Operation on Two Phases. Puls PIANO Series

Add to My manuals
20 Pages

advertisement

Operation on Two Phases. Puls PIANO Series | Manualzz

PIANO-Series

Wiring examples:

Fig. 23-1 1+1 Redundant wiring with 1 YR40.242

20A

Load

Failure

Monitor

+ -

Output

+ + - -

Output

24V,20A

DC-

OK

Power

Supply o o YR40.242

Redundancy

Module

+ + - -

Output

24V,20A

DC-

OK

Power

Supply o o

Input

L N PE

Input

1

+ -

Input

2

+ -

Input

L N PE

I I

L

N

PE

Optionally a YR40.241 can be used, which has the input terminals on top and output on bottom

L

N

PE

I

24V, 20A, 480W,

PIC480.241D

S

INGLE

P

HASE

Fig. 23-2 1+1 Redundant wiring with 2 PIRD20.241

+ + - -

Output

24V,20A

DC-

OK

Power

Supply o o

Input

L N PE

+ +

Input

1

Input

2

PIRD20.241

Redundancy

Module

Output

+ +

+ + - -

Output

24V,20A

DC-

OK

Power

Supply o o

Input

L N PE

I

+ +

Input

1

Input

2

PIRD20.241

Redundancy

Module

Output

+ +

I

NPUT

Failure

Monitor

20A

Load

23.5.

O

PERATION ON

T

WO

P

HASES

The power supply can also be used on two-phases of a three-phase-system.

Such a phase-to-phase connection is allowed as long as the supplying voltage is below 240V +10% .

Ensure that the wire, which is connected to the N-terminal, is appropriately fused.

The maximum allowed voltage between a Phase and the PE must be below 300Vac.

L3

L1

L2

Power Supply

AC

L

N

PE

DC

23.6.

U

SE IN A

T

IGHTLY

S

EALED

E

NCLOSURE

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.

The power supply is placed in the middle of the box, no other heat producing items are inside the box

The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of

1cm.

The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.

Enclosure size

Case A

180x180x165mm

Rittal Typ IP66 Box

PK 9519 100, plastic

Input voltage

Load

230Vac

24V, 16A; (=80%)

Temperature inside the box 48.3°C

Temperature outside the box 21.0°C

Temperature rise 27.3K

Case B

180x180x165mm

Rittal Typ IP66 Box

PK 9519 100, plastic

230Vac

24V, 20A; (=100%)

55.3°C

21.0°C

34.3K

Dez. 2019 / Rev. 1.0 DS-PIC480.241D-EN (MR1-RP22G) All parameters are typical values specified 230Vac, 50Hz input voltage, 24V, 20A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany

20/20