Non-Volatile Memory. Liebert 3000, Liebert Challenger 3000, CHALLENGER 3000
Add to My manuals76 Pages
advertisement
Operation with Advanced Microprocessor Controls
2.8.2 Non-Volatile Memory
All critical information is stored in nonvolatile memory. Setpoints, setup parameters, and component run hours are kept inside the microcontroller in EEPROM. Information retained for the alarm history is kept in non-volatile RAM.
2.8.3 DIP Switches
Equipment options are selected and enabled using DIP switches 1 through 7. These are located at the upper left of the control board and are labeled SW1. Switch 1 is at the top. These switches are factory set and should not require any user changes. The setting and function of the switches can be read from the LCD display (see Show DIP Switches on page 8 or the accompanying Table 4).
2.8.4 Control Outputs
Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is lit if the control output is active (on). The LEDs assist in troubleshooting the system. Refer to the following table.
Table 6 Control output LEDs
LED
R5
LLSV
HGBP
C1
RH1
RH2
HUM
FAN
HMV
LLSV2
Control Output
Heat Rejection
Liquid Line Solenoid Valve
Hot Gas By-Pass or Compressor Unloader Valve
Compressor
Reheat Stage 1, Hot Gas, Hot Water Reheat Solenoid or SCR Reheats
Reheat Stage 2
Humidifier
Main Fan
Humidifier Make-Up Valve
Part Coil Solenoid Valve
14
DISCONTINUED
PRODUCT
advertisement
Related manuals
advertisement
Table of contents
- 9 System Descriptions
- 9 Compressorized Systems
- 9 GLYCOOLâ„¢ (Chilled Glycol Cooling) Systems
- 9 Chilled Water Systems
- 10 Start-Up Procedure
- 11 Basics
- 13 Status Display
- 13 Main Menu
- 13 Status/Alarm Data
- 13 Active Alarms
- 13 Operating Status
- 13 Alarm History Log
- 14 Run Hours Log
- 14 Analog Sensors
- 14 Setpoints/Setup
- 14 View Setpoints
- 15 Setup System
- 20 Run Diagnostics
- 21 Change Passwords
- 21 Date and Time
- 21 Status Display
- 21 Control Circuit Board
- 21 LCD Display Contrast
- 22 Non-Volatile Memory
- 22 DIP Switches
- 22 Control Outputs
- 23 Basics
- 25 Status Display
- 25 Main Menu
- 25 View/Set Alarms
- 25 Active Alarms
- 25 Alarm History Log
- 26 Setup Alarms
- 27 Setup Custom Alarms
- 27 View Water Detect Floor Plan (for Optional LTM1000/LT750)
- 27 Setup Water Detect Floor Plan
- 28 Operating Status
- 28 View/Set Control Setpoints
- 28 System Setup
- 28 Setup Operation
- 30 Select Options
- 30 Calibrate Sensors
- 30 Calibrate Valve Actuator
- 30 Select Control Algorithm (Chilled Water and SCR Reheats only)
- 31 Select Humidity Sensing Mode
- 31 Set Status Display
- 31 Change Passwords
- 31 Run Diagnostics
- 32 Show Inputs
- 32 Test Outputs
- 32 Test Control Board
- 33 DIP Switches
- 33 Date and Time
- 33 Plot Graphs
- 33 3.10.1 Modify Plot Scales
- 34 Analog/Digital Inputs
- 34 3.11.1 Read Analog Inputs
- 34 3.11.2 Setup Analog Inputs
- 34 3.11.3 Read Digital Inputs
- 34 3.11.4 Setup Digital Inputs
- 34 View Run Hours Log
- 35 3.12.1 View 24 Hour Run Time History
- 35 3.12.2 View Total Run Hours
- 35 Control Circuit board
- 35 3.13.1 LCD Contrast
- 36 3.13.2 Nonvolatile Memory
- 36 3.13.3 DIP Switches
- 36 3.13.4 Control Outputs
- 37 Temperature Control
- 37 Cooling/Heating Required, in Percent (%)
- 37 Response to Control Types
- 38 Cooling Operation
- 39 Heating Operation
- 39 Humidity Control
- 39 Dehumidification/Humidification Required, in Percent
- 39 Response to Control Types
- 39 Dehumidification Operation
- 40 Humidification Operation
- 40 Control Types
- 40 Proportional Control
- 40 PID Control (Chilled Water or SCR Reheats only)
- 41 Intelligent Control (Chilled Water only)
- 42 Load Control Features
- 42 Short Cycle Control
- 42 Sequential Load Activation Control
- 42 Additional Features
- 42 Connecting the Analog Sensors
- 43 Water Detection Display
- 45 Communications
- 46 Standard Alarms
- 46 Change Filter
- 47 Compressor Overload
- 47 Custom Alarms
- 47 High Head Pressure
- 47 High Humidity
- 47 High Humidity and Low Humidity (Simultaneously)
- 47 High Temperature
- 48 High Temperature and Low Temperature (Simultaneously)
- 48 Humidifier Problem
- 48 5.1.10 Loss of Air Flow
- 48 5.1.11 Loss of Power
- 48 5.1.12 Low Humidity
- 48 5.1.13 Low Suction Pressure
- 48 5.1.14 Low Temperature
- 48 5.1.15 Main Fan Overload
- 49 5.1.16 Short Cycle
- 49 Optional/Custom Alarms
- 49 Loss of Water Flow
- 49 Smoke Detected
- 49 Standby GC Pump On
- 49 Standby Unit On
- 49 Water Under Floor
- 50 System Testing
- 50 Environmental Control Functions
- 52 Filters
- 53 Blower Package
- 53 Fan Impellers and Bearings
- 53 Air Distribution
- 54 Refrigeration System
- 54 Suction Pressure
- 54 Discharge Pressure
- 54 Superheat
- 55 Thermostatic Expansion Valve
- 55 Hot Gas Bypass Valve
- 56 Air Cooled Condenser
- 57 Water/Glycol Cooled Condensers
- 59 Compressor Functional Check
- 59 Compressor Replacement