Load Control Features. Liebert 3000, Liebert Challenger 3000, CHALLENGER 3000
Add to My manuals76 Pages
advertisement
System Performance with Advanced Microprocessor Controls
4.4
Load Control Features
4.4.1 Short Cycle Control
The control system monitors the compressor and prevents it from turning on within 3 minutes of being turned off. If this (on, off, on) occurs too often, 10 times in one hour, a Short Cycle alarm could occur.
4.4.2 Sequential Load Activation Control
The control allows only one load output to be energized at a time on a restoration of power or microcontroller reset. Each additional load output will be activated at one second intervals until desired operating conditions have been met.
4.5
Additional Features
4.5.1 Connecting the Analog Sensors
The sensor inputs are factory set to accept a 4 - 20 mA signal. However, the inputs can be changed by removing the appropriate jumpers on the control circuit board. See Table 14, Figure 5 and
Figure 6 .
The user supplied analog sensors MUST have their own power supply. To reduce the effects of interference from any noise source, the sensor input wiring should be shielded twisted pair and the shield tied to earth ground at one end.
Analog input terminals for field connections are factory wired to the microprocessor board if specified when ordered. Eight terminals are located in the field wiring compartment of the unit. Wire sensors to the terminals as follows:
Table 14 Analog input terminals
Terminal
41
42
43
44
45
46
47
48
Signal
Input #1 (+)
Input #1 (–)
Input #2 (+)
Input #2 (–)
Input #3 (+)
Input #3 (–)
Input #4 (+)
Input #4 (–)
Consult your Liebert supplier for a field installation kit to add these connections after unit delivery, if required.
Table 15 Additional connections available after unit delivery
Input #1 Input #2 Input #3 Input #4
4–20 mA
0–5 VDC
Jumper P50.1 & 2 and P50.3 & 4
Jumper P50.1 & 2
0–10 VDC NO Jumper on P50.1 & 2 and P50.3 & 4
Jumper P50.5 & 6 and P50.7 & 8
Jumper P50.5 & 6
NO Jumper on P50.5 & 6 and P50.7 & 8
Jumper P50.9 &10 and P50.11 & 12
Jumper P50.9 & 10
NO Jumper on P50.9 &10 and P50.11 & 12
Jumper P50.13 &14 and P50.15 & 16
Jumper P50.13 & 14
NO Jumper on P50.13 & 14 and P50.15 & 16
34
DISCONTINUED
PRODUCT
advertisement
Related manuals
advertisement
Table of contents
- 9 System Descriptions
- 9 Compressorized Systems
- 9 GLYCOOLâ„¢ (Chilled Glycol Cooling) Systems
- 9 Chilled Water Systems
- 10 Start-Up Procedure
- 11 Basics
- 13 Status Display
- 13 Main Menu
- 13 Status/Alarm Data
- 13 Active Alarms
- 13 Operating Status
- 13 Alarm History Log
- 14 Run Hours Log
- 14 Analog Sensors
- 14 Setpoints/Setup
- 14 View Setpoints
- 15 Setup System
- 20 Run Diagnostics
- 21 Change Passwords
- 21 Date and Time
- 21 Status Display
- 21 Control Circuit Board
- 21 LCD Display Contrast
- 22 Non-Volatile Memory
- 22 DIP Switches
- 22 Control Outputs
- 23 Basics
- 25 Status Display
- 25 Main Menu
- 25 View/Set Alarms
- 25 Active Alarms
- 25 Alarm History Log
- 26 Setup Alarms
- 27 Setup Custom Alarms
- 27 View Water Detect Floor Plan (for Optional LTM1000/LT750)
- 27 Setup Water Detect Floor Plan
- 28 Operating Status
- 28 View/Set Control Setpoints
- 28 System Setup
- 28 Setup Operation
- 30 Select Options
- 30 Calibrate Sensors
- 30 Calibrate Valve Actuator
- 30 Select Control Algorithm (Chilled Water and SCR Reheats only)
- 31 Select Humidity Sensing Mode
- 31 Set Status Display
- 31 Change Passwords
- 31 Run Diagnostics
- 32 Show Inputs
- 32 Test Outputs
- 32 Test Control Board
- 33 DIP Switches
- 33 Date and Time
- 33 Plot Graphs
- 33 3.10.1 Modify Plot Scales
- 34 Analog/Digital Inputs
- 34 3.11.1 Read Analog Inputs
- 34 3.11.2 Setup Analog Inputs
- 34 3.11.3 Read Digital Inputs
- 34 3.11.4 Setup Digital Inputs
- 34 View Run Hours Log
- 35 3.12.1 View 24 Hour Run Time History
- 35 3.12.2 View Total Run Hours
- 35 Control Circuit board
- 35 3.13.1 LCD Contrast
- 36 3.13.2 Nonvolatile Memory
- 36 3.13.3 DIP Switches
- 36 3.13.4 Control Outputs
- 37 Temperature Control
- 37 Cooling/Heating Required, in Percent (%)
- 37 Response to Control Types
- 38 Cooling Operation
- 39 Heating Operation
- 39 Humidity Control
- 39 Dehumidification/Humidification Required, in Percent
- 39 Response to Control Types
- 39 Dehumidification Operation
- 40 Humidification Operation
- 40 Control Types
- 40 Proportional Control
- 40 PID Control (Chilled Water or SCR Reheats only)
- 41 Intelligent Control (Chilled Water only)
- 42 Load Control Features
- 42 Short Cycle Control
- 42 Sequential Load Activation Control
- 42 Additional Features
- 42 Connecting the Analog Sensors
- 43 Water Detection Display
- 45 Communications
- 46 Standard Alarms
- 46 Change Filter
- 47 Compressor Overload
- 47 Custom Alarms
- 47 High Head Pressure
- 47 High Humidity
- 47 High Humidity and Low Humidity (Simultaneously)
- 47 High Temperature
- 48 High Temperature and Low Temperature (Simultaneously)
- 48 Humidifier Problem
- 48 5.1.10 Loss of Air Flow
- 48 5.1.11 Loss of Power
- 48 5.1.12 Low Humidity
- 48 5.1.13 Low Suction Pressure
- 48 5.1.14 Low Temperature
- 48 5.1.15 Main Fan Overload
- 49 5.1.16 Short Cycle
- 49 Optional/Custom Alarms
- 49 Loss of Water Flow
- 49 Smoke Detected
- 49 Standby GC Pump On
- 49 Standby Unit On
- 49 Water Under Floor
- 50 System Testing
- 50 Environmental Control Functions
- 52 Filters
- 53 Blower Package
- 53 Fan Impellers and Bearings
- 53 Air Distribution
- 54 Refrigeration System
- 54 Suction Pressure
- 54 Discharge Pressure
- 54 Superheat
- 55 Thermostatic Expansion Valve
- 55 Hot Gas Bypass Valve
- 56 Air Cooled Condenser
- 57 Water/Glycol Cooled Condensers
- 59 Compressor Functional Check
- 59 Compressor Replacement