T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

Cable Termination

The FTT network segment requires termination for proper data transmission performance. Use a 209541B Termination

Module to connect two of the three termination module wires to the L

ON

W

ORKS®

Bus terminals. Refer to L

ON

W

ORKS®

Bus

Wiring Guidelines form 74-2865 for details.

Singly Terminated Network Segment

In a singly terminated topology segment, only one termination is required and can be placed anywhere on the segment.

Singly terminated segments use the yellow and brown wires.

If the network topology requires a singly terminated termination module at a T7350H, connect the singly terminated module wiring on the appropriate terminals as

shown in Fig. 6

.

SUBBASE

T5 T6 T7 T4 T3 OS OS AS AS AUX W3/Y4 Y3 W2 Y2

EB EB HS HC HP M M X RH RC AUX W1 Y1 G

BROWN YELLOW

PART NO. 209541B

TERMINATION MODULE

ORANGE M22494

Fig. 6. Singly terminated LonWorks® bus termination module.

Doubly Terminated Daisy-Chain Network Segment

In a doubly terminated daisy-chained topology segment, two terminations are required, one at each end of the topology segment. Doubly terminated segments use the orange and brown wires. If the network topology requires a doubly terminated module at a T7350H (T7350H is the first or last device on the network cable) connect the termination module

wiring on the appropriate terminals as shown in Fig. 7. For

additional wiring information, refer to the E-Bus Wiring

Guidelines, form 74-2865, and the Excel 10 FTT Termination

Module Installation Instructions, form 95-7554.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment circuitry.

Disconnect power supply before installation.

IMPORTANT

All wiring must agree with applicable codes, ordinances and regulations.

1. Loosen subbase terminal screws and connect system wires.

NOTE: Maximum (and recommended) wire size is 18gauge. Do not use wire smaller than 22-gauge. Follow equipment manufacturer wiring instructions when available. Refer to the Wiring Diagram section for typical hookups. A letter code is located near each terminal for identification. Refer to the Specifications section, Tables 8 and 9 for terminal designations.

2. Securely tighten each terminal screw.

3. Push excess wire back into the hole in the wall.

4. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.

Wiring Details

L

ON

W

ORKS®

network cable should be wired separately from the power and I/O wires when installing T7350H models. If this is not possible, use a minimum of 4 in. (102 mm) separation between split ferrite cores (Fair-Rite 0443164151, www.fair-rite.com) to ensure compliance with Class B limits

(does not apply to Class A limits). See Fig. 8 to apply ferrite

cores to L

ON

W

ORKS®

Bus input and output.

Step 4. Prepare Wiring Diagrams

Fig. 9 through 12

show T7350 terminal arrangements and provide detailed wiring diagrams. Reference these diagrams to prepare the site-specific job drawings.

1.

WIRES TO T7300H

COMMUNICATING SUBBASE

SUBBASE

T5 T6 T7 T4 T3 OS OS AS AS AUX W3/Y4 Y3 W2 Y2

EB EB HS HC HP M M X RH RC AUX W1 Y1 G

WIRES TO ALL

INPUTS AND

OUTPUTS

2.

BROWN ORANGE

PART NO. 209541B

TERMINATION MODULE

YELLOW M22495

Fig. 7. Doubly terminated L ON W ORKS® bus termination modules.

WIRES TO ALL

INPUTS AND

OUTPUTS

M22496

WIRES TO T7300H

COMMUNICATING SUBBASE

Fig. 8. Ferrite core wires from T7350H to L ON W ORKS® inputs and outputs.

63-4368 12

T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

T7770 REMOTE SENSOR

9 8 7 6 5 4 3 2 1

OUTDOOR

AIR

SENSOR

4

ECONOMIZER

COMPRESSOR

CONTACTOR 2

DISCHARGE

AIR

SENSOR

HEAT

RELAY 3

HEAT

RELAY 2

SUBBASE

T5 T6 T7 T4 T3 OS OS AS AS AUX W3/Y4 Y3 W2 Y2

EB EB HS HC HP M M X RH RC AUX W1 Y1 G

COMPRESSOR

CONTACTOR 3

L

ON

W

ORKS

®

BUS

L ON W ORKS

®

BUS

1 2

L2

L1

(HOT)

HUMIDITY

SENSOR

MOTION

SENSOR

3 HEAT

RELAY 1

FAN

RELAY

COMPRESSOR

CONTACTOR 1

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2

3

ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.

HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.

4 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

M22499

Fig. 9. Typical hookup of T7350H1009 in three-stage heat and three-stage cool conventional system with one transformer.

T7770 REMOTE SENSOR

9 8 7 6 5 4 3 2 1

OUTDOOR

AIR

SENSOR

COMPRESSOR

CONTACTOR 2

DISCHARGE

AIR

SENSOR

HEAT

RELAY 3

HEAT

RELAY 2

SUBBASE

T5 T6 T7 T4 T3 OS OS AS AS AUX W3/Y4 Y3 W2 Y2

EB EB HS HC HP M M X RH RC AUX W1 Y1 G

COMPRESSOR

CONTACTOR 3

L ON W ORKS

®

BUS

HUMIDITY

SENSOR

MOTION

SENSOR

3 HEAT

RELAY 1

FAN

RELAY

L ON W ORKS

®

1

BUS 4

ECONOMIZER

COMPRESSOR

CONTACTOR 1

L2

2

L1

(HOT)

L2

L1

(HOT)

AUXILIARY

TRANSFORMER

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2

3

ENSURE TRANSFORMER IS SIZED TO HANDLE THE LOAD.

HEAT/COOL SYSTEMS WITH ONE TRANSFORMER REQUIRE THE FACTORY-INSTALLED JUMPER.

4 USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

M22497

Fig. 10. Typical hookup of T7350H1009 with auxiliary transformer.

13 63-4368

T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT

T7770 REMOTE SENSOR

OUTDOOR

AIR

SENSOR

9 8 7 6 5 4 3 2 1

DISCHARGE

AIR

SENSOR

MODULATING

+

HEAT

(4-20 mA)

SUBBASE

T5 T6 T7 T4 T3 OS OS AS AS AX AH AC

R

X

AUX

MODULATING

– COOL

+ (4-20 mA)

R

X

EB EB HS HC HP M M X RH

2

RC AUX W1 Y1 G

L ON W ORKS

®

BUS

L ON W ORKS

®

BUS

HUMIDITY

SENSOR

MOTION

SENSOR

HEAT

RELAY 1

FAN

RELAY

3

ECONOMIZER

COMPRESSOR

CONTACTOR 1

1

L2

L1

(HOT)

HEATING

TRANSFORMER

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2

3

WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.

USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

COOLING

TRANSFORMER

L2

L1

(HOT)

1

M22498

Fig. 11. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating), two independent cool stages (one modulating), and two transformers.

T7770 REMOTE SENSOR

9 8 7 6 5 4 3 2 1

OUTDOOR

AIR

SENSOR

DISCHARGE

AIR

SENSOR

MODULATING

+

HEAT

(4-20 mA)

SUBBASE

T5 T6 T7 T4 T3 OS OS AS AS MX MH MC

R

X

AUX

MODULATING

+

COOL

(4-20 mA)

R

X

HS HC HP M M X RH

2

RC AUX W1 Y1 G

L ON W ORKS

®

BUS

L ON W ORKS

®

BUS

HUMIDITY

SENSOR

MOTION

SENSOR

HEAT

RELAY 1

FAN

RELAY

3

ECONOMIZER

COMPRESSOR

CONTACTOR 1

1

L2

L1

(HOT)

HEATING

TRANSFORMER

L2

L1

(HOT)

AUXILIARY

TRANSFORMER

1

2

3

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

WHEN INSTALLED ON A SYSTEM WITH TWO TRANSFORMERS, REMOVE THE FACTORY-INSTALLED JUMPER.

USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

COOLING

TRANSFORMER

L2

L1

(HOT)

1

M22491

Fig. 12. Typical hookup of T7350H1017 for system with two independent heat stages (one modulating), two independent cool stages (one modulating), and three transformers.

63-4368 14