OMRON NT-series NT20S, NT20S-ST121-EV3, NT20S-ST161-EV3, NT20S-ST122-V1, NT20S-ST128, NT20S-ST168, NT20M-DT131, NT600S-ST121(B)-EV3, NT600S-ST211(B)-EV3 Programmable Terminal Operation Manual
Below you will find brief information for Programmable Terminal NT-series NT20S-ST121-EV3, Programmable Terminal NT-series NT20S-ST161-EV3, Programmable Terminal NT-series NT20S-ST122-V1, Programmable Terminal NT-series NT20S-ST128, Programmable Terminal NT-series NT20S-ST168. The NT20S is a programmable terminal that enables displays of production line monitoring and instructions to the operation site and notifies the switch ON/OFF status and numeric value inputs to the Host. All functions of NT20M are compatible with NT20S. The NT20S has a downsized body and it is easy to read, can be read even in direct sunlight, and the angle of visibility is equal to NT20M-DT131. NT20S-ST121-EV3 can be connected to Mitsubishi A series PCs. NT20S-ST121-EV3, NT20S-ST122-V1 and NT20S-ST128 are connected to the host via an RS-232C cable.
Advertisement
Advertisement
NT-series
Programmable Terminal
Operation Manual
Cat. No. V020-E3-2
iv
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an
OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
The abbreviation “Host” means PC that controls NT20S.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1. Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1997, 1998
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS
1
2
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Intended Audience
General Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Functions of the NT20S . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 Role and Operation of NT20S
1-2 Functions of NT20S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Direct Connection Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 Communications with PC by Direct Connection
1-6 Communications by RS-232C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7 Before Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Hardware Settings and Connections . . . . . . . . . . . . . . . . .
2-1 Description of Parts and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Connecting to the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Connection to a PC by the Host Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Connection to a PC by the NT Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Connection to a PC by the NT Link (1:N) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7 Communicating with the PC Using C200H Direct Communication . . . . . . . . . . . . . . .
2-8 Host Connections by RS-232C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
System Menu Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Operation Flow by the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Starting the NT20S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Operation Modes and the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Initializing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5 Setting the Conditions of Communications with the Host by Using the Memory Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-6 Registering the Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 Starting the Operation
3-8 Various System Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9 System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xiii
xiv xiv xiv
1
10
12
15
18
19
2
4
21
22
27
31
32
45
49
58
63
65
66
67
68
72
75
86
90
91
99 vii
viii
SECTION 4
NT20S Functions and Operation . . . . . . . . . . . . . . . . . . . .
4-1 Creating and Transmitting Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Outline of Functions
4-3 Screen Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Memory Tables
4-5 Bar Graphs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7 Touch Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8 Numeral Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
How to Use the Host Link/NT Link . . . . . . . . . . . . . . . . . .
5-1 Overview of Direct Connection Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Memory Tables and Bar Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Lamps, Touch Switches, Numeral Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 NT20S Status Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Notification of the Operating Status to the PC
(Determining the NT20S Operating Status) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Using the RS-232C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 RS-232C Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Screen Display
6-3 Memory Tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Lamps, Touch Switches, Numeral Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5 Controlling the NT20S Status
6-6 Terminal Commands
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7 Key to Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXAMPLE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 7
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . .
7-1 Hardware Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Responding to Displayed Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3 Maintenance of the NT20S
7-4 Inspection and Cleaning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
199
200
201
204
205
208
214
216
222
223
235
236
237
239
241
111
112
118
122
126
129
133
136
140
151
152
163
178
191
196
APPENDICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Handling the RS-232C/RS-422A Converter Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D. NT20S Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E. NT20S Internal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F. Function Restrictions Depending on the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G. Method for Making the Cable for Connection to the Host . . . . . . . . . . . . . . . . . . . . . . . . .
H. Making the Cable for Connection to the Support Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I. Connecting to an RS-232C/RS-422A Converter Unit (1:1) . . . . . . . . . . . . . . . . . . . . . . . .
J. Model List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
K. Option List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L. PC Memory Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
M. Special Characters
INDEX
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
243
243
248
249
251
252
255
256
268
269
271
276
278
279
281
ix
x
About this Manual:
This manual describes the basic functions and operation procedures of the NT-series programmable terminal NT20S, its operations when connected to a PC or a Host, and includes the sections described below.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate the NT-series programmable terminal NT20S.
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
Section 1 describes the operation functions, system configuration, and the direct connection function of the NT20S.
Section 2 describes the NT20S hardware settings, its installation in an operation panel, its connection to the Host, etc.
Section 3 describes the procedure before operating the NT20S, and useful functions when operating it.
Also describes how to perform an operation check.
Section 4 describes the functions of the NT20S when it is connected to a Host.
Section 5 describes how to operate the NT20S when the host link/NT link is used for communication.
Read this chapter only when using the NT20S-ST121j/ST161j/ST122j.
Section 6 describes how to operate the NT20S when the RS-232C interface is used for communication.
Read this chapter only when using the NT20S-ST128j/ST168.
Section 7 describes the procedures to follow when the system does not operate correctly, and the procedure for routine maintenance of the NT20S.
APPENDIX describes the specifications and the method for making connecting cables, and includes an area list for the PC.
xi
Related Manuals and Their Contents:
The related manuals are indicated below.
The j symbol at the end of the manual number is the revision history symbol.
[Operating the programmable terminal and communicating with the host]
S NT20S Programmable Terminal Operation Manual (V020-E1-j)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
This manual
This operation manual is the manual for the NT20S itself.
The NT20S is a unit which integrates a programmable terminal body and host interface unit. This operation manual describes the functions and handling of both the programmable terminal body and the host interface function.
[Creating and transferring screen data]
S NT Series Support Tool Ver.2j Operation Manual (V028-E1-j)
The screens displayed on the NT20S are created with the support tool and transferred to the NT20S. This manual describes how to create and transfer screen data.
[For Connection to Other Makers’ PCs]
S
PC Connection V042-E1-j
NT600S-ST121(B)-EV3 and NT600S-ST211(B)-EV3 can be connected to Mitsubishi A series PCs. This manual describes how to make the connection and how to make settings when connecting the PT to a Mitsubishi A series PC.
In order to use the PT while connected to a PC made by a manufacturer other than OMRON, the Ver. 2.3 support tool must be used.
xii
PRECAUTIONS
This section provides general precautions for using the Programmable Terminal.
The information contained in this section is important for the safe and reliable application of the Programmable
Terminal. You must read this section and understand the information contained before attempting to set up or operate a Programmable Terminal.
1 Intended Audience
2 General Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xiv xiv xiv xiii
Safety Precautions
1
2
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
S Personnel in charge of installing FA systems.
S Personnel in charge of designing FA systems.
S Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not desctibed in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for using the Programmable Terminal. Be sure to read this manual before attempting to use the software and keep this manual close at hand for reference during operation.
WARNING It is extremely important that Programmable Terminals and related devices be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying Programmable Terminals to the abovementioned applications.
WARNING Do not use input functions such as PT touch switches for applications where danger to human life or serious damage is possible, or for emergency switch applications.
3 Safety Precautions
Safety Conventions and their Meanings
Read these safety precautions carefully and make sure you understand them before using the Programmable Terminal so that you can use it safely and correctly.
This operation manual uses the following conventions and symbols to indicate cautions, warnings, and dangers in order to ensure safe use of the PT. The cautions, warnings, and dangers shown here contain important information related to safety. The instructions in these cautions, warnings, and dangers must be observed.
The conventions used and their meanings are presented below.
DANGER! Indicates information that, if not heeded, is likely to result in loss of life or serious injury.
WARNING Indicates information that, if not heeded, could possibly result in loss of life or serious injury.
CAUTION Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
xiv
Safety Precautions
WARNING: Do not attempt to take the PC apart and do not touch any internal parts while the power is being supplied. Doing either of these may result in electrical shock.
Turn off the power before replacing the backlight. Otherwise you could sustain an electric shock.
CAUTION: If the DIP switch settings have been changed when the NT20S is powered, reset the power to the NT20S. The changes with the DIP switches become effective only after the power supply is reset.
With systems in which the user program operates in accordance with the PC cycle time, since there is some fluctuation in the PC cycle time, the system operation may not be consistent, and this should be born in mind when designing the system.
S When making the connection, switch off the power to the NT20S and PC before disconnecting or connecting any connector.
When screen data transmission is in screen units, if there is data other than screen data, for example memory table or direct access changes, transmit this data also.
S Do not use input functions such as PT touch switches for applications where danger to human life or serious property damage is possible or for emergency switch applications.
During work at the panel, take care to ensure that no metal scraps enter the unit.
Otherwise, the product may malfunction.
For the connection to the power supply terminal block, twisted wires of 2 mm 2 greater cross sectional area and M3.5 size crimp terminals must be used.
Tighten the screws on the terminal block to a torque of 0.8N·m.
Otherwise fire may occur.
or
S After connecting the communication cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
S The cable’s tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Do not install the NT20S at sites subject to the following conditions.
Otherwise, the product may malfunction.
S
Severe temperature variations
S Temperatures or humidities outside the ranges stated in the specifications
S High humidity, condensation
S
Splashing chemical agents
S Severe oil splashing
S
Corrosive or flammable gases
S
Strong vibrations or shocks xv
xvi
S Direct exposure to wind and rain (outdoor sites)
S
Strong ultra-violet irradiation
Take adequate measures to ensure shielding if the NT20S is used at a location subject to any of the following conditions.
S
Static electricity, or noise from other equipment
S Strong electric or magnetic fields
S Nearby power cables
S
Potential exposure to radioactivity
S Do not install at a site exposed to chemicals, steam, etc, or subject to excessive airborne dust.
S Do not install the unit at locations where the ambient temperature goes outside the range 0 to 50_C or where the relative humidity goes outside the range 35 to
85% RH.
If the ambient temperature exceeds the range indicated above, install a fan or an air conditioner.
S Do not install the unit directly above equipment that generates a lot of heat
(heaters, transformers, large capacity resistors, etc.)
S
Take the following points into account in order to prevent noise
(1) Avoid installing the unit in panels in which high-voltage equipment is also installed.
(2) Install the unit at a distance of at least 200 mm from power lines.
(3) If the unit is installed next to equipment that generates a strong electric or magnetic field (solenoids, etc.), provide a gap of at least 40 mm.
S Secure sufficient space for ventilation.
S Do not install in sites subject to severe vibration or strong shocks.
S
Install at a distance from high-voltage devices and power equipment in consideration of operability and safety during maintenance.
S Press touch switches with a force of no greater than 30 N.
S
If touch switches are pressed in rapid succession, their inputs may not be successfully received.
Confirm that the input of a touch switch has been successfully received before moving on to the next operation.
S Do not press touch switches carelessly while the backlight is off or while nothing is displayed on the screen. Otherwise the system may operate unpredictably.
Only press touch switches after confirming system safety.
Confirm system safety carefully before changing monitor data.
To ensure system safety, be sure to periodically read the PT operating status bit from the host in order to ensure that the PT is always operating normally.
S Always turn off the power at the PC and PT before connecting the C200H interface cable. Otherwise the system may operate unpredictably.
If the actual character string is longer than the specified character string length, the specified number of characters is written and the remainder are discarded.
A timeout error message is displayed if the actual character string is shorter than the specified character string length.
This command cannot be used to write negative numbers. Use the 8-digit Write
Command (refer to 6-3 8-digit Write Numeral Memory Table).
The display attributes set with the Support Tool determine if lamps #0 to #31 light continuously or flash. The display status set with this command is ignored.
This command cannot be used for negative numbers. Always set “8” as the number of transferred digits when negative numbers may be input.
xvii
xviii
SECTION 1
Functions of the NT20S
NT20S is a new programmable terminal (PT) which incorporates a host interface unit and a RS-232C interface unit in a programmable terminal body. It can be easily installed and used.
This section gives the operation examples and characteristics of the NT20S so that you will understand the applications of the
NT20S.
1-1 Role and Operation of NT20S
1-1-1 Operations of NT20S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 Functions of NT20S
1-2-1 Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 Principal Functions of NT20S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-3 Comparison between NT20S and NT20M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-4 Differences Between the NT20S-ST121-EV3 and NT20S-ST122-V1 . . . . . . . . . . . . . .
1-2-5 Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 Host Link/NT Link (1:1)/C200H direct Systems
1-3-2 NT Link (1:N) System
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Direct Connection Function
1-4-1 NT Link
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-2 C200H Direct Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 Communications with PC by Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5-1 Functions of the Allocated Bits and Words
1-6 Communications by RS-232C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7 Before Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
10
7
8
10
11
4
4
2
3
6
15
18
19
12
13
14
15
1
2
Role and Operation of NT20S Section 1-1
1-1 Role and Operation of NT20S
NT20S is a programmable terminal used to display and transmit the information in an FA site. The following gives a general description of the role and operation of the NT20S for those who use a programmable terminal (PT) for the first time.
Production Line Status
Monitoring
The NT20S displays real-time information about the system and equipment operating status, etc.
Production Control 1994/1/25
Product
Today’s target
Current Production
NT20M
560 units
NT600M
441 units
275 units
% achieved
305 units
54.5 % 63.0 %
Messages The NT20S warns of system or equipment failures and prompts the appropriate remedial action.
Assembly line B is defective.
Alarm
-
Positioning pin
Panel Switch Functions Setting touch switches on the NT20S allows workers to use the NT20S as an operating panel. Production data input to the NT20S or the Host can be transmitted to a
PC.
Electroplating Control
Transport
Clamp UnClamp
Role and Operation of NT20S Section 1-1
1-1-1 Operations of NT20S
Displays Screens The information to be displayed (screen data) can be created on a computer by using support tools and stored in the NT20S. The screen data can be displayed on the NT20S in response to the instructions from a Host or touch switch operation.
Host
The screen data designated by instructions from Host or touch switch operation is displayed.
Receives Data from a Host The NT20S can be connected to the Host using the host link or NT link communication method, or by using the RS-232C interface or C200H direct communication to enable reception of the required data from the Host.
Host link, NT link, RS-232C,
C200H direct communication
Host
Sends Data to a Host Data input through a touch panel can be sent to a Host.
Host
Touch panel
ON/OFF information, numeric data, etc.
Screen Data The screen data to be displayed on the NT20S can be created by a computer by using support tools. Connect the NT20S to a PC/AT with an RS-232C cable so that the screen data are transferred to the NT20S.
RS-232C
Create screen data.
PC/AT
(support tools)
Screen data
This connection is made only to transmit the screen data by using NT20S and tools.
(If C200H direct communication is used, the support tool and Host can both be connected at the same time.)
3
Functions of NT20S Section 1-2
1-2 Functions of NT20S
The NT20S has the following features which are different from those of existing
NT20M;
1-2-1 Features
Downsized Body S The NT20S has the thinnest depth (54 mm or less in the panel) in the NT series.
S The width is shorter by 30 mm, maintaining the existing display area.
S
The system keys and tool connectors are located at other than the front side.
S
The communication cable connectors are housed in the unit so that they do not protrude from the unit.
S
The tool connectors and the Host communication connectors are used in common (when the host link/NT link or RS-232C is used).
Construction Best Suited to the FA Environment
S Easy-to-read screen even in direct sunlight.
(The monochrome mode liquid crystal display of ST16j models is even easier to read.)
S The angle of visibility is equal to that of NT20M-DT131.
S
Its backlight unit can be replaced at the operation site.
S
Conforms to IP65 waterproof requirements.
256 dots
128 dots
Wide angle of visibility 35_
A Host Link I/F Unit, Screen Data Memory, and a System ROM are All Incorporated
S With the NT link communication method, 1:1 and 1:N connections are possible.
S There is no complicated installation work except a simple connection to a Host.
S A flash memory is used for the screen data memory. There is no need of backup battery.
S The following communication systems are standard for each model:
NT20S-ST121-EV3/ST161-EV3
: Host link (direct) and NT link
NT20S-ST122-V1
NT20S-ST128/ST168
: C200H direct communication
: RS-232C communication (command control)
S
NT20S-ST121-EV3/ST161-EV3 can be connected to Mitsubishi FX series and
Mitsubishi A series PCs.
(Refer to “PC Connection, Operation Manual” V042-E1-j.)
4
Functions of NT20S Section 1-2
Touch Switch Operation The System Menu can be displayed by using the touch switches located in four corners of the screen.
Compatibility with NT20M Existing screen data, user programs, are compatible.
5
Functions of NT20S
1-2-2 Principal Functions of NT20S
Section 1-2
Functions Related to the Data Display
S Character display
Characters of various sizes can be displayed. Characters can flash or be highlighted.
S
Figure display
Straight lines, circles, and other graphic figures can be displayed.
S Memory data display
Contents of the character-string memory table and the numeral memory table can be displayed. The memory table contents can be changed from the PC/Host.
S Bar graph display
Bar graphs corresponding to the contents of the numeral memory table can be displayed.
S Lamp display
Lamps which turn on or flash as controlled by the Host can be displayed.
Functions Related to the Data Input
S Input by the touch switch
Data can be input by simply touching the screen.
S
Numeric setting function
The touch keys can be assigned with numeric values so that the numeric values can be input at the operation site and sent to the PC/Host.
Other Functions
S Buzzer
A built-in buzzer can be used.
S Communications with a PC
By connecting the NT20S with a PC using the host link, NT link, C200H, or RS-232C communication method, data can be received from the host and touch switch status information can be sent to the host.
S
System function
The system setting and maintenance can be executed by using the System Menu on the screen.
S Screen data creation
The screen data can be created by using support tools on the computer and stored in the unit.
S Unrestricted screen display
When the NT20S is connected to the host via an RS-232C interface, characters and graphics can be displayed independently of the registered screens.
(Terminal function) (NT20S-ST128/ST168)
6
Functions of NT20S Section 1-2
1-2-3 Comparison between NT20S and NT20M
The NT20S is a unitary PT which incorporates a system ROM, screen memory, and a host I/F unit (Host link, NT link, RS-232C, and C200H direct communication) as the standard equipment in one body.
The NT20S has the following features which are different from those of existing
NT20M;
Function NT20S
Communication
S
Host link/NT link incorporated
NT20S-ST121-EV3
S
C200H direct communication incorporated
NT20S-ST122-V1
S
RS-232C incorporated
NT20S-ST128
(other host I/F units cannot be connected)
Communication connector S The communication connector (9-pin) for a
Host is shared with that for a support tool.
(NT20S-ST121-EV3/ST128)
S
Connectors for support tool (9-pin) and Host connections on the rear face
(NT20S-ST122-V1).
Host RUN input terminal/
Alarm output terminal
System keys
Contrast control
Not provided
Waterproof performance Conforms to IP65.
Visibility in direct sunlight Excellent
Allowable momentary power interruption time
System ROM
Not provided
Back side
Not guaranteed
Built in (not replaceable)
NT20M-DT121-V2
Host I/F units are required.
The support tool connector (9-pin) is located on the front side. The Host connector (25-pin) is located on the back side.
Provided
Provided
Front side
Conforms to IP54F.
Average
5 msec
Resume function Not provided
History retaining function Not provided
Screen transfer f
Screen data compatibility f
(Note)
PC ladder compatibility f
Backlight replacement
Screen data memory f
Built in (flash memory only)
Screen data memory capacity
Outside dimensions
96KB
System ROM compatible with host I/F unit is required.
Provided
Provided
--
-f
(Only possible if screen data memory is an
SRAM)
Possible with NT20M-DT131.
Optional (select from EP-ROM, SRAM, and
EEP-ROM)
128 KB max.
190 × 110 × 58mm 220 × 110 × 82mm
Note: If a system key function is required on continuous screens or for numerical setting or buzzer stop, use a support tool and set the touch switches which have the system key function in such screens.
For details, refer to “System Key Functions” on page 139.
7
Functions of NT20S Section 1-2
1-2-4 Differences Between Existing Models and NT20S-ST121-EV3
The differences between the existing NT20S-ST121, NT20S-ST121-V1/
ST122-V1/ST121-V2 models for direct connection and the upgraded version
NT20S-ST121-EV3 are indicated in the table below.
Item
Communication type
ST121
Host link/NT link (1:1 connection) built in
ST121-V1/
ST122-V1
ST121-V1:
Host link/NT link (1:1 connection) built in
ST122-V1:
C200H direct communication built in
S
ST121-EV3
Host link/NT link (1:1 communication)/NT link
(1:N connection) built in
“20S” (“20M”--compatible mode available) “PT type” setting made with support tool
Memory capacity
Max. number of screens
“20M”
64KB
250
Screen transmission speed Standard only
Screen transmission unit
Direct connection version
File units only
Ver.4 only
96KB
500
Standard, high-speed
File units, screen units
Ver.4, Ver.5
( £ )Refer to the “PC Connection, Operation Manual” (V042-E1-j).
Differences between NT20S-ST12j and NT20S-ST16j.
S The only way in which NT20S-ST161 differs from NT20S-ST121 is that the display is a monochrome liquid crystal display. Functionally, the NT20S-ST121 and
NT20S-ST161 are absolutely identical and therefore if you are using an
NT20S-ST161 please refer to the explanations for the NT20S-ST121.
S The only way in which NT20S-ST168 differs from NT20S-ST128 is that the display is a monochrome liquid crystal display. Functionally, the NT20S-ST128 and
NT20S-ST168 are absolutely identical and therefore if you are using an
NT20S-ST168 please refer to the explanations for the NT20S-ST128.
Difference between direct connection Ver.4 and Ver.5
Ver.5 of the direct connection function has the following additional functions in comparison with Ver.4.
S
“Thumbwheel” type setting possible with the numeral setting function.
S
Upper and lower limit check can be set with the numeral setting function.
S
The type of operation (alternate, set, reset) can be selected for touch switch input notification.
S Indirect specification possible for numeral display and character string display functions.
8
Functions of NT20S
1-2-5 Displays
Characters
(character string)
Characters (text)
Bar graph
Section 1-2
The NT20S can display various kinds of elements such as characters, lamps, touch switches, and bar graphs on a screen. The screen data displayed on the
NT20S are created by using support tools on a computer.
Touch switches
Line 1 Status
Emergency stop
Restart
Machine name : NT20M-DT131
Production qty.
: 137 units
Numeric value
(Numeral table)
0%
Stage 1
50%
Stage 2
30%
100%
Stage 3 Lamps
Characters (text) Characters and marks which do not need to be changed can be written directly to the screen.
Characters (character-string memory table)
Character-strings stored in the character-string memory table are displayed. The display characters can be changed by changing the data stored in the characterstring memory table.
Numeric Values (numeral tables)
Lamps
Touch Switches
Numeric Keys
Bar Graphs
Marks
Numbers stored in the numeral table are displayed. The display numbers can be changed by changing the data stored in the numeral table. Hexadecimal values can also be displayed.
Lamps are displayed as square or round frames and indicate the operating status.
They are controlled by the Host and can be lit (reversed) or made flash (alternates normal with reversed displays).
Touch switches can be set anywhere on the screen. Touching the screen at a touch switch location can switch the display (display switch function) or notify the Host
(notification function). The touch switches can be lit or made flash by controlling from the Host in the same way as the lamps.
These are the touch switches used to input numeric values.
The bar graph extends and contracts in proportion to the data stored in the numeral table. A percentage value can also be displayed simultaneously.
Marks can be designed, created, and handled like characters by the user.
9
System Configuration Section 1-3
1-3 System Configuration
This section gives the basic configuration of a system which uses an NT20S. Refer to the manual for individual device for information on the equipment other than the
NT20S in the system.
Reference: Refer to Section 3-5 “Setting the Conditions of Communications with the Host by
Using the Memory Switches” on page 75 for the communication method and the conditions of communications between the NT20S and the Host. It is impossible to connect a computer to use a support tool and a Host together at the same time.
(except when using an NT20S-ST122-V1)
The principal optional devices for NT20S are as follows;
Replacement backlight NT20S-CFL01 (one white light)
Anti-glare sheet NT20M-KBA04 (five sheets in a pack)
Chemical-resistant cover (made of silicone rubber) NT20S-KBA01
1-3-1 Host Link/NT Link (1:1)/C200H direct Systems
D When using host link/NT link, RS-232C
RS-232C cable
(for host link)
(Max. 15 m)
D
When using C200H direct communication
I/O connection cable
Host (PC manufactured by OMRON, personal computer, etc.)
Controls NT20S as required while controlling machines and monitoring the production line.
Host link: C series, CQM1, CVM1/CV series PC, CjjH, CQM1,
C200HS, CVM1/CV series:
NT20S can be connected directly to the CPU unit.
NT link:
CVM1/CV series: NT20S can be used with version [-EV1] and subsequent versions.
Note that the C series requires a host link unit.
In the CVM1/CV series system, the NT20S can be connected also to the host link unit.
CQM1, CVM1/CV series PC
CQM1 can be used with CPU41/42/43/44-E.
C200HS can be used with CPU21/23/31/33-E.
CVM1/CV series can be used with [-EV1] CPU unit and subsequent versions.
RS-232C: Personal computer, FA computer
C200H direct communication:
C200H, C200HS, C200HX/HG/HE, CjjH PC
Support tool
NT20S
Gives displays of production line monitoring and instructions to the operation site and notifies the switch
ON/OFF status and numeric value inputs to the Host.
Computer (support tool)
Connected to NT20S as required and used to transfer the NT20S screens and make settings for the NT20S.
Computer: IBM PC/AT or compatible
Support tool: NT-ZA3AT-EV2
10
System Configuration Section 1-3
1-3-2 NT Link (1:N) Systems
When NT20S is connected to a PC in a 1:N connection, use an RS-232C cable and
RS-422/485 cables.
DM Setting to set for 1:N NT Link
C200HX Setup
Com 06 Port A
DM6655 = 5700
PLEASE NOTE:
The second digit signifies the max. # of PT Nodes for 1:N
NT Link.
e.g. 1= 2 PT Nodes
7= 8 PT Nodes
System will not accept a 0 (zero).
NT20S Setup
1:N NT Link
Unit #0
NT20S Setup
1:N NT Link
Unit #1
COM06
RS-422
Cable 1
RS-422
Cable 2
RS-232
NT-AL001 Dipswitch settings:
1 & 6 are ON.
Everything else is OFF.
NT-AL001
Cable 2
RS-232
Dipswitch settings:
1 & 6 are ON.
2 is ON - only if this is the last AL001 unit
Everything else is OFF.
Cable 3
RS-422
NT-AL001
RS-422
NT-AL001
RS-422
NT-AL001
RS-422
It is extremely important that you have this handshaking connection established, or communication will not exist.
NT-AL001
RS-232
NT20S
RS-232
Reference: When connecting the C200HX/HG/HE and an RS-232C/RS-422 converter unit, use a converter unit whose lot number is 15Y5 or later. Converter units of lot numbers previous to 15Y5 cannot be connected.
11
Direct Connection Function Section 1-4
1-4 Direct Connection Function
The communication method applied between the NT20S-ST121-EV3 and the PC is either a host link or NT link. To connect an NT20S-ST122-V1 and PC, the C200H direct communication function is used.
The following describes the “direct connection” function available with the
NT20S-ST121-EV3/ST122-V1, and communication with a PC.
➡ The NT20S-ST128 uses an RS-232C interface for communication with the PC
(refer to Section “Communications by RS-232C”).
The NT20S can be used to refer to the contents necessary for the display information or to allocate the bits and words used for storing the input data to any area in the PC. The NT20S can directly write and read such allocated bits and words so as to change the display elements, control the operating status, and notify the status.
This function is called the “direct connection function”. The NT20S-ST121-EV3/
ST122-V1 is designed exclusively for use with the direct connection.
The bits and words allocated by the direct connection function are called “allocated bit” and “allocated word” respectively.
This function allows to read the information to be displayed on the NT20S from the memory area in the PC and to write it to the memory table in the NT20S. Also, the data input on the NT20S can be written to the PC’s memory area. The NT20S screen status can be switched according to the PC’s memory area, and the
NT20S’s status data can be written to the PC’s memory area.
The NT20S-ST121-EV3 can only communicate with a PC that supports the host link or NT link function. The NT20S-ST122-V1 can only communicate with PCs that support the C200H direct communication function.
NT20S PC
DM area Internal relay area
Auxiliary relay area Timer/counter
12
Direct Connection Function Section 1-4
Features of the Direct Connection Function
S
The bits and words referring to operating status and work instruction information and those for storing input data can be freely allocated to almost any part of the
PC memory. Bits and words in the PC can be referenced from any memory table.
S The NT20S can directly refer to PC bit and word data so that it can be connected to a PC without changing the PC program which controls currently running production line.
S The area to control and notify the NT20S status, including display screens, backlighting or a flash control, and alarms and buzzers can be freely allocated to any part of the PC memory.
S Can be used irrespective of the operating mode of the PC.
The direct connection function allows the NT20S to directly read and write almost all bits and words in the PC and to automatically change the NT20S screen display.
This function can reduce the load on the PC so that the program development efficiency of the PC improves.
1-4-1 NT Link
The NT link uses the direct connection function and can execute high-speed communications with the CPU (with built-in host link) of the CPM1, CQM1, C200HS,
C200HX/HG/HE, or CVM1/CV series,
When using the NT20S in an NT link, two communications modes are possible: a single NT20S can be connected to one PC (1:1 NT link), or alternatively, up to eight
NT20S units can be connected to a single PC port (1:N NT link).
However, the 1:N connection NT link can be used with C200HX/HG/HE only. In the following sections, the NT link communication mode in general will be indicated by the term “NT link”, a 1:1 connection NT link will be indicated by “NT link (1:1)”, and a 1:N connection NT link will be indicated by “NT link (1:N)”.
Features of the NT Link
S High speed communications with specific types of PCs can be executed.
S Writing in units of bits to the PC memory area is possible.
This enables another bit of a word data to which a touch switch has been allocated to be used for other purpose (e.g., to allocate a lamp).
S
Can be used even while the PC is in the run mode. When using a host link, the
NT20S switches from the run mode to the monitor mode.
S
With NT link (1:N), up to eight NT20S units can be connected to a single PC port and used simultaneously.
S When using C200HX/HG/HE, by installing an expansion communication board in the option slot of the CPU unit, it is possible to connect up to three NT link (1:N) systems (comprising a total of 24 NT20S units). For details on communication boards, refer to the SYSMAC C200HW-COM01 to C200HW-COM06-E Communication Board OPERATION MANUAL (W304-E1-j).
The NT link is compatible with the host link. The NT20S screen data and the PC programs handled by the host link direct connection can be used with for the NT link as they are.
13
Direct Connection Function Section 1-4
1-4-2 C200H Direct Communication
C200H direct communication is a communication method that uses C200H,
C200HS, C200HX/HG/HE and CjjH I/O extensions.
The C200H direct communication function of the NT20S-ST122-V1 allows communication with a PC (C200H, C200HS, C200HX/HG/HE, CjjH) using the direct connection function.
Characteristics of C200H direct communication
C200H direct communication has the following characteristics.
S High-speed communication is possible through an I/O cable easily connected to the CPU unit.
S Data can be written to the PC memory area in bit units.
This means that the unused bits of words allocated to touch switches can be used for other applications (for example, lamp allocations).
Since the C200H direct communication function is compatible with the host link, the NT20S screen data and PC programs for host link direct connection can also be communicated by C200H direct communication without alteration.
Caution: With systems in which the user program operates in accordance with the PC cycle time, since there is some fluctuation in the PC cycle time, the system operation may not be consistent, and this should be born in mind when designing the system.
14
Communications with PC by Direct Connection Section 1-5
1-5 Communications with PC by Direct Connection
1-5-1 Functions of the Allocated Bits and Words
When using an NT20S-ST121-EV3 with the direct connection function (host link or
NT link), NT20S-ST122-V1 (C200H direct communication), the elements displayed on the NT20S and the NT20S status can be allocated to the bits and words of the PC. By changing the contents of the bits and words, the NT20S can be controlled by the PC. It is also possible to send data to the PC by pressing the touch switches on the NT20S.
S Controlling the NT20S by a PC
The following NT20S functions can be controlled by a PC.
Screens
Memory tables
: Display of designated screens, confirmation of screen numbers, etc.
: Writing to a memory table, copying from a memory table to another memory table, etc.
Lamps and touch switches : Display instructions, confirmation of display status, etc.
System control : Buzzer ON/OFF, backlight ON/OFF, and other
NT20S status
S Notifying from the NT20S to a PC
Data in the NT20S is sent to a PC when a touch switch is pressed. The following types of data are sent to a PC.
- NT20S status
- Touch switch status
- Numerical values input with touch switches by using the numeral setting function
- Changes in a memory table after copying between memory tables
Functions of Display Elements
S Lamps
Allocation destination: Bit
Lamp #1 (Bit 000100)
NT20S PC
Lit
Unlit
Switch 1: ON (Bit 000100)
Switch 2: OFF (Bit 000101)
Lamp #2 (Bit 000101)
PC’s bit status is displayed by the “Lamp” on the NT20S.
The lamp comes on (flashes) when the PC’s bit status (lamp bit) is ON (1), and goes off when it is OFF (0).
15
Communications with PC by Direct Connection
S
Touch switches
Allocation destination: Bit
Touch switch
12 Bit 009012
NT20S PC
Section 1-5
Bit 009012: ON
The lamp comes on (flashes) when the PC’s control bit is ON (1) and goes off when it is OFF (0). When the touch switch is pressed, the PC’s notification bit comes ON (1) or goes OFF (0).
S Numeral memory table
Allocation destination: Word
Numeral memory table 1 (TIM003)
NT20S PC
Numeral memory table 150 (0005CH)
Allocate numeral memory tables to arbitrary words in the PC. If word contents change when corresponding numeral memory table is displayed on the screen, the value on the screen will also change. Monitoring of words can also be made easily.
Reading and writing are executed so that the contents of allocated words and contents of numeral memory tables are always the same during display.
S Character-string memory table
Allocation destination: Word
NT20S PC
(“a”, “b”)
(“c”, “d”)
(“e”, “f”)
Character-string memory table 1
Allocated word number: 3ch
First word: DM0100
Allocate character-string memory tables to arbitrary words in the PC. If word contents change when corresponding character-string memory table is displayed on the screen, the value on the screen will also change. Messages can be displayed easily.
Reading and writing are executed so that the contents of allocated words and contents of character string memory tables are always the same during display.
16
Communications with PC by Direct Connection Section 1-5
Functions of the PT Status Control Area (PC to NT20S)
The “PT status control area” is used to control the NT20S status. When data is written to this area in the PC, the NT20S reads the contents and operates according to the contents.
[Example of the PT status control area application]
When data is written to the PT status control area, the NT20S will operate as given below.
Screen 3 display
NT20S
Continuous buzzer sound
Copy
Numeral memory table 50
Numeral memory table 7
PC
PT status control area
Screen switch setting
Memory table
Copy setting
PT status control bits
Functions of the PT Status Notify Area (NT20S to PC)
The “PT status notify area” is used to notify the changes of the NT20S status.
When a change is made in the NT20S status, the change is written to this area in the PC. By reading the data from the area, the NT20S status can be checked.
[Example of the PT status notify area application]
When a change is made in the NT20S status, such change will be notified to the PT status notify area as mentioned below.
12345678
NT20S PC
Numeral memory table 13
12345678
PT status notify area
Currently display screen
Content update memory table
PT status
Allocated word (numeral table 13)
12345678 Start
Start + 1
17
Communications by Rs-232C Section 1-6
1-6 Communications by RS-232C
This section gives a brief description of the NT20S control commands sent from the host through the RS-232C interface when the NT20S-ST128 is used.
Operation commands
Terminal commands
➡ For details of each of the commands sent through the RS-232C interface, refer to Section 6 “Using the RS-232C”.
Control of the NT20S by a Host is executed by two kinds of commands supported by the RS-232C interface which is built into the NT20S.
Operation commands are used to control the display and status of the running
NT20S as well as to notify information.
They are used for purposes such as screen display, data writing, and enquiries.
Notification of the NT20S operation contents to the Host.
Terminal commands are used to use the NT20S as a display terminal of the Host.
When the NT20S is used as a display terminal, it can display characters and figures in accordance with instructions given by the Host, independently of the screens registered to the NT20S.
These commands are also used if unexpected problems occur.
18
Before Operating Section 1-7
1-7 Before Operating
Follow the procedure given below to start the system of the NT20S.
NT20S Support tool Host
Check and change the Host settings.
S
For the host link, refer to page 36 and the manuals for the host link unit and peripheral tools.
S
For the NT link (1:1), refer to page 47.
S
For the NT link (1:N), refer to page 49.
S
When using C200H direct communication, no settings are required.
S
For the RS-232C, refer to page 63 and the manuals for the Host.
Connect to the NT20S.
Set the DIP switches.
(page 24)
Install to the operation panel.
(page 28)
Connect the power supply.
(page 29)
Connect to the Host.
S
(Host link: page 32)
S (NT link (1:1) : page 45)
S
(NT link (1:N) : page 49)
S
(C200H direct communication: page 58)
S
(RS-232C: page 63)
Check the settings and communications.
Install support tools to the computer.
Create the PC program.
Transfer the screen data.
(page 86)
Create the screens.
(refer to Section 4 and the manuals for the support tools)
Start operation.
Reference: As far as possible, use NT series support tool Ver.2.j as the support tool. For details on the support tools that can be used, see Appendix F “Function Restrictions Depending on the Support Tool” (page 255).
19
Before Operating
Equipment or Software
Support tools
PCs
Peripheral tools
Host link Unit
Section 1-7
Refer to the following manuals for the equipment and software.
Manual Title
NT-series Support Tool
Operation Manual
SYSMAC C20H/C28H/C40H/C60H Operation Manual
(Programming/RS-232C Interface)
SYSMAC C120/C500 User’s Manual (Programming)
SYSMAC C200H Operation Manual
SYSMAC C200HS Installation Guide
SYSMAC C200HS Operation Manual
SYSMAC C200HX/HG/HE Installation Guide
SYSMAC C200HX/HG/HE Operation Manual
SYSMAC C1000H/C2000H Operation Manual
SYSMAC CQM1 Operation Manual
SYSMAC CQM1-CPM1 Programming Manual
SYSMAC CV500/CV1000/CV2000 Operation Manual (Ladder)
£ For a PC of the CVM1 series, refer to the SYSMAC
CV500/CV1000/CV2000 User’s Manual.
SYSMAC C-series and CVM1 PCs SYSMAC Support Software
Operateon Manual:C-series PCs
SYSMAC C-series and CVM1 PCs SYSMAC Support Software
Operation Manual:CVMQ PCs
SYSMAC C Series Host Link Unit System Manual
SYSMAC CVM1/CV Series Host Link System Operation Manual
Manual Number
V028-E1-j
W176-E1-j
W060-E1-j
W130-E1-3j
W236-E1-j
W235-E1-2j
W302-E1-j
W303-E1-j
W140-E1-j
W226-E1-j
W228-E1-j
W202-E1-j
W248-E1-j
W249-E1-j
W143-E1-j
W205-E1-j
20
SECTION 2
Hardware Settings and Connections
This section describes the settings of the NT20S, connections to a Host, and other hardware settings.
2-1 Description of Parts and Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 Description of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-2 Operation Status DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-3 Setting the Communication Condition Setting Switches (NT20S-ST122-V1 Only)
2-2 Installation
. . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-2 Installation to the Operation Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2-3 Power Supply Connection
2-3 Connecting to the Support Tool
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Connection to a PC by the Host Link
2-4-1 Compatible PCs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4-2 Connecting the NT20S
2-4-3 PC Switch Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 Connection to a PC by the NT Link
2-5-1 Compatible PCs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-2 Connecting the NT20S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5-3 PC Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Connection to a PC by the NT Link (1:N) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-1 Compatible PCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-2 Connecting the NT20S Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6-3 PC Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7 Communicating with the PC Using C200H Direct Communication . . . . . . . . . . . . . . . . . . . . .
2-7-1 Applicable PC Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7-2 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-7-3 Switching the Power ON/OFF When Using C200H Direct Communication . . . . . . . . .
2-8 Host Connections by RS-232C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8-1 Host Computer Communication Settings
2-8-2 Connector Pin Arrangement
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
36
45
45
46
29
31
32
32
57
58
58
47
49
49
49
59
62
63
63
63
22
22
24
25
27
27
28
21
Description of Parts and Settings Section 2-1
2-1 Description of Parts and Settings
Before getting to the operation, confirm the names and functions of parts. Also set the DIP switches on the NT20S.
2-1-1 Description of Parts
Front View
POWER LED
Lit when the power is supplied.
RUN LED
Lit when the unit is in
RUN mode.
Display
An STN LCD screen with a backlight. The whole area of the screen is a touch panel which works as an input device.
Reference: The NT20S comes in two body colors.
S NT20S-ST12j: beige
S NT20S-ST12jB: black
22
Description of Parts and Settings
Rear View
Lid for backlight replacement
The backlight unit is installed behind this lid.
Warning label
Section 2-1
Contrast control
Use a fine flat-blade screwdriver. Clockwise turns will increase the brightness.
The NT20S-ST122-V1 has the support tool connector and communication condition setting switches under this cover.
Power input terminals
Connect the power to the
NT20S at these terminals.
Reset switch
The NT20S statuses are reset to the initial statuses by pressing this switch.
The screen data memory and the memory switch will retain the status even if this switch is pressed.
Host I/F tool connector
Connect the cable here from a PC/Host or support tool.
(On the NT20S-ST122-V1 this connector is for connection to a host only.)
23
Description of Parts and Settings Section 2-1
2-1-2 Operation Status DIP Switch Settings
Set the NT20S operation status with the DIP switches located in the bottom right corner on the rear side of the body.
24
Switch #
SW2-1
SW2-2
SW2-3
SW2-4
Function
Screen data forced initialize effective/ineffective
ON The NT20S will start in a special RUN mode in which the screen data memory is initialized. When it is started, the memory initialization menu will be displayed. For the initialization procedure, refer to Section 3-4 Initializing Memory (page 72).
[OFF] The NT20S will start in normal RUN mode.
Screen display language mode
[ON] Messages are displayed in English.
OFF
Switching to the System Menu enabled/disabled
ON The System Menu cannot be displayed. If an error occurs during a start-up, the System Menu will be automatically displayed.
However, “transfer mode” cannot be entered.
[OFF] The System Menu can be displayed.
Reserved for system use
ON
[OFF] Must always be OFF.
[ ] indicates factory setting.
CAUTION: If the DIP switch settings have been changed when the NT20S is powered, reset the power to the NT20S. The changes with the DIP switches become effective only after the power supply is reset.
Reference: S In addition to the DIP switches, set also the “communication type”, “host link baud rate”, etc. at the memory switches when host link/NT link is used.
When using the RS-232C interface, set the “RS-232C communication conditions” and other appropriate settings.
For these settings, refer to Section 3-5” Setting the Conditions of Communications with the Host by Using the Memory Switches” (page 75)
S It may be necessary to change the DIP switch settings after installing the NT20S in an operation panel. Bear this in mind when deciding the installation position.
During work at the panel, take care to ensure that no metal scraps enter the unit.
Description of Parts and Settings Section 2-1
2-1-3 Setting the Communication Condition Setting Switches
(NT20S-ST122-V1 Only)
When using the NT20S-ST122-V1, the communication conditions are set with the rotary switch (SW4) under the cover at the top right of the back of the terminal.
Rotary switch (SW3)
Connector for peripheral device
Setting the rotary switch The rotary switch is used to set the unit number.
Since the NT20S-ST122-V1 serves as a C200H special I/O unit, it requires a unit number setting. Make sure the set unit number does not duplicate the unit number set for any other special I/O unit.
SW3
8
7
9
6
0 1
2
3
5
4
(Factory setting)
25
Description of Parts and Settings Section 2-1
When using a C200H/C200HS, C200HX/HG/HE, the words indicated below are occupied according to the set unit number. However, since the NT20S-ST122-V1 executes processing using allocated bits and words, these words are not used for processing.
These words can be used as internal auxiliary relays.
Unit No.
0
1
2
5
6
3
4
7
8 ( £ )
9 ( £ )
Word No.
100 to 109
110 to 119
120 to 129
130 to 139
140 to 149
150 to 159
160 to 169
170 to 179
180 to 189
190 to 199
( £ ) Cannot be set with CjjH.
Reference: S If “8” or “9” is set as the unit number when using CjjH, a special I/O unit error will occur.
S When an NT20S-ST122-V1 is connected to a CjjH, I/O extension units cannot be connected. In other words, it is not possible to connect another special
I/O unit, so whatever unit number is set will not duplicate an existing one.
26
Installation Section 2-2
2-2 Installation
Install the NT20S to the operation panel and connect the power to the NT20S as described below.
2-2-1 Installation Environment
Observe the following points when installing the PT in an operation panel.
Caution: Do not install the NT20S at sites subject to the following conditions.
Otherwise, the product may malfunction.
S Severe temperature variations
S Temperatures or humidities outside the ranges stated in the specifications
S
High humidity, condensation
S
Splashing chemical agents
S
Severe oil splashing
S
Corrosive or flammable gases
S Strong vibrations or shocks
S Direct exposure to wind and rain (outdoor sites)
S Strong ultra-violet irradiation
Take adequate measures to ensure shielding if the NT20S is used at a location subject to any of the following conditions.
S
Static electricity, or noise from other equipment
S
Strong electric or magnetic fields
S
Nearby power cables
S Potential exposure to radioactivity
27
Installation Section 2-2
2-2-2 Installation to the Operation Panel
The NT20S can be flush mounted to an operation panel.
Use the panel fittings and tools included in the product package and follow the procedure below.
Caution: During work at the panel, take care to ensure that no metal scraps enter the unit.
Otherwise, the product may malfunction.
Note: The thickness of applicable operation panel is 1.6 mm to 4.8 mm. All fittings must be tightened uniformly to a torque of at least 0.5 to 0.6 N·cm in order to ensure water- and dust-resistance. The panel must not be soiled or warped, and must be able to support an installation that will remain secure and strong.
(1) Open a hole, shown below, in the panel and install the NT20S from the front side of the panel.
100.5
+0.5 mm
0 mm
178.5
+0.5 mm
0 mm
(2) Attach the panel fittings at four positions, shown below, on the rear side of the
NT20S.
Fit the hook of the fitting in the square hole in the body and tighten the screw with a Phillips head screwdriver while lightly pulling the fitting.
Note: In order to ensure adequate water and dustproof performance, tighten the four panel fittings uniformly and make sure there are no gaps between the fittings and the NT20S panel.
28
Installation Section 2-2
2-2-3 Power Supply Connection
Connect a 24 VDC power supply to the power input terminals.
Note: S Check the wiring carefully before turning on the power.
S Do not connect an AC power supply to the power supply terminals.
S
Use a DC power supply with low voltage fluctuation.
S
If complying with EC directives (low voltage directives), use a power supply with reinforced insulation.
Reference: When using an NT20S-ST122-V1, the NT20S must be started up before the host.
For details, refer to “Switching the Power ON/OFF When Using C200H Direct”
(page 62). When not using C200H direct communication, there are no restrictions on the order in which power supplies are switched ON and OFF.
24 VDC
© ¨
Breaker
Power Supply
24 VDC
S
Power supply
The specifications of the power supply that can be connected are as follows.
Item
Power supply voltage
Allowable power supply voltage fluctuation range
Power supply capacity
Value
24 VDC
20.4 VDC to 26.4 VDC
(24 VDC --15%, +10%)
10 W or over
29
Installation Section 2-2
S
Parts used for connection
Caution: For the connection to the power supply terminal block, twisted wires of 2 mm 2 or greater cross sectional area and M3.5 size crimp terminals must be used.
Tighten the screws on the terminal block to a torque of 0.8N·m.
Otherwise fire may occur.
7 mm or less
Fork type
7 mm or less
Round type
[Recommended terminals]
Maker
Japan Solderless Terminal MFG
Fuji Terminal
Nichifu Terminal
Type
(fork type)
2-YS3A
Type
(round type)
2-3.5
2-YAS3.5
V2-S3.5
2Y-3.5
2-3.5
Applicable Wire
(stranded wire)
2.00 to 2.63 mm 2
30
Connecting to the Support Tool Section 2-3
2-3 Connecting to the Support Tool
Connect the NT20S to a computer with an RS-232C cable to transfer the screen data created by using a support tool to the NT20S.
An NT20S-ST121-EV3/ST128 cannot be connected to both a personal computer running the support tool and a Host at the same time. Connect the personal computer only when transmitting screen data.
[NT20S-ST121-EV3/ST128]
[NT20S-ST122-V1]
S
Communication conditions
Communication conditions are set when a support tool is started.
Reference: To make a connector cable, refer to Appendix H Making the Cable for Connection to the Support Tool (page 268).
31
Connection to a PC by the Host Link Section 2-4
2-4 Connection to a PC by the Host Link
Connect the NT20S-ST121-EV3 to an OMRON PC by the host link method.
To connect the NT20S to a PC using the host link method, the NT20S “Comm.
Type” memory switch must be set to “Host Link”. For details on the “Comm. Type” setting, refer to “Selecting the Host Communication Method” (page 78).
2-4-1 Compatible PCs
Some models and series of OMRON PCs have the host link function built in. In the
C200HX/HG/HE series, there are CPU units that can support host link connections by installing an expansion communication board.
When making a connection, check the series and model of the PC to which the connection is being made, and the type of host link unit that is installed. The following is a list of the PCs that can be connected to the NT20S via a host link.
Units with Built-in Host Link Function
Host Link Unit CPU Unit
C20H/C28H/
C40H/C60H
CjjH
C120-LK201-V1
C200H-LK201-V1
C120
C200H
C500 (F)
C1000H
C2000 (H)
C200H
C200H-LK201-V1
C200H-LK201-V1
C200HS-CPU21-E
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU42-E
C200HS
C200HE
C series
C200H-LK201-V1
C200H-LK201-V1
C200HG-CPU43-E
C200HG-CPU63-E
C200HX-CPU44-E
C200HX-CPU64-E
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
C200HG
C200HX
C500-LK201-V1
C500-LK203
C500 (F)
C1000H (F)
C2000 (H)
CPM1-10CDR-j
CPM1-20CDR-j
CPM1-30CDR-j
CQM1-CPU21-E
CQM1-CPU41-E
CQM1-CPU42-E
CQM1-CPU43-E
CQM1-CPU44-E
CPM1
CQM1
32
Connection to a PC by the Host Link Section 2-4
CV series
CVM1 series
Units with Built-in Host Link Function
Host Link Unit CPU Unit
CV500-LK201
CV500-LK201
CV500-LK201
CV500-LK201
CV500-CPU01-EV1
CV1000-CPU01-EV1
CV2000-CPU01-EV1
CVM1-CPU01-EVj
CVM1-CPU11-EVj
CVM1-CPU21-EVj
CV500
CV1000
CV2000
CVM1
£ Connection is not possible to the CPU units of CVM1/CV series PCs that do not have the suffix “-EV j
”.
In the case of these CPU units, make the connection to NT20S by using a host link unit.
33
Connection to a PC by the Host Link Section 2-4
2-4-2 Connecting the NT20S
Refer to the illustrations below to select the appropriate cable for the unit connectors and connect the NT20S to the PC/Host.
To make a connector cable, refer to Appendix G Method for Making the Cable for
Connection to the Host (page 256).
Caution: S After connecting the communication cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
S The cable’s tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Connecting to a PC with a 25-pin Connector
Use a connector cable with a 25-pin connector on one end and a 9-pin connector on the other end (NT20S side) to connect the NT20S to a PC with a 25-pin connector.
NT20S
Host link unit/CPU unit
SYSMAC C series
PC, CVM1/CV series PC
9-pin connector
Host I/F connector
(RS-232C 9-pin type)
RS-232C connector cable
25-pin connector
Use the following recommended cables (OMRON);
Connector
Specification
Type
XW2Z-200S
XW2Z-500S
2m
5m
Cable Length
Applicable
Host Link Unit
C500-LK203
C500-LK201-V1
C120-LK201-V1
C200H-LK201
CV500-LK201
Connecting to a PC with a 9-pin Connector
Use a connector cable with a 9-pin connector on both ends to connect the NT20S to a PC with a 9-pin connector.
NT20S
Host link unit/CPU unit
SYSMAC C series
PC, CVM1/CV series PC
9-pin connector Host I/F connector
(RS-232C 9-pin type)
RS-232C connector cable
9-pin connector
Note: The connector cable wiring for the C series CPU unit (C jj
H) is different from that for the other PCs. For details, refer to Appendix G Method for Making the Cable for
Connection to the Host (page 256).
34
Connection to a PC by the Host Link Section 2-4
Connecting the NT20S to a CVM1/CV Series Host Link Unit
Two types of connectors are provided to CV500-LK201 host link unit. Both of these connector types can connect to the NT20S with an RS-232C connector cable. Select the connector cable which matches the connector type.
Communications port 1
(RS-232C)
Communications port 2
(RS-232C/
RS-422A)
I/O port selector switch
RS-232C
S To connect to communication port 1
This is a 25-pin RS-232C connector. Use a connector cable with a 25-pin connector on one end and a 9-pin connector on the other end (NT20S side).
S
To connect to communication port 2
This is a 9-pin RS-232C/RS-422A connector. Use a connector cable with a
9-pin connector on both ends.
Set the I/O port selector switch to the RS-232C side (upper side) to use this port.
RS-422A
Connecting the NT20S to a C Series CQM1 Unit
CQM1 can connect to the NT20S by the RS-232C method. Use an RS-232C 9-pin type connector cable.
S To connect to the RS-232C port
This is a 9-pin RS-232C connector. Use a connector cable with a 9-pin connector on both ends.
Connecting to C Series C200HX/HG/HE
When using C series C200HX/HG/HE models, the NT20S can be connected to the standard port of the CPU unit, or to ports A and B of the expansion communication board. Procure an RS-232C 9-pin type connection cable for the connection. For details on the specifications, installation method, etc., of the communication board used for the connection, refer to the “SYSMAC C200HX/HG/HE Installation
Guide” (W302-E1-j).
Connecting to C Series CPM1
The CPM1 is connected via an RS-232C adapter (type CPM1-CIF01).
Procure an RS-232C 9-pin type connection cable for the connection.
When a Connection Cable Longer Than 5 m is Required
When a connection cable longer than 5 m is required, it must be specially made.
However, note that the maximum transmission distance is 15 m. For details on the method for making the connection cable, refer to Appendix G
“Method for Making the Cable for Connection to the Host” (page 256).
35
Connection to a PC by the Host Link Section 2-4
When Long-Distance Transmission is Required
When transmission over a distance exceeding the RS-232C specification is required, it can be achieved by using an RS-232C/RS-422A converter unit (type NT-
AL001) to switch to RS-422A communication (RS-485 communication cannot be used).
For details, refer to “Connecting to an RS-232C/RS-422A Converter Unit (1:1)”
(page 269).
2-4-3 PC Switch Settings
When the NT20S and PC are connected to each other, set the conditions at the PC host link unit or the CPU as given in the table below.
The following is a general description of switch settings.
Refer to the manual for respective units for the details of the switch settings.
Item
I/O port
Baud rate
Transfer code
Parity
1-to-1/1-to-N
Instruction level
Unit #
Switch Setting
RS-232C
Set the same baud rate as the NT20S. ( £ 1)
ASCII 7 data bits, 2 stop bits
Even
1-to-N ( £ 2)
Level 1, 2, 3
00
Note: 1. Set the host link baud rate at 9600 bps or 19200 bps with the memory switch for “host link baud rate”. For the details, refer to “Selecting the Host Link Communication Speed” (page 79).
2. The 1-to-N setting enables BCC (Block Check Character).
It is not possible to connect more than one NT20S in a single host link.
When using CVM1/CV series, always set CPU execution processing (execution control 2) in the PC system settings to simultaneous processing.
36
Connection to a PC by the Host Link Section 2-4
Connecting to a Host Link Unit
Two types of host link units are available: a rack-mounting type and a CPUmounted type. The switch settings differ according to the type of host link unit. Set the switches according to the unit type.
S C200H rack-mounting type: C200H-LK201(-V1)
[Setting the front switches]
Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
S
Unit # (SW1, SW2)
Set these switches to “0”.
S
Instruction level, parity, and transfer code (SW4)
Set this switch to “2”.
5 2
S
Baud rate (SW3)
Set this switch to “5” to select 9600 bps.
Set this switch to “6” to select 19200 bps.
[Setting the rear switches]
CTS selector switch
External
0V (ON)
S 1-to-1/1-to-N selection (DIP switch)
Set #3 to “ON”.
S
CTS selection (selector switch)
Set this always to “0V” (ON).
S C500/C1000H/C2000(H) rack-mounting type: C500-LK201-V1
[Setting the front switches]
Host
Local
S
Mode control (key switch)
Set this to “host link”.
37
Connection to a PC by the Host Link
I/O port
RS-422A
RS-232C
Synchronization
Internal
External
[Setting the rear switches]
S
I/O port selection (selector switch)
Set this to “RS-232C”.
S
Unit # (DIP SW1)
Set SW1-1 to SW1-5 to “OFF” (“0”).
NO
S
Synchronization (selector switch)
Set this to “Internal”.
Termination resistance
OFF
ON
CTS
0V
External
NO
S
Baud rate (DIP SW2-1 to SW2-4)
Set these switches to “1010” to select 9600 bps.
Set these switches to “0010” to select 19200 bps.
(0 : OFF 1 : ON)
Section 2-4
S
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to “0” (1-to-N).
S
Instruction level (DIP SW2-7, SW2-8)
Set these switches to “1”.
(Levels 1, 2, and 3 are enabled.)
S
CTS selection (selector switch)
Set this always to “0V” (ON).
38
Connection to a PC by the Host Link Section 2-4
S
C500/C1000H/C2000(H) rack-mounting type: C500-LK203
[Setting the rear switches]
S
I/O port selection (selector switch)
Set this to “RS-232C”.
S
Unit #, parity, and transfer code (DIP SW1-1 to SW1-7)
Set SW1-1 to SW1-7 to “OFF” (“0”).
5V supply
ON
OFF
I/O port
RS-422A
RS-232C
Synchronization
Internal
External
Termination resistance
OFF
ON
CTS
0V
External
NO
NO
S
Synchronization (selector switch)
Set this to “Internal”.
S
Baud rate (DIP SW2-1 to SW2-4)
Set these switches to “1010” to select 9600 bps.
Set these switches to “0010” to select 19200 bps.
(0 : OFF 1 : ON)
S
1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to “0” (1-to-N).
S Instruction level (DIP SW2-7, SW2-8)
Set these switches to “1”.
(Levels 1, 2, and 3 are enabled.)
S
CTS selection (selector switch)
Set this always to “0V” (ON).
39
Connection to a PC by the Host Link
S
CPU-mounted type: C120-LK201-V1
[Setting the rear switches]
S
Unit #, parity, and transfer code (DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to “OFF” (“0”).
£ Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits.
Section 2-4
S
Baud rate (DIP SW2-1 to SW2-4)
Set these switches to “1010” to select 9600 bps.
Set these switches to “0010” to select 19200 bps.
(0 : OFF 1 : ON)
S 1-to-1/1-to-N selection (DIP SW2-6)
Set SW2-6 to “0” (1-to-N).
S Instruction level (DIP SW2-7, SW2-8)
Set these switches to “1”.
(Levels 1, 2, and 3 are enabled.)
S
CTS selection (DIP SW3-1 and SW3-2)
Set SW3-1 to “ON” (1) and SW3-2 to “OFF” (0). (Set this always to “0V”.)
S
Synchronization (DIP SW3-3 to SW3-6)
Set SW3-3, SW3-5, and SW3-6 to “ON“ (1), and
SW3-4 to “OFF” (0). (Set these to “Internal”.)
40
Connection to a PC by the Host Link Section 2-4
S
CVM1/CV series backplate mounted type: CV500-LK201
[Setting the front switches]
Set the operating conditions with the PC System Setting functions when a
CVM1/CV series host link unit is connected to the NT20S. The PC system settings can be made directly from the peripheral tool (LSS etc.) or the PC system setting information created with a peripheral tool can be transferred to the CPU.
The following describes the switch settings so as to enable the PC system settings. For the details of the PC system settings, refer to the SYSMAC CVM1/CV
Series Host Link User’s Manual (W205-E1-j).
Communications port 1
(RS-232C)
Communications port 2
(RS-232C/
RS-422A)
I/O port selector switch
RS-232C
RS-422A
S
Unit # (SW3 and SW4)
Set these switches to “0”.
S
I/O port selection (selector switch)
Set this to “RS-232C”.
S
CTS selection (DIP SW2 and SW3)
Set SW2 or SW3 to “ON”. (Set this always to “0V”.)
To use communication port 1, set SW2. To use communication port 2, set SW3.
S PC system setting (DIP SW1)
Set SW1 to “OFF”.
Communication is performed in accordance with the values set in the PC CPU special I/O unit system settings. The initial values in the system settings are as follows:
Baud rate :9600 bps
Communication mode
Parity
Stop bit
:Full duplex
:Even
:2 bits
Xon/Xoff control :Not performed
Data length :7 bits
41
Connection to a PC by the Host Link
Connecting to a CPU
Section 2-4
S
C-series CjjH, CVM1/CV-series (-EVj)
Set the operating conditions with the PC System Setting functions when a C jj
H, CVM1/CV-series host link unit is connected to the NT20S. The PC system settings can be made directly from the peripheral tool (LSS etc.) or the PC system setting information created with a peripheral tool can be transferred to the CPU.
The following describes the switch settings so as to enable the PC system settings. For the details of the PC system settings, refer to the “SYSMAC CjjH
User’s Manual (Programming)” (W176-E1-j) and the CVM1/CV500/CV1000/
CV2000 User’s Manual (W195-E1-j).
(1) C-series CjjH : C20H/C28H/C40H/C60H
No switch settings are required when connecting to a C-series CjjH CPU.
(2) CVM1/CV-series : CV500-CPU01-EV1
CV1000-CPU01-EV1
CV2000-CPU01-EV1
CVM1-CPU01-EVj
CVM1-CPU11-EVj
CVM1-CPU21-EVj
Only CVM1/CV series CPU units designated “-EV1” or higher can be connected.
When connecting to a CVM1/CV-series CPU, set the switches as given below.
[Setting the front switches]
I/O port selector switch
RS-232C
RS-422A
S
I/O port selection (selector switch)
Set this to “RS-232C”.
S
System setting (DIP SW4)
To effect the existing DIP switch settings, set SW4 to “ON”.
To effect the existing PC system settings, set SW4 to “OFF”.
Note: In the case of CPU units manufactured before June
1995 (lot No. “ jj 65”), the factory settings of the DIP switches do not agree with the factory settings for the
PC system settings.
S
The factory settings for the DIP switches are:
2400 bps, 1 stop bit, even parity, 7-bit data length.
S The factory settings for the PC system settings are:
9600 bps, 2 stop bits, even parity, 7-bit data length.
For CPU units manufactured from July 1995 (lot No.
“jj75”) onward, the factory settings for the DIP switches are also 9600 bps and 2 stop bits.
42
Connection to a PC by the Host Link Section 2-4
[Making the PC system settings]
The possible settings and existing settings which can be set by the PC system setting are as given below.
Item
Baud rate
Stop bit
Parity
Data length
Unit #
Possible Setting
1200/2400/4800/9600/19200 bps
1 or 2 stop bits
Even/odd/non-parity
ASCII 7 bits or JIS 8 bits
00 to 31
Existing Setting
9600 bps
2 stop bits
Even parity
ASCII 7 bits
Unit #00
S C-series C200HS, C200HX/HG/HE, CPM1, CQM1
Set the operating conditions to the PC system setting area when a C200HS
C200HX/HG/HE, CPM1 or CQM1 CPU is connected to the NT20S. The PC system setting area (data memory) can be directly accessed from the peripheral tool (LSS etc.).
The following describes the switch settings so as to enable the PC system settings. For the details of the operation with the PC system setting area, refer to the manual for the PC you are using.
[Switch setting] (C200HX/HG/HE, CQM1)
DIP switch settings
S
RS232C port communication condition settings
Set DIP switch 5 to OFF (right side) to enable the PC system settings.
ON ↔ OFF
[Switch setting] (CPM1)
Set the mode setting switch to the “HOST”
(upper) position.
CPM1-
CIF01 CPM1
[PC system setting area settings]
Write values to the PC system setting area (data memory) in accordance with the
CPU unit port used for connection to the NT20S.
S
When using the RS232 port of C200HX/HG/HE, CQM1
Channel #
DM6645
DM6648
Writing Value
0001
0303
0304
0000
Settings
Host link mode
Set the conditions with the contents of DM.
Data length: 7 bits, 2 stop bits, even parity, baud rate: 9600 bps.
Data length: 7 bits, 2 stop bits, even parity, baud rate: 19200 bps.
Unit No. 0
43
Connection to a PC by the Host Link Section 2-4
S
When using port A of C200HX/HG/HE
Channel # Writing Value
DM6555
DM6558
0001
0303
0304
0000
Settings
Host link mode
Set the conditions with the contents of DM.
Data length: 7 bits, 2 stop bits, even parity, baud rate: 9600 bps
Data length: 7 bits, 2 stop bits, even parity, baud rate: 19200 bps
Unit No. 0
S When using port B of C200HX/HG/HE
Channel # Writing Value
DM6550
DM6553
0001
0303
0304
0000
Settings
Host link mode
Set the conditions with the contents of DM.
Data length: 7 bits, 2 stop bits, even parity, baud rate: 9600 bps
Data length: 7 bits, 2 stop bits, even parity, baud rate: 19200 bps
Unit No. 0
S When using CPM1
Channel #
DM6650
Writing Value
0001
DM6653
0303
0304
0000
Settings
Host link mode
Set the conditions with the contents of DM.
Data length: 7 bits, 2 stop bits, even parity, baud rate: 9600 bps
Data length: 7 bits, 2 stop bits, even parity, baud rate: 19200 bps
Unit No. 0
44
Connection to a PC by the NT Link (1:1) Section 2-5
2-5 Connection to a PC by the NT Link (1:1)
Connect the NT20S-ST121-EV3 to an OMRON PC by the NT link method.
To connect the NT20S to a PC by the NT link (1:1) method, the NT20S memory switch for “host communication” must be set for the NT link. For the “host communication” setting, refer to “Selecting of the Host Communication Method”
(page 78).
2-5-1 Compatible PCs
Some models and series of OMRON PCs have the host link function built in. In the
C200HX/HG/HE series, there are CPU units that can support host link connections by installing an expansion communication board.
When making a connection, check the series and model of the PC to which the connection is being made, and the type of host link unit that is installed. The following is a list of the PCs that can be connected to the NT20S via a host link.
The compatible PCs are listed in the table below.
PC Series CPU Unit
CPU Units Connectable
Using an Expansion
Communication Board
Connectable to
CPM1-10CDR-
CPM1-20CDR-
CPM1-30CDRj j j
CQM1-CPU41-E
CQM1-CPU42-E
CQM1-CPU43-E
CQM1-CPU44-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
CPM1
CQM1
C200HS
C200HE-CPU42-E
C200HG-CPU43-E
C200HG-CPU63-E
C200HX-CPU44-E
C200HX-CPU64-E
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
C200HE
C200HG
C200HX
CV series
CVM1 series
CV500-CPU01-EV1
CV1000-CPU01-EV1
CV2000-CPU01-EV1
CVM1-CPU01-EV j
CVM1-CPU11-EV
CVM1-CPU21-EV j j
CV500
CV1000
CV2000
CVM1
45
Connection to a PC by the NT Link (1:1) Section 2-5
2-5-2 Connecting the NT20S
Refer to the illustrations below to select the appropriate cable for the unit connectors and connect the NT20S to the PC.
A host link connector cable can also be used. To make a connector cable, refer to
Appendix G Method for Making the Cable for Connection to the Host (page 256).
Caution: S After connecting the communication cable, always secure it with the screws.
Otherwise the cably may disconnect, causing operation to fail.
S The cable’s tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Use a connector cable with a 9-pin connector on both ends to connect the NT20S to a PC with a 9-pin connector.
NT20S CPU unit
SYSMAC C series
PC, CVM1/CV series PC
9-pin connector
Host I/F connector
(RS-232C 9-pin type)
RS-232C connector cable
9-pin connector
The following are the recommended cables (manufactured by OMRON).
Connector Specification Model
XW2Z-200T
XW2Z-500T
Cable Length
2m
5m
If a Cable Longer Than 5 m is Required
If a cable longer than 5 m is required, a connector cable will have to be made. Refer to Appendix F Method for Making the Cable for Connection to the Host (page 256).
The maximum transmission distance is 15 m.
When Long-Distance Transmission is Required
When transmission over a distance exceeding the RS-232C specification is required, it can be achieved by using an RS-232C/RS-422A converter unit (type NT-
AL001) to switch to RS-422A communication (RS-485 communication cannot be used).
For details, refer to “Connecting to an RS-232C/RS-422A Converter Unit (1:1)”
(page 269).
46
Connection to a PC by the NT Link (1:1) Section 2-5
2-5-3 PC Switch Settings
When the NT20S and PC are connected to each other, set the conditions at the PC
CPU so as to enable the NT link communications.
The following is a general description of switch settings.
S
C-series C200HS, C200HX/HG/HE, CPM1, CQM1
Set the operating conditions to the PC system setting area when a C200HS,
C200HX/HG/HE, CPM1 or CQM1 CPU is connected to the NT20S. The PC system setting area (data memory) can be directly accessed from the peripheral tool (LSS etc.).
The following describes the switch settings so as to enable the PC system settings. For the details of the operation with the PC system setting area, refer to the manual for the PC you are using.
[Switch setting] (C200HX/HG/HE, CQM1)
DIP switch settings
S
RS-232C port communication condition settings
Set DIP switch 5 to OFF (right side) to enable setting of the PC system settings.
ON ↔ OFF
[PC system setting area settings] (C200HX/HG/HE, CPM1, CQM1)
Write values to the PC system setting area (data memory) in accordance with the
CPU unit port used for connection to the NT20S.
PC Side
RS-232 port of
C200HX/HG/HE,
CQM1
Port A of C200HX/
HG/HE
Port B of C200HX/
HG/HE
CPM1
Channel #
DM6645
DM6555
DM6550
DM6650
Writing Value
4000
Settings
Use NT link (1:1)
47
Connection to a PC by the NT Link (1:1) Section 2-5
S
CVM1/CV-series (-EVj)
When connecting to a CVM1/CV-series (-EVj) CPU, set the switches as given below.
S
I/O port selection (selector switch)
Set this to “RS-232C”.
S NT link setting (DIP SW3)
Set SW3 to “ON”.
OFF ↔ ON
When using CVM1/CV series, always set CPU execution processing (execution control 2) in the PC system settings to simultaneous processing.
48
Connection to a PC by the NT Link (1:N) Section 2-6
2-6 Connection to a PC by the NT Link (1:N)
Connect the NT20S to an OMRON PC by the NT link method.
To connect the NT20S to a PC by the NT link (1:N) method, the communication conditions must be set with the memory switches.
S Setting NT link (1:N)
(Refer to “Selecting the Host Communication Method” (page 78))
S Setting the unit No. of the connected NT20S
(Selecting Unit Numbers (page 80))
2-6-1 Compatible PCs
The only OMRON PCs that can be connected in an NT link (1:N) are the C series
C200HX/HG/HE models. When making a connection, check the series and model of the PC to which the connection is being made, and the type of host link unit that is installed.
The following is a list of the PCs that can be connected to the NT20S via a host link
(1:N).
PC Series
C series
CPU Unit with Built-in
NT Link Function
C200HE-CPU42-E
C200HG-CPU43-E
C200HG-CPU63-E
C200HX-CPU44-E
C200HX-CPU64-E
CPU Units Connectable
Using an Expansion
Communication Board
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
Connectable to
C200HE
C200HG
C200HX
2-6-2 Connecting the NT20S Units
Referring to the illustrations below and using a cable appropriate for the CPU unit’s connector, connect the NT20S units and the PC using RS-232C/RS-422A converter units (type NT-AL001).
An NT link connection cable can be used as the RS-232C cable. For details on making a connection cable, refer to Appendix G “Method for Making the Cable for
Connection to the Host” (page 256).
Caution:
S
After connecting the communication cable, always secure it with the screws.
Otherwise the cably may disconnect, causing operation to fail.
S
The cable’s tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Reference: When connecting the C200HX/HG/HE and an RS-232C/RS-422A converter unit, use a converter unit whose lot number is 15Y5 or later. Converter units of lot numbers previous to 15Y5 cannot be connected.
49
Connection to a PC by the NT Link (1:N) Section 2-6
Connection Diagram
As shown in the figure below, connect multiple NT20S units to one PC. In an NT link (1:N), up to eight NT20S units can be connected to one PC port.
C200HX/HG/HE
OMRON PC
While controlling machinery and monitoring lines, controls the
NT20S units when necessary.
C200HX/HG/HE can be used.
RS-232C cable
(max. length: 2 m), or directly connected
RS-422A/485 cable
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
(Not required if the connection is made at the RS-422A/485 port.)
RS-422A/485 cable ( £ ) RS-422A/485 cable (
RS-232C cable
(max. length: 2 m)
£ )
( £ ) Total cable length: 500 m
RS-232C cable
(max. length: 2 m)
NT20S NT20S
(Up to eight NT20S units can be connected.)
[Maximum Number of NT20Ss Connectable to One Port]
The maximum numbers of NT20S units that can be connected to one port of each of the C200HX, -HG, and -HE CPU units are indicated below.
S C200HE :Up to 4 NT20S units per port (unit Nos. 0 to 3)
S C200HG, C200HX :Up to 8 NT20S units per port (unit Nos. 0 to 7)
50
Connection to a PC by the NT Link (1:N) Section 2-6
Converter Unit Connector Specifications
The terminal block specifications of the RS-232C/RS-422A converter unit are indicated here. For details on the method for making the connection cable, refer to
“Making the Cable” (page 265).
NT-AL001 RS-422A terminal block specifications
S Connected terminal block RS-422A terminal block (M3 screws)
S Electrical characteristics Conform to EIA RS-422A
S Signal direction Signal input and output is relative to the NT-AL001.
Terminal
Block Pin
No.
8
7
4
3
6
5
2
1
Request to send (−)
Request to send (+)
Receive data (−)
Receive data (+)
Send data (−)
Send data (+)
Signal ground
Functional ground
CSA
CSB
RDA
RDB
SDA
SDB
SG (GND)
Signal Direction
Input Output
○
○
○
○
−
−
○
○
−
−
£ The CSA and CSB signals are for special applications.
Terminal Screws and Crimp Terminals
The terminal screws are M3 screws. Use M3 size crimp terminals. Tighten the terminal screws with a torque of 0.4 N·m.
Note: During wiring, crimp terminals must be used for connections.
[Recommended crimp terminals]
Fork Type Round Type
6.2mm or less 6.2mm or less
Maker
Japan Solderless
Terminal MFG
Molex
Type
1.25-N3A (Fork)
Y1.25-3.5L (Fork)
Recommended Wire Size
AWG22 to 18 (0.3 to 0.75mm
2 )
51
Connection to a PC by the NT Link (1:N)
Wiring Method
Section 2-6
C200HX/HG/HE
For the connections between the PC and NT20S units, wire as shown below. The wiring method differs depending on the cables used for connection.
S
RS-422A connection
OMRON PC
While controlling machinery and monitoring lines, controls the
NT20S units when necessary.
C200H/HG/HE can be used.
RS-232C cable
(max. length: 2 m), or directly connected RS-422A cable
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-422A cable ( £ )
➀
RS-232C cable
(max. length: 2 m)
RS-422A cable ( £ )
➁
RS-232C cable
(max. length: 2 m)
RS-422A cable ( £ )
➁
RS-232C cable
(max. length: 2 m)
RS-422A cable ( £ )
➁
RS-232C cable
(max. length: 2 m)
NT20S NT20S NT20S NT20S
( £ ) Total cable length: 500 m
[RS-232C Cable Wiring]
PT, PC
RS-232C interface
Abbrev.
SD
RD
RS
CS
+5V
SG
Pin No.
Connector cover
2
3
4
5
6
9
The pin numbers are the numbers at the
NT20S. For the pin numbers at the PC, refer to the manual for the PC used.
Shielding wire
NT-AL001
4
5
2
3
6
9
Pin No.
Abbrev.
Connector cover
SD
RD
RS
CS
+5V
SG
: Only connected at PC
RS-232C interface
52
Connection to a PC by the NT Link (1:N)
[RS-422A Cable Wiring (
➀
)]
S RS-232C connection at the PC side
NT-AL001
RS-422A terminal block
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
Pin No.
1
5
6
3
4
Shielding wire
Section 2-6
NT-AL001
Pin No.
1
5
6
3
4
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
RS-422A terminal block
S RS-422A connection at the PC side
PC
RS-422A interface
Abbrev.
Connector cover
SDA
SDB
RDA
RDB
Shielding wire
NT-AL001
Pin No.
1
5
6
3
4
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
RS-422A terminal block
[RS-422A Cable Wiring (
➁
)]
NT-AL001
RS-422A terminal block
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
Pin No.
1
5
6
3
4
Shielding wire
NT-AL001
Pin No.
1
5
6
3
4
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
RS-422A terminal block
53
Connection to a PC by the NT Link (1:N)
S
RS-485 connection
C200HX/HG/HE
OMRON PC
While controlling machinery and monitoring lines, controls the
NT20S units when necessary.
C200H/HG/HE can be used.
RS-232C cable
(max. length: 2 m), or directly connected
RS-485 cable RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
Section 2-6
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C/RS-422A converter unit, type NT-AL001
RS-485 cable ( £ ) RS-485 cable ( £ ) RS-485 cable ( £ ) RS-485 cable ( £ )
RS-232C cable
(max. length: 2 m)
RS-232C cable
(max. length: 2 m)
RS-232C cable
(max. length: 2 m)
RS-232C cable
(max. length: 2 m)
NT20S NT20S NT20S NT20S
( £ ) Total cable length: 500m
[RS-232C Cable Wiring]
Same as for an RS-422A connection. Refer to “RS-422A connection” (page 52).
[RS-485 Cable Wiring]
S NT-AL001 to NT-AL001
NT-AL001
RS-422A terminal block
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
Pin No.
1
5
6
3
4
NT-AL001
Pin No.
1
5
6
3
4
Abbrev.
Functional ground
SDB
SDA
RDB
RDA
RS-422A terminal block
Shielding wire
S PC to NT-AL001
PC
RS-422A interface
Abbrev.
Connector cover
SDA
SDB
NT-AL001
Pin No.
1
3
4
Abbrev.
Connector cover
SDB
SDA
RS-422A terminal block
Shielding wire
54
Connection to a PC by the NT Link (1:N) Section 2-6
NT-AL001 Converter Unit DIP Switch Settings
The DIP switch settings to be made at an NT-AL001 used in the wiring depend on whether it is connected part way along the RS-422A/485 cable or is at the end of the RS-422A/485 cable.
S RS-422A connection, RS-232C at the PC side
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
C200HX/HG/HE
RS-232C/RS-422A converter unit, type NT-AL001
RS-422A cable ( £ )
RS-232C cable
(max. 2 m)
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
RS-422A cable ( £ )
RS-232C cable
(max. 2 m)
(End connection)
RS-232C/RS-422A converter unit, type NT-AL001
( £ ) Total cable length: 500 m
(End connection)
NT20S NT20S NT20S
S RS-485 connection, RS-232C at the PC side
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
C200HX/HG/HE
RS-232C/RS-422A converter unit, type NT-AL001
RS-485 cable ( £ )
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
(End connection)
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C cable
(max. 2 m)
RS-485 cable ( £ )
RS-232C cable
(max. 2 m)
( £ ) Total cable length: 500m
(End connection)
NT20S NT20S NT20S
55
Connection to a PC by the NT Link (1:N)
S
RS-422A connection, RS-422A at the PC side
Section 2-6
(End connection)
(Communication board)
C200HX/HG/HE
RS-422A cable ( £ )
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
RS-422A cable ( £ )
RS-232C cable
(max. 2 m)
(End connection)
RS-232C/RS-422A converter unit, type NT-AL001
( £ ) Total cable length: 500 m
RS-232C cable
(max. 2 m)
NT20S NT20S
RS-485 connection, RS-485 at the PC side
NT20S
(End connection)
(Communication board)
C200HX/HG/HE
RS-485 cable ( £ )
RS-232C/RS-422A converter unit, type NT-AL001
RS-232C cable
(max. 2 m)
NT20S NT20S
RS-232C/RS-422A converter unit, type NT-AL001
RS-485 cable ( £ )
RS-232C cable
(max. 2 m)
(End connection)
RS-232C/RS-422A converter unit, type NT-AL001
( £ ) Total cable length: 500 m
RS-232C cable
(max. 2 m)
NT20S
56
Connection to a PC by the NT Link (1:N) Section 2-6
2-6-3 PC Switch Settings
When the PC and NT20S units have been connected, set the switches at the CPU module at the PC side in order to enable communication using the NT link method.
S C series, C200HX/HG/HE
Write the communication conditions directly to the “PC system area” (data memory) using a peripheral tool (e.g., SYSMAC support software). For details on the operation for setting the “PC system area”, refer to the “SYSMAC C200HX/
HG/HE Installation Guide” (W302-E1-j).
[PC system setting area setting]
With C200HX/HG/HE, the setting area differs according to which port among the standard port of the CPU unit and the port of the expansion communication board is used for the connection.
Port
C200HX/HG/HE
RS-232C port
C200HX/HG/HE port A
C200HX/HG/HE port B
Channel #
DM6645
DM6555
DM6550
5
Witing Value j 00
Settings
Use NT link (1:N) j = highest unit No in the maximum number of connect able PTs (1 to 7). ( )
( £ ) When using C200HE, the PT unit No. range is 1 to 3.
57
Communicating with the PC Using C200H Direct Communication Section 2-7
2-7 Communicating with the PC Using C200H Direct Communication
Connect an NT20S-ST122-V1 and PC made by OMRON with an I/O cable.
2-7-1 Applicable PC Units
Before making the connection, check the series and model of the PC to which the connection is to be made. A list of the PCs that can be connected to an NT20S using C200H direct communication is presented below.
CPU Unit
C20H/C28HC40H/C60H
C200H-CPU01-E
C200H-CPU03-E
C200H-CPU11-E
C200H-CPU21-E
C200H-CPU23-E
C200H-CPU31-E
C200HS-CPU01-E
C200HS-CPU03-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU11-E
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
Model Name
CjjH
C200HE
Caution: With systems in which the user program operates in accordance with the PC cycle time, since there is some fluctuation in the PC cycle time, the system operation may not be consistent, and this should be born in mind when designing the system.
58
Communicating with the PC Using C200H Direct Communication Section 2-7
2-7-2 Connection Method
Connect the NT20S and PC.
The connection conditions are different for C200H/HS, C200HX/HG/HE and
CjjH.
Caution: S Always turn off the power at the PC and PT before connecting the C200H interface cable. Otherwise the system may operate unpredictably.
S
After connecting the communication cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
[I/O connection cable]
Use the following models of I/O connection cable.
For connecting
C200H/HS/HE/HG/HX
Model
C200H-CN311
NT20M-CNP711
C200H-CN711
NT20M-CNP221
C200H-CN221
NT20M-CNP521
C200H-CN521
NT20M-CNP131
C200H-CN131
C20H-CN312
NT20M-CNP712
C20H-CN712
NT20M-CNP222
C20H-CN222
Cable Length (L)
30 cm
70 cm
2 m
5 m
10 m
30 cm
70 cm
2 m
£ The C200H interface side connector of NT20M-CNPjjj has been downsized.
Caution:
S
Keep the total length of I/O cables used within 12 m (6 m for CjjH).
S The cable’s tensile load is 30 N. Do not subject it to loads greater than this.
Otherwise a discontinuity may occur, causing operation to fail.
Reference: If a C200H-CNjjj or C20H-CNjjj is used as the I/O connection cable, the connector will project beyond the bottom face of the NT20S.
If the I/O cable is passed through a hole or other opening, the hole or opening must be at least 53 mmφ. Removing the top cover reduces this requirement to 33 mmφ or larger. During installation, this cover must be replaced before securing the PT.
59
Communicating with the PC Using C200H Direct Communication Section 2-7
Connection to C200H/C200HS and C200HX/HG/HE
Connect the CPU unit or I/O extension unit with an I/O cable. The following restrictions apply when making this connection.
S
A maximum of one CPU unit and one I/O extension unit can be connected. Connection to two I/O extension units is not possible.
S Connection to a remote I/O slave station is not possible.
S There is only one C200H interface unit interface connector. This means that it is not possible to connect an NT20S between a CPU unit and an I/O extension unit.
It must be the final connection in the system.
CPU unit
I/O connection cable
(C200H-CNjj1)
I/O extension unit
Max. 1 unit
(Rear face of NT20S)
I/O extension cable
(NT20M-CNPjj1
/C200H-CNjj1)
Host interface connector
60
Communicating with the PC Using C200H Direct Communication
Connection to CjjH
Section 2-7
Connect the CPU unit with an I/O connection cable. The following restrictions apply when making this connection.
S
A maximum of one CPU unit can be connected.
S
Up to two I/O units can be connected for the one CPU unit, but I/O extension units cannot be connected.
S It is not possible to connect a CjjH I/O unit after the NT20S. It must be the final connection in the system.
CPU unit
I/O connection cable
(C20H-CNjj2)
I/O connection cable
(C20H-CNjj2)
I/O unit
I/O unit Max. 2 units
(Rear face of NT20S)
I/O connection cable
(NT20M-CNPjj2
/C20H-CNjj2)
Host interface connector
Note: When connecting a CjjH, always install a noise filter.
1. Insert the noise filter in the power supply line of the CjjH.
2. Make the distance between the noise filter and the CjjH as short as possible and separate it from the power supply line.
3. Install the noise filter case on the FG face.
4. Use a ZGB2202-01U(manufacutred by TDK) or equivalent as the noise filter.
+24V
1
2
IN
Noise filter
4
OUT
3
+
--
24V
61
Communicating with the PC Using C200H Direct Communication Section 2-7
2-7-3 Switching the Power ON/OFF When Using C200H Direct
Communication
The NT20S-ST122-V1 functions as an I/O extension unit of the PC. Use the following procedure to switch the power ON and OFF.
Power ON
Caution: Depending on the method used to switch the power ON and OFF, the entire system may stop. Follow the procedure described below to switch the power ON and
OFF.
Switch the power ON as follows:
[NT20S power ON] . . . .
“Connecting to Host” is displayed on the NT20S screen.
↓
[PC power ON] . . . . . . .
After “Connecting to Host” has been displayed for approximately 1 second, normal operation starts.
Note: S If the power to the PC is switched on first, the CPU of the PC is subjected to a system reset, making operations such as programming console impossible.
Then, when the power to the NT20S is switched on, “Connecting to Host” is displayed on the NT20S screen for approximately 1 second, after which normal operation starts.
S If the I/O connection cable is disconnected during system operation, an I/O bus error occurs at the PC side and operation stops. If this happens, connect the I/O connection cable and cancel the error.
Power OFF Switch the power OFF as follows:
[Switch the power supplies to the PC and NT20S off simultaneously]
. . . . . . . . . . . . . . . . . . . . .
The next time the power is switched ON, the NT20S displays the screen that was displayed when the power was switched OFF.
Note: S If the power to the NT20S is switched off first, the CPU of the PC is subjected to a system reset, making operations such as programming console impossible.
S Switch off the system temporarily before replacing the NT20S (when a fault occurs, for example). If the power to the NT20S only is switched off, the system stops immediately and this could cause an accident or damage machinery.
62
Host Connections by RS-232C Section 2-8
2-8 Host Connections by RS-232C
Connect NT20S-ST128 with an RS-232C Interface Unit installed to the host computer with an RS-232C cable.
RS-232C connection allows a single NT20S to be connected to the host.
A computer or other control device with a built-in RS-232C interface is a suitable host for connection to the NT20S.
2-8-1 Host Computer Communication Settings
Set the host communication conditions according to the following table.
Item
Baud rate
Data bits
Stop bits
Parity
Flow control
Setting
Set to the same baud rate as the NT20S: 2400, 4800, 9600,
19200
7 bits/8 bits
1 bit/2 bits
Even, Odd, None
RS/CS control
XON/XOFF control
None
Note: Set the same communication conditions at the NT20S and Host.
Refer to the appropriate instruction manuals for the method of setting the Host communication conditions.
Set to the maximum baud rate supported by both the NT20S and Host.
The communication condition settings of the NT20S-ST128 are set with the
RS-232C communication conditions memory switches. For details, refer to “Setting RS-232C Communication Conditions” on page 82.
2-8-2 Connector Pin Arrangement
The RS-232C connection between the NT20S and Host is described below.
NT20S Interface Unit The connector specification is described below.
Electrical characteristics: Conforms to EIA RS-232C specifications.
Signal direction: Signal input and output are relative to the host computer.
1 6
5 9
63
Host Connections by RS-232C
Connector pin #
2
3
4
5
6
9
Send data
Receive data
Request to send
Clear to send
+5 V output, max. 150 mA
Signal ground
£ Unlisted pins are not used.
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
+5V
SG (GND)
Section 2-8
Signal direction
NT20S ← → Host
→
←
→
←
→
—
Note: For cable parts and the wiring method, refer to APPENDIX G Method for Making the Cable for Connection to the Host (page 256).
Connecting to the Host Computer
Use a cable that is compatible with the RS-232C connector of the host to connect the NT20S and the host (see the example in the figure below).
In the example shown here, the cable connects the 9-pin connector of the NT20S and 25-pin connector of the host. If the host has a 9-pin RS-232C connector, use an RS-232C cable with 9-pin connectors at both ends.
NT20S
9-pin connector
Host Interface connector
(RS-232C, 9-pin type)
RS-232C cable
25-pin connector
Caution: S When making the connection, switch off the power to the NT20S and PC before disconnecting or connecting any connector.
S After connecting the communication cable, always secure it with the screws.
Otherwise the cable may disconnect, causing operation to fail.
Note: If using the +5 V supply of pin No.6, check first that the equipment that is to receive the supply has a current capacity no greater than 150 mA. The +5 V output of the
NT20S is +5 V DC 5%, max. 150 mA.
64
SECTION 3
System Menu Operation
This section describes the operation of the System Menu focusing on the procedure to start up the NT20S.
Functions which will be convenient to use the NT20S and those which are useful for the system maintenance are also explained here.
3-1 Operation Flow by the System Menu
3-2 Starting the NT20S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 Changing the System Settings etc.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Operation Modes and the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-1 System Menu and the Operation Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-2 Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-3 Operations with the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 Initializing Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-1 Initialization by Using the System Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-2 Initialization by Using the DIP Switch (Forced Initialization) . . . . . . . . . . . . . . . . . . . .
3-5 Setting the Conditions of Communications with the Host by Using the Memory Switches . . .
3-5-1 Selecting the Host Communication Method (NT20S-ST121-EV3 only) . . . . . . . . . . . .
3-5-2 Selecting the Host Link Communication Speed (NT20S-ST121-EV3 only) . . . . . . . . .
3-5-3 Selecting Unit Numbers (NT20S-ST121-EV3 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-5-4 Setting RS-232C Communication Conditions (NT20S-ST128) . . . . . . . . . . . . . . . . . . .
3-5-5 Selecting the Automatic Reset Function
3-6 Registering the Screen Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7 Starting the Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8 Various System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-1 Setting the Key Press Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-2 Using the Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-3 Backlight OFF Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-8-4 Support Tool Mode Setting (NT20S-ST121-EV3/ST122-V1 Only)
3-8-5 Lamp Bit Control (NT20S-ST128)
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9 System Maintenance
3-9-1 I/O Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9-2 Checking the PT Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-9-3 Checking the NT20S DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
68
69
70
72
72
66
67
67
80
82
84
86
90
74
75
78
79
99
99
107
109
91
91
92
94
95
97
65
Operation Flow by the System Menu Section 3-1
3-1 Operation Flow by the System Menu
Follow the procedure below when using the NT20S for the first time or when changing the system.
Create the Screen Data Create the screen data to be displayed on the NT20S by using a support tool.
For the screen data creation, refer to the “NT-series Support Tool Operation Manual” (V028-E1-j).
Start Up the NT20S (Display the System Menu.) (page 68)
Turn ON the power to the NT20S.
When no screen data has been registered, the “SYSTEM MENU” will be displayed. If the NT20S enters the RUN mode, press appropriate touch switches to display the System Menu.
Initializeing Memory (page 72)
Select a System Menu and initialize the NT20S unit memory.
Memory Switch Settings (page 75)
Select the System Menu and make settings such as the communication conditions for communication with the Host by setting the memory switches.
Registerung the Screen Data (page 86)
Connect a support tool to the NT20S and transfer the screen data from the support tool to the NT20S.
For the connection of a support tool, refer to Section 2-3 Connecting to the Support
Tool. (page 31)
Starting the Operation (page 90)
Connect to the PC/Host and start the operation.
System Maintenance (page 99)
If an error has occurred during operation, check the I/Os, settings, etc. referring to this guide.
66
Starting the NT20S Section 3-2
3-2 Starting the NT20S
When the NT20S is started, it will enter the RUN mode if system settings and screen data registration have been completed. If no screen data has been registered or the screen data are destroyed, the System Menu will be displayed.
Before turning ON the power, check the following DIP switch settings on the
NT20S.
S SW2-3 “Switch to the System Menu enabled/disabled” is set to OFF (enabled).
S
SW2-1 “Screen data forced initialize Yes/No” is set to No (ineffective).
For the DIP switch settings of the unit, refer to the “DIP switch settings” (page 24).
3-2-1 Changing the System Settings etc.
Follow the procedure below to change the system settings or screen data contents.
Procedure 1. Turn ON the power to the NT20S.
The NT20S will enter the RUN mode and the start-up screen will be displayed.
The start-up screen varies according to registered screen data.
2. Press appropriate touch switches to display the System Menu, and change system settings. For the method for calling the System Menu, refer to the “Operations with the System Menu” (page 70).
Note: If the NT20S has failed to start up normally; an error message is displayed or no screen is displayed, memory needs to be initialized.
For the memory initializing procedure, refer to Section 3-4 Initializing memory
(page 72).
67
Operation modes and the System Menu Section 3-3
3-3 Operation Modes and the System Menu
The NT20S operates in either “RUN”, “Transmit”, or “Maintenance” mode. The operation modes can be switched by using the System Menu.
3-3-1 System Menu and the Operation Modes
Select an operation mode by pressing the corresponding touch switch in the System Menu. The operation modes with respect to the System Menu are related to each other as shown below.
For the operations with the System Menu, refer to the “Operations with the System
Menu” (page 70).
RUN mode
The NT20S runs in this state. Controls from the
Host are enabled and various indications and
I/O operations are made.
Power ON
When system settings and screen data registration have been completed
To change system settings or screen data contents
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance mode
Transmit mode
Screen data and other data are transmitted between the NT20S and a support tool.
Maintenance mode
The NT20S maintenance operations such as memory initialize and setting check are executed.
68
Operation modes and the System Menu
3-3-2 Menu Tree
Section 3-3
The System Menu allows to effect various NT20S functions by using the touch switches. The NT20S’s functions with respect to the System Menu are related as shown below.
For the operations with the System Menu, refer to the “Operations with the System
Menu” (page 70).
SYSTEM MENU
Quit
Transmit Mode (page 86)
Maintenance Mode
NT20S-ST121-EV3/ST122-V1
COMM. CHECK MENU
Quit
Tool I/F (page 100)
MAINTENANCE MENU
Quit
PT Setting (page 107)
I/O Check
Init. Memory
Memory Switch
DIP-SW Status (page 109)
I/O CHECK MENU
Quit
LED Check (page 105)
Buzzer (page 104)
Touch Switch (page 99)
Data Memory (page 106)
LCD Display (page 103)
Comm. Check
INITIALIZE MEMORY MENU
Quit
Init. Screen (page 72)
NT20S-ST121-EV3
MEMORY SWITCH MENU
Comm. Type (page 78)
Key Press Sound (page 91)
Buzzer Sound (page 92)
Backlight Off (page 94)
Support Tool Mode (page 95)
Automatic Reset (page 84)
Baud Rate (page 79)
NT20S-ST122-V1
MEMORY SWITCH MENU
Key Press Sound (page 91)
Buzzer Sound (page 92)
Backlight Off (page 94)
Comm. Type (page 78)
Automatic Reset (page 84)
Support Tool Mode (page 95)
NT20S-ST128
MEMORY SWITCH MENU
Key Press Sound (page 91)
Buzzer Sound (page 92)
Backlight Off (page 94)
Automatic Reset (page 84)
Data Bits (page 82)
Stop Bits (page 82)
Parity Check (page 82)
Flow Control (page 82)
Baud Rate (page 82)
LMP Bit Control (page 97)
NT20S-ST128
COMM. CHECK MENU
Quit
Tool I/F (page 101)
RS-232C I/F (page 102)
First screen
Second screen
First screen
Second screen
69
Operation modes and the System Menu Section 3-3
3-3-3 Operations with the System Menu
The following gives the procedure to call the System Menu, select the menu items, and other operations with the System Menu.
Make sure that DIP SW2-3 “Switch to the System Menu enabled/disabled” is set to
OFF (enabled). If the setting is ON (disabled), the System Menu will not be displayed by following the procedure given below.
Displaying the System Menu Press appropriate touch switches to display the System Menu as mentioned below. The “RUN” LED goes off when the System Menu is displayed.
The NT20S display screen has four touch switches to display the System Menu in the four corners (about 8 mm x 8 mm size). Press any two of these switches at the same time to call the System Menu screen.
RUN mode
Press any two of these four corners at the same time.
[SYSTEM MENU]
Quit
Transmit Mode
Maintenance mode
Note that the touch switches used to call the System Menu are not displayed on the screen. If a touch switch displayed in a corner is pressed first, the touch switch will function and the System Menu will not be displayed. To successfully call the
System Menu, first press a corner where no touch key is displayed, and then, press any other corner regardless of the presence of a touch key.
If a screen has the touch switches registered at all of the four corners, it is impossible to call the System Menu from the screen.
A “system key” function can be assigned to a touch switch. Pressing the touch switch so assigned on the screen can easily display the System Menu. For the relationship between the system key and the touch switch, refer to the “System key functions” (page 139).
70
Operation modes and the System Menu
Selecting the Menu Items
Section 3-3
Press (touch) a menu item on the screen to select the item.
Menu items allow to make the ON/OFF selection or to call subsequent menu or screen.
Example 1
To call the “Maintenance mode menu” by pressing the “Maintenance Mode” on the
System Menu screen:
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
System Menu Items The System Menu items and the functions are as given below.
Menu Item Function
Quit
Transmit Mode
The System Menu screen is cleared and the NT20S will return to the RUN mode.
The Transmit Mode screen will be displayed to allow the transmission of the screen data between the NT20S and the support tool. For the transmission of the screen data, refer to Section 3-6
Registering the Screen Data (page 86).
Maintenance Mode The MAINTENANCE MENU will be displayed to allow the maintenance of the NT20S system.
Switching from the System Menu to the RUN mode
The NT20S will exit the System Menu and switch to the RUN mode in the cases mentioned below.
S
Selecting “Quit” in the System Menu.
S
The screen (touch switches) is not pressed for over 10 seconds.
71
Initializing Memory Section 3-4
3-4 Initializing Memory
If the NT20S is used for the first time or if the screen data is ruined and the NT20S cannot be normally started, the memory needs to be initialized.
The memory initialization is required in the cases mentioned below.
S
When the NT20S is used for the first time or when an error message indicating that the screen data is ruined etc. when the NT20S is started.
➡ Use the “Maintenance Mode” -- “Init. Memory” in the System Menu.
S When the NT20S has made a buzzer sound and the screen has disappeared during the start-up or operation.
➡ Use the NT20S DIP SW2-1 “Screen data forced initialize Yes/No”.
When an error has occurred, the error messages such as “Screen data corrupted” will be displayed. For the error messages displayed on the screen, refer to Section
7-2 “Responding to Displayed Error Messages” (page 237).
Note: Initializing the screen data memory will erase entire screen data registered in the
NT20S. Make sure that there are backup copies of the screen data on floppy disks before starting the initialization.
S
Data of the NT20S to be initialized
Screen data
System memory
Memory table
Mark data
Direct information (NT20S-ST121-EV3/ST122-V1)
3-4-1 Initialization by Using the System Menu
Initialize the screen data memory by following the procedure given below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
72
Initializing Memory
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Section 3-4
Select “Init. Memory”.
Select “Init. Screen”.
[ INITIALIZE MEMORY MENU ]
Quit
Init. Screen
Yes
No
Initialize Screen Memory?
Select “Yes”.
The screen data memory is initialized. During the initialization, the “Initializing” message will be displayed.
If “No” is selected, the memory initialization will be canceled and the NT20S returns to the
“operation mode”.
Example:
NT20S-ST121-EV3/ST122-V1
Direct information is also initialized. Set the direct information with the support tool.
No direct information is set!
Use the Support Tool to set the PT Control Area and PT Notify Area
After initialization of the screen data memory, the system enters the operation mode. At this point, nothing is displayed on the screen of the NT20S. Return to the
System Menu, select the Transmit Mode, and transmit the screen data from the support tool.
If the screen data cannot be initialized for any reason, the message “An Error Occur Initializing Memory” is displayed.
73
Initializing Memory Section 3-4
3-4-2 Initialization by Using the DIP Switch (Forced Initialization)
Note: Be sure to turn the power OFF before setting the NT20S DIP switch.
Set the DIP switch as follows to initialize the screen data memory.
Operation 1. Set DIP SW2-1 on the NT20S to ON and turn the power ON or reset the
NT20S.
Yes
Initialize Screen Memory?
Select “Yes”.
The screen data memory is initialized. During the initialization, the “Initializing” message will be displayed.
No
Initialized the
Screen Data Memory.
Turn OFF the DIP Switch 2-1 and push the Reset Switch, then return to RUN mode.
2. Turn the NT20S power to OFF.
3. Set NT20S DIP SW2-1 to OFF and turn the power ON.
Reference: S Selecting “No” will cancel the memory initialization. In either case, when changing the system settings or registering screen data, display the system menu after setting DIP switch SW2-1 to the OFF position while the NT20S power is OFF, then switching the power back ON.
S The NT20S DIP SW2-1 is used to set “Screen data forced initialize Yes/No”. Setting this to Yes selects “effective”, and No “ineffective”.
74
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
3-5 Setting the Conditions of Communications with the Host by Using the Memory Switches
The communications between the NT20S and a PC/Host are called the host communications.
Memory Switches
The NT20S models can be connected to the host using the following communication methods.
NT20S-ST121-EV3 :Host link or NT link (both direct connection)
NT20S-ST122-V1 :C200H direct communication (direct connection)
NT20S-ST128 :RS-232C communication (command control)
With NT20S-ST121-V3, the host link, NT link (1:1), and NT link (1:N) communication methods are set with memory switches. Other settings such as baud rate and automatic resetting of communication are also set with memory switches.
This section describes the communications condition settings by using the memory switches.
The NT20S has the memory areas used to store the PC connection method, communications conditions, system settings, etc. which can be used as the switches and called the “memory switches”. Since the memory switches use the flash memory, the stored data can be held even when the power supply is turned OFF.
Setting Functions and the Memory Switch Menu
The memory switches can be set easily by using the memory switch menu in the
System Menu.
The following settings can be made with the memory switches. Refer to the subsequent pages and Section 3-8 Various System Settings for the details of each setting and function.
[When using NT20S-ST121-EV3, host link/NT link] j
Host link method
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
MEMORY SW MENU
Automatic Reset
Baud Rate
(2/2)
No
9600bps
Quit
Page
WRT&
EXIT
75
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5 j
NT Link method (1:1)
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
NT Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
MEMORY SW MENU
Automatic Reset No
(2/2)
Quit
Page
WRT&
EXIT j NT Link method (1:N)
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
NT Link (1:N)
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
MEMORY SW MENU
Automatic Reset
Unit No.
No
7
(2/2)
Quit
Page
WRT&
EXIT
S Key Press Sound 3-8 Various System Settings (page 91)
S Buzzer Sound 3-8 Various System Settings (page 92)
S Backlight Off
S Comm. Type
3-8 Various System Settings (page 94)
Selecting the Host Communication Method (page 78)
S
Baud Rate Selecting the Host Link Communication Speed (page 79)
S
Automatic Reset Selecting the Automatic Reset Function (page 84)
S
Tool Mode
[NT20S-ST122-V1 C200H]
3-8 Various System Settings (page 95)
Key Sound
Buzzer Sound
Bk light Off
Comm. Type
Automatic Reset
Tool Mode
ON
ON
10min
C200H
Yes
NT20S
Quit
WRT&
EXIT
S Key Press Sound 3-8 Various System Settings (page 91)
S Buzzer Sound 3-8 Various System Settings (page 92)
S Backlight Off
S Comm. Type
3-8 Various System Settings (page 94)
Fixed as “C200H”
S Automatic Reset Selecting the Automatic Reset Function (page 84)
S Tool Mode 3-8 Various System Settings (page 95)
76
Setting the Conditions of Communications with the PC/Host with Memory Switches
[NT20S-ST128 RS-232C]
Key Press Sound ON
Buzzer Sound ON
Bk light Off 10min
Automatic Reset Yes
Quit
Page
WRT&
EXIT
Data Bits
Stop Bits
Parity Check
Flow Control
Baud Rate
LMP Bit Control
Section 3-5
8bits
1bit
Even
RS/CS
19200bps
Enable
Quit
Page
WRT&
EXIT
S
Key Press Sound 3-8 Various System Settings (page 91)
S Buzzer Sound
S Backlight Off
S Automatic Reset Selecting the Automatic Reset Function (page 84)
S Data Bits Setting RS-232C Communication Conditions
(page 82)
S
Stop Bits
3-8 Various System Settings (page 92)
3-8 Various System Settings (page 94)
S
S
Parity Check
Flow Control
Setting RS-232C Communication Conditions
(page 82)
Setting RS-232C Communication Conditions
(page 82)
Setting RS-232C Communication Conditions
(page 82)
S
Baud Rate Setting RS-232C Communication Conditions
(page 82)
S LMP Bit Control 3-8 Various System Settings (page 97)
77
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
3-5-1 Selecting the Host Communication Method (NT20S-ST121-EV3 only)
The NT20S-ST121-EV3 can be connected to a PC by the host link or the NT link.
Either link can be selected by setting the “Comm. Type” memory switch. The factory setting has been made to the “Host link”.
Select the host communication method by the menu operation from the System
Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Memory Switch”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Repeatedly pressing the
“Comm. Type” touch switch causes the setting to cycle through the options “Host link”,
“NT link”, and “NT Link 1:N”, in that order.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
Reference: The communication method must be selected according to the method that the connecting PC supports.
78
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
3-5-2 Selecting the Host Link Communication Speed
(NT20S-ST121-EV3 only)
When using the NT20S-ST121-EV3 with the host link, the baud rate of the communications with the PC can be set. Use the “Baud Rate” switch and select 9600 bps or 19200 bps.
The factory setting has been made at 9600 bps.
Select the baud rate of the communication with the PC by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Select “Page”.
If the host link is not selected, press the “Comm. Type” touch switch and select “Host link”.
MEMORY SW MENU
Automatic Reset
Baud Rate
(2/2)
No
9600bps
Quit
Page
Each time the “Baud Rate” touch switch is pressed, the setting option alternates between
“9600 bps” and “19200 bps”.
WRT&
EXIT
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
79
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
3-5-3 Selecting Unit Numbers (NT20S-ST121-EV3 only)
When using NT20S-ST121-EV3 with the NT link (1:N) communication method, set unit numbers.
When using NT link (1:N), unit numbers are used to identify each of the multiple
PTs connected to a single PC port. Set a different unit number for each of the PTs connected to the port.
The unit numbers that can be set differ in accordance with the type of host PC as follows.
C200HE :Unit Nos. 0 to 3
C200HG, C200HX :Unit Nos. 0 to 7
Set the unit numbers by following the menu operation from the System Menu described below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
NT Link 1:N
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Press the “Comm Type” touch switch to select “NT link (1:N)”.
Select “Page”.
80
Setting the Conditions of Communications with the PC/Host with Memory Switches
MEMORY SW MENU
Automatic Reset
Unit No.
No
7
(2/2)
Quit
Page
Section 3-5
Repeatedly pressing the “Unit
No.” touch switch cycles through the numbers that can be set.
WRT&
EXIT
To set and quit the menu, press the [WRT & EXIT] touch switch. To quit without setting, press [Quit]. The run mode will be established.
81
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
3-5-4 Setting RS-232C Communication Conditions (NT20S-ST128)
When using an NT20S-ST128 (using the RS-232C interface for communication with the host), set the following communication conditions.
S Data Bits
S
Stop Bits
S
Parity Check
S
Flow Control
S
Baud Rate
Set the same communication conditions at the host and the NT20S. You are recommended to set the highest baud rate that can be used by the host and NT20S.
The factory settings are as follows:
S Data Bits
S Stop Bits
S Parity Check
S Flow Control
8bits
2bits
Even
None
S Baud Rate 9600bps
Set the conditions of the communication with the Host by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
82
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
Select “Page down”.
Key Press Sound ON
Buzzer Sound
Bk light Off
Automatic Reset
ON
10min
Yes
Quit
Page
WRT&
EXIT
Data Bits
Stop Bits
Parity Check
Flow Control
Baud Rate
LMP Bit Control
8bits
1bit
Even
RS/CS
19200bps
Enable
Quit
Page
WRT&
EXIT
➡ The selected option displayed when the corresponding touch switch is pressed: the options for each switch are indicated below:
S Data Bits
S Stop Bits
7bits / 8bits
1bit / 2bits
S Parity Check
S Flow Control
None / Even / Odd
None / RS/CS / XON/XOFF
S Baud Rate 2400bps / 4800bps / 9600bps / 19200bps
S LMP Bit Control Enable / Disable
Note: Use the same condition settings as set for the host. It is recommended that the highest baud rate possible is selected for both the host and the NT20S.
➡ For details on lamp bit control, refer to Section 3-8 “Various System Settings” on page 91.
83
Setting the Conditions of Communications with the PC/Host with Memory Switches Section 3-5
3-5-5 Selecting the Automatic Reset Function
The “Automatic Reset” memory switch is used to set whether or not the communication is automatically reset after the occurrence of a communication error.
The factory setting has been made at “No”.
Select the baud rate of the communication with the PC by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Memory Switch”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Select “Page”.
84
Setting the Conditions of Communications with the PC/Host with Memory Switches
MEMORY SW MENU
Automatic Reset
Baud Rate
(2/2)
No
9600bps
Quit
Page
Section 3-5
Each time the “Automatic Reset” touch switch is pressed, the setting option “Yes” alternates with “No”.
(The figure to the left shows the
NT20S-ST121-EV3 screen.)
WRT&
EXIT
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
S “No”: If a communication error has occurred, corresponding error message is displayed and the operation stops.
S
“Yes”: If a communication error has occurred, corresponding error message will not be displayed and the operation will be automatically reset.
85
Registering the Screen Data Section 3-6
3-6 Registering the Screen Data
The screen data is created by using the support tool and registered to the NT20S screen data memory. This section describes the procedure to register the screen data to the NT20S. For the screen data creation and the support tool operation, refer to the NT-series Support Tool Operation Manual (V028-E1-1).
Reference: The screen data transmission speed can be increased by setting “Hi speed” for
“Communication Mode” on the Tool Settings screen of the support tool.
Unit of Screen Transmission -- Transmission in File Units
The NT20S uses several screens which are switched on its display. The screen data of one NT20S unit corresponds to the files created by using the support tool.
Select a file which contains the screen data to be transmitted when selecting the screen data to be transmitted to the NT20S so that the required screen data can be transmitted to the NT20S.
Screen data file
Screen 1
Screen 2
:
Screen N
Memory table
Mark data
System memory
(Direct information)
All screen data are transmitted by one operation.
NT20S
Screen 1
Screen 2
Screen N
:
Memory table
Mark data
System memory
(Direct information)
When the screen data is transmitted from the support tool to the NT20S, the screen data already existing in the NT20S will be erased.
If an error message and the System Menu are displayed immediately after the
NT20S has been started, the screen data memory needs to be initialized.
86
Registering the Screen Data Section 3-6
Data Transmission in Screen Units
The NT20S allows the transmission of data for specified screens. By selecting the screen number of the screen to be transmitted using the support tool, it is possible to transmit the required screen only to the NT20S (it is also possible to transmit multiple screens in a batch).
When changes have also been made to the memory tables or direct connection information, transmit the changed data to the NT20S too, for example by using transmission in screen units.
Support Tool
Screen 2
Only the required screen data is transmitted
NT20S
Screen 1
Screen 2
Screen N
:
Memory table
(Direct information)
Caution: When screen data transmission is in screen units, if there is data other than screen data, for example memory table or direct access changes, transmit this data also.
Reference: When screen data is transmitted to an NT20S, it is written into a free area of the memory without overwriting the existing data. This means that if data transmission in screen units is performed frequently, there will come a time when there is no more free area in the memory and further transmission is impossible. If this happens, transmit the data in file units to reorganize the contents of the NT20S memory.
Transmitting the Screen Data from the Support Tool
To transmit the screen data from the support tool to the NT20S, connect the
NT20S to the computer on which the support tool is being used, and follow the procedure below.
Reference: When the screen data transmission is attempted, the screen data memory in the
NT20S is automatically initialized before new screen data is transmitted. It is not necessary to initialize the screen data memory by using the menu before the screen data transmission.
The NT20S-ST121-EV3/ST128 uses the same connector for screen data transmission and connection to the Host. If this connector is currently connected to the host, disconnect the cable from it and connect it to the support tool (personal computer) before attempting screen data transmission.
87
Registering the Screen Data Section 3-6
Operation 1. Connect the NT20S to a PC in which the support tool has been installed and turn on the power to the NT20S.
2. Turn ON the computer and start up the support tool.
3. Enter the “Transmit Mode” by operating the menu of the NT20S as mentioned below.
Select “Transmit Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ TRANSMIT MODE ]
ABORT Tool Mode : NT20S
The transmit mode is established. When using an NT20S-
ST121-EV3/ST122-V1, the
“support tool mode” setting will be displayed on the bottom line of the screen, as shown in the figure to the left (nothing is displayed here on the screen of the
NT20S-ST128).
4. Select a screen data to be transmitted to the NT20S in the File Selection screen of the support tool, and press the Send key.
5. The NT20S will display the following screen when the screen data is being transmitted.
[ TRANSMIT MODE ]
ABORT
Tool → PT
Screen Data
0 KB
Tool Mode : NT20S
88
Registering the Screen Data Section 3-6
6. When the screen data transmission is completed, the support tool will display the following screen.
-- -- -- -- -- Help Message -- -- -- -- --
Data successfully transmitted
(Hit any key to continue.....)
7. Press any key on the support tool to return to the File Selection screen.
8. Pressing the ABORT touch switch in the Transmit Mode screen of the NT20S will exit the Transmit Mode and enter the RUN Mode.
Note: Press the “Abort” touch switch on the NT20S when the screen data transmission is completed. Unless this touch switch is pressed, the screen data will not be correctly registered. If the “Abort” touch switch is pressed during transmission, the screen data will not be correctly registered.
If screen data cannot be transmitted from the support tool, confirm normal communication between the NT20S and the support tool (Personal computer). Use the tool communication check function in the Maintenance Mode of the NT20S to check communication with the support tool. Refer to “Checking the Communications with the Support Tool” on page 100.
Precautions to be Observed During the Screen Data Transmission
When any of the following or a system error occurs during the screen data transmission, the transmitted screen data will not be registered correctly to the NT20S.
If an error message is displayed in the System Menu and the RUN Mode cannot be selected, the screen data memory needs to be initialized.
S The power to the NT20S is interrupted or reset.
S The power to the computer on which the support tool is running is interrupted or reset.
S The cable connecting the NT20S to the computer on which the support tool is running is interrupted or reset.
S
The “Abort” touch switch on the NT20S screen is pressed to end the transmission.
S
The ESC key on the support tool is pressed to end the transmission.
When the power to the NT20S is turned ON or reset, the screen data is checked.
However, if any of the above occurs during the screen data transmission, the screen may disappear and other unexpected problems may occur.
In the case of such problems, set DIP SW2-1 to ON to initialize the memory.
For the memory initialization by using the DIP switch, refer to the “Initialization by using the DIP switch” (page 74).
89
Starting the Operation Section 3-7
3-7 Starting the Operation
After completing the screen data transmission and setting the communication conditions, connect the NT20S to the Host and start operation.
Switching to the RUN mode Press the Quit touch switch in the System Menu. The start-up screen in the RUN mode will be displayed.
If the NT20S has failed to start correctly; e.g., the start-up screen is not displayed, an error message is displayed, or the screen is not displayed at all, refer to Section
7-2 “Responding to Displayed Error Messages” (page 237) and take appropriate action.
Reference: When using an NT20S-ST121-EV3/ST122-V1, the screen displayed on startup is the one specified in the screen switch setting of the PT status control area.
When using an NT20S-ST128, the startup screen is specified with the support tool when creating the screen data. If no startup screen is specified, screen No.1 becomes the startup screen. If no screen data is registered for the startup screen, the error message “Screen not registered” is displayed. For details on screen numbers, see 4-3 “Screen Display” (page 122).
Confirming the Communications between the NT20S and the PC/Host
When using the NT20S-ST128, use the RS-232C communication check function in the Maintenance Mode to confirm normal communication between the NT20S and the host. Refer to “Checking the Communications with the Host” on page 102.
When using the NT20-ST121-EV3/ST122-V1, run the Host program and check that the following operations are executed normally.
S Confirm that the NT20S screens switch according to the Host program execution.
If the screens do not switch correctly, check the connection between the NT20S and the Host and also check the settings.
Refer to Section 2 Hardware Settings and Connections.
S
Confirm that the information selected by the NT20S touch switches has been correctly sent to the PC by displaying the information of bits and words by using a peripheral tool (LSS etc.). If the information sent from the NT20S has not been correctly received by the PC, check the screen data settings (specifically the switch settings).
For the details of the screen data creation, refer to the NT-series Support Tool
Operation Manual (V028-E1-j).
90
Various System Settings Section 3-8
3-8 Various System Settings
The NT20S can set a variety of functions to the memory switches which are convenient during the operation. This section describes the memory switch settings related to the operation environment.
3-8-1 Setting the Key Press Sound
Whether or not the key press sound is given when the NT20S touch switch is pressed can be set with the memory switch.
The factory setting has been set to give the key press sound when the touch key is pressed.
Set the key press sound by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Memory Switch”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Each time the “Key Sound” touch switch is pressed, the setting option “ON” alternates with
“OFF”.
(The figure to the left shows the
NT20S-ST121-EV3 screen.)
91
Various System Settings Section 3-8
To set and quit the menu, press the [WRT & EXIT] touch switch. To quit without setting, press [Quit].
S
ON: The key press sound will be given for 0.2 second when a touch switch is pressed.
S OFF: The key press sound will not be given when a touch key is pressed.
3-8-2 Using the Buzzer
The NT20S can set a buzzer to indicate the occurrence of an emergency or an
NT20S error.
Setting the Buzzer Except when the buzzer has been set so as not to sound at all, the buzzer will sound when an error occurs. To set the buzzer to sound in other cases, the following two procedures can be used.
S Controlled by the Host
It is possible to control the NT20S from the Host to sound the buzzer during the operation.
Refer to Section 5-4 NT20S Status Control (page 191).
S Set the buzzer as a screen data attribute by using the support tool.
When creating the screen data by using the support tool, set the buzzer as a screen attribute so that the buzzer will sound. When the screen in which this attribute has been set is displayed, the NT20S will give the buzzer sound.
If the control by the Host and the display of the screen in which the buzzer attribute has been set are executed simultaneously, the priority is given to the control by the
Host. Refer to the NT-series Support Tool Operation Manual (V028-E1-j).
To Stop the Buzzer Sound The buzzer sound can be stopped by the following operation.
S
Control by the Host
S Switch the screen to a screen which does not have a buzzer attribute.
S Press the touch switch to which the buzzer stop attribute has been set.
Reference: If a buzzer stop attribute has been set to a touch switch created on the screen in which the buzzer attribute has been set, such touch switch can be used to stop the buzzer sound. For details on setting buzzer attributes for touch switches, see “Allocation of System Key Functions” (page 139).
92
Various System Settings Section 3-8
Types of the Buzzer Sounds The following buzzer sounds can be set.
S
Continuous sound: The buzzer continues to sound.
S Intermittent sound: The buzzer sounds intermittently at constant intervals.
Reference: If both the continuous buzzer and the intermittent buzzer are instructed by the
Host, the continuous buzzer will sound.
Setting the Buzzer Use the memory switches to set whether or not the buzzer sounds when the buzzer sound has been instructed by the Host or with a screen attribute or when an error has occurred.
The factory setting is “ON”, which means that the buzzer will sound when a command is received from the host, when a screen for which the buzzer attribute is set is displayed, and when errors occur.
Set the buzzer sound by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Memory Switch”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Repeatedly pressing the “Buzzer Sound” touch switch cycles through the setting options
“ON”, “ERR ON”, and “OFF”, in that order.
(The figure to the left shows the
NT20S-ST121-EV3 screen.)
93
Various System Settings Section 3-8
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
S
OFF: The buzzer will not sound at all during the operation.
S
When “ON” is set, the buzzer will sound when a command is received from the host, when a screen for which the buzzer attribute is set is displayed, and when errors occur.
S
When “ERR ON” has been set, the buzzer will sound only when an error has occurred.
Reference: The buzzer will sound when “Buzzer check” is selected in the Maintenance Mode regardless of the buzzer setting.
3-8-3 Backlight OFF Function
The NT20S has a function that turns off the backlight of the LCD panel to maximize its service life if no operation is performed for a certain period of time.
Turning on the Backlight When a touch switch on the NT20S is pressed or a screen is switched or redisplayed by the PC when the backlight is off by the backlight off function, the backlight will turn on. Any changes of numeric values or characters displayed on the screen will not effect the backlight to turn on again.
Setting the Backlight OFF Function
Use the memory switches to set whether or not the backlight off function is used and the length of time to turn off the backlight.
The factory setting has been made so as to turn off the backlight if no operation has been performed for 10 minutes.
Set the backlight off function by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Memory Switch”.
94
Various System Settings Section 3-8
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Repeatedly pressing the “BK light Off” touch switch cycles through the setting options “10 min”, 1 hour, and None, in that order.
(The figure to the left shows the
NT20S-ST121-V2 screen.)
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
S None: The backlight off function is not used. As long as no operation is performed, the same screen remains to be displayed.
S 10 minutes: The backlight will be turned off when no operation has been performed for 10 minutes.
S 1 hour: The backlight will be turned off when no operation has been performed for 1 hour.
Caution: Do not press touch switches carelessly while the backlight is off or while nothing is displayed on the screen.
Otherwise the system may operate unpredictably.
Only press touch switches after confirming system safety.
Correct Use: Continuous display of the same pattern for an extended time (as a guide, about 1 hour) will lead to the formation of an afterimage.
In order to prevent this, either use the screen saver function or periodically switch screens.
3-8-4 Support Tool Mode Setting (NT20S-ST121-EV3/ST122-V1 Only)
By setting “Tool Mode” to “NT20M”, the NT20M-ST121-EV3/ST122-V1 can be used in the same way as the conventional NT20M, and it becomes possible to use the NT20M/NT2000M/NT600M support tool (Ver.4.j).
However, the following restrictions apply when “NT20M” is set:
S
Ver.5 of the direct connection function cannot be used.
S
The PT type setting must be “NT20M”.
S High-speed data transfer with the support tool is not possible.
S It is not possible to transfer the direct information alone.
S When screen data transmission is in screen units, simultaneous transmission of multiple screens is not possible. An attempt to transmit multiple screens may destroy the screen data.
S When screen data transmission is in screen units, transmission with verification set is not possible.
S The image data memory must be initialized before starting transfer in file units.
S Screen data for RS-232C communication cannot be used.
95
Various System Settings Section 3-8
Set the support tool mode by the menu operation from the system menu shown below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “Memory Switch”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
MEMORY SW MENU
Comm. Type
Key Sound
Buzzer Sound
Bk light Off
Tool Mode
(1/2)
Host Link
OFF
OFF
None
NT20M
Quit
Page
WRT&
EXIT
Each time the “Tool Mode” touch switch is pressed, the setting option alternates between
“NT20S” and “NT20M”.
(The figure to the left shows the
NT20S-ST121-EV3 screen.)
To quit after setting the selected item, press the WRT & EXIT touch switch. To quit without setting, press the Quit touch switch. The NT20S will enter the RUN mode.
S When “NT20M” is set, the NT20M compatible mode is established and the terminal can be used as an NT20M.
S When “NT20S” is set, the terminal can be used as an NT20S.
96
Various System Settings Section 3-8
3-8-5 Lamp Bit Control (NT20S-ST128)
When using the NT20S-ST128 (using the RS-232C interface for communication with the host), you can select whether lamp statuses are controlled by bit designation or not.
The factory setting for this function is Enable (lamps numbered 0 to 31 controlled by bits).
Set the lamp bit control function by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Key Press Sound ON
Buzzer Sound
Bk light Off
Automatic Reset
ON
10min
Yes
Select “Memory Switch”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Quit
Page
Select “Page down”.
WRT&
EXIT
97
Various System Settings
Data Bits
Stop Bits
Parity Check
Flow Control
Baud Rate
LMP Bit Control
8bits
1bit
Even
RS/CS
19200bps
Enable
Quit
Page
WRT&
EXIT
Section 3-8
Each time the “LMP Bit Control” touch switch is pressed, the setting option “Enable” alternates with “Disable”.
To set and quit the menu, press the [WRT&EXIT] touch switch. To quit without setting, press [Quit].
S When “Disable” is set, the control of lamp display statuses by bits is not possible.
The lamps numbered 0 to 31 can be controlled only by specifying lamp numbers.
S
When “Enable” is set, lamp control by bits is possible. This means that the lamps numbered 0 to 31 can be controlled by specifying either lamp numbers or bits.
However, it is not possible to make “lit”/“flashing” status selections by specifying lamp numbers: the selection made when the screen data was created remains effective.
98
System Maintenance Section 3-9
3-9 System Maintenance
The NT20S has the self maintenance functions such as I/O check and setting status check.
3-9-1 I/O Check
The I/O operations for the following items of the NT20S are checked by the I/O check function.
S Touch Switch
S Communications with the support tool
S Communications with the Host (NT20S-ST128 RS-232C only)
S
LCD
S
LED Check
S
The Screen Data Memory
S
Buzzer
Checking the Touch Switches
Execute a touch switch check by the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “I/O Check”.
Select “Touch Switch”.
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
99
System Maintenance Section 3-9
A panel of 6-row x 12-column touch switches, each switch sized 1 x 1 cm, will be displayed.
“EXIT” switch to exit the touch switch check menu.
The touch switch is normal if it is highlighted while it is pressed.
S Press a touch switch on the screen. If the touch switch is highlighted while it is pressed, the touch switch is normally functioning.
S
When the check is finished, press the EXIT touch switch. The I/O check menu will be redisplayed.
Reference: If memory switch setting for the key press sound has been made for ON, the key press sound will be made when a touch switch is pressed.
The statuses of touch switches pressed during an I/O check are not notified to the host.
Checking the Communications with the Support Tool
Execute a NT20S-to-support tool communication check by the menu operation from the System Menu as mentioned below.
The NT20S-ST121-EV3/ST128 uses the same connector for connection to the support tool and connection to the Host. If this connector is currently connected to the host, disconnect the cable from it and connect it to the support tool (personal computer) before attempting screen data transmission.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “I/O Check”.
100
System Maintenance
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
Section 3-9
Select “Comm. Check”.
Select “Tool I/F”.
[ COMM. CHECK MENU ]
Quit
Tool I/F
[ TOOL I/F INPUT CHECK ]
The data received from the connected support tool are displayed in hexadecimal numbers.
EXIT
When the check is finished, press the Exit touch switch. The NT20S will enter the
I/O CHECK MENU.
101
System Maintenance Section 3-9
Checking the Communications with the Host (NT20S-ST128)
Execute a NT20S-to-Host communication check by the menu operation from the
System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “I/O Check”.
Select “Comm. Check”.
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
Select “RS-232C I/F”.
[ COMM. CHECK MENU ]
Quit
Tool I/F
RS-232C I/F
102
System Maintenance
[ RS-232C I/F INPUT CHECK ]
Section 3-9
The data received from the connected Host are displayed in hexadecimal numbers.
Checking the LCD
EXIT
When the check is finished, press the EXIT touch switch. The NT20S will enter the
RUN mode.
Check the NT20S LCD by using the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “I/O Check”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “LCD Display”.
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
S The LCD displays dots (segments of the screen) line by line beginning with the top left corner. If all the dots are displayed normally, the NT20S will enter the I/O
CHECK MENU after all the dots have been turned off.
S To cancel the LCD indication check, press any touch switch (anywhere) on the screen. The I/O Check Menu will be redisplayed.
103
System Maintenance
Checking the Buzzer
Section 3-9
Check the NT20S buzzer by using the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “I/O Check”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Buzzer”.
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
S
If the buzzer function is normal, the continuous buzzer sound will be made.
S To stop the buzzer, press “EXIT” touch switch in the buzzer check screen. The
NT20S will enter the I/O CHECK MENU.
Reference: Though memory switch setting for the buzzer has been made for OFF, the buzzer will sound when the buzzer check is executed.
104
System Maintenance
Checking the LED
Section 3-9
Check the LED by using the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “I/O Check”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “LED Check”.
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
The “RUN” LED on the front face of the NT20S will flash. The “POWER” LED remains lit.
S To quit the LED check, press the “EXIT” touch switch. The NT20S will enter the
I/O CHECK MENU.
105
System Maintenance Section 3-9
Checking the Screen Memory
Check the screen memory by using the menu operation from the System Menu as mentioned below.
Reference: When the screen data memory is checked, the memory is initialized and all the screen data is lost. Check that the screen data has been backed up using the support tool before executing a screen data memory check.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
Select “I/O Check”.
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “Data Memory”.
[ I/O CHECK MENU ]
Quit
LED Check
Buzzer
Touch Switch
Data Memory
LCD Display
Comm. Check
[ SCREEN DATA MEMORY CHECK ]
Caution!!
This test will destroy the Screen Data.
CANCEL
TEST
START
Press “TEST START”.
Pressing “Cancel” will cancel the memory check.
106
System Maintenance Section 3-9
The screen memory check will start.
While the screen memory is checked, the “Memory checking...” message will be displayed.
S
If the memory check has been normally completed, the “Memory is OK” message will be displayed.
S To quit the memory check, press the “Cancel” touch switch. The NT20S will enter the I/O CHECK MENU.
S
If the “Memory error!!” message is displayed, the screen data memory may have been used up to its service life or there may be a hardware fault. In that case, initialize the screen data memory and check the memory again. If the same error message is displayed again, consult the OMRON Service Center.
3-9-2 Checking the PT Setting
Display the NT20S settings by using the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “PT Setting”.
107
System Maintenance
[NT20S-ST121-EV3]
(Host link)
[ PT SETTING ]
PT Control Area
PT Notify Area
Comm. Type
Baud Rate
DM0000
DM0010
Host Link
9600bps
EXIT
(NT Link (1:N))
[ PT SETTING ]
PT Control Area
PT Notify Area
Comm. Type
Unit No.
DM0000
DM0010
NT Link 1:N
7
EXIT
EXIT
(NT Link (1:1))
[ PT SETTING ]
PT Control Area
PT Notify Area
Comm. Type
DM0000
DM0010
NT Link
Section 3-9
[NT20S-ST122-V1 (C200H direct communication)]
[ PT SETTING ]
PT Control Area
PT Notify Area
Comm. Type
Unit No.
DM0100
DM0200
C200H
0
EXIT
£ If no unit number is set at the PC, “0” will be displayed.
[NT20S-ST128 (RS-232C)]
[ PT SETTING ]
Data Bits
Stop Bits
Parity Check
Flow Control
Baud Rate
EXIT
8bits
1bit
Even
RS/CS
19200bps
S
The current PT settings will be displayed.
S
Pressing the “EXIT” touch switch will exit the PT settings display, and the NT20S will return to the RUN Mode.
108
System Maintenance Section 3-9
3-9-3 Checking the NT20S DIP Switch Settings
Display the NT20S DIP switch settings by using the menu operation from the System Menu as mentioned below.
Select “Maintenance Mode”.
[ SYSTEM MENU ]
Quit
Transmit Mode
Maintenance Mode
[ MAINTENANCE MENU ]
Quit
PT Setting
I/O Check
Init. Memory
Memory Switch
DIP-SW Status
Select “DIP-SW Status”.
[ DIP-SWITCH STATUS ]
1. Forced Init.
2. Message Mode
3. Mode Change
4. Reserved
No
English
Enable
OFF
1 2 3 4
EXIT
[SW2]
ON
OFF
S
The NT20S DIP switch statuses are displayed.
S
Pressing the EXIT touch switch clears the DIP switch status display from the screen and causes the NT20S to enter the RUN mode.
Note: If the DIP switch settings have been changed when the NT20S is powered, reset the power to the NT20S. The changes with the DIP switches become effective only after the power supply is reset.
109
110
SECTION 4
NT20S Functions and Operation
This section describes the functions of the NT20S.
4-1 Creating and Transmitting Screen Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-1 Setting the support tool for use with the NT20S
4-1-2 Creating Screen Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Outline of Functions
4-2-1 NT20S Screen
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-2 Characters and Figures Which can be Displayed
4-2-3 Communications with the Host
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Screen Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Classification of Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-2 Screen Attributes
4-4 Memory Tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-1 Character-String Memory Table
4-4-2 Numeral Memory Table
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 Bar Graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5-1 Bar Graph Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-1 Lamp Functions
4-7 Touch Switches
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-1 Functions of Touch Switches
4-7-2 Screen Switching Function
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-7-3 System Key Functions
4-8 Numeral Setting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8-1 The Numeral Setting Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8-2 Types of Numeral Setting
4-8-3 Creating Numeric Keys
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8-4 Using Numeric Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-8-5 Using The Thumbwheel Type of Numeral Setting (Ver.5 Direct Connection Only)
4-8-6 Settings for Numeral Settings
. . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122
122
125
126
126
127
129
129
133
133
136
137
138
139
140
140
142
143
145
147
148
112
112
113
118
118
119
120
111
Creating and Transmitting Screen Data Section 4-1
4-1 Creating and Transmitting Screen Data
This section describes briefly the support tool settings required for creating screen data and the screen data creation procedure.
Reference: For the details of the support tool and screen data creation, refer to the “NT-series
Support Tool Operation Manual” (V028-E1-j).
4-1-1 Setting the support tool for use with the NT20S
To create the screen data for the NT20S, make settings with the support tool for use with the NT20S.
Select “Tool Settings”.
112
To create the NT20S screen data, make settings in the “Tool Settings” screen as follows.
Creating and Transmitting Screen Data Section 4-1
NT20S-ST121-EV3 (Host link/NT link), NT20S-ST122-V1 (C200H direct communication)
PT Setting
Memory Size
: 20S
: 96 KB
Direct setting : Ver.4 or Ver.5
Direct Macn Type: OMRON
NT20S-ST128 (RS-232C)
PT Setting
Memory Size
Direct setting
: NT20S
: 96 KB
: None
Direct Macn Type: OMRON
4-1-2 Creating Screen Data
Screen Data Creation Method
The screen data is created by using the support tool. The support tool registers the screen data used with one NT20S to one file.
Screen data can be created by one of the following three methods:
S creating a new file;
S editing an existing file;
S reading and editing selected screens from an existing file.
Screen Data Creation Procedure
The following gives the basic screen data creation procedure. Required settings and reference pages are given for each step of the procedure.
➡ Select “Tool Settings” in the Main Menu to display the “Tool Settings” screen.
Settings of PT setting, memory size, and direct setting are made in this screen.
Refer to “Setting the support tool for use with the NT20S” on the previous page.
113
Creating and Transmitting Screen Data Section 4-1
Select “Tool Settings”.
➡ Select a file used for storing the screen data for the NT20S in the “File List” screen.
To create a new file, select “New File”.
To edit an existing file, select a file to edit.
Select “New File” and press [Enter]. Enter filename on completion of creation.
Select “Screen Creation”.
114
Select a screen number to edit in the selected file in the “Screen List” screen.
Note that when using the host link, NT link, or C200H direct communication, the PT status control area and PT status notify area must be set as described below before selecting the screen number.
To read the screen data from other file, press the [F5] (Read) function key.
Creating and Transmitting Screen Data Section 4-1
Host link/NT link/C200H direct communication
➡ Press [F10] (Next) in the “Screen List” screen, then press [F2] (Direct) to display the Direct Conn. Setting screen. On this screen, specify the first words allocated to the following areas in the PC memory.
S
PT status control area: Section 5-4 NT20S Status Control (page 191)
S PT status notify area: Section 5-5 Notification of the Operating Status to the PC
(page 196)
S
Numeral memory table: Numeral Memory Table (page 127)
S
Character string memory table: Character-String Memory Table (page 126)
Common to All Communication Methods
Press [F4] (Attrib) in the “Screen List” screen to set the screen attributes in the
Help Message. The following attributes can be set.
S Buzzer (None/Cont/Long/Shrt)
S
Bit In (YES/NO)
S
Keypad (Syst/User)
S
Backlight (ON/OFF)
➡ Bit input attributes can be set when using the NT20S-ST128 (RS-232C).
Select a screen number and press [Enter].
Create screen data in the Edit screen. Data of one screen can be created by registering (laying out) the following display elements and attributes on the screen.
S
Fix display:
Input character strings and figure.
. . . . . . . . . . . . .
“Characters and Figures Which can be Displayed” (page 119)
S Numeral display:
Set numbers in the numeral memory table.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
“Numeral Memory Table” (page 127)
115
Creating and Transmitting Screen Data Section 4-1
S
Character string display:
Set the character string memory table number and display method.
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
“Character-String Memory Table” (page 126)
S Lamp:
Set the lamp number or allocated bit and display method.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 4-6 Lamps (page 133)
S Touch switch:
Set the touch switch number, screen switching number, allocated bits for control and notification, and display method.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 4-7 Touch Switches (page 136)
S Graph:
Set the numeral memory table number and display method.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 4-5 Bar Graphs (page 129)
S Input setting:
Set numbers in the numeral memory table.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section 4-8 Numeral Setting (page 140)
[Edit screen quit]
Return to the “Screen List”.
To successively create or modify another screen, select the screen number.
116
Creating and Transmitting Screen Data
Enter filename to newly created screen data.
Return to the “File List”.
Section 4-1
[To the File Selection]
Pressing the [F8] (Start-up screen) key allows setting of the screen number to be displayed when the NT20S is booted. (Only effective when using RS-232C)
Transmitting Screen Data to the NT20S
Transmit the screen data created by using the support tool to the NT20S screen data memory.
Pressing the [F6] (Tmx.) key on the “File List” screen will cause the created screen data to be transmitted to the NT20S in file units. Pressing [F10] (Next) and then
[F6] (Tmx.) on the “File List” screen will cause the screen data to be transmitted in screen units. Before attempting data transmission, connect the NT20S and support tool and set the NT20S to the transmit mode.
For the connection procedure to the support tool, refer to Section 2-3 Connecting to the Support Tool (page 31). For the transmission of the screen data, refer to
Section 3-6 Registering the Screen Data (page 86).
Note: When transmitting data in screen units, if changes have been made to memory tables or direct information in addition to the screens, transmit this changed data also.
117
Outline of Functions Section 4-2
4-2 Outline of Functions
4-2-1 NT20S Screen
This section gives the outline of the screen which is the basis of all NT20S functions.
For specific operation procedure such as screen switching, refer to “Switching the
Screen Display” (page 157).
Composition of the Screen The NT20S screen is composed of horizontal 256 dots x vertical 128 dots. Each dot is set by the combination of the X (horizontal) and Y (vertical) coordinates. The origin of coordinates (0, 0) is set at the top left corner of the screen.
0
0 X coordinate (horizontal)
255
Y coordinate
(vertical)
Coordinates
(x, y)
Screen Management
Special Screen Number
127
255, 127
The screens displayed on the NT20S are managed by the screen numbers.
When using the NT20S, up to 495 screens can be created and screen numbers in the ranges 1 to 250 and 256 to 500 can be used (numbers 251 to 255 are reserved for system use).
The display screens can be switched or the start-up screen can be set by designating the screen number from the Host.
Screen number “0” is reserved for the system as the no-display screen. Select this to display nothing on the NT20S screen.
118
Outline of Functions Section 4-2
4-2-2 Characters and Figures Which can be Displayed
The NT20S screen can display characters, figures, and other various elements.
This section describes the types and attributes of the characters and figures which can be displayed and do not need to be changed at all.
For the settings, display, and use of the characters, numeric values, and graphs which change according to the system operation status and other conditions, refer to Section 4-4 Memory Table (page 126).
The power of expression of the screen can be increased by giving various attributes such as the enlarged or reverse display to the characters and figures.
The character and figure attributes can be set in the edit screen when creating the screen data by using the support tool.
When using the NT20S-ST128 (RS-232C), character strings can also be displayed in accordance with commands from the host, independently of the currently displayed screen (this is the “terminal function”).
Types and Attributes of Characters and Figures
The following types of characters can be input by using the support tool and be displayed during operation.
Character
Type
Half height characters
Normal characters
Marks
Dots
(vertical x horizontal)
8 x 8
16 x 8
16 x 16
Character Set
Alphanumerics and symbols
Alphanumerics and symbols
Create by using the support tool
Maximum Number of
Characters Displayed in One
Screen (without overwriting)
32 characters x 16 lines
(512 characters)
32 characters x 8 lines
(256 characters)
S Marks
A mark is a graphic pattern created by combining 16 x 16 dots by using the support tool. Marks can be handled the same as the wide size characters. Up to 64 patterns can be defined within the total screen data using character code FF20 to FF5F.
S Enlarged display of the characters and marks
The characters and marks can be enlarged to the following scales.
x1 scale
Double width scale
Double height scale x4 scale x9 scale x16 scale
Reference: Smoothing
The characters and marks enlarged to the x4 scale or larger are displayed with the outline automatically smoothed. This function is called “smoothing”.
119
Outline of Functions Section 4-2
S
Reverse and flashing display
Reverse display: The display brightness of the character and the background is reversed comparing with the normal display.
Flashing display:
Reverse and flashing display: The reverse display alternates with the normal display.
Types and Attributes of the Figures
Characters are displayed as they flash. The normal display alternates with no-display.
The following types of figures can be input by using the support tool and be displayed during operation. Continuous straight lines including up to 256 vertexes can be drawn (up to 255 straight lines can be connected).
Continuous straight lines Circle
4-2-3 Communications with the Host
Communication using the host link/NT link/C200H direct communication
The NT20S-ST121-EV3/ST122-V1 can communicate with the PC through the host link/NT link/C200H direct communication. Bits and words are allocated to areas of the PC memory (selectable without restriction) and the NT20S can write data to them or read from them directly. This makes the following functions possible:
S
Control/Notification of display elements
S
Control/Notification of the NT20S status
S
Screen switching
S Ascertaining the number of the screen currently displayed
S Memory table operations
For details on actual operations, refer to Section 5 “How to Use the Host Link/NT
Link”
120
Outline of Functions Section 4-2
Communication through RS-232C
The NT20S-ST128 can communicate with the host through the RS-232C interface. In other words, it can receive and send commands through the RS-232C interface, which allows various types of host to utilize the functions of the NT20S:
S Control/Notification of display elements
S Control/Notification of the NT20S status
S Memory table operations
S Screen operation
S Display/Deletion of characters/graphics
For details on actual operations, refer to Section 6 “Using the RS-232C”
Controllable NT20S functions
The following NT20S statuses can be controlled:
S
Screen switching: Screen is displayed or cleared.
S
Continuous/intermittent buzzer: Buzzer operation is started or stopped.
S Back light mode: Back light is lit or made to flash.
For details on how these NT20S functions are actually controlled, refer to Section
5-4 “NT20S Status Control” on page 191, “Screen Display Control” on page 215, and “Buzzer Control” on page 215.
Ascertainable operating statuses of the NT20S
The following operating statuses of the NT20S can be ascertained:
S NT20S operating/stopped status: Whether the NT20S is active or inactive
S Screen number: Number of the screen currently displayed
S
Numeral setting input: Whether or not numerical values have been input by numeral setting
For details on how these NT20S operating statuses are actually detected, refer to
Section 5-5 “Notification of the Operating Status to the PC (Determining the
NT20S Operating Status)” on page 196, “Screen Number Response” on page
205, and “8-digit Number Input Notify” on page 212.
Caution: To ensure system safety, be sure to periodically read the PT operating status bit from the host in order to ensure that the PT is always operating normally.
121
Screen Display Section 4-3
4-3 Screen Display
This section describes the screen information required for the operation with the
NT20S.
For details on how to change the displayed screen, refer to “Switching the Screen
Display” on page 157, and “Display Specified Screen” on page 204. For the methods used to ascertain the screen number of the screen currently displayed, refer to
“Notifying the Display Screen to the PC (To Display the Number of Currently Displayed Screen)” on page 160, and “Request Screen Number” on page 204.
4-3-1 Classification of Screens
The NT20S is provided with the following types of screens which are classified by the display method.
Normal Screen
Overlapping Screen
S Normal screen
S
Overlapping screen
S
Continuous screen
The screen type is set with each screen in the “Screen List” screen of the support tool. Select a screen type according to the purpose, and create characters and figures on the screen. In the case of the NT20S-ST128 (RS-232C), character strings and graphics can be also displayed in accordance with commands from the host, independently of the currently displayed screen. The details of each screen type are given below.
A normal screen is the basic screen of the NT20S. It is not necessary to select a screen type (overlapping or consecutive) when to create the screen data on a normal screen.
When a normal screen is selected, existing screens will be erased and a normal screen will be displayed.
Several normal screens can be overlapped and displayed as one screen. A group of overlapped screens is called an “overlapping screen”.
Several normal screens are displayed in the order of screen numbers which have been designated to each screen and form an overlapping screen. Up to eight screens can be overlapped to form one overlapping screen. The base screen used for making an overlapping screen is called a “parent screen”, and a bunch of screens which are laid over the parent screen are called “child screens”.
All display elements can be used on a parent screen.
The screen attributes such as a buzzer attribute set in the parent screen become effective in an overlapping screen.
122
Screen Display
Continuous Screens
Section 4-3
[Example overlapping screen]
Screen #10
(1)
This is an
Screen #8
This is an overlapping screen.
(2)
Screen #7 overlapping
(3)
Screen #25 screen.
S
Parent screen: #8
S
Child screens: #10, #7, and #25
When screen #8 is designated, screen #8 becomes the parent screen and the child screens #10, #7, and #25 are displayed over the parent screen in that order.
Only one numeral setting screen which allows numeric values to be set on the
NT20S screen can be registered as a child screen. For the numeral setting, refer to
Section 4-8 Numeral Setting (page 140).
Make sure that the touch switches and numbers set in the normal screens do not overlap in an overlapping screen. If the set positions of the touch switches and/or numbers in the normal screens overlap with each other, such settings may sometimes not be effective as intended. Use the support tool and make sure that the set positions do not overlap with each other.
A group of normal screens which are related in series and can be switched consecutively is called the “continuous screens”. Up to eight screens can be registered to one screen as a group of continuous screens.
The base screen used for registering the continuous screens is called a “parent screen”, and the registered continuous screens are called “child screens”.
The current screen number and the total number of continuous screens can be displayed in the top right corner of the screen. This is called the “page number display”.
The page number is set when creating the screen data by using the support tool.
Refer to the “NT-series Support Tool Operation Manual” (V028-E1-j).
All display elements except “numeral setting” can be used in the continuous screens.
The screen attributes set in the parent screen become effective in the continuous screens.
123
Screen Display Section 4-3
[Example continuous screens]
1/3
Continuous screen (1)
Screen #20 touch switch touch switch
Continuous
2/3 screen (2)
Screen #15 touch switch touch switch
Continuous screen (3)
3/3
Screen #5
S
Parent screen: #10
S
Child screens: #20, #15, and #5
When screen #10 (continuous screen) is designated, screen #20 which is page 1 of the continuous screens will be displayed. Screen #15 or #5 can be displayed by using the touch switches. Since screen #10 has been set for the continuous screens, that screen cannot be displayed as an individual screen.
Switching the Continuous Screens by Using the Touch Switches
Continuous screens can be switched by using the and touch switches which have the system key functions.
When creating the screen, create touch switches and to which the system key functions are allocated. (Refer to “System key functions” (page 139).)
1/3
Production Status
Line A: Normal
Line B: Normal
124
Screen Display Section 4-3
4-3-2 Screen Attributes
Each screen can be set with a specific function by designating a screen attribute, so that the specific function can be executed by displaying the screen. For example, by displaying a screen to which a “buzzer attribute” has been set, the buzzer of the NT20S starts sounding.
Buzzer Attribute
Set the screen attributes for each screen on the “screen selection” screen of the support tool.
Note that the support tool displays some items that are not used with the NT20S, such as “history attribute”, “alarm”, and “backlight color”.
The following several attributes can be set with one screen.
This attribute will become effective to sound the buzzer in the NT20S when the screen to which this attribute has been set is displayed. The buzzer sound can be set as follows:
No: Buzzer does not sound when the screen is displayed.
Continuous sound: Buzzer sounds continuously.
Intermittent sound: Buzzer sounds intermittently at constant intervals.
The buzzer sound is set with the NT20S memory switch. The buzzer can also be set by using the Host. Refer to “Using the buzzer” (page 92) for the buzzer setting using the memory switch.
To stop the buzzer by using the screen operation, create a system key as a touch switch.
Numeral Setting Attribute Select whether the numeric keys are automatically displayed or the numeric keys are created at arbitrary positions on the numeral setting screen. The following two numeral setting attributes are used.
System: The numeric keys registered to the system are automatically displayed.
User: The numeric keys can be created at any arbitrary positions.
Reference: If the numeral setting attribute on the NT20S has been set for “system”, the touch switches [ENT], and which are allocated to the system besides the numeric keys need to be created. (System key functions (page 139))
Bit input attributes (applies to NT20S-ST128/RS232C only)
Select whether the touch switch number or bit information is notified to the host when the touch switch is pressed. There are two types of bit input attribute in the screen attributes, as indicated below:
Backlight attributes
S
Off : Bit control when a touch switch is pressed is invalid. The status of the touch switch is notified using its number.
S Touch SW : Bit control when a touch switch is pressed is valid. The status of the touch switch is notified using bit information.
Select whether the backlight is lit or flashes when the screen is displayed. There are two types of backlight attribute in the screen attributes, as indicated below:
S Lit : Backlight is lit when the screen is displayed.
S
Flashing : Backlight flashes when the screen is displayed.
125
Memory Tables Section 4-4
4-4 Memory Tables
The NT20S has the “character-string memory table” for the character data and the
“numeral memory table” for numeric data which can be written and updated by the
PC/Host.
The contents of the memory tables can be set by using the support tool when displaying the memory tables on the screen or by editing the table.
4-4-1 Character-String Memory Table
The character-string memory table is an NT20S internal memory used to store the character data. Up to 128 character-string memory tables can be used, and up to
16 full size characters (32 bytes) can be stored in one memory table. The character-string memory tables at up to 32 positions can be registered in one screen.
Displaying a Character String
The character-string memory tables are registered with table numbers 0 to 127.
When creating the screen data by using the support tool, set the position on the screen to display a character string and also set a character string number to be displayed.
When the NT20S is operated, the screen displays the contents of the characterstring memory table.
When using Ver.5 direct connection, it is possible to display the contents of character-string memory tables by specifying their numbers with numeral memory tables
(indirect specification), rather than directly changing the character-string memory table contents.
For details on how to change currently displayed character strings, refer to
“Changing Displayed Numerals or Character Strings (Changing the Contents of
Allocated Words)” on page 169, and “Write Character-string Memory Table” on page 205.
When using the NT20S-ST128 (RS-232C), character strings can be also displayed in accordance with commands from the host, independently of the currently displayed screen (terminal function). Refer to “Specify Displayed Characters” on page 220.
Characters and Figures Which can be Displayed
The power of expression of the screen can be increased by giving various attributes such as the enlarged or reverse display to the characters of the characterstring memory table.
The character attributes can be set in the edit screen when creating the screen data by using the support tool.
126
Memory Tables Section 4-4
The following types of characters can be displayed on the NT20S:
Character
Type
Half size characters
Normal size characters
Marks
Dots
(vertical x horizontal)
8 x 8
8 x 16
16 x 16
Character Set
Alphanumerics and symbols
Alphanumerics and symbols
Create by using the support tool
Maximum Number of
Characters Displayed in One
Screen (without overwriting)
32 characters x 16 lines
(512 characters)
32 characters x 8 lines
(256 characters)
S Enlarged display of the characters and marks
The characters and marks can be enlarged to the following scales.
Double width scale, Double height scale, x4 scale, x9 scale, x16 scale
S Smoothing
The characters and marks enlarged to the x4 scale or larger are displayed with the outline automatically smoothed. This function is called “smoothing”.
S
Reverse and flashing display
Reverse display: The display brightness of the character and the background is reversed comparing with the normal display.
Flashing display: Characters are displayed as they flash. The normal display alternates with no-display.
Reverse and flashing display: The reverse display alternates with the normal display.
4-4-2 Numeral Memory Table
The numeral memory table is an NT20S internal memory used to store the numeral data. Up to 128 numeral memory tables can be used, and up to eight digits (four bytes) of numeral data (including signs) can be stored in one numeral memory table. The numeral memory tables at up to 50 positions can be registered in one screen.
Displaying a Numeral The numeral memory tables are registered with table numbers 0 to 127.
When creating the screen data by using the support tool, set the position on the screen to display a numeral and also set a numeral number to be displayed.
When the NT20S is operated, the screen displays the contents of the numeral memory table.
➡ For details on how to change the currently displayed numeric data, refer to
“Changing Displayed Numerals or Character Strings (Changing the Contents of Allocated Words)” on page 169, and “4-digit Write Numeral Memory Table” on page 206.
127
Memory Tables Section 4-4
Numerals Which can be Displayed
The power of expression of the screen can be increased by giving various attributes such as the enlarged or reverse display to the numerals of the numeral memory table.
The numeral attributes can be set in the edit screen when creating the screen data by using the support tool.
S
Digits of the whole numbers: 1 to 8 digits
S
Digits of the decimal fraction: 0 to 7 digits
S
Character sizes: Half, normal
S Enlarged display: Double width, double height, x4, x9, x16
The characters enlarged to the x4 scale or larger are displayed with the outline automatically smoothed. This function is called “smoothing”.
Normal, reverse, flashing, reverse and flashing S Display attribute:
S Sign display setting
S Decimal/hexadecimal display setting
S Zero suppress setting
To display one numeral memory table on several different screens simultaneously, the display attributes on such screens must be the same. If there is discrepancies among the display attributes, the numeral table may not be displayed correctly.
Reference: Zero suppress setting
The numeral data are displayed in designated display areas as right-aligned. If the number of digits of a numeral data is smaller than that of the display area, number
“0”s will be displayed at the vacant digits. These “0”s will not be displayed if the zero suppress setting is made for “Yes”.
128
Bar Graphs Section 4-5
4-5 Bar Graphs
The contents of the numeral memory tables of the NT20S can be displayed as bar graphs as well as numeral data.
This section describes the bar graphs which can be displayed.
In order to change the data displayed in a bar graph, the contents of its numeral memory table have to be changed.
For details on how to update the data of a currently displayed bar graph, refer to
“Upgrading Bar Graphs (Changing the Contents of Allocated Words)” on page
177, and “4-digit Write Numeral Memory Table” on page 206.
4-5-1 Bar Graph Functions
The bar graph function displays a value in a bar graph form as a percentage to the specified value according to the contents of a numeral memory table. Up to 50 bar graphs can be registered in one screen.
Bar Graph Attributes
S Reference table
The numeral memory table used as the reference for the bar graph display can be set.
The support tool has the “direct” and “indirect” options for the reference method of the numeral memory table. However, the NT20S recognizes the “direct” method only.
The bar graph display cannot use hexadecimal numbers. If hexadecimal numbers are set in the reference numeral memory table, the bar graph cannot be displayed. Use caution not to write hexadecimal numbers except the minus sign
“F” to the reference numeral memory table.
The following attributes can be set with the NT20S for the bar graph display:
S Position and size
The display position and size (length) of a bar graph can be set.
The width of the bar graph can be set in the range of 2 to 255 dots.
129
Bar Graphs Section 4-5
S
Orientation and incremental direction
The orientation and incremental direction of the bar graph can be selected from those mentioned below.
↑ (up): The bar graph increments upward in the vertical orientation.
↓ (down):The bar graph increments downward in the vertical orientation.
← (left): The bar graph increments to the left in the horizontal orientation.
→ (right):The bar graph increments to the right in the horizontal orientation.
Direction: ↑
Direction: →
S
Graph frame
Select whether or not the graph frame (boundary line of a graph display area) which indicates the effective display range is displayed.
← This frame is not displayed if
“Graph frame: No” has been set.
S
Setting the 100 % value and % display
Set a value which corresponds to 100 % for the “100 % value”. The available value range is “0 to 99999999” (max. eight digits). For the “% display”, whether or not the proportion (percentage) of the reference numeral memory table value to the “100 % value” is displayed in a numeral can be selected. The display value is calculated as follows:
“% display” value = Numeral memory table value ÷ “100 % value” x 100
For the font and attributes used for the numeral display, refer to “Numerals which can be displayed” (page 127).
S Sign display and display method
Select whether or not the bar graph which indicates a value below 0 % is displayed.
130
Bar Graphs Section 4-5
[To display a value below 0 %: Sign display “Yes”]
The bar graph is displayed in the range of --100 % to 100 %. The middle of the bar graph indicates 0 %.
% display
--60 %
--100 % 0 % 100 %
[Not to display a value below 0 %: Sign display “No”]
The bar graph is displayed in the range of 0 % to 100 %. The end of the bar graph indicates 0 %. Values below 0 % are indicated as 0 %.
% display
60 %
0 % 100 %
S Differences in the bar graph display method according to the % values
The bar graph display method varies according to the % value range.
(1) When the % value is in the minus range
The display varies as follows according to the sign display setting:
Sign display “No”: Displayed as 0 %.
Sign display “Yes”: Displayed in the minus range.
(2) When the absolute value of the % value is in the range of 100 % to 999 %
The % value is displayed as it is.
Sign display “No”: The display will be as mentioned below according to the graph frame setting.
When the frame is displayed:
% display
999 %
0 %
↔
100 %
Graph width: 8 dots
131
Bar Graphs Section 4-5
When the frame is not displayed:
% display
999 %
1-dot-wide space
0 %
↔
100 %
Graph width: 8 dots
Sign display “Yes”: A value below --100 % will be displayed in the minus direction as shown above.
(3) When the absolute value of the % value is above 1000 %
The bar graph will be displayed the same as (2) above.
The % value is displayed as follows according to the sign display setting:
Sign display “No”: £££ %
Sign display “Yes”: ££££ %
132
Lamps Section 4-6
4-6 Lamps
The NT20S has the “lamp” function used to simply display the PC bit status.
This section describes the lamps which can be displayed.
The lamp display status (lit (flashing) or unlit) can be changed by instructions from the PC/host.
For details on how to change the status of a currently displayed lamp, refer to
“Turning ON (lit) and OFF (unlit) the Lamps (Changing the Contents of Allocated
Bits)” on page 179, “Lamp and Touch Switch Display (Bit Specification)” on page
210, and “Lamp and Touch Switch Display (Number Specification)” on page 210.
4-6-1 Lamp Functions
The lamps are the graphic areas whose method of display can be changed by using the PC. Available display methods are “lit”, “unlit”, and “flash“. Up to 128 lamps can be registered in one screen.
The display status (lit, unlit, and flashing) which are registered when creating the screen data can be switched according to the ON/OFF of the PC bit status.
Lamp Attributes
PC
Unlit Lit
The following attributes can be set with the lamp. Use the support tool to set the lamp attributes.
S Shape
Select from the square and circle shapes. The display size can be freely selected.
Square Circle
S Frame
Select whether or not the boundary line (frame) of the lamp display area is displayed. If the frame is not set, only the guide display message for the lamp is displayed when the lamp is not lit (or flashing). If the guide display message is not set, nothing is displayed.
133
Lamps Section 4-6
S
Lit and flashing
Select whether the lamp is lit (reverse display) or flashing (reverse flashing) when the lamp is turned ON by the PC.
S
Guide display message
Lamps can be displayed with the guide display messages.
The guide display message attributes are the same as that for the “character display”. Refer to “Characters and Figures which can be Displayed” (page 126).
S Frame and lit/flashing
The display method of “lit/flashing” varies according to the frame setting.
Frame is set:
Frame is not set:
Only the area in the frame will be lit/flashing.
The area including the frame will be lit/flashing.
[Frame is set]
Unlit
Flash
[Frame is not set]
Unlit
Flash
Lit Lit
Area inside the frame flashes.
Area including the frame flashes.
S
Controlling the lamps in batch
More than one lamp can be lit or flashing in batch by registering those lamps to the same bit.
[Example of batch lighting]
Set the lamps L1 to L5 to the same bit number.
L1
L2
L3 L4 L5
L1 L2
L4
L5
L3
134
Lamps Section 4-6
When a lamp is overlapped with a memory table display
The guide display message for a lamp is a fixed character-string. If you want to change the lamp guide display in accordance with some condition, overlap the display area of a numeral memory table or character-string memory table with the lamp. However, note that different results will be achieved depending on the timing of the lighting of the lamp and the updating of the memory table. Bear this in mind when creating the control program.
135
Touch Switches Section 4-7
4-7 Touch Switches
The NT20S has a function whereby input operations can be performed by using touch panels displayed on the screen. NT20S screens can be switched, or bit information sent to the Host, by pressing (lightly touching) the “touch switches” in a panel.
The touch switches can also be made to light up (or flash) and go off like lamps.
Touch switches are set when creating the screen data with the support tool.
This section describes the touch switches that can be displayed, and explains the screen switching function and the system key function.
For details on how the status of the currently displayed touch switch is notified to the Host, refer to “Lit (Flashing) and Unlit Touch Switch Statuses (Changing the
Status of Allocated Bits)” on page 183, “Lamp and Touch Switch Display (Bit Specification)” on page 210, and “Lamp and Touch Switch display (Number Specification)” on page 210.
For details on how the statuses of touch switches are ascertained by the Host, refer to “Notifying the Host that a Switch has been Pressed (Determining Touch
Switch Status)” on page 183, and “Lamp and Touch Switch Display Status Enquiry” on page 211.
Caution:
S
Do not use input functions such as PT touch switches for applications where danger to human life or serious property damage is possible or for emergency switch applications.
S Press touch switches with a force of no greater than 30 N.
S
Do not press touch switches carelessly while the backlight is off or while nothing is displayed on the screen. Otherwise the system may operate unpredictably.
Only press touch switches after confirming system safety.
S If touch switches are pressed in rapid succession, their inputs may not be successfully received.
Confirm that the input of a touch switch has been successfully received before moving on to the next operation.
Reference: Caution on pressing touch switches at 3 points
When multiple touch switches are created at the relative positions indicated in the example below, malfunctions may occur due to the characteristics of this switch configuration.
Example 1: When switches are created at positions A and B and at the points where the vertical and horizontal lines extending from these two points intersect, i.e. points C and D:
A
C
B
D
Smallest touch switch frame
S When switches A, B, and C are switched on at the same time, switch D is also assumed to have been switched on due to the configuration of the touch switches.
S When switches A, B, and D are switched on at the same time, switch C is also assumed to have been switched on due to the configuration of the touch switches.
136
Touch Switches Section 4-7
4-7-1 Functions of Touch Switches
Touch switches are created using rectangular elements measuring 19 dots horizontally by 19 dots vertically. A touch switch can comprise more than one touch switch element. Up to 72 touch switches (12 horizontally x 6 vertically) can be registered on one screen.
19 dots
19 dots
A touch switch can comprise more than one touch switch element.
PC
When the touch switch is pressed, bit information is sent to the PC.
(Host link/NT link)
Host
When the touch switch is pressed, the touch switch number or bit information is sent to the Host.
(RS-232C)
S
Functions of touch switches
Touch switches can have the following functions:
Touch Switch Attributes
- PC notification function
NT20S-ST121-EV3/ST122-V1
:Host link/NT link/C200H direct communication (page 183)
NT20S-ST128 :RS-232C (page 212)
- Screen switch (standalone) function (page 138)
- System key function (page 139)
- Numeral setting function
NT20S-ST121-EV3/ST122-V1
:Host link/NT link/C200H direct communication (page 188)
NT20S-ST128 :RS-232C (page 212)
The following attributes can be set for touch switches.
S
Display frame
The area that will respond as a touch switch is displayed in the form of a frame, as shown in the table below. One of three types of frame - standard, 3-D, and none - can be selected.
Type of Display
Frame
Switch OFF Switch ON
Standard
3-D
None
137
Touch Switches Section 4-7
If “none” is selected, only the touch switch’s guide display message (or nothing, if there is none) are displayed until a “light” or “flash” designation is sent from the
PC/Host or the touch switch is pressed.
S Inverse display on input
It is possible to set a touch switch so that its display will be inverted when it is pressed.
S
Lighting and flashing
It is possible to specify whether the touch switch will be lit continuously or flash when the bit allocated to it is turned ON by the PC/Host.
S
Presence/absence of a guide display
A guide display message can be displayed at a touch switch location.
4-7-2 Screen Switching Function
The NT20S has a function that allows screens to be switched by pressing touch switches on its screen, rather than by designation from the PC/Host. This function is called the “standalone function”.
The screen number of the screen that will be displayed when a touch switch is pressed is set for that touch switch when the screen data is created using the support tool.
If the touch switch is pressed during operation, the screen whose number was designated will be displayed. Simultaneously, the PC/Host will be notified of the screen number of the screen selected for display.
To next screen
Touch switch pressed once
Screen #5
“Screen #5” set for touch switch 1
To set a screen number for a touch switch, use “Touch SW”, “Bit specification” and
“Screen switch” of the support tool.
Note: Only one screen number can be set for one touch switch within one screen (or within one overlapping screen).
138
Numeral Setting Section 4-8
4-7-3 System Key Functions
The NT20S allows the allocation of “system key” functions to touch switches. The system key functions can then be used during operation by pressing the touch switches to which they have been allocated.
For example, if, when a screen for which buzzer sounding has been set is displayed, a touch switch is also displayed, the buzzer can be stopped by pressing this touch switch.
To set a system key function for a touch switch, use “Touch SW”, “Bit specification” and “Numeric key” of the support tool.
Allocation of System Key Functions
The system key functions are allocated to touch switch numbers 227 to 230 and
255, as shown below. When a touch switch with one of these numbers is displayed on the screen, it has the same function as the corresponding system key.
System Key
System menu display
Key Symbol
MENU
[Buzzer stop]
[ENT]
Touch Switch No.
227
228
229
230
255
➡ When a touch switch to which a system key function has been allocated is pressed, the touch switch bit information is not notified to the PC.
The , , and keys are not displayed among the system numeric keys. Accordingly, when using the system numeric keys, create the , , and keys.
Alternatively, create user numeric keys.
139
Numeral Setting Section 4-8
4-8 Numeral Setting
The NT20S has a “numeral setting” function to enable numerical values to be input from the screen. This function inputs numerical values to numeral memory tables in response to touch switch operations, displays these numerical values on the screen, and sends them to the host.
This section outlines the numeral setting function and the method for creating the ten keys required to set numerical values on the screen, and explains how to use ten keys during operation.
Numeral setting screens cannot be registered as child screens of continuous screens. In the case of overlapping screens, only one of the screens can be set as a numeral setting screen.
For details of the actual methods used to ascertain input numerical values at the
PC side, refer to “Notification of Numbers to the PC” on page 188, and “Number
Input Notify” on page 212.
Numeral settings are set during screen creation with the support tool.
Caution: Confirm system safety carefully before changing monitor data.
4-8-1 The Numeral Setting Function
The numeral setting function is described below.
Basic Procedure The procedure for numeral setting is as follows.
(1) Input the numerical value at the touch panel.
(2) The input numerical value is displayed in the numeral setting area on the screen.
(3) Confirm the input numerical value; it will be written to the numeral memory table, and simultaneously notified to the PC.
Numeral setting area
NT20S
Input
1 2 3 4
Write
1 2 3 4
Numeral memory table
Notification
PC
Touch switch
140
Numeral Setting Section 4-8
Restrictions on Numerical Value Input and Attribute Setting
Numerical values of up to 8 digits (7 if there is a minus sign) can be input in either decimal or hexadecimal format.
S
Decimal input
When the display attribute is set for decimal display, values are input in the decimal format.
- Numerical value range
The range for numerical values that can be input differs according to whether or not there is a sign display.
When there is no sign display : 0 to 99999999 (8 digits)
When there is a sign display : --9999999 to +99999999
(7 digits for negative numbers,
8 digits for positive numbers)
If a sign is displayed when using the thumbwheel type of numeral setting, the maximum number of digits for both positive and negative numbers is 7.
- Decimal point
A maximum of 7 digits can be input after the decimal point (or 6 for negative numbers).
S Hexadecimal input
When the display attribute is set for hexadecimal display, values are input in the hexadecimal format.
- Numerical value range
Numerical values can be input in the range 0 to FFFFFFFF (8 digits).
S
Attributes that can be set
The attributes of the numerical values displayed in the input field are the same as for numeral displays. See “Numerals Which can be Displayed” (page 127).
Upper/lower limit check (Ver.5 direct connection only)
When Ver.5 direct connection is used with an NT20S-ST121-EV3/ST122-V1, upper and lower limits can be set for input numerical values to prevent erroneous values that are outside the valid range being stored in the numeral memory table or notified to the PC.
The upper/lower limit check is executed when the input numerical value has been confirmed: if the value is outside the valid range, the screen returns to its status before input.
Correct Use: In order to use the numerical value input setting safely, always use the upper/lower limit check function. Since this function is not featured with NT20S-ST128 and
Ver.4 and previous versions of the direct connection function, take appropriate measures using the user application software.
141
Numeral Setting Section 4-8
4-8-2 Types of Numeral Setting
There are two types of numeral setting: the numeric key type, and the thumbwheel type.
The basic function of these two types is the same, but the screen displays and input methods are different.
A maximum of 50 input fields, including both numeric key and thumbwheel types, can be registered on one screen.
The thumbwheel type of numeral setting can only be used when using Ver.5 direct connection with an NT20S-ST121-EV3/ST122-V1.
Numeric Key Type When a numerical value is input using touch switches to which numeric key functions have been allocated, the input numerical value is displayed on the screen.
On pressing the return key after completing input, the input numerical value is written to the numeral memory table and notified to the host.
If there is more than one numeral setting input field, the field in which the input is to be made can also be selected with the numeric keys.
In order to perform numeric key input, it is necessary not only to create a numeral setting input field on the screen, but also to create the numeric keys to be used for input (see page 143).
Displayed in the numeral setting input field
NT20S
1 2 3 4
Input
Input the numerical value using the numeric keys on the screen.
Write
1 2 3 4
Numeral memory table
Notification
Host
On pressing the key, the input value is written to the numeral memory table and simultaneously notified to the PC.
Thumbwheel Type (Ver.5 Direct Connection Only)
When using an NT-20S-ST121-EV3/ST122-V1 with Ver.5 direct connection, numerical values are input directly at the numeral setting input field using touch switches that increment or decrement each of the digits in the display when pressed. Each time the displayed numerical value is changed, the new displayed value is written to the numeral memory table and simultaneously notified to the host.
This means that, when using the Thumbwheel type of numeral setting, all that is required to input numerical values is to create the numeral setting input field on the screen.
Pressing the [--] key decrements the digit by one.
NT20S
1 2 3 4
Pressing the [+] key increments the digit by one.
Write
1 2 3 4
Numeral memory table
Notification
Host
Each time a [+] or [--] key is pressed, the input value is written to the numeral memory table and simultaneously notified to the hos.
142
Numeral Setting Section 4-8
4-8-3 Creating Numeric Keys
In order to input numerical values using the numeral setting function, apart from the display area for the numeral setting, the numeric keys must also be created.
Setting Screen Attributes The type of numeric keys can be selected using the numeral setting attributes of the screen attributes. There are two numeral setting attributes: “system” and
“user”.
S
Screen when “system” is specified
When a numeral setting area is created, numeric keys are automatically displayed. The display position and arrangement of the numeric keys are fixed. On this screen, only the types of numeric key shown in the figure below (system keys) are used.
Tank A Tank B Tank C
1
7
2
8
3
9
4
0
5
CLR
6
When using the NT20S with the numeral setting attribute set to “system”, apart from the numeric keys provided by the system, the touch switches allocated to system keys ( , , ) also have to be created (system key function). To enable input of hexadecimal values, it is also necessary to create numeric keys A through
F.
With the NT20S, if the numeral setting attribute is set to “system”, apart from the numeric keys prepared by the system, the touch switches allocated to system keys ( , , ) have to be created. (“System key functions”, page 139)
S When the numeral setting attribute is “user”
The display position and arrangement of the numeric keys can be set as required by allocating them to touch switches (see page 125).
Tank A Tank B Tank C
When the numeral setting attribute is set to “user”, numeric keys are created by using the control keys of the “input key” function. In addition, by using the character keys of the “input key” function, the one-byte characters 0 to 9 and A to F can be used as numeric keys.
143
Numeral Setting Section 4-8
Reference: Even when the numeral setting attribute is set to “user”, the same numeric keys as displayed with the “system” attribute can be displayed.
If “User” is selected for “Keypad” during data creation on the numeral setting screen, the numeric keys shown below are displayed.
Tank A Tank B Tank C
1
7
2
8
3
9
4
0
5
CLR
6
Numeric Key Allocations
232
233
234
235
236
228
229
230
231
The numeric keys are allocated to touch switches.
The numeric keys allocated to touch switches are specified when the touch switches are created. The following numeric keys (system keys) can be used for numeral setting.
For details on how to create touch switches, refer to 4-7 “Touch Switches” (page
136).
Touch
Switch
Number
227 ( £ )
Numeric
Key
Menu display
Touch
Switch
Number
237
Numeric
Key
6
Touch
Switch
Number
247
Numeric
Key
CLR
2
3
0
1
4
5
242
243
244
245
246
238
239
240
241
D
E
B
C
F
7
8
9
A
252
253
254
255
248
249
250
251
.
HOME
↑
↓
←
→
( £ ) Numeric key number 227 is the system menu display key.
When the touch switches allocated as numeric keys and system keys on a numeral setting screen are pressed, no notification is made to the PC. This means that when using the NT20S-ST128 (RS-232C), the touch switches numbered 227 to
255 cannot be used as normal touch switches on a numeral setting screen.
144
Numeral Setting Section 4-8
4-8-4 Using Numeric Keys
To input numerical data by using numeric keys, first select the numeral setting area into which the value is to be input, then input the numerical value by pressing the appropriate numeric keys.
Selecting the Numeral Setting Area for Data Input
Select the numeral setting area into which the numerical value is to be input by using either the numeric keys or the system keys.
S Selection with the numeric keys
Use the [HOME], [→], [←], [↑] and [↓] keys. By using these keys, the cursor can be shifted between numeral setting areas in the way shown in the figure below.
→
6563
4568
HOME
3200
0000
↑
↑
←
5107 4624
Pressing the [HOME] key will shift the cursor to the area whose top left corner has the smallest XY coordinate sum (the top left numeral setting input field in the example above).
S Selection with the system keys
When the and system keys on the touch panel are pressed, the cursor moves between the numeral setting areas by following the order in which they were created using the support tool.
For example, if three numeral setting areas have been created, the cursor can be moved between them following the order of creation as follows.
key:1st area → 2nd area → 3rd area → 1st area key:1st area → 3rd area → 2nd area → 1st area
If the “numeral setting” screen attribute is set to “system”, the order of cursor motion when the and system keys are used can be changed. For details, refer to the NT series support tool operation manual (V028-E1-j).
145
Numeral Setting Section 4-8
Inputting Numerical Values Input numerical values using the following numeric keys (touch switches): numerals (0 to 9, A to F), decimal point (.), sign (+,--), clear (CLR), and return ( ).
When inputting a numerical value that includes a decimal point, input the integer and decimal fraction separately. First input the integer, then press the decimal point key (.) and input the decimal fraction.
If the integer or decimal fraction exceed their respective allowable numbers of display digits, they are shifted to the left. In the system keys, however, the decimal point key (.) is not included. Therefore, it is necessary to create the decimal point key (.) apart from the ten keys of the system keys to input a numerical value including decimal fraction.
S Changing the sign
When there is a sign display, pressing the sign () key changes minus to plus or plus to minus.
S
Confirming input numerical values
Always press the return key as the final step when inputting a numerical value.
When the return key is pressed, the displayed numerical value is written to the numeral memory table and at the same time notified to the host.
S Initial operation of input keys
The sign key (), decimal point key (.), and alphabet key (A to F), operate as follows on initial use (first use after displaying the screen).
- Sign key ()
The display is cleared to zero (assuming decimal input with sign display).
- Decimal point key (.)
The display is cleared to zero, after which input starts from the decimal fraction digits (assuming decimal input with sign display).
- Alphabet (A to F) key
The display is cleared to zero (assuming decimal input).
S Upper/lower limit check
When using an NT-20S-ST121-EV3/ST122-V1 with Ver.5 direct connection, when the return key is pressed after inputting a numerical value, an upper/lower limit check is executed. If the input numerical value is outside the valid range, the data in the numeral memory table before input is redisplayed and not notified to the host.
146
Numeral Setting Section 4-8
4-8-5 Using The Thumbwheel Type of Numeral Setting (Ver.5 Direct
Connection Only)
When using the thumbwheel type of numeral setting, numerical values are input by directly touching the incrementing/decrementing (+/--) keys.
This type of input can only be used with Ver.5 of the direct connection function.
Numerical Value Input Input numerical values by using the incrementing/decrementing (+, --) keys provided for each digit.
S Numerical value specification
When an incrementing/decrementing (+, --) key is touched, the numeral at the corresponding digit is incremented or decremented by one. Whenever a plus or minus key is touched, the changed value is notified to the host. There is no need to press the return key as is the case when using the numeric key type of numeral setting.
Thumbwheel numeral setting
1 2 3 4
Numeral memory table
1 2 3 4
Press
2 2 3 4 2 2 3 4 Host
Numerical value incremented by one
Numerical values cannot be set in thumbwheel type numeral setting fields by using numeric keys.
S
Changing the sign
In settings with a sign display, touching the incrementing/decrementing (+, --) keys at the digit where the sign is displayed will change plus to minus and minus to plus.
S Upper/lower limit check
When using Ver.2 and later versions of the direct connection function, an upper/ lower limit check is executed when the incrementing/decrementing (+, --) keys are pressed. If the input numerical value is outside the valid range, the data in the numeral memory table before the key was pressed is redisplayed and not notified to the host.
However, with thumbwheel type numeral setting, if the situation is such that with an upper limit of 1n..n, and a lower limit of 0m..m (where n and m are the values of each digit), n..n < m..m, it is not possible to carry digits upward or downward.
Example:
When the upper limit value is 1200 and the lower limit value is 201, if the initial value has three digits the value can be changed within the range 201 to 999, and if the initial value has four digits it can only be changed within the range 1000 to
1200.
147
Numeral Setting Section 4-8
This is because if an attempt is made to change the leftmost digit from 0 to 1, or from 1 to 0, an upper/lower limit value check is always performed.
In order to avoid this, either set the values so that n..n ≦ m..m, or create another touch switch and write values to the host when digits are carried up or down.
4-8-6 Settings for Numeral Settings
The following settings are made for numeral settings during their creation with the support tool. Note that restrictions apply to several of the settings made for thumbwheel type numeral settings.
Settings S Referenced numeral memory table
Set the number of the numeral memory table used to record the numerical value input using the numeral setting function.
S Number of digits in the input numerical value
Set the number of digits in the numerical values that can be input. A maximum of
8 digits (total of integer and decimal fraction parts) can be set. However, if there is a sign display, the maximum number of digits for negative values will be seven.
S Upper/lower limits (Ver.5 direct connection only)
Set the upper limit and lower limit separately. The maximum number of digits in the set values is eight (or seven if there is a sign display).
When the upper limit value and lower limit value are set as negative values, set
“F” as the eighth digit.
Example: Upper limit value or lower limit value is “--123” → F0000123.
S Display attribute
Set attributes in the same way as for numeral display. For details, see Numerals
Which can be Displayed (page 127).
Restrictions and Additional Settings for Thumbwheel Type Numeral Settings
There are the following restrictions and additional items to set when creating thumbwheel type numeral settings.
S
Number of input digits for positive values when there is a sign display
When a sign display is set for a thumbwheel type numeral setting, a maximum of
7 digits can be input for positive values.
S Display size
One of two sizes can be selected: “small” in which each digit comprises two touch switch units, and “medium”, in which each digit comprises three touch switch units. Note that if “small” is selected the area in which the numerical value is displayed is also the touch switch input area.
148
Numeral Setting Section 4-8
S
Shape (end plates)
Set which of the two shapes shown below will be used. One has “end plates” at right and left sides and the other does not.
With Without
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
S Restrictions on display attributes
The following restrictions apply to display attributes.
Character type : Wide size only
Character enlargement : Standard only,
Zero suppress regardless of the display size specification
: No zero suppression only
See “Numerals Which can be Displayed” (page 127).
149
150
SECTION 5
How to Use the Host Link/NT Link
This Section describes in concrete terms how to use the Host link/NT link/C200H direct communication with the
NT20S-ST121-EV3/ST122-V1.
5-1 Overview of Direct Connection Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-1 Equipment and Settings Used in This Section
5-1-2 Allocatable Bits and Words
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-3 NT20S Status Control and Notification to PC
5-1-4 Switching the Screen Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2
5-1-5 Notifying the Display Screen to the PC
(To Display the Number of Currently Displayed Screen)
Memory Tables and Bar Graphs
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-1 Displaying the Contents of Allocated Words of Memory Tables . . . . . . . . . . . . . . . . . .
5-2-2 Changing Displayed Numerals or Character Strings
(Changing the Contents of Allocated Words ... Direct Specification) . . . . . . . . . . . . . .
5-2-3 Changing Displayed Numerical Values or Character Strings
(Changing the Contents of Allocated Words ... Indirect Specification) . . . . . . . . . . . . .
5-2-4 Copying the Memory Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
5-2-5 Upgrading Bar Graphs
(Changing the Contents of Allocated Words)
Lamps, Touch Switches, Numeral Setting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-1 Allocation Bits and Display of Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-2 Turning ON (lit) and OFF (unlit) the Lamps
(Changing the Contents of Allocated Bits) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-3 Allocated Bits, and Display, of Touch Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-4 Lit (Flashing) and Unlit Touch Switch Statuses
(Changing the Status of Allocated Bits) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-5 Notifying the Host that a Switch has been Pressed
(Determining Touch Switch Status) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-6 Notification of Numbers to the PC
5-4 NT20S Status Control
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-1 Controllable NT20S Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-2 How to Control NT20S Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Notification of the Operating Status to the PC (Determining the NT20S Operating Status)
5-5-1 Ascertainable NT20S Statuses (Notified Operating Statuses)
. .
. . . . . . . . . . . . . . . . . . . .
5-5-2 Reading the NT20S Operating Statuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
152
152
152
153
157
160
163
167
169
171
174
177
178
178
179
181
183
183
188
191
191
194
196
196
197
151
Overview of Direct Connection Operations Section 5-1
DM
CH
TIM
CNT
HR
AR
LR
5-1 Overview of Direct Connection Operations
This section explains allocated bits and words, control of the NT20S and PC notification methods, and the actual procedures used for switching screens, thereby providing the basic information required to use the NT20S-ST121-EV3 host link/
NT link and NT20S-ST122-V1 (C200H direct communication).
5-1-1 Equipment and Settings Used in This Section
The following equipment and settings are used in the examples in this section:
[Equipment] PT
PC
: NT20S-ST121-EV3
: CQM1
Support tool : NT-series Support Tool Ver. 2.j
[Support tool settings]
PT type : NT20S
Memory capacity : 96 KB
Direct setting : Ver.5
Direct Macn Type : OMRON
5-1-2 Allocatable Bits and Words
When the host link/NT link is used, the following bits and words are allocated to the
PC and used for the NT20S operation. The range of respective area varies with the type of PC. Refer to Appendix L PC Memory Map (page 278).
The allocations must be made without exceeding respective area range.
[OMRON PCs]
Area Name
Data Memory
Internal/Special
Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
C Series PCs
Allocated
Bit f
Allocated Word
Numeral
Character
String f f f
×
× f f f f f f f f
×
× f f f
Area Name
CVM1/CV Series PCs
Allocated Word
Allocated
Bit Numeral
Character
String
Data Memory f f f
Internal/Special
Relay f f f
Timer
Counter
--
Auxiliary Relay
--
×
× f f
×
×
× f
: OK : 1 word only ×: NG
When allocating a memory table to words, the allocation must not exceed the word area.
Since the special auxiliary relays of the CV series PCs are allocated to the system, they cannot be used for purposes other than the system use. However, reading from them is possible.
152
Overview of Direct Connection Operations Section 5-1
Reference: One allocation word of the memory table can use continuous areas of up to 2 words in the case of numeral memory table or 16 words in the case of character string memory table.
5-1-3 NT20S Status Control and Notification to PC
The following describes the fundamentals of the display elements, NT20S status control, and notification which are the basics of the NT20S functions when using the host link/NT link.
For the detail method of use of the PT status control area and the PT status notify area, refer to Sections 5-4 NT20S Status Control (page 191) and 5-5 Notification of the Operating Status to the PC (Determining the NT20S Operating Status)
(page 196).
Controlling the Display Elements by Using Allocated Bits and Words
The NT20S will operate as follows in the display element control operation.
[NT20S operation]
(1) The NT20S checks the allocation bits and words of the display elements and makes an inquiry to the PC.
(2) The PC answers the NT20S about the bit and word data.
(3) The NT20S changes the display status according to the bits and words obtained from the PC.
[NT20S operation example]
Lamp #0
Bit 010012
NT20S
Bit 010012?
TIM003?
DM0100 to DM0102?
Character-string memory table2
First word
Number of saved words : 3
Numeral memory table0
: DM0100 First word : TIM003
Number of saved words : 1
PC
(“a”, “b”)
(“c”, “d”)
(“e”, “f”)
153
Overview of Direct Connection Operations Section 5-1
Controlling the NT20S Status by Using Allocated Bits and Words ..... PT Status Control Area (PC to PT)
The PT status control area (PC to PT) is provided to control the NT20S status from the PC. When data is written to this area in the PC, the NT20S will read the data and operates according to the data. The PT status control area is configured as four consecutive words as shown below.
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit n n+1 n+2
0
Copy type
Screen # (4-digit BCD)
Copy source memory table # (3-digit BCD)
Copy destination memory table # (3-digit BCD)
Screen switch setting
Copy memory table setting n+3 PT status control bit 0 0 PT status control n+3 CH
The first word (word n) of the PT status control area must be set with the support tool.
S Screen switch settings (refer to page 157)
Specify the screen # to switch the screen displayed on the NT20S.
S
Copy memory table settings (refer to page 174)
Specify the memory table # to copy the contents of a memory table internally in the NT20S.
Set the copy type to match the type of memory table to be copied:
0: Character-string memory table
1: Numeral memory table
S PT status control bits (refer to page 191)
These bits are switched ON and OFF to control the NT20S buzzer and backlight.
15 14 13 12 11 10 9 8 Bit
0 0 0
Item Controlled
Screen display (Note 1)
Processing priority registration (Note 2)
1(ON)
ON
ON
0(OFF)
OFF
OFF
Continuous buzzer ON OFF
Intermittent buzzer ON OFF
Backlight mode ON Flash
Note 1:When “ON” is set for screen display, the backlight is on; when “OFF” is set for screen display, the backlight is off.
Note 2:Priority registration is only valid when NT link (1:N) is set.
154
Overview of Direct Connection Operations Section 5-1
The PT status control area (PC to PT) can be allocated to the following PC areas.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since the special auxiliary relays of the CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
Correct Use: Make sure there is no duplication in the PT status control area allocations and PT status notify area allocations.
Reference: When NT link (1:N) is set, the PT status control area must be set for each connected PT.
Notifying the Display Elements by Using Allocated Bits and Words
The NT20S will operate as follows in the display element notification operation.
[NT20S operation]
The NT20S will write any changes in the contents of the numeral or characterstring memory table being displayed or pressing of a touch switch to the bits and words area in the PC.
[NT20S operation example]
Touch switch #12
Bit009012
NT20S PC
Bit 009012:ON
DM0110:0432
Numeral memory table 100
0 4 3 2
Copy
Numeral memory table0
Number of saved words : 1
First word : DM0110
155
Overview of Direct Connection Operations Section 5-1
Notifying the NT20S Status by Using Allocated Bits and Words ..... PT Status Notify Area (PT to PC)
The PT status notify area (PT to PC) is provided to notify the NT20S status changes to the PC. When any NT20S status has changed, such change is written to this area in the PC, and the PC will read the data from this area to check the
NT20S status.
The PT status notify area is configured as three consecutive words as shown below.
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit m Screen # (4-digit BCD)
Screen being displayed m+1 m+2
0
PT status
Numeral memory table # (3-digit BCD)
0 0
Content upgrade memory table
PT status
The first word (word m) of the PT status notify area must be set with the support tool.
S Currently displayed screen (refer to page 160)
The screen number displayed on the NT20S is written to this word.
Simultaneously, the PT status screen switch strobe flag is set to ON (1). After this is notified to the PC, this flag reverts to OFF (0). Checking the status of this flag will provide a simple method of checking if the NT20S display has switched.
S
Content upgrade memory table (refer to page 188)
The number of the numeral memory table is written to the word when the numeral memory table contents change due to the touch switch operation on the
NT20S.
As the number of the numeral table is written, the PT status numeral setting strobe flag is simultaneously set ON (1). After this is notified to the PC, this flag reverts to OFF (0). Checking the status of this flag will provide a simple method of checking if a number has been input from the NT20S.
Note that this function is not available with the character-string memory table.
S PT status (refer to page 196)
The NT20S operation status and other information are written with the ON or
OFF of the bits as shown below.
Word m+2
PT status notify bits
15 14 13 12 11 10 9 8 Bit
0 0 0 0 0
PT operation status (1 (ON): RUN / 0 (OFF): STOP)
Screen switching strobe
Numeral setting strobe flag
156
Overview of Direct Connection Operations Section 5-1
The PT status control area (PC to PT) can be allocated to the following PC areas.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
Correct Use: Make sure there is no duplication in the PT status control area allocations and PT status notify area allocations.
Reference: When NT link (1:N) is set, the PT status control area must be set for each connected PT.
5-1-4 Switching the Screen Display
The following describes the procedure used to switch the NT20S screen display by controlling from the PC.
Reference: The display screen can be switched also by pressing a touch switch during the operation after registering a screen number to the touch switch. For this function, refer to the “Standalone Function“ (page 138).
To switch the NT20S screen display by controlling from the PC, write a screen number at the “screen switch setting” in the PT status control area.
NT20S PC
Word n
Designated screen
PT status control area
Screen switch setting
Copy memory table setting
PT status control setting
[Screen switch setting in the PT status control area]
PT status notify bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
Screen number (4-digit BCD) Screen switch setting
Screen number :0000 (screen clear, no-display)
:0001 to 0500
Screen number
157
Overview of Direct Connection Operations Section 5-1
S
Available allocation words
The PT status control area (PC to PT) can be allocated to the following PC areas.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f
Auxiliary Relay × f -f : OK ×: NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use. The range of respective area varies with the type of PC. Refer to Appendix L PC Memory Map
(page 278).
Procedure 1. Use the support tool to allocate the PT status control area (PC to PT) to the PC memory.
2. Create a PC program to write the number of the displayed screen to the
“screen switch setting word” in the PT status control area.
Use a 4-digit BCD (binary-coded decimal) value to set a screen number.
If a screen has been switched by operating the PT status control area (PC to PT), the contents of the “currently displayed screen word” in the PT status notify area
(PT to PC) also change.
S Screen switching timing
The NT20S screen switches when the contents of the “screen switch setting” have changed. To re-specify the number of the currently specified screen, first write the value 0000 to clear the screen before writing the appropriate screen number.
S
Use of the screen switching strobe
Create a program to read the number of the currently displayed screen and to write the number to the “screen switch setting word” at the leading edge of the
“screen switching strobe” of the PT status notify area. This program enables screen switching by using the touch switches on the NT20S and eliminates repeated setting of the same screen number. If the screen switching is not executed on the NT20S, the screen switching strobe does not need to be checked.
For the screen switching strobe, refer to the “notifying the displayed screen to the PC” mentioned below.
158
Overview of Direct Connection Operations Section 5-1
S
Continuous screens and overlapping screens
Continuous or overlapping screens can be displayed by designating the parent screen. If a child screen is designated, only the child screen is displayed.
For the continuous and overlapping screens, refer to the “Classification of
Screens” (page 122).
Example of Display Screen Switching
This example operates the PC switch (bit) to switch the NT20S display screen.
S Support tool settings
Make the following settings with the support tool:
PT status control area:
PT status notify area:
Word 0100
Word 0110
Screen number to be created: Screen #2 and #3
S
PC ladder program
Create a PC ladder program as follows:
00002
(1)
Screen number
Screen switch setting word
00003
@MOV(21)
#0002
100
@MOV(21)
#0003
100
(2)
Screen number
Screen switch setting word
11212
@MOV(21)
110
100
(3)
Screen number
Screen switch setting word
Screen switch strobe flag
S Program operation
(1) Screen #2 is displayed on the NT20S when bit 00002 turns ON.
(2) Screen #3 is displayed on the NT20S when bit 00003 turns ON.
(3) When the screen switch strobe flag turns ON, the number of the currently displayed screen is read and written to the currently displayed screen word in the
PT status notify area. In this case, the NT20S will not write the same screen twice.
159
Overview of Direct Connection Operations Section 5-1
5-1-5 Notifying the Display Screen to the PC
(To Display the Number of Currently Displayed Screen)
The following describes the processing to display the number of currently displayed screen of the NT20S.
This processing reads the data from the PC status notify area.
To indicate that the screen has switched, use the screen switch strobe flag.
To display the number of the currently displayed screen, use the currently displayed screen word.
When the screen has switched, the NT20S notifies the following to PT status notify area (PT to PC) allocated to the PC.
Screen switch notification:
New screen number:
Screen switch strobe flag of the PT status word
Currently displayed screen word
By reading the currently displayed screen word when the screen switch strobe flag has turned ON, the number of the currently displayed screen on the NT20S is displayed.
NT20S
Currently displayed screen
PC
PT status notify area
Currently displayed screen
Content upgrade memory table
PT status
Screen number
Screen switch strobe flag
[Currently displayed screen] and [PT status] words in the PT status notify area
Word m
15 1413 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
Screen number (4-digit BCD) Screen switch setting m+2 PT status 0 0 PT status
15 14 13 12 11 10 9 8 Bit
-0 0 -0 0 0
Screen switch strobe
Screen number: 0001 to 0500
Use a 4-digit BCD (binary-coded decimal) value to set a screen number.
The screen switch strobe bit reverts to OFF (0) after this is notified to the PC.
160
Overview of Direct Connection Operations Section 5-1
S
Available allocation words
The PT status notify area (PT to PC) can be allocated to the following PC areas.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since the special auxiliary relays of the CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 278).
Procedure 1. Use the support tool to allocate the PT status notify area (PT to PC) to the PC memory.
2. Create a PC program to read the “currently displayed screen word” in the in the
PT status notify area when the “screen switch strobe flag” in the PT status notify area has turned ON.
Reference: The contents of the “currently displayed screen word” are updated also by switching the screen by pressing a touch switch on the NT20S.
For this function (standalone function or screen switch function), refer to the “Standalone Function” (page 138).
S Continuous screens and overlapping screens
When a continuous or overlapping screen is displayed, the number of the parent screen is written to the “currently displayed screen word”.
For the continuous and overlapping screens, refer to the “Classification of
Screens” (page 122).
161
Overview of Direct Connection Operations Section 5-1
Example of Reading the Number of Currently Display Screen
This example gives a PC program that reads the screen number each time the screen is switched. In this example, the number of the previous screen is also stored.
S Support tool settings
Make the following settings with the support tool:
PT status notify area: Word 0110
S PC ladder program
11212
(1)
@MOV(21)
DM0100
DM0101
Screen switch strobe flag
@MOV(21)
110
DM0100
Word for storing the number of the previous screen
(2)
Word for notifying the number of the currently displayed screen
Word for storing a new screen number
S Program operation
(1) When the NT20S screen display switches and the screen switch strobe flag
(bit 11212) turns ON, the contents of DM0100 are transferred to DM0101.
The number of the previously displayed screen is stored in word 0101.
(2) The new screen number notified by the NT20S is read and transferred to
DM0100. The number of the currently displayed screen is stored in DM0100.
162
Memory Tables and Bar Graphs Section 5-2
5-2 Memory Tables and Bar Graphs
Displaying and Referencing Character String Memory Table Contents
Since the character-string memory tables can be allocated to the words in the PC, the PC can write data to the character-string memory tables or the initial values can be set when creating the screen data.
Automatic updating is performed to ensure that the currently displayed NT20S character string memory table contents and PC word contents always match each other.
There are two methods for referencing character string memory tables used for character string display, as follows:
- Direct specification
- Indirect specification (with Ver.5 direct connection only)
S Direct specification
Direct specification is a method of specification in which the contents of displayed memory tables are directly correlated with the contents of the allocated words.
NT20S a b c d
Direct specification
Character string memory table 51 a b c d
PC
Allocated channel
(character string memory table 51)
DM0100
6 1 6 2
6 3 6 4
S
Indirect specification (with Ver.5 direct connection only)
In indirect specification, even if the displayed data is a character string, the display is correlated with a numeral memory table. The contents (numerical value) of this numeral memory table are regarded as a character string memory table number and the contents of the table with this number are displayed.
Up to 50 numeral displays and 50 character string displays can be specified on one screen by using indirect specification.
NT20S PC a b c d
Indirect specification
Numeral memory table 20
0 0 5 1
Allocated word (numeral memory table 20)
DM0000
0 0 5 1
Character Allocated word (character string table 51) string memory table 51
DM0100 a b c d 6 1 6 2
6 3 6 4
163
Memory Tables and Bar Graphs Section 5-2
This specification method is a little complex, but it allows the display to be changed more easily according to the circumstances. In the example above, if 1 were added to the contents of memory table 20 to give 52, the contents of memory table 52 would be displayed instead.
The memory tables used for display can also be allocated to areas in the PC, so that the display can also be changed in response to changes in the data to be displayed (i.e., the contents of character string memory table 51 in the example above).
However, in comparison with direct specification, indirect specification requires more time for processing.
Setting the Words of the Character-String Memory Table
When creating the screen data by using the support tool, make the following settings for each numbered character string:
S
Initialization setting
Set whether or not the PC words are initialized with the character-string memory table initial value registered to the screen data memory when the main power supply is turned ON or reset.
S Number of registration words
Set the number of words within 16 words required for registering the characterstring data. One word can store two normal-size characters.
S
Setting the words for the character-string memory tables
The character-string memory tables can be allocated to the following PC words.
Set the word type and the first word.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f f
Internal/Special Relay
Timer
Counter
--
Auxiliary Relay f
×
×
× f
-f : OK ×: NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
If the “number of registration words x 2” (“word setting window”) set with the support tool is larger than the “number of character digits” (“character-string display setting” window), the character string may be broken halfway.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 278).
164
Memory Tables and Bar Graphs Section 5-2
Displaying and Referencing Numeral Memory Table Contents
Since the numeral memory tables can be allocated to the words in the PC, the PC can write data to the numeral memory tables or the initial values can be set when creating the screen data.
Also, by relating the numeral memory tables with the bar graphs, the bar graphs corresponding to the data of the numeral memory tables can be displayed.
During the operation, the display contents are automatically updated so that the contents of the numeral memory table being displayed are the same as that of the
PC word.
There are two methods for referencing numeral memory tables used for numeral displays, as follows:
- Direct specification
- Indirect specification (with Ver.5 direct connection only)
Reference: The only method available for numeral memory tables used for graphs and numeral settings is direct specification.
S
Direct specification
Direct specification is a method of specification in which the contents of displayed memory tables are directly correlated with the contents of the allocated words.
NT20S
0 0 6 2
Direct specification
PC
Character string memory table 18
0 0 6 2
Allocated channel
(character string memory table 18)
DM0100
0 0 6 2
S Indirect specification (with Ver.5 direct connection only)
NT20S
7 7 7 7
Indirect specification
Numeral memory table 18
0 0 6 2
PC
Allocated word
(numeral memory table 18)
DM0100
0 0 6 2
Character Allocated word (character string table 62) string memory table 62
DM0200
7 7 7 7 7 7 7 7
In indirect specification, the contents (numerical value) of the specified numeral memory table are regarded as a memory table number and the contents of the table with this number are displayed.
Up to 50 numeral displays and 50 character string displays can be specified on one screen by using indirect specification.
165
Memory Tables and Bar Graphs Section 5-2
This specification method is a little complex, but it allows the display to be changed more easily according to the circumstances. In the example above, if one were added to the contents of memory table 18 to give 63, the contents of memory table
63 would be displayed instead.
The memory tables used for display can also be allocated to areas in the PC, so that the display can also be changed in response to changes in the data to be displayed (i.e., the contents of character string memory table 62 in the example above).
However, in comparison with direct specification, indirect specification requires more time for processing.
Setting the Words of the Numeral Memory Table
When creating the screen data by using the support tool, make the following settings for each numbered numeral:
S
Initialization setting
Set whether or not the PC words are initialized with the numeral memory table initial value registered to the screen data memory when the main power supply is turned ON or reset.
S Number of registration words
Set the number of words within 2 words required for registering the numeral data. One word can store up to 4 digits. Two words can store up to 8 digits.
S
Setting the words for the numeral memory tables
The numeral memory tables can be allocated to the following PC words. Set the word type and the first word.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
Internal/Special Relay
Timer
Counter f f f f
--
Auxiliary Relay
--
× f
: OK : 1 word only ×: NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 278).
166
Memory Tables and Bar Graphs Section 5-2
5-2-1 Displaying the Contents of Allocated Words of Memory Tables
The relationship between the contents of the allocated words of numeral and character string memory tables and the display is described below.
S Contents of the numeral memory tables
Numerals are stored in the allocated words as shown below.
[Stored as a single word]
15 to 12 11 to 8 7
Digit 4 Digit 3 to 4 3
Digit 2 to 0 Bit
Digit 1
Example: 1234
15 to 12 11 to 8 7
1 2 3 to 4 3
4 to 0 Bit
[Stored as a double words]
Word
Start
Start+ 1
15 to 12 11 to 8 7 to 4 3 to 0 Bit
Digit 4 Digit 3 Digit 2 Digit 1
Digit 8 Digit 7 Digit 6 Digit 5
Example: 12345678
Word
Start
Start+ 1
15 to 12 11 to 8 7 to 4 3 to 0 Bit
5 6 7 8
1 2 3 4
S Displaying the numeral memory table
Numerals can be displayed in three different ways according to the contents of the numeral memory table, as mentioned below.
The most significant digit (digit 4 of a single word or digit 8 of a double word) is processed in different ways.
Hexadecimal display: All digits are handled as stored in the allocated words.
Decimal display without signs: If the most significant digit is “F”, it is handled as “0”, and the most significant digit other than
“F” and other digits are handled as stored in the allocated words.
Decimal display with signs: If the most significant digit is “F”, it is handled as “--” (minus sign), and the most significant digit other than “F” and other digits are handled as stored in the allocated words.
167
Memory Tables and Bar Graphs
[Numeral memory table display examples]
S
When the data are numeral data (0 to 9)
Start
Start + 1
3 4 5 6
F 0 1 2
Decimal without sign 123456
Decimal with sign --123456
Hexadecimal F0123456
Section 5-2
S
When the data contain characters (A to F)
Start
Start + 1
3 B 5 6
F 0 1 2
Decimal without sign 123B56
Decimal with sign --123B56
Hexadecimal F0123B56
If the hexadecimal data (A to F) are stored when the decimal display has been set, the alphabets are displayed.
If the number of display digits has been set to be smaller than the maximum number of digits of the registration words (4 digits for 1 word; 8 digits for 2 words), the contents of the allocated words are not displayed and “ at all digits.
£ ” symbols will be displayed
If the most significant digit is “F” when “decimal with signs” has been set, the numeral is handled as a negative number. The maximum number of digits of the negative number becomes smaller than that of the positive number by 1 digit.
The actual display will vary according to the “zero suppress” setting and decimal fraction setting as well as the contents mentioned above. Refer to the “NT-series
Support Tool Operation Manual” (V028-E1-j).
S Contents of the character-string memory table
A character string is stored in the allocated words beginning with the first word in normal-size characters.
Two normal-size characters are stored in one word. One memory table can store up to 16 words (32 characters).
Start Start + 1
Code 1 Code 2 Code 3 Code 4
Start + 15
Code31 Code32
[Character-string memory table display example]
To display the characters in order, allocate the characters as follows.
“A”=41H, “B”=42H Start
“C”=43H, “D”=44H Start + 1
“E”=45H, “F”=46H Start + 2
“G”=47H, “G”=48H Start + 3
4 1 4 2
4 3 4 4
4 5 4 6
4 7 4 8
“ABCDEFGH”
168
Memory Tables and Bar Graphs Section 5-2
5-2-2 Changing Displayed Numerals or Character Strings
(Changing the Contents of Allocated Words ... Direct Specification)
The following explains the actual procedure for changing the contents of allocated words referenced by direct specification in order to change numerical values and character strings displayed by the NT20S.
For the situation when using indirect specification, see “Changing Displayed Numerals Values or Character Strings (Changing the Contents of Allocated Words ...
Indirect Specification)” (page 171).
Numerals and character strings can be changed also by making a copy of the memory tables. Refer to “Copying the memory table” explained later.
To change the numerals or character strings displayed on the NT20S, make changes with the numeral or character-string memory table. To make changes with the numeral or character-string memory table of the NT20S, change the contents of words by the PC.
NT20S
12345678 abcdef
Numeral table 1
12345678
Character-string memory table 4 abcdef
PC
Allocated word
(numeral table)
Start
Start+1
Start
Start+1
Start+2
Allocated word (character-string memory table)
61 62 63 64 65 66
(“a b c d e f”)
Reference: This method is convenient when changing data has to be displayed: for example when monitoring the contents of PC words.
Procedure 1. Use the support tool to allocate the numeral and character-string memory tables to the PC memory.
2. Register the memory tables for the numerals and character strings to be displayed when creating the screen data by using the support tool. Specify “direct” as the reference method.
To display a character string, use “character display” and specify the character-string memory table by using the support tool.
To display numerals, use “numeral display” and specify the numeral memory table by using the support tool.
3. Create a PC program to write the contents of numerals and character strings to be displayed on the NT20S to the PC words.
S Important points when writing a character string
If a character string to be written is smaller than “allocated word x 2”, fill up the vacant space with normal-size spaces (20H). If unnecessary characters are left in the area, the character string will not be displayed correctly.
169
Memory Tables and Bar Graphs Section 5-2
Application Example of the Numeral Memory Tables Allocated to the PC Words
This example gives the procedure to directly display the contents of the words allocated as the numeral memory tables in the PC memory. The NT20S screen display will change as the contents of the PC word change.
S Support tool settings
Allocate the memory as shown below by using the support tool.
Numeral memory table entry #1: DM0000 (allocated words: 2 words)
Numeral memory table entry #2: DM0002 (allocated words: 1 word)
Screen numbers to be created: #1 and #2
Line 1
Numeral memory table entry #1
(8-digit input)
Qty.
Defects
15289 units
23 units
Numeral memory table entry #2
(4-digit input)
S PC ladder program
Create a PC ladder program as follows:
25502 (1 second clock)
DIFU(13)
00100
00100
INC(38)
DM0000
25506 (=)
INC(38)
DM0001
00001
@INC(38)
DM0002
(1)
Word for least significant 4 digits of #1
(2)
Word for most significant 4 digits of #1
Word for #2
(3)
S Program operation
(1) The contents of word DM0000 are incremented by 1 each second. The value displayed on the NT20S in numeral memory table entry #1 increases by 1 each second.
(2) When the counter in (1) above causes an increase in the most significant digits, the contents of word DM0001 are incremented by 1 each second. The value displayed on the NT20S in numeral memory table entry #1 most significant digits increases by 1.
170
Memory Tables and Bar Graphs Section 5-2
(3) When bit 00001 turns ON, the contents of DM0002 are incremented by 1. The value displayed on the NT20S in numeral memory table entry #2 increases by
1.
5-2-3 Changing Displayed Numerical Values or Character Strings
(Changing the Contents of Allocated Words ... Indirect Specification)
The following explains how to change numerical values or character strings displayed by the NT20S by changing the contents of the referenced allocated words using indirect specification. This method can only be used with Ver.5 of the direct connection function.
If using direct specification, see “Changing Displayed Numerical Values or Character Strings (Changing the Contents of Allocated Words ... Direct Specification)”
(page 169).
Numerical values and character strings can also be changed by making a copy of the memory tables. Refer to “Copying the memory table” (page 174).
In indirect specification, a numeral memory table is specified to display a numerical value or character string. The numerical value stored in this numeral memory table (“39” in the figure below) is taken as the number of the memory table whose contents are to be displayed.
Either of the following two methods can be used to change the display when indirect specification is used:
1) Changing the memory table number for the memory table whose contents are to be displayed
(In the example in the figure below, this would mean changing the contents of numeral memory table 41.)
2) Changing the contents of the memory table used for display
(In the example in the figure below, this would mean changing the contents of character string memory table 39.)
Here, the method for changing the display using method 1) is explained. For details on method 2), see the explanations on direct specification (page 169) and copying memory tables (page 174).
NT20S PC
AaBb
Indirect numeral memory table 41
0039
Allocated word
(numeral memory table 41)
0 0 3 9 0039
Character string memory table 39
AaBb
Character string memory table 40
Moji
Reference: This method is convenient when switching the display at the same location, for example when monitoring a series of words, or when using unique codes to specify individual character strings, etc.
171
Memory Tables and Bar Graphs Section 5-2
Procedure 1. Set the PC area for allocation of the numeral memory table to be referenced in indirect specification using the support tool.
2. When using the support tool to create screen data, register on the screen the numeral memory table referenced in indirect specification. Specify the “indirect” option for the reference method.
In the case of a character string, use the “character display” function of the support tool to specify the numeral memory table.
In the case of a numerical value, use the “numeral display” function of the support tool to specify the numeral memory table.
3. Use the “table edit” function of the support tool to write the actually displayed data to the memory table for display. If displaying a numerical value, use a numeral memory table and if displaying a character string use a character string memory table.
4. Create a PC program to change the contents of the word allocated to the numeral memory table referenced in the indirect specification.
S Notes on writing memory table numbers
When writing the number of the memory table for display to the numeral memory table referenced in indirect specification, always specify it in BCD. Also, be sure to specify a number within the range of memory table numbers that actually exist
(0 to 127).
If the contents of the numeral memory table for indirect specification are specified in hexadecimal format, or the number specified is outside the valid range for memory table numbers, the display is not updated.
S Notes on writing character strings
The points to note when displaying character strings are the same as those described for direct specification. See “Important points when writing a character string” (page 149).
172
Memory Tables and Bar Graphs Section 5-2
Example Use of Indirect Specification
This example shows a case where the displayed character string is changed by incrementing the contents of the allocated word of the numeral memory table referenced in indirect specification.
S Settings with the support tool
Make the following settings with the support tool.
Numeral memory table number 51: DM 0000 (number of registered words: 1)
Character string memory table number 100: “NT610G” (6 digits)
Character string memory table number 101: “NT610C” (6 digits)
Character string memory table number 102: “NT20S ” (6 digits)
Character string memory table number 103: “NT600S” (6 digits)
Data registered for the screen: numeral memory table number 51.
Line 1
Product
NT20S
Numeral memory table number 51 specified in indirect specification of character string display
S PC program
Create the PC ladder program as follows:
00100
@INC(38)
DM0000
(1)
Numeral memory table number used in indirect specification
00101
@DEC(39)
DM0000
(2)
Numeral memory table number used in indirect specification
S Program operation
(1) Each time contact 00100 comes ON, the display on the NT20S screen changes in accordance with one of the steps in the following sequence:
“NT610G” → “NT610C” → “NT20S” → “NT600S”.
(2) Each time contact 00101 comes ON, the display on the NT20S screen makes changes in accordance with one of the steps in the following sequence: “NT600S” → “NT20S” → “NT610C” → “NT600S”.
In this example, the contents of numeral memory table number 51 referenced in indirect specification are not checked. Make sure that the contents of numeral memory table number 51 stay within the range of 0100 to 0103 when the program is actually used.
173
Memory Tables and Bar Graphs Section 5-2
5-2-4 Copying the Memory Table
The following describes the procedure to change displayed numerals or character strings by copying the contents of the memory table.
Numerals and character strings can be changed also by changing the contents of the allocated words. Refer to “Changing Displayed Numerals or Character
Strings” (page 169) explained before.
To change the numerals or character strings displayed on the NT20S, copy the data between the numeral or character-string memory tables by using the “copy memory table setting” of the PT status control area.
A
NT20S
Memory table copy source
A
A
Copy destination
(for display)
PC
PT status control area
Screen switch setting
Copy memory table setting
PT status control setting
Copy source number
Copy destination number
Write a memory table number etc. to the copy memory table setting area in the PT status control area in the PC memory. Data will be copied between the memory tables in the NT20S and the displayed value will change accordingly.
Reference: This procedure is convenient to switch predetermined values or character strings according to the situation. By preparing several units of contents, various contents can be displayed by switching them to suit the situation.
[“Copy memory table setting” of the PT status control area]
Word n+1 n+2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0 Copy source memory table # (3-digit BCD)
Copy type Copy destination memory table # (3-digit BCD)
Copy memory table setting
Copy type:
0: Copy between the character-string memory tables
1: Copy between the numeral memory tables
Copy source and destination memory table numbers: 000 to 127
S Available allocation words
The PT status control area can be allocated to the following PC areas:
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
174
Memory Tables and Bar Graphs Section 5-2
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 278).
Procedure 1. Use the support tool to allocate the PT status control area (PC to PT) to the PC memory.
2. Register the memory tables for the numerals and character strings to be displayed when creating the screen data by using the support tool.
To display a character string, use “character display” and specify the character-string memory table by using the support tool.
To display numerals, use “numeral display” and specify the numeral memory table by using the support tool.
3. Set the copy source data to the memory table when creating the screen data by using the support tool.
Use “table edit”.
4. Create a PC program to write the copy type, copy destination memory table number, and copy source memory table number to the “copy memory table” setting word in the PT status control area.
S
Order for writing to the PT status control area (PC to PT)
First write the “copy destination memory table number”, and then, write the
“copy source memory table number” to the PT status control area (PC to PT).
The NT20S reads the area sometimes when the PC is writing the settings. If the
“copy source memory table number” has been written first and is changed, unexpected memory table may possibly be changed.
S
Allocated words that the NT20S reads
The NT20S reads the allocated words in the PC for the memory tables which need to be displayed. Even when a copy source memory table is allocated to a
PC word, if its contents are never displayed it will be used only at initialization.
S Use of the “copy type”
Copy will not be executed when the “copy type” is other than “0” or “1”. The memory table copy is executed only when the contents of the area are changed.
To repeat copying of the same copy source and same copy destination, write a value other than “0” or “1” for the copy type, and then, write a correct value again.
S Copying a numeral memory table
If the display method or the number of registered words include discrepancies, a numeral memory table may not be copied and displayed correctly.
175
Memory Tables and Bar Graphs Section 5-2
Application Example of Copying of a Character-String Memory Table
This example gives a PC program to switch the character string display on the screen by using the memory table copy operation as the allocated bit is turned ON and OFF.
S Support tool settings
Allocate the memory as shown below by using the support tool.
PT status control area allocation: Word 0100
Contents registered to the screen: Character-string memory table #4
Line 1
Normal
Character-string memory table #4
Character-string memory table settings
#
4
10
11
Contents
Normal
Error
Normal
Number of
Character Digits
6 digits
6 digits
6 digits
S PC ladder program
Create a PC ladder program as follows:
09000
@MOV(21)
#0004
102
Copy type, copy destination memory table #
(1)
Copy destination word
Error flag
09000
@MOV(21)
#0010
101
@MOV(21)
#0004
102
Copy source memory table #
Copy source word
Copy type, copy destination memory table #
(2)
Copy destination word
Error flag @MOV(21)
#0011
101
Copy source memory table #
Copy source word
S Program operation
(1) When an error occurs (bit 09000 turns ON), the NT20S displays the message
“Error”.
(2) When the error is cleared (bit 09000 turns OFF), the NT20S display message reverts to “Normal”.
176
Memory Tables and Bar Graphs Section 5-2
5-2-5 Upgrading Bar Graphs
(Changing the Contents of Allocated Words)
The following describes the procedure to upgrade the bar graph display on the
NT20S by changing the contents of the allocated words.
To change the bar graph display on the NT20S, change the contents of the PC words to which the numeral memory tables have been allocated.
The bar graph display cannot use hexadecimal numbers. If hexadecimal numbers are set, the bar graph will not be displayed.
By writing a negative number (whose most significant digit is “F”) to the allocated word of a graph set as “Sign display “No””, the graph display will become 0 % and the % display will show “ £££ %”.
For the procedure to write numeral values to the allocated words of the numeral memory tables, refer to “Displaying the Contents of Allocated Words of Memory
Tables” (page 167).
For the procedure to change the contents of the numeral memory table (PC words), refer to “Changing Displayed Numerals or Character Strings (Changing the Contents of Allocated Words)” (page 169).
S Available allocation words
The numeral memory tables can be allocated to the following PC areas:
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
Internal/Special Relay
Timer f f f f
Counter
--
Auxiliary Relay
--
× f : OK : 1 word only ×: NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 278).
177
Lamps, Touch Switches, Numeral Setting Section 5-3
5-3 Lamps, Touch Switches, Numeral Setting
5-3-1 Allocation Bits and Display of Lamps
Lamps are controlled by allocating them to the PC bits. Set the area and bit number.
S Available allocation bits
The lamps can be allocated to the following PC areas:
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the system, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 278).
To set the data memory (DM), specify the word number and then the bit number
(00 to 15).
178
Lamps, Touch Switches, Numeral Setting Section 5-3
5-3-2 Turning ON (lit) and OFF (unlit) the Lamps
(Changing the Contents of Allocated Bits)
The following describes the procedure to change the lamp display status on the
NT20S by changing the contents of the allocated bits.
To change the lamp display status on the NT20S, turn ON and OFF the lamp control bit allocated in the PC.
NT20S PC
Lamp #1 Lamp #2
Lit Unlit
Allocated bit (Lamp #1)
1 1 (ON)
Allocated bit (Lamp #2)
2 0 (OFF)
The lamp bit indicates the lamp status as follows:
0 (OFF): Unlit
1 (ON): Lit (reverse display) or flashing
Procedure 1. Use the support tool to set the PC memory area where the lamp bit is to be allocated to.
2. Register the lamps to the screen when creating the screen data by using the support tool.
3. Create a PC program to turn ON/OFF the lamp bit.
Use the support tool to set the lamp display attributes whether the lamp is lit or flashing when the lamp control bit is turned ON.
179
Lamps, Touch Switches, Numeral Setting Section 5-3
Application Example to Make the Lamp Light or Flash
This example gives a procedure to control the bits to move a robot arm and turning the lamps ON and OFF.
S
Support tool settings
Allocate the memory as shown below by using the support tool.
Lamp #0: Word 000200 (output bit to raise robot arm), guide display message
“UP”
Lamp #1: Word 000201 (output bit to lower robot arm), guide display message
“DOWN”
Lamp #2: Word 000202 (output bit to rotate robot arm counterclockwise), guide display message “C/CLOCK”
Lamp #3: Word 000203 (output bit to rotate robot arm clockwise), guide display message “CLOCK”
Lamp #4: Word 000204 (output bit to clamp rotate robot arm), guide display message “CLAMP”
Lamp #5: Word 000205 (output bit to unclamp rotate robot arm), guide display message “UNCLAMP”
Contents registered to the screen: Lamp #0 to #5
Line 1 Process 3
Conveyor Loading Robot Arm
Raise:
Lower:
Counterclockwise: Lamp#2
Clockwise:
Clamp:
Unclamp:
Lamp#0
Lamp#1
Lamp#3
Lamp#4
Lamp#5
UP CLAMP
C/
CLOCK
CLOCK
DOWN
UNCLAMP
S PC ladder program
No PC ladder program is required to control the NT20S. Only a program to control the robot arm movements is required.
S NT20S operation
When the ladder program to control the robot arm is executed, the lamps on the
NT20S screen turn ON and OFF in synchronization with the robot arm movement.
For example, lamp #0 lights when the robot arm moves up and goes out when it stops moving up.
180
Lamps, Touch Switches, Numeral Setting Section 5-3
5-3-3 Allocated Bits, and Display, of Touch Switches
Method for PC Notification and NT20S Control
Two types of bit can be allocated to touch switches: notify bits - which serve to notify statuses to the PC - and control bits, lamp bit, which control the lighting
(flashing) of the touch switches. (For other types of function, only lamp bits can be allocated.) When a touch switch is pressed the notify bit status changes and, when the lamp bit is ON, the touch switch lights (or flashes).
Press
START abcde
NT20S
Notification bit
1
Control
1
←1
PC
Lights
In order to notify the status of a touch switch to the PC, the touch switch must be allocated to a specified PC bit so that it can be managed. Designate the area and bit number.
To use touch switches for notification to the PC, the following settings must be made using the support tool: “touch switch” -- “bit setting” -- “notify bit”.
S
Types of notification operation
When using Ver.5 of the direct connection function, the notification operation when the touch switch is pressed can be selected from the following four types
(with Ver.4 direct connection, the type is fixed as “momentary”):
- Momentary
When the touch switch is pressed the bit comes ON; when it is released the bit goes OFF.
- Alternate
Each time the touch switch is pressed, the bit status changes from ON to OFF or OFF to ON.
- Set
When the touch switch is pressed, the bit comes ON and remains ON even if the switch is pressed again.
- Reset
When the touch switch is pressed, the bit goes OFF and remains OFF even if the switch is pressed again.
181
Lamps, Touch Switches, Numeral Setting
S
Notes on the Notification Operation
The touch switch notification operations are as follows:
Type of Notification
Operation
Momentary
Alternate
Set
Reset
When Using Host Link or
NT Link with DM Area
(1)Notification in word units
(other bits go OFF)
(2)Notification in word units
(however, the word contents are read on display and notification is based on this reading)
When Using C200H Direct
Communication or NT Link with other than DM Area
(3)Notification in bit units
(4)Notification in bit units
When using touch switch input notification, note the following points:
- In the case of (1), the other bits in the same word as the notification bit are turned OFF by the notification operation.
- In the case of (2), notification is executed on the basis of the contents of the word before display, which means that the other bits are not rewritten. However, if the word contents are changed at the PC side, they will be rewritten based on the contents before display.
- If the screen is switched while a momentary key is being pressed, the touch switch itself disappears, so the status “OFF” is notified. In the case of (1) this means that the other bits in the word will also be turned OFF.
- When using the host link, or NT link with the DM area, do not allocate momentary touch switches and other types of touch switch to the same word, since the notification operations are different.
In the case of (3) and (4), the notification operation has no influence on the other bits in the word.
S
Possible bit allocations
Notify bits and lamp bits for touch switches can be allocated to the areas of the
PC memory listed in the following table.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since all the CVM1/CV-series special auxiliary relays are allocated to the system, they cannot be used for applications not related to the system.
The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 278 of the APPENDICES) for more details.
When making a data memory (DM) specification, specify the bit number (00 to 15) following the word number.
182
Section 5-3
Lamps, Touch Switches, Numeral Setting Section 5-3
5-3-4 Lit (Flashing) and Unlit Touch Switch Statuses
(Changing the Status of Allocated Bits)
This section describes how to change the statuses of allocated bits and thereby the statuses of the touch switches displayed by the NT20S.
The statuses of touch switches displayed by the NT20S are changed by switching the control bits allocated in the PC memory ON and OFF.
NT20S PC
Allocated bit (touch switch #1)
1 1 (ON)
Lit
Touch switch #1
The status of the lamp bit reflects the touch switch status, as follows:
0 (OFF): Unlit
1 (ON): Lit (inverse display) or flashing
Procedure 1. Use the support tool to allocate the touch switch lamp bits to the PC memory.
2. When creating the screen data using the support tool, register the touch switch for a screen.
3. Create the PC program to switch the lamp bit of the touch switch ON and OFF.
Set whether the lamp lights continuously or flashes when the bit comes ON by setting the touch switch display attribute with the support tool.
5-3-5 Notifying the Host that a Switch has been Pressed
(Determining Touch Switch Status)
This section describes how the status of a touch switch (whether it has been pressed or not) is ascertained.
With the NT20S, when a touch switch is pressed, the notify bit allocated to that touch switch in the PC memory is automatically notified.
Touch switch #1
NT20S PC
Allocated notify bit (touch switch #1)
1
183
Lamps, Touch Switches, Numeral Setting Section 5-3
Depending on the set operation type, the status of the allocated bit for touch switch status notification will be controlled in one of the following ways (unless Ver.4 direct connection is used, in which case the setting is fixed as “momentary”):
Momentary : 0 (OFF) ... Not pressed
:1 (ON) ... Pressed
Alternate
Set
Reset
: The allocated bit is switched to 1 (ON) if currently 0, and to 0
(OFF) if currently 1.
: The allocated notify bit is forcibly switched to 1 (ON).
: The allocated notify bit is forcibly switched to 0 (OFF).
In order to determine the status of a touch switch, the status of the touch switch notification bit allocated to it is determined.
The touch switch notify bits can be allocated to the following areas of the PC memory.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since all the CVM1/CV-series special auxiliary relays are allocated to the system, they cannot be used for applications not related to the system.
The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 278 of the APPENDICES) for more details.
When making a data memory (DM) specification, specify the bit number (00 to 15) following the word number.
Procedure 1. Use the support tool to allocate the touch switch notify bits to the PC memory.
2. When creating the screen data using the support tool, register the touch switch for a screen.
3. Create a PC program to determine whether the touch switch notify bit is ON or
OFF.
184
Lamps, Touch Switches, Numeral Setting
The touch switch notification operations are as follows:
Section 5-3
Type of Notification
Operation
Momentary
Alternate
Set
Reset
When Using Host Link or
NT Link with DM Area
(1)Notification in word units
(other bits go OFF)
(2)Notification in word units
(however, the word contents are read on display and notification is based on this reading)
When Using C200H Direct
Communication or NT Link with other than DM Area
(3)Notification in bit units
(4)Notification in bit units
When using touch switch input notification, note the following points:
- In the case of (1), the other bits in the same word as the notification bit are turned
OFF by the notification operation.
Bit 15 14
0 1
1 0
0 1
Press the touch switch
Bit 15 14
0 0
1
1
0
0
Touch switch notify bit
Bits other than notify bits are set to 0 (OFF).
- In the case of (2), notification is executed on the basis of the contents of the word before display, which means that the other bits are not rewritten. However, if the word contents are changed at the PC side, they will be rewritten based on the contents before display.
- If the screen is switched while a momentary key is being pressed, the touch switch itself disappears, so the status “OFF” is notified. In the case of (1) this means that the other bits in the word will also be turned OFF.
- When using the host link, or NT link with the DM area, do not allocate momentary touch switches and other types of touch switch to the same word, since the notification operations are different.
In the case of (3) and (4), the notification operation has no influence on the other bits in the word.
185
Lamps, Touch Switches, Numeral Setting Section 5-3
Example of determination of touch switch status
This example uses the touch switches as normal switches (bits) in order to use the
NT20S as an operating panel.
S
Support Tool Settings
Make the following settings using the support tool.
Touch switch #10:
Function “Notify Bit”
Display attribute “Light”
Control bit CH05000 (Run flag) ... Guide message: “RUN”
Notify bit CH 06000
Touch switch #11:
Function “Notify Bit”
Display attribute “Light”
Control bit CH 05000 (Stop flag) ... Guide message: “STOP”
Notify bit CH 06001
Data registered for the screen: touch switch #10, touch switch #11
Touch switch #10
Line 1
RUN
STOP
Touch switch #11
186
Lamps, Touch Switches, Numeral Setting
S
PC program
Create the following ladder program.
1 scan ON
↓
11212
Touch switch #10 notify bit
06000
↓
05001
Stop flag
(touch switch #11 control bit)
06001
← Touch switch #11 notify bit
05001
Touch switch #10 notify bit
↓
06000 06001
05000
05000
↑
Touch switch #11 notify bit
Run flag
(touch switch #10 control bit)
Section 5-3
S Program operation
The operation when the program is executed is presented below.
Execute program
Stop flag : 1 (ON)
Stop touch switch : Lit
Press Run touch switch.
Press Stop touch switch.
Run flag : 1 (ON)
Run touch switch : Lit
Stop flag : 0 (OFF)
Stop touch switch : Unlit
Run flag : 0 (OFF)
Run touch switch : Unlit
Stop flag : 1 (ON)
Stop touch switch : Lit
187
Lamps, Touch Switches, Numeral Setting Section 5-3
5-3-6 Notification of Numbers to the PC
The following describes how the numerical data input at the NT20S by using the numeral setting function is ascertained by the PC.
In order to determine when numerical data has been input at the NT20S, the numeral setting strobe flag in the PT status notify area is used. In order to determine the upgraded numeral memory table number, the “content upgrade memory table” in the PT status notify area is used.
When numerical data is input at the NT20S, this is automatically notified to the PT status notify area (PT → PC) allocated in the PC memory as follows.
Notification of upgrade: PT status numeral setting strobe flag turned ON (1)
Upgraded numeral table number: Stored in the “content upgrade memory table”
When the PC reads the “content upgrade memory table” at the leading edge of the numeral setting strobe flag, it determines the numeral memory table number in which the numerical data that was changed at the NT20S is stored.
12345678
NT20S PC
Numeral memory table 1
12345678
PT status notify area
Currently displayed screen
Content upgrade memory table
PT status
Allocated word (numeral table 1)
12345678 Start
Start + 1
Table No.
Numeral setting strobe flag
Word m+1 m+2
[“Content upgrade memory table” in the PT status notify area and PT status]
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0 Numerl memory table # (BCD, 3 digits) Content upgrade memory table
PT status 0 0 PT status
15 14 13 12 11 10 9 8 Bit
-0 0 -0 0 0 PT status
Numeral setting strobe flag
Numeral memory table #: 000 to 127
Data is written to the content upgrade memory table as three digits of BCD (binary coded decimal) data.
When the numeral setting strobe flag bit has been notified to the PC it returns to the
OFF (0) status.
For details on the method for storing a number in the word allocated for the numeral memory table, see “Displaying the Contents of Allocated Words of Memory
Tables” (page 167).
188
Lamps, Touch Switches, Numeral Setting Section 5-3
S
Restrictions on allocating words
The PT status notify area can be allocated to the PC memory areas listed in the following table.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f
Auxiliary Relay × f -f : OK ×: NG
Since all the CVM1/CV-series special auxiliary relays are allocated to the system, they cannot be used for applications not related to the system.
The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 278 of the APPENDICES) for more details.
Procedure 1. Use the support tool to allocate the PT status notify area (PT → PC) to the PC memory.
2. Using the support tool, create a numeral setting screen and allocate the numeral memory table to the PC memory.
3. Create a PC program for reading the “content upgrade memory table” in the
PT status notify area when the numeral setting strobe flag in the PT status notify area comes ON (1).
4. Read the allocated word for the numeral memory table number read in step 3.
189
Lamps, Touch Switches, Numeral Setting Section 5-3
Example of reading a numeral memory table into which a numerical value has been input
This example shows the reading of the numeral memory table number after a value has been changed by inputting numerical data at the NT20S.
S
Setting at the support tool
Make the following settings using the support tool.
Allocated word for the PT status notify area : CH0110
Numeral memory table entry No.3: DM 0005 (saved word: One)
Numeral memory table entry No.4: DM 0006 (saved word: One)
Data registered for the screens:
Numeral setting 1 ... Reference table “numeral memory table #3”
Numeral setting 2 ... Reference table “numeral memory table #4”
Numeral memory table entry number 3 (4-digit input)
Line 1
Qty.
800 unit
Defect limit 30 unit
1 2 3 4 5 6 7 8 9 0 CLR +/--
Numeral memory table entry number 4 (4-digit input)
S PC program
Create the following PC ladder program.
11211
@MOV(21)
111
DM0105
Numeral setting strobe flag
(1)
Notification word for content upgrade memory table
Word that stores the numeral memory table number
S
Program operation
(1) When the numeral setting strobe flag (bit 11211) comes ON (1), the contents of CH-0111 (the word where the content upgrade memory table is located) are transferred to DM 0105. The number of the numeral memory table that contains the upgraded data is stored in DM 0105 (in this case it is 0003 or 0004).
If the numeral memory table is allocated to a PC word, the value input to it can be read easily by referring to the allocated word.
In this case, the contents of numeral memory table #3 are stored in DM 0005 and the contents of numeral table #4 are stored in DM 0006.
190
NT20S Status Control Section 5-4
5-4 NT20S Status Control
The statuses of the NT20S can be controlled from the PC by writing control data to the “PT status control bits” of the PT status control area allocated in the PC memory.
Buzzer sounds
Screen off
NT20S PC
PT status control area
Screen switch setting
Copy memory table setting
PT status control bits Control data
5-4-1 Controllable NT20S Functions
[“PT status control bits” of the PT status control area]
Word n+3
15 1413 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
PT status control bits 0 0 PT status control designation
15 14 13 12 11 10 9 8 Bit
0 0 0
Item Controlled
Screen display
(Note 1)
1 (ON)
ON
0 (OFF)
OFF
Processing priority registration
(Note 2)
Continuous buzzer
Intermittent buzzer
ON
ON
ON
OFF
OFF
OFF
Backlight mode ON Flash
Note 1: The backlighting is on when the screen display bit is set to ON and off when the screen display bit is set to OFF.
Note 2: Priority registration is only valid when
NT link (1:N) is set.
The PC status control bits remain unchanged if the NT20S status is changed with the screen attributes or memory switches, which means that the statuses of the
PT status control bits do not match the actual status of the NT20S. For example, the buzzer may sound even though the setting for continuous buzzer bit 13 is
“OFF”.
In this kind of case, control the NT20S by using the PT status control bits.
191
NT20S Status Control Section 5-4
S
Screen display (bit 15)
The screen display bit is used to display and clear the screen to prevent “burn-in” on the CRT. Set bit 15 to 0 (OFF) to clear the screen. The backlight will also go
OFF at the same time.
When the screen has been cleared, the last displayed screen can be redisplayed either by turning Bit 15 ON, or by pressing a touch switch. The backlight will also light at the same time.
Note that if the screen is OFF by the backlight OFF or EL screen OFF function with Bit 15 ON (1), turn Bit 15 OFF (0) once and then turn it back ON (1) to redisplay the screen.
Reference: Instead of turning Bit 15 ON, a screen can be displayed by specifying its screen number. For details on screen switching, see “Switching the Screen Display”
(page 157).
S Priority registration for processing (NT link 1:N connections only) (bit 14)
It is possible to register one of the multiple PTs connected by the 1:N NT link method to have processing priority. The PT for which bit 14 is set ON (1) is given priority over the other PTs and has a higher response speed for display, touch switches, etc.
When bit 14 is turned OFF (0), this registration is canceled and the normal response speed is reinstated. If priority registration is set for more than one PT, the one for which the registration was made last will have priority.
By monitoring C200HX/HG/HE words, the unit number of the PT for which priority registration has been set can be confirmed. For details on the monitoring operation at the PC side, refer to the manual for the PC used.
[Connection to RS-232C port of C200HX/HG/HE]
Channel
CI0265CH (standard port)
CI0284CH (port A) (
CI0285CH (port B) ( )
)
)
) p )
Bit Function
0 Unit No.0 Communication in progress flag, ON when connected
1 Unit No.1 Communication in progress flag, ON when connected
2 Unit No.2 Communication in progress flag, ON when connected
3 Unit No.3 Communication in progress flag, ON when connected
4 Unit No.4 Communication in progress flag, ON when connected
5 Unit No.5 Communication in progress flag, ON when connected
6 Unit No.6 Communication in progress flag, ON when connected
7 Unit No.7 Communication in progress flag, ON when connected
8 Unit No.0 Priority registration lamp, ON when registered
9 Unit No.1 Priority registration lamp, ON when registered
10 Unit No.2 Priority registration lamp, ON when registered
11 Unit No.3 Priority registration lamp, ON when registered
12 Unit No.4 Priority registration lamp, ON when registered
13 Unit No.5 Priority registration lamp, ON when registered
14 Unit No.6 Priority registration lamp, ON when registered
15 Unit No.7 Priority registration lamp, ON when registered
( £ ) This is the port of the communication port.
192
NT20S Status Control Section 5-4
S
Continuous buzzer (bit 13) and intermittent buzzer (bit 12)
In the case of both buzzers, when the respective bit is ON the buzzer sounds and when it is OFF the buzzer does not sound.
The “continuous buzzer” sounds continuously without interruption.
The “intermittent buzzer” sounds for 0.5 seconds at 0.5 second intervals.
If both Bit 13 and Bit 12 are turned ON simultaneously, Bit 13 takes priority and the continuous buzzer is selected.
Another way to stop a buzzer sounding is to use a touch switch to which the buzzer stop attribute function is allocated.
Whether or not the buzzer actually sounds also depends on the setting of the
“buzzer” memory switch of the NT20S. For details on this setting, see “Using the
Buzzer” (page 92).
Besides using PT status control bit operations, the buzzer status can also be controlled by the screen attributes. The screen attributes are set by using the support tool. The functions that can be set using the screen attributes are the following:
Buzzer attribute: Set whether or not the buzzer will sound when the screen is displayed and, if it sounds, the type of buzzer.
S
Backlight mode (bit 8)
If bit 8 is turned ON when the screen is displayed (bit 15 = ON), the screen is made to flash using the backlight. When bit 8 is turned OFF, normal display is resumed.
When the screen is not displayed (bit 15 = OFF), the backlight mode is invalid.
It is possible to use NT20S switch settings to make the backlight go off automatically after a set time during which there have been no operations.
Besides using PT status control bit operations, the backlight status can also be controlled by the screen attributes. The screen attributes are set by using the support tool. The functions that can be set using the screen attributes are the following:
Backlight: Set whether the backlight will be continuously or intermittently lit when the screen is displayed.
193
NT20S Status Control Section 5-4
5-4-2 How to Control NT20S Functions
This section describes how to control the functions of the NT20S.
S Restrictions on allocating words
The PT status control area (PC → PT) can be allocated to the PC memory areas listed in the following table.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since all the CVM1/CV-series special auxiliary relays are allocated to the system, they cannot be used for applications not related to the system.
The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 278 of the APPENDIX L) for more details.
Procedure 1. Use the support tool to set the area at the PC used for allocation of the PT status control area (PC → PT).
2. Write a PC program for writing the control data into the “PT status control bit” of the PT status control area.
S
Timing for control of the PT status control bit
The PT status control bit is not read when the NT20S is started up. It is read, and control executed, only when the contents of the PT status control bit are read for the first time after the NT20S is started up.
Since NT20S status control is executed when the bit corresponding to the PT status control bit changes, in order to perform the same control again the corresponding bit must be specified again.
194
NT20S Status Control Section 5-4
Example of Use of PT Status Control Bit
The example below explains how operation with the PT status control bit can be used to use the NT20S like a warning lamp.
S Setting with the support tool
Make the following setting with the support tool.
Allocated word for PT status control area: CH 0100
S PC program
Create the PC ladder program as follows.
09002 09003
@MOV(21)
#A000
103
09003
Display screen, sound buzzer continuously
(1)
PT status control word
09002 09003
@MOV(21)
#9000
103
Display screen, sound buzzer continuously
PT status control word
(2)
@ANDW(34)
103
#CFFF
103
(3)
PT status control word
“0” set for continuous and intermittent buzzer sounds only
PT status control word
S
Program operation
(1) The PT status control bits are set as shown below when bit 09002 turns OFF.
This command block is not executed when bit 09003 is ON.
Screen display (bit 15)
Continuous buzzer (bit 13)
1 (ON)
1 (ON)
The NT20S continuous buzzer sounds.
(2) The PT status control bits are set as shown below when bit 09003 turns OFF.
Screen display (bit 15)
Intermittent buzzer (bit 12)
Continuous buzzer (bit 13)
Intermittent buzzer (bit 12)
The NT20S buzzer stops.
1 (ON)
1 (ON)
The NT20S intermittent buzzer sounds.
(3) The PT status control bits are set as shown below when both bits 09002 and
09003 turn ON.
0 (OFF)
0 (OFF)
195
Notification of the Operating Status to the PC Section 5-5
5-5 Notification of the Operating Status to the PC
(Determining the NT20S Operating Status)
The status (operating statuses, etc.) of the NT20S can be determined from the PC by reading the “PT status” word in the PT status notify area allocated in the PC memory.
NT20S
PT stopped
Screen number
PC
PT status notify area
Currently displayed screen
Content upgrade memory table
PT status
5-5-1 Ascertainable NT20S Statuses (Notified Operating Statuses)
[“PT status notification bits” of the PT status notify area]
Word m+2
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
PT status notification bits 0 0 PT status
15 14 13 12 11 10 9 8 Bit
0 0 0 0 0
PT operating status
(1(ON) = operating / 0 (OFF) = stopped)
Screen switch strobe flag
Numeral setting strobe flag
Caution: Make the settings so that the PT control area and PT status notify area do not overlap.
S PT operating status (bit 15)
When the NT20S is in the RUN mode this bit is set to ON (1). In other modes and while the system menu is displayed it is OFF (0). When this bit is OFF allocated bits and words cannot be read or written to.
During the run mode, ON (1) is periodically written into this bit. In order to check whether the NT20S is operating normally or not, write OFF (0) to this bit: if it is
ON (1) 30 seconds later the NT20S is running, and if it is OFF (0), the NT20S is stopped.
Caution: To ensure system safety, be sure to periodically read the PT operating status bit from the host in order to ensure that the PT is always operating normally.
196
Notification of the Operating Status to the PC Section 5-5
S
Screen switch strobe flag (bit 12)
When the screen displayed on the NT20S is switched by a designation from the
PC or by the standalone function, the screen switch strobe flag comes ON (1).
On notification to the PC, it returns to the OFF (0) status.
For details on how the screen switch strobe flag is used, see “Notifying the Display Screen to the PC” (page 160).
S
Numeral setting strobe flag (bit 11)
When numerical data is input to a numeral memory table using the NT20S numeral setting function, the numeral setting strobe flag comes ON (1). On notification to the PC, it returns to the OFF (0) status.
For details on how the numeral setting strobe flag is used, see “Notification of
Numbers to the PC” (page 188).
5-5-2 Reading the NT20S Operating Statuses
This section explains how to determine the status of the NT20S, and ascertain its operating status.
To ascertain the operating status of the NT20S, “PT status” is used.
The NT20S automatically notifies information such as the operating status to the
PT status word of the PT status notify area (PT → PC) allocated to the PC memory as shown below.
Notification of operation mode: PT operating status
Notification of screen switching: Screen switch strobe flag
Notification of numerical data upgrade: Numeral setting strobe flag
S Restrictions on allocating words
The PT status notify area (PT → PC) can be allocated to the PC memory areas listed in the following table.
Symbol
DM
CH
TIM
CNT
HR
AR
LR
C Series PCs
Data Memory
Internal/Special Relay
Timer
Counter
Holding Relay
Auxiliary Relay
Link Relay
Allocated CVM1/CV Series PCs Allocated f
Data Memory f f
×
× f
Internal/Special Relay
Timer
Counter
-f
×
× f f
Auxiliary Relay
--
× f : OK ×: NG
Since all the CVM1/CV-series special auxiliary relays are allocated to the system, they cannot be used for applications not related to the system.
The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 278 of the APPENDIX L) for more details.
Procedure 1. Use the support tool to allocate the PT status notify area (PT → PC) to the PC memory.
2. Write a PC program to read the “PT status” word of the PT status notify area and check each bit status.
197
Notification of the Operating Status to the PC Section 5-5
S
Timing of PT status notify bit notification
The contents of the PT status notify area (PT → PC) are written to the PC whenever the status of the NT20S changes during operation.
Example of PT Status Notify Bit Application
In the example below, the status of the NT20S is checked by PT status notify bit notification.
S Settings with the support tool
Make the following setting with the support tool.
Allocated word for PT status notify area: CH0110
S PC program
Create the following PC ladder program.
11215
@MOV(21)
#0001
DM0001
11215
PT stopped
Word that stores the PT status
@MOV(21)
#0002
DM0001
PT running
Word that stores the PT status
(1)
(2)
S Program operation
(1) When the PT operating status (contact 11215) is OFF (0), “1” (PT stopped) is stored in DM0001.
(2) When the PT operating status (contact 11215) is ON (1), “2” (PT running) is stored in DM0001.
198
SECTION 6
Using the RS-232C
This section explains how to carry out communication via the RS-232C interface used with an NT20S-ST128, focusing on the commands.
Table of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 RS-232C Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-1 Communication Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-2 Precautions
6-2 Screen Display
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Memory Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Lamps, Touch Switches, Numeral Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-1 Notification and Control of Touch Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4-2 Notification of numeral setting input and touch switch status . . . . . . . . . . . . . . . . . . . .
6-5 Controlling the NT20S Status
6-6 Terminal Commands
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7 Key to Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7-1 Use of Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EXAMPLE PROGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
200
201
201
203
204
205
208
208
212
214
216
222
222
223
199
Table of Commands
Table of Commands
Operating Commands
Type
Screen control
Memory table operation
Lamp and Touch
S p
Switch Display
Touch Switch and
Function Key Input
Notification
Command
[ESC] 0
[ESC] X
[ESC] B
[ESC] C
[ESC] D
[ESC] /
[ESC] K
[ESC] Q
[ESC] R
[ESC] U
[ESC] V
[ESC] P
[ESC] T
[ESC] W
[ESC] Y
[ESC] E
[ESC] F
[ESC] S
[ESC] J
[ESC] H
Name
Display Specified Screen
Request Screen Number
Write Character-string Memory Table
4-digit Write Numeral Memory Table
8-digit Write Numeral Memory Table
Copy Memory Table
Lamp and Touch Switch Display (Bit Specification)
Lamp and Touch Switch Display (Number Specification)
Lamp and Touch Switch Display Status Enquiry
Touch Switch Disable
Touch Switch Enable
Screen Display Control
Buzzer Control
System Menu Display Permission
Screen Number Response
4-digit Number Input Notify
8-digit Number Input Notify
Lamp and Touch Switch Display Status Response
Touch Switch Bit Output (from NT20S to Host)
Touch Switch Number Output (from NT20S to Host)
Terminal Commands
Type
Character Size
Character Display
Attributes p y
Character String
Display g
Command
[ESC] &
[ESC] )
[ESC] *
[ESC] !
[ESC] ”
[ESC] #
[ESC] $
[ESC] %
[ESC] +
[ESC] 4
[ESC] 7
[ESC] 8
Clear Screen
Character Specify Size
Specify Character Enlargement
Normal Display
Set Inverse Display
End Inverse Display
Set Flashing Display
End Flashing Display
Set Cursor Position
Specify Displayed Characters
Draw Polyline
Draw Circle
Name
Section 6-1
219
219
220
220
221
221
Page
216
217
217
218
218
218
215
215
215
205
212
210
210
211
214
214
212
211
213
213
Page
204
204
205
206
206
207
200
RS-232C Interface Unit Communications Section 6-1
6-1 RS-232C Communications
This section describes the communication procedure when using an
NT20S-ST128 (RS-232C), and program flow using examples in BASIC.
6-1-1 Communication Procedure
The Host and NT20S communicate according to the following procedure.
1, 2, 3...
1. The RS-232C circuit must be opened (i.e., communication enabled) before communication can start.
2. Commands are used to control the PT and to receive notification from the
NT20S.
3. Close the RS-232C circuit again after communication is complete.
NT20S operation Host program
OPEN command
PRINT # command
Open circuit
Send instruction
RS-232C circuit
Open status
Send instruction
Receive instruction
LINE INPUT # command
CLOSE command
Send instruction
Close circuit
OPEN
PRINT #
LINE INPUT #
CLOSE
After a circuit has been opened, it can be used until it is closed again.
Opens the RS-232C circuit. The Host communication conditions are also set.
Refer to (3-5-4) Setting RS-232C Communication Conditions.
Sends an instruction via the RS-232C circuit to the NT20S.
Receives a command from the NT20S. [LINE INPUT] is used when receiving input delimited by commas (,) or double quotation marks (”).
Closes the RS-232C circuit.
Refer to the Host’s BASIC Manual for more details about the commands.
201
RS-232C Interface Unit Communications Section 6-1
Operation by Operating Commands
The operating commands display monitored data from the production line and messages to the factory workers. They are also used for NT20S control and management.
The communication flow between the Host and NT20S differs according to the following three cases:
Message from Host to NT20S
Host program NT20S operation
Message operating command
Message to PT Process message
Enquiry from Host to NT20S
Host program
Enquiry
Receive command
Notification of Operation at NT20S to the Host
Host program
Receive notification
Enquiry operating command
Response operating command
NT20S operation
Receive command
Send response command
Notification operating command
NT20S operation
Send notification command
Operation by Terminal Commands
The terminal commands allow the NT20S to be used as a terminal of the Host to display text and graphics independently of the screens stored in the NT20S.
The Host sends a command and the NT20S processes the message. The NT20S does not send back a response to the Host.
Host program
Message to PT
Terminal command
NT20S operation
Process message
202
RS-232C Interface Unit Communications Section 6-1
6-1-2 Precautions
Command Length
Some important points to consider when using commands are listed below.
If a mistake during command specification results in a command being too long, the correct length of the command is executed and the remainder is ignored.
A timeout error results if a mistake during command specification results in a command being too short.
Interval Between Transmitted Commands
As a small number of bytes is transmitted by the Host, the interval between transmissions should not exceed 5 seconds if a command is divided up for transmission. A timeout error occurs if the interval between transmissions exceeds 5 seconds.
When commands are sent too frequently, a buffer overflow error may occur if the
NT20S cannot keep up with the command processing.
In order to prevent buffer overflow, use flow control.
Controlling PT Status with Operating Commands
Control of the NT20S status by the operating commands is restricted by the
NT20S memory switch settings as listed below.
Operating command
Buzzer control command [ESC] T
Restriction from memory switch setting
Effective when “buzzer turned on”
Coordinate Specification with the Terminal Commands
The entire command is ignored if any point specified at coordinates X, Y with the
Terminal commands lies outside the screen.
Error display If the “automatic reset after communication” memory switch of the NT20S is set to
ON, no message is displayed when a communication error occurs.
However, time-out errors are displayed.
203
Screen Display Section 6-2
6-2 Screen Display
This section describes the commands for switching the screen display of the
NT20S and the commands for ascertaining the screen number of the screen currently displayed by the NT20S.
The displayed screen can be also switched by pressing a touch switch for which the screen number of the screen to be displayed has been registered. For details on this method, refer to “Screen Switching Function” on page 138.
To change the NT20S screen, use the Display Specified Screen Command.
To ascertain the screen number of the currently displayed screen, use the Request
Screen Number Command. When this command is executed, the NT20S returns the Screen Number Response Command.
When the currently displayed NT20S screen is changed by pressing a touch switch to which a screen number has been allocated, the Screen Number Response Command is automatically sent from the NT20S.
Display Specified Screen
Format
[ESC]
1B
0
30 m
1
* * m
2
* * m
3
* * m
4
* *
Description
Request Screen Number
Format m
1 m
2 m
3 m
4
: Number of displayed screen (4-digit hexadecimal)
0000: No display
0001 to 01FA
H
: Screen #1 to #500
The specified screen is displayed on the NT20S when a screen number is sent from the Host with this command.
[ESC]
1B x
58
Description Enquires what number screen is displayed on the NT20S. The NT20S returns the number of the displayed screen using the Screen Number Response Command
(refer to 6-2 Screen Number Response).
204
Memory Tables Section 6-3
Screen Number Response
Format
[ESC]
1B
Y
59 m
1
* * m
2
* * m
3
* *
[CR]
OD m
1 m
2 m
3
: Number of displayed screen (4-digit hexadecimal)
000 to 1FA
H
(0 to 500)
Description
S The NT20S returns this command to report the currently displayed screen number to the Host in response to the Request Screen Number Command (refer to
6-2 Request Screen Number) sent from the Host.
S
The new screen number is report to the Host with this command after the displayed screen is switch with the Stand-alone functions (screen switch function).
6-3 Memory Tables
This section explains the commands used for memory table operations.
To change the contents of a character string memory table, use the Write Character-string Memory Table Command.
To change the contents of a numeral memory table, use a Write Numeral Memory
Table Command.
Note that different commands are used to write 4-digit and 8-digit numerical values.
Values can be copied from one memory table to another of the same type by using the Copy Memory Table Command.
Reference: S When the contents of an NT20S numeral memory table are changed by numeral setting input, a Number Input Notify Command is automatically sent from the
NT20S (refer to page 212)
S
By creating a bar graph screen and arranging for it to refer to a particular numeral memory table, the display contents of the bar graph can be updated by changing the contents of the numeral table.
Write Character-string Memory Table
Format
[ESC] B
1B 42 n
1
* * n
2
* * d
1
* * d
2
* * c
1
* * c
2
* * c
3
* * c n
* * n
1 n
2
: Character string length as a number of normal characters (2-digit hexadecimal) 01 to 20
H
(1 to 32) d
1 d
2
: Character-string memory table address of write destination (2-digit hexadecimal) 00 to 7F
H
(0 to 127) c
1 c
2 c
3 to c n
: Character-string data
205
Memory Tables
Description
Section 6-3
Writes the character-string data to the character-string memory table.
The character-string data can contain a mixture of normal alphanumeric characters and marks. When determining the character string length, count each mark as two normal characters.
Caution: If the actual character string is longer than the specified character string length, the specified number of characters is written and the remainder are discarded.
A timeout error message is displayed if the actual character string is shorter than the specified character string length.
4-digit Write Numeral Memory Table
Format
[ESC]
1B
C
43 d
1
* * d
2
* * d
3
* * n
1
* * n
2
* * n
3
* * n
4
* * d
1 d
2 d
3
: Numeral memory table address of write destination (3-digit hexadecimal)
000 to 07F
H
(0 to 127) n
1 n
2 n
3 n
4
: Number data (4-digit BCD or 4-digit hexadecimal)
Description
S Writes 4-digit number data (decimal or hexadecimal) to the specified numeral memory table.
S If a 4-digit number data is written while an 8-digit numeral is displayed, the lower
4 digits are updated.
Caution: This command cannot be used to write negative numbers. Use the 8-digit Write
Command (refer to 6-3 8-digit Write Numeral Memory Table).
8-digit Write Numeral Memory Table
Format
[ESC]
1B
D
44 d
1
* * d
2
* * d
3
* * n
1
* * n
2
* * n
3
* * n
4
* * n
5
* * n
6
* * n
7
* * n
8
* * d
1 d
2 d
3
: Numeral memory table address of write destination (3-digit hexadecimal) 000 to 07F
H
(0 to 127) n
1 n
2 n
3 n
4 n
5 n
6 n
7 n
8
: Number data (8-digit BCD or 8-digit hexadecimal)
Description
S Writes the 8-digit number data (decimal or hexadecimal) to the specified numeral memory table
S
To write a negative numeral (decimal), specify “F(46
H
7-digit numeral is written.)
)” for “n
1
” (in this case, a
206
Memory Tables
Copy Memory Table
Format
Description
Section 6-3
[ESC]
1B
/
2F m
1
* * s
1
* * s
2
* * s
3
* * d
1
* * d
2
* * d
3
* * m
1
: Type of memory table
0 (30
H
1 (31
H
): Character-string memory table
): Numeral memory table s
1 s
2 s
3
: Copy source memory table address
000 to 127 (3-digit BCD) d
1 d
2 d
3
: Copy destination memory table address
000 to 127 (3-digit BCD)
Copies the contents of the copy source memory table to the copy destination memory table. The memory table contents are copied to a memory table of the same type: character-string memory table to character-string memory table or numeral memory table to numeral memory table.
207
Lamps, Touch Switches, Numeral Setting Section 6-4
6-4 Lamps, Touch Switches, Numeral Setting
This sectioin describes the commands for operating the lamps, touch switches.
In order to change the display status (lit (flashing) or unlit) of a lamp or touch switch, use the Lamp and Touch Switch Display Commands. There are two such commands, one for bit specification and the other for number specification.
The Lamp and Touch Switch Display Status Enquiry Command is used to ascertain the status of a lamp or touch switch. When this command is executed the
NT20S returns the Lamp/Touch Switch Display Status Response Command.
Reference: When the status of an NT20S touch switch is changed - for example by pressing it the Touch Switch Number Output Command is sent to the host. When a numerical value is input by pressing a touch switch to which a numeral setting function has been allocated, a Number Input Notify Command is sent to the host.
6-4-1 Notification and Control of Touch Switches
If a touch switch is pressed, the corresponding touch switch number or bit information is sent to the Host. Conversely, to turn ON a touch switch or cause it to flash, the touch switch # or bit information is sent from the Host.
The type of data relating to the touch switch notification is specified with the “bit input attribute” in the screen attributes when creating the screen data with the support tool. It is not permissible to use both notification and control by a touch switch number and notification and control by bit information on the same screen.
Press
START abcde
NT20S
Touch switch # or bit information
Lighting command
HOST
Lit
S Bit touch switch method (bit input permitted setting)
If a touch switch is pressed, bit information is sent in accordance with the position of the touch switch. It can be used as a normal bit input switch at the PC side.
When this method is used, if more than one touch switch is pressed at the same time, the information of all the pressed touch switches (0 to 63) is reported to the
Host.
S
Touch switch # method (bit input not-permitted setting)
If the touch switch status is changed, the touch switch number set when the touch switch is created is sent as a 8-digit hexadecimal number.
208
Lamps, Touch Switches, Numeral Setting Section 6-4
Cautions when bit input is permitted
If the touch switches are set in the following positions using the support tool while the setting is “bit input permitted”, the following operations will occur due to the configuration of the touch switches.
Take this into consideration when setting touch switch areas.
Example 1:
Touch switches are set at positions A, B, C, and D using the minimum switch setting unit.
A C
S
If switches A, B, and C are turned ON at the same time, switch D is also set ON.
S Similarly, if switches A, B, and D are turned ON at the same time, switch C is also set ON.
D B
Example 2:
Touch switch areas E, F, and G are set.
E F
S If switches E and F are turned ON at the same time, switch G is also set ON.
G
Touch switch notification/control and attributes
Inverse and normal display states can be set as attributes of touch switches by using the support tool. There are slight differences in the operation when a touch switch is pressed depending on whether bit input is permitted or not permitted.
Bit input not permitted: Touch switch notification by number
The touch switch is lit for 0.2 seconds when pressed and then returns to the unlit status.
Bit input permitted: Touch switch notification by bit information
The touch switch is lit while pressed and returns to the unlit status when released.
When a touch switch which is currently lit or flashing is pressed, it is continuously lit while pressed and returns to its original state when released.
Simultaneous pressing of multiple touch switches
Two or more touch switches can be simultaneously pressed if their statuses are notified by bit information or if they use different host notification methods. However, two or more switches cannot be simultaneously pressed if their statuses are notified to the host by their numbers.
209
Lamps, Touch Switches, Numeral Setting Section 6-4
Lamp and Touch Switch Display (Bit Specification)
Format
[ESC]
1B
K
4B m0
1
* * m0
2
* * m1
1
* * m1
2
* * m2
1
* * m2
2
* * m3
1
* * m3
2
* *
[CR]
0D
Example
m0 to m3: Specification of lamps and touch switches (2-digit hexadecimal)
The relationship between the lamp and touch switch number and an expression of m0 to m3 in bits is given in the following table.
Bit mx
1 mx
2
Parameter m0 m1 m2 m3
7
07
15
23
31
6
06
14
22
30
5
05
13
21
29
4
04
12
20
28
3
03
11
19
27
2
02
10
18
26
1
01
09
17
25
0
00
08
16
24 mx1: Higher 4 bits of mx (x: 0 to 3) mx2: Lower 4 bits of mx
Bit ON: The lamp or touch switch is turned on (or caused to flash).
Bit OFF: The lamp or touch switch is turned off.
To turn on lamps and touch switches with the numbers 1, 5, 6, 7, and 26 m0
1 m0
2 m1
1 m1
2 m2
1 m2
2 m3
1 m3
2
=E200004
Description
S
Changes the display status of the lamps or touch switches.
S
Whether the lamp or touch switch which corresponds to the specified bit is turned on or flashes is determined by the setting made using the support tool.
S
This command can be used only when the setting for the “LMP Bit Control” memory switch is “Enable”.
Lamp and Touch Switch Display (Number Specification)
Format
[ESC] Q
1B 51 m
1
* * n
1
* * n
2
* * m
1
: Display status
0 (30
H
1 (31
2 (32
3 (33
H
H
H
): Not lit (normal display)
): Lit
): Flashing inverse
): All not lit n
1 n
2
: Lamp or touch switch # (2-digit hexadecimal)
000 to FF
H
(0 to 255)
210
Lamps, Touch Switches, Numeral Setting
Description
Section 6-4
Changes the lamp or touch switch lighting status.
Specify the display status as 3 (all not lit) to turn off all the lamps and touch switches. In this case, specify the lamp or touch switch number to any number in the permitted range.
Caution: The display attributes set with the Support Tool determine if lamps #0 to #31 light continuously or flash. The display status set with this command is ignored.
Lamp and Touch Switch Display Status Enquiry
Format
[ESC]
1B
R
52 n
1
* * n
2
* *
Description n
1 n
2
: Lamp or touch switch # (2-digit hexadecimal)
000 to FF
H
(0 to 255)
Enquires the status of a lamp or touch switch specified by its address.
The NT20S returns the Lamp and Touch Switch Display Status Response Command (refer to 6-4-1 Lamp and Touch Switch Display Status Response) to report the display status.
Lamp and Touch Switch Display Status Response
Format
[ESC]
1B
S
53 m
1
* * n
1
* * n
2
* *
Description m
1
: Display status
0 (30
H
1 (31
H
2 (32
H
): Not lit (normal display)
): Lit
): Flashing inverse n
1 n
2
: Lamp or touch switch # (2-digit hexadecimal)
00 to FF
H
(0 to 255)
The NT20S returns this command to report the lamp or touch switch number display status to the Host in response to the Lamp and Touch Switch Display Status
Enquiry Command (refer to 6-4-1 Lamp and Touch Switch Display Status Enquiry) sent from the Host.
Note: Lamps 0 to 31 are reported as being lit when in the “flashing inverse” status.
211
Lamps, Touch Switches, Numeral Setting Section 6-4
6-4-2 Notification of numeral setting input and touch switch status
The following describes the commands for notifying the host when numeral setting is performed (i.e., when the contents of a numeral memory table are changed by pressing a touch switch) or when a touch switch is pressed, when operating the
NT20S.
When a numerical value is input by numeral setting, the NT20S sends a Number
Input Notify Command to the host. The command sent differs depending on whether a 4-digit or 8-digit number is input.
When a touch switch is pressed, the NT20S sends a Touch Switch Number Output
Command or Touch Switch Bit Output Command to the host. The command sent depends on the set screen attributes.
4-digit Number Input Notify
Format
[ESC]
1B
E
45 d
1
* * d
2
* * d
3
* * n
1
* * n
2
* * n
3
* * n
4
* *
[CR]
0D
Description d
1 d
2 d
3
: Numeral memory table address to which number was input (3-digit hexadecimal) 000 to 07F
H
(0 to 127) n
1 n
2 n
3 n
4
: Input number data (4-digit BCD)
A number with 4 transferred digits set with the NT20S number setting function is reported to the Host with this command.
Caution: This command cannot be used for negative numbers. Always set “8” as the number of transferred digits when negative numbers may be input.
8-digit Number Input Notify
Format
[ESC]
1B
F
46 d
1
* * d
2
* * d
3
* * n
1
* * n
2
* * n
3
* * n
4
* * n
5
* * n
6
* * n
7
* * n
8
* *
[CR]
0D
Description d
1 d
2 d
3
: Numeral memory table address to which number was input (3-digit hexadecimal) 000 to 07F
H
(0 to 127) n
1 n
2 n
3 n
4 n
5 n
6 n
7 n
8
: Input number data (8-digit BCD)
A number with 8 transferred digits set with the PT number setting function is reported to the Host with this command.
When a negative number is written, n1 becomes “F” (46 prises 7 digits.
H
) and the number com-
212
Lamps, Touch Switches, Numeral Setting Section 6-4
Touch Switch Number Output (from NT20S to Host)
Format
[ESC] H
1B 48 m
1
* * m
2
* *
[CR]
0D
Description m
1 m
2
: Address of the pressed touch # (2-digit hexadecimal)
00 to E2
H
(0 to 226)
If a touch switch is pressed while the screen for which the “Bit In = Off” attribute is set is displayed, the address of the pressed touch switch is reported to the Host.
Reference: If more than one touch switch is pressed at the same time, only the address of the touch switch which was pressed first is reported to the Host.
Notification of numeral setting is not executed in the case of touch switches which have been allocated as ten keys.
Touch Switch Bit Output (from NT20S to Host)
Format
[ESC]
1B
J
4A s0
1
* * s0
2
* * s1
1
* * s1
2
* * s2
1
* * s2
2
* * s3
1
* * s3
2
* *
[CR]
0D
Example
s0,…s3: Status of the touch switch (2-digit hexadecimal value for each switch)
The relationship between the touch switch number and an expression of s0 to s3 in bits is given in the following table.
Bit sx
1 sx
2
Parameter s0 s1 s2 s3
7
07
15
23
31
6
06
14
22
30
5
05
13
21
29
4
04
12
20
28
3
03
11
19
27
2
02
10
18
26
1
01
09
17
25
0
00
08
16
24 sx1: Higher 4 bits of sx (x: 0 to 3) sx2: Lower 4 bits of sx
Bit ON: The touch switch is on.
Bit OFF: The touch switch is off.
Touch switches at addresses 0, 3, 21, and 27 are ON s0
1 s0
2 s1
1 s1
2 s2
1 s2
2 s3
1 s3
2
=09002008
Description
S
If the touch switch status is changed while the screen for which the “Bit Input,
Touch Switch” attribute is set is displayed, the status of the corresponding bit is reported to the Host.
S This report is made each time a touch switch is turned ON or OFF.
213
Controlling the NT20S Status Section 6-5
6-5 Controlling the NT20S Status
This section describes the actual methods used for controlling the NT20S status.
The Screen Display Control Command is used to operate the back light of the
NT20S (i.e., switch it on and off).
The Buzzer Control Command is used to control the buzzer status of the NT20S.
To inhibit the display of the system menu or cancel this inhibition, use the Mode
Switch Enable Command.
Touch switch data input or host notification can be inhibited, or this inhibition canceled, by using the Touch Switch and Function Key Disable Command or Touch
Switch and Function Key Enable Command respectively.
Touch Switch Disable
Format
[ESC]
1B
U
55
2
32
Description Disables touch switch and function key input and notification to the Host.
Reference: Use the Touch Switch Enable Command (refer to 6-5 Touch Switch Enable) to use a disabled touch switch again. Disabled touch switches are also enabled when the
NT20S power is turned off.
Touch Switch Enable
Format
[ESC]
1B
V
56
2
32
Description Enables input and notification to the Host of a disabled touch switch or function key.
Reference: Disabled touch switches are also enabled when the NT20S power is turned off.
214
Controlling the NT20S Status Section 6-5
Screen Display Control
Format
[ESC]
1B
P
50 m
1
* *
Description
Buzzer Control
Format m
1
: Display on or off
0 (30
H
1 (31
H
): on
): off
Turns off the backlighting.
Reference: S The screen is redisplayed if a touch switch is pressed.
S When a Display Specified Screen Command (page 204) is sent, the specified screen is displayed.
[ESC]
1B
T
54 m
1
* *
Description m
1
: Buzzer status
0 (30
H
1 (31
H
2 (32
H
): Buzzer off
): Continuous buzzer
): Short intermittent buzzer
Controls the NT20S buzzer.
Reference: The buzzer turned on with this command can be stopped with a Buzzer control command, press the “buzzer stop” touch switch on the screen, or by displaying a screen with no buzzer attributes.
System Menu Display Permission
Format
[ESC]
1B
W
57 m
1
* * m
1
: System menu display permission/inhibition
0 (30
H
1 (31
H
): Display permitted
): Display inhibited
215
Terminal Commands
Description
Section 6-6
System menu is displayed when “display permitted” is set, and from the system menu, selection of transmit mode or maintenance mode is possible. If “display inhibited” is set, the system menu is not displayed.
Turning off the power or resetting operation validates the settings made with the
DIP switch (SW2-3) on the NT20S.
6-6 Terminal Commands
This section describes the terminal commands used to display character strings or graphics in accordance with instructions from the host, independently of the screens registered in the NT20S.
Terminal commands designate screen attributes such as inversion, flashing, cursor position and size of characters before the characters are displayed.
Once screen attributes are set, they remain effective for screen displays until they are cancelled or other attributes are set.
In addition, continuous lines and circles can be drawn.
Clear Screen
Format
[ESC]
1B
&
26
Description Clears all text and graphics on the NT20S screen.
Reference: Even if this command is used to clear a screen, the NT20S still displays the preceding screens.
After the display of number, text, lamps or touch switches is upgraded, only the upgraded parts are re-displayed.
216
Terminal Commands Section 6-6
Character Specify Size
Format
Description
[ESC]
1B
)
29 m
1
* *
Description m
1
: Character size
0 (30
H
1 (31
H
): Normal size, 16 x 8 dots (H x W)
): 1/2 size, 8 x 8 dots (H x W)
Specifies if 1-byte alphanumeric characters sent subsequently are displayed as normal characters or 1/2-size characters.
Reference: The character string is specified with the Specify Displayed Characters Command
(refer to 6-6 Specify Displayed Characters). Both normal characters and 1/2-size characters are enlarged as specified by the Specify Character Enlargement Command (refer to 6-6 Specify Character Enlargement below).
The character size specified with this command remains valid until the screen display is switched or another character size is specified with the command. The default character size is normal characters.
Specify Character Enlargement
Format
[ESC]
1B
*
2A m
1
* * m
1
: Character enlargement
0 (30
H
1 (31
H
2 (32
H
3 (33
4 (34
5 (35
H
H
H
): No enlargement
): Enlarge height x 2
): Enlarge width x 2
): 2 x 2 enlargement
): 3 x 3 times enlargement
): 4 x 4 times enlargement
All text and marks sent after this command are displayed in the specified size.
Reference: The character string is specified with the Specify Displayed Characters Command(refer to 6-6 Specify Displayed Characters).
The enlargement specified with this command remains valid until the screen display is switched or another enlargement is specified with the command. The default enlargement is no enlargement.
217
Terminal Commands Section 6-6
Normal Display
Format
Description
[ESC]
1B
!
21
Cancels all display attribute settings(inverse, flashing, flashing inverse) for characters and marks so that all characters are displayed as “normal” characters (not inverse or flashing).
Set Inverse Display
Format
[ESC]
1B
”
22
Description Sets the display attribute to inverse so that all characters and marks sent subsequently are highlighted. Other attributes remain unchanged.
Reference: The Set Inverse Display Command is cancelled by the End Inverse Display Command or the Normal Display Command.
The setting with this command remains valid until the screen display is switched or another display attribute setting is made. The default display attributes are set to a normal display when a screen is initially displayed.
Use this command with the Set Flashing Display Command (refer 6-6 Set Flashing
Display) to produce a flashing inverse display.
End Inverse Display
Format
[ESC]
1B
#
23
Description Clears the inverse display attribute so that all characters and marks sent subsequently are not highlighted. Other attributes remain unchanged.
Reference: The inverse display attribute is set with the Set Inverse Display Command.
The setting with this command remains valid until the screen display is switched or another display attribute setting is made. The default display attributes are set to a normal display when a screen is initially displayed.
218
Terminal Commands Section 6-6
Set Flashing Display
Format
[ESC]
1B
$
24
Description Sets the display attribute to flashing so that all characters and marks sent subsequently are displayed flashing. Other attributes remain unchanged.
Reference: The Set Flashing Display Command is cancelled by the End Flashing Display
Command or the Normal Display Command (refer to 6-6 Normal Display and 6-6
End Flashing Display).
The setting with this command remains valid until the screen display is switched or another display attribute setting is made. The default display attributes are set to a normal display when a screen is initially displayed.
Use this command with the Set Inverse Display Command (refer to 6-6 Set In-
verse Display) to produce a flashing inverse display.
End Flashing Display
Format
[ESC]
1B
%
25
Description Clears the flashing display attribute so that all characters and marks sent subsequently are not flashing. Other attributes remain unchanged.
Reference: The flashing display attribute is set with the Set Flashing Display Command.
The setting with this command remains valid until the screen display is switched or another display attribute setting is made. The default display attributes are set to a normal display when a screen is initially displayed.
219
Terminal Commands Section 6-6
Set Cursor Position
Format
[ESC]
1B
+
2B x
1
* * x
2
* * x
3
* * y
1
* * y
2
* * y
3
* *
Description x
1 x
2 x
3
: X coordinate (3-digit BCD)
000 to 255 y
1 y
2 y
3
: Y coordinate (3-digit BCD)
000 to 127
Before displaying a character string with the Terminal commands, use this command to set the bottom-left point of the first character to be displayed.
Reference: The cursor position set with this command is also the bottom-left point of the first character displayed if the displayed characters are enlarged.
Specify Displayed Characters
Format
[ESC]
1B
4
34 n
1
* * n
2
* * c
1
* * c
2
* * c
3
* * c n
* * n
1 n
2
: Character string length as a number of normal characters (2-digit hexadecimal)
01 to 20H (1 to 32) c
1 c
2 c
3 to c n
: Character-string to display
Description
S The character string is displayed from the cursor position.
S
The character-string data can contain a mixture of normal (alphanumeric) characters and marks. Refer to Appendix M Special Characters for details.
S The character string is displayed according to the enlargement and display attributes set with commands.
Reference: The character string continues on the next line if it cannot fit into a single line.
Set the position where the character string is displayed with the Set Cursor Position Command (refer to 6-6 Set Cursor Position).
220
Terminal Commands
Draw Polyline
Format
Description
Draw Circle
Format
Description
Section 6-6
[ESC]
1B
7
37 xn
1
* * m
1
* * xn
2
* * m
2
* * xn
3
* * x0
1
* * yn
1
* * x0
2
* * yn
2
* * x0
3
* * yn
3
* * y0
1
* * y0
2
* * y0
3
* * m
1
, m
2
: Number of lines to draw (2-digit hexadecimal)
01 to 28
H
(1 to 40) x0
1 x0
2 x0
3 to xn
1 xn
2 xn
3
: X coordinates of line end points (3-digit BCD)
000 to 255 y0
1 y0
2 y0
3 to yn
1 yn
2 yn
3
: Y coordinates of line end points (3-digit BCD)
000 to 127
Draws the specified number of lines between the specified points.
[ESC]
1B
8
38 x
1
* * x
2
* * x
3
* * y
1
* * y
2
* * y
3
* * r
1
* * r
2
* * r
3
* * x
1 x
2 x
3
: X coordinate of circle center (3-digit BCD)
000 to 255 y
1 y
2 y
3
: Y coordinate of circle center (3-digit BCD)
000 to 127 r
1 r
2 r
3
: circle radius in dots (3-digit BCD)
001 to 063
Draws a circle of the specified radius around the circle center point.
221
Key to Programs Section 6-7
6-7 Key to Programs
The following programs include all the commands that can be used with the
NT20S.
6-7-1 Use of Programs
The sample program appears as follows on the screen.
Menu bar Sub-menu Parameter input column
222
Send command column Run confirm column
Receive command display column
Interrupt display when command received
Use the program as shown below.
Execute program
[ESC]
[ESC]
Select type of send command
[ESC]
Select send command
Main Menu
Sub-menu
Input parameter Input parameter column
Confirm send command
Send command column, confirm execution
Execute transfer command
Up, Down, Left, Right keys: select item
[ENT]: confirm
[Esc]: stop
End program
1. This sample program is written in N88BASIC (86) (NEC) for a PC-9801 computer. Modify this program for use with any other computer language or computer such as an IBM PC/AT or compatible.
2. The interval between parameter input and command transmission is a hold interval for interrupt processing of the received command. If an interrupt is permitted between the interval of parameter input and a command is received, all subsequent receive interrupts are displaced. If this occurs, send an enquiry command to read all the accumulated receive data.
3. When a parameter is input, no check is made that the parameter is in the permitted range. Make sure that parameters are input within the permitted range.
EXAMPLE PROGRAM Section 6-7
EXAMPLE PROGRAM
1000 ’ ********************************************************
1010 ’ * OPERATION COMMAND EXAMPLE PROGRAM (NT20S-ST128) *
1020 ’ ********************************************************
1030 ’ ............................................
1040 SECT=9
Draw screen frame
1050 DIM CMND$(SECT,10,1),CMND(SECT),TS.B(31)
1060 SCREEN 3:CLS 3:CONSOLE 15,10,0,0
1070 LINE (0,176)-(639,176),7,,&HF0F0
1080 LINE (159,0)-(159,176),7,,&HF0F0
1090 LINE (300,0)-(300,176),7,,&HF0F0
1100 LINE (0, 16)-(159, 16),7,,&HF0F0
1110 LINE (0, 96)-(159, 96),7,,&HF0F0
1120 LINE (0,112)-(159,112),7,,&HF0F0
1130 LINE (520,176)-(520,224),7,,&HF0F0
1140 LINE (0,223)-(639,224),7,B
1150 COLOR 0:LOCATE 2,0:PRINT ”OPERATING COMMANDS”
1160 COLOR 0:LOCATE 2,6:PRINT ”TERMINAL COMMANDS”
Set display character strings 1170 CMND(0)=SECT ’
1180 FOR I=1 TO SECT
............................
1190 READ CMND$(0,I,0)
1200 NEXT I
1210 FOR I=1 TO SECT
1220 READ CMND(I)
1230 FOR J=1 TO CMND(I)
1240 READ CMND$(I,J,0),CMND$(I,J,1)
1250 IF CMND$(I,J,1) = ”@@@@@@” THEN CMND$(I,J,1) = ”[ESC]”+CHR$(&H22)
1260 NEXT J
1270 NEXT I
1280 ’
1290 RY=15
1300 ON COM(1) GOSUB *RECV ’ ..................
1310 OPEN ”COM1:E81NN” AS #1 ’ ...............
1320 ’ NT20S_SETTING OF ST128
1330 ’ DATA BIT LENGTH 8 BITS
1340 ’ STOP BIT LENGTH
1350 ’ PARITY
1360 ’ FLOW CONTROL
1 BIT
ODD
RS/CS
Set receive interrupt routine
Open communication port
(VALUE SET BY SWITCH COMMAND) 1370 ’ BAUD RATE
1380 COM(1) ON
1390 ’
Main Menu 1400 *LV0 ’ ......................................
1410 LV=0:SECT.NO=0:SEL.NO=1
1420 GOSUB *SELECT
1430 IF SEL.NO=0 THEN GOTO *PRO.END
223
EXAMPLE PROGRAM Section 6-7
1440 SECT.NO = SEL.NO
1450 ’
1460 *LV1 ’ ......................................
1470 LV=1:SEL.NO=1
1480 GOSUB *SELECT
1490 IF SEL.NO=0 THEN GOTO *LV0
Sub-menu
1500 *LV2 ’ ............................
1510 COM(1) STOP
Branch according to command (parameter input)
1520 LV=2:SEND$=CMND$(SECT.NO,SEL.NO,1)
1530 *SECT1
1540 IF SECT.NO<>1 THEN GOTO *SECT2
1550 ON SEL.NO GOSUB *ESC.0,*ESC.X
1560 *SECT2
1570 IF SECT.NO<>2 THEN GOTO *SECT3
1580 ON SEL.NO GOSUB *ESC.B,*ESC.C,*ESC.D,*ESC.2F
1590 *SECT3
1600 IF SECT.NO<>3 THEN GOTO *SECT4
1610 ON SEL.NO GOSUB *ESC.K,*ESC.Q,*ESC.R
1620 *SECT4
1630 IF SECT.NO<>4 THEN GOTO *SECT5
1640 ON SEL.NO GOSUB *ESC.U,*ESC.V
1650 *SECT5
1660 IF SECT.NO<>5 THEN GOTO *SECT6
1670 ON SEL.NO GOSUB *ESC.P,*ESC.T,*ESC.W
1680 *SECT6
1690 IF SECT.NO<>6 THEN GOTO *SECT7
1700 ON SEL.NO GOSUB *ESC.26,*ESC.29,*ESC.2A
1710 *SECT7
1720 IF SECT.NO<>7 THEN GOTO *SECT8
1730 ON SEL.NO GOSUB *ESC.21,*ESC.22,*ESC.23,*ESC.24,*ESC.25
1740 *SECT8
1750 IF SECT.NO<>8 THEN GOTO *SECT9
1760 ON SEL.NO GOSUB *ESC.2B,*ESC.4
1770 *SECT9
1780 IF SECT.NO<>9 THEN GOTO *LV2.END
1790 ON SEL.NO GOSUB *ESC.7,*ESC.8
1800 *LV2.END ’ .................................
Confirm transmission
1810 LOCATE 0,12:PRINT LEFT$(SEND$,56);
1820 IF LEN(SEND$)>56 THEN PRINT ”...”
1830 LOCATE 66,12:PRINT ”OK?”;
1840 YN=1
1850 *YN.KY.IN
1860 LOCATE 74,12:COLOR 2+2*YN:PRINT ”Y”;:COLOR 2-2*YN:PRINT ”N”;
1870 A$=INKEY$:IF A$=”” THEN GOTO *YN.KY.IN
1880 IF A$=CHR$(&H1C) OR A$=CHR$(&H1D) THEN YN=YN*(-1):GOTO *YN.KY.IN
1890 IF A$<>CHR$(&HD) THEN GOTO *YN.KY.IN
224
EXAMPLE PROGRAM Section 6-7
1900 LOCATE 66,12:COLOR 0:PRINT SPACE$(14);
1910 IF YN=-1 THEN GOTO *LV3.END
1920 GOSUB *SEND ’ ..............................
1930 COM(1) ON
Send command
1940 LOCATE 43,9:COLOR 4:PRINT ”Press ESC Key”;:COLOR 0
1950 *SND.KY.IN
1960 A$=INKEY$:IF A$<>CHR$(&H1B) THEN *SND.KY.IN
1970 *LV3.END
1980 LOCATE 0,12:PRINT SPACE$(79);
1990 FOR I=0 TO 10
2000 LOCATE 39,I:PRINT SPACE$(40);
2010 NEXT I
2020 GOTO *LV1 ’
2030 ’
2040 *PRO.END ’
................................
.................................
Return to Sub-menu
End routine
Close communication port 2050 COM(1) OFF:CLOSE ’ ........................
2060 CONSOLE 0,25,0,1:CLS 3
2070 END
2080 ’
2090 *SEND ’ .....................................
Send command routine
2100 SND$=CHR$(&H1B)+MID$(SEND$,6)
2110 PRINT #1,SND$
2120 RETURN
2130 ’
2140 *RECV ’ .....................................
2150 IF LOC(1)=0 THEN GOTO *NORCV
2160 SX=POS(0):SY=CSRLIN
2170 LINE INPUT #1,RCV$
2180 LOCATE 0,RY:COLOR 0
2190 PRINT ”[ESC]”;MID$(RCV$,2)
Receive interrupt routine
2200 R.CODE$=MID$(RCV$,2,1)
2210 *ESC.Y ’ ....................................
Notify screen number
2220 IF R.CODE$<>”Y” THEN GOTO *ESC.E
2230 PRINT ”Screen Number : ”;VAL(”&H”+MID$(RCV$,3,4))
2240 PRINT:GOTO *RCV.END
2250 *ESC.E ’ ....................................
2260 IF R.CODE$<>”E” THEN GOTO *ESC.F
Notify 4-digit number
2270 PRINT ”Numeral table # : ”;VAL(”&H”+MID$(RCV$,3,3))
2280 PRINT ”Input decimal value”;VAL(MID$(RCV$,6,4))
2290 PRINT:GOTO *RCV.END
2300 *ESC.F ’ ....................................
Notify 8-digit number
2310 IF R.CODE$<>”F” THEN GOTO *ESC.H
2320 PRINT ”Numeral table # : ”;VAL(”&H”+MID$(RCV$,3,3))
2330 IF MID$(RCV$,6,1)=”F” THEN NN=0-VAL(MID$(RCV$,7,7)) ELSE NN=VAL(MID$(RCV$,6,8))
2340 PRINT ”Input decimal value : ”;NN
2350 PRINT:GOTO *RCV.END
225
EXAMPLE PROGRAM Section 6-7
2360 *ESC.H ’ ....................................
Notify touch switch (number)
2370 IF R.CODE$<>”H” THEN GOTO *ESC.J
2380 PRINT ”Pressed touch switch number : ”;VAL(”&H”+MID$(RCV$,3,3))
2390 PRINT:GOTO *RCV.END
Notify touch switch (bit) 2400 *ESC.J ’ ....................................
2410 IF R.CODE$<>”J” THEN GOTO *ESC.S
2420 PRINT ”Pressed touch switch number : ”;
2430 TS=0
2440 FOR I=0 TO 13
2450 S=VAL(”&H”+MID$(RCV$,3+I*2,2))
2460 FOR J=0 TO 7
2470
2480
IF (S MOD 2)=1 THEN PRINT TS;” ”;
S=S¥2:TS=TS+1
2490 NEXT J,I
2500 PRINT:PRINT:GOTO *RCV.END
2510 *ESC.S ’ ....................................
Notify lamp and touch switch status
2520 IF R.CODE$<>”S” THEN GOTO *RCV.ERR
2530 PRINT ”Lamp/touch switch number : ”;VAL(”&H”+MID$(RCV$,4,2))
2540 M=VAL(MID$(RCV$,3,1))
2550 IF M=0 THEN M$=”OFF” ELSE IF M=1 THEN M$=”ON” ELSE M$=”INVERSE”
2560 PRINT ”Display status
2570 PRINT:GOTO *RCV.END
: ”;M$
2580 ’
2590 *RCV.ERR
2600 PRINT ”Receive data error”
2610 PRINT
2620 ’
2630 *RCV.END
2640 RY=CSRLIN
2650 LOCATE SX,SY
2660 *NORCV
2670 RETURN
2680 ’
2690 *ESC.0 ’ ....................................
2700 LOCATE 43,0:INPUT ”Screen number : ”,M
2710 M$=RIGHT$(”000”+HEX$(M),4)
2720 SEND$=SEND$+M$
2730 RETURN
2740 *ESC.X ’ ....................................
Display specified screen
Screen # enquiry
2750 RETURN
2760 *ESC.B ’ ....................................
Write character screen
2770 LOCATE 43,0:INPUT ”Character-screen memory table number : ”,M
2780 LOCATE 43,1:PRINT ”Write character string (MAX 32 CHARACTERS) -->”
2790 LOCATE 43,2:INPUT C$
2800 M$=RIGHT$(”0”+HEX$(M),2)
2810 C$=LEFT$(C$,32):L$=RIGHT$(”0”+HEX$(LEN(C$)),2)
226
EXAMPLE PROGRAM Section 6-7
2820 SEND$=SEND$+L$+M$+C$
2830 RETURN
2840 *ESC.C ’ ....................................
2850 LOCATE 43,0:INPUT ”Numeral table #
Write 4-digit number
: ”,M
2860 *NAGAIN
2870 LOCATE 43,1:INPUT ”Write 1 to 4-digit number : ”,N%
2880 IF N%<-999 OR N%>9999 THEN GOTO *NAGAIN
2890 IF N%<0 THEN S$=”F” ELSE S$=””
2900 M$=RIGHT$(”00”+HEX$(M),3)
2910 N%=ABS(N%)
2920 N$=STR$(N%):N$=RIGHT$(N$,LEN(N$)-1)
2930 IF S$<>”F” THEN N$=RIGHT$(”000”+N$=RIGHT$(”00”+N$,3)
2940 SEND$=SEND$+M$+S$+N$
2950 RETURN
2960 *ESC.D ’ ....................................
2970 LOCATE 43,0:INPUT ”Numeral table #
2980 *N8AGAIN
Write 8-digit number
: ”,M
2990 LOCATE 43,1:PRINT SPACE$(36)
3000 LOCATE 43,1:INPUT ”Write 1 to 8-digit number : ”,N#
3010 N#=INT(N#)
3020 IF N#<-9999999# OR N#>99999999# THEN GOTO *N8AGAIN
3030 IF N#<0 THEN S$=”F” ELSE S$=””
3040 M$=RIGHT$(”00”+HEX$(M),3)
3050 N#=ABS(N#)
3060 N$=STR$(N#):N$=RIGHT$(N$,LEN(N$)-1)
3070 IF S$<>”F” THEN N$=RIGHT$(”0000000”+N$,8) ELSE N$=RIGHT$(”000000”+N$,7)
3080 SEND$=SEND$+M$+S$+N$
3090 RETURN
3100 *ESC.2F ’ ..................................
Copy memory table
3110 LOCATE 43,0:INPUT ”0: character string/1 : number ”,M$
3120 IF M$<>”0”AND M$<>”1” THEN *ESC.2F
3130 LOCATE 43,1:INPUT ”Copy source memory table number : ”,S%
3140 LOCATE 43,2:INPUT ”Copy destination memory table number : ”,D%
3150 S$=STR$(S%):S$=RIGHT$(S$,LEN(S$)-1):S$=RIGHT$(”00”+S$,3)
3160 D$=STR$(D%):D$=RIGHT$(D$,LEN(D$)-1):D$=RIGHT$(”00”+D$,3)
3170 SEND$=SEND$+M$+S$+D$
3180 RETURN
3190 *ESC.K ’ .................................
3200 FOR I=0 TO 31:TS.B(I)=-1:NEXT I
Display lamps and touch switches (bits)
3210 FOR I=0 TO 31
3220 LOCATE 65-(I MOD 8)*3,I¥8:PRINT RIGHT$(STR$(I),2)
3230 NEXT I
3240 LOCATE 43,5:PRINT ”Input # : Inverse Input : Run input 99 : Execute”
3250 *ESC.K.2
3260 COLOR 0:LOCATE 43,6:PRINT SPACE$(36)
3270 LOCATE 43,6:INPUT ”Lamp/touch switch number : ”;N
227
EXAMPLE PROGRAM Section 6-7
3280 IF N=99 THEN GOTO *ESC.K.3
3290 IF N<0 OR N>31 THEN GOTO *ESC.K.2
3300 TS.B(N)=TS.B(N)*(-1)
3310 COLOR 2+TS.B(N)*2
3320 LOCATE 65-(N MOD 8)*3,N¥8:PRINT RIGHT$(STR$(N),2)
3330 GOTO *ESC.K.2
3340 *ESC.K.3
3350 FOR I=0 TO 3
3360 M=0
3370 FOR J=0 TO 7
3380 IF TS.B(I*8+J)=1 THEN M=M+2^J
3390 NEXT J
3400 SEND$=SEND$+RIGHT$(”0”+HEX$(M),2)
3410 NEXT I
3420 COLOR 0
3430 RETURN
3440 *ESC.Q ’ ...............................
Display lamps and touch switches (number)
3450 LOCATE 43,0:PRINT ”Display specification”
3460 LOCATE 43,1:PRINT ” 0 : OFF”
3470 LOCATE 43,2:PRINT ” 1 : ON”
3480 LOCATE 43,3:PRINT ” 2 : Inverse flashing (lamps only)”
3490 LOCATE 43,4:PRINT ” 3 : All ON”
3500 *QAGAIN
3510 LOCATE 43,5:INPUT ” : ”,M$
3520 IF M$<>”0” AND M$<>”1” AND M$<>”2” AND M$<>”3” THEN GOTO *QAGAIN
3530 LOCATE 43,6:INPUT ”Lamp/touch switch number : ”,N
3540 N$=RIGHT$(”00”+HEX$(N),2)
3550 SEND$=SEND$+M$+N$
3560 RETURN
3570 *ESC.R ’ ....................................
Enquire lamp and touch switch status
3580 LOCATE 43,0:INPUT ”Lamp/touch switch number : ”,N
3590 N$=RIGHT$(”00”+HEX$(N),2)
3600 SEND$=SEND$+N$
3610 RETURN
3620 *ESC.U ’ ....................................
3630 SEND$=SEND$+”0”
3640 RETURN
Disable inputs
Enables inputs 3650 *ESC.V ’ ....................................
3660 SEND$=SEND$+”0”
3670 RETURN
3680 *ESC.P ’ ....................................
3690 LOCATE 43,0:PRINT ”Controlled item”
3700 LOCATE 43,1:PRINT ” 0 : Display”
3710 LOCATE 43,2:PRINT ” 1 : No display
3720 *PAGAIN
3730 LOCATE 43,3:INPUT ” : ”,M$
Display screen
228
EXAMPLE PROGRAM Section 6-7
3740 IF M$<>”0” AND M$<>”1” THEN GOTO *PAGAIN
3750 SEND$=SEND$+M$
3760 RETURN
Buzzer control 3770 *ESC.T ’ ....................................
3780 LOCATE 43,0:PRINT ”Controlled item”
3790 LOCATE 43,1:PRINT ” 0 : Stop buzzer”
3800 LOCATE 43,2:PRINT ” 1 : Continuous buzzer”
3810 LOCATE 43,3:PRINT ” 2 : Intermittent buzzer”
3820 *TAGAIN
3830 LOCATE 43,4:INPUT ” : ”,M$
3840 IF M$<>”0” AND M$<>”1” AND M$<>”2” THEN GOTO *TAGAIN
3850 SEND$=SEND$+M$
3860 RETURN
3870 *ESC.W ’ ....................................
3880 LOCATE 43,0:PRINT ”Controlled item”
System menu display
3890 LOCATE 43,1:PRINT ” 0:MENU TRANSFER ENABLE”
3900 LOCATE 43,2:PRINT ” 1:MENU TRANSFER DISABLE”
3910 *WAGAIN
3920 LOCATE 43,3:INPUT ” : ”,M$
3930 IF M$<>”0” AND M$<>”1” THEN GOTO *WAGAIN
3940 SEND$=SEND$+M$
3950 RETURN
3960 ’
3970 *ESC.26 ’ ..................................
Clear screen
3980 RETURN
3990 *ESC.29 ’ ..................................
Specify 1-byte character
4000 LOCATE 43,0:PRINT ”Character specify size”
4010 LOCATE 43,1:PRINT ” 0 : NORMAL SIZE (16x8)”
4020 LOCATE 43,2:PRINT ” 1 : HALF SIZE (8x8)”
4030 *E26AGAIN
4040 LOCATE 43,3:INPUT ” : ”,M$
4050 IF M$<>”0” AND M$<>”1” THEN GOTO *E26AGAIN
4060 SEND$=SEND$+M$
4070 RETURN
4080 *ESC.2A ’ ..................................
Specify character enlargement
4090 LOCATE 43,0:PRINT ”Specify character enlargement”
4100 LOCATE 43,1:PRINT ” 0:NO ENLARGEMENT”
4110 LOCATE 43,2:PRINT ” 1:ENLARGE HEIGHT”
4120 LOCATE 43,3:PRINT ” 2:ENLARGE WIDTH”
4130 LOCATE 43,4:PRINT ” 3:2X2 ENLARGEMENT”
4140 LOCATE 43,5:PRINT ” 4:3X3 TIMES ENLARGEMENT”
4150 LOCATE 43,6:PRINT ” 5:4X4 TIMES ENLARGEMENT”
4160 *E2AAGAIN
4170 LOCATE 43,7:INPUT ” : ”,M$
4180 IF M$=”0” OR M$=”1” OR M$=”2” THEN GOTO *E2ASEND
4190 IF M$=”3” OR M$=”4” OR M$=”5” THEN GOTO *E2ASEND
229
EXAMPLE PROGRAM Section 6-7
4200 GOTO *E2AAGAIN
4210 *E2ASEND
4220 SEND$=SEND$+M$
4230 RETURN
..................................
4240 *ESC.21 ’
4250 RETURN
4260 *ESC.22 ’
4270 RETURN
..................................
Normal display
Set inverse display
4280 *ESC.23 ’
4290 RETURN
4300 *ESC.24 ’
..................................
..................................
4310 RETURN
4320 *ESC.25 ’
4330 RETURN
4340 *ESC.2B ’
..................................
..................................
4350 *E2B.X
4360 LOCATE 43,0:PRINT SPACE$(36)
End inverse display
Set flashing display
End flashing display
Set cursor position
4370 LOCATE 43,0:INPUT ”X COORDINATE(000-255)”,BX
4380 IF BX>639 OR BX<0 THEN *E2B.X
4390 *E2B.Y
4400 LOCATE 43,1:PRINT SPACE$(36)
4410 LOCATE 43,1:INPUT ”Y COORDINATE(000-127)”,BY
4420 IF BY>255 OR BY<0 THEN *E2B.Y
4430 BX$=STR$(BX):BX$=RIGHT$(BX$,LEN(BX$)-1):BX$=RIGHT$(”00”+BX$,3)
4440 BY$=STR$(BY):BY$=RIGHT$(BY$,LEN(BY$)-1):BY$=RIGHT$(”00”+BY$,3)
4450 SEND$=SEND$+BX$+BY$
4460 RETURN
4470 *ESC.4 ’ ....................................
Specify Displayed Characters
4480 LOCATE 43,0:PRINT ”Write character string (MAX. 32 CHARACTERS) -->|”
4490 LOCATE 43,1:INPUT C$
4500 C$=LEFT$(C$,32):L$=RIGHT$(”0”+HEX$(LEN(C$)),2)
4510 SEND$=SEND$+L$+C$
4520 RETURN
Draw Polyline 4530 *ESC.7 ’ ....................................
4540 LN=0:SL$=””
4550 *E7.X
4560 LOCATE 41,8:PRINT SPACE$(38)
4570 LOCATE 41,9:PRINT SPACE$(38)
4580 LOCATE 41,8:INPUT ”X COORDINATE(END AT 999) : ”,LX
4590 IF LX=999 THEN *E7.E
4600 IF LX<0 OR LX>255 THEN GOTO *E7.X
4610 *E7.Y
4620 LOCATE 41,9:PRINT SPACE$(38)
4630 LOCATE 41,9:INPUT ”Y COORDINATE : ”,LY
4640 IF LY<0 OR LY>127 THEN GOTO *E7.Y
4650 LX$=STR$(LX):LX$=RIGHT$(LX$,LEN(LX$)-1):LX$=RIGHT$(”00”+LX$,3)
230
EXAMPLE PROGRAM
4660 LY$=STR$(LY):LY$=RIGHT$(LY$,LEN(LY$)-1):LY$=RIGHT$(”00”+LY$,3)
4670 LOCATE 39+(LN MOD 5)*8,LN¥5:PRINT LX$;”,”;LY$;
4680 SL$=SL$+LX$+LY$
4690 LN=LN+1
4700 IF LN<40 THEN GOTO *E7.X
4710 *E7.E
4720 LN$=HEX$(LN-1):LN$=RIGHT$(”0”+LN$,2)
4730 SEND$=SEND$+LN$+SL$
4740 RETURN
4750 *ESC.8 ’ ....................................
Draw circle
4760 *E8.X
4770 LOCATE 43,0:PRINT SPACE$(36)
4780 LOCATE 43,0:INPUT ”X COORDINATE OF CENTER OF CIRCLE : ”,CX
4790 IF CX>255 OR CX<0 THEN *E8.X
4800 *E8.Y
4810 LOCATE 43,1:PRINT SPACE$(36)
4820 LOCATE 43,1:INPUT ”Y COORDINATE OF CENTER OF CIRCLE : ”,CY
4830 IF CY>127 OR CY<0 THEN *E8.Y
4840 *E8.R
4850 LOCATE 43,2:PRINT SPACE$(36)
4860 LOCATE 43,2:INPUT ”?????#####”,CR
4870 IF CR>63 OR CR<0 THEN *E8.R
4880 CX$=STR$(CX):CX$=RIGHT$(CX$,LEN(CX$)-1):CX$=RIGHT$(”00”+CX$,3)
4890 CY$=STR$(CY):CY$=RIGHT$(CY$,LEN(CY$)-1):CY$=RIGHT$(”00”+CY$,3)
4900 CR$=STR$(CR):CR$=RIGHT$(CR$,LEN(CR$)-1):CR$=RIGHT$(”00”+CR$,3)
4910 SEND$=SEND$+CX$+CY$+CR$
4920 RETURN
4930 ’
4940 *SELECT ’ ..................................
4950 IF LV=0 THEN LX=3 ELSE LX=LV*20+1
Item selection routine
4960 IF LV=0 THEN LY=1 ELSE LY=0
5970 COLOR 4:LOCATE LX,LY:PRINT CMND$(SECT.NO,1,0)
5980 COLOR 0
5990 FOR I=2 TO CMND(SECT.NO)
5000 IF LV=0 AND I<=5 THEN LY=I
5010 IF LV=0 AND I>5 THEN LY=I+1
5020 IF LV=1 THEN LY=I-1
5030 LOCATE LX,LY:PRINT CMND$(SECT.NO,I,0)
5040 NEXT I
5050 *KY.IN
5060 A$=INKEY$:IF A$=”” THEN GOTO *KY.IN
5070 IF A$<>CHR$(&H1B)
5080 COLOR 0
THEN GOTO *KY1
5090 FOR I=1 TO CMND(SECT.NO)
5100
5110
IF LV=0 AND I<=5 THEN LY=I
IF LV=0 AND I>5 THEN LY=I+1
Section 6-7
231
EXAMPLE PROGRAM Section 6-7
5120 IF LV=1 THEN LY=I-1
5130 LOCATE LX,LY:PRINT SPACE$(20)
5140 NEXT I
5150 SEL.NO=0
5160 GOTO *SEL.RET
5170 *KY1
5180 IF A$<>CHR$(&H1E) AND A$<>CHR$(&H1F) THEN GOTO *KY2
5190 IF LV=0 AND SEL.NO<=5 THEN LY=SEL.NO
5200 IF LV=0 AND SEL.NO>5
5210 IF LV=1
THEN LY=SEL.NO+1
THEN LY=SEL.NO-1
5220 COLOR 0:LOCATE LX,LY:PRINT CMND$(SECT.NO,SEL.NO,0)
5230 IF A$=CHR$(&H1E)
5240 IF SEL.NO=0
THEN SEL.NO=SEL.NO-1 ELSE SEL.NO=SEL.NO+1
THEN SEL.NO=CMND(SECT.NO)
5250 IF SEL.NO>CMND(SECT.NO) THEN SEL.NO=1
5260 IF LV=0 AND SEL.NO<=5 THEN LY=SEL.NO
5270 IF LV=0 AND SEL.NO>5
5280 IF LV=1
THEN LY=SEL.NO+1
THEN LY=SEL.NO-1
5290 COLOR 4:LOCATE LX,LY:PRINT CMND$(SECT.NO,SEL.NO,0)
5300 GOTO *KY.IN
5310 *KY2
5320 IF A$<>CHR$(&HD) THEN GOTO *KY.IN
5330 *SEL.RET
5340 COLOR 0
5350 RETURN
5360 DATA ”SCREEN CONTROL”,”MEMORY TABLE OPERATION”,”LAMP, TOUCH SWITCH OPERATION”
5370 DATA ”TOUCH SWITCH INPUT”,”SYSTEM CONTROL”,”CHARACTER SIZE”
5380 DATA ”CHARACTER DISPLAY ATTRIBUTE”,”CHARACTER-STRING DISPLAY”,”FIGURE DISPLAY”
5390 DATA 2
5400 DATA ”Display specified screen”,”[ESC]0”
5410 DATA ”Request screen number”,”[ESC]X”
5420 DATA 4
5430 DATA ”Write character-string memory table”,”[ESC]B”
5440 DATA ”4-digit write numeral table”,”[ESC]C”
5450 DATA ”8-digit write numeral table”,”[ESC]D”
5460 DATA ”Copy memory table”,”[ESC]/”
5470 DATA 3
5480 DATA ”Lamp and touch switch display (bit specification)”,”[ESC]K”
5490 DATA ”Lamp and touch switch display (address specification)”,”[ESC]Q”
5500 DATA ”Lamp and touch switch display status enguiry”,”[ESC]R”
5510 DATA 2
5520 DATA ”Touch switch disable”,”[ESC]U”
5530 DATA ”Touch switch enable”,”[ESC]V”
5540 DATA 3
5550 DATA ”Screen display control”,”[ESC]P”
5560 DATA ”Buzzer control”,”[ESC]T”
5570 DATA ”Mode Transition Enable”,”[ESC]W”
232
EXAMPLE PROGRAM
5580 DATA 3
5590 DATA ”Clear screen”,”[ESC]&”
5600 DATA ”Character specify size”,”[ESC])”
5610 DATA ”Specify character enlargement”,”[ESC]*”
5620 DATA 5
5630 DATA ”Normal display”,”[ESC]!”
5640 DATA ”Set inverse display”,”@@@@@@”
5650 DATA ”End inverse display”,”[ESC]#”
5660 DATA ”Set flashing display”,”[ESC]$”
5670 DATA ”End flashing display”,”[ESC]%”
5680 DATA 2
5690 DATA ”Set cursor position”,”[ESC]+”
5700 DATA ”Specify displayed characters”,”[ESC]4”
5710 DATA 2
5720 DATA ”Draw polyline”,”[ESC]7”
5730 DATA ”Draw circle”,”[ESC]8”
Section 6-7
233
234
SECTION 7
Troubleshooting and Maintenance
This section describes the action to take when NT20S errors occur, and how to carry out maintenance and inspections to prevent the occurrence of errors.
7-1 Hardware Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Responding to Displayed Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2-1 Errors Occurring when the Power is Turned ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2-2 Errors Occurring During Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2-3 Errors Occurring on Screen Data Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2-4 Communication Errors
7-3 Maintenance of the NT20S
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
236
237
237
237
237
237
239
241
235
Hardware Faults Section 7-1
7-1 Hardware Faults
When a fault relating to the operation of the NT20S occurs, find the symptoms in the table below and respond by following the corresponding “Remedy” indicated in the table.
NT20S Symptoms
POWER LED fails to come ON
Nothing is displayed on the screen (it is completely white).
Communication with the support tool not possible.
Cause
Power is not being supplied.
Power supply fuse has blown
Screen #0 has been read at the host side.
Remedy
Check the connections and make sure that power is supplied correctly.
(Refer to “2-2-3 Power Supply Connection”, page 29.)
Contact your OMRON service center.
This is not an error. Change the screen number.
(Refer to “4-3 Screen Display”, page 122.)
The Transmit Mode has not been established.
Not connected to the support tool.
Cannot communicate with the PC/Host.
The PT type/direct connection settings made at the support tool do not agree with the NT20S.
Memory switch settings do not match.
NT20S and PC are not correctly connected.
Buzzer sounds, RUN LED is OFF.
When NT link (1:N), there is unit number duplication.
Power not supplied to the NT20S,
PC, or host
Malfunction due to external noise.
Display the system menu and select the Transmit
Mode.
(Refer to “3-6 Registering the Screen Data”, page 86.)
Check the installation of the connector cable.
(Refer to “2-3 Connecting to the Support Tool”, page
31.)
Make the PT type setting and direct connection setting in the “tool settings” of the support tool agree with the
NT20S.
Check the communication setting in the “Memory
Switch” menu of the Maintenance Mode, and match the PC and NT20S settings.
(Refer to “3-5 Setting the Conditions of
Communications with the PC/Host by Using the
Memory Switches”, page 75.)
Check that the type, length and installation of the connector cable match the specifications.
(Refer to “2-4 Connection to a PC by the Host Link”, page 32, “2-5 Connection to a PC by the NT Link”, page 45, and “2-8 Host Connections by RS-232C”, page 63.)
Set again with no duplication.
Check the power supply.
Touch panel does not respond
PC mode changes to monitor mode.
Malfunction due to external noise
Touch panel is broken.
The NT20S changes the mode during host link communication.
Distance the communication cable from the source of the noise and insert a noise filter in the power supply line.
Distance the communication cable from the source of the noise and insert a noise filter in the power supply line.
Check the touch panel by performing the touch panel test in the I/O check in the maintenance mode.
This is normal with the NT20S specification. When using a PC that can also be connected using the NT link, connect it with the NT link (the mode is not changed when using the NT link).
236
Responding to Displayed Error Messages Section 7-2
7-2 Responding to Displayed Error Messages
When the NT20S displays an error message, find the corresponding symptoms in the appropriate table below and respond by following the “Remedy” indicated in the table.
7-2-1 Errors Occurring when the Power is Turned ON
The table below shows the errors that can occur when the power supply to the
NT20S is turned ON, and their remedies.
Message
Screen Data Corrupted
Mark Data Corrupted
(
No direct information is set!
(NT20S-ST121-EV3/
ST
/
Cause
There is an error in the registered screen data.
There is an error in the registered mark data.
The allocated words for the PT status control area and PT status notify area have not been set .
There is no screen data.
Remedy
After initializing the screen data memory in the
Maintenance Mode, transmit the screen data once more with the support tool.
After initializing the screen data memory in the
Maintenance Mode, transmit the screen data once more using the support tool.
Use the support tool to set the head words of the PT status control area and PT status notify area, and transmit the screen data again.
Transmit screen data from the support tool.
7-2-2 Errors Occurring During Operation
The table below shows the errors that can occur during operation of the NT20S, and their remedies.
Message
Setting Error
QQ command is not available
Cause
Bits or words allocated to the PC memory cannot be found in the screen data.
The PC cannot be connected to the
NT20S.
Remedy
Check the memory area in the PC used and correct the bit and word allocations in the screen data.
Select a type of PC that can be connected to the
NT20S.
7-2-3 Errors Occurring on Screen Data Initialization
The table below shows the errors that can occur when data is written to the NT20S screen data memory, and their remedies.
Message
Initialization Error
Cause
Hardware fault or screen data memory life reached
Remedy
If the same message is displayed even after executing screen data memory initialization or screen data transmission several times, contact your OMRON service center.
7-2-4 Communication Errors
This section describes the errors relating to communication with the PC/Host that can occur during operation, and their remedies.
S Operation when a communication error occurs
When a communication error occurs, the error message is displayed at the
NT20S, and the buzzer sounds. Error messages are displayed when the “Automatic Reset” memory switch is not set.
237
Responding to Displayed Error Messages Section 7-2
Some error messages are displayed even if the “Automatic Reset” memory switch is set.
S
Procedure when a communication error occurs
When an error message is displayed, press the [EXIT] touch switch displayed on the screen. The screen display will return to the RUN mode.
S Display of communication errors
As shown below, communication errors are displayed in the center of the screen, together with a classification indicating whether they are receive or send errors.
[Screen when an error has occurred during reception]
RECEIVING ERROR
EXIT
<Error Description>
Parity Error
Overrun Error
Overflow Error
Framing Error
Buffer Overflow
Time Out
NAK Received
Unit No. Error
FCS Error
[Screen when an error has occurred during sending]
SENDING ERROR
EXIT
<Type of error>
Time Out
238
Maintenance of the NT20S Section 7-3
(ACIA)
Message
Parity Error
Overflow Error
Buffer Overflow
Time Out
NAK Received
(end code simultaneously displayed)
Unit No. Error
FCS Error
Cause
Communication parameters/ conditions of communications set incorrectly.
Remedy
Check whether the parity bit, frame length, baud rate, stop bit length, and flow control settings of the PC match the settings of the NT20S.
Noise caused data corruption during communication.
The connectors of the connecting cable are not connected correctly.
The NT20S receive buffer is full.
Use a noise-resistant cable if communication occurs in an environment with high levels of noise.
Reconnect the cable.
Lengthen the command transmission intervals. If this error occurs frequently, set flow control for communications.
Reconnect the cable.
The connectors of the connecting cable have become disconnected.
The PC is stopped.
During transmission of one command a time lapse exceeding 5 seconds is detected.
Make sure the PC is able to communicate with the
NT20S.
Confirm the proper command length.
Reconnect the cable.
Noise caused data corruption during communication.
Use a noise-resistant cable if communication occurs in an environment with high levels of noise.
Check the end code by referring to the PC user’s manual.
The unit # does not match that set on the PC.
Set the PC unit # to “0”.
The PC is transmitting incorrect data. Check PC operation.
Noise caused data corruption during communication.
Use a noise-resistant cable if communication occurs in an environment with high levels of noise.
The PC is transmitting incorrect data. Check PC operation.
Noise caused data corruption during communication.
Use a noise-resistant cable if communication occurs in an environment with high levels of noise.
7-3 Maintenance of the NT20S
Carry out maintenance work in order to ensure that the NT20S is always used in its optimum condition.
Spare PT
Backlight
WARNING: Do not attempt to take the PC apart and do not touch any internal parts while the power is being supplied. Doing either of these may result in electrical shock.
It is advisable to have a spare NT20S available to minimize system downtime in the event of an NT20S failure or if the screen display becomes difficult to read due to deterioration of the display unit.
When the backlight in the display is getting dim and the screen cannot be read easily, replace the backlight. The backlight can be replaced at the rear of the NT20S while it is mounted in an operation panel.
S Replaceable Backlight Model
NT20S-CFL01
239
Maintenance of the NT20S Section 7-3
S
Guide to Backlight Replacement
Under normal conditions it can be assumed that the backlight will need to replaced after about 20,000 hours. However, the life of the backlight does vary in accordance with the environment in which it is used and it should be replaced when it is getting dim and the screen is getting hard to read.
Replacing the Backlight
WARNING: Turn off the power before replacing the backlight. Otherwise you could sustain an electric shock.
Operation 1. Switch the power to the NT20S off, remove the screw from the backlight replacement cover using a Philips screwdriver, and open the cover. Then disconnect the backlight connector from the NT20S.
2. Pull out the T-shaped backlight loading tool and replace the backlight.
3. Re-install the backlight and connect its connector to the NT20S.
Close the cover and tighten the screw with a flat-head screwdriver.
240
Inspection and Cleaning Section 7-4
7-4 Inspection and Cleaning
Clean and inspect the NT20S regularly to ensure that it is always used in its optimum condition.
Cleaning Method
Inspection Method
If the display is dirty the screen is difficult to see. Clean the screen from time to time as follows.
S In daily cleaning, wipe the display with a soft dry cloth.
S If the soiling cannot be removed with a dry cloth, wet the cloth with water, wring it out well and wipe the display with it.
S
If rubber or vinyl products, tape, etc. are left stuck to the display for long periods they will cause staining. If such items are stuck to the display, remove them during cleaning.
Note: Never use volatile solvents such as benzene or thinners, or dusters.
In normal environments, inspect the NT20S at intervals of between 6 months and a year. In environments that are extremely hot and humid, or very dusty environments, shorten the inspection interval.
S Items required for the inspection
Prepare the following items before starting the inspection.
- The tools supplied with the NT20S
- Screwdrivers (Philips, flat-head)
- Tester (or digital voltmeter)
- Industrial alcohol
- 100% cotton cloth
- Hygrometer (required in some cases)
- Thermometer (required in some cases)
- Synchroscope (required in some cases)
- Pen-writing oscilloscope (required in some cases)
241
Inspection and Cleaning Section 7-4
S
Points inspected
Inspect the following points to determine if there is any divergence from the stated criteria. If there is, either improve the surrounding environment so that the values fall within the stated range, or adjust the NT20S.
Point Inspected
Power supply voltage
Ambient environmental conditions
Mounting conditions
Components with limited lives
Inspection Details
Fluctuation in power supply terminal voltage
Ambient temperature
(temperature in the operation panel)
Ambient humidity
(humidity in the operation panel)
Presence/absence of dust
Looseness of mounting brackets etc.
Connector connections of connecting cable
Looseness of screws in external wiring
Conditions of external connecting cables
Brightness of the backlight
Criterion
Permissible voltage fluctuation range
(24 VDC --15% +10%)
0 to 50_C
35% to 85%RH
Dust must not be settled
To be no looseness
Inspection Instrument
Tester
To be fully inserted and locked, with no looseness
To be no looseness Philips screwdriver
Faults such as incipient disconnections.
Must be sufficiently bright.
Backlight life:
Brightness is halved after about 20,000 hours in use.
Thermometer
Hygrometer
Visual inspection
Accessory tools
Visual inspection
Visual inspection
Note: S Do not attempt to disassemble the NT20S for repair or modification.
S
The disposal of the NT20S (and used backlights) may be regulated by national or local authorities. Dispose of them in accordance with the laws and regulations of the relevant country and local authority.
Reference: When replacing the NT20S after discovering a fault during inspections, note the following points:
S Be sure to switch the power OFF before replacement.
S
After replacement, check that the new NT20S is not subject to the same error.
S
If a faulty unit is returned for repairs, write as detailed a description of the fault as possible and send this description together with the unit to the OMRON address indicated on the back cover of this book.
242
Specifications Appendix A
APPENDIX A
Specifications
General Specifications
Item
Power supply voltage
Allowable power supply voltage range
Power consumption
Inrush current
Ambient operating temperature
Storage temperature
Ambient operating humidity
Operating environment
Resistance to electrostatic discharge
Electromagnetic field strength
Fast transient/burst noise
Damped oscillatory wave
Vibration resistance
Shock resistance
Dimensions (mm)
Weight
Enclosure ratings
Applicable standards
Specification
24 VDC
20.4 VDC to 26.4 VDC (24 VDC --15% +10%)
10 W max.
3 A max.
0 to +50_C (with no freezing)
--20 to +70_C
35 to 85% RH (with no condensation)
No corrosive gases.
Level 3 (IEC801-2)
In air 8 kV, contact 6 kV, indirect 7 kV
10 V/m (IEC801-3)
Power supply line: 2 kV (IEC801-4)
I/O line: 0.25 kV
Power supply line: 1 kV (IEC255-4)
10 to 22 Hz with 1.5 mm double amplitude for a total of 30 min. in X, Y, and Z directions.
22 to 500 Hz with 1.5 G {14.7 m/s 2 } acceleration in X, Y, and Z directions.
Durability: 30 G, 3 times each in X, Y, and Z directions.
Malfunction: 20 G, 3 times each in X, Y, and Z directions.
190 (W) x 110 (H) x 58 (D) mm
0.7 kg max.
Front panel:
Equivalent to IP65 (front face waterproof construction).
Rear case:
Terminals:
IP20
IP00
IEC1131-2 (1992)
EN50081-2 (1992)
243
Specifications Appendix A
Performance Specifications
Display Specifications
Item
Dot matrix of STN liquid crystal display panel
Backlight
(white cold cathode tube)
Indicators
Specification
Number of dots
(resolution)
128 dots (vertically) x 256 dots (horizontally) (dot size: 0.407 mm)
Effective display area 56 mm (vertically) x 112 mm (horizontally)
Display mode £ 1
View angle
Life expectancy
Life expectancy
Automatic turn-off
Blue mode (NT20S-ST12j)
Monochrome mode (NT20S-ST16j)
Left/right direction: 35_
50,000 hours minimum
10,000 hours minimum
(average: 20,000 hours) £ 2
Can be set to turn off in 10 minutes or 1 hour, or to remain on.
POWER indicator
(Green LED)
RUN indicator
(Green LED)
Lit while power is being supplied.
Lit during operation
£ 1: The contrast in the monochrome mode is five times that in the blue mode.
£ 2: This is the time it takes for the brightness to decline to half its original value under normal temperature and humidity conditions.
Panel Specifications
Touch panel
Item Specification
Number of switches: Max. 72 registerable per screen
(6 vertically x 12 horizontally)
Input: Pressure-sensitive type
Operating force: 100 gf min.
Life expectancy: 1 million operations minimum
244
Specifications Appendix A
Display Capacity p y elements
Character displays
Character string displays
Numeral displays £
Graph displays £
Graphic displays
Lamps
Touch switches
Numeral settings £
Normal screen
Overlapping screens
Continuous screens
Screen attributes
Max. number of registered screens
Screen registration method
Screen saving method
(screen data memory)
Specification
NT20S-ST121-EV3/ST122-V1 NT20S-ST128
Fixed character data (character strings registered for each screen)
128 strings per file (32 bytes per string), 32 positions per screen
50 positions per screen, 8-digit display
50 per screen
Can be displayed wherever required
128 per screen
72 per screen
Max. 256 strings per file
Max. 256 strings per file
Display of set numerical values 50 per screen
Displays screens registered as normal.
A maximum of 8 registered screens can be displayed overlapped with each other.
A maximum of 8 screens can be displayed sequentially by scrolling.
(The screen can be changed by pressing the and touch switches)
Buzzer, numeral setting
495
Transfer screen data created using the support tool to the PT.
Saved to flash memory (recording format unique to NT20S)
£ : Number of numeral memory tables that can be set (number used for numeral display + number used for graphs + number used for numeral settings) ≦ 128
Display Element Specifications
Smoothing processing
Character display attributes
Graphics
Data Quantities
Item
Enlargement function
Specification
Half-size characters (8 x 8 dots): Alphanumerics and symbols
Normal characters (8 x 16 dots): Alphanumerics and symbols
Marks (16 x 16 dots): User-defined pictographs
Horizontal and vertical magnifications of double width,double height,4x, 9x, and
16x
Enlarged characters up to 4x
Normal, inverse, flashing, inverse flashing
Continuous straight lines, circles
Strings
Numeral data
Marks
Touch switches
Lamps
Item Specification
NT20S-ST121-EV3/ST122-V1
128 strings comprising 32 characters each
128 max. (8 digits each)
64 marks
No maximum restriction
No maximum restriction
NT20S-ST128
Max. 256 strings per file
Max. 256 strings per file
245
Specifications Appendix A
Special Features
Buzzer
Item
Maintenance functions
Key input sound setting
Specification
Two types: Continuous sound and intermittent sound
Setting: Set “key press sound” in the “Memory Switch” menu of the
Maintenance Mode ON.
If “ERR ON” is set the buzzer only sounds when an error occurs.
ON: The buzzer sounds on designation from the PC, when a screen with a buzzer-ON specification is called, or on display of an error screen such as for a receive error.
OFF: The buzzer is turned off on designation from the PC, by touch switch input, or when a screen without a buzzer-ON specification is displayed.
Sound pressure: Min. 80 dB, average 87 dB (measured 10 cm from front face)
S
Self-test for memory, switches, etc.
S
Status setting confirmation for communications and other conditions.
S
Simple communications confirmation.
0.2 second input sound when a touch switch is pressed
Setting: Set “key press sound” of the “Memory Switch” menu in the
Maintenance mode ON.
Communications Specifications
[For a Host Link] (NT20S-ST121-EV3)
Item
Communications standard
Communications settings
Connector
Number of units connected
Transmission distance
Communications protocol
EIA RS-232C
Start-stop synchronization
Baud rate: 9600, 19,200 bps
Data length: 7 bits
Stop bit:
Parity:
2 bits
Even
9-pin, D-SUB connector (female)
1 to 1
Max. 15 m
C-series SYSWAY (1:N)
Specification
[For an NT Link (1 to 1)] (NT20S-ST121-EV3)
Item
Communications standard
Connector
Number of units connected
Transmission distance
EIA RS-232C
9-pin D-SUB connector (female)
1 to 1
Max. 15 m
[For an NT Link (1:N)] (NT20S-ST121-EV3)
Item
Communications standard
Connector
Number of units connected
Transmission distance
Specification
Specification
EIA RS-232C
9-pin D-SUB connector (female)
1:1 to 8
S
RS-232C cable : Max. 2 m (*)
S
RS-422A/485 cable : Total length 500 m (*)
(*) When NT-AL001 used
246
Specifications
[For RS-232C] (NT20S-ST128)
Item
Communication standard
Communication settings
Connector
Number of units connected
Transmission distance
Specification
EIA RS-232C
Start-stop synchronization
Baud rate: 2400/4800/9600/19200 (bps)
Data length: 7, 8 bits
Stop bit: 1, 2 bits
Parity: Even/Odd/None
Flow control:RS/CS control
XON/XOFF control
None
9-pin D-SUB female
1-to-1
Max. 15 m
Appendix A
247
Dimensions
[Outside Dimensions]
178 (7.00)
APPENDIX B
Dimensions
Appendix B
POWER
RUN
[Dimensions for Installation]
190 (7.48)
4.5 (0.17)
58 (2.28)
Unit: mm (in.)
15.5 (0.61)
140 (5.51)
NT20S
Installation fitting
Installation panel
34 (1.34)
(min.)
38 (1.5)
(max.)
Unit: mm (in.)
248
Handling the RS-232C/RS-422 Converter Unit Appendix C
APPENDIX C
Handling the RS-232C/RS-422A Converter Unit
This section shows the dimensions of the RS-232C/RS-422A converter unit (NT-AL001), and describes the methods for installing and removing it. Refer to this information when designing the control panel.
Dimensions
53.5
(2.11)
110
(4.33)
4
(0.16)
74.5 (2.93)
100.2 (3.94)
105 (4.13) or less
[30]
(1.18) om R on NT-AL001
45 (1.77)
30 (1.18)
Unit = mm (in.)
With RS-422A terminal block cover closed:
30 [1.18] (W) x 114 [4.49] (H) x 100.2 [3.94] (D) mm [in.]
With RS-422A terminal block cover open:
30 [1.18] (W) x 114 [4.49] (H) x 119.5 [4.7] (D) mm [in.]
Installation and Removal
The RS-232C/RS-422A converter unit (NT-AL001) is installed on a DIN rail or in an operation panel.
The RS-422A terminal block of the converter unit can easily be removed.
249
Handling the RS-232C/RS-422 Converter Unit Appendix C
Installation on a DIN Rail
Hook the top part of the rear of the converter unit ((a) in the figure) onto the top edge of the DIN rail, and push the unit in direction (b).
Then fit end plates on the right and left sides of the converter unit so that the unit cannot shift sideways.
(a)
(b)
Removal from the DIN Rail
Remove the end plates at right and left, then insert a flat-tipped screwdriver into the rail stopper on the bottom of the unit and pry the unit away.
Installation in an Operation Panel
Make two screw holes in an operation panel wall at least 2 mm thick and secure the converter to the wall with screws.
30
(1.18)
100 (3.94) 110 (4.33)
21
(0.83)
2-M4
Unit = mm (in.)
Note: In order to ensure a strong installation, the wall of the operation panel must be at least 2 mm thick.
250
NT20S Installation Environment Appendix D
APPENDIX D
NT20S Installation Environment
When installing the PT in the operation panel, observe the following points. See also the section “Getting Starting”.
S The view angle of the LCD display screen is 40_. Install it at a position and height where operators will be able to see it well.
Caution: S Do not install at a site exposed to chemicals, steam, etc, or subject to excessive airborne dust.
S Do not install the unit at locations where the ambient temperature goes outside the range 0 to
50_C or where the relative humidity goes outside the range 35 to 85% RH.
If the ambient temperature exceeds the range indicated above, install a fan or an air conditioner.
S
Do not install the unit directly above equipment that generates a lot of heat (heaters, transformers, large capacity resistors, etc.)
S Take the following points into account in order to prevent noise
(4) Avoid installing the unit in panels in which high-voltage equipment is also installed.
(5) Install the unit at a distance of at least 200 mm from power lines.
(6) If the unit is installed next to equipment that generates a strong electric or magnetic field
(solenoids, etc.), provide a gap of at least 40 mm.
S Secure sufficient space for ventilation.
S Do not install in sites subject to severe vibration or strong shocks.
S Install at a distance from high-voltage devices and power equipment in consideration of operability and safety during maintenance.
Note: S The angle of visibility of the LCD display screen is 35 degrees to left and right. Install it at a position, height, and orientation that will make it easy for personnel to see it.
S Install the PT at a location as far as possible from personal computers, radio equipment, radios, etc. The electromagnetic waves generated by the PT will cause radio interference.
S When using the RS-232C +5V output, check the current capacity of the connected equipment. The maximum current value of the NT20S +5 V output is 150 mA.
Transportation and Storage of the PT
Note on transportation
Pack the PT in the packaging intended for it before transporting it.
Note on storage
Maintain the storage ambient temperature (-20 to 70 _C) and storage ambient humidity (35 to 85% RH).
251
NT20S Internal Processing Appendix E
APPENDIX E
NT20S Internal Processing
When the direct connection function is used, the following processing is executed inside the NT20S. Processing is divided into two types: periodic processing and event processing.
Periodic Processing (When Using Direct Connection)
The following processing is executed inside the NT20S to enable high-speed control from the PC.
Usually, the only data read from the PC area the elements used for the currently displayed screen. Even if the contents of the PC words allocated to memory tables are changed, these contents are not updated at the PT unless the memory table is used for the displayed screen.
[NT20S (PT) processing] [Details of processing]
PT power ON
Initial processing
Operation start
Initial values written to the memory tables
Screen switching
Screen element registration
(PT → PC)
(PT → PC)
Hardware check, communication status check, etc., executed.
When the values registered in the NT20S are used as the initial values in the memory tables, these values are written into the allocated words of the PC.
In order to enable fast batch processing, the elements used in the displayed screen are registered in the PC in advance.
Approximately 120 words can be registered per screen.
The statuses of the registered elements are read from the PC and the display is changed.
The status of the elements that were in excess of the registrable number and could not be registered is read from the PC, and the display is changed. This processing is continued until the statuses of all the remaining elements has been read.
Reading of registered elements
(PT ← PC)
Reading of elements that could not be registered.
(PT ← PC)
Reading of the elements that could not be registered.
(PT ← PC)
Reading the PT status control area
(PT ← PC)
Reading of elements that could not be registered
Reading of elements that could not be registered
Reading of the PT status control area
(PT ← PC)
(PT ← PC)
(PT ← PC)
If the number of elements that could not be registered is large, the PT status control area is read after every two element readings.
: Processing performed if necessary
252
NT20S Internal Processing Appendix E
S
Number of words for screen element registration
The number of words used for screen element registration is as follows.
Allocated words: Number of words
Allocated bits : Number of words calculated by summing the number of bits in each area and taking 1 word to be 16 bits.
[Example]
Character string memory tables : 3 of 12 allocated words each
Numeral memory tables
Allocated bits for control
: 4 of 2 allocated words each
: 19 I/O relays, 7 link relays (contiguous bits)
The number of words assigned to character string memory tables and numeral memory tables is as follows:
12 words X 3 + 2 words X 4 = 44 words
The assignment for bits is as follows:
19 I/O relays ÷ 16 = 1 word with a remainder of 3 bits → 2 words
7 link relays ÷ 16 = 0 words with a remainder of 7 bits → 1 word
The total is therefore 44 words + 2 words + 1 word = 47 words
Elements occupying up to approximately 120 words, calculated in this way, can be registered. If the number of elements is larger than this, internal processing is increased in proportion to the excess number and this generates a delay in processing.
If the point where the registrable quantity is exceeded is in the middle of an element that spans several words (for example a character string memory table), registration is quit without registering that element.
S Order of priority for registration
Elements are registered in the following order of priority according to their type.
(1) Allocated words of the PT status control area
(2) Allocated bits for control (lamps, touch switches)
(3) Allocated words of numeral memory tables
(4) Allocated words of character string memory tables
If there is more than one element for each of (2) through (4), the elements are registered in accordance with the following priority of word and bit areas:
(1) Data memory (DM)
(2) I/O relays (CH)
(3) Timers (TIM)
(4) Counters (CNT)
(5) Holding relays (HR)
(6) Auxiliary relays (AR)
Within each area, words and bits are allocated from the smallest number up.
253
NT20S Internal Processing Appendix E
Event Processing (When Using Direct Connection)
When the status of the NT20S changes during operation, the processing for writing the changed data to the relevant area of the PC memory is executed.
This kind of processing is only executed when statuses change. When changes occur simultaneously, the processings are executed in accordance with the order of priority.
[NT20S processing]
High
Writing to PT status notify area
Bit writing
(PT → PC)
(PT → PC)
Writing to numeral memory tables (PT → PC)
Low
Writing to character string memory tables (PT → PC)
[Details of processing]
Writing to the PT status notify area in order to inform the PC of changes in the PT operation status.
Updating the contents of words allocated to the PC when the value in a numeral memory table has changed.
Updating the contents of words allocated to the PC when the contents of a character string memory table have changed.
Writing to bits in order to inform the PC of touch switch statuses.
Data is only written to PC bits and numeral/character string memory tables for elements in screens currently being displayed. If the contents of numeral/character string memory tables that are not being displayed change, the changed data is not written to the PC.
254
Function Restrictions Depending on the Support Tool Appendix F
APPENDIX F
Function Restrictions Depending on the Support Tool
Screens can be created for an NT20S-ST121-EV3/ST122-V1 by using the conventional support tools indicated below.
S NT series NT20M/NT2000M/NT600M support tool (Ver.4.j)
In addition, the NT series support tool (Ver.2.j) can be used with Ver.4 of the direct connection function.
However, when the above support tools are used or Ver.4 direct connection is used, restrictions apply to some functions, as shown in the table below.
The expressions used for support tools in the table have the following meanings.
NTM V4 : NT series NT20M/NT2000M/NT600M support tool (Ver.4.j)
NT V2 : NT series support tool (Ver.2.j)
Support Tool NT Model Direct Connection Communication Mode
Support Tool
Mode
(NT20S memory switch)
Restrictions
NTM V4
NT V2
NT20M
NT20M
NT20S
NT20S
OMRON
Ver. 4
Ver. 4
Ver. 5
-- (Standard)
Standard
NT20M
NT20M
Standard/High-speed NT20S
Standard/High-speed NT20S
Max. 250 screens, Thumbwheel numeral settings not possible, no upper/lower limits, hexadecimal input not possible, indirect specification not possible, touch switch input notification fixed as “momentary”, data transmission in screen units not possible.
No restriction
The NT20S cannot be used with combinations of support tools and settings other than those indicated above.
Reference: The NT20S-ST128 can be used in the same way with the NT series support tool (Ver.2.j). The necessary support tool and “Support Tool Mode” (NT20S memory switch) settings in this case are as follows:
NT Model : NT20S
Direct setting : No
Communication mode : Standard/High-speed
Support Tool Mode : NT20S
255
Method for Making the Cable for Connection to the Host Appendix G
APPENDIX G
Method for Making the Cable for Connection to the Host
Explained below is the method for making the cable that connects the NT20S-ST121-EV3/ST128 with the PC.
Connect the wires to the connectors in accordance with the connector specification for each unit.
Parts Required
Two connectors, two connector covers and one cable are required to make up a connecting cable. One connector and one connector cover is supplied with most PCs.
The parts supplied with each unit are indicated in the table below.
Name
Connector
Connector cover
Model
XM2A-0901
XM2A-2501
DB-25P
XM2S-0911
XM2S-2511
DB-C2-J9
Delivered with
C series CQM1
CVM1/CV series CPU unit
CV500-LK201
C500-LK203
C500-LK201
C200H-LK201
C500-LK201-V1
C120-LK201-V1
C series CQM1
CVM1/CV series CPU unit
CV500-LK201
C500-LK203
C500-LK201
C200H-LK201
C500-LK201-V1
C120-LK201-V1
Remarks
9-pin, manufactured by OMRON
25-pin, manufactured by OMRON
25-pin, manufactured by JAE
9-pin, manufactured by OMRON
25-pin, made by OMRON
25-pin, made by JAE
When connecting the NT20S to a CjjH PC manufactured by OMRON, the connector and connector hood must be prepared separately since they are not supplied with the CjjH.
The connector provided in the CPU unit of the CjjH is a 9-pin connector. For the connection, the following connector and connector hood should be prepared.
S Connector : XM2A-0901 (9-pin, OMRON)
S Connector cover : XM2S-0911 (9-pin, OMRON)
Use the cable recommended by OMRON.
The recommended cables are indicated in the table below.
Name Remark
AWG28×5P
IFVV-SB
CO-MA-VV-SB
5P×28AWG
Model
Multiconductor shielded cable (FUJIKURA, Ltd.)
Multiconductor shielded cable (HITACHI Cable, Ltd.)
256
Method for Making the Cable for Connection to the Host Appendix G
Connector Specifications and Wiring for OMRON Units
The combination of pin numbers to which the connecting wires are connected differs according to the connector specifications for each unit. Check the connector specifications of the unit to be connected and make the wiring connections for the items in the connection combination indicated below which are applicable.
[NT20S Connector Specifications (9-pin)]
S Electrical characteristics: Complies with EIA RS-232C
S Signal direction: Signal input and output is relative to NT20S.
1 6
5
9
Connector
Pin No.
4
5
6
9
2
3
Send data
Receive data
Request to send
Clear to send
+5 V output, 150 mA max.
Signal ground
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
+5V
SG
Signal Direction
Input Output f f f f
-f
--
Correct Use: If using the +5 V supply of pin No.6, check first that the equipment that is to receive the supply has a current capacity no greater than 150 mA. The +5 V output of the NT20S is +5 V5%, max. 150 mA.
Connecting an NT20S to a C-Series Host Link
S C-Series Host Link Unit 25-pin Connector Specifications
Applicable Host Link Unit: C200H-LK201(-V1)
C500-LK201-V1
C500-LK203
C120-LK201-V1
S
Electrical characteristics: Complies with EIA RS-232C
S
Signal direction: Signal input and output is relative to the PC.
1
13
14
25
Connector
Pin No.
14
15
5
7
3
4
1
2
17
20
24
Frame ground
Send data
Receive data
Request to send
Clear to send
Signal ground
Optical connector +5V (see note 2)
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
SG (GND)
+5V
Send signal element timing 2 (see note 1) ST2
Receive signal element timing
(see note 1)
RT
Data terminal ready
Data signal element timing (see note 1)
ER (DTR)
ST1 f f
Note 1. No element timing signals on C200H-LK201(-V1)
2. C500-LK201 and C200H-LK201(-V1) only f
--
-f
Signal Direction
Input Output
--f f
--
-f f
257
Method for Making the Cable for Connection to the Host Appendix G
S
Wiring Connections
The NT20S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see £ in the figure).
Connect the cable shielding wire to the connector cover and pin 1 at the host link unit end of the cable only.
NT20S
RS-232C interface
Abbreviatioon
SD
RD
RS
CS
SG
Pin number
7
8
5
6
9
3
4
1
2
Shielding wire
£
PC (host link unit)
Pin number
7
8
5
6
3
4
1
2
--
--
--
--
20
Abbreviatioon
25-pin connector
FG
SD
RD
RS
CS
--
SG
--
--
ER
--
--
--
Connecting an NT20S to a C-Series CPU (CjjH)
S C-Series CPU Unit (CjjH) 9-pin Connector Specifications
S Applicable CPU: C20H/C28H/C40H/C60H
S Electrical characteristics: Complies with EIA RS-232C
S Signal direction: Signal input and output is relative to the PC.
RS-232C interface
1
5
6
9
Connector
Pin No.
4
5
7
1
2
3
Frame ground
Send data
Receive data
Request to send
Clear to send
Signal ground
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
SG (GND)
Signal Direction
Input Output
--f f f f
---
258
Method for Making the Cable for Connection to the Host Appendix G
S
Wiring Connections
The NT20S does not use pin 4 (RS) or pin 5 (CS). Short the RS and CS pins of the PC connector together (see the figure).
£ in
Connect the cable shielding wire to the connector cover and pin 1 at both the NT20S and CPU ends of the cable.
NT20S PC CPU
RS-232C interface
Abbreviatioon
SD
RD
RS
CS
--
--
--
SG
Pin number
1
2
3
4
5
6
7
8
9
Shielding wire
£
Pin number
Abbreviatioon
1
2
3
4
5
6
CS
--
7
--
SG
--
--
9-pin connector
--
FG
SD
RD
RS
Connecting an NT20S to a CVM1/CV-Series Host Link Unit
RS-232C interface
S CVM1/CV-Series Host Link Unit Connector Specifications
S Applicable host link unit: CV500-LK201
S Electrical characteristics: Complies with EIA RS-232C
S Signal direction: Signal input and output is relative to the PC.
Communication Port 1 (25-pin Connector)
1
13
14
25
Connector Pin
No.
Connector cover Frame ground
1
2
3
Frame ground
Send data
Receive data
4
5
7
Request to send
Clear to send
Signal ground
8
14
20
Carrier detected
Optical connector +5V
Data terminal ready
Communication Port 2 (9-pin Connector)
FG
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
SG (GND)
CD (DCD)
+5V
ER (DTR) f
-f
--
Signal Direction
Input Output
---
--f f f
-f f
1
5
6
9
Connector
Pin No.
Connector cover Frame ground
2 Send data
3
4
Receive data
Request to send
5
9
Clear to send
Signal ground
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
SG (GND)
Signal Direction
Input Output
--f f f f
---
259
Method for Making the Cable for Connection to the Host Appendix G
S
Wiring Connections
CVM1/CV-series host link units have two types of connector, which must be wired differently.
The NT20S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see £ in the figure).
Connect the cable shielding wire to the connector cover and pin 1 at the host link unit end of the cable only.
Communication Port 1 (25-pin Connector)
NT20S
RS-232C interface
Abbreviatioon
--
--
--
SG
SD
RD
RS
CS
Pin number
1
2
5
6
3
4
7
8
9
Shielding wire
£
PC (host link unit)
Pin number
Abbreviatioon
3
4
5
6
1
2
--
--
--
20
7
8
--
CS
--
SG
--
--
--
FG
SD
RD
RS
--
--
ER
25-pin connector
RS-232C interface
Communication Port 2 (9-pin Connector)
NT20S
RS-232C interface
Abbreviatioon
SD
RD
RS
CS
SG
Pin number
7
8
5
6
9
3
4
1
2
Shielding wire
£
PC (host link unit)
Pin number
Abbreviatioon
6
7
4
5
--
9
2
3
Connector cover
CS
--
CD
--
SG
FG
SD
RD
RS
9-pin connector
RS-232C interface
260
Method for Making the Cable for Connection to the Host Appendix G
Connecting an NT20S to a C-Series C200HS, C200HX/HG/HE, CPM1, CQM1, CVM1/CV-Series (-EVj)CPU
S
C-Series C200HX/HG/HE, CPM1, CQM1, CVM1/CV-Series (-EVj) CPU Unit 9-pin Connector Specifications
Applicable CPU:
CQM1-CPU21-E
CQM1-CPU41-E
CV2000-CPU01-EVj C200HS-CPU33-E C200HX-CPU34-E
CVM1-CPU01-EVj C200HE-CPU32-E C200HX-CPU44-E
CQM1-CPU42-E
CQM1-CPU43-E
CVM1-CPU11-EVj C200HE-CPU42-E C200HX-CPU54-E
CVM1-CPU21-EVj C200HG-CPU33-E C200HX-CPU64-E
CQM1-CPU44-E C200HS-CPU21-E
CV500-CPU01-EV1 C200HS-CPU23-E
CV1000-CPU01-EV1 C200HS-CPU31-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
Note: The host link function incorporated in CV/CVM1 CPUs (with the exception of -EVj) cannot be used.
S Electrical characteristics: Complies with EIA RS-232C
S Signal direction: Signal input and output is relative to the PC.
1 6
5
9
Connector
Pin No.
Connector cover Frame ground
2
3
Send data
Receive data
4
5
9
Request to send
Clear to send
Signal ground
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
SG (GND)
Signal Direction
Input Output
--f f f f
---
S
Wiring Connections
The NT20S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see £ in the figure).
NT20S
RS-232C interface
Abbreviatioon
--
--
--
SG
SD
RD
RS
CS
Pin number
1
8
9
6
7
4
5
2
3
Shielding wire
£
PC (host link unit)
Pin number
Abbreviatioon
Connector cover
2
3
4
5
--
--
--
9
CS
--
--
--
SG
FG
SD
RD
RS
9-pin connector
RS-232C interface
261
Method for Making the Cable for Connection to the Host Appendix G
Connecting an NT20S to an RS-232C/422A Converter Unit (NT-AL001)
Connecting an RS-232C/422A converter unit enables the transmission distance to be made greater than 15 m (up to 500 m).
NT-AL001
NT20S Host
RS-232C RS-422A
Max. 2 m Max. 500 m
Reference: When connecting the C200HX/HG/HE and an RS-232C/RS-422A converter unit, use a converter unit whose lot number is 15Y5 or later. Converter units of lot numbers previous to 15Y5 cannot be connected.
NT-AL001 RS-232C connector specifications (9-pin type)
Electrical characteristics: Comply with EIA RS-232C
Signal direction: Signal input and output is relative to the NT-AL001
1 6
5
9
Connector
Pin No.
Connector cover Frame ground
2
3
Send data
Receive data
6
9
4
5
Request to send
Clear to send
+5 V input
Signal ground
FG
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
+5V
SG (GND)
NT-AL001 RS-422A terminal block specifications
Connected terminal block: RS-422A terminal block (M3 screws)
Electrical characteristics: Comply with EIA RS-422A
Signal direction: Signal input and output direction is relative to the NT-AL001
Signal Direction
Input Output
--f f f f f
---
7
5
3
1
8
6
4
2
5
6
3
4
7
8
1
2
Frame ground
Signal ground
Send data (+)
Send data (--)
Receive data (+)
Receive data (--)
Request to send (+)
Request to send (--)
FG
SG
SDB
SDA
RDB
RDA
CSB
CSA
Signal Direction
Input Output
---
--f f f f f f
262
Method for Making the Cable for Connection to the Host
Wiring method
RS-232C interface
SD
RD
RS
CS
+5V
--
--
SG
9-pin
NT20S
Abbreviation
Pin No.
7
8
5
6
9
3
4
1
2
RS-232C
Pin No.
7
8
5
6
9
3
4
1
2
Abbreviation
FG
SD
RD
RS
CS
+5V
DSR
ER
SG
9-pin
NT-AL001
RS-232C interface
RS-422A interface
Abbreviation
FG
SG
SDB
SDA
RDB
RDA
CSB
CSA
Terminal block
Terminal
No.
7
8
5
6
3
4
1
2
Appendix G
RS-422A
HOST
Signal bame
Frame ground
Signal ground
Receive data(+)
Receive data(--)
Send data(+)
Send data(--)
RS-422A interface
263
Method for Making the Cable for Connection to the Host Appendix G
Preparing RS-232C Connector Cables
Prepare a connector cable to connect a NT20S to a Host separated by more than 5 m so that the standard connector cable cannot be used. The maximum cable length is 15 m.
Recommended Parts
Name
Connector
(NT20S)
Connector cover
(NT20S)
Cable
Model
XM2A-0901
XM2S-0911
9-pin, manufactured by OMRON
9-pin, manufactured by OMRON
Remarks
AWG28X5P
IFVV-SB
CO-MA-VV-SB
5PX28AWG
Multicore cable, manufactured by Fujikura, Ltd.
Multicore cable, manufactured by Hitachi Cable, Ltd.
On the other end of the cable use the type of connector and connector cover which matches the host computer connector type.
Connection For Host The shielding wire of the cable is connected at the host side only, to the connector cover and pin No.1.
The figure below shows the wiring when RS/CS control is used. If RS/CS control is not used, short RS and CS at both the NT20S side and host side.
NT20S
RS-232C interface
Abbreviation
CS
--
--
--
SG
FG
SD
RD
RS
Pin number
7
8
5
6
9
3
4
1
2
Shielding wire
HOST
Pin number
4
5
6
7
--
--
1
2
3
Abbreviation
CS
--
SG
--
--
FG
SD
RD
RS
(25-pin type)
RS-232C interface
264
Method for Making the Cable for Connection to the Host Appendix G
Making the Cable
The procedure to make up the cable is described below.
Refer to the following explanation when making an RS-422A cable also.
Cable Preparation
The preparation of the cable differs according to whether or not the shielding wire is to be connected to the FG.
S Cable with Shielding Wire Connected to FG
(1) Cut the cable to the required length.
(2) Remove the external vinyl insulation from the cable with a razor blade. Take care not to damage the shielding underneath.
(3) Cut back the shielding wire with scissors.
(4) Use wire strippers to strip the insulation from each wire.
(5) Fold back the shielding wire.
(6) Wrap aluminum foil tape around the folded-back shielding wire.
(1)
(2)
40(1.57)(RS-232C)
25(RS-422A)
(3)
10(0.39)
(4)
5(0.19)
(5)
(6)
[Units: mm (in.)]
Aluminum foil tape
265
Method for Making the Cable for Connection to the Host Appendix G
S
Cable with Shielding Wire Not Connected to FG
(1) Cut the cable to the required length.
(2) Remove the external vinyl insulation from the cable with a razor blade. Take care not to damage the shielding underneath.
(3) Cut back the shielding wire with scissors.
(4) Use wire strippers to strip the insulation from each wire.
(5) Wrap vinyl tape over the cut off end of the shielding wire.
(1)
(2)
40(1.57)(RS-232C)
25(RS-422A)
(3)
(4)
(5)
5(0.19)
[Units: mm (in.)] Vinyl tape
266
Method for Making the Cable for Connection to the Host
Soldering
(1) Slide heat-shrink tube over each wire.
(2) Pre-solder each wire and connector cable.
(3) Solder each wire to the connector terminal.
Soldering iron
Heat-shrink tube
(Hishitube F, 1.5 dia, l = 10)
(4) Push the heat-shrink tube over the soldered joint and heat the tube to shrink it in place.
Heat-shrink tube
Connector Cover Assembly
Assemble the connector covers as shown in the diagram below.
Appendix G
End connected to FG
Aluminum foil tape
End not connected to FG
267
Making the cable for Connection to the Support Tool Appendix H
APPENDIX H
Making the Cable for Connection to the Support Tool
The wiring to be done depends on the type of RS-232C connector at the personal computer.
S For a 25-pin connector
7
8
5
6
20
3
4
1
2
CS
DR
SG
CD
ER
FG
SD
RD
RS Personal computer
SD
RD
RS
CS
SG
FG
2
3
4
5
7
1
Shielding wire
2
3
4
5
9
1
SD
RD
RS
CS
SG
FG
Peripheral device connector on PT body
When making the connecting cable, use the following recommended parts.
Name Model
XM2A-2501
XM2A-0901
XM2S-2511
XM2S-0911
AWG28¢5P
IFVV-SB
CO-MA-VV-SB
5P¢28AWG
Remarks
25-pin, manufactured by OMRON (personal computer side)
9-pin, manufactured by OMRON (PT side)
25-pin, manufactured by OMRON (personal computer side)
9-pin, manufactured by OMRON (PT side)
Multiconductor shielded cable (FUJIKURA, Ltd.)
Multiconductor shielded cable (HITACHI Cable, Ltd.)
S For a 9-pin connector
7
8
5
6
9
3
4
1
2
CD
RD
SD
DTR
SG
DR
RS
CS
Personal computer
RD
SD
RS
CS
SG
2
3
7
8
5
Shielding wire
2
3
4
5
9
1
SD
RD
RS
CS
SG
FG
Peripheral device connector on PT body
When making the connecting cable, use the following recommended parts.
Name Model
XM2D-0901
XM2A-0901
Connector cover XM2S-0911
AWG28¢5P
IFVV-SB
CO-MA-VV-SB
5P¢28AWG
Remarks
9-pin, manufactured by OMRON (personal computer side)
9-pin, manufactured by OMRON (PT side)
9-pin, manufactured by OMRON (two)
Multiconductor shielded cable (FUJIKURA, Ltd.)
Multiconductor shielded cable (HITACHI Cable, Ltd.)
268
Connecting to an RS-232C/RS-422A Converter Unit (1:1) Appendix I
APPENDIX I
Connecting to an RS-232C/RS-422A Converter Unit (1:1)
By using an RS-232C/RS-422A converter unit (NT-AL001), RS-232C can be converted to RS-422A, allowing longdistance communication of up to 500 m.
Connection Method
OMRON PC
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
RS-422A cable
(max. 500 m)
RS-232C cable
(max. 2 m)
RS-232C/RS-422A converter unit, type NT-AL001
NT20S
Wiring
S Wiring of RS-232C cable
PT or PC
Abbrev.
Pin No.
Connector cover
RS-232C interface
SD
RD
RS
CS
+5V
SG
4
5
2
3
6
9
The pin numbers are the numbers at the NT20S.
For the pin numbers at the PC, refer to the manual for the PC used.
Shielding wire
Pin No.
Connector cover
NT-AL001
Abbrev.
4
5
2
3
6
9
SD
RD
RS
CS
+5V
SG
Only connected at PC
RS-232C interface
269
Connecting to an RS-232C/RS-422A Converter Unit (1:1)
S
RS-422A Cable Wiring
RS-422A terminal block
NT-AL001
Abbrev.
FG
SDA
SDB
RDA
RDB
Pin No.
4
5
1
3
6
Shielding wire
DIP Switch Settings at RS-232C/RS-422A Converter Unit
Pin No.
1
3
4
5
6
NT-AL001
Abbrev.
FG
SDA
SDB
RDA
RDB
RS-422A terminal block
Appendix I
270
Model List
APPENDIX J
Model List
PT
Model
NT20S-ST121-EV3
NT20S-ST121B-EV3
NT20S-ST161-EV3
NT20S-ST161B-EV3
NT20S-ST122-V1
NT20S-ST122B-V1
NT20S-ST128
NT20S-ST128B
NT20S-ST168
NT20S-ST168B
Host Link Unit
Model
C120-LK201-V1
Host link/NT link Blue mode display
Host link/NT link Monochrome mode display
C200H direct communication
RS-232C
RS-232C
Blue mode display
Specification
Monochrome mode display
(Beige)
(Black)
(Beige)
(Black)
(Beige)
(Black)
(Beige)
(Black)
(Beige)
(Black)
Specification
S
Features a connector for RS-232C connections
S
Type mounted to a CPU
C200H-LK201(-V1)
C500-LK201-V1
C500-LK203
CV500-LK201
S
Features a connector for RS-232C connections
S
Type mounted to C200H base
Features a connector for RS-232C/RS-422A connections
(switchable type).
Type mounted to C500 base
S
Features a connector for RS-232C connections and a connector for RS-232C/RS422A connections
(switchable type).
S
Type mounted to base for CVM1/CV use.
Appendix J
Applicable PC
C-series
C120
C200H
C500(F)
C1000H
C2000(H)
C-series
C200H(S)/HE/HG/HX
C-series
( )
C1000H
C2000(H)
CVM1/CV-series
CV500
CV1000
CV2000
CVM1
271
Model List
CPUs (For Connection Via a Host Link)
Model Specification
C20H/C28H/C40H/C60H Features a 9-pin connector for RS-232C connections
CPM1-10CDR-j
CPM1-20CDR-j
CPM1-30CDR-j
CQM1-CPU21-E
CQM1-CPU41-E
CQM1-CPU42-E
CQM1-CPU43-E
CQM1-CPU44-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU32-E( £ )
C200HE-CPU42-E
C200HG-CPU33-E( £ )
C200HG-CPU43-E
C200HG-CPU53-E( £ )
C200HG-CPU63-E
C200HX-CPU34-E( £ )
C200HX-CPU44-E
C200HX-CPU54-E( £ )
C200HX-CPU64-E
CV500-CPU01-EV1
CV1000-CPU01-EV1
CV2000-CPU01-EV1
CVM1-CPU01-EV1
CVM1-CPU11-EV1
CVM1-CPU21-EV1
Connect an RS-232C adapter to the peripheral port.
Features a 9-pin connector for RS-232C connections
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Note: For CPU units marked ( £ ), a communications board is required.
Appendix J
C-series
C20H
C28H
C40H
C60H
C-series
CPM1
PC Type
C-series
CQM1
C200HS
C-series
C200HE
C-series
C200HG
C-series
C200HX
CVM1/CV-series
CV500
CV1000
CV2000
CVM1
272
Model List
CPUs (For Connection Via an NT Link (1:1))
Model
CPM1-10CDR-j
CPM1-20CDR-j
CPM1-30CDR-j
CQM1-CPU41-E
CQM1-CPU42-E
CQM1-CPU43-E
CQM1-CPU44-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU32-E( £ )
C200HE-CPU42-E
C200HG-CPU33-E( £ )
C200HG-CPU43-E
C200HG-CPU53-E( £ )
C200HG-CPU63-E
C200HX-CPU34-E( £ )
C200HX-CPU44-E
C200HX-CPU54-E( £ )
C200HX-CPU64-E
CV500-CPU01-V1-EV1
CV1000-CPU01-V1-EV1
Specification
Connect an RS-232C adapter to the peripheral port.
Features a 9-pin connector for RS-232C connections
Features a 9-pin connector for RS-232C connections
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Features a 9-pin connector for RS-232C connections
CVM1-CPU01-V1-EVj
CVM1-CPU11-V1-EVj
CVM1-CPU21-EVj
Note: For CPU units marked ( £ ), a communications board is required.
CPUs (For Connection Via an NT Link (1:N))
Model
C200HE-CPU32-E( £ )
C200HE-CPU42-E
C200HG-CPU33-E( £ )
C200HG-CPU43-E
C200HG-CPU53-E( £ )
C200HG-CPU63-E
C200HX-CPU34-E( £ )
C200HX-CPU44-E
C200HX-CPU54-E( £ )
C200HX-CPU64-E
Specification
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Features a connector for RS-232C connections
(selectable/9-pin)
Note: For CPU units marked ( £ ), a communications board is required.
PC Type
C-series
C200HE
C-series
C200HG
C-series
C200HX
Appendix J
C-series
CPM1
PC Type
C-series
CQM1
C200HS
C-series
C200HE
C-series
C200HG
C-series
C200HX
CV500
CV1000
CVM1-series
273
Model List Appendix J
CPU Unit (Connection by C200H Direct Communication)
Product Name Model
C20H-CjDR-DE-V1
C20H-CjDT-DE-V1
C28H-CjDR-DE-V1
C28H-CjDT-DE-V1
C40H-CjDR-DE-V1
C40H-CjDT-DE-V1
C60H-CjDR-DE-V1
C60H-CjDT-DE-V1
C200H-CPU01-E
C200H-CPU03-E
C200H-CPU11-E
C200H-CPU21-E
C200H-CPU23-E
C200H-CPU31-E
C200HS-CPU01-E
C200HS-CPU03-E
C200HS-CPU21-E
C200HS-CPU23-E
C200HS-CPU31-E
C200HS-CPU33-E
C200HE-CPU11-E
C200HE-CPU32-E
C200HE-CPU42-E
C200HG-CPU33-E
C200HG-CPU43-E
C200HG-CPU53-E
C200HG-CPU63-E
C200HX-CPU34-E
C200HX-CPU44-E
C200HX-CPU54-E
C200HX-CPU64-E
RS-232C/RS-422A Converter Unit
C20H
C28H
C40H
C60H
C200H
C200HS
C200HE
C200HG
C200HX
NT-AL001
Model Specification
RS-232C : 9-pin connector
RS-422A : 8-pin terminal block
RS-232C Adapter
Model
CPM1-CIF01
Specification
Connect the RS-232C port of the NT20S and the peripheral port of the CPM1.
274
Model List Appendix J
Related Parts and Equipment for PT
Name
Support Tool
Model
NT-ZA3AT-EV2
NT20S-CFL01
NT20M-KBA04
Parts Used for Connection
Cables with connectors
Remarks
3.5 inch FD for NT Series
Replaceable backlight
Reflection-suppressing protective sheet
Model
XW2Z-200S
XW2Z-500S
XW2Z-200T
XW2Z-500T
C200H-CN311
NT20M-CNP711
C200H-CN711
NT20M-CNP221
C200H-CN221
NT20M-CNP521
C200H-CN521
NT20M-CNP131
C200H-CN131
C20H-CN312
NT20M-CNP712
C20H-CN712
NT20M-CNP222
C20H-CN222
Cable Length
2 m
5 m
2 m
5m
30 cm
70 cm
2 m
5 m
10 m
30 cm
70 cm
2 m
Applicable Units
Host link units with 25-pin connectors
C200H, C200HS,
C200HX/HG/HE
Communication Method
Host link units and CPU units with Host link,
9-pin connectors NT link (1 to 1)
Connecting cables (for host link, NT link, RS-232C)
Model
AWG28¢5P
IFVV-SB
CO-MA-VV-SB
5P¢28AWG
Specification
Multiconductor shielded cable (FUJIKURA, Ltd.)
Multiconductor shielded cable (HITACHI Cable, Ltd.)
Applicable connectors (for host link, NT link, RS-232C)
Name
Connector
Model
XM2A-2501
XM2A-0901
DB-25P
Connector cover XM2S-2511
XM2S-0911
DB-C2-J9
Remark
25-pin, manufactured by OMRON
9-pin (Plug), manufactured by OMRON
25-pin, manufactured by JAE
25-pin, manufactured by OMRON
9-pin, manufactured by OMRON
25-pin, manufactured by JAE
275
Option List
Replaceable Backlight ... NT20S-CFL01
This is a backlight for replacement purposes.
APPENDIX K
Option List
Appendix K
Note: The disposal of used backlights may be regulated by national or local authorities. Dispose of them in accordance with the laws and regulations of the relevant country and local authority.
Reflection-Suppressing Protective Sheet ... NT20M-KBA04
Stuck to the display to prevent it from being soiled. The entire sheet is colorless and transparent.
276
Option List Appendix K
Chemical-resistant Cover .. Type NT20S-KBA01
Covers the front panel and protects it from chemical agents. The entire sheet is milky white and made of silicone rubber.
The protection the cover affords is summarized below.
Protects Against
Boric acid
Sulfuric acid
Nitric acid
Ammonia gas
Carbon dioxide
Phenol
Glycerin
Ammonia water
Calcium chloride
Developing fluid (“hypo”)
Acetaldehyde
Lard
Does Not Protect Against
Hexane
Lubricating oils
Benzene
Butane
Carbonic acid
Chlorinated solvents
Napthalene
Soya oil
Toluene
For information on protection against chemical agents not included in the table above, please ask OMRON. (If it is a chemical agent to which silicone rubber is recognized to be resistant, the cover can be used with confidence even if that chemical agent is not listed in the “Protects Against” column above.
Reference: S This cover does not afford protection against all chemical agents.
S Since the cover is milky white, it reduces the clarity of the display a little.
S This cover is intended to be affixed to the display in order to provide protection against chemical agents. It will not provide protection against chemical agents that enter through the installation panel or through the gap between the cover and the display.
277
PC Memory Map Appendix L
APPENDIX L
PC Memory Map
OMRON C-Series Memory Map
Area IR Area HR Area AR Area
Link Relay
Area
Timer/Count er Area
DM Area
Ladder type C20H
C28H
C40H
C60H
C120
C200H
C200HS
C200HE
C200HG
C200HX
C500
C1000H
C2000(H)
CQM1
0000 to 0255 0000 to 0099 0000 to 0027 0000 to 0063 0000 to 0511 0000 to 1999
0000 to 0063 0000 to 0031 0000 to 0127 0000 to 0051
0000 to 0255 0000 to 0099 0000 to 0027 0000 to 0063 0000 to 0511 0000 to 1999
0000 to 0063 0000 to 0031 0000 to 0031 0000 to 0127 0000 to 0511
0000 to 4095
0000 to 0255 0000 to 0099 0000 to 0027 0000 to 0063 0000 to 0051
0000 to 6655
CPM1
C500F
C1000HF
0000 to 0019
0200 to 0255 0000 to 0019 0000 to 0015 0000 to 0015 0000 to 0127
0000 to 0063 0000 to 0031
0000 to 1023
6144 to 6655
0000 to 0031 0000 to 0127 0000 to 0511
0000 to 0255 0000 to 0099 0000 to 0027 0000 to 0063 0000 to 0511 0000 to 4095
OMRON CV-Series Memory Map
Area IR Area HR Area ( £ 1) AR Area
Link Relay
Area
Timer/Counter
Area
DM Area
CV500
CVM1-CPU01(-Vj)
CV1000
CVM1-CPU011(-Vj)
CV2000
CVM1-CPU21(-Vj)
0000 to 2555
0000 to 2555
0000 to 0511
0000 to 0511
0000 to 0511 0000 to 8191
0000 to 1023
0000 to 9999
( £ 2)
( £ 1)
( £ 2)
Included in the IR area in the case of CVM1/CV-series PCs.
This is the area that can be used with an NT20S. The DM area itself occupies the range 00000 to 24575.
278
Special Characters Appendix M
APPENDIX M
Special Characters
English Character Codes
Pin 2 of SW2 must be ON to enable English language messages to use the following codes.
Example: Hex code is represented by 30, decimal code by 48, and character by 0.
30
48
0
Code 20 and 32 in the table represents a space, as indicated by “SP”.
Hex Digits
1st
2nd
-0
23-
0
4-
@
5-
P
6-
-1
-2
-3
-4
-5
-6
-7
-8
-9
-A
-B
-C
-D
-E
-F
35
24
36
25
37
26
38
27
39
33
22
34
23
20 SP 30
32
21 !
48
31
”
#
49
32
50
33
$
%
&
’
51
34
52
35
53
36
54
37
55
44
2D
45
2E
2B
43
2C
46
2F
47
41
2A
42
28
40
29
/
.
-
,
)
(
*
+
60
3D
61
3E
3B
59
3C
62
3F
63
57
3A
58
38
56
39
1
2
3
4
5
6
7
8
9
;
:
<
=
>
?
67
44
68
45
69
46
70
47
71
65
42
66
43
40
64
41
76
4D
77
4E
4B
75
4C
78
4F
79
73
4A
74
48
72
49
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
83
54
84
55
85
56
86
57
87
81
52
82
53
50
80
51
92
5D
93
5E
5B
91
5C
94
5F
95
89
5A
90
58
88
59
Q
R
S
T
U
V
W
X
Y
Z
]
\
[
^
_
99
64
100
65
101
66
102
67
103
97
62
98
63
60
96
61
6B
107
6C
108
6D
109
6E
110
6F
111
68
104
69
105
6A
106
‘ a b d e g h l j i c f k m n o
7p q s u v w x y z
}
|
{ r t
~
8-
115
74
116
75
117
76
118
77
119
70
112
71
113
72
114
73
7B
123
7C
124
7D
125
7E
126
7F
127
78
120
79
121
7A
122
131
84
132
85
133
86
134
87
135
80
128
81
129
82
130
83
8B
139
8C
140
8D
141
8E
142
8F
143
88
136
89
137
8A
138
Ç
ü
é
â
ä
à
å
ç
ê
ë
è
ï
î
ì
Ä
Å
9-
147
94
148
95
149
96
150
97
151
90
144
91
145
92
146
93
9B
155
9C
156
9D
157
9E
158
9F
159
98
152
99
153
9A
154
É
æ
Æ
ô
ö
ò
û
ù
ÿ
Ö
Ü
¢
£
¥
Pt
ƒ
279
Special Characters
Hex Digits
1st
2nd
-0
ABC-
-1
-2
-3
-4
-5
-6
-7
-8
-9
-A
-B
-C
-D
-E
-F
165
A6
166
A7
167
A8
168
A9
163
A4
164
A5
169
AA
170
AB
A0
160
A1
161
A2
162
A3
171
AC
172
AD
173
AE
174
AF
175
á
í
ó
ú
ñ
Ñ a o
¿
1 /
2
1 /
4
¡
«
»
∗1: Used as the prefix for mark data codes (2 bytes).
181
B6
182
B7
183
B8
184
B9
179
B4
180
B5
185
BA
186
BB
B0
176
B1
177
B2
178
B3
187
BC
188
BD
189
BE
190
BF
191
197
C6
198
C7
199
C8
200
C9
195
C4
196
C5
201
CA
202
CB
C0
192
C1
193
C2
194
C3
203
CC
204
CD
205
CE
206
CF
207
213
D6
214
D7
215
D8
216
D9
211
D4
212
D5
217
DA
218
DB
D0
208
D1
209
D2
210
D3
219
DC
220
DD
221
DE
222
DF
223
D-
Appendix M
FE-
229
E6
230
E7
231
E8
232
E9
227
E4
228
E5
233
EA
234
EB
E0
224
E1
225
E2
226
E3
235
EC
236
ED
237
EE
238
EF
239
ε
∩
∞
ø
245
F6
246
F7
247
F8
248
F9
243
F4
244
F5
249
FA
250
FB
F0
240
F1
241
F2
242
F3
251
FC
252
FD
253
FE
254
FF
255
_
¯
.
J
∗ 1 n
2
≡
≥
≤
⌠
⌡
÷
≈
Θ
Ω
τ
Φ
δ
Γ
π
α
β
Σ
σ
μ
280
INDEX
A
Allocatable bits and words . . . . . . . . . . . . . . . . . .
152
Allocated bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
Allocated word . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
Alternate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
181
Automatic reset . . . . . . . . . . . . . . . . . . . . . . . . . . .
238
Automatic reset function . . . . . . . . . . . . . . . . . . . . .
84
B
Backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . .
193, 239
Backlight OFF function . . . . . . . . . . . . . . . . . . . . . .
94
Backlight attributes . . . . . . . . . . . . . . . . . . . . . . . .
125
Backlight mode . . . . . . . . . . . . . . . . . . . . . . . . . . .
193
Bar graphs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
129
Batch lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
134
Baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
Before operating . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
Bit input attributes . . . . . . . . . . . . . . . . . . . .
125, 208
Bit touch switch . . . . . . . . . . . . . . . . . . . . . . . . . . .
125
Bit touch switch method . . . . . . . . . . . . . . . . . . . .
208
Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
193
Buzzer attribute . . . . . . . . . . . . . . . . . . . . . . . . . . .
193
Buzzer control . . . . . . . . . . . . . . . . . . . . . . . . . . . .
215
C
C200H/C200HS . . . . . . . . . . . . . . . . . . . . . . . . . . . .
60
C200H direct communication . . . . . . . . . . . . .
14, 58
CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42, 273
CjjH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
61
Cables with connectors . . . . . . . . . . . . . . . . . . . .
275
Cannot be normally started . . . . . . . . . . . . . . . . . .
72
Cannot communicate . . . . . . . . . . . . . . . . . . . . . .
236
Caution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xii, xiii
Changing displayed numerals or character strings . . . . . . . . . . . . . . . . .
169, 171, 174
Changing the contents of allocated words . . . . . . . . . . . . . . . . . .
169, 171, 174
Changing the lamp display status . . . . . . . . . . . .
179
Changing the status of allocated bits . . . . . . . . .
183
Changing the system settings . . . . . . . . . . . . . . . .
67
Character-string . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
Character-string memory table . . . . . . . . .
126, 168
Character specify size . . . . . . . . . . . . . . . . . . . . .
217
Characters . . . . . . . . . . . . . . . . . . . . . . . .
9, 119, 126
Checking the LCD . . . . . . . . . . . . . . . . . . . . . . . . .
103
Checking the LED . . . . . . . . . . . . . . . . . . . . . . . . .
105
Checking the PT setting . . . . . . . . . . . . . . . . . . . .
107
Checking the buzzer . . . . . . . . . . . . . . . . . . . . . . .
104
Checking the communications . . . . . . . . . . . . . . .
100
Checking the screen memory . . . . . . . . . . . . . . .
106
Checking the touch switches . . . . . . . . . . . . . . . . .
99
Child screens . . . . . . . . . . . . . . . . . . . . . . . .
122, 123
Classification of screens . . . . . . . . . . . . . . . . . . . .
122
Clear screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
216
Comm. check . . . . . . . . . . . . . . . . . . . . . . . .
101, 102
Comm. type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
Communication is automatically reset . . . . . . . . .
84
Communication procedure . . . . . . . . . . . . . . . . . .
201
Comparison between NT20S and NT20M . . . . . . .
7
Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Compatible PCs . . . . . . . . . . . . . . . . . . . . .
32, 45, 49
Connecting cables . . . . . . . . . . . . . . . . . . . . . . . . .
275
Connecting the NT20S . . . . . . . . . . . . . . .
34, 46, 49
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
281
Connector cover . . . . . . . . . . . . . . . . . . . . . . . . . .
275
Connector specifications . . . . . . . . . . . . . . . . . . .
257
Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
275
Content upgrade memory table . . . . . . . . . . . . . .
188
Continuous buzzer . . . . . . . . . . . . . . . . . . . . . . . .
193
Continuous screens . . . . . . . . .
123, 140, 159, 161
Continuous sound . . . . . . . . . . . . . . . . . . . . .
93, 125
Contrast control . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
Control bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
181
Controlling the NT20S status . . . . . . . . . . .
154, 191
Controlling the display elements . . . . . . . . . . . . .
153
Copy memory table . . . . . . . . . . . . . . . . . . . . . . . .
207
Copy memory table setting . . . . . . . . . . . . . . . . .
174
Copy type . . . . . . . . . . . . . . . . . . . . . . . . . . .
174, 175
Copying the memory table . . . . . . . . . . . . . . . . . .
174
Creating numeric keys . . . . . . . . . . . . . . . . . . . . .
143
Creating screen data . . . . . . . . . . . . . . . . . . . . . . .
113
Crimp terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30
Currently displayed screen word . . . . . . . .
160, 161
D
DIP-SW status . . . . . . . . . . . . . . . . . . . . . . . . . . . .
109
DIP switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24, 42
DIP switch settings . . . . . . . . . . . . . . . . . . . . . . . .
109
Data bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
Data memory (DM) . . . . . . . . . . . . . . . . . . . . . . . .
178
Data transmission in screen units . . . . . . . . . . . . .
87
Decimal fraction parts . . . . . . . . . . . . . . . . . . . . . .
146
Determining the numeral memory table number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
188
Determining touch switch status . . . . . . . . . . . . .
183
Difference between direct connection Ver. 4 and
Ver. 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Difference between the NT20S-ST12j and
NT20S-ST16j
282
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Direct conn. setting screen . . . . . . . . . . . . . . . . .
115
Direct connection . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
Direct information . . . . . . . . . . . . . . . . . . . . . . . . .
237
Direct setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
113
Direct specification . . . . . . . . . . . . . . .
163, 165, 169
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Display frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
137
Display specified screen . . . . . . . . . . . . . . . . . . . .
204
Draw circle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
221
Draw polyline . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
221
E
ERR ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
94
EXIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100
Edit screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115
8-digit number input notify . . . . . . . . . . . . . . . . . .
212
8-digit write numeral memory table . . . . . . . . . . .
206
End flashing display . . . . . . . . . . . . . . . . . . . . . . .
219
End inverse display . . . . . . . . . . . . . . . . . . . . . . . .
218
End plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
149
Enlarged display . . . . . . . . . . . . . . . . . . . . . . . . . .
119
Error message when the NT20S is started . . . . .
72
F
FA site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
File list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
114
File units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
86
Flash memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
Flashing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133, 138
Flashing display . . . . . . . . . . . . . . . . . . . . . .
120, 127
Flow control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133
4-digit number input notify . . . . . . . . . . . . . . . . . .
212
4-digit write numeral memory table . . . . . . . . . . .
206
Function restrictions depending on the support tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
255
G
Graph frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
130
Guide display . . . . . . . . . . . . . . . . . . . . . . . .
134, 138
H
Host I/F tool connector . . . . . . . . . . . . . . . . . . . . . .
23
Host communication conditions . . . . . . . . . . . . . . .
63
Host link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12, 78
Host link method . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
Host link unit . . . . . . . . . . . . . . . . . . . . . . .
35, 37, 271
I
I/O check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99
I/O connection cable . . . . . . . . . . . . . . . . . . . . . . . .
59
IP65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4, 28
Indirect specification . . . . . . . . . . . . . .
163, 165, 171
Init. Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . .
73, 74
Initialization by using the DIP switch . . . . . . . . . .
89
Initialization by using the DIP switch
(Forced initialization) . . . . . . . . . . . . . . . . . . . . . . . .
74
Initialization by using the system menu . . . . . . . .
72
Initialization error . . . . . . . . . . . . . . . . . . . . . . . . . .
237
Initialization setting . . . . . . . . . . . . . . . . . . .
164, 166
Initialize the screen data memory . . . . . . . . . . . . .
87
Initializing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
72
Initializing memory . . . . . . . . . . . . . . . . . . . . . . . . . .
72
Installation environment . . . . . . . . . . . . . . . . . . . .
251
Integer fraction parts . . . . . . . . . . . . . . . . . . . . . . .
146
Intermittent buzzer . . . . . . . . . . . . . . . . . . . . . . . .
193
Intermittent sound . . . . . . . . . . . . . . . . . . . . .
93, 125
Internal processing . . . . . . . . . . . . . . . . . . . . . . . .
252
Inverse display . . . . . . . . . . . . . . . . . . . . . . . . . . . .
138
K
Key press sound . . . . . . . . . . . . . . . . . . . . . . . . . . .
91
L
LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
251
LCD panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
94
LSS . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41, 42, 43, 47
Lamp and touch switch display
(Bit specification) . . . . . . . . . . . . . . . . . . . . . . . . . .
210
Lamp and touch switch display
(Number specification) . . . . . . . . . . . . . . . . . . . . .
210
Lamp and touch switch display status enquiry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
211
Lamp and touch switch display status response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
211
Lamp bit control . . . . . . . . . . . . . . . . . . . . . . . . . . . .
97
Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9, 15, 133
Lid for backlight replacement . . . . . . . . . . . . . . . . .
23
Lit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133, 138
M
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
Maintenance mode . . . . . . . . . . . . . . . . . . . . . . . . .
71
Making up a connecting cable . . . . . . . . . . . . . . .
256
Mark data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
237
Marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9, 119, 127
Memory error . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107
Memory size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
113
Memory switches . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
69
Momentary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
181
Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
More than one lamp can be lit in batch . . . . . . .
134
283
N
NT-AL001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
262
NT20S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
NT20S has made a buzzer sound . . . . . . . . . . . .
72
NT link . . . . . . . . . . . . . . . . . . . . . . . . . .
12, 13, 45, 78
Names of parts . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
9-pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
Normal display . . . . . . . . . . . . . . . . . . . . . . . . . . . .
218
Normal screen . . . . . . . . . . . . . . . . . . . . . . . . . . . .
122
Notes on the notification operation . . . . . . . . . . .
182
Nothing is displayed . . . . . . . . . . . . . . . . . . . . . . .
236
Notification of numbers to the PC . . . . . . . . . . . .
188
Notify bit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
181
Notifying the NT20S status . . . . . . . . . . . . . . . . .
156
Notifying the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Notifying the display elements . . . . . . . . . . . . . . .
155
Notifying the display screen . . . . . . . . . . . . . . . . .
160
Number of registration words . . . . . . . . . .
164, 166
Numeral memory table . . . . . . . . . . . . . . . .
127, 167
Numeral setting . . . . . . . . . . . . . . . . . . . . . .
123, 140
Numeral setting attribute . . . . . . . . . . . . . .
125, 143
Numeral setting strobe . . . . . . . . . . . . . . . .
188, 197
Numeric key type . . . . . . . . . . . . . . . . . . . . . . . . . .
142
Numeric keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
143
Numeric values . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
O
OMRON product references . . . . . . . . . . . . . . . . . .
v
100% value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
130
Operating status . . . . . . . . . . . . . . . . . . . . . . .
2, 197
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
Operation by operating commands . . . . . . . . . . .
202
Operation by terminal commands . . . . . . . . . . . .
202
284
Operation commands . . . . . . . . . . . . . . . . . . . . . . .
18
Operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
Operation panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
Operations with the system menu . . . . . . . . . . . .
70
Order for writing . . . . . . . . . . . . . . . . . . . . . . . . . . .
175
Overlapping screen . . . . . . . . . .
122, 140, 159, 161
P
PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32, 45, 48
PC memory map . . . . . . . . . . . . . . . . . . . . . . . . . .
278
PC switch settings . . . . . . . . . . . . . . . . . . . . . .
36, 47
PC system setting . . . . . . . . . . . . . . . .
41, 42, 43, 47
POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
105
POWER LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
236
PT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2, 271
PT operating status . . . . . . . . . . . . . . . . . . . . . . . .
196
PT setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
113
PT status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
196
PT status control area . . . . . . . . . . . . .
17, 154, 191
PT status notify area . . . . . . . . . . . . . . . . . . .
17, 156
Page number display . . . . . . . . . . . . . . . . . . . . . .
123
Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Panel fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
Parent screen . . . . . . . . . . . . . . . . . . . . . . . .
122, 123
Parity check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
% display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
130
% values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
131
Peripheral tool . . . . . . . . . . . . . . . . . . .
41, 42, 43, 47
Power input terminals . . . . . . . . . . . . . . . . . . .
23, 29
Power to the computer is interrupted . . . . . . . . . .
89
Programmable terminal . . . . . . . . . . . . . . . . . . . . . .
2
+5V output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64
Q
QQ command . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
237
R
RS-232C/422A converter unit . . . . . . . . . . . . . . .
262
RS-232C I/F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
102
RS-232C cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
RS/CS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
105
RUN LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
236
Reflection-suppressing protective sheet . . . . . .
276
Related manuals and their contents . . . . . . . . . . .
xi
Replaceable backlight . . . . . . . . . . . . . . . . . . . . . .
276
Replacing the backlight . . . . . . . . . . . . . . . . . . . . .
240
Request screen number . . . . . . . . . . . . . . . . . . . .
204
Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
89, 181
Reset switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
Reverse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
134
Reverse and flashing display . . . . . . . . . . .
120, 127
Reverse display . . . . . . . . . . . . . . . . . . . . . .
120, 127
Revision history . . . . . . . . . . . . . . . . . . . . . . . . . . .
287
Rotary switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
S
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . .
xiv
Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
118
Screen #0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
236
Screen No. 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
90
Screen attributes . . . . . . . . . . . . . . . . . . . . . . . . . .
125
Screen data . . . . . . . . . . . . . . . . . . . . . . . . . .
86, 237
Screen data displayed on the NT20S . . . . . . . . . . .
9
Screen data memory . . . . . . . . . . . . . . . . . . . . . . . .
72
Screen display . . . . . . . . . . . . . . . . . . . . . . . . . . . .
192
Screen display control . . . . . . . . . . . . . . . . . . . . .
215
Screen list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
115
Screen number . . . . . . . . . . . . . . . . . . . . . . . . . . .
118
Screen number “0” . . . . . . . . . . . . . . . . . . . . . . . .
118
Screen number response . . . . . . . . . . . . . . . . . . .
205
Screen switch setting . . . . . . . . . . . . . . . . . . . . . .
157
Screen switching . . . . . . . . . . . . . . . . . . . . . . . . . .
138
Screen switching strobe . . . . . . . . . . .
158, 160, 196
Screen switching timing . . . . . . . . . . . . . . . . . . . .
158
Selecting communication speed . . . . . . . . . . . . . .
79
Selecting the host communication method . . . . .
78
Selecting the items . . . . . . . . . . . . . . . . . . . . . . . . .
71
Selecting the numeral setting area for data input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
145
Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
181
Set cursor position . . . . . . . . . . . . . . . . . . . . . . . . .
220
Set flashing display . . . . . . . . . . . . . . . . . . . . . . . .
219
Set inverse display . . . . . . . . . . . . . . . . . . . . . . . .
218
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
107
Setting a screen number for a touch switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
138
Setting a system key function for a touch switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
139
Setting error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
237
Setting the buzzer . . . . . . . . . . . . . . . . . . . . . . . . . .
92
Setting the support tool . . . . . . . . . . . . . . . . . . . . .
112
Setting the words of the character-string memory table . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
164
Setting the words of the numeral memory table . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
166
Sign display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
130
Smoothing . . . . . . . . . . . . . . . . . . . . . . . . . . .
119, 127
Specify character enlargement . . . . . . . . . . . . . .
217
Specify displayed characters . . . . . . . . . . . . . . . .
220
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
137
Start-up screen . . . . . . . . . . . . . . . . . . . . . . . . . . .
118
285
Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
67
Statuses of touch switches are changed . . . . . .
183
Stop bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
Support tool mode . . . . . . . . . . . . . . . . . . . . .
95, 255
Support tools . . . . . . . . . . . . . . . . . . . .
3, 31, 86, 113
Switching predetermined values or character strings according to the situation . . . . . . . . . . . .
174
Switching the continuous screens . . . . . . . . . . . .
124
Switching the power ON/OFF when using
C200H direct communication . . . . . . . . . . . . . . . . .
62
Switching the screen display . . . . . . . . . . . . . . . .
157
Switching to the RUN mode . . . . . . . . . . . . . . . . . .
90
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
125
System key functions . . . . . . . . . . . . . . . . . . . . . .
139
System menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
System menu display permission . . . . . . . . . . . .
215
T
Terminal commands . . . . . . . . . . . . . . . . . . . . . . . .
18
3-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
137
Thumbwheel type . . . . . . . . . . . . . . . . . . . . . . . . .
142
Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
198
To stop the buzzer sound . . . . . . . . . . . . . . .
92, 104
Tool I/F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
101
Tool settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
113
Touch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
71
Touch switch number output
(from NT20S to host) . . . . . . . . . . . . . . . . . . . . . .
213
Touch switch # method . . . . . . . . . . . . . . . . . . . . .
208
Touch switch bit output
(from NT20S to host) . . . . . . . . . . . . . . . . . . . . . .
213
Touch switch disable . . . . . . . . . . . . . . . . . . . . . . .
214
Touch switch enable . . . . . . . . . . . . . . . . . . . . . . .
214
Touch switches . . . . . . . . . . . . . . . . . . .
9, 16, 70, 136
286
Touch switches used to call the system menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
70
Transmission in file units . . . . . . . . . . . . . . . . . . . .
86
Transmit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
Transmit mode . . . . . . . . . . . . . . . . . . . . .
71, 88, 117
Transmitting screen data . . . . . . . . . . . . . . .
87, 117
Transportation and storage . . . . . . . . . . . . . . . . .
251
Turn ON the power . . . . . . . . . . . . . . . . . . . . . . . . .
67
Types of notification operation . . . . . . . . . . . . . . .
181
25-pin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
34
U
Unit number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25
Unlit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133
Upgrading bar graphs . . . . . . . . . . . . . . . . . . . . . .
177
Upper/lower limit check . . . . . . . . . . . . . . . . . . . .
141
Used for the first time . . . . . . . . . . . . . . . . . . . . . . .
72
User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
125
Using numeric keys . . . . . . . . . . . . . . . . . . . . . . . .
145
Using the thumbwheel type . . . . . . . . . . . . . . . . .
147
Using touch switches for notification to the
PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
181
W
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xv
Waterproof requirements . . . . . . . . . . . . . . . . . . . . .
4
Wide angle of visibility . . . . . . . . . . . . . . . . . .
4, 251
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
257, 264
Write character-string memory table . . . . . . . . .
205
X
XON/XOFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
Z
Zero suppress . . . . . . . . . . . . . . . . . . . . . . . . . . . .
128
Revision History
NT-20S
Programmable Terminal
Operation Manual
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. V020-E3-2
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code Date
V020-E1-1
V020-E1-2
V020-E1-3
September 1994
June 1995
May 1997
V020-E1-4
V020-E3-2
August 1997
May 1998
Revised content
Original production
Overall revision by addition of a new model
Overall revision by addition of a new model
S Revisions due to addition of NT link (1:N)
S Revisions due to addition of new model (NT20S-ST16j)m addition of an applicable PC (CDM1), addition of explanations, and correction of errors.
Correction of errors
Revisions made to version V020-E1-4.
Section 1-3, NT Link (1:N) Systems, replaced graphic.
Changed Heading in Section 3-5.
289
OMRON ELECTRONICS LLC
1
Commerce Drive
Schaumburg, IL
60173
847.843.7900
For US technical support or other inquiries: 800.556.6766
OMRON CANADA, INC.
885
Milner Avenue
Toronto, Ontario M
1
B
5
V
8
416.286.6465
OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.omron.com/oei
Canada - http://www.omron.ca
V020-E3-2 2/99 ©1999 OMRON ELECTRONICS LLC Specifications subject to change without notice.
Printed in the U.S.A.
Download
Advertisement
Key features
Downsized Body
Easy-to-read screen even in direct sunlight
Host Link I/F Unit, Screen Data Memory, and System ROM are All Incorporated
Compatibility with NT20M
Touch Switch Operation
Wide angle of visibility
Conforms to IP65 waterproof requirements
Backlight unit can be replaced at the operation site
1:1 and 1:N connections are possible
Flash memory is used for the screen data memory
Frequently asked questions
The NT20S displays information about the system and equipment operating status in real time, including production control data, production line status monitoring data, and alarm messages.
NT20S-ST121-EV3 uses the Host link and NT link for communications, while NT20S-ST122-V1 uses C200H direct communication.
You can create and transfer the screen data with the support tool to the NT20S using an RS-232C cable. Then, you can connect the NT20S to the Host using either the host link, NT link, RS-232C, or C200H direct communication method.
The NT20S supports the following communication methods: Host link, NT link (1:1 and 1:N), C200H direct communication, and RS-232C interface.
The NT20S is compatible with existing NT20M screen data and user programs. It also supports the system key functions that were available on NT20M.
The NT20S has touch switches that can be set anywhere on the screen. Touching a touch switch can switch the display (display switch function) or notify the Host (notification function). The touch switches can also be lit or made flash by controlling from the Host in the same way as the lamps.