SECTION 3: Programming the 7845GSM. Honeywell 7845C, AlarmNet 7845GSMCN, AlarmNet 7845GSM
Διαφήμιση
Διαφήμιση
Section 1: General Information
Antenna
The 7845GSM comes equipped with an internal antenna. This feature provides additional security to the installation by making the device tamper resistant.
AMPS antennas, such as the 7825-OC antenna, cannot be used with this product.
Specifications
Mechanical
Dimensions: 8.4" x 8.0" x 1.5"
Weight: 2.4 lbs., with battery
Electrical
Input Power: 9VAC, 15VA transformer, Honeywell part number 1332/1332CN in Canada
(included)
Backup Battery: 6V, 3.1AH, Honeywell part number K14139, (included)
Current Drain: 35mA average standby, 500mA peak transmit
Fault Relay Output: Open collector, 12VDC, .25W max.
Input Trigger Levels: (V+) 2V – 13V
(V-) 1V
RF
Band
GSM 850
GSM 1800
GSM 1900
Transceiver Type: Tri-Band GSM/GPRS Class 10
Modulation: GMSK
Antenna: Internal GSM quad-band antenna 1.3 dBi gain
Transmission
Frequency
(MHz)
Transmit
Power
(dBm)
Receive
Frequency
(MHz)
Receive
Sensitivity
(dBm)
Number of
Channels
Channel
Spacing
(MHz)
Duplex
Separation
(kHz)
Environmental
Operating temperature: -20º to +55ºC
Storage temperature: -40º to +70ºC
Humidity: 0 to 90% relative humidity, non-condensing
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
1-3
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
7845GSM/7845GSMCN Installation and Setup Guide
1-4 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
S E C T I O N 2
Mounting and Wiring
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
Mounting the 7845GSM
♦
Wiring the 7845GSM
♦ Power Connections and Options
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Mounting the 7845GSM
The 7845GSM must be mounted indoors. To mount the 7845GSM, see Figure 1 and complete the following steps:
1. Unpack the 7845GSM and detach the case back by pushing up into the two tabs located at the bottom of the 7845GSM with the blade of a screwdriver while pulling the case back and case front apart.
2. Temporarily connect the 7845GSM to the AC transformer, supplied.
3. Choose the installation site with the best signal strength by observing the signal strength (RSSI) bar graph (refer to Section 6 for information about signal strength and status indications). Signal strength should be within 3-5 bars. The best signal strength is usually found at the highest point in the building, near a window. Unplug the transformer.
3 BARS MIN.
R Y Y G G G
7845i-GSM-025-V0
4. Locate the case back over the mounting surface such that the opening in the case back is aligned with the wire/cable access opening (in the mounting surface) while passing the wires/cable through the opening in the case back, or through the removable knockouts located on the bottom of the back cover.
5. Secure the case back to the mounting surface using four screws (supplied).
6. When all wiring is completed, attach the case front of the 7845GSM to the case back.
Attach the top of the 7845GSM first then press the bottom section inward until it snaps into place. Secure bottom using cover securing screw (supplied) as shown below,
(required for UL installations).
CASE
BACK
MOUNTING
SCREW (4)
(TYP)
INTERNAL
ANTENNA
WALL OR
MOUNTING
SURFACE
FOR
EXTERNAL
ANTENNA
ONLY
USE!
PORT
SERVICE
LED
7720P
NOT
TELEPHONE
TRANSMIT
PRIMARY
BATTERY:
POWER:
6V.
FCC
ID: GIPMC56
MAC
9 - 1
Hr FOR
3.1 A
6.5 VAC
24 Hr
267W
IC: Y
BACKUP
- MC56
LABEL
HERE
Honeywell
OPTIONAL WIRING
KNOCKOUT
CASE
FRONT
OPTIONAL WIRING
KNOCKOUTS
TAB
TAB
COVER SECURING SCREW
7845GSM-015-V0
Figure 1. Mounting the 7845GSM
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
2-1
7845GSM/7845GSMCN Installation and Setup Guide
Wiring the 7845GSM
Unshielded, 22 AWG cable is recommended for 7845GSM power/data wires.
Wiring for ECP, 4204 and Two-4204 Modes
Most Honeywell ADEMCO control panels support LRR-ECP data communication, (e.g.,
VISTA-10P, VISTA-15P, VISTA-20P, LynxR-I, VISTA-128BP and VISTA-128FBP). However, there are some panels that do not. Check the Installation and Setup Guide for the control panel you are using to see if it supports ECP communication.
Connect the 7845GSM to a compatible Honeywell VISTA control panel's ECP terminals, in parallel with keypads and other peripheral devices such as RF receiver, VIP module, etc.
Wire length/gauge limitations are the same for the module as they are for keypads and other peripheral devices. To wire the module for ECP or 4204 modes, see Figure 2 and make the following connections:
Table 1. Wiring connections for ECP or 4204 modes
7845GSM Control
Terminal 3 V+
Terminal 4 GND
+12 V Aux
Ground
Terminal 5 Data In Data Out
Terminal 6 Data Out Data In
+12 V AUX
TRANSFORMER
RED
TB1
1 AC INPUT 1
2 AC INPUT 2
3 ECP (+) VOLTAGE INPUT
4 GND GND
DATA OUT
BLK
YEL
GRN
5 ECP DATA IN
DATA IN 6 ECP DATA OUT
J1
VISTA CONTROL PANEL
7845GSM
Figure 2. Wiring a VISTA for ECP Mode or 4204 Modes
BATTERY
K14139
7845GSM-009-V0
To install a 7845GSM with a LynxR-I Security System, wire the devices as shown in
Figure 3. Refer to the LynxR-I Installation and Setup Guide.
2-2 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
4-WIRE CABLE (N4632-4)
RED
BLK
YEL
GRN
Section 2: Mounting and Wiring
TB1
1
2
ECP (+) VOLTAGE INPUT
4 GND
Z1/Z2 OR DATA IN
6 Z3 OR DATA OUT
LRR/IP COMMUNICATIONS PORT
LYNXR-I CONTROL PANEL 7845GSM
LYNX
STANDARD
CAPACITY
BATTERY
NOTE
DO NOT CONNECT THE 7845GSM BACKUP BATTERY
OR TRANSFORMER
WHEN USING WITH LYNXR-I
LYNX
SUPER HIGH
CAPACITY
BATTERY
(OPTIONAL)
REQUIRED FOR
24-HR BACKUP
7845GSM-028-V0
Figure 3. Wiring a LynxR-I for ECP Mode
Wiring for Zone Trigger Mode
To trip a zone on the 7845GSM in V+ trigger mode, the positive triggering voltage from the control panel must be within 2.0V-14.5V.
Trigger levels above this range may cause permanent damage to the unit.
Trigger levels below this range result in unreliable operation.
To trip a zone on the 7845GSM in V- trigger mode, the negative triggering voltage must be less than 1.0V.
NOTE: LynxR and LynxR-EN have a designated trigger for V+ trigger.
Connect a wire from the triggering source (bell output, voltage trigger, etc.) of the control panel to the zone input of the module, and connect a common ground between the module and control panel.
UL
The configurations shown in Figures 4 and 5 have not been evaluated by UL.
Examples of zone connections follow:
TRANSFORMER
+12 V AUX
GND
BELL (+)
BELL ( )
( ) (+)
TB1
1 AC INPUT 1
2 AC INPUT 2
3 ECP (+) VOLTAGE INPUT
4 GND
5 ZONE INPUT Z1/Z2
J1
CONTROL PANEL 7845GSM
BATTERY
K14139
Figure 4. Wiring the 7845GSM Zone 1 Input for a Positive (+) Triggered Bell Output
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
2-3
7845GSM/7845GSMCN Installation and Setup Guide
TRANSFORMER
+12 V AUX
GND
BELL (+)
BELL ( )
TB1
1 AC INPUT 1
2 AC INPUT 2
3 ECP (+) VOLTAGE INPUT
4 GND
5 ZONE INPUT Z1/Z2
( ) (+)
CONTROL PANEL J1
7845GSM
BATTERY
K14139
Figure 5. Wiring the 7845GSM Zone 1 Input for a Ground (-) Triggered Bell Output
TRANSFORMER
TB1
1 AC INPUT 1
2 AC INPUT 2
9
LRR / AAV
TRIGGER
8
LYNXR/LYNXR-EN
CONTROL PANEL
2K EOL
RESISTOR
4
GND
5
ZONE INPUT Z1/Z2
J1
7845GSM
BATTERY
K14139
7845-GSM-021-V0
Figure 6. Wiring the 7845GSM Zone 1 Input to a LynxR Trigger Output
Wiring for Module Fault Relay
You may wire and program the module's fault output trigger for fail-safe mode (see the question "FLT REL ON Y/N").
To sense a module fault at the control panel, make connections as shown in Figure 7, including the proper EOL resistor required by the control.
TRANSFORMER
12V AUX
GND
ZONE IN (+)
CONTROL PANEL
2K EOL
RESISTOR
TB1
1 AC INPUT 1
2 AC INPUT 2
3 ECP (+) VOLTAGE INPUT
4 GND
5 Z1/ Z2 or DATA IN
6
11 RAD FLT
J1
2-4
7845GSM
BATTERY
K14139
7845GSM-007-V0
Figure 7. Wiring the 7845GSM to Trip a Control Panel Zone for Normally Closed Fault
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 2: Mounting and Wiring
TRANSFORMER
2K EOL
RESISTOR
N.O.
N.C.
TB1
1 AC
2 AC
3
ECP (+) VOLTAGE INPUT
4
GND
5
ZONE INPUT Z1/Z2
J1
7845GSM
BATTERY
K14139
7845-GSM-030-V0
Figure 8. Wiring the 7845GSM Zone 1 Input for EOL Supervised N.O./N.C. Triggers
Power Connections and Options
Primary power for the 7845GSM is provided by the AC plug-in transformer. For ECP communication, you must also connect the +12VDC AUX voltage output of the control panel
(9.6V-13.8V typical) (see Figure 9). In the case of the LynxR-I, primary power is supplied by the LynxR-I unit through the IP/LRR communication port.
In all installations, TB1-4 GND must be connected to ground (GND) on the control panel.
12V AUX
GND
TRANSFORMER
CONTROL PANEL
TB1
1 AC INPUT 1
2 AC INPUT 2
3 ECP (+) VOLTAGE
4 GND
5 Z1/ Z2 or DATA IN
11 RAD FLT
J1
BATTERY
K14139
7845GSM
Figure 9. Powering the 7845GSM
NOTE: When calculating the total load on the auxiliary power output of the control panel, budget 10mA for the 7845GSM when using ECP mode.
Backup Battery Connection
The included battery (K14139) is used for backup in the event of a system power loss.
• The battery can provide over 24 hours of system life in the event of a power failure.
• A programmable power loss message can alert the AlarmNet Control Center when system power is lost (power loss messages are reported within 1-3 hours of actual loss).
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
2-5
7845GSM/7845GSMCN Installation and Setup Guide
• The module transmits a low-battery message (programmable) when the battery reaches 5.7V ±5%, indicating subsequent message may not be transmitted.
• The system shuts down when the battery reaches 5.1V, and radio transmissions are no longer possible.
• If system power is restored before the module shuts down, a power restore message is sent within 1-3 hours after power is restored, and the battery is recharged using the
7845GSM’s built-in battery charger. If system power is restored after the 7845GSM has shut down, a power-on reset condition exists, the module initializes itself and the battery will recharge.
Install the battery as follows, and refer to the Summary of Connections diagram at the end of this document.
1. Place the battery inside the case back.
2. Snap the right side of the battery clip onto the inside of the case back and secure the left side with the screw provided.
1. Do not plug the battery in until after you have powered-up the 7845GSM.
2. If using a LynxR-I, do not connect the module's backup battery. The LynxR-I backup battery will supply backup power in the event of a power outage.
Initial Power-Up Sequence
Before connecting power, check that the following have been completed:
1. If using ECP Mode, terminal block TB1 V+ and GND terminals are connected to the control panel’s auxiliary power output: 12VDC nominal.
2. Plug in the transformer (or other main power source). Initially, all 7845GSM programming options are set to the factory default settings.
3. Connect the red and black battery cables to the battery terminals. Connect battery cable to connector J1.
4. Power up the control panel.
2-6 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
S E C T I O N 3
Programming the 7845GSM
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
General Information
♦
ECP Mode Programming
♦
Alternative Modes (Zone Trigger, 4204 and
Two-4204)
♦
Alternative Mode Programming
♦
Exiting Programming Mode
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Information
The 7845GSM is designed to deliver alarms via the GSM network to an AlarmNet central station when it is registered with a valid AlarmNet account.
The 7845GSM module requires an AlarmNet–I account. For new installations, please obtain the account information from the central station prior to programming this module. For replacement installations, the AlarmNet-I account is created automatically when the module is registered (based on the existing "C Series" account).
You can program a 7845GSM by one of the following methods:
• Through the AlarmNet Direct website
• Through use of a 7720P Programming Tool
• Through a programming mode in the control panel on panels that support this option
(e.g., VISTA-128BP and FBP)
Using the AlarmNet Direct website
To program the module via the website (if you are already signed up for this service), go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx
If you are not signed up for this service, click on “Dealer Sign-Up.
Log in and follow the on-screen prompts.
Please have the following information available when programming the module:
1. Primary City ID (two-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label inside module) or MIN number of the device you are replacing
5. Mode of operation of existing module if replacing a "C" series radio.
After programming is complete, you must transfer the data to the module and the module must be registered. Refer to Section 4: Registration, for further instructions.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-1
7845GSM/7845GSMCN Installation and Setup Guide
Using a 7720P Programming Tool
Connect the 7720P Programming Tool as shown below. The 7845GSM powers the 7720P
Programming Tool via the programming jack, and automatically senses the presence of the
7720P when it is plugged in.
Xmit
Shift
/
N / Y
Shift
BS / ESC
7
S
Space
4
1
D
0
8
T
5
E
2
B
9
X
Enter
#
6
3
F
C
LEDs
INTERNAL
ANTENNA
7720P
PROGRAMMING
JACK
TB1
RSSI / MODE AND
STATUS LEDs
MODE AND STATUS
INDICATOR SWITCH
3-2
TAMPER
SWITCH
J1
BATTERY
CONNECTOR
7845GSM-005-V1
Figure 10. Cable Connections
Each key of the 7720P has two possible functions: a normal function and a Shift function.
To perform a normal key function, simply press the desired key.
To perform a Shift function, press the [shift] key, and then press the appropriate key.
The prompts in this document reflect use of the 7720P Programming Tool. Table 2 below lists each normal and shift key function.
Table 2. 7720P Normal and Shift Key (shift LED lit) Functions
KEY
BS/ESC
↓/↑
N/Y
SHIFT
1/A
2/B
3/C
4/D
5/E
6/F
7/S
8/T
9/X
SPACE
0
NORMAL KEY FUNCTION SHIFT KEY FUNCTION
[BS]: Press to delete entry
[ ↓]: Scroll down programming
[N]: Press for "NO" answer
[
[ESC]: Press to quit program mode; also can reset programming defaults*
↑]: Scroll up programming
[Y]: Press SHIFT-Y for "YES" answer
Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out once a key is pressed. Press again for each SHIFT function desired.
[1]: For entering the number 1
[2]: For entering the number 2
[3]: For entering the number 3
[A]: For entering letter A
[B]: For entering letter B
[C]: For entering letter C
[4]: For entering the number 4
[5]: For entering the number 5
[6]: For entering the number 6
[7]: For entering the number 7
[8]: For entering the number 8
[9]: For entering the number 9
[SPACE]: For scrolling option list
[0]: For entering the number 0
[D]: For entering letter D
[E]: For entering letter E
[F]: For entering letter F
[S]: For entering letter S
[T]: For entering letter T
[X]: For entering letter X
No SHIFT function
No SHIFT function
#/ENTER [#/ENTER]: Starts programming mode;
Press to accept entries
No SHIFT function
*Active only when the "Exit Programming Mode" prompt is displayed.
Using the Control Panel Programming Mode
Some control panels support programming of the 7845GSM through the control panel programming mode (e.g., Vista-128BP). If programming through the control panel, only the ECP Mode programming options are available. The "mode" questions will not be displayed, and the mode cannot be changed. For a description of key functions on the
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 3: Programming the 7845GSM control panel keypad, and how they map to the 7720P Programming tool, refer to the control panel's Programming Guide.
Programming Conventions
Programming is accomplished by answering a series of prompts (questions). Most prompts require only a [Y]es or [N]o response, while others require a numerical response (ID numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an invalid entry.
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the entered value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing any values. Press the [ESC] key to go to the end of the list of questions.
ECP Mode Programming
The 7845GSM supports ECP messaging to communicate with the control panel. LRRenabled control panels send Contact ID format alarms to the 7845GSM directly on the 4-wire console bus. Not all control panels support the LRR interface on ECP, so be sure to check the
Installation and Setup Guide of the control panel to see if it supports this feature.
1
2
3
4
5
Refer to Table 3 for ECP Mode programming and follow the prompts.
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears:
Access to Prog
Mode Denied
NOTE: The default programming values for ECP mode are listed in the prompts below.
PROMPTS
Strt Prog Mode?
(Y/N)_
Enter Password
Program 7845?
(Y/N)_
Table 3: Programming a 7845GSM for ECP mode only.
Create Password?
(Y/N)_
Change Password?
(Y/N)_
ENTRY OPTIONS
[Y], [N]
[0-9, A-F, N,
S, T, X, Y]
[Y], [N]
[Y], [N]
[Y], [N]
DESCRIPTION
Enters programming mode.
If a password has been previously assigned, this prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
To begin programming the module, press [Y] and go to
Prompt 9: "Device Mode."
To create a password if none has been assigned, press
[N] and go to Prompt 4: "Create Password."
To change an existing password, press [N] and go to
Prompt 5: "Change Password."
Passwords can be used to protect account and programming information.
If no password has been assigned, this prompt appears after pressing [N] at the "Program 7845?" prompt.
If a password is desired, press [Y] and go to Prompt 6:
"Enter Password."
If a password has already been assigned, this prompt appears after pressing [N] at the "Program 7845?" prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering a new one, answer [Y] to the "Change
Password?" prompt, then press the [Enter] key when prompted for the new password and its confirmation.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-3
7845GSM/7845GSMCN Installation and Setup Guide
6 Enter Password [0-9, A-F, N,
S, T, X, Y]
DESCRIPTION
This prompt is displayed if [Y] was pressed in Prompt 4 or 5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
3-4
S, T, X, Y] If the password doesn't match the first entry, the following is displayed followed by the "Exit Prog.
Mode?" prompt:
Verify Not OK
PSWD not created
8
9
Exit Prog. Mode?
(Y/N)_
Device Mode
(ECP)_
[Y], [N]
[ESC]
• ECP
• Zone Trig.
• 4204 Emu
• Two 4204s
Otherwise, the "Exit Prog. Mode?" prompt is displayed directly.
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in this section.
Press the [space] key to scroll through the modes of operation . Press [ENTER] to select ECP mode.
See Table 5 if programming other modes.
10
11
12
13
14
15
16
17
Important Information Regarding Primary and Secondary Accounts (Questions 10-16)
Account information is provided by the central station administrator. If the control supports secondary account reporting, you will need secondary account information. The City ID, CS ID or Subscriber ID of the secondary account must differ from that of the primary account.
Primary City ID
(??)_
[01-99] Enter the 2-digit primary city ID, 01-99 (decimal).
Primary CS ID
(???)
[01-FE] Enter the 2-digit primary central station ID number,
01-FE (HEX).
Primary Sub ID
(????)
En. 2 nd
CS Y/N
(N)_
[0001-9999]
[Y], [N]
Enter the 4-digit subscriber account number, 0001-
9999 (decimal).
Applicable only if control supports Central Station #1 and #2 Category Enable reporting for the LRR device
(e.g., VISTA-128BP, FA1660C, etc.).
Used if reporting to a second central station is desired.
If [N], go to Prompt 17: "Device Address."
2 nd
City ID
(??)_
2 nd
CS ID
(??)_
2 nd
Sub ID
(????)_
[01-99]
[01-FE]
Enter the 2-digit secondary city ID, 01-99 (decimal).
[0001-9999]
Enter the 2-digit second central station's ID number,
01-FE (HEX).
Enter the 4-digit subscriber account number for the second central station, 0001-9999.
Device Address
(03)_
[01-30]
In ECP mode, the 7845GSM communicates with the panel as a Long Range Radio (LRR) device. Enter the appropriate ECP device address. For VISTA-10 and
VISTA-20 series control panels, use address 03. For other controls, see the control panel’s Installation and
Setup Guide.
NOTES:
1. When programming the control, enable the LRR output.
2. The device address must be unique from the
"Direct Wire Addr" entered in Prompt 19.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
18 Enable DW Y/N
(N)_
19 Direct Wire Addr
(28)_
20 Supervision
(24 Hours)_
21 Old Alarm Time
(10 Minutes)_
22 GSM Flt Time
(60 mins)_
23 Flt Rel ON Y/N
(N)_
24 Pwr Loss Rpt Y/N
(Y)_
Section 3: Programming the 7845GSM
[Y], [N]
DESCRIPTION
Applies only to VISTA-128BP/250BP and FBP Series controls.
Enables Direct Wire Downloading over GSM.
If [N], skip to Prompt 20: "Supervision."
[01-30]
[Y], [N]
When using Direct Wire downloading, the 7845GSM communicates with the panel as an alpha keypad to initiate the direct wire download session. Enter the appropriate device address.
NOTES:
1. This address must also be programmed as an alpha keypad in the control panel (Device
Programming Mode). DO NOT connect an actual keypad (or any other device) assigned to this address.
2. This address must be unique from the "Device
Address" entered in Prompt 17.
• 30 Day
• 24 Hour
• None
The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred. (If the supervision period is changed after registration, you must re-register the module.)
Press the [space] key to scroll through choices.
•10 Minutes
• 15 Minutes
• 30 Minutes
• 1 Hour
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
[01-99]
[00] = not used
The old alarm time sets how long an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
In the event the module detects a communication path failure, enter the time delay (in minutes) before the module notifies the control panel with a trouble message (and trips the Fault Output if used; (terminal
11) see next prompt). The control panel can then notify the central station.
UL NOTE: Must be two (02) minutes.
If enabled, the fault open collector output is normally energized to ground, and de-energizes (open circuit) in the event of a module fault. For conditions that trip the fault relay refer to Module Supervision Features in
Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
[Y], [N]
UL NOTE: Must be set to "Y."
Sends a primary power loss report to the central station within 1-3 hours after its detection. A restore report is sent within 1-3 hours after power is restored.
UL NOTE: Must be set to "Y."
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-5
7845GSM/7845GSMCN Installation and Setup Guide
25 Low Bat Rpt Y/N
(Y)_
[Y], [N]
26 Tamper Rpt Y/N
(Y)_
[Y], [N]
DESCRIPTION
Sends a low-battery report when a low battery condition exists.
UL NOTE: Must be set to "Y" unless used with
LynxR-I series controls. Must be set to "N" when using
LynxR-I series controls.
Sends a tamper report when the module detects a tamper condition. A tamper restore is automatically sent when the tamper condition clears.
UL NOTE: Must be set to "Y."
Important Information Regarding Zone Input Options
ECP mode supports two optional hardwire zone input triggers by making connections to the module’s zone 6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by open collector, voltage trigger, NO, NC.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting, which allows time for the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
27
28
29
Enable Zn6 Y/N
(N)_
Zn6 Trigger Type
(V+)_
[Y], [N]
• (V+)
• (V–)
• (EOLR)
[Y], [N]
Enables alarm reporting for zone 6.
If [N], skip to Prompt 32: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 6 trigger; otherwise uses normal input signal.
30
31
32
33
34
35
36
Invert Zn6 Y/N
(N)_
Restore Zn6 Y/N
(Y)_
Delay Zn6 (secs)
(00)_
Enable Zn7 Y/N
(N)_
Zn7 Trigger Type
(V+)_
Invert Zn7 Y/N
(N)_
Restore Zn7 Y/N
(Y)_
Delay Zn7 (secs)
(00)_
[Y], [N]
Enables restore reporting for zone 6.
[01-15]
[00] = no delay
[Y], [N]
Defines the reporting delay in seconds for zone 6.
Enables alarm reporting for zone 7.
If [N], skip to Prompt 37: "Review."
• (V+)
• (V–)
• (EOLR)
[Y], [N]
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone 7 trigger; otherwise uses normal input signal.
[Y], [N]
Enables restore reporting for zone 7.
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 7.
3-6 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 3: Programming the 7845GSM
37 Review? Y/N [Y] = review
[N] = exit
DESCRIPTION
Reviewing Programming Mode Entries
To review the programming options (to ensure that the correct entries have been made), press [Y]. The programming prompts are displayed again. Use the up/down arrow keys to scroll through the program fields without changing any of the values. If a value requires change, simply type in the correct value. When the last field is displayed, the “REVIEW?” prompt again appears.
To exit the programming mode, press [N] in response to the "REVIEW?" prompt, and refer to
Exiting Programming Mode paragraph at the end of this section.
ECP Status Codes
When the 7845GSM is configured for ECP mode, it sends status messages to the control panels for battery, power, tamper, and network connectivity failures. Some of the control panels, (e.g., VISTA-10P, VISTA-15P and VISTA-20P Series) display these on the keypad as
“LngRng Radio” followed by a 4-digit code (listed in Table 4). In addition, the Contact ID codes (listed in Appendix A) for these conditions are sent to the central station by the module.
Table 4. Common ECP Keypad Display Status Codes
STATUS CODE
0000
DESCRIPTION
Control panel lost communication with 7845GSM.
0880
0005
000F
7845GSM tamper detected (cover removed).
7845GSM has lost contact with AlarmNet-G network.
7845GSM is not registered; account not activated.
0400
0C80
0C8F
08E0
3000
8000
7845GSM power-on reset AND the control panel lost communications with
7845GSM.
7845GSM power on reset AND tamper detected.
7845GSM power on reset AND tamper detected AND not registered.
7845GSM tamper detected and 7845GSM battery low.
Primary power loss (will only be displayed in conjunction with another event).
Battery charger failure (will only be displayed in conjunction with another event).
Low battery (will only be displayed in conjunction with another event). 0060
Alternative Modes (Zone Trigger, 4204 and Two-4204)
Zone Trigger Mode
There are six input zones available on the 7845GSM. Each zone is selectable for +V, -V, or
EOLR trigger. The first zone input can detect both pulsed and steady signals if connected to a bell output.
Additionally, the first zone input can be programmed to detect a single pulse
(characteristic of a Panic indication on the Lynx, LynxR or LynxR-EN control panel by enabling the Lynx Panic option). If the programming option “Lynx Panic” is enabled, the
7845GSM reports an alarm on zone 3. No restores are reported for this zone. If this option is selected, the second physical zone input is ignored.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-7
7845GSM/7845GSMCN Installation and Setup Guide
When using Zone Trigger mode, messages are sent in ADEMCO High-Speed format.
Zones 3, 4, 5, 6 and 7 are voltage trigger inputs located on TB1 pins 6-10. If the Lynx Panic feature is being used, do not connect zone 3 (the second physical zone input).
Refer to Table 5 for Zone Trigger Mode programming and follow the prompts that pertain to
Zone Trigger Mode.
4204 Emulation Mode
In 4204 Emulation Mode, the 7845GSM communicates with a compatible Honeywell VISTA series or First Alert control panel as though it were a 4204 Relay Module. If two 4204s are enabled in the module, it acts as two 4204s at consecutive device addresses. The control panel must be configured to recognize one or two 4204 relay modules accordingly. On
VISTA-32FB (or higher) control panels and First Alert equivalents, addresses 6 and 13 should not be used when the secondary 4204 is enabled. Messages are sent in ADEMCO
High-Speed format.
NOTE: See your control panel Installation and Setup Guide for the number of 4204 modules supported. The LynxR-I does not support 4204 mode.
4204 Emulation Mode Options
For control panels that do not support LRR-ECP communication, the 4204 Emulation modes provide a means of sending up to eight unique reports based on defined system conditions. In
4204 mode, the 7845GSM functions as a logical 4204 Relay Module, where each relay number, referred to in the module as zone number, can be programmed to send a report based on the output function programmed in the control for that relay. Each relay-zone can also be programmed to send a restore message of the reported condition, can be set to delay transmission of messages, and can be programmed to send reports only when a conditional zone is triggered (armed), (see Zone Input Options later in this section).
In single 4204 mode, the 7845GSM supports up to four relay-zones. In Two-4204 mode, the
7845GSM functions as two 4204 modules, supporting up to eight relay-zones.
4204 Relay Outputs map to 7845GSM zones as follows:
First 4204 Zones
(device address entered in Prompt 13):
Relay 1 = Zone 1
Relay 2 = Zone 2
Relay 3 = Zone 3
Relay 4 = Zone 4 or conditional zone trigger if
“report only if armed” is selected in any zone 1-3 when using single 4204 mode.
NOTE: Zone 4 status is not reported when being used as the conditional (arming) trigger zone.
Second 4204 Zones
(device address entered in Prompt 13, plus 1):
Relay 1 = Zone 5
Relay 2 = Zone 6
Relay 3 = Zone 7
Relay 4 = Zone 8 or conditional zone trigger if
“report only if armed” is selected in any zone 1-7 when using Two-4204 mode.
NOTE: Zone 8 status is not reported when being used as the conditional (arming) trigger zone or if tamper reporting is enabled.
When using the 7845GSM in 4204 Emulation Mode, DO NOT enable the Long-Range Radio module reporting in the control panel programming. Instead, enable the module device address(es) and program the appropriate relay activation functions for the relay-zones being used. In some control panels, it is called “relay programming” and in others it is called “output device programming.” It is recommended that “close and stay closed” (usually choice 2) action is selected. Selection of momentary activation will cause the 7845GSM to generate an alarm and NOT a restore, even if the 7845GSM is programmed to send a restore for the given zone.
In 4204 mode, messages are reported in ADEMCO High-Speed format. Zone alarms
(status 7) are reported with “1” (alarm) or “3” (restore) displayed in the zone position for the respective zone (e.g. alarm on zone 2: 5155 5555 7; restore 5355 5555 7). A supervision fault trouble message is automatically sent if the module detects no activity on its connection to the control. The message is: 5555 5515 5; restore message is: 5555 5535 5.
3-8 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 3: Programming the 7845GSM
Refer to Table 5 for 4204 Emulation Mode programming and follow the prompts that pertain to 4204 or Two-4204 mode. Check marks ( ✔) indicate whether the prompt applies to that mode.
Alternative Mode Programming
Press the [ENTER] key to begin programming and f ollow the prompts for the mode of operation being programmed.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears:
Access to Prog
Mode Denied
1
2
3
4
5
6
7
Table 5: Programming a 7845GSM for Zone Trigger, 4204 Emulation, or Two-4204 Emulation modes.
PROMPTS
Strt Prog Mode?
(Y/N)_
Enter Password
Change Password?
(Y/N)
Program 7845?
(Y/N)_
Create Password?
(Y/N)_
Enter Password
Verify Password
ZONE
TRIG.
✔
✔
4204/
2-4204
✔
✔
ENTRY OPTIONS
[Y], [N]
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
DESCRIPTION
Enters programming mode.
[0-9, A-F, N,
S, T, X, Y]
[Y], [N]
[Y], [N]
[Y], [N]
[0-9, A-F, N,
S, T, X, Y]
[0-9, A-F, N,
S, T, X, Y]
If a password has been previously assigned, this prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
To begin programming the module, press [Y] and go to Prompt 9: "Device Mode."
To create a password if none has been assigned, press [N] and go to Prompt 4: "Create Password."
To change an existing password, press [N] and go to Prompt 5: "Change Password."
Passwords can be used to protect account and programming information.
If no password has been assigned, this prompt appears after pressing [N] at the "Program 7845?" prompt.
If a password is desired, press [Y] and go to Prompt
6: "Enter Password."
If a password has already been assigned, this prompt appears after pressing [N] at the "Program
7845?" prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering a new one, answer [Y] to the "Change
Password?" prompt, then press the [Enter] key when prompted for the new password and its confirmation.
If [Y] was pressed in Prompt 4 or 5, this prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
Re-enter the password as confirmation.
If the password doesn't match the first entry, the following is displayed followed by the "Exit Prog.
Mode?" prompt:
Verify Not OK
PSWD not created
Otherwise, the "Exit Prog. Mode?" prompt is displayed directly.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-9
7845GSM/7845GSMCN Installation and Setup Guide
8
9
PROMPTS
Exit Prog. Mode?
(Y/N)_
Device Mode
(ECP)_
ZONE
TRIG.
✔
✔
4204/
2-4204
✔
✔
ENTRY OPTIONS
[Y], [N]
[ESC]
• ECP
• Zone Trig.
• 4204 Emu
• Two 4204s
DESCRIPTION
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in this Section.
Press the [space] key to scroll through the modes of operation.
Press [ENTER] to select the mode of operation.
See Table 3 for ECP mode programming.
Important Information Regarding Primary Account (Questions 10-12)
Account information is provided by the central station administrator.
10 Primary City ID
11
12
13
14
15
(??)_
Primary CS ID
(???)
Primary Sub ID
(????)
Device Address
(12)_
Enable DW Y/N
(N)_
Direct Wire Addr
(28)_
✔
✔
✔
✔
✔
✔
✔
✔
✔
[01-99]
[01-FE]
Enter the 2-digit primary city ID, 01-99 (decimal).
Enter the 2-digit primary central station ID number, 01-FE (HEX).
[0001-9999] Enter the 4-digit subscriber account number, 0001-
[01-15]
[Y], [N]
[01-30]
9999 (decimal).
The 7845GSM communicates with the control panel as a 4204 relay module. Enter the appropriate address. For VISTA-10P and
FA130CP Series control panels, this must be address 12. For other controls, see the control panel’s Installation and Setup Guide.
NOTES:
1. The 4204 protocol limits address range to 01-15.
If using 2-4204 mode, the 7845GSM assigns the second 4204 to the next higher device address
(e.g., if entering address 12 for the first 4204, then address 13 is automatically assigned to the second 4204 module). Program the control panel accordingly.
2. The device address(es) must be unique from the
"Direct Wire Addr" entered in Prompt 15 and any other address used on the control panel.
Applies only to VISTA-128BP/250BP and FBP
Series controls, and FA1660C and 1700C Series controls.
Enables Direct Wire Downloading over GSM.
If [N], skip to Prompt 16: "Supervision."
When using Direct Wire downloading, the
7845GSM communicates with the panel as an alpha keypad to initiate the direct wire download session. Enter the appropriate device address.
NOTES:
1. This address must also be programmed as an alpha keypad in the control panel (Device
Programming Mode). DO NOT connect an actual keypad (or any other device) assigned to this address.
2. This address must be unique from the "Device
Address" entered in Prompt 13, and cannot equal that device address plus 1 (one) if using
2-4204 mode.
3-10 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
16
17
18
19
20
21
22
Section 3: Programming the 7845GSM
PROMPTS
Supervision
(24 Hours)_
Old Alarm Time
(10 Minutes)_
GSM Flt Time
(60 mins)_
Flt Rel ON Y/N
(N)_
Pwr Loss Rpt Y/N
(Y)_
Low Bat Rpt Y/N
(Y)_
Tamper Rpt Y/N
(Y)_
ZONE
TRIG.
✔
4204/
2-4204
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
ENTRY OPTIONS
• 30 Day
• 24 Hrs
• None
• 10 Min
• 15 Min
• 30 Min
• 1 Hr
• 2 Hrs
• 4 Hrs
• 8 Hrs
• 12 Hrs
• 24 Hrs
[01-99]
[00] = not used
DESCRIPTION
The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred. (If the supervision period is changed after registration, you must re-register the module.)
Press the [space] key to scroll through choices.
UL NOTE: Must be set to 24 hours.
Sets how long an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
[Y], [N]
[Y], [N]
[Y], [N]
[Y], [N]
UL NOTE: Must be set to 10 minutes.
In the event the module detects a communication path failure, enter the time delay (in minutes) before the module notifies the control panel with a trouble message (and trips the Fault Output if used (terminal 11); see next question). The control panel can then notify the central station.
UL NOTE: Must be two (02) minutes.
If enabled, the fault open collector output is normally energized to ground, and de-energizes
(open circuit) in the event of a module fault. For conditions that trip the fault relay refer to Module
Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
UL NOTE: Must be set to "Y".
Sends a primary power loss report to the central station within 1-3 hours after its detection. A restore report is sent within 1-3 hours after power is restored.
UL NOTE: Must be set to "Y."
Sends a low-battery report when a low battery condition exists. A low-battery restore is automatically sent when the low battery condition clears.
UL NOTE: Must be set to "Y" unless used with
LynxR-I series controls. Must be set to "N" when using LynxR-I series controls.
Sends a tamper report when the module detects a tamper condition. A tamper restore is automatically sent when the tamper condition clears.
UL NOTE: Must be set to "Y."
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-11
7845GSM/7845GSMCN Installation and Setup Guide
23
PROMPTS
Lynx Panic Y/N
(Y)_
ZONE
TRIG.
✔
4204/
2-4204
ENTRY OPTIONS
[Y], [N]
DESCRIPTION
Applies only if used with a Lynx, LynxR or
LynxR-EN control LRR trigger connected to the module's zone terminal.
Reports a Panic alarm on zone 3 when the module detects a single pulse on zone 1.
No restores are generated for a Panic alarm.
Important Information Regarding Zone Input Options
If desired, 4204 mode supports two optional hardwire zone input triggers by making connections to the module’s zone
6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
NOTE: These triggers are not available when using 2-4204 mode.
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the module’s zone terminals and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell output to the 7845GSM zone causes a bell fault on the control panel, enable the "Trip Inputs 1or2" option. The
7845GSM reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when it detects a steady signal.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a telco line fault or open/close report respectively, in
ADEMCO High-Speed format. Connect the appropriate trigger from the control to the selected zone input for each of these options.
Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the following conditions:
• (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
• (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
• (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by open collector, voltage trigger, NO, NC.
Inverted Trigger: Zones can be programmed for inverted trigger, where the alarm and normal states of the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
Restore and Delayed Reports: Zone inputs can be programmed for restore reporting, and for delayed reporting
(allowing time for the user to abort false alarms).
UL NOTE: Zone restoral must be enabled.
Report Only if Armed option: To help eliminate redundant reports, zone alarms can be restricted to report only if a conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the
“arming” zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be programmed as necessary in the control panel.
The conditional (arming) zone on the module is a different dedicated zone for each programming mode, as follows:
Mode
Zone Trigger
Conditional (Arming) Zone
7
4204 4
2-4204 8
IMPORTANT: If any zone (zones 1-6 in zone trigger mode, zones 1-3 in 4204 mode, zones 1-7 in 2-4204 mode) is set for
Report Only if Armed, the conditional (arming) zone becomes unavailable for reporting (as it is reserved for the
“arming” trigger connection).
24 Trip Inputs 1or2 w/Bell Out (N)_
✔ [Y], [N]
Use if the zone 1 connection to the control's bell output causes a bell fault on the control panel.
NOTES:
1. If used, EOLR trigger type is not available for zones 1 and 3.
2. Do not use with Lynx controls.
3-12 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
Section 3: Programming the 7845GSM
25 Telco Zone
(0)_
26 Open/Close Zone
(0)_
27 Zn1 Trigger Type
(V+)_
28
29
30
Restore Zn1 Y/N
(Y)_
Delay Zn1 (secs)
(00)_
Rpt Zn1 ONLY if
Armed (N)_
31 Invert Zn2 Y/N
(N)_
TRIG.
✔
2-4204
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
DESCRIPTION
Zone Trig: [3-7]
4204: [1-4]
2-4204: [1-8]
[0] = not used
Zone Trig: [3-7]
4204 : [1-4]
2-4204: [1-8]
[0] = not used
• (EOLR)
• (V+)
• (V–)
[Y], [N]
See "Important Information Regarding Zone
Input Options" on previous page.
Enter the zone number to be used for telco line fault reports. This zone assignment must be unique from the open/close zone selected in
Prompt 26.
Zone Trigger Mode: If any zone is programmed for "report only if armed," zone 7 cannot be used. If Lynx Panic is enabled, zone
3 cannot be used.
4204 Mode: If any zone is programmed for
"report only if armed," zone 4 cannot be used as a telco zone.
2-4204 Mode: If any zone is programmed for
"report only if armed," or if tamper reporting is enabled, zone 8 cannot be used.
NOTE: Connect the telco line fault output (or relay output programmed for "telco line fault") to the telco zone.
Enter the zone number to be used for open/close
(arm/disarm) reports. This zone assignment must be unique from the telco zone selected in
Prompt 25.
Zone Trigger Mode: If any zone is programmed for "report only if armed," zone 7 cannot be used. If Lynx Panic is enabled, zone
3 cannot be used.
4204 Mode: If any zone is programmed for
"report only if armed," zone 4 cannot be used as an open/close zone.
2-4204 Mode: If any zone is programmed for
"report only if armed," or if tamper is enabled, zone 8 cannot be used.
NOTE: Connect an open/close (arm/disarm) trigger (or relay output) from the control panel to the open/close zone.
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Enables restore reporting for zone 1.
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 1.
[Y], [N]
[Y], [N]
Reports alarms on zone 1 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; or zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 1.
Inverts the alarm and normal states of the zone
2 trigger; otherwise uses normal input signal.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-13
7845GSM/7845GSMCN Installation and Setup Guide
32
33
Restore Zn2 Y/N
(Y)_
Delay Zn2 (secs)
(00)_
TRIG.
✔
✔
2-4204
✔
✔
[Y], [N]
[01-15]
Enables restore reporting for zone 2.
Defines the reporting delay in seconds for zone 2.
[00] = no delay
34
Reports alarms on zone 2 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 2.
If Lynx Panic is enabled, then skip to Prompt 39: "Rpt Zn3 ONLY if Armed."
35
Rpt Zn2 ONLY if
Armed (N)_
✔
✔
✔ [Y], [N]
• (EOLR)
• (V+)
• (V–)
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
36
37
38
Zn3 Trigger Type
(V+)_
Invert Zn3 Y/N
(N)_
Restore Zn3 Y/N
(Y)_
Delay Zn3 (secs)
(00)
✔
✔
✔
✔
✔
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
Inverts the alarm and normal states of the zone
3 trigger; otherwise uses normal input signal.
Enables restore reporting for zone 3.
Defines the reporting delay in seconds for zone 3.
39 Rpt Zn3 ONLY if
Armed (N)_
✔ ✔ [Y], [N]
DESCRIPTION
Reports alarms on zone 3 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 3.
4204 mode: If any zone is programmed to
"Report Only if Armed," skip to Prompt 50:
"Enable Zn6."
40
41
Zn4 Trigger Type
(V+)_
Invert Zn4 Y/N
(N)_
✔
✔
• (EOLR)
• (V+)
• (V–)
[Y], [N]
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone
4 trigger; otherwise uses normal input signal.
42 Restore Zn4 Y/N
(Y)_
✔ ✔ [Y], [N] Enables restore reporting for zone 4.
43 Delay Zn4 (secs)
(00)
✔ ✔ [01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 4.
44 Rpt Zn4 ONLY if
Armed (N)_
✔
2-
4204 only
[Y], [N] Reports alarms on zone 4 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 4.
45
46
Zn5 Trigger Type
(V+)_
Invert Zn5 Y/N
(N)_
✔
✔
• (EOLR)
• (V+)
• (V–)
[Y], [N]
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone
5 trigger; otherwise uses normal input signal.
3-14 WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
47
48
Restore Zn5 Y/N
(Y)_
Delay Zn5 (secs)
(00)_
49 Rpt Zn5 ONLY if
Armed (N)_
TRIG.
✔
✔
✔
2-4204
2-
4204 only
2-
4204 only
2-
4204 only
50
51
Enable Zn6 Y/N
(N)_
Zn6 Trigger Type
(V+)_
52
53
54
55
Invert Zn6 Y/N
(N)_
Restore Zn6 Y/N
(Y)_
Delay Zn6 (secs)
(00)_
Rpt Zn6 ONLY if
Armed (N)_
✔
✔
✔
✔
✔
4204 only
4204 only
4204 only
✔
✔
✔
56
57
58
59
60
61
Enable Zn7 Y/N
(N)_
Zn7 Trigger Type
(V+)_
Invert Zn7 Y/N
(N)_
Restore Zn7 Y/N
(Y)_
Delay Zn7 (secs)
(00)_
Rpt Zn7 ONLY if
Armed (N)_
✔
✔
✔
✔
4204 only
4204 only
4204 only
✔
✔
✔
Section 3: Programming the 7845GSM
DESCRIPTION
Enables restore reporting for zone 5. [Y], [N]
[01-15]
[00] = no delay
Defines the reporting delay in seconds for zone 5.
[Y], [N]
[Y], [N]
• (EOLR)
• (V+)
• (V–)
[Y], [N]
Reports alarms on zone 5 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 5.
Enables alarm reporting for zone 6.
If [N], skip to Prompt 56: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
[Y], [N]
Inverts the alarm and normal states of the zone
6 trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
[01-15]
[00] = no delay
[Y], [N]
Defines the reporting delay in seconds for zone 6.
Reports alarms on zone 6 ONLY if the conditional zone (zone 7 in zone trigger mode; zone 4 in 4204 mode; zone 8 in 2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 6.
[Y], [N]
Enables alarm reporting for zone 7, if used.
If [N], skip to Prompt 64: "Review."
• (EOLR)
• (V+)
• (V–)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
Inverts the alarm and normal states of the zone
7 trigger; otherwise uses normal input signal.
Enables restore reporting for zone 7.
Zone Trigger mode: This question will only be displayed if zone 7 is not used as the conditional
(arming) trigger zone.
Defines the reporting delay in seconds for zone 7.
Zone Trigger mode: This question will only be displayed if zone 7 is not used as the conditional
(arming) trigger zone.
Reports alarms on zone 7 ONLY if the conditional zone (zone 4 in 4204 mode; zone 8 in
2-4204 mode) is triggered (armed).
If [N], always reports alarms on zone 7.
2-4204 mode: If any zone is programmed to
"Report Only if Armed," or if tamper is enabled, skip to "Review."
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM
3-15