSR
- EPSR
Meaning ground connection of the encoder(s)
+ supply terminal of the encoder(s)
- supply terminal of the encoder(s) outputs of the encoder(s) error output of the encoder(s) command to inhibit the 0 encoder outputs (for multiplexing) command to inhibit the 1 encoder outputs (for multiplexing) encoder multiplexing command shared AD0 and AD1 signals encoder supply return input + (connect to +5 V if no monitoring) encoder supply return input + (connector at 0 V if no monitoring)
Terminal No.
1...24
25
26
27
28,30
32
29
31
Note: refer to wiring rules and precautions (See
Rules and precautions for wiring, p. 126)
for encoder outputs.
116
Example of the multiplexing of encoders with a 5 V supply.
General Illustration:
+ +
TELEFAST ABE-7CPA11
Appendices
Absolute encoders with parallel outputs to encoder 1 to encoder 0 to encoder 0 or encoder 1
TSX CTY 2C (1)
0 V
Q1
Q0
117
Appendices
IMPORTANT
When carrying out multiplexing, encoders with parallel outputs of the same type l l must be used: with the same number of data bits, and the same supply (the encoders have a supply of either 10…30 VDC, or 5 VDC).
Note: if the control supply encoder is not used, the +EPSR terminal (encoder + supply feedback) must be connected to +10…30 V or +5 Vand the –EPSR terminal
(encoder supply feedback) must be connected to 0 V.
(1) Using the Q0 and Q1 reflex outputs from TSX CTY 2C is not compulsory for addressing encoders; as this operation can be carried out by 2 outputs from a discrete module. In this case, the shared outputs at the COM input of the
TELEFAST ABE-7CPA11 must be connected.
(2) It is compulsory to set the configuration micro-switch according to the number of encoders connected on the base (OFF if 1 encoder, or ON if 2 encoders).
118
Appendices
Example of connection: each TSX CTY 2C channel is only connected to one
TELEFAST
Illustration This diagram illustrates the connection of each TSX CTY 2C channel to one
TELEFAST:
TSX CTY 2C
TELEFAST 0
ABE-7CPA11
TSX CDP••2 cable or TSX CDP••3 cable
Channel 0
Channel 1
Configuration:
1 encoder per base
TSX CCP S15 cable (2.5 m) or TSX CCP S15100 (1 m) or TSX CCP S15050 (0.5 m)
Absolute encoder with parallel outputs
Configuration:
2 encoders per base
TELEFAST
ABE-7H16R20
TELEFAST
ABE-7CPA11
Encoder 0
Encoder 1
Encoder addressing (AD0, COM) (1)
Note: (1) it is not necessary to wire the TELEFAST 0 (channel 0) encoder addressing because it has the default address of 00.
119
Appendices
Addressing the encoders
Addressing the TELEFAST encoders is as follows:
0
1
AD1
0
1
1
0
AD0
0
1
Action
Read encoder 0
Reading encoder 1
No reading
No reading
120
Appendices
Example of connection: 2 TELEFAST are connected on the same channel
Illustration This diagram illustrates the connection of 2 TELEFAST on the same channel:
TSX CTY 2C
TELEFAST 0
ABE-7CPA11
Channel 0
Configuration:
1 encoder per base
Channel 1
TSX CDP••2 cable or TSX CDP••3 cable
TSX CCP S15 cable (2.5 m) or TSX CCP S15100 (1 m) or TSX CCP S15050 (0.5 m)
Encoder 0
TELEFAST
ABE-7CPA11
TELEFAST
ABE-7H16R20
Encoder 1
Absolute encoder with parallel outputs
Configuration:
2 encoders per base
Encoder 1
Encoder 0
Encoder addressing (AD0, AD1, COM) (1)
Addressing the encoders
(1) Addressing the TELEFAST encoders is as follows:
0
1
AD1
0
1
1
0
AD0
0
1
Action
Reading the TELEFAST 0 encoder 0
Reading the TELEFAST 0 encoder 1
Reading the TELEFAST 1 encoder 0
Reading the TELEFAST 1 encoder 1
121
Appendices
Example of connection: 3 TELEFAST are connected on the same channel
Illustration This diagram illustrates the connection of 3 TELEFAST on the same channel:
TELEFAST 0
ABE-7CPA11
Configuration:
1 encoder per base
TSX CCP S15 cable (2.5 m) or TSX CCP S15100 (1 m) or TSX CCP S15050 (0.5 m)
Absolute encoder with parallel outputs
TSX CTY 2C
TSX CDP••2 cable or TSX CDP••3 cable
Channel 0
Channel 1
TELEFAST
ABE-7CPA11
TELEFAST
ABE-7CPA11
Configuration:
1 encoder per base
Configuration:
2 encoders per base
TELEFAST
ABE-7H16R20
Encoder 1
Encoder 0
Encoder addressing (AD0, AD1, COM) (1)
122
Addressing the encoders
Appendices
(1) Addressing the TELEFAST encoders is as follows:
0
1
AD1
0
1
1
0
AD0
0
1
Action
Reading the TELEFAST 0 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 2 encoder 0
Reading the TELEFAST 2 encoder 1
If, for example, 2 encoders are wired on TELEFAST 0 and a single encoder on
TELEFAST 2, the addressing becomes: 00-reading of the TELEFAST 0 encoder 0,
01-reading of the TELEFAST 0 encoder 1,10-reading of the TELEFAST 1 encoder and 11-reading of the TELEFAST 2 encoder.
123
Appendices
Example of connection: 4 TELEFAST are connected on the same channel
Illustration This diagram illustrates the connection of 4 TELEFAST on the same channel:
TELEFAST 0
ABE-7CPA11
TSX CCP S15 cable (2.5 m) or TSX CCP S15100 (1 m) or TSX CCP S15050 (0.5 m) Configuration:
1 encoder per base
Absolute encoder with parallel
TSX CTY 2C
Configuration:
1 encoder per base
Channel 1
TELEFAST
ABE-7CPA11
Absolute encoder with parallel outputs
TSX CDP••2 cable or TSX CDP••3 cable
TSX CCP S15 cable (2.5 m) or TSX CCP S15100 (1 m) or TSX CCP S15050 (0.5 m)
Absolute encoder with parallel
TELEFAST
ABE-7CPA11
Configuration:
1 encoder per base
TELEFAST
ABE-7H16R20
TELEFAST
ABE-7CPA11
Configuration:
1 encoder per base
Absolute encoder with parallel outputs
Encoder addressing (AD0, AD1, COM) (1)
124
Addressing the encoders
(1) Addressing the TELEFAST encoders is as follows:
0
1
AD1
0
1
1
0
AD0
0
1
Action
Reading the TELEFAST 0 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 2 encoder
Reading the TELEFAST 3 encoder
Appendices
125
Appendices
Rules and precautions for wiring
Important All connections or disconnections on the TELEFAST must be made when
SWITCHED OFF (encoders, link to counting module, links between TELEFAST bases).
Connecting
TELEFAST 0 to
TELEFAST counting and chaining module
The TSX CCP S15 (2.5m), TSX CCP S15100 (1m) and TSX CCP S15050 (0.5m) cables are offered for connecting TELEFASTS amongst themselves or for connecting TELEFAST 0 to the TSX CTY 2C module. The user can however carry out longer links by using the wiring kit, reference no. TSX CAP S15••, and by respecting the following setpoint when the encoders have a 5 V supply : if the link between the counting module and the TELEFAST 0 does not exceed 100m, use gauge 28 wires (0.008mm
2
). If it is > 100m, use wires with at least gauge 22
(0.34mm
2
). However, to limit the drop in voltage at 0 V (due to the encoder supply current), we recommend that you wire the 0 V according to the following diagram.
Illustration Wiring diagram:
24 V supply
TELEFAST ABE-7CPA11
+ 24 V encoder +0 V encoder
126
Appendices
Cable length between counting module and TELEFAST
The total length of the link between the counting module and the TELEFAST (sum of the lengths between the counting channel and the first TELEFAST and the different TELEFAST between one another) must not exceed 200m, in the knowledge that the maximum cable length between 2 TELEFAST is 50m.
If the total distance between the first and the last TELEFAST exceeds 20m, the line on the right connector of the last TELEFAST must be adapted by inserting an endof-line stopper (220 Ω resistance between pins 1 and 2 of the connector).
The following table shows the serial transmission clock frequencies, according to the total length of the link:
Cable lengths
< 10m
< 20m
< 50m
< 100m
< 150m
< 200m
Frequency of the serial transmission clock
1 MHz
750 kHz
500 kHz
375 kHz
200 kHz (default)
150 kHz
Protecting the encoder supply
The voltage used by the encoder(s) connected to TELEFAST determine whether this supply should be 10…30 VDC or 5 VDC. If the supply is 10…30 VDC, the protective fuse is built-in to the TELEFAST (fast-blow 1A fuse). However, if the
TELEFAST has a supply of 5 VDC, the user must provide in series with the +supply terminal a fast-blow fuse, which is adapted to TELEFAST consumption and to the encoders connected.
Monitoring the encoder supply voltage
This function is only valid if a single encoder is connected to the TELEFAST. If the encoder supply voltage decreases by more than 15%, the default EPSR is sent back to the module.
If the encoder does not have an encoder supply feedback, you must wire: l l the TELEFAST +EPSR terminal to the + of the encoder supply, the TELEFAST -EPSR terminal to the - of the encoder supply.
127
Appendices
Wiring the encoder outputs
If the encoder outputs have positive logic and there are less than 24 of them, the following rules must be adhered to: l wire the encoder outputs to the TELEFAST inputs, working up from the least to the most significant, l wire the unused TELEFAST inputs to the 0 V terminal.
Illustration:
14 bits encoder
If the encoder outputs have negative logic, and there are less than 24 of them, the following rules must be adhered to: l wire the encoder outputs to the TELEFAST inputs, working from the up from the least to the most significant, l do not wire the unused TELEFAST inputs (leave loose).
Illustration:
14 bits encoder
128
Appendices
Configuration of the TELEFAST base
Introduction The base is configured by setting the 4 micro-switches, which are located under the connector to the right of this.
They make it possible to inhibit the encoder outputs and to define the number and the type of encoders connected to the TELEFAST base.
Illustration:
Type of encoders connected to TELEFAST base
Number of encoders connected to TELEFAST base
Inhibition of encoder outputs
Inhibiting the encoder outputs
This micro-switch chooses the state of the 2 inhibition commands (3ST0 and 3ST1) of the encoder outputs.
Illustration Description
The encoder outputs are at high impedance with a 3ST0 or 3ST1 command active at 0.
The encoder outputs are at high impedance with a 3ST0 or 3ST1 command active at 1.
129
Appendices
Number of encoders connected to
TELEFAST
This micro-switch makes it possible to define the number of encoders connected to the TELEFAST base (1 or 2 parallel output absolute encoders).
Illustration Description
An encoder is connected to the base.
Two encoders are connected to the base.
If the number of connected encoders is odd and the number of TELEFAST in series is equal to 2 or 3 for one counting channel, the TELEFAST must be configured so that the sum of the encoders equals 4 .
With 2
TELEFAST bases
This table shows the configuration if there are two TELEFAST bases:
Hardware configuration (number of encoders per TELEFAST)
TELEFAST micro-switch
2 encoders on TELEFAST 0 and
1 encoder on TELEFAST 1
0
ON
1
ON
1 encoder on TELEFAST 0 and
2 encoders on TELEFAST 1
ON ON
Address
1
1
0
0
AD0
0
0
1
1
0
1
0
1
AD1
0
1
0
1
Action
Reading the TELEFAST 0 encoder 0
Reading the TELEFAST 0 encoder 1
Reading the TELEFAST 1 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 0 encoder
Reading the TELEFAST 0 encoder
Reading the TELEFAST 1 encoder 0
Reading the TELEFAST 1 encoder 1
130
Appendices
With 3
TELEFAST bases
This table shows the configuration if there are two TELEFAST bases:
Hardware configuration
(number of encoders per
TELEFAST)
1 encoder on TELEFAST 0
1 encoder on TELEFAST 1 and
1 encoder on TELEFAST 2
1 encoder on TELEFAST 0
1 encoder on TELEFAST 1 and
1 encoder on TELEFAST 2
1 encoder on TELEFAST 0
1 encoder on TELEFAST 1 and
1 encoder on TELEFAST 2
TELEFAST micro-switch
0 1 2
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
Address
0
1
0
1
0
1
0
1
0
1
0
1
1
1
0
0
0
0
1
1
0
0
1
1
Action
Reading the TELEFAST 0 encoder
Reading the TELEFAST 0 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 2 encoder
Reading the TELEFAST 0 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 2 encoder
Reading the TELEFAST 0 encoder
Reading the TELEFAST 1 encoder
Reading the TELEFAST 2 encoder
Reading the TELEFAST 2 encoder
131
Appendices
Type of encoders connected to
TELEFAST
These micro-switches make it possible to define the type of encoders connected to the TELEFAST base. The following tables show the performance characteristics of the encoder/TELEFAST link, according to the code chosen by the micro-switches:
Table 1
Encoders with positive logic outputs, Totem pole outputs, TTL outputs and NPN open collector outputs coded in Gray
Max.length
encoder/
TELEFAST
50 m
Max. frequency for changing least significant bit
75 kHz
Table 2
Encoders with negative logic outputs, Totem pole outputs, TTL outputs and NPN open collector outputs coded in Gray
Max.length
encoder/
TELEFAST
50 m
Max. frequency for changing least significant bit
75 kHz
100 m
200 m
40 kHz
5 kHz
132
Appendices
Table 3
Encoders with positive or negative logic outputs,
NPN open collector, binary coded
Max. length encoder/
TELEFAST
10 m
Max. frequency for changing least significant bit
40 kHz
30 m 20 kHz
50 m 5 kHz
Note: For encoders with positive logic, TTL and Totem pole outputs, it is possible to go beyond these capacities, without exceeding the recommendations of the encoder manufacturers.
133
Appendices
Overview of the TSX TAP S15•• wiring accessories
General The TSX TAP S15•• wiring accessories make it possible to connect an incremental encoder to the counting module, by using a specific cable (supplied by the encoder manufacturer): l TSX TAP S15 05: makes it possible to connect an incremental encoder with a l
VDC supply: encoder with RS 422 line issuer outputs,
TSX TAP S15 24: makes it possible to connect an incremental encoder with a
24 VDC supply: encoder with totem pole outputs or open collector PNP outputs.
The TSX TAP S15•• has 2 connectors: l a female 12-pin DIN base, labeled in an anti-clockwise direction. This connector l makes it possible to connect the encoder, via a cable supplied by the manufacturer of the encoder, a standard 15-pin SUB-D connector making it possible to connect the module counting inputs to the SUB-D connector, using a standard TSX CCP S15 cable.
The TSX TAP S15•• product can be fixed onto a DIN rail using a bracket supplied with the accessories, or it can be fixed to a cabinet lead-in with a gasket, which is supplied with the product.
Illustration:
Incremental encoder equipped with a DIN 12 pin connector
Specific cable supplied by encoder manufacturer
TSX TAP S15••
M
2
3
1 9
10
11
12
8
6
7
4 5
F
8 9
7
6
12 10
11
5 4
1
3
2
M
7
6
8 9
12
11
10
1
3
2
5 4
F
2
3
1 9
10
11
12
8
6
7
4 5
134
Appendices
Mounting and measurements of the TSX TAP S15 05/24
Mounting on a
Telequick plate
The set square supplied makes it possible to fix the TSX TAP S15 05/24 on an
AM1-PA••• type perforated plate or on any other support.
Mounting through a cabinet
Thanks to its rifle nut, the TSX TAP S15 05/24 can be mounted through a cabinet.
Its seal means the area between the interior and the exterior is guaranteed to be watertight. max. width = 5mm joint perforation = 37mm in diameter
135
Appendices
Size Illustration:
136
Appendices
Connecting an encoder with a TSX TAP S15 05 accessory.
General
Illustration
A specific cable, supplied by the manufacturer of the encoder, is used for connecting an encoder using an auxiliary TSX TAP S15 05.
The pinout of TSX TAP S15 05 is as follows:
TSX CPP S15
1
9
10
11
12
13
14
15
4
5
2
3
6
7
8
A+ 5 V
A- 5 V
B+ 5 V
B- 5 V
Z+ 5 V
Z- 5 V
EPSR
+5 V
0 V
4
5
10
11
1
2
13
15
8
3
4
8
1
5
6
2
12
10
Specific cable supplied by the manufacturer of encoder
2
3
1 9
10 12
11
4 5
8
6
7
137
Appendices
Connecting an encoder with a TSX TAP S15 24 accessory
General
Illustration
A specific cable, supplied by the manufacturer of the encoder, is required for connecting an encoder using an auxiliary TSX TAP S15 24.
The pinout of TSX TAP S15 24 is as follows:
TSX CPP S15
9
10
1
2
3
3
9
12
B+ 24 V
8
A+ 24 V
5
Z+ 24 V
Supply feedback
24 V encoder
3
24 V
12
Specific cable supplied by encoder manufacturer
11
12
4
5
7
13
2
3
1 9
10
11
12
4 5
8
6
7
13 2
6
14
5
7
15
8
8
0 V
11 10
TSX TAP S15 24
This type of connection is compatible with encoders with a 24V supply (Heidenheim,
Hengstler, Codechamp, Ivo, Ideacod, etc.).
138
Appendices
Pre-wired strands and cable
TSX CDP 301 and
TSX CDP 501 pre-wired strands
These pre-wired strands (or strips) make it possible to connect the sensors, preactuators or terminals directly to the counting modules. They comprise 20 gauge-
22 wires (0.34m
2
) and are fitted with an HE10 connector at one end. The free wires at the other end are labeled with a color code according to the DIN 47100 standard.
The correspondence between the color of the wires and the pin number of the HE10 connector is as follows:
Cable:
TSX CDP 301 (3 m)
TSX CDP 501 (5 m) white brown green yellow gray pink blue red black violet gray-pink red-blue white-green brown-green white-yellow yellow-brown white-gray gray-brown white-pink pink-brown
139
Appendices
TSX CDP 102,
TSX CDP 202 and
TSX CDP 302 connection cables
These stranded and clad connection cables make it possible to connect the HE10 connector of a counting module to a TELEFAST 2 (1) connection interface. They are made up of a stranded, flat cable and clad with gauge-28 wires (0.08mm
2
, and are fitted with an HE10 connector at each end.
Given the small area of each of the wires, you are advised to only use these connection cables for low current inputs or outputs (< 100mA per input or output).
3 connection cable lengths are offered:
TSX CDP 102: 1 meter long,
TSX CDP 202: 2 meters long,
TSX CDP 503.302: 3 meters long.
TSX CDP 053/
103/203/303/503 connection cable
These connection cables make it possible to connect the HE10 connector of a counting module to a TELEFAST 2 (1) connection interface. They are made up of a cable with gauge-22 wires (0.34 mm
2
, and are fitted with a compound-filled HE10 connector at each end.
These cables allow higher levels of current to enter (< 500mA) than connection cables.
5 cable lengths are offered:
TSX CDP 053 : 0.5 meter long,
TSX CDP 103 : 1 meter long,
TSX CDP 203 : 2 meters long,
TSX CDP 303 : 3 meters long,
TSX CDP 503 : 5 meters long.
140
Appendices
Module display
General The TSX CTY 2A/4A/2C modules are fitted with LEDs on the front panel, which make it possible to view the state of the module and the counting channels: l Module state LEDs (RUN, ERR, I/O)
These 3 LEDs provide information on the operation mode of the module: l l RUN indicates the state of the module operation, l ERR signals an error inside the module, l I/O signals an external module error or an application fault.
Channel state LEDs (CH.)
These are 2 or 4 LEDs, which make it possible to view and diagnose the state of each channel in the module.
141
Appendices
Diagnostics This table shows the diagnostics of the module according to the state of the LEDs:
Lit Flashing Off
RUN
ERR
I/O
CH
TSX CTY 2A/2C
CH0 and CH1
TSX CTY 4A
CH0, CH1, CH2,
CH3.
Module operative /
Internal module error: module has broken down.
External module error: l l wiring fault, encoder supply error, l measurement overrun.
Application fault
/
The channel is operational.
Communication error or awaiting configuration.
The channel is not functioning correctly due to: l l l an internal fault, an external fault, a communication error, l an application fault.
Module switched off or experiencing a fault
No error.
No error.
Channel inoperative:
The channel is not configured, or is badly configured.
Illustration of module LEDs:
142
TSX CAY axis command modules
II
At a Glance
Subject of this part
What's in this
Part?
This part provides an overview of the TSX CAY axis command modules, their functionality and how to implement them.
This part contains the following chapters:
Chapter
5
6
7
8
Chapter Name
Introduction to the TSX CAY modules
Page
Implementing
Appendices
143
TSX CAY axis command modules
144
Introduction to the TSX CAY modules
5
At a Glance
Subject of this chapter
What's in this
Chapter?
This chapter provides an overview of the different TSX CAY axis command modules.
This chapter contains the following topics:
Topic
General
Physical description
Page
145
Introduction
General
Introduction
Terminology
The axis command and controlled placement offer for Premium PLCs is designed for machines, which require a simultaneous performing movement command and a sequential command by programmable controller.
The following modules: TSX CAY 21 (2 axes) and TSX CAY 41 (4 axes) make controlled placement possible on independent, linear and limited axes.
The modules TSX CAY 22 (2 axes) and TSX CAY 42 (4 axes) make controlled placement possible on independent, circular and infinite axes.
The module TSX CAY 33 (3 axes) makes a placement on 2 or 3 synchronized axes
(linear interpolation) possible.
l l l the term TSX CAY covers everything on the axis command offer, the reference TSX CAY 2 regroups the TSX CAY 21 and 22 modules, the reference TSX CAY 4• corresponds to the TSX CAY 41 and 42 modules.
These modules in standard format (TSX CAY 2•) or double format (TSX CAY 4• and
TSX CAY 33) can be installed in all the available slots of a PLC configuration
(TSX, or PCX).
l l l l
To ensure position measurement, an encoder (which may be a different type) is wired onto each of the channels:
RS 422/485 incremental encoder,
5 V Totem pole incremental encoder,
SSI serial absolute encoder, parallel output absolute encoder (with ABE-7CPA11 interface).
146
Illustration This diagram illustrates different types of TSX CAY modules:
TSX CAY 4•
TSX CAY 2• encoder variable motor
TSX CAY 33
Introduction
147
Introduction
Physical description
Illustration This diagram illustrates different TSX CAY modules:
TSX CAY 21/22 TSX CAY 41/42
8
9
8
9
10
1
5
2
10
3
1
5
4
2
6
7
7
6
TSX CAY 33
3
1
5
4
8
9
10
7
6
148
Introduction
Table of numbers The following table describes the above diagrams using numbers:
7
8
9
10
4
5
6
2
3
Number
1
Description
15-pin SUB-D connector for connecting an axis 0 encoder.
15-pin SUB-D connector for connecting an axis 1 encoder.
15-pin SUB-D connector for connecting an axis 2 encoder.
15-pin SUB-D connector for connecting an axis 3 encoder.
9-pin SUB-D connector for connecting speed references.
l l
HE10 connector(s) for connecting: l auxiliary inputs: l cam reference point, l l emergency stop, recalibration, of auxiliary outputs, of external supplies (encoders and sensors).
HE10 connector for connecting variable controller inputs/outputs.
Screw for fixing module in place.
Rigid body, which functions as the module captor in the slot.
Module diagnostic LEDs: l module level diagnostics: l green LED RUN: indicates the operating mode of the module, l l red LED ERR: indicates an internal error, red LED I/O: indicates an external error or application fault, l module channel level diagnostics: l CHx green LEDs: indicates of channel diagnostics.
149
Introduction
150
Functions
6
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter introduces the various functions of the TSX CAY modules.
This chapter contains the following topics:
Topic
Circuit diagram of an axis command
Command processing
Page
151
Functions
Circuit diagram of an axis command
Illustration Process diagram:
Processor
TSX CAY module
Configuration
+adjust
%K,%M
Configuration parameter
Adjust
SMOVE function
%Q/ %QW
%I/ %IW
Processing
Application
Encoder input
Loop for automatic control
Variable output
Processing
Auxiliary I/O
PO cam input
Event input
Adjustment input
Emergency stop input
Variable error input
Enable relay output variable
Auxiliary output
Functions provided by the axis command modules
The axis command modules provide the following functions for each axis: l Inputs: l one input for the acquisition of position measurements:
RS 485 incremental encoder or 5 V totem pole, 16 to 25-data bit SSI serial l l l l absolute encoder, one machine reference point input, one event input, one variable default input, l l one recalibration input, one emergency stop input.
Outputs: l one +/- 10 V, + sign 13-bit resolution analog output, for the speed controller command, l one relay output for validating the controller, l one auxiliary static output.
152
Functions
Command processing
Introduction Each movement, controlled from the PLC sequential program, is described by a
SMOVE movement command function in the PL7 language. From this SMOVE command, the TSX CAY modules work out a position/speed trajectory.
The PL7 screens make it possible to easily achieve the configuration, adjustment, and setting of the axes.
Axis configuration
The configuration screen enables the required parameters to be entered, in order to adapt the operation of the module to the characteristics of the machine. These are: the encoder type, position limits, maximum speed, etc. These parameters cannot be modified by a program. There is no default configuration.
Axis adjustment The parameters offered by the adjustment screen are linked to axis operation. The parameters are adjusted when on or offline.
l l l l l l
The operating parameters are: corrected resolution, mmovement control: errors of following, adjustment, overspeed, etc., stop control: delay, speed, debug window, position loop: position gain, speed anticipation coefficient, offset, command: soft stops, acceleration, acceleration profile, manual mode parameters: speed, reference point value etc.
Note: These parameters can be changed by program.
Debug The debug screen can only be accessed in online mode. This makes it possible to l l l l control and observe the performance of the axis.
Information and commands differ according to the operation mode chosen: automatic mode, manual mode, loop control disabled mode, measurement mode (off).
The top part of the screen indicates the operating state and diagnostics of the module. The lower part accesses the commands and indications on the operation of movement, inputs/outputs, errors, etc.
153
Functions
154
Implementing
7
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter describes the implementation of TSX CAY axis command modules.
This chapter contains the following sections:
Section
7.1
7.2
7.3
7.4
7.5
7.6
7.7
Topic
General
Connecting speed reference signals
Connecting the counting signals
Wiring accessories
Connection of sensors/ pre-actuator and supply modules, without variable speed controller
Connecting the variable speed controller signals
Electrical characteristics of modules
Page
155
Implementing
156
Implementing
7.1
General
At a Glance
Subject of this section
What's in this
Section?
This Section introduces general instructions for the installation of TSX CAY axis command modules.
This section contains the following topics:
Topic
Standard configuration required
Installation procedure
General precautions for wiring
Choice of encoders
Module display
Page
157
Implementing
Standard configuration required
General The servomotor axis command modules can be installed in all the available slots in a Premium (TSX, or PCX) PLC configuration.
To be used to the maximum:
Processors
TSX P57 103
TSX P57 153
TSX P57 203 / PCX 57 203 / TSX P57 2•23
TSX P 57 253
TSX P 57 2623 / TSX P 57 2823
TSX P 57 303
TSX P57 353 / PCX 57 353 / TSX P57 3623
TSX P57 453 / TSX P57 4823
24
24
24
32
8
8
Number of "application-specific" channels supported (*)
32
48
(*) The term "application-specific" applies to all channels on an application-specific module (axis command counting module, etc.). TSX CAY 2 modules include 2•
"application-specific" channels, TSX CAY 4• modules include 4 "applicationspecific" channels and TSX CAY 33 modules include 3 "application-specific" channels.
Note: TSX CAY 22/42 and 33 modules are not compatible with the old
TSX P57 10 and TSX P57 20 processors.
The rack power supply must be chosen according to the number of modules installed.
158
Implementing
Installation procedure
General The module can be installed or removed without cutting off the rack supply voltage.
The design of the modules allows this action to be carried out with the power on, in order to ensure that a device is available.
CAUTION
Connecting or disconnecting the connectors
Connecting or disconnecting connectors with sensor supplies is not recommended, as some encoders do not support this action. The auxiliary input/output connectors can be disconnected while switched on without damaging the module. However, for safety reasons it is recommended that you turn off the auxiliary supply before any type of disconnection.
Failure to follow this precaution can result in injury or equipment damage.
The module fixing screws and connectors must be correctly screwed in place in order to obtain good electrical contacts, thus guaranteeing effective resistance to electrostatic and electromagnetic interference.
159
Implementing
General precautions for wiring
General The supplies to sensors and actuators must be protected against overloading or excess voltage by non-delay fuses.
When wiring, use wires of a satisfactory size to avoid on-line drops in voltage and overheating,
Keep sensor and actuator cables away from any source of radiation resulting from high-power electric circuit switches.
All cables which link the incremental or absolute encoders must be shielded. The shielding should be good quality and linked to the protective ground connection on the side of the module and the side of the encoder. Continuity must be ensured throughout connections. Do not introduce any other signals than those of the encoders in the cable.
For reasons of performance, the auxiliary inputs of the module have a short response time. You must therefore make sure that the supply autonomy of these inputs is sufficient to ensure the module continues to operate correctly in the event of short power breaks. It is recommended that you use regulated supplies to ensure more reliable response times from the actuators and sensors. The 0 V supply must be linked to the protective ground connection as near to the supply output as possible.
160
Implementing
Choice of encoders
Output interface The output interfaces of incremental encoders or pulse generators are: l l
RS 422/485 standard output, two push-pull outputs, complemented by the signal,
5 V Totem pole output, two complementary push-pull outputs.
Absolute SSI serial encoders have a standardized RS 485 interface for clock and data signals.
We recommend an encoder with opto type "CLOCK" signal input stage. Different types of encoders can be connected onto the same module. For example, an incremental encoder on channel 0 and an absolute SII encoder on channel 1.
Encoder supply The module is designed to supply encoders with 5 V or 24 V. Mixing supply voltages is possible on all module channels.
Incremental encoders usually have a 5 V supply.
Absolute SSI encoders have a 24 V (10/30 V) supply.
5 V encoder supply: maximum drop in voltage.
In this case there is reason for taking the on-line voltage drop into account. This drop depends on cable length and encoder consumption for a given wire gauge.
Example for a 100m-long cable:
Section of the wire
Encoder consumption
Gauge 28 = 0.08mm
2
Gauge 22 = 0.34mm
2
0.5 mm
2
1 mm
2
Drop in voltage for a 100m-long cable
50 mA 100 mA 150 mA
1.1 V 2.2 V 3.3 V
0.25 V 0.5 V 0.75 V
0.17 V
0.09 V
0.34 V
0.17 V
0.51 V
0.24 V
200 mA
4.4 V
1 V
0.68 V
0.34 V
24 V encoder supply.
This type of encoder is recommended, because it does not need a precise supply
(10 V/30 V). When there is a 24 V supply, these encoders make it possible to have a very large cable, which makes the voltage drop in the cable rather insignificant.
This is the case for SSI serial link encoders.
Note: If a 24 V absolute SSI serial encoder is used, it is not necessary to connect the 5 V supply.
161
Implementing
Shielding To ensure good working order in the case of interference, an encoder, whose metal casing is grounded by the connected device, must be chosen. The encoder must ground the connection cable shielding.
162
Implementing
Module display
General The TSX CAY 2•/4• and 33 modules are provided with LEDs, used to display the state of the modules and channels.
l l
Module state LEDs (RUN, ERR, I/O)
Three LEDs located on the front panel of the module provide information about the module’s operation through their state (LED off, blinking or lit): l RUN LED: indicates the operating state of the module, l ERR LED: indicates an internal module error, l I/O LED: indicates an external error.
Channel state LEDs (CH.)
The TSX CAY 2•/4• and 33 modules have 2, 3 or 4 LEDs, which are used to display and diagnose the state of each channel. These LEDs are green.
163
Implementing
Diagnostic table This table shows the diagnostics of the module according to the state of the LEDs:
Lit Blinking Off
RUN
ERR
I/O
CH
TSX CAY 2•
CH0 and CH1
TSX CTY 4•/33
CH0, CH1, CH2,
CH3.
Module normal
Internal module error: module has broken down.
/ Module switched off or experiencing a fault
Communication error
Application missing, invalid or experiencing a fault during execution
No error.
No error.
External module error: l l wiring fault,
Encoder supply and 10/30 V l supply fault, absolute encoder error
(*).
/
The channel is operational.
The channel is not functioning correctly due to: l l an external fault, a communication error, l a processing error.
Channel inoperative.
The channel is not configured, or is badly configured.
(*) application fault: l l configuration declined,
SMOVE function declined.
Illustration of module LEDs:
164
Implementing
7.2
Connecting speed reference signals
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of speed reference signals.
This section contains the following topics:
Topic
Signal labeling
Connection using TSX CAP S9
Connection using TSX CDP 611 strips
Connection of terminals with the TELEFAST pre-wiring system
Correspondence between the SUB-D connector pins and the TELEFAST terminals
TAP MAS connection device
Connecting the variable using the TAP MAS device
Page
165
Implementing
Signal labeling
Process diagram This diagram illustrates the principles for labeling signals:
Male connector seen from wiring side
Connecting the speed references
Four types of connection are offered: l l l l wiring with TSX CAP S9 connector and cover, using the TSX CDP 611 strip, wiring with output on terminals with TELEFAST ABE-7CPA01, wiring with output on TAP MAS (exploding device).
166
Implementing
Connection using TSX CAP S9
General The connection is made manually by soldering onto the 9 pins SUB-D connector, as labeled in the preceding principle diagram. However, checks must be carried out to ensure that the shielding is properly connected to the cable, which must be correctly clamped to the cover of the connector.
167
Implementing
Connection using TSX CDP 611 strips
General This pre-wired cable is made up of a SUB-D 9-pin connector at one end, to connect to the TSX CAY module, and free wires at the other end. With a length of 6m, it is made up of 24 gage wires, corresponding to the SUB-D connector pins; It enables direct connection of the equipment to the module. The different signals are labeled using a color code.
Note: It is imperative to connect the shielding to the protective ground of the connected equipment.
Diagram of the priciple
This diagram illustrates the principle for connection using TSX CDP 611 strips:
3
8
4
9
5
2
7
1
6
Vref0+ axis 0
Vref0-
Vref1+ axis 1
Vref1-
Vref2+ axis 2
Vref2-
Vref3+ axis 3
Vref3-
GND-ANA shielding
Note: the TSX CDP 611 cable is 6m in length.
168
Implementing
Connection of terminals with the TELEFAST pre-wiring system
General The TELEFAST 2 system is a collection of products, which allow rapid connection of the modules from the Micro and Premium range. It acts as a substitute for screw terminal blocks, by realigning the single wire connection.
The connection on speed reference terminals is necessary when the variable speed controllers are not close to each other. The TELEFAST pre-wiring system facilitates installation by allowing access to signals via the screw terminal blocks. Connection to the module with the TELEFAST reference: ABE-7CPA01 assists a cable equipped with a 9-pin SUB-D connector on the module side and a 15 pin SUB-D connector on the TELEFAST side. This cable can be: TSX CXP 213 or
TSX CXP 613.
169
Implementing
Diagram of the principle
This diagram illustrates the principle for connection with the TELEFAST pre-wiring system:
ABE-7CPA01
TSX CXP 213
TSX CXP 613
TSX CXP 213 cable: I = 2 m
TSX CXP 613 cable: I = 6 m
Variable with
2-wire inputs shared
Links to GND-
ANA (terminals
5, 11, 15 and 19)
Variable with differential inputs
170
Implementing
Correspondence between the SUB-D connector pins and the TELEFAST terminals
General This table shows the correspondence between the SUB-D connector pins and the
TELEFAST terminals:
Kind of signal
23
24
26
28
30
19
20
21
22
14
15
16
18
8
10
11
12
5
6
2
4
TELEFAST screw terminal block
(Terminal No.)
Standard SUB D
15-pin connector
(Pin No.)
1
2
TSX CAY module
SUB-D 9-pin connector
10
3
11
1
6
2
4
12
7
3
5
13
8
4
6 nc
14 nc nc nc nc
9
5
Vref0+
Vref0vref1+
Vref1-
Vref2+
Vref2-
Vref3+
Vref3link to terminal 23
GND-ANA
171
Implementing
TAP MAS connection device
General The connection device enables the speed references of each variable speed controller to start again at the same time. This allows the simple connection of several variables, while maintaining good ground connection continuity.
Illustration of the connection device:
Dimensions and fixing
The TSX TAP MAS device is installed either on an AM1 PA… type perforated board or on a DIN rail with an LA9 D09976 fixation board with two M3x8 or M3x10 screws:
172
Implementing
Connecting the variable using the TAP MAS device
General
Illustration
The NUM MDLA modular variable speed controllers can be connected to the
TSX CAY module using the TSX TAP MAS connection device. Installation is simplified by using predefined cables and the connection device, which simply directs the voltage references to the different axes.
This diagram illustrates the principle for connection using the TAP MAS connection device:
Modular variable
SUB-D 9 pin
1 Vref+
6 Vref-
5 GND-ANA male
SUB-D 9 pin
1 Vref+
6 Vref-
5 GND-ANA male
TSX CXP 223
Cables:
TSX CXP 223: length = 2.5 m
TSX CXP 213: length = 2.5 m
TSX CXP 613: length = 6 m male
SUB-D 25 pin
5 Vref+
18 Vref-
6 GND-ANA
TSX CDP 611 black ref+ blue refbrown GND-ANA shielding
173
Implementing
7.3
Connecting the counting signals
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of counting signals.
This section contains the following topics:
Topic
Connecting counting signals
Connecting an incremental encoder
Connecting an absolute SSI encoder
Connecting the encoder supply
Page
174
Implementing
Connecting counting signals
Introduction
Signal labeling
To ensure position measurement, the TSX CAY modules are equipped with connectors allowing direct connection of an incremental or absolute SSI encoder on each channel. Each of these channels can be equipped with a different type of encoder.
TSX CAY modules can be connected either to incremental encoders, or to SSI type encoders with serial links. In configuration mode, the available functions are as follows: l Two types of interface are possible for the incremental encoders: l l RS 422/RS 485 outputs with two outputs complemented by a signal, l 5 V Totem Pole outputs.
Absolute SSI encoder, standard RS 485 interface.
A 15-pin SUB-D connector is assigned to each channel. This also allows the encoder supply. These supplies are elaborated from the +supply discrete HE10 connector. Signal: +return supply encoder, from the encoder allows monitoring for accidental disconnection of the encoder.
175
Implementing
Illustration This diagram illustrates the principles for labeling signals:
SSI data+/A+
SSI data-/A-
Z+
Z-
CLKSSI+ encoder +supply (10...30V) encoder -supply (0V)
7
8
1
2
5
6
3
4
11
12
9
10
13
14
15
B+
B-
+ return supply of encod
CLKSSI-
5 V encoder supply
1
3
2
4
5V
0V
10...30V
0V supply for encoders
176
Branching Branching table:
Element
Incremental encoder
Absolute SSI encoder:
5 V encoder supply
Encoder supply (10-30 V)
Designation input A+ input Ainput Z+ input Zinput B+
5
10 input B11 return supply of encoder 13
2
4
Terminal
1
+ SSI Data
- SSI data
CLKSSI+
CLKSSI-
+supply (5 V)
- supply (0 V)
+supply (10-30 V)
- supply (0 V)
1
2
6
14
15
8
7
8
Implementing
177
Implementing
Connecting an incremental encoder
Connection diagram
The type of interface is either RS 422 / RS 485 or totem pole:
TSX CAY ENCODER(*)
10-30V
5V
0V
3
4
5
6
1
2
7
8
14
15
9
10
11
12
13
4
2
3
1
5
6
8
12
10
A+
A-
B+
B-
Z+
Z-
+ return supply
+ supply
- supply
(*) standard pinouts for an encoder equipped with a 12-pin DIN connector.
Each signal (A+, A- for example) should be connected by a twisted pair. To reduce on-line voltage falls, it is recommended to connect each supply point using a pair.
Cable shielding should be connected at each end to the protective ground.
CAUTION
+supply encoder input
The +supply encoder input of the DIN connector is linked to a 10-30 V supply wire or a 5 V wire, according to the type of encoder used.
Failure to follow this precaution can result in injury or equipment damage.
178
Implementing
Connecting an absolute SSI encoder
Connection diagram illustration:
ENCODER
Data+
Datareturn + supply (*)
CLKSSI+
CLKSSI-
+ supply
- supply
10..30 V
5 V
0 V
WARNING
Connecting the encoder supply
The encoder supply is linked to pin 15 or 7 of the SUB-D connector, according to the encoder supply voltage.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
(*) + return supply: encoder output, which returns the supply voltage to the module, therefore allowing the module to monitor the presence of the encoder.
179
Implementing
Connecting the encoder supply
Diagram of the principle
This diagram illustrates the connection of the encoder supply:
24 VDC supply connection auxiliary input sensors
TELEFAST 2
ABE-7H16R20
TSX CDP053 / 503 cable
Supply.
24 V
Supply.
5 V
Cable length:
Cable
TSX CDP 053
TSX CDP 103
TSX CDP 203
TSX CDP 303
TSX CDP 503
Length
0.5 m
1 m
2 m
3 m
5 m
Note: The maximum length of the wire between the supply outputs and the connection points on the TELEFAST should be less than 0.5 m.
Only one supply is required if the encoders on the two channels are of the same type.
180
Fuses
Implementing l l l
This module integrates several basic protection systems against wiring errors and accidental short circuits on the cable: polarity inversions of the supplies, inversion of 5 V supplies <--> 10/30 V,
10/30 V short circuit on the CLOCK signal of the serial link.
The module cannot tolerate them for very long time, it should therefore have very fast blow fuses. The fuses should therefore be "rapid" and of 1A caliber maximum.
Supplies should have a limitation current, such that the blow of the fuse can be correctly executed.
181
Implementing
7.4
Wiring accessories
At a Glance
Subject of this section
What's in this
Section?
This Section introduces the wiring accessories for the TSX CAY modules.
This section contains the following topics:
Topic
Encoder connection accessories
Information on FRB type 12 pin connectors
TSX TAP S15 05 mounting and dimensions
Connecting absolute encoder // via a TELEFAST with ABE-7CPA11 adaptation
Connecting to a NUM MDLA variable speed controller
Page
182
Implementing
Encoder connection accessories
General A number of accessories are available to facilitate implementation and installation.
These accessories are used to pre-wire the installation. A direct link with the installation can be established using cover kits containing the 15 pin SUB-D connector, TSX CAP S15. To facilitate installation, the TSX TAP S15 05 is used as an interface between the SUB-D and 12 pin DIN connector. Using a fixing hook, this accessory can be mounted on a DIN rail or on a cabinet lead-in with a gasket and adjusting nut. Connection to the module is via a 2.5m long TSX CCP S15 cable.
183
Implementing
Examples Illustration:
Incremental encoder or absolute encoder
Incremental encoder or absolute encoder
Incremental encoder 5 V
RS 422
Incremental encoder 5 V
RS 422
Note: Good signal and shielding continuity can be ensured in difficult conditions thanks to these accessories. Encoder connection cables can generally be obtained from encoder suppliers.
184
Implementing
Information on FRB type 12 pin connectors
General Number labeling of pins in these connectors is performed in two different ways.
Most encoders have a built-in 12 pin base and are labeled anti-clockwise. The
TSX TAP S15 has a 12 pin female base labeled anti-clockwise. All user cables must be equipped with connecting plugs labeled clockwise, so that the pin numbers correspond to one another when wired.
Illustration: coupling connectors
Encoder with connector anti-clockwise
TSX TAP S15 05 user cable base base
M
2
3
1 9
10
11
12
4 5
8
6
7
F
8 9
7
6
12
11
10
4 5
1
3
2 clockwise anti-clockwise
M
7
6
8 9
12
11
10
4 5
1
3
2
F
2
3
1 9
10
11
12
4 5
8
6
7
185
Implementing
Labeling of the
DIN and 15 pin
SUB-D connector of the
TSX TAP S15 05
Table of numbers:
7
8
9
10
11
12
5
6
3
4
1
2
DIN
Pin
Signal nc
0 V nc
5 V
B-
Supp return
Z+
Z-
A+
A- nc
B+
1
2
4
5
SUB_D
Pin
11
13
10
8
15
Shielding should be continuous along the connections which should be linked to the mechanical ground connection on both sides.
186
Implementing
TSX TAP S15 05 mounting and dimensions
Mounting onto a
Telequick board
The TSX TAP S15 05 can be attached to an AM1-PA••• type perforated board or any other support using the bracket supplied.
Mounting through a cabinet
The TSX TAP S15 05 can be mounted through a cabinet as it has a fixing nut. Its joint creates an impervious seal between the interior and exterior. max width=5mm gasket hole = 37 mm in diameter
187
Implementing
Dimensions Illustration:
70,4
Ø5,5
27,4 43
188
Implementing
Connecting absolute encoder // via a TELEFAST with ABE-7CPA11 adaptation
General
Illustration l l l l l l l l the multiplexing function must not be used: each channel uses a base, to which only one absolute encoder with parallel outputs is connected, the encoder frame should be configured as follows: code: binary or Gray (according to the encoder type), header bits: 0, data bits: 24 (irrespective of the number of encoder data bits), status bits: 3, rank of the error bit: 1 (optional), parity: even.
This diagram shows the connection between a TSX CAY and a TELEFAST
ABE-7CPA11:
TSX CAY
TELEFAST
ABE-7CPA11
ON
OFF
Absolute encoder with parallel output inhibiting the outputs of the encoder encoder configuration using base type of encoder connected
189
Implementing
Connecting to a NUM MDLA variable speed controller
General
Illustration
The NUM 400 V controller contains all the elements necessary to functioning.
It offers an output whose signals simulate the functioning of an incremental encoder as a position report. Direct connection is possible using the 2.5 cm or 6m long
TSX CXP 233 / 633 cable accessory.
Connection to a variable speed controller:
J2 signal encoder
0 V
Cable length:
Cable
TSX CXP 213
TSX CXP 633
Length
2.5 cm
6 m
Note: Here, it is not necessary to have an encoder supply.
190
7.5
Implementing
Connection of sensors/ pre-actuator and supply modules, without variable speed controller
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of sensors/pre-actuators and supply modules without a variable speed controller.
This section contains the following topics:
Topic
General
TELEFAST connection and wiring accessories
Availability of signals on TELEFAST
Example of connecting sensors to the auxiliary inputs and their supply.
Correspondence between TELEFAST terminal blocks and module HE10 connector
Connection using TSX CDP 301 or 501 strips
Wiring precautions
Page
191
Implementing
General
Introduction
Signal labeling
The TSX CAY modules integrate basic inputs/outputs, which ensure complete functioning of the movement command, as well as ensuring the encoder supply.
The connector is a high density HE10:
Supply input of encoders
Auxiliary inputs channels
0,1 channels
0,1 channel
0 channel
2
Auxiliary inputs
Reflex output
Reflex output
Supply input of sensors
TSX CAY 2• module: Channels 0 and 1
TSX CAY 4• module: Channels 0,1,2 and 3
TSX CAY 33• module: Channels 0,1 and 2 l l l l l l
The auxiliary inputs/outputs are allocated the following functions:
I0 = cam reference point input,
I1 =emergency stop input (stop if there is no current in the input),
I2 = adjusting input,
I3 = adjustment input,
Q0 = reflex output (static output),
0 V = shared auxiliary inputs and reflex outputs.
channel
1 channel
3 channel
1 channel
1 channel
2 channel
3 channels
0,1 channels
2,3
192
Principle for connecting the
I/O associated with channel 0
Illustration:
Po
FcD FcG At_Urg
Evt
Rec
Implementing
193
Implementing
TELEFAST connection and wiring accessories
General
Illustration
When connecting this high density connector, it is recommended that you use the discrete TELEFAST ABE-7H16R20 pre-wiring accessory and the TSX
CDP 053/503 cable or a 3m long strip of the 20-wire TSX CDP 301 or a 5m strip of the TSX CDP 501, which contains a HE10 connector at one end and free wires at the other.
Discrete TELEFAST wiring:
194
Cable length:
Cable
TSX CDP 053
TSX CDP 103
TSX CDP 203
TSX CDP 303
TSX CDP 503
Length
0.5 m
1 m
2 m
3 m
5 m
Implementing
Availability of signals on TELEFAST
Illustration The terminal below represents the terminal of the ABE-7H16R20 base. The signals are represented using TSX CDP 053 / 503 cable:
(1) At the ABE-7H16R20 base, the position of the jumper wire determines the polarity of all terminals from 200 to 215: l jumper wire in position 1 or 2: terminals 200 to 215 have + polarity, l jumper wire in position 3 or 4: terminals 200 to 215 have - polarity,
(2) At the ABE-7H16R20 base, it is possible to add an optional ABE-7BV20 strip to create a second shared sensor (+ or - according to user’s choice).
195
Implementing
Example of connecting sensors to the auxiliary inputs and their supply.
Illustration This connection is made using a TELEFAST 2 connection base: ABE-7H16R20:
24 VDC supply connection auxiliary input sensors
TELEFAST 2
ABE-7H16R20
TSX CDP053 / 503 cable
ABE-7BV20
(shared -)
Channel 0
Connecting sensors to auxiliary inputs
Channel 1
Mechanical contact
Proximity sensor
2 wires
PNP
Proximity sensor
3 wires
PNP
NO NC NO NO
NO: Normally Open.
NC: Normally Closed (Conductor).
NO NC NO NO
196
Implementing
Correspondence between TELEFAST terminal blocks and module HE10 connector
General This table shows the correspondence between TELEFAST terminals and the module’s HE10 connector:
Kind of signal TELEFAST screw terminal block
(Terminal No.)
HE10 20-pin connector
(Pin No.)
100
101
102
103
104
1
2
3
4
5
105
106
107
108
109
110
111
1
2
112
113
114
115
+ 24 VDC
- 0 VDC
+ 24 VDC
- 0 VDC
6
7
8
9
10
11
12
17
18
19
20
13
14
15
16
+ 5 VDC
- 0 VDC
+10...30 VDC nc
Reference point cam input I0
(channel 0)
Emergency stop input I1
(channel 0)
Event input I2 (channel 0)
Recalibration input I3
(channel 0)
Reference point cam input I0
(channel 1)
Emergency stop input I1
(channel 1)
Event input I2 (channel 1)
Recalibration input I3
(channel 1)
Q0 reflex output (channel 0) nc
Q0 reflex output (channel 1) nc (1)
Auxiliary input sensor supply
Encoder supply
Channel 0 auxiliary inputs:
Channel 1 auxiliary inputs
Terminals 200 to 215 at + 24 VDC
197
Implementing
TELEFAST screw terminal block
(Terminal No.)
HE10 20-pin connector
(Pin No.)
3
4
200...215
Kind of signal
Terminals 200 to 215 at –0 VDC
300...315
Connecting shared sensors to: l l
+ 24 VDC if terminals 1 and 2 are connected,
- 0 VDC if terminals 3 and 4 are connected
On the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected by a wire to the shared voltage.
(1) nc = not connected
The same wiring applies to the TSX CAY 4• modules for channels 2 and 3, as well as for channel 2 of the TSX CAY 33 module.
198
Implementing
Connection using TSX CDP 301 or 501 strips
Introduction
Illustration
Connection using strips allows a direct connection to actuators, pre-actuators or terminals. This strand comprises 20 gage 22 wires (0.34 mm
2
) with a HE10 connector at one end and free wires at the other end, each identified using a color code.
This diagram shows the relation between the color of the wires and the pin number of the HE10 connector:
Cable: length
TSX CDP 301: 3 m
TSX CDP 501: 5 m
1 2
3
5
7
9 10
11 12
13 14
4
6
8
15 16
17 18
19 20 pre-wired strand brown yellow pink red violet red-blue brown-green yellow-brown gray-brown pink-brown white +5 VDC
0 VDC green +10...30 VDC gray nc
I0
I1
I2 blue black
I3
I0
I1
I2 gray-pink
I3 white-green Q0 nc white-yellow Q0 white-gray nc
+24 VDC
0 VDC white-pink +24 VDC
0 VDC
199
Implementing
Wiring precautions
General The I0, I1 and I3 inputs are rapid inputs, which should be connected to the sensor using either a twisted wire if it is a dry contact, or using shielded cables if it is a 2 or
3-wire proximity sensor.
The module integrates basic protection against short circuits or voltage inversions.
However, the module cannot remain operational for long with an error. You must therefore ensure that the fuses in series with the supply carry out their protective function. These are 1A maximum non-delay fuses, the supply energy must be sufficient to ensure their fusion.
Important note: wiring of Q0 static outputs
The actuator connected to the Q0 output has its shared point at 0 V of the supply. If for any reason (poor contact or accidental unplugging) there is a 0 V outage of the output amplifier supply, when the 0 V of the actuators remains connected to the 0 V supply, there may be enough mA output current from the amplifier to keep lowpower actuators locked.
Illustration:
+ + - -
+ + - -
IO I1 I2 Q0 IO I1 I2 Q0
204 104 205 105 206 106 112 312
+ + +
208 108 209 109 210 110 114 314
+ + +
RI RI
Connection via
TELEFAST
This kind of connection provides the most guarantees, on condition that the shared actuators are connected to the bar for shared points 200 to 215 (jumper wire in position 1-2). In this case there can be no outage of the shared module without an outage of the shared actuators.
200
Connection using strips
Implementing
This kind of connection must be carried out with the highest care and attention. It is recommended that you take special care in wiring this cable, for example using cable markers on screw terminals. It may be necessary to double the connections in order to ensure permanent contacts. When the actuator supply is a long distance away from the modules and close to the shared actuators, there may be an accidental break in the link between the latter and the 0 V or modules terminal
Illustration:
Critical wire
If there is a break of the supply section between A and B, there is a risk that the RL actuators may not remain operational. You must, if possible, double connections of
0 V supply to the modules.
Using TSX CDP 301/501 strips:
TSX CDP 301/501 strip white-pink white-gray white-green white-yellow gray-brown pink-brown terminal block connection
201
Implementing
7.6
Connecting the variable speed controller signals
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of variable speed controller signals.
This section contains the following topics:
Topic
Signal labeling
Connection using the TELEFAST pre-wiring system
Correspondence between TELEFAST terminals and HE10 connector
Page
202
Implementing
Signal labeling
General The TSX CAY modules implement basic management of the signals necessary for correct operation of the variable speed controllers. There is only one connector, regardless of the number of TSX CAY module channels.
Illustration:
COM0 1
3 nc
VALVAR1
COM2
5
7 nc
VALVAR3
9 10 nc
11 12
13 14 OK_VAR0
OK_VAR2 nc
15 16
17 18
19 20
6
8
2
4
VALVAR0
COM1 nc
VALVAR2
COM3 nc
OK_VAR1
Variable control inputs
OK_VAR3
0 V
0 V
24 V shared
I/O supply auxiliary
COMx – VALVARx: potential free contact to validate variable speed controller
OK_VARx: variable speed controller input check
24 V – 0 V sensor supply
Note: Each channel uses a potential free closing contact.
203
Implementing
Principle for connecting the variable speed controller I/O associated with channel 0
Illustration:
HE10 connector
To connect this HE10 connector, use the discrete ABE-7H16R20 TELEFAST wiring accessories and the TSX CDP 303 or TSX CDP 503 cable.
204
Connection using the TELEFAST pre-wiring system
Diagram of the principle
This diagram illustrates the principles for connection:
+ + - -
+ + - -
24 VDC supply
Implementing
(*)
1 P4 0 P4
P4
100 200 201 101 112 301
24 V
REFEN
DROK
GND24
24 V
REFEN
DROK
GND24
103 203 204 104 113 303
To connect directly, use the TSX CDP 301 or 501 strip (See Connection using TSX
CDP 301 or 501 strips, p. 199).
(*) Strap between 1 and 2: terminals 200 to 215 are +24 VDC.
205
Implementing
Correspondence between TELEFAST terminals and HE10 connector
General This table shows the correspondence between TELEFAST terminals and the module’s HE10 connector:
Kind of signal
113
114
115
+ 24 VDC
- 0 VDC
+ 24 VDC
- 0 VDC
1
2
3
4
200...215
109
110
111
112
105
106
107
108
TELEFAST screw terminal block
(Terminal No.)
100
101
102
103
104
18
19
20
14
15
16
17
10
11
12
13
8
9
6
7
4
5
2
3
HE10 20-pin connector
(Pin No.)
1
300...315
COM0
VALR0 nc
COM1
VALR1 nv
COM2 closed contact = variable speed controller confirmation
VALR2 nc
COM3
VALR3 nc
OK_VAR0
OK_VAR1
OK_VAR2
VARiable OK = voltage presence of the encoder supply
OK_VAR3
Auxiliary input sensor supply
Terminals 200 to 215 at +24 VDC
Terminals 200 to 215 at –0 VDC
Connecting shared sensors to: l l
+24 VDC if terminals 1 and 2 are connected,
- 0 VDC if terminals 3 and 4 are connected
On the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected by a wire to the shared voltage.
(1) nc = not connected.
206
Implementing
7.7
Electrical characteristics of modules
At a Glance
Subject of this section
What's in this
Section?
This Section introduces the different characteristics of the TSX CAY axis command modules.
This section contains the following topics:
Topic
General characteristics
Characteristics of the analog outputs
Characteristics of the counting inputs
Characteristics of auxiliary inputs
Characteristics of the Q0 reflex outputs
Monitoring sensor/pre-sensor voltage
Characteristics of the variable speed controller inputs
Characteristics of the relay outputs
Page
207
Implementing
General characteristics
Table of characteristics
This table shows the general characteristics of TSX CAY modules:
Maximum frequency of counting: absolute SSI encoder: transmission CLK frequency incremental encoder
200 kHz
Current used on internal 5 V
(ventilator in operation)
Module
CAY 2•
CAY 4•/33
500 kHz x 1
250 kHz x 4
Typical
1.1 A
1.5 A
Current used on the 24V sensor/ pre-sensor, outputs OFF
Current consumed by the module on the 10/30
V encoder at 24V (1)
CAY 2•
CAY 4•/33
Power dissipated in the module
CAY 2•
CAY 4•/33
Insulation resistance
Dielectric rigidity with ground connection or 0 V logical PLC
15 mA
30 mA
11 mA
22 mA
CAY 2•
CAY 4•/33
7.2 W (2)
10 W (2)
> 10 M
Ω
under 500 VDC
1000 Veff 50/60 Hz per min
Operating temperature
Storage temperature
Hygrometry (without condensation)
Operating altitude
0 to 60 °C
-25 °C to 70 °C
5% to 95%
< 2000 m
Max.
1.4 A
1.8 A
18 mA
36 mA
20 mA
40 mA
11.5 W (3)
17 W (3)
Note (1): absolute encoder and supply used exclusively in 24V.
Note (2): normal conditions of use: one active auxiliary input per channel
(under 24V).
Note (3): "worst" case and extreme conditions: all auxiliary inputs active
(under 30 V).
This module has a mini internal ventilator, which enables good working order in all temperatures. The ventilator is started up when necessary by the module’s internal temperature sensor (triggered at an external temp. of 45 °C).
It is possible to use external ventilation blocks (TSX FAN••), if the conditions around the module surpass the above parameters.
208
Implementing
Characteristics of the analog outputs
Table of characteristics
This table shows the characteristics of the analog inputs:
Parameters
Range
Real dynamic
Resolution
LSB value
Max. current supplied by an output
Value
+/- 10,24
+/- 10,24
13 bits + signs
1,25
1,5 fallback value
Monotony
Differential linearity
Accuracy max +/- 1
100
+ /- 2
0,5
Dielectric rigidity between the channels and the protective ground
1000 VAC
Units
V
V m V m A
LSB
%
LSB
% P.E.
Each output is protected against short circuits or overloads. In case of error, a signal is sent to the CPU using a status word. A short circuit of these outputs is not harmful to the module.
There is no check for an absent connector on the analog output.
209
Implementing
Characteristics of the counting inputs
Diagram Example of input A:
200 Ω
10 nF
190 Ω line check input A
Characteristics This table shows the characteristics of the counting inputs:
Electrical characteristics
Nominal voltage
Voltage limit
Nominal current
Input impedance (under 5 V) Re
Voltage for "On" state Uon
Current at "On" state
Voltage for "Off" state
Ion
Uoff
Current at "Off" state
Encoder/sensor voltage feedback check
Symbol
One
U1
In
Ioff
Presence check
Value
+/- 5
+/- 5,5
+/- 18
270
>= +2,4
> +3,7
<1,2
<1
Units
V
V mA
Ohms
V
mA
V mA
210
Implementing
Compatibility of
A, B, Z inputs
RS 422 / RS 485 line transmitter outputs, 7 mA current loop Differential line monitor on each input:
220
Ω line check
Outputs complemented by 5 V totem pole supply. Differential line monitor on each input:
220
Ω line check
211
Implementing
Characteristics of the return
+supply encoder inputs
Illustration:
+ return input supply encoder
0 V
Table of characteristics:
Characteristics
Voltage for ON state (OK)
Voltage limits
Input current (2.5 < Uok < 30)
Symbol
Uok
Umax
Imax
Value
> 2,5
30
3
Units
V
V mA
As long as the input is active, the presence of the encoder is detected.
212
Characteristics of auxiliary inputs
Illustration The inputs use 24 V from a supply provided via the connector.
Diagram:
24V sensors/pre-actuators
Monitoring: voltage
0 V sensor/pre-actuators
Implementing
213
Implementing
Characteristics Table of characteristics for auxiliary inputs:
Electrical characteristics
Nominal voltage
Voltage limits (1)
(ripple included)
Nominal current
Input impedance (at Unom)
Voltage for "On" state
Current at Uon (11 V)
Symbol
Un
U1
Utime (*)
In
Re
Uon
Ion
Value
24
19 to 30
34
8
3
>=11
>6
Unit
V
V
Voltage for "Off" state
Current at "Off" state
Uoff
Ioff
<5
<2
Immunity Off -->On (for I0, I2 and I3)
(for I1)
EVT input (on G07) ton 0.1 to 0.2
1 to 4 incremental encoder: 1
µ s absolute encoder:
≤
400
µ s
Dielectric rigidity with the ground connection 1500 Veff 50 / 60 Hz for 1 mn
IEC compatibility with sensors
2-/3-wire proximity sensor compatibility
Type of input
Logic type type 2 all proximity sensors function at 24 VDC current ducts
Positive (sink) mA k
Ω
V mA
V mA ms ms
(*) Utime: maximum permitted voltage for 1 hour in every 24 hours.
214
Implementing
Characteristics of the Q0 reflex outputs
General
Illustration
Each positioning channel has an output controlled by the processor and which allows the integrated command from an ordered axis function to be performed.
For example, a brake command between two shifts, safety etc. This output is static, the shared load is at 0 V of the sensor/pre-sensor voltage.
The output is protected against overloads and short circuits and in case of fault, information is made available to the processor about it.
Reflex output:
Supply check sensors /
pre-actuators command
Fault monitoring short-circuit
24 V
Q0
215
Implementing
Characteristics Table of characteristics:
Electrical characteristics
Nominal voltage
Voltage limits max for 1 hour in 24 hours (Utime)*
Nominal current
Max voltage fall "On"
Leakage current
Max current to 30 V and to 34 V
Communication time
Dielectric rigidity with the ground connection
Compatibility with direct current inputs
Value
24
19 to 30
34
V
V
Units
V
500
< 1 mA
V
< 0,3 mA
625
< 500 mA
µ s
1500 Veff 50/60 Hz per min
All positive logic inputs whose input resistance is less than 15 k
Ω
Yes
One signaling bit per channel
One bit per channel in write mode via program
IEC 1131 compatibility
Monitoring short-circuits of each channel
Reset l l via application program automatic
Protection against overloads and short-circuits
Protection against overvoltage of the channels
Protection against polarity inversions
Power of a lamp with filament
Using current limiter and thermal circuit breaker (0.7A< id < 2 A)
Zener (breakdown) between outputs and +24V
Using a reverse diode on the supply
10 W (max)
(*) Utime is the maximum voltage applicable to the module for 1 hour in a 24 hour period of operation.
216
Implementing
Monitoring sensor/pre-sensor voltage
General The supply for the actuators / pre-actuators is monitored by the module to signal to the processor any malfunction, which could lead to incorrect working order.
Table of characteristics:
Electrical characteristics
Voltage for OK state
Voltage for faulty state
Immunity OK --> Error
Immunity error --> OK
Inclusion of error
Inclusion of non-error
Symbol
Uok
Udef
Im.off
Im.on
Toff
Ton
Value
> 18
< 14
> 1
> 1
< 10
< 10
Units
V
V ms ms ms ms
217
Implementing
Characteristics of the variable speed controller inputs
General The auxiliary inputs of the variable speed controller are supplied by the same supply as the auxiliary input/outputs. This is not monitored by the module, but any loss in voltage less than 5 V on a CTRL_VAR input can signal to the processor a fault with the variable speed controller.
Illustration:
0V Speed drive
218
Table of characteristics
Implementing
Table of electrical characteristics:
Electrical characteristics
Nominal voltage
Voltage limits (1)
(ripple included)
Nominal current
Input impedance (at Un)
Voltage for "OK" state
Current at Uon (11 V)
Voltage for "Error" state
Current at "Error" state
Immunity OK --> Error
Immunity at Error --> OK
Dielectric rigidity with the ground connection
IEC 1131 compatibility with sensors
Logic type
Symbol
One
U1
Utime (*)
Value
24
19 to 30
34
8 In
Re
Uon
Ion
Uoff
Ioff toff ton
3
≥
11
> 3,5
< 5
< 1,5
1 to 4
1 to 4
1500 Veff 50/60 Hz per min
Type 1
Positive (sink)
(*) Utime: maximum permitted voltage for 1 hour in every 24 hour period.
mA
V mA ms ms
Units
V
V
V mA k
Ω
V
219
Implementing
Characteristics of the relay outputs
Illustration Each channel has a relay output.
Table of characteristics
This table describes the electrical characteristics:
Electrical characteristics
Direct voltage used
Switched current permitted in direct 30 V on resistive load
Minimum permitted load
Switching time
Dielectric rigidity: l between contacts and between channels l between contacts and ground connection
Value
5 to 30
200
1V/1mA
< 5
300 VAC per min
1000 VAC per min
Units
V mA ms
220
Appendices
8
Compatibility of the absolute encoders with the TSX CAY modules
General All absolute SSI encoders, 16 ≤ Number of data bits ≤ 25, Gray or binary code are compatible with the TSX CAY modules. For example: l IVO trademark l GM 400 0 10 11 01 l
24 Volts, Gray code, 0 header bits, 25 data bits, 0 status bits, without parity,
GM 401 1 30 R20 00
24 Volts, Gray code, 0 header bits, 25 data bits, 1 status bit, with even parity.
l l
Hengstler trademark l RA58-M/1212
24 Volts, Gray code, 0 header bits, 24 data bits, 1 status bit, without parity.
Stegmann trademark l AG 661 01
24 Volts, Gray code, 0 header bits, 25 data bits, 0 status bits, without parity.
l IDEACOD trademark l SHM506S 428R / 4096 / 8192 / 26
11-30 Volts, Gray code, 0 header bits, 25 data bits, 0 status bits, without parity,
221
Appendices
222
Step by step axis command
III
At a Glance
Subject of this part
What's in this
Part?
This Part deals with the implementation of step by step axis commands.
This part contains the following chapters:
Chapter
9
10
11
Chapter Name
Introduction to step by step axis command
Installation
Appendix
Page
223
Step by step axis command
224
Introduction to step by step axis command
9
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter introduces the step by step axis command.
This chapter contains the following topics:
Topic
General
Physical description
Standard functions
Page
225
Introduction
General
Step by step axis command offer
The TSX CFY 11/21 step by step axis command for Premium PLCs is offered to satisfy the demands of the machine manufacturers.
It is designed for machines, which require a step by step movement command by a motor linked with a sequential command by a programmable PLC.
Illustration:
FIP translator motor
226
At a Glance
Introduction
Two modules are available: l TSX CFY 11 module: an axis with a command output with one translator, l TSX CFY 21 module: two axes with two command outputs with two translators.
Illustration:
227
Introduction
Physical description
Description of step-by-step axis command modules.
TSX CFY 11 module:
Translator axis 0
I/O Discrete check translator axis 0
TSX CFY 21:
Translator axis 0
Translator axis 1
I/O Discrete translator check axis 0 and 1
228
Introduction
Standard functions
Illustration Summary of step-by-step axis command module:
Enable check
Monitoring of commands
Modes
Generator of pulses
Parameters for operation
Status
Cams and stops
Translator enable
Boost
+ pulses
- pulses or direction
Translator check
Loss of step
Loss of step check reactivation
Brake
Emergency stop
External stop
End limit stop -
End limit stop + reference point cam
External event
229
Introduction
Features of
TSX CFY 11/21 step-by-step axis command modules l l l l l l
Each axis of TSX CFM 11/21 axis command modules has: l inputs l l l a translator check input, an control input for loss of step, l l a + end limit input, l l a - end limit input, a reference point cam input, an event input, l an emergency stop input, l an external stop input, outputs brake output, pulse+ output, pulse - output or direction, loss of step control reactivation output, boost output, translator enable output.
230
Installation
10
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter deals with the installation of step-by-step axis command modules.
This chapter contains the following sections:
Section
10.1
10.2
10.3
10.4
Topic
General
Connection of translator signals
Connecting sensors/pre-actuators and supply modules
Electrical characteristics of modules
Page
231
Installation
232
Installation
10.1
General
At a Glance
Subject of this section
What's in this
Section?
This Section introduces general points for installing TSX CFY modules.
This section contains the following topics:
Topic
Necessary basic configuration
Installation procedure
General precautions for wiring
Page
233
Installation
Necessary basic configuration
Introduction
Maximum number of
TSX CFY • 1 modules per station
Step-by-step axis command modules can be installed in any slot of a TSX RKY•• rack. The rack power supply must be chosen according to the number of modules installed.
l l
Each step-by-step command module supports:
1 application-specific channel for TSX CFY 11 module,
2 application-specific channels for TSX CFY 21 module.
Since the maximum number of application-specific channels managed by a PLC station depends of the type of processor installed, the maximum number of l l
TSX CFY •1 modules in a PLC station will therefore depend on: the type of processor installed, the number of application-specific channels already used other than step-by-step command application-specific channels.
You should therefore make a global report at PLC station level to find out the number of application-specific channels already in use and thus define the number of
TSX CFY •1 modules which can be used.
Reminder of number of application-specific channels managed by each type of processor:
Processors
TSX P57 103
TSX P57 153
TSX P57 203 / PCX 57 203 / TSX P57 2•23
TSX P 57 253
TSX P 57 2623 / TSX P 57 2823
TSX P 57 303
TSX P57 353 / PCX 57 353 / TSX P57 3623
TSX P57 453 / TSX P57 4823
24
24
24
32
8
8
Number of "application-specific" channels managed
32
48
234
Installation
Installation procedure
General The module can be installed or removed without cutting the rack power supply, to ensure that a device is available.
CAUTION
Connection and disconnection of connectors
It is not recommended that you connect or disconnect the connectors with the translator power supplies, as some translators cannot cope with this action. The auxiliary input/output connector can be disconnected while switched on without damaging the module.
However, for safety reasons it is recommended that you turn off the auxiliary power supply before any type of disconnection.
Failure to follow this precaution can result in injury or equipment damage.
The module fixing screws and connectors must be correctly screwed in place in order to guarantee effective resistance to electrostatic and electromagnetic interference.
235
Installation
General precautions for wiring
General The power supply to sensors and actuators must be protected against overload or overvoltage by fast-blow fuses.
l l l when wiring use wires of sufficient size to avoid on-line voltage falls and overheating, keep sensor and actuator cables away from any source of radiation resulting from high-power electric circuit switching, all cables connecting the translators must be shielded, the shielding must be good quality and connected to the protective ground both for the module and the translator. Continuity must be ensured throughout connections. Do not transmit any other signals in the cable than those for the translators.
For reasons of performance the auxiliary inputs of the module have a short response time. You must therefore make sure that there is enough self-sufficient supply to these inputs to ensure the module continues to operate correctly in the event of a short power break. It is recommended that you use a regulated supply to ensure more reliable response times from the actuators and sensors. The 0 V supply must be connected to the protective ground nearest to the supply module output.
236
Installation
10.2
Connection of translator signals
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of translator signals.
This section contains the following topics:
Topic
Signal labeling
Connection to a translator with RS 422/485 interface
Connecting to a translator with NPN open collector interface
Page
237
Installation
Signal labeling
Diagram of the principle
This diagram illustrates the principles for labeling:
+ pulses output
- pulses output
(or direction)
Boost output
Enable output translator
Loss of step check
reactivation output
Translator check input
Loss of step check input insulated 0 V insulated 5 V nc: not connected
238
Description
Installation
Each module output signal is RS 485, for each output there is therefore a direct signal (+) and its complement (-). The outputs are TTL type current extraction compatible. The 5 V insulated voltage is only available, if necessary, to supply translator input and output. The 0 V is common to inputs and outputs. 5 V must only be used with translators with open collector outputs and TTL type inputs
(5 V insulated not provided by the translator).
Illustration:
+ output driver
RS 485
- output input
The proposed type of connection is direct wiring by soldering onto the connector: the
TSX CAP S15 (See
Overview of the TSX TAP S15•• wiring accessories, p. 134) kit
comprising a SUB-D connector and its protective cover.
239
Installation
Connection to a translator with RS 422/485 interface
Diagram of the principle
It is recommended that you use a shielded cable containing 7 twisted pairs.
The + and – wires of each module output signal must be connected in the same pair.
This diagram illustrates the principle of connection:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
12
13
14
5
6
7 NC
0V 8
5V 15 NC
3
4
9
1
2
10
11
+
-
+
-
+
-
+
-
+
-
-
-
-
NC
NC
NC
+ pulses
- pulses (or direction)
Boost,
Translator enable
Reactivation of loss of step check
Translator check
Loss of step check
TRANSLATOR
RS 422/485 input compatible
RS 422/485 outputs
240
Installation
Connecting to a translator with NPN open collector interface
Diagram of the principle
Only one wire is used per input/output signal. If the translator does not provide 5 V insulated voltage do not forget to supply the interface from the insulated 5 V provided by the module.
This diagram illustrates the principle of connection:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
9
10
3
4
-
-
-
14
5
6
11
12
13
-
-
7
0V 8
5V 15
NC
0V
+ pulses
- pulses (or direction)
Boost,
Translator enable
Reactivation of loss of step check
Translator check
Loss of step check
TRANSLATOR
TTL/5 V “source” compatible inputs
NPN open collector outputs
241
Installation
10.3
Connecting sensors/pre-actuators and supply modules
At a Glance
Subject of this section
What's in this
Section?
This Section deals with the connection of sensors/pre-actuators and supply modules.
This section contains the following topics:
Topic
Signal labeling
Connections
Connecting auxiliary inputs and outputs to processor.
Principle of connecting I/O channel 0
Connection using a TSX CDP 301/501 pre-wired strand
Connection with TELEFAST pre-wiring system
Availability of signals on TELEFAST
Correspondence between TELEFAST terminals and HE10 connector
Wiring precautions
Page
242
Installation
Signal labeling
Diagram of the principle
This diagram illustrates the principles for labeling signals:
I0 reference point cam
1 2 emergency stop 11
3
5
4
6
I3 event
I4 external stop channel 0 input
I5 limit-
+I2 end limit
I0 reference point cam emergency stop 11
+I2 end limit
7
9
11
8
10
12
I3 event
I4 external stop channel 1 input
I5 limit-
Q0 brake
Q0 brake
13
15
14
16 channel output 0 channel output 1
24V supply sensors/pre-actuators
17 18
19 20
0 V supply sensors/pre-actuators
The 0 V of sensors/pre-actuators is connected in the module to the protective ground by an R/C network with the value: R = 100M
Ω
/ C = 4.7 nF.
243
Installation
Connections
General There are several possible options for connecting the sensors/pre-actuators of the
TSX CFY 11 / 21 module. They can be connected directly by the TSX
CDP 301 / 501 (See
Connection using TSX CDP 301 or 501 strips, p. 199) strip or
via the Discrete TELEFAST pre-wiring system.
244
Installation
Connecting auxiliary inputs and outputs to processor.
General To ensure optimum operation, the event and reference point inputs have a weak immunity. It is recommended that you use contacts without bounce (proximity sensor for example).
245
Installation
Principle of connecting I/O channel 0
Diagram of the principle
This diagram illustrates the principles for connecting I/I channel 0:
TSX CFY 21 event reference point cam external stop emergency stop limitlimit+ idem channel 0 electro brake channel 0
Supply for sensors and pre-actuators
246
Description
Installation
The emergency stop or end limit switch contacts are open.
End limit switch contacts are not contacts which have to be wired in series with the emergency input. End limit switch contacts are used to command movement stop with deceleration. The end limit switch (ELS+) stops movement in the +direction, the end limit switch (ELS-) stops movement in the- direction. It is therefore important to positions them at the correct end of the axis (see diagram below).
Illustration: on-limit on-limit emergency stop
ELRP moving
EVT EL+
247
Installation
Connection using a TSX CDP 301/501 pre-wired strand
General Connection using a pre-wired strand enables direct contact to the actuators, preactuators or any terminal system. This strand comprises 20 gage 22 wires
(0.34 mm
2
) with a connector at one end and free wires at the other end, labeled using a color code.
248
Illustration This diagram shows the color code:
TSX CFY 21 cable: length:
TSX CDP 301 (3 m)
TSX CDP 501 (5 m)
Installation white brown green yellow gray pink blue red black violet gray-pink red-blue white-green brown-green white-yellow yellow-brown white-gray gray-brown white-pink pink-brown reference point cam event emergency stop external stop limit+ limitreference point cam event emergency stop external stop limit+ limitbrake Q0 channel 0 nc brake Q0 channel 1 nc
24 V
0 V
24 V
0 V channel 0 channel 1
249
Installation
Connection with TELEFAST pre-wiring system
Diagram of the principle
This connection is made using a TELEFAST 2 base: ABE-7H16R20.
TSX CDP 053 / 503
24 VDC sensors/pre-actuators supply
+ + - -
+ + - -
ABE-7H16R20
Example of wiring:
IO I1 I2 I3 I4 I5 Q0 IO I1 I2 I3 I4 I5 Q0
200
+
100
202
+
102
204
+
104
201
+
101
203
+
103
205
+
105 112
RI
312
-
206
+
106
208
+
108
210
+
110
207
+
107
209
+
109
211
+
111 114
314
RI
-
200
+
100
202
102
204
+ +
104
201
101
+
203
+
103
205
+
105 112
312
RI
-
206
+
106
208
+
108
210
+
110
207
+
107
209
+
109
211
+
111 114
314
RI
-
NO NC NC NO NO NC NO NC NC NO NO NC
200
+
100
202
102
204
+ +
104
201
+
101
203
+
103
205
+
105 112
312
RI
-
206
+
106
208
+
108
210
+
110
207
107
+
209
+
109
211
+
111 114
RI
314
-
NO NC NC NO NO NC NO NC NC NO NO NC
NO: normally open,
NC: normally conductor.
250
Availability of signals on TELEFAST
Illustration This diagram shows the availability of signals on TELEFAST:
Installation
(1) At the ABE-7H16R20 base, the position of the jumper wire determines the polarity of all terminals from 200 to 215: l l jumper wire in position 1 or 2: terminals 200 to 215 have + polarity, jumper wire in position 3 or 4: terminals 200 to 215 have - polarity,
(2) At the ABE-7H16R20 base, it is possible to add an optional ABE-7BV20 strip to create a second shared sensor (+ or - according to user’s choice).
251
Installation
Correspondence between TELEFAST terminals and HE10 connector
General This table shows the correspondence between TELEFAST terminals and the module’s HE10 connector:
Nature of signal
112
113
114
115
+ 24 VDC
- 0 VDC
+ 24 VDC
- 0 VDC
3
4
1
2
200...215
104
105
106
107
108
109
110
111
TELEFAST screw terminal block
(Terminal No.)
100
101
102
103
300...315
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
HE10 20-pin connector
(Pin No.)
I0 cam reference point channel 0
I3 event
I1 emergency stop
I4 external stop
I2 limit
I5 limit
I0 cam reference point channel 1
I3 event
I1 emergency stop
I4 external stop
I2 limit+
I5 limit-
Q0 brake output nc
Q0 brake output nc (1) channel 0 channel 1
Auxiliary input sensor supply
Terminals 200 to 215 at +24 VDC
Terminals 200 to 215 at –0 VDC
Connecting shared sensors to: l l
+24 VDC if terminals 1 and 2 are connected,
- 0 VDC if terminals 3 and 4 are connected
On the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected by a wire to the shared voltage.
(1) nc = not connected
For a TSX CFY 11 module, the signals corresponding to the channel are not connected.
252
Installation
Wiring precautions
General To ensure the best performance, inputs I0 to I5 are rapid inputs. If the actuator is a dry contact, the inputs must be connected by a twisted pair, or by a shielded cable if the sensor is a two or three-wire proximity detector.
The module includes as standard basic protection against short circuits or voltage inversions. However, the module cannot remain operational for long with an error.
You must therefore ensure that the fuses in series with the supply carry out their protective function. These are 1A maximum fast-blow fuses, the supply energy must be sufficient to ensure their fusion.
Important note: wiring of Q0 static outputs
The actuator connected to the Q0 brake output has its shared pin connected to supply 0 V. If for any reason there is a 0 V outage of the output amplifier supply
(e.g. poor contact or accidental unplugging), when the 0 V of the actuators remains connected to the 0 V supply, there may be enough mA output current from the amplifier to keep low-power actuators triggered.
Illustration:
+ + - -
+ + - -
IO I1 I2 Q0 IO I1 I2 Q0
204
+
104
205
+
105
206
+
106 112
312
208
+
108
209
+
109
210
+
110 114
314
RI RI
253
Installation
Connection via
TELEFAST
This kind of connection is the most guaranteed, on the condition that the shared actuators are connected to the 200 to 215 shared points strip (jumper wire in position
1-2). In this case there can be no outage of the shared module without an outage of the shared actuators.
254
Installation
Connection using a TSX
CDP 301 / 501 pre-wired strand
This kind of connection must be carried out with the greatest care and attention. It is recommended that you take special care in wiring this cable, for example using the cable ferules on screw terminals. It may be necessary to double the connections in order to ensure permanent contacts. When the actuator supply is a long distance away from the modules and close to the shared actuators, there may be an accidental break of the link between the latter and the 0 V terminal of the module(s).
Illustration:
TSX CFY 11/21
Supplying actuators
Critical wire
If there is a break of the supply section between A and B, there is a risk that the RL actuators may not remain operational. You must, if possible, double connections of
0 V supply to the modules.
Connection using a TSX CDP 301 / 501 pre-wired strand:
TSX CFY 11/21
HE10
17 white-pink white-gray
19 white-green
13
15 white-yellow
RL
24 V
0 V
RL
0VDC
18
20 gray-brown pink-brown
0VDC user connection terminal block
255
Installation
10.4
Electrical characteristics of modules
At a Glance
Subject of this section
What's in this
Section?
This Section introduces the different electrical characteristics of TSX CFY modules.
This section contains the following topics:
Topic
General characteristics
Characteristics of translator inputs (SUB-D connector)
Characteristics of translator outputs (SUB-D connector)
Characteristics of auxiliary inputs (HE10 connector)
Characteristics of Q0 brake output
Page
256
General characteristics
Table of characteristics
This table introduces the general characteristics of TSX CFY modules:
Maximum frequency of pulses
Current consumed on internal 5 V
Current consumed by the module on sensor/pre-actuator 24V with no sensor/ pre-actuator current
Power dissipated in the module
Module
TSX CFY 11
TSX CFY 21
TSX CFY 11
TSX CFY 21
187.316 KHz
Value
510 mA
650 mA
50 mA
100 mA
Insulation resistance
Dielectric rigidity between I/O "translator" and protective ground or PLC logic
Operating temperature
Storage temperature
Hygrometry (without condensation)
Operating altitude
TSX CFY 11
TSX CFY 21
3.8 W
5.6 W
> 10 M
Ω
under 500 VDC
1000 Veff 50 / 60 Hz for 1 mn
0 to 60 °C
-25 °C to 70 °C
5% to 95%
< 2000 m
Installation
257
Installation
Characteristics of translator inputs (SUB-D connector)
Diagram These inputs have positive logic current extraction:
Characteristics The following table shows the characteristics of translator inputs:
Characteristics
Nominal current
(Ue = 0 V)
Voltage for ON state
Voltage for OFF state
Immunity of loss of step input
Immunity of translator error input
Symbol
Ie
Uon
Uoff
Value
4,5
2
3,6
15 to 30
3 to 10
Unit mA
V
V
µ s ms
258
Installation
Characteristics of translator outputs (SUB-D connector)
Table of characteristics
These outputs are insulated RS 422/485. There are two complemented outputs per signal.
Characteristics
Differential voltage output on R load
≤
100
Ω
Short-circuit current
Permitted shared mode voltage
Permitted differential voltage
Values
+/- 2
< 150
≤
7
≤
12
Units
V mA
V
V
259
Installation
Characteristics of auxiliary inputs (HE10 connector)
Illustration Diagram:
260
Installation
Characteristics Table of characteristics for auxiliary inputs:
Electrical characteristics
Nominal voltage
Nominal voltage limits
(ripple included)
Nominal current
Input impedance (at Unom)
Voltage for "On" state
Current at Uon (11 V)
Voltage for "Off" state
Current at "Off" state
Input immunity:
Cam reference point input and event
Other inputs
IEC 1131 compatibility with sensors
Compatibility with 2 and 3-wire sensors
Type of input
Logic type
Pre-actuator voltage check
Time of supply detection
Symbol
Un
U1
Utime (1)
In
Re
Uon
Ion
Uoff
Ioff
3,4
≥
11
>6
<5
<2
Value
24
19 to 30
34
7
Unit
V
V mA k
Ω
V mA
V mA supply threshold OK supply threshold error supply OK supply error ton/toff (2) ton/toff
< 250
3 to 10
µ s ms type 2 all proximity sensors supplied at 24 VDC current ducts
Positive (sink)
> 18
< 14
< 30
> 1
V
V ms
ms
(1) Utime: maximum permitted voltage for 1 hour in every 24 hours.
(2) Inputs: reference point cam and events are fast inputs (response time < 250 µ s) compliant with maximum frequency of 187.316 KHz of translator command outputs.
261
Installation
Characteristics of Q0 brake output
Illustration Brake output:
Supply check sensors / pre-actuators
Fault monitoring short-circuit command
+
-
24V
Q0
262
Characteristics
Installation
Table of characteristics:
Electrical characteristics
Nominal voltage
Voltage limits
Temporary voltage
Nominal current
Max voltage fall "On"
Leakage current at "OFF" state
Load impedance
Max current to 30 V and to 34 V
Communication time
Electro unload time
Max switching frequency
(on inductive load)
Compatibility with inductive inputs
Value
24
19 to 30
34 (1)
500
< 1 mA
V
< 0,3 mA
80<Zon<1500
Ω
625
< 250 mA
µ s
< L/R s
F<0.6 / (LI
2
)
Hz
V
V
Unit
V
IEC 1131 compatibility
Protection from overloads and short-circuits
Monitoring short-circuits of each channel
Reset l l via application program automatic
Protection against channel overvoltage
Any input whose Re is less than 15 k
Ω
and has positive logic
Yes by current limiter and circuit breaker thermal, signaling: 1 bit per channel
One bit per module
Protection against polarity inversions
Power of a filament lamp
Pre-actuator voltage check
Reaction time of voltage check
Zener (55 V) between outputs and
+24 V
Using a reverse diode on the supply
8 W
OK if supply >
18 (ascending) not OK if supply
< 14
(decreasing)
V
V
NOK --> OK<30
OK --> NOK>1 ms ms
(1) maximum permitted voltage for 1 hour in every 24 hours of operation.
263
Installation
264
Appendix
11
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter is an appendix which deals with the compatibility of translators with
TSX CFY modules, and with the installation of these modules with Phytron translator.
This chapter contains the following topics:
Topic
Translators compatible with TSX CFY 11/21
Connection of Phytron translators with TSX CFY 11/21 modules
Page
265
Appendix
Translators compatible with TSX CFY 11/21
Phytron
Translator
Reference table:
Manufacturers
Phytron Elektronik
References
MSD MINI 172/140 (17 A: 140 V)
MSD MINI 172/70 (17 A: 70 V)
SP MINI 92/70 (9 A: 70 V)
SP MINI 72/70 (7 A: 70 V)
SP MINI 52/70 (5 A: 70 V)
Other translators Reference table:
Manufacturers
Others
References
All RS 422 / RS 485 translators: l RS 422 / RS 485 differential inputs or TTL/5
V "source" compatible inputs, l RS 422 / RS 485 differential outputs or NPN open collector outputs.
266
Appendix
Connection of Phytron translators with TSX CFY 11/21 modules
Connection diagrams
The TSX CXP 611 cable is designed to facilitate connection between TSX
CFY 11/21 modules and Phytron Elektronik range translators, MSD MINI series and
SP MINI:
TSX CFY 21 Phytron Translator
TSX CXP 611
(6 meter length)
TSX CFY 11/21 TSX CXP 611 cable
+ pulses
- pulses
+ Direction
- Direction
On + supply
On - supply
+ Enable
- Enable
Reactivate + default
Reactivate - default
Translator ready
Fault
Insulated 0 V
Translator
Phytron
267
Appendix
268
TSX CCY 1128 Cam module
IV
At a Glance
Subject of this part
What's in this
Part?
This Part deals with the TSX CCY 1128 Cam module.
This part contains the following chapters:
Chapter
12
13
14
15
16
17
18
Chapter Name
Introduction to the TSX CCY 1128 electronic cam module
General instructions for installing the TSX CCY 1128 module
Connecting an incremental and absolute SSI encoder to the
TSX CCY 1128
Connecting the auxiliary inputs and track outputs of the
TSX CCY 1128
TSX CCY 1128 module displays
TSX CCY 1128 module electrical characteristics
Connecting an absolute encoder with parallel outputs to
TSX CCY 1128
Page
269
TSX CCY 1128 Cam module
270
Introduction to the TSX CCY 1128 electronic cam module
12
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter introduces the TSX CCY 1128 electronic cam module
This chapter contains the following topics:
Topic
Introduction to the TSX CCY 1128 in its environment
Physical introduction of the TSX CCY 1128
Electronic cam function of the TSX CCY 1128
TSX CCY 1128 compatibility with the installed base
Page
271
Introduction to the TSX CCY 1128
Introduction to the TSX CCY 1128 in its environment
Introduction
Operating principle
Installation diagram
The TSX CCY 1128 module is a standard application-specific module in the
Premium range, which integrates with the TSX RKY •• rack of a TSX/PMX/PCX 57
PLC station. It executes the "electronic cam" function for a rotational, alternative, cyclic or endless axis, managed by an incremental or absolute type encoder.
The module manages up to 128 cams independently, which can be distributed to a maximum of 32 tracks to which up to 24 physical and 8 logical outputs can be assigned. When the PLC processor has transmitted the configuration and calibration information, the module, independently of the PLC cycle, processes the cam program and controls the track outputs. The module’s various functions are described in the application-specific "electronic cam" manual –
Reference 35001381.
The diagram below represents a basic configuration of an installation
Example: TSX 57 PLC station
Machine
Command elements
Programming and adjustment terminal equipped with PL7
Junior/Pro software
TSX CCY 1128
Encoder signals
Auxiliary inputs
Encoder
Sensors
Track outputs
Actuators
272
Introduction to the TSX CCY 1128
Physical introduction of the TSX CCY 1128
Introduction
Appearance of the module
The input and output interface connectors for the machine are located on the front panel of the module. The connector for the X bus is situated on the back. All of the processor’s data and command signals travel via this bus.
The diagram below represents the TSX CCY 1128 module and its various elements
273
Introduction to the TSX CCY 1128
Elements and their function
4
5
6
7
Number Elements
1 Screw
2
3
Module casing
Display block comprising 4
LEDs:
• green LED RUN
• red LED ERR
• red LED I/O
• green LED CH0
15 pin SUB D connector
HE 10 connector
HE 10 connector
HE 10 connector
Functions
Ensures that the module is properly fixed to the
TSX RKY •• rack
Ensures the following functions:
• support and protection of the electronic boards,
• locking of the module in its slot,
• support of the connectors.
Displays state and errors of the module as well as the channel diagnostics.
Indicates the operating mode of the module,
Indicates an internal module error,
Indicates an external module error or an application fault,
Allows channel diagnostics.
(The various states of the LEDs and their meanings are described in Chapter 6).
Allows connection to the encoder.
Allows connection to group 0 and 1 track outputs
Allows connection to group 2 and 3 track outputs
Allows connection to auxiliary inputs and encoder supply.
274
Introduction to the TSX CCY 1128
Electronic cam function of the TSX CCY 1128
Introduction
Illustration
The electronic cam function controls the module’s outputs according to the position l l l l of the encoder installed on the machine. Several encoder types can be used: incremental encoder with RS 422/ RS 485 line transmitter outputs, incremental encoder with Totem Pole outputs, absolute SSI encoder with series outputs, absolute encoder with parallel outputs. The use of this encoder requires a
TELEFAST ABE-7CPA11 interface, which converts parallel output signals into series output signals.
The diagram below represents the various types of encoder, which can be connected to the module.
Incremental encoder
RS 422/485 or Totem Pole
Absolute encoder with SSI serial connection
TELEFAST ABE-7CPA11
Absolute encoder with parallel outputs
275
Introduction to the TSX CCY 1128
TSX CCY 1128 compatibility with the installed base
Hardware compatibility
Software compatibility
In order to receive the TSX CCY 1128 module, the PLC station must have a processor of software version SV 3.3 or above at its disposal.
To develop an application that uses the TSX CCY 1128, the PL7 Junior/Pro software must be of version SV 3.4 or above
276
General instructions for installing the TSX CCY 1128 module
13
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter describes the general instructions for installing the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
Installing the TSX CCY 1128 in a PLC station rack
Installing the TSX CCY 1128 in a PLC station
Number of application-specific channels managed by one PLC station
Installation precautions for the TSX CCY 1128
General wiring instructions
Selecting and protecting auxiliary power supplies
Choice of encoders for the TSX CCY 1128
Page
277
General instructions for installation
Installing the TSX CCY 1128 in a PLC station rack
Introduction
Illustration
The TSX CCY 1128 module can be installed into all the available slots of the
TSX RKY •• rack of a TSX 57/PMX 57/PCX 57 PLC station, with the exception of the slots taken up by the supply and processing modules.
The diagrams below show the procedure for installing a module from the Premium range onto the TSX RKY •• rack.
Procedure The table below describes the procedure:
Step
1
2
3
Action
Insert the pins at the back of the module into the centering holes located on the lower part of the rack.
Twist the module to bring it into contact with the support.
Fix the module onto the rack using the screw located on the upper part of the module. Maximum screw tightening: 2.0 N. m
278
General instructions for installation
Installing the TSX CCY 1128 in a PLC station
Introduction The TSX CCY 1128 module can be installed onto all PLC station racks: l TSX RKY•• extendable racks located on the main segment of bus X,
(the segment on which the rack supporting the processor is installed).
l TSX RKY•• extendable racks located on the remote segments of bus X.
Installation onto a rack belonging to the main segment of bus X
The diagram below represents the installation of the module onto a rack belonging to the main segment of bus X. The module can be installed onto the rack supporting the processor and onto all other racks present on bus X. The distance between the rack supporting the module and the rack supporting the processor must not exceed
100 meters.
Installing the module
Bus X < 100 m
TSX CCY 1128
Application specific module
Processor
279
General instructions for installation
Installing onto a rack belonging to a remote segment of bus X
The diagram below represents the installation of the module onto a rack belonging to the remote segments of bus X. The distance between the rack supporting the module and the rack supporting the processor must, under no circumstances, exceed 225 meters.
Installing the module
< 225 m
Remote location of Bus X via TSX REY 200
TSX CCY 1128
Application specific module
Processor
Remote location of Bus X via
TSX REY 200 module
< 225 m
Bus X <
100m
Processor
Remote Bus X segment
280
General instructions for installation
Number of application-specific channels managed by one PLC station
Definition of an applicationspecific channel
An application-specific module (TSX CTY• counting modules, TSX CAY• axis command modules, TSX CFY• step by step command modules, TSX YSP Y• weighing modules, TSX CCY 1128 electronic cam modules, etc.) uses a number of channels, varying from 1 to n according to the module type; these channels are called application-specific channels.
Reasons for counting the number of applicationspecific channels of a station
Number of applicationspecific channels managed by each type of processor l l
To determine: the power of the processor to be installed the maximum number of application-specific modules that can be installed in the station.
The table below shows the number of channels managed by each type of processor:
Type of processor
TSX P57 102 / TPMX P57 102 / TPCX 57 1012
TSX P57 202 / TPMX P57 202
TSX P57 252
TSX P57 302
TSX P57 352 / TPMX P57 352 / TPCX 57 3512
TSX P57 402
TSX P57 452 / TPMX P57 452
24
32
32
48
48
Number of application-specific channels managed
8
24
Number of applicationspecific channels for a
TSX CCY 1128 module
A TSX CCY 1128 module has one application-specific module at its disposal.
281
General instructions for installation
Installation precautions for the TSX CCY 1128
Installation
Installing and removing the module
In order to guarantee good working order, it is necessary to take certain precautions during its installation and removal, when plugging and unplugging the connectors on the front panel of the module, and when adjusting its fixing screws and the SUB D
15-pin connector.
The module can be installed or removed without cutting the supply to the rack. The design of the module allows this action to be carried out with the power on in order to ensure the availability of the device.
Plugging and unplugging the connectors on the front panel of the module
It is not recommended that you plug in or unplug the connectors located at the front panel of the module when the sensor/pre-sensor supply is switched on.
Reasons: l the encoders will not tolerate a simultaneous start-up or outage of the signals and supplies.
l The track outputs can become damaged if they are in state 1 and connected to an inductive supply
Adjusting the screws and locking the HE10 connectors in place
In order to ensure good electrical contact between the devices and by doing so create effective resistance to electrostatic and electromagnetic interference: l the fixing screws on the module and the SUB D 15-pin connector must be correctly screwed in.
l l l tightening on the module’s fixing screw: 2.0 N.m
tightening on the SUB D 15-pin connector’s fixing screw: 0.5 N.m
The HE10 connectors must be correctly locked.
282
General instructions for installation
General wiring instructions
Introduction In order to guarantee that the automatism operates correctly, it is necessary to respect some basic rules.
Section of wires used
Must be of sufficient size to avoid on-line voltage falls and overheating.
Cable path.
The encoder connector cables, the other sensors and the pre-actuators must be kept away from any source of radiation resulting from high-power electric circuit switches and which could cause malfunctions.
Encoder signal connector cables l l l
The module/encoder connector cables must adhere to the following rules:
They must be shielded using a high quality shielding, they must only carry related signals to the encoder, the cable shielding must be linked to the protective ground connection both at the l module and the encoder, the grounding must be continuous throughout the connection.
283
General instructions for installation
Selecting and protecting auxiliary power supplies
Introduction
Type of power supply
Encoders, sensors and pre-actuators associated with the module require auxiliary power supplies (5VDC and/or 24VDC).
Only use regulated power supplies to: l l ensure optimum reliable response time for sensors and pre-actuators, increase the reliability of devices by minimum heating of module I/O circuits.
These power supplies must be independent enough (> 10ms) to override micropower outages and ensure the module continues to run effectively.
Protecting power supplies
The power supplies for encoders, other sensors and pre-actuators MUST be protected from overloads and short-circuits by appropriately calibered fast-blow fuses.
Connection of the 0V supply to the protective ground:
The 0V supply must be connected to the protective ground nearest to the supply module output.
General rules for installing the encoder power supply module l l l this must be used only for supplying the encoder, it must be independent enough to override micro-power outages (> 10ms).
it must be placed as close as possible to the TSX CCY 1128 module to reduce circuit capacities to the maximum.
284
General instructions for installation
Choice of encoders for the TSX CCY 1128
Introduction The TSX CCY 1128 module inputs are able to receive signals from the following l l l encoders: incremental, absolute with SSI serial outputs, absolute with parallel outputs. This last type requires the use of a specific interface TELEFAST ABE-7CPA11.
The user can choose from these encoder types according to the requirements.
Encoder output interface
The table below summarizes the main characteristics of the output interface for the encoder types normally used.
Type of encoder
Supply voltage
Incremental 5 VDC
Absolute with SSI outputs
10...30 VDC
10...30 VDC
Absolute with parallel outputs
5 VDC or
10...30 VDC
Output voltage
Types of interface
5 VDC differential Outputs with line transmitters to
RS 422 standard, with 2 outputs per signal A+/A-, B+/B-, Z+/Z-
10...30 VDC Totem Pole outputs with one output per signal A, B, Z
5 VDC differential Output with line transmitters to RS
422 standard for the data signal
(Data SSI)
RS 422 compatible input for the clock signal (CLK SSI).
5 VDC or 10...30
VDC
Parallel outputs. Require the use of the Telefast ABE-7CPA11 interface to transform parallel output signals into serial signals.
Encoder supply The design of the module allows an encoder supply of: l 5 VDC l 24 VDC, standardized voltage in the 10…30 VDC format.
The choice of supply voltage is dependent on the encoder supply voltage.
285
General instructions for installation
5 VDC encoder supply
For encoders with a 5 VDC supply, voltage falls must be taken into account.
These are dependent upon: l l l the length of the cable between the module and the encoder (double length), the section of wire, the encoder consumption.
The acceptable voltage fall for the encoder is generally 10% of the nominal voltage.
The table below gives the on-line voltage fall, according to the section of the wire, for a 100 meter length of wire with a given encoder consumption.
Section of wire
0.22 mm = gauge 24
0.34 mm = gauge 22
0.5 mm
1 mm
Voltage fall for a 100 meter length of wire with an encoder consumption of:
50 mA
0.4 V
100 mA
-
150 mA
-
200 mA
-
0.25 V
0.17 V
0.09 V
0.5 V
0.34 V
0.17 V
-
0.51 V
0.24 V
-
-
0.34 V
CAUTION
Recommendation for a 5 VDC encoder supply voltage
It is dangerous to raise the supply voltage of the encoder to compensate for an on-line voltage fall. After a break in the supply, there is a risk of an overvoltage at the module inputs.
Failure to follow this precaution can result in injury or equipment damage.
24 VDC encoder supply
Encoders with a supply voltage of 24 VDC are recommended for the following reasons: l the supply source does not need to be completely accurate. As a general rule, these encoders use a supply format of 10…30 V.
l an on-line voltage fall is of little significance due to a substantial distance between the module and the encoder.
Ground connection continuity
In order to ensure correct operation during interference, it is vital: l to choose an encoder with a metal casing that is referenced to the protective ground of the connected device.
l that the ground connection is continuous between: l l l the encoder, the shielding of the connector cable, the module.
286
Connecting an incremental and absolute SSI encoder to the
TSX CCY 1128
14
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter describes the procedure for connecting an incremental and absolute
SSI encoder to the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
Principles for connecting an encoder to a TSX CCY 1128
Connecting an incremental encoder with RS422 outputs to the TSX CCY 1128
Connecting an incremental encoder with Totem Pole outputs to the
TSX CCY 1128
Page
Connecting an absolute SSI encoder to the TSX CCY 1128
Connecting an encoder supply monitor to the TSX CCY 1128
Connecting the encoder supply to the TSX CCY 1128
TSX CAP S15 connection accessory
TSX TAP S1505/S1524 and TSX CCP S15• connection accessories
287
Connecting an incremental and absolute SSI encoder
Principles for connecting an encoder to a TSX CCY 1128
Connection interfaces
Illustration
The 15-pin SUB D connector, located on the front panel of the module, allows the connection of encoder and module. This connector carries: l l all signals travelling to or from the encoder, the encoder supply source, which is also connected: l either by a TELEFAST ABE-7H16R20 cable interface. l or directly, using a TSX CDP •01 prewired strand
The design of the module allows the encoder to be connected at either 5VDC or
10…30VDC.
The diagram below shows the principles for connecting an encoder to a TSX CCY
1128 module.
TSX CCY 1128 SUB D 15 pins connextor 5VCC ou 10..30VCC
Encoder power supply
Encode
Module/encoder connection system
(cables + connectors)
TSX CDP •01
Prewired cable
OR
TSX CDP ••3
Cable
TELEFAST ABE-7H16R20
5VDC ou 10..30VDC
Encoder power supply
5VDC ou 10..30VDC
Encoder power supply
288
Connecting an incremental and absolute SSI encoder
Connecting an incremental encoder with RS422 outputs to the TSX CCY 1128
Pinouts of the module’s 15-pin
SUB D connector
The pinout configuration of the module’s 15-pin SUB D connector, for connection to an incremental encoder with RS 422 outputs, are as follows:
Diagram (front view)
Pin No.
Signal Designation
7
8
5
6
3
4
1
2
9
10
11
12
13
14
15
A+ 5V
A-
-
Z+ 5V
Encoder input, pulse A+ (5VDC)
Encoder input, pulse A-
-
Encoder input, zero latch pulse Z+ (5VDC)
Z-
-
Encoder input, zero latch pulse Z-
-
10…30 V Encoder supply output (+ 10…30VDC)
0 V Encoder supply output (- 0VDC)
-
B+
B-
-
EPSR
-
5 V
-
Encoder input, pulse B+ (5VDC)
Encoder input, pulse B-
-
Positive encoder supply feedback input. Receives positive supply feedback from the encoder, which allows the module to verify the encoder’s presence.
-
Encoder supply output (+ 5VDC)
289
Connecting an incremental and absolute SSI encoder
Diagram showing the A, B and Z encoder inputs of the module
The diagram below shows an A, B or Z encoder input used with an incremental encoder equipped with: l l a high-level output with a line transmitter, a 5VDC output voltage to the RS 422 standard.
Note: Note: each A, B and Z input uses a differential line monitor.
Diagram of input A
This diagram shows the equivalent circuit diagram of input A.
The diagram is identical for inputs B and Z.
Connection process diagram
The diagram below describes the process of connecting a TSX CCY 1128 module to an incremental encoder with RS 422 outputs and a 5VDC supply.
TSX CCY 1128
Encoder
A
B
Z
EPSR
+ 5 VDC
- 0 VDC
1
2
9
3
4
5
6
12
13
14
7
11
15
8
10
1
3
4
2
5
6
8
12
10
A+
A-
B+
B-
Z+
Z-
Return supply + supply + supply -
290
Recommendations
Connecting an incremental and absolute SSI encoder l l
When connecting, adhere to the following recommendations:
Connect each signal encoder A+/A-, B+/B-, Z+/Z-, using a twisted pair.
l
Connect each supply point using a twisted pair, in order to reduce the on-line voltage falls.
Connect both terminals of the cable shielding to the protective ground.
CAUTION
Recommendations on the pinout configuration of the encoder inputs/outputs
Before connecting the encoder to the module, check the pinout configuration given by the encoder’s manufacturer.
Failure to follow this precaution can result in injury or equipment damage.
291
Connecting an incremental and absolute SSI encoder
Connecting an incremental encoder with Totem Pole outputs to the
TSX CCY 1128
Pinout configuration of the module’s 15pin SUB D connector
The pinout configuration of the module’s 15-pin SUB D connector, for connection to an incremental encoder with Totem Pole outputs, is as follows:
Diagram
(front view)
Pin No.
Signal Designation
7
8
5
6
3
4
1
2
9
10
11
12
13
14
15
-
A-
-
Input to be connected to 0V encoder
B+ 24V Encoder input, pulse B+ (10…30VDC)
-
Z-
-
Input to be connected to 0V encoder
-
10…30 V Encoder supply output (+ 10…30VDC)
0 V Encoder supply output (- 0VDC)
A+ 24V Encoder input, pulse A+ (10…30VDC)
-
B-
Z+ 24V
EPSR
Input to be connected to 0V encoder
Encoder input, zero latch pulse Z+ (10…30VDC)
Positive encoder supply feedback input. Receives positive supply feedback from the encoder, which allows the module to verify the encoder’s presence.
-
5 V
-
Encoder supply output (+ 5VDC)
292
Connecting an incremental and absolute SSI encoder
Diagram showing the A, B and Z encoder inputs of the module
The diagram below shows an A, B or Z encoder input used with an incremental encoder equipped with: l l a Totem Pole type high-level output, an output voltage of 10…30VDC.
Note: l differential assembly is not possible, the negative polarity of each input (A-, B- and Z-), must be linked to the 0V encoder and the positive inputs (A+, B+ and l
Z+) to encoder outputs A+, B+ and Z+.
No line monitoring.
Diagram of input A
This diagram shows the equivalent circuit diagram of input A.
The diagram is identical for inputs
B and Z.
293
Connecting an incremental and absolute SSI encoder
Connection process diagram for the encoder
The diagram below describes the process of connecting an incremental encoder with Totem Pole outputs, with a 10...30VDC supply.
TSX CCY 1128
A
B
Z
EPSR
+ 10...30 VDC
- 0 VDC
7
8
1
2
5
9
10
3
4
11
12
13
6
14
15
A+
B+
Z+
Return supply + supply + supply -
Encoder
Recommendations l l l connect the positive encoder supply to pin 7 of the module’s 15-pin SUB D connector, connect the module’s EPSR input to the positive supply if the encoder does not have a positive supply feedback output. connect both terminals of the cable shielding to the protective ground.
CAUTION
Recommendations on the pinout configuration of the encoder inputs/outputs
Before connecting the encoder to the module, check the pinout configuration given by the encoder’s manufacturer.
Failure to follow this precaution can result in injury or equipment damage.
294
Connecting an incremental and absolute SSI encoder
Connecting an absolute SSI encoder to the TSX CCY 1128
Pinout configuration of the module’s
15-pin SUB D connector
The pinout configuration of the module’s 15-pin SUB D connector, for connection to an absolute SSI encoder, is as follows:
Diagram
(front view)
Pin No.
Signal Designation
1
2
7
8
9
10
5
6
3
4
11
12
13
14
15
-
positive
SSI data negative
SSI data
-
CLK +
Encoder input, positive SSI data (5VDC)
Encoder input, negative SSI data
-
-
-
Encoder output, positive SSI CLK (5VDC)
-
-
10…30 V Encoder supply output (+ 10…30VDC)
0 V Encoder supply output (- 0VDC)
-
-
-
-
EPSR
CLK -
5 V
-
-
Positive encoder supply feedback input. Receives positive supply feedback from the encoder, which allows the module to verify the encoder’s presence.
Encoder output, negative SSI CLK
Encoder supply output (+ 5VDC)
295
Connecting an incremental and absolute SSI encoder
Diagram of the module’s SSI
Data encoder input
The diagram below shows the SSI Data encoder input used with an absolute SSI encoder equipped with: l l a high-level output with a line transmitter, a 5VDC output voltage to the RS 422/RS 485 standard.
Note: The SSI Data input uses a differential line monitor.
Diagram of input A
This diagram shows the equivalent circuit diagram of input A.
The diagram is identical for inputs B and Z.
Diagram showing the process for connecting an absolute SSI encoder
The diagram below describes the process for connecting an absolute SSI encoder with a serial link, a 10…30VDC supply and outputs with standard RS 422 line transmitters.
Supply return supply + supply -
Encoder
296
Recommendations
Connecting an incremental and absolute SSI encoder l l l l
Connect each DATA SSI+/SATA SSI- encoder signal using a twisted pair,
Connect each supply point using a twisted pair, in order to reduce the on-line voltage falls
Connect both terminals of the cable shielding to the protective ground.
If the encoder does not have a positive supply feedback output, connect the module’s EPSR input to the positive supply of the encoder.
CAUTION
Recommendations on the pinout configuration of the encoder inputs/outputs
Before connecting the encoder to the module, check the pinout configuration given by the encoder’s manufacturer.
Failure to follow this precaution can result in injury or equipment damage.
297
Connecting an incremental and absolute SSI encoder
Connecting an encoder supply monitor to the TSX CCY 1128
Principle
Diagram of the encoder return supply monitor
The EPSR input signal from the encoder is comparable to: l either a fixed internally generated voltage of 3.3V if the Vref input is not connected.
l or a voltage equal to 66% of the voltage recorded at the Vref input, positive polarity of the encoder supply voltage.
The diagram below is of the encoder supply feedback monitor. encoder supply +
Encoder power supply return (EPSR)
- encoder 0V
Using the VRef input
The table below summarizes the use of the Vref input according to the encoder supply voltage.
If
The encoder is using a 5V supply
Then
The Vref input is not connected to the positive encoder supply.
The EPSR signal is comparable to the internal voltage of 3.3V. OK if > 3.3V
The encoder is using a 10…30V supply The Vref input is connected to the positive encoder supply.
The ESPR signal is comparable to 66% of the encoder supply voltage. OK if >66%
298
Diagram showing the connection process for an encoder on a
10…30V supply
Connecting an incremental and absolute SSI encoder
The diagram below shows the connection process for the encoder supply feedback monitor if the encoder is using a 10…30 V supply. encoder supply +
Encoder
- encoder 0V
Diagram showing the connection process for an encoder on a 5V supply
The diagram below gives the process for connecting the encoder supply feedback monitor if the encoder is using a 5V supply. encoder supply +
Encoder
- Encoder 0V
Diagram of the connection process if the encoder has no supply feedback
In this case, the EPSR input is connected to the positive supply at the encoder.
3,3 V encoder supply +
VRef
EPSR
(1) encoder supply +
Encoder
- Encoder OV
TSX CCY 1128 - 0 V
299
Connecting an incremental and absolute SSI encoder
Connecting the encoder supply to the TSX CCY 1128
Introduction The encoder supply can be connected: l either by using a TELEFAST ABE-7H16R20 cable interface, which is then connected to the module using a TSX CDP ••3 cable.
l or directly, using a TSX CDP •01 pre-wired strand
Process diagram for connecting the encoder supply to the
TELEFAST interface
The diagram below shows the process for connecting the encoder supply.
l l
At 24 VDC for an encoder with a 10…30 VDC supply format, and at 5 VDC for an encoder with a 5 VDC supply.
TSX CCY 1128
+ + - -
TSX CDP
••3 cable
1
3
2
4
5 V
0 V
10...30 V
VRef
TSX CDP
••3 cable
Supply
24 VDC
101 102 103
- 0 V
FU
+ 24 V
VRef
(1)
Supply
5 VDC
- 0 V
101 100
FU
+ 5 V
(1) to control encoder supply at 66% of voltage provided.
Connection only to be made if supply voltage 10…30 VDC
300
Connecting an incremental and absolute SSI encoder
Catalog of
TSX CDP ••3 connector cables
The table below gives the different references for the cables connecting the
TELEFAST to the module, and their respective lengths.
Cable references
TSX CDP 053
TSX CDP 103
TSX CDP 203
TSX CDP 303
TSX CDP 503
Cable lengths
0.5 meters
1 meter
2 meters
3 meters
5 meters
Diagram showing the process for connecting the supply using a
TSX CDP •01 pre-wired strand l l
The diagram below shows the process for connecting the encoder supply.
At 24 VDC for an encoder with a 10…30 VDC supply format, and at 5 VDC for an encoder with a 5 VDC supply.
TSX CCY 1128
HE 10
5
7
1
3
9
2
4
6
VRef
(1)
8
10
White
Brown
Green
Yellow
Fu
+ 5 VDC
Fu
+ 24 VDC
0 VDC
11 12
13 14
Cable
TSX CDP •01
TSX CDP •01 cable
15 16
17
19
18
20
TSX CDP •01 cable
(1) to control encoder supply at 66% of voltage provided.
Connection only to be made if supply voltage 10…30 VDC
Catalog of
TSX CDP •01 connector cables
The table below gives the different references for the cables connecting the
TELEFAST to the module, and their respective lengths.
Cable references
TSX CDP 301
TSX CDP 501
Cable lengths
3 meters
5 meters
301
Connecting an incremental and absolute SSI encoder
Recommendations l l l
Maximum length of wires between the supply outputs and the connection points on the TELEFAST: must be less than 0.5 meters.
Protection on the + supply: although the module has several built-in protection systems to guard against wiring errors and accidental short-circuits on the cables, it is vital to install a 1A maximum non-delay fuse (Fu) on the + supply.
Connection of the 0 V supply to the protective ground: must be as close as possible to the supply output.
302
Connecting an incremental and absolute SSI encoder
TSX CAP S15 connection accessory
At a Glance The TSX CAP S15 accessory comprises 2 15-pin SUB D connectors, and ensures the link between the module’s connection interface and the encoder’s connection string.
The table below introduces the TSX CAP S15 connection accessory.
Diagram References Use
TSX CAP S15 Can be used in the module/encoder connection string
Composition
Kit comprises 2 15-pin
SUB D connectors with covers.
Integrating the
TSX CAP S15 into the connection string
The diagram below shows how to integrate a 15-pin SUB D connector from the
TSX CAP S15 kit into the encoder connection string.
12-pins DIN connector
Cable
Cable female male
12-pins DIN connector
Cable
Codeur incrémental ou absolu SSI
Encoder outputs: via shielded cable without connector
12-pins DIN connector
Encoder outputs:
12-pin DIN connector integrated in the encoder
303
Connecting an incremental and absolute SSI encoder
TSX TAP S1505/S1524 and TSX CCP S15• connection accessories
Introduction to the various accessories
The table below introduces the various accessories, their uses and functions.
Diagram
12-pin
DIN
12-pin
DIN
15-pin
SUB D
15-pin
SUB D
References Use Function
TSX TAP S1505 Can be used in a module/encoder connection string to connect a 5VDC incremental encoder with RS422 outputs, using A+/A-, B+/B- and Z+/Z- signals.
Mechanical interface equipped with two connectors, which allow a
15-pin SUB D connection and a 12-pin DIN connection to be used.
15-pin
SUB D
TSX TAP S1524 Can be used in a module/encoder connection string to connect a 24VDC encoder with Totem
Pole outputs, using
A, B, and Z signals.
Mechanical interface equipped with two connectors, which allow a
15-pin SUB D connection and a 12-pin DIN connection to be used.
15-pin
SUB D
TSX CCP S15• Can be used in a module/encoder connection string to connect the module to a TSX TAP S1505 or TSX TAP S1524
Connector cables comprising one cable with
24 gage wires, and equipped with a 15-pin
SUB D connector at each terminal.
304
Integrating the
TSX TAP S1505/
S1524 and
TSX CCP S15• into the connection string
Connecting an incremental and absolute SSI encoder
The diagram below shows how to integrate the TSX CCP S15, TSX TAP S1505 and
TSX TAP S1524 accessories into the connection string of an encoder:
12-pin DIN connectors female male
Incremental encoder
Cable
Encoder outputs via shielded cable
Cable
Encoder outputs via 12-pin DIN connector integrated in the encoder
Installing the
TSX TAP S1505/
S1524 accessories
The diagrams below show the two methods for installing these accessories.
Installing on a Telequick AM1-PA• board
Installing on the cabinet lead-in
Max. thickness =5mm
Seal
Cut-out
∅
7mm
305
Connecting an incremental and absolute SSI encoder
Dimensions of the TSX TAP
S1505/S1524 accessories
The diagram below provides the dimensions of the sides and the mounting distance on the Telequick AM1-PA• board of the TSX TAP S1505 and TSX TAP 1524 accessories.
55
31 38
47
Anti-clockwise direction for the
12-pin DIN connectors in the connection string
In order to facilitate connections, the pin numbers of the various 12-pin DIN connectors in the connection string must correspond to each other. In order to allow this, the pinout configuration of the connectors must be: l in an anti-clockwise direction for connectors belonging to the cable that relies on encoder accessory TSX TAP S1505/S1524, l in an anti-clockwise direction for connectors belonging to the encoder and the
TSX TAP S1505/S1524 accessory.
TSX TAP S1505/S1524 Cable to be made by the user or supplied by the encoder manufacturer
Encoder with counterclockwise connector female 12-pin DIN
2
3
1 9
10
11
12
4 5
8
6
7 male 12-pin DIN
7
6
8 9
12
11
10
5 4
1
3
2
Clockwise
Counterclockwise female 12-pin DIN
8 9
7
6
12
11
10
5 4
1
3
2 male 12-pin DIN
2
3
1 9
10
11
12
8
6
7
4 5
306
Connecting an incremental and absolute SSI encoder
Pinout configuration for the TSX TAP
S1505 accessory connectors
The diagram below shows the pinout configuration of the TSX TAP S1505 accessory at the 15-pin SUB-D connector terminal, and the 12-pin DIN connector terminal. male 15-pin
SUB D
TSX CCP S15•
9
10
1
2
1
2
10
A+ 5 V
A- 5 V
B+ 5 V
5
6
8 female 12-pin DIN
Special cable to be made or supplied by the encoder manufacturer
3
B- 5 V
11 11 1
12
13
4
5
4
5
Z+ 5 V
Z- 5 V
3
4
2
3
1 9
10
11
12
4 5
8
6
7
6
TSX CCY 1128
14
15
7
8
13
15
EPSR
+5 V
2
12
RS 422 output incremental encoder
(signals (A+/A-,
B+/B-, Z+/Z-)
0 V
8 10
TSX TAP S1505
307
Connecting an incremental and absolute SSI encoder
Pinout configuration for the TSX TAP
S1524 accessory connectors
The diagram below shows the pinout configuration of the TSX TAP S1524 accessory at the 15-pin SUB D connector terminal, and the 12-pin DIN connector terminal. male 15-pin
SUB D
TSX CCP S15•
9
10
11
12
13
1
2
3
4
5
3
9
12
7
13
2
B+ 24 V
8
A+ 24 V
5
Z+ 24 V
Encoder power supply return
24 V
3
12 female 12-pin DIN
Special cable to be made or supplied by the encoder manufacturer
2
3
1 9 8
10
11
12
6
7
4 5
6
TSX CCY 1128
14
15
7
8
5
8
0 V
Totem Pole output incremental encoder
(signals (A, B,
Z)
11 10
TSX TAP S1524
308
Connecting the auxiliary inputs and track outputs of the
TSX CCY 1128
15
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter describes the connection procedure for the auxiliary inputs and track outputs of the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
Introduction to the connection interfaces of the TSX CCY 1128
Connecting the auxiliary inputs of the TSX CCY 1128
Connecting the track outputs of the TSX CCY 1128
Page
309
Connecting the auxiliary inputs and track outputs
Introduction to the connection interfaces of the TSX CCY 1128
Connection interfaces
Illustration
The three HE10 connectors located on the front panel of the module are for connecting: l l l l the sensors and pre-actuators inline with the module inputs/outputs, the sensor and pre-actuators supplies inline with the module inputs/outputs.
The module is connected to the sensors and pre-actuators using: either TELEFAST connectors and TSX CDP ••3 cables (recommended), or TSX CDP •01 strips.
The diagram below shows the input/output connection strip of a TSX CCY 1128 module.
Preactuator power supply
Connection of the track output preactuators
Preactuator power supply or or
Connection of the track output preactuators or
Sensor power supply
Connection of the auxiliary input sensors
310
Elements and their functions
Connecting the auxiliary inputs and track outputs
The table below gives the different elements of the connection strip.
Number Elements
0
1
2
3
4
5
Functions
20-pin HE10 type connector Allows connection of: l l the pre-actuators controlled by the group 0 and
1 track outputs the pre-actuator supply
20-pin HE10 type connector Allows connection of: l the pre-actuators controlled by the group 2 and
3 track outputs l the pre-actuator supply
20-pin HE10 type connector Allows connection of: l l l the sensors that control the auxiliary inputs, the sensor supply, the incremental or absolute SSI encoder supply
TSX CDP••3 cables, equipped with a HE10 connector at each terminal
TSX CDP•01 strips, equipped with a HE10 connector at one terminal, and free wires at the other, identified using a color code
Allow the module to be connected to the
TELEFAST connector. 5 lengths are suggested: l l l l l
TSX CDP 053: 0.5 meters in length
TSX CDP 103: 1 meter in length
TSX CDP 203: 2 meters in length
TSX CDP 303: 3 meters in length
TSX CDP 503: 5 meters in length
Allow direct connection between the module inputs/ outputs and the sensors and pre-actuators. 2 lengths are suggested: l l
TSX CDP 301: 3 meters in length
TSX CDP 501: 5 meters in length
TELEFAST ABE-7H16R20 connectors
Connects a HE10 connection and a screw terminal block connection, allowing a rapid connection of supplies, sensors and pre-actuators
311
Connecting the auxiliary inputs and track outputs
Connection accessories
The sensors are connected to the auxiliary inputs, and the pre-actuators to the track outputs by: l either using a TELEFAST ABE-7H16R20 connector and TSX CDP ••3 cable
(recommended system), l or directly, using TSX CDP •01 strips
The diagram below shows these two types of connection
TSX CDP ••3 cable
TSX CDP •01 flat cable
Connection to terminal block or directly to sensors/ preactuators
Sensor/preactuator connection
312
Connecting the auxiliary inputs and track outputs
Connecting the auxiliary inputs of the TSX CCY 1128
Number of auxiliary inputs
The TSX CCY 1128 module has 3 auxiliary inputs:
Auxiliary Functions
IREC Adjustment of the position measurement
ICAPT0
ICAPT1
Position capture in register 0
Position capture in register 1
Diagram The auxiliary inputs use a 24 VDC from an external supply provided via the connector.
The diagram below shows this supply.
Voltage monitoring
Sensor power supply
24 VDC
313
Connecting the auxiliary inputs and track outputs
Positioning the
HE10 connector, and identifying the signals
The diagram below represents the position of the HE10 connector on the module in relation to the auxiliary inputs and the identification of the different signals delivered by the connector.
This connector delivers exactly the same supply as the incremental or absolute SSI encoder. This information will be elaborated in Chapter 3.
TSX CCY 1128
5 V 1
10...30 V 3
2 0 V
4 VRef
IREC 5
ICAPT0 7 nc 9
6
8 nc
ICAPT1
10 nc nc 11 12 nc nc 13 14 nc nc 15 16 nc
24 V 17 18 0 V
24 V 19 20 0 V
314
Connecting the auxiliary inputs and track outputs
Pinout configuration of the module’s
HE10 connector
The pinout configuration of the HE10 connector in relation to the auxiliary inputs is as follows:
Diagram
(front view)
Pin No.
Signal Designation
1
3
5
7
9
2
4
6
8
10
11 12
13 14
15 16
17 18
19 20
17
18
19
20
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
5 V
0 V
10..30V
VRef
-
-
-
-
-
-
IREC
-
ICAPT0
ICAPT1
24 V
0 V
24 V
0 V
Encoder supply input +5 VDC
Encoder supply input – 0VDC
Encoder supply input + 10…30VDC
Reference input voltage for encoder supply monitoring
Auxiliary adjustment input
Not wired
Auxiliary capture input 0
Auxiliary capture input 1
Not wired
Not wired
Not wired
Not wired
Not wired
Not wired
Not wired
Not wired
Sensor supply input + 24VDC
Sensor supply input - 0VDC
Sensor supply input + 24VDC
Sensor supply input - 0VDC
315
Connecting the auxiliary inputs and track outputs
Process diagram The diagram below represents the process for connecting the auxiliary inputs
Encoder power supply to module and encoder
15-pin SUB D connector
Sensor power supply
316
Connecting the auxiliary inputs and track outputs
Connection using TELEFAST connector and
TSX CDP
••3cable
Availability of signals at the screw terminal block of the TELEFAST connector
(1) At the TELEFAST ABE-7H16R20 connector, the position of the jumper wire determines the polarity of all terminals from 200 to 215: l l jumper wire in position 1 or 2: terminals 200 to 215 have positive polarity, jumper wire in position 2 or 4: terminals 200 to 215 have negative polarity.
(2) At the TELEFAST ABE-7H16R20 connector, it is possible to add an optional
ABE-7BV20 bar to create a second shared sensor (positive or negative according to user’s choice).
317
Connecting the auxiliary inputs and track outputs
Connection using TELEFAST connector and
TSX CDP
••3cable
Example for connecting sensors to the auxiliary inputs
Connection of 24 VDC power supply for auxiliary input sensors
Connection of sensors to auxiliary inputs
Mechanical contact
2-wire PNP proximity sensor
3-wire PNP proximity sensor
318
Connecting the auxiliary inputs and track outputs
Correspondence between the TELEFAST terminal block and the module’s HE10 connector
TELEFAST screw terminal block (No. of terminal)
HE10 connector
20 points (pin number)
100
101
1
2
102
103
3
4
Type of signal Functions
+ 5VDC
- 0 VDC
+10...30VDC
VRef
Encoder supply
104
105
106
107
108 to 115
+ 24VDC
- 0 VDC
+ 24VDC
2
3
- 0 VDC
1
4
200...215
300...315
5
6
7
8
9 to 16
17
18
19
-
-
-
-
20
-
-
IREC
Not connected
ICAPT0
ICAPT1
Not connected
-
-
-
-
-
-
-
-
-
-
Reference input voltage for encoder supply feedback monitoring
Adjustment input
-
Capture input register 0
Capture input register 1
-
Auxiliary input sensor supply
Terminals 200 to 215 at + 24VDC if terminals 1 and 2 are connected
Terminals 200 to 215 at - 24VDC if terminals 3 and 4 are connected
Connecting shared sensors to: l +24VDC if terminals 1 and 2 are connected l - 0VDC if terminals 3 and 4 are connected
At the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected, using a wire, to the desired shared voltage.
319
Connecting the auxiliary inputs and track outputs
Connection using TSX
CDP •01 strips
This type of connection is used to connect all signals travelling to or from the module directly: l l at a terminal block, or at the sensors.
white brown green yellow grey pink blue red black grey-pink purple red-blue white-green brown-green white-yellow yellow-brown white-grey grey-brown white-pink pink-brown
Incremental encoder or
SSI absolute encoder power supply
Voltage reference input
Auxiliary inputs
Sensor power supply nc – not connected
320
Connecting the auxiliary inputs and track outputs
Connecting the track outputs of the TSX CCY 1128
Number of track outputs and their distribution
The TSX CCY 1128 module has 32 track outputs of which 24 are physically accessible.
These track outputs are divided into 4 groups on two HE10 connectors at the front panel of the module
Connectors
Groups
Tracks
Outputs
0
0 1
01234567 0123
Q0.
01234567
Q1.
0123
1
2
01234567
Q2.
01234567
3
0123
Q3.
0123
Diagram The diagram below shows a track output.
Preactuator power supply monitoring
Command
Short-circuit fault monitoring
Output
Preactuator
321
Connecting the auxiliary inputs and track outputs
Positioning the
HE10 connector, and identifying the signals
The diagram below represents the position of the HE10 connectors on the module in relation to the track outputs and the identification of the different signals delivered by the connectors.
Track outputs group 0
Track outputs group 1
Output power supply
Q0.0
1 2 Q0.1
4 Q0.3
Q0.2
3
Q0.4
5 6 Q0.5
Q0.6
7 8 Q0.7
Q1.0
9 10 Q1.1
Q1.2
11 12 Q1.3
+ 24 V 13 14 + 24 V
+ 24 V 15 16 + 24 V
24 V 17 18 0 V
24 V 19 20 0 V
Connector 0
TSX CCY 1128
Track outputs group 2
Track outputs group 3
Output power supply
Q2.0
1
Q2.2
3
Q2.4
5
Q2.6
7
2 Q2.1
4 Q2.3
6 Q2.5
8 Q2.7
Q3.0
9 10 Q3.1
Q3.2
11 12 Q3.3
+ 24 V 13 14 + 24 V
+ 24 V 15 16 + 24 V
+ 24 V 17 18 0 V
+ 24 V 19 20 0 V
Connector 1
322
Connecting the auxiliary inputs and track outputs
Process diagram The diagrams below show the connection process.
Preactuators
0
1
2
3
4
5
6
7
0
1
2
3
1
0
2
3 4
5
7
9 10
11 12
13 14
6
8
15 16
17 18
19 20
Q0.0
1
2
3
4
5
6
7
Q1.0
1
2
3
- 0 V
Preactuator power supply
FU2
+ 24 VDC
Preactuators
0
1
2
3
4
5
6
7
0
1
2
3
Preactuator power supply
- 0 V
FU2
+ 24 VDC
Group 0 outputs
Group 1 outputs
11 12
13 14
15 16
17 18
19 20
7
9
3
5
1
1
2
4
6
8
10
Q2.0
1
2
3
4
5
6
7
Q3.0
1
2
3
Group 2 outputs
Group 3 outputs
323
Connecting the auxiliary inputs and track outputs
Connection using TELEFAST connector and
TSX CDP
••3cable
Availability of connector 0 signals at the TELEFAST screw terminal block
Availability of connector 1 signals at the TELEFAST screw terminal block
324 l l
(1) At the TELEFAST ABE-7H16R20 connector, the position of the jumper wire determines the polarity of all terminals from 200 to 215: jumper wire in position 1 or 2: terminals 200 to 215 have positive polarity, jumper wire in position 3 or 4: terminals 200 to 215 have negative polarity.
Connecting the auxiliary inputs and track outputs
Connection using TELEFAST connector and
TSX CDP
••3cable
Example for connecting pre-actuators to the track outputs of connector 0 (groups 0 and 1). Proceed in the same way for connector 1 (output groups 2 and 3).
TSX CCY 1128
+ + - -
24 VDC 0 VDC
+ + - -
Connection of the 24 VDC power supply for track output preactuators
TELEFAST
ABE-7H16R20
Q0.0
Connection of preactuators to track outputs
Group 0 Group 1
Q0.1
Q0.2
Q0.3
Q0.4
Q0.5
Q0.6
Q0.7
Q1.0
Q1.1
Q1.2
Q1.3
200 100 201 101 202 102 203 103 204 104 205 105 206 106 207 107 208 108 209 109 210 110 211 111
-
Connection of + 24VDC commons
1
+ 24 VDC
112 113 114 115
+ + +
325
Connecting the auxiliary inputs and track outputs
The table below gives the correspondence between the TELEFAST screw terminal block and the HE10 connectors of the module (connectors 0 and 1).
326
-
-
17-19
18-20
Connecting the auxiliary inputs and track outputs
No. of terminal on
TELEFAST screw terminal block
200...215
-
Pin no. of
HE10 connector
Type of signals at connectors
0 1
Functions at connectors
0 1 l l
+ 24 VDC if terminals 1 and 2 are connected, -
0VDC if terminals
3 and 4 are connected
+ 24 VDC if terminals 1 and 2 are connected, -
0VDC if terminals
3 and 4 are connected
Connecting shared sensors
327
Connecting the auxiliary inputs and track outputs
Connection using TSX
CDP •01 strips
HE 10
1
3
5
7
9
8
10
2
4
6
11 12
13 14
15 16
17 18
19 20
This type of connection is used to connect all signals travelling to or from the module directly: l at a terminal block, or l at the pre-actuators.
The diagram below gives the correspondence between wire color and HE10 connector pin number for connectors 0 and 1
TSX CDP •01
Connector 0 Connector 1 white brown green yellow grey pink blue red black purple grey-pink red-blue white-green brown-green white-yellow yellow-brown white-grey grey-brown white-pink pink-brown
Q1.1
Q1.2
Q1.3
+24 VDC
+24 VDC
+24 VDC
+24 VDC
+24 VDC
Q0.0
Q0.1
Q0.2
Q0.3
Q0.4
Q0.5
Q0.6
Q0.7
Q1.0
0 VDC
+24 VDC
0 VDC
Group 0 track outputs
Q2.0
Q2.1
Q2.2
Q2.3
Q2.4
Q2.5
Q2.6
Q2.7
Q3.0
Group 1 track outputs
Q3.1
Q3.2
Q3.3
+24 VDC supply
+24 VDC
Preactuator +24 VDC power +24 VDC
+24 VDC
0 VDC
+24 VDC
0 VDC
Group 2 track outputs
Group 3 track outputs
Preactuator power supply
328
TSX CCY 1128 module displays
16
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter introduces the various LEDs of the TSX CCY 1128 electronic cam module and their meanings.
This chapter contains the following topics:
Topic
Introduction to the display block of the TSX CCY 1128 module
The various states of the LEDs on the TSX CCY 1128 and their meaning
Page
329
Module displays
Introduction to the display block of the TSX CCY 1128 module
Role
Physical presentation
The module’s display block has four LEDs, which provide information on: l the operating mode of the module, normal operating mode or module switched off or experiencing a fault l internal or external module operating faults.
The diagram below is a representation of the physical appearance of the module’s display block and the location of its four LEDs
330
Module displays
The various states of the LEDs on the TSX CCY 1128 and their meaning
Signaling operating mode
The table below gives the various states of the RUN lamp and their meanings
LED
RUN
Color
Green
State
Lit
Off
Meaning
Module operating normally
Module switched off or experiencing a fault
Signaling faults The table below gives the various states of the ERR, I/O and CH0 LEDs and their meanings.
LED
ERR
I/O
CH0
Color
Red
Red
Green
State Meaning
Lit Internal module error: l module has broken down
Flashing l Error in communication with processor l Application missing, invalid or experiencing a fault during execution
Off Operating normally, no faults
Lit External module fault: l l l
Cabling fault
Encoder supply fault
Configuration/adjustment parameters declined
Flashing Insignificant
Off
Lit
Operating normally, no faults
Operating normally, channel is active
Flashing The channel is not functioning correctly due to: l l an external fault a communication error
Off Channel inoperative: l l
Channel not configured
Channel incorrectly configured
331
Module displays
332
TSX CCY 1128 module electrical characteristics
17
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter describes the various electrical characteristics of the TSX CCY 1128 cam module.
This chapter contains the following topics:
Topic
General electrical characteristics of the TSX CCY 1128
Characteristics of the auxiliary inputs of the TSX CCY 1128
Characteristics of the encoder supply feedback monitor for the TSX CCY 1128
Page
Characteristics of the auxiliary inputs of the TSX CCY 1128
Characteristics of the track outputs of the TSX CCY 1128
333
Module electrical characteristics
General electrical characteristics of the TSX CCY 1128
Table of the general characteristics of the module
The following table gives the general characteristics of the module.
Parameter designation
Current used by the module
Values
Typical internal 5 V
(with internal ventilator in the operating module)
0.66 A
Maximum
1 A
Power dissipated in the module
Sensor/pre-actuator supply monitoring
Insulation resistance
Dielectric rigidity with the ground connection or the 0 V PLC logic
24V sensors/preactuators (auxiliary inputs and track outputs)
15 mA
10…30 V
(using an absolute SSI encoder, and 24V supply only)
11 mA
18 mA
20 mA
7 W (1)
Yes
10 W (2)
> 10 MOhms at 500 VDC
1000 V eff. - 50/60Hz per min
Operating temperature
Storage temperature
Hygrometry without condensation
Operating altitude
0 to 60°C
-25°C to 70°C
5% to 95%
0 to 2000m
(1) Under normal operating conditions: only one active auxiliary input, 24 VDC supply voltage, RS 422 standard signal.
(2) Under extreme operating conditions: all auxiliary inputs active, 30 VDC supply voltage, etc
334
Module electrical characteristics
Characteristics of the auxiliary inputs of the TSX CCY 1128
Characteristics of the encoder inputs
The table below gives the characteristics of the A, B and Z encoder inputs.
Input
Logic
Nominal values
Voltage
Current
Thresholds Voltage
In state 1 Voltage
Current
In state 0 Voltage
Current
Input impedance at nominal voltage
Type of input
Maximum permitted frequency
Incremental encoders
RS 422 use
Differential inputs
-
10 mA
< 5.5 V
> 3 V (1)
> 5.8 mA (1)
< - 3 V
< - 5.8 mA
-
Resistant
500 kHz multiplied by 1
250 kHz multiplied by 4
Use at 10… 30 VDC
Positive or negative
24 V
15.5 mA
< 30 V (possible up to
34V, limited to 1hr in
24)
> 11 V
> 5 mA
< 5 V
< 2 mA
1.5 kOhms
Resistant l l
(1) The positive or negative differential voltage must be higher then 3 volts, and the current in the positive or negative loop must be higher than 5.8 volts to guarantee: the inclusion of count pulses up to 500 kHz, that the line control does not detect errors, irrespective of the frequency.
Note: Comparison of the RS 422 standard encoder outputs
An encoder with RS 422 standard outputs can control the inputs of two
TSX CCY 1128 modules in parallel. In order to guarantee the necessary voltage levels, the encoder supply voltage must be higher than 4.5 V.
335
Module electrical characteristics
Characteristics of the encoder supply feedback monitor for the TSX CCY 1128
Characteristics of the EPSR input
The table below gives the characteristics of the encoder supply feedback monitor.
Parameters
Thresholds for the
EPSR input
Voltage
Current
Voltage for OK state Vref input free
VRef connected to + encoder supply
Values
30 V (possible up to 34V, limited to 1h. par 24h)
< 1.5 mA
OK if U> 3.3V
OK if U > 66% of the voltage recorded at the VRef input
336
Module electrical characteristics
Characteristics of the auxiliary inputs of the TSX CCY 1128
Table of the auxiliary inputs characteristics
The following table gives the characteristics of the IREC, ICAPT1 and ICAPT2 auxiliary inputs.
Parameter designation
Nominal values
Thresholds
Response time
Sensor voltage check threshold
Voltage
Current
Sensor supply, ripple included
In state 1 Voltage Uon
Current at Uon Ion
In state 0 Voltage
Current
Uoff
Ioff
Symbols Values Units
Un 24 V
In
U1
Utime (1)
8
19...30
34 mA
V
> 11
> 3
< 5
< 1,5
V mA
V mA
State 0 to 1
State 1 to 0
OK
Fault
Ton
Toff
Uok
Udef
Re
< 100
< 100
> 18
< 14
3
V
V ms ms kOhms
Resistive
Positive (sink)
Type 1
Input impedance
Type of input
Logic type
IEC 1131 compatibility with sensors
3-wire/2-wire proximity sensor compatibility
Dielectric rigidity with the ground connection l l
3-wire proximity sensor: all 3-wire proximity sensors operating at 24 VDC
2-wire proximity sensor: all 2-wire proximity sensors operating at 24 VDC have the following characteristics:
Breakdown voltage when closed: < 7V
Minimum switched current: < 2.5 mA
Residual current when open: < 1.5 mA
1500 V eff 50/60 Hz per mn
(1) Utime: maximum permitted voltage for 1 hour in every 24.
337
Module electrical characteristics
Characteristics of the track outputs of the TSX CCY 1128
Table of characteristics of the track outputs
The following table gives the characteristics of the track outputs.
Parameter designation
Nominal values
Thresholds
Dielectric rigidity with the ground connection
Compliance with IEC 1131-2
Voltage
Current
Voltage
Maximum current per output for U= 30 V or 34 V
I1
Maximum current per connector I2 per module
Maximum power for lamp with tungsten filament
Maximum switching frequency on inductive load
Electro unload time
Pre-actuator voltage check threshold
Compatibility with direct current inputs
OK
Fault
Protection against overloads and short-circuits
Protection against overvoltage of the outputs
Utime (1)
I3
P1
F
T
Uok
34
600
< 6
< 12
10
<0.6/LI
V mA
A
A
W
Hz
< L/R
> 18 s
V
Udef < 14 V
All direct current inputs with positive logic, and an input resistance of < at 15 kOhms
Using current limiter and thermal circuit breaker (0.7A<Id<2A)
Using a Zener (breakdown) diode between the outputs and the +24V
Protection against polarity inversions
Symbols Values
Un 24
In
U1
500
19...30
Units
V mA
V
Using a reverse diode on the supply
1500 V eff 50/60 Hz per mn
Yes
338
Connecting an absolute encoder with parallel outputs to
TSX CCY 1128
18
At a Glance
Subject of this chapter
What's in this
Chapter?
This Chapter describes the procedure for connecting an absolute encoder with parallel outputs to the TSX CCY 1128 electronic cam module.
This chapter contains the following topics:
Topic
Principle for connecting an absolute encoder to a TSX CCY 1128
TELEFAST ABE-7CPA11 base
Pinout configuration of the 15-pin SUB-D connectors of the module and the
TELEFAST
Connecting an absolute encoder with parallel outputs
Wiring rules and precautions specific to the TELEFAST
Configuration of the TELEFAST connector
Page
339
Connecting an encoder with parallel outputs
Principle for connecting an absolute encoder to a TSX CCY 1128
Connection string
Illustration
The 15-pin SUB D connector, located on the front panel of the module, allows the connection of encoder and module using a TELEFAST ABE-7CPA11 connector. l The TELEFAST connector receives: l all parallel signals from the encoder, l l the 5VDC or 10…30VDC encoder supply source.
The TELEFAST connector restores l signals for the module that have been encoded as RS 422 standard signals.
The diagram below shows the principle for connecting an absolute encoder with parallel outputs to a TSX CCY 1128 module.
Module/ABE-7CPA11 connection cable:
TSX CCP S15•, length 0.5m, 1m, 1.5m
Encoder power supply
5 VDC or 10...30 VDC
Module/ABE-7CPA11 connection cable made using the TSX CAP S15 kit
Parallel output absolute encoder
340
Connecting an encoder with parallel outputs
TELEFAST ABE-7CPA11 base
Role
Appearance of the TELEFAST base
The TELEFAST ABE-7CPA11 base ensures: l l the connection interface between: l l the absolute encoder with parallel outputs, and the TSX CCY 1128 module the conversion of the value position provided by the encoder with parallel outputs as RS 422 standard serial information. The absolute encoder must have pure or gray binary coding, with a maximum of 24 bits of data.
The diagram below represents the TELEFAST ABE-7CPA11 base and its various elements.
Elements and their functions
The table below gives the functions of the various elements of the TELEFAST.
2
3
4
Number Elements
1 15 pin SUB-D connector.
5
6
7
Screw terminal block.
15 pin SUB-D connector.
LED
Fuse
Screw terminal block
Microswitches
Functions
Allows connection to the TSX CCY 1128 module, via a TSX CCP S15• cable.
Allows connection of the encoder supply.
Not used.
When lit, shows that the TELEFAST is switched on.
Ensures protection of the supply: l l calibre: 1A, type: non-delay fusion.
Allows connection to the encoder.
Allow configuration of the type of encoder relevant to the TELEFAST (gray or binary).
341
Connecting an encoder with parallel outputs
Characteristics of the TELEFAST base
General characteristics
The table below gives the general characteristics of the TELEFAST ABE-7CPA11 base.
Parameters
Permitted voltage at 10…30 VDC
Permitted voltage at 5 VDC
Maximum frequency for changing the state of the lightweight bit
Read frequency of the serial frame
Current used (excluding encoder)
Dissipated power
Limit of encoder supply feedback monitor
Insulation resistance
Dielectric rigidity
Operating temperature
Storage temperature
Hygrometry
Operating altitude
Values
11...30 VDC
5...6 VDC
75 kHz
150 kHz...1 MHz
Typical: 90mA - Maximum: 130 mA
Typical: 450mW - Maximum: 1,5 W
- 15% < V supply < + 15%
> 10MW at 500 VDC
1000 V eff -50/60 Hz per mn
0…60°C
-25°C…+70°C
5%…95% without condensation
0…2000 meters
Characteristics of the encoder reading inputs In0 to In23
The table below gives the different parameters of the TELEFAST inputs connected to the encoder channels.
Parameters
Logical input
Compatibility with encoder outputs
Maximum input voltage
Maximum length of encoder/TELEFAST cable
Type Values
Positive State 0: U < 2.5 V, state 1: U > 3.9V
Negative
Totem Pole outputs
State 0: U > 3.9V, state 1: U < 2.5 V
11...30 VDC
5 VDC
11...30 VDC
-
-
TTL 5 V outputs
Transistor outputs with NPN open collector
+30 VDC
200 m
This maximum distance depends on the type of encoder used, and limits the frequency of changing the lightweight bit. See TELEFAST base configuration
342
Connecting an encoder with parallel outputs
Parameters
Maximum length of encoder/TELEFAST cable
Low limit for input voltage -
Upper limit for input voltage -
Type Values
200 m.
This maximum distance limits the frequency of the serial transmission clock. See the specific precautions and rules for cabling
0 VDC < VIL < 2.5 VDC
3.9 VDC < VIH < 30 VDC
343
Connecting an encoder with parallel outputs
Pinout configuration of the 15-pin SUB-D connectors of the module and the
TELEFAST
Pinout configuration of the module’s
15-pin SUB-D connector
The pinout configuration for connecting an absolute encoder with parallel outputs using a TELEFAST ABE-7CPA11 is as follows.
Diagram
(front view)
Pin No.
Signal Designation
7
8
5
6
3
4
1
2
9
10
11
12
13
14
15
-
-
Data+
Data-
-
-
Encoder input, + data (5 VDC)
Encoder input, - data
-
CLK +
-
Encoder input, CLK + (5 VDC)
10…30 V Encoder supply input (+ 10…30 VDC)
0 V Encoder supply input (- 0 VDC)
-
-
-
-
EPSR
CLK -
5 V
-
-
-
-
+ encoder supply feedback input. Receives + supply feedback from the encoder, which allows the module to verify the encoder’s presence.
Encoder input, CLK -
Encoder supply input (+ 5 VDC)
344
Connecting an encoder with parallel outputs
Pinout configuration of the TELEFAST
15-pin SUB-D connector
The pinout configuration of the TELEFAST ABE-7CPA11 15-pin SUB-D connector is as follows.
Diagram
(front view)
Pin No.
Signal Designation
7
8
5
6
3
4
1
2
9
10
11
12
13
14
15
-
-
Data+
Data-
-
-
Encoder output, + data signal (5 VDC)
Encoder output, - data signal
-
CLK +
-
Encoder output, + CLK signal (5 VDC)
10…30 V Encoder supply output (+ 10…30 VDC)
0 V Encoder supply output (- 0 VDC)
-
-
-
-
EPSR
CLK -
5 V
-
-
-
-
+ encoder supply feedback input. Receives + supply feedback from the encoder, which allows the module to verify the encoder’s presence.
Encoder output, - CLK signal
Encoder supply output (+ 5 VDC)
345
Connecting an encoder with parallel outputs
Connecting an absolute encoder with parallel outputs
Introduction An absolute encoder with parallel outputs must always be connected to the module using a TELEFAST ABE-7CPA11 base. The signals sent to the module are RS 422 standard SSI serial signals. The encoder supply is 10…30 VDC or 5 VDC depending on the encoder type.
Diagram showing the principle of connecting an absolute encoder with parallel outputs on a 10…30 VDC supply
The diagram below represents the connection string of an absolute encoder with parallel outputs on a 10…30 VDC supply.
TSX CCY 1128
Cable
TSX CCP S15• + - +
+10...30 VDC
0 VDC
Encoder supply
TELEFAST ABE-7CPA11
TSX CAP S15 kit
+cable
GND
Local protective ground
Connection of cable shielding
Encoder
346
Connecting an encoder with parallel outputs
Diagram showing the principle of connecting an absolute encoder with parallel outputs on a 5 VDC supply
The diagram below represents the connection string of an absolute encoder with parallel outputs on a 5 VDC supply.
TSX CCY 1128
Cable
TSX CCP S15• + - +
+ 5 VDC
0 VDC
Encoder supply
TELEFAST ABE-7CPA11
TSX CAP S15 kit
+cable
GND
Local protective ground
Connection of cable shielding
Encoder
347
Connecting an encoder with parallel outputs
Functions of the
TELEFAST screw terminal block
The TELEFAST base has two terminal blocks:
One located on the upper part, comprising four terminals and used to connect the supply source to the encoder,
Functions
+
-
Terminals on the screw terminal blocks
Signals
-
-
+ inputs, source of encoder supply
- inputs, source of encoder supply
Two terminal blocks comprising 36 terminals are located on the lower part. These are used to connect all signals travelling to or from the encoder.
Functions Terminals on the screw terminal blocks
GND
Signals
-
+10..30 V
+5 V
0 V
1 to 24
25
29
30
-
-
-
In0 to In24
ERR
+ EPSR
- EPSR
Connection to TELEFAST protective ground.
Ensures the continuity of the ground connection between the encoder and the module
Connecting the + encoder supply for an encoder using a 10…30 VDC supply
Connecting the + encoder supply for an encoder using a 5 VDC supply
Connecting the - encoder supply
Parallel outputs of the encoder
Default output of the encoder
+ return supply of the encoder. If there is no return encoder supply, connect the terminal to the +10…30
V or +5 V terminal according to the encoder supply
- return supply of the encoder. - return supply of the encoder. If there is no return encoder supply, connect the terminal to the 0 V terminal
348
Connecting an encoder with parallel outputs
Wiring rules and precautions specific to the TELEFAST
Connecting or disconnecting the TELEFAST
You should always connect or disconnect the TELEFAST’s connectors and various connection wires when the voltage is SWITCHED OFF: l connecting or disconnecting the cable connectors linking the module and the
TELEFAST connector, l connecting or disconnecting the wires linking the TELEFAST connector to the encoder.
Length of the connection cable between the module and the
TELEFAST
The table below gives the clock frequency of the transmission series according to the distance.
If cable length < to 10 meters cable length < to 20 meters cable length < to 50 meters cable length < to 100 meters cable length < to 150 meters cable length < to 200 meters then frequency of the transmission series clock: 1 MHz frequency of the transmission series clock: 750 kHz frequency of the transmission series clock: 500 kHz frequency of the transmission series clock: 375 kHz frequency of the transmission series clock: 200 kHz frequency of the transmission series clock: 150 kHz
Cross-section of the wire connecting the module and the
TELEFAST
In order to reduce the on-line voltage falls as much as possible, please respect the following points:
If
The encoder is using a
5VDC supply
And Then
The distance from the module to the TELEFAST is
< 100m
Use a wire with minimum crosssection 0.08 mm (gage 28)
The distance from the module to the TELEFAST is
> 100m
Use a wire with minimum crosssection 0.34 mm (gage 22)
349
Connecting an encoder with parallel outputs
Connecting the encoder supply
In order to limit voltage falls with a 0V, caused by the encoder supply current, we recommend that you wire the 0V as follows:
24 VDC or
5 VDC
Power supply
Connection depending on the encoder power supply
Encoder 0 VDC
350
Connecting an encoder with parallel outputs
Wiring the encoder outputs on the
TELEFAST
If the encoder outputs have positive or negative logic with a number lower than 24, use the following connection procedure:
If the encoder outputs have positive logic
And their number is lower than 24
Then l l wire the encoder outputs to the TELEFAST inputs, working from the least significant to the most significant wire the unused TELEFAST inputs to the 0V terminal
Example: 14-bit encoder the encoder outputs have negative
Logic their number is lower than 24 l l wire the encoder outputs to the TELEFAST inputs, working from the least significant to the most significant do not wire (leave free) the unused TELEFAST inputs.
Example: 14-bit encoder
351
Connecting an encoder with parallel outputs
Protecting the encoder supply
According to the encoder supply voltage, the supply should be protected as follows:
If Then
The encoder supply voltage is 10…30VDC
The encoder supply voltage is 5VDC
The protective fuse is built into the TELEFAST: l l size: 1A type: fast-blow fusion.
Provide a series fuse (Fu) for the positive supply: l calibre: to be determined by the user, dependent upon the
TELEFAST and encoder consumption l type: fast-blow fusion
5 VDC encoder power supply
Monitoring the encoder supply
If the encoder supply voltage decreases by more than 15%, the default (EPSR signal) is sent back to the module. If the encoder does not have a return supply, do the following:
If
No return encoder supply
Then
Connect the positive and negative EPSR of the TELEFAST: l the positive EPSR terminal of the TELEFAST to the positive terminal of the encoder supply l the negative EPSR terminal of the TELEFAST to the negative terminal of the encoder supply
352
Connecting an encoder with parallel outputs
Configuration of the TELEFAST connector
At a Glance The connector is configured by setting the 4 micro-switches located under the
SUB D 15-pin connector to the right of this. For the TSX CCY 1128 module, the configuration is limited according to the type of connected encoder.
The diagram below shows the location and function of the 4 micro-switches.
Type of encoder connected to the TELEFAST sub-base
Not used with the TSX CCY 1128 module (always in OFF position)
Not used with the TSX CCY 1128 module (always in OFF position)
The two micro-switches located on the right must always be in the OFF position. The two micro-switches on the left allow the link performance to be set according to the encoder output characteristics, and dependent upon the distance between the
TELEFAST and the encoder.
Positions of the micro-switches: encoder with positive Logic outputs
Encoder with positive Logic outputs, coded GRAY
Type of encoder output
Logic Output interface
Code position of the microswitch
Maximum length encoder/
TELEFAST
50 meters Positive l Totem Pole l l
TTL
NPN open collector
Gray
Max. frequency for changing least significant bit
75 kHz
353
Connecting an encoder with parallel outputs
Positions of the micro-switches: encoder with negative Logic outputs
Encoder with negative Logic outputs, coded GRAY
Type of encoder output
Logic Output interface
Code
Totem Pole position of the microswitch
Maximum length encoder/
TELEFAST
50 meters
Max. frequency for changing least significant bit
75 kHz
Gray Negative
TTL 100 meters 40 kHz
NPN open collector
200 meters 5 kHz
Positions of the micro-switches: encoder with positive or negative Logic outputs,
Encoder with positive or negative logic outputs, Binary code
Type of encoder output
Logic Output interface
Totem Pole
Code
Positions of the microswitches
Maximum length encoder/
TELEFAST
10 meters
Max. frequency for changing least significant bit
40 kHz
Positive or negative
TTL
Binary
30 meters 20 kHz
NPN open collector
50 meters 5 kHz
354
SERCOS® TSX CSY 84 / 164
Modules
V
At a Glance
Subject of this
Part
What's in this
Part?
This part presents the SERCOS® TSX CSY 84 / 164 modules, their operating features and their installation.
This part contains the following chapters:
Chapter
19
20
21
22
23
24
Chapter Name
Presentation of the TSX CSY 84 / 164 modules
Installing the modules
Description of the multi-axis control system
Fiber optic cables
Characteristics, Standards and service conditions
Compatible variable speed controllers
Page
355
SERCOS® TSX CSY 84 / 164 Modules
356
Presentation of the
TSX CSY 84 / 164 modules
19
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This chapter presents the TSX CSY 84 and TSX CSY 164 multi-axis control modules.
This chapter contains the following topics:
Topic
Presentation of the modules in their environment
Physical presentation of the modules
Compatibility with the installed base
Page
357
Presentation of the TSX CSY 84 / 164 modules
Presentation of the modules in their environment
Introduction TSX CSY 84 / 164 modules are double format application-specific modules from the
Premium range. They fit on a TSX RKY•• rack of a TSX/PCX 57 PLC station. They are one of the components of the SERCOS® range on Premium PLCs, and are used to create a multi-axis control system.
Presentation of the components of the SERCOS® range on
Premium PLCs
The SERCOS® range on Premium PLCs is composed of the following elements: l l l l l l l l l l l a TSX/PCX 57 PLC station composed of: one or more racks, power supply modules, a CPU, the various modules necessary for the application.
one or more TSX CSY 84 / 164 multi-axis control modules, each of which can be used to drive up to 8 variable speed controllers spread out over a SERCOS® network.
a range of LEXIUM MHD• (See
List of variable speed controllers, p. 391) variable
speed controllers, motors associated with these variable speed controllers, plastic fiber optic cables ranging between 0.3 m to 16.5 m in length: l which provide the physical connection between the module/controller and the controller/controller in a ring network structure, l which act as a support for the digital link between the TSX CSY 84 / 164 modules (master) and the variable controllers (slaves), a digital link that is defined by the European standard EN61491.
a PL7 Junior/Pro software which is used to configure the TSX CSY 84 / 164 modules and program the movement application, a UniLink LXM 17 software application, used to set up the variable speed controllers.
358
Installation diagram
Presentation of the TSX CSY 84 / 164 modules
The figure below shows an example of the installation of a SERCOS® multi-axis control module with the TSX CSY 164 module.
PLC station:
TSX 57 station example
Programming and adjustment terminal
PL7 Junior/Pro software to:
• configure the module,
• program and adjust the application.
Unilink software to:
• set up and adjust the variable speed controllers.
Variable speed controllers
LEXIUM
MHDS
Motors
Fiber optic cables
SERCOS ® ring network
359
Presentation of the TSX CSY 84 / 164 modules
Physical presentation of the modules
Description of the front panel
Appearance of the module
The following can be found on the front panel of the modules: l l l l a display block comprising 6 LEDs for viewing and diagnosing the module status, a group of 24 LEDs for viewing and diagnosing the various module channels, two connectors for connecting the fiber optic cables which make up the link between the module and variable speed controllers, two 8-pin Mini DIN connectors.
The diagram below shows the TSX CSY 84 module and its various elements.
360
Elements and their functions
Presentation of the TSX CSY 84 / 164 modules
7
8
9
4
5
6
Number
1
2
3
Elements
Screw
Module casing
Display block comprising 6 LEDs:
• green RUN LED
• red ERR LED
• red I/O LED
• yellow SER LED
• yellow COM LED
• yellow INI LED
Recessed button
COM2 8-pin Mini DIN connector
24 LED indicators
COM1 8-pin Mini DIN connector
TX send SMA connector
RX receive SMA connector.
Functions
Attaches the module to the TSX RKY •• rack
Does the following:
• Supports and protects the electronic boards,
• Locks the module into its slot.
These enable the user to visualize the status and errors of the module.
Indicates the operating mode of the module.
Indicates an internal module error.
Indicates an external module error or an application error.
Indicates that traffic on the SERCOS® network is flowing correctly.
Not significant
Indicates that the module is in reinitialization phase.
Used to initialize the module.
Reserved.
Used to visualize and diagnose the module channels.
Reserved.
Used to connect the send fiber optic cable of the SERCOS® ring network.
Used to connect the receive fiber optic cable of the SERCOS® ring network.
361
Presentation of the TSX CSY 84 / 164 modules
Compatibility with the installed base
Hardware compatibility
Software compatibility
In order to receive the TSX CSY 84 modules, the PLC station must be equipped with a processor running software version SV > 3.3.
l l l
To develop an application using the TSX CSY 84 modules, the PL7 Junior/Pro software must be version SV 3.4 + C functional complement or version SV > 3.4.
For a TSX CSY 84 module, a program is compatible with a TSX CSY 164 module after reconfiguring the PL7 application.
To develop an application using the TSX CSY 164 modules, the PL7 Junior/Pro software must be version SV 4.3 + Motion TSX CSY 164 Add-on or version
SV ≥ 4.4.
362
Installing the modules
20
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This chapter describes the installation operations for the TSX CSY 84 / 164 multiaxis control modules.
This chapter contains the following topics:
Topic
Mounting the modules in a PLC station rack
Installing the modules in a PLC station
Number of application-specific channels managed by a TSX CSY 84 or
CSY 164 station
Installation precautions
Module displays
Initialization of the module after an internal error
Operating mode of the TSX CSY 84/164 modules
Page
363
Installing the modules
Mounting the modules in a PLC station rack
Introduction
Illustration
The TSX CSY 84 / 164 modules can be mounted into all the available slots of a
TSX RKY •• rack of a TSX 57/PMX 57/PCX 57 PLC station, with the exception of the slots dedicated to the supply and processor modules. This double format module takes up 2 slots on a TSX RKY •• rack.
The diagrams below show the procedure for mounting a standard format module from the Premium range into the TSX RKY •• rack. The procedure is identical for a double format module.
Procedure The table below describes the procedures.
Steps
1
2
3
Actions
Insert the pins at the back of the module into the centering holes located on the lower part of the rack.
Twist the module to bring it into contact with the rack.
Attach the module to the rack by tightening the screw located on the upper part of the module. Maximum tightening torque of the screw: 2.0 Nm
364
Installing the modules
Installing the modules in a PLC station
Introduction
Installing the module
The TSX CSY 84 / 164 modules can be installed in all the racks located on the main
X bus segment of a PLC station.
The diagram below represents the installation of a TSX CSY module in a rack belonging to the main X bus segment. The module can be installed in the rack supporting the processor and in all other racks present on the X bus. The distance between the rack supporting the TSX CSY module and the rack supporting the processor must not exceed 100 meters.
X bus ≤ 100 meters
Applicationspecific
TSX CSY 84 / 164 TSX CSY 84 / 164
Processor
Note: The TSX CSY 84 / 164 modules cannot be installed in a rack belonging to a remote X bus segment by a TSX REY 200 module.
365
Installing the modules
Number of application-specific channels managed by a TSX CSY 84 or
CSY 164 station
Definition of an applicationspecific channel
An application-specific module (TSX CTY• counting modules, TSX CAY• axis command modules, TSX CFY• step by step command modules, TSX YSP Y• weighing modules, TSX CCY 1128 electronic cam modules, TSX CSY 84 movement control modules, TSX CSY 164, etc.) is equipped with a number of channels, varying from 1 to n according to the module type (see ); these channels are called application-specific channels.
Reasons for counting the number of applicationspecific channels in a station
Number of applicationspecific channels for a
TSX CSY 84 module
Number of applicationspecific channels for a
TSX CSY 164 module l l
To determine: the power of the CPU to be installed the maximum number of application-specific modules that can be installed in the station.
A TSX CSY 84 module can comprise up to 32 application-specific channels.
Only configured application-specific modules should be taken into account.
The TSX CSY 84 module manages up to 8 real axes (channels 1 to 8), which are associated with variable speed controllers. In addition to these real axes, the module can manage: l l l l l
4 imaginary axes (channels 9 to 12),
4 external measurement axes (channels 13 to 16),
4 coordinated sets of axes (channels 17 to 20),
4 follower sets of axes (channels 21 to 24),
7 cam profiles (channels 25 to 31).
Channel 0 (SERCOS® channel) manages the digital bus, l Channels 1 to 16 support real axis functions, imaginary axis functions, and external setpoints, l l l
4 coordinated sets of axes (channels 17 to 20),
4 follower sets of axes (channels 21 to 24),
7 cam profiles (channels 25 to 31).
Channel 0 (SERCOS® channel) manages the digital bus,
366
Installing the modules
Installation precautions
Introduction
Installing and removing a module
In order to guarantee optimum operating conditions, it is necessary to take certain precautions when installing and removing a module, plugging and unplugging connectors to and from the front panel of the module, and adjusting its fixing screws.
Installing and removing a module should be down with the power off. However, a module can be installed or removed without cutting the rack’s power and without any risk of damaging the module.
Screwing in and unscrewing the fiber optic connectors on the front panel of the module
It is possible to screw in and unscrew the fiber optic connectors on the front panel of the module with the module powered up without any risk of damaging it.
In order to avoid malfunction of the application, these operations should preferably be carried out with the power supply off.
Tightening torque of the module's fixing screw
Tightening torque: 2.0 Nm.
367
Installing the modules
Module displays
Role The TSX CSY 84 or TSX CSY 164 module is equipped with two display units: l A display block in standard Premium composed of 6 LEDs, whose function is to inform the user of: l l the operating mode of the module: module operation normal, in error or switched off, l internal or external module operating errors.
A set of 24 LEDs for displaying the status of the application-specific channels of the module (real axes, imaginary axes, etc.).
Presentation of the display block
The diagram below shows the physical appearance of the module’s display block and the location of its six LEDs.
368
Installing the modules
Statuses of the various display block LEDs and their meaning
The following tables show the different statuses for each LED on the display block and their meaning.
LED
RUN
ERR
I/O
INI
SER
COM
Color
Green
Red
Red
Yellow
Yellow
Yellow
Status
On
Off
On
Blinking
Off
On
Blinking
Off
On
Blinking
Off
On
Blinking
Off
-
Meaning
Module in normal operating mode
Module in error, powered down, in initialization phase or application missing
Internal module error:
• module has broken down.
• Start-up of the module,
• Communication error,
• Application missing, invalid or execution error.
Operating normally, no faults
External module error:
• Cabling error
Not significant
Operating normally, no faults
Not significant
The module is in Reset phase
Operating normally
Not significant
Traffic on the SERCOS® network in normal operating mode
No traffic on the SERCOS® network
Unused
369
Installing the modules
Presentation of the display LEDs of the applicationspecific channels
The diagram below shows the physical characteristics of the 24 display LEDs for certain application-specific channels.
TSX CSY 84 TSX CSY164
LEDs 1 to 8: display of the 8 imaginary axes
LEDs 9 to 12: display of the 4 imaginary axes
LEDs 13 to 16: display of the 4 external measurement axes
LEDs 17 to 20: of axes
display of the 4 coordinated sets
LEDs 1 to 16: display of independent axes (real and imaginary axes, and external setpoint)
LEDs 17 to 20: display of the 4 coordinated sets of axes
LEDs 21 to 24: display of the 4 follower sets of axes
LEDs 21 to 24: display of the 4 follower sets of axes
370
Installing the modules
13
14
15
16
9
10
11
12
6
7
4
5
8
1
2
3
21
22
23
24
17
18
19
20
Statuses and meanings of the applicationspecific channel display LEDs
LEDs
The table below shows the different statuses of the application-specific channel display LEDs:
CSY 84 Assignment CSY 164
Assignment
Real axis 1
Real axis 2
Real axis 3
Real axis 4
Real axis 5
Real axis 6
Real axis 7
Real axis 8 either real axis, imaginary axis, external setpoint
Imaginary axis 1
Imaginary axis 2
Imaginary axis 3
Imaginary axis 4
External setpoint 1
External setpoint 2
External setpoint 3
External setpoint 4
Coordinated set of axes 1
Coordinated set of axes 2
Coordinated set of axes 3
Coordinated set of axes 4
Follower set of axes 1
Follower set of axes 2
Follower set of axes 3
Follower set of axes 4
Statuses Meanings
On
Blinking
Off
Axis in normal operating mode
Axis in configuration mode or in error
Axis not configured or configuration error
371
Installing the modules
Initialization of the module after an internal error
How to initialize the module
The module is initialized by using the recessed button on the front panel, as indicated in the following diagram.
Recessed button
Note: Recommendations for using the recessed button: l l
Apply pressure gently to the button,
The tip of the tool should be kept perpendicular to the front panel of the module and centered in the access window.
Failure to observe this may result in damage to the recessed button.
Consequence of initialization
The module starts up again in initialization phase, as when powering up. See
Diagram of the operating mode , p. 373.
372
Installing the modules
Operating mode of the TSX CSY 84/164 modules
Diagram of the operating mode
The following diagram describes the different stages of the operating mode and, for each stage, gives the status of the LEDs on the front panel.
RESET using the recessed button
Power up
Initialization
Self-tests
Self-tests for the PC card built into the module
(duration 20 to 30s)
Self-tests for the module
(duration 2 to 3s)
LEDs
ERR
INI
Other
LEDs
All
Status flashing flashing off
Status flashing
Serious error
LEDs
ERR
Others
Status on not significant
Start-up
Ready
Initialization of firmware
(duration 5 to 20s)
Module ready to receive a configuration
LEDs
ERR
INI
Other
LEDs
ERR
Other
Status flashing flashing off
Status flashing off
Configured
(1) flashing when working normally, otherwise off
(2) on: off: blinking: channel functioning channel not configured channel configuration in progress or in error
Module in communication with the processor
LEDs
RUN
INI
I/O
Status on off off
SER (1) flashing switched off
ERR off
1 to 24 (2) on flashing switched off
373
Installing the modules
374
Description of the multi-axis control system
21
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This chapter describes how the TSX CSY 84 and TSX CSY 164 modules interface with the variable speed controllers in a SERCOS® network configuration to form a multi-axis control.
This chapter contains the following topics:
Topic
SERCOS® multi-axis control system on Premium PLCs
SERCOS® ring network
Page
375
Description of the multi-axis control system
SERCOS® multi-axis control system on Premium PLCs
Architecture of a
SERCOS® multiaxis control system
The architecture of a SERCOS® multi-axis control system on Premium PLCs comprises: l l l l a TSX/PCX 57 PLC station, a TSX CSY 84 or TSX CSY 164 multi-axis control module, variable speed controllers that control the motors associated with the different axes, a SERCOS® fiber optic network.
Illustration The following diagram shows an example of the architecture of a SERCOS® multiaxis control system.
Programming terminal
PLC station: TSX 57 station example
Supply Processor Transmission
Reception
Variable speed controller
Fiber optic cable
Variable speed controller
SERCOS® ring network
Variable speed controller
Variable speed controller
Variable speed controller
376
Description of the multi-axis control system
Operating principle
The TSX CSY 84 or TSX CSY 164 multi-axis control modules and variable speed controllers are connected to the network through fiber optic cables to form the multiaxis control system.
The variable controllers interconnected to the fiber optic network act as individual axes.
The movement control instructions transmitted by the TSX CSY 84 module are sent to each variable controller on the network and, in return, the module receives from the network the real position values of each axis.
Maximum number of real axes managed by a TSX CSY 84 module
A TSX CSY 84 module manages up to 8 real axes, which are in turn associated with l l l l l variable speed controllers.
In addition to these real axes, the module can manage:
4 imaginary axes,
4 external measurement axes,
4 coordinated sets of axes,
4 follower sets of axes,
7 cam profiles.
Number of applicationspecific channels for a
TSX CSY 164 module l l l l
Channels 1 to 16 support real axis functions, imaginary axis functions, and external setpoints,
4 coordinated sets of axes (channels 17 to 20),
4 follower sets of axes (channels 21 to 24),
7 cam profiles (channels 25 to 31).
Development of the application
The application is developed from a terminal (PC) equipped with the PL7 Junior/Pro software that is used to: l l l configure the axes, perform commissioning, adjust the application and run diagnostics.
(See ).
377
Description of the multi-axis control system
SERCOS® ring network
At a Glance By way of the SERCOS® ring structure fiber optic network, the TSX CSY 84/164 modules: l transmits to each axis the movement control instructions defined by the application program, l receives in return, by way of the variable speed controllers, the real data transmitted by the various position sensors of the axes.
SERCOS® ring network
Note: Mounting procedures for the TSX CSY 164 module are the same as for the
TSX CSY 84 module.
The diagram below shows an example of a SERCOS® network configuration composed of 5 LEXIUM variable speed controllers, interconnected by way of fiber optic cables to a TSX CSY 84 module.
PLC station: TSX 57 station example
Transmission
SERCOS® ring network
Reception
Motor 1 Motor 3 Motor 5 Motor 2 Motor 4
378
Sending commands and receiving data
Description of the multi-axis control system
The module coordinates the movements of the different axes installed in the network: l it transmits through the network and to the variable speed controllers the movement control instructions of the various axes, l it receives through the network the current data for each axis and executes on the basis of this data the necessary processes.
From the connector (TX) and by way of the fiber optic cable, the module sends movement instructions to the first variable speed controller, which interprets and executes them. These instructions are then sent to the next variable speed controller.
The last variable speed controller in the ring sends the current data for all the axes to the module connector (RX) by means of the fiber optic cable.
Note: a powered down variable speed controller in the SERCOS® network causes the ring to open, consequently creating a system error.
Cycle time
Transmission speed
Data is transmitted on the network in a single direction, with a typical cycle time of
4 ms. This can be reduced to 2 ms in configuration mode if permitted by the volume of data exchanged.
(See ).
The transmission speed is set by default to 4 Mbauds. If the variable speed controllers cannot support this speed, it may be reduced to 2 Mbauds in configuration mode.
(See ).
Maximum length of the different network segments
The maximum length of each segment of the SERCOS® network is limited to
40 meters, using the plastic fiber optic cables specified by Schneider Automation.
379
Description of the multi-axis control system
Illustration of the various segments
The various segments of the SERCOS® network: l l
TSX CSY 84 module / variable speed controller: segment 1
Variable control / variable control: segment 2 to n l Variable control / module: segment n+1
The diagram below shows the various segments of a SERCOS® network, to which
5 variable speed controllers have been connected.
Segment 1
Variable speed controller
Segment 6
Variable speed controller
Segment 2
Variable speed controller
SERCOS® ring network
Segment 5
Variable speed controller
Segment 3
Segment 4
Variable speed controller
380
Description of the multi-axis control system
Adjusting the optical strength of the transmitter according to the segment length
Each component of the SERCOS® network (TSX CSY 84 module and variable speed controllers) is equipped with an optical transmitter.
For each optical transmitter, the operator must adjust the optical power of the transmitter according to the segment length.
l Optical power of segment 1 (module / first variable speed controller): this is always provided by the optical transmitter of the TSX CSY 84 module. Optical power is adjusted in configuration mode using the PL7 Junior / Pro software by setting a percentage of the optical power in accordance with the segment length.
(See ).
Segment length (in meters)
0 < L < 15
15 < L < 40
Optical power (as a percentage of total power)
66%
100% l Optical power of the other segments (variable controller/variable controller and last variable controller/module): this is always provided by the optical transmitter of the variable controller.
Optical power is adjusted using the UniLink software by setting the segment length only.
381
Description of the multi-axis control system
382
Fiber optic cables
22
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This chapter presents the fiber optic cables for connecting the various components of the SERCOS® network (TSX CSY 84 / 164 modules and variable speed controllers).
This chapter contains the following topics:
Topic
Pre-assembled fiber optic cables
Kits for creating custom fiber optic cables
Page
383
Fiber optic cables
Pre-assembled fiber optic cables
At a Glance
List of cables
Schneider Automation offers a range of 1 mm diameter plastic fiber optic cables for connecting the different components of the SERCOS® network (TSX CSY 84 / 164 modules and variable speed controllers). Each cable is equipped at each end with an SMA type connector.
The table below provides the reference and length of each cable.
References
990 MCO 00001
990 MCO 00003
990 MCO 00005
990 MCO 00015
990 MCO 00055
990 MCO 00075
990 MCO 000125
Lengths
0.3 meters
0.9 meters
1.5 meters
4.5 meters
16.5 meters
22.5 meters
37.5 meters
Recommendations
When installing fiber optic cables, it is necessary to comply with the following recommendations:
Note: Recommendations concerning the curve radius of the cables.
For this type of cable, the minimum curve radius must be greater than 25 mm.
Failure to observe this may result in damage to the cables.
Note: Recommendation concerning the tension applied to the cables on installation.
The maximum tension applied to the cables on installation must not exceed 6 Kg.
Failure to observe this may result in damage to the cables.
Maximum permitted temperature: -40°C+80°C.
384
Fiber optic cables
Kits for creating custom fiber optic cables
At a Glance
Tool kit
Schneider Automation offers two kits for creating custom cables: l l
1 tool kit,
1 equipment kit comprising a cable and connectors.
The table below provides the reference and the contents of the tool kit.
Reference
990 MCO KIT 00
1
1
1
1
Contents
Quantity Description
Service instructions for creating a cable
Cable stripping tool
Connector clip pliers
25 W / 110 V soldering iron
Equipment kit The table below provides the reference and the contents of the equipment kit.
Reference
990 MCO KIT 01
Contents
Quantity
12
12
1
Description
SMA type connectors
Insulation sleeves
30-meter plastic fiber optic cable
385
Fiber optic cables
386
Characteristics, Standards and service conditions
23
At a Glance
Subject of this
Chapter
What's in this
Chapter?
This chapter presents the different characteristics of the TSX CSY 84 module and the SERCOS® network.
This chapter contains the following topics:
Topic
Characteristics of the module
Characteristics of the SERCOS® network
Standards and service conditions
Page
387
Characteristics, Standards and service conditions
Characteristics of the module
Electrical characteristics
The following table gives the electrical characteristics of the module.
Description of the parameters Values
Typical
1.8 A
Maximum
2 A Current consumed by the module from the
5V of the rack power supply
Power dissipated in the module
Fiber optic outputs
9 W 10 W
Complies with standard EN 61491
Operating and storage temperature/ hygrometry/ altitude
The following table gives the electrical characteristics of the module.
Description of the parameters
Operating temperature
Storage temperature
Hygrometry (without condensation)
Operating altitude
Values
0 to 60°C
-25°C to 70°C
5% to 95%
0 to 2000 m
388
Characteristics, Standards and service conditions
Characteristics of the SERCOS® network
Table of characteristics
The following table gives the main characteristics of the SERCOS® network.
Description of the parameters
Addresses
Baud rate
Cycle time
Values
1...254
2 or 4 Mbauds, configurable by software
4 ms
389
Characteristics, Standards and service conditions
Standards and service conditions
Standards Identical standards to those applied to Premium PLCs (see).
Standard EN 61491:
Electrical equipment of industrial machinery. Serial data link for real-time communication between control units and drive devices.
Service conditions and recommendations linked to the environment
These are identical to those applied to Premium PLCs (see).
390
Compatible variable speed controllers
24
List of variable speed controllers
List of variable controllers in the
Schneider
Electric range
Schneider Electric offers a range of variable speed controllers that are compatible with the SERCOS® range on Premium PLCs. The table below provides the reference and description of each variable speed controller.
Reference
MHD• 1004 •00
MHD• 1008 •00
MHD• 1017 •00
MHD• 1028 •00
MHD• 1056 •00
MHD• 1112 •00
MHD• 1198 •00
Description
LEXIUM variable speed controller, continuous current of 1.5 A rms
LEXIUM variable speed controller, continuous current of 3 A rms
LEXIUM variable speed controller, continuous current of 6 A rms
LEXIUM variable speed controller, continuous current of 10 A rms
LEXIUM variable speed controller, continuous current of 20 A rms
LEXIUM variable speed controller, continuous current of 40 A rms
LEXIUM variable speed controller, continuous current of 70 A rms
Other variable speed controllers
All EN 61491-compliant variable speed controllers may be used with the
TSX CSY 84/164 modules.
391
Compatible variable speed controllers
392
Index
Numerics
15-pin SUB-D connector, 63, 66
A
Auxiliary input characteristics, 59
Auxiliary output characteristics, 61
Availability of counting signals, 101, 104
Availability of signals on TELEFAST, 195,
C
Caractéristiques TELEFAST 2
Compatibility of translators, 266
Connecting
counting signals on the TSX CAY, 175
encoder with TSX TAP S15 05, 137
encoder with TSX TAP S15 24, 138
encoders with 10...30 V supply, 113
sensors onto auxiliary I/O, 91
TELEFAST 2
the variable speed controller using the
to a NUM MDLA variable speed controller, 190
Connection
of terminals with the TELEFAST prewiring system, 169
Phytron translator with TSX CFY 11/21 modules, 267
TSX CFY to a translator, 240, 241
TSX CFY with TELEFAST system, 250
using a TSX CDP 301 / 501 pre-wired strand, 248
using the TELEFAST pre-wiring system,
393
Index
using TSX CDP 301 or 501 strips, 199
Count sensor supply monitor characteristics,
Counter input characteristics, 53, 55
Counting module characteristics, 52, 54, 56
Counting modules
up/down counting and measurement functions, 27
E
H
I
IA, IB and IZ compatibility, 57
M
Mounting and measurements of the TSX
O
Overview of the TSX TAP 15•• wiring accessories, 134
P
Pre-wired strands and cable, 139
R
Rules and precautions for wiring, 126
394
S
Signal labeling, 203, 238, 243
T
TAP MAS connection device, 172
TELEFAST 2
TELEFAST/15 pin SUB-D correspondence,
TELEFAST/HE10 correspondence, 105,
TELEFAST/SUB-D correspondence, 171
TSC CFY
characteristics of translator inputs, 258
TSX CAY
analog output characteristics, 209
characteristics of auxiliary inputs, 213
characteristics of the counting inputs,
characteristics of the Q0 reflex outputs,
characteristics of the relay outputs, 220
characteristics of the variable speed controller inputs, 218
connection using TSX CAP S9, 167
general precautions for wiring, 160
TSX CAY modules
TSX CFY
characteristics of auxiliary inputs, 260
characteristics of Q0 brake output, 262
characteristics of translator outputs, 259
general precautions for wiring, 236
TSX CFY module
TSX TAP S15 05 mounting and dimensions,
U
Up/down counting and measuring on the
Up/down counting on the TSX CTY 2A/4A,
W
Wiring precautions, 78, 200, 253
Index
395
Index
396