Omron NT600M Series Operation Manual
PDF
Document
Advertentie
Advertentie
NT600M
Programmable Terminal
Operation Manual
Revised October 1997
iv
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers
to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
IBM and IBM PC/AT are registered trademarks of International Business Machines Corporation.
MS-DOS is a registered trademark of Microsoft Corporation.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of
information.
Note Indicates information of particular interest for efficient and convenient operation
of the product.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1991
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any
form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is
constantly striving to improve its high-quality products, the information contained in this manual is subject to change
without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no
responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1-2
1-3
1-4
1-5
1-6
1-7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminology and NT-series Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Support Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Switch Settings, Installation, and Wiring . . . . . . . . . . . . .
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the NT600M PT in a Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring and Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS-232C Interface Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12-key Function Key Units (for DN-type PTs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Function Key Units (to DN-type PTs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3-2
3-3
3-4
Powering Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transferring Data to and from the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
Display Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4-2
4-3
4-4
4-5
4-6
4-7
4-8
4-9
4-10
4-11
4-12
4-13
Character Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Graphics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Screen Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overlapping Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Numeric Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Character Strings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bar Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Graphics Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xi
xii
xii
xii
1
2
4
5
6
9
10
13
15
16
20
22
23
25
27
28
28
31
32
32
35
37
39
40
41
42
42
43
45
46
47
47
48
48
50
50
vii
TABLE OF CONTENTS
SECTION 5
Input Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5-2
5-3
On-screen Switch Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inputting Numeric Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standalone Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6-2
6-3
Configuration of System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Menu and Transmit Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 7
Online Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1
7-2
Host to PT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PT to Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 8
Maintenance and Inspection . . . . . . . . . . . . . . . . . . . . . . .
8-1
8-2
8-3
8-4
Checking Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the Lithium Backup Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RUN Mode Function Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
54
56
59
61
62
63
71
75
76
76
79
80
80
81
83
Appendices
A
B
C
D
Standard Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Check Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Characters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
viii
85
87
91
93
95
97
About this Manual:
This manual describes the installation and operation of the NT600M Programmable Terminals (PTs) and
includes the sections described below. Further information is provided in manuals on the Host Interface
Units and Support Tool. Refer to the list in Section 1 Introduction.
Please read this manual completely and be sure you understand the information provide before attempting to install and operate a Programmable Terminal.
Section 1 introduces the PTs, describes the terminology used in this manual, and provides examples
of system configurations for programming and operation.
Section 2 provides procedures and specifications required to set up a PT system, including hardware
switch settings and installation.
Section 3 provides steps required for initial PT operation.
Section 4 describes functions used to create screens and control display attributes on the PT.
Included is automatic transfer of data from the host computer via character string and numeral tables.
Section 5 describes functions used to input data on-screen and transfer it to the host computer via
the numeral table.
Section 6 describes basic data transfer and maintenance functions.
Section 7 describes transferring screens online to and from the host computer.
Section 8 provides troubleshooting and basic maintenance methods, including battery replacement.
Appendices of OMRON products used with PTs, PT specifications, and a memory check table are
provided at the back of the manual.
! WARNING Failure to read and understand the information provided in this manual may result in
personal injury or death, damage to the product, or product failure. Please read each
section in its entirety and be sure you understand the information provided in the section
and related sections before attempting any of the procedures or operations given.
ix
PRECAUTIONS
This section provides general precautions for using the Programmable Terminal.
The information contained in this section is important for the safe and reliable application of the Programmable Terminal. You must read this section and understand the information contained before attempting to set up or operate a
Programmable Terminal.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xii
xii
xii
xi
Safety Precautions
1
3
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2
General Precautions
The user must operate the product according to the performance specifications
described in the operation manuals.
Before using the product under conditions which are not described in the manual
or applying the product to nuclear control systems, railroad systems, aviation
systems, vehicles, combustion systems, medical equipment, amusement
machines, safety equipment, and other systems, machines, and equipment that
may have a serious influence on lives and property if used improperly, consult
your OMRON representative.
Make sure that the ratings and performance characteristics of the product are
sufficient for the systems, machines, and equipment, and be sure to provide the
systems, machines, and equipment with double safety mechanisms.
This manual provides information for using the Programmable Terminal. Be sure
to read this manual before attempting to use the software and keep this manual
close at hand for reference during operation.
! WARNING It is extremely important that Programmable Terminals and related devices be
used for the specified purpose and under the specified conditions, especially in
applications that can directly or indirectly affect human life. You must consult
with your OMRON representative before applying Programmable Terminals to
the abovementioned applications.
! WARNING Do not use input functions such as PT touch switches for applications where
danger to human life or serious damage is possible, or for emergency switch
applications.
3
Safety Precautions
Read these safety precautions carefully and make sure you understand them
before using the Programmable Terminal so that you can use it safely and correctly.
Safety Conventions and
their Meanings
!
DANGER
This operation manual uses the following conventions and symbols to indicate
cautions, warnings, and dangers in order to ensure safe use of the PT. The cautions, warnings, and dangers shown here contain important information related
to safety. The instructions in these cautions, warnings, and dangers must be
observed.
The conventions used and their meanings are presented below.
Indicates information that, if not heeded, is likely to result in loss of life or serious
injury.
! WARNING Indicates information that, if not heeded, could possibly result in loss of life or
serious injury.
! Caution
xii
Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
Safety Precautions
! Caution
3
• The ROM may be destroyed if it is mounted while power is being supplied to
the PT.
• Screen memory must be initialized before using a new PT. If the PT is used as
shipped from the factory without initialization, messages indicating errors in
the host will not be displayed.
• After the transfer has been completed, be sure to return to RUN Mode by
pressing the Buzzer Key, Up Key, and Down Key simultaneously. If the power
is turned off or if a reset is executed without having first returned to RUN Mode,
the data that has been transmitted will be corrupted. If that occurs, a message
will be displayed on the screen to indicate that the data has been corrupted.
• If a load (e.g., a buzzer or alarm light) is connected to a 10/02 Terminal or a
32/16 Terminal, it will actually operate. This can be potentially dangerous, so
exercise caution.
• The lithium battery can explode if placed into a fire, or it can explode, burn, or
leak if the + and -- terminals are short-circuited or if the battery is recharged or
dismantled. Handle the battery with care.
xiii
SECTION 1
Introduction
This section provides information necessary to familiarize you with the features and parts of a PT system.
1-1
1-2
1-3
1-4
1-5
1-6
1-7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminology and NT-series Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-1 NT600M Programmable Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-2 Screen Data Memory Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-3 System ROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-4 Host Interface Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-5 12-key Function Key Units (for DN-type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Support Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Nomenclature and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7-1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7-2 Rear Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
4
5
6
6
6
7
8
9
9
10
13
13
14
1
Introduction
1-1
Section 1-1
Introduction
This manual describes the installation and operation of NT600M Programmable Terminals (PTs). Programmable Terminals have three main functions:
1) monitoring operating conditions, 2) directing on-site personnel, and 3) inputting data.
Host
Directing
operations,
monitoring
conditions
Programmable Terminal
Device
Instructions
(Programmable Controller or FA computer)
1) PTs can monitor, in real time, system and equipment operating conditions,
production quantities, and so on. The PT display can show, for example,
whether the production line is operating normally, and what percentage of the
production target has been met. Bar graphs can be continually updated as
data is received from the host. On-screen characters can be displayed as
plain, reverse video, blinking, or reverse blinking. In addition, lamps, bar
graphs, and figures can all be created. Screen data can be registered at the
PT in advance, and can be displayed simply by transmitting the appropriate
screen number from the host.
Lamp Display
Bar Graph Display
Operating conditions
Run
Normal
Emergency
stop
Normal
Error
Conveyance System
Rotation (rpm)
Air
L1-0
0
Run
Graphics Display
Oil
1800
3600
Oil pressure (kg/cm2)
M10
L2-0
0
5.0
L1-2
10
2) PTs can inform on-site personnel of current conditions that need to be addressed. Depending on the nature of the situation, built-in or external buzzers
can be sounded to alert personnel to problems that have developed. Depending on factors such as distance from the host, the number of devices
2
Introduction
Section 1-1
connected, and the response time, any of a variety of communications methods may be selected.
EMERGENCY STOP
Abnormality
occurs!
Device
(Flashing display)
Air pressure is abnormal.
Please check
PC
PT
3) PTs can input data for controlling certain operations and communicating
information to the host. Setting switches and a ten-key pad allows a PT to be
used as a control panel. In the example shown below, touch switches used
for inputs to the host are displayed. When this screen is displayed, the onsite operator can control a device by means of touch switches.
Crane Operation
Run
Normal
operation
Up
Left
Stop
Device
Right
(Touch switches
created by Support
Tool.)
Down
PC
PT
Aside from touch switches, the PT can provide inputs by means of numeric
settings and externally connected switches. The illustration below shows a
numeric setting screen that can be used for inputting numeric data.
Tank A
0654
Tank C
0000
Tank E
0800
MENU
Tank B
0650
1
2
3
4
5
6
7
8
9
0
HO
ME
C
Tank D
0550
Tank F
0990
Change
Set
The screens used for these operations can be created in advance by using
the “Support Tool” software on a personal computer. The screen data that is
created using the Support Tool can be printed out, saved to a diskette, or
transferred to the PT. An FA Computer, a Programmable Controller, or a
compatible device can be used as the host.
3
Features
1-2
Section 1-2
Features
Wide Selection of Models
The NT600-series PTs provide a choice of three models depending on the
input specifications of your system. You can also choose either of two types
of display devices. Any of six methods can be selected for communicating
with the host, which may be an FA Computer, a Programmable Controller, or
a compatible device.
Drip-proof Structure
The PTs have a drip-proof front panel structure when the dust cover is
mounted to protect the display area and the key input area.
Clear Display
Either of two types of display can be selected: an STN liquid crystal display
with a backlight, or a yellow-orange EL (electro-luminescent) display.
Two-way Communications
with Host
Screens at the PT can be changed, messages can be received, and numbers can be displayed from the host. The PT, in turn, can transmit key inputs
and numbers back to the host.
Display Functions
A maximum of 1000 screens can be registered. As many as 64 rectangular
or circular lamps can be created for a single screen, up to a total of 256 and
direct connection can be used without restrictions. Character strings, numerals, bar graphs and simple graphics can also be created and registered.
Input Options
Depending on the input specifications of the control system, any of three
NT600M types may be selected: the touch panel (DT) type, the non-touchpanel type (DN), and the function key type (DF). DT-type PTs enable the user
to create and use as many as 64 touch switches per screen, up to a total of
256 and direct connection can be used without restrictions. DN-type PTs allow the connection of 12-key Function Key Units, up to a maximum of 32 input points and 16 output points. DF-type PTs enable various inputs by means
of 12 function keys.
Standalone Capability
Screens can be changed on-site, using touch switches, function keys, or external inputs. The screen-changing capability can be allocated to touch
switches or function keys at the time that the screens are created in advance
by the Support Tool.
Online Transfer
Screen data can be written by means of commands from the host when an
RS-232C or RS-422A Host Interface Unit is mounted.
Direct Connection
The direct connection function can be used to directly correlate host data
areas with PT operations. Ordinarily, instructions to the PT and inputs from
the PT are executed in response to commands from the host. Such commands are not required for direct connection, however, and thus the size of
the host program can be greatly reduced. The direct connection can only be
used by DT-type PTs, with the restrictions on Host I/F Units, System ROM,
and Support Tool versions shown in the following table.
PT
System ROM
NT600M-DT12 NT600M-SMR31-E
2
NT600M-DT211 NT600M-SMR32-E
Host Interface Unit
NT600M-LK201 Host Link Interface Unit
NT600M-LB122-V1 C200H Host Interface Unit
Support Tool
NT20M-ZASAT-EV4
(Version 4.0
4 0 or later)
NT-ZA3AT-EV2
When direct connection is used, the PT data is as follows:
4
Lamps
255 per screen (with no limit on number registered)
Touch switches
128 per screen (with no limit on number registered)
Character string data
memory
50 places per screen (with a maximum of 512
registered)
Terminology and NT-series Manuals
1-3
Section 1-3
Terminology and NT-series Manuals
Names of items in this manual related to the NT-series Programmable Terminals and SYSMAC C-series Programmable Controllers are defined in the
following tables.
The following abbreviations are used in the text.
Abbreviations
Abbreviation
Term
Meaning
PT
Programmable Terminal
Refers to an OMRON NT-series Programmable Terminal.
PC
Programmable
Controller
Refers to an OMRON SYSMAC C-series or CV-series Programmable
Controller, or programmable controllers manufactured by other companies.
I/F
interface
A communications device that connects the Programmable Terminal with
peripheral devices.
I/O
input/output
Refers to PT and PC inputs and outputs.
SYSMAC Terminology
Terminology
Explanation
SYSMAC
A generic name for OMRON’s Programmable Controllers.
Host Link System
A system employing SYSMAC C-series Host Link Units used to create a communications bus
between PCs, between PCs and PTs, etc.
SYSMAC BUS
A remote I/O network created between SYSMAC C-series PCs and input/output devices.
C200H
An OMRON SYSMAC C-series Programmable Controller.
Reference Manuals
Name of Manual
The NT20M/NT2000M Series and NT600M Series are covered in the seven
manuals described below.
Contents
Manual No.
NT20M/NT2000M Operation
Manual
This manual provides specifications, functions, and operating
instructions for the NT20M and NT2000M Programmable Terminals.
V001
NT600M Operation Manual
This manual provides specifications, functions, and operating
instructions for NT600M Programmable Terminals.
V002
NT-series Host Interface Unit
Operation Manual
This manual covers the commands, controls, and communications
specifications for operating the NT20M and the NT600M. Refer to
this manual when programming host computer communications.
V003
NT20M/NT600M Support Tool
Operation Manual
This manual covers methods for creating screens, including screen
data preparation, switches, lights, and alarms.
(for NT20M-ZASAT-EV4)
V004
NT-series Host Interface Unit
Direct Connection Operation
Manual
This manual covers the Direct Connection feature which has been
added to the Host Interface Unit.
V015
NT-series RS-232C/RS-422A
Interface Unit Operation Manual
This manual covers the commands, controls, and communications
specifications for operating the NT20M and the NT600M with the
RS-232C/RS-422 Interface Unit. Refer to this manual when
programming host computer communications.
V016
NT-series Support Tool Operation
Manual
This manual covers methods for creating screens, including screen
data preparation, switches, lights, and alarms. (NT-ZA3AT-EV2)
V028
5
Models
1-4
1-4-1
Section 1-4
Models
NT600M Programmable Terminals
There are three types of NT600M PTs, shown in the following table. There
are also two types of display from which to choose.
PT
Touch panel (DT)
Display device
Model number
LCD with backlight
NT600M-DT122
EL
NT600M-DT211
Without touch panel (DN)
EL
NT600M-DN211
Function Key Unit (DF)
LCD with backlight
NT600M-DF122
System ROM
Purchased separately.
Varies according to
which Host Interface
Unit is installed.
installed
Screen data mem.
Purchased separately.
Screen data memory
boards can be SRAM
or IC sockets for
commerciallyy
available
il bl EPROM or
EEPROM.
NT600M-jj122/211
Type of Unit
DT: Touch-panel
DN: Non-touch-panel
DF: Function-key
NT600M-series, basic model
1-4-2
Screen Data Memory Boards
A Screen Data Memory Board is required for registering screen, character
string, and numeric data. The Screen Data Memory Board is not built into the
PT and must be purchases separately.
NT600M-Mjjjj
Memory capacity
Type of memory
P: IC socket type
R: SRAM-type
Screen Data Memory Board
NT600M-series, basic model
Model
NT600M-MP251
NT600M-MR641
NT600M-MR151
NT600M-MR251
Type of memory
IC socket type
SRAM
SRAM
SRAM
Memory capacity
(Depends on memory chip.)
64K
128K
256K
Remarks
IC-socket for memory chip*
Type and capacity fixed.
Type and capacity fixed.
Type and capacity fixed.
Note *The NT600M-MP251 provides only an IC socket and is not equipped with a
memory chip. The memory chip must be installed by the user.
Memory Chips
6
The memory chips that can be installed in the NT600M-MP251 IC socket are
shown in the table below. Use either the model shown here or an equivalent.
Models
Section 1-4
If an equivalent is not used, the capacity of the memory backup battery may
not be sufficient.
Type
SRAM
EPROM
EEPROM
Memory Capacity and
Number of Screens
Memory
capacity
32K bytes
Model
Recommended memory chips
RAM22-15
HM62256ALP-15 (Hitachi).
128K bytes
RAM13-10
HM628128LP-10 (Hitachi).
64K bytes
ROM-KD-B
M5M27C512AK-12 (Mitsubishi)
128K bytes
ROM13-12B
HN27C101AG-12 (Hitachi).
256K bytes
ROM23-15B
M5M27C201K-15 (Mitsubishi)
32K bytes
EER22-20
HN58C256P-20 (Hitachi).
Screen memory capacity varies according to which Screen Data Memory
Board is installed. The screen memory capacity, in turn, determines the number of screens that can be registered. Use the table below as a guide to select the amount of memory suitable for your needs.
Screen memory capacity
32K bytes
Number of registered screens
Mostly messages: 40 screens
Mostly graphics: 15 screens
Mostly messages: 120 screens
Mostly graphics: 40 screens
Mostly messages: 250 screens
Mostly graphics: 100 screens
Mostly messages: 600 screens
Mostly graphics: 200 screens
64K bytes
128K bytes
256K bytes
Note The table above is strictly a guide. If the messages or other display data per
screen increase, the number of screens that can be registered will decrease.
Likewise, if the messages decrease, the number of screens that can be registered will increase.
1-4-3
System ROM
Purchase the System ROM according to the NT600M and Host Interface Unit
models that are used.
NT600M-DT122/211
NT600M-DN122/211
NT600M-DF122
NT600M
Host I/F Unit
NT600M-DT122
NT600M-DT211
NT600M-LK201 (RS-232C) (see note 1)
NT600M-LK202 (RS-422A)
NT600M-LK201 (Host Link) (see note 1)
NT600M-RT201 (SYSMAC BUS)
NT600M-LB122-V1 (C200H) (see note 1)
NT600M-SMR01-EV1
---
NT600M-SMR02-EV1
---
NT600M-LK201 (see note 1) (Host Link)
---
NT600M-SMR31-E (Direct connection
can be used when version 4 of the
Support Tool is used.)
NT600M-LB122-V1 (C200H) (see note 2)
---
NT600M-SMR32-E (Direct connection
can be used when version 4 of the
Support Tool is used.)
7
Models
Section 1-4
Note 1. RS-232C Interface Units and Host Link Interface Units are the same
(NT600M-LK201). Change the communications specifications by means
of the internal DIP switch.
NT600M-SMRjj-EVj
Version
Overseas specifications (English)
Communications
01: RS-232C, RS-422A, SYSMAC WAY,
SYSMAC BUS Interface
02: C200H Host Interface
03: SYSMAC BUS/2, 32/32 Parallel Interface
31: Host Interface Direct Connection
32: C200H Host Interface
System ROM
NT600M-series, basic model
2. For the NT600M-LB122-V1, set the pin 4 of the Interface Unit’s DIP switch
SW2 ON or OFF to determine whether to allow direct connection or not.
Without direct connection: Turn ON pin 4 of SW2
With direct connection: Turn OFF pin 4 of SW2.
1-4-4
Host Interface Units
The Host Interface Unit provides the interface for communications between
the PT and the host (either a Programmable Controller or an FA computer).
The Host Interface Unit models that can be used with the NT600M PT are
shown in the table below. Select the Host Interface Unit to match the communications specifications of the system.
NT600M-jjjjj
Model number
Communications specifications
LK: Serial communications
RT: Remote communications
LB: C200H Host Interface
NT600M-series, basic model
Name
Model number
RS-232C Interface Unit
NT600M-LK201
RS-422A Interface Unit
NT600M-LK202
SYSMAC BUS Interface Unit
NT600M-RT121
Host Link Interface Unit
NT600M-LK201
C200H Host Interface Unit
NT600M-LB122-V1
8
Remarks
Connect for general-purpose communications with an FA
computer or personal computer.
computer For communications with a
SYSMAC PC, connect to an ASCII Unit.
Can be connected as a Slave Unit in a SYSMAC Wired Remote
I/O System.
Can communicate one-to-one with a SYSMAC Host Link Unit.
Can be connected to a SYSMAC C200H, C20H, C40H, or C60H
PC to provide the functions of an Expansion I/O Rack.
Support Tools
1-4-5
Section 1-5
12-key Function Key Units (for DN-type)
Function-key input for NT600M non-touch panel (DN) type models is made
possible by attaching an NT600M-FK210 12-key Function Key Unit.
NT600M-DN211 PT
(Without touch panel)
NT600M-FK210
12-key Function Key Unit
1-5
Support Tools
NT600M screen data, memory table data, and system data are all created by
the Support Tool. In order to fully utilize the functions of the NT600M PTs,
use the NT-ZA3AT-EV2 Support Tool or a version of NT20M-ZASAT-EV4 or
higher.
NT20M-ZASAT-EVj
Version
Overseas specifications (English)
Compatible platform
AT: IBM PC/AT compatible
Floppy disk size
3: 3.5 inch
5: 5.25 inch
S: 3.5 and 5 inch
Support software
NT model
NT:
NT20M:
NT Series (common)
NT20M Series
Contrast Between Functions when New and Old Versions of Peripheral Devices are Used
(1) I/O Functions
Function
NT20M-ZASAT
Support Tool
NT600M-SMRjjj
System ROM
PT Models
Remarks
-EV4
onwards
F
-EV1
-EV1
-E
X
F
X
All models
X: Only “lit” is available
for bit designation
control.
Touch switches: Reverse
video display during input
(yes or no)
F
X
F
X
DT-type only
X: Setting not possible.
Standalone function
F
X
F
X
All models
X: Cannot be used.
Lamps (bit designation)
Display attributes: Lit or
flashing
9
System Configuration
Section 1-6
(2) Display Functions
Function
NT20M-ZASAT
Support Tool
-EV4
onwards
NT600M-SMRjjj
System ROM
-EV1
-EV1
PT Models
-E
Vertical and
horizontal
display
X: Horizontal only.
Bar
Display width
graphs enlargement (2
to 255 dots)
+/-- display
% value
enlargement
display
X: Select either 8 or 16
dots.
X
F
F
X
All models
Lamp display:
Rectangular or circular
Lamps/touch switches:
Guide character mark
input
Touch switches: Solid or
rectangular frame
Numeric setting 10-key
layout
Numeric display
enlargement (64x max.)
Direct connection
Remarks
X: + direction only.
X: Equivalent display
only.
X: Rectangular only.
X: Mark input not
possible.
DT-type only
F
X
F
X
All models
(See note 1.)
F
X
F
X
All models
See note 3.
SMR 31-E/32-E
X: Rectangular frame
only.
Only when the screen
attribute “10-key” is set to
“User.”
X: Equivalent display
only.
DT-type only
Notes 3. Some restrictions may apply, depending on the PT model.
4. In order to use the direct connection function, a Support Tool version of
“-EV4” or higher must be used.
1-6
System Configuration
In order to operate the NT600M, connect a personal computer or a Programmable Controller, to serve as a host, to the Host Interface Unit (sold separately) at the back of the NT600M. For details on connecting the Host Interface Unit, and on host programs, refer to the Host Interface Unit Operation
Manual.
The following interfaces can be used for communications: RS-232C,
RS-422A, Wired Remote I/O System (SYSMAC BUS), Host Link System
(SYSMAC WAY), or C200H Host Interface. A Screen Data Memory Board,
NT600M-MP/MRjjj, is also required and must be purchased separately.
10
System Configuration
Section 1-6
Using the NT600M-LK201 Host Interface Unit, the Programmable Terminal
can be connected one-to-one to a personal computer or to an ASCII Unit
mounted to a Programmable Controller.
RS-232C Interface
Personal computer
C200H, C500, C1000H,
or C2000H PC
NT600M with
NT600M-LK201
NT600M with
NT600M-LK201
RS-232C
ASCII Unit
RS-232C
15 m max.
15 m max.
Using the NT600M-LK202 Host Interface Unit and 3G2A9-AL004-(P) and
3G2A9-AL001 Link Adapters, up to 16 Programmable Terminals can be connected to a to a PC through an ASCII Unit, or to an FA computer.
RS-422A Interface
C-series PC
Personal computer
ASCII Unit
(RS-232C)
3G2A9-AL004-(P)E
Link Adapter
RS-422A
Cable length: 500 m max.
3G2A9-AL001
Link Adapters
Branch lines: 10 m max. each.
NT600M with
NT600M-LK202
11
System Configuration
Section 1-6
Using the NT600M-LK201 Host Interface Unit, the Programmable Terminal
can be connected one-to-one to a Host Link Unit mounted to a Programmable Controller.
Host Link Interface
Mini H-type, C200H, C500, C1000H, C2000H PC
NT600M with
NT600M-LK201
RS-232C
Host Link Unit
15 m max.
SYSMAC BUS Interface
Using NT600M-RT121 Host Interface Units, up to 8 Programmable Terminals
can be connected to a PC through a Wired Remote I/O Master Unit.
8 Terminals max.
C200H, C500, C1000H, or
C2000H PC
NT600M with
NT600M-RT121
Remote I/O
Master Unit
200 m max. (2 wire cable)
C200H Host Interface
With an NT600M-LB122-V1 (for direct connection) Interface Unit, the interface is set up simply by connecting one-to-one with C200H-CN221 Connection Cable to a C200H CPU Rack or Expansion I/O Rack. It is also possible
to connect a PT to a C20H, C28H, C40H, or C60H CPU Unit or I/O Units. Be
sure to use a noise filter when connecting CjjH. Refer to the Host Interface
Units Operation Manual for details.
Be sure to use a noise filter (TDK’s ZGB2202-O1U or equivalent) when connecting to the Mini H-type PC.
1, 2, 3... 1.
2.
3.
4.
The noise filter must be inserted into the power line of the Mini H-type
PC.
The distance between the noise filter and the Mini H-type PC must be as
short as possible.
Keep the noise filter away from high-tension lines.
The case of the noise filter must be grounded to the FG terminal of the
Mini H-type PC.
Noise filter
1
IN
24 V
2
12
4
+
OUT
24 V
3
--
Nomenclature and Functions
Section 1-7
In a C200H PC System, you can ordinarily connect two Expansion I/O Racks to
the CPU Rack. The C200H Host Interface Unit itself, however, functions as an
Expansion I/O Rack, and therefore when using a C200H Host Interface Unit, you
can only connect one other Expansion I/O Rack. (If the CPU Rack is either
C200H-CPU02 or C200H-CPU22, it is not possible to connect both an Expansion Rack and a PT.)
CPU Rack
C20H/28H/40H/60H
CPU Unit
C200H Expansion I/O
Connection Cable
CjjH I/O Unit
Expansion I/O Rack
NT600M PT +
NT600M-LB122-V1
NT600M PT + NT600M-LB122-V1
1-7
1-7-1
Nomenclature and Functions
Front Panel
The illustrations below show the front panels of PTs with and without touch
panels (i.e., DT-type and DN-type PTs) and PTs with function keys (i.e., DFtype PTs). A 12-key Function Key Unit can be attached to a DN-type PT to
give it the same outer appearance and functions of a DF-type PT.
NT600M-DT/DNjjj: Programmable Terminals With and Without a Touch Panel
POWER Indicator (green)
Lit while power is on.
System Keys
Used for maintenance of the N600M,
selecting the System Menu, etc. Used
during operation for scrolling the
screen and inputting numeric values.
RUN Indicator (green)
Lit during operation
BAT LOW Indicator (red)
Lights if the lithium
battery voltage level
drops.
Display
Dust-proof Cover (liquid crystal type only)
Covers the contrast control. Turning the
contrast control clockwise increases the
contrast.
Touch Switches (touch panel type only)
Used as an input device corresponding to
the display screen.
13
Nomenclature and Functions
Section 1-7
NT600M-DF122: Programmable Terminals with Function Keys
Display
POWER Indicator (green)
Lit while power is on.
System Keys
Used for maintenance of the
NT600M, selecting the System
Menu, etc. Used during operation for scrolling the screen and
inputting numerical values.
RUN Indicator (green)
Lit during operation
BAT LOW Indicator (red)
Lights if the battery level
drops
Drip-proof Cover (liquid crystal type only)
The contrast control is behind this cover. Turning it clockwise increases the
contrast.
Function Keys
Used for input.
Note The operation of the BAT LOW LED will be unstable if a battery is not
installed.
1-7-2
Rear Panel
All Models (NT600M-DT/DN/DFjjj)
Switch cover
Host Interface Unit connector
This connector is used for connecting
to a Host Interface Unit.
Memory Board fitting
This fitting comes off by pulling up
on the black knob. To put the fitting back on, push down until the
knob snaps into place.
Connector cover
The Support Tool interface connector is located under this cover. This is used when transferring screen data between the
NT600M and Support Tool.
Memory Board installation space
Insert the Screen Data Memory
Board here.
Function Keys
(DF-type only)
I/O interface
connector
System ROM cover
Open this cover to access the
System ROM socket.
Terminal block
Switch Cover Area
Lithium battery
Reset switch
Pressing this switch initializes the NT600M.
The status of screen
data before initialization
is retained.
System DIP switch
14
SECTION 2
Switch Settings, Installation, and Wiring
This section provides procedures to set hardware switches and install the PT.
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 System DIP Switch Settings (SW1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Mounting System ROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 Screen Data Memory Board Settings and Installation . . . . . . . . . . . . . . . . . . . . .
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Installation Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Mounting Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-1 Terminals with Function Keys (DF-type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3-2 PTs With (DT-type) and Without (DN-type) Touch Panels . . . . . . . . . . . . . . . . .
Installing the NT600M PT in a Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring and Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-1 Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-2 AC INPUT Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-3 LG and GR Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-4 HOST RUN INPUT Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-5 ALM OUTPUT Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS-232C Interface Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12-key Function Key Units (for DN-type PTs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Function Key Units (to DN-type PTs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
16
17
18
20
20
21
22
22
23
23
25
25
25
26
26
27
27
28
28
15
Switch Settings
2-1
Section 2-1
Switch Settings
There are switches to set under the switch cover on the back of the Terminal
and also on the Host Interface Unit. For Host Interface Unit switch settings,
refer to the Host Interface Unit Operation Manual.
2-1-1
System DIP Switch Settings (SW1)
The 8-position DIP switch for system settings is located under the DIP switch
cover on the back of the Terminal. Be sure that power is off when changing
switch settings.
SW1
ON
1
(The settings at the time of shipping
are as shown on the left.)
2
3
4
5
6
7
8
Communications specification
(only for when NT600M-LK201 is mounted)
ON:
Host Link
OFF: RS-232C
Not used.
Mode change enable/disable
ON:
Enable
OFF: Disable
Not used.
Bit designation for lamps/touch switches
ON:
0 to 63
OFF: 0 to 111
Reserved for system use. (Always keep ON.)
HOST RUN input enable/disable
ON:
Disable
OFF: Enable
Automatic reset after communications error
ON:
No automatic reset.
OFF: Automatic reset.
16
Switch Settings
Pin no.
Section 2-1
Setting
Content
1
Automatic reset after
communications error.
ON: No automatic reset.
OFF: Automatic reset.
“Automatic reset” means that, when an error occurs, no error message
will be displayed and the next command will be executed when received.
“No Automatic reset” means that, when an error occurs, an error message will be displayed and operation will stop. If an RS-232C or RS-422A
Interface Unit is mounted, the host will be notified that an error occurred
and there will be no automatic reset regardless of whether this pin is set
to ON or OFF.
2
Host RUN input enable/disable
ON: Disable
OFF: Enable
If this pin is turned OFF, then the host RUN input will be enabled and PT
operation can be controlled by external sequences. If this pin is set to
ON, the PT will operate but when the host RUN input turns OFF, Host
Error will be displayed and operation will stop.
3
ON
This pin is reserved for system use, and must remain set to ON. If this
pin is set to OFF, messages will not display properly.
4
Bit designation for lamps and
touch switches
This pin designates the bits for lamp and touch switch display control for
when Host Link Interface Units or C200H Host Interface Units are used.
5
Not used.
---
6
Mode change enabled/disable
ON: Enable
OFF: Disable
“Mode change” refers to changing between the System Menu and Transmit Mode, Maintenance Mode, or RUN Mode. When an RS-232C or
RS-422A Host Interface Unit is used, mode changes can be prohibited
by means of a command from the host.
7
Not used.
---
8
Communications specification
setting (only when NT600M-LK201
is used)
ON: Host Link Unit
OFF: RS-232C
The NT600M-LK201 can be used as either a Host Link Interface Unit or
an RS-232C Interface Unit. Operation will not be possible if the setting of
this switch does not match the communications system. If another type
of Host Interface Unit is mounted, this setting will be ignored.
2-1-2
Mounting System ROM
Turn off the power supply to the PT and mount the System ROM into the PT
as described below.
1, 2, 3... 1.
Open the System ROM cover on the back of the PT.
System ROM cover
NT600M-DF122 only
17
Switch Settings
Section 2-1
2.
When the System ROM cover is opened, the IC socket will be exposed.
Turn the tightening screw (located to the left of the IC socket) to align
the slot with the O (open).
Label
Tightening
screw
3.
Mount the ROM to the socket in the direction indicated on the label and
turn the tightening screw clockwise to the C (close) secure the ROM.
Socket
0
0
Insufficiently tightened
! Caution
The ROM may be destroyed it mounted while power is being supplied to the PT.
Turn off the power supply before mounting the System ROM.
Notes 1. The PT may not operate properly if the IC socket is not completely secured. Be sure to install the System ROM securely.
2. OMRON reserves all copyrights to the programs on the System ROM.
Copying these programs is forbidden.
2-1-3
Screen Data Memory Board Settings and Installation
There are two types of Screen Data Memory Board: SRAM type and IC socket type. The NT600M-MP251 Screen Data Memory Board does not come
with a memory chip installed, and the memory chip must be purchased separately.
The memory type and capacity must be set for the NT600M-MP251.
Switches SW M1 and SW M2 are used to set the type and capacity of the
screen data memory chip installed in the top socket of the Screen Data
18
Switch Settings
Section 2-1
Memory Board. Set these switches to match the memory chip which is installed.
NT600M-MP251
Socket
The factory-set default setting is shown at the left.
Top
Middle
Bottom
SW M2 SW M1
Connector
Settings
SW M2
SW M1
Screen data memory
Top
Bottom
64K, EPROM
Middle
Bottom
128K, EPROM
Bottom
Bottom
256K, EPROM
Top
Middle
32K, EEPROM
Note 1. Be sure that the power is off when changing the settings. If settings are
made with the power on, memory may be lost or damaged.
2. Carefully check the switch settings and the memory chip before turning
the power on. If the memory is different from that specified on the switch
settings, the PT will not operate correctly.
Installation
Install the Screen Data Memory Board in the order shown below. If the Host
Interface Unit is mounted, remove it before installation.
1, 2, 3... 1.
Turn off the power supply to the PT.
19
Installation Environment
Section 2-2
2.
Place the Screen Data Memory Board on the main rail, push the spacer
in the direction of the arrow until it makes a clicking sound, and line the
board up with the connector.
Rail
Spacer
Connector
3.
Lined up with connector
Holding the Memory Board’s installation fitting as shown in diagram A,
insert the black latch on the bottom into the hole in the main unit and
press the black knob down until it clicks into place.
When the knob is
pulled up, it looks
like Illustration A
on the left.
Black knob
Installation fitting
A
Black latch
B
Installation fitting
Spacer
Screen Data Memory Board
When removing the Screen Data Memory Board, first turn off the power to
the PT and then remove the installation fitting by pulling up on the black
knob. Then pull the Memory Board’s spacer in the opposite direction of that
shown above and take out the Memory Board.
2-2
Installation Environment
The NT600M has strong environmental resistance and high reliability, but you
can maximize system reliability and make the most of its functions by observing the following considerations during installation.
2-2-1
Installation Site
Avoid installing the NT600M where any of the following conditions exist.
• Ambient temperatures exceeding a range of 5°C to 40°C for liquid crystal
display PTs or 0°C to 50°C for EL display PTs.
• Abrupt temperature changes and condensation.
20
Installation Environment
Section 2-2
• Relative humidity exceeding a range of 35% to 85%.
• Corrosive or inflammable gasses.
• Strong magnetism.
• Excessive dust, salt, or iron dust.
• Direct vibration or shock.
• Direct sunlight.
• Spray from water, oil, or chemicals (the front panel is basically drip-proof).
2-2-2
Mounting Position
Mounting Location
PTs with LCD display have a field of vision of 20° up, 30° down, and 30° right
and left. Install the Terminal at a height and direction that make it easy for the
operator to see.
Ambient Temperature
The ambient operating temperature range is 5°C to 40°C for liquid crystal
display PTs and 0°C to 50°C for EL display PTs. Take the following factors
into consideration.
• Leave sufficient ventilation space.
• Do not install directly above machinery that puts out a lot of heat (e.g.,
heaters, transformers, high-capacity resistors).
• If the ambient temperature of a PT with LCD display rises above 40%C or
that of a PT with EL display rises above 50%C, set up a fan or air conditioner.
Control panel
Fan
PT
Louver
Operation and Maintenance For safety during operation and maintenance, place the Terminal as far as
possible from high-voltage machinery and power equipment.
Improving Noise Resistance Do not install in a panel with high-voltage devices and install at least 200 mm
from electric power lines. To avoid noise interference from external devices,
separate them with a transformer or noise filter when wiring.
Power line
200 mm min.
PT
200 mm min.
21
Dimensions
Section 2-3
• When installing the Terminal near devices with strong electrical or magnetic
fields (such as solenoids), allow a distance of at least 40 mm, more if necessary.
Solenoid
40 mm min.
Solenoid
NT600M
40 mm min.
2-3
Dimensions
All dimensions are in millimeters.
2-3-1
Terminals with Function Keys (DF-type)
The dimensions illustrated below are for PTs with function keys (i.e., DF-type
PTs). PTs without a touch panel (i.e., a DN-type PT) will have the same outer
appearance and dimensions as a DF-type PT.
313
186
238
226
12
325
22
105
Installing the NT600M PT in a Panel
2-3-2
Section 2-4
PTs With (DT-type) and Without (DN-type) Touch Panels
313
186
198
12
325
2-4
105
Installing the NT600M PT in a Panel
The NT600M is designed to be inserted in a panel. Install as follows:
1, 2, 3... 1.
Cut a hole in the panel in accordance with the recommended dimensions shown below. The panel should be between 1.6 and 4.8 mm thick.
All dimensions are in millimeters.
NT600M-DF122 or NT600M-DNjjj + 12-key Function Key Unit
Installation
space
+0.5
227 mm --0
314 mm+0.5
NT600M-DTjjj/DNjjj
Installation
space
+0.5
186.5 mm --0
314 mm+0.5
23
Installing the NT600M PT in a Panel
Section 2-4
2.
Insert the PT into the hole from the front of the panel.
3.
Use the accessory metal fittings and tool to fasten the PT to the panel
surface. Do not use a screwdriver. A screwdriver may damage the fittings or the PT.
After setting the PT in the panel, secure it as shown below.
(1)
Fitting
(2)
Plastic
NT600M
(a)
(1) First pass the plastic part of the fitting through slot (a).
(2) Next, put the hook of the fitting into
slot (b) and pull so that the leg
catches in the PT case.
(b)
Accessory tool
NT600M
4.
(3) Turn the screw with the tool that
comes with the PT, and secure
the PT to the panel. There are six
places to be secured. When you
are finished, rotate the tool in the
inverse direction and remove it
from the screw.
To remove the PT from the panel, use a flat-blade screwdriver.
6 panel installation fittings
NT600M
24
-- Standard screwdriver
Wiring and Connectors
2-5
2-5-1
Section 2-5
Wiring and Connectors
Terminal Block
The terminal block shown in the following illustration is located on the PT’s
rear panel.
HOST
RUN
INPUT
ALARM
OUTPUT
Terminal screws: M4
100 to 240 VAC
50/60 Hz
LG
GR
Use crimp-style terminals for wiring. If twisted wires are connected directly,
there is a possibility of poor contact or short-circuiting. Use crimp-style terminals with holes to match M3.5 screws.
Fork-type
Round-type
8 mm max.
7 mm max.
Recommended Crimp-style Terminals
Maker
2-5-2
Fork-type
Round-type
Japan Solderless Terminal MFG
Fuji Terminals
2-YS3A
2-YAS3.5
2-3.5
V2-S3.5
Nichifu Terminals
2Y-3.5
2-3.5
Conforming wire (twisted)
1.04 to 2.63 mm2
AC INPUT Terminals
These terminals are the power supply input terminals to run the NT600M.
MCCB
100 to 240 VAC
50/60 Hz
Power Supply Wiring
Insulated
transformer
• Provide a 100 to 240 VAC power.
• Use a power supply within the allowable voltage range.
Power supply voltage
100 to 240 VAC
Allowable voltage range
85 to 264 VAC
25
Wiring and Connectors
Section 2-5
• Insulated Transformer
The NT600M has built-in anti-noise features which are sufficient for handling general noise from power lines, but ground noise can be greatly reduced by supplying power through a 1:1 insulated transformer. The secondary side of the insulated transformer should be an isolated neutral system.
• Power Capacity
Use a rated power supply (100 to 240 VAC; 50/60 Hz) of at least 50 VA.
• If power lines are long, then use wires of at least 2 mm2 to avoid a drop in
voltage.
• Use twisted-pair cables.
2-5-3
LG and GR Terminals
HOST
RUN
INPUT
ALARM
OUTPUT
100 to 240 VAC
50/60 Hz
LG
GR
Terminal screws are M4.
• GR is the ground terminal. In order to avoid electric shock, use separate
ground wire (at least 2 mm2) and a class-3 ground (ground resistance
100 W or less).
• LG is the noise filter neutral terminal. If malfunction results from excessive
noise, or to prevent electrical shock, short-circuit LG and GR and use a
class-3 dedicated ground.
• The ground line should be 20 m or less.
• Sharing a ground line with other machinery or grounding to the girders of a
building may be harmful.
2-5-4
HOST RUN INPUT Terminals
Use the HOST RUN INPUT when you want to monitor the RUN status of the
host.
Enable:
Disable:
Turn OFF SW1, pin 2.
Turn ON SW1, pin 2.
Host
Host RUN status
with transistor ON.
HOST
RUN
INPUT
620 W
5.6 kW
1,000 PF
(This terminal has no polarity.)
26
Internal circuit
24 VDC
RS-232C Interface Connector
Section 2-6
Item
Content
+10%/
Rated input voltage
24 VDC
Input impedance
5.6 kW
Input current
4.1 mA typical (at 24 VDC)
ON voltage
14.4 V min.
OFF voltage
5.0 V max.
--15%
If host RUN input goes OFF when this terminal is enabled, a host error is displayed regardless of other conditions and processing is halted. This status is
maintained until the host RUN is restored. When errors are displayed on the
PT screen, it allows for rapid recognition of problems at the host.
2-5-5
ALM OUTPUT Terminals
DC Load
100 to 240 VAC input
External device
Internal circuit
Load
ALM output
Item
2-6
Content
Output type
Relay output
Rated load
0.5 A at 100 VAC or 1 A at 24 VDC
Maximum load current
1A
Minimum switching capacity
10 mA at 5 VDC
RS-232C Interface Connector
The RS-232C interface connector is used during communications between
the NT600M and Support Tool. It is located under the RS-232C interface connector cover on the back of the NT600M.
Pin Allocation
Pin no.
Symbol
Name
1
FG
Frame Ground (not used)
2
SD
Send Data
3
RD
Receive Data
4
RS
Request to Send
5
CS
Clear to Send
9
SG
Signal Ground
27
Mounting Function Key Units (to DN-type PTs)
Section 2-8
Connection Diagram
Personal computer
(25 pins)
SD
RD
RS
CS
SG
FG
RS-232C
NT600M
2
2
3
3
4
4
5
5
7
9
SD
RD
RS
CS
SG
FG
1
1
Shielded wire
D-SUB connector,
9 pins
Note RS-232C communications conditions are set automatically by the Support
Tool. Connectors can be put on and taken off even with power on.
Applicable Connectors
(Cable Side)
Plug: XM2A-0901 (OMRON) or equivalent.
Hood: XM2S-0911 (OMRON) or equivalent.
Recommended Cable
AWG28 x 5P IFVV-SB (Fujikura, Ltd.)
CO-MA-VV-SB 5P x 28 AWG (Hitachi Cable, Ltd.)
Cable Set
CV500-CN228 (OMRON)
Cable length: 2 m
2-7
12-key Function Key Units (for DN-type PTs)
12-key Function Key Unit
(NT600M-FK210)
12-key Function Key Units can be connected to NT600M-DN122-E and
NT600M-DN211-E Programmable Terminals.
Connector (for connecting to PT)
PT mounting screws and rubber packing are included
with 12-key Function Key Units.
2-8
Mounting Function Key Units (to DN-type PTs)
Mounting Procedure
1, 2, 3...
1. Remove the rubber packing and bottom connector seal from the DN-type
PT.
2. Mount the 12-key Function Key Unit to the PT, matching the connectors. Using a Phillips screwdriver, tighten the five mounting screws.
NT600M-DNjjj
Programmable Terminal
Phillips screwdriver
NT600M-FK210 12-key
Function Key Unit
Mounting screws (4 places)
28
Mounting Function Key Units (to DN-type PTs)
Section 2-8
3. Attach the rubber packing that comes with the 12-key Function Key Unit.
Rubber packing
4. Mount to the panel.
29
SECTION 3
Initial Operation
This section provides an introduction to the operations necessary to use a PT for the first time and to the menus and keys
used to control PT operation.
3-1
3-2
3-3
3-4
Powering Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Initializing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-2 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transferring Data to and from the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Trial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
32
32
34
35
37
31
Initialization
3-1
Section 3-2
Powering Up
When first starting up the system, do not connect the Host Interface Unit to
the host. When power is turned on to the PT, either a “Connecting to host”
message or the initial screen set by the Support Tool will be displayed. The
“Connecting to host” message will be displayed if a Host Link Interface Unit,
a SYSMAC BUS Interface Unit, or a C200H Host Interface Unit is mounted.
The initial screen will be displayed if an RS-232C or RS-422A Interface Unit
is mounted.
If there is no screen data registered for the PT, or if there is an error in the
screen data that is registered, then the System Menu will be displayed
instead, with an error message at the bottom. In that case, it will be necessary to initialize the memory and transmit the correct data.
3-2
Initialization
Initialize the memory in the PT using the procedure described below. This
procedure can also be used later to completely delete data from the PT. Data
will be initialized regardless of the setting for the resume function. Always be
careful not to initialize and delete essential data.
3-2-1
Initializing Memory
Perform the initialization if the screen memory is either SRAM or EEPROM.
Check to be sure that the screen memory is installed.
Memory initialization can be used to initialize screen memory, memory tables,
and history data. Initializing screen memory completely deletes the contents
of the screen memory, including the contents of numeral tables and text
string memory tables. Initializing memory tables overwrites numeral tables
and text string memory tables with the initial values set by the Support Tool.
Initializing the display history deletes all of the display history data.
32
Initialization
Section 3-2
To initialize the screen memory, for example, first access the System Menu
by simultaneously pressing the Buzzer Key, Up Key, and Down Key. Then
proceed as shown as shown in the following chart.
System Menu
Select “MAINTENANCE MODE.”
Refer to Section 6.
Select “Init. Memory.”
Select “Init. Screen.”
Initialize Screen Memory?
Yes
No
If you select yes, then memory will be initialized and all data used for displays
will be erased. After initialization, operation will begin in RUN Mode.
If you select no, then operation will begin in RUN Mode without initialization.
When entering RUN Mode after initialization, nothing will be displayed on the
screen and the Terminal will wait for a command from the host.
To initialize other data memory, return to the Maintenance Mode and follow
the same procedure.
! Caution
Screen memory must be initialized before using a new PT. If the PT is used as
shipped from the factory without initialization, messages indicating errors in the
host will not be displayed properly.
33
Initialization
3-2-2
Section 3-2
Menus
The System Menu is called up by using the the system keys during operation. The System Menu can always be displayed regardless of the PT mode.
If there is no key input for 10 seconds after the System Menu has been
called up, the System Menu will be exited and RUN Mode will return.
V1.x
SYSTEM MENU
Version no.
Quit
Transmit Mode
Maintenance Mode
Expansion Mode
Using System Keys
Operation
Content
Press the Buzzer Key, Up Key,
and Down Key simultaneously.
Pressing the Up Key and Down Key while the Buzzer Key is being held down changes
PT modes and menus in the following ways:
RUN Mode → System Menu
System Menu → RUN Mode
Maintenance Mode → previous screen or RUN Mode
Transmit Mode → RUN Mode
Press the Up Key.
Moves the bar cursor upward.
Press the Down Key.
Moves the bar cursor downward.
Press the Enter Key.
Selects the menu at the position of the bar cursor.
Quit
Leave the system menu and return to operation by either of the following
methods.
1, 2, 3... 1.
Select “Quit.”
OR
2.
Selecting Items
Press the Buzzer Key, Up Key, and Down Key simultaneously.
In addition, if there are no key inputs within 10 s of calling up the system
menu, the system will automatically return to normal operation.
To select an item, move the bar cursor to that item and press the Enter Key.
Selected item
Function
Quit
Quits and return to normal operation.
Transmit Mode
Shifts to Transmit Mode.
Select when transferring data between the NT600M and Support Tool. For details, refer to 3-3
Transferring Data to and from the Support Tool.
Maintenance Mode
Shifts to Maintenance Mode.
Used to check the setting status of the NT600M and conduct self-testing.
Not used. Reserved for future function expansion.
Expansion Mode
34
Transferring Data to and from the Support Tool
Error Messages
Section 3-3
When there is an error in screen data registered in the NT600M, the System
Menu will appear before entering RUN Mode, and the error message will be
displayed on the bottom line.
V1.x
System Menu
Version no.
Quit
Transmit Mode
Maintenance Mode
Expansion Mode
Screen Data Corrupted
Example of error message
There are three types of error messages, as shown below. If an error message is displayed, first initialize the screen data memory before re-transmitting the data. Operation will not begin again until the error has been corrected.
Error message
Screen Data Corrupted
Mark Data Corrupted
Memory Not Formatted
3-3
Error Content and Correction
This is displayed when registered screen data is corrupted. Initialize the screen data and
then re-register it. Operation will not begin again until the data is restored.
This is displayed when registered mark data is corrupted. Initialize the screen data and
transfer the screen data files. The mark data is included in the screen data files. Re-register
the mark data. Operation will not begin again until the data is restored.
This is displayed when the screen data area is not formatted. Initialize the screen data
memory. All registered screen data, mark data, and system data will be deleted by the
initialization, so they will have to be transferred again from the Support Tool. In addition, if
an IC socket-type Screen Data Memory Board is being used, recheck the socket’s memory
and its settings.
Transferring Data to and from the Support Tool
Data can be transferred back and forth between the NT600M and the Support Tool. Transfer the screen data created by the Support Tool before operating the NT600M.
Procedure
Use the following procedure to transfer data.
1, 2, 3... 1.
2.
Connect the NT600M and personal computer running the Support Tool.
Select Transmit Mode from the System Menu.
System Menu
Refer to 3-1 Powering Up.
Select “Transmit Mode.”
3.
At the NT600M, it is only necessary to place the NT600M in Transmit
Mode. The direction of transmission and the contents of the data to be
transmitted are set at the Support Tool. (For instructions on operating
the Support Tool, refer to the NT-series Support Tool Operation Manual.
35
Transferring Data to and from the Support Tool
4.
Section 3-3
When the data transfer begins, the direction of transmission, the type of
data being transmitted, and the memory capacity are displayed on the
screen.
Transmit Mode
KB
PT ----> Tool
Tool ----> PT
Shows direction
of data transfer.
Screen Data
System Memory
Memory Tables
Mark Data
History Data
Shows type of data.
Number of bytes transferred (in kilobytes).
Abort:
Press these three System Keys simultaneously to stop the transfer in progress.
5.
When the data transfer has been completed, those items will no longer
be displayed.
Transmit Mode
Abort:
! Caution
36
6.
In the event of a disconnected cable or other disruption while the transfer is in progress, the NT600M screen will go blank and a message telling you that transfer was not possible will be displayed at the Support
Tool. If the transfer is completed successfully, then at the end of the
transfer the NT600M screen will go blank and a message telling you that
the transfer has been completed will be displayed at the Support Tool.
7.
To return from Transmit Mode to RUN Mode, press the Buzzer Key, Up
Key, and Down Key simultaneously.
After the transfer has been completed, be sure to return to RUN Mode by pressing the Buzzer Key, Up Key, and Down Key simultaneously. If the power is turned
off or if a reset is executed without having first returned to RUN Mode, the data
that has been transmitted will be corrupted. If that occurs, a message will be displayed on the screen to indicate that the data has been corrupted.
Trial Operation
Section 3-4
The following data can be transferred between the NT600M and the Support
Tool.
Support Tool to NT600M
NT600M to Support Tool
Screen data
Data
All screens or one screen
All screens or one screen
Character string table
YES
YES
Numeral table
YES
YES
Mark data
YES
YES
Display history data (in
order of frequency or in
order of occurrence)
None
YES
System Memory (Initial
screen after power-up)
YES
YES
Note When using the EEPROM as a screen data memory, screens cannot be
transferred screen by screen from the Support Tool to the PT. The screen
data must be transferred in file units after initializing the memory.
3-4
Trial Operation
After screen data has been transferred, or after a screen data memory chip
has been installed (when EPROM is used), the following procedure can be
used to carry out a trial operation.
1, 2, 3... 1.
2.
3.
4.
5.
Connect the Host Interface Unit to the host. (Refer to the Host Interface
Operation Manual.)
If the screen data memory is okay, then the PT will automatically go into
RUN Mode when it is powered up, and the RUN indicator on the front
panel will light.
Check the host-to-PT communications by transmitting a screen-change
command from the host, and checking whether the screen is changed.
Check the PT-to-host communications by transmitting to the host by
means of function keys, touch switches, and external inputs, and seeing
that they are all transmitting properly.
If communications with the host cannot be executed properly, refer to
6-2-6 I/O Checks.
37
SECTION 4
Display Functions
This section describes the functions used to create screens and control display attributes on the PT. Functions used to input data on-screen are described in Section 5 Input Functions. Data transfer and maintenance functions are described in
Section 6 System Menu. Transferring screens online to and from the host computer is described in Section 7 Online
Transfer.
4-1
4-2
4-3
4-4
4-5
4-6
4-7
4-8
4-9
4-10
4-11
4-12
4-13
Character Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Types of Characters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Designating Display Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-3 Character Scale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-4 Display Attributes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Graphics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Screen Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Procedure for Changing Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Continuous Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overlapping Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Numeric Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Character Strings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bar Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Graphics Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11-1 Backlight ON/OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11-2 Alarm Output On/Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11-3 Buzzer On/Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11-4 Initialize Display History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11-5 HOST RUN INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-11-6 Normal/Inverse Display (LCD-type Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40
40
40
40
41
41
42
42
42
43
45
46
47
47
48
48
48
49
49
49
49
50
50
50
39
Character Displays
4-1
Section 4-1
Character Displays
The type, size, and attributes of characters that can be displayed on the
NT600M screen are shown on the next page. Character type, size, and attributes are set at the time of creation on the Support Tool. When an
RS-232C or RS-422A Host Interface Unit is used, coordinates, characters,
etc, can be designated with commands from the host in Terminal Mode.
4-1-1
Types of Characters
Character fonts
Half-size characters (8 x 8 dots)
Alphanumeric characters, symbols.
Normal characters (8 X 16 dots)
Marks (16 X 16 dots)
Character scale
Alphanumeric characters, symbols.
Pictographs defined by the user (up to 64 possible)
Character codes: FF20 to FF5F
Number of digits displayed
1 to 8
Number of decimal digits
0 to 7
Zero suppress (see note)
Select “yes” or “no.”
+/-- sign
Select “yes” or “no.”
No sizing (equal), double-width, double-height, 4x, 9x, 16x, or 64x character sizes
Display attributes
Standard display, inverse, blinking, and, inverse blinking
Numeric display
p y
Note When zero suppress is in effect, zeros on the left of the number are not displayed. For example, “00028050” would be displayed as “28050”.
4-1-2
Designating Display Positions
The display positions can be designated in increments of display dots. When
characters overlap, characters written last overwrite those written earlier.
(Terminal Mode)
4-1-3
Character Scale
You can designate no sizing (equal), double-width, double-height, 4x, 9x,
16x, or 64x character sizes. When enlarging by 4x or more, you can make
the characters easier to read with the smoothing process (a process that removes the notches from characters when they are enlarged).
40
Display Graphics
4-1-4
Section 4-2
Display Attributes
Besides the standard display (black characters on a white background), you
can designate individual characters as inverse, blinking, or inverse/blinking.
Blinking
Inverse blinking
__
Note You cannot designate the blinking cycle.
64x characters
16x characters
64x characters
4x
characters
Normal
characters
4x
characters
16x
characters
16x
characters
9x characters
4x characters
16x characters
Wide characters
64x
characters
4x characters
9x
characters
Wide characters
16x
characters
Double-height characters
4-2
Display Graphics
Polylines (broken continuous lines) and circles can be created on the Support Tool for display on the PT. When using RS-232C or RS-422A communications, coordinates can also be designated through commands from the
host in terminal mode.
Display positions for graphics can be designated at dot increments and can
overlap characters on the display. When they overlap, graphics are displayed
on top of characters.
Either continuous lines (called polylines) or circles can be designated. Line
widths are 1 dot for either.
41
Continuous Screens
4-3
Section 4-4
Normal Screen Changes
The displayed screen can be changed to another screen by designating the
screen number from the host (a Programmable Controller or personal computer). The designated screen must have already been created at the Support Tool and downloaded to the NT600M or it must have been placed in
ROM, with the Screen Data Memory Board installed.
4-3-1
Procedure for Changing Screens
1, 2, 3... 1.
By designating a screen number (0 to 1,000) from the host, you can
switch to the designated screen.
Note Screen no. 0 is blank (with no display).
2.
3.
Standalone Function
When an ordinary screen is displayed, the screens cannot be changed
by means of the Up and Down Keys on the front panel of the NT600M.
The screen-changing procedures vary for each interface. For details,
refer to the Host Interface Unit Operation Manual.
When Support Tool versions NT-ZA3AT-EV2 or NT20M-ZASAT-EV4 and later
are used, screen changes can be made on-site. In order to be able to make
on-site screen changes, when creating screen data use the expansion function to assign screen numbers to touch switches, function keys, or external
inputs.
Screen 1
Screen 2
Screen 2
Screen 1
For example, here a touch switch is assigned
the screen-change function.
4-4
Continuous Screens
Screens can be linked to display consecutively, without breaks. A maximum
of eight screens can be made consecutive, and treated as one screen.
• By pressing the Up Key and Down Key, you can scroll screens up or down.
• Page number displays are designated on the Support Tool at the time of
registration.
42
Overlapping Screens
Section 4-5
If screen 9 is designated from the host, the content of screen 20 is displayed
first. If you press the Down Key, you scroll down to the next screens.
Example
Parent screen for consecutive screens
Screen no. 9
Screen no. 9: Screens displayed
20→21→23
20
A
21
B
23
D
Register the screen numbers of the child screens
that you want to make consecutive. (You can set
screen numbers in any order you want.)
Screen contents
Screen
20
A
21
B
22
C
23
D
Note 1. Parent screens (screen no. 09 in this case) cannot have screen data.
They can be treated only as parent screens.
2. Scrolling is done in screen units.
3. Screens with numeric settings cannot be designated as child screens.
4-5
Overlapping Screens
The contents of multiple screens can be laid one on top of another and registered as one screen, when the screens are created on the Support Tool. Just
as with ordinary screens, if the number of a screen registered as an overlapping screen is designated from the host, then the overlapping screens corresponding to that number are displayed.
• A maximum of eight screens may be overlapped.
• Screens with touch switches, lamps, graphs, character strings, and numeric
displays can be overlapped. If screens with numeric settings are to be overlapped with screens that have touch switches or lamps, then use touch
switch/lamp numbers 0 to 243 (or 0 to 230 when the ten-key is registered to
“user”). In addition, do not overlap touch switches/lamps with numeric keys.
• An overlapping screen cannot be set as a child screen of a continuous
screen.
43
Overlapping Screens
Section 4-5
If screen 02 is designated from the host, then screens 03, 05, and 08 are displayed.
Example
Parent screen: Screen no. 02
Screen no. 02 is designated by the host.
Overlapping screens
Screen no. 02: Screen displayed
Numbers of child screens:
My name is Smith.
03
05
08
Contents of child screens registered to overlapping screen no. 02:
Screen no. 03
My name
Note
The contents of the screens
are not displayed during setting operations.
Screen no. 05
is
Screen no. 08
Smith.
Note Parent screens (screen no. 02 in this case) cannot have screen data. They
can be treated only as parent screens.
44
Numeric Displays
4-6
Section 4-6
Numeric Displays
A numeral table is stored in the NT600M, and you can display numeric values from the table at designated positions on a screen. In addition, the values in the table can be transferred from the host so that they are renewed
each time a new value is transferred. The display positions are set in advance with the Support Tool.
Example
Screen Registered
Screen Displayed
Production
Production
Line 1
Line 1
1020
Line 2
556
Paint
832
999
# 6
Assem
711
807
# 7
Final
630
777
Line 2
Weld
# 0
# 4
Weld
Paint
# 1
# 5
Assem
# 2
Final
# 3
Contents registered to screens by Support Tool:
Numeral table numbers
Display positions (50/screen max.)
Number of digits displayed (whole numbers, fractions)
Character fonts
Sizes of characters displayed
Numeral Table
(Maximum of 256 entries)
Number
Contents
#0
1020
#1
832
#2
711
#3
630
#4
556
#5
999
#6
807
#7
777
to
#255
These contents are transmitted from the host.
When the PC is used as the host, for example, these values will be transferred via the Host
Interface Unit and updated on screen when the contents of the DM Area are changed at the
PC.
45
Character Strings
4-7
Section 4-7
Character Strings
This function displays variable character strings on the screen. A character
string memory table is stored in the NT600M. By changing, from the host, the
memory table values corresponding to the display position, you can update
the characters displayed. The designation of the display positions is set in
advance at the Support Tool.
Example
Screen Registered
Screen Displayed
Production
Production
Line 1
Line 1
Line 2
Line 2
Weld
# 0
# 4
Weld
Van
Sports car
Paint
# 1
# 5
Paint
Car A
Convertible
Assem
# 2
# 6
Assem
Car B
Final
# 3
# 7
Final
High-roof
Contents registered to screens by Support Tool:
Character string memory table numbers
Display positions
Number of characters displayed
Font displayed
Sizes of characters displayed
Character String Table
(Maximum of 256 entries)
Number
Contents
#0
Van
#1
Car A
#2
Car B
#3
High-roof
#4
Sports car
#5
Convertible
#6
#7
to
#255
These contents are transmitted from the host.
When the PC is used as the host, for example, these values will be transferred via the Host
Interface Unit and updated on screen when the contents of the DM Area are changed at the
PC.
46
Lamps
Section 4-9
4-8
Bar Graphs
If the numeric values that you want to make into a bar graph have been input
into the numeral table in advance, then that graph can be displayed simply
by designating the screen on which the graph is registered. Just as with numeric displays, the graph display is also updated when the contents of the
numeral table are updated. Bar graphs can be displayed either horizontally or
vertically. They can also be displayed in the negative direction.
Example
Graph Display
Production Targets
Line 1
#0
Line 2
#1
Line 3
Production Targets
#2
Contents registered to screens by Support Tool:
Display positions (50 bars max.)
Graph width (2 to 255 dots)
100% value
% display (yes/no)
% display position
Numeral table numbers for referencing
Display direction
Graph frame (yes/no) (see note)
Sign display
% display fonts
% enlargement sizes
+/-- sign (yes/no)
Order
Line 1
10%
With sign
Line 2
--55%
Reverse
Line 3
66%
Production Targets
Line 1
Line 2
Line 3
33%
66%
Numeral Table
(Maximum of 256 entries)
Number
Contents
#0
1020
#1
832
#2
711
Order
With sign
Reverse
Note: When “with frame” is set for a graph, the width
of the graph is reduced by two dots, so in that case
the graph must have an original width of at least
three dots.
to
#255
4-9
10%
Lamps
On the Support Tool you can set lamp areas in the display screen, and the
lamps will light (or blink) by means of a designation from the host. Lamps are
registered in advance at the Support Tool.
Display position:
Can be set as desired, but must match the switch
frames when combining lamps with the switch function.
Shape:
Rectangle or circle
47
Special Controls
Section 4-11
Size:
Can be freely set with a rectangle or a circle.
Number:
128 maximum per screen
Display attributes:
Lit, blinking
Guide characters:
Select “yes” or “no.”
Lamps set from the host can be turned on and off by either of two methods:
number designation or bit designation (when there is no direct connection).
For details, refer to the Host Interface Unit Operation Manual.
Example 1: Usage with
Switch Frames
If using a lamp together with a switch, then set the lamp within the switch
frames, of which there are 12 horizontal and 6 vertical.
Example 2: Emphasis
The display of the number defective can be emphasized setting it to light.
Goal
Complete
Defective
4-10
1234
600
2
Graphics Display
Unbroken straight lines (polylines) and circles can be created by the Support
Tool and displayed at the PT. When an RS-232C or RS-422A Interface Unit is
used, the graphics can be displayed by using the terminal function and transmitting commands from the host.
Designating Display
Positions
4-11
Graphics display positions can be designated in dot units. In cases where
graphics and characters overlap, the graphics will be overwritten (Terminal
Mode). Polylines and circles are both drawn with a width of one dot.
Special Controls
The status of the NT600M to be controlled from the host during operation.
4-11-1
Backlight ON/OFF
In order to prolong the life of the backlight, the backlight can be turned off by
a backlight-off command from the host when it is not needed during operation.
48
Special Controls
Section 4-11
Note If there is any key input or transmission while the backlight is off, the backlight will turn on again.
4-11-2
Alarm Output On/Off
The output of the ALM OUTPUT terminal, which is located in the terminal
block on the rear panel of the NT600M, can be turned ON and OFF from the
host. The ALM OUTPUT terminal is turned ON and OFF when a screen registered for an alarm is displayed, and also when there is an NT600M error.
ALARM
OUTPUT
4-11-3
Buzzer On/Off
The built-in buzzer can be turned on and off from the host. There are two
types of buzzers, continuous and intermittent. The buzzer also sounds when
a screen registered with the buzzer is displayed. The buzzer stops when the
Buzzer Key is pressed.
Continuous
buzzer
(Continuous sound)
Intermittent
buzzer
(Intermittent sound)
4-11-4
Initialize Display History
History data in the NT600M can be cleared (initialized) by the host. Until this
operation is executed, history data continues to be registered.
4-11-5
HOST RUN INPUT
The HOST RUN INPUT detects when the host in not in RUN, and displays
the host error screen. Pin 2 of SW1 is used to enable and disable this input.
When the HOST RUN INPUT is enabled, the host error screen is displayed if
it turns OFF.
Pin 2 of SW1 ON:
Pin 2 of SW1 OFF:
HOST RUN INPUT disabled.
HOST RUN INPUT enabled.
HOST
RUN
INPUT
49
Display Speed
4-11-6
Section 4-13
Normal/Inverse Display (LCD-type Only)
The display background can be set to either normal or inverse. The normal
background is white, and the inverse background is black.
4-12
Normal display
Inverse display
Normal display
Inverse display
Terminal Function
This function allows you the option of displaying, by transmission on command, the codes (coordinates, type, etc.) of characters and figures you want
to display from the host, in addition to screens registered in advance. This
function is possible only when the Host Interface Unit is the NT600M-LK201
for the RS-232C or the NT600M-LK202 for the RS-422A. For details, refer to
the terminal commands listed in the RS-232C/RS-422A Interface Unit Operation Manual.
Item
Content
Display position
Optional
Character size
Normal, half-size, double-height, double-width, 4x, 9x, 16x,
or 64x
Normal, inverse, blinking, inverse blinking
Display attributes
Character designation ASCII
Graphics
Polyline, circle
Note 1. If a displayed character string exceeds the line, that string is displayed
beginning from the left side of the next line.
2. In addition, strings that do not fit at the bottom of the screen over-write
from the left side of the same screen.
4-13
Display Speed
NT600M display speed varies according to the amount of elements displayed
on the screen. As a standard, the following diagrams shows the time required
for changing displays on screens that include characters.
Measurement Conditions
50
System ROM:
Host Interface Unit:
Screen data:
Measurement time:
NT600M-SMR02-EV1
NT600M-LB122-V1
Character display (1 to 40 characters)
Time (in ms) from when the PT receives the
command until the display is executed.
Display Speed
Section 4-13
Time it Takes to Display the Same Normal Characters
Time (ms)
64x characters
16x characters
9x characters
4x characters
Double-height characters
Double-width characters/Mark
Equal characters
Number of characters displayed
51
Display Speed
Section 4-13
Time it Takes to Display a Variety of Normal Characters
64x characters
16x characters
Time (ms)
9x characters
4x characters
Double-height
characters
Double-width
characters/Mark
Equal
characters
Number of characters displayed
52
SECTION 5
Input Functions
This section describes the functions used to input data on-screen. Functions used to create screens and control display
attributes on the PT are described in Section 4 Display Functions. Data transfer and maintenance functions are described
in Section 6 System Menu. Transferring screens online to and from the host computer is described in Section 7 Online
Transfer.
5-1
5-2
5-3
On-screen Switch Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-1 Transmitting to the Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-2 Creating Touch Switches (DT-type PTs Only) . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-3 Function Keys (NT600M-DF122) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inputting Numeric Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standalone Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54
54
55
56
56
59
53
On-screen Switch Inputs
5-1
Section 5-1
On-screen Switch Inputs
DT-type PTs can transmit to the host the input status of touch switches set on
screens. A maximum of 64 switches can be set per screen. DN-type PTs can
transmit to the host the inputs of 12-key Function Key Units. DF-type PTs can
transmit to the host the input status of the function keys located at the bottom
of the display. (The standard number of function keys is 12.)
5-1-1
Transmitting to the Host
There are two ways to transmit the input status of switches to the host.
These two methods, which are determined by a “screen attributes” setting at
the Support Tool, are described briefly below. For more detail, refer to the
Host Interface Unit Operation Manual. For instructions on setting screen attributes, refer to the NT-series Support Tool Operation Manual.
Switch-number Method
In order to use the switch-number method, “bit input” screen attribute must
be set to “disabled.” Using this method, when a switch is pressed the number
corresponding to that switch is transmitted to the host as a numeric value in
three digits of BCD. When two switches are pressed, the first one is given
priority in transmission. When using an NT600M-LK201 or NT600M-RT121
Host Interface Unit, send the data to the host by means of the strobe signal
in the PT status information which is output when switches are pressed.
Bit-switch Method
In order to use the switch-number method, “bit input” screen attribute must
be set to “enabled.” When this method is used, the status of each switch is
transmitted to the host as a bit status. This is the method used when substituting for ordinary operating switches. You can use it for ordinary bit input
switches from a Programmable Controller.
Note With this method, it is possible to push a number of switches simultaneously.
The following considerations must be taken into account, however, when
configuring the switches.
Example 1:
Switches Created at Points C and D, Which are Vertical and Horizontal Points of
Intersection for Points A and B
A
C
B
D
Minimum touch switch frame
54
If switches A, B, and C are turned ON
simultaneously in this switch configuration, switch D
will also turn ON.
If switches A, B, and D are turned ON simultaneously, switch C will also turn ON.
On-screen Switch Inputs
Section 5-1
Example 2: Switches Created at Points E, F, and G
E
F
G
If switches E and F are turned ON
simultaneously in this switch configuration, switch G
will also turn ON.
Minimum touch switch frame
5-1-2
Creating Touch Switches (DT-type PTs Only)
Just as with lamps, touch switches are created and registered with the Support Tool. The setting content is as follows:
Setting Parameters
Combine your choices of rectangular sections from the among the 128
blocks shown in the diagram below, and designate them as switches. The
smallest possible switch is one block.
Number of Settings
A maximum total of 128 switches can be set per screen. If you wish, the entire screen can also be set as one input switch.
Settings by Support Tool
Frame display
Standard/Solid/None
Reverse video display at input
Yes/No
Guide characters
Yes/No
8
16
Example of On-screen Touch Switches
Power error
Oil pres error
Auto
Forwd
Up
Man
Back
Down
Stop
55
Inputting Numeric Settings
5-1-3
Section 5-2
Function Keys (NT600M-DF122)
The NT600M-DF122 is the PT with function keys. DN-type PTs (NT600MDN-221) can also be provided with function keys by connecting a 12-key
Function Key Unit (NT600M-FK210).
Function keys
Example of Function Key Input Screen
Time Setting
PV
56 s
SV
1
2
3
4
5
6
7
8
9
0 CLR +/-
The function keys all have the same size screen display frames. You can display customized function names on the screen to identify them. Up to two
function keys can be pressed simultaneously.
5-2
Inputting Numeric Settings
Numeric values input while the numeric setting screen is being displayed are
written to the designated numeral table and transmitted to the host.
Numeric Setting Screens
56
The standard numeric setting screen is as shown below. This screen is reserved for system use by the Support Tool. Standard screen key arrangements and functions are fixed. In order to change the key arrangement or
add keys (such as a decimal point) for numeric input, set the “numeric setting” item under “screen attributes” to “user.” (When it is set to “system,” the
Inputting Numeric Settings
Section 5-2
standard screen will be displayed.) For instructions on registering numeric
setting screens, refer to the NT-series Support Tool Operation Manual.
Standard Screen (Screen Attribute: System)
User-set Screen Example
(Screen Attribute: User)
Tank A
Tank B
0654
0650
Tank C
Tank D
0000
0550
Tank E
Tank F
0800
0990
HOME
MENU
1
2
3
↑
4
5
6
↓
7
8
9
←
0
. CLR →
CHANGE
SET
1 2 3 4 5 6 7 8 9 0 CLR +/Creating Numeric Setting
Screens
When creating a numeric setting screen with the Support Tool, take note of
the following points.
1) A numeric setting screen cannot be set as the child screen of a continuous
screen.
2) Ordinary touch switches can be set in numeric input screens, but touch
switch numbers 244 through 255 cannot be used.
3) When “10-key” is set to “user” in the screen attributes, touch switch numbers 231 through 255 cannot be used for purposes other than numeric input.
4) The numeric setting function cannot be used when the screen attribute “bit
input” is enabled for PTs with no touch panel.
Inputting Numeric Values
(PTs With Touch Panels)
1) Inputting Numeric Values with the Standard Screen:
• The numeral shifts from the rightmost digit to the left each time a screen
key is pressed.
• If a decimal point is set, the shift is from the rightmost digit in the decimal
area to the integer side.
2) Inputting Numeric Values with a User-set Screen:
• The numeral shifts from the rightmost digit to the left each time a screen
key is pressed.
• If a decimal point is set, the integer portion is received first, and with each
numeric key input there is a shift from the rightmost digit to the left.
• When the decimal point key is pressed, the decimal portion will then be received. From that point on, with each numeric key input there is a shift from
the rightmost digit in the decimal portion to the left.
Inputting Numeric Values
Use the 12-key Function Key Unit).
(PTs Without Touch Panels)
1) Inputting Numeric Values with the Standard Screen:
Use the corresponding function keys. Numeric input is the same as for PTs
with touch panels.
2) Inputting Numeric Values with a User-set Screen:
Use the corresponding function keys. Numeric input is the same as for PTs
with touch panels.
57
Inputting Numeric Settings
Section 5-2
Numeric Input Example
This example shows numeric input with a user-set screen. The display settings made with the Support Tool are as follows:
Number of digits displayed:
Number of integer digits:
Number of decimal digits:
Zero suppress:
Plus/minus mark display:
7
4
3
No
No
The following table shows the inputs and the resulting changes in the display.
Input operation
Set value
Initial display
1234.567
Input “CLR”
0000.000
Input “2”
0002.000
Input “7”
0027.000
Input “.”
0027.000
Input “2”
0027.002
Input “1”
0027.021
Input “9”
0027.219
Input “↵”
0027.219
Numeric values input with the input keys are stored in the numeral table justified to the right, as shown above. When the CLR Key is pressed for the first
time, the initial display is cleared. If zero suppress were enabled, the number
displayed would be “0.000” instead of “0000.000.” When the “2” is then input,
it is registered at the rightmost integer position, as described on the preceding table. The “2” is then shifted to the left as the “7” is input. After the decimal point is input, numerals are then registered at the rightmost decimal position. (To return to integer input status, press the CLR Key again.) Finally,
pressing the Enter Key causes the numeral table data to be transmitted to
the host.
Direction Keys and Home
Key
Pressing the direction keys (i.e., the arrow keys) moves the cursor to other
numeric setting columns. Pressing the Home Key moves the cursor to the
upper left of the screen.
Differences in Cursor
Movement
When multiple numeric setting areas are created for a numeric setting
screen, cursor movement will be different depending on whether system keys
or touch switches are used.
Screen Example
Numeric setting 3
Numeric setting 4
Numeric setting n: “n” represents the order
in which numeric setting areas are created
by the Support Tool.
Numeric setting 1
Numeric setting 2
Present cursor position
Numeric setting 5
1) When System Keys are Used:
When system keys are used, the cursor moves from area to area in the order
in which the areas were created by the Support Tool. Thus, in the screen example shown above, the cursor would start at numeric setting 2 and move in
order to numeric settings 3, 4, 5, and back to 1.
58
Standalone Function
Section 5-3
2) When Touch Switches are Used:
When touch switches are used, the cursor moves from area to area according to the layout of the screen. Thus, in the screen example shown above,
the Down Key would move the cursor from numeric setting 2 to numeric setting 5. After that, the Down Key cannot move the cursor any further.
Pressing the Up Key would then move the cursor back to numeric setting 2,
and then continue to move it upward in order to numeric settings 1 and 3.
The Right Key would then have to be used to move the cursor to numeric
setting 4.
5-3
Standalone Function
When a screen for which the standalone function has been set by the Support
Tool is displayed, the screen can be changed by means of touch switches and
function keys.
Example
Registered Screen
Production Target
Screen No. 5
Screen 5
Touch switch
no. 1 display
area
Model no. NT600M-DT122
Number
produced
2,500
Items Registered to Screen by Support Tool
• Standalone function setting
Production Conditions
Production target: 5,000
Number produced: 2,500
Number defective: 2
When touch switch no. 1 is input,
screen no. 5 is displayed.
• Touch switch or function key number
• Screen number to be displayed when touch
switches or function keys are input
Example
Standalone function is set.
Touch switch number: No. 1
Screen to be displayed: No. 5
59
SECTION 6
System Menu
This section describes data transfer and maintenance functions. Functions used to create screens and control display attributes on the PT are described in Section 4 Display Functions. Functions used to input data on-screen are described in
Section 5 Input Functions. Transferring screens online to and from the host computer is described in Section 7 Online
Transfer.
6-1
6-2
6-3
Configuration of System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Menu and Transmit Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-1 Quit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-2 Transmit Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-3 Maintenance Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-4 Expansion Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-5 Display History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-6 I/O Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-7 PT Settings Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2-8 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Memory Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
62
63
63
63
63
63
63
65
69
70
71
61
Configuration of System Menu
6-1
Section 6-1
Configuration of System Menu
The System Menu is used to set NT600M system parameters in advance
and perform maintenance. With the System Menu you can, in addition to determining the NT600M’s status, check switch settings and perform simple I/O
checks.
(1) If there is no key input within 10 seconds while the System
Menu is being displayed, the system will automatically return to
RUN Mode. To toggle between RUN Mode and the System
Menu, press the Up, Down, and Buzzer keys simultaneously.
SYSTEM MENU
(2) The RUN indicator will be OFF while the System Menu is being
displayed.
Quit
Expansion
Mode
Maintenance
Mode
Transmit Mode
(Maintenance Mode)
Display History
Quit
Occur.
I/O Check
Freq.
PT Settings
Quit
Quit
Init. Screen
Init. Table
Key Press Sound
Init. History
Backlight Off
*1
Quit
Function Key
Touch Switch
Comm. Check
*3
Tool I/F
LED
*4
*5
*1: For PTs with EL displays, this becomes the residual image elimination function.
*2: This does not apply to PTs with EL displays.
*3: This in turn has two submenus: “Function Key Check” and “Lamp Check.”
*4: For PTs with EL displays, this becomes “EL Display.”
*5: This applies only to PTs with EL displays.
62
Display
Resume
*2
LCD Display
Host I/F
Memory SW
Init. Memory
Buzzer
System Menu and Transmit Mode
6-2
6-2-1
Section 6-2
System Menu and Transmit Mode
Quit
To leave the System Menu and return to RUN Mode, select Quit. If no key is
pressed for 10 seconds, the PT will automatically return to RUN Mode.
SYSTEM MENU
Quit
Transmit Mode
Maintenance Mode
Expansion Mode
6-2-2
Transmit Mode
This mode is used to transfer data between the PT and the Support Tool.
6-2-3
Maintenance Mode
When making initial settings or when there is an operating error, select Maintenance Mode and conduct all the checks.
Maintenance Mode Menu
MAINTENANCE MENU
Quit
Display Hist.
I/O Check
PT Settings
Init. Memory
Memory SW
Move the bar cursor with the Up key and Down key, and select with the Enter
Key.
6-2-4
Expansion Mode
This mode is not presently being used. This mode is being reserved for
future expansion of functions.
6-2-5
Display History
The NT600M saves into memory and can display the history of screens displayed during operation, as long as the history attribute has been set for
them by the Support Tool. The history can be displayed either in order of occurrence or in order of frequency. This function can be used to help identify
the causes of malfunctions or to enable the operator to know which functions
are often being used.
63
System Menu and Transmit Mode
Setting History Data
Section 6-2
(1) When creating screens with the Support Tool, use screen attribute designations to register history attributes and messages (within 24 characters) for
the screens you want to save in the history.
(2) Whenever the screen number registered for history attributes is designated by the host, the occurrence and message are saved in memory. The
capacity of the history is 1,023 screens in chronological order or 255 occurrences per screen in frequency order. The only things that can be recorded
are screen numbers and messages. History record data is backed up by a
battery, so, as long as the battery is installed, the contents will be retained
even when the power is turned off.
(3) Before beginning to record, initialize the history data by transmitting an
Initialize History command from the host, or by selecting Init. Hist. from the
Maintenance Mode. If the history data capacity is exceeded, newly occurring history data will not be saved.
Reading History Data
Enter Maintenance Mode from the System Menu.
MAINTENANCE MENU
Quit
Display Hist.
I/O Check
PT Settings
Init. Memory
Memory SW
Move the bar cursor to History Record by pressing the Up and Down Keys.
Then press the Enter Key.
History Record
Occurrence
Frequency
Select whether the history is to be displayed in order of occurrence or in order of frequency. First move the bar cursor to your selection by means of the
Up and Down Keys, and then press the Enter Key.
Order of Occurrence
Record data is displayed in order of occurrence.
No.
Times
Message
1
( )
Coolant Mal.
5
( )
Motor Mal.
200
( )
Comp. Mal.
150
( )
Press Mal.
Number of times occurred.
Screen number
64
System Menu and Transmit Mode
Section 6-2
• Up to 48 items of registered data can be displayed on a screen.
• If not all of the record data shows on the screen, then use the Down Key to
scroll down.
• To return to the System Menu, press the Buzzer Key, Up Key, and Down
key simultaneously.
Order of Frequency
Record data is displayed in order of frequency.
No.
Of
Times
Message
200
( 2)
Comp. Mal.
1
( 1)
Coolant Mal.
5
( 1)
Motor Mal.
Number of times occurred.
Screen number
When different messages occur with the same frequency, they are displayed
in order beginning with the lowest screen number.
When there is no display data, the following message will be displayed (for
both order of occurrence and order of frequency).
History Record Not Found
Initializing History Data
To delete history data, first select Maintenance Mode from the System Menu.
The Maintenance Mode Menu will be displayed. Then select “Init. Memory,”
followed by “Init. History.” A message will then be displayed asking for confirmation that you want to initialize the history.
Select whether or not the history is to be initialized. If you select Yes, then
initialization will be executed. All recorded history will be deleted. If you select
No, then operation will commence without initialization.
6-2-6
I/O Checks
In the Maintenance Mode Menu, use the Up and Down Keys to move the bar
cursor to I/O Check. When you then press the Enter Key, one of the following
menu will be displayed, depending on the input switch specifications. With
the I/O Check Menu displayed, move the bar cursor to the item you want to
check, and then press the Enter Key.
65
System Menu and Transmit Mode
Section 6-2
(1) DT-type PT with LCD Display
I/O CHECK MENU
Quit
Function Key
Touch Switch
Comm. Check
LCD Display
Buzzer
(2) DT-type PT with EL Display
I/O CHECK MENU
Quit
Function Key
Touch Switch
Comm. Check
EL Display
Buzzer
(3) DF-type PT with LCD Display
I/O CHECK MENU
Quit
Exp. I/O Unit
Comm. Check
LCD Display
Buzzer
(4) DN-type PT with EL Display
I/O CHECK MENU
Quit
Exp. I/O Unit
Comm. Check
EL Display
Buzzer
66
LED
System Menu and Transmit Mode
Section 6-2
Function Key Check (DN-type PTs)
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
F17
F18
F19
F20
F21
F22
F23
F24
F25
F26
F27
F28
F29
F30
F31
F32
F33
F34
F35
F36
F37
F38
F39
F40
F41
F42
F43
F44
F45
F46
F47
F48
F49
F50
F51
F52
F53
F54
F55
F56
F57
F58
F59
F60
F61
F62
F63
F64
The operation of the function keys can be checked. Press a function key. If
the number of that key is displayed in reverse video on the screen, then it is
operating properly.
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
Touch Switch Check (DT-type PTs)
The operation of the touch switches can be checked. Press each switch displayed on the screen. If the switch that has been pressed (for approximately
0.5 s) is displayed in reverse video on the screen, then it is operating properly. Switch numbers are not transmitted to the host during the check operation.
If “Key Press Sound” (under the Memory SW Menu in Maintenance Mode) is
set to “ON,” then the buzzer will sound simultaneously with the inverse video
display.
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
12-key Function Key Unit
Check (DN-type PTs)
12-key Funcion Key Unit inputs and outputs can be checked if the Programmable Terminal is a DN type. Select “Exp. I/O Unit,” and then select either
“Function Key Input Check” or “Lamp Output Check.”
External Function Key Input When the external input terminals are turned on one-by-one, the corresponding function keys are displayed in reverse video and can be checked. When
Check
67
System Menu and Transmit Mode
Section 6-2
a 12-key Function Key Unit is connected, F1 through F12 correspond to IN0
through IN11.
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
F17
F18
F19
F20
F21
F22
F23
F24
F25
F26
F27
F28
F29
F30
F31
F32
F33
F34
F35
F36
F37
F38
F39
F40
F41
F42
F43
F44
F45
F46
F47
F48
F49
F50
F51
F52
F53
F54
F55
F56
F57
F58
F59
F60
F61
F62
F63
F64
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
Lamp Output Check
When “Lamp Output” is selected, “L1” is displayed in reverse video and output 1 turns ON. Use the Up Key and the Down Key to check all of the lamp
outputs. (The Up Key moves the reverse video location from left to right, and
the Down Key moves it from right to left.)
When a 10/02 Terminal or a 32/16 Terminal is connected, the corresponding
output turns on simultaneously with the lamp number that is displayed in reverse video.
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25
L26
L27
L28
L29
L30
L31
L32
L33
L34
L35
L36
L37
L38
L39
L40
L41
L42
L43
L44
L45
L46
L47
L48
L49
L50
L51
L52
L53
L54
L55
L56
L57
L58
L59
L60
L61
L62
L63
L64
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
! Caution
Communications Check
If a load (e.g., a buzzer or alarm light) is connected to a 10/02 Terminal or a 32/16
Terminal, it will actually operate. This can be potentially dangerous, so exercise
caution.
When “Communications Check” is selected, the Communications Check
Menu is displayed. Use the Up and Down Keys to move the bar cursor to the
item you want to check, and then press the Enter Key.
COMM. CHECK MENU
Tool I/F
Host I/F
68
System Menu and Transmit Mode
Section 6-2
To return to the I/O Check Menu, press the Buzzer Key, Up Key, and Down
Key simultaneously.
Tool Interface Check
Data transmitted from the Support Tool is displayed in hexadecimal. If any
numeral is displayed, then the interface is operating properly. If no numerals
are displayed, then there is a Support Tool operation error, communications
cable error, or communications hardware error.
Host Interface Units with RS-232C Specifications (NT600M-LK201)
RS-232C I/F Input Check
1B 51 30 33
LCD/EL Display Check
The display check can be carried out for both the LCD display and EL display.
The lines of the display are reversed one at a time, starting from the top of
the screen. When the reversal is finished, then they are cleared one at a
time. When all of them have been cleared, the I/O Check Menu is returned
to. You can interrupt the check and return to the I/O Check Menu by pressing
the Buzzer Key, Up Key, and Down Key simultaneously while the check is in
progress.
Buzzer Check
By selecting “Buzzer” from the I/O Check Menu, the PT buzzer can be
checked. The buzzer should produce a continuous sound. To stop the buzzer, press the Buzzer Key. While the buzzer is sounding, it will not be possible
to change screens or stop the buzzer by pressing the Buzzer Key, Up Key,
and Down Key simultaneously.
LED Check
When PTs with EL displays (i.e., NT600M-DT/DN211 PTs) are used, a lighting check can be carried out for the front panel RUN and BAT LOW indicators. When“LED” is selected, the RUN and BAT LOW indicators should begin
to blink if they are operating properly. If the battery voltage is low, the BAT
LOW indicator will remain steadily lit.
6-2-7
PT Settings Check
The status of the NT600M and Host Interface Unit can be checked, as well
as the settings of switches. First select “PT Settings” from the Maintenance
Menu. There are two screens. One displays the contents of PT settings, and
the other displays the contents of Host Interface Unit settings. Use the Up
Key and the Down Key to change back and forth between the screens.
PT Settings
When “PT Settings” is selected, the status of internal NT600M settings is displayed first.
1) DT-type PTs
69
System Menu and Transmit Mode
Section 6-2
PT Settings
Next Page
Memory Type
RAM
Memory Size
128 KB
Host RUN
Disable
Mode Changes
No
i
Memory type and memory size are displayed only after the screen memory
has been initialized. If it has not been initialized, then “N.A.” is displayed.
2) DN-type PTs
PT Settings
Next Page
Memory Type
RAM
Memory Size
128 KB
Host RUN
Disable
Mode Changes
No
Exp. I/O Unit
Standard
i
• When an Expansion I/O Unit is connected to a DN-type PT, the 12-key
Function Key Unit type is displayed.
Standard:
12-key Function Key Unit
Not Connected; No Expansion I/O Unit is connected.
• If a 12-key Function Key Unit becomes disconnected during operation, a
continuous buzzer will sound and a “No Expansion I/O Unit” error message
will be displayed.
Host Interface Unit Settings The DIP switch settings on the Host Interface Unit can be displayed by pressing the Down Key while PT settings are being displayed. The following display example is for the NT600M-LK201 Host Link Interface Unit. For examples of other Host Interface Units, see the Host Interface Unit Operation
Manual.
Host Link I/F Settings
Beginning word
Page
j
DM0000
Number tables
32
String tables
8
Baud Rate
9600 bps
To return to the PT Settings display, press the Up Key.
6-2-8
Initialization
You must initialize the internal memory when using the SRAM or EEPROM
for the first time. Initialization can also be used to clear all of the data already
registered in the NT600M. Screen data can be initialized regardless of the
setting for the resume function.
70
Memory Switch Settings
Initializing Screen Memory
Section 6-3
In order to initialize screen memory, for example, first select “Init. Memory”
from the Maintenance Menu. The Memory Initialization Menu will then be displayed, offering several choices of memory to initialize.
Screen data
Screen data and all kinds of set values
Memory table data
Numeral tables, string tables (Initialization restores
values set by Support Tool.)
Retains the number of times a screen for which “history
attributes have been set is displayed by means of
commands from the host. (Only when battery is
installed.)
Display history data
When “Init. Screen is selected, the following screen will be displayed for confirmation.
Initialize Screen Memory?
Yes
No
If you select Yes, then initialization will be executed and all screen data will
be deleted. After processing has been completed, RUN Mode will be restored.
If you select No, then RUN Mode will be restored without initialization.
If you also wish to initialize any other data, display the System Menu again
and start the process from the beginning.
Initializing Display History
The display history can be saved either in terms of order of occurrence or
order of frequency. Once the capacity is full, history records beyond that point
will not be saved, so it is necessary to periodically initialize the history.
To initialize the history, first select “Init. History” from the Memory Initialization
Menu. The following message will then be displayed for confirmation.
Initialize History?
Yes
No
If you select Yes, then initialization will be executed and history data will be
deleted and RUN Mode will be restored. If you select No, then RUN Mode
will be restored without initialization.
It is also possible to initialize the display history by means of a command
from the host. For details, refer to the Host Interface Unit Operation Manual.
6-3
Memory Switch Settings
Memory switch settings set the NT600M display and key input sounds.
71
Memory Switch Settings
Section 6-3
Select “Memory SW” from the Maintenance Mode Menu.
MAINTENANCE MODE MENU
Quit
Display History
I/O Check
PT Settings
Initialize Memory
Memory SW
Liquid Crystal Display Type
Select one
Move the cursor to the item that is to be set and press the Enter Key. Each time
that it is pressed, the set value will change.
After the settings have been made, press the Buzzer, Up, and Down keys to return to RUN Mode. If the power to the NT600M is turned off at this point, the settings will not be registered.
MEMORY SW MENU
Quit
Key Input Sound
ON
Backlight Off
10 min
Display
Normal
Resume Function
ON
EL Display Type
MEMORY SW MENU
Quit
Key Input Sound
ON
Residual Image Elimination Function
1 hr
Resume Function
ON
Contents of Settings
Item
Key input sound
Setting
ON
OFF
Backlight off (LCD type)
72
10 min
Contents
The buzzer sounds for 0.2 second when a system key, touch switch, or
function key is input.
The buzzer does not sound when a system key, touch switch, or
function key is input.
If a backlight-off command is
If no key input (see note 1) or
command (see note 2) is received transmitted from the host, the
backlight turns off regardless of
for 10 minutes while a screen is
this setting.
being displayed, the backlight
turns off.
1 hr
If no key input (see note 1) or
command (see note 2) is received
for one hour while a screen is
being displayed, the backlight
turns off.
None
The backlight stays on constantly.
Memory Switch Settings
Section 6-3
Item
Setting
Display (LCD type)
Residual image elimination
function (EL type)
Normal
The screen display is normal.
Reverse video
The screen is displayed with dark and light reversed.
10 min
If no key input (see note 1) or command (see note 2) is received for 10
minutes while a screen is being displayed, the screen turns off.
If no key input (see note 1) or command (see note 2) is received for
one hour while a screen is being displayed, the screen turns off.
The screen stays on constantly. The residual image elimination
function does not operate, so turn off the screen periodically by means
of the host program.
1 hr
None
Resume function
Contents
ON
The contents of memory tables written by the host during operation are
retained even if the NT600M power turns off or a reset is executed.
If power to the NT600M is turned off or a reset is executed, the
contents of the memory table are overwritten by the contents of data
created by the Support Tool.
OFF
Note
1. Key Inputs
System keys, touch switches, function keys
2. Commands
Screen-change command
Setting screen overlap command (serial type communications only)
On-line transfer completed command (Restart with change to RUN Mode)
Backlight-on command
3.
Operating Conditions for
the Backlight Off and
Residual Image Elimination
Functions
indicates a default setting.
When either “backlight off” or “residual image elimination” is set to either “10 minutes” or “one hour,” the internal timer starts counting as soon as the key input or
command is received. When the time is up, the backlight or EL screen turns off.
The relevant key inputs and commands are as follows:
When any one of the above key inputs or commands is received, the backlight
will be turned back on and the internal timer will start counting again. If a key input or command is then received before the time is up, the timer will be reset and
the count will start over.
The resume function retains character string and numeral table data when power is interrupted or when the reset switch is pressed.
Resume Function
1, 2, 3...
1. When the Resume Function is Set to Off
The contents of character string and numeral tables are cleared when the
power to the PT is turned off or when the reset switch is pressed. After the
power is turned back on, or after the reset, character string and numeral
table data is read from the screen memory and operation begins again. If
new character string or numeral table data is transferred from the Support
Tool, that new data overwrites the data in the memory tables.
2. When the Resume Function is Set to On
If the power to the PT is turned off, or if the reset switch is pressed, the character string or numeral table data prior to the power interruption or reset is
retained. If new character string or numeral table data is transferred from the
Support Tool, the contents of the screen memory are refreshed but the
memory table data does not change. In order to return the contents of the
memory tables to the initial values that were created by the Support Tool,
execute “initialize memory table.”
73
Memory Switch Settings
Display Examples
Section 6-3
Depending on the setting of the resume function, the display at the time of powering up will be as follows:
Display After Power is Turned
Back On or After Reset
Display at Beginning
of Operation
0123
ABC
The initial values
created by the Support
Tool are displayed.
Display just Prior to Power
Interruption or Reset
When resume function
is set to “on”
0123
ABC
When resume function
is set to “off”
9999
XYZ
Memory Table Data
Power turned off or reset
switch pressed.
74
9999
XYZ
SECTION 7
Online Transfer
This section describes transferring screens online to and from the host computer. This function can only be used with
RS-232C and RS-422A Host Interface Units. For details on Host Interface Unit commands, refer to information on online transfers in the Host Interface Unit Operation Manual. Functions used to create screens and control display attributes
on the PT are described in Section 4 Display Functions of this manual. Functions used to input data on-screen are described in Section 5 Input Functions. Data transfer and maintenance functions are described in Section 6 System Menu.
7-1
7-2
Host to PT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PT to Host . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
76
76
75
PT to Host
7-1
Section 7-2
Host to PT
• Screen data can be transferred along with screen numbers. Set the desired
screen number. If you set a screen number which is identical with one already registered in the NT600M, then the screen data for that number will
be overwritten.
• In addition to screen data, it is possible to transfer memory tables and
marks.
• A data transfer can be aborted by pressing the Buzzer Key, Up Key and
Down Key simultaneously. If that is done in the middle of a transmission,
that portion of the data which has already been transferred will be stored,
but all data beyond that point will be destroyed.
• If a transfer of mark data is interrupted, the data may be corrupted. If that
occurs, a message will be displayed to that effect when the System Menu is
next opened.
Screen during online transfer processing
(Blinks during transmission.)
PT ----> Host
Host ----> PT
Transmitting
Screen Data
System Memory
Memory Tables
Mark Data
History Data
Shows direction
of data transfer.
Shows type of data.
KB
Abort: BUZZER + UP+ DOWN
Number of bytes transferred (in kilobytes).
7-2
PT to Host
PT to Host
Screen data can be transferred along with screen numbers. All screens can be
transferred together, or any particular screen can be transferred individually. In
addition to screen data, memory tables, marks, and display histories can also be
transferred. Screen data is not lost even if the transmission is interrupted by a
system key input.
Transmitting Data
PT→Host
Screen data
0 KB
Abort: BUZZER + UP+ DOWN
76
PT to Host
Relationship Between
On-line Transfer and the
Resume Function
Section 7-2
Just as when transferring data from the Support Tool, on-line transfer writes data
directly from the host to the screen memory. The display contents, therefore, are
affected by the resume function.
Display After Data is Received Directly
9999
XYZ
Reception
Display After Data is Received from Host
9999
XYZ
When resume function is set to “on”
2752
UVW
When resume function is set to “off”
New Data Transferred from the Host
2752
UVW
77
SECTION 8
Maintenance and Inspection
This section provides troubleshooting and basic maintenance methods, including battery replacement.
8-1
8-2
8-3
8-4
Checking Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the Lithium Backup Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3-1 Spare Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3-2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3-3 Precautions When Cleaning the PT Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RUN Mode Function Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80
80
81
81
81
82
83
79
Changing the Lithium Backup Battery
8-1
Section 8-2
Checking Operation
The hardware status of the NT600M can be checked with the Maintenance
Menu. Symptoms and corrective measures for errors that cannot be checked
are shown in the table below.
Symptom
POWER indicator does
not light.
Probable cause
Power is not being input.
A fuse is blown.
Corrective measures, processing
Provide a power supply with a rated voltage of 100 to
240 VAC.
Contact your OMRON representative.
Screen does not display. It is waiting for a command from the Transfer a command from the host. Screen data
host, or there is no screen data, or should be registered at the Support Tool in advance.
the contrast is poorly adjusted.
Adjust the contrast.
Screen suddenly goes
blank.
Cannot communicate
with
ihS
Support T
Tool.
l
The System ROM is not installed
correctly.
Screen no. 0 has been called by
the host.
PT is not in Transmit Mode.
There is a faulty connection with
the Support Tool.
DIP switch settings are not correct.
Cannot communicate
s g Host
os Interface
e ace U
using
Unit
(Serial communications Host Interface Unit connections are
type)
faulty.
For the NT600M-LK202, terminator
settings are not correct.
Mount the System ROM into the socket in the correct
direction, and make sure that it is secured.
There is no problem. Correct the application program.
Select Transmit Mode from the System Menu.
Check connecting cables.
Check PT settings under the Maintenance Mode and
be sure that settings match the host settings.
Check wiring of connecting cables.
Use shielded wire.
Check whether the cables are within the maximum
lengths.
When using RS-422A communications, specify only
the last Terminal from the host as the terminator (turn
on termination resistance on the last terminal only).
Cannot communicate
using Host Interface Unit
(Parallel
communications type))
Message displayed
indicating Host Interface
Unit is missing.
Communications timing with Host
Interface Unit is incorrect.
Check switch setting and the host’s strobe cycle time.
The Maintenance Mode can be used to check
communications.
The Host Interface Unit is not
installed properly.
Install the Host Interface Unit.
Check to be sure that the specifications match for the
System ROM and the Host Interface Unit.
Lamp remains lit when
screens are changed.
Message displayed
indicating screen data is
corrupted.
Lamp and touch switch are
overlapping.
1) Screen memory is defective.
2) There was a power interruption
or the reset button was pressed
while data was being transferred.
1) System ROM is not properly
installed.
2) There was a malfunction due to
external noise
Touch switches can be used as lamps just as they are.
(They have shared functions.)
1) Replace the screen memory.
2) Initialize the screen memory, and then re-transmit
the data.
DIP switch 1-3 is OFF.
Turn off the power, then set DIP switch 1-3 to ON and
turn the power on again.
Buzzer sounds and
RUN indicator turns off.
Operation suddenly
stops. Displays go out
and do not return.
System messages
display is wrong.
8-2
1) Mount the System ROM into the socket in the
correct direction, and make sure that it is secured.
2) Keep the communications cable separate from
sources of noise. Install noise filters in power supply
lines.
Changing the Lithium Backup Battery
In the NT600M, a lithium cell is used for a memory backup. If the BAT LOW
indicator on the front panel lights, replace the battery within five days.
Battery model
3G2A9-BAT08
Battery backup time
5 years at 25%C.
Replacement time
Within 5 minutes from the time power is turned off.
Note 1. The battery can also be replaced while the power is on. If you do it that
way, then there is no need to replace the battery within five minutes, but
you must exercise care in handling.
80
Maintenance and Inspection
Section 8-3
2. Even if the BAT LOW indicator does not light, the battery should be replaced after five years.
Replacing the Battery
1, 2, 3... 1.
2.
3.
Turn the power off. If the power has not been on, turn it on for at least
one minute and then turn it of again before replacing the battery.
Take off the switch cover on the back of the Terminal.
Remove the battery from the connector and put in a new battery. Be
sure that the connector is straight when inserted.
Note a) Do not take more than five minutes to replace the battery, otherwise the internal memory may be lost.
b) The battery can be replaced with the PT turned on, in which case
there is no limitation for battery replacement time.
Lithium battery
Battery connector
Reset button
Press this button to initialize
the PT. (The status of screen
data prior to initialization will
be retained.)
8-bit DIP switch
Used for system
settings.
4.
! Caution
Replace the cover.
The lithium battery can explode if placed into a fire, or it can explode, burn, or
leak if the + and -- terminals are short-circuited or if the battery is recharged or
dismantled. Handle the battery with care.
Note If no battery is connected, BAT LOW indicator operation is not stable.
8-3
8-3-1
Maintenance and Inspection
Spare Terminals
In order to restore operations as quickly as possible in the event of a
NT600M breakdown, it is a good idea to always keep a spare Terminal on
hand.
8-3-2
Inspection
• The NT600M’s liquid crystal display and backlight can wear out. If they become hard to see, replace the Terminal.
81
Maintenance and Inspection
Section 8-3
• The standard inspection period is once every 6 to 12 months, but it should
be moved up if the operating environment is harsh. If there is any deviation
from the criterion, then it should be corrected.
Inspection item
Power supply
Operating
environment
Installation
Replaceable
parts
Inspection content
Measure at the power supply terminal block. Are
voltage fluctuations within the criterion?
Is the ambient temperature (the temperature inside
of the panel) suitable?
Is the ambient humidity (the humidity inside of the
panel) suitable?
Is dust collecting?
Criterion
Remarks
Voltage fluctuation range
(85 VAC to 264 VAC)
5%C to 40%C
Tester
35% to 85% There should
be no condensation.
There should be no dust.
Hydroscope
Is each Terminal firmly secured?
There should be no loose
screws.
Are the connectors for the connecting cable inserted There should be no loose
perfectly and locked?
screws.
Are any screws for the external wiring coming loose? There should be no loose
screws.
Is any external wiring loose or disconnected?
There should be no external
abnormalities.
Can you read the characters on the liquid crystal
Average life expectancy of
display?
liquid crystal: 50,000 hrs
Is the backlight illumination as bright as it should be? Average life expectancy of
backlight:
20,000 hrs
Thermometer
Visual
Accessory
tool
--Phillips
screwdriver
Visual
Visual
Tools for Inspection
• Phillips and Flat-blade screwdrivers
• Voltage tester or digital voltmeter
• Industrial alcohol and all-cotton cloth
Measuring Instruments (Depending on Case)
• Synchroscope
• Oscilloscope with pen output
• Thermometer
• Hydroscope
Precautions for Handling
• Turn off the power before replacing Terminals.
• When you discover a defective Terminal and replace it, check again to be
sure that the problem was actually with the Terminal.
• When returning a defective Terminal for service, please describe the problem in as much detail as possible. Send the Terminal to the OMRON offices
closest to you.
8-3-3
Precautions When Cleaning the PT Screen
If the NT600M screen gets dirty, it will become hard to read. Be careful of the
following points when cleaning it.
• When cleaning, wipe with a dry, soft cloth. If the dirt does not come off, then
moisten the rag with water and rub hard.
• Wiping with a chemical cloth or with volatile solutions such as benzine or
thinner may cause degeneration. A little alcohol may be used if necessary.
• Prolonged contact with rubber, vinyl products, or tape may leave marks.
82
RUN Mode Function Configuration
8-4
Section 8-4
RUN Mode Function Configuration
This chart shows the measures to be taken in response to an error which
occurs in RUN Mode.
RUN Mode Chart
Power on
Screen
message
check
Error
Normal
Screen
memory
check
DIP Switch
Check
Screen display
Error
Normal
Screen Data
Corrupted
Operation
Stopped
Settings
check
Mark Data
Corrupted
Remedy
Memory Not
Formatted
Initialize the memory and re-transmit the
screen data.
Error
Normal
Setting Error
Operation
Stopped
Remedy
Check the NT600M and Host Interface Unit switch settings.
(1)
Remedy
Host connection
check
Normal
Error
Host Connecting
Turn on host’s power. Make sure
host is running. Check host’s
connecting cables.
(2)
83
RUN Mode Function Configuration
Section 8-4
(2)
I/O check
Normal
Continue Mode
PC mode
check
PC: Programmable Controller
Stop Mode
I/O Check Error Has Occurred
Remedy
Operation
Stopped
Power
supply
check
Once only when power is turned on.
Normal
Designated Screen
(1) (Previous page)
84
Check I/O settings of remote devices.
Check the PC’s I/O Units.
Initial Screen
Appendix A
Standard Models
RS-232C Cable for Connecting Devices (CV500-CN228)
2 ,000 +150
--0
Note
The personal computer end of the CV500-CN228 Connecting Cable is a 25-pin D-sub male connector. To connect to an IBM PC/AT or compatibles, a 9-pin or 25-pin D-sub female adapter is
required.
Dustproof Cover
NT600M-KBA01 (for NT600M-DT/DNjjj)
NT600M-KBA02 (for NT600M-DF122 and NT600M-DN211 + NT600M-FK210)
Under severe conditions, this can be used to protect the display area and the controls from oil and dust.
NT600M-KBA01 Dimensions
214.4 +0.2
Material: Silicon rubber
13.2
327.4 +0.2
Dimensions (mm)
85
Standard Models
Appendix A
NT600M-KBA02 Dimensions
254.4+0.2
13.2
327.4+0.2
Protective Sheet
NT600M-KBA11 (for NT600M-DT/DN/DF122)
NT600M-KBA12 (for NT600M-DT/DN211)
The protective sheet protects the display screen from dirt and scratches, and eliminates reflection and glare.
(The back side of the sheet has a sticky surface. Peel the paper off of the back and attach the sheet.)
Protective film
Protective sheet
Display screen
Back-side paper
NT600M
Dimensions
NT600M-KBA11
0
151.8 --0.5
NT600M-KBA12
0
151.8 --0.5
28.5+0.3
32.7+0.3
0
244.8 --0.5
0
244.8 --0.5
NT600M-DF122 Key Sheets (Five Sheets)
Use these sheets for NT600M-DF122 and NT600M-FK210 function keys. By simply peeling them off of the
paper, you can easily write on them and attach them. You can also rub off anything written with oil-base ink. If
they get dirty, you can easily remove and replace them.
Rectangular hole
86
Appendix B
Specifications
General Specifications
Item
Specifications
Power supply voltage
100 to 240 VAC
Allowable power supply voltage range
Power consumption
85 to 264 VAC, 50/60 Hz
Insulating resistance
Between AC terminal block and GR:
20 MW min. (at 500 VDC)
Dielectric strength
Between AC terminal block and GR:
Leakage current: 0.8 mA max.
1000 VACp-p
Pulse width:
100 ns to 1 ms
Pulse rise time: 1 ns
2,300 VAC at 50/60 Hz for 1 min
Noise resistance
Vibration resistance
40 VA max.
NT600M-DT/DF-122:
10 Hz to 22 Hz with 1.5-mm double amplitude in X,Y, and Z directions
22 Hz to 500 Hz (1.5 G; 14.7 m/s2) in X,Y, and Z directions for 30 min total
NT600M-DT/DN211:
10 Hz to 50 Hz with 0.5-mm single amplitude (acceleration: 2.0 G; 19.6 m/s2) in X,Y, and
Z directions for 1 hr each
Ambient operating temperature
Ambient operating humidity
Destruction: 30G (294 m/s2) 3 times each in X, Y, and Z directions
Malfunction: 20G (196 m/s2) 3 times each in X, Y, and Z directions
NT600M-DT/DF-122: 5°C to 40°C
NT600M-DT/DN211: 0°C to 50°C
35% to 85% (with no condensation)
Operating environment
No corrosive gas
Storage temperature
Enclosure ratings
NT600M-DT/DF-122: --20°C to 60°C
NT600M-DT/DN211: --20°C to 70°C
Front control panel IP52 (Drip-proof when dust cover is installed.)
Rear case
IP20
Terminal section
IP00
Weight
Approx. 3 kg
Dimensions
NT600M-DT122/DT211/DN211: 325 x 198 x 105 (WxHxD)
NT600M-DF122: 325 x 238 x 105 (WxHxD)
(These dimensions do not include the cable.)
Shock resistance
87
Specifications
Appendix B
Characteristics
Display Specifications
Item
LCD-type display:
(NT600M-Dj122)
EL-type display
(NT600M-Dj211)
Indicators
Specifications
Dot matrix STN liquid crystal display device (9.5 inches equivalent)
No. of dots:
640 x 400
Effective display area: 206 mm x 130 mm
Angle of vision:
Up 20°; down 35°; right/left ±30°
Life expectancy:
50,000 hrs min.
Backlight
Cold-cathode tube
Life expectancy:
10,000 hrs min. (20,000 hrs average)
Automatic turn-off:
Can be set to not turn off, or to turn off in 10 min or 1 hr
EL display (9 inches equivalent)
No. of dots:
640 x 400
Effective display area: 192 mm x 120 mm
Display color:
Yellow-orange
Life expectancy (with a 30% decrease in brightness): Approx. 30,000 hrs
Automatic turn-off:
Can be set to none, 10 min or 1 hr
Three indicators:
POWER indicator (Green LED):
RUN indicator (Green LED):
BAT LOW indicator (Red LED):
Lit when power is being supplied.
Lit during operation.
Lit when battery level drops.
Control Panel Specifications
Item
Specifications
System keys
Four keys: buzzer-stop, up-scroll, down-scroll, execute (enter)
Functions: System Menu selection, buzzer off, bar cursor movement, up/down scroll for
continuous screens, execution of numeric settings
Touch panel (DT type)
Number of switches:
128 per screen max.
Input switch type:
Pressure-sensitive
Operating force:
100 g min.
Life expectancy:
1,000,000 operations min.
No. of keys:
12 (fixed)
Input switch type
Pressure-sensitive
Key sheets are replaceable.
12-key Function Key Unit
(DN type)
NT600M-FK210
Function Keys (DF type)
Display Capacity
Item
Specifications
Display characters
Half-size character (8 x 8 dots):
Normal character (8 x 16 dots):
Mark (16 x 16 dots):
Character size
Half-size characters: Approx. 2.5 x 2.5 mm
Normal characters: Approx. 2.5 x 5.0 mm
Marks:
Approx. 5.0 x 5.0 mm
Enlargement function
Horizontal, vertical, 4 times, 9 times, 16 times, 64 times
Display attributes
Inverse, blinking, inverse blinking
Graphics
Polyline, circle
88
Alphanumeric and symbols
Alphanumeric and symbols
User defined, 64 max.
Specifications
Appendix B
Display Capacity
Item
Terminal mode
Specifications
Display
Character
Characters, numeric values, and graphics designated by the host are displayed
(RS-232C or RS-422A interface required).
Displays optional characters (screen number designation).
elements
Graphics
Polylines (broken continuous line) and circles
String displays
Maximum 256 total, 50 places per screen and 40 bytes per string
Numeral displays
Maximum 256 total, 50 places per screen, 8-digit display
Bar graph display 2 to 255 dots; 50 places per screen
Screen
Lamps
Maximum 256, 128 places/screen
Touch-switch
Maximum 256, 128 places/screen
Numeral settings
50 places/screen
Normal screen
Displays screen.
types
Overlapping
screens
Continuous
screens
Screen attributes
No. of
screens
No. of registered
screens
Screen numbers
Screen registration method
Screen saving method
% and ± display capability
Overlapping of a maximum of 8 screens is possible.
Scrolling the display for a maximum of 8 registered screens is possible.
Page scroll with system Up and Down Keys.
Alarm, continuous buzzer, intermittent buzzer, bit function keys, bit touch-switch, display
history recording, ten key
1,000 max.
0:
No display (Full screen designation at time of screen data upload.)
1 to 1,000: User-registered screens
Transfer data to the PT from IBM PC/AT compatible or write to EPROM chip and then
install it.
Can be saved to SRAM (with battery backup), EEPROM, or EPROM chip.
Memory format: Special NT600M format
Data Quantities
Item
Specifications
String data
40 characters (normal size characters) x 256 strings max.
Numeral data
8 columns x 256 values max.
Mark data
64 items
Switches and lamps
p combined: 256 max.
(Th
(There
iis no lilimit
i when
h the
h di
direct connection
i method
h d is
i used.)
d)
Switches
Lamps
89
Specifications
Appendix B
Special Features
Item
Alarm output
Host RUN input
Buzzers
Maintenance functions
Specifications
Relay output on rear terminal block; NO contact.
Rating: 1 A at 24 VDC or 0.5 A at 100 VAC, with resistance load
Output condition: NO Contact (Closes when a command is received from the host or
when there is a screen displayed with an alarm-ON specification.)
Photocoupler input on rear terminal block.
Rating 24 VDC +10%/--15%
When this input goes OFF, the display “host error” regardless of other conditions.
Two types: Continuous sound and intermittent sound.
ON:
The buzzer will sound when a key input is made, when a buzzer-ON command is received from the host, or when a screen with a buzzer-ON specification is called.
OFF:
The buzzer is turned OFF when the Buzzer Key is pressed, when a buzzerOFF command is received from the host, or when a screen without a buzzer-ON specification is displayed.
Loudness: 80 dB min. and 87 dB on average (measured at a distance of 10 cm)
Self-test for memory, switches, etc.
Status setting confirmation for communications and other conditions.
Simple communications confirmation.
Battery backup
Data backed up by battery when screen memory is SRAM.
Data backup time: 5 years (at 25°C)
If there is a voltage drop, the BAT LOW indicator on the front panel will light and the Battery Low Flag to the host will turn ON.
The battery can be replaced from the rear of the Terminal during operation.
Key input sound setting
If Key Input Sound is set to ON in the Memory Switch Menu, a beep will sound for 0.2 s
when a system key, function key, or touch switch is pressed.
90
Appendix C
Memory Check Table
This table shows the amount of memory required for creating various kinds of screen data. It can be used a standard for selecting screen memory.
Data
Item
Without direct
connection
(Unit: byte)
With direct
connection
(Unit: byte)
Remarks
13,480
20,146
Minimum amount required for lower limit.
Number of screens req
ed
quired.
Tables, error screens,
etc.
Basic information
File units
Link information
Each header
Normal screens only
Command units
Character input
p
1 character
1 character added
Polyline
y
One
10
10
One added
+4
+4
-------
6
8
12
6
--16
----No guide characters
1 guide character
1 character added
12
24
16
+12
+1
16
38
30
+12
+1
Circle: no guide characters
Rectangle: no guide
characters
1 guide character
1 character added
16
30
16
34
+12
+1
+12
+1
Numeric setting
Function key
Overlapping screen
-------
4
--18
18
18
18
Continuous screen
---
18
18
Circle
Standalone
Character string display
Numeric display
Bar graph
Touch switch
Lamp
Single screen units
W/o history:
10
With history:
34
2
Fixed information:6
Other:
4
14
+1
62
4
6
14
+1
Required first time
only.
Fixed information
1 byte added when all
sums are odd numbers.
---
Variable information
--1 byte added when result is odd number.
---
1 byte added when result is odd number.
--Basic screen information added regardless
of number of child
screens.
Note If the edge of a screen goes beyond 64K bytes, the data will move to the next page
(when 128 bytes or 256 bytes). 32K bytes = 32,768; 64K bytes = 65,536; 128K bytes = 131,072;
256K bytes = 262,144
I/O headers:
62 bytes (even for only one) + number x 20 bytes
91
Appendix D
Special Characters
English Character Codes
Pin 2 of SW2 must be ON to enable English language messages to use the following codes.
Example: Hex code is represented by 30, decimal code by 48, and character by 0.
30
0
48
Code 20 and 32 in the table represents a space, as indicated by “SP.”
2-0
20
3SP
32
-1
21
22
23
”
24
#
25
$
26
%
-8
-9
-A
-B
-C
-D
-E
-F
27
39
28
40
29
41
2A
42
2B
43
2C
44
2D
45
2E
46
2F
47
34
35
36
3
(
)
*
+
,
.
/
37
55
38
56
39
57
3A
58
3B
59
3C
60
3D
61
3E
62
3F
63
42
43
4
44
45
B
46
C
8
9
:
;
<
=
>
?
47
71
48
72
49
73
4A
74
4B
75
4C
76
4D
77
4E
78
4F
79
52
53
D
54
55
R
56
S
H
I
J
K
L
M
N
O
57
87
58
88
59
89
5A
90
5B
91
5C
92
5D
93
5E
94
5F
95
62
63
T
64
65
b
66
c
X
Y
Z
[
\
]
^
_
67
103
68
104
69
105
6A
106
6B
107
6C
108
6D
109
6E
110
6F
111
72
73
d
74
75
r
76
s
h
i
j
k
l
m
n
o
77
119
78
120
79
121
7A
122
7B
123
7C
124
7D
125
7E
126
7F
127
82
83
t
84
85
é
86
â
x
y
z
{
|
}
~
87
135
88
136
89
137
8A
138
8B
139
8C
140
8D
141
8E
142
8F
143
æ
92
Æ
93
ô
147
ä
94
ö
148
à
95
ò
149
å
134
w
91
146
133
v
É
145
132
u
90
144
ü
131
118
g
81
130
117
f
9Ç
129
116
e
80
128
q
115
102
W
71
114
101
V
8p
113
100
U
70
112
a
99
86
G
61
98
85
F
7‘
97
84
E
60
96
Q
83
70
7
51
82
69
6
6P
81
68
5
50
80
A
67
54
’
41
66
53
&
38
-7
2
52
37
-6
33
5@
65
51
36
-5
32
40
64
1
50
35
-4
31
49
34
-3
40
48
!
33
-2
30
96
û
150
ç
ê
ë
è
ï
î
ì
Ä
Å
97
151
98
152
99
153
9A
154
9B
155
9C
156
9D
157
9E
158
9F
159
ù
ÿ
Ö
Ü
¢
£
¥
Pt
ƒ
93
Index
Numbers
12-key Function Key Units, checking, 67
A--B
abbreviations, 5
alarms, controlling from host, 49
ALM OUTPUT terminals, 27
ASCII Unit, 11
backlight, controlling from host, 48
bar graphs, displaying, 47
types available, 4
display history, 63
controlling from host, 49
initializing, 70, 71
E--F
error messages, 35
Expansion Mode, 63
Function Key Units, 9
function keys, 14, 56
checking, 67
external input check, 67
battery, replacing, 80
buzzer, controlling from host, 49
C
C200H, host interface, 12
H
host computer
controlling PT operation, 48
data transfer, 45, 46, 47, 50, 54, 56
cable, 85
Host Interface Units, 8
displaying settings, 69
child screens, 43, 44
Host Link Unit, interface, 12
cleaning, precautions, 82
HOST RUN INPUT
controlling from host, 49
enable/disable setting, 16
communications
checking, 68
setting for NT600-LK201-EV1, 16
communications errors, automatic reset setting, 16
contrast control, 14
control panel, specifications, 88
cover, 85
HOST RUN INPUT terminals, 26
I--K
I/O checks, 65
indicators, 14
D
data transfer, PT to host, 54
dimensions, 22
DIP switch, 16
direct designation, applicable models, 4
display
attributes, 41
capacity, 88, 89
character scale, 40
characters, 40
controlling from host, 50
data quantities, 89
LCD/EL check, 69
positioning, 40
specifications, 88
speed, 50
initialization, 70
memory, 32
installation
environment, 20
mounting position, 21
panel mounting, 23
Key Sheets, 86
L
lamps
attributes, 47
displaying, 47
number per screen, 4
output check, 68
language, setting, 16
LG and GR terminals, 26
95
Index
M
screen memory, initializing, 70
memory capacity, 7
screens
changing, 42
continuous screens, 42
examples, 41
maximum limit, 7
maximum registered, 4
overlapping screens, 43
transferring online, 76
memory chips, 6
specifications, 87
memory switch settings, 71
standalone function, 4, 59
menus
overview, 34
selecting items, 34
system menu, 62
string table, 46
mode changes, enable/disable setting, 16
Support Tools, data transfer, 35
models, 6
switch inputs, transferring to host, 54
maintenance, inspection, 81
Maintenance Mode, 63
manuals, 5
memory, initializing, 32
Support Tool, 9
checking interface, 69
switch settings, 16
N
nomenclature, 13
SYSMAC BUS, interface, 12
system configuration, 10
system keys, 14, 34
numeral table, 45, 47, 56
numeric display, 45
numeric settings, 56
T
terminology, 5
P
parent screens, 43, 44
text strings, displaying, 46
touch panel, 13
precautions, general, xi
touch switches, 13
checking, 67
creating, 55
protective sheet, 86
Transmit Mode, 63
PT settings, displaying, 69
troubleshooting, 80
power supply, wiring, 25
R--S
RS-232C interface, 11
connector, 27
RS-422A interface, 11
Screen Data Memory Boards, 6
installation, 18, 19
switch settings, 18
96
W
wiring
ALM OUTPUT terminals, 27
HOST RUN INPUT terminals, 26
LR and GR terminals, 26
power supply, 25
RS-232C connector, 27
terminal block, 25
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. V002-E1-3
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the
previous version.
Revision code
1
Date
October 1991
1A
October 1992
Revised content
Original production
Page 3:
A row defining the C200H has been added
to the SYSMAC terminology table. Manual numbers
have been changed in the Reference Manuals table.
Page 4:
The numbers of registered screens have
been changed in the Memory Capacity and Number of
Screens table. The model legend for the system ROM
has been changed to incorporate the C200H. A model
number for the Host Interface Units has been added to
the legend and table, and the Note has been modified
accordingly.
Pages 6 to 7: C200H Interface has been added to the
list of allowable interfaces for communications in 1-4-2
Operation. NT600M-SMR01-E has been added to the
descriptions of each interface in 1-4-2 Operation.
Page 7:
added.
A C200H Interface description has been
Page 12: “Transfer Mode” has been changed to “Transmit Mode” for pin 6 of the switch settings table.
Page 41: Numbers have been added to the graph’s
horizontal scale.
Page 52: “Transfer Mode” has been changed to “Transmit Mode” within the text.
Page 57 to 58: NT600M-SMR01-E has been added to
the descriptions of each Host Interface Unit I/O checks.
Page 58: C200H Host Interface Unit I/O check description has been added.
Page 59 to 60: NT600M-SMR01-E has been added to
the descriptions of each Host Interface Unit PT checks.
Page 58: C200H Host Interface Unit PT check description has been added.
Page 69: A row for the C200H Host Interface Units has
been added to the table.
2
September 1993
2A
October 1996
The section on Precautions has been added in front of Section 1.
3
October 1997
Page xii: ROM and screen memory precautions added.
Pages 2 to 4: A general introduction has been added.
Pages 4 to 5: New features are described.
Pages 5 to 12: New model numbers have been added.
Pages 12 to 17: System configuration has been updated.
Pages 20 to 33: Changes have been made concerning
settings and installation.
Pages 36 to 37: Changes have been made concerning
powering up and initialization.
Pages 38 to 39: Changes have been made concerning
system keys and error messages.
Pages 39 to 40: Changes have been made concerning
transferring data to and from the Support Tool.
Page 41: A section on trial operation has been added.
Pages 44 to 45: Information on character displays has
been updated.
Pages 45 to 48: Changes have been made concerning
screens.
Pages 49 to 52: Changes have been made concerning
numeric displays, character strings, bar graphs, and
lamps.
Pages 52 to 53: Information has been added concerning graphics.
Pages 53 to 54: Changes have been made concerning
special controls.
Pages 54 to 56: Changes have been made concerning
display times.
Pages 57 to 60: Information has been added concerning on-screen switch inputs.
Pages 60 to 61: The section on inputting numeric settings has been revised.
Page 62: A description of the standalone function has
been added.
Page 64: The system configuration diagram has been
changed.
Pages 65 to 67: Changes have been made concerning
the System Menu and Transmit Mode.
Pages 67 to 71: The section on I/O checks has been
changed and updated.
Pages 71 to 72: The PT settings check has been revised.
Page 73: Changes have been made concerning initialization.
Pages 74 to 76: A section has been added concerning
memory switch settings.
Pages 78 to 79: Changes have been made concerning
on-line data transfers.
Page 81: Changes were made to troubleshooting chart.
Pages 82 to 85: Minor changes were made concerning
maintenance and inspection.
Appendix A: Additions and changes were made concerning optional equipment.
Appendix B: Some specifications were changed.
Appendix C: A memory check table was added.
Pages 4, 5, 7, 8, 9, 10, 17, 32, 40, 41, 48, 50, 75, 80, 89: RS-422 Interface
corrected to RS-422A Interface
Pages 4, 8, 42: NT-ZA3AT-EV2 Support Tool added.
Page 5: NT-series Support Tool Operation Manual added to the list in Reference Manuals.
Pages 4, 7, 8, 11, 12, 50: NT600M-LB121 and/or NT600M-LB122 Host Interface Units changed to NT600M-LB122-V1.
Page 7: Note added to table in 1-4-3 System ROM.
Page 26: Circuit diagram in 2-5-4 HOST RUN INPUT Terminals corrected.
Page 88: “100 g max.” corrected to “100 g min.” for the operating force in Control Panel Specifications.
Page 93: Appendix D Special Characters added.
97
">
/
Downloaden
Even een vriendelijke herinnering. U kunt het document hier bekijken. Maar het belangrijkste is dat onze AI het al heeft gelezen. Het kan complexe dingen in eenvoudige bewoordingen uitleggen, uw vragen in elke taal beantwoorden en u helpen snel te navigeren, zelfs in de langste of meest ingewikkelde documenten.