Schneider Electric PL7 Junior/Pro - Premium PLC Applications - Analog, Regulation PID, Weighing User Guide
Annonce
Annonce
PL7 Junior/Pro
Premium PLC Applications
Analog, Regulation PID, Weighing
TLX DS 57 PL7 xx eng
2
Related Documentation
At a Glance This manual is made up of 8 volumes: l l
Volume 1 l l
Common application specific functions
Discrete Application l AS-i Implementation l Operator Dialog Application
Volume 2 l l Counting Application
Volume 3 l l l Axis Command Application
Volume 4 l Step by Step Control Application
Volume 5 l l Electronic Cam Application
Volume 6 l l l SERCOS(r) Movement Command Application
Volume 7 l Analog Application l PID Control Application l Weighing Application
Volume 8 l Regulation Application
Related Documentation
TLX DS 57 PL7 xxE
3
Related Documentation
4
TLX DS 57 PL7 xx
Table of Contents
About the book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Part I
Analog task function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 1
The analog task. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chapter 2
The racked analog modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.1
TSX AEY 800 and TSX AEY 1600 modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Introducing the TSX AEY 800 and TSX AEY 1600 modules. . . . . . . . . . . . . . . . 21
Calibration of the TSX AEY 800 and TSX AEY 1600 modules . . . . . . . . . . . . . . 31
2.2
2.3
Sensor alignment for the TSX AEY 1614 module . . . . . . . . . . . . . . . . . . . . . . . . 52
5
6
2.4
Sensor alignment for the TSX AEY 414 module . . . . . . . . . . . . . . . . . . . . . . . . . 65
Cold junction compensation of the TSX AEY 414 module. . . . . . . . . . . . . . . . . . 66
2.5
Sensor alignment for the TSX AEY 420 module . . . . . . . . . . . . . . . . . . . . . . . . . 78
2.6
TSX ASY 410 and TSX ASY 800 modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Monitoring under/overshoots for the TSX ASY 410 module . . . . . . . . . . . . . . . . 83
Behavior of the TSX ASY 410 module outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Monitoring under/overshoots for the TSX ASY 800 module . . . . . . . . . . . . . . . . 89
Behavior of the outputs of the TSX ASY 800 module . . . . . . . . . . . . . . . . . . . . . 90
Chapter 3
The remote analog TBX modules . . . . . . . . . . . . . . . . . . . . . . . 91
3.1
3.2
Monitoring under/overshoots on the TBX AMS 620 module outputs . . . . . . . . 114
3.3
Output characteristics for the TBX ASS 200 module . . . . . . . . . . . . . . . . . . . . 120
Monitoring under/overshoots for the TBX ASS 200 module . . . . . . . . . . . . . . . 122
Chapter 4
The remote analog Momentum modules . . . . . . . . . . . . . . . . 123
4.1
4.2
Displaying measurements on the 170 AAI 140 00 module . . . . . . . . . . . . . . . . 132
4.3
Displaying measurements on the 170 AAI 520 40 module . . . . . . . . . . . . . . . . 140
4.4
Measurement correspondence on the 170 AAO 120 00 module . . . . . . . . . . . 145
4.5
Measurement correspondence on the 170 AAO 921 00 module . . . . . . . . . . . 150
4.6
Introduction to the 170 AAM 090 00 module . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Displaying measurements in the module 170 AMM 090 00 . . . . . . . . . . . . . . . 156
7
8
Chapter 5
Module configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
5.1
Description of the configuration screen of a racked TBX analog module . . . . . 163
Description of the configuration screen of a Momentum analog module . . . . . . 165
How to access the configuration parameters of a racked analog module . . . . . 167
How to access the configuration parameters of a remote analog module on the
Modifying channel parameters of an analog module: General . . . . . . . . . . . . . 170
5.2
Input parameters for racked analog modules . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Input parameters for remote TBX analog modules . . . . . . . . . . . . . . . . . . . . . . 176
Input parameters for remote Momentum analog modules . . . . . . . . . . . . . . . . . 177
5.3
Output parameters for racked analog modules . . . . . . . . . . . . . . . . . . . . . . . . . 179
Output parameters for remote TBX analog modules . . . . . . . . . . . . . . . . . . . . . 180
Output parameters for remote Momentum analog modules . . . . . . . . . . . . . . . 181
5.4
Modifying the range of an input or output of an analog module. . . . . . . . . . . . . 183
Modifying the task associated to an analog module channel. . . . . . . . . . . . . . . 184
Modifying the display format of an input channel as voltage or as current . . . . 185
Modifying display format of a thermocouple or thermowell channel . . . . . . . . . 187
Modifying the filter value of analog module channels . . . . . . . . . . . . . . . . . . . . 189
Modifying the Scanning cycle of the inputs of a racked analog module . . . . . . 190
Modifying terminal block presence detection in TSX and TBX analog modules 191
Modifying overshoot monitoring and event processing selection. . . . . . . . . . . . 193
High precision mode for TSX AEY 1614 module . . . . . . . . . . . . . . . . . . . . . . . . 195
Modifying the fallback mode of analog outputs . . . . . . . . . . . . . . . . . . . . . . . . . 196
Modifying parameters common to TBX or TSX output modules . . . . . . . . . . . . 197
Chapter 6
The Debugging function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Introducing the Debugging Function of an analog module . . . . . . . . . . . . . . . . 200
Description of an analog module debugging screen . . . . . . . . . . . . . . . . . . . . . 201
Chapter 7
Associated bits and words . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
7.1
Addressing objects of analog rack module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Addressing objects of remote analog modules . . . . . . . . . . . . . . . . . . . . . . . . . 221
7.2
Implicit exchange objects associated with the analog function . . . . . . . . . . . . . 223
7.3
Explicit exchange objects associated with outputs . . . . . . . . . . . . . . . . . . . . . . 227
Details on analog function explicit exchange words . . . . . . . . . . . . . . . . . . . . . 230
Part II
The regulation functions . . . . . . . . . . . . . . . . . . . . . . . . 233
Chapter 8
General on the PID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Development methodology of a regulation application . . . . . . . . . . . . . . . . . . . 238
Chapter 9
Description of the regulation functions . . . . . . . . . . . . . . . . . 239
Performance of the functions in the operating mode. . . . . . . . . . . . . . . . . . . . . 258
Chapter 10
Operator dialogue on CCX 17 . . . . . . . . . . . . . . . . . . . . . . . . . 259
Performance of the PID_MMI function according to the PLC and CCX 17’s operating
9
10
Chapter 11
Characteristics of the functions . . . . . . . . . . . . . . . . . . . . . . . 271
Chapter 12
Example of application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 275
Chapter 13
Appendices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Part III
Weighing Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Chapter 14
General Introduction to the Weighing Dedicated Function . 295
Chapter 15
Configuration of the Weighing application . . . . . . . . . . . . . . 305
Description of the Dedicated Weighing Function Configuration Screen . . . . . . 306
Weighing Module Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
How to Modify Measurement Input Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Chapter 16
Weighing programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
16.1
Principle of programming a weighing application. . . . . . . . . . . . . . . . . . . . . . . . 323
Addressing Language Objects Associated with the Weighing Module . . . . . . . 324
Description of the Main Objects Linked to the Weighing Function . . . . . . . . . . 325
16.2
Language objects for programmed exchange. . . . . . . . . . . . . . . . . . . . . . . . . . 329
Bit language objects for default exchange associated with the weighing function
Implicit Exchange Language Word Objects Associated with the Weighing
16.3
Language objects for user-defined exchange . . . . . . . . . . . . . . . . . . . . . . . . . . 333
Explicit Exchange Objects: Current Exchange and Report . . . . . . . . . . . . . . . . 336
Object for user-defined exchange: Module Status %MWxy.MOD.2 . . . . . . . . . 337
Explicit Exchange Object: %MWxy.0.2 status channel . . . . . . . . . . . . . . . . . . . 338
Explicit Exchange Object: Command Word %MWxy.0.3 . . . . . . . . . . . . . . . . . 339
16.4
Description of the commands conveyed by program . . . . . . . . . . . . . . . . . . . . 340
Send Commands to Weighing Module by Program . . . . . . . . . . . . . . . . . . . . . 341
How to carry out the tare mode via the program . . . . . . . . . . . . . . . . . . . . . . . . 342
How to set to zero the value of the weight by the program . . . . . . . . . . . . . . . . 345
How to return to gross weight measurement via the program. . . . . . . . . . . . . . 347
How to display the manual tare via the program . . . . . . . . . . . . . . . . . . . . . . . . 348
How to Enable or Disable Thresholds by Program . . . . . . . . . . . . . . . . . . . . . . 349
16.5
Description of Parameters Adjustable by Program . . . . . . . . . . . . . . . . . . . . . . 356
Chapter 17
Calibrating the measurement string . . . . . . . . . . . . . . . . . . . 361
Calibrating the Analog Measurement System . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Calibrating the Analog Measurement System by Program . . . . . . . . . . . . . . . . 367
Performing a Forced Calibration by Program . . . . . . . . . . . . . . . . . . . . . . . . . . 370
Chapter 18
Debugging the weighing function. . . . . . . . . . . . . . . . . . . . . . 371
Description of the Debugging Screen for the Dedicated Weighing Function . . 372
Description of the module zone on the debugging screen . . . . . . . . . . . . . . . . 374
Description of the weighing debug screen’s display zone. . . . . . . . . . . . . . . . . 376
Description of the Parameter Adjustment Zone . . . . . . . . . . . . . . . . . . . . . . . . 377
11
12
Chapter 19
Protecting the adjustments. . . . . . . . . . . . . . . . . . . . . . . . . . . 379
Protection of the Adjustments to Weighing Parameters . . . . . . . . . . . . . . . . . . 380
Chapter 20
Operating a weighing application . . . . . . . . . . . . . . . . . . . . . 385
Chapter 21
Diagnostics of the weighing application . . . . . . . . . . . . . . . . 391
Chapter 22
Examples of the weighing program . . . . . . . . . . . . . . . . . . . . 395
Glossary
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 401
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407
About the book
At a Glance
Document Scope This manual deals with the software implementation of applications (apart from communication applications) on TSX/PMX/PCX57 by the PL7 software.
Validity Note The update of this publication takes into account the functions of PL7 V4.3.
Nevertheless, it enables you to use earlier versions of PL7.
Related
Documents
Title of Documentation
Hardware Implementation Manual
Reference Number
TSX DM 57 xx E
User Comments We welcome your comments about this document. You can reach us by e-mail at
TLX DS 57 PL7 xxE
13
About the book
14
TLX DS 57 PL7 xxE
Analog task function
I
At a Glance
Aim of this part
What's in this part?
This part introduces the analog task function on Premium PLCs and describes its implementation withPL7 software.
This Part contains the following Chapters:
Chapter
1
2
3
6
7
4
5
Chaptername
The analog task
The racked analog modules
The remote analog TBX modules
The remote analog Momentum modules
Module configuration
The Debugging function
Associated bits and words
Page
15
TLX DS 57 PL7 xxE
Analog task function
16
TLX DS 57 PL7 xxE
The analog task
1
Introduction to the analog function
Introduction The analog function applies to: l l analog input/output modules placed on a rack, remote analog input/output modules on the FIPIO bus.
Note: To access the latter, the configured processor must be a processor with a built-in FIPIO link.
Installing the analog function requires the physical operating context to be defined in which it will be integrated (e.g. rack, supply, processor, modules or devices, etc.), and then the software installation to be carried out.
This second point is carried out by various PL7 editors: l l either offline, or in online mode; in this instance, modification is limited to certain parameters.
Note: Online mode functions cannot be accessed for remote input/output modules.
17
TLX DS 57 PL7 xxE
Analog task
Installation principle
Mode
Offline
On- or offline
Online
On- or offline
The table below shows the different installation phases for the analog function.
Phase
Module declaration
Configuration
Confirming configuration parameters
Global application confirmation
Symbolization
Description
Choice: l of geographical position, l number and slot in the case of racked module, l l connection point for a remote module, module type.
Entering configuration parameters.
Confirmation at module level.
Confirmation at application level.
Programming
Transfer
Debugging
Calibration
Documentation
Symbolizing the variables associated with the application specific function.
Programming the functions that the specific function must carry out using: l l word and bit objects associated with the module, task-specific instructions.
Transferring the application to the PLC.
Debugging the application using: l debug help screens, allowing inputs and outputs to be controlled, l diagnostics screens, allowing faults to be identified.
Module calibration, which allows: l l long term module drifts to be corrected, increased measurement accuracy.
Printing different information relating to the application.
Note: The order defined above is given as an indication. The PL7 software can use editors interactively in any order you wish (however you cannot use the data or program editors without first configuring the input/output modules).
18
TLX DS 57 PL7 xxE
The racked analog modules
2
At a Glance
Aim of this chapter?
What's in this
Chapter?
This chapter introduces the racked analog modules.
This Chapter contains the following Sections:
Section
2.1
2.2
2.3
2.4
2.5
2.6
Topic
TSX AEY 800 and TSX AEY 1600 modules
TSX AEY 810 Module
TSX AEY 1614 Module
TSX AEY 414 Module
TSX AEY 420 Module
TSX ASY 410 and TSX ASY 800 modules
Page
TLX DS 57 PL7 xxE
19
Racked analog modules
2.1
TSX AEY 800 and TSX AEY 1600 modules
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TSX AEY 800 and TSX AEY 1600 rack modules.
This Section contains the following Maps:
Topic
Introducing the TSX AEY 800 and TSX AEY 1600 modules
Timing of measurements
Monitoring under/overshoot
Measurement filtering
Displaying measurements
Sensor alignment
Calibration of the TSX AEY 800 and TSX AEY 1600 modules
Page
20
TLX DS 57 PL7 xxE
Racked analog modules
Introducing the TSX AEY 800 and TSX AEY 1600 modules
General
Structural diagram
The TSX AEY 800 and TSX AEY 1600 modules are high level 8 /16 input devices for industrial measurement.
Associated to sensors or transmitters, they support surveillance, measurement and regulation functions for continuous processes.
The TSX AEY 800 and TSX AEY 1600 modules support the range +/-10 V, 0..10 V,
0..5 V, 1..5 V, 0..20 mA or 4..20 mA for each of their inputs, depending on the selection made in configuration (See Modifying the range of an input or output of an
The debugging screen displays the value and status for each channel in the selected module in real-time. It also enables the user to access channel command (forcing the input or output value, reactivation of outputs, etc.).
The TSX ASY 800 and TSX AEY 1600 input modules support the following functions:
Channel selection Optocoupler
Multiplexer A/D
Optocoupler
Processing
X bus
Interface
1000
Vrm s
Function
1 2 3
DC/DC
Converter
4
7
5 V
5
6
TLX DS 57 PL7 xxE
21
Racked analog modules
Description The table below shows the various functions
Address Element
1
2
3
Function
Connection to the process and scanning of input channels l l l l physical connection to the process, via SubD connector(s), protection of the module against voltage surges using limiter diodes, adapting input signals using analog filtering, scanning input channels using static multiplexing.
Adapting input signals l gain selection, based on the input signal characteristics, defined at configuration (unipolar or bipolar range, voltage or current), l compensation for drifts in the amplification string.
l 12 bit analog/digital converter.
Digitalization of analog input measurement signals
4
5 transformation of input measurements into a unit that can be used by the user l l
Interface and communication with the application l l l l l acknowledgment of recalibration and alignment coefficients to be applied to measurements, as well as self-calibration coefficients for the module, measurement filtering (digital filtering), based on configuration parameters, scaling of measurements, based on configuration parameters.
management of exchanges with the processor, geographical addressing, receiving module and channel configuration parameters, transmitting measured values, as well as module status, to the application.
6
7
Module power supply -
Module monitoring and notification of possible errors to the application l l l l testing conversion string, testing for range under/overshoot on channels, testing for presence of terminal block, testing watchdog.
22
TLX DS 57 PL7 xxE
Racked analog modules
Timing of measurements
At a Glance The timing of measurements depends on the cycle used, defined on configuration: l l normal cycle or fast cycle.
in normal cycle, the scanning cycle time is fixed, in fast cycle, only channels registered as used are scanned. The scanning cycle time is therefore proportional to the number of channels registered as used.
Note: In fast cycle, filtering is inhibited
Channel scanning cycle
The scanning cycle of channels used in normal cycle is as follows:
Channel 0
Tv
Channel 1
Tv
Channel 7 (or 15)
Tv
Internal ref.
Tv
Cycle time
Tv = scanning time for one channel
Internal ref. = corresponds to the acquisition of voltage references built-in to the module, to allow periodic self-calibration
The scanning cycle of channels used in fast cycle is as follows:
Example for channels 3, 5, 6
Channel 3
Tv
Channel 5
Tv
Channel 6
Tv
Internal ref.
Tv
Cycle time = (3+1)xTv
Tv = scanning time for one channel
Internal ref. = corresponds to the acquisition of voltage references built-in to the module, to allow periodic self-calibration
TLX DS 57 PL7 xxE
23
Racked analog modules
Calculating cycle time
The table below gives the values of cycle time according to the cycle used:
Module
TSX AEY 800
TSX AEY 1600
Normal cycle
27 ms
51 ms
Fast cycle
(N+1) x 3 ms l where N = number of channels used.
(N+1) x 3 ms l where N = number of channels used.
Note: The module cycle is asynchronous with the PLC cycle. At the start of each
PLC cycle, the channel values are recognized. If the cycle time of the MAST task is less than that of the module, some values will not have changed.
Illustration:
Module processing time
MAST task time changes of the channel values
24
TLX DS 57 PL7 xxE
Racked analog modules
Monitoring under/overshoot
At a Glance
Measurement zones
The TSX AEY 800 and TSX AEY 1600 modules give the choice of 6 ranges of voltage or current for each of their inputs. For the selected range, the module monitors over/undershoot: it checks that the measurement is between a lower and upper limit.
This check is always enabled.
Generally speaking, the modules will authorize an over/undershoot by 5% of the positive electrical part of the range.
The measurement scale is divided into three zones: undershoot zone nominal zone overshoot zone lower limit upper limit l l l the nominal zone is the measurement scale that corresponds to the range selected, the overshoot zone is the zone above the upper limit, the undershoot zone is the zone below the lower limit.
Over/undershoot indications
In the over/undershoot zones, there is a risk of saturation of the measurement string
, which is signaled by:
Bit name
%Ixy.i.ERR
%MWxy.i.2:X1
Meaning (when = 1)
Channel fault
Range over/undershoot on the channel
TLX DS 57 PL7 xxE
25
Racked analog modules
Over/Undershoot limits
Range
+/-10V
0..10V
0..5V
1..5V
0..20mA
4..20mA
+3.2mA
The over/undershoot limit values are as follows:
Lower limit Lower limit Values available by default in standardized format
-10.5V
-0.5V
+10.5V
+10.5V
+/- 10500
-500...10500
0V
0.8V
0mA
+5.25V
+5.25V
+21mA
-500...10500
-500...10500
0...10500
+20.8mA
-500...10500
Minimum limit in userdefined format
Maximum limit in userdefined format
Min-5%x(Max-Min)/2
Min-5%x(Max-Min)/2 approx. -10mV
Min-5%x(Max-Min)/2 approx. -40
µ
A
Min-5%x(Max-Min)/2
Max+5%x(Max-Min)/2
Max+5%x(Max-Min)/2
Max+5%x(Max-Min)/2
Max+5%x(Max-Min)/2
Max+5%x(Max-Min)/2
Max+5%x(Max-Min)/2
Note: Min designates the minimum value indicated by the user. Max designates the maximum value indicated by the user.
26
TLX DS 57 PL7 xxE
Racked analog modules
Measurement filtering
At a Glance
Mathematical formula
The filtering used is first order filtering.
The filtering coefficient can be modified (See Modifying the channel filtering value,
p. 208) from the PL7 screen or via the program.
The mathematical formula used is as follows :
Mesf n = α × ( – 1 ) + ( 1 – α ) × Valb n with:
α =filter efficiency,
Mesf(n)=measurement filtered at moment n,
Mesf(n-1)=measurement filtered at moment n-1,
Valb(n)=gross value at moment n.
At configuration, the user selects the filter value from 7 possible values. This value can be modified, even when the application is in RUN mode .
Note: Filtering is inhibited in fast cycle mode
Values for the
TSX AEY 800 module
The filter values are as follows:
Required efficiency
No filtering
Low filtering
Medium filtering 3
4
High filtering 5
6
0
1
2
Value to be selected
α
corresponding
0
0,750
0,875
0,937
0,969
0,984
0,992
Filter response time at 63%
Cut-off frequency
(Hz)
0
100 ms
202 ms
0
1,591
0,788
419 ms
851 ms
1,714 ms
3,442 ms
0,379
0,187
0,093
0,046
TLX DS 57 PL7 xxE
27
Racked analog modules
Values for the
TSX AEY 1600 module
The filter values are as follows:
Required efficiency
No filtering
Low filtering
Medium filtering 3
4
High filtering 5
6
0
1
2
Value to be selected
α
corresponding Filter response time at 63%
Cut-off frequency
(Hz)
0
0,750
0,875
0,937
0,969
0,984
0,992
0
178 ms
382 ms
791 ms
1,607 s
3,239 s
6,502 s
0
0,894
0,416
0,201
0,099
0,049
0,024
28
TLX DS 57 PL7 xxE
Racked analog modules
Displaying measurements
At a Glance
Standardized display
The measurement provided to the application can be applied directly by the user, l l who can choose between: using standardized display 0..10000 (or +/-10000 for the range +/-10 V), parameterizing his display format by indicating the minimum and maximum values required.
The values are displayed in standardized units (in % with 2 decimals, also symbolized °/
°°°
):
Type of range Display unipolar range:
0-10V, 0-5V, 0-20mA, 4-20mA bipolar range:
+/-10V from 0 to 10000 (0 °/
°°°
to 10000 °/ from -10000 to +10000 (-10000 °/
°°°
°°°
)
to +10000 °/
°°°
)
User-defined display
The user can select the value scale (See Modifying the display format of an input
channel as voltage or as current, p. 185) in which the measurements are expressed,
by selecting: l the minimum limit corresponding to the range minimum 0 °/
°°°
(or -10000 °/
°°°
), l the maximum limit corresponding to the range maximum (+ 10000 °/
°°°
).
These minimum and maximum limits are integers within the range – 30000 and +
30000.
Example:
Let us suppose that a conditioning unit indicates pressure information on a 4-20mA loop, with 4mA corresponding to 3200 mB and 20mA corresponding to 9600 mB.
The user can, therefore, select the user-defined format (User), defining the following minimum and maximum limits:
3200 °/
°°°
for 3200 mB as minimum limit,
9600 °/
°°°
for 9600 mB as maximum limit,
Values sent to the program will change between 3200 (= 4 mA) and 9600 (= 20 mA).
The corresponding values are as follows:
Value transmitted to the program
Value of current
3200 current value
9600
4 mA between 4 and 20mA
20 mA
Value of pressure
3200 mB current value
9600 mB
TLX DS 57 PL7 xxE
29
Racked analog modules
Sensor alignment
At a Glance Alignment consists of eliminating systematic deviation observed with a given sensor around a given operating point. An error linked to the process is compensated for.
For this reason, replacing a module does not necessitate a new alignment, whereas the replacement of the sensor or modification of the operating point of this sensor does necessitate a new alignment.
Conversion line after alignment
Initial conversion line
Example
Alignment values
Let us suppose that a pressure sensor, linked to a conditioning unit (1mV/mB), indicates 3200 mB, whereas the actual pressure is 3210 mB.
The value measured by the module in standardized scale will be 3200 (3.20 V). The user can align the measurement to the value 3210 (value required).
After this alignment procedure, the measurement channel will apply a systematic offset of +10. The alignment value that must be entered is 3210.
The alignment value can be modified (See
Aligning an input channel, p. 210) from
the PL7 screen, even when the program is in RUN mode.
For each input channel, the user can: l l l view and modify the required measurement value, save the alignment value, see if the channel already possesses an alignment.
The alignment offset can also be modified by the program.
Alignment is performed on the channel under normal usage, without affecting the module channel operating modes. The maximum difference between the value measured and the value required (aligned value) must not exceed 1000.
The alignment offset is stored in the word %Mwxy.i.8.
30
TLX DS 57 PL7 xxE
Racked analog modules
Calibration of the TSX AEY 800 and TSX AEY 1600 modules
At a Glance
Precautions
Calibration (See
Calibration function for an analog module, p. 213) is performed
globally for the module on channel 0. It is advisable to calibrate the module outside the application. Calibration can be performed with the PLC task linked to the channel in RUN or STOP modes.
When in calibration mode, measurements for all channels in the module are declared invalid (%Ixy.i.ERR bit = 1), filtering and alignment is prevented and channel acquisition cycles may be lengthened.
As inputs other than channel 0 will not be acquired during calibration, the value transmitted to the application for these other channels is the last value that was measured before switching to calibration.
Procedure
Step
1
2
3
4
5
6
7
The following table gives the procedure for calibrating the module:
Action
Access the calibration adjustment screen.
Double click on channel 0.
Result : A question appears ‘Do you wish to switch to recalibration mode?’.
Reply to this question with Yes .
Result : The calibration window appears.
According to the range to be calibrated, connect a reference voltage to the voltage input of channel 0: l reference voltage = 10 V (20 ppm precision) in order to calibrate the module on the +/-10 V and 0..10
V ranges, l reference voltage = 5 V (20 ppm precision) in order to calibrate the module on the 0..5 V, 1..5 V, 0..20 mA and 4..20 mA ranges.
Caution: the 5 V reference is used to calibrate the whole measurement device for the 0..20 mA and 4..20 mA ranges, with the exception of the 250 Ohm current shunt situated on the current entry.
Once the reference has been connected to the voltage input (e.g. 10 V), use the Reference drop-down list box to slect this value. Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the Confirm command button. The ranges linked to this reference (e.g. +/-
10 V and 0..10 V) are then calibrated automatically.
Calibrate the module for other ranges, if applicable.
the Return to Factory Parameters command button cancels all previous calibrations, and return to the original calibration settings configured in the factory.
Press the Save command button, in order to recognize and save the new calibration in the module. If you exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost.
TLX DS 57 PL7 xxE
31
Racked analog modules
2.2
TSX AEY 810 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TSX AEY 810 rack-based module.
This Section contains the following Maps:
Topic
Introducing the TSX AEY 810 module
Timing of measurements
Monitoring under/overshoot
Measurement filtering
Displaying measurements
Calibrating the TSX AEY 810 module
Page
32
TLX DS 57 PL7 xxE
Racked analog modules
Introducing the TSX AEY 810 module
General
Structural diagram
TSX AEY 810
The TSX AEY 810 module is a high level 8 input industrial measurement device.
Associated to sensors or transmitters, it is used for monitoring, measuring and regulating continuous processes.
The TSX AEY 810 module offers the range +/-10 V, 0..10 V, 0..5 V, 1..5 V, 0..20 mA or 4..20 mA for each of its inputs, according to the selection made in configuration
(See
Modifying the range of an input or output of an analog module, p. 183).
The debugging screen displays the value and status for each channel of the selected module in real-time. It also enables the user to access the channel command (forcing the input or output value, reactivation of outputs, etc.).
The TSX AEY 810 input module supports the following functions:
1000 Vrms insulation
Channel selection
Optocoupler
Filter
A/D
Optocoupler
Processing
X bus
Interface
Filter
1 2 3
7
DC/DC
Converter
4
5 V
5
6
TLX DS 57 PL7 xxE
33
Racked analog modules
Description The table below shows the various functions :
Address
1
2
3
4
5
6
7
Element
Connection to process and scanning of input channels
Adapting input signals
Digitalization of analog input measurement signals
Transformation of input measurements into a unit that can be used by the user
Interface and communication with the application
Module power supply
Module monitoring and notification of possible errors to the application l l
Function l l l l l l physical connection to the process, via SubD connector(s), protection of the module against voltage surges using limiter diodes, adapting input signals using analog filtering, scanning input channels using static multiplexing, inter-channel isolation assured by optical connectors.
gain selection, based on the input signal characteristics, defined at configuration
(unipolar or bipolar range, voltage or current), compensation for drifts in the amplification string.
16 bit analog/digital converter.
l l l acknowledgment of recalibration and alignment coefficients to be applied to measurements, as well as self-calibration coefficients for the module, filtering (digital filtering) of measurements, based on configuration parameters, scaling of measurements, based on configuration parameters.
l l l l
management of exchanges with the processor, geographical addressing, receiving module and channel configuration parameters, transmitting measured values, as well as module status, to the application.
l l l l testing conversion string, testing for range under/overshoot on channels, testing for presence of terminal block, testing watchdog.
34
TLX DS 57 PL7 xxE
Racked analog modules
Timing of measurements
At a Glance The timing of measurements depends on the cycle used, defined at configuration l l
(See
Modifying the Scanning cycle of the inputs of a racked analog module, p. 190) :
normal cycle or fast cycle.
in normal cycle, the scanning cycle time is fixed, in fast cycle, only channels registered as used are scanned. The scanning cycle time is therefore proportional to the number of channels registered as used.
Note: In fast cycle, filtering is inhibited
Channel scanning cycle
The scanning cycle of channels used in normal cycle is as follows:
Channel 0
Tv
Channel 1
Tv
Channel 7 (or 15)
Tv
Internal ref.
Tv
Cycle time
Tv = scanning time for one channel
Internal ref. = corresponds to the acquisition of voltage references built-in to the module, to allow periodic self-calibration
The scanning cycle of channels used in fast cycle is as follows:
Example for channels 3, 5, 6
Channel 3
Tv
Channel 5
Tv
Channel 6
Tv
Internal ref.
Tv
Cycle time = (3+1)xTv
Tv = scanning time for one channel
Internal ref. = corresponds to the acquisition of voltage references built-in to the module, to allow periodic self-calibration
TLX DS 57 PL7 xxE
35
Racked analog modules
Calculating cycle time
The table below gives the values of cycle time according to the cycle used:
Module Normal cycle Fast cycle
TSX AEY 810 29.7 ms (N+1) x 3.3 ms l where N = number of channels used.
Note: The module cycle is asynchronous with the PLC cycle. At the start of each
PLC cycle, the channel values are recognized. If the cycle time of the MAST task is less than that of the module, some values will not have changed.
Illustration:
Module processing time
MAST task time changes of the channel values
36
TLX DS 57 PL7 xxE
Racked analog modules
Monitoring under/overshoot
At a Glance
Measurement zones
The TSX AEY 810 module provides a choice of 6 voltage or current ranges for each of its inputs. For the selected range, the module monitors over/undershoot: it checks that the measurement is between a lower and upper limit.
This check is optional.
Generally speaking, the module will authorize an overshoot of 5% on the positive electrical part of the range.
The measurement scale is divided into five zones :
Lower limit
Lower value in range
Upper value in range Upper limit l l l l l undershoot zone lower tolerance zone nominal zone upper tolerance zone overshoot zone the nominal zone is the measurement scale that corresponds to the range selected, the upper tolerance zone contains the values between the upper value of the range (e.g.: +10V for a range -10V/+10V) and the upper limit, the lower tolerance zone contains the values between the lower value of the range (e.g.: -10V for a range -10V/+10V) and the lower limit, the overshoot zone is the zone above the upper range limit, the undershoot zone is the zone below the lower range limit.
Over/undershoot indications
In the over/undershoot zones, there is a risk of measurement device saturation. To overcome this risk of the user program, error bits are provided:
Bit name
%IWxy.i.1:X5
%IWxy.i.1:X6
%MWxy.i.2:X1
%Ixy.i.ERR
Meaning (when = 1)
Measurement in the lower tolerance zone.
Measurement in the upper tolerance zone.
If over/undershoot monitoring is required, this bit signals an over/undershoot fault in the range: l l
%MWxy.i.2:X14 signals an undershoot,
%MWxy.i.2:X15 signals an overshoot.
Channel fault.
TLX DS 57 PL7 xxE
Note: If an over/undershoot occurs, the value measured is limited to value of the corresponding limit.
37
Racked analog modules
Over/undershoot limit values
The overshoot or undershoot values can be configured (See Modifying overshoot
monitoring and event processing selection, p. 193) independently of each other.
They can take integer values between the following values:
Lower limit = Vinf range + lower tolerance zone
Upper limit = Vsup range + upper tolerance zone
The table below gives the values of the tolerance zones for the different ranges:
Range
-
Bipolar
Lower tolerance zone
Default value Max. value
-0.125 x
∆ gamme /2
0
0 Unipolar -0.125 x
∆ gamme
Standardize d Bipolar
-1250 0
Min. value
-0.25 x
∆ gamme /2
-0.25 x
∆ gamme
-2500
Upper tolerance zone
Default value Min. value
-0.125 x
∆ gamme /2
0.125 x
∆ gamme
1250
Standardize d Unipolar
-1250
Userdefined
Bipolar
-0.125 x
∆ gamme /2
0
0
-2500
-0.25 x
∆ gamme /2
1250
0.125 x
∆ gamme /2
Userdefined
Unipolar
-0.125 x
∆ gamme
0 -0.25 x
∆ gamme
With
∆ gamme = Upper range value - Lower range value,
0.125 x
∆ gamme
0
0
0
0
0
0
Max. value
0.25 x
∆ gamme /2
0.25 x
∆ gamme
2500
2500
0.25 x
∆ gamme /2
0.25 x
∆ gamme
Note: l The bipolar range is range +/-10V, the unipolar ranges are ranges 0..20mA,
0..10V, 0..5V, 1..5V, 4..20mA, l By default, overshoot monitoring is active but it can be partially activated (only for overshoots or undershoots) or deactivated.
38
TLX DS 57 PL7 xxE
Example
20 mA 24 mA
Racked analog modules
Overshoot for the range 4..20mA in standardized mode on channel 0
Lower limit : -1250 (2mA) Upper limit = 10625 (21mA)
0 mA 4 mA
1 2 3
Measurement range
Range measurable electronically
4 5
%MWxy.0.2:X1
%MWxy.0.2:X14
%MWxy.0.2:X15
%IWxy.0.1:X5
%IWxy.0.1:X6
%Ixy.0.ERR
Upper limit:
10625
10000
Lower limit:
0
-1250
2 mA 4 mA
1.
Undershoot zone
2.
Lower tolerance zone
3.
Nominal zone
4.
Upper tolerance zone
5.
Overshoot zone
20 mA 21 mA
TLX DS 57 PL7 xxE
39
Racked analog modules
Measurement filtering
At a Glance
Mathematical formula
The filtering used is first order filtering. The filter coefficient can be modified from a programming terminal and by program (See Modifying the filter value of analog
The mathematical formula used is as follows :
Mesf n = α × ( – 1 ) + ( 1 – α ) × Valb n with:
α =filter efficiency,
Mesf(n)=measurement filtered at moment n,
Mesf(n-1)=measurement filtered at moment n-1,
Valb(n)=gross value at moment n.
At configuration, the user selects the filter value from 7 possible values. This value can be changed, even when the application is in RUN mode .
Note: Filtering is inhibited in fast cycle mode.
Values for the
TSX AEY 810 module
The filter values are as follows: .
Required efficiency
No filtering
Low filtering
Medium filtering
High filtering
3
4
5
6
0
1
2
Value to be selected
α
corresponding
0
0,750
0,875
0,937
0,969
0,984
0,992
Filter response time at 63% cut-off frequency (Hz)
0
104.3 ms
224.7 ms
0
1,526
0,708
464.8 ms
944.9 ms
1,905 ms
3,825 ms
0,342
0,168
0,084
0,042
40
TLX DS 57 PL7 xxE
Racked analog modules
Displaying measurements
Introduction
Standardized display
The measurement provided to the application can be applied directly by the user, l l who can choose (See Modifying the display format of an input channel as voltage or
using standardized display 0..10000 (or +/-10000 for the range +/-10 V), creating parameters for its display format by indicating the minimum and maximum values required.
The values are displayed in standardized units (in % with 2 decimals, also with symbol °/
°°°
):
Type of range Display unipolar range:
0-10V, 0-5V, 0-20mA, 4-20mA bipolar range:
+/-10V from 0 to 10000 (0 °/
°°°
to 10000 °/ from -10000 to +10000 (-10.000 °/
°°°
°°°
).
to +10.000 °/
°°°
).
User display The user can select the value range in which the measurements are expressed, by selecting: l the minimum limit corresponding to the range minimum 0 °/
°°°
(or -10000 °/
°°°
), l the maximum limit corresponding to the range maximum + 10000 °/
°°°
.
These minimum and maximum limits should be integers within the range -30000 to
+30000.
Example:
Suppose that a conditioning unit indicates pressure on a loop of 4-20mA, where
4mA corresponds to 3200mB and 20mA corresponds to 9600mB. The user can, therefore, select the User display format, defining the following minimum and maximum limits:
3200 °/
°°°
for 3200 mB as minimum limit,
9600 °/
°°°
for 9600 mB as maximum limit,
Values sent to the program will change between 3200 (=4mA) and 9600 (=20mA).
The corresponding values are as follows:
Value transmitted to program
Value of current
3200 current value
9600
4 mA between 4 and 20mA
20 mA
Value of pressure
3200 mB current value
9600 mB
TLX DS 57 PL7 xxE
41
Racked analog modules
Calibrating the TSX AEY 810 module
Introduction
Precautions
Calibration (See
Calibration function for an analog module, p. 213) is performed
globally for the module on channel 0. It is advisable to calibrate the module outside the application. Calibration can be performed with the PLC task linked to the channel, in RUN or STOP modes.
When in calibration mode, measurements for all channels in the module are declared invalid (bit %IWxy.i.1:X2 = 1), filtering and alignment is prevented and channel acquisition cycles may be lengthened.
As inputs other than channel 0 will not be acquired during calibration, the value transmitted to the application for these other channels is the last value that was measured before commencing calibration.
Procedure
Step
1
2
3
4
5
6
7
The following table shows the module calibration procedure:
Action
Access the calibration adjustment screen.
Double-click on channel 0.
Result : The system asks for confirmation ‘Do you wish to switch to recalibration mode?’.
Reply to this question with Yes .
Result : The calibration window appears.
Connect a reference voltage on the voltage input of channel 0, according to the range to be calibrated: l reference voltage = 10 V (20 ppm precision) in order to calibrate the module on the +/-10 V and 0..10
V ranges, l reference voltage = 5 V (20 ppm precision) in order to calibrate the module on the 0..5 V, 1..5 V, 0..20 mA and 4..20 mA ranges.
Caution: the reference 5 V is used to recalibrate the whole measurement channel for ranges 0..20 mA and 4..20 mA, with the exception of the 250 Ohm current shunt situated mounted on the current input.
Once the reference has been connected to the voltage input (e.g. 10 V), select the value from the
Reference drop-down list box. Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the Confirm command button. The ranges linked to this reference (e.g. +/-10
V and 0..10 V) are then calibrated automatically.
Calibrate the module for any other ranges in use.
the Return to Factory Settings command button will cancel all previous calibrations, and return the module to the calibration settings configured in the factory.
Click on the Save command button in order to register and save the new calibration in the module. If an attempt is made to exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost.
42
TLX DS 57 PL7 xxE
Racked analog modules
2.3
TSX AEY 1614 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TSX AEY 1614 rack-based module.
This Section contains the following Maps:
Topic
Introducing the TSX AEY 1614 module
Timing of measurements
Monitoring under/overshoot
Measurement filtering
Displaying measurements
Sensor alignment for the TSX AEY 1614 module
Calibrating the TSX AEY 1614 module
Page
TLX DS 57 PL7 xxE
43
Racked analog modules
Introducing the TSX AEY 1614 module
General The TSX AEY 1614 module is a 16 input thermocouple industrial measurement device.
The TSX AEY 1614 module offers the following ranges for each of its inputs l l according to the selection made at configuration (See Modifying the range of an
input or output of an analog module, p. 183):
Thermocouple: B,E,J,K,L,N,R,S,T or U;
Voltage: -80..+80 mV.
Note: The TELEFAST ABE 7 CP A12 connection accessory facilitates connection and provides a cold junction compensation device
Structural diagram
The TSX AEY 1614 input module performs the following functions:
Channels
0 to 7
Cold junction
Telefast 8
TSX AEY1614
Acquisition channel
Supply Opto
ADC Opto
Processing
X bus
Interface
Channels
8 to 15
Cold junction
Telefast 8
Acquisition channel ADC Opto
Supply Opto 6
1 2 3
7
4 5
44
TLX DS 57 PL7 xxE
Racked analog modules
Description Details of the functions are as follows:
Address Element
1 Adaptation and multiplexing
2
3
4
5
6
7
8
Amplification
Function
Adaptation consists of a common mode and differential mode filter. It is followed by channel multiplexing via opto switches in order to offer the possibility of common mode voltage between channels (up to 400 V). A second multiplexing stage is used to self calibrate the acquisition string offset as close as possible to the input limit, and select the cold junction compensation sensor included in the telefast package.
This is built around a weak offset amplifier. Lopping the amplifier on entry enables it to withstand voltage surges of 30V.
Conversion
Transformation of input measurements into a unit that can be used by the user l l
The converter receives the signal coming from an input channel or cold junction compensation. Conversion is based on a
Σ∆
16 bit converter.
l acknowledgment of recalibration and alignment coefficients to be applied to measurements, as well as self-calibration coefficients for the module, measurement filtering (digital filtering), based on configuration parameters, scaling of measurements, based on configuration parameters.
Interface and communication with the application l l l l
management of exchanges with the processor, geographical addressing, receiving module and channel configuration parameters, transmitting measured values, as well as module status, to the application.
Module power supply
Module monitoring and notification of possible errors to the application l l l l testing conversion string, testing for range under/overshoot on channels, testing for presence of terminal block, testing watchdog.
Cold junction compensation l l integrated into TELEFAST ABE 7CP A12, to be allowed for by the user if TELEFAST is not used.
TLX DS 57 PL7 xxE
45
Racked analog modules
Timing of measurements
Introduction The cycle time for the TSX AEY 1614 module depends on which cycle is used: l l normal cycle or fast cycle, defined in configuration (See Modifying the Scanning
cycle of the inputs of a racked analog module, p. 190), and the configured options.
in normal cycle, the scanning cycle time is fixed, in fast cycle, only channels registered as used are scanned. The scanning cycle time is therefore proportional to the number of channels registered as used.
Note: The channels are acquired simultaneously in pairs (channel 0 and channel
8, channel 1 and channel 9, …, channel 7 and channel 15).
Normal cycle Example for a module in which all the options are activated.
Wt0 V0
Wt8 V8
Wt1
Wt9
V1
V9
Wt2 V2
Wt10 V10
.......
Wt7 V7
.......
Wt15 V15
TCJC
TCJC
High prec.
High prec.
8ms 70ms 8ms 8ms 70ms 8ms 70ms 70ms 70ms
Module cycle time
Wt: wiring test (8 ms per channel requesting the test)
TCJC: Telefast cold junction compensation (70ms)
High prec. : high precision mode (corresponds to a self-calibration procedure of the module) (70ms)
46
TLX DS 57 PL7 xxE
Fast cycle
Racked analog modules
To reduce the cycle time to the maximum, the system will take account of the fact that the channels are acquired simultaneously in pairs.
Example of optimal cabling for 3 channels used with wiring test, Telefast cold junction compensation, and high precision mode:
If the user wishes to use only 3 channels and have the minimum cycle time, it is best to connect the dual channels. In this way, there will only be an elementary time for two channels. In our example, the dual channels 0 and 8 and channel 1 are selected.
The cycle time is therefore as follows:
2
×
70ms + 2
×
8ms + 70ms + 70ms = 296ms
Tf0
Tf8
8ms
V0
V8
Tf1
Tf9
V1
V9
CSFT
CSFT
70ms 8ms 70ms 70ms
Temps de cycle = 296ms
Hte préc.
Hte préc.
70ms
Note: The module cycle is asynchronous with the PLC cycle. At the start of each
PLC cycle, the channel values are recognized. If the cycle time of the MAST task is less than that of the module, some values will not have changed.
Illustration:
Module processing time
MAST task time changes of the channel values
TLX DS 57 PL7 xxE
47
Racked analog modules
Monitoring under/overshoot
Introduction
Measurement zones
The TSX AEY 1614 module provides the choice of one voltage range and six thermocouple ranges for each of its inputs.
For the selected range, the module monitors over/undershoot: it checks that the measurement is between a lower and upper limit (See Modifying overshoot
monitoring and event processing selection, p. 193).
This check is optional.
The measurement range is divided into three zones: lower limit upper limit undershoot zone nominal zone overshoot zone l l l the nominal zone is the measurement range corresponding to the range selected, the overshoot zone is the zone above the upper range limit, the undershoot zone is the zone below the lower range limit.
Note: Beyond these limits (in the overshoot or undershoot zones) which correspond to nominal values in the selected range (thermocouple value limits or -
80mV and +80mV for the electrical range), there is measurement saturation, even if overshoot monitoring has not been activated.
Over/undershoot indications
In the over/undershoot zones, there is a risk of measurement device saturation. To overcome this risk with a user program the following error bits can be used:
Bit name
%Ixy.i.ERR
%MWxy.i.2:X1
%MWxy.i.2:X14
%MWxy.i.2:X15
Meaning (when = 1)
Channel fault
Indicates a range over/undershoot on the channel
Indicates a undershoot on the channel
Indicates an overshoot on the channel
Note: If overshoot monitoring is not activated, all bits described above will remain at zero irrespective of the measurement value.
48
TLX DS 57 PL7 xxE
‘Temperature’ range
Racked analog modules
The range overshoot corresponds either to a dynamic overshoot on the acquisition device or to an overshoot of the standardized sensor measurement zone or to
°
C).
TLX DS 57 PL7 xxE
49
Racked analog modules
Measurement filtering
Introduction
Mathematical formula
The filtering used is first order filtering. The filter coefficient can be modified (See
Modifying the channel filtering value, p. 208) from a programming terminal and by
program.
The mathematical formula used is as follows :
Mesf n = α × ( – 1 ) + ( 1 – α ) × Valb n where:
α =filter efficiency,
Mesf(n)=measurement filtered at moment n,
Mesf(n-1)=measurement filtered at moment n-1,
Valb(n)=gross value at moment n.
At configuration, the user selects the filter value from 7 possible values. This value can be changed, even when the application is in RUN mode .
Note: Filtering is inhibited in fast cycle mode.
Values for the
TSX AEY 1614 module
The filter values are as follows. They are dependent on the cycle time T:
Required efficiency
No filtering
Low filtering
Medium filtering
High filtering
3
4
5
6
0
1
2
Value to be selected corresponding
α
0
0,750
0,875
0,937
0,969
0,984
0,992
Filter response time at 63% cut-off frequency (Hz)
0
4 x T
8 x T
0
0.040 / T
0.020 / T
16 x T
32 x T
64 x T
128 x T
0.010 / T
0.005 / T
0.025 / T
0.012 / T
50
TLX DS 57 PL7 xxE
Racked analog modules
Displaying measurements
Introduction
Range -
80..+80mV
Thermocouple ranges
This process is used to select the display format depending on which formats are provided in the user program. It is necessary to differentiate between the electric ranges and the thermocouple or thermowell ranges.
The measurement supplied to the application can be applied directly by the user, who can choose between standardized and user-defined display formats.
Standardized display:
The values are displayed in standardized units (in % to 2 decimal points, also with
°/
°°°
symbol).
Display from -10000 to +10000 (-10.000 °/
°°°
°°°
)
to +10.000 °/ l l
User display:
The user can select (See Modifying the display format of an input channel as voltage
or as current, p. 185) the range of values within which the measurements are
expressed, by selecting: the minimum limit corresponding to the minimum limit of the range (-10000 °/ the maximum limit corresponding to the maximum limit of the range (+10.000°/
).
),
+30000.
The measurement supplied to the application can be applied directly by the user, who can select (See Modifying display format of a thermocouple or thermowell
channel, p. 187) one of the two types of display: temperature display and
standardized display.
Temperature display :
The values are supplied in tenths of a degree (Celsius or Fahrenheit, depending on the unit selected on configuration).
User display :
The user can select standardized display 0..10000 (i.e. 0 to 10000 °/
°°°
), by specifying the minimum and maximum temperatures corresponding to 0 and 10000.
TLX DS 57 PL7 xxE
51
Racked analog modules
Sensor alignment for the TSX AEY 1614 module
Introduction Alignment consists of eliminating systematic deviation observed with a given sensor around a given operating point. An error linked to the process is compensated for.
For this reason, replacing a module does not necessitate a new alignment, whereas the replacement of the sensor or modification of the operating point of this sensor does necessitate a new alignment.
Conversion line after alignment
Conversion line before alignment
Alignment values
The alignment value can be modified (See
Aligning an input channel, p. 210) from a
programming terminal, even when the program is in RUN mode. For each input channel, the user can: l l l view and modify the required measurement value, save the alignment value, see if the channel is already aligned.
The alignment offset can also be modified by the program.
Alignment is performed on the channel during normal operation, without affecting the module channel operating modes.
The maximum difference between the value measured and the value required
(aligned value) should not exceed 1500.
Note: bit %IWxy.i.1:X0 = 1 indicates that the channel is aligned.
52
TLX DS 57 PL7 xxE
Racked analog modules
Calibrating the TSX AEY 1614 module
Introduction
Recommendations
Calibration (See
Calibration function for an analog module, p. 213) is performed on
channels 0 and 8.
On channel 0, two types of calibration are possible: l l calibration of the measurement string for one channel, calibration of the current source necessary for the measurements from resistive probe sensors.
On channel 8, only calibration of the measurement string is possible.
It is advisable to calibrate the module outside the application. Calibration can be performed with the PLC task linked to the channel, in RUN or STOP modes.
Note: in the calibration screen, the values displayed on the left side of the screen
(channels 0 et 8) indicate the value measured on the connected voltage reference.
The display format in tenths of mV (16000 displayed for 1.6 V) is not intended to monitor the reference precision but simply to indicate the presence of this reference.
Procedure for recalibrating the measurement string
The following table shows the procedure for calibrating the measurement string:
Step
1
2
3
4
5
Action
Access the calibration adjustment screen
Double-click on channel 0.
Result : The system asks for confirmation ‘Do you wish to switch to recalibration mode?’.
Reply to this question with Yes.
Result : The recalibration window appears.
Connect a voltage reference to the voltage input to be calibrated, according to the l l range to be calibrated l +25.000mV+/-0.039% for the ranges to be calibrated Thermocouples B, R, S, and T, l +55.000mV+/-0.026% for the ranges to be calibrated Thermocouples U, N, L, and K,
+80.000mV+/-0.023% for the ranges to be calibrated Thermocouples J and E,
+166.962mV+/-0.019% for the range Pt100.
Once the reference has been connected to the voltage input (e.g. 10 V), select the value from the Reference drop-down list box. Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the Confirm command button. The ranges linked to this reference (e.g. 10 V and 0..10 V) are then calibrated automatically.
TLX DS 57 PL7 xxE
53
Racked analog modules
Step
6
7
Action
Calibrate the module for any other ranges in use.
The Return to Factory Settings command button will cancel all previous calibrations, and return the module to the calibration settings configured in the factory.
Click on the Save command button in order to take into account and save the new calibration in the module. If an attempt is made to exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost.
Calibrating the
1.25 mA current source
The current source is used for cold junction compensation. The following table shows the procedure for calibrating the current source:
Step
1
2
3
4
5
6
Action
Access the calibration adjustment screen.
Double-click on channel 0.
Result : The system asks for confirmation ‘Do you wish to switch to recalibration mode?’.
Reply to this question with Yes.
Result : The calibration window appears.
Using a precision multimeter (0.068% to 1.25mA), measure the current source value given by the channel to be calibrated.
Note this value and convert it into micro-Amps.
Use the Reference drop-down list box to select Source .
Enter the converted value in the Source field (for example 12501 for 1.2501 mA) then confirm the selection with the OK command button.
Click on the Save command button in order to acknowledge and save the new calibration in the module. If an attempt is made to exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost.
54
TLX DS 57 PL7 xxE
Racked analog modules
2.4
TSX AEY 414 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TSX AEY 414 rack-based module.
This Section contains the following Maps:
Topic
Introducing the TSX AEY 414 module
Timing of measurements
Monitoring under/overshoot
Sensor link monitoring
Measurement filtering
Displaying measurements
Sensor alignment for the TSX AEY 414 module
Cold junction compensation of the TSX AEY 414 module
Calibration
Page
TLX DS 57 PL7 xxE
55
Racked analog modules
Introducing the TSX AEY 414 module
General The TSX AEY 414 module is a multi-range acquisition device with 4 separately insulated inputs. For each of its inputs, the module offers ranges dependent on the selection made at (See Modifying the range of an input or output of an analog
module, p. 183) configuration:
l l l
Thermocouple: B, E, J, K, L, N, R, S, T and U,
Voltage: -13..+63 mV,
Thermowell Pt100, Pt1000, Ni1000 with 2 or 4 wires, or an ohmic range of: 0..400
Ohms, 0..3850 Ohms, l High level +/-10 V, 0..10 V, +/- 5 V, 0..5 V (0..20 mA with external shunt) or 1..5
V (4..20 mA with external shunt). It should be noted that the external shunts are supplied with the product.
Note: The terminal block is supplied separately under the reference TSX BLY 01.
Structural diagram
The TSX AEY 414 input module performs the following functions:
TSX AEY 414
1780 Vrms insulation
2830 Vrm s insulation
Optocouplers
Function
Optocoupler
Optocouplers
Optocouplers
1
Optocouplers
DC / DC converter
1 couplers
2
6
A/D
Measurement of the internal temperature
5 V
3
Processing
X bus
Interface
4
5
56
TLX DS 57 PL7 xxE
Racked analog modules
Description
Address
1
2
3
4
5
6
Details of the functions are as follows:
Element
Connection to process and scanning of input channels
Digitization of analog input measurement signals
Transformation of input measurements into a unit that can be used by the user
Interface and communication with the application
Module power supply
Module monitoring and notification of possible errors to the application
Function l l l physical connection to the process via a screw terminal block, gain selection, based on the input signal characteristics, defined in configuration for each channel (high-level range, thermocouple or thermowell), multiplexing.
Digitization of analog input measurement signals l l l l
l l l l consideration of recalibration and alignment coefficients to be applied to measurements (channel-by-channel and range-by-range), as well as selfcalibration coefficients for the module, linearization of the measurement provided by the Pt or Ni thermowells, linearization of measurement and adjustment for internal or external cold junction compensation in the case of thermocouples, scaling of measurements, based on configuration parameters (in physical units or user-defined range).
management of exchanges with the processor, geographical addressing, receiving module and channel configuration parameters, transmitting measured values, as well as module status, to the application.
l l l l l testing conversion string, testing for range under/overshoot on channels, testing for presence of terminal block, sensor link test (except for the ranges +/-10 V, 0..10V, +/-5 V, 0..5V (0..20mA)), watchdog test.
TLX DS 57 PL7 xxE
57
Racked analog modules
Timing of measurements
Introduction
Breakdown of the cycle time
The cycle length for the TSX AEY 414 module is always 550 ms.
This time is independent of the mains frequency (50Hz or 60Hz). The measurements are linked in the following manner: channel 0, channel 1, channel 2, channel 3 and internal selection.
The table below breaks down the different times:
Type of time
Scanning time for channel 0
Scanning time for channel 1
Scanning time for channel 2
Scanning time for channel 3
Scanning time for channel 4
Internal selection
TOTAL
Breakdown of times l l l l l l l l l l l
Wiring test: 4 ms,
Channel conversion: 106 ms.
Wiring test: 4 ms,
Channel conversion: 106 ms.
Wiring test: 4 ms,
Channel conversion: 106 ms.
Wiring test: 4 ms,
Channel conversion: 106 ms.
Wiring test: 4 ms,
Channel conversion: 106 ms.
Internal selection: 110 ms.
Total
110 ms
110 ms
110 ms
110 ms
110 ms
110 ms
550 ms
Note: The internal selection corresponds to the internal temperature, internal references for the self-calibration of the module or to the line compensation for thermowell ranges.
Illustration
110 ms
Tconv Ttf
Tconv
110 ms
Tconv
Channel 0 Channel 1 Internal selection
The cycle is always performed in the same way and lasts 550 ms.
58
TLX DS 57 PL7 xxE
Racked analog modules
Monitoring under/overshoot
Introduction
Measurement zones
The TSX AEY 414 module provides a choice of voltage ranges, thermocouple ranges and thermowell ranges for each input.
For the selected range, the module monitors over/undershoot: it checks that the measurement is between a lower and upper limit.
The measurement range is divided into three zones: lower limit upper limit undershoot zone nominal zone overshoot zone l l l the nominal zone is the measurement range corresponding to the range selected, the overshoot zone is the zone above the upper range limit, the undershoot zone is the zone below the lower range limit.
Over/undershoot indications
In the over/undershoot zones, there is a risk of measurement device saturation. To overcome this risk with a user program the following error bits can be used:
Bit name
%Ixy.i.ERR
%IWxy.channel.2:X1
Meaning (when equal to 1)
Channel fault
Indicates a range over/undershoot on the channel
Voltage range overshoot values
Range
When using voltage ranges, 5% overshoot of the positive electric part of the range is authorized by the module.
Table of values:
Lower limit Upper limit
+/-10 V
0..10 V
+/-5 V
0..5 V
1..5 V
0..20 mA
4..20 mA
-10.5 V
-0.5 V
-5.25 V
-0.25 V
+0.8 V
-1 mA
+3.2 mA
+10.5 V
+10.5 V
+5.25 V
+5.25 V
+5.2 V
+21 mA
+20.8 mA
Default values Minimum limit in User mode
+/- 10500
-500..+ 10500
Min - 5%(Max-Min)/2
Min - 5%(Max-Min)
+/- 10500
-500..+ 10500
-500..+ 10500
-500..+ 10500
-500..+ 10500
Min - 5%(Max-Min)
Min - 5%(Max-Min)
Min - 5%(Max-Min)
Min - 5%(Max-Min)
Min - 5%(Max-Min)
Maximum limit in User mode
Max + 5%(Max-Min)/2
Max + 5%(Max-Min)
Max + 5%(Max-Min)
Max + 5%(Max-Min)
Max + 5%(Max-Min)
Max + 5%(Max-Min)
Max + 5%(Max-Min)
TLX DS 57 PL7 xxE
59
Racked analog modules
Thermal range overshoot values
The range overshoot corresponds either to a dynamic overshoot on the acquisition device or to an overshoot of the standardized sensor measurement zone or to
Table of values:
Lower limit Upper limit Range
Thermo B
Thermo E
Thermo J
Thermo K
Thermo L
Thermo N
Thermo R
Thermo S
Thermo T
Thermo U
Pt100
Pt1000
Ni1000
-13..+63 mV
0..400
Ω
0..3850
Ω
° °
°
°
°
°
°
°
°
°
°
°
°
°
°
-60 °C (-76 °F)
°
°
°
°
°
°
°
°
°
-13 mV
0
0
°
° °
°
°
° °
°
°
°
°
°
°
°
°
+240 °C (+464 °F)
°
°
°
°
°
°
°
°
°
+63 mV
400
Ω
3850
Ω
°
°
°
°
°
°
Default values Minimum limit in
User mode
Maximum limit in
User mode
°
°
0
0
+10000
+10000
°
°
°
°
0
0
0
0
+10000
+10000
+10000
+10000
°
°
°
°
°
°
°
° 0
0
0
0
°
°
°
° 0
0
° 0
-2064..+ 10000 Min
+10000
+10000
+10000
+10000
+10000
+10000
+10000
Max
0..+10000 Min Max
0..+10000 Min Max
60
TLX DS 57 PL7 xxE
Racked analog modules
Sensor link monitoring
Resistance values
Sensor link monitoring imposes a maximal value on the resistance Rs of the sensors connected to the module’s inputs. This value Rs max. is compatible with normal operation of the TSX AEY 414 module.
The sensor link fault may correspond to a short-circuit or an open circuit depending on the type of sensor used. On the other hand, the report is global and doesn’t differentiate between a short-circuit and an open circuit.
Table of resistance values:
Sensors
Rs max.
Open circuit
Short-circuit
Thermowells
Pt1000/Ni1000
-
>3850 ohms
150 ohms
Thermowells
Pt100
0
>400 ohms
15 ohms
Thermocouples -15/60 mV,
B, E, J, K, L, N, R, S, T and U
100 ohms
100000 ohms undetectable
Note: l The module manages consistency between the terminal block fault and the sensor link fault, l A sensor link fault is not detected in the range 0-5 V / 0-20 mA (the service is not offered to the user and the wiring test is not executed), l In the range 1-5 V / 4-20 mA the wiring test is only effective if the 250 W shunt is connected. If this is not the case (the shunt is not connected), the wiring test cannot detect a fault, even if the cables are cut, l With thermowells, a sensor link fault caused by an anomaly in line compensation can appear or disappear with a maximum delay of 12 s, in relation to the occurrence of the anomaly.
TLX DS 57 PL7 xxE
61
Racked analog modules
Measurement filtering
Introduction
Mathematical formula
The filtering used is first order filtering. The filter coefficient can be changed (See
Modifying the channel filtering value, p. 208) from the PL7 screen and by program.
The mathematical formula used is as follows :
Mesf n =
α × (
– 1
)
+
(
1 –
α ) ×
Valb n where:
α =filter efficiency,
Mesf(n)=measurement filtered at moment n,
Mesf(n-1)=measurement filtered at moment n-1,
Valb(n)=gross value at moment n.
On configuration, the user selects the filtering value from 7 possible values. This value can be changed, even when the application is in RUN mode .
Note: Filtering is inhibited in fast cycle mode.
Values for the
TSX AEY 414 module
The filter values are as follows:
Required efficiency
No filtering
Low filtering
Medium filtering
High filtering
0
1
2
3
4
5
6
Value to be selected corresponding
α
Filter response time at 63%
0
0,750
0,875
0,937
0,969
0,984
0,992
0
1.91 s
4.12 s
8.45 s
17.5 s
34.1 s
68.5 s
Cut-off frequency (Hz)
0
0,083
0,039
0,019
0,0091
0,0046
0,0022
62
TLX DS 57 PL7 xxE
Racked analog modules
Displaying measurements
Introduction This process is used to select the display format in which the data is supplied to the user-program. It is necessary to distinguish between electrical ranges and thermocouple or thermowell ranges:
Standardized display of electrical ranges
The values are displayed in standardized units (in % to 2 decimal points, also with
°/
°°°
symbol)
Type of range Display unipolar range bipolar range from 0 to 10000 (0 °/
°°°
to +10.000 °/ from -10000 to 10000 (-10000 °/
°°°
°°°
)
to +10000 °/
°°°
)
User-defined display
The user can select the range of values (See Modifying the display format of an
input channel as voltage or as current, p. 185) within which the measurements are
expressed, by selecting: l the minimum limit corresponding to the minimumrange value: 0 °/
°°°
) (or -10000
°/
°°°
), l the maximum limit corresponding to the maximum range value +10.000 °/
The minimum and maximum limits should be integers within the range -30000 to
.
+30000.
Example:
Let us suppose that a conditioning unit indicates pressure information on a 4-20mA loop, with 4mA corresponding to 3200 mB and 20mA corresponding to 9600 mB.
The user can, therefore, select the user-defined format (User), defining the following minimum and maximum limits:
3200 °/
°°°
for 3200 mB as minimum limit,
9600 °/
°°°
for 9600 mB as maximum limit,
Values sent to the program will change between 3200 (=4mA) and 9600 (=20mA).
The corresponding values are as follows:
Value of pressure Value transmitted to the program
Value of current
3200 current value
9600
4 mA between 4 and 20mA
20 mA
3200 mB current value
9600 mB
TLX DS 57 PL7 xxE
63
Racked analog modules
Displaying thermal ranges
The measurement supplied to the application can be applied directly by the user, who can choose (See Modifying display format of a thermocouple or thermowell
channel, p. 187) between standardized and temperature display formats.
l With the temperature display format, values are given in tenths of a degree
Celsius or Fahrenheit, depending on the unit selected.
l With user display, the user can select standardized display 0..10000 (or 0 to
10000 °/
°°°
) by specifying minimum and maximum temperatures corresponding to 0 and 10000.
64
TLX DS 57 PL7 xxE
Racked analog modules
Sensor alignment for the TSX AEY 414 module
Introduction
Illustration
Alignment consists of eliminating systematic deviation observed with a given sensor around a given operating point. Alignment provides compensation for errors linked to the process, not to the equipment. For this reason, replacing a module will not require realignment, whereas the replacement of a sensor or modification of the operating point of an existing sensor will require realignment.
The conversion process is as follows:
Conversion line after alignment
Conversion line before alignment
Example
Alignment values
Suppose that a Pt100 probe, immersed in melting ice (procedure for adjustment of probes) indicates a a temperature of 10 °C (and not 0 °C) after measurement and display. The user can align the measurement to the value 0 (value required). After this alignment procedure, the measurement channel will apply an offset of -10 systematically for any new measurement.
The alignment value can be modified (See
Aligning an input channel, p. 210) from a
programming terminal, even when the program is in RUN mode.
For each input channel, the user can: l l l view and modify the required measurement value, save the alignment value, see if the channel is already aligned.
The alignment offset can also be modified by the program. Alignment is performed on the channel under normal usage, without affecting the module channel operating modes.
The maximum difference between the value measured and the value required
(aligned value) should not exceed +/-1000.
TLX DS 57 PL7 xxE
65
Racked analog modules
Cold junction compensation of the TSX AEY 414 module
Definition For thermocouple ranges, the module provides cold junction compensation.
However, the cold junction temperature can be measured either on the module terminal block (by a probe inside the module), or remotely by using an external class
A Pt100 probe (not supplied) connected to channel 0 of the module (See Cold
junction compensation, p. 194).
66
TLX DS 57 PL7 xxE
Racked analog modules
Calibration
Introduction
Important
Module calibration (See
Calibration function for an analog module, p. 213) is used
to correct long-term drifts in the module, and to optimize precision at ambient temperatures other than 25 ºC. The TSX AEY414 module is calibrated channel by channel.
The calibration dynamic is limited to 1% of the full scale, as above this level the module considers there to be an acquisition channel anomaly.
Full scale calibration is done on each of the channels and in each of the ranges by placing a calibration source directly on the input terminal block.
Procedure for a voltage input
This procedure is performed from the recalibration screen
Step
1
2
3
4
5
Action
Access the calibration adjustment screen.
Select a channel and switch to calibration mode.
Connect a voltage reference to the voltage input to be calibrated, according to the range to be calibrated l l
+10.000mV +/-0.018% for voltage ranges,
+60.000mV +/-0.028% for thermocouples B, E, J, K, L, N, R, S, T and U and the range 13..63 mV, l +2.500mV +/-0.016% for the Pt100, Pt1000 Ni1000 thermowell ranges.
Once the reference has been connected to the voltage input, select the reference value from the drop-down list.
Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the "Confirm" button. The ranges linked to this reference are then calibrated automatically.
Procedure for thermowell current source
This procedure is performed from the calibration screen
Step
1
2
3
4
Action
Access the calibration adjustment screen.
Select a channel and switch to calibration mode.
Connect a reference current channel-by-channel in order to calibrate.
l +2.5mA +/-0.0328% for thermowell ranges.
Read the value supplied, and give this value in units of x 100 nA.
TLX DS 57 PL7 xxE
67
Racked analog modules
Acknowledgment The calibration value is not acknowledged until it has been saved in the module using the "Save" button.
The "Return to Factory Parameters" button cancels all previous calibrations, and restores the module to its initial calibration (factory settings).
Selecting this button triggers a confirmation message. On the other hand, after confirmation, acknowledgment is immediate and does not need to be saved.
Leaving the screen without saving triggers a message which will remind the user that the save has not been performed. If the user chooses to exit the screen anyway, the new calibration coefficients are lost (the former values are restored).
Note: l For the calibration voltages 10 v and 2.5 V, the expected read value after calibration is 10000 +/-2, l For 60 mV calibration, the expected read value is 9523 +/-2 (10000 corresponds to the full scale, i.e. 63mV).
68
TLX DS 57 PL7 xxE
Racked analog modules
2.5
TSX AEY 420 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TSX AEY 420 rack-based module.
This Section contains the following Maps:
Topic
Introducing the TSX AEY 420 module
Timing of measurements
Monitoring under/overshoot
Thresholds and Event Processing
Displaying measurements
Sensor alignment for the TSX AEY 420 module
Page
TLX DS 57 PL7 xxE
69
Racked analog modules
Introducing the TSX AEY 420 module
General
Structural diagram
The TSX AEY 420 module is an industrial measurement device comprising 4 highlevel fast inputs.
Associated to sensors or transmitters, they support surveillance, measurement and regulation functions for continuous processes.
The TSX AEY 420 module supports the range +/-10 V, 0..10 V, 0..5 V, 1..5 V, 0..20 mA or 4..20 mA for each of its inputs, according to the selection made on configuration (See Modifying the range of an input or output of an analog module,
The TSX AEY 420 input module performs the following functions:
TSX AEY 420
1000 Vrms insulation
Channel selection
Optocoupler
Filter
A/D
Optocoupler
Processing
Filter
Internal reference 9
DC/DC
Converter
5 V 7
1 2 3 4
8
5 6
70
TLX DS 57 PL7 xxE
Racked analog modules
Description The table below shows the various functions :
Address
1
2
3
4
5
6
7
8
9
Element
Connection to the input channel process and scanning
Function l l physical connection to the process, via SubD connector(s), adapting input signals using analog filtering.
Multiplexing input signals l scanning input channels using static multiplexing.
Adapting input signals l Adapting input signals.
Digitization of analog input measurement signals l
Transformation of input measurements into a unit that can be used by the user l l
Interface and communication with the application l l l l
Module power supply -
16 bit analog/digital converter.
acknowledgment of recalibration and alignment coefficients to be applied to measurements, as well as self-calibration coefficients for the module, scaling of measurements, based on configuration parameters.
management of exchanges with the processor, geographical addressing, receiving module and channel configuration parameters, transmitting measured values, as well as module status, to the application.
Module monitoring and notification of possible errors to the application
Internal reference l l l l l testing conversion string, testing for range under/overshoot on channels, testing for presence of terminal block, watchdog test.
An internal calibration reference voltage is used by the module to calculate its self-calibration coefficients.
TLX DS 57 PL7 xxE
71
Racked analog modules
Timing of measurements
Introduction
Breakdown of the cycle time
The cycle length for the TSX AEY 420 module is 1 ms when no event processing is activated. It is independent of the number of input channels used.
The measurements are sequenced as follows: channel 0, channel 1, channel 2 and channel 3.
The scanning cycle is prolonged by 0.150 ms per channel if event processing is activated.
The table below gives the different cycle times
Configuration
No event processing
1 channel with event processing
2 channels with event processing
3 channels with event processing
4 channels with event processing
Cycle time
1 ms
1.15 ms
1.30 ms
1.45 ms
1.60 ms
Illustration
Channel 0 Channel 1 Channel 2 Channel 3
Cycle time independent of the number of inputs used
72
TLX DS 57 PL7 xxE
Racked analog modules
Monitoring under/overshoot
Introduction
Measurement zones
The TSX AEY 420 module provides a choice of 6 voltage or current ranges for each of its inputs.
For the selected range, the module monitors over/undershoot: it checks that the measurement is between a lower and upper limit.
This check is optional.
Generally speaking, the module will authorize an overshoot of 5% on the positive electrical part of the range.
The measurement range is divided into five zones: lower limit
Lower value in range
Upper value in range upper limit undershoot zone lower tolerance zone nominal zone upper tolerance zone overshoot zone l l l l l the nominal zone is the measurement range corresponding to the range selected, the upper tolerance zone comprises the values between the upper value of the range (e.g.: +10V for a range -10V/+10V) and the upper limit, the lower tolerance zone comprises the values between the lower value of the range (e.g.: -10V for a range -10V/+10V) and the lower limit, the overshoot zone is the zone above the upper range limit, the undershoot zone is the zone below the lower range limit.
TLX DS 57 PL7 xxE
73
Racked analog modules
Over/undershoot indications
In the over/undershoot zones, there is a risk of measurement device saturation. To overcome this risk with a user program the following error bits can be used: .
Bit name
%IWxy.i.1:X5
%IWxy.i.1:X6
%IWxy.i.2:X1
%Ixy.ERR
Meaning (when =1)
The value read is in the lower tolerance zone.
The value read is in the upper tolerance zone.
If overshoot monitoring is required, this bit signals that the value read is in one of the two overshoot zones. l l
%MWxy.i.2:X14 signals an undershoot in the lower zone,
%MWxy.i.2:X15 signals an overshoot in the upper zone.
Channel fault.
Note: If an overshoot occurs, the value measured is limited to the corresponding limit value.
Over/undershoot limit values
Range
-
Bipolar
+/-10V
The overshoot or undershoot values can be configured (See Modifying overshoot
monitoring and event processing selection, p. 193) independently of each other.
They can take integer values between the following values:
Unipolar
0..10V,0..5V,1..5V,0..20m
A,4..20mA
Standardized
User-defined Bipolar
+/-10V
User-defined Unipolar
0..10V,0..5V,1..5V,0..20m
A,4..20mA
Lower tolerance zone
Default value
Max. value
-0.125 x
∆ gamme /2
-0.125 x
∆ gamme
-1250
-0.125 x
∆ gamme /2
-0.125 x
∆ gamme
0
0
0
0
0
Min. value
-0.25 x
∆ gamme /2
-0.25 x
∆ gamme
-2500
-0.25 x
∆ gamme /2
-0.25 x
∆ gamme
Upper tolerance zone
Default value Min. value
0.125 x
∆ gamme /2
0
0.125 x
∆ gamme
0
1250
0.125 x
∆ gamme /2
0.125 x
∆ gamme
0
0
0
Max. value
0.25 x
∆ gamme /2
0.25 x
∆ gamme
2500
0.25 x
∆ gamme /2
0.25 x
∆ gamme
With ∆ gamme = Upper range value - lower range value,
74
TLX DS 57 PL7 xxE
Racked analog modules
Thresholds and Event Processing
At a Glance
Event causes
The TSX AEY 420 module manages 2 thresholds per channel (threshold 0 and 1).
When these thresholds are crossed, the module can trigger an event processing operation.
The user assigns an event processing operation to an analog channel when configuring the module software (See Modifying overshoot monitoring and event
processing selection, p. 193).
The event can be raised in a variety of ways: the measurement taken is lower than threshold 0 the measurement taken is higher than threshold 0 the measurement taken is lower than threshold 1 the measurement taken is higher than threshold 1
Masking event triggers
These triggers can be masked or enabled by program using %Qwxy.i word bits.
Address
%QWxy.i:X 0
%QWxy.i:X 1
%QWxy.i:X 2
%QWxy.i:X 3
Function (0 = masking, 1 = enabling)
Rising threshold 0 crossing
Descending threshold 0 crossing
Rising threshold 1 crossing
Descending threshold 1 crossing
Event source The source of the event is indicated by %Iwxy.i.2 word bits:
Address
%IWxy.i.2:X0
%IWxy.i.2:X1
%IWxy.i.2:X2
%IWxy.i.2:X3
Function (1= event, 0= no event)
Rising threshold 0 crossing
Descending threshold 0 crossing
Rising threshold 1 crossing
Descending threshold 1 crossing
TLX DS 57 PL7 xxE
75
Racked analog modules
Example
%QWxy.0:X0
%QWxy.0:X1
%QWxy.0:X2
%QWxy.0:X3
Threshold 1
Threshold 0
Additional information
76
Evt
%IWxy.0.2:X0
%IWxy.0.2:X1
Evt
%IWxy.0.2:X2
Evt
Evt
%IWxy.0.2:X3 l l l l
The %Iwxy.i.2 input word is only updated each time a new event is raised.
When the value measured is equal to the threshold but does not exceed it, no event is raised.
The event processing operation can be activated or deactivated by configuring each channel accordingly.
An event number (0 to 63) is assigned to each channel. The number selected determines the event priority (0=maximum priority, 1 to 63=minimum priority).
TLX DS 57 PL7 xxE
Racked analog modules
Displaying measurements
Introduction
Standardized display
User display
The measurement provided to the application can be applied directly by the user, l l who can choose between: using standardized display 0..10000 (or +/-10000 for the range +/ 10 V), creating parameters for its display format by indicating the minimum and maximum values required.
The values are displayed in standardized units (in % with 2 decimals, also with symbol °/
°°°
).
Type of range Display unipolar range bipolar range from 0 to 10000 (0 °/
°°°
to +10.000 °/ from -10000 to 10000 (-10000 °/
°°°
°°°
).
to +10000 °/
°°°
).
The user can select the value range (See Modifying the display format of an input
channel as voltage or as current, p. 185) in which the measurements are expressed,
by selecting: l the minimum limit corresponding to the range minimum: 0 °/
°°°
(or -10000 °/
°°°
), l the maximum limit corresponding to the range maximum +10000 °/
°°°
.
These minimum and maximum limits should be integers within the range -30000 to
+30000.
Example:
Suppose that a conditioning unit indicates pressure on a loop of 4-20mA, where
4mA corresponds to 3200mB and 20mA corresponds to 9600mB. The user can, therefore, select the User display format, defining the following minimum and maximum limits:
3200 °/
°°°
for 3200 mB as minimum limit,
9600 °/
°°°
for 9600 mB as maximum limit,
Values sent to the program will change between 3200 (=4mA) and 9600 (=20mA).
The corresponding values are as follows:
Value of pressure Value transmitted to program
Value of current
3200 current value
9600
4 mA between 4 and 20mA
20 mA
3200 mB current value
9600 mB
TLX DS 57 PL7 xxE
77
Racked analog modules
Sensor alignment for the TSX AEY 420 module
Introduction
Illustration
Alignment consists of eliminating a systematic shift observed with a given sensor with respect to a given operating parameter. The system compensates an error linked to the process. For this reason, replacing a module will not require realignment, whereas the replacement of a sensor or a change of operating parameter of an existing sensor will require realignment.
The conversion process is as follows:
Conversion line after alignment
Initial conversion line
Example
Alignment values
For example, supposing that a pressure sensor, linked to a conditioning unit (1mV/ mB), indicates 3200 mB, while the actual pressure is 3210 mB. The value measured by the module in standardized scale will be 3200 (3.20 V). The user can align the measurement to the value 3210 (value required). After this alignment procedure, the measurement channel will apply a systematic offset of +10 on any new measurement. The alignment value which must be entered is 3210.
The alignment value can be modified (See
Aligning an input channel, p. 210) from
the PL7 screens, even when the program is in RUN mode.
For each input channel, the user can: l l l view and modify the required measurement value, save the alignment value, see if the channel is already aligned.
The alignment offset can also be modified by program.
Alignment is performed on the channel under normal usage, without affecting the module channel function modes. The maximum difference between the value measured and the value required (aligned value) should not exceed 1000.
The alignment offset is stored in the word %Mwxy.i.8.
Note: bit %IWxy.i.1:X0 = 1 indicates that the channel has been aligned.
78
TLX DS 57 PL7 xxE
2.6
Racked analog modules
TSX ASY 410 and TSX ASY 800 modules
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TSX ASY 410 and TSX ASY 800 rack modules.
This Section contains the following Maps:
Topic
Introducing the TSX ASY 410 module
Characteristics of the outputs
Monitoring under/overshoots for the TSX ASY 410 module
Behavior of the TSX ASY 410 module outputs
Introducing the TSX ASY 800 module
Output characteristics
Monitoring under/overshoots for the TSX ASY 800 module
Behavior of the outputs of the TSX ASY 800 module
Page
TLX DS 57 PL7 xxE
79
Racked analog modules
Introducing the TSX ASY 410 module
General
Overview
The TSX ASY 410 module comprises 4 separately insulated analog outputs.
Depending on the selection made at configuration, (See Modifying the range of an
input or output of an analog module, p. 183) for each of its inputs, the module offers
ranges: l l l
+/-10V,
0..20 mA,
4..20 mA.
The TSX ASY 410 output module performs the following functions:
TSX ASY 410
Optocouplers
Voltage / Current
X bus interface
Processing
Optocouplers
Insulation 1500 Vrm s
N/A
Optocouplers
N/A
Optocouplers
N/A
6
5 V
5 4
Optocouplers
DC / DC converter couplers
3
7
N/A
2 1 Function
80
TLX DS 57 PL7 xxE
Racked analog modules
Description Details of the functions are as follows:
Address
1
2
3
4
5
6
7
8
Function
Link to process
Adapting to different actuators
Conversion of digital data into analog signals
Characteristics l l l l l physical link to the process via a 20-pin screw terminal block,
Protection of the module against voltage surges.
Adaptation is performed in terms of voltage or current.
conversion is performed over 11 bits with sign (-2048 to 2047), data supplied by the program is recentered automatically in the converter dynamic,
Transformation of application values to data that can be used by the digital/analog converter
-
Communication interface with application l l l l management of exchanges with the processor, geographical addressing, receipt of module and channel configuration parameters from the application, as well as digital channel setpoints, transmission of module status to the application.
Module power supply
Module surveillance and notification of possible errors on the application
l l l l
24V external supply for outputs converter test, testing for range under/overshoot on channels, testing for presence of terminal block, testing watchdog.
Output updating The maximum time between the output value being sent to the PLC bus and its final positioning on the terminal block is 2.5 ms.
Outputs can be individually assigned to the MAST or FAST tasks of the application program.
Output writing The application must provide the outputs with values in the standard format: l l
-10000 to +10000 in range +/-10 V,
0 to +10000 in ranges 0-20 mA and 4-20 mA.
These values must be written in the words %Qwy.i.0 to 3 for channels 0 to 3 of the module.
TLX DS 57 PL7 xxE
81
Racked analog modules
Characteristics of the outputs
Output writing
Digital / analog conversion
The application must provide the outputs with values in the standard format: l l
-10000 to +10000 in range +/-10 V,
0 to +10000 in ranges 0-20 mA and 4-20 mA.
The values must be written in the words %Qwy.i.0 to 3 for channels 0 to 3 of the module.
Digital / analog conversion is performed on: l 11 bits + sign (-2048 to +2047).
Re-scaling of the data, provided by the program, in the converter dynamics is done automatically
Forcing outputs Each output can be forced using the PLC Debugging screen to a value between
10000 and +10000, defined by the user. This function is essentially dedicated to testing the wiring system.
Forcing cannot be accessed unless the program task which controls the outputs is in RUN mode (with the output in Fallback or Maintain position when the program task is in STOP mode).
82
TLX DS 57 PL7 xxE
Racked analog modules
Monitoring under/overshoots for the TSX ASY 410 module
Introduction The type of under/overshoot monitoring on the TSX ASY 410 module depends on the software version (the software version is indicated on the module reference label, affixed to the side panel of the product, or accessible via PL7 in connected mode).
For modules with the SV<=1.0 software version
If the values given by the application are less that –10000 or greater than +10000, the outputs saturate at the following value: l l l
-10 V or +10 V in range +/-10 V,
4 mA or 20 mA in range 4..20 mA,
0 mA or 20 mA in range 0..20 mA.
An overshoot fault is signaled by the following bits (usable by the program):
Bit name
%Ixy.i.ERR
%IWxy.i.2:X1
Meaning
When = 1, Indicates a channel error.
When = 1, Indicates a range overshoot/undershoot on the channel.
For modules with the SV>=2.0 software version
These modules allow an over/undershoot of: l l
+/-5 % on voltage ranges and 4..20 mA,
+5 % on the range 0..20 mA.
The measurement range is divided into three zones: lower limit upper limit undershoot zone nominal zone overshoot zone l the nominal zone is the measurement range that corresponds to the range selected, l l the the overshoot zone is the zone above the upper range limit, undershoot zone is the zone below the lower range limit.
Overshoot values in relation to range:
Range
+/-10V
0..20mA
4..20mA
Lower limit
-10500 (i.e. –10.5 V)
0 (i.e. 0mA)
-500 (i.e. 3.2 mA)
Upper limit
+10500 (i.e. +10.5 V).
+10500 (i.e. +21 mA).
+10500 (i.e. +20.8 mA).
TLX DS 57 PL7 xxE
83
Racked analog modules
Range overshoot detection is optional:
The user can select (See Modifying overshoot monitoring and event processing
selection, p. 193) whether overshoot, undershoot or both are to be indicated.
When the value sent is outside the over/undershoot limits and the over/undershoot monitor is requested, the over/undershoots are signaled by the following bits:
Address
%Ixy.i.ERR
Meaning
When = 1, Indicates a channel error
%MWxy.i.2:X1 When = 1, Indicates a range over/undershoot on the channel.
l l
%MWxy.i.2:X3 = 1 indicates overshoot by a greater value,
%MWxy.i.2:X3 = 0 indicates undershoot by a lower value.
84
TLX DS 57 PL7 xxE
Racked analog modules
Behavior of the TSX ASY 410 module outputs
Fallback/
Maintain or clearing outputs
When a fault occurs, depending on the gravity of the fault, the outputs shift individually or as a group to the Fallback/Maintain position or they are forced to 0 (0
V or 0 mA).
Different cases of output behavior:
Fault
Task in STOP mode or program missing
Communication fault
Configuration fault
Internal module fault
Output value outside limits
(range overshoot)
Software version>=2.0
Output value outside limits
(range overshoot)
Software version=1.0
Terminal block fault
Plugging in on power-up
Processor in STOP mode
Reloading program
Voltage output behavior
Fallback/Maintain (channel by channel)
Fallback/Maintain (channel by channel)
0V (channel by channel)
0V (channel by channel)
Value transmitted with saturation to +10.5/-10.5V
(channel by channel)
+10V/-10V
Current output behavior
Fallback/Maintain (channel by channel)
Fallback/Maintain (channel by channel)
0mA (channel by channel)
0mA (channel by channel)
Value transmitted with saturation to 3.2/20.8 mA or
0/20mA
4/20 mA or 0/20mA
Value maintain (all channels) Value maintain (all channels)
Outputs to 0 (all channels) 0 mA (all channels)
0 V (all channels) 0 mA (all channels)
Fallback or maintain at the current value is selected on configuration of the module.
The fallback value can be modified from the PL7 Debugging (See Modifying the
fallback value of an output, p. 211) screen or by program.
TLX DS 57 PL7 xxE
85
Racked analog modules
Introducing the TSX ASY 800 module
General The TSX ASY 800 module comprises 8 non-insulated analog outputs. Depending l l l on the selection made at configuration (See Modifying the range of an input or
output of an analog module, p. 183), for each of its inputs, the module offers ranges:
+/-10V,
0..20 mA,
4..20 mA.
The TSX ASY 800 output module performs the following functions: Overview
TSX ASY 800
Optocoupler
6
5
Processing
Optocoupler
D/A
4
DC/DC
Converter
7
3 2 1
8
86
TLX DS 57 PL7 xxE
Racked analog modules
Description Details of the functions are as follows:
Address Element
1
2
3
4 Transformation of application values to data that can be used by the digital/analog converter
Function
Link to process l l physical connection to the process via a 25 pin SubD connector, protection of the module against voltage surges.
Adapting to different actuators l Adaptation is performed in terms of voltage or current.
Conversion of digital data into analog signals l l in terms of voltage, conversion is performed on 13 bits sign + (-
8192 to +8191), in terms of current, conversion is performed on 13 bits (0 to +8191).
-
5
6
7
8
Communication interface with application l
l l l management of exchanges with the processor, geographical addressing, reception of module and channel configuration parameters from the application, as well as digital channel setpoints, transmission of module status to the application.
Module power supply
Module surveillance and notification of possible errors to the application l l l l
24V external supply for outputs converter test, testing for range under/overshoot on channels, testing for presence of terminal block, testing watchdog.
Output refresh period
The maximum time between the output value being sent to the PLC bus and its final positioning on the terminal block is 5 ms.
Action on external supply fault on outputs
If there is an external supply fault on the outputs, all outputs on the TSX ASY 800 module are set to 0.
Note: When the module has both an external supply fault and a terminal block fault, only the supply fault is signaled.
Output writing The application must provide the outputs with values in the standard format: l l
-10000 to +10000 in range +/-10 V,
0 to +10000 in ranges 0-20 mA and 4-20 mA.
These values must be written in the words %Qwy.i.0 to 7 for channels 0 to 7 of the module.
TLX DS 57 PL7 xxE
87
Racked analog modules
Output characteristics
Writing output
Digital / analog conversion
The application must provide values in a standardized format to the outputs: l l
-10000 to +10000 in range +/-10 V,
0 to +10000 in ranges 0-20 mA and 4-20 mA.
The values must be written in the words %QWxy.i.0 to 7 for channels 0 to 7 in the module.
Digital / analog conversion is carried out on: l l
13 bits + sign (-8192 to +8191) in voltage,
13 bits (0 to +8191) in current.
Re-scaling of the data, provided by the program, in the converter dynamics is done automatically.
Forcing the outputs
From the PL7 Debugging screen, each output can be forced to a value between –
10000 and +10000, as defined by the user. Essentially, this function is dedicated to testing the wiring.
Forcing can only be accessed if the program task controlling the output is in RUN mode (the output being in Fallback or Maintain position when the program task in
STOP mode).
What happens with an output external supply fault
With output external supply fault all the module outputs switch to 0.
Note: When the module has an external supply fault and a terminal block fault at the same time, only the supply fault is signaled.
88
TLX DS 57 PL7 xxE
Racked analog modules
Monitoring under/overshoots for the TSX ASY 800 module
Introduction
Measurement zones
The TSX ASY 800 module supports an under/overshoot of +/-5% on the voltage ranges and 4..20mA and +5% on the current range.
Under/overshoot detection is optional.
The measurement range is divided into three zones: lower limit upper limit
Overshoot indications undershoot zone nominal zone overshoot zone l l l the nominal zone is the measurement range that corresponds to the range selected, the overshoot zone is the zone above the upper range limit, the undershoot zone is the zone below the lower range limit.
The overshoot or undershoot values for different ranges are as follows:
Range
+/-10V
0..20mA
4..20mA
Lower limit
-10500 (i.e. –10.5 V)
0 (i.e. 0mA)
-500 (i.e. 3.2 mA)
Upper limit
+10500 (i.e. +10.5 V)
+10500 (i.e. +21 mA)
+10500 (i.e. +20.8 mA)
The user can select (See Modifying overshoot monitoring and event processing
selection, p. 193)whether overshoot, undershoot or both are to be indicated.
When the overshoot control is requested, the following bits signal the indications:
Bit name
%Ixy.i.ERR
%MWxy.i.2:X1
Meaning
When = 1, Indicates a channel error
When = 1, Indicates a range overshoot/undershoot on the channel.
l l
%MWxy.i.2:X3 = 1 indicates overshoot by a greater value,
%MWxy.i.2:X3 = 0 indicates undershoot by a lower value.
TLX DS 57 PL7 xxE
89
Racked analog modules
Behavior of the outputs of the TSX ASY 800 module
Fallback/
Maintain or clearing outputs
Fault
Task in STOP mode or program missing
Communication fault
Configuration fault
Internal module fault
Output value outside limits
(range overshoot)
Terminal block fault
Plugging in on power-up
Processor in STOP mode
Reloading program
When a fault occurs, depending on the gravity of the fault, the outputs shift individually or as a group to the Fallback/Maintain position or they are forced to 0 (0
V or 0 mA).
Different cases of output behavior:
Current output behavior
Fallback/Maintain (channel by channel)
Voltage output behavior
Fallback/Maintain (channel by channel)
Fallback/Maintain (channel by channel)
0V (channel by channel)
0V (channel by channel)
Value transmitted with saturation to
+10.5/-10.5V (channel by channel)
Value maintain (all channels)
Outputs to 0 V (all channels)
0 V (all channels)
Fallback/Maintain (channel by channel)
0mA (channel by channel)
0mA (channel by channel)
Value transmitted with saturation to 3.2/
20.8 mA or 0/20mA
Value maintain (all channels)
0 mA (all channels)
0 mA (all channels)
Fallback or maintain at the current value is selected on configuration of the module.
The fallback value can be modified from the PL7 Debugging (See Modifying the
fallback value of an output, p. 211) screen or by program.
Behavior on power-up
On power-up of the module (powering up the rack or plugging in on power-up), the outputs are fixed at 0V/0mA for one second before becoming operational.
This time period is needed to stabilize the output power supply.
90
TLX DS 57 PL7 xxE
The remote analog TBX modules
3
At a Glance
Aim of this chapter
What's in this
Chapter?
This chapter introduces the remote analog TBX modules.
This Chapter contains the following Sections:
Section
3.1
3.2
3.3
Topic
TBX AES 400 Module
TBX AMS 620 Module
TBX ASS 200 Module
Page
TLX DS 57 PL7 xxE
91
analog TBXs
3.1
TBX AES 400 Module
At a Glance
What’s in this section?
What's in this
Section?
This section introduces the TBX AES 400 remote module.
This Section contains the following Maps:
Topic
Introducing the TBX AES 400 module
Timing of measurements
Monitoring under/overshoot
Measurement filtering
Displaying measurements
Calibrating the TBX AES 400 module
Sensor alignment
Page
92
TLX DS 57 PL7 xxE
analog TBXs
Introducing the TBX AES 400 module
General
Overview
The TBX AES 400 base is an analog input module containing 4 insulated multiple l l l l range channels. It must be connected to a TBX LEP 030 communicator.
This module supports the following ranges on each input:
High-level voltage,
High-level current,
Thermocouples (B, E ,J, K, N, R, S, T),
Thermowells (Pt100, Pt1000, Ni1000).
TBX AES 400 input module connected to the TBX LEP 030 :
Input 0
Input 1
Input 2
Input 3
Analog/
Digital
Conversion
2
Processes (in chronological order:
-range selection
-overshoot
-sensor check
-filtering
-linearization
-display
Measure
Channel
Channel 0
24/48V
Time
Base
1
Cold junction temperature
3 4 5 6 7
Supply
TLX DS 57 PL7 xxE
93
analog TBXs
Description The TBX AES 400 module connected to the TBX LEP 030 communicator supports the following functions:
Address Function
1 l acquisition by relay multiplexing of the 4 channels with 50 Hz or 60 Hz rejection,
2
3
4
5
6
7 l l l l l l l l
12 bit + sign analog digital conversion, range selection for each input: voltage, current or thermocouple, input under/overshoot check, sensor check, measurement filtering, linearization and cold junction compensation for thermocouples, linearization for thermowells, user-defined measurement formatting.
94
TLX DS 57 PL7 xxE
analog TBXs
Timing of measurements
Introduction
Breakdown of the cycle time
The cycle length (time) for the TBX AES 400 module depends on the electricity network frequency (50Hz or 60Hz) and therefore on the rejection mode selected upon configuration.
The measurements are sequenced in the following manner: channel 0, channel 1, channel 2, channel 3 then acquisition of the module’s cold junction temperature.
Illustration of the cycle time
Channel 1
Channel 0
Channel 3
Channel 2 T cj
Channel 1 Channel 3
Channel 0 Channel 2 T cj
T channel
T cycle
T cj: time to acquire the cold junction temperature
The table below shows the various terms of the calculation.
Type of time
Scanning time for a channel
Acquisition time for the cold junction temperature
Acquisition time for a complete cycle
50 Hz rejection
80 ms
80 ms
400 ms
60 Hz rejection
68 ms
68 ms
340 ms
Note: l l
The cycle is always identical, even when some channels are not in use,
The time required for the program to access the measurements also depends on the transmission times on the FIPIO bus and on the PLC task period.
TLX DS 57 PL7 xxE
95
analog TBXs
Monitoring under/overshoot
Introduction
Measurement zone
The TBX AES 400 module provides a choice of voltage ranges, current ranges, thermocouple ranges and thermowell ranges for each input.
The module checks for an under/overshoot corresponding to the selected range: it checks that the measurement falls between a lower and upper limit.
The measurement range is divided into five zones: undershoot limit nominal zone overshoot limit l l l l l undershoot zone Lower tolerance zone
Upper tolerance zone overshoot zone
The nominal zone is the measurement range that corresponds to the range selected, the upper tolerance zone contains the values between the upper value of the range (e.g.: +10V for a range -10V/+10V) and the upper limit, the lower tolerance zone contains the values between the lower value of the range (e.g.: -10V for a range -10V/+10V) and the lower limit, the overshoot zone is the zone above the upper range limit, the undershoot zone is the zone below the lower range limit.
Under/overshoot indications
If the values supplied by the application fall outside the limits, saturation occurs at the value of the limit exceeded and under/overshoot is indicated by:
The module continues to supply the converted value until saturation of the converter or of the display format (+32767/-32768), even though the validity of the measurement is not guaranteed.
The user can use the under/overshoot bit as a means of eliminating these measurements.
Under/overshoot bit:
Address
%I\p.2.c\m.i.ERR
Meaning
When = 1, Indicates a range overshoot/undershoot on the channel
Electrical range under/overshoot values
For voltage ranges, the module allows an overshoot of 5% on the positive part of the range.
96
TLX DS 57 PL7 xxE
analog TBXs
TLX DS 57 PL7 xxE
Electrical ranges:
Range
+/-10 V
+/-5 V
0..20 mA
4..20 mA
-20..+20 mV
-50..+50 mV
-200..+200 mV
-500..+500 mV
Lower limit
-10.5 V
-5.25 V
-1 mA
+3.2 mA
-21 mV
-52.5 mV
-210 mV
-525 mV
Upper limit
+10.5 V
+5.25 V
+21 mA
+20.8 mA
+21 mV
+52.5 mV
+210 mV
+525 mV
Thermal range under/overshoot values
The range under/overshoot corresponds either to a dynamic under/overshoot of the acquisition string or to an under/overshoot of the standardized sensor measurement
°
°
Thermocouple ranges:
Range
Thermo B
Lower limit
Thermo E
Thermo J
Thermo K
Thermo N
Thermo R
Thermo S
Thermo T
°
°
°
°
°
°
Upper limit
°
°
°
°
°
°
Thermowell range:
Range
Pt100
Pt1000
Ni1000
Lower limit
°
°
° °
°
°
Upper limit
°
°
°
°
°
°
97
analog TBXs
Measurement filtering
Introduction
Mathematical formula
Values for the
TBX AEY 400 module
The system uses first order filtering. The filter coefficient can be modified from a programming terminal and by program (See Modifying the filter value of analog
The mathematical formula used is as follows :
Mesf n = α × ( – 1 ) + ( 1 – α ) × Valb n with:
α =filter efficiency,
Mesf(n)=measurement filtered at moment n,
Mesf(n-1)=measurement filtered at moment n-1,
Valg(n)=gross value at moment n.
On configuration, the user selects the filter value from 7 possible values.
The filter values are as follows. They are dependent on the power voltage:
Efficiency
No filtering
Low filtering
Medium filtering 3
4
High filtering 5
6
0
1
2
Correspo nding
α value
0
0,750
0,875
0,937
0,969
0,984
0,992
Rejection time constant at 50 Hz
Rejection time constant at 60 Hz
0
1.6 s
3.2 s
6.4 s
12.8 s
25.6 s
51.2 s
0
1.4s
2.7s
5.4 s
10.8 s
21.1 s
43.5 s
98
TLX DS 57 PL7 xxE
analog TBXs
Displaying measurements
Introduction This process is used to select the display format depending on which formats are provided in the user program.
It is necessary to differentiate between the electric ranges and the thermocouple or thermowell ranges.
Standardized display of electrical ranges
The values are displayed in standardized units (in % with 2 decimals, also with symbol °/
°°°
):
Type of range Display unipolar range
0-10V, 0-5V, 0-20mA, 4-20mA bipolar range
+/-10V from 0 to 10000 (0 °/
°°°
to 10000 °/
°°° from -10000 to +10000 (-10.000 °/
°°°
°°°
)
)
to +10.000 °/
User-defined display of electrical ranges
The user can select the value range in which the measurements are expressed, by selecting: l the minimum limit corresponding to the range minimum: 0 (or - 10000 °/
°°°
), l the maximum limit corresponding to the range maximum: + 10000 °/
The minimum and maximum limits are between -31128 and +31128.
°°°
.
Example:
Use of a 2/20 bar pressure sensor supplying a 0/20 mA signal and having a linear characteristic.
The user is interested in the pressure rather than the current value. The best resolution is obtained by selecting user display: l l for minimum limit: 2000, for maximum limit: 20000.
The user-program then uses values expressed directly in the physical unit, the millibar.
Illustration
Pressure
20.000 bars
2.000 bars
20 mA
Current
TLX DS 57 PL7 xxE
99
analog TBXs
Displaying thermocouple and thermowell ranges
With the temperature display format, values are provided in tenths of a degree.
With user display, the user can select standardized display 0..10000 by specifying the minimum and maximum temperatures corresponding to 0 and 10000.
The measurement provided to the application can be applied directly by the user, who can choose between standardized and temperature display formats.
Example:
Thermocouple J connected to a TBX AES 400 module. The user wishes to monitor a temperature range from 200 °C to 600 °C and obtain a result expressed as a percentage of the dynamic range.
In order to do this, select a standardized display format and define the limits: l l lower limit = 2000, upper limit = 6000.
The measurement accessible by program then falls between 0 and 10000.
For a temperature of 400°C, the module supplies a digital value equal to 5000 as the measurement, i.e. 50 % of the input dynamic range.
Illustration:
Displayed measurement value
%
100.00
50.00
0
200 400 600 T in degrees Celsius
100
TLX DS 57 PL7 xxE
analog TBXs
Calibrating the TBX AES 400 module
Introduction Calibration (See
Calibration function for an analog module, p. 213) is performed
globally for the module on channel 0.
It is advisable to calibrate the module outside the application. Calibration can be performed with the PLC task linked to the channel, in RUN or STOP modes.
l l
Calibration consists of two steps: calibration of the zero value, full scale calibration.
Calibration of the zero value
Calibration of the zero value is recommended for ranges +/-20mV, +/-50mV and thermocouple ranges. It involves simultaneously calibrating the zero value of each channel in range +/- 20 mV to the required ambient temperature by placing shunts directly on the input limits of the base unit.
Full scale calibration
Precautions
Full scale calibration is performed on channel 0 by placing the adjusted calibration source at full scale +/-0,01% directly on the input limits of channel 0 of the base unit.
When in calibration mode, measurements for all channels in the module are declared invalid, filtering and alignment is prevented and channel acquisition cycles may be lengthened.
As inputs other than channel 0 will not be acquired during calibration, the value transmitted to the application for these other channels is the last value that was measured before commencing calibration.
How to calibrate the module
The following table shows the module calibration procedure:
Step
1
2
3
4
Action
Access the calibration adjustment screen.
Double-click on channel 0.
Result : The system asks for confirmation ‘Do you wish to switch to recalibration mode?’.
Place a shunt on all the module inputs to perform calibration at 0.
Reply Yes to the previous question (reply No to avoid performing calibration at 0).
Result : The calibration window appears.
TLX DS 57 PL7 xxE
101
analog TBXs
Step
5
6
7
8
Action
Perform full scale calibration.
Connect a reference voltage on the voltage input of channel 0, according to the range to be calibrated: l reference voltage = 10 V (+/- 0.01% precision) in order to calibrate the module on ranges 10 V and 0..10 V, l reference voltage = 5 V (+/- 0.01% precision) in order to calibrate the module on ranges 0..5 V, 1..5 V, 0..20 mA and 4..20 mA, l reference voltage = 2 V (+/- 0.01% precision) in order to calibrate the module on ranges Pt1000 and Ni1000, l reference voltage = 500 mV (+/- 0.01% precision) in order to calibrate the module on range 500 mV, l reference voltage = 200 mV (+/- 0.01% precision) in order to calibrate the module on ranges Pt100 and +/- 200 mV, l reference voltage = 50 mV (+/- 0.01% precision) in order to calibrate the module on ranges +/- 200 mV and thermocouples E, J, K and N, l reference voltage = 20 mV (+/- 0.01% precision) in order to calibrate the module on ranges +/- 200 mV and thermocouples B, R, S and T.
Caution: the reference 5 V is used to recalibrate the whole measurement channel for ranges 0..20 mA and 4..20 mA, with the exception of the 250 Ohm current shunt situated on the current entry.
Once the reference has been connected to the voltage input (e.g. 10 V), select the value from the Reference drop-down list box. Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the Confirm command button. The ranges linked to this reference (e.g. 10 V and 0..10 V) are then calibrated automatically.
Calibrate the module for any other ranges in use.
the Return to Factory Settings command button will cancel all previous calibrations, and return the module to the calibration settings configured in the factory.
Click on the Save command button in order to take into account and save the new calibration in the module. If an attempt is made to exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost.
102
TLX DS 57 PL7 xxE
analog TBXs
Sensor alignment
Introduction Alignment consists of eliminating a systematic shift observed with a given sensor in relation to a given operating parameter. The system compensates an error linked to the process. For this reason, replacing a module will not require realignment, whereas the replacement of a sensor or modification of the operating parameter of this sensor will require realignment.
Conversion line after alignment
Initial conversion line
Example
Alignment values
Supposing that a pressure sensor, linked to a conditioning unit (1mV/mB), indicates
3200 mB, whereas the actual pressure is 3210 mB.
The value measured by the module in standardized scale will be 3200 (3.20 V). The user can align the measurement to the value 3210 (value required).
After this alignment procedure, the measurement channel will apply a systematic offset of +10. The alignment value which must be entered is 3210.
The alignment value can be changed (See
Aligning an input channel, p. 210) from
the PL7 screen, even when the program is in RUN mode.
For each input channel, the user can: l l l view and modify the required measurement value, save the alignment value, see if the channel is already aligned.
The alignment offset can also be modified by program.
Alignment is performed on the channel under normal usage, without affecting the module channel operating modes. The maximum difference between the value measured and the value required (aligned value) should not exceed 1000.
The alignment offset is stored in the word %Mwxy.i.8.
TLX DS 57 PL7 xxE
103
analog TBXs
3.2
TBX AMS 620 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TBX AMS 620 remote module.
This Section contains the following Maps:
Topic
Introducing the TBX AMS 620 module
Timing of measurements on inputs
Under/overshoot monitoring on inputs
Filtering of measurements on inputs
Displaying measurements on inputs
Characteristics of the outputs
Fault handling
Monitoring under/overshoots on the TBX AMS 620 module outputs
Calibrating the TBX AMS 620 module
Sensor alignment
Page
104
TLX DS 57 PL7 xxE
analog TBXs
Introducing the TBX AMS 620 module
General The TBX AMS 620 base unit is an analog output module containing 6 high-level noninsulated channels and 2 insulated outputs. It must be associated to a TBX LEP 030 communicator.
l l
This module supports the following ranges on each input :
High-level voltage,
High-level current.
l l
This module supports the following ranges on each output :
High-level voltage,
High-level current.
TLX DS 57 PL7 xxE
105
analog TBXs
Overview Overview of the TBX AMS 620 module associated to the TBX LEP 030 communicator: processor
Input 0
Input 1
Channel 1
Channel 0
Input 2
Input 3
Input 4
Input 5
1
Analog
Digital conversion
2
Processes:
- range selection
- overshoot
- filtering
- display
6
4
5
3
Channel 7
Channel 6
Bus interface
Time base
FIPIO
Output 0
Output 1
Channel 6
Channel 7
Digital
Analog conversion
10
Processes:
- refreshing
- error handling
- range selection
8
7
9
24/48V
Supply
106
TLX DS 57 PL7 xxE
Description analog TBXs
The TBX AMS 620 module associated with the TBX LEP 030 communicator supports the following input functions :
Address Function
1
2
3
4
5
6 l l l l l l acquisition of the 6 channels using multiplexing,
12 bit + sign analog digital conversion, range selection for each input: voltage, current, thermocouple, input under/overshoot monitoring, measurement filtering, user-defined measurement formatting.
The TBX AMS 620 module associated with the TBX LEP 030 communicator supports the following output functions:
8
9
Address Function
7 refreshing the digital values transmitted by the processor,
10 processing PLC dialog faults, range selection for each output: voltage, current, digital analog conversion.
TLX DS 57 PL7 xxE
107
analog TBXs
Timing of measurements on inputs
Introduction
Breakdown of the cycle time
The cycle time for the TBX AMS 620 module is fixed at 42.4 ms.
The measurements are sequenced in the following manner: channel 0, channel 1, channel 2, channel 3, channel 4, channel 5 then acquisition of two internal reference voltage channels, required for cyclical calibration.
Scanning time values:
Type of time
Scanning time for a channel
Acquisition time for a complete cycle
Time l l
5.3 ms,
42.4 ms.
Illustration:
Channel 1
Channel 0
Channel 3
Channel 2
Channel 5
Channel 4
Int.
T channel channel
Int. channel
Channel 1
Channel 0
Channel 3
Channel 2
T cycle = 42.4 ms
Note: l l
The cycle is always identical, even when some channels are not in use,
The time required for the program to access the measurements also depends on the transmission times on the FIPIO bus and on the PLC task period.
108
TLX DS 57 PL7 xxE
analog TBXs
Under/overshoot monitoring on inputs
Introduction
Measurement zone
The TSX AMS 620 module provides a choice between voltage or current ranges.
The module checks for under/overshoot corresponding to the selected range: it checks that the measurement falls between a lower and upper limit.
The measurement zone is in the nominal zone.
Beyond the nominal zone, under/overshoot is tolerated up to the under/overshoot limits:
Illustration: undershoot limit overshoot limit nominal zone undershoot zone overshoot zone
Under/overshoot indications
If values provided by the application fall outside the limits, then saturation will occur at the value of the limit exceeded.
The module continues to supply the converted value until saturation of the converter or of the display format (+32767/-32768), even though the validity of the measurement is not guaranteed.
The user can use the under/overshoot bit as a means of elminating these measurements.
Under/overshoot bit:
Bit name
%I\p.2.c\m.i.ERR
Meaning
When = 1, indicates a range over/undershoot on the channel.
Electrical range under/overshoot values
For voltage ranges, the module allows an overshoot of 5% on the positive electric part of the range.
Under/overshoot values according to the type of input
Range
+/-10 V
0..5 V
0..20 mA
4..20 mA
Lower limit
-10.5 V
Upper limit
+10.5 V.
0 V: this under/overshoot cannot be detected +5.25 V.
0 V: this under/overshoot cannot be detected +21 mA.
+3.2 mA +20.8 mA.
TLX DS 57 PL7 xxE
109
analog TBXs
Filtering of measurements on inputs
Introduction
Mathematical formula
Values for the
TBX AMS 620 module
The system uses first order filtering. The filter coefficient can be modified from a programming terminal and by program (See Modifying the filter value of analog
The mathematical formula used is as follows :
Mesf n = α × ( – 1 ) + ( 1 – α ) × Valb n with:
α =filter efficiency,
Mesf(n)=measurement filtered at moment n,
Mesf(n-1)=measurement filtered at moment n-1,
Valg(n)=gross value at moment n.
On configuration, the user selects the filter value from 7 possible values.
The filter values are as follows:
Efficiency
No filtering
Low filtering
Medium filtering 3
4
High filtering 5
6
0
1
2
Value to be selected
Corresponding
0 s
170 ms
339 ms
678 ms
1.35 s
2.71 s
5.42 s
α
time constant
0
0,750
0,875
0,937
0,969
0,984
0,992
110
TLX DS 57 PL7 xxE
analog TBXs
Displaying measurements on inputs
Introduction This process is used to select the display format depending on which formats are provided in the user program.
Standardized display of electrical ranges
The values are displayed in standardized units (in % with 2 decimals, also with symbol °/
°°°
):
Type of range Display unipolar range
0-10V, 0-5V, 0-20mA, 4-20mA bipolar range
+/-10V from 0 to 10000 (0 °/
°°°
to 10000 °/
°°° from -10000 to +10000 (-10.000 °/
°°°
°°°
).
).
to +10.000 °/
User-defined display of electrical ranges
The user can select the value range in which the measurements are expressed, by selecting: l the minimum limit corresponding to the range minimum: 0 (or - 10000 °/
°°°
), l the maximum limit corresponding to the range maximum: + 10000 °/
The minimum and maximum limits are between -31128 and +31128.
°°°
.
Example:
Use of a 2/20 bar pressure sensor supplying a 0/20 mA signal and having a linear characteristic.
The user is interested in the pressure rather than the current value. The best resolution is obtained by selecting user display: l l for minimum limit: 2000, for maximum limit: 20000.
The user-program then uses values expressed directly in the physical unit, the millibar.
Illustration:
Pressure
20.000 bars
2.000 bars
20 mA
Current
TLX DS 57 PL7 xxE
111
analog TBXs
Characteristics of the outputs
Output writing
Refreshing outputs via the module
The user has access via the program to 2 words (1 16-bit word per channel) in which the values of the analog outputs are given.
l l from 0 to 10000 (that is 0 °/
4/20 mA,
°°°
to 10000 °/
°°°
) for unipolar ranges 0/20 mA and from -10000 to +10000 (-10000 °/
°°°
to +10000 °/
°°°
) for bipolar range +/-10 V.
Outputs are refreshed every 5 ms
The response time between writing the output via the program and updating the outputs to the module limits depends on the PLC task period in which the module is configured.
112
TLX DS 57 PL7 xxE
analog TBXs
Fault handling
Dialog faults with the PLC
This type of handling groups together: l l l l l setting the PLC to STOP mode (or the task in which the module is configured), a PLC fault, a link fault between the PLC and the module.
In the above cases, the user has two options for each output: maintain the output at the current value, fallback to a defined value. The value must be selected between the normal display limits (0/10000) for unipolar ranges or –10000/10000 for the voltage range. By default, the module is configured in fallback to 0 mode.
Internal errors in the module
When the module has an internal error the outputs are forced to 0.
TLX DS 57 PL7 xxE
113
analog TBXs
Monitoring under/overshoots on the TBX AMS 620 module outputs
At a Glance
Characteristics of the ranges
The TBX AMS 620 module includes an under/overshoot monitoring device.
The limits and precisions of the various ranges are as follows:
Range
+/- 10V
0.20mA
4.20mA
Lower limit
-10000
0
0
Upper limit
+10000
+10000
+10000
Precision conversion on 11 signed bits of -
2048 to +2047 pulses conversion on 11 bits of 0 to
+2047 pulses conversion on 11 bits of 0 to
+2047 pulses
Illustration
Analog output value
+10 V
-10000
20 mA
Analog output value
10000
Numerical value
-10 V
20 mA
Analog output value
4 mA
0
10000
Numerical value
10000
Numerical value
Under/overshoot identifiers
If the values provided by the application are outside the limits, saturation occurs at the value of the limit exceeded. The overshoot is shown by:
Bit name
%I\p.2.c\m.voie.ERR
Meaning
When equal to 1, shows a range overshoot on the channel.
114
TLX DS 57 PL7 xxE
analog TBXs
Calibrating the TBX AMS 620 module
At a Glance Calibration (See
Calibration function for an analog module, p. 213) is carried out
globally for the module on channel 0.
It is advised that you calibrate the module outside the application. Calibration can be done with the PLC task linked to the channel, in RUN or STOP mode. Calibration is a full scale calibration
Full scale calibration is done on the 0 channel by placing the standard reference source scaled to +/-0.01% directly on the input limits of the 0 channel of the base.
Full scale calibration
Precautions When in calibration mode, measurements for all channels in the module are declared invalid, filtering and alignment are prevented and channel acquisition cycles may be lengthened.
As inputs other than the 0 channel will not be acquired during calibration, the value transmitted to the application for these other channels is the last value that was measured before switching to calibration.
How to calibrate the module
Step
1
2
3
4
5
6
7
The following table shows the procedure for calibrating the module:
Action
Access the calibration adjustment screen
Double click on the 0 channel.
Result : A question appears ‘Do you wish to switch to recalibration mode?’.
Reply to this question with Yes .
Result : The calibration window appears.
Then perform the full scale calibration.
According to the range to be calibrated, connect a reference voltage to the voltage input of channel 0: l l reference voltage = 10 V (precision +/- 0.01%) in order to calibrate the module on the +/-10 V ranges reference voltage = 5 V (precision +/- 0.01%) in order to calibrate the module on the 0..5 V ranges
Once the reference has been connected to the voltage input (e.g. 10 V), use the Reference drop-down list box to select this value. Wait, if necessary, for the reference voltage connected to stabilize, then confirm the selection using the Confirm command button. The ranges linked to this reference are then calibrated automatically.
Calibrate the module for other ranges, if applicable.
the command button Return to Factory Settings allows you to cancel all calibrations previously carried out and to return the module to the initial calibration settings configured in the factory.
Click on the Save command button in order to recognize and save the new calibration in the module. If you exit the calibration screen without saving, a message is displayed indicating that the new calibration values will be lost
TLX DS 57 PL7 xxE
115
analog TBXs
Sensor alignment
At a Glance Alignment consists of eliminating systematic deviation observed with a given sensor around a given operating parameter. An error linked to the process is compensated for. For this reason, replacing a module does not necessitate a new alignment, whereas the replacement of the sensor or modification of the operating parameter of this sensor does necessitate a new alignment.
Conversion line after alignment
Initial conversion line
Example
Alignment values
Let us suppose that a pressure sensor, linked to a conditioning unit (1mV/mB), indicates 3200 mB, whereas the actual pressure is 3210 mB.
The value measured by the module in standardized scale will be 3200 (3.20 V). The user can align the measurement to the value 3210 (value required).
After this alignment procedure, the measurement channel will apply a systematic offset of +10. The alignment value that must be entered is 3210.
The alignment value can be modified from the PL7 screen, even when the program is in RUN mode.
For each input channel, the user can: l l l view and modify the required measurement value, save the alignment value, see if the channel already possesses an alignment.
The alignment offset can also be changed by program.
Alignment is performed on the channel under normal usage, without affecting the module channel operating modes. The maximum difference between the value measured and the value required (aligned value) must not exceed 1000.
The alignment offset is stored in the word %Mwxy.i.8.
116
TLX DS 57 PL7 xxE
analog TBXs
3.3
TBX ASS 200 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the TBX ASS 200 rack-based module.
This Section contains the following Maps:
Topic
Introducing the TBX ASS 200 module
Output characteristics for the TBX ASS 200 module
Fault handling
Monitoring under/overshoots for the TBX ASS 200 module
Page
TLX DS 57 PL7 xxE
117
analog TBXs
Introducing the TBX ASS 200 module
General
Overview
The TBX ASS 200 base unit is an analog output module containing 2 insulated l l channels. It must be associated with a TBX LEP 030 communicator. This module offers the following ranges for each of its outputs:
Voltage: 10V,
Current: 0/20 mA and 4/20 mA.
The TBX ASS 200 module associated with the TBX LEP 030 communicator supports the following functions: l refreshing the digital values corresponding to the analog output values transmitted by the PLC, l l l processing dialog errors with the PLC, range selection for each output: voltage, current, digital analog conversion.
Overview of the TBX ASS 200 module associated with the TBX LEP 030 communicator:
Writing outputs
Channel 1
Channel 0
Output 0
Output 1
Digital
Analog
Conversion
Processes:
- refreshing
- error handling
- range selection
3
2
1
Bus interface
4
Channel 0
Channel 1
FIPIO
24/48V
Supply
118
TLX DS 57 PL7 xxE
Description analog TBXs
The TBX ASS 200 module associated with the TBX LEP 030 communicator supports the following functions:
2
3
Address Function
1 refreshing the digital values transmitted by the processor,
4 processing PLC dialog faults, range selection for each output: voltage, current, digital analog conversion.
Note: One channel can only be used in a single range, i.e. current or voltage.
TLX DS 57 PL7 xxE
119
analog TBXs
Output characteristics for the TBX ASS 200 module
Writing outputs
Refreshing the outputs via the module
The user can access two words via the program (1 word of 16 bits per channel), where the analog output values are given. l l from 0 to 10000 (or 0 °/ mA,
°°°
à 10000 °/
°°°
) for unipolar ranges 0/20 mA and 4/20 from -10000 to +10000 (-10.000 °/
°°°
to +10.000 °/
°°°
) for bipolar range +/-10 V.
The outputs are refreshed every 5 ms
The response time between the output write via the program and updating the output at the module terminals depends on the period of the PLC task where the module is configured.
120
TLX DS 57 PL7 xxE
analog TBXs
Fault handling
Dialog faults with the PLC
This type of handling groups together: l l l l l setting the PLC to STOP mode (or the task in which the module is configured), a PLC fault, a link fault between the PLC and the module.
In the above cases, the user has two options for each output: maintain the output at the current value, fallback to a defined value. The value must be selected between the normal display limits (0/10000) for unipolar ranges or –10000/10000 for the voltage range. By default, the module is configured in fallback to 0 mode.
Internal errors in the module
When the module has an internal error the outputs are forced to 0.
TLX DS 57 PL7 xxE
121
analog TBXs
Monitoring under/overshoots for the TBX ASS 200 module
Introduction
Range characteristics
The TBX ASS 200 module contains an under/overshoot monitoring device.
The limits and specifications for the different ranges are as follows:
Range
+/-10V
0.20mA
0
4.20mA
0
Lower limit Upper limit
-10000 +10000
+10000
+10000
Precision conversion on 11 bits + sign from -2048 to +2047 points.
conversion on 11 bits from 0 to +2047 points.
conversion on 11 bits from 0 to +2047 points.
Illustration
Analog output value
+10 V
Overshoot indications
-10000
20 mA
Analog output value
10000
Numerical value
-10 V
20 mA
Analog output value
4 mA
0
10000
Numerical value
10000
Numerical value
If the values supplied by the application fall outside the limits, saturation occurs at the value of the limit exceeded. Overshoot is indicated by:
Bit name Meaning
%I\p.2.c\m.channel.ERR
When = 1, Indicates a range over/undershoot on the channel.
122
TLX DS 57 PL7 xxE
The remote analog Momentum modules
4
At a Glance
Aim of this chapter
What's in this
Chapter?
This chapter introduces the remote analog Momentum modules.
This Chapter contains the following Sections:
Section
4.1
4.2
4.3
4.4
4.5
4.6
Topic
170 AAI 030 00 module
170 AAI 140 00 Module
170 AAI 520 40 Module
170 AAO 120 00 Module
170 AAO 921 00 Module
170 AMM 090 00 module
Page
TLX DS 57 PL7 xxE
123
Analog Momentums
4.1
170 AAI 030 00 module
At a Glance
Aim of this
Section?
What's in this
Section?
This Section introduces the AAI 030 00 remote module.
This Section contains the following Maps:
Topic
Introduction to the 170 AAI 030 00 module
Words for the 170 AAI 030 00 module
Page
124
TLX DS 57 PL7 xxE
Analog Momentums
Introduction to the 170 AAI 030 00 module
General The 170 AAI 030 00 analog base features eight isolated inputs. l l l l l
It can be configured according to the following ranges:
+/- 10 V,
+/-5 V,
1…5 V,
+/-20 mA,
4.20 mA.
Configuration of the base
The base uses: l 8 adjacent input words, to send the input analog values of the base to the l processor module,
2 adjacent output words, to define the parameters of each of the 8 inputs.
Note: The 8 analog inputs must be parametered before the base is brought into service.
Conversion time The conversion time depends on the number of declared inputs. A set time is to be systematically added.
Time value:
Type
Conversion time of an input
Set time
Value
1.33 ms
1.33 ms
Illustration
T fixed
Channel 1 Channel 3
Channel 2
Channel 5
Channel 4
Channel 7
Channel 6 Channel 8
1,33ms 1,33ms 1,33ms 1,33ms 1,33ms 1,33ms 1,33ms 1,33ms 1,33ms
Maximum time for 8 declared inputs: 12 ms
TLX DS 57 PL7 xxE
125
Analog Momentums
Words for the 170 AAI 030 00 module
Input values The analog values in input are read or written in one word per channel. Therefore, the 170 AAI 030 00 base uses 8 adjacent words. The sign is always assigned to bit
15 of the word.
The value is left-justified.
The representation format is binary 2’s complement.
The digital/analog conversion is carried out on 12 bits + polarity sign.
The bits 2 … 0 are unused and always at 0. As a result, the read value will be modified in increments of 8 units.
Illustration:
%IW\p.2.c\0.0.0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 to
Sign Value of input 1 Always at 0
%IW\p.2.c\0.0.7
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of input 8 Always at 0
126
TLX DS 57 PL7 xxE
Parameters
Analog Momentums
These words are transmitted via the communicator to the module, in the format of words to configure the operating mode for the inputs. Each nibble of a word corresponds to an analog channel.
The order of the nibbles is as follows:
%MW\p.2.c\0.0.4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 4 Channel 3 Channel 2 Channel 1
%MW\p.2.c\0.0.5
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 8 Channel 7 Channel 6 Channel 5
The value of each nibble is coded according to the following rules:
Nibble value (in binary)
2#0000
2#0010 2
2#0011 3
2#0100 4
2#1001
Value in Hex.
0
9
Meaning reserved
+/-5 VDC and +/-20 mA
+/-10 VDC
1...5 VDC and 4...20 mA
Note: Any value apart from those indicated in the table above is prohibited. The module continues to function with the last valid parameters it received.
TLX DS 57 PL7 xxE
127
Analog Momentums
4.2
170 AAI 140 00 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the 170 AAI 140 00 remote module.
This Section contains the following Maps:
Topic
Introducing the 170 AAI 140 00 module
170 AAI 140 00 module words
Displaying measurements on the 170 AAI 140 00 module
Page
128
TLX DS 57 PL7 xxE
Analog Momentums
Introducing the 170 AAI 140 00 module
General The analog base unit 170 AAI 140 00 has 16 common point inputs which are mutually non-insulated.
It can be used for continuous process monitoring, measuring and regulation functions.
l l l
This module also monitors wire breaking.
It can be configured according to the following ranges:
+/-10 V,
+/-5 V,
4.20 mA.
Configuration of the base unit
The base unit uses: l 16 contiguous input words, to send the analog values input at the base unit back to the processor module, l 4 contiguous output words, to define the parameters of each of the 16 inputs.
Note: The 16 analog inputs must have parameters before the base unit is put into service.
Conversion time The conversion time depends on the number of registered inputs. A fixed time is added systematically.
Time values:
Type
Conversion time for an input
Fixed time
Value
1.5 ms
1.5 ms
Illustration
Channel 1
T fixed
Channel 3
Channel 2
Channel 5
Channel 4
1ms 1,5ms 1,5ms 1,5ms 1,5ms 1,5ms
Channel 15
Channel 14 Channel 16
1,5ms 1,5ms 1,5ms
Maximum time for 16 declared inputs: 25 ms
TLX DS 57 PL7 xxE
129
Analog Momentums
170 AAI 140 00 module words
Input values The input analog values are read or written in one word per channel. The base unit
170 AAI 140 00 therefore use 16 contiguous words. The sign is always assigned to bit 15 of the word.
The value is left justified.
The representation format is binary, two’s complement.
Analog digital conversion is performed on 12 bits + polarity sign (bipolar ranges).
Bits 2 … 0 are unused and always at 0. Hence the reading value will be modified in increments of 8 units.
Illustration:
%IW\p.2.c\0.0.0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of input 1 Always at 0 to
%IW\p.2.c\0.0.15
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of input 16 Always at 0
130
TLX DS 57 PL7 xxE
Parameters
Analog Momentums
These parameters are transmitted via the communicator to the module in the form of words to configure the input operating mode. Each nibble of a word corresponds to an analog channel.
The nibbles are in the following order:
%MW\p.2.c\0.0.20
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 4 Channel 3 Channel 2 Channel 1
%MW\p.2.c\0.0.21
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 8 Channel 7 Channel 6 Channel 5
%MW\p.2.c\0.0.22
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 12 Channel 11 Channel 10 Channel 9
%MW\p.2.c\0.0.23
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 16 Channel 15 Channel 14 Channel 13
The value of each quartet is encoded according to the following rules:
Nibble value (binary)
2#0000
2#1010
2#1011
2#1100 C
2#1110 E
A
B
Value in Hexa
0
Meaning reserved.
+/-5 VDC.
+/-10 VDC.
4..20 mA.
Note: All parameter values other than those indicated in the table above are forbidden. The module continues to function with the last valid parameters it received.
TLX DS 57 PL7 xxE
131
Analog Momentums
Displaying measurements on the 170 AAI 140 00 module
Range +/-10V
Range +/-5V
The digital value transmitted by the base unit, based on the analog input voltage, is determined by the formula:
Vn = 3200 x Va (in volts).
Illustration:
Vn
32767
32000
-10.2397 V -10 V
10 V
10.2397 V
Va
-32000
-32767
Reminder: the resolution is on 12 bits + sign
The digital value transmitted by the base unit, based on the analog input voltage, is determined by the formula:
Vn = 6400 x Va (Va in volts).
Illustration:
Vn
32767
32000
-5,1198 V -5 V
5 V
5,1198 V
Va
-32000
-32767
Reminder: the resolution is on 12 bits + sign
132
TLX DS 57 PL7 xxE
Analog Momentums
Range 4...20 mA In current range 3.6165 … 20.3835 mA, the value transmitted by the base unit, based on the input current (Ia) is determined by the formula:
Vn = 2000 x Ia - 8000 (Ia in mA).
Illustration:
Vn
32767
32000
-1 mA +1 mA
+4 mA
-767
+20 mA +20,3835 mA
Ia
-32767
Reminder: the resolution is on 12
TLX DS 57 PL7 xxE
133
Analog Momentums
4.3
170 AAI 520 40 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the 170 AAI 520 40 remote module.
This Section contains the following Maps:
Topic
Introducing the 170 AAI 520 40 module
170 AAI 520 40 module words
Displaying measurements on the 170 AAI 520 40 module
Page
134
TLX DS 57 PL7 xxE
Analog Momentums
Introducing the 170 AAI 520 40 module
General The base unit 170 AAI 520 40 has four differential analog inputs. The inputs associated with the thermowells or thermocouples, support temperature monitoring, measurement and regulation functions. They can also be configured as voltage inputs in mV.
l l l l l
The base unit recognizes wire breaks.
This base unit has 4 analog inputs which can be configured with the following ranges:
+/-100 mV,
+/-25 mV,
Temperature probe Pt100, Pt1000,
Temperature probe Ni100 or Ni1000,
Thermocouple B, E, J, K, N, R, S or T.
Configuration of the base unit
The base unit uses: l 4 contiguous input words, to send the analog values at the inputs of the base unit back to the processor module, l 4 contiguous output words, to define the parameters of each of the 4 inputs.
Note: The 16 analog inputs must be assigned parameters before the base unit is put into service.
Conversion time The conversion time is independent of the number of registered inputs.
Conversion time = 500ms
TLX DS 57 PL7 xxE
135
Analog Momentums
170 AAI 520 40 module words
Input values The input analog values are read or written in one word per channel. The base unit
170 AAI 520 40 therefore uses 4 contiguous words. The sign is always assigned to bit 15 of the word.
The value is left justified.
The representation format is binary, two’s complement.
Analog digital conversion is performed on 15 bits + polarity sign.
Illustration:
%IW\p.2.c\0.0.0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 to
Sign Value of input 1
%IW\p.2.c\0.0.3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of input 4
Parameters These parameters are transmitted via the communicator to the module in the form of words, to configure the input operation mode. The parameter corresponds: to the type of sensor, to the selected unit of temperature, to the need for a wiring check.
%MW\p.2.c\0.0.4
to
%MW\p.2.c\0.0.7
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel parameters
Thermocouple ranges:
Range Temperature
Thermocouple B 1/10 degrees C
1/10 degrees F
Wiring check inactive active inactive active
Parameter word
(hexa)
2201
2301
2281
2381
136
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
Range Temperature
Thermocouple E 1/10 degrees C
1/10 degrees F
Thermocouple J 1/10 degrees C
1/10 degrees F
Thermocouple K 1/10 degrees C
1/10 degrees F
Thermocouple N 1/10 degrees C
1/10 degrees F
Thermocouple R 1/10 degrees C
1/10 degrees F
Thermocouple S 1/10 degrees C
1/10 degrees F
Thermocouple T 1/10 degrees C
1/10 degrees F
Wiring check inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active
Analog Momentums
2287
2387
2208
2308
2288
2388
1285
1385
2206
2306
2286
2386
2207
2307
1283
1383
1204
1304
1284
1384
1205
1305
Parameter word
(hexa)
1202
1302
1282
1382
1203
1303
137
Analog Momentums
138
Ranges PT100, PT1000, Ni 100 and Ni 1000:
Range Cabling Temperature
IEC PT100 RTD
IEC PT1000 RTD
2 or 4 wires
3 wires
2 or 4 wires
3 wires
US/JIS PT100 RTD 2 or 4 wires
3 wires
US/JIS PT1000 RTD 2 or 4 wires
3 wires
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active inactive active
Wiring check Parameter word (hexa) inactive active
0A20
0B20 inactive active inactive active
0AA0
0BA0
0E20
0F20
0221
0321
0221
0321
02A1
03A1
0621
0721
0EE0
0FE0
0261
0361
02E1
03E1
0661
0761
06E1
07E1
06A1
07A1
0A60
0B60
0AE0
0BE0
0E60
0F60
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
Analog Momentums
Range
DIN Ni 100 RTD
DIN Ni 1000 RTD
Voltage ranges
Range Wiring check
+/-25mV
+/-100mV inactive active active inactive
Cabling
2 or 4 wires
3 wires
2 or 4 wires
3 wires
Temperature
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F
1/10 degrees C
1/10 degrees F inactive active inactive active inactive active inactive active inactive active
Wiring check Parameter word (hexa) inactive active
0A23
0B23 inactive active inactive active
0AA3
0BA3
0E23
0F23
0EA3
0FA3
0222
0322
02A2
03A2
0622
0722
06A2
07A2
Parameter word
(hexa)
2210
2310
1211
1311
139
Analog Momentums
Displaying measurements on the 170 AAI 520 40 module
Display for the range +/-100 mV
The digital value transmitted by the base unit, based on the analog input voltage is determined by the formula:
Vn = 320 x Va (Va in mV)
Illustration:
Vn
32767
32000
-102.326 mV -100 mV
100 mV
102.326 mV
Va
-32000
-32767
Display for the range +/-25 mV
The digital value transmitted by the base unit, based on the analog input voltage is determined by the formula:
Vn = 1280 x Va (Va in mV)
Illustration:
Vn
32767
32000
-25.599 mV -25 mV
25 mV 25.599 mV
Va
-32000
-32767
Ranges for thermal probes
140
If a Probe or Thermocouple input range is selected, the digital value transmitted is the temperature value directly expressed either in tenths of a degree Celsius or in tenths of a degree Fahrenheit, according to the unit of temperature selected in configuration.
TLX DS 57 PL7 xxE
4.4
170 AAO 120 00 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the 170 AAO 120 00 remote module.
This Section contains the following Maps:
Topic
Introducing the 170 AAO 120 00 module
Words of base unit 170 AAO 120 00
Measurement correspondence on the 170 AAO 120 00 module
Analog Momentums
Page
TLX DS 57 PL7 xxE
141
Analog Momentums
Introducing the 170 AAO 120 00 module
General The base unit 170 AAO 120 00 has 4 analog outputs for controlling actuators in continuous movement, such as variable speed drives, proportional valves or electropneumatic converters.
This module can be configured according to the following ranges: l l
+/-10 V,
0 ... 20 mA.
Configuration of the base unit
The base unit uses: l 4 contiguous input words, to write the output analog values of the processor module to the base unit, l 1 word, to define the parameters of each of the 4 outputs.
Note: The 4 analog outputs must have parameters before the base unit is put into service.
Cycle time The cycle time is independent of the number of registered outputs.
Cycle time = 2 ms
142
TLX DS 57 PL7 xxE
Analog Momentums
Words of base unit 170 AAO 120 00
Output values
%QW\p.2.c\0.0.0
The output analog values are written in one word per channel. The base unit 170
AAO 120 00 therefore uses 4 contiguous words. The sign is always assigned to bit
15 of the word.
The value is left justified.
The representation format is binary, two’s complement.
Analog digital conversion is performed on 12 bits + polarity sign (in +/-10 V).
Bits 2 … 0 are unused and always at 0. Hence the reading value will be modified in increments of 8 units.
Illustration:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of output 1 Always at 0 to
%QW\p.2.c\0.0.3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of output 4 Always at 0
TLX DS 57 PL7 xxE
143
Analog Momentums
Parameters These parameters are transmitted via the communicator to the module in the form of a word, to configure the input operation mode. Each nibble of this word corresponds to an analog channel.
The nibbles are in the following order:
%MW\p.2.c\0.0.4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 4 Channel 3 Channel 2 Channel 1
The value of each nibble is encoded according to the following rules:
Meaning Nibble value (binary) Value in
Hexa
2#0000
2#00x1
0
1 or 3
2#01x1
2#10x1
5 or 7
9 or B reserved.
Output configured to zero by default: sends a value to the base unit which makes it force the actuators to zero (0 V or 0 mA).
Output configured to full scale by default: sends a value to the base unit which makes it force the actuators to the full scale value (+10 V or +20 mA).
Output configured to the last displayed value by default.
x has a value of either 0 or 1
Note: All parameter values other than those indicated in the table above are prohibited. The module continues to function with the last valid parameters it received.
144
TLX DS 57 PL7 xxE
Analog Momentums
Measurement correspondence on the 170 AAO 120 00 module
Range +/-10 V The digital value of the output voltage transmitted by the base unit is determined by the formula:
Va = 1/3200 x Vn in volts.
Illustration:
Va
10 V
-32000
32000
Vn
-10 V
Range 0...20 mA The digital value of the output current is determined by the following formula:
1a = 1/1600 x Vn in mA.
Illustration:
Ia
20 mA
0
32000
Vn
TLX DS 57 PL7 xxE
145
Analog Momentums
4.5
170 AAO 921 00 Module
At a Glance
Aim of this section?
What's in this
Section?
This section introduces the 170 AAO 921 00 remote module.
This Section contains the following Maps:
Topic
Introducing the 170 AAO 921 00 module
170 AAO 921 00 module words
Measurement correspondence on the 170 AAO 921 00 module
Page
146
TLX DS 57 PL7 xxE
Analog Momentums
Introducing the 170 AAO 921 00 module
General The base unit 170 AAO 921 00 has 4 analog outputs for controlling actuators in continuous movement, such as variable speed drives, proportional valves or electropneumatic converters.
This module can be configured according to the following ranges: l l
+/-10 V,
4 ... 20 mA.
Configuration of the base unit
The base unit uses: l 4 contiguous words to write the output analog values of the processor module to the base unit, l 1 word, to define the parameters of each of the 4 outputs.
Note: The 4 analog outputs must be assigned parameters before the base unit is put into service.
Cycle time The cycle time is independent of the number of registered outputs.
Cycle time = 2 ms
TLX DS 57 PL7 xxE
147
Analog Momentums
170 AAO 921 00 module words
Output values
%QW\p.2.c\0.0.0
The output analog values are written in one word per channel. The base unit 170
AAO 921 00 therefore uses 4 contiguous words. The sign is always assigned to bit
15 of the word.
The value is left justified.
The representation format is binary, two’s complement.
Analog digital conversion is performed on 12 bits + polarity sign (in +/-10 V).
Bits 2 … 0 are unused and always at 0. Hence the reading value will be modified in increments of 8 units.
Illustration:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of output 1 Always at 0 to
%QW\p.2.c\0.0.3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of output 4 Always at 0
148
TLX DS 57 PL7 xxE
Parameters
Analog Momentums
These parameters are transmitted via the communicator to the module in the form of a word, to configure the input operation mode. Each nibble of this word corresponds to an analog channel.
The nibbles are in the following order:
%MW\p.2.c\0.0.4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 4 Channel 3 Channel 2 Channel 1
The value of each nibble is encoded according to the following rules:
Nibble value (binary) Value in
Hexa
2#0000
2#00x1
0
1 or 3
2#01x1
2#10x1
5 or 7
9 or B
Meaning reserved.
Output configured to zero by default: sends a value to the base unit which makes it force the actuators to zero (4 V or 0 mA).
Output configured to full scale by default: sends a value to the base unit which makes it force the actuators to the full scale value (+10 V or +20 mA).
Output configured to the last displayed value by default.
x has a value of either 0 or 1
Note: All parameter values other than those indicated in the table above are prohibited. The module continues to function with the last valid parameters it received.
TLX DS 57 PL7 xxE
149
Analog Momentums
Measurement correspondence on the 170 AAO 921 00 module
Range +/-10 V The digital value of the output voltage transmitted by the base unit is determined by the formula:
Va = 1/3200 x Vn in volts.
Illustration:
Va
10 V
-32000
32000
Vn
-10 V
Range 4...20 mA The digital value of the output current is determined by the following formula: la = 1/20000 x Vn + 4 in mA.
Illustration:
Ia
20 mA
4 mA
32000 Vn
150
TLX DS 57 PL7 xxE
4.6
170 AMM 090 00 module
At a Glance
Aim of this
Section
What's in this
Section?
This Section introduces the 170 AMM 090 00 remote module.
This Section contains the following Maps:
Topic
Introduction to the 170 AAM 090 00 module
170 AAM 090 00 module words
Displaying measurements in the module 170 AMM 090 00
Analog Momentums
Page
TLX DS 57 PL7 xxE
151
Analog Momentums
Introduction to the 170 AAM 090 00 module
General The 170 AAM 090 00 analog base is a mixed module.
It has analog channels and discrete channels: l l l
4 differential inputs,
2 analog outputs,
4 24 VDC discrete inputs, l 2 24 VDC/ 0.5 A discrete outputs.
The discrete inputs are used to directly connect 2-wire proximity sensors. A thermal protection device protects every output from short-circuits and overloads. The outputs remain tripped until the fault disappears.
The analog inputs of this base can be configured with the following ranges: l l l l l l l
+/- 10 V,
+/-5 V,
1-5 V,
+/- 20 mA,
4-20 mA.
The analog outputs can be configured with the following ranges:
+/- 10 V,
4-20 mA.
Configuration of the base l l l
The base uses: l 4 adjacent input words, to send the input analog values from the base to the processor module,
2 adjacent output words, to define the parameters of each of the 16 inputs,
1 word to exchange with the discrete inputs,
1 word to exchange with the discrete outputs.
Note: The 16 analog inputs must be parametered before the base is brought into service.
Conversion time The conversion times are fixed regardless of the number of analog inputs or outputs used.
Time value:
Type
Analog input conversion times
Analog output conversion times
Value
10 ms
1 ms
152
TLX DS 57 PL7 xxE
Analog Momentums
170 AAM 090 00 module words
Discrete inputs The 170 AMM 090 00 base sends four discrete input bits (and an error detected message if necessary) to the master in a 16 bit word. The inputs are connected to base connector 2.
Illustration:
%IW\p.2.c\0.4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Terminal block 1
I4 I3 I2 I1
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Discrete outputs The master sends two discrete output bits to the base in a single 16 bit word. The outputs are connected to connector 3.
Illustration:
%QW\p.2.c\0.2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Terminal block 1
Analog inputs
16
O2
15 14
O1
13 12 11 10 9 8 7 6 5 4 3 2 1
The analog values in input are read or written in one word per channel. The 170 AAM
090 00 base uses 4 adjacent words. The sign is always assigned to bit 15 of the word.
The value is left-justified.
The representation format is binary 2’s complement.
The analog digital conversion is carried out on 12 bits + polarity sign (for bipolar ranges).
Bits 2 … 0 are unused and always at 0. As a result, the read value will be modified in increments of 8 units.
TLX DS 57 PL7 xxE
153
Analog Momentums
Illustration:
%IW\p.2.c\0.0.0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of input 1 Always at 0 to
%IW\p.2.c\0.0.3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of input 4 Always at 0
Output values
%QW\p.2.c\0.0.0
to
The analog values in outputs are written in one word per channel. The base uses 2 adjacent words.
The format is identical to the analog inputs.
Illustration:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of output 1 Always at 0
%QW\p.2.c\0.0.1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Sign Value of output 2 Always at 0
Parameters for analog inputs
These parameters are transmitted via the communicator to the module, in the format of words to configure the operating mode for the inputs. Each nibble of a word corresponds to an analog channel.
The order of the nibbles is as follows:
%MW\p.2.c\0.0.4
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Channel 4 Channel 3 Channel 2 Channel 1
The value of each nibble is coded according to the following rules:
Nibble value (in binary)
2#0000
2#0010
2#0011
2
3
Value in Hex.
0
Meaning reserved
+/-5 VDC or +/-20 mA
+/-10 VDC
154
TLX DS 57 PL7 xxE
Nibble value (in binary) Value in Hex.
2#0100 4
2#1010 A
Analog Momentums
Meaning
1...5V or 4...20 mA
Parameters for analog outputs
%MW\p.2.c\0.0.4
These parameters are transmitted via the communicator to the module, in the format of a word to configure the operating mode for the outputs. Each nibble of this word corresponds to an analog channel.
The order of the nibbles is as follows:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Reserved Reserved Channel 2 Channel 1
The value of each nibble is coded according to the following rules:
Meaning Nibble value (in binary)
2#0000
2#00x1
2#01x1
2#10x1
Value in
Hex.
0
1 or 3
5 or 7
9 or B reserved
Output configured by default to zero: sends a value to the base that makes it force the actuators to zero (0
V or 0 mA).
Output configured by default to full scale: sends a value to the base that makes it force the actuators to the full scale value (+10 V or +20 mA).
Output configured by default to the last displayed value x equals 0 or 1 (doesn't matter)
Note: Any parameter value apart from those indicated in the tables above is prohibited. The module continues to function with the last valid parameters it received.
TLX DS 57 PL7 xxE
155
Analog Momentums
Displaying measurements in the module 170 AMM 090 00
Input range +/-
10V
The voltage value is calculated using the following formula with the help of the digital measurement values:
Vn = 3200 x Va in volts (for the linear zone)
Illustration
Vn
(overshoot error) 32767
32760
32000
<-10.238 V
-10.238 V
-10 V
10 V > 10.238 V
10.238 V
Va
-32000
-32760
-32767 (undershoot
error)
: linear zone
Reminder: the resolution is on 12 bits + sign
Input range
+/- 5V
The voltage value is calculated using the following formula with the help of the digital measurement values:
Vn = 6400 x Va in volts (for the linear zone).
156
TLX DS 57 PL7 xxE
Analog Momentums
Illustration
Vn
(overshoot error) 32767
32752
32000
<-5.118 V
-5.118 V
-5 V
5 V
5.118 V
> 5.118 V
-32000
-32752
-32767 (undershoot
error))
: linear zone
Va
Reminder: the resolution is on 12 bits + sign
Input range
+/- 20 mA
The current value is calculated using the following formula with the help of the digital measurement values:
Vn = 1600 x Ia in mA (for the linear zone).
Illustration
Vn
(overshoot error) 32767
32752
32000
<-20,470 mA
-20,470 mA
-20 mA
20 mA > 20,470 mA
20,470 mA
Ia
-32000
-32752
-32767 (undershoot
error)
: linear zone
Reminder: the resolution is on 12 bits + sign
TLX DS 57 PL7 xxE
157
Analog Momentums
Input range 1-5 V The voltage value is calculated using the following formula with the help of the digital measurement values:
Vn = 8000 x Va in volts (for the linear zone).
Illustration:
Vn
(overshoot error) 32767
32752
32000
-766
(undershoot error) -768
<0.5 V
1 v
5 V >5.094 V
5.094 V
0.904 V
Va
: linear zone
-32738 (wire break)
Reminder: the resolution is on 12 bits
Input range
4-20 mA
The current value is calculated using the following formula with the help of the digital measurement values:
Vn = 2000 x Ia in mA (for the linear zone).
158
TLX DS 57 PL7 xxE
Illustration:
Analog Momentums
(overshoot error) 32767
32752
32000
Vn
-766
(undershoot error) -768
<2 mA
4 mA
20 mA >20.376 mA
20.376 mA
Ia
<3.617 mA
: linear zone
-32738 (wire break)
Reminder: the resolution is in 12 bits
Note: Inactive channels deliver a value of 0
Output range +/-
10 V
The digital value of the output voltage transmitted by the base is determined by the formula:
Va = 1/3200 x Vn in volts.
Illustration:
Va
10 V
-32000
32000
Vn
-10 V
TLX DS 57 PL7 xxE
159
Analog Momentums
Output range
0…20 mA
Note: When the bus is restarting, the outputs use the configured parameters. If the module has no valid parameter, the outputs are initialized at 0 V.
The digital value of the output current is determined by the following formula: la = 1/1600 x Vn in mA.
Illustration:
Ia
20 mA
0
32000
Vn
Note: When the bus is restarting, the outputs use the configured parameters. If the module has no valid parameter, the outputs are initialized at 0 V.
160
TLX DS 57 PL7 xxE
Module configuration
5
At a Glance
Aim of this
Chapter?
What's in this
Chapter?
This chapter shows how to configure an analog input/output module.
This Chapter contains the following Sections:
Section
5.1
5.2
5.3
5.4
Topic
Configuring the analog application: General
Parameters for analog input channels
Parameters for analog output channels
Module configurations (illustrations)
Page
TLX DS 57 PL7 xxE
161
Configuration
5.1
Configuring the analog application: General
At a Glance
Aim of this
Section
What's in this
Section?
This section describes the basic operations required to configure the analog application.
This Section contains the following Maps:
Topic
Description of the configuration screen of a racked TBX analog module
Description of the configuration screen of a Momentum analog module
How to access the configuration parameters of a racked analog module
How to access the configuration parameters of a remote analog module on the
FIPIO bus
Modifying channel parameters of an analog module: General
Page
162
TLX DS 57 PL7 xxE
Configuration
Description of the configuration screen of a racked TBX analog module
At a Glance
Illustration
The configuration screen of the selected analog module in the rack displays the parameters that are associated to it.
This screen provides access to the display and modification of parameters in offline mode, as well as to Debugging in online mode.
1 TSX AEY 1600 [RACK 0 POSITION 2]
Configuration
Designation: 16E ANA. HIGH LEVEL
Cycle
Normal
Fast
Terminal block detection
4
7
8
5
6
9
10
11
12
13
14
Channel
0
3
4
1
2
15
Used
MAST
Task
MAST
MAST
MAST
Symbol Range
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
%..
%..
%..
%..
%..
%..
%..
%..
%..
%..
Scale
%..
%..
%..
%..
%..
%..
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Filter
TLX DS 57 PL7 xxE
163
Configuration
Description The table below shows the different elements of the configuration screen and their functions.
Address Element
1 Title bar
2
3
4
Function
Gives the reference of the selected module and its physical position in the PLC.
Command zone Is used to display and select the type of parameters: l l operating mode (e.g.:
Debugging
Configuration ),
mode (diagnostics), only accessible when in online mode.
Module zone Gives a short name for the module and supplies supplementary information for certain modules, such as: l l l the input scanning the Cold Junction the output
Cycle ,
compensation made,
Fallback mode .
Channel zone Shows the parameters configured for each of the analog module channels.
164
TLX DS 57 PL7 xxE
Configuration
Description of the configuration screen of a Momentum analog module
At a Glance
Illustration
The configuration screen of the selected analog module displays the parameters that are associated with it.
This screen provides access to the display and modification of parameters in offline mode, as well as to Debugging in online mode.
1
2
170 AAI 140 00 [FIPIO2 MODULE 0]
Adjustment
Designation: 16 IN ANA COMMON POINT
3
Channel 0 Task: MAST
4
Default parameters
Input 0
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Label
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
4..20mA
Channel inactive
4..20mA
4..20mA
4..20mA
Value
Base
TLX DS 57 PL7 xxE
165
Configuration
Description
Address Element
1 Title bar
2
3
4
The table below shows the different elements of the configuration screen and their functions.
Command zone
Module zone
Channel zone
Function
Gives the reference of the selected module and its physical position on the FIPIO bus.
Is used to display and select the type of parameters: l l
Configuration
Adjustment
enables modification of the
enables modification of the
Module
Channel
zone,
zone.
Note: Adjustment is not allowed unless the PLC is in RUN mode.
Gives a short name for the module and provides complementary information: l the channel scanning Cycle .
Shows the value configured for each of the analog module channels.
Note: The assignment of a channel in the task is fixed in configuration mode and the type of channel is fixed in adjustment mode.
166
TLX DS 57 PL7 xxE
Configuration
How to access the configuration parameters of a racked analog module
Procedure This operation is used to access the configuration parameters of the channels of a module.
Step
1
2
Action
Access the module hardware configuration screen.
Double-click on the module to be configured or select the module then perform the
Facility
→
Open module command.
Result: The configuration screen of the selected module appears.
TSX AEY 800 [RACK 0 POSITION 10]
Configuration
Designation: 8I ANA. HIGH LEVEL
Cycle
Normal
Fast
Terminal block detection
Channel
0
1
2
3
4
5
6
7
Used
MAST
Task
MAST
Symbol Range
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
Scale
%..
%..
%..
%..
%..
%..
%..
%..
0
0
0
0
0
0
0
0
Filter
Some modules have a dialog box that enables the complementary parameters to be accessed.
To access this dialogue box perform one of the following: l right-click on the line of the table corresponding to the channel to be parametered l then select the Properties command in the drop-down menu, double left-click on the line of the table corresponding to the channel to be parametered, l select a cell of the channel to be parametered then confirm with Enter.
TLX DS 57 PL7 xxE
167
Configuration
Example of complementary parametering screen:
TSX AEY 800 [RACK 0 POSITION 10]
Configuration
Designation: 8I ANA. HIGH LEVEL
Cycle
Normal
Fast
Terminal block detection
3
4
5
6
7
Channel
0
1
2
Used
MAST
Task
MAST
Symbol Range
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
Channel 7 parameters
Scale
%..
%..
%..
%..
%..
%..
%..
%..
Scale
-100% ->
Display
-10000
0
0
0
0
0
0
0
0
100% ->
Filter
10000
168
TLX DS 57 PL7 xxE
Configuration
How to access the configuration parameters of a remote analog module on the
FIPIO bus
Procedure This operation is used to access the configuration parameters of the channels of a remote analog module on the bus:
2
3
Step
1
Action
Access the module hardware configuration screen.
Double click on the FIPIO zone of the processor.
Double-click on the module to be configured or select the module then perform the
Facility
→
Open module command.
Result: The configuration screen of the selected module appears:
TBX AMS 620 [FIPIO 64 MODULE 0]
Configuration
Designation: 6 IN HL 2 OUT ANA
Channel
0
Task
MAST
1
2
3
4
5
Symbol Range
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
+/- 10 V
Scale
%..
%..
%..
%..
%..
%..
0
0
0
0
0
0
Filter
Channel Task
6
7
MAST
Symbol Range Fallback Value
+/- 10 V 0
+/- 10 V 0
TLX DS 57 PL7 xxE
169
Configuration
Modifying channel parameters of an analog module: General
Introduction
Access the contextual menus.
The configuration editor offers a group of functions which are used to facilitate entry l l l or modification of module parameters such as: the contextual menus, single or multiple selection of channels, copy/paste parameters (using contextual menus).
They can be accessed by right-clicking on the mouse, and are used for fast access to the main commands.
Then the available functions are … If the element to be selected is
… the cell the module zone (outside table)
Copy parameters
Paste parameters
Cancel modifications
Confirm
Animate
Select a channel or a cell
The table below shows the procedure for selecting a channel or the cell of a channel in a module:
Step
1
Action
Left click on the number of the required channel or cell.
Select a group of consecutive channels
The table below shows the procedure for selecting a group of consecutive channels in a module:
Step
1
2
Action
Select the first channel.
Press Shift and click on the last channel.
170
TLX DS 57 PL7 xxE
Configuration
Select a group of unconsecutive channels
The table below shows the procedure for selecting a group of unconsecutive channels in a module:
Step
1
2
Action
Select the first channel.
Press Ctrl and click successively on each of the channels.
Select a group of consecutive cells
The table below shows the procedure for selecting a group of consecutive cells in a module:
Step
1
2
Action
Select the first cell.
Drag the mouse downwards or upwards while keeping the mouse button depressed, then release it when the last cell has been reached.
TLX DS 57 PL7 xxE
171
Configuration
5.2
Parameters for analog input channels
At a Glance
Aim of this
Section
What's in this
Section?
This section shows the different input channel parameters by type of analog module.
This Section contains the following Maps:
Topic
Input parameters for racked analog modules
Input parameters for remote TBX analog modules
Input parameters for remote Momentum analog modules
Page
172
TLX DS 57 PL7 xxE
Configuration
Input parameters for racked analog modules
At a Glance
Parameters
Analog input modules have parameters for each channel displayed in the module configuration screen.
Parameters for each of the modules (the default parameters are in bold in the tables)
Parameter
Number of input channels
Terminal block detection
Range undershoot monitoring
TSX AEY 1600
16
Channel used Yes / No
Scanning cycle
Range
Normal
Fast
+/-10 V
0..10 V
0..5 V
1..5 V
0..20 mA
4..20 mA
Filtering
Display
0 ..6
% oo
User
MAST / FAST Task associated to the channel
Group of channels affected by the modification of the task
4 consecutive channels
Yes / No
-
TSX AEY 800
8
Yes
Fast
0 ..6
% oo
User
/ No
Normal
+/-10 V
0..10 V
0..5 V
1..5 V
0..20 mA
4..20 mA
Yes / No
Normal
Fast
+/-10 V
0..10 V
0..5 V
1..5 V
0..20 mA
4..20 mA
0 ..6
% oo
User
MAST / FAST MAST / FAST
4 consecutive channels
Yes /
-
No
TSX AEY 810
8
4 consecutive channels
Yes /
Yes
No
/ No
TSX AEY 420
4
Yes / No
-
+/-10 V
0..10 V
0..5 V
1..5 V
0..20 mA
4..20 mA
-
% oo
User
MAST / FAST
2 consecutive channels
Yes / No
Yes / No
TLX DS 57 PL7 xxE
173
Configuration
174
Parameter
Range overshoot monitoring
Range undershoot limit
Range overshoot limit
Threshold 0
Threshold 1 event processing
-
-
-
TSX AEY 1600 TSX AEY 800 TSX AEY 810
Yes / No
-
-
-
-
-
-
min-12.5% max+12.5%
-
-
-
TSX AEY 420
Yes / No min-12.5% max+12.5%
0
0
Yes / No
Parameters for each of the modules (the default parameters are in bold in the tables).
Parameter TSX AEY 414
Number of input channels
4
Channel used -
Scanning cycle -
Range
TSX AEY 1614
16
Yes / No
Normal
Fast
+/-10 V / 0..10 V /0..5 V / 1..5 V
0..20 mA / 4..20 mA
Pt100 / Pt1000 / Ni1000 / Thermo B
/ Thermo E / Thermo J / Thermo K /
Thermo L / Thermo N / Thermo R /
Thermo S / Thermo T / Thermo U
-13..63 mV
0..400 Ohms / 0..3850 Ohms
Thermo K / Thermo B / Thermo E /
Thermo J / Thermo L / Thermo N /
Thermo R / Thermo S / Thermo T /
Thermo U
-80..+80 mV
0 ..6
0 ..6
Filtering
High level
Display
Display thermowells thermocouples
% oo
User
1/10 °C
1/10 °F
% oo
% oo
User
1/10 °C
1/10 °F
% oo
Task associated to the channel
MAST / FAST MAST / FAST
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
Parameter
Group of channels affected by the modification of the task
Terminal block detection
Wiring check
Cold junction compensation
Range undershoot monitoring
Range overshoot monitoring
TSX AEY 414
1 channel
Yes / No
Active /
Internal
-
-
Range undershoot limit
-
Range overshoot limit
-
High precision -
Inactive
/ External
Configuration
TSX AEY 1614
4 consecutive channels
Yes / No
Active / Inactive
Telefast / Pt100 read cold junction
Yes / No
Yes / No min-12.5% max+12.5%
Yes / No
175
Configuration
Input parameters for remote TBX analog modules
At a Glance
Parameters
Remote TBX analog input modules have parameters for each channel displayed in the module configuration screen.
Parameters for each of the modules (the default parameters are in bold in the tables).
Parameter TBX AES 400
Number of input channels
4
Range
TBX AMS 620
6
+/-10 V
+/-5 V
0..20 mA
4..20 mA
Pt100 / Pt1000 / Ni1000
Thermo B / Thermo E / Thermo J /
Thermo K / Thermo L / Thermo N /
Thermo R / Thermo S / Thermo T
+/-20 mV, +/-50 mV
+/-200 mV, +/-500 mV
0 ..6
+/-10 V
0..5 V
0..20 mA
4..20 mA
0 ..6
Filtering
High level
Display
% oo
User
-
% oo
User
Display thermowells thermocouples
1/10°C
1/10 °F
% oo
Task associated to the channel
Sensor check
Rejection
MAST
FAST
Active /
50Hz
Inactive
/ 60Hz
MAST
FAST
-
-
176
TLX DS 57 PL7 xxE
Configuration
Input parameters for remote Momentum analog modules
At a Glance Remote Momentum analog input modules have parameters for each channel displayed in the module configuration screen.
Note: Most of these parameters can only be accessed in the Adjustment (See
Description of the configuration screen of a Momentum analog module, p. 165)
mode of Momentum modules
Parameters
Parameter
Number of input channels
Range
Parameters for each of the modules (the default parameters are in bold in the tables).
170 AAI 030 00 170 AAI 1400 00
8 16
Display thermowells thermocouples
Task associated to all the channels
Wiring test
Cabling
-
-
-
MAST
FAST
170 AAI 520 400
4
170 AMM 090 00
4
+/-10 V
+/-5 V or
+/-20 mA
1..5 V or
4..20 mA
Channel inactive
+/-10 V
+/-5 V
4..20 mA
Channel inactive
-
+/-25 mV
+/-100 mV
EIC Pt100
EIC Pt1000
US/JIS Pt100
US/JIS Pt1000
Ni100 / Ni1000
Thermo B / Thermo E /
Thermo J / Thermo K /
Thermo L / Thermo N /
Thermo R /Thermo S /
Thermo T
+/-10 V
5 V or
4..20mA
1..5 V or
4..20 mA
Channel inactive
1/10 °C
1/10 °F
-
MAST
FAST
-
-
MAST
FAST
Active / Inactive
2 or 4 wires
Only 3 wires for the thermowells
MAST
FAST
-
-
TLX DS 57 PL7 xxE
177
Configuration
5.3
Parameters for analog output channels
At a Glance
Aim of this
Section
What's in this
Section?
This section shows the different output channel parameters by type of analog module.
This Section contains the following Maps:
Topic
Output parameters for racked analog modules
Output parameters for remote TBX analog modules
Output parameters for remote Momentum analog modules
Page
178
TLX DS 57 PL7 xxE
Configuration
Output parameters for racked analog modules
At a Glance
Parameters
Racked analog output modules have parameters for each channel displayed in the module configuration screen.
Parameters for each of the modules (the default parameters are in bold in the tables).
Module
Number of output channels
Range
TSX ASY 410
4
TSX ASY 800
8
+/-10 V
0..20 mA
4..20 mA
+/-10 V
0..20 mA
4..20 mA
High level Display
% oo
(non modifiable) % oo
(non modifiable)
Task associated to the channel
Terminal block detection Yes / No No
Fallback Fallback to 0
Maintain
Fallback to a value
Fallback to 0
Maintain
Fallback to a value
24V supply check
Supply
Range undershoot monitoring
Range overshoot monitoring
/
/
MAST
Yes / No
Yes
/ FAST
/ No
MAST
Yes /
/ FAST
Internal /
Yes
Yes
No
/ No
/ No
External
TLX DS 57 PL7 xxE
179
Configuration
Output parameters for remote TBX analog modules
At a Glance
Parameters
Remote analog output modules have parameters for each channel displayed in the module configuration screen.
Parameters for each of the modules (the default parameters are in bold in the tables).
Module
Number of output channels
Range
TBX AMS 620
2
+/-10 V
0..20 mA
4..20 mA
Display
% oo
Task associated with the channel
Fallback
MAST / FAST
Fallback to 0
Maintain
Fallback to a value
TBX ASS 200
2
+/-10 V
0..20 mA
4..20 mA
% oo
MAST / FAST
Fallback to 0
Maintain
Fallback to a value
180
TLX DS 57 PL7 xxE
Configuration
Output parameters for remote Momentum analog modules
At a Glance Remote analog Momentum output modules have parameters for each channel displayed in the module configuration screen.
Note: Most of these parameters can only be accessed in the Adjustment (See
Description of the configuration screen of a Momentum analog module, p. 165)
mode of Momentum modules
Parameters Parameters for each of the modules (the default parameters are in bold in the tables).
Module
Number of output channels
Range
170 AAO 120 00
4
170 AAO 921 00
4
170 AMM 090 00
2
+/-10 V
0..20mA
MAST / FAST
+/-10 V
4..20mA
MAST / FAST
+/-10 V
0..20mA
MAST / FAST Task associated with all the channels
Fallback Maintain
Fallback to 0
Full scale fallback
Maintain
Fallback to 0
Full scale fallback
Maintain
Fallback to 0
Full scale fallback
TLX DS 57 PL7 xxE
181
Configuration
5.4
Module configurations (illustrations)
At a Glance
Aim of this section
What's in this
Section?
This section introduces most of the procedures for modifying configuration parameters at analog input/output module level.
This Section contains the following Maps:
Topic
Modifying the range of an input or output of an analog module
Modifying the task associated to an analog module channel
Modifying the display format of an input channel as voltage or as current
Modifying display format of a thermocouple or thermowell channel
Modifying the filter value of analog module channels
Modifying the Scanning cycle of the inputs of a racked analog module
Modifying terminal block presence detection in TSX and TBX analog modules
Page
Modifying Input channels used
Modifying overshoot monitoring and event processing selection
Cold junction compensation
High precision mode for TSX AEY 1614 module
Modifying the fallback mode of analog outputs
Modifying parameters common to TBX or TSX output modules
182
TLX DS 57 PL7 xxE
Configuration
Modifying the range of an input or output of an analog module
At a Glance
Procedure
This parameter defines the range of the input or output channel. l l l l
According to the type of module, the input or output range can be: in electrical voltage, in electrical current, thermocouple, thermowell.
The table below shows the procedure for defining the range assigned to the channels of an analog module.
Step
1
2
3
4
Procedure
Access the hardware configuration screen of the required module.
To access the required input channel, click on the browse button in the drop-down menu which is in the Range column of the input channels zone.
Result : a drop-down list appears.
Range
+/-10V
+/-10V
0..20mA
4..20mA
Select the required range.
Confirm the reconfiguration if necessary.
TLX DS 57 PL7 xxE
183
Configuration
Modifying the task associated to an analog module channel
At a Glance This parameter defines the task in which inputs are acquired and outputs are updated.
The task is defined: l l for all the channels of an FIPIO connection point, for a group of 2 or 4 consecutive channels.
Possible options are: l the task MAST , l the task FAST .
Note : It is vital that no more than 2 analog modules, each having 4 channels used, are assigned to the FAST task. If more than 2 are assigned, there is a risk of system problems.
Note: The FAST task is only assigned to input channels in a fast scanning cycle.
Procedure The table below shows the procedure for defining the type of task assigned to the channels of an analog module.
Step
1
2
3
4
Action
Access the hardware configuration screen of the required module.
To access the group of input channels, click on browse button of the drop-down menu situated in the Task column of the input channels zone.
Result : a drop-down list appears:
Task
MAST
MAST
FAST
Select the required task.
Confirm the reconfiguration if necessary.
184
TLX DS 57 PL7 xxE
Configuration
Modifying the display format of an input channel as voltage or as current
At a Glance This parameter defines the display format of a measurement for an analog module l l channel whose range is configured as voltage or as current.
The display format can be: standardized 0..10000 or +10000 ( user ( User ),
% ),
TLX DS 57 PL7 xxE
185
Configuration
Procedure The table below shows the procedure for defining the display scale assigned to an analog module channel.
Step
1
2
3
Action
Access the hardware configuration screen of the required module.
For the required channel, double click on the corresponding box in the Scale column of the input channels zone.
Result : The Channel parameters dialog box appears:
Channel 0 parameters
Scale
-100%->
100%->
Display
-10000
10000
Under/overshoots
Under: -11250
Checked.
Over: 11250
Checked
Event
Event
Threshold 0:
Threshold 1:
0
0
0
4
5
6
Type in the values to be assigned to the channel in the two Display boxes situated in the Scale zone.
Confirm the selection by closing the dialog box
If the default values have been selected (standardized display), the corresponding cell in the Scale zone shows %..
Otherwise, it shows User
(user-defined display)
186
TLX DS 57 PL7 xxE
Configuration
Modifying display format of a thermocouple or thermowell channel
At a Glance This parameter defines the display format of the measurement of an analog module channel whose range is configured in thermocouples or thermowells.
The display format can be for display in degrees Celsius or in degrees Fahrenheit , with signaling of short circuit or open circuit if necessary.
The display format can be: l standardized, which is the default scale of the selected thermocouple of l user-defined ( User ).
TLX DS 57 PL7 xxE
187
Configuration
Procedure The table below shows the procedure for defining the display scale assigned to an analog module channel.
Step
1
2
3
Action
Access the hardware configuration screen of the required module.
For the required channel, double click on the corresponding box in the Scale column of the input channels zone.
Result : The Channel parameters dialog box appears:
Channel 0 parameters
Broken wire test
Temperature range: from -2700 to 13720 1/10°C
Scale
Normalized
Display
Unit
°C
°F
-2700
13720
1/10°C
1/10°C
Under/overshoots
Under: -2700 Checked
Over: 13720 Checked
4
5
6
Select or deselect the Broken wire test .
Check the Standardized box for a standardized display, or modify at least one of the limits: the display zone of the channel parameters shows %..
whichever unit of temperature has been selected.
188
TLX DS 57 PL7 xxE
Configuration
Modifying the filter value of analog module channels
At a Glance This parameter defines the type of filtering of the selected input channel for analog modules.
The available filter values are: l l l 0 : no filtering, l 1 and 2 : low filtering,
3 and 4 : medium filtering,
5 and 6 : high filtering.
Note: If the fast scanning cycle is selected, filtering is not recognized.
Procedure The table below shows the procedure for defining the filter value assigned to the inputs of analog modules.
Step
1
2
3
3
4
5
1
2
0
0
Action
Access the hardware configuration screen of the required module.
For the required input channel, click on the arrow of the drop-down menu in the
Filter column.
Result : The drop-down menu appears:
Filter
4
5
Select the filter value to be assigned to the selected channel.
The efficiency value (alpha coefficient) of the selected filter and the associated response time are then displayed in the status bar at the bottom of the screen.
TLX DS 57 PL7 xxE
189
Configuration
Modifying the Scanning cycle of the inputs of a racked analog module
At a Glance This parameter defines the scanning cycle of the inputs of racked analog modules. l l
The input scanning cycle can be: l normal : the channels are sampled according to the time specified in the module characteristics, l fast : only the registered and Used inputs are sampled. The cycle time depends on the number of channels used and on the scanning time of a channel.
Input registers are updated: for the for the
Normal
Fast
cycle, at the start of the assigned ( MAST or FAST ).
MAST task cycle,
cycle, at the start of the cycle of the task to which the module is
Note: The Normal / Fast cycle and channels Used parameters cannot be modified in online mode, if the application has been transferred to the PLC with the default values of these parameters (normal cycle and all channels used).
Procedure The table below shows the procedure for defining the scanning cycle assigned to the inputs of an analog module.
Step
1
2
Action
Access the hardware configuration screen of the required module.
For the groups of input channels, click on the checkbox Normal / Fast situated in the Cycle field of the module zone.
Result : the selected scanning cycle will then be assigned to the channels.
TSX AEY 800 [RACK 0 POSITION 9]
Configuration
Designation: 8E ANA. HIGH LEVEL
Cycle
Normal
Fast
Terminal block detection
Channel
0
3
4
1
2
5
6
Used Task
MAST
MAST
Symbol Range not used
+/-10V
+/-10V
+/-10V not used not used
+/-10V not used
Scale
%...
%...
%...
%...
%...
%...
%...
%...
0
0
0
0
0
0
0
0
Filter
190
TLX DS 57 PL7 xxE
Configuration
Modifying terminal block presence detection in TSX and TBX analog modules
At a Glance This function detects the presence of the SubD connector(s) or of the terminal block and signals a fault when the latter is absent.
Note: for modules equipped with two SubD connectors, the terminal block fault is signaled if at least one channel is used on the absent connector.
Designation: 8I ANA. HIGH LEVEL
Cycle
Normal
Fast Terminal block detection
Procedure The table below gives the procedure for selecting terminal block detection.
Step
1
2
Action
Access the hardware configuration screen of the required module.
Click on the Terminal block detection checkbox.
TLX DS 57 PL7 xxE
191
Configuration
Modifying Input channels used
At a Glance
Procedure
A channel is declared in a task when the measured values are ‘returned’ to the task assigned to the channel.
When a channel is unused the line is grayed out, the value 0 is returned to the application program and the faults on this channel (range overshoot, etc.) are inactive.
The table below shows the procedure for modifying the use of a channel:
Step
1
2
3
Action
Access the module hardware configuration screen.
Select the required channel.
Click on the Used checkbox of the channel to be parameterized to select or deselect the channel:
1
2
3
0
Ch.
Used
192
TLX DS 57 PL7 xxE
Configuration
Modifying overshoot monitoring and event processing selection
At a Glance Overshoot monitoring is defined by a monitored or unmonitored lower limit and by a monitored or unmonitored upper limit.
Event processing is defined by the event number that is activated on crossing one of the thresholds indicated.
Note: Event processing is only possible if the PL7 application includes an event
Procedure The table below gives the procedure for adjusting these parameters:
Step
1
2
Action
Access the hardware configuration screen of the required module.
Double click on the channel to be modified.
Result : The Channel parameters dialog box appears.
Channel 0 parameters
Scale
-100%->
100%->
Display
-10000
10000
Under/overshoots
Under: -11250
Checked.
Over: 11250
Checked
Event
Event
Threshold 0:
Threshold 1:
0
0
0
3
4
5
Check or uncheck the box Monitored undershoot to indicate an undershoot limit.
Check or uncheck the box Monitored overshoot to indicate an undershoot limit.
Check or uncheck the box Event to characterize an event trigger. The event processing selected in this screen is activated on crossing one of the thresholds indicated in Threshold 0 and Threshold 1 .
TLX DS 57 PL7 xxE
193
Configuration
Cold junction compensation
At a Glance This function is available on input modules TSX and TBX. It can be internal or external. By default, internal compensation is offered.
Note: If external compensation is selected, channel 0 of the module is forced, after confirmation, in range Pt100
For the
TSX AEY 414 module
The table below gives the procedure for modifying cold junction compensation.
Step
1
2
Action
Access the hardware configuration screen of the required module.
Click on the Internal or External checkbox in the Cold Junction box.
For the
TSX AEY 1614 module
The table below gives the procedure for modifying cold junction compensation.
Step
1
2
Action
Access the hardware configuration screen of the required module.
Click on the Internal Telefast or External Pt100 button.
These two command buttons are used to select the type of cold junction compensation: l Internal Telefast (default). Compensation is made at the level of the Telefast terminal block; in this case it is possible to ‘return’ the cold junction temperature value via channel 8, by checking the box Read Cold Junction after confirming l the warning message,
External, via a PT100 probe to be connected to channels 0 and 8. Channel 0 supplies current to the probe and channel 8 measures the temperature.
194
TLX DS 57 PL7 xxE
Configuration
High precision mode for TSX AEY 1614 module
At a Glance This mode offers greater precision on temperature measurements using a selfcalibration procedure.
Note: this self-calibration procedure adds a period of 70 ms to each cycle (See
Timing of measurements, p. 46).
Procedure The table below gives the procedure for selecting the high precision mode.
Step
1
2
Action
Access the hardware configuration screen of the required module.
Click on the High Precision checkbox.
TLX DS 57 PL7 xxE
195
Configuration
Modifying the fallback mode of analog outputs
At a Glance
Procedure
This parameter defines the fallback mode that is assumed by the outputs when the
PLC switches to STOP mode or when there is a communication fault.
Possible modes are: l Fallback : the outputs are set to a value between -10000 et 10000 (0 by default) l which can be parameterized,
Maintain the value : the outputs remain in the state in which they were before the switch into STOP mode.
The table below gives the procedure for defining the fallback mode assigned to the outputs of analog modules.
Step
1
Action
To modify the fallback value, leave the Fallback box checked and type the required value in the Value box.
Result : The selected fallback mode will then be assigned to the module outputs.
Fallback Value
706
1964
2 For maintenance, click in the Fallback check box.
Result : The maintenance of the value will then be assigned to the module outputs.
Fallback Value
196
TLX DS 57 PL7 xxE
Configuration
Modifying parameters common to TBX or TSX output modules
At a Glance TBX or TSX analog output modules have parameters which apply to the whole module.
These parameters define l l the type of supply for the module, the module supply monitoring, l the terminal block detection.
This information is all displayed in the module zone
Designation: 8O ANA. HL NON INS.
Supply
Internal
24V output supply monitoring
External Terminal block detection
Supply to outputs
This is carried out using 2 buttons: l l internal external
: the 24V supply internal to the module feeds the outputs channels,
: a 24V supply external to the module feeds the outputs channels
Note: Do not supply more than two TSX ASY 800 modules with the power supply from the same rack.
Supply fault
Terminal block detection
When the 24V output supply fault monitoring box is checked, the module monitors the presence of the internal or external 24V supply.
When the Terminal block detection box is checked, the module monitors the presence of the terminal block, and indicates a fault if this is missing.
TLX DS 57 PL7 xxE
197
Configuration
198
TLX DS 57 PL7 xxE
The Debugging function
6
At a Glance
Aim of this
Chapter?
What's in this
Chapter?
This chapter looks at the debugging function and commands in analog input/output modules.
This Chapter contains the following Maps:
Topic
Introducing the Debugging Function of an analog module
Description of an analog module debugging screen
Analog module diagnostics
Forcing/unforcing analog channels
Detailed analog channel diagnostics
Modifying the channel filtering value
Aligning an input channel
Modifying the fallback value of an output
Calibration function for an analog module
Page
199
TLX DS 57 PL7 xxE
Debugging
Introducing the Debugging Function of an analog module
Introduction
Procedure
This function is only accessible in online mode. Debugging is used for each input/ output module of the application: l to display the parameters of each of its channels (channel state, filtering value, etc.), l to access the diagnostics and adjusting function for the selected channel (forcing the channel, masking the channel, etc.).
The function also gives access to the module diagnostics in the case of a fault.
The table below shows the procedure for accessing the Debugging function:
Step
1
2
Action
Switch to on-line mode.
Double-click on the module in hardware configuration.
Result : The module Debugging screen then appears.
200
TLX DS 57 PL7 xxE
Debugging
Description of an analog module debugging screen
At a Glance
Illustration
2
1
3
4
5
The debugging screen displays the value and status for each channel in the selected module in real-time. It also enables the user to access the channel command
(forcing the input or output value, reactivation of outputs, etc.).
The debugging screen is composed as follows:
TSX AEY 420 [RACK 0 POSITION 6]
Debugging
Designation: 4E ANA. RAPIDES HN. Version: 1.0
Channel
2
3
0
1
Symbol F
Global unforcing
ERR
DIAG..
DIAG..
DIAG..
DIAG..
<
0
-4
-2
-3
Value
RUN ERR IO DIAG...
Adjusting Channel 2
>
0
0
0
0
A
Display
Range +/-10V
-100000 to 10000
Forcing
0
Event
Event
Threshold 0:
0
Threshold 1:
0
Alignment
Target value
0
Confirm
0
Force
Unforce
Confirm
Offset
0
Reset
TLX DS 57 PL7 xxE
201
Debugging
Description The table below presents the different elements of the debugging screen and their functions.
Address Element
1
2
3
4
5
Title bar
Drop-down menu
Function
Indicates the reference of the selected module and its physical location as well as the rack number for the rack-mounted modules or the FIPIO connection point for the remote input/ outputs.
Enables selection: l of the debug phase: l l
Configuration,
Debugging (diagnostics), only possible when in online mode, l l Calibration (for input modules).
of channels by type (input or output), when the specified module contains both inputs and outputs.
Module zone Displays the name of the selected module as well as a copy of the module status LEDs
(Run, Err, I/O).
Provides direct access: l to module diagnostics when the module has an error (indicated by the LED integrated in the diagnostics access button switching to red), l to the Global unforcing function for channels.
Note: Displaying this zone is optional. The selection is made using the View
→
Module zone command.
Channel zones
Command zone
Displays the value and status for each channel in the module in real-time. The symbol column displays the symbol associated with the channel when the user has defined this
(from the variables editor).
Provides direct access: l to channel-by-channel diagnostics when channels have an error (indicated by the LED integrated in the diagnostics access button switching to red), l to the output reactivation command.
Gives access to the commands of a channel.
202
TLX DS 57 PL7 xxE
Debugging
Analog module diagnostics
At a Glance
Procedure
The Module diagnostics function displays errors when they occur, classified l l l according to category: internal errors (module breakdown, running self-test), external errors (terminal block fault), other errors (configuration error, module missing or switched off, faulty channel(s)
(details in channel diagnostics)).
A module error is indicated by a number of LEDs changing to red, such as: l l l l in the rack-level configuration editor: l the module position LED, in the module-level configuration editor: the Err and I/O LEDs, depending on the type of error, the Diag LED.
The table below shows the procedure for accessing the Module diagnostics screen.
Step
1
2
Action
Open the module debugging screen.
Click on the Diag button in the module zone.
Result: The list of module errors appears.
Module diagnostics
Internal faults External faults Other faults
Terminal block
OK
Note: It is not possible to access the module diagnostics screen if a configuration error, major breakdown error or module missing error occurs.
The following message appears on the screen: " The module is missing or different from that configured for this position ."
TLX DS 57 PL7 xxE
203
Debugging
Forcing/unforcing analog channels
At a Glance
Procedure
This function is used to modify the state of all or some of the channels of a module.
The state of a forced output is fixed and cannot be modified by the application until after unforcing.
Note: However, in the case of a fault involving an output fallback, the state of the outputs takes the value defined on configuration of the Fallback mode parameter.
The various commands available are: l for one or several channels: l forcing to the indicated value, l l unforcing (when the selected channel(s) are forced, for all the channels of a module (when at least one channel is forced: l global channel unforcing.
The table below shows the procedure for forcing or unforcing all or some of the channels of a module:
2
3
Step
1
4
Action for a channel
Open the module debugging screen.
Double-click in the cell in the Value column of the required channel (1).
Enter the required value in the Forcing box.
Click on the Force button.
Result : an F appears in the column F
Adjusting Channel 2
Display
Range +/-10V
-100000 to 10000
Forcing
0
Force
Unforce
Event
Event
0
0
Confirm
204
TLX DS 57 PL7 xxE
Debugging
Step Action for a channel
(1) The Channel adjustment screen can also be accessed by right-clicking on the required channel then left-clicking on the Properties button.
It is possible to disable forcing of all the channels of a module with the command button Global unforcing in the Debugging screen.
TSX AEY 420 [RACK 0 POSITION 6]
Debugging
Designation : 4 FAST HN. ANALOG INPUT Version : 1.0
Global Unforcing RUN ERR IO DIAG...
Rules to be respected
It is only possible to force an output when the task associated with this output is in
RUN mode. If the task is in STOP mode, forcing is accepted but not applied; the output is in Fallback/Maintain mode.
If an output is in forced state, it switches to Fallback/Maintain mode when the associated task switches to STOP mode. When this task returns to RUN mode, the output takes the forced value again.
A forced channel cannot be reconfigured in online mode.
TLX DS 57 PL7 xxE
205
Debugging
Detailed analog channel diagnostics
At a Glance The Channel diagnostics function displays errors when they occur, classified according to category: l internal faults: l Module failure l external faults: l sensor link fault l l terminal block fault range overshoot or undershoot fault l l calibration fault cold junction compensation fault l other faults: l terminal block fault l l configuration fault communication error l l application error
24V power supply fault l value outside limits l channel not ready
A faulty channel is indicated by the Diag LED in the Err column in the configuration editor switching to red.
206
TLX DS 57 PL7 xxE
Procedure
Debugging
The table below shows the procedure for accessing the Channel diagnostics screen.
Step
1
2
Action
Open the module debugging screen.
For the faulty channel, click on the Diag button in the Err column.
2
3
0
1
Ch.
Symbole F ERR
DIAG..
DIAG..
DIAG..
DIAG..
<
0
-4
-2
-3
Value >
0
0
0
0
A
Result: The list of channel errors appears.
Channel diagnostics
Internal faults External faults Other faults
Terminal block
Forced channel
OK
Note: The channel diagnostics information can also be accessed by program
(refer to the Shared task functions manual: READ_STS instruction).
TLX DS 57 PL7 xxE
207
Debugging
Modifying the channel filtering value
At a Glance This function is used to modify the filtering value of one or several channels of an l l l l analog module.
The available commands are:
0 : no filtering,
1
3
5
and
and
and
2
4
6
: low filtering,
: medium filtering,
: high filtering.
208
TLX DS 57 PL7 xxE
Debugging
Procedure
Step
1
2
3
The table below gives the procedure for changing a filtering value.
Action for a channel
Access the debug screen.
Select the channel to be modified in the channel zone and double-click in the corresponding box in the
Filter box.
Click on the little arrow in the box in the Filtering field of the Channel adjustment dialog box, and define the new selected filtering value in the drop-down menu.
Result : The Channel adjustment dialog box appears.
TSX AEY 1600 [RACK 0 POSITION 9]
Debugging
Designation: 16E ANA. HIGH LEVEL Version: 0.4
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
0
Channel Symbol F
Global unforcing RUN
ERR
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
Value
-252
-193
-188
-177
-166
-177
-177
-177
-257
-198
-182
-177
-171
-171
-166
-182
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Filter
ERR
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
A
IO
Adjusting Channel 7
DIAG...
Display
Range +/-10V
-100000 to 10000
Forcing
0
Force
Unforce
Filtering
1
4
Alignment
6
0
Confirm
Confirm
Offset
0
Reset
4
5
Confirm the choice by closing the Channel adjustment dialog box.
The new filtering value then appears in the box corresponding to the selected channel in the Filter column of the channel zone.
TLX DS 57 PL7 xxE
209
Debugging
Aligning an input channel
At a Glance
Procedure
The procedure for aligning an input is used to add an offset value to the value measured by this input, in order to compensate for a sensor shift (e.g. to adjust to 0
°C the measurement of a Pt100 probe immersed in a bucket of ice for adjustment).
The table below shows the procedure for aligning an input channel:
Step Action for a channel
1 Access the debug screen.
2 Select the channel to be aligned in the channel zone and double-click on the corresponding box in column A .
3 Click on the box in the Target value field in the Alignment dialog box and enter the new alignment value.
4 Confirm this new alignment value by clicking on the OK button.
Result : The new offset value is applied and appears in column A .
Channel 3 adjustments
Display
Range +/- 10V
-10000 to 10000
Forcing
0 Force
Unforce
Filtering
0 Confirm
Align
Target value
1964
Confirm
Offset
0
Reset
5 Close the Channel adjustment dialog box.
Notes
Note: When the alignment offset is modified by program with the WRITE_PARAM instruction (see
Shared task functions manual), its value must be between +1500 and –1500.
Note: The calculated offset value does not take into account the "keyboard" commands given by the user. Running the program (RUN), which also controls the alignment, simultaneously, renders the offset invalid.
210
TLX DS 57 PL7 xxE
Debugging
Modifying the fallback value of an output
At a Glance
Procedure
When an output is configured in Fallback mode, the corresponding button is valid but the Fallback/Maintain information is grayed out, because the fallback mode cannot be modified in Debugging mode. However, it is possible to change the fallback value by entering a new value.
The table below summarizes the procedure for modifying the fallback value:
Step
1
2
3
Action for a channel
Access the debug screen.
Select the channel in the channel zone and double-click in the corresponding box in the Fallback column.
Click on the box in the Value field in the Fallback dialog box and enter the new fallback value.
The value must be: l For TSX ASY 800 and ASY 410 software version modules < 1.0, l between -10000 and 10000 in range 10 V, l l between 0 and 10000 in ranges 0..20 mA and 4..20 mA,
For TSX ASY 800 and ASY 410 software version modules > 1.0, l l between -10500 and 10500 in range 10 V, between 0 and 10500 in ranges 0..20 mA and 4..20 mA.
TLX DS 57 PL7 xxE
211
Debugging
Notes
Step
4
Action for a channel
Confirm this new value by clicking on the OK button.
Result : The new fallback value is applied and appears.
TSX AEY 410 [RACK 0 POSITION 4]
Debugging
Designation: 16I ANA. HIGH LEVEL Version: 0.4
Channel
0
1
2
3
Symbol
Global unforcing
F ERR
DIAG.
DIAG.
DIAG.
DIAG.
0
0
0
0
Value
RUN ERR
0
0
0
0
Fallback
IO DIAG ...
Display
Range +/-10V
-100000 to 10000
Forcing
0 Force
Unforce
Fallback
Fallback Maintain
Value:
0 Confirm
5 Close the Channel adjustment dialog box.
Note: The fallback value can also be modified by program, with the
WRITE_PARAM instruction (see Shared task functions manual).
Note: The fallback value cannot be modified on TBX modules.
212
TLX DS 57 PL7 xxE
Debugging
Calibration function for an analog module
Introduction This function is only accessible in online mode. It is used to recalibrate the channels of each analog input module of an application.
Calibration is used to correct the long-term module drift. It can also be used to optimize the precision of the measurement at ambient temperatures other than 25 degrees C.
Procedure Procedure for accessing the Calibration function:
Step Action
1 Double-click on the module in hardware configuration.
Result : The Debugging screen appears.
2 In the drop-down menu at the top left, select the Calibration function to make the Calibration screen appear.
TSX AEY 1600 [RACK 0 POSITION 9]
Calibration
Configuration
Debugging
Calibration
HIGH LEVEL
RUN ERR IO DIAG...
TLX DS 57 PL7 xxE
213
Debugging
Introduction to the calibration screen
This screen displays the state of each of its channels in real-time and enables their calibration to be accessed.
Screen view:
1
2 Calibration
Designation: 16I ANA. HIGH LEVEL
3
RUN ERR IO DIAG ...
4
12
13
14
15
8
9
10
11
1
2
3
4
5
6
7
0
Channel Symbol F ERR
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
DIAG..
Value
-258
-198
-188
694
-177
-177
-182
-182
-263
-204
-188
-182
-177
-177
-172
-188
Different functions of the calibration screen
3
4
Address Function
1 This panel gives the module catalogue reference and slot in the PLC (rack and position).
2 This command zone displays the function in progress (Calibration function) and is used to select the Configuration or Debugging function from a dropdown list box. By activating the Calibration checkbox, the calibration of the channels (TSX AEY 800 / 810 / 1600, TBX AES 400, TBX AMS 620) or of the selected channel (TSX AEY 414) can be accessed.
This zone at "module" level contains the module name and version.
This zone at "channel" level displays the ERR information for each channel: all the measurements are invalid; filtering and alignment are inhibited.
214
TLX DS 57 PL7 xxE
Use
List
Debugging
For TSX AEY 800 / 810 / 1600, TBX AES 400 and TBX AMS 620 modules, only channel 0 needs to be calibrated for all the module channels to be calibrated.
For the TSX AEY 1614 module, only channels 0 and 8 need to be calibrated for all the module channels to be calibrated.
For the TSX AEY 414 module, general channel calibration must be performed.
The different calibration procedures are described in each section referring to input l l l l l modules: l TSX AEY 800 and TSX AEY 1600 (See Calibration of the TSX AEY 800 and TSX
TSX AEY 810 (See
Calibrating the TSX AEY 810 module, p. 42)
TSX AEY 1614 (See
TSX AEY 414 (See
TBX AES 400 (See
TBX AMS 620 (See
Calibrating the TSX AEY 1614 module, p. 53)
Calibrating the TBX AES 400 module, p. 101)
Calibrating the TBX AMS 600 module, p. 115)
TLX DS 57 PL7 xxE
215
Debugging
216
TLX DS 57 PL7 xxE
Associated bits and words
7
At a Glance
Aim of this
Chapter?
What's in this
Chapter?
This chapter looks at the addressing of objects associated to analog inputs/outputs.
This Chapter contains the following Sections:
Section
7.1
7.2
7.3
Topic
Addressing of analog module objects
Implicit exchange objects
Explicit exchange objects
Page
217
TLX DS 57 PL7 xxE
Bits and words
7.1
Addressing of analog module objects
At a Glance
Aim of this section
What's in this
Section?
This section introduces the principle of addressing for analog module objects.
This Section contains the following Maps:
Topic
Addressing objects of analog rack module
Addressing objects of remote analog modules
Page
218
TLX DS 57 PL7 xxE
Bits and words
Addressing objects of analog rack module
At a Glance
Illustration
The addressing of the main bit and word objects of input/output modules is done on l l l a geographical basis. It depends on: the number (address) of the rack, the physical position of the module in the rack, the module channel number.
Addressing is defined in the following way:
% I, Q, M, K X, W, D, F
Symbol Object type Format
X
Rack
Y
Position i r
Channel no. Position
Syntax The table below describes the different addressing parameters.
Family
Symbol
Object type
Element Values Description
% -
I
Q
M
-
-
-
Image of the physical input of the module.
Image of the physical output of the module.
This information is exchanged automatically at each cycle of the task to which it is attached.
Internal variable.
This reading or writing information is exchanged at the request of the application.
Format (size)
K
X
-
-
Internal constant.
This configuration information is available as read only.
Boolean.
For Boolean objects this element can be omitted.
Single length.
Double length.
W
D
16 bits
32 bits
Rack address
Module position
F x y
32 bits
0 or 1
0 to 7
00 to 14
(1)
Floating. The floating format used is the IEEE Std 754-1985 standard
(equivalent to IEC 559).
TSX 5710/102/103/153, PMX 57102, PCX 571012.
Other processors.
Position number in the rack.
When the rack number (x) is different from 0, the position (y) is encoded with 2 digits: 00 to 14; on the other hand, if the rack number (x) is 0, you remove the insignificant zeros (elimination from the left) from "y" ("x" does not appear and "y" is 1 digit for values less than 9).
(1) : the maximum number of slots means that 2 racks must be used for the same address.
TLX DS 57 PL7 xxE
219
Bits and words
Family
Channel no.
i
Element Values
0 to 127 or MOD
Description
MOD: channel reserved for managing the module and parameters common to all the channels.
Rank r 0 to 127 or ERR
Position of the bit in the word.
ERR: indicates a module or channel fault.
(1) : the maximum number of slots means that 2 racks must be used for the same address.
Examples
Object
%IW102.5
%QW204.3
%I102.MOD.ERR
%I204.3.ERR
The table below shows some examples of addressing analog objects.
Description word picture of analog input 5 of the module placed in position 2 in rack address 1.
%QW204.3 designates the word picture of analog input 3 of the module placed in position 4 in rack 2.
Information on analogue input module fault in position 2 of rack 1.
Information on a fault on channel 3 of the analogue output module in position 4 of rack 2.
Illustration
220
TLX DS 57 PL7 xxE
Bits and words
Addressing objects of remote analog modules
At a Glance
Illustration
The addressing of the main bit and word objects of remote modules on the FIPIO l l l bus is on a geographical basis. It depends on: the connection point, the type of module (standard or extended), the channel number.
Addressing is defined in the following way:
% I, Q, M, K X, W, D, F
Symbol Object type Format
\ p.2.c
\ m
Address module/channel and no.
connection point
Module i r
Channel no.Position
Syntax The table below describes the different elements that make up addressing.
Family
Symbol
Object type
Format (size)
Module/channel address and connection point p
2 c
Module position m
Channel no.
i
W
D
F
Element Values Meaning
% -
I
Q
M
-
-
-
Image of the physical input of the module,
Image of the physical output of the module,
This information is exchanged automatically at each cycle of the task to which it is attached.
Internal variable,
This reading or writing information is exchanged at the request of the application.
K
X
-
-
Internal constant,
This configuration information is available as read only.
Boolean,
For Boolean objects the X can be omitted.
16 bits
32 bits
32 bits
Single length.
Double length.
Floating. The floating format used is the IEEE Std 754-1985 standard
(equivalent to IEC 559).
0 or 1
-
Position number of the processor in the rack.
Channel number of the built-in FIPIO link in the processor.
1 to 127 Connection point number.
0 or 1 0 : standard module, 1: extension module.
0 to 127 or MOD
MOD: channel reserved for managing the module and parameters common to all the channels.
TLX DS 57 PL7 xxE
221
Bits and words
Family
Rank
Element Values Meaning r 0 to 255 or ERR
ERR: indicates a module or channel fault.
Examples The table below shows some examples of addressing objects of remote analog modules.
Object
%IW\0.2.6\0.5
Meaning word image of analog input 5 of the standard remote input module at connection point 6 of the FIPIO bus.
%QW\0.2.8\1.7
0 word image of analog output 7 of the extended remote output module at connection point 8 of the FIPIO bus.
TSX 57352 FIPIO manager
1 TBX LEP 030 0 TBX AES 400
2
3
TBX LEP 030 0 TBX ASM 620
170 FNT 110 01 0 170 ADI 350 00
4 TBX LEP 030 0 TBX AES 400 1 TBX ASS 200
222
TLX DS 57 PL7 xxE
Bits and words
7.2
Implicit exchange objects
Implicit exchange objects associated with the analog function
At a Glance
Channel values
These are objects used for programming and performing diagnostics of analog modules These objects are exchanged automatically on each task cycle in which the module channels are configured.
Values of analog channels, applicable to all modules.
Address
Function
Value of input channel in analog input module.
Value of output channel in analog output module.
Example: Word %IW105.3 always contains the present value on input 3 of the module in position 5 in address 1 rack.
Error bit objects Error bit objects, applicable to all modules.
Address (1)
R
Meaning
When it is on 1, this indicates that the i input channel of the module at the @module address is faulty.
When it is on 1, this indicates that the module at the @module address is faulty.
Key: @module = module address: l l xy for racked modules,
\p2c\m for remote modules.
Measurement status word
Address
%IWxy.i.1
Modules involved
TSX AEY420 / 810 / 1614
Meaning of bits for %IWxy.i.1measurement status word
Address
%IWxy.i.1:X0
%IWxy.i.1:X1
%IWxy.i.1:X2
Meaning
Aligned channel
Forced channel
Recalibration mode
TLX DS 57 PL7 xxE
223
Bits and words
Address
%IWxy.i.1:X3
%IWxy.i.1:X4
%IWxy.i.1:X5
%IWxy.i.1:X6
%IWxy.i.1:X7
%IWxy.i.1:X8 to 15
Meaning
Recalibration command in progress
Recalibrated channel
Measurement in the lower tolerance zone
Measurement in the upper tolerance zone
Loss of event (only in TSX AEY 420)
Reserved
Event source status word
Address
%IWxy.i.2
Module involved
TSX AEY 420
Meaning of bits for %IWxy.i.2 event source status word (1 = no event, 1 = event)
Address
%IWxy.i.2:X0
%IWxy.i.2:X1
%IWxy.i.2:X2
%IWxy.i.2:X3
%IWxy.i.2:X4 to 15
Meaning
Rising threshold 0 crossing
Descending threshold 0 crossing
Rising threshold 1 crossing
Descending threshold 1 crossing
Reserved
Enable event command word
Address
%QWxy.i.1
Module involved
TSX AEY 420
Meaning of bits for %QWxy.i.1 enable event command word (0 = masking, 1 = enable)
Address
%QWxy.i.1:X0
%QWxy.i.1:X1
%QWxy.i.1:X2
%QWxy.i.1:X3
%QWxy.i.1:X4 to 15
Meaning
Rising threshold 0 crossing
Descending threshold 0 crossing
Rising threshold 1 crossing
Descending threshold 1 crossing
Reserved
224
TLX DS 57 PL7 xxE
Bits and words
7.3
Explicit exchange objects
At a Glance
What's in this section
What's in this
Section?
This section introduces explicit exchange objects for analog modules.
This Section contains the following Maps:
Topic
Explicit exchange objects: General
Explicit exchange objects associated with outputs
Details on analog function explicit exchange words
Page
TLX DS 57 PL7 xxE
225
Bits and words
Explicit exchange objects: General
At a Glance Explicit exchange objects give information (e.g.: terminal block fault, module missing, etc.) and additional commands for performing advanced programming of the task functions.
Note: Configuration constants %[email protected] (@module = module address), not explained in this manual can only be accessed in read mode and correspond to the configuration parameters entered using the Configuration editor.
Explicit exchange objects are exchanged on request from the program user using the following instructions: l l l l l l
READ_STS (read status words),
WRITE_CMD (write command words),
WRITE_PARAM
READ_PARAM
SAVE_PARAM
(write adjustment parameters),
(read adjustment parameters),
(save adjustment parameters),
RESTORE_PARAM (restore adjustment parameters).
Note: All these instructions are detailed in the manual: Shared Task Functions
226
TLX DS 57 PL7 xxE
Bits and words
Explicit exchange objects associated with outputs
Racked output modules
Table of words available according to the different racked modules:
Address Meaning TSX AEY
800
Yes %MWxy.MOD.2
Module status word
%MWxy.i
%MWxy.i.1
%MWxy.i.2
Exchange in progress
Exchange report
Channel status word
%MWxy.i.3
%MWxy.i.4
Yes
Yes
Yes
Command
(recalibration/ forcing)
No
Command (forcing value)
No
%MWxy.i.5
%MWxy.i.6
%MWxy.i.7
%MWxy.i.8
%MWxy.i.9
Command (range to be recalibrated)
Command (current source to be recalibrated)
No
No
Command word containing the channel filtering co-efficient
Command word containing the channel alignment offset
Yes
Yes
Command word containing the value of threshold
0 assigned to the channel
No
TSX AEY
810
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
TSX AEY
1600
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
No
TSX AEY
420
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
TSX AEY
414
Yes
TSX AEY
1614
Yes
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
TLX DS 57 PL7 xxE
227
Bits and words
Address
%MWxy.i.10
Meaning
Command word containing the value of threshold
1 assigned to the channel
TSX AEY
800
No
TSX AEY
810
No
TSX AEY
1600
No
TSX AEY
420
Yes
TSX AEY
414
No
TSX AEY
1614
No
Remote modules Table of words available according to the different remote modules:
Address Meaning
%MW\p.2.c\m.MOD.2
Module state
%MW\p.2.c\m.i
Exchange in progress
%MW\p.2.c\m.i.1
%MW\p.2.c\m.i.2
%MW\p.2.c\m.i.3
Exchange report
Channel state
Command
(recalibration/ forcing)
TBX
ASS
200
Yes
No
Yes
Yes
Yes
TBX
AES
400
Yes
No
Yes
Yes
Yes
TBX
AMS
620
Yes
Yes (*) Yes
Yes
Yes
Yes
170 AAI
14000
170 AAI
52040
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
No
170
AAO
12000
Yes
Yes
Yes
Yes
No
170
AAO
92100
Yes
Yes
Yes
Yes
No
%MW\p.2.c\m.i.4
%MW\p.2.c\m.i.5
%MW\p.2.c\m.i.6
Command (forcing value)
Yes
Command (range to be recalibrated)
No
Command (current source to be recalibrated)
No
Yes
No
No
Yes
Yes (*)
Yes (*)
No
No
No
No
No
No
No
No
No
No
No
No
%MW\p.2.c\m.i.7
%MW\p.2.c\m.i.8
Adjust (filtering coefficient)
Adjust (alignment offset)
No
No
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
(*) These words only exist for channel 0 and channel 4 of the modules TBX AMS 620. Information contained in these words concerns the 2 or 4 successive module channels.
The command words above can be modified by program:
Example:
Filtering co-efficient for channel 3 of module TSX AEY 1600 modified by giving it the value 2.
The module is in position 3 of rack 0.
The sequence is as follows:
228
TLX DS 57 PL7 xxE
Racked output modules
Bits and words
! %MW9.3.7:=2; ! WRITE_CMD %CH9.3;
For more information on programming explicit objects, refer to the manual: Common
Tasks.
Table of words available according to the different racked modules:
Address
%MWxy.MOD
%MWxy.MOD.1
%MWxy.MOD.2
%MWxy.MOD.3
%MWxy.i
%MWxy.i.1
%MWxy.i.2
%MWxy.i.3
%MWxy.i.4
%MWxy.i.5
Meaning
Reserved
Reserved
Module state
Reserved
TSX ASY
410
Yes
Yes
Exchange in progress
Exchange report
Channel state
Reserved
Yes
Yes
Command word containing the channel forcing value
Yes
Command word containing the channel fallback value
Yes
Yes
Yes
Yes
Yes
Yes
TSX ASY
810
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
TLX DS 57 PL7 xxE
229
Bits and words
Details on analog function explicit exchange words
Module status word the word %[email protected] contains the module status word. This is an explicit exchange word. The bits in this word have the following meaning:
Address (1)
Meaning
Module failure
Faulty channel(s)
Terminal block fault
Self-testing in progress
Reserved
Configuration fault
Module is missing or off
%[email protected]:X10
%[email protected]:X11
%[email protected]:X12
%[email protected]:X13
%[email protected]:X14
Reserved
Possible FIPIO extension module failure
Faulty channel(s) on any FIPIO extension module
Terminal block fault on any FIPIO extension module
Self-testing in progress on any FIPIO extension module
Reserved
Configuration fault on any FIPIO extension module
Any FIPIO extension module missing or off
%[email protected]:X15
(1)
@module = module address.
l l xy for racked modules,
\p.2.c\m for remote modules.
Reserved
Status word for an input channel
Word %[email protected] contains the status word of a module channel. This is an explicit exchange word. The bits in this word have the following meaning:
Address (1) Meaning
%[email protected]:X0 Sensor link fault
%[email protected]:X1 Range under/overshoot fault
%[email protected]:X2 Terminal block fault
%[email protected]:X3 Reserved
%[email protected]:X4 Module failure
%[email protected]:X5 Configuration fault
230
TLX DS 57 PL7 xxE
Bits and words
Address (1) Meaning
%[email protected]:X6 Communication fault
%[email protected]:X7 Value outside range
%[email protected]:X8 Channel not ready
%[email protected]:X9 Action rejected
%[email protected]:X10 Calibration fault
%[email protected]:X11 l Recalibration in progress for modules TSX AEY 1600 /
800 / 414, TBX AES 400 and TBX AMS 620, l Reserved for other modules.
%[email protected]:X12 l Recalibration mode for modules TSX AEY 1600 / 800 /
414, TBX AES 400 and TBX AMS 620, l Reserved for other modules.
%[email protected]:X13 l Forced channel, for modules TSX AEY 1600 / 800 / 414,
TBX AES 400 and TBX AMS 620, l Reserved for other modules.
%[email protected]:X14 l Recalibrated channel, for modules TSX AEY 1600 / 800
/ 414, TBX AES 400 and TBX AMS 620, l Range limit undershoot for modules TSX AEY 810 / 420
/ 1614, l Reserved for other modules.
%[email protected]:X15 l Aligned channel for modules TSX AEY 1600 / 800 / 414, l Range limit overshoot for modules TSX AEY 810 / 420 /
1614, l Reserved for other modules.
(1)
@module = module address.
l l xy for racked modules,
\p.2.c\m for remote modules.
Status word for an output channel
Word %[email protected] contains the channel status word. This is an explicit exchange word. The bits in this word have the following meaning:
Address (1)
Meaning l l
24 V supply fault for module TSX ASY 800,
Reserved for other modules.
Range under/overshoot fault %[email protected]:X
1
2
Terminal block fault
TLX DS 57 PL7 xxE
231
Bits and words
Address (1)
3
Meaning l l
Range limit overshoot by higher value if bit
%[email protected]:X1 is on 1 for module TSX ASY 800 and module TSX ASY 410 (Software version >= 2.0),
Reserved for other modules.
Module failure %[email protected]:X
4
5
6
7
8
9
10
11
12
Configuration fault
Communication fault
Value outside range
Channel not ready
Action rejected
Reserved
Reserved
Reserved
13
14
Forced channel
Reserved
15
(1)
@module = module address.
l l xy for racked modules,
\p.2.c\m for remote modules.
Reserved
232
TLX DS 57 PL7 xxE
The regulation functions
II
Introduction
Aim of this part
What's in this part?
This part introduces the regulation functions on the Premium PLCs and describes its implementation with the PL7 Junior and Pro software.
This Part contains the following Chapters:
Chapter
8
9
10
11
12
13
Chaptername
General on the PID
Description of the regulation functions
Operator dialogue on CCX 17
Characteristics of the functions
Example of application
Appendices
Page
233
TLX DS 57 PL7 xxE
Regulation functions
234
TLX DS 57 PL7 xxE
General on the PID
8
Introduction
Aim of this chapter
What's in this
Chapter?
This chapter introduces the standard regulation functions of the PL7 software.
This Chapter contains the following Maps:
Topic
General introduction
Principal of the regulation loop
Development methodology of a regulation application
Page
235
TLX DS 57 PL7 xxE
General on the PID
General introduction
General The regulation functions are the standard elements of the PL7 language.
They support programming of the regulation loops of the Micro and Premium PLC’s.
These functions are particularly adapted to: l answering the needs of the sequential process which need the auxiliary adjustment functions (examples: Plastic film packaging machine, finishing treatment machine, presses…), l respond to the needs of the simple adjustment process’ (examples: metal furnaces, ceramic furnaces, small refrigerating groups…), l respond to the automatic control features or to the mechanical regulation which has a critical sampling time (examples: torque regulation, speed regulation).
A pre-configured interface with the CCX_17 range supports the driving and the adjustment of the regulation loops. In this area, up to 9 regulation loops are accessible via the CCX_17.
Available functions
Note: There is not a limit to the number of PID functions that are available in a function. In practice, it is the maximum number of input and output modules which are accepted by the PLC that limits the number of loops.
The standard regulation functions are split into two categories: l a family of algorithm functions: l l
PID function to execute a mixed PID correction (serial – parallel),
PWM function to execute the modulation adjustment period on the discrete l l outputs,
SERVO function to execute the motor command adaptations, an operator dialogue function (PID_MMI) which integrates a driving and adjustment application for the PID application on CCX_17 version 2.
The PID_MMI function is linked to 3 types of pre-configured screens.
236
TLX DS 57 PL7 xxE
General on the PID
Principal of the regulation loop
Introduction
Illustration l l
The working of a regulation loop has three distinct phases: l the acquisition of data and of: l l measurements from the process’ sensors (analog, encoders), setpoint(s) generally from PLC internal variables or from data from the
CCX_17.
execution of the PID regulation algorithm, the sending of orders adapted to the characteristics of the actuators to be driven via the discrete or analog outputs.
The PID algorithm generates the command signal from: l l l the measurement sampled by the input nodule, the setpoint value fixed by either the operator or the program, the values of the different corrector parameters.
The signal from the corrector is either directly handled by an analog output card of the PLC linked to the actuator, or handled via the PWM or SERVO adjustments in function with the kinds of actuator to be driven on a PLC discrete output card.
The following diagram schematizes the principal of a regulation loop.
Operator dialogue desk
CCX 17
Corrector
PLC
Adapter
Process to order
TLX DS 57 PL7 xxE
237
General on the PID
Development methodology of a regulation application
Diagram of the principal
The following diagram describes the linking of tasks to be carried out during the creation and debugging of a regulation application.
Note: The defined order is given for information only.
Application / Configuration
Configuration of interfaces
Discrete, Analog, Counts
Application / Data
Input data
constant, mnemonic,
numerical values
Programming: Ladder, List
MAST, FAST, SR
Regulation functions,
Operator dialogue
Animation tables
Variable table
PLC /Connector
Transfer of the application
in the PLC
Debugging
program
and adjustment
Debugging
by the CCX 17
238
File / Save
Storing of
the application
Documentation
Application
folder
Operating
the regulation
loops
Operating
the process via the
CCX 17
TLX DS 57 PL7 xxE
Description of the regulation functions
Introduction
Aim of this
Chapter
What's in this
Chapter?
This chapter describes the regulation functions.
This Chapter contains the following Maps:
Topic
Programming a regulation function
PID Function
Programming the PID function
PWM Function
Programming the PWM function
SERVO Function
Programming the SERVO function
Performance of the functions in the operating mode
9
Page
TLX DS 57 PL7 xxE
239
Description of the regulation functions
Programming a regulation function
Programming rules
The regulation function parameters must all be informed. The functions use 3 kinds l l l of parameters: read only parameters, considered at the beginning of the function’s execution, write only parameters, positioned at the conclusion of the function’s execution, the read and write only parameters, whose contents are considered at the beginning of the function’s execution, are then updated by the results of the function.
Note: The regulation functions must be programmed in a periodic task (MAST periodic or FAST). They must not be conditioned.
Parametering The word type input parameters are the analog sizes expressed in the scale [0,
+10000] and can be directly connected to measurement sensors via the words
%IWxy.i des analog inputs.
The bit type output parameters support ordering discrete actuators and can be directly connected to the %Qxy.i. type variables.
In the same way, the word type output parameters support ordering of analog actuators on the scale [0, +10000] and can be directly appointed to the %QWxy.i. type variables.
The MWi:L word table type parameters regroup the user parameters and the data necessary to the internal working of the function.
If the length of a table is sufficient, the function is not executed.
Note: In order to keep the adjustment parameters of the OF adjustment on cold start, it is necessary to delete the %MWi reset to zero option (in the processor’s configuration screen).
240
TLX DS 57 PL7 xxE
Description of the regulation functions
PID Function
General
Available functions
The PID function completes a PID correction via an analog measurement and setpoint on the [0-10000] format and provides an analog command to the same format.
The PID OF is composed of the following functions: l l l l l l l l l serial / parallel PID algorithm, forward / backward action (according to the KP gain sign), action derived from measurement or from distance, high and low limitation of the setpoint to [0-10000], high and low limitation of the output in automatic mode, anti-saturation of the integral action,
Manual/Automatic operating modes without definitely changing,
PID access control through the dialog operator, operating in integrator for (KP = TD =0).
l l
Note:
The display parameters used by the CCX 17 are shown in physical units,
For a correct PID operation, you must stay within the scale of [0-1000] for the measurement and the setpoint.
TLX DS 57 PL7 xxE
241
Description of the regulation functions
Operating principles
The following diagram presents the operating principle of the PID function.
TS
CORRECTOR P.I.D
.
TI
The Setpoint branch
INTERNAL
SETPOINT
SET POINT
S.P
INTERNAL
MEASUREM
PROCESS
VALUE
P.V
10000
Limiter
0
Deviation Integrated
+
SETPOINT
USED
-
MEASUREMENT
USED
ε
0
1
Derivative action
Action derived on the measurement
PV_DEV
TD
d
dt
Derived
+
The PID action
The Measurement branch
+
+
KP
OUT_MAX
Limiter
OUT_MIN
The PID operation modes
1
AUTO
0
OUTP
OUT_MAN
Followed without repeated command attempts on Auto – Manu >switching
DIALOGUE OPERATOR CCX 17
- PV_MMI - PV_SUP
- SP_MMI - PV_INF
Note: The description of the parameters used is presented in the (See Programming
the PID function, p. 243) module.
242
TLX DS 57 PL7 xxE
Description of the regulation functions
Programming the PID function
At a Glance PID functions are standard PL7 functions. They are therefore available from the function library.
This means that it is possible, by working with the language editors, to use assisted entry for a PID function in order to facilitate programming.
Note: A PID function can be entered in any periodic task (MAST or FAST). The function must not be subject to any conditions.
Illustration The illustration below shows the Functions screen in the library which can be used to implement the PID function.
EF
Function Information: Parameters
Family
Orphee function
Timer functions
GRAFCET
Single precision reals
Process control
Integer tables
Call format
V.Bib V.App
2.10
2.00
1.00
2.22
2.01 2.01
2.10
-
-
-
-
-
PID
Name
PID_MMI
PWM
SERVO
Mixed PID controller
Management of dedicated HMI on CCX17 for PIDs
Pulse Width Modulation of a numerical value
PID output stage for discrete valve control
FUNCTION parameters:
Name Type Nature
TAG STRING IN
UNIT STRING
PV WORD
IN
IN
OUT WORD OUT
Comment
Label of PID (8 char.), used by the HMI on CCX17
Unit of measurement (6 char.), used by the HMI>>
Process variable, format [0; +10000]
Output, format [0; +10000]
“TEMP”
Comment
“DEGRES”
%MW10
%MW11
Entry field
Display the call
PID ( “TEMP”,”DEGRES”,%MW10,%MW11,TRIG_PROD_A,%MW20:43 )
Syntax The call syntax for the PID function is:
PID(TAG,UNIT,PV,OUT,AUTO,PARA)
TLX DS 57 PL7 xxE
243
Description of the regulation functions
Parameters of the PID function
The table below shows the different parameters of the PID function.
Parameter Type Nature
IN = Input
OUT =
Output
TAG IN 8 characters (maximum) or
%MBi:L where L is less than or equal to 8
UNIT
PV
6 characters (maximum) or
%MBi:L where L is less than or equal to 6
%MWi or %IWxy.i.j
IN
IN
Default value
Description
-
-
-
Name used for the PID used by the CCX 17.
Unit of measure for the PID used by the CCX
17.
OUT
AUTO
PARA
%MWi or %QWxy.i.j
%Mi , %Ixy.i or %Qxy.i
%MWi:43
OUT
IN / OUT
IN / OUT -
0
0
Input representing the process variable for the function.
Analog output of the PID.
If TI = 0, an offset of 5000 is added to the OUT output in Auto mode.
Operating mode of the PID and the CCX 17.
0: manual, 1 = Auto.
(See table below for details of PARA table).
The table below shows the different parameters of the PARA table:
Parameter
SP
OUT_MAN
KP
TI
TD
TS
Position
%MWi
%MW(i+1)
%MW(i+2)
%MW(i+3)
%MW(i+4)
%MW(i+5)
Function
Internal setpoint in 0/10000 format
Value of the manual output of the PID (between
0 and 10000)
Proportional gain of the PID (x100), with sign and without units (-10000<KP<+10000). The sign of
Kp determines the direction in which the PID acts
(negative: direct, positive: reverse)
Integral time of the PID (between 0 and 20000) expressed in 10
-1
seconds
Derivative time of the PID (between 0 and 10000) expressed in 10
-1
seconds
Sampling period of the PID (between 1 and
32000) expressed in 10
-2
seconds The actual sampling period will be a multiple of the task period in which the PID closest to TS is located
244
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
Parameter
OUT_MAX
OUT_MIN
PV_DEV
NO_BUMP
DEVAL_MMI
PV_SUP (CCX 17)
PV_INF (CCX 17)
PV_MMI (CCX17)
SP_MMI (CCX 17)
Position
%MW(i+6)
%MW(i+7)
%MW(i+8):X0
%MW(i+8):X4
%MW(i+8):X8
%MW(i+9)
%MD(i+11)
%MD(i+13)
%MD(i+15)
Description of the regulation functions
Function
Upper limit of the PID output in auto mode.
(between 0 and 10000)
Lower limit of the PID output in auto mode.
(between 0 and 10000)
Derivative action chosen 0 = on process variable,
1 = on deviation
Bump or bumpless mode.
0 = bumps, 1 = no bumps
= 1 : inhibits acknowledgment of the PID by the
Human Machine Interface.
= 0 : the PID is used by the Human Machine
Interface.
This bit makes it possible to avoid having to carry out scale conversions on PIDs not being used by the CCX_17, and to select the PIDs being used, particularly when there are more than 9 PIDs in the PL7 application.
Upper limit of the process variable scale, in physical units (x100) (between -9 999 999 and +
9 999 999).
Lower limit of the process variable scale, in physical units (x100) (between -999 999 and + 9
999 999).
Image of the process variable in physical units
(x100)
Operator setpoint and image of the setpoint, in physical units (x100)
Note: l The other parameters used for internal management of the PID must never be modified by the application.
l The values used by the CCX 17 are multiplied by 100 so that they can be shown with 2 figures after the decimal point on the CCX 17 (the CCX 17 does not use floating point format but supports a fixed decimal point format).
245
Description of the regulation functions
Rules There is no alignment of the internal setpoint to the process variable in manual mode.
Scaling is only performed when one of the setpoints is modified (SP or DOP_SP).
The algorithm without integral action (TI = 0) performs the following operation:
For
ε t = SP – PV
The output is ...
Where ...
Dt= derivative action
The algorithm with integral action (TI <0) performs the following operation:
For
ε t = SP – PV
The output is ...
∆
OUT = KP [
∆ε ε ∆
Dt]/100 OUT
= OUT +
∆
OUT
Where ...
Dt= derivative action
Note:
Dt =
TD x Dt(t-1) - 10(PV - PV(t-1))
TD + TS
Examples
On cold start, the PID resumes in manual, with the output at 0. To impose automatic mode or a manual input not at zero after a cold start, you must program the initialization sequence after the PID call.
The examples provided below are in Ladder language.
Where the process control Human Machine Interface is used (DEVAL_MMI = 0)
(* PID correction on temperature process control loop *)
OPERATE
PID(‘TEMP’,’DEGRES’,%MW10,%MW1>> with PID(‘TEMP’,’DEGRES’,%MW10,%MW11,%M10,%MW20:43)
246
TLX DS 57 PL7 xxE
Description of the regulation functions
Where no Human Machine Interface is used DEVAL_MMI = 1.
(* PID correction on process control loop without built-in HMI
OPERATE
PID(‘ ’,’ ’,%MW10,%MW1>> with PID(‘ ’,’ ’,%IW3.1,%QW4.0,%M10,%MW20:43)
Note: In this example, the TAG and UNIT parameters are not applicable, so you can simply enter the values.
TLX DS 57 PL7 xxE
247
Description of the regulation functions
PWM Function
General
Operating principles
The PWM function supports regulation of a pulse width on a TOR output. It is a function that formats the PID’s output.
The pulse width depends on the PID’s output (The PWM function’s INP input) and the modulation period.
The circuit diagram of the function’s operation is as follows:
PV
PID OUTP INP
PWM PW_O
SP
T_MOD
Note: The description of the parameters used is presented in the (See Programming
the PWM function, p. 250) module.
248
TLX DS 57 PL7 xxE
Pulse widths
Description of the regulation functions
To each TOP of the T_MOD modulation period, the activation period in 10
-3
second of the PW_O output is calculated according to the following formula:
State 1 of the gap (shown in 10
-2
seconds) = INP * T_MOD / 1000
The following timing diagram illustrates this formula:
PW_O
Modulation period
50% 75% 35%
Time
Width of pulse
Practical rules T_MOD = TS (where TS is the sampling period of the upstream PID),
The period of the current task (expressed in 10
-3
second) is equal to:
(Required resolution)* 10 * T_MOD .
The PID is in the MAST task, the MAST’s period is 50*10
-3
s, TS = 500*10
-2
s and the required resolution is 1/50 (a T_MOD period must contain at least 50 periods of the current task).
T_MOD = TS = 500.
The period of the task where the PWM is introduced must therefore be less than 500
* 10 /50 =100 10
-3
s.
The PWM function can therefore be programmed in the MAST task. the resolution will be 1/100.
TLX DS 57 PL7 xxE
249
Description of the regulation functions
Programming the PWM function
Introduction The PWM function is a standard PL7 function. As such, it is available from the functions library.
From the language editors there, it is possible to use the help of a PWM function’s input to facilitate its programming.
Note: The PWM function’s input can be done in any periodic task (MAST or FAST).
The function does not have to be conditioned.
Illustration The illustration below gives you a general idea of the Functions screen in the library supporting the implementation of the PWM function.
EF
Information Functions: Parameters
Family
Orphee Function
Stalling functions
GRAFCET
Single precision reals
Process Control
Integer tables
Call format
Lib.V App.V.
2.10
2.00
1.00
2.22
2.01 2.01
2.10
-
-
-
-
-
PID
Name
PID_MMI
PWM
SERVO
Mixed PID regulator
Comment
Management of operator dialogue dedicated to CCX17 from
Pulse width modulation of a numerical size
PID output stage for open/close valve order
Parameters of the FUNCTION:
Name Type
INP
PARA
WORD
PW_O EBOOL
AR_W
Kind Comment
IN Numerical size to modulate
OUT Discrete output cyclic report equal to the LESS than value
IN/OUT PWM parameters (5 word table)
%MW11
%Q6.3
%MW90:5
Entry field
Call display
PWM ( %MW11,%Q6.3,%MW90:5 )
Syntax The PWM function’s call syntax is:
PWM(INP,PW_0,PARA)
250
TLX DS 57 PL7 xxE
Description of the regulation functions
The table below presents the different parameters of the PWM function. Parameters of the PWM function
Parameter Type Description
INP
PW_0
PARA
%MWi
%Qxy.i ou %Mi
%MWi:5
Kind
IN = Input
OUT = Output
IN
OUT
IN / OUT
Analog value to be modulated in the pulse width (format [0 – 10000])
Logic output (TOR) whose aspect ratio is the image of the INP input
Modulation period shown in 1/100ths of seconds (between 0 and 32767). T_MOD must be more than or equal to the current task’s period and it is adjusted by the system to be a whole multiple of this.
Table of 5 words whose first word corresponds to the T_MOD parameter.
The following are used internally by the function and must never be modified by the application
Examples The example offered below is done in Ladder language.
(* PID furnace regulation *)
OPERATE
PID(‘FOUR’,’DEGRES’,%IW4.0,%MW>>
(* Alignment of the T_MOD (PWM) on the TS of the PID *)
OPERATE
%MW90:=%MW105
(* Discrete output command in period modulation *)
OPERATE
PWM(%MW11,%Q6.3,%MW90:5) with PID(‘FOUR’,’DEGRES’,%IW4.0,%MW11,%M10,%MW100:43)
TLX DS 57 PL7 xxE
251
Description of the regulation functions
SERVO Function
General The SERVO function supports regulation with a motor type actuator steered by 2 alternating actions (UP and DOWN).
Note: It must be connected in tandem with the analog output of a PID. It cannot be used alone.
When there is a copy of a position, the valve’s position is locked via the INP
(setpoint) and POT (position measurement) inputs.
When the copy does not physically exist, the algorithm no longer uses the PID’s absolute output but the output’s variation. The UP output (or DOWN, according to the variation sign) is put at 1 for a length of time proportional to the actuator opening time and to the variation of the value. Also the notion of minimum pulse time is introduced.
Principle of operating with a position copy
The SERVO function locks the motor’s position according to a setpoint of the INP position from a PID’s output on the [0-10000] format, and to a POT position measurement.
The locking algorithm is a relay with hysteresis.
In this case, the PID, T_MOTOR and T_MINI parameters are not used.
SERVO
PV
UP
OUTP INP
PID
+
SP
-
DOWN
POT HYST
Note: The description of the parameters used is presented in the (See
Programming the SERVO function, p. 255) module.
252
TLX DS 57 PL7 xxE
Principle of operating without a position copy
(POT= -10000)
Example
Description of the regulation functions
In this case the SERVO function synchronizes itself with the upstream PID via the bias of the PID parameters table, passed in parameter to the SERVO function.
The algorithm receives in input the PID’s variation output and converts it into pulse period, according to the following formula:
T_IMP (shown in 10
-3
s) = OUT x T_MOTOR / 1000
The acquired period adds itself to the remaining period of the preceding cycles: in fact, what is not "consumed" in a cycle is memorized for the following cycles. This ensures a smooth operation especially with sudden variations of the (ex: PID setpoint level) command and in manual mode.
Note: The description of the parameters used is presented in the (See
Programming the SERVO function, p. 255) module.
The example offered below is done in Ladder language.
+20%
+2%
+2%
+24%
+22%
OUT
1 2 3 4 5
UP
DOWN
5 s 1 s
1 s
T_MOTOR = 25 s
T_MINI = 1 s
Caption:
1.
The PID variation output is of +20% (T_MOTOR pulse =25 s for a 100% variation), in this case the pulse affects the UP output for a period of 5 s,
2.
The PID variation is of +2%, which would correspond to a pulse of 0.5 s. This pulse is less than T_MINI (=1 s.), and it does not affect the outputs,
3.
A second variation of +2% appears and the function holds this variation concurrently with the preceding one (which corresponded to a variation less than the minimal value) for its calculation, which corresponds to a positive global variation of
+4%, and therefore to a pulse of 1 s on the UP output,
TLX DS 57 PL7 xxE
253
Description of the regulation functions
4.
A variation of –24% appears and the activated pulse is therefore of 6 s on the
DOWN output,
5.
Before the following second, another variation of +22% brings the system back to a global variation of 2% < to the variation of T_MINI (4%). The function finishes carrying out the minimal pulse of 1 s.
Note 1: The SERVO function does not manage the position limits, these must be managed by the application. If a limit is detected, you must force the output corresponding to 0 (UP for the high limit, DOWN for the low limit).
Example: (done in Ladder language)
(* Management of limits *)
Limit_up
Limit_down
OPERATE
SERVO(Outp,%IW3.1,%Q2.1,%Q2.1,%Q2.2,%M>>)
%Q2.1
R
%Q2.2
R
Note 2: Passing to the operating mode with copy to the mode without copy is possible (for example: when the copy has an error, go to mode without copy).
254
TLX DS 57 PL7 xxE
Description of the regulation functions
Programming the SERVO function
Introduction The SERVO function is a standard PL7 function. As such, it is available from the functions library.
From the language editors there, it is possible to use the help of a SERVO function’s input to facilitate its programming.
Note: The SERVO function’s input can be done in any periodic task (MAST or
FAST). The function does not have to be conditioned.
Illustration The illustration below gives you a general idea of the Functions screen in the library supporting the implementation of the SERVO function.
EF
Information Functions: Parameters
Family
Single precision reals
Process Control
Integer tables
Bit tables
Integer tables
Integer tables
Call format
Lib.V App.V.
2.22
2.01
2.00
2.00
2.10
2.00
-
-
-
-
-
-
PID
Name
PID_MMI
PWM
SERVO
Mixed PID regulator
Management of operator dialogue dedicated to CCX17 from PID
Modulated in the pulse width of a numerical size
PID output stage for open/close valve order
Parameters of the PROCEDURE:
Name Type
INP WORD
Kind Comment
Position setpoint, format [0;10000] (to conn>>
POT
UP
DOWN
WORD
EBOOL
EBOOL
IN
IN
OUT
OUT
Position copy, format [0;10000] [-10000>>
Alternating output, UP operating direction
Alternating output, DOWN operating direction
OUTP
-10000
%Q2.1
Comment
%MW100:43
Entry field
Call display
SERVO ( OUTP,-10000,%Q2.1,%MW100:43,%MW180:10 )
Syntax The SERVO function’s call syntax is:
SERVO(INP,POT,UP,DOWN,PID,PARA)
TLX DS 57 PL7 xxE
255
Description of the regulation functions
Parameters of the SERVO function
Parameter
INP
POT
UP
DOWN
PID
PARA
The table below presents the different parameters of the SERVO function.
Type
%MWi
%MWi or direct
%Qxy.i or %Mi bit type %Q or
%M
%MWi:43
Kind
IN = Input
OUT = Output
IN
Description
IN
OUT
OUT
IN / OUT
Position setpoint ([0 – 10000] format) that has to be connected to the PID output.
Position copy, ([0 - 10000] format)
0 : closed valve; 10000: open valve.
If the copy does not exist. POT must be initialized at –10000.
This particular value indicates "no copy".
Output signal for the motor’s UP operating direction.
Output signal for the motor’s DOWN operating direction.
%MWi:10 IN / OUT
The PARA parameter table of the upstream PID. Used if there are no copy words for the synchronization with the upstream
PID. See
Parameters of the PID function, p. 244
.
(See the table below for the breakdown of the PARA table).
The table below presents the different parameters of the PARA table:
Parameter
T_MOTOR
T_MINI
HYST
Position
%MWi
%MW(i+1)
%MW(i+2)
Function
Valve opening time shown in 10
-2
s.
Used if the copy does not exist (POT = -10000).
Minimal pulse time shown in 10
-2
s.
Used if the copy does not exist (POT = -10000).
Value of the hysteresis on the [0 – 10000] format.
Used if the copy does not exist (POT: [0 - 10000]).
Note: l The other parameters that are used by the function’s internal management must never be modified by the application.
l All the parameters are obligatory, regardless of the operating mode.
256
TLX DS 57 PL7 xxE
Examples
Description of the regulation functions
The examples offered below are done in Ladder language.
Case with a position copy.
OPERATE
PID(‘PID1’,’m/s’,PV,OUTP,MAN_AUTO>> with PID(‘PID1’,’m/s’,PV,OUTP,MAN_AUTO,%MW100:43)
OPERATE
PID(‘TEMP’,’DEGRES’,%MW10,%MW1>> with SERVO(OUTP,%IW3.1,%Q2.1,%Q2.2,%MW100:43,%MW180:10)
Case without a position copy.
OPERATE
PID(‘PID1’,’m/s’,PV,OUTP,MAN_AUTO>> with PID(‘PID1’,’m/s’,PV,OUTP,MAN_AUTO,%MW100:43)
OPERATE
PID(‘TEMP’,’DEGRES’,%MW10,%MW1>> with SERVO(OUTP,-10000,%Q2.1,%Q2.2,%MW100:43,%MW180:10)
TLX DS 57 PL7 xxE
257
Description of the regulation functions
Performance of the functions in the operating mode
Introduction
Cold start
Warm restart
This paragraph describes the performance of the functions in different starting l l l cases: cold start (new application, change of cartridge…), warm restart (power return without changing the application context), first execution after adding a function via modification in connected mode.
This type of start occurs for a new application or a change of cartridge.
On a cold start, the PLC can start automatically in RUN (according to the application’s configuration). The function correctors have a security performance: manual mode, outputs at 0. In addition, this supports the switching of the PLC into
RUN mode without carrying out the PID adjustment, then its debugging with the
CCX 17 (the adjustment can only be done in RUN).
This type of restart occurs for a power return, without changing the application context.
With a power return after an outage (regardless of how long it lasted) and if the application context is not lost or modified, the functions go back to their state before the outage. If the user wants to use another performance, it is his responsibility to test the %S1 system bit and to associate the required processing to it (forcing in manual mode…).
Note: The PLC’s time-and-date stamp allows you find out the duration of the last outage.
Adding a new call in connected mode
Following the addition of a new function regulation call in connected mode, an identical initialization to the case of the cold start is carried out.
Note: In order to be seen as a new function, this must use a new parameter table.
Therefore, the removal of a PID, followed by adding a PID that uses the same parameter table is not considered as an addition of a new PID. In this case the PID is executed in the same state and with the same parameters as the preceding PID.
258
TLX DS 57 PL7 xxE
Operator dialogue on CCX 17
10
Introduction
Aim of this
Chapter
What's in this
Chapter?
This chapter presents the operator dialogue on CCX 17.
This Chapter contains the following Maps:
Topic
Dialog operator on the CCX 17
Selecting a loop
Controlling a loop
Adjusting a loop
PID_MMI Function: programming
Performance of the PID_MMI function according to the PLC and CCX 17’s operating modes
Page
TLX DS 57 PL7 xxE
259
Operator dialogue on CCX 17
Dialog operator on the CCX 17
Introduction The CCX 17 permits viewing and control of all the modifiable parameters of a PID corrector without having to program a specific aplication.
The dialog operator function integrates a control and adjustment application on the
CCX 17 application’s PIDs. It provides management of 3 types of screens on the
CCX 17 supporting selection of a PID, viewing and controlling of this PID and adjusting the parameters of the PID. It inserts itself easily into any dialog operator application on the CCX 17.
Note: This function is only effective if the PLC is in RUN.
Limitations
What the keys do
Position of the keys
There is no limit to the number of PIDs in the application. On the other hand, a maximum of 9 PIDs are accessible via the dialog operator function on the CCX 17-
30 and on the CCX 17-30.
Navigating from one screen to another is done via the CCX’s command buttons and within screens via the up and down arrow buttons. The navigation offered is a
"vertical" navigation. You must always return to the loop selection screen to gain access to the values of other correctors.
The display is done over 4 lines (8 lines with the CCX 17-30) with the messages in
40 characters.
Fixed messages
Functions
The MOD key supports switching from display mode to input mode (in this case, the selected value starts flashing).
On the same screen, the input mode remains active for all the fields and pressing MOD again allows you to exit the input mode (stopping the flashing).
In input mode, the modification of a parameter is acknowledged by pressing the ENTER key.
MOD ENTER
260
TLX DS 57 PL7 xxE
Set up principle
Operator dialogue on CCX 17 l l
Setting up the dialog operator is easy: the PID_MMI function(s) are started at each cycle (non-conditioned call), a single call to the PID_MMI function manages all the application’s PIDs.
However, a call from the PID_MMI function via CCX_17, which is connected to the PLC is necessary, l detection of the application’s PIDs via the PID_MMI function is automatic, including when adding or removing in RUN. Therefore there is no declaration to do, l Identification of the required corrector is done via the "TAG" parameter from the
PID function and its selection depends on the value of the function’s
"DEVAL_MMI" parameter. (Only acknowledged via the PID_MMI function, the
PIDs whose DEVAL_MMI parameter is = 0).
TLX DS 57 PL7 xxE
261
Operator dialogue on CCX 17
Selecting a loop
Introduction
Selection screen
Display
Ex
Rf
The number of PIDs operated by the CCX 17s is a maximum of 9 loops, regardless of the number of connected CCX 17s.
Ex 1 : TEMPERA
4 : FURNACE
7 : TANK
2 : DEBIT1 3 : DEBIT2
5 : LEVEL
8 : HOPPER
6 : BOILER
9 : MIXER
Rf LOOP SELECT : 0
Functions
This screen displays all the labels implemented in the
PL7.
A figure is associated to each label (from 1 to 9 maximum).
To control a loop, the operator must input the corresponding number.
After inputting the loop number, the loop controlling screen is displayed.
Pressing the Exit (Ex) button allows you to leave the regulation screens.
Pressing the Refresh (Rf) button allows you to refresh the screen. This operation must be performed after deleting or adding loops via the PL7 in connected mode.
Note: If the application has no accessible PID via the CCX 17 (whether there is no
PID in the application, or the PID’s existing DEVAL_MMIs are all at 1), the "NO
PID" message is displayed. The Exit and Refresh buttons keep their functions.
262
TLX DS 57 PL7 xxE
Operator dialogue on CCX 17
Controlling a loop
Introduction
Selection screen
Display
This screen supports control over the setpoint, command and Manual/Auto mode values. The PV_INF and PV_SUP values are also displayed and controlable via this screen and they allow you to set the scale of the measurement in physical units.
Up
Dn
Up FURNACE AUTO
Dn
PV
SP
OUT
: 66,00 units
: 51,50
: 45,00
SUP : 100,00
INF : 100,00
Functions
The Manual/Auto screen is highlighted. Every time you press the associated command button you switch from one mode to the other.
In automatic mode, controlling an output is not authorized.
You can switch from one input field to another by using the up and down arrow keys. The operating mode is as follows: as soon as the screen is displayed, it is the SP value which is selected (highlighted), then using the down arrow button, OUT (if manual), LESS and MORE.
Pressing MOD supports switching into input mode (press
MOD again to exit it).
The Dn button gives access to the adjustment screen and to return to the loop selection screen use the UP button.
(the PV, SP, OUT, LESS and MORE values are displayed as integers with 2 significant figures after the comma).
PV, SP, LESS and MORE are in physical units. OUT is in percentage.
Note: When a field is flashing (input mode), the value is not refreshed in case of modification by the application or the PL7.
TLX DS 57 PL7 xxE
263
Operator dialogue on CCX 17
Adjusting a loop
Introduction This screen supports adjustment of the PID parameters (KP, TI, TD, TS) as well as the output limits OUT_MIN and OUT_MAX.
Selection screen
Display
Up Up
TI(s)
Ts(s)
OUT_MIN
FURNAC
E
KP
TD(s)
PV_DEV
OUT_MAX : 0,0
: 1,0
: -20,00
: 1,00
: 0,0
0
: 20,00
Functions
You can switch from one input field to another by using the up and down arrow keys.
As soon as the screen is displayed, the KP value is displayed (highlighted).
The KP parameter has no unit. TI, TD and TS are in seconds. OUT_MIN and OUT_MAX are in percentage.
Pressing the Up button returns you to the loop controlling screen.
Note: When a field is flashing (input mode), the value is not refreshed in case of modification by the application or the PL7.
264
TLX DS 57 PL7 xxE
Operator dialogue on CCX 17
PID_MMI Function: programming
Introduction The PID_MMI function supports establishment of the dialog with the PLCs to which the CCX 17 is connected. A PID_MMI function is necessary via CCX 17 for the steering, the display and the adjustment of the application’s PIDs.
The PID_MMI function is a standard PL7 function. As such, it is available from the functions library.
From the language editors there, it is possible to use the help of a PID_MMI function’s input to facilitate its programming.
Note: Inputting a PID_MMI function must be done in the task with the slowest period containing PIDs (MAST or FAST). The function does not have to be conditioned.
Example: An application with: l a FAST task at 10*10
-3
s containing PIDs, l a MAST task at 50*10
-3
s containing PIDs, the PID_MMI function must therefore be programmed in the MAST task.
Illustration The illustration below gives you a general idea of the Functions screen in the library supporting the implementation of the PID_MMI function.
EF DFB
Information Functions: Parameters
Family
Orphee Function
Stalling functions
GRAFCET
Single precision reals
Process Control
Integer tables
Call format
Lib.V App.V.
2.10
2.00
1.00
2.22
2.10
-
-
-
-
2.01 2.01
-
PID
PWM
Name
PID_MMI
SERVO
Parameters of the FUNCTION:
Name
ADDR
Type
AR_W
EN EBOOL
BUTT AR_X
PARA AR_Y
Kind
IN
Comment
Topological address of the destination CCX17 [ta>>
IN/OUT Activation of DOP on CCX17
IN/OUT
IN/OUT
5 bit table linked to the command buttons>>
PID_MMI parameters [62 word table]
Comment
Mixed PID regulator
Management of operator dialogue dedicated to CCX17 from PID
Modulated in the pulse width of a numerical size
PID output stage for open/close valve order
ADR#0.0.4
%M1
%M10:5
%MW45:62
Entry field
Call display
PID_MMI ( ADR#0.0.4,%M1,%MW10:5,%MW45:62 )
TLX DS 57 PL7 xxE
265
Operator dialogue on CCX 17
Syntax
Parameters of the PID_MMI function
The PID_MMI function’s call syntax is:
PID_MMI (ADDR, EN, BUTT, PARA)
The table below presents the different parameters of the PID_MMI function.
Parameter
ADDR
EN
Type Kind
IN = Input
OUT = Output
Description
%MWi:6 IN
%Mi IN / OUT
CCX 17’s address
Activation of the regulation operator dialog.
The application puts this bit to 1 and the PID_MMI function puts it back to 0 when you exit the regulation operator dialog (press Ex)
BUTT
PARA
%Mi:5
%MWi:62
IN / OUT
IN / OUT
Bits associated to the CCX 17 buttons.
These bits allow you to drive different screens as well as Manual/Auto.
Parameters of the PID_MMI.
The first 4 are the words of the communication report.
Note: The 4 words of the report are the same as in all the asynchronous communication functions (communication OF, integrated OF DOP and OF
PID_MMI). However the OF PID_MMI automatically manages these words and the application never has to modify them. They are provided for information.
For more information, refer to the Dialog operator (See Manual Premium PLC applications volume 1).
Example of the CCX 17:
If the CCX 17 is connected directly to the PLC’s (UNI-TELWAY) AUX socket, it is at the UNI-TELWAY 4-5 slave addresses.
The coding can be done: l via immediate value: PID_MMI(ADR#{0.254}0.0.4,....) or simply:
PID_MMI(ADR#0.0.4,....), l via a table of 6 words: %MW10:6 := ADR#0.0.4 PID_MMI(%MW10:6,...).
Synchronization of the dialog operator
The CCX 17 can be used to show screens other than the regulation screens. The IN bit is there to activate/deactivate the regulation dialog operator.
Setting IN to 1 activates the regulation operator dialog and is displayed on the PIDs’ selection screen.
266
TLX DS 57 PL7 xxE
Examples
Operator dialogue on CCX 17
The examples offered below are done in Ladder language.
%MI is associated to the IN bit (display switch on the operator). The alarm management application is always activated, just like the regulation operator dialog.
(*Management of display communication on the CCX 17*)
%M1
%L1
(*DOP application for the display of screens relative to PL7 *)
P
OPERATE
SEND_MSG(ADR#0.0.4,%KW20.6,%MW30:5)
(*DOP application for the display of adjustment screens *)
OPERATE
PID_MMI(ADR#0.0.4,%M1,%M10:5,%MW45:62)
(*Exchange flag bit calculation in progress *)
%MW45:X0 MSG_in_progress
%MW200:X0 error ala_900
R
(*Send alarm upon error appearance *) error MSG_in_progress %M1 OPERATE
SEND_ALARM(ADR#0.0.4,%KW140:29,%MW200:4) ala_900
S rz_ala_900
R
(* Cancellation of the alarm if it is sounded *) ala_900 rz_ala_900 OPERATE
PANEL_CMD(ADR#0.0.4,%KW170:3,%MW200:4) rz_ala_900
S
TLX DS 57 PL7 xxE
267
Operator dialogue on CCX 17
Management of the command buttons
When the PID_MMI is activated (IN at 1), it assigns the CCX 17 command buttons.
If the application uses these buttons for anything but regulation, they must be reassigned on the falling edge of IN (using the ASSIGN_KEYS function described in the DOP (See Manual Premium PLC applications volume 1)).
On the other hand, if the CCX 17 is only for regulation, it is advised that you carry out a non-conditioned SET of the IN bit in the application.
Selection of the
PIDs managed by the PID_MMI function
Each PID possesses a bit type DEVAL_MMI parameter. If this bit is at 1, the PID is not managed by PID_MMI. It is the only available level of protection. Moreover, if the application has more than 9 PIDs, it is the way to master those that are handled by the PID_MMI.
Alarm management
It is up to the user to program his/her own alarm management. This overlays itself on the management of the regulation screens.
If an alarm (coming from the dialog operator’s application) goes off while one of the
3 regulation screens is displayed, the CCX_17 is then dedicated to managing the alarm messages. When you return to the regulation operator dialog, the screen appears incomplete. Up/Dn or Refresh allows you to refresh this screen.
Several PID_MMI functions
It is possible to connect several CCX 17 terminals to the same PLC, so it can be useful to have several PID_MMI in the same application.
In this case, the different PID_MMI must be executed consecutively (no integrated
PID call) via the same PL7 task.
268
TLX DS 57 PL7 xxE
Operator dialogue on CCX 17
Performance of the PID_MMI function according to the PLC and CCX 17’s operating modes
Introduction
Warm start l l l
This paragraph describes the performance of the PID_MMI function according to the different operating modes of the PLC and the CCX 17: warm restart, crossing into Run or Stop, reconnecting to the CCX 17.
This type of restart occurs for a power return, without changing the application context.
If a problem such as a micro-outage on the PLC occurs while sending a message, the command is not repeated. It is therefore necessary to reinitialize the dialog by activating the IN bit via the application program.
STOP/RUN and
RUN/STOP crossing
In STOP, the PID_MMI function is no longer active. Nevertheless, you can still output parameters belonging to the displayed screen.
In STOP/RUN, the function goes back to the state it was in before crossing into
STOP.
Power outage or reconnecting to the CCX 17
With a power return or reconnection to the CCX 17, this reinitializes the communication with the PLC. Periodically, the PID_MMI reassigns the CCX 17’s command buttons. So after 20 seconds or more, pressing one of the first 3 buttons will display one of the regulation screens (preferably the Ref or Dn button on the left of the second row).
Note: Via the application, it is also possible to detect the presence of the CCX 17 by using the language words associated to the communication channels and to manage the dialog reset via the IN bit.
Cold start It is only on a cold start that the regulation screens are reset.
TLX DS 57 PL7 xxE
269
Operator dialogue on CCX 17
270
TLX DS 57 PL7 xxE
Characteristics of the functions
11
Introduction
Aim of this
Chapter
What's in this
Chapter?
This chapter presents the characteristics.
This Chapter contains the following Maps:
Topic
Memory occupency
Function running time
Page
TLX DS 57 PL7 xxE
271
Characteristics
Memory occupency
Table The memory occupation of the functions is as follows:
Function
PID
PWM
SERVO
PID_MMI
Generated code volume
2,2 K words
2,2 K words
1,2 K words
4,4 K words
272
TLX DS 57 PL7 xxE
Characteristics
Function running time
Table The running time of the functions is as follows:
Function Running time
Address
PID (TI=0 et TD=0) 1,2 ms (1 ms without
PID_MMI)
PWM
SERVO
PID_MMI (en=1)
0,6 ms
0,6 ms
1,3 ms
Symbol
1,7 ms (1,5 ms)
0,7 ms
0,8 ms
1,4 ms
Task
1,1 ms (0,9 ms)
0,5 ms
0,6 ms
1 ms
TLX DS 57 PL7 xxE
273
Characteristics
274
TLX DS 57 PL7 xxE
Example of application
12
Introduction
Aim of this
Chapter
What's in this
Chapter?
This chapter presents an example of application.
This Chapter contains the following Maps:
Topic
Description of the application example
Configuration of the example
Programming the example
Page
TLX DS 57 PL7 xxE
275
Example
Description of the application example
Context This is about maintaining the water temperature of an open air swimming pool at a required value. This value itself is determined according to the ambient air temperature.
Air Temp.
TT
Water Temp
Measure
Reheater
Regul
Output
Setpoint calcualation Setpoint
Pump
A discrete regulation is generally used in this type of installation. It is suggested that in this example, you substitute it for a proportional regulation with a modulated output, which should support reduction in the size of the temperature oscillations around the required value.
Temperature required
Output
Discrete regulation Proportional regulation
T_CYCL
Measuring the water temperature as well as the ambient temperature is done using a Pt 100 resistance thermometer.
276
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
Example
The setpoint of the water temperature depends on the exterior temperature according to the below law:
Temperature of the water
30°C
24°C
5°C
35°C
Temperature outside l l l l
A HIGH TEMPERATURE alarm will go off if the water temperature exceeds 32°C,
A LOW TEMPERATURE alarm will go off if it falls below 22°C,
A REGULATION ERROR alarm will go off if the SETPOINT/MEASUREMENT gap exceeds 2°C in either direction,
The regulation will become inoperative (output at 0) in case the pump stops.
277
Example
Configuration of the example
Hardware configuration
To execute this application you need: l l l l a TSX 57-103 PLC, a discrete TSX DEY 32D2K input module, a discrete TSX DSY 08R5A output module, a TSX AEY 414 analog input module.
The configuration is therefore as follows:
4
2
6
0
0
P
S
Y
0
T
S
X
5
7
1
0
3
1
3
2
D
2
K
D
E
Y
2
0
8
R
5
A
D
S
Y
3
A
E
Y
4
1
4
Allocation The discrete %Q2.0 output is allocated to the heater command.
The discrete %Q2.1 output is allocated to the pump command.
The discrete %Q2.2, %Q2.3 and %Q2.4 outputs are allocated to the alarms.
The %M0 bit is used to select the regulator’s AUTO/MANUAL operating mode.
The discrete %I1.1 and %I1.2 inputs support modification of the setpoint value in
AUTO mode and value of the output in MANUAL mode according to the following l l algorithm:
%I1.1 = 1 increase of 0.1% per cycle,
%I1.2 = 1 decrease of 0.1% per cycle.
The %I1.3 input provides the state of the pump.
%IW3.0 and %IW3.1 are the analog input values.
278
TLX DS 57 PL7 xxE
Example
Circuit diagram of the regulation loops
The PID’s regulator direction is in REVERSE (an increase of the measurement must correspond to a decrease of the output).
Water
Temp.
Air Temp.
Monitoring overheats driving
Monitoring overheats heater
Probe
Pt100
Probe
Pt100
Th J
Th K
TSX AEZ 414
Measure
%IW3.0
%IW3.1
%IW3.2
%IW33
+
-
Setpoint
PID
EXIT
PID1
AUTO
MANU
Setpoint
Calculation
To resistance of heating
%Q4.0
PWM
Configuration Rack configuration
1
2
Slot
0
3
Family
Processors
Discrete
Discrete
Analog
Reference
TSX 57103
TSX DEY 32D2K
TSX DSY 08R5A
TSX AEY 414
0
1 l
Channe Address
%Q2.0
%Q2.1
Parametering of the TSX DEY 32D2K module channels
7
..
31
5
6
3
4
1
2
Channel
0
Address
%I1.0
%I1.1
%I1.2
%I1.3
%I1.4
%I1.5
%I1.6
%I1.7
..
%I1.31
-
..
-
Symbol
-
Consig_increm
Consig_decrem
Etat_pompe
Act_pompe
-
Valid_dop_reg
Task
MAST
MAST
MAST
MAST
MAST
MAST
MAST
MAST
..
MAST
Parametering of the TSX DSY 08R5A module channels
Symbol Task Fallback value Resetting
Com_rechauf
Com_pompe
MAST
MAST
Fallback mode
Fallback
Fallback
Fallback to 0
Fallback to 0
Programmed
Programmed
TLX DS 57 PL7 xxE
279
Example
4
5
2
3
6
7 l
Channe Address
%Q2.2
%Q2.3
%Q2.4
%Q2.5
%Q2.6
%Q2.7
Symbol
-
-
Alarm_temp_haut
Alarm_temp_bas
Alarm_def_reg
-
Task
MAST
MAST
MAST
MAST
MAST
MAST
Fallback mode
Fallback
Fallback
Fallback
Fallback
Fallback
Fallback
Fallback value Resetting
Fallback to 0
Fallback to 0
Fallback to 0
Fallback to 0
Fallback to 0
Fallback to 0
Programmed
Programmed
Programmed
Programmed
Programmed
Programmed
Parametering of the TSX AEY 414 module channels
Range Scale Min Max Unit Chann el
0
Address Symbol
%IW3.0
Temp_eau Pt100 User 0 500 °C
Filtering Task
0 MAST
1
2
3
%IW3.1
%IW3.2
%IW3.3
Temp_air
Surchauf
_moteur
Surchauf
_rechauf
Pt100 User
Thermo J User
Thermo K User
-200 800
0
0
°C
1000 °C
1000 °C
0
0
0
MAST
MAST
MAST
Wiring test
Inactiv e
Inactiv e
Inactiv e
Inactiv e
Bit
Internal (%M): 256
System (%S): 128
Configuration of the bits, words and function blocks
Words
Internal (%MB,%MW,%MD,%MF): 512
System (%SW,%SD): 128
Common (%NW): 0
Constant (%KB,%KW,%KD,%KF): 128
Function blocks
Serial timer(s) 7 (%T): 0
Timer(s) (%TM): 64
Monostable(s) (%MN): 8
Counter(s) (%C): 32
Register(s) (%R): 4
Drum(s) (%DR): 8
280
TLX DS 57 PL7 xxE
Example
Programming the example
Proposed processing method
MAST-MAIN
The block PID1 is assigned to temperature process control. The temperature setpoint is calculated on the basis of the ambient temperature.
On reconnection to the mains, the process control operating mode is selected and the pump is started.
The state of the controller is conditioned by the operating state of the pump. If the pump is faulty the PID switches to MANU and the output is forced to 0.
The status word bits (process value high threshold, process value low threshold, deviation high threshold and deviation low threshold) are used to generate alarms.
The PID loop coefficients will be initialized to: l l l
KP = 600
TI = 300
TD = 50
The display on the CCX is as follows: l l
KP = 6
TI = 30 l TD = 5
These values can of course be fine-tuned during a subsequent adjustment phase.
(*Initialization of constants on cold restart-> PID loop buffer and initialization of PWM period to 10 s*)
%LO
%SW10:XO OPERATE
%MW10:10:=%KW10:10
OPERATE
%MW55:=1000
TLX DS 57 PL7 xxE
281
Example
282
(*Pump activation *)
%L1O
%I1.4
%Q2.1
(* PID loop controller operating mode management. This program allows the CCX17 to modify the A/M bit *)
%L11
%I1.3
P
%I1.3
N
OPERATE
%MW11:=0
(* Initialization of water temperature setpoint to 27 °C *)
OPERATE
%MW10:=5400
(* Execution of the temperature process control loop *)
%L12
%M10
S
%M10
R
OPERATE
(1)
OPERATE
PWM(%MW53,%Q2.0,%MW55:5)
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
(* Management of process value alarms *)
%L15
COMPARE
%IW3.0>6400
COMPARE
%IW3.0<4400
(* Management of deviation alarms *)
%L16
OPERATE
(%MW60:=%IW3.0-%MW10)
COMPARE
%MW60>400
COMPARE
%MW60<-400
(* PID loop controller on CCX17 *)
%L20
%Q2.2
%Q2.3
%Q2.4
OPERATE
PID_MMI(ADR#0.0.4,%I1.6,%MO:5,%MW100/62)
%I1.6
S
Example
283
Example
284
TLX DS 57 PL7 xxE
Appendices
13
At a Glance
Overview
What's in this
Chapter?
This Chapter reviews several aspects of the process control application.
This Chapter contains the following Maps:
Topic
PID parameter adjustment method
Role and influence of PID parameters
Page
TLX DS 57 PL7 xxE
285
Appendices
PID parameter adjustment method
Introduction
Closed loop adjustment
Numerous methods to adjust the PID parameters exist, we suggest Ziegler and
Nichols which have two variants: l l closed loop adjustment, open loop adjustment.
Before implementing one of these methods, you must set the PID action direction: l if an increase in the OUT output causes an increase in the PV measurement, make the PID inverted (KP > 0), l on the other hand, if this causes a PV reduction, make the PID direct (KP < 0).
This principal consists of using a proportional command (Ti = 0, Td = 0 ) to start the process by increasing production until it starts to oscillate again after having applied a level to the PID corrector setpoint. All that is required is to raise the critical production level (Kpc) which has caused the non damped oscillation and the oscillation period (Tc) to reduce the values giving an optimal regulation of the regulator.
Measure
286
Tc time
According to the kind of (PID or PI) regulator, the adjustment of the coefficients is executed with the following values:
-
PID
PI
Kp Ti Td
Kpc/1,7 Tc/2 Tc/8
Kpc/2,22 0,83 x Tc where Kp = proportional production, Ti = integration time and TD = diversion time.
Note: This adjustment method provides a very dynamic command which can express itself through unwanted overshootsduring the change of setpoint pulses.
In this case, lower the production value until you get the required behaviour.
TLX DS 57 PL7 xxE
Open loop adjustment
Appendices
As the regulator is in manual mode, you apply a level to the output and make the procedure response start the same as an integrator with pure delay time. .
Output
S
Measure
Integrator Process response t
TLX DS 57 PL7 xxE
M = S
Tu Tg t
The intersection point on the right hand side which is representative of the integrator with the time axes, determines the time Tu. Next, Tg time is defined as the time necessary for the controlled variable (measurement) to have the same variation size
(% of the scale) as the regulator output.
According to the kind of (PID or PI) regulator, the adjustment of the coefficients is executed with the following values:
-
PID
PI
Kp
-1,2 Tg/Tu
-0,9 Tg/Tu
Ti
2 x Tu
3,3 x Tu
Td
0,5 x Tu
where Kp = proportional production, Ti = integration time and TD = diversion time.
Note: Attention to the units. If the adjustment is carried out in PL7, multiply the value obtained for KP by 100.
This adjustment method also provides a very dynamic command, which can express itself through unwanted overshoots during the change of setpoints’ pulses. In this case, lower the production value until you get the required behavior. The method is interesting because it does not require any assumptions about the nature and the order of the procedure. You can apply it just as well to the stable procedures as to real integrating procedures. It is really interesting in the case of slow procedures
(glass industry,…) because the user only requires the beginning of the response to regulate the coefficients Kp, Ti and Td.
287
Appendices
Role and influence of PID parameters
Influence of proportional action
Proportional action is used to influence the process response speed. The higher the gain, the faster the response, and the lower the static error (in direct proportion), though the more stability deteriorates. A suitable compromise between speed and stability must be found. The influence of integral action on process response to a scale division is as follows:
Kp too high
Kp correct
°C
Static error
Kp too low t
288
TLX DS 57 PL7 xxE
Influence of integral action
Appendices
Integral action is used to cancel out static error (deviation between the process value and the setpoint). The higher the level of integral action (low Ti), the faster the response and the more stability deteriorates. It is also necessary to find a suitable compromise between speed and stability. The influence of integral action on process response to a scale division is as follows:
Ti too high
Ti correct
C
Ti too low
Note: A low Ti means a high level of integral action.
where Kp = proportional gain, Ti = integration time and Td = derivative time.
t
TLX DS 57 PL7 xxE
289
Appendices
Influence of derivative action
Derivative action is anticipatory. In practice, it adds a term which takes account of the speed of variation in the deviation, which makes it possible to anticipate changes by accelerating process response times when the deviation increases and by slowing them down when the deviation decreases. The higher the level of derivative action (high Td), the faster the response. A suitable compromise between speed and stability must be found. The influence of derivative action on process response to a scale division is as follows:
Td too high
C
Td too low
Td correct t
290
TLX DS 57 PL7 xxE
Appendices
Limits of the PID control loop
If the process is assimilated to a pure delay first order with a transfer function:
( )
= K
(
(
1
( ) p
+
θ p
)
) where:
τ
=model delay,
θ = model time constant,
100%
Measure = M
0
+ ∆ M
∆ M
Measure = M
0
τ θ t
The process control performance depends on the ratio
τ
The suitable PID process control is attained in the following domain: 2- -20
τ
θ delay (high t) the PID process control is no longer suitable. In such cases more complex algorithms should be used.
τ
For >20, a process control using a threshold plus hysterisis is sufficient.
TLX DS 57 PL7 xxE
291
Appendices
292
TLX DS 57 PL7 xxE
Weighing Application
III
At a glance
Aim of this part
What's in this part?
This part introduces the application-specific Weighing function on the TSX/PCX57
PLC and describes its implementation with the PL7 Pro and Junior software.
This Part contains the following Chapters:
Chapter
14
15
16
17
18
19
20
21
22
Chaptername
General Introduction to the Weighing Dedicated Function
Configuration of the Weighing application
Weighing programming
Calibrating the measurement string
Debugging the weighing function
Protecting the adjustments
Operating a weighing application
Diagnostics of the weighing application
Examples of the weighing program
Page
293
TLX DS 57 PL7 xxE
Weighing Application
294
TLX DS 57 PL7 xxE
General Introduction to the
Weighing Dedicated Function
14
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter introduces the weighing dedicated function on TSX/PCX 57 PLCs.
This Chapter contains the following Maps:
Topic
Description of the weighing package
Operation of the weighing module
Implementing the Weighing Application
Weighing Application Terminology
Page
295
TLX DS 57 PL7 xxE
General Introduction
Description of the weighing package
General
Illustration
The whole weighing package consists of: l l l the weighing module, a weight indicator, sensors.
The application specific weighing function supports software implementation of a weighing application around this hardware device.
The below illustration shows the standard elements of the weighing package.
2
1
3
296
TLX DS 57 PL7 xxE
Description
General Introduction
The following table describes the elements of the weighing package.
Address Element
1 Weighing module
2
3
Weight indicator
Sensors
Description
The ISP Y101 weighing module is the central element in the weighing string. It has: l l l a measurement input able to receive up to 8 sensors, a link for the display panel,
2 "discrete" reflex outputs for adjusted dosage applications.
The TSX XBT H100 remote display panel displays the measured weight with no previous configuration.
Detection of the measurement occurs through the strain gauge sensors.
TLX DS 57 PL7 xxE
297
General Introduction
Operation of the weighing module
General
Circuit diagram
In the PLC’s environment, the module has its own set of data in the same way as the other modules.
This information is used for the exchanges (reports and commands) with the processor.
The following circuit diagram of the operation shows the processes executed by the module and supports access to all the elements to be configured.
3
Processor exchange
Sensors
Processing the measure
1
Monitoring the measure
2
Display
4
5
Outputs management
298
TLX DS 57 PL7 xxE
Description of operation
General Introduction
The following table describes the different operation phases of the module.
Phase Operation
1 Processing the measurement
Description
The signal from the weighing sensors is: l l converted, the measurement is filtered according to the choice made on the configuration screen, l put on the scale, the scale’s characteristics are determined from a calibration.
2 Monitoring the measurement
3 Exchanges of data with the processor
The measurement coming from the process undergoes the following checks: l l monitoring the underload, monitoring the stability defined by a stability format and a stability time, l monitoring the presence of anything in the zero zone.
The module receives and processes the commands from the processor (Set to zero, tare mode semi-automatic, …).
It also prepares the data in a suitable format for display on the TSX
XBT H100.
It sends various information up to the processor such as the gross weight, the net weight, the debit, the tare and the statuses.
4 Displaying the data
5 Output management
The TSX XBT H100 displays the manual weight and tare in the unit chosen in the configuration as well as 4 extra pieces of information: the net weight, the stability, the presence of anything in the zero zone and the unit of the weight.
The card can directly manage 2 discrete outputs and control them according to the thresholds transmitted to the module by the application program.
The elements used to manage this are: l l l the transfer thresholds, the weight development direction (Weighing or Down weighing), the logic of output transfer.
TLX DS 57 PL7 xxE
299
General Introduction
Implementing the Weighing Application
At a Glance Implementing the weighing application requires the physical context in which it will be executed (rack, supply, processor, modules or devices, etc.) to be defined and implementation of the software to be carried out.
This latter aspect is performed by the different PL7 editors: l l either in local mode, or in offline mode.
Implementation
Principle
Mode
Local
Local or connected
The table below presents the different dedicated weighing function implementation phases.
Phase Description
Declaring the module Choice: l l of geographical position: number and slot of module in the rack, of the module type.
Configuring the module channels (See Configuration of the Weighing application,
)
Entering configuration parameters.
Enabling a new module.
Enabling configuration parameters. (See Manual
Premium PLC applications volume 1)
Globally confirming the application (See Manual
Premium PLC applications volume 1)
Enabling a new application.
Symbolization (See
Programming (See
Weighing programming,
)
Symbolizing variables associated with the application-specific function.
Programming functions the application should perform using: bit and word objects associated with the module,
300
TLX DS 57 PL7 xxE
Mode
Connected
Local or connected
Connected
Connected
General Introduction
Phase
Transfers
Description
Transfers the application to the PLC.
Calibration (See Calibrating the measurement string ,
Calibrating the measuring circuit.
Debug (See Debugging the
)
Debugging the application using: l debug help screens, which allow the status of inputs and outputs to be visualized, l diagnostics screens, which allow faults to be identified.
Protecting adjustments made.
Protecting adjustments (See
Protecting the adjustments,
Documentation Printing different information that relates to the application.
Operation (See Operating a
weighing application, p. 385 )
Operating the application using: l debug help screens, which allow the principal information about the weight measurement to be visualized.
l TSX XBT H100 remote displays.
Protecting parameters associated with the measurement.
Diagnostics (See
Diagnostics of the weighing
)
Note: The order below is purely for indication purposes, as PL7 software allows editors to be used interactively in whichever order is desired. (Nevertheless, you can use the data or program editors without having configured the weighing module in advance).
TLX DS 57 PL7 xxE
301
General Introduction
Weighing Application Terminology
Limit Load (Lim) The maximum static load that can be supported by the instrument, without permanently altering its meteorological qualities.
Zero Load
Set to Zero
Device
Tare weight of load receiver when equipped with its mechanical accessories
(vibratory extractor, screw, trap, screw jack, etc.). It does not appear in the weight indication but must be taken into account when calculating the maximum load of the sensors.
Device allowing the indicator to be "recalibrated" in the event of a deviation from zero (due to dirt accumulation, for example). This operation can only be carried out in the extent of zero calibration range (+/-2% or +/-5% of the maximum range according to the weighing instrument).
Tare Predefining
Device
Device allowing a predefined tare value to be subtracted from a gross weight value and indicating the result of the calculation. The weighing range is consequently reduced.
Tare Device l l
Device allowing the instrument indication to be moved to zero when a load is positioned on the load receiver: without encroaching on the weighing range of net loads (tare additive device),
or reducing the weighing range of net loads (tare subtracting device, such as
TSX ISP Y101).
(Weighing
Instrument)
Indicator Device
Part of load measuring device from which direct reading of result is obtained (TSX
XBT H100).
Part of instrument that will receive the load.
Load Receiver
Device
Scale Division Value in mass units, expressing the difference between two consecutive indications for one numerical indication.
Calibration Graduates a piece of measuring apparatus.
Weighing Range Interval between maximum and minimum weight.
302
TLX DS 57 PL7 xxE
General Introduction
Weighing
Instruments
Non-Automatic
Functioning
Weighing
Instruments
Measuring instruments, which determine the mass of a body using the force of gravity.
These instruments can also be used to determine other sizes, quantities, parameters or characteristics linked to the mass. According to the way they function, weighing instruments are either classified as automatic or non-automatic functioning instruments.
Weighing instruments that require the intervention of the operator during the weighing process, in order to deposit loads on the load receiver device and retrieve loads from it, for example, as well as to obtain the result. These instruments allow the weighing result to be directly observed, either displayed or printed out. The two possibilities are covered by the word "indication".
The science of weights and measures.
Metrology
Lead Sealing
Gross Weight
Sealing a piece of apparatus with lead. The positioning of a rider in the weighing module ensures this function.
The objective of this device is to guarantee measurement conformity. The accessible parameters only have influence on the aspects of the automatic action's exploitation of module information. the unit, weight, scale division, etc, are read only).
Indication of the load weight on an instrument when no tare or predefining device has been used.
Net Weight (Net) Weight indication of a load placed on an instrument after a tare device has been used.
Net weight = Gross weight - Tare weight
Maximum Weight
(Max)
Maximum weighing capacity, not taking account of the additive capacity of the tare.
Minimum Weight
(Min)
Load value under which weighing results can be marred by a relative error that is too large.
Tare
Taring
Load placed on the load receiver along with the product to be weighed. For example: product packaging or container.
Action allowing the instrument indication to be moved to zero when a load is positioned on the load receiver.
TLX DS 57 PL7 xxE
303
General Introduction
Tare Value (T) Weight value of a load, determined by a tare weighing device.
Predefined Tare
Value (PT)
Numerical value, representing a weight, which is entered into the instrument at configuration or by program.
Zero Tracking Device allowing slow derivations from zero to be made up, within the limits of the extent of the zero range.
304
TLX DS 57 PL7 xxE
Configuration of the Weighing application
15
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter describes how to select and modify the parameters of the weighing module’s configuration.
This Chapter contains the following Maps:
Topic
Description of the Dedicated Weighing Function Configuration Screen
Weighing Module Configuration Parameters
How to modify the task parameter
How to modify metrological information
How to modify the zero
How to modify the data format
How to modify the stability
How to Modify Measurement Input Filtering
How to Modify the Flow Calculation
How to Modify the Tare
How to Modify the Threshold Check
Page
305
TLX DS 57 PL7 xxE
Configuration
Description of the Dedicated Weighing Function Configuration Screen
General
Illustration
The configuration information allows measuring characteristics to be defined and the module's operation to be adapted to the application it is intended for.
This screen gives access to the visualization and modification of configuration parameters.
1
2
TSX ISP Y101 [RACK 0 POSITION 4]
Configuration
Designation: 1I. WEIGHING 3 FILTERS
3
Symbol:
Channel: Function:
Weighing
Task:
MAST
Metrological Data
Unit:
Max Range (MR):
Scale Division (d):
Overload Threshold:
Threshold check
Active
Direction:
Weighing
S0 kg
150
0.01
+9d
LF Mask Time:
0
Outputs Active Phase 1: s
.00
S0 and S1 kg
Downweighing
Zero
Recalibration range:
Zero Tracking
:±2%MR
Stability
Format range:
Time:
3
1
/.e
s
Flow
Calculate on 4
Tare
Predefined
Value: 0.1
measurements kg
Cut-off points
Low Flow (LF)
High Flow (HF)
0.0000
0.0000
kg kg
Format of data
Legal
High resolution
Filtering
F1:
F2: 0
4
F3: 0
T
Description The table below introduces the different zones on the configuration screen.
Address Element
1
2
3
Title bar
Function
Indicates the reference of the module selected and its physical position as well as the rack number.
Module zone Allows the type of screen to be selected: l l l
Configuration
Calibration, only accessible in offline mode,
Debug
,
only accessible in offline mode.
Displays the designation of the selected module.
Displaying this zone is optional. Choose using the View
→
Module Zone command.
Channel zone Gives access to modification of the module's parameters.
306
TLX DS 57 PL7 xxE
Configuration
Weighing Module Configuration Parameters
Parameters List
Parameters
Task
Metrology/Unit
Metrology/Max Weight
Metrology/Scale division
150
0,01
Metrology/Overload threshold +9 d
Zero/Zero tracking
Zero/recalibration range
Data format
Stability/Extent of Range
Stability/Time
Filtering/Coefficients
F1
F2, F3
Flow/Calculation
Tare
Threshold check
LF mask time
Output logic
Phase 1 active outputs
Cut-off points LF and HF
The following table lists the parameters, which can be accessed during configuration.
Possibilities Unit
Legal
3
1
Default configuration
Mast kg
Inactive
+/-2% MW
4
0
4
Not predefined
Inactive
0
Weighing
S0
0
Mast or Fast kg g t lb oz
<none> from 0 to 65,535
1, 2 or 5 10 n
+9 d
+2% PM
+5% PM
Inactive or active
+/-2% MW,
+/-5% MW
Legal
High resolution
2, 3, 4, 6 or 8
0.4, 0.5, 0.7 or 1 from 0 to 19
kilogram gram ton (metric) pound (=453g) ounce (=28.35g) no unit in the weight unit chosen in the weight unit chosen
-
scale divisions
% of Max W
% of Max W
-
1/4 of the scale division seconds
-
2, 8, 4, 16 32 or 64 measurements
Not predefined or predefined in the weight unit chosen
Inactive or Active -
0 to 1.5 seconds per 0.1s step seconds
Weighing or Downweighing
S0 or (S0 and S1) from 0 to Max W
-
in 1/100 of the unit
TLX DS 57 PL7 xxE
307
Configuration
How to modify the task parameter
At a glance This parameter defines the task processor in which the input acquisition and the output update take place.
The possible choices are: l l
The
The
MAST
FAST
task
task
Note: Modifying this parameter is only possible in local mode.
Procedure The table below introduces the procedure for defining the task type assigned to the module.
Step
1
2
Action
Access the hardware configuration screen from the weighing module.
From the pull-down menu, click Task .
Result: a drop-down list appears.
MAST
MAST
FAST
Task
3
4
Select the required task.
If need be, confirm the reconfiguration.
308
TLX DS 57 PL7 xxE
Configuration
How to modify metrological information
At a glance The configuration screen offers the following metrological information.
Designation
Unit
Maximum Range
(MR)
Grade
Overload threshold
Description gives you the choice of unit of weight: l l l l l l g kg t : ton (metric) lb
: gram oz
: kilogram
: pound (lb = 453g)
: ounce (oz = 28.35g) none : no unit
This is the maximum load that it is possible to weigh with the instrument, without considering the weight of the empty load holder (on legal format
(See
How to modify the data format, p. 312 )).
The grade’s value is of the 1, 2 or 5 format that multiplies 10 n
(n being a positive, negative or non integer with |n| less than or equal to 3.
Example: for a grade of 0.002 (if the unit chosen is kg), the measurement is increased 2g at a time.
This threshold is the value of the surplus weight that the display panel no longer indicates (the overload is therefore indicated by a ‘>‘ line on the display panel).
It can take these values: l l l
+9 grades
+2% of the maximum range
+5% of the maximum range
Example: the maximal range has been established at 150 kg and the grade at 10 g. According to the user’s choice, the utilization limit will be for: l l l
9 grades: Max Range + 9 grades is 150.09 kg
+2%MR: 102% of Max Range is 153 kg
+5%MR: 105% of Max Range is 157.5 kg
Note: the underload threshold cannot be parameterized: it sets the tolerated identifier limit to below zero. It is -2% of the maximum range
(underloading is therefore indicated by a ‘<‘ line on the display panel).
TLX DS 57 PL7 xxE
309
Configuration
Procedure
Note: Because of the industrial environment, select a resolution higher than 3000 pulses as a serious installation precaution.
With the programming screen, it will not be possible to enter a higher resolution than 50000 pulses.
In other words the following imbalance must be considered:
Max Range (RM) ≤ 50000 x Grade.
The table below introduces the procedure for setting metrological information.
Step
1
2
3
Action
Access the weighing module’s hardware configuration screen.
Select the values of the Unit , Grade or Overload threshold parameters by using the drop-down lists and enter the Max Range value.
If need be, confirm the reconfiguration.
310
TLX DS 57 PL7 xxE
Configuration
How to modify the zero
At a glance The configuration screen offers the following information for adjusting the zero.
Designation
Format print recalibration range
Zero follower
Description
Each zero shift register can be corrected so that it will not go over this print range.
It is defined in % of the maximum range. It can take the values: l l
+/- 2% PM (+/- 2% of the maximum range)
+/- 5% PM (+/- 5% of the maximum range)
This optional function supports correction of any slow losses of accuracy of the zero in the print range of the format (+/- 2% of the maximum range).
It is not advised to select this option in automatic installations.
Procedure
Note: The difference between a slow drift and a real weighing is based on the following rule: all variations of weights lighter than a half-grade whose repetition frequency is sufficiently weak to conserve the stability of the measurement is considered as a drift. The correction created by the function is limited to +/-2% of the counter output’s maximum range. When this limit has been passed, there is no automatic correction.
The table below introduces the procedure for setting the zero.
Step
1
2
3
4
Action
Access the hardware configuration screen from the weighing module.
Select the format’s print range by using the drop-down lists.
If necessary, tick the Zero follower box to confirm this function.
If need be, confirm the reconfiguration.
TLX DS 57 PL7 xxE
311
Configuration
How to modify the data format
At a glance The configuration screen supports selection of the measurement’s display format.
l l
The value of the weight is given to or entered by the user: either in a fixed point physical unit: legal format or in a hundredth of a fixed point physical unit: high resolution
Note: A fixed point physical unit is called a whole number shown as a unit of weight where a comma can be put.The position of this is given by the grade to the power of ten.
Example
Procedure
Legal format: The value 3014 means 301.4 kg if the grade is worth 2.10-
1 kg.
High resolution format: The value 301403 means 301.403 kg if the grade is worth
2.10-
1 kg. This unit offers more accuracy but it is not accepted by the legal Metrology department.
The table below introduces the procedure for the data format.
Step
1
2
3
Action
Access the weighing module’s hardware configuration screen.
Check the format of the required data.
If need be, confirm the reconfiguration.
312
TLX DS 57 PL7 xxE
Configuration
How to modify the stability
At a glance The configuration screen offers the following parameters to set the stability.
Designation
Format print range
Time
Description
A weight cannot be measured immediately after receiving a load because the inevitable oscillations affect the mechanical part.
The stability format shows the size below which the measurement is considered stable.
It is parameterized on 2, 3, 4, 6 or 8 quarters of a grade.
The stability time shows how long the measurement must stay in the stability format before it is considered stable.
It is parameterized on 0.4, 0.5, 0.7 or 1 second.
Procedure The table below introduces the procedure for setting the stability.
Step
1
2
3
4
Action
Access the weighing module’s hardware configuration screen.
Select the format’s print range by using the drop-down list.
Select the stability time by using the drop-down list.
If need be, confirm the reconfiguration.
TLX DS 57 PL7 xxE
313
Configuration
How to Modify Measurement Input Filtering
At a Glance
Measurement
Phases
Filters concern the measurement input of the weighing sensors.
By default. PL7 offers a unique filter, which is defined for the total duration of the weighing action.
To increase the speed/precision performance of weighing, 3 distinct filters can be used for one weighing action, as follows: l l l filter F1 associated with phase 1 (default phase), filter F2 associated with phase 2, filter F3 associated with phase 3.
Each filter can either have: l a sliding average (filtering coefficients from 1 to 11), where the measurement is the average of the last n values, l or be of second order (filtering coefficients from 12 to 19), which are referenced by their cut-off frequencies.
l l l
The different phases of a continuous weighing action can be broken down into: a phase 1, where speed is the prime feature of control precision (High flow), a measurement refining phase 2 (Low flow), a final phase 3, where the measurement value differs very little and requires a high level of precision (Residual flow).
314
TLX DS 57 PL7 xxE
Filter
Coefficients
Procedure
Configuration
The following list gives the meanings of filter coefficients:
11
12
13
14
7
8
9
10
15
16
17
18
19
5
6
3
4
1
2
Value Filter type
0 none sliding average sliding average sliding average sliding average sliding average sliding average sliding average sliding average sliding average sliding average sliding average second order filter second order filter second order filter second order filter second order filter second order filter second order filter second order filter
Characteristics not filtered average of the last 2 measurements average of the last 3 measurements average of the last 4 measurements average of the last 5 measurements average of the last 8 measurements average of the last 16 measurements average of the last 25 measurements average of the last 32 measurements average of the last 40 measurements average of the last 50 measurements average of the last 64 measurements cut-off frequency at 15 Hz cut-off frequency at 10 Hz cut-off frequency at 8 Hz cut-off frequency at 6 Hz cut-off frequency at 4 Hz cut-off frequency at 2 Hz cut-off frequency at 1 Hz cut-off frequency at 0.8 Hz
The table below introduces the procedure for defining filtering:
Step
1
2
3
4
Action
Access the hardware configuration screen of the weighing module.
If filters F2 and F3 are being used, check the Active box, located in the
Threshold Check field.
For each phase, select the filtering coefficient from the drop-down menu.
Confirm reconfiguration if necessary.
TLX DS 57 PL7 xxE
315
Configuration
How to Modify the Flow Calculation
At a Glance
Functioning
Example
Procedure
You can choose the number of measurements for calculating the flow. (One measurement is taken every 20 milliseconds).
The flow is calculated using the following formula:
Flow n = (Valn - Valn-b)
This is a difference of the value of filtered weights for a number of configured measurements.
l l l
Where: b is the number of measurements for the flow calculation,
Valn and
is the value of filtered weight at the instant n,
Valn-b is the value of filtered weight at the instant n-b.
At each instant, the frequency is calculated and implicitly sent back to the processor as the weight measurement, in order to allow threshold corrections.
The flow is always calculated in high resolution format.
This calculation can be done on 2, 4,8, 16, 32 or 64 measurements.
By default, the number of measurements is 4.
The following figure illustrates a calculation on 4 measurements. n n+1 n+2 n+3 n+4 n+5
20ms 20ms 20ms 20ms 20ms flow n flow n+1 flow n+4 = Val n+4 - Val n flow n+5 = Val n+5 - Val n+1
The table below introduces the procedure for defining the flow calculation.
Step
1
2
3
Action
Access the hardware configuration screen of the weighing module.
Select the number of measurements using the drop-down menu.
Confirm reconfiguration if necessary.
316
TLX DS 57 PL7 xxE
Configuration
How to Modify the Tare
At a Glance The Tare is the weight measurement memorized during the last semi automatic
Taring command.
However, if necessary, you can introduce a tare value manually. Therefore, this tare value is known as "predefined" or "manual" and can be transmitted to the module. It is expressed in legal format (phys. unit with fixed decimal point).
The tare must be positive or zero and be lower than the Max. Weight.
Once a device of this sort is used, the "predefined" tare (PT) indicator is positioned.
It is no longer valid once a Taring order is executed.
Procedure
Note: The entry format extends from 0 to 65,535. If the user wants a greater tare, s/he must modify the scale division and enter the tare accordingly.
The table below presents the procedure for defining a predefined tare and the tare value.
Step
1
2
Action
Access the hardware configuration screen of the weighing module.
If necessary, check the Predefined box to confirm this function.
3
4
Note: If the box is already checked, you must firstly: l l l uncheck this box, confirm the configuration screen, check the Predefined box again.
Enter the tare value.
Confirm the reconfiguration.
TLX DS 57 PL7 xxE
317
Configuration
How to Modify the Threshold Check
At a Glance The threshold check manages the module's discrete outputs: l l
The
The
High flow cut-off point
Low flow cut-off point is associated with output S0.
is associated with output S1.
The configuration screen gives the following threshold check information.
Designation
Active
Direction
Phase 1 active outputs
Cut-off points
LF (Low Flow) mask time
Description
Discrete output management is in operation if this box is checked.
It is not checked by default.
The detection direction corresponds to the direction in which the thresholds are recognized, in either: l l
Weighing (filling)
Downweighing (emptying)
This is the concept of exceeding by a greater value, in the case of weighing, or by a lower value, in the case of downweighing.
By default, Weighing is selected.
The choice concerns the control of the S0 output on its own, or the S0 and S1 outputs at the same time.
See the explanation that follows.
By default, the module only activates S0 in the first phase.
The measurement can be associated with 2 thresholds for the following dosages: A High Flow cut-off point and a Low Flow cut-off point .
Depending on the logic defined, the S0 and S1 outputs go to zero when these thresholds are met.
The threshold values allowed lie between 0 and the maximum weight.
They are expressed in high resolution (one hundredth of a physical unit with fixed decimal point).
It defines the time after the high flow cut-off, during which the module no longer checks the Weight/Threshold;
This is to mask the overshoot caused when the product has a drop in voltage. The values allowed lie between 0 and 1.5 seconds per 1/10th sec step.
See the explanation that follows.
By default, this time is zero.
318
TLX DS 57 PL7 xxE
Activating
Outputs
Configuration
The following illustration describes the output functioning differences between the choice of active phase 1 Outputs: S0 or S0 and S1.
Active output phase 1 (S0)
Net Weight
Weighing
Low flow cut-off point
High flow cut-off point
Net Weight
Downweighing
High flow cut-off point
Output S0
Output S1
Time
Low flow cut-off point
Output S0
Output S1
Time
Active output phase 1 (S0and S1)
Net Weight
Weighing
Low flow cut-off point
High flow cut-off point
Net Weight
Downweighing
Output S0
Output S1
Time
High flow cut-off point
Low flow cut-off point
Output S0
Output S1
Time
TLX DS 57 PL7 xxE
319
Configuration
Masking Time The following illustration shows the role of the masking time, the role of which is to mask the overshoot caused when the product has a drop in voltage.
Net Weight
False cut-off point
Weighing
Low flow cut-off point
True cut-off point
High flow cut-off point
Dosage masking time
Total dosage time
Switch to low flow Restart weight monitoring
Time
Stop dosage
Procedure The table below introduces the procedure for threshold checks.
Step
1
2
3
4
5
6
Action
Access the hardware configuration screen of the weighing module.
If necessary, check the Active box to activate the Threshold Check function.
All parameters change from gray to black.
Click on the buttons corresponding to the detection direction ( Weighing ou
Downweighing ) and to the active phase 1 outputs ( S0 or S0 and S1 ).
Enter the Low flow and High flow cut-off points.
Select the LF masking time from the drop-down menu.
Confirm reconfiguration if necessary.
320
TLX DS 57 PL7 xxE
Weighing programming
16
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter describes the principles of programming a weighing application and all of the associated language objects.
This Chapter contains the following Sections:
Section
16.1
16.2
16.3
16.4
16.5
Topic
General on the weighing programming
Language objects for programmed exchange
Language objects for user-defined exchange
Description of the commands conveyed by program
Modifying the parameters by program
Page
321
TLX DS 57 PL7 xxE
Programming
16.1
General on the weighing programming
At a glance
The subject of this section
What's in this
Section?
This section describes the general principles of programming a weighing application.
This Section contains the following Maps:
Topic
Principle of programming a weighing application
Addressing Language Objects Associated with the Weighing Module
Description of the Main Objects Linked to the Weighing Function
Presymbolization
Page
322
TLX DS 57 PL7 xxE
Programming
Principle of programming a weighing application
General
Access to the measurements
Dynamic modification of the parameters
Once configured, the weighing module with sensors and associated with a TSX XBT
Y100 display panel can function autonomously (without a program). These outputs can be controlled without the intervention of the PLC processor’s program.
Programming the PLC processor supports: l Making available weighing information in order to carry out other processes or to guide other control units, l Dynamic modification of the weighing function’s parameters via explicit commands.
The numerical values, measurement of weight (GROSS or NET) and the flow are arranged into 2 double input register words (%ID). They are completed by 1 measurement Status word (%IW), 1 double tare value word (%ID) and 1 double shift register memory word (offsetting the zero) (%ID).
The following table lists the numerical weighing values conveyed by the weighing function.
Register address Meaning of the register
%IDxy.0.0
Weight value (GROSS or NET)
%IDxy.0.2
%IWxy.0.4
Flow
Measurement status: stability, zero…
%IDxy.0.5
%IDxy.0.7
Tare value
Shift register memory (offsetting the zero)
This data is automatically sent back to the processing unit at the beginning of the task associated with the channel, whether the task is in Run or in Stop. The data is directly accessible: l via a dialog operator in the application (access to the image objects in the PLC’s memory), l via the terminal by using the animation tables.
The adjustment parameters entered in configuration can be automatically modified during the course of the program via the WRITE_PARAM explicit exchange instruction.
Example : modification of the S0 large flow and S0 small flow cut-off points.
TLX DS 57 PL7 xxE
323
Programming
Addressing Language Objects Associated with the Weighing Module
At a Glance
Illustration
Bit and words object addressing is defined in the Common Applications (See Manual
Premium PLC applications volume 1) part.
This page introduces specifics linked to weighing modules.
Reminder of addressing principle:
% I, Q, M, K X, W, D, F
Symbol Type of Object Format
X
Rack
Y
Position i r
Channel No. Rank
Specific values The table below gives the values that are specific to weighing module objects.
i
Element Values Comment x y
0 to 1
0 to 7
TSX/PCX 5710).
TSX/PCX 572•/3•/4•).
00 to 10 When the rack number (x) is not 0, the position (y) is coded on 2 digits:
00 to 10. Conversely, if the rack number (x) = 0, eliminate the non significant zeros (elimination from the left) from "y" ("x" does not appear and "y" is on 1 digit for values <10).
r
0 or MOD MOD: channel reserved for module management and parameters common to all channels.
0 to 16 or
ERR
ERR: indicates a module or channel fault.
324
TLX DS 57 PL7 xxE
Programming
Description of the Main Objects Linked to the Weighing Function
Illustration
Sensors
Max range
Weight
The illustration presents the formation of the different functions executed by the module, and the associated language objects.
Measurement number %MWxy.0.14
%IDxy.0.5
%IDxy.0.2
Manual tare %MWxy.0.7
Tare Flow
%MWxy.0.6
Scaling
Filtering
F1
Adaptation to the process
Gross
Weight +
-
%IDxy.0.0
Net
Weight
Threshold monitoring
Signal
Metrological
Data
Stability criterion
Zero
Configuration
- Shift from source
%IDxy.0.7
%MDxy.0.8
%MDxy.0.10
Low flow
High flow
Weight
Direction
F1
F2
F3
%MWxy.0.12
%MWxy.0.13
%MWxy.0.15
%MWxy.0.16
Outputs
S0
S1
TLX DS 57 PL7 xxE
325
Programming
Description
Address
%IDxy.0.0
%IDxy.0.2
%IDxy.0.5
%IDxy.0.7
%MWxy.0.6
%MWxy.0.7
%MDxy.0.8
%MDxy.0.10
%MWxy.0.12
%MWxy.0.13
%MWxy.0.14
%MWxy.0.15
%MWxy.0.16
The following table describes the main language objects.
Role
Explicit
Explicit
Explicit
Explicit
Explicit
Explicit
Explicit
Type of object to exchange
Implicit
Implicit
Implicit
Implicit
Explicit
Explicit
Weight value (gross or net)
Flow
Tare value
Recalibration memory (zero offset)
F1 filter coefficient
Manual tare
S0 high flow cut-off point (dosage)
S1 low flow cut-off point (dosage)
Logic of outputs S0 and S1 (dosage)
LF mask time
Number of measurements used to calculate flow rate
F2 filter coefficient
F3 filter coefficient
326
TLX DS 57 PL7 xxE
Programming
Presymbolization
Introduction
Syntax
The weighing application supports automatic symbolization of the language objects associated with the module.
These objects are symbolized with the following syntax:
PREFIXE_UTILISATEUR_SUFFIXE_CONSTRUCTEUR
The elements have the following characteristics and meanings:
Description Element Maximum number of characters
PREFIXE_UTILISATE
UR
12
SUFFIXE_CONSTRU
CTEUR
20 generic symbol given to the channel by the user part of the symbol corresponding to the channel’s bit or word object given by the system
Example
Note: As well as the symbol, a comment constructor is automatically generated.
This comment reiterates the object’s role.
This example is about a weighing module situated in slot 3 of the PLC’s tray.
If the generic symbol (PREFIXE_UTILISATEUR) given is MESURE , the following symbols are automatically generated.
Address Type
%ID3.0
DWORD
Symbol
MESURE_POIDS
%ID3.0.2
DWORD MESURE_DEBIT
%ID3.0.5
EBOOL MESURE_TARE
Comment
Weight value
Flow value
Tare value
%ID3.0.7
EBOOL MESURE_MEMOIRE_RECALAGE Reset memory value
TLX DS 57 PL7 xxE
327
Programming
Procedure The table below introduces the procedure
Step
1
2
3
4
5
Action
Access the variables editor.
Access the I/O type variables.
Note: The channels whose objects can be symbolized have a letter P on the button on the left of the %CH address.
Double click on the P button of the channel to be symbolized.
Enter the user access code.
Note: If a symbol is already set by the channel, the suggested access code is the restored symbol, shortened to 12 characters.
Confirm with the Presymbolize button.
Deleting the presymbolization
Canceling the presymbolization supports, for any given logic channel, deletion of all or some of an object’s symbols.
Two options are available:
If the option chosen is…
Delete all presymbols
Then…
No prefix is chosen and all the symbols are deleted (including those that have been modified directly in the editor).
Delete the access-coded presymbols Only the objects that have an identical access code to the one entered are deleted.
328
TLX DS 57 PL7 xxE
16.2
Programming
Language objects for programmed exchange
At a glance
The subject of this section
What's in this
Section?
This section describes all the weighing module’s objects for programmed exchange.
This Section contains the following Maps:
Topic
Bit language objects for default exchange associated with the weighing function
Implicit Exchange Language Word Objects Associated with the Weighing
Application
Page
TLX DS 57 PL7 xxE
329
Programming
Bit language objects for default exchange associated with the weighing function
At a glance
Bit objects
Address (1)
%Ixy.0.ERR
%Ixy.MOD.ERR
Caption:
(1)
These are the bit objects whose exchanges are done automatically in each task cycle in which the module channels are configured.
The table below introduces the different bit objects for user defined exchange.
Function
Channel bit error
Module bit error
Meaning when the bit is at state 1
Indicates that there is an error with the channel.
Indicates that there is an error with the module.
Note xy = module address. l l x for the rack number, y for the position in the rack.
With the weighing module, the channel and the module information levels are identical.
Validity conditions for the measurements and the module
The channel (or module) error bit is there to make sure that the numerical values are valid, so it is necessary to monitor this error bit.
Note: The error bit rises to 1 when an error condition appears on the channel
(underload/overload,…). To find out the details of the error, you have to monitor the channel status.
Performance of the error bits
According to the type and seriousness of the errors, the corresponding error bit can be transient (it goes back to 0 when the error disappears) or stored (it stays at 1 even if the error disappears). Only internal errors are stored type, the others are transient errors.
330
TLX DS 57 PL7 xxE
Programming
Implicit Exchange Language Word Objects Associated with the Weighing
Application
At a Glance
Word objects
Address (1)
%IDxy.0.0
%IDxy.0.2
%IWxy.0.4
%IDxy.0.5
%IDxy.0.7
These are word objects whose exchanges are done automatically at each cycle of the task in which the module channels are configured.
The table below presents the different implicit exchange word objects.
Function
Double status word
Double status word
Status word
Double status word
Double status word
Meaning (for the bit at status 1)
Weight value (gross or net).
By default, if no taring command has been executed, the weight value is expressed as a GROSS weight. It changes to NET weight as soon as the taring command is executed or a tare has been manually introduced.
The measurement is expressed in legal format or high resolution according to the choice created at configuration.
Flow .
Example: %IDxy.0.2 = 450 000 signifies that, if the scale division is equal to
1.10
-2
kg, a weight difference of 45 kg has been measured between n measurements (sampling every 20 ms).
The n number of measurements is defined at configuration.
Information about the measured value (see details in following table).
Tare value .
This word allows the current tare value to be visualized in the same format as the weight. It is memorized by the module.
It is reset to 0 at each calibration.
Recalibration memory (zero offset)
This word allows the offset to be visualized currently in high resolution format. This value is memorized by the module. It is reset to 0 at each calibration.
Key:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
TLX DS 57 PL7 xxE
331
Programming
Measurement
Status Words
Address (1)
%IWxy.0.4:X0
%IWxy.0.4:X1
%IWxy.0.4:X2
%IWxy.0.4:X3
%IWxy.0.4:X4
%IWxy.0.4:X5
%IWxy.0.4:X6
%IWxy.0.4:X7
%IWxy.0.4:X8
%IWxy.0.4:X9
%IWxy.0.4:X10
%IWxy.0.4:X11
%IWxy.0.4:X12
%IWxy.0.4:X13
%IWxy.0.4:X14
%IWxy.0.4:X15
The table below describes the coding of the %IWxy.0.4 status word.
Meaning (for the bit at status 1)
Image of output S0.
Image of output S1.
Indicator that voltage is too low. The measurement is deviating. There is a strong possibility of an error on a sensor or in the wiring.
Voltage too high on module input.
Sealed module.
Processing in progress (Taring, Reset, etc.)
Calibration during processing.
Fault during command.
NET weight measurement.
Measurement instability.
This is set when the measurement is outside the stability range during the defined time. The extent of the stability range and the time are defined during configuration.
Zero indicator. This is set when the deviation from zero is not greater than +/- 1/4 of the scale division.
Zero tracking indicator active.
Predefined or manual tare indicator (language element specific to module, accessible in read only). This is set when the tare is not the result of a taring command but rather an entry by the user
Reserved.
Module in forced calibration.
Number of converter points.
Key:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
332
TLX DS 57 PL7 xxE
16.3
Programming
Language objects for user-defined exchange
At a glance
The subject of this section
What's in this
Section?
This section describes all the weighing module’s objects for user-defined exchange.
This Section contains the following Maps:
Topic
Explicit Exchange Objects
Explicit Exchange Objects: Current Exchange and Report
Object for user-defined exchange: Module Status %MWxy.MOD.2
Explicit Exchange Object: %MWxy.0.2 status channel
Explicit Exchange Object: Command Word %MWxy.0.3
Page
TLX DS 57 PL7 xxE
333
Programming
Explicit Exchange Objects
At a Glance Explicit exchange objects carry information (e.g.: default terminal block, missing module, etc.) and additional commands for advanced programming of applicationspecific functions.
Note: The configuration constants (See Reading the configuration parameters,
p. 357) %[email protected] (@module = module address), are read only and
correspond to the configuration parameters entered using the Configuration editor.
Explicit exchange objects are exchanged at the demand of the user program, using l l l l l l the following instructions:
READ_STS (read status words),
WRITE_CMD (write command words),
WRITE_PARAM
READ_PARAM
SAVE_PARAM
(write adjustment parameters),
(read adjustment parameters),
(save adjustment parameters),
RESTORE_PARAM (restoring adjustment parameters).
334
TLX DS 57 PL7 xxE
Description
Programming
The table below provides the meaning of the different %MWxy.i.j
words.
Address (1)
%MWxy.MOD.2
%MWxy.0.0
%MWxy.0.1
%MWxy.0.2
%MWxy.0.3
%MDxy.0.4
%MWxy.0.6
%MWxy.0.7
%MDxy.0.8
%MDxy.0.10
%MWxy.0.12
%MWxy.0.13
%MWxy.0.14
%MWxy.0.15
%MWxy.0.16
Meaning (for the bit at status 1)
Module status
Exchange in progress
Exchange report
Instructions ensuring exchange
READ_STS
-
-
Channel status
Command order (See Explicit Exchange Object:
Command Word %MWxy.0.3, p. 339 )
(calibration, taring, setting to zero, etc.)
READ_STS
WRITE_CMD
Standard load weight for the calibration command
F1 filter coefficient
Manual tare value
S0 high flow cut-off point (dosage)
S1 high flow cut-off point (dosage)
Logic of S0 and S1 outputs
Low Flow mask time
Number of measurements used to calculate flow rate.
F2 filter coefficient
F3 filter coefficient
WRITE_PARAM
READ_PARAM
SAVE_PARAM
RESTORE_PARAM
Legend:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
TLX DS 57 PL7 xxE
335
Programming
Explicit Exchange Objects: Current Exchange and Report
Introduction to
"Current
Exchange" Word
This word type object with the address %MWxy.0.0
carries information about the current exchanges in the channel.
"Current
Exchange"
Description
The table below provides the meaning of the different bits of the %MWxy.0.0
word.
Address (1)
%MWxy.0.0:X0
%MWxy.0.0:X1
%MWxy.0.0:X2
Meaning (for the bit at status 1)
Current status parameter exchange.
Current command parameter exchange.
Current adjustment parameter exchange.
Legend:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
Introduction to the "Report"
Word
"Report" Word
Description
This word type object with the address %MWxy.0.1
carries information about the exchange reports in the channel.
The table below provides the meaning of the different bits of the %MWxy.0.1
word.
Address (1)
%MWxy.0.1:X0
%MWxy.0.1:X1
%MWxy.0.1:X2
Meaning (for the bit at status 1)
Status parameter exchange fault.
Command parameter exchange fault.
Adjust parameter exchange fault.
Legend:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
336
TLX DS 57 PL7 xxE
Programming
Object for user-defined exchange: Module Status %MWxy.MOD.2
At a glance
Description
This word type object supplies information on the state of the module.
The table below provides the meaning of the different bits of the %MWxy.MOD.2
word.
Address (1)
%MWxy.MOD.2:X0
%MWxy.MOD.2:X1
%MWxy.MOD.2:X2
%MWxy.MOD.2:X3
%MWxy.MOD.2:X4
%MWxy.MOD.2:X5
%MWxy.MOD.2:X6
%MWxy.MOD.2:X7
Meaning (for the bit at state 1)
Internal error: Module is Out of Service.
Functional Error: communication or application error
Unused
Unused
Reserved
Configuration Error: the recognized module is not the one anticipated.
Default module is absent or switched off.
Unused
Caption:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
TLX DS 57 PL7 xxE
337
Programming
Explicit Exchange Object: %MWxy.0.2 status channel
At a Glance
Description
This word type object carries channel information about the status of channel 0.
The table below provides the meaning of the different bits of the %MWxy.0.2
word.
Address (1)
%MWxy.0.2:X0
%MWxy.0.2:X1
%MWxy.0.2:X2
%MWxy.0.2:X3
%MWxy.0.2:X4
%MWxy.0.2:X5
%MWxy.0.2:X6
%MWxy.0.2:X7
%MWxy.0.2:X8
%MWxy.0.2:X9
%MWxy.0.2:X10
%MWxy.0.2:X11
%MWxy.0.2:X12
%MWxy.0.2:X13
%MWxy.0.2:X14
%MWxy.0.2:X15
Meaning (for the bit at status 1)
External error: Overload or underload during calibration
Range (2) overshoot fault or dynamics lower than 4.5mV at calibration
External error: saturation of the measurement circuit
External error: sealed module, configuration refused
Internal error: module failure
Configuration fault: the current module is not the one declared at configuration
Communication fault with the processor
Application fault
Protected module error, parameter refused: the module refuses the parameter if it influences the current value.
Non-calibrated module
Overload error
Underload error
Taring mode
Zero mode
Calibration mode
Forced calibration mode
Legend:
(1)
(2) xy = module address.
l l x for the rack number, y for the position in the rack.
This bit is activated as soon as the gross measured filtered weight value overshoots the overload threshold or is below the underload threshold. The 2 errors can be discriminated by the specific errors: underload error or overload error.
Note All internal fault detection on the module is conveyed by the position control of the discrete outputs to their fallback values (0 electric).
338
TLX DS 57 PL7 xxE
Programming
Explicit Exchange Object: Command Word %MWxy.0.3
At a Glance
Description
This word type object allows weighing module commands to be sent by explicit exchange ( WRITE_CMD instruction).
The table below provides the meaning of the different bits of the %MWxy.0.3
word.
Address (1)
%MWxy.0.3:X0
%MWxy.0.3:X1
%MWxy.0.3:X2
%MWxy.0.3:X3
%MWxy.0.3:X4
%MWxy.0.3:X5
%MWxy.0.3:X6
%MWxy.0.3:X7
%MWxy.0.3:X8
%MWxy.0.3:X9
%MWxy.0.3:X10
%MWxy.0.3:X11
%MWxy.0.3:X12
%MWxy.0.3:X13
%MWxy.0.3:X14
%MWxy.0.3:X15
Meaning (for the bit at status 1)
Save calibration coefficients in module.
Zero Load calibration.
Calibration Weight Calibration (Normal condition).
Cancellation of command (calibration, setting to zero, taring).
Taring order.
Reset order.
Return to GROSS weight order.
3 second display of manual tare.
Enable thresholds.
Disable thresholds.
Forced calibration (CPU -> Module).
Save calibration coefficients in processor.
Calibration weight calibration in degraded condition (Standard load < 70% of maximum weight).
Unused
Unused
Unused
Key:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
TLX DS 57 PL7 xxE
339
Programming
16.4
Description of the commands conveyed by program
At a glance
The subject of this section
What's in this
Section?
This section describes the different commands that can be executed by program.
This Section contains the following Maps:
Topic
Send Commands to Weighing Module by Program
How to carry out the tare mode via the program
How to set to zero the value of the weight by the program
How to return to gross weight measurement via the program
How to display the manual tare via the program
How to Enable or Disable Thresholds by Program
Page
340
TLX DS 57 PL7 xxE
Programming
Send Commands to Weighing Module by Program
General Sending commands to the module is done using the WRITE_CMD instruction with the following syntax: WRITE_CMD %CHxy.0
This instruction sends the order to the module and awaits its acknowledgement. This wait may require several task cycles.
Monitoring
Parameter
Recognition
Note: The module only interprets one command at a time. If a command is requested while the previous command is being processed, the new command is refused. There should never be more than one bit at 1 in the command word.
As the module may require several task cycles to recognize commands, two memory words are standardized to monitor the %MWxy.0.0 and %MWxy.0.1 exchanges
The first word %MWxy.0.0 indicates a current exchange.
The second word %MWxy.0.1 gives the exchange report.
The following table describes the objects used for monitoring the sending of commands to the module.
Address (1)
%MWxy.0.0:X1
%MWxy.0.1:X1
%MWxy.0.2:X7
Meaning (for the bit at status 1)
indicates that the command has been sent to the module.
specifies if the command is accepted by the module.
signals that a command or parameter has been refused (application fault).
Legend:
(1) xy = module address.
l l x for the rack number, y for the position in the rack.
TLX DS 57 PL7 xxE
341
Programming
How to carry out the tare mode via the program
At a glance This function leads the value of the measured NET weight to zero when a load, or tare, is placed on the load holder.
It therefore supports movement of the measurement with an offset value, in order to make it conform to the user’s expected value.
When no tare mode operation has been carried out, the NET weight is the same as the GROSS weight.
Note: l When changing configuration, all tares are deleted. Any Tare mode execution cancels all tares input in manual mode and resets the "manual" tare indicator to l zero.
Also, an order to return to GROSS weight allows you to delete all tare modes. It does not need any acceptance condition.
Execution conditions for the tare mode l l l
The Tare mode command’s execution acceptance conditions are the following:
The measurement is stable.
The measurement is below the maximum range.
The measurement is strictly positive.
342
TLX DS 57 PL7 xxE
Programming
Procedure The following table describes the procedure for executing a tare mode operation.
Step Action Performance of the module
1 Input the WRITE_CMD instruction while programming the tare mode order (%MWxy.0.3:X4 = 1).
-
2 Confirm the execution, with the application in RUN.
The module switches to tare mode and sends the
%IWxy.0.4:X5 = 1 TRAITEMENT_EN_COURS report.
Acquires the tare.
Note: The value of the weight is measured and stored in the associated %IDxy.0.5.It will be taken from all further GROSS weight measurements to determine the NET weight.
End of acquisition: TRAITEMENT_EN_COURS = 0
3 Monitoring the command’s smooth execution: State
TRAITEMENT_EN_COURS : %IWxy.0.4:X5
The module stays in the TRAITEMENT_EN_COURS state for as long as the acceptance conditions are not met or until it receives an order to cancel the command.
Summary of the data used
The table below provides a table of the data used for a tare mode.
Type
Command
Display
Role
Tare mode order
Tare value
Tare mode in progress
Associated data
%MWxy.0.3:X4
%IDxy.0.5
%IWxy.0.4:X5
TLX DS 57 PL7 xxE
343
Programming
Example The following example in instruction list language describes a tare mode order being sent to the weighing module in slot 2, rack 0.
LD TRUE
S %MW 2.0.3:X4
[WRITE_CMD %CH2.0]
Executing the program involves:
2
3
Phase
1
4
Description
Sending the command.
Setting the %MW2.0.0:X1 bit to 1, showing that the command is being sent.
This bit remains at 1 until the module sends a report. The bit then goes back to
0. The exchange report bit is then relevant.
The %MW2.0.1:X1 exchange report bit rises to 1 if there is a problem during the exchange. The 0 value shows that the command has been accepted by the module.
Note:
%IW2.0.4:X5 stays at 1 (In progress) for as long as the acceptance conditions are not met (waiting for measurement stability, for example).
The status channel’s application fault bit is at 1 (module executing command). As for all commands, the order can be cancelled by sending the "cancel command in progress" command.
344
TLX DS 57 PL7 xxE
Programming
How to set to zero the value of the weight by the program
At a glance This function leads the value of the measured weight to zero. The zero flag is therefore set.
It is controlled via the Set to Zero command bit. The correction carried out on the measurement is stored in the %IDxy.0.7 word, in high format resolution. It can be saved by the application. This parameter is reset to zero on each calibration.
Note: When changing configuration, all settings to zero are deleted.
Execution conditions for setting to zero l l l
The set to zero command’s execution acceptance conditions are the following:
The measurement is in GROSS weight.
The measurement is stable.
The measurement is included in the zero format’s print range, as set in configuration.
Procedure The following table describes the procedure for executing a set to zero :
Step Action Performance of the module
1 Input WRITE_CMD while programming the Set to zero order (%MWxy.0.3:X5 = 1).
-
2 Confirm the execution, with the application in RUN.
The module switches to MISE_A_ZERO mode and sends the TRAITEMENT_EN_COURS report.
%IWxy.0.4:X5 = 1.
The module proceeds to acquire the measurement and stores the new value in the %IDxy.0.7 shift register memory.
TRAITEMENT_EN_COURS = 0 shows the end of the procedure.
3 Monitoring the command’s smooth execution: State
TRAITEMENT_EN_COURS : %IWxy.0.4:X5
The module stays in the TRAITEMENT_EN_COURS state for as long as the acceptance conditions are not met or until it receives an order to cancel the command.
TLX DS 57 PL7 xxE
345
Programming
Summary of the data used
The table below provides the data used for resetting to zero.
Type
Command
Display
Report
Role
Setting to 0 order
Associated data
%MWxy.0.3:X5
Shift register memory %IDxy.0.7
In progress %IWxy.0.4:X5
Example The following example in instruction list language describes a MISE_A_ZERO order being sent to the weighing module in slot 2, rack 0.
LD TRUE
S %MW 2.0.3:X5
[WRITE_CMD %CH2.0]
Executing this order involves:
2
3
Phase
1
4
Description
Sending the command.
Setting the %MW2.0.0:X1 bit to 1, showing that the command is being sent.
This bit remains at 1 until the module sends a report. The bit then goes back to
0. The exchange report bit is then relevant.
The %MW2.0.1:X1 exchange report bit rises to 1 if there is a problem during the exchange.The 0 value shows that the command has been accepted by the module.
Note:
%IW2.0.4:X5 stays at 1 (In progress) for as long as the acceptance conditions are not met (waiting for measurement stability, for example).
The status channel’s application fault bit is at 1 (module executing command).
As for all commands, the order can be cancelled by sending the cancel command in progress command.
346
TLX DS 57 PL7 xxE
Programming
How to return to gross weight measurement via the program
At a glance This function cancels the value of the tare so that the value of the current weight is in gross weight.
The current weight is stored in the %IDxy.0.0 word, in the format set in configuration.
This command does not require any particular execution conditions.
Execution conditions for the tare mode
Procedure The following table describes the procedure for executing a return to measurement in gross weight.
Step Action Performance of the module
1 Input the WRITE_CMD while programming the return to measurement in gross weight (%MWxy.0.3:X6 =
1).
-
2 Confirm the execution, with the application in RUN. The module switches to "return to gross weight" mode.
The module then sets the tare to zero.
3 Monitoring the command’s smooth execution: State of the NET flag: %IWxy.0.4:X8
-
The NET = 0 (%IWxy.0.4:X8=0) flag shows the end of the procedure.
Summary of the data used
The table below provides the data used for resetting to zero.
Type
Command
Display
Report
Role
Return to gross weight order
Measured weight
Value of the Tare in progress
In progress
Gross weight
Associated data
%MWxy.0.3:X6
%IDxy.0.0
%IDxy.0.5
%IWxy.0.4:X5
%IWxy.0.4:X8 = 0
TLX DS 57 PL7 xxE
347
Programming
How to display the manual tare via the program
At a glance
Execution conditions for the tare mode
This function supports display of the manual tare on the display panel for 3 seconds.
For this command, a manual tare must have already been configured.
Procedure The following table describes the procedure for displaying the manual tare.
Step Action
1 Input WRITE_CMD while programming the display order (%MWxy.0.3:X7 = 1).
Performance of the module
-
2 Confirm the execution, with the application in RUN.
The module manages its data normally.The values displayed on the TSX XBT H100 display panel show the manual tare’s value.
3 After the 3 second delay, the display panel reverts to its current values.
-
Summary of the data used
The table below provides the data used for resetting to zero.
Type
Command
Display
Role
Tare display order
Manual tare
Associated data
%MWxy.0.3:X7
The data on the display panel show the manual tare.
348
TLX DS 57 PL7 xxE
Programming
How to Enable or Disable Thresholds by Program
At a Glance
Operating
Principle
Enabling
Procedure
These functions are primarily used to coordinate the output command with the processor-managed mechanism.
The threshold check option must first be enabled in the configuration screen.
Action on outputs is performed from the: Enable thresholds command. Once this command has been executed, the threshold check cycle starts.
A disable command lets you to stop the threshold check cycle in progress and authorize a new threshold enabling command.
If need be, this command will also reset outputs S0and S1 to 0.
The following table describes the procedure for enabling thresholds.
Step Action Module behavior
1 Make the necessary changes to the threshold values, output logic and mask time.
-
2 Position the threshold enabling order
(%MWxy.0.3:X8 = 1).
-
3 Launch threshold enabling using the
WRITE_CMD instruction.
The module interprets the request, sets the
S0 and S1 outputs and ensures the conformity of the image bits: l l
%IWxy.0.4: Current X0 position of S0.
%IWxy.0.4: Current X1 position of S1.
Disabling
Procedure
The following table describes the procedure for disabling thresholds.
Step Action
1 Position the threshold disabling order (%MWxy.0.3:X9 = 1).
Module behavior
-
2 Launch threshold disabling using the
WRITE_CMD instruction.
The module sets outputs to idle and image bits to 0.
TLX DS 57 PL7 xxE
349
Programming
Summary of Data
Used
The table below provides the data used for enabling and disabling thresholds.
Type
Command
Display
Role
Threshold enabling order
Threshold disabling order
Current flow
High flow threshold
Low flow threshold
Output logic
PD mask time
S0 current position
S1 current position
Associated data
%MWxy.0.3:X8
%MWxy.0.3:X9
%IDxy.0.2
%MDxy.0.8
%MDxy.0.10
%MWxy.0.12
%MWxy.0.13
%IWxy.0.4:X0
%IWxy.0.4:X1
350
TLX DS 57 PL7 xxE
Programming
16.5
Modifying the parameters by program
At a glance
The subject of this section
What's in this
Section?
This section describes how to dynamically modify the application’s parameters by program.
This Section contains the following Maps:
Topic
Modify Parameters by Program
PL7 instructions used for adjustments
Description of Parameters Adjustable by Program
Reading the configuration parameters
Page
TLX DS 57 PL7 xxE
351
Programming
Modify Parameters by Program
Principle
List of
Adjustable
Parameters
You can command the modification of certain parameters by program, in order to automatically adapt the measurements to the processing applications.
Example: modifying the tare value by program if several types of product are to be weighed with different conditioning.
The following parameters may be modified by program:
Adjustable parameters
F1 filter coefficient
"Manual" tare value
Cut-off points (thresholds)
Logic of S0 and S1 outputs
LF mask time
Number of measurements used to calculate flow rate
F2 filter coefficient
F3 filter coefficient
Corresponding data
%MWxy.0.6
%MWxy.0.7
%MDxy.0.8 and %MDxy.0.10
%MWxy.0.12
%MWxy.0.13
%MWxy.0.14
%MWxy.0.15
%MWxy.0.16
Possible Actions You can: l l l l
Modify an adjustment parameter by program,
Send adjustment parameters to the module,
Control the module's parameter recognition,
Read the adjustment parameter value in the module and thereby update the PLC l l memory,
Save the adjustment parameters,
Restore the value of saved parameters to the PLC memory.
352
TLX DS 57 PL7 xxE
Instructions
Used
Programming
The instructions used to do these operations are as follows:
Instruction
WRITE_PARAM %CH xy.0
READ_PARAM %CH xy.0
Function carried out
Send the parameter contents of the previous table to the weighing module.
Reads the adjustment parameters in the module and updates the previously cited table.
SAVE_PARAM %CH xy.0
Saves the adjustment parameter values in the memory zone of the processor. These parameter values will be the ones used when the PLC is started from cold.
RESTORE_PARAM %CH xy.0
Allows the adjustment parameters to be reloaded with the values entered at module configuration or at the last
SAVE_PARAM .
The module can process several adjustments simultaneously.
TLX DS 57 PL7 xxE
353
Programming
PL7 instructions used for adjustments
General
Send the adjustment parameters to the module
To be able to carry out adjustment operations, you must be able to access the module’s own data.
This is done by using the following instructions.
Sending the parameters from the module’s channel is done by using the
WRITE_PARAM instruction, with the following syntax:
WRITE_PARAM %CH xy.0
This instruction sends the contents of the parameters to the module and waits for its acknowledgement. This can take several task cycles.
Monitoring the acknowledgeme nt of the parameters
As the module can take several task cycles to acknowledge values, two memory l l l words are used to monitor the exchanges: %MWxy.0.0
and %MWxy.0.1
The first word %MWxy.0.0
shows that there is an exchange in progress,
The second word %MWxy.0.1
gives the report on the exchange,
The bits in position 2 are associated to the adjustment parameters: l The %MWxy.0.0:X2 bit shows that the adjustment parameters are sent to the module, l The %MWxy.0.1:X2 bit specifies whether the adjustment parameters are accepted by the module.
Example l l
Writing the module’s parameters in slot 2 of rack 0,
WRITE_PARAM %CH2.0
involves:
Sending the adjustment parameters,
Setting the %MW2.0.0:X2 bit to 1, showing that the adjustment parameters are being sent. This bit remains at 1 until the module sends a report. The bit then l goes back to 0. The exchange report bit is then relevant.
The %MW2.0.1:X2 exchange report bit rises to 1 if there is a problem during the exchange. The 0 value shows that the data has been accepted by the module.
354
TLX DS 57 PL7 xxE
Reading the adjustment parameters
Saving the adjustment parameters
Restoring the saved adjustment parameters
Programming
The READ_PARAM instruction supports reading the module’s adjustment parameters and updating the PLC’s memory. It is particularly useful after a WRITE_PARAM that the module has not accepted. Reading the adjustment parameters can take several task cycles.
Reading the adjustment parameters from the module’s channel is done by using the
READ_PARAM instruction, with the following syntax:
READ_PARAM %CH xy.0
The SAVE_PARAM instruction allows you to copy the current values of the module’s adjustment parameters in the backup zone, set in the processor’s memory. The backup zone is not accessible from the language.
This instruction can take several task cycles to be executed. Saving the module’s adjustment parameters is done by using the SAVE_PARAM instruction, with the following syntax:
SAVE_PARAM %CH xy.0
The RESTORE_PARAM instruction supports restoring of the saved adjustment parameter values in the processor’s memory and in the module.
Restoring the adjustment parameters from the module is done by using the
RESTORE_PARAM instruction, with the following syntax:
RESTORE_PARAM %CH xy.0
TLX DS 57 PL7 xxE
355
Programming
Description of Parameters Adjustable by Program
Description The following table describes the parameters that can be adjusted by program, using the WRITE_PARAM instruction.
Word
%MWxy.0.6
%MWxy.0.15
%MWxy.0.16
Role
Filter Coefficients
Description
The admissible filter coefficient values are between 0 and 19.
%MWxy.0.7
%MD xy.0.8
%MD xy.0.10
%MWxy.0.12
"Manual" tare value The admissible "manual" tare values are between 0 and 65535. They cannot exceed the maximum range.
Cut-off points
(thresholds)
Output logic
S0 high flow cut-off point
S1 low flow cut-off point
The threshold values allowed lie between 0 and the maximum weight in high resolution format..
If a threshold check has not been defined at configuration, no detection processing is done. The value of these threshold is zero by default.
Note: l l
When weighing, HF < LF < Maximum weight
In downweighing: LF < HF < Maximum weight
The module carries out a coherence check of the threshold values. If this logic is not respected, the thresholds will be refused.
l l
%MWxy.0.12:X0 l l
0: Weighing
1: Downweighing l l
%MWxy.0.12:X1
0: S0 then S1
1: S0 then S1 then S1
%MWxy.0.13
LF mask time
%MWxy.0.14
Number of measurement for flow
Admissible values are between 0 and 15 per 1/10 of a second step (0 = 0s, 1= 0.1s, 2 = 0.2s, etc.).
Admissible values are values 2, 4, 8, 16, 32 or 64.
356
TLX DS 57 PL7 xxE
Programming
Reading the configuration parameters
General All of the parameters entered during the module’s configuration can be accessed by program in read only.
These parameters are coded in 3 words from the %KW constant zone.
Coding the maximum range
Reading the maximum range, which is configured for measurement channel, can be accessed via the %KWxy.0.0 word.
Coding the measurement unit
Reading the unit and the grade, which are configured for measurement channel, can be accessed via the %KWxy.0.1 word.
The measurement unit is coded on 3 bits of the least significant byte.
%KWxy.0.1:least significant bit bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
The following table describes the coding for the unit of measurement.
3
4
5
1
2
Bits 0 to 2
0
Corresponding unit g t kg lb oz
<none>
Role gram kilogram ton (metric) pound (= 453g) ounce (= 28.35g) no unit
TLX DS 57 PL7 xxE
357
Programming
Coding the grade Reading the unit and the grade, which are configured for measurement channel, can be accessed via the %KWxy.0.1 word.
Note: The grade is still set in the same unit as the measurement
The grade is coded on 5 bits of the most significant byte. most significant bit %KWxy.0.1
bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8
The following table describes the coding for the grade.
7
8
9
10
5
6
3
4
1
2
Bits 8 to 12 Corresponding unit
0 0.001
0.002
0.005
0.01
0.02
0.05
0.1
1
2
0.2
0.5
18
19
20
14
15
16
17
Bits 8 to 12 Role
11 5
12
13
10
20
50
100
200
500
1000
2000
5000
358
TLX DS 57 PL7 xxE
Programming
Coding the stability, the zero, the thresholds, the outputs and the format
Reading the format print range and the stability time as well as the zero format print range, the zero follower’s activity, the overload threshold, the use of outputs and the weight value formats, configured for the measurement channel, can be accessed via the %KWxy.0.2 memory word.
Coding of the %KWxy.0.2 word.
%KWxy.0.2:least significant bit bit 7 bit 6 bit 5
Stability time bit 4 bit 3 bit 2 bit 1
Stability print range bit 0 most significant bit %KWxy.0.2
bit 15 bit 14 bit 13 bit 12 bit 11 bit 10
Format Outputs Zero follower
Manual tare
Print range
Zero
Sensor supply bit 9 bit 8 overload
The following table describes the stability print range’s coding (bits 0 to 2).
3
4
1
2
Value read Equivalence in grade
0 2
3
4
6
8
The following table describes the stability time’s coding (bits 4 to 5).
1
2
Value read Equivalence in seconds
0 0.4
3
0.5
0.7
1
The following table describes the overload’s coding (bits 8 to 9).
1
2
Value read Type of overload selected
0 Maximum range + 9 grades
Maximum range + 2% of the maximum range
Maximum range + 5% of the maximum range
TLX DS 57 PL7 xxE
359
Programming
The following table describes the coding for the other parameters. These parameters are all coded on a %KWxy.0.2 word bit.
bit at 0 bit at 1 Bit number
11
Parameter
Recalibration range
12
13
14
15
Predetermined tare
Activity of the zero follower
Using the outputs
Format
+/-2% of the maximum range
No predetermined tare
Inactive
+/-5% of the maximum range
Predetermined tare
Active
Not used
Legal (fixed point physical unit)
Used
High resolution (100th of a fixed point physical unit)
360
TLX DS 57 PL7 xxE
Calibrating the measurement string
17
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter describes how to calibrate the measurement string.
This Chapter contains the following Maps:
Topic
Introduction to the Calibration Function
Description of the Calibration Screen
Calibrating the Analog Measurement System
Calibrating the Analog Measurement System by Program
How to Achieve Forced Calibration
Performing a Forced Calibration by Program
Page
TLX DS 57 PL7 xxE
361
Calibration
Introduction to the Calibration Function
General The calibration of the analog measurement system consists in making a weight value correspond to an electrical signal transmitted by sensors.
This adaptation is made on site when the product is set up. It is necessary to ensure the measurement's validity.
Note: The calibration function, forced or not, is only accessible in offline mode with the PLC in Run.
Calibration rules Any non-calibrated module is in channel fault (can be seen in the debug screen or on the module, by the flashing of channel 0).
The first calibration must be complete:
1.
Zero Load
2.
Standard Load
3.
Save otherwise the information returned means nothing.
Calibration cannot be performed if the PLC processor has a Flash-Eprom memory card (TSX MFP 032P or TSX MFP 064P or TSX MFP 0128P).
Calibration can be redone throughout the module's life. The electronics characteristics do not require regular recalibration. However, legal constraints or the application's mechanical characteristics may require calibration, particularly for commercial transactions.
Note: Calibration is independent of the configured filter, but takes into account
Metrological and Stability Information parameters.
362
TLX DS 57 PL7 xxE
Calibration
Calibration Type You can choose one of the following 3 calibration types: l normal calibration (The calibration function must be performed with a standard l load weight that is greater than or equal to 70% of the maximum weight), graded calibration (If for various reasons calibration cannot performed under the conditions previously described), l forced calibration: l CPU -> Module: Being able to restore adjustments made to a different module in the event of a maintenance concern or duplication l Module -> CPU: Being able to make the processor parameters conform with the parameters of a calibrated module that is connected to a new slot.
TLX DS 57 PL7 xxE
363
Calibration
Description of the Calibration Screen
At a Glance
Illustration
The calibration screen gives access to calibration commands.
This screen can be only accessed in offline mode.
1
2
TSX ISP Y101 [RACK 0 POSITION 3]
Calibration
Designation: 1I. WEIGHING 3 FILTERS
RUN ERR IO
3
4
Symbol:
Channel:
0
Function:
Weighing
Weight
Value: 137.66
Kg
NET
Task:
MAST
Calibration
Zero load
Standard
Load 130.00
Cancel Save
Kg
Forced Calibration
CPU --> Module
Module --> CPU
Cancel
DIAG...
DIAG...
General
Description
Element Addre ss
1
2
3
4
The table below shows the different elements of the calibration screen and their functions.
Function
Title bar Indicates the reference of the module selected and its physical position and the rack number.
Module zone Allows selection of screen type, access to the adjustment part of the screen, and to diagnostic functions.
Displaying this zone is optional. Choose using the View
→
Module Zone command.
Visualization zone
Gives access to the weighing information visualization (See Description of the weighing
debug screen’s display zone, p. 376
).
Calibration zone
Gives access to calibration commands (See Calibrating the Analog Measurement System,
364
TLX DS 57 PL7 xxE
Calibration
Calibrating the Analog Measurement System
At a Glance Calibrating can be done on a PL7 station connected to the PLC using the calibration screen.
It can also be done using an operator dialog, which uses PL7 language instructions.
Note: The procedure can be stopped at any time by pressing Cancel . The module reverts to the previous parameters. The current calibration parameters are therefore lost.
The procedure is only enabled if the module has been calibrated correctly.
If there is a measurement saturation problem, the new parameters cannot be saved.
Either the error must be corrected or the procedure be cancelled, using Cancel .
Procedure This table describes the procedure for calibrating the analog measurement system.
Step
1
Action
Switch the rack on.
2 Access the calibration screen:
1.
select Tools
→
Configuration
2.
click on the module's slot
3.
select Calibration from the drop-down menu
Note: the processor must be in RUN and the terminal in offline mode.
3 Check that the counter output is empty.
4 Click the Zero Load button to carry out zero load calibration (recognized by the load receiver).
5 Place calibration weight.
Result
The product is initialized, carries out self-tests and receives its configuration.
-
-
This phase requires around 20 seconds.
The Zero Load button switches to reverse image during this phase and an hour glass appears.
The module switches to channel fault and all measurements are invalid.
The status of the indicator %IWxy.0.4:X6
Calibration_in_progress changes. The module indicates the acquisition of the zero weight reference and processes the reports.
-
TLX DS 57 PL7 xxE
365
Calibration
Step Action Result
6 Enter the calibration weight value in the "Standard
Load" field (this value is equal to the maximum weight) and click on the Standard Load button.
If the command is disabled, an error message indicates the type of problem encountered.
This phase requires around 20 seconds.
The module checks the standard load weight against the maximum weight.
The status of the indicator %IWxy.0.4:X6
Calibration_in_progress changes.
The module acquires the standard load weight reference, processes and positions the report.
7 Click the Save button to recognize the parameters resulting from calibration.
The module and the processor recognize and save the parameters resulting from calibration.
During the write phase, the measurement remains in channel fault. This fault disappears as soon as writing is finished (current channels faults and calibration in progress disappear). The measurement is valid.
366
TLX DS 57 PL7 xxE
Calibration
Calibrating the Analog Measurement System by Program
General
Procedure
Several language elements are used to implement and supervise the calibration mechanism.
The calibration screen facilitates the procedure, but it can also be performed by program using reserved data.
Program the following operations to perform a calibration by program.
Step Action
1 Zero weight Enter WRITE_CMD while positioning the calibration order of the channel using the zero weight
(%MWxy.0.3:X1=1).
Result
The status of the indicator
%IWxy.0.4:X6 Calibration in progress changes.
This operation enables you to determine the Offset parameter.
2 Standard
Load
3
Load the standard load weight value in the %MDxy.0.4 word
-
Enter WRITE_CMD while positioning the calibration order of the channel using the standard load weight
(%MWxy.0.3:X2=1, or
%MWxy.0.3:X12=1 for a graded calibration).
4 Save the parameters in the module
Enter WRITE_CMD while positioning the save order of the calibration in the module (%MWxy.0.3:X0=1).
-
5 Copy the module parameters in the CPU
Enter WRITE_CMD while positioning the save order in the processor
(%MWxy.0.3:X11=1).
The status of the indicator
%IWxy.0.4:X6 Calibration in progress changes.
This operation enables you to determine the Gain parameter.
TLX DS 57 PL7 xxE
367
Calibration
Summary of Data
Used
The table below shows the data involved in a calibration.
Type
Command type
Role
Save calibration in the module
Zero weight
Standard load weight (Normal)
Associated data
%MWxy.0.3:X0
%MWxy.0.3:X1
%MWxy.0.3:X2
Forced calibration(CPU -> Module) %MWxy.0.3:X10
Save calibration in the processor %MWxy.0.3:X11
Standard load weight (Graded)
Value of standard load weight
%MWxy.0.3:X12
%MDxy.0.4
Command parameter
Report Calibration in progress (Normal)
Instability
Overload or underload during calibration
Non-calibrated module
Calibration mode
Forced calibration mode
%IWxy.0.4:X6
%IWxy.0.4:X9
%%MWxy.0.2:X0
%MWxy.0.2:X9
%MWxy.0.2:X14
%MWxy.0.2:X15
368
TLX DS 57 PL7 xxE
Calibration
How to Achieve Forced Calibration
At a Glance This function responds to the needs of speedy maintenance.
Forced calibration allows calibration values from a weighing module to be transferred to the central unit, and vice versa.
Note: This action cannot be reversed. Once the transfer has occurred, it is not possible to cancel the command.
Note: This function is only accessible in offline mode, with the PLC in Run.
Operating Mode
Procedure
Transferring the CPU to the weighing module is always authorized once the CPU has the requisite calibration parameters for the desired slot.
Transferring the weighing module to the central unit requires the module to be calibrated (not forced calibration).
This table describes the procedure for achieving forced calibration.
Step
1
2
3
Action
Switch the rack on.
Access the calibration screen:
1.
Select Tools
→
Configuration
2.
Click on the module's slot
3.
Select Calibration from the drop-down menu
In the Forced Calibration field, click either CPU -->Module or CPU -->Module , according to the desired transfer direction.
Note: The procedure is not enabled unless the transfer is done correctly. If there is a problem, click the Cancel button in the Forced Calibration field.
TLX DS 57 PL7 xxE
369
Calibration
Performing a Forced Calibration by Program
General
Procedure
Several language elements are used to implement and supervise the calibration mechanism.
The calibration screen facilitates the procedure, but it can also be performed by program using reserved data.
Carry out the following operations to perform a forced calibration by program.
Direction of copy
CPU ->
Module
Action
Enter WRITE_CMD while positioning the save order of the calibration in the module
(%MWxy.0.3:X10=1).
Module ->
CPU
Enter WRITE_CMD while positioning the save order in the processor (%MWxy.0.3:X11=1)
Result
This operation is used for example when replacing a module. It enables you to automatically restore the calibration parameters in the module (gain, offset and converter configuration.
This operation enables you to automatically restore the calibration parameters in the processor when, for example, you are using a module that is placed in a new slot.
This operation is only possible if the module is calibrated.
370
TLX DS 57 PL7 xxE
Debugging the weighing function
18
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter introduces the debugging screen and describes the functions available for debugging the application.
This Chapter contains the following Maps:
Topic
Description of the Debugging Screen for the Dedicated Weighing Function
Description of the module zone on the debugging screen
Description of the weighing debug screen’s display zone
Description of the Parameter Adjustment Zone
Page
371
TLX DS 57 PL7 xxE
Debugging
Description of the Debugging Screen for the Dedicated Weighing Function
At a Glance
Illustration
The debugging screen allows access to the display of weighing information and access to the adjustment of certain parameters.
This screen can be only accessed in offline mode.
1
2
TSX ISP Y101 [RACK 0 POSITION 3]
Debug Adjustment
Designation: 1I. WEIGHING 3 FILTERS
RUN ERR IO
3
4
DIAG...
Symbol:
Channel:
0
Function:
Weighing
Task:
MAST
DIAG...
Weight
No. Converter Points
Value: 100.63
Kg
NET
Outputs
0
S0
1 0
S1
1
Measurement Information
Flow: 0.0000
Zero Tracking
Threshold Check
Activate
LF Mask Time:
Direction:
Kg
Deactivate
0
Tare Value:
Zero Memory:
Flow
Calculate on s
4
Tare
Predefined
Value:
Weighing Downweighing
Cut-off points
0.00
0.0000
0.1
Kg
Kg measurements
Kg
Filtering
F1:
LF
HF
4
KG
F1
F2
Active Outputs Phase 1:
S0 S0 and S1
Low Flow (LF)
High Flow (HF)
0.0000
0.0000
Kg
Kg
F2: 0 F3:
F3
0
T
372
TLX DS 57 PL7 xxE
Debugging
Description The table below shows the different elements of the debugging screen and their functions.
3
4
Address
1
2
Element
Title bar
Function
Indicates the reference of the module selected and its physical position and the rack number.
Module zone Allows selection of screen type, access to the adjustment part of the screen, and to diagnostic functions.
Displaying this zone is optional. Choose using the View
→
Module Zone command.
Display zone Gives access to the weighing information display.
Adjustment zone
Gives access to adjustment of the module's parameters.
TLX DS 57 PL7 xxE
373
Debugging
Description of the module zone on the debugging screen
At a glance
Illustration
This zone displays general information on the state of the module or the channel.
This zone on the screen informs you about the state of the module.
Debugging Adjustments
Designation: 1I. WEIGHING 3 FILTERS
RUN ERR
Symbol:
Channel:
0
Function:
Weighing
Task:
MAST
IO DIAG...
DIAG...
Description
374
The following table describes the different elements of the module screen zone and channel state.
Address
Debugging
Adjustment
Description
Drop-down list of choices of operating modes
Check box supporting access to the adjustment functions. When this box is ticked, an extra zone is added to the debugging screen giving access to the parameters.
Indicates whether the module is closed (locked padlock) or not.
ou
RUN
ERR
I/O
DIAG
Indicator lit: normal operation
Indicator unlit: module error or switched off
Indicator lit: internal error, module broken down
Indicator blinking: communication error, absent, invalid or faulty application
Indicator unlit: no error
Indicator lit: External error: l l l l overload or underload error during calibration, range overshoot error, measurement error
Closed module: configuration refused
Indicator blinking:loss of communication with the processor
Indicator unlit: no error
This light goes red when there is a module level error. The details about the error are accessible via the DIAG button below.
TLX DS 57 PL7 xxE
Address
Channel
Function
Task
DIAG
Debugging
Description
Equal to zero, the module only has one channel, which is the 0 channel.
Weighing
Recalls the task in which the module is configured
This light goes red when there is an error linked to the weighing function. The details about the error are accessible via the DIAG button below.
TLX DS 57 PL7 xxE
375
Debugging
Description of the weighing debug screen’s display zone
illustration This zone is the dynamic display zone containing important information connected to weighing.
Weight
No. Converter Points
Value: 100.63
Kg
Measurement Information
Flow:
0.0000
Zero Tracking
Kg
NET
Tare Value:
Zero Memory:
Outputs
0
S0
1 0
S1
1
0.00
0.0000
Kg
Kg
Description
Zone Field
Weight Nb Converter
Pulses
Value
NET
The following table describes the different elements belonging to the weighing debugging screen’s display zone.
Description
By default, the screen displays the current weight value. Click on the key No. Converter
Points will allow you to switch to points mode during the next disconnection of PLC.
The display weight will be reapplied when the PLC next runs.
The current weight value in a defined unit. If there is a default on the measurement circuit detected by the module or during its calibration mode, the ERR indicator will be displayed on the screen.
The NET weight indicator is positioned if the module returns NET weight information, otherwise this relates to GROSS weight.
The "stable measurement" indicator specifies that the measurement is in the defined stability range.
The zero zone indicator is activated when the measured weight is in zero format (+/- 1/
4 of the scale indicator).
Outputs The supplied indications correspond to the physical output states S0 and S1.
Measurement Information This zone displays: l l l l the flow value, it is indicated by the unit measurement, the current tare value, the memory zero value corresponds to zero shift from the last calibration, the PT indicator specifies the tare value which has been manually introduced and not measured, l the Zero indicator shows that the function has been parameterized.
376
TLX DS 57 PL7 xxE
Debugging
Description of the Parameter Adjustment Zone
Illustration This zone allows you to modify the adjustment parameters.
Filtering
F1: 4
Threshold Check
Activate
LF Mask Time:
Direction:
Weighing
Deactivate
0
Downweighing
Active Outputs Phase 1:
S0 S0 and S1 s:
Flow
Calculate on 4
Tare
Predefined
Value:
Cut-off points
Low Flow (LF)
High Flow (HF)
0.1
measurements
0.0000
0.0000
Kg
Kg
Kg F2: 0
KG
LF
HF
F1
F2
F3
F3: 0
T
Description It gives access to the modification and display of the following parameters:
Address
Filtering (See How to
Modify Measurement
)
PD mask time
Weighing/Unweighing direction
Phase 1 active outputs
Low flow (PD) and high flow (GD) cut off points
Description
You have the possibility to modify for each phase the filter coefficient value of the measurement input.
You can choose a value from 0 to 19.
Note: The stronger the filter (value from 1 to 11), the longer the response time.
You have the possibility to modify the number of measurements for the flow calculation.
The listed choices carry the values 2, 4, 8 16, 32 and 64.
Flow (See How to Modify the Flow Calculation,
)
Tare (See How to Modify
You have the possibility to introduce a predetermined tare by checking the corresponding box and filling in this tare value in the defined unit.
Threshold check (See
How to Modify the Flow Calculation, p. 316 ): These parameters are only displayed if, during
configuration, the "Threshold check" option has been activated. Recognition of all parameters is effected from the confirmation command in the Edit menu.
Activate
Deactivate
This key activates the threshold check monitoring cycle.
This key deactivates the threshold check monitoring cycle and positions outputs S0 and
S1 into fallback mode.
Lets the user modify the mask time during switch to low flow.
Lets you modify the threshold recognition.
Lets you choose the active outputs during the first dosage phase.
Lets you modify the threshold values.
TLX DS 57 PL7 xxE
377
Debugging
378
TLX DS 57 PL7 xxE
Protecting the adjustments
19
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter describes how to protect the adjustments done during the previous phases.
This Chapter contains the following Maps:
Topic
Protection of the Adjustments to Weighing Parameters
How to protect the adjustments
Legal metrology and regulations
Page
379
TLX DS 57 PL7 xxE
Protecting the adjustments
Protection of the Adjustments to Weighing Parameters
General Any weighing instrument which can be used for commercial transactions must be approved. The parameters associated with the measurement must therefore be protected. It should not be possible to introduce into an instrument, via the interface, instructions or data likely to: l l falsify the weighing results displayed, change an adjustment factor.
Note: Protection by sealing aims to guarantee measurement conformity, so that the parameters accessible only apply to the exploitation aspects of the module information by the mechanism.
380
TLX DS 57 PL7 xxE
Protecting the adjustments
Effect of
Protecting the
Configuration
Parameters
Consequences of Protection
There are two types of information. Information, which can be protected (if a module is sealed, this type of information will be available in read only) and information with free access (Read and Write)
The table below identifies the characteristics of this information according to the protection put in place.
Functions
Task
Flow/ Calculation on n measurements
Tare/ Predefined
Threshold checking/ Active
Threshold checking/ Direction
Threshold checking/ Active outputs
Threshold Checking/ Cut-off points
Threshold checking/ LV Mask Time
Unit
Max Range (MR)
Scale Division
Overload Threshold
Filtering/ Coefficient
Data format
Stability/ Extent of Range
Stability/ Time
Zero/ Zero tracking
Zero/ Recalibration range
Without sealing
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
With sealing
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Modifiable
Non modifiable
Non modifiable
Non modifiable
Non modifiable
Modifiable
Non modifiable
Non modifiable
Non modifiable
Non modifiable
Non modifiable
The information word %IWxy.0.4:X4 (to 1) tells you if the measurement is protected. l l l
A sealed module that receives a different configuration to the one memorized
(before being switched off prior to the movement of the rider) is refused.
In this case the module is seen as missing in the PLC diagnostics, but sends a weight to the display.
A sealed module will not accept a new calibration request
Note: Using the file lets you keep a paper record for the configuration
TLX DS 57 PL7 xxE
381
Protecting the adjustments
How to protect the adjustments
Necessary conditions
Illustration
The calibration and adjustment operations must be completed.
The following illustration shows how to position the riders in order to protect the adjustments.
Display block
Backpanel connector
1
2
3
Procedure The following table describes the operation of protecting the adjustments (leading).
Step
1
2
3
4
5
Action
Take the module out of the PLC rack (the rack can remain switched on).
Remove the module’s casing (use a TORX type screwdriver for this).
Place the rider in position 2-3 as shown in the illustration.
Put the module back into its casing.
Replace the module in the rack in its previous position.
382
TLX DS 57 PL7 xxE
Protecting the adjustments
Legal metrology and regulations
EU approval The set consisting of: load holder + sensors + module can be considered as an
IPFNA (non automatic weighing instrument).
As such, and to be able to use it for commercial transitions, it has been approved by the EU.
If it is only used for internal processes, the displayt must have an identification plate mentioning:
Trademark
Type of instrument
Serial number
‘All transitions prohibited’
Max = e =
If it is used for regulated uses (e.g. commercial transitions), the display must have a identification plate, showing:
Trademark
Type of instrument
Serial Number
Max =
Min = e=
Number and date of EU approval of typeNumber 97.00.620.016.0
29th September 1997
Moreover, it must receive a first check on leaving the factory, as well as regular onsite monitoring by a licensed body. Generally, monitoring takes place once a year, and this is the responsibility of the owner.
TLX DS 57 PL7 xxE
383
Protecting the adjustments
Approval of the model
Measurement and control device for filling machine and a discontinuous counter
This IPFNA can be supplemented by the specific software applications ‘Filling
Machine’ or ‘Discontinuous counter’. As such, it has passed national approvals, as a measurement and automatic control device for filling machines and discontinuous counters.
It is therefore up to the manufacturer of the measurer or discontinuous counter to get a complete approval of any automatic weighing instruments made up in this way, in the most straightforward conditions possible.
It is also up to the manufacturer of the machine to install the identification plate and to present the machine for its first check, when necessary.
Approval of a continuous counter model
Associated with a weighing table, it is authorized as a continuous counter device.
Except for when used for commercial transitions, the identification plate shows:
-
- Serial number
‘All transitions prohibited’ dt type =
Class of appliance
When used for commercial transitions, the identification plate shows:
-
-
- Serial number
Weighed products:
- Max=
- v=
QMax mark = dt type =
L = d =
It must be checked. The first phase of the first check is done in the factory on the complete instrument uncoupled from its conveyor, by means of a movement simulator; the other phases are carried out on the complete instrument.
With average precision, the appliance covers the range from the minimum (500 scale divisions) up to 6000 scale divisions. These instruments can be authorized or unauthorized to carry out commercial transitions. If it is unauthorized, ‘PROHIBITED
FOR ALL TRANSACTIONS’ must be written on the appliance’s front panel.
384
TLX DS 57 PL7 xxE
Operating a weighing application
20
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter describes the tools that allow you to operate a weighing application.
This Chapter contains the following Maps:
Topic
Ways of displaying weighing information
Description of the display transfer
Weighing module operating modes
Page
385
TLX DS 57 PL7 xxE
Operation
Ways of displaying weighing information
Description The following table describes the different ways of displaying weighing information.
Ways
TSX XBT H100 module’s display panel (See Description of the
Description
Automatically displays the weight measurement without any prior programming.
Debugging Screen (See
Description of the weighing debug
screen’s display zone, p. 376 )
Displays all information relevant to the weighing and allows the modification of certain parameters (See
Description of the Parameter Adjustment Zone, p. 377 ).
Animation tables
Operation screen
Supervision
All information about the measurement can be accessed as PLC variables and can be displayed in the animation tables.
It is possible to create operation screens (PL7 Pro), using the weighing language objects to display necessary information on the application’s performance there.
The weighing language objects can be conveyed and operated by a supervision system.
Language
Objects
The following language objects are used for operating the weighing application.
Displayed data
Protected module
Non calibrated module
Weight value
Net weight flag
Stability flag
Zero flag
Discrete S0 output status
Discrete S1 output status
Flow
Tare value
Shift register memory
Zero follower flag
Predetermined tare flag
Object address
%MWxy.0.2:X8 (Object for user defined exchange)
%MWxy.0.2:X9 (Object for user defined exchange)
%IDxy.0.0
%IWxy.0.4:X8
%IWxy.0.4:X9
%IWxy.0.4:X10
%IWxy.0.4:X0
%IWxy.0.4:X1
%IDxy.0.2
%IDxy.0.5
%IDxy.0.7
%IWxy.0.4:X11
%IWxy.0.4:X12
386
TLX DS 57 PL7 xxE
Operation
Description of the display transfer
General
Illustration
The identifiers provided by the module to the TSX XBT H100 display panel are metrological identifiers (see the documentation on the installation of the TSX XBT
H100).
This display is done automatically, without having to be programmed.
The following illustration introduces the TSX XBT H100 display panel.
1 2 3 4 5
Note: On the TSX XBT H100, a slot is reserved on the punched rating plate to comply with the constraints specified by the legal metrology.
TLX DS 57 PL7 xxE
387
Operation
Description of the display
2
3
4
5
Address
1
Identifier
= none
Net
0
none
+
141.25
kg
All valid measurements are sent to the display panel in a fixed point physical unit every 100ms.
The following table describes the identifiers that can appear on the display panel in a normal operation.
Description
The measurement is stable.
Measurement is not stable (the stability criteria are set in configuration).
The measurement indicates a Net weight.
The measurement indicates a gross weight.
The measurement is positive
The measurement is around 0 (in the range between –1/4 and +1/4 grades).
The measurement is negative: l the associated digital value blinks: the measurement is between –9 grades and –1/
4 grades l if no associated digital value is displayed: the measurement is below –9 grades.
Digital value of the weight.
Unir of mass measurement symbol: g for gram, kg for kilogram, lb for pound, oz for ounce and t for metric tonne.
Note: Testing the serial link is done at the weighing module’s power-up. For this the TSX XBT H100 display panel module must be connected to the TSX ISP Y100 at the PLC’s power-up.
Error messages The following table describes the error identifiers that can appear on the display panel.
Identifier Description
------------The measurement is not valid, a channel error is detected.
>>>>>
<<<<<
Detection of an overload.
Detection of an underload.
Time out The display panel no longer receives the weighing module’s data.
Checksum error
A problem has been encountered at power-up. At power-up, the TSX XBT
H100 runs a test on its resources. During operation, all received information is monitored. If there is a problem, the checksum error is displayed.
388
TLX DS 57 PL7 xxE
Operation
Weighing module operating modes
Operation The following illustration describes the operation of the module.
Power-up
Self-testing
Internal error
Fail
Internal error
End self-testing
Enable
Behavior on encountering an error
During power-up, the module carries out its own self-tests (REPROM , RAM, Link display, etc.).
If an error is detected at the end of these tests, the module switches to fall back mode, the outputs are at 0.
Similarly, if, when operating normally, an internal malfunction (error in RAM, CDG, etc.) is detected in the module, the outputs are positioned to 0 and the display shows dashes on the screen (----).
Behavior on power outage
On power outage the machine parameters are saved (Tare mode, Zero offset, etc.) whereas the operating parameters are lost (Thresholds, number of measurements used to calculate flow rate, etc.).
TLX DS 57 PL7 xxE
389
Operation
390
TLX DS 57 PL7 xxE
Diagnostics of the weighing application
21
Introduction to Diagnostics
General
Display LEDs
Module or application faults can be detected using the following methods: l l l l display LEDs on the front face of the module, debugging screen, diagnostic screens accessible by the faulty bits and status words.
DIAG keys from the debugging screen,
The operation and status of the module are shown on the display block, these display LEDs are reported in a software method in the debugging screen (See
Description of the module zone on the debugging screen, p. 374):
l two display LEDs display the apply voltage and the correct operation of the module (RUN in green and ERR in red), l the I/O display LED (red) displays an external fault on the measurement channel.
The following table describes the status of the module in operation and the status of the display LEDs.
Flashing Off Display
LED
RUN
Lit
Working normally
ERR
IO
Internal error, module broken down l l l
External errors: l overload or underload error during calibration, range overshoot error, measurement error, sealed module
(configuration refused)
-
Communication error, missing, invalid or faulty application.
Absence of the measurement sensors connector.
Module faulty or switched off
No error
No error
TLX DS 57 PL7 xxE
391
Diagnostics
Diagnostics screens
The diagnostic screens are accessible using the DIAG buttons from the debugging screen. They enable you to carry out a detailed diagnostic.
When an error is detected, the red indicator lamp located on the DIAG button is lit.
The screen gives 2 DIAG buttons: l module diagnostic, detects module errors (module broken, missing, switched off etc.), l channel diagnostic (below), detects application errors (range overshoot, overload etc.).
The following illustration shows a diagnostic screen.
Module Diagnostics
Internal errors External errors Other errors
OK
Bit and word objects
392
The following bit and word objects can be used in the animation tables or at program level to detect errors.
Object
%Ixy.MOD.ERR
%Ixy.0.ERR
%IWxy.0.4:X2
Meaning when the bit is at status 1
Indicates that the module is faulty.
Indicates that the channel is faulty.
Indicator that voltage is too low. The measurement is deviating. There is a strong possibility of an error on a sensor or in the wiring.
%IWxy.0.4:X3
%IWxy.0.4:X7
%IWxy.0.4:X9
Voltage too high on module input.
Fault during command
Measurement instability. This is set when the measurement is outside the stability range during the defined time. The extent of the stability range and the time are defined during configuration.
%MWxy.MOD.2:X0 Internal error: Module Out of Order.
%MWxy.MOD.2:X1 Functional Error: communication or application error
%MWxy.MOD.2:X5 Configuration Error: the module recognized is not the one expected.
%MWxy.MOD.2:X6 Module fault, missing or switched off
%MWxy.0.2:X0 External error: Overload or underload during calibration
TLX DS 57 PL7 xxE
TLX DS 57 PL7 xxE
Diagnostics
Object
%MWxy.0.2:X1
%MWxy.0.2:X2
%MWxy.0.2:X3
%MWxy.0.2:X4
%MWxy.0.2:X5
%MWxy.0.2:X6
%MWxy.0.2:X7
%MWxy.0.2:X8
%MWxy.0.2:X9
%MWxy.0.2:X10
%MWxy.0.2:X11
Meaning when the bit is at status 1
Range overshoot fault or dynamics lower than 4.5mV at calibration.
External error: saturation of the measurement circuit
External error: sealed module, configuration refused
Internal error: module out of order
Configuration Error: the current module is not the one declared at configuration
Communication fault with the processor
Application fault
Protected module error, parameter refused: the module refuses the parameter if it influences the current value.
Non-calibrated module
Overload error
Underload error
393
Diagnostics
394
TLX DS 57 PL7 xxE
Examples of the weighing program
22
At a glance
Aim of this chapter
What's in this
Chapter?
This chapter provides programming examples for a weighing application.
This Chapter contains the following Maps:
Topic
Example of a tare mode
Dosage example
Page
TLX DS 57 PL7 xxE
395
Examples
Example of a tare mode
Description of the example
Program
This example emphasizes the running of a weighing process by focusing on the essential operations to be carried out: it deals with carrying out a switch into NET weight (tare mode).
The %M101 bit is used for this action. Its positioning causes the gross weight, which is currently measured as the weighed tare, to be acknowledged, then it causes the display to be switched to NET mode.
(* Closed weighing module, slot 6 *)
!(* waiting for tare mode conditions *)
IF %M100 THEN
IF NOT %MW6.0:X1 AND NOT %MW6.0.1:X1
THEN
SET %M101;
RESET %M100;
ELSE
RETURN;
END_IF;
END_IF
!(* Tare mode *)
IF %M101 THEN
(* send tare mode order *)
IF NOT %MW6.0:X1 AND NOT %MW6.0.1:X1 AND NOT %M102 THEN
%MW6.0.3:=0;
SET %MW6.0.3:X4;
WRITE_CMD %CH6.0;
SET %M102;
END_IF;
(* tare mode ended and OK *)
IF NOT %MW6.0:X1 AND NOT %MW6.0.1:X1 THEN
%MW6.0.3:=0;
RESET %M101;
RESET %M102;
SET %M103;
ELSE
(* tare mode refused => error *)
IF NOT %MW6.0:X1 AND %MW6.0.1:X1 THEN
SET %M200;
%MW6.0.3:=0;
RESET %M101;
RESET %M102;
RESET %MW6.0.1:X1;
SET %M100;
END_IF;
END_IF;
END_IF;
396
TLX DS 57 PL7 xxE
Summary
Examples
The following table summarizes the language objects for monitoring the exchanges.
%MW6.0:X1 Exchange in progress
%MW6.0.1:X1 Report on the exchanges
%MW6.0.3:X4 Tare mode order
%MW6.0.3
Command order (Tare mode, calibration, etc…)
TLX DS 57 PL7 xxE
397
Examples
Dosage example
Description of the example
The following example uses a weighing module in slot 2 of the PLC.
It describes a dosage application split into steps as in the diagram below.
Init
Send thresholds
Tare mode
Dosage monitoring continued
Data used in the program
The following table describes the data used in the program for the weighing module:
%IW2.0.4:X0
%IW2.0.4:X1
%IW2.0.4:X5
%CH2.0
%MD2.0.8
%MD2.0.10
%MW2.0:X1
%MW2.0:X2
%MW2.0.1:X1
%MW2.0.1:X2
%MW2.0.2:X2
%MW2.0.2:X7
%MW2.0.3
Image of the S0 output.
Image of the S1 output.
In progress flag
Data structure for sending the command
Large flow cut off point S0
Small flow cut off point S1
Exchange in progress
Send in progress
Command accepted
Command accepted
Saturation of the measurement string
Application fault
Command order
398
TLX DS 57 PL7 xxE
Program
TLX DS 57 PL7 xxE
The program is processed in structured text:
Main Program
(* ///////// Sending thresholds ///////////*)
%L100:
IF NOT %M99 THEN
JUMP %L120;
END_IF;
(*Loading and sending the thresholds *)
IF RE %M99 THEN
%MD2.0.8:=%MD230;(* S0 Large Flow cut off point*)
%MD2.0.10:=%MD232; (* S1 Small Flow cut off point *)
WRITE_PARAM %CH2.0;JUMP %L120;
END_IF;
(*Send in progress*)
IF %MW2.0:X2 THEN
JUMP %L120;
END_IF;
(*command accepted*)
IF NOT %MW2.0.1:X2 THEN
RESET %M99;
END_IF;
(*END INIT CYCLE*)
%L120:
(* //////// TARE MODE PHASE (%MW100 =4) //////////// *)
%L260:
IF %MW100<>4 THEN
JUMP %L300;
END_IF;
(*Tare mode request *)
IF %M72 THEN
RESET %M72;
%MW270:2:=4;
END_IF;
(*Management of commands *)
SR8; (* %MW270 informs the command type of tare mode 4 *)
(*Waiting for tare mode resonse*)
IF %MW270=-1 AND %MW271=-1 THEN
%MW100:=5;
SET %M72;
JUMP %L800;
END_IF;
Examples
399
Examples
400
Program (continued)
(* //////// DOSAGE PHASE (%MW100 =5) //////////// *)
%L300:
IF %MW100<>5 THEN
JUMP %L340;
END_IF;
(*Confirmation of the thresholds*)
IF %M72 THEN
RESET %M72;
%MW270:2:=8;
END_IF;
(*Management of commands *)
SR8;(* %MW270 = command type of thresholds confirmation 8 *)
(*Waiting for tare mode response*)
IF %MW270>=0 OR %MW271>=0 THEN
JUMP %L800;
END_IF;
(*Monitor outputs to continue*)
IF NOT %IW2.0.4:X0 AND NOT %IW2.0.4:X1 THEN
%MW100:=6;
SET %M72;
JUMP %L800;
END_IF;
(*PHASE 6 continued *)
%L340:
IF %MW100<>6 THEN
JUMP %L380;
END_IF;
%L800:
SUBROUTINE SR8: out *)
(* Send request for the module*)
IF %MW270>=0 THEN (* %MW270 informs of the order to be carried
%M0:16:=0;
SET %M0[%MW270];
%MW2.0.3:=%M0:16;
%MW271:=%MW270;
%MW270:=-1;
WRITE_CMD %CH2.0;
RET;
END_IF;
(*Command in progress ?*)
IF %MW2.0:X1 OR %IW2.0.4:X5 THEN
RET;
END_IF;
END_IF;
(*command accepted ?*)
IF NOT %MW2.0.1:X1 AND NOT %MW2.0.2:X7 THEN
%MW270:2:=-1;
ELSE
%MW270:=%MW271;
TLX DS 57 PL7 xxE
Glossary
C
Calibration
CCX17
Closed loop adjustment
Comparison
Configuration
CPU
Grading a measuring appliance.
Schneider Automation operator dialogue desk family.
PID research method which consists of using a proportional command to start the procedure until it starts to oscillate
Function, which allows you to cancel the static error of a PID without, integral action
The configuration gathers together the data which characterize the machine
(invariable) and which are necessary for the operation of the module. All this information is stored in the PLC %KW constants zone. The PLC application can not modify them.
Central Processing Unit: generic name for Schneider Automation processors.
D
Debugging Debugging is a PL7 service which supports direct control of the module in connected mode.
Derivative action Third parameter of a PID which allows you to anticipate what will happen by accelerating or slowing down a process response.
TLX DS 57 PL7 xxE
401
Glossary
Device for setting to zero
Discrete
Device supporting "readjustment" of the flag if the zero has drifted (because of an overwrite, for example). This operation can only be done within the zero’s print range
(+/-2% or +/-5% of the maximum range according to the type of weighing instrument).
Discrete inputs/outputs.
E
Explicit exchanges
Exchanges between the CPU and the task modules, initiated by the PL7 program for updating module-specific data.
F
FIPIO Field bus used to connect sensor or actuator type devices.
Flag device (for a weighing instrument)
The part of the device that measures the load where the direct reading of the result is obtained (TSX XBT H100).
G
Grade
Gross weight
A value shown as a unit of mass for the difference between two consecutive identifiers for a numerical identifier.
Indication of the load’s weight on an instrument, when no tare or tare predetermination device has been implemented.
I/O
I
Inputs/Outputs
402
TLX DS 57 PL7 xxE
Integral action Second parameter of a PID which supports the deletion of a static error.
Glossary
L
Leading Encasing an appliance in lead. Putting a rider in the weighing module makes this function possible.
This device guarantees measurement conformity. The accessible parameters only concern the operating aspects of the module’s information via the process control
(the parameters able to modify the measurement conformity: unit, range, grade… are therefore accessible in read-only).
The part of the instrument for holding the load.
Load holder device
Load limit (Lim) The maximum static load that the instrument can support without permanently altering its metrological qualities.
M
Maximum range
(Max)
Metrology
Minimum range
(Min)
Momentum
Maximum weighing capacity, not including the tare’s additional capacity.
The science of weight and measurements.
The load value below which the weighing results can be affected by a very important error.
Inputs/outputs modules using several open standard communication networks.
N
Net weight (N) Indication of a load’s weight on an instrument after implementing a tare device.
Net weight = Gross weight – Tare weight
TLX DS 57 PL7 xxE
403
Glossary
Non-automatic weighing instruments
Weighing instruments that need to be manned during weighing, for example when placing or removing loads from the load holder device, as well as for getting the result. These instruments support direct observation of the result of the weighing, either by displaying it or printing it.The two possibilities are covered by the
" identifier " word.
O
Open loop adjustment
Operating mode
PID research method which consists of applying a level to the output and make the response the same as an integrator with pure delay time
It is the group of rules which govern the behavior of the module during the transitional phases or upon the appearance of a fault.
P
PID
PID in tandem
PL7
Proportional action
Regulation algorithm made up of a P roportional action, an I ntegral action and a
D erivative action.
Adjustment technique which consists of linking 2 PID in a chain and instructing the second via commands from the first.
Programming software of the Schneider Automation PLCs.
First parameter of a PID which allows you to match the processor’s response speed.
R
Regulation loop Group containing the acquisition of analog measurements, the execution of a PID and the sending of analog commands
404
TLX DS 57 PL7 xxE
Glossary
T
Tare The load placed on the load holder along with the product to be weighed. For example: packaging or a product’s container.
Tare device
Tare mode
Tare predetermining device
Device that allows you to lead the instrument’s identifier to zero when a load is placed on the load holder: l without encroaching on the weighing print range of the net loads (tare additive device), l or reducing the weighing print range of the net loads (tare subtractive device, with the ISP Y100).
An action that allows you to lead the instrument’s identifier to zero when a load is placed on the load holder.
Device supporting subtraction of a predetermined tare value from a gross weight value, which shows the result of this calculation. As a result, the weighing print range is reduced.
TBX Remote analog input/output modules on the FIPIO bus.
TSX/PMX/PCX57 Family of Schneider Automation hardware products.
V
Value of the predetermined tare (PT)
A numerical value, representing a weight, which is entered into the instrument, by input during configuration or setting, or by program.
Value of the tare
(T)
The value of a load’s weight, determined by a tare weighing device.
W
Weighing instruments
TLX DS 57 PL7 xxE
Measuring instruments that determine a body’s mass by using the action of gravity.
405
Glossary
Weighing print range
These instruments can also be used to determine other sizes, quantities, parameters or characteristics to do with the mass. According to their operating nature, the weighing instruments are classed as automatic operation or nonautomatic operation.
The gap between the minimum and maximum range.
Z
Zero follower
Zero Load
A device allowing you to capture any of the zero’s slow drifts, within the limits of the zero format’s print range.
Empty load holder equipped with its mechanical accessories (vibrating extractor, screws, hatch, jack,…). It does not appear in the weight indication, but it must be taken into account for the maximum sensor load calculation.
406
TLX DS 57 PL7 xxE
Index
Symbols
Numerics
A
Accessing the configuration editor
Addressing
addressing
Associated task
TLX DS 57 PL7 43F
A C
B
Bit language objects
C
calibration
channel status word
Channel zone
Cold junction compensation, 194
configuration
Configuration function
D
Data format
407
Index
Default parameters
analog, 173, 176, 177, 179, 180, 181
Display
E
explicit exchange
F
Fallback mode
Fallback to 0
FAST
Filter
Filter alpha coefficient
Filter value
filtering
Filtering value
flow
forced calibration
G
408
H
I
implicit exchanges
L
language word objects
Leading
M
Maintain the value
MAST
Measurement stability
Module status word
Module zone
Monitoring under/overshoots
O
Objects
TLX DS 57 PL7 43F
Operating mode
Operating modes of the dialog operator, 269
Output behavior
P
Presence of terminal block, 191
Presymbolization
Programming
protection
R
READ_PARAM
Regulation functions, 233, 239
RESTORE_PARAM
S
SAVE_PARAM
Scale
Scanning cycle
TLX DS 57 PL7 43F
Setting to zero
Sortie
T
Task
threshold
Timing of AEY1614 measurements, 46
Index
U
User defined exchanges
W
weighing
WRITE_CMD
WRITE_PARAM
409
Index
Z
Zero
Zero follower
410