- Industrial & lab equipment
- Measuring, testing & control
- Satec
- PM172EH Series
- Installation and Operation Manual
advertisement
2.2 Electrical Installation
)
Before installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
Connections to the PM172EH are made via terminals located on the rear panel of the instrument as shown in Figure 2-6.
26 27 28 29 18 19 20
V
V
1
2
18 19 20
1 2
STATUS INPUT
2
5
8
21 22 23 24 25
+ +
2
-
1
ANALOG OUTPUT
26
1
27 28
2
29
RELAYS
R
POWER SUPPLY
90-264VAC
50/60Hz
STANDARD
85-290VDC
10W
NOM. VOLT. MEASUREMENT
690V
O
120V (OPT. U)
(12) 10-16VDC
P
(24) 18-36VDC
LOW DC
INPUT
T
1A CT.
5A CT.
(48) 36-72VDC I
ANALOG OUTPUT
S/N
O
COMM. PROTOCOL
N
ASCII & MODBUS
SW. VER
S ASCII & DNP3.0
-
+
-
-
+ 1
I
1
3
4
I
2
6
+ 7
I
3
9
V
11
V
3
N
ATTENTION
Static-Sensitive
Devices
Handle Only at
Static-Safe
Workstations
COM.1
RS-232
5
9
RS-422/485
6
1
N/10
POWER SUPPLY
COM.2
RS-422/RS-485
-TX -RX +TX +RX
L/+ 12
13 14 15 16 17
13 14 15 16 17
00-06007
Figure 2-6 Terminals - Rear View
2.2.1 Power Source Connection
The power source can be dedicated-fused, or from a monitored voltage if it is within the instrument’s power supply range.
AC power supply: line to terminal 12; neutral to terminal 10.
DC power supply: positive to terminal 12; negative to terminal 10.
Chapter 2 Installation 11
2.2.2 Current Inputs
To ensure accurate readings, the input current should not exceed 1.2A
RMS and 1.76A amplitude for the 1A CT secondary, or 6A RMS and 8.8A amplitude for the 5A CT secondary.
Copper wiring 2.5 – 3.5 mm 2 (12 AWG) should be used.
2.2.3 Ground
Connect the chassis ground of the PM172EH to the switchgear earth ground using dedicated wire greater than 2 mm
2
/14 AWG.
2.2.4 Voltage Inputs
Input of 690V (Standard): To ensure accurate readings, the measured voltage between terminals 2-5, 5-8 and 8-2 should not exceed 790V AC
RMS, and the measured voltage between terminals 2-11, 5-11 and 8-11 should not exceed 460V AC RMS and 695V amplitude. Use any of the seven wiring configurations shown in Figures 2-7 through 2-13.
Input of 120V (Option U): To ensure accurate readings, the measured voltage between terminals 2-5, 5-8, 8-2, 2-11, 5-11 and 8-11 should not exceed 144V AC RMS and 225V amplitude. 120V input usually implies use of a potential transformer (PT). The PT requires use of any of the four wiring configurations shown in Figures 2-9 through 2-12.
Wiring Configuration
(See parameter setup instructions in Section 4.2)
3-wire direct connection using 2 CTs (2-element)
4-wire WYE direct connection using 3 CTs (3-element)
4-wire WYE connection using 3 PTs, 3 CTs (3-element)
3-wire open delta connection using 2 PTs, 2 CTs (2element)
Setup Code Figure
3dir2 2-7
4Ln3 or 4LL3 2-8
4Ln3 or 4LL3 2-9
3OP2 2-10
4-wire WYE connection using 2 PTs, 3 CTs (2½ -element) 3Ln3 or 3LL3 2-11
3-wire open delta connection using 2 PTs, 3 CTs (2½ element)
3OP3 2-12
4-wire delta direct connection using 3 CTs (3-element) 4Ln3 or 4LL3 2-13
12 Chapter 2 Installation
Figure 2-7 Three Wire Direct Connection Using 2 CTs (2-element)
Wiring Mode = 3dir2
LINE 1 (A)
LINE 2
LINE 3
(B)
(C)
N
K
+ -
L
K
+ -
L
K
+ -
L LOAD
Shorting
Switches
Voltages
V
1
V
2
V
3
Currents
1
+
3
-
4
6
+
-
7
+
9
-
10
V
N
12
Figure 2-8 Four Wire WYE Direct Connection Using 3 CTs (3element) Wiring Mode = 4LL3 or 4Ln3 c99-05030
Chapter 2 Installation 13
Figure 2-9 Four Wire WYE Connection Using 3 PTs, 3 CTs (3element) Wiring Mode = 4LL3 or 4Ln3
Figure 2-10 Three Wire Open Delta Connection Using 2 PTs, 2
CTs (2-element) Wiring Mode = 3OP2
14 Chapter 2 Installation
Figure 2-11 Four Wire Wye Connection Using 2 PTs, 3 CTs
(2½-element) Wiring Mode = 3LL3 or 3Ln3
This configuration will provide accurate power measurements only if the voltages are balanced.
Figure 2-12 Three Wire Open Delta Connection Using 2 PTs, 3 CTs
(2½-element) Wiring Mode = 3OP3
Chapter 2 Installation 15
LINE 1(A)
LINE 2(B)
LINE 3(C)
*
L
1
*
L
1
(A)
240VAC
*
L
2
240VAC
240VAC
*
L
3
120VAC
208VAC
N
*
*
L
3
120VAC N
(C)
K
+ -
L
K
+
-
L
K
+ -
L
LOAD
N
Shorting
Switches
Grounded delta connection
*
L
1
(A)
120V
*
L
2
(B)
120V
*
L
3
(C)
Voltages
2
5
8
V
1
V
2
V
3
11 V
N
Currents
1
+
-
3
4
6
7
-
+
9
10
12
N
VOLTAGES DISPLAYED:
1. Line to neutral voltages: 120V; 208V; 120V.
2. Line to line voltages: 240V; 240V; 240V.
Figure 2-13 Four Wire Delta Direct Connection Using 3 CTs
(3-element) Wiring Mode = 4LL3 or 4Ln3
2.2.5 Relays
c99-05031
Two relays are provided for energy pulsing, alarms or remote control.
Figure 2-14 Relays Connection
2.2.6 Status Inputs
Two optically isolated status inputs are provided for status monitoring, counting pulses and for external power demand period and time synchronization.
Figure 2-15 Status Inputs Connection
16 Chapter 2 Installation
2.2.7 Analog Output
The PM172EH provides two optically isolated analog outputs with an internal power supply and current output options of 0-20 mA and 4-20 mA
(current loop load of up to 500 Ohm), 0-1 mA and ± 1 mA (current loop load of 10 kOhm).
Figure 2-16 Analog Output Connection
Chapter 2 Installation 17
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 7 Chapter 1 Introduction
- 7 About this Manual
- 7 About the PM172EH
- 14 Chapter 2 Installation
- 14 Mechanical Installation
- 17 Electrical Installation
- 24 Chapter 3 Using the Menus
- 26 Chapter 4 Setup Menus
- 26 Basic Setup Menu
- 28 Communications Port Setup Menus
- 30 Digital Inputs Setup Menu
- 31 Pulse Counters Setup Menu
- 32 Analog Output Setup Menu
- 35 Analog Expander Setup Menu
- 36 Pulsing Output Setup Menu
- 37 Alarm/Event Setpoints Setup Menu
- 44 Timers Setup Menu
- 45 RTC Setup Menu
- 47 Display Setup Menu
- 48 User Selectable Options Menu
- 51 Relay Operation Control Menu
- 52 Access Control Menu
- 53 Reset Menu
- 55 Chapter 5 Data Display
- 55 Navigating in the Display Mode
- 58 Data Display Formats
- 64 Self-Test Diagnostics Display
- 65 Chapter 6 Viewing Status Information
- 65 The Status Information Menu
- 66 Status Display Formats
- 68 Chapter 7 Communications
- 71 Appendix A Technical Specifications
- 77 Appendix B Using Setpoints
- 81 Appendix C Configuring TOU
- 83 Appendix D Event and Data Logging
- 87 Appendix E Power Quality Setup