THE BATTERY MODULE. Ever Superline 11, 3 x 28 x 7Ah, Superline 11, 1 x 28 x 7Ah, Poweline 11, 2 x 28 x 7Ah
Add to my manuals
41 Pages
advertisement
Instruction Manual for SUPERLINE series battery back-ups
THE BATTERY MODULE
Battery back-ups from the SUPERLINE series offer the option of connecting additional battery modules. Modules are connected to connection clamps located on the rear panel of the battery back-up. Connecting battery modules extends the time of battery operation mode. Battery modules are installed in a series and are safeguarded with additional cut-offs located on their rear panels.
WARNING! If the fuses burn out, they should be replaced in accordance with the specification.
Connecting the modules
Figure 11: Connecting battery modules
WARNING! With the safeguards active there is hazardous, and possibly lethal, voltage on the connection clamps. Disable all safeguards before commencing any installation works!
1. Turn off the battery back-up via the user interface (KONTROLA 1/4; UPS).
2. Switch the F3 and F4 circuit breakers to OFF.
3. Disable all accumulator safeguards (F1, F2 and F5) by opening the fuse holders. There is no fixed order to do this. Remove the fuse-elements.
4. Disable all accumulator safeguards for the already connected battery modules and those being connected by opening the fuse holders and removing the fuseelements.
5. Disable the safeguards of the basic and BYPASS lines on the switchboard of the room/building.
6. Remove the protective stoppers from connectors (rear panels of the battery back-up and modules).
7. Connect the module to the battery back-up, ensuring correct terminal polarity.
Modules are connected in a series: UPS to first module, then first module to second module, second module to third module and so on. Protective earthing cables from each device are connected to a common point in the room’s/building’s switching station.
2010/01/13 www.ever.eu
23
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 TABLE OF CONTENTS
- 3 INTRODUCTION
- 3 GENERAL INFORMATION
- 3 PURPOSE OF THE DEVICE
- 3 GENERAL FEATURES
- 5 ELEMENTS OF THE BATTERY BACK-UP
- 6 USER INTERFACE
- 8 SCREENS
- 8 Main menu
- 9 The POMIARY (MEASUREMENTS) submenu
- 11 The KONTROLA (CONTROL) submenu
- 13 The KONFIGURACJA (CONFIGURATION) submenu
- 15 The ALARMY (ALERTS) submenu
- 17 The STATYSTYKA (STATISTICS) submenu
- 18 The USTAWIENIA PANELU (PANEL SETTINGS) submenu
- 19 The IDENTYFIKACJA (IDENTIFICATION) submenu
- 20 SAFETY AND HEALTH INSTRUCTIONS
- 20 HANDLING
- 20 ELECTRIC SAFETY
- 21 INSTALLATION
- 21 UNPACKING
- 22 INSTALLATION OF THE BATTERY BACK-UP
- 23 THE BATTERY MODULE
- 23 Connecting the modules
- 24 Disconnecting the modules
- 25 CONNECTING THE BATTERY BACK-UP
- 25 Connection terminals
- 26 Electric system
- 27 STARTING THE BATTERY BACK-UP
- 27 POWERING OFF AND DISCONNECTING THE BATTERY BACK-UP
- 28 OPERATING MODES OF THE BATTERY BACK-UP
- 30 OTHER FUNCTIONAL ELEMENTS
- 30 Safeguards
- 32 Manual BYPASS
- 33 COMMUNICATION BETWEEN THE UPS AND A COMPUTER
- 33 COMMUNICATION VIA RS232 OR USB
- 33 EVER SNMP/HTTP NETWORK CONTROL CARD
- 35 INSTALLATION AND CONFIGURATION OF THE POWERSOFT PERSONAL SOFTWARE
- 35 Installation on computers with Windows
- 35 Installation on computers with Linux/Unix
- 36 Software updates
- 37 ADDITIONAL REMARKS
- 38 BATTERY BACK-UP AND POWER GENERATORS
- 38 STORAGE, MAINTENANCE AND TRANSPORT
- 38 DISPOSAL
- 39 TECHNICAL PARAMETERS
- 39 INSTALLATION GUIDELINES
- 40 TECHNICAL DATA
- 41 INFORMATION REGARDING REGULATIONS AND WARRANTY
- 41 DECLARATION OF CONFORMITY
- 41 WARRANTY