Omron SYSDRIVE 3G3JV-A2007, SYSDRIVE 3G3JV-AB002 Manual
광고
광고
Note: Do not use this document to operate the Unit.
OMRON Corporation
FA Systems Division H.Q.
66 Matsumoto
Mishima-city, Shizuoka 411-8511
Japan
Tel:(81)55-977-9181
Fax:(81)55-977-9045
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel:(31)2356-81-300/Fax:(31)2356-81-388
OMRON ELECTRONICS LLC
1 East Commerce Drive, Schaumburg, IL 60173 U.S.A.
Tel:(1)847-843-7900/Fax: (1)847-843-8568
OMRON IDM Controls
9510 North Houston, Tx. 77088 U.S.A.
Tel: (1)800-395-4106/Fax: (1)713-849-4666
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue, #11-01, UE Square,
Singapore 239920
Tel:(65)6835-3011/Fax : (65)6835-2711
Authorized Distributor:
Note: Specifications subject to change without notice.
Cat.No.I905-E1-05
Printed in Japan
0204-1M
Simple, Compact Inverters
3G3JV
Series
There has been a great demand for inverters that provide easier motor speed control. OMRON's simple, compact 3G3JV Series meets the demand.
The 3G3JV Inverters provide versatile functions and ensure powerful performance.
The front panel of the 3G3JV Inverter has a frequency adjuster that makes it possible to start the motor and easily control the motor speed.
The 3G3JV Inverters are easy to mount and operate and support a wide range of applications for efficient motor control.
2
Actual
Size
Three-phase 100 W at 200 V
68 x 128 x 78.5 mm (W x H x D)
The frequency adjuster on the front panel makes it possible to easily adjust the speed of the motor.
The Inverter can be operated immediately after the power is turned ON.
C o n t e n t s
Features
Applications
Nomenclature
Using Digital Operator
List of Parameters
Function of Each Parameter
Specifications
Dimensions
Standard Connections
Protective and Diagnostic Functions
Options
Inverter Models
6
8
2
4
11
14
22
27
28
29
34
47
This catalog provides information for the selection of models, but does not provide operational precautions. For information on the operation of the 3G3JV Inverters and operational precautions, be sure to read the operation manual.
The 3G3JV Inverter performs versatile speed control, such as multi-step speed control up to a maximum of nine steps, acceleration and deceleration (UP/DOWN) control, and jog operations. Furthermore, the 3G3JV Inverter provides a variety of useful functions, including slip compensation, overtorque detection, and speed search functions.
The cooling fan can be easily mounted or dismounted. The cooling fan can also be turned on only when the 3G3JV
Inverter is in operation, prolonging the life of the fan.
The 3G3JV Inverter incorporates main circuit terminals arranged in two rows on the top and bottom of the housing, making it possible to mount the 3G3JV
Inverter like a contactor. The optional DIN Track
Mounting Bracket makes it possible to easily mount a
3G3JV Inverter to a
DIN track.
The 3G3JV Inverters are compact and space-saving to mount easily into a panel.
The 3G3JV Inverter supports a variety of I/O, such as analog inputs between 0 and 10V, 4 to 20 mA, or 0 to 20 mA, multifunction I/O, and analog monitor outputs. Multi-function inputs can set to either PNP or NPN, providing flexibility in input signals.
Standard models meet CE and UL/cUL standards.
C
3
Relay contact welding occurs, which may put the system and operators in danger. Furthermore, the life of the system is comparatively short.
The system employs a gearbox for speed control, the designing and adjustment of which require time and labor.
Breaker
To ensure the safety of the system, the system needs peripheral safety devices, the wiring of which requires time and labor.
Open-phase detection
The motor always rotates at top speed, consuming a high amount of power.
A strong shock is produced when the motor is driven, which may cause loads to shift, deteriorate the quality of products, or put the system and operators in danger.
Contactor
Three-phase inductive motor
Current leakage detection
Gear box Starter
A 3G3JV Inverter has no mechanical relay contacts and thus allows a safe, long-life system operation.
A 3G3JV Inverter performs versatile speed control, such as multi-step speed control for up to nine steps, acceleration and deceleration (UP/DOWN) control, and jog operations.
A 3G3JV Inverter provides a variety of protective functions, such as a highspeed current limit, ground fault protection, and undervoltage protection.
A 3G3JV Inverter drives the motor at flexible speeds within the rated speed range of the motor, thus reducing motor power consumption.
A 3G3JV Inverter provides soft-start and soft-stop functions, preventing loads from shifting and deterioration of product quality, while ensuring the safety of the system.
Breaker
3G3JV
Inverter
Three-phase inductive motor
A strong shock results at the moment the motor is driven, which may cause load shifting, deteriorates the quality of products, or puts the system and operators in danger.
The capacity of the motor is small.
Therefore, the rotation speed of the motor will drop if a speed reducer is used for the maintenance of the torque.
The rotation of the motor fluctuates.
Failures in the motor are not detected by the host controller.
The types of available motors are limited.
Breaker
4
Gear box
Speed controller
A 3G3JV Inverter provides soft-start and soft-stop functions, preventing loads from shifting and deterioration of product quality while ensuring the safety of the system.
The 3G3JV Inverters are available up to a maximum motor capacity of 3.7 kW and ensure smooth rotation speed and torque in the motor.
A three-phase motor has less speed fluctuation compared with a singlephase motor, ensuring the safe operation of the system.
A 3G3JV Inverter can report errors in contact outputs or data to a host controller, such as a Programmable
Controller.
A wide range of motors is available.
Breaker
3G3JV
Inverter
Three-phase inductive motor
A 3G3JV Inverter provides soft-start and soft-stop functions to prevent loads from shifting. Furthermore, a 3G3JV Inverter performs flexible speed control of the conveyor up to nine steps.
A 3G3JV Inverter performs flexible speed control of a compact agitator or separator.
A 3G3JV Inverter provides optimum control of fan speed according to the room temperature. The 3G3JV Inverter has no mechanical relay contacts, ensuring the safety and reliability of the system compared with the ON/OFF control of contactors. Optimum control of fan speed also saves energy.
A 3G3JV Inverter provides multi-step speed control to open and close an electric shutter safely and efficiently. The shutter opens quickly at a high speed, but closes at a medium-range speed while the system checks the safety of the operation and decelerates to low speed before it is fully closed to prevent people from being caught by the shutter.
5
6
Nomenclature
Panel
Top protection cover:
Remove this cover when wiring the upper terminal block.
Upper terminal block:
A terminal block on the input side of the main circuit.
Digital Operator:
Used to set parameters, perform various monitoring, and start and stop the Inverter.
ALARM indicator:
RUN indicator:
Displays the operating status of the Inverter.
Alarm (Red): Lights when an error occurs. Flashes when a warning occurs.
RUN (Green): Flashes when no RUN command is input during normal status. Lights when a RUN command is input during normal status.
Optional cover:
Remove this cover when setting the input method selector.
Front cover:
Remove this cover when wiring the upper or lower terminal block.
Front cover mounting screw:
A screw for fixing the front cover.
Lower terminal blocks:
A terminal block on the output side of the main circuit and a terminal block for the control circuit.
Bottom protection cover:
Remove this cover when wiring the lower terminal blocks.
Nomenclature
Digital Operator
Data display
Keys
Indicators
(Setting/Monitor item indicators)
FREQ adjuster
Appearance Name
Data display
Frequency adjuster
Function
Displays relevant data items, such as frequency reference, output frequency, and parameter set values.
Sets the frequency reference within a range between 0 Hz and the maximum frequency.
Frequency reference indicator
Output frequency indicator
Output current indicator
Multi-function monitor indicator
Forward/Reverse selection indicator
Local/Remote selection indicator
Parameter setting indicator
Mode Key
Increment Key
Decrement Key
Enter Key
RUN Key
STOP/RESET Key
The frequency reference can be monitored or set while this indicator is lit.
The output frequency of the Inverter can be monitored while this indicator is lit.
The output current of the Inverter can be monitored while this indicator is lit.
The values set in U01 through U10 are monitored while this indicator is lit.
The direction of rotation can be selected while this indicator is lit when operating the Inverter with the RUN Key.
The operation of the Inverter through the Digital Operator or according to the set parameters is selectable while this indicator is lit. (See note 1.)
The parameters in n01 through n79 can be set or monitored while this indicator is lit. (See note 2.)
Switches the setting and monitor item indicators in sequence.
Parameter being set will be canceled if this key is pressed before entering the setting.
Increases multi-function monitor numbers, parameter numbers, and parameter set values.
Decreases multi-function monitor numbers, parameter numbers, and parameter set values.
Enters multi-function monitor numbers, parameter numbers, and internal data values after they are set or changed.
Starts the Inverter running when the 3G3JV is in operation with the Digital
Operator.
Stops the Inverter unless parameter n06 is set to disable the STOP Key.
Used to reset the Inverter when an error occurs. (See note 3.)
Note: 1. The status of the local/remote selection indicator can be only monitored while the Inverter is in operation. Any RUN command input is ignored while this indicator is lit.
2. While the Inverter is in operation, the parameters can be only monitored and only some parameters can be changed. Any
RUN command input is ignored while the parameter setting indicator is lit.
3. For safety reasons, the reset function cannot be used while an operation instruction (forward/reverse) is being input. Turn the operation instruction OFF before using this function.
7
8
Using Digital Operator
Selecting Indicators
Power ON
Frequency reference
Output frequency
Output current represents a lit indicator.
Parameter settings
Parameter n01
Parameter n02
Local/Remote selection
Remote mode
Local mode
Direction of rotation
Forward
Reverse
Multi-function monitor
Frequency reference
Output frequency
Other parameters Other monitor items
Note: If the power is turned OFF with the FOUT or IOUT indicator lit, the same indicator will light when the power is turned ON again.
In other cases, the FREF indicator will light when the power is turned ON.
Example of Frequency Reference Settings
Flashing
Key sequence Indicator Display example Explanation
Power ON
Note If the FREF indicator has not been lit, press the Mode
Key repeatedly until the FREF indicator is lit.
Use the Increment or Decrement Key to set the frequency reference.
The data display will flash while the frequency reference is set. (see note 1)
Press the Enter Key so that the set value will be entered and the data display will be lit. (see note 1)
Note: The Enter Key need not be pressed when performing the setting for n08. The frequency reference will change when the set value is changed with the Increment or Decrement Key while the data display is continuously lit.
Using Digital Operator
Example of Multi-function Display
Frequency reference
DC bus voltage
Monitor data
Complete
Key sequence Indicator Display Explanation
Power ON
Press the Mode Key repeatedly until the MNTR indicator is lit.
U01 will be displayed.
Use the Increment or Decrement Key to select the monitor item to be displayed.
Press the Enter Key so that the data of the selected monitor item will be displayed.
The monitor number display will appear again by pressing the Mode Key.
U01
U02
U03
U04
U05
U06
Status Monitor
Item Display
Frequency reference Hz
Display unit
Output frequency Hz
Output current
Output voltage
A
V
DC bus voltage V
Input terminal status ---
Function
Monitors the frequency reference. (Same as FREF)
Monitors the output frequency. (Same as FOUT)
Monitors the output current. (Same as IOUT)
Monitors the internal output voltage reference value of the Inverter.
Monitors the DC voltage of the internal main circuit of the Inverter.
Shows the ON/OFF status of inputs.
U07
U09 status
---
---
: Input ON : No input
Not used
Terminal S1: Forward/Stop
Terminal S2: Multi-function input 1 (S2)
Terminal S3: Multi-function input 2 (S3)
Terminal S4: Multi-function input 3 (S4)
Terminal S5: Multi-function input 4 (S5)
Shows the ON/OFF status of outputs.
: Closed : Open
Not used
Displays the latest error.
Terminal MA: Multi-function contact output recent one) )
U10 Software No.
---
Error
OMRON use only.
9
10
Using Digital Operator
Example of Parameter Settings
The following example shows how to set 2 to enable the frequency reference control terminal for 0- to 10-V input in parameter n03
(Frequency Reference Selection).
Cancels set data.
Enable the frequency reference control terminal for 0- to 10-V input.
Complete
In approximately 1 s.
Key sequence Indicator Display example Explanation
Power ON
Press the Mode Key repeatedly until the PRGM indicator is lit.
Use the Increment or Decrement Key to set the parameter number.
Press the Enter Key.
The data of the selected parameter number will be displayed.
Use the Increment or Decrement Key to set the data. At that time the display will flash.
Press the Enter Key so that the set value will be entered and the data display will be lit. (see note 1)
The parameter number will be displayed.
In approximately 1 s.
Note: 1. To cancel the set value, press the Mode Key instead. The parameter number will be displayed.
2. There are parameters that cannot be changed while the Inverter is in operation. Refer to the list of parameters. When attempting to change such parameters, the data display will not change by pressing the Increment or Decrement Key.
List of Parameters
List of Parameters
Parameter
No.
n01 n02 n03 n04 n05 n06 n07 n08 n09 n10 n11 n12 n13 n14 n15 n16 n17 n18 n19 n20 n25 n26 n27 n28 n29 n21 n22 n23 n24
Name
Parameter write-prohibit selection/ parameter initialization
Operation mode selection
Frequency reference selection
Interruption mode selection
Reverse rotation-prohibit selection
STOP/RESET Key function selection
Frequency selection in local mode
Key sequential frequency setting
Maximum frequency
(FMAX)
Maximum voltage
(VMAX)
Maximum voltage frequency (FA)
Middle output frequency (FB)
Middle output frequency voltage (VC)
Minimum output frequency (FMIN)
Minimum output frequency voltage
(VMIN)
Acceleration time 1
Used to prohibit parameters to be written, sets parameters, or change the monitor range of parameters.
Used to initialize parameters to default values.
Used to select the input method for the RUN and STOP commands in remote mode.
Used to set the input method for the frequency reference in remote mode.
Description
Used to set the stopping method for use when the
STOP command is input.
Used to select the operation with the reverse command input.
Used to select the stop method in remote mode with n02 for operation mode selection set to 1.
Used to set the input method for the frequency reference in local mode.
Used to enable the Enter Key for setting the frequency reference with the Increment and Decrement Keys.
Used to set the V/f pattern as the basic characteristic of
Note Set the parameters so that the following condition will be satisfied.
14 x 12 11 x 09
Note p
14 d 12 th i l
Setting
0, 1
0, 1
0, 1
0, 1
0, 1
0, 1 range
0, 1, 6, 8, 9
0 to 4
50.0 to 400
1 to 255
(see note 1)
0.2 to 400
0.1 to 399
1 to 255
(see note 1)
0.1 to 10.0
1 to 50
(see note 1)
Deceleration time 1
Acceleration time 2
Deceleration time 2
Acceleration time: The time required to go from 0% to
100% of the maximum frequency.
Deceleration time: The time required to go from 100% to 0% of the maximum frequency.
Note The actual acceleration or deceleration time is ob tained from the following formula.
Acceleration/Deceleration time = (Acceleration/Deceleration time set value)
×
(Frequency reference value)
÷
(Max. frequency)
Used to set S-shape acceleration/deceleration characteristics.
0.0 to 999
0 to 3 S-shape acceleration/deceleration characteristic
Frequency reference 1
Frequency reference 2
Frequency reference 3
Frequency reference 4
Frequency reference 5
Frequency reference 6
Frequency reference 7
Frequency reference 8
Inching frequency command
Note Frequency reference 1 is enabled in remote mode
Note These frequency references are selected with mul multi-step speed references and frequency refer-
Used to set the inching frequency command.
f frequency
1
1
1
1
1
1
1
1
(see note 2)
0.1 Hz
1 V
0.1 Hz
0.1 Hz
1 V
Unit of setting
0.1 Hz
1 V
0.1 s
1
1
0
0
0
0
0
0
0
Default setting
60.0
No
No
No
No
No
No
No
No
No
Changes during operation
No
No
No
No
No
No
No
No
No
200 (see note 1)
60.0
No
No
1.5
12 (see note 1)
1.5
12 (see note 1)
10.0
10.0
10.0
10.0
0
0.0
0.0
0.0
0.0
6.0
6.0
0.0
0.0
0.0
No
No
No
No
Yes
Yes
Yes
Yes
No
Reference page
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
15
15
15
15
15
15
15
15
15
15
15
15
15
15
Note: 1. With 400-class Inverters, the default settings and maximum values setting ranges for n10, n13, and n15 are double those given in the table.
2. Values longer than 3 digits are rounded up to the next unit multiple.
11
List of Parameters
Parameter
No.
n30 n31 n32 n33 n34 n35 n36 n37 n38
Name Description Setting range
Frequency reference upper limit
Frequency reference lower limit
Used to set the upper and lower frequency reference
Rated motor current Used to set the rated motor current for motor overload detection (OL1) based on the rated motor current.
Note Motor overload detection (OL1) is disabled by setting the parameter to 0.0.
Motor protection characteristics
Motor protective time setting
Cooling fan operation function
Used to set the motor overload detection (OL1) for the electronic thermal characteristics of the motor.
Used to set the electric thermal characteristics of the motor to be connected in 1-minute increments.
Used to operate the Cooling Fan of the Inverter while the Inverter is turned on or only while the Inverter is in operation.
Used to select the functions of multi-function input terMulti-function input 1
(Input terminal S2)
Multi-function input 2
(Input terminal S3)
Multi-function input 3
(Input terminal S4)
0 to 110
0 to 110
0.0 to 120% of rated output current
0 to 2
1 to 60
0, 1
2 to 22
0 to 22
2 to 22
Unit of setting
(see note)
1%
1%
0.1 A
1
1 min
1
1
1
1 n40 n41 n42 n43 n44 n45 n46
(Input terminal S5)
Multi-function output
(MA/MB and MC output terminals)
Frequency reference gain
Frequency reference bias
Analog frequency reference filter time
Analog monitor output
Analog monitor output gain
Carrier frequency selection
Used to select the functions of multi-function output terminals.
Used to the input characteristics of analog frequency
Used to set the digital filter with a first-order lag for analog frequency references to be input.
Used to set the output frequency or current as a monitored item.
Used to set the output characteristics of analog monitor output.
Used to set the carrier frequency.
0 to 7, 10 to
17
0 to 255
–99 to 99
0.00 to 2.00
0.01 s
0, 1
1 to 4, 7 to
9
1
1%
1%
1
0.00 to 2.00
0.01
1
1 n49 n50 n51 n52 n53 n47 n48 n54 n55 n56 n57 n58
Momentary power interruption compensation
Fault retry
Used to specify the processing that is performed when a momentary power interruption occurs.
Used to set the number of times the Inverter is reset and restarted automatically in the case the Inverter has an overvoltage fault, overcurrent fault, or ground fault.
Jump frequency 1
Jump frequency 2
Jump width
DC control current
Interruption DC control time
Startup DC control time
Stall prevention during deceleration tion: n49 y n50
Stall prevention level during acceleration
Stall prevention level during operation
Frequency detection level
Used to select a function to change the deceleration time of the motor automatically so that there will be no overvoltage imposed on the motor during deceleration.
Used to select a function to stop the acceleration of the motor automatically for stall prevention during acceleration.
Used to select a function to reduce the output frequency of the Inverter automatically for stall prevention during operation.
Used to set the frequency to be detected.
0 to 2
0 to 10
0.0 to 400
0.0 to 400
0.0 to 400
0 to 100
0.0 to 25.5
0.0 to 25.5
0, 1
30 to 200
30 to 200
0.0 to 400
Note: Values longer than 3 digits are rounded up to the next unit multiple.
1
0.1 Hz
0.1 Hz
0.1 Hz
1%
0.1 s
0.1 s
1
1%
1%
0.1 Hz
2
5
3
0
8
0
Default setting
100
Changes during operation
No
Reference
16 page
0
Varies with the capacity.
No
No
16
16
1
0.0
0.0
0.0
50
0.5
0.0
0
No
100
0
0.10
0
1.00
No
Yes
Varies with the capacity.
0
No
No
Yes
Yes
No
0
170
160
0.0
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
17
17
18
17
17
17
16
16
16
18
18
18
18
18
18
18
16
16
16
17
18
18
19
19
19
12
List of Parameters n65 n66 n67 n68 to n74 n75
Parameter
No.
n59 n60 n61 n62 n63 n64
Name
Overtorque detection function selection
Overtorque detection level
Overtorque detection time
UP/DOWN command frequency memory
Torque compensation gain
Motor rated slip
Description
Used to enable or disable overtorque detection and select the processing method after overtorque detection.
Used to set overtorque detection level.
Used to set the detection time of overtorque.
Used to store the adjusted frequency reference with the
UP/DOWN function.
Used to set the gain of the torque compensation function.
Used to set the rated slip value of the motor in use.
Setting range
0 to 4
30 to 200
0.1 to 10.0
0, 1
0.0 to 2.5
0.0 to 20.0
1
1%
0.1 s
1
Unit of setting
(see note)
0.1
0.1 Hz
0
Default setting
Changes during operation
No
Reference
19 page
160
0.1
0
No
No
No
19
19
20
21
21 n76 n77 n78
Motor no-load current
Used to set the no-load current of the motor in use based on the rated motor current as 100%.
Slip compensation gain
Slip compensation time constant
OMRON’s control reference use
Low-speed carrier frequency reduction selection
Used to set the gain of the slip compensation function.
Used for the response speed of the slip compensation function.
Do not change the set value.
Used to select a function to reduce the carrier frequency when Inverter is at low speed.
0 to 99
0.0 to 2.5
0.0 to 25.5
---
0.1
---
Error log Used to display the latest error recorded.
---
1%
0.1
0.1 s
---
1
---
---
2.0
---
0
1.0
Yes
Varies with the capacity.
Varies with the capacity.
0.0
Yes
No
Yes
No
---
No
---
---
---
---
21
21
21
---
---
---
--n79 Software number
Note
Display
“– – –” will be displayed if no error has been recorded.
Note This parameter is monitored only.
Used to display the software number of the Inverter for
OMRON’s control reference use.
Note This parameter is monitored only.
---
Note: Values longer than 3 digits are rounded up to the next unit multiple.
---------
13
14
Function of Each Parameter
Note: The shaded values indicate default settings.
Parameter Write-prohibit Selection/Parameter
Initialization (n01)
1
6
8
This parameter makes it possible to write-prohibit parameters, change the parameter set or displayed range, or initialize all parameters to default values.
0
Value
9
Description
Only n01 can be displayed and set. The n02 through n79 parameters can be displayed only.
The n01 through n79 parameters can be displayed and set.
Only the error log memory is cleared.
Enables the initialization of all parameters in 2-wire sequence so that the parameters will return to default values.
Enables the initialization of all parameters in 3-wire sequence.
Operation Mode Selection (n02)
Select the method of operation mode input to start or stop the Inverter in remote mode.
0
Value
1
Description
The RUN and STOP/RESET Keys of the Digital Operator are enabled.
Multi-function input in 2- or 3-wire sequence through the control circuit terminals is enabled.
Note: In local mode, RUN commands can be entered using the
Digital Operator only.
Frequency Reference Selection (n03)
(Remote Mode)
Select the method for inputting the frequency reference to the Inverter in remote mode.
0
1
2
Value
3
4
Description
The FREQ adjuster of the Digital Operator is enabled.
Frequency reference 1 (n21) is enabled.
The frequency reference control terminal (for 0- to 10-V input) is enabled.
The frequency reference control terminal (for 4- to 20-mA current input) is enabled.
The frequency reference control terminal (for 0- to 20-mA current input) is enabled.
Interruption Mode Selection (n04)
Select the stopping method to be used when the STOP command is input.
0
1
Value Description
Frequency deceleration stop (Decelerates to stop in preset time.)
Free running (Output shut OFF by STOP command.)
Reverse Rotation-prohibit Selection (n05)
Select the operation to be performed when the reverse rotation command is input.
0
Value
1
Description
Reverse rotation possible (command accepted)
Reverse rotation prohibited (command not accepted)
STOP/RESET Key Function Selection (n06)
When parameter n02 is set to 1, set whether or not to use the
STOP/RESET Key of the Digital Operator to stop the Inverter in remote mode. The STOP/RESET Key is always enabled in local mode regardless of the setting in n02.
0
1
Value Description
The STOP/RESET Key of the Digital Operator is enabled.
The STOP/RESET Key of the Digital Operator is disabled.
Frequency Reference Selection (n07)
(Local Mode)
Select the input method of frequency references in local mode.
0
1
Value Description
The FREQ adjuster of the Digital Operator is enabled.
Key sequences on the Digital Operator are enabled.
Key Sequential Frequency Setting (n08)
Select whether to enable the Enter Key when setting the frequency reference with the Increment and Decrement Keys on the Digital Operator.
0
Value
1
Description
The Enter Key is enabled. (The setting is made valid by pressing the Enter Key.)
The Enter Key is disabled. (The setting is directly treated as a frequency reference without the Enter Key being pressed.)
V/f Pattern Settings (n09 to n15)
Set the V/f pattern as the basic characteristic of the Inverter with output voltage per frequency set.
Value n09 n10 n11 n12 n13 n14 n15
Name Setting range
Unit of setting
50.0 to 400 0.1 Hz Maximum Frequency
(FMAX)
Maximum Voltage (VMAX) 1 to 255
Maximum Voltage
Frequency (FA)
0.2 to 400
Middle Output Frequency
(FB)
0.1 to 399
1 V
0.1 Hz
0.1 Hz
Middle Output Frequency
Voltage (VC)
Minimum Output
Frequency (FMIN)
Minimum Output
Frequency Voltage (VMIN)
1 to 255
0.1 to 10.0
1 to 50
1 V
0.1 Hz
1 V
Default settings
60.0
200
60.0
1.5
12
1.5
12
Function of Each Parameter
Note: For n09, n11, and n12, the unit of setting is as follows:
Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if the frequency is
100 Hz or greater.
Output voltage (V) n10 n13 n15
Frequency
(Hz)
Note: 1. Set the parameters so that the following condition will be satisfied.
n14 x n12 < n11 x n09
2. The value set in n13 will be ignored if parameters n14 and n12 are the same in value.
Acceleration/Deceleration Time Settings
(n16 to n19)
The acceleration time is the time required to go from 0% to 100% of the maximum frequency and the deceleration time is the time required to go from 100% to 0% of the maximum frequency. The actual acceleration or deceleration time is obtained from the following formula.
Acceleration/Deceleration time =
(Acceleration/Deceleration time set value) × (Frequency reference value) ÷ (Max. frequency)
Value n16 n17 n18 n19
Name
Acceleration time 1
Deceleration Time 1
Acceleration time 2
Deceleration Time 2
Setting range
Unit of setting
Default settings
10.0
10.0
10.0
10.0
S-shape Acceleration/Deceleration Characteristic
(n20)
Any one of three S-shape acceleration/deceleration times (0.2,
0.5, and 1.0 s) is selectable.
1
2
3
0
Value Description
No S-shape acceleration/deceleration characteristic
(Trapezoidal acceleration/deceleration)
S-shape acceleration/deceleration characteristic time is 0.2 s
S-shape acceleration/deceleration characteristic time is 0.5 s
S-shape acceleration/deceleration characteristic time is 1.0 s
Note: When the S-shape acceleration/deceleration characteristic time is set, the acceleration and deceleration times will be lengthened according to the S-shape at the beginning and end of acceleration/deceleration.
Setting the Frequency References 1 to 8 and the
Inching Frequency Command (n21 to n28 and n29)
Set internal frequency references.
Value n21 n22 n23 n24 n25 n26 n27 n28 n29
Name Setting range
Unit of setting
Frequency reference 1
Frequency reference 2
Frequency reference 3
Frequency reference 4
Frequency reference 5
Frequency reference 6
Frequency reference 7
Frequency reference 8
Inching frequency command f frequency ( t
Note: 1. Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if the frequency is 100 Hz or over.
2. Frequency reference 1 is enabled with n03 for frequency reference selection set to 1. (Remote mode)
3. Frequency references 1 to 8 are enabled by setting multistep speed references 1, 2, and 3 in n36 to n39 for multi-function input. Refer to the following table for the relationship between multi-step speed references 1 to 3 and frequency references 1 to 8.
Multi-step speed reference 2
OFF
Multi-step speed reference 3
OFF
Frequency reference
Frequency reference 1
Frequency reference 2
Frequency reference 3
Frequency reference 4
Frequency reference 5
Frequency reference 6
Frequency reference 7
Frequency reference 8
Multi-step speed reference 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
ON
ON
0.0
0.0
0.0
0.0
0.0
6.0
Default settings
6.0
0.0
0.0
Note: 1. “ON” and “OFF” represent “input ON” and “input OFF,” respectively.
2. Inching frequency commands take precedence over multistep speed references.
15
Function of Each Parameter
Frequency Reference Upper and Lower Limit
Settings (n30 and n31)
Set the upper and lower frequency reference limits in percentage based on the maximum frequency as 100%.
Value Name n30
Setting range
0 to 110
Unit of setting
1%
Default settings
100 n31
Frequency Reference
Upper Limit
Frequency Reference
Lower Limit
0 to 110 1% 0
Note: If n31 is set to a value less than the minimum output frequency (FMIN) (n14), the Inverter will have no output when a frequency reference less than the minimum output frequency input is ON.
Rated Motor Current Setting (n32)
Set the rated motor current as the reference value for motor overload detection (OL1).
Note: 1. Setting 0.0 disables the motor overload detection (OL1) function.
2. The rated motor current value is factory-set for each Inverter according to the maximum applicable motor capacity.
Value n32
Name Setting range
Rated Motor Current 0.0% to 120% (A) of rated output current of Inverter
Unit of setting
0.1 A
Default settings
Varies with the capacity.
Motor Protection Characteristic Selection (n33)
Set the motor overload detection (OL1) for the electronic thermal characteristics of the motor.
1
2
0
Value Description
Protection characteristics for general-purpose induction motors
Protection characteristics for Inverter-dedicated motors
No protection
Note: When connecting multiple motors to one Inverter, set 2
(equivalent to n32 = 0.0). In addition, take overload prevention measures by mounting a thermal relay in each motor, for example.
Motor Protective Time Setting (n34)
Set the electronic thermal characteristics of the motor to be connected in 1-minute increments.
Value Name Setting range
1 to 60
Unit of setting
1 min
Default settings
8 n34 Motor Protective Time
Setting
Note: 1. The default setting does not need any changes in normal operation.
2. To set the parameter according to the characteristics of the motor, confirm the thermal time constant with the motor manufacturer and set the parameter with some margin. In other words, set the value a little shorter than the thermal time constant.
3. To detect motor overloading more quickly, reduce the set value, provided that it does not cause any application problems.
Cooling Fan Operation Function Selection (n35)
This parameter is used to operate the cooling fan of the Inverter while the Inverter is turned on or only while the Inverter is in operation.
0
Value
1
Description
The fan rotates only while the RUN command is input and for 1 minute after the Inverter stops operating.
The fan rotates while the Inverter is turned ON.
Note: 1. This parameter is available only if the Inverter incorporates a cooling fan.
2. If the operation frequency of the Inverter is low, the life of the fan can be prolonged by setting the parameter to 0.
Multi-function Input Selection (n36 to n39)
Select the functions of multi-function input terminals S2 to S5.
Value Name n36 n37 n38 n39
Multi-function Input 1
(S2)
Multi-function Input 2
(S3)
Multi-function Input 3
(S4)
Multi-function Input 4
(S5)
Setting range
2 to 8, 10 to
22
0, 2 to 8, 10 to 22
2 to 8, 10 to
22
2 to 8, 10 to
22, 34
1
Unit of setting
1
1
1
2
Default settings
5
3
6
3
4
5
Value
0
2
6
7
8
10
11
12
13
14
Function
Forward/Reverse rotation command
Reverse/Stop
External fault (NO)
External fault (NC)
Fault reset
Description
3-wire sequence (to be set in n37 only)
This setting overrides the n36 setting.
S1: RUN input (RUN when ON)
S2: STOP input
(STOP when OFF)
S3: Forward/Reverse rotation command
(ON: Reverse)
Reverse rotation command (2-wire sequence) (ON: Reverse)
ON: External fault
OFF: External fault
ON: Fault reset
Note Disabled while RUN command is input
Signals to select frequency references 1 to Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
Inching frequency command
Acceleration/Deceleration time selection
External base block command (NO)
External base block command (NC)
Search command
(Searching starts from maximum frequency)
ON: Inching frequency command
ON: Acceleration/deceleration time 2
ON: Output shut OFF (while motor coasting to a stop and “bb” flashing)
OFF: Output shut OFF (with motor free running and “bb” flashing)
ON: Speed search (Searching starts from n09)
16
Function of Each Parameter
Value
15
16
17
19
20
Function
Search command
(Searching starts from preset frequency)
Acceleration/Deceleration-prohibit command
Local or remote selection
Emergency stop fault (NO)
Emergency stop alarm (NO)
Description
ON: Speed search (Searching starts from the frequency specified by n03.)
ON: Acceleration/Deceleration is on hold
ON: Local mode (operated with the Digital
Operator)
The Inverter stops according to the setting in n04 for interruption mode selection when the emergency stop input turns ON.
NO Emergenc stop ith the con tact closed.
NC: Emergency stop with the con-
21 Emergency stop fault (NC)
Note Fault: Fault output is ON and reset with RESET input. Alarm output is
22 Emergency stop alarm (NC)
34 Up or down command
Note “STP” is displayed (lit with fault input ON and flashes with alarm input ON)
Up or down command (set in n39 only)
This setting overrides the n38 setting.
S4: Up command
S5: Down command
Multi-function Output Selection (n40)
Select the functions of multi-function output terminals.
Value Name Setting range
Unit of setting n40 Multi-function Output (MA/
MB and MC)
0 to 7, 10 to
17
1
Default settings
1
0
1
2
3
4
5
6
7
Value
(
Function
Fault output
Operation in progress
Frequency detection
Idling
Frequency detection 1
Frequency detection 2
Overtorque being monitored
(NO-contact output)
Overtorque being monitored
(NC-contact output)
)
ON: Fault output
Description
ON: Operation in progress
ON: Frequency detection
ON: Idling
ON: Output frequency y
frequency detection level (n58)
ON: Output frequency x frequency detection level (n58)
Output if any of the following parameter conditions is satisfied.
•
Overtorque detection function selection (n59)
• Overtorque detection level (n60)
•
Overtorque detection time (n61)
Note NO contact: ON with overtorque being detected; NC contact: OFF with overtorque being detected
--8
9
10
11
12
13
14
Value
Alarm output
Base block in progress
RUN mode
Inverter ready
Fault retry
Function
ON: Alarm being detected (Nonfatal error)
ON: Base block in progress
ON: Local mode
ON: Inverter ready to operate
ON: Fault retry
Description
15
16
17
UV in progress ON: Undervoltage being monitored (main circuit undervoltage UV or UV1 detected)
ON: Rotating in reverse direction Rotating in reverse direction
Speed search in progress
ON: Speed search in progress
Note: Use “operation in progress” or “frequency detection 1/2” for the timing of the external brake.
Gain and Bias Settings (n41 and n42)
Set the input characteristics of analog frequency references in n41 (for the frequency reference gain) and n42 (for the frequency reference bias).
Set the frequency of maximum analog input (10 V or 20 mA) in n41 as percentage based on the maximum frequency as 100%.
Set the frequency of minimum analog input (0 V, 0 mA, or 4 mA) in n42 as percentage based on the maximum frequency as
100%.
Value n41
Name Setting range
0 to 255
Unit of setting
1%
Default settings
100 n42
Frequency Reference
Gain
Frequency Reference
Bias
–99 to 99 1% 0
Analog Frequency Reference Filter Time Setting
(n43)
The digital filter with a first-order lag can be set for analog frequency references to be input.
Value n43
Name
Analog Frequency Reference Filter Time
Setting range
0.00 to 2.00
Unit of setting
0.01 s
Default settings
0.10
Analog Monitor Output Setting (n44)
Set a monitored item for analog monitor output.
0
1
Value Description
Output frequency (Reference: 10 V at max. frequency)
Output current (Reference: 10 V with rated output current)
Note: The values in parentheses are applicable when n45 is set to 1.00.
Analog Monitor Output Gain Setting (n45)
Set the output characteristics of analog monitor output.
Value Name n45 Analog Monitor Output
Gain
Setting range
0.00 to 2.00
Unit of setting
0.01
Default settings
1.00
17
Function of Each Parameter
Carrier Frequency Selection (n46)
Set the carrier frequency.
1
2
3
4
7
Value
8
9
Description
2.5 kHz
5.0 kHz
7.5 kHz
10.0 kHz
2.5 kHz (12 × ): 12 times as high as output frequency (between 1.0
and 2.5 kHz)
2.5 kHz (24
×
): 24 times as high as output frequency (between 1.0
and 2.5 kHz)
2.5 kHz (36
×
): 36 times as high as output frequency (between 1.0
and 2.5 kHz)
Note: Normally, the factory setting need not be changed.
Momentary Power Interruption Compensation
(n47)
The parameter specifies the processing that will be performed when a momentary power interruption occurs.
0
Value
1
2
Description
Disabled.
The Inverter will continue operating if power is restored within 0.5
s.
The Inverter will restart when power is restored.
Fault Retry (n48)
Set the number of times the Inverter is to be automatically reset and restarted when the Inverter has an overvoltage fault, overcurrent fault, or ground fault.
Value n48
Name
Fault Retry
Setting range
0 to 10 1
Unit of setting
Default settings
0
Frequency Jump Function (n49 to n51)
Set the frequency jump function.
Value n49 n50
Name
Jump Frequency 1
Jump Frequency 2
Setting range
0.0 to 400
0.0 to 400
Unit of setting
0.1 Hz
(see note
1)
0.1 Hz
(see note
1)
0.1 Hz
Default settings
0.0
0.0
n51 Jump Width 0.0 to 25.5
0.0
Note: 1. Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1 Hz-increments if the frequency is 100 Hz or greater.
2. Make settings so that n49 y
n50.
Output frequency
FMIN
(n14)
Output frequency n50 n51 n49
Deceleration time is controlled to prevent overvoltage.
Reference frequency
DC Control Functions (n52 to n54)
Used to impose DC on the induction motor for braking control.
Value n52 n53 n54
Name
DC Control Current
Interruption DC Control
Time
Startup DC Control Time
Setting range
0 to 100
0.0 to 25.5
0.0 to 25.5
Unit of setting
1%
0.1 s
0.1 s
Default settings
50
0.5
0.0
DC Control Current:
Set this value in percentage based on the rated output current of the Inverter as 100%.
Output frequency n54 n53
Time
Stall Prevention during Deceleration (n55)
Select a function to change the deceleration time of the motor automatically so that there will be no overvoltage imposed on the motor during deceleration.
0
1
Value Description
Stall prevention during deceleration
No stall prevention during deceleration
Time
Deceleration time (Set value)
18
Function of Each Parameter
Stall Prevention Level during Acceleration (n56)
Set the operation level of a function to stop the acceleration of the motor automatically for stall prevention during acceleration.
Set this value in percentage based on the rated output current of the Inverter as 100%.
Value Name n56 Stall Prevention Level during Acceleration
Setting range
30 to 200
Unit of setting
1%
Default settings
170
Stall Prevention during Acceleration
Output current
Output frequency n56
Time
The output frequency is controlled so that the
Inverter will not stall.
Time
Stall Prevention Level during Operation (n57)
Select the operation level of a function to reduce the output frequency of the Inverter automatically for stall prevention during operation. Set this value in percentage based on the rated output current of the Inverter as 100%.
Value Name n57 Stall Prevention Level during Operation
Setting range
30 to 200
Unit of setting
1%
Default settings
160
Overtorque Detection Function Selection
(n59 to n61)
Set n59 to enable or disable overtorque detection and select the processing to be performed after overtorque detection.
0
1
Value
2
3
4
Description
Inverter does not monitor overtorque.
Inverter monitors overtorque only when speed is matched.
It continues operation (issues warning) even after overtorque is detected.
Inverter monitors overtorque only when speed is matched.
It discontinues operation (through protective function) when overtorque is detected.
Inverter always monitors overtorque during operation.
It continues operation (issues warning) even after overtorque is detected.
Inverter always monitors overtorque during operation.
It discontinues operation (through protective function) when overtorque is detected.
Set the overtorque detection level in n60 and the overtorque detection time in n61.
Value Name Setting range
Unit of setting
Default settings
160 n60 n61
Overtorque Detection
Level
Overtorque Detection
Time
30 to 200
0.1 to 10.0
1%
0.1 s 0.1
Note: 1. In n60, set the overtorque detection level in percentage based on the rated output current of the Inverter as 100%.
2. In n61, set the overtorque detection time in 0.1-s increments.
Overtorque Detection
Output current
See note.
n60
Stall Prevention during Operation
Output current n57
Time
Time n61
Overtorque detection
(NO)
Time
Note: Overtorque detection will be canceled if the output current decreases from the detection level by approximately 5% of the Inverter rated current.
Output frequency
The output frequency is controlled so that the
Inverter will not stall.
Time
Frequency Detection Level (n58)
Set the frequency to be detected.
Note: When frequency detection 1 and 2 are to be output, n40
(multi-function output) must be set.
Value n58
Name
Frequency Detection
Level
Setting range
0.0 to 400
Unit of setting
0.1 Hz
Default settings
0.0
19
20
Function of Each Parameter
UP/DOWN Command Frequency Memory
Selection (n62)
Select whether to store the frequency reference adjusted with the UP/DOWN function.
0
1
Value Description
The frequency on hold is not retained.
The frequency on hold for 5 s or more is retained.
The UP/DOWN function uses UP and DOWN commands to change frequency references.
When using the UP/DOWN function, set multi-function input 4
(n39) to 34 (UP or DOWN command). The terminals for multifunction input 3 (S4) and multi-function input 4 (S5) will be set to function in the following way:
Multiple-function input 3 (S4): UP command
Multiple-function input 4 (S5): DOWN command
Use n62 (UP/DOWN command frequency memory) to set whether the frequency reference on hold is stored or not when an UP or DOWN command is sent to the multi-function input terminals.
If n62 is set to 1, the output frequency held by the UP/DOWN function for 5 s or more will be stored in the memory. This value will be stored in memory even if power is interrupted. When a
RESET command is input, operation will start with this value as the frequency.
If n62 is set to 0, the frequency will be cleared. If parameter initialization is performed (i.e.: n01 is set to 8 or 9), the stored frequency will be initialized.
Note: If the UP/DOWN function is used in remote mode, frequency references can only be given with UP/DOWN commands and inching commands. Multi-step speed references will be invalid.
Operation of UP/DOWN Function
RUN command
(Forward rotation)
UP command (S4)
Time
Time
DOWN command
(S5)
Output frequency
Upper limit
Time
Lower limit
Status
Frequency detection
Status U: UP (acceleration)
D: DOWN (deceleration)
H: Hold
U1: Frequency acceleration restricted by upper limit.
D1: Frequency deceleration restricted by lower limit.
Time
Time
Function of Each Parameter
Torque Compensation Gain (n63)
Set the gain of the torque compensation function.
Note: Normally, the factory setting need not be changed.
Value n63
Name
Torque Compensation
Gain
Setting range
0.0 to 2.5
Unit of setting
0.1
Default settings
1.0
Slip Compensation Functions (n64 to n67)
In n64, set the rated slip value of the motor in use.
In n65, set the no-load current of the motor in use based on the rated motor current as 100%.
In n66, set the gain of the slip compensation function.
In n67, set the response speed of the slip compensation function.
Value n64 n65 n66 n67
Name
Motor Rated Slip
Motor No-load Current
Slip Compensation
Gain
Slip Compensation
Time Constant
Setting range
0.0 to 20.0
0 to 99
0.0 to 2.5
0.0 to 25.5
Unit of setting
0.1 Hz
1%
Default settings
Varies
0.1
capacity.
0.0
0.1 s 2.0
Note: If 0.0 is set for n66, the slip compensation function will be disabled.
21
Specifications
Specifications
Model 3G3JV-
Power Rated voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Input power supply capacity
(kVA) (see note 1)
Heat radiation (W) (see note 2)
Weight (kg)
Cooling method
A2001 A2004
3-phase 200 to 230 V AC at 50/60 Hz
–15% to 10%
± 5%
0.4
A2002
0.9
13.0
0.5
Natural cooling
18.0
0.5
1.6
28.1
0.8
A2007 A2015
2.7
4.3
45.1
0.9
Cooling fan
72.8
1.3
A2022
5.9
94.8
1.5
A2037
9.3
149.1
2.1
Model 3G3JV-
Power Rated voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Input power supply capacity
(kVA) (see note 1)
Heat radiation (W) (see note 2)
Weight (kg)
Cooling method
AB001 AB002 AB004
Single-phase 200 to 240 V AC at 50/60 Hz
–15% to 10%
± 5%
AB007
0.5
0.9
14.1
0.5
Natural cooling
20.0
0.5
1.6
31.9
0.9
2.7
51.4
1.5
AB015
4.3
---
82.8
1.5
Cooling fan
---
---
---
---
---
---
---
Note: 1. The power supply capacity, is the capacity when the Inverter is operating at its rated output. The value will vary with the impedance at the input power supply side. (Because the power factor of the input power supply changes, the power factor will improve if an AC reactor is inserted.) The ratio with the rated current of the motor used and the rated output current of the Inverter will vary.
2. The “heat radiation” is the power consumed in the Inverter when it is operating at its rated output.
Max. applicable motor capacity (kW) ifi ti
Rated output capacity (kW)
Rated output current (A)
Rated output voltage (V) t i ti
Max. output frequency
Harmonic-current countermeasures
Control method
Carrier frequency
Frequency control range
Frequency precision (temperature characteristics)
Frequency setting resolution
Protective f ti
Output frequency resolution
Overload capacity
External frequency set signal
Acceleration/deceleration time
Braking torque
Voltage/frequency characteristics
Motor protection
Instantaneous overcurrent protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power interruption compensation (selection)
Cooling fin overheating
Grounding protection
Charge indicator (RUN indicator)
0.1
0.2
0.4
0.75
1.5
0.3
0.8
0.6
1.6
1.1
3.0
1.9
5.0
3-phase 200 to 230 V AC (according to the input voltage)
3.0
8.0
2.2
4.2
11.0
3.7
6.7
17.5
400 Hz parameter setting
DC reactor (option) connection possible
Sine wave PWM (V/f control)
2.5 to 10.0 kHz (in vector control)
0.1 to 400 Hz
Digital commands: ± 0.01% (–10 ° C to 50 ° C)
Analog commands:
±
0.5% (25
°
C
±
10
°
C)
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
0.01 Hz (calculated resolution)
150% of rated output current for 1 min
Selectable with FREQ adjuster: 0 to 10 V DC (20 k Ω ), 4 to 20 mA (250 Ω ), and 0 to 20 mA
(250
Ω
)
0.0 to 999 s (Independent acceleration and deceleration time settings)
Approx. 20%
Set a user V/f pattern
Protection by electronic thermal
Stops at approx. 250% of rated output current
Stops in 1 min at approximately 150% of rated output current
Stops when main-circuit DC voltage is approximately 410 V
Stops when main-circuit DC voltage is approximately 200 V (160 V for single-phase 200-V AC model)
Stops for 15 ms or more. By setting the Inverter to momentary power interruption mode, operation can be continued if power is restored within approximately 0.5 s.
Detects at 110
°
C
±
10
°
C
Protection at rated output current level
Lit when the main circuit DC voltage is approximately 50 V or less.
22
Environment Location
Ambient temperature
Ambient humidity
Ambient temperature
Altitude
Insulation resistance
Vibration resistance
Degree of protection
Specifications
Indoors (with no corrosive gas, oil spray, or metallic dust)
Operating: –10
°
C to 50
°
C
Operating: 95% max. (with no condensation)
–20 ° C to 60 ° C
1,000 m max.
5 M
Ω
min. (Do not carry out any insulation resistance or withstand voltage tests)
9.8 m/s
2.0 m/s
2
2
max. between 10 to 20 Hz
max. between 20 and 50 Hz
Panel-mounting models: Conforms to IP20
23
24
Specifications
Model 3G3JV-
Power Rated voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Input power supply capacity
(kVA) (see note 1)
Heat radiation (W) (see note 2)
Weight (kg)
Cooling method
A4002 A4004 A4007
3-phase 380 to 460 V AC at 50/60 Hz
–15% to 10%
± 5%
1.3
1.9
23.1
1.0
Natural cooling
30.1
1.1
3.6
54.9
1.5
5.1
A4015
75.7
1.5
Cooling fan
5.9
A4022
83.0
1.5
9.1
A4037
117.9
2.1
Note: 1. The power supply capacity, is the capacity when the Inverter is operating at its rated output. The value will vary with the impedance at the input power supply side. (Because the power factor of the input power supply changes, the power factor will improve if an AC reactor is inserted.) The ratio with the rated current of the motor used and the rated output current of the Inverter will vary.
2. The “heat radiation” is the power consumed in the Inverter when it is operating at its rated output.
Max. applicable motor capacity (kW) ifi ti
Rated output capacity (kW)
Rated output current (A) t i ti
Rated output voltage (V)
Max. output frequency
Harmonic-current countermeasures
Control method
Carrier frequency
Frequency control range
Frequency precision (temperature characteristics)
Frequency setting resolution
Protective f ti
Environment
Output frequency resolution
Overload capacity
External frequency set signal
Acceleration/deceleration time
Braking torque
Voltage/frequency characteristics
Motor protection
Instantaneous overcurrent protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power interruption compensation (selection)
Cooling fin overheating
Grounding protection
Charge indicator (RUN indicator)
Location
Ambient temperature
Ambient humidity
Ambient temperature
Altitude
Insulation resistance
Vibration resistance
Degree of protection
0.2
0.9
1.2
0.4
1.4
1.8
0.75
2.6
3.4
1.5
3.7
4.8
2.2
4.2
5.5
3.7
6.6
8.6
3-phase 380 to 460 V AC (according to the input voltage)
400 Hz parameter setting
DC reactor (option) connection possible
Sine wave PWM (V/f control)
2.5 to 10.0 kHz (in vector control)
0.1 to 400 Hz
Digital commands: ± 0.01% (–10 ° C to 50 ° C)
Analog commands:
±
0.5% (25
°
C
±
10
°
C)
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
0.01 Hz (calculated resolution)
150% of rated output current for 1 min
Selectable with FREQ adjuster: 0 to 10 V DC (20 k
Ω
), 4 to 20 mA (250
Ω
), and 0 to 20 mA
(250 Ω )
0.0 to 999 s (Independent acceleration and deceleration time settings)
Approx. 20%
Set a user V/f pattern
Protection by electronic thermal
Stops at approx. 250% of rated output current
Stops in 1 min at approximately 150% of rated output current
Stops when main-circuit DC voltage is approximately 820 V
Stops when main-circuit DC voltage is approximately 400 V
Stops for 15 ms or more. By setting the Inverter to momentary power interruption mode, operation can be continued if power is restored within approximately 0.5 s.
Detects at 110 ° C ± 10 ° C
Protection at rated output current level
Lit when the main circuit DC voltage is approximately 50 V or less.
Indoors (with no corrosive gas, oil spray, or metallic dust)
Operating: –10
°
C to 50
°
C
Operating: 95% max. (with no condensation)
–20 ° C to 60 ° C
1,000 m max.
5 M
Ω
min. (Do not carry out any insulation resistance or withstand voltage tests)
9.8 m/s
2.0 m/s
2
2
max. between 10 to 20 Hz
max. between 20 and 50 Hz
Panel-mounting models: Conforms to IP20
Specifications
Terminal Block
Position of Terminal Block
Ground terminal
Main circuit input terminals
Main circuit output terminals
Arrangement of Control Circuit Terminals
Control circuit terminals
Ground terminal
Note: This illustration shows the terminal block with the front cover removed.
Main Circuit Terminals
Symbol
R/L1
Name
Power supply input
S/L2
T/L3
U/T1 Motor output terminals
V/T2
W/T3
+1
Description
3G3JV-A2 j : 3-phase 200 to 230 V AC
3G3JV AB j Si l h 200 t 240 V AC
3G3JV-A4 j : 3-phase 380 to 460 V AC
Note Connect single-phase input to terminals R/L1 and S/L2.
3-phase power supply output for driving motors.
3G3JV-A2 j : 3-phase 200 to 230 V AC
3G3JV-AB j : 3-phase 200 to 240 V AC
3G3JV-A4 j : 3-phase 380 to 460 V AC
Note The maximum output voltage corresponds to the input power supply voltage for the Inverter.
Connect the DC reactor for suppressing harmonics to terminals +1 and +2.
+2
Connection terminals +1 and +2: terminals and –.
(Terminal +1 is a positive terminal.)
–
DC power supply input terminals
Ground terminal Be sure to ground the terminal under the following conditions.
3G3JV-A2 j : Ground at a resistance of 100 Ω or less.
3G3JV-AB j : Ground at a resistance of 100 Ω or less.
3G3JV-A4 j : Ground at a resistance of 10 Ω or less. Connect to a neutral point on the power supply to conform to EC Directives.
Note Be sure to connect the ground terminal directly to the motor frame ground.
25
26
Specifications
Control Circuit Terminals
Symbol
S1
S2
Output
S3
S4
S5
SC
FS
FR
FC
MA
MB
MC
AM
AC
Name
Forward/Stop
Multi-function input 1 (S2)
Multi-function input 2 (S3)
Multi-function input 3 (S4)
Multi-function input 4 (S5)
Sequence input common
Frequency reference power supply
Function Signal level
Forward at ON. Stops at OFF.
Photocoupler
Set by parameter n36 (Re-
8 A 24 V DC ( verse/Stop)
Set by parameter n37 (Fault reset)
Set by parameter n38 (External fault: Normally open)
Set by parameter n39 (Multistep reference 1)
Common for S1 through S5
DC power supply for frequency reference use
20 mA at 12 V DC
0 to 10 V DC
( pu peda ce 0 Ω ) )
Frequency reference input
Multi-function contact output
(Normally open)
Input terminal for frequency reference use
Frequency reference common Common for frequency reference use
Set by parameter n40 (during
Multi-function contact output
(Normally closed)
Multi-function contact output common
Analog monitor output
Common for MA and MB use
Analog monitor output common
Set by parameter n44 (Output frequency)
Common for AM use
Relay output
2 mA max. at 0 to 10 V DC
2)
Note: 1. Functions in parentheses are default settings.
2. The input method is set to NPN by default, so use the GND common for wiring. An external power supply is not required.
When a power supply is used and a common on the plus side is used for wiring, set SW7 to PNP and use a 24-V DC ( ± 10%) power supply.
Dimensions
Dimensions
3G3JV-A2001 to 3G3JV-A2007 (0.1 to 0.75 kW)
3-phase 200-V AC Input
3G3JV-AB001 to 3G3JV-AB004 (0.1 to 0.4 kW)
Single-phase 200-V AC Input
3G3JV-A2015 to 3G3JV-A2022 (1.5 to 2.2 kW)
3-phase 200-V AC Input
3G3JV-AB007 to 3G3JV-AB015 (0.75 to 1.5 kW)
Single-phase 200-V AC Input
3G3JV-A4002 to 3G3JV-A4022 (0.2 to 2.2 kW)
3-phase 400-V AC Input
Two, 5-dia. holes t
Rated voltage
A2001
A2002
A2004
A2007
Single-phase 200 V AC AB001
AB002
AB004
Model Dimensions
(mm)
D
70
70
3
3 t
102 5
122 5
70
70
112 5
3
3
Weight (kg)
Approx. 0.5
Approx. 0.5
Approx. 0.8
Approx. 0.9
Approx. 0.5
Approx. 0.5
Approx. 0.9
Rated voltage
A2015
A2022
Single-phase 200 V AC AB007
AB015
A4002
A4004
A4007
A4015
A4022
Model
154
81
99
129
154
154
Dimensions
(mm)
D
129
154
129
Weight (kg)
Approx. 1.3
Approx. 1.5
Approx. 1.5
Approx. 1.5
Approx. 1.0
Approx. 1.1
Approx. 1.5
Approx. 1.5
Approx. 1.5
3G3JV-A2037 (3.7 kW) 3-phase 200-V AC Input
3G3JV-A4037 (3.7 kW) 3-phase 400-V AC Input
Rated voltage
3-phase 200 V AC
3-phase 400 V AC
Model
A2037
A4037
Dimensions
(mm)
D
161
161
Weight (kg)
Approx. 2.1
Approx. 2.1
27
Standard Connections
Standard Connections
Noise Filter
DC reactor
(optional)
3-phase 200 V AC
Single-phase 200 V AC (see note 1)
3-phase 400 V AC
Forward/Stop
Multi-function input 1 (S2)
Multi-function input 2 (S3)
Multi-function input 3 (S4)
Multi-function input 4 (S5)
FREQ adjuster
(2 k Ω , 1/4 W min.)
Sequence input common
Frequency reference power supply
20 mA at +12 V
Frequency reference input
Frequency reference common
Multi-function contact output
NO
NC
Common
Analog monitor output
Analog monitor output common
Note: 1. Connect single-phase 200 V AC to terminals R/L1 and S/L2 of the 3G3JV-AB j .
2. The braking resistor cannot be connected because no braking transistor is incorporated.
Input Method Selection
Switches SW7 and SW8, both of which are located above the control circuit terminals, are used for input method selection.
Remove the front cover and optional cover to use these switches.
Selector
Control circuit terminal block
Sequence Input Method Selection
By using SW7, NPN or PNP input can be selected as shown below.
(Factory setting)
S1 to 5
24 V DC
( ± 10%)
S1 to 5
24 V
Frequency Reference Input Method Selection
By using SW8, frequency reference voltage or current input can be selected.
Parameter settings are required together with the selection of the frequency reference input method.
SW8 setting Frequency reference input method
Voltage input
Current input
V (OFF)
I (ON)
Frequency reference selection (parameter n03)
Set value 2
Set value 3 or 4
28
Protective and Diagnostic
Functions
Fault Detection (Fatal Error)
The Inverter will detect the following faults if the Inverter or motor burns or the internal circuitry of the Inverter malfunctions. When the
Inverter detects a fault, the fault code will be displayed on the Digital Operator, the fault contact output will operate, and the Inverter output will be shut off causing the motor to coast to a stop. The stopping method can be selected for some faults, and the selected stopping method will be used with these faults. If a fault has occurred, refer to the following table to identify and correct the cause of the fault. Use one of the following methods to reset the fault after restarting the Inverter. If the operation command is being input, however, the reset signal will be ignored. Therefore, be sure to reset the fault with the operation command turned off.
• Turn on the fault reset signal. A multi-function input (n36 to n39) must be set to 5 (Fault Reset).
•
Press the STOP/RESET Key on the Digital Operator.
• Turn the main circuit power supply off and then on again.
Fault Displays and Processing
Fault display
%c
%U uU1
%h
Fault name and meaning
Overcurrent (OC)
The Inverter output current is as high as or higher than 200% of the rated output current.
Overvoltage (OV)
The main circuit DC voltage has reached the overvoltage detection level
(200-V models: 410 V DC min.; 400-V models: 820 V DC min.).
Main circuit undervoltage (UV1)
The main circuit DC voltage has reached the undervoltage detection level (200 V DC for the 3G3JV-A2 j
,
160 V DC for the 3G3JV-AB j
, and 400
V DC for the 3G3JV-A4 j ).
Radiation fin overheated (OH)
The temperature of the radiation fins of the Inverter has reached 110 _ C ±
10 _ C.
Probable cause and remedy
• A short-circuit or ground fault has occurred and at the Inverter output.
→ Check and correct the motor power cable.
• The V/f setting is incorrect.
→
Reduce the V/f set voltage.
•
The motor capacity is too large for the Inverter.
→ Reduce the motor capacity to the maximum permissible motor capacity.
• The magnetic contactor on the output side of the Inverter has been opened and closed.
→
Rearrange the sequence so that the magnetic contactor will not open or close while the Inverter has current output.
• The output circuit of the Inverter is damaged.
→
Replace the Inverter.
• The deceleration time is too short.
→
Increase the deceleration time.
•
The power supply voltage is too high.
→ Decrease the voltage so it will be within specifications.
• There is excessive regenerative energy due to overshooting at the time of acceleration.
→
Suppress the overshooting as much as possible.
• Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power cable is disconnected.
→
Check the above and take necessary countermeasures.
•
Incorrect power supply voltage
→ Make sure that the power supply voltage is within specifications.
• Momentary power interruption has occurred.
→ Use the momentary power interruption compensation (Set n47 so that the Inverter restarts after power is restored)
→ Improve the power supply.
• The internal circuitry of the Inverter is damaged.
→
Change the Inverter.
• The ambient temperature is too high.
→
Ventilate the Inverter or install a cooling unit.
•
The load is excessive.
→ Reduce the load.
→ Decrease the Inverter capacity.
• The V/f setting is incorrect.
→
Reduce the V/f set voltage.
•
The acceleration/deceleration time is too short.
→
Increase the acceleration/deceleration time.
•
The ventilation is obstructed.
→ Change the location of the Inverter to meet the installation conditions.
• The cooling fan of the Inverter does not work.
→
Replace the cooling fan.
29
Protective and Diagnostic Functions
Fault display
%l1
%l2
%l3
gf ef j f00 f01 f04 f05 f07
Fault name and meaning
Motor overload (OL1)
The electric thermal relay actuated the motor overload protective function.
Inverter overload (OL2)
The electronic thermal relay has actuated the Inverter overload protective function.
Probable cause and remedy
•
The load is excessive.
→ Reduce the load.
→ Decrease the Inverter capacity.
• The V/f setting is incorrect.
→
Reduce the V/f set voltage.
•
The value in n11 for maximum voltage frequency is low.
→ Check the motor nameplate and set n11 to the rated frequency.
• The acceleration/deceleration time is too short.
→
Increase the acceleration/deceleration time.
•
The value in n32 for rated motor current is incorrect.
→
Check the motor nameplate and set n32 to the rated current.
•
The Inverter is driving more than one motor.
→ Disable the motor overload detection function and install an electronic thermal relay for each of the motors.
The motor overload detection function is disabled by setting n32 to 0.0 or n33 to 2.
•
The motor protective time setting in n34 is short.
→ Set n34 to 8 (the default value).
• The load is excessive.
→
Reduce the load.
•
The V/f setting is incorrect.
→ Reduce the V/f set voltage.
• The acceleration/deceleration time is too short.
→
Increase the acceleration/deceleration time.
•
The Inverter capacity is insufficient.
→ Use an Inverter model with a higher capacity.
• The mechanical system is locked or has a failure.
→
Check the mechanical system and correct the cause of overtorque.
•
The parameter settings were incorrect.
→ Adjust the n60 and n61 parameters according to the mechanical system.
Increase the set values in n60 and n61.
Overtorque detection (OL3)
There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time. A fault has been detected with n59 for overtorque detection function selection set to 2 or 4.
Ground fault (GF)
The ground fault current at the output of the Inverter has exceeded the rated output current of the Inverter.
External fault j (EF j )
An external fault has been input from a multi-function input.
A multi-function input 1, 2, 3, or 4 set to
3 or 4 has operated. The EF number indicates the number of the corresponding input (S2 to S5).
Digital Operator transmission fault 1
(F00)
An initial memory fault has been detected
Digital Operator transmission fault 2
(F01)
A ROM fault has been detected.
Initial memory fault (F04)
An error in the built-in EEPROM of the
Inverter has been detected.
Analog-to-digital converter fault
(F05)
An analog-to-digital converter fault has been detected.
Digital Operator fault (F07)
An error in the built-in control circuit of the Digital Operator has been detected.
•
•
A ground fault has occurred at the Inverter output.
→
Check the connections between the Inverter and motor and reset the fault after correcting its cause.
An external fault was input from a multi-function input.
→
Remove the cause of the external fault.
•
The sequence is incorrect.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
•
The internal circuitry of the Inverter has a fault.
→ Turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
•
The internal circuitry of the Inverter has a fault.
→ Turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
•
The internal circuitry of the Inverter has a fault.
→ Initialize the Inverter with n01 set to 8 or 9 and turn the Inverter off and on.
→ Replace the Inverter if the same fault occurs again.
• The internal circuitry of the Inverter has a fault.
→
Turn the Inverter off and on.
→
Replace the Inverter if the same fault occurs again.
• The internal circuitry of the Digital Operator has a fault.
→
Turn the Digital Operator off and on.
→
Replace the Digital Operator if the same fault occurs again.
30
Protective and Diagnostic Functions
Fault display ce
Fault name and meaning
Communications time-over (CE)
Normal RS-422A/485 communications were not established within 2 s. The
Inverter will detect this error if n68
(RS-422A/485 communications time-over detection selection) is set to
0, 1, or 2.
OFF
Emergency stop (STP)
An emergency stop alarm is input to a multi-function input. (A multi-function input 1, 2, 3, or 4 set to 19 or 21 has operated.)
Power supply error
• Insufficient power supply voltage
•
Control power supply fault
• Hardware fault
Probable cause and remedy
•
A short-circuit, ground fault, or disconnection has occurred on the communications line.
→ Check and correct the line.
• The termination resistance setting is incorrect.
→
Set the termination resistance of only the Inverter located at each end of the network to ON.
•
Noise influence.
→ Do not wire the communications line along with power lines in the same conduit.
→ Use the twisted-pair shielded wire for the communications line, and ground it at the Master.
• Master’s program error.
→
Check and correct the program so that communications will be performed more than once every
2-s period.
• Communications circuit damage.
→
If the same error is detected as a result of a self-diagnostic test, change the Inverter.
• An emergency stop alarm is input to a multi-function input.
→
Remove the cause of the fault.
•
The sequence is incorrect.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
• No power supply is provided.
→
Check and correct the power supply wire and voltage.
•
Terminal screws are loosened.
→ Check and tighten the terminal screws.
• The Inverter is damaged.
→ Replace the Inverter.
Warning Detection (Nonfatal Error)
The warning detection is a type of Inverter protective function that does not operate the fault contact output and returns the Inverter to its original status once the cause of the error has been removed. The Digital Operator flashes and display the detail of the error. If a warning occurs, take appropriate countermeasures according to the table below.
Note: Some warnings or some cases stop the operation of the Inverter as described in the table.
Fault display
uU
(flashing)
%U
(flashing)
%h
(flashing)
cal
(flashing)
%l3
(flashing)
Warning name and Meaning
Main Circuit Undervoltage (UV)
The main circuit DC voltage has reached the undervoltage detection level (200 V DC for the 3G3JV-A2 j ,
160 V DC for the 3G3JV-AB j
, and 400
V DC for the 3G3JV-A4 j
).
Main Circuit Overvoltage
The main circuit DC voltage has reached the overvoltage detection level
(200-V models: 410 V DC min.; 400-V models: 820 V DC min.).
Radiation fin overheated (OH)
The temperature of the radiation fins of the Inverter has reached 110 _ C ±
10 _ C.
Communications standby (CAL)
No normal DSR message has been received during RS-422A/4895 communications.
The Inverter detects this warning only when RUN command selection (n02) is set to 2 or frequency reference selection (n03) is set to 6. Until the warning is reset, no input other than communications input will be ignored.
Overtorque detection (OL3)
There has been a current or torque the same as or greater than the setting in n60 for overtorque detection level and that in n61 for overtorque detection time. A fault has been detected with n59 for overtorque detection function selection set to 1 or 3.
Probable cause and remedy
• Power supply to the Inverter has phase loss, power input terminal screws are loose, or the power line is disconnected.
→ Check the above and take necessary countermeasures.
•
Incorrect power supply voltage
→ Make sure that the power supply voltage is within specifications.
•
The power supply voltage is too high.
→ Decrease the voltage so it will be within specifications.
• The ambient temperature is too high.
→
Ventilate the Inverter or install a cooling unit.
•
A short-circuit, ground fault, or disconnection has occurred on the communications line.
→ Check and correct the line.
• The termination resistance setting is incorrect.
→
Set the termination resistance of only the Inverter located at each end of the network to ON.
•
Master’s program error.
→ Check the start of communications and correct the program.
• Communications circuit damage.
→
If a CAL or CE error is detected as a result of a self-diagnostic test, change the Inverter.
•
The mechanical system is locked or has a failure.
→ Check the mechanical system and correct the cause of overtorque.
• The parameter settings were incorrect.
→
Adjust the n60 and n61 parameters according to the mechanical system.
Increase the set values in n60 and n61.
31
32
Protective and Diagnostic Functions
Fault display ser
(flashing)
bb
(flashing)
ef
(flashing)
(flashing) fRn
(flashing) ce
Warning name and Meaning
Sequence error (SER)
A sequence change has been input while the Inverter is in operation.
Local or remote selection is input while the Inverter is in operation.
Note The Inverter coasts to a stop.
External base block (bb)
The external base block command has been input.
Note The Inverter coasts to a stop.
Forward- and reverse-rotation input
(EF)
The forward and reverse commands are input to the control circuit terminals simultaneously for 0.5 s or more.
Note The Inverter stops according to the method set in n04.
Emergency stop (STP)
The Digital Operator stops operating.
The STOP/RESET Key on the Digital
Operator is pressed while the Inverter is operating according to the forward or reverse command through the control circuit terminals.
Note The Inverter stops according to the method set in n04.
The emergency stop alarm signal is input as multi-function input.
A multi-function input 1, 2, 3, or 4 set to
20 or 22 has been used.
Note The Inverter stops according to the method set in n04.
Cooling fan fault (FAN)
The cooling fan has been locked.
Communications time-over (CE)
Normal RS-422A/485 communications were not established within 2 s. The
Inverter will detect this error if n68
(RS-422A/485 communications time-over detection selection) is set to
0, 1, or 2.
•
A sequence error has occurred.
Probable cause and remedy
→ Check and adjust the local or remote selection sequence as multi-function input.
•
The external base block command has been input as multi-function input.
→ Remove the cause of external base block input.
• The sequence is incorrect.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
•
A sequence error has occurred.
→ Check and adjust the local or remote selection sequence.
• The parameter setting was incorrect.
→
Turn off the forward or reverse command once, check that the n06 parameter setting for
STOP/RESET Key function selection, and restart the Inverter.
•
An emergency stop alarm is input to a multi-function input.
→ Remove the cause of the fault.
• The sequence is incorrect.
→ Check and change the external fault input sequence including the input timing and NO or NC contact.
• The cooling fan wiring has a fault.
→
Turn off the Inverter, dismount the fan, and check and repair the wiring.
•
The cooling fan in not in good condition.
→ Check and remove the foreign material or dust on the fan.
• The cooling fan is beyond repair.
→ Replace the fan.
•
A short-circuit, ground fault, or disconnection has occurred on the communications line.
→ Check and correct the line.
• The termination resistance setting is incorrect.
→
Set the termination resistance of only the Inverter located at each end of the network to ON.
•
Noise influence.
→ Do not wire the communications line along with power lines in the same conduit.
→ Use the twisted-pair shielded wire for the communications line, and ground it at the Master.
• Master’s program error.
→ Check and correct the program so that communications will be performed more than once every
2-s period.
• Communications circuit damage.
→
If the same error is detected as a result of a self-diagnostic test, change the Inverter.
Protective and Diagnostic Functions
Fault display
%p1
(flashing)
%p2
(flashing)
Warning name and Meaning
Operation error (OP j
)
( g )
%p3
(flashing)
%p4
(flashing)
%p5
(flashing)
Probable cause and remedy
•
The values in n36 through n39 for multi-function inputs 1 through 4 have been duplicated.
→ Check and correct the values.
• The V/f pattern settings do not satisfy the following condition.
n14 x n12 t n11 x n09
→
Check and correct the set value.
•
The rated motor current set in n32 exceeds
150% of the rated output current of the Inverter.
→ Check and correct the value.
• The frequency reference upper limit set in n30 and the frequency reference lower limit set in n31 do not satisfy the following condition.
n30 y
n31
→ Check and correct the set values.
• The jump frequencies set n49, n50 do not satisfy the following condition.
n49 y
n50
→ Check and correct the set values.
33
Options
Overview of Options
Power Supply
3G3JV-A2 j
: 3-phase 200 V AC
3G3JV-AB j : single-phase 200 V AC (connect to R/L1, S/L2)
3G3JV-A4 j : 3-phase 400 V AC
Molded case circuit breaker or leakage breaker
Supplied by the customer
Suppresses harmonic current generated from the
Inverter and improves the power factor of the
Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much larger than that of the Inverter.
Electromagnetic contactor Supplied by the customer
Recommended Option
AC Reactor
3G3IV-PUZBAB j
Recommended Option
Input Noise Filter
Eliminates noise in the power line connected to the Inverter and suppresses noise leaking from the Inverter to the power line. There are 2 types available: the EMC-conforming Input Noise Filter and the
Simple Input Noise Filter.
Simple Input Noise Filter
3G3EV-PLNFD j
R/L1 S/L2 T/L3
Dedicated Option
DC Reactor
3G3HV-PUZDAB j
+1
+2
Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter.
Dedicated Option
DIN Track Mounting Bracket
3G3IV-PEZZ08122 j
An adapter making it possible to easily mount the Inverter to DIN tracks.
34
Separately Mounted Option
Process Meter
K3MA-J
U/T1 V/T2 W/T3
Mounted Option
Fan Unit
3G3IV-PFAN j
Replacement for the existing cooling fan of the Inverter.
Dedicated Option
Adapter Panel
3G3JV-PSI232J (permanent)
3G3JV-PSI232JC (removable)
+
Digital Operator
3G3IV-PJVOP146
3G3IV-PJVOP140+
3G3IV-PEZZ08386 (Digital Operator Case)
+
Digital Operator Connection Cable
3G3IV-PCN126 (1 m)
3G3IV-PCN326 (3 m)
An Adapter Panel is required as an interface to connect a Digital Operator (3G3IV-PJVOP140 or 3G3IV-PJVOP146) to the 3G3JV Inverter.
There are two models of Adapter Panel available. The
3G3JV-PSI232J is permanently installed and cannot be removed and the 3G3JV-PSI232JC for copying parameters is installed so that it can be removed.
Recommended Option
Output Noise Filter
3G3IV-PLF j
Connect this Filter to the output side of the Inverter to suppress the noise generated by the Inverter from being transmitted to the output line.
3-phase Inductive Motor
Dedicated Option
RS-422/485 Communications Unit
3G3JV-PSI485J
The RS-422/485 Communications Unit (3G3JV-
PSI485J) functions as an interface for RS-422/485 general-purpose communications. The communications protocol conforms to MODBUS (same protocol as 3G3MV and 3G3RV Inverters). Communications can be used for Inverter control inputs, frequency references, monitoring Inverter operating status, and reading/writing parameter settings.
Options
Mounted Option
Name Model Description Reference page
36 Fan Unit 3G3IV-PFAN j Replacement for the existing cooling fan of the Inverter.
Replace the cooling fan if it has reached the end of its service life or a warning of cooling fan failure (FAN) is indicated.
Separately Mounted Option
Name Model
AC Reactor (Yaskawa
Electric)
EMC-conforming Input
Noise Filter (Rasmi)
Simple Input Noise Filter
(Yaskawa Electric)
Output Noise Filter (Tokin)
3G3IV-PUZBAB j
3G3JV-PRS j
3G3EV-PLNFD j
3G3IV-PLF j
Description Reference page
36 Process Meter K3MA-J Connected to the multi-function analog output of the Inverter.
Displays the rpm or speed of the machine or line in actual units.
Dedicated Options
Name Model Description
DC Reactor 3G3HV-PUZDAB j
Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter.
An adapter making it possible to easily mount the Inverter to DIN tracks.
DIN Track Mounting
Bracket
Adapter Panel
3G3IV-PEZZ08122 j 38
Digital Operator
Digital Operator Connection
Cable
RS-422/485
Communications Unit
3G3JV-PSI232J
(permanent)
3G3JV-PSI232JC
(removable)
3G3IV-PJVOP146
3G3IV-PJVOP140+
3G3IV-PEZZ08386A
(Digital Operator Case)
3G3IV-PCN126 (1 m)
3G3IV-PCN326 (3 m)
3G3JV-PSI485J
An Adapter Panel is required as an interface to connect a Digital Operator
(3G3IV-PJVOP140 or 3G3IV-PJVOP146) to the 3G3JV Inverter.
There are two models of Adapter Panel available. The 3G3JV-PSI232J is permanently installed and cannot be removed and the 3G3JV-PSI232JC for copying parameters is installed so that it can be removed.
The Digital Operator is used to control the Inverter from a distance. There are two models available. The 3G3IV-PJVOP140 is equipped with an adjuster and the 3G3IV-PJVOP146 is not.
Always use the 3G3IV-PJVOP140 together with a Digital Operator Case.
Without the Case, the Digital Operator’s connection cable cannot be wired. Using the Case also enables mounting to a control panel.
The Digital Operator Connection Cable is required to connect a Digital
Operator to a 3G3JV Inverter.
The RS-422/485 Communications Unit (3G3JV-PSI485J) functions as an interface for RS-422/485 general-purpose communications. The communications protocol conforms to MODBUS (same protocol as
3G3MV and 3G3RV Inverters). Communications can be used for Inverter control inputs, frequency references, monitoring Inverter operating status, and reading/writing parameter settings.
39
40
41
41
Reference page
37
Recommended Options
Name Model Description
Suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much larger than that of the Inverter.
A Noise Filter on the input side meeting the EC Directive’s EMC requirements.
Each of these Filters connected to the power input side eliminates noise in the power line connected to the Inverter and suppresses noise leaking from the Inverter to the power line.
Connect this Filter to the output side of the Inverter to suppress the noise generated by the Inverter from being transmitted to the output line.
Reference page
42
43
45
46
35
36
Options
Fan Unit
3G3IV-PFAN
j
The Fan Unit is a replacement for the presently installed cooling fan of the Inverter. Replace the cooling fan if it has reached the end of its service life or a warning of cooling fan failure (FAN) is indicated.
Fan Unit
Single-phase 200 V AC
Inverter
3G3JV-A2007
3G3JV-A2015/-A2022
3G3JV-A2037
3G3JV-AB015
3G3JV-A4015/-A4022
3G3JV-A4022
3G3JV-A4037
3G3IV-PFAN2007
3G3IV-PFAN2015J
3G3IV-PFAN2037
3G3IV-PFAN2015J
3G3IV-PFAN2037
Process Meter
K3MA-J
The Process Meter is connected to the analog monitor output of the Inverter to display the rpm and speed values of machines and lines in actual units.
Models and Applications
DC voltage/ None
Relay:
2SPST-NO
Power supply voltage
100 to 240 V AC
(50/60 Hz)
K3MA-J:
100 to 240 V AC
K3MA-J-A2, 100 to 240 V AC
24 V AC (50/60 Hz),
24 V DC
K3MA-J:
24 V AC/DC
K3MA-J-A2,
24 V AC/DC
Standard Specifications
Input signals
A/D conversion
Input impedance
Sampling period
DC voltage/current (0 to 20 mA, 4 to 20 mA, 0 to 5 V,
1 to 5 V,
±
10 V)
Double integral method
Current input: 45 Ω max.; voltage input: 1 M
Ω
min.
250 ms
Display refresh period
Max. displayed digits
Display type
Sign display
Sampling period (with average value processing:
Sample period x No. of averages)
5 (–19,999 to 99,999)
7-segment digital display
Minus sign (–) displayed automatically for negative input signals.
Supported Zero suppression
(leftmost digits)
Scaling Programmed (The displayed range corresponds to the maximum number of displayed digits.)
The decimal point position can be set as required.
Wiring Example
Circuit breaker for wiring
Threephase power supply
Inverter’s internal circuitry
Analog monitor
Analog output
–10 to +10 V DC
Hold functions
Comparative output hysteresis
Other functions
Maximum value hold, minimum value hold
Programmed with front-panel keys (0001 to 9999)
Output form
Comparative output response time
Enclosure ratings
Forced–zero by front-panel keys, zero reset, scaling teaching, display color switching (green [red], green, red [green], red), comparative output switching (upper limit, lower limit, upper/lower limits), average value processing (simple averaging: OFF, 2, 4, or 8 times)
Relay: DPST-NO
750 ms max.
Memory protection
Front panel: NEMA4X for indoor use (equivalent to
IP66), Rear case: IP20
Terminals: IP00 + finger protection (VDE0106/100)
Nonvolatile memory (100,000 overwrites)
Dimensions (mm)
Terminal cover
(included)
Recommended panel cutout
Terminals: M3, Terminal cover included.
Main display LED size
Options
DC Reactor
3G3HV-PUZDAB
j
The DC Reactor suppresses harmonic current generated from the Inverter and improves the power factor of the
Inverter. The DC Reactor suppresses harmonic current more effectively than the AC Reactor. Furthermore, the DC
Reactor can be used in combination with the AC Reactor.
Used with 3-phase or single-phase 200-V AC Inverters, or
3-phase 400-V AC Inverters.
Applicable Models
Voltage class
200 V
400 V
Inverter
Max. applicable motor capacity (kW)
0.1 to 0.75
1.5 to 3.7
0.2 to 0.75
1.5 to 2.2
3.7
Model Rated voltage
(V)
3G3HV-PUZDAB5.4A8MH
800 V DC
DC Reactor
Rated current
5.4
(A)
3G3HV-PUZDAB18A3MH
3G3HV-PUZDAB3.2A28MH
800 V DC
3G3HV-PUZDAB5.7A11MH
3G3HV-PUZDAB12A6.3MH
18
3.2
5.7
12
Inductance
(mH)
8
3
28
11
6.3
8
18
9
11
16
Loss (W)
External Dimensions (mm)
External Dimensions 1 External Dimensions 2
Two, d2 mounting holes
Two, d1 mounting holes
Four, d1 mounting holes
Model 3G3HV-
PUZDAB j
5.4A8MH
18A3MH
3.2A28MH
5.7A11MH
12A6.3MH
1
1
1
2
2
External i
53
76
53
60
76
H
85
86
85
90
86
W
74
W1
60
74
80
60
60
72
60
60
72
D
Dimension (mm)
D1 D2
32
55
32
32
55
---
80
---
---
80
0.8
1.2
0.8
0.8
1.2
t
M4 d1
M4
M4
M4
M4
---
M5 d2
---
---
M5
0.8
2.0
0.8
1.0
2.0
37
38
Options
DIN Track Mounting Bracket
3G3IV-PEZZ08122
j
An adapter making it possible to easily mount the Inverter to DIN tracks.
Applicable Models
Inverter
3G3JV-A2001/-A2002/-A2004/-A2007
3G3JV-A2015/-A2022
3G3JV-A2037
3G3JV-AB001/-AB002/-AB004
3G3JV-AB007/-AB015
3G3JV-A4002/-A4004/-A4007/-A4015/-A4022
3G3JV-A4037
External Dimensions (mm)
3G3IV-PEZZ08122A
3G3IV-PEZZ08122B
DIN Track Mounting Bracket
3G3IV-PEZZ08122A
3G3IV-PEZZ08122B
3G3IV-PEZZ08122C
3G3IV-PEZZ08122A
3G3IV-PEZZ08122B
3G3IV-PEZZ08122B
3G3IV-PEZZ08122C
Four, M4 tap
3G3IV-PEZZ08122C
Four, M4 tap
Four, M4 tap
Options
Adapter Panel
3G3JV-PSI232J
j
An Adapter Panel is required as an interface to connect a Digital Operator (3G3IV-PJVOP140 or 3G3IV-PJVOP146) to the 3G3JV
Inverter.
There are two models of Adapter Panel available. The 3G3JV-PSI232J is permanently installed and cannot be removed and the
3G3JV-PSI232JC for copying parameters is installed so that it can be removed.
Connections
3G3JV
Inverter Adapter Panel
3G3JV-PSI232J (permanent)
3G3JV-PSI232JC (removable)
Digital Operator
3G3IV-PJVOP146
3G3IV-PJVOP140 + 3G3IV-
PEZZ08386A (Digital Operator Case)
Digital Operator Connection
Cable
3G3IV-PCN126 (1 m)
3G3IV-PCN326 (3 m)
External Dimensions (mm)
3G3JV-PSI232J (Permanent)
3G3JV-PSI232JC (Removable)
39
40
Options
Digital Operator
3G3IV-PJVOP140/PJVOP146
The Digital Operator (3G3IV-PJVOP140/PJVOP146) is used to control the Inverter from a distance. There are two models available.
The 3G3IV-PJVOP140 is equipped with an adjuster and the 3G3IV-PJVOP146 is not.
Always use the 3G3IV-PJVOP140 together with a Digital Operator Case (3G3IV-PEZZ08386A). Without the Case, the Digital Operator’s connection cable cannot be wired. Using the Case also enables mounting to a control panel.
Note: When a Digital Operator is connected, the Operator on the Inverter cannot be used to control operation (i.e., only display functions will work).
3G3IV-PJVOP140 (with Adjuster)
8 max.
3G3IV-PJVOP146 (without Adjuster)
3.6 dia
Four, 4.4-dia. mounting holes
Four depressions for M4 bolts (Depth: 3.5)
Options
Digital Operator Case
3G3IV-PEZZ08386A
The Digital Operator Case (3G3IV-PEZZ08386A) is used to secure the 3G3IV-PJVOP140 Digital Operator. Without this Case, the
Digital Operator’s connection cable cannot be wired. Always use the 3G3IV-PJVOP140 and the Digital Operator Case together.
Four, 4.4-dia. mounting holes
Four depressions for
M4 bolts (Depth: 3.5)
Digital Operator Connection Cable
3G3IV-PCN126/PCN326
The Digital Operator Connection Cable (3G3IV-PCN126/PCN326) is required to connect a Digital Operator to a 3G3JV Inverter.
Models and Specifications
Digital Operator Connection Cable
3G3IV-PCN126
3G3IV-PCN326
1 m
3 m
Cable length
RS-422/485 Communications Unit
3G3JV-PSI485J
The RS-422/485 Communications Unit (3G3JV-PSI485J) functions as an interface for RS-422/485 general-purpose communications. The communications protocol conforms to MODBUS (same protocol as 3G3MV and 3G3RV Inverters). Communications can be used for Inverter control inputs, frequency references, monitoring Inverter operating status, and reading/writing parameter settings.
External Dimensions (mm)
41
Options
AC Reactor
3G3IV-PUZBAB
j
(Yaskawa Electric)
The AC Reactor suppresses harmonic current generated from the Inverter and improves the power factor of the Inverter. Connect the
AC Reactor to the Inverter if the capacity of the power supply is much larger than that of the Inverter. Select the AC Reactor model from the following table according to the motor capacity.
Note: The AC Reactor can be used with either 3-phase or single-phase 200-V AC Inverters.
Connection Example
MCCB AC Reactor
Motor
Applicable Range
AC Reactor required for smooth operation under present power supply conditions
Power supply capacity (kVA)
AC Reactor not required
Inverter capacity (kVA)
Applicable Models and Dimensions
200-V Class
Max.
Model
3G3IV-
PUZBAB j
Current Inducta
(mH)
Loss motor capacity
(kW)
0.1 to 0.2
0.4
0.75
1.5
2.2
3.7
2A7.0MH
2.5A4.2MH
5A2.1MH
10A1.1MH
15A0.71MH
20A0.53MH
10
15
20
2
2.5
5
7.0
4.2
2.1
1.1
0.71
0.53
25
30
35
8
15
15
Weight
3
3
3
2.5
2.5
2.5
A B
120 71
120 71
120 71
130 88
130 88
130 88
B1 C D
---
---
---
115 40
120 40
120 40
---
---
130
130
50
50
114 105 50
Dimension (mm)
E
65
65
65
50
50
50
F
105
105
105
130
130
130
H
22
22
22
20
20
20
J K
M6 10.5
7
M6 10.5
7
M6 10.5
7
M6 11.5
7
M6 11.5
7
M6 11.5
7
L M
400-V Class
Max.
motor capacity
(kW)
0.2 to 0.4
0.75
1.5
2.2
3.7
Model
3G3IV-
PUZBAB j
1.3A18.0MH
2.5A8.4MH
5A4.2MH
7.5A3.6MH
10A2.2MH
Current
1.3
2.5
5
7.5
10
Inducta
(mH)
18.0
8.4
4.2
3.6
2.2
15
15
25
35
43
Loss Weight
3
3
3
2.5
2.5
A B
120 71
120 71
130 88
130 88
130 88
B1
---
---
---
---
---
C D
120 40
120 40
130 50
130 50
130 50
Dimension (mm)
E
50
50
70
70
65
F
105
105
130
130
130
H
20
20
22
22
22
J K
M6 10.5
7
M6 10.5
7
M6 9
M6 9
M6 11.5
7
7
7
L M
M4
M4
M4
M4
M4
External dimensions for AC Reactors are shown below. “External Dimensions 2” shows the dimensions of the 200-V-class AC Reactor for 3.7-kW motors. “ External Dimensions 1” shows the dimensions of all other models.
M4
M4
M4
M4
M4
M5
External
Dimensions 1
M Terminal
External
Dimensions 2
M Terminal
Nameplate
Nameplate
42
Mounting Dimensions
4-J mounting bolt
Mounting Dimensions
4-J mounting bolt
Options
EMC-conforming Input Noise Filter
3G3JV-PRS
j
(Rasmi)
The Input Noise Filter is connected between the power supply input terminals (R/L1, S/L2, T/L3) of the Inverter and the power supply in order to meet the EC Directive’s EMC requirements.
Connection Example
MCCB Noise Filter
Clamp core
3-phase 200 V AC, single-phase 200 V AC, or 3-phase 400 V AC
Applicable Models
Voltage
Inverter
Model
3G3JV-A2001/-A2002/-A2004/-A2007
3G3JV-A2015/-A2022
3G3JV-A2037
3G3JV-AB001/-AB002/-AB004
3G3JV-AB007/-AB015
3G3JV-A4002/-A4004
3G3JV-A4007/-A4015/-A4022
3G3JV-A4037
External Dimensions
3G3JV-PRS2010J
Model
3G3JV-PRS2010J
3G3JV-PRS2020J
3G3JV-PRS2030J
3G3JV-PRS1010J
3G3JV-PRS1020J
3G3JV-PRS3005J
3G3JV-PRS3010J
3G3JV-PRS3020J
EMC-conforming Input Noise Filter
Rated current (A)
10 0.8
20
5
10
16
26
10
15
1.0
1.3
0.6
1.0
1.0
1.0
1.1
3G3JV-PRS2030J
Three,
5-dia. holes
Three,
5-dia. holes
Weight (kg)
Two, M4 holes
Four, M4 holes
(for Inverter mounting use)
3G3JV-PRS2020J
Three, 5-dia. holes
Four, M4 holes
3G3JV-PRS1010J
Three,
5-dia. holes
Two, M4 holes
43
44
Options
3G3JV-PRS1020J
Three,
5-dia holes
Four, M4 holes
3G3JV-PRS3005J
Three,
5-dia holes
Four, M4 holes
(for Inverter mounting use)
3G3JV-PRS3010J
Three,
5-dia holes
Four, M4 holes
(for Inverter mounting use)
3G3JV-PRS3020J
Three,
5-dia holes
Four, M4 holes
(for Inverter mounting use)
Options
Simple Input Noise Filter
3G3EV-PLNFD
j
(Yaskawa Electric)
Applicable Models
Inverter
Voltage Model
3G3JV-A2001/-A2002/-A2004/-A2007
3G3JV-A2015
3G3JV-A2022
3G3JV-A2037
00 C 3G3JV-AB001/-AB002
3G3JV-AB004
3G3JV-AB007
3G3JV-AB015
3G3JV-A4002/-A4004/-A4007
3G3JV-A4015/-A4022
3G3JV-A4037
Connection Example
3-phase input
Noise filter
The Simple Input Noise Filter is connected to the power input side to eliminate the noise in the power line connected to the Inverter and suppress noise leaking from the Inverter to the power line.
Model
3G3EV-
PLNFD2103DY
PLNFD2153DY
PLNFD2203DY
PLNFD2303DY
PLNFB2102DY
PLNFB2152DY
PLNFB2202DY
PLNFB2302DY
PLNFD4053DY
PLNFD4103DY
PLNFD4153DY
Simple Input Noise Filter
Rated current (A)
10
15
20
10
15
20
30
30
5
10
15
0.2
0.2
0.4
0.5
0.1
0.2
0.2
0.3
0.3
0.4
0.4
Weight (kg)
Single-phase input
Noise filter
External Dimensions
External Dimensions 1
(Single-phase Input)
Input Noise Filter
Connection Example
External Dimensions 2
(Three-phase Input)
Input Noise Filter
Connection Example
External Dimensions 3
(Three-phase Input)
Model
PLNFD2103DY
PLNFD2153DY
PLNFD2203DY
PLNFD2303DY
PLNFB2102DY
PLNFB2152DY
PLNFB2202DY
PLNFB2302DY
PLNFD4053DY
PLNFD4103DY
PLNFD4153DY
3
1
External figure (above)
2
120
120
120
130
170
170
170
120
120
170
170
W
80
80
80
90
130
130
130
80
80
90
110
D
75
95
95
50
50
50
65
55
55
70
70
H max.
---
---
---
108
108
108
118
108
108
158
---
Dimension (mm)
A A’
79
79
79
---
---
---
---
---
---
---
79
68
68
68
78
118
118
118
68
68
78
98
B Mounting screw
M4 × 4, 20 mm
M4 × 4, 20 mm
M4
×
4, 20 mm
M4 × 4, 20 mm
M4
×
6, 20 mm
M4 × 4, 20 mm
M4 × 4, 20 mm
M4 × 4, 20 mm
M4
×
6, 30 mm
M4 × 6, 30 mm
M4 × 6, 30 mm
45
Options
Output Noise Filter
3G3IV-PLF
j
(Tokin)
The Output Noise Filter suppresses the generated noise of the Inverter from being transmitted to the output line. Connect the Output Noise Filter to the output side of the
Inverter.
Connection Example
Noise filter
Output Noise Filter Connection Example
Applicable Models
Voltage class
200-V class
400-V class
3.7
0.2
0.4
0.75
1.5
2.2
3.7
0.1
0.2
0.4
0.75
1.5
2.2
Inverter
Max. applicable motor capacity (kW)
External Dimensions
6.7
0.9
1.4
2.6
3.7
4.2
6.6
0.3
0.6
1.1
1.9
3.0
4.2
Inverter capacity (kVA) Model
Output Noise Filter
Rated current (A)
3G3IV-PLF310KA 10
3G3IV-PLF320KA
3G3IV-PLF310KB
20
10
Model
PLF310KA
PLN320KA
PLF310KB
Terminal board
TE-K5.5 M4
TE-K5.5 M4
TE-K5.5 M4
140
A
140
140
100
B
100
100
100
C
100
100
Dimensions (mm)
D
90
90
90
70
70
70
E
45
45
45
F G
7 × 4.5 dia.
7
×
4.5 dia.
7
×
4.5 dia.
H
4.5 dia.
0.5
0.6
0.5
46
Inverter Models
Inverter Models
Rated voltage Degree of protection
Single-phase 200 V AC g yp ( q ) 0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
Max. applicable motor capacity
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
Model
3G3JV-A2001
3G3JV-A2002
3G3JV-A2004
3G3JV-A2007
3G3JV-A2015
3G3JV-A2022
3G3JV-A2037
3G3JV-AB001
3G3JV-AB002
3G3JV-AB004
3G3JV-AB007
3G3JV-AB015
3G3JV-A4002
3G3JV-A4004
3G3JV-A4007
3G3JV-A4015
3G3JV-A4022
3G3JV-A4037
Explanation of Product Code
3G3JV-A2007
Series name:
3G3JV Series
Max. applicable motor capacity
001
002
004
007
015
022
037
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
Voltage class
2
B
4
3-phase 200 V AC (200-V class)
Single-phase 200 V AC (200-V class)
3-phase 400 V AC (400-V class)
Degree of protection
A Panel-mounting type (IP10 or higher)/closed wall-mounting type
47
48
Warranty and Application Considerations
Read and Understand this Catalog
Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANT-
ABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUY-
ER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED
USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COM-
MERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY,
NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UN-
LESS OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAIN-
TAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer’s application or use of the products.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products.
•
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
•
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING
THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROP-
ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this catalog has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
49
OMRON Corporation
FA Systems Division H.Q.
66 Matsumoto
Mishima-city, Shizuoka 411-8511
Japan
Tel: (81)55-977-9181/Fax: (81)55-977-9045
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
1 East Commerce Drive, Schaumburg, IL 60173
U.S.A.
Tel: (1)847-843-7900/Fax: (1)847-843-8568
OMRON IDM CONTROLS, INC.
9510 N. Houston-Rosslyn Rd.
Houston, Texas 77088
Tel: (1)713-849-1900/Fax: (1)713-849-4666
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
Singapore 239920
Tel: (65)6835-3011/Fax: (65)6835-2711
Authorized Distributor:
Cat. No. I905-E1-04 Note: Specifications subject to change without notice.
Printed in Japan
0503-0.6M