Modicon Quantum
Hot Standby with Unity
User Manual
UNY USE 107 10 V20E
September 2004
2
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Part I Introducing the Modicon Quantum Hot Standby with
Unity System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 1 Modicon Quantum Hot Standby with Unity Overview. . . . . . . 15
Overview of the Modicon Quantum Hot Standby with Unity System. . . . . . . . . . 16
Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Module
Modicon Quantum Hot Standby with Unity System Overview. . . . . . . . . . . . . . . 19
Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Components. . . . . 21
Operating the Modicon Quantum Hot Standby with Unity 140 CPU 671 60
Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LED
Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LCD
Chapter 2 Modicon Quantum Hot Standby with Unity Compatibility,
Differences, and Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Understanding System Words and System Bits . . . . . . . . . . . . . . . . . . . . . . . . . 41
Understanding Other Module Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3
4
Chapter 3 Using IEC Logic and Modicon Quantum Hot Standby with
Unity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Modicon Quantum Hot Standby with Unity and IEC Logic. . . . . . . . . . . . . . . . . . 48
Understanding the Modicon Quantum Hot Standby with
Understanding System Scan Time in Modicon Quantum Hot Standby with
Transferring Application Data in a Modicon Quantum Hot Standby with
Part II Setting up and Maintaining a Modicon Quantum Hot
Standby with Unity System. . . . . . . . . . . . . . . . . . . . . . . . 55
Chapter 4 Setting up, Installing, and Cabling a Modicon Quantum
Hot Standby with Unity System . . . . . . . . . . . . . . . . . . . . . . . . 57
Setting Up the Modicon Quantum Hot Standby with Unity System . . . . . . . . . . . 58
Connecting Two Modicon Quantum Hot Standby with Unity
Testing the Modicon Quantum Hot Standby with Unity System . . . . . . . . . . . . . 66
Chapter 5 Configuring a Modicon Quantum Hot Standby with
Unity System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.1
Configuring a System with the Unity Pro Tabs and Dialogs . . . . . . . . . . . . . . . . 70
Using the Animation Tab and PLC Screen Dialogs . . . . . . . . . . . . . . . . . . . . . . . 81
Configuring the Modbus Plus Communication Type . . . . . . . . . . . . . . . . . . . . . . 87
Swapping Network Addresses at Switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
5.2
Overview of Modicon Quantum Hot Standby with Unity Solution for
NOE Operating Modes and Modicon Quantum Hot Standby with Unity . . . . . . . 98
Network Effects of Modicon Quantum Hot Standby with Unity Solution . . . . . . 105
5.3
Understanding the Non-Transfer Area, Transferring State RAM,
Understanding the Unity Command Register . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Chapter 6 Maintaining a Modicon Quantum Hot Standby with
Unity System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Verifying the Health of a Modicon Quantum Hot Standby with
Detecting and Diagnosing Failures in a Modicon Quantum Hot Standby with
Detecting Primary Controller, Copro, and RIO Head Failures. . . . . . . . . . . . . . 123
Detecting Standby Controller, Copro, and RIO Head Failures . . . . . . . . . . . . . 125
Detecting High-Speed Data Link (HDSL) Failures . . . . . . . . . . . . . . . . . . . . . . 126
Checking for Identical Application Programs—Checksum . . . . . . . . . . . . . . . . 131
Part III Understanding the Modicon Quantum Hot Standby with
Unity System Special Features . . . . . . . . . . . . . . . . . . . 135
Chapter 7 Enabling EXEC Upgrade with Unity Pro . . . . . . . . . . . . . . . . . 137
Overview of Modicon Quantum Hot Standby with Unity EXEC Upgrade . . . . . 138
Executing the EXEC Upgrade Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Chapter 8 Handling Logic Mismatch with Unity Pro . . . . . . . . . . . . . . . .141
Understanding Modicon Quantum Hot Standby with Unity Logic Mismatch . . . 142
5
6
Understanding Switchover Behavior during Logic Mismatch. . . . . . . . . . . . . . . 146
Online or Offline Modifications and Logic Mismatch . . . . . . . . . . . . . . . . . . . . . 148
Online Modifications to an Application Program in the Standby and
Online Modifications to an Application Program in the Primary and
Offline Modification of an Application Program and Logic Mismatch. . . . . . . . . 151
Switchover Methods and Logic Mismatch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Application Program Transfer Method and Logic Mismatch . . . . . . . . . . . . . . . 155
Recommendations for Using Logic Mismatch . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Chapter 9 Transferring an Application Program with Unity Pro . . . . . . 159
Overview of Application Program Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Executing the Application Program Transfer Procedure Using the
Executing the Application Program Transfer Procedure Using the Keypad . . . 164
Chapter 10 Using the Modicon Quantum Hot Standby with
Unity EFBs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Appendices for Quantum Hot Standby Planning and Installation Guide . . . . . . 181
Appendix A Modicon Quantum Hot Standby with Unity
Additional Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
140 CPU 671 60 Specifications for Modicon Quantum Hot Standby with
CRP Remote I/O Head Processor Error Patterns . . . . . . . . . . . . . . . . . . . . . . . 187
Safety Information
§
Important Information
NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
7
Safety Information
PLEASE NOTE Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.
© 2004 Schneider Electric. All Rights Reserved.
8
About the Book
At a Glance
Document Scope This guide describes the Modicon Quantum Hot Standby with Unity system consisting of the Unity Pro software, the Modicon Quantum Hot Standby with Unity
140 CPU 671 60, power supplies, and remote I/O (RIO).
This guide describes how to build a Modicon Quantum Hot Standby with Unity system. Users of legacy Quantum Hot Standby systems should note that significant differences exist between Unity and legacy systems, and where important, this guide identifies those differences.
Note: Software Requirements
Required to use a Quantum Modicon Hot Standby with Unity system: z z z
Unity Pro 2.0 or higher
CRA firmware: Release 1.25 or higher
CRP firmware: Release 1.14 or higher
Note: Who should use this document?
Anyone who uses a Hot Standby system or needs fault-tolerant availability through redundancy in an automation system.
You should have knowledge of programmable logic controllers (PLCs). Familiarity with automation controls is expected.
You should possess a working knowledge of the Unity Pro software. Familiarity with Concept, ProWORX, or Modsoft will help.
9
About the Book
Validity Note
Note: Terminology
This guide uses the following terminology.
z z application program = a project or logic program controller = a Unity Programmable Logic Controller (PLC), module, which contains both
1.
a CPU z z
2.
a Copro
CPU = (Central Processing Unit) a microprocessor in the controller, which processes the application program copro = a microprocessor in the controller, which communicates between two z z z controllers modify = to edit or to change an application program module = any unit either a controller, NOE, RIO, CRP, CRA, DDI, AVO scan = program cycle
Because Modicon Quantum Hot Standby with Unity systems deliver fault-tolerant availability through redundancy, use a Modicon Quantum Hot Standby with Unity system when downtime cannot be tolerated. Redundancy means that two backplanes are configured identically. A Modicon Quantum Hot Standby with Unity system must have identical configurations: z z identical 140 CPU 671 60s which contain both a CPU and a Copro identical versions of the EXEC z z identical power supplies identical RIO Heads z z identical cabling and cabling systems identical I/O drops z identical sequential placement on the backplane
The data and illustrations found in this book are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.
10
About the Book
Related
Documents
Title of Documentation
Quantum with Unity Pro Hardware Reference Manual
Quantum with Unity Pro Discrete and Analog I/O Reference
Manual
Quantum with Unity Pro Experts and Communication Reference
Manual
Quantum Automation Series Hardware Reference Manual
Modbus Plus Network I/O Servicing Guide, Version 2.0
Remote I/O Cable System Planning and Installation Guide,
Version 3.0
Modbus Plus Network Planning and Installation Guide,
Version 4.0
Reference Number
Electronic Documentation
CD: UNYUSE909CDM
Electronic Documentation
CD: UNYUSE909CDM
Electronic Documentation
CD: UNYUSE909CDM
840USE10000
840USE10400
890USE10100
890USE10000
Product Related
Warnings
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of
Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When controllers are used for applications with technical safety requirements, please follow the relevant instructions.
Failure to use Schneider Electric software or approved software with our hardware products may result in improper operating results.
Failure to observe this product related warning can result in injury or equipment damage.
User Comments We welcome your comments about this document. You can reach us by e-mail at [email protected]
11
About the Book
12
Introducing the Modicon Quantum
Hot Standby with Unity System
I
At a Glance
Purpose
What's in this
Part?
This part introduces the Modicon Quantum Hot Standby with Unity system. The content describes the hardware available, the compatibility of Modicon Quantum
Hot Standby with Unity system with legacy systems, and using IEC logic and Unity.
This part contains the following chapters:
Chapter
1
2
3
Chapter Name
Modicon Quantum Hot Standby with Unity Overview
Modicon Quantum Hot Standby with Unity Compatibility,
Differences, and Restrictions
Using IEC Logic and Modicon Quantum Hot Standby with Unity
Page
13
Introducing Modicon Quantum Hot Standby with Unity
14
Modicon Quantum Hot Standby with Unity Overview
1
Introduction
Overview
What's in this
Chapter?
In this chapter you will find a brief overview of the Modicon Quantum Hot Standby with Unity system, the module, and the indicators.
This chapter contains the following topics:
Topic
Overview of the Modicon Quantum Hot Standby with Unity System
Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Module Overview
Modicon Quantum Hot Standby with Unity System Overview
Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Components
Operating the Modicon Quantum Hot Standby with Unity 140 CPU 671 60
Keypad
Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LED
Indicators
Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LCD
Display Screens
Page
15
Overview Modicon Quantum Hot Standby with Unity
Overview of the Modicon Quantum Hot Standby with Unity System
Purpose of a Hot
Standby System
Use a Modicon Quantum Hot Standby with Unity system when downtime cannot be tolerated. Hot standby systems deliver high availability through redundancy. A hot standby system consists of two identical configurations.
z Modicon Quantum 140 CPU 671 60 z Modicon Quantum Power Supply Module
Modicon Quantum RIO Head z z Modicon Optional Modules (NOE, NOM)
One of the 140 CPU 67160’s acts as the Primary controller, and the other acts as the Standby controller. The Primary controller runs the application program and operates the remote I/O.
Identical
Configurations
Primary and
Standby
Controllers
Two backplanes are configured with identical hardware and software.
One of the programmable logic controllers (PLCs) functions as the Primary controller and the other as a Standby controller, and either controller can be put in the Primary state, but the other must be in the Standby state or offline.
The Primary controller executes the application program, controls the remote I/O, and updates the Standby controller after every scan (program cycle). If the Primary controller fails, the Standby controller takes control within one scan. To determine if the Primary controller failed, note controller’s status displayed in the HE CPU LCD screen and the RIO Head’s status displayed by the RIO Head’s LEDs. (See
Troubleshooting the Primary, p. 133 )
The Standby controller does not execute the full application program but only the first section, and the Standby controller does not control the remote I/O but checks out the availability of the Modicon Quantum Hot Standby with Unity equipment.
Switchover
Capability
Either of the two controllers may function as the Primary controller and the other as the Standby controller.
Primary and Standby states are switchable.
Therefore, if one of the two controllers is functioning as the Primary controller, the other must be in Standby mode. Otherwise, the second controller is in the default mode, which is offline.
The remote I/O is always controlled by the Primary controller.
16
Monitoring the
System
Power Cycle
Overview Modicon Quantum Hot Standby with Unity
The Primary and the Standby controllers communicate with each other constantly to monitor the functionality of the system.
z If the Primary controller fails, the state of the controllers is switched.
The Standby controller becomes the Primary, executes the application program, z and controls the remote I/O.
If the Standby controller fails, the Primary controller continues to run without redundancy and acts as a stand alone system.
On power cycle, the controller that has the lowest MAC address will become the
Primary. The second system automatically becomes the Standby.
Handling I/O
Note: The Modicon Quantum Hot Standby with Unity system supports I/O connected to a Remote I/O network and Ethernet I/O scanning.
Handling Local
I/O
Software
Requirements
Local I/O is not supported in a Modicon Quantum Hot Standby with Unity system environment. However, local I/O can be configured and run but will not have any corresponding backup.
Required to use a Quantum Modicon Hot Standby with Unity system: z z z
Unity Pro 2.0 or higher
CRA firmware: Release 1.25 or higher
CRP firmware: Release 1.14 or higher
Configuring
Modbus Plus
(MB+) Addresses
Note: Configure MB+ address first time
1.
Default MB+ address = 1 (new 140 CPU 671 60 from factory)
2.
Change MB+ address at first configuration (on both controllers)
Schneider Electric recommends: do not change MB+ address after first configuration because unintended operation may result.)
(See
Configuring a System with the Unity Pro Tabs and Dialogs, p. 70 )
17
Overview Modicon Quantum Hot Standby with Unity
Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Module Overview
Illustration
18
The following figure shows the Modicon Quantum Hot Standby (with Unity)
140 CPU 671 60 module and its components. Its HSBY fiber optic communications port differentiates this High End CPU module from the 140 CPU 651 60.
140
CPU 671 60
1
2
3
12
13
RESTAR
ESC MO ENT
Mem. Extract Rdy
6
7
4
5
COM
ST
8
9
10
11
Mac Address
1 Model number, module description, color code
2 Lens cover (open)
3 LCD Display (here covered by lens cover)
4 Key switch
5 Keypad (with 2 red LED indicators)
6 Modbus port (RS-232) (RS-485)
7 USB port
8 Modbus Plus port
9 PCMCIA slots A and B (Type II, Type III)
10 LED indicators (yellow) for Ethernet communication
11 HSBY fiber optic communications port
12 Restart button
13 Battery (user installed)
Note: Unity Quantum High End CPUs are equipped with two receptacles (A and
B) in which to install PCMCIA cards. PCMCIA is a standard type of memory card.
Overview Modicon Quantum Hot Standby with Unity
Modicon Quantum Hot Standby with Unity System Overview
System
Components
The following graphic shows the components required for a Modicon Quantum Hot
Standby with Unity system.
5
1
3 6 10 5
2
3 6 10
9A
4
A B
7
9
7A
8
A B
7C
8
7B
1 Primary PLC
2 Standby PLC
3 Modicon Quantum Hot Standby with Unity controller with integrated coprocessor
4 Fiber Optic Cable to connect to both controllers
5 Modicon Quantum power supply module: Install power supply in first slot for better rack layout.
6 Modicon Quantum RIO head
7 Coaxial cable with splitters (7A) (MA-0186-100), trunk terminators (7B) (52-0422-000), and tap (7C) (MA-0185-100) for connecting the RIO heads (6) with the RIO drops (8). The dashed connections represent a redundant connection in the RIO network, which is not required for the Modicon Quantum Hot Standby with Unity system.
8 Modicon Quantum RIO drop
9 Unity Pro computer connected to both controllers via Modbus or Modbus Plus (9A)
10 Optional modules (NOMs, NOEs) if required
19
Overview Modicon Quantum Hot Standby with Unity
Software
Requirements
Please note z z
CRA modules must have V1.25 or higher of the firmware
The Unity Hot Standby system is NOT compatible with previous versions of CRA modules.
CRP modules must have V1.14 or higher of the firmware
The Unity Hot Standby system is NOT compatible with previous versions of CRP modules.
20
Overview Modicon Quantum Hot Standby with Unity
Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Components
Lens Cover
LCD Display
Protects and provides access to z Key Switch z z
Battery
Reset Button
Open the lens cover by sliding upwards.
Has a 2 lines by 16 characters LCD display with a backlight (dims) and adjustable contrast.
The backlight turns on when z keypad driver detects a key press z z z key switch state is changed error message is displayed on the LCD
The backlight dims if no key switch or keypad activity z
Backlight dims in 5 seconds.
error message is generated
Backlight remains on until the error is corrected and the error message stops.
2 Lines by 16 characters LCD
21
Overview Modicon Quantum Hot Standby with Unity
Key Switch Use the key switch as a security feature and memory protection switch.
The key switch has two positions: locked and unlocked.
Key position unlocked
PLC operation z z all system menu operations are able to be invoked and all changeable module parameters are able to be modified by the operator via the LCD and keypad memory protection is OFF locked z z no system menu operations are able to be invoked and all module parameters are read only memory protection is ON
Switching the key switch position from locked to unlocked or vice versa will turn on the LCD's backlight.
Keypad The Modicon Quantum Hot Standby with Unity 140 CPU 671 60 keypad consists of five keys that are mapped to a hardware address.
5-key keypad with 2 LEDs
1
ESC MOD ENTER
Reset Button
2
1 5 keys
2 2 LEDs
Use the keys on the keypad to access the Modicon Quantum Hot Standby with Unity set of system menus, which enable you to z perform PLC operations for example: Start PLC, Stop PLC z display module parameters for example, communications parameters
Forces a cold start of the PLC.
22
Overview Modicon Quantum Hot Standby with Unity
Operating the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 Keypad
Using the Keys Functionality
Key
ESC
Function
To cancel an entry, or suspend or stop an action in progress
To display the preceding screens successively (step up the menu tree)
To confirm a selection or an entry
ENTER
To set a field on the display into modify mode
MOD
LED: on
LED: flashing
LED: off
LED on
LED flashing
LED off z z key active
To scroll through menu options
To scroll through modify mode field options key active z Field in modify mode has options to scroll through key inactive z No menu options, no field options z z key active
To move around in a screen, field to field
To go to the sub-menu key active z To move around in a field that is in modify mode, digit to digit z z z key inactive
No sub-menu for menu option
No moving around in a screen
No moving around in a field
23
Overview Modicon Quantum Hot Standby with Unity
Adjusting the
Contrast
The contrast is adjustable from the keypad when the Default screen is displayed as follows:
Step
1
2
Action
Press the MOD key:
MOD
To adjust the contrast darker press:
3 To adjust the contrast lighter press:
Using the
Backlight
4 To confirm the setting press:
ENTER
Pressing a key will turn on the LCD backlight (if it was off). When the user presses the ESC key and the LCD backlight was off, the LCD backlight will turn on and the
Default Screen will stay as the displayed screen.
If at any time the executive detects an error in the CPU it will display an error message to the LCD and the LCD's backlight will turn on until the error condition disappears
24
Overview Modicon Quantum Hot Standby with Unity
Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LED
Indicators
Overview The Modicon Quantum Hot Standby with Unity 140 CPU 671 60 offers two indicators:
1.
LCD display screen
(See Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LCD
The default display screen serves as a controller status screen. (See
Understanding the Default Screen, p. 29 )
2.
LED Indicators
(See
Interpreting the LED Indicators, p. 26
)
Position of indicators on Modicon Quantum Hot Standby with Unity 140 CPU 671 60
140
CPU 671 60
HOT STANDBY CONTROLLER
1
RESTART
ESC
Mem. Extract Rdy
MOD ENTER
COM
2
STS
COM
STS
Mac Address
00:00:##:##:##:##
1 LCD Display (lens cover closed)
2 LED Indicators
25
Overview Modicon Quantum Hot Standby with Unity
Interpreting the
LED Indicators
The LEDs provide information
CPU 671 60 (HSBY)
LEDs
COM
Color Description
Yellow Controlled by the
Coprocessor
1
hardware
Indicates
Communication activity between Primary and
Standby controllers
STS Yellow Controlled by the
Coprocessor
1
firmware
Status of Copro z Blinking z system is redundant and data are exchanged from the Primary to Standby z controller
Steady on z z z system is NOT redundant
Copro booting from power-on to end of self-tests
Steady off z
Copro auto tests failed
Note: No activity returns the LEDs to the default.
1 The Modicon Quantum Hot Standby with Unity HE CPU uses an embedded coprocessor
(Copro) to provide a dedicated communications link, which transfers data between the
Primary and Standby controllers.
26
Overview Modicon Quantum Hot Standby with Unity
Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LCD
Display Screens
Overview
1
The controller’s LCD displays messages. These messages indicate the controller’s status. There ae four levels of menus and submenus. All menus are accessed using the keypad on the front of the controller.
For detailed information about the menus and submenus see: z
Using the PLC Operations Menus and Submenus, p. 30
z
Using the Communications Menus and Submenus, p. 33
Using the System Info Menus and Submenus, p. 36
z z
Using the LCD Settings Menus and Submenus, p. 37
Structure: LCD display menus and submenus
Mode State Bat L port
2
Quantum
PLC Operations =>
3
Quantum
Communications =>
Quantum
System Info =>
Quantum
LCD Settings =>
4
1 Default Screen
2 System Menus
3 Sub Menus
4 Sub Screens
27
Overview Modicon Quantum Hot Standby with Unity
Accessing the
Screens
Use the keys on the keypad to access the system menus and submenus.
Step
1
Action
To access the screens, ensure that the key switch is in the unlocked position .
2 To step down to a lower menu, operate one of the following keys:
ENTER
3 To return to the previous menu, press:
ESC
28
Understanding the Default
Screen
Overview Modicon Quantum Hot Standby with Unity
Default screen displays the following information
Mode State Bat L port PCM
The default screen is read only.
Default
Screen
Displays
Default
Fields Available
State
Options
Available
RUN
BatL
Port USB
Modbus
Plus
Modbus
PCM
STOP
No Conf
MB+ mb+
232
485
1
2
Description
Application program is running
RUN Primary
RUN Standby
RUN Offline
Application program is NOT running
STOP Offline
CPU has no application program z z
Indicates health of battery
Steady = Battery is low
No message = Battery is OK
Indicates that port has activity
Indicates Modbus Plus activity
No activity
Serial port activity for RS-232
Serial port activity for RS-485
Indicates the card in slot 1 is being accessed
The status displayed indicates the health z z of the battery
Steady = Battery is OK
No message = Batery is low z z
Blinks, when the card in slot 2 is being accessed
The status displayed indicates the health of the battery
Steady = Battery is OK
No message = Batery is low
29
Overview Modicon Quantum Hot Standby with Unity
Using the PLC
Operations
Menus and
Submenus
Structure: PLC Operations menu and submenus
Quantum
PLC Operations =>
PLC Operations
Start PLC =>
PLC Operations
Stop PLC =>
PLC Operations
Init PLC =>
PLC Operations
Hot Standby =>
Press <ENTER> to confirm Start =>
Press <ENTER> to confirm Stop =>
Press <ENTER> to confirm Init =>
Hot Standby
State: State
Hot Standby
Mode: Mode
Hot Standby
Order: OOOOOO
Hot Standby
Transfer =>
Hot Standby
Diag: =>
Press <ENTER> to confirm Transfer =>
Hot Standby diag: halt
Hot Standby diag: rio fails
Hot Standby diag: hsby fails
Hot Standby diag: stop
Hot Standby diag: off keypad
Hot Standby diag: off %sw60
Hot Standby diag: takeover
Hot Standby diag: run
Hot Standby diag: plug&run
Hot Standby diag: power up
30
Overview Modicon Quantum Hot Standby with Unity
Submenu: PLC Operations: Start, Stop, Init
Start, Stop,
Init Screens
Display
Start PLC
Stop PLC
Init PLC
Fields Available Description
Press <ENTER> to confirm Start Pressing <ENTER> starts the controller
Press <ENTER> to confirm Stop Pressing <ENTER> stops the controller
Press <ENTER> to confirm Init Pressing <ENTER> initializes the controller
Submenu: PLC Operations: Hot Standby
Hot Standby
Screen
Displays
Hot Standby
State:
Hot Standby
Mode:
Hot Standby
Order:
Fields
Available
State
(read only)
Mode modifiable only if z key switch is in the unlocked z position
Invalidate
Keypad is not selected
OOOOOO
(read only)
Options Available Description
PRIMARY
STANDBY
Off Line
RUN
Controller serves as Primary
Controller serves as Standby
Controller is offline steady Controller is active and is either serving as the Primary or is capable of taking over the Primary role if needed blinking Controller is waiting for configuration
A
B
OFFLINE steady z Controller is taken out of service without stopping it or disconnecting it from power z If the controller is the Primary when the Mode state is changed to OFFLINE, control switches to the Standby z z
If the Standby is taken OFFLINE, the Primary continues to operate without a backup
OFFLINE mode does not manage the Remot I/O (RIO). (Only
Primary state manageds the RIO) blinking Controller is waiting for configuration
Hot Standby Power Order
The order comes from the MAC address. The controller with the lowest MAC address is A.
31
Overview Modicon Quantum Hot Standby with Unity
Hot Standby
Screen
Displays
Hot Standby
Transfer:
Hot Standby
Diag
Fields
Available
Mode modifiable only if z z
Options Available Description key switch is in the unlocked position
Invalidate Keypad is not selected
Order of diagnostic screens varies with the operation; therefore your order may be different from the list here.
Halt
RIO fails
HSBY fails
Stop
Off keypad
Off %sw60
Take over
Run
Plug & Run
Power up
Pressing the <ENTER> key confirms the Transfer. The transfer initiates the request for an application program update from the Primary controller.
Pressing any other key cancels the
Transfer request and returns the Hot
Standby Transfer menu option screen to the display.
User’s task in halt mode
Error reported by RIO head
Error reported by optical link
Stop command ordered
Offline command entered on keypad
Offline command set in command register
Standby switched to Primary mode
Run command ordered
Standby plugged and started
User powered up controller
32
Overview Modicon Quantum Hot Standby with Unity
Using the
Communications
Menus and
Submenus
Structure: Communications menu and submenus structure
Quantum
PLC Communications =>
Communications
TCP/IP Ethernet =>
Communications
Modbus Plus =>
Communications
Serial Port =>
TCP/IP Ethernet
IP Address =>
TCP/IP Ethernet
Subnet Mask =>
TCP/IP Ethernet
IP Gateway =>
TCP/IP Ethernet
MAC Address =>
MB+ Address: ##
Modbus Plus State
Mode Protocol: Adr
Rate,Par,DB,SB
=>
IP Address:
###.###.###.###
Subnet Mask:
###.###.###.###
IP Gateway:
###.###.###.###
MAC Address:
##.##.##.##.##.##
Serial Port
RS-Mode: RS-232
Serial Port
Protocol: Modbus
Serial Port
Unit Address: 1
Serial Port
Baudrate: 9600
Serial Port
Parity: Even
Serial Port
Databits: RTU - 8
Serial Port
RS-Mode: RS-232
Serial Port
Stopbits: 1
33
Overview Modicon Quantum Hot Standby with Unity
Submenu: PLC Communications: TCP/IP Ethernet
TCP/IP Ethernet
Screen Displays
TCP/IP Ethernet
IP Address 1,2
TCP/IP Ethernet
Subnet Mask
1
TCP/IP Ethernet
IP Gateway
1
TCP/IP Ethernet
MAC Address
Fields Available
###.###.###.###
(not modifiable)
###.###.###.###
(not modifiable)
###.###.###.###
(not modifiable)
##.##.##.##.##.##
(read only)
Options Available decimal numbers
Description displays IP address decimal numbers decimal numbers displays Subnet
Mask address displays Ethernet IP
Gateway address hexadecimal numbers displays MAC
(Medium Access
Control) address
Submenu: PLC Communications: Modbus Plus
Modbus Plus
Screen Displays
Modbus Plus
Address
Fields Available
##
(modifiable only if the key switch is in the unlocked position)
Modbus Plus State
Options Available
1-64
Monitor Link
Normal Link
Sole Station
Duplicate address
No Token
Description to enter a valid
Modbus Plus address
Modbus Plus State
34
Overview Modicon Quantum Hot Standby with Unity
Submenu: PLC Communications: Serial Port
Seriial Port
Screen Displays
Serial Port
Fields Available* Options Available Description
Mode
Protocol
Adr
232
485
ASCII
RTU
1 - 247 for Modbus switchover
Primary 1-119
Standby 129 - 247
RS mode
Protocols available
Unit address
Rate
Par
50, 75, 110, 134.5, 150,
300, 600, 1200, 1800,
2400, 3600. 4800, 7200,
9600, 19200 bits/s
NONE
ODD
Baud rate
Parity
DB
EVEN
7,8 Databits: if Protocol is Modbus then RTU-8 or ASCII-7
SB 1,2 Stopbits
* If the key switch is in the unlocked position, all fields are modifiable.
35
Overview Modicon Quantum Hot Standby with Unity
Using the
System Info
Menus and
Submenus
Structure: System Info menus and submenus
Quantum
System Info =>
System Info
Stop Code =>
System Info
Firmware Info =>
System Info
Hardware Info =>
Stop Code: ####
Description
OS Ldr Rev: ##.##
Exec Rev: ##.##
HW Rev: Rev
SN: ########
Submenu: PLC Communications: System Info
System Info
Screen Displays
Stop Code
Firmware Info
Hardware Info
Fields
Available*
Option
Available
Description
####
Description
##.##
##.##
Rev shows the machine stop code shows the description to the machine stop code shows the number of OS Loader Revision shows the number of Exec Revision
########
* All fields are read only.
shows the number of Hardware Revision shows the serial number of Hardware
36
Using the LCD
Settings Menus and Submenus
Overview Modicon Quantum Hot Standby with Unity
Structure: LCD Settings menus and submenus
Quantum
LCD Settings =>
LCD Settings
LCD Contrast:
LCD Settings
LCD Light:
### time
0% is black
100% is green
On
Off
1 Min
5 Min
10 Min
15 Min
Submenu: LCD Settings: LCD Contrast
LCD Screen
Contrast Screen
Displays
LCD Contrast:
Fields
Available
####
Description
A lower percent is darker. A higher percent is brighter.
z z
Use the arrow keys to adjust the setting.
Up arrow increases percent
Down arrow decreases percent
Submenu: LCD Settings: LCD Light
Screen Displays Fields Available Description
LCD Light: On
Off
LCD light remains on permanently or until changed
LCD light remains off permanently or until changed
1 Min
5 Min
10 Min
LCD light remains on for one minute
LCD light remains on for five minutes
LCD light remains on for ten minutes
15 Min LCD light remains on for fifteen minutes
37
Overview Modicon Quantum Hot Standby with Unity
38
Modicon Quantum Hot Standby with Unity Compatibility,
Differences, and Restrictions
2
Introduction
Overview
What's in this
Chapter?
In this chapter you will find an overview of compatibilities within a system that has already been installed, differences from Legacy Hot Standby systems, and restrictions for the Modicon Quantum Hot Standby with Unity system.
This chapter contains the following topics:
Topic
Compatibility with Installed Systems
Understanding System Words and System Bits
Understanding Multitasking Restrictions
Local I/O and Distributed I/O Restrictions
Understanding Other Module Restrictions
Understanding USB Link Restrictions
Understanding Application Restrictions
Page
39
Compatibility, Differences, Restrictions
Compatibility with Installed Systems
Modicon
Quantum Legacy
Systems
If you install a Unity Pro executive, you have to replace the Legacy CPU (16 and 32 bit) and the CHS option module with a Modicon Quantum Hot Standby with Unity
140 CPU 671 60. Otherwise, Modicon Quantum Hot Standby with Unity will not be available.
Note: EXISTING FIBER CONNECTIONS
Fiber connections used on the CHS module will NOT work with the Modicon
Quantum Hot Standby with Unity 140 CPU 671 60.
Note: CHANGING FROM LEGACY
To install a Modicon Quantum Hot Standby with Unity 140 CPU 671 60 controller in the backplane requires two sequential slots.
Legacy systems required two slots in the backplane, but the two slots did not need to be sequential.
Copro and
Remote I/O Head
Instead of a Modicon Quantum Hot Standby Option Module (140 CHS 110 00), an embedded coprocessor (Copro) provides a dedicated communications link transferring data between the Primary and Standby controllers. This dedicated link cannot be used for any other communications.
S908 Remote I/O Head Option Modules (140 CRP 93 x00) are required in the system for communicating with the remote I/O drops and exchanging status between the Primary and Standby controllers.
40
Compatibility, Differences, Restrictions
Understanding System Words and System Bits
Overview
System Word
%SW60
In conforming with IEC standards, Unity uses global objects called system bits and system words. Users of legacy Schneider Electric products may be familiar with registers (984LL notation). Regardless of notation, the behavior remains the same.
System Word %SW60 can be used to read from and to write to the Modicon
Quantum Hot Standby with Unity Command Register.
Note: %SW60 is described using the IEC convention.
System Word
%SW61
System Word
%SW62 and
%SW63
System Word %SW61 can be used to read the contents of the Modicon Quantum
Hot Standby with Unity Status Register.
Note: %SW61 is described using the IEC convention.
System Words %SW62 and %SW63 are reverse registers reserved for the Reverse
Transfer process. Both reverse registers can be written to the application program
(first section) of the Standby controller and are transferred at each scan to the
Primary controller.
41
Compatibility, Differences, Restrictions
Understanding Multitasking Restrictions
General
MAST
Asynchronous
Events
In a Modicon Quantum Hot Standby with Unity system, the Standby controller is kept ready to assume the role of the Primary controller by having the same application loaded (in the Standby) and by receiving from the Primary—once per scan—a copy of the Primary's data. During the scan, there is a tight synchronization between the
Primary and Standby.
Schneider Electric recommends using only MAST to transfer data during a scan.
Tasks are handled singly and sequentially. Using MAST is consistent with current
Modicon Quantum Hot Standby systems because multi-tasking is not provided, and data transfer will be synchronized with MAST.
Using a Modicon Quantum Hot Standby with Unity system in a multitasking environment may cause data to change between scans. Because in a multi-tasking system, events may occur asynchronously to the normal scan. Those events may happen at a faster rate, the same rate, or at a slower rate. The result is that data modified by these events can be changed during a transfer.
FAST and AUX
Note: FAST and AUX can be used.
Ensure that you both analyze your system needs and account for problems that may arise if you use FAST or AUX.
42
Compatibility, Differences, Restrictions
Local I/O and Distributed I/O Restrictions
General Note the two following restrictions: z Although local I/O and distributed I/O (DIO) can be used in a Modicon Quantum
Hot Standby with Unity system, they are not considered as part of the redundant system.
z When either local I/O and/or distributed I/O (DIO) are used in a Hot Standby system, each controller in the configured Hot Standby system controls ONLY its own local I/O and/or DIO respectively.
43
Compatibility, Differences, Restrictions
Understanding Other Module Restrictions
General The Modicon Quantum Hot Standby with Unity, V2.0 does not support the following modules.
Model
140 NOE 771 00
140 NOE 771 10
140 NOE 311 00
140 NOE 351 00
140 CHS 110 00
140 NOA 611 10
140 NOA 622 00
140 NOL 911 10
140 CRP 811 00
140 HLI 340 00
Support Provided
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
Module NOT supported in Unity V2.0
44
Compatibility, Differences, Restrictions
Understanding USB Link Restrictions
No Hot Standby
Switchover through the USB
Link
USB link switchover is not available in a Modicon Quantum Hot Standby with Unity system because the USB link is connected to only one CPU, allowing Unity Pro to communicate only to this local controller.
Therefore, USB cannot be used for transparent access to the Primary controller.
45
Compatibility, Differences, Restrictions
Understanding Application Restrictions
Timer Events and
I/O Errors
Timer events are NOT synchronized in Modicon Quantum Hot Standby with Unity applications. Schneider Electric recommends not using timer events.
Note: NOT EXCHANGING I/O ERRORS
If timer events are used, I/O errors are not exchanged between Primary and
Standby.
46
Using IEC Logic and Modicon
Quantum Hot Standby with Unity
3
Introduction
Overview
What's in this
Chapter?
This chapter provides information about using IEC Logic with a Modicon Quantum
Hot Standby with Unity system.
This chapter contains the following topics:
Topic
Modicon Quantum Hot Standby with Unity and IEC Logic
Understanding the Modicon Quantum Hot Standby with Unity State RAM
Transfer Process
Understanding System Scan Time in Modicon Quantum Hot Standby with
Unity Systems
Transferring Application Data in a Modicon Quantum Hot Standby with Unity
System
Page
47
IEC Logic
Modicon Quantum Hot Standby with Unity and IEC Logic
Overview
Data Transfer and User Data
A Modicon Quantum Hot Standby with Unity system requires two backplanes configured with identical hardware, software, and firmware. One of the controllers
(PLC) functions as the Primary controller and the other as a Standby controller.
z The Primary updates the Standby after every scan.
z The Primary and Standby communicate constantly monitoring the health of the system.
z If the Primary fails, the Standby takes control within one scan.
In a Modicon Quantum Hot Standby with Unity system, data is transferred from
Primary to Standby after every scan.
The following data transfers after every scan: z Located Variables (State RAM 128 Kb) z z all Unlocated variables up to 512 Kb
All instances of the DFB and EFB type z z
SFC variable area
System Bits and Words
Note: Forced Bits at Transfer
At each scan, all forced bits are transferred from the Primary to the Standby.
State RAM
Definition
State RAM is the memory range, which is used for z z word-orientated input and output components (for example, analog modules) bit oriented input and output components (for example, digital modules) z binary and word variables for the application program
State RAM is assigned the four reference types: %IW, %QW, %I and %Q.
48
Understanding the Modicon Quantum Hot Standby with Unity State RAM
Transfer Process
IEC Logic
Hot Standby
Transfer
Diagram
The following illustrates the transfer of data from the Primary to the Standby Copro:
Scan n
Primary PLC
CPU
Copro
IEC Logic Solve Comm Diag IEC Logic Solve
User Data
State RAM: Located + Unlocated Data
(max. 128 + max. 512 kByte)
640K bytes
640K bytes
Comm Diag IEC Logic Solve Diag
640K bytes
Standby PLC
User Data
State RAM: Located + Unlocated Data
(max. 128 + max. 512 kByte)
Copro
640K bytes
Diag
640K bytes
User Data
State RAM: Located + Unlocated Data
Comm Diag
CPU
640K bytes
Comm Diag
Scan n-1
49
IEC Logic
Understanding System Scan Time in Modicon Quantum Hot Standby with Unity
Systems
Effect on System
Scan Time
The scan time of any Modicon Quantum Hot Standby with Unity system depends on the amount of data transferred.
Because data must be transferred from Primary to Standby, any Modicon Quantum
Hot Standby with Unity system always has a higher scan time than a comparable standalone system.
Note: CHANGING FROM LEGACY
In legacy systems, the CPU performed both z application program (project) processing z communication transfer
In a Modicon Quantum Hot Standby with Unity system, in parallel z z
CPU performs application program processing
Copro performs communication transfer
Result: Greatly reduced transfer time with Unity
50
Performance
Considerations
IEC Logic
A Modicon Quantum Hot Standby with Unity system increases the length of a MAST scan, creating system overhead.
Note: System Overhead
System overhead is the time required to copy the application data to the communication link layer.
The network scan (communication between Primary and Standby copros)
1.
exchanges data between both controllers
2.
runs in parallel with the application program
A Hot Standby system
Input
HSBY
Input
HSBY
5 ms per 100 Kb of Overhead
First
Section
Logic
Data
(Copro)
Data
(Copro)
30 ms per 100 Kb
Output
Primary Standby
Output
Most of time, the MAST scan hides the network scan.
51
IEC Logic
Examples
Standalone scan time: 80 ms
100 KB data to exchange
Input
HSBY
Scan time in a HSBY system: 85 ms
100 KB data exchanged
Result
Primary
5 ms per 100 Kb of overhead
Data
Transfer
30 ms
No impact on scan time data exchange (30 < 80 ms)
Logic
Exec
However, when processing some application programs, additional system overhead may occur.
Example #1 z Standalone application scan time: 80 ms z Data (state RAM + unlocated variables): 100 Kb
Output
Example #2 z
Standalone application scan time: 80 ms z Data (state RAM + unlocated variables): 300 Kb
52
IEC Logic
Standalone scan time: 80 ms
300 KB data to exchange
Input
HSBY
Scan time with HSBY: 105 ms
300 KB data exchanged
Result
Primary
15 ms per 100 Kb of overhead
90 ms
HSBY impact on scan time = 25ms
= 15 ms + (90 - 80 ms)
= 25 ms
Logic
Exec Data
Transfer
Output
53
IEC Logic
Transferring Application Data in a Modicon Quantum Hot Standby with
Unity System
Changing from
Legacy
Modicon
Quantum Hot
Standby with
Unity
Memory
Consumption
Current Modicon Quantum controllers that use the Concept software have an application data transfer limit of approximately 128 Kb. This limit includes located data (in state RAM) and unlocated data. To transfer the unlocated data, the system must use a part of the 3x area in the state RAM. Schneider Electric chose this method to be compatible with the existing CHS option module (140 CHS 110 00).
Thus, a trade-off is necessary: the more unlocated data, the less state RAM and vice versa.
In the Modicon Quantum Hot Standby with Unity 140 CPU 671 60, the CHS option module is no longer used. Both the controller and Hot Standby functions are in the same unit. Thus, there is no need to force unlocated data through the 3x area. Not forcing means that all of the state RAM can be used as state RAM (up to 128 Kb).
In addition to the state RAM, you may have a maximum of 512 Kb of unlocated data.
The amount of data to be transferred is automatically adjusted by the system.
For Information on the size of the memory consumption, select PLC → Memory
Consumption .
54
Setting up and Maintaining a
Modicon Quantum Hot Standby with Unity System
II
At a Glance
Purpose
What's in this
Part?
This part describes three important processes in using a Modicon Quantum Hot
Standby with Unity system.
z setting up, installing, and cabling a Modicon Quantum Hot Standby with Unity system z z configuring a Modicon Quantum Hot Standby with Unity system using the Unity
Pro software maintaining a Modicon Quantum Hot Standby with Unity system once installed
This part contains the following chapters:
Chapter
4
5
6
Chapter Name
Setting up, Installing, and Cabling a Modicon Quantum Hot
Standby with Unity System
Configuring a Modicon Quantum Hot Standby with Unity
System
Maintaining a Modicon Quantum Hot Standby with Unity
System
Page
55
Maintaining Modicon Quantum Hot Standby with Unity
56
Setting up, Installing, and Cabling a Modicon Quantum Hot Standby with Unity System
4
Introduction
Overview
What's in this
Chapter?
This chapter provides an overview of setting up, installing, and cabling a Modicon
Quantum Hot Standby with Unity system.
This chapter contains the following topics:
Topic
Setting Up the Modicon Quantum Hot Standby with Unity System
Mapping the Backplane Extension
Connecting Two Modicon Quantum Hot Standby with Unity HE CPU 671 60s
Connecting the Remote I/O
Testing the Modicon Quantum Hot Standby with Unity System
Page
57
Installation and Cabling
Setting Up the Modicon Quantum Hot Standby with Unity System
Overview
Mapping the
Backplane
Extensions
Schneider Electric is a leader in offering fault-tolerant, redundant systems, Hot
Standby. Setting up a Modicon Quantum Hot Standby with Unity system involves a number of processes, summarized in the following paragraphs here and explained in detail elsewhere.
A Modicon Quantum Hot Standby with Unity requires two backplanes with at least four slots.
You must map the two backplanes in an identical manner: z same Modicon Quantum Hot Standby with Unity HE CPU with integrated coprocessor (Copro) z z z z same firmware same revision level same Modicon Quantum power supply module same Modicon Quantum RIO Head
And, if other modules are used, for example local I/Os, NOMs, NOEs, those modules must be identical.
Connecting Two
High End CPUs
Connect the two Modicon Quantum Hot Standby with Unity High End CPUs with a fiber optic cable as described in Connecting Two Modicon Quantum Hot Standby
with Unity HE CPU 671 60s, p. 62
.
Establishing the
Primary and
Standby
Controllers
The system determines that one of the two Modicon Quantum Hot Standby with
Unity HE CPUs will be the Primary controller and the second controller as the
Standby.
The Keypad may provide status information. Therefore, to view the status, use the
Modicon Quantum Hot Standby with Unity HE CPU’s keypad by selecting Quantum
PLC Operations => → PLC Operations Hot Standby => → Hot Standby Order .
See Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LCD
.
Connecting the
Remote I/O
Configuring in
Unity Pro
Connect the Modicon Quantum RIO Heads with each other and with the RIO drops as described in
Connecting the Remote I/O, p. 63 .
Using Unity Pro, configure a network that is appropriate for the installed backplanes and the cabling.
Configure the Hot Standby Register for the Modicon Quantum Hot Standby with
Unity HE CPU in Unity Pro as described in
Accessing the Base Configuration, p. 73 .
58
Installation and Cabling
Transferring and
Sending the
Program from
Primary to
Standby
Transfer the program from your PC to High End CPU using the Unity Pro command
PLC → Transfer program to PLC .
See
Overview of Application Program Transfer, p. 160 .
Send your program from the Primary to the Standby using the Primary’s keypad.
Select Quantum PLC Operations => → PLC Operations Hot Standby => → Hot
Standby Transfer => → Press <ENTER> to confirm Transfer => .
See Using the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 LCD
Note: A program can be sent only from the Primary controller to the Standby controller.
59
Installation and Cabling
Mapping the Backplane Extension
Requiring
Identical
Backplanes
Two backplanes must be configured with identical hardware, software, and firmware in identical order. Then, both controllers may function either as a Primary controller or as a Standby controller.
Note: INSTALLING CONTROLLERS
Schneider Electric recommends referring to Schneider Electric planning and installation guidelines. You will find more information in the Quantum Automation
Series Hardware Reference Guide 840 USE 100 00 and in Remote I/O Cable
System Planning and Installation Guide 840 USE 101 00 .
Noting the
Module Version
The Primary and Standby must belong to the Modicon Quantum Hot Standby with
Unity product family.
The Modicon Quantum RIO drops can be from Schneider Electric’s 800 series of modules.
60
Installation and Cabling
Installing
Components and
Modules
A Modicon Quantum Hot Standby with Unity system requires two backplanes with at least four slots.
The backplanes (1, 2) must be identically equipped with: z Modicon Quantum Hot Standby with Unity 140 CPU 671 60 with integrated z coprocessor (Copro) (3)
Modicon Quantum power supply module (4) z z
Modicon Quantum RIO Head (5)
Other modules for example, Modicon Quantum NOMs, NOEs (6)
Note: The sequence of the modules on the backplane is not predefined, but the sequence of the modules on the backplanes of the Primary and the Standby must be identical. Otherwise, a Modicon Quantum Hot Standby with Unity system does not exist.
The following graphic shows a possible scheme for components and their connectors.
1 2
4 3 5 6 4 3 5 6
A B
7
A B
8A
9 8
1 Primary controller backplane
2 Standby controller backplane
3 Modicon Quantum Hot Standby with Unity 140 CPU 671 60 with integrated coprocessor
(Copro)
4 Modicon Quantum power supply module: Install power supply in first slot for better rack layout.
5 Modicon Quantum RIO head
6 Other modules, for example Modicon Quantum NOMs, NOEs
7 Fiber Optic Cable to connect to both Modicon Quantum Hot Standby with Unity 140 CPU
671 60s.
8 Coaxial cable with splitters (8A) for connecting the RIO heads (5) with the RIO drops in the network. The dashed connection represents a redundant connection in the RIO network, which is not required for the Modicon Quantum Hot Standby with Unity system.
9 Connection to the Unity Pro computer via Modbus or Modbus Plus
61
Installation and Cabling
Connecting Two Modicon Quantum Hot Standby with Unity HE CPU 671 60s
Handling Cable
Connections
If the cable is not connected properly, the Modicon Quantum Hot Standby with Unity
HE CPU 671 60s cannot communicate, and the Hot Standby system will not function. Therefore, the Primary operates without a backup, and the Standby remains offline.
Fiber optic cables are sold separately.
Model
490NOR0003
490NOR0005
490NOR0015
Description
3 m MTRJ/ MTRJ
5 m MTRJ/ MTRJ
15 m MTRJ/ MTRJ
Controllers connected by a crossed fiber optic cable.
COM
STS
COM
STS
Mac Address
00:00:##:##:##:##
Mac Address
00:00:##:##:##:##
Note: REDUCING FAILED COMPONENTS
Hubs and switches are not allowed as part of the fiber optic link.
Therefore, the fiber connection between Primary and Standby must be a direct cable connection, which reduces the components that could fail in the redundant system.
Connecting Two
Backplanes
However, the Primary and Standby backplanes may be placed as much as 2 km apart. If you will be placing the modules more than 15 m apart, use 62.5/125 micrometer cable with MTRJ type connectors. Refer to Modicon Quantum Hot
Standby with Unity Additional Information, p. 183
for details.
62
Installation and Cabling
Connecting the Remote I/O
Connecting
Cables to
Remote I/O
In each configuration: z The cables connecting the RIO head processors to the RIO network have to be z fitted with self-terminating F adapters.
An MA-0186-100 coaxial splitter has to be installed between the RIO head z processors and the RIO network.
The remote drops have to be connected to the trunk cable via an MA-0185-100 z tap and a drop cable.
The last tap on a trunk cable has to be terminated with a 52-0422-000 trunk z terminator. Remote drops have not be connected directly to the trunk cable.
An optional 60-0545-000 Ground Block at the head will provide earth ground connection when the cable and RIO processor are disconnected. Ground blocks may also be used at other ground points along the trunk cable, as required.
Refer to the Remote I/O Cable System Planning and Installation Guide, 890 USE
101 00 for details.
Note: CABLING REQUIREMENTS z If you are using a Modicon Quantum Hot Standby with Unity system for data logging, the RIO heads have to be configured and connected with coaxial cable, and you have to configure one (1) or more RIO drops.
63
Installation and Cabling
The following diagram shows the hardware required for the Remote I/O cabling.
1 2
3 3
A B A B
6
5
7
4
8
4
9
1 Primary controller
2 Standby controller
3 Modicon Quantum RIO head
4 Modicon Quantum RIO drop
5 Coaxial cable (components shown with dashed lines are not mandatory)
6 Self-terminating F adapter
7 Splitter (MA-0186-100)
8 Tap (MA-0185-100)
9 Trunk Terminator (52-0422-000)
64
Installation and Cabling
Connecting over
Long Distances
If you intend to place the units more than 3 meters apart, you have to consider the effect on the RIO network and any Modbus Plus network.
The controllers are linked to the RIO network by coaxial cable. The longer the distance between the controllers, the higher the grade of trunk cable required to maintain signal integrity.
Refer to the Remote I/O Cable System Planning and Installation Guide, 890 USE
101 00 for details regarding cable grades, distances, and signal integrity.
If no coaxial cable will be sufficient to maintain signal integrity throughout the RIO network, fiber optic repeaters may be used to boost the signal.
Refer to the Modbus Plus Network Planning and Installation Guide, UNY USE 10410
V10E for details on extending a Modbus Plus network.
65
Installation and Cabling
Testing the Modicon Quantum Hot Standby with Unity System
Testing Methods
(First Time)
Follow these steps to conduct tests to observe z Hot Standby start-up z z automatic Application Program Transfer switchover of control from Primary to Standby
These tests are not necessary but helpful. If your backplanes are horizontally parallel and within 1 meter (3 feet) apart, the transfer process is easier to observe.
Hot Standby
Start-up and
Application
Program
Transfer
Follow these steps.
Step
1
2
3
4
5
6
7
8
Action
Configure two backplanes with identical hardware and firmware in identical order.
Connect to a Remote I/O (RIO) drop. Establishing the Primary and Standby
Note: Ensure that the fiber optic cable is connected between the controllers.
Start Unity Pro software and configure the local rack and the Remote I/O drop as per your physical configuration.
After completing Step 3, execute the Build Project command, and save your application program.
Power up and connect to one controller.
Note: The front panel keypad will display No Conf .
Download your application program and RUN the controller.
Note: The controller will become RUN Primary.
Power up the other controller.
Note: Application Program Transfer will occur automatically. The "other" controller will become RUN Standby.
Ensure the Primary and Standby controllers are in RUN Primary and RUN
Standby mode.
66
Preparing to
Switchover
Installation and Cabling
After completing the preceding steps, your Modicon Quantum Hot Standby with
Unity system is ready to perform a switchover. Perform the switchover using either: z z
Hot Standby submenu on the front panel keypad
Command Register, system bit %SW60.1 or %SW60.2
Note: Observing the Switchover
If you would like to observe a switchover effect on the I/O modules, configure the
Remote I/O (RIO) drop with a discrete output module during your initial start-up.
Before performing a switchover, connect to the Primary and force the output bits in the module. Perform the switchover and take note of the bumpless switchover effect on the forced bits.
Switchover Test
Using Front
Panel Keypad
To force a switchover using the front panel keypad, do the following:
Step
1
2
3
4
5
6
Action
Access the front panel keypad of the Primary controller.
Go to PLC Operation menu.
Go to Hot Standby submenu.
Go to Hot Standby mode
Modify Run to Offline.
Note: Ensure that Standby switched to Primary.
Modify offline to run.
Note: Ensure that the LCD displays Run Standby .
67
Installation and Cabling
Switchover Test
Using Command
Register
Follow these steps.
Step
1
2
3
4
5
6
7
8
Action
Connect to the Primary.
Observe whether the controller order on the Primary is A or B.
Note: Observe using either of the following methods: z Front panel keypad of the Primary
PLC Operation | Hot Standby | Hot Standby Order z Unity Pro status dialog
Refer to the bottom of the Unity Pro window when connected online
Access the Command Register system bit z %SW60.1
(If the connected Primary order is A.) z %SW60.2
(If the connected Primary order is B.)
Set bit to 0.
Note: Ensure that the Standby switched to Primary
Connect to the new Primary.
Access the Command Register system bit. Choose the same bit selected in Step
3.
Set bit to 1.
Note: Ensure Standby displays RUN Standby.
Ensure the Primary and Standby controllers are in RUN Primary and RUN
Standby mode.
68
Configuring a Modicon Quantum
Hot Standby with Unity System
5
Introduction
Overview
What's in this
Chapter?
This chapter describes configuring the Modicon Quantum Hot Standby with Unity
140 CPU 671 60 module.
This chapter contains the following sections:
Section
5.1
5.2
5.3
Topic
Configuring a System with the Unity Pro Tabs and Dialogs
Configuring a NOE with Unity Pro
Configuring Registers with Unity Pro
Page
69
Configuring a Modicon Quantum Hot Standby with Unity System
5.1
Configuring a System with the Unity Pro Tabs and
Dialogs
At a Glance
Purpose
What's in this
Section?
Use the Unity Pro editor dialog tabs to
1.
select options for configuring the Modicon Quantum Hot Standby with Unity 140
CPU 671 60
2.
obtain system status information
This material describes how you can z z z
Accessing the Base Configuration, p. 73 , including Modbus Ports and HSBY
Configuring with Unity Pro, p. 86
Configuring with Unity Pro, p. 87
This section contains the following topics:
Topic
Introducing Unity Pro
Accessing the Base Configuration
Using the Summary Tab
Using the Overview Tab
Using the Configuration Tab
Using the Modbus Port Tab
Using the Animation Tab and PLC Screen Dialogs
Using the Hot Standby Tab
Configuring the PCMCIA Cards
Configuring the Modbus Plus Communication Type
Setting the Invalidate Keypad Option
Swapping Network Addresses at Switchover
Page
70
Configuring a Modicon Quantum Hot Standby with Unity System
Introducing Unity Pro
Overview Unity Pro software is a fully Windows compatible application. Unity Pro supports only the IEC method of configuration with some simplifications: z Removes the legacy requirement to reserve the 3xxxx area for transferring unlocated variables z
(Unlocated variables are transferred with the State RAM).
Uses system words for the command and status registers, which are removed from the State Ram.
No Loadables
Needed
Command
Register
Changes from
Concept
Note: CHANGING FROM LEGACY
The current Modicon Quantum Hot Standby loadable (CHS) is no longer needed.
For Unity Pro Modicon Quantum Hot Standby with Unity systems, the control functionality will be embedded in the executive.
For legacy Modicon Quantum Hot Standby systems (Modsoft, Concept, or
ProWORX), the CHS module owns the control functionality.
The Command Register defines the basic operational parameters of a Modicon
Quantum Hot Standby with Unity solution. The command register’s functionality is described in
Understanding the Unity Command Register, p. 110 .
z z z z z
Command and Status Registers are no longer stored in the State RAM.
Command and Status Registers are accessible in the system words %SW60 and
%SW61.
Reverse Transfer registers are no longer stored in the State RAM.
System automatically allocates system words %SW62 and %SW63 as Reverse
Transfer words.
Reverse Transfer words are no longer part of the Non-Transfer Area of the 4xxxx registers.
71
Configuring a Modicon Quantum Hot Standby with Unity System
Changes from
LL984 z z
Note: CHANGING FROM LEGACY
There is no longer a Non-Transfer Area for the 0xxx, 1xxx, and 3xxx registers.
Transferring over multiple scans is no longer available.
In current Modicon Quantum Hot Standby Systems using the CHS option module, additional state RAM could be transferred over multiple scans. Not transferring over multiple scans minimizes the impact of state RAM transfers.
In the Unity Pro Modicon Quantum Hot Standby with Unity 140 CPU 671 60, transfer speeds will be much faster, and the amount of state RAM used for transfers will be smaller since unlocated data will be used instead.
Opening the
Editor Dialog
After starting Unity Pro, go to the Local Bus in the Structural View of the Project
Browser.,
Step Action
1 Open the Local configuration editor either by double-clicking on the Local Bus or by selecting the Local Bus and executing right-click Open
A graphical representation of the local bus appears in the configuration editor.
2 Select the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 module and right-click.
The context menu appears.
3 Select Open Module.
4 The editor appears. The Summary tab is the default.
Unity Pro Hot
Standby Editor
Dialog
The editor with the Hot Standby tab selected
NA
CPU
1.2 : 140 CPU 671 60
P266 CPU Hot-Standby, 1Mb Program + PCMCIA, Ethernet-HSBY Fiber optic, USB, MB, MB+
Over...
Sum...
Confi...
M
B Modb...
Anima...
Hot St...
Run Mode
Controller A
Controller B
Online
Online
Standby On Logic Mismatch
Offline
Online
State RAM
Non-Transfer Area
Start: %MW 0
Invalidate Keypad
Yes
Swap Address At Switchover
Modbus Port 1
Modbus Port 2
Modbus Port 3
Length: 0
I/O objects
72
Configuring a Modicon Quantum Hot Standby with Unity System
Accessing the Base Configuration
Accessing with
Unity Pro
After starting Unity Pro, go to the Local Bus in the Structural View of the Project
Browser.
Step Action
1 Open the Local Bus configuration editor either by double-clicking on the Local Bus or by selecting the Local Bus and executing right-click Open.
A graphical representation of the local bus appears in the configuration editor.
2 Select the Modicon Quantum Hot Standby with Unity HE CPU module and right-click.
The context menu appears.
Bus:
Local Bus
1 140 CPU 671 60 01.00
1
CPS
111
00
2
CPU
671
60
CPU
671
60
ACI
030
00
4 5 6 7 8 9 10
1
Cut
Copy
Paste
Delete Module
Open Module
Move Module
Replace Processor...
Power Supply and IO Budget...
3 Select Open Module.
The editor appears. The Summary tab is default.
4 Choose one of these tabs: z z
Summary (See
Using the Summary Tab, p. 74 )
Overview (See
Using the Overview Tab, p. 75 )
z Configuration (See
Using the Configuration Tab, p. 76 )
Modbus Port (See
Using the Modbus Port Tab, p. 79 )
z z z
Animation (See
Using the Animation Tab and PLC Screen Dialogs, p. 81
Hot Standby (See
Using the Hot Standby Tab, p. 85
)
)
73
Configuring a Modicon Quantum Hot Standby with Unity System
Using the Summary Tab
Viewing Use the Summary tab of the Unity Pro editor to determine if Peer Cop and Hot
Standby are enabled.
NA
CPU
1.2 : 140 CPU 671 60
P266 CPU Hot-Standby, 1 Mb Program + PCNCIA, Ethernet-HSBY Fiber optic, USB, MB, MB+
Over...
Sum...
Confi...
M
B Modb...
Anima...
Hot St...
I/O objects
CPU Name/Model
Peer Cop:
Hot Standby:
Quantum CPU
Enabled
Enabled
Describing Summary tab:
Item Option Value Description
CPU Name/Model: Quantum CPU N/A
Peer Cop: Disabled
Read Only
Enabled Read Only
Peer Cop="Enabled" if the function is valid in the Modbus Plus menu
Hot Standby: Enabled Enabled Read Only
74
Configuring a Modicon Quantum Hot Standby with Unity System
Using the Overview Tab
Viewing The read only Overview tab of the editor displays detailed information about the module’s specifications.
NA
CPU
1.2 : 140 CPU 671 60
P266 CPU Hot-Standby, 1 Mb Program + PCMCIA, Ethernet-HSBY Fiber optic, USB, MB, MB+
Over...
CPU
671
60
ACI
030
00
Sum...
Confi...
M
B Modb...
Anima...
Hot St...
P266 CPU MB MB+ USB ETHERNET HSBY 1024K IEC AND PCMCIA
SPECIFICATIONS
Model
Description
General Specifications
Communications ports
I/O objects
140-CPU-671-60
P266 CPU MB MB
Bus Current required
Max. number of NOM, NOK, CRP 811 and
MMS modules supported (any combination)
Key switch
Processor
-
1 Modbus (RS-232
1 Modbus Plus (R
1 USB
1 Ethernet (used
6
Yes
75
Configuring a Modicon Quantum Hot Standby with Unity System
Using the Configuration Tab
Viewing Change values using the Configuration tab of the editor.
NA
CPU
1.2 : 140 CPU 671 60
P226 CPU Hot-Standby, 1 Mb Program + PCMCIA, Ethernet-HSBY Fiber optic, USB, MB, MB+
Over...
Sum...
Operating Mode On Cold Start
Automatic start in Run
%MWi Reset
Confi...
M
B Modb...
Memory Card
A: TSX MCP C 002M
Usage: Data Storage
Size
Application Size
1,024
2,048
B: TSX MRP F 008M
Usage: Data Storage
Size 8,192
KBytes
KBytes
KBytes
Anima...
State RAM
Mem usage
Hot St...
%M
%I
0x
256
1x
256
I/O objects
4%
%MW
%IW
4x
1024
3x
1024
Viewer
76
Describing
Configuring a Modicon Quantum Hot Standby with Unity System
Configuration tab:
Item
Operating Mode
On Cold Start
Memory Cards
State RAM
Option
Automatic start in Run
Value Description x
%MWi Reset on cold start x
Determines the operating condition during Cold Start
A:
B:
N/A
N/A
Displays the configuration in the
PCMCIA Slots
Mem usage
%M-0x
%MW-4x
%I-1x
%IW-3x
1.
2.
2.
2.
2.
A bar displays percent of memory used.
Size of the different memory areas
Note: The values for %IW and %MW have to be divisible by 8.
Viewer N/A Opens the State RAM Viewer tab, which displays the allocation of used memory. (See the illustration following.)
1. The value (expressed as a percentage and displayed on the scale) depends on the memory usage of the Hot Standby configuration.
2. Enter the appropriate values. All values depend on Hot Standby configuration.
77
Configuring a Modicon Quantum Hot Standby with Unity System
Using the State
RAM Viewer
The State RAM Viewer dialog
State Ram Viewer
1 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 1
0
100
200
300
400
500
600
700
800
900
1000
1100
Legend
Modules
Language
Variables
Modules Variables
Address Information
Address %M 0
Module Address
Language
Go To
Memory Area
%M (0x) %I (1x) %IW (3x) %MW (4x)
78
Each cell in the grid represents an address location and displays the entity stored in that location. The contents of the grid may be changed by selecting options in either of two filters:
1.
Memory used grid options
Select one—or all—of the three options (using the check box) and one to three bar graphs appear.
z
Modules
Indicates the topological address used in the modules. Address appears as a z bar graph in the grid.
Language
Indicates the topological address used in the program. Address appears as a bar graph in the grid.
z
Variables
Indicates the topological address used in the variables. Address appears as a bar graph.
2.
Memory Area options
Using this option, you designate a state RAM address. Select one of four reference types.
z z z z
%M
%I
%IW
%MW
Your choice appears in the Address field of the Address Information area.
Configuring a Modicon Quantum Hot Standby with Unity System
Using the Modbus Port Tab
Viewing You may change Modbus communication options using the Modbus Port tab of the
Unity Pro editor:
NA
CPU
1.2 : 140 CPU 671 60
P266 CPU Hot-Standby, 1Mb Program + PCMCIA, Ethernet-HSBY Fiber optic, USB, MB, MB+
Over...
Sum...
Confi...
M
B Modb...
Anima...
Hot St...
Bridge Mode
I/O objects
Modbus Port
Baud
1
2
3
9600
9600
9600
Data
Bits
Stop Bits
8 1
Parity
Even
Delay (ms) Address Head Slot
10 1
Mode
0 RTU
8 1
8 1
Even
Even
10
10
1
1
0 RTU
0 RTU
Protocol
RS232
RS232
RS232
Note: FINDING MODBUS ADDRESS
If you need the Modbus address of the controller, go to the 140 CPU 671 60 module and find the address using the keypad. (See Understanding the Default Screen,
79
Configuring a Modicon Quantum Hot Standby with Unity System
Describing Modbus Port tab:
Item Option
Modbus Port Baud
Data Bits
Stop Bits
Parity
Delay (ms)
Address
Head Slot
Mode
Protocol
Value
9600
50-19200 kBit/s
8
1 or 2
EVEN
ODD
NONE
1 ms
1 -247 for Modbus switchover
1 - 119 (Primary)
129 - 247 (Standby)
0
RTU
ASCII
RS232
RS485
Description
Data must be specified for every link.
80
Configuring a Modicon Quantum Hot Standby with Unity System
Using the Animation Tab and PLC Screen Dialogs
Accessing the
PLC Screen
Dialogs
To access the Task, Realtime clock, and Information tabs of the Unity Pro Animation tab,
Step
1
2
Action
Select the Animation tab.
The PLC screen tab appears automatically.
Note: The dialogs illustrated here are depicted in offline mode. When Unity Pro is connected to a PLC, the information displayed in these tabs changes.
Viewing the Task
Tab
Unity Pro Task tab dialog:
PLC Screen
Task
Events
Activate or
Disable all
State:
Number:
Last Stop
Realtime clock
Start/reStart
Warm restart
Cold start i Information
Output Fallback
Applied Outputs
Output Fallback
81
Configuring a Modicon Quantum Hot Standby with Unity System
Describing the
Task Tab
Description of the Task tab:
Item
Events
Option
State:
Value xxx
Start/reStart
Number: xxx
Activate or Disable all Click button
Warm Start
Cold Start
Click button
Click button
Output fallback Applied Outputs
Output Fallback
Last Stop Read only z z z
N/A
N/A
Day
DD/MM/YY
Time
Description
Status information of events available Online
N/A
Button to control the events
To initialize Warm Start
To initialize Cold Start
Not used in Modicon Quantum
Hot Standby with Unity system
Indicates the day, date, time, and cause of the last controller stop
Viewing the
Realtime Clock
Tab
Unity Pro Realtime clock tab dialog: i PLCScreen
Task
PLC Date and Time
Tuesday, 01. January 2002
12:00:00 AM
PC Date and Time
Thursday, 25. September 2003
2:38:05 PM
1 2
Update :
PC -> PLC
Error PLC Data
Realtime clock
User Date and Time
September, 2003
Sun Mon Tue Wed Thu Fri Sat
31 1 2 3 4 5 6
7 8 9 10 11 12 13
14 15 16 17 18 19 20
21 22 23 24 25 26 27
28 29 30 1
5 6 7 8
2
9
3 4
10 11
Today: 9/25/2003 i Information
Date:
25/09/2203
Time:
2:36:42 AM
Update :
User -> PLC
82
Describing the
Realtime Clock
Tab
Configuring a Modicon Quantum Hot Standby with Unity System
Description of the Realtime clock tab:
Item
PLC Date and Time
Option
Read only
Description
Indicates the current PLC date and time
PC Date and Time Update PC->PLC Updates the PLC with the PC system time
User Date and Time Update User->PLC Updates the PLC with the time set by the user
Viewing the
Information Tab
Unity Pro Information tab dialog:
P L
C S
PLC Screen
Task
SYSTEM INFORMATION
PLC
IDENTIFICATION
MEMORY
APPLICATION
IDENTIFICATION
OPTION
HOTSTANDBY
Realtime clock i Information
83
Configuring a Modicon Quantum Hot Standby with Unity System
Describing the
Information Tab
Description of the Information tab:
Item
System
Information
Option
PLC / Identification
Value
PLC Range
Hardware ID
Processor Name
Processor Version
Network address
PLC / Memory
Application / Identification
Application / Option
Hot Standby
Name
Creation Product
Date
Modification Product
Date
Version
Signature
Empty Terminal Support
Upload Information
Comments
Animation Table
Global Protection
Section Protection
Application Diagnostic
Forced Bits
Bit Number
Status Register
PLC Mode
Other PLC Mode
PLCs matching Logic
PLC switch
Copro Health
Hot Standby Capability
Description
Only Online available
84
Configuring a Modicon Quantum Hot Standby with Unity System
Using the Hot Standby Tab
Viewing the Hot
Standby Tab
Configure Hot Standby values in the Hot Standby tab of the Unity Pro editor:
NA
CPU
1.2 : 140 CPU 671 60
P266 CPU Hot-Standby, 1Mb Program + PCMCIA, Ethernet-HSBY Fiber optic, USB, MB, MB+
Over...
Sum...
Run Mode
Controller A
Controller B
Online
Online
Standby On Logic Mismatch
Offline
Online
State RAM
Non-Transfer Area
Start: %M 1
Confi...
M
B Modb...
Anima...
Invalidate Keypad
Yes
Length: 0
Hot St...
Swap Address At Switchover
Modbus Port 1
Modbus Port 2
Modbus Port 3
I/O objects
Describing the
Hot Standby Tab
Description of the Hot Standby tab:
Item
Run Mode
Invalidate Keypad
Option
Controller A
Controller B
Disable
Enable
Value
Offline/Online
Offline/Online
Yes is NOT selected
Yes is selected
(Check mark displays)
Description
Indicates which controller is offline and which controller is online
When selected, you prevent keypad changes to the Hot
Standby submenu.
Standby On Logic
Mismatch
Swap Address At
Switchover
State RAM: Non-
Transfer Area
Offline
Online -
Default
Offline button selected
Modbus Port 1 x
Start: %MW
Length:
1.
1.
If mismatch is detected,
Standby goes Offline
If button is selected and mismatch is detected, Standby remains Standby
When selected, enables
Modbus switchover to occur.
%MW is not transferred.
Specify the range of the length.
1. Enter the appropriate values. All values depend on Hot Standby configuration.
85
Configuring a Modicon Quantum Hot Standby with Unity System
Configuring the PCMCIA Cards
Configuring with
Unity Pro
Allocating memory to the memory card
Step Action
1 If not opened, open the Local Bus configuration editor.
2 Go to the local bus in the Structural View of the Project Browser.
3 Open the local bus either by double-clicking on the Local Bus or by selecting the
Local Bus and executing right-click Open.
A graphical representation of the local bus appears.
4 Point to and select either PC CardA (1 slot) or PC CardB (2 slot).
1
CPS
111
00
2
CPU
671
60
CPU
671
60
ACI
030
00
4 5 6 7 8 9 10 11 12 13 14
1
2
1 Memory configuration of the PCMCIA card 1
2 Memory configuration of the PCMCIA card 2
5 Double-click or right-click either PCMCIA card.
The New/Replace Submodule dialog appears.
New/Replace Submodule
PartNumber
ATA FLASH DISK
TSX MDP F 032M
FLASH EPROM
SRAM
TSX MRP F 0128P
TSX MRP F 0256P
TSX MRP C 001M
TSX MRP C 002M
TSX MRP C 003M
TSX MRP C 007M
TSX MRP C 768K
SRAM Data or Files
TSX MRP F 002M
TSX MRP F 004M
TSX MRP F 008M
Description
ATA FLASH DISK
ATA PCMCIA, Files 32768kb
FLASH EPROM
SRAM
SRAM PCMCIA, Prog 192kb
SRAM PCMCIA, Prog 384kb
SRAM PCMCIA, Prog 1024kb, Data 1600kb
SRAM PCMCIA, Prog 2048kb, Data 1856kb
SRAM PCMCIA, Prog 3072kb, Data 2880kb
SRAM PCMCIA, Prog 7168kb, Data 6976kb
SRAM PCMCIA, Prog 768kb, Data 576kb
SRAM Data or Files
SRAM PCMCIA, Data or Files 2048kb
SRAM PCMCIA, Data or Files 4096kb
SRAM PCMCIA, Data or Files 8192kb
6 Add or replace the desired memory.
OK
Cancel
86
Configuring a Modicon Quantum Hot Standby with Unity System
Configuring the Modbus Plus Communication Type
Configuring with
Unity Pro
Configuring the Modbus Plus communication type
Step Action
1 If not opened, open the Local Bus configuration editor.
2 Go to the local bus in the Structural View of the Project Browser.
3 Open the Local Bus editor either by double-clicking on the Local Bus or by selecting the Local Bus and executing right-click Open.
A graphical representation of the local bus appears.
4 Point to the Modbus Plus port, No. 3.
1
CPS
111
00
2
CPU
671
60
CPU
671
60
ACI
030
00
4 5 6 7 8 9 10 11 12 13 14
3
5 Double-click or right-click on the Modbus Plus port.
The Submodule dialog appears. The General tab is default.
1.2 : MBP
MBP
Overview General
Communication Type
DIO Bus
Peer Cop
I/O objects
Please choose a link:
No Link
6 Select one or both Communication Type: z z
DIO bus
Peer Cop
87
Configuring a Modicon Quantum Hot Standby with Unity System
Setting the Invalidate Keypad Option
Overview
Methods for
Selecting the
Invalidate
Keypad Option
The keypad is located on the front panel of the Modicon Quantum Hot Standby with
Unity 140 CPU 671 60 module.
Setting the Invalidate Keypad option can disable the Hot Standby submenu ( PLC
Operations | Hot Standby ). (See
) When the
Invalidate Keypad option is selected, the Hot Standby submenu is read only.
You may choose to prevent access to the Hot Standby control through the keypad z to avoid the possibility of accidental (or malicious) state changing z for security or convenience
There are two methods for selecting/enabling this option:
Method Used
Hot Standby tab
Description
Select the Invalidate Keypad option in the Hot Standby tab using the
Unity Pro software. (See
Using the Hot Standby Tab, p. 85 )
Selecting the Invalidate Keypad option requires that the application program be downloaded to the CPU.
Command Register Set the system bit, %SW60.0 to 1.
Selecting the system bit %SW60.0 must be performed online in the
Primary controller.
Note: By setting the Invalidate Keypad option, the Run/Stop PLC control option on the PLC Operation menu is NOT disabled.
88
Disabling
Options
Configuring a Modicon Quantum Hot Standby with Unity System
Two Hot Standby options/controls are disabled using the front panel keypad z Changing the HSBY mode (Run/Offline) z Application program transfer to/from Standby
Note: CHANGING FROM LEGACY
In the legacy Quantum Hot Standby system, setting command register bit 16 affects both the mode (offline or run) of controllers A and B and affects the state of bit 14 and bit 15 z z
Bit 16 set to 0 z disables (overrides) Command Register bit 14 and bit 15 state z enables key switch state
Bit 16 set to 1 z z enables Command Register bit 14 and bit 15 state disables key switch state
In Unity, z the state/condition of system bit %SW60.0 ONLY disables/enables the Hot
Standby submenu option in the front panel keypad.
z z setting system bit %SW60.0 does NOT affect the state of system bits %SW60.1 and %SW60.2
regardless of the setting for system bit %SW60.0, system bits %SW60.1 and
%SW60.2 control the mode (offline or run) of controllers A and B. (See Setting
the Bits in the Command Register, p. 110 )
89
Configuring a Modicon Quantum Hot Standby with Unity System
Swapping Network Addresses at Switchover
Overview
Handling
Modbus
Addresses at
Switchover
The following material describes handling network addresses at Switchover. A
Modicon Quantum Hot Standby with Unity system can communicate data over different network protocols: z Modbus z z
Modbus Plus
TCP/IP
In a Modicon Quantum Hot Standby with Unity system, the Modbus port addresses are: z Primary: 1-119 z Standby: Offset +128
Maximum address: 247 z
Range 1-247
The Modbus port addresses can be changed using one of two methods: z z
Communication menu in the front panel keypad
Modbus Port tab in the Unity Pro editor
Changing addresses:
Using the Communication menu in the Front Panel Keypad
Change address on either
Primary
1.
Access the front panel keypad of the
Primary.
2.
Go to Communication menu
3.
Go to Serial Port submenu
4.
Select address
5.
Change address
6.
Perform application program transfer
7.
Verify Standby Modbus address is +128.
Standby
1.
Access the front panel keypad of the
Standby.
2.
Go to Communication menu
3.
Go to Serial Port submenu
4.
Select address
5.
Change address
6.
Perform switchover
7.
Ensure Standby switched to Primary
8.
Perform application program transfer
9.
Verify Standby Modbus address is +128
Using the Modbus Port Tab in Unity Pro Editor
To change address, download application program. (See Offline Modification of an
Application Program and Logic Mismatch,
Note: If the Modbus address is changed in the Primary using the front panel keypad, ensure that application program transfer is made to enable the corresponding Modbus switchover in the Standby.
90
Configuring a Modicon Quantum Hot Standby with Unity System
Note: CHANGING FROM LEGACY
In a Modicon Quantum Hot Standby with Unity system only one port is available for
Modbus.
By default address swap at switchover is maintained between the Primary and
Standby Modbus ports. This default condition can be changed using the following two methods: z Using Hot Standby menu in the Unity Pro editor
This choice requires the application program to be downloaded.
Using the Command Register system bit %SW60.8
z
This choice MUST be performed online in the Primary.
Selecting/deselecting address swap at Switchover
Using Hot Standby Menu in Editor
1.
Open Hot Standby menu in Unity Pro
2.
Go to Swap Address at Switchover area
3.
Deselect Modbus Port 1
4.
Verify modifications
5.
Download application program to controller. (See Offline Modification of an
Application Program and Logic Mismatch,
6.
Perform switchover
7.
Ensure Standby switch to Primary
8.
Perform application program transfer
Using the Command Register system bit
%SW60.8
1.
Connect to Primary
2.
Access the Command Register System bit %SW60.8
3.
Set bit to 1
Default is 0
Swap Modbus
Addresses at
Switchover
If controller A is the Primary controller and its Modbus port has an address of 1, then the default addresses for the comparable port on controller B, the Standby, is 129, which is 1 plus the offset of 128.
If controller B becomes the Primary controller as the result of a switchover, its
Modbus port assumes the address of 1, and the comparable port on controller A assumes the address of 129.
No Swap Modbus
Addresses at
Switchover
If controller A is the Primary controller and its Modbus port 1 address is 1, then that port address remains at 1 after the switchover occurs. Likewise, if controller B becomes the Primary controller as a result of a switchover, its Modbus port 1 address is remains at 1.
91
Configuring a Modicon Quantum Hot Standby with Unity System
Important
Information
Note: Important Information
1.
If you change the options, the port addresses are not affected until a switchover occurs.
2.
If NOM modules are used in the configuration, the offset of the Modbus address is +/-32 following the Modbus Plus address switchover.
Handling
Modbus Plus
Addresses at
Switchover
92
In a Modicon Quantum Hot Standby with Unity system, the Modbus Plus port addresses on the Standby controller are offset +/-32 from the comparable ports on the Primary controller.
Modbus Plus address swap behavior at switchover
Default Behavior at Switchover z z
Controller A = Primary
MB+ address = 1
Controller B = Standby
MB+ address = 33 (1 +32)
(+32 = Offset)
Switchover occurs.
z z
Controller A = new Standby
MB+ address = 33 (1 +32)
Controller B = new Primary
MB+ address = 1
Note: Numerical address of both ports (A and B) range: 1 - 64.
If Primary address = 50, corresponding Standby = 18 (50 - 32)
The Modbus Plus address of the controllers can be changed using the front panel keypad: Communication | Modbus Plus | Modify Address
Modbus Plus address swap behavior when addressed is changed
Forced Behavior at Switchover z z
Controller A = Primary
MB+ address = 1
Controller B = Standby
MB+ address = 33 (1 +32)
(+32 = Offset)
Change address of Primary = 5.
z z
Controller A = Primary
MB+ address = 5
Controller B = Standby
MB+ address = 33
Perform Application Program Transfer.
Configuring a Modicon Quantum Hot Standby with Unity System
Forced Behavior at Switchover z z
Controller A = Primary
MB+ address = 5
Controller B = Standby
MB+ address = 37 (5 +32)
Force switchover.
z z
Controller A = new Standby
MB+ address = 37 (5 +32)
Controller B = new Primary
MB+ address = 5
If he Modbus Plus address is modified, perform an Application Program Transfer. (See
Transferring an Application Program with Unity Pro, p. 159 ) Failure to perform a transfer
creates a different offset address in the Standby.
Note: SWAPPING ADDRESSES
At switchover, the Modicon Quantum Hot Standby with Unity system and NOMs swap Modbus Plus addresses almost instantaneously (within one or two milliseconds). This almost instantaneous switchover means that host devices which are polling the controller should be talking to the Primary controller and that the network should have minimal network interruption during switchover.
Note: EXEC UPGRADE USING OSLOADER
When using Modbus Plus communication and OSLoader, only address 1 is valid.
(See
Executing the EXEC Upgrade Procedure, p. 139 )
93
Configuring a Modicon Quantum Hot Standby with Unity System
Handling TCP/IP
Addresses at
Switchover
When used in a Modicon Quantum Hot Standby with Unity system, the Modicon
Quantum Ethernet TCP/IP network option modules NOE 771 01 and 11 support address swapping at switchover. The swapping of IP addresses behaves much like the address swap of the Modbus Plus ports, except that the offset is 1 instead of 32.
At switchover, the modules exchange their IP addresses. NOE 771 address swapping occurs automatically and can not be controlled by options selected in any of the tabs of the editor or controlled by turning ON/OFF any of the bits in the command register.
All standard rules apply to IP addressing with the additional restriction that the IP address cannot be greater than 253 or the broadcast address minus 2. Also, no other device should be assigned the configured IP +1 address.
Note: NOE 771 01 and 11 ADDRESS SWAP z NOE 771 01 and 11 are the only Ethernet option modules that support the IP address swap in Modicon Quantum Hot Standby with Unity system V2.0. z z
NOE 77101 and 11 modules must be configured in the same slot of the Primary and Standby backplanes.
NOE 771 01, 11 requires minimum firmware revision 2.0 or higher.
94
5.2
At a Glance
Purpose
Configuring a Modicon Quantum Hot Standby with Unity System
Configuring a NOE with Unity Pro
What's in this
Section?
This material describes configuring a NOE, a Quantum Ethernet module, using Unity
Pro. For a complete description of all models of the NOE, see the Quantum NOE
771 xx Ethernet Modules User Guide, 840 USE 116 00 .
This section contains the following topics:
Topic
Overview of Modicon Quantum Hot Standby with Unity Solution for NOEs
NOE Operating Modes and Modicon Quantum Hot Standby with Unity
IP Address Assignment
Address Swap Times
Network Effects of Modicon Quantum Hot Standby with Unity Solution
Page
95
Configuring a Modicon Quantum Hot Standby with Unity System
Overview of Modicon Quantum Hot Standby with Unity Solution for NOEs
Please Note The Modicon Quantum Hot Standby with Unity system supports up to six NOE 771
Ethernet adapters on bus controllers.
Description of the Hot Standby
Solution
The NOE Hot Standby allows automatic IP Address swap. Both controllers are configured identically. One controller is the Primary NOE; the other controller, the
Secondary NOE. In case of a failure, the controllers switchover and the system recovers.
The NOEs coordinate the swapping of IP addresses. After closing both the client and the server connections, each NOE sends a swap UDP message to its peer
NOE. The sending NOE then waits a specified timeout (500 ms) for the peer swap of UDP messages. Either after receiving the messages or after a timeout, the NOE changes its IP address.
Note: NOEs must communicate with each other in order to swap IP Addresses.
Schneider Electric recommends that you connect the primary and Secondary
NOEs to the same switch because z z
Communication failures between the NOEs increases the time to swap
Connecting two NOEs to the same switch, minimizes the probability of a communication failure
Note: Schneider Electric recommends that a switch (not a hub) is used to connect the NOEs to each other or to the network. Schneider Electric offers switches; please contact a local sales office for more information.
The NOE waits for either a change in the controller’s Hot Standby state or the swap of UDP messages. Then the NOE performs one of two Hot Standby actions.
If the NOE:
1.
Detects that the new Hot Standby state is either primary or standby:
The NOE changes the IP address
2.
Receives a swap UDP message:
The NOE transmits a Swap UDP message and swaps the IP address
All client/server services (I/O Scanner, Global Data, Messaging, FTP, SNMP, and
HTTP) continue to run after the switchover from the old to the new Primary NOE.
Note: Failure of an NOE module is not a condition for the primary system to leave the primary state.
96
Configuring a Modicon Quantum Hot Standby with Unity System
Hot Standby and
NOE Module
Functionality
The NOE 771 family provides different Ethernet services. Some services are enabled or disabled in a Modicon Quantum Hot Standby with Unity system. The following table shows which services are enabled and disabled.
Service
I/O Scanning
Global Data
Modbus Messaging
FTP/TFTP
SNMP
HTTP Server
DHCP
NOE 771 x1
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Disabled
Note: Only the 140 NOE 771 01 or 140 NOE 771 11 (TCP/IP Ethernet Modules) support a Modicon Quantum Hot Standby with Unity V2.0 system.
97
Configuring a Modicon Quantum Hot Standby with Unity System
NOE Operating Modes and Modicon Quantum Hot Standby with Unity
The NOE Modes The NOE modes are z Primary Mode z
The Hot Standby state is primary, and all client/server services are active.
Secondary Mode
The Hot Standby state is standby, and all server services are active except
DHCP.
z Standalone Mode
Occurs when NOE is in a nonredundant system, or if the HE CPU module is not present or is not healthy.
Offline Mode z
CPU is stopped.
CPU module is in Offline mode.
The Modicon Quantum Hot Standby with Unity and the NOE operating modes are synchronized by the conditions described in the following table.
HE CPU Module Status
Present and Healthy
Present and Healthy
Present and Healthy
Present and Healthy
Not present or unhealthy
HSBY State
Primary
Standby
Offline
Unassigned
N/A
NOE Operating Mode
Primary
Secondary
Offline
Standalone
Standalone
Any one of four events will affect the NOE operating mode. These four events occur when the NOE is powered-up, when an NOE executes a Hot Standby switchover, when an NOE goes to offline mode, or when a new application is downloaded to the
NOE.
98
Configuring a Modicon Quantum Hot Standby with Unity System
Power-Up and IP
Address
Assignment
An NOE obtains its IP Address assignment at power-up as follows:
If the HSBY state is ...
Unassigned
Primary
Secondary
Unassigned to Offline
Then the IP Address assigned is ...
Configured IP Address
Configured IP Address
Configured IP Address + 1
See the Offline Mode at Power-up Sequence table following
If two NOEs power-up simultaneously, a "resolution algorithm" determines the
Primary NOE, and after determining the Primary NOE, the "resolution algorithm" assigns the configured IP Address to the Primary NOE and then assigns the configured IP Address + 1 to the Secondary NOE.
Offline Mode at Power-up Sequence table:
Offline Mode at Power-up Sequence
Both controller A and controller B power-up a the same time
Result
Controller A powers-up before controller B z IP Address of controller A is configured IP
Address z IP Address of controller B is the configured
IP Address + 1
The resolution algorithm will assign controller A the configured IP address and will assign controller B the configured IP address + 1.
The NOE performs a "duplicate IP" test by issuing an ARP request to the configured
IP Address. If a response is received within 3 seconds, the IP Address remains at the Default IP and blinks a diagnostic code.
If no IP configuration exists, the NOE remains in standalone mode, and the IP
Address must be obtained from either a BOOTP server or from a MAC address.
99
Configuring a Modicon Quantum Hot Standby with Unity System
Power-Up and
Ethernet
Services
The following table shows how the status of an NOE service is affected by the
Modicon Quantum Hot Standby with Unity HSBY state.
HSBY State Status of NOE Services
Client Services Client/
Server
Services
I/O Scanner Global Data Modbus
Messaging
Unassigned Run
Primary Run
Secondary
Offline
Stop
Stop
Run
Run
Stop
Stop
Run
Run
Run
Run
Server Services
FTP
Run
Run
Run
Run
SNMP
Run
Run
Run
Run
HTTP
Run
Run
Run
Run
100
Hot Standby
Switchover
Configuring a Modicon Quantum Hot Standby with Unity System
The following steps describe how NOEs coordinate the Hot Standby switchover.
Step
1
2
3
4
5
6
7
8
9
10
Action
NOE A (installed in a HSBY rack) detects that its local controller changed from
Primary to Offline.
NOE A changes its HSBY state from Primary to Offline with the same Ethernet services running, starts its watch-dog timer (with 500 ms timeout setting), and expects from its peer NOE a UDP request to swap the IP Address.
NOE B (installed in peer HSBY rack) detects that its local controller changed state from Secondary to Primary.
NOE B stops all Ethernet services, sends a UDP request to its peer NOE (NOE
A) for the synchronization of the IP Address swap, starts its watch-dog timer
(with 500 ms timeout setting), and then waits for an UDP response from its peer
NOE.
Once NOE A receives the UDP request from NOE B (or after its watch-dog timer times out), it stops all Ethernet services, sends a UDP response to NOE B (no
UDP response is sent to NOE B for watch-dog timeout case), swaps IP Address as Secondary, and starts Secondary services.
As soon as NOE B receives the UDP response from NOE A (or after its watchdog timer times out), it swaps IP Addresses and starts Ethernet services as
Primary.
After NOE A senses that its local controller changes state from Offline to
Standby, it changes to Secondary accordingly.
The Secondary NOE now becomes the Primary NOE.
Primary NOE opens all client connections and listens for all server connections and re-establishes those connections.
Simultaneously, Secondary NOE listens for all server connections and reestablishes those connections.
Going to Offline When either the CPU stops or the Hot Standby state goes to offline mode, two events occur:
1.
NOE mode goes to Offline
2.
NOE uses the IP Address of the present configuration
IP Address Assignment and Going Offline
HSBY State
Primary to Offline
Standby to Offline
IP Address Assigned Is ...
Configured IP Address, if other controller does not go to
Primary
Configured IP Address + 1
101
Configuring a Modicon Quantum Hot Standby with Unity System
IP Address Assignment
Configuring the
NOE
The NOE can be configured to work in conjunction with the Modicon Quantum Hot
Standby with Unity controller. Since the Primary and Secondary controllers must have an identical configuration, the configured IP Addresses will be the same. The
NOE’s IP Address is either the configured IP Address or the configured IP Address
+1. The IP Address is determined by the current local Hot Standby state.
In the Offline state, the IP Address is determined by whether or not the other controller is in transition to the Primary state.
Note: For a Modicon Quantum Hot Standby with Unity system, the two IP
Addresses will be consecutive.
The following table shows the IP Address assignments.
Hot Standby State
Primary
Standby
Transition from Primary to Offline
Transition from Standby to Offline
IP Address
Configured IP Address
Configured IP Address + 1
Configured IP Address, if peer controller does not go to Primary
Configured IP Address + 1
Note: Offline - Results depend on whether or not the other controller is detected as in transition into the primary state. If Current IP is the configured IP Address, then change the IP Address to the configured IP Address + 1.
IP Address
Restriction
Note: Configuring NOE
Do not use either broadcast IP Address or broadcast IP Address - 2 to configure a
NOE.
102
IP Address
Transparency
Configuring a Modicon Quantum Hot Standby with Unity System
For continued Ethernet communication, the new Primary NOE must have the same
IP Address as the former Primary NOE. The IP Address in the Secondary NOE (an
NOE in the secondary state) is IP Address + 1.
The NOEs integrated into the Modicon Quantum Hot Standby with Unity configuration coordinate this swapping IP Address with the management of Ethernet services used.
Note: Do not use the address IP + 1. For a Modicon Quantum Hot Standby with
Unity system, do not use consecutive addresses of the configured IP Address. If you configure the last IP Address (255), NOE returns diagnostic code "Bad IP configuration".
103
Configuring a Modicon Quantum Hot Standby with Unity System
Address Swap Times
Description The following table details what the "time for an Address swap" comprises, such as the time to close connections, time to swap IP addresses, or time to establish connections.
The following table shows the swap time for each of the Ethernet services.
Service
Swap IP Addresses
I/O Scanning
Global Data
Client Messaging
Server Messaging
FTP/TFTP Server
SNMP
HTTP Server
Typical Swap Time
6 ms
Maximum Swap Time
500 ms
1 initial cycle of I/O Scanning 500 ms + 1 initial cycle of I/O scanning
500 ms + 1 CPU scan For swap times, please see the 840USE11600, Quantum
NOE 771 xx Ethernet
Modules User Guide
1 CPU scan
1 CPU scan + the time of the client reestablishment connection
The time of the client reestablishment connection
1 CPU scan
The time of the client reestablishment connection
500 ms + 1 CPU scan
500 ms + the time of the client reestablishment connection
500 ms + the time of the client reestablishment connection
500 ms + 1 CPU scan
500 ms + the time of the client reestablishment connection
104
Configuring a Modicon Quantum Hot Standby with Unity System
Network Effects of Modicon Quantum Hot Standby with Unity Solution
Overview The Modicon Quantum Hot Standby with Unity solution is a powerful feature of
NOEs, a feature that increases the reliability of your installation. Hot Standby uses a network, and using the Hot Standby feature over a network can affect the behavior of z z z z
Browsers
Remote and Local clients
I/O Scanning service
Global Data service z FTP/TFTP server
The following are factors you may encounter while using the Modicon Quantum Hot
Standby with Unity solution.
Browsers
Remote Clients
Local Clients
Note: In Modicon Quantum Hot Standby with Unity configuration the NOE’s I/O scanner is enabled.
If a browser requests a page and during the process of downloading that page an IP
Address swap occurs, the browser will either hang or time out. Click the Refresh or
Reload button.
Hot Standby swaps affect remote clients.
An NOE will reset under the following conditions: z Remote Connection Request during Hot Standby Swap
If a remote client establishes a TCP/IP connection during a Hot Standby swap, z the server closes the connection using a TCP/IP reset.
Hot Standby Swap during Remote Connection Request
If a remote client makes a connection request and a Hot Standby swap occurs during the connection request, the sever rejects the TCP/IP connection by z sending a reset.
Outstanding Requests
If there is an outstanding request, the NOE will not respond to the request, but the NOE will reset the connection.
The NOE will do a Modbus logout if any connection has logged in.
During a swap, the NOE will reset all client connections using a TCP/IP reset.
105
Configuring a Modicon Quantum Hot Standby with Unity System
I/O Scanning
Service
The I/O Scanning provides the repetitive exchange of data with remote TCP/IP nodes I/O devices. While the PLC is running the Primary NOE sends Modbus Read/
Write, read or write request to remote I/O devices, and transfer data to and from the
PLC memory. In the secondary controller, the I/O scanning service is stopped.
When the Hot Standby swap occurs, the Primary NOE closes all connections with I/
O devices by sending a TCP/IP reset. The I/O scanning service in this NOE is standby.
After the swap, the new Primary NOE re-establishes the connection with each I/O devices. It restarts the repetitive exchange of data with these re-connections.
The NOE 771 01 and 11 provides the I/O scanning feature. Configure using either z z
Unity Pro software
Internal I/O Scanner Web page
Using either method, the configuration and transfer of data between network addresses can be done without using the MSTR/IEC function block.
Note: I/O SCANNING AND SWITCHOVER WITH CRITICAL APPLICATIONS
Account for the following Ethernet I/O scanning considerations during a switchover.
z z
If MSTR/IEC function block is used for TCP/IP, only some of the Op Code will be used. Therefore, the block will not complete its transaction and returns error code 0x8000.
While the NOE is in the process of performing the transaction, a new MSTR/IEC z function block may become active.
The output states of the scanned I/Os will follow the state defined in the last value option configured in the I/O scanning table of the NOE module (in Unity
Pro software).
These two states are either
1.
set to 0
2.
Hold last
With the above considerations, Schneider Electric recommends using switchover with Ethernet I/O scanning for less critical applications.
106
Configuring a Modicon Quantum Hot Standby with Unity System
Global Data
(Publish/
Subscribe)
Service
The Hot Standby NOE is one station within a distribution group. Distribution groups exchange application variables. Exchanging application variables allows the system to coordinate all the stations in the distribution group. Every station publishes local application variable in a distribution group for all other stations and can subscribe to remote application variables independent of the location of the producer.
The communication port has only one multicast address.
In this network service, the Modicon Quantum Hot Standby with Unity controllers are viewed like only one station. The Primary NOE publishes the Hot Standby application variables and receives the subscription variables. The Secondary NOE global data service is in a stopped state.
When the Hot Standby swap occurs, the Primary NOE stops the Global Data service. The NOE does not publish the local variable during a swap. And after the swap, the new Primary NOE starts to publish application variables and to receive the subscription variables.
FTP/TFTP Server The File Transfer Protocol/Trivial File Transfer Protocol (FTP/TFTP) server is available as soon as the module receives an IP address. Any FTP/TFTP client can logon to the module. Access requires the correct user name and password. Modicon
Quantum Hot Standby with Unity allows only one active FTP/TFTP client session per NOE module.
When the Hot Standby swap occurs, the Primary and Secondary NOEs close the
FTP/TFTP connection. If a user sends an FTP/TFTP request during the swap, the communication is closed.
Whenever you re-open communication, you must re-enter a user name and a password.
107
Configuring a Modicon Quantum Hot Standby with Unity System
5.3
Configuring Registers with Unity Pro
At a Glance
Purpose
What's in this
Section?
This material describes configuring a Modicon Quantum Hot Standby with Unity system by selecting options that affect the registers. You may want to use this method if your system has specific configuration needs.
This section contains the following topics:
Topic
Understanding the Non-Transfer Area, Transferring State RAM, and Reverse
Transfer Words
Understanding the Unity Command Register
Understanding the Unity Status Register
Transferring User Data
Using Initialized Data
Synchronizing Time-of-Day Clocks
Page
108
Configuring a Modicon Quantum Hot Standby with Unity System
Understanding the Non-Transfer Area, Transferring State RAM, and Reverse
Transfer Words
Designating a
Non-Transfer
Area
Using the Hot Standby tab of the editor dialog, you may designate a block of %MW words as a Non-Transfer area.
Step
1
2
3
Action
Ensure that the Hot Standby tab is selected.
If you want to review the process for starting Unity Pro and opening the editor dialog, please see
Accessing the Base Configuration, p. 73 .
Enter the starting address in the system word field, %MW.
The field is located in the Non-Transfer Area of the Hot Standby tab.
Enter the number of contiguous registers in the Length: field.
The field is located in the Non-Transfer Area of the Hot Standby tab.
Non-Transfer
Area of State
RAM
Transferring
Data to the
Primary
The designated registers will be ignored when state RAM values are transferred from the Primary controller to the Standby. Placing registers in the Non-Transfer
Area is one way to reduce scan time.
Note: With the new hardware design of the Modicon Quantum Hot Standby with
Unity 140 CPU 671 60s, the scan time optimization provided by the Non-Transfer area may be very low.
A pair of system words,%SW62 and %SW63, are dedicated to transfer data from the
Standby controller to the Primary.
These system words can be used by the application program (in the first section) to register diagnostic information.
The data coming from the Standby are transferred at each scan and are available to the Primary.
109
Configuring a Modicon Quantum Hot Standby with Unity System
Understanding the Unity Command Register
Setting the Bits in the Command
Register
The Command Register defines the operating parameters of a Hot Standby application for both the Primary and Standby and is located at system word %SW60.
At each scan, the Command Register is replicated and transfers data from the
Primary to the Standby. Transfer occurs only from Primary to Standby. Any changes made to the Command Register on the Standby will have no effect because the values transferred from the Primary overwrite the values in the Standby.
The following illustration identifies the operating options provided by the Command
Register.
Disables LCD Invalidate Keypad = 0
Enables LCD Invalidate Keypad = 1
Sets Controller A to OFFLINE mode = 0
Sets Controller A to RUN mode = 1
Sets Controller B to OFFLINE mode = 0
Sets Controller B to RUN mode = 1
Forces Standby offline if there is a logic mismatch = 0
Does not force Standby offline if there is a logic mismatch = 1
Allows exec upgrade only after application stops = 0
Allows exec upgrade without stopping application = 1
MSB
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
LSB
0 = No application program transfer
1 = Application program transfer requested
0 = Swaps Modbus port 1 address during switchover
1 = Does not swap Modbus port 1 address on switchover
System Word
%SW60.0
Invalidate Keypad is an option that allows a controller to accept or refuse commands from the Hot Standby submenu in the front panel keypad.
z %SW60.0 = 1
Invalidate Keypad enabled.
z
The Modicon Quantum Hot Standby with Unity system refuses all changes from the Hot Standby submenu in the front panel keypad.
%SW60.0 = 0
Invalidate Keypad disabled.
The Modicon Quantum Hot Standby with Unity system accepts all changes from the Hot Standby submenu in the front panel keypad.
(See
Setting the Invalidate Keypad Option, p. 88 )
110
System Word
%SW60.1
System Word
%SW60.2
System Word
%SW60.3
System Word
%SW60.4
Configuring a Modicon Quantum Hot Standby with Unity System
Controller A OFFLINE/RUN mode z %SW60.1 = 1 z
Controller A goes to Run mode
%SW60.1 = 0
Controller A goes to Offline mode
Controller B OFFLINE/RUN mode z %SW60.2 = 1 z
Controller B goes to Run mode
%SW60.2 = 0
Controller B goes to Offline mode
Logic mismatch z %SW60.3 = 0
If a logic mismatch is detected, Standby forced to Offline mode.
%SW60.3 = 1 z
Standby operates normally even if a mismatch occurs.
(See
Handling Logic Mismatch with Unity Pro, p. 141
)
EXEC upgrade z %SW60.4 = 1
Allows the executive to be upgraded on the Standby and the Primary continues z to control the process.
%SW60.4 = 0
Allows the executive to be upgraded and to stop the Primary’s control of the process.
Upgrading allows z a Hot Standby system to operate with different versions of the OS running on the z
Primary and Standby upgrades without shutting down the process
To perform the executive upgrade, the Standby must be stopped. When started again, the Standby operates as a valid Standby. (See Enabling EXEC Upgrade with
111
Configuring a Modicon Quantum Hot Standby with Unity System
System Word
%SW60.5
Commands Standby to initiate an application transfer.
z z
%SW60.5 = 1 means Standby requests an application program transfer from
Primary
%SW60.5 = 0 is default and no transfer occurs
Note: %SW60.5 is a Monitor Bit
%SW60.5 monitors an action. Once the action occurs, %SW60.5 returns to the default, which is zero (0).
System Word
%SW60.8
Swap Modbus port z %SW60.8 = 1
Swaps Modbus addresses on port 1when a switchover occurs.
Note: In a Modicon Quantum Hot Standby with Unity system only Modbus port 1 is available for use.
112
Configuring a Modicon Quantum Hot Standby with Unity System
Understanding the Unity Status Register
Bits in the Hot
Standby Status
Register
The Hot Standby Status Register is a readable register located at system word
%SW61 and is used to monitor the current machine status of the Primary and
Standby.
Both the Primary and the Standby/Offline have their own copy of the Status register.
The Status register is not transferred from Primary to Standby. Each PLC must maintain its local Status Register based on the regular communication between the two controllers.
The following illustration identifies the operating options provided by the Status
Register.
This PLC in OFFLINE mode = 0 1
This PLC running in primary mode =1 0
This PLC running in standby mode = 1 1
Other PLC in OFFLINE mode = 0 1
Other PLC running in primary mode =1 0
Other PLC running in standby mode = 1 1
PLCs have matching logic = 0
PLCs do not have matching logic = 1
This PLC’s switch set to A = 0
This PLC’s switch set to B = 1
MSB 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 LSB
0 = Unlocated Variables being transferred Primary to Standby
1 = Unlocated Variables not being transferred Primary to Standby
0 = The hot standby has not been activated
1 = The hot standby is active
113
Configuring a Modicon Quantum Hot Standby with Unity System
System Words
%SW61.0 to
%SW61.3
System Word
%SW61.4
System Word
%SW61.5
These four bits display the states of the local and remote Hot Standby controllers.
Status of local PLC z z
%SW61.1 = 0 and %SW61.0 = 1means local PLC is in OFFLINE mode
%SW61.1 = 1 and %SW61.0 = 0 means local PLC is running in Primary mode z %SW61.1 = 1 and %SW61.0 = 1 means local; PLC is running in Standby mode
Status of remote PLC z z z
%SW61.3 = 0 and %SW61.2 = 1means remote PLC is in OFFLINE mode
%SW61.3 = 1 and %SW61.2 = 0 means remote PLC is running in Primary mode
%SW61.3 = 1 and %SW61.2 = 1 means remote PLC is running in Standby mode
%SW61.4 is set = 1 whenever a logic mismatch is detected between the Primary and Standby controllers.
%SW61.4 depends on %SW60.3 (Command Register) set = 1.
%SW61.5 identifies the Order reported by the Copro at start time.
The order depends on the range of the MAC addresses.
z z
If the A/B designation is A, then bit 5 will be set = 0.
If the A/B designation is B, then bit 5 will be set = 1.
Note: On controller LCD displays z z
A
B
System Word
%SW61.14
System Word
%SW61.15
If %SW61.14 is set = 1, the setting indicates that a logic mismatch has been detected, which prevents Unlocated Variables to be transferred from the Primary to
Standby.
If %SW 61.15 is set = 1, the setting indicates that the Copro device is set up correctly and working.
114
Configuring a Modicon Quantum Hot Standby with Unity System
Transferring User Data
General
Variables,
Instances, Bits,
Words
At end of scan in a redundant system the Primary must send its data to the Standby in order to keep in ready to assume the role of Primary if the need arises.
The user data that will be transferred includes: z z
Located variables (in state RAM)
All unlocated variables z z
All instances of DFB and EFB data
SFC states z System Bits and Words
115
Configuring a Modicon Quantum Hot Standby with Unity System
Using Initialized Data
Loading at Coldstart Time
The Modicon Quantum Hot Standby with Unity 140 CPU 671 60 supports initialized data.
Initialized data allows you to specify initial values for the data that are to be loaded at cold-start time. Declare the variables before a cold start.
Updating Online In addition to declaring values before a cold start, you can update the initial values online.
Updating the initial values online creates a mismatch situation in a redundant system.
Handling
Problems at
Switchover
Updating the initial values online presents a problem: if a switchover occurs to the non-updated PLC, then you execute a cold-start, the older initial values will be used.
Note: WINDOW OF TIME
Pay attention to the fact that there is a window of time during which a mismatch can occur. Mismatches may cause inconsistent operations.
Solving
Mismatch
Problems
However, logic mismatches cause the same problems. Thus, value mismatches will be treated in the same way as logic mismatches. Value mismatches give the same indications and the same update requirements.
116
Configuring a Modicon Quantum Hot Standby with Unity System
Synchronizing Time-of-Day Clocks
Setting the Timeof-Day Clocks in the Primary and
Standby
Controllers
In a Modicon Quantum Hot Standby with Unity system, the Primary and Standby controllers have their own Time-of-Day clocks, which are not implicitly synchronized.
If the clocks are not synchronized, then at switchover, the Time-of-Day would change by the difference between the two clocks. Non synchronization of the clocks could cause problems if you are controlling a time critical application.
117
Configuring a Modicon Quantum Hot Standby with Unity System
118
Maintaining a Modicon Quantum
Hot Standby with Unity System
6
Introduction
Overview
What's in this
Chapter?
This chapter provides information about maintaining a Modicon Quantum Hot
Standby with Unity system.
This chapter contains the following topics:
Topic
Verifying the Health of a Modicon Quantum Hot Standby with Unity System
Detecting and Diagnosing Failures in a Modicon Quantum Hot Standby with
Unity System
Detecting Primary Controller, Copro, and RIO Head Failures
Detecting Standby Controller, Copro, and RIO Head Failures
Detecting High-Speed Data Link (HDSL) Failures
Detecting Remote I/O (RIO) Link Failures
Checking for Identical Application Programs—Checksum
Replacing a Faulty Module
Troubleshooting the Primary Controller
Troubleshooting the Standby Controller
Page
119
Maintaining a Modicon Quantum Hot Standby with Unity System
Verifying the Health of a Modicon Quantum Hot Standby with Unity System
Generating and
Sending Health
Messages
Performing
Automatic
Confidence
Tests
Conducting
Startup Tests
The Modicon Quantum Hot Standby with Unity modules exchange a health message approximately every 10 ms.
If the Primary has an error, the Standby is notified and assumes the Primary role.
If the Standby has an error, the Primary continues to operate as a standalone.The
RIO head processors periodically verify communication with one another.
The Primary sends a health message to the Standby either
1.
every 10 milliseconds when no other data is being sent on the high speed Copro link
2.
every 5 milliseconds if no communication is required with any drop on RIO link.
If the Standby never receives any message on either link, the Standby will try to determine the cause of the failure and assumes control if necessary.
If the Primary does not receive a valid response from the Standby, the Primary will operate as if there was no back up available as if the Primary were a standalone.
The system automatically performs two kinds of confidence tests on the Modicon
Quantum Hot Standby with Unity Copro: z z
Startup tests
Run time tests
Startup confidence testing on the Modicon Quantum Hot Standby with Unity Copro attempt to detect hardware errors in the module before the application is allowed to run.
If the module fails any of its tests, it will remain offline and will not communicate with the other Modicon Quantum Hot Standby with Unity module.
Conducting Run
Time Tests
Run time tests are performed whenever the Copro is in the operational state. Run time tests are executed in small slices to prevent delays in scan time.
If the module fails any of its tests, the module remains offline and will not communicate with the other module.
120
Maintaining a Modicon Quantum Hot Standby with Unity System
Detecting and Diagnosing Failures in a Modicon Quantum Hot Standby with
Unity System
Important
Information
Please note.
If...
Component of Primary fails
Component of Standby fails
Fiber optic cable link fails
Then ...
Control shifts to Standby
Standby goes offline
Standby goes offline
Understanding
Health Messages
The Primary sends a health message to the Standby every 10 milliseconds.
If ...
No communication is required with any drop on RIO link
All systems OK
Then Primary Sends Health Message ...
every 5 milliseconds every scan
Exceptions
If ...
Standby never receives any message on either link
Primary does not receive a valid response from the Standby
Then ...
1.
Standby determines cause of failure
2.
Standby assumes control
Primary operates as if
1.
no back up available
2.
Primary were a standalone
Standalone = 1) no working Copro 2) no Hot
Standby Functionality
Finding
Diagnostic
Information with
Unity Pro
Errors and switchovers are logged in the diagnostic buffer. To view the log,
Step
1
Action
Select Tools → Diagnostic Viewer from the main menu.
121
Maintaining a Modicon Quantum Hot Standby with Unity System
Finding More
Information in this Manual
Refer to the following sections
Type of failure
Primary controller
Primary Copro
Primary RIO head
Standby controller
Standby Copro
Standby RIO head
High speed data link failures
Remote I/O link
Application program checksum failures
Refer to section
Detecting Primary Controller, Copro, and
Detecting Standby Controller, Copro, and
Detecting High-Speed Data Link (HDSL)
Detecting Remote I/O (RIO) Link Failures,
Checking for Identical Application
122
Maintaining a Modicon Quantum Hot Standby with Unity System
Detecting Primary Controller, Copro, and RIO Head Failures
Understanding
CPU to Copro
Communication
Facts
1
2
3
4
On every scan, CPU communicates with Copro.
Main CPU executes the Hot Standby control at the start of the scan, the main CPU asks the Copro to service its requests.
CPU reports any errors detected.
If Primary Copro fails, Primary Controller operates as a standalone.
Standalone = 1) no working Copro 2) no Hot Standby functionality
Failure Detection between Two
Controllers
If an error occurs in either one of two controllers,
Situation
Controller with error
Controller without error
Response
Reports error to other controller by sending a message through either
1.
high speed Copro transfer link
2.
RIO link
Detects error from a timeout which occurs because of no activity on link
Note: Primary maintains continuous activity on link, which ensures Standby can detect an error as soon as possible.
Failure Detection within
One CPU —
Hard Errors
Facts
1
2
RAM failure is a hard error.
Copro detects hard errors.
Detecting failures:
If ...
Hard error occurs
Then ...
1.
Copro sends a take control command to the Standby
2.
Primary Copro stops because of an interface error
123
Maintaining a Modicon Quantum Hot Standby with Unity System
Failure Detection in Either Copro
Detecting failures
If ...
Primary Copro reports any error
Primary Copro does not respond within
5 milliseconds
Primary Copro sends a take control command to the other Copro
Standby copro experiences an error
Then ...
1.
Primary controller acknowledges the error
2.
Primary controller attempts to transfer control to the other controller by sending a take control command to the Standby through the
RIO link
1.
Primary controller acknowledges the error
2.
Primary controller attempts to transfer control to the other controller by sending a take control command to the Standby through the
RIO link
1.
Primary Copro relinquishes control
2.
Primary Copro does not expect any response
1.
Standby controller reports the error by sending a No Standby message
2.
Standby controller goes offline
Failure Detection by an RIO Head
Table with two columns
If ... RIO Head
Responds
Then ... Primary Controller
Releases control and the Standby station becomes a Standalone.
Standalone = 1) no working Copro 2) no Hot Standby functionality
Does NOT respond Continues to scan the I/O.
Understanding
RIO Head Failure
If the RIO Head fails,
3
4
1
2
5
Main CPU times out when it fails to communicate with the RIO Head.
Main CPU stops.
Main CPU reports RIO failure to log.
Main CPU reports RIO failure error to the Copro.
Copro goes offline.
124
Maintaining a Modicon Quantum Hot Standby with Unity System
Detecting Standby Controller, Copro, and RIO Head Failures
Standby CPU
Failure
When Standby CPU fails,
Stage
1
2
3
Description
The Standby CPU reports errors to the Standby Copro.
The Standby Copro sends a No Standby message to the Primary Copro.
The Standby CPU and the standby copro go offline.
Standby Copro
Failure
When Standby Copro fails,
Stage
1
2
3
4
Description
When the Primary CPU communicates with the Standby, the Standby Copro reports its error to the Primary.
The Primary requests the Copro to go offline.
The Standby Copro will also report its error to the Primary Copro by sending a
No Standby message.
Standby goes offline.
Standby RIO
Head Failure
When the Remote IO Head fails,
Step
1
2
3
4
Description
The CPU stops and reports a RIO failure.
The CPU reports the error to the Copro
The Copro sends a No Standby command to the Primary.
The Standby goes offline.
125
Maintaining a Modicon Quantum Hot Standby with Unity System
Detecting High-Speed Data Link (HDSL) Failures
Important
Information
Facts
1
2
3
High-speed data link connects the two Copros.
Using the high-speed data link, the Primary controller communicates with the
Standby every 10 milliseconds.
Primary sends either
1.
data message
2.
health message
Note: If both the Primary and Standby do not hear from each other, either station can detect a high speed data link failure.
126
Maintaining a Modicon Quantum Hot Standby with Unity System
Standby Detects a Failure
At first,
Step Action
1 Standby does not hear from the
Primary on the high-speed data link
Result
1.
Standby requests the Primary CPU to monitor the RIO link
2.
Primary CPU sends a request to the RIO
Head
When the RIO Head receives the request,
If ...
RIO Head finds the
RIO link not active
RIO Head finds the
RIO link is active
Then ...
1.
RIO Head assumes that the Primary must be down
2.
Standby assumes control
Message received from Primary CPU must be either
1.
health message
Messages are sent every 5 milliseconds from Primary RIO Head to
Standby RIO Head.
2.
I/O transaction data message
Messages are sent from the Primary RIO Head to the I/O drops at the request of the controller.
Facts about the I/O
1
2
3
If the message is an I/O transaction, the RIO Head
1.
concludes the failure occurred on the high-speed data link
2.
informs the Primary controller to go to offline
If you never configure an I/O drop, the failure on the high-speed data link could cause the Standby to assume control since the Standby RIO head will never receive any I/O transaction message.
After any CPU fails,
1.
RIO Head will not perform drop communication
2.
RIO Head sends only health messages
127
Maintaining a Modicon Quantum Hot Standby with Unity System
Standby
Assumes
Control
The Standby becomes Primary
Step
1
2
3
4
Action Result
After the Primary controller goes offline, A health message from the Standby controller is the only message received by the Standby RIO Head.
Standby controller listens to the highspeed data link for one scan.
If Standby controller hears nothing, Standby knows that the failure must be on both the Primary Copro and Primary
CPU.
Standby assumes control.
128
Maintaining a Modicon Quantum Hot Standby with Unity System
Detecting Remote I/O (RIO) Link Failures
Important
Information
Facts
1
2
3
4
Remote I/O (RIO) Link connects the two RIO Heads.
Primary RIO Head performs a health check on the RIO link by sending health messages.
Primary RIO Head sends a health message every 5 milliseconds.
Unlike the health communication check performed on the Copro link, the Primary
Copro does not wait for a response from the Standby Copro. Instead the Primary
Copro expects a reply every second. Expecting a reply every second minimizes the impact on the Primary's performance.
Standby
Controller and
Messages
How the Standby handles messages depends on:
If Standby ...
Never Responds to any message
Never Receives a message from the Primary
Then ...
Primary assumes that the
Standby RIO Head failed.
Standby assumes failure may be in the RIO link.
Action
Standby continues to control the drops.
Standby cannot assume control.
129
Maintaining a Modicon Quantum Hot Standby with Unity System
Standby
Monitors RIO and
Copro Links
To start the process,
Step Action
1 Standby RIO Head sends a request to the Primary RIO
Head.
2 Standby requests that the Main
CPU monitor the Copro link.
Result
Confirm whether Primary RIO
1.
Head failed or
2.
link failed
Main CPU passes this request to Copro either as a
1.
monitor RIO request
2.
Copro link request
To complete the process, the Standby determines
If ...
Copro link is down and the
Primary is down
Copro link is up
Then ...
Standby assumes control
Standby Copro sends a message to the Primary Copro and
1.
Primary Copro passes this request to the Primary CPU
2.
Primary checks the Primary RIO link
Understanding
Communication
Status to the
Drops
Depending on the status, the Primary RIO Head continues either to operate as the
Primary or goes offline.
If communication to drops is
Healthy
Then Action
Not healthy
RIO link failure must be on Standby side.
1.
The station continues to operate as the
Primary
2.
Standby RIO Head shows the link error pattern on the LEDs
RIO link failure is on
Primary side.
1.
The Primary RIO Head displays a link error
2.
Standby assumes control
130
Maintaining a Modicon Quantum Hot Standby with Unity System
Checking for Identical Application Programs—Checksum
Important
Information
Please note
Fact
A Hot Standby system requires that both stations must have the same application program.
Result
This requirement prevents the Standby from executing a different application program if transfer of control occurs.
Note: OVERRIDING SAME APPLICATION PROGRAM REQUIREMENT
To override the requirement that both controllers have the same application program, ensure that the Command Register’s %SW60.3 is set = 1. (See System
Standby Checks for Mismatches
Checking for identical application programs
Step
1
2
3
Action
At each scan, the application program's instruction, checksum
(CKSM), is transferred from the
Primary to the Standby along with any other necessary data.
Standby determines if mismatch occurs.
Result
The Standby validates the new checksum (CKSM) against its existing checksum (CKSM).
1.
Mismatch: Standby goes Offline
2.
No mismatch: system operates normally
The controller returns to Online and is the Standby as soon as the application programs are identical.
131
Maintaining a Modicon Quantum Hot Standby with Unity System
Replacing a Faulty Module
Important You may replace a faulty module while a system is running.
Ensure that the module being replaced:
1.
installs into the Standby backplane
2.
resides in the same position in both backplanes
3.
is same type of module
Same type of module means NOE replaces NOE, CRP replaces CRP.
Note: IMPORTANT INFORMATION
1.
Perform a switchover if replacing a Primary.
2.
Do NOT remove a Primary controller under power supply (Hot Swap).
132
Maintaining a Modicon Quantum Hot Standby with Unity System
Troubleshooting the Primary Controller
Troubleshooting the Primary
To determine which component failed, note controller’s status displayed in the HE
CPU LCD screen and the RIO Head’s status displayed by the RIO Head’ LEDs.
Controller Status RIO Head Status
Stop All LEDs off except
READY on and Com
Act blinks four times
Offline All LEDs off except
READY on
Stop
Failure Type Description
Controller An Interface error occurred.
Fiber Optic connection between both controllers
RIO Head
A Com Act error occurred.
A Com Act error occurred.
Stop
All LEDs off except
READY on and Com
Act displays error pattern
READY on and Com
Act blinks four times
RIO Cable
Failure at
Primary End
In a dual cable system, if only one cable fails, the Error A or
Error B indicator on the RIO
Head lights instead of stopping the system, and the system continues to operate. When the RIO cable fails at the
Primary end, input data may be reset to 0 for one scan because the communication failure to the drop occurs before the broken link is detected.
133
Maintaining a Modicon Quantum Hot Standby with Unity System
Troubleshooting the Standby Controller
Troubleshooting the Standby
To determine which component failed, note controller’s status displayed in the HE
CPU LCD screen and the RIO Head’s status displayed by the RIO Head’s LEDs.
RIO Head Status Failure Type Description Controller
Status
Stop
Offline
Stop
Stop
Offline
All LEDS off except
READY on or READY on and Com Act blinks once a second
READY on and Com
Act stops blinking
Com Act displays error pattern
Controller
Fiber Optic connection between both controllers
RIO Head
READY on and Com
Act blinks four times
An Interface error occurred.
A Com Act error occurred.
RIO Cable Failure at
Standby end
After you have replaced the module and cycled power, to ensure that the controllers have identical application programs, you must perform an application program update.
In a dual cable system, the RIO
Head gives no indication if only one cable has failed.
Com Act stops blinking Fiber Link failures: z from Standby
Transmit to z
Primary Receive from Primary
Transmit to
Standby Receive
134
Understanding the Modicon
Quantum Hot Standby with Unity
System Special Features
III
At a Glance
Purpose
What's in this
Part?
This part describes the special features of a Modicon Quantum Hot Standby with
Unity system.
z z z enabling an EXEC upgrade handling logic mismatch transferring application programs
This part contains the following chapters:
Chapter
7
8
9
10
Chapter Name
Enabling EXEC Upgrade with Unity Pro
Handling Logic Mismatch with Unity Pro
Transferring an Application Program with Unity Pro
Using the Modicon Quantum Hot Standby with Unity EFBs
Page
135
Understanding Modicon Quantum Hot Standby with Unity Special Features
136
Enabling EXEC Upgrade with
Unity Pro
7
Introduction
Overview
What's in this
Chapter?
In this chapter you will find information regarding the EXEC upgrade method for a
Modicon Quantum Hot Standby with Unity system. Upgrading allows you to update the EXEC for the standby controller while the process is still controlled by the primary controller.
This chapter contains the following topics:
Topic
Overview of Modicon Quantum Hot Standby with Unity EXEC Upgrade
Executing the EXEC Upgrade Procedure
Page
137
Enabling EXEC Upgrade
Overview of Modicon Quantum Hot Standby with Unity EXEC Upgrade
Upgrading while
Process is
Running
The Executive Upgrade feature allows upgrading the EXEC of the Standby controller while the Primary controller continues to control the process. However, during the upgrade, the system can no longer be considered redundant. That is, there is no Standby available to assume control if the Primary should fail before the
Standby upgrade is complete.
Upgrading EXEC without Stopping
Under normal operating conditions, both controllers in a redundant system must have the same versions of firmware.
In fact, there are checks by the controllers to detect if there is a mismatch in firmware.
Normally, when a mismatch exists, performing a switchover would not be possible because the Standby controller would not be allowed to go online.
However, to allow an EXEC Upgrade without stopping the application, overriding is possible by setting the Command Register system bit %SW60.4. Details of the
Modicon Quantum Hot Standby with Unity command register can be found in
Understanding the Unity Command Register, p. 110 .
Note: Enabling EXEC upgrade without stopping the application overrides the process of checking whether the Primary and Standby are configured identically.
Disable the upgrade without stopping bit as soon as the EXEC upgrade is finished.
Note: IMPORTANT INFORMATION
EXEC upgrade is possible only with compatible firmware.
138
Enabling EXEC Upgrade
Executing the EXEC Upgrade Procedure
General
Using Modbus
RTU
Perform an EXEC upgrade using the installed OSLoader tool. Use one of two communication methods available in the OSLoader: z z
Modbus RTU
Modbus Plus
Follow these steps.
Step
1
2
3
6
7
4
5
10
11
13
14
15
8
9
12
Action
Connect to the Primary.
Access the Command Register system bit %SW60.4; set bit to 1.
Disconnect the fiber optic cable on both controllers.
Open the OSLoader tool.
Select the Modbus communication option.
Stop the Standby.
Connect to the Standby using Modbus.
Note: Use the Standby’s Modbus address.
Download the OS to the Standby.
After completing the OS download, perform application program transfer to the
Standby.
Reconnect the fiber optic cables.
Put in RUN mode.
Note: Ensure Primary and Standby are in RUN Primary and RUN Standby mode.
Perform a switchover.
Note: Ensure Standby becomes Primary.
Repeat Steps 4 through 9 on the new Standby.
Connect to the new Primary.
Access Command Register system bit %SW60.4; set bit to 0).
Important If you upgrade using Modbus Plus, only address 1 is allowed for downloading.
Otherwise, there is no communication.
Ensure that no device in the Modbus Plus network is using the address ‘1’. (See
Handling Modbus Plus Addresses at Switchover, p. 92
)
139
Enabling EXEC Upgrade
Using Modbus
Plus
Follow these steps.
Step
1
2
3
4
9
10
7
8
5
6
11
12
13
14
15
16
Action
Connect to the Primary.
Access the Command Register system bit %SW60.4; set bit to 1.
Note: Before stopping the Standby, note the Modbus Plus address.
Stop the Standby.
Disconnect the fiber optic cable from both controllers.
Note: Primary operates without a Standby.
Switch off power, and switch on power to the Standby.
If not set to 1, change the Modbus Plus address of the Standby to 1.
Open the OSLoader tool.
Connect the Standby using Modbus Plus.
Note: Use the Standby’s Modbus Plus address.
Download the OS to the Standby.
Download application program to the Standby.
Note: Ensure that you download a valid application program.
Ensure that the Modbus Plus address is the same as the address noted in Step
3.
Reconnect fiber optic cable to both controllers.
Note: Primary operates with a Standby.
Put in RUN mode.
Ensure Primary and Standby are in RUN Primary and RUN Standby mode.
Perform switchover.
Note: Ensure Standby becomes Primary.
Repeats Steps 3 through 12 to the new Standby.
Ensure Primary and Standby are in RUN Primary and RUN Standby mode.
Connect to the new Primary, and access the Command Register system bit
%SW60.4; set to 0.
Compatibility
Issues
To upgrade a Modicon Quantum Hot Standby with Unity EXEC without shutting down the process, the current application program must be executable by the new
EXEC.
Observe this requirement when installing minor revisions targeted for bug fixes or minor enhancements.
When a major function enhancement needs to be made, maintaining this compatibility may not be possible.
In this case, to perform an EXEC upgrade requires a system shut down.
140
Handling Logic Mismatch with
Unity Pro
8
Introduction
Overview
What's in this
Chapter?
This chapter provides information about using the Logic Mismatch feature available in Unity Pro.
This chapter contains the following topics:
Topic
Understanding Modicon Quantum Hot Standby with Unity Logic Mismatch
Understanding Switchover Behavior during Logic Mismatch
Online or Offline Modifications and Logic Mismatch
Online Modifications to an Application Program in the Standby and Logic
Mismatch
Online Modifications to an Application Program in the Primary and Logic
Mismatch
Offline Modification of an Application Program and Logic Mismatch
Switchover Methods and Logic Mismatch
Application Program Transfer Method and Logic Mismatch
Recommendations for Using Logic Mismatch
Page
141
Logic Mismatch
Understanding Modicon Quantum Hot Standby with Unity Logic Mismatch
Needing
Identical
Application
Programs
In a fault-tolerant redundant system and under normal operating conditions, both controllers must load the identical application program (also called a logic program).
The application program is updated every scan by transferring data from the Primary to the Standby. Both controllers conduct tests to detect if a mismatch exists between the application programs.
The following conditions cause a mismatch in the application program: a difference between: z programs z z animation tables comments (on variables)
Note: Animation Tables and Comments
Both animation tables and comments (on variables) may be excluded from the mismatch by not including in the upload information.
z z
Exclude by selecting Tools | Project Settings | Build tabs (default).
In the Upload Information area, select without .
Not including requires downloading application program
When a mismatch exists, a switchover is not possible, and the Standby controller would NOT go online. However, there are situations when you may want to allow a mismatch between the application programs. To enable this condition, use the
Modicon Quantum Hot Standby with Unity Logic Mismatch feature.
Note: Switchover can NOT occur while the Standby controller is offline.
Defining Logic
Mismatch
Logic Mismatch is a Modicon Quantum Hot Standby with Unity feature that allows a mismatch between the application programs of the Primary and Standby controllers.
Use the Logic Mismatch feature to modify an application program without stopping the process.
Using the Build
Project Function
Note: Build Project vs. Rebuild All Project
1.
Use the Build Project function to perform a logic mismatch with Unity Pro.
Schneider Electric recommends do not use Rebuild All Project to create a logic mismatch because the Rebuild All Project function creates a completely new project even if nothing has been changed in the application.
142
Causing a
Mismatch
Allowing a
Mismatch
Creating a
Mismatch
Logic Mismatch
Note: CHANGING FROM LEGACY
Legacy Hot Standby systems reserved areas of the State RAM for user data, which was transferred from the Primary to the Standby during scans. Because of the transfer process, legacy Hot Standby systems could support different application programs in the two controllers. One application program resided in one controller, and a different application program resided in the other controller.
In the legacy system, the user could program the logic (now called application program) and decide where to store the data. With this method of programming, the memory is known as static data memory layout and is necessary to have different user data accessing the same variables.
In the Modicon Quantum Hot Standby with Unity system, all memory is allocated by a memory manager, which automatically transfers the logical memory to a physical memory location.
This dynamic data memory layout is the heart of the programming flexibility and platform independence that Unity Pro provides, but on a Modicon Quantum Hot
Standby with Unity system with different user logic, dynamic data memory layout makes a cyclical data update very difficult. Therefore, mismatches occur.
In a Modicon Quantum Hot Standby with Unity system, Logic Mismatch allows the following without stopping the application program process.
z modify (edit) online an application program in the Standby while the Primary controls the process
(See Online Modifications to an Application Program in the Standby and Logic z z
modify online an application program in the Primary while the Primary controls the process
(See Online Modifications to an Application Program in the Primary and Logic
download an offline-modified application program to the Standby and perform a switchover to run the modified application program
(See
Offline Modification of an Application Program and Logic Mismatch, p. 151 )
Use one of two methods to create a Logic Mismatch condition:
1.
select Standby on Logic Mismatch ; select online
(Hot Standby Tab in the Unity Pro dialog)
This action requires the application program to be downloaded to the controller.
2.
set to 1 the Command Register system bit %SW60.3
This action MUST be performed online in the Primary controller.
143
Logic Mismatch
Transferring
User Data during a Mismatch
The table following shows which user data is transferred when a mismatch occurs
Data Type Transferred on Logic Mismatch
Located variables (State RAM) Yes
Unlocated global variables
DFB & EFB instance data
Yes unless variables exist ONLY in modified controller
Yes unless data exist ONLY in modified controller
SFC variable area
System Bits and Words
Yes unless associated-SFC section is modified
Yes
Using Care with
Logic Mismatch
WARNING
I/O MAP HAZARD; CONFIGURATION HAZARD
A mismatch in either the I/O map or the configuration is not allowed under any circumstances.
z z
Ensure that both I/O maps are identical.
Ensure that both configurations are identical.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
Selecting the Standby On Logic Mismatch option, allows you to override this default condition (Standby going offline).
If you change the parameter in this field from Offline to Running, the Standby remains online if a logic mismatch is detected between the application program of the Standby and the application program of the Primary.
Updating Section
Data in an
Application
Program
All data of a section will be fully updated during every scan if the data in the Standby is equal to the counterpart data on the Primary. Section data will not be updated if it is not equal to its counterpart on the Primary.
If the sections are equal on the Primary and the Standby, the section data that is updated is: z Internal states of Elementary Function Blocks (EFBs) used in the section
For example, Timers, Counters, PID z All Derived Function Block (DFB)-Instance data blocks of each DFB instantiated in the section including nested DFBs.
144
Logic Mismatch
Updating Global
Data in an
Application
Program
With the Logic Mismatch enabled, application program global data will be updated with every scan. Global data that does not exist on both controllers is not updated.
The application program’s updated global data includes both:
1.
All declared variables in the Variable-Editor.
2.
All section and transition variables.
The process of updating the application program global data in a Hot Standby system affects: z z z
Declared variables
All declared variable will be updated on every scan as long as they are declared on both controllers.
Updating Standby
If a complete application program transfer is done to the controller that did not receive the modified changes, then both controllers will have equal application programs, and the Standby controller is fully updated.
Deleted and redeclared variables
If, due to a modification, a global variable has been deleted first, and then redeclared , this variable would be treated as a NEW variable, even if the same name is used. The update procedure must be followed to bring the controllers to an equalized state.
Note: GLOBAL DATA VARIABLES
The system reserves space for these variables whether they are used in the controller’s application program or not.
Unused variables consume space and require time to be transferred from the
Primary to the Standby. Therefore, in the Primary’s application program, Schneider
Electric does not recommend using variables that are defined but not used.
145
Logic Mismatch
Understanding Switchover Behavior during Logic Mismatch
Modifying the
Application
Variables
If a switchover occurs during logic mismatch, the new Primary will execute its own application program with the data received from the other controller.
Depending on the modification, different behaviors occur:
Modification
Only code changed (same variables).
Variables added to the initial Primary
Variables deleted from the initial Primary
Variables added to the initial Standby
Variables deleted from the initial Standby
Effect
All the variables exchanged between the controllers are equal.
Variables are not used by the new Primary.
New Primary executes application program using the latest values for these variables.
New Primary executes application program using initial values for these variables.
New Primary will not use these variables
146
Logic Mismatch
Modifying an
SFC Section with
Unity Pro
The SFC code-generation process does not generate direct executable code but generates a set of data used by the SFC interpreter in the controller’s OS to compute the next state.
As with Concept, Unity Pro z z does not maintain the equality between the two application programs when a modification of a SFC section occurs does execute an SFC section by restarting the controller from its initial state after a switchover
When a SFC section is modified in the Primary, its data are not transferred to the
Standby. When a transfer of logic occurs from the Primary to the Standby, the first section of the logic is diagnostic information.
Note: SFC Programming Language
Schneider Electric recommends not using the SFC programming language.
WARNING
SWITCHOVER HAZARD
If switchover occurs when the Run mode is selected and there is a logic mismatch between the two controllers, the Standby assumes Primary responsibilities and starts solving a different application program from the previous Primary.
z After completing modifications, perform application program transfer to ensure controllers contain the same application and remove logic mismatch.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
147
Logic Mismatch
Online or Offline Modifications and Logic Mismatch
Modifying
Application
Programs
Normally, once a fault-tolerant redundant system is configured, programmed, and controlling its process, the system is not shut down—not even for periodic maintenance. However, there may be situations when you may need to make modifications to the application program and continue to control the process.
The logic mismatch feature allows you to modify application programs online or offline while controlling the process.
WARNING
IMMEDIATE CONTROL OF PROCESS
Once a new application program is switched to the Standby, the
Standby takes control of the process.
z Ensure that you understand the
1.
operation of your process
2.
modifications made z Monitor all modifications to the application program
Failure to follow this precaution can result in death, serious injury, or equipment damage.
148
Logic Mismatch
Online Modifications to an Application Program in the Standby and
Logic Mismatch
Executing the
Procedure
To make online modifications to an application program (logic program or project) in the Standby controller, follow these steps.
Step
1
2
5
6
3
4
7
8
9
10
11
Action
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
Connect to the Primary controller and access the Command Register system bit
%SW60.3.
Set to 1 the Command Register system bit %SW60.3
Connect to the Standby controller.
Modify online the application program.
After completing the modifications, perform Build Project .
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
Perform a switchover. (See
Switchover Methods and Logic Mismatch, p. 153 )
Note: Standby will change to Primary.
Perform application transfer to Standby. Application Program Transfer Method
Connect to the new Primary controller and access the Command Register system bit%SW60.3.
Set to 0 the Command Register system bit %SW60.3
Note: Command Register is returned to 0 from 1.
Important
Reference
(See
Recommendations for Using Logic Mismatch, p. 156
)
149
Logic Mismatch
Online Modifications to an Application Program in the Primary and Logic
Mismatch
Executing the
Procedure
To make online modifications to an application program (logic program or project) in the Primary controller, follow these steps.
Step
1
2
5
6
3
4
7
8
9
Action
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
Connect to the Primary controller and access the Command Register system bit
%SW60.3.
Set to 1 the Command Register system bit %SW60.3
Modify online the application program.
After completing the modifications, perform Build Project .
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
Perform an application transfer to the Standby. Application Program Transfer
Method and Logic Mismatch, p. 155
Connect to the new Primary controller and access the Command Register system bit %SW60.3.
Set to 0 the Command Register system bit %SW60.3
Note: Command Register is returned to 0 from 1.
Important
Reference
(See
Recommendations for Using Logic Mismatch, p. 156 )
150
Logic Mismatch
Offline Modification of an Application Program and Logic Mismatch
Executing the
Procedure
To make offline modifications to an application program in either controller, follow these steps.
Step
1
2
3
4
5
6
7
8
9
10
11
12
Action
Modify offline the application program.
After completing the modifications, perform Build Project and save.
Note: Do NOT use the Rebuild All Project option because using Rebuild
All Project will cause the Standby to go offline when the application program is downloaded.
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
Connect to the Primary controller and access the Command Register system bit
%SW60.3.
Set to 1 the Command Register system bit %SW60.3
Open the modified program and connect to the Standby controller.
Download the program and select RUN.
Note: Check your controller’s state and ensure state is Run | Standby .
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
Perform a switchover. (See
Switchover Methods and Logic Mismatch, p. 153 )
Note: Ensure Standby switched to Primary.
Perform application transfer to Standby. Application Program Transfer Method
Connect to the new Primary controller and access the Command Register system bit %SW60.3.
Set to 0 the Command Register system bit %SW60.3
Note: Command Register is returned to 0 from 1.
Important
Reference
(See
Recommendations for Using Logic Mismatch, p. 156
)
151
Logic Mismatch
Important
WARNING
IMMEDIATE CONTROL OF PROCESS
Once a new application program is switched to the Standby, the
Standby takes control of the process.
z Ensure that you understand the
1.
operation of your process z
2.
modifications made
Monitor all modifications to the application program
Failure to follow this precaution can result in death, serious injury, or equipment damage.
152
Switchover Methods and Logic Mismatch
General
Switchover
Using Front
Panel Keypad
Switchover can be performed using one of two methods: z Hot Standby submenu on the front panel keypad z Command Register either system bit %SW60.1 or %SW60.2
To force a switchover using the front panel keypad, do the following:
Step
1
2
3
4
5
6
Action
Access the front panel keypad of the Primary controller.
Go to PLC Operation menu.
Go to Hot Standby submenu.
Go to Hot Standby mode
Modify Run to Offline.
Note: Ensure that Standby switched to Primary.
Modify offline to run.
Note: Ensure that the LCD displays Run Standby .
Logic Mismatch
Important for
Command
Register
Switchover
To perform the switchover using Command Register system bit %SW60.1 or
%SW60.2, ensure that following are considered: z application program is saved twice. Each save uses a different file name.
z file 1
Saved before modification z file 2
Saved after modification z order of the controller is [(A) or (B)]; use one of two methods: z
Hot Standby submenu on the front panel keypad ( PLC Operation | Hot z
Standby | Hot Standby Order ).
Unity Pro status dialog (refer to the bottom of the Unity Pro window when connected online)
153
Logic Mismatch
Switchover
Using Command
Register System
Bit %SW60.1 or
%SW60.2
To force a switchover by setting the bits in the Command Register, do the following:
Step
1
2
3
4
5
8
9
6
7
10
Action
Open file 1.
Connect to the Primary.
Ensure the controller order of the Primary is A or B.
Access z Command Register system bit %SW60.1
If the connected controller order is A.
z Command Register system bit %SW60.2
If the connected controller order is B.
Set bit to 0.
Note: Ensure that the Standby switched to Primary.
Open file 2.
Connect to the new Primary controller.
Access the Command Register system bit used in Step 4.
Set bit to 1.
Note: Ensure Standby controller is now online.
Ensure both Primary and Standby controllers are in Run Primary and Run
Standby mode.
154
Logic Mismatch
Application Program Transfer Method and Logic Mismatch
General
Application
Program
Transfer Using
Front Panel
Keypad
Application Program Transfer can be performed using one of two methods: z Hot Standby submenu on the front panel keypad z Command Register system bit %SW60.5
To transfer an application program (logic program or project) to either the Primary or Standby controller using the front panel keypad, do the following>
Step
1
2
3
4
Action
Access the front panel keypad of any controller (Primary or Standby)
Go to PLC Operations menu
Go to Hot Standby submenu
Go to Hot Standby transfer and press ENTER to confirm the transfer.
Note: Ensure transfer to Standby occurs.
Application
Program
Transfer Using
Command
Register System
Bit %SW60.5
To transfer an application program (logic program or project) to either the Primary or Standby controller using Command Register system bit %SW60.5, do the following.
Step
1
2
3
Action
Connect to the Primary controller.
Access Command Register system bit %SW60.5.
Set bit to 1.
Note: The process of setting the bit toggles the bit from 0 to 1 and back to 0.
155
Logic Mismatch
Recommendations for Using Logic Mismatch
General
Upload
Information
Management
Feature—
General
When using the Logic Mismatch feature, Schneider Electric recommends noting that the following are affected z z
Upload Information Management
Online modifications to the Standby z z
Application Program Transfer
Setting the Command Register system bit %SW60.3
During online modifications, your system detects that the application-program information in the controller differs from the application-program information in the computer. Because this information will be used later when an upload is performed, the system requires you to update this information and constantly presents a confirmation dialog. To avoid constant display of the dialog, use the Upload
Information Management feature.
Using the Upload
Information
Management
Feature
Before doing any modifications and at the initial start up of your system, do the following:
Step
1
2
3
4
5
Action
From the menu, select Tools | Option .
In the Options window, select the General tab (default).
Select Automatic in the Upload Information Management area.
Press OK to close the window.
Save the program and download to the controller.
Handling Online
Modifications to the Standby
For major modifications to the application program on the Standby, ensure the
Standby is in offline mode.
Two benefits result from this action: z Run process continues z Primary does NOT perform a switchover during modification of the Standby
Note: SWITCHOVER DURING MODIFICATION
If the Standby is online during modifcations, there is a possibilty of switchover occuring. If a switchover occurs, the Standby becomes Primary, and the process may run with incomplete modifications.
156
Performing
Application
Program
Transfer
Logic Mismatch
When performing an application program transfer, you want to avoid the possibility of having two different application programs running in the Primary and Standby.
Step
1
Action
Perform Application program transfers after completing online modifications with
Logic Mismatch.
Resetting
Command
Register System
Bit %SW60.3
When resetting the Command Register system bit %SW60.3 to 0, you want to avoid the possibility of having two different application programs running in the Primary and Standby.
Step
1
2
3
Action
Connect to Primary.
Access the Command Register system bit %SW60.3.
Reset bit to 0.
157
Logic Mismatch
158
Transferring an Application
Program with Unity Pro
9
Introduction
Overview
What's in this
Chapter?
This chapter provides information about the Application Program Transfer feature that enables you to configure the Standby controller from the Primary controller.
This chapter contains the following topics:
Topic
Overview of Application Program Transfer
Executing the Application Program Transfer Procedure Using the Command
Register
Automatic Application Program Transfer
Executing the Application Program Transfer Procedure Using the Keypad
Page
159
Application Program Transfer
Overview of Application Program Transfer
Overview
Methods of
Transferring
Programs
Validating
Transfer
Understanding
Transfer Time
The Application Program Transfer feature provides you with the ability to configure the Standby from the Primary controller.
Use this feature when you reprogram the Primary controller or replace the Standby controller because the process copies the full application program of the Primary to the Standby. This feature not only saves time but ensures that the controllers have identical configurations.
The system transfers the application program over the dedicated Modicon Quantum
Hot Standby with Unity communications link. In a redundant system, this link connects the two Copros.
Application transfer is always from the Primary to the Standby. There are three methods of transferring application programs: z z
Hot Standby submenu on the front panel keypad
Command Register system bit %SW60.5
z Automatic transfer (Occurs when you start a Hot Standby system for the first time.) Therefore, the Primary automatically transfers the application program to the Standby. (See
Automatic Application Program Transfer, p. 163
)
The Standby validates the transferred application program. After validating, the
Standby starts automatically.
Application Program Transfer time depends on the size of the application program, the larger the program, the longer the time. Application Program Transfer takes a few seconds.
Note: During application program transfer, the system can no longer be considered redundant.
If the Primary should fail before the Standby is ready to assume the role of Primary, there is no Standby available.
Updating from the Primary
An application program update may only be performed from the Primary to the
Standby.
Note: UPDATING STANDBYS
The Standby controller cannot update the Primary.
160
Application Program Transfer
Understanding
Transfer Size
Limits
Note: CHANGING FROM LEGACY
Legacy Modicon Quantum controllers running Concept have an Application
Program Transfer limit of 1 megabyte.
In the Modicon Quantum Hot Standby with Unity 140 CPU 671 60 transfer size depends on the configuration. For example, using a card bridge you may transfer up to 7 Mb.
Therefore, transfer the complete application program regardless of the size. This transfer takes place over multiple scans, thus will be broken up into multiple transfer packets.
161
Application Program Transfer
Executing the Application Program Transfer Procedure Using the Command
Register
Overview To transfer, use the command register in the Unity Pro software tools. The Primary copies the complete application program and data to the Standby.
Transferring the
Application
Program Using
Command
Register System
Bit %SW60.5
To transfer an application program (logic program or project) to either the Primary or Standby controller using Command Register system bit %SW60/5, do the following.
Step
1
2
3
Action
Connect to the Primary controller.
Access Command Register system bit %SW60.5.
Set bit to 1.
Note: The process of setting the bit toggles the bit from 0 to 1 and back to 0.
162
Application Program Transfer
Automatic Application Program Transfer
Overview New in a Modicon Quantum Hot Standby system with Unity is automatic application program transfer.
As soon as a Primary controller detects a blank controller, the Primary transfers the program to the blank controller, which becomes the Standby. After application program transfer both controllers have identical application programs.
This new feature works well when two controllers are at a maximum of 2 Km apart.
Note: Same Configuration
The controllers need to have the same configuration (with the same PCMCIA cards or without cards).
163
Application Program Transfer
Executing the Application Program Transfer Procedure Using the Keypad
Overview
Using the
Keypad
For specifics on setting Modicon Quantum Hot Standby with Unity state, mode, order, and transfer from the keypad, see Configuring a Modicon Quantum Hot
Standby with Unity System, p. 69
.
To transfer, use the front panel keypad on the controller unit (Primary or Standby).
The Primary copies the complete application program and data to the Standby.
Note: CHANGING FROM LEGACY
In legacy Quantum Hot Standby systems, an application program transfer could be performed ONLY on the Standby controller.
The Standby requested from the Primary an application transfer. The process was performed on the CHS module and required setting the key in the Xfer key position while pushing the update button.
In Modicon Quantum Hot Standby with Unity, an application transfer is performed either z using the command register z
An application program transfer can be performed at any time.
automatically z
Transfer occurs first time Primary finds an empty Standby using the keypad
Use either the Primary or Standby.
Transferring the
Application
Program
The following table shows the Application Program Transfer Procedure.
Step
1
2
3
4
5
Action
Ensure the Primary Controller is in RUN PRIMARY mode.
Result: The LCD on the PLC will display the mode as RUN PRIMARY.
Check that both
1.
Invalidate Keypad option is NOT selected
2.
the key switch is unlocked
Go to the submenu Hot Standby | Transfer.
Push Enter to execute the application program transfer from the Primary to the
Standby.
Note: The Hot Standby | Transfer command can be performed either in the
Primary or Standby controller, BUT only the Standby controller will be updated.
164
Identical
Configurations and Application
Programs
Application Program Transfer
After the transfer, the Primary and Standby have identical configurations and application programs.
In the event of a failure in the Primary and depending on the mode selected for the
Standby (Run or Offline), the Standby may or may not be ready to assume the role of Primary.
165
Application Program Transfer
166
Using the Modicon Quantum Hot
Standby with Unity EFBs
10
Introduction
Overview
What's in this
Chapter?
This chapter describes the Modicon Quantum Hot Standby with Unity elementary function blocks (EFBs) z z
HSBY_RD
HSBY_ST z z
HSBY_WR
REV_XFER
This chapter contains the following topics:
Topic
Description: HSBY_RD
Description: HSBY_ST
Description: HSBY_WR
Description: REV_XFER
Page
167
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Description: HSBY_RD
Function description
Representation in FBD
This EFB allows you to use the Hot Standby function. It searches (together with other EFBs in the Hot Standby family) the configuration of the respective
Quantum PLC for the required components. These components always refer to hardware that is actually connected.
Therefore the correct behavior of this EFB on the simulators cannot be guaranteed.
The HSBY_RD EFB independently checks if a Hot Standby configuration exists.
( %SW60 ). If a configuration is present the contents of the command register are given and the HSBY output is set to "1". If there is no Hot Standby configuration present the HSBY_ConfigurationFound output is set to "0".
EN and ENO can be configured as additional parameters.
Representation:
HSBY_RD_Instance
HSBY_RD
HSBY
INV_KEY
PCA_RUN
PCB_RUN
SBY_OFF
EXC_UPD
SWP_MB1
SWP_MB2
SWP_MB3
HSBY_ConfigurationFound
InvalidateKeypad
PLC_A_Running
PLC_B_Running
StandbyOff
ExecUpdate
SwapAddressModbusPort1
168
Representation in LD
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Representation:
HSBY_RD_Instance
HSBY_RD
EN ENO
HSBY
INV_KEY
PCA_RUN
PCB_RUN
SBY_OFF
EXC_UPD
SWP_MB1
SWP_MB2
SWP_MB3
HSBY_ConfigurationFound
InvalidateKeypad
PLC_A_Running
PLC_B_Running
StandbyOff
ExecUpdate
SwapAddressModbusPort1
Representation in IL
Representation in ST
Representation:
CAL HSBY_RD_Instance (HSBY=>HSBY_ConfigurationFound,
INV_KEY=>InvalidateKeypad, PCA_RUN=>PLC_A_Running,
PCB_RUN=>PLC_B_Running, SBY_OFF=>StandbyOff,
EXC_UPD=>ExecUpdate, SWP_MB1=>SwapAddressModbusPort1)
Representation:
HSBY_RD_Instance (HSBY=>HSBY_ConfigurationFound,
INV_KEY=>InvalidateKeypad, PCA_RUN=>PLC_A_Running,
PCB_RUN=>PLC_B_Running, SBY_OFF=>StandbyOff,
EXC_UPD=>ExecUpdate,
SWP_MB1=>SwapAddressModbusPort1);
169
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Parameter description
Description of the output parameters:
Parameter Data type Meaning
HSBY BOOL "1" = Hot Standby configuration found
INV_KEY
PCA_RUN
BOOL
BOOL
"1" = The submenu for the Hot Standby PLC button is disabled.
"1" = The PLC with the Hot Standby CPU
1.
function is "A" on local rack
2.
Command Register is selected RUN
PCB_RUN
SBY_OFF
BOOL
BOOL
"0" = The PLC with the Hot Standby CPU
1.
function is "A" on local rack
2.
Command Register is selected OFFLINE
"1" = The PLC with the Hot Standby CPU
1.
function is "B" on local rack
2.
Command Register is selected RUN
"0" = The PLC with the Hot Standby CPU
1.
function is "B" on local rack
2.
Command Register is selected OFFLINE
"1" = The standby PLC switches to the offline mode as soon as both PLCs receive a different program.
EXC_UPD
SWP_MB1
SWP_MB2
SWP_MB3
BOOL
BOOL
BOOL
BOOL
"1" = Exec-(Operating system-)Update in the Standby-PLC is possible with the primary PLC still running.
(After Exec-Update the standby PLC changes back to the online mode.)
If a switchover has occurred,
"1" = No Swap address of Modbus ports 1.
"0" = Swap address of Modbus ports 1.
Not used. Reserved
Not used. Reserved
170
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Description: HSBY_ST
Function description
Representation in FBD
This EFB allows you to use the Hot Standby function. It searches (together with other procedures in the Hot Standby family) the configuration of the respective
Quantum PLC for the required components. These components always refer to hardware that is actually connected.
Therefore the correct behavior of this EFB on the simulators cannot be guaranteed.
The EFB is used to read the IEC Hot Standby status register ( %SW61 ). If there is no
Hot Standby configuration present the HSBY output is set to "0".
EN and ENO can be configured as additional parameters.
Representation:
HSBY_ST_Instance
HSBY_ST
HSBY
THIS_OFF
THIS_PRY
THIS_SBY
REMT_OFF
REMT_PRY
REMT_SBY
LOGIC_OK
THIS_ISA
THIS_ISB
HSBY_ConfigurationFound
PLC_Offline
Primary_PLC
Standby_PLC
Remote_PLC_Offline
PrimaryRemote_PLC
StandbyRemote_PLC
IdenticalPrograms
HSBY_ModuleSwitchA
HSBY_ModuleSwitchB
171
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Representation in LD
Representation:
HSBY_ST_Instance
HSBY_ST
EN ENO
HSBY
THIS_OFF
THIS_PRY
THIS_SBY
REMT_OFF
REMT_PRY
REMT_SBY
LOGIC_OK
THIS_ISA
THIS_ISB
HSBY_ConfigurationFound
PLC_Offline
Primary_PLC
Standby_PLC
Remote_PLC_Offline
PrimaryRemote_PLC
StandbyRemote_PLC
IdenticalPrograms
HSBY_ModuleSwitchA
HSBY_ModuleSwitchB
Representation in IL
Representation:
CAL HSBY_ST_Instance (HSBY=>HSBY_ConfigurationFound,
THIS_OFF=>PLC_Offline, THIS_PRY=>Primary_PLC,
THIS_SBY=>Standby_PLC,
REMT_OFF=>Remote_PLC_Offline,
REMT_PRY=>PrimaryRemote_PLC,
REMT_SBY=>StandbyRemote_PLC,
LOGIC_OK=>IdenticalPrograms,
THIS_ISA=>HSBY_ModuleSwitchA,
THIS_ISB=>HSBY_ModuleSwitchB)
172
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Representation in ST
Parameter description
Representation:
HSBY_ST_Instance (HSBY=>HSBY_ConfigurationFound,
THIS_OFF=>PLC_Offline, THIS_PRY=>Primary_PLC,
THIS_SBY=>Standby_PLC,
REMT_OFF=>Remote_PLC_Offline,
REMT_PRY=>PrimaryRemote_PLC,
REMT_SBY=>StandbyRemote_PLC,
LOGIC_OK=>IdenticalPrograms,
THIS_ISA=>HSBY_ModuleSwitchA,
THIS_ISB=>HSBY_ModuleSwitchB);
Description of output parameters:
Parameter Data type Meaning
HSBY BOOL "1" = Hot Standby configuration found
THIS_OFF
THIS_PRY
BOOL
BOOL
"1" = This PLC is offline
"1" = This PLC is the primary PLC
THIS_SBY
REMT_OFF
REMT_PRY
REMT_SBY
BOOL
BOOL
BOOL
BOOL
"1" = This PLC is the standby PLC
"1" = The other (remote) PLC is offline
"1" = The other PLC is the primary PLC
"1" = The other PLC is the standby PLC
LOGIC_OK
THIS_ISA
THIS_ISB
BOOL
BOOL
BOOL
"1" = The programs for both PLCs are identical and Logic
Mismatch is active.
"1" = This PLC chose the CPU with the lower IP address between both Hot Standby CPUs. This is the Hot Standby CPU "A".
"1" = This PLC chose the CPU with the higher IP address between both Hot Standby CPUs. This is the Hot Standby CPU "B".
173
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Description: HSBY_WR
Function description
Representation in FBD
This EFB allows you to use the Hot Standby function. It searches (together with other EFBs in the Hot Standby family) the configuration of the respective
Quantum PLC for the required components. These components always refer to hardware that is actually connected.
Therefore the correct behavior of this EFB on the simulators cannot be guaranteed.
The EFB HSBY_WR is used to set different Hot Standby Modes permitted for Hot
Standby. Setting the respective modes means a change in the Hot Standby command register ( %SW60 ), which is carried out automatically by the function block.
If there is no Hot Standby configuration, the HSBY_ConfigurationFound output is set to "0", otherwise it is set to "1".
Note: This function only affects the primary CPU.
EN and ENO can be configured as additional parameters.
Representation:
InvalidateKeypad
PLC_A_Running
PLC_B_Running
SwapAddressModbusPort1
HSBY_WR_Instance
HSBY_WR
INV_KEY
PCA_RUN
PCB_RUN
SWP_MB1
SWP_MB2
SWP_MB3
HSBY HSBY_ConfigurationFound
174
Representation in LD
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Representation:
InvalidateKeypad
PLC_A_Running
PLC_B_Running
SwapAddressModbusPort1
HSBY_WR_Instance
HSBY_WR
EN ENO
HSBY INV_KEY
PCA_RUN
PCB_RUN
SWP_MB1
SWP_MB2
SWP_MB3
HSBY_ConfigurationFound
Representation in IL
Representation in ST
Representation:
CAL HSBY_WR_Instance (INV_KEY:=InvalidateKeypad,
PCA_RUN:=PLC_A_Running, PCB_RUN:=PLC_B_Running,
SWP_MB1:=SwapAddressModbusPort1,
HSBY=>HSBY_ConfigurationFound)
Representation:
HSBY_WR_Instance (INV_KEY:=InvalidateKeypad,
PCA_RUN:=PLC_A_Running, PCB_RUN:=PLC_B_Running,
SWP_MB1:=SwapAddressModbusPort1,
HSBY=>HSBY_ConfigurationFound);
175
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Parameter description
Description of the input parameters:
Parameter Data type Meaning
INV_KEY BOOL In the submenu for the Hot Standby PLC button
"1" = Changes are disabled.
"0" = Changes are allowed.
PCA_RUN
PCB_RUN
BOOL
BOOL
"1 -> 0" = The Hot Standby CPU with function "A" on the local rack is forced into OFFLINE mode.
"0 -> 1" = The Hot Standby CPU with function "A" is forced into
RUN mode if its own button mode is in RUN mode.
"1 -> 0" = The Hot Standby CPU with function "B" on the local rack is forced into OFFLINE mode.
"0 -> 1" = The Hot Standby CPU with the function "B" is forced into
RUN mode if its own button mode is in RUN mode.
SWP MB1
SWP_MB2
SWP MB3
BOOL
BOOL
BOOL z z
"0" and a switchover has occurred: The Modbus address on port 1 of the NEW primary PLC changes.
new primary PLC address = old primary address new standby PLC address = old address + 128.
"1" and a switchover has occurred: The Modbus address at Port 1 z z of the NEW primary PLC changes.
new primary PLC address = old primary address new standby PLC address = old primary address
Not used. Reserved
Not used. Reserved
Description of the output parameters:
Parameter
HSBY
Data type
BOOL
Meaning
"1" = Hot Standby configuration found.
176
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Description: REV_XFER
Function description
Appearance in
FBD
This EFB allows you to use the Hot Standby function. It searches (together with other EFBs in the Hot Standby family) the configuration of the respective
Quantum PLC for the required components. These components always refer to hardware that is actually connected.
Therefore the correct behavior of this EFB on the simulators cannot be guaranteed.
The EFB REV_XFER provides the option of transferring two 16 bit words from the standby PLC to the primary PLC. The two registers transferred by this procedure are
%SW62 and %SW63 .
REV_XFER must be called up absolutely in the first section of the project executed.
The parameter addresses TO_REV1 and TO_REV2 must be in the non-transfer area to prevent an overwriting by the Primary PLC.
Note: In the old (Concept) Hot Standby System these two registers (Reverse
Transfer Registers) are the first addresses in the non-transfer area.
As additional parameters, EN and ENO are projected.
Appearance:
Standby_PLC_FirstReg
Standby_PLC_SecondReg
REV_XFER_Instance
REV_XFER
TO_REV1
TO_REV2
HSBY
PRY
SBY
FR_REV1
FR_REV2
HSBY_ConfFlag
Primary_PLC_Flag
Standby_PLC_Flag
FirstRevTransReg
SecondRevTransReg
177
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Appearance in
LD
Appearance:
Standby_PLC_FirstReg
Standby_PLC_SecondReg
REV_XFER_Instance
REV_XFER
EN
TO_REV1
TO_REV2
ENO
HSBY_ConfFlag
HSBY
PRY
Primary_PLC_Flag
Standby_PLC_Flag
SBY
FR_REV1
FR_REV2
FirstRevTransReg
SecondRevTransReg
Appearance in IL Appearance :
CAL REV_XFER_Instance (TO_REV1:=Standby_PLC_FirstReg,
TO_REV2:=Standby_PLC_SecondReg, HSBY=>HSBY_ConfFlag,
PRY=>Primary_PLC_Flag, SBY=>Standby_PLC_Flag,
FR_REV1=>FirstRevTransReg,
FR_REV2=>SecondtRevTransReg)
Appearance in
ST
Appearance:
REV_XFER_Instance (TO_REV1:=Standby_PLC_FirstReg,
TO_REV2:=Standby_PLC_SecondReg, HSBY=>HSBY_ConfFlag,
PRY=>Primary_PLC_Flag, SBY=>Standby_PLC_Flag,
FR_REV1=>FirstRevTransReg,
FR_REV2=>SecondtRevTransReg);
178
Parameter description
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
Description of input parameters:
Parameter Data type Description
TO_REV1 INT Describes the first reverse transfer register if this PLC is the standby PLC.
TO_REV2 INT Describes the second reverse transfer register if this PLC is the standby PLC.
Description of the output parameters:
Parameter Data type Meaning
HSBY BOOL 1= Hot Standby configuration
PRY
SBY
FR_REV1
FR_REV2
BOOL
BOOL
INT
INT
1 = This PLC is the primary PLC.
1 = This PLC is the standby PLC.
Content of first reverse transfer register ( %SW62 ). Output only if
HSBY is "1".
Content of second reverse transfer register ( %SW63 ). Output only if
HSBY is "1".
179
Using Modicon Quantum Hot Standby with Unity HSBY EFBs
180
Appendices
Appendices for Quantum Hot Standby Planning and Installation Guide
At a Glance
What's in this
Appendix?
The appendices for the Quantum Hot Standby Planning and Installation Guide are included here.
The appendix contains the following chapters:
Chapter
A
Chapter Name
Modicon Quantum Hot Standby with Unity Additional Information
Page
181
Appendices
182
Modicon Quantum Hot Standby with Unity Additional Information
A
Introduction
Overview
What's in this
Chapter?
This chapter describes the necessary cables, design specifications, error codes.
This chapter contains the following topics:
Topic
Fiber Optic Cable
140 CPU 671 60 Specifications for Modicon Quantum Hot Standby with Unity
CRP Remote I/O Head Processor Error Patterns
TextIDs
Page
183
Additional Information
Fiber Optic Cable
Schneider
Electric
Recommends
Recommendations
1
2
3
4
Use up to 2 km of 62.5/125 µ m graded index, duplex, multimode glass fiber for all applications because of the relatively low loss of signal and signal distortion.
Note: Most 62.5/125 µ m cables are rated at 3.5 dB loss per km.
Use a 3 mm diameter cable for your Modicon Quantum Hot Standby with Unity system.
Note: The fiber cable clasps used to maneuver the cable into the ports are designed to be used with 3 mm cable.
Select the cable that meets the demands of your application.
Wherever possible, use a multiconductor cable since the cable is inexpensive and provides a backup in case the cable is cut in the process of pulling.
Cables Available From Schneider Electric
Part Number
490 NOR 000 03
490 NOR 000 05
490 NOR 000 15
Maximum Length
3 meters
5 meters
15 meters
184
Additional Information
140 CPU 671 60 Specifications for Modicon Quantum Hot Standby with Unity
Module
Specifications
Component
Communication ports
Bus current required
Max. number of NOM, NOE, CRP 811 and
MMS modules supported (any combination)
Key switch
Keypad
Yes
Yes
Description
1 Modbus (RS-232/RS-485)
1 Modbus Plus (RS-485)
1 USB
1 Ethernet (used as HSBY port)
1800 mA
6
Processor
Feature
Model
Clock speed
Coprocessor
Watchdog timer
Description
Pentium
266 MHz
Yes, Built-in Ethernet
250 ms S/W adjustable
Memory
Reference
Capacity
RAM
768 kbytes
128 kbytes
64 kwords
8.192 kbytes
Discrete (bits)
Registers (words)
Description memory for on board program and unlocated data, extensible to 7,168 Mb by PCMCIA max memory for configuration memory for located data (state RAM)
PCMCIA extension for data storage
64 k (any combination)
64 k max.
185
Additional Information
Remote I/O
Max. I/O words/drop
Max. number of remote drops
64 in / 64 out*
31
* This information can be a mix of discrete or register I/O. For each word of configured I/O, one of the I/O words must be subtracted from the total available.
Battery and
Clock
Battery type
Service life
Shelf life
Battery load current @ power-off
TOD clock
3 V Lithium
1200 mAh
10 years with 0.5% loss of capacity/year typical: 14 µ A max. 420 µ A
+/-8.0 s/day @ 0 ... 60 ° C
Diagnostic
Power-up
Run Time
RAM
RAM address
Executive Checksum
User Logic Check
Processor
RAM
RAM address
Executive Checksum
User Logic Check
186
Additional Information
CRP Remote I/O Head Processor Error Patterns
Error Patterns The following table displays both z number of times the Com Act indicator blinks for each type of error z possible codes for each type of blink
187
Additional Information
5
6
7
All codes are in hex.
Number of blinks on
Com Act Indicator
Slow (steady)
2
3
4
8
Code in hex
684B
684C
6729
6616
6617
6619
681A
681C
6503
6402
6300
6301
8001
8002
8003
6840
6841
6842
6843
6844
6845
0000
6820
6822
6823
682A
682B
682C
6846
6847
6849
684A
Error requested kernel mode hcb frame pattern error head control block diag error mod personality diag error fatal start IO error bad read IO pers request bad execute diag request
ASCII input xfer state
ASCII output xfer state
IO input comm state
IO output comm state
ASCII abort comm state
ASCII pause comm state
ASCII input comm state
ASCII output comm state building 10 byte packet building 12 byte packet building 16 byte packet illegal IO drop number
984 interface bus ack stuck high coax cable initialization error coax cable dma xfer error coax cable dumped data error coax cable DRQ line hung coax cable DRQ hung
RAM address test error
RAM data test error
PROM checksum error (exec not loaded)
PROM checksum error kernel PROM checksum error flash prog / erase error unexpected executive return
188
Additional Information
TextIDs
TextIDs TextIds define the warning messages written in the diagnostic buffer.
TextIDs switching from Primary to Offline
TextID
13001
13002
13003
13004
13005
13006
13007
Warning message
System halt
Remote IO failure
ETH device failure
ETH communication problem
Stop PLC command
Offline keypad switch
Offline Command register request
TextIDs switching from Standby to Offline
TextID
13008
13009
13010
13011
13012
13013
13014
Warning message
System halt
Remote IO failure
ETH device failure
ETH communication problem
Stop PLC command
Offline keypad switch
Offline Command register request
TextIDs switching from Standby to Primary
TextID
13015
13016
Warning message
Control command over ETH
Control command over RIO
TextIDs switching from Offline to Primary/Standby
TextID
13017
13018
Warning message
Switch from Offline to Primary
Switch from Offline to Standby BY
189
Additional Information
190
Glossary
!
%I
%IW
%KW
%M
%MW
%Q
%QW
According to the IEC standard, %I indicates a discrete input-type language object.
According to the IEC standard, %IW indicates an analog input -type language object.
According to the IEC standard, %KW indicates a constant word-type language object.
According to the IEC standard, %M indicates a memory bit-type language object.
According to the IEC standard, %MW indicates a memory word-type language object.
According to the IEC standard, %Q indicates a discrete output-type language object.
According to the IEC standard, %QW indicates an analog output-type language object.
A
ADDR_TYPE
ANL_IN
This predefined type is used as output for ADDR function. This type is ARRAY[0..5]
OF Int. You can find it in the libset, in the same family than the EFs which use it.
ANL_IN is the abbreviation of Analog Input data type and is used when processing analog values. The %IW adresses for the configured analog input module, which were specified in the I/O component list, are automatically assigned data types and should therefore only be occupied with Unlocated Variables.
191
Glossary
ANL_OUT
ANY
192
ANL_OUT is the abbreviation of Analog Output data type and is used when processing analog values. The %MW adresses for the configured analog input module, which were specified in the I/O component list, are automatically assigned data types and should therefore only be occupied with Unlocated Variables.
There is a hierarchy between the different types of data. In the DFB, it is sometimes possible to declare which variables can contain several types of values. Here, we use ANY_xxx types.
The following diagram shows the hierarchically-ordered structure:
ANY
ANY_ELEMENTARY
ANY_MAGNITUDE_OR_BIT
ANY_MAGNITUDE
ANY_NUM
ANY_REAL
REAL
ANY_INT
DINT, INT, UDINT, UINT
TIME
ANY_BIT
DWORD, WORD, BYTE, BOOL
ANY_STRING
STRING
ANY_DATE
DATE_AND_TIME, DATE, TIME_OF_DAY
EBOOL
ANY_DERIVED
ANY_ARRAY
ANY_ARRAY_ANY_EDT
ANY_ARRAY_ANY_MAGNITUDE
ANY_ARRAY_ANY_NUM
ANY_ARRAY_ANY_REAL
ANY_ARRAY_REAL
ANY_ARRAY_ANY_INT
ANY_ARRAY_DINT
ANY_ARRAY_INT
ANY_ARRAY_UDINT
ANNY_ARRAY_UINT
ANY_ARRAY_TIME
ANY_ARRAY_ANY_BIT
ANY_ARRAY_DWORD
ANY_ARRAY_WORD
ANY_ARRAY_BYTE
ANY_ARRAY_BOOL
ANY_ARRAY_ANY_STRING
ANY_ARRAY_STRING
ANY_ARRAY_ANY_DATE
ANY_ARRAY_DATE_AND_TIME
ANY_ARRAY_DATE
ANY_ARRAY_TIME_OF_DAY
ANY_ARRAY_EBOOL
ANY_ARRAY_ANY_DDT
ANY_STRUCTURE
ANY_DDT
ANY_IODDT
ANY_FFB
ANY_EFB
ANY_DFB
ARRAY
Glossary
An ARRAY is a table of elements of the same type.
The syntax is as follows: ARRAY [<terminals>] OF <Type>
Example:
ARRAY [1..2] OF BOOL is a one-dimensional table made up of two BOOL -type elements.
ARRAY [1..10, 1..20] OF INT is a two-dimensional table made up of 10x20
INT -type elements.
B
Base 10 literals
Base 16 Literals
Base 2 Literals
Base 8 Literals
A literal value in base 10 is used to represent a decimal integer value. This value can be preceded by the signs "+" and "-". If the character "_" is employed in this literal value, it is not significant.
Example:
-12 , 0 , 123_456 , +986
An literal value in base 16 is used to represent an integer in hexadecimal. The base is determined by the number "16" and the sign "#". The signs "+" and "-" are not allowed. For greater clarity when reading, you can use the sign "_" between bits.
Example:
16#F_F or 16#FF (in decimal 255)
16#F_F or 16#FF (in decimal 224)
A literal value in base 2 is used to represent a binary integer. The base is determined by the number "2" and the sign "#". The signs "+" and "-" are not allowed. For greater clarity when reading, you can use the sign "_" between bits.
Example:
2#1111_1111 or 2#11111111 (in decimal 255)
2#1110_0000 or 2#11100000 (in decimal 224)
A literal value in base 8 is used to represent an octal integer. The base is determined by the number "8" and the sign "#". The signs "+" and "-" are not allowed. For greater clarity when reading, you can use the sign "_" between bits.
Example:
8#3_77 or 8#377 (in decimal 255)
8#34_0 or 8#340 (in decimal 224)
193
Glossary
BCD
BOOL
BYTE
BCD is the abbreviation of Binary Coded Decimal format
BCD is used to represent decimal numbers between 0 and 9 using a group of four bits (half-byte).
In this format, the four bits used to code the decimal numbers have a range of unused combinations.
Example of BCD coding: z the number 2450 z is coded: 0010 0100 0101 0000
BOOL is the abbreviation of Boolean type. This is the elementary data item in computing. A BOOL type variable has a value of either: 0 ( FALSE ) or 1 ( TRUE ).
A BOOL type word extract bit, for example: %MW10.4
.
When 8 bits are put together, this is callad a BYTE . A BYTE is either entered in binary, or in base 8.
The BYTE type is coded in an 8 bit format, which, in hexadecimal, ranges from
16#00 to 16#FF
D
DATE
DATE_AND_
TIME
The DATE type coded in BCD in 32 bit format contains the following information: z the year coded in a 16-bit field, z z the month coded in an 8-bit field, the day coded in an 8-bit field.
The DATE type is entered as follows: D# <Year> <Month> <Day>
This table shows the lower/upper limits in each field:
Field
Year
Limits Comment
[1990,2099] Year
Month [01,12]
Day [01,31]
The left 0 is always displayed, but can be omitted at the time of entry
For the months 01\03\05\07\08\10\12
[01,30]
[01,29]
[01,28]
For the months 04\06\09\11
For the month 02 (leap years)
For the month 02 (non leap years) see DT
194
DBCD
DDT
DFB
DINT
Glossary
Representation of a Double BCD-format double integer.
The Binary Coded Decimal (BCD) format is used to represent decimal numbers between 0 and 9 using a group of four bits.
In this format, the four bits used to code the decimal numbers have a range of unused combinations.
Example of DBCD coding: z the number 78993016 z is coded: 0111 1000 1001 1001 0011 0000 0001 0110
DDT is the abbreviation of Derived Data Type.
A derived data type is a set of elements of the same type ( ARRAY ) or of various types
(structure)
DFB is the abbrevation of Derived Function Block.
DFB types are function blocks that can be programmed by the user ST, IL, LD or
FBD.
By using DFB types in an application, it is possible to: z z z z simplify the design and input of the program, increase the legibility of the program, facilitate the debugging of the program, reduce the volume of the generated code.
DINT is the abbrevation of Double Integer format (coded on 32 bits).
The lower and upper limits are as follows: -(2 to the power of 31) to (2 to the power of 31) - 1.
Example:
-2147483648 , 2147483647 , 16#FFFFFFFF .
195
Glossary
DT DT is the abbreviation of Date and Time.
The DT type coded in BCD in 64 bit format contains the following information: z The year coded in a 16-bit field, z z the month coded in an 8-bit field, the day coded in an 8-bit field, z z the hour coded in a 8-bit field, the minutes coded in an 8-bit field, z the seconds coded in an 8-bit field.
Note: The 8 least significant bits are unused.
The DT type is entered as follows:
DT# <Year> <Month> <Day> <Hour> : <Minutes> : <Seconds>
This table shows the lower/upper limits in each field:
Field
Year
Limits Comment
[1990,2099] Year
Month [01,12]
Day [01,31]
The left 0 is always displayed, but can be omitted at the time of entry
For the months 01\03\05\07\08\10\12
Hour
[01,30]
[01,29]
[01,28]
[00,23]
Minute [00,59]
Second [00,59]
For the months 04\06\09\11
For the month 02 (leap years)
For the month 02 (non leap years)
The left 0 is always displayed, but can be omitted at the time of entry
The left 0 is always displayed, but can be omitted at the time of entry
The left 0 is always displayed, but can be omitted at the time of entry
196
DWORD
Glossary
DWORD is the abbreviation of Double Word.
The DWORD type is coded in 32 bit format.
This table shows the lower/upper limits of the bases which can be used:
Base
Hexadecimal
Octal
Binary
Lower limit
16#0
8#0
2#0
Upper limit
16#FFFFFFFF
8#37777777777
2#11111111111111111111111111111111
Representation examples:
Data content
00000000000010101101110011011110
00000000000000010000000000000000
00000000000010101011110011011110
Representation in one of the bases
16#ADCDE
8#200000
2#10101011110011011110
E
EBOOL
EF
EBOOL is the abbrevation of Extended Boolean type. It can be used to manage rising or falling edges, as well as forcing.
An EBOOL type variable takes up one byte of memory.
Is the abbreviation of Elementary Function.
This is a block which is used in a program, and which performs a predefined software function.
A function has no internal status information. Multiple invocations of the same function using the same input parameters always supply the same output values.
Details of the graphic form of the function invocation can be found in the "[Functional block (instance)] ". In contrast to the invocation of the function blocks, function invocations only have a single unnamed output, whose name is the same as the function. In FBD each invocation is denoted by a unique [number] via the graphic block, this number is automatically generated and can not be altered.
You position and set up these functions in your program in order to carry out your application.
You can also develop other functions using the SDKC development kit.
197
Glossary
EFB
Elementary
Function
EN
ENO
Is the abbreviation for Elementary Function Block.
This is a block which is used in a program, and which performs a predefined software function.
EFBs have internal statuses and parameters. Even where the inputs are identical, the output values may be different. For example, a counter has an output which indicates that the preselection value has been reached. This output is set to 1 when the current value is equal to the preselection value.
see EF
EN means EN able, this is an optional block input. When EN is activated, an ENO output is automatically drafted.
If EN = 0, the block is not activated, its internal program is not executed and ENO ist set to 0.
If EN = 1, the internal program of the block is executed, and ENO is set to 1 by the system. If an error occurs, ENO is set to 0.
ENO means E rror NO tification, this is the output associated to the optional input EN .
If ENO is set to 0 (caused by EN =0 or in case of an execution error), z the outputs of function blocks remain in the status they were in for the last correct z executed scanning cycle and the output(s) of functions and procedures are set to "0".
F
FBD
FFB
Function
Function Block
Diagram
FBD is the abbreviation of Function Block Diagram.
FBD is a graphic programming language that operates as a logic diagram. In addition to the simple logic blocks ( AND , OR , etc.), each function or function block of the program is represented using this graphic form. For each block, the inputs are located to the left and the outputs to the right. The outputs of the blocks can be linked to the inputs of other blocks to form complex expressions.
Collective term for EF (Elementary Function), EFB (Elementary Function Block) and
DFB (Derived Function block) see EF see FBD
198
Glossary
G
GRAY Gray or "reflected binary" code is used to code a numerical value being developed into a chain of binary configurations that can be differentiated by the change in status of one and only one bit.
This code can be used, for example, to avoid the following random event: in pure binary, the change of the value 0111 to 1000 can produce random numbers between
0 and 1000, as the bits do not change value altogether simultaneously.
Equivalence between decimal, BCD and Gray:
Decimal 0
BCD
1 2 3 4 5 6 7 8 9
0000 0001 0010 0011 0100 0101 0110 0111 1000 1001
Gray 0000 0001 0011 0010 0110 0111 0101 0100 1100 1101
I
IEC 61131-3
IL
INF
International standard: Programmable Logic Controls
Part 3: Programming languages.
IL is the abbreviation of Instruction List.
This language is a series of basic instructions.
This language is very close to the assembly language used to program processors.
Each instruction is composed of an instruction code and an operand.
Used to indicate that a number overruns the allowed limits.
For a number of Integers, the value ranges (shown in gray) are as follows:
-INF
-3.402824e+38 -1.1754944e-38 0.0
1.1754944e-38
INF
3.402824e+38
When a calculation result is: z z less than -3.402824e+38, the symbol -INF (for -infinite) is displayed, greater than +3.402824e+38, the symbol INF (for +infinite) is displayed.
199
Glossary
INT
Integer Literals
IODDT
INT is the abbreviation of single integer format (coded on 16 bits).
The lower and upper limits are as follows: -(2 to the power of 15) to (2 to the power of 15) - 1.
Example:
-32768 , 32767 , 2#1111110001001001 , 16#9FA4 .
Integer literal are used to enter integer values in the decimal system. The values can have a preceding sign (+/-). Individual underlines (_ ) between numbers are not significant.
Example:
-12 , 0 , 123_456 , +986
IODDT is the abbreviation of Input/Output Derived Data Type.
The term IODDT designates a structured data type representing a module or a channel of a PLC module. Each application expert module possesses its own
IODDTs.
K
Keyword A keyword is a unique combination of characters used as a syntactical programming language element (See annex B definition of the IEC standard 61131-3. All the key words used in Unity Pro and of this standard are listed in annex C of the IEC standard 61131-3. These keywords cannot be used as identifiers in your program
(names of variables, sections, DFB types, etc.)).
LD
L
Located variables
LD is the abbreviation of Ladder Diagram.
LD is a programming language, representing the instructions to be carried out in the form of graphic diagrams very close to a schematic electrical diagram (contacts, coils, etc.).
A located variable is a variable for which it is possible to know its position in the PLC memory. For example, the variable Water_pressure , is associated with %MW102 .
Water_pressure is said to be localized.
200
Glossary
M
Multiple Token Operating mode of an SFC. In multitoken mode, the SFC may possess several active steps at the same time.
N
Naming conventions
(Identifier)
NAN
An identifier is a sequence of letters, numbers and underlines beginning with a letter or underline (e.g. name of a function block type, an instance, a variable or a section).
Letters from national character sets (e.g: ö,ü, é, õ) can be used except in project and
DFB names. Underlines are significant in identifiers; e.g. A_BCD and AB_CD are interpreted as different identifiers. Multiple leading underlines and consecutive underlines are invalid.
Identifiers cannot contain spaces. Not case sensitive; e.g. ABCD and abcd are interpreted as the same identifier.
According to IEC 61131-3 leading digits are not allowed in identifiers. Nevertheless, you can use them if you activate in dialog Tools → Project settings in tab
Language extensions the ceck box Leading digits .
Identifiers cannot be keywords.
Used to indicate that a result of an operation is not a number (NAN = Not A Number).
Example: calculating the square root of a negative number.
Note: The IEC 559 standard defines two classes of NAN: quiet NAN ( QNAN ) and signaling NaN ( SNaN ) QNAN is a NAN with the most significant fraction bit set and a
SNAN is a NAN with the most significant fraction bit clear (Bit number 22). QNAN s are allowed to propagate through most arithmetic operations without signaling an exception. SNAN generally signal an invalid-operation exception whenever they appear as operands in arithmetic operations (See %SW17 and %S18).
201
Glossary
Network There are two meanings for Network.
z In LD:
A network is a set of interconnected graphic elements. The scope of a network z is local to the program organization unit (section) in which the network is located.
With communication expert modules:
A network is a group of stations which communicate among one another. The term network is also used to define a group of interconnected graphic elements.
This group forms then a part of a program which may be composed of a group of networks.
P
Procedure Procedures are functions view technically. The only difference to elementary functions is that procedures can take up more than one output and they support data type VAR_IN_OUT . To the eye, procedures are no different than elementary functions.
Procedures are a supplement to IEC 61131-3.
202
Glossary
R
REAL Real type is a coded type in 32 bits.
The ranges of possible values are illustrated in gray in the following diagram:
-INF
-3.402824e+38 -1.1754944e-38 0.0
1.1754944e-38
INF
3.402824e+38
When a calculation result is: z between -1.175494e-38 and 1.175494e-38 it is considerd as a DEN , z z z less than -3.402824e+38, the symbol -INF (for - infinite) is displayed, greater than +3.402824e+38, the symbol INF (for +infinite) is displayed, undefined (square root of a negative number), the symbol NAN or NAN is displayed.
Note: The IEC 559 standard defines two classes of NAN: quiet NAN ( QNAN ) and signaling NaN ( SNaN ) QNAN is a NAN with the most significant fraction bit set and a
SNAN is a NAN with the most significant fraction bit clear (Bit number 22). QNAN s are allowed to propagate through most arithmetic operations without signaling an exception. SNAN generally signal an invalid-operation exception whenever they appear as operands in arithmetic operations (See %SW17 and %S18).
Note: when an operand is a DEN (Denormalized number) the result is not significant.
Real Literals
Real Literals with
Exponent
An literal real value is a number expressed in one or more decimals.
Example:
-12.0
, 0.0
, +0.456
, 3.14159_26
An Literal decimal value can be expressed using standard scientific notation. The representation is as follows: mantissa + exponential.
Example:
-1.34E-12 or -1.34e-12
1.0E+6 or 1.0e+6
1.234E6
or 1.234e6
203
Glossary
S
SFC
Single Token
ST
STRING
SFC is the abbreviation of Sequential Function Chart.
SFC enables the operation of a sequential automation device to be represented graphically and in a structured manner. This graphic description of the sequential behavior of an automation device, and the various situations which result from it, is performed using simple graphic symbols.
Operating mode of an SFC chart for which only a single step can be active at any one time.
ST is the abbreviation of Structured Text language.
Structured Text language is an elaborated language close to computer programming languages. It enables you to structure series of instructions.
A variable of the type STRING is an ASCII standard character string. A character string has a maximum length of 65534 characters.
T
TIME
Time literals
TIME_OF_DAY
The type TIME expresses a duration in milliseconds. Coded in 32 bits, this type makes it possible to obtain periods from 0 to 2
32
-1 milliseconds.
The units of type TIME are the following: the days ( d ), the hours ( h ), the minutes ( m ), the seconds ( s ) and the milliseconds ( ms ). A literal value of the type TIME is represented by a combination of previous types preceded by T# , t# , TIME# or time# .
Examples: T#25h15m , t#14.7S
, TIME#5d10h23m45s3ms
The units of type TIME are the following: the days ( d ), the hours ( h ), the minutes ( m ), the seconds ( s ) and the milliseconds ( ms ). A literal value of the type TIME is represented by a combination of previous types preceded by T# , t# , TIME# or time# .
Examples: T#25h15m , t#14.7S
, TIME#5d10h23m45s3ms see TOD
204
TOD
Glossary
TOD is the abbreviation of Time of Day.
The TOD type coded in BCD in 32 bit format contains the following information: z the hour coded in a 8-bit field, z z the minutes coded in an 8-bit field, the seconds coded in an 8-bit field.
Token
TOPO_ADDR_TY
PE
Note: The 8 least significant bits are unused.
The Time of Day type is entered as follows: TOD# <Hour> : <Minutes> : <Seconds>
This table shows the lower/upper limits in each field:
Field
Hour
Minute
Second
Limits
[00,23]
[00,59]
[00,59]
Comment
The left 0 is always displayed, but can be omitted at the time of entry
The left 0 is always displayed, but can be omitted at the time of entry
The left 0 is always displayed, but can be omitted at the time of entry
Example: TOD#23:59:45 .
An active step of an SFC is known as a token.
This predefined type is used as output for READ_TOPO_ADDR function. This type is an ARRAY[0..4] OF Int. You can find it in the libset, in the same family than the
EFs which use it.
U
UDINT
UINT
UDINT is the abbreviation of Unsigned Double Integer format (coded on 32 bits) unsigned. The lower and upper limits are as follows: 0 to (2 to the power of 32) - 1.
Example:
0 , 4294967295 , 2#11111111111111111111111111111111 , 8#37777777777 ,
16#FFFFFFFF .
UINT is the abbreviation of Unsigned integer format (coded on 16 bits). The lower and upper limits are as follows: 0 to (2 to the power of 16) - 1.
Example:
0 , 65535 , 2#1111111111111111 , 8#177777 , 16#FFFF .
205
Glossary
Unlocated variable
An unlocated variable is a variable for which it is impossible to know its position in the PLC memory. A variable which have no address assigned is said to be unlocated.
V
Variable Memory entity of the type BOOL , WORD , DWORD , etc., whose contents can be modified by the program during execution.
W
WORD The WORD type is coded in 16 bit format and is used to carry out processing on bit strings.
This table shows the lower/upper limits of the bases which can be used:
Base
Hexadecimal
Octal
Binary
Lower limit
16#0
8#0
2#0
Upper limit
16#FFFF
8#177777
2#1111111111111111
Representation examples
Data content
0000000011010011
1010101010101010
0000000011010011
Representation in one of the bases
16#D3
8#125252
2#11010011
206
Index
Symbols
Numerics
A
adapters
addresses
application programs, 112, 131, 157, 160
A C
B
backplanes
blinking indicators, 26, 133, 134, 187
buttons
C
cables
checksums
transferring, 131 validating, 131
clasps
207
Index clocks
commands
Copro link, 130 monitor RIO, 130
communications
compatibility
components
configurations
CRAs
CRPs
D
diagnostics
208 diagrams
drops
E
errors
F
failures
dual cables, 133, 134 fiber links, 62, 134
high-speed data links (HSDL), 126
G
H
health messages, 120, 121, 126
I
indicators
K
L
LCDs
limits
logic mismatches, 114, 142, 146
logs
M
menus
messages
mismatches
modes
modifications, 146, 156 offline, 151, 156 online, 149, 150, 156
modules
monitor RIO commands, 130 monitor RIO requests, 130
multiple transfer packets, 161
N
Index
209
Index
not healthy communications, 130
O
offsets, 90 network addresses, 90
order
P
packets
Primary controllers
programs
R
requests
Copro link, 130 monitor RIO, 130
restrictions
210
S
scan times, 49, 50, 110, 120, 121, 123, 124,
sections
setup methods
splitters
Standby controllers
state RAM, 48, 49, 71, 78, 143
states
static data memory layout, 143
steady off indicators, 26 steady on indicators, 26
submenus
T
tabs
tests
of the Copro, 120 run time, 120
U
unlocated variables, 48, 71, 111, 114
updating
Upload Information Management, 156
Index
V
values
redeclared, 145 section, 145 transition, 145
unlocated, 48, 71, 111, 114, 144
W
warnings
Immediate Control of Process, 148, 152
211
Index
212
دانلود