Schneider Electric ATV61/ATV71 Integrated Modbus User`s manual
Reklama
Reklama
Altivar 71
Integrated Modbus
User's manual
11/2010
www.schneider-electric.com
Contents
While every precaution has been taken in the preparation of this document, Schneider
Electric SA assumes no liability for any omissions or errors it may contain, nor for any damages resulting from the application or use of the information herein.
The products and options described in this document may be changed or modified at any time, either from a technical point of view or in the way they are operated. Their description can in no way be considered contractual.
1755863 11/2010 3
4
Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARDOUS VOLTAGE
• Read and understand this manual before installing or operating the Altivar 71 drive. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical standards in force concerning protective grounding of all equipment.
• Many parts in this variable speed drive, including printed wiring boards, operate at line voltage. DO NOT TOUCH.
Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• DO NOT short across terminals PA and PC or across the DC bus capacitors.
• Install and close all covers before applying power or starting and stopping the drive.
• Before servicing the variable speed drive:
- Disconnect all power
- Place a "DO NOT TURN ON" label on the variable speed drive disconnect
- Lock the disconnect in the open position
• Disconnect all power including external control power that may be present before servicing the drive. WAIT 15
MINUTES for the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure given in the Installation Manual to verify that the DC voltage is less than 45 Vdc. The drive LEDs are not accurate indicators of the absence of DC bus voltage.
Electric shock will result in death or serious injury
CAUTION
DAMAGED EQUIPMENT
Do not operate or install any drive that appears damaged.
Failure to follow this instruction can result in equipment damage.
1755863 11/2010
Documentation structure
Installation manual
This manual describes:
• How to assemble the drive
• How to connect the drive
Programming manual
This manual describes:
• The functions
• The parameters
• How to use the drive display terminal (integrated display terminal and graphic display terminal)
Communication parameters manual
This manual describes:
• The drive parameters with specific information (addresses, formats, etc.) for use via a bus or communication network
• The operating modes specific to communication (status chart)
• The interaction between communication and local control
Modbus
®
, CANopen
®
, Ethernet™, Profibus
®
, INTERBUS, Uni-Telway, FIPIO, DeviceNet™, Modbus
®
Plus manuals ...
These manuals describe:
• Connection to the bus or network
• Configuration of the communication-specific parameters via the integrated display terminal or the graphic display terminal
• Diagnostics
• Software setup
• The communication services specific to the protocol
Altivar 58/58F migration manual
This manual describes the differences between the Altivar 71 and the Altivar 58/58F.
It explains how to replace an Altivar 58 or 58F, including how to replace drives communicating on a bus or network.
1755863 11/2010 5
6
Introduction
Presentation
Two integrated communication ports mean that the Modbus protocol can be accessed directly:
• One RJ45 Modbus HMI connector port, located on the drive front panel, which is used to connect:
- The graphic display terminal
- A Magelis industrial HMI terminal
- The PC-Software workshop
• One RJ45 Modbus network port, located on the drive control terminals, which is dedicated to control and signaling by a PLC or other type of controller. It also supports the connection of a terminal or the PC software workshop when the terminal port is not available.
The two Modbus ports on the Altivar 71 can be used for the following functions:
• Configuration
• Adjustment
• Control
• Monitoring
The Altivar 71 supports:
• The 2-wire RS485 physical layer
• The RTU transmission mode
This manual describes how to set up the Altivar 71 drive on Modbus and also describes the Modbus services that are available on this drive.
Notation
Drive terminal displays
The graphic display terminal menus are shown in square brackets.
Example:
[1.9 COMMUNICATION]
.
The integrated 7-segment display terminal menus are shown in round brackets.
Example: (
COM-)
.
Parameter names are displayed on the graphic display terminal in square brackets.
Example:
[Fallback speed]
Parameter codes are displayed on the integrated 7-segment display terminal in round brackets.
Example: (
LFF)
.
Formats
In this manual, hexadecimal values are written as follows: 16#.
1755863 11/2010
Bus connection
Connecting to the Altivar 71
Connection accessories should be ordered separately (please consult our catalogs).
Connect the RJ45 cable connector to either of the RJ45 connectors on the Altivar 71:
Modbus
HMI
Modbus network
RJ45 connector pinouts
View from underneath
8........................1
Modbus network
Pin Signal
1 CAN_H (1)
4
5
2
3
CAN_L (1)
CAN_GND (1)
D1
D0
6
7
8
Not connected
VP (2)
Common
Modbus HMI
Pin Signal
1
6
7
4
5
2
3
8
Not connected
Not connected
Not connected
D1
D0
Not connected
VP (2)
Common
(1) CANopen
®
signal.
(2) Power supply ( c
10 V 20 mA) for an RS232/RS485 converter (to PC-Software) or for the graphic display terminal.
Note: Avoid using pins marked “Not connected”.
1755863 11/2010 7
8
Bus connection
Wiring recommendations
• Use the Schneider-Electric cable with 2 pairs of shielded twisted conductors (catalog number: TSXCSA100, TSXCSA200 or
TSXCSA500).
• Keep the Modbus cable away from the power cables (30 cm minimum).
• If it is necessary for the Modbus cable and the power cables to cross each other, be sure they cross at right angles.
• Whenever possible, connect the cable shielding to the protective ground, e.g., to the ground of each device if this ground is connected to the protective ground.
• Install a line terminator at both ends of the line.
• Ensure the correct polarization of the line.
• Connect the common polarity (“Common” signal) to the protective ground at one or more points on the bus.
For more information, please refer to the TSX DG KBL E guide: "Electromagnetic compatibility of industrial networks and fieldbuses".
RS485 standard
The RS485 standard allows variants of different characteristics:
• Polarization
• Line terminator
• Distribution of a reference potential
• Number of slaves
• Length of bus
The new Modbus specification published on www.modbus.org in 2002 contains precise details of all these characteristics. They are also summarized in the next paragraph (standard schematic). The new Schneider-Electric devices conform to this specification.
Some devices comply with earlier specifications. The two most widespread are described in the appendices:
• "Uni-Telway schematic" page
• "Jbus schematic" page
Requirements enabling different types of protocol to coexist are given in the appendix:
• "Mixed schematic" page
1755863 11/2010
Bus connection
Modbus standard schematic
The standard schematic corresponds to the Modbus specification published in 2002 on www.modbus.org (Modbus_over_serial_line_V1.pdf,
Nov 2002) and in particular to the schematic of the 2-wire multidrop serial bus.
The ATV71 drive conforms to this specification.
Schematic diagram:
Master
R
650
Ω
0 V
T
5 V
650
Ω
D1
120
Ω
1n F
120
Ω
1n F
D0
Common
Type of trunk cable
Maximum length of bus
Maximum number of stations (without repeater)
Maximum length of tap links
Bus polarization
Line terminator
Common polarity
R
T
Slave 1
R
T
Slave n
Shielded cable with 1 twisted pair and at least a 3 rd
conductor
1000 m at 19200 bps with the Schneider-Electric TSX CSA p
cable
32 stations, i.e., 31 slaves
• 20 m for one tap link
• 40 m divided by the number of tap links on a multiple junction box
• One 450 to 650
Ω
pulldown resistor at 5 V (650
Ω
or thereabouts recommended)
• One 450 to 650
Ω pulldown resistor at Common
(650
Ω
or thereabouts recommended)
This polarization is recommended for the master.
One 120
Ω
0.25 W resistor in series with a 1nF 10 V capacitor
Yes (Common), connected to the protective ground at one or more points on the bus
1755863 11/2010 9
Bus connection
Connection via RJ45 wiring system
1. Master (PLC, PC or communication module)
2. Modbus cable depending on the type of master (see table)
1
2 3 4 6 4 6 5
3. Modbus splitter block LU9 GC3
4. Modbus drop cables VW3 A8 306 Rpp
4
5
4 4
5. Line terminators VW3 A8 306 RC
6. Modbus T-junction boxes VW3 A8 306 TFpp (with cable)
7
7. Modbus cable (to another splitter block) TSX CSAp00
ATV 71
Connection accessories
Description
Modbus splitter block
Modbus T-junction boxes
Line terminators
For RJ45 connector
Code
10 RJ45 connectors and 1 screw terminal block 3
With integrated cable (0.3 m) 6
With integrated cable (1 m) 6
R = 120
Ω, C = 1 nF
5
R = 150
Ω (specific to "Jbus schematic" page
5
Connecting cables
Description
Cables for
Modbus bus
RS 485 double shielded twisted pair cables
Length (m)
3
0.3
1
3
100
200
500
Connectors
1 RJ45 connector and 1 stripped end
2 RJ45 connectors
2 RJ45 connectors
2 RJ45 connectors
Supplied without connector
Supplied without connector
Supplied without connector
Catalog number
LU9 GC3
VW3 A8 306 TF03
VW3 A8 306 TF10
VW3 A8 306 RC
VW3 A8 306 R
Code
4
7
7
4
4
7
Catalog number
VW3 A8 306 D30
VW3 A8 306 R03
VW3 A8 306 R10
VW3 A8 306 R30
TSX CSA 100
TSX CSA 200
TSX CSA 500
10 1755863 11/2010
Bus connection
Type of master
Twido PLC
TSX Micro PLC
Master interface
Adaptor or mini-DIN
RS485 interface module
Adaptor or screw terminal RS485 interface module
Mini-DIN RS485 connector port
Modbus connection accessories for RJ45 wiring system
Description Catalog number
TWD XCA RJ030 3 m cable equipped with a mini-DIN connector and an RJ45 connector
3 m cable equipped with an RJ45 connector and stripped at the other end
VW3 A8 306 D30
3 m cable equipped with a mini-DIN connector and an RJ45 connector
TWD XCA RJ030
TSX Premium PLC
PCMCIA card (TSX
SCP114)
TSX SCY 11601 or TSX
SCY 21601 module
(SUB-D 25 socket)
Stripped cable
Cable equipped with a SUB-D 25 connector and stripped at the other end (for connection to the screw terminals of the
LU9GC3 splitter block)
PCMCIA card
(TSX SCP114)
Stripped cable
TSX SCP CM 4030
TSX SCY CM 6030
TSX SCP CM 4030
Screw terminal RS485 3 m cable equipped with an RJ45 connector and stripped at the other end
RJ45 RS485 1 m cable equipped with 2 RJ45 connectors
VW3 A8 306 D30
VW3 P07 306 R10
Ethernet bridge
(174 CEV 300 10)
Profibus DP gateway
(LA9P307)
Fipio (LUFP1) or
Profibus DP (LUFP7) or
DeviceNet (LUFP9) gateway
Serial port PC
RJ45 RS485
Male SUB-D 9
RS232 serial port PC
0.3 m cable equipped with 2 RJ45 connectors or
1 m cable equipped with 2 RJ45 connectors or
3 m cable equipped with 2 RJ45 connectors
RS232/RS485 converter and 3 m cable equipped with an
RJ45 connector and stripped at the other end (for connection to the screw terminals of the LU9GC3 splitter block)
VW3 A8 306 R03 or
VW3 A8 306 R10 or
VW3 A8 306 R30
TSX SCA 72 and
VW3 A8 306 D30
1755863 11/2010 11
Bus connection
Connection via junction boxes
1
2 5
6
3 4
1. Master (PLC, PC or communication module)
2. Modbus cable depending on the type of master
3. Modbus cable TSX CSAp00
4. Junction box TSX SCA 50
7
5. Subscriber sockets TSX SCA 62
6. Modbus drop cables VW3 A8 306
7. Modbus drop cable VW3 A8 306 D30
ATV 71
Connection accessories
Description
Tap junction
3 screw terminals and an RC line terminator, to be connected using cable VW3 A8 306 D30
Subscriber socket
2 female 15-way SUB-D connectors, 2 screw terminals, and an RC line terminator, to be connected using cable VW3 A8 306 or VW3 A8 306 D30
Code
4
5
Catalog number
TSX SCA 50
TSX SCA 62
Connecting cables
Description Length (m)
Cables for Modbus bus
3
3
RS 485 double shielded twisted pair cables
100
200
500
Connectors
1 RJ45 connector and one stripped end
1 RJ45 connector and 1 male 15-way SUB-D connector for
TSX SCA 62
Supplied without connector
Supplied without connector
Supplied without connector
Code
7
6
3
3
3
Catalog number
VW3 A8 306 D30
VW3 A8 306
TSX CSA 100
TSX CSA 200
TSX CSA 500
12 1755863 11/2010
Bus connection
Type of master
Twido PLC
TSX Micro PLC
TSX Premium PLC
Ethernet bridge
(174 CEV 300 10)
Profibus DP gateway
(LA9P307)
Fipio (LUFP1) or
Profibus DP (LUFP7) or
DeviceNet (LUFP9) gateway
Serial port PC
Master interface
Adaptor or screw terminal
RS485 interface module
Mini-DIN RS485 connector port
PCMCIA card
(TSX SCP114)
TSX SCY 11601 or TSX SCY
21601 module
(SUB-D 25 socket)
PCMCIA card
(TSX SCP114)
Screw terminal RS485
RJ45 RS485
RJ45 RS485
Male SUB-D 9
RS232 serial port PC
Modbus connection accessories for junction boxes using screw terminals
Description
Modbus cable
Catalog number
TSX CSA100 or
TSX CSA200 or
TSX CSA500
Tap junction TSX P ACC 01
Cable equipped with a special connector and stripped at the other end
Cable equipped with a SUB-D 25 connector and stripped at the other end
Cable equipped with a special connector and stripped at the other end
Modbus cable
3 m cable equipped with an RJ45 connector and stripped at the other end
3 m cable equipped with an RJ45 connector and stripped at the other end
RS232/RS485 converter and
Modbus cable
TSX SCP CU 4030
TSX SCY CM 6030
TSX SCP CU 4030
TSX CSA100 or
TSX CSA200 or
TSX CSA500
VW3 A8 306 D30
VW3 A8 306 D30
TSX SCA 72 and
TSX CSA100 or
TSX CSA200 or
TSX CSA500
Type of master
Twido PLC
TSX Micro PLC
TSX Premium PLC
Master interface
Adaptor or screw terminal RS485 interface module
Mini-DIN RS485 connector port -
-
Modbus connection accessories for junction boxes using
SUB-D 15
Description
-
-
Catalog number
PCMCIA card (TSX SCP114)
TSX SCY 11601 or TSX SCY
21601 module (SUB-D 25 socket)
PCMCIA card (TSX SCP114)
Cable equipped with a special connector and a
SUB-D 25 connector
Cable equipped with a SUB-D 25 connector and stripped at the other end
TSX SCY CU
4530
TSX SCP CU
4530
Screw terminal RS485 -
Cable equipped with a special connector and stripped at the other end
-
TSX SCY CU
4530
Ethernet bridge
(174 CEV 300 10)
Profibus DP gateway
(LA9P307)
Fipio gateway (LUFP1) or
Profibus DP gateway (LUFP7)
Serial port PC
RJ45 RS485
RJ45 RS485
Male SUB-D 9 RS232 serial port
PC
-
-
3 m cable equipped with an RJ45 connector and a SUB-D 25 connector
-
-
VW3 A8 306
1755863 11/2010 13
Bus connection
Connection onto screw terminals
Connection accessories
Description
Line terminators
For screw terminals
Connecting cables
Description
Cables for
Modbus bus
RS 485 double shielded twisted pair cables
Length (m)
3
100
200
500
R = 120
Ω, C = 1 nF
R = 150
Ω
(specific to "Jbus schematic" page 42
)
Catalog number
VW3 A8 306 DRC
VW3 A8 306 DR
Connectors
1 RJ45 connector and one stripped end
Supplied without connector
Supplied without connector
Supplied without connector
Catalog number
VW3 A8 306 D30
TSX CSA 100
TSX CSA 200
TSX CSA 500
14 1755863 11/2010
Configuration
Configuring communication parameters
Modbus network
The configuration of the Modbus network parameters can be accessed via the
[1.9 - COMMUNICATION]
(
CON-) menu
(
[MODBUS NETWORK]
(
Nd1-) submenu).
Modbus parameter
[Modbus Address]
(
Add)
[Modbus add CI card]
(
AMOA)
[Mdbs add com card]
(
AMOC)
[Modbus baud rate]
( tbr)
[Modbus format]
( tFO)
Description/Possible values
1 to 247
Drive Modbus server disabled
1 to 247
“Controller inside” card Modbus server disabled
1 to 247
(Ethernet) communication card Modbus server disabled
4800 bps
9600 bps
19200 bps (1)
38400 bps
8 data bits, odd parity, 1 stop bit
8 data bits, even parity, 1 stop bit (1)
8 data bits, no parity, 1 stop bit
8 data bits, no parity, 2 stop bits
display
Terminal
[1]
(
1)
to
[247]
(
247)
[Off]
(
OFF)
[1]
(
1)
to
[247]
(
247)
[Off]
(
OFF)
[1]
(
1)
to
[247]
(
247)
[Off]
(
OFF)
[4.8 Kbps]
(
4 8)
[9.6 Kbps]
(
9 6)
[19.2 Kbps]
(
19 2)
[38.4 Kbps]
(
38 4)
[8-O-1]
(
8O1)
[8 E 1]
(
8E1)
[8-N-1]
(
8n1)
[8-N-2]
(
8n2)
value
Default
[Off]
(
OFF)
[Off]
(
OFF)
[Off]
(
OFF)
[19.2 Kbps]
(
19 2)
[8 E 1]
(
8E1)
The addresses are applicable to both Modbus network and Modbus HMI. These 3 addresses can be freely chosen and must all be different.
To access the drive parameters, which are described in the parameters manual, just use the address
[Modbus Address]
(
Add)
. The addresses
[Modbus add CI card]
(
AMOA)
and
[Mdbs add com card]
(
AMOC)
are used solely for accessing the “Controller
Inside” (catalog number: VW3 A3 510) and Ethernet (catalog number: VW3 A3 310) option card parameters.
Modbus HMI
The configuration of the Modbus HMI parameters can be accessed via the
[1.9 - COMMUNICATION]
(
CON-)
menu (
[MODBUS
HMI]
(
Nd2-).
submenu).
Note: The drive address on Modbus HMI is identical to that on Modbus network. If Modbus network is disabled (value 0 or display “OFF”), the Modbus HMI connection remains active for the graphic display terminal and for PC-Software.
Parameter Possible values
[HMI baud rate]
( tbr2)
[HMI format]
( tFO2)
9600 bps
19200 bps (1)
8 data bits, even parity, 1 stop bit (1)
(1) The graphic display terminal will only work with these values.
Any other value will make communication with the graphic display terminal impossible.
Terminal display
[9.6 Kbps]
(
9 6)
[19.2 Kbps]
(
19 2)
[8 E 1]
(
8E1)
Default value
[19.2 Kbps]
(
19 2)
[8 E 1]
(
8E1)
1755863 11/2010 15
Configuration
Control-signal configuration
Numerous control-signal configurations are possible. For more information, refer to the programming manual and the parameters manual.
The following configurations are just some of the possibilities available.
Control via Modbus in I/O profile
The command and target come from Modbus.
The command is in I/O profile.
Configure the following parameters:
Parameter
Profile
Target 1 configuration
Command 1 configuration
Value Comment
I/O profile The run command is simply obtained by bit 0 of the command word.
Modbus The target comes from Modbus.
Modbus The command comes from Modbus.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
[1.6 - COMMAND]
(
CtL-)
Parameter
[Profile]
(
CHCF)
[Ref.1 chan]
(
Fr1)
[Cmd channel 1]
(
Cd1)
Value
[I/O profile]
(
IO)
[Modbus]
(
Mdb)
[Modbus]
(
Mdb)
Control via Modbus or the terminals in I/O profile
Both the command and target come from Modbus or the terminals. Input LI5 at the terminals is used to switch between Modbus and the terminals.
The command is in I/O profile.
Configure the following parameters:
Parameter Value
Profile
Target 1 configuration
Target 1B configuration
I/O profile
Modbus
Analog input 1 on the terminals
Target switching Input LI5
Command 1 configuration Modbus
Command 2 configuration Terminals
Command switching Input LI5
Comment
The run command is simply obtained by bit 0 of the command word.
Target 1 comes from Modbus.
Target 1B comes from input AI1 on the terminals.
Input LI5 switches the target (1
↔
1B).
Command 1 comes from Modbus.
Command 2 comes from the terminals.
Input LI5 switches the command.
Target 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
16 1755863 11/2010
Configuration
Configure the following parameters:
Menu
[1.6 - COMMAND]
(
CtL-)
[1.7 - APPLICATION FUNCT.]
(
FUn)
[REFERENCE SWITCH.]
Parameter
[Profile]
(
CHCF)
[Ref.1 chan]
(
Fr1)
[Cmd channel 1]
(
Cd1)
[Cmd channel 2]
(
Cd2)
[Command switching]
(
CCS)
[Ref.1B chan]
(
Fr1B)
[Ref 1B switching]
( rCb)
Control via Modbus in Drivecom profile
The command and target come from Modbus.
The command is in Drivecom profile.
Configure the following parameters:
Parameter
Profile
Target 1 configuration
Value
Combined Drivecom profile
Modbus
Value
[I/O profile]
(
IO)
[Modbus]
(
Mdb)
[Modbus]
(
Mdb)
[Terminals]
( tEr)
[LI5]
(
LI5)
[AI1 ref.]
(
AI1)
[LI5]
(
LI5)
Comment
The run commands are in Drivecom profile, the command and the target come from the same channel.
The command comes from Modbus.
Configuration via the graphic display terminal or the integrated display terminal
Menu
[1.6 - COMMAND]
(
CtL-)
Parameter
[Profile]
(
CHCF)
[Ref.1 chan]
(
Fr1)
Value
[Combined]
(
SIM)
(factory setting)
[Modbus]
(
Mdb)
Control via Modbus or the terminals in Drivecom profile
Both the command and target come from Modbus or the terminals. Input LI5 at the terminals is used to switch between Modbus and the terminals. The command is in Drivecom profile.
Configure the following parameters:
Parameter
Profile
Target 1 configuration
Target 2 configuration
Target switching
Value
Combined Drivecom profile
Modbus
Analog input 1 on the terminals
Input LI5
Comment
The run commands are in Drivecom profile, the command and the target come from the same channel.
Target 1 comes from Modbus.
Target 2 comes from input AI1 on the terminals.
Input LI5 switches the target (1
↔
2) and the command.
Note: Target 2 is directly connected to the drive’s reference limit. In the event of switching, the functions that have an effect on the target
(summing, PID, etc.) are disabled.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
[1.6 - COMMAND]
(
CtL-)
Parameter
[Profile]
(
CHCF)
[Ref.1 chan]
(
Fr1)
[Ref.2 chan]
(
Fr2)
[Ref. 2 switching]
( rFC)
Value
[Combined]
(
SIM)
[Modbus]
(
Mdb)
[AI1 ref.]
(
AI1)
[LI5]
(
LI5)
1755863 11/2010 17
Configuration
Control in Drivecom profile via Modbus and target switching at the terminals
The command comes from Modbus.
The command comes either from Modbus or from the terminals. Input LI5 at the terminals is used to switch the target between Modbus and the terminals.
The command is in Drivecom profile.
Configure the following parameters:
Parameter
Profile
Target 1 configuration
Target 1B configuration
Target switching
Command 1 configuration
Command switching
Value
Separate Drivecom profile
Comment
The run commands are in Drivecom profile, the command and the target can come from different channels.
Modbus Target 1 comes from Modbus.
Analog input 1 on the terminals Target 1B comes from input AI1 on the terminals.
Input LI5 Input LI5 switches the target (1
↔
1B).
Modbus Command 1 comes from Modbus.
Channel 1 Channel 1 is the command channel.
Target 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.
Configuration via the graphic display terminal or the integrated display terminal:
Menu
[1.6 - COMMAND]
(
CtL-)
[1.7 - APPLICATION FUNCT.]
(
FUn)
[REFERENCE SWITCH.]
Parameter
[Profile]
(
CHCF)
[Ref.1 chan]
(
Fr1)
[Cmd channel 1]
(
Cd1)
[Command switching]
(
CCS)
[Ref.1B channel]
(
Fr1b)
[Ref 1B switching]
( rCb)
Value
[Separate]
(
SEP)
[Modbus]
(
Mdb)
[Modbus]
(
Mdb)
[ch1 active]
( cd1)
[AI1 ref.]
(
AI1)
[LI5]
(
LI5)
18 1755863 11/2010
Configuration
Configuring the communication scanner
Advantages of the communication scanner
The communication scanner enables all the application-relevant parameters to be grouped in 2 consecutive word tables so that single read and write operations may be performed. Even combined single operations are possible using the 23 = 16#17 Read/Write Multiple Registers function.
The 8 periodic output variables are assigned by means of parameters NCA1 to NCA8. They are configured using the graphic display terminal or integrated display terminal via the
[1.9 - COMMUNICATION]
(
COM-)
menu and
[COM. SCANNER OUTPUT]
(
OCS-)
submenu. An NCAp parameter with a value of zero does not designate any parameter in the drive. These 8 words are described in the table below:
Parameter name Default assignment
[Scan.Out1 address]
( nCA1)
Command word (CMD)
[Scan.Out2 address]
( nCA2)
Speed target (LFRD)
[Scan.Out3 address]
( nCA3)
Not used
[Scan.Out4 address]
( nCA4)
Not used
[Scan.Out5 address]
( nCA5)
Not used
[Scan.Out6 address]
( nCA6)
Not used
[Scan.Out7 address]
( nCA7)
Not used
[Scan.Out8 address]
( nCA8)
Not used
The 8 periodic input variables are assigned by means of parameters NMA1 to NMA8.
They are configured using the graphic display terminal or integrated display terminal via the [1.9 - COMMUNICATION] (CON-) menu and [COM. SCANNER INPUT] (ICS-) submenu. An NCA parameter with a value of zero does not designate any parameter in the drive. These 8 words are described in the table below:
Parameter name
[Scan. In1 address]
( nMA1)
[Scan. In2 address]
( nMA2)
[Scan. In3 address]
( nMA3)
[Scan. In4 address]
( nMA4)
[Scan. In5 address]
( nMA5)
[Scan. In6 address]
( nMA6)
[Scan. In7 address]
( nMA7)
[Scan. In8 address]
( nMA8)
Default assignment
Status word (ETA)
Output speed (RFRD)
Not used
Not used
Not used
Not used
Not used
Not used
Example of communication scanner configuration via the graphic display terminal:
RDY MDB +00.00Hz
COM. SCANNER INPUT
0A RDY MDB +00.00Hz
0A
COM. SCANNER OUTPUT
Scan. In1 address
Scan. In2 address
Scan. In3 address
Scan. In4 address
Scan. In5 address
Code
Scan. In6 address
Scan. In7 address
Scan. In8 address
: 3201
: 8604
: 0
: 0
: 0
Quick
: 0
: 0
: 0
Scan.Out1 address
Scan.Out2 address
Scan.Out3 address
Scan.Out4 address
Scan.Out5 address
Code
Scan.Out6 address
Scan.Out7 address
Scan.Out8 address
: 8501
: 8502
: 0
: 0
: 0
Quick
: 0
: 0
: 0
Note : All modifications to parameters NMA1 ... NMA8 or NCA1 ... NCA8 must be made with the motor stopped.
The master PLC program should be updated to take account of this modification.
1755863 11/2010 19
Configuration
Configuring monitored parameters
Up to 4 parameters can be selected and their value displayed in the
[1.2 - MONITORING]
menu on the graphic display terminal.
The selection is made via the
[6 – MONITOR CONFIG.]
menu (
[6.3 - CONFIG. COMM. MAP]
submenu).
Each of the parameters [Address 1 select] … [Address 4 select] can be used to select the logic address of the parameter. An address at zero is used to disable the function.
In the example given here, the monitored words are:
• Parameter 1 = Motor current (LCR): Logic address 3204; signed decimal format
• Parameter 2 = Motor torque (OTR): Logic address 3205; signed decimal format
• Parameter 3 = Last fault (LFT): Logic address 7121; hexadecimal format
• Disabled parameter: Address W0; default format: Hexadecimal format
RDY MDB +0.00Hz
0A
6.3
CONFIG. COMM. MAP
Address 1 select
Format address 1
Address 2 select
: 3204
: Signed
: 3205
Format address 2
Address 3 select
Code
Format address 3
Address 4 select
Format address 3
: Signed
: 7121
Quick
: Hex
: 0
: Hex
One of the three display formats below can be assigned to each monitored word:
Format
Hexadecimal
Signed decimal
Unsigned decimal
Range
0000 ... FFFF
-32 767 ... 32 767
0 ... 65 535
Terminal display
[Hex]
[Signed]
[Unsigned]
Note: If a monitored parameter:
- has been assigned to an unknown address (e.g., 3200)
- has been assigned to a protected parameter
- has not been assigned the value displayed on the
[COMMUNICATION MAP]
screen will be "-----" (see "Diagnostics" section).
20 1755863 11/2010
Configuration
Configuring communication fault management
If the drive does not receive any Modbus request sent to its address for a predefined period of time (time out), a Modbus fault is triggered.
The “time out” can be set to between 0.1 and 30 s using the graphic display terminal or integrated display terminal via the
[Modbus time out]
( ttO)
parameter in the
[1.9 COMMUNICATION]
(
COM-)
menu (
[MODBUS NETWORK]
(
Md1-)
submenu). The default value is 10 s.
The response of the drive in the event of a Modbus communication fault can also be configured.
RDY MDB +0.00Hz
0A
COM. FAULT MANAGEMENT
Configuration can be performed using the graphic display terminal or integrated display terminal via the parameter in the
[Modbus fault mgt]
(
SLL)
[1.8 – FAULT MANAGEMENT]
(
FLt-)
menu
(
[COM. FAULT MANAGEMENT]
(
CLL-)
submenu).
Network fault mgt
CANopen fault mgt
Modbus fault mgt
: Freewheel
: Freewheel
: Freewheel
Code
The values of the
[Modbus fault mgt]
(SLL) parameter, which trigger a drive fault
[Modbus com.]
(SLF1) , are:
Value
[Freewheel]
(YES)
[Ramp stop]
(rMP)
[Fast stop]
(FSt)
[DC injection]
(dCI)
Meaning
Freewheel stop (factory setting).
Stop on ramp.
Fast stop.
DC injection stop.
Quick
The values of the
[Modbus fault mgt]
(SLL) parameter, which do not trigger a drive fault, are:
Value Meaning
[Ignore]
(nO) Fault
[Per STT]
(Stt) Stop according to configuration of
[Type of stop]
(Stt) .
[fallback spd]
(LFF)
Change to fallback speed, maintained as long as the fault persists and the run command has not been removed.
[Spd maint.]
(rLS)
The drive maintains the speed at the time the fault occurred, as long as the fault persists and the run command has not been removed.
The fallback speed can be configured in the
[1.8 – FAULT MANAGEMENT]
(FLt-) menu using the
[Fallback speed]
(LFF) parameter.
1755863 11/2010 21
Diagnostics
LEDs
The HMI and MOD LEDs are located on the left-hand side of the 4-digit 7-segment display on the front of the Altivar 71.
They indicate the status of Modbus communications.
HMI: Activity on Modbus HMI serial link
MOD: Activity on Modbus network serial link
Each LED lights up for 200 ms when a frame is being transmitted on the corresponding Modbus network, whether or not this is destined for the drive.
Note: Altivar 71 drives with high power ratings (>15 kW) do not feature an integrated display terminal. The HMI and MOD statuses are fed back to the graphic display terminal.
22 1755863 11/2010
Diagnostics
Communication diagnostics
RUN MDB +50.00Hz
80A
COMMUNICATION MAP
Cmd Channel : Modbus
Cmd value
Active ref. channel
: 000F
Hex
: Modbus
Frequency ref
Status word
Code
W3204
: 500.0
: 827
Quick
: 53
Hz
Hex
W3205
W7132
: 725
: 0000
Hex
W0 : -------
COM. SCANNER INPUT MAP
COM SCANNER OUTPUT MAP
CMD. WORD IMAGE
FREQ. REF. WORD MAP
MODBUS NETWORK DIAG
MODBUS HMI DIAG
CANopen MAP
PROG. CARD SCANNER
On the terminal, in the
[1.2 - MONITORING]
(
SUP-)
menu (
[COMMUNICATION MAP.]
(
CMM)
submenu):
• The
[MODBUS NETWORK DIAG]
submenu can be used to display the status of Modbus network communications.
• The
[MODBUS HMI DIAG]
submenu can be used to display the status of Modbus HMI communications.
RUN MDB +50.00Hz
80A RUN MDB +50.00Hz
80A
MODBUS NETWORK DIAG MODBUS HMI DIAG
COM LED
Mb1 process frames
Mb1 CRC errors
:
: 568
: 0
Scan.Out1 address :
Mb2 process frames : 10753
Mb2 CRC errors : 0
Code Quick Code Quick
LED display
• MOD LEDs: Modbus network activity
• HMI LED: Modbus HMI activity
The symbol signifies a non-illuminated LED (no Modbus frames).
The symbol signifies an illuminated LED (Modbus frame detected).
The LED remains illuminated for 200 ms whenever the drive detects transmission of a Modbus frame, even if the drive itself is not the intended recipient.
These LEDS are equivalent to the LEDs on the 7-segment integrated terminal (where supplied together with the drive).
The graphic display terminal is connected to Modbus HMI; the symbol assigned to the
[COM LED]
field in the
[MODBUS HMI DIAG]
submenu is always .
1755863 11/2010 23
Diagnostics
Modbus counters
•
[Mb1 process frames]
and
[Mb2 process frames]
indicate the number of Modbus frames received. The counter counts both correct and incorrect frames.
•
[Mb1 CRC errors]
and
[Mb2 CRC errors]
indicate the number of Modbus frames containing checksum errors.
In the case of these two counters, only frames that are destined for the drive and whose Modbus address is supplied by the
[Modbus
Address]
(
Add)
parameter are counted. Broadcast frames are not counted.
[Mb1 process frames]
and
[Mb2 process frames]
are modulo 65 536 counters, i.e., the value is reset to zero once the value of
65 535 is reached.
By contrast, the
[Mb1 CRC errors]
and
[Mb2 CRC errors]
remain at 65 535 once this value is reached.
Each Modbus counter corresponds to a drive parameter:
Menu
[MODBUS NETWORK DIAG]
[MODBUS HMI DIAG]
Parameter name
[Mb1 process frames]
[Mb1 CRC errors]
[Mb2 process frames]
[Mb2 CRC errors]
Code
M1CT
M1EC
M2CT
M2EC
Logical address
6011
6010
6031
6030
24 1755863 11/2010
Diagnostics
Control-signal diagnostics
On the graphic display terminal, the
[1.2 - MONITORING]
(
SUP-)
menu (
[COMMUNICATION MAP]
(
CMM)
submenu) can be used to display control-signal diagnostic information between the Altivar 71 drive and the Modbus master:
• Active command channel
• Value of the command word (CMD) produced by the active command channel
• Active target channel
• Value of the target produced by the active target channel
• Value of the status word
• Values of four parameters selected by the user
• In the
[COM. SCANNER INPUT MAP]
submenu: Values of communication scanner input words
• In the
[COM SCANNER OUTPUT MAP]
submenu: Values of communication scanner output words
• In the
[CMD. WORD IMAGE]
submenu: Command words produced by all channels
• In the
[FREQ. REF. WORD MAP]
submenu: Frequency targets produced by all channels
Example of displaying communication diagnostic information
RUN MDB +50.00Hz
80A
COMMUNICATION MAP
Cmd Channel
Cmd value
Active ref. channel
Frequency ref
:
: Modbus
: 000F
Hex
Modbus
: 500.0
Hex
Status word
Code
W3204
W3205
W7132
W0 :
:
: 8627
Hex
Quick
: 53
: 725
0000
Hex
-----
COM. SCANNER INPUT MAP
COM SCANNER OUTPUT MAP
CMD. WORD IMAGE
FREQ. REF. WORD MAP
MODBUS NETWORK DIAG
MODBUS HMI DIAG
CANopen MAP
PROG. CARD SCANNER
Displaying the command word
The
[Cmd Channel]
parameter indicates the active command channel.
The
[Cmd value]
parameter indicates the hexadecimal value of the command word (CMD) used to control the drive.
The
[CMD. WORD IMAGE]
submenu (
[Modbus cmd.]
parameter) is used to display the hexadecimal value of the command word produced by Modbus.
1755863 11/2010 25
Diagnostics
Displaying the frequency target
The
[Active ref. channel]
parameter indicates the active target channel.
The
[Frequency ref]
parameter indicates the value (in 0.1 Hz units) of the frequency target (LFR) used to control the drive.
The
[FREQ. REF. WORD MAP]
submenu (
[Modbus ref.]
parameter) is used to display the value (in 0.1 Hz units) of the speed target produced by Modbus.
Displaying the status word
The
[Status word]
parameter indicates the value of the status word (ETA).
Displaying parameters selected by the user
The four
[W
••••]
parameters indicate the value of the four words selected for monitoring by the user.
The address and display format of these parameters can be configured in the
[6 - MONITORING CONFIG.]
menu
(
[6.3 - COM. MAP CONFIG.]
submenu).
The value of a monitored word equals "-----" if:
• Monitoring has not been activated (address equals W0)
• The parameter is protected
• The parameter is not known (e.g., W3200)
Displaying communication scanner values
On the graphic display terminal, in the
[1.2 - MONITORING]
(
SUP-)
menu (
[COMMUNICATION MAP]
(
CMM-)
submenu):
- The
[COM. SCANNER INPUT MAP]
(
ISA-)
submenu is used to display the value of the 8 communication scanner input parameters NM1 to NM8.
- The
[COM SCANNER OUTPUT MAP]
(
OSA-)
submenu is used to display the value of the 8 communication scanner output parameters NC1 to NC8.
Configuration of these periodic parameters is described in the "Configuration" section.
Example of communication scanner display on the graphic display terminal:
RUN MDB +50.00Hz
80A
COM. SCANNER INPUT MAP
Com Scan In1 val.
Com Scan In2 val.
: 34359
: 600
Com Scan In3 val.
Com Scan In4 val.
Com Scan In5 val.
Code
: 0
: 0
: 0
Quick
Com Scan In6 val.
Com Scan In7 val.
Com Scan In8 val.
: 0
: 0
: 0
RUN MDB +50.00Hz
80A
COM SCANNER OUTPUT MAP
Com Scan Out1 val.
Com Scan Out2 val.
Com Scan Out3 val.
Com Scan Out4 val.
Com Scan Out5 val.
Code
Com Scan Out6 val.
Com Scan Out7 val.
Com Scan Out8 val.
: 15
: 598
: 0
: 0
: 0
Quick
: 0
: 0
: 0
In this example, only the first two parameters have been configured (default assignment).
[Com Scan In1 val.]
[Com Scan In2 val.]
= [34343] Status word = 34359 = 16#8637
= [600] Output speed = 600
[Com Scan Out1 val.]
= [15] Command word = 15 = 16#000F
[Com Scan Out2 val.]
= [598] Speed target = 600
V
V
Drivecom status "Operation enabled", reverse operation, speed reached.
600 rpm
V
"Enable operation" (Run) command
V
598 rpm
26 1755863 11/2010
Diagnostics
Communication faults
If there is no Modbus communication, the indicators of the integrated display terminal or graphic display terminal do not light.
There is no specific indicator for Modbus communication fault.
In factory settings, a Modbus communication fault triggers a re-settable drive fault
[Modbus com.]
(
SLF1)
and a freewheel stop.
The response of the drive in the event of a CANopen
®
communication fault can be changed (see "Configuring communication fault management") :
- Drive fault
[Modbus com.]
(
SLF1)
(freewheel stop, stop on ramp, fast stop or DC injection stop).
- No drive fault (stop, maintain, fallback).
The fault management is described in the user’manual "Communication parameters", chapter "Communication monitoring" :
• After initialization (power up), the drive checks that at least one of the command or target parameters has been written once via
Modbus.
• Then, if a Modbus communication fault occurs, the drive reacts according to the configuration (stop, maintain, fallback ...).
The Modbus communication fault is generated if the drive receives no request during a predefined period (see "Configuration of the communication fault management").
Every type of request is taken into account (write, read...).
If the drive is connected to a Modbus communication gateway, the upper level network may be connected to :
- a PLC that commands the drive,
- an industrial display terminal (Magelis) or a SCADA that monitors the drive.
If the PLC fails, the SCADA may go on transmitting Modbus requests to the drive. In this case, the Modbus communication fault will not appear.
1755863 11/2010 27
Modbus protocol
RTU mode
The transmission mode used is RTU mode. The frame contains no message header byte, nor end of message bytes.
It is defined as follows:
Slave address
Request code Data
The data is transmitted in binary code.
CRC16: cyclic redundancy check parameter.
The end of the frame is detected on a silence greater than or equal to 3.5 characters.
CRC16
Principle
The Modbus protocol is a master-slave protocol.
Master
Only one device can transmit on the line at any time.
The master manages the exchanges and only it can take the initiative.
It interrogates each of the slaves in succession.
No slave can send a message unless it is invited to do so.
In the event of an error during data exchange, the master repeats the question and declares the interrogated slave absent if no response is received within a given time period.
If a slave does not understand a message, it sends an exception response to the master.
The master may or may not repeat the request.
Slave j
Slave i
Slave k
Direct slave-to-slave communications are not possible.
For slave-to-slave communication, the application software must therefore be designed to interrogate one slave and send back data received to the other slave.
Two types of dialog are possible between master and slaves:
• The master sends a request to a slave and waits for it to respond
• The master sends a request to all slaves without waiting for them to respond (broadcasting principle)
28 1755863 11/2010
Modbus protocol
Altivar 71 Integrated Modbus
The Altivar 71 features 2 integrated Modbus ports:
· Modbus network
· Modbus HMI
These 2 ports are physically independent of one another. They are connected to 2 different Modbus networks, each with its own master.
Different speeds and formats are possible in each case.
These 2 networks provide access to the drive’s 3 Modbus servers, which are identified by their address. The address of each server is the same on both networks.
These 2 networks constitute a single channel: The drive makes no distinction between the commands and targets that come from the 2 ports (i.e., the 2 Modbus masters).
In practice, a single PLC or industrial HMI terminal (Magelis type) controls the drive.
The display terminal and PC-Software are also Modbus masters, but benefit from designated channels. They are identified as setup tools and make use of specific services.
Addresses
• The Modbus addresses of the drive can be configured from 1 to 247.
• Address 0 coded in a request sent by the master is reserved for broadcasting. ATV 71 drives take account of the request, but do not respond to it.
The drive has 3 Modbus servers, each with its own address:
• One Modbus server for the drive parameters
• One Modbus server for the variables (%MW...) of the "Controller inside" programmable card
• One Modbus server for the communication card (Ethernet) parameters
The addresses of these servers are identical for both Modbus network and Modbus HMI. The assignment of these addresses is subject only to the following regulations:
- Addresses must be between 1 and 247.
- Each address must be unique within the context of the network.
1755863 11/2010 29
Modbus protocol
Modbus functions
The following table indicates which Modbus functions are managed by the Altivar 71, and specifies their limits.
The "read" and "write" functions are defined from the point of view of the master.
Code
3 = 16#03
6 = 16#06
8 = 16#08
16 = 16#10
23 = 16#17
43 = 16#2B
Modbus name
Read Holding Registers
Write Single Register
Diagnostics
Write Multiple Registers
Read/Write Multiple Registers
Read Device Identification
Function name
Read N output words
Write one output word
Diagnostics
Write N output words
Read/write N words
Identification
Broadcast
NO
YES
NO
YES
NO
NO
Max. value of N
63 words max.
–
61 words max.
20/20 words max.
–
Read N output words: Function 3
Note:
Hi = high order byte, Lo = low order byte.
This function can be used to read the ATV 71 parameters, regardless of type.
Request
Slave no.
1 byte
03
1 byte
No. of first word
Hi Lo
2 bytes
Number of words
Hi Lo
2 bytes
Response
Slave no.
1 byte
03
1 byte
Number of bytes read
1 byte
First word value
Hi Lo
2 bytes
-------
Lo
CRC16
Hi
2 bytes
Last word value
Hi Lo
2 bytes
Lo
CRC16
2 bytes
Hi
Example 1: Use function 3 to read 4 words W3 102 to W3 105 (16#0C1E to 16#0C21) on slave 2, where:
• SFr = Switching frequency = 4 kHz (W3 102 = 16#0028)
• tFr = Maximum output frequency = 60 Hz (W3 103 = 16#0258)
• HSP = High speed = 50 Hz (W3 104 = 16#01F4)
• LSP = Low speed = 0 Hz (W3 105 = 16#0000)
Request
02 03 0C1E 0004 276C
Response
02 03
Value of:
Parameters:
08 0028
W3 102
SFr
0258
W3 103 tFr
01F4
W3 104
HSP
0000
W3 105
LSP
52B0
30 1755863 11/2010
Modbus protocol
Example 2: Use function 3 to read 5 memory words %MW20 (16#0014) to %MW24 (16#0018) on the “Controller Inside” card (catalog number: VW3 A3 510); the Modbus server address for this card is configured using the
[Modbus add CI card]
(
AMOA)
parameter:
Modbus address 54 (16#36). The five values read are as follows: 16#0054, 16#0123, 16#01A3, 16#1AD5, and 16#009E.
Request
36 03 0014 0005 C18A
Response
36 03 0A 0054
%MW20
0123
%MW21
01A3
%MW22
1AD5
%MW23
009E
%MW24
214C
Example 3: Use function 3 to read the current value of the Ethernet card IP address (reference: VW3 A3 310); the Modbus server address for this card is configured using the
[Mdbs add com card]
(
AMOC)
parameter: Modbus address 104 (16#68). The 4 consecutive addresses used for this IP address run from 60 006 (16#EA66) to 60 009 (16#EA69) and their values are equal to 16#008B, 16#00A0,
16#0045, and 16#F1 (IP address = IPC1.IPC2.PC3.IPC4 = 139.160.69.241).
Request
68 03 EA66 0004 9937
Response
68 03 08 008B
IPC1
00A0
IPC2
0045
IPC3
00F1
IPC4
2E0A
Write one output word: Function 6
Request and response (the frame format is identical)
Slave no.
1 byte
06
1 byte
Hi
Word number
Lo
2 bytes
Hi
Value of word
Lo
2 bytes
Example: Write value 16#000D to word W9 001 (16#2329) on slave 2 (ACC = 13 s).
Request and response
02 06 2329 000D 9270
Lo
CRC16
2 bytes
Hi
1755863 11/2010 31
Modbus protocol
Diagnostics: Function 8
Subcode 16#00: Echo
This function asks the slave being interrogated to echo (return) the message sent by the master in its entirety.
Subcode 16#0A: Counter reset
This function resets all the counters responsible for monitoring a slave’s exchanges.
Subcode 16#0C: Read message counter responsible for counting messages received with checksum errors
Subcode 16#0E: Read message counter responsible for counting messages addressed to slave
Read a word indicating the total number of messages addressed to the slave, regardless of type (excluding broadcast messages).
Request and response
Slave no.
1 byte
08
1 byte
Hi
Subcode
Lo
2 bytes
Hi
Data
N bytes
Lo Lo
CRC16
2 bytes
Hi
Subcode
00
0A
0C
0E
Request data
XX YY
00 00
00 00
00 00
Response data
XX YY
00 00
XX YY
(= counter value)
XX YY
(= counter value)
Function executed
Echo
Counter reset
Read message counter responsible for counting messages received with checksum errors
Read message counter responsible for counting messages addressed to slave
Example: Values 16#31 and 16#32 echoed by slave 4
Request and response (if function successful)
Slave no.
Request code or Response code
08
Hi
00
Subcode
Lo
00 04
(hexadecimal values)
Value of 1
31 st
byte Value of 2 nd
32
byte
Lo
74
CRC16
Hi
1B
32 1755863 11/2010
Modbus protocol
Write N output words: Function 16 (16#10)
Request
Slave no.
1 byte
10
1 byte
No. of first word
Hi Lo
2 bytes
Number of words Number of bytes
Hi Lo
2 bytes 1 byte
Response
Slave no.
10
Value of first word
Hi Lo
2 bytes
1 byte 1 byte
No. of first word
Hi Lo
2 bytes
Number of words
Hi Lo
2 bytes
Lo
CRC16
Hi
2 bytes
-------
Lo
CRC16
Hi
2 bytes
Example: Write values 20 and 30 to words W9 001 and W9 002 on slave 2 (acceleration time = 20 s and deceleration time = 30 s)
Request
Slave no.
02
Request code
10
No. of first word
Hi
23
Lo
29
Number of words
Hi Lo
00 02
Number of bytes
04
Value of first word Value of second word
Hi Lo Hi Lo
00 14 00 1E
CRC16
Lo
73
Hi
A4
Response
Slave no.
Response code
10
Hi
No. of first word
Lo
23 29
Number of words
Hi Lo
00 02
Lo
9B
CRC16
Hi
B7 02
(hexadecimal values)
1755863 11/2010 33
Modbus protocol
Identification: Function 43 (16#2B)
Request
Slave no.
1 byte
2B
1 byte
Type of MEI
0E
1 byte
ReadDeviceId
01
1 byte
Response
Slave no.
1 byte
2B
1 byte
Type of MEI
0E
1 byte
ReadDeviceId
01
1 byte
------Number of additional frames
00
1 byte
Object Id
00
1 byte
Lo
CRC16
Hi
2 bytes
Degree of conformity
02
1 byte
Next object Id
00
1 byte
-------
Number of objects
04
1 byte
-------
------Id of object no. 1
00
1 byte
------Id of object no. 2
01
1 byte
------Id of object no. 3
02
1 byte
------Id of object no. 4
06
1 byte
Length of object no. 1
0D
1 byte
Length of object no. 2
0B
1 byte
Length of object no. 3
04
1 byte
Length of object no. 4
09
1 byte
Value of object no. 1
“Schneider-Electric”
18 bytes
Value of object no. 2
“ATV71HU15M3”
11 bytes
Value of object no. 3
“0201”
0 4 bytes
Value of object no. 4
“MACHINE 4”
0 9 bytes
-------
-------
-------
-------
-------
Lo
1 byte
CRC16
Hi
1 byte
The total response size given in this example equals 55 bytes
The response contains the following four objects:
• Object no. 1: Manufacturer name (always "Schneider-Electric", i.e., 18 bytes).
• Object no. 2: Device reference (ASCII string; for example: “ATV71HU15M3”, i.e., 11 bytes).
The length of this object varies according to drive type. Use the “Length of object no. 2” field to determine the length.
• Object no. 3: Device version, in "MMmm" format where "MM" represents the determinant and "mm" the subdeterminant
(4-byte ASCII string; for example: "0201" for version 2.1).
• Object no. 4: Device name (ASCII string; for example: "MACHINE 4", i.e., 9 bytes).
The length of this object varies according to the device name assigned to the drive (the latter being configured by the user):
[7. DISPLAY CONFIG.]
menu,
[7.1 USER PARAMETERS]
submenu,
[DEVICE NAME]
parameter.
Maximal length 16 bytes.
34 1755863 11/2010
Modbus protocol
Negative response specifically related to identification function
Slave no.
1 byte
Error code:
2B + 80
AB
1 byte
16#00 =
16#01 =
16#02 =
Type of MEI
0E
1 byte
Error code
00 to 02
1 byte
Lo
1 byte
CRC16
Hi
1 byte
No error
The "Request code" (16#2B), the "Type of MEI" (16#0E) or the "ReadDeviceId" (16#01) contained in the request is incorrect
The "Object Id" (16#00) contained in the request is incorrect
Example of positive response: Following the request from the Modbus master, slave 2 identifies itself as follows:
• Manufacturer name = “Schneider-Electric”
• Device name = “ATV71HU15M3”
• Device version = “0201”
• Device name = “MACHINE 4”
Request
Slave no.
02
Request code
2B
Type of MEI
0E
ReadDeviceld
01
Object Id
00
CRC
Lo
34
CRC
Hi
77
Response
Slave no.
02
Response code
2B
Type of
MEI
0E
ReadDeviceld
01
Degree of conformity
02
No. of additional frames
Next object Id
00 00
Object no.
04
-------
-------
-----
-----
Id of object no.
1
00
Length of object no. 1
0D
’T’
54
’e’
65
’l’
6C
’e’
65
’m’
6D
Value of object no. 1
’e’ ’c’ ’a’
65 63 61
’n’
6E
’i’
69
’q’
71
’u’
75
’e’
65
-----
-----
----
----
Id of object no.
2
01
Length of object no. 2
0B
’A’ ’T’ ’V’
41 54 56
’7’
37
Value of object no. 2
’1’
31
’H’
48
’U’
55
’1’ ’5’ ’M’ ’3’
31 35 4D 33
----
----
----
----
Id of object no.
02
Length of object no. 3
04
Value of object no. 3
’0’ ’2’ ’0’ ’1’
30 32 30 31
----
----
Id of object no.
4
06
Length of object no. 4
09
Value of object no. 4
’M’ ’A’ ’C’ ’H’ ’I’ ’N’ ’E’
4D 41 43 48 49 4E 45
’ ’ ’4’
20 34
CRC CRC
Lo Hi
6F 50
1755863 11/2010 35
Modbus protocol
Read/write N words: Function 23 (16#17)
Request
Slave no.
1 byte
17
1 byte
--Number of bytes to be written
---
1 byte
No. of 1 st
word to be read
Hi Lo
2 bytes
Number of words to be read
Hi Lo
2 bytes
No. of 1 st
word to be written
Hi Lo
2 bytes
Number of words to be written
Hi Lo
2 bytes
---
---
Value of 1 st
word to be written
Hi Lo
2 bytes
-----------------------------
Value of last word to be written
Hi
2 bytes
Lo Lo
CRC16
2 bytes
Hi
Response
Slave no.
17 Number of bytes read
Value of 1 st
word read Value of last word read CRC16
1 byte
---
---
---
1 byte
No. of bytes to be written
Response
04
1 byte
Hi
2 bytes
Value of 1 st
word to be written
Hi
00
Lo
14
Lo -------------Hi
2 bytes
Value of 2 nd
word to be written
Hi
00
Lo
1E
Lo
Example: This example combines the two examples for functions 3 and 16. With function 23, the line is less busy than with these two functions. However, the number of words that can be read and written is restricted.
• Write values of 20 (16#14) and 30 (16#1E) respectively to the 2 words W9 001 and W9 002 on slave 2.
• Read the 4 words W3 102 to W3 105 on the same slave (values read = 16#0028, 16#0258, 16#01F4, and 16#0000).
Request
Slave no.
02
Request code No. of 1 st
word to be read
17
Hi
0C
Lo
1E
No. of words to be
Hi
00 read
Lo
04
No. of 1 st
word to be written
Hi
23
Lo
29
No. of words to be written
Hi
00
Lo
02
---
---
---
CRC
Lo
D2
Lo
2 bytes
Hi
CRC
Hi
F5
Slave no.
02
Response code
17
No. of bytes read
08
Value of 1 st word read
Hi
00
Lo
28
Value of 2 nd word read
Hi
02
Lo
58
Value of 3 rd word read
Hi
01
Lo
F4
Value of 4 th word read
Hi
00
Lo
00
CRC
Lo
12
CRC
Hi
F0
36 1755863 11/2010
Modbus protocol
Communication scanner
To improve communication performance with an Altivar 71, non-contiguous drive parameters can be copied automatically to contiguous parameters. Thus, the copy of several non-contiguous drive parameters can be read or written using a single read and/or write request (an operation, which would normally have required several Modbus requests).
This function is called the “communication scanner”.
The Altivar 71 communication scanner supports up to eight control scanner parameters and eight monitoring scanner parameters.
These parameters can be accessed via all the read and write requests supported by the Altivar 71.
There is a marked improvement in performance for the following functions:
Code
3 = 16#03
16 = 16#10
43 = 16#2B
Modbus name
Read Holding Registers
Write Multiple Registers
Read Device Identification
Function name
Read N output words
Write N output words
Identification
Max. value of N
63 words max.
61 words max.
–
The eight control scanner parameters are NC1 to NC8 (W12 761 to W12 708).
Their addresses are NCA1 to NCA8 (W12 721 to W12 728).
The eight monitoring scanner parameters are NM1 to NM8 (W12 741 to W12 748).
Their addresses are NMA1 to NMA8 (W12 701 to W12 708).
Configuration of the communication scanner is described in the "Configuration" section.
Example of how scanner parameters can be used:
• Use of the “Read/write N words” function (request code = 23 = 16#17)
• Transmission of the request to an Altivar 71 located at address 20 (16#14)
• Read all 8 monitoring scanner parameters (NM1 to NM8: W12 741 to W12 748 = addresses 16#31C5 to 16#31CC)
• List of source parameters:
No.
Parameter
3
4
1
2
ETA
RFRD
LCR
OTR
Logical address
W3 201
W8 604
W3 204
W3 205
Read value
16#0007
16#1388
16#0064
16#0045
No.
Parameter
7
8
5
6
ULN
THD
THR
LFT
Logical address
W3 207
W3 209
W9 630
W7 121
Read value
16#00F0
16#0065
16#0032
16#0000
1
2
3
4
• Write first 6 control scanner parameters (NC1 to NC6: W12 761 to W12 766 = addresses 16#31D9 to 16#31DE)
• List of target parameters:
No.
Parameter Logical address No.
Parameter Logical address
CMD
LFRD
HSP
LSP
W8 501
W8 602
W3 104
W3 105
Value to be written
16#000F
16#1388
16#1F40
16#01F4
5
6
7
8
ACC
DEC
-
-
W9 001
W9 002
W0
W0
Value to be written
16#04B0
16#0258
16#0000
16#0000
1755863 11/2010 37
Modbus protocol
The control scanner and monitoring scanner parameters are configured via the display terminal as follows:
Command
Menu
[Scan.Out1 address]
( nCA1)
[Scan.Out2 address]
( nCA2)
[Scan.Out3 address]
( nCA3)
[Scan.Out4 address]
( nCA4)
[Scan.Out5 address]
( nCA5)
[Scan.Out6 address]
( nCA6)
[Scan.Out7 address]
( nCA7)
[Scan.Out8 address]
( nCA8)
Value
8 501
8 602
3 104
3 105
9 001
9 002
0
0
Code
CMD
LFRD
HSP
LSP
ACC
DEC
Command word
Speed target
High speed
Low speed
Acceleration time
Deceleration time
Parameter name
Monitoring
Menu
[Scan. In1 address]
( nNA1)
[Scan. In2 address]
( nNA2)
[Scan. In3 address]
( nNA2))
[Scan. In4 address]
( nNA4)
[Scan. In5 address]
( nNA5)
[Scan. In6 address]
( nNA6)
[Scan. In7 address]
( nNA7)
[Scan. In8 address]
( nNA8)
Value
3 201
8 604
3 204
3 205
3 207
3 209
9 630
7 121
Code
ETA
RFRD
LCR
OTR
ULN
THD
THR
LFT
Parameter name
Status word
Output speed
Motor current
Torque
Mains voltage
Thermal state of the drive
Thermal state of the motor
Last fault
Request
Slave no.
Request code No. of 1 st
word to be read
Hi Lo
14 17 31 C5
No. of words to be read
Hi Lo
00 08
No. of 1 st
word to be written
Hi Lo
31 D9
No. of words to be written
Hi Lo
00 06
No. of bytes to be written
---
0C
---
---
---
---
---
Value of 1 st word to be written
Hi
00
Lo
0F
Value of 2 nd word to be written
Hi
13
Lo
88
Value of 3 rd word to be written
Hi
1F
Lo
40
Value of 4 th word to be written
Hi
01
Lo
F4
Value of 5 th word to be written
Hi
04
Lo
B0
Value of 6 th word to be written
Hi
02
Lo
58
CRC CRC
Lo
56
Hi
3D
Response
Slave no.
Response code
14 17
No. of bytes read
10
Value of 1 st
word read
Hi
00
Lo
07
Value of 2 nd
word read
Hi
13
Lo
88
Value of 3 rd
word read
Hi
00
Lo
64
Value of 4 th
word read
---
Hi
00
Lo
45
---
---
--Value of 5 th
word read Value of 6 th
word read Value of 7 th
word read Value of 8 th
word read
---
---
Hi
00
Lo
F0
Hi
00
Lo
65
Hi
00
Lo
32
Hi
00
Lo
00
CRC
Lo
E4
CRC
Hi
90
38 1755863 11/2010
Modbus protocol
Exception responses
An exception response is returned by a slave when it is unable to perform the request, which is addressed to it.
Format of an exception response:
CRC16
Slave no.
Response code Error code
Lo Hi
1 byte 1 byte 1 byte 2 bytes
Response code: Function code of the request + 16#80 (the most significant bit is set to 1).
Error code:
1 = The function requested is not recognized by the slave.
2 = The word addresses indicated in the request do not exist in the slave.
3 = The word values indicated in the request are not permissible in the slave.
4 = The slave has started to execute the request but cannot continue to process it completely.
Example: Write the value 1 to word ETA = W3 201 (which cannot be written, as in “read-only" mode) on slave 4.
Request
Slave no.
04
Request code
10
No. of 1st word
Hi Lo
0C 81
No. of words
Hi Lo
00 01
No. of bytes
02
Value of 1st word
Hi Lo
00 01
Response
Slave no.
Response code Error code
04 10 + 80 = 90 04
CRC
Lo
5D
CRC
Hi
C2
CRC
Lo
8A
CRC
Hi
D1
Read non-existent or protected parameters
If a set of parameters is read using a Modbus function, the value returned for non-existent and protected parameters is equal to 16#8000.
If the same Modbus function is used to read parameters, all of which are non-existent or protected, the drive sends back an exception response with an error code equal to 2.
Example of non-existent or protected parameters being read:
In this example, the same read request is used several times in a row for a non-existent parameter (W8400), CHCF (W8401) and COP
(W8402) in order to demonstrate the effects of parameter protection.
The read request is a Read N output words request (function 3) and is addressed to a drive whose Modbus address is equal to 12 (16#0C).
The read operation is performed for 3 consecutive words, starting with address W8400 (16#20D0).
The value of CHCF is equal to 16#0003 (I/O profile) and the value of COP is equal to 16#0002 (copy of the command word on switching from command channel no. 1 to command channel no. 2).
Read N output words request:
Slave no.
0C
Request code
03
No. of 1st word
Hi Lo
20 D0
Hi
No. of words
Lo
00 03
Lo
0E
CRC16
Hi
EF
1755863 11/2010 39
Modbus protocol
Response to the Read N output words request:
Scenario no. 1: Parameters CHCF (W8 401) and COP (W8 402) not protected
V
Successful reading of these two parameters and value equal to 16#8000 for the non-existent parameter located at address W8 400.
Slave no.
0C
Response code No. of bytes read Value of W8 400 Value of W8 401 Value of W8 402
Hi Lo Hi Lo Hi Lo
03 06 80 00 00 03 00 02
Lo
CRC16
Hi
17 E4
Scenario no. 2: Parameter CHCF (W8 401) protected and COP (W8 402) not protected
V
Successful reading of COP and value equal to
16#8000 for the non-existent parameter located at address W8 400 and for parameter CHCF.
Slave no.
Response code
0C 03
No. of bytes read Value of W8 400 Value of W8 401 Value of W8 402
Hi Lo Hi Lo Hi Lo
06 80 00 80 00 00 02
Lo
CRC16
Hi
CE 24
Scenario no. 3: Parameters CHCF (W8 401) and COP (W8 402) protected
V
Exception response (response code = 16#80 + request code), as all the parameters read are either non-existent, or protected; error code equal to 2 (the word addresses indicated in the request do not exist in the slave).
Slave no.
Response code Error code
0C 80+03 = 83 02
Lo
CRC16
Hi
51 32
40 1755863 11/2010
Appendix: Non-standard schematics
UNI-TELWAY schematic
Schneider-Electric used the UNI-TELWAY bus schematic for drives and soft starters (ATV58, ATV28, ATS48, etc.) sold prior to the publication of the Modbus specifications on www.modbus.org. In the case of the ATV31 and ATV71 speed drives, the standard schematic applies (see page
Schematic diagram:
Master
R
4,7 k
Ω
0 V
T
5 V
4,7 k
Ω
D(B)
120
Ω
1 nF
120
Ω
1 nF
D(A)
0VL
4,7 k
Ω
0 V
5 V
4,7 k
Ω
R
T
Slave 1
4,7 k
Ω
0 V
R
T
5 V
4,7 k
Ω
Slave n
Type of trunk cable
Maximum length of bus
Maximum number of stations (without repeater)
Maximum length of tap links
Bus polarization
Line terminator
Common polarity
Cable with 2 twisted pairs shielded in pairs
1000 m at 19200 bps
29 stations, i.e., 28 slaves
• 20 m
• 40 m divided by the number of tap links on a multiple junction box
For the master and each slave:
• One 4.7 k
Ω pulldown resistor at 5 V
• One 4.7 k
Ω pulldown resistor at 0 VL
One 120
Ω 0.25 W resistor in series with a 1 nF 10 V capacitor
Yes (0 VL) and high impedance placed between 0 VL and the ground in each station
1755863 11/2010 41
Appendix: Non-standard schematics
Jbus schematic
Schematic diagram:
Master
R
470
Ω
0 V
T
5 V
470
Ω
L- (B/B')
150
Ω
L+ (A/A')
150
Ω
R
T
Slave 1
R
T
Slave n
Type of trunk cable
Maximum length of bus
Maximum number of stations (without repeater)
Maximum length of tap links
Bus polarization
Line terminator
Common polarity
Cable with 1 shielded twisted pair
1300 m at 19200 bps
32 stations, i.e., 31 slaves
3 m
One 470
Ω pulldown resistor at 5 V
One 470
Ω pulldown resistor at 0 V
This polarization is often provided in the master.
One 150
Ω resistor
No
42 1755863 11/2010
Appendix: Non-standard schematics
Use of UNI-TELWAY slaves in a standard schematic
Slaves with 4.7k
Ω polarization can be integrated into a standard schematic. Suitable polarization resistance (Rp) must be calculated.
Schematic diagram:
In this example, slave 1 has a 4.7 k
Ω polarization.
Master
R
T
5 V
Rp
Rp
0 V
D1
120
Ω
1 nF
D0
Common
4,7 k
Ω
0 V
5 V
4,7 k
Ω
R
R
T T
Slave 1
Slave n
Type of trunk cable
Maximum length of bus
Maximum number of stations (without repeater)
Maximum length of tap links
Shielded cable with 1 twisted pair and at least a 3
1000 m at 19200 bps
rd
conductor
Up to 32 stations, i.e., 31 slaves (depending on Rp and the number of 4.7 k
Ω resistors)
Bus polarization
Line terminator
Common polarity
• 20 m for a single tap link
• 40 m divided by the number of tap links on a multiple junction box
• One pulldown resistor at 5 V (Rp)
• One pulldown resistor at the Common (Rp)
This polarization can be provided in the master.
The value of Rp should be validated (or determined) by calculating the equivalent polarization (Re) according to the polarization of the master and slave stations.
The value of Re must be between 162
Ω and 650 Ω (recommended value: 650 Ω).
One 120
Ω 0.25 W resistor in series with a 1 nF 10 V capacitor
Yes (Common)
• If the master has a 470
Ω polarization and all the slaves have 4.7 kΩ polarization, up to 18 slaves can be connected.
• To calculate the polarization resistance (Rp), all station polarizations must be deemed to be connected in parallel.
Example:
If the bus Rp polarization is 470
Ω (installed in the master) and 2 slaves have 4700 Ω polarization, the equivalent polarization is:
1/Re = 1/470 + 1/4700 + 1/4700, i.e., Re = 1/ (1/470 + 1/4700 + 1/4700) and therefore Re = 390
Ω.
390
Ω is greater than 162 Ω, and the schematic is correct.
For an ideal equivalent polarization (650
Ω), Rp bus polarization can be installed so that:
1/650 = 1/Rp + 1/4700 + 1/4700, i.e., Rp = 1/(1/650 - 1/4700 - 1/4700) and therefore Rp = 587
Ω.
1755863 11/2010 43
Appendix: Non-standard schematics
Recommendations for setting up a Modbus network using non-standard devices
1. Identify polarities D0 and D1.
They are labeled in a variety of ways according to the specification used:
Modbus
EIA/TIA-485
UNI-TELWAY
Jbus
D0
A / A’
D(A)
RD + / TD +
L +
D1
B / B’
D(B)
RD - / TD -
L -
Common
C / C’
0VL
However, certain RS485 electronic components are labeled in the opposite way to the EIA/TIA-485 standard.
It may be necessary to perform a test by connecting a master to a slave, then reversing the connection in the event of failure.
2. Check polarizations.
Study the documentation supplied with the devices to determine the polarization resistance.
Polarization is not always possible. For example, in the event of the 5 V not being available in the master.
3. Select a line terminator.
In the case of polarization, select an RC line terminator (R = 120
Ω, C = 1 nF).
If polarization is not possible, select an R line terminator (R = 150
Ω).
44 1755863 11/2010
ATV71_modbus_int_EN_1755863_03
1755863 11/2010
Atsisiųsti