T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

INTRODUCTION

Device Description

The T7350H is a L

ON

M

ARK®

certified thermostat that provides networking capability in a L ON W ORKS® system using a transformer-coupled Free Topology Transceiver (FTT). See

Fig. 1.

The T7350H communicates with many L ON M ARK® devices including the following:

— Other T7350H Communicating Commercial Thermostat devices.

— T7300F/Q7300H Commercial Thermostat/Communicating

Subbase.

— Excel 15 S7760A Command Display.

— Excel 10 W7750A,B,C Constant Volume Air Handler Unit

(CVAHU) Controller.

— Excel 15 W7760A, B, C Building & Plant Managers.

— Excel 10 W7751B, D, F, H, J Variable Air Volume Terminal

Unit Controllers.

— Excel 10 W7752D, E, F, G Fan Coil Unitcontrollers.

— Excel 10 W7753A Unit Ventilator Controller.

— Excel 10 W7762A,B Hydronic Controllers.

— Excel 10 W7763C, D, E Chilled Ceiling Controllers.

Control Application

The T7350H programmable communicating Thermostat controls commercial single zone heating, ventilating and air conditioning (HVAC) equipment through staged and modulating outputs. The T7350H consists of a two piece assembly with a thermostat cover and subbase. The thermostat cover includes the keypad and display for 7-day programming. Calendar programming is available through a direct connect PDA (Configuration Tool) or network

(L ON S PEC ™ with model T7350H) tool configuration. The subbase includes equipment control, inputs and network connections. The subbase mounts on the wall and the thermostat cover mounts to the subbase. In addition, the

T7350H model can communicate local sensor data, schedule information, master clock operations and accept configuration and override instructions to or from other devices/tools in a

L

ON

W

ORKS®

network. Fig. 9 shows a typical T7350H

application in a three-stage heat and two-stage cool heat

pump system. For additional hookups, see Fig. 10 through 12.

NOTEBOOK PC

BUILDING MANAGER

1 4 8 12 16

EXCEL 15

W7760

EXCEL 10

CVAHU

WALL MODULE

17 23 30 31 37 44

RS-232

SERIAL

PORT

SLTA

S7760

LonWorks BUS

T7350H

Back Select

MODEM

MODEM

BUILDING MANAGER

1 4 8 12 16

EXCEL 15

W7760

RS-232

SERIAL

PORT

SLTA

17 23 30 31 37 44

S7760

EXCEL 10

CVAHU

LonWorks BUS

Back Select

Fig. 1. Typical T7350H L ON W ORKS® network diagram.

WALL MODULE

T7350H

M22490