- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- TRIANGLE TUBE
- PEA110
- User manual
advertisement
5.0
Installing Vent/Combustion Air & Condensate Drain
SECTION V - INSTALLING VENT
/ COMBUSTION AIR &
CONDENSATE DRAIN
5.1
Installing Vent and Combustion Air
WARNING
Ensure installation of the condensate drain assembly included the metal washer. Failure to comply could result in the trap assembly dislocating from the boiler.
DANGER
The PRESTIGE Excellence must be vented and supplied with combustion air as shown in the PRESTIGE Excellence Vent
Supplement, included in the boiler installation envelope. Refer to optional vent kit instructions for additional vent installation instructions. Once installation is completed, inspect the vent and combustion air system thoroughly to ensure systems are airtight and comply with the instructions given in the venting supplement and are within all requirements of applicable codes. Failure to comply with the installation requirements on the venting and combustion air piping will cause severe personal injury or death.
5.2
Installing Condensate Drain
Assembly ensure the metal washer is installed as shown in Fig. 11 on page 23.
NOTICE
The installer may want to fill the condensate trap with water prior to assembling on the unit.
2. Install the condensate drain assembly on the boiler condensate drain by pushing the condensate drain assembly up until it stops.
WARNING
Ensure the condensate drain assembly contains the plastic seated ball. Do not install the condensate drain assembly if the ball is lost or missing, replace the entire assembly.
4. Remove the compression nut and rubber seal from the condensate drain assembly drain outlet.
5. Using 3/4” x 2’ flexible PVC tube provided, slide the compression nut and rubber seal over the pipe
NOTICE also acceptable. If 3/4” pipe is used deburr and chamfer pipe to allow mating onto the drain assembly.
6. Thread the rubber seal into the compression nut to ease installation of the pipe to the drain assembly.
7. Seat the pipe onto the drain assembly and tighten the compression nut. Hand tight only!
NOTICE
The installer may opt to use 13/16" ID tubing in lieu of rigid piping.
3. Tighten the condensate drain assembly retaining nut with rubber seal.
22 664A0100 - Rev. A
5.0
Installing Vent/Combustion Air & Condensate Drain
NOTICE
The drain line materials must be an approved material by the authority having jurisdiction. In absence of such authority, PVC and CPVC piping must comply with ASTM D1785 or D2845.
The cement and primer used on the piping must comply with ASME D2564 or
F493. For installations in Canada, use
CSA or ULC certified PVC or CPVC pipe, fittings and cement/primer.
8. Continue the pipe from the drain assembly to a floor drain or condensate pump.
9. The PRESTIGE Excellence will typically produce a condensate that is considered slightly acidic with a pH content below 3.0.
Install a neutralizing filter if required by authority having jurisdiction.
CAUTION
The condensate drain must remain filled and unobstructed and allow unrestricted flow of condensate. The condensate should not be subject to conditions where freezing could occur. If the condensate is subjected to freezing or becomes obstructed , it can leak, resulter and surrounding area.
NOTICE
When selecting and installing a condensate pump, ensure the pump is approved naces. The pump should be equipped with an overflow switch to prevent property damage from potential condensate spillage.
Fig. 11: Condensate Drain Assembly
664A0100 - Rev. A 23
advertisement
Related manuals
advertisement
Table of contents
- 8 Qualified Installer
- 9 1.1 Code Compliance
- 9 1.2 Determining Product Location
- 9 1.3 Boiler Replacement
- 10 1.4 Recommended Clearances
- 10 1.5 Residential Garage Installations
- 10 1.6 Boiler Freeze Protection Feature
- 11 2.1 Combustion Air Contamination
- 12 2.2 Ventilation and Combustion Air Requirements - Direct Vent
- 12 2.3 Ventilation and Combustion Air Requirements - Category IV
- 13 2.4 Methods of Accessing Combustion Air Into A Space - Category IV
- 13 2.4.1 Indoor Combustion Air Opening Size and Location
- 13 2.4.2 Outdoor Combustion Air Opening Size and Location
- 13 2.4.2.1 One Permanent Opening Method
- 14 2.4.2.2 Two Permanent Openings Method
- 15 2.4.3 Combination of Indoor and Outdoor Combustion Air
- 15 2.5 Combustion Air and Vent Piping
- 16 2.6 Removal of an Existing Boiler from a Common Vent System
- 17 2.7 Commonwealth of Massachusetts Installations Only
- 18 3.1 Handling Instructions
- 18 3.2 Wall Mounting Installation
- 18 3.3 Wall Mounting Guidelines
- 19 3.4 Wall Bracket Installation - Stud Wall Installation
- 19 3.5 Wall Bracket Installation - Solid Walls
- 19 3.6 Boiler Mounting
- 20 4.1 General Piping Requirements
- 20 4.2 Pressure Relief Valve
- 20 4.3 Boiler Air Vent
- 21 4.4 Low Water Cutoff Device
- 21 4.5 Additional Limit Control
- 22 4.6 Backflow Preventer
- 22 4.7 Boiler System Piping Applications
- 22 4.8 Expansion Tank and Makeup Water
- 22 4.8.1 Diaphragm Expansion Tank
- 22 4.8.2 Closed-Type Expansion Tank
- 23 4.10 Sizing Primary Piping
- 23 4.11 Domestic Hot Water System Piping
- 23 4.12 System Piping - Zone Circulators
- 23 4.13 System Piping - Zone Valves
- 23 4.14 System Piping - Through Boiler
- 23 4.15 System Piping - Radiant Heating
- 24 4.16 System Piping - Special Application
- 28 5.1 Installing Vent and Combustion Air
- 28 5.2 Installing Condensate Drain Assembly
- 30 6.1 Gas Supply Piping Connection
- 31 6.2 Natural Gas
- 31 6.2.1 Pipe Sizing
- 31 6.2.2 Supply Pressure Requirements
- 32 6.3 Propane Gas
- 32 6.3.1 Pipe Sizing - Propane Gas
- 32 6.3.2 Propane Gas Supply Pressure Requirements
- 34 7.1 General Requirements
- 34 7.2 Fuse Locations
- 36 8.1 Installation Compliance
- 36 8.2 Line Voltage Connections
- 36 8.3 Circulator Wiring
- 37 8.4 Alarm Wiring
- 37 8.5 Low Voltage Connections
- 37 8.6 Thermostat Wiring
- 38 8.7 Outdoor Sensor Wiring
- 38 8.8 Domestic Hot Water Wiring
- 38 8.9 Additional Boiler Limits
- 38 8.10 External Modulation Control
- 38 8.11 System Sensor Wiring
- 38 8.12 Cascade Wiring
- 62 10.4 Check For Gas Leaks
- 62 10.5 Check Thermostat Circuit
- 62 10.6 Inspection of Condensate Drain Assembly
- 63 11.1 Final Checks Before Start-Up
- 63 11.2 PRESTIGE Solo Start-Up
- 63 11.3 Check the PRESTIGE Solo and System
- 68 12.1 Mounting the Outdoor Sensor
- 68 12.2 Wiring the Sensor
- 69 13.1 Wiring the Modulating Controller
- 69 13.2 ACVMax Adjustment
- 69 13.3 Programming of External Modulating Control
- 73 16.1 Service Technician
- 73 16.2 Owner Maintenance
- 74 17.1 Maintenance Procedures
- 74 17.2 Reported Problems
- 74 17.3 Check Surrounding Area
- 74 17.4 Inspect Burner Area
- 74 17.5 Check System Piping
- 75 17.6 Clean Condensate Drain Assembly
- 75 17.7 Check Ventilation Air Openings
- 75 17.8 Inspect Vent and Combustion Air Piping
- 75 17.9 Check Boiler System
- 76 17.10 Check Expansion Tank
- 76 17.11 Check Boiler Relief Valve
- 76 17.12 Inspection of Ignitor
- 76 17.13 Check Ignition Wiring and Ground Wiring
- 77 17.14 Check Control Wiring
- 77 17.15 Check Control Settings
- 77 17.16 Perform Start-up and Checkout Procedures
- 77 17.17 Check Burner Flame
- 78 17.18 Check Flame Signal
- 78 17.19 Check Combustion Levels
- 78 17.20 Check Flue Gas Temperature
- 78 17.21 Clean Heat Exchanger
- 79 17.22 Review With Owner
- 79 17.23 Handling Previously Fired Combustion Chamber Insulation
- 79 17.24 Torque Specifications Table
- 80 PRESTIGE Excellence Front View
- 81 PRESTIGE Excellence Right Side View
- 82 PRESTIGE Excellence Top View