Schneider Electric XBTL1AB01 DF1 Protocol Instruction Sheet
Reklamë
Reklamë
Telemecanique
Protocole DF1
DF1 Protocol
Instruction de service
Instruction sheet
Bedienungsanweitsung
Istruzioni di servizio
Instrucción de servicio
03/2006
XBT-L1 AB 01 DF1 Protocol
Contents
Safety Information _________________________________ 25
1 - Compatibility ____________________________________ 27
2 - Installing the Protocol: Start up XBT L1000 ____________ 27
3 - Operating Principle _______________________________ 28
4 - Content of the Dialog Table ________________________ 29
5 - Configuring the Dialog Table _______________________ 32
6 - Equipment Symbol (CPU)__________________________ 32
7- DF1 Protocol Parameters __________________________ 33
8 - Objects Supported _______________________________ 34
9 - Implementation __________________________________ 35
9.1 Cables ____________________________________ 35
9.2 Diagrams___________________________________ 35
10 - Diagnosis ______________________________________ 38
11 - Internal Date and Time ___________________________ 39
I
S
H
E
N
G
L
35012365 02
23
03/2006
I
S
H
E
N
G
L
XBT-L1 AB 01 DF1 Protocol
35012365 02
24
03/2006
XBT-L1 AB 01
Safety Information
Important Information
NOTICE
DF1 Protocol
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
I
S
H
E
N
G
L
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.
PLEASE NOTE
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.
© 2006 Schneider Electric. All Rights Reserved.
35012365 02 03/2006
25
I
S
H
E
N
G
L
XBT-L1 AB 01 DF1 Protocol
35012365 02
26
03/2006
XBT-L1 AB 01 DF1 Protocol
1 - Compatibility
The DF1 protocol developed on the MAGELIS terminal can be used to communicate with the following Allen Bradley process controllers:
- SLC-500, Micrologix 1000 / Micrologix 1200,
- PLC-5,
- PLC-2, PLC-3 and PLC-4.
2 - Installing the Protocol: Start up XBT L1000
CAUTION
EQUIPMENT DAMAGE HAZARD
The protocol should only be installed and used by authorized and properly trained personnel.
Failure to follow this instruction can result in injury, equipment damage or production loss.
Two scenarios:
- If no protocol has been installed, the "Install Protocol" dialog box opens automatically.
- If a protocol has already been installed, you can update the previous version or install another protocol. Close all open applications in XBT L1000 then select the File/Install
Protocol menu.
I
S
H
E
N
G
L
35012365 02
27
03/2006
I
S
H
E
N
G
L
XBT-L1 AB 01 DF1 Protocol
3 - Operating Principle
XBT is Client.
The XBT operating principle is based on a "dialog table" which is situated in the process controller (Server).
XBT in its capacity as Client performs 3 types of action:
- initiated by the automated system,
- initiated by the operator,
- self-initiated.
The DF1 protocol is the communication protocol for Allen Bradley process controllers.
Depending on the type of process controllers in the range, the dialog will be supported by different types of frames:
• Specific SLC-500 frames or Micrologix 1000 / Micrologix 1200 (if only SLC-500 or Micrologix 1000 / Micrologix 1200 process controllers are addressed),
• Specific PLC-5 frames (if only PLC-5 process controllers are addressed),
• "BASIC COMMAND SET" generic frames (if different types of equipment such as
SLC-500, PLC-5, PLC-4, PLC-3, PLC-2, Micrologix 1000 / Micrologix 1200 are addressed without distinction,
Certain restrictions will apply to the access to the process controller data depending on the type of frame selected (see
).
The dialog between the MAGELIS terminal as client (requester) of the exchange, and the equipment as servers is of question/reply type.
Half/Full Duplex Link
The terminal automatically detects whether the link is of half or full duplex type.
The XBT can be connected in point-to-point mode, or the network of 254 possible PLCs can be used via the polling system. This characteristic is transparent to the user and the
XBT functions remain the same except for addressing which in the case of a point-topoint link is limited to the directly connected process controller (MASTER).
Automatic Detection of Full Duplex
It is important to note that the XBT should be connected to the network before turning on the power supply.
The polling detection mechanism is switched on when the XBT is powered on and switches off after about 30 seconds. This is why if the XBT is connected to the network when the mechanism is switched off, the controller will be automatically considered to be configured in Full Duplex and the XBT will behave as such.
Note:
If using Basic Command Set, you cannot write to an odd address when linked to a PLC-5.
Accordingly, it is best not to use the dialog table.
35012365 02 03/2006
28
XBT-L1 AB 01 DF1 Protocol
4 - Content of the Dialog Table
The dialog table will vary according to which XBT is selected. Below is a list of accessible functions for each type of terminal as well as the default table for each one .
N° FUNCTION
XBT H
XBT HM
00 • 010
XBT H
XBT HM
02 • 010
XBT H
XBT HM
01 • 010
XBT H
XBT HM
01 • 110
XBT P
01 • 010
XBT P
02 • 010
XBT P
02 • 110
XBT E
01 • 010
XBT E
01 • 110
1 Image of static function keys
2 Image of system keys
3 Image of numeric keys
4 Communication control
5 Set PLC clock
6 No. of displayed page
7 No. of last field entered
22 No. of last alarm acknowledged
8 Report
9 Log filling rate
10 N° of page to be processed
11 N° of field to be entered
12 Print command
13 Table write autorization
14 Clear log/Advanced functions
15 Static function keys LEDs lighting
16 Static function keys locking
17 System keys locking
18 Numeric keys locking
19 Alarm table
20 Set terminal clock
21 Free format print table
I
S
H
E
N
G
L
: Functions selected by default in XBT L1000
: Other available functions
: Not available
WARNING
UNINTENDED EQUIPMENT OPERATION
The protocol should only be installed and used by authorized and properly trained personnel.
Failure to follow this instruction can result in death, serious injury, equipment damage or production loss.
35012365 02 03/2006
29
XBT-L1 AB 01
I
S
H
E
N
G
L
N° FUNCTION
3
4
1
2
Image of static function keys
Image of system keys
Image of numeric keys
Communication control
5
6
Set PLC clock
No. of displayed page
7 No. of last field entered
22 No. of last alarm acknowledged
8
9
Report
Log filling rate
24 Graphs plotting performed
30 Checksum application
31 Terminal advanced state
32 Last recipe transferred
10 No. of page to be processed
11 No. of field to be entered
12 Print command
33 No. of recipe to be transferred
25 Activating graphs plotting
13 Table write authorization
26 Recipe transfer not allowed
14 Clear log/Advanced functions
15 LED control
16 Static function keys locking
17 System keys locking
18 Numeric keys locking
34 Terminal language
19 Alarm table
20 Set terminal clock
21 Free format print table
Other device:
FUNCTION
No. of last alarm acknowledged
Last groups of alarm acknowledged
Alarm table
: Functions selected by default in XBT L1000
: Other available functions
: Not available
XBT F01/F02
XBT F01/F02
35012365 02
30
DF1 Protocol
XBT F03/FC
XBT F03/FC
03/2006
XBT-L1 AB 01 DF1 Protocol
Device Containing the Main Dialog Table
N° FUNCTION
1 Image of static function keys
2 Image of system keys
3 Image of numeric keys
4 Communication control
5 Set PLC clock
6 No. of displayed page
7 No. of last field entered
22 No. of last alarm acknowledged
8 Report
9 Log filling rate
24 Graphs plotting performed
30 Checksum application
31 Terminal advanced state
32 Last recipe transferred
10 N° of page to be processed
11 N° of field to be entered
12 Print command
33 N° of recipe transferred
25 Activating graphs plotting
13 Table write autorization
26 Recipe transfer not allowed
14 Clear log/Advanced functions
15 LED control
16 Static function keys locking
17 System keys locking
18 Numeric keys locking
34 Terminal language
19 Alarm table
20 Set terminal clock
21 Free format print table
Other device:
FUNCTION
No. of last alarm acknowledged
Alarm table
Function
XBT N401(1)
Input
XBT N401(2)
Function
XBT N410(1)
Input
XBT N410(2)
XBT N401
: Functions selected by default in XBT L1000
: Other available functions
: Not available
XBT N410
XBT R410 XBT R411
XBT R4..
35012365 02 03/2006
31
I
S
H
E
N
G
L
XBT-L1 AB 01 DF1 Protocol
I
S
H
E
N
G
L
5 - Configuring the Dialog Table
To configure the dialog table:
2
3
Step
1
Action
Select Configuration/Dialog Table.
Enter the table start address and the scan time.
Construct the tabme by adding or deleting the functions required for your application.
Note:
Refer to the user’s manuals for graphic (XBT F/FC), alphanumeric terminals
(XBT H/E/P/HM) and XBT N/XBT R terminals in the MAGELIS range for more detailed information about dialog table content.
The dialog tables are made up of words
.
The addresses produced by XBT-L1000 are byte-type addresses. This means that the address of a dialog table element is equal to:
Address = n + 2 i
where: n = address of the beginning of the table,
i = word index of the element in the table.
6 - Equipment Symbol (CPU)
-Select the target equipment in the "Configuration/Equipment Symbol" menu.
WARNING
UNINTENDED EQUIPMENT OPERATION
The protocol should only be installed and used by authorized and properly trained personnel.
Failure to follow this instruction can result in death, serious injury, equipment damage or production loss.
35012365 02 03/2006
32
XBT-L1 AB 01
7- DF1 Protocol Parameters
DF1 Protocol
Under XBT-L1000, from the configuration menu, select the protocol parameters.
Parameters
Encoding system
Bits per character
- start bit
- significant bit
- parity
- stop bit
- speed
(9600 bauds by default)
Message organization
- Control
- Resend on error
- Request for ackowledgement
Station number
Type of automation
Types of link
Possible values
8-bit binary code
1
8 even/none
1
300 to 19200 baud
BCC on 8 bits or CRC on 16 bits
1 to 255 ( 3 by default)
1 to 255 (3 by default)
1 to 254
Default/PLC-500/PLC-/Micrologix
RS232C
I
S
H
E
N
G
L
35012365 02
33
03/2006
XBT-L1 AB 01 DF1 Protocol
8 - Objects Supported
Type of object supported Mnemonic (syntax) bit word double word floating string
Nf:i/j
Nf:i
= word
= word
= word
I
S
H
E
N
G
L
Mnemonic identifiers f : 7... 255 i : 0…255 j : 0…15
•
File f number
Indicates the number of the file in the process controller that the operator wishes to access.
Depending on the choice of process controller type, the possible file number will be:
Process controller type File number
Default (Basic Command Set) - For a SLC-500 use 9.
- For a PLC-5 this number.
corresponds to the transmitter's network address.
PLC-5
SLC-500
Micrologix 1000 / Micrologix 1200 7
Between 9 and 255.
Between 9 and 255.
• Index i
Indicates the item number in the selected field.
Note :
If you use the Basic Command Set this item number may be interpreted differently according to the type of process controller. For further information refer to your process controller's technical documentation.
• Index j
It will only be possible to access this field if the selected data type is Nf:i/j.
It indicates the bit's row in the word (selected by means of the i field)
35012365 02 03/2006
34
XBT-L1 AB 01
9 - Implementation
9.1 Cables
Automatons
SLC5
PLC5
Micrologix
Physical link
RS232
RS232
RS232
References
XBT-Z9730
XBT-Z9720
XBT-Z9731
Length
2.5 m
2.5 m
2.5 m
DF1 Protocol
I
S
H
E
N
G
L
9.2 Diagrams
RS 232 C LINK
Length
M
M
23#
+ + +
Speed (Bauds)
Wiring = 3 shielded wires (minimum cross-section 0,6 mm
2
AWG22)
35012365 02 03/2006
35
I
S
H
E
N
G
L
XBT-L1 AB 01
- PLC-5
XBT MAGELIS Terminal
0'
TRANSMISSION 48$
RECEPTION 28$
0V
3' 3'
243
#43
$32
$42
Console DF1 coupler
0'
48$
TRANSMISSION
28$
RECEPTION
DF1 Protocol
* The connection of the shielding at each end depends on the electrical constraints relative to the installation.
Note:
In certain configurations, it will not be necessary to invert pins 2 and 3.
Refer to the documentation for the process controller you are using.
35012365 02
36
03/2006
XBT-L1 AB 01 DF1 Protocol
- Micrologix 1000 / Micrologix 1200
Use the XBT-Z9731 cable
XBT MAGELIS Terminal PLC DF1 coupler
0'
48$
28$
3'
28$
48$
3'
6
I
S
H
E
N
G
L
- SLC-500
XBT MAGELIS Terminal PLC DF1 coupler
0'
48$
28$
3'
35012365 02
37
03/2006
XBT-L1 AB 01 DF1 Protocol
I
S
H
E
N
G
L
10 - Diagnosis
Behavior in the event of an error:
Display of "??????…" in the event of a transmission error: format/parity/CRC/no response or exception response.
Display of check marks for graphic objects if there is no response, or if the communication function is faulty
No repetition in the event of no response.
Diagnosis counters:
3 diagnosis counters can be displayed on the protocol’s system page (line parameters):
CPT 1/ Counter #1
: Number of errorfree
replies received.
CPT 2/ Counter #2
: Number of replies received with
a check frame byte error.
CPT 3/ Counter #3
: Number of requests still unanswered.
For XBT N/R, the counters #4 to #8 are not used.
35012365 02
38
03/2006
XBT-L1 AB 01 DF1 Protocol
11 - Internal Date and Time
In order to access the date and time in the terminals, it is possible to define alphanumeric fields addressed on internal variables in XBT L1000.
XBT H/P/E/HM terminals
XBT device
VB:i type variable i = 100000 for date, i = 100002 for time
I
S
H
E
N
G
L
Object: String
Type: ASCII
Length: 8
Date format: DD/MM/YY
Time format: HH:MM:SS
XBT F terminals
XBT device
VB:i type variable
Two possible syntaxes:
Symbol: century, year, month, day_of_the_week, hour, minute, second
Format type: decimal
Length: 2
Format: Word
Or
Symbol: Date_ASCII, Time_ASCII
Format type: String
Length: 6
Format: ASCII
XBT N/R terminals
XBT device
VB:i type variable
Symbol: Date_ASCII, Time_ASCII
Format type: String
Length: 8 or 10
Format: ASCII
35012365 02 03/2006
39
I
S
H
E
N
G
L
XBT-L1 AB 01 DF1 Protocol
35012365 02
40
03/2006
03 / 2006 35012365 02