advertisement
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
L ON M ARK®
Functional Profile
Hardware Output
Node
Object nv1 nviRequest
SNVT_obj_request
Mandatory
Network
Variables nv2 nvoStatus
SNVT_ obj_status nv3 nviTimeSet
SNVT_ time_stamp nv5 nviFileReq
SNVT_file_req nv7 nviFilePos
SNVT_file_pos nc1 - nciDeviceName nc2 - nciApplVer
Optional
Network
Variables
UCPTdevName
UCPTapplVer nv6 nvoFileStat
SNVT_file_status
Configuration Properties
(manf specific)
(manf specific)
Hardware Output nv1 nviSpaceTemp
SNVT_temp_p
SCC-Rooftop
Object Number 8504.
Mandatory
Network
Variables nv26 nvoSpaceTemp
SNVT_ temp_p nv2 nviSetpoint
SNVT_ temp_p nv5 nviOccSchedule
SNVT_tod_event nv6 nviOccManCmd
SNVT_occupancy nv7 nviOccSensor
SNVT_occupancy nv8 nviApplicMode
SNVT_hvacMode
Optional
Network
Variables nv28 nvoEffectSetpt
SNVT_temp_p nv29 nvoEffectOccup
SNVT_occupancy nv30 nvoHeatCool
SNVT_hvac_mode nv34 nvoDischAirTemp
SNVT_temp_p nv37 nvoTerminalLoad
SNVT_lev_percent nv43 nvoSpaceRH
SNVT_lev_percent nv45 nvoOutdoorTemp
SNVT_temp_p nv9 nviInUse
UNVT_inUse nv10 nviPgm
UNVT_pgmIn
Manufacturer
Defined
Section nv11 nroT7350Ver
UNVT_version nv12 nroPgmVer
UNVT_pgmId nv13 nvoPgm
UNVT_pgmOut nv14 nvoTime
SNVT_time_stamp nv15 nvoAlarmH
UNVT_alarm nv16 nvoAlarmStatus
UNVT_alarmStatus nv17 nvoAlarmLog
UNVT_alarmLog nv18 nvoError
UNVT_error nc1 - nciSndHrtBt nc4 - nciRevHrtBt nc2 - nciSetpoints nc6 - nciBypassTime
nciConfig
nciConfigPts
nciDayLghtSav
nciDaySchedule0
nciDaySchedule1
nciDaySchedule2
nciDaySchedule3
nciDaySchedule4
nciDaySchedule5
nciDaySchedule6
nciDaySchedule7
nciHolSched
Configuration Properties
SNVT_time_sec
SNVT_time_sec
SNVT_temp_setpt
SNVT_time_min
UCPTconfig
UCPTconfigPts
UCPTdaylightSav
UCPTschedule0
UCPTschedule1
UCPTschedule2
UCPTschedule3
UCPTschedule4
UCPTschedule5
UCPTschedule6
UCPTschedule7
UCPTholSched
(mandatory)
(optional)
(mandatory)
(optional)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
(manf specific)
Hardware Input nv30 nviBypass
SNVT_switch nv31 nviFanAuto
SNVT_switch nv32 nviManValue
UNVT_manValue nv34 nviDlcShed
UNVT_dlcShed
Manufacturer
Defined
Section nv43 nvoBypass
SNVT_switch nv44 nvoOccSchedule
SNVT_tod_event nv45 nvoOccSensor
SNVT_occupancy nv46 nvoData1
UNVT_data1 nv47 nvoData2
UNVT_data2
Hardware Input
Fig. 3. T7350H L
ON
M
ARK®
Space Comfort Controller Rooftop Object (8504) with Node Object.
M22431
63-4368 8
T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
NETWORK CONFIGURATIONS
The T7350H can be configured to perform a variety of activities in which data is sent to and/or received from other nodes on the L ON W ORKS® network. Information that can be shared with other network devices includes:
— Current year, month, day, hour, minute, second.
— System mode (HEAT, COOL, AUTO, OFF, EM HEAT).
— Current fan setting (ON, AUTO).
— Space temperature.
— Space relative humidity.
— Discharge air temperature.
— Outdoor air temperature.
— Occupancy sensor status.
— Terminal load.
— Current setpoint.
— Occupied/Unoccupied schedule commands.
— Current occupancy status.
— Occupancy schedule including current occupancy state, next state and time in minutes until next scheduled change of occupancy state.
— Relay status (heat/cool stages and fan).
— Alarm status.
— Alarm log including the last five alarms.
— Device Error status.
— Bypass state (multiple XL10 devices follow the bypass operation of a master device).
A network configuration tool is used to configure the T7350H
Thermostats and other nodes with which the T7350H interacts. The following is a brief description of the configurable features that can be commanded over the network:
• Time Master:
When a T7350H is designated as the network time master, the current time of day and date is synchronized across the network every minute. The L ON S PEC ™ T7350H General
Screen can be used to configure a T7350H as the Network
Time Master. Whenever the time of day or date of the time master is changed, it automatically adjusts all the other network devices (T7350H, Q7300 & XL15A) bound to the time master. When a T7350H is controlled by a time master, the local day light saving schedule is disabled. The
Day Light Saving option on all time master recipients should be disabled. This prevents erroneous time changes
(local daylight savings switchover) during temporary network outages.
Source
T7350H.nvoTime or
XL15a.nvoTimeOut
Q7300.nvoTime
Destination
T7350H.nviTimeSet or
XL15a.nviTimeIn
Q7300.nviTime
the user is not prevented from making local schedule changes at the recipient thermostat. Local schedule changes (at a recipient device) have no effect on the scheduling commands received from the master device.
When a T7350H is designated as a master schedule device, it sends its schedule information (current state, next state, time until next change of state) to the appropriate T7350H(s) which, in turn, overrides any existing internal time schedule. The T7350H Thermostat can provide master scheduling information to multiple
Excel 10 devices. One T7350H shares the schedule information (current state, next state, time until next change of state) with the designated Excel 10 devices.
Source
T7350H.nvoOccSchedule or
XL15a.nvoTodEventCmd[i]
Q7300.nvoOccSchedulei
Destination
T7350H.nviOccSchedule or
XL10.nviTodEvent
XL15c.nviTodEventIn[i]
• System Mode Settings:
System mode settings (HEAT, COOL, AUTO, OFF, EM
HEAT) can be commanded by a remote T7350H or other compatible XL10 device. A one to many network binding can be used to command multiple devices from a single unit. In addition, a network connected Workstation can be used to change the System Mode.
Command Source
T7350H.nvoHeatCool or Workstation
Command Destination
T7350H.nviApplicMode
• Fan Settings:
Fan settings (ON, AUTO) can be changed from a network connected Workstation.
Source
Workstation or Network Tool
Destination
T7350H.nviFanAuto
• Outdoor Air Temperature Sharing:
If a valid outdoor air temperature value is received at the
T7350H OAT network variable input, that value will be used in the T7350H. The local OAT sensor of the T7350H is ignored until the network sensor fails.
Source
T7350H.nviOutdoorTemp or
XL10.nvoOdTemp
XL15c.nvoOdTemp
Destination
T7350H.nvoOutdoorTemp or
XL10.nviOdTemp
XL15c.nviOdTemp
• Time Schedule:
The occupancy schedule used by a T7350H may reside locally in that device or remotely in another schedule device (T7350H, XL15a, XL15b or T7300/Q7300). Local schedules can be created and modified using the T7350H keypad, a direct connected PDA, a network connected configuration tool (L ON S PEC ™) or Command Display.
External schedules can also be modified using the keypad of the master schedule device, or with a network connected configuration tool or Workstation. When a
T7350H receives scheduling information over the network,
9
• Discharge Air Temperature Sharing:
The discharge air temperature value can be shared with other devices on the network. Note that the T7350H does not accept a network discharge air temperature input.
Source
T7350H.nvoDischAirTemp
Destination
XL15c.nviDATemp
• Space Temperature Sharing:
If a valid space temperature value is received at the
T7350H Space Temperature network variable input, that
63-4368
advertisement
Related manuals
advertisement
Table of contents
- 2 Device Description
- 2 Control Application
- 3 Network Control Provided
- 3 Products Covered
- 4 Applicable Literature
- 5 Performance Specifications
- 7 Communications
- 8 LonMark® Functional Profile
- 10 Overview
- 11 Step 1. Plan the System
- 11 Step 2. Determine Required Network Devices
- 11 Step 3. Layout Communications and Power Wiring:
- 11 LonWorks® Bus Layout
- 12 Cable Termination
- 12 Wiring Details
- 12 Step 4. Prepare Wiring Diagrams
- 15 General Considerations
- 17 Step 5. Order Equipment
- 17 Step 6. Configure T7350
- 18 Step 7. Troubleshooting
- 33 S7760 - Command Display
- 44 Class Description