Water Detection Display. Liebert 3000, Liebert Challenger 3000, CHALLENGER 3000

Add to My manuals
76 Pages

advertisement

Water Detection Display. Liebert 3000, Liebert Challenger 3000, CHALLENGER 3000 | Manualzz

Figure 5 Analog input jumpers

System Performance with Advanced Microprocessor Controls

ENLARGED AREA

Analog input jumper location

4.5.2 Water Detection Display

The water detection display is designed to graphically display the location of water under a raised floor when connected to an LT750 water detection system. The graphical floor plan screen shows a 30 x 16 grid. Each square represents one standard floor tile (approximately 2 ft. x 2 ft.).

Installation—LT750 DIP Switch Settings

Install the LT750 following the instructions in the LT750 user manual. The following additional switch selections should be made when connecting to an Advanced Microprocessor control:

• DIP SW3-4—Off-(water alarm relay energizes for alarm)

• DIP SW3-5—Off-(cable fault relay energizes for alarm)

• Switch 1—Off-(LT750 sources power for 4-20 mA loop)

Figure 6 Connecting the LT750

TB6

TB5 fault

3

2

1

2

1

TB4 water

3

2

1

-

+

NO

NO

LT750

4 5

4 6

4 7

4 8

4 1

4 2

4 3

4 4

2 4

5 0

5 1

5 5

5 6

Environmental Unit

35

DISCONTINUED

PRODUCT

System Performance with Advanced Microprocessor Controls

Physical Connections

Figure 6 shows the 4-20 mA output of LT750 connected to Analog Input #1 (41 and 42) on the external inputs terminal strip. This strip is provided on units ordered with analog inputs. (If this strip is not installed, there is a field installation kit available from your Liebert representative.)

The 4-20 mA output of the LT750 must be connected to the first analog input, as shown.

TB4 is the water detected relay output. It can be connected to any one of the four special alarm inputs.

TB5 is the cable fault relay output. It can also be connected to any one of the four special alarm inputs.

Setup

(The following description assumes the wiring connections as shown above.) First, verify that special alarms 1 and 2 are ENABLED to either WARNING or URGENT type. Do this by selecting VIEW/SET

ALARMS from the Main Menu. Then, select SETUP ALARMS. Follow the instructions on the display to select the required type for CUSTOM ALARM #1 and CUSTOM ALARM #2 if not already set.

Next, select the alarm message for CUSTOM ALARM #1 and #2. From the Main Menu, select VIEW/

SET ALARMS. Then, select SETUP CUSTOM ALARMS. Then, select SETUP CUSTOM ALARM

TEXT. Define CUSTOM ALARM #1 to be CUSTOM 1. (CUSTOM 1 is the default message that will be displayed if a message has never been programmed.) Next, select the text for custom alarm #2 to be

WATER UNDER FLOOR. Now, change the message CUSTOM 1 to LT750 CABLE FAULT. This is done by selecting the CHANGE CUSTOM TEXT 1 menu item in the SETUP CUSTOM ALARMS menu. Follow the instructions on the screen to change the message.

The slope and intercept values of Analog Input #1 are used to calculate the location of water. These values should initially be set to zero. The default values are zero, but it may be a good idea to verify those values. They can be viewed by selecting ANALOG/DIGITAL INPUTS from the Main Menu, then SETUP ANALOG INPUTS.

See 3.4.6 - Setup Water Detect Floor Plan for more information.

Calibration

Calibration should not be required for most installations. The accuracy of this display is approximately 1%.

The display is calibrated by the slope and intercept values of Analog Input #1. The position of the water is calculated from the analog output of the LT750 using this formula: position = analog reading/full scale reading x (measured length + slope) + intercept position is the distance from the LT750 to the position of the detected water. measured length is the length of the cable which is calculated automatically when the layout is defined. The units for these values are in floor tiles.

The intercept value read from Analog Input #1 is added to the measured position of a water indication to determine which tile to highlight. For example, if water is displayed under the seventh tile but determined to be under the fifth tile, set the offset value to -2 tiles. Use the intercept value to correct errors close to the start of the cable.

Accuracy errors farther out on the cable should be corrected using Analog Input #1's slope value. This value effectively adjusts the measured length of the cable. Increasing the effective length of cable will increase the distance of the water and move the highlighted tile farther along the cable, and vice versa. Unlike the intercept, which adjusts by the same amount for all locations on the cable, the slope increases its effect for larger distances.

The best procedure to calibrate the cable would be to first simulate water close to the LT750, about five tiles out. Adjust the intercept to get the correct reading. Next, simulate water five tiles from the end. Adjust the slope to get the correct reading.

36

DISCONTINUED

PRODUCT

advertisement

Related manuals

advertisement

Table of contents