Schneider Electric Quantum using EcoStruxure™ Control Expert - Ethernet Network Modules User Manual
Publicitate
Publicitate
Quantum using EcoStruxure™ Control Expert
33002479 10/2019
Quantum using
EcoStruxure™
Control Expert
Ethernet Network Modules
User Manual
Original instructions
10/2019 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this document on any medium whatsoever without permission of Schneider Electric, given in writing. You also agree not to establish any hypertext links to this document or its content.
Schneider Electric does not grant any right or license for the personal and noncommercial use of the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.
33002479 10/2019
Table of Contents
Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part I Modicon Quantum with Control Expert Ethernet
Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Module Description 140 CPU 651 x0 . . . . . . . . . . . . . . . . . . . . . . . . .
140 CPU 651 x0 Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Presentation and Mounting of Standard High End Modules .
CPU Controls and Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the CPU LCD Display Screens . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Module Description 140 NOE 771 xx and 140 NWM 100 00 . . . . . . .
Modicon Quantum Ethernet Modules Overview . . . . . . . . . . . . . . . . .
Indicators for Ethernet Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connectors and Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the 140 NOE 771 11 Ethernet Module in a Quantum Safety
Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Installing the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable Schemes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting the Module in the Quantum PLC Backplane . . . . . . . . . . . .
Connecting the Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assigning Ethernet Address Parameters. . . . . . . . . . . . . . . . . . . . . . .
Establishing the FTP Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Establishing HTTP and Write Passwords for NOE . . . . . . . . . . . . . . .
Using BOOTP Lite to Assign Address Parameters . . . . . . . . . . . . . . .
1.4 Customer Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Customer Support Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Ethernet Communication Services . . . . . . . . . . . . . . . . .
Modicon Quantum with Control Expert Ethernet Services . . . . . . . . .
Address Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SNMP and Schneider Private MIB Overview . . . . . . . . . . . . . . . . . . .
Modbus Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33002479 10/2019
9
13
71
72
73
74
63
66
69
70
76
78
79
56
57
59
60
49
51
52
54
22
24
28
30
17
19
20
21
41
42
46
48
3
4
I/O Scanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Synchronization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electronic Mail Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bandwidth Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FTP Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Embedded Web Pages (HTTP Server, Web Configuration and
Diagnostics) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Additional Ethernet Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part II Modicon Quantum with Control Expert Ethernet
Modules Services. . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3 Start Communication with Control Expert. . . . . . . . . . . . .
3.1 How to Configure the Communication . . . . . . . . . . . . . . . . . . . . . . . . .
Add a New Network to the Communication Folder . . . . . . . . . . . . . . .
Configure Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Properties of a Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Delete an Existing Network Folder. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Control Expert Communication Links. . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Configuration Principle . . . . . . . . . . . . . . . . . . . . . . . .
Link between Configuration and Communication. . . . . . . . . . . . . . . . .
Link between Data and Communication . . . . . . . . . . . . . . . . . . . . . . .
3.3 Selecting the Ethernet Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting the Quantum NOE Ethernet Module . . . . . . . . . . . . . . . . . .
Security (Enable / Disable HTTP, FTP, and TFTP) . . . . . . . . . . . . . . .
IP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum NOE Ethernet Messaging Configuration . . . . . . . . . . . . . . .
3.4 Selecting the Ethernet Coprocessor . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting the Modicon Quantum with Control Expert Ethernet
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the IP Address of the Ethernet Controller . . . . . . . . . . . . .
Modicon Quantum with Control Expert Ethernet Controller Messaging
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100
101
102
103
104
107
108
109
112
96
97
98
99
91
93
94
95
113
115
116
81
83
84
85
86
87
88
90
33002479 10/2019
Part III Using the Modicon Quantum with Control Expert
Ethernet Services . . . . . . . . . . . . . . . . . . . . . . . . . . .
117
Chapter 4 Transferring Data Using Communication Blocks . . . . . .
4.1 IEC Data Transfer Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CREAD_REG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CWRITE_REG. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
READ_REG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WRITE_REG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TCP_IP_ADDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 MBP_MSTR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Block Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network Control Block Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Plus, SY/MAX, and Ethernet TCP/IP Error Codes. . . . . . . . .
CTE Error Codes for SY/MAX and TCP/IP Ethernet . . . . . . . . . . . . . .
SY/MAX-Specific Error Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Read Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Write Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Get Local Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear Local Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Get Remote Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear Remote Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TCP/IP Ethernet Network Statistics. . . . . . . . . . . . . . . . . . . . . . . . . . .
TCP/IP Ethernet Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reset Optional Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Read CTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Write CTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Send Email . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Send Modbus Request . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Close Connection Request . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Change Modbus Plus Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Read/Write Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enable / Disable HTTP or FTP/TFTP Services . . . . . . . . . . . . . . . . . .
169
171
173
178
179
181
182
154
155
156
158
159
162
166
167
136
139
140
143
147
148
150
152
119
120
121
124
127
130
133
135
33002479 10/2019
5
6
Chapter 5 Global Data (Publish/Subscribe) Utility. . . . . . . . . . . . . . .
185
Planning the Global Data (Publish/Subscribe) System . . . . . . . . . . . .
Multicast Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum NOE Global Data Configuration . . . . . . . . . . . . . . . . . . . . . .
186
190
192
Configuration of Global Data (Publish/Subscribe) by the Web for NOE
771 x1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Scanner Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
195
Chapter 6 I/O Scanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
199
Configuring the Quantum I/O Scanner. . . . . . . . . . . . . . . . . . . . . . . . .
I/O Scanning Contextual Menu for Copy/Cut/Paste. . . . . . . . . . . . . . .
200
204
210
212
I/O Scanning with Multiple Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction to Configuring Advantys from Control Expert . . . . . . . . . .
Introduction to Configuring the PRM Master DTM . . . . . . . . . . . . . . . .
Introduction to Configuring a BMX PRA 0100 from Control Expert . . .
Property Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Saving an Advantys Configuration in an Control Application . . . . . . . .
Managed Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Scanner Response Times: Remote Input to Remote Output . . . . .
Chapter 7 Address Server Configuration/Fast Device Replacement
Address Server Configuration/Fast Device Replacement . . . . . . . . . .
ASN.1 Naming Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring an NOE with SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring an NOE with TFE Private MIB . . . . . . . . . . . . . . . . . . . . .
214
218
220
224
230
231
233
237
238
240
Understanding Fast Device Replacement . . . . . . . . . . . . . . . . . . . . . .
Configuring Fast Device Replacement. . . . . . . . . . . . . . . . . . . . . . . . .
242
Chapter 8 Network Management Service (SNMP) . . . . . . . . . . . . . .
247
SNMP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
248
250
252
254
Chapter 9 NTP Time Synchronization Service . . . . . . . . . . . . . . . . .
263
Introducing the NTP Time Synchronization Service. . . . . . . . . . . . . . .
Using the R_NTPC Block for Time Synchronization . . . . . . . . . . . . . .
264
267
NTP Time Synchronization Service Operating Conditions. . . . . . . . . .
Configuring the NTP Time Service. . . . . . . . . . . . . . . . . . . . . . . . . . . .
269
270
Chapter 10 Electronic Mail Notification Service . . . . . . . . . . . . . . . . .
275
Introducing the Electronic Mail Notification Service . . . . . . . . . . . . . . .
Mail Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the MBP_MSTR Block for Mail Service Communication . . . . . .
Mail Service Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electronic Mail Notification Service Subtree . . . . . . . . . . . . . . . . . . . .
276
278
279
281
282
33002479 10/2019
Chapter 11 Embedded Web Pages. . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Monitoring Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostics Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the Web Utility Home Page . . . . . . . . . . . . . . . . . . . . . . . .
Configured Local Rack Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Status Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CPU Configuration Screen: Data Field Descriptions . . . . . . . . . . . . . .
Remote I/O Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum PLC Data Monitor Page. . . . . . . . . . . . . . . . . . . . . . . . . . . .
SNMP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global Data (Publish/Subscribe) Utility Configuration . . . . . . . . . . . . .
Configure Address Server Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the Time Synchronization Service . . . . . . . . . . . . . . . . . .
Mail Service Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ethernet Module Diagnostic Pages . . . . . . . . . . . . . . . . . . . . . . . . . . .
NTP Diagnostics Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Properties Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contacting Schneider Electric Page . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 12 Hot Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quantum Hot Standby for Control Expert . . . . . . . . . . . . . . . . . . . . . .
Hot Standby Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NOE Module Configuration and Hot Standby . . . . . . . . . . . . . . . . . . .
140 NOE 771 x1 / 140 NOC 78• 00 IP Address Assignment . . . . . . .
140 NOE 771 x1 / 140 NOC 78• 00 Operating Modes in Quantum Hot
Standby System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
NOE IP Address Swap Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reading and Clearing the Crash Log . . . . . . . . . . . . . . . . . . . . . . . . .
Downloading a New NOE Exec. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloading a New NOE Exec via FTP . . . . . . . . . . . . . . . . . . . . . . .
Downloading a New NOE Kernel . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
332
336
Network Effects of Modicon Quantum Hot Standby with Control Expert
Solution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
337
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
341
Appendix A Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Responding to Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
343
344
349
350
351
353
355
355
293
294
295
296
299
302
305
310
283
284
285
287
288
290
291
292
312
320
322
323
325
326
328
329
330
33002479 10/2019
7
8
Appendix C Quantum Ethernet TCP/IP Modbus Application Protocol .
357
Modbus Application Protocol Overview . . . . . . . . . . . . . . . . . . . . . . . .
Modbus Application Protocol PDU . . . . . . . . . . . . . . . . . . . . . . . . . . . .
358
360
Modbus Application Protocol Service Classes. . . . . . . . . . . . . . . . . . .
Modbus Application Protocol PDU Analysis. . . . . . . . . . . . . . . . . . . . .
TCP/IP Specific Issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Closing a TCP Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
362
363
365
366
367
Appendix D Installation and Configuration of a Modicon Quantum
Platform . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
369
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring the Rack with Control Expert . . . . . . . . . . . . . . . . . . . . . .
Configuring the Ethernet Network with Control Expert. . . . . . . . . . . . .
Configuring the I/O Scanning Service . . . . . . . . . . . . . . . . . . . . . . . . .
Building and Downloading the Configuration Program . . . . . . . . . . . .
Diagnosing the Ethernet Module Using the Web Server . . . . . . . . . . .
370
371
372
375
378
384
388
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
391
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
399
33002479 10/2019
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
33002479 10/2019
9
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
BEFORE YOU BEGIN
Do not use this product on machinery lacking effective point-of-operation guarding. Lack of effective point-of-operation guarding on a machine can result in serious injury to the operator of that machine.
WARNING
UNGUARDED EQUIPMENT
Do not use this software and related automation equipment on equipment which does not have point-of-operation protection.
Do not reach into machinery during operation.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
10
This automation equipment and related software is used to control a variety of industrial processes.
The type or model of automation equipment suitable for each application will vary depending on factors such as the control function required, degree of protection required, production methods, unusual conditions, government regulations, etc. In some applications, more than one processor may be required, as when backup redundancy is needed.
Only you, the user, machine builder or system integrator can be aware of all the conditions and factors present during setup, operation, and maintenance of the machine and, therefore, can determine the automation equipment and the related safeties and interlocks which can be properly used. When selecting automation and control equipment and related software for a particular application, you should refer to the applicable local and national standards and regulations. The
National Safety Council's Accident Prevention Manual (nationally recognized in the United States of America) also provides much useful information.
In some applications, such as packaging machinery, additional operator protection such as pointof-operation guarding must be provided. This is necessary if the operator's hands and other parts of the body are free to enter the pinch points or other hazardous areas and serious injury can occur.
Software products alone cannot protect an operator from injury. For this reason the software cannot be substituted for or take the place of point-of-operation protection.
Ensure that appropriate safeties and mechanical/electrical interlocks related to point-of-operation protection have been installed and are operational before placing the equipment into service. All interlocks and safeties related to point-of-operation protection must be coordinated with the related automation equipment and software programming.
33002479 10/2019
NOTE: Coordination of safeties and mechanical/electrical interlocks for point-of-operation protection is outside the scope of the Function Block Library, System User Guide, or other implementation referenced in this documentation.
START-UP AND TEST
Before using electrical control and automation equipment for regular operation after installation, the system should be given a start-up test by qualified personnel to verify correct operation of the equipment. It is important that arrangements for such a check be made and that enough time is allowed to perform complete and satisfactory testing.
WARNING
EQUIPMENT OPERATION HAZARD
Verify that all installation and set up procedures have been completed.
Before operational tests are performed, remove all blocks or other temporary holding means used for shipment from all component devices.
Remove tools, meters, and debris from equipment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Follow all start-up tests recommended in the equipment documentation. Store all equipment documentation for future references.
Software testing must be done in both simulated and real environments.
Verify that the completed system is free from all short circuits and temporary grounds that are not installed according to local regulations (according to the National Electrical Code in the U.S.A, for instance). If high-potential voltage testing is necessary, follow recommendations in equipment documentation to prevent accidental equipment damage.
Before energizing equipment:
Remove tools, meters, and debris from equipment.
Close the equipment enclosure door.
Remove all temporary grounds from incoming power lines.
Perform all start-up tests recommended by the manufacturer.
33002479 10/2019
11
OPERATION AND ADJUSTMENTS
The following precautions are from the NEMA Standards Publication ICS 7.1-1995 (English version prevails):
Regardless of the care exercised in the design and manufacture of equipment or in the selection and ratings of components, there are hazards that can be encountered if such equipment is
improperly operated.
It is sometimes possible to misadjust the equipment and thus produce unsatisfactory or unsafe operation. Always use the manufacturer’s instructions as a guide for functional adjustments.
Personnel who have access to these adjustments should be familiar with the equipment manufacturer’s instructions and the machinery used with the electrical equipment.
Only those operational adjustments actually required by the operator should be accessible to the operator. Access to other controls should be restricted to prevent unauthorized changes in operating characteristics.
12
33002479 10/2019
About the Book
At a Glance
Document Scope
This document is for users who want their Quantum PLC to communicate with devices over an
Ethernet network. It assumes that you have some knowledge of PLC systems and a working knowledge of Modsoft, Concept, ProWORX, or Control Expert programming tools. You also need to understand the use of Ethernet networks and TCP/IP.
This document describes the functionality of the Modicon Quantum Ethernet modules, the
104 NOE 771 xx and 140 NWM 100 00 modules, and the Ethernet port of the 140 CPU 651 x0 modules.
Model Number
140 NOE 771 00
140 NOE 771 01
140 NOE 771 10
140 NOE 771 11
140 NWM 100 00
140 CPU 651 50
140 CPU 651 60
Module Type
Ethernet option adapter
Ethernet option adapter
FactoryCast Ethernet option adapter
FactoryCast Ethernet option adapter
FactoryCast HMI option adapter
CPU with embedded Ethernet port
CPU with embedded Ethernet port
This document describes how to install, set up, and use Ethernet-enabled modules in a Modicon
Quantum control system. These modules allow the Quantum system to communicate with devices over an Ethernet network. Topics addressed in this manual include:
the hardware architecture of a Modicon Quantum Ethernet module, which is designed to fit into
a single slot on the standard Modicon Quantum backplane capabilities and installation of 140 NOE 771 xx and 140 NWM 100 00 modules in a Modicon
Quantum system capabilities of the Ethernet port on the 140 CPU 651 x0 CPU modules
33002479 10/2019
13
14
This document describes the procedures for:
setting up the modules to transfer data using either the Global Data modules (140 NOE 771 01,
140 NOE 771 11, or 140 CPU 651 x0 mobules) or the I/O scanner utility (in the
140 NOE 771 00/01/11 modules and the 140 CPU 651 50/60 modules) using an embedded Web server to access diagnostics and online configurations for the module and its associated controller
using the FactoryCast Web server to customize your configuration via embedded Web pages
(in 140 NOE 771 10/11 and 140 NWM 100 00 modules) using an NOE module in a Hot Standby solution for fault-tolerant remote I/O and communications
Nomenclature
The following table describes the naming rules for various groups of modules:
The Name ...
140 NOE 771 xx
140 NOE 771 x0
140 NOE 771 x1
140 NOE 771 0x
140 NOE 771 1x
140 CPU 651 x0
Refers to the ...
140 NOE 771 00, 140 NOE 771 01, 140 NOE 771 10 and 140 NOE 771 11 modules
140 NOE 771 00 and 140 NOE 771 10 modules
140 NOE 771 01 and 140 NOE 771 11 modules
140 NOE 771 00 and 140 NOE 771 01 modules
140 NOE 771 10 and 140 NOE 771 11 modules
140 CPU 651 50 and 140 CPU 651 60 modules
NOTE: Before adding a node to an existing corporate network, consult with your information technology (IT) department about any possible consequences.
33002479 10/2019
Validity Note
This document is valid for EcoStruxure™ Control Expert 14.1 or later.
The technical characteristics of the devices described in the present document also appear online.
To access the information online:
Step
1
2
3
4
5
6
Action
Go to the Schneider Electric home page www.schneider-electric.com
.
In the Search box type the reference of a product or the name of a product range.
Do not include blank spaces in the reference or product range.
To get information on grouping similar modules, use asterisks ( * ).
If you entered a reference, go to the Product Datasheets search results and click on the reference that interests you.
If you entered the name of a product range, go to the Product Ranges search results and click on the product range that interests you.
If more than one reference appears in the Products search results, click on the reference that interests you.
Depending on the size of your screen, you may need to scroll down to see the datasheet.
To save or print a datasheet as a .pdf file, click Download XXX product datasheet.
The characteristics that are presented in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.
Related Documents
Title of Documentation
Control Panel Technical Guide, How to protect a machine from malfunctions due to electromagnetic disturbance
Reference Number
CPTG003_EN (English),
CPTG003_FR (French)
EIGED306001EN (English) Electrical installation guide
Quantum using EcoStruxure™ Control Expert, TCP/IP Configuration, User
Manual
33002467 (English),
33002468 (French),
33002469 (German),
31008078 (Italian),
33002470 (Spanish),
31007110 (Chinese)
Quantum using EcoStruxure™ Control Expert, Hardware Reference Manual 35010529 (English),
35010530 (French),
35010531 (German),
35013975 (Italian),
35010532 (Spanish),
35012184 (Chinese)
33002479 10/2019
15
16
Title of Documentation
Quantum using EcoStruxure™ Control Expert, Discrete and Analog I/O,
Reference Manual
Quantum using EcoStruxure™ Control Expert, Experts and Communication,
Reference Manual
Communication Services and Architectures, Reference Manual
Reference Number
35010516 (English),
35010517 (French),
35010518 (German),
35013970 (Italian),
35010519 (Spanish),
35012185 (Chinese)
35010574 (English),
35010575 (French),
35010576 (German),
35014012 (Italian),
35010577 (Spanish),
35012187 (Chinese)
35010500 (English),
35010501 (French),
35006176 (German),
35013966 (Italian),
35006177 (Spanish),
35012196 (Chinese)
31002087 Schneider Automation BOOTP Lite Ethernet IP Address Download Utility for
Schneider Automation Ethernet Products Instruction Sheet
FactoryCast for Quantum, Premium and Micro User Guide
Quantum using EcoStruxure™ Control Expert, Hot Standby System, User
Manual
31001229
35010533 (English),
35010534 (French),
35010535 (German),
35013993 (Italian),
35010536 (Spanish),
35012188 (Chinese)
Modbus Protocol Reference Guide
Open Modbus Specification
PI-MBUS-300 http://www.modbus.org/
FactoryCast HMI 1.7, Setup Manual, Premium and Quantum HMI Modules 35007632 (English),
35007634 (French),
35007633 (German),
35007635 (Spanish),
35007636 (Italian)
You can download these technical publications and other technical information from our website at https://www.schneider-electric.com/en/download
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Ethernet Products
33002479 10/2019
Modicon Quantum with Control Expert Ethernet Products
Part I
Modicon Quantum with Control Expert Ethernet Products
Purpose
This part introduces the Modicon Quantum with Control Expert products used for Ethernet communication.
What Is in This Part?
This part contains the following chapters:
Chapter
1
2
Chapter Name
Product Description
Ethernet Communication Services
Page
33002479 10/2019
17
Ethernet Products
18
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Product Description
33002479 10/2019
Product Description
Chapter 1
Product Description
Overview
This chapter includes product overviews for:
the 140 NOE 771 xx modules
the 140 NWM 100 00 module the built-in Ethernet port of the 140 CPU 651 x0 modules
When inserted in the backplane, these modules allow your Quantum PLC to communicate over
Ethernet networks.
What Is in This Chapter?
This chapter contains the following sections:
Section
1.1
1.2
1.3
1.4
Topic
Module Description 140 CPU 651 x0
Module Description 140 NOE 771 xx and 140 NWM 100 00
Installing the Module
Customer Support
Page
33002479 10/2019
19
Product Description
Module Description 140 CPU 651 x0
Section 1.1
Module Description 140 CPU 651 x0
Overview
This is a discussion of the the Modicon Quantum High-End CPU (HE CPU) (140 CPU 651 x 0).
What Is in This Section?
This section contains the following topics:
Topic
140 CPU 651 x0 Product Overview
Physical Presentation and Mounting of Standard High End Modules
CPU Controls and Displays
Indicators
Using the CPU LCD Display Screens
Page
20
33002479 10/2019
Product Description
140 CPU 651 x0 Product Overview
General Description
The Quantum-140 CPU 651 x0 module
processor modules. It combines standard PLC functions with the diagnostic possibilities of a Web server. The 140 CPU 651 x
see page 22
) is among the newest in a series of Quantum
0 communicates using an RJ45 connection.
The 140 CPU 651 configure services.
x 0 module is in a double-width standard Quantum housing, which requires 2 sequential slots in a Quantum rack. Its server functions are diagnostic only, so use software to
The table shows the key Ethernet services that are implemented:
Service
FTP Server
Flash File System
Address Server
SNMP V2 Agent (Network Management Service)
Modbus Messaging ( see page 79 )
Hot Standby
Global Data (Publish/Subscribe)
Bandwidth Monitoring
Fast Device Replacement (Server) ( see page 237 )
Enhanced Web Diagnosis ( see page 88 )
Schneider Private MIB
FactoryCast Application
User-programmed Web pages
RJ45 Connection, see Modbus port in the Quantum Platform manual.
Fiber Optic Connection
Time Synchronization Service
Electronic Mail Notification Service ( see page 85 )
x x x x x x x x x x x
140 CPU 651 x0 x x x
X
33002479 10/2019
21
Product Description
Physical Presentation and Mounting of Standard High End Modules
Illustration
The figure shows a standard High End module and its components.
22
1 model number, module description, color code
2 lens cover (open)
3 LCD display (here covered by the lens cover)
4 key switch
5 keypad (with 2 red LED indicators)
6 modbus port (RS-232) (RS-485)
7 USB port
8 Modbus Plus port
9 PCMCIA slot A (depends on CPU reference)
10 PCMCIA slot B
11 LED indicators (yellow) for Ethernet communication
12 Ethernet port
13 battery (user installed)
14 reset button
15 2 screws
NOTE: Quantum High End processors are equipped with one PCMCIA slot (B) or two PCMCIA slots (A and B) in which to install Schneider PCMCIA cards (other cards are not accepted).
33002479 10/2019
Mounting
Mounting the module onto the central back plane:
Product Description
1 Hang the module.
2 Screw the module to the back plane.
33002479 10/2019
23
Product Description
CPU Controls and Displays
Lens Cover
The protective lens cover (2 on the CPU front panel (see Quantum using EcoStruxure™ Control
Expert, Hot Standby System, User Manual) ) can be opened by sliding it upwards.
With the lens cover open you have access to the following items:
key switch
battery reset button
Key Switch
The key switch (4) is a security feature and a memory protection switch. The key switch has two positions: locked and unlocked. The key switch is only read and deciphered by the PLC OS portion of the firmware and not by the OS loader portion.
The Quantum processors have a set of system menus that enable the operator to:
perform PLC operations (i.e., start PLC, stop PLC)
display module parameters (i.e., communications parameters) switch to the maintenance mode (in Safety processors)
The key positions are shown in the table below:
Key Position unlocked:
PLC Operation
System menu operations can be invoked and module parameters can be modified by the operator with the LCD and keypad.
Memory protection is OFF.
You can switch to Maintenance mode (in Safety processors).
locked:
No system menu operations can be invoked and module parameters are read-only.
Memory protection is ON.
Safe mode forced (in Safety processors).
Switching the key switch position from locked to unlocked or vice versa turns on the LCD's backlight.
NOTE: For more explanations about Maintenance and Safe modes, refer to the Modicon Quantum,
Quantum Safety PLC, Safety Reference Manual .
24
33002479 10/2019
Product Description
Key Switch Description Tables
The following table provides information on switch position for high end Quantum 140 CPU 6•• ••• with firmware < 3.12:
Operation
Programming mode
Monitoring mode
Upload application
Download, online modification
Stop/Run/Init commands from Control Expert
Switch Position
Unlocked
Allowed
Allowed
Allowed
Allowed
Allowed
Locked
Allowed
Allowed
Allowed
Forbidden
Allowed
Unity Pro is the former name of Control Expert for version 13.1 or earlier.
The following table provides information on switch position for high end Quantum 140 CPU 6•• ••• with firmware ≥ 3.12 and Unity Pro < V8:
Operation
Programming mode
Monitoring mode
Upload application
Download, online modification
Stop/Run/Init commands from Unity Pro
Switch Position
Unlocked
Allowed
Allowed
Allowed
Allowed
Allowed
Locked
Forbidden
Allowed
Forbidden
Forbidden
Forbidden
Unity Pro is the former name of Control Expert for version 13.1 or earlier.
The following table provides information on switch position for high end Quantum 140 CPU 6•• ••• with firmware ≥ 3.2 and Unity Pro ≥ V8:
Operation
Programming mode
Monitoring mode
Upload application
Download, online modification
Switch Position
Unlocked
Allowed (1)
Allowed
(1)
Allowed
(1)
Allowed (1)
Locked
Forbidden
Allowed
(1)
Forbidden
Forbidden
Stop/Run/Init commands from Control
Expert/UnityPro
Allowed (1) Forbidden
(1) : Password-protected if a password has been defined in the Control Expert/Unity Pro application
33002479 10/2019
25
Product Description
Reset Button
Pressing the reset button (12) forces a cold start of the PLC.
LCD Display
The liquid crystal display (LCD - 3) has 2 lines with 16 characters each with changeable backlight state and contrast:
The backlight handling is entirely automated to save the life of the LCDs. The backlight turns on when one of the following occurs:
a key is pressed the key switch state is changed an error message is displayed on the LCD
The backlight stays on for error messages as long as the error message is displayed otherwise, the backlight automatically turns off after five minutes.
Adjusting the Contrast
The contrast is adjustable from the keypad when the default screen is displayed:
Step
1
Action
Press the MOD key:
2 To adjust the contrast darker press:
3 To adjust the contrast lighter press:
4 To confirm the setting press:
26
33002479 10/2019
Product Description
Keypad
The keypad (5) has five keys that are mapped to hardware addresses. Each of the two arrow keys includes an LED:
1 5 keys
2 2 LEDs
Using the Keys
Keypad functions:
Key Function
To cancel an entry, suspend or stop an action in progress
To display the preceding screens successively (move up the menu tree)
To confirm a selection or an entry
To set a field on the display into the modify mode
LED: on
LED: flashing
LED: off
LED on
LED flashing
LED off
Key active:
to scroll through menu options
to scroll through modify mode field options
Key active: The modify mode field can be scrolled.
Key inactive: No menu options and no field options.
Key active:
to move around in a screen, field to field
to go to the sub-menu
Key active: Used to move digit to digit in a modify mode field.
Key inactive, there is no:
sub-menu for menu option
scrolling around a screen scrolling around a field
33002479 10/2019
27
Product Description
Indicators
Overview
The High End processors use two types of indicators:
1. LCD display: The Default Screen (
see page 31
serves as a Controller status screen.
2. LED Indicators: The functionality of the LEDs is described in a table after the figure.
The following figure shows the two types of indicators.
28
1 LCD Display (lens cover closed)
2 LED Indicators
33002479 10/2019
Product Description
LED Description
The following table shows the description for the LED indicators of the different High End CPU modules.
LEDs
COM
(yellow)
STS
(yellow)
Indication
Standard Processors 140 CPU 65• •0 /
140 CPU 651 60S
Controlled by the Coprocessor hardware
Indicates Ethernet activity
Controlled by the Coprocessor software
ON Normal
OFF Copro auto tests unsuccessful. Possible hardware problem.
Flashing:
1 Flash
2 Flashes
3 Flashes
4 Flashes
Configuration in progress.
Temporary situation.
Invalid MAC address
Link not connected
5 Flashes
6 Flashes
7 Flashes
Duplicate IP Address.
Module is set to its default IP address.
Waiting for IP address from address server
Invalid IP address.
Module is set to its default IP address.
Firmware incompatibility between PLC OS and
Copro firmware
Hot StandBy Processors 140 CPU 67• 6• /
140 CPU 671 60S
Controlled by the Coprocessor hardware
Indicates Primary or Standby activity
Controlled by the Coprocessor firmware
Blinking: system is redundant and data
are exchanged from the Primary to
Standby controller
ON: system not redundant / Copro booting from power-on to end of self-
tests
OFF: Copro auto tests were not successfull
33002479 10/2019
29
Product Description
Using the CPU LCD Display Screens
Introduction
The controller LCD displays messages. These messages indicate the controller status. There are four levels of menus and submenus. Use the keypad access the menus.
see page 27
on the front of the controller to
For detailed information about the menus and submenus see:
PLC Operations Menus and Submenus (
see page 33
Using the Communications Menus and Submenus
Using the LCD Settings Menus and Submenus
Using the System Info Menus and Submenus (
see page 36
see page 39
see page 40
Structure: LCD display menus and submenus:
30
1 default screen
2 system menus
3 sub menus
4 sub screens
33002479 10/2019
Product Description
Accessing the Screens
Use the keys on the keypad to access the system menus and submenus:
Step
1
Action
To access the screens, confirm that the key switch is in the unlocked position.
2 To step down to a lower menu, operate one of the following keys:
3 To return to the previous menu, press:
140 CPU 65• •• Default Screen
The default screen is read-only and contains the following fields:
The default screen displays the following information:
Field
0
2
CPU mode
CPU state
Display
M
S
RUN
STOP
No Conf
Halt
Description maintenance mode (only on safety processors) safe mode (only on safety processors)
Application program is running.
Application program is NOT running.
STOP offline
Processor has no application program.
detected state error (in maintenance mode for safety modules)
33002479 10/2019
31
Product Description
Field
BatL
Port
Display Description
Indicates battery health:
steady = Battery is low.
no message = Battery is OK.
USB
Modbus Plus MB+ mb+
Dup
Modbus
PCM
ERR
INI
232
485
Indicates that the port has activity.
Indicates Modbus Plus activity.
no activity duplicate MB+ address detected Modbus communications error initial network search serial port activity for RS-232 serial port activity for RS-485
1
2
Displayed status indicates battery health of the PCMCIA card in slot 1:
steady = Battery is OK.
flashing = Battery is low (only for green PCMCIAs
(version <04)) (1) .
Displayed status indicates battery health of the PCMCIA card in slot 2:
steady = Battery is OK.
flashing = Battery is low (only for green PCMCIAs
(version < 04)) (1) .
(1) With blue PCMCIAs (version >= 04), when main battery is low, there is no flash.
32
33002479 10/2019
PLC Operations Menu
The structure of the PLC Operations menu and submenus are:
Product Description
33002479 10/2019
33
Product Description
Submenu for PLC Operations: Start, Stop and Init:
Start, Stop, Init
Screens Display
Start PLC
Stop PLC
Init PLC
Fields Available
Press <ENTER> to confirm Start.
Press <ENTER> to confirm Stop.
Press <ENTER> to confirm Init.
Description
Pressing <ENTER> starts the controller.
Pressing <ENTER> stops the controller.
Pressing <ENTER> initializes the controller.
On safety processors, this command is only available in the maintenance mode.
Submenu for PLC Operations Hot Standby CPU:
Screen
Hot Standby
State:
Hot Standby
Mode:
Hot Standby
Order:
Field
State read-only
Mode
(modifiable only if the key switch is in the unlocked position)
A or B
(modifiable only if the key switch is in the unlocked position)
Option
PRIMARY CPU
STANDBY CPU
Offline
RUN
Description
Controller serves as primary unit.
Controller serves as standby unit.
Controller is neither primary nor standby unit.
STS steady Controller is active and is either serving as primary PLC or able to take over the primary PLC role if needed.
STS flashing
Controller is transferring/updating. When the transfer is done, RUN stays on steady.
OFFLINE
FIRST
SECOND
STS steady Controller is taken out of service without stopping it or disconnecting it from power.
If the controller is the primary PLC when the mode is changed to offline, control switches to the standby PLC.
If the standby PLC changes to offline, the primary PLC continues to operate without a backup.
STS flashing
Controller is transferring/updating.When the transfer is done, OFFLINE stays on steady.
Hot Standby power order
NOTE: To change the A/B order, confirm that the PLC is in STOP mode.
34
33002479 10/2019
Product Description
Screen
Hot Standby
Transfer:
Hot Standby
Diag:
Field Option
-
(This menu option is enabled only when the key switch is in the unlocked position.)
Description
Pressing the <ENTER> key confirms the transfer. The transfer initiates the request of a program update from the primary PLC. Pressing any other key cancels the transfer initiation and returns to the Hot Standby
Transfer menu option screen.
NOTE: Transfer by keypad is based on %SW60.5
(see Unity Pro, Program Languages and Structure,
Reference Manual ) use: modifying %SW60.5 by application and requiring simultaneously a transfer by
Keypad, could lead to some issues (no transfer or transfer retry).
The order of diagnostic screen varies with the operation.
Halt
RIO fails user task in halt mode detected error reported by RIO head
HSBY fails
Stop
Off keypad
Off %SW60 detected error reported by optical link stop command sent offline command entered on keypad offline command set in command register
Off appli
Off vers
Off RIO
Take over
Run
Plug & Run
Power up offline due to application mismatch offline due to PLC or co-processor OS mismatch offline due to detectedRIO error standby CPU switched to primary CPU mode run command sent sun-link operational and standby CPU started no message: PLC just started
33002479 10/2019
35
Product Description
Communications Menu
Communications menu and submenus:
36
33002479 10/2019
Product Description
Submenu for TCP/IP Ethernet PLC Communications submenus:
TCP/IP Ethernet Screen
Displays
TCP/IP Ethernet IP
Address 1,2
TCP/IP Ethernet Subnet
Mask 1,2
TCP/IP Ethernet IP
Gateway
1,2
TCP/IP Ethernet MAC
Address
Fields Available
###.###.###.###
###.###.###.###
###.###.###.###
##.##.##.##.##.##
(read-only)
Options Available decimal numbers decimal numbers decimal numbers hexadecimal numbers
Description
Displays IP address.
Displays subnetwork mask address.
Displays Ethernet IP gateway address.
Displays MAC address.
1) Parameters can be modified only if no applications have been downloaded (in NO CONF state).
2) When a new PLC application has been downloaded, the Ethernet address on the screen is updated only after accessing the highest level of the menu structure.
Modbus Plus PLC Communications submenus:
Fields Available
##
(modifiable only if the key switch is in the unlocked position)
Modbus Plus State
Options Available
1-64
Description
Enter a valid Modbus Plus address.
Modbus Plus state Monitor Link
Normal Link
Sole Station
Duplicate Address
No Token
33002479 10/2019
37
Product Description
Serial PLC Communications submenus:
Fields Available*
Mode
Protocol
Adr
Rate
Par
DB
Options Available
232
485
ASCII
RTU
1 - 247 for Modbus Switchover
Primary CPU 1-119
Standby CPU 129 - 247
50, 75, 110, 134.5, 150, 300, 600, 1200, 1800,
2400, 3600. 4800, 7200, 9600, 19200 bits/s
NONE
ODD
EVEN
7,8
SB 1,2
*If the key switch is in the unlocked position, fields are modifiable.
Description
RS mode protocols available unit address baud rate parity data bits: If protocol is Modbus, then RTU-8 or ASCII-7.
stop bits
38
33002479 10/2019
System Info Menu
Structure of System Info menus and submenus:
Product Description
System Info, PLC Communications submenus:
System Info Screen
Displays
Stop Code
Fields Available* Option Available Description
Firmware Info
Hardware Info
Copro Info
*Fields are read-only.
####
Description
Rev.Ldr: ##.##
OS: ##.##-##-##
HW Rev: ####
##-IE-## machine stop code description of the machine stop code
OS revision
OSLoader revision hardware revision co-processor revision
33002479 10/2019
39
Product Description
LCD Settings Menu
LCD Settings menus and submenus:
40
LCD Contrast settings submenu:
LCD Screen Contrast
Screen Displays
LCD Contrast:
Fields Available
####
Description
Use the arrow keys to adjust the setting:
Up arrow increases percent (brighter).
Right arrow decreases percent (darker).
LCD Light setting submenus:
Screen Displays
LCD Light:
Fields Available
On
Off
1 Min
5 Min
10 Min
15 Min
Description
LCD remains on permanently or until changed.
LCD remains off permanently or until changed.
LCD remains on for 1 minute.
LCD remains on for 5 minutes.
LCD remains on for 10 minutes.
LCD remains on for 15 minutes.
33002479 10/2019
Product Description
Module Description 140 NOE 771 xx and 140 NWM 100 00
Section 1.2
Module Description 140 NOE 771 xx and 140 NWM 100 00
Overview
This section contains the module descriptions for 140 NOE 771 xx and 140 NWM 100 00.
What Is in This Section?
This section contains the following topics:
Topic
Modicon Quantum Ethernet Modules Overview
Indicators for Ethernet Modules
Connectors and Cabling
Using the 140 NOE 771 11 Ethernet Module in a Quantum Safety Project
Page
33002479 10/2019
41
Product Description
Modicon Quantum Ethernet Modules Overview
Overview
The following information provides overviews of all Modicon Quantum Ethernet modules.
General Description
The Modicon Quantum Ethernet module, shown below, is one of the latest models in a line of
Modicon Quantum Ethernet TCP/IP modules designed to make it possible for a Modicon Quantum
PLC to communicate with devices over an Ethernet network. The electronics for the Ethernet modules are contained in a standard Modicon Quantum single-width case that takes up one slot in a Modicon Quantum backplane. The module, which is capable of being hot swapped, can be plugged into any available slot in the backplane.
The NOE 771 x 0 and NOE 771 x 1 modules provide real-time peer-to-peer communications and
I/O scanning and a Modbus/TCP server. The included HTTP services provide maintenance and configuration utilities to the module.
42
33002479 10/2019
Product Description
Front View
The following figure shows the front of the NOE 771 00 Ethernet module as an example for all
Ethernet modules.
1 model number, module description, color code
2 LED display
3 IP Address writable area
4 Global address label
5 100 BASE-FX MT-RJ cable connector
6 10/100 BASE-T RJ45 cable connector
7 removable door
33002479 10/2019
43
Product Description
Key Ethernet Services
The key Ethernet services of the 140 NOE 771 (-00, -01, -10, -11) and 140 NWM 100 00 models are listed below:
Service
FTP Server
Flash File System
Address Server
SNMP V2 Agent (Network Management Service)
Modbus Messaging ( see page 79 )
Hot Standby
Global Data (Publish/Subscribe)
Bandwidth Monitoring
Fast Device Replacement (Server) ( see page 237 )
Enhanced Web Diagnosis ( see page 88 )
Schneider Private MIB
FactoryCast Application
User-programmed Web pages
JAVA Virtual Machine
Fiber optic connection
RJ45 connection
Time Synchronization Service
Electronic Mail Notification Service ( see page 85 )
X
X
X
X
X
X
X
X
X
-00
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-01
X
X
X
X
X
X
X
X
X
X
X
-10
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
-11
X
X
X
X
X
X
X
X
NWM
X
X
X
X
NOTE: In the detailed description of the key features, only modules in the NOE family are named.
The features are also available for the 140 NWM 100 00 module, depending on the listed properties in the above table.
NOTE: In Control Expert software, the 140 NWM 100 00 module is set in the TCP/IP Regular
Network family, although it belongs to the TCP/IP FactoryCast network family. So, the services listed above (I/O scanning, Global Data, address server, Bandwidth monitoring) are not supported by the module. However, they can be selected in the TCP/IP regular network configuration in
Control Expert. (Even if they are configured, those services won't work with the module.)
44
33002479 10/2019
Product Description
Maximum Number of Networks Per CPU
The following table summarizes the maximum number of networks per CPU, where "networks" means the sum of NOE, Modbus+ and any other communication modules:
Modicon Quantum CPU Type
140 CPU 311 10
140 CPU 434 12A
140 CPU 534 14A
140 CPU 651 50
140 CPU 651 50
140 CPU 652 60
140 CPU 658 60
140 CPU 670 60
140 CPU 671 60
140 CPU 672 60
140 CPU 672 61
140 CPU 678 61
6
6
3
6
6
6
6
6
6
6
6
Supported Number of Networks
2
Front Panel Components
The front panel of the Ethernet modules contains identification markings, color codes, and LED displays. A writable area for an IP address, a global address label, and two Ethernet cable connectors is located behind the removable front panel door.
The following table provides a description of the front panel components that are shown in following figure:
Component
LED Indicator Panel
IP Address Area
Global Address Label
100 BASE-FX Connector
10/100 BASE-T Connector
Description
Indicates the operating status of the module, and the fiber optic or Ethernet communications network to which it is connected.
Provides a writable area to record the module’s assigned IP address.
Indicates the module’s global Ethernet MAC address assigned at the factory.
Provides an MT-RJ socket for connection to a 100-megabit fiber-optic Ethernet cable.
Provides an RJ45 socket for connection to a shielded, twisted pair Ethernet cable.
33002479 10/2019
45
Product Description
Indicators for Ethernet Modules
Illustration
The following figure shows the NOE 771 00 LED indicators as a placeholder for all other Ethernet modules:
Description
The following table shows the LED descriptions:
LED
Active
Ready
Fault
Run
Coll.
Link
Tx Act
Rx Act
10MB
100MB
Fduplex
Kernel
Appl
Color
Green
Green
Red
Green
Red
Green
Green
Green
Green
Green
Amber
Green
Description
Indicates the backplane is configured.
Indicates module is healthy.
Flashes when the NOE is in crash state.
Flashes to indicate diagnostic code, as described below.
Flashes when Ethernet collisions occur.
On when Ethernet link is active.
Flashes to indicate Ethernet transmission.
Flashes to indicate Ethernet reception.
On when the module is connected to a 10-Megabit network.
On when the module is connected to a 100-Megabit network.
On when Ethernet is operating in the full duplex mode.
On when in Kernel Mode.
Flashing while in download mode.
On when crash log entry exists.
46
33002479 10/2019
Product Description
Run LED Status
The following table lists each available state of the Run LED indicator and provides diagnostic information for that state in both the 140 NOE 771x1 module and the 140 NWM 100 module.
7
8
9
Indicator State
On (steady)
2
3
Number of flashes in sequence
1 Not used
Not used
No Link: the network cable is not connected or is defective
4
5
Status for 140NOE771x1
Normal operation: The NOE module is ready for network communication.
Duplicate IP address: The module will be set to its default IP address.
No IP address: The module is attempting to obtain an IP address from a BOOTP server. Module is set to its default IP address.
6
-
Invalid IP configuration. (Likely cause: Default gateway is not on the same subnet mask.) Module is set to its default IP address.
No valid executive NOE present
Not used
Status for 140NWM100
Normal operation: The NOE module is ready for network communication.
Not used
Not used
No Link: the network cable is not connected or is defective
Duplicate IP address: The module will stay off-line.
No IP address: The module is attempting to obtain an IP address from a BOOTP server.
Using default IP address
No valid executive NOE present
Not used
Flash file system inoperative.
33002479 10/2019
47
Product Description
Connectors and Cabling
Overview
The following information describes the 10/100 BASE-T and 100 BASE-FX connectors.
10/100 BASE-T Twisted Pair Connector
The NOE 771 xx , NWM 100 00, and CPU 651 below) is a standard RJ-45 twisted pair socket: x 0 modules’ 10/100 BASE-T connector (shown
Schneider Electric recommends that you use Category 5 STP cabling, which is rated to 100 Mbps, with an RJ-45 connector.
The eight pins are arranged vertically and numbered in order from the bottom to the top. The RJ-
45 pinout used by this module is:
Receive Data (+) 3
Receive Data (-) 6
Transmit Data (+) 1
Transmit Data (-) 2
100 BASE-FX
The 100 BASE-FX connector for the NOE 771 xx , NWM 100 00, and CPU 651 60 modules is an
MT-RJ socket or a mating fiber optic cable connector.
For the NOE 771 xx and NWM 100 00, you may need an MT-RJ to SC (duplex) multimode fiber optic cable assembly 62.5/125mm. Schneider Electric recommends cable number 490NOC00005 to connect to fiber hubs/switches.
NOTE: The NOE 771 the same time.
xx and NWM 100 00 are one-channel devices that can communicate over either 10/100 BASE-T or 100 BASE-FX Ethernet networks at any given time, but not over both at
48
33002479 10/2019
Product Description
Using the 140 NOE 771 11 Ethernet Module in a Quantum Safety Project
Overview
Version 4.2 and higher of the 140 NOE 771 11 Ethernet module can be included in one of the following:
Quantum safety applications non-safety applications
A Quantum safety application is controlled by a Quantum safety PLC, consisting exclusively of safety modules that perform safety functions. A safety module is denoted by the letter of its module name.
S at the end
When used in a Quantum safety application, the 140 NOE 771 11 is a does not negatively affect the execution of the PLC’s safety functions.
non-interfering module –it
For more information about Quantum safety products, refer to the Quantum Safety PLC Safety
Manual .
Restricted and Unrestricted Memory Areas
The memory addresses of a Quantum safety PLC can be configured as one of the following:
safety-restricted memory areas
unrestricted memory areas
Only safety modules can write data to a safety-restricted memory area. For more information about restricted versus unrestricted memory areas, refer to the topic Safety PLC Write Protection in the
Unity Pro XLS Operating Mode Manual .
The 140 NOE 771 11 Ethernet module–as a non-interfering module–cannot write data to safetyrestricted memory areas. Instead, the 140 NOE 771 11 Ethernet module can write data only to unrestricted memory areas.
The memory areas of a Quantum safety project are user-configurable. Using Control Expert, you can designate address ranges as either safety-restricted or unrestricted. For instructions on how to configure memory areas, refer to the topic Configuration of Quantum Processors with Unity Pro
XLS in the Unity Pro XLS Operating Mode Manual .
33002479 10/2019
49
Product Description
Health Bit Assignments
CAUTION
RISK OF DATA LOSS
The default address assignments for the following data blocks overlap:
Global Data Health Bit block (%MW1)
I/O Scanning Health Bit block (%MW1)
I/O Scanning Device Control block (%MD1)
You must edit these address assignments so they do not overlap. If these address assignments overlap, the PLC will overwrite data and the overwritten data will be lost.
Failure to follow these instructions can result in injury or equipment damage.
The 140 NOE 771 11 makes different address assignments–regarding both I/O Scanning and
Global Data Health Bit Blocks–for safety and non-safety applications, as follows:
Health Bit Block
I/O Scanning
Non-Safety Application Addresses Safety Application Addresses
%I
%IW
%M 1
%MW 1
Global Data %I
%IW
%MW
%MW
1
(only)
1
All I/O Scanning and Global Data Health Bit Block address assignments, for a Quantum safety application, must be made in unrestricted memory address areas.
50
33002479 10/2019
Product Description
Installing the Module
Section 1.3
Installing the Module
Introduction
This section contains installation and configuration information for the NOE 771 modules.
xx Ethernet
What Is in This Section?
This section contains the following topics:
Topic
Before You Begin
Cable Schemes
Security
Mounting the Module in the Quantum PLC Backplane
Connecting the Cable
Assigning Ethernet Address Parameters
Establishing the FTP Password
Establishing HTTP and Write Passwords for NOE
Using BOOTP Lite to Assign Address Parameters
Page
33002479 10/2019
51
Product Description
Before You Begin
Initial Checks
CAUTION
UNINTENTIONAL OPERATION
If you do not enter the correct address pairs into the BOOTP server, you could communicate to the wrong device.
Confirm that the MAC address matches the intended IP address in your BOOTP server.
Having two or more devices with the same IP address may cause unpredictable operation of your network.
Confirm that your Ethernet module receives a unique IP address.
Failure to follow these instructions can result in injury or equipment damage.
Complete the following checks before installing the module.
Determine how the module is assigned its Ethernet address parameters. The default method is
BOOTP.
Verify that your Ethernet network is properly constructed.
Verify that you are using the proper cabling scheme
see page 54
Determine the Appropriate Ethernet Address Parameters
The module obtains Ethernet address parameters in one of the following ways. Consult your system administrator to determine which method is suitable.
Configure new IP, gateway, and subnet mask addresses.
— or —
The module obtains its Ethernet address parameters from a BOOTP server.
If the administrator assigns new address parameters, configure the module through the Control
Expert interface module configuration screen.
52
33002479 10/2019
Product Description
Verify the Network Topology
Schneider Electric recommends that you connect an NOE module to another NOE module or other device through a hub or a switch (as shown in the following correct network topology graphic).
The following figure shows two incorrect network topologies.
The following figure shows a correct network topology.
33002479 10/2019
53
Product Description
Cable Schemes
Overview
The following information provides guidelines on proper cabling schemes for your Ethernet configuration.
Twisted Pair Length
In a standard Ethernet cabling scheme network nodes such as the Quantum Ethernet module connect via a cable to a port on a central hub or switch. The maximum cable length between nodes depends on whether they are connected through hubs or switches, as the following table describes:
Device Type hub switch
Max. Cable Length from
Node to Hub/Switch
10 BASE-T: 100 m
10/100 BASE-T: 100 m
100 BASE-FX: 2 km
Max. Number of Hubs/Switches
Between Any Two Nodes
3 unlimited
Max. Distance Between Network
Nodes
500 m unlimited
Cabling with Conventional Hubs
The figures and tables that follow show the maximum number of hubs and the maximum cable length between nodes allowed if using hubs.
10BASE-T Distances with Hubs
The 10 BASE-T cabling allows for 3 hubs with a link maximum distance of 100 m (325 ft) and a total network diameter of 500 m (1625 ft).
54
33002479 10/2019
Product Description
10/100BASE-T Cable Distances with Switches
The 10/100BASE-T cabling has a link maximum distance of 100 m. The is no limit on the number of switches.
100BASE-FX
The maximum cable segment length for 100BASE-FX multimode cable (1300 nm) is 2 km. The number of switches you can implement over that distance is unlimited.
33002479 10/2019
55
Product Description
Security
Overview
The following information describes firewalls. A firewall is a gateway that controls access to your network. To restrict access to your Ethernet controller and I/O network, you may want to consider a firewall.
Types of Firewalls
There are network-level and application-level firewalls:
Network-level firewalls: These firewalls are frequently installed between the Internet and a
single point of entry to an internal, protected network.
Application-level firewalls: An application-level firewall acts on behalf of an application. It intercepts all traffic destined for that application and decides whether to forward that traffic to the application. Application-level firewalls reside on individual host computers.
Port Numbers Used by NOE
The following table contains the port numbers used by NOE:
Protocol
Modbus/TCP
HTTP
SNMP
FTP
Port Number
TCP 502
TCP 80
UDP 61
TCP 21
You may need to provide the information in this table to your system administrator so that the firewall configuration will allow access to your PLC from outside of your facility.
56
33002479 10/2019
Product Description
Mounting the Module in the Quantum PLC Backplane
Before you Begin
Locate the backplane in which you will mount the module. Ensure that an open slot is available.
NOTE: The module can be installed only in a local backplane.
NOTE: Ensure when installing the module that it does not exceed the Quantum backplane power requirements as specified in Quantum using EcoStruxure™ Control Expert, Hardware Reference
Manual .
Backplane Slot Replacement
You may place the module in any slot on the backplane. You do not need to place it next to other modules.
Tools Required
You will need one medium-size, Phillips-head screw driver.
Mounting the Module in the Backplane
Perform the following steps to mount the module.
Step
1
Action
Holding the module at an angle, mount it on the two hooks located near the top of the backplane. The following figure shows the correct way to hold the module.
33002479 10/2019
2
3
Swing the module down so its connector engages the backplane connector.
Using a Phillips-head screw driver, tighten the screw at the bottom of the module between 2 and 4 in-lbs or between .22 and .45 Newton meters of torque.
57
Product Description
Grounding the Module
The module is grounded upon installation in the Quantum PLC backplane. For instructions on grounding the backplane, see Quantum using EcoStruxure™ Control Expert, Hardware Reference
Manual .
NOTE: If you connect the module to the Ethernet hub or switch using a shielded cable, the cable is also grounded. Elsewhere in this guide is a discussion of cabling schemes and recommen dations Cabling Schemes
see page 54
Ethernet network Connecting the Cable
, as well as instructions for connecting the module to an
see page 59
58
33002479 10/2019
Product Description
Connecting the Cable
Overview
The following information pertains to cabling.
NOTE: The 140 NOE 771 xx is capable of communicating over either a 10/100BASE-T or a
100BASE-FX Ethernet network at any given time, but not both at the same time.
Accessories
Schneider Electric sells the following switches:
Hub or Switch
499NEH10410
499NOH10510
499NTR10010
499NEH14100
499NTR10100
499NES18100
499NES17100
499NOS17100
Description hub with 4 ports 10 BASE-T hub with 3 ports 10 BASE-T and 2 ports 10 BASE-FL transceiver 10 BASE-T/10 BASE-FL hub with 4 ports 100 BASE-TX transceiver 100 BASE-TX switch with 8 ports 10/100 BASE-TX managed switch with 7 ports 10/100 BASE-TX managed switch with 5 ports 10/100 BASE-TX and 2 ports
100 BASE-FX
The following Schneider Electric cables support multicast filtering (
see page 190
Cable
490NTW000 02/05/12/40/80 U
490NTC000 05/15/40/80 U
Description
StraightThru cable
Crossover cable
Fiber Optic
Remove the protective cap from the module’s MT-RJ connector port and the protective cap from the tip of the black connector on the MT-RJ fiber optic cable (as shown in the following figure). The plug only fits to the socket in one way. It should snap into place.
33002479 10/2019
59
Product Description
Assigning Ethernet Address Parameters
Overview
CAUTION
UNINTENTIONAL OPERATION
If you do not enter the correct address pairs into the BOOTP server, you could communicate to the wrong device.
Ensure that the MAC address matches the intended IP address in your BOOTP server.
Having two or more devices with the same IP address can cause unpredictable operation of your network.
Ensure that your Ethernet module receives a unique IP address.
Failure to follow these instructions can result in injury or equipment damage.
The following information describes how to assign IP address parameters.
As shipped from the factory, the 140 NOE 771 xx module does not contain an IP address. If you have not programmed the unit with an Ethernet configuration extension, the module does not contain an IP address. When the module starts up without an IP address, the module will attempt to obtain an IP address from the network’s BOOTP server.
You can assign IP address parameters using the BOOTP Lite software utility.
NOTE: You can configure the IP address using Web pages on the modules 140 NOE 771 01, -11, and NWM 100 00.
Using a BOOTP Server
A BOOTP server is a program that manages the IP addresses assigned to devices on the network.
Your system administrator can confirm whether a BOOTP server exists on your network and can help you use the server to maintain the adapter’s IP address.
See Using BOOTP Lite to Assign Address Parameters,
page 69
.
How an Unconfigured Module Obtains an IP Address
On startup, an unconfigured NOE 771 xx module ("as shipped") will attempt to obtain an IP address by issuing BOOTP requests. When a response from a BOOTP server is obtained, the IP address in the response is used. If no BOOTP response is received within two minutes, the module uses the default IP address derived from its MAC address.
NOTE: The MAC address is assigned at the factory and is recorded on a label on the front panel, above the cable connector. This is a unique 48-bit global assigned address. It is set in PROM. The
Ethernet address is recorded on the label in hexadecimal, in the form 00.00.54.
xx .
xx .
xx .
60
33002479 10/2019
Product Description
Connecting to the Default IP Address
To connect to the default IP address with your PC, set up an active route from your PC. To do this with Windows 95/98/ME/NT/2000 or Windows XP, use the following procedure. You can use the routes for connecting Ethernet components with other address ranges.
Step
1
2
3
4
5
Action
Be sure the NOE module is running.
Obtain the default IP address of the NOE derived from its MAC address (for example,
84.0.0.2).
Open an MS-DOS window.
Add an active route for the local NOE by typing:
C:\>ROUTE ADD <target> MASK <mask> <gateway> e.g.
C:\>ROUTE ADD 84.0.0.0 MASK 255.0.0.0 205.217.193.205
Use the default IP address of the NOE module as target address. Use a class A subnet mask for connecting to every 84.0.0.0 address. The gateway address is the IP of your
PC. The result is that MS Windows will now talk to any address that starts with an 84 that is directly connected to a hub or switch directly accessible to your machine, or that can be seen by the specified route/gateway.
Confirm that there is a new entry in the active route table by typing:
C:\>route print :
The following figure confirms that the new entry was added to the active route table.
6 Verify that a connection is made by typing:
C:\>ping 84.0.0.2
The following figure shows that the connection is verified.
Specifying Address Parameters
Consult your system administrator to obtain a valid IP address and an appropriate gateway and a subnet mask, if required. Then use your programming panel to make the appropriate changes.
33002479 10/2019
61
Product Description
BOOTP Server Responds
If the server responds with address parameters, the NOE 771 as long as power remains applied to the module.
xx module will use those parameters
If the server does not respond, the module will retry its request for two minutes.
BOOTP Server Does Not Respond
If no BOOTP response is received, the NOE 771 xx module will use the default IP Address.
During this time the Run indicator displays a pattern of five flashes for a BOOTP attempt and six flashes for using the default IP.
NOE 771 xx Duplicate IP Address Test
In all cases, when the NOE 771 xx module receives an IP address, it will test for duplicate addresses by sending broadcast ARP requests three times at 5-second intervals.
If a Duplicate IP Address is found on the network, the NOE 771 detection.
xx will stay off-line to avoid a network disruption. It will display a pattern of four flashes to indicate a Duplicate IP Address
Automatic ARP
If there are no replies to its requests, the NOE 771 xx automatically sends three ARP requests at
2-second intervals to announce its presence on the network.
62
33002479 10/2019
Product Description
Establishing the FTP Password
Establishing the FTP Password
The FTP password is established using the Embedded Web Server. This topic contains information on how to access the web server for purposes of changing the FTP and HTTP passwords. The first thing the system administrator should do upon accessing the web server is change the FTP password. Doing this restricts access to the web server functionality to the system administrator.
Web server pages and their functionality are discussed in deatil in the chapter Embedded Web
Pages.
Introduction to Accessing the Web Server
Each Quantum NOE module contains an embedded Web server, which allows you to access diagnostics and online configurations for the module and its associated controller (PLC).
The web pages can only be viewed using Internet Explorer 4.0 or higher supporting JRE 1.4.2_04 or higher.
For information about the additional functionality provided by the FactoryCast system in the NOE modules, see the FactoryCast Manual .
How to Access the Web Server
Before you can access the module’s home page, you must enter the full IP address in the Address or Location box in the browser window. For example: address or DNS host name).
http://hostname ( hostname is the full IP
After you do this, the Schneider Electric Web Utility home page displays.
Schneider Web Utility Home Page
From the Quantum home page, you can access pages for:
changing the FTP password
information)
see page 64
see page 67
diagnostic and configuration information (the embedded Web pages chapter provides additional
33002479 10/2019
63
Product Description
Modifying the FTP Server Password
The following steps detail how to link to the correct web page for modifying the FTP password
Step Action
1 Enter the URL, for example, http://hostname/secure/embedded/ftp_passwd_config.htm
2 At that URL, supply a user name and password:
Note: The default User name is USER, and the default Password is USERUSER.
Both should be changed by the system administrator during module installation.
3 Upon supplying the user name, password, and clicking the OK button, the Modify
FTP Server User Name and Password page displays.
FTP Username and Password Modify Page Overview
The following figure shows the page used for modifying the FTP user name and password:
64
33002479 10/2019
Product Description
Change the Username and Password
At this point, the system administrator should change the Username and Password to restrict future access to the system. The following steps should be used.
2
3
Step
1
Action
Type in the new Username in the New User Name field.
Type in the new Password in the New Password field.
Click the Submit FTP Password Change button.
The following figure shows the message that is generated if you click on the Submit FTP Password
Change button:
Clicking the Reboot Device button will reset the username and password for the NOE board.
NOTE: The reboot requires about 40 seconds. (With large applications, reboot may require up to one (1) minute.)
During the reboot, all services provided by the NOE module are not available.
33002479 10/2019
65
Product Description
Establishing HTTP and Write Passwords for NOE
Overview
The following information describes how to set the passwords for HTTP and Data Monitor Write for the NOE.
Connect to the Web Page
Before you can change the HTTP or Data Monitor Write passwords, connect to the correct web page:
Step Action
1 Enter the URL, for example, http://hostname/secure/embedded/http_passwd_config.htm
2 At that URL, supply a user name and password in the dialog box. The size of the user name and password is a maximum of 16 characters in non-extended ASCII.
66
Note: The default User Name is USER, and the default Password is USER. Both should be changed by the system administrator during module installation.
3 Upon supplying the user name, password, and clicking the OK button, the Modify
Passwords page displays.
33002479 10/2019
Product Description
Modify Passwords Page
A single web page is used to modify both the HTTP and Data Monitor Write passwords:
33002479 10/2019
67
Product Description
Changing Security Access Parameters
A system administrator should change the default username (USER) and password (USER) to restrict future access to the system. After you decide whether you are changing the HTTP or Write
Password security parameters, follow the appropriate procedure below:
HTTP (Username and Password)
2
3
Step
1
4
Action
Type a new username in the New User Name field.
Type a new password in the New Password field.
Confirm the new password in the Confirm Password field.
Click the Change HTTP Access button.
Data Monitor Write (Password)
3
4
Step
1
2
Action
Type the old password in the Write Password field.
Type a new password in the New Password field.
Confirm the new password in the Confirm Password field.
Click the Change Write Password button.
Security Access Change Verification
The following figure shows the message that is generated if you click the Change HTTP Access or
Change Write Password button:
68
Clicking the Reboot Device button will reset the username and password for the NOE board.
NOTE: The Reboot will take about 40 seconds. Larger applications can take up to one (1) minute.
During the reboot all services provided by the NOE are not available.
33002479 10/2019
Product Description
Using BOOTP Lite to Assign Address Parameters
Overview
CAUTION
UNINTENTIONAL OPERATION
Ensure that the MAC address matches the intended IP address in your BOOTP server. If you do not enter the correct address pairs into the BOOTP server, you could communicate to the wrong device.
Failure to follow these instructions can result in injury or equipment damage.
The following information describes how to use the BOOTP Lite utility software.
BOOTP Lite Utility
Instead of a BOOTP server, Schneider Electric’s BOOTP Lite Server Software utility can be used to provide the IP address, subnet mask, and default gateway to the NOE 771 xx module.
Refer to the BOOTP Lite Server Software user documentation for instructions.
NOTE: BOOTP Lite Server Software and user documentation are available for download at www.modicon.com.
33002479 10/2019
69
Product Description
Customer Support
Section 1.4
Customer Support
Overview
This section tells you how to get customer support from Schneider Electric’s documentation and regional help centers.
What Is in This Section?
This section contains the following topics:
Topic
Customer Support Documentation
Contact Information
Page
70
33002479 10/2019
Product Description
Customer Support Documentation
Support Documentation
If you have any problems, please first consult the documentation listed above or the MS-Windows documentation.
For the most up-to-date NOE Ethernet controller information, please:
2
3
Step
1
4
Action
Access the Schneider Electric Web site.
Search technical information.
Select Quantum from the list of cross-product families.
Access either:
resolutions for resolutions to product issues
product manuals for the most recently published user documentation product announcements
33002479 10/2019
71
Product Description
Contact Information
Contact Information
Please find the nearest Schneider Electric sales office by visiting http://www.schneiderelectric.com. In the Select a country list, click the country closest to you for customer support.
72
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Ethernet Communication Services
33002479 10/2019
Ethernet Communication Services
Chapter 2
Ethernet Communication Services
Introduction
This chapter describes the Ethernet communications services available on 140 NOE 771
140 CPU 651 x 0.
x 1 and
What Is in This Chapter?
This chapter contains the following topics:
Topic
Modicon Quantum with Control Expert Ethernet Services
Address Server
SNMP and Schneider Private MIB Overview
Modbus Messaging
I/O Scanner
Global Data
Time Synchronization
Electronic Mail Notification
Bandwidth Monitoring
FTP Server
Embedded Web Pages (HTTP Server, Web Configuration and Diagnostics)
Additional Ethernet Services
Page
33002479 10/2019
73
Ethernet Communication Services
Modicon Quantum with Control Expert Ethernet Services
Table of Ethernet Services
The Ethernet services of the 140 NOE 771 01, 140 NOE 771 11, and CPU 651 x0 add functionality to the system. Some services can be configured, others require no configuration.
Some services provide diagnostic information. Access to the services is through either a Web page or the Control Expert application.
NOE 771 01 NOE 771 11 CPU 651 x0
Service
Address Server ( see page 76 )
configure Web
diagnostic configure diagnostic configure SNMP V2 Agent (Network
Management Service)
diagnostic
Schneider Private MIB
configure
Modbus Messaging ( see page 79 )
diagnostic configure diagnostic
Global Data (Publish/Subscribe)
Time Synchronization Service see page 84 )
configure diagnostic
Electronic Mail Notification Service see page 85 )
configure diagnostic
Bandwidth Monitoring
configure diagnostic
FTP Server
configure diagnostic configure diagnostic configure diagnostic
Web
Control Expert
NA
Control Expert
NA
Web
Control Expert
NA
NA
NA
Control Expert
Web
Control Expert
Control Expert
Web
Control Expert
Web
Control Expert
Web
Control Expert
NA
NA
Web
Web
Control Expert
Web
Control Expert
NA
NA
Web
Control Expert
NA
Control Expert
NA
Web
Control Expert
NA
NA
NA
Control Expert
Web
Control Expert
Control Expert
Web
Control Expert
Web
Control Expert
Web
Control Expert
Web
Web
Web
Web
Control Expert
Web
Control Expert
NA
NA
NA
Control Expert
NA
Web
Control Expert
NA
NA
NA
Control Expert
Web
Control Expert
Control Expert
Web
Control Expert
Control Expert
Web
Control Expert
NA
NA
Web
Web
Control Expert
Web
Control Expert
NA
NA
74
33002479 10/2019
Service
Fast Device Replacement (Server)
Hot Standby
Flash File System
FactoryCast Application see page 90 )
configure diagnostic configure diagnostic configure diagnostic configure diagnostic configure diagnostic
Ethernet Communication Services
NOE 771 01
NA
NA
NA
NA
NA
NA
NA
NA
NA
Web
Control Expert
NOE 771 11
NA
NA
NA
NA
NA
NA
Web
Control Expert
NA
Web
Web
CPU 651 x0
NA
NA
NA
NA
NA
NA
NA
NA
NA
Control Expert
33002479 10/2019
75
Ethernet Communication Services
Address Server
Overview
The following information describes the services provided by the address server.
BOOTP server
DHCP server
The DHCP server responds to both a DHCP and a BOOTP server.
BOOTP Server
NOTE: The BOOTP server is available on the 140 NOE 771 xx models.
The BOOTstrap Protocol (BOOTP) software, compliant with RFC 951, is used to assign IP addresses to nodes on an Ethernet network. Devices (hosts) on the network send BOOTP requests during their initialization sequence. A BOOTP server that receives the request will extract the required IP address information from its database and place it in BOOTP response messages to the requesting devices. The devices will use the assigned IP addresses from the BOOTP server for all network communication.
NOTE: In order for BOOTP to work properly, you need to correctly configure the following:
IP address
subnetwork mask gateway address
NOE BOOTP Server
Your NOE 771 xx module comes supplied with a BOOTP server. This feature allows you to provide
IP addresses to all the I/O devices being serviced by the NOE 771 that is built into your NOE 771 xx xx . Providing a BOOTP server
module eliminates the need for an external BOOTP server.
NOTE: The NOE 771 xx’s BOOTP server can not provide its own IP address.
You can configure your NOE 771
Configure the 140 CPU 651 x xx ’s BOOTP server from the module’s HTTP Web page.
0 using the Control Expert editors. Configuring allows you to add to, remove from, and edit devices in the BOOTP server’s database, which is maintained in the module’s non-volatile memory.
76
33002479 10/2019
Ethernet Communication Services
DHCP Server
NOTE: The DHCP server is available on the 140 NOE 771 x 1 models.
The Dynamic Host Configuration Protocol (DHCP) is a superset of the BOOTP protocol. Your
140 NOE 771 x 1 has a DHCP server. The DHCP server is compliant with RFC 1531. The DHCP server can be used to provide the IP configuration to devices using BOOTP or devices using
DHCP.
The DHCP server has entries that use the MAC address to serve the IP configuration and entries in the server that use the role name to serve the IP configuration. Elsewhere in this book are details for the NOE address server configuration
see page 237
.
If you are migrating a BOOTP configuration from a 140 NOE 771
140 NOE 771 x 0 module to the new x
1 module, see Address Server Configuration/Fast Device Replacement
see page 237
for details on the automatic upgrade of your configuration for the new DHCP server.
NOTE: Before placing the NOE on a corporate network, Schneider Electric recommends that you discuss the installation with your MIS department. It is likely that your company's corporate network has at least one DHCP server running already. If the NOE's DHCP server is running on the same network, it may disturb the network.
To avoid any possible problem related to the NOE's DHCP server on the corporate network, ensure that the DHCP server is not running in the NOE by not having address entries in the configuration.
If there are no configured devices in the address server configuration page
the NOE will not start the DHCP server.
see page 237
Device Replacement
Fast device replacement and the address server are discussed in detail at Address Server
Configuration/Fast Device Replacement (
see page 237
.
33002479 10/2019
77
Ethernet Communication Services
SNMP and Schneider Private MIB Overview
Overview
Simple Network Management Protocol (SNMP) is configured on your NOE or 140 CPU 651 x 0.
Introduction
Network management software allows a network manager to:
monitor and control network components
isolate problems and find their causes query devices, such as a host computer(s), routers, switches, and bridges, to determine their status obtain statistics about the networks to which they are attached
Simple Network Management Protocol
Your NOE module or 140 CPU 651 x0 controller supports the Simple Network Management
Protocol (SNMP), which is the standard protocol used to manage a local area network (LAN).
SNMP defines exactly how a manager communicates with an agent .
The SNMP defines the format of:
requests that a manager sends to an agent
replies that the agent returns to the manager
MIB
Each object to which SNMP has access must be defined and given a unique name. Manager and agent programs must both agree on the names and meanings of the fetch and store operations.
The set of all objects SNMP can access is known as a Management Information Base (MIB ).
Private MIB
Schneider obtained a private MIB, Groupe_Schneider (3833). Under the Groupe Schneider private
MIB is a Transparent Factory Ethernet (TFE) private MIB. The Transparent Factory SNMP embedded component controls the Schneider private MIB function.
78
33002479 10/2019
Ethernet Communication Services
Modbus Messaging
Overview
The following information describes the functionality of the Modbus/TCP server.
The Client
The node that initiates a data transaction is called a client . All Modicon Quantum Ethernet modules provide the user with the capability to transfer data to and from nodes on a TCP/IP network using a communication instruction. All PLCs that support networking communication capabilities over
Ethernet can use either the MBP_MSTR Ladder Logic instruction to read or write controller information or IEC communication blocks.
The Server
The node that receives an inquiry is the server . Using the standard Modbus/TCP protocol, all
Modicon Quantum Ethernet modules provide access to controller data. Any device, PC, HMI package, another PLC, or any Modbus/TCP compliant device, can access data from the PLC. The
Modbus/TCP server also allows programming panels to log into the controller over Ethernet.
Modbus/TCP Connections and Commands
The Ethernet module supports up to 64 simultaneous Modbus/TCP server connections. To guarantee consistency of changes to the controller configuration, the Ethernet module allows only one programming panel to be logged in at a time.
The Ethernet modules supports these Modbus/TCP commands:
Read Data
Write Data
Read/Write Data
Get Remote Statistics
Clear Remote Statistics
Modbus 125 Commands (used by programming panels to download a new exec to the NOE)
The maximum register size for read requests, write requests, or read/write requests made using either a MBP_MSTR or Modbus command is as follows:
Command Request Type
Read
Write
Read/Write
Maximum size
125 read registers
123 read registers
125 read registers / 121 write registers
33002479 10/2019
79
Ethernet Communication Services
Performance
The following table shows the performance characteristics of the NOE Ethernet module’s
Modbus/TCP server.
Parameter
Typical Response Time (ms)
Number of Modbus connections (client and server)
Number of simultaneous login channels
Value
0.6
64 (NOE 771 x1, NWM 100 00,
HE CPU 651 x0), 16 Client
(NOE 771 x0), 32 Server
(NOE 771 x0)
1
NOTE: Ethernet module’s Modbus/TCP performance measurements are made with a Modicon
Quantum 140 CPU 534 14A PLC.
80
33002479 10/2019
Ethernet Communication Services
I/O Scanner
Introduction
The functionality of your Ethernet module is further enhanced by the addition of an I/O Scanner, which you can configure with the Schneider Electric programming panels.
I/O Scanner Features
NOE version 3.5 and later include these enhancements:
Feature
Improved Timeout and
Retry Transmission algorithm
Enable/Disable I/O
Scanner entry
Availability
Control Expert
Concept
ProWORX
Control Expert
Concept
Send Modbus requests across a router
Dynamic TCP port allocation
Repetitive rate display
Control Expert
Concept
ProWORX
Control Expert
Concept
ProWORX
Control Expert
Improvement
Improves TCP connection management
Reduces network traffic volume
Description
2004 version uses a variable timeout.
Older versions used a fixed timeout.
Difference: Faster retransmission rates
Use the ‘Device Control Block’
Set = 0 Enable channel for normal
data exchange
Set = 1 Disable channel
Note: Concept Users
Concept uses diagnostic words.
Set = FF Disable channel
Automatic Allows routers to connect remote I/O devices to a controller
Improves connection/disconnection performance
Check status using GUI
Reserves TCP client ports 3072 (0xC00) through 4992 (0x1380)
Allocates ports dynamically
Status displays in I/O Scanning tab of module editor
33002479 10/2019
81
Ethernet Communication Services
I/O Scanner Parameters
Functionality of the I/O Scanner.
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Health Timeout Value
Last Value (Input)
IP Address
Local and Remote Register
Reference
Repetitive Rate
Value
64: 140 NOE 771 00 (Version 2.2 or earlier)
128: 140 NOE 771 00 (Version 3.0 or later), 140 NOE 771 01, and 140 NOE 771 11 only
128: HE CPU 651 x 0
4000
4000
User configured: 1...65535 ms in 1 ms increments
User configured (zero or Hold)
User configured
IP address of scanned device (Slave IP)
User configured
Unit ID
Operation through a bridge
Gateway/Bridge Device
User configured: 0...65535 in multiples of:
16 ms, for 140 NOE 771
10 ms, for 140 CPU 651 x 1 x 0
User configured
Configure ID only if using a bridge
Modbus bridge: Supported
Modbus Plus bridge: Supported
Select the check box if you are using a bridge or a gateway device.
The I/O Scanner Concepts topic
see page 200
) explains how to configure the I/O scanner.
Performance
Performance data details are provided at I/O Scanner Response Times topic (
see page 233
.
82
33002479 10/2019
Ethernet Communication Services
Global Data
Overview
The Global Data service is a real-time publisher/subscriber mechanism providing the most efficient data exchange for PLC application coordination.
Devices that support Global Data are arranged in a distribution group for the purpose of application variable exchange and synchronization. Each Global Data device can publish up to one network
(application) variable and subscribe up to 64 network (application) variables.
The Quantum NOE module’s embedded Global Data Configuration Page provides a configuration screen to determine which and how many application variables are exchanged with this service.
After configuration, the exchanges between all stations belonging to the same distribution group are done automatically.
The Global Data service uses %MW words (4x registers) or unlocated variables for Global Data exchanges.
Key Features of Global Data
The main features for Global Data are:
One publisher and multiple subscribers
A device can publish one network variable of up to 512 %MW words (4x registers) or unlocated variables
A device can subscribe to several network variables of up to 2048 %MW words (4x registers) or unlocated variables
A device subscribes to the complete network variable
One distribution group per network IP address
Application defined publication rate
Up to 64 Global Data network variables (numbered from 1 to 64) can be part of the data distribution group
The NOE module has only one multicast address; consequently, it can only publish and subscribe inside the group
A device can participate in several distribution groups by using multiple NOE communication modules in the rack
Global Data's publish/subscribe mechanism allows multiple subscribers to receive a single data transmission. This is an advantage over client/server services, which require multiple transmissions to specific destinations. There are two immediate benefits:
reduces overall network traffic
ensures tighter synchronization of multiple subscribers
33002479 10/2019
83
Ethernet Communication Services
Time Synchronization
General
The time service synchronizes computer clocks over the Internet. For example, the time of one client is synchronized either with another server or to a referenced time source like a radio or satellite receiver.
Typical time service configurations utilize multiple redundant servers and diverse network paths to achieve high accuracy and reliability. Time service accuracy can be within a millisecond on LANs and up to a few tenths of milliseconds on WANs.
Use the time service for:
event recording: sequence events
event synchronization: trigger simultaneous events alarm and I/O synchronization: time stamp alarms
Time Synchronization and Time Stamps
On an Ethernet network, all controllers should be synchronized with the same clock time, which is provided by an NTP server. In each application program, events or application data (I/O values for example) can be time stamped using the application stacks.
The Ethernet interface module connects to an NTP time server and provides the source-time synchronization signal, which is sent to the CPU.
To read the clock, a function block is used in the controller’s project (application program):
84
33002479 10/2019
Ethernet Communication Services
Electronic Mail Notification
General
The electronic mail notification service allows controller-based projects to report alarms or events.
The automation controller monitors the system and can automatically create an electronic mail message alert with data, alarms, and/or events. Mail recipients can be either local or remote.
Based on predefined events or conditions, messages are created using the MBP_STR function
block.
The email message is constructed from predefined headers plus variables and text (a maximum of 238 bytes). This message is sent directly from the automation system to the local email server.
Mail headers contain common predefined items—recipient list, sender name, and subject.
These items can be updated by an authorized administrator.
Mail Service Client
The NOE communications module and 140 CPU 651 the mail server.
x 0 modules include an SMTP client. When the module receives a specific request from the controller, the module sends an email message to
33002479 10/2019
85
Ethernet Communication Services
Bandwidth Monitoring
Overview
Bandwidth Monitoring allows the user to access and monitor the NOE module’s CPU allocation for each of the following services:
see page 185
see page 199
Modbus messaging
see page 79
The Bandwidth Monitoring service retrieves workload data and returns one of two pieces of information: whether the module has free resources or whether the module is working at capacity.
Knowing the resource allocation helps you:
assess resource allocation
determine the number of NOEs needed in a system
NOTE: Users who want to use Bandwidth Monitoring do not need to develop a new set of access functions. The actual NOE CPU load is computed each second.
Bandwidth Monitoring Load Rates
The Bandwidth Monitoring service checks once a second and computes four (4) values in private data. These values are returned as the percentage of the NOE’s CPU that is allocated to:
see page 185
see page 199
Modbus messaging
see page 79
other services and idle
CPU time spent in other services is shown as "Other" or "Free." Bandwidth Monitoring uses the same functions as used by SNMP.
The three service rates, Global Data, I/O Scanner, and Messaging, are computed using the following formula:
(Current load * 100) / Maximum Load
The table shows the (dynamically computed) Maximum Load Rate for the NOE module:
Diagnostic Service
Global Data
I/O Scanner
Messaging
Workload Data Returned
Number of published variables per second
Number of transactions per second
Number of messages treated per second
Maximum Load
800
4200
410
NOTE: The loads depend on controller scan times. Each application has an expected scan time.
Therefore, when evaluating loads, ensure that the controller scan time is set to the expected scan time for the modeled application.
86
33002479 10/2019
Ethernet Communication Services
FTP Server
Overview
The following information describes the services provided by the FTP Server. The FTP server is available on all:
140 NOE 771
CPU 651 x xx communications modules (including the NOE module)
0 modules
FTP Server
The FTP server on the NOE module and CPU 651 user name and password.
x 0s is available as soon as the module receives an IP address. Any FTP client can log on to the module, which requires the client use the correct
The FTP Server can:
update the NOE module’s firmware by downloading a new Exec
provide error log visibility by uploading error log files upload/download BOOTP server and SNMP configuration files
NOTE: There is only one FTP client per module.
The FTP server is protected with a default user name and password.
Default user name USER case-sensitive
Default password USERUSER case-sensitive
See the FTP password on the FTP server.
( see page 63 ) topic to change the password or add/delete usernames
33002479 10/2019
87
Ethernet Communication Services
Embedded Web Pages (HTTP Server, Web Configuration and Diagnostics)
HTTP Server
The Modicon Quantum with Control Expert Ethernet modules’ Hypertext Transport Protocol
(HTTP) server is available as soon as the module receives an IP address.
Use the HTTP Server to:
1. view . . .
the module's Ethernet statistics the controller and I/O information the server information (BOOTP/DHCP/FDR) the diagnostic information for some Ethernet services
2. configure the module's Ethernet services
Use Internet Explorer version 4.0 or later. For a complete list of services, see the Key Features
see page 44
The HTTP server is protected with a default user name and password.
Default user name
Default password
USER case-sensitive
USER case-sensitive
The size of the user name and password is a maximum of 16 characters in non-extended
ASCII.
NOTE: The NOE 771 simultaneous users.
xx and CPU 651 xx support a maximum of 32 HTTP simultaneous connections. Browsers may open multiple connections so 32 HTTP connections do not indicate 32
NOTE: The NOE 771 00 and NOE 771 01 modules do not support user downloaded Web pages.
You will need to purchase either the NOE 771 10, NOE 771 11, or the NWM 100 00 module to support user downloaded Web pages.
88
33002479 10/2019
Ethernet Communication Services
Web Diagnostics
The embedded Web server provides Web pages to diagnose the following Transparent
Factory/Real Time services.
Diagnostic Service
Global Data
I/O Scanning
Time Synchronization
Electronic Mail Notification
Bandwidth Monitoring
Description status of all Global Data services status of all subscribed and published variables publication/subscription rate status of all I/O Scanning services status of individual scanned devices actual I/O scanning rate
diagnostic information for Port 502 messaging status of client and link to the server date and time status of Daylight Saving Time (DST) option status of SMTP server track messages sent and received track errors throughput measurement of NOE by service
NOTE: All these pages are protected by the general HTTP password.
Web Configuration
Elsewhere in this guide is a description of the web configuration pages (
see page 88
.
33002479 10/2019
89
Ethernet Communication Services
Additional Ethernet Services
Hot Standby
The Ethernet Hot Standby system consists of two identical Modicon Quantum systems. Each
Quantum system contains:
a Modicon Quantum Hot Standby with Control Expert controller (140 CPU 671
(140 CPU 672 xx0) or (140 CPU 678 61) a remote I/O head
NOE 771 xx modules (no more than six) a power supply xx 0),
The Hot Standby modules are connected to each other via a fiber-optic cable. Both remote I/O heads are connected to the remote I/O network and to each other.
Schneider Electric recommends:
1. remote I/O networks use redundant cables (drops are not redundant)
2. switch connecting the NOEs to the network (available switches):
499NES17100
499NOS17100
FactoryCast and User Customizable Web Pages
FactoryCast is a software package that you use to customize a Web site on the embedded Web server module. The site can be accessed via a browser to view and modify data from a Modicon
Quantum with Control Expert controller (PLC).
FactoryCast provides all the Web pages and Java applets you need to view run-time data from your controller. You can use the FactoryCast default Web site simply by configuring the module and accessing it with a browser over an intranet.
Modules that use FactoryCast to add customized web pages on a site are:
NOE 771 10
NOE 771 11
140 NWM 100 00
Flash File System
The NOE 771 xx modules are equipped with a Flash File System, which allows changing or updating the executive, kernel, and Web site files by an upload.
90
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Ethernet Services
33002479 10/2019
Modicon Quantum with Control Expert Ethernet Modules Services
Part II
Modicon Quantum with Control Expert Ethernet Modules
Services
33002479 10/2019
91
Ethernet Services
92
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Start Communication with Control Expert
33002479 10/2019
Start Communication with Control Expert
Chapter 3
Start Communication with Control Expert
Introduction
This chapter tells you how to begin Ethernet network configuration with Control Expert.
What Is in This Chapter?
This chapter contains the following sections:
Section
3.1
3.2
3.3
3.4
Topic
How to Configure the Communication
Control Expert Communication Links
Selecting the Ethernet Module
Selecting the Ethernet Coprocessor
Page
33002479 10/2019
93
Start Communication with Control Expert
How to Configure the Communication
Section 3.1
How to Configure the Communication
Overview
This section describes how to configure the communication.
What Is in This Section?
This section contains the following topics:
Topic
Add a New Network to the Communication Folder
Configure Network
Properties of a Network
Delete an Existing Network Folder
Page
94
33002479 10/2019
Start Communication with Control Expert
Add a New Network to the Communication Folder
Add a New Network to the Communication Folder
After starting a new application, the Communication folder under the Station tree branches the
Network folder and the Routing table folder (Premium platforms only). These two folders are empty. Under the Network folder, the user can insert the networks by menu. A click on the right mouse-button above Network pops up a contextual menu. The user selects the type of network he wants to add. For easier use, a network name will be suggested with the prefix of the network type
(Ethernet_1 or Modbus+_1). By choosing a new network the next available number for the network is chosen automatically, for example, Ethernet_1 then Ethernet_2 and so on. At any moment, the user may rename any Netlink.
The user can also attach a comment that describes each configured network. The OK button adds the network as subfolder.
The names of network nodes are also called NetLink. These are the names of logical networks.
33002479 10/2019
95
Start Communication with Control Expert
Configure Network
Configure Network
On the network folder, by a double-clicking action or by the Open item on contextual menu, the editor of the corresponding communication screen is opened in order to set the specific network services.
The figure shows the contextual menu to start network properties.
96
33002479 10/2019
Start Communication with Control Expert
Properties of a Network
Properties of a Network
The contextual menu proposes the user to see again the properties of a configured network. Here, the user can change the NetLink name and the associated comment.
The figure shows the Ethernet property window:
33002479 10/2019
97
Start Communication with Control Expert
Delete an Existing Network Folder
Delete an Existing Network Folder
With a right-mouse-click above the network folder, a contextual menu appears. Here the user is able to delete the network configuration. In this case, the subfolder of the network will also be removed in application browser.
NOTE: If this removed network was previously attached to a communication module, this module loses its link and it will work with its default parameters.
98
33002479 10/2019
Control Expert Communication Links
Section 3.2
Control Expert Communication Links
Start Communication with Control Expert
Overview
This section presents the principle of communication implementation and describes the relationship between software configuration of networks and the hardware configuration of the network controllers.
What Is in This Section?
This section contains the following topics:
Topic
Communication Configuration Principle
Link between Configuration and Communication
Link between Data and Communication
Page
33002479 10/2019
99
Start Communication with Control Expert
Communication Configuration Principle
Introduction
The configuration of communication links between different devices with Control Expert includes three different configuration parts.
configuration of the network controller configuration of the logical network configuration of network variables
Configuration
The communication configuration supports the communication and then the module.
free mode of Control Expert. That means the user can first configure the module and then the communication or the user can configure the
This will be provided through a NetLink that must be selected in the module configuration. The network variables including in the VAR folder are linked with a group name that defines an IP domain over Internet network.
The illustration shows the three parts involved in communication configuration:
100
33002479 10/2019
Start Communication with Control Expert
Link between Configuration and Communication
NetLinks
During Control Expert application design, the NetLinks are created and inserted on sub-folder
Communication under Network. These are the names of logical networks.
Under configuration folder, on the communication module node included in the current station, the list of existing NetLinks is proposed to select and attach one network to one module. Only the
NetLink that can be managed by this module, are displayed in the list box on module configuration screen. No NetLink can be edited and created here (no edit box), but this list contains at least the
No_Link field.
The following figure shows the window for the Ethernet link for the Quantum NOE module.
Attaching a NetLink to a Module
When a network is attached to a module, the icon of the corresponding node is changed and the network editor displays the address of the module in the rack .
The Icon in the Network folder indicates whether the link is attached to a module or not:
Icon when no communication module is attached to the NetLink
Icon when a communication module has been attached to the NetLink
33002479 10/2019
101
Start Communication with Control Expert
Link between Data and Communication
Network Variables and Groups
The groups of Ethernet network variables are created in the Ethernet network communication folders. An IP domain determines a group. In Control Expert, one network can support only one group.
In Data Editor, the list of all current groups is provided to select in which group each Ethernet network variables is included. Nevertheless, the group field is also a free entry editing box, in order to give a group name not yet defined in communication folder. The build step checks this link.
The illustration shows corresponding fields in Communication configuration and the Data Editor:
102
33002479 10/2019
Start Communication with Control Expert
Selecting the Ethernet Module
Section 3.3
Selecting the Ethernet Module
Introduction
This chapter contains the software pages for the NOE module.
What Is in This Section?
This section contains the following topics:
Topic
Selecting the Quantum NOE Ethernet Module
Security (Enable / Disable HTTP, FTP, and TFTP)
IP Configuration
Quantum NOE Ethernet Messaging Configuration
Page
33002479 10/2019
103
Start Communication with Control Expert
Selecting the Quantum NOE Ethernet Module
General Description
After configuring Ethernet communication configured.
see page 95
, the Ethernet module parameters can be
When you select the model family, all the corresponding communication module configuration options are displayed automatically. The module services allow the following settings to be made:
Setting
No
Yes
Web
Description
Setting deactivated.
Setting activated. Parameters are set using the Control Expert menu window.
Setting activated. Parameters are set using the configured NOE Web pages.
Control Expert menu window deactivated.
Note: Not available for every model family.
NOTE: The availability of the displayed settings depends on the selected model family and can vary.
104
33002479 10/2019
Start Communication with Control Expert
The screen shot shows an example of the menu window of the NOE Ethernet module (TCP/IP
10/100 Regular connection).
Parameter description:
Parameter
Model Family
Module Address
Module Utilities
Module IP Address
Description
Quantum NOE Ethernet Module settings
Not used
For module service configuration options, see above
Overview of the IP address parameter set
33002479 10/2019
105
Start Communication with Control Expert
After selecting the model family TCP/IP 10/100 Regular Connection, the following mask appears.
The image also displays the activated module services.
106
NOTE: The availability of the displayed register depends on the selected model family and can vary.
After selecting the Yes option in module services, the tab corresponding to the module is activated.
33002479 10/2019
Start Communication with Control Expert
Security (Enable / Disable HTTP, FTP, and TFTP)
Security and HTTP, FTP, and TFTP Services
The module uses HTTP services to provide access to its embedded Web pages. The module uses
FTP and TFTP services to support various features including firmware upgrades, FDR services, and Ethernet remote IO.
The module’s HTTP, FTP, and TFTP services can be disabled or enabled using the Control Expert
Network Editor → Security screen.
HTTP, FTP, and TFTP services are disabled by default in projects created using Quantum EIO
Version 1.5 and Unity Pro Version 8 or higher. They are enabled by default in projects created using previous versions of Unity Pro.
You can use Control Expert to enable or disable HTTP, FTP, and TFTP services as described in the following procedure.
If the HTTP, FTP, or TFTP services have been enabled with Control Expert, they can also be enabled or disabled at run time using an MBP_MSTR block with operation code 65520 (dec)
(see Quantum EIO, Control Network, Installation and Configuration Guide) .
Using Control Expert to Enable and Disable Firmware Upgrade & FDR and Web Access Services
Perform the following steps to enable or disable FTP/TFTP or HTTP services on the module.
Step
1
2
3
Action
In the Control Expert Project Browser → Structural View, double-click the desired network in the
Communication → Networks directory to open the Network Editor.
Click the Security tab.
On the Security screen, choose the appropriate setting: (Enabled or Disabled) for the service or services.
The edits will not take effect until they are successfully downloaded from your PC to the CPU and from the CPU to the communication modules and network devices.
33002479 10/2019
107
Start Communication with Control Expert
IP Configuration
General Description
The IP configuration tab enables you to configure IP address settings for the Quantum Ethernet module. IP address settings become active after:
the hardware is connected the configuration is downloaded to the PLC in the Quantum Ethernet module
The following figure shows the IP configuration for the Quantum Ethernet model family:
108
Description of the selection properties
Selection
Configured
Client / Server
Ethernet configuration
Description
Activate the IP address, subnet mask, and gateway address. The data is activated after the configuration is downloaded to the PLC.
The Quantum NOE Ethernet module receives its IP address parameter through a BOOTP server on startup.
Select the default protocol as Ethernet or 802.3.
33002479 10/2019
Start Communication with Control Expert
Quantum NOE Ethernet Messaging Configuration
Introduction
Ethernet messaging gives the user the opportunity to send and receive Ethernet messages. Data traffic is handled by the client/server procedure.
Parameter description:
Setting
Connection configuration
Access
IP Address
Access Control
Description
Activates general data transfer.
Activates data transfer between specific nodes.
Defines the node for the Ethernet Messaging procedure.
Activates or deactivates control of remote devices that are attempting to open a TCP connection to the module.
Messaging Tab
The following procedure shows how to access the Messaging page:
Step
1
2
3
Action
In the Control Expert project browser, go to the Structural view. Expand (+) the
Communication folder until you locate the name of the Ethernet logical network associated with the module.
Right click the Ethernet logical network and select Open.
Result: The module configuration screen appears.
Select the Messaging tab. (See the illustration below.)
33002479 10/2019
109
Start Communication with Control Expert
The Messaging tab is shown below.
Configuration parameters can be accessed in two areas on the Messaging tab screen:
the Connection Configuration area
the Access Control area
Connection Configuration Area
The Connection Configuration area is used to:
activate an access control utility
list the remote devices that can connect to the module according to a communication protocol
110
33002479 10/2019
Start Communication with Control Expert
Access Control
The Access Control box is used to activate or deactivate control of remote devices that are attempting to open a TCP connection to the module. The functionality depends on whether the box is checked or not:
checked: Access control management is activated and the Access column of the table is active
(no longer grayed out).
The module can only communicate to the addresses entered in the 128 available spaces in
the Slave IP Address column.
With the module in client mode it can only connect to remote devices selected by the Access column in the Connection Configuration table.
unchecked: Access control management is inoperative and the Access column of the table is not active (grayed out).
With the module in server mode, remote third-party devices can connect as clients (before communication with the module) without being declared in the table.
NOTE: Access control is only effective on the TCP/IP profile and assists module operations in server and client mode.
33002479 10/2019
111
Start Communication with Control Expert
Selecting the Ethernet Coprocessor
Section 3.4
Selecting the Ethernet Coprocessor
Introduction
This section describes configuring the Modicon Quantum with Control Expert coprocessor, 140
CPU 651 x0.
What Is in This Section?
This section contains the following topics:
Topic
Selecting the Modicon Quantum with Control Expert Ethernet Controller
Configuring the IP Address of the Ethernet Controller
Modicon Quantum with Control Expert Ethernet Controller Messaging Configuration
Page
112
33002479 10/2019
Start Communication with Control Expert
Selecting the Modicon Quantum with Control Expert Ethernet Controller
General Description
After configuring Ethernet communication configured.
see page 95
, the Ethernet module parameters can be
When you select the model family, all the corresponding communication-module configuration options display automatically. The module services allow the following settings to be made:
Setting
No
Yes
Description
Setting deactivated.
Setting activated. Parameters are set using the Control Expert menu window.
NOTE: The availability of the displayed settings varies and depends on the selected model family.
The screen shot shows an example of the menu window of the Ethernet module CPU 651
(TCP/IP 10/100 Extended connection).
x 0
Parameter description:
Parameter
Model Family
Module Address
Module Utilities
Module IP Address
Description
Modicon Quantum with Control Expert Ethernet module settings.
Not used.
For module service configuration options, see above.
Overview of the IP address parameter set.
33002479 10/2019
113
Start Communication with Control Expert
After selecting the model family TCP/IP 10/100 Extended Connection, the following mask appears.
The image also displays the activated module services.
114
NOTE: The availability of the displayed register depends on the selected model family and can vary.
After selecting the Yes option in module services, the tab corresponding to the module is activated.
33002479 10/2019
Start Communication with Control Expert
Configuring the IP Address of the Ethernet Controller
General Description
The IP configuration tab enables you to configure the IP address settings. The settings are activated after the connection to the hardware and the configuration is downloaded to the Modicon
Quantum with Control Expert Ethernet controller, 140 CPU 651 x0.
The diagram shows the IP configuration for the Modicon Quantum with Control Expert Ethernet controller, 140 CPU 651 x0.
Description of the selection properties
Selection
Configured
Client / Server
Description
Activate the IP address, Subnet mask and Gateway address. The data is activated after the configuration is downloaded to the controller.
The Modicon Quantum with Control Expert Ethernet controller receives its IP address parameter through a BOOTP server on startup.
33002479 10/2019
115
Start Communication with Control Expert
Modicon Quantum with Control Expert Ethernet Controller Messaging Configuration
Introduction
Use the Messaging tab in Control Expert to send and receive messages via Ethernet. The data traffic is handled by the client / server procedure.
The following illustration shows the Messaging dialog box.
116
Parameter description:
Setting
Connection configuration
Access
IP address
Access Control
Description
Activates general data transfer.
Activates data transfer between specific nodes.
Defines the node for the Ethernet messaging procedure.
Activates or deactivates control of remote devices that are attempting to open a TCP connection to the module.
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Using Ethernet Services
33002479 10/2019
Using the Modicon Quantum with Control Expert Ethernet Services
Part III
Using the Modicon Quantum with Control Expert Ethernet
Services
Purpose
This part describes how to use the Ethernet services available on Modicon Quantum with Control
Expert Ethernet modules.
What Is in This Part?
This part contains the following chapters:
9
10
7
8
Chapter
4
5
6
11
12
Chapter Name
Transferring Data Using Communication Blocks
Global Data (Publish/Subscribe) Utility
I/O Scanner
Address Server Configuration/Fast Device Replacement
Network Management Service (SNMP)
NTP Time Synchronization Service
Electronic Mail Notification Service
Embedded Web Pages
Hot Standby
Page
33002479 10/2019
117
Using Ethernet Services
118
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Transferring Data Using Communication Blocks
33002479 10/2019
Transferring Data Using Communication Blocks
Chapter 4
Transferring Data Using Communication Blocks
Introduction
This chapter describes how to transfer data to and from nodes on a TCP/IP network using communication blocks. You transfer the data using either a special MBP_MSTR instruction or an
IEC Logic function. Operational statistics and error codes for reading and writing the controller information are included.
What Is in This Chapter?
This chapter contains the following sections:
Section
4.1
4.2
IEC Data Transfer Functions
MBP_MSTR
Topic Page
33002479 10/2019
119
Transferring Data Using Communication Blocks
IEC Data Transfer Functions
Section 4.1
IEC Data Transfer Functions
Overview
This section describes several IEC function blocks that manage data transfer to and from nodes on a TCP/IP network.
What Is in This Section?
This section contains the following topics:
Topic
CREAD_REG
CWRITE_REG
READ_REG
WRITE_REG
TCP_IP_ADDR
Page
120
33002479 10/2019
Transferring Data Using Communication Blocks
CREAD_REG
Function Description
The CREAD_REG block reads register data continuously from an addressed node via TCP/IP-
Ethernet.
EN and ENO can be projected as additional parameters.
NOTE: About this function block:
When programming this function, you must be familiar with the routing procedures used by your
network.
For technical reasons, this function block does not allow the use of ST and IL programming languages.
Representation
Block representation:
Parameter Description
Description of parameters:
Parameter Data Type
SLAVEREG DINT
NO_REG
AddrFld
INT
WordArr5
REG_READ WORD
STATUS WORD
Meaning offset address of the first %MW word (4x register) in the slave to be read from number of registers to be read from slave data structure describing the TCI/IP address first %MW word (4x register) for read values error code
33002479 10/2019
121
Transferring Data Using Communication Blocks
Elementary Description for WordArr5 with TCP/IP Ethernet
Elementary description for WordArr5 with TCP/IP Ethernet:
Element
WordArr5[1]
WordArr5[2]
WordArr5[3]
WordArr5[4]
WordArr5[5]
Data Type
WORD
WORD
WORD
WORD
WORD
Meaning
Low value byte: MBP on Ethernet Transporter (MET) mapping index
High value byte: Slot of the NOE module
Byte 4 (MSB) of the 32-bit destination IP address
Byte 3 of the 32-bit destination IP address
Byte 2 of the 32-bit destination IP address
Byte 1 (LSB) of the 32-bit destination IP address
Function Mode of the CREAD_REG Block
CREAD_REG , CWRITE_REG , READ_REG , WRITE_REG , and MBP_MSTR function blocks use one data transaction path and require multiple cycles to complete an operation. The number of transaction paths available by module and by MAST cycle depends on the communication port used:
Modbus Plus embedded port or NOM modules support up to 4 blocks at the same time.
TCP/IP Ethernet embedded port support up to 4 blocks at the same time.
TCP/IP Ethernet NOE, NOC, and 140 CRP 312 00 modules support up to 16 blocks at the same time.
More communication function blocks may be programmed on the same communication port.
However, a communication block exceeding the maximum number on that port is not serviced until one of the transaction paths is available. Then, the next block on the same port becomes active and begins using an available path.
NOTE: A TCP/IP communication between a Quantum PLC (NOE 771 ••) and a Momentum PLC
(all TCP/IP CPUs and all TCP/IP I/O modules) is only possible, when only one read or write job is carried out in every cycle. If several jobs are sent per PLC cycle, the communication stops without generating an error message in the status register of the function block.
NOTE: A TCP/IP communication between a Quantum PLC (NOE 211 00) and a Momentum PLC
(all TCP/IP CPUs and all TCP/IP I/O modules) is only possible, when only one read or write job is carried out in every cycle. If several jobs are sent per PLC cycle, the communication stops without generating an error message in the status register of the function block.
The entire routing information is contained in data structure WordArr5 of input AddrFld. The type of function block connected to this input and thus the contents of the data structure depends on the network used.
Please use:
TCP/IP Ethernet: the function block TCP_IP_ADDR
NOTE: For experts: The WordArr5 data structure can be used with constants as well.
122
33002479 10/2019
Transferring Data Using Communication Blocks
NOTE: This function block puts a heavy load on the network; therefore the network load must be carefully monitored. If the network load is too high, the program logic should be reorganized in order to work with the READ_REG function block, a variation of this function block that does not operate in a continuous mode, but under command control.
SLAVEREG
SLAVEREG is the start of the area in the addressed slave from which the source data is read. The source area always resides within the %MW word (4x register) area. SLAVEREG expects the source reference as offset within that area. (In 4x registers, the leading "4" must be omitted. For example, "59" (contents of the variables or value of the literal) = 40059).
The parameter can be specified as direct address, located variable, unlocated variable, or literal.
NO_REG
NO_REG is the number of registers to be read from the addressed slave (1 ... 100). The parameter can be entered as a direct address, located variable, unlocated variable, or literal.
REG_READ
The REG_READ word parameter addresses the first register in a series of NO_REG registers, listed one after the other, which are used as a destination data area. The parameter must be entered as a direct address or located variable.
STATUS
Error code, see Runtime errors.
The STATUS parameter can be specified as direct address, located variable, or unlocated variable.
33002479 10/2019
123
Transferring Data Using Communication Blocks
CWRITE_REG
Function Description
The CWRITE_REG block writes data to a register area continuously, transferring data from the
PLC via TCP/IP Ethernet to an addressed slave.
EN and ENO can be configured as additional parameters.
NOTE: About this function block:
When programming this function, you must be familiar with the routing procedures used by your
network.
For technical reasons, this function block does not allow the use of ST and IL programming languages.
Symbol
Block representation:
Parameter Description
Description of parameters:
Parameter Data Type
SLAVEREG DINT
NO_REG INT
REG_WRIT WORD
AddrFld
STATUS
WordArr5
WORD
Meaning offset address of the first %MW word (4x register) in the slave to be written to number of registers to be written to slave first %MW word (4x register) of the source data area data structure for transferring the TCI/IP address
MBP_MSTR error code
124
33002479 10/2019
Transferring Data Using Communication Blocks
Elementary Description for WordArr5 with TCP/IP Ethernet
Elementary description for WordArr5 with TCP/IP Ethernet:
Element Data Type
WordArr5[1] WORD
WordArr5[2] WORD
WordArr5[3] WORD
WordArr5[4] WORD
WordArr5[5] WORD
Meaning low value byte: MBP on Ethernet Transporter (MET) mapping index high value byte: slots of the NOE module byte 4 (MSB) of the 32-bit destination IP address byte 3 of the 32-bit destination IP address byte 2 of the 32-bit destination IP address byte 1 (LSB) of the 32-bit destination IP address
CWRITE_REG Block Function Mode
CREAD_REG , CWRITE_REG , READ_REG , WRITE_REG , and MBP_MSTR function blocks use one data transaction path and require multiple cycles to complete an operation. The number of transaction paths available by module and by MAST cycle depends on the communication port used:
Modbus Plus embedded port or NOM modules support up to 4 blocks at the same time.
TCP/IP Ethernet embedded port support up to 4 blocks at the same time.
TCP/IP Ethernet NOE, NOC, and 140 CRP 312 00 modules support up to 16 blocks at the same time.
More communication function blocks may be programmed on the same communication port.
However, a communication block exceeding the maximum number on that port is not serviced until one of the transaction paths is available. Then, the next block on the same port becomes active and begins using an available path.
If several CWRITE_REG function blocks are used within an application, they must at least differ in the values of their NO_REG or REG_WRITE parameters.
NOTE: A TCP/IP communication between a Quantum PLC (NOE 771 xx ) and a Momentum PLC
(all TCP/IP CPUs and all TCP/IP I/O modules) is only possible, when only one read or write job is carried out in every cycle. If several jobs are sent per PLC cycle, the communication stops without generating an error message in the status register of the function block.
The entire routing information is contained in data structure WordArr5 of input AddrFld. The type of function block connected to this input and thus the contents of the data structure depend on the network used.
Please use:
TCP/IP Ethernet: the function block TCP_IP_ADDR
NOTE: For experts: The WordArr5 data structure can also be used with constants.
NOTE: This function block puts a heavy load on the network. The network load must therefore be carefully monitored. If the network load is too high, the program logic should be reorganized to work with the WRITE_REG function block, which is a variant of this function block that does not operate in continuous mode but is command driven.
33002479 10/2019
125
Transferring Data Using Communication Blocks
SLAVEREG
SLAVEREG is the start of the area in the addressed slave to which the source data are written.
The destination area always resides within the %MW word (4x register) area. SLAVEREG expects the destination address as offset within that area. In 4x registers, the leading 4 must be omitted.
For example, 59 (contents of the variables or value of the literal) = 40059.
The parameter can be specified as direct address, located variable, unlocated variable, or literal.
NO_REG
NO_REG is the number of registers to be written to slave processor (1...100). The parameter can be specified as direct address, located variable, unlocated variable, or literal.
STATUS
Error code, see Runtime errors.
The STATUS parameter can be specified as direct address, located variable or unlocated variable.
REG_WRIT
The REG_WRIT word parameter addresses the first register in a series of NO_REG Successive registers used as source data area.
The parameter must be entered as a direct address or located variable.
126
33002479 10/2019
Transferring Data Using Communication Blocks
READ_REG
Function Description
Upon request, the READ_REG block reads a register area once (rising edge of the REQ input). It reads data from an addressed slave via TCP/IP Ethernet.
EN and ENO can be projected as additional parameters.
NOTE: About this function block:
When programming this function, you must be familiar with the routing procedures used by your
network.
For technical reasons, this function block does not allow the use of ST and IL programming languages.
Symbol
Block representation:
Parameter Description
Description of block parameters:
Parameter
REQ
SLAVEREG
Data Type
BOOL
DINT
NO_REG
AddrFld
NDR
ERROR
STATUS
REG_READ
INT
WordArr5
BOOL
BOOL
WORD
WORD
Meaning start read operation once offset address of the first %MW word (4x register) in the slave to be read from number of registers to be read from slave data structure describing the TCP/IP address set to 1 for one cycle after reading new data set to 1 for one scan in case of error error code first %MW word (4x register) for read values
33002479 10/2019
127
Transferring Data Using Communication Blocks
Elementary Description for WordArr5 with TCP/IP Ethernet
Elementary description for WordArr5 with TCP/IP Ethernet:
Element Data Type
WordArr5[1] WORD
WordArr5[2] WORD
WordArr5[3] WORD
WordArr5[4] WORD
WordArr5[5] WORD
Meaning low value byte: MBP on Ethernet Transporter (MET) mapping index high value byte: Slot of the NOE module byte 4 (MSB) of the 32-bit destination IP address byte 3 of the 32-bit destination IP address byte 2 of the 32-bit destination IP address byte 1 (LSB) of the 32-bit destination IP address
Function Mode of READ_REG Blocks
CREAD_REG , CWRITE_REG , READ_REG , WRITE_REG , and MBP_MSTR function blocks use one data transaction path and require multiple cycles to complete an operation. The number of transaction paths available by module and by MAST cycle depends on the communication port used:
Modbus Plus embedded port or NOM modules support up to 4 blocks at the same time.
TCP/IP Ethernet embedded port support up to 4 blocks at the same time.
TCP/IP Ethernet NOE, NOC, and 140 CRP 312 00 modules support up to 16 blocks at the same time.
More communication function blocks may be programmed on the same communication port.
However, a communication block exceeding the maximum number on that port is not serviced until one of the transaction paths is available. Then, the next block on the same port becomes active and begins using an available path.
NOTE: A TCP/IP communication between a Quantum PLC (NOE 771 xx ) and a Momentum PLC
(all TCP/IP CPUs and all TCP/IP I/O modules) is possible only when 1 read or write job is carried out in every cycle. If several jobs are sent per PLC cycle, the communication stops without generating an error message in the status register of the function block.
The entire routing information is contained in data structure WordArr5 of input AddrFld. The type of function block connected to this input and thus the contents of the data structure depends on the network used.
Please use:
TCP/IP Ethernet: the function block TCP_IP_ADDR
NOTE: For experts: The WordArr5 data structure can be used with constants as well.
REQ
A rising edge triggers the read transaction.
The REQ parameter can be specified as direct address, located variable, unlocated variable, or
Literal.
128
33002479 10/2019
Transferring Data Using Communication Blocks
SLAVEREG
SLAVEREG is the start of the area in the addressed slave from which the source data is read. The source area always resides within the %MW word (4x register) area. SLAVEREG expects the source reference as offset within that area. In 4x registers, the leading 4 must be omitted. For example, 59 (contents of the variables or value of the literal) = 40059.
The parameter can be specified as direct address, located variable, unlocated variable, or literal.
NO_REG
Number of registers to be read from the addressed slave (1 ... 100).
The NO_REG parameter can be specified as direct address, located variable, unlocated variable, or literal.
NDR
Transition to ON state for one program cycle signifies receipt of new data ready to be processed.
The NDR parameter can be specified as direct address, located variable, or unlocated variable.
ERROR
Transition to ON state for one program cycle signifies detection of a new error.
The ERROR parameter can be specified as direct address, located variable, or unlocated variable.
REG_READ
This word parameter addresses the first register in a series of NO_REG registers lying in series used as destination data area.
The REG_READ parameter must be entered as a direct address or located variable.
STATUS
Error code, see Runtime errors.
The STATUS parameter can be specified as direct address, located variable or unlocated variable.
33002479 10/2019
129
Transferring Data Using Communication Blocks
WRITE_REG
Function Description
Upon request, the WRITE_REG block writes a register area once (rising edge of the REQ input).
It transfers data from the PLC via TCP/IP Ethernet to an addressed slave.
EN and ENO can be configured as additional parameters.
NOTE: About this function block:
When programming this function, you must be familiar with the routing procedures used by your
network.
For technical reasons, this function block does not allow the use of ST and IL programming languages.
Symbol
Block representation:
Parameter Description
Description of parameters:
Parameter
REQ
Data Type
BOOL
SLAVEREG DINT
NO_REG
AddrFld
REG_WRIT
DONE
ERROR
STATUS
INT
WordArr5
WORD
BOOL
BOOL
WORD
Meaning start write operation once offset address of the first %MW word (4x register) in the slave to be written to number of registers to be written from slave data structure transferring the TCP/IP address first %MW word (4x register) of the source data area set to "1" for one scan after writing data set to "1" for one scan in case of error error code
130
33002479 10/2019
Transferring Data Using Communication Blocks
Elementary Description for WordArr5 with TCP/IP Ethernet
Elementary description for WordArr5 with TCP/IP Ethernet:
Element Data Type
WordArr5[1] WORD
WordArr5[2] WORD
WordArr5[3] WORD
WordArr5[4] WORD
WordArr5[5] WORD
Meaning high value byte: Slot of the NOE module low value byte: MBP on Ethernet Transporter (MET) mapping index byte 4 (MSB) of the 32-bit destination IP address byte 3 of the 32-bit destination IP address byte 2 of the 32-bit destination IP address byte 1 (LSB) of the 32-bit destination IP address
Function Mode of the WRITE_REG Module
CREAD_REG , CWRITE_REG , READ_REG , WRITE_REG , and MBP_MSTR function blocks use one data transaction path and require multiple cycles to complete an operation. The number of transaction paths available by module and by MAST cycle depends on the communication port used:
Modbus Plus embedded port or NOM modules support up to 4 blocks at the same time.
TCP/IP Ethernet embedded port support up to 4 blocks at the same time.
TCP/IP Ethernet NOE, NOC, and 140 CRP 312 00 modules support up to 16 blocks at the same time.
More communication function blocks may be programmed on the same communication port.
However, a communication block exceeding the maximum number on that port is not serviced until one of the transaction paths is available. Then, the next block on the same port becomes active and begins using an available path.
If several WRITE_REG function blocks are used within an application, they must at least differ in the values of their NO_REG or REG_WRITE parameters.
NOTE: A TCP/IP communication between a Quantum PLC (NOE 771 xx ) and a Momentum PLC
(all TCP/IP CPUs and all TCP/IP I/O modules) is possible only when one read or write job is carried out in every cycle. If several jobs are sent per PLC cycle, the communication stops without generating an error message in the status register of the function block.
The status signals DONE and ERROR report the function block state to the user program.
The entire routing information is contained in data structure WordArr5 of input AddrFld. The type of function block connected to this input and thus the contents of the data structure depend on the network used.
Please use:
TCP/IP Ethernet: the function block TCP_IP_ADDR
NOTE: For experts: The WordArr5 data structure can also be used with constants.
33002479 10/2019
131
Transferring Data Using Communication Blocks
REQ
A rising edge triggers the read transaction.
The REQ parameter can be specified as direct address, located variable or unlocated variable.
SLAVEREG
SLAVEREG is the start of the area in the addressed slave from which the source data is read. The source area always resides within the %MW word (4x register) area. SLAVEREG expects the source reference as offset within that area. In 4x registers, the leading 4 must be omitted. For example, 59 (contents of the variables or value of the literal) = 40059.
The parameter can be specified as direct address, located variable, unlocated variable, or literal.
NO_REG
Number of registers to be read from the addressed slave (1...100).
The parameter can be specified as direct address, located variable, unlocated variable, or literal.
REG_WRIT
The REG_WRIT word parameter addresses the first register in a series of NO_REG registers used as source data area.
The parameter must be entered as a direct address or located variable.
DONE
Transition to ON state for one program scan signifies data have been transferred.
The DONE parameter can be specified as direct address, located variable or unlocated variable.
ERROR
Transition to ON state for one program scan signifies detection of a new error.
The parameter can be specified as direct address, located variable or unlocated variable.
STATUS
Error code, see Runtime errors.
The parameter can be specified as direct address, located variable, or unlocated variable.
132
33002479 10/2019
Transferring Data Using Communication Blocks
TCP_IP_ADDR
Function Description
The TCP_IP_ADDR block enables the input of TCP/IP addresses for the READ_REG
see page 127
see page 121
see page 130
see page 124
blocks. The address is transferred in the form of a data structure.
EN and ENO can be projected as additional parameters.
NOTE: When programming the TCP_IP_ADDR function, you must be familiar with your network’s routing procedures.
Symbol
Block representation:
Parameter Description
Description of parameters:
Parameter
Map_Idx
Data Type
BYTE
Slot_ID
Ip_B4
Ip_B3
Ip_B2
Ip_B1
AddrFld
BYTE
BYTE
BYTE
BYTE
BYTE
WordArr5
Meaning
Map-Index
MBP on Ethernet Transporter (MET) mapping index slot ID slot of the NOE module byte 4 (MSB) of the 32-bit destination IP address byte 3 of the 32-bit destination IP address byte 2 of the 32-bit destination IP address byte 1 (LSB) of the 32-bit destination IP address data structure used to transfer the TCP/IP address
33002479 10/2019
133
Transferring Data Using Communication Blocks
Elementary Description for WordArr5
Elementary description for WordArr5:
Element Data Type
WordArr5[1] WORD
WordArr5[2] WORD
WordArr5[3] WORD
WordArr5[4] WORD
WordArr5[5] WORD
Meaning high value byte: Slot of the NOE module low value byte: MBP on Ethernet Transporter (MET) mapping index byte 4 (MSB) of the 32-bit destination IP address byte 3 of the 32-bit destination IP address byte 2 of the 32-bit destination IP address byte 1 (LSB) of the 32-bit destination IP address
Map_Idx
The MBP on Ethernet Transporter (MET) mapping index is given at the Map_Idx input. That is, if
MET is 6, the value appears as follows:
Slot_ID
If an NOE in the rack of a Quantum controller is addressed as destination node, the value at the
Slot_ID input represents the physical NOE slot. That is, if the NOE is plugged in at Slot 7 of the rack, the value appears as follows:
NOTE: When using an integrated Ethernet CPU module such as the 140 CPU 651 must be 254 (FE hex) regardless of the CPU slot.
x 0, the slot ID
AddrFld
If an NOE in the rack of a Quantum controller is addressed as a destination node, the value in the
High value byte represents the physical slot of the NOE and the Low value byte represents the
MBP on Ethernet Transporter (MET) mapping index. That is, if the NOE is inserted in slot 7 of the rack and the MET mapping index is 6, the first element of the data structure looks as follows:
134
High value byte Slots 1 ... 16
Low value byte MBP on Ethernet Transporter (MET) mapping index
33002479 10/2019
Transferring Data Using Communication Blocks
MBP_MSTR
Section 4.2
MBP_MSTR
Overview
This section describes the 14 different communication function provided in the MBP_MSTR function block.
What Is in This Section?
This section contains the following topics:
Topic
Block Description
Operational Function Codes
Network Control Block Structures
Modbus Plus, SY/MAX, and Ethernet TCP/IP Error Codes
CTE Error Codes for SY/MAX and TCP/IP Ethernet
SY/MAX-Specific Error Codes
Read Data
Write Data
Get Local Statistics
Clear Local Statistics
Get Remote Statistics
Clear Remote Statistics
TCP/IP Ethernet Network Statistics
TCP/IP Ethernet Error Codes
Reset Optional Module
Read CTE
Write CTE
Send Email
Send Modbus Request
Close Connection Request
Change Modbus Plus Address
Read/Write Data
Enable / Disable HTTP or FTP/TFTP Services
Page
33002479 10/2019
135
Transferring Data Using Communication Blocks
Block Description
Function Description
You can select one of 14 available network communication operations
MBP_MSTR function block.
see page 139
The MBP_MSTR block is supported on various hardware platforms
Expert, Communication, Block Library) .
(see EcoStruxure™ Control
EN and ENO can be configured as additional parameters.
NOTE: Verify that the programmer is familiar with the routing procedures of your network when programming an MBP_MSTR function block. Modbus Plus routing path structures are described in detail in the communication architectures manual (see Communication Services and
Architectures, Reference Manual) and the Modbus Plus Network Planning and Installation Guide .
If TCP/IP or SY/MAX Ethernet routing is implemented (see Quantum using EcoStruxure™Control
Expert, TCP/IP Configuration, User Manual) , use standard EtherNet IP router products.
CREAD_REG , CWRITE_REG , READ_REG , WRITE_REG , and MBP_MSTR function blocks use one data transaction path and require multiple cycles to complete an operation. The number of transaction paths available by module and by MAST cycle depends on the communication port used:
Modbus Plus embedded port or NOM modules support up to 4 blocks at the same time.
TCP/IP Ethernet embedded port support up to 4 blocks at the same time.
TCP/IP Ethernet NOE, NOC, and 140 CRP 312 00 modules support up to 16 blocks at the same time.
More communication function blocks may be programmed on the same communication port.
However, a communication block exceeding the maximum number on that port is not serviced until one of the transaction paths is available. Then, the next block on the same port becomes active and begins using an available path.
NOTE: In FBD and LD sections, this function block can be used on the program level and with derived function blocks (DFBs). When using DFBs, verify that the parameters CONTROL and
DATABUF are directly connected to the I/O pins of the DFB.
NOTE: A TCP/IP communication between a Quantum PLC and a Momentum PLC is only possible when one read or write job is carried out in every cycle. If several jobs are sent per PLC cycle, the communication stops without generating a detected error message in the status register of the function block.
NOTE: In Quantum or Premium Hot Standby, to help prevent the former standby CPU from executing communication functions (now in RUN offline state), add a condition on the status bits to disable the function if the CPU is offline.
Example:
You can send MBP_MSTR .Enable:=(HSBY_NOEPLCMSTR_ON) AND (%SW61.1) AND NOT
(%SW61.0) or
You can create a boolean variable, primary_state:=(%SW61.1) AND NOT (%SW61.0), and insert it for executing the section
136
33002479 10/2019
Transferring Data Using Communication Blocks
NOTE: In M580 Hot Standby, to help prevent the former standby CPU from executing communication functions (now in RUN offline state), add a condition on the status bits to disable the function if the CPU is offline.
Example:
You can set MBP_MSTR .Enable:=(HSBY_NOEPLCMSTR_ON AND
ECPU_HSBY_1.LOCAL_HSBY_STS.RUN_PRIMARY) or
Use the boolean variable ECPU_HSBY_1.LOCAL_HSBY_STS.RUN_PRIMARY as condition for executing the section
NOTE: Several copies of this function block can be used in the program. However, multiple instancing of these copies is not possible.
Representation in FBD
Representation in LD
33002479 10/2019
137
Transferring Data Using Communication Blocks
Input Parameters
Parameter
ENABLE
ABORT
Data Type
BOOL
BOOL
Description
When ON, the operation specified in the first element of the CONTROL register is enabled.
When ON, the currently active operation ( see page 139 )
is aborted.
Output Parameters
Parameter
ACTIVE
ERROR
SUCCESS
CONTROL
Data Type
BOOL
BOOL
BOOL
WORD
DATABUF WORD
Description
ON when the operation is active.
ON when the operation is aborted without success.
ON when the operation concludes successfully.
This field contains the control block. The first element CONTROL[1] contains
the number of the operation code of the operation to be performed
( see page 139 ) . The content of the sequence register is determined by the
operation.
Verify that the data field is declared as a located variable.
The structure of the control block differs according to the network used
For operations providing data (for example a write operation) the data field is the data source. For operations receiving data (for example a read operation) the data field is the data destination.
With Ethernet CTE read and write operations, the data field holds the contents of the Ethernet configuration extension table. Verify that DATABUF is defined as an array of at least 10 elements in this case.
Verify that the data field is declared as a located variable.
Runtime Error
In the event of a detected error occurring during an MBP_MSTR operation, a hexadecimal error code is displayed in the CONTROL[2] register of the control block for one cycle.
NOTE: Function error codes are network-specific.
(see EcoStruxure™ Control Expert, I/O Management, Block Library)
NOTE: For a list of all block error codes and values, refer to the tables of error codes for the communication library (see EcoStruxure™ Control Expert, Communication, Block Library) .
138
33002479 10/2019
Transferring Data Using Communication Blocks
Operational Function Codes
Valid MBP_MSTR Function Codes
Using the MBP_MSTR block, network communication operations can be triggered via the network.
As shown in the following table, each operation has a function code assigned to it. The availability of specific operations depends on both the type of network and the type of module you are using.
CIP Ethernet
10
11
12
13
14
15
16
17
7
8
9
3
4
5
1
2
Function
Code
6
23
65520 (dec)
FFF0 (hex)
Operation
Write data
Read data
Get local statistics
Clear local statistics
Write global data, peer cop
(see EcoStruxure™ Control Expert,
Communication, Block Library)
Read global data, peer cop
(see EcoStruxure™ Control Expert,
Communication, Block Library)
Get remote statistics
Clear remote statistics ( see page 158 )
Peer cop health status (see EcoStruxure™
Control Expert, Communication, Block
Library)
X
Reset optional module
Read CTE (Config extension)
Write CTE (Config extension)
CIP Explicit message
Send Modbus Request
Close Connection Request ( see page 178 )
-
Change Modbus Plus Address
X
-
-
Read / write data ( see page 181 )
Enable / disable HTTP or FTP/TFTP -
-
-
-
-
-
X
X
X
X
X
X
X
X
Modbus Plus TCP/IP
Ethernet
X
X
-
X
X
-
X
X
-
X
X
X
-
X
X
-
X
X
X
-
-
X
-
-
X
X
-
-
-
-
-
-
-
-
-
-
X
X
SY/MAX
Ethernet
-
-
-
X
-
-
-
-
-
-
-
-
-
-
-
-
-
-
where:
X indicates
- indicates
Yes
No
33002479 10/2019
139
Transferring Data Using Communication Blocks
Network Control Block Structures
Summary
The structure of the MBP_MSTR control block varies according to the type of network you are using.
Structures for Modbus Plus, TCP/IP Ethernet, and SyMax Ethernet are described below.
Control Block for Modbus Plus
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Contents
Indicates an operation that is valid for Modbus Plus
Indicates the error status
Indicates the length, i.e., the number of data units transferred (max. 100)
Indicates MSTR operation-dependent information
Routing register 1: used to specify a destination node during network transfer (routing path addresses one of five)
Most significant byte: source node address, i.e., the slot for the Modbus
Plus Network Options Module (NOM)
When using the Modbus Plus Port on the CPU, this byte must be set to 0
(regardless of the CPU slot).
Least significant byte: destination node address, i.e., a value that represents a direct or a bridge address. If there is no bridge, this value contains the destination node address. If there is a bridge, this value contains the address of the bridge.
If the NOM is inserted in slot 7 on the module rack, the most significant byte of routing register 1 looks as follows (value 0x0706):
CONTROL[6]
CONTROL[7]
CONTROL[8]
CONTROL[9]
Most significant byte Slots 1 ... 16
Least significant byte Destination address (binary value between 1 and 64
(normal) or 65 to 255 (extended))
Routing register 2, the destination node address (further bridge or Modbus
Plus modules). If addressing in the previous routing register has finished, the value is set to 0.
Routing register 3, similar to routing register 2
Routing register 4, similar to routing register 2 (see Routing Register 2)
Routing register 5, similar to routing register 2 (see Routing Register 2)
140
33002479 10/2019
Transferring Data Using Communication Blocks
Control Block for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Contents
Indicates an operation that is valid for TCP/IP
Indicates the error status
Indicates the length, i.e., the number of data units transferred (max. 100)
Indicates MSTR operation-dependent information
Routing register: used to specify a destination node during network transfer
Most significant byte: source node address, i.e., the NOE slot for the NOE module
When using an integrated Ethernet on the CPU, this byte must be set to
254 (FE hex) regardless of the CPU slot.
Least significant byte: destination node address, i.e, a value that represents a direct or bridge address. If there is no bridge the value in the least significant byte is set to 0. If there is a bridge, this value contains the
MBP for the Ethernet mapping index (MET).
If the NOE is inserted in slot 7 on the module rack and the Ethernet mapping index (MET) is 6, the routing register looks as follows (value
0x0706):
CONTROL[6]
CONTROL[7]
CONTROL[8]
CONTROL[9]
Most significant byte Slots 1 ... 16
Least significant byte MBP on Ethernet Transporter (MET) mapping index
Byte 4, MSB of the 32-bit destination IP address
Byte 3 of the 32-bit destination IP address
Byte 2 of the 32-bit destination IP address
Byte 1, LSB of the 32-bit destination IP address
CONTROL[10] Indicates MSTR operation-dependent information
CONTROL[11] Indicates MSTR operation-dependent information
NOTE: CONTROL[10] and CONTROL[11] are used when configuring the MBP_MSTR block for a
Read/Write Data operation (function code 23).
33002479 10/2019
141
Transferring Data Using Communication Blocks
Control Block for SY/MAX Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Contents
Indicates an operation that is valid for SY/MAX
Indicates the error status
Indicates the length, i.e., the number of registers transferred (max. 100)
Indicates MSTR operation-dependent information
Routing register: used to specify a destination node during network transfer
Most significant byte: source node address, ie.e, the slot for the NOE module
Least significant byte: destination node address, i.e, a value that represents a direct or bridge address. If there is no bridge the value in the least significant byte is set to 0. If there is a bridge, this value contains the
MBP for the Ethernet mapping index (MET).
If NOM is inserted in slot 7 on the module rack and the Ethernet mapping index (MET) is 6, the routing register looks as follows (value 0x0706):
CONTROL[6]
CONTROL[7]
Most significant byte Slots 1 ... 16
Least significant byte MBP on Ethernet Transporter (MET) mapping index
Destination drop number (or set to FF hex)
Terminator (set to FF hex)
142
33002479 10/2019
Transferring Data Using Communication Blocks
Modbus Plus, SY/MAX, and Ethernet TCP/IP Error Codes
Form of the Function Error Code
Function error codes for Modbus Plus and SY/MAX Ethernet transactions appear as Mmss, where:
M is the high code
m is the low code ss is a subcode
Modbus Plus and SY/MAX Ethernet Network Errors
Hexadecimal error codes for Modbus Plus and SY/MAX Ethernet:
2003
2004
2005
2006
2007
2008
2009
200A
200C
200D
200E
Hex. Error Code Description
1001 Abort by user
2001
2002
An operation type that is not supported has been specified in the control block
One or more control block parameters were modified while the MSTR element was active (this only applies to operations which require several cycles for completion). Control block parameters my only be modified in inactive MSTR components.
30ss
4001
5001
6mss
Invalid value in the length field of the control block
Invalid value in the offset field of the control block
Invalid value in the length and offset fields of the control block
Unauthorized data field on slave
Unauthorized network field on slave
Unauthorized network routing path on slave
Routing path equivalent to their own address
Attempt to get more global data words than available
Bad pattern for change address request
Bad address for change address request
The control block is not assigned, or parts of the control block are located outside of the %MW (4x) range.
Exceptional response by Modbus slave ( see page 146 )
Inconsistent response by Modbus slave
Inconsistent response by the network
Routing path error ( see page 146 )
The subfield m shows where the error occurred (a 0 value means local node, 2 means 2nd device in route, etc).
33002479 10/2019
143
Transferring Data Using Communication Blocks
TCP/IP Ethernet Network Errors
Hexadecimal error codes for TCP/IP Ethernet:
5029
502A
502B
502C
502D
502E
502F
5038
5039
503A
503B
503C
503D
5030
5031
5032
5033
5034
5035
5036
5037
Hex. Error Code Meaning
5004 Interrupted system call
5005
5006
I/O error
No such address
5009
500C
500D
5011
Socket descriptor is invalid
Not enough memory
Permission denied
Entry exists
5016
5017
5020
5028
Argument is invalid
Internal table has run out of space
Connection is broken
Destination address required
Protocol wrong type for socket
Protocol not available
Protocol not supported
Socket type not supported
Operation not supported on a socket
Protocol family not supported
Address family not supported
Address already in use
Cannot assign requested address
Socket operation on a non-socket
Network is unreachable
Network dropped connection on reset
Network caused connection abort
Connection reset by peer
No buffer space available
Socket already connected
Socket not connected
Cannot send after socket shutdown
Too many references, cannot splice
Connection timed out (see note below)
Connection refused
144
33002479 10/2019
Transferring Data Using Communication Blocks
504B
5050
5051
5052
5053
5054
5055
5044
5045
5046
5047
5048
5049
504A
Hex. Error Code Meaning
503E
503F
Network down
Text file busy
5040
5041
5042
5043
Too many levels of links
No route to host
Block device required
Host is down
Operation now in progress
Operation already in progress
Operation would block
Function not implemented
Hardware length is invalid
Route specified cannot be found
Collision in select call: these conditions have already been selected by another task
5056
5057
Task ID is invalid
No network resource
Length error
Addressing error
Application error
Client in bad state for request
No remote resource -- may indicate no path to remote device (see note below)
Non-operational TCP connection
Incoherent configuration
NOTE:
Error code 5055 can occur before a 503C error.
No remote device takes precedence over a timeout.
33002479 10/2019
145
Transferring Data Using Communication Blocks ss Hexadecimal Value in 30ss Error Code ss hexadecimal value in 30ss error code:
05
06
07 ss Hex. Value
01
02
03
Description
Slave does not support requested operation
Non-existing slave registers were requested
An unauthorized data value was requested
Slave has accepted a lengthy program command
Function cannot currently be carried out: lengthy command running
Slave has rejected lengthy program command ss Hexadecimal Value in 6mss Error Code
NOTE: Subfield m in error code 6mss is an Index in the routing information that shows where an error has been detected (a 0 value indicates the local node, 2 means the second device in the route, etc.).
The ss subfield in error code 6mss is as follows:
08
10
20
40
80
F001
04
05
06
07 ss Hex. Value
01
02
03
Description
No response reception
Access to program denied
Node out of service and unable to communicate
Unusual response received
Router-node data path busy
Slave out of order
Wrong destination address
Unauthorized node type in routing path
Slave has rejected the command
Slave has lost an activated transaction
Unexpected master output path received
Unexpected response received
Wrong destination node was specified for the MSTR operation
146
33002479 10/2019
Transferring Data Using Communication Blocks
CTE Error Codes for SY/MAX and TCP/IP Ethernet
CTE Error Codes for SY/MAX and TCP/IP Ethernet
The following error codes are displayed in the CONTROL[1] register of the control block, if there is a problem with the Ethernet configuration extension table (CTE) in your program configuration.
CTE error codes for SY/MAX and TCP/IP Ethernet:
Description Hex. Error
Code
7001
7002
7003
7004
7005
There is no Ethernet configuration extension.
The CTE is not available for access.
The offset is not valid.
Offset + length are not valid.
Bad data field in the CTE.
33002479 10/2019
147
Transferring Data Using Communication Blocks
SY/MAX-Specific Error Codes
SY/MAX-Specific Error Codes
When utilizing SY/MAX Ethernet, three additional types of errors may appear in the CONTROL[1] register of the control block ().
The error codes have the following meaning:
71xx Error: Errors found by the SY/MAX remote device
72xx Error: Errors found by the server
73xx Error: Errors found by the Quantum translator
SY/MAX-Specific Hexadecimal Error Codes
SY/MAX-specific hexadecimal error codes:
Description Hex. Error
Code
7101
7103
7109
F710
7110
7111
7113
711D
7149
714B
7101
7203
7209
F720
7210
7211
7213
721D
7249
724B
Invalid opcode found by the SY/MAX remote device
Invalid address found by the SY/MAX remote device
Attempt to write to a write protected register found by the SY/MAX remote device
Receiver overflow found by the SY/MAX remote device
Invalid length found by the SY/MAX remote device
Remote device not active, no connection (occurs when retry attempts and time-out have been used up), found by the SY/MAX remote device
Invalid parameter in a read operation found by the SY/MAX remote device
Invalid route found by the SY/MAX remote device
Invalid parameter in a write operation found by the SY/MAX remote device
Invalid drop number found by the SY/MAX remote device
Invalid opcode found by the SY/MAX server
Invalid address found by the SY/MAX server
Attempt to write to a write protected register found by the SY/MAX server
Receiver overflow found by the SY/MAX server
Invalid length found by the SY/MAX server
Remote device not active, no connection (occurs when retry attempts and time-out have been used up), found by the SY/MAX server
Invalid parameter in a read operation found by the SY/MAX server
Invalid route found by the SY/MAX server
Invalid parameter in a write operation found by the SY/MAX server
Invalid drop number found by the SY/MAX server
148
33002479 10/2019
Transferring Data Using Communication Blocks
Hex. Error
Code
7301
7303
7309
731D
734B
Description
Invalid opcode in an MSTR block request from the Quantum translator
Read/Write QSE module status (200 route address out of range)
Attempt to write to a write protected register when a status write is carried out (200 route)
Invalid route found by the Quantum translator.
Valid routes:
dest_drop, 0xFF
200, dest_drop, 0xFF
100+drop, dest_drop, 0xFF
All other routing values produce an error
One of the following errors occurred:
No CTE (configuration extension table) has been configured
No CTE table entry has been made for the QSE model slot number
No valid drop has been specified
The QSE module has not been reset after the creation of the CTE.
Note: After writing and configuring the CTE and downloading to the QSE module, the QSE module must be reset for the modifications to become effective.
When using an MSTR instruction no valid slot or drop has been specified
33002479 10/2019
149
Transferring Data Using Communication Blocks
Read Data
Description
A read operation transfers data from a specified slave source device to a master destination device on the network. The operation uses a master transaction path, and may require several cycles to complete. To program an MBP_MSTR
block to perform a write operation, use function code 2
see page 139
.
NOTE: Do not attempt to program an MBP_MSTR to read to its own station address. This action causes the function block to generate an error in the CONTROL[2] register of the control block
see page 140
.
You can perform a read operation on a nonexistent slave register. The slave detects and logs the status, which can last for several cycles.
NOTE: For Quantum PLC communication with a Premium/Atrium PLC, confirm that the addressing is made with an offset of 1. In order to access an address object n of a Premium PLC, confirm that the communication function of the Quantum PLC uses the n+1 address. IEC addressing starts at
0, and Modbus addressing starts at 1.
Network Implementation
The read operation can be performed on Modbus Plus, TCP/IP Ethernet, and SY/MAX Ethernet networks.
Control Block Usage for Modbus Plus
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
...
CONTROL[9]
Meaning
2 = read data
Indicates the error status.
Number of registers to be read from the slave.
Determines the %MW starting register in the slave from which the data is read, e.g.,
1 = %MW1, 49 = %MW49.
Routing register 1 is used to specify the address (routing path address 1 of 5) of the node during a network transfer.
The last byte in the routing path that is not 0 is the destination node.
150
33002479 10/2019
Transferring Data Using Communication Blocks
Control Block Usage for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
2 = read data
Indicates the error status.
Number of addresses to be read from the slave.
Determines the %MW starting register in the slave from which the data is read, e.g., 1 = %MW1, 49 = %MW49.
Routing register
most significant byte: network adapter module slot
least significant byte: MBP on Ethernet Transporter (MET) mapping index
Each address contains 1 byte of the 32-bit IP address, where the MSB is in
CONTROL[6] and the LSB is in CONTROL[9].
Control Block Usage for SY/MAX Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
2 = read data
Indicates the error status.
Number of addresses to be read from the slave.
Determines the %MW starting register in the slave to which the data is written, e.g., 1 = %MW1, 49 = %MW49.
Routing register:
most significant byte: network adapter module slot
least significant byte: destination drop number terminator: FF hex
33002479 10/2019
151
Transferring Data Using Communication Blocks
Write Data
Description
A write operation transfers data from a master source device to a specified slave destination device on the network. The operation uses a master transaction path, and may require several cycles to complete. To program an MBP_MSTR
block to perform a write operation, use function code 1
see page 139
.
NOTE: Do not attempt to program an MBP_MSTR to write to its own drop address. This action causes the function block to generate an error in the CONTROL[2] register of the control block
see page 140
.
You can perform a write operation to a nonexistent slave register. The slave detects and logs the status, which can last for several cycles.
NOTE: For Quantum PLC communication with a Premium/Atrium PLC, confirm that the addressing is made with an offset of 1. In order to access an address object n of a Premium PLC, confirm that the communication function of the Quantum PLC uses the n+1 address. IEC addressing starts at
0, and Modbus addressing starts at 1.
Network Implementation
The write operation can be performed on Modbus Plus, TCP/IP Ethernet, and SY/MAX Ethernet networks.
Control Block Usage for Modbus Plus
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
...
CONTROL[9]
Meaning
1 = write data
Indicates the error status.
Number of addresses sent to the slave.
Determines the %MW starting register in the slave to which the data is written, e.g. 1 = %MW1, 49 = %MW49.
Routing register 1 is used to specify the address (routing path address 1 of 5) of the node during a network transfer.
The last byte in the routing path that is not 0 is the destination node.
152
33002479 10/2019
Transferring Data Using Communication Blocks
Control Block Usage for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
1 = write data
Indicates the error status.
Number of addresses sent to the slave.
Determines the %MW start address of the slave to which the data is written.
Routing register:
most significant byte: network adapter module slot
least significant byte: MBP on Ethernet transporter (MET) mapping index
Each address contains 1 byte of the 32-bit IP address.
Control Block Usage for SY/MAX Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
1 = write data
Indicates the error status.
Number of addresses sent to the slave.
Determines the %MW starting register in the slave to which the data is written, e.g., 1 = %MW1, 49 = %MW49.
Routing register:
most significant byte: network adapter module slot
least significant byte: destination drop number terminator: FF hex
33002479 10/2019
153
Transferring Data Using Communication Blocks
Get Local Statistics
Description
A Get Local Statistics operation reads the data from the local node in one cycle and does not require a master transaction path.To program an MBP_MSTR block to
Get Local Statistics , use function code 3
see page 139
.
Network Implementation
A Get Local Statistics operation can be performed on Modbus Plus and TCP/IP Ethernet networks
see page 159
.
Control Block Usage for Modbus Plus
Register Meaning
CONTROL[1] 3 = get local statistics
CONTROL[2] Indicates the error status
CONTROL[3] Number of addresses to be read from local statistics (1 ... 54)
Note: The size of databuf must be at least the size of this entry.
CONTROL[4] First address from which the statistics table must be read (Reg1=0)
CONTROL[5] Routing register 1 is used to specify the address (routing path address 1 of
5) of the node during a network transfer.
The last byte in the routing path that is not 0 is the destination mode.
Control Block Usage for TCP/IP Ethernet
Register Meaning
CONTROL[1] 3 = get local statistics
CONTROL[2] Indicates the error status
CONTROL[3] Number of addresses to be read from local statistics (1 ... 38)
Note: The size of databuf must be the size of this entry.
CONTROL[4] First address from which the statistics table must be read (Reg1=0)
CONTROL[5] Routing register
Most significant byte: Network adapter module slot
CONTROL[6]
...
CONTROL[9]
Not used
154
33002479 10/2019
Transferring Data Using Communication Blocks
Clear Local Statistics
Description
A clear local statistics operation clears the values from words 13 ... 22 in the statistics table of the local node. The operation is carried out in one cycle and does not require a master transaction path. To program an MBP_MSTR
block to clear local statistics, use function code 4 (
see page 139
.
Network Implementation
A clear local statistics operation can be performed on Modbus Plus and TCP/IP Ethernet networks
see page 159
.
Control Block Usage for Modbus Plus
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
Meaning
4 = clear local statistics
Indicates the error status
Reserved
Reserved
Routing register 1 is used to specify the address (routing path address 1 of
5) of the node during a network transfer.
The last byte in the routing path that is not 0 is the destination mode.
Control Block Usage for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
4 = clear local statistics
Indicates the error status
Reserved
Reserved
Routing register
Most significant byte: network adapter module slot
Reserved
33002479 10/2019
155
Transferring Data Using Communication Blocks
Get Remote Statistics
Description
A get remote statistics operation can be used to read data from remote nodes on the network. With each query, the remote communications processor supplies a complete table of statistics even if the query does not refer to the entire table. It then copies only the words that you queried into identified $MW addresses.
An operation can take several cycles to complete; it does not require a master data transaction path. To program an MBP_MSTR
block to get remote statistics, use function code 7 (
see page 139
.
Network Implementation
A get remote statistics operation can be performed on Modbus Plus and TCP/IP Ethernet networks.
Control Block Usage for Modbus Plus
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
...
CONTROL[9]
Meaning
7 = get remote statistics
Indicates the error status
Number of addresses to be read from the statistics data field (1 ... 54).
Note: The size of databuf must be at least the size of this entry.
First address from which the node statistics must be read. The number of available statistics registers cannot be exceeded.
Routing address 1 ... 5 of the node.
The last byte in the routing path that is not 0 is the destination node.
156
33002479 10/2019
Transferring Data Using Communication Blocks
Control Block Usage for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
7 = get remote statistics
Indicates the error status
Number of addresses to be read from the statistics data field (1 ... 38).
Note: The size of databuf must be at least the size of this entry.
First address from which the node statistics must be read. The number of available statistics registers cannot be exceeded.
Routing register
Most significant byte: network adapter module slot
Each address contains 1 byte of the 32-bit IP address, where the value in
CONTROL[6] is the MSB and the value in CONTROL[9] is the LSB.
33002479 10/2019
157
Transferring Data Using Communication Blocks
Clear Remote Statistics
Description
A clear remote statistics operation clears remote-node values from words 13 ... 22 in the statistics table of the local node. It uses a master transaction path and may require several cycles to complete. To program an MBP_MSTR block to perform a clear remote statistics operation, use
see page 139
Network Implementation
A clear remote statistics operation can be performed on Modbus Plus and TCP/IP Ethernet networks
see page 159
.
Control Block Usage for Modbus Plus
Register Meaning
CONTROL[1] 8 = clear remote statistics
CONTROL[2] Indicates the error status
CONTROL[3] Reserved
CONTROL[4]
CONTROL[5]
...
CONTROL[9]
Reserved
Routing register 1 is used to specify the address (routing path address 1 of
5) of the destination node during a network transfer.
The last byte in the routing path that is not 0 is the destination mode.
Control Block Usage for TCP/IP Ethernet
Register Meaning
CONTROL[1] 8 = clear remote statistics
CONTROL[2] Indicates the error status
CONTROL[3] Reserved
CONTROL[4] Reserved
CONTROL[5] Routing Register
Most significant byte: network adapter module slot
CONTROL[6]
...
CONTROL[9]
Each address contains one byte of the 32-bit IP address, where the MSB is in CONTROL[6] and the LSB is in CONTROL[9].
158
33002479 10/2019
Transferring Data Using Communication Blocks
TCP/IP Ethernet Network Statistics
03
04 and 05
06 and 07
08 and 09
10 and 11
12 and 13
14 and 15
16 and 17
18 and 19
20 and 21
22 and 23
24 and 25
26 and 27
28 and 29
30 and 31
32 and 33
34 and 35
36 and 37
TCP/IP Ethernet Network Statistics
A TCP/IP Ethernet module replies to local and remote statistics commands from the MBP_MSTR block with the the contents of the databuf array (see the information in the table below):
Word
00 to 02
Meaning
MAC address e.g. MAC address 00 00 54 00 12 34 is displayed as follows:
Word
00
01
02
Board status (refer to the following table)
Number of receiver interrupts
Number of transfer interrupts
Transfer timeout error count
Collision detection error count
Omitted packets
Memory error count
Number of restarts performed by the driver
Receive framing error count
Overflow error count receiver
Receive CRC error counter
Receive buffer error counter
Transfer buffer error counter
Transfer bin underflow counter
Late collision counter
Lost carrier counter
Number of retries
IP address e.g. the IP address 198.202.137.113 (or
C6 CA 89 71) is represented as follows:
Word
36
37
Contents
00 00
54 00
12 34
Contents
89 71
C6 CA
33002479 10/2019
159
Transferring Data Using Communication Blocks
Board Status Word Bit Definition
NOTE: It is best to view the board status word in binary format.
The following table describes the bit definitions of the board status word:
140 NOE 771
140 NOE 771 x x
1, versions 2.0, 3.0, 3.1, 3.3 and 3.6 or higher
0, versions 3.0, 3.3 and 3.4 or higher
2
1
0
Bit #
15
14
13
12
11 ... 8
7 ... 4
3
Definition
0 = Link LED off 1 = Link LED on
0 = Appl LED off 1 = Appl LED on
0 = twisted pair 1 = fiber
0 = 10 Mbit 1 = 100 Mbit
(Reserved)
Module type (see table, below)
(Reserved)
0 = half duplex 1 = full duplex
0 = not configured 1 = configured
0 = not running 1 = running
NOTE: Bits are numbered from right to left, starting with bit 0 (low bit). For example, PLC running
= 0000 0000 0000 0001 and LED connection = 1000 0000 0000 0000.
The following table describes the word bit definitions for board status for the:
140 NOE 771
140 NOE 771
140 CPU 651 x x x
1, version 3.5
0, versions 1.02 and 2.0
0
7
6
9
8
Bit #
15 ... 12
11
10
5
4
3 ... 0
Definition
Module type (see table below)
(Reserved)
0 = half duplex 1 = full duplex
0 = not configured 1 = configured
0 = PLC not running 1 = PLC/NOE running
0 = Link LED off 1 = Link LED on
0 = Appl LED off 1 = Appl LED on
0 = twisted pair 1 = fiber
0 = 10 Mbit 1 = 100 Mbit
(Reserved)
160
33002479 10/2019
Transferring Data Using Communication Blocks
NOTE: Bits are counted from right to left, starting with bit 0 (low bit). For example, PLC running =
0x0100, Application LED = 0x0040, and LED Connection = 0x0080.
Board Status Word Bit Definition by Module Type
The following table describes the values of the module types:
Module Type
8
9
6
7
10
11
12
13 ... 15
4
5
2
3
0
1
Value of Bits 7...4 or 15...12
Note: See the previous tables for the bit range that applies to your module’s software version.
NOE 2x1
ENT
M1E
NOE 771 00
ETY
CIP
(reserved)
140 CPU 651 x0
(reserved)
(reserved)
NOE 771 10
NOE 771 01
NOE 771 11
(reserved)
33002479 10/2019
161
Transferring Data Using Communication Blocks
TCP/IP Ethernet Error Codes
TCP/IP Ethernet Error Codes
An error in an MSTR routine via TCP/IP Ethernet may produce one of the following errors in the
MSTR control block:
The error code appears as Mmss, where:
M is the high code
m is the low code ss is a subcode
Hexadecimal Error Codes TCP/IP Ethernet
Hexadecimal error codes TCP/IP Ethernet:
Meaning Hex. Error
Code
1001
2001
2002
2003
2004
2005
2006
2008
200E
3000
30ss
4001
Abort by user
An operation type that is not supported has been specified in the control block
One or more control block parameters were modified while the MSTR element was active (this only applies to operations which require several cycles for completion). Control block parameters my only be modified in inactive MSTR components.
Invalid value in the length field of the control block
Invalid value in the offset field of the control block
Invalid value in the length and offset fields of the control block
Unauthorized data field on slave
Unauthorized network routing path on slave
The control block is not assigned, or parts of the control block are located outside of the %MW (4x) range.
Generic Modbus failure code
Exceptional response by Modbus slave ( see page 163 )
Inconsistent response by Modbus slave
162
33002479 10/2019
Transferring Data Using Communication Blocks ss Hexadecimal Value in 30ss Error Code ss hexadecimal value in 30ss error code:
05
06
07 ss hex. Value Meaning
01 Slave does not support requested operation
02
03
Non-existing slave registers were requested
An unauthorized data value was requested
Slave has accepted a lengthy program command
Function cannot currently be carried out: lengthy command running
Slave has rejected lengthy program command
Hexadecimal Error Codes TCP/IP Ethernet Network
An error on the TCP/IP Ethernet network itself may produce one of the following errors in the
CONTROL[1] register of the control block.
Hexadecimal error codes TCP/IP Ethernet network:
5026
5027
5028
5029
502A
5011
5016
5017
5020
5023
5024
5025
Hex. Error
Code
5004
5005
5006
5009
500C
500D
Meaning
Interrupted system invocation
I/O error
No such address
The socket descriptor is not valid
Not enough storage space
Authorization denied
Entry exists
An argument is not valid
An internal table has no more space
There is interference on the connection
This operation was blocked and the socket is non-blocking
The socket is non-blocking and the connection cannot be closed down
The socket is non-blocking and a previous connection attempt has not been concluded
Socket operation on a non-socket
The destination address is not valid
Message too long
Wrong type of protocol for the socket
Protocol not available
33002479 10/2019
163
Transferring Data Using Communication Blocks
504B
5050
5051
5052
5053
5054
5037
5038
5039
503A
503B
503C
503D
5040
5041
5042
5046
5047
5048
5049
504A
5031
5032
5033
5034
5035
5036
Hex. Error
Code
502B
502C
502D
502E
502F
5030
Meaning
Protocol not supported
Socket type not supported
Operation not supported at socket
Protocol family not supported
Address family not supported
Address is already in use
Address not available
Network is out of order
Network cannot be reached
Network shut down the connection during reset
The connection was terminated by the peer
The connection was reset by the peer
An internal buffer is required, but cannot be assigned
The socket is already connected
The socket is not connected
Cannot transmit after the socket has been shut off
Too many references; cannot splice
Connection timed out
The connection attempt was denied
Host is out of order
The destination host could not be reached from this node
Directory not empty
NI_INIT returned -1
The MTU is not valid
The hardware length is not valid
The route specified cannot be found
Collision when invoking Select; these conditions have already been selected by another job
The job ID is not valid
No Network Resource
Length Error
Addressing Error
Application Error
Client cannot process request
164
33002479 10/2019
Hex. Error
Code
5055
5056
5057
6003
F001
F002
Meaning
No Network Resource
Non-Operational TCP connection
Incoherent configuration
FIN or RST not expected
In reset mode
Component not fully initialized
Transferring Data Using Communication Blocks
33002479 10/2019
165
Transferring Data Using Communication Blocks
Reset Optional Module
Description
A reset optional module operation causes a Quantum NOE Ethernet communications module or the Ethernet port on a 140CPU65150/60 CPU module to enter a cycle that resets its working environment. To program an MBP_MSTR block to perform a reset option module operation, use function code 10
see page 139
.
Network Implementation
A reset optional module operation can be performed on TCP/IP Ethernet
SY/MAX Ethernet networks.
see page 159
Control Block Usage for TCP/IP Ethernet
Register Meaning
CONTROL[1] 10 = reset optional module
CONTROL[2] Indicates the error status
CONTROL[3] No significance
CONTROL[4] No significance
CONTROL[5]
Routing register ( see page 141 )
CONTROL[6]
...
CONTROL[9]
No significance
Control Block Usage for SY/MAX Ethernet ( CONTROL )
Register Meaning
CONTROL[1] 10 = reset optional module
CONTROL[2] Indicates the error status
CONTROL[3] No significance
CONTROL[4] No significance
CONTROL[5]
Routing register ( see page 142 )
CONTROL[6]
...
CONTROL[9]
No significance
166
33002479 10/2019
Transferring Data Using Communication Blocks
Read CTE
Description
A read CTE operation reads a specified number of bytes from the Ethernet configuration extension table in the specified buffer of PLC memory. These bytes start with a byte offset at the CTE table start. The CTE table contents are displayed in the DATABUF output parameter
see page 139
.
see page 138
program an MBP_MSTR block to perform a clear remote statistics operation, use function code 11
Network Implementation
A read CTE operation can be performed on TCP/IP Ethernet and SY/MAX Ethernet networks.
Control Block Usage for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]...
CONTROL[9]
Meaning
11 = read CTE
Indicates the error status
The length setting: a value from 12 to 37
No significance
Routing register
Least significant byte = mapping index
Either a value displayed in the byte of the register or is not used.
or Most significant byte = network adapter module slot
No significance
Control Block Usage for SY/MAX Ethernet
Register Meaning
CONTROL[1] 11 = read CTE
CONTROL[2] Indicates the error status
CONTROL[3] Number of words transferred
CONTROL[4]
CONTROL[6]
...
CONTROL[9]
Byte offset in the PLC register structure, specifying from where the CTE bytes are read
CONTROL[5] Routing register
MSB: slot of the NOE module
Terminator: FF hex
33002479 10/2019
167
Transferring Data Using Communication Blocks
CTE Indicator Implementation ( DATABUF )
The values in the CTE table are displayed in the DATABUF output when a CTE read operation is implemented. The registers display the following CTE data:
CTE indicator implementation ( DATABUF ):
Parameter
Frame type
IP address
Lower netmask
Gateway
Register
DATABUF[0]
DATABUF[1]
DATABUF[2]
DATABUF[3]
DATABUF[4]
DATABUF[5]
DATABUF[6]
DATABUF[7]
DATABUF[8]
Contents
1 = 802.3
2 = Ethernet
First byte of the IP address
Second byte of the IP address
Third byte of the IP address
Fourth byte of the IP address
Most significant word
Least significant word
First byte of the gateway
Second byte of the gateway
DATABUF[9] Third byte of the gateway
DATABUF[10] Fourth byte of the gateway
168
33002479 10/2019
Transferring Data Using Communication Blocks
Write CTE
Description
A write CTE operation writes the CTE configuration table from the specified data ( DATABUF ) to a specified Ethernet configuration extension table or to a specific slot. To program an MBP_MSTR
block to perform a write CTE operation, use function code 12 (
see page 139
Network Implementation
A write CTE operation can be performed on TCP/IP Ethernet
Ethernet networks.
see page 159
and SY/MAX
Control Block Usage for TCP/IP Ethernet
Register Meaning
CONTROL[1] 12 = write CTE
CONTROL[2] Indicates the error status
CONTROL[3] The length setting: a value from 12 to 37.
CONTROL[4]
CONTROL[6]
...
CONTROL[9]
No significance
CONTROL[5] Routing register
Least significant byte = mapping index
Either a value displayed in the byte of the address or is not used.
or
Most significant byte = network adapter module slot
No significance
33002479 10/2019
169
Transferring Data Using Communication Blocks
Control Block Usage for SY/MAX Ethernet
Register Meaning
CONTROL[1] 12 = Write CTE (Config extension table)
CONTROL[2] Indicates the error status
CONTROL[3] Number of words transferred
CONTROL[4] Byte offset in the PLC address structure specifying where the CTE bytes are written
CONTROL[5] Routing register
Most significant byte = NOE module slot
Least significant byte = Destination drop number
CONTROL[6] Terminator: FF hex
CONTROL[7]
...
CONTROL[9]
No significance
CTE Indicator Implementation ( DATABUF )
The values in the Ethernet configuration extension table are displayed in the DATABUF output field when a write CTE operation is implemented. The registers are used to transfer the following CTE data:
CTE indicator implementation ( DATABUF ):
Parameter
Frame type
IP address
Lower netmask
Gateway
Register
DATABUF[0]
DATABUF[1]
DATABUF[2]
DATABUF[3]
DATABUF[4]
DATABUF[5]
DATABUF[6]
DATABUF[7]
DATABUF[8]
Contents
1 = 802.3
2 = Ethernet
First byte of the IP address
Second byte of the IP address
Third byte of the IP address
Fourth byte of the IP address
Most significant word
Least significant word
First byte of the gateway
Second byte of the gateway
DATABUF[9] Third byte of the gateway
DATABUF[10] Fourth byte of the gateway
170
33002479 10/2019
Transferring Data Using Communication Blocks
Send Email
Description
The electronic mail notification service allows controller-based projects to report alarms or events.
The controller monitors the system and dynamically creates an electronic mail message, which alerts local or remote users.
A user-defined event or condition triggers the MSTR block to create a message. Each message uses one of three user-defined headers. Each message sent from the controller can contain text and variable information (with a maximum of 238 bytes).
The project selects the appropriate header. Each header contains:
sender name
list of recipients subject
To program an MBP_MSTR block to send email, use function code 13 (
see page 139
Network Implementation
A send email operation can be performed on a TCP/IP Ethernet network.
Control Block Usage for TCP/IP Ethernet
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Meaning
13 = send Email
Indicates the email-specific error codes (see EcoStruxure™ Control
Expert, I/O Management, Block Library)
Number of words transferred
Not used
High byte: slot address of the NOE module or 0xFE for the 140 CPU 651 60
Low byte: always 0
Not used
33002479 10/2019
171
Transferring Data Using Communication Blocks
DATABUF Parameter Description
Register
DATABUF 1
DATABUF 2
...
DATABUF 119
Contents
The mail header is the least significant byte with a value of 1, 2, or
3.
The most significant byte contains the number ( the subject, a value between 0 and 238.
n ) of characters in
The data (in ASCII format) that will be copied into the Email message.
The first n characters are added to the configured Email subject.
The remaining characters (2 * body, where N
N -2 n ) are part of the message
is the number of words transferred.
172
33002479 10/2019
Transferring Data Using Communication Blocks
Send Modbus Request
At a Glance
Use MSTR operation 15 to send generic Modbus requests on the network.
NOTE: This operation is not available on Modbus Plus ports (embedded port on CPU or NOM modules) and the embedded Ethernet port on a CPU.
Block Operation
The MBP_MSTR block can send requests and receive responses up to 253 bytes long.
For the operation, refer to Block Operation
see page 136
When the ENABLE input pin is turned ON, operation 15 begins.
If the ABORT input pin is turned ON or if the ENABLE input pin is turned OFF, the operation ends.
The ACTIVE output pin is ON during the operation.
The ERROR output pin turns ON if the operation aborts without success.
The SUCCESS output pin turns ON if the operation completes with success.
The CONTROL and DATABUF output pins define the operation (refer to the Control Block
see page 173
and Data Buffer
see page 174
).
EN and ENO can be configured as additional parameters.
Control Block
The format of the Control block is described in the following table:
Word
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
CONTROL[5]
CONTROL[6]
CONTROL[7]
CONTROL[8
CONTROL[9]
Description
15 = Send Modbus Request
Indicates detected error status
DATABUF length (WORDs)
Offset for the beginning of the response in the DATABUF (WORDs).
NOTE: To avoid overwriting the request, the Response Offset value multiplied by 2 must be greater than the Request Length
(CONTROL[10]).
Routing register:
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index (also known as Unit ID)
Byte 4 of the IP address (MSB)
Byte 3 of the IP address
Byte 2 of the IP address
Byte 1 of the IP address (LSB)
33002479 10/2019
173
Transferring Data Using Communication Blocks
Word
CONTROL[10]
CONTROL[11]
Description
Length of the DATABUF Request data (bytes)
Length of the DATABUF Response received (bytes)
NOTE: This is read only, it is set by option module after operation completion.
Data Buffer
The MODBUS protocol defines a simple protocol data unit (PDU) independent of the underlying communication layers.
The data buffer (DATABUF) consists of contiguous registers that include both the Modbus Request
PDU and the Modbus Response PDU:
DATABUF
Data Buffer Length is set in the CONTROL[3] word.
Modbus Request PDU:
Data Request Length is set in the CONTROL[10] word.
Modbus Response PDU:
Data Response Start (
CONTROL[4] word.
Response offset ) is set in the
NOTE: To avoid overwriting the request, the Response Offset value multiplied by 2 must be greater than the Request Length
(CONTROL[10]).
Data Response Length is set in the CONTROL[11] word.
CAUTION
LOSS OF DATA
Verify that the Response Offset is greater than the Data Request Length .
Failure to follow these instructions can result in injury or equipment damage.
NOTE: Both the Request and Response must be structured in little endian order. Each word of 2 bytes of data in little endian format, where the least significant byte is stored in the smallest memory address.
174
33002479 10/2019
Transferring Data Using Communication Blocks
Modbus Request
The Modbus Request PDU format is:
Byte offset
1
2
Field
Function code
Request data
Data type
BYTE
BYTE area
Description
Modbus function code
This field is function code dependent and contains information such as variable references, variable counts, data offsets, sub-function codes and so on.
Modbus Response
The Modbus Response PDU format is:
Byte offset
1
2
Field Data type
Function code BYTE
Response data BYTE area
Description
Modbus function code
This field is function code dependent and contains information such as variable references, variable counts, data offsets, sub-function codes and so on.
Modbus Exception Response
The Modbus Exception Response PDU format is:
Byte offset
1
2
Field Data type
Function code BYTE
Exception code BYTE
Description
Modbus function code + 80 (hex)
This field is defined in the MODBUS
Application Protocol Specification .
Modbus Specification
The standard Modbus function codes are defined in the MODBUS Application Protocol
Specification , V1.1b, which can be downloaded from www.modbus-ida.org.
33002479 10/2019
175
Transferring Data Using Communication Blocks
Example of a Send Modbus Request
To read 4 contiguous Input registers (Modbus Function code 4) starting at register 100 (64 hex) in a remote device. A Modbus Request has to be sent on the network with the following Modbus
Response.
Request Field Name
Function code
Starting address, High
Starting address, Low
Number of registers, High
Number of registers, Low
Value
04
00
64
00
04
Response Field Name
Function code
Byte count
Register 100 value, High
Register 100 value, Low
Register 101 value, High
Register 101 value, Low
Register 102 value, High
Register 102 value, Low
Register 103 value, High
Register 103 value, Low
03
00
04
01
00
02
00
Value
04
08
00
Using the following CONTROL word values:
CONTROL[1] (MSTR operation) = 15
CONTROL[2] (Error Code) = refer to CONTROL block description (read-only)
CONTROL[3] (DATABUF length) = 11
CONTROL[4] (Response Offset) = 5
CONTROL[5] (Routing Register) = refer to CONTROL block description
CONTROL[6] (IP1) = refer to CONTROL block description
CONTROL[7] (IP1) = refer to CONTROL block description
CONTROL[8] (IP1) = refer to CONTROL block description
CONTROL[9] (IP1) = refer to CONTROL block description
CONTROL[10] (Request Length) = 5
CONTROL[11] (Response Length) = 10
176
33002479 10/2019
Transferring Data Using Communication Blocks
Request the data encoding in the Data Buffer is as follows:
Response
Field
DATABUF[1]
DATABUF[2]
DATABUF[3]
DATABUF[4]
DATABUF[5]
DATABUF[6]
DATABUF[7]
DATABUF[8]
DATABUF[9]
DATABUF[10]
DATABUF[11]
Value (hex) Description
0400 Function code + Starting address, High
6400
0400
Starting address, Low + Number of registers, High
Number of registers, Low + NULL
0000
0000
0408
0001
Null
Null
Function code + Byte count
Register 100 value, High + Register 100 value, Low
0002
0003
0004
0000
Register 101 value, High + Register 101 value, Low
Register 102 value, High + Register 102 value, Low
Register 103 value, High + Register 103 value, Low
Null
33002479 10/2019
177
Transferring Data Using Communication Blocks
Close Connection Request
At a Glance
Use MBP_MSTR operation 16 to close a Modbus TCP/IP connection on the network.
NOTE: This operation is not available on Modbus Plus ports (embedded port on CPU or NOM modules).
Block Operation
The MBP_MSTR block can send requests and receive responses up to 253 bytes long. For block operation, refer to the block description
see page 136
ends.
The ACTIVE output pin is ON during the operation.
:
When the ENABLE input pin is turned ON, operation 15 begins.
If the ABORT input pin is turned ON or if the ENABLE input pin is turned OFF, the operation
The ERROR output pin turns ON if the operation aborts without success.
The SUCCESS output pin turns ON if the operation completes with success.
The CONTROL and DATABUF output pins
see page 138
EN and ENO can be configured as additional parameters.
define the operation.
Control Block
The format of the CONTROL block is described below:
Register
CONTROL[1 ]
CONTROL[2]
CONTROL[3 ]
CONTROL[4 ]
CONTROL[5 ]
CONTROL[6]
CONTROL[7]
CONTROL[8]
CONTROL[9 ]
Function
Operation
Error status
(not used)
(not used)
Routing Register
IP Address
Description
16 = close connection
Indicates detected error status
(see EcoStruxure™ Control Expert, I/O
Management, Block Library) (read only)
–
–
High byte = Ethernet communication module slot
Low byte = MBP on Ethernet transporter (MET) mapping index (also known as Unit ID)
Byte 4 of the IP address (MSB)
Byte 3 of the IP address
Byte 2 of the IP address
Byte 1 of the IP address (LSB)
178
33002479 10/2019
Transferring Data Using Communication Blocks
Change Modbus Plus Address
Description
Use MSTR Operation 17 (Change Modbus Plus Address) to change the Modbus Plus address associated with the embedded Modbus Plus port of the CPU.
On Low End CPUs, this function overrides the address switch (the hardware rotary switch behind the CPU) as long as the CPU is powered on. The address of hardware switch is restored when the
CPU is restarted.
On High End CPUs, a new address set with this function is saved in the configuration table and is restored on subsequent CPUs starts.
Setting an address to a station that is already used by another station on the network disconnects the station already on the network and may cause unpredictable operation on the network.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
Ensure that the Modbus Plus address to be set is not assigned to another station before using
Operation 17.
Failure to follow these instructions can result in injury or equipment damage.
Network Implementation
The Operation 17 can only be performed for a Modbus Plus CPU embedded port. This operation is not available on the Modbus Plus ports of NOM modules.
33002479 10/2019
179
Transferring Data Using Communication Blocks
Control Block
The following table describes the format of the Operation 17 Control Block:
Register
Control[1]
Control[2]
Control[3]
Control[4]
Control[5]
Control[6
Control[7]
Control[8]
Control[9]
Meaning
17 (Change Modbus Plus Address operation)
Detected error status, see Modbus Plus, SY/MAX, and
Ethernet TCP/IP Error Codes ( see page 143 )
16#1234
16#5678
16#00AA
16#00BB
16#00CC
16#00DD
16#00EE
NOTE: The constant values in CONTROL[3] to CONTROL[9] consist of a signature that prevents unintentional use of this operation.
Data Buffer
The following table describes the format of the Operation 17 Data Buffer:
Register
DADABUF[1]
Meaning
Low byte: new address (range: 1 to 64)
180
33002479 10/2019
Transferring Data Using Communication Blocks
Read/Write Data
Introduction
In a single transaction, the MSTR read and write operations can transfer data from a master source device to a specified slave destination device, then transfer data from this specified slave source to the master. It uses a master transaction path and may require several cycles to complete. To program an MBP_MSTR block to perform a combined read/write operation, use function code 23
see page 139
.
The combined read/write operation can be used only with these models:
Quantum: NOE 771 01 (3.0 or later) or NOE 771 11 (3.0 or later)
Momentum: M1E CPU (1.0 or later)
Control Block Usage
Register
CONTROL[1]
CONTROL[2]
CONTROL[3]
CONTROL[4]
Content
23 = read/write data.
Indicates the error status.
Number of registers to be sent to the slave.
CONTROL[5]
CONTROL[6]
...
CONTROL[9]
Specifies the %MW starting register in the slave to which the data will be written, e.g. 1 = %MW1, 49 = %MW49.
Routing register:
Most significant byte: network adapter module slot.
Least significant byte: MBP on Ethernet Transporter (MET) mapping index.
Each address contains 1 byte of the 32-bit IP address, where the MSB is in CONTROL[6] and the LSB is in CONTROL[9].
CONTROL[10] Number of registers to be read from slave.
CONTROL[11] Specifies the %MW starting register in the slave from which the data is read, e.g. 1 = %MW1, 49 = %MW49.
NOTE:
When configuring the MBP_MSTR block for a read/write data operation, note that
The DATABUF output parameter is used to store, in the following sequence, both:
1 the data to be written
2 the data to be read
The size of the DATABUF output parameter must equal the combined size of the data to be written and the data to be read; if the size is smaller, data will be overwritten and may be lost.
Both the CONTROL and DATABUF parameters must be stored at located addresses, for example
%MW addresses.
33002479 10/2019
181
Transferring Data Using Communication Blocks
Enable / Disable HTTP or FTP/TFTP Services
Description
An Enable Disable HTTP or FTP/TFTP Services operation changes the enabled state of the module’s HTTP or FTP/TFTP services.
Network Implementation
An Enable Disable HTTP or FTP/TFTP Services operation can be performed on TCP/IP
see page 159
Control Block Usage for TCP/IP Ethernet
When HTTP or FTP/TFTP has been enabled using Control Expert configuration tools
see page 107
, an MSTR block can be used to change the enabled state of the service while the application is running. The MSTR block cannot change the state of the HTTP or FTP/TFTP services if the service was disabled using one of the configuration tools.
Register Meaning
CONTROL[1] 65520 (dec) FFF0 (hex) = enable / disable HTTP or FTP/TFTP
CONTROL[2] Indicates the error status. Possible return codes include:
0x000 (Success): MSTR block with operational code 65520 was called and the enabled state of HTTP or FTP/TFTP was changed.
0x5068 (Busy): MSTR block with operational code 65520 was called within
2 seconds of the previous call (regardless of return code from previous call).
0x4001 (Same state): MSTR block with operational code 65520 was called to change the enabled state of HTTP and FTP/TFTP to the states they were already in.
0x2004 (Invalid data): MSTR block with operational code 65520 was called and the data in the control block did not match the specifications.
0x5069 (Disabled): If the HTTP or FTP/TFTP service was already disabled via the Control Expert interface when the MSTR block with operational code 65520 was called to change the state of the disabled service.
CONTROL[3] Set this register to 1
CONTROL[4]
CONTROL[5] Module slot number and destination ID
High byte = Module slot number communication module slot
Low byte = Destination ID
CONTROL[6] Request mode
Bit 0 (LSB) = 1: Enable FTP/TFTP
Bit 0 (LSB) = 0: Disable FTP/TFTP
Bit 1 = 1: Enable HTTP
Bit 1 = 0: Disable HTTP
182
33002479 10/2019
Transferring Data Using Communication Blocks
Register
CONTROL[7] Set this register to 0
CONTROL[8]
CONTROL[9]
Meaning
HTTP, FTP, and TFTP service state changes made by MSTR with operation code 65520 (dec) are overridden by the configured value when the module is power-cycled or reset and when a new application is downloaded to the module.
Here are some examples:
Result State Configured By
Control Expert
Disabled
Action attempted using
MSTR with operation code 65520) (dec)
Any
Enabled Disable
Enable
MSTR returns error code 0x5069 (service was already disabled by configuration)
MSTR returns code 0x000 (success).
Another MSTR block action enables the service
--OR--
The module is reset or power-cycled
--OR--
A new application is downloaded with the service disabled by configuration
MSTR returns error code 0x4001 (same state). No change made.
33002479 10/2019
183
Transferring Data Using Communication Blocks
184
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Global Data (Publish/Subscribe)
33002479 10/2019
Global Data (Publish/Subscribe) Utility
Chapter 5
Global Data (Publish/Subscribe) Utility
Introduction
The material in this section presents the Global Data (Publish/Subscribe) utility available on the following modules.
140 NOE 771 01
140 NOE 771 11
140 CPU 651 x0
For more information on the publish-subscribe model, go to this URL: http://www.isa.org/journals/intech/feature/printable/1,1171,596,00.html
What Is in This Chapter?
This chapter contains the following topics:
Topic
Planning the Global Data (Publish/Subscribe) System
Multicast Filtering
Quantum NOE Global Data Configuration
Configuration of Global Data (Publish/Subscribe) by the Web for NOE 771 x1
Page
33002479 10/2019
185
Global Data (Publish/Subscribe)
Planning the Global Data (Publish/Subscribe) System
Overview
Global Data service is a real-time publisher/subscriber mechanism that provides the most efficient data exchange for PLC application coordination.
Devices that support Global Data are arranged in a distribution group for the purpose of application variable exchange and synchronization. Each Global Data device can publish up to one network
(application) variable and subscribe to up to 64 network (application) variables.
The Quantum NOE’s embedded Global Data Configuration Web page provides a configuration
see page 192
) to determine which and how many application variables are exchanged
with this service. After configuration, exchanges between all stations belonging to the same distribution group are done automatically.
The Global Data service uses %MW (4x registers) or unlocated variables for Global Data exchanges.
Key Features of Global Data
The main features for Global Data are:
One publisher and many subscribers
A device can publish one network variable of up to 512 %MW words (4x registers) or unlocated variables
A device can subscribe to up to 64 network variables of up to 2048 %MW words (4x registers) or unlocated variables
A device subscribes to the complete network variable
One distribution group per network IP address
Application-defined publication rate
Up to 64 Global Data Network variables (numbered from 1 to 64) can be part of the data distribution group
An NOE has only one multicast address. Consequently, it can only publish and subscribe within the group
A device can participate in several distribution groups by using multiple NOEs in the rack
Global Data has an advantage over client/server services when more than one subscriber is receiving the same data since only one transaction is necessary for all subscribers to receive the data. There are two benefits:
the reduction of overall network traffic
tighter synchronization of multiple subscribers
186
33002479 10/2019
Global Data (Publish/Subscribe)
Planning Your System Configuration
The Global Data (publish/subscribe) utility is a powerful function incorporated into the NOE product line. Implementing Global Data requires a configuration that spans many PLCs throughout the system. Therefore, we recommend pre-planning your installation before implementation. Preplanning saves time and money by:
reducing errors, which circumvents a debugging effort ensuring system consistency
Go to paper before computer.
We offer the following table to assist in system planning. The Global Data Planning Spreadsheet below is a graphic representation of a recommended configuration table for system planning. You can create your own table using the format below or you can download a Microsoft spreadsheet template, which is available on the Schneider public Web site.
Excel TM
Here is the graphic representation of the Global Data Planning Spreadsheet:
Parameter
Checking
Variable ID Symbol* Length
(Registers)
Device Number Variable Public.
Status
...
64
1
2
VALVE_STATUS
VALVE_CONTROL
20
10
1
PUB
SUB
2
SUB
NONE
PUMP_CONTROL 50 SUB PUB
Device Publication Status: OK OK
Total Publication Size per Node:
Total Subscription Size per Node:
239.255.255.0
OFF
20
60
50
20
...
3
NONE
PUB
NONE
OK
10
0
OK
OK
OK
Group IP Address
Multicast Filtering
Enabled
Default %MW Address for
Health
%MW100
Distribution Period
Health Timeout
10
1000
Data Zone %MW200
*Entries or changes to the symbol (description) do NOT affect or change a variable or the system. The symbol used in the Quantum product line has no relation to the Concept/Control Expert product line symbol(s).
33002479 10/2019
187
Global Data (Publish/Subscribe)
Table of Global Data Limits:
Parameter
Maximum number of publish variables per device
Maximum size for the publish variable
Maximum number of subscription variables per device
Maximum size for the subscribe variables per device
Limit
1
512 registers = 512 Words (16 bits) = 1024 bytes
64 (63 if this device is publishing)
2048 registers = 2048 Words (16 bits) = 4096 bytes
NOTE: We recommend that you consider the following when planning.
Allow for a 10 to 20 % increase in growth of any variable.
Add variables at the end of the configuration where they do not affect the existing application address. Therefore, you avoid changing the existing addresses in your configuration, which can be a time consuming process.
Table of Global Data Planning Spreadsheet
Parameter
Parameter Checking
Variable Id
Symbol
Length Words (Registers)
Device Number
Variable Public. Status
Device Publication Status
Description
Reserved
Represents the Data ID on the NOE’s Global Data Configuration Web page
Symbolic name for Global Data exchange.
Length of Global Data information. Number of %MW words (4x registers) or unlocated variables.
Number of devices (up to 64) for the Global Data network.
Automatic information of the correct publication status of the Global Data network. Only by using the Microsoft Excel TM spreadsheet. Information per symbol.
Automatic information of the correct publication status of the Global Data network. Only by using the Microsoft Excel TM spreadsheet. Information per device.
Total Publication Size per
Node
Total Subscription Size per
Node
Publication size for the specific node. The maximum publication size is 512 words
(registers) per node
Subscription size for the specific node. The maximum subscription size is 2048 words
(registers) per node
Group IP Address Enabled IP address for multicast networking. Identifies the stations distribution group. The address range is from 224.0.0.0 to 239.255.255.255
Multicast Filtering Enabled A check box for Ethernet switches that support multicast filtering.
Default Address for
Health%MW (4x register)
Distribution Period
%MW (4x register) address for the Health bits. This is the memory area where the
Health bits are stored. It has the size of 4 words (registers).
Is the minimum number of controller scan times before an update will occur.
188
33002479 10/2019
Parameter
Health Timeout
Data Zone
Global Data (Publish/Subscribe)
Description
Is the maximum time between received subscriptions before a subscription is declared unhealthy (faulty). The value is measured in milliseconds and can be set from 50 to
15000 ms in 50 ms increments.
The starting address for the data. This are the registers where the data information are stored.
33002479 10/2019
189
Global Data (Publish/Subscribe)
Multicast Filtering
Overview
Your NOE may offer the multicast filtering functionality.
The global data service synchronizes several stations located in a distribution group. A distribution group is a set of stations identified by using the same IP multicast address for all stations in the group. By using the same IP address for multiple devices, multicast exchanges can be used to distribute global data. Several independent distribution groups can coexist on the same subnetwork. Each distribution group possesses its own unique IP multicast address.
Early versions of switches treat multicast packets as a broadcast, thereby broadcasting to all nodes and suppressing all benefits of both switching and multicasting. Newer versions of switches provide automatic multicast filtering, and consequently only forward multicast traffic to ports that are connected to registered end stations.
Multicast Filtering Protocols
The following multicast filtering protocols are supported by Ethernet modules for its global data service.
GARP Multicast Registration Protocol (GMRP)
GMRP provides a mechanism that allows bridges and end stations to dynamically manage the membership of multicast groups.
NOTE: GMRP is defined in the IEEE 802.1D-1998 Standard, which is available as a free download at: http://IEEE802.org.
Internet Group Management Protocol (IGMP)
IGMP is a communications protocol used to manage the membership of internet protocol multicast groups. IGMP is used by IP hosts and adjacent multicast routers to establish multicast group memberships.
Reducing Traffic
Multicast filtering helps to reduce the traffic on a network, because broadcasts are sent only to interested, or subscribed, devices.
For distributed applications and one to many communications, multicast affords advantages over unicast because it:
utilizes the network bandwidth more efficiently sends a single transmission instead of multiple transmissions.
reduces collisions optimizes the performance of Ethernet module processing
190
33002479 10/2019
Global Data (Publish/Subscribe)
Using Multicast Filtering
These ConneXium switches support multicast filtering. Other switches from alternate vendors also support multicast filtering.
Switch Description
499NES17100 Managed Switch with 7 ports 10/100 BASE-TX
499NOS17100 Managed Switch with 5 ports 10/100 BASE-TX and 2 ports 100 BASE-FX
33002479 10/2019
191
Global Data (Publish/Subscribe)
Quantum NOE Global Data Configuration
Introduction
Global data configuration is carried out in the network configuration as well as the data editor. The variables for the publish/subscribe procedure are configured in the data editor.
The screen shot shows the network configuration global data configuration settings:
192
Parameter description:
Parameter
Health time out
Group address
Distribution period
Group name
Health bit block
Description
After this time period expires, the received data becomes invalid.
Class D multicast IP address. All nodes in the global data procedure use the same multicast address for distributing or receiving data. The address range is: 224.0.0.0 to 239.255.255.255.
Time after which the data is received or sent. Minimum scan time of the PLC.
Logical name. Defines the varibale allocation to different communication configurations in the variable editor.
Address for retrieving the status information of the global data procedure.
33002479 10/2019
Global Data (Publish/Subscribe)
Parameter
Multicast filtering
Description
Activates an Ethernet module that supports multicast filtering. From the drop down list, select:
None: disable both GMRP & IGMP
(Data will be sent to all end devices in the network.)
GMRP
Make sure your client, server and switches, and routers support and enable GMRP.
IGMP V1
Make sure your client, server and switches, and routers support and enable IGMP.
Note: The following modules support IGMP V1:
140 NOE 771 01 V4.4 or later
140 NOE 771 11 V4.4 or later
140 CPU 651 50/60 V2.7 or later
NOTE: The IGMP and None features are only available in Unity 4.1 or later.
NOTE: Unity Pro is the former name of Control Expert for version
13.1 or earlier.
NOTE: A Quantum PLC does not update health bits in STOP mode.
The screen shot shows an image of the data editor:
33002479 10/2019
193
Global Data (Publish/Subscribe)
Parameter description:
Parameter
Name
Type
Address
Global Data
Group
ID
Description
Variables symbols
Variable type
Variable address
Type of Global Data Variable. Options: No/Publish/Subscribe
Group name for allocating the variables of the existing network description. When creating the different Ethernet networks, a logical connection is arranged here between the network and the variable declaration.
Variable ID
194
33002479 10/2019
Global Data (Publish/Subscribe)
Configuration of Global Data (Publish/Subscribe) by the Web for NOE 771 x1
Modeling the System Configuration
There are two methods of configuring a system:
Configuring each device separately
Configure each device through the Global Data Configuration Web page (
see page 299
Repeat for each device in the system. Entry errors may occur because the same information must be reentered on each and every device, possibly as many as 64 times.
Copying the configuration (preferred)
Configure all variable IDs, symbols (descriptions), and lengths on one NOE, upload to your PC, download the same configuration to all devices and finish with a small customization to each node.
NOTE: The Copy Configuration method reduces entry errors, allows for verifying the configuration, and permits you to determine if the system is satisfactory for your needs before implementing the configuration system wide.
You enter the variable ID, symbol (description), and length only once, thus maintaining consistency.
When your planning is complete, follow the steps both as a picture and as instructions.
Configuring Your NOE steps below. We present these
33002479 10/2019
195
Global Data (Publish/Subscribe)
The following illustration shows the Configuring Your NOE steps:
196
33002479 10/2019
Global Data (Publish/Subscribe)
Configuring the NOE
6
7
3
4
Step Action
1 Select one NOE.
2 Using your browser, navigate to that NOE’s Global Data Configuration page.
Follow these links: | Setup | Global Data |
Enter the configuration’s variable IDs, symbols (description), and lengths.
Click the Update Global Data Configuration button to update the file. This creates the file glbdata.ini
.
Full path follows: ftp://NOE_IP_ADDRESS/wwwroot/conf/glbdata/glbdata.ini
Note: You substitute NOE_IP_ADDRESS with an address like 192.168.000.010.
Please check the address with your system administrator.
5
8
Using the FTP process, upload the glbdata.ini
file to a PC. (See the information below at Uploading a glbdata.ini file.)
Stop each controller before you do the customization.
Using the same path, download the glbdata.ini
file to the other devices. (See the information below at Downloading a glbdata.ini file.)
Connect your Web browser to each device to customize start address and the
Publish/Subscribe setting.
NOTE: The Global Data Configuration page is populated with data from the glbdata.ini
configuration file.
Uploading a glbdat.ini File to a PC
Step Action
1 At the DOS prompt type FTP followed by the IP address and press Enter.
2 At the User prompt type FTP Username and press Enter.
3 At the password prompt enter your FTP Password and press Enter.
4 At the FTP prompt type cd wwwroot/conf/glbdata and press Enter.
5 At the FTP prompt type get and press Enter.
6 At the local file prompt type glbdata.ini and press Enter.
7 At the remote file prompt type glbdata.ini and press Enter.
33002479 10/2019
197
Global Data (Publish/Subscribe)
Downloading a glbdat.ini File to another NOE
Step Action
1 At the DOS prompt type FTP followed by the IP address and press Enter.
2 At the User prompt type the FTP username and press Enter.
3 At the password prompt enter your FTP Password and press Enter.
4 At the FTP prompt type cd wwwroot/conf/glbdata and press Enter.
5 At the FTP prompt type put and press Enter.
6 At the local file prompt type glbdata.ini and press Enter.
7 At the remote file prompt type glbdata.ini and press Enter.
Verifying System Operation
Step Action
1 Verify all controllers are running.
2 Look at the health of all variables using the Global Data Diagnostic page.
Follow these links: | Diagnostics | NOE Diagnostics | Global Data
198
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Transferring Data with the I/O Scanner
33002479 10/2019
I/O Scanner
Chapter 6
I/O Scanner
Introduction
This chapter discusses the Ethernet modules’ I/O scanner capabilities.
What Is in This Chapter?
This chapter contains the following topics:
Topic
I/O Scanner Concepts
Configuring the Quantum I/O Scanner
I/O Scanning Contextual Menu for Copy/Cut/Paste
I/O Scanning with Multiple Lines
Introduction to Configuring Advantys from Control Expert
Introduction to Configuring the PRM Master DTM
Introduction to Configuring a BMX PRA 0100 from Control Expert
Property Box
Saving an Advantys Configuration in an Control Application
Managed Variables
I/O Scanner Response Times: Remote Input to Remote Output
Page
33002479 10/2019
199
Transferring Data with the I/O Scanner
I/O Scanner Concepts
Introduction
The I/O Scanner is a feature that resides in Ethernet (NOE 771 00, -01, -11, and CPU 651 scanned devices.
x 0) modules. The I/O Scanner allows, through a controller, repeated reading from and/or writing to
Use the I/O scanner to transfer data between network devices.
Configure the I/O Scanner with Schneider Electric’s programming package Control Expert. (I/O
Scanner configuration information (
see page 204
) appears elsewhere in this guide.)
NOTE: We recommend you program with words if your project involves both 140 CPU 651 whereas, the controller module reads in LL984 format.
x which each of these modules were developed, they both correctly scan towards %I, but they interpret the data in different programming languages. The NOE module reads in IEC format;
0 modules and 140 NOE 771 01 modules in the same application. Due to the unique manner in
Health Block Bits
Each bit corresponds to an entry in the I/O Scanner table. Each entry in the table represents one logical device.
The bits contain the health status for the Modicon Quantum I/O Scanner.
NOTE: A Quantum PLC does not update health bits in STOP mode.
Device Control Block
With the Device Control Block, disable an individual entry/device in the I/O Scanner table by checking the box and setting the associated bit in Device Control Block to 1.
Repetitive Rate Step
In the Repetitive Rate Step field, enter a rate of time for how often you want the I/O scanner to send a query to the device after the rate has timed out.
I/O Scan List
The I/O scan list is a configuration table that identifies the targets to which repetitive communications are authorized. While the controller is running, the Ethernet module transfers data to and from the controller’s registers as indicated by the I/O scan list.
200
33002479 10/2019
Transferring Data with the I/O Scanner
I/O Scanner Parameters
The I/O Scanner parameters are described in the following table:
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Health Timeout Value
Last Value (Input)
IP Address
Local and Remote Register
Reference
Repetitive Rate
Value
64: 140 NOE 771 00 (Version 2.2 or earlier)
128: 140 NOE 771 00 (Version 3.0 or later), 140 NOE 771 01, and
140 NOE 771 11 only
128: 140 CPU 651 x0
4000
4000
User configured: 1...65535 ms in 1 ms increments
User configured (Zero or Hold)
User configured
IP address of scanned device (Slave IP)
User configured
Unit ID
Gateway/Bridge Device
Operation through a bridge
The rate at which data will be scanned, from 0...65535 in multiples of:
If you are running Unity Pro V2.0 or higher
140 NOE 771 01/11: 16 ms
140 CPU 651 x0: 10 ms
If you are running Unity Pro V4.0
140 NOE 771 01/11: 5 ms (min), 200 ms (max)
140 CPU 651 x0: 5 ms
User configured
Configure ID only if using a bridge
To allow slower TCP/IP network devices (i.e., gateways and bridges) to be compatible with the I/O Scanner:
Select the check box to enable this feature. Defines a new bit, and sets it to high (1).
Deselect the check box to disable this feature (default). Defines a new bit, and sets it to zero (0).
Modbus bridge: Supported
Modbus Plus bridge: Supported
Elsewhere in this guide is information about I/O scan response times for high-performance communications modules
see page 233
.
Using the I/O Scanner with an IP Router
NOTE: The I/O Scanners in the 140 NOE 771 x1 and 140 CPU 651 x0 modules send out requests with a Time To Live (TTL) of 32, which allows passage through multiple routers.
33002479 10/2019
201
Transferring Data with the I/O Scanner
Device Control Block
Important information about using the Device Control Block:
Registers
Disabling Devices
Mapping Device Control
Block Bits to I/O Scanner
Entry Numbers (#)
Setting Bits
The Device Control Block consists of registers either 8 single words or 4 double words. Contents of the registers are mapped in the controller’s memory. Each bit corresponds to an entry in the table (see the tables below.)
Each I/O Scanner device can be disabled. To disable individual devices:
1. Select the Device Control Block option on the I/O Scanner tab in Control
Expert. (Insert a check mark in the box.)
2. Set the associated bit = 1.
See the table for mapping entry numbers to bits.
Each entry number represents a logical device on the network.
If Device Control Block bit is set to
0 = Device is enabled
1 = Device is disabled
Mapping Device Control Block Bits to I/O Scanner Entry Numbers (#)
Single Word (W)
Register (%MD x :4)
W1
%MW
[x+1]
W2
%MW
[x+2]
W3
%MW
[x+3]
Table
Entry
#
Bit
Table
Entry
#
Bit
Table
Entry
#
Bit
1
15
17
15
33
W8
%MW
[x+8]
Table
Entry
#
Bit
2 3
14 13
18 19
14 13
34 35
4 5
12 11
20 21
12 11
36 37
6 7
10 9
22 23
10 9
38 39
8 9 10
8 7 6
24 25 26
8 7 6
40 41 42
11 12
5 4
27 28
5 4
43 44
13 14
3 2
29 30
3 2
45 46
15 16
1 0
31 32
1 0
47 48
15 14 13 12 11 10 9 8 7 6 5 4
Word 4 through Word 7 (Table Entry 49 through 112)
3 2 1 0
113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
NOTE: Bits are counted from right to left starting from bit 0 (low bit). Examples: to configure
%MD1:4 as a device control block in the I/O Scanner table, use %MW2, bit 15 to enable or disable table entry 1. Use %MW3, bit 15 to enable or disable table entry 17.
202
33002479 10/2019
Transferring Data with the I/O Scanner
NOTE: Quantum and Premium co-processors follow Premium Ethernet module control bit operation.
Double Word (DW)
Register (%MD x :4)
DW1%MD x[0]
DW2
%MD x[1]
Table
Entry #
Bit
Table
Entry #
Bit
Table
Entry #
Bit
DW %MD x[4]
Table
Entry #
Bit
1
31
17
15
33
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
Word 3 through Word 4 (Table Entry 49 through 112)
113 114 115 116 117 118 119 120 12 122 123 124 125 126 127 128
15
2 3 4 5 6 7
30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
14 13 12 11 10 9
8
8
9
7
10 11 12 13 14 15 16
6 5 4 3 2 1 0
NOTE: Bits are counted from right to left starting from bit 0 (low bit). For example, to configure
%MD1:4 as a device control block in the I/O scanner table, use %MD1[0], bit 31 to enable or disable table entry 1. Use %MD1[1], bit 15 to enable or disable table entry 17.
33002479 10/2019
203
Transferring Data with the I/O Scanner
Configuring the Quantum I/O Scanner
The I/O Scanner Configuration Dialog
When you click the I/O Scanning tab in the Ethernet module configuration screen, the I/O Scanner screen opens:
204
NOTE: This screen shows I/O Scanner services for an 140 NOE 771 01 or -11 module. The I/O
Scanner screen is slightly different for the CPU 651 x0 module, which does not display a Health
Block field.
33002479 10/2019
Transferring Data with the I/O Scanner
Health Block
The Health Block field (number 1 in previous figure) lets you define the first word or bit in a health table. That table can be up to 8 words (%IW) or 128 bits (%I) in length. Each bit in the table represents the status of an individual device. The following table shows how the bits are displayed based on the data type you use:
Bit
1
2
...
16
17
Data Type
%I
%I1
%I 2
%I16
%I17
%IW
%IW1.15
%IW1.14
%IW1.0
%IW2.15
By default, the table comprises words starting at %IW1.0. If you want to set the table to bits, you need to specify a %I value in an increment of 16 (%I1, %I16, %I32, etc.).
NOTE: The Health Block field is available only for the NOE 771 00, -01, and -11. It is not available for the CPU 651 x0.
NOTE: For Safety Monitor applications, the Health Block is mapped on %M/%MW from the UMA zone instead of %I/%IW.
Device Control Block
The Device Control Block (number 2 in previous figure) lets you disable any scanned device by setting a bit associated with that device to 1. The I/O scanner closes the connection and sets the
Health Bit to 0 (unhealthy state).
To enable the Device Control Block, select the check box in the I/O Scanner configuration dialog
(item 2 in previous figure).
NOTE: To enable the Device Control Block, use:
Control Expert at V2.0 or later
an 140 NOE 771 01 or 140 NOE 771 11 at version 3.5 or later a 140 CPU 651 x0 at version 2.0 or later
If you attempt to enable the Device Control Block with an earlier version of the firmware, the I/O scanning service is disabled.
If the check box is not selected, the I/O scanner service is enabled, and you cannot disable the I/O scanning of individual devices.
Disabling I/O scanning with the Device Control Block is equivalent to ending communication between the scanner and the device.
33002479 10/2019
205
Transferring Data with the I/O Scanner
Therefore:
The fallback positions are applied to the inputs by the scanner.
Communication with the device stops.
All entries in the IN and OUT tables still transfer between the CPU and the scanner on each scan.
As a consequence of the last point above, if you modify a %MWi attached to an input, this %MWi is overwritten by the values coming from the I/O scanner in the next scan (with either 0 or the last input value).
It is possible (but meaningless) to access %MW attached to the outputs because they are not transmitted to the device.
Repetitive Rate Step
The Repetitive Rate Step (number 3 in previous figure) is set in multiples of 5 ms (the minimum) through 200 ms (the maximum).
The Repetitive Rate column is where you enter a rate of time for how often you want the I/O scanner to send a query to the device after the rate has timed out.
NOTE: The repetitive rate of the I/O scanner table is a multiple of the rate displayed in the
Repetitive Rate Step. The real repetitive rate being executed by the I/O scanner service is shown in the Repetitive Rate column.
NOTE: An entry in the Repetitive Rate column is rounded up to the next multiple that was entered in the Repetitive Rate Step if the entry is not a multiple of the Repetitive Rate Step.
For example, if the entry in the Repetitive Rate Step is 5 and you enter a 7 in the Repetitive Rate column, the 7 is rounded up to 10; if you change the Repetitive Rate Step to 6 and enter a 7 in the
Repetitive Rate column, the 7 is rounded up to 12.
206
33002479 10/2019
Transferring Data with the I/O Scanner
I/O Scanner Table Parameters
The I/O Scanner parameters are described in the table below:
Parameter
Entry #
IP address
Device Name
Unit ID
Slave Syntax
Description
This is the first column; it has no name.
Valid range: 1 ... 128
Each entry represents an I/O Scanning exchange on the network.
This is the IP address of the scanned Ethernet slave device.
To configure a device (Advantys island or DTM), click the
... button to open the Property box
the device configuration software.
For an introduction to this procedure for Advantys, go
For an introduction to this procedure for DTMs, go to FDT
Container
.
to start
(see EcoStruxure™ Control Expert, Operating
Modes) .
NOTE: While the Property box is open, I/O scanning cannot be edited.
This field associates the slave address of the device connected to an Ethernet/Modbus gateway with the IP address of that gateway:
Value range: 1 to 255
Default value: 255
NOTE:
When using a bridge, enter the bridge index (1 to 255) in this field.
If you are copying the I/O scanning configuration from a 140 NOE 771 •• to a 140 NOC 771 ••, set the Unit ID to a value from 1 to 254.
Use this drop-down menu to pick the way RD Ref Slave and WR Ref Slave values are displayed. There are 4 types of display available:
Index: 100
Modbus: 400101
(Modbus register)
IEC 0: %MW100
M340 and Premium PLC slaves
IEC 1: %MW101
Quantum PLC slaves
Example
192.168.1.100
MySTB1 or
Master_PRM_DTM_10
255
Index (default value)
33002479 10/2019
207
Transferring Data with the I/O Scanner
Parameter
Health Timeout
(ms)
Repetitive rate
(ms)
Description
This field sets the maximum interval between the responses from a remote device. After this time period expires, the received data is invalid. The Health Timeout should be longer than the Repetitive rate time (ms).
For a Quantum NOE Ethernet module, it also should be longer than the CPU scan time.
For the Health Timeout:
Range: 0ms to 65535 ms
Interval: 1ms
The rate at which data is scanned, from 0...65535 in multiples of the Repetitive Rate Step:
If you are running Unity Pro V3.1 or earlier with the following firmware versions:
140 NOE (V4.0 or earlier): 16 ms
CPU (V2.5 or lower): 10 ms
If you are running Unity Pro V4.0 or later with the following firmware versions:
140 NOE (V4.3 or later): 5 - 200 ms
CPU (V2.6 or later): 5 - 200 ms
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
RD Master
Object*
Destination address in the master PLC where, from each device, newly read information is stored
RD Slave Ref.** Source address index in the slave/remote device
RD length
Last value
(Input)
Example
1500 ms
60 ms
%mw10
Number of words to read
This field configures the behavior of inputs in the event of an access error in relation to the remote device (for example: inoperative network or device power supply, etc.):
Set to 0: fall back to 0
Hold last: maintain last value
The format of this value depends on the Slave Syntax:
Index: 5
Modbus: 400006
IEC 0: %MW5
IEC 1: %MW6
10
Hold last
NOTE: When you select hold last in a 140 CPU 651 •0 coprocessor, the input data may fall back to 0 when the I/O scanner health bits are NOT
OKAY. Confirm that the I/O scanner health bits are valid
(OK=1) before removing the
Ethernet cable to maintain hold last value.
208
33002479 10/2019
Transferring Data with the I/O Scanner
Parameter
WR Master
Object*
WR Slave
Ref.**
Description
Source address of the master PLC whose data is being written into the slave/remote device.
Write operations are always performed at the word level.
The address of the first word written into the slave/remote device.
Example
%mw20
WR length
Gateway/Bridge
Device
Number of words to be written
To allow slower TCP/IP network devices (i.e., gateways and bridges) to be compatible with the I/O Scanner:
Select the check box to enable this feature. Defines a
new bit, and sets it to high (1).
De-select the check box to disable this feature
(default). Defines a new bit, and sets it to zero (0).
10
Description Additional information
*Master refers to the client PLC that makes the request.
**Slave refers to the server from which data is read or to which data is written.
The format of this value depends on the Slave Syntax:
Index: 1
Modbus: 400002
IEC 0: %MW1
IEC 1: %MW2
NOTE: For more information, refer to the Contextual Menu for Copy/Cut/Paste topic
see page 210
.
NOTE: For more information, refer to the I/O Scanning with Multiple Lines topic (
see page 212
33002479 10/2019
209
Transferring Data with the I/O Scanner
I/O Scanning Contextual Menu for Copy/Cut/Paste
At a Glance
A right-click on a line in the I/O Scanning table opens the I/O Scanning Contextual Menu. Use this menu to perform common operations on the lines of the I/O Scanning table, such as, delete a device, copy & paste, cut & paste, insert a new line, etc.
Contextual Menu
The following illustration is the I/O Scanning contextual menu:
210
The following table describes the menu functions:
Menu Item
Delete Device
Cut line(s)
Copy line(s)
Paste line(s)
Description
For an ACS or PRA configuration, Delete Device permanently deletes the Device Name and all its data (and associated ACS symbols).
For a PRM Master DTM, its link to the I/O Scanning table is deleted,
NOTE: Deleting a PRM Master DTM link from the I/O Scanning table does not delete the corresponding DTM from the connectivity tree in the DTM Browser.
Cut line(s) copies and deletes the selected I/O Scanning lines. The lines are copied without the Device Name information.
For an ACS or PRA configuration, it permanently deletes the Device
Name and all its data (and associated ACS symbols).
For a PRM Master DTM, the link between the DTM and the I/O
Scanning line is removed.
Copy line(s) copies the selected lines, but without the Device Name.
Paste line(s) has 2 actions depending on its target line:
If the line is empty, it fills the line with the copied line (without a
Device Name)
If the line is not empty, it replaces the line with the copied line
(without a Device Name).
Be careful, it also permanently deletes the Device Name link to the
I/O Scanning table and, for an ACS or PRA configuration, all its data (and associated ACS symbols) of the old line before replacing it with the copied line.
33002479 10/2019
Transferring Data with the I/O Scanner
Menu Item
Insert copied line(s) Insert copied line(s) inserts the copied line between the selected line and the line just above it.
Be careful with ACS or DTM configurations, all the lines below the inserted line become desynchronized. To synchronize these lines, open and close the device configuration tool, then do an Update from
the Property box ( see page 224 )
.
Insert empty line
Description
Pack all lines
Insert empty line inserts an empty line above the line selected line.
Inserting an empty line does not desynchronize the devices below the line, but using this line for a new device can, depending the number of words needed, desynchronize the devices below the line.
Pack all lines removes any empty lines between the top of the I/O
Scanning table and the last non-empty of the table.
33002479 10/2019
211
Transferring Data with the I/O Scanner
I/O Scanning with Multiple Lines
At a Glance
Modbus exchanges are limited to a maximum of 125 input words and 100 output words. If an application needs to exchange more than these limits for a device, more than one I/O Scanning line can be used: multiple lines for one device.
When the length is higher than the authorized limit for one Modbus exchange, the length is divided into 2 or more Modbus exchanges. New lines are created for each Modbus exchanges with the
PLC.
The following I/O Scanning table is used for the multiple device lines example:
NOTE: This example shows an Advantys island, but DTM and PRA devices work the same way.
Multiple Line Length Configuration Example
In this example, the first (the main) I/O Scanning line 2 contains all the information for the exchanges with the device including the totals for the RD length and WR length.
The second line 2 contains the specific word lengths (125 and 100) needed so that it can also be used for part of the exchanges.
Line 2 needs a RD length of 300 word and a WR length of 110 words. How many extra lines are needed?
RD length = 300/125 = 2.72 = 3 lines needed
WR length = 110/100 = 1.10 = 2 lines needed
The larger of the 2 numbers is used:
Three lines are needed to accommodate the RD length: 125 words, 125 words, 50 words for a
total of 300 words
The 3 lines for the WR length are: 100 words, 10 words, 0 words for a total of 110 words
The second line 2, line 3, and line 4 correspond to the Modbus exchange queries.
When multiple lines are used, only the RD length and WR length columns of these new lines can be edited. In the case of Advantys or DTM, the software supplies the RD length and the WR length, and they cannot be changed in the I/O Scanning table.
NOTE: It is not necessary to have a Device Name defined to use multiple lines.
212
33002479 10/2019
The total number of words allowed in an I/O Scanning table is:
4 KW for Premium extended and Quantum networks
2 KW for Premium ETY and M340 NOE modules
Transferring Data with the I/O Scanner
Line Length for Multiple Word Variables
When using variables with 2 or more words, adjust the RD and WR lengths so that a variable is not partly on one I/O Scanning line and partly on the next. Because the 2 newly created lines result in
2 independent Modbus exchanges that can be sent non-synchronized to the device. The variables can receive the wrong values (if the 2 parts are received at different times). It may be necessary to use a RD length < 125 and a WR length < 100 for some of the scanned lines, in order to get each variable on only one exchange line.
WARNING
UNEXPECTED SYSTEM BEHAVIOR
Verify that multiple word variables are completely on the same I/O Scanning line to avoid sending parts of a variable data in 2 non-synchronized I/O Scanning Modbus exchanges.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
33002479 10/2019
213
Transferring Data with the I/O Scanner
Introduction to Configuring Advantys from Control Expert
At a Glance
The Advantys Configuration Software (ACS) is integrated in Control Expert. This allows you to configure Advantys STB and OTB islands from the Control Expert Ethernet I/O scanning tab.
Configuring an Advantys Island
WARNING
UNEXPECTED SYSTEM BEHAVIOR
Always launch ACS from Control Expert in order to synchronize variables and data between
Control Expert and ACS.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
UNEXPECTED SYSTEM BEHAVIOR
Stop the PLC before transferring an ACS configuration and/or I/O scanning modifications.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The following procedure configures an Advantys STB or OTB island:
Step
1
2
3
4
5
8
9
6
7
Action
Open the Ethernet network configuration screen.
In the Module Utilities zone select YES for IO Scanning.
Select the I/O Scanning tab.
Enter, on a free line, the IP address for the connection you want to use to communicate with the Advantys island.
Enter RD length and WR length on the same line. The lengths must be long enough for the expected Advantys configuration.
Validate the I/O Scanning screen.
Click on the ... button (that is next to Device Name cell on the same line).
Select STB or OTB in the Device Type drop-down menu.
Enter a Device Name (following the naming rules
Results
I/O Scanning screen opens.
The Property box opens.
214
33002479 10/2019
Step
10
11
12
13
Transferring Data with the I/O Scanner
Action
You have 2 choices:
1. If you want to go to ACS now to configure an island, click on the Launch Advantys Configuration Software button.
Click on Yes in the “ Confirm device name and type
Message Box and go to Step 11.
2. If you want to configure the Advantys island later, click on the OK button.
Click on Yes in the “
Message Box.
Confirm device name and type
”
”
To open the ACS later:
Carry out Step 7.
Click on the Launch Advantys Configuration Software button.
After ACS opens, configure your Advantys island.
NOTE: While the ACS is open Ethernet screen is locked and cannot be edited, but the other Control Expert services can be edited.
NOTE: The User Defined Label must be filled in the IO image . If not, the Advantys varialble will no be added in the
Control Expert Data Editor.
When your Advantys island has been built and validated, close ACS.
You have 2 choices:
1. Click on Yes in the “
14.
update ” Message Box and go to Step
2. Click on No in the “
You are returned to the I/O Scanning screen without carrying out the Yes results.
Later, when you want to update the Advantys symbols into Control Expert:
Carry out Step 7
update ” Message Box.
In the Property box, click on the Update button and go to Step 14.
Results
Results for both 1. and 2. are:
A Control Expert message box opens: “ The device name and device type won’t be
modifiable. Do you want to confirm the device name and device type?
”
The Device Type and Device
Name are verified and saved.
The Property box closes.
A Control Expert message box opens “ Do you want to update your symbols now?
”
If you clicked on No:
You are returned to I/O
Scanning without carrying out the results in Step 14.
The Device Name is displayed in the I/O Scanning in red. This indicates that the island configuration has not been synchronized with
Control Expert.
33002479 10/2019
215
Transferring Data with the I/O Scanner
Step
14
15
16
17
18
Action
Your Advantys island configuration is being synchronized with Control Expert.
After the synchronization is finished, you are returned to I/O
Scanning. Verify that the Device Name is now displayed in black.
Build your Control Expert application.
STOP the PLC.
Transfer:
Control Expert application to the PLC
STB or OTB configuration to the Advantys island using
ACS
RUN your application in the PLC.
Results
The results are:
The Advantys island
modifications are synchronized with the Control
Expert application.
The Advantys island symbols
are imported into the Control
Expert Data Editor.
The Advantys Device Name is displayed in the I/O Scanning in black. This indicates that the island configuration is synchronized.
Copy an Existing Island
This following procedure copies an existing Advantys island file (*.isl) into a new Advantys island configuration:
Step
1
2
3
4
5
Action
From Control Expert, open a new Advantys island in ACS.
In ACS, select File menu → Copy Island Contents.
In the Open island window, select the island file (*.isl) to copy.
Click on Yes in the “Do you want to proceed?” message box.
The message “Island file has been saved.” in the Log Window verifies that the operation was successful.
216
33002479 10/2019
Transferring Data with the I/O Scanner
Copy an Island File to a New Location
The following procedure copies an Advantys island file (*.isl) to a new directory:
Step
1
2
3
4
Action
In ACS, open an island configuration, for example, STB1.
Select File menu => Copy STB1 Contents
In the Copy STB1.isl to window, select the target directory.
The message “A copy of the island file has been saved with another name.” includes in the
Log Window verifies that the operation was successful. The name is new because its path has changed.
33002479 10/2019
217
Transferring Data with the I/O Scanner
Introduction to Configuring the PRM Master DTM
At a Glance
The PRM Bus Master uses the Control Expert I/O Scanner to communicate with the CPU through an Ethernet port. This requires configuring the PRM Master DTM in the Control Expert Ethernet I/O
Scanning tab.
Configuring a PRM Master DTM
The following procedure configures a PRM Master DTM in the I/O Scanner:
Step
1
2
3
13
14
15
16
6
7
4
5
8
9
10
11
12
Action
Install the PRM Master DTM on the Host PC.
NOTE: After installing new DTMs, the Hardware Catalog must be updated.
Add a PRM Master DTM to the connectivity tree in the DTM Browser using the contextual Device menu service.
In the DTM Browser, select the PRM Master and use the contextual Device menu function to open the DTM PRM Offline Parameter screen.
In the General Setting part of this screen set the IP address of the PRM device.
Open the I/O Scanning configuration editor (tab).
In the Module Utilities zone select YES for IO Scanning.
Select the I/O Scanning tab.
Results: I/O Scanning configuration editor opens.
Enter, on a free line, the IP address for the connection to be used to communicate with the PRM
Bus Master.
Set correct values for the Read Ref. and Write Ref. parameters.
Enter RD length and WR length for the IP address line (within the Read Ref. and Write Ref. constraints).
NOTE: The lengths must be long enough for the expected configuration PRM Master DTM and its subnode DTMs.
Validate the I/O Scanning screen.
Click on the ... button (next to Device Name cell).
Results: The Property box
Select DTM in the Device Type drop-down menu.
Select the protocol in the DTM Protocol drop-down menu.
Select a PRM Master DTM in the DTM Name drop-down menu.
Click on OK to validate the choices you made.
Results:
The Device Type, Device Protocol and Device Name are verified and saved.
The Property box closes.
218
33002479 10/2019
Transferring Data with the I/O Scanner
Step
17
18
19
20
21
22
23
Action
Update the I/O Scanning line, refer to Updating I/O Scanning for a PRM Master DTM
Build the Control Expert application.
Stop the PLC.
Transfer the Control Expert application to the PLC.
In the DTM Browser, right click on PRM Master and select the Connect function.
In the DTM Browser, right click on PRM Master and select the Store data to device function.
Run the application in the PLC.
Updating I/O Scanning for a PRM Master DTM
The following procedure updates the I/O Scanning information for a PRM Master DTM:
Step
1
2
3
4
Action
Configure and validate the PRM Bus Masters in the DTM Browser using the contextual Device menu function.
Open the I/O Scanning configuration editor (tab).
Click on the ... button (that is next to the Device Name of the PRM Master DTM to update).
In the open Property box
Results:
( see page 224 ) , click on the Update button.
The PRM Master DTM modifications are synchronized with the Control Expert application.
The PRM Master DTM symbols are imported into the Control Expert Data editor.
The DTM Name is displayed in the I/O Scanning configuration tab in black. This indicates that the PRM configuration is synchronized.
The Property box closes.
33002479 10/2019
219
Transferring Data with the I/O Scanner
Introduction to Configuring a BMX PRA 0100 from Control Expert
At a Glance
Control Expert allows configuration of BMX PRA 0100 modules through the Ethernet I/O scanning tab. The PRA device configuration is done in a second instance of Control Expert.
Configuring a PRA
The following procedure configures a PRA device:
Step
1
2
5
6
7
8
9
3
4
Action
Open the Ethernet network configuration screen.
In the Module Utilities zone select YES for IO
Scanning.
Select the I/O Scanning tab.
Enter, on a free line, the IP address for the connection you want to use to communicate with the
PRA.
NOTE: The IP address in the I/O Scanning table must be the same as the IP address of the PRA device.
Enter RD length and WR length on the same line.
Validate the I/O Scanning screen.
Click on the ... button (that is next to Device Name cell on the same line).
Select PRA in the Device Type drop-down menu.
Enter a Device Name (following the naming rules
Results
I/O Scanning screen opens.
The Property box ( see page 224 )
opens.
220
33002479 10/2019
Step
10
11
Transferring Data with the I/O Scanner
Action
You have 2 choices:
1. If you want to now configure a PRA, click on the
Launch PRA button.
Click on Yes in the “ Confirm device name and type ” Message Box and go to Step 11.
2. If you want to configure a PRA later, click on the
OK button.
Click on Yes in the “ Confirm device name and type ” Message Box.
NOTE: The Device Name becomes red in the
I/O Scanning table. This indicates that a PRA has not been configured for the table line that contains the Device Name
To configure a PRA later:
Carry out Step 7.
Click on the Launch PRA button.
NOTE: While the second PRA instance of Control
Expert is running no changes can be made to the
Ethernet Editor in the first (master) instance of
Control Expert.
After the second instance of Control Expert opens:
File menu → Open
Change the file type to .XEF
Open the PRA application template,
PRA_Template.XEF
Results
Results for both 1. and 2. are:
A Control Expert message box opens:
“ The device name and device type won’t be modifiable. Do you want to
confirm the device name and device type?
”
The Device Type and Device Name are verified and saved.
The Property box closes.
33002479 10/2019
221
Transferring Data with the I/O Scanner
Step
12
13
14
15
Action
When your PRA application is configured:
If desired, you can build the PRA application now.
Save the application.
NOTE: The Save As function is not available. To copy your PRA application use the Export or
Save Archive function.
Close this instance of Control Expert.
NOTE: You are asked if you want to save the
PRA application in the master application *.stu file. If you select No, all changes are lost.
NOTE: Later you can build your PRA application by carrying out Step 7. Because the PRA application is saved (embedded) in the master application *.stu file, it is opened. You can then build the PRA application.
NOTE: If there is no PRA application in the master
*.stu, an empty application is opened (as happens the first time the Launch PRA button is used in the
Property box)
Build your Control Expert application.
STOP the PLC.
Transfer:
Control Expert application to the PLC
PRA configuration to the PRA device
NOTE: There are no imported variables, the user must ensure the synchronization of the data exchange.
RUN your application in the PLC.
Results
16
NOTE: When the second (PRA) instance of Control Expert is closed, there is no indication if the
PRA application has been built or not.
222
33002479 10/2019
Transferring Data with the I/O Scanner
Copy an Existing PRA Application
This following procedure copies an existing PRA application:
Step
1
2
5
6
7
3
4
Action
From the Control Expert I/O Scanning table using the ... button, open an existing PRA application.
In the second Control Expert instance, save the existing PRA application with a new name as a
*.sta or .xef file.
Close this second Control Expert instance.
In the Control Expert I/O Scanning table create a new PRA application on a new line.
Import or Open the *.xef or *.sta file previously saved.
If desired, build the new PRA application and transfer it to the PRA device.
Close the second Control Expert instance.
33002479 10/2019
223
Transferring Data with the I/O Scanner
Property Box
At Glance
The Property box is the link between Control Expert and a device configuration tool. It is used to select and name a device and to launch the configuration tool for the device.
Property Box
The following illustration is the Property box before selecting the Device Type.
For details on how top use the Property box, refer to:
see page 225
see page 228
see page 226
224
33002479 10/2019
Transferring Data with the I/O Scanner
Property Box for Advantys
This Property box allows you to choose the name and type of Advantys island to be configured using the Advantys Configuration Software (ACS).
The following illustration is the Property box for Advantys entered: after Device Type and Device Name
Property Box for Advantys Elements
The elements of the Advantys Property box are:
Element
Device Type
Device Name
Data Exchange
Required
Use Device Name as prefix
Description
Selection of a STB or OTB device is made from this drop-down list.
After the first validation (using the OK or Launch Advantys button) the Device Type cannot be changed.
The Device Name
is used as a prefix to all variables created for an
Advantys island in ACS. This allows unique variables for duplicated islands.
After validation (using the OK or Launch Advantys button) the Device Name cannot be changed.
These are the minimum number of words necessary for communication between the
Control Expert module and the Advantys island.
These values cannot be changed via the Property box.
NOTE: Increasing the RD/WR lengths via the I/O Scanning tab leaves enough data exchange words for the future expansion of your Advantys island. Expanding an island that does not use the last line in the I/O Scanning table requires changing the values for all the lines below the line that needs the additional exchange words.
If this checkbox is unchecked, the user is in charge of giving unique names to the variables and symbols in all Advantys islands.
This checkbox is only available for ASC V5.5 or higher. For versions less than 5.5 the
Device Name is automatically added to all variables and symbols in all Advantys islands.
33002479 10/2019
225
Transferring Data with the I/O Scanner
Element
OK
Launch Advantys
Configuration
Software
Update
Close
Description
This button is only available after entering the Device Type and Device Name.
When clicked, the Device Type and Device Name are checked to see if they are valid.
If there is a problem, a message box opens explaining the why they were not valid.
OK is only available during the first use of the Property box for a new island.
This button is only available if both:
The Device Type and Device Name have been entered
ACS is installed
This button does two things:
It carries out the action of the OK button
If there is no problem during validation, it launches ACS
When clicked, the ACS modifications are synchronized with your Control Expert application (after these modifications have been validated in ACS).
It also imports and updates all ACS symbols and variables into the Control Expert variable manager.
NOTE: All variables modified in ACS are deleted and rewritten in the Control Expert
Data Editor. But they are not updated in the program.
This button closes the Property box without saving anything.
Property Box for BMX PRA 0100
This Property box allows you to choose the name for the PRA module to be configured.
The following illustration is the Property box for the PRA after Device Name validation:
226
33002479 10/2019
Transferring Data with the I/O Scanner
Property Box for PRA Elements
The elements of the PRA Property box are:
Element
Device Type
Device Name
Data Exchange
Required
OK
Description
Selection of the PRA device is made from this drop-down list.
After the first validation (using the OK or Launch PRA button) the Device Type cannot be changed.
The Device Name ( see page 227 )
is the name of PRA application.
This is not used when configuring a PRA device.
Launch PRA
Close
This button is only available after entering the Device Type and Device Name.
When clicked, the Device Type and Device Name are checked to see if they are valid.
If there is a problem, a message box opens explaining why they are not valid.
OK is only available during the first use of the Property box for a new PRA configuration.
This button is only available if the Device Type and Device Name has been entered.
This button does two things:
It carries out the action of the OK button
If there is no problem during validation, it launches another instance of Control
Expert, which is used to do the actual configuration of the PRA.
This button closes the Property box without saving anything.
Valid Name
A valid Device Name for a configuration:
Does not already exist in the application
Is not a empty name
Starts with a letter
Has a maximum of 8 characters
Only ASCII characters, not Unicode characters
Has no spaces
Follows the Windows file naming conventions: no slashes, question marks, etc.
Follows Control Expert variable naming conventions
33002479 10/2019
227
Transferring Data with the I/O Scanner
Property Box for a PRM Master DTM
This Property box allows you to choose the type and protocol for a PRM Master DTM:
The following illustration is the Property box
DTM Name: after selecting the Device Type, DTM Protocol and
Property Box PRM Master DTM Elements
The elements of the DTM Property box are:
Element
Device Type
DTM Protocol
Device Name
Data Exchange
Required
Description
Selection of DTM device type is made from this drop-down list.
Select the protocol to be used from this drop-down list.
This list contains the DTM protocols of all the DTMs in the DTM Browser that can be linked with I/O Scanning.
Select a PRM Master DTM from this drop-down list.This list uses the DTM Browser Alias names.
This list contains all the PRM Master DTMs in the DTM Browser that support the selected DTM Protocol.
To validate the choices, click on the OK button.
These are the minimum number of words necessary for communication between Control
Expert and the PRM Master DTMs.
These values cannot be changed via the Property box.
NOTE: Increasing the RD/WR lengths via the I/O Scanning tab leaves enough data exchange words for the future expansion of your DTM topology tree. Expanding a tree that does not use the last line in the I/O Scanning table requires changing the values for all the lines below the line that needs the additional exchange words.
228
33002479 10/2019
Transferring Data with the I/O Scanner
Element
OK
Launch No Tool
Update
Close
Description
The OK button is only available after selecting the Device Type, DTM Protocol and DTM
Name.
When clicked, the DTM Protocol and DTM Name are checked to see if they are valid.
If there is a problem, a message box opens explaining the why they were not valid.
The OK button is only available during the first use of the Property box for a new PRM
Master DTM.
This button is never available for PRM Master DTMs.
Use the Update button after validating or changing the configuration of the linked PRM
Master DTM. Refer to Update I/O Scanning for a PRM Master DTM
The Close button closes the Property box without saving anything.
33002479 10/2019
229
Transferring Data with the I/O Scanner
Saving an Advantys Configuration in an Control Application
At a Glance
ACS saves an island configuration in an *.isl file. To add the island to an application, it is necessary for Control Expert to know the location of the island configuration information.
Saving the Configuration
The recommended way to save your island configuration information is to save your Control Expert application as a *.stu or *.sta file. The *.isl file is automatically included in these files.
Uploading or Importing
There are 2 situations where the information contained in the *.isl file is not available:
1. Uploading the application running in the PLC
2. Importing an *.xef file
In these 2 cases, if ACS is launched from the Property box open the latest Device Name.isl file the Control Expert General Path => Project Path directory:
see page 224
, it automatically tries to
If the same PC is used for the import (upload) and export (download) and the Control Expert
Project Path has not changed, the island configuration is synchronized with ACS.
If the same PC is not used for the import (upload) and export (download) or if the Control Expert
Project Path has changed, either:
Create a new island
Use the File menu => Copy Island Contents function
NOTE: The new Device Name.isl file is copied to the Project Path directory.
230
33002479 10/2019
Transferring Data with the I/O Scanner
Managed Variables
At a Glance
Variables of devices that are linked to Control Expert through I/O Scanning or DTM are managed variables . They are created by the device configuration tool or by the DTM and are imported into
Control Expert. They are named as a concatenation of the Property box
Name + device symbol name.
see page 224
Managed Variables in the Data Editor
Advantys symbols become managed variables when imported into Control Expert. An Advantys managed variable name is a concatenation of: the Advantys island name + Advantys symbol name.
This Data Editor illustration shows managed variables with their device name prefixes and their
Owner attributes:
Managed variables follow the usual rules for Control Expert and ACS or DTM naming.
The optional Owner column lists the owner attribute of the managed variables. This allows you to filter the variables according to their Device Name.
The Control Expert managed variables are locked and cannot be modified through the Data Editor.
You have to use the device configuration tool (ACS or the DTM) to modify these variables.
33002479 10/2019
231
Transferring Data with the I/O Scanner
Importing Managed Variables from a Device (Advantys, DTM)
Using the Update button on the Property box (
see page 224
Data Editor as Control Expert managed variables.
imports the device Symbols into the
In the case of a conflict between an device Symbol and an existing variable in the Data Editor:
If the Control Expert variable
If the Control Expert variable is not managed, a message box allows you to replace this variable with the managed variable coming from the ACS- or DTM-controlled device).
is already managed, the update is cancelled.
For an already managed variable, there are 2 options, either:
1. Use the device configuration tool (ACS or the DTM) to rename the variable.
2. Delete the old managed variable using the tool that manages the variable, then use the tool to perform an Update.
After performing one of these options, use the Update button again on the device being updated to complete the import without a conflict.
Permanent Deletion of a Managed Variable
Managed variables cannot be deleted directly from the Data Editor.
Removing a managed variable from a configuration must be done from the tool (ACS or the DTM) that manages the device (either delete the device using the DTM or delete the Symbol using the
ACS).
NOTE: During an Update, all managed variables are deleted and recreated during synchronization between Control Expert and the device.
Partial Import of a Managed Variable
Starting with Unity Pro V5.0, the managed variables become unmanaged during a partial import from an .XSY file. This allows deletion of the variables if the linked device is not also imported.
After importing variables from an .XSY file, an Update is needed to resynchronize the managed variables linked to a device. During this Update, a conflict box appears to allow validation of the replacement managed variables.
232
33002479 10/2019
Transferring Data with the I/O Scanner
I/O Scanner Response Times: Remote Input to Remote Output
Measurement Setup
The set of curves below illustrates Quantum PLC response times when a signal is sent from a remote input module to a remote output module through a Quantum PLC:
The signal is:
1 triggered by a Momentum input module with a response time of ~2 ms
2 scanned into the Quantum PLC at a repetitive rate of 0 ms
3 copied to another internal variable within the PLC
4 written to a Momentum output module with a response time of ~2 ms
33002479 10/2019
233
Transferring Data with the I/O Scanner
140 CPU 434 12A with 140 NOE 771 x1 Module
The 140 CPU 434 12A with an NOE 771 x1 (v3.3) was used for the following measurements:
The plot shows four lines representing the number of scanned devices:
1 device
8 devices
16 devices
32 devices
The four lines are indistinguishable at this scale because the response times are so similar. You can see the similarity in the following table of data from which the above graph was plotted:
Number of Devices to Scan
434 12A + NOE 771 x1 (v3.3)
1 device
8 devices
16 devices
32 devices
Time from Scanned Device Input to Scanned Device Output (ms)
10 ms scan 20 ms scan 50 ms scan 100 ms scan 200 ms scan
41
42
73
75
179
180
358
360
665
666
44
46
77
79
182
185
361
364
668
671
234
33002479 10/2019
Transferring Data with the I/O Scanner
140 CPU 65 150 with NOE 771 x1 (v3.3)
The 140 CPU 65 150 with an NOE 771 x1 (v3.3) is used used for the following measurements:
The plot shows four lines representing the number of scanned devices:
1 device
8 devices
16 devices
32 devices
The four lines are indistinguishable at this scale because the response times are so similar. You can see the similarity in the following table of data from which the above graph was plotted:
Number of Devices to Scan
65150 + NOE 771x1 (v3.3)
1 device
8 devices
16 devices
32 devices
Time from Scanned Device Input to Scanned Device Output (ms)
10 ms scan 20 ms scan 50 ms scan 100 ms scan 200 ms scan
35
36
61
62
153
154
302
303
602
603
38
40
64
66
155
157
305
307
606
609
33002479 10/2019
235
Transferring Data with the I/O Scanner
236
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Address Server Configuration/Fast Device Replacement
33002479 10/2019
Address Server Configuration/Fast Device Replacement
Chapter 7
Address Server Configuration/Fast Device Replacement
Introduction
This chapter covers the Address Server Configuration/Fast Device Replacement service available on the NOE 771 01 and -11 (Transparent Factory/Real Time modules) and HE CPU modules. The
Fast Device Replacement service offers you a method of handling device replacement without disrupting the system or service.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Address Server Configuration/Fast Device Replacement
Understanding Fast Device Replacement
Configuring Fast Device Replacement
Page
33002479 10/2019
237
Address Server Configuration/Fast Device Replacement
Address Server Configuration/Fast Device Replacement
Overview
The address server provides two capabilities:
1. Standard BOOTP server behavior: Enter the MAC address and IP configuration. The NOE
BOOTP server will provide the IP configuration when the device sends a BOOTP request.
2. Fast Device Replacement (FDR) behavior: Enter the role name or the MAC address of the device. The device will send its role name or the MAC address with its DHCP request. With the
DHCP response from the NOE, the device will receive its IP Configuration, plus the name and location of a configuration file.
The next step for an FDR-compliant device is to download its configuration from the NOE.
NOTE: Consult your Schneider Electric sales representative for the current list of FDR-compliant devices.
The address server in the NOE supports both modes at the same time. You select a mode by
entering either the MAC address or the role name in the Address Server Node Configuration
see page 302
page. You may enter only one or the other, but not both.
The Fast Device Replacement capability allows automatic configuration of FDR-compliant devices.
Identifying a Role Name
Role names play an important role in Fast Device Replacement. A role name is a logical name that the user assigns to a device, a logical name that has a meaning within the application. Example role names might be:
ENT_6: The sixth Momentum ENT in your application.
OUTPUT_VALVE_2: The second output valve in your application
NOTE: Role names are case-sensitive.
Role Name
The logical role name should be written on devices. The technician can get the new device from stores, enter the corresponding role name into the device, and place the device in the system. The device automatically gets its configuration and starts running with no further input from the technician. This process is designed to get your machine up and running quickly. All the technician has to do for any FDR compliant device is to enter the role name into the new device.
238
33002479 10/2019
Address Server Configuration/Fast Device Replacement
Address Server Limits
This table displays the parameters and limits of the address server:
Parameter
Maximum number of address server entries
Maximum size of the configuration file per device
Total size of Fast Device Replacement storage
Maximum role name size
Limit
128
4K bytes
512K bytes
16 Characters
NOTE: For the DHCP server to work correctly the following must be observed.
Address class and subnet class configured for the devices must match.
Address class of the NOE and of the devices must be the same.
Operating on a Corporate Network
Keep these points in mind when operating on a corporate network:
Before placing the NOE on a corporate network, Schneider Electric recommends that you
discuss the installation with your MIS department. It is likely that your company's corporate network has at least one DHCP server running already. If the NOE's DHCP server is running on the same network, it may disturb the network.
To avoid any possible problem related to the NOE's DHCP server on the corporate network, you have to ensure that the DHCP server is not running in the NOE by not having address entries in the configuration. If there are no configured devices in the address server Configuration page, then the NOE will not start the DHCP server.
Available FDR Agents
Three FDR agents are available:
Momentum ENT
Micro ETZ
ATV58
The role-name.prm
configuration files are stored in the NOE in non-volatile memory. Therefore, after a power failure all configurations will be available.
BOOTP and DHCP Compatible Devices
Use either the MAC address or the role name
see page 303
) to assign IP addresses. Therefore,
you may use the DHCP server with devices that support BOOTP only, such as Momentum ENT v1.
33002479 10/2019
239
Address Server Configuration/Fast Device Replacement
Understanding Fast Device Replacement
Understanding Confirmation and Error Messages
In addition to highlighting errors, the system provides confirmation information and error messages.
Confirmation Message If you successfully added, modified, or removed and entry, the following alert message appears:
Error Messages Error messages, appearing as icons in the seventh column, display on the
Address Server Configuration page (
see page 302
Error Icon If an entry is not loaded in the DHCP server or loaded with a different configuration, an icon of an exclamation point displays in the seventh column. The icon informs you of the difference between the current and stored information.
Not loaded in the server: A red icon displays.
Duplicate configuration: A blue icon displays.
Place the pointer over the icon and a pop-up window appears and displays a message
Not Loaded in the server:
Present configuration:
240
33002479 10/2019
Address Server Configuration/Fast Device Replacement
Error Dialog Box If you entered an existing role name or MAC address, you will receive an alert message asking you to correct the entry.
Modifying the Database
If you need to add or modify an entry in the database, use the Address Server Configuration page
see page 302
. Three fields must be filled in:
Device IP address
Subnet Mask
Gateway
Choose either the Role Name or Device MAC address field. When one field is selected, the other is made unavailable.
Adding Entries If you are adding a device, the page appears with values. You need to enter either a Role Name or a MAC Address.
If you are adding an entry, submit your selection using the Add the Entry button.
Modifying Entries If you are modifying an entry, the Device IP address, Subnet Mask, and Gateway fields display with the current configuration.
If you are modifying an entry, submit your selection using the Reset the Form button.
Each field of the Address Server Node Configuration page has restrictions, which are detailed below.
Role Name: Each role name must be unique. Only letters, numerals, and underscores are allowed. No more than 16 characters are allowed, and no spaces are allowed.
Device MAC Address: This address must be in hexadecimal format and six (6) bytes long (6x2 characters). The MAC address can be entered with or without a delimiting character between each pair of lower- or upper-case hexadecimal characters. The delimiting characters improve readability. There are three choices for a delimiting character:
Space " " (spacebar)
Colon ":"
Hyphen "-"
Device IP Address: The IP address must use the standard numeric Internet Protocol address that uniquely identifies each computer on the network. The IP address is a 32-bit identifier made up of four groups of numbers (from 0 through 255), each number separated by a period, for example 123.456.78.9
.
Subnet Mask: The subnet mask must be entered in IP address format.
Gateway: The gateway must be entered in IP address format. The gateway must be on the same subnet as the device.
33002479 10/2019
241
Address Server Configuration/Fast Device Replacement
Configuring Fast Device Replacement
Configuring the Address Server
To configure the Address Server you use Web pages generated by the embedded Web server.
The first page that appears is the Address Server Configuration page. The first column contains buttons used for selecting devices. The Address Server Configuration page displays configuration information for each device in the system and has seven columns in the table.
Displayed on this page is information about:
Role Name
MAC Address
IP Address
Subnet Mask
Gateway
An additional, unnamed column indicates any difference between the current and stored configuration. If a difference exists, an exclamation point is displayed.
This is the Address Server Configuration page. In this sample page, the configured and stored configurations are the same for each device.
On the Address Server Configuration page you can:
Add a New Entry
Change an Entry
Delete an Entry
Refresh the data table
242
33002479 10/2019
Address Server Configuration/Fast Device Replacement
Choosing Options
The Address Server Configuration page allows you to choose different options for adding or altering the configurations of your NOE. The options available to you are:
select an entry add an entry
change an entry delete an entry
Below we describe the method and options chosen to perform any of the four options listed above.
Screen shots are presented to accompany the Adding an entry section.
Selecting an Entry When the page displays, by default no entries are selected. Use the radio buttons in the first column to select an entry. Only one entry may be selected at a time.
Adding an Entry When the Add a New Entry button is selected, the Address Server Node
Configuration page appears. This page displays information about a device.
If you selected a device, this page displays the device’s configuration. Configuration information appears in four of the five fields of the dialog box. Only the Role information field is blank. You should enter a Role name, for example ENT_7 .
If no device is selected, default values appear in each field.
Changing an Entry Before using this button, you must select an entry in the database by choosing one of the radio buttons in the first column. If you do not choose an entry, a message appears.
When the Change an Entry button is selected, the Address Server Node Configuration page appears. The information displayed is for the device selected.
Deleting an Entry Before using this button, select an entry in the database by choosing one of the radio buttons in the first column. If you do not choose an entry, a message appears.
The entry selected will be removed from the database. Before completely deleting an entry, a warning message appears. Click Yes if you want to delete the entry, No if you don’t.
33002479 10/2019
243
Address Server Configuration/Fast Device Replacement
If you click Yes, a dialog box appears.
Click OK. Another dialog box appears notifying you that the deletion was successful.
Highlighting Anomalies
If there are anomalies with the entered configuration parameter information, the system indicates anomalies using a highlighting mechanism. Valid device configurations appear in purple and italic.
A device with configuration anomalies appears in red and bold.
The system detects the following anomalies:
Bad Role Name
The valid Role Name characters are:
a through z (lower case)
A through Z (upper case)
"_" (underscore)
Bad MAC Address
The valid MAC Address characters are:
0 through 9
A through F
Wrong IP Address
Wrong Subnet Mask
Wrong Gateway
Double Entry
Each entry needs a unique Role Name or MAC Address. If a duplicate Role Name or MAC
Address is entered, the system highlights the duplication.
244
33002479 10/2019
Address Server Configuration/Fast Device Replacement
Erroneous entries are not loaded into the DHCP server. Therefore, correct erroneous before loading. There are two ways of correcting the erroneous entries:
Correcting through Web page: Make the changes on the Web page and submit the change.
Correcting through the Address Server configuration file: Make the changes in the file and reboot the server.
33002479 10/2019
245
Address Server Configuration/Fast Device Replacement
246
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
SNMP
33002479 10/2019
Network Management Service (SNMP)
Chapter 8
Network Management Service (SNMP)
Introduction
The following material describes SNMP and the Schneider private MIB. Under the Schneider private MIB is the Transparent Factory Ethernet private MIB.
What Is in This Chapter?
This chapter contains the following topics:
Topic
SNMP
ASN.1 Naming Scheme
Configuring an NOE with SNMP
Configuring an NOE with TFE Private MIB
Page
33002479 10/2019
247
SNMP
SNMP
Introduction
This topic describes the Simple Network Management Protocol (SNMP), which is configured on your NOE or 140 CPU 651 x0. Network management software allows a network manager to:
monitor and control network components isolate problems and identify their causes
query the status of devices such as a host computer, routers, switches, and bridges obtain statistics about the networks to which devices are connected
Manager/Agent Paradigm
Network management software follows the conventional client-server model. To avoid confusion with other network communication protocols that use the client/server terminology, network management software uses the following terms:
manager : the client application that runs on the manager’s computer agent : the application that runs on a network device
The manager uses conventional transport protocols (for example, TCP or UDP) to establish communication with the agent. Managers and agents then exchange requests and responses according to the network management protocol.
Simple Network Management Protocol
Your NOE module is configured with SNMP, which is the standard protocol used to manage a local area network (LAN). SNMP defines exactly how a manager communicates with an agent .
The SNMP defines the format of the requests that a manager sends to an agent and the format of the replies that the agent returns to the manager.
The MIB
Each SNMP object has to be defined and given a unique name. Both the manager and agent programs must agree on the names and the meanings of the fetch and store operations. The set of all objects SNMP can access is known as a Management Information Base (MIB ).
Private MIB
Schneider obtained a private MIB, Groupe_Schneider (3833). Under the Groupe Schneider private
MIB is a Transparent Factory Ethernet (TFE) private MIB. The Transparent Factory SNMP embedded component controls the Schneider private MIB function.
248
33002479 10/2019
SNMP
Choosing an SNMP Manager
If you already have a working SNMP manager, you may continue to use it. Any of the many SNMP version 1-compliant managers on the market will work.
If you do not currently use an SNMP manager in your organization and are evaluating SNMP managers for purchase, then we recommend that you consider HiVision with the ConnexView Add-
On developed for use with Schneider Electric PLCs.
Please contact your Schneider Electric sales office for availability and pricing of HiVision and
ConnexView.
Using an SNMP Manager
The process for obtaining an SNMP manager:
2
3
Step
1
Action
Get Schneider .mib
file from the NOE Web page.
Find the .mib
file as a packed file under /wwwroot/SchneiderTFE.zip on your NOE module.
Load .mib
file to the SNMP manager.
When you are done, you will see the Schneider private MIB manager in your manager.
Other SNMP Resources
SNMP and related subjects are well-documented on Web sites and in many books:
As of this writing, a useful description appears on Microsoft’s
Browse to http://www.microsoft.com/technet
Management for Microsoft Networks Using SNMP."
Technet pages.
. Use the Search function to find "Network
Use an Internet search engine to search for an SNMP introduction, tutorial, or other resource.
The SNMP FAQs from the news group comp.protocols.snmp
appear on many .com
and
.org
Web pages. Search for the combination of " comp.protocols.snmp
" and " FAQ ."
33002479 10/2019
249
SNMP
ASN.1 Naming Scheme
ASN.1 Overview
Abstract Syntax Notation One (ASN.1) is a formal language for abstractly describing messages to be exchanged between distributed computer systems.
An Example
Objects in a MIB are defined with the ASN.1 naming scheme that assigns each object a long prefix that guarantees that the name will be unique. For example, an integer that counts the number of
IP datagrams that a device has received is named: iso.org.dod.internet.mgmt.mib.ip.ipinReceives
.
The following figure depicts the ASN.1 naming scheme example.
250
This object name is represented in an SNMP message by assigning each part an integer. So, the above message would appear as 1.3.6.1.2.2.4.3.
33002479 10/2019
SNMP
Each integer has the following meaning:
1 = ISO (International Organization for Standardization)
3 = identified organization (one of branches under the ISO root)
6 = U. S. Department of Defense (DoD) (one of the children under branch1.3)
1 = the Internet subtree under 1.3.6
2 = the mgm branch — (one of seven) of the Internet subtree. It is managed by the Internet
Assigned Numbers Authority, and includes the standard MIBs
2 = mib-2(1) group of managed objects
4 = ip (the mib-2(1) IP group (one of 11))
3 = ipinReceives (the MIB object)
33002479 10/2019
251
SNMP
Configuring an NOE with SNMP
Object Identifier (OID)
In the ASN.1 Naming Scheme example (
see page 250
) , the MIB object identified by the notation
1.3.6.1.2.2.4.3 is referred to as the Object Identifier or OID. All OIDs can be seen as part of a tree structure that begins at the root (ISO) and branches out with each subtree identified by an integer.
SNMP Protocol Data Units
SNMP uses protocol data units (PDUs) to carry the requests and responses, between the manager and the agents, for the information contained in an OID.
As the following figure shows, the SNMP message is the innermost part of a typical network transmission frame.
The PDUs within the SNMP initiate the communication between the manager and the agents.
The SNMP installed on your NOE module uses the following three PDUs:
GetRequest
SetRequest
Trap
GetRequest PDU
The GetRequest (shortened to Get) PDU is used by the SNMP manager to retrieve the value of one or more objects (OIDs) from an agent.
SetRequest PDU
The SetRequest (shortened to Set) PDU is used by the SNMP manager to assign a value to one or more objects (OIDs) residing in an agent.
Trap PDU
The Trap PDU is used by the agent to alert the manager that a predefined event has occurred.
252
33002479 10/2019
SNMP
Version & Community Identifiers
The version identifies the version number of the SNMP software being used by the manager and the agent. Your NOE supports Version 1 of the SNMP. The community is an identifier that you assign to your SNMP network. If community names for the manager and the agent do not agree, the agent will send an authentication failure trap message to the manager. If the community names and version number agree, the SNMP PDU will be processed.
What Can Be Configured
Your NOE module can be configured to send an authentication trap to two SNMP managers if it receives a community name in a Get/Set request that does not match the configured name. Also, you can configure the SysContact and SysLocation via the configuration page in the module’s embedded web pages. After making changes in the SNMP Configuration Web page and to set those changes, reboot the module using hot swap.
33002479 10/2019
253
SNMP
Configuring an NOE with TFE Private MIB
Introduction
A MIB, a Management Information Base, is an element used in network management. Network management services are based on the need to monitor and manage:
performance fault occurrences security
Each MIB contains a finite number of objects. Manage your MIB with a management station running an SNMP management application. The management application uses GETs and SETs to retrieve system information and to set system environment variables.
Schneider Private MIB
Schneider Electric obtained a Private Enterprise Number (PEN) from the Internet Assigned
Numbers Authority (IANA). That number represents a subtree in the SNMP MIB, a number that is a unique identifier used for Groupe Schneider.
The object identifier for the root of the Groupe Schneider subtree is 1.3.6.1.4.1.3833
and represents a path to the subtree as follows: iso(1) org(3) dod(6) internet(1) private(4) enterprise(1)
GroupeSchneider(3833)
Transparent_Factory_Ethernet(1)
Under the GroupeSchneider private MIB is a Transparent Factory Ethernet (TFE) private MIB,
Transparent_Factory_Ethernet(1).
TFE Private MIB
The Transparent Factory SNMP-embedded component controls the Schneider private MIB function. The Schneider private MIB, and associated services, perform Network Management on all system components. The Transparent Factory private MIB provides the data to manage the main Transparent Factory communication services for all the communication components of the
Transparent Factory architecture (ETYs, NOEs, third party toolkit, ENTs, M1Es). The Transparent
Factory private MIB does not define the specific management applications and policies.
254
33002479 10/2019
The diagram following illustrates the Schneider Electric (Groupe_Schneider (3833)) private enterprise MIB subtree.
SNMP
The Groupe_Schneider (3833) subtree is the root of Groupe Schneider's private MIB in the
Structure of Management Information (SMI) used by SNMP and defined in RFC-1155, which is a specification that defines the structure and identification of management information for TCP/IPbased networks.
33002479 10/2019
255
SNMP
Transparent Factory Ethernet Subtree
The Transparent_Factory_Ethernet (1) subtree defines groups that support the Transparent
Factory Ethernet services and devices.
Service
Switch(1)
Port502_Messaging(2)
I/O_Scanning(3)
Global_Data(4)
Web(5)
Address_Server(6)
Equipment_Profiles(7) timeManagement(8) email(9)
Subtree Definition brand of switches labeled: ConneXium switches private MIB objects for managing explicit client/server communications supporting applications, such as HMI, SCADA, or programming tools objects for managing I/O device communications that use the I/O Scanner mechanism with the MB/TCP protocol objects for managing the application coordination service using a publish/subscribe protocol objects for managing the activity of the embedded Web servers objects for managing the activity of the BOOTP and (or) DHCP servers objects for each type of device in Transparent Factory Ethernet's product portfolio objects for managing the UTC time stamp service objects for managing the mail service
Device subtrees, or groups, will be defined for the following devices:
Premium(1)
Quantum(2)
Generic_Device(3)
M1E(4)
ENT(5)
As devices are added to Schneider's catalog, Schneider's private MIB will be extended in the following manner:
If needed, a Transparent Factory, communication-service object will be added for the new device in the corresponding Equipment_Profiles(7) subtree. This subtree can hold as many
objects as are required.
If needed, a new branch will be added at the same level as Transparent_Factory_Ethernet(1).
This subtree will be created for product-specific objects (such as the ATV58 object under the
IndustrialControlProducts (3) subtree).
When a new device is created, a corresponding object description is created in the ASN.1 format.
The ASN.1 file(s) are then given to producers of SNMP manager software for inclusion in their products.
256
33002479 10/2019
SNMP
Port502 Messaging Subtree
The Port502_Messaging (2) subtree, or group, provides connection management and data flow services. The following list describes the function of each object.
Service port502Status(1) port502SupportedProtocol(2) port502IpSecurity(3): port502MaxConn(4) port502LocalConn(5) port502RemConn(6) port502IpSecurityTable(7) port502ConnTable(8) port502MsgIn(9) port502MsgOut(10) port502MsgOutErr(11) port502AddStackStat(12) port502AddStackStatTable(13)
Indicates . . .
status of the service (idle, operational) supported protocols (MODBUS, Xway) status of the Port502 IP Security service (enabled/disabled) maximum number of TCP connections supported by the Port502 entity
TCP connection number currently opened by the local Port502 entity
TCP connection number currently opened by the remote entity to the local
Port502 entity a table containing the number of unsuccessful TCP connection open tries from a remote TCP entity a table containing Port502 TCP specific information (MsgIn, MsgOut) total number of Port502 messages received from the network total number of Port502 messages sent from the network total number of error messages built by the Port502 messaging entity and sent to the network the support of additional port502 stack statistics:
1 - disabled
2 - enabled additional stack statistics for Port502 (optional)
I/O Scanning Subtree
The I/O_Scanning (3) subtree, or group, contains the objects related to I/O scanning device management and associated MODBUS communications on Port502.
Service ioScanStatus(1) ioScanMaxDevice(2) ioScanPolledDevice(3) ioScanTransSend(4) ioScanGlbHealth(5) ioScanDeviceTable(6)
Indicates . . .
global status of the I/O scanning service:
1 - idle
2 - operational
3 - stopped maximum number of devices supported by the I/O scanning entity number of devices currently polled by the I/O scanning entity total number of transactions sent by the I/O scanning entity global status of health for the I/O scanning service:
2 - OK: Every remote I/O device is responding
4- Warning: At least one remote I/O device is not responding a table containing information on each remote devices polled by the I/O scanning entity
33002479 10/2019
257
SNMP
Global Data Subtree
The Global_Data (4) subtree, or group, contains the objects related to the Global Data service.
Service glbDataStatus(1) glbDataMaxPub(2) glbDataMaxSub(3) glbDataPub(4) glbDataSub(5) glbDataPubErr(6) glbDataSubErr(7) glbDataGlbSubHealth(8) glbDataPubTable(9) glbDataSubTable(10)
Indicates . . .
global status of the Global Data service:
1 - idle
2 - operational
3 - stopped maximum number of published variables configured by the Global Data entity maximum number of subscribed variables configured by the Global Data entity total number of publications sent to the network total number of subscriptions received from the network total number of publication errors detected by the local entity total number of subscription errors detected by the local entity global status of health for the Global Data subscribed variables:
2 - OK: The health status of all subscribed variables is OK
4 - Warning: At least one subscribed variable has a health fault a table containing information on each published variable (the number of publications, the source IP address, the number of errors) a table containing information on each subscribed variable (the number of subscriptions, the source IP address, the number of errors, Health)
Web Subtree
The Web (5) subtree, or group, contains the objects related to the Web server service.
Service webStatus(1) webPassword (2) webSuccessfullAccess (3) webFailedAttempts (4)
Indicates . . .
global status of the Web service:
1 - idle
2 - operational switch to enable or disable the use of Web passwords:
1 - disabled
2 - enabled total number of successful accesses to the Web site total number of unsuccessful accesses to the Web site
258
33002479 10/2019
SNMP
Address Server Subtree
The Address_Server (6) subtree, or group, contains the objects related to the Address Server service. The Address Server can be either a BOOTP server or a DHCP server.
Service addressServerStatus(1)
Indicates . . .
global status of the address server service:
1 - idle
2 - operational
Equipment Profile Subtree
The Equipment_Profiles (7) subtree contains a set of common objects.
Service profileProductName(1) profileVersion(2) profileCommunicationServices(3) profileGlobalStatus(4) profileConfigMode(5) profileRoleName(6) profileBandwidthMgt(7) profileBandwidthDistTable(8) profileLedDisplayTable(9) profileSlot(10) profileCPUType(11) profileTrapTableEntriesMax(12) profileTrapTable(13)
Indicates . . .
the commercial name of the communication product in a string form (for example, 140 NOE 771 11) the software version of the communication product in a string form (for example, Vx.y or V1.1) the communication services supported by the profile (Port502Messaging, I/O scanning Messaging, Global Data, Web, and Address Server) the global status of the communication module:
1 - NOK
2 - OK the IP configuration mode of the communication module:
1 - Local: The IP configuration is created locally
2 - dhcpServed: The IP configuration is created by a remote DHCP server rthe ole name for the IP address management if it exists (empty string if there is none) the status of Bandwidth Management:
1 - disabled
2 - enabled the CPU time distribution between Global Data, Port502 Messaging, I/O scanning a table giving the name and the state of each module’s LEDs the position of the communication module inside the rack if there is one. If there is no rack, the profileSlot value will be zero the host for which that communication module is a part when a CPU type exists (if there is no host, the string is empty) the maximum numbers of entries in the Trap Table (equal to the number of possible remote managers) a table allowing you to enable or disable the private traps for each of the communication services
33002479 10/2019
259
SNMP
Service profileSpecificId(14) profileIpAddress(15) profileIpNetMask(16) profileIpGateway(17) profileMacAddress(18)
Indicates . . .
a unique Profile Specific Identification inside the equipmentProfile object of the Schneider Transparent Factory MIB (for example, the PLC Premium family is 100) the IP address of the SNMP agent the subnet mask associated with the IP address of the SNMP agent (the value of the mask is an IP address with all the network bits set to 1 and all the host bits set to 0) the default Gateway IP address of the SNMP agent the Ethernet media-dependent address of the SNMP agent
NTP Subtree
The NTP (1) subtree contains a set of common objects.
Service ntpStatus(1) ntpSrvAddr(2) ntpLnkSrvStatus(3) ntpReqCnt(4) ntpRespCnt(5) ntpErrCnt(6) ntpDate(7) ntpTime(8) ntpTimeZone(9) ntpDSTStatus(10) ntpLastErr(11)
Indicates . . .
the status of NTP service (not server):
1. 1 = Idle no configuration
2. 2 = Operational the IP address of NTP server in dot notation format the status of link between module and NTP server:
1. 1 = NOK (module can not reach NTP server)
2. 2 = OK the number of requests sent to NTP server the number of responses received from NTP server the total number of communication errors date of the day time of the day current time zone
Daylight Savings Time status:
1. 1 = ON (Daylight Savings Time)
2. 2 = OFF (Standard Time)
Last error code generated by system
260
33002479 10/2019
SNMP
SMTP Subtree
The SMTP (1) subtree contains a set of common objects.
Service emailIndex(1) smtpStatus(2) smtpSrvAddr(3) smtpMailSentCnt(4) smtpErrCnt(5) smtpLastErr(6) smtpLastMailElapsedTime(7) smtpLnkSrvStatus(8) smtpSrvChkFailCnt(9)
Indicates . . .
the index value in the email service table the status of SMTP service (not server):
1 = Idle (no configuration)
2 = operational the IP address of SMTP server in dot notation format the total number of emails sent to the network and successfully acknowledged by the server the total number of email messages that could not be sent to the network or that have been sent but not acknowledged by the server the error code of the last error that occurred while trying to send an email message to the network the number of elapsed seconds since last successful email was sent to the server the status of link with SMTP server:
1. 1 = NOK (not OK), link is down; module failed to contact SMTP server
2. 2 = OK the number of times the link to SMTP server is detected as ‘down.’
See the Electronic Mail Notification Service subtree table (
see page 282
NOTE: A diagram of the Schneider Electric private enterprise MIB subtree appears in Simple
Network Management Service (SNMP) (
see page 247
.
Private Traps and MIB Files
Traps are used to signal status changes to the manager. Using traps helps to avoid adding traffic.
The status changes signaled by the trap are for the:
LEDs
communication ports
I/O scanning health values
Global Data health
NTP service
SMTP service
33002479 10/2019
261
SNMP
The following list describes the characteristics of private traps, which means that they can:
send messages to the two managers whose IP addresses are configured in the SNMP
configuration (either the PL7 or the Web page) use the community name given to this configuration enable or disable each of the Transparent Factory Ethernet Private MIB groups: Switch (1),
Port502_Messaging (2), I/O_Scanning (3), Global_Data (4), Web (5), Address_Server (6),
Equipment_Profiles (7), NTP (8), and SMTP (9)
Private traps are described in the MIB ASN.1 description, which is contained in a .mib
text file.
NTP Traps
1. DST Change Trap: notifies the manager that the NTP server time has changed either from (a) standard time to daylight saving time or (b) daylight saving time to standard time
2. NTP Status Change Trap: sent when the NTP component status changes (ntpStatus(1))
3. Leap Second Trap: sent when leap seconds are inserted
SMTP Traps
1. SMTP Status Change Trap: sent when SMTPStatus changes
2. SMTP Link to Server Status Change: sent when tSMTPLnkSrvStatus changes. Trap is sent when service tries to send an email. Every 30 minutes a periodic test checks the connection to the SMTP server.
262
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Using the NTP Time Service
33002479 10/2019
NTP Time Synchronization Service
Chapter 9
NTP Time Synchronization Service
Introduction
This chapter describes the NTP time synchronization service, which provides an accurate local clock using NTP.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Introducing the NTP Time Synchronization Service
Using the R_NTPC Block for Time Synchronization
NTP Time Synchronization Service Operating Conditions
Configuring the NTP Time Service
Page
33002479 10/2019
263
Using the NTP Time Service
Introducing the NTP Time Synchronization Service
General
The NTP time service synchronizes computer clocks over the Internet. For example, the time of one client is synchronized either with another server or to a referenced time source like a radio or satellite receiver.
Typical time service configurations utilize redundant servers and diverse network paths to achieve high accuracy and reliability. Time service accuracy can be within a millisecond on LANs and up to a few tenths of milliseconds on WANs.
Use the time service for:
event recording (sequence events)
event synchronization (trigger simultaneous events) alarm and I/O synchronization (time stamp alarms)
Features of the NTP Time Service
Some features of the NTP time synchronization service are:
periodic time correction obtained from the reference-standard time server
automatic switch over to a backup time server if a problem occurs with the normal time server system controller projects use a function block to read the accurate clock, a feature that allows project events or variables to be time stamped
estimated time stamping accuracy of:
5 mSec for 140 CPU 651
10 mSec for other CPUs x 0’s and higher
local time zone is configurable and customizable including daylight savings time
Web page diagnostics for the time synchronization service
NTP Time Synchronization and Time Stamps
The Schneider Electric Ethernet interface module NOE 771 11 provides the source timesynchronization signal sent to a controller. The module’s firmware includes an NTP client, which provides time synchronization.
Action
NTP Client requests a time synchronization signal from an NTP server. (Request is sent over an Ethernet network.)
NTP Client stores the time.
NTP Client sends a message to the controller’s clock system counter.
Result
NTP Server responds with a signal.
The controller updates its internal clock with the following granularity:
1 ms
264
33002479 10/2019
Using the NTP Time Service
To read the clock from the PLC application:
Use the R_NTPC function block (
see page 267
) in either MAST, FAST, or Interrupt sections.
On an Ethernet network, all controllers should be synchronized with the same NTP server.
NTP Time Synchronization Definitions
Term
Local clock offset
Time accuracy
Time zone
Daylight savings time
Description of Service
Accurate local time is maintained by adjusting the time by using a local clock offset. The local clock offset is calculated by the formula: ( (T4 - T1) + (T3 - T2) ) / 2
The formula’s variables are:
T1 = Time at which the NTP request is transmitted from the module
T2 = Time at which the NTP Server receives the request (provided by the module in response)
T3 = Time at which the NTP Server transmits the response (provided to the module in the response)
T4 = Time at which the NTP Response is received by the module
Local Time error is < 10 ms compared to the reference NTP server:
Typical: under 5 ms
Worst case: <10 ms
Note:
1. Settling Time: The maximum accuracy is obtained after 2 updates from the NTP server.
2. Polling Period Dependency: The accuracy is dependent upon the polling period. Less than
10 mSec of error is guaranteed for polling periods of 120 seconds or less. To obtain the best possible accuracy and if your network bandwidth will allow, reduce the polling period to a small value.
3. For example, choosing a polling time of 5 seconds provides better accuracy than a time of
30 seconds.
Default format: Universal Time, Coordinated (UTC)
Optional: Configure the service to use a local time zone. For example, GMT+1 for Barcelona or
Paris
Automatic: module adjusts time in spring and fall
33002479 10/2019
265
Using the NTP Time Service
Term
Leap Second
Description of Service
Automatic: module inserts or deletes a second
Note:
1. To compensate for the deceleration of the earth’s rotation, a leap second is inserted in the
UTC time every 18 months by an INTERNATIONAL EARTH ROTATION SERVICE (IERS).
2. Leap seconds will be inserted automatically as needed. If needed, leap seconds are inserted at the end of the last minute in June or December, as commanded by the NTP server.
266
33002479 10/2019
Using the NTP Time Service
Using the R_NTPC Block for Time Synchronization
R_NTPC Representation
The block reads the Ethernet network system time and transfers it into specified parameters. The additional parameter EN should be configured.
R_NTPC block has a 16-bit status word.
R_NTPC Parameter Description
Description of parameters:
Parameter
Display_NTPC
(OUT1)
Calc_NTPC
(OUT2)
Data Type
DT + INT
Description
NTP clock value displayed in:
year, month, day, hours, minutes, and seconds using the DT
format milliseconds as an INT
UDINT+INT NTP clock value displayed in:
seconds as an UDINT
fractions of a second as an INT
33002479 10/2019
267
Using the NTP Time Service
Parameter
Status
Data Type
INT
Description
Low Byte
0
High Byte Description
0 un-initialized state
1
0
0
1 illegal
The CPU is out of synchronization with the NTP server, but the clock has been updated at least once by an external server.
normal operation 1 1
The low byte is managed by the controller
Set = 0
The clock value is NOT available.
The date/time is NOT updated within last two minutes.
Set = 1
The date/time is updated within the last two minutes.
The date/time is acceptable.
The high byte is managed by the NOE.
Set = 0
The NTP server clock value is not available.
Set = 1
The updated date/time is received from server and sent to the module (at least once).
within two-minute time interval
acceptable (10 ms or less error)
For a valid time in the CPU, the low and high bytes of the
STATUS parameter must be set to 1.
268
33002479 10/2019
Using the NTP Time Service
NTP Time Synchronization Service Operating Conditions
Introduction
This material describes special operating conditions related to:
powering up
stop or run PLC downloading applications configuring the time service
Power up
To establish the accurate Ethernet system network time, the system does the following at powerup:
requires the Ethernet module to boot uses the Ethernet module to obtain the time from the NTP server
requires a predefined interval until time is accurate; user’s configuration determines how long before time is accurate may require several updates to achieve peak accuracy
Once an accurate time is received, the service sets the STATUS in the associated time service register.
The time-service clock value starts at 0 until fully updated from the module.
Model
Modicon Quantum with Control Expert
Starting Date
January 1st 1980 00:00:00.00
Stop or Run PLC
Stop and Run have no effect on the accuracy of the clock.
Stop and Run have no effect on the update of the clock.
A transition from one mode to the other has no effect on the accuracy of the system Ethernet network time.
Download Application
The status clock value associated with the time service register in the CPU is reinitialized after an application is downloaded or after an NTP server swap.
There will be two polling periods before the time is accurate.
NTP Configuration
Elsewhere in this section is information about the NTP configuration.
33002479 10/2019
269
Using the NTP Time Service
Configuring the NTP Time Service
Configuring the NTP Time Service
In Control Expert, click the NTP tab to configure the following parameters.
270
33002479 10/2019
Using the NTP Time Service
Field Parameter
NTP Server Configuration
Action
IP address of primary NTP server Enter a valid IP address
IP address of secondary NTP server Enter a valid IP address
Polling period (in seconds Enter a value
min = 1 sec
max = 120 sec default = 5 sec
Time Zone Select from the drop-down menu:
Universal Time, Coordinated (GMT) = default
Custom time zone
Automatically adjust clock for daylight saving change
This parameter is selected by default (check mark appears) if daylight saving time is chosen.
Changing Time Service Parameters
To make any changes to the time synchronization service:
Step
1
2
Action
Enter changes in the appropriate field on the NTP configuration page for one or all of the configurable parameters.
Click Save.
Important Information about the Time Service
NOTE: Regarding the time service:
1. Automatically adjust clock for daylight savings change parameter: If this check box is selected, the module automatically corrects the local time to account for daylight saving time. Therefore, no action is required, since the daylight saving time start and end are automatically changed each year.
2. Polling Time Parameter: The time (in seconds) is the time between time updates from the NTP server. The default is 5 seconds.
3. Storing the Time Service Configuration: The last time service configuration is saved internally in the Ethernet module.
4. Replacing the Ethernet Module: If the Ethernet module has to be replaced, the stored configuration is lost, and the system returns to the default configuration.
33002479 10/2019
271
Using the NTP Time Service
Customizing Time Zone Parameters
If you want a time zone not listed in the time zone table:
Step Action
1 Write the text rules for the custom time zone.
2 Using an FTP client, store your rules in the file:
/FLASH0/wwwroot/conf/NTP/customrules user ID: ntpupdate password: ntpupdate
3 When the rules are written, choose the drop down menu on the NTP Configuration web page, and configure (or reboot) the module by selecting
Time Zone = Custom
Comment
Root directory to store 'customrules' is set by the FTP server as:
/FLASH0/wwwroot/conf/NTP
The NTP component looks for customrules, calls the tz compiler and generates a new file called
'tz_custom'. This file is binary file and should not be edited.
If the tz compiler detects a syntax error in customrules, the error is logged in the file:
/FLASH0/wwwroot/conf/NTP/error.log
1. NTP component is not launched
2. NTP Status field in diagnostic web page displays
NOT OK.
4 If you want more information, the syntax to write those rules along with a few examples are found in the module in:
/FLASH0/wwwroot/conf/NTP/instructions.txt
Time Zone Parameters
Select a time zone from the drop-down menu:
Time Zone Description
Custom
(GMT-12:00) Dateline Standard Time [Eniwetok Kwajalein]
(GMT-11:00) Samoa Standard Time [Midway Is Samoa]
(GMT-10:00) Hawaiian Standard Time [Hawaii Honolulu]
(GMT-09:00) Alaskan Standard Time [Anchorage]
(GMT-08:00) Pacific Standard Time [Los Angeles Tijuana]
(GMT-07:00) Mexican Standard Time [Chihuahua La Paz Mazatlan]
(GMT-07:00) Mountain Standard Time [Arizona Phoenix]
(GMT-07:00) Mountain Standard Time [Denver]
(GMT-06:00) Central Standard Time [Chicago]
(GMT-06:00) Mexico Standard Time [Tegucigalpa]
(GMT-06:00) Canada Central Standard Time [Saskatchewan Regina]
(GMT-06:00) Central America Standard Time [Mexico_city]
Yes
No
Yes
Yes
No
No
Yes
No
No
Yes
Yes
DST
Available
Yes
No
272
33002479 10/2019
Time Zone Description
(GMT-05:00) SA Pacific Standard Time [Bogota Lima Quito]
(GMT-05:00) Eastern Standard Time [New York]
(GMT-05:00) Eastern Standard Time [Indiana (East)] [Indianapolis]
(GMT-04:00) SA Western Standard Time [Caracas La Paz]
(GMT-04:00) Pacific SA Standard Time [Santiago]
(GMT-03:30) Newfoundland Standard Time [Newfoundland St Johns]
(GMT-03:00) E. South America Standard Time [Brasilia Sao_Paulo]
(GMT-03:00) SA Eastern Standard Time [Buenos Aires Georgetown]
(GMT-02:00) Mid-Atlantic Standard Time [South_Georgia]
(GMT-01:00) Azores Standard Time [Azores Cape Verde Island]
(GMT)
(GMT0)
Universal Coordinated Time [Casablanca, Monrovia]
Greenwich Mean Time [Dublin Edinburgh Lisbon London]
(GMT+01:00) Romance Standard Time [Amsterdam CopenHagen Madrid Paris Vilnius]
(GMT+01:00) Central European Standard Time [Belgrade Sarajevo Skopje Sofija Zagreb]
(GMT+01:00) Central Europe Standard Time [Bratislava Budapest Ljubljana Prague Warsaw]
(GMT+01:00) W. Europe Standard Time [Brussels Berlin Bern Rome Stockholm Vienna]
(GMT+02:00) GTB Standard Time [Athens Istanbul Minsk]
(GMT+02:00) E. Europe Standard Time [Bucharest]
(GMT+02:00) Egypt Standard Time [Cairo]
(GMT+02:00) South Africa Standard Time [Johannesburg Harare Pretoria]
(GMT+02:00) FLE Standard Time [Helsinki Riga Tallinn]
(GMT+02:00) Israel Standard Time [Israel Jerusalem]
(GMT+03:00) Arabic Standard Time [Baghdad]
(GMT+03:00) Arab Standard Time [Kuwait Riyadh]
(GMT+03:00) Russian Standard Time [Moscow St. Petersburg Volgograd]
(GMT+03:00) E. Africa Standard Time [Nairobi]
(GMT+03:30) Iran Standard Time [Tehran]
(GMT+04:00) Arabian Standard Time [Abu Dhabi Muscat]
(GMT+04:00) Caucasus Standard Time [Baku Tbilisi]
(GMT+04:00) Afghanistan Standard Time [Kabul]
(GMT+05:00) Ekaterinburg Standard Time [Ekaterinburg]
(GMT+05:00) West Asia Standard Time [Islamabad Karachi Tashkent]
(GMT+05:30) India Standard Time [Bombay Calcutta Madras New Delhi]
(GMT+06:00) Central Asia Standard Time [Almaty Dhaka]
33002479 10/2019
Using the NTP Time Service
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
No
No
Yes
Yes
DST
Available
No
Yes
No
Yes
No
Yes
No
No
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
273
Using the NTP Time Service
Time Zone Description
(GMT+06:00) Sri Lanka Standard Time [Columbo]
(GMT+07:00) SE Asia Standard Time [Bangkok Hanoi Jakarta]
(GMT+08:00) China Standard Time [Beijing Chongqing Hong Kong Urumqi]
(GMT+08:00) W. Australia Standard Time [Perth]
(GMT+08:00) Singapore Standard Time [Singapore]
(GMT+08:00) Taipei Standard Time [Taipei]
(GMT+09:00) Tokyo Standard Time [Osako Sapporo Tokyo]
(GMT+09:00) Korea Standard Time [Seoul]
(GMT+09:00) Yakutsk Standard Time [Yakutsk]
(GMT+09:30) Cen. Australia Standard Time [Adelaide]
(GMT+09:30) AUS Central Standard Time [Darwin]
(GMT+10:00) E. Australia Standard Time [Brisbane]
(GMT+10:00) AUS Eastern Standard Time [Canberra Melbourne Sydney]
(GMT+10:00) West Pacific Standard Time [Guam Port Moresby]
(GMT+10:00) Tasmania Standard Time [Hobart]
(GMT+10:00) Vladivostok Standard Time [Vladivostok]
(GMT+11:00) Central Pacific Standard Time [Magadan Solomon Is New Caledonia]
(GMT+12:00) New Zealand Standard Time [Auckland Wellington]
(GMT+12:00) Fiji Standard Time [Fiji Kamchatka Marshall Is]
Yes
No
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
No
No
No
No
No
No
DST
Available
No
No
274
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Using the Mail Service
33002479 10/2019
Electronic Mail Notification Service
Chapter 10
Electronic Mail Notification Service
Introduction
This chapter describes the electronic mail notification service, which uses SMTP to allow the controller’s project to send e-mail messages.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Introducing the Electronic Mail Notification Service
Mail Service
Using the MBP_MSTR Block for Mail Service Communication
Mail Service Error Codes
Electronic Mail Notification Service Subtree
Page
33002479 10/2019
275
Using the Mail Service
Introducing the Electronic Mail Notification Service
General
The electronic mail notification service allows controller-based projects to report alarms or events.
The automation controller monitors the system and can automatically create an electronic mail message alert with data, alarms, and/or events. Mail recipients can be either local or remote.
Based on predefined events or conditions, messages are created using the MSTR function
block.
The email message is constructed from predefined headers plus variables and text (a maximum of 238 bytes). This message is sent directly from the automation system to the local email server.
Mail headers contain common predefined items—recipient list, sender name, and subject.
These items can be updated by an authorized administrator.
Mail System Types
The Simple Mail Transfer Protocol (SMTP) provides two mechanisms for the transmission of email messages:
direct connection relay system
Mechanism
Direct connection
Relay system
Condition
Sender and receiver are connected to the same transport service.
Sender and receiver are NOT connected to the same transport service.
Result
Email messages are sent to host.
Email messages are relayed from one server to another server.
To relay messages, the SMTP server must be supplied with the address of the:
destination host
destination mailbox
276
33002479 10/2019
Using the Mail Service
Mail Service Client
The Quantum Ethernet module includes an SMTP client. When the module receives a specific request from the project, it sends an email message to the mail server.
Operating Modes and Sending Requests
Because the project sends the email request, a controller cannot send an email message either while in the stopped mode or while downloading a project. As soon as the controller is in RUN mode, the function block sends a request during the first project scan.
Diagnostic counters are reset to 0 after either a power-up, a project download, or a reconfiguration of the mail service.
33002479 10/2019
277
Using the Mail Service
Mail Service
Configuring the Mail Service
As an authorized administrator, use the SMTP Configuration Web page to:
configure the service
set the IP address of the mail server
Elsewhere in this guide is detailed information about configuring the electronic mail service
see page 310
.
NOTE: Default TCP Port: The default TCP port number for SMTP is 25. Ensure that you configure the port specified by your local mail server.
Message Creation and Delivery
A user-defined event or condition triggers the MSTR block to create a message. Each message uses one of three user-defined headers. Each message sent from the controller can contain text and variable information (with a maximum of 238 bytes).
The project selects the appropriate header. Each header contains:
sender name
list of recipients subject
Header Examples
The text and variable information can be defined and updated by an authorized administrator using an embedded Web page (SMTP Configuration page). Define mail headers to indicate different levels of importance. For example:
Header 1 could be "Urgent problem reported by PLC 10"
Header 2 could be "NOTIFICATION from substation 10"
Header 3 could be "INFO message from water system"
Listing different recipients in each of the three headers ensures that the right information quickly flows to the right recipients. The project adds pertinent information such as the specific device, process, or location. This pertinent information is added to the body of the mail message. Then the complete message is sent to an electronic mail server for distribution to recipients. These recipients could be engineers, managers, or process owners.
Security (Authentication)
An optional login (system ID) and password can be used to authenticate the connection to the
SMTP mail server. The SMTP-supported authentication method is LOGIN.
System Diagnostics
The SMTP Diagnostic Web page displays the status of the service. Diagnostic information is also available for remote management using the SNMP network management standard.
278
33002479 10/2019
Using the Mail Service
Using the MBP_MSTR Block for Mail Service Communication
Block Representation
Each operation is designated by a code. To send an email message, use the MBP_MSTR block
see page 171
Parameter Description
The following table describes the MBP_MSTR parameters:
Parameter
ENABLE
ABORT
ACTIVE
ERROR
SUCCESS
CONTROL
33002479 10/2019
Data Type
None
None
None
None
None
INT, UINT
Description
ON = enables selected MBP_MSTR operation
ON = terminates active MBP_MSTR operation
ON while the instruction is active
ON if the MBP_MSTR operation is terminated prior to completion
ON = operation successful
Control block is the first of several network-dependant, contiguous, holding words, and the first of nine contiguous words entered in the top node.
The remaining eight words are:
Displayed: Identifies one of the MBP_MSTR = 13
First implied
Second implied
displays error status (see Mail Service Error Codes
) displays length (number of words transferred)
Third implied
Fourth implied
(not used) high byte: slot address of the NOE module or 0
140 CPU 651 x 0 x FE for the low byte: 0 (not used)
Fifth implied
Sixth implied
Seventh implied
Eighth implied
(not used)
(not used)
(not used)
(not used)
279
Using the Mail Service
Parameter
DATABUF
Data Type
INT, UINT
Description
The DATABUF parameter is the address of the buffer including the data inserted into the body of the email message. The data should be in ASCII format starting at the second word.
Note:
1. Least significant byte of the first word: contains a valid (configured) mail header
(should be of value 1, 2, or 3).
2. Most significant byte of the first word: contains the length of the dynamic part of the message’s subject field. The length must be between 0 and 238 characters.
DATABUF Parameter Description
The first word of the DATABUF parameter contains the following information:
Byte Number
1 (least significant byte)
Description
Mail header
2 (most significant byte) Nb n of extra characters in subject
Value
{1, 2, 3}
User-defined (between 0 and
238)
The second and subsequent words (maximum 119) contain the data (ASCII format) that will be copied into the email message. The first
The remaining characters (2* words transferred.
N -2n n characters will be added to the configured email subject.
) will be part of the message body. N represents the number of
280
33002479 10/2019
Using the Mail Service
Mail Service Error Codes
Error Codes
The electronic mail notification service supports the following error codes:
5109
510A
510B
510C
510D
510E
Hex. Error Code
5100
5101
5102
5103
5104
5105
5106
5107
5108
Description
Internal error.
SMTP component not operational.
Mail header not configured.
Invalid mail header value (should be 1, 2, or 3).
Cannot connect to SMTP server.
Error in transmitting content of email body to SMTP server.
Closing SMTP connection with the server returned an error.
SMTP HELO request failed.
SMTP mail request failed. SMTP server may require authentication.
SMTP RCPT request failed.
No recipient has been accepted by the SMTP server.
SMTP data request failed.
Send email request contains an invalid length.
Authentication failed.
A reset component request has been received while the connection was open.
33002479 10/2019
281
Using the Mail Service
Electronic Mail Notification Service Subtree
Summary
The electronic mail delivery service subtree contains the following objects:
Service emaillndex (1) smtpStatus (2) smtpSrvAddr (3) smtpMailSentCnt (4) smtpErrCnt (5)
Description index value in the email service table global status of the SMTP service:
idle(1): no configuration
operational(2): operational and running stopped(3): stopped
IP address of the remote SMTP server total number of emails sent to the network and successfully acknowledged by server total number of emails:
not sent to the network
sent but not successfully acknowledged by server smtpLastErr (6)
(The smtpLastErr (6) object details the errors.) last error code (see details at Configuring an NOE with TFE
Private MIB) smtpLastMailElapsedTime (7) number of seconds elapsed since last successful email sent smtpLnkSrvStatus (8) status of link between communication module and remote
SMTP server:
NOK (1) = SMTP server can NOT be reached
OK (2) = SMTP server can be reached smtpSrvChkFailCnt (9) number of times link to SMTP server has been detected as down
282
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Embedded Web Pages
33002479 10/2019
Embedded Web Pages
Chapter 11
Embedded Web Pages
Introduction
This chapter presents the contents of the embedded Web pages contained in the Quantum 140
NOE 771 xx modules. These Web pages enable you to access diagnostic information, view configuration information, and change the online configurations for the module.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Quantum Home Page
Monitoring Home Page
Diagnostics Home Page
Setup Home Page
Accessing the Web Utility Home Page
Configured Local Rack Page
Controller Status Page
CPU Configuration Screen: Data Field Descriptions
Remote I/O Status
Quantum PLC Data Monitor Page
SNMP Configuration
Global Data (Publish/Subscribe) Utility Configuration
Configure Address Server Page
Configuring the Time Synchronization Service
Mail Service Configuration
Ethernet Module Diagnostic Pages
NTP Diagnostics Page
Properties Page
Contacting Schneider Electric Page
Page
33002479 10/2019
283
Embedded Web Pages
Quantum Home Page
Home Page
To access the Quantum home page enter the IP address of the module in his web browser. No password is required to display the home page:
Links
From the Quantum home page, you can access the following pages:
Monitoring
see page 285
see page 288
Documentation
see page 287
Enter a user name and a password to access the services on these pages.
Language
In the Quantum home page, you can display the Quantum web pages in either English or Chinese.
284
33002479 10/2019
Embedded Web Pages
Monitoring Home Page
Home Page
This page lists the various viewer services supported by the default Web site of the module and provides links for accessing the services you require.
Illustration
The Monitoring home page looks like this:
To access a service, click on a link. The services include:
Data editor (see Modicon M340, FactoryCast, User Manual) determine their values when the table is animated.
Data editor lite
Graphic viewer determine the values of variables when the graphic is animated.
: for creating variable data tables to determine their values when the table is animated. (This editor contains fewer features than the standard Data editor.)
Graphic editor
: for creating variable data tables to
(see Modicon M340, FactoryCast, User Manual)
(see Modicon M340, FactoryCast, User Manual) : for creating graphics to determine the values of variables when the graphic is animated.
(see Modicon M340, FactoryCast, User Manual) : for viewing graphics to
33002479 10/2019
285
Embedded Web Pages
PLC Program viewer
Silverlight pages pages created with
(see Modicon M340, FactoryCast, User Manual) programs in run mode using a web browser.
Password-protected custom pages
Custom pages without password protection for unrestricted access to web pages created by the user.
: Display Control Expert
(see Modicon M340, FactoryCast, User Manual) restricting access to web pages created by the user.
(see Modicon M340, FactoryCast, User Manual)
(see Modicon M340, FactoryCast, User Manual)
Microsoft Expression Blend®
: for
: for viewing user-defined
:
software that have been added to the web site
286
33002479 10/2019
Embedded Web Pages
Diagnostics Home Page
Home Page
This page lists the various services supported by the default Web site of the module and provides links for accessing the services you require.
Illustration
The Diagnostics home page looks like this:
Links
To access the service you require, click on a link:
Rack Viewer
RIO Status
Alarm Viewer
Ethernet
see page 292
see page 294
see page 312
see page 322
33002479 10/2019
287
Embedded Web Pages
Setup Home Page
Home Page
The NOE 771 11 Setup page lists the various services used to configure the module. You can
navigate to this page from the link on the Home Page (
see page 284
Illustration
The Setup page looks like this:
288
33002479 10/2019
Embedded Web Pages
Setup Page Links
These links are on the Setup page:
Link
SNMP
Address Server
Global Data
Security
FTP
Result
Provides the ability to configure the SNMP Agent in the NOE
Configure the IP assignments, including showing the BOOTP and DHCP database
Displays the Global Data Configuration page. Configure the Group Address,
Multicast filtering, Distribution period, Health Time Out, Health Bits, and Data
Zones. The Global Data Configuration page also displays a Variable Table.
Configure the IP address of the primary and secondary NTP server. Set a polling period. Select a time zone from the drop-down list, and automatic adjustment for daylight savings time.
Configure the email server’s IP and Port (default port is 25). If security is required, select Enable and set a Login and Password. Create three mail headers.
View and edit:
the username and password for accessing the home page
the password for writing variables to the data editor
View and edit the username and password for the FTP service.
33002479 10/2019
289
Embedded Web Pages
Accessing the Web Utility Home Page
Introduction
Each Modicon Quantum 10-/100-Megabit Ethernet module contains an embedded Web server that allows you to access diagnostics and online configurations for the module and its associated controller (PLC).
Pages on the embedded Web site display the following information:
Configurable menus of the Address Server both BOOTP and DHCP and for SNMP
see page 302
Ethernet statistics for the node
see page 283
Controller’s configuration (Controller Status on menu)
Controller’s register values
Remote I/O status and configuration
Remote I/O register values
Remote I/O distributed values
see page 294
see page 292
The FactoryCast/Real Time modules
Configuration and status for Global Data (publish/subscribe)
MODBUS Messaging status
NTP configuration and status
see page 317
see page 86
see page 314
see page 90
see page 79
see page 318
offer these additional pages:
see page 299
The web pages can be viewed using Internet Explorer 4.0 or higher. Either browser supports JRE
1.4.2_04 or higher.
For information about the additional functionality provided by the FactoryCast system in the
Ethernet modules, see the FactoryCast Manual (31001229).
Accessing the Module’s Home Page
Do the following.
Step
1
2
3
4
5
Action
Obtain the full IP address or URL from your system administrator.
Type the address or URL in the address or location box in the browser window. The
Schneider Electric Web Utility home page displays.
On the Quantum home page ( see page 284 )
, click Diagnostics.
You will be requested to supply a user name and password.
After supplying the user name, password, and clicking OK, the Quantum Welcome
Page appears. The Quantum Welcome Page provides the links to all the Quantum configuration and diagnostic pages and to the Data Editor / Data Monitor.
NOTE: The default User Name is USER, and the default password is USER. Both should be changed by the system administrator during module installation.
290
33002479 10/2019
Configured Local Rack Page
Overview
The Configured Local Rack page shows the current configuration:
Embedded Web Pages
Configured Local Rack Page Overview
The following table details the links on the Configured Local Rack page. To view the pages related to each of these topics, click the topic.
Link
Global Data
I/O Scanning
Bandwidth Monitoring
Display general diagnostics of the global data and a table of all published/subscribed variables in a distribution group general diagnostics of the I/O scanning utility and a summary of the status of all modules current information on open TCP connections on Port502 load distribution of the Embedded Server module between the global data utilities, I/O scanning, messaging, and other utilities
Ethernet module statistics with the reset counters link time synchronization service parameters
Email notification service parameters
Upload MIB file upload the private MIB source file
Crash Log file ( see page 319 )
crash message (after crash) and status message (normal operations)
33002479 10/2019
291
Embedded Web Pages
Controller Status Page
Overview
The Controller Status Page provides up-to-date information about the controller and its
configuration. Access this page by selecting the CPU model from the Rack Viewer
or the hyperlink Controller Status.
see page 291
Sample Page
Here is an example of a Controller Status page.
Dynamic Data
Some of the data provided on this page is dynamic. Dynamic data is constantly refreshed at a rate determined by the performance of the Embedded Server, network, and client CPU.
292
33002479 10/2019
Embedded Web Pages
CPU Configuration Screen: Data Field Descriptions
Description Fields
The following table describes the description fields on the CPU Configuration Screen
see page 292
:
Field
System Memory [Kb]
Extended Memory [Kb]
Total Memory [Bytes]
I/O Map Words
Segments
DCP Drop ID
Memory Protect
Constant Sweep
Optimize
Description
Amount of system memory used
Amount of extended memory used
Total memory used in bytes
Number of I/O words mapped.
Number of segments
Drop number for distributed control
Position of the memory protect switch
Current status of constant sweep
Current status of optimization
Word Fields
The following table describes the Word fields on the CPU Configuration Screen (
see page 292
Field
%M
%I
%IW
%MW
Battery Coil
Timer Register
Time of Day Clock
Stopped Codes
Description valid address of %M valid address of %I valid address of %IW valid address of %MW address of battery bit address of timer word address of timer of day clock reason for controlled stopping
ASCII Fields
The ASCII column on the CPU Configuration Screen the ASCII fields.
see page 292
contains information about
33002479 10/2019
293
Embedded Web Pages
Remote I/O Status
Overview
The Remote I/O Status page gives an overview of the status and health of the Remote I/O network communications. Access this page by selecting the CRP Drop down menu item Remote I/O Status or using the hyperlink RIO Status.
Sample Page
Here is an example of a Remote I/O Status page.
Dynamic Data
Some of the data provided on this page is dynamic. Dynamic data is constantly refreshed at a rate determined by the performance of the embedded server, network, and client CPU.
294
33002479 10/2019
Embedded Web Pages
Quantum PLC Data Monitor Page
Introduction to the PLC Data Monitor Page
The following figure shows the Web page that allows you to display Quantum PLC data.
You can add, delete, and copy Quantum PLC data as described in the following list:
Insert additional rows of data by clicking on the Insert Rows button.
Delete specific rows of data by clicking on the Cut Rows button.
Copy in rows of data by clicking on the Paste Rows button.
33002479 10/2019
295
Embedded Web Pages
SNMP Configuration
Overview
This topic describes SNMP configuration for the Quantum Ethernet module through the SNMP
Configuration page.
SNMP Configuration Page
Click the SNMP link in the Setup home page to display the Configure SNMP page:
296
The following table describes the SNMP configuration tasks that you can perform through the Web page:
Task How To
To display the current SNMP configuration Click Show SNMP Configuration.
To clear the fields
To change the SNMP configuration
Click Reset the Form.
Change the information on the page and click
Update SNMP.
33002479 10/2019
Embedded Web Pages
SNMP Page Fields
The following table describes the SNMP fields that you can modify.
Field
Manager I
Manager II
Location [SysLocation]
Contact [SysContact]
Set
Get
Trap
Authentication Failure Trap
Enabled
Information To Be Supplied
IP Address of first SNMP Manager
IP Address of second SNMP Manager
Location of the module
Name of the responsible systems engineer
Designation of user level who can set the configuration
Designation of user level who can view the configuration
Designation of user level who can capture information
Turns on Community Name Checking
After you make your modifications to any of the above parameters, click Update SNMP. A new page displays the following message: "Successfully updated SNMP database." Note that this page contains the same links as those on the Configure SNMP page.
NOTE: Reset the module to implement the changes.
SNMP Community Strings
Use strings to restrict access to the SNMP Agent. These strings should be set to non-trivial names during module installation.
33002479 10/2019
297
Embedded Web Pages
Modifying the SNMP Community Strings
To configure the SNMP community strings:
Step
1
2
Action
Enter the following URL into your browser: http://hostname/secure/embedded/builtin?submit=Configure+SNMP or click the SNMP link in the Setup home page to navigate to the SNMP Configuration page.
Enter the Community names for Set, Get, and Trap into the SNMP Configuration page as shown below.
298
3
4
Click Update SNMP.
To set your changes, use hot swap to reboot the module.
33002479 10/2019
Embedded Web Pages
Global Data (Publish/Subscribe) Utility Configuration
Overview
Whether you use either the Configure Each Device Separately or the Copy Configuration method
see page 195
, the procedure to configure individual parameters is the same. Therefore, in order to use the Global Data (publish/subscribe) utility in the NOE, you need to configure the Global Data parameters including:
Distribution period
Multicast filtering
Health bit location
Global Data base address
Group IP address
The following sections describe in detail the exact steps to configure each parameter on the Global
Data Configuration page.
Illustration
You can change the configuration in the Global Data Configuration page:
33002479 10/2019
299
Embedded Web Pages
Configuring Global Data
After you have completed the Modeling System Configuration process
second method, Copy Configuration, you modify the following parameters:
Distribution period
Health Time Out
Health Bits location
Start address
Type: Pub / Sub / None
see page 195
Please do not change Symbol (description), and Length.
To change the Global Data variables of the group box on the Global Data Configuration page, follow the instructions below.
4
5
Step
1
2
3
6
Action
Adjust the Distribution Period cycle. Enter a value from 1 through 50.
Note: Distribution Period is the minimum number of controller scan times before an update occurs.
Before entering a value in the Group Address field, identify the station’s distribution group. The Group Address entry will be an IP address from 224.0.0.0
through
239.255.255.255
.
Group Address: the Class D Multicast IP address used for a distribution group.
Members of this distribution group are configured to use the same group address; therefore, members can communicate with each other using Global Data.
Set the timeout in the Health Time Out field. This value is measured in milliseconds and can be set to a value that ranges from 50 through 15000 ms (in 50 ms increments)
Note: Health Time Out is the maximum time between received subscriptions before a subscription is declared unhealthy (inoperable).
In the 4x starting address, set the Data Zone field.
If you are connected to an Ethernet switch that supports multicast filtering, click the
Multicast filtering check box.
Enter %MW word (4x register) location for the Health Bits. This is the location for storing health bits.
NOTE: Health bits run in different directions.
I/O scanner health bits run left to right.
Global Data health bits run right to left.
300
33002479 10/2019
Embedded Web Pages
Changing Global Data Variables
To change the Global Data variables that appear in the Variable Table area, follow the instructions below.
Step Action
1 Highlight the identification number in the Data ID column.
2 In the Type column select the publish/subscribe variable type from the drop down list. Three options are available publish, subscribe, or none, displayed as:
NONE
SUB
PUB
3 In the Symbol column you may enter text to describe the variable.
4 In the Address column you see the application address for this variable.
Note: This is a read only field.
5 In the Length column for each row, type a value, which represents the number of
4x registers. The ending 4x register field is automatically updated. If you are using the second method, Copy Configuration, update Length the first time only.
6 When you are finished, click the Update Global Data Configuration button.
Verifying System Operation
To verify that the system is operational, do the following:
Step Action
1 Verify that every controller is running.
2 Look at the health of variables using the Global Data Diagnostics page.
Follow these links: Diagnostics → Ethernet → Global Data
33002479 10/2019
301
Embedded Web Pages
Configure Address Server Page
Overview
This topic describes the DHCP and BOOTP address server configuration for the Transparent
Factory Ethernet modules.
NOTE: To configure the address server for the 140 NOE 771
see Address Server Configuration/Fast Device Replacement
BOOTP process.
x FactoryCast Web server modules,
see page 238
Address Server Page
The Address Server Configuration page appears below:
302
33002479 10/2019
Adding Entries
Create new address server configurations with these steps:
Step Action
1 Press Add a New Entry. A dialog appears in the web frame:
Embedded Web Pages
3
4
5
6
2
Note: The system does not allow you to enter text in both the Role Name and Device
MAC Address text fields. Create either a DHCP configuration (Role Name) or a
BOOTP (Device MAC Address) configuration.
For the address server configuration type (DHCP or BOOTP), enter text in the appropriate field:
Role Name: variable name for DHCP address server configuration
Device MAC Address: MAC address for BOOTP address server configuration
Enter an address in the Device IP Address field. (We have provided an example address.)
Enter an address in the Subnet Mask field. (We have provided an example address.)
Enter an address in the Gateway field. (We have provided an example address.)
Press the Add the Entry button.
33002479 10/2019
303
Embedded Web Pages
When you press the Add the Entry button, a new entry that corresponds to your input appears in the table in the web frame:
When you use the same Add the Entry procedure to add subsequent entries, multiple entries appear in the table:
In the above figure, a user has highlighted the radio button for with the last row of buttons: test_1 . That item can now be edited
Button
Change an Entry
Function
Change the table data for the entry.
Delete an Entry Delete the entry from the table data for the entry.
Note: The selected radio button has no effect on the Add a New Entry function.
Note: You can press the Refresh Address Server Database Table button to refresh the table data at any time.
304
33002479 10/2019
Embedded Web Pages
Configuring the Time Synchronization Service
Configuring the Time Service
You can configure the time service using either the module’s NTP Configuration page in Control
Expert or the embedded Web page.
Time Service Command Buttons
Execute the following commands:
Button
Save
Cancel
Disable NTP
Description
Stores new NTP (time service) configuration. Previous configuration is no longer valid.
Cancels new NTP (time service) configuration. Previous configuration is valid.
IP of Primary and Standby set = 0.
NTP server not polled.
Time in controller not updated.
33002479 10/2019
305
Embedded Web Pages
Configurable Time Service Parameters
Configure or change the following parameters on the NTP Configuration page.
1. IP address of primary NTP server
Enter a valid IP address
2. IP address of secondary NTP server
Enter a valid IP address
3. Polling Period (in seconds)
Enter a value
min = 1sec max = 120sec default = 5 sec
4. Time Zone
Select from drop-down menu
Universal Time, Coordinated (GMT) = default
Custom time zone
5. Automatically adjust clock for daylight saving change
Parameter is selected by default (check mark appears) if daylight saving time is chosen.
Changing Time Service Parameters
To make any changes to the time synchronization service:
Step
1
2
Action
Enter changes in the appropriate field on the NTP Configuration page for one or all of the configurable parameters.
Click Save.
Important Information about the Time Service
NOTE: About the time service:
1. Enable/Disable Daylight Savings Time parameter: If the Enable/Disable check box is selected, the module automatically corrects the local time to account for daylight savings time. Therefore, no action is required, since the daylight saving time start and end are automatically changed each year.
2. Polling Time Parameter: The time (in seconds) is the time between time updates from the NTP server. The default is 5 seconds.
3. Storing the Time Service Configuration: The last time service configuration is saved internally in the Ethernet module.
4. Replacing the Ethernet Module: If the Ethernet module has to be replaced, the stored configuration is lost, and the system returns to the default configuration.
306
33002479 10/2019
Embedded Web Pages
Customizing Time Zone Parameters
If you want a time zone not listed in the time zone table:
Step Action
1 Write the text rules for the custom time zone.
2 Using an FTP client, store your rules in the file:
/FLASH0/wwwroot/conf/NTP/customrules user ID: ntpupdate password: ntpupdate
3 When the rules are written, choose the drop down menu on the NTP Configuration web page, and configure (or reboot) the module by selecting
Time Zone = Custom
Comment
Root directory to store 'customrules' is set by the FTP server as:
/FLASH0/wwwroot/conf/NTP
The NTP component looks for customrules, calls the tz compiler and generates a new file called
'tz_custom'. This file is binary file and should not be edited.
If the tz compiler detects a syntax error in customrules, the error is logged in the file:
/FLASH0/wwwroot/conf/NTP/error.log
1. NTP component is not launched
2. NTP Status field in diagnostic web page displays
NOT OK.
4 If you want more information, the syntax to write those rules along with a few examples are found in the module in:
/FLASH0/wwwroot/conf/NTP/instructions.txt
Time Zone Parameters
Select a time zone from the drop-down menu.
Time Zone
Custom
Description
(GMT-12:00) Dateline Standard Time [Eniwetok Kwajalein]
(GMT-11:00) Samoa Standard Time [Midway Is Samoa]
(GMT-10:00) Hawaiian Standard Time [Hawaii Honolulu]
(GMT-09:00) Alaskan Standard Time [Anchorage]
(GMT-08:00) Pacific Standard Time [Los Angeles Tijuana]
(GMT-07:00) Mexican Standard Time [Chihuahua La Paz Mazatlan]
(GMT-07:00) Mountain Standard Time [Arizona Phoenix]
(GMT-07:00) Mountain Standard Time [Denver]
(GMT-06:00) Central Standard Time [Chicago]
(GMT-06:00) Mexico Standard Time [Tegucigalpa]
(GMT-06:00) Canada Central Standard Time [Saskatchewan Regina]
(GMT-06:00) Central America Standard Time [Mexico_city]
(GMT-05:00) SA Pacific Standard Time [Bogota Lima Quito]
33002479 10/2019
No
Yes
Yes
No
No
Yes
No
No
Yes
Yes
Yes
DST Available
Yes
No
No
307
Embedded Web Pages
Time Zone Description
(GMT-05:00) Eastern Standard Time [New York]
(GMT-05:00) Eastern Standard Time [Indiana (East)] [Indianapolis]
(GMT-04:00) SA Western Standard Time [Caracas La Paz]
(GMT-04:00) Pacific SA Standard Time [Santiago]
(GMT-03:30) Newfoundland Standard Time [Newfoundland St Johns]
(GMT-03:00) E. South America Standard Time [Brasilia Sao_Paulo]
(GMT-03:00) SA Eastern Standard Time [Buenos Aires Georgetown]
(GMT-02:00) Mid-Atlantic Standard Time [South_Georgia]
(GMT-01:00) Azores Standard Time [Azores Cape Verde Island]
(GMT) Universal Coordinated Time [Casablanca, Monrovia]
(GMT0) Greenwich Mean Time [Dublin Edinburgh Lisbon London]
(GMT+01:00) Romance Standard Time [Amsterdam CopenHagen Madrid Paris Vilnius]
Yes
Yes
(GMT+01:00) Central European Standard Time [Belgrade Sarajevo Skopje Sofija Zagreb] Yes
(GMT+01:00) Central Europe Standard Time [Bratislava Budapest Ljubljana Prague Warsaw] Yes
No
No
Yes
No
DST Available
Yes
No
No
Yes
Yes
Yes
(GMT+01:00) W. Europe Standard Time [Brussels Berlin Bern Rome Stockholm Vienna]
(GMT+02:00) GTB Standard Time [Athens Istanbul Minsk]
(GMT+02:00) E. Europe Standard Time [Bucharest]
(GMT+02:00) Egypt Standard Time [Cairo]
(GMT+02:00) South Africa Standard Time [Johannesburg Harare Pretoria]
(GMT+02:00) FLE Standard Time [Helsinki Riga Tallinn]
(GMT+02:00) Israel Standard Time [Israel Jerusalem]
(GMT+03:00) Arabic Standard Time [Baghdad]
(GMT+03:00) Arab Standard Time [Kuwait Riyadh]
(GMT+03:00) Russian Standard Time [Moscow St. Petersburg Volgograd]
(GMT+03:00) E. Africa Standard Time [Nairobi]
(GMT+03:30) Iran Standard Time [Tehran]
(GMT+04:00) Arabian Standard Time [Abu Dhabi Muscat]
(GMT+04:00) Caucasus Standard Time [Baku Tbilisi]
(GMT+04:00) Afghanistan Standard Time [Kabul]
(GMT+05:00) Ekaterinburg Standard Time [Ekaterinburg]
(GMT+05:00) West Asia Standard Time [Islamabad Karachi Tashkent]
(GMT+05:30) India Standard Time [Bombay Calcutta Madras New Delhi]
(GMT+06:00) Central Asia Standard Time [Almaty Dhaka]
(GMT+06:00) Sri Lanka Standard Time [Columbo]
No
Yes
No
Yes
No
Yes
No
Yes
No
No
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
308
33002479 10/2019
Time Zone Description
(GMT+07:00) SE Asia Standard Time [Bangkok Hanoi Jakarta]
(GMT+08:00) China Standard Time [Beijing Chongqing Hong Kong Urumqi]
(GMT+08:00) W. Australia Standard Time [Perth]
(GMT+08:00) Singapore Standard Time [Singapore]
(GMT+08:00) Taipei Standard Time [Taipei]
(GMT+09:00) Tokyo Standard Time [Osako Sapporo Tokyo]
(GMT+09:00) Korea Standard Time [Seoul]
(GMT+09:00) Yakutsk Standard Time [Yakutsk]
(GMT+09:30) Cen. Australia Standard Time [Adelaide]
(GMT+09:30) AUS Central Standard Time [Darwin]
(GMT+10:00) E. Australia Standard Time [Brisbane]
(GMT+10:00) AUS Eastern Standard Time [Canberra Melbourne Sydney]
(GMT+10:00) West Pacific Standard Time [Guam Port Moresby]
(GMT+10:00) Tasmania Standard Time [Hobart]
(GMT+10:00) Vladivostok Standard Time [Vladivostok]
(GMT+11:00) Central Pacific Standard Time [Magadan Solomon Is New Caledonia]
(GMT+12:00) New Zealand Standard Time [Auckland Wellington]
(GMT+12:00) Fiji Standard Time [Fiji Kamchatka Marshall Is]
Embedded Web Pages
No
Yes
No
Yes
No
Yes
Yes
No
Yes
Yes
Yes
No
No
No
No
No
DST Available
No
No
33002479 10/2019
309
Embedded Web Pages
Mail Service Configuration
Configuring the Mail Service with the Email Configuration Page
Use the module’s embedded Web page to configure the Electronic Mail Notification service. No other method is available.
Mail Service Command Buttons
Button
Save
Cancel
Disable Email
Description
Saves the new Email configuration.
Note: The previous configuration is no longer valid and it is not stored.
Cancels the entries in the fields.
The previous configuration is valid.
Clears the stored configuration, and disables the email service.
Note: The next time the service is enabled, a new configuration is required.
310
33002479 10/2019
Embedded Web Pages
Configurable Mail Service Parameters
Parameter
IP address of Email
Port
Password Authentication
Description
Enter a valid IP address. (This parameter identifies the SMTP server.)
Default = 25 (If necessary, you may enter a new value.)
If you want to restrict access, enable Password Authentication by entering a check mark in the box.
Enter values for:
Login:
Any printable character allowed
64 character maximum
Password:
Any printable character allowed
64 character maximum
3 mail headers Each header contains:
sender’s ID in the From: field
32 character maximum; no spaces
list of recipients in the To: field
Separate each email address with a comma.
128 character maximum
fixed part of message in the Subject: field
(32 character maximum)
The Subject field consists of two parts:
1. Fixed (32 character maximum)
2. Dynamic (206 character maximum)
33002479 10/2019
311
Embedded Web Pages
Ethernet Module Diagnostic Pages
Overview
The Ethernet menu contains a list of links for accessing the different diagnostic pages for the
Ethernet module:
Global Data
I/O Scanning
see page 199
Messaging
Statistics
NTP (network time protocol)
Upload MIB File
Crash Log File
see page 86
Click a link to access the desired diagnostics utility.
312
33002479 10/2019
Embedded Web Pages
Global Data Page
Information on the general diagnostics of Global Data can be found at the top of this page:
Status
Number of publications per second
Number of subscriptions per second
This page also shows a table of published and subscribed variables in the same distribution group.
Each variable is identified by its Identifier:
Green for the subscribed variables
Black for the published variables
White for unconfigured variables
Red for variables with communication interruptions
33002479 10/2019
313
Embedded Web Pages
I/O Scanning Page
General diagnostics for the I/O scanning service are shown at the top of this page:
the I/O scanning status
the number of transactions per second the number of connections
A value of NOK in the I/O Scanning Status field indicates that the local system is not scanning. In this case, any data that appears in the Scanned Device Status display is meaningless.
A value of OK in the I/O Scanning Status field indicates that the values in the Scanned Device
Status display are reporting the state of scanned devices.
In the Scanned Device Status display, the colors that appear in each block indicate the following states for specific remote devices:
Green indicates that a device is being scanned
Black indicates that I/O scanning of the specific device has been intentionally disabled via the
Device Control Block
White indicates an unconfigured device
Red indicates a suspect device
314
NOTE: Be aware that the green Scanning indicator may incorrectly remain green for a remote scanned device after the Ethernet cable gets removed from that device. This inaccurate indication
occurs when the health timeout value in the I/O Scanning configuration screen is set to 0
see page 204
.
You should configure an operational health timeout value in the range 1...65535 (in 1 ms increments). If the health timeout value is set to any value in this range, the Scanning indicator reports I/O scanning health correctly.
33002479 10/2019
Embedded Web Pages
Messaging Page
This page provides current information on the open TCP connections on port 502.
The number of sent/received messages on the port can be found at the top of this page.
A table provides, for each connection (numbered from 1 to 64):
remote IP Address
remote TCP port local TCP port number of messages sent from this connection number of messages received from this connection detected event number on this connection
NOTE: Following a request to close a connection, the PLC may hold the connection open in its memory for a few minutes, during which the table will reflect the open connection.
Number of Messages received is not reset after a port 502 connection is closed. Therefore, the count indicates the total number of messages that have been received since the module was started.
The remote address ‘127.0.0.1’ is used as Private System Connection For Diagnostic Feature or
SOAP Communications.
33002479 10/2019
315
Embedded Web Pages
Bandwidth Monitoring Page
This page displays the load distribution of the Embedded Server module between the Global Data utilities, I/O Scanning, Messaging, and other utilities:
Ethernet Statistics Page
The Ethernet Module Statistics page provides information about the status, transmit and receive statistics, and detected errors for the Embedded Server module. Access this page by selecting the
NOE module from the local rack or use the hyperlink Statistics. The following graphic is an example
Ethernet Module Statistics page:
316
NOTE: Refer to Modicon Quantum Ethernet TCP/IP Module User Guide (840 USE 107) and
Modicon Quantum Ethernet TCP/IP Module User Guide (840 USE 115) for definitions of terms.
33002479 10/2019
Embedded Web Pages
NTP Diagnostics Page
Time synchronization service parameters:
Parameter
NTP status
Description
Service is correctly configured (OK)
NTP server status NTP client is connected to the NTP server, and if the server is Primary or Standby
NTP requests
NTP responses
Number of errors
Last error code
Total number of client requests sent to the NTP server
Total number of server responses sent from the NTP server
Total number of unanswered NTP requests
Last detected error code received from the NTP client
Date
Time
Time zone
DST
Date in d/m/y format
Time
Time zone plus or minus Universal Time, Coordinated (UTC)
Daylight saving time (DST) parameter is either
1. on (enabled)
2. off (disabled)
33002479 10/2019
317
Embedded Web Pages
Last Error field displays values, which indicate the type of detected event.
Type of detected event
Component OK and running
Excessive network traffic or server overload
Bad parameters in the configuration
Component is disabled
Incorrect IP
Time zone file absent
Incorrect syntax in the customrules file
4
9
14
15
1
3
Value
0
Email Diagnostics Page
318
Parameter
Email status
Link to Server Status
SMTP Server IP Address
Number of e-mails sent
Description
Email service is correctly configured (OK).
Ethernet module is connected to the SMTP server.
Status is checked at start-up and at least every 30 minutes after start-up:
Green = module connected to server
Red = module NOT connected to server
IP address of the SMTP server
Total number of e-mails sent successfully
33002479 10/2019
Embedded Web Pages
Parameter
Number of Responses from
SMTP Server
Number of Errors
Last Errors
Last Mail Header Used
Number of seconds elapsed since last e-mail successfully sent
Number of times the link to the server has been detected down
Description
Total number of SMTP messages received from the SMTP server
Total number of e-mails not sent because of a detected error
Reason for the last detected error with a code in hexadecimal.
0 indicates no detected error.
Last header used by giving the number.
Counts the number of seconds since the last email was successfully sent.
Number of times the SMTP server could not be reached.
(Link checked every 30 minutes.)
Upload MIB File
When you select Upload MIB File, the File Download dialog box appears. You are asked if you want to save the MIB file or open it:
Crash Log Diagnostics Page
The Crash Diagnostics Page displays a crash log file when an unrecoverable event has occurred, and a status message otherwise.
Press Clear Crash Log File to clear the log file (
see page 349
.
33002479 10/2019
319
Embedded Web Pages
NTP Diagnostics Page
NTP Diagnostic Dialog
Time synchronization service parameters are in the table:
Parameter
NTP status
NTP server status
NTP requests
NTP responses
Number of errors
Last error code
Date
Time
Time zone
DST
Description
Service is correctly configured (OK)
NTP client is connected to the NTP server, and if the server is Primary or Standby
Total number of client requests sent to the NTP server
Total number of server responses sent from the NTP server
Total number of unanswered NTP requests
Last error code received from the NTP client
Date in d/m/y format
Time
Time zone plus or minus Universal Time, Coordinated (UTC)
Daylight saving time (DST) parameter is either
1. on (enabled)
2. off (disabled)
The dialog:
320
33002479 10/2019
Embedded Web Pages
Last Error Field
Last Error field displays values, which indicate the type of error.
Type of Error
Component OK and running
Excessive network traffic or server overload
Bad parameters in the configuration
Component is disabled
Incorrect IP
Time zone file absent
Syntax error in the customrules file
4
9
14
15
1
3
Value
0
33002479 10/2019
321
Embedded Web Pages
Properties Page
Introduction to the Properties Page
You can navigate to the Properties page from the Diagnostics page.The Properties page displays the versions of the Exec, Kernel, Web Server, Web Pages and the Physical Media:
NOTE: This page only reports this information. The fields cannot be changed.
322
33002479 10/2019
Embedded Web Pages
Contacting Schneider Electric Page
Schneider Electric Contact Page
The following figure shows the Contacting Schneider Electric page, which contains information about how to obtain support for the NOE 771 xx modules.
33002479 10/2019
323
Embedded Web Pages
324
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Hot Standby
33002479 10/2019
Hot Standby
Chapter 12
Hot Standby
Overview
The Quantum Ethernt module offers a Hot Standby configuration available for Quantum controllers.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Quantum Hot Standby for Control Expert
Hot Standby Topology
NOE Module Configuration and Hot Standby
140 NOE 771 x1 / 140 NOC 78• 00 IP Address Assignment
140 NOE 771 x1 / 140 NOC 78• 00 Operating Modes in Quantum Hot Standby System
NOE IP Address Swap Times
Network Effects of Modicon Quantum Hot Standby with Control Expert Solution
Page
33002479 10/2019
325
Hot Standby
Quantum Hot Standby for Control Expert
The Hot Standby Solution
RISK OF INCREASE OF TIME TO SWAP
CAUTION
Whenever possible, use of a switch (not a hub) to connect the NOE modules to each other or to the network.
Schneider Electric offers switches. Contact a local sales office for more information.
Failure to follow these instructions can result in injury or equipment damage.
WARNING
UNINTENDED EQUIPMENT OPERATION
Design your application so that unmonitored modules support communication only to noncritical parts of the application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
In the hot standby solution, two identically configured PLC systems are set up to control the same application. One PLC, the primary, runs the application and updates the other secondary (standby)
PLC. The standby maintains awareness of the application status but does not perform any control functions. In the event of a failure in the primary PLC, the standby PLC takes over the primary PLC responsibilities. When the PLC that has failed becomes operational again, it comes back up in the hot standby system as the new secondary PLC.
The NOEs coordinate the swapping of IP addresses. After closing both the client and the server connections, each NOE sends a swap UDP message to its peer NOE. The sending NOE then waits a specified timeout (500 ms) for the peer swap of UDP messages. Either after receiving the messages or after a timeout, the NOE changes its IP address.
NOTE: NOEs must communicate with each other in order to swap IP addresses. Schneider Electric recommends that you connect the primary and secondary NOEs to the same switch because:
Communication failures between the NOEs increases the time to swap.
Connecting 2 NOEs to the same switch minimizes the probability of a communication failure.
NOTE: Schneider Electric recommends that you use a switch (not a hub) to connect the NOEs to each other or to the network. Schneider Electric offers switches; please contact a local sales office for more information.
326
33002479 10/2019
Hot Standby
The NOE waits for either a change in the controller’s Hot Standby state or the swap of UDP messages. Then the NOE performs 1 of 2 Hot Standby actions.
If the NOE . . .
Detects that the new Hot Standby state is either primary or standby
Receives a swap UDP message
Then
The NOE changes the IP address.
The NOE transmits a Swap UDP message and swaps the IP address.
All client/server services (I/O scanner, global data, messaging, FTP, SNMP, and HTTP) continue to run after the switch from the old to the new primary NOE.
NOTE: Failure of an NOE module is not a condition for the primary system to leave the primary state.
Hot Standby and NOE Module Functionality
The following table identifies the Ethernet services that are available and unavailable in a hot standby solution.
Service
I/O Scanning
Global Data
Modbus Messaging
FTP/TFTP
SNMP
HTTP Server
DHCP
NOE 771 Family
Available
Available
Available
Available
Available
Available
Unavailable
NOTE: Only the 140 NOE 771 01 or 140 NOE 771 11 (TCP/IP Ethernet modules) support a
Modicon Quantum Hot Standby with Unity V2.0 system.
33002479 10/2019
327
Hot Standby
Hot Standby Topology
Hot Standby Interconnection
The following diagram shows a Hot Standby system and the relationship between the 2 redundant systems. Two 140 CPU 67• 6• controllers are connected via a link created with fiber optic cable.
The RIOs are connected both to each other (through the fiber optic cable) and to the RIO drops.
328
NOTE: The following three items are required.
1. Two identical systems
2. identical order of modules in each rack
3. identical software revisions
The NOEs are connected to the same switch. Connecting to the same switch is recommended because the NOEs communicate with each other in order to swap the IP address.
There are two reasons to connect to the same switch:
If a failure to communicate between the NOEs occurs, the time to swap increases.
To minimize the probability of a failure, connect the two NOEs to the same switch.
The other requirement for the switches is that they are on the same sub-network.
33002479 10/2019
Hot Standby
NOE Module Configuration and Hot Standby
TCP/IP Configuration
When the NOE module goes into service the first time, it attempts to get its IP address from a
BOOTP server. If a BOOTP server is not available, the NOE module derives its IP address from its MAC address. Connecting to a BOOTP server or deriving the IP address from a MAC address gives you a connection to the NOE, and you can then download a project to the PLC.
All standard rules apply to IP addressing with the additional restriction that the IP address cannot be greater than 253 or broadcast address minus 2. Also, no other device can be assigned the configured IP + 1 address.
33002479 10/2019
329
Hot Standby
140 NOE 771 x1 / 140 NOC 78• 00 IP Address Assignment
Configuring a 140 NOE 771 •1 / 140 NOC 78• 00 Module
Since the primary and standby PLCs in a Quantum Hot Standby system have identical configurations, the configured 140 NOE 771 •1 / 140 NOC 78• 00 module IP addresses are the same. The current local Hot Standby mode determines the IP address.
This table shows how the 140 NOE 771 •1 / 140 NOC 78• 00 module IP addresses are assigned:
Hot Standby State primary CPU standby CPU transition from primary to offline transition from standby to offline
IP Address
IP address configured in Control Expert
IP address configured in Control Expert + 1
IP address configured in Control Expert, if peer controller does not go to primary
IP address configured in Control Expert + 1
IP Address Restrictions
Do not use either the broadcast IP address -1 or broadcast IP address - 2 to configure a
140 NOE 771 •1 / 140 NOC 78• 00 module.
For example, do not configure the primary CPU address as nnn.nnn.nnn.254
. This causes the standby CPU IP address to be nnn.nnn.nnn.255
. The standby CPU would then return the diagnostic code Bad IP configuration.
IP Address Transparency
WARNING
UNINTENDED EQUIPMENT OPERATION
For a Quantum Hot Standby configuration:
Do not use the IP address configured in Control Expert + 1.
Do not use consecutive IP addresses of the IP address configured in Control Expert.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
When a switchover occurs, the new primary PLC takes the IP address of the old primary PLC.
When the PLC that has stopped becomes operational again and rejoins the Hot Standby system, it takes the IP address of the standby PLC.
The new primary 140 NOE 771 •1 / 140 NOC 78• 00 module has the same IP address as the former primary module. The IP address in the secondary module is IP address + 1.
330
33002479 10/2019
Hot Standby
The 140 NOE 771 •1 / 140 NOC 78• 00 modules integrated into the Quantum Hot Standby configuration coordinate this swapping of IP addresses with the management of Ethernet services used.
140 NOE 771 •1 IP Address Swap Time
The following table details the 140 NOE 771 •1 module IP address swap time:
Service swap IP address
I/O scanning
Typical Swap Time
6 ms
1 initial cycle of I/O scanning
Maximum Swap Time
500 ms
500 ms + 1 initial cycle of I/O scanning
140 NOC 78• 00 IP Address Swap Time
The following table details the 140 NOC 78• 00 module IP address swap time:
Maximum swap time
Recommended setting for implicit message
500 ms (IP address swapping) + connection establishment time (3 s)
Set RPI to 1/2 of MAST cycle time (50 ms maximum)
Timeout multiplier setting for EtherNet/IP (EIP) scanner connections:
MAST Cycle Time (ms) Recommended RPI (ms) Timeout Multiplier
20
50
100
200
255
10
25
50
50
50
4
4
4
16
8
Connection Timeout
(ms)
160
200
200
200
200
NOTE: The maximum swap time may increase if the end device does not respond in a timely manner.
NOTE: During the swap, there may be disruption in communication between the 140 NOE 771 •1
/ 140 NOC 78• 00 module and the end device. Confirm that the application can tolerate this communication disruption.
33002479 10/2019
331
Hot Standby
140 NOE 771 x1 / 140 NOC 78• 00 Operating Modes in Quantum Hot Standby System
Operating Modes
The 140 NOE 771 x1 / 140 NOC 78• 00 module modes are:
primary mode:
The Hot Standby mode is primary CPU and client/server services are active.
standby mode:
The Hot Standby mode is standby CPU and server services are active except DHCP.
standalone mode:
The 140 NOE 771 x1 / 140 NOC 78• 00 module is in a non-redundant system, or the CPU is not present or not healthy.
offline mode:
The CPU is stopped.
The Quantum Hot Standby and the 140 NOE 771 x1 / 140 NOC 78• 00 operating modes are synchronized by these conditions:
CPU Module Status present and healthy present and healthy present and healthy present and healthy
Not present or unhealthy
Hot Standby State primary CPU standby CPU offline unassigned
N/A
140 NOE 771 x1 / 140 NOC 78• 00
Operating Mode primary standby offline standalone standalone
Any of the following events affect the 140 NOE 771 x1 / 140 NOC 78• 00 operating mode:
a 140 NOE 771 x1 / 140 NOC 78• 00 module is powered up
a 140 NOE 771 x1 / 140 NOC 78• 00 module executes a Hot Standby switchover a 140 NOE 771 x1 / 140 NOC 78• 00 module goes to offline mode a new application is downloaded to the 140 NOE 771 x1 / 140 NOC 78• 00 module
332
33002479 10/2019
Hot Standby
IP Address Assignment at Power-Up
A 140 NOE 771 x1 / 140 NOC 78• 00 module obtains its IP address assignment at power-up as follows:
If the Hot Standby state is...
unassigned primary CPU standby CPU unassigned to offline transition
Then the IP address assigned is...
Default IP address
IP address configured in Control Expert
IP address configured in Control Expert + 1
See the Offline Mode at Power-up Sequence topic in the next table.
If two 140 NOE 771 x1 / 140 NOC 78• 00 modules power-up simultaneously, then:
Their mode (primary or standby) is determined by the mode of CPU in their rack.
The primary 140 NOE 771 x1 / 140 NOC 78• 00 has the IP address configured in Control
Expert.
The standby 140 NOE 771 x1 / 140 NOC 78• 00 has the IP address configured in Control
Expert + 1.
Offline Mode at Power-up Sequence
Controller A powers up before controller B.
Both controller A and controller B power up at the same time.
Result
IP address of controller A is the IP address configured in
Control Expert.
IP address of controller B is the IP address configured in
Control Expert + 1.
The resolution algorithm assigns the configured IP address to controller A, and it assigns the configured IP address + 1 to controller B.
The 140 NOE 771 x1 / 140 NOC 78• 00 module detects a duplicate IP address, the IP address remains at the default IP and the 140 NOE 771 x1 / 140 NOC 78• 00 module blinks a diagnostic code.
If no IP configuration exists, 140 NOE 771 x1 / 140 NOC 78• 00 modules remains in the standalone mode. The IP address must be obtained for the:
140 NOE 771 x1 via a BOOTP server
140 NOC 78• 00 based on the MAC address
33002479 10/2019
333
Hot Standby
Ethernet Services at Power Up
The following table shows how the status of a 140 NOE 771 x1 / 140 NOC 78• 00 module’s service is affected by the Quantum Hot Standby state:
Hot Standby State Status of 140 NOE 771 x1 / 140 NOC 78• 00 Services
Client Services Client/Server
Services
Server Services
EIP
Scanner
Global
Data
Modbus/EIP
Messaging
FTP SNMP unassigned primary CPU standby CPU offline not running run run stop stop run stop stop run run run run run run run run run run run run
HTTP run run run run
Hot Standby Switchover
The following table describes how the 140 NOE 771 x1 / 140 NOC 78• 00 modules coordinate a
Hot Standby switchover. The 140 NOE 771 x1 module is used as the example in the following procedure.
Step
1
7
8
4
5
2
3
6
9
Action
In a Hot Standby configuration NOE A is running in the primary PLC and NOE B is in the standby
PLC.
NOE A detects that its PLC has changed from primary CPU to the offline mode.
NOE A changes from primary NOE to offline with the same Ethernet services running and starts its watchdog timer (with a 500 ms time-out setting). It waits for a message to swap IP addresses from NOE B.
NOE B detects that its PLC has changed state from standby PLC to primary CPU.
NOE B stops all its Ethernet services, sends a request to NOE A for the synchronization of the
IP address swap, starts its watchdog timer (with a 500 ms time-out setting) and waits for a response from NOE A.
When NOE A receives the request from NOE B (or after the NOE A watchdog timer times out), it stops all its Ethernet services:
If it has received a request, NOE B sends a response to NOE A.
If its watchdog timer has timed out, NOE B does not send a response.
NOE A then swaps its IP address and starts the secondary services.
NOE B swaps IP addresses and starts Ethernet services as the primary NOE.
After NOE A senses that its local CPU changes from offline to standby, it takes the secondary
IP address.
NOE B now becomes the primary NOE.
334
33002479 10/2019
Hot Standby
Step
10
Action
NOE B opens all client connections, listens for all server connections, and reestablishes those connections.
NOE A listens for all server connections and reestablishes those connections.
11
NOTE: During the Hot Standby switchover, there is a loss of communication during 500 ms between the PLC and the HMI and/or Control Expert.
Going to Offline
When either the CPU stops or the Hot Standby CPU goes to offline mode, 2 events occur:
1. the 140 NOE 771 x1 / 140 NOC 78• 00 module goes to the offline mode
2. the 140 NOE 771 x1 / 140 NOC 78• 00 module uses the IP address of the present configuration
The IP address assignment when going offline:
Hot Standby State primary CPU to offline standby CPU to offline
IP Address Assigned Is...
configured IP address, if other controller does not go to primary
CPU mode configured IP address + 1
NOTE: For more information, refer to the 140 NOE 771 x1 / 140 NOC 78• 00 IP Address
see page 330
33002479 10/2019
335
Hot Standby
NOE IP Address Swap Times
Description
The following table details the 140 NOE 771 •1module address swap times, such as the time to close connections, time to swap IP addresses or time to establish connections:
Service
Swap IP addresses
I/O Scanning
Global data
Client messaging
Server messaging
FTP/TFTP server
SNMP
HTTP server
Typical Swap Time
6 ms
1 initial cycle of I/O scanning
Maximum Swap Time
500 ms
500 ms + 1 initial cycle of I/O scanning
500 ms + 1 CPU scan For swap times, please see the
Quantum NOE 771xx Ethernet
Modules User Guide (840 USE 116).
1 CPU scan
1 CPU scan + the time for the client to reestablish the connection
The time for the client to reestablish the connection
1 CPU scan
The time for the client to reestablish the connection
500 ms + 1 CPU scan
500 ms + the time for the client to reestablish the connection
500 ms + the time for the client to reestablish the connection
500 ms + 1 CPU scan
500 ms + the time for the client to reestablish the connection
336
33002479 10/2019
Hot Standby
Network Effects of Modicon Quantum Hot Standby with Control Expert Solution
Overview
The Modicon Quantum Hot Standby with Control Expert solution is a powerful feature of NOEs, a feature that increases the reliability of your installation. Hot Standby uses a network, and using the
Hot Standby feature over a network can affect the behavior of:
browsers
remote and local clients
I/O scanning service global data service
FTP/TFTP server
The following are factors you may encounter while using the Modicon Quantum Hot Standby with
Control Expert solution.
Browsers
If a browser requests a page and during the process of downloading that page an IP address switchover occurs, the browser either hangs or times out. Click the Refresh or Reload button.
Remote Clients
Hot Standby switchover affect remote clients.
A NOE module resets under the following conditions:
Remote Connection Request during Hot Standby : If a remote client establishes a TCP/IP connection during a Hot Standby switchover, the server closes the connection using a TCP/IP reset.
Hot Standby Switchover during Remote Connection Request : If a remote client makes a connection request and a Hot Standby switchover occurs during the connection request, the sever rejects the TCP/IP connection by sending a reset.
Outstanding Requests : If there is an outstanding request, the NOE module does not respond to the request, but the NOE module does reset the connection.
The NOE module does a Modbus logout if any connection has logged in.
Local Clients
During a switchover, the NOE module resets all client connections using a TCP/IP reset.
33002479 10/2019
337
Hot Standby
I/O Scanning Service
WARNING
UNINTENDED EQUIPMENT OPERATION - DEVICES GO TO THEIR FALLBACK STATES
DURING SWITCHOVER
Configure Ethernet output devices to their Hold Last Value fallback state whenever possible.
Output devices that support only a Set to Zero fallback state may produce a pulse during switchover.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
NOTE: When you select hold last in a 140 CPU 651 •0 coprocessor, the input data may fall back to 0 when the I/O scanner health bits are NOT OKAY. Confirm that the I/O scanner health bits are valid (OK=1) before removing the Ethernet cable to maintain hold last value.
I/O scanning provides the repetitive exchange of data with remote TCP/IP nodes I/O devices.
While the PLC is running, the primary CPU NOE sends Modbus read/write, read, or write requests to remote I/O devices, and transfers data to and from the PLC memory. In the secondary controller, the I/O scanning service is stopped.
When the Hot Standby switchover occurs, the primary CPU NOE closes all connections with I/O devices by sending a TCP/IP reset. The I/O scanning service in this NOE is standby CPU.
After the switchover, the new primary CPU NOE re-establishes the connection with each I/O devices. It restarts the repetitive exchange of data with these re-connections.
The module provide the I/O scanning feature. Configure this feature with the Control Expert software.
Using either method, the configuration and transfer of data between network addresses can be done without using the MSTR/IEC function block.
NOTE:
Account for the following Ethernet I/O scanning considerations during a switchover.
If MSTR/IEC function block is used for TCP/IP, only some of the opcode is used. Therefore, the block does not complete its transaction, and it returns error code 0•8000.
While the NOE module is in the process of performing the transaction, a new MSTR/IEC function block may become active.
The output states of the scanned I/Os follows the state defined in the last value option configured in the I/O scanning table of the NOE module (in Control Expert software).
These 2 states are either: a. set to 0 b. hold last
With the above considerations, we recommend using switchover with Ethernet I/O scanning for less critical applications.
338
33002479 10/2019
Hot Standby
Global Data (Publish/Subscribe) Service
The Hot Standby primary CPU NOE is 1 station within a distribution group. Distribution groups exchange application variables. Exchanging application variables allows the system to coordinate all the stations in the distribution group. Every station publishes local application variable in a distribution group for all other stations and can subscribe to remote application variables independent of the location of the producer.
The communication port has only 1 multicast address.
In this network service, the Modicon Quantum Hot Standby with Control Expert controllers are viewed like only 1 station. The primary CPU NOE publishes the Hot Standby application variables and receives the subscription variables. The secondary NOE global data service is in a stopped state.
When the Hot Standby switchover occurs, the primary CPU NOE stops the global data service. The
NOE module does not publish the local variable during a switchover. And after the switchover, the new primary CPU NOE starts to publish application variables and to receive the subscription variables.
FTP/TFTP Server
The FTP/TFTP server is available as soon as the module receives an IP address. Any FTP/TFTP client can logon to the module. Access requires the correct user name and password. Modicon
Quantum Hot Standby with Control Expert allows only 1 active FTP/TFTP client session per NOE module.
When the Hot Standby switchover occurs, the primary CPU and secondary NOEs close the
FTP/TFTP connection. If you send an FTP/TFTP request during the switchover, the communication is closed.
Whenever you re-open communication, you must re-enter a user name and a password.
33002479 10/2019
339
Hot Standby
340
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
33002479 10/2019
Appendices
Introduction
The appendices provide supplementary reference information for the Quantum 140 NOE 771 series of modules and the 140 NWM 100 00 module.
xx
What Is in This Appendix?
The appendix contains the following chapters:
Chapter
A
B
C
D
Chapter Name
Maintenance
Specifications
Quantum Ethernet TCP/IP Modbus Application Protocol
Installation and Configuration of a Modicon Quantum Platform
Page
33002479 10/2019
341
342
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Maintenance
33002479 10/2019
Maintenance
Appendix A
Maintenance
Introduction
This chapter details information about system maintenance including accessing and clearing the crash log and downloading the new NOE exec.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Responding to Errors
Reading and Clearing the Crash Log
Downloading a New NOE Exec
Downloading a New NOE Exec via FTP
Downloading a New NOE Kernel
Page
33002479 10/2019
343
Maintenance
Responding to Errors
Overview
The following information describes how to respond to errors on the NOE module.
Detecting Errors
When faults occur, the NOE module’s LED display can help you determine what went wrong. The following figure shows the pattern that the LEDs should display during normal operation.
344
The Run indicator will be solid. The Coll (collision) LED may flash, indicating that collisions are occurring on the Ethernet network. Such collisions are normal.
If a fault occurs, the normal LEDs may be extinguished or other indicators may light. This topic discusses errors reported by the Active, Ready, Coll, Link, Kernel, Appl and Fault indicators.
For each type of error, try the suggested remedies in the order given. If no remedy suggested here overcomes the error, call your local service representative or call Schneider Electric customer service at 1-800-468-5342 for further directions.
33002479 10/2019
Maintenance
Procedure for Responding to an Active LED Error Indicator
If the Active LED fails to light, the NOE module is not communicating with the backplane . The following procedure describes the steps to perform to respond to an Active LED error.
Step Action
1 Make sure the NOE module and the controller are installed properly.
2 Verify that the controller is working; if it is not, replace it.
3 If neither the new controller nor the NOE module functions, replace the backplane.
4 Make sure that the number of network option modules (including NOE, NWM, NOM, and CRP 811 modules) in the backplane is not exceeded:
140 CPU 311 10: 2 modules
140 CPU 670 60: 3 modules
140 CPU 434 12A, 140 CPU 534 14A, 140 CPU 651
140 CPU 678 61: 6 modules x 0, 40 CPU 652 60,
140 CPU 658 60, 140 CPU 671 60, 140 CPU 672 60, 140 CPU 672 61,
5 Check the version of the controller executive. You must have version 2.0 or later to support the Ethernet module. Earlier versions do not recognize the module.
6 If steps 4 and 5 above check out ok, replace the NOE module.
Procedure for Responding to a Ready LED Error Indicator
If the Ready LED fails to light, the NOE module has failed internal diagnostic tests. The following procedure describes the steps to perform.
Step Action
1 Make sure that power has been applied to the backplane.
2 If step 1 checks out ok, replace the NOE module.
Procedure for Responding to a Link LED Error Indicator
If the Link LED fails to light, the NOE module is not communicating with the Ethernet hub/switch.
The following procedure describes the steps to perform to respond to a Link LED error.
Step Action
1 Make sure that the cable has been installed correctly and the module is functioning properly.
2 Verify that the hub/switch is working properly.
3 If steps 1 and 2 check ok, replace the NOE module.
33002479 10/2019
345
Maintenance
Kernel LED Error
The following table describes the Kernel LED errors that may occur and how to respond to them.
If
The Ready LED is on and the Kernel LED is flashing
The Ready LED is on and the Kernel LED is shining steadily,
Either of the above conditions exists.
Then
The module has detected an invalid software image.
An attempt to download a software image has failed and the module is in kernel mode.
Download a new NOE Exec
Fault LED
The Fault LED will flash briefly following an error as the module attempts to recover.
The following figure shows the Fault LED.
346
33002479 10/2019
Maintenance
Collision LED Error
If the twisted pair cable has not been connected properly, the Coll LED will shine steadily and the
Link LED will be extinguished. (This condition does not occur with fiber optic modules.)
The following figure shows the Collision LED.
Procedure for Responding to a Collision LED Error
If the Collision LED fails to light, use the following procedure.
Step
1
2
Action
Make sure that the cable has been installed and is working properly.
Verify that the Ethernet Hub/Switch is working properly.
33002479 10/2019
347
Maintenance
Collision LED Normal Condition
If the Coll LED is flashing, the module is reporting collisions on the Ethernet network. While such collisions are normal, the frequency of the flashes is an indication of the volume of traffic on the network. The flashes may be so frequent that the LED appears to be shining steadily. Heavy traffic will slow communications. If response time is important to your application, you should consider segmenting your network to reduce the frequency of collisions.
The following figure shows the Collision LED under normal conditions.
Run LED
The following table describes the action to be taken if the Run LED is flashing. The action depends on the number of flashes in sequence.
Number of Flashes in Sequence Action
Three Check Ethernet connection
Four
Five
Change IP address
Provide IP address
Six
Seven
Connect using default IP address and configure
Download a new NOE Exec ( see page 350 )
Application LED
If the module crashes, it will note the reason in a log. If the module is able to recover, the Appl LED will light, indicating that an entry has been made in the crash log. You can read and clear the crash log
see page 349
.
348
33002479 10/2019
Maintenance
Reading and Clearing the Crash Log
Overview
The following information describes the crash log.
Introduction
The crash log provides you with the ability to capture conditions that lead to an anomalous condition. By providing the crash log to Schneider Electric technical support, you can facilitate their assistance in resolving your problems.
NOTE: The crash log is provided with the understanding that, with a complex product in thousands of customer applications, there may be conditions that require advance diagnostics. The crash log is one of the tools used to solve complex problems.
The Crash Log
If the Appl (application) indicator is on, entries have been made in the crash log. The log may hold up to 64K of entries.
Reading the Crash Log
The crash log can be read from the embedded web pages or via FTP.
Procedure for Reading the Crash Log via FTP
To access the crash log via FTP:
Step
1
2
3
Action
Log in to the module’s FTP server.
Change the directory to wwwroot/conf/diag .
Perform an FTP to get the crash log file: get crash.log
Clearing the Crash Log
The crash log can be cleared from the embedded web pages or via FTP.
Procedure for Clearing the Crash Log via FTP
To access the crash log via FTP:
Step
1
2
3
Action
Log in to the module’s FTP Server.
Change the directory to wwwroot/conf/diag.
Perform an FTP to delete the crash log file: rm crash.log
33002479 10/2019
349
Maintenance
Downloading a New NOE Exec
Introduction
The following tools can be used to download a new NOE Exec:
Schneider Electric programming packages (see corresponding manuals)
FTP
Use the OS loader to update the NOE Executive and web pages. (Refer to the Control Expert documentation.)
350
33002479 10/2019
Maintenance
Downloading a New NOE Exec via FTP
Exec Version
Please check the current NOE Exec file version on the NOE Properties Web page.
Follow these links: | Diagnostics | NOE Properties |
Procedure
The following procedure describes the steps to use to download a new NOE Exec via FTP. An example follows the procedure.
Step Action
1 At the DOS prompt, type FTP , followed by the IP Address and press Enter.
2 At the User prompt, type: USER and press Enter.
3 At the password prompt, enter your FTP Password and press Enter.
4 At the FTP prompt, type cd wwwroot/conf/exec and press Enter.
5 At the FTP prompt, type put and press Enter.
Note: Pay attention that the NOE771xx.bin has to be to the local path on your PC
(default path: c:\ ).
6 At the local file prompt, type NOE771xx.bin
and press Enter.
7 At the remote file prompt, type NOE771xx.bin
and press Enter.
8 After the transfer is complete you must reboot the NOE to allow the new EXEC to become operational.
Note: The file name is case-sensitive and must be entered with the name in uppercase and the extension in lowercase as shown in the figure below.
For example: NOE771xx.bin
33002479 10/2019
351
Maintenance
Sample FTP Session
The following FTP session was used to download an NOE Exec.
NOTE: The NOE Kernel can not be downloaded via FTP.
Reboot Information after FTP
NOTE: After downloading by FTP, reboot the module.
Perform a download or a reboot when your system can tolerate these actions.
352
33002479 10/2019
Maintenance
Downloading a New NOE Kernel
Procedure
The NOE Executive (Exec) adds a new feature that allows updating of the low level Kernel within the NOE module’s firmware. For the proper installation of new kernel firmware, use the following procedure.
Step Action
1 Check the current version of the NOE module’s Executive firmware (Exec file).
2 If the Exec is not the appropriate version, the Exec must be updated before updating the Kernel.
3 Use the EXECLoader to load the latest version of the EXEC.
4 After loading the new Exec and before loading the Kernel, make sure to cycle power to the NOE module.
5 Load the Kernel using the EXECLoader.
6 After the transfer displays as Successful, the NOE module needs approximately
1 minute to burn the new Kernel into its Flash memory.
7 The NOE module goes go through a reboot sequence.
Kernel Version
CAUTION
UNINTENDED EQUIPMENT OPERATION
Failure to perform the preceding update procedure will render the NOE module inoperable.
Failure to follow these instructions can result in injury or equipment damage.
The NOE Kernel can not be downloaded via FTP.
Please check the current NOE Kernel version on the NOE Properties (
see page 322
Follow these links: | Diagnostics | NOE Properties |
33002479 10/2019
353
Maintenance
354
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Specifications
33002479 10/2019
Specifications
Appendix B
Specifications
Specifications
140 NOE 771 •• Specification Table
The main specifications for the Quantum 140 NOE 771 xx Ethernet module are described in the following table:
Communication Ports
Bus Current Required
Power Dissipation
Fuse
Programming Software
Type and version
One auto-sensing 10/100 BASE-T shielded twisted pair (RJ-45 connector) port and one 100 BASE-FX (MT-RJ connector) port. Both ports transmit and receive Modbus commands encapsulated in TCP/IP protocol
750 mA
3.8 W
None
Concept, Ver. 2.2, or higher
Unity Pro, Ver. 1.0, or higher
Modlink, Ver. 2.0, or higher
Modsoft, Ver. 2.6, or higher
ProWORX NxT, Ver. 2.1, or higher
Firmware
CPU Type and version
NOE Upgradeable
Operating Conditions
Temperature
Humidity
Altitude
Vibration
Quantum Executive, Ver. 2.0, or higher
Field Upgradeable via FTP or Programming Panel.
0 to +60° C
0 to 95% Rh non condensing @ 60° C
15,000 ft (4500 m)
10-57 Hz @ 0.0075 mm d.a
57-150 Hz @ 1 g
Storage Conditions
Temperature
Humidity
Free Fall
Shock
-40 to +85°C
0 to 95% Rh non condensing @ 60°C
1 m unpackaged
3 shocks / axis, 15 g, 11 ms
33002479 10/2019
355
Specifications
140 NWM 100 00 Specification Table
The main specifications for the Quantum 140 NWM 100 00 Ethernet module are described in the following table:
Specification Description
Communication Ports One auto-sensing 10/100 BASE-T shielded twisted pair (RJ-45 connector) port and one 100 BASE-FX (MT-RJ connector) port.
Both ports transmit and receive Modbus commands encapsulated in TCP/IP protocol
Bus Current Required 900 mA
Power Dissipation 4.5 W
Fuse
Programming Software
None
Type and version
NOE Upgradeable
Operating Conditions
Concept, Ver. 2.6, or higher
Unity Pro, Ver. 1.0, or higher
Firmware
CPU Type and version Quantum Executive, Ver. 2.6, or higher
Field Upgradeable via FTP or Programming Panel.
Temperature
Humidity
Altitude
Vibration
0 to +60° C
0 to 95% Rh non-condensing @ 60° C
15,000 ft (4500 m)
10-57 Hz @ 0.0075 mm d.a
57-150 Hz @ 1 g
Storage Conditions
Temperature
Humidity
Free Fall
-40 to +85°C
0 to 95% Rh non-condensing @ 60°C
1 m unpackaged
3 shocks/axis, 15 g, 11 ms Shock
Immunity
International Standard IEC 61131-2
US Standard UL 508
European Standard
Canadian Standard
Agency Approvals
EN61131-2, EN50081-2
CAN/CSA C22.2 No. 142
UL: UL 508
CSA: CSA 142
CE: EN61131-2
Factory Mutual Class 1 Division 2
356
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Ethernet TCP/IP Modbus Application Protocol
33002479 10/2019
Quantum Ethernet TCP/IP Modbus Application Protocol
Appendix C
Quantum Ethernet TCP/IP Modbus Application Protocol
Introduction
This chapter describes the Quantum Ethernet TCP/IP Modbus Application Protocol.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Modbus Application Protocol Overview
Modbus Application Protocol PDU
Modbus Application Protocol Service Classes
Modbus Application Protocol PDU Analysis
TCP/IP Specific Issues
Closing a TCP Connection
Reference Documents
Page
33002479 10/2019
357
Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol Overview
Introduction
The following information describes the Modbus Application Protocol (MBAP).
The Modbus Application Protocol (MBAP) is a layer-7 protocol providing peer-to-peer communication between programmable logic controllers (PLCs) and other host-based nodes on a
LAN. Collectively, these nodes implement all or part of a control application used for industrial automation applications in the automotive, tire and rubber, food and beverage, and utilities industries, to name a few
Client-Server Communications
Modbus protocol transactions are typical request-response message pairs between a client node and a server node. These nodes function as follows
Client : The node that initiates a data transaction is called a module provides the user with the capability to transfer data to and from nodes on a TCP/IP network using a communication instruction. All PLCs that support networking communication capabilities over Ethernet can use either the MBP_MSTR Ladder Logic instruction to read or write controller information or IEC communication blocks.
Server : The node that receives an inquiry is the server client . The Modicon Quantum Ethernet
. Using the standard Modbus/TCP protocol, the Modicon Quantum Ethernet module provides access to controller data. Any device, PC, HMI package, another PLC, or any Modbus/TCP compliant device can access data from the PLC.
The Modbus/TCP server also allows programming panels to log into the controller over
Ethernet.
Modbus requests contain function codes representing several classes of service including data access, online programming, and program download and upload classes. Modbus responses can be ACKs with and without data, or NACKs with error information.
The Modbus Application Protocol can be transmitted over any communication system that supports messaging services. However, the current Quantum implementation transports Modbus
Application Protocol PDUs over TCP/IP. The Quantum PLC accommodates both Ethernet II and
IEEE 802.3 framing, although Ethernet II framing is the default.
358
33002479 10/2019
Ethernet TCP/IP Modbus Application Protocol
Limitations
The Modicon Quantum Ethernet module supports up to 64 simultaneous Modbus/TCP server connections. To guarantee consistency of changes to the controller configuration, the module allows only one programming panel to be logged in at a time.
The module supports these Modbus/TCP commands:
Read Data
Write Data
Read/Write Data
Get Remote Statistics
Clear Remote Statistics
Modbus 125 Commands (used by programming panels to download a new exec to the module
For More Information
For more information about Modbus communications, consult the Modbus Protocol Reference
Guide (PI-MBUS-300). For more information about communication blocks, consult Chapter 4,
Transferring Data Using Communication Blocks
see page 119
.
33002479 10/2019
359
Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol PDU
Overview
The following information describes the structure and content of the Modbus Application Protocol
PDU.
Description
The Modbus Application Protocol PDU, mbap_pdu, is received at TCP port number 502. The current maximum size of the mbap_pdu for this class of services is 256 bytes. The structure and content of the mbap_pdu is defined to be: mbap_pdu::={inv_id[2], proto_id[2], len[2],dst_idx[1], data=mb_pdu}
The header is seven bytes long and includes the fields listed in the following table:
Field inv_id proto_id len
Description
[2 bytes] invocation id used for transaction pairing
[2 bytes] used for intra-system multiplexing, default is 0 for Modbus services
[2 bytes] the len field is a byte count of the remaining fields, and it includes the dst_id and data fields
The remainder of the pdu includes two fields:
Field dst_idx data
Description
[1 byte] destination index is used for intra-system routing of packets (currently not implemented)
[n bytes] this is the service portion of the Modbus pdu, mb_pdu, and it is defined below
The service portion of the Modbus Application Protocol, called mb_pdu, contains two fields: mb_pdu::={func_code[1], data[n]}
The following table describes the fields in mb_pdu.:
Field func_code{1 byte data
Description
Modbus function code
[n bytes] this field is function code dependent and usually contains information such as variable references, variable counts, and data offsets
The size and content of the data field are dependent on the value of the function code.
360
33002479 10/2019
Ethernet TCP/IP Modbus Application Protocol
Example
Here are the values for a sample mbap_pdu for reading a register:
00 01 00 00 00 06 01 03 00 00 00 01
The following table shows the structure and content for this example: inv_id 00 01 proto_id len dst_idx func_code data
00 00
00 00
01
03
00 00 00 01
33002479 10/2019
361
Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol Service Classes
Introduction
There are several classes of service that are part of the Modbus Application Protocol. Each of these classes is described below.
Data Access
Read/write both discrete and analog data values from PLC register files.
Online Programming
Services make relatively minor alterations to ladder logic programs with a highly controlled introduction of these changes into the executing program.
Image Download/Upload
Image download services support the downloading of a ladder logic control program to the PLC.
Image upload services support the uploading of a ladder logic control program from a PLC to PC host for archival/backup purposes.
Configuration
Configuration services allow the user to define parameter values which affect the PIC’s register files, I/O map, communication port configuration and scan attributes, to name a few.
Device Execution State Control
The class of service allows the user to start/stop the PLC scan execution. These services require the user to be in an application login context which is obtained through other Modbus services.
362
33002479 10/2019
Ethernet TCP/IP Modbus Application Protocol
Modbus Application Protocol PDU Analysis
Overview
The following information provides an analysis of the Modbus Application Protocol.
Analysis
The Modbus Application Protocol PDU is transmitted over a TCP/IP Ethernet stack. Both Ethernet
II and IEEE 802.3 framing will be accommodated. Ethernet II framing is the default.
. . . from the wire in for IEEE 802.3 framing . . .
. . . is IEEE 802.3 framing if length <=1500 . . .802.3_pdu ::=
{dst_addr[6], src_addr[6], length[2], data=802.2_pdu} *an IEEE 802.3
PDU has a maxFrameSize of 1518 octets
*an IEEE 802.3 PDU has a minFrameSize of 64 octets802.2_pdu : {dsap[1], ssap[1], frm_cntrl[1], snap_hdr[5], data=ip_pdu} *the snap_hdr is associated with a "well-known" 802.2 sap snap_hdr
::={org_code[3], ethertype[2] }
*the snap hdr (sub network access protocol) allows the older style
Ethernet protocols to run on the newer IEEE 802.2 interface. The
ethertype parameter indicates the service, ex. ip or arp. IP has a value
0x800. . . . from the wire in for Ethernet II framing . . .
. . . is Ethernet II framing if length >1500 . . .802.3_pdu ::=
{dst_addr[6], src_addr[6], length[2], data=ip_pdu} . . . the common part of the packet begins here . . .ip_pdu ::= {ip_hdr[20], data=tcp_pdu}tcp_pdu ::= {tcp_hdr[24], data=appl_pdu=mbap_pdu}
The mbap_pdu is the Modbus Application Protocol whose messages are received at a well-known port. The current maximum size of the mbap_pdu for this class of services in 256 bytes.
33002479 10/2019
363
Ethernet TCP/IP Modbus Application Protocol
Structure and Content
The structure and content of the mbap_pdu is defined to be: mbap_pdu ::={ inv_id[2], proto_id[2], len[2], dst_idx[1], data=mb_pdu
}The header is 7 bytes long, and includes the following fields:
inv_id [2 bytes] invocation id used for transaction pairing proto_id [2 bytes] used for intra-system multiplexing, default is
0 for Modbus
services len [2 bytes] the len field is a byte count of the remaining fields and
includes the dst_id and data fields.
The remainder of the pdu includes two fields:
dst_idx [1 byte] destination index is used for intra-system routing of
packets. (currently not implemented) data [n bytes] this is the service portion of the Modbus pdu, mb_pdu, and is
defined below
The service portion of the Modbus Application Protocol, called mb_pdu, contains 2 fields: mb_pdu ::= { func_code[1], data[n] }
func_code [1 byte] MB function code data [n bytes] this field is function code dependent and usually contains
information such as variable references, variable counts, and data offsets.
The size and content of the data field are dependent on the value of the function code.
364
33002479 10/2019
Ethernet TCP/IP Modbus Application Protocol
TCP/IP Specific Issues
Overview
The following information describes some TCP/IP specific issues.
Broadcast/Multicast
Although broadcast and/or multicast are supported by both IP network address and IEEE 802.3
MAC address, the Modbus Application Protocol does not support either broadcast or multicast at the application layer.
Schneider Electric’s Quantum PLCs use broadcast addressing because they use ARP as the means of locating the destination node. The client interface to the Modbus Application Protocol service on the PLC, the MBP_MSTR block, requires the user to provide the destination IP address.
Also the embedded stack does use a pre-configured default gateway IP address in the case where
ARP does not succeed.
TCP Port Number
Schneider Electric has obtained a well-known system port from an Internet Authority. Schneider
Electric’s well-known system port number is 502. The Internet Authority assigned the system port number 502 to asa-appl-proto with Dennis Dubé as the company point of contact.
This port number allows Schneider Electric to transport various application protocols over with TCP or UDP. The particular protocol is indicated by the value of the proto_id parameter in the mbap_pdu. Currently the only assignment is 0 meaning Modbus Application Protocol.
33002479 10/2019
365
Ethernet TCP/IP Modbus Application Protocol
Closing a TCP Connection
Overview
A TCP connection can be closed by one of the following:
a remote station (which closes a connection by sending a TCP/IP connection closure message)
the local PLC
When the Maximum Number of Connections are Open
If the PLC receives a request to open a new connection when the maximum number of connections has been reached, the PLC:
closes an open but inactive connection
- then opens a new connection
To identify which connection to close, the PLC examines groups of connections for inactive open connections, in the following sequence:
1 non-referenced connections to devices that are not configured as part of the Control Expert application
2 client connections
3 server connections
If the PLC discovers one or more inactive connections in the first group, it closes the oldest inactive connection in that group then opens a new connection.
If no inactive connection is discovered in the first group, the PLC examines the second group of connections and, if it discovers one or more inactive connections in the second group, the PLC closes the oldest inactive connection in that group and opens a new connection.
If no inactive connection is discovered in the first and second groups, the PLC examines the third group and, if it discovers one or more inactive connections in the third group, the PLC closes the oldest inactive connection in that group and opens a new connection.
If the PLC fails to discover an inactive connection in any of the three groups, no open connection is closed and no new connection can be opened.
NOTE: Closure of a connection is indicated to the application by means of a status report
(message refused) on any exchanges in progress.
366
33002479 10/2019
Ethernet TCP/IP Modbus Application Protocol
Reference Documents
Overview
The following information provides a list of reference documents that you may find helpful.
Introduction
Following is a list of related documentation.
ANSI/IEEE Std 802.3-1985, ISO DIS 8802/3, ISBN - 0-471-82749-5, May 1988
ANSI/IEEE Std 802.2-1985, ISO DIS 8802/2, ISBN 0-471-82748-7, Feb 1988
RFC793, TCP (Transmission Control Protocol) DARPA Internet Program Protocol
Specification, Sep 1981
RFC 791, IP (Internet Protocol) DARPA Internet Protocol Specification, Sep 1981
RFC826, An Ethernet Address Resolution Protocol (ARP), David Plummer, NIC Sep 1982
RFC1042, A Standard for the Transmission of IP Datagrams over IEEE 802.2 Networks, Postel
& Reynolds, ISI, Feb 1988
RFC 792, ICMP (Internet Control Message Protocol) DARPA Internet C Control Message
Protocol Specification, Jon Postel, Sep 1981
RFC951, BOOTSTRAP PROTOCOL (BOOTP), Bill Croft and John Gilmore, September 1985
RFC783, The Trivial File Transfer Protocol (TFTP) rev 2, K.R. Solons MIT, June 1981
33002479 10/2019
367
Ethernet TCP/IP Modbus Application Protocol
368
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Installation and Configuration
33002479 10/2019
Installation and Configuration of a Modicon Quantum Platform
Appendix D
Installation and Configuration of a Modicon Quantum Platform
Overview
This quick start guide describes how to install and configure a Modicon Quantum Ethernet module.
It also sets up the I/O scanning service to allow data transfer to occur between the PLC and a remote slave device. Instructions for connecting to the module’s embedded web server pages are also provided at the end of the guide.
What Is in This Chapter?
This chapter contains the following topics:
Topic
Overview
Installation
Configuring the Rack with Control Expert
Configuring the Ethernet Network with Control Expert
Configuring the I/O Scanning Service
Building and Downloading the Configuration Program
Diagnosing the Ethernet Module Using the Web Server
Page
33002479 10/2019
369
Installation and Configuration
Overview
Introduction
This quick start guide explains how to install and configure Modicon Quantum Ethernet modules and set up a I/O scanning communication service. The following types of modules are applicable to this guide:
140 NOE 771 01
140 NOE 771 11
140 CPU 651 50
140 CPU 651 60
Hardware/Software Requirements
For the example discussed in this guide, the following Modicon Quantum Ethernet modules are required:
140 CPS 114 x0 power supply
140 CPU 651 50 CPU
140 NOE 77101 communication module
Also, a PC running Windows 2000 or XP with Schneider’s Control Expert configuration software installed on it is required.
Finally, either a USB or a Modbus cable is required to connect the PC to the network PLC.
Intended Audience
This user guide is intended for anyone who is involved in installing and configuring Modicon
Quantum Ethernet modules in a network arrangement that can perform a variety of communication services.
Anyone reading this guide should:
be familiar with Ethernet networks and the TCP/IP protocol
understand the operation of PLCs
370
33002479 10/2019
Installation and Configuration
Installation
Introduction
The Modicon Quantum Ethernet modules used for the example in this guide may vary from the ones available at your site. You can substitute the appropriate power supply, CPU, and Ethernet communication module(s) and other Quantum modules to make up a rack similar to the one described below.
Assembling the Rack
Assemble the modules into the rack as follows:
2
3
Step
1
Action
Insert the power supply into the leftmost slot (1) on the rack.
Add the CPU to the next two slots (2 & 3)on the right of the power supply.
Place the remaining Quantum communication modules, beginning with slot 4, to complete your installation.
In our example (see below), we use a CPS 114 x0 power supply, a CPU 651 50 processor, and a single NOE 771 01 Ethernet module to make up our rack.
33002479 10/2019
371
Installation and Configuration
Configuring the Rack with Control Expert
Introduction
We begin this procedure by configuring the Modicon Quantum Ethernet module rack using
Control Expert configuration program.
Configuring the Rack
Using a PC loaded with Control Expert software, proceed as follows:
4
5
Step
1
Action
Start Control Expert software.
Select New in the File menu to create a New Project dialog box.
In the New Project dialog box, expand the Quantum family to select the installed processor (the
140 CPU 65150 in our example).
372
33002479 10/2019
Step
6
Installation and Configuration
Action
In the project browser, double-click Station → Configuration → PLC bus to access the configuration of the local rack (shown below).
33002479 10/2019
373
Installation and Configuration
Step
7
Action
Double-click slot 4 to bring up the New Device menu to show the hardware catalog.
8
9
Double-click the module that goes in slot 4 (140 NOE 771 01 in our example, shown above).
Note: Alternately, you can click the module and drag it to the selected slot on the rack.
Repeat step 8 for each module included in your configuration.
The figure below shows the completed rack assembly for our example with the 140 NOE
771 01 module in slot 4.
374
33002479 10/2019
Installation and Configuration
Configuring the Ethernet Network with Control Expert
Introduction
The following procedure describes how to add a new Ethernet network and link it to the Modicon
Quantum module we configured in the previous section.
Setting Up the Network
Perform the following steps to add the Ethernet network:
Step
1
2
3
4
5
Action
Locate the Communications directory in the Project browser.
Right-click the Network subdirectory located under the Communications directory.
Select the New Network option to bring up the Add Network dialog box.
Scroll to Ethernet in the List of available Networks box.
Enter a meaningful name for your network in the Change Name field
(NOE77101 was used in our example).
6 Click OK.
33002479 10/2019
375
Installation and Configuration
Linking the Network to the NOE 77101 Module
Perform the following steps to link the new logical Ethernet network with the NOE 77101 module.
Step
1
2
Action
Double-click Local Bus in the Project browser to show the rack configuration.
Expand the Local Quantum Drop to show the ETHERNET port under the 140
NOE 77101.
3
4
Double-click the ETHRNET port to bring up the network link screen.
Under Please choose a network, scroll to locate the name of your logical network (NOE77101 in our example).
376
5 Click the validate check box in the upper toolbar to confirm the network link configuration.
33002479 10/2019
Installation and Configuration
Assigning an IP Address to the 140 NOE 771 01 Module
Perform the following steps to assign an IP address to the 140 NOE 771 01 communication module.
Step
1
2
Action
Locate the Communications\Networks directory in the Project browser.
Double-click your new logical network (NOE77101 in our example) to open the
NOE077101 configuration screen.
33002479 10/2019
4
5
3 Click Configured in the IP Address Configuration group (circled area shown above).
Note: Be sure to contact your network administrator and request the IP,
Subnetwork mask, and Gateway addresses prior to performing the next step.
Enter the appropriate values in the IP address, Subnetwork mask, and
Gateway address text fields.
Click the validate check box in the upper tool bar to confirm the IP configuration settings.
377
Installation and Configuration
Configuring the I/O Scanning Service
Introduction
The Modicon 140 NOE 771 01 module supports Ethernet communication services such as I/O scanning, Global Data, Modbus messaging, SNMP, etc. This example shows you how to configure the I/O scanning service. This service is used to:
transfer data between network devices
allow a CPU to regularly read data from and write data to scanned devices
Selecting the I/O Scanning Parameters
Perform the following steps to setup the I/O scanning parameters:
2
3
Step
1
4
Action
Open the Control Expert program on your PC.
In the Project Browser, locate the Communication → Networks sub-directory.
Click the network name (140 NOE 771 01 in our example) to open the module configuration table.
In the Module Utilities dialog, select Yes in the I/O Scanning field:
5 Click the I/O Scanning tab to display the I/O scanning configuration screen:
6 Type in the parameter settings under each of the column headings for the I/O Scanner Configuration.
Refer to the parameter definitions below.
378
33002479 10/2019
Step
7
Installation and Configuration
Action
Click the validate check box in the upper tool bar to confirm the I/O scanning parameter settings.
Health Block
The Health Block (number 1 in previous figure) lets you define the first word or bit in a health table.
That table can be up to 8 words (%IW) or 128 bits (%I) in length. Each bit in the table represents the status of an individual device. The table below shows how the bits are displayed based on the data type you use.
Bit
1
2
...
16
17
Data Type
%I
%I1
%I 2
%I16
%I17
%IW
%IW1.0
%IW1.1
%IW1.15
%IW2.0
By default, the table comprises words starting at %IW1.0. If you want to set the table to bits, you need to specify a %I value in an increment of 16 (%I1, %I16, %I32, etc.).
NOTE: The Health Block is available only for the NOE 771 00, -01, and -11. It is not available for the CPU 651 x0.
NOTE: For Safety Monitor applications, the Health Block is mapped on %M/%MW from the UMA zone instead of %I/%IW.
33002479 10/2019
379
Installation and Configuration
Device Control Block
The Device Control Block (number 2 in previous figure) lets you disable any scanned device by setting a bit associated with that device to 1. The I/O scanner closes the connection and sets the
Health Bit to 0 (unhealthy state).
To enable the Device Control Block select the check box in the I/O Scanner configuration dialog
(number 2 in previous figure).
NOTE:
To enable the Device Control Block, use:
Unity Pro at V2.0 or later a 140 NOE 771 01 or 140 NOE 771 11at version 3.5 or later a 140 CPU 651 x0 at version 2.0 or later
If you attempt to enable the Device Control Block with an earlier version of the firmware, the I/O scanning service is disabled.
If the check box is not selected, the I/O scanner service is enabled, and you cannot disable the I/O scanning of individual devices.
Disabling I/O scanning with the Device Control Block is equivalent to ending communication between the scanner and the device. Therefore:
The fallback positions are applied to the inputs by the scanner.
Communication with the device stops.
All entries in the IN and OUT tables transfer between the CPU and the scanner on each scan.
As a consequence of the last point above, if you modify a %MWi attached to an input, this %MWi is overwritten by the values coming from the I/O scanner in the next scan (with either 0 or the last input value).
It is possible (but meaningless) to access %MW attached to the outputs because they are not transmitted to the device.
Repetitive Rate Step
The Repetitive Rate Step (number 3 in previous figure) is set in multiples of 5 ms (the minimum) through 200 ms (the maximum).
The Repetitive Rate column is where you enter a rate of time for how often you want the I/O scanner to send a query to the device after the rate has timed out.
NOTE: The repetitive rate of the I/O scanner table is a multiple of the rate displayed in the
Repetitive Rate Step. The real repetitive rate being executed by the I/O scanner service is shown in the Repetitive Rate column.
Note: An entry in the Repetitive Rate column is rounded up to the next multiple that was entered in the Repetitive Rate Step if the entry is not a multiple of the Repetitive Rate Step.
For example, if the entry in the Repetitive Rate Step is 5 and you enter a 7 in the Repetitive Rate column, the 7 is rounded up to 10; if you change the Repetitive Rate Step to 6 and enter a 7 in the
Repetitive Rate column, the 7 is rounded up to 12.
380
33002479 10/2019
Installation and Configuration
I/O Scanner Table Parameters
The I/O Scanner parameters are described in the table below:
Parameter
Entry #
IP address
Device Name
Unit ID
Slave Syntax
Description
This is the first column; it has no name.
Valid range: 1 ... 128
Each entry represents an I/O Scanning exchange on the network.
This is the IP address of the scanned Ethernet slave device.
To configure a device (Advantys island or DTM), click the ...
button to open the Property box
device configuration software.
to start the
For an introduction to this procedure for Advantys, go here
.
For an introduction to this procedure for DTMs, go FDT
Container (see EcoStruxure™ Control Expert, Operating
Modes) .
NOTE: While the Property box is open, Property cannot be edited.
This field associates the slave address of the device connected to an Ethernet/Modbus gateway with the IP address of that gateway:
Value range: 1 to 255
Default value: 255
NOTE:
When using a bridge, enter the bridge index (1 to 255) in this field.
If you are copying the I/O scanning configuration from a
140 NOE 771 •• to a 140 NOC 771 ••, set the Unit ID to a value from 1 to 254.
Use this drop-down menu to pick the way RD Ref Slave and WR
Ref Slave values are displayed. There are 4 types of display available:
Index: 100
Modbus: 400101
(Modbus register)
IEC 0: %MW100
M340 and Premium PLC slaves
IEC 1: %MW101
Quantum PLC slaves
Example
192.168.1.100
MySTB1 or
Master_PRM_DTM_10
255
Index (default value)
33002479 10/2019
381
Installation and Configuration
Parameter
Health Timeout
(ms)
Description
This field sets the maximum interval between the responses from a remote device. After this time period expires, the received data is invalid. The Health Timeout must be longer than the Repetitive Rate time (ms). For a Quantum
140 NOE771 01 Ethernet module, it also should be longer than the CPU scan time.
For the Health Timeout:
Range: 1 ms to 50 s
Interval: 1 ms
Repetitive Rate
(ms)
RD Master
Object*
The rate at which data is scanned, in multiples of 16 ms.
Destination address in the master PLC where, from each device, newly read information is stored
RD Slave Ref.** Source address index in the slave/remote device
Example
1500 ms
64 ms
%MW10
The format of this value depends on the Slave
Syntax:
Index: 5
Modbus: 400006
IEC 0: %MW5
IEC 1: %MW6
RD length Number of words to read 10
Using these examples, Master Object 140 NOE 771 01 reads data from address 192.168.1.100 starting at index 5. It puts the data into the NOE address starting at %MW10 using a read size of 10 words.
Last value
(Input)
This field configures the behavior of inputs in the event of an access error in relation to the remote device (for example: inoperative network or device power supply, etc.):
Set to 0: fall back to 0
Hold last: maintain last value
Hold last
NOTE: When you select hold last in a
140 CPU 651 •0 coprocessor, the input data may fall back to 0 when the I/O scanner health bits are NOT
OKAY. Confirm that the
I/O scanner health bits are valid (OK=1) before removing the Ethernet cable to maintain hold last value.
WR Master
Object*
Source address of the master PLC whose data is being written into the slave/remote device.
Write operations are always performed at the word level.
%MW20
382
33002479 10/2019
Installation and Configuration
Parameter Description
WR Slave Ref.** The address of the first word written into the slave/remote device.
Example
The format of this value depends on the Slave
Syntax:
Index: 100
Modbus: 400101
IEC 0: %MW100
IEC 1: %MW101
WR length Number of words to be written
To allow slower TCP/IP network devices (i.e., gateways and bridges) to be compatible with the I/O Scanner:
Select the check box to enable this feature. Defines a new bit, and sets it to high (1).
De-select the check box to disable this feature (default).
Defines a new bit, and sets it to zero (0).
1
Using these examples, Master Object 140 NOE 771 01 writes data from address %MW20 to slave address
192.168.1.100 starting at index 100. It puts the data into the NOE address starting at %MW5 using a write size of 1 word.
Gateway/Bridge
Device
Description Additional information
*Master refers to the client PLC that makes the request.
**Slave refers to the server from which data is read or to which data is written.
NOTE: For more information, refer to the Contextual Menu for Copy/Cut/Paste topic
see page 210
.
NOTE: For more information, refer to the I/O Scanning with Multiple Lines topic (
see page 212
33002479 10/2019
383
Installation and Configuration
Building and Downloading the Configuration Program
Building the Program
Next, you need to build the whole program before downloading it to the PLC. To do this, select
Build\Rebuild All Project in the toolbar at the bottom of the screen (shown below). If it is successful, a Process succeeded message will appear at the program’s completion.
Connection Options
In order to run the configuration program it must first be downloaded to the PLC. Prior to downloading the program, the PLC must be connected to the PC containing the Control Expert software. The connection can be accomplished using a communication network such as Ethernet,
USB, Modbus, or Modbus Plus cabling. We describe both the USB and Modbus cable setups in the following examples.
384
33002479 10/2019
Installation and Configuration
Connecting the PC to the PLC with a USB Cable
Proceed as follows to connect the PC to the PLC with USB.
Step
1
2
3
Action
Ensure that the Quantum system is powered up.
Connect the PLC to the PC with a USB cable.
On the PC, click the Control Expert PLC\Set Address tab to bring up the Set Address dialog box.
4
5
6
7
Select USB in the PLC Media box.
Leave the PLC Address field blank.
Click OK.
Proceed to Downloading and Running the Configuration Program ( see page 387 )
.
33002479 10/2019
385
Installation and Configuration
Connecting the PC to the PLC with a Modbus Cable
Proceed as follows to connect the PC to the PLC with Modbus.
Step
1
2
3
Action
Ensure that the Quantum system is powered up.
Connect the PLC to the PC with a Modbus cable.
On the PC, click the Control Expert PLC\Set Address tab to bring up the Set Address menu.
6
7
4
5
Select MODBUS01 in the PLC Media field.
Enter the Modbus address in the PLC Address field (the default address is 1).
Note: You can also use the keypad on the 140 CPU 651 50 module to enter or change the
Modbus address.
Click OK.
Proceed to Downloading and Running the Configuration Program (below).
386
33002479 10/2019
Installation and Configuration
Downloading and Running the Configuration Program
Once the PC and the PLC are physically connected (above steps), the I/O scanning program can be downloaded to the PLC.
Step
1
2
Action
On the PC, select PLC \Connect on the Control Expert screen.
Click the PLC\Transfer Project to PLC tab to bring up the Transfer Project to PLC dialog box.
3
4
Click the Transfer button to download the program to the PLC.
When the confirm screen appears, click OK.
5 Click Run on the Control Expert upper toolbar to start the program.
33002479 10/2019
387
Installation and Configuration
Diagnosing the Ethernet Module Using the Web Server
Introduction
Quantum Ethernet modules have an embedded web server that provides web pages to diagnose the Ethernet module services, such as statistics, I/O scanning, Messages, global data, etc. You can access an Ethernet module's web pages by entering the IP address of the module in the web browser. No password is required to display the home page. From the NOE home page, you can access the Monitoring, Diagnostics, and Setup pages.
You can also use the module’s LED display to diagnose problems. For information regarding the module’s LED display refer to the Quantum NOE 771xx Ethernet Modules User Manual .
Accessing the Ethernet Module’s Web Page
To access the NOE 771 01 module’s web page, proceed as follows:
Step
1
2
Action
At the PC, start a Web browser such as Internet Explorer.
Enter the NOE 771 01’s currently assigned IP address in the Address field of the browser to bring up the NOE’s home page.
388
3
4
Click the Diagnostics tab.
Enter a user name and password (the default is USER for both).
Note: Check with your system administrator to see if the user name and password have been changed.
33002479 10/2019
Step
5
Action
Click OK to bring up the NOE diagnostic web page.
Installation and Configuration
6 Click the I/O Scanning link on the left-hand side of the screen to access the I/O scanning diagnostics web page.
33002479 10/2019
389
Installation and Configuration
390
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Glossary
33002479 10/2019
Glossary
A
ACK
Acknowledgement address
On a network, the identification of a station. In a frame, a grouping of bits that identifies the frame’s source or destination.
API
Application Program Interface. The specification of functions and data used by one program module to access another; the programming interface that corresponds to the boundary between protocol layers.
ARP
Address Resolution Protocol. A network layer protocol used to determine the physical address that corresponds to the IP address for a host on the network. ARP is a sub-protocol that operates under
TCP/IP.
ASN.1
Abstract Syntax Notation. Grammar used to define a protocol (OSI scope)
B
BOOTP
BOOTstrap Protocol. A protocol used at power-up in order to get an IP address that is provided by a BOOTP server and is based on the module’s MAC address.
bps
Bits per second.
bridge
A device that connects two or more physical networks that use the same protocol. Bridges read frames and decide whether to transmit or block them based on their destination address.
BSP
Board Support Package. A software package that maps a specific real-time operating system
(RTOS0 onto a specific hardware.
C
client
A computer process requesting service from other computer processes.
33002479 10/2019
391
Glossary
Cyclic Data Exchange
Provides data transfer between two or more NOE 771 xx controllers on a TCP/IP network.
D
default gateway
The IP address of the network or host to which all packets addressed to an unknown network or host are sent. The default gateway is typically a router or other device.
DHCP
Dynamic Host Configuration Protocol. An improved version of BOOTP.
DHCP Client
Host on the network obtaining its configuration from a DHCP Server.
DHCP Server
Server providing configuration parameters to a DHCP Client.
DNS
Domain Name System. A protocol within TCP/IP used to find IP addresses based on host names
F
FactoryCast
An embedded Web server that the user customizes, permitting user access to controller diagnostics and Ethernet configuration.
field
A logical grouping of contiguous bits that convey one kind of information, such as the start or end of a message, an address, data, or an error check.
firewall
A gateway that controls access to a network or an application.
frame
A group of bits that form a discrete block of information. Frames contain network control information or data. The size and composition of a frame is determined by the network technology being used.
framing types
Two common framing types are Ethernet II and IEEE 802.3.
FTP
File Transfer Protocol. The protocol (over TCP) used to read or write a file into a remote station
(the FTP server side).
392
33002479 10/2019
Glossary
G
gateway
A device that connects networks with dissimilar network architectures and that operates at the
Application Layer. This term may refer to a router.
Global Data (Publish / Subscribe)
Service of inter PLC synchronization (shared databases).
H
half duplex
(HDX) A method of data transmission capable of communication in two directions, but only one direction at a time.
host
A node on a network.
hostname
A domain name given to a specific computer on a network and used to address that computer.
HTTP
A domain name given to a specific computer on a network and used to address that computer.
hub
A device that connects a series of flexible and centralized modules to create a network.
I
I/O Drop
One or two (depending on the system type) Remote I/O Channels consisting of a fixed number of
I/O points.
I/O Map
An area in the controller configuration memory used to map input and output points. Previously called traffic cop.
I/O Scan
A procedure the processor follows to monitor inputs and control outputs.
I/O Scan List
A configuration table that identifies the targets with which repetitive communication is authorized.
I/O scanner
Software component that is in charge of scanning Ethernet based Momentum IO in order to get inputs and set outputs.
33002479 10/2019
393
Glossary
ICMP
Internet Control Message Protocol. A protocol within TCP/IP used to report errors in datagram transmission.
Internet
The global interconnection of TCP/IP based computer communication networks.
IP
Internet Protocol. A common network layer protocol. IP is most often used with TCP.
IP Address
Internet Protocol Address. A 32-bit address assigned to hosts using TCP/IP.
L
layer
In the OSI model, a portion of the structure of a device that provides defined services for the transfer of information.
Legacy
In the sense of network communication: Existing Components (PLC products etc.) that do not provide special (hardware) support for Control Intranet.
M
MAC Address
Media Access Control address. The hardware address of a device. A MAC address is assigned to an Ethernet TCP/IP module in the factory.
MBAP
Modbus Application Protocol
MBP_MSTR
A special master instruction that uses ladder logic to read and write controller information.
MIB
Management Information Base. Database that holds the configuration of a SNMP enabled device.
Modbus
A communication system that links Modicon controllers with intelligent terminals and computers over common carrier or dedicated lines
N
NACK
Negative acknowledgment indicating an error.
394
33002479 10/2019
Glossary
NDDS
Network Data Delivery Services.
NetLink
The logical name of a network.
network
Interconnected devices sharing a common data path and protocol for communication.
node
An addressable device on a communications network.
NTP
Network Time Protocol. A protocol used to synchronize the time of a client or server to the time of another server or referenced source like a satellite receiver.
O
OIT / OID
Object Information True / Object ID (identify OIT) Contain databases managing SNMP (MIBs)
OSI model
Open System Interconnection model. A reference standard describing the required performance of devices for data communication. Produced by the International Standards Organization.
P
packet
The unit of data sent across a network.
Peer Cop
Software that allows you to configure data blocks to be transferred between controllers on a
Modbus Plus network.
PING
Packet Internet Groper. A program used to test whether a destination on a network can be reached.
PLC
Programmable Logic Controller port
An access point for data entry or exit within a host using TCP services.
protocol
Describes message formats and a set of rules used by two or more devices to communicate using those formats.
33002479 10/2019
395
Glossary
R
repeater
A device that connects two sections of a network and conveys signals between them without making routing decisions or filtering packets.
RFC
Request For Comment. Paper identified by a number in Internet world. They define the state of art regarding Internet protocols (ruled by IETF = Internet Engineering Task Force) http://www.ietf.org
router
A device that connects two or more sections of a network and allows information to flow between them. A router examines every packet it receives and decides whether to block the packet from the rest of the network or transmit it. The router will attempt to send the packet through the network by the most efficient path.
S
server
Provides services to clients. This term may also refer to the computer on which the service is based.
SMTP
Simple Mail Transfer Protocol. A common protocol used to transfer e-mail messages.
SNMP
Simple Network Management Protocol socket
The association of a port with an IP address, serving as an identification of sender or recipient.
stack
The software code that implements the protocol being used. In the case of the NOE modules it is
TCP/IP.
STP
Shielded Twisted Pair. A type of cabling consisting of several strands of wire surrounded by foil shielding, twisted together.
subnet
A physical or logical network within an IP network that shares a network address with other portions of the network.
subnet mask
A bit mask used to identify or determine which bits in an IP address correspond to the network address and which bits correspond to the subnet portions of the address. The subnet mask is the network address plus the bits reserved for identifying the subnetwork.
396
33002479 10/2019
Glossary switch
A network device that connects two or more separate network segments and allows traffic to be passed between them. A switch determines whether a frame should be blocked or transmitted based on its destination address.
T
TCP
Transmission Control Protocol.
TCP/IP
A protocol suite consisting of the Transmission Control Protocol and the Internet Protocol; the suite of communications protocols on which the Internet is based.
Transparent Factory
Transparent Factory is a Schneider Electric initiative to bring Internet technologies to the factory floor to "information enable" Schneider Products to provide easy "transparent" access to plant operational data over open networks with open tools. Interfacing with products from other manufacturers for similar access, customers can expect improved methods for monitoring and controlling factory processes at reduced costs.
Transparent Ready
A Schneider Electric product line based on universal Ethernet TCP/IP and Web technologies.
These industrial automation products (Trademark Telemecanique) and electrical distribution products (TrademarkMerlin Gerin) can be integrated into real-time data sharing systems with no need for interfaces. The product line includes Sensor and preactuator type field products (simple or intelligent), controllers and PLCs, HMI applications, and dedicated gateways and servers.
U
UDP
User Datagram Protocol. A protocol that transmits data over IP.
Uni-Te
Télémecanique unified application protocol (used in S7, Premium, and Micro PLC ranges).
URL
Uniform Resource Locator. The network address of a file.
UTP
Unshielded Twisted Pair. A type of cabling consisting of insulated cable strands that are twisted together in pairs.
33002479 10/2019
397
Glossary
W
Web
Worldwide interconnection of stations based on Internet protocols. The most famous one is HTTP
(Web server).
WWW
World Wide Web. A hypertext-based, distributed information system in which clients and servers are freely available.
398
33002479 10/2019
Quantum using EcoStruxure™ Control Expert
Index
33002479 10/2019
Index
0-9
10/100BASE-T cable distances,
100BASE-FX cable distances,
10BASE-T
hubs,
140 NOE 771 01 configure I/O scanning,
140CPU65150,
140CPU65160,
140CPU651x0
scan difference from 140NOE77101,
140NOE771•• to 140NOC771•• transfer
140NOE77100,
140NOE77101,
scan difference from 140CPU651x0,
140NOE77110,
140NOE77111,
A
address server,
Advantys,
B
bandwidth monitoring,
C
change modbus plus address operation 17,
33002479 10/2019 configuring Ethernet devices,
140NOE77100,
140NOE77101,
140NOE77110,
140NOE77111,
Control Expert
CREAD_REG,
customer support,
CWRITE_REG,
D
data transfer communication blocks
diagnosing Hot Standby,
Diagnostics web page
DTM container,
duplicate IP tests,
E
electronic mail notification, embedded web pages,
,
F
FTP,
FTP servers,
FTP/TFTP services enable/disable,
G
,
,
399
Index
H
Hot Standby
diagnosing,
,
hot standby network effects,
HTTP services enable/disable,
I
,
140CPU651x0 and 140NOE77101 scan differences,
140NOE771•• to 140NOC771•• transfer,
configure140 NOE 771 01, multiple lines, installing Ethernet devices
140NOE77100,
140NOE77101,
140NOE77110,
140NOE77111,
K
key switches, keypads,
L
M
maintaining Ethernet modules,
MBAP,
MBP_MSTR,
change modbus plus address, menus
400
MIB,
Modbus messaging,
N
,
O
P
PRA
Properties web page
Q
Quantum
140CPU651x0 and 140NOE77101 scan differences,
Diagnostics web page,
Properties web page,
R
remote clients,
S
scanning
140CPU651x0 and 140NOE77101 differ ences,
33002479 10/2019
Index services
140NOE77100,
140NOE77101,
140NOE77110,
140NOE77111,
address server, bandwidth monitoring,
global data,
Modbus messaging,
SNMP,
,
,
,
,
SMTP electronic mail notification,
SMTP electronic mail notification,
specifications
,
T
TCP_IP_ADDR,
transferring data
,
W
web pages
WRITE_REG,
,
33002479 10/2019
401
Index
402
33002479 10/2019