advertisement
Installation/Owner’s Manual
Heavy-Duty Vehicular Slide Gate Operator
Use this manual for circuit board 4404-010 Revision A or higher.
9210-065-H-2-13
CONF
AN ORM
SI/U
CA
N/
CER
TIF
L-3
S TO
VE
CS
MODE
A C2
HICU
CLA
SS
25
IED TO
2.2 NO.
LA
R GA
TE
247
SERIA
L
53382
OP
ER
HP
AT
OR
L
VOL
TS
AM
PS
MAX
GA
Do
TE LO orKing
AD
PHA
SE
60 Hz
, In c.,
Ing lewo od
, CA
W
ARNING
Ope
Do
Do pa rate
fre not
ga e of
allow rate not th wh
sta nd ile
pe
ga ad ow ne r’s
GATE CAN te onl y w child te is
m ren gate
m hen ga
to
pa oving.
anua obs th l and te a tru re a is s.
in s
AT
H igh te a rea or wa lk thr ough
saf
ins truct ions
Date Installed:
Installer/Company Name:
Phone Number:
Leave Manual with Owner
Circuit Board
Serial Number and Revision Letter:
Copyright 2013 DoorKing, Inc. All rights reserved.
UL 325 Compliant
Copyright 2009 DoorKing, Inc. All rights reserved.
TM
Horse
Power
1
2
3
3
3
3
SPECIFICATIONS
Use this manual for the 9200 series operators with circuit board 4404-010 Rev A or higher ONLY.
Volt/Phase Amps Gearbox
Mech. Disc
Brake
Gate
Speed
Slow
Down
Chain #
Max Gate
Weight - lbs.
AC
Module
Electronic
Brake
115 / 1
208 / 1
230 / 1
208 / 3
230 / 3
208 / 1
9.7
5.0
4.9
3.3
3.4
11.5
40:1 No
1 ft/sec
Fixed
No
50
60
50
2000
3000
1800
No No
230 / 1
208 / 3
11.7
6.6
40:1 No
2 ft/sec
Adjustable
Yes
60 2000
3 HP No
230 / 3
208 / 3
230 / 3
208 / 3
230 / 3
208 / 3
230 / 3
208 / 1
230 / 1
6.2
9.8
9.6
12.8
12.6
9.8
9.6
12.8
12.6
40:1
10:1
40:1
10:1
No
Yes
No
Yes
2 ft/sec
Adjustable
4 ft/sec
Adjustable
2 ft/sec
Adjustable
2 ft/sec
Adjustable
Yes
Yes
Yes
Yes
60
60
80
80
5000
3000
8000
8000
5 HP
10 HP
10 HP
10 HP
Yes
Yes
Yes
Yes
Pedestal
Stand Kit
Not
Included
Not
Included
Included
Included
Included
Included
Class of Operation
Type of Gate
Max Gate Length
Series 9200 - UL 325 Class III, IV
Vehicular Slide Gates Only
100 Ft (Installed Level)
Cycles Continuous
Operating Temperature 10° F to 140° F (-12° C to 62° C)
“Optional” heater kits recommended for colder temperatures.
Entrapment Protection Provision for connection of a non-contact sensor (Type B1) and/or a contact sensor (Type B2).
18”
Heavy-Duty Pedestal
Mounting Stand Kit
P/N 9200-135
18”
20”
16”
WARNING
CONFORMS TO
ANSI/UL-325
53382
CERTIFIED TO
CAN/CSA C22.2 NO. 247
VEHICULAR GATE OPERATOR
CLASS
MODEL
SERIAL
VOLTS
HP
PHASE
60 Hz AMPS
MAX GATE LOAD
DoorKing, Inc., Inglewood, CA
MOVING GATE CAN CAUSE
SERIOUS INJURY OR DEATH
Operate gate only when gate area is in sight and free of people and obstructions.
Do not allow children to play in gate area or operate gate.
Do not stand in gate path or walk through path while gate is moving.
Read owner’s manual and safety instructions.
2”
12”
35.5”
20”
16”
16.25”
31.25”
14”
Chain Height:
Idler wheels in factory set position.
DoorKing, Inc. reserves the right to make changes in the products described in this manual without notice and without obligation of DoorKing, Inc. to notify any persons of any such revisions or changes. Additionally, DoorKing, Inc. makes no representations or warranties with respect to this manual. This manual is copyrighted, all rights reserved. No portion of this manual may be copied, reproduced, translated, or reduced to any electronic medium without prior written consent from DoorKing, Inc.
9210-065-H-2-13 1
2
TABLE OF CONTENTS
SPECIFICATIONS
Gate Construction
Important Safety Instructions
Instructions regarding intended installation:
Important Notices
UL325 Entrapment Protection
Glossary
Slide Gate Requirements
Slide Gate Protection
SECTION 1 - INSTALLATION
1.2 Underground Conduit Requirements
1.3 Installation Options, Gate Types
1.5 Installation #2, Chain Tray Kit
1.7 Installation of Warning Signs
SECTION 2 - AC POWER TO OPERATOR(S)
2.1 High Voltage Wire Runs
2.2 High Voltage Terminal Connection
SECTION 3 - ADJUSTMENTS
3.1 Circuit Board Description and Adjustments
3.2 DIP-Switch SW 1 and SW 2 Settings
10
10
10
11-12
13
14-15
16
17
1
8
9
6
7
4
5
4
4
17
17
18
19
19
20-21
22
9210-065-H-2-13
TABLE OF CONTENTS
3.4 Inherent Reverse Sensor Adjustment
3.5 Current Sensor Adjustment
3.6 AC Module Adjustment
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION
4.1 UL 325 Terminal Description
4.2 Secondary Entrapment Protection Device Locations
4.3 Loop Detector Wiring
SECTION 5 - MAIN TERMINAL WIRING
5.1 Main Terminal Description
5.2 Control Wiring for Single/Primary Operator
5.3 Auxiliary Device Wiring
5.4 Bi-Parting Gates Wiring - Dual Gate Operators
SECTION 6 - OPERATING INSTRUCTIONS
6.1 AC Power and Reset Button
(
s
)
Soft Shutdown
Hard Shutdown
6.3 Manual Gate Operation
SECTION 7 - MAINTENANCE AND TROUBLESHOOTING
7.1 Maintenance
7.2 Built-In Diagnostic Tests
7.3 Troubleshooting
9210-065-H-2-13
25
25
26-27
28
29
29
30
31
32
33
33
34
23
23
24
35
36
36
37
37-38
39
3
ASTM F2200 Standard for Gate Construction
Vehicular gates should be constructed and installed in accordance with ASTM F2200; Standard Specification for Automated
Vehicular Gate Construction. For a copy of this standard, contact ASTM directly at 610-832-9585; [email protected]; or www.astm.org
.
Important Safety Instructions
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object
activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust
and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate
hardware.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. SAVE THESE INSTRUCTIONS!
4
Instructions regarding intended installation:
• Install the gate operator only if:
1. The operator is appropriate for the construction of the gate and the usage class of the gate.
2. All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of 6 feet
(1.83 m) above the ground to prevent a 2 ¼ inch (57.2 mm) diameter sphere from passing through the openings
anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
3. All exposed pinch points are eliminated or guarded.
4. Guarding is supplied for exposed rollers.
• The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate
access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that
persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
• The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures
when opening and closing to reduce the risk of entrapment. Swinging gates should not open into public access areas.
• The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not
over-tighten the operator clutch, pressure relief valve or reduce reversing sensitivity to compensate for a damaged gate.
• For gate operators utilizing Type D protection:
1. The gate operator controls must be placed so that the user has full view of the gate area when the gate is moving.
2. A warning placard shall be placed adjacent to the controls.
3. An automatic closing device (such as a timer, loop sensor, or similar device) shall not be employed.
4. No other activation device shall be connected.
• Controls intended for user activation must be located at least ten feet (10’) away from any moving part of the gate and
where the user is prevented from reaching over, under, around or through the gate to operate the controls. Outdoor or
easily accessible controls should have a security feature to prevent unauthorized use.
• The Stop and/or Reset button must be located in the line-of-sight of the gate. Activation of the reset control shall not
cause the operator to start.
• A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
• For gate operators utilizing a non-contact sensor:
1. See the instructions on the placement of non-contact sensors for each type of application.
2. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate
is still moving in the opening direction.
3. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exist, such as the
perimeter reachable by a moving gate or barrier.
9210-065-H-2-13
• For gate operators utilizing contact sensors:
1. One or more contact sensors shall be located where the risk of entrapment or obstruction exist, such as at the
leading edge, trailing edge, and post mounted both inside and outside of a vehicular horizontal slide gate.
2. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate.
3. One or more contact sensors shall be located at the pinch point of a vehicular vertical pivot gate.
4. A hardwired contact sensor shall be located and its wiring arranged so that the communication between the sensor
and the gate operator is not subjected to mechanical damage.
5. A wireless contact sensor such as one that transmits radio frequency (RF) signals to the gate operator for
entrapment protection functions shall be located where the transmission of the signals are not obstructed or
impeded by building structures, natural landscaping or similar obstructions. A wireless contact sensor shall function
under the intended end-use conditions.
6. One or more contact sensors shall be located at the bottom edge of a vertical barrier (arm).
Important Notices
Vehicular gate operator products provide convenience and security. However, gate operators must use high levels of force to move gates and most people underestimate the power of these systems and do not realize the potential hazards associated with an incorrectly designed or installed system. These hazards may include:
•
• Pinch points
Entrapment areas
•
•
•
• Reach through hazards
Absence of entrapment protection devices
Improperly located access controls
Absence of vehicle protection devices
• Absence of controlled pedestrian access
In addition to these potential hazards, automated vehicular gate systems must be installed in accordance with the UL 325
Safety Standard and the ASTM F2200 Construction Standard. Most lay persons are unaware of, or are not familiar with, these standards. If an automated vehicular gate system is not properly designed, installed, used and maintained, serious injuries or death can result. Be sure that the installer has instructed you on the proper operation of the gate and gate operator system.
Be sure that the installer has trained you about the basic functions of the required reversing systems associated with your gate operating system and how to test them. These include reversing loops, inherent reversing system, electric edges, photoelectric cells, or other external devices.
• This Owner’s Manual is your property. Keep it in a safe place for future reference.
• Be sure that all access control devices are installed a minimum distance of 10 feet away from the gate and gate operator, or in such a way that a person cannot touch the gate or gate operator while using the device. If access control devices are installed in violation of these restrictions, immediately remove the gate operator from service and contact your installing dealer.
• Loops and loop detectors, photo-cells or other equivalent devices must be installed to prevent the gate from closing on vehicular traffic.
• The speed limit for vehicular traffic through the gate area is 5 MPH. Install speed bumps and signs to keep vehicular traffic from speeding through the gate area. Failure to adhere to posted speed limits can result in damage to the gate, gate operator, and to the vehicle.
• Be sure that all persons who will use the gate system are familiar with the proper use of the gate and gate operator and are familiar with the possible hazards associated with the gate system.
• Be sure that warning signs are permanently installed on both sides of the gate in an area where they are fully visible to traffic.
• It is your responsibility to periodically check all entrapment protection devices. If any of these devices are observed to function improperly, remove the operator from service immediately and contact your installing or
• Follow the recommended maintenance schedule.
• Do not allow children to play in the area of the operator or to play with any gate-operating device.
• To remove the gate operator from service, operate the gate to the full open position and then shut off power to the operator at the service panel.
9210-065-H-2-13 5
UL325 Entrapment Protection
Class I
A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or a garage or parking area associated therewith.
Class II
A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units) hotel, garages, retail store or other building servicing the general public.
STATE PRISON
Class III
A vehicular gate operator (or system) intended for use in a industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
Class IV
A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
This table illustrates the entrapment protection requirements for each of the four UL325 classes.
6
UL325
Classifications
Horizontal Slide, Vertical Lift, Vertical Pivot
Primary Protection
Swing and Vertical Barrier (arm)
Secondary Protection Primary Protection Secondary Protection
Class I and II
Class III
Class IV
A
A, B1 or B2
A, B1, B2 or D
B1, B2 or D
A, B1, B2, D or E
A, B1, B2, D or E
A or C
A, B1, B2 or C
A, B1, B2, C or D
A, B1, B2, C or D
A, B1, B2, C or D
A, B1, B2, C, D or E
A - Inherent entrapment protection system.
B1 - Provision for connection of, or supplied with, a non-contact sensor (photoelectric sensor or the equivalent).
When used as the PRIMARY device, must be monitored.
B2 - Provision for connection of, or supplied with, a contact sensor (edge device or the equivalent).
When used as the PRIMARY device, must be monitored.
C - Inherent adjustable clutch or pressure relief device.
D - Provision for connection of, or supplied with, an actuating device requiring continuous pressure to maintain
opening or closing motion of the gate.
E - An inherent audio alarm.
9210-065-H-2-13
Glossary
GATE - A moving barrier such as a swinging, sliding, raising, lowering, or the like, barrier, that is a stand-alone passage barrier or is that portion of a wall or fence system that controls entrance and/or egress by persons or vehicles and completes the perimeter of a defined area.
RESIDENTIAL VEHICULAR GATE OPERATOR – CLASS I - A vehicular gate operator (or system) intended for use in a home of one-to four single family dwelling, or garage or parking area associated therewith.
COMMERCIAL / GENERAL ACCESS VEHICULAR GATE OPERATOR - CLASS II - A vehicular gate operator (or system) intended for use in a commercial location or building such as a multi-family housing unit (five or more single family units), hotels, garages, retail store, or other building servicing the general public.
INDUSTRIAL / LIMITED ACCESS VEHICULAR GATE OPERATOR - CLASS III - A vehicular gate operator (or system) intended for use in an industrial location or building such as a factory or loading dock area or other locations not intended to service the general public.
RESTRICTED ACCESS VEHICULAR GATE OPERATOR - CLASS IV - A vehicular gate operator (or system) intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
VEHICULAR BARRIER (ARM) OPERATOR (OR SYSTEM) - An operator (or system) that controls a cantilever type device (or system), consisting of a mechanical arm or barrier that moves in a vertical arc, intended for vehicular traffic flow at entrances or exits to areas such as parking garages, lots or toll areas.
VEHICULAR HORIZONTAL SLIDE-GATE OPERATOR (OR SYSTEM) - A vehicular gate operator (or system) that controls a gate which slides in a horizontal direction that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
VEHICULAR SWING-GATE OPERATOR (OR SYSTEM) - A vehicular gate operator (or system) that controls a gate which moves in an arc in a horizontal plane that is intended for use for vehicular entrance and exit to a drive, parking lot, or the like.
SYSTEM - In the context of these requirements, a system refers to a group of interacting devices intended to perform a common function.
WIRED CONTROL - A control implemented in a form of fixed physical interconnections between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
WIRELESS CONTROL - A control implemented in means other than fixed physical interconnections (such as radio waves or infrared beams) between the control, the associated devices, and an operator to perform predetermined functions in response to input signals.
INHERENT ENTRAPMENT PROTECTION SYSTEM - A system, examples being a motor current or speed sensing system, which provides protection against entrapment upon sensing an object and is incorporated as a permanent and integral part of the operator.
EXTERNAL ENTRAPMENT PROTECTION DEVICE - A device, examples being an edge sensor, a photoelectric sensor, or similar entrapment protection device, which provides protection against entrapment when activated and is not incorporated as a permanent part of an operator.
ENTRAPMENT - The condition when an object is caught or held in a position that increases the risk of injury.
9210-065-H-2-13 7
8
Slide Gate Requirements
The operator is intended for installation only on gates used for vehicles.
Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate.
(ref. UL 325 56.8.4.b)
Adjacent fence that covers open gate position.
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
Fence
High Risk of Entrapment Area
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
Closed Gate
X X X
All openings of a horizontal slide gate are guarded or screened from the bottom of the gate to a minimum of six (6) feet (1.83 m) above the ground to prevent a 2 1/4 inch (57.2 mm) diameter sphere from passing through the openings anywhere in the gate and in that portion of the adjacent fence that the gate covers in the open position.
(ref. ASTM F2200-11a, 6.1.2)
Compliant openings
less than 2 1/4”.
X X X X X X X X X X X X X X X X X X X X X X X X X
Gate Frame and Adjacent Fence Area
Drawings NOT to scale.
Non-compliant openings
wider than 2 1/4”.
Less than 2 1/4”
Screened Wire Mesh.
Note: Install screened wire mesh to an existing non-compliant gate and the adjacent fence that covers open gate position
(See above).
A gap, measured in the horizontal plane parallel to the roadway, between a fixed stationary object nearest the roadway (such as a gate support post) and the gate frame when the gate is in either the fully open position or the fully closed position, shall not exceed
2 1/4 inch (57.2 mm).
(ref. ASTM F2200 6.1.4)
Note: A filler post or barrier may need to be installed in the gap area to reduce the distance to 2 1/4 inches or
less. A contact sensor should be installed in this area for safety.
Gate Frame and Adjacent Fence Area
9210-065-H-2-13
Slide Gate Protection
Entrapment protection devices are required to reduce the risk of injury.
Install sensors where the risk of entrapment or obstruction exists while gate is moving. Individual requirements will vary.
Contact Sensor (Reversing Edges)
A Installed on the fence to help minimize the potential of entrapment between the gate and fence. A filler post or barrier may need to be installed between fence and gate.
B Helps minimize the potential of entrapment during the back travel of the gate.
C Minimizes the potential of the gate closing on vehicular or other traffic that loops cannot sense.
2
B
Non-Contact Sensors (Photo Sensors)
1 Minimizes the potential of the gate closing on vehicular or other traffic that loops cannot sense.
2 Helps minimize the potential of entrapment during the back travel of the gate.
Note: DO NOT USE MMTC, Inc. Model IR55 Photo Sensor - P/N 8080-010 for the
9200 series slide gate operator.
Automatic
Exit Loop
(Optional) will provide an open command to the gate operator(s) when a vehicle is exiting the property.
Reverse
Loop
Minimizes the potential of the gate closing when a vehicle is present. Number and placement of loops is dependent on the application.
A
1
Warning Signs
Permanently mounted and easily visible from either side of the gate.
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time without prior warning.
Do not let children operate the gate or play in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
Reverse
Loop
Minimizes the potential of the gate closing when a vehicle is present. Number and placement of loops is dependent on the application.
Separate
Pedestrian
Walkway
Located so pedestrians cannot come in contact with the vehicular gate.
9210-065-H-2-13
Warning Signs
Permanently mounted and easily visible from either side of the gate.
Moving Gate Can Cause
Serious Injury or Death
KEEP CLEAR! Gate may move at any time without prior warning.
Do not let children operate the gate or play in the gate area.
This entrance is for vehicles only.
Pedestrians must use separate entrance.
C
9
SECTION 1 - INSTALLATION
Prior to beginning the installation of the slide gate operator, we suggest that you become familiar with the instructions, illustrations, and wiring guide-lines in this manual. This will help insure that your installation is performed in an efficient and professional manner compliant with UL 325 safety and ASTM F2200 construction standards.
The proper installation of the vehicular slide gate operator is an extremely important and integral part of the overall access control system. Check all local building ordinances and building codes prior to installing this operator. Be sure your installation is in compliance with local codes.
1.1 Gate Hardware
6 Inch 4 Inch
DoorKing has a full line of Tandem V-wheels that are ideal for heavy gates and will ensure safe, reliable and long lasting gate operation. The gate must be properly installed and roll smoothly in both directions.
Guide Rollers with Protective Covers
Helps to minimize a pinch point on the gate.
1.2 Underground Conduit Requirements
Single/
Primary
Operator
Position
Secondary
Operator
Position
10
Primary/Secondary Interconnection Cable (Dual Operator Application Only)
Sweeps
Control and/or P.A.M.S. Wires (Low Voltage wire insulation)
Loop Lead-In Wires (Low Voltage wire insulation)
AC Input Power (High Voltage wire insulation)
AC Input Power (High Voltage wire insulation)
3/4 Inch Minimum
• The conduit requirements are for a typical slide gate operator installation (the secondary operator is shown for
those applications where a secondary operator may be used). The conduit requirements for your application may
vary from this depending on your specific needs.
•
• Use only sweeps for conduit bends. Do not use 90° elbows as this will make wire pulls very difficult and can cause
damage to wire insulation.
DoorKing recommends using 3/4-inch conduit.
Sweep
YES
• Be sure that all conduits are installed in accordance with local codes.
Elbow
NO
• Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
9210-065-H-2-13
1.3 Installation Options
The operator MUST be level. See the next page for typical gate types. We suggest that you contact the local building department to determine the required depth of the concrete pad since soil conditions and code requirements vary from city to city.
#1 - Operator Mounted Directly on a Concrete Pad
Typically used when gates are less than 20 feet in length and under 2000 lbs. in weight. V-rail v-wheel gate type shown.
Chain
Configuration
See page
16 for details.
CO NF
AN
VE HIC
CL ASS
ORM /UL S T
N/C CE
SA RT
-32 5 O
MO DE
SE
RIAL
L
VO LTS
2.2
UL AR NO . 2
GA TE O 47
PER
ATO
HP
AM PS
MA
X G
Doo
ATE ing
LO
, In
AD c., I ngl
PHAS
E
60 H ew ood
, C A
R
SE
Op and
Do or o
Do
MO VIN
RI era
fre
no per
no
w
Rea d o te g e o t all ate t sta hile
G G
OUS
on ow c
ga nd i gate wn er’s
INJ ly w ople hild te. n g
is m
UR
an d o
to pl
pa ovin
CA N C
Y O hen gate bstr th o ucti
AU
R DEA
are a is ons.
n ga te a
SE
TH igh rea anu al a g. r w alk nd s afe
thr oug ty in struc tion s.
Idler
Wheels
See page 13 for details.
Concrete Pad
Idler wheels are factory set in the correct position.
Remove the chain knock-outs in operator housing.
#2 - Operator Mounted on the Heavy-Duty Pedestal Mounting Stand
The pedestal mounting stand kit (P/N 9200-135) MUST be used when gates require a chain tray (Typically for gates that are longer than 20 feet in length). The chain tray helps support the weight of the chain and reduce the chain stretching that occurs over time. DoorKing offers a chain tray kit that will fit any length gate (P/N 2601-270 10 ft. connecting sections).
DoorKing highly recommends using the pedestal stand for gates heavier than 2000 lbs. for a more secure attachment to a larger and heavier concrete pad. V-rail v-wheel gate type shown.
CO NF
CAN
/CSA
ANSI
CE
RT
OR MS
-3
IFIE
D TO
TO
VE HICU
CL ASS
2.2
NO
LAR
GA
. 24
TE O
PE
533 82
HP
RA TO
R
MO DE
SE
RIAL
VOL
TS
AMPS
MAX
GAT E LO
Doo rKin g, In
AD c., I ngle
PH
ASE
60 H wo od, CA
W
ARNI
NG
MO VIN
SE RIO G G
Op era
Do
no
Do path
Rea te g
fre t all era t sta
w d o
US ate ow
ga er’s
INJ ly w ople ildr ate n g te is
m anu
ATE
UR hen d ob en t ate
CA
Y O ga stru o p th o ovin g. al a nd s
N C rea ctio lay r w
AU
R D
is i ate alk
SE thro ugh afe ty in
are
H n s igh
Chain
Configuration
See page
16 for details.
9210-065-H-2-13
Chain T ray
Concrete Pad
Pedestal
Mounting
Stand
See pages 14 and 15 for details.
Idler
Wheels
The idler wheels must be moved to the lower position to use a chain tray. DO NOT remove the chain knock-outs.
11
1.3 Continued
Gate Types
• Steel or Aluminum.
• 8,000 lb Max. Weight
per Gate (9240, 9245).
Heav y-Dut y Ornamental Cantilever
AR NIN
Pedestal mounting stand and chain tray recommended for gates over 20 ft
.
Heav y-Dut y Box Frame Cantilever
AR
NIN
Pedestal mounting stand and chain tray recommended for gates over 20 ft.
12
Heav y-Dut y Box Frame Roller y V-Rail V-Wheel Ornamental
Pedestal mounting stand and chain tray recommended for gates over 20 ft.
y-Dut
Heav
otal Gate Length
Single Operator - 100 Ft Max. Gate Length
Dual Operators - 200 Ft Max. T
W AR
NIN
S IN
Pedestal mounting stand and chain tray recommended for gates over 20 ft.
otal Gate Length
Single Operator - 100 Ft Max. Gate Length
Dual Operators - 200 Ft Max. T
9210-065-H-2-13
1.4 Installation #1
Operator Mounted Directly on a Concrete Pad
Tip: Trace the base plate of the operator on a piece of masonite (Not provided) and make a template to help locate where the conduit runs will be positioned in the concrete pad.
18”
CA N/
CO
NF
AN OR
SI/ UL MS TO
5
CS
VEHI
CLA
SS
A C
LA
IED
TO
NO
MODE
SERI
AL
L
R GA
. 2 47
TE OP
533 82
HP
ERA
TOR
VO
LT S
AM
PS
X G
ATE
LOA
D Door
King
, Inc
., Ingl
PHA
SE
60 Hz ew ood,
CA
WA
RNING
MO
SE
RI
VIN
OU
G G
ATE
Op era and
fre te g
Do
no
Do per
no t all e o f pe ople
an ate t sta hile wn ate ow
ga nd i
ga er’s
on chil te.
n g te is
m anu ate
m
URY OR DE ly wh en g dre d o
pa ate
are th
or
CA
ATH a is ons in s igh y in ga te a rea ovin g.
al a nd s wal k th rou gh afe ty in ns.
The operator is heavy. Two persons are required when handling the operator during installation.
Electronic Box
1
2
emplate
20”
3
Caution: DO NOT lay the operator on it’s side or oil will leak out of the gear reducer.
Gain Access Inside
Operator
Remove the limit assembly guard.
Remove the 3 locknuts inside the electronic box to swing box open.
Gate
11.75”
10.75”
6.75”
Base Plate
Conduit
Area
Conduit
Area
Conduit
Area
DO NOT set anchor bolts in wet concrete. Sleeve anchors should be used after concrete has cured for greater flexibility in positioning the operator on the pad.
7.5”
11.25”
12”
16”
16.75”
20.5”
Concrete Pad
Pad depth is determined by soil conditions and local building codes. Minimum depth is 18 inches.
Reinforced concrete recommended.
9210-065-H-2-13
Concrete pad
MUST be level!
Concrete Pad
Wire Mesh
28”
Conduit
4”
1”
4”
23”
1”
Important:
Operator
MUST be parallel to gate!
1/2
To attach operator to concrete pad DoorKing recommends twelve (12)
1/2” x 3” sleeve anchors
(not supplied).
Conduit suggestions:
• High voltage conduit
• Low voltage access control device conduit
• Automatic exit loop conduit
• Reverse loop conduit
4” Minimum Above Ground
13
1.5 Installation #2
Operator Mounted on the Heavy-Duty
Pedestal Mounting Stand
The operator is heavy. Two persons are required when handling the operator during installation.
Caution: DO NOT lay the operator on it’s side or oil will leak out of the gear reducer.
1. Assemble and install the pedestal mounting stand kit (P/N
9200-135) on the concrete pad, then mount the operator to it.
Follow the instructions that came with the pedestal mounting stand kit for assembly of the stand.
2. Move the idler wheels to the lower operating position in the operator AFTER the operator has been installed on the pedestal mounting stand. See the previous page’s instructions to gain access inside the operator.
3. Install chain tray kit on the gate (See next page for details).
Gate
1”
4” 1.75”
Important:
Pedestal mounting stand MUST be parallel to gate!
4”
11.625”
DO NOT set anchor bolts in wet concrete. Sleeve anchors should be used after concrete has cured for greater flexibility in positioning the pedestal stand on the pad.
Concrete Pad
14
Pad depth is determined by soil conditions and local building codes.
Minimum depth is 18 inches.
Reinforced concrete recommended.
Concrete Pad
Wire Mesh
11.75”
Conduit
Area
15.75”
6.25”
39”
Pedestal mounting stand MUST be level!
1/2
4”
11.625”
4”
22”
To attach pedestal stand to concrete pad DoorKing recommends sixteen (16)
1/2” x 3” sleeve anchors
(not supplied).
Conduit suggestions:
• High voltage conduit
• Low voltage access control device conduit
• Automatic exit loop conduit
• Reverse loop conduit
Conduit
4” Minimum Above Ground
9210-065-H-2-13
1.5 Continued - Chain Tray Kit
Installing the Chain Tray Kit
A chain tray is recommended for gates longer than 20 ft. to support the weight of the chain. DoorKing offers a chain tray kit in sections to fit any length gate. (DoorKing P/N 2601-270 10 Ft. section)
Chain Tray
Supporting
Bracket
(Facing up)
10 Ft. Segment Carriage Bolts
Weep Hole
Chain Tray
Segments
Connection
10 Ft. Segment
Chain Tray
Supporting
Bracket
(Facing down)
1”
Tip: Chain tray supporting brackets can be mounted facing down (as shown on right), facing up or extended depending on the chain height and position. For further information, refer to instructions provided with the chain tray kit.
Note: The chain should sag at least one (1) inch per 10 feet of travel.
10.5”
Note: All gate types can have the chain tray installed on them, V-rail v-wheel ornamental is shown here.
Chain Tray
Supporting
Bracket
9210-065-H-2-13
Ground
4” Minimum Pad
15
1.6 Chain Installation
1 Operator MUST be parallel to gate!
2
Note: Be sure to follow all 3 guidelines. Installing the chain in any other manner will cause excessive noise, chain idler wheel wear and chain stretching.
Chain brackets MUST align with idler wheels so chain stays parallel to gate!
3 Chain brackets MUST be mounted so the chain remains the same height as it is on the idler wheels!
Directly on a Concrete Pad - #1 Factory Set Idler Wheels
Gate
2 2
Chain
Bracket
Idler Wheels
Chain
Bracket
Chain
Configuration
1
3 3
Idler
Wheels
14” 14” 14” 14”
4” Min.
Concrete Pad
Ground
Heavy-Duty Pedestal Mounting Stand - #2 Lower Idler Wheel Position
Gate
2 2
Chain
Bracket
Idler Wheels
Chain
Bracket
Chain
Configuration
1
16
Chain Bracket
Option 1
Option 2
Master Link
Chain
Nut
Chain
Bolt
Chain Bracket
Connect Chain Bracket to Gate.
Weld completely around bracket. Chain nut and chain bolt should not protrude past gate frame.
10.5”
3
10.5”
Idler
Wheels
10.5”
Ground
4” Min.
Connect Chain to Chain Bracket.
Connect chain to chain bolt with master link. Adjust the chain nuts to tighten the chain. The chain should sag no more than one (1) inch per 10 feet of travel.
Do not over tighten the chain.
3
10.5”
Concrete Pad
9210-065-H-2-13
1.7 Installation of Warning Signs
This DoorKing Slide Gate Operator is shipped with two warning signs. The purpose of the warning sign is to alert uninformed persons, and to remind persons familiar with the gate system, that a possible hazard exists so that appropriate action can be taken to avoid the hazard or to reduce exposure to the hazard. See page 9 for typical placement of signs.
• Permanently install the supplied warning signs in locations so
that the signs are visible by persons on both sides of the gate.
• Use appropriate hardware such as wood or sheet metal screws
(not supplied) to install the warning signs.
SECTION 2 - AC POWER TO OPERATOR(S)
Before attempting to connect any wiring to the operator, be sure that the circuit breaker in the electrical panel is in the OFF position. Permanent wiring must be installed to the operator as required by local electrical codes. It is recommended that a licensed electrical contractor perform this work.
Since building codes vary from city to city, we highly recommend that you check with your local building department prior to installing any permanent wiring to be sure that all wiring to the operator (both high and low voltage) complies with local code requirements.
THIS GATE OPERATOR MUST BE PROPERLY GROUNDED!!
Typical
Grounding
Sources
Electrical
Panel
Ground to existing electrical system.
Ground to metallic cold water pipe.
Ground
Wire
Grounding rod
10 feet in soil.
Ground
Wire
IMPORTANT: Ground wire shown without safety protection for clarity. Make sure ground wire is protected from being touched or electrical shock could occur!
2.1 High Voltage Wire Runs
The 9200 draws significant power and each operator should have a “Dedicated” circuit breaker at the power source. If power wiring is greater than the maximum distance shown, it is recommended that a service feeder be installed. When large gauge wire is used, a separate junction box must be installed for the operator connection. The wire table is based on stranded copper wire. Wire run calculations are based on the NEC recommended maximum 3% voltage drop on the power line, plus an additional 10% reduction in distance to allow for other losses in the system.
This table illustrates the high voltage AC power wire size and distance limitations for a single operator.
Never run low voltage rated wire insulation in the same conduit as high voltage rated wire insulation.
Single Phase
Three Phase
9210 Single 1 HP: 115 VAC
9210 Single 1 HP: 208 VAC
9210 Single 1 HP: 230 VAC
9220 Single 2 HP: 208 VAC
9220 Single 2 HP: 230 VAC
9245 Single 3 HP: 208 VAC
9245 Single 3 HP: 230 VAC
9210 Single 1 HP: 208 VAC
9210 Single 1 HP: 230 VAC
9220 Single 2 HP: 208 VAC
9220 Single 2 HP: 230 VAC
9230, 9240 Single 3 HP: 208 VAC
9230, 9240 Single 3 HP: 230 VAC
9235 Single 3 HP: 208 VAC
9235 Single 3 HP: 230 VAC
Amps
9.8
9.6
12.8
12.6
3.3
3.4
6.6
6.2
9.7
5.0
4.9
11.5
11.7
12.8
12.6
12 AWG
110
340
400
225
255
177
195
150
170
680
730
390
440
165
180
Wire Size / Max Distance in Feet
10 AWG
175
545
640
365
415
280
315
620
700
270
290
240
270
1090
1170
8 AWG
295
905
1070
610
690
465
525
1040
1170
450
490
400
450
1815
1950
6 AWG
440
1360
1605
915
1035
700
790
1560
1760
675
735
600
680
2720
2920
“Optional” Heater Installation Note: When installing a heater, refer to the “high voltage AC power wire size
and distance limitations” table on the instruction sheet with the heater kit for AC power wire run limitations.
9210-065-H-2-13 17
2.2 High Voltage Terminal Connection
• Route incoming AC power wire through the high voltage conduit and run wire in the operator electronic box as shown.
• Be sure wiring is installed in accordance with local codes. Be sure to color code all wiring.
• It is recommended that a surge suppressor be installed on the high voltage power lines to help protect the operator
and circuit board from surges and power fluctuations.
Dual Operators
• Dual operators (Primary/Secondary) require AC power to EACH operator.
AC Power AC Power
18
AC
POWER
OFF
DO NOT
power up and cycle the operator until the
“DIP-Switches” and the “Limit Switches” have been adjusted. Damage could occur to the gate and operator.
Hot Neu
Chassis
Ground
High Voltage
AC Input Wire
115 VAC Output
115 VAC
SINGLE Phase
White - Neutral
Black - 115 VAC Hot
Green - Chassis Ground
CA
N/
VEHI
CLA
MO
CO
NF
SI
CER
CS
SS
DE
L
OR
A C
/UL
-32
5
TIFI
ED
22.
CU
LA
SER
IAL
2 N
O. 2
47
GAT
E OP
533
82
ERA
HP
TO
R
VO
LTS
AM
PS
MA
X G
Doo
AT
E L
OA
D rKin g, In c., I ngle
AS
E wo od,
CA
WA
RNI
NG
SER
Ope and
Do
Re
op
Do pa th not ad
VING
IO rate free not
allow
sta
US IN
ga te o te ga nd le g nly te.
in ga ate
TE
JU
w he
an ldre te pa ov
RY
CA
OR n ga n to th or ing rea
pla y in
w alk l and safe
is i gate th
USE
ATH
are a rough ty ins truc tions
DANGER
HIGH VOLTAGE!
High
Voltage
AC Input
Wire
1
Hot Hot
115 VAC Output
Chassis
Ground
High Voltage
AC Input Wire
208/230 VAC
SINGLE Phase
Use only two legs of the incoming 3-phase power.
CAUTION
High Voltage AC input power
MUST MATCH the operator specifications or DAMAGE will occur and VOID the warranty!
High Voltage
Conduit
Keep wire clear of all moving parts.
2
Hot Hot Hot
115 VAC Output
3
Chassis
Ground
208/230 VAC
Remove the 3 locknuts inside the electronic box to swing box open.
High Voltage
AC Input Wire
External Power Disconnect Switch
A separate power disconnect switch may be needed in your area. Check local building codes before installation.
Recommended by DoorKing.
THREE Phase
Check polarity of three phase motor.
See page 22.
9210-065-H-2-13
SECTION 3 - ADJUSTMENTS
The switch settings and adjustments in this chapter should be made after your installation and wiring to the operator(s) is complete. Whenever any of the programming switches on the circuit board are changed, power must be shut-off, and then turned back on for the new setting to take effect.
3.1 Circuit Board Description and Adjustments
LEDs
Indicates that low voltage power is applied to the circuit board. Input LEDs should be OFF and will only illuminate when the input is activated. Limit LEDs will be on when the respective limit switch is activated.
AC Module
Adjustment
9220, 9230, 9235,
9240 and 9245 models
1 ft/s
Single Channel Loop Detector
See page 28.
9410
Dual Channel Loop Detector
See page 32.
9409
AC Module Dual
Adjustment
9235 models with mechanical disc brake.
1495-010
P2
HIGH SPEED
ADJUST
.5 ft/s 1.5 ft/s
0 ft/s 2 ft/s SLOW SPEED
ADJUST
P1
Min Max
Speed
See page 24.
Mechanical
Disc Brake
Plug P8
9235 and 9245 models ONLY
Reverse Loop Port
4404-010
4404-010
Limit Switch Plug P2
Power LED
Exit Loop Port See page 24.
DIP-Switches
Set the DIP-switches on the circuit board to the desired setting. See switch descriptions on next 2 pages.
4 23 1 8 67 45 23 1
ON
SW 2 is Upside-Down on Board SW 1 is Upside-Down on Board
ON
4 8 67 45 23 1
Motor
Plug P6
Input LED
23 1
ON ON
Self-Test
Self-test (when turned on)
SW 2, switch 1.
4 23 1
UL 325 Terminal
ON
SW 2 is Upside-Down on Board
Input LEDs
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Inherent
Reverse
Sensors
Adjust reversing sensitivity for open and close directions.
Full counter clockwise for minimum sensitivity, full clockwise for maximum sensitivity.
See page 23.
Min
Max
Sensitivity
Dry Relay Contact
Dry relay contacts
(terminals 11-12) can be set for Normally Open
(NO) or Normally Closed
(NC) operation by placing the relay shorting bar on the
N.O. or N.C. pins respectively.
SW 1, switches 4 and 5 must be set to control relay. See next 2 pages for descriptions.
8 67 45 1
ON
23
SW 1 is Upside-Down on Board
CAUTION
Do not run self-test with the operator connected to the gate.
The drive chain MUST be disconnected before running the self-test. This feature is designed for bench testing ONLY.
Auto-Close Timer
Auto-close timer (when turned on) SW 1, switch 2.
Adjust from 1 second
(full counter-clockwise) to approximately 23 seconds
(full clockwise).
78
1 23
56 34 1
ON
2
SW 1 is Upside-Down on Board
9210-065-H-2-13 19
3.2 DIP-Switch SW 1 and SW 2 Settings
The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
4 23 1 8 67 45 23 1
Left 4 Switches - SW 2
SW 2 is Upside-Down on Circuit Board.
ON
Typical
Settings ON
SW 1 - Right 8 Switches
SW 1 is Upside-Down on Circuit Board.
Switch Function Setting
SW 1 - Right 8 Switches
Description
1
Changes the direction the operator will open/close the gate.
Opening direction using OFF setting.
Opening direction using ON setting.
Opening direction using ON setting.
Opening direction using OFF setting.
20
2
3
Auto-Close
Timer
Exit Loop Port
Output
Full Open Input
Jumper
Wire
Needed
OFF
ON
OFF
4 and 5
Relay Activation and
LED Indicator
Light Activation
6
7
Warn Before
Operate
Reverses Gate
ON
4-OFF 5-OFF
4-OFF 5-ON
4-ON 5-OFF
4-ON 5-ON
OFF
ON
OFF
8
Stops Gate
Quick-Close
Timer Override
ON
OFF
ON
Factory Set Configuration Lower Configuration
Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
The output wired to terminal #4 becomes the output from the loop detector installed in the EXIT loop port. Plug-in loop detector required for “OFF” function.
Normal Setting. Terminal #4 is a normal full open input for a single gate operator.
Relay activates and LED is ON when the gate is fully open.
Relay activates and LED is ON when the gate is not closed.
Relay activates and LED is ON when the gate is opening and open.
Relay activates and LED is ON when the gate is opening and closing.
Normal Setting. No sound.
Internal alarm will sound before gate starts and throughout gate’s cycle.
Normal Setting. Input to terminal #6 and/or reverse loops will REVERSE gate during CLOSE cycle.
Input to terminal #6 and/or reverse loops will STOP gate during CLOSE cycle.
Normal Setting. Timer will function normally.
Opening gate will stop and begin to close as soon as all reversing inputs (Reverse loops, photo sensors) are cleared regardless of the distance the gate has opened.
Switch Function
1
2
3
4
Self-Test
Gate Opens
Uphill
Gate Opens
Downhill
Spare
Setting
SW 2 - Left 4 Switches
Description
OFF
ON
Normal Setting. Normal gate operation.
Self-test mode. Operator MUST be disconnected from gate to run self-test.
OFF
ON
OFF
ON
Normal Setting. Normal gate operation.
MUST be ON if gate opens UPHILL.
Normal Setting. Normal gate operation.
MUST be ON if gate opens DOWNHILL.
OFF Leave in the OFF position.
9210-065-H-2-13
3.2 Continued
The two DIP-switches located on the circuit board (Upside-Down ) are used to program the operator to operate in various modes and to turn on or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
8
Switch Definitions
Typical Settings
67 45 23 1
ON
SW 1 - Right 8 Switches
SW 1 is Upside-Down on Circuit Board.
Switch 1 Motor direction switch - Must OPEN the gate upon initial AC power up and open command. If the open command begins to close the gate, turn AC power off and reverse this switch.
Switch 2 Turns the auto-close timer on or off. Can be adjusted from 1 to 23 seconds to close gate.
Switch 3 A device wired to terminal #4 (Switch 3 ON) is a normal full open input. The output wired to terminal #4 (Switch 3
OFF) becomes the output of a plug-in loop detector that is installed in the EXIT loop port of the circuit board (Which must be installed for the “OFF” setting to function). A jumper wire is needed to open and close gate(s). Terminal #4 jumpered to #5 is used for partially opening an automatic exit loop using a single channel plug-in loop detector for a single gate operator (Page
28) OR terminal #4 jumpered to #2 will fully open bi-parting gates using a dual channel plug-in loop detector (Page 32).
Switches 4-5 These work in conjunction with each other and determine when the relay on the board will be activated. This relay can be used as a switch for various functions such as illuminating a warning light when the gate is moving, or turning on a green light when the gate is full open. If a magnetic lock is used with the gate operator, these switches must be set for magnetic lock operation which limits the relay to activate only when the gate is opening and full open.
Switch 6 Warn Before Operate, When set to the ON position, the internal alarm in the operator will start sounding 2-3 seconds prior to the gate starting and continue throughout the gate’s cycle.
Switch 7 Determines if an input to terminal #6 (Photo Sensors) AND/OR reverse loops will reverse OR stop a CLOSING gate.
A tailgating vehicle can activate terminal #6 (Photo sensors) and/or reverse loops while the gate is in the closing cycle from the previous vehicle’s authorized entry:
If switch 7 is turned OFF (Reverse), the closing gate that gets activated by a tailgating vehicle will reverse back to the open position, possibly allowing the tailgating vehicle unauthorized entry while the gate is reversing back to the open position.
If switch 7 is turned ON (Stop), the closing gate that gets activated by a tailgating vehicle will stop, partially or completely blocking the pathway, NOT allowing the tailgating vehicle to enter without proper authorization. The gate will not move until all sensors are clear, usually forcing the tailgating vehicle that activated the sensors to back away from the gate. The gate will then continue until closed, helping prevent the tailgating vehicle from unauthorized entry.
Switch 8 Turning the quick-close feature on will cause the auto close timer to close the gate after 1 second, regardless of the setting of the auto close timer potentiometer. This will also cause an opening gate to stop and reverse when the reverse loops and/or photo sensors are cleared. This feature, along with turning switch 7 ON above, is useful to help prevent tailgating vehicles from unauthorized entry.
Typical Settings
4 23 1
ON
SW 2 - Left 4 Switches
SW 2 is Upside-Down on Circuit Board.
Switch 1 This switch is a self-test feature that checks various functions of the circuit board and is used for bench test only.
Do not run this test with the operator connected to the gate.
Switch 2 Set to the OFF position for normal operation. Set to the ON position if gate OPENS in an UPHILL direction.
Switch 3 Set to the OFF position for normal operation. Set to the ON position if gate OPENS in an DOWNHILL direction.
Switch 4 Spare switch, leave in the OFF position.
9210-065-H-2-13 21
22
3.3 Limit Switches
A Limit
Switch
A1
Slow-Down
Limit
(3/4 inch adjustment
ONLY)
Partial Open
Magnetic
Pick-up
Sensor
Adjustment
C1
Slow-Down
Limit
(3/4 inch adjustment
ONLY)
C Limit
Switch
B
A1
C1
Check the polarity of “Three Phase” operator ONLY: Position the gate half way open. Give open command and while gate is opening, activate the appropriate limit switch with your finger. Gate should STOP. If it does not, activate the other limit switch. If this STOPS the gate, AC power wires must be changed (Reverse the connection of any 2 wires and re-check limits).
Adjust Limit Nuts
Important: Turn power OFF and set AC module (On select models) to maximum speed before adjusting limit nuts!
1 Push and hold the lock plate down where shown to adjust the
Open and Close limit nuts.
2 After adjusting the limit nuts, be sure that the lock-plate is engaged in the slots on the limit nuts to prevent them from rotating.
3 On select 9200 models, the slow-down limit assembly will move up or down 3/4 inch. DO NOT remove the slow-down limit assembly from the 3/4 inch slot and re-attach it in the partial open adjustment rail to gain further adjustment. This will cause mechanical damage to the switch assembly when the operator is activated.
4 Turn power on and activate the gate operator.
5 Re-adjust the limit nuts as necessary for full-open and full-close gate travel. After you are satisified with the gate limit settings, the AC module (On select models) can then be adjusted to personal preference (See page 24).
Middle Limit Nut
Magnet - Align with pick-up sensor
B Magnetic Pick-Up Sensor
Partial Open Feature:
When using the partial open feature, the operator’s access control device must be connected to terminal
#5 . Adjust the middle limit nut and magnetic pick-up sensor assembly to the gate’s desired stopping position. Be sure to align the magnet (Recessed in the limit nut) with the magnetic pick-up sensor.
Limit LEDs
A
B
4
C
ON
23 1
4404-010
8 67 45
ON
23 1
Note: If limit plug is not connected to the circuit board and
AC power is turned on, alarm will sound and operator will
NOT function.
Main Terminal Partial Open Connection
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
9210-065-H-2-13
3.4 Inherent Reverse Sensors Adjustment
This vehicular gate operator is equipped with an inherent adjustable reversing sensor (Type A) used as the primary entrapment protection system according to UL 325 standards. The gate will reverse direction after “physically” encountering an
obstruction in either the opening or closing gate cycle.
If the Auto-Close Timer (DIP-switch SW 1, switch 2) is ON and the gate physically encounters an obstruction during the
CLOSING cycle, it will reverse to the open position and HOLD the gate at this position (Soft shutdown condition). Another input command is needed before the gate will reset and close again.
If the Partial Open Feature is being used and the gate physically encounters an obstruction during the CLOSING cycle, the gate will only reverse to the FULL open limit switch setting and NOT the partial open setting.
For the reverse system to function correctly, the gate must be properly installed and work freely in both directions and the limit switches must be properly adjusted before adjusting these sensors. The ideal adjustment will allow the operator to move the gate through its entire travel cycle without reversing, but will reverse upon contact with an obstruction with no more than 40
Lbs of force. This force can be measured with a gate scale, P/N 2600-225. Min
1
2
Momentarily jumper a wire across terminals 1 and 4 to OPEN the gate.
After opening gate reaches full speed, slowly rotate the OPEN reverse sensor clockwise until the LED lights up and gate reverses direction. Rotate the OPEN reverse sensor back counter-clockwise approximately 1/8 turn to decrease the sensitivity (LED will turn off). The gate will assume a soft shutdown so momentarily jumper a wire across terminals 1 and 4 to cycle the operator.
Max
Sensitivity
3 Momentarily jumper a wire across terminals 1 and 4 to CLOSE the gate.
LED
4 After closing gate reaches full speed, slowly rotate the CLOSE reverse sensor clockwise until the
LED lights up and the gate reverses direction. Rotate the CLOSE reverse sensor back counter-
5 clockwise approximately 1/8 turn to decrease the sensitivity (LED will turn off). The gate will assume a soft shutdown so momentarily jumper a wire across terminals 1 and 4 to cycle the operator.
Cycle the gate a few times to be sure that it cycles completely. The current sensor may
LED
Note: Each operator must be need to be adjusted if gate will not reverse properly (See 3.5 below) individually adjusted if dual
Test the operator reversing sensitivity:
operators have been installed.
Place an immobile object along the gate path, allowing the gate to strike it while in the open and close cycles. The gate must and repeat this testing until the correct sensitivity has been achieved in BOTH directions. The operator will assume a soft shutdown after striking and reversing the gate which will require a momentary jumper wire across terminals 1 and 4 to cycle the operator again.
3.5 Current Sensor Adjustment
This vehicular gate operator uses a current sensing device to detect any obstructions in the path of the opening or closing gate.
The current sensor uses a sensing coil with a given number of turns through it to monitor the current flow into the operator.
Each time the wire passes through the coil, it is considered a turn. The number of turns through the sensing coil is dependant on the operating voltage of the operator, the speed of the gate and the weight of the gate.
In general, light weight gates may require additional turns of wire through the current sensor, while heavier gates may require less turns. In addition, the speed of the gate can affect how the current sensor works. Gates running at a higher speed may require less turns of wire through the sensor. CAUTION – HIGH VOLTAGE: Be sure power is turned OFF before changing the number of wire turns to the current sensor. If you are setting the reverse sensors (section 3.4 above) and reach the full sensitive position without activating the reversing function, add an additional turn of wire through the current sensor. If you are decreasing the sensitivity and the gate will not run properly, reduce the number of turns through the current sensor.
Sample
Turns
1
1 Turn
2
2 Turns
5
5 Turns
6
6 Turns
Voltage and Phase Turns
115 Single Phase
208 Single Phase
230 Single Phase
208 Three Phase
230 Three Phase
1
2
2
5
6
9210-065-H-2-13 23
3.6 AC Module Adjustment
The 9220, 9230, 9235, 9240 and 9245 models are equipped with an AC module that allows you to adjust the speed of the gate from 0 to 2 feet per second. To adjust the speed, simply rotate the speed control knob clockwise to increase the gate speed, or counter-clockwise to decrease the gate speed. The digital readout on the AC module will display the gate speed.
L1 L2 L3 BB+
Min Max
Speed
1 ft/s
.5 ft/s 1.5 ft/s
EPM
1. 0
0 ft/s 2 ft/s
Mode
Min Max
Speed
1 ft/s
.5 ft/s 1.5 ft/s
Mode
EPM
L1 L2/N
PE
BB+
1. 6
Min Max
Speed
1 ft/s
.5 ft/s 1.5 ft/s
EPM
L1 L2
2. 0
L3
Mode
0 ft/s 2 ft/s 0 ft/s 2 ft/s
24
SCM series basic I/O control
SCM series basic I/O control
SCF series basic I/O control
Min Max
Speed
2 ft/s
1 ft/s 3 ft/s T1
U
T2 T3
9235 Models with AC Module Dual Adjustment and Mechanical Disc Brake
There are 2 speed adjustments that must be adjusted on the 9235. The high speed adjust (Emergency Close) is designed to
0 ft/s 4 ft/s close an open gate as quick as possible.
All secondary entrapment protection devices and reversing sensors
9235 Only
WILL NOT WORK during the high speed closing operation!
The slow speed adjust is for normal gate operation.
The 9235 models are equipped with a mechanical disc brake. It is automatically controlled by the AC module and needs NO adjustment. Note: There is a manual release lock on the disc brake that must be unlocked before the gate can be manually operated (See section 6.3 manual gate operation on page 35 for further information).
DANGER
Gate WILL NOT stop after the Emergency
Close is activated until gate is closed!
AC Module
Dual Adjustment
Emergency Close Adjustment:
Adjust the high speed from 0 to 6 feet per second. Closing device must be connected to P2 terminal on 1495 circuit board.
Important: Closing device must be far enough from the gate so that the user is prevented from coming in contact with the gate while operating the device.
Outdoor or easily accessible closing device should have a security feature to prevent unauthorized use.
EMERGENCY
CLOSE
Stand-Alone
Push-Button
Normal Gate Adjustment:
Adjust the slow speed from
0 to 4 feet per second. Opening device must be connected to 4404 main circuit board (See page 30).
1495-010
P2
Min Max
Speed
HIGH SPEED
ADJUST
P1
SLOW SPEED
ADJUST
To adjust the speed, rotate each speed control potentiometer clockwise to increase the gate speed, or counter-clockwise to decrease the gate speed. The digital readout on the AC module will display EITHER high speed OR slow speed, which ever open/close device has been activated.
L1
EPM
Mode
L2
2. 0
L3
SCF series basic I/O control
T1
U
T2
V
T3
W BB+
10 HP AC Module
9210-065-H-2-13
SECTION 4 - ENTRAPMENT AND SAFETY PROTECTION
Secondary Entrapment Protection Devices:
In addition to the inherent reversing sensor system, the 9200 Series has a 6-pin UL 325 terminal for the connection of photo sensors-Type B1 and reversing edges-Type B2 secondary entrapment protection devices required by UL 325 standards. Entrapment protection devices must
be installed to reduce the risk of injury. Install these devices where the risk of entrapment or obstruction exists while the gate is moving.
The 9200 Series offers numerous options to meet your specific needs. The next 2 pages show wiring and typical positioning of the entrapment protection devices but specific installations will vary.
Note: Secondary entrapment protection devices will open the gate to the “Partial Open” setting when the opening device is connected to main terminal #5 (See page 30 for opening device wiring information).
115 VAC
4.1 UL 325 Terminal Description
Convenience
Outlets
6-Pin UL 325 Terminal
Secondary Entrapment Protection
Device Connection
6 5 4 3 2 1
1
4
2
1
4
3
2
1
4
3
2
3
4404-010
4 23 1
ON
8 67 45 23 1
ON
Note: The 6-pin terminal can be unplugged from circuit board for easy wire connections.
All inputs are normally open (NO).
44
04
-010
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1
OPEN Entrapment Sensor (Photo Sensor): Obstructed opening-direction photo beam will stop the gate during the
opening-direction only. Gate will resume the open cycle when the obstructed photo beam has been cleared.
Wall / Fence
Opening-Direction Photo Beam
Entrapment Area
Closed Gate
2
CLOSE Entrapment Sensor (Photo Sensor): Obstructed closing-direction photo beam will stop the gate during the
closing-direction only. Gate will resume the close cycle when the obstructed photo beam has been cleared.
Wall / Fence
Entrapment Area
Closing-Direction Photo Beam
Closed Gate
3
OPEN Contact Sensor (Reversing Edge(s)): Obstructed opening-direction reversing edge(s) will stop, then reverse the gate to the close position during the opening-direction only.
Wall / Fence
Filler Post if necessary
Closed Gate opening input will cycle the gate again. Note: If the gate is
opening by a time clock and an opening-direction reversing
edge gets obstructed, the gate will return to the closed
Opening-Direction Reversing Edges
Entrapment Area
position and another input (automatic exit loop, reverse loop. etc.) is needed to cycle the gate open
again.
Gate Support Post if Installed
4 CLOSE Contact Sensor (Reversing Edge): Obstructed closing-direction reversing edge will stop, then reverse the gate to the open position, during the closing-direction only.
Entrapment Area
Wall / Fence
Closing-Direction Reverse Edge
Closed Gate automatically close the gate (if it is turned on). If the
closing-direction reverse edge is activated a second time prior to the gate reaching the
close position, the operator will stop and enter a soft shutdown condition (See page 34).
position and the opening-direction revering edge gets obstructed, the gate will stop and enter a soft shutdown condition (See page 34).
5
&
6
Common terminals for all the secondary entrapment protection device inputs.
9210-065-H-2-13 25
4.2 Secondary Entrapment Protection Device Locations
Typical UL Photo Sensor mounting height and distance away from gate.
Secure Side
Inside Property
5” or Less
5” or Less
Non-Secure Side
Outside Property
If the distance between the gate and wall is greater than 2 1/4”.
Filler Post or Barrier
Reversing Edge (Open Contact Sensor)
Wall
21”
Typical
Photo sensors may be installed on either side of gate frame.
A filler post or barrier may need to be installed between the gate and wall area to reduce the distance to 2 1/4” or less.
A reversing edge should be installed on the post or barrier for safety (See page 8 for more information).
Photo Sensors (With Filler Post and Reverse Edge) Sample Setup
Closing-Direction Photo Beam
Wall
Filler Post with Opening-Direction Reversing Edge (If necessary, see above)
Closed Gate
Opening-Direction Photo Beam
Closing-direction photo sensors wired to UL 325 terminal.
4 23 1
ON
8 67 45 23 1
ON
26
6-Pin
UL 325
Terminal
Wiring
6 5 4 3 2 1
Normally Open
Normally Open
Normally Open
Common
Common
Common
IF the closing-direction photo sensor is wired to the UL 325 terminal, a closing-direction photo beam that gets obstructed will STOP the gate, then resume closing the gate when the obstructed photo beam has been cleared.
Photo Sensor Power Note: Photo sensors can be powered by the built-in convenience outlets located on the operator (See previous page).
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Normally Open
Common
8 7 6 45 23 1
ON
SW 1, switch 7
MUST be OFF.
SW 1 is Upside-Down on Board
IF the closing-direction photo sensor is wired to the #6 main terminal, a closing-direction photo beam that gets obstructed will REVERSE the gate back to the open position.
9210-065-H-2-13
Wireless Reverse Edge Sample Setup - Single Receiver
Normally Open
Filler Post Note: Install reversing edges on all the gate support posts or filler post in this area
(e.g. cantilever gate installations, See below).
Edge
Transmitter
9 V battery operated transmitter mounted on gate.
Common
Normally Open
Wall
Opening-Direction
Reversing Edge
Filler Post
(If necessary)
Opening-Direction Reversing Edge (If filler post is used).
Closed Gate
6-Pin UL 325
Terminal Wiring
When either direction reversing edge get obstructed, the gate will STOP and reverse direction.
4 23 1
ON
Normally Open
Normally Open
Common
8 67 45 23
ON
24 VAC Receiver
Place receiver in operator.
Closing-
Direction
Reversing
Edge
Antenna mounted outside operator cover.
Coax Antenna Kit
P/N 1514-073
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
20-Pin
Main
Terminal
To #1 Com
Wireless Note: Refer to the instruction sheet that comes with the receiver/transmitter for more specific wiring and mounting instructions.
To #3 24 Volt - Power is limited to 250 mamps.
Photo Sensor and Wireless Reverse Edge Sample Setup
Photo Sensor Power Note: Photo sensors can be powered by the built-in convenience outlets located on the operator (See page 25).
Install Opening-Direction reverse edges on the gate support post(s) in this area.
Cantilever Gate
Closing-
Direction
Reversing
Edge
Opening-Direction Photo Beam
4404-101
4 23 1 8 67 45
ON 9 V battery operated transmitter mounted on gate.
ON
23 1
Edge
Transmitter
6 5 4 3 2 1
6-Pin
UL 325
Terminal
Wiring
Common
Normally Open
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
To #3 24 Volt - Power is limited to 250 mamps.
To #1 Com
20-Pin
Main
Terminal
Antenna mounted outside operator cover.
When a reversing edge gets obstructed, the gate will STOP and reverse direction. When a photo beam gets obstructed the gate will
STOP, then continue in the same direction after obstructed photo beam has been cleared until the gate cycle is complete.
Normally Open
Common
24 VAC Receiver
Place receiver in operator.
Coax Antenna Kit
P/N 1514-073
Wireless Note: Refer to the instruction sheet that comes with the receiver/transmitter for more specific wiring and mounting instructions.
9210-065-H-2-13
Common
27
4.3 Loop Detector Wiring
To help protect the operator from accidentally closing on vehicles in the gate’s path, DoorKing highly recommends that loops and loop detectors be installed. Loops are laid underneath, cut into asphalt or concrete driveways or buried beneath gravel and earth driveways. A loop detection system will sense a vehicle like a metal detector and send a signal to the gate operator preventing the gate from automatically opening or closing on a vehicle when it is in the gate’s path. DoorKing recommends that a licensed installer perform this work.
DoorKing offers a free “Loop and Loop-Detectors
Information Manual” PDF located at DoorKing’s web site for more information. www.dkaccess.com
Reverse Loops
Reverse loops are placed on each side of the gate to prevent the gate from closing on a vehicle in the gate’s path. They will stop or reverse the cycling of the gate while a vehicle is in or near the gate’s pathway.
CA
CO
AN
N/CS
VE CU
CLA SS
MO DE
SER IAL
VO LTS
NF
SI/U
IED
22.2
LAR
NO
AM
MA PS
X G ATE
AD Doo ing
MS
TO
GA
TE O
, In c., lew
PERA
HP
AS PH
Ing
60 H
TO
WA
RN
ING
MO
SERI and te g or o t allow ople path
Rea
OUS
fre f pe t stan hile
GA
INJ d in
TE CA
URY hen en t te p er’s ovin
OR te a ruc lay
or al a nd s
N C
DE tion wal k th ty in
AU
ATH rou stru ctio
28 ference.
PVC Conduit
Reverse Loop
A ference.
Reverse loop lead-in wires are twisted approx.
6 twists per foot and are wired in series.
Note: SW 1, switch 7 must be set for the reverse loops.
See page 21 for more information about SW 1, switch 7 ON/OFF options.
8 7 6 45 23 1
SW 1 is Upside-Down on Board
ON
Loop Lead In Wires
Reverse Loop
Loop Lead In Wire ference.
Loop
Automatic Exit
DoorKing
Plug-in
Loop Detectors
Single Channel
Automatic Exit Loop
Automatically opens the gate for exiting vehicles without having to use a transmitter or keypad. The exit loop can be placed a minimum of 4 feet away from the reverse loop or far enough away from the gate so the gate has started opening or even completely opened by the time you drive up to it (Free exit).
A
9410
Single Channel
B
9410
PVC Conduit
B
Exit loop lead-in wires are twisted approx. 6 twists per foot.
SW 1, switch 3 must be ON to
FULLY open gate
8
(Normal function).
67 45 3 2 1
SW 1 is Upside-Down on Board
ON
Note: The plug-in exit loop detector can be wired to partially open the gate if SW 1, switch 3 is turned OFF. A jumper wire must be connected from terminal #4 to terminal
#5 (See next page for more information).
8 67 45 3 2 1
4404
4 23 1
ON
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
8 67 45 23 1
ON
Note: Loop detector wiring is shown for
DoorKing plug-in loop detector P/N
9410-010 (Single
Channel). If other loop detectors are used, refer to the installation instructions supplied with those detectors for wiring and separate power instructions.
SW 1 is Upside-Down on Board
ON
Exit Loop Partial Open
9210-065-H-2-13
SECTION 5 - MAIN TERMINAL WIRING
5.1 Main Terminal Description
4404
#2 - Jumper Wire - SW 1, switch 3 OFF (Dual Operators Full Open)
#1 - Jumper Wire - SW 1, switch 3 OFF (Single Operator Exit Loop Partial Open)
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Auxiliary Common
Terminal
Connect any low voltage common wire to these 2 terminals.
DANGER
HIGH VOLTAGE!
16
17
Used in conjunction with the circuit board inherent reversing sensors. See page
23 for further information.
15 14
DoorKing’s Remote alarm reset station can be connected. See page 31 for wiring.
It MUST be mounted in the line-of-sight of the gate operator.
(DoorKing P/N 1404-080)
11
12
Operation of relay is dependent on setting of SW 1, switches 4 and 5.
See page 20 and 21 for DIP-switch function descriptions.
8 67 45 23
SW 1 is Upside-Down on Board
ON
1
Relay contacts can be set for
Normally Open (NO) or Normally
Closed (NC) operation.
Contact rating is 1 amp maximum at 24-volts DC.
6
4
5
• SW 1, switch 3 is ON, terminal #4 functions as a normal FULL open input. (Normal Setting). Single operator use ONLY.
• SW 1, switch 3 is OFF, input to terminal #4
8 67 45 3 2 becomes the output from a plug-in loop detector installed in the EXIT loop port of the circuit board. A jumper wire is needed to open SW 1 is Upside-Down on Board and close the gate(s) for these applications:
ON
1
#1 Terminal #4 jumpered to terminal #5 will PARTIALLY open an automatic exit loop using a single channel plug-in loop detector installed in the exit loop port when using a single gate operator.
#2 Terminal #4 jumpered to terminal #2 will FULLY open bi-parting gates using a dual channel plug-in loop detector installed in the exit loop port when using dual gate operators.
For long gate applications. An input device connected to terminal #5 will open the gate to the partial open setting,
See page 22 for more information.
This input ONLY fuctions when gate is fully opened or in the
closing cycle.
• When gate is closing: SW 1, switch 7 is OFF, an input to terminal #6 (eg: photo beam gets obstructed) will reverse and open the gate.
Note: If the auto-close timer is ON, when gate reaches the open position, timer will
8 7 6 45 23
not close the gate. Another input command is needed to reset and close the gate.
SW 1 is Upside-Down on Board
1
ON
• When gate is closing: SW 1, switch 7 is ON, an input to terminal #6 (eg: photo beam gets obstructed) will stop the gate, then continue to close the gate when input is clear
(Used to help prevent tailgating vehicles from unauthorized enrty). See page 21 for more information.
9210-065-H-2-13 29
5.2 Control Wiring for Single/Primary Operator
Important: Controls must be far enough from the gate so that the user is prevented from coming in contact with the gate while operating the controls. Outdoor or easily accessible controls should have a security feature to prevent unauthorized use.
4404
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Auxiliary Common
Terminal
Connect any common wire to these 2 terminals.
Note: All stand-alone and telephone entry devices must use a separate power source.
8 67 45 3 2 1
ON
SW 1 is Upside-Down on Board
SW 1, Switch 3 MUST be ON except for dual operators or exit loop partial open applications.
Telephone Entry
Key Switch
Stand-Alone
Keypad
Red Full Open
Green Close
White Com
3-Button Control Station
DoorKing ONLY
9235 Model Operator
1495-010
P2
HIGH SPEED
ADJUST
EMERGENCY
CLOSE
Stand-Alone
Push-Button P1
SLOW SPEED
ADJUST
Com
“Optional” REVERSE GATE for Closing Direction
Photo Sensors
Functions ONLY during gate closing cycle.
8 7 6 45 23 1
ON
SW 1 is Upside-Down on Board
SW 1, switch 7: After photo sensor beam gets obstructed:
OFF Setting - REVERSES GATE.
ON Setting - Stops gate then continues closing when gate is clear (Same function as UL 325 terminal #2).
Note: The ON setting is used to help prevent tailgating but the photo sensor should be wired to the UL 325 terminal #2 when the “stop gate” function is desired, see page 26 for more information.
To #4 or #5
30
Stand-Alone
Card Reader
#1-Com
#2-Fully opens gate.
Safety Opening Device
#1-Com
#2 or #5-Relay
#3-24 volt
250 mamp. max.
3-Wire Radio Receiver
#1-24 Volt Power Com
#1-Relay Com
#2 or #5-Relay
#3-24 Volt Power
4-Wire Radio Receiver
#5 Terminal Note: Any opening device connected to terminal #5 will open the gate to the partial open setting. Secondary entrapment protection devices will also open the gate to the partial open setting. If the
Inherent Reverse Sensor gets activated during the close cycle, it will always fully open the gate.
9210-065-H-2-13
5.3 Auxiliary Device Wiring
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Blue Alarm Reset Terminal
Red Alarm Output Terminal
White Common Terminal
Remote Alarm Reset Station
(DoorKing P/N 1404-080 Only)
MUST be mounted in the line-of-sight of the gate operator.
Gate Tracker DoorKing Access Control System (Model 1833, 1835, 1837 or
1838) tracker system can be connected. This system can keep track of gate operator cycle count, shorted inputs, loop detector problems, any forced entry attempts, if the gate has struck anything during the open or close cycle, power interruptions, etc. For more detailed information refer to the Tracker
Installation and Wiring Manual, DoorKing P/N 2351-010.
Terminal #2 (Full open) or #5 (Partial open) required only if the tracker board will activate the gate operator. Refer to the manual 2351-065 for detailed information.
9210-065-H-2-13
Gate Tracker
(Quad Box Shown)
31
32
5.4 Bi-Parting Gates Wiring - Dual Gate Operators
1 2 3 4 5 6 UL 325
• Requires AC power to each operator.
• Both operator DIP-switches must be set.
Primary Operator
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
• Connect all control devices, auxiliary
devices and loops to the primary
operator only.
DoorKing offers a free “Loop and Loop-Detectors
Information Manual” PDF located at Doorking’s web site for more information. www.dkaccess.com
Green to primary operator chassis ground.
3-Wire Receiver
Com
Relay
B
Reverse
Loop
Reverse
Loop
Automatic
Exit Loop
A
Loop Detector
When using plug-in loop detector
Connect a jumper from #4 to #2:
8 fully opens gates.
67 45 3 2 1
ON
SW 1 is Upside-Down on Board
Primary SW 1, switch 3 must be OFF.
Com to #1
Normally Open to #6
A
24 Volt Power
250 mamp. max.
PVC Conduit
Reverse loop lead-in wires are twisted approx.
6 twists per foot and are wired in series.
Note: 4-wire radio receiver, or any other opening devices get wired to primary operator
ONLY, as shown on page 30.
PVC Conduit
Dual Channel
9409
Plug the DoorKing DUAL channel loop detector into Primary Operator’s
Exit Loop Port.
B
To Open Photo #1
To Close Photo #2
To Open Edge #3 To Open Edge #3
To Common #5
Fence
Opening Non-Contact Sensor
Opening Contact Sensor
Gate
Primary
Operator
Closing Non-Contact Sensor
Opening Contact Sensor
Gate
Secondary
Operator
To Open Edge #3
• Separate power source for photo sensors.
See page 25 for more information.
Exit loop lead-in wires are twisted approx. 6 twists per foot.
Secondary Entrapment
Protection Devices for Bi-Parting Gates
Fence
Filler Post if necessary (See page 8 for more info).
Opening Non-Contact Sensor
To Open Photo #1
To Common #5
1 2 3 4 5 6 UL 325
Secondary Operator
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Note: Secondary operator ‘s
DIP-switches MUST be set for the dual operators to cycle correctly. See pages 20 and 21 for more information about dual operator DIP-switch settings.
Green to secondary operator chassis ground.
9210-065-H-2-13
SECTION 6 - OPERATING INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
WARNING - To reduce the risk of injury or death:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. Never let children operate or play with gate controls. Keep the remote control away from children.
3. Always keep people and objects away from gate. NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE .
4. Test the operator monthly. The gate MUST reverse on contact with a rigid object or stop or reverse when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of injury or death.
5. Use the emergency release only when the gate is not moving and power has been shut-off.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner's manual. Have a qualified service person make repairs to gate hardware.
7. The entrance is for vehicles only. Pedestrians must use separate entrance.
8. .
6.1 AC Power and Reset Button
(
s
)
Motor Reset Button
On select 1 HP models.
Used to reset the motor when weight overload or overheating occurs.
Press firmly to reset.
R E S E T
CO
CAN/C
VEHI
CLA
DE
SER
IA
NF
SA
OR
CUL
SS
L
L
L-3
2.2
TO
IED
TO
NO
AR
GA
. 24
7
TE OPE
RA
HP
5338
2
TOR
PS
60
X G
AT
Door
E L
Ki ng,
D
Inc.
, Ing
AS
Hz
E lewood
, CA
WA
RNING
MO
VIN
Ope and
Do or o
Do rate pera
no whi
ga t sta te o te g ate nd le g in
Rea d owne r’s m
INJ nly hild nd
.
w e a
ob stru
to p lay ate
is ga
m te p anua ov ing
. l and
sa
AN
OR ction
in g
DE
is i ate s.
US
E
AT
H n s ight
are a alk
thr oug h fety tru
AC
POWER
Unlock the power switch cover and open to access the main power, and the operator reset button.
Reset Button - Used to turn off the entrapment alarm and to reset the operator after a HARD shutdown has occurred.
Alarm Siren
AC Power Switch - Powers the operator
ON (toggle up) or OFF (toggle down).
OFF
33 9210-065-H-2-13
6.2 Shutdown Conditions
Under various entrapment conditions the operator will assume either a soft or hard (alarm) shutdown. To determine what type of reset action is required, you will need to understand how the different entrapment conditions affect the gate operator.
Soft Shutdown
This occurs in various situations where the inherent or secondary entrapment protection devices have been activated. In a soft shutdown condition, the operator will not respond to any input that was present when the entrapment protection device sensed an obstruction. If the gate stops at the open position, the operator will not respond to the automatic close timer.
• Example 1 - A time clock keys the gate open in the morning and an entrapment protection device senses an
obstruction prior to the gate reaching the full open position. If the entrapment is sensed by the inherent system, the
gate will reverse and run back to the closed position. The time clock input is still present, but the gate will not re-open.
Note: In some systems, the time clock input comes from the telephone entry system relay. This same relay may also provide open commands for a card reader, MicroPLUS transmitters and the visitor telephone entry. If so, these devices will also be disabled in a soft shutdown condition.
• Example 2 - If the gate is closing and an entrapment protection device is activated, the gate will either stop or reverse
and run back to the open position, depending upon if the secondary or inherent device was activated. The automatic
close timer will not close the gate.
• Example 3 - Vehicle arrives at exit loop and gate runs towards the open position. If the inherent entrapment protection
gets activated during this opening cycle, the gate reverses and runs back to the closed position. After the inherent
entrapment protection is cleared, If the vehicle is still present at the exit loop, a soft shutdown condition does not
occur. The exit loop input provides an immediate reset of the operator and the gate will again run to the open position.
Resetting a Soft Shutdown
In some conditions, a soft shutdown will reset as soon as the entrapment condition clears. For example, if a non-contact sensor
(photo cell) is sensing an obstruction, the operator will stop the gate and assume a soft shutdown condition. When the photocell clears, the operator will return to normal operation.
When the operator is in a soft shutdown, activation of any “intended input” will reset the operator. An “ intended input” includes any command, any standard safety input and any loop input. Activating any of these inputs will reset the gate. At that point the gate will return to normal operation. If the gate is open, the automatic close timer will then time out and close the gate.
Hard Shutdown (Alarm Activated)
A hard shutdown condition occurs when: (1.) The inherent entrapment protection system (Type A) gets activated TWO consecutive times before the gate completes the open or close cycle. (2.) The reversing edge (Type B2) gets activated and reverses but before the gate completes the reverse cycle the inherent entrapment protection system (Type A) gets activated.
• Example of a Hard Shutdown - The gate is closing and the inherent entrapment protection system senses an obstruction and
causes the gate to reverse direction. As the gate begins to run in the open direction, a second obstruction is sensed prior to the
gate reaching the full open position. Once the second obstruction has been sensed, the operator will stop, the audio alarm will
sound and all standard inputs are shut down (including open commands, safety commands, loop inputs, etc.).
– To silence the alarm, press the reset button or after 5 minutes, the audio alarm will shut off but will “chirp” every 5 seconds. This indicates that the operator is in a hard shutdown condition (The reset button must be pressed to reset the operator and stop the alarm “chirping”).
Resetting a Hard Shutdown
The operator is in a hard shutdown condition when the audio alarm is sounding OR “chirping” every 5 seconds.
• Before resetting a hard shutdown, determine why the shutdown occurred. Inspect the gate for any obstructions along
its path that could have activated the inherent entrapment sensing system. Inspect the gate and gate hardware.
The audio alarm will sound for five minutes, or until the operator’s reset button is pushed. After (5) five minutes the alarm will “chirp every 5 sec.” and the hard shutdown condition will remain in affect until the reset button is pushed.
34
Once the operator has been reset, an open or close command is needed to start the gate operator. Most activating commands will cause the gate operator to cycle to the open position. This includes activation of a key switch or open command and activation of an automatic exit loop. Activation of a close command will run the gate to the closed position.
Note: DoorKing operators have a built-in alarm reset push button mounted on the operator (See previous page for reset button location).
Activating this button will return the gate operator to normal operation, but will not cycle the gate operator. A remote alarm/reset station (P/N
1404-080) can be mounted external of the gate operator provided that it is installed in the line-of-sight of the gate and gate operator.
9210-065-H-2-13
6.3 Manual Gate Operation
Caution:
Never attempt to manually operate any gate until you have verified that power to the operator has been shut-off.
2 Manual Crank
Insert the supplied manual hand crank into the access hole until it engages with the motor shaft.
Turn the crank to open the gate. 9235, 9245 mechanical disc brake model operators
MUST also have the disc brake manually released before manually cranking the hand crank (See below).
1 Unlock Manual Crank
Access Panel
Cuts off AC power to the operator.
Motor
Shaft
1
4
2
1
4
3
1
2
3
4
2
3
R E S E T
Manual crank in stored position.
9210-065-H-2-13
CA
N/
VEHIC
CLA
MODE
SERI
CONFOR
ANSI
/UL-
CS
AL
L
TIF
22
SS
UL
TO
325
IED TO
AR
.2 NO.
GAT
247 53 382
E OP
ER
AT
OR
HP
VOL
TS
AM
PS
MA
X GA
TE LO
Doo rKi
AD ng, I nc.,
PH
AS
60 H z
E lewo od, C
A
WA
RN
ING
MO
SE
RIO
Op er an ate
Do not
Do pat no t st h w
Rea d o
US I gat
of p hile wn er e on
allo w rat e g an ate gat
NJU ly wh eop le a
.
ga e is
’s m an
m ovi ual
RY OR en g n to ng. an h o ate ea
DE uctio
play
in ns. d sa fet is in ht
gat e ar ea r wa lk th
US
AT
E
H rou gh y in struct ion s.
Disc
Brake
R
E
S
E
T
MAN
UAL
LEAS
E
A
E
R
E
L
E
Access
Panel
1 ft/s
1.5
ft/s
.5 ft/s
0 ft/s
2 ft/s
EP
M
B-
L1 L2
L3
0 0 0
B+
M od e
SCM
ser bas ic I/O control ies
Turn manual release
1/4 turn clockwise to release the disc brake.
R
E
S
E
T
MANUAL
RELEASE
R
E
L
E
A
S
E
9235, 9245
Mechanical Disc
Brake
The disc brake MUST be manually released (disengaged) with a slotted screwdriver (Not provided) before manually operating the gate.
Disc brake will automatically reengage after power has been restored.
35
SECTION 7 - MAINTENANCE AND TROUBLESHOOTING
Inspection and service of this gate operator by a qualified technician should be performed anytime a malfunction is observed or suspected. High cycle usage may require more frequent service checks.
7.1 Maintenance
When servicing the gate operator, always check any secondary (external) reversing devices (loops, photocells, etc.) for proper operation. If external reversing devices cannot be made operable, do not place this operator in service until the malfunction can be identified and corrected.
Always check the inherent reversing system when performing any maintenance. If the inherent reversing system cannot be made operable, remove this operator from service until the cause of the malfunction is identified and corrected. Keeping this operator in service when the inherent reversing system is malfunctioning creates a hazard for persons which can result in serious injury or death should they become entrapped in the gate.
When servicing this gate operator, always turn power OFF!!
If gearbox requires oil, use only Mobil SHC-629 Synthetic Gear Oil. Do not completely fill gearbox with oil. Gearbox should be half full only. Do not exceed this level.
36
Monthly Interval
Operator
Component
Maintenance
Alarm
Chain
Fire Dept.
Gate
Grease
Loop(s)
Primary Reverse System
Release
Secondary Reverse Device
Sprockets
Complete System
Activate the primary (inherent) reverse system by blocking the gate with a solid object. When the gate reverses, block the gate in the opposite direction prior to the limit being reached. The entrapment alarm should activate. Press the reset button to silence the alarm.
Check for sagging. Tighten if necessary.
Check emergency vehicle access device for proper operation.
✓
✓
✓
Inspect for damage. Check gate wheels. rollers and guides for wear and grease if necessary.
Wheels and guide rollers if necessary.
Check vehicular exit and reverse loops for proper operation.
Check that the gate reverses on contact with an object in both the opening and closing cycles.
Adjust the reversing sensor if necessary.
Check manual release for proper operation.
Check secondary (external) reverse device(s) stop or reverse the gate when activated.
✓
✓
Check set screws for tightness.
Complete check of gate and gate operating system.
✓
✓
9210-065-H-2-13
7.2 Built-In Diagnostic Tests
This gate operator is designed with built-in diagnostics that will alert you to potential or existing problems that the microprocessor has detected. Specific fault conditions are checked and the operator will signal that a fault exist through the built-in alarm.
Constant alarm is heard when power is applied:
This indicates that the limit switch wire harness is not connected to the circuit board. In this condition, the operator will not run and the tone will continue until the fault is corrected. Check to be sure that the limit switch plug is properly inserted into the limit switch plug on the circuit board.
Constant alarm is heard:
This indicates that the operator is in a hard shutdown condition (section 6.2 on page
34). The tone will continue to sound for five minutes, and then will beep once every five seconds. The operator-reset button must be pressed or power must be removed and then reapplied to return the operator to normal operation.
Short “chirp” is heard every five seconds:
This indicates that the operator has been in a hard shutdown condition in excess of five minutes. This will continue until the operator-reset button is pressed or until power is removed from the operator (section 6.2 on page 34).
Operator runs for 1 second and stops, two short “chirps” are heard:
This indicates that there may be a fault with the current sensor circuit.
7.3 Troubleshooting
Have a good VOM meter to check voltages and continuity. A Meg-Ohm meter capable of checking up to 500 meg-ohms of resistance is necessary to properly check the integrity of the ground loops. When a malfunction occurs, isolate the problem to one of three areas: 1. the operator, 2. the loop system, 3. the keying devices. Use caution when checking high voltage terminals, motor capacitor and the motor.
1. Check the input indicator LEDs. They should only come ON when a keying device (card reader, push button, etc.) is activated.
If any of the input LEDs are ON continuously, this will cause the gate operator to hold open. Disconnect the keying devices one at a time until the LED goes OFF.
2. Check any external secondary entrapment protection devices. Any short or malfunction in these devices can cause the gate operator to stop or to hold open.
3. A malfunction in a loop or loop detector can cause the gate operator to hold open, or to not detect a vehicle when it is present over the loop. Pull the loop detector circuit boards from the loop ports on the operator circuit board. If the malfunction persists, the problem is not with the loop system. For more information on trouble shooting loops and loop detectors, refer to your loop detector instruction sheet and to the DoorKing Loop and Loop Detector Information Manual located on DoorKing’s web site.
4. Check to be sure that there are no shorted or open control wires from the keying devices to the gate operator. If a keying device fails to open the gate, press the Key Switch or momentarily jumper across terminals 1 and 4 on the operator circuit board. If the gate operator starts, this indicates that a problem exist with the keying device and is not with the gate operator.
5. If a three-button control station (open-close-stop) is connected to this gate operator, check for proper wiring. Only a
DoorKing three button control station (P/N 1200-006 or 007) can be used with this gate operator. Others will cause a malfunction.
6. Check the high voltage supply. A voltage drop on the supply line (usually caused by using too small supply voltage wires) will cause the operator to malfunction. Refer to the wire size chart in section 2.1 on page 17.
9210-065-H-2-13 37
Operator will not run.
Power LED is OFF.
• Check that AC power to the operator is turned ON.
• Transformer may be overheated. Turn power off and allow board to cool for several minutes then retest. Check
for low VAC power and low voltage shorts.
• Check for VAC at high voltage input terminal. If voltage measures 0, check the incoming power wires or
replace the circuit board.
Gate opens a short distance, then stops and reverses.
• Disconnect the gate from the gate operator and check that the gate slides freely without any binding.
• Re-adjust the reverse sensitivity.
• Continue troubleshooting or replace circuit board.
Gate opens but will not close.
• Check the input LEDs. Any ON will hold the gate open and indicates a problem with a keying device.
• Check the secondary safety devices. Any activated will hold the gate open and indicates a problem with the
• Check the loop detectors. Any activated can hold the gate open and indicates a problem with the loop detector
or ground loop.
• Operator may be in a “soft shutdown.” Activate any keying device to determine if operator returns to normal
operation.
• If automatic close is desired, be sure SW 1, switch 2 is ON and set timer open from 1-23 seconds.
• Bypass circuit board and check motor as above.
Gate closes but will not open.
• Operator may be in a “soft shutdown.” Check input LEDs. If any are ON, momentarily disconnect, then
re-connect the wire going to the respective terminal. Operator should open.
• Check to be sure that the operator is running in the proper direction. Turn power OFF, and then back ON.
Activate a keying device. Operator should run in the open direction. If operator runs in the close direction, turn
power OFF and change direction switch SW 1, switch 1. Go to above section if operator now opens but will not
close.
• Be sure that the each LED on the control board lights when the keying device connected to the that terminal is
activated. If LED does not light, momentarily place a jumper wire from terminal 1 to the input terminal being
checked. If LED lights and gate opens, problem is with the keying device. If LED does not light, replace control
board.
• Bypass circuit board and check motor as described above.
Gate starts to close, then reverses to open.
• Re-adjust the reverse sensitivity.
• Disconnect the gate from the gate operator and check that the gate slides freely without any binding.
• Check the loop detector LEDs and input LEDs. Any that flash ON will cause the gate to reverse.
• Continue troubleshooting or replace circuit board.
Gate closes then re-opens.
• Check for any input or loop detector LED’s that are ON.
• Check that the operator is running in the proper direction (see “gate closes but will not open”).
Alarm is sounding.
Operator will not run.
• Operator is in a “hard shutdown” condition. Reset button must be pushed to return operator to normal
operation, see Section 6.2 Shutdown Conditions, page 34.
• Check the gate and gate hardware for any binding, correct where necessary.
• Gate may be too heavy.
38
Alarm chirps once every 5 seconds.
Operator will not run.
• Operator has been in a “hard shutdown” condition in excess of 5 minutes. Reset button must be
pushed to return operator to normal operation, see Section 6.2 Shutdown Conditions, page 34.
Alarm sounds when power is applied and operator will not run.
• The limit switch wire harness is not plugged into the circuit board. Check that the limit switch connector is
properly plugged into the limit switch plug on the circuit board.
Operator runs for 1 second and stops, two short chirps are heard.
• There may be a problem with the current sensor on the circuit board. Replace the circuit board.
9210-065-H-2-13
7.4 Accessory Items
The following accessory items are available for the series 9200 slide gate operators.
Contact Sensors - For use as a secondary entrapment protection device. Miller Edge, Inc., MGO20, MGR20, MGS20
Chain Tray Kit - 10 Ft. section. Sections connect together to fit any length gate. P/N 2601-270
Pedestal Mounting Stand - Heavy-duty pedestal mounting stand for the 9200 series operator. P/N 9200-135
Heater and Fan Kit - Recommended for cold weather climates.
P/N 1601-195: 115 VAC models P/N 1601-197: 208/230 VAC models
Photo Cell - Non-contact (photocell) sensors for use as a secondary entrapment protection device.
MMTC, Inc. Model 60-278 - P/N 8080-011
Carlo Gavazzi Type PMP12 - P/N 8080-030
Carlo Gavazzi Type PMT - P/N 8080-031
Note: DO NOT USE MMTC, Inc. Model IR55 - P/N 8080-010 for the 9200 series slide gate operator.
Loop Detector - Detectors plug directly into ports on circuit board simplifying wiring.
Single channel detector - P/N 9410-010 Dual channel detector - P/N 9409-010
Loop Wire - 18 AWG loop wire with XLPE insulation is ideal for ground loops. Available in 500 and 1000 foot rolls. Red, blue or black insulation.
Pre-Fab Loops - Prefabricated ground loops. 24-foot circumference with 50-foot lead-in. Available in yellow, red or blue jackets.
Not for use in asphalt roadways.
Loop Test Meter - Meg-ohm meter checks the integrity of ground loops. P/N 9401-045
3-Button Control Station - Provides open-close-stop manual operation of the gate.
Stand Alone Box - P/N 1200-006 Interior (fits in single gang box) - P/N 1200-007
Interconnection Cable - Interconnect wire cable contains all the necessary wires to interconnect primary / secondary operators.
Cable length: 30 ft. - P/N 2600-755 40 ft. - P/N 2600-756 50 ft. - P/N 2600-757
Time Clock - 7 day and 365 day time clocks can be used to automatically open gate at pre-set time and days. Compact clock fits inside the operator. 7 day clock - P/N 2600-791 365 day clock - P/N 2600-795
V-Wheels - 4 inch and 6 inch. UHMW or Steel. Roller bearings or sleeve bearings. Single or tandem wheel configurations.
Surge Devices - High and low voltage surge suppressors help prevent circuit board failure caused by lightning strikes and power surges. High Voltage - P/N 1876-010 Low Voltage - P/N 1878-010
Gate Scale - Use to test torque required to move gate. P/N 2600-225
Remote Alarm/Reset Station - Provides a remote station to reset an operator in a hard shutdown condition. Must be mounted
in line-of-site of the gate and operator. Includes visual alarm light and audible siren. P/N 1404-080.
Speed Bumps - Prefabricated six-foot speed bump reduces traffic speed through gate system. P/N 1610-150
9210-065-H-2-13 39
Installation/Owner’s Manual
Heavy-Duty Vehicular Slide Gate Operator
Use this manual for circuit board 4404-010 Revision A or higher.
9210-065-H-2-13
www.doorking.com
DoorKing, Inc.
120 Glasgow Avenue
Inglewood, California 90301
U.S.A.
Phone: 310-645-0023
Fax: 310-641-1586
Copyright 2009 DoorKing, Inc. All rights reserved.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement