Schneider Electric Twido Hardware User Guide
Annonce
Annonce
Twido Programmable Controllers
35011387 06/2011
Twido Programmable
Controllers
Modular and Compact Bases
Hardware Guide
06/2011 www.schneider-electric.com
2
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of
Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2011 Schneider Electric. All rights reserved.
35011387 06/2011
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Part I Twido Hardware Guide - Compact & Modular Bases
7
9
Chapter 1 Twido Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About Twido . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum Hardware Configuration for Compact Bases . . . . . . . . . . . . . .
13
Maximum Hardware Configuration for Modular Bases . . . . . . . . . . . . . . .
Main Features of the Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communications Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Installation Overall Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compact and Modular Bases Mounting Positions. . . . . . . . . . . . . . . . . . .
Assembling an Expansion I/O Module to a Base . . . . . . . . . . . . . . . . . . .
Disassembling an Expansion I/O Module from a Base . . . . . . . . . . . . . . .
Minimum Clearances for Bases and Expansion I/O Modules in a Control
Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Compact Bases Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions of the Compact Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Direct Mount a Compact Base on a Panel Surface. . . . . . . . . . . .
How to Install and Remove a Compact Base from a DIN Rail . . . . . . . . .
How to Install the Operator Display Module . . . . . . . . . . . . . . . . . . . . . . .
How to Install a Serial Interface Adapter to a Compact Base . . . . . . . . . .
How to Install a Memory or RTC Cartridge in a Compact base . . . . . . . .
How to Connect the Power Supply to Compact Bases . . . . . . . . . . . . . . .
How to Install and Replace an External Battery . . . . . . . . . . . . . . . . . . . .
2.3 Modular Bases Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions for the Modular Controllers . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Direct Mount a Modular Base on a Panel Surface . . . . . . . . . . . .
How to Install and Remove a Modular Base from a DIN Rail . . . . . . . . . .
How to Install the Operator Display Expansion Module . . . . . . . . . . . . . .
How to Install a Serial Interface Adapter to Modular Bases . . . . . . . . . . .
33
35011387 06/2011
3
4
How to Install a Second Serial Interface Expansion Module to a Modular
Base. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing a Terminal Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to Install a Memory or RTC Cartridge in a Modular Base . . . . . . . .
How to Connect the Power Supply to Modular Bases . . . . . . . . . . . . . . .
Chapter 3 Description of Compact Bases. . . . . . . . . . . . . . . . . . . . .
3.1 Compact Bases Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview of Compact Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Description of a Compact Base . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Specifications for Compact Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications for the Compact Bases . . . . . . . . . . . . . . . . . . . .
Electrical Specifications for the Compact Bases . . . . . . . . . . . . . . . . . . .
Input Specifications for the Compact Base . . . . . . . . . . . . . . . . . . . . . . .
Relay Output Specifications for the Compact Base . . . . . . . . . . . . . . . . .
Output Transistor Specifications for the Compact Base . . . . . . . . . . . . .
Description of Analog Potentiometers . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional Specifications for the Compact Bases . . . . . . . . . . . . . . . . . .
3.3 Wiring Rules and Recommendations, and Wiring Schematics for
Compact Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Rules and Recommendations for Compact Bases. . . . . . . . . . . .
Compact Base Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Compact Bases Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock (RTC) Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Display Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input Simulators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 4 Description of Modular Bases . . . . . . . . . . . . . . . . . . . . .
4.1 Modular Bases Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview of Modular Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts Description of a Modular Base . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Modular Bases Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Specifications for the Modular Bases. . . . . . . . . . . . . . . . . . . . .
Electrical Specifications for the Modular Bases. . . . . . . . . . . . . . . . . . . .
Input Specifications for the Modular Bases . . . . . . . . . . . . . . . . . . . . . . .
Relay Output Specifications for the Modular Bases. . . . . . . . . . . . . . . . .
Transistor Output Specifications for the Modular bases . . . . . . . . . . . . .
Description of Analog Potentiometers . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview of Analog Voltage Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional Specifications for the Modular Bases. . . . . . . . . . . . . . . . . . .
4.3 Modular Bases Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Rules and Recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modular Base Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
119
79
35011387 06/2011
4.4 Modular Bases Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real Time Clock (RTC) Cartridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Display Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5 Telefast® Pre-Wired Systems for Twido. . . . . . . . . . . . .
Overview of the Telefast
®
Pre-Wired System for Twido . . . . . . . . . . . . . .
Dimensions of the Telefast
®
Bases. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications for the Telefast
®
Bases . . . . . . . . . . . . . . . . . . . . . . . . . . .
Telefast
®
Bases Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Specifications for the TeleFast Cables. . . . . . . . . . . . . . . . . . . . . .
Chapter 6 Controller Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Dedicated I/Os. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RUN/STOP Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Status Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Latching input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fast Counting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Very Fast Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pulse (PLS) Generator Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pulse Width Modulation (PWM) Output. . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Controller Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cyclic Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Periodic Scan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking Scan Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dealing with Power Outages and Restoration. . . . . . . . . . . . . . . . . . . . . .
Dealing with a Warm Restart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dealing with a Cold Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialization of Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 7 Operator Display Operation. . . . . . . . . . . . . . . . . . . . . . .
Operator Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Identification and State Information . . . . . . . . . . . . . . . . . . . . .
System Objects and Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Serial Port Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
157
Time of Day Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Real-Time Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A System Diagnostic using the Front Panel LED’s. . . . . .
221
System Diagnostic Using the Front Panel LEDs . . . . . . . . . . . . . . . . . . . .
Appendix B Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking I/O Connections on the Base Controller . . . . . . . . . . . . . . . . . .
Appendix C The DIN Rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
225
227
175
203
35011387 06/2011
5
Appendix D IEC Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
229
Glossary of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix E Agency Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
231
Agency Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 35011387 06/2011
Safety Information
§
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
7
35011387 06/2011
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
8 35011387 06/2011
About the Book
At a Glance
Document Scope
This is the Hardware Guide for Twido programmable controllers for compact modular bases.
Validity Note
The information in this manual is applicable only for Twido programmable controllers. This documentation is valid for TwidoSuite Version 2.3.
User Comments
We welcome your comments about this document. You can reach us by e-mail at [email protected].
35011387 06/2011
9
10 35011387 06/2011
Twido Programmable Controllers
Compact & Modular Base
35011387 06/2011
Twido Hardware Guide - Compact
& Modular Bases
I
Introduction
This part of the guide provides parts descriptions, specifications, wiring schematics, installation, set up, and troubleshooting information about all Twido compact & modular bases.
What’s in this Part?
This part contains the following chapters:
6
7
4
5
Chapter
1
2
3
Chapter Name
Twido Overview
Installation
Description of Compact Bases
Description of Modular Bases
Telefast® Pre-Wired Systems for Twido
Controller Operation
Operator Display Operation
Page
11
35011387 06/2011
Compact & Modular Base
12 35011387 06/2011
Twido Programmable Controllers
Twido Overview
35011387 06/2011
Twido Overview
1
Introduction
This chapter provides an overview of the Twido products, the maximum configurations, the main functions of the bases, and an overview of the communication system.
What’s in this Chapter?
This chapter contains the following topics:
Topic
About Twido
Maximum Hardware Configuration for Compact Bases
Maximum Hardware Configuration for Modular Bases
Main Features of the Controllers
Communications Overview
Page
35011387 06/2011
13
Twido Overview
About Twido
Introduction z z
The Twido controller is available in the two following models:
Compact Bases
Modular Bases
Compact bases are available with 10, 16, 24 or 40 I/Os.
Modular bases are available with either 20 or 40 I/Os.
Additional I/O can be added to the bases using expansion I/O modules. They are: z z
15 expansion modules for discrete I/O or relay type
10 expansion modules for the analog I/O type
There are also several options that can be added to the bases as in the table from the Base Options
paragraph below.
z z z
In addition to these options, other options listed below can be added:
Programming cables
Discrete I/O cables
Telefast pre-wired systems with I/O interfaces
Connection to Communication Modules
Connecting to an AS-Interface bus interface module also permits you to manage up to 62 slave devices. Use the following module: z
AS-Interface V2 bus interface master module: TWDNOI10M3.
The 24 I/O and 40 I/O compact bases and all modular bases can connect to a
CANopen fieldbus interface module. The CANopen master module permits you to manage up to 16 CANopen slave devices (not to exceed 16 Transmit-PDOs (TPDO) and 16 Receive-PDOs (RPDO)). Use the following module: z
CANopen fieldbus interface master module: TWDNCO1M.
Advanced Features for TWDLC••40DRF Compact Bases
Advanced integrated features are provided on the TWDLC••40DRF series compact bases: z z z z
Built-in 100Base-TX Ethernet network port: TWDLCAE40DRF and
TWDLCDE40DRF only
Onboard Real-Time Clock (RTC): TWDLC••40DRF
A fourth Fast Counter (FC):TWDLC••40DRF
External battery support:TWDLC••40DRF
14 35011387 06/2011
Twido Overview
Base Models
Base Name
Compact 10 I/O
Compact 10 I/O
Compact 16 I/O
Compact 16 I/O
Compact 24 I/O
Compact 24 I/O
Compact 40 I/O
Compact 40 I/O
Compact 40 I/O
Compact 40 I/O
Modular 20 I/O
Modular 20 I/O
Modular 20 I/O
The following table lists the bases:
Reference
TWDLCAA10DRF
TWDLCDA10DRF
TWDLCAA16DRF
TWDLCDA16DRF
TWDLCAA24DRF
TWDLCDA24DRF
TWDLCAA40DRF
14
10
24
16
9
7
14
10
9
7
6
4
6
4
Channels Channel type
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
TWDLCAE40DRF 24
16
Inputs
Outputs
TWDLCDA40DRF
TWDLCDE40DRF
TWDLMDA20DUK
TWDLMDA20DTK
TWDLMDA20DRT
12
8
12
8
12
6
2
24
16
24
16
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Inputs
Outputs
Outputs
Input/Output type Power supply
100/240 VAC 24 VDC
Relay
24 VDC
Relay
24 VDC
Relay
24 VDC
Relay
24 VDC
Relay
24 VDC
Relay
24 VDC
Relay X 14
Transistors X 2
24 VDC
Relay X 14
Transistors X 2
Ethernet port
24 VDC
Relay X 14
Transistors X 2
24 VDC
Relay X 14
Transistors X 2
Ethernet port
24 VDC
Transistor sink
24 VDC
Transistor source
24 VDC
Relay
Transistor source
24 VDC
100/240 VAC
24 VDC
100/240 VAC
24 VDC
100/240 VAC
100/240 VAC
24 VDC
24 VDC
24 VDC
24 VDC
24 VDC
35011387 06/2011
15
Twido Overview
Base Name
Modular 40 I/O
Modular 40 I/O
Reference
TWDLMDA40DUK
TWDLMDA40DTK
Channels Channel type
24
16
Inputs
Outputs
24
16
Inputs
Outputs
Input/Output type Power supply
24 VDC
Transistor sink
24 VDC
Transistor source
24 VDC
24 VDC
Base Options
The following table lists the options:
Option name
Operator display module (Compact bases only)
Operator display expansion module (Modular bases only)
Real Time Clock (RTC) cartridge
32 Kb EEPROM memory cartridge
64 Kb EEPROM memory cartridge
Communication adapter, RS485, miniDIN
Communication adapter, RS232, miniDIN
Communication adapter, RS485, terminal
Communication expansion module, RS485, miniDIN (Modular bases only)
Communication expansion module, RS232, miniDIN (Modular bases only
Communication expansion module, RS485, terminal (Modular bases only)
ConneXium TwidoPort Ethernet interface module (except for
TWDLCAE40DRF and TWDLCDE40DRF with on-board Ethernet interface)
6-point input simulator (Compact bases only)
9-point input simulator (Compact bases only)
14-point input simulator (Compact bases only)
External backup battery (TWDLCA•40DRF only)
5 mounting strips
2 terminal blocks (10 positions)
2 terminal blocks (11 positions)
2 terminal blocks (13 positions)
2 terminal blocks (16 positions)
2 connectors (20 pins)
2 connectors (26 pins)
Reference
TWDXCPODC
TWDXCPODM
TWDXCPRTC
TWDXCPMFK32
TWDXCPMFK64
TWDNAC485D
TWDNAC232D
TWDNAC485T
TWDNOZ485D
TWDNOZ232D
TWDNOZ485T
499TWD01100
TWDXSM6
TWDXSM9
TWDXSM14
TSXPLP01 (single battery order)
TSXPLP101 (10 pack order)
TWDDXMT5
TWDFTB2T10
TWDFTB2T11
TWDFTB2T13
TWDFTB2T16T
TWDFCN2K20
TWDFCN2K26
16 35011387 06/2011
Cables
The following table lists the cables:
Cable name
Programming cables
PC to controller programming cable: Serial
PC to controller programming cable: USB
Mini-DIN to free wire communication cable
Twido Overview
Reference
TSX PCX1031
TSX CUSB485, TSX CRJMD25 and
TSX PCX3030
TSX CX100
35011387 06/2011
17
Twido Overview
Maximum Hardware Configuration for Compact Bases
Introduction
This section provides the maximum hardware configurations for a compact base.
Maximum Hardware Configurations
The following tables list the maximum number of configuration items for each type of compact base:
Base specifics:
Base Item
TWD...
Serial ports
Ethernet port
1
0
Compact base
LCAA10DRF
LCDA10DRF
2
0
LCAA16DRF
LCDA16DRF
2
0
LCAA24DRF
LCDA24DRF
LCAA40DRF
LCAE40DRF
LCDA40DRF
LCDE40DRF
2
1 (TWDLCAE40DRF and TWDLCDE40DRF only)
1
64
Cartridge slots
Largest application/backup size (KB)
Optional memory cartridge
(KB)
Optional RTC cartridge
Optional Operator Display
Optional 2nd serial port
Optional Ethernet interface module
1
8
32 1
1
16
32 1
1
32
32 1 32 or 64 2 yes 1 yes no yes yes 1 yes yes yes yes 1 yes yes yes
RTC onboard 3 yes yes yes (TWDLCAA40DRF and
TWDLCDA40DRF) no (TWDLCAE40DRF and
TWDLCDE40DRF)
NOTE:
1.
A Compact base can have either a memory cartridge or an RTC cartridge.
2.
Memory cartridge only, for RTC is already onboard.
3.
All TWDLC••40DRF compact bases have a built-in RTC. Therefore, only a memory cartridge can be added to those controllers.
18 35011387 06/2011
Twido Overview
Base Item
TWD...
Discrete I/O expansions:
Standard discrete inputs
Standard discrete outputs
Built-in analog inputs
Max analog I/O (controller I/O + exp I/O)
6
4
Compact base
LCAA10DRF
LCDA10DRF
Max expansion I/O modules
(Discrete or analog)
Max discrete inputs
(controller I/O + exp I/O)
Max discrete outputs
(controller I/O + exp I/O)
Max digital I/O
(controller I/O + exp I/O)
Max relay outputs
Potentiometers
Base Item
TWD...
0
6
4
10
0
9
7
16
4
14+(4x32)=142
10+(4x32)=138
24+(4x32)=152
4 base only 7 base only
1
Analog I/O expansions:
1
Compact base
LCAA10DRF
LCDA10DRF
LCAA16DRF
LCDA16DRF
10 base + 32 expansion
2
LCAA24DRF
LCDA24DRF
0
0 in or 0 out
9
7
LCAA16DRF
LCDA16DRF
0
0 in or 0 out
LCAA24DRF
LCDA24DRF
14
10
0
32 in or 8 out
LCAA40DRF
LCAE40DRF
LCDA40DRF
LCDE40DRF
24
16 (14 Relay + 2
Transistor outputs)
7
24+(7x32)=248
16+(7x32)=240
40+(7x32)=264
14 base + 96 expansion
2
LCAA40DRF
LCAE40DRF
LCDA40DRF
LCDE40DRF
0
56 in / 14 out
35011387 06/2011
19
Twido Overview
Base Item
TWD...
Communication modules:
Compact base
LCAA10DRF
LCDA10DRF
LCAA16DRF
LCDA16DRF
Max AS-Interface bus interface modules
Max I/O with AS-Interface modules
(7 I/O per slave)
Max CANopen fieldbus interface modules
Max T/R-PDOs with CANopen devices
Remote controllers
0
10
0
0
7
0
0
0
16
7
LCAA24DRF
LCDA24DRF
LCAA40DRF
LCAE40DRF
LCDA40DRF
LCDE40DRF
2 2
24+(2x62x7)=892 40+(2x62x7)=908
1
16 TPDOs
16 RPDOs
7
1
16 TPDOs
16 RPDOs
7
20 35011387 06/2011
Twido Overview
Maximum Hardware Configuration for Modular Bases
Introduction
This section provides the maximum hardware configurations for a modular base.
Maximum Hardware Configurations
The following tables list the maximum number of configuration items for each type of modular base:
Base specifics:
Base Item
TWD...
Serial ports
Cartridge slots
Largest application/backup size (KB)
Optional memory cartridge (KB)
Optional RTC cartridge
Optional Operator Display
Optional Ethernet interface module
Modular base
LMDA20DUK
LMDA20DTK
2
2
32
32 yes yes 1 yes
LMDA20DRT
2
2
64
32 or 64 yes yes 1 yes
2
2
LMDA40DUK
LMDA40DTK
64
32 or 64 yes yes 1 yes
NOTE:
1.
A modular base can have either an Operator Display expansion module (with an optional communication adapter) or a communication expansion module.
Discrete I/O expansions:
Base Item
TWD...
Standard discrete inputs
Standard discrete outputs
Max expansion I/O modules (Discrete or analog)
Modular base
LMDA20DUK
LMDA20DTK
12
8
4
Max discrete inputs (controller I/O + exp I/O) 12+(4x32)=140
Max discrete outputs (controller I/O + exp I/O) 8+(4x32)=136
Max digital I/O
(controller I/O + exp I/O)
20+(4x32)=148
LMDA20DRT
12
8
7
12+(7x32)=236
8+(7x32)=232
20+(7x32)=244
LMDA40DUK
LMDA40DTK
24
16
7
24+(7x32)=248
16+(7x32)=240
40+(7x32)=264
35011387 06/2011
21
Twido Overview
Base Item
TWD...
Max relay outputs
Potentiometers
Modular base
LMDA20DUK
LMDA20DTK
LMDA20DRT
64 expansion only 6 base + 96 expansion
1 1
Analog I/O expansions:
LMDA40DUK
LMDA40DTK
96 expansion only
1
Base Item
TWD...
Built-in analog inputs
Max analog I/O (controller I/O + exp I/O)
Modular base
LMDA20DUK
LMDA20DTK
1
33 in or 17 in and
8 out
LMDA20DRT
1
57 in or 29 in and
14 out
LMDA40DUK
LMDA40DTK
1
57 in or 29 in and 14 out
Communication modules:
Base Item
TWD...
Max AS-Interface bus interface modules
Max I/O with AS-Interface modules (7 I/O per slave)
Max CANopen fieldbus interface modules
Max T/R-PDOs with CANopen devices
Remote controllers
Modular base
LMDA20DUK
LMDA20DTK
LMDA20DRT LMDA40DUK
LMDA40DTK
2 2 2
20+(2x62x7)=888 20+(2x62x7)=888 40+(2x62x7)=908
1
16 TPDOs
16 RPDOs
7
1
16 TPDOs
16 RPDOs
7
1
16 TPDOs
16 RPDOs
7
22 35011387 06/2011
Twido Overview
Main Features of the Controllers
Introduction
By default all I/Os on the bases are configured as discrete I/Os. However, certain dedicated I/Os
can be assigned to specific tasks during configuration such as: z
RUN/STOP input z z z
Latching inputs
Fast counters: z
Single up/down counters: 5 kHz (1-phase) z
Very fast counters: Up/down counters - 20 kHz (2-phase)
Controller status output
Pulse Width Modulation (PWM) z z
Pulse (PLS) generator output
Twido controllers are programmed using TwidoSuite which also enables the PID and PID Auto-Tuning functions to be used on certain controllers:
Main Features
Feature
Scanning
Execution time
Memory capacity
RAM backup
35011387 06/2011
The following table lists the main features of the bases:
Description
Normal (cyclical) or periodic (constant) (2 to 150 ms)
0.14 μ s to 0.9 μ s for a list instruction
Data:
3000 memory words for all bases
128 memory bits for TWDLCAA10DRF and TWDLCAA16DRF
256 memory bits for all other bases.
Program:
10 I/O compact base: 700 list instructions
16 I/O compact base: 2000 list instructions
24 I/O compact, and 20 I/O modular bases: 3000 list instructions
20 I/O modular and 40 I/O modular bases, and 40 I/O compact bases: 6000 list instructions
(with a 64 Kb cartridge, otherwise 3000 list instructions)
All bases: By lithium internal battery. Backup duration is approximately 30 days (typically) at
25 ° C (77 ° F) after battery is fully charged. It take 15 hours to obtain 0 to 90% of the full battery charge. Battery life is 10 years when charged for 9 hours and discharged for 15 hours. The battery cannot be replaced.
40DRF compact bases: By user-replaceable lithium external battery (in addition to internal battery onboard). Backup duration is approximately 3 years (typically) at 25 ° C (77 ° F) under normal operating conditions of the base (typically, no long-term powering off of the base). BAT
LED on front-panel provides indication of battery-power status.
23
Twido Overview
Feature Description
Programming port All bases: EIA RS485
TWDLC•E40DRF compact bases: Built-in RJ45 Ethernet communications port
Expansion I/O modules
AS-Interface V2 bus interface modules
CANopen fieldbus interface modules
10 and 16 I/O compact bases: no expansion modules
24 I/O compact and 20 I/O modular bases: up to 4 expansion I/O modules
40 I/O modular and 40 I/O compact bases: up to 7 expansion I/O modules
10 and 16 I/O compact bases: no AS-Interface bus interface module
24 I/O and 40 I/O compact, 20 I/O and 40 I/O modular bases: up to 2 AS-Interface bus interface modules
10 and 16 I/O compact bases: no CANopen fieldbus interface module
24 I/O and 40 I/O compact, 20 I/O and 40 I/O modular bases: 1 CANopen fieldbus interface module
Remote link communication
Modbus communication
Ethernet communication
Maximum 7 slaves by remote I/O or peer bases.
Maximum length of entire network: 200 m (650 feet).
Non-isolated EIA RS485 type, maximum length limited to 200 m.
ASCII or RTU mode.
TWDLCAE40DRF, TWDLCDE40DRF compact bases and 499TWD01100 Ethernet interface module: 100Base-TX auto-negotiated type Ethernet communications over TCP/IP protocol, via built-in RJ45 port.
Half-duplex protocol to a device.
ASCII communication
Dedicated function blocks
Fast counters TWDLCA•40DRF and TWDLCD•40DRF Compact bases: 4
All other compact bases: 3
All modular bases: 2
Analog potentiometers
Built-in analog channel
Programmable input filter
Very fast counters TWDLCA•40DRF and TWDLCD•40DRF compact bases: 2
All other compact bases: 1
All modular bases: 2
All modular and 40 I/O compact bases: 2 PWM/PLS
24 I/O and 40 I/O compact bases: 2
All other bases: 1
Compact bases: none
Modular bases: 1 input
Input filter time can be changed during configuration
No filtering or filtering at 3 ms or 12 ms
I/O points are configured in groups
24 35011387 06/2011
Feature
Special I/O
Description
Inputs
Outputs
Twido Overview
RUN/STOP: Any one of the base inputs
Latching: up to 4 inputs (%I0.2 to %I0.5)
0-10 V built-in analog input connected to %IW0.0.0
Fast counters: 5 kHz maximum
Very fast counters: 20 kHz maximum
Frequency meter: 1 kHz to 20 kHz maximum
Controller status output: 1 of 3 outputs (%Q0.1 to %Q0.3)
PWM: 7 kHz maximum
PLS: 7 kHz maximum
35011387 06/2011
25
Twido Overview
Communications Overview
Introduction
Twido bases have one, or an optional second, serial port that is used for real-time or system management services.
Four types of communication can be used with Twido controllers: z
AS-Interface bus connection z z
CANopen fieldbus connection
Ethernet network connection z
Modem connection
The real-time services provide data distribution functions for exchanging data with
I/O devices and messaging functions for communicating to external devices.
System management services manage and configure the base through TwidoSuite.
Either serial port is used for any of these services but only serial port 1 is for communicating with TwidoSuite.
To provide these services, there are three protocols available on each base: z
Remote Link z z
Modbus
ASCII
In addition, the TWDLCAE40DRF and TWDLCDE40DRF compact bases feature a built-in RJ45 Ethernet communications port allowing to perform all real-time communications and system management tasks via the network. Ethernet communications implements the following protocol: z
Modbus TCP/IP
26 35011387 06/2011
Twido Overview
Communications Architecture with Protocols
The following diagram shows the communication architecture with all three protocols.
NOTE: Communication between the "Modbus" and "Remote Link" protocols cannot occur at the same time.
AS-Interface Connection
The AS-Interface (abbreviation for Actuator-Sensor-Interface) bus is a field bus
(level 0), and can be used to connect sensors/actuators. This allows "discrete" or analog type information to run between a bus "master" and sensor/actuator type
"slave" devices.
AS-Interface is made up of three major basic elements: z z z a specific supply providing a 30 VDC voltage, a bus master, one or more slave devices (sensors, actuators and others).
These components are interconnected by a two-wire cable dedicated to data transmission and power supply.
35011387 06/2011
27
Twido Overview
AS-Interface Connection Illustration
The following illustration describes the AS-Interface Connection:
CANopen Fieldbus Connection
The CANopen architecture of a Twido system consists of: z z z a Twido PLC (compact base or modular base)
1
, a CANopen fieldbus master module (TWDNCO1M module) installed on the
Twido PLC’s expansion bus
2
,
CANopen slave devices
3,4
.
NOTE:
1.
The TWDNCO1M CANopen master module is supported by the following Twido base controllers: z
Compact bases: TWDLC•A24DRF, TWDLCA•40DRF and z
TWDLCD•40DRFseries
All modular bases: TWDLMDA20••• and TWDLMDA40••• series
2.
Only 1 TWDNCO1M CANopen master module can be installed on the Twido system expansion bus.
3.
The TWDNCO1M CANopen master module can manage up to 16 CAN slave devices on a single bus segment.
4.
The TWDNCO1M CANopen fieldbus does not support extended addressing for
CANopen slave devices.
28 35011387 06/2011
Twido CANopen Fieldbus Topology
The following figure shows the Twido CANopen fieldbus topology:
Twido Overview
35011387 06/2011
29
Twido Overview
Ethernet Network Connection
NOTE: Although direct cable connection (using a Ethernet crossover cable) is supported between the Twido TWDLCAE40DRF (or TWDLCDE40DRF) and the PC running the TwidoSuite programming software, making the connection, via a network Ethernet hub/switch, is recommended.
The following figure shows a PC-to-Twido connection via a network Ethernet hub/switch:
30
NOTE: The PC running the TwidoSuite application must be Ethernet-capable.
The Twido TWDLCAE40DRF and TWDLCDE40DRF bases feature a RJ45 connector to connect to the 100 BASE-TX network Ethernet with auto negotiation. It can accommodate both 100Mbps and 10 Mbps network speeds.
The following figure shows the RJ45 connector of the Twido controller:
The eight pins of the RJ45 connector are arranged vertically and numbered in order from bottom to top. The pinout for the RJ45 connector is described in the table below:
Polarity
7
6
Pinout
8
5
Function
NC
NC
RxD
NC
(-)
35011387 06/2011
Twido Overview
2
1
Pinout
4
3
Function
NC
RxD
TxD
TxD
Polarity
(+)
(-)
(+) z z
NOTE:
The same connector and pinout is used for both 10Base-T and 100Base-TX.
When connecting the Twido controller to a 100Base-TX network, use at least a category 5 Ethernet cable.
Modem Connection
A PC executing TwidoSuite can be connected to a Twido controller for transferring applications, animating objects and executing operator mode commands. It is also possible to connect a Twido controller to other devices, such as another Twido controller, for establishing communication with the application process.
35011387 06/2011
31
Twido Overview
32 35011387 06/2011
Twido Programmable Controllers
Installation
35011387 06/2011
Installation
2
Introduction
This chapter provides installation overall instructions and installation preparation, installation and mounting instructions for the compact bases, for the modular bases, and for their options, and how to connect the power supply.
What’s in this Chapter?
This chapter contains the following sections:
2.1
Section
2.2
2.3
Topic
Installation Overall Instructions
Compact Bases Installation
Modular Bases Installation
Page
33
35011387 06/2011
Installation
2.1
Installation Overall Instructions
Introduction
This section provides information for installation preparation, safety, how to assemble and disassemble bases and modules, and minimum clearances for bases and modules.
What’s in this Section?
This section contains the following topics:
Topic
Installation Requirements
Installation Preparation
Compact and Modular Bases Mounting Positions
Assembling an Expansion I/O Module to a Base
Disassembling an Expansion I/O Module from a Base
Minimum Clearances for Bases and Expansion I/O Modules in a Control Panel
Page
34 35011387 06/2011
Installation
Installation Requirements
NOTICE
Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.
(c) 2008 Schneider Electric All Rights Reserved
Additional Information
Those responsible for the application, implementation or use of this product must ensure that the necessary design considerations have been incorporated into each application, completely adhering to applicable laws, performance and safety requirements, regulations, codes and standards.
General Information
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z
Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
35011387 06/2011
35
Installation
WARNING
EXPLOSION HAZARD z z z
This equipment is suitable for use in Class 1, Division 2, Groups A, B, C and D or non-hazardous locations only.
Substitution of components may impair suitability for Class I, Division 2 compliance.
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING z z z z
UNINTENDED EQUIPMENT OPERATION z z
This product is not intended for use in safety critical machine functions. Where personnel and or equipment hazards exist, use appropriate safety interlocks.
Do not disassemble, repair, or modify the modules.
This controller is designed for use within an enclosure appropriately rated for its intended environment.
Install the modules in the operating environment conditions described.
Use the sensor power supply only for supplying power to sensors connected to the module.
For power line and output circuits, use a fuse in compliance with local and national requirements for the circuit voltage and current requirements.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
36 35011387 06/2011
Installation
WARNING
LOSS OF CONTROL z z z z
The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop.
Separate or redundant control paths must be provided for critical control functions.
System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.
1
Each implementation of the Twido Programmable Controller must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1
For additional information refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control”.
Safe Battery Disposal
The TWDLCA•40DRF compact bases use an optional external lithium battery for longer duration of data backup. (Note: The lithium battery is not supplied with the compact bases; you must purchase it separately.)
WARNING
FIRE OR CHEMICAL HAZARD
The Lithium batteries used in this device may present a risk of fire or chemical burn if not handled properly z z z z
Do not recharge, disassemble, heat above 212 ° F (100 ° C), or incinerate.
Recycle or properly dispose of used batteries.
Replace with identical type: TSXPLP01 (Tadiran, TL-5902) only.
Follow all battery manufacturers’ instructions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
35011387 06/2011
37
Installation
Reverse Polarity
Reverse-Polarity at Transistor Output is Not Allowed
The TWDLCA•40DRF compact bases transistor outputs cannot withstand any reverse polarity.
CAUTION
REVERSE-POLARITY DAMAGE AT TRANSISTOR OUTPUTS
Make sure to conform to the polarity markings on the transistor output terminals.
Failure to follow these instructions can result in injury or equipment damage.
38 35011387 06/2011
Installation
Installation Preparation
Introduction
The following section provides information on preparation for all TwidoSuite bases and expansion I/O modules.
Before Starting
Before installing any of the TwidoSuite products read the Safety Information at the beginning of this book.
CAUTION
INOPERABLE EQUIPMENT
Before adding/removing any module or adapter, turn off the power to the base.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: All options, expansion I/Os, AS-Interface bus and CANopen fieldbus interface modules should be assembled before installing a Twido system on a DIN rail, onto a mounting plate, or in a control panel, should be removed from a DIN rail, a mounting plate, or a control panel before disassembling the modules.
35011387 06/2011
39
Installation
Compact and Modular Bases Mounting Positions
Introduction
This section shows the correct and incorrect mounting positions for all bases.
NOTE: Keep adequate spacing for proper ventilation and to maintain an ambient temperature between 0 ° C (32 ° F) and 55 ° C (131 ° F).
CAUTION
EQUIPMENT OVERHEATING
Do not place heat generating devices such as transformers and power supplies underneath the controllers or expansion I/O modules.
Failure to follow these instructions can result in injury or equipment damage.
Correct Mounting Position for all Bases
Compact and Modular bases must be mounted horizontally on a vertical plane as shown in the figures below.
Additional Permitted Mounting Positions for Compact Bases
Where the ambient temperature will not exceed 40 ° C (104 ° F), the compact bases may be mounted sideways on a vertical place as shown below:
40 35011387 06/2011
35011387 06/2011
Installation
Where the ambient temperature will not exceed 35 ° C (95 ° F), the compact bases may also be mounted upright on a horizontal plane as shown below:
Do not mount the products in any other orientation.
41
Installation
Assembling an Expansion I/O Module to a Base
Introduction
This section shows how to assemble an expansion I/O module to a base. This procedure is for both Compact and Modular bases. Your base and expansion I/O module may differ from the illustrations in this procedure.
WARNING
UNEXPECTED EQUIPMENT OPERATION
Update the software each time you change the hardware configuration of the I/O expansion bus. Otherwise, the expansion bus will no longer operate while the local base inputs and outputs will continue to operate.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Assembling an Expansion I/O Module to a Base.
The following procedure shows how to assemble a base and an expansion I/O module together.
Step Action
1 Remove the expansion connector cover from the base.
2 Verify that the black latch button on the I/O module is in the up position.
42 35011387 06/2011
35011387 06/2011
Installation
Step Action
3 Align the connector on the left side of the Expansion I/O module with the connector on the right side of the base.
4
5
Press the expansion I/O module to the base until it "clicks" into place.
Push down the black latch button on the top of the expansion I/O module to lock the module to the base.
43
Installation
Disassembling an Expansion I/O Module from a Base
Introduction
This section describes how to disassemble an expansion I/O module from a base.
This procedure is for both Compact and Modular bases. Your base and expansion
I/O module may differ from the illustrations in these procedures but the basic mechanism procedures are still applicable.
Disassembling an Expansion I/O Module from a Base.
The following procedure describes how to disassemble an expansion I/O module from a base.
Step
1
2
Action
Remove the assembled base and module from the DIN rail before disassembling them, see
.
Push up the black latch from the bottom of the expansion I/O module to disengage it from the base.
44 35011387 06/2011
Step
3
Action
Pull apart the base and module.
Installation
35011387 06/2011
45
Installation
Minimum Clearances for Bases and Expansion I/O Modules in a Control Panel
Introduction
This section provides the minimum clearances for bases and expansion I/O modules in a control panel.
Minimum Clearances for a Compact Base and Expansion I/O Modules
In order to maintain a natural circulation of air around the Compact base and expansion I/O modules in a control panel, observe the minimum clearances shown in the figures below.
46 35011387 06/2011
Installation
Minimum Clearances for a Modular Base and Expansion I/O Modules
In order to maintain a natural circulation of air around the Modular base and expansion I/O modules in a control panel, observe the minimum clearances shown in the figures below.
35011387 06/2011
47
Installation
2.2
Compact Bases Installation
Introduction
This section provides information for installing Compact bases.
What’s in this Section?
This section contains the following topics:
Topic
Dimensions of the Compact Bases
How to Direct Mount a Compact Base on a Panel Surface
How to Install and Remove a Compact Base from a DIN Rail
How to Install the Operator Display Module
How to Install a Serial Interface Adapter to a Compact Base
How to Install a Memory or RTC Cartridge in a Compact base
How to Connect the Power Supply to Compact Bases
How to Install and Replace an External Battery
Page
48 35011387 06/2011
Installation
Dimensions of the Compact Bases
Introduction
The following section shows the dimensions for all Compact bases.
TWDLC•A10-DRF and TWDLC•A16-DRF
The following diagrams show the dimensions for the TWDLC•A10DRF and
TWDLC•A16DRF series Compact bases.
Illustration showing TWDLC•A10DRF series base: mm in.
80,0 mm
3.17 in.
70,0 mm
2.78 in.
TWDLC•A24-DRF
The following diagrams show the dimensions for the TWDLC•A24DRF series
Compact base.
35011387 06/2011
49
Installation
TWDLC••40-DRF
The following diagrams show the dimensions for the TWDLC••40DRF series
Compact base.
NOTE: * 8.5 mm (0.33 in) when the clamp is pulled out.
50 35011387 06/2011
Installation
How to Direct Mount a Compact Base on a Panel Surface
Introduction
This section also provides mounting hole layouts for a Compact base and module.
Your base or module may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
Mounting Hole Layout for Compact Bases
The following diagram shows the mounting hole layout for all the Compact bases.
35011387 06/2011
51
Installation
How to Install and Remove a Compact Base from a DIN Rail
Introduction
This section describes how to install and remove compact bases from a DIN rail. The device you want to install or remove may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
NOTE: When mounting compact bases on a DIN rail, use two end stops, type AB1-
AB8P35 or equivalent.
For additional information about the DIN rail,
see The DIN Rail. The DIN Rail, page 227
How to Install a Compact Base on a DIN Rail
The following procedure shows how to install a compact base on a DIN rail.
Step
1
2
Action
Fasten the DIN rail to a panel using screws.
Pull out the clamp at the bottom of the compact base and module assembly.
3 Put the top groove of the compact base and module on the DIN rail and press the modules toward the DIN rail.
52 35011387 06/2011
Installation
Step
4
5
Action
Push the clamp into the DIN rail.
Place mounting clips on both sides of the modules to keep the system from moving sideways.
How to Remove a Compact Base from a DIN Rail
The following procedure shows how to remove a compact base from a DIN rail.
Step
1
2
Action
Insert a flat screwdriver into the slot in the clamp.
Pull out the clamp.
3 Pull the compact base and the associated module off the DIN rail from the bottom.
35011387 06/2011
53
Installation
How to Install the Operator Display Module
Introduction
This section describes installation of the TWDXCPODC operator display module.
Installing the Operator Display Module into a Compact Base
The following procedure shows how to install the TWDXCPODC operator display module into a Compact base.
Step
1
Action
Remove the operator display connector cover on the Compact base.
2 Locate the operator display connector inside the Compact base.
54 35011387 06/2011
Step
3
Installation
Action
Push the operator display module into the operator display connector in the
Compact base until it "clicks".
35011387 06/2011
55
Installation
How to Install a Serial Interface Adapter to a Compact Base
Introduction
This section shows how to install the TWDNAC232D, TWDNAC485D, or
TWDNAC485T serial interface adapter into the port 2 in a Compact base. Your base may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
How to Install the Serial Interface Adapter into the Port 2 in a Compact Base
The following procedure shows how to install the TWDNAC232D, TWDNAC485D, or TWDNAC485T serial interface adapter into the port 2 in a Compact base.
Step
1
2
3
Action
Open the hinged lid.
Remove the cartridge cover located on the bottom of the Compact base.
Push the serial interface adapter connector into the port 2 of the Compact base connector until it
"clicks".
56
4
5
Look in the opening at the bottom of the Compact base where the cartridge cover resided and verify that the serial interface adapter connector is seated in the port 2 connector of the Compact base .
Adjust the adapter if it is not seated correctly.
Attach the cartridge cover.
35011387 06/2011
Installation
How to Install a Memory or RTC Cartridge in a Compact base
Introduction
This section shows how to install the TWDXCPMFK32 memory cartridge, the
TWDXCPMFK64 memory cartridge (only for TWDLC••40DRF bases) and the
TWDXCPRTC RTC cartridge in a Compact base.
Installing a Cartridge in a Compact Base
The following procedure shows how to install the TWDXCPMFK32 memory, the
TWDXCPMFK64 memory (only for TWDLC••40DRF bases) or the TWDXCPRTC
RTC cartridge in a Compact base. Only one of these cartridges can be installed in the Compact base.
NOTE: The catridge electrical elements are sensitive to static electricity.
CAUTION
INOPERABLE EQUIPMENT
Do not touch catridge pins. Use proper Electrically Sensitive Device (ESD) procedures when handling cartridge.
Failure to follow these instructions can result in injury or equipment damage.
2
3
Step
1
Action
Open bottom terminal cover.
Remove the cartridge cover.
Push the cartridge into the cartridge connector until it "clicks".
35011387 06/2011
4 Close the terminal cover.
57
Installation
How to Connect the Power Supply to Compact Bases
Introduction
This section describes how to connect the power supply to the Compact bases.
NOTE: When operating outside of the specified voltage range, outputs may not switch accordingly. Use appropriate safety interlocks and voltage monitoring circuits.
CAUTION z z
INCOMPATIBLE OR IMPROPER POWER SUPPLY CONNECTIONS
Verify that proper voltage and frequency is applied to the device.
Verify that you have made proper lead connections to the power supply terminal block.
Failure to follow these instructions can result in injury or equipment damage.
Connect an AC Power Supply to a Compact Base
The following diagram shows how to connect an AC power supply to a
TWDLCA•••DRF series Compact Base.
58 35011387 06/2011
Connect a DC Power Supply to a Compact Base
The following diagram shows how to connect a DC power supply to a
TWDLCD•••DRF series Compact Base.
Installation
Compact Base Power Supply Specifications
The following table provides power supply information for the Compact base.
Item
Power supply voltage
Inrush current flow at power-up
Power supply wiring
Ground wiring
AC Specifications
Rated power voltage: from 100 to 240 VAC
Allowable range: from 85 to 264 VAC
The detection of the absence of a power supply depends on the number of inputs and outputs used. Usually the absence of a power supply is detected when voltage drops to less than 85
VAC, stopping the current operation.
Note: Momentary power interruption for 20 ms or less at 100 to 240 VAC is not recognized as a loss of power.
TWDLCAA10DRF and TWDLCAA16DRF:
35 A maximum
TWDLCAA24DRF: 40 A maximum
DC Specifications
Rated power voltage: 24 VDC
Allowable range: from 19.2 to 30 VDC
The detection of the absence of a power supply depends on the number of inputs and outputs used. Usually the absence of a power supply is detected when voltage drops to below 14 VDC, stopping the current operation.
Note: Momentary power interruption for 10 ms or less at 24 VDC is not recognized as a loss of power.
TWDLCD•40DRF: 60 A maximum
0.64 mm 2 (UL1015 AWG22) or 1.02 mm 2 (UL1007 AWG18)
Make the power supply wiring as short as possible.
1.30 mm 2 (UL1007 AWG16)
Do not connect ground wire in common with ground wire of motor equipment.
35011387 06/2011
59
Installation
How to Install and Replace an External Battery
NOTE: The following information about the external battery applies to
TWDLC••40DRF series compact bases only. If you have another compact base model, you may skip this section.
Introduction
In addition to the built-in internal battery used for RAM backup, all TWDLC••40DRF compact bases are equipped with a battery compartment that can host a userreplaceable external battery. Note that for most applications, no external battery is required.
The external battery option provides extended backup duration to meet the needs for long-term backup for specific applications, such as HAVC applications.
Battery Type
Your compact base uses one 1/2 AA, 3.6 V, lithium battery to provide optional extended data storage duration of up to 3 years.
NOTE: The external battery is not included with your Twido base and is purchased separately. Please use part number TSXPLP01 to order a single battery or
TSXPLP101 to order a 10 pack.
Safe Battery Disposal
The TWDLC••40DRF compact bases use an optional external lithium battery for longer duration of data backup. (Note: The lithium battery is not supplied with the compact base and is purchased separately.)
WARNING
FIRE OR CHEMICAL HAZARD z z z z
The Lithium batteries used in this device may present a risk of fire or chemical burn if not handled properly
Do not recharge, disassemble, heat above 212 ° F (100 ° C), or incinerate.
Recycle or properly dispose of used batteries.
Replace with identical type: TSXPLP01 (Tadiran, TL-5902) only.
Follow all battery manufacturers’ instructions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
60 35011387 06/2011
Installation
Battery Power Status
The BAT LED indicator located on the front panel of your Twido compact base is used as an indicator for low battery alert. The BAT LED state is described in the following table:
LED State
Off
Steady red
Description
Indicates that either: z the external battery is functioning normally, or z the BAT LED has been disabled by user by setting the%S66 system bit to 1.
Indicates that either: z the power of the external battery is low (voltage below 2.5V) (The z external battery must be replaced within two weeks from the date the
BAT LED was first lit.), or there is no external battery installed in the battery compartment.
Battery Installation Requirements
When installing or replacing the external battery, verify that the following two conditions are met:
1.
The internal battery of your Twido compact base must be fully charged.
2.
After installing the external battery, power up your Twido base immediately.
NOTE: Not meeting either of the above two conditions will result in a significantly shorter battery life. The external battery life can be rapidly reduced to less than one month.
Installing and Replacing an External Battery
The battery compartment is located on the lower-panel of the Twido compact base case. To install or replace an external battery, follow these steps:
Step
1
2
Action
Before installing or replacing the external battery, verify that the internal battery of your Twido base is fully charged so that the data stored in RAM memory are not lost when the external battery is removed from its compartment.
Press sideways on the small latch protruding from the compartment cover to unlock the door of the battery compartment.
35011387 06/2011
61
Installation
Step
3
Action
Pull to open the compartment door, as shown in the figure below:
6
7
4
5
Remove the used battery from the compartment, if any.
Insert the new battery in the compartment, observing the correct polarity, as indicated by the polarity marking located inside the battery compartment.
Close the door of the battery compartment (verify the latch clicks into place to lock the compartment door).
Power up your Twido base immediately to preserve battery life.
Battery Status Monitoring and Control via System Bits
The following information describes how the battery status can be monitored and how the battery LED management can be controlled via two system bits%S75 and%S66, respectively:
System Bit
%S75
%S66
Description
This is a read-only system bit that indicates the current battery status: z %S75 = 0: external battery is operating normally.
z %S75 = 1: external battery power is low, or battery is absent from compartment.
This system bit is writable and allows you to turn on/off the BAT LED: z Set this bit to 1 to disable the BAT LED (LED is off even if there is no z battery inside the compartment).
Set this bit to 0 to enable the BAT LED indicator. Note that the%S66 system bit is reset to 0 as default at system start-up.
62 35011387 06/2011
Installation
2.3
Modular Bases Installation
Introduction
This section provides Information about installing Modular bases.
What’s in this Section?
This section contains the following topics:
Topic
Dimensions for the Modular Controllers
How to Direct Mount a Modular Base on a Panel Surface
How to Install and Remove a Modular Base from a DIN Rail
How to Install the Operator Display Expansion Module
How to Install a Serial Interface Adapter to Modular Bases
How to Install a Second Serial Interface Expansion Module to a Modular Base
Removing a Terminal Block
How to Install a Memory or RTC Cartridge in a Modular Base
How to Connect the Power Supply to Modular Bases
Page
35011387 06/2011
63
Installation
Dimensions for the Modular Controllers
Introduction
The following section shows the dimensions for all Modular controllers.
TWDLMDA20-DRT Dimensions
The following diagrams show the dimensions for the TWDLMDA20DRT Modular base.
mm in.
47,5 mm
1.87 in.
14,6 mm
0.57 in.
70,0 mm
2.76 in.
TWDLMDA20-DUK and TWDLMDA20-DTK Dimensions
The following diagrams show the dimensions for the TWDLMDA20DUK and
TWDLMDA20DTK Modular bases.
mm in.
34,5
1.39
11,3
0.44
70
2.76
64 35011387 06/2011
Installation
TWDLMDA40-DUK and TWDLMDA40-DTK Dimensions
The following diagrams show the dimensions for the TWDLMDA40DUK and
TWDLMDA40DTK Modular bases.
mm in.
47,5
1.87
11,3
0.44
70
2.76
NOTE: * 8.5 mm (0.33 in) when the clamp is pulled out.
35011387 06/2011
65
Installation
How to Direct Mount a Modular Base on a Panel Surface
Introduction
This section shows how to install mounting strips directly on modular bases. This section also provides mounting hole layouts for modular bases. Your base may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
Installing a Mounting Strip
The following procedure shows how to install a mounting strip.
Step
1
2
3
Action
Remove the clamp from the back side of the module by pushing the clamp inward.
Insert the mounting strip, with the hook entering last, into the slot where the clamp was removed.
Slide the mounting strip into the slot until the hook enters into the recess in the module.
Mounting Hole Layout for Modular Bases
The following diagram shows the mounting hole layout for all the Modular bases.
66 35011387 06/2011
Installation
How to Install and Remove a Modular Base from a DIN Rail
Introduction
This section describes how to install and remove modular base from a DIN rail. The device you want to install or remove may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
NOTE: When mounting modular bases on a DIN rail, use two end stops, type AB1-
AB8P35 or equivalent.
For additional information about the DIN rail,
see The DIN Rail. The DIN Rail, page 227
How to Install a Modular Base on a DIN Rail
The following procedure shows how to install a Modular base on a DIN rail.
Step
1
2
Action
Fasten the DIN rail to a panel using screws.
Pull out the clamp at the bottom of the modular base and module assembly.
3 Put the top groove of the modular base and module on the DIN rail and press the modules toward the DIN rail.
35011387 06/2011
67
Installation
Step
4
5
Action
Push the clamp into the DIN rail.
Place mounting clips on both sides of the modules to help to minimize side-toside movement of the system.
How to Remove a Modular Base from a DIN Rail
The following procedure shows how to remove a modular base from a DIN rail.
Step
1
Action
Insert a flat screwdriver into the slot in the clamp.
2
3
Pull out the clamp.
Pull the modular base and the associated module off the DIN rail from the bottom.
68 35011387 06/2011
Installation
How to Install the Operator Display Expansion Module
Introduction
This section describes the TWDXCPODM installation and removal of the operator display expansion module .
Assembling the Operator Display Expansion Module to a Modular Base
The following procedure shows how to assemble the TWDXCPODM operator display expansion module to a Modular base.
Step
1
2
Action
Remove the communication connector cover on the left side of the Modular base.
Verify that the black latch button on the operator display expansion module is in the up position.
3 Align the connector opening on the left side of the Modular base to the connector on the right side of the operator display expansion module.
4
5
Press the operator display expansion module to the Modular base until it "clicks" into place.
Push down the black latch button on the top of the operator display expansion module to lock the module to the Modular base.
Disassembling an Operator Display Expansion Module from a Modular Base
To remove the TWDXCPODM operator display expansion module from a Modular
base, see Disassembling an Expansion I/O Module from a Base, page 44 .
35011387 06/2011
69
Installation
How to Install a Serial Interface Adapter to Modular Bases
Introduction
This section shows how to install the TWDNAC232D, TWDNAC485D or
TWDNAC485T serial interface adapter in a TWDXCPODM operator display expansion module. Your base may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
How to Install a Serial interface Adapter in the Operator Display Expansion Module
The following procedure shows how to install the TWDNAC232D, TWDNAC485D, or TWDNAC485T serial interface adapter in a TWDXCPODM operator display expansion module.
Step
1
2
Action
Open the hinged lid.
Push the serial interface adapter connector into the operator display expansion module connector until it "clicks".
3 Close the hinged lid.
70 35011387 06/2011
Installation
How to Install a Second Serial Interface Expansion Module to a Modular Base
Introduction
This section shows how to assemble the TWDNOZ232D, TWDNOZ485D, and
TWDNOZ485T second serial interface expansion module to a Modular base. Your base may differ from the illustrations in these procedures but the basic mechanism procedures are applicable.
Assembling a Second Serial Interface Expansion Module to a Modular Base
The following procedure shows how to assemble the TWDNOZ485D,
TWDNOZ232D, or TWDNOZ485T second serial interface expansion module to a
Modular base.
Step
1
2
Action
Remove the communication connector cover on the left side of the Modular base.
Verify that the black latch button on the second serial interface expansion module is in the up position.
3 Align the connector opening on the left side of the Modular base to the connector on the right side of the second serial interface expansion module.
35011387 06/2011
71
Installation
Step
4
5
Action
Press the second serial interface expansion module to the Modular base until it "clicks" into place.
Push down the black latch button on the top of the second serial interface expansion module to lock the module to the Modular base.
Installing a Second Serial Interface Expansion Module with Operator Display
The following procedure shows how to assemble the TWDNOZO485D,
TWDNOZO232D, or TWDNOZO485T second serial interface expansion module to a Modular base.
Step
1
2
Action
Remove the communication connector cover on the left side of the Modular base.
Verify that the black latch button on the operator display expansion module is in the up position.
3 Align the connector opening on the left side of the Modular base to the connector on the right side of the operator display expansion module.
72
4
5
Press the operator display expansion module to the Modular base until it
"clicks" into place.
Push down the black latch button on the top of the operator display expansion module to lock the module to the Modular base.
35011387 06/2011
Installation
Second Serial Interface Expansion Module Dimensions
The following diagram shows the dimensions for all second serial interface expansion modules (TWDNOZ232D, TWDNOZ485T, and TWDNOZ485D).
Illustration of the TWDNOZ485T module:
35011387 06/2011
73
Installation
Removing a Terminal Block
Introduction
This section shows how to remove a terminal block from the TWDLMDA20DRT
Modular base.
Removing a Terminal Block
The following procedure shows how to remove a terminal block from the
TWDLMDA20DRT Modular base.
CAUTION
TERMINAL BLOCK DAMAGE
Do not pull the terminal block out from the top or bottom of the block.
Failure to follow these instructions can result in injury or equipment damage.
Step
1
Action
Power off to the Modular base and disconnect all wires.
Note: The terminal block on the left (1) must be removed before the terminal block on the right (2).
2 Remove the terminal block by holding the center of the terminal block and pulling it out straight.
74 35011387 06/2011
Installation
How to Install a Memory or RTC Cartridge in a Modular Base
Introduction
This section shows how to install the TWDXCPMFK32 or TWDXCPMFK64 memory cartridge in a Modular base, and the TWDXCPRTC RTC cartridge in a Modular base.
Installing a Cartridge in a Modular Base
The following procedure shows how to install the TWDXCPMFK32 or
TWDXCPMFK64 memory cartridge or the TWDXCPRTC RTC cartridge in a
Modular base. Only one RTC cartridge can be installed. A memory cartridge and a
RTC cartridge can be installed at the same time.
CAUTION
INOPERABLE EQUIPMENT
Do not touch cartridge pins. Use proper Electrically Sensitive Device (ESD) procedures when handling cartridge.
Failure to follow these instructions can result in injury or equipment damage.
Step
1
2
3
Action
Open the hinged door.
Remove the cartridge cover by holding and pulling the opposite edges of the cover until it is out.
Push the cartridge into the Modular base connector until it "clicks".
4 Close the hinged door.
35011387 06/2011
75
Installation
How to Connect the Power Supply to Modular Bases
Introduction
This section describes how to connect the power supply to the Modular bases.
NOTE: When operating outside of the specified voltage range, outputs may not switch as expected. Use appropriate interlocks and voltage monitoring circuits.
CAUTION
INCOMPATIBLE OR IMPROPER POWER SUPPLY CONNECTIONS z z
Verify that proper voltage and frequency is applied to the device.
Verify that you have made proper lead connections to the power supply terminal block.
Failure to follow these instructions can result in injury or equipment damage.
Connect a Power Supply to a Modular Base
The following diagram shows how to connect a power supply to a Modular Base.
76 35011387 06/2011
Installation
Modular Base Power Supply Specifications
The following table provides power supply information for the Modular base.
Item
Power supply voltage
Inrush current flow at power-up
Power supply wiring
Ground wiring
Specifications
Rated power voltage: 24 VDC
Allowable range: from 20.4 to 26.4 VDC
The detection of the absence of a power supply depends on the number of inputs and outputs used. Usually the absence of a power supply is detected when voltage drops to below 20.4 VDC, stopping the current operation.
Note: Momentary power interruption for 10 ms or less at 24 VDC is not recognized as a loss of power.
50 A maximum
0.64 mm 2 (UL1015 AWG22) or 1.02 mm 2 (UL1007 AWG18)
Make the power supply wiring as short as possible.
0.64 mm 2 (UL1015 AWG22) or 1.02 mm 2 (UL1007 AWG18)
Do not connect ground wire in common with ground wire of motor equipment.
35011387 06/2011
77
Installation
78 35011387 06/2011
Twido Programmable Controllers
Description of Compact Bases
35011387 06/2011
Description of Compact Bases
3
Introduction
This chapter provides descriptions, overviews, parts, specifications, wiring rules and recommendations, and wiring schematics for the Twido Compact Bases.
What’s in this Chapter?
This chapter contains the following sections:
3.1
Section
3.2
3.3
3.4
Compact Bases Description
Topic
Specifications for Compact Bases
Wiring Rules and Recommendations, and Wiring Schematics for Compact Bases
Compact Bases Options
Page
79
35011387 06/2011
Description of Compact Bases
3.1
Compact Bases Description
Introduction
This section provides an overview and a parts description of the Compact bases.
What’s in this Section?
This section contains the following topics:
Topic
Overview of Compact Bases
Parts Description of a Compact Base
Page
80 35011387 06/2011
Description of Compact Bases
Overview of Compact Bases
Introduction
The information in this section describes the main features of the Compact bases.
Compact Controllers Features Overview
The following table gives information about the main features of the different types of Compact controllers:
Features
Inputs
Outputs
Battery Compartment
Expansion I/O Modules
AS-I V2 bus Modules
CANopen fieldbus Module
Operator Display Module
(optional)
Ethernet interface
10 I/O bases:
TWDLCAA10DRF
TWDLCDA10DRF
16 I/O bases:
TWDLCAA16DRF
TWDLCDA16DRF
24 I/O bases:
TWDLCAA24DRF
TWDLCDA24DRF
6 discrete inputs
4 relay outputs
Analog Potentiometers
Integrated Serial Port
1
√
No Additional Serial Port
RTC cartridge (optional) √
Memory cartridge (optional) 32 KB
No
No
No
No
√
1 ConneXium
TwidoPort module
9 discrete inputs
7 relay outputs
1
√
√
32 KB
No
No
No
No
√
1 ConneXium
TwidoPort module
14 discrete inputs
10 relay outputs
2
√ one slot available one slot available
√
32 KB
No up to 4 modules up to 2 modules
√
√
1 ConneXium
TwidoPort module
40 I/O bases:
TWDLCAA40DRF
TWDLCAE40DRF
TWDLCDA40DRF
TWDLCDE40DRF
24 discrete inputs
14 relay and 2 transistor outputs
2
√ one slot available
RTC onboard
32 KB or 64 KB
√
√
√ up to 7 modules up to 2 modules
For
TWDLC•A40DRF: 1
ConneXium
TwidoPort module
For
TWDLC•E40DRF: 1
Built-in RJ45 port
35011387 06/2011
81
Description of Compact Bases
Illustration of Compact 10 I/O Controllers
The following illustration gives a picture of the two types of 10 I/O Compact controllers:
Controller References
TWDLCAA10DRF
TWDLCDA10DRF
Note: Power supply: z 100/240 VAC for theTWDLCAA10DRF z 24 VDC for theTWDLCDA10DRF
Illustration
Illustration of Compact 16I/O Controllers
The following illustration gives a picture of the two types of 16 I/O Compact controllers:
Controller References
TWDLCAA16DRF
TWDLCDA16DRF
Note: Power supply: z 100/240 VAC for theTWDLCAA16DRF z 24 VDC for theTWDLCDA16DRF
Illustration
82 35011387 06/2011
Description of Compact Bases
Illustration of Compact 24 I/O Controllers
The following illustration gives a picture of the two types of 24 I/O Compact controllers:
Controller References
TWDLCAA24DRF
TWDLCDA24DRF
Note: Power supply: z 100/240 VAC for theTWDLCAA24DRF z 24 VDC for theTWDLCDA24DRF
Illustration
35011387 06/2011
83
Description of Compact Bases
Illustration of Compact 40 I/O Controllers
The following illustration gives a picture of the two types of 40 I/O Compact controllers:
Controller References
TWDLCAA40DRF
TWDLCDA40DRF
TWDLCAE40DRF
TWDLCDE40DRF
Note: Power supply: z 100/240 VAC for the TWDLCA•40DRF z 24 VDC for the TWDLCD•40DRF
Illustration
84 35011387 06/2011
Description of Compact Bases
Parts Description of a Compact Base
Introduction
The following section describes the parts of a Compact base. Your base may differ from the illustrations but the parts will be the same.
Parts Description of a Compact Base
The following figure shows the parts of a Compact base. This figure is the
TWDLCAA24DRF base.
Caption
35011387 06/2011
8
9
10
6
7
4
5
2
3
Label
1
11
12
Description
Mounting hole
Terminal cover
Hinged lid
Removable cover to operator display connector
Expansion connector - On both 24DRF and 40DRF series compact bases
Sensor power terminals
Serial port 1
Analog potentiometers - TWDLCAA10DRF and TWDLCAA16DRF have one
Serial port 2 connector - TWDLCAA10DRF does not have any
100-240 VAC power supply terminals on TWDLCA•••DRF series
24 VDC power supply terminals on TWDLCD•••DRF series
Cartridge connector - located on the bottom of the base
Input terminals
85
Description of Compact Bases
Label
13
14
Description
LEDs
Output terminals
Rear Panel of a 40DRF Compact Base
The following figure shows the rear panel of a 40 I/O Compact base. This figure is the TWDLCAE40DRF base.
Caption
Label
1
2
Description
RJ45 100Base-TX Ethernet port (only TWDLCAE40DRF has one)
External user-replaceable battery compartment (both TWDLCAA40DRF and
TWDLCAE40DRF have one)
86 35011387 06/2011
3.2
Description of Compact Bases
Specifications for Compact Bases
Introduction
This section provides general, electrical, I/O, and functional specifications, and
Analog Potentiometers description for Compact bases.
What’s in this Section?
This section contains the following topics:
Topic
General Specifications for the Compact Bases
Electrical Specifications for the Compact Bases
Input Specifications for the Compact Base
Relay Output Specifications for the Compact Base
Output Transistor Specifications for the Compact Base
Description of Analog Potentiometers
Functional Specifications for the Compact Bases
Page
35011387 06/2011
87
Description of Compact Bases
General Specifications for the Compact Bases
Introduction
This section provides general specifications for the Compact bases. The Twido compact base is certified to CISPR.
TWDLCA•40DRF
WARNING
ELECTROMAGNETIC EMISSION
Class A equipment is intended for use in industrial environments. Compliance with
5.1.2/CISPR11 for electromagnetic compatibility in other than industrial environments may need to be verified.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Normal Operating Specifications
Compact base
TWDLC...
Ambient operating temperature
Storage temperature
Relative humidity
Degree of pollution
Degree of protection
Corrosion immunity
Altitude
Resistance to vibration
AA10DRF
DA10DRF
0 to 55 ° C (32 °
AA16DRF
DA16DRF
F to 131 ° F)
AA24DRF
DA24DRF
AA40DRF
AE40DRF
DA40DRF
DE40DRF
0 to 55 ° C (32 ° F to 131 ° F) at
75% load
0 to 45 ° C (32 ° F to 113 ° F) at full load
-25 ° C to +70 ° C (-13 ° F to 158 ° F)
Level RH1, 30 to 95% (non-condensing)
2 (IEC60664)
IP20
Free from corrosive gases
Operation: 0 to 2,000 m (0 to 6,560 ft)
Transport: 0 to 3,000 m (0 to 9,840 ft)
When mounted on a DIN rail:
10 to 57 Hz amplitude 0.075 mm, 57 to 150 Hz acceleration 9.8 ms axis on each of three mutually perpendicular axes.
When mounted on a panel surface:
2 (1G), 2 hours per
2 to 25 Hz amplitude 1.6 mm, 25 to 100 Hz acceleration 39.2 ms per axis on each of three mutually perpendicular axes.
2
(4G) Lloyd’s 90 min
88 35011387 06/2011
Description of Compact Bases
Compact base
TWDLC...
Impact strength
Weight
AA10DRF
DA10DRF
AA16DRF
DA16DRF
AA24DRF
DA24DRF
AA40DRF
AE40DRF
DA40DRF
DE40DRF
147 ms 2 (15G), 11 ms duration, 3 shocks per axis, on three mutually perpendicular axes (IEC 61131)
230 g
(8.11 oz)
250 g
(8.81 oz)
305 g
(10.75 oz)
522 g
(18.4 oz)
Specifications for the Backup Internal Battery
All compact base controllers have one non-removable internal battery
Compact backed up elements
Time
Battery type
Charging time
Service life
Internal RAM: internal variables, internal bits and words, timers, counters, shift registers, etc.
Approximately 30 days at 25 ° C (77 ° F) after battery fully charged.
Non-interchangeable lithium accumulator
Approximately 15 hours for 0% to 90 % of total load
10 years
Specifications for the Backup External Battery
Only TWDLCA•40DRF and TWDLCD•40DRF series compact bases have one external battery compartment.
Compact backed up elements
Time
Battery type
Internal RAM: internal variables, internal bits and words, timers, counters, shift registers, etc.
Approximately 3 years at 25 ° C (77 ° F) under following conditions: z Internal backup battery is fully charged.
z The Twido compact base is constantly powered. It has had no (or minor) down-time.
½ AA, 3.6V, lithium battery
Part number TSXPLP01 (Tadiran, TL-5902)
Note that the external battery must be purchased separately by user. No external battery is included with the Twido controller package.
35011387 06/2011
89
Description of Compact Bases
Electrical Specifications for the Compact Bases
Introduction
This section provides electrical specifications for the Compact bases. The Twido compact base is certified to CISPR.
TWDLCA•40DRF
WARNING
ELECTROMAGNETIC EMISSION WARNING (5.1.2/CISPR11)
Class A equipment is intended for use in industrial environments. Compliance with
5.1.2/CISPR11 for electromagnetic compatibility in other than industrial environments may need to be verified.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Electrical Specifications
Compact base
TWDLC...
Rated power voltage
Allowable voltage range
Rated power frequency
Maximum input current
Maximum power consumption
Allowable momentary power interruption
Dielectric strength
Insulation resistance
AA10DRF AA16DRF AA24DRF AA40DRF
AE40DRF
100 to 240 VAC
85 to 264 VAC
50/60 Hz (47 to 63 Hz)
0.25 A (85 VAC)
30 VA (264 VAC),
20 VA (100 VAC)
This base power consumption includes 250 mA sensor power.
0.30 A (85 VAC)
31 VA (264 VAC),
22 VA (100 VAC)
This base power consumption includes 250 mA sensor power.
0.45 A (85 VAC) 0.79 A (85 VAC)
40 VA (264 VAC),
33 VA (100 VAC)
This base plus 4
I/O modules power consumption includes 250 mA sensor power.
110 VA (264 VAC),
77 VA (100 VAC)
This base plus 7 I/O modules power consumption includes 400 mA sensor power.
10 ms, 100% drop out (at the rated inputs and outputs)
(IEC61131 and IEC61000-4-11)
Between power and ground terminals: 1,500 VAC, 1 min
Between I/O and ground terminals: 1,500 VAC, 1 min
Between power and ground terminals: 10 M Ω minimum
(500 VDC)
Between I/O and ground terminals: 10 M Ω minimum
(500 VDC)
90 35011387 06/2011
Description of Compact Bases
Compact base
TWDLC...
Electromagnetic resistance
AA10DRF
Inrush current
Ground wiring
Power supply wiring
Effect of improper power supply connection
AA16DRF AA24DRF
AC power terminals: 2kV, Level 3
I/O terminals:
- DC: 1kV, Level 3
- AC: 2kV, Level 4
According to IEC61131-2 (Zone B) and IEC61000-4-4
35 A maximum 35 A maximum 40 A maximum
UL1007 16 AWG (1.30 mm 2 )
UL1015 22 AWG (0.33 mm 2 ), UL1007 18 AWG (0.82 mm 2 )
Reverse polarity: normal operation
Improper voltage or frequency: internal fuse protection
AA40DRF
AE40DRF
35 A maximum
Compact base
TWDLC...
Rated power voltage
Allowable voltage range
Maximum input power
Electromagnetic resistance
Inrush current
Ground wiring
DA10DRF DA16DRF DA24DRF
24 VDC from 19.2 to 30 VDC (including ripple)
Base Base Base plus 4 I/O
Modules
3.9 W (@ 24 VDC) 4.6 W (@ 24 VDC) 5.6 W (@
24 VDC)
10 ms, 100% drop out (at the rated inputs and outputs)
(IEC61000-4-11)
Allowable momentary power interruption
Dielectric strength
Between power and ground terminals:
Between I/O and ground terminals:
Insulation resistance
500 VAC, 1 min
1500 VAC, 1 min
Between power and ground terminals: 10 M Ω minimum
(500 VDC)
Between I/O and ground terminals: 10 M Ω minimum
(500 VDC)
AC power terminals: 2kV, Level 3
I/O terminals:
- DC: 1kV, Level 3
- AC: 2kV, Level 4
According to IEC61131-2 (Zone B) and IEC61000-4-4
35 A maximum
(@ 24 VDC)
35 A maximum
(@ 24 VDC)
40 A maximum
(@ 24 VDC)
UL1015 22 AWG (0.33 mm
2
), UL1007 18 AWG (0.82 mm
2
)
DA40DRF
DE40DRF
Base plus 7 I/O
Modules
30 W (@ 24 VDC)
1000 VAC, 1 min
1500 VAC, 1 min
35 A maximum
(@ 24 VDC)
35011387 06/2011
91
Description of Compact Bases
Compact base
TWDLC...
Power supply wiring
Effect of improper power supply connection
DA10DRF DA16DRF DA24DRF
UL1015 22 AWG (0.33 mm 2 ), UL1007 18 AWG (0.82 mm 2 )
Reverse polarity: no operation, no damage
Improper voltage or frequency: internal fuse protection
DA40DRF
DE40DRF
92 35011387 06/2011
Description of Compact Bases
Input Specifications for the Compact Base
Introduction
This section provides Input specifications for the Compact bases.
DC Input Specifications
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified below.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Compact base TWDLCAA10DRF
TWDLCDA10DRF
TWDLCAA16DRF
TWDLCDA16DRF
TWDLCAA24DRF
TWDLCDA24DRF
TWDLCAA40DRF
TWDLCAE40DRF
TWDLCDA40DRF
TWDLCDE40DRF
24 points in 2 common lines Input points 6 points in 1 common line
9 points in 1 common line
Rated input voltage 24 VDC sink/source input signal
Input voltage range from 20.4 to 28.8 VDC
Rated input current I0 and I1: 11 mA
I2 to I13: 7 mA/point (24 VDC)
Input impedance
Turn on time
Turn off time
Isolation
Input type
14 points in 1 common line
I0 and I1: 2.1 k
I2 to I13: 3.4 k
I0 to I1: 35 μ
I2 to I13: 40
I0 and I1: 45
I2 to I13: 150
μ
Ω
Ω s + filter value
μ s + filter value
μ s + filter value s + filter value
I0, I1, I6, I7: 11 mA
I2 to I5, I8 to I23: 7 mA/point
(24 VDC)
I0, I1, I6, I7: 2.1 k Ω
I2 to I5, I8 to I23: 3.4 k Ω
I0, I1, I6, I7: 35 μ s + filter value
I2 to I5, I8 to I23: 40 μ s + filter value
I0, I1, I6, I7: 45 μ s + filter value
I2 to I5, I8 to I23: 150 μ s + filter value
Between input terminals and internal circuit: photocoupler isolated (isolation protection up to
500 V)
Between input terminals: not isolated
Type 1 (IEC 61131)
35011387 06/2011
93
Description of Compact Bases
Compact base TWDLCAA10DRF
TWDLCDA10DRF
TWDLCAA16DRF
TWDLCDA16DRF
TWDLCAA24DRF
TWDLCDA24DRF
TWDLCAA40DRF
TWDLCAE40DRF
TWDLCDA40DRF
TWDLCDE40DRF
External load for I/O interconnection
Signal determination method
Input signals type
Cable length
Not needed
Static
The input signals can be both sink and source.
3m (9.84 ft) for compliance with electromagnetic immunity.
I/O Usage Limits
When using TWDLC•AA16DRF, TWDLC•A24DRF, TWDLCA•40DRF and
TWDLD•40DRF at an ambient temperature of 55 ° C (131 ° F) in the normal mounting direction, limit the inputs and outputs, respectively, which turn on simultaneously along line (1).
Also, when using the above-mentioned bases at 45 ° C (113 ° F), all I/O can be turned on simultaneously at input voltage 28.8 VDC as indicated by line (2).
94 35011387 06/2011
Description of Compact Bases
Relay Output Specifications for the Compact Base
Introduction
This section provides relay output specifications for the Compact bases.
Relay Output Specifications
Compact base
Output points
Output points per common line:
COM0
Output points per common line:
COM1
Output points per common line:
COM2
Output points per common line:
COM3
Output points per common line:
COM4
Output points per common line:
COM5
Output points per common line:
COM6
Maximum load current
Minimum switching load
Initial contact resistance
TWDLCAA10DRF
TWDLCDA10DRF
4 output
3 NO contacts
1 NO contact
—
—
—
—
—
TWDLCAA16DRF
TWDLCDA16DRF
7 output
4 Normally Open
2 NO contacts
1 NO contact
—
—
—
—
TWDLCAA24DRF
TWDLCDA24DRF
10 output
4 NO contacts
4 NO contacts
1 NO contact
1 NO contact
—
—
—
TWDLCAA40DRF
TWDLCDAE40DRF
14 output
—
—
4 NO contact
4 NO contact
4 NO contact
1 NO contact
1 NO contact
2 A per output
8 A per common line
0.1 mA/0.1 VDC (reference value)
30 m Ω maximum:
@ 240VAC/2A load
@ 30VDC/2A load
100,000 operations minimum (rated resistive load 1,800 operations/h) Electrical life
Mechanical life 20,000,000 operations minimum (no load 18,000 operations/h)
Rated load (resistive/inductive) 240 VAC/2 A, 30 VDC/2 A
Dielectric strength Between output to internal circuit: 1500 VAC, 1 min
Between output groups: 1500 VAC, 1 min
35011387 06/2011
95
Description of Compact Bases
Relay Output Contact
The relay output contact is shown below.
Relay Output Delay
The relay output delay is shown below.
96 35011387 06/2011
Description of Compact Bases
Output Transistor Specifications for the Compact Base
Introduction
This section provides Output transistor specifications for the Compact bases.
Reverse Polarity Hazard
Reverse-Polarity at Transistor Output is Not Allowed
The TWDLC••40DRF compact bases transistor outputs cannot withstand any reverse polarity.
CAUTION z z
RISK OF REVERSE-POLARITY DAMAGE AT TRANSISTOR OUTPUTS
Conform to the polarity markings on the transistor output terminals.
Use of a reverse polarity can permanently damage or destroy the output circuits.
Failure to follow these instructions can result in injury or equipment damage.
Transistor Source Output Specifications
Compact base
Output type
Number of discrete output points
Output points per common
Line
TWDLC••40DRF bases
Source output
2
1
Rated load voltage
Maximum load current
24 VDC
1 A per common line
Operating load voltage range from 20.4 to 28.8 VDC
Voltage drop (on voltage) 1 V maximum (voltage between COM and output terminals when output is on)
Rated load current
Inrush current
Leakage current
Maximum lamp load
Inductive load
External current draw
1 A per output
2.5 A maximum
0.25 mA maximum
19 W
L/R = 10 ms (28.8 VDC, 1 Hz)
12 mA maximum, 24 VDC
(power voltage at the +V terminal)
35011387 06/2011
97
Description of Compact Bases
Compact base
Isolation
Output delay - turn on/off time
TWDLC••40DRF bases
Between output terminal and internal circuit: photocoupler isolated (isolation protection up to 500 VDC)
Between output terminals: 500 VDC
Q0, Q1: 5 μ s maximum ( )
Transistor Source Output Contact
The transistor source output contact applicable to TWDLC••40DRF series compact bases is shown below.
98 35011387 06/2011
Description of Compact Bases
Description of Analog Potentiometers
Introduction
The following section describes the analog potentiometer on the Compact bases.
Description
The TWDLC•A10DRF
1
and TWDLC•A16DRF
1
bases have one analog potentiometer. The TWDLC•A24DRF
1
, TWDLCA•40DRF
2
and TWDLCD•40DRF
2 bases have two analog potentiometers. The two analog potentiometers can be set to a value between 0 and 1023. The value is stored in a system word and is updated in every scan. For more information on setting the analog potentiometer, see the
TwidoSuite Software Reference Manual.
NOTE:
1.
• = D as in 24 VDC power supply
• = A as in 110/240 VAC power supply
2.
• = A as in standard model (no Ethernet port)
• = E as in built-in Ethernet communications interface
Analog Potentiometer on a Compact Base
The following figure shows the analog potentiometers on a TWDLC•A24DRF
Compact base.
Caption
Label
1
2
Description
Analog potentiometer 1
Analog potentiometer 2
35011387 06/2011
99
Description of Compact Bases
Functional Specifications for the Compact Bases
Introduction
This section provides functional specifications for the Compact bases.
Communication Function Specifications
Communication
Port
Standards
Maximum baud rate
Modbus communication
(RTU master/slave)
ASCII communication
Remote communication
Maximum cable length
Port 1 (RS485)
RS485
PC Link: 19,200 bps
Remote Link: 38,400 bps
Possible
Possible
Port 2 (RS232C)
Communication
Adapter:
TWDNAC232D
RS232
19,200 bps
Possible
Possible
Port 2 (RS485)
Communication
Adapters:
TWDNAC485D
TWDNAC485T
RS485
PC Link: 19,200 bps
Remote Link: 38,400 bps
Possible
Possible -
Ethernet Port (RJ45)
(TWDLCAE40DRF and TWDLCDE40DRF bases only)
100Base-TX, RJ45
100 Mbps, depending on network speed.
TCP/IP Modbus
Client/Server
7 links possible
Maximum distance between the base controller and the remote controller: 200 m (656 ft)
Not possible 7 links possible
Maximum distance between the base controller and the remote controller:
10 m (32.8 ft)
Not isolated
Maximum distance between the base controller and the remote controller: 200 m (656 ft)
Not isolated up to 16 remote nodes configured per base
Maximum distance between network nodes (depending on network architecture)
Isolated Isolation between internal circuit and communication port
Telephone communication
Not isolated
Possible
Possible to connect from a receive only modem.
Not possible Not possible Not possible
100 35011387 06/2011
Description of Compact Bases
Built-in Function Specifications
Sensor power supply
Counting
Analog potentiometers
Output voltage/current
Overload detection
Isolation
Number of channels
Frequency
Capacity
1 adjustable from 0 through to 1023 steps
1 adjustable from 0 through to 1023 steps
24 VDC (+10% to -15%), 250 mA max. current
(For TWDLCA•40DRF, 400 mA max. current)
(For TWDLCD•40DRF, 700 mA max. current)
Short-circuit protection for
TWDLCA•40DRF.
Short-circuit and overload protection for TWDLCD•40DRF.
Not available on all other bases.
Isolated from the internal circuit
4
For TWDLCA•40DRF and
TWDLCD•40DRF:
- 4 channels at 5kHz (FCi),
- 2 channels at 20kHz (VFCi)
For all other bases:
- 3 channels at 5kHz (FCi),
- 1 channel at 20kHz (VFCi)
16 bits (0..65535 steps)
32 bits (0..4294967295 steps)
FCi: Fast Counter "i".
VFCi: Very Fast Counter "i".
35011387 06/2011
101
Description of Compact Bases
3.3
Wiring Rules and Recommendations, and Wiring
Schematics for Compact Bases
Introduction
This section provides wiring rules and recommendations, and wiring schematics for
Compact bases.
What’s in this Section?
This section contains the following topics:
Topic
Wiring Rules and Recommendations for Compact Bases
Compact Base Wiring diagrams
Page
102 35011387 06/2011
Description of Compact Bases
Wiring Rules and Recommendations for Compact Bases
Introduction
There are several rules that must be followed when wiring a compact base.
Recommendations, when needed, are provided on how to comply with the rules.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z
Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
WARNING
MALFUNCTION OF OUTPUTS
Use appropriate interlocks where personal and/or equipment hazards exist.
Outputs can malfunction and remain ON or OFF.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Rules
35011387 06/2011 z z z z
Each terminal accepts up to two 18 AWG (0.82 mm
2
) through 28 AWG (0.08 mm
2
) fitted with cable ends or tags.
The power supply wire should be between 18 AWG (0.82 mm
2
) and 22 AWG
(0.33 mm
2
). Use the shortest wire length possible.
The grounding wire should be 16 AWG (1.30 mm
2
).
Power supply wires routed inside the panel must be kept separate from power wires, I/O wiring and communication wiring. Route wiring in separate cable ducting.
103
Description of Compact Bases z z
Verify that the operating conditions and environments are within the specification values.
Use proper wire size to meet voltage and current requirements.
Terminal Tightening Torque
Recommended tightening torque of terminal blocks is listed for all products on the product label.
Input Operating Range
The input operating range of the Type 1 (IEC 61131-2) input module is shown below.
Input Internal Circuit
The input internal circuit is shown below.
104 35011387 06/2011
Description of Compact Bases
Contact Protection Circuit for Relay and Transistor Outputs
Depending on the load, a protection circuit may be needed for the relay output on the bases. Choose a protection circuit, from the following diagrams, according to the power supply. Connect the protection circuit to the outside of the base or relay output module.
Protective circuit A: this protection circuit can be used when the load impedance is smaller than the RC impedance in an AC load power circuit.
z z
C represents a value from 0.1 to 1 μ F.
R represents a resistor of approximately the same resistance value as the load.
Protective circuit B: this protection circuit can be used for both AC and DC load power circuits.
z z
C represents a value from 0.1 to 1 μ F.
R represents a resistor of approximately the same resistance value as the load.
Protective circuit C: this protection circuit can be used for DC load power circuits.
35011387 06/2011 z z
Use a diode with the following ratings:
Reverse withstand voltage: power voltage of the load circuit x 10.
Forward current: more than the load current.
105
Description of Compact Bases
Protective circuit D: this protection circuit can be used for both AC and DC load power circuits.
Explanation of Source Inputs/Sink Outputs
NOTE: Sink corresponds to the sensors’ common on the (+) terminal of the power supply.
Input side COM field terminal connects to the "-" terminal or common of the field power supply. Output side COM field terminal connects to +24V field power supply.
Explanation of Sink Inputs/Source Outputs
NOTE: Source corresponds to the sensors’ common on the (-) terminal of the power supply.
106
Input side COM field terminal connects to +24V field power supply. Output side COM field terminal connects to the "-" terminal or common of the field power supply.
35011387 06/2011
Description of Compact Bases
Compact Base Wiring diagrams
Introduction
This section shows examples of wiring diagrams for Compact bases. Symbols used in the following diagrams are explained in the Glossary of Symbols
in the appendix.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z
Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
CAUTION z z
RISK OF REVERSE-POLARITY DAMAGE AT TRANSISTOR OUTPUTS
Observe the polarity markings on the transistor output terminals.
Use of a reverse polarity can permanently damage or destroy the output circuits.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: These diagrams are for external wiring only.
NOTE: The shaded boxes are markings on the base. The I and Q numbers are the input and output points.
35011387 06/2011
107
Description of Compact Bases
AC Power Supply Wiring Diagram
The following AC power supply wiring diagram is for the TWDLCA•••DRF series controllers.
DC Power Supply Wiring Diagram
The following DC power supply wiring diagram is for the TWDLCD•••DRF series bases.
DC Source Input Wiring Diagram
The following diagram is for the TWDLC•A10DRF, TWDLC•A16DRF, and
TWDLC•A24DRF bases (external power).
The following schematic is for the TWDLC•A10DRF, TWDLC•A16DRF, and
TWDLC•A24DRF bases (internal power).
z
Max current: 250mA.
108 35011387 06/2011
Description of Compact Bases
The following DC source input wiring diagram is for the TWDLC••40DRF series bases (external power).
The following DC source input wiring diagram is for the TWDLC••40DRF series bases (internal power).
z
Max current: 400mA.
DC Sink Input Wiring Diagram
This wiring diagram is for the TWDLC•A10DRF, TWDLC•A16DRF, and
TWDLC•A24DRF bases (external power).
This wiring diagram is for the TWDLC•A10DRF, TWDLC•A16DRF, and
TWDLC•A24DRF bases (internal power).
z
Max current: 250mA.
The following DC sink input wiring diagram is for the TWDLC••40DRF series controllers (external power).
35011387 06/2011
109
Description of Compact Bases
The following DC sink input wiring diagram is for the TWDLC••40DRF series controllers (internal power).
z
Max current: 400mA.
Relay and Transistor Output Wiring Diagram
This wiring diagram is the protection for inductive load:
This wiring diagram is for the TWDLC•A10DRF series bases.
This wiring diagram is for the TWDLC•A16DRF series bases.
This wiring diagram is for the TWDLC•A24DRF series bases.
110 35011387 06/2011
Description of Compact Bases
This wiring diagram is for the TWDLC••40DRF series bases.
Reverse-Polarity at Transistor Output is Not Allowed
The TWDLC••40DRF compact bases transistor outputs cannot withstand any reverse polarity.
35011387 06/2011
111
Description of Compact Bases
3.4
Compact Bases Options
Introduction
This section provides information about memory cartridges, RTC cartridges, operator display modules and input simulators as options for Compact bases.
What’s in this Section?
This section contains the following topics:
Topic
Memory Cartridges
Real Time Clock (RTC) Cartridge
Operator Display Modules
Input Simulators
Page
112 35011387 06/2011
Description of Compact Bases
Memory Cartridges
Introduction
The following section provides an overview and specifications about the
TWDXCPMFK32 and TWDXCPMFK64 memory cartridges, as options for the
Compact bases.
Overview of the Memory Cartridges
There are two optional memory cartridges, 32 KB (TWDXCPMFK32) and 64 KB
(TWDXCPMFK64), available. The memory cartridges provide additional memory for application storage. The memory cartridges are used to: z z z
Provide a removable backup of the application.
Load an application into a compact base if certain conditions exist.
Increase the program memory capacity.
The following table presents the available memory cartridge for each compact base.
Memory Cartridge
TWDXCPMFK32
TWDXCPMFK64
Compact 10 I/O yes no
Compact 16 I/O yes no
Compact 24 I/O yes no
Compact 40 I/O yes yes
The TWDXCPMFK32 memory cartridge is for back up only. The TWDXCPMFK64 memory cartridge is for back up and expansion.
Memory Cartridge Specifications
The following table describes the memory cartridge specifications.
Memory Type
Accessible memory capacity
Hardware for storing data
Software for storing data
Quantity of stored programs
Program execution priority
EEPROM
32 KB: TWDXCPMFK32
64 KB: TWDXCPMFK64
Twido base
TwidoSuite
One user program is stored on one memory cartridge.
When a memory cartridge is installed and enabled, the external user program will be loaded and executed if it differs from the internal program.
35011387 06/2011
113
Description of Compact Bases
Real Time Clock (RTC) Cartridge
Introduction
This section provides an overview and specifications for the TWDXCPRTC RTC cartridge, as an option for Compact bases.
Overview of the Real Time Clock (RTC) Cartridge
An optional Real Time Clock cartridge (TWDXCPRTC) is available for all compact bases. (Note that 40 I/O compact bases have RTC onboard)
The Real Time Clock cartridge provides the compact base with the current time and date.
The RTC is required for the Schedule Blocks to operate.
When the compact base is powered down, the Real Time Clock (RTC) will keep time for 1000 hours at 25 ° C (77 ° F) or 300 hours at 55 ° C (131 ° F) when using a fully charged battery.
Real Time Clock Cartridge Specifications
The following table describes the Real Time Clock cartridge specifications.
Accuracy
Backup duration
Battery
Charging time
Replaceable
30 s/month (typical) at 25 ° C (77 ° F)
Approximately 30 days (typical) at 25 ° C (77 ° F) after backup battery fully charged
Lithium secondary battery
Approximately 10 hours for charging from 0% to 90% of full charge
Not possible
114 35011387 06/2011
Description of Compact Bases
Operator Display Modules
Introduction
The following section provides an overview of the TWDXCPODC operator display module. This section also describes the parts, specifications and dimensions of the
TWDXCPODC operator display module
Overview
The operator display is an optional module that can be added to any of the compact bases. It is installed into a Compact base as an operator display module
(TWDXCPODC). See
How to Install the Operator Display Module, page 54
.
The operator display provides the following services: z z
Displays the controller state information
Allows the user to control the base z
Allows the user to monitor and tune application data objects
The operator display has two states: z z
Display state - Displays data
Edit state - Allows the user to change data
Parts Description of an Operator Display Module
The following figure shows the parts of the TWDXCPODC operator display module.
Caption
35011387 06/2011
Label Part
1 Display screen
2 ESC button
3 Up arrow button
Description
Shows menus, operands, and data.
In Edit state - Returns to the previous display state and rejects changes made by the user.
In Edit state - Changes the current edit element to the next value.
115
Description of Compact Bases
Label Part
4 Right arrow button
5 MOD/ENTER button
Description
In Display state - Advances to the next display state.
In Edit state - Advances to the next editing element. The current editing element blinks.
In Display state - Works in MOD function, goes to the corresponding edit state.
In Edit state - Works in ENTER function, returns to previous display state and accepts changes made by the user.
Connects to the Compact base.
6 Operator display connector
Operator Display Module Dimensions
The following diagram shows the dimensions for the operator display module
(TWDXCPODC).
Operator Display Module Specifications
The following table describes the operator display module specifications.
Part Number
Power voltage
Internal current draw
Weight
TWDXCPODC
5 VDC (supplied from the base)
200 mA DC
20 g (0.7 oz)
116 35011387 06/2011
Description of Compact Bases
Input Simulators
Introduction
The following section provides an overview of the TWDXSM6, TWDXSM9, and
TWDXSM14 input simulators for compact bases.
Overview of the Input Simulators
There are three input simulators: 6, 9, and 14 point. These are used only on the three
Compact bases. Used for debugging, you can control the inputs to test your application logic.
35011387 06/2011
117
Description of Compact Bases
118 35011387 06/2011
Twido Programmable Controllers
Description of Modular Bases
35011387 06/2011
Description of Modular Bases
4
Introduction
This chapter provides overviews, parts descriptions, specifications, wiring rules and recommendations, wiring schematics, and options for the Modular bases.
What’s in this Chapter?
This chapter contains the following sections:
4.1
Section
4.2
4.3
4.4
Topic
Modular Bases Description
Modular Bases Specifications
Modular Bases Wiring
Modular Bases Options
Page
119
35011387 06/2011
Description of Modular Bases
4.1
Modular Bases Description
Introduction
This section provides an overview and a parts description of the Modular bases.
What’s in this Section?
This section contains the following topics:
Overview of Modular Controllers
Parts Description of a Modular Base
Topic Page
120 35011387 06/2011
Description of Modular Bases
Overview of Modular Controllers
Introduction
The information in this section describes the main features of the Modular bases.
Modular Bases Features Overview
The following table gives information about the main features of the different types of Modular bases:
Features 20 I/O bases:
TWDLMDA20DTK
TWDLMDA20DUK
Inputs
Outputs
12 discrete inputs
8 transistor source outputs:
TWDLMDA20DTK
8 transistor sink outputs:
TWDLMDA20DUK
1 Analog Voltage Input
Connector
Analog Potentiometers 1
Integrated Serial Port
Wiring
√
Connector
RTC cartridge (optional) √
Memory cartridge
(optional)
32 KB / 64 KB
Expansion I/O Modules up to 4 modules
AS-I V2 bus Modules up to 2 modules
√ CANopen fieldbus
Module
Operator Display
Expansion Module
(optional)
√
Communication
Expansion Module
(optional)
Ethernet interface
√
1 ConneXium TwidoPort module
20 I/O bases:
TWDLMDA20DRT
12 discrete inputs
6 relay outputs + 2 transistor source outputs
1
1
√
Terminal Block
√
32 KB / 64 KB up to 7 modules up to 2 modules
√
√
√
1 ConneXium TwidoPort module
40 I/O bases:
TWDLMDA40DTK
TWDLMDA40DUK
24 discrete inputs
16 transistor source outputs:
TWDLMDA40DTK
16 transistor sink outputs:
TWDLMDA40DUK
1
1
√
Connector
√
32 KB / 64 KB up to 7 modules up to 2 modules
√
√
√
1 ConneXium TwidoPort module
35011387 06/2011
121
Description of Modular Bases
Illustrations
The following illustrations are the Modular bases:
Illustration
122 35011387 06/2011
Description of Modular Bases
Parts Description of a Modular Base
Introduction
The following section describes the parts of a Modular base. Your base may differ from the illustrations but the parts will be the same.
Parts Description of a Modular Base
The following figure shows the parts of a Modular base. This figure shows the
Modular 40 I/O base.
Caption
6
7
8
9
10
3
4
5
Label
1
2
Description
Hinged lid
Expansion connector
Analog potentiometer
Serial port 1
Cartridge covers
24 VDC power supply terminals
Analog voltage input connector
LEDs
I/O terminals
Communication connector
35011387 06/2011
123
Description of Modular Bases
4.2
Modular Bases Specifications
Introduction
This section provides general specifications, electrical specifications, inputs and outputs specifications, analog potentiometers description, analog voltage input overview, and functional specifications for Modular bases.
What’s in this Section?
This section contains the following topics:
Topic
General Specifications for the Modular Bases
Electrical Specifications for the Modular Bases
Input Specifications for the Modular Bases
Relay Output Specifications for the Modular Bases
Transistor Output Specifications for the Modular bases
Description of Analog Potentiometers
Overview of Analog Voltage Input
Functional Specifications for the Modular Bases
Page
124 35011387 06/2011
Description of Modular Bases
General Specifications for the Modular Bases
Introduction
This section provides general specifications for the Modular bases.
Normal Operating Specifications
Modular base
Operating temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Corrosion immunity
Altitude
Resistance to Vibration
Impact strength
Weight
TWDLMDA20DTK
TWDLMDA20DUK
TWDLMDA20DRT TWDLMDA40DTK
TWDLMDA40DUK
0 to 55 ° C (32 ° F to 131 ° F) operating ambient temperature
-25 ° C to +70 ° C (-13 ° F to 158 ° F) from 30 to 95% Rh (non-condensing)
2 (IEC60664)
IP20
Free from corrosive gases
Operation: from 0 to 2000 m (0 to 6,560 ft)
Transport: 0 to 3,000 m (0 to 9,840 ft)
When mounted on a DIN rail: from 10 to 57 Hz amplitude 0.075 mm, from 57 to 150 Hz acceleration 9.8 ms
2
(1G), 2 hours per axis on each of three mutually perpendicular axes.
When mounted on a panel surface: from 2 to 25 Hz amplitude 1.6 mm, from 25 to 100 Hz acceleration 39.2 ms
2
(4G)
Lloyd’s 90 min per axis on each of three mutually perpendicular axes.
147 ms 2 (15G), 11 ms duration, 3 shocks per axis, on three mutually perpendicular axes (IEC 61131).
140 g
(4.93 oz)
185 g
(6.52 oz)
180 g
(6.35 oz)
Specifications for the Backup Battery
Modular backed up elements
Time
Battery type
Charging time
Service life
Internal RAM: internal variables, internal bits and words, timers, counters, shift registers, etc.
Approximately 30 days at 25 ° C (77 ° F) after battery fully charged.
Non-interchangeable lithium accumulator
Approximately 15 hours for 0% to 90 % of total load
10 years
35011387 06/2011
125
Description of Modular Bases
Electrical Specifications for the Modular Bases
Introduction
This section provides electrical specifications for the Modular bases.
Electrical Specifications
Modular base
Rated power voltage
Allowable voltage range
Maximum input power
Allowable momentary power interruption
Dielectric strength
Insulation resistance
Electromagnetic resistance
Inrush current
Ground wiring
Power supply wiring
Effect of improper power supply connection
TWDLMDA20DTK
TWDLMDA20DUK
TWDLMDA20DRT
24 VDC from 20.4 to 26.4 VDC (including ripple)
TWDLMDA40DTK
TWDLMDA40DUK
Base plus 4 I/O Modules Base plus 7 I/O Modules
15 W (26.4 VDC) 19 W (26.4 VDC)
10 ms, 100% drop out (at the rated inputs and outputs)
(IEC61131 and IEC61000-4-11)
19 W (26.4 VDC)
Between power and ground terminals: 500 VAC, 1 min
Between I/O and ground terminals: 1500 VAC, 1 min
Between power and ground terminals: 10 M Ω minimum
(500 VDC)
Between I/O and ground terminals: 10 M Ω minimum
(500 VDC)
AC power terminals: 2kV, Level 3
DC power terminals: 2kV, Level 3
I/O terminals:
- DC: 1kV, Level 3
- AC: 2kV, Level 4
According to IEC61131-2 (Zone B) and IEC61000-4-4
50 A maximum (24 VDC)
UL1015 22 AWG (0.33 mm
2
), UL1007 18 AWG (0.82 mm
2
)
UL1015 22 AWG (0.33 mm
2
), UL1007 18 AWG (0.82 mm
2
)
Reverse polarity: no operation, no damage
Improper voltage or frequency: internal fuse protection
126 35011387 06/2011
Description of Modular Bases
Input Specifications for the Modular Bases
Introduction
This section provides Input specifications for the Modular bases.
DC Input Specifications
WARNING
UNINTENDED EQUIPMENT OPERATION
If any input exceeding the rated value is applied, permanent damage may be caused.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Modular base
Input points
Rated input voltage
Input voltage range
Rated input current
Input impedance
Turn on time
(ON Time)
Turn off time
(OFF Time)
Isolation
Filtering (3 possibilities: none, 3 ms or 12 ms.)
Input type
External load for I/O interconnection
Signal determination method
Input signals type
TWDLMDA20DUK
TWDLMDA20DTK
12 points in 1 common line
TWDLMDA20DRT
12 points in 1 common line
24 VDC source/sink input signal from 20.4 to 26.4 VDC
TWDLMDA40DUK
TWDLMDA40DTK
24 points in 1 common line
I0, I1, I6, I7: 5 mA/input (24 VDC)
I2 to I5, I8 to I23: 7 mA/input (24 VDC)
I0, I1, I6, I7: 5.7 k Ω
I2 to I5, I8 to I23: 3.4 k Ω
I0 to I7: 35 μ s + filter value
I8 to I23: 40 μ s + filter value
I0, I1, I6, I7: 45 μ s + filter value
I2 to I5, I8 to I23: 150 μ s + filter value
Between input terminals and internal circuit: photocoupler isolated (isolation protection up to 500 V)
Between input terminals: not isolated
I0 to I11 I0 to I11 I0 to I7
Type 1 (IEC 61131)
Not needed
Static
The input signals can be both sink and source.
35011387 06/2011
127
Description of Modular Bases
Modular base
Cable length
Connector insertion/removal durability
I/O Usage Limits
TWDLMDA20DUK
TWDLMDA20DTK
TWDLMDA20DRT TWDLMDA40DUK
TWDLMDA40DTK
3m (9.84 ft) for compliance with electromagnetic immunity
100 times minimum
When using TWDLMDA20DUK and TWDLMDA20DTK at an ambient temperature of 55 ° C (131 ° F) in the normal mounting direction, limit the inputs and outputs, respectively, which turn on simultaneously along line (1).
When using TWDLMDA40DUK and TWDLMDA40DTK limit the inputs and outputs, respectively, which turn on simultaneously along line (2).
At 40 ° C (104 ° F), all inputs and outputs can be turned on simultaneously at 26.4 VDC as indicated with line (3).
When using the TWDLMDA20DRT controller, all inputs and outputs can be turned on simultaneously at 55 ° C (131 ° F), input voltage 26.4 VDC.
Transistor Sink and Source Output Specifications
Modular controller
TWDLMDA...
Output type
Output points per common Line
20DUK
Sink
8
40DUK
Sink
2
Rated load voltage 24 VDC
Maximum load current
1 A per common line
Operating load voltage range from 20.4 to 28.8 VDC
20DRT
Source
2
20DTK
Source
8
40DTK
Source
16
128 35011387 06/2011
Description of Modular Bases
Modular controller
TWDLMDA...
Voltage drop (on voltage)
20DUK 40DUK 20DRT 20DTK 40DTK
1 V maximum (voltage between COM and output terminals when output is on)
Rated load current 0.3 A per output
Inrush current 1 A maximum
Leakage current
Clamping voltage
Maximum lamp load 8 W
Inductive load L/R = 10 ms (28.8 VDC, 1 Hz)
External current draw
0.1 mA maximum
39 V +/-1 V
Isolation
100 mA maximum, 24 VDC
(power voltage at the +V terminal)
100 mA maximum, 24 VDC
(power voltage at the -V terminal)
Between output terminal and internal circuit: photocoupler isolated
(isolation protection up to 500 V)
Between output terminals: not isolated
100 times minimum Average number of connector insertions/removals
Output delay - turn on/off time
Q0, Q1: 5 μ s maximum
Q2 to Q15: 300 μ s maximum
Relay Output Specifications
Modular controller
Number of outputs
TWDLMDA20DRT
8 discrete inputs consisting of 6 relay outputs and
2 transistor source outputs
Output points per common line - COM0 2 outputs
Output points per common line - COM1 3 NO contacts
Output points per common line - COM2 2 NO contacts
Output points per common line - COM3 1 NO contact
Maximum load current 2 A per output
8 A per common line
Minimum switching load 0.1 mA/0.1 VDC (reference value)
Initial contact resistance
Mechanical life
30 m Ω maximum
20,000,000 operations minimum (no load 18,000 operations/h)
35011387 06/2011
129
Description of Modular Bases
Modular controller
Dielectric strength
TWDLMDA20DRT
Between output to internal circuit: 1500 VAC,
1 min
Between output groups: 1500 VAC, 1 min
Connector insertion/removal durability 100 times minimum
Usage category Rated load Electrical life (number of operations)
AC1
Resistive load command
AC14
Weak solenoid load
AC15
Solenoid
DC1
Resistive load command
DC13
Solenoid L/R=150ms
500 VA(*)
250 VA
200 VA
60 W(*)
30 W
(*) for AC1 & DC1 the outputs indicated here take the maximum per point on Twido
(2A) into account.
Output delay
The output delay is shown below.
130 35011387 06/2011
Relay Output Contact
The relay output contact is shown below.
Description of Modular Bases
Transistor Source Output Contact
The transistor source output contact is shown below.
Transistor Sink Output Contact
The transistor sink output contact is shown below.
35011387 06/2011
131
Description of Modular Bases
Relay Output Specifications for the Modular Bases
Introduction
This section provides Relay output specifications for the Modular bases.
Relay Output Specifications
Modular base
Number of outputs
Output points per common line - COM0
Output points per common line - COM1
Output points per common line - COM2
Output points per common line - COM3
Maximum load current
Minimum switching load
Initial contact resistance
Mechanical life
Dielectric strength
Connector insertion/removal durability
TWDLMDA20DRT
8 discrete inputs consisting of 6 relay outputs and 2 transistor source outputs
2 outputs
3 NO contacts
2 NO contacts
1 NO contact
2 A per output
8 A per common line
0.1 mA/0.1 VDC (reference value)
30 m Ω maximum
20,000,000 operations minimum (no load 18,000 operations/h)
Between output to internal circuit: 1500 VAC,
1 min
Between output groups: 1500 VAC, 1 min
100 times minimum
Usage category
AC1
Resistive load command
AC14
Weak solenoid load
AC15
Solenoid
DC1
Resistive load command
DC13
Solenoid L/R=150ms
Rated load
500 VA(*)
250 VA
200 VA
60 W(*)
30 W
Electrical life (number of operations)
(*) for AC1 & DC1 the outputs indicated here take the maximum per point on
TwidoSuite (2A) into account.
132 35011387 06/2011
Output delay
The output delay is shown below.
Description of Modular Bases
Relay Output Contact
The relay output contact is shown below.
35011387 06/2011
133
Description of Modular Bases
Transistor Output Specifications for the Modular bases
Introduction
This section provides Transistor output specifications for the Modular bases.
Transistor Sink and Source Output Specifications
Modular controller
TWDLMDA...
Output type
Output points per common
Line
20DUK
Sink output
8
40DUK
Sink output
2
20DRT
Source output
2
20DTK
Source output
8
40DTK
Source output
16
Rated load voltage
Maximum load current
24 VDC
1 A per common line
Operating load voltage range from 20.4 to 28.8 VDC
Voltage drop (on voltage) 1 V maximum (voltage between COM and output terminals when output is on)
Rated load current
Inrush current
Leakage current
Clamping voltage
Maximum lamp load
Inductive load
0.3 A per output
1 A maximum
0.1 mA maximum
39 V +/-1 V
8 W
L/R = 10 ms (28.8 VDC, 1 Hz)
External current draw
Isolation
100 mA maximum, 24 VDC
(power voltage at the +V terminal)
100 mA maximum, 24 VDC
(power voltage at the -V terminal)
Between output terminal and internal circuit: photocoupler isolated (isolation protection up to 500 V)
Between output terminals: not isolated
100 times minimum Average number of connector insertions/removals
Output delay - turn on time
Output delay - turn off time
Q0, Q1: 5 μ s maximum
Q2 to Q15: 300 μ s maximum
Q0, Q1: 5 μ s maximum
Q2 to Q15: 300 μ s maximum
134 35011387 06/2011
Transistor Source Output Contact
The transistor source output contact is shown below.
Description of Modular Bases
Transistor Sink Output Contact
The transistor sink output contact is shown below.
35011387 06/2011
135
Description of Modular Bases
Description of Analog Potentiometers
Introduction
The following section describes the analog potentiometer on the Modular bases.
Description
The TWDLMDA20DUK, TWDLMADA20DTK, TWDLMDA20DRT,
TWDLMDA40DUK, and TWDLMADA40DTK bases have one analog potentiometer.
The analog potentiometer can be set to a value between 0 and 1023. The value is stored in a system words and is updated in every scan. For more information on setting the analog potentiometer, see the TwidoSuite Software Reference Manual.
Analog Potentiometer on a Modular Base
The following figure shows the analog potentiometer on a Modular base, the
TWDLMDA40DUK.
Caption
Label
1
Description
Analog potentiometer 1
136 35011387 06/2011
Description of Modular Bases
Overview of Analog Voltage Input
Introduction
The following section describes the analog voltage input on the Modular bases.
Description
All Modular bases have one analog voltage input. The analog voltage input connects an analog voltage source of 0 through 10 VDC. The analog voltage is converted to a value of 0 through 1023 and is stored in a system word.
35011387 06/2011
137
Description of Modular Bases
Functional Specifications for the Modular Bases
Introduction
This section provides functional specifications for the Modular bases.
Communication Function Specifications
Communication
Port
Possible
Possible to connect from a receive only modem.
Port 2 (RS232C)
Communication Expansion
Module (TWDNOZ232D) or
Operator Display Expansion
Module (TWDXCPODM) with Communication
Adapter (TWDNAC232D)
Port 2 (RS485)
Communication
Expansion Modules
(TWDNOZ485D) or
(TWDNOZ485T) or
Operator Display
Expansion Module
(TWDXCPODM) with Communication
Adapter (TWDNAC485D) or (TWDNAC485T)
RS485
PC Link: 19,200 bps
Remote Link: 38,400 bps
Possible
Standards RS485
Maximum baud rate PC Link: 19,200 bps
Remote Link: 38,400 bps
Possible Modbus communication
(RTU master/slave)
ASCII communication
Remote communication
Maximum cable length
Possible
7 links possible
Maximum distance between the base controller and the remote controller: 200 m (656 ft)
Not isolated
RS232
19,200 bps
Possible
Possible
Not possible
Maximum distance between the base controller and the remote controller: 200 m (656 ft)
Not isolated
Possible
7 links possible
Maximum distance between the base controller and the remote controller: 200 m (656 ft)
Not isolated Isolation between internal circuit and communication port
Telephone communication
Port 1 (RS485)
Not possible Not possible
138 35011387 06/2011
Built-in Function Specifications
Analog voltage input
Movement
Counting
Analog potentiometers
FCi = Fast Counter "i"
VFCi = Very Fast Counter "i"
Description of Modular Bases
Number of channels
Input voltage range
Input impedance
Resolution
Input tolerance
Sample duration time
Sample repeat time
Total input transfer time
1 from 0 to 10 VDC
100 k Ω
9 bits (0 to 1023 steps)
+/- 5%
5 ms
5 ms
5 ms + 1 cycle time
Number of channels
Frequency
Functions
2
7 kHz
PWM - Pulse Width
Modulation output
PLS - Pulse generator output
Number of channels
Frequency
4
2 channels at 5kHz (FCi),
2 channels at 20kHz (VFCi)
Capacity 16 bits (0..65535 steps)
1 adjustable from 0 through to 1023 steps
35011387 06/2011
139
Description of Modular Bases
4.3
Modular Bases Wiring
Introduction
This section provides wiring rules and recommendations, and wiring schematics for
Modular bases.
What’s in this Section?
This section contains the following topics:
Topic
Wiring Rules and Recommendations
Modular Base Wiring Diagrams
Page
140 35011387 06/2011
Description of Modular Bases
Wiring Rules and Recommendations
Introduction
There are several rules that must be followed when wiring a controller or module.
Recommendations, when needed, are provided on how to comply with the rules.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z
Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
WARNING
MALFUNCTION OF OUTPUTS
Use appropriate safety interlocks where personal and/or equipment hazards exist.
Outputs can malfunction and remain ON or OFF.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Rules
35011387 06/2011 z z z z
Each terminal accepts up to two 18 AWG (0.82 mm
2
) through 28 AWG (0.08 mm
2
) fitted with cable ends or tags.
Output module fusing is the responsibility of the user. It is not within the Twido product itself. Select a fuse appropriate for the load with respect to the electrical codes.
Depending on the load, a protection circuit may be needed for relay outputs on modules.
The power supply wire should be between 18 AWG (0.82 mm 2 ) and 22 AWG
(0.33 mm 2 ). Use the shortest wire length possible.
141
Description of Modular Bases z z z z z
The grounding wire should be 16 AWG (1.30 mm
2
).
Power supply wires routed inside the panel must be kept separate from power wires, I/O wiring and communication wiring. Route wiring in separate cable ducting.
Take care when wiring output modules that are designed to work as either source or sink. Incorrect wiring can cause equipment damage.
Verify that the operating conditions and environments are within the specification values.
Use proper wire size to meet voltage and current requirements.
Terminal Tightening Torque
Recommended tightening torque of terminal blocks is listed for all products on the product label.
Contact Protection Circuit for Relay and Transistor Outputs
CAUTION
OUTPUT CIRCUIT DAMAGE DUE TO INDUCTIVE LOADS
Use one of the following protective circuits to reduce the risk of inductive load damage.
Failure to follow these instructions can result in injury or equipment damage.
Depending on the load, a protection circuit may be needed for the relay output on the controllers and certain modules. Choose a protection circuit, from the following diagrams, according to the power supply. Connect the protection circuit to the outside of the controller or relay output module.
Protective circuit A: this protection circuit can be used when the load impedance is smaller than the RC impedance in an AC load power circuit.
142 z z
C represents a value from 0.1 to 1 μ F.
R represents a resistor of approximately the same resistance value as the load.
35011387 06/2011
35011387 06/2011
Description of Modular Bases
Protective circuit B: this protection circuit can be used for both AC and DC load power circuits.
z z
C represents a value from 0.1 to 1 μ F.
R represents a resistor of approximately the same resistance value as the load.
Protective circuit C: this protection circuit can be used for DC load power circuits.
z z
Use a diode with the following ratings:
Reverse withstand voltage: power voltage of the load circuit x 10.
Forward current: more than the load current.
Protective circuit D: this protection circuit can be used for both AC and DC load power circuits.
143
Description of Modular Bases
Explanation of Source Inputs/Sink Outputs
NOTE: Sink corresponds to the sensors’ common on the (+) terminal of the power supply.
Input side COM field terminal connects to the "-" terminal or common of the field power supply. Output side COM field terminal connects to +24V field power supply.
Explanation of Sink Inputs/Source Outputs
NOTE: Source corresponds to the sensors’ common on the (-) terminal of the power supply.
Input side COM field terminal connects to +24V field power supply. Output side COM field terminal connects to the "-" terminal or common of the field power supply.
144 35011387 06/2011
Description of Modular Bases
Modular Base Wiring Diagrams
Introduction
This section shows examples of wiring diagrams for the Modular bases. Symbols used in the following diagrams are explained in the Glossary of Symbols
in the appendix.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH z z z z
Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
CAUTION z z
RISK OF REVERSE-POLARITY DAMAGE AT TRANSISTOR OUTPUTS
Make sure to conform to the polarity markings on the transistor output terminals.
Use of a reverse polarity can permanently damage or destroy the output circuits.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: These diagrams are for external wiring only.
NOTE: The shaded boxes are markings on the base. The I and Q numbers are the input and output points.
35011387 06/2011
145
Description of Modular Bases
DC Power Supply Wiring z z
Make the power supply wiring as short as possible.
Connnect functional earth as close as possible to plate.
Fast Input/Output Wiring Rules
TWDLMDA20-DUK Wiring Diagram
This diagram is for the TWDLMDA20DUK base with connector.
146 z z z z z z
The COM(-) terminals are connected together internally.
The COM and COM(-) terminals are not connected together internally.
The +V terminals are connected together internally.
Connect an appropriate fuse for the load.
A is the positive logic.
B is the negative logic.
35011387 06/2011
Description of Modular Bases
TWDLMDA20-DTK Wiring Diagram
This diagram is for the TWDLMDA20DTK base with connector.
z z z z z z
The COM(+) terminals are connected together internally.
The COM and COM(+) terminals are not connected together internally.
The -V terminals are connected together internally.
Connect an appropriate fuse for the load.
A is the positive logic.
B is the negative logic.
TWDLMDA20-DRT Wiring Diagram
This diagram is for the TWDLMDA20DRT base with terminal block.
35011387 06/2011 z z z z z
Output points 0 and 1 are transistor source outputs, all other output points are relay.
The COM terminals are not connected together internally.
Connect an appropriate fuse for the load.
A is the positive logic.
B is the negative logic.
147
Description of Modular Bases
TWDLMDA40-DUK Wiring Diagram
This diagram is for the TWDLMDA40DUK base with connector.
148 z z z z z z z
The terminals on CN1 and CN2 are not connected together internally.
The COM(-) terminals are connected together internally.
The COM and COM(-) terminals are not connected together internally.
The +V terminals are connected together internally.
Connect an appropriate fuse for the load.
A is the positive logic.
B is the negative logic.
35011387 06/2011
Description of Modular Bases
TWDLMDA40-DTK Wiring Diagram
This diagram is for the TWDLMDA40DTK base with connector.
35011387 06/2011 z z z z z z z
The terminals on CN1 and CN2 are not connected together internally.
The COM(+) terminals are connected together internally.
The COM and COM(+) terminals are not connected together internally.
The -V terminals are connected together internally.
Connect an appropriate fuse for the load.
A is the positive logic.
B is the negative logic.
149
Description of Modular Bases
4.4
Modular Bases Options
Introduction
This section provides information about memory cartridges, RTC cartridges, and operator display modules for Modular bases.
What’s in this Section?
This section contains the following topics:
Topic
Memory Cartridges
Real Time Clock (RTC) Cartridge
Operator Display Expansion Modules
Page
150 35011387 06/2011
Description of Modular Bases
Memory Cartridges
Introduction
The following section provides an overview and specifications about the
TWDXCPMFK32 and TWDXCPMFK64 memory cartridges, as options for the
Modular bases.
Overview of the Memory Cartridges
There are two optional memory cartridges, 32 KB (TWDXCPMFK32) and 64 KB
(TWDXCPMFK64), available. The memory cartridges provide additional memory for application storage. The memory cartridges are used to: z z z
Provide a removable backup of the application.
Load an application into a modular base if certain conditions exist.
Increase the program memory capacity.
The following table presents the available memory cartridge for each type of modular base.
Memory Cartridge
TWDXCPMFK32
TWDXCPMFK64
20 I/O modular yes yes
40 I/O modular yes yes
The TWDXCPMFK32 memory cartridge is for back up only. The TWDXCPMFK64 memory cartridge is for back up and expansion.
Memory Cartridge Specifications
The following table describes the memory cartridge specifications.
Memory Type
Accessible memory capacity
Hardware for storing data
Software for storing data
Quantity of stored programs
Program execution priority
EEPROM
32 KB: TWDXCPMFK32
64 KB: TWDXCPMFK64
Twido base
TwidoSuite
One user program is stored on one memory cartridge.
When a memory cartridge is installed and enabled, the external user program will be loaded and executed if it differs from the internal program.
35011387 06/2011
151
Description of Modular Bases
Real Time Clock (RTC) Cartridge
Introduction
This section provides an overview and specifications for the TWDXCPRTC RTC cartridge, as an option for Modular bases.
Overview of the Real Time Clock (RTC) Cartridge
An optional Real Time Clock cartridge (TWDXCPRTC) is available for all types of modular bases.
The Real Time Clock cartridge provides the Modular base with the current time and date. The RTC is required for the Schedule Blocks to operate.
When the Modular base is powered down, the Real Time Clock (RTC) will keep time for 1000 hours at 25 ° C (77 ° F) or 300 hours at 55 ° C (131 ° F) when using a fully charged battery.
Real Time Clock Cartridge Specifications
The following table describes the Real Time Clock cartridge specifications.
Accuracy
Backup duration
Battery
Charging time
Replaceable
30 s/month (typical) at 25 ° C (77 ° F)
Approximately 30 days (typical) at 25 ° C (77 ° F) after backup battery fully charged
Lithium secondary battery
Approximately 10 hours for charging from 0% to 90% of full charge
Not possible
152 35011387 06/2011
Description of Modular Bases
Operator Display Expansion Modules
Introduction
The following section provides an overview of the TWDXCPODM operator display expansion module.
Overview
The operator display is an optional module that can be added to any of the modular bases. It is assembled to a Modular base using the operator display expansion module (TWDXCPODM). See
How to Install the Operator Display Module, page 54 .
The operator display provides the following services: z
Displays the base state information z z z
Allows the user to control the base
Allows the user to monitor and tune application data objects
The operator display has two states: z
Display state - Displays data
Edit state - Allows the user to change data
Parts Description of an Operator Display Expansion Module
The following figure shows the parts of the TWDXCPODM operator display expansion module.
35011387 06/2011
153
Description of Modular Bases
Caption
7
8
9
10
Label Part
1
2
3
4
5
6
Display screen
ESC button
Up arrow button
Description
Shows menus, operands, and data.
In Edit state - Returns to the previous display state and rejects changes made by the user.
In Edit state - Changes the current edit element to the next value.
Right arrow button
MOD/ENTER button
In Display state - Advances to the next display state.
In Edit state - Advances to the next editing element. The current editing element blinks.
In Display state - Works in MOD function, goes to the corresponding edit state.
In Edit state - Works in ENTER function, returns to previous display state and accepts changes made by the user.
Connects to a Modular base.
Operator display connector
Hinged door
Latch button
Opens to access the serial port 2.
Holds/releases the module from a base.
Clamp Secures the module to a DIN rail.
Serial port 2 connector Connects to the connector on an optional
TWDNAC232D, TWDNAC485D, or TWDNAC485T communication adapter.
Operator Display Expansion Module Specifications
The following table describes the operator display expansion module specifications.
Part Number
Weight
Internal current draw
TWDXCPODM
78 g (2.75 oz)
200 mA DC
154 35011387 06/2011
Description of Modular Bases
Operator Display Expansion Module Dimensions
The following diagram shows the dimensions for the operator display expansion module (TWDXCPODM).
NOTE: * 8.5 mm (0.33 in) when the clamp is pulled out.
35011387 06/2011
155
Description of Modular Bases
156 35011387 06/2011
Twido Programmable Controllers
Telefast Pre-Wired Systems for Twido
35011387 06/2011
Telefast® Pre-Wired Systems for
Twido
5
Introduction
This chapter provides an overview of the Telefast® pre-wired system for Twido,
Telefast® bases specifications, dimensions, and wiring schematics.
What’s in this Chapter?
This chapter contains the following topics:
Topic
Overview of the Telefast ® Pre-Wired System for Twido
Dimensions of the Telefast ® Bases
Specifications for the Telefast
®
Bases
Telefast
®
Bases Wiring Schematics
Wiring Specifications for the TeleFast Cables
Page
157
35011387 06/2011
Telefast Pre-Wired Systems for Twido
Overview of the Telefast
®
Pre-Wired System for Twido
Introduction
The following section provides an overview of the z
ABE 7B20MPN20, z
ABE 7B20MPN22, z
ABE 7B20MRM20, z z
ABE 7E16EPN20,
ABE 7E16SPN20, z z
ABE 7E16SPN22,
ABE 7E16SRM20 Telefast
®
pre-wired systems for Twido.
158 35011387 06/2011
Illustration
Telefast Pre-Wired Systems for Twido
The following illustration shows the Telefast
®
system for Twido:
Caption
35011387 06/2011
Telefast system parts shown in the previous illustration are listed below:
1.
Modular base controller with 26-way HE 10 connectors. The modular sizes available are 20 or 40 I/O.
2.
Input and output modules with 20-way HE 10 connectors. The modular sizes available are 16 or 32 I/O.
159
Telefast Pre-Wired Systems for Twido
3.
Cable (ABF T26B••0) equipped with a 26-way HE 10 connector at each end. This cable is available in 0.5, 1 and 2 meter lengths (AWG 28/0.08 mm
2
).
4.
Cable (ABF T20E••0) equipped with a 20-way HE 10 connector at each end. This cable is available in 0.5, 1, 2 and 3 meter lengths (AWG 28/0.08 mm
2
).
5.
20 channel sub-base (ABE 7B20MPN2• or ABE 7B20MR20) for modular base controllers.
6.
16 channel sub-base (ABE 7E16SPN22 or ABE 7E16SRM20) for output extension modules.
7.
16 channel sub-base (ABE 7E16EPN20 or ABE 7E16SPN20) for input or output extension modules.
Compatibility Table
The following table describes compatibility between Twido (modular bases and I/O modules) and Telefast
®
components (bases and cables):
160 35011387 06/2011
Telefast Pre-Wired Systems for Twido
Dimensions of the Telefast
®
Bases
Introduction
The following section shows the dimensions for the Telefast
®
bases.
ABE7B20MPN20 ABE7B20MPN22 ABE7B20MRM20 ABE7E16SPN22 ABE7E16SRM20
The following diagrams show the dimensions for the ABE7B20MPN20,
ABE7B20MPN22, ABE7B20MRM20, ABE7E16SPN22 and ABE7E16SRM20
Telefast
®
bases.
ABE7E16EPN20 ABE7E16SPN20
The following diagrams show the dimensions the dimensions for the
ABE7E16EPN20 and ABE7E16SPN20 Telefast
®
bases.
35011387 06/2011
161
Telefast Pre-Wired Systems for Twido
Specifications for the Telefast
®
Bases
Introduction
This section provides specifications for the Telefast
®
bases.
See Catalog 8501CT9801, "Advantys, TeleFast
®
pre-wired system for Twido" for more specifications on these Telefast
®
bases.
Supply Specifications (controller side)
The following table provides supply specifications on the Telefast
®
bases at controller side:
Control Circuit Specifications (sensor/controller side)
The following table provides specifications on the Telefast
®
bases control circuit (per channel) at sensor/controller side:
162 35011387 06/2011
Telefast Pre-Wired Systems for Twido
Output Circuit Specifications (preactuator side)
The following table provides specifications on the Telefast channel) at preactuator side:
®
bases output circuit (per
35011387 06/2011
163
Telefast Pre-Wired Systems for Twido
Telefast
®
Bases Wiring Schematics
Introduction
This section provides wiring schematics for the Telefast
®
bases.
WARNING
INTERNAL FUSE MAY NOT DEACTIVATE OUTPUTS
When multiple ABE7 modules are connected to a single PLC output source, module outputs may remain active after an internal fuse is removed or blown. To deactivate module outputs or to service the equipment, halt the PLC, disconnect all power and disconnect the HE10.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
ABE7B20MPN20
The following diagram provides specifications for the ABE7B20MPN20 Telefast
® base wiring.
164 35011387 06/2011
Telefast Pre-Wired Systems for Twido
ABE7B20MPN22
The following diagram provides specifications for the ABE7B20MPN22 Telefast
® base wiring.
35011387 06/2011
165
Telefast Pre-Wired Systems for Twido
ABE7B20MRM20
The following diagram provides specifications for the ABE7B20MRM20 Telefast
® base wiring.
166 35011387 06/2011
Telefast Pre-Wired Systems for Twido
ABE7E16EPN20
The following diagram provides specifications for the ABE7E16EPN20 Telefast
® base wiring.
35011387 06/2011
167
Telefast Pre-Wired Systems for Twido
ABE7E16SPN20
The following diagram provides specifications for the ABE7E16SPN20 Telefast
® base wiring.
168 35011387 06/2011
Telefast Pre-Wired Systems for Twido
ABE7E16SPN22
The following diagram provides specifications for the ABE7E16SPN22 Telefast
® base wiring.
35011387 06/2011
169
Telefast Pre-Wired Systems for Twido
ABE7E16SRM20
The following diagram provides specifications for the ABE7E16SRM20 Telefast
® base wiring.
170 35011387 06/2011
Telefast Pre-Wired Systems for Twido
Wiring Specifications for the TeleFast Cables
Introduction
This section provides cable wiring specifications for the TWDFCW30K/50K and
TWDFCW30M/50M TeleFast cables that connect to Twido controllers discrete I/Os.
TWDFCW30K/50K
The following table provides specifications for the TWDFCW30K/50K with free wires for 20-pin Modular controller.
15
16
17
18
19
20
11
12
13
14
7
8
9
10
5
6
3
4
1
2
Pin Connector A
Twido Connector Side
Wire Color
White
Brown
Green
Yellow
Gray
Pink
Blue
Red
Black
Violet
Gray/Pink
Red/Blue
White/Green
Brown/Green
White/Yellow
Yellow/Brown
White/Gray
Gray/Brown
White/Pink
Pink/Brown
35011387 06/2011
171
Telefast Pre-Wired Systems for Twido
Illustration
Illustration of a TWDFCW30K cable:
TWDFCW30M/50M
The following table provides specifications for the TWDFCW30M/50M cable with free wires for 26-pin Modular controller.
15
13
11
9
23
21
19
17
6
4
2
25
14
12
10
8
22
20
18
16
Pin Connector A
Twido Connector Side
26
24
Wire Color for Input
Brown/Black
Brown/Red
Brown/Blue
Pink/Brown
Gray/Brown
Yellow/Brown
Brown/Green
Red/Blue
Violet
Red
Pink
Yellow
Brown
Wire Color for Output
White/Black
White/Red
White/Blue
White/Pink
White/Gray
White/Yellow
White/Green
Gray/Pink
No Connect
172 35011387 06/2011
Illustration
3
1
7
5
Pin Connector A
Twido Connector Side
Wire Color for Input
Telefast Pre-Wired Systems for Twido
Wire Color for Output
Blue
Gray
Green
White
Illustration of a TWDFCW30M cable:
35011387 06/2011
173
Telefast Pre-Wired Systems for Twido
174 35011387 06/2011
Twido Programmable Controllers
Controller Operation
35011387 06/2011
Controller Operation
6
Introduction
This chapter provides information about dedicated I/O and the controller operating modes.
What’s in this Chapter?
This chapter contains the following sections:
6.1
Section
6.2
Dedicated I/Os
Controller Operating Modes
Topic Page
175
35011387 06/2011
Controller Operation
6.1
Dedicated I/Os
Introduction
This section provides information about I/O assignments and capabilities for the
RUN/STOP input, controller status output, latching input, counters (FC and VFC),
PLS and PWM outputs.
What’s in this Section?
This section contains the following topics:
Topic
RUN/STOP Input
Controller Status Output
Latching input
Fast Counting
Very Fast Counters
Pulse (PLS) Generator Output
Pulse Width Modulation (PWM) Output
Page
176 35011387 06/2011
Controller Operation
RUN/STOP Input
Introduction
This section provides basic information on the RUN/STOP input special function.
Principle
The RUN/STOP input is a special function that can be assigned to anyone of the base controller inputs. This function is used to start or stop a program.
Determining the State of Run/Stop Input
At power up, if configured, the controller state is set by the Run/Stop input: z z if RUN/STOP input is at state 0, controller is in STOP mode.
if RUN/STOP input is at state 1, controller is in RUN mode.
While the controller is powered, a rising edge on the RUN/STOP input state sets the controller to RUN. The controller is stopped if the RUN/STOP input is at 0. If the
RUN/STOP input is at 0, a RUN command from a connected PC is ignored by the controller.
35011387 06/2011
177
Controller Operation
Controller Status Output
Introduction
This section provides basic information on the controller status output special function.
Principle
The controller status output is a special function that can be assigned to 1 of 3 outputs (%Q0.0.1 to %Q0.0.3) on a base or a remote controller.
At power up, if there is no controller error issue Base status, page 221 , the controller
status output changes to 1. This function can be used in circuits external to the controller, for example, to control: z z
The power supply to the output devices.
The controller power supply.
178 35011387 06/2011
Controller Operation
Latching input
Introduction
This section provides basic information on the latching inputs special function.
Principle
The latching inputs is a special function that can be assigned to one of four inputs
(%I0.0.2 to %I0.0.5) on a base or a remote controller. This function is used to memorize any pulse with a duration less than the controller scan time. When a pulse is shorter than one scan and has a value greater than or equal to 1 ms, the controller latches the pulse, which is then updated in the next scan.
35011387 06/2011
179
Controller Operation
Fast Counting
Introduction
This section provides basic information on the fast counting special function.
Principle
The base controllers have two fast counter types: z
A single up counter with a maximum frequency of 5 kHz.
z
A single down counter with a maximum frequency of 5 kHz.
The single up counter and single down counter functions enable up counting or down counting of pulses (rising edges) on a discrete I/O. The fast counter functions enable counting of pulses from 0 to 65535 in single-word mode and from 0 to
4294967295 in double-word mode.
Controllers Fast Counting Capabilities
Compact controllers can have up to 3 fast counters, with the exception of the
TWDLCA•40DRF series compact controllers that have 4 fast counters. Modular controllers can have up to 2 fast counters. The availability of the double-word counting option depends on the controller model. The following table lists the fast counting capabilities of the Twido line Compact and Modular controllers.
Twido Line
Controllers
Fast Counters
Single-Word
Double-Word
Compact controllers
TWDLC••...
10DRF
3
16DRF
3
Yes
No
Yes
Yes
24DRF
3
Yes
Yes
40DRF
4
Yes
Yes
Modular controllers
TWDLMDA...
20D••
2
40D••
2
Yes
Yes
Yes
Yes
Discrete I/O Assignment for a Fast Counter
The discrete I/O assignment for fast counters depends on whether discrete I/O was assigned for the optional pre-set and catch inputs on the very fast counters. See
Very Fast Counters, page 181 for more information.
180 35011387 06/2011
Controller Operation
Very Fast Counters
Introduction
This section provides basic information on the very fast counting special function.
Principle
The base controllers have five very fast counter types: z
An up/down counter with a maximum frequency of 20 kHz. z z
An up/down 2-phase counter with a maximum frequency of 20 kHz.
A single up counter with a maximum frequency of 20 kHz.
z z
A single down counter with a maximum frequency of 20 kHz.
A frequency meter with a maximum frequency of 20 kHz.
The up/down counter, up/down 2-phase counter, single up counter, and single down counter functions enable counting of pulses from 0 to 65535 in single-word mode and pulses from 0 to 4294967295 in double-word mode. The frequency meter function measures the frequency of a periodic signal in Hz.
Controllers Very Fast Counting Capabilities
The number of very fast counters supported varies with the Twido controller models, as shown in the table below. Also, the availability of the double-word counting option depends on the controller model. The following table lists the very fast counting capabilities of the Twido line Compact and Modular controllers.
Twido Line
Controllers
Compact controllers
TWDLC••...
10DRF
Fast Counters 1
16DRF
1
Single-Word
Double-Word
Yes
No
Yes
Yes
24DRF
1
Yes
Yes
40DRF
2
Yes
Yes
Modular controllers
TWDLMDA...
20D••
2
40D••
2
Yes
Yes
Yes
Yes
35011387 06/2011
181
Controller Operation discrete I/O Assignment for a Very Fast Counter on all Controllers
The following tables lists the assigned I/O for one very fast counter on all controllers models.
Functions First Input
(pulses)
Second
Input (pulses or Up/Down)
%I0.0.0*
Pre-set Input Catch Input First Reflex
Output
%I0.0.2** %I0.0.3** %Q0.0.2** Up/down counter %I0.0.1
(pulses)
Up/down 2-phase counter
%I0.0.1
(pulses
Phase A)
Single Up Counter %I0.0.1
(pulses)
Single Down
Counter
%I0.0.1
(pulses)
Frequency Meter %I0.0.1
(pulses)
%I0.0.0
(pulses
Phase B)
Not used
Not used
Not used
NOTE: z
* Indicates up/down z
** Optional use
%I0.0.2**
%I0.0.2**
%I0.0.2**
Not used
%I0.0.3**
%I0.0.3**
%I0.0.3**
Not used
%Q0.0.2**
%Q0.0.2**
%Q0.0.2**
Not used
Second
Reflex Output
%Q0.0.3**
%Q0.0.3**
%Q0.0.3**
%Q0.0.3**
Not used
Discrete I/O Assignment for the Other Very Fast Counter on Modular Controllers
The following tables lists the assigned I/O for the other very fast counter on Modular controllers only.
Functions First Input
(pulses)
Up/down counter %I0.0.7
(pulses)
Up/down 2-phase counter
%I0.0.7
(pulses Phase A)
Single Up Counter %I0.0.7
(pulses)
Second Input
(pulses or
Up/Down)
%I0.0.6*
%I0.0.6
(pulses Phase B)
Not used
Pre-set Input Catch Input First
%I0.0.5**
%I0.0.5**
%I0.0.5**
%I0.0.4**
%I0.0.4**
%I0.0.4**
Reflex
Output
Second
Reflex
Output
%Q0.0.4** %Q0.0.5**
%Q0.0.4**
%Q0.0.4**
%Q0.0.5**
%Q0.0.5**
182 35011387 06/2011
Controller Operation
Functions First Input
(pulses)
Second Input
(pulses or
Up/Down)
Not used Single Down
Counter
%I0.0.7
(pulses)
Frequency Meter %I0.0.7
(pulses)
Not used
NOTE: z
* Indicates up/down z
** Optional use
Pre-set Input Catch Input First
Reflex
Output
%I0.0.5** %I0.0.4**
Second
Reflex
Output
%Q0.0.4** %Q0.0.5**
Not used Not used Not used Not used
35011387 06/2011
183
Controller Operation
Pulse (PLS) Generator Output
Introduction
This section provides basic information on the PLS special function.
Principle
The PLS is a special function that can be assigned to output %Q0.0.0 or %Q0.0.1 on a base or a peer controller. A user-defined function block generates a signal on output %Q0.0.0 or %Q0.0.1. This signal has a variable period but has a constant duty cycle, or on to off ratio of 50% of the period.
Controllers PLS Capabilities
The number of PLS generators supported varies with the Twido controller models, as shown in the table below. Note that all controllers that have a PLS generator support both single-word and double-word functions. The following table lists the
PLS capabilities of the Twido line Compact and Modular controllers.
Twido Line
Controllers
Compact controllers
TWDLC••...
10DRF
PLS Generator None
16DRF
None
Single-Word
Double-Word -
-
-
-
-
-
24DRF
None
40DRF
2
Yes
Yes
Modular controllers
TWDLMDA...
20D••
2
40D••
2
Yes
Yes
Yes
Yes
184 35011387 06/2011
Controller Operation
Pulse Width Modulation (PWM) Output
Introduction
This section provides basic information on the PWM special function.
Principle
The PWM is a special function that can be assigned to output %Q0.0.0 or %Q0.0.1 on a base or a peer controller. A user-defined function block generates a signal on output %Q0.0.0 or %Q0.0.1. This signal has a constant period with the possibility of varying the duty cycle, or on to off ratio.
Controllers PWM Capabilities
The number of PWM generators supported varies with the Twido controller models, as shown in the table below. Note that all controllers that have a PWM generator support both single-word and double-word functions. The following table lists the
PWM capabilities of the Twido line Compact and Modular controllers.
Twido Line
Controllers
Compact controllers
TWDLC••...
10DRF
PWM Generator None
16DRF
None
Single-Word
Double-Word -
-
-
-
-
-
24DRF
None
40DRF
2
Yes
Yes
Modular controllers
TWDLMDA...
20D••
2
40D••
2
Yes
Yes
Yes
Yes
35011387 06/2011
185
Controller Operation
6.2
Controller Operating Modes
Introduction
This section provides information about scanning, operating modes, power supply outages and restoration, warm and cold start, and objects initialization.
What’s in this Section?
This section contains the following topics:
Topic
Cyclic Scan
Periodic Scan
Checking Scan Time
Operating Modes
Dealing with Power Outages and Restoration
Dealing with a Warm Restart
Dealing with a Cold Start
Initialization of Objects
Page
186 35011387 06/2011
Controller Operation
Cyclic Scan
Introduction
Cyclic scanning involves linking controller cycles together one after the other. After having effected the output update (third phase of the task cycle), the system executes a certain number of its own tasks and immediately triggers another task cycle.
NOTE: The scan time of the user program is monitored by the controller watchdog timer and must not exceed 500 ms. Otherwise an unintended operation occurs causing the controller to stop immediately in Halt mode. Outputs in this mode are forced to their default fallback state.
Operation
The following drawing shows the running phases of the cyclical scan time.
Description of the phases of a cycle
The following table describes the phases of a cycle.
Address Phase
I.P.
Internal processing
-
%I, %IW Acquisition of input
Program processing
%Q,
%QW
Updating of output
Description
The system implicitly monitors the controller (managing system bits and words, updating current timer values, updating status lights, detecting RUN/STOP switches, etc.) and processes requests from TwidoSuite (modifications and animation).
Writing to the memory the status of discrete and application specific module inputs.
Running the application program written by the user.
Writing output bits or words associated with discrete and application specific modules.
35011387 06/2011
187
Controller Operation
Operating mode z z z z z z
Controller in RUN , the processor carries out:
Internal processing
Acquisition of input
Processing the application program
Updating of output
Controller in STOP , the processor carries out:
Internal processing
Acquisition of input
Illustration
The following illustration shows the operating cycles.
Check Cycle
The check cycle is performed by watchdog.
188 35011387 06/2011
Controller Operation
Periodic Scan
Introduction
In this operating mode, acquiring inputs, processing the application program, and updating outputs are done periodically according to the time defined at configuration
(from 2-150 ms).
At the beginning of the controller scan, a timer, the value of which is initialized at the period defined at configuration, starts to count down. The controller scan must end before the timer has finished and relaunches a new scan.
Operation
The following drawing shows the running phases of the periodic scan time.
Description of Operating Phases
The table below describes the operating phases.
Address
I.P.
Phase Description
Internal processing The system implicitly monitors the controller (managing system bits and words, updating current timer values, updating status lights, detecting RUN/STOP switches, etc.) and processes requests from TwidoSuite (modifications and animation).
-
%I, %IW Acquisition of input Writing to the memory the status of discrete and application specific module inputs.
Program processing
Running the application program written by the user.
%Q, %QW Updating of output Writing output bits or words associated with discrete and application specific modules.
35011387 06/2011
189
Controller Operation
Operating mode z z z z
Controller in RUN , the processor carries out:
Internal processing
Acquisition of input
Processing the application program
Updating of output
If the period has not finished, the processor completes its operating cycle until the end of the internal processing period. If the operating time is longer than that allocated to the period, the controller indicates that the period has been exceeded by setting the system bit %S19 to 1. The process continues and is run completely.
However, it must not exceed the watchdog time limit. The following scan is linked in after writing the outputs of the scan in progress implicitly.
z z
Controller in STOP , the processor carries out:
Internal processing
Acquisition of input
190 35011387 06/2011
Illustration
The following illustration shows the operating cycles.
Controller Operation
Check Cycle z z
Two checks are carried out:
Period overflow
Watchdog
35011387 06/2011
191
Controller Operation
Checking Scan Time
General
The task cycle is monitored by a watchdog timer called Tmax (a maximal duration of the task cycle). It allows the detection of application errors (infinite loops, and so on.) and specifies a maximal duration for output refreshing.
Software WatchDog (Periodic or Cyclic Operation)
In periodic or cyclic operation, the triggering of the watchdog causes a software message. The application passes into a HALT state and sets system bit%S11 to 1.
The relaunching of the task necessitates a connection to Trotskyite in order to analyze the cause of the detected error, modification of the application to correct the error, then reset the program to RUN.
NOTE: The HALT state is when the application is stopped immediately because of detection of an application software error such as a scan overrun. The data retains the current values, which allows for an analysis of the cause of the error. The program stops on the instruction in progress. Communication with the controller is open.
Check on Periodic Operation
In periodic operation an additional check is used to detect the period being exceeded: z
%S19 indicates that the period has been exceeded. It is set to: z z
1 by the system when the scan time is greater that the task period,
0 by the user.
z
%SW0 contains the period value (0-150 ms). It is: z
Initialized when starting from a cold start by the value selected on the z configuration,
Able to be modified by the user.
Using Master Task Running Time
The following system words are used for information on the controller scan cycle time: z z z z
%SW11 initializes to the maximum watchdog time (10 to 500 ms).
%SW30 contains the execution time for the last controller scan cycle.
%SW31 contains the execution time for the longest controller scan cycle since the last cold start.
%SW32 contains the execution time for the shortest controller scan cycle since the last cold start.
NOTE: This different information can also be accessed from the configuration editor.
192 35011387 06/2011
Controller Operation
Operating Modes
Introduction
TwidoSuite is used to take into account the three main operating mode groups: z
Checking z
Running or production z
Stopping
Starting through Grafcet
These different operating modes can be obtained either starting from or using the following Grafcet methods: z
Grafcet initialization z z z
Presetting of steps
Maintaining a situation
Freezing charts
Preliminary processing and use of system bits provide effective operating mode management without complicating and overburdening the user program.
Grafcet System Bits
Use of bits %S21, %S22 and %S23 is reserved for preliminary processing only.
These bits are automatically reset by the system. They must be written by Set
Instruction S only.
The following table provides Grafcet-related system bits:
Bit
%S21
%S22
Function
GRAFCET initialization
GRAFCET RESET
Description
Normally set to 0, it is set to 1 by: z a cold-start, %S0=1 ; z The user, in the pre-processing program part only, using a Set
Instruction S %S21 or a set coil -(S)- %S21 .
Result: z Deactivation of all active steps.
z Activation of all initial steps.
Normally set to 0, it can only be set to 1 by the program in preprocessing.
Result: z Deactivation of all active steps.
z Scanning of sequential processing stopped.
35011387 06/2011
193
Controller Operation
Bit
%S23
Function
Preset and freeze GRAFCET
Description
Normally set to 0, it can only be set to 1 by the program in preprocessing.
z z
Prepositioning by setting %S22 to 1.
Preposition the steps to be activated by a series of S Xi z instructions.
Enable prepositioning by setting %S23 to 1.
Freezing a situation: z In initial situation: by maintaining %S21 at 1 by program.
z z
In an "empty" situation: by maintaining %S22 at 1 by program.
In a situation determined by maintaining %S23 at 1.
194 35011387 06/2011
Controller Operation
Dealing with Power Outages and Restoration
Illustration
The following illustration shows the various power restarts detected by the system.
If the duration of the outage is less than the power supply filtering time (about 10 ms for an alternating current supply or 1 ms for a direct current supply), this is not noticed by the program which runs normally.
RUN
Run
Application
Power outage
Standby power
Power restoration
WAIT
Power outage detected
No
Yes
Auto-test
Save context OK
Yes
No
Memory card identical
No
Yes
Normal execution of program
Warm Start Cold Start
NOTE: The context is saved in a battery backed-up RAM. At power up, the system checks the state of the battery and the saved context to decide if a warm start can occur.
35011387 06/2011
195
Controller Operation
Run/Stop Input Bit Versus Auto Run
The Run/Stop input bit has priority over the "Automatic Start in Run" option that is available from the Scan Mode dialog box. If the Run/Stop bit is set, then the controller will restart in the Run Mode when power is restored.
The mode of the controller is determined as follows:
Run/Stop Input Bit
Zero
Zero
Rising edge
One
Not configured in software
Not configured in software
Auto Start in Run
Zero
One
No effect
No effect
Zero
One
Resulting State
Stop
Stop
Run
Run
Stop
Run
NOTE: For all Compact type of controllers of software version V1.0, if the controller was in Run mode when power was interrupted, and the "Automatic Start in Run" flag was not set from the Scan Mode dialog box, the controller will restart in Stop mode when power is restored. Otherwise it will perform a cold restart.
NOTE: For all Modular and Compact type of controllers of software version V1.11, if the battery in the controller is operating normally when power was interrupted, the controller will startup in the mode that was in effect at the time the power was interrupted. The "Automatic Start in Run" flag, that was selected from the Scan
Mode dialog, will have no effect on the mode when the power is restored.
Operation
The table below describes the processing phases for power outages.
Phase Description
1 In the event of a power outage the system stores the application context and the time of the outage.
2 All outputs are set to fallback status (0).
3 When power is restored, the context saved is compared with the one in progress which defines the type of start to run: z If the application context has changed (loss of system context or new application), the controller initializes the application: Cold restart (systematic for z compact).
If the application context is the same, the controller restarts without initializing data: warm restart.
196 35011387 06/2011
Controller Operation
Dealing with a Warm Restart
Cause of a Warm Restart
A warm restart can occur: z z z
When power is restored without loss of application context,
When bit %S1 is set to state 1 by the program,
From the Operator Display when the controller is in STOP mode
Illustration
The drawing below describes a warm restart operation in RUN mode.
RUN WAIT
Acquisition of inputs
Stop the processor
Save application context Execution of program
TOP if bit %S1=1, possible process with warm restart
Restoration of power
Partial configuration auto-tests
Detection of power outage
>Micro power outage
No
BOT
Yes
Set bit %S1 to 1 for only one cycle
Set bit %S1 to 0
Update outputs
35011387 06/2011
197
Controller Operation
Restart of the Program Execution
The table below describes the restart phases for running a program after a warm restart.
Phase
1
2
3
Description
The program execution resumes from the same element where it was prior to the power outage, without updating the outputs.
Note: Only the same element from the user code is restarted. The system code
(for example, the updating of outputs) is not restarted.
At the end of the restart cycle, the system: z Unreserves the application if it was reserved (and provokes a STOP z application in case of debugging)
Reinitializes the messages
The system carries out a restart cycle in which it: z Relaunches the task with bits %S1 (warm-start indicator) and %S13 (first z cycle in RUN) set to 1
Resets bits %S1 and %S13 to 0 at the end of the first task cycle
Processing of a Warm-Start
In the event of a warm-start, if a particular application process is required, bit %S1 must be tested at the start of the task cycle, and the corresponding program called up.
Outputs after Power Outage
Once a power outage is detected, outputs are set to (default) fallback status (0).
When power is restored, outputs are at last state until they are updated again by the task.
198 35011387 06/2011
Controller Operation
Dealing with a Cold Start
Cause of a Cold Start
A cold-start can occur: z z z z
When loading a new application into RAM
When power is restored with loss of application context
When system bit %S0 is set to state 1 by the program
From the Operator Display when the controller is in STOP mode
Illustration
The drawing below describes a cold restart operation in RUN mode.
RUN WAIT
Acquisition of inputs
Stop the processor
Save application context
Execution of program
TOP if bit %S0=1, possible process with cold restart
Detection of power outage
>Micro power outage
No
BOT
Set bit %S0 to 0
Yes
Restoration of power
AUTO-TESTS
Completion of configuration auto-tests
Initialization of application
Set bit %S0 to 1
Update outputs
35011387 06/2011
199
Controller Operation
Operation
The table below describes the restart phases for running a program after a cold restart.
Phase
1
2
3
Description
At start up, the controller is in RUN.
At a cold restart after a stop due to a detected error, the system forces a cold restart.
The program execution restarts at the beginning of the cycle.
The system: z Resets internal bits and words and the I/O images to 0 z z
Initializes system bits and words
Initializes function blocks from configuration data
For this first restart cycle, the system: z Relaunches the task with bits %S0 (cold-start indicator) and %S13 (first cycle z in RUN) set to 1
Resets bits %S0 and %S13 to 0 at the end of this first task cycle z z
Sets bits %S31 and %S38 (event control indicators) to their initial state 1.
Resets bits %S39 (event control indicator) and word %SW48 (counts all events executed except periodic events).
Processing of a Cold-Start
In the event of a cold-start, if a particular application process is required, bit %S0
(which is at 1) must be tested during the first cycle of the task.
Outputs after Power Outage
Once a power outage is detected, outputs are set to (default) fallback status (0).
When power is restored, outputs are at zero until they are updated again by the task.
200 35011387 06/2011
Controller Operation
Initialization of Objects
Introduction
The controllers can be initialized by TwidoSuite by setting system bits %S0 (a cold restart) and %S1 (a warm restart).
Cold Start Initialization
For a cold start initialization, system bit %S0 must be set to 1.
Initialization of Objects (Identical to Cold Start) on Power-up using %S0 and %S1
To initialize objects on power-up, system bit %S1 and %S0 must be set to 1.
The following example shows how to program a warm restart object initialization using system bits.
35011387 06/2011
201
Controller Operation
202 35011387 06/2011
Twido Programmable Controllers
Operator Display Operation
35011387 06/2011
Operator Display Operation
7
Introduction
This appendix provides an overview, information about operator display controller
ID, system objects, serial port settings, time of day clock, and real-time correction .
What’s in this Chapter?
This chapter contains the following topics:
Topic
Operator Display
Controller Identification and State Information
System Objects and Variables
Serial Port Settings
Time of Day Clock
Real-Time Correction Factor
Page
203
35011387 06/2011
Operator Display Operation
Operator Display
Introduction
The Operator Display is a Twido option for displaying and controlling application data and some controller functions such as operating state and the Real-Time Clock
(RTC). This option is available as a cartridge (TWDXCPODC) for the Compact controllers or as an expansion module (TWDXCPODM) for the Modular controllers. z z
The Operator Display has two operating modes:
Display Mode: only displays data.
Edit mode: allows you to change data.
NOTE: The operator display is updated at a specific interval of the controller scan cycle. This can cause confusion in interpreting the display of dedicated outputs for
%PLS or %PWM pulses. At the time these outputs are sampled, their value will be zero, and this value will be displayed.
Displays and Functions
The Operator Display provides the following separate displays with the associated functions you can perform for each display.
z
Controller Identification and State Information: Operations Display
Display firmware revision and the controller state. Change the controller state z with the Run, Initial, and Stop commands.
System Objects and Variables: Data Display
Select application data by the address: %I, %Q, and all other software objects on the base controller. Monitor and change the value of a selected software data z z z object.
Serial Port Settings: Communication Display
Display and modify communication port settings.
Time of Day Clock: Time/Date Display
Display and configure the current date and time (if the RTC is installed).
Real Time Correction: RTC Factor
Display and modify the RTC Correction value for the optional RTC.
NOTE:
1.
The TWDLC••40DRF series of compact controllers have RTC onboard.
2.
On all other controllers, time of day clock and real-time correction are only available if the Real-Time Clock (RTC) option cartridge (TWDXCPRTC) is installed.
204 35011387 06/2011
Illustration
Operator Display Operation
The following illustration shows a view of the Operator Display, which consists of a display area (here in Normal mode) and four push-button input keys.
Display area
Input keys
35011387 06/2011
The Operator Display provides an LCD display capable of displaying two lines of characters: z z
The first line of the display has three 13-segment characters and four 7-segment characters.
The second line has one 13-segment character, one 3-segment character (for a plus/minus sign), and five 7-segment characters.
NOTE: If in Normal mode, the first line indicates an object name and the second line displays its value. If in Data mode, the first line displays %SW68 value and the second line displays %SW69 value.
The functions of the four input push-buttons depend on the Operator Display mode.
Key
ESC
In Display Mode In Edit Mode
Discard changes and return to previous display.
Go to the next value of an object being edited.
205
Operator Display Operation
Key In Display Mode In Edit Mode
Advance to next display.
Go to the next object type to edit.
MOD/ENTER Go to edit mode.
Accept changes and return to previous display.
Selecting and Navigating the Displays
The initial display or screen of the Operator Display shows the controller identification and state information. Press the push-button to sequence through each of the displays. The screens for the Time of Day Clock or the Real-Time Correction
Factor are not displayed if the optional RTC cartridge (TWDXCPRTC) is not detected on the controller.
As a shortcut, press the ESC key to return to the initial display screen. For most screens, pressing the ESC key will return to the Controller Identification and State
Information screen. Only when editing System Objects and Variables that are not the initial entry (%I0.0.0), will pressing ESC take you to the first or initial system object entry.
To modify an object value, instead of pressing the push-button to go to the first value digit, press the MOD/ENTER key again.
206 35011387 06/2011
Operator Display Operation
Controller Identification and State Information
Introduction
The initial display or screen of the Twido optional Operator Display shows the
Controller Identification and State Information.
Example
The firmware revision is displayed in the upper-right corner of the display area, and the controller state is displayed in the upper-left corner of the display area, as seen in the following:
Controller States
Controller states include any of the following: z z z z
NCF: Not Configured
The controller is in the NCF state until an application is loaded. No other state is allowed until an application program is loaded. You can test the I/O by modifying system bit S8. (see the Programming Guide for additional information about
System Bits and System Words.)
STP: Stopped
Once an application is present in the controller, the state changes to the STP or
Stopped state. In this state, the application is not running. Inputs are updated and data values are held at their last value. Outputs are not updated in this state.
INI: Initial
You can choose to change the controller to the INI or initial state only from the
STP state. The application is not running. The controller’s inputs are updated and data values are set to their initial state. No outputs are updated from this state.
RUN: Running
When in the RUN or running state the application is running. The controller’s inputs are updated and data values are set according to the application. This is the only state where the outputs are updated.
35011387 06/2011
207
Operator Display Operation z z
HLT: Halted (User Application Error Detected)
If the controller has entered an ERR or error state, the application is halted. Inputs are updated and data values are held at their last value. From this state, outputs are not updated. In this mode, the error code is displayed in the lower-right portion of the Operator Display as an unsigned decimal value.
NEX: Not Executable (not executable)
An online modification was made to user logic. Result: The application is no longer executable. It will not go back into this state until all causes for the Non-
Executable state have been resolved.
Displaying and Changing Controller States
Using the Operator Display, you can change to the INI state from the STP state, or from STP to RUN, or from RUN to STP. Do the following to change the state of the controller:
Step
1
2
3
4
Action
Press the key until the Operations Display is shown (or press ESC). The current controller state is displayed in the upper-left corner of the display area.
Press the MOD/ENTER key to enter edit mode.
Press the key to select a controller state.
Press the MOD/ENTER key to accept the modified value, or press the ESC key to discard any modifications made while in edit mode.
208 35011387 06/2011
Operator Display Operation
System Objects and Variables
Introduction z z z
The optional Operator Display provides these features for monitoring and adjusting application data:
Select application data by address (such as %I or %Q).
Monitor the value of a selected software object/variable.
Change the value of the currently displayed data object (including forcing inputs and outputs).
System Objects and Variables
The following table lists the system objects and variables, in the order accessed, that can be displayed and modified by the Operator Display.
Object
Input
Output
Timer
Counter
Memory Bit
Word Memory
Constant Word
System Bit
System Word
Analog Input
Analog Output
Fast Counter
Variable/Attribute
%Ix.y.z
%Qx.y.z
%TMX.V
%TMX.P
%TMX.Q
%Cx.V
%Cx.P
%Cx.D
%Cx.E
%Cx.F
%Mx
%MWx(3)
%KWx
%Sx
%SWx(4)
%IWx.y.z
%QWx.y.z
%FCx.V
%FCx.VD(1)
%FCx.P
%FCx.PD(1)
%FCx.D
Description
Value
Value
Current Value
Preset value
Done
Current Value
Preset value
Done
Empty
Full
Value
Value
Value
Value
Value
Value
Value
Current Value
Current Value
Preset value
Preset value
Done
Access
Read/Force
Read/Write/Force
Read/Write
Read/Write
Read
Read/Write
Read/Write
Read
Read
Read
Read/Write
Read/Write
Read
Read/Write
Read/Write
Read
Read/Write
Read
Read
Read/Write
Read/Write
Read
35011387 06/2011
209
Operator Display Operation
Object
Very Fast Counter
Step counter
Register
Variable/Attribute
%VFCx.V
%VFCx.VD(1)
%VFCx.P
%VFCx.PD(1)
%VFCx.U
%VFCx.C
%VFCx.CD(1)
%VFCx.S0
%VFCx.S0D(1)
%VFCx.S1
%VFCx.S1D(1)
%VFCx.F
%VFCx.T
%VFCx.R
%VFCx.S
Input Network Word %INWx.z
Output Network
Word
%QNWx.z
Grafcet
Pulse Generator
%Xx
%PLS.N
%PLS.ND(1)
%PLS.P(5)
%PLS.D
%PLS.Q
Pulse Width
Modulator
Drum Controller
%PWM.R
%PWM.P
%DRx.S
%DRx.F
%SCx.n
%Rx.I
%Rx.O
%Rx.E
%Rx.F
Shift bit register
Message
%SBR.x.yy
%MSGx.D
%MSGx.E
%IAx.y.z
AS-Interface slave input
AS-Interface analog slave input
AS-Interface slave output
%IWAx.y.z
%QAx.y.z
Value
Value
Description
Current Value
Current Value
Preset value
Preset value
Count Direction
Catch Value
Catch Value
Threshold 0 Value
Threshold 0 Value
Threshold Value1
Threshold Value1
Overflow
Timebase
Reflex Output Enable
Reflex Input Enable
Value
Value
Access
Read
Read
Read/Write
Read/Write
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read/Write
Read/Write
Read/Write
Read
Read/Write
Step Bit
Number of Pulses
Number of Pulses
Preset value
Done
Current Output
Ratio
Preset value
Current Step Number
Full
Step Counter bit
Input
Output
Empty
Full
Register Bit
Done
Error Detected
Value
Read
Read/Write
Read/Write
Read/Write
Read
Read
Read/Write
Read/Write
Read
Read
Read/Write
Read/Write
Read/Write
Read
Read
Read/Write
Read
Read
Read/Force
Read
Read/Write/Force
210 35011387 06/2011
Operator Display Operation
Object
AS-Interface analog slave output
CANopen slave PDO input
CANopen slave PDO output
Variable/Attribute
%QWAx.y.z
%IWCx.y.z
%QWCx.y.z
Description
Value
Single-word value
Single-word value
Access
Read/Write
Read
Read/Write
Notes:
1.
32-bit double word variable. The double word option is available on all controllers with the exception of the Twido TWDLC•A10DRF controllers.
2.
Variables will not be displayed if they are not used in an application since Twido uses dynamic memory allocation.
3.
If the value of %MW is greater than +32767 or less than -32768, the operator display will continue to blink.
4.
If the value of %SW is greater than 65535, the operator display continues to blink, except for %SW0 and %SW11. If a value is entered that is more than the limit, the value will return to the configured value.
5.
If a value is entered for %PLS.P that is more than the limit, the value written is the saturation value.
Displaying and Modifying Objects and Variables
Each type of system object is accessed by starting with the Input Object (%I), sequencing through to the Message object (%MSG), and finally looping back to the
Input Object (%I).
To display a system object:
Step
1
2
3
4
Action
Press the key until the Data Display screen is shown.
The Input object ("I") will be displayed in the upper left corner of the display area.
The letter " I " (or the name of the object previously viewed as data) is not blinking.
Press the MOD/ENTER key to enter edit mode.
The Input Object "I" character (or previous object name viewed as data) begins blinking.
Press the key to step sequentially through the list of objects.
Press the key to step sequentially through the field of an object type and press the key to increment through the value of that field. You can use the key and key to navigate and modify all fields of the displayed object.
35011387 06/2011
211
Operator Display Operation
Step
5
6
Action
Repeat steps 3 and 4 until editing is complete.
Press the MOD/ENTER key to accept the modified values.
Note: The object’s name and address have to be validated before accepting any modifications. That is, they must exist in the configuration of the controller prior to using the operator display.
Press ESC to discard any changes made in edit mode.
Data Values and Display Formats
In general, the data value for an object or variable is shown as a signed or unsigned integer in the lower-right of the display area. In addition, all fields suppress leading zeros for displayed values. The address of each object is displayed on the Operator
Display in one of the following 8 formats: z z z z z z z z
Input/Output format
AS-Interface slaves I/O format
CANopen slaves I/O format
Function block format
Simple format
Network I/O format
Step Counter Format
Shift Bit Register format
Input/Output Format
The input/output objects (%I, %Q, %IW and %QW) have three-part addresses (e.g.:
%IX.Y.Z) and are displayed as follows: z z z
Object type and controller address in the upper-left
Expansion address in the upper-center
I/O channel in the upper-right
In the case of a simple input (%I) and output (%Q), the lower-left portion of the display will contain a character that is either "U" for unforced or "F" for a forced bit.
The force value is displayed in the lower-right of the screen.
The output object %Q0.3.11 appears in the display area as follows:
212 35011387 06/2011
Operator Display Operation
AS-Interface Slaves I/O Format
AS-Interface slave I/O objects (%IA, %QA, %IWA and %QWA) have four-part addresses (e.g.: %IAx.y.z) and are displayed as follows: z z z z
The object type in the upper-left
AS-Interface master address on the expansion bus in the upper-left center
Address of the slave on the AS-Interface bus in the upper-right center
Slave I/O channel in the upper-right.
In the case of a simple input (%IA) and output (%QA), the lower-left portion of the display will contain a character that is either "U" for unforced or "F" for a forced bit.
The force value is displayed in the lower-right of the screen.
The output object %QA1.3A.2 appears in the display area as follows:
CANopen Slaves I/O Format
CANopen slave PDO I/O objects (%IWC and %QWC) have four-part addresses
(e.g.: %IWCx.y.z) and are displayed as follows: z z z z z
The object type in the upper-left
CANopen master address on the expansion bus in the upper-left center
Address of the slave on the CANopen bus in the upper-right center
Slave PDO I/O channel in the upper-right.
Signed value for the object in the lower portion
In the following example, the PDO output object %QWC1.3.2 contains the signed value +24680:
Function Block Format
The function blocks (%TM, %C, %FC, %VFC, %PLS, %PWM, %DR, %R, and
%MSGj) have two-part addresses containing an object number and a variable or attribute name. They are displayed as follows: z z
Function block name in the upper-left
Function block number (or instance) in the upper-right
35011387 06/2011
213
Operator Display Operation z z
The variable or attribute in the lower-left
Value for the attribute in the lower-right
In the following example, the current value for timer number 123 is set to 1,234.
Simple Format z z
A simple format is used for objects %M, %MW, %KW, %MD, %KD, %MF, %KF, %S,
%SW and %X as follows:
Object number in the upper-right
Signed value for the objects in the lower portion
In the following example, memory word number 67 contains the value +123.
Network I/O Format z z z z
The network input/output objects (%INW and %QNW) appear in the display area as follows:
Object type in the upper-left
Controller address in the upper-center
Object number in the upper-right
Signed value for the object in the lower portion
In the following example, the first input network word of the remote controller configured at remote address #2 is set to a value -4.
214 35011387 06/2011
Operator Display Operation
Step Counter Format
The step counter (%SC) format displays the object number and the step counter bit as follows: z z z
Object name and number in the upper-left
Step counter bit in the upper right
The value of the step counter bit in the lower portion of the display
In the following example, bit number 129 of step counter number 3 is set to 1.
Shift Bit Register Format
The shift bit register (%SBR) appears in the display area as follows: z z z
Object name and number in the upper-left
Register bit number in the upper-right
Register bit value in the lower-right
The following example shows the display of shift bit register number 4.
35011387 06/2011
215
Operator Display Operation
Serial Port Settings
Introduction
The operator display allows you to display the protocol settings and change the addresses of all serial ports configured using TwidoSuite. The maximum number of serial ports is two. In the example below, the first port is configured as Modbus protocol with an address 123. The second serial port is configured as a remote link with an address of 4.
Displaying and Modifying Serial Port Settings
Twido controllers can support up to two serial ports. To display the serial port settings using the operator display:
Step
1
Action
Press the key until the Communication Display is shown. The single letter of the protocol setting of the first serial port ("M", "R", or "A") will be displayed in the upper left corner of the operator display.
Press the MOD/ENTER key to enter the edit mode.
2
3
Press the key until you are in the field that you wish to modify.
4
5
6
Press the key to increment the value of that field.
Continue steps 3 and 4 until the address settings are complete.
Press the MOD/ENTER key to accept the modified values or ESC to discard any modifications made while in edit mode.
Note: The address is part of the configuration data on the Controller. Changing its value using the operator display means that you can no longer connect using TwidoSuite as equal.
TwidoSuite will require that you do a download to become equal again.
216 35011387 06/2011
Operator Display Operation
Time of Day Clock
Introduction
You can modify the date and time using the operator display if the RTC option cartridge (TWDXCPRTC) is installed on your Twido controller. The Month is displayed in the upper-left side of the HMI Display. Until a valid time has been entered, the month field will contain the value "RTC". The day of the month is displayed in the upper-right corner of the display. The time of day is in military format. The hours and minutes are shown in the lower-right corner of the display and are separated by the letter "h". The example below shows that the RTC is set to
March 28, at 2:22 PM.
NOTE:
1.
The TWDLC••40DRF series of compact controllers have RTC onboard.
2.
On all other controllers, time of day clock and real-time correction are only available if the Real-Time Clock (RTC) option cartridge (TWDXCPRTC) is installed.
Displaying and Modifying Time of Day Clock
To display and modify the Time of Day Clock:
Step
1
Action
Press the key until the Time/Date Display is shown. The month value ("JAN",
"FEB") will be displayed in the upper-left corner of the display area. The value "RTC" will be displayed in the upper-left corner if no month has been initialized.
2 Press the MOD/ENTER key to enter the edit mode.
3
Press the key until you are in the field that you wish to modify.
4
Press the key increment the value of that field.
5 Continue steps 3 and 4 until the Time of Day value is complete.
6 Press the MOD/ENTER key to accept the modified values or ESC to discard any modifications made while in edit mode.
35011387 06/2011
217
Operator Display Operation
Real-Time Correction Factor
Introduction
You can display and modify the Real-Time Correction Factor using the operator display. Each Real-Time Clock (RTC) Option module has a RTC Correction Factor value that is used to correct for inaccuracies in the RTC module’s crystal. The correction factor is an unsigned 3-digit integer from 0 to 127 and is displayed in the lower-right corner of the display.
The example below shows a correction factor of 127.
Displaying and Modifying RTC Correction
To display and modify the Real-Time Correction Factor:
Step
1
2
3
4
5
6
Action
Press the key until the RTC Factor Display is shown. "RTC Corr" will be displayed in the upper line of the operator display.
Press the MOD/ENTER key to enter edit mode.
Press the key until you are in the field that you wish to modify.
Press the key to increment the value of that field.
Continue Steps 3 and 4 until the RTC correction value is complete.
Press the MOD/ENTER key to accept the modified values or ESC to discard any modifications made while in edit mode.
218 35011387 06/2011
Twido Programmable Controllers
35011387 06/2011
Appendices
Introduction
This appendix provides information on system diagnostic using LED’s, operator display operation, troubleshooting, the DIN rail, common IEC symbols used in this manual, and agency compliance.
What’s in this Appendix?
The appendix contains the following chapters:
Chapter
A
B
C
D
E
Chapter Name
System Diagnostic using the Front Panel LED’s
Troubleshooting
The DIN Rail
IEC Symbols
Agency Compliance
Page
35011387 06/2011
219
220 35011387 06/2011
Twido Programmable Controllers
System diagnostic using the Front Panel LED’s
35011387 06/2011
System Diagnostic using the
Front Panel LED’s
System Diagnostic Using the Front Panel LEDs
Introduction
This section provides information about the base operating status and troubleshooting using the front panel LEDs.
Status of the Discrete I/O Module
LED state
I/O LEDs
Discrete I/O Module
I/O not active
I/O active
A
Base status
LED status
RUN green
The following table displays the different LED statuses on a base controller, peer controller, and remote controller.
Base Controller or Peer Controller
Application not executed
Remote I/O Controller
Incorrectly or not connected
Controller is in STOP mode error (HALT) Same as base controller
221
35011387 06/2011
System diagnostic using the Front Panel LED’s
LED status
ERR red
Base Controller or Peer Controller
OK
Remote I/O Controller
OK
Application not executable, or execution error (HALT)
Internal detected errors (watchdog, etc.)
N/A
Same as base controller
STAT green
Controlled by the user or application through system bit
%S69
N/A
Same as base controller
N/A
Controlled by the user or application through system bit
%S69
Same as base controller
BAT red
TWDLC•A40DRF and TWDLC•E40DRF Compact bases. (For detailed information about the BAT
LED status, please see BAT LED Status
.)
External battery power is OK or LED has been disabled.
(Controlled by the user or system through system bit
%S66)
N/A
N/A N/A
LAN ACT green/amber
No external battery or low battery power.
Controlled by the user or system through system bit
%S66
N/A
TWDLC•E40DRF Compact base. (For detailed information about the LAN ACT LED status, please see "link-TBD".)
No Ethernet signal.
N/A green: communicating over 10Base-T link.
amber: communicating over 100Base-TX link.
green: 10Base-T network connection.
amber: 100Base-TX network connection.
N/A
N/A
222 35011387 06/2011
System diagnostic using the Front Panel LED’s
LED status
LAN ST green
Base Controller or Peer Controller Remote I/O Controller
TWDLC•E40DRF Compact base. (For detailed information about the LAN ACT LED status, please see "link-TBD".)
Base controller is powered OFF.
N/A
Multiple, consecutive flashes of various numbers to provide a visual diagnostic tool of the Ethernet network connection status.
N/A
Base controller is powered ON. Ethernet port is ready.
N/A
Off
On
35011387 06/2011
223
System diagnostic using the Front Panel LED’s
224 35011387 06/2011
Twido Programmable Controllers
Troubleshooting
35011387 06/2011
Troubleshooting
B
Checking I/O Connections on the Base Controller
Introduction
This section provides a procedure for checking the I/O connections.
WARNING
UNINTENDED OPERATION OF EXTERNAL EQUIPMENT z z
To avoid unintended operation of external equipment, check that:
Power fuses are removed from the motor controls.
Pneumatic and hydraulic inputs are closed.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Checking I/O Connections Procedure
The following procedure ensures that the I/O connections are connected:
Step
1
2
3
Action
To test the I/O connections, the base needs to be in the non-configured state. To accomplish this: z If an Operator Display is attached, press and hold ESC and cycle the power on the base. After the base restarts, the Operator Display indicates "NCF".
z From TwidoSuite, issue the Erase all command from the Program → Memory
Cartridge Commands task.
With the base in the non-configured state, set system bit %S8 to 0. At state 0, the base outputs are kept in their existing state.
Check the inputs by activating each external sensor. To accomplish this: z z
Check that each of the input LEDs for the corresponding bit changes state.
Using the TwidoSuite Program Debug for the corresponding bit changes state.
→ task, check that each of the input LEDs
Note: Check PLC can only be used in connected mode.
35011387 06/2011
225
Troubleshooting
Step
4
5
Action
Check the outputs by setting the bit corresponding to each output state to 1. To accomplish this: z Check that each of the output LEDs for the corresponding bit changes state.
z Using the TwidoSuite Program → Check PLC task, check that each of the output LEDs for the corresponding bit changes state.
Note: Check PLC can only be used in connected mode.
To complete this procedure, set system bit %S8 to 1. This is automatically accomplished by downloading a valid user application.
226 35011387 06/2011
Twido Programmable Controllers
The DIN Rail
35011387 06/2011
The DIN Rail
C
The DIN Rail
Introduction
You can mount the Twido controller and its expansions on a DIN rail. A DIN rail can be attached to a smooth mounting surface or suspended from a EIA rack or in a
NEMA cabinet.
Dimensions of the DIN Rail
The DIN rail measures 35 mm ( 1.38 in.
) high and 15 mm ( 0.59 in.
) deep, as shown below.
227
35011387 06/2011
The DIN Rail
Recommended Equipment
You can order the suitable DIN rail from Schneider Electric:
Rail depth
15 mm ( 0.59 in.
)
Catalogue part number
AM1DE200
228 35011387 06/2011
Twido Programmable Controllers
IEC Symbols
35011387 06/2011
IEC Symbols
D
Glossary of Symbols
Introduction
This section contains illustrations and definitions of common IEC symbols used in describing wiring schematics.
Symbols
Common IEC symbols are illustrated and defined in the table below:
Fuse
Load
AC power
DC power
Discrete sensor/input, for example, contact, switch, initiator, light barrier, and so on.
Ground
229
35011387 06/2011
IEC Symbols
2-wire sensor
Thermocouple element
230 35011387 06/2011
Twido Programmable Controllers
Agency Compliance
35011387 06/2011
Agency Compliance
E
Agency Requirements
Introduction
This section provides agency standards for the Twido products.
Standards
Twido controllers comply with the main national and international standards concerning electronic industrial control devices.
The following are specific controller requirements: z z z
EN 61131-2 (IEC 61131-2)
UL 508
UL 1604 / CSA 213 Class I Division 2 Groups A, B, C, D
35011387 06/2011
231
Agency Compliance
232 35011387 06/2011
Twido Programmable Controllers
Glossary
35011387 06/2011
Glossary
A
Analog potentiometer
It can be used to preset a value for an analog timer. All Modular controllers and
Compact 10 and 16 I/O controllers have one analog potentiometer. The Compact 24
I/O controller has two:
Analog Voltage Input Connector
Connects an analog voltage source of 0 through 10 VDC. The analog voltage is converted to a discrete value and is stored in a system word.
C
CAN
Cartridge Connector
A connector to attach an optional memory cartridge or an RTC.
Catch Input
Controller Area Network : field bus originally developed for automobile applications which is now used in many sectors, from industrial to tertiary.
Verify that you are receiving short input pulses (rising pulse of 40 μ s or falling pulse of 150 μ s minimum) from sensors without regard to the scan time.
35011387 06/2011
233
Glossary
CiA
CAN in Automation : international organization of users and manufacturers of CAN products.
COB
Communication OBject : transport unit on CAN bus. A COB is identified by a unique identifier, which is coded on 11 bits, [0, 2047]. A COB contains a maximum of 8 data bytes. The priority of a COB transmission is shown by its identifier - the weaker the identifier, the more priority the associated COB has.
Communication Adapter
An optional cartridge that can be attached to any Compact controller or Operator
Display Expansion Module to provide an optional Serial Port 2.
Communication Expansion Module
An optional module that can be attached to any Modular controllers communications expansion bus to provide an optional Serial Port 2.
Controller status output
A special function. This function is used in circuits, external to the controller, to control the power supply to the output devices or the controller power supply.
E
EDS
Electronic Data Sheet : description file for each CAN device (provided by the manufacturers).
ERR LED
An LED that illuminates when a detected error is detected in the controller.
Expansion connector
A connector to attach expansion I/O modules.
Expansion Connector Cover
A cover to protect the expansion connector.
234 35011387 06/2011
Glossary
Expansion I/O Module
Either a discrete or analog module that adds additional I/O to the base controller.
F
Fast Counting
A special function, it is available as a single up counter and single down counter.
These functions enable up counting or down counting of pulses (rising edges)on a discrete I/O. Compact controllers can be equipped with three fast counters. Modular controllers can have two fast counters.
Free Wire
I
The end of a discrete I/O cable whose wires do not have a connector. This scheme provides connectivity from Modular I/O to discrete I/O points.
I/O
Input/Output.
I/O terminals
Terminals on all Modular controllers and expansion I/O modules used to connect input and output signals. The input terminals accept both sink and source DC input signals. The output terminals are either transistor source or sink or relay contacts.
IN LED
An LED that illuminates when a corresponding input is on. All modules have IN
LEDs.
Input Filter
A special function that rejects input noises. This function is useful for addressing input noises and chatter in limit switches. All inputs provide a level of input filtering using the hardware. Additional filtering using the software is also configurable through TwidoSuite.
35011387 06/2011
235
Glossary
Input Simulators
An optional accessory for Compact controllers that is used for debugging. It can simulate input sensors to test application logic.
Input terminals
Terminals on the top of all Compact controllers used to connect input signals from input devices such as sensors, push buttons, and limit switches. The input terminals accept both sink and source DC input signals.
L
Latching input
A special function. This function is used to memorize any pulse with a duration less than the controller scan time. When a pulse is shorter than one scan and has a value greater than or equal to 100 μ s, the controller latches the pulse, which is then updated in the next scan.
M
Memory Cartridge
An optional cartridge available in two sizes: 32 KB and 64 KB (64 KB not available on Compact). It can be added to any controller for removable backup of applications or to load an application, if certain conditions exist. The 64 KB cartridge is also used to increase program memory.
Modbus Master Mode
Allows the controller to initiate a Modbus query transmission, with a response expected from a Modbus slave.
Modbus Slave Mode
Allows the controller to respond to Modbus queries from a Modbus master and is the default communications mode if no communication is configured.
236 35011387 06/2011
Glossary
O
Operator display expansion module
An optional module that can be attached to any Modular controller to display program information.
Operator display module
An optional module that can be attached to any Compact controller to display program information.
OUT LED
An LED that illuminates when a corresponding output is on. All modules have OUT
LEDs.
Output terminals
Terminals on the bottom of all Compact controllers used to connect output signals from output devices such as electromechanical relays and solenoid valves. The internal output relay contact is rated up to 240 VAC/2A or 30 VDC/2A.
P
PLS
Power Supply Terminals
The power supply is connected to these terminals to provide power to the controller.
The power voltage for a Compact controller is 100-240 VAC and 24 VDC for a
Modular controller.
PWM
A special function. This user-defined function block generates a signal on output
%Q0.0.0 or %Q0.0.1. This signal has a variable period but has a constant duty cycle, or on to off ratio of 50% of the period.
A special function. This user-defined function block generates a signal on output
%Q0.0.0 or %Q0.0.1. This signal has a constant period with the possibility of varying the duty cycle, or on to off ratio.
35011387 06/2011
237
Glossary
PWR LED
An LED that illuminates when power is supplied to the controller.
R
Removable Cover
A cover on all Compact controllers that can be removed to install an optional
Operator Display.
RTC
Real Time Clock.
RTD
Temperature detector of type PT100, PT1000 etc. Resistor Temperature Detector.
RUN LED
An LED that illuminates when the controller is executing a program.
S
Sensor power terminals
Supplies power to the sensors (24 VDC, 400 mA for -40DRF compact controllers and 250 mA for all other controllers). Output terminals are only intended for input devices and not be used as a source for driving external loads.
Serial Port 1
An EIA RS-485 connector used to download and monitor the controller operation using TwidoSuite.
Serial port 2
An optional port that can be configured as either EIA RS-232 or EIA RS-485.
STAT LED
An LED that blinks on and off to indicate a specific status of the user program.
238 35011387 06/2011
Glossary
T
Terminal cover
A cover on all Compact controllers to protect the input and output terminals.
V
Very Fast Counting
A special function available as an up/down counter, an up/down 2-phase counter, a single up counter, a single down counter, and frequency meter. The counter functions enable counting of pulses from 0 to 65,535 in single-word mode and from
0 to 4,294,967,295 in double-word mode. The frequency meter function measures the frequency of a periodic signal in Hz.
35011387 06/2011
239
Glossary
240 35011387 06/2011
Twido Programmable Controllers
Index
35011387 06/2011
Symbols
A
Accessories,
Adding a second serial port
Agency requirements,
Overview,
AS-Interface bus
Illustration,
AS-Interface Master module,
AS-Interface V2 bus
Reminder,
Assembling
Communication adapter,
Operator display expansion module, 69
Second serial interface expansion mod-
A C
B
Bases
Assembling an expansion I/O module, 42
Assembling to a second serial interface expansion module,
Assembling to a second serial interface expansion module with Operator Display,
Dimensions,
Disassembling an expansion I/O module,
Features,
How to Install a serial interface adapter,
Mounting positions,
Parts description,
Specifications,
Status,
Wiring diagrams,
,
Battery
External battery,
C
,
CANopen Master module,
Checking I/O connections,
Checking scan time,
Communication architecture, 27
241
35011387 06/2011
Index
Index
Compact
Backup external battery specifications,
Backup internal battery specifications,
Connect a DC power supply,
Connect an AC power supply,
Dimensions,
How to Install a serial interface adapter,
Input internal circuit,
Installing a memory cartridge, 57
Installing an operator display module,
Installing an RTC,
Mounting hole layout,
Operating range,
Output delay,
Parts description,
Power supply specifications,
Relay output contact,
Transistor source output contact,
Compact 10 I/O Controllers
Illustration,
Compact 16 I/O Controllers
Illustration,
Compact 24 I/O Controllers
Illustration,
Compact 40 I/O Controllers
Illustration,
Compact Bases
Installing on a DIN rail,
Options,
,
Compact bases
Compact Controllers Features
Configuration
Hardware,
Modular,
Connect a DC power supply
242
Connect a power supply
Connect an AC power supply
Controller status output , 178
Controllers
Dimensions,
Parts description,
Counters
Fast counters,
D
Dedicated function blocks,
Determining the state of Run/Stop input,
Dimensions
Operator display expansion module, 155
Second Serial Interface expansion mod-
DIN rail
15 mm AM1DE200 rail,
Discrete I/O assignment
Controller status output,
Fast counters,
PLS,
,
Double-word
Fast counters,
PLS,
E
35011387 06/2011
Expansion I/O modules
Disassembling from a base,
F
Fast counters,
Double-word,
Single-word,
G
Grafcet methods,
H
How to Install
Second serial interface expansion module with operator display,
Serial interface adapter,
Serial Interface adapter,
I
I/O connections
Checking,
I/O modules
Discrete,
I/O usage limits
Compact bases,
Modular bases,
IEC symbols,
Illustration
Compact 10 I/O Controllers,
Compact 16 I/O Controllers,
Compact 24 I/O Controllers,
Compact 40 I/O Controllers,
Initialization of objects,
Input internal circuit
Compact bases,
Input Simulators
Options,
35011387 06/2011
Index
Input simulators
Overview,
Input specifications
Installation preparation,
Installing
,
,
,
L
LED
Status,
M
Maximum hardware configuration,
Memory cartridge
Installing in a Compact,
Installing in a Modular,
Overview,
,
Specifications,
,
Minimum clearance
Compact,
Modular
Assembling to a second serial interface expansion module,
Assembling to a second serial interface expansion module with Operator Display,
Dimensions,
Disassembling of an operator display ex-
243
Index
Installing a memory cartridge, 75
Installing an RTC,
Mounting hole layout,
Output delay,
,
Parts description,
Power supply specifications,
Relay output contact,
Removing the terminal block, 74
Transistor sink output contact, 131 ,
Transistor source output contact,
,
Modular Bases
Disassembling of an operator display ex-
Modular bases
Installing on a DIN rail,
Modular Bases
Options,
Modular Bases Features
Mounting hole layout
Modular base,
O
Operating range
Compact bases,
Operator Display
Controller ID and states,
Serial port settings,
System objects and variables,
244
Operator display expansion module
Dimensions,
How to Install a serial interface adapter,
Parts description,
Operator display expansion modules
Disassembling from a Modular base, 69
Operator display module
Dimensions,
Installing in a Compact,
Parts description,
Options,
Communication expansion modules,
Input Simulators,
Operator display expansion module, 16
Real Time Clock cartridge, 114 ,
Terminal blocks,
Output delay
,
Output transistor specifications
Overview
Compact Controllers Features, 81
Operator display expansion module, 153
Real Time Clock cartridge, 114 ,
35011387 06/2011
P
Parts description
Bases,
Operator display expansion module, 153
Physical description
Analog potentiometer on Compact base,
Analog potentiometer on Modular base,
PLS,
Double-word,
Single-word,
Power restoration,
Power supply
Specifications,
Programming cables,
Programming port,
Pulse generator output,
Pulse width modulation,
PWM,
R
Real Time Clock cartridge
Overview,
,
Specifications,
,
Real-Time correction factor,
Relay output contact
Modular controllers,
,
Relay Output specifications
Removing
RTC
Installing in a Compact,
Installing in a Modular,
RUN/STOP input,
35011387 06/2011
Index
S
Scanning,
Cyclic,
Scanning
Second serial interface expansion modules
Assembling to a Modular,
Second Serial Interface expansion modules
Dimensions,
Second serial interface expansion modules with Operator Display
Assembling to a Modular,
Serial Interface adapters
How to Install in a Compact,
serial interface adapters
How to Install in an operator display expansion module,
Single counter
Down,
Up,
Single-word
PLS,
Very fast counters,
Special functions
Controller status output,
PLS,
Very fast counters,
Specifications
Operator display expansion module,
,
Real Time Clock cartridge,
,
Standards,
Starting,
245
Index
Status
Base,
Symbols,
System Diagnostic
T
Task cycle,
Telefast
Bases,
Dimensions,
Pre-wired systems,
System overview,
Wiring schematics,
Transistor sink output contact
Modular bases,
Modular controllers,
Transistor source output contact
Compact bases,
Modular bases,
Modular controllers,
U
Unintended operation of external equipment,
V
Double-word,
W
Warm restart,
Wiring diagrams
Base,
,
Modular,
Wiring schematics
Telefast bases,
246 35011387 06/2011
Download