Distributed Clock. Beckhoff EL3443, EL3483, EL3443-0011, EL3453, EL3483-0060, EL3423, EL3443-0010, EL3443-0013, EL34 Series

Add to My manuals
295 Pages

advertisement

Distributed Clock. Beckhoff EL3443, EL3483, EL3443-0011, EL3453, EL3483-0060, EL3423, EL3443-0010, EL3443-0013, EL34 Series | Manualzz

Basics communication

4.6

Distributed Clock

The distributed clock represents a local clock in the EtherCAT slave controller (ESC) with the following characteristics:

• Unit 1 ns

• Zero point 1.1.2000 00:00

• Size 64 bit (sufficient for the next 584 years; however, some EtherCAT slaves only offer 32-bit support, i.e. the variable overflows after approx. 4.2 seconds)

• The EtherCAT master automatically synchronizes the local clock with the master clock in the EtherCAT bus with a precision of < 100 ns.

For detailed information please refer to the EtherCAT system description .

42 Version: 1.5

EL34xx

advertisement

Key Features

  • Measures voltage, current, power, energy, and power factor
  • Supports 3-phase systems with up to 500 V and 10 A per phase
  • High accuracy class 0.5
  • Fast sampling rate of 1024 samples per cycle
  • EtherCAT interface for real-time data transfer
  • Compact design for easy installation
  • Wide range of mounting options
  • LED indicators for status and diagnostics
  • Can be used with current transformers for extended current measurement range
  • Supports TwinCAT software for configuration, monitoring, and data acquisition

Related manuals

Frequently Answers and Questions

What is the maximum voltage and current that the EL3443-0013 can measure?
The EL3443-0013 can measure up to 500 V and 10 A per phase.
What is the accuracy class of the EL3443-0013?
The EL3443-0013 has an accuracy class of 0.5.
What is the sampling rate of the EL3443-0013?
The EL3443-0013 has a sampling rate of 1024 samples per cycle.
Can the EL3443-0013 be used with current transformers?
Yes, the EL3443-0013 can be used with current transformers for extended current measurement range.
What software is used to configure and monitor the EL3443-0013?
The EL3443-0013 is configured and monitored using TwinCAT software.