Programming Conventions. Honeywell IntelliPath Series, IntelliPath LTE-IC, IntelliPath LTE-IV
Iklan
Iklan
Section 3: Programming the Communicator
Programming Conventions
Programming is accomplished by answering a series of prompts (questions). Most prompts require only a [Y]es or [N]o response, while others require a numerical response (ID numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an invalid entry.
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the entered value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing any values. Press the [ESC] key to go to the end of the list of questions.
ECP Mode Programming
The communicator supports ECP messaging to communicate with the control panel. Likewise the control panel sends Contact ID format alarms to the communicator via the ECP bus. Not all control panels support the communicator interface on ECP, so be sure to check the Installation and Setup Guide of the control panel to see if it supports this feature.
ULC
ECP Mode has been approved for ULC installations.
Refer to
Table 3-2
for ECP Mode programming and follow the prompts.
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears:
Access to Prog
Mode Denied
1
2
3
4
5
6
NOTE: The default programming values for ECP mode are listed in each prompt below.
Table 3-2: Programming the Communicator for ECP mode only.
PROMPTS
Strt Prog Mode?
(Y/N)_
Enter Password:
Program Device?
(Y/N)_
Create Password?
(Y/N)_
Change Password?
(Y/N)_
Enter Password
OPTIONS
[Y], [N]
[0-9, A-F, N, S, T,
X, Y]
[Y], [N ]
[Y], [N]
[Y], [N]
[0-9, A-F, N, S,
T, X, Y]
Enters programming mode.
DESCRIPTION
If a password has been previously assigned, this prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
To begin programming the communicator, press [Y] and go to Prompt
10: "Device Mode."
To create a password if none has been assigned, press [N] and go to
Prompt 5: "Create Password."
To change an existing password, press [N] and go to Prompt 6:
"Change Password."
Passwords can be used to protect account and programming information.
If no password has been assigned, this prompt appears after pressing
[N] at the "Program Device?" prompt.
If a password is desired, press [Y] and go to "Enter Password."
If a password has already been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering a new one, answer [Y] to the "Change Password?" prompt, then press the [Enter] key when prompted for the new password and its confirmation.
This prompt is displayed if [Y] was pressed in Prompt 4 or 5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
19
LTE-I Installation and Setup Guide
7
PROMPTS
Verify Password
OPTIONS
[0-9, A-F, N, S,
T, X, Y]
DESCRIPTION
Re-enter the password as confirmation.
If the password doesn't match the first entry, the following is displayed followed by the "Exit Prog. Mode?" prompt:
Verify Not OK
PSWD not created
Otherwise, the "Exit Prog. Mode?" prompt is displayed directly.
8 Exit Prog. Mode?
(Y/N)_
[Y], [N]
[ESC]
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the
Exiting Programming Mode paragraph in this section.
9 Comm Path Choice
(IP&Cell)_
IP&Cell
IP
Cell
Press the [space] key to scroll through the communication path choices. Press [ENTER] to select.
For maximum reliability, select IP&Cell, and ensure the Internet is connected using the Ethernet cable.
NOTE : After going from a “Cell” only com path choice to an “IP” only choice, Prompt 45: “DHCP” will default to No.
10 Device Mode
(ECP)_
ECP
Zone Triggers
Press [ENTER] to select ECP mode.
Press the [space] key to scroll through choices.
IMPORTANT , if Zone Trig device mode is desired, use
Table 3-4
for programming.
Important Information Regarding Multi-Mode Options
NOTE: In order for the Multi Mode, Remote Access, and Keypad Address programming fields to appear an account must be created in the AlarmNet 360 website and “Remote Access” must be enabled for the comm device.
Users can receive email notification of system events by using the Multi-Mode feature. In ECP mode, this is accomplished through emulation of a 4204 relay module, or two 4204 relay modules.
When “4204-sourced” is selected, the user can be notified of up to four events, plus two additional events if using the optional communication device zones of 6 and 7.
When “2-4204-sourced” is selected, the user can be notified of up to eight events. The Multi-Mode address must match the address of a relay module enabled in the control panel (although you don’t actually connect a module). If using “2-
4204-sourced,” the address of the second module is automatically assigned the next device address after the first 4204.
When “Enhanced Reports” is selected, a device address of 25 should be selected.
Make sure the addresses are also enabled in the control panel. Program outputs to trigger on system events the user would like to be notified of through Output Device (Relay) programming in the control panel.
These events are configured at the AlarmNet Total Connect website at: https://services.alarmnet.com/TotalConnect
Multi-Mode (email notification) is intended as a convenience for the user, and does not replace
Central Station reporting of critical events (alarms, troubles, etc.).
UL / ULC
Multi-Mode has not been evaluated by UL or ULC.
11 Multi Mode
(Disabled)_
Disabled
4204 Sourced
2-4204 Sourced
Enhanced
Reports
Enable if you want system events sent by email to the user. Select
"4204 Sourced" to send up to four events (plus two additional reports triggered by optional hardwire zones 6 and 7), or "2-4204 Sourced" to send eight events.
Disable for normal alarm processing and go to Prompt 13: "Primary City
ID".
Select “Enhanced Reports” to enable reporting to TC2 web services.
Note, to use “Enhanced Reports” ensure the control panel is Total
Connect 2.0 Ready.
12 Multi Mode Addr
(12)_
[01-30] This address must be programmed if using the Multi- Mode (email notification) feature. The device address must be unique from the normal communicator (or LRR) device address, and the Keypad
Address used for Remote Access or Direct Wire downloading. The address used must also be enabled as a 4204 relay module in Vista and First Alert control panels.
See Important Information above.
20
Section 3: Programming the Communicator
PROMPTS OPTIONS DESCRIPTION
13
Important Information Regarding Primary and Secondary Accounts (Questions 12-18)
Account information is provided by the central station administrator. If the control panel supports secondary account reporting, you will need secondary account information. The City ID, CS ID or Subscriber ID of the secondary account must differ from that of the primary account.
Primary City ID
(??)_
[01-99] Enter the 2-digit primary city ID, 01-99 (decimal).
14
15
16
17
Primary CS ID
(??)
Primary Sub ID
(????)
En. 2nd CS Y/N
(N)_
2nd City ID
(??)_
[01-FE]
[0001-9999]
[Y], [N]
[01-99]
Enter the 2-digit primary central station ID number, 01-FE (HEX).
Enter the 4-digit subscriber account number, 0001-9999 (decimal).
Applicable only if the control panel supports Central Station #1 and #2
Category Enable reporting for the communicator device (e.g., VISTA-
128BP, FA1660C).
Used if reporting to a second central station is desired.
If [N], go to Prompt 20: "Device Address."
Enter the 2-digit secondary city ID, 01-99 (decimal).
18
19
2nd CS ID
(??)_
2nd Sub ID
(????)_
[01-FE]
[0001-9999]
Enter the 2-digit second central station's ID number, 01-FE (HEX).
Enter the 4-digit subscriber account number for the second central station, 0001-9999.
20
21
Device Address
(03)_
Remote Access Y/N
(N)_
[01-30]
[Y], [N]
In ECP mode, the LTE-I communicates with the control panel using the
ECP bus. Enter the appropriate ECP device address. For VISTA-10 and VISTA-20 series control panels, use address 03. For other control panels, see their Installation and Setup Guide.
NOTES:
1. When programming the control panel, enable the communicator (or
LRR) output.
2. The device address must be unique from the "Keypad Address" entered in Prompt 23, and the “Multi-Mode Address” entered in
Prompt 12.
UL / ULC
Remote access has not been evaluated by UL or ULC.
Press [Y] to allow the end user to access their system via a website.
Availability of this service is controlled by the dealer via the web-based programming tool on the AlarmNet 360 website.
22 Direct Wire Y/N
(N)_
[Y], [N]
Applies only to VISTA-128BP/250BP and FBP Series control panels, and FA1660C and 1700C Series control panels.
Enables Direct Wire Downloading over IP.
If [N], and if Prompt 21: "Remote Access" is disabled, skip to Prompt
24: "Supervision."
23 Keypad Address
(28)_
[01-30]
Must be programmed if using either the Remote Access feature or
Direct Wire downloading.
NOTES:
1. This address must also be programmed as an alpha keypad in the control panel or an AUI (advanced user interface) type device, if a full enhanced graphic interface to the system is desired and the control panel supports it. DO NOT connect an actual keypad (or any other device) assigned to this address.
2. This address must be unique from the "Device Address" entered in
Prompt 20.
21
LTE-I Installation and Setup Guide
24
25
PROMPTS
Supervision
(24 Hours)_
Cell Rollover Y/N
(Y)_
OPTIONS
IP & Cell or Cell
Only:
None
30 Day
24 Hours
IP only:
None
30 Day
24 Hours
6 minutes
3 minutes
90 seconds
Additional options for CN only.
1 Hr
3 Min
90 seconds
75 seconds
[Y] , [N]
26 Cell 24Hr Tst Y/N
(N)_
27 Old Alarm Time
10 Minutes_
28 IP Flt Time
(60 mins)_
29 Cell Flt Time
(60 mins)_
[Y], [N]
10 Minutes
15 Minutes
30 Minutes
1 Hour
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
[00-99]
[00-99]
DESCRIPTION
The AlarmNet network must hear at least one supervisory message from the communicator during this supervision period; otherwise,
AlarmNet notifies the central station that a communication failure has occurred. (If the supervision period is changed after registration, you must re-register the communicator.)
Press the [space] key to scroll through choices.
UL: For IP + Cell set to 24 Hrs. For IP only set to 3 Min. For Cell only set to 24 Hrs.
A loss of communications is treated as an Alarm condition.
ULC : Must be set to "CN UL Line Lvl 3" for ULC-S304 Active Level 3 or
ULC-S559 Active Fire installations. All other commercial applications must be set to "24 Hrs".
This prompt appears only if comm. path is set to IP & Cell.
If enabled, all messages (including AlarmNet network supervisory messages) are sent over the cell network in the event of an Internet failure.
If disabled, all messages (except AlarmNet network supervisory messages) are sent automatically over the cell network in the event of an Internet failure.
UL/ULC : Must be set to "Y" if 24 hours is selected in Prompt: 24:
Supervision. Must be set to "N" for ULC-S304 Active Level 3 or ULC-
S559 Active Fire installations where CN UL Line Lvl 3 is selected.
IMPORTANT WARNING: If set to "Y", AND Prompt 24: Supervision is set to occur less than every 24 hours, this can result in data overage charges on your monthly bill.
This prompt appears only if comm. path is set to IP & Cell.
If enabled a message is sent every 24 hrs over Cell to verify proper operation. If it fails, a Periodic Comm Test Failure message will be sent over Ethernet.
UL/ULC: Must be set to "Y".
Sets how long an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
UL/ULC: Must be 10 minutes.
This prompt appears only if comm. path includes IP.
In the event there is a loss of contact with the network over the Ethernet connection, enter the time delay (in minutes) before the communicator notifies the central station. IP failure will always be sent to the central station as Primary Communication Path Failure.
UL/ULC: Must be one (01) minute.
This prompt appears only if comm. path includes Cell.
In the event the communicator detects a communication path failure, enter the time delay (in minutes) before the communicator notifies the central station. A cell failure will always be sent to the central station as
Secondary Communication Path Failure.
UL/ULC: Must be one (01) minute.
22
Section 3: Programming the Communicator
30
31
32
PROMPTS
Notify Panel Of_
(Neither Fault)
Flt Rel ON Y/N
(N)_
Pwr Loss Rpt Y/N
(Y)_
OPTIONS
[Neither fault]
[Both IP and Cell
Faults]
[Y], [N]
[Y], [N]
DESCRIPTION
This prompt appears only if comm. path is set to IP & Cell.
If "Both IP and Cell Fault" is selected, the device will only notify the control panel if both communication paths fail, but will always send notification of either failure to the central station.
(If the "Cell Fault Time" and "IP Fault Time" options are set to zero, faults will not be reported.)
Press the [space] key to scroll through choices.
UL/ULC: Must be set to "Both IP and Cell Faults".
If enabled, the fault open collector output is normally energized to ground, and de-energizes (open circuit) in the event of a communicator fault. For conditions that trip the fault relay refer to
Supervision
Features
in Section 1.
Set to [Y] if fail-safe mode is desired.
See
Wiring the Fault Relay
in Section 2.
UL/ULC: Must be set to "Y."
Sends a primary power loss report to the central station within 1-3 hours after its detection. A restore report is sent within 1-3 hours after power is restored.
UL Standard Installations (using transformer and battery) : Must be set to "Y".
ULC Commercial Fire & Burglary Installations (powered from the control panel) : Must be set to "N."
33
34
Low Bat Rpt Y/N
(Y)_
Tamper Rpt Y/N
(Y)_
[Y], [N]
[Y], [N]
Sends a low-battery report when a low battery condition exists. A low battery restore is automatically sent when the low battery condition clears.
UL Standard Installations (using transformer and battery) : Must be set to "Y".
ULC Commercial Fire & Burglary Installations (powered from the control pan`el) : Must be set to "N."
Sends a tamper report when the communicator detects a tamper condition. A tamper restore is automatically sent when the tamper condition clears.
UL/ULC: Must be set to "Y."
Important Information Regarding Zone Input Options
ECP mode supports two optional hardwire zone input triggers by making connections to the communicator’s zone 6 and/or zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
(V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
(V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
(EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by open collector, voltage trigger, NO, NC.
UL/ULC: Set V+ to inverted, and V– as non-inverted.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting (NOT for UL installations), which allows time for the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
35
36
Enable Zn6 Y/N
(N)_
Zn6 Trigger Type
(V+)_
[Y], [N]
(V+)
(V–)
(EOLR)
Enables alarm reporting for zone 6.
If [N], skip to Prompt 40: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL/ULC: V+ must be set as inverted and V– as non-inverted.
23
LTE-I Installation and Setup Guide
37
38
39
PROMPTS
Invert Zn6 Y/N
(N)_
Restore Zn6 Y/N
(Y)_
Delay Zn6 (secs)
(00)_
OPTIONS
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
DESCRIPTION
Inverts the alarm and normal states of the zone 6 trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
Defines the reporting delay in seconds for zone 6.
UL/ULC: Must be set to 00.
40 Enable Zn7 Y/N
(N)_
[Y], [N] Enables alarm reporting for zone 7.
If [N], skip to Prompt 45: "Use DHCP."
41
42
43
44
50 Enable Pwr Save
Zn7 Trigger Type
(V+)_
Invert Zn7 Y/N
(N)_
Restore Zn7 Y/N
(Y)_
Delay Zn7 (secs)
(00)_
(N)_
(V+)
(V–)
(EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
Selects the triggering method for this zone input.
Press the [space] key to scroll choices.
UL/ULC: V+ must be set as inverted and V– as non-inverted.
Inverts the alarm and normal states of the zone 7 trigger; otherwise, uses normal input signal.
Enables restore reporting for zone 7.
Prompts 45-51 appear only if communication path includes IP.
45 Use DHCP Y/N
(Y)_
[Y], [N] Dynamically allocates the IP addresses (recommended); then skip to
Prompt 50: "Enable Pwr Save".
If [N], uses fixed IP addresses.
46 NIC IP Address:
255.255.255.255_
12 digit: xxx.xxx.xxx.xxx
Enter the 4-part address for this device. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
47
48
Subnet Mask:
255.255.255.255_
Gateway IP Addr:
255.255.255.255_
12 digit: xxx.xxx.xxx.xxx
12 digit: xxx.xxx.xxx.xxx
Enter the 32-bit address mask used to indicate the portion (bits) of the
IP address that is being used for the subnet address. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
Enter the 4-part address assigned to the Gateway. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
49 DNS Serv IP Addr:
255.255.255.255_
12 digit: xxx.xxx.xxx.xxx
Enter the 4-part IP address assigned to the DNS (Domain Name
System) server. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
[Y], [N]
Defines the reporting delay in seconds for zone 7.
UL/ULC: Must be set to 00.
To meet the 24 hour UL battery backup requirement, choose "Y" to enable this feature. If this causes connectivity problems with certain routers or switches, then choose "N" and wire the communicator so it is plugged into a UL listed UPS.
UL: Must be set to Y.
24