Possible Errors Running Network Diagnostics. Honeywell IntelliPath Series, IntelliPath LTE-IC, IntelliPath LTE-IV
Quảng cáo
Quảng cáo
LTE-I Installation and Setup Guide
Possible Errors Running Network Diagnostics
Errors may occur either while tracing the connection to a given Redir or while testing the service at a given Redir. The following list highlights the most common errors. Please contact the
AlarmNet Technical Assistance Center (TAC) for help regarding any errors NOT listed below:
Possible Errors
Testing Redir x
FAIL before Gtwy
Testing Redir x
FAIL at Gtwy
Testing Redir x
FAIL at Pvt IP
Testing Redir x
FAIL on IP Addr
Redir x
ERR:Proxy 18
While tracing the connection to Redir x, the trace fails before ever reaching the local gateway (router).
While tracing the connection to Redir x, the trace fails after reaching the local gateway (router).
While tracing the connection to Redir x, the trace fails after reaching the private IP.
While tracing the connection to Redir x, the trace fails after reaching the public IP.
After a successful trace to Redir x, the test of the network service timed out without a response.
46
Appendices
Appendices
Appendix A: Summary of LED Operation
ON - Module registered, no second site available.
OFF - Module not registered with network carrier.
SLOW BLINK - Module registered, second site available, and low signal strength.
FAST BLINK - Module registered, second site available, excellent signal strength.
ON - Cell service available.
OFF - No Cell service available.
FAST BLINK - Cell in use.
ON - Connected to Internet.
OFF - Not connected to Internet.
A-1
LTE-I-005-V0
LTE-I Installation and Setup Guide
A-2
Appendices
Appendix B: Central Station Messages
ECP Mode
Alarm Condition
Alarm Code Restore Code
Power On / Reset E339 C08xx*
Alarm Code
Zone Mode
Restore Code
Tamper
(Compromise Indication)
Power Loss
Low Battery
Battery Charger Failure
ECP Supervision
(Compromise Indication)
Primary Comm Path Supervision
Secondary Comm Path Supervision
Application Code Update
Application Code Update Failure
Module Firmware Update
Module Firmware Update Failure
Telco (Compromise Indication)
Open/Close
E341 C08xx*
E337 C08xx*
E338 C08xx*
E314 C08xx*
E355 C0000
E350 C0951
E350 C0952
E903 C08xx
E904 C08xx
E365 C08xx
E366 C08xx
R341 C08xx*
R337 C08xx*
R338 C08xx*
R314 C08xx*
R355 C0000
R350 C0951
R350 C0952
R903 C08xx
(success)
R365 C08xx
(success)
5551 5555 6
5555 5551 7
1555 5555 6
5155 5555 6
5155 5555 1
5555 5515 5
5555 5551 5
5555 5551 1
5555 5155 6
2 sent in selected zone
5555 5553 7
3555 5555 6
5355 5555 6
5355 5555 1
5555 5535 5
5555 5553 5
5555 5553 1
5555 5355 6
4 sent in selected zone
Periodic Cell Comm Test Failure
UL
E358 C0803
Test 5555 5555 9 5555 5555 9
Specific to RESIDENTIAL / COMMERCIAL Control Panels (Such as the VISTA-10P, 15P, and 20P series.)
The information provided in this section for the VISTA-10P, 15P, and 20P series control panels has not been evaluated with this communicator.
Communicator Trouble (low battery, ECP bus, network)
(Possible Compromise Indication)
E353 C08xx* ◊ R353 C08xx* ‡
Radio Fault E353 0 1xx* ‡ R353 0 1xx* ‡
Specific to COMMERCIAL Control Panels (Such as the VISTA-128/250 series.)
Communicator Trouble (low battery, ECP bus, network)
(Possible Compromise Indication)
E333 C08xx* ‡ R333 C08xx* ‡
Radio Loss of Signal
(Possible Compromise Indication)
Bus)
AlarmNet Messages
Communication failure.
(Possible Compromise Indication)
Authorized Radio Substitution
Radio Fault (low battery, tamper, ECP
E357 0 8xx* †
E333 0 8xx* ‡
E359 0 C950
00D0 010C 0
R357 0 8xx* ‡ or
R380 0 8xx* ‡
R333 0 8xx* ‡
R 359 0 C950
Unauthorized Radio Substitution Attempt 00D0 010E 0
Service Termination 00D0 020E 0
* xx = Communicator Device Address
† = Message is sent by dialer only.
‡ = Message is sent by dialer and radio.
◊ = Message is sent by dialer only, or dialer and radio, depending on failure.
B-1
LTE-I Installation and Setup Guide
B-2
Appendix C: Glossary
4G LTE Refers to the fourth generation of cellular wireless standards. It is a successor to
3G and 2G families of standards. 4G provides up to 10 times the data transfer speeds of 3G.
AES
DACT
DHCP
DNS
DSL
ECP
Gateway IP
Address
IMEI
IP
IP Address
Advanced Encryption Standard
Digital Automated Communications Terminal
Dynamic Host Configuration Protocol, which provides a mechanism for allocating
IP addresses dynamically so that addresses can be reused when hosts no longer need them.
Domain Name System, which is a distributed hierarchical naming system used to resolve domain names (e.g., www.yahoo.com) into numerical IP addresses (e.g.,
204.17.25.1.).
Digital Subscriber Line.
Enhanced Console Protocol, which is a proprietary bus used in Honeywell control panels to communicate with keypads and peripheral devices. It uses four wires; power, ground, data in, data out.
A gateway (sometimes called a router) is a computer and/or software used to connect two or more networks (including incompatible networks) and translates information from one network to the other. The Gateway IP address is the IP address for the gateway.
International Mobile Equipment Identity number.
Internet Protocol.
A unique number consisting of four parts separated by periods (for example:
204.17.29.11). An IP Address can be fixed or "static", or "dynamic," where the IP
Address is assigned via DHCP at every startup.
ISDN
ISP
LAN
LRR
Integrated Services Digital Network.
Internet Service Provider.
Local Area Network.
Long Range Radio, an older term now referred to as communicator. A broader term communications module or communications device may also be used.
MAC ID
TCP/IP
Media Access Code, this is a unique address assigned to every network communications device. For the communicator it is located on the box and inside the communicator.
Subnet Mask A Subnet is a portion of a network that shares a network address with other portions of the network, and is distinguished by a subnet number. The Subnet
Mask is a 32-bit address mask used in IP to indicate the bits of an IP address that are being used for the subnet address.
Transmission Control Protocol / Internet protocol.
C-1
NOTES
NOTES
NOTES
FEDERAL COMMUNICATIONS COMMISSION & ISED STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information.
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in
Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, have a quality outdoor antenna installed.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control panel.
• Move the antenna leads away from any wire runs to the receiver/control panel.
• Plug the receiver/control panel into a different outlet so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
ISED CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / ISED STATEMENT
This device complies with Part 15 of the FCC Rules, and ISED’s license-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC et exempt de licence RSS d’ISED. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les interférences causant une réception indésirable.
Responsible Party / Issuer of Supplier’s
Declaration of Conformity: Honeywell
International, 2 Corporate Center Drive.,
Melville, NY 11747, Ph: 516-577-2000
Partie responsable / Émetteur de la déclaration de conformité du fournisseur : Honeywell
International, 2 Corporate Center Drive.,
Melville, NY 11747, Tél. 516 577-2000
RF Exposure
Warning – The antenna(s) used for this device must be installed to provide a separation distance of at least 7.8 inches (20 cm) from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter except in accordance with FCC and
ISED multi-transmitter product procedures.
Mise en Garde
Exposition aux Fréquences Radio : La/les antenne(s) utilisée(s) pour cet émetteur doit/doivent être installée(s) à une distance de séparation d'au moins 20 cm (7,8 pouces) de toute personne et ne pas être située(s) ni fonctionner parallèlement à tout autre transmetteur ou antenne, excepté en conformité avec les procédures de produit multi transmetteur FCC et ISED.
IMPORTANT NOTE ABOUT EXTERNAL ANTENNAS
If an external cellular radio antenna is used, the antenna may be installed or replaced ONLY by a professional installer.
TO THE INSTALLER
LTE-IV : The external antenna gain shall not exceed 6.94 dBi for 700 MHz 6.00 dBi for 1700 MHz, and 9.01 dBi for 1900 MHz. Under no conditions may an antenna gain be used that would exceed the ERP and EIRP power limits as specified as specified in FCC Parts 22H,
24E and 27.
LTE-IA: The external antenna gain shall not exceed 6.63 dBi for 700 MHz and 850MHz, 6.00 dBi for 1700 MHz, and 8.51 dBi for 1900
MHz. Under no conditions may an antenna gain be used that would exceed the ERP and EIRP power limits as specified in FCC Parts
22H, 24E and 27.
LTE-IC: The external antenna gain shall not exceed 6.63 dBi for 700 MHz and 850MHz, 6.00 dBi for 1700 MHz, and 8.51 dBi for 1900
MHz. Under no conditions may an antenna gain be used that would exceed the ERP and EIRP power limits as specified in ISED RSS-
130, RSS-132, RSS-133 and RSS-139.
ULC
WARNING: RADIO FREQUENCY FROM TRANSMITTING DEVICES MAY IMPAIR INTENDED OPERATION OF THE CONTROL
UNIT. MAINTAIN A MINIMUM OF 30 CM BETWEEN TRANSMITTING DEVICES AND CONTROL UNIT.
AVERTISSEMENT: LES RADIOFRÉQUENCES ÉMISES PAR LES DISPOSITIFS DE TRANSMISSION PEUVENT NUIRE AU
FONCTIONNEMENT PRÉVU DU POSTE DE CONTRÔLE. MAINTENIR UNE DISTANCE D’AU MOINS 30 CM ENTRE LES
DISPOSITIFS DE TRANSMISSION ET LE POSTE DE CONTRÔLE.
The maintenance instructions shall detail all test and maintenance instruction codes and software necessary to provide test and inspection requirements of CAN/ULC-S536, Standard for the Inspection and Testing of Fire Alarm Systems.
SUPPORT, WARRANTY, & PATENT
INFORMATION
For the latest documentation and online support information, please go to: https://mywebtech.honeywellhome.com/
For the latest warranty information, please go to: www.honeywell.com/security/hsc/resources/wa.
For patent information, see www.honeywell.com/patents
MyWebTech Warranty Patents
Summary of Connections
INTERNAL
ANTENNA
STATUS LED
MESSAGE LED
FAULT LED
FACTORY
USE ONLY
CELLULAR
STATUS LED
7720P
PROGRAMMER
PORT
AC 1
AC 2
12V DC IN
GND
ECP INPUT
ECP OUTPUT
TB 1
1
2
3
4
5
9
10
11
6
7
8
1
BLACK RED
INTERNAL
ANTENNA
SIGNAL QUALITY /
MODE AND
STATUS LEDs
MOUNTING HOLE
(UNDER BATTERY)
BATTERY CLIP
MOUNTING HOLE
CONNECTOR
FOR USE WITH
DCID ONLY
BATTERY
SCREW
TAMPER
SWITCH
J1
BATTERY
CONNECTOR
RJ45
ETHERNET
PORT
(SUPERVISED)
NETWORK
CONNECTIVITY
LEDs
MODE SWITCH
NOTE: All circuits are supervised and all circuits are power limited except the battery.
Communicator TB1 Wiring
7
8
9
10
11
4
5
6
2
3
TB1 ECP Mode
1 AC 1
AC 2
ECP V+ (RED)
GND (BLK)
ECP IN (YEL)
ECP OUT (GRN)
NOT USED
NOT USED
Z6
Z7
FLT OUT
Zone Trigger Mode
AC 1
AC 2
NOT USED
GND (BLK)
Z1/Z2
Z3
Z4
Z5
Z6
Z7
FLT OUT
Ê800-244536Š
800-24453 9/18 Rev A
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
2018 Honeywell International Inc. www. honeywell.com/security