Application examples

7.3

Power measurement in a single-phase mains network with ohmic consumers

• The voltage is measured via connections L1, L2, L3 and N.

• The current is measured via three

current transformers [ }  29]

and the connections I

L1

, I

L2

, I

L3

and I

N

(star point of the current transformers).

WARNING

WARNING: Risk of electric shock!

Bring the Bus Terminal system into a safe, voltage-free state before starting mounting, disassembly or wiring of the Bus Terminals!

NOTE

Attention! Risk of device damage!

Avoid confusing the current and voltage circuit during connection, since the direct connection of mains voltage to the terminal points for the current transformers (typical input resistance 220 mΩ) would destroy the power measurement terminal!

Fig. 165: Power measurement at ohmic consumers

264 Version: 1.5

EL34xx

advertisement

Key Features

  • Measures voltage, current, power, energy, and power factor
  • Supports 3-phase systems with up to 500 V and 10 A per phase
  • High accuracy class 0.5
  • Fast sampling rate of 1024 samples per cycle
  • EtherCAT interface for real-time data transfer
  • Compact design for easy installation
  • Wide range of mounting options
  • LED indicators for status and diagnostics
  • Can be used with current transformers for extended current measurement range
  • Supports TwinCAT software for configuration, monitoring, and data acquisition

Related manuals

Frequently Answers and Questions

What is the maximum voltage and current that the EL3443-0013 can measure?
The EL3443-0013 can measure up to 500 V and 10 A per phase.
What is the accuracy class of the EL3443-0013?
The EL3443-0013 has an accuracy class of 0.5.
What is the sampling rate of the EL3443-0013?
The EL3443-0013 has a sampling rate of 1024 samples per cycle.
Can the EL3443-0013 be used with current transformers?
Yes, the EL3443-0013 can be used with current transformers for extended current measurement range.
What software is used to configure and monitor the EL3443-0013?
The EL3443-0013 is configured and monitored using TwinCAT software.